Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2024-07-03 12:20:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1552.93 | 311.70 | 311.70 |
Net Site Energy | 1552.93 | 311.70 | 311.70 |
Total Source Energy | 4918.12 | 987.14 | 987.14 |
Net Source Energy | 4918.12 | 987.14 | 987.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 114.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 292.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 67.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 48.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1552.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 114.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 292.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 67.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 48.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 114.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 292.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 67.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 48.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 311.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 104.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 311.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1552.928 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1552.928 | 100.00 |
Total On-Site and Utility Electric Sources | 1552.928 | 100.00 |
Total Electricity End Uses | 1552.928 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 132.17 |
Time Setpoint Not Met During Occupied Cooling | 159.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1762.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | - | 05-JAN-12:09 |
Heating | 192831.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 974.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4952.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1946.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 237229.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 192831.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8334.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 974.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4952.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 1946.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 362.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 925.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 736.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 213.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 152.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4918.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 72.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 987.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 72.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 42.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 30.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 987.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.55 | 0.293773 | 0.250000 | 0.637784 | 0.783394 | 0.500000 | 0.001297 |
CORE_MID VAV BOX COMPONENT | 2.04 | 0.367614 | 0.312000 | 0.636075 | 0.980303 | 0.500000 | 0.001036 |
CORE_TOP VAV BOX COMPONENT | 2.19 | 0.342347 | 0.291000 | 0.637048 | 0.912925 | 0.500000 | 0.001113 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.689999 | 0.228974 | 0.195000 | 0.134550 | 0.610597 | 0.500000 | 0.001664 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.670231 | 0.149235 | 0.127000 | 0.085119 | 0.397959 | 0.500000 | 0.002553 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.802968 | 0.196760 | 0.167000 | 0.134096 | 0.524692 | 0.500000 | 0.001936 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.741356 | 0.134909 | 0.115000 | 0.085256 | 0.359756 | 0.500000 | 0.002824 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.552220 | 0.286103 | 0.243000 | 0.134189 | 0.762941 | 0.500000 | 0.001332 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.573002 | 0.174557 | 0.148000 | 0.084804 | 0.465486 | 0.500000 | 0.002183 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.651526 | 0.242495 | 0.206000 | 0.134214 | 0.646653 | 0.500000 | 0.001571 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.594270 | 0.168299 | 0.143000 | 0.084981 | 0.448798 | 0.500000 | 0.002264 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.594862 | 0.265594 | 0.226000 | 0.134439 | 0.708250 | 0.500000 | 0.001435 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.644159 | 0.414066 | 0.500000 | 0.002454 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.707101 | 0.223436 | 0.190000 | 0.134349 | 0.595828 | 0.500000 | 0.001705 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.671144 | 0.149022 | 0.127000 | 0.085235 | 0.397392 | 0.500000 | 0.002557 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20537.30 |
CORE_MID VAV BOX REHEAT COIL | 20482.27 |
CORE_TOP VAV BOX REHEAT COIL | 35177.27 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16046.65 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10409.10 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15909.27 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10492.21 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12189.64 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7977.39 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12065.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8056.71 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 12584.22 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8205.96 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12455.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8281.80 |
PACU_VAV_BOT HEATING COIL | 18409.17 |
PACU_VAV_MID HEATING COIL | 19366.70 |
PACU_VAV_TOP HEATING COIL | 18591.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.46 | 1.08 | 4.92 | 1.68 | 4.45 | 4.45 | 0.300000 | 0.376905 | 4.45 |
PACU_VAV_MID | 2.33 | 1.08 | 4.66 | 1.90 | 4.08 | 4.08 | 0.300000 | 0.466630 | 4.08 |
PACU_VAV_TOP | 2.55 | 1.08 | 5.09 | 2.73 | 4.80 | 4.80 | 0.300000 | 0.569538 | 4.80 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.45 |
PACU_VAV_MID_OA_CONTROLLER | 4.08 |
PACU_VAV_TOP_OA_CONTROLLER | 4.80 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.45 | 98003.87 | 0.740118 | 1.48 | 32664.69 | 0.740118 |
PACU_VAV_MID COOLING COIL | 4.08 | 92078.84 | 0.731799 | 1.36 | 30689.88 | 0.731799 |
PACU_VAV_TOP COOLING COIL | 4.80 | 103530.70 | 0.748178 | 1.60 | 34506.78 | 0.748178 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.45 |
PACU_VAV_MID FAN | 4.08 |
PACU_VAV_TOP FAN | 4.80 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 11.90 | 7.70 | 4.00 | 7.90 | 13.80 | 17.20 | 20.80 | 24.80 | 26.10 | 26.50 | 22.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 | 33.63 | -84.43 | -5.00 | 308.00 | 97679 | 1.1610 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.60 | 22.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9876E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0268E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5034E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5358E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3121E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3378E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1007 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5921E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1122 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9771E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6206E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0413E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9904E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0437E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5066E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5545E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3151E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3510E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4493E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0494E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2883E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8840E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1659E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5527E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7894E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8053E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6401E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6517E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2824E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2868E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9303E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9681E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4705E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5013E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1767E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2002E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7223E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5417E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1120E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1824E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9625E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.3066E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9294E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9674E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4691E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4983E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1741E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1911E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8870E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3300E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3808E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0040E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7587E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9122E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7839E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8175E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4043E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4384E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4155E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4331E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1088 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6949E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1209 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.1608E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3084E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.9068E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2765E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9482E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1295E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7901E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0446E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4791E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1220E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0325E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4696E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6078E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3197E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2232E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7613E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2607E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2800E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9497E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6778E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8660E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1088 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6943E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1209 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.1601E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3079E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.9063E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2764E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9479E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1293E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7899E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0443E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4788E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1221E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0324E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4696E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6077E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3196E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2231E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7613E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2606E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2800E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9496E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6775E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8658E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34147.06023 | 34147.06023 | 2.55114 | 2.55114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 6693.11398 | 6693.11398 | 0.29144 | 0.42469 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27315.12564 | 27315.12564 | 2.03870 | 2.03870 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 27.37000 | 1.44605E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14017.15182 | 14017.15182 | 0.61513 | 0.61513 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29049.85167 | 29049.85167 | 2.18917 | 2.18917 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 34.02000 | 1.44726E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 24779.90628 | 24779.90628 | 1.09243 | 1.09243 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9155.93771 | 9155.93771 | 0.69000 | 0.69000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.11500 | 1.44727E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 11270.28953 | 11270.28953 | 0.49833 | 0.49833 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8893.66745 | 8893.66745 | 0.67023 | 0.67023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.26500 | 1.44675E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7310.33060 | 7310.33060 | 0.32325 | 0.32325 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10655.00355 | 10655.00355 | 0.80297 | 0.80297 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 11174.07733 | 11174.07733 | 0.49406 | 0.49406 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9837.47827 | 9837.47827 | 0.74136 | 0.74136 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.91167 | 1.44705E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7368.53526 | 7368.53526 | 0.32583 | 0.32583 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7327.77353 | 7327.77353 | 0.55222 | 0.55222 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8567.86215 | 8567.86215 | 0.37855 | 0.37855 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7603.60272 | 7603.60272 | 0.57300 | 0.57300 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.50250 | 1.44680E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5606.51686 | 5606.51686 | 0.24774 | 0.24774 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8645.55172 | 8645.55172 | 0.65153 | 0.65153 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8480.67417 | 8480.67417 | 0.37468 | 0.37468 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7885.82876 | 7885.82876 | 0.59427 | 0.59427 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.59500 | 1.44700E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5662.06017 | 5662.06017 | 0.25020 | 0.25020 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7893.54968 | 7893.54968 | 0.59486 | 0.59486 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.30500 | 1.44731E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8844.85024 | 8844.85024 | 0.39080 | 0.39080 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8547.75837 | 8547.75837 | 0.64416 | 0.64416 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 31.02750 | 1.44671E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5767.00794 | 5767.00794 | 0.25484 | 0.25484 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9382.93103 | 9382.93103 | 0.70710 | 0.70710 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40000 | 1.44733E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8754.68860 | 8754.68860 | 0.38680 | 0.38680 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 8905.84678 | 8905.84678 | 0.67114 | 0.67114 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.75333 | 1.44703E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5820.12046 | 5820.12046 | 0.25719 | 0.25719 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30000 | 2.29779E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 69548.22 | 4.44637 | 4.44637 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 21099.13 | 1.67586 | 1.67586 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64540.26 | 4.08196 | 4.08196 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 21042.03 | 1.90476 | 1.90476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73814.24 | 4.80021 | 4.80021 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 20984.74 | 2.73390 | 2.73390 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.55114 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29377 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63778 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78339 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29692E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20537.30422 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.03870 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36761 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63608 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98030 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03641E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 20482.26978 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.18917 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34235 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63705 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91292 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11291E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 35177.26774 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22897 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19500 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13455 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61060 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66395E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16046.64759 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67023 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14923 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51193E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39796 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55302E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10409.09862 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80297 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19676 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13410 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52469 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93637E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 15909.27491 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74136 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13491 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52559E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35976 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82413E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10492.20607 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55222 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28610 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13419 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76294 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33169E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12189.64017 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57300 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17456 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14800 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48043E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46549 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18266E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7977.39003 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65153 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24249 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13421 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64665 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57117E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12065.13886 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59427 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16830 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14300 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49807E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44880 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.26383E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8056.70686 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59486 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26559 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13444 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70825 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43452E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12584.22426 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64416 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41407 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45371E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8205.95606 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70710 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22344 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13435 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59583 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70519E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12455.47912 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67114 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14902 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52353E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39739 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55667E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8281.79919 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46108 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07597 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.92215 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.67586 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.44637 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.44637 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.37690 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.32798 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07513 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.65597 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.90476 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.08196 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.08196 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.46663 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.54686 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07607 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.09372 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.73390 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.80021 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.80021 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.56954 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.44637 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.08196 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.80021 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.44637 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.44637 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98003.86889 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74012 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.48198 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32664.68950 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74012 |
152 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 18409.16700 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.44637 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.08196 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.08196 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92078.84181 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73180 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.36052 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30689.87798 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73180 |
161 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 19366.69512 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.08196 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.80021 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.80021 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103530.70087 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74818 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59991 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34506.78260 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74818 |
170 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 18591.58984 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.80021 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 97457.34 | 332538.26 | 12.34 | 3.15 | 3.53 | 3.72 | 3.89 | 10.76 | 12.06 | 12.70 | 13.27 | 4.9583 | 3.9503 | 2.6595 | 1.1038 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 91639.28 | 312686.21 | 12.39 | 3.16 | 3.55 | 3.74 | 3.90 | 10.80 | 12.11 | 12.76 | 13.30 | 4.5519 | 3.6218 | 2.4374 | 1.0212 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 102873.63 | 351019.40 | 12.29 | 3.14 | 3.52 | 3.71 | 3.88 | 10.73 | 12.01 | 12.64 | 13.23 | 5.3528 | 4.2685 | 2.8746 | 1.1835 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.9654150739E-003 | 5.5549809222E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.3261322723E-002 | 2.9906719500E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8588546140E-003 | 4.1863616964E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.1276822434E-003 | 3.8015006788E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4773404050E-003 | 6.5794786937E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.4959612232E-002 | 1.1143588273E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.3614495067E-002 | 2.4187691278E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.4865674469E-002 | 2.5955271540E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.5382680917E-002 | 2.7775413398E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.5075199706E-002 | 2.4614006716E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2703846438E-002 | 2.0312548890E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.3583467546E-002 | 2.2070499037E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.4082673473E-002 | 2.2965863307E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.3606393534E-002 | 2.0735781370E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6282249867E-002 | 2.2309110437E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.7541177191E-002 | 2.4298747236E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.8019663975E-002 | 2.5627789332E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.7688608785E-002 | 2.2777930365E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2916.53 | 26.24 | 0.00 | 1090.34 | 1542.89 | 5576.01 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 90.00 | 25 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.07 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.76 | 0.0000 | Y | 4.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.59 | 0.0000 | Y | 6.64 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 4.25 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 4.27 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.55 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.77 | 41.77 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.77 | 62.77 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.77 | 47.60 | 42.13 | |
Exterior Lighting Total | 5686.19 | 51.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98003.87 | 72534.41 | 25469.45 | 0.74 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92078.84 | 67383.23 | 24695.62 | 0.73 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103530.70 | 77459.41 | 26071.30 | 0.75 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 97457.3 | 3.15 | 10.76 | N/A | N/A | 12.34 | |
PACU_VAV_MID COOLING COIL | 91639.3 | 3.16 | 10.80 | N/A | N/A | 12.39 | |
PACU_VAV_TOP COOLING COIL | 102873.6 | 3.14 | 10.73 | N/A | N/A | 12.29 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 20537.30 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 20482.27 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 35177.27 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16046.65 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10409.10 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 15909.27 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10492.21 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12189.64 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7977.39 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12065.14 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8056.71 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12584.22 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8205.96 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12455.48 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8281.80 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 18409.17 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 19366.70 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 18591.59 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.45 | 9733.16 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.08 | 8935.45 | 2189.01 | 1.00 | 1.15 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.80 | 10507.72 | 2189.01 | 1.00 | 1.14 | General | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97457.34 | 3.15 | 10.76 | 12.34 | 4.9583 | 3.53 | 12.06 | 3.9503 | 3.72 | 12.70 | 2.6595 | 3.89 | 13.27 | 1.1038 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91639.28 | 3.16 | 10.80 | 12.39 | 4.5519 | 3.55 | 12.11 | 3.6218 | 3.74 | 12.76 | 2.4374 | 3.90 | 13.30 | 1.0212 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102873.63 | 3.14 | 10.73 | 12.29 | 5.3528 | 3.52 | 12.01 | 4.2685 | 3.71 | 12.64 | 2.8746 | 3.88 | 13.23 | 1.1835 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34147.06 | 34147.06 | 34.72 | 2.551 | 2.551 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_MID | 27315.13 | 27315.13 | 27.77 | 2.039 | 2.039 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 27.37 | 0.01446 | 0.425 | 0.00 |
CORE_TOP | 29049.85 | 29049.85 | 29.54 | 2.189 | 2.189 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00891 | 34.02 | 0.01447 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9155.94 | 9155.94 | 44.16 | 0.690 | 0.690 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00888 | 34.12 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8893.67 | 8893.67 | 67.75 | 0.670 | 0.670 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 24.00 | 24.00 | 0.00875 | 31.26 | 0.01447 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10655.00 | 10655.00 | 51.39 | 0.803 | 0.803 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00883 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9837.48 | 9837.48 | 74.95 | 0.741 | 0.741 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00873 | 32.91 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7327.77 | 7327.77 | 35.34 | 0.552 | 0.552 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7603.60 | 7603.60 | 57.93 | 0.573 | 0.573 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.00 | 24.00 | 0.00876 | 31.50 | 0.01447 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8645.55 | 8645.55 | 41.70 | 0.652 | 0.652 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7885.83 | 7885.83 | 60.08 | 0.594 | 0.594 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00875 | 32.59 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7893.55 | 7893.55 | 38.07 | 0.595 | 0.595 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00892 | 34.30 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8547.76 | 8547.76 | 65.12 | 0.644 | 0.644 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00875 | 31.03 | 0.01447 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9382.93 | 9382.93 | 45.25 | 0.707 | 0.707 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00885 | 34.40 | 0.01447 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8905.85 | 8905.85 | 67.85 | 0.671 | 0.671 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 32.75 | 0.01447 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 6693.11 | 6693.11 | 6.81 | 0.291 | 0.425 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_MID | 14017.15 | 14017.15 | 14.25 | 0.615 | 0.615 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
CORE_TOP | 24779.91 | 24779.91 | 25.19 | 1.092 | 1.092 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -6.30 | 0.00230 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 11270.29 | 11270.29 | 54.36 | 0.498 | 0.498 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7310.33 | 7310.33 | 55.69 | 0.323 | 0.323 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11174.08 | 11174.08 | 53.89 | 0.494 | 0.494 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7368.54 | 7368.54 | 56.14 | 0.326 | 0.326 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8567.86 | 8567.86 | 41.32 | 0.379 | 0.379 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5606.52 | 5606.52 | 42.71 | 0.248 | 0.248 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8480.67 | 8480.67 | 40.90 | 0.375 | 0.375 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 5662.06 | 5662.06 | 43.14 | 0.250 | 0.250 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8844.85 | 8844.85 | 42.66 | 0.391 | 0.391 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5767.01 | 5767.01 | 43.94 | 0.255 | 0.255 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8754.69 | 8754.69 | 42.22 | 0.387 | 0.387 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -6.30 | 0.00230 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5820.12 | 5820.12 | 44.34 | 0.257 | 0.257 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -6.30 | 0.00230 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.45 | 4.45 | 1.68 | 1.68 | 4.4464 | 1.6759 | 4.4464 | 0.3769 | 0.3000 |
PACU_VAV_MID | 4.08 | 4.08 | 1.90 | 1.90 | 4.0820 | 1.9048 | 4.0820 | 0.4666 | 0.3000 |
PACU_VAV_TOP | 4.80 | 4.80 | 2.73 | 2.73 | 4.8002 | 2.7339 | 4.8002 | 0.5695 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20537.304 | 20537.304 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20537.30 | 13675.49 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 6693.11 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 20482.270 | 20482.270 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20482.27 | 19807.89 | 0.615132 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 14017.15 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 35177.268 | 35177.268 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35177.27 | 35177.27 | 1.092427 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00800000 | 49.8624 | 24779.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16046.648 | 16046.648 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16046.65 | 16046.65 | 0.498327 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775921 | 48.3835 | 11270.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10409.099 | 10409.099 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10409.10 | 10409.10 | 0.323254 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775423 | 48.3529 | 7310.33 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 15909.275 | 15909.275 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15909.27 | 15909.27 | 0.494061 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775665 | 48.3677 | 11174.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10492.206 | 10492.206 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10492.21 | 10492.21 | 0.325835 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775659 | 48.3674 | 7368.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 12189.640 | 12189.640 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12189.64 | 12189.64 | 0.378548 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00774955 | 48.3237 | 8567.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7977.390 | 7977.390 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7977.39 | 7977.39 | 0.247737 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00775705 | 48.3699 | 5606.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12065.139 | 12065.139 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12065.14 | 12065.14 | 0.374682 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00774271 | 48.2816 | 8480.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8056.707 | 8056.707 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8056.71 | 8056.71 | 0.250200 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00776354 | 48.4097 | 5662.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 12584.224 | 12584.224 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12584.22 | 12584.22 | 0.390802 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00769671 | 47.9988 | 8844.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8205.956 | 8205.956 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8205.96 | 8205.96 | 0.254835 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00769853 | 48.0100 | 5767.01 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 12455.479 | 12455.479 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12455.48 | 12455.48 | 0.386804 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00769012 | 47.9582 | 8754.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8281.799 | 8281.799 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8281.80 | 8281.80 | 0.257191 | 12.80 | 11.27 | 0.00800000 | 40.00 | 20.76 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 0.0000 | 21.00 | 0.00770389 | 48.0430 | 5820.12 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 98003.869 | 72534.414 | 4.446372 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 98003.84 | 77795.14 | 4.446372 | 26.24 | 18.07 | 0.01007986 | 10.96 | 10.96 | 0.00850000 | 34.40 | 0.01447326 | 23.54 | 21.5029 | 24.00 | 0.00887256 | 46.0252 | 58856.66 | 0.00 | 101055.14 | 72495.14 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 18409.167 | 18409.167 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18409.17 | 18409.17 | 1.333912 | 0.97 | 0.37 | 0.00378094 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 71.6764 | 19.63 | 0.00748755 | 50.8195 | 14377.80 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 92078.842 | 67383.226 | 4.081959 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 92523.20 | 72214.24 | 4.081959 | 26.43 | 18.25 | 0.01023096 | 10.96 | 10.96 | 0.00850000 | 34.30 | 0.01447309 | 23.52 | 23.4226 | 24.00 | 0.00892434 | 46.2902 | 53877.58 | 0.00 | 94945.65 | 67367.94 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 19366.695 | 19366.695 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19366.70 | 19366.70 | 1.224588 | -0.76 | -1.11 | 0.00344167 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 78.0753 | 19.41 | 0.00728046 | 50.1197 | 17431.76 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 103530.701 | 77459.406 | 4.800213 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 103414.01 | 82845.18 | 4.800213 | 26.02 | 17.92 | 0.00998823 | 10.96 | 10.96 | 0.00850000 | 34.12 | 0.01447274 | 23.47 | 19.9179 | 24.00 | 0.00886880 | 46.0061 | 63512.46 | 0.00 | 106754.05 | 77354.56 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 18591.590 | 18591.590 | -999.0 | -999.0 | -999.000 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18591.59 | 18591.59 | 1.440064 | 1.73 | 1.22 | 0.00406899 | 12.80 | 11.27 | 0.00800000 | -6.30 | 0.00229779 | -6.30 | 66.3929 | 17.66 | 0.00740220 | 56.8686 | 20171.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 20537.304 | 20537.304 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20537.30 | 13675.49 | 1.0000 | 0.49305639 | 0.424691 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20537.30 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 6693.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 20482.270 | 20482.270 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20482.27 | 19807.89 | 1.0000 | 0.71415408 | 0.615132 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20482.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 14017.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 35177.268 | 35177.268 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35177.27 | 35177.27 | 1.0000 | 1.26828203 | 1.092427 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35177.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.8624 | 24779.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16046.648 | 16046.648 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16046.65 | 16046.65 | 1.0000 | 0.57854621 | 0.498327 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16046.65 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775921 | 21.00 | 0.00775921 | 48.3835 | 11270.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10409.099 | 10409.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10409.10 | 10409.10 | 1.0000 | 0.37528989 | 0.323254 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10409.10 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775423 | 21.00 | 0.00775423 | 48.3529 | 7310.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 15909.275 | 15909.275 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15909.27 | 15909.27 | 1.0000 | 0.57359337 | 0.494061 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15909.27 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775665 | 21.00 | 0.00775665 | 48.3677 | 11174.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10492.206 | 10492.206 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10492.21 | 10492.21 | 1.0000 | 0.37828624 | 0.325835 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10492.21 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775659 | 21.00 | 0.00775659 | 48.3674 | 7368.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12189.640 | 12189.640 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12189.64 | 12189.64 | 1.0000 | 0.43948557 | 0.378548 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12189.64 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00774955 | 21.00 | 0.00774955 | 48.3237 | 8567.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7977.390 | 7977.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7977.39 | 7977.39 | 1.0000 | 0.28761701 | 0.247737 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7977.39 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775705 | 21.00 | 0.00775705 | 48.3699 | 5606.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12065.139 | 12065.139 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12065.14 | 12065.14 | 1.0000 | 0.43499680 | 0.374682 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12065.14 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00774271 | 21.00 | 0.00774271 | 48.2816 | 8480.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8056.707 | 8056.707 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8056.71 | 8056.71 | 1.0000 | 0.29047670 | 0.250200 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8056.71 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00776354 | 21.00 | 0.00776354 | 48.4097 | 5662.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12584.224 | 12584.224 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12584.22 | 12584.22 | 1.0000 | 0.45371192 | 0.390802 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12584.22 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00769671 | 21.00 | 0.00769671 | 47.9988 | 8844.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8205.956 | 8205.956 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8205.96 | 8205.96 | 1.0000 | 0.29585773 | 0.254835 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8205.96 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00769853 | 21.00 | 0.00769853 | 48.0100 | 5767.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12455.479 | 12455.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12455.48 | 12455.48 | 1.0000 | 0.44907014 | 0.386804 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12455.48 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00769012 | 21.00 | 0.00769012 | 47.9582 | 8754.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8281.799 | 8281.799 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8281.80 | 8281.80 | 1.0000 | 0.29859218 | 0.257191 | 12.80 | 11.27 | 0.00800000 | 33059.8 | 40.00 | 20.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8281.80 | -6.30 | 0.00229779 | -6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00770389 | 21.00 | 0.00770389 | 48.0430 | 5820.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98003.869 | 72534.414 | 4.446372 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5780 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.446372 | 5.16213338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 98003.84 | 77795.14 | 1.0000 | 5.16213338 | 4.446372 | 26.24 | 18.07 | 0.01007986 | 52068.6 | 10.96 | 10.96 | 0.00850000 | 32442.1 | -999.0 | -999.00 | -999.00 | -999.00 | 9733.157 | 88270.69 | 34.40 | 0.01447326 | 23.54 | 0.95610000 | 21.5029 | 24.00 | 0.00887256 | 24.00 | 0.00887256 | 46.0252 | 58856.66 | 0.00 | 101055.14 | 72495.14 | 4.95826814 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.35 | 12.34 | 0.00892626 | 34941.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18409.167 | 18409.167 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.446372 | 5.16213338 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18409.17 | 18409.17 | 1.0000 | 1.54864001 | 1.333912 | 0.97 | 0.37 | 0.00378094 | 10437.6 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18409.17 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 71.6764 | 19.37 | 0.00753422 | 19.63 | 0.00748755 | 50.8195 | 14377.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92078.842 | 67383.226 | 4.081959 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8588 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.081959 | 4.73905845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 92523.20 | 72214.24 | 1.0048 | 4.73905845 | 4.081959 | 26.43 | 18.25 | 0.01023096 | 52643.0 | 10.96 | 10.96 | 0.00850000 | 32442.6 | -999.0 | -999.00 | -999.00 | -999.00 | 8935.453 | 83587.74 | 34.30 | 0.01447309 | 23.52 | 0.95610000 | 23.4226 | 24.00 | 0.00892434 | 24.00 | 0.00892434 | 46.2902 | 53877.58 | 0.00 | 94945.65 | 67367.94 | 4.55190146 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.17 | 12.15 | 0.00880926 | 34463.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19366.695 | 19366.695 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.081959 | 4.73905845 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19366.70 | 19366.70 | 1.0000 | 1.42171753 | 1.224588 | -0.76 | -1.11 | 0.00344167 | 7842.7 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19366.70 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 78.0753 | 18.99 | 0.00751506 | 19.41 | 0.00728046 | 50.1197 | 17431.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103530.701 | 77459.406 | 4.800213 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4076 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.800213 | 5.57293523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | Sensible | 103414.01 | 82845.18 | 0.9989 | 5.57293523 | 4.800213 | 26.02 | 17.92 | 0.00998823 | 51608.4 | 10.96 | 10.96 | 0.00850000 | 32441.8 | -999.0 | -999.00 | -999.00 | -999.00 | 10507.720 | 92906.29 | 34.12 | 0.01447274 | 23.47 | 0.95610000 | 19.9179 | 24.00 | 0.00886880 | 24.00 | 0.00886880 | 46.0061 | 63512.46 | 0.00 | 106754.05 | 77354.56 | 5.35284642 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.52 | 12.51 | 0.00903125 | 35379.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18591.590 | 18591.590 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1610 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.800213 | 5.57293523 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18591.59 | 18591.59 | 1.0000 | 1.67188057 | 1.440064 | 1.73 | 1.22 | 0.00406899 | 11931.4 | 12.80 | 11.27 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18591.59 | -6.30 | 0.00229779 | -6.30 | 0.95610000 | 66.3929 | 17.60 | 0.00756808 | 17.66 | 0.00740220 | 56.8686 | 20171.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.45 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.08 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3048.67 | 1675.83 | 14.83 |
CORE_MID | 2482.83 | 2822.33 | 249.83 |
CORE_TOP | 2776.67 | 3171.50 | 680.33 |
PERIMETER_TOP_ZN_3 | 3412.83 | 3377.67 | 1314.33 |
PERIMETER_TOP_ZN_2 | 3486.17 | 3100.33 | 1177.83 |
PERIMETER_TOP_ZN_1 | 3269.00 | 2850.50 | 900.00 |
PERIMETER_TOP_ZN_4 | 3476.67 | 3152.50 | 1204.17 |
PERIMETER_BOT_ZN_3 | 3009.67 | 3426.50 | 937.33 |
PERIMETER_BOT_ZN_2 | 3166.00 | 2964.33 | 731.17 |
PERIMETER_BOT_ZN_1 | 3006.00 | 3115.50 | 777.67 |
PERIMETER_BOT_ZN_4 | 3155.83 | 2988.33 | 750.50 |
PERIMETER_MID_ZN_3 | 3208.50 | 3184.17 | 962.50 |
PERIMETER_MID_ZN_2 | 2802.00 | 2535.83 | 796.83 |
PERIMETER_MID_ZN_1 | 3164.83 | 2565.50 | 587.00 |
PERIMETER_MID_ZN_4 | 3334.50 | 2945.83 | 865.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4647.17 | 4072.83 | 1762.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.00 | 0.00 | 0.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 19.00 | 6.00 | 9.83 | 4.17 |
PERIMETER_TOP_ZN_2 | 12.83 | 38.00 | 2.67 | 34.00 |
PERIMETER_TOP_ZN_1 | 8.83 | 29.17 | 2.83 | 26.50 |
PERIMETER_TOP_ZN_4 | 11.83 | 40.33 | 3.17 | 22.33 |
PERIMETER_BOT_ZN_3 | 1.33 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.33 | 18.17 | 0.00 | 18.17 |
PERIMETER_BOT_ZN_1 | 124.50 | 65.83 | 124.50 | 65.83 |
PERIMETER_BOT_ZN_4 | 0.33 | 24.17 | 0.00 | 13.50 |
PERIMETER_MID_ZN_3 | 2.50 | 1.33 | 1.83 | 1.17 |
PERIMETER_MID_ZN_2 | 0.83 | 30.50 | 0.33 | 29.83 |
PERIMETER_MID_ZN_1 | 0.83 | 20.00 | 0.33 | 19.83 |
PERIMETER_MID_ZN_4 | 0.83 | 32.67 | 0.33 | 19.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 143.33 | 189.00 | 132.17 | 159.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.686 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.527 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.519 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.591 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.745 | 0.040 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.757 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.746 | 0.040 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.520 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.659 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.671 | 0.817 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.641 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.588 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.684 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.771 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.743 | 0.033 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.05 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 10799014.36 | 0.00 | 10799014.36 | 0.00 | 10799014.36 | 13393058.27 | 5182.36 | 132.47 | 3445.18 | 4.46 |
CORE_MID | 8325935.45 | 0.00 | 8325935.45 | 0.00 | 8325935.45 | 13393058.27 | 5879.76 | 354.21 | 2526.03 | 14.60 |
CORE_TOP | 8219137.37 | 0.00 | 8219137.37 | 0.00 | 8219137.37 | 13393058.27 | 5898.11 | 414.44 | 2447.45 | 70.33 |
PERIMETER_TOP_ZN_3 | 1974563.55 | 0.00 | 1974563.55 | 253748.86 | 2228312.41 | 2823374.22 | 4452.46 | 309.29 | 3998.25 | 70.33 |
PERIMETER_TOP_ZN_2 | 1571568.34 | 0.00 | 1571568.34 | 169164.89 | 1740733.22 | 1787429.43 | 4343.06 | 300.19 | 4116.75 | 70.33 |
PERIMETER_TOP_ZN_1 | 2522504.02 | 0.00 | 2522504.02 | 253748.86 | 2776252.88 | 2823374.22 | 4445.12 | 426.05 | 3888.83 | 70.33 |
PERIMETER_TOP_ZN_4 | 1573460.25 | 0.00 | 1573460.25 | 169164.89 | 1742625.14 | 1787312.18 | 4401.98 | 255.97 | 4102.05 | 70.33 |
PERIMETER_BOT_ZN_3 | 1733406.74 | 0.00 | 1733406.74 | 134917.23 | 1868323.97 | 2823374.22 | 5868.00 | 228.11 | 2663.90 | 4.46 |
PERIMETER_BOT_ZN_2 | 1386621.48 | 0.00 | 1386621.48 | 89944.28 | 1476565.76 | 1787429.43 | 4770.64 | 206.82 | 3782.55 | 4.46 |
PERIMETER_BOT_ZN_1 | 2233833.77 | 0.00 | 2233833.77 | 2786735.31 | 5020569.08 | 2823374.22 | 4998.04 | 157.91 | 3604.05 | 4.46 |
PERIMETER_BOT_ZN_4 | 1349085.64 | 0.00 | 1349085.64 | 89944.28 | 1439029.92 | 1787312.18 | 4949.31 | 210.93 | 3599.76 | 4.46 |
PERIMETER_MID_ZN_3 | 1958137.38 | 0.00 | 1958137.38 | 211226.68 | 2169364.06 | 2823374.22 | 4479.51 | 259.54 | 4020.94 | 14.60 |
PERIMETER_MID_ZN_2 | 1444842.23 | 0.00 | 1444842.23 | 140816.94 | 1585659.17 | 1601953.02 | 4311.03 | 185.86 | 4263.11 | 923.60 |
PERIMETER_MID_ZN_1 | 2563813.42 | 0.00 | 2563813.42 | 211226.68 | 2775040.10 | 2823374.22 | 4390.47 | 235.22 | 4134.31 | 14.60 |
PERIMETER_MID_ZN_4 | 1564918.77 | 0.00 | 1564918.77 | 140816.94 | 1705735.71 | 1787312.18 | 4403.43 | 160.64 | 4195.92 | 14.60 |
Total Facility | 49220842.77 | 0.00 | 49220842.77 | 4651455.83 | 53872298.60 | 67658168.57 | 6467.83 | 1001.36 | 4504.40 | 981.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5045 | 0.0000 | 0.5045 | 0.0000 | 0.5045 | 0.4247 | 2367.36 | 132.47 | 3443.18 |
CORE_MID | 0.3883 | 0.0000 | 0.3883 | 0.0000 | 0.3883 | 0.4247 | 3068.79 | 354.21 | 2520.00 |
CORE_TOP | 0.3826 | 0.0000 | 0.3826 | 0.0000 | 0.3826 | 0.4247 | 3088.11 | 414.44 | 2440.45 |
PERIMETER_TOP_ZN_3 | 0.0919 | 0.0000 | 0.0919 | 0.0059 | 0.0978 | 0.0895 | 1642.46 | 309.29 | 3991.25 |
PERIMETER_TOP_ZN_2 | 0.0732 | 0.0000 | 0.0732 | 0.0039 | 0.0771 | 0.0567 | 1533.25 | 300.19 | 4109.56 |
PERIMETER_TOP_ZN_1 | 0.1175 | 0.0000 | 0.1175 | 0.0059 | 0.1234 | 0.0895 | 1635.15 | 426.05 | 3881.80 |
PERIMETER_TOP_ZN_4 | 0.0733 | 0.0000 | 0.0733 | 0.0039 | 0.0772 | 0.0567 | 1592.21 | 255.97 | 4094.83 |
PERIMETER_BOT_ZN_3 | 0.0810 | 0.0000 | 0.0810 | 0.0031 | 0.0841 | 0.0895 | 3053.00 | 228.11 | 2661.90 |
PERIMETER_BOT_ZN_2 | 0.0648 | 0.0000 | 0.0648 | 0.0021 | 0.0669 | 0.0567 | 1955.78 | 206.78 | 3780.44 |
PERIMETER_BOT_ZN_1 | 0.1043 | 0.0000 | 0.1043 | 0.1271 | 0.2314 | 0.0895 | 2183.06 | 157.91 | 3602.03 |
PERIMETER_BOT_ZN_4 | 0.0630 | 0.0000 | 0.0630 | 0.0021 | 0.0651 | 0.0567 | 2134.42 | 210.93 | 3597.65 |
PERIMETER_MID_ZN_3 | 0.0913 | 0.0000 | 0.0913 | 0.0049 | 0.0962 | 0.0895 | 1668.61 | 259.54 | 4014.85 |
PERIMETER_MID_ZN_2 | 0.0672 | 0.0000 | 0.0672 | 0.0035 | 0.0707 | 0.0567 | 1500.35 | 185.86 | 3347.79 |
PERIMETER_MID_ZN_1 | 0.1196 | 0.0000 | 0.1196 | 0.0049 | 0.1245 | 0.0895 | 1579.52 | 235.22 | 4128.26 |
PERIMETER_MID_ZN_4 | 0.0730 | 0.0000 | 0.0730 | 0.0033 | 0.0763 | 0.0567 | 1592.75 | 160.64 | 4189.60 |
Total Facility | 2.2955 | 0.0000 | 2.2955 | 0.1705 | 2.4660 | 2.1513 | 3652.16 | 1001.32 | 4495.53 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23590282.67 | 0.00 | 23590282.67 | 22614548.33 | 4233.28 | 2.09 | 4524.64 | 4.46 |
PACU_VAV_MID | 21373990.18 | 0.00 | 21373990.18 | 22429071.92 | 4220.11 | 1.98 | 4537.91 | 14.60 |
PACU_VAV_TOP | 21378720.08 | 0.00 | 21378720.08 | 22614548.33 | 4255.68 | 2.31 | 4502.00 | 70.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1019 | 0.0000 | 1.1019 | 0.7171 | 1418.30 | 2.09 | 4522.61 |
PACU_VAV_MID | 0.9969 | 0.0000 | 0.9969 | 0.7084 | 1409.16 | 1.98 | 4531.87 |
PACU_VAV_TOP | 0.9954 | 0.0000 | 0.9954 | 0.7171 | 1445.68 | 2.31 | 4495.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 205.98 | 2143.16 | 0.00 | 0.00 | 0.00 | 2221.23 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 105.99 | 2070.55 | 0.00 | 0.00 | 0.00 | 2419.48 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 70.44 | 2097.32 | 0.00 | 0.00 | 0.00 | 2489.89 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2396 | 1.8447 | 0.0000 | 0.0000 | 0.0000 | 1.0584 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1938 | 1.5942 | 0.0000 | 0.0000 | 0.0000 | 1.0425 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1894 | 1.5895 | 0.0000 | 0.0000 | 0.0000 | 1.0489 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2220 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
Electricity:Building | 952.24 | 13383.13 | 23-APR-17:20 | 66677.71 | 30-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 952.24 | 13383.13 | 23-APR-17:20 | 66677.71 | 30-OCT-07:10 |
InteriorLights:Electricity | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.55 | 905.38 | 23-APR-17:20 | 24978.45 | 30-OCT-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2473.26 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.64 | 261.88 | 23-APR-17:10 | 1565.70 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.98 | 413.67 | 12-MAR-17:10 | 2473.25 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.67 | 261.87 | 26-FEB-18:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.09 | 413.68 | 12-MAR-17:10 | 2473.16 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:50 | 1037.91 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:50 | 1037.91 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.63 | 261.88 | 23-APR-17:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:00 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.23 | 17.46 | 01-JAN-09:00 | 657.08 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.97 | 413.67 | 12-MAR-17:10 | 2473.15 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1037.91 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.64 | 27.57 | 01-JAN-09:10 | 1037.91 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.66 | 261.87 | 20-FEB-18:10 | 1565.60 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.25 | 17.46 | 01-JAN-10:40 | 657.03 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.25 | 17.46 | 01-JAN-10:40 | 657.03 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2473.26 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-11:00 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.64 | 261.88 | 23-APR-17:10 | 1565.70 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.24 | 17.46 | 01-JAN-09:10 | 657.13 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.98 | 413.67 | 12-MAR-17:10 | 2473.25 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.65 | 27.57 | 01-JAN-09:10 | 1038.01 | 30-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.67 | 261.87 | 26-FEB-18:10 | 1565.65 | 30-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:50 | 657.08 | 30-OCT-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 501.04 | 367.92 | 01-JAN-00:10 | 198758.81 | 13-FEB-07:10 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
ElectricityPurchased:Plant | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
Cogeneration:ElectricityPurchased | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
ElectricityNet:Plant | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
Cogeneration:ElectricityNet | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
General:Cogeneration:ElectricityNet | 1552.93 | 13760.90 | 07-MAY-17:30 | 237229.50 | 13-FEB-07:10 |
Heating:Electricity | 114.48 | 0.00 | 01-JAN-00:10 | 192831.40 | 13-FEB-07:10 |
General:Heating:Electricity | 114.48 | 0.00 | 01-JAN-00:10 | 192831.40 | 13-FEB-07:10 |
Fans:Electricity | 67.51 | 0.00 | 01-JAN-00:10 | 14740.47 | 02-AUG-15:50 |
General:Fans:Electricity | 67.51 | 0.00 | 01-JAN-00:10 | 14740.47 | 02-AUG-15:50 |
ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.35 | 0.00 | 01-JAN-07:50 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 292.17 | 0.00 | 01-JAN-00:10 | 69402.51 | 07-JUL-16:00 |
General:Cooling:Electricity | 292.17 | 0.00 | 01-JAN-00:10 | 69402.51 | 07-JUL-16:00 |
Electricity:Plant | 48.29 | 0.00 | 01-JAN-00:10 | 6221.07 | 31-JAN-12:40 |
WaterSystems:Electricity | 48.14 | 0.00 | 01-JAN-00:10 | 6214.22 | 31-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 48.14 | 0.00 | 01-JAN-00:10 | 6214.22 | 31-JAN-12:40 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-18:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-18:10 |
WIRED_LTG_ELECTRICITY | 6.53 | 0.00 | 01-JAN-00:10 | 701.89 | 30-OCT-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2575.35 | 0.00 | 01-JAN-00:10 | 405428.55 | 07-JUL-16:00 |
EnergyTransfer:Building | 1164.78 | 0.00 | 01-JAN-00:10 | 155506.78 | 02-AUG-15:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 240.16 | 0.00 | 01-JAN-00:10 | 24722.12 | 05-SEP-07:40 |
Heating:EnergyTransfer | 58.23 | 0.00 | 01-JAN-00:10 | 137878.49 | 09-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1349.87 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 58.23 | 0.00 | 01-JAN-00:10 | 137878.49 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 1349.87 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 1106.55 | 0.00 | 01-JAN-00:10 | 155506.78 | 02-AUG-15:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 240.16 | 0.00 | 01-JAN-00:10 | 24722.12 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer | 1106.55 | 0.00 | 01-JAN-00:10 | 155506.78 | 02-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 240.16 | 0.00 | 01-JAN-00:10 | 24722.12 | 05-SEP-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 44.57 | 0.00 | 01-JAN-00:10 | 12080.78 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 10.44 | 0.00 | 01-JAN-00:10 | 12080.78 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 10.44 | 0.00 | 01-JAN-00:10 | 12080.78 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.13 | 0.00 | 01-JAN-00:10 | 10219.41 | 01-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.13 | 0.00 | 01-JAN-00:10 | 10219.41 | 01-AUG-14:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.75 | 0.00 | 01-JAN-00:10 | 6713.76 | 09-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.15 | 0.00 | 01-JAN-00:10 | 6713.76 | 09-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.15 | 0.00 | 01-JAN-00:10 | 6713.76 | 09-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.60 | 0.00 | 01-JAN-00:10 | 4370.63 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.60 | 0.00 | 01-JAN-00:10 | 4370.63 | 10-JUL-15:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.24 | 0.00 | 01-JAN-00:10 | 4669.52 | 10-JUL-15:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.72 | 0.00 | 01-JAN-00:10 | 3255.68 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 2.72 | 0.00 | 01-JAN-00:10 | 3255.68 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.52 | 0.00 | 01-JAN-00:10 | 4669.52 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.52 | 0.00 | 01-JAN-00:10 | 4669.52 | 10-JUL-15:30 |
EnergyTransfer:Zone:CORE_MID | 169.37 | 0.00 | 01-JAN-00:10 | 18625.36 | 21-AUG-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.35 | 0.00 | 01-JAN-00:10 | 13161.30 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.35 | 0.00 | 01-JAN-00:10 | 13161.30 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 169.02 | 0.00 | 01-JAN-00:10 | 18625.36 | 21-AUG-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 169.02 | 0.00 | 01-JAN-00:10 | 18625.36 | 21-AUG-07:30 |
EnergyTransfer:Zone:CORE_TOP | 165.59 | 0.00 | 01-JAN-00:10 | 26495.83 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.17 | 0.00 | 01-JAN-00:10 | 26495.83 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.17 | 0.00 | 01-JAN-00:10 | 26495.83 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 162.42 | 0.00 | 01-JAN-00:10 | 20048.31 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 162.42 | 0.00 | 01-JAN-00:10 | 20048.31 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.13 | 0.00 | 01-JAN-00:10 | 8838.69 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.62 | 0.00 | 01-JAN-00:10 | 8838.69 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.62 | 0.00 | 01-JAN-00:10 | 8838.69 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.51 | 0.00 | 01-JAN-00:10 | 7123.85 | 14-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.51 | 0.00 | 01-JAN-00:10 | 7123.85 | 14-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.22 | 0.00 | 01-JAN-00:10 | 8081.49 | 07-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.32 | 0.00 | 01-JAN-00:10 | 7486.28 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.32 | 0.00 | 01-JAN-00:10 | 7486.28 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.90 | 0.00 | 01-JAN-00:10 | 8081.49 | 07-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.90 | 0.00 | 01-JAN-00:10 | 8081.49 | 07-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 56.01 | 0.00 | 01-JAN-00:10 | 10786.23 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.99 | 0.00 | 01-JAN-00:10 | 9808.36 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 3.99 | 0.00 | 01-JAN-00:10 | 9808.36 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 52.01 | 0.00 | 01-JAN-00:10 | 10786.23 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 52.01 | 0.00 | 01-JAN-00:10 | 10786.23 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.01 | 0.00 | 01-JAN-00:10 | 8139.67 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.84 | 0.00 | 01-JAN-00:10 | 7294.84 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.84 | 0.00 | 01-JAN-00:10 | 7294.84 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.18 | 0.00 | 01-JAN-00:10 | 8139.67 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.18 | 0.00 | 01-JAN-00:10 | 8139.67 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.88 | 0.00 | 01-JAN-00:10 | 6686.65 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.53 | 0.00 | 01-JAN-00:10 | 6686.65 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.53 | 0.00 | 01-JAN-00:10 | 6686.65 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.35 | 0.00 | 01-JAN-00:10 | 5882.27 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 35.35 | 0.00 | 01-JAN-00:10 | 5882.27 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.92 | 0.00 | 01-JAN-00:10 | 6741.86 | 07-AUG-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.13 | 0.00 | 01-JAN-00:10 | 4694.89 | 13-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.13 | 0.00 | 01-JAN-00:10 | 4694.89 | 13-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.78 | 0.00 | 01-JAN-00:10 | 6741.86 | 07-AUG-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.78 | 0.00 | 01-JAN-00:10 | 6741.86 | 07-AUG-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 54.98 | 0.00 | 01-JAN-00:10 | 10052.71 | 18-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.80 | 0.00 | 01-JAN-00:10 | 10013.74 | 03-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 7.80 | 0.00 | 01-JAN-00:10 | 10013.74 | 03-FEB-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.18 | 0.00 | 01-JAN-00:10 | 10052.71 | 18-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.18 | 0.00 | 01-JAN-00:10 | 10052.71 | 18-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.72 | 0.00 | 01-JAN-00:10 | 6650.37 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.22 | 0.00 | 01-JAN-00:10 | 4721.80 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.22 | 0.00 | 01-JAN-00:10 | 4721.80 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.50 | 0.00 | 01-JAN-00:10 | 6650.37 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.50 | 0.00 | 01-JAN-00:10 | 6650.37 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 41.69 | 0.00 | 01-JAN-00:10 | 7284.94 | 13-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.68 | 0.00 | 01-JAN-00:10 | 7284.94 | 13-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.68 | 0.00 | 01-JAN-00:10 | 7284.94 | 13-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.00 | 0.00 | 01-JAN-00:10 | 6370.08 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 39.00 | 0.00 | 01-JAN-00:10 | 6370.08 | 10-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.48 | 0.00 | 01-JAN-00:10 | 7886.98 | 07-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 5275.25 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 5275.25 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.15 | 0.00 | 01-JAN-00:10 | 7886.98 | 07-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.15 | 0.00 | 01-JAN-00:10 | 7886.98 | 07-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.41 | 0.00 | 01-JAN-00:10 | 9777.52 | 10-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.43 | 0.00 | 01-JAN-00:10 | 7820.13 | 09-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.43 | 0.00 | 01-JAN-00:10 | 7820.13 | 09-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.98 | 0.00 | 01-JAN-00:10 | 9777.52 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 52.98 | 0.00 | 01-JAN-00:10 | 9777.52 | 10-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.66 | 0.00 | 01-JAN-00:10 | 7523.88 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.50 | 0.00 | 01-JAN-00:10 | 5308.37 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.50 | 0.00 | 01-JAN-00:10 | 5308.37 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.16 | 0.00 | 01-JAN-00:10 | 7523.88 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.16 | 0.00 | 01-JAN-00:10 | 7523.88 | 02-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
PlantLoopHeatingDemand:Plant | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
EnergyTransfer:HVAC | 1365.20 | 0.00 | 01-JAN-00:10 | 249431.30 | 07-JUL-16:00 |
HeatingCoils:EnergyTransfer | 114.48 | 0.00 | 01-JAN-00:10 | 192831.40 | 13-FEB-07:10 |
CoolingCoils:EnergyTransfer | 1250.72 | 0.00 | 01-JAN-00:10 | 249431.30 | 07-JUL-16:00 |
EnergyTransfer:Plant | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterSystems:EnergyTransfer | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 45.37 | 0.00 | 01-JAN-00:10 | 5951.33 | 01-FEB-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.002 | -240.157 | 0.000 | 0.000 | 32.904 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -98.770 |
CORE_MID | 0.000 | 0.000 | 0.352 | -169.024 | 0.000 | 0.000 | 34.018 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -36.370 |
CORE_TOP | 0.000 | 0.000 | 3.165 | -162.421 | 0.000 | 0.000 | 34.646 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -46.414 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.621 | -38.510 | 0.000 | 0.000 | 7.430 | 6.784 | 24.333 | 18.015 | 0.000 | 0.129 | 2.290 | 0.000 | -24.714 | 0.000 | -2.378 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.320 | -33.902 | 0.000 | 0.000 | 4.625 | 4.239 | 15.404 | 29.091 | 0.000 | 0.080 | 0.001 | 0.000 | -15.313 | 0.000 | -1.630 | -5.914 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 3.991 | -52.013 | 0.000 | 0.000 | 7.235 | 6.648 | 24.332 | 51.275 | 0.000 | 0.121 | 0.001 | 0.000 | -23.240 | 0.000 | -2.538 | -15.812 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.837 | -33.175 | 0.000 | 0.000 | 4.665 | 4.265 | 15.403 | 29.354 | 0.000 | 0.080 | 0.000 | 0.000 | -16.364 | 0.000 | -1.642 | -6.423 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.532 | -35.345 | 0.000 | 0.000 | 7.387 | 6.762 | 24.333 | 18.356 | 0.000 | 0.075 | 3.138 | 0.000 | -25.890 | 0.000 | -1.349 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.132 | -31.784 | 0.000 | 0.000 | 4.578 | 4.230 | 15.404 | 29.238 | 0.000 | 0.045 | 0.001 | 0.000 | -16.327 | 0.000 | -0.938 | -5.577 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 7.798 | -47.183 | 0.000 | 0.000 | 7.303 | 6.636 | 24.332 | 51.791 | 0.000 | 3.908 | 0.004 | 0.000 | -24.738 | 0.000 | -20.509 | -9.338 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.218 | -30.498 | 0.000 | 0.000 | 4.614 | 4.254 | 15.403 | 29.597 | 0.000 | 0.044 | 0.001 | 0.000 | -17.472 | 0.000 | -0.945 | -6.215 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.681 | -39.003 | 0.000 | 0.000 | 7.348 | 6.784 | 24.333 | 17.894 | 0.000 | 0.111 | 8.253 | 0.000 | -26.285 | 0.000 | -2.117 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.335 | -32.149 | 0.000 | 0.000 | 3.375 | 4.239 | 15.404 | 28.839 | 0.000 | 0.067 | 0.001 | 0.000 | -16.259 | 0.000 | -1.453 | -3.397 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.433 | -52.979 | 0.000 | 0.000 | 7.155 | 6.648 | 24.332 | 51.061 | 0.000 | 0.104 | 0.000 | 0.000 | -24.633 | 0.000 | -2.252 | -10.869 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.503 | -33.158 | 0.000 | 0.000 | 4.613 | 4.265 | 15.403 | 29.281 | 0.000 | 0.067 | 0.002 | 0.000 | -17.377 | 0.000 | -1.458 | -3.140 |
TOPFLOOR_PLENUM | 10.443 | -34.125 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.122 | 27.186 | 0.000 | 0.000 | 0.000 | -3.627 | -0.000 |
MIDFLOOR_PLENUM | 4.148 | -18.598 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.157 | 17.979 | 0.000 | 0.000 | 0.000 | -3.686 | -0.000 |
FIRSTFLOOR_PLENUM | 2.723 | -22.518 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.119 | 22.717 | 0.000 | 0.000 | 0.000 | -3.041 | -0.000 |
Total Facility | 17.314 | -75.241 | 40.920 | -1031.300 | 0.000 | 0.000 | 171.895 | 232.552 | 719.689 | 383.791 | 0.000 | 5.231 | 81.574 | 0.000 | -248.612 | 0.000 | -49.564 | -248.242 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-AUG-04:03 | 0.00 | 0.00 | 0.00 | -38198.99 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 32345.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-JUL-04:03 | 0.00 | 0.00 | 0.00 | -29326.55 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 26672.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:12 | 0.00 | 0.00 | 0.00 | -31467.02 | 0.00 | 0.00 | 335.77 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 27556.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:02 | 0.00 | 0.00 | 0.00 | -11228.94 | 0.00 | 0.00 | 27.17 | 27.57 | 478.42 | 3550.10 | 0.00 | 99.03 | 7046.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 27-AUG-09:22 | 0.00 | 0.00 | 0.00 | -11870.59 | 0.00 | 0.00 | 14.97 | 17.46 | 302.86 | 7778.42 | 0.00 | 0.00 | 3760.29 | 0.00 | -0.00 | 0.00 | -3.40 | 0.00 |
PERIMETER_TOP_ZN_1 | 24-SEP-13:43 | 0.00 | 0.00 | 0.00 | -13806.25 | 0.00 | 0.00 | 25.25 | 27.57 | 478.41 | 7504.18 | 0.00 | 14.85 | 5755.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:22 | 0.00 | 0.00 | 0.00 | -12867.95 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 7246.48 | 0.00 | 25.72 | 5333.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6796.96 | 0.00 | 0.00 | 147.83 | 182.63 | 637.89 | 514.32 | 0.00 | 0.00 | 5316.19 | 0.00 | -0.00 | 0.00 | -1.90 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:52 | 0.00 | 0.00 | 0.00 | -9842.72 | 0.00 | 0.00 | 16.35 | 17.46 | 302.86 | 6600.74 | 0.00 | 7.55 | 2897.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-14:53 | 0.00 | 0.00 | 0.00 | -11361.03 | 0.00 | 0.00 | 25.40 | 27.57 | 478.41 | 7744.97 | 0.00 | 1.40 | 3083.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-17:52 | 0.00 | 0.00 | 0.00 | -10451.33 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 5848.57 | 0.00 | 16.33 | 4324.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-13:02 | 0.00 | 0.00 | 0.00 | -9491.15 | 0.00 | 0.00 | 28.41 | 27.57 | 478.42 | 3616.55 | 0.00 | 86.38 | 5253.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-10:12 | 0.00 | 0.00 | 0.00 | -11640.54 | 0.00 | 0.00 | 14.75 | 17.46 | 302.86 | 6333.81 | 0.00 | 5.68 | 4965.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 11-NOV-13:43 | 0.00 | 0.00 | 0.00 | -12248.13 | 0.00 | 0.00 | 25.46 | 27.57 | 478.41 | 12155.96 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -112.69 | -326.59 |
PERIMETER_MID_ZN_4 | 02-JUL-17:42 | 0.00 | 0.00 | 0.00 | -11908.84 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 5983.03 | 0.00 | 18.12 | 5645.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 01-AUG-14:05 | 0.00 | -10219.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.46 | 10179.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-JUL-15:30 | 0.00 | -4370.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 4313.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-JUL-15:30 | 0.00 | -4669.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 4624.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-04:02 | 0.00 | 8826.46 | 0.00 | -181336.44 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 161272.79 | 0.00 | -5156.74 | 0.00 | -248.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-JAN-07:01 | 0.00 | 0.00 | 12850.46 | 0.00 | 0.00 | 0.00 | 886.20 | 1645.36 | 10194.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25576.87 |
CORE_MID | 09-JAN-06:10 | 0.00 | 0.00 | 14971.79 | 0.00 | 0.00 | 0.00 | 494.28 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18703.72 |
CORE_TOP | 09-JAN-05:01 | 0.00 | 0.00 | 30736.76 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33390.54 |
PERIMETER_TOP_ZN_3 | 12-FEB-07:12 | 0.00 | 0.00 | 10224.84 | 0.00 | 0.00 | 0.00 | 59.23 | 57.81 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3772.37 | 0.00 | -846.03 | -6201.90 |
PERIMETER_TOP_ZN_2 | 12-FEB-06:33 | 0.00 | 0.00 | 9532.28 | 0.00 | 0.00 | 0.00 | 37.53 | 36.60 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2450.24 | 0.00 | -644.03 | -6814.98 |
PERIMETER_TOP_ZN_1 | 12-FEB-07:12 | 0.00 | 0.00 | 11763.04 | 0.00 | 0.00 | 0.00 | 59.06 | 57.81 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3667.34 | 0.00 | -854.98 | -7835.99 |
PERIMETER_TOP_ZN_4 | 12-FEB-06:33 | 0.00 | 0.00 | 9517.89 | 0.00 | 0.00 | 0.00 | 37.51 | 36.59 | 302.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2538.98 | 0.00 | -644.28 | -6711.59 |
PERIMETER_BOT_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 7670.41 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3076.14 | 0.00 | -368.40 | -4785.31 |
PERIMETER_BOT_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 6666.72 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2087.07 | 0.00 | -251.20 | -4682.60 |
PERIMETER_BOT_ZN_1 | 03-FEB-07:10 | 0.00 | 0.00 | 10282.47 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 11975.25 | 0.00 | -3883.15 | 0.00 | -19552.60 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-05:01 | 0.00 | 0.00 | 6661.31 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1731.33 | 0.00 | -166.33 | -5117.80 |
PERIMETER_MID_ZN_3 | 13-FEB-05:01 | 0.00 | 0.00 | 8508.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3002.41 | 0.00 | -558.04 | -5507.28 |
PERIMETER_MID_ZN_2 | 13-FEB-05:01 | 0.00 | 0.00 | 7133.74 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2011.76 | 0.00 | -375.48 | -5100.66 |
PERIMETER_MID_ZN_1 | 09-JAN-05:01 | 0.00 | 0.00 | 9878.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2453.20 | 0.00 | -377.16 | -7607.07 |
PERIMETER_MID_ZN_4 | 13-FEB-05:01 | 0.00 | 0.00 | 7075.12 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1984.21 | 0.00 | -379.59 | -5065.47 |
TOPFLOOR_PLENUM | 13-FEB-06:13 | 13132.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -268.40 | -12863.80 |
MIDFLOOR_PLENUM | 09-JAN-07:11 | 7093.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -166.55 | -6926.88 |
FIRSTFLOOR_PLENUM | 09-JAN-08:50 | 3271.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -91.35 | -3180.10 |
Total Facility | 09-JAN-07:01 | 19723.51 | 0.00 | 134213.15 | 0.00 | 0.00 | 0.00 | 4615.43 | 8334.71 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29164.95 | 0.00 | -21114.85 | -139103.84 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.9222 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4464 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.6560 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0820 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.0937 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8002 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4611 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3280 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0751 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5469 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0761 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5511 | 2.5511 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0387 | 2.0387 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1892 | 2.1892 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6900 | 0.6900 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6702 | 0.6702 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8030 | 0.8030 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7414 | 0.7414 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5522 | 0.5522 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5730 | 0.5730 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6515 | 0.6515 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5943 | 0.5943 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5949 | 0.5949 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6442 | 0.6442 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7071 | 0.7071 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6711 | 0.6711 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.9222 | 4.4464 | 4.9222 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.6560 | 4.0820 | 4.6560 | 1.0751 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.0937 | 4.8002 | 5.0937 | 1.0761 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2756 | 1.2756 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0194 | 1.0194 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0946 | 1.0946 | 0.6370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3450 | 0.3450 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3351 | 0.3351 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4015 | 0.4015 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3707 | 0.3707 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2761 | 0.2761 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2865 | 0.2865 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3258 | 0.3258 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2971 | 0.2971 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2974 | 0.2974 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3221 | 0.3221 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3536 | 0.3536 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3356 | 0.3356 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4611 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3280 | 1.0751 | 1.0751 | 1.0751 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5469 | 1.0761 | 1.0761 | 1.0761 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 132.17 |
Number of hours cooling loads not met | 159.67 |
Number of hours not met | 291.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 114.48 | 192831.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 292.17 | 69402.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.55 | 24978.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.35 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 67.51 | 14740.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 48.14 | 6214.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1552.93 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1552.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.68 |
Space Heating | 22.98 |
Space Cooling | 58.64 |
Fans (All) | 13.55 |
Service Water Heating | 9.66 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 311.70 |
Subtotal | 311.70 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.98 |
Space Heating | 7.37 |
Space Cooling | 18.81 |
Fans (All) | 4.35 |
Service Water Heating | 3.10 |
Receptacle Equipment | 46.34 |
Miscellaneous | 5.05 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1042. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8438.17 | 321.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8691.00 | 69.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8670.00 | 90.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8708.00 | 52.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8739.67 | 20.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8707.67 | 52.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8691.83 | 68.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8675.50 | 84.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8565.17 | 194.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8438.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 321.83 | 0.00 | 0.00 | 0.00 |
Average | 8700.60 | 59.40 | 0.00 | 0.00 | 0.00 |
Sum | 156610.83 | 1069.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128201.67 | 102.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 102.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.65 | 5.69 | 0.00 | 0.00 | 0.00 |
Sum | 614477.67 | 102.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8215.50 | 544.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8196.17 | 563.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8113.83 | 646.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8176.50 | 583.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8090.17 | 669.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8401.50 | 358.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8233.33 | 526.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8131.67 | 628.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8179.67 | 580.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8183.17 | 576.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8086.67 | 673.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8157.50 | 602.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8055.17 | 704.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8483.00 | 277.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8587.33 | 172.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8636.17 | 123.83 | 0.00 | 0.00 | 0.00 |
Min | 8055.17 | 0.83 | 0.00 | 0.00 | 0.00 |
Max | 8759.17 | 704.83 | 0.00 | 0.00 | 0.00 |
Average | 8302.38 | 457.62 | 0.00 | 0.00 | 0.00 |
Sum | 149442.83 | 8237.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128070.00 | 234.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128302.67 | 1.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24898.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24898.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24906.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23823.17 | 1085.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24899.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24899.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 1085.83 | 0.00 | 0.00 | 0.00 |
Average | 34067.58 | 75.75 | 0.00 | 0.00 | 0.00 |
Sum | 613216.50 | 1363.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 3.965 |
February | 7.937 |
March | 13.764 |
April | 17.213 |
May | 20.837 |
June | 24.797 |
July | 26.063 |
August | 26.547 |
September | 22.525 |
October | 16.026 |
November | 11.940 |
December | 7.696 |
Annual Sum or Average | 16.653 |
Minimum of Months | 3.965 |
Maximum of Months | 26.547 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107786E+11 | 12542.98 | 31-JAN-17:00 | 19.40 | 13.37 | 0.185219E+10 | 2606.62 | 31-JAN-10:30 | 19.40 | 13.37 |
February | 0.116082E+11 | 17952.27 | 28-FEB-17:00 | 23.90 | 12.94 | 0.174582E+10 | 2606.66 | 22-FEB-14:20 | 23.90 | 12.94 |
March | 0.183749E+11 | 28151.29 | 31-MAR-06:03 | 17.30 | 16.12 | 0.215548E+10 | 2606.71 | 08-MAR-10:09 | 17.30 | 16.12 |
April | 0.192604E+11 | 33395.93 | 17-APR-06:03 | 13.58 | 10.46 | 0.191818E+10 | 2606.65 | 07-APR-13:20 | 13.58 | 10.46 |
May | 0.236417E+11 | 37721.18 | 30-MAY-05:12 | 19.07 | 17.52 | 0.207945E+10 | 2606.74 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.261476E+11 | 37805.49 | 19-JUN-05:12 | 20.93 | 20.12 | 0.207263E+10 | 2606.68 | 09-JUN-09:00 | 20.93 | 20.12 |
July | 0.263923E+11 | 38064.75 | 15-JUL-04:03 | 23.90 | 20.50 | 0.192728E+10 | 2606.59 | 03-JUL-09:20 | 23.90 | 20.50 |
August | 0.286105E+11 | 38200.51 | 09-AUG-04:03 | 24.40 | 22.40 | 0.216225E+10 | 2606.59 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.245105E+11 | 37756.04 | 18-SEP-05:12 | 14.40 | 13.71 | 0.192094E+10 | 2606.63 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.210686E+11 | 36589.07 | 10-OCT-05:12 | 15.73 | 14.81 | 0.199410E+10 | 2606.63 | 04-OCT-13:20 | 15.73 | 14.81 |
November | 0.168872E+11 | 31901.86 | 06-NOV-07:03 | 9.08 | 8.50 | 0.196947E+10 | 2606.76 | 16-NOV-10:09 | 10.68 | 10.03 |
December | 0.128757E+11 | 16567.75 | 14-DEC-17:00 | 13.90 | 10.25 | 0.189270E+10 | 2606.69 | 11-DEC-10:20 | 13.90 | 10.25 |
Annual Sum or Average | 0.240156E+12 | 0.236905E+11 | ||||||||
Minimum of Months | 0.107786E+11 | 12542.98 | 9.08 | 8.50 | 0.174582E+10 | 2606.59 | 10.68 | 10.03 | ||
Maximum of Months | 0.286105E+11 | 38200.51 | 24.40 | 22.40 | 0.216225E+10 | 2606.76 | 23.90 | 22.59 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82185147.30 | 1033.53 | 31-JAN-17:30 | 19.15 | 13.30 | 0.00 | 0.00 | 01-JAN-00:10 | 19.15 | 13.30 |
February | 0.412590E+09 | 3290.86 | 28-FEB-16:00 | 23.30 | 12.53 | 0.00 | 0.00 | 01-FEB-00:10 | 23.30 | 12.53 |
March | 0.139276E+10 | 6806.97 | 30-MAR-14:50 | 27.80 | 17.21 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.21 |
April | 0.259834E+10 | 7768.15 | 17-APR-15:00 | 28.90 | 16.41 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 16.41 |
May | 0.426217E+10 | 8547.19 | 30-MAY-15:00 | 30.60 | 21.44 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 21.44 |
June | 0.604215E+10 | 9146.73 | 12-JUN-15:00 | 33.30 | 22.72 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 22.72 |
July | 0.641682E+10 | 10057.66 | 07-JUL-15:20 | 35.20 | 23.90 | 0.00 | 0.00 | 01-JUL-00:10 | 35.20 | 23.90 |
August | 0.669599E+10 | 10219.41 | 01-AUG-14:00 | 33.90 | 23.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 23.66 |
September | 0.366605E+10 | 8776.24 | 06-SEP-14:20 | 30.53 | 23.42 | 0.00 | 0.00 | 01-SEP-00:10 | 30.53 | 23.42 |
October | 0.176451E+10 | 6897.17 | 10-OCT-14:40 | 29.07 | 20.78 | 0.00 | 0.00 | 01-OCT-00:10 | 29.07 | 20.78 |
November | 0.609072E+09 | 2855.23 | 06-NOV-15:00 | 20.60 | 10.48 | 0.00 | 0.00 | 01-NOV-00:10 | 20.60 | 10.48 |
December | 0.182713E+09 | 1712.64 | 10-DEC-14:23 | 17.50 | 8.24 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 8.24 |
Annual Sum or Average | 0.341254E+11 | 0.00 | ||||||||
Minimum of Months | 82185147.30 | 1033.53 | 17.50 | 8.24 | 0.00 | 0.00 | 17.50 | 8.24 | ||
Maximum of Months | 0.669599E+10 | 10219.41 | 35.20 | 23.90 | 0.00 | 0.00 | 35.20 | 23.90 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39314476.16 | 1949.63 | 14-JAN-06:01 | -6.7 | -7.8 | 0.00 | 0.00 | 01-JAN-00:10 | -6.7 | -7.8 |
February | 0.150699E+09 | 1985.06 | 24-FEB-07:03 | 3.07 | 0.07 | 0.00 | 0.00 | 01-FEB-00:10 | 3.07 | 0.07 |
March | 0.622550E+09 | 2352.71 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.117882E+10 | 2986.21 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.213203E+10 | 3755.48 | 30-MAY-15:20 | 29.67 | 21.52 | 0.00 | 0.00 | 01-MAY-00:10 | 29.67 | 21.52 |
June | 0.325329E+10 | 4041.07 | 26-JUN-06:03 | 23.30 | 21.67 | 0.00 | 0.00 | 01-JUN-00:10 | 23.30 | 21.67 |
July | 0.361414E+10 | 4370.63 | 10-JUL-15:30 | 32.50 | 22.22 | 0.00 | 0.00 | 01-JUL-00:10 | 32.50 | 22.22 |
August | 0.390673E+10 | 4265.27 | 07-AUG-12:10 | 30.87 | 23.75 | 0.00 | 0.00 | 01-AUG-00:10 | 30.87 | 23.75 |
September | 0.233750E+10 | 3840.87 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.978807E+09 | 2790.32 | 11-OCT-16:00 | 26.10 | 17.12 | 0.00 | 0.00 | 01-OCT-00:10 | 26.10 | 17.12 |
November | 0.279379E+09 | 1759.20 | 18-NOV-07:03 | 3.98 | 1.87 | 0.00 | 0.00 | 01-NOV-00:10 | 3.98 | 1.87 |
December | 0.105064E+09 | 1944.54 | 15-DEC-07:03 | 3.22 | 0.92 | 0.00 | 0.00 | 01-DEC-00:10 | 3.22 | 0.92 |
Annual Sum or Average | 0.185983E+11 | 0.00 | ||||||||
Minimum of Months | 39314476.16 | 1759.20 | -6.7 | -7.8 | 0.00 | 0.00 | -6.7 | -7.8 | ||
Maximum of Months | 0.390673E+10 | 4370.63 | 32.50 | 23.75 | 0.00 | 0.00 | 32.50 | 23.75 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44546774.39 | 1791.57 | 21-JAN-07:03 | 5.00 | 3.19 | 0.00 | 0.00 | 01-JAN-00:10 | 5.00 | 3.19 |
February | 0.210689E+09 | 2307.85 | 24-FEB-07:03 | 3.07 | 0.07 | 0.00 | 0.00 | 01-FEB-00:10 | 3.07 | 0.07 |
March | 0.911623E+09 | 2450.18 | 30-MAR-16:00 | 27.80 | 17.47 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 17.47 |
April | 0.150447E+10 | 3214.88 | 06-APR-06:02 | 1.20 | -0.4 | 0.00 | 0.00 | 01-APR-00:10 | 1.20 | -0.4 |
May | 0.247216E+10 | 4011.85 | 30-MAY-15:20 | 29.67 | 21.52 | 0.00 | 0.00 | 01-MAY-00:10 | 29.67 | 21.52 |
June | 0.364309E+10 | 4220.97 | 26-JUN-15:30 | 30.00 | 23.57 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 23.57 |
July | 0.401903E+10 | 4669.52 | 10-JUL-15:30 | 32.50 | 22.22 | 0.00 | 0.00 | 01-JUL-00:10 | 32.50 | 22.22 |
August | 0.447261E+10 | 4612.76 | 07-AUG-14:05 | 31.88 | 24.30 | 0.00 | 0.00 | 01-AUG-00:10 | 31.88 | 24.30 |
September | 0.304226E+10 | 4521.33 | 11-SEP-16:00 | 30.00 | 22.85 | 0.00 | 0.00 | 01-SEP-00:10 | 30.00 | 22.85 |
October | 0.154704E+10 | 3506.43 | 10-OCT-16:00 | 30.00 | 20.56 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 20.56 |
November | 0.516010E+09 | 2178.47 | 21-NOV-07:01 | -2.8 | -3.9 | 0.00 | 0.00 | 01-NOV-00:10 | -2.8 | -3.9 |
December | 0.134588E+09 | 1800.91 | 08-DEC-07:03 | 4.90 | 2.14 | 0.00 | 0.00 | 01-DEC-00:10 | 4.90 | 2.14 |
Annual Sum or Average | 0.225181E+11 | 0.00 | ||||||||
Minimum of Months | 44546774.39 | 1791.57 | -2.8 | -3.9 | 0.00 | 0.00 | -2.8 | -3.9 | ||
Maximum of Months | 0.447261E+10 | 4669.52 | 32.50 | 24.30 | 0.00 | 0.00 | 32.50 | 24.30 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.736296E+10 | 7765.50 | 31-JAN-17:00 | 19.40 | 13.37 | 0.156738E+10 | 2357.33 | 31-JAN-14:00 | 19.40 | 13.37 |
February | 0.834670E+10 | 10965.02 | 28-FEB-17:00 | 23.90 | 12.94 | 0.152842E+10 | 2606.61 | 28-FEB-14:20 | 23.90 | 12.94 |
March | 0.126972E+11 | 13777.98 | 30-MAR-16:00 | 27.80 | 17.47 | 0.206430E+10 | 2606.64 | 30-MAR-09:20 | 27.80 | 17.47 |
April | 0.134998E+11 | 14688.56 | 17-APR-16:00 | 28.90 | 16.41 | 0.188625E+10 | 2606.65 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.169133E+11 | 29154.65 | 30-MAY-05:12 | 19.07 | 17.52 | 0.206589E+10 | 2606.70 | 11-MAY-09:00 | 19.07 | 17.52 |
June | 0.190881E+11 | 29085.38 | 19-JUN-05:12 | 20.93 | 20.12 | 0.206626E+10 | 2606.67 | 09-JUN-09:50 | 20.93 | 20.12 |
July | 0.196016E+11 | 29327.65 | 07-JUL-04:03 | 25.22 | 21.53 | 0.192095E+10 | 2606.61 | 03-JUL-09:20 | 25.22 | 21.53 |
August | 0.209851E+11 | 28982.82 | 22-AUG-05:12 | 22.80 | 21.57 | 0.215766E+10 | 2606.59 | 28-AUG-09:20 | 24.97 | 21.71 |
September | 0.169293E+11 | 29082.00 | 11-SEP-05:12 | 20.20 | 19.05 | 0.191019E+10 | 2606.65 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.136580E+11 | 15163.47 | 11-OCT-16:00 | 26.10 | 17.12 | 0.193819E+10 | 2606.64 | 10-OCT-09:20 | 26.10 | 17.12 |
November | 0.107375E+11 | 11995.09 | 06-NOV-17:00 | 18.90 | 9.61 | 0.184453E+10 | 2606.60 | 06-NOV-10:20 | 18.90 | 9.61 |
December | 0.920378E+10 | 9045.35 | 13-DEC-17:00 | 16.70 | 16.70 | 0.162609E+10 | 2605.57 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.169023E+12 | 0.225761E+11 | ||||||||
Minimum of Months | 0.736296E+10 | 7765.50 | 16.70 | 9.61 | 0.152842E+10 | 2357.33 | 16.70 | 9.61 | ||
Maximum of Months | 0.209851E+11 | 29327.65 | 28.90 | 21.57 | 0.215766E+10 | 2606.70 | 28.90 | 21.71 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521445E+10 | 7649.93 | 20-JAN-17:00 | 16.70 | 11.48 | 0.150327E+10 | 2298.33 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.678380E+10 | 10972.83 | 28-FEB-17:00 | 23.90 | 12.94 | 0.145059E+10 | 2606.62 | 28-FEB-14:20 | 23.90 | 12.94 |
March | 0.119458E+11 | 15787.35 | 30-MAR-16:00 | 27.80 | 17.47 | 0.196829E+10 | 2606.62 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.131738E+11 | 16925.89 | 17-APR-16:00 | 28.90 | 16.41 | 0.184563E+10 | 2606.63 | 17-APR-09:20 | 28.90 | 16.41 |
May | 0.172158E+11 | 20401.62 | 30-MAY-05:12 | 19.07 | 17.52 | 0.205518E+10 | 2606.67 | 22-MAY-09:09 | 19.07 | 17.52 |
June | 0.200822E+11 | 31345.86 | 19-JUN-05:12 | 20.93 | 20.12 | 0.206347E+10 | 2606.68 | 09-JUN-09:00 | 20.93 | 20.12 |
July | 0.207669E+11 | 31461.58 | 24-JUL-05:12 | 20.60 | 19.55 | 0.192021E+10 | 2606.61 | 03-JUL-09:20 | 20.60 | 19.55 |
August | 0.220737E+11 | 31289.08 | 28-AUG-05:12 | 21.50 | 20.43 | 0.215747E+10 | 2606.64 | 25-AUG-09:20 | 21.50 | 20.43 |
September | 0.165508E+11 | 31101.72 | 05-SEP-05:12 | 21.70 | 20.50 | 0.189911E+10 | 2606.68 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.124323E+11 | 16098.66 | 11-OCT-15:50 | 26.28 | 17.62 | 0.186395E+10 | 2606.65 | 10-OCT-09:20 | 26.28 | 17.62 |
November | 0.941162E+10 | 10804.65 | 06-NOV-17:00 | 18.90 | 9.61 | 0.170483E+10 | 2606.51 | 03-NOV-13:00 | 18.90 | 9.61 |
December | 0.676980E+10 | 8356.46 | 13-DEC-17:00 | 16.70 | 16.70 | 0.151657E+10 | 2541.11 | 13-DEC-14:00 | 16.70 | 16.70 |
Annual Sum or Average | 0.162421E+12 | 0.219486E+11 | ||||||||
Minimum of Months | 0.521445E+10 | 7649.93 | 16.70 | 9.61 | 0.145059E+10 | 2298.33 | 16.70 | 9.61 | ||
Maximum of Months | 0.220737E+11 | 31461.58 | 28.90 | 20.50 | 0.215747E+10 | 2606.68 | 28.90 | 20.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318418E+09 | 1585.46 | 31-JAN-16:40 | 19.60 | 13.44 | 0.309090E+09 | 482.84 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.786674E+09 | 2741.49 | 28-FEB-15:30 | 24.15 | 13.12 | 0.292934E+09 | 549.49 | 28-FEB-14:20 | 24.15 | 13.12 |
March | 0.221415E+10 | 4704.34 | 30-MAR-15:50 | 27.80 | 17.41 | 0.391454E+09 | 549.49 | 29-MAR-13:20 | 27.80 | 17.41 |
April | 0.291731E+10 | 5036.87 | 19-APR-14:30 | 26.15 | 17.54 | 0.375304E+09 | 549.49 | 12-APR-13:00 | 26.15 | 17.54 |
May | 0.450914E+10 | 6495.41 | 30-MAY-15:00 | 30.60 | 21.44 | 0.429253E+09 | 549.50 | 18-MAY-09:20 | 30.60 | 21.44 |
June | 0.613378E+10 | 11151.98 | 25-JUN-18:12 | 30.20 | 22.65 | 0.434853E+09 | 549.50 | 09-JUN-09:00 | 30.20 | 22.65 |
July | 0.639171E+10 | 11229.11 | 16-JUL-13:02 | 32.48 | 24.02 | 0.405310E+09 | 549.49 | 03-JUL-09:20 | 32.48 | 24.02 |
August | 0.663649E+10 | 10825.42 | 06-AUG-18:02 | 32.02 | 22.82 | 0.455043E+09 | 549.49 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.409761E+10 | 6252.20 | 06-SEP-14:30 | 30.25 | 23.24 | 0.396407E+09 | 549.50 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.241885E+10 | 4476.53 | 02-OCT-14:40 | 26.70 | 20.10 | 0.371883E+09 | 549.49 | 12-OCT-13:20 | 19.80 | 11.85 |
November | 0.143789E+10 | 2139.50 | 02-NOV-15:30 | 22.50 | 16.22 | 0.334723E+09 | 549.46 | 03-NOV-13:00 | 21.70 | 17.40 |
December | 0.648790E+09 | 1712.18 | 13-DEC-15:00 | 18.30 | 16.86 | 0.304328E+09 | 524.49 | 13-DEC-14:00 | 18.30 | 16.86 |
Annual Sum or Average | 0.385108E+11 | 0.450058E+10 | ||||||||
Minimum of Months | 0.318418E+09 | 1585.46 | 18.30 | 13.12 | 0.292934E+09 | 482.84 | 18.30 | 11.85 | ||
Maximum of Months | 0.663649E+10 | 11229.11 | 32.48 | 24.02 | 0.455043E+09 | 549.50 | 32.48 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359084E+09 | 1034.84 | 31-JAN-15:00 | 21.10 | 12.97 | 0.197876E+09 | 318.33 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.713179E+09 | 2368.19 | 27-FEB-10:30 | 13.90 | 6.16 | 0.194912E+09 | 347.87 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.182274E+10 | 3804.27 | 30-MAR-11:00 | 22.20 | 17.83 | 0.265320E+09 | 347.88 | 08-MAR-10:20 | 22.20 | 17.83 |
April | 0.278971E+10 | 7500.16 | 16-APR-09:43 | 22.02 | 14.52 | 0.249011E+09 | 347.88 | 12-APR-13:00 | 22.02 | 14.52 |
May | 0.414117E+10 | 11230.39 | 07-MAY-09:53 | 25.00 | 20.03 | 0.274880E+09 | 347.89 | 11-MAY-09:50 | 16.73 | 12.76 |
June | 0.532896E+10 | 11840.27 | 04-JUN-09:32 | 25.93 | 19.04 | 0.276101E+09 | 347.89 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.555291E+10 | 11302.92 | 09-JUL-08:23 | 23.90 | 21.72 | 0.256999E+09 | 347.87 | 17-JUL-09:20 | 26.67 | 21.67 |
August | 0.566143E+10 | 11867.92 | 27-AUG-09:22 | 26.10 | 21.69 | 0.288442E+09 | 347.88 | 25-AUG-09:20 | 26.10 | 21.69 |
September | 0.370963E+10 | 11229.76 | 04-SEP-09:32 | 26.13 | 22.05 | 0.253018E+09 | 347.88 | 15-SEP-09:00 | 23.90 | 16.09 |
October | 0.210214E+10 | 4574.16 | 11-OCT-10:20 | 23.73 | 19.29 | 0.247215E+09 | 347.87 | 10-OCT-09:20 | 23.73 | 19.29 |
November | 0.111589E+10 | 2119.79 | 06-NOV-10:20 | 15.33 | 12.73 | 0.225056E+09 | 347.87 | 08-NOV-10:20 | 12.80 | 6.72 |
December | 0.605393E+09 | 1105.56 | 13-DEC-13:30 | 19.45 | 17.14 | 0.198947E+09 | 338.73 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.339022E+11 | 0.292778E+10 | ||||||||
Minimum of Months | 0.359084E+09 | 1034.84 | 13.90 | 6.16 | 0.194912E+09 | 318.33 | 12.80 | 6.72 | ||
Maximum of Months | 0.566143E+10 | 11867.92 | 26.13 | 22.05 | 0.288442E+09 | 347.89 | 26.67 | 21.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122548E+10 | 4618.09 | 11-JAN-14:30 | 6.70 | 2.05 | 0.344723E+09 | 549.47 | 05-JAN-14:00 | 6.70 | 2.05 |
February | 0.183869E+10 | 13359.10 | 26-FEB-15:02 | 24.90 | 12.68 | 0.321490E+09 | 549.50 | 22-FEB-14:20 | 24.90 | 12.68 |
March | 0.362899E+10 | 9650.27 | 30-MAR-13:40 | 27.43 | 17.97 | 0.414585E+09 | 549.51 | 13-MAR-13:00 | 27.43 | 17.97 |
April | 0.408842E+10 | 11402.83 | 16-APR-14:23 | 28.05 | 15.93 | 0.382757E+09 | 549.52 | 12-APR-13:00 | 28.05 | 15.93 |
May | 0.514453E+10 | 9626.37 | 29-MAY-13:43 | 28.40 | 20.38 | 0.429139E+09 | 549.50 | 18-MAY-09:20 | 28.40 | 20.38 |
June | 0.632650E+10 | 12940.67 | 25-JUN-14:13 | 31.83 | 23.24 | 0.434149E+09 | 549.50 | 09-JUN-09:20 | 31.83 | 23.24 |
July | 0.670953E+10 | 13099.18 | 09-JUL-13:02 | 31.88 | 23.72 | 0.405302E+09 | 549.49 | 03-JUL-09:20 | 31.88 | 23.72 |
August | 0.781475E+10 | 13539.67 | 27-AUG-13:23 | 31.70 | 22.52 | 0.455293E+09 | 549.49 | 25-AUG-09:20 | 31.70 | 22.52 |
September | 0.580504E+10 | 13805.46 | 24-SEP-13:43 | 28.40 | 19.81 | 0.398330E+09 | 549.50 | 25-SEP-09:09 | 24.78 | 19.25 |
October | 0.460975E+10 | 13794.59 | 09-OCT-13:13 | 26.47 | 18.95 | 0.391594E+09 | 556.15 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.295404E+10 | 13616.44 | 11-NOV-14:13 | 21.10 | 11.73 | 0.371947E+09 | 549.49 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.186859E+10 | 6397.28 | 08-DEC-14:10 | 12.80 | 5.52 | 0.346645E+09 | 549.48 | 08-DEC-14:30 | 12.80 | 5.48 |
Annual Sum or Average | 0.520143E+11 | 0.469595E+10 | ||||||||
Minimum of Months | 0.122548E+10 | 4618.09 | 6.70 | 2.05 | 0.321490E+09 | 549.47 | 6.70 | 2.05 | ||
Maximum of Months | 0.781475E+10 | 13805.46 | 31.88 | 23.72 | 0.455293E+09 | 556.15 | 31.88 | 23.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363507E+09 | 1117.83 | 20-JAN-16:40 | 16.87 | 11.91 | 0.200645E+09 | 334.28 | 20-JAN-16:49 | 16.78 | 11.69 |
February | 0.724512E+09 | 4429.21 | 27-FEB-17:00 | 22.20 | 11.44 | 0.190720E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.202660E+10 | 6427.28 | 30-MAR-16:00 | 27.80 | 17.47 | 0.252983E+09 | 347.85 | 31-MAR-09:20 | 20.20 | 17.21 |
April | 0.283907E+10 | 12029.44 | 09-APR-17:42 | 21.20 | 11.15 | 0.239691E+09 | 347.85 | 12-APR-13:00 | 28.90 | 17.10 |
May | 0.398831E+10 | 12810.52 | 21-MAY-16:42 | 26.70 | 19.84 | 0.271959E+09 | 347.85 | 18-MAY-09:20 | 26.70 | 19.84 |
June | 0.505526E+10 | 12459.78 | 25-JUN-16:12 | 33.13 | 22.15 | 0.275178E+09 | 347.85 | 09-JUN-09:20 | 33.13 | 22.15 |
July | 0.522861E+10 | 12865.24 | 30-JUL-17:22 | 30.60 | 23.73 | 0.256756E+09 | 347.85 | 03-JUL-09:20 | 30.60 | 23.73 |
August | 0.551473E+10 | 12784.04 | 13-AUG-17:02 | 31.10 | 22.35 | 0.288338E+09 | 347.85 | 25-AUG-09:20 | 25.53 | 18.30 |
September | 0.354943E+10 | 11288.25 | 04-SEP-17:03 | 28.12 | 21.99 | 0.251669E+09 | 347.85 | 25-SEP-09:20 | 25.17 | 19.30 |
October | 0.214735E+10 | 11193.70 | 09-OCT-16:33 | 27.07 | 19.44 | 0.239232E+09 | 347.84 | 18-OCT-09:20 | 21.30 | 20.48 |
November | 0.117299E+10 | 4106.00 | 06-NOV-16:00 | 20.60 | 10.48 | 0.219629E+09 | 347.84 | 03-NOV-13:20 | 20.60 | 10.48 |
December | 0.565923E+09 | 1692.97 | 11-DEC-15:50 | 21.10 | 15.67 | 0.200446E+09 | 347.83 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.331763E+11 | 0.288725E+10 | ||||||||
Minimum of Months | 0.363507E+09 | 1117.83 | 16.87 | 10.48 | 0.190720E+09 | 334.28 | 16.78 | 10.48 | ||
Maximum of Months | 0.551473E+10 | 12865.24 | 33.13 | 23.73 | 0.288338E+09 | 347.85 | 33.13 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390732E+09 | 1519.89 | 31-JAN-16:30 | 19.70 | 13.48 | 0.310149E+09 | 468.49 | 31-JAN-14:00 | 19.70 | 13.48 |
February | 0.840162E+09 | 1740.90 | 28-FEB-15:40 | 23.87 | 12.92 | 0.291713E+09 | 537.20 | 28-FEB-14:00 | 23.87 | 12.92 |
March | 0.204034E+10 | 2777.02 | 30-MAR-16:00 | 27.80 | 17.47 | 0.383829E+09 | 549.49 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.224921E+10 | 3038.01 | 19-APR-14:30 | 26.15 | 17.54 | 0.365095E+09 | 549.49 | 17-APR-13:20 | 26.15 | 17.54 |
May | 0.322953E+10 | 4601.99 | 30-MAY-15:00 | 30.60 | 21.44 | 0.427068E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.44 |
June | 0.495395E+10 | 5373.73 | 26-JUN-06:03 | 23.30 | 21.67 | 0.434951E+09 | 549.50 | 09-JUN-09:20 | 23.30 | 21.67 |
July | 0.548768E+10 | 6795.21 | 17-JUL-06:03 | 21.70 | 19.38 | 0.405131E+09 | 549.49 | 03-JUL-09:20 | 21.70 | 19.38 |
August | 0.603156E+10 | 6610.68 | 07-AUG-06:03 | 22.88 | 22.15 | 0.455009E+09 | 549.49 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.416701E+10 | 5570.78 | 06-SEP-14:30 | 30.25 | 23.24 | 0.402010E+09 | 549.49 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.278486E+10 | 4137.44 | 02-OCT-14:30 | 26.70 | 20.05 | 0.394518E+09 | 549.49 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.200776E+10 | 2182.27 | 03-NOV-14:00 | 21.70 | 17.40 | 0.361511E+09 | 549.48 | 03-NOV-13:20 | 21.70 | 17.40 |
December | 0.116233E+10 | 1710.59 | 13-DEC-13:30 | 19.45 | 17.14 | 0.312840E+09 | 524.20 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.353451E+11 | 0.454382E+10 | ||||||||
Minimum of Months | 0.390732E+09 | 1519.89 | 19.45 | 12.92 | 0.291713E+09 | 468.49 | 18.30 | 12.92 | ||
Maximum of Months | 0.603156E+10 | 6795.21 | 30.60 | 23.24 | 0.455009E+09 | 549.50 | 30.60 | 22.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462794E+09 | 1016.36 | 31-JAN-14:50 | 21.02 | 13.03 | 0.200225E+09 | 313.88 | 31-JAN-14:00 | 21.10 | 12.97 |
February | 0.755584E+09 | 2124.08 | 27-FEB-10:30 | 13.90 | 6.16 | 0.195828E+09 | 347.87 | 24-FEB-10:20 | 13.90 | 6.16 |
March | 0.161391E+10 | 2765.75 | 14-MAR-09:30 | 16.95 | 13.93 | 0.265845E+09 | 347.88 | 08-MAR-10:20 | 16.95 | 13.93 |
April | 0.210389E+10 | 4392.63 | 17-APR-10:10 | 23.27 | 15.57 | 0.247896E+09 | 347.88 | 17-APR-09:20 | 23.27 | 15.57 |
May | 0.318628E+10 | 5429.81 | 30-MAY-10:00 | 27.80 | 21.16 | 0.274757E+09 | 347.89 | 11-MAY-09:00 | 27.80 | 21.16 |
June | 0.454189E+10 | 9796.58 | 04-JUN-09:32 | 25.93 | 19.04 | 0.276182E+09 | 347.88 | 09-JUN-09:00 | 24.40 | 15.46 |
July | 0.495971E+10 | 9805.12 | 04-JUL-09:52 | 27.20 | 23.54 | 0.257120E+09 | 347.87 | 03-JUL-09:20 | 27.20 | 23.54 |
August | 0.532223E+10 | 9840.91 | 06-AUG-09:52 | 29.40 | 23.75 | 0.288574E+09 | 347.87 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.384928E+10 | 9369.92 | 24-SEP-10:02 | 26.38 | 18.55 | 0.255349E+09 | 347.88 | 15-SEP-09:39 | 26.38 | 18.55 |
October | 0.249252E+10 | 4638.36 | 10-OCT-10:20 | 24.23 | 18.95 | 0.257577E+09 | 347.87 | 04-OCT-13:20 | 24.23 | 18.95 |
November | 0.150794E+10 | 2704.54 | 06-NOV-10:10 | 14.87 | 12.62 | 0.244705E+09 | 347.87 | 14-NOV-14:30 | 19.15 | 8.88 |
December | 0.988037E+09 | 1121.75 | 13-DEC-12:00 | 20.00 | 17.41 | 0.210650E+09 | 343.82 | 13-DEC-10:00 | 20.00 | 17.41 |
Annual Sum or Average | 0.317841E+11 | 0.297471E+10 | ||||||||
Minimum of Months | 0.462794E+09 | 1016.36 | 13.90 | 6.16 | 0.195828E+09 | 313.88 | 13.90 | 6.16 | ||
Maximum of Months | 0.532223E+10 | 9840.91 | 29.40 | 23.75 | 0.288574E+09 | 347.89 | 27.80 | 23.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.811457E+09 | 2881.96 | 28-JAN-14:40 | 11.67 | 4.40 | 0.319920E+09 | 548.47 | 31-JAN-14:50 | 21.02 | 13.03 |
February | 0.131330E+10 | 10719.75 | 26-FEB-15:02 | 24.90 | 12.68 | 0.304472E+09 | 549.50 | 28-FEB-10:00 | 20.60 | 11.95 |
March | 0.253911E+10 | 7795.91 | 30-MAR-16:10 | 27.62 | 17.53 | 0.400179E+09 | 549.50 | 13-MAR-13:00 | 27.62 | 17.53 |
April | 0.284271E+10 | 7858.30 | 17-APR-16:10 | 28.80 | 16.45 | 0.368283E+09 | 549.50 | 27-APR-13:20 | 20.97 | 11.53 |
May | 0.384491E+10 | 8761.14 | 30-MAY-12:00 | 29.40 | 21.24 | 0.419821E+09 | 549.50 | 10-MAY-13:20 | 29.40 | 21.24 |
June | 0.586525E+10 | 9446.26 | 06-JUN-16:30 | 33.90 | 21.77 | 0.432928E+09 | 575.21 | 06-JUN-12:09 | 33.90 | 21.77 |
July | 0.653966E+10 | 9852.44 | 07-JUL-16:50 | 35.10 | 23.67 | 0.405535E+09 | 598.80 | 14-JUL-12:09 | 33.40 | 24.44 |
August | 0.810014E+10 | 10810.17 | 06-AUG-13:53 | 32.80 | 24.04 | 0.457374E+09 | 624.80 | 18-AUG-12:09 | 33.98 | 23.68 |
September | 0.607834E+10 | 11114.97 | 24-SEP-13:23 | 28.60 | 19.84 | 0.401321E+09 | 602.80 | 07-SEP-12:09 | 28.60 | 19.84 |
October | 0.453797E+10 | 11360.93 | 09-OCT-14:53 | 27.80 | 19.57 | 0.398392E+09 | 596.23 | 10-OCT-13:00 | 29.40 | 21.05 |
November | 0.290139E+10 | 10851.83 | 12-NOV-13:33 | 18.53 | 10.32 | 0.379316E+09 | 549.50 | 21-NOV-14:09 | 9.08 | 3.58 |
December | 0.180969E+10 | 6665.97 | 10-DEC-14:33 | 17.77 | 8.37 | 0.340027E+09 | 549.49 | 27-DEC-14:20 | 17.23 | 8.31 |
Annual Sum or Average | 0.471839E+11 | 0.462757E+10 | ||||||||
Minimum of Months | 0.811457E+09 | 2881.96 | 11.67 | 4.40 | 0.304472E+09 | 548.47 | 9.08 | 3.58 | ||
Maximum of Months | 0.810014E+10 | 11360.93 | 35.10 | 24.04 | 0.457374E+09 | 624.80 | 33.98 | 24.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423814E+09 | 1063.90 | 23-JAN-17:00 | 10.00 | 3.54 | 0.200928E+09 | 321.07 | 23-JAN-16:00 | 10.00 | 3.54 |
February | 0.728573E+09 | 3253.24 | 27-FEB-17:00 | 22.20 | 11.44 | 0.191122E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.171717E+10 | 4400.69 | 30-MAR-16:00 | 27.80 | 17.47 | 0.256064E+09 | 347.84 | 29-MAR-13:20 | 27.80 | 17.47 |
April | 0.207000E+10 | 4933.52 | 17-APR-16:00 | 28.90 | 16.41 | 0.239860E+09 | 347.85 | 18-APR-09:20 | 22.93 | 15.81 |
May | 0.296919E+10 | 9814.88 | 29-MAY-17:32 | 29.60 | 20.23 | 0.272911E+09 | 347.85 | 17-MAY-09:20 | 29.60 | 20.23 |
June | 0.424166E+10 | 10178.41 | 11-JUN-16:52 | 32.20 | 20.99 | 0.275863E+09 | 347.85 | 09-JUN-09:20 | 32.20 | 20.99 |
July | 0.460658E+10 | 10450.44 | 04-JUL-17:52 | 30.60 | 22.43 | 0.256912E+09 | 347.85 | 03-JUL-09:20 | 30.60 | 22.43 |
August | 0.515650E+10 | 10261.42 | 13-AUG-16:51 | 31.10 | 22.45 | 0.288550E+09 | 347.85 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.366594E+10 | 9659.52 | 04-SEP-16:53 | 28.30 | 22.10 | 0.255278E+09 | 347.85 | 20-SEP-09:20 | 20.93 | 15.94 |
October | 0.242783E+10 | 8423.53 | 09-OCT-15:32 | 27.80 | 19.57 | 0.254866E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.155779E+10 | 4075.96 | 06-NOV-16:30 | 19.75 | 10.05 | 0.238937E+09 | 347.85 | 09-NOV-14:20 | 19.60 | 12.10 |
December | 0.933511E+09 | 1674.04 | 11-DEC-16:00 | 21.10 | 15.91 | 0.207584E+09 | 347.84 | 12-DEC-14:20 | 22.80 | 16.78 |
Annual Sum or Average | 0.304985E+11 | 0.293887E+10 | ||||||||
Minimum of Months | 0.423814E+09 | 1063.90 | 10.00 | 3.54 | 0.191122E+09 | 321.07 | 10.00 | 3.54 | ||
Maximum of Months | 0.515650E+10 | 10450.44 | 32.20 | 22.45 | 0.288550E+09 | 347.85 | 32.20 | 22.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462320E+09 | 1603.47 | 31-JAN-16:40 | 19.60 | 13.44 | 0.311569E+09 | 490.73 | 31-JAN-14:00 | 19.60 | 13.44 |
February | 0.101958E+10 | 2754.46 | 28-FEB-15:00 | 25.00 | 13.71 | 0.298429E+09 | 549.49 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.246559E+10 | 4188.01 | 30-MAR-15:50 | 27.80 | 17.41 | 0.406212E+09 | 549.49 | 30-MAR-09:20 | 27.80 | 17.41 |
April | 0.294942E+10 | 4588.04 | 18-APR-14:00 | 27.20 | 15.86 | 0.384477E+09 | 549.50 | 17-APR-09:20 | 27.20 | 15.86 |
May | 0.434511E+10 | 5885.79 | 30-MAY-15:00 | 30.60 | 21.44 | 0.433321E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.44 |
June | 0.580047E+10 | 7223.07 | 26-JUN-06:03 | 23.30 | 21.67 | 0.435674E+09 | 549.50 | 09-JUN-09:50 | 23.30 | 21.67 |
July | 0.601462E+10 | 9490.82 | 16-JUL-13:02 | 32.48 | 24.02 | 0.405534E+09 | 549.49 | 03-JUL-09:20 | 32.48 | 24.02 |
August | 0.628816E+10 | 7665.52 | 14-AUG-04:02 | 24.22 | 20.90 | 0.455219E+09 | 549.49 | 18-AUG-13:20 | 34.03 | 22.77 |
September | 0.410757E+10 | 5692.11 | 06-SEP-14:30 | 30.25 | 23.24 | 0.400563E+09 | 549.50 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.270664E+10 | 4200.87 | 02-OCT-14:30 | 26.70 | 20.05 | 0.386693E+09 | 549.49 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.182932E+10 | 2303.64 | 03-NOV-14:00 | 21.70 | 17.40 | 0.352648E+09 | 549.48 | 03-NOV-13:20 | 21.70 | 17.40 |
December | 0.101486E+10 | 1751.04 | 13-DEC-13:30 | 19.45 | 17.14 | 0.311771E+09 | 536.70 | 13-DEC-14:20 | 18.30 | 16.86 |
Annual Sum or Average | 0.390037E+11 | 0.458211E+10 | ||||||||
Minimum of Months | 0.462320E+09 | 1603.47 | 19.45 | 13.44 | 0.298429E+09 | 490.73 | 18.30 | 13.44 | ||
Maximum of Months | 0.628816E+10 | 9490.82 | 32.48 | 24.02 | 0.455219E+09 | 549.50 | 34.03 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379169E+09 | 1153.24 | 31-JAN-15:05 | 20.92 | 13.08 | 0.149179E+09 | 345.68 | 31-JAN-15:09 | 20.92 | 13.08 |
February | 0.755113E+09 | 4439.17 | 23-FEB-13:02 | 13.40 | 6.52 | 0.147021E+09 | 356.45 | 28-FEB-11:09 | 20.87 | 12.02 |
March | 0.182905E+10 | 5452.84 | 15-MAR-12:02 | 13.48 | 6.47 | 0.200064E+09 | 356.46 | 13-MAR-14:09 | 13.48 | 6.47 |
April | 0.267525E+10 | 7112.49 | 17-APR-10:05 | 23.27 | 15.57 | 0.185817E+09 | 356.47 | 12-APR-10:09 | 23.27 | 15.57 |
May | 0.384135E+10 | 11098.79 | 07-MAY-09:02 | 23.58 | 19.38 | 0.204490E+09 | 356.48 | 11-MAY-10:09 | 17.67 | 13.57 |
June | 0.487427E+10 | 11372.45 | 04-JUN-09:22 | 25.55 | 18.85 | 0.204821E+09 | 356.46 | 09-JUN-10:09 | 24.78 | 15.66 |
July | 0.507383E+10 | 11638.71 | 09-JUL-10:12 | 28.67 | 23.11 | 0.191307E+09 | 356.45 | 17-JUL-10:09 | 27.88 | 22.09 |
August | 0.519490E+10 | 11389.29 | 27-AUG-10:22 | 28.90 | 22.36 | 0.213907E+09 | 356.45 | 18-AUG-14:09 | 28.90 | 22.36 |
September | 0.352136E+10 | 10719.74 | 04-SEP-09:53 | 26.70 | 22.31 | 0.188772E+09 | 356.47 | 15-SEP-10:09 | 24.18 | 16.24 |
October | 0.216039E+10 | 6006.36 | 10-OCT-10:05 | 23.77 | 18.74 | 0.187276E+09 | 356.45 | 04-OCT-14:09 | 23.77 | 18.74 |
November | 0.117083E+10 | 4002.33 | 28-NOV-13:02 | 15.87 | 7.11 | 0.175315E+09 | 356.45 | 14-NOV-13:09 | 15.87 | 7.11 |
December | 0.674259E+09 | 3026.34 | 14-DEC-13:02 | 13.98 | 9.85 | 0.153865E+09 | 356.45 | 13-DEC-15:09 | 13.98 | 9.85 |
Annual Sum or Average | 0.321498E+11 | 0.220183E+10 | ||||||||
Minimum of Months | 0.379169E+09 | 1153.24 | 13.40 | 6.47 | 0.147021E+09 | 345.68 | 13.48 | 6.47 | ||
Maximum of Months | 0.519490E+10 | 11638.71 | 28.90 | 23.11 | 0.213907E+09 | 356.48 | 28.90 | 22.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152636E+10 | 4975.37 | 27-JAN-14:30 | 3.35 | -2.1 | 0.351448E+09 | 549.47 | 26-JAN-14:00 | 3.35 | -2.1 |
February | 0.216203E+10 | 11197.22 | 26-FEB-13:13 | 24.07 | 12.58 | 0.328436E+09 | 549.50 | 22-FEB-14:20 | 24.07 | 12.58 |
March | 0.392213E+10 | 9054.72 | 30-MAR-13:40 | 27.43 | 17.97 | 0.427064E+09 | 549.51 | 08-MAR-10:20 | 27.43 | 17.97 |
April | 0.409874E+10 | 10131.52 | 16-APR-13:23 | 28.60 | 16.10 | 0.390567E+09 | 549.52 | 12-APR-13:00 | 28.60 | 16.10 |
May | 0.494785E+10 | 7109.09 | 30-MAY-14:00 | 30.60 | 21.03 | 0.433188E+09 | 549.50 | 17-MAY-09:20 | 30.60 | 21.03 |
June | 0.596297E+10 | 9646.92 | 25-JUN-14:13 | 31.83 | 23.24 | 0.435349E+09 | 549.50 | 09-JUN-09:20 | 31.83 | 23.24 |
July | 0.629972E+10 | 11270.98 | 16-JUL-13:02 | 32.48 | 24.02 | 0.405658E+09 | 549.49 | 03-JUL-09:20 | 32.48 | 24.02 |
August | 0.740193E+10 | 11754.95 | 06-AUG-13:53 | 32.80 | 24.04 | 0.455514E+09 | 549.49 | 10-AUG-13:20 | 30.93 | 23.78 |
September | 0.575700E+10 | 12106.46 | 24-SEP-13:23 | 28.60 | 19.84 | 0.401739E+09 | 549.73 | 06-SEP-13:20 | 28.60 | 19.84 |
October | 0.496995E+10 | 12215.17 | 09-OCT-12:53 | 26.10 | 18.71 | 0.402068E+09 | 573.73 | 10-OCT-13:50 | 29.22 | 21.00 |
November | 0.350370E+10 | 12246.65 | 11-NOV-13:43 | 21.10 | 11.67 | 0.387176E+09 | 552.93 | 06-NOV-14:09 | 21.10 | 11.67 |
December | 0.242779E+10 | 6942.27 | 08-DEC-13:50 | 12.62 | 5.51 | 0.357486E+09 | 549.49 | 11-DEC-10:50 | 14.45 | 11.70 |
Annual Sum or Average | 0.529802E+11 | 0.477569E+10 | ||||||||
Minimum of Months | 0.152636E+10 | 4975.37 | 3.35 | -2.1 | 0.328436E+09 | 549.47 | 3.35 | -2.1 | ||
Maximum of Months | 0.740193E+10 | 12246.65 | 32.80 | 24.04 | 0.455514E+09 | 573.73 | 32.48 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.461057E+09 | 1122.57 | 20-JAN-16:40 | 16.87 | 11.91 | 0.203335E+09 | 337.08 | 23-JAN-16:00 | 10.00 | 3.54 |
February | 0.871174E+09 | 4330.02 | 27-FEB-17:00 | 22.20 | 11.44 | 0.194727E+09 | 347.84 | 28-FEB-14:20 | 25.00 | 13.71 |
March | 0.217831E+10 | 6005.60 | 30-MAR-16:00 | 27.80 | 17.47 | 0.262199E+09 | 347.85 | 30-MAR-09:20 | 27.80 | 17.47 |
April | 0.281554E+10 | 11035.95 | 09-APR-16:23 | 21.70 | 10.70 | 0.245459E+09 | 347.85 | 17-APR-09:20 | 20.93 | 14.77 |
May | 0.382625E+10 | 11412.77 | 29-MAY-17:32 | 29.60 | 20.23 | 0.274599E+09 | 347.86 | 17-MAY-09:20 | 29.60 | 20.23 |
June | 0.477214E+10 | 11741.06 | 11-JUN-17:02 | 32.20 | 20.99 | 0.275907E+09 | 347.85 | 09-JUN-09:20 | 32.20 | 20.99 |
July | 0.491647E+10 | 11907.59 | 02-JUL-17:42 | 30.60 | 22.04 | 0.256966E+09 | 347.85 | 03-JUL-09:20 | 25.60 | 20.82 |
August | 0.522795E+10 | 11682.83 | 13-AUG-16:51 | 31.10 | 22.45 | 0.288472E+09 | 347.85 | 21-AUG-09:20 | 23.50 | 22.59 |
September | 0.351782E+10 | 11098.46 | 04-SEP-16:53 | 28.30 | 22.10 | 0.254132E+09 | 347.85 | 21-SEP-09:20 | 21.33 | 17.87 |
October | 0.232957E+10 | 9576.30 | 09-OCT-15:32 | 27.80 | 19.57 | 0.247984E+09 | 347.85 | 10-OCT-09:20 | 21.50 | 18.02 |
November | 0.143533E+10 | 4237.85 | 06-NOV-15:50 | 20.60 | 10.48 | 0.230199E+09 | 347.84 | 03-NOV-13:20 | 20.60 | 10.48 |
December | 0.806996E+09 | 1918.65 | 11-DEC-15:40 | 21.10 | 15.44 | 0.205884E+09 | 347.83 | 12-DEC-14:30 | 22.80 | 16.62 |
Annual Sum or Average | 0.331586E+11 | 0.293986E+10 | ||||||||
Minimum of Months | 0.461057E+09 | 1122.57 | 16.87 | 10.48 | 0.194727E+09 | 337.08 | 10.00 | 3.54 | ||
Maximum of Months | 0.522795E+10 | 11907.59 | 32.20 | 22.45 | 0.288472E+09 | 347.86 | 32.20 | 22.59 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1580947.46 | 12850.47 | 09-JAN-07:01 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.92 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1.80 |
Annual Sum or Average | 1580947.46 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 1580947.46 | 12850.47 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328785E+10 | 12691.46 | 09-JAN-06:12 | -2.6 |
February | 0.207788E+10 | 13132.21 | 13-FEB-06:13 | -5.6 |
March | 0.719905E+09 | 4566.47 | 20-MAR-06:03 | 5.00 |
April | 0.438407E+09 | 4554.15 | 06-APR-06:02 | 1.20 |
May | 0.167854E+09 | 2936.91 | 10-MAY-05:03 | 8.98 |
June | 75979879.66 | 2605.93 | 08-JUN-05:03 | 11.70 |
July | 23953511.42 | 3102.93 | 15-JUL-05:03 | 23.98 |
August | 22646977.12 | 4381.81 | 14-AUG-04:02 | 24.22 |
September | 0.135910E+09 | 2526.52 | 29-SEP-05:03 | 12.30 |
October | 0.593326E+09 | 4872.79 | 26-OCT-06:03 | 2.20 |
November | 0.101442E+10 | 9518.13 | 22-NOV-07:02 | -3.2 |
December | 0.188479E+10 | 12289.21 | 18-DEC-06:13 | -5.0 |
Annual Sum or Average | 0.104429E+11 | |||
Minimum of Months | 22646977.12 | 2526.52 | -5.6 | |
Maximum of Months | 0.328785E+10 | 13132.21 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150642E+10 | 7093.44 | 09-JAN-07:11 | -3.3 |
February | 0.843919E+09 | 6403.01 | 13-FEB-07:11 | -5.6 |
March | 0.223897E+09 | 2349.88 | 26-MAR-13:03 | 17.98 |
April | 53350875.02 | 2386.10 | 09-APR-16:23 | 21.70 |
May | 10492275.64 | 1511.08 | 07-MAY-09:02 | 23.58 |
June | 8881161.49 | 1645.41 | 11-JUN-08:23 | 22.50 |
July | 13070687.64 | 1880.18 | 09-JUL-16:11 | 33.70 |
August | 12163383.21 | 2108.51 | 13-AUG-16:11 | 30.37 |
September | 11476965.96 | 1836.67 | 24-SEP-11:23 | 28.05 |
October | 0.144925E+09 | 3077.44 | 09-OCT-15:32 | 27.80 |
November | 0.429552E+09 | 3254.63 | 12-NOV-12:33 | 17.43 |
December | 0.889387E+09 | 3522.05 | 04-DEC-07:03 | -3.3 |
Annual Sum or Average | 0.414754E+10 | |||
Minimum of Months | 8881161.49 | 1511.08 | -5.6 | |
Maximum of Months | 0.150642E+10 | 7093.44 | 33.70 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112902E+10 | 3271.32 | 09-JAN-08:50 | -3.3 |
February | 0.618321E+09 | 3054.15 | 13-FEB-08:19 | -4.8 |
March | 55483942.34 | 1543.34 | 12-MAR-14:30 | 17.50 |
April | 10321739.75 | 1628.84 | 09-APR-16:12 | 21.70 |
May | 10237034.75 | 1346.89 | 14-MAY-09:40 | 20.77 |
June | 13723815.31 | 1290.20 | 11-JUN-07:17 | 20.57 |
July | 15313659.21 | 2769.93 | 07-JUL-04:03 | 25.22 |
August | 17563604.07 | 2956.04 | 09-AUG-04:03 | 24.40 |
September | 23097860.34 | 1754.01 | 17-SEP-11:20 | 26.13 |
October | 66083101.51 | 2155.22 | 09-OCT-15:32 | 27.80 |
November | 0.158012E+09 | 2235.08 | 26-NOV-13:05 | 17.57 |
December | 0.605798E+09 | 2106.85 | 10-DEC-13:13 | 15.97 |
Annual Sum or Average | 0.272298E+10 | |||
Minimum of Months | 10237034.75 | 1290.20 | -4.8 | |
Maximum of Months | 0.112902E+10 | 3271.32 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232536E+09 | 14971.83 | 09-JAN-06:10 | -2.4 |
February | 87131402.17 | 14265.67 | 06-FEB-07:05 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.85 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 |
December | 31876994.91 | 14289.93 | 26-DEC-07:05 | 3.30 |
Annual Sum or Average | 0.351544E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.4 | |
Maximum of Months | 0.232536E+09 | 14971.83 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173080E+10 | 30736.77 | 09-JAN-05:01 | -2.2 |
February | 0.754155E+09 | 30250.88 | 13-FEB-05:01 | -5.1 |
March | 11012620.10 | 24910.07 | 23-MAR-06:03 | 6.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 10303565.44 | 24939.56 | 31-OCT-06:03 | 8.22 |
November | 70965589.77 | 26209.75 | 22-NOV-06:01 | -3.3 |
December | 0.587970E+09 | 28730.72 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.316521E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.173080E+10 | 30736.77 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300220E+10 | 9921.84 | 09-JAN-04:43 | -2.1 |
February | 0.161506E+10 | 10224.93 | 12-FEB-07:12 | -12.6 |
March | 0.134399E+09 | 8399.43 | 23-MAR-05:12 | 6.10 |
April | 35392836.85 | 7891.97 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 57855270.99 | 8421.88 | 26-OCT-05:12 | 2.20 |
November | 0.395158E+09 | 9061.28 | 22-NOV-05:03 | -2.9 |
December | 0.138102E+10 | 9839.24 | 18-DEC-05:01 | -5.0 |
Annual Sum or Average | 0.662108E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.300220E+10 | 10224.93 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158559E+10 | 9197.60 | 23-JAN-05:01 | -1.7 |
February | 0.811010E+09 | 9532.35 | 12-FEB-06:33 | -12.6 |
March | 61087109.73 | 7759.98 | 23-MAR-05:12 | 6.10 |
April | 15323659.95 | 7299.37 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 35057459.10 | 7767.37 | 26-OCT-05:12 | 2.20 |
November | 0.170941E+09 | 8380.89 | 25-NOV-06:01 | 0.68 |
December | 0.641074E+09 | 9226.98 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.332009E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.158559E+10 | 9532.35 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187379E+10 | 11340.65 | 02-JAN-06:11 | 3.30 |
February | 0.100336E+10 | 11763.11 | 12-FEB-07:12 | -12.6 |
March | 87479000.08 | 9700.52 | 23-MAR-05:12 | 6.10 |
April | 29890944.99 | 9132.60 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 42929048.45 | 9555.44 | 26-OCT-05:12 | 2.20 |
November | 0.206499E+09 | 10260.26 | 25-NOV-06:01 | 0.68 |
December | 0.746788E+09 | 11271.60 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.399074E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.187379E+10 | 11763.11 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174604E+10 | 9136.20 | 23-JAN-05:01 | -1.7 |
February | 0.927653E+09 | 9517.95 | 12-FEB-06:33 | -12.6 |
March | 73714788.10 | 7553.27 | 23-MAR-05:12 | 6.10 |
April | 19648627.45 | 7245.10 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 35481342.47 | 7494.73 | 26-OCT-05:12 | 2.20 |
November | 0.234368E+09 | 8234.10 | 25-NOV-06:01 | 0.68 |
December | 0.799725E+09 | 9168.89 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.383663E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.174604E+10 | 9517.95 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148647E+10 | 7537.26 | 09-JAN-05:01 | -2.2 |
February | 0.756988E+09 | 7670.44 | 13-FEB-05:01 | -5.1 |
March | 29896678.98 | 6282.17 | 22-MAR-06:03 | 5.50 |
April | 9880923.56 | 6317.55 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 313043.61 | 2086.96 | 26-OCT-06:03 | 2.20 |
November | 15015730.78 | 6365.58 | 22-NOV-07:01 | -3.2 |
December | 0.233567E+09 | 6914.21 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.253214E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.148647E+10 | 7670.44 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720235E+09 | 6626.79 | 09-JAN-05:01 | -2.2 |
February | 0.308353E+09 | 6666.80 | 13-FEB-05:01 | -5.1 |
March | 11514054.25 | 5404.57 | 23-MAR-06:03 | 6.10 |
April | 2370556.27 | 5420.77 | 07-APR-06:02 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 93591.94 | 568.40 | 26-OCT-06:03 | 2.20 |
November | 3363202.94 | 5411.41 | 22-NOV-07:01 | -3.2 |
December | 85982452.29 | 5864.14 | 04-DEC-06:01 | -2.9 |
Annual Sum or Average | 0.113191E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.720235E+09 | 6666.80 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279825E+10 | 10023.36 | 27-JAN-07:10 | -6.7 |
February | 0.171832E+10 | 10282.79 | 03-FEB-07:10 | -8.9 |
March | 0.685020E+09 | 8165.35 | 23-MAR-07:00 | 6.10 |
April | 0.385582E+09 | 8572.43 | 06-APR-06:10 | 1.20 |
May | 90026572.85 | 7423.43 | 11-MAY-06:10 | 8.17 |
June | 9374579.96 | 3833.37 | 08-JUN-06:05 | 12.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 10063043.04 | 4405.81 | 14-SEP-06:07 | 12.30 |
October | 0.338470E+09 | 8194.29 | 26-OCT-07:00 | 2.20 |
November | 0.672697E+09 | 8992.56 | 22-NOV-07:10 | -3.2 |
December | 0.109097E+10 | 9381.51 | 18-DEC-07:10 | -5.1 |
Annual Sum or Average | 0.779876E+10 | |||
Minimum of Months | 0.00 | 0.00 | -8.9 | |
Maximum of Months | 0.279825E+10 | 10282.79 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748382E+09 | 6661.60 | 09-JAN-05:01 | -2.2 |
February | 0.351178E+09 | 6601.39 | 13-FEB-05:01 | -5.1 |
March | 8078407.34 | 5391.50 | 23-MAR-06:03 | 6.10 |
April | 2183707.60 | 5289.60 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 9997.05 | 66.65 | 31-OCT-06:03 | 8.22 |
November | 6742209.11 | 5399.04 | 22-NOV-07:01 | -3.2 |
December | 0.101162E+09 | 5847.71 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.121774E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.748382E+09 | 6661.60 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147226E+10 | 8349.49 | 09-JAN-05:01 | -2.2 |
February | 0.672305E+09 | 8508.25 | 13-FEB-05:01 | -5.1 |
March | 15884347.74 | 6741.06 | 23-MAR-06:03 | 6.10 |
April | 3383307.27 | 6763.94 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 5706029.73 | 6755.92 | 31-OCT-06:03 | 8.22 |
November | 68126055.13 | 7318.00 | 22-NOV-06:01 | -3.3 |
December | 0.443754E+09 | 7823.87 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.268142E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.147226E+10 | 8508.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773159E+09 | 6946.79 | 09-JAN-05:01 | -2.2 |
February | 0.319966E+09 | 7133.71 | 13-FEB-05:01 | -5.1 |
March | 9204869.07 | 5380.40 | 23-MAR-06:03 | 6.10 |
April | 1873152.08 | 5252.96 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 3937940.42 | 5357.74 | 26-OCT-06:03 | 2.20 |
November | 26439835.61 | 5836.03 | 22-NOV-06:01 | -3.3 |
December | 0.200225E+09 | 6629.19 | 04-DEC-05:01 | -2.8 |
Annual Sum or Average | 0.133481E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.773159E+09 | 7133.71 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.825798E+09 | 9878.12 | 09-JAN-05:01 | -2.2 |
February | 0.350082E+09 | 9769.01 | 13-FEB-05:01 | -5.1 |
March | 9349914.49 | 7958.02 | 23-MAR-06:03 | 6.10 |
April | 2498164.54 | 7947.55 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 4329089.85 | 7954.74 | 31-OCT-06:03 | 8.22 |
November | 30175774.56 | 8457.95 | 22-NOV-06:01 | -3.3 |
December | 0.210614E+09 | 9152.21 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.143285E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.825798E+09 | 9878.12 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829732E+09 | 6969.86 | 09-JAN-05:01 | -2.2 |
February | 0.367526E+09 | 7075.09 | 13-FEB-05:01 | -5.1 |
March | 7836472.69 | 5374.15 | 23-MAR-06:03 | 6.10 |
April | 1675351.68 | 5616.83 | 06-APR-06:02 | 1.20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.28 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.40 |
October | 3953091.54 | 5241.41 | 26-OCT-06:03 | 2.20 |
November | 41363124.80 | 5838.81 | 22-NOV-06:01 | -3.3 |
December | 0.251287E+09 | 6328.19 | 26-DEC-06:11 | 3.30 |
Annual Sum or Average | 0.150337E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.829732E+09 | 7075.09 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.621701E+09 | 950.03 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.560104E+09 | 1011.44 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601732E+09 | 957.97 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516580E+09 | 865.53 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539682E+09 | 570.89 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.531085E+09 | 562.52 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.503002E+09 | 675.59 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571568E+09 | 823.21 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.532828E+09 | 904.88 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.598181E+09 | 1038.01 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.601553E+09 | 1025.00 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.606438E+09 | 952.56 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.678446E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.503002E+09 | 562.52 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.621701E+09 | 1038.01 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381030E+09 | 588.12 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344466E+09 | 640.12 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376158E+09 | 599.64 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326188E+09 | 523.41 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344041E+09 | 338.93 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338944E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320160E+09 | 362.00 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362229E+09 | 493.31 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334437E+09 | 555.99 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.366053E+09 | 657.13 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373043E+09 | 643.36 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372110E+09 | 589.92 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423886E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320160E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381030E+09 | 657.13 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.586184E+09 | 936.67 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.535491E+09 | 1011.44 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594583E+09 | 956.57 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518448E+09 | 869.03 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545919E+09 | 582.39 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.537539E+09 | 573.92 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508833E+09 | 717.72 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.574766E+09 | 833.11 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.529757E+09 | 896.92 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.573051E+09 | 1038.01 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.574029E+09 | 1019.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.569357E+09 | 937.96 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.664796E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508833E+09 | 573.92 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594583E+09 | 1038.01 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381858E+09 | 603.40 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.348211E+09 | 640.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.381215E+09 | 609.51 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328317E+09 | 562.94 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345332E+09 | 498.57 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339498E+09 | 369.02 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321841E+09 | 478.36 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364292E+09 | 539.86 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.338538E+09 | 578.82 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.374689E+09 | 657.08 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.370521E+09 | 649.87 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370858E+09 | 604.32 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426517E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321841E+09 | 369.02 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381858E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.617943E+09 | 946.55 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.556860E+09 | 1010.34 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599850E+09 | 954.78 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.515537E+09 | 858.68 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539643E+09 | 567.41 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530785E+09 | 558.63 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.502609E+09 | 584.57 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.570834E+09 | 814.71 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.531435E+09 | 899.62 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.595446E+09 | 1037.91 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.598366E+09 | 1024.39 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.603024E+09 | 949.19 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.676233E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.502609E+09 | 558.63 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.617943E+09 | 1037.91 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379756E+09 | 585.72 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.343491E+09 | 639.54 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375431E+09 | 597.68 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325783E+09 | 518.60 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.343649E+09 | 335.77 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338668E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.319779E+09 | 359.95 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.361880E+09 | 487.68 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333853E+09 | 552.53 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.365116E+09 | 657.08 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.371974E+09 | 642.79 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370931E+09 | 587.60 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423031E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.319779E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.379756E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.585062E+09 | 932.51 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534720E+09 | 1010.34 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593664E+09 | 953.32 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.517286E+09 | 862.34 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545008E+09 | 579.67 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.536696E+09 | 570.78 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508036E+09 | 705.22 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.573778E+09 | 825.09 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.528780E+09 | 891.27 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.571711E+09 | 1037.91 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.573121E+09 | 1018.74 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.567917E+09 | 933.85 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.663578E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508036E+09 | 570.78 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.593664E+09 | 1037.91 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.380588E+09 | 601.69 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346907E+09 | 639.50 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380229E+09 | 608.00 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.327745E+09 | 560.01 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344782E+09 | 493.97 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338962E+09 | 367.49 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321257E+09 | 472.85 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363528E+09 | 536.22 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.337670E+09 | 576.37 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.373494E+09 | 657.03 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.369535E+09 | 649.60 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.369753E+09 | 602.64 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425445E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321257E+09 | 367.49 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380588E+09 | 657.03 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.621697E+09 | 950.03 | 03-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.560101E+09 | 1011.44 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601731E+09 | 957.96 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516580E+09 | 865.52 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.539682E+09 | 570.88 | 24-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.531085E+09 | 562.51 | 23-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.503001E+09 | 675.55 | 27-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571567E+09 | 823.19 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.532827E+09 | 904.86 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.598179E+09 | 1038.01 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.601550E+09 | 1025.00 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.606435E+09 | 952.55 | 06-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.678443E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.503001E+09 | 562.51 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.621697E+09 | 1038.01 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381029E+09 | 588.11 | 03-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.344464E+09 | 640.11 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376158E+09 | 599.63 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.326188E+09 | 523.40 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344041E+09 | 338.92 | 02-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338943E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.320160E+09 | 362.00 | 27-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362228E+09 | 493.30 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334436E+09 | 555.98 | 29-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.366052E+09 | 657.13 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373042E+09 | 643.36 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.372109E+09 | 589.92 | 06-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423885E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.320160E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381029E+09 | 657.13 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.586183E+09 | 936.66 | 03-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.535489E+09 | 1011.44 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594582E+09 | 956.57 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518447E+09 | 869.01 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.545918E+09 | 582.38 | 24-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.537539E+09 | 573.91 | 23-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.508832E+09 | 717.69 | 27-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.574765E+09 | 833.09 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.529756E+09 | 896.91 | 29-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.573049E+09 | 1038.01 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.574028E+09 | 1019.62 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.569356E+09 | 937.95 | 06-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.664795E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.508832E+09 | 573.91 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594582E+09 | 1038.01 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381857E+09 | 603.39 | 03-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.348209E+09 | 640.07 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.381215E+09 | 609.50 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328317E+09 | 562.93 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.345332E+09 | 498.55 | 24-MAY-07:30 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.339498E+09 | 369.01 | 23-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321841E+09 | 478.34 | 27-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364291E+09 | 539.84 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.338537E+09 | 578.82 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.374688E+09 | 657.08 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.370520E+09 | 649.87 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.370857E+09 | 604.32 | 06-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426516E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321841E+09 | 369.01 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381857E+09 | 657.08 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.621701E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459643E+09 |
February | 0.901968E+09 | 0.560104E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 935637.93 | 0.393051E+09 |
March | 0.107774E+10 | 0.601732E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146985.63 | 0.257230E+09 |
April | 0.956342E+09 | 0.516580E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2959132.87 | 0.163037E+09 |
May | 0.103597E+10 | 0.539682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7834879.84 | 0.107104E+09 |
June | 0.103308E+10 | 0.531085E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32877323.45 | 53607836.89 |
July | 0.959235E+09 | 0.503002E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35438590.33 | 35715449.75 |
August | 0.107774E+10 | 0.571568E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34526459.12 | 22595241.08 |
September | 0.956342E+09 | 0.532828E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10166887.46 | 53812231.23 |
October | 0.994195E+09 | 0.598181E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3083130.50 | 0.172903E+09 |
November | 0.984487E+09 | 0.601553E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 312997.56 | 0.244229E+09 |
December | 0.959235E+09 | 0.606438E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415498E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678446E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129282E+09 | 0.237843E+10 |
Minimum of Months | 0.901968E+09 | 0.503002E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22595241.08 |
Maximum of Months | 0.107774E+10 | 0.621701E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35438590.33 | 0.459643E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.381030E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310782E+09 |
February | 0.571020E+09 | 0.344466E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198956.27 | 0.268489E+09 |
March | 0.682301E+09 | 0.376158E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 673450.45 | 0.179549E+09 |
April | 0.605444E+09 | 0.326188E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1521842.90 | 0.113154E+09 |
May | 0.655854E+09 | 0.344041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4583455.09 | 75049950.14 |
June | 0.654023E+09 | 0.338944E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21180831.44 | 36802663.95 |
July | 0.607275E+09 | 0.320160E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22588017.76 | 24808582.79 |
August | 0.682301E+09 | 0.362229E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22178341.68 | 15715748.34 |
September | 0.605444E+09 | 0.334437E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5959827.90 | 36899883.68 |
October | 0.629407E+09 | 0.366053E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1400863.03 | 0.120058E+09 |
November | 0.623262E+09 | 0.373043E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164144.19 | 0.168401E+09 |
December | 0.607275E+09 | 0.372110E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280757E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423886E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80449730.70 | 0.163047E+10 |
Minimum of Months | 0.571020E+09 | 0.320160E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15715748.34 |
Maximum of Months | 0.682301E+09 | 0.381030E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22588017.76 | 0.310782E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.586184E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489184E+09 |
February | 0.901968E+09 | 0.535491E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51441.17 | 0.420418E+09 |
March | 0.107774E+10 | 0.594583E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 888148.53 | 0.280962E+09 |
April | 0.956342E+09 | 0.518448E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2208047.74 | 0.169345E+09 |
May | 0.103597E+10 | 0.545919E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7214300.93 | 0.108204E+09 |
June | 0.103308E+10 | 0.537539E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32691838.11 | 53032484.34 |
July | 0.959235E+09 | 0.508833E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35096806.77 | 35601489.31 |
August | 0.107774E+10 | 0.574766E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33461610.97 | 23331099.75 |
September | 0.956342E+09 | 0.529757E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8448112.80 | 56056593.50 |
October | 0.994195E+09 | 0.573051E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367541.92 | 0.188549E+09 |
November | 0.984487E+09 | 0.574029E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269977E+09 |
December | 0.959235E+09 | 0.569357E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443149E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664796E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121428E+09 | 0.253781E+10 |
Minimum of Months | 0.901968E+09 | 0.508833E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23331099.75 |
Maximum of Months | 0.107774E+10 | 0.594583E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35096806.77 | 0.489184E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.381858E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312009E+09 |
February | 0.570983E+09 | 0.348211E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 305362.97 | 0.268868E+09 |
March | 0.682256E+09 | 0.381215E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 597009.54 | 0.183632E+09 |
April | 0.605404E+09 | 0.328317E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1618494.81 | 0.114307E+09 |
May | 0.655811E+09 | 0.345332E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4665107.06 | 74862800.79 |
June | 0.653980E+09 | 0.339498E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21019433.19 | 37337873.98 |
July | 0.607235E+09 | 0.321841E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22532041.58 | 24868147.11 |
August | 0.682256E+09 | 0.364292E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21577453.29 | 16760979.52 |
September | 0.605404E+09 | 0.338538E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6024527.23 | 37787760.12 |
October | 0.629366E+09 | 0.374689E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1233800.02 | 0.121067E+09 |
November | 0.623221E+09 | 0.370521E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169393E+09 |
December | 0.607235E+09 | 0.370858E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281428E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426517E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79573229.69 | 0.164232E+10 |
Minimum of Months | 0.570983E+09 | 0.321841E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16760979.52 |
Maximum of Months | 0.682256E+09 | 0.381858E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22532041.58 | 0.312009E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.617943E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263450E+09 |
February | 0.901968E+09 | 0.556860E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 543157.41 | 0.219969E+09 |
March | 0.107774E+10 | 0.599850E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 916251.80 | 0.136941E+09 |
April | 0.956342E+09 | 0.515537E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2332384.01 | 81746590.77 |
May | 0.103597E+10 | 0.539643E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5000191.99 | 54117659.02 |
June | 0.103308E+10 | 0.530785E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18875617.29 | 27234923.74 |
July | 0.959235E+09 | 0.502609E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20708955.42 | 18335084.12 |
August | 0.107774E+10 | 0.570834E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19748810.37 | 11550316.94 |
September | 0.956342E+09 | 0.531435E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5631776.97 | 31580590.50 |
October | 0.994195E+09 | 0.595446E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1589955.88 | 0.104358E+09 |
November | 0.984487E+09 | 0.598366E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22144.30 | 0.148853E+09 |
December | 0.959235E+09 | 0.603024E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250725E+09 |
Annual Sum or Average | 0.119305E+11 | 0.676233E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75369245.43 | 0.134886E+10 |
Minimum of Months | 0.901968E+09 | 0.502609E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11550316.94 |
Maximum of Months | 0.107774E+10 | 0.617943E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20708955.42 | 0.263450E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.379756E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178924E+09 |
February | 0.571020E+09 | 0.343491E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116833.90 | 0.151578E+09 |
March | 0.682301E+09 | 0.375431E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 462212.25 | 98176808.22 |
April | 0.605444E+09 | 0.325783E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021759.71 | 58686111.10 |
May | 0.655854E+09 | 0.343649E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2697119.19 | 39418523.49 |
June | 0.654023E+09 | 0.338668E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744976.74 | 19462543.19 |
July | 0.607275E+09 | 0.319779E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12524997.60 | 13332695.14 |
August | 0.682301E+09 | 0.361880E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12152116.79 | 8637148.26 |
September | 0.605444E+09 | 0.333853E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3304424.46 | 22025335.91 |
October | 0.629407E+09 | 0.365116E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 714277.39 | 73192075.37 |
November | 0.623262E+09 | 0.371974E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.76 | 0.104129E+09 |
December | 0.607275E+09 | 0.370931E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170756E+09 |
Annual Sum or Average | 0.755301E+10 | 0.423031E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44740446.78 | 0.938318E+09 |
Minimum of Months | 0.571020E+09 | 0.319779E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8637148.26 |
Maximum of Months | 0.682301E+09 | 0.379756E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12524997.60 | 0.178924E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.585062E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431001E+10 |
February | 0.901968E+09 | 0.534720E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 620466.68 | 0.315559E+10 |
March | 0.107774E+10 | 0.593664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26632563.38 | 0.228998E+10 |
April | 0.956342E+09 | 0.517286E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139995E+09 | 0.129556E+10 |
May | 0.103597E+10 | 0.545008E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333029E+09 | 0.694500E+09 |
June | 0.103308E+10 | 0.536696E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935100E+09 | 0.261840E+09 |
July | 0.959235E+09 | 0.508036E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.967039E+09 | 0.197464E+09 |
August | 0.107774E+10 | 0.573778E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107090E+10 | 0.121436E+09 |
September | 0.956342E+09 | 0.528780E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368525E+09 | 0.464242E+09 |
October | 0.994195E+09 | 0.571711E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66434839.03 | 0.177626E+10 |
November | 0.984487E+09 | 0.573121E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270924E+10 |
December | 0.959235E+09 | 0.567917E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323322E+10 |
Annual Sum or Average | 0.119305E+11 | 0.663578E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390827E+10 | 0.205093E+11 |
Minimum of Months | 0.901968E+09 | 0.508036E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121436E+09 |
Maximum of Months | 0.107774E+10 | 0.593664E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107090E+10 | 0.431001E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.380588E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179420E+09 |
February | 0.570983E+09 | 0.346907E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152734.92 | 0.151307E+09 |
March | 0.682256E+09 | 0.380229E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355549.83 | 0.100592E+09 |
April | 0.605404E+09 | 0.327745E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 956104.89 | 59767673.30 |
May | 0.655811E+09 | 0.344782E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2624340.69 | 39495559.39 |
June | 0.653980E+09 | 0.338962E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11538907.00 | 19846942.54 |
July | 0.607235E+09 | 0.321257E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12467235.22 | 13333812.38 |
August | 0.682256E+09 | 0.363528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11754031.99 | 9286818.83 |
September | 0.605404E+09 | 0.337670E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3239480.08 | 22590586.16 |
October | 0.629366E+09 | 0.373494E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 605478.95 | 74030329.52 |
November | 0.623221E+09 | 0.369535E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104482E+09 |
December | 0.607235E+09 | 0.369753E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170568E+09 |
Annual Sum or Average | 0.755252E+10 | 0.425445E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43693863.59 | 0.944720E+09 |
Minimum of Months | 0.570983E+09 | 0.321257E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9286818.83 |
Maximum of Months | 0.682256E+09 | 0.380588E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12467235.22 | 0.179420E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.621697E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406266E+09 |
February | 0.901968E+09 | 0.560101E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 683133.08 | 0.345660E+09 |
March | 0.107774E+10 | 0.601731E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 955051.13 | 0.228789E+09 |
April | 0.956342E+09 | 0.516580E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2612539.39 | 0.142531E+09 |
May | 0.103597E+10 | 0.539682E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6932392.59 | 92776749.14 |
June | 0.103308E+10 | 0.531085E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28338397.37 | 46029114.16 |
July | 0.959235E+09 | 0.503001E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30746248.60 | 30546832.88 |
August | 0.107774E+10 | 0.571567E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29682867.62 | 19367895.88 |
September | 0.956342E+09 | 0.532827E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8727609.30 | 48139410.88 |
October | 0.994195E+09 | 0.598179E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2524480.21 | 0.156640E+09 |
November | 0.984487E+09 | 0.601550E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88406.10 | 0.223028E+09 |
December | 0.959235E+09 | 0.606435E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377405E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678443E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111291E+09 | 0.211718E+10 |
Minimum of Months | 0.901968E+09 | 0.503001E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19367895.88 |
Maximum of Months | 0.107774E+10 | 0.621697E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30746248.60 | 0.406266E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.381029E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275244E+09 |
February | 0.421807E+09 | 0.344464E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129885.99 | 0.236814E+09 |
March | 0.502994E+09 | 0.376158E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 534534.96 | 0.159651E+09 |
April | 0.447140E+09 | 0.326188E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1284528.93 | 98705313.07 |
May | 0.484071E+09 | 0.344041E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3851071.05 | 64868733.27 |
June | 0.482240E+09 | 0.338943E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17706290.48 | 31607830.85 |
July | 0.448971E+09 | 0.320160E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19069272.34 | 21297296.29 |
August | 0.502994E+09 | 0.362228E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18550579.43 | 13539826.36 |
September | 0.447140E+09 | 0.334436E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4985410.18 | 33104895.89 |
October | 0.465148E+09 | 0.366052E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1150963.24 | 0.108483E+09 |
November | 0.460569E+09 | 0.373042E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35335.27 | 0.154181E+09 |
December | 0.448971E+09 | 0.372109E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255969E+09 |
Annual Sum or Average | 0.557719E+10 | 0.423885E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67297871.86 | 0.145347E+10 |
Minimum of Months | 0.421807E+09 | 0.320160E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13539826.36 |
Maximum of Months | 0.502994E+09 | 0.381029E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19069272.34 | 0.275244E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.586183E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432864E+09 |
February | 0.901968E+09 | 0.535489E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44394.72 | 0.370268E+09 |
March | 0.107774E+10 | 0.594582E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 755119.13 | 0.247774E+09 |
April | 0.956342E+09 | 0.518447E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1930219.11 | 0.147508E+09 |
May | 0.103597E+10 | 0.545918E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6354833.87 | 93636211.27 |
June | 0.103308E+10 | 0.537539E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28096283.34 | 45593577.34 |
July | 0.959235E+09 | 0.508832E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30235812.48 | 30486149.33 |
August | 0.107774E+10 | 0.574765E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28457686.56 | 20010349.78 |
September | 0.956342E+09 | 0.529756E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7183695.53 | 49925336.79 |
October | 0.994195E+09 | 0.573049E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1142751.51 | 0.168659E+09 |
November | 0.984487E+09 | 0.574028E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243774E+09 |
December | 0.959235E+09 | 0.569356E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401279E+09 |
Annual Sum or Average | 0.119305E+11 | 0.664795E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104201E+09 | 0.225178E+10 |
Minimum of Months | 0.901968E+09 | 0.508832E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20010349.78 |
Maximum of Months | 0.107774E+10 | 0.594582E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30235812.48 | 0.432864E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.381857E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275634E+09 |
February | 0.570983E+09 | 0.348209E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198663.70 | 0.236437E+09 |
March | 0.682256E+09 | 0.381215E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 501688.61 | 0.162311E+09 |
April | 0.605404E+09 | 0.328317E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1364851.37 | 99669906.52 |
May | 0.655811E+09 | 0.345332E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3964008.55 | 64751771.28 |
June | 0.653980E+09 | 0.339498E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17758182.36 | 32074925.21 |
July | 0.607235E+09 | 0.321841E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19125576.51 | 21284994.67 |
August | 0.682256E+09 | 0.364291E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18200015.20 | 14344927.79 |
September | 0.605404E+09 | 0.338537E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5081050.97 | 33654458.89 |
October | 0.629366E+09 | 0.374688E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008226.38 | 0.108949E+09 |
November | 0.623221E+09 | 0.370520E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153942E+09 |
December | 0.607235E+09 | 0.370857E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255272E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426516E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67202263.65 | 0.145833E+10 |
Minimum of Months | 0.570983E+09 | 0.321841E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14344927.79 |
Maximum of Months | 0.682256E+09 | 0.381857E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19125576.51 | 0.275634E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579287E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172846.11 | 0.497144E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685464.24 | 0.329763E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2148448.86 | 0.197942E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6625445.35 | 0.127423E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31480760.13 | 60974303.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35490141.74 | 40337895.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32720633.41 | 25332257.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8059040.93 | 68884149.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1558327.89 | 0.230359E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42948.44 | 0.330575E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553024E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118984E+09 | 0.304105E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25332257.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35490141.74 | 0.579287E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699787E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651718.24 | 0.602451E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1049262.44 | 0.405309E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3189564.97 | 0.248876E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9012760.99 | 0.161639E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40796458.60 | 77848670.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45809958.50 | 51052049.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42304271.34 | 32009329.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11244540.46 | 83731582.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2593341.91 | 0.275769E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533005.40 | 0.391211E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655877E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157185E+09 | 0.368556E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32009329.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45809958.50 | 0.699787E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689671E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.37 | 0.595820E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405222.89 | 0.405989E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898135.06 | 0.254895E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4659610.99 | 0.166075E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33233844.73 | 75617088.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37720472.19 | 51028635.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36350123.65 | 30128517.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7755036.27 | 80653431.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944128.53 | 0.270375E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122131.16 | 0.377473E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628859E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122089E+09 | 0.362658E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30128517.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37720472.19 | 0.689671E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 950.03 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 905.40 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.52 | 26-FEB-13:20 | 1089.30 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 957.97 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 11-MAR-16:00 | 648.74 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 865.53 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.93 | 16-APR-11:57 | 364.85 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 570.89 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 | 07-MAY-12:20 | 285.04 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 562.52 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.42 | 11-JUN-15:00 | 211.31 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 675.59 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.13 | 08-JUL-18:53 | 152.68 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 823.21 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.20 | 06-AUG-14:08 | 98.05 | 23-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 904.88 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.18 | 17-SEP-15:00 | 189.48 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.99 | 08-OCT-14:00 | 383.22 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1025.00 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 | 19-NOV-15:00 | 624.60 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 952.56 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 943.48 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 562.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.05 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 175.42 | 1089.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 588.12 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 601.90 | 07-JAN-18:05 |
February | 827.22 | 01-FEB-10:09 | 640.12 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 26-FEB-15:30 | 726.19 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 599.64 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 30-MAR-16:00 | 429.42 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 523.41 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 | 16-APR-13:53 | 242.79 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 338.93 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.05 | 29-MAY-17:50 | 189.60 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.01 | 25-JUN-16:15 | 141.44 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 362.00 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 | 08-JUL-19:10 | 102.42 | 01-JUL-20:00 |
August | 827.22 | 01-AUG-09:09 | 493.31 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 | 06-AUG-14:08 | 65.50 | 23-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 555.99 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 17-SEP-15:00 | 125.61 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 657.13 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 09-OCT-16:00 | 255.50 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 643.36 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 | 19-NOV-15:00 | 415.92 | 30-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 589.92 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 627.56 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | |||||
Maximum of Months | 827.22 | 657.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 120.02 | 726.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.67 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 916.16 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 28-FEB-15:00 | 1115.55 | 11-FEB-18:05 |
March | 1306.65 | 01-MAR-10:09 | 956.57 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 | 30-MAR-16:00 | 652.24 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 869.03 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 16-APR-13:53 | 365.77 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 582.39 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 | 29-MAY-17:50 | 286.40 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 573.92 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.33 | 11-JUN-15:00 | 211.72 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 717.72 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | 08-JUL-18:53 | 152.96 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 833.11 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.88 | 06-AUG-14:08 | 98.77 | 23-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 896.92 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 17-SEP-15:20 | 190.14 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 | 09-OCT-15:57 | 395.99 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 624.81 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 937.96 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 960.40 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.92 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.77 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 161.33 | 1115.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 603.40 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 608.04 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 640.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 | 26-FEB-12:53 | 768.64 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 609.51 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 30-MAR-16:00 | 431.99 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 562.94 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.62 | 16-APR-11:53 | 241.65 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 498.57 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 | 07-MAY-12:20 | 192.88 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 369.02 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.31 | 25-JUN-15:53 | 143.12 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 478.36 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.14 | 08-JUL-19:10 | 103.00 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 539.86 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 06-AUG-14:08 | 66.54 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 578.82 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 24-SEP-12:43 | 125.50 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 08-OCT-13:43 | 257.69 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.87 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 416.20 | 30-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 604.32 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 626.23 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 369.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | |||||
Maximum of Months | 827.17 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 | 768.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 946.55 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 502.31 | 07-JAN-18:10 |
February | 1306.65 | 01-FEB-10:09 | 1010.34 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 | 26-FEB-13:20 | 611.18 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 954.78 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 | 11-MAR-18:05 | 367.96 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 858.68 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.72 | 08-APR-17:03 | 191.79 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 567.41 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 | 07-MAY-11:53 | 159.35 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 558.63 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.94 | 11-JUN-15:00 | 113.50 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 584.57 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.90 | 08-JUL-18:53 | 83.81 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 814.71 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.51 | 06-AUG-14:00 | 55.66 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 899.62 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.98 | 17-SEP-15:00 | 116.74 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1037.91 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 | 08-OCT-14:00 | 233.63 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1024.39 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 19-NOV-15:00 | 346.83 | 07-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 949.19 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 590.17 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 558.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.66 | |||||
Maximum of Months | 1306.65 | 1037.91 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 109.94 | 611.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 585.72 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 334.32 | 07-JAN-18:10 |
February | 827.22 | 01-FEB-10:09 | 639.54 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 26-FEB-16:10 | 406.69 | 12-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 597.68 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 11-MAR-16:00 | 249.78 | 22-MAR-03:00 |
April | 827.22 | 03-APR-09:09 | 518.60 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 08-APR-17:03 | 127.94 | 05-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 335.77 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 29-MAY-18:00 | 108.50 | 10-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 | 11-JUN-15:00 | 78.21 | 07-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 359.95 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 | 08-JUL-18:53 | 55.58 | 28-JUL-22:00 |
August | 827.22 | 01-AUG-09:09 | 487.68 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.11 | 06-AUG-13:58 | 37.10 | 25-AUG-05:00 |
September | 827.22 | 01-SEP-09:09 | 552.53 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 | 17-SEP-15:00 | 77.67 | 29-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 09-OCT-16:00 | 159.86 | 28-OCT-04:00 |
November | 827.22 | 01-NOV-09:09 | 642.79 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 05-NOV-16:00 | 236.18 | 07-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 587.60 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 395.77 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 | |||||
Maximum of Months | 827.22 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 68.11 | 406.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 932.51 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23077.89 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1010.34 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.19 | 28-FEB-15:00 | 25029.78 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 953.32 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2811.36 | 30-MAR-16:10 | 14368.43 | 06-MAR-07:03 |
April | 1306.65 | 03-APR-09:09 | 862.34 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.84 | 17-APR-16:10 | 15674.95 | 06-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 579.67 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5093.93 | 19-MAY-16:10 | 10416.38 | 11-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 570.78 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7129.21 | 06-JUN-16:05 | 7562.93 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 705.22 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8345.39 | 07-JUL-16:03 | 3687.59 | 03-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 825.09 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7980.75 | 01-AUG-16:03 | 3783.04 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 891.27 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5344.99 | 07-SEP-16:03 | 8138.81 | 14-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 1037.91 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3829.09 | 10-OCT-16:05 | 14932.95 | 26-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1018.74 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 19623.29 | 22-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 933.85 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21581.31 | 18-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 570.78 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3687.59 | |||||
Maximum of Months | 1306.65 | 1037.91 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8345.39 | 25029.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 601.69 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 336.55 | 07-JAN-18:10 |
February | 827.17 | 01-FEB-10:09 | 639.50 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | 26-FEB-13:20 | 417.36 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 608.00 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 30-MAR-16:00 | 251.10 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 560.01 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 16-APR-11:33 | 127.87 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 493.97 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.71 | 07-MAY-11:53 | 110.46 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 367.49 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.54 | 25-JUN-15:55 | 79.27 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 472.85 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 08-JUL-18:53 | 56.52 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 536.22 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 | 06-AUG-13:58 | 38.78 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 576.37 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.70 | 24-SEP-12:50 | 77.71 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.03 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 | 08-OCT-13:53 | 160.83 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.60 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 239.27 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 602.64 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 393.55 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 367.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 | |||||
Maximum of Months | 827.17 | 657.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 65.93 | 417.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 950.03 | 03-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 778.09 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 | 26-FEB-13:00 | 927.28 | 12-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 957.96 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 11-MAR-16:00 | 591.24 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 865.52 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.03 | 16-APR-11:53 | 320.37 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 570.88 | 24-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.13 | 07-MAY-12:10 | 254.80 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 562.51 | 23-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.66 | 11-JUN-14:53 | 182.19 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 675.55 | 27-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.07 | 08-JUL-18:53 | 131.84 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 823.19 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.38 | 06-AUG-14:00 | 87.32 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 904.86 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.51 | 17-SEP-15:00 | 173.95 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 | 08-OCT-14:00 | 350.74 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1025.00 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 19-NOV-15:00 | 524.48 | 30-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 952.55 | 06-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 871.19 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 562.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 157.66 | 927.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 588.11 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 516.50 | 07-JAN-18:05 |
February | 805.43 | 01-FEB-08:09 | 640.11 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 | 26-FEB-15:30 | 617.38 | 11-FEB-19:00 |
March | 805.43 | 01-MAR-08:09 | 599.63 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 30-MAR-16:00 | 392.00 | 22-MAR-03:00 |
April | 805.43 | 03-APR-07:10 | 523.40 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 08-APR-17:03 | 213.31 | 05-APR-05:00 |
May | 805.43 | 01-MAY-07:10 | 338.92 | 02-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 | 29-MAY-18:00 | 169.54 | 10-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.59 | 11-JUN-15:10 | 122.03 | 07-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 362.00 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 | 08-JUL-18:53 | 87.45 | 28-JUL-22:00 |
August | 805.43 | 01-AUG-07:10 | 493.30 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 | 06-AUG-13:58 | 57.79 | 25-AUG-05:00 |
September | 805.43 | 01-SEP-07:10 | 555.98 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 | 17-SEP-15:00 | 115.40 | 29-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 657.13 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 09-OCT-16:00 | 233.88 | 28-OCT-04:00 |
November | 805.43 | 01-NOV-07:10 | 643.36 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 19-NOV-15:00 | 349.32 | 30-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 589.92 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 579.88 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 | |||||
Maximum of Months | 805.43 | 657.13 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 | 617.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 936.66 | 03-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 786.60 | 07-JAN-18:05 |
February | 1306.65 | 01-FEB-10:09 | 1011.44 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 28-FEB-15:00 | 960.64 | 11-FEB-19:00 |
March | 1306.65 | 01-MAR-10:09 | 956.57 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.18 | 30-MAR-16:00 | 594.40 | 22-MAR-03:00 |
April | 1306.65 | 03-APR-09:09 | 869.01 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 | 16-APR-14:10 | 321.20 | 05-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 24-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.75 | 07-MAY-12:10 | 255.95 | 10-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 573.91 | 23-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.17 | 11-JUN-15:10 | 182.52 | 07-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 717.69 | 27-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.79 | 08-JUL-18:53 | 132.07 | 28-JUL-22:00 |
August | 1306.65 | 01-AUG-09:09 | 833.09 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.96 | 06-AUG-13:58 | 87.79 | 25-AUG-05:00 |
September | 1306.65 | 01-SEP-09:09 | 896.91 | 29-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 17-SEP-15:20 | 174.49 | 29-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 1038.01 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 09-OCT-15:38 | 360.37 | 28-OCT-04:00 |
November | 1306.65 | 01-NOV-09:09 | 1019.62 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 538.91 | 07-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 937.95 | 06-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 886.52 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.91 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.79 | |||||
Maximum of Months | 1306.65 | 1038.01 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 146.96 | 960.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 603.39 | 03-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 521.98 | 07-JAN-18:05 |
February | 827.17 | 01-FEB-10:09 | 640.07 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.94 | 26-FEB-13:00 | 656.59 | 11-FEB-18:05 |
March | 827.17 | 01-MAR-10:09 | 609.50 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 30-MAR-16:00 | 393.73 | 22-MAR-03:00 |
April | 827.17 | 03-APR-09:09 | 562.93 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 | 16-APR-12:10 | 212.34 | 05-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 498.55 | 24-MAY-07:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 | 07-MAY-12:10 | 172.21 | 10-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 369.01 | 23-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 | 25-JUN-15:53 | 123.34 | 07-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 478.34 | 27-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.98 | 08-JUL-19:10 | 88.79 | 28-JUL-22:00 |
August | 827.17 | 01-AUG-09:09 | 539.84 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.40 | 06-AUG-13:58 | 59.21 | 25-AUG-05:00 |
September | 827.17 | 01-SEP-09:09 | 578.82 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 24-SEP-12:50 | 115.19 | 29-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 657.08 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 08-OCT-13:43 | 235.27 | 28-OCT-04:00 |
November | 827.17 | 01-NOV-09:09 | 649.87 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 349.95 | 07-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 604.32 | 06-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 578.07 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 369.01 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.21 | |||||
Maximum of Months | 827.17 | 657.08 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 103.40 | 656.59 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1100.51 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 26-FEB-14:53 | 1352.33 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 30-MAR-16:00 | 855.61 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 16-APR-11:53 | 442.48 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 07-MAY-11:53 | 358.98 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.38 | 11-JUN-15:00 | 246.96 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.28 | 08-JUL-18:53 | 176.08 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.96 | 06-AUG-14:00 | 119.29 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.16 | 17-SEP-15:00 | 249.40 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.99 | 09-OCT-16:00 | 512.82 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 19-NOV-15:00 | 756.00 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1294.39 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.38 | 1352.33 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1363.16 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 | 26-FEB-15:02 | 1672.95 | 12-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 11-MAR-16:00 | 1051.26 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 16-APR-11:53 | 562.72 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.41 | 07-MAY-12:10 | 455.95 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.71 | 11-JUN-14:53 | 315.41 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.99 | 08-JUL-18:53 | 222.71 | 28-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.10 | 06-AUG-14:00 | 150.18 | 25-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.81 | 17-SEP-15:00 | 308.92 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 | 08-OCT-13:53 | 617.50 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.21 | 19-NOV-15:00 | 929.62 | 07-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1554.73 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.18 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.71 | 1672.95 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1451.37 | 07-JAN-18:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 26-FEB-14:53 | 1726.62 | 11-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 30-MAR-16:00 | 980.49 | 22-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 | 16-APR-13:57 | 542.42 | 05-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.83 | 19-MAY-13:00 | 412.86 | 10-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.27 | 11-JUN-15:00 | 311.45 | 07-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.84 | 08-JUL-18:50 | 242.39 | 01-JUL-20:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.68 | 06-AUG-13:53 | 145.11 | 23-AUG-05:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 06-SEP-12:00 | 269.10 | 29-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.42 | 09-OCT-15:40 | 576.80 | 28-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 19-NOV-15:00 | 908.27 | 30-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1430.00 | 17-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.84 | 1726.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12542.98 | 31-JAN-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17952.27 | 28-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28151.29 | 31-MAR-06:03 | 3811.58 | 4936.08 | 30584.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33395.93 | 17-APR-06:03 | 5082.11 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37721.18 | 30-MAY-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37805.49 | 19-JUN-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38064.75 | 15-JUL-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38200.51 | 09-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37756.04 | 18-SEP-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36589.07 | 10-OCT-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31901.86 | 06-NOV-07:03 | 5082.11 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16567.75 | 14-DEC-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12542.98 | 0.00 | 846.94 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38200.51 | 6035.01 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1033.53 | 31-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
February | 3290.86 | 28-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 |
March | 6806.97 | 30-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 0.00 |
April | 7768.15 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 | 0.00 |
May | 8547.19 | 30-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.11 | 0.00 |
June | 9146.73 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 0.00 |
July | 10057.66 | 07-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 0.00 |
August | 10219.41 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 0.00 |
September | 8776.24 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | 0.00 |
October | 6897.17 | 10-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 |
November | 2855.23 | 06-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 |
December | 1712.64 | 10-DEC-14:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1033.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10219.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 76.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1949.63 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.73 |
February | 1985.06 | 24-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.52 |
March | 2352.71 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.98 | 0.00 |
April | 2986.21 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.82 |
May | 3755.48 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 |
June | 4041.07 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 |
July | 4370.63 | 10-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 0.00 |
August | 4265.27 | 07-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 0.00 |
September | 3840.87 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
October | 2790.32 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 0.00 |
November | 1759.20 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.92 |
December | 1944.54 | 15-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1759.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4370.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 199.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1791.57 | 21-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.43 |
February | 2307.85 | 24-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.44 |
March | 2450.18 | 30-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 | 0.00 |
April | 3214.88 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.98 |
May | 4011.85 | 30-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 0.00 |
June | 4220.97 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.92 | 0.00 |
July | 4669.52 | 10-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 0.00 |
August | 4612.76 | 07-AUG-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 | 0.00 |
September | 4521.33 | 11-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | 0.00 |
October | 3506.43 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.48 | 0.00 |
November | 2178.47 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.81 |
December | 1800.91 | 08-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1791.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4669.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.07 | 145.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7765.50 | 31-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10965.02 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13777.98 | 30-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14688.56 | 17-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29154.65 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29085.38 | 19-JUN-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29327.65 | 07-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28982.82 | 22-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29082.00 | 11-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15163.47 | 11-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11995.09 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9045.35 | 13-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7765.50 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29327.65 | 6035.01 | 4936.01 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7649.93 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10972.83 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15787.35 | 30-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16925.89 | 17-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20401.62 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31345.86 | 19-JUN-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31461.58 | 24-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31289.08 | 28-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31101.72 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16098.66 | 11-OCT-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10804.65 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8356.46 | 13-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7649.93 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31461.58 | 6035.01 | 4936.01 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1585.46 | 31-JAN-16:40 | 1272.23 | 558.15 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 |
February | 2741.49 | 28-FEB-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 0.00 |
March | 4704.34 | 30-MAR-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 0.00 |
April | 5036.87 | 19-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
May | 6495.41 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 0.00 |
June | 11151.98 | 25-JUN-18:12 | 0.00 | 137.87 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 53.11 | 0.00 |
July | 11229.11 | 16-JUL-13:02 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 | 0.00 |
August | 10825.42 | 06-AUG-18:02 | 0.00 | 137.87 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 81.47 | 0.00 |
September | 6252.20 | 06-SEP-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 0.00 |
October | 4476.53 | 02-OCT-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 0.00 |
November | 2139.50 | 02-NOV-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
December | 1712.18 | 13-DEC-15:00 | 1306.65 | 563.80 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1585.46 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11229.11 | 1306.65 | 563.80 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 | 16.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1034.84 | 31-JAN-15:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
February | 2368.19 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 |
March | 3804.27 | 30-MAR-11:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 |
April | 7500.16 | 16-APR-09:43 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.79 |
May | 11230.39 | 07-MAY-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 |
June | 11840.27 | 04-JUN-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
July | 11302.92 | 09-JUL-08:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 |
August | 11867.92 | 27-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
September | 11229.76 | 04-SEP-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 |
October | 4574.16 | 11-OCT-10:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
November | 2119.79 | 06-NOV-10:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 |
December | 1105.56 | 13-DEC-13:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1034.84 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | |
Maximum of Months | 11867.92 | 827.22 | 314.23 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4618.09 | 11-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.81 |
February | 13359.10 | 26-FEB-15:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 |
March | 9650.27 | 30-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 | 0.00 |
April | 11402.83 | 16-APR-14:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 | 0.00 |
May | 9626.37 | 29-MAY-13:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 | 0.00 |
June | 12940.67 | 25-JUN-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 68.12 | 0.00 |
July | 13099.18 | 09-JUL-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 71.08 | 0.00 |
August | 13539.67 | 27-AUG-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 0.00 |
September | 13805.46 | 24-SEP-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 0.00 |
October | 13794.59 | 09-OCT-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
November | 13616.44 | 11-NOV-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 |
December | 6397.28 | 08-DEC-14:10 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4618.09 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13805.46 | 1306.65 | 496.34 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 124.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1117.83 | 20-JAN-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.43 |
February | 4429.21 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
March | 6427.28 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 |
April | 12029.44 | 09-APR-17:42 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
May | 12810.52 | 21-MAY-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
June | 12459.78 | 25-JUN-16:12 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 87.97 | 0.00 |
July | 12865.24 | 30-JUL-17:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | 0.00 |
August | 12784.04 | 13-AUG-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 0.00 |
September | 11288.25 | 04-SEP-17:03 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 | 0.00 |
October | 11193.70 | 09-OCT-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 0.00 |
November | 4106.00 | 06-NOV-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 |
December | 1692.97 | 11-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1117.83 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12865.24 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 87.97 | 30.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1519.89 | 31-JAN-16:30 | 1272.23 | 542.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
February | 1740.90 | 28-FEB-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 0.00 |
March | 2777.02 | 30-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
April | 3038.01 | 19-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
May | 4601.99 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.29 | 0.00 |
June | 5373.73 | 26-JUN-06:03 | 803.52 | 886.59 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
July | 6795.21 | 17-JUL-06:03 | 803.52 | 547.88 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
August | 6610.68 | 07-AUG-06:03 | 803.52 | 996.42 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 |
September | 5570.78 | 06-SEP-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
October | 4137.44 | 02-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 0.00 |
November | 2182.27 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
December | 1710.59 | 13-DEC-13:30 | 1272.23 | 538.55 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1519.89 | 803.52 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6795.21 | 1306.65 | 996.42 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 9.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1016.36 | 31-JAN-14:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
February | 2124.08 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 |
March | 2765.75 | 14-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 |
April | 4392.63 | 17-APR-10:10 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
May | 5429.81 | 30-MAY-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 0.00 |
June | 9796.58 | 04-JUN-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
July | 9805.12 | 04-JUL-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
August | 9840.91 | 06-AUG-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
September | 9369.92 | 24-SEP-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
October | 4638.36 | 10-OCT-10:20 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
November | 2704.54 | 06-NOV-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 |
December | 1121.75 | 13-DEC-12:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1016.36 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9840.91 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 20.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2881.96 | 28-JAN-14:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 |
February | 10719.75 | 26-FEB-15:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 |
March | 7795.91 | 30-MAR-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 2811.36 | 0.00 |
April | 7858.30 | 17-APR-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3713.84 | 0.00 |
May | 8761.14 | 30-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4101.66 | 0.00 |
June | 9446.26 | 06-JUN-16:30 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6719.02 | 0.00 |
July | 9852.44 | 07-JUL-16:50 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 7273.21 | 0.00 |
August | 10810.17 | 06-AUG-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 86.60 | 0.00 |
September | 11114.97 | 24-SEP-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 0.00 |
October | 11360.93 | 09-OCT-14:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
November | 10851.83 | 12-NOV-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.47 |
December | 6665.97 | 10-DEC-14:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2881.96 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11360.93 | 687.71 | 496.34 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7273.21 | 47.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1063.90 | 23-JAN-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 |
February | 3253.24 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
March | 4400.69 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
April | 4933.52 | 17-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
May | 9814.88 | 29-MAY-17:32 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 0.00 |
June | 10178.41 | 11-JUN-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 0.00 |
July | 10450.44 | 04-JUL-17:52 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 0.00 |
August | 10261.42 | 13-AUG-16:51 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | 0.00 |
September | 9659.52 | 04-SEP-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 0.00 |
October | 8423.53 | 09-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 0.00 |
November | 4075.96 | 06-NOV-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 |
December | 1674.04 | 11-DEC-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1063.90 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10450.44 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 | 25.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1603.47 | 31-JAN-16:40 | 1272.23 | 558.14 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 |
February | 2754.46 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 | 0.00 |
March | 4188.01 | 30-MAR-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 0.00 |
April | 4588.04 | 18-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
May | 5885.79 | 30-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 0.00 |
June | 7223.07 | 26-JUN-06:03 | 803.52 | 892.49 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
July | 9490.82 | 16-JUL-13:02 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 0.00 |
August | 7665.52 | 14-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
September | 5692.11 | 06-SEP-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 0.00 |
October | 4200.87 | 02-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 0.00 |
November | 2303.64 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 |
December | 1751.04 | 13-DEC-13:30 | 1272.23 | 542.86 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1603.47 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9490.82 | 1306.65 | 892.49 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 17.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1153.24 | 31-JAN-15:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 |
February | 4439.17 | 23-FEB-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.32 |
March | 5452.84 | 15-MAR-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 |
April | 7112.49 | 17-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
May | 11098.79 | 07-MAY-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 |
June | 11372.45 | 04-JUN-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
July | 11638.71 | 09-JUL-10:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
August | 11389.29 | 27-AUG-10:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
September | 10719.74 | 04-SEP-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
October | 6006.36 | 10-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
November | 4002.33 | 28-NOV-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 |
December | 3026.34 | 14-DEC-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1153.24 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11638.71 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 62.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4975.37 | 27-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 |
February | 11197.22 | 26-FEB-13:13 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.37 |
March | 9054.72 | 30-MAR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 |
April | 10131.52 | 16-APR-13:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 0.00 |
May | 7109.09 | 30-MAY-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 0.00 |
June | 9646.92 | 25-JUN-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 58.94 | 0.00 |
July | 11270.98 | 16-JUL-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 0.00 |
August | 11754.95 | 06-AUG-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 130.75 | 0.00 |
September | 12106.46 | 24-SEP-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 0.00 |
October | 12215.17 | 09-OCT-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 |
November | 12246.65 | 11-NOV-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.69 |
December | 6942.27 | 08-DEC-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4975.37 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12246.65 | 1306.65 | 496.34 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 130.75 | 112.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1122.57 | 20-JAN-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 |
February | 4330.02 | 27-FEB-17:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
March | 6005.60 | 30-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
April | 11035.95 | 09-APR-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.40 |
May | 11412.77 | 29-MAY-17:32 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 | 0.00 |
June | 11741.06 | 11-JUN-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.42 | 0.00 |
July | 11907.59 | 02-JUL-17:42 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 0.00 |
August | 11682.83 | 13-AUG-16:51 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
September | 11098.46 | 04-SEP-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 |
October | 9576.30 | 09-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 0.00 |
November | 4237.85 | 06-NOV-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
December | 1918.65 | 11-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1122.57 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11907.59 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.42 | 20.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.150365E+12 | 234037.50 | 09-JAN-07:10 | 0.00 | 0.00 |
February | 0.117999E+12 | 237229.50 | 13-FEB-07:10 | 0.00 | 0.00 |
March | 0.112079E+12 | 110404.42 | 30-MAR-15:20 | 0.00 | 0.00 |
April | 0.109335E+12 | 112870.88 | 17-APR-15:30 | 0.00 | 0.00 |
May | 0.128967E+12 | 129426.11 | 30-MAY-15:09 | 0.00 | 0.00 |
June | 0.146849E+12 | 137261.75 | 19-JUN-15:00 | 0.00 | 0.00 |
July | 0.153258E+12 | 149581.71 | 07-JUL-15:00 | 0.00 | 0.00 |
August | 0.166462E+12 | 148578.61 | 01-AUG-15:30 | 0.00 | 0.00 |
September | 0.130888E+12 | 141017.96 | 07-SEP-15:00 | 0.00 | 0.00 |
October | 0.113305E+12 | 123266.68 | 10-OCT-15:30 | 0.00 | 0.00 |
November | 0.106273E+12 | 150378.83 | 22-NOV-07:10 | 0.00 | 0.00 |
December | 0.117149E+12 | 198960.67 | 18-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.155293E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.106273E+12 | 110404.42 | 0.00 | 0.00 | |
Maximum of Months | 0.166462E+12 | 237229.50 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.198175E+11 | 0.544208E+10 | 0.605851E+11 | 0.225727E+10 | 0.323044E+10 | 12379742.02 | 0.531890E+11 | 0.121675E+10 | 0.00 | 0.00 | 0.00 | 0.461464E+10 | 0.00 |
February | 0.179794E+11 | 0.447543E+10 | 0.548702E+11 | 0.204819E+10 | 0.306782E+10 | 11196021.66 | 0.281621E+11 | 0.318758E+10 | 0.00 | 0.00 | 0.00 | 0.419681E+10 | 0.00 |
March | 0.208723E+11 | 0.443078E+10 | 0.627783E+11 | 0.235485E+10 | 0.396130E+10 | 12675672.10 | 0.343743E+10 | 0.944176E+10 | 0.00 | 0.00 | 0.00 | 0.478974E+10 | 0.00 |
April | 0.184586E+11 | 0.378945E+10 | 0.586172E+11 | 0.219176E+10 | 0.441015E+10 | 11960507.72 | 0.118440E+10 | 0.166023E+11 | 0.00 | 0.00 | 0.00 | 0.406894E+10 | 0.00 |
May | 0.197872E+11 | 0.345949E+10 | 0.616817E+11 | 0.230565E+10 | 0.613428E+10 | 12527707.06 | 0.152841E+09 | 0.314007E+11 | 0.00 | 0.00 | 0.00 | 0.403265E+10 | 0.00 |
June | 0.196404E+11 | 0.317507E+10 | 0.604966E+11 | 0.226788E+10 | 0.852872E+10 | 12231776.97 | 20522924.30 | 0.490012E+11 | 0.00 | 0.00 | 0.00 | 0.370649E+10 | 0.00 |
July | 0.184155E+11 | 0.336986E+10 | 0.597911E+11 | 0.222868E+10 | 0.934013E+10 | 12256437.81 | 0.00 | 0.567530E+11 | 0.00 | 0.00 | 0.00 | 0.334719E+10 | 0.00 |
August | 0.206313E+11 | 0.373343E+10 | 0.627783E+11 | 0.235465E+10 | 0.103739E+11 | 12675672.10 | 0.00 | 0.629099E+11 | 0.00 | 0.00 | 0.00 | 0.366739E+10 | 0.00 |
September | 0.185961E+11 | 0.405491E+10 | 0.585950E+11 | 0.219061E+10 | 0.706229E+10 | 11960507.72 | 19142235.07 | 0.368953E+11 | 0.00 | 0.00 | 0.00 | 0.346312E+10 | 0.00 |
October | 0.196424E+11 | 0.470282E+10 | 0.605962E+11 | 0.225781E+10 | 0.478162E+10 | 12379742.02 | 0.145989E+10 | 0.160067E+11 | 0.00 | 0.00 | 0.00 | 0.384536E+10 | 0.00 |
November | 0.195059E+11 | 0.511872E+10 | 0.591197E+11 | 0.219997E+10 | 0.347596E+10 | 12059151.09 | 0.631885E+10 | 0.643499E+10 | 0.00 | 0.00 | 0.00 | 0.408662E+10 | 0.00 |
December | 0.192055E+11 | 0.559902E+10 | 0.597800E+11 | 0.222855E+10 | 0.314650E+10 | 12256437.81 | 0.205359E+11 | 0.231540E+10 | 0.00 | 0.00 | 0.00 | 0.432568E+10 | 0.00 |
Annual Sum or Average | 0.232552E+12 | 0.513511E+11 | 0.719689E+12 | 0.268859E+11 | 0.675131E+11 | 0.146559E+09 | 0.114480E+12 | 0.292165E+12 | 0.00 | 0.00 | 0.00 | 0.481446E+11 | 0.00 |
Minimum of Months | 0.179794E+11 | 0.317507E+10 | 0.548702E+11 | 0.204819E+10 | 0.306782E+10 | 11196021.66 | 0.00 | 0.121675E+10 | 0.00 | 0.00 | 0.00 | 0.334719E+10 | 0.00 |
Maximum of Months | 0.208723E+11 | 0.559902E+10 | 0.627783E+11 | 0.235485E+10 | 0.103739E+11 | 12675672.10 | 0.531890E+11 | 0.629099E+11 | 0.00 | 0.00 | 0.00 | 0.478974E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 24030.94 | 03-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:20 | 5284.91 | 09-JAN-07:10 | 6.85 | 03-JAN-18:10 | 189309.27 | 09-JAN-07:10 |
February | 24713.90 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:09 | 4952.88 | 13-FEB-07:10 | 6.85 | 02-FEB-06:10 | 192831.40 | 13-FEB-07:10 |
March | 24169.18 | 21-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 06-MAR-08:09 | 8273.03 | 30-MAR-15:00 | 6.85 | 06-MAR-08:09 | 63611.20 | 23-MAR-06:10 |
April | 23249.44 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 06-APR-16:10 | 9082.29 | 17-APR-15:50 | 6.85 | 01-APR-05:10 | 56627.80 | 06-APR-06:10 |
May | 20676.82 | 24-MAY-07:30 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-07:10 | 12011.75 | 30-MAY-14:00 | 6.85 | 01-MAY-05:10 | 11242.41 | 11-MAY-06:10 |
June | 20258.51 | 23-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 12467.00 | 26-JUN-15:30 | 6.85 | 01-JUN-05:10 | 3780.18 | 08-JUN-06:19 |
July | 21397.89 | 27-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:10 | 14055.10 | 10-JUL-15:30 | 6.85 | 09-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 22850.66 | 24-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-11:09 | 14740.47 | 02-AUG-15:50 | 6.85 | 13-AUG-16:19 | 0.00 | 01-AUG-00:10 |
September | 23601.02 | 29-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-07:10 | 13835.63 | 07-SEP-15:30 | 6.85 | 01-SEP-05:10 | 3940.39 | 29-SEP-06:19 |
October | 24978.45 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 24-OCT-11:09 | 10670.41 | 10-OCT-15:30 | 6.85 | 26-OCT-07:10 | 58856.18 | 26-OCT-06:10 |
November | 24819.27 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 13-NOV-12:09 | 5729.30 | 06-NOV-15:30 | 6.85 | 13-NOV-12:09 | 108292.23 | 22-NOV-07:10 |
December | 24050.81 | 06-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 3726.56 | 04-DEC-07:10 | 6.85 | 04-DEC-12:09 | 155843.73 | 18-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20258.51 | 5686.19 | 41699.26 | 1410.29 | 3726.56 | 6.85 | 0.00 | |||||||
Maximum of Months | 24978.45 | 5686.19 | 41699.26 | 1410.29 | 14740.47 | 6.85 | 192831.40 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 12114.25 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 6214.22 | 31-JAN-12:39 | 0.00 |
February | 19192.35 | 28-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6214.22 | 02-FEB-12:30 | 0.00 |
March | 35125.14 | 30-MAR-15:20 | 0.00 | 0.00 | 0.00 | 6181.44 | 03-MAR-12:39 | 0.00 |
April | 37465.25 | 17-APR-13:00 | 0.00 | 0.00 | 0.00 | 5783.50 | 03-APR-11:50 | 0.00 |
May | 51535.71 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 5375.55 | 01-MAY-11:50 | 0.00 |
June | 58805.34 | 27-JUN-15:00 | 0.00 | 0.00 | 0.00 | 4970.88 | 01-JUN-11:50 | 0.00 |
July | 69402.51 | 07-JUL-15:00 | 0.00 | 0.00 | 0.00 | 4599.00 | 03-JUL-11:30 | 0.00 |
August | 68069.42 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 4595.97 | 31-AUG-11:39 | 0.00 |
September | 61088.18 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 4957.59 | 29-SEP-11:50 | 0.00 |
October | 46065.65 | 10-OCT-15:00 | 0.00 | 0.00 | 0.00 | 5361.66 | 31-OCT-11:39 | 0.00 |
November | 19125.74 | 02-NOV-14:09 | 0.00 | 0.00 | 0.00 | 5776.33 | 30-NOV-12:00 | 0.00 |
December | 18138.24 | 12-DEC-13:00 | 0.00 | 0.00 | 0.00 | 6057.06 | 27-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12114.25 | 0.00 | 0.00 | 0.00 | 4595.97 | 0.00 | ||
Maximum of Months | 69402.51 | 0.00 | 0.00 | 0.00 | 6214.22 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 234037.50 | 09-JAN-07:10 | 8334.71 | 22496.85 | 5686.19 | 974.52 | 5284.91 | 6.85 | 189309.27 | 0.00 | 0.00 |
February | 237229.50 | 13-FEB-07:10 | 8334.71 | 22496.85 | 5686.19 | 974.52 | 4952.88 | 6.85 | 192831.40 | 0.00 | 0.00 |
March | 110404.42 | 30-MAR-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 8116.93 | 6.85 | 0.00 | 35125.14 | 0.00 |
April | 112870.88 | 17-APR-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 9064.73 | 6.85 | 0.00 | 36865.12 | 0.00 |
May | 129426.11 | 30-MAY-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 11926.99 | 6.85 | 0.00 | 50882.55 | 0.00 |
June | 137261.75 | 19-JUN-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 12250.84 | 6.85 | 0.00 | 58580.23 | 0.00 |
July | 149581.71 | 07-JUL-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13946.98 | 6.85 | 0.00 | 69402.51 | 0.00 |
August | 148578.61 | 01-AUG-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 14342.03 | 6.85 | 0.00 | 67953.41 | 0.00 |
September | 141017.96 | 07-SEP-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13630.98 | 6.85 | 0.00 | 61088.18 | 0.00 |
October | 123266.68 | 10-OCT-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 10670.41 | 6.85 | 0.00 | 45960.31 | 0.00 |
November | 150378.83 | 22-NOV-07:10 | 8334.71 | 22496.85 | 5686.19 | 974.52 | 2925.11 | 6.85 | 108292.23 | 0.00 | 0.00 |
December | 198960.67 | 18-DEC-07:10 | 8334.71 | 22496.85 | 5686.19 | 974.52 | 3671.92 | 6.85 | 155843.73 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 110404.42 | 8334.71 | 22496.85 | 0.00 | 974.52 | 2925.11 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 237229.50 | 19671.42 | 41670.51 | 5686.19 | 1410.29 | 14342.03 | 6.85 | 192831.40 | 69402.51 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.41 | 0.50 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
February | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 1.00 | 18.72 | 0.83 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.43 | 0.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 17.23 | 4.67 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
February | 7.67 | 16.50 | 3.50 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.44 | 0.83 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 2.33 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.50 | 18.28 | 1.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 19.00 | 17.07 | 9.83 | 17.52 | 6.00 | 19.24 | 4.17 | 20.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 18.28 | 4.67 | 18.72 | 3.67 | 27.54 | 2.33 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 15.94 | 1.33 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
February | 5.00 | 15.47 | 0.83 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.53 | 4.17 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.70 | 7.50 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.75 | 11.33 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.73 | 8.50 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 17.29 | 0.50 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
Annual Sum or Average | 12.83 | 15.86 | 2.67 | 16.06 | 38.00 | 24.33 | 34.00 | 25.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 17.29 | 1.33 | 17.47 | 13.50 | 27.75 | 11.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 16.87 | 1.50 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
February | 3.50 | 15.82 | 1.00 | 15.90 | 1.00 | 18.01 | 1.00 | 19.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.45 | 2.67 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.52 | 6.33 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.68 | 5.33 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.58 | 3.17 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.71 | 3.83 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.52 | 2.17 | 27.52 |
December | 0.67 | 17.93 | 0.33 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
Annual Sum or Average | 8.83 | 16.53 | 2.83 | 16.81 | 29.17 | 24.50 | 26.50 | 25.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 17.93 | 1.50 | 18.31 | 7.67 | 27.71 | 6.33 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.99 | 1.50 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 4.67 | 15.34 | 1.33 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.67 | 2.00 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 2.00 | 27.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.97 | 3.83 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.08 | 6.00 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.04 | 4.33 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.67 | 3.00 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.17 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 17.90 | 0.33 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
Annual Sum or Average | 11.83 | 15.84 | 3.17 | 15.96 | 40.33 | 24.69 | 22.33 | 25.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 17.90 | 1.50 | 18.34 | 12.00 | 28.08 | 6.00 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.85 | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 0.67 | 18.99 | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 18.92 | 1.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.99 | 0.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 0.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.58 | 3.00 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.55 | 7.33 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.56 | 5.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 1.67 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.15 | 0.00 | 17.15 | 18.17 | 27.36 | 18.17 | 27.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.18 | 0.00 | 17.18 | 7.33 | 27.58 | 7.33 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.50 | 18.13 | 45.50 | 18.13 | 0.00 | 18.13 | 0.00 | 18.13 |
February | 30.17 | 18.34 | 30.17 | 18.34 | 0.50 | 18.42 | 0.50 | 18.49 |
March | 11.17 | 19.51 | 11.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
April | 4.33 | 18.70 | 4.33 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.70 | 5.00 | 24.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 24.92 | 14.67 | 24.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 25.31 | 25.00 | 25.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.31 | 8.67 | 25.31 |
October | 2.00 | 19.46 | 2.00 | 19.46 | 9.83 | 24.17 | 9.83 | 24.96 |
November | 10.83 | 19.49 | 10.83 | 19.49 | 2.17 | 20.22 | 2.17 | 20.83 |
December | 20.50 | 18.48 | 20.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
Annual Sum or Average | 124.50 | 18.52 | 124.50 | 18.52 | 65.83 | 19.96 | 65.83 | 20.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.50 | 19.51 | 45.50 | 19.51 | 25.00 | 25.31 | 25.00 | 25.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
February | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.47 | 1.00 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.64 | 2.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.78 | 4.17 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.77 | 3.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.00 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 0.83 | 27.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 17.18 | 0.00 | 17.18 | 24.17 | 27.54 | 13.50 | 27.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.20 | 0.00 | 17.20 | 7.83 | 27.78 | 4.17 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.78 | 1.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 1.00 | 18.66 | 0.67 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.34 | 1.17 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 18.74 | 1.83 | 19.04 | 1.33 | 20.99 | 1.17 | 22.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 18.78 | 1.17 | 19.06 | 1.33 | 27.34 | 1.17 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.92 | 0.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
February | 0.17 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.60 | 0.83 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 3.67 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.68 | 5.67 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.66 | 10.50 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.67 | 7.00 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.57 | 2.17 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.68 | 0.33 | 18.12 | 30.50 | 27.29 | 29.83 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.92 | 0.33 | 18.36 | 10.83 | 27.68 | 10.50 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.96 | 0.33 | 18.38 | 0.17 | 19.65 | 0.17 | 20.60 |
February | 0.17 | 17.01 | 0.00 | 17.01 | 1.17 | 26.23 | 1.17 | 26.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.40 | 3.00 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.52 | 4.67 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.51 | 2.50 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.65 | 4.50 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.77 | 0.33 | 18.18 | 20.00 | 27.02 | 19.83 | 27.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.96 | 0.33 | 18.38 | 4.83 | 27.65 | 4.67 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 17.90 | 0.33 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
February | 0.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 1.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.79 | 1.67 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 3.33 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.95 | 5.17 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.97 | 3.50 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.61 | 2.67 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.58 | 1.17 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 17.68 | 0.33 | 18.12 | 32.67 | 27.50 | 19.17 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.90 | 0.33 | 18.34 | 10.00 | 27.97 | 5.17 | 28.01 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.83 | 22.98 | 14.83 | 22.95 | 14.83 | 22.91 |
February | 374.50 | 23.40 | 9.50 | 23.44 | 0.00 | 23.44 |
March | 160.83 | 23.96 | 113.00 | 24.29 | 0.00 | 24.29 |
April | 42.33 | 23.99 | 223.50 | 24.65 | 0.00 | 24.65 |
May | 2.00 | 24.00 | 419.83 | 24.55 | 0.00 | 24.55 |
June | 0.00 | 0.00 | 451.33 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 497.00 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 514.00 | 24.42 | 0.00 | 24.42 |
September | 0.00 | 0.00 | 461.50 | 24.52 | 0.00 | 24.52 |
October | 15.33 | 23.89 | 244.67 | 24.71 | 0.00 | 24.71 |
November | 177.00 | 23.97 | 81.83 | 24.26 | 0.00 | 24.26 |
December | 417.00 | 23.73 | 17.67 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 1675.83 | 23.49 | 3048.67 | 24.17 | 14.83 | 24.16 |
Minimum of Months | 0.00 | 0.00 | 9.50 | 22.95 | 0.00 | 22.91 |
Maximum of Months | 486.83 | 24.00 | 514.00 | 24.71 | 14.83 | 24.71 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 154.17 | 21.12 | 154.17 | 21.02 |
February | 447.83 | 21.98 | 74.00 | 21.80 | 74.00 | 21.66 |
March | 402.50 | 23.15 | 34.83 | 23.23 | 0.00 | 23.23 |
April | 216.00 | 23.43 | 106.17 | 23.74 | 0.00 | 23.74 |
May | 46.67 | 23.52 | 270.67 | 24.19 | 0.00 | 24.19 |
June | 17.67 | 23.68 | 396.83 | 24.26 | 0.00 | 24.26 |
July | 5.67 | 23.29 | 470.83 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 501.67 | 24.28 | 0.00 | 24.28 |
September | 19.00 | 23.18 | 349.00 | 24.30 | 0.00 | 24.30 |
October | 236.67 | 23.16 | 102.00 | 23.49 | 0.00 | 23.49 |
November | 439.83 | 22.99 | 0.00 | 22.99 | 0.00 | 22.99 |
December | 488.50 | 21.94 | 22.67 | 21.90 | 21.67 | 21.86 |
Annual Sum or Average | 2822.33 | 22.43 | 2482.83 | 23.14 | 249.83 | 23.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 | 21.02 |
Maximum of Months | 502.00 | 23.68 | 501.67 | 24.31 | 154.17 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.71 | 314.50 | 20.54 | 314.50 | 20.47 |
February | 450.83 | 21.38 | 141.17 | 21.13 | 141.17 | 20.98 |
March | 441.50 | 22.62 | 43.67 | 22.67 | 12.33 | 22.62 |
April | 262.67 | 23.10 | 88.50 | 23.39 | 0.00 | 23.39 |
May | 93.17 | 23.38 | 260.00 | 24.02 | 0.00 | 24.02 |
June | 28.50 | 23.49 | 391.67 | 24.24 | 0.00 | 24.24 |
July | 12.00 | 23.16 | 464.83 | 24.32 | 0.00 | 24.32 |
August | 0.00 | 0.00 | 494.83 | 24.30 | 0.00 | 24.30 |
September | 67.83 | 23.14 | 293.67 | 24.10 | 0.00 | 24.10 |
October | 341.33 | 22.73 | 72.00 | 22.97 | 0.50 | 22.97 |
November | 477.50 | 22.16 | 33.33 | 22.06 | 33.33 | 21.96 |
December | 494.17 | 21.17 | 178.50 | 20.96 | 178.50 | 20.84 |
Annual Sum or Average | 3171.50 | 21.94 | 2776.67 | 22.59 | 680.33 | 22.36 |
Minimum of Months | 0.00 | 0.00 | 33.33 | 20.54 | 0.00 | 20.47 |
Maximum of Months | 502.00 | 23.49 | 494.83 | 24.32 | 314.50 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 413.83 | 20.06 | 413.83 | 20.02 |
February | 450.17 | 20.80 | 245.83 | 20.56 | 245.83 | 20.44 |
March | 450.50 | 21.90 | 110.17 | 21.84 | 73.50 | 21.67 |
April | 283.67 | 22.53 | 117.83 | 22.90 | 16.67 | 22.81 |
May | 112.83 | 23.01 | 285.17 | 23.93 | 0.00 | 23.93 |
June | 37.67 | 24.03 | 411.00 | 24.34 | 11.00 | 24.39 |
July | 32.83 | 25.26 | 474.17 | 24.53 | 25.17 | 24.59 |
August | 21.83 | 25.67 | 500.33 | 24.43 | 18.67 | 24.49 |
September | 123.67 | 23.29 | 294.67 | 24.05 | 17.00 | 24.10 |
October | 385.17 | 22.09 | 92.33 | 22.36 | 25.17 | 22.34 |
November | 480.33 | 21.39 | 141.50 | 21.15 | 141.50 | 20.99 |
December | 497.00 | 20.49 | 326.00 | 20.30 | 326.00 | 20.22 |
Annual Sum or Average | 3377.67 | 21.46 | 3412.83 | 22.14 | 1314.33 | 21.86 |
Minimum of Months | 21.83 | 20.16 | 92.33 | 20.06 | 0.00 | 20.02 |
Maximum of Months | 502.00 | 25.67 | 500.33 | 24.53 | 413.83 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 371.67 | 20.22 | 371.67 | 20.15 |
February | 435.83 | 21.14 | 201.67 | 20.82 | 201.67 | 20.65 |
March | 378.83 | 22.31 | 93.33 | 22.36 | 37.83 | 22.21 |
April | 180.17 | 22.63 | 179.00 | 23.43 | 9.33 | 23.38 |
May | 87.00 | 23.60 | 353.50 | 24.29 | 12.50 | 24.37 |
June | 47.17 | 25.59 | 451.00 | 24.55 | 32.50 | 24.68 |
July | 70.33 | 26.17 | 478.67 | 24.78 | 62.50 | 24.97 |
August | 48.67 | 26.46 | 506.17 | 24.63 | 47.17 | 24.78 |
September | 100.00 | 23.64 | 343.50 | 24.27 | 25.00 | 24.36 |
October | 297.83 | 22.24 | 146.50 | 22.81 | 23.17 | 22.78 |
November | 459.33 | 21.78 | 97.00 | 21.57 | 90.33 | 21.39 |
December | 493.17 | 20.72 | 264.17 | 20.46 | 264.17 | 20.33 |
Annual Sum or Average | 3100.33 | 21.79 | 3486.17 | 22.55 | 1177.83 | 22.33 |
Minimum of Months | 47.17 | 20.37 | 93.33 | 20.22 | 9.33 | 20.15 |
Maximum of Months | 502.00 | 26.46 | 506.17 | 24.78 | 371.67 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.00 | 20.99 | 274.83 | 20.65 | 271.17 | 20.47 |
February | 395.83 | 21.35 | 181.00 | 21.18 | 162.17 | 20.98 |
March | 327.67 | 22.13 | 131.50 | 22.43 | 44.50 | 22.25 |
April | 218.17 | 22.56 | 166.17 | 23.26 | 14.17 | 23.20 |
May | 114.17 | 23.03 | 296.50 | 23.99 | 1.50 | 24.00 |
June | 51.00 | 24.14 | 403.83 | 24.35 | 16.33 | 24.42 |
July | 45.17 | 25.72 | 467.83 | 24.60 | 37.83 | 24.72 |
August | 36.50 | 26.18 | 501.50 | 24.54 | 33.17 | 24.65 |
September | 108.67 | 23.70 | 327.67 | 24.28 | 27.50 | 24.39 |
October | 267.33 | 22.37 | 190.33 | 23.19 | 27.00 | 23.25 |
November | 368.00 | 21.91 | 125.67 | 22.02 | 74.33 | 21.83 |
December | 439.00 | 21.20 | 202.17 | 20.91 | 190.33 | 20.70 |
Annual Sum or Average | 2850.50 | 21.95 | 3269.00 | 22.76 | 900.00 | 22.54 |
Minimum of Months | 36.50 | 20.99 | 125.67 | 20.65 | 1.50 | 20.47 |
Maximum of Months | 479.00 | 26.18 | 501.50 | 24.60 | 271.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 357.33 | 20.22 | 357.33 | 20.13 |
February | 431.00 | 20.99 | 219.17 | 20.75 | 212.67 | 20.60 |
March | 370.67 | 21.95 | 133.83 | 22.13 | 59.33 | 21.94 |
April | 228.33 | 22.61 | 175.33 | 23.29 | 17.33 | 23.28 |
May | 110.67 | 23.35 | 325.50 | 24.12 | 10.67 | 24.19 |
June | 54.67 | 24.70 | 424.17 | 24.45 | 25.00 | 24.56 |
July | 49.17 | 25.86 | 471.17 | 24.65 | 42.50 | 24.78 |
August | 36.50 | 26.25 | 503.83 | 24.56 | 33.83 | 24.68 |
September | 116.17 | 23.73 | 323.83 | 24.26 | 31.50 | 24.38 |
October | 326.50 | 22.15 | 139.17 | 22.74 | 24.17 | 22.75 |
November | 435.67 | 21.55 | 129.50 | 21.37 | 116.00 | 21.18 |
December | 491.17 | 20.76 | 273.83 | 20.48 | 273.83 | 20.35 |
Annual Sum or Average | 3152.50 | 21.68 | 3476.67 | 22.44 | 1204.17 | 22.21 |
Minimum of Months | 36.50 | 20.43 | 129.50 | 20.22 | 10.67 | 20.13 |
Maximum of Months | 502.00 | 26.25 | 503.83 | 24.65 | 357.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 396.00 | 20.44 | 396.00 | 20.41 |
February | 454.00 | 20.97 | 210.50 | 20.77 | 210.50 | 20.67 |
March | 488.00 | 21.89 | 55.17 | 21.80 | 47.50 | 21.70 |
April | 399.67 | 22.53 | 38.33 | 22.62 | 7.17 | 22.58 |
May | 177.17 | 23.13 | 212.33 | 23.73 | 0.00 | 23.73 |
June | 26.67 | 23.71 | 402.17 | 24.24 | 2.67 | 24.25 |
July | 13.50 | 24.65 | 477.33 | 24.40 | 8.33 | 24.42 |
August | 5.83 | 26.08 | 509.17 | 24.35 | 5.83 | 24.37 |
September | 56.83 | 23.95 | 361.83 | 24.29 | 15.83 | 24.34 |
October | 339.67 | 22.89 | 101.67 | 23.18 | 6.00 | 23.21 |
November | 466.17 | 22.24 | 34.33 | 22.19 | 26.67 | 22.11 |
December | 497.00 | 21.07 | 210.83 | 20.92 | 210.83 | 20.83 |
Annual Sum or Average | 3426.50 | 21.80 | 3009.67 | 22.43 | 937.33 | 22.20 |
Minimum of Months | 5.83 | 20.52 | 34.33 | 20.44 | 0.00 | 20.41 |
Maximum of Months | 502.00 | 26.08 | 509.17 | 24.40 | 396.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.77 | 330.67 | 20.63 | 330.67 | 20.57 |
February | 443.00 | 21.43 | 165.50 | 21.15 | 165.50 | 21.00 |
March | 427.50 | 22.56 | 52.33 | 22.60 | 16.17 | 22.53 |
April | 262.50 | 22.90 | 113.50 | 23.32 | 2.83 | 23.30 |
May | 92.50 | 23.29 | 317.50 | 24.20 | 2.17 | 24.21 |
June | 19.33 | 25.48 | 451.67 | 24.46 | 11.50 | 24.51 |
July | 36.67 | 26.20 | 482.83 | 24.69 | 31.67 | 24.80 |
August | 23.00 | 26.82 | 513.00 | 24.56 | 23.00 | 24.65 |
September | 49.83 | 24.46 | 415.00 | 24.47 | 20.83 | 24.54 |
October | 207.83 | 22.98 | 177.00 | 23.65 | 7.33 | 23.67 |
November | 413.17 | 22.75 | 35.17 | 22.81 | 7.67 | 22.77 |
December | 487.00 | 21.45 | 111.83 | 21.28 | 111.83 | 21.15 |
Annual Sum or Average | 2964.33 | 22.14 | 3166.00 | 22.92 | 731.17 | 22.74 |
Minimum of Months | 19.33 | 20.77 | 35.17 | 20.63 | 2.17 | 20.57 |
Maximum of Months | 502.00 | 26.82 | 513.00 | 24.69 | 330.67 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.67 | 20.90 | 245.00 | 20.62 | 240.00 | 20.46 |
February | 406.17 | 21.23 | 149.67 | 21.06 | 135.50 | 20.85 |
March | 390.17 | 22.15 | 84.00 | 22.37 | 24.67 | 22.26 |
April | 323.50 | 22.48 | 95.00 | 22.82 | 11.67 | 22.75 |
May | 188.17 | 22.84 | 234.83 | 23.63 | 13.50 | 23.62 |
June | 89.00 | 23.56 | 401.33 | 24.15 | 49.33 | 24.13 |
July | 75.50 | 24.05 | 478.50 | 24.38 | 69.17 | 24.35 |
August | 86.83 | 24.44 | 511.00 | 24.45 | 85.83 | 24.45 |
September | 91.83 | 23.92 | 405.00 | 24.39 | 46.83 | 24.44 |
October | 213.00 | 22.82 | 230.00 | 23.72 | 29.83 | 23.79 |
November | 323.50 | 22.47 | 82.83 | 22.91 | 8.33 | 22.87 |
December | 438.17 | 21.57 | 88.83 | 21.51 | 63.00 | 21.32 |
Annual Sum or Average | 3115.50 | 22.11 | 3006.00 | 22.91 | 777.67 | 22.77 |
Minimum of Months | 75.50 | 20.90 | 82.83 | 20.62 | 8.33 | 20.46 |
Maximum of Months | 489.67 | 24.44 | 511.00 | 24.45 | 240.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 324.67 | 20.61 | 324.67 | 20.54 |
February | 440.50 | 21.26 | 170.83 | 21.04 | 167.83 | 20.90 |
March | 410.17 | 22.33 | 69.50 | 22.49 | 17.83 | 22.43 |
April | 279.17 | 22.83 | 111.67 | 23.25 | 4.00 | 23.23 |
May | 107.50 | 23.31 | 297.67 | 24.09 | 2.50 | 24.11 |
June | 27.67 | 24.67 | 434.00 | 24.41 | 10.33 | 24.46 |
July | 30.00 | 25.97 | 481.67 | 24.59 | 25.50 | 24.68 |
August | 20.33 | 26.74 | 513.00 | 24.54 | 20.33 | 24.62 |
September | 55.33 | 24.55 | 410.83 | 24.48 | 24.17 | 24.56 |
October | 229.33 | 23.01 | 167.83 | 23.61 | 8.17 | 23.65 |
November | 401.50 | 22.56 | 40.50 | 22.65 | 12.00 | 22.60 |
December | 484.83 | 21.39 | 133.67 | 21.20 | 133.17 | 21.08 |
Annual Sum or Average | 2988.33 | 22.05 | 3155.83 | 22.85 | 750.50 | 22.66 |
Minimum of Months | 20.33 | 20.78 | 40.50 | 20.61 | 2.50 | 20.54 |
Maximum of Months | 502.00 | 26.74 | 513.00 | 24.59 | 324.67 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 386.33 | 20.36 | 386.33 | 20.31 |
February | 450.00 | 21.10 | 184.33 | 20.84 | 184.33 | 20.69 |
March | 441.17 | 22.32 | 72.17 | 22.35 | 31.83 | 22.25 |
April | 258.00 | 22.85 | 111.83 | 23.25 | 3.83 | 23.23 |
May | 83.17 | 23.31 | 313.83 | 24.09 | 0.00 | 24.09 |
June | 19.17 | 24.18 | 425.67 | 24.34 | 6.17 | 24.36 |
July | 18.67 | 25.03 | 482.83 | 24.48 | 13.83 | 24.51 |
August | 9.00 | 25.76 | 508.50 | 24.39 | 9.00 | 24.42 |
September | 77.83 | 23.66 | 331.33 | 24.22 | 17.00 | 24.27 |
October | 358.67 | 22.58 | 92.50 | 22.88 | 11.67 | 22.90 |
November | 473.33 | 21.95 | 56.67 | 21.80 | 56.00 | 21.68 |
December | 493.17 | 20.89 | 242.50 | 20.70 | 242.50 | 20.61 |
Annual Sum or Average | 3184.17 | 21.75 | 3208.50 | 22.48 | 962.50 | 22.23 |
Minimum of Months | 9.00 | 20.47 | 56.67 | 20.36 | 0.00 | 20.31 |
Maximum of Months | 502.00 | 25.76 | 508.50 | 24.48 | 386.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.64 | 282.83 | 20.45 | 282.83 | 20.37 |
February | 363.33 | 21.34 | 143.33 | 21.08 | 138.83 | 20.90 |
March | 310.67 | 22.59 | 59.33 | 22.74 | 12.83 | 22.66 |
April | 154.83 | 22.98 | 146.83 | 23.71 | 4.67 | 23.71 |
May | 62.50 | 23.99 | 298.33 | 24.48 | 12.17 | 24.56 |
June | 31.33 | 25.95 | 381.83 | 24.64 | 23.83 | 24.75 |
July | 55.17 | 26.36 | 412.83 | 24.88 | 50.83 | 25.05 |
August | 36.00 | 26.65 | 430.50 | 24.71 | 36.00 | 24.85 |
September | 66.33 | 24.23 | 307.33 | 24.49 | 24.83 | 24.59 |
October | 238.17 | 22.65 | 126.33 | 23.26 | 12.50 | 23.28 |
November | 376.67 | 22.27 | 47.00 | 22.20 | 32.00 | 22.08 |
December | 413.83 | 21.11 | 165.50 | 20.86 | 165.50 | 20.72 |
Annual Sum or Average | 2535.83 | 22.08 | 2802.00 | 22.87 | 796.83 | 22.69 |
Minimum of Months | 31.33 | 20.64 | 47.00 | 20.45 | 4.67 | 20.37 |
Maximum of Months | 427.00 | 26.65 | 430.50 | 24.88 | 282.83 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.67 | 21.28 | 230.33 | 20.98 | 225.33 | 20.79 |
February | 386.83 | 21.68 | 128.83 | 21.57 | 109.00 | 21.36 |
March | 305.50 | 22.57 | 107.17 | 22.99 | 12.50 | 22.92 |
April | 190.00 | 22.91 | 167.50 | 23.61 | 4.17 | 23.60 |
May | 79.00 | 23.25 | 321.50 | 24.13 | 0.00 | 24.13 |
June | 31.33 | 24.14 | 421.17 | 24.34 | 8.33 | 24.38 |
July | 26.33 | 25.57 | 482.83 | 24.54 | 21.50 | 24.60 |
August | 27.33 | 26.52 | 509.00 | 24.52 | 27.33 | 24.62 |
September | 72.67 | 24.17 | 370.33 | 24.42 | 25.33 | 24.51 |
October | 230.50 | 22.85 | 209.67 | 23.63 | 19.67 | 23.72 |
November | 339.67 | 22.48 | 90.67 | 22.80 | 25.50 | 22.74 |
December | 414.67 | 21.60 | 125.83 | 21.44 | 108.33 | 21.24 |
Annual Sum or Average | 2565.50 | 22.24 | 3164.83 | 23.13 | 587.00 | 22.96 |
Minimum of Months | 26.33 | 21.28 | 90.67 | 20.98 | 0.00 | 20.79 |
Maximum of Months | 461.67 | 26.52 | 509.00 | 24.54 | 225.33 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 20.75 | 313.17 | 20.53 | 313.17 | 20.43 |
February | 430.00 | 21.30 | 161.50 | 21.07 | 155.33 | 20.89 |
March | 354.33 | 22.40 | 100.33 | 22.70 | 19.00 | 22.61 |
April | 195.33 | 22.96 | 191.00 | 23.66 | 7.00 | 23.67 |
May | 79.83 | 23.68 | 355.00 | 24.25 | 8.17 | 24.30 |
June | 38.33 | 25.15 | 440.50 | 24.48 | 21.00 | 24.57 |
July | 40.67 | 26.03 | 486.83 | 24.64 | 36.17 | 24.75 |
August | 27.33 | 26.59 | 510.00 | 24.55 | 27.33 | 24.65 |
September | 78.67 | 24.19 | 370.17 | 24.41 | 28.83 | 24.51 |
October | 293.67 | 22.66 | 146.17 | 23.23 | 14.00 | 23.27 |
November | 422.17 | 22.10 | 70.33 | 22.08 | 46.83 | 21.94 |
December | 484.00 | 21.16 | 189.50 | 20.92 | 188.67 | 20.78 |
Annual Sum or Average | 2945.83 | 21.98 | 3334.50 | 22.81 | 865.50 | 22.61 |
Minimum of Months | 27.33 | 20.75 | 70.33 | 20.53 | 7.00 | 20.43 |
Maximum of Months | 501.50 | 26.59 | 510.00 | 24.64 | 313.17 | 24.75 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.01340 | 26.46485 | -0.0577 | 5.78734 |
February | 454.00000 | 23.57923 | 27.42411 | 0.10637 | 6.03640 |
March | 514.00000 | 24.24896 | 30.68922 | 0.33459 | 7.63304 |
April | 485.00000 | 24.41061 | 35.75339 | 0.42626 | 9.14025 |
May | 508.00000 | 24.46380 | 42.45267 | -0.3413 | 8.04551 |
June | 496.00000 | 24.41527 | 44.29475 | -0.3141 | 7.60381 |
July | 497.00000 | 24.49796 | 45.98036 | -0.2721 | 7.14376 |
August | 514.00000 | 24.41848 | 46.29360 | -0.2868 | 7.22703 |
September | 485.00000 | 24.49029 | 44.86810 | -0.2952 | 7.47941 |
October | 502.00000 | 24.40937 | 37.99889 | 0.45010 | 9.54848 |
November | 489.00000 | 24.27120 | 28.76922 | 0.32334 | 7.48084 |
December | 497.00000 | 23.80673 | 28.33763 | 0.17099 | 5.97834 |
Annual Sum or Average | 5943.00000 | 24.17244 | 36.68556 | 0.01887 | 7.43331 |
Minimum of Months | 454.00000 | 23.01340 | 26.46485 | -0.3413 | 5.78734 |
Maximum of Months | 514.00000 | 24.49796 | 46.29360 | 0.45010 | 9.54848 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29553 | 28.54239 | -0.4462 | 10.03386 |
February | 454.00000 | 22.00572 | 29.48520 | -0.2486 | 7.90014 |
March | 514.00000 | 23.36506 | 32.82813 | 0.13034 | 6.15748 |
April | 485.00000 | 23.84526 | 37.40164 | 0.29273 | 7.25917 |
May | 508.00000 | 24.10619 | 43.42885 | -0.4725 | 10.06107 |
June | 496.00000 | 24.21838 | 45.24578 | -0.3968 | 8.68489 |
July | 497.00000 | 24.29034 | 47.15499 | -0.3547 | 7.99018 |
August | 514.00000 | 24.27135 | 47.50296 | -0.3529 | 7.90882 |
September | 485.00000 | 24.18956 | 45.90418 | -0.4184 | 9.12615 |
October | 502.00000 | 23.68486 | 40.38691 | 0.27004 | 7.10726 |
November | 489.00000 | 23.09742 | 31.63705 | 0.04645 | 5.84277 |
December | 497.00000 | 21.97144 | 31.52512 | -0.2419 | 7.21538 |
Annual Sum or Average | 5943.00000 | 23.37166 | 38.49244 | -0.1829 | 7.94237 |
Minimum of Months | 454.00000 | 21.29553 | 28.54239 | -0.4725 | 5.84277 |
Maximum of Months | 514.00000 | 24.29034 | 47.50296 | 0.29273 | 10.06107 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.70962 | 28.86596 | -0.6184 | 14.80320 |
February | 454.00000 | 21.40110 | 30.05842 | -0.4129 | 10.90887 |
March | 514.00000 | 22.81823 | 33.26868 | -0.0042 | 6.52339 |
April | 485.00000 | 23.57759 | 37.32291 | 0.22563 | 6.96877 |
May | 508.00000 | 24.01910 | 42.87253 | -0.5011 | 10.86326 |
June | 496.00000 | 24.20977 | 44.87304 | -0.3910 | 8.68375 |
July | 497.00000 | 24.30341 | 46.82903 | -0.3394 | 7.83278 |
August | 514.00000 | 24.28525 | 47.21945 | -0.3381 | 7.69604 |
September | 485.00000 | 24.05925 | 45.66991 | -0.4680 | 10.28556 |
October | 502.00000 | 23.15191 | 41.19420 | 0.13509 | 6.59179 |
November | 489.00000 | 22.20429 | 32.77194 | -0.1739 | 7.01996 |
December | 497.00000 | 21.18303 | 32.70340 | -0.4530 | 10.77262 |
Annual Sum or Average | 5943.00000 | 23.00590 | 38.70579 | -0.2778 | 9.06535 |
Minimum of Months | 454.00000 | 20.70962 | 28.86596 | -0.6184 | 6.52339 |
Maximum of Months | 514.00000 | 24.30341 | 47.21945 | 0.22563 | 14.80320 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16432 | 29.64935 | -0.8070 | 21.53080 |
February | 454.00000 | 20.83130 | 31.76168 | -0.5867 | 15.46383 |
March | 514.00000 | 22.16217 | 35.83106 | -0.1615 | 8.27015 |
April | 485.00000 | 23.20727 | 39.97450 | 0.14866 | 7.63093 |
May | 508.00000 | 23.94733 | 44.95603 | -0.4987 | 11.78846 |
June | 496.00000 | 24.26445 | 46.30263 | -0.3214 | 8.25168 |
July | 497.00000 | 24.43451 | 48.90399 | -0.2375 | 7.27323 |
August | 514.00000 | 24.36005 | 49.45522 | -0.2576 | 7.15589 |
September | 485.00000 | 23.97758 | 48.52334 | -0.4739 | 11.47462 |
October | 502.00000 | 22.53931 | 45.31157 | -0.0020 | 7.33127 |
November | 489.00000 | 21.43757 | 36.08757 | -0.3656 | 10.04334 |
December | 497.00000 | 20.49181 | 33.68090 | -0.6590 | 16.71056 |
Annual Sum or Average | 5943.00000 | 22.66590 | 40.93960 | -0.3504 | 11.04106 |
Minimum of Months | 454.00000 | 20.16432 | 29.64935 | -0.8070 | 7.15589 |
Maximum of Months | 514.00000 | 24.43451 | 49.45522 | 0.14866 | 21.53080 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36545 | 30.39712 | -0.7339 | 18.96259 |
February | 454.00000 | 21.26432 | 31.97432 | -0.4624 | 13.41295 |
March | 514.00000 | 22.77759 | 35.21181 | -0.0008 | 7.63373 |
April | 485.00000 | 23.64656 | 38.81856 | 0.28352 | 8.70309 |
May | 508.00000 | 24.18028 | 44.06924 | -0.3638 | 9.96898 |
June | 496.00000 | 24.37764 | 45.75916 | -0.2196 | 7.48343 |
July | 497.00000 | 24.54011 | 48.29589 | -0.1366 | 7.21995 |
August | 514.00000 | 24.44467 | 48.95406 | -0.1670 | 6.88576 |
September | 485.00000 | 24.13419 | 47.90449 | -0.3689 | 10.20582 |
October | 502.00000 | 23.03408 | 44.25454 | 0.13317 | 8.05394 |
November | 489.00000 | 21.92057 | 36.10611 | -0.2369 | 8.69707 |
December | 497.00000 | 20.73818 | 34.27510 | -0.5770 | 14.63517 |
Annual Sum or Average | 5943.00000 | 22.96548 | 40.56719 | -0.2362 | 10.12561 |
Minimum of Months | 454.00000 | 20.36545 | 30.39712 | -0.7339 | 6.88576 |
Maximum of Months | 514.00000 | 24.54011 | 48.95406 | 0.28352 | 18.96259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.14589 | 28.28701 | -0.5285 | 15.78337 |
February | 454.00000 | 21.76265 | 30.11839 | -0.3293 | 12.16522 |
March | 514.00000 | 22.92063 | 33.71980 | 0.04215 | 8.42289 |
April | 485.00000 | 23.49887 | 38.73148 | 0.23978 | 8.62652 |
May | 508.00000 | 23.97854 | 44.65560 | -0.4704 | 11.61037 |
June | 496.00000 | 24.24571 | 46.32691 | -0.3227 | 8.54888 |
July | 497.00000 | 24.44316 | 48.82770 | -0.2258 | 7.37691 |
August | 514.00000 | 24.39960 | 49.07613 | -0.2118 | 7.03163 |
September | 485.00000 | 24.12368 | 47.50438 | -0.3750 | 10.43330 |
October | 502.00000 | 23.24584 | 42.52367 | 0.20392 | 9.22231 |
November | 489.00000 | 22.54023 | 33.22140 | -0.0738 | 9.11604 |
December | 497.00000 | 21.55458 | 31.71881 | -0.3658 | 12.31831 |
Annual Sum or Average | 5943.00000 | 23.16582 | 39.63357 | -0.2010 | 10.03669 |
Minimum of Months | 454.00000 | 21.14589 | 28.28701 | -0.5285 | 7.03163 |
Maximum of Months | 514.00000 | 24.44316 | 49.07613 | 0.23978 | 15.78337 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42660 | 30.29119 | -0.7258 | 19.44867 |
February | 454.00000 | 21.16591 | 32.01760 | -0.4909 | 14.13054 |
March | 514.00000 | 22.59324 | 35.29822 | -0.0395 | 8.56065 |
April | 485.00000 | 23.46959 | 39.44283 | 0.24321 | 8.85494 |
May | 508.00000 | 24.04207 | 44.70731 | -0.4189 | 11.02619 |
June | 496.00000 | 24.30658 | 46.29117 | -0.2585 | 8.15318 |
July | 497.00000 | 24.48151 | 48.93477 | -0.1752 | 7.34448 |
August | 514.00000 | 24.42674 | 49.30613 | -0.1820 | 7.01774 |
September | 485.00000 | 24.09726 | 48.26102 | -0.3902 | 10.65917 |
October | 502.00000 | 22.87448 | 44.77941 | 0.09703 | 8.26000 |
November | 489.00000 | 21.84614 | 35.96862 | -0.2571 | 9.58037 |
December | 497.00000 | 20.79294 | 34.18784 | -0.5731 | 15.08886 |
Annual Sum or Average | 5943.00000 | 22.89050 | 40.85760 | -0.2629 | 10.64717 |
Minimum of Months | 454.00000 | 20.42660 | 30.29119 | -0.7258 | 7.01774 |
Maximum of Months | 514.00000 | 24.48151 | 49.30613 | 0.24321 | 19.44867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52077 | 29.58024 | -0.6943 | 16.54988 |
February | 454.00000 | 20.97368 | 32.19479 | -0.5346 | 13.00150 |
March | 514.00000 | 21.98713 | 37.15498 | -0.2029 | 7.43806 |
April | 485.00000 | 22.79559 | 42.08377 | 0.03608 | 6.53398 |
May | 508.00000 | 23.78682 | 46.94160 | -0.5945 | 13.55407 |
June | 496.00000 | 24.20570 | 46.60997 | -0.3822 | 8.57645 |
July | 497.00000 | 24.37039 | 48.40371 | -0.2951 | 7.35032 |
August | 514.00000 | 24.32735 | 48.49788 | -0.2971 | 7.24105 |
September | 485.00000 | 24.19923 | 47.94043 | -0.3992 | 9.08025 |
October | 502.00000 | 23.25938 | 43.52240 | 0.17820 | 6.78975 |
November | 489.00000 | 22.32310 | 34.67819 | -0.1279 | 6.79212 |
December | 497.00000 | 21.07387 | 33.14026 | -0.4735 | 10.90210 |
Annual Sum or Average | 5943.00000 | 22.83179 | 40.96435 | -0.3148 | 9.46817 |
Minimum of Months | 454.00000 | 20.52077 | 29.58024 | -0.6943 | 6.53398 |
Maximum of Months | 514.00000 | 24.37039 | 48.49788 | 0.17820 | 16.54988 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76875 | 30.38567 | -0.6104 | 14.23278 |
February | 454.00000 | 21.49727 | 32.39186 | -0.3897 | 10.89246 |
March | 514.00000 | 22.81212 | 36.38614 | 0.00459 | 6.69235 |
April | 485.00000 | 23.50690 | 40.52580 | 0.22837 | 7.47148 |
May | 508.00000 | 24.14569 | 45.60523 | -0.4204 | 10.35307 |
June | 496.00000 | 24.37210 | 45.85817 | -0.2624 | 7.33627 |
July | 497.00000 | 24.54340 | 47.68257 | -0.1717 | 6.91208 |
August | 514.00000 | 24.45909 | 47.87967 | -0.1888 | 6.68704 |
September | 485.00000 | 24.35130 | 47.30456 | -0.2911 | 7.98212 |
October | 502.00000 | 23.71896 | 42.36807 | 0.30913 | 8.23491 |
November | 489.00000 | 22.96940 | 34.26835 | 0.03410 | 6.45814 |
December | 497.00000 | 21.49929 | 33.51215 | -0.3547 | 9.07071 |
Annual Sum or Average | 5943.00000 | 23.23255 | 40.41103 | -0.1753 | 8.51348 |
Minimum of Months | 454.00000 | 20.76875 | 30.38567 | -0.6104 | 6.45814 |
Maximum of Months | 514.00000 | 24.54340 | 47.87967 | 0.30913 | 14.23278 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.01364 | 26.82528 | -0.5007 | 13.45900 |
February | 454.00000 | 21.59909 | 29.26166 | -0.3256 | 11.01717 |
March | 514.00000 | 22.69391 | 34.49837 | 0.00486 | 7.44910 |
April | 485.00000 | 23.07456 | 40.38176 | 0.12997 | 7.35720 |
May | 508.00000 | 23.69610 | 48.61817 | -0.5840 | 13.99356 |
June | 496.00000 | 24.15024 | 50.35258 | -0.3687 | 8.80716 |
July | 497.00000 | 24.40127 | 53.04826 | -0.2442 | 6.98722 |
August | 514.00000 | 24.44862 | 53.48727 | -0.1865 | 6.43983 |
September | 485.00000 | 24.29198 | 49.77377 | -0.2889 | 8.39672 |
October | 502.00000 | 23.71317 | 41.90017 | 0.35007 | 9.66558 |
November | 489.00000 | 23.14937 | 31.48553 | 0.12133 | 7.90920 |
December | 497.00000 | 21.91540 | 30.14011 | -0.2132 | 8.73691 |
Annual Sum or Average | 5943.00000 | 23.19005 | 40.91351 | -0.1752 | 9.17878 |
Minimum of Months | 454.00000 | 21.01364 | 26.82528 | -0.5840 | 6.43983 |
Maximum of Months | 514.00000 | 24.44862 | 53.48727 | 0.35007 | 13.99356 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78084 | 30.35490 | -0.6104 | 14.51345 |
February | 454.00000 | 21.35536 | 32.52178 | -0.4257 | 11.41480 |
March | 514.00000 | 22.71922 | 36.26187 | -0.0146 | 7.07890 |
April | 485.00000 | 23.42660 | 40.79795 | 0.20716 | 7.44565 |
May | 508.00000 | 24.06149 | 46.04204 | -0.4596 | 10.81649 |
June | 496.00000 | 24.32804 | 46.26950 | -0.2920 | 7.69523 |
July | 497.00000 | 24.48281 | 48.18165 | -0.2097 | 6.98826 |
August | 514.00000 | 24.45223 | 48.09324 | -0.1990 | 6.73013 |
September | 485.00000 | 24.35245 | 47.48576 | -0.3001 | 8.08770 |
October | 502.00000 | 23.68310 | 42.62451 | 0.29805 | 8.13670 |
November | 489.00000 | 22.86344 | 34.22604 | 0.00981 | 6.74031 |
December | 497.00000 | 21.44875 | 33.55573 | -0.3703 | 9.49698 |
Annual Sum or Average | 5943.00000 | 23.17573 | 40.59830 | -0.1963 | 8.74727 |
Minimum of Months | 454.00000 | 20.78084 | 30.35490 | -0.6104 | 6.73013 |
Maximum of Months | 514.00000 | 24.48281 | 48.18165 | 0.29805 | 14.51345 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46978 | 29.38030 | -0.6973 | 17.19991 |
February | 454.00000 | 21.12305 | 31.44815 | -0.4857 | 12.73691 |
March | 514.00000 | 22.55719 | 35.47023 | -0.0557 | 6.99787 |
April | 485.00000 | 23.46380 | 39.84403 | 0.21288 | 7.38005 |
May | 508.00000 | 24.06649 | 45.07337 | -0.4634 | 10.35986 |
June | 496.00000 | 24.29089 | 46.30698 | -0.3245 | 7.86528 |
July | 497.00000 | 24.43739 | 48.76093 | -0.2513 | 7.10399 |
August | 514.00000 | 24.36271 | 49.25877 | -0.2710 | 7.12444 |
September | 485.00000 | 24.12718 | 48.32944 | -0.4227 | 9.78781 |
October | 502.00000 | 22.98955 | 44.33261 | 0.11472 | 6.83765 |
November | 489.00000 | 22.01667 | 35.17604 | -0.2061 | 7.62120 |
December | 497.00000 | 20.91437 | 33.05970 | -0.5212 | 12.43067 |
Annual Sum or Average | 5943.00000 | 22.91518 | 40.60704 | -0.2800 | 9.42860 |
Minimum of Months | 454.00000 | 20.46978 | 29.38030 | -0.6973 | 6.83765 |
Maximum of Months | 514.00000 | 24.43739 | 49.25877 | 0.21288 | 17.19991 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.63525 | 29.92422 | -0.6406 | 15.71462 |
February | 385.00000 | 21.51645 | 31.57608 | -0.3778 | 11.42284 |
March | 433.00000 | 23.04425 | 34.42489 | 0.06749 | 7.04122 |
April | 410.00000 | 23.81607 | 38.52960 | 0.31567 | 8.60422 |
May | 430.00000 | 24.31772 | 43.74403 | -0.3450 | 9.37544 |
June | 418.00000 | 24.47961 | 45.46563 | -0.2241 | 7.41225 |
July | 422.00000 | 24.65952 | 47.89100 | -0.1376 | 7.18578 |
August | 433.00000 | 24.54032 | 48.59317 | -0.1747 | 6.99911 |
September | 410.00000 | 24.31644 | 47.54696 | -0.3277 | 9.06046 |
October | 427.00000 | 23.36846 | 43.25196 | 0.21567 | 7.90778 |
November | 417.00000 | 22.45604 | 34.82274 | -0.0955 | 7.20531 |
December | 422.00000 | 21.15981 | 33.59910 | -0.4481 | 11.19430 |
Annual Sum or Average | 5034.00000 | 23.20240 | 40.00113 | -0.1802 | 9.07773 |
Minimum of Months | 385.00000 | 20.63525 | 29.92422 | -0.6406 | 6.99911 |
Maximum of Months | 433.00000 | 24.65952 | 48.59317 | 0.31567 | 15.71462 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.54354 | 27.79247 | -0.4041 | 12.54205 |
February | 454.00000 | 22.10094 | 29.65583 | -0.2224 | 10.07311 |
March | 514.00000 | 23.27577 | 33.31994 | 0.13786 | 7.71709 |
April | 485.00000 | 23.73600 | 38.56640 | 0.29868 | 8.44308 |
May | 508.00000 | 24.09898 | 44.73846 | -0.4357 | 10.13863 |
June | 496.00000 | 24.28258 | 46.30110 | -0.3234 | 8.03915 |
July | 497.00000 | 24.45968 | 48.64226 | -0.2366 | 7.15430 |
August | 514.00000 | 24.41067 | 48.84479 | -0.2242 | 6.95138 |
September | 485.00000 | 24.26319 | 47.33874 | -0.3287 | 8.91618 |
October | 502.00000 | 23.61442 | 41.66069 | 0.30217 | 9.12883 |
November | 489.00000 | 23.07578 | 32.22182 | 0.07301 | 8.01929 |
December | 497.00000 | 22.05134 | 30.81479 | -0.2186 | 9.43629 |
Annual Sum or Average | 5943.00000 | 23.41915 | 39.23355 | -0.1318 | 8.87020 |
Minimum of Months | 454.00000 | 21.54354 | 27.79247 | -0.4357 | 6.95138 |
Maximum of Months | 514.00000 | 24.45968 | 48.84479 | 0.30217 | 12.54205 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.75641 | 30.05949 | -0.6124 | 15.42269 |
February | 454.00000 | 21.47013 | 31.70437 | -0.3887 | 11.62683 |
March | 514.00000 | 22.98067 | 34.90329 | 0.06341 | 7.52754 |
April | 485.00000 | 23.73196 | 39.24640 | 0.30706 | 8.67623 |
May | 508.00000 | 24.16914 | 44.76271 | -0.3828 | 9.52449 |
June | 496.00000 | 24.35115 | 46.24455 | -0.2577 | 7.60991 |
July | 497.00000 | 24.50003 | 48.73645 | -0.1858 | 7.07392 |
August | 514.00000 | 24.43926 | 49.06961 | -0.1942 | 6.90483 |
September | 485.00000 | 24.24308 | 48.07000 | -0.3414 | 9.07206 |
October | 502.00000 | 23.30270 | 43.78475 | 0.20791 | 7.92165 |
November | 489.00000 | 22.40655 | 34.97848 | -0.1033 | 7.58155 |
December | 497.00000 | 21.23757 | 33.52323 | -0.4330 | 11.19353 |
Annual Sum or Average | 5943.00000 | 23.14510 | 40.49107 | -0.1924 | 9.15747 |
Minimum of Months | 454.00000 | 20.75641 | 30.05949 | -0.6124 | 6.90483 |
Maximum of Months | 514.00000 | 24.50003 | 49.06961 | 0.30706 | 15.42269 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167731E+10 | 0.414378E+09 | 52.83 | 0.103141E+10 | 0.645905E+09 | 0.00 | 0.59 | 19-JAN-16:00 | 0.00 | 01-JAN-00:10 | 17583.41 | 19-JAN-16:00 | 13671.83 | 31-JAN-15:10 | 8679.91 | 19-JAN-16:00 | 4147.16 | 19-JAN-16:00 | 0.00 |
February | 0.444469E+10 | 0.108354E+10 | 132.70 | 0.368649E+10 | 0.758200E+09 | 0.00 | 0.96 | 28-FEB-15:10 | 0.00 | 01-FEB-00:10 | 32000.80 | 28-FEB-15:10 | 32000.80 | 28-FEB-15:10 | 7001.13 | 18-FEB-16:30 | 6944.07 | 28-FEB-15:10 | 0.00 |
March | 0.139129E+11 | 0.324525E+10 | 268.22 | 0.108823E+11 | 0.303062E+10 | 0.00 | 1.00 | 13-MAR-15:30 | 0.00 | 01-MAR-00:10 | 49156.38 | 30-MAR-15:20 | 49156.38 | 30-MAR-15:20 | 12411.94 | 29-MAR-09:00 | 11384.20 | 30-MAR-15:20 | 0.00 |
April | 0.241872E+11 | 0.557027E+10 | 332.65 | 0.198645E+11 | 0.432271E+10 | 0.00 | 1.00 | 04-APR-10:05 | 0.00 | 01-APR-00:10 | 53990.79 | 17-APR-14:20 | 53990.79 | 17-APR-14:20 | 14968.20 | 04-APR-07:30 | 12893.81 | 17-APR-14:20 | 0.00 |
May | 0.470530E+11 | 0.106332E+11 | 413.64 | 0.358614E+11 | 0.111917E+11 | 0.00 | 1.00 | 01-MAY-13:40 | 0.00 | 01-MAY-00:10 | 69665.67 | 30-MAY-15:00 | 56089.69 | 30-MAY-15:00 | 23962.63 | 23-MAY-06:03 | 17176.50 | 30-MAY-15:00 | 0.00 |
June | 0.717438E+11 | 0.168923E+11 | 436.71 | 0.538424E+11 | 0.179013E+11 | 0.00 | 1.00 | 01-JUN-05:12 | 0.00 | 01-JUN-00:10 | 80061.54 | 26-JUN-14:30 | 71665.51 | 26-JUN-05:12 | 30198.38 | 29-JUN-06:03 | 19890.03 | 19-JUN-16:00 | 0.00 |
July | 0.827166E+11 | 0.197011E+11 | 443.69 | 0.588094E+11 | 0.239072E+11 | 0.00 | 1.00 | 01-JUL-05:12 | 0.00 | 01-JUL-00:10 | 87461.74 | 07-JUL-12:05 | 67320.95 | 17-JUL-06:03 | 37230.72 | 26-JUL-06:03 | 23404.91 | 07-JUL-16:00 | 0.00 |
August | 0.943440E+11 | 0.222225E+11 | 469.96 | 0.656504E+11 | 0.286936E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 87447.73 | 15-AUG-06:03 | 74212.58 | 07-AUG-05:12 | 31958.48 | 29-AUG-06:03 | 23006.85 | 01-AUG-15:00 | 0.00 |
September | 0.602471E+11 | 0.135790E+11 | 416.92 | 0.444608E+11 | 0.157862E+11 | 0.00 | 1.00 | 01-SEP-05:12 | 0.00 | 01-SEP-00:10 | 84160.05 | 07-SEP-16:00 | 64766.93 | 05-SEP-06:03 | 25934.01 | 06-SEP-12:03 | 21211.32 | 07-SEP-16:00 | 0.00 |
October | 0.266344E+11 | 0.599001E+10 | 305.86 | 0.198820E+11 | 0.675238E+10 | 0.00 | 1.00 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 68591.09 | 10-OCT-15:50 | 56862.14 | 10-OCT-16:00 | 35243.36 | 02-OCT-06:03 | 16690.08 | 10-OCT-16:00 | 0.00 |
November | 0.101836E+11 | 0.239304E+10 | 223.31 | 0.778658E+10 | 0.239706E+10 | 0.00 | 0.99 | 02-NOV-14:10 | 0.00 | 01-NOV-00:10 | 33649.48 | 03-NOV-15:00 | 28720.86 | 02-NOV-14:10 | 11278.23 | 02-NOV-10:40 | 7125.90 | 03-NOV-15:00 | 0.00 |
December | 0.355990E+10 | 0.844131E+09 | 113.96 | 0.237277E+10 | 0.118713E+10 | 0.00 | 0.91 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 30052.16 | 12-DEC-14:00 | 23313.42 | 12-DEC-15:10 | 15066.03 | 13-DEC-16:00 | 6500.11 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.440705E+12 | 0.102569E+12 | 3610.46 | 0.324131E+12 | 0.116574E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.167731E+10 | 0.414378E+09 | 52.83 | 0.103141E+10 | 0.645905E+09 | 0.00 | 0.59 | 0.00 | 17583.41 | 13671.83 | 7001.13 | 4147.16 | 0.00 | ||||||
Maximum of Months | 0.943440E+11 | 0.222225E+11 | 469.96 | 0.656504E+11 | 0.286936E+11 | 0.00 | 1.00 | 0.00 | 87461.74 | 74212.58 | 37230.72 | 23404.91 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.159176E+10 | 0.393152E+09 | 53.37 | 0.973453E+09 | 0.618309E+09 | 0.00 | 0.59 | 19-JAN-16:00 | 0.00 | 01-JAN-00:10 | 16682.00 | 19-JAN-16:00 | 11189.42 | 31-JAN-15:05 | 8230.84 | 19-JAN-16:00 | 3929.40 | 19-JAN-16:00 | 0.00 |
February | 0.422054E+10 | 0.103512E+10 | 136.61 | 0.348363E+10 | 0.736902E+09 | 0.00 | 0.93 | 28-FEB-15:05 | 0.00 | 01-FEB-00:10 | 28889.30 | 28-FEB-15:05 | 28889.30 | 28-FEB-15:05 | 7151.82 | 18-FEB-16:00 | 6323.46 | 28-FEB-15:05 | 0.00 |
March | 0.128808E+11 | 0.302495E+10 | 279.17 | 0.100511E+11 | 0.282969E+10 | 0.00 | 1.00 | 29-MAR-14:05 | 0.00 | 01-MAR-00:10 | 48503.24 | 30-MAR-15:20 | 48503.24 | 30-MAR-15:20 | 11373.36 | 30-MAR-10:00 | 11231.62 | 30-MAR-15:20 | 0.00 |
April | 0.230100E+11 | 0.531353E+10 | 343.94 | 0.189673E+11 | 0.404268E+10 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 54031.56 | 17-APR-15:30 | 54031.56 | 17-APR-15:30 | 13714.56 | 21-APR-10:50 | 12901.29 | 17-APR-15:30 | 0.00 |
May | 0.438601E+11 | 0.995993E+10 | 429.42 | 0.334486E+11 | 0.104116E+11 | 0.00 | 1.00 | 01-MAY-12:03 | 0.00 | 01-MAY-00:10 | 66133.26 | 30-MAY-14:05 | 53353.71 | 30-MAY-14:05 | 17373.90 | 31-MAY-13:00 | 16295.08 | 30-MAY-14:05 | 0.00 |
June | 0.655444E+11 | 0.154306E+11 | 442.14 | 0.484133E+11 | 0.171311E+11 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 76392.85 | 26-JUN-14:05 | 68186.78 | 26-JUN-05:12 | 24584.33 | 23-JUN-10:05 | 18637.25 | 30-JUN-14:05 | 0.00 |
July | 0.751332E+11 | 0.178473E+11 | 447.62 | 0.522207E+11 | 0.229125E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 79567.38 | 07-JUL-12:02 | 68703.27 | 17-JUL-05:12 | 27484.78 | 26-JUL-10:40 | 21569.62 | 07-JUL-16:00 | 0.00 |
August | 0.839364E+11 | 0.196978E+11 | 467.43 | 0.564790E+11 | 0.274574E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 87117.64 | 21-AUG-06:03 | 67939.09 | 07-AUG-05:12 | 26416.35 | 24-AUG-14:05 | 21144.26 | 01-AUG-15:20 | 0.00 |
September | 0.504726E+11 | 0.114404E+11 | 414.63 | 0.359543E+11 | 0.145183E+11 | 0.00 | 1.00 | 01-SEP-08:30 | 0.00 | 01-SEP-00:10 | 77823.92 | 06-SEP-14:05 | 55719.29 | 06-SEP-14:05 | 23186.43 | 16-SEP-13:00 | 19084.77 | 06-SEP-14:05 | 0.00 |
October | 0.218047E+11 | 0.495676E+10 | 304.78 | 0.157330E+11 | 0.607172E+10 | 0.00 | 1.00 | 02-OCT-08:40 | 0.00 | 01-OCT-00:10 | 61061.95 | 11-OCT-14:05 | 47831.80 | 10-OCT-15:30 | 22752.49 | 18-OCT-15:00 | 14530.00 | 10-OCT-14:05 | 0.00 |
November | 0.836477E+10 | 0.200020E+10 | 220.67 | 0.615345E+10 | 0.221133E+10 | 0.00 | 0.90 | 02-NOV-14:05 | 0.00 | 01-NOV-00:10 | 27677.67 | 02-NOV-14:05 | 22005.78 | 08-NOV-15:05 | 9905.65 | 27-NOV-18:00 | 6006.44 | 02-NOV-14:05 | 0.00 |
December | 0.300950E+10 | 0.727473E+09 | 113.53 | 0.196385E+10 | 0.104565E+10 | 0.00 | 0.84 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 25640.72 | 12-DEC-14:00 | 18257.59 | 12-DEC-14:00 | 10001.77 | 13-DEC-15:05 | 5647.64 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.393829E+12 | 0.918272E+11 | 3653.31 | 0.283842E+12 | 0.109987E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.159176E+10 | 0.393152E+09 | 53.37 | 0.973453E+09 | 0.618309E+09 | 0.00 | 0.59 | 0.00 | 16682.00 | 11189.42 | 7151.82 | 3929.40 | 0.00 | ||||||
Maximum of Months | 0.839364E+11 | 0.196978E+11 | 467.43 | 0.564790E+11 | 0.274574E+11 | 0.00 | 1.00 | 0.00 | 87117.64 | 68703.27 | 27484.78 | 21569.62 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.164393E+10 | 0.409224E+09 | 53.33 | 0.993971E+09 | 0.649956E+09 | 0.00 | 0.54 | 19-JAN-16:00 | 0.00 | 01-JAN-00:10 | 16914.01 | 19-JAN-16:00 | 11462.05 | 31-JAN-15:00 | 8370.34 | 19-JAN-16:00 | 4037.69 | 19-JAN-16:00 | 0.00 |
February | 0.432094E+10 | 0.106893E+10 | 135.58 | 0.350378E+10 | 0.817164E+09 | 0.00 | 0.81 | 28-FEB-15:30 | 0.00 | 01-FEB-00:10 | 27339.87 | 28-FEB-15:30 | 27339.87 | 28-FEB-15:30 | 7209.73 | 18-FEB-16:00 | 6162.83 | 28-FEB-15:00 | 0.00 |
March | 0.133792E+11 | 0.317156E+10 | 279.62 | 0.103114E+11 | 0.306786E+10 | 0.00 | 1.00 | 29-MAR-14:20 | 0.00 | 01-MAR-00:10 | 54019.68 | 30-MAR-15:20 | 54019.68 | 30-MAR-15:20 | 11346.90 | 28-MAR-13:00 | 12509.32 | 30-MAR-15:20 | 0.00 |
April | 0.246039E+11 | 0.571851E+10 | 344.17 | 0.202531E+11 | 0.435081E+10 | 0.00 | 1.00 | 04-APR-13:05 | 0.00 | 01-APR-00:10 | 60406.53 | 17-APR-16:00 | 60406.53 | 17-APR-16:00 | 13767.68 | 21-APR-11:00 | 14423.78 | 17-APR-16:00 | 0.00 |
May | 0.472397E+11 | 0.108075E+11 | 433.20 | 0.365716E+11 | 0.106681E+11 | 0.00 | 1.00 | 01-MAY-13:40 | 0.00 | 01-MAY-00:10 | 73808.43 | 30-MAY-15:00 | 61965.27 | 16-MAY-16:00 | 17429.91 | 31-MAY-13:00 | 18131.45 | 30-MAY-15:00 | 0.00 |
June | 0.704143E+11 | 0.166783E+11 | 444.70 | 0.529568E+11 | 0.174575E+11 | 0.00 | 1.00 | 01-JUN-09:00 | 0.00 | 01-JUN-00:10 | 81927.81 | 26-JUN-15:00 | 76503.04 | 26-JUN-05:12 | 24319.17 | 23-JUN-10:40 | 20783.56 | 12-JUN-15:00 | 0.00 |
July | 0.802623E+11 | 0.192046E+11 | 450.95 | 0.570548E+11 | 0.232075E+11 | 0.00 | 1.00 | 01-JUL-08:00 | 0.00 | 01-JUL-00:10 | 88027.98 | 07-JUL-16:00 | 70008.00 | 07-JUL-16:00 | 27477.68 | 26-JUL-10:50 | 24427.99 | 07-JUL-16:00 | 0.00 |
August | 0.888859E+11 | 0.209897E+11 | 469.46 | 0.611369E+11 | 0.277490E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 87621.59 | 01-AUG-15:00 | 71680.70 | 07-AUG-05:12 | 26039.75 | 24-AUG-14:00 | 23928.77 | 01-AUG-15:00 | 0.00 |
September | 0.519296E+11 | 0.118759E+11 | 416.04 | 0.370236E+11 | 0.149060E+11 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 83991.59 | 06-SEP-14:00 | 63382.09 | 07-SEP-15:30 | 24048.98 | 16-SEP-13:40 | 20838.36 | 07-SEP-16:00 | 0.00 |
October | 0.220299E+11 | 0.505991E+10 | 302.47 | 0.156982E+11 | 0.633168E+10 | 0.00 | 1.00 | 02-OCT-10:05 | 0.00 | 01-OCT-00:10 | 64338.74 | 10-OCT-14:20 | 52263.75 | 10-OCT-15:30 | 22797.15 | 18-OCT-15:00 | 15273.99 | 10-OCT-14:00 | 0.00 |
November | 0.843414E+10 | 0.204175E+10 | 220.12 | 0.604262E+10 | 0.239152E+10 | 0.00 | 0.81 | 02-NOV-14:10 | 0.00 | 01-NOV-00:10 | 27609.82 | 02-NOV-14:00 | 19739.51 | 02-NOV-14:10 | 10274.02 | 27-NOV-18:00 | 6143.35 | 02-NOV-14:00 | 0.00 |
December | 0.304626E+10 | 0.743797E+09 | 112.39 | 0.194442E+10 | 0.110184E+10 | 0.00 | 0.79 | 12-DEC-14:00 | 0.00 | 01-DEC-00:10 | 26800.92 | 12-DEC-14:00 | 18672.54 | 12-DEC-14:15 | 9647.65 | 13-DEC-11:10 | 5990.50 | 12-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.416190E+12 | 0.977696E+11 | 3662.05 | 0.303491E+12 | 0.112699E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.164393E+10 | 0.409224E+09 | 53.33 | 0.993971E+09 | 0.649956E+09 | 0.00 | 0.54 | 0.00 | 16914.01 | 11462.05 | 7209.73 | 4037.69 | 0.00 | ||||||
Maximum of Months | 0.888859E+11 | 0.209897E+11 | 469.46 | 0.611369E+11 | 0.277490E+11 | 0.00 | 1.00 | 0.00 | 88027.98 | 76503.04 | 27477.68 | 24427.99 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 49.86 | 1679.51 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 146.21 | 1381.78 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 320.54 | 882.04 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 590.37 | 711.22 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 883.74 | 464.28 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1249.39 | 294.76 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1244.00 | 214.28 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1135.49 | 177.53 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 660.21 | 391.73 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 310.92 | 806.37 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 179.39 | 1082.65 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 56.53 | 1354.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 571.26 | 783.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 49.86 | 177.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1249.39 | 1679.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 304.21 | 1004.41 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 515.77 | 834.95 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 748.37 | 550.35 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1084.64 | 453.53 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1314.16 | 309.26 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1543.77 | 198.28 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1552.06 | 144.85 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1445.70 | 119.40 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1037.56 | 255.96 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 723.96 | 507.22 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 462.61 | 658.44 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 311.72 | 811.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 922.48 | 485.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 304.21 | 119.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1552.06 | 1004.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1732.06 | 1421.92 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1750.28 | 1230.65 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1698.98 | 866.88 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1404.69 | 735.86 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1193.23 | 492.80 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1305.59 | 313.75 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1384.05 | 223.10 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1685.64 | 185.83 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1588.76 | 403.27 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 2001.29 | 790.98 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1952.86 | 1009.57 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1817.54 | 1200.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1625.92 | 736.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1193.23 | 185.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 2001.29 | 1421.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 346.51 | 1045.25 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 506.84 | 884.26 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 889.94 | 590.29 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1139.45 | 490.04 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1250.06 | 334.33 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1480.01 | 217.21 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1443.52 | 155.43 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1430.73 | 131.44 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1020.08 | 271.32 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 777.35 | 546.00 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 523.83 | 714.81 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 334.54 | 869.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 930.81 | 518.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 334.54 | 131.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1480.01 | 1045.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.29 | 0.00 | 92.29 | 15.63 | 589.25 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 50.18 | 476.35 | 0.00 | 0.00 | 0.00 |
March | 143.62 | 0.00 | 143.62 | 115.03 | 292.11 | 0.00 | 0.00 | 0.00 |
April | 173.72 | 0.77 | 172.95 | 212.42 | 224.83 | 0.00 | 0.00 | 0.00 |
May | 207.77 | 6.63 | 201.14 | 307.75 | 146.26 | 0.00 | 0.00 | 0.00 |
June | 228.66 | 15.10 | 213.56 | 425.75 | 94.41 | 0.00 | 0.00 | 0.00 |
July | 215.74 | 10.49 | 205.25 | 423.02 | 68.48 | 0.00 | 0.00 | 0.00 |
August | 191.86 | 2.09 | 189.77 | 383.89 | 58.05 | 0.00 | 0.00 | 0.00 |
September | 145.03 | 0.02 | 145.01 | 219.33 | 140.97 | 0.00 | 0.00 | 0.00 |
October | 110.27 | 0.00 | 110.27 | 98.03 | 300.45 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 51.33 | 405.18 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 16.25 | 499.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.86 | 2.94 | 146.93 | 194.02 | 273.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 15.63 | 58.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.66 | 15.10 | 213.56 | 425.75 | 589.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 15.63 | 589.28 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 50.18 | 476.37 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 115.03 | 292.12 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 212.42 | 224.84 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 307.76 | 146.27 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 425.77 | 94.42 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 423.04 | 68.48 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 383.91 | 58.05 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 219.34 | 140.98 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 98.03 | 300.47 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 51.33 | 405.20 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 16.25 | 499.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 194.03 | 273.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 15.63 | 58.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 425.77 | 589.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.30 | 0.00 | 92.30 | 15.63 | 589.28 | 0.00 | 0.00 | 0.00 |
February | 102.30 | 0.00 | 102.30 | 50.18 | 476.37 | 0.00 | 0.00 | 0.00 |
March | 143.63 | 0.00 | 143.63 | 115.03 | 292.12 | 0.00 | 0.00 | 0.00 |
April | 173.73 | 0.77 | 172.96 | 212.42 | 224.84 | 0.00 | 0.00 | 0.00 |
May | 207.78 | 6.63 | 201.14 | 307.76 | 146.27 | 0.00 | 0.00 | 0.00 |
June | 228.67 | 15.10 | 213.57 | 425.77 | 94.42 | 0.00 | 0.00 | 0.00 |
July | 215.75 | 10.49 | 205.26 | 423.04 | 68.48 | 0.00 | 0.00 | 0.00 |
August | 191.87 | 2.09 | 189.78 | 383.91 | 58.05 | 0.00 | 0.00 | 0.00 |
September | 145.04 | 0.02 | 145.02 | 219.34 | 140.98 | 0.00 | 0.00 | 0.00 |
October | 110.28 | 0.00 | 110.28 | 98.03 | 300.47 | 0.00 | 0.00 | 0.00 |
November | 98.69 | 0.00 | 98.69 | 51.33 | 405.20 | 0.00 | 0.00 | 0.00 |
December | 85.32 | 0.00 | 85.32 | 16.25 | 499.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.87 | 2.94 | 146.93 | 194.03 | 273.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.32 | 0.00 | 85.32 | 15.63 | 58.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 228.67 | 15.10 | 213.57 | 425.77 | 589.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 389.97 | 175.89 | 214.07 | 287.00 | 1026.15 | 0.00 | 0.00 | 0.00 |
February | 491.62 | 264.15 | 227.48 | 498.23 | 841.85 | 0.00 | 0.00 | 0.00 |
March | 618.52 | 281.57 | 336.95 | 733.86 | 540.49 | 0.00 | 0.00 | 0.00 |
April | 747.95 | 341.04 | 406.91 | 1068.97 | 427.03 | 0.00 | 0.00 | 0.00 |
May | 821.31 | 347.32 | 473.99 | 1288.50 | 290.72 | 0.00 | 0.00 | 0.00 |
June | 850.33 | 356.39 | 493.94 | 1503.13 | 189.65 | 0.00 | 0.00 | 0.00 |
July | 829.10 | 348.57 | 480.54 | 1508.75 | 140.07 | 0.00 | 0.00 | 0.00 |
August | 758.36 | 300.87 | 457.49 | 1401.66 | 118.93 | 0.00 | 0.00 | 0.00 |
September | 623.27 | 276.15 | 347.11 | 998.48 | 270.74 | 0.00 | 0.00 | 0.00 |
October | 531.70 | 276.65 | 255.04 | 684.70 | 552.01 | 0.00 | 0.00 | 0.00 |
November | 425.10 | 192.48 | 232.62 | 419.35 | 723.44 | 0.00 | 0.00 | 0.00 |
December | 368.22 | 167.85 | 200.37 | 285.15 | 876.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 621.91 | 277.36 | 344.54 | 891.85 | 498.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 368.22 | 167.85 | 200.37 | 285.15 | 118.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 850.33 | 356.39 | 493.94 | 1508.75 | 1026.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.42 | 6.95 | 8.46 | 11.35 | 40.57 | 0.00 | 0.00 | 0.00 |
February | 19.44 | 10.44 | 8.99 | 19.70 | 33.29 | 0.00 | 0.00 | 0.00 |
March | 24.46 | 11.13 | 13.32 | 29.02 | 21.37 | 0.00 | 0.00 | 0.00 |
April | 29.57 | 13.48 | 16.09 | 42.27 | 16.88 | 0.00 | 0.00 | 0.00 |
May | 32.47 | 13.73 | 18.74 | 50.95 | 11.49 | 0.00 | 0.00 | 0.00 |
June | 33.62 | 14.09 | 19.53 | 59.43 | 7.50 | 0.00 | 0.00 | 0.00 |
July | 32.78 | 13.78 | 19.00 | 59.65 | 5.54 | 0.00 | 0.00 | 0.00 |
August | 29.98 | 11.90 | 18.09 | 55.42 | 4.70 | 0.00 | 0.00 | 0.00 |
September | 24.64 | 10.92 | 13.72 | 39.48 | 10.70 | 0.00 | 0.00 | 0.00 |
October | 21.02 | 10.94 | 10.08 | 27.07 | 21.83 | 0.00 | 0.00 | 0.00 |
November | 16.81 | 7.61 | 9.20 | 16.58 | 28.60 | 0.00 | 0.00 | 0.00 |
December | 14.56 | 6.64 | 7.92 | 11.27 | 34.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.59 | 10.97 | 13.62 | 35.26 | 19.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.56 | 6.64 | 7.92 | 11.27 | 4.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 33.62 | 14.09 | 19.53 | 59.65 | 40.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 581.58 | 507.97 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 590.48 | 433.69 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 578.36 | 297.24 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 484.95 | 237.03 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 412.21 | 155.72 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 444.92 | 100.58 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 469.29 | 71.95 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 566.29 | 63.18 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 530.27 | 147.00 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 665.44 | 298.51 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 644.08 | 384.85 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 602.76 | 451.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 547.44 | 261.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 412.21 | 63.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 665.44 | 507.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.60 | 344.14 | 149.47 | 581.58 | 507.97 | 0.00 | 0.00 | 0.00 |
February | 460.70 | 308.82 | 151.88 | 590.48 | 433.69 | 0.00 | 0.00 | 0.00 |
March | 414.32 | 215.92 | 198.40 | 578.36 | 297.24 | 0.00 | 0.00 | 0.00 |
April | 310.30 | 101.01 | 209.29 | 484.95 | 237.03 | 0.00 | 0.00 | 0.00 |
May | 250.71 | 29.14 | 221.57 | 412.21 | 155.72 | 0.00 | 0.00 | 0.00 |
June | 231.81 | 12.90 | 218.91 | 444.92 | 100.58 | 0.00 | 0.00 | 0.00 |
July | 234.36 | 17.47 | 216.88 | 469.29 | 71.95 | 0.00 | 0.00 | 0.00 |
August | 279.80 | 52.27 | 227.54 | 566.29 | 63.18 | 0.00 | 0.00 | 0.00 |
September | 307.71 | 114.45 | 193.26 | 530.27 | 147.00 | 0.00 | 0.00 | 0.00 |
October | 446.10 | 288.98 | 157.12 | 665.44 | 298.51 | 0.00 | 0.00 | 0.00 |
November | 479.92 | 318.47 | 161.45 | 644.08 | 384.85 | 0.00 | 0.00 | 0.00 |
December | 486.56 | 342.30 | 144.26 | 602.76 | 451.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.92 | 178.21 | 187.71 | 547.44 | 261.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.81 | 12.90 | 144.26 | 412.21 | 63.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.60 | 344.14 | 227.54 | 665.44 | 507.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.57 | 344.12 | 149.46 | 581.55 | 507.94 | 0.00 | 0.00 | 0.00 |
February | 460.67 | 308.80 | 151.87 | 590.45 | 433.66 | 0.00 | 0.00 | 0.00 |
March | 414.30 | 215.91 | 198.39 | 578.32 | 297.22 | 0.00 | 0.00 | 0.00 |
April | 310.28 | 101.00 | 209.28 | 484.92 | 237.02 | 0.00 | 0.00 | 0.00 |
May | 250.70 | 29.14 | 221.56 | 412.18 | 155.71 | 0.00 | 0.00 | 0.00 |
June | 231.80 | 12.90 | 218.90 | 444.89 | 100.57 | 0.00 | 0.00 | 0.00 |
July | 234.34 | 17.47 | 216.87 | 469.26 | 71.94 | 0.00 | 0.00 | 0.00 |
August | 279.79 | 52.26 | 227.52 | 566.26 | 63.17 | 0.00 | 0.00 | 0.00 |
September | 307.69 | 114.45 | 193.25 | 530.24 | 146.99 | 0.00 | 0.00 | 0.00 |
October | 446.07 | 288.96 | 157.11 | 665.40 | 298.49 | 0.00 | 0.00 | 0.00 |
November | 479.89 | 318.45 | 161.44 | 644.04 | 384.82 | 0.00 | 0.00 | 0.00 |
December | 486.53 | 342.27 | 144.25 | 602.72 | 451.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 365.90 | 178.20 | 187.69 | 547.40 | 261.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 231.80 | 12.90 | 144.25 | 412.18 | 63.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.57 | 344.12 | 227.52 | 665.40 | 507.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 400.55 | 185.80 | 214.75 | 334.20 | 1068.28 | 0.00 | 0.00 | 0.00 |
February | 459.83 | 215.00 | 244.83 | 494.88 | 890.54 | 0.00 | 0.00 | 0.00 |
March | 677.76 | 327.51 | 350.25 | 873.30 | 584.15 | 0.00 | 0.00 | 0.00 |
April | 762.47 | 348.90 | 413.57 | 1123.30 | 466.44 | 0.00 | 0.00 | 0.00 |
May | 766.30 | 290.32 | 475.98 | 1225.55 | 316.78 | 0.00 | 0.00 | 0.00 |
June | 805.87 | 310.01 | 495.86 | 1442.67 | 209.31 | 0.00 | 0.00 | 0.00 |
July | 760.12 | 281.83 | 478.29 | 1403.93 | 150.23 | 0.00 | 0.00 | 0.00 |
August | 744.81 | 278.53 | 466.28 | 1386.84 | 131.27 | 0.00 | 0.00 | 0.00 |
September | 606.82 | 252.76 | 354.05 | 981.85 | 287.54 | 0.00 | 0.00 | 0.00 |
October | 540.60 | 280.63 | 259.97 | 739.88 | 596.74 | 0.00 | 0.00 | 0.00 |
November | 431.44 | 193.65 | 237.79 | 487.23 | 783.62 | 0.00 | 0.00 | 0.00 |
December | 355.93 | 155.69 | 200.25 | 314.49 | 932.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 610.14 | 260.24 | 349.90 | 902.83 | 532.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.93 | 155.69 | 200.25 | 314.49 | 131.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 805.87 | 348.90 | 495.86 | 1442.67 | 1068.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.84 | 7.35 | 8.49 | 13.21 | 42.24 | 0.00 | 0.00 | 0.00 |
February | 18.18 | 8.50 | 9.68 | 19.57 | 35.21 | 0.00 | 0.00 | 0.00 |
March | 26.80 | 12.95 | 13.85 | 34.53 | 23.10 | 0.00 | 0.00 | 0.00 |
April | 30.15 | 13.80 | 16.35 | 44.41 | 18.44 | 0.00 | 0.00 | 0.00 |
May | 30.30 | 11.48 | 18.82 | 48.46 | 12.53 | 0.00 | 0.00 | 0.00 |
June | 31.86 | 12.26 | 19.61 | 57.04 | 8.28 | 0.00 | 0.00 | 0.00 |
July | 30.05 | 11.14 | 18.91 | 55.51 | 5.94 | 0.00 | 0.00 | 0.00 |
August | 29.45 | 11.01 | 18.44 | 54.83 | 5.19 | 0.00 | 0.00 | 0.00 |
September | 23.99 | 9.99 | 14.00 | 38.82 | 11.37 | 0.00 | 0.00 | 0.00 |
October | 21.37 | 11.10 | 10.28 | 29.25 | 23.59 | 0.00 | 0.00 | 0.00 |
November | 17.06 | 7.66 | 9.40 | 19.26 | 30.98 | 0.00 | 0.00 | 0.00 |
December | 14.07 | 6.16 | 7.92 | 12.43 | 36.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.12 | 10.29 | 13.83 | 35.70 | 21.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.07 | 6.16 | 7.92 | 12.43 | 5.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.86 | 13.80 | 19.61 | 57.04 | 42.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 276.89 | 0.00 | 276.89 | 44.45 | 1776.30 | 0.00 | 0.00 | 0.00 |
February | 306.91 | 0.00 | 306.91 | 138.83 | 1463.28 | 0.00 | 0.00 | 0.00 |
March | 430.88 | 0.00 | 430.88 | 307.69 | 942.11 | 0.00 | 0.00 | 0.00 |
April | 521.19 | 2.31 | 518.87 | 584.62 | 745.98 | 0.00 | 0.00 | 0.00 |
May | 623.33 | 19.89 | 603.44 | 884.82 | 480.98 | 0.00 | 0.00 | 0.00 |
June | 686.00 | 45.29 | 640.71 | 1256.76 | 301.12 | 0.00 | 0.00 | 0.00 |
July | 647.25 | 31.46 | 615.78 | 1254.19 | 217.35 | 0.00 | 0.00 | 0.00 |
August | 575.62 | 6.27 | 569.35 | 1144.51 | 180.79 | 0.00 | 0.00 | 0.00 |
September | 435.11 | 0.06 | 435.05 | 658.27 | 414.67 | 0.00 | 0.00 | 0.00 |
October | 330.83 | 0.00 | 330.83 | 297.95 | 872.09 | 0.00 | 0.00 | 0.00 |
November | 296.08 | 0.00 | 296.08 | 159.62 | 1177.59 | 0.00 | 0.00 | 0.00 |
December | 255.96 | 0.00 | 255.96 | 48.34 | 1468.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 449.61 | 8.81 | 440.80 | 567.41 | 833.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.96 | 0.00 | 255.96 | 44.45 | 180.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 686.00 | 45.29 | 640.71 | 1256.76 | 1776.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 405.39 | 182.85 | 222.54 | 291.54 | 1063.51 | 0.00 | 0.00 | 0.00 |
February | 511.07 | 274.59 | 236.48 | 503.24 | 884.99 | 0.00 | 0.00 | 0.00 |
March | 642.99 | 292.71 | 350.28 | 734.30 | 585.39 | 0.00 | 0.00 | 0.00 |
April | 777.54 | 354.54 | 423.00 | 1077.79 | 472.76 | 0.00 | 0.00 | 0.00 |
May | 853.79 | 361.06 | 492.74 | 1312.63 | 318.87 | 0.00 | 0.00 | 0.00 |
June | 883.96 | 370.49 | 513.47 | 1545.79 | 202.37 | 0.00 | 0.00 | 0.00 |
July | 861.90 | 362.35 | 499.54 | 1555.87 | 147.28 | 0.00 | 0.00 | 0.00 |
August | 788.35 | 312.77 | 475.59 | 1448.70 | 121.90 | 0.00 | 0.00 | 0.00 |
September | 647.92 | 287.08 | 360.84 | 1033.69 | 269.71 | 0.00 | 0.00 | 0.00 |
October | 552.73 | 287.60 | 265.13 | 710.95 | 544.88 | 0.00 | 0.00 | 0.00 |
November | 441.91 | 200.10 | 241.82 | 439.03 | 715.56 | 0.00 | 0.00 | 0.00 |
December | 382.78 | 174.49 | 208.29 | 294.45 | 882.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.51 | 288.34 | 358.17 | 914.47 | 515.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.78 | 174.49 | 208.29 | 291.54 | 121.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 883.96 | 370.49 | 513.47 | 1555.87 | 1063.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1480.84 | 1032.44 | 448.40 | 1709.93 | 1506.81 | 0.00 | 0.00 | 0.00 |
February | 1382.12 | 926.47 | 455.65 | 1734.17 | 1303.95 | 0.00 | 0.00 | 0.00 |
March | 1242.99 | 647.78 | 595.22 | 1687.05 | 920.37 | 0.00 | 0.00 | 0.00 |
April | 930.92 | 303.03 | 627.89 | 1401.55 | 769.45 | 0.00 | 0.00 | 0.00 |
May | 752.14 | 87.42 | 664.73 | 1196.59 | 510.71 | 0.00 | 0.00 | 0.00 |
June | 695.44 | 38.70 | 656.74 | 1314.04 | 321.64 | 0.00 | 0.00 | 0.00 |
July | 703.07 | 52.43 | 650.65 | 1394.67 | 227.11 | 0.00 | 0.00 | 0.00 |
August | 839.42 | 156.81 | 682.61 | 1695.81 | 189.55 | 0.00 | 0.00 | 0.00 |
September | 923.15 | 343.37 | 579.79 | 1589.00 | 424.66 | 0.00 | 0.00 | 0.00 |
October | 1338.31 | 866.96 | 471.35 | 1990.54 | 847.19 | 0.00 | 0.00 | 0.00 |
November | 1439.78 | 955.42 | 484.37 | 1927.54 | 1089.71 | 0.00 | 0.00 | 0.00 |
December | 1459.70 | 1026.91 | 432.79 | 1791.82 | 1295.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1097.78 | 534.66 | 563.12 | 1619.12 | 781.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 695.44 | 38.70 | 432.79 | 1196.59 | 189.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1480.84 | 1032.44 | 682.61 | 1990.54 | 1506.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.39 | 193.15 | 223.24 | 339.45 | 1106.42 | 0.00 | 0.00 | 0.00 |
February | 478.02 | 223.50 | 254.51 | 501.01 | 936.96 | 0.00 | 0.00 | 0.00 |
March | 704.57 | 340.46 | 364.10 | 883.22 | 629.03 | 0.00 | 0.00 | 0.00 |
April | 792.63 | 362.70 | 429.92 | 1137.41 | 513.22 | 0.00 | 0.00 | 0.00 |
May | 796.61 | 301.81 | 494.81 | 1252.79 | 346.54 | 0.00 | 0.00 | 0.00 |
June | 837.74 | 322.28 | 515.47 | 1486.51 | 222.90 | 0.00 | 0.00 | 0.00 |
July | 790.18 | 292.97 | 497.21 | 1450.69 | 158.24 | 0.00 | 0.00 | 0.00 |
August | 774.27 | 289.55 | 484.72 | 1437.43 | 133.84 | 0.00 | 0.00 | 0.00 |
September | 630.82 | 262.76 | 368.05 | 1020.01 | 286.11 | 0.00 | 0.00 | 0.00 |
October | 561.98 | 291.73 | 270.25 | 770.62 | 588.07 | 0.00 | 0.00 | 0.00 |
November | 448.50 | 201.31 | 247.19 | 510.40 | 774.79 | 0.00 | 0.00 | 0.00 |
December | 370.01 | 161.84 | 208.17 | 325.17 | 940.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.27 | 270.54 | 363.73 | 928.49 | 551.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 370.01 | 161.84 | 208.17 | 325.17 | 133.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 837.74 | 362.70 | 515.47 | 1486.51 | 1106.42 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.133534E+09 | 0.449840E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.353720E+09 | 0.334280E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.858536E+09 | 0.236245E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.153025E+10 | 0.184348E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.236702E+10 | 0.124352E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.323841E+10 | 0.764019E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.333192E+10 | 0.573932E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.304130E+10 | 0.475487E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.171127E+10 | 0.101536E+10 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.832774E+09 | 0.215977E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.464973E+09 | 0.280624E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.151418E+09 | 0.362859E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.180151E+11 | 0.247141E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.133534E+09 | 0.475487E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.333192E+10 | 0.449840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.814804E+09 | 0.269022E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.124774E+10 | 0.201991E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.200444E+10 | 0.147405E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.281140E+10 | 0.117555E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.351984E+10 | 0.828313E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.400144E+10 | 0.513950E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415705E+10 | 0.387974E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.387215E+10 | 0.319789E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.268935E+10 | 0.663445E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.193905E+10 | 0.135853E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.119909E+10 | 0.170668E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.834907E+09 | 0.217471E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.290913E+11 | 0.153131E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.814804E+09 | 0.319789E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.415705E+10 | 0.269022E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.463915E+10 | 0.380846E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.423429E+10 | 0.297719E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.455055E+10 | 0.232184E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.364095E+10 | 0.190735E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.319596E+10 | 0.131991E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.338408E+10 | 0.813242E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.370705E+10 | 0.597549E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.451482E+10 | 0.497717E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.411807E+10 | 0.104527E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.536027E+10 | 0.211857E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.506181E+10 | 0.261681E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.486811E+10 | 0.321574E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.512751E+11 | 0.232397E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.319596E+10 | 0.497717E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.536027E+10 | 0.380846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.928079E+09 | 0.279960E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.122614E+10 | 0.213921E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.238362E+10 | 0.158104E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.295346E+10 | 0.127018E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.334816E+10 | 0.895468E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.383618E+10 | 0.563014E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.386632E+10 | 0.416314E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.383206E+10 | 0.352059E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.264404E+10 | 0.703260E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.208205E+10 | 0.146240E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.135776E+10 | 0.185280E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.896025E+09 | 0.232815E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.293539E+11 | 0.163635E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.896025E+09 | 0.352059E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.386632E+10 | 0.279960E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247195E+09 | 0.00 | 0.247195E+09 | 41857480.59 | 0.157824E+10 |
February | 0.247477E+09 | 0.00 | 0.247477E+09 | 0.121385E+09 | 0.115237E+10 |
March | 0.384670E+09 | 0.00 | 0.384670E+09 | 0.308097E+09 | 0.782376E+09 |
April | 0.450284E+09 | 1997142.59 | 0.448287E+09 | 0.550580E+09 | 0.582756E+09 |
May | 0.556484E+09 | 17759922.67 | 0.538724E+09 | 0.824272E+09 | 0.391741E+09 |
June | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.110354E+10 | 0.244722E+09 |
July | 0.577834E+09 | 28088916.80 | 0.549745E+09 | 0.113303E+10 | 0.183405E+09 |
August | 0.513888E+09 | 5598005.79 | 0.508290E+09 | 0.102821E+10 | 0.155476E+09 |
September | 0.375920E+09 | 52919.09 | 0.375867E+09 | 0.568514E+09 | 0.365395E+09 |
October | 0.295352E+09 | 0.00 | 0.295352E+09 | 0.262552E+09 | 0.804734E+09 |
November | 0.255803E+09 | 0.00 | 0.255803E+09 | 0.133043E+09 | 0.105023E+10 |
December | 0.228514E+09 | 0.00 | 0.228514E+09 | 43535784.92 | 0.133822E+10 |
Annual Sum or Average | 0.472610E+10 | 92627734.38 | 0.463347E+10 | 0.611861E+10 | 0.862966E+10 |
Minimum of Months | 0.228514E+09 | 0.00 | 0.228514E+09 | 41857480.59 | 0.155476E+09 |
Maximum of Months | 0.592679E+09 | 39130827.43 | 0.553548E+09 | 0.113303E+10 | 0.157824E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 41857891.39 | 0.157834E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.121389E+09 | 0.115245E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.308107E+09 | 0.782423E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.550602E+09 | 0.582790E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.824306E+09 | 0.391763E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110359E+10 | 0.244734E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113308E+10 | 0.183414E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.102825E+10 | 0.155483E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.568538E+09 | 0.365414E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.262562E+09 | 0.804782E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.133046E+09 | 0.105029E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 43535633.21 | 0.133830E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.611887E+10 | 0.863018E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 41857891.39 | 0.155483E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113308E+10 | 0.157834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247205E+09 | 0.00 | 0.247205E+09 | 41857891.39 | 0.157834E+10 |
February | 0.247487E+09 | 0.00 | 0.247487E+09 | 0.121389E+09 | 0.115245E+10 |
March | 0.384685E+09 | 0.00 | 0.384685E+09 | 0.308107E+09 | 0.782423E+09 |
April | 0.450302E+09 | 1997196.27 | 0.448305E+09 | 0.550602E+09 | 0.582790E+09 |
May | 0.556506E+09 | 17760400.06 | 0.538746E+09 | 0.824306E+09 | 0.391763E+09 |
June | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.110359E+10 | 0.244734E+09 |
July | 0.577857E+09 | 28089671.84 | 0.549767E+09 | 0.113308E+10 | 0.183414E+09 |
August | 0.513909E+09 | 5598156.26 | 0.508311E+09 | 0.102825E+10 | 0.155483E+09 |
September | 0.375935E+09 | 52920.51 | 0.375882E+09 | 0.568538E+09 | 0.365414E+09 |
October | 0.295364E+09 | 0.00 | 0.295364E+09 | 0.262562E+09 | 0.804782E+09 |
November | 0.255813E+09 | 0.00 | 0.255813E+09 | 0.133046E+09 | 0.105029E+10 |
December | 0.228523E+09 | 0.00 | 0.228523E+09 | 43535633.21 | 0.133830E+10 |
Annual Sum or Average | 0.472629E+10 | 92630224.23 | 0.463366E+10 | 0.611887E+10 | 0.863018E+10 |
Minimum of Months | 0.228523E+09 | 0.00 | 0.228523E+09 | 41857891.39 | 0.155483E+09 |
Maximum of Months | 0.592703E+09 | 39131879.28 | 0.553571E+09 | 0.113308E+10 | 0.157834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104448E+10 | 0.471113E+09 | 0.573371E+09 | 0.768689E+09 | 0.274843E+10 |
February | 0.118934E+10 | 0.639020E+09 | 0.550317E+09 | 0.120531E+10 | 0.203660E+10 |
March | 0.165665E+10 | 0.754150E+09 | 0.902495E+09 | 0.196557E+10 | 0.144765E+10 |
April | 0.193869E+10 | 0.883988E+09 | 0.105470E+10 | 0.277078E+10 | 0.110686E+10 |
May | 0.219979E+10 | 0.930254E+09 | 0.126953E+10 | 0.345111E+10 | 0.778677E+09 |
June | 0.220405E+10 | 0.923768E+09 | 0.128028E+10 | 0.389612E+10 | 0.491578E+09 |
July | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404103E+10 | 0.375165E+09 |
August | 0.203118E+10 | 0.805839E+09 | 0.122534E+10 | 0.375422E+10 | 0.318534E+09 |
September | 0.161550E+10 | 0.715785E+09 | 0.899719E+09 | 0.258807E+10 | 0.701763E+09 |
October | 0.142410E+10 | 0.740991E+09 | 0.683110E+09 | 0.183389E+10 | 0.147849E+10 |
November | 0.110185E+10 | 0.498912E+09 | 0.602939E+09 | 0.108694E+10 | 0.187516E+10 |
December | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.763740E+09 | 0.234702E+10 |
Annual Sum or Average | 0.196125E+11 | 0.874698E+10 | 0.108656E+11 | 0.281255E+11 | 0.157059E+11 |
Minimum of Months | 0.986230E+09 | 0.449560E+09 | 0.536670E+09 | 0.763740E+09 | 0.318534E+09 |
Maximum of Months | 0.222067E+10 | 0.933599E+09 | 0.128707E+10 | 0.404103E+10 | 0.274843E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41297968.64 | 18627401.67 | 22670566.97 | 30393278.02 | 0.108671E+09 |
February | 47025321.95 | 25266263.70 | 21759058.25 | 47656731.28 | 80525353.48 |
March | 65502272.49 | 29818417.68 | 35683854.81 | 77717006.05 | 57238931.46 |
April | 76654026.86 | 34952094.60 | 41701932.26 | 0.109554E+09 | 43764313.64 |
May | 86977579.04 | 36781404.46 | 50196174.57 | 0.136454E+09 | 30788191.58 |
June | 87146182.83 | 36524961.51 | 50621221.33 | 0.154049E+09 | 19436561.15 |
July | 87803420.16 | 36913651.60 | 50889768.56 | 0.159779E+09 | 14833669.13 |
August | 80311103.59 | 31862138.09 | 48448965.50 | 0.148438E+09 | 12594535.31 |
September | 63875563.18 | 28301493.83 | 35574069.35 | 0.102330E+09 | 27747095.57 |
October | 56307668.25 | 29298132.82 | 27009535.43 | 72510302.08 | 58458278.74 |
November | 43566232.40 | 19726548.35 | 23839684.04 | 42976724.71 | 74141968.65 |
December | 38994650.79 | 17775203.84 | 21219446.95 | 30197604.17 | 92799138.74 |
Annual Sum or Average | 0.775462E+09 | 0.345848E+09 | 0.429614E+09 | 0.111206E+10 | 0.620999E+09 |
Minimum of Months | 38994650.79 | 17775203.84 | 21219446.95 | 30197604.17 | 12594535.31 |
Maximum of Months | 87803420.16 | 36913651.60 | 50889768.56 | 0.159779E+09 | 0.108671E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.155771E+10 | 0.136055E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.142850E+10 | 0.104917E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.154908E+10 | 0.796130E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.125698E+10 | 0.614385E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.110405E+10 | 0.417075E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115322E+10 | 0.260693E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.125694E+10 | 0.192710E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.151676E+10 | 0.169216E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137447E+10 | 0.381012E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178232E+10 | 0.799534E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.166945E+10 | 0.997525E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.161442E+10 | 0.120833E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.172639E+11 | 0.824634E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.110405E+10 | 0.169216E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178232E+10 | 0.136055E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132207E+10 | 0.921741E+09 | 0.400330E+09 | 0.155771E+10 | 0.136055E+10 |
February | 0.111452E+10 | 0.747093E+09 | 0.367430E+09 | 0.142850E+10 | 0.104917E+10 |
March | 0.110973E+10 | 0.578322E+09 | 0.531406E+09 | 0.154908E+10 | 0.796130E+09 |
April | 0.804304E+09 | 0.261816E+09 | 0.542488E+09 | 0.125698E+10 | 0.614385E+09 |
May | 0.671509E+09 | 78046639.51 | 0.593462E+09 | 0.110405E+10 | 0.417075E+09 |
June | 0.600853E+09 | 33434677.84 | 0.567418E+09 | 0.115322E+10 | 0.260693E+09 |
July | 0.627698E+09 | 46804225.75 | 0.580894E+09 | 0.125694E+10 | 0.192710E+09 |
August | 0.749425E+09 | 0.139994E+09 | 0.609431E+09 | 0.151676E+10 | 0.169216E+09 |
September | 0.797594E+09 | 0.296662E+09 | 0.500933E+09 | 0.137447E+10 | 0.381012E+09 |
October | 0.119482E+10 | 0.774006E+09 | 0.420819E+09 | 0.178232E+10 | 0.799534E+09 |
November | 0.124395E+10 | 0.825462E+09 | 0.418487E+09 | 0.166945E+10 | 0.997525E+09 |
December | 0.130320E+10 | 0.916806E+09 | 0.386390E+09 | 0.161442E+10 | 0.120833E+10 |
Annual Sum or Average | 0.115397E+11 | 0.562019E+10 | 0.591949E+10 | 0.172639E+11 | 0.824634E+10 |
Minimum of Months | 0.600853E+09 | 33434677.84 | 0.367430E+09 | 0.110405E+10 | 0.169216E+09 |
Maximum of Months | 0.132207E+10 | 0.921741E+09 | 0.609431E+09 | 0.178232E+10 | 0.136055E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132199E+10 | 0.921683E+09 | 0.400305E+09 | 0.155761E+10 | 0.136047E+10 |
February | 0.111445E+10 | 0.747046E+09 | 0.367407E+09 | 0.142841E+10 | 0.104911E+10 |
March | 0.110966E+10 | 0.578285E+09 | 0.531372E+09 | 0.154898E+10 | 0.796080E+09 |
April | 0.804253E+09 | 0.261800E+09 | 0.542454E+09 | 0.125691E+10 | 0.614346E+09 |
May | 0.671466E+09 | 78041707.40 | 0.593424E+09 | 0.110398E+10 | 0.417049E+09 |
June | 0.600815E+09 | 33432564.96 | 0.567382E+09 | 0.115315E+10 | 0.260676E+09 |
July | 0.627659E+09 | 46801267.99 | 0.580857E+09 | 0.125686E+10 | 0.192697E+09 |
August | 0.749378E+09 | 0.139985E+09 | 0.609393E+09 | 0.151667E+10 | 0.169205E+09 |
September | 0.797544E+09 | 0.296643E+09 | 0.500901E+09 | 0.137438E+10 | 0.380988E+09 |
October | 0.119475E+10 | 0.773957E+09 | 0.420792E+09 | 0.178221E+10 | 0.799484E+09 |
November | 0.124387E+10 | 0.825410E+09 | 0.418461E+09 | 0.166935E+10 | 0.997462E+09 |
December | 0.130311E+10 | 0.916748E+09 | 0.386365E+09 | 0.161432E+10 | 0.120826E+10 |
Annual Sum or Average | 0.115389E+11 | 0.561983E+10 | 0.591911E+10 | 0.172628E+11 | 0.824582E+10 |
Minimum of Months | 0.600815E+09 | 33432564.96 | 0.367407E+09 | 0.110398E+10 | 0.169205E+09 |
Maximum of Months | 0.132199E+10 | 0.921683E+09 | 0.609393E+09 | 0.178221E+10 | 0.136047E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107283E+10 | 0.497654E+09 | 0.575180E+09 | 0.895114E+09 | 0.286128E+10 |
February | 0.111242E+10 | 0.520121E+09 | 0.592297E+09 | 0.119722E+10 | 0.215439E+10 |
March | 0.181531E+10 | 0.877198E+09 | 0.938116E+09 | 0.233904E+10 | 0.156459E+10 |
April | 0.197632E+10 | 0.904353E+09 | 0.107197E+10 | 0.291158E+10 | 0.120901E+10 |
May | 0.205247E+10 | 0.777597E+09 | 0.127487E+10 | 0.328252E+10 | 0.848457E+09 |
June | 0.208881E+10 | 0.803554E+09 | 0.128526E+10 | 0.373940E+10 | 0.542525E+09 |
July | 0.203590E+10 | 0.754841E+09 | 0.128106E+10 | 0.376029E+10 | 0.402370E+09 |
August | 0.199490E+10 | 0.746009E+09 | 0.124889E+10 | 0.371451E+10 | 0.351595E+09 |
September | 0.157286E+10 | 0.655165E+09 | 0.917700E+09 | 0.254494E+10 | 0.745302E+09 |
October | 0.144794E+10 | 0.751639E+09 | 0.696304E+09 | 0.198169E+10 | 0.159832E+10 |
November | 0.111829E+10 | 0.501943E+09 | 0.616344E+09 | 0.126291E+10 | 0.203114E+10 |
December | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.842326E+09 | 0.249862E+10 |
Annual Sum or Average | 0.192414E+11 | 0.820706E+10 | 0.110343E+11 | 0.284715E+11 | 0.168076E+11 |
Minimum of Months | 0.953332E+09 | 0.416987E+09 | 0.536345E+09 | 0.842326E+09 | 0.351595E+09 |
Maximum of Months | 0.208881E+10 | 0.904353E+09 | 0.128526E+10 | 0.376029E+10 | 0.286128E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42418767.26 | 19676731.62 | 22742035.64 | 35391856.49 | 0.113133E+09 |
February | 43983894.94 | 20565053.16 | 23418841.78 | 47336871.58 | 85182602.97 |
March | 71775721.37 | 34683525.60 | 37092195.77 | 92483188.46 | 61862605.75 |
April | 78141703.59 | 35757173.75 | 42384529.84 | 0.115121E+09 | 47803307.39 |
May | 81152613.96 | 30745385.62 | 50407228.33 | 0.129787E+09 | 33547203.82 |
June | 82589595.18 | 31771686.60 | 50817908.58 | 0.147852E+09 | 21450943.60 |
July | 80497582.55 | 29845636.76 | 50651945.78 | 0.148678E+09 | 15909319.05 |
August | 78876146.14 | 29496422.79 | 49379723.36 | 0.146868E+09 | 13901710.17 |
September | 62189492.73 | 25904536.92 | 36284955.81 | 0.100624E+09 | 29468558.31 |
October | 57250228.41 | 29719041.32 | 27531187.09 | 78353924.69 | 63196154.86 |
November | 44215952.03 | 19846317.65 | 24369634.38 | 49934173.01 | 80309445.70 |
December | 37693793.36 | 16487250.69 | 21206542.66 | 33304677.61 | 98793271.23 |
Annual Sum or Average | 0.760785E+09 | 0.324499E+09 | 0.436287E+09 | 0.112574E+10 | 0.664558E+09 |
Minimum of Months | 37693793.36 | 16487250.69 | 21206542.66 | 33304677.61 | 13901710.17 |
Maximum of Months | 82589595.18 | 35757173.75 | 50817908.58 | 0.148678E+09 | 0.113133E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.119057E+09 | 0.475765E+10 |
February | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.335859E+09 | 0.353998E+10 |
March | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.824111E+09 | 0.252335E+10 |
April | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.151533E+10 | 0.193359E+10 |
May | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.236991E+10 | 0.128825E+10 |
June | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.325752E+10 | 0.780492E+09 |
July | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.335923E+10 | 0.582161E+09 |
August | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.306547E+10 | 0.484229E+09 |
September | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.170624E+10 | 0.107483E+10 |
October | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.798031E+09 | 0.233582E+10 |
November | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.413745E+09 | 0.305231E+10 |
December | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.129471E+09 | 0.393271E+10 |
Annual Sum or Average | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.178940E+11 | 0.262854E+11 |
Minimum of Months | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.119057E+09 | 0.484229E+09 |
Maximum of Months | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.335923E+10 | 0.475765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.780848E+09 | 0.284850E+10 |
February | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.121744E+10 | 0.214096E+10 |
March | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.196675E+10 | 0.156791E+10 |
April | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.279363E+10 | 0.122539E+10 |
May | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.351575E+10 | 0.854062E+09 |
June | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.400670E+10 | 0.524533E+09 |
July | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.416724E+10 | 0.394480E+09 |
August | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.388019E+10 | 0.326508E+09 |
September | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.267933E+10 | 0.699097E+09 |
October | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.190420E+10 | 0.145940E+10 |
November | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.113796E+10 | 0.185472E+10 |
December | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.788659E+09 | 0.236359E+10 |
Annual Sum or Average | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.288387E+11 | 0.162592E+11 |
Minimum of Months | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.780848E+09 | 0.326508E+09 |
Maximum of Months | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.416724E+10 | 0.284850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.457988E+10 | 0.403585E+10 |
February | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.419530E+10 | 0.315452E+10 |
March | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.451860E+10 | 0.246512E+10 |
April | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.363282E+10 | 0.199441E+10 |
May | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.320494E+10 | 0.136788E+10 |
June | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.340599E+10 | 0.833686E+09 |
July | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.373547E+10 | 0.608281E+09 |
August | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.454205E+10 | 0.507702E+09 |
September | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.411869E+10 | 0.110073E+10 |
October | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.533146E+10 | 0.226911E+10 |
November | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.499619E+10 | 0.282453E+10 |
December | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.479922E+10 | 0.347070E+10 |
Annual Sum or Average | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.510606E+11 | 0.246325E+11 |
Minimum of Months | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.320494E+10 | 0.507702E+09 |
Maximum of Months | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.533146E+10 | 0.403585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.909187E+09 | 0.296344E+10 |
February | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.121204E+10 | 0.226668E+10 |
March | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.236561E+10 | 0.168478E+10 |
April | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.294816E+10 | 0.133028E+10 |
May | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.335546E+10 | 0.928175E+09 |
June | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.385303E+10 | 0.577747E+09 |
July | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.388554E+10 | 0.423822E+09 |
August | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.385002E+10 | 0.358481E+09 |
September | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.264387E+10 | 0.741606E+09 |
October | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.206403E+10 | 0.157508E+10 |
November | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.132295E+10 | 0.200826E+10 |
December | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.870948E+09 | 0.251821E+10 |
Annual Sum or Average | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.292808E+11 | 0.173766E+11 |
Minimum of Months | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.870948E+09 | 0.358481E+09 |
Maximum of Months | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.388554E+10 | 0.296344E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 49.86 | 1679.51 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 146.21 | 1381.78 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 320.54 | 882.04 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 590.37 | 711.22 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 883.74 | 464.28 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1249.39 | 294.76 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1244.00 | 214.28 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1135.49 | 177.53 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 660.21 | 391.73 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 310.92 | 806.37 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 179.39 | 1082.65 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 56.53 | 1354.76 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 571.26 | 783.68 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 49.86 | 177.53 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1249.39 | 1679.51 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.21 | 1004.41 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 515.77 | 834.95 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 748.37 | 550.35 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1084.64 | 453.53 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1314.16 | 309.26 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1543.77 | 198.28 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1552.06 | 144.85 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1445.70 | 119.40 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1037.56 | 255.96 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 723.96 | 507.22 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 462.61 | 658.44 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 311.72 | 811.95 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 922.48 | 485.58 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 304.21 | 119.40 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1552.06 | 1004.41 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1732.06 | 1421.92 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1750.28 | 1230.65 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1698.98 | 866.88 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1404.69 | 735.86 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1193.23 | 492.80 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1305.59 | 313.75 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1384.05 | 223.10 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1685.64 | 185.83 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1588.76 | 403.27 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 2001.29 | 790.98 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1952.86 | 1009.57 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1817.54 | 1200.62 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1625.92 | 736.92 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1193.23 | 185.83 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 2001.29 | 1421.92 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 346.51 | 1045.25 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 506.84 | 884.26 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 889.94 | 590.29 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1139.45 | 490.04 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1250.06 | 334.33 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1480.01 | 217.21 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1443.52 | 155.43 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1430.73 | 131.44 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1020.08 | 271.32 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 777.35 | 546.00 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 523.83 | 714.81 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 334.54 | 869.23 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 930.81 | 518.88 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 334.54 | 131.44 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1480.01 | 1045.25 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.88 | 1767.82 | 276.88 | 0.00 | 276.88 | 0.00 | 0.00 |
February | 150.53 | 1429.09 | 306.90 | 0.00 | 306.90 | 0.00 | 0.00 |
March | 345.10 | 876.35 | 430.87 | 0.00 | 430.87 | 0.00 | 0.00 |
April | 637.26 | 674.51 | 521.18 | 2.31 | 518.86 | 0.00 | 0.00 |
May | 923.27 | 438.79 | 623.32 | 19.89 | 603.43 | 0.00 | 0.00 |
June | 1277.28 | 283.25 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
July | 1269.11 | 205.43 | 647.23 | 31.46 | 615.77 | 0.00 | 0.00 |
August | 1151.70 | 174.15 | 575.61 | 6.27 | 569.34 | 0.00 | 0.00 |
September | 658.02 | 422.93 | 435.10 | 0.06 | 435.04 | 0.00 | 0.00 |
October | 294.08 | 901.40 | 330.82 | 0.00 | 330.82 | 0.00 | 0.00 |
November | 153.99 | 1215.59 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 48.76 | 1498.96 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 582.08 | 820.97 | 449.60 | 8.81 | 440.79 | 0.00 | 0.00 |
Minimum of Months | 46.88 | 174.15 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1277.28 | 1767.82 | 685.99 | 45.29 | 640.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.34 | 1066.72 | 405.38 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 517.92 | 875.13 | 511.06 | 274.59 | 236.47 | 0.00 | 0.00 |
March | 762.88 | 561.86 | 642.98 | 292.70 | 350.28 | 0.00 | 0.00 |
April | 1111.24 | 443.91 | 777.52 | 354.53 | 423.00 | 0.00 | 0.00 |
May | 1339.44 | 302.22 | 853.78 | 361.05 | 492.73 | 0.00 | 0.00 |
June | 1562.57 | 197.15 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
July | 1568.40 | 145.61 | 861.89 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1457.08 | 123.63 | 788.34 | 312.76 | 475.58 | 0.00 | 0.00 |
September | 1037.96 | 281.45 | 647.91 | 287.07 | 360.84 | 0.00 | 0.00 |
October | 711.77 | 573.83 | 552.72 | 287.59 | 265.13 | 0.00 | 0.00 |
November | 435.93 | 752.04 | 441.91 | 200.09 | 241.81 | 0.00 | 0.00 |
December | 296.42 | 910.92 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 927.12 | 517.72 | 646.50 | 288.33 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 296.42 | 123.63 | 382.78 | 174.48 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1568.40 | 1066.72 | 883.95 | 370.48 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1744.71 | 1523.88 | 1480.78 | 1032.39 | 448.39 | 0.00 | 0.00 |
February | 1771.42 | 1301.03 | 1382.07 | 926.44 | 455.63 | 0.00 | 0.00 |
March | 1735.04 | 891.70 | 1242.95 | 647.75 | 595.20 | 0.00 | 0.00 |
April | 1454.81 | 711.08 | 930.89 | 303.02 | 627.87 | 0.00 | 0.00 |
May | 1236.59 | 467.14 | 752.12 | 87.42 | 664.71 | 0.00 | 0.00 |
June | 1334.72 | 301.72 | 695.42 | 38.70 | 656.72 | 0.00 | 0.00 |
July | 1407.83 | 215.84 | 703.05 | 52.42 | 650.63 | 0.00 | 0.00 |
August | 1698.85 | 189.53 | 839.39 | 156.80 | 682.59 | 0.00 | 0.00 |
September | 1590.78 | 440.98 | 923.12 | 343.35 | 579.77 | 0.00 | 0.00 |
October | 1996.28 | 895.52 | 1338.26 | 866.92 | 471.34 | 0.00 | 0.00 |
November | 1932.20 | 1154.52 | 1439.73 | 955.38 | 484.35 | 0.00 | 0.00 |
December | 1808.23 | 1353.39 | 1459.64 | 1026.87 | 432.78 | 0.00 | 0.00 |
Annual Sum or Average | 1642.27 | 784.45 | 1097.74 | 534.63 | 563.11 | 0.00 | 0.00 |
Minimum of Months | 1236.59 | 189.53 | 695.42 | 38.70 | 432.78 | 0.00 | 0.00 |
Maximum of Months | 1996.28 | 1523.88 | 1480.78 | 1032.39 | 682.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.41 | 1110.52 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 514.45 | 925.75 | 478.01 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 907.83 | 607.25 | 704.56 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1167.71 | 484.88 | 792.62 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1274.01 | 329.30 | 796.60 | 301.80 | 494.80 | 0.00 | 0.00 |
June | 1499.71 | 217.58 | 837.73 | 322.27 | 515.46 | 0.00 | 0.00 |
July | 1459.44 | 156.17 | 790.17 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1441.67 | 136.46 | 774.26 | 289.54 | 484.72 | 0.00 | 0.00 |
September | 1020.67 | 298.91 | 630.81 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 769.13 | 620.34 | 561.97 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 506.50 | 814.60 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 326.92 | 969.76 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 938.52 | 554.04 | 634.27 | 270.53 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 326.92 | 136.46 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1499.71 | 1110.52 | 837.73 | 362.70 | 515.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.45 | 1776.30 | 276.89 | 0.00 | 276.89 | 0.00 | 0.00 |
February | 138.83 | 1463.28 | 306.91 | 0.00 | 306.91 | 0.00 | 0.00 |
March | 307.69 | 942.11 | 430.88 | 0.00 | 430.88 | 0.00 | 0.00 |
April | 584.62 | 745.98 | 521.19 | 2.31 | 518.87 | 0.00 | 0.00 |
May | 884.82 | 480.98 | 623.33 | 19.89 | 603.44 | 0.00 | 0.00 |
June | 1256.76 | 301.12 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
July | 1254.19 | 217.35 | 647.25 | 31.46 | 615.78 | 0.00 | 0.00 |
August | 1144.51 | 180.79 | 575.62 | 6.27 | 569.35 | 0.00 | 0.00 |
September | 658.27 | 414.67 | 435.11 | 0.06 | 435.05 | 0.00 | 0.00 |
October | 297.95 | 872.09 | 330.83 | 0.00 | 330.83 | 0.00 | 0.00 |
November | 159.62 | 1177.59 | 296.08 | 0.00 | 296.08 | 0.00 | 0.00 |
December | 48.34 | 1468.31 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Annual Sum or Average | 567.41 | 833.50 | 449.61 | 8.81 | 440.80 | 0.00 | 0.00 |
Minimum of Months | 44.45 | 180.79 | 255.96 | 0.00 | 255.96 | 0.00 | 0.00 |
Maximum of Months | 1256.76 | 1776.30 | 686.00 | 45.29 | 640.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.54 | 1063.51 | 405.39 | 182.85 | 222.54 | 0.00 | 0.00 |
February | 503.24 | 884.99 | 511.07 | 274.59 | 236.48 | 0.00 | 0.00 |
March | 734.30 | 585.39 | 642.99 | 292.71 | 350.28 | 0.00 | 0.00 |
April | 1077.79 | 472.76 | 777.54 | 354.54 | 423.00 | 0.00 | 0.00 |
May | 1312.63 | 318.87 | 853.79 | 361.06 | 492.74 | 0.00 | 0.00 |
June | 1545.79 | 202.37 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
July | 1555.87 | 147.28 | 861.90 | 362.35 | 499.54 | 0.00 | 0.00 |
August | 1448.70 | 121.90 | 788.35 | 312.77 | 475.59 | 0.00 | 0.00 |
September | 1033.69 | 269.71 | 647.92 | 287.08 | 360.84 | 0.00 | 0.00 |
October | 710.95 | 544.88 | 552.73 | 287.60 | 265.13 | 0.00 | 0.00 |
November | 439.03 | 715.56 | 441.91 | 200.10 | 241.82 | 0.00 | 0.00 |
December | 294.45 | 882.46 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Annual Sum or Average | 914.47 | 515.57 | 646.51 | 288.34 | 358.17 | 0.00 | 0.00 |
Minimum of Months | 291.54 | 121.90 | 382.78 | 174.49 | 208.29 | 0.00 | 0.00 |
Maximum of Months | 1555.87 | 1063.51 | 883.96 | 370.49 | 513.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1709.93 | 1506.81 | 1480.84 | 1032.44 | 448.40 | 0.00 | 0.00 |
February | 1734.17 | 1303.95 | 1382.12 | 926.47 | 455.65 | 0.00 | 0.00 |
March | 1687.05 | 920.37 | 1242.99 | 647.78 | 595.22 | 0.00 | 0.00 |
April | 1401.55 | 769.45 | 930.92 | 303.03 | 627.89 | 0.00 | 0.00 |
May | 1196.59 | 510.71 | 752.14 | 87.42 | 664.73 | 0.00 | 0.00 |
June | 1314.04 | 321.64 | 695.44 | 38.70 | 656.74 | 0.00 | 0.00 |
July | 1394.67 | 227.11 | 703.07 | 52.43 | 650.65 | 0.00 | 0.00 |
August | 1695.81 | 189.55 | 839.42 | 156.81 | 682.61 | 0.00 | 0.00 |
September | 1589.00 | 424.66 | 923.15 | 343.37 | 579.79 | 0.00 | 0.00 |
October | 1990.54 | 847.19 | 1338.31 | 866.96 | 471.35 | 0.00 | 0.00 |
November | 1927.54 | 1089.71 | 1439.78 | 955.42 | 484.37 | 0.00 | 0.00 |
December | 1791.82 | 1295.81 | 1459.70 | 1026.91 | 432.79 | 0.00 | 0.00 |
Annual Sum or Average | 1619.12 | 781.09 | 1097.78 | 534.66 | 563.12 | 0.00 | 0.00 |
Minimum of Months | 1196.59 | 189.55 | 695.44 | 38.70 | 432.79 | 0.00 | 0.00 |
Maximum of Months | 1990.54 | 1506.81 | 1480.84 | 1032.44 | 682.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 339.45 | 1106.42 | 416.39 | 193.15 | 223.24 | 0.00 | 0.00 |
February | 501.01 | 936.96 | 478.02 | 223.50 | 254.51 | 0.00 | 0.00 |
March | 883.22 | 629.03 | 704.57 | 340.46 | 364.10 | 0.00 | 0.00 |
April | 1137.41 | 513.22 | 792.63 | 362.70 | 429.92 | 0.00 | 0.00 |
May | 1252.79 | 346.54 | 796.61 | 301.81 | 494.81 | 0.00 | 0.00 |
June | 1486.51 | 222.90 | 837.74 | 322.28 | 515.47 | 0.00 | 0.00 |
July | 1450.69 | 158.24 | 790.18 | 292.97 | 497.21 | 0.00 | 0.00 |
August | 1437.43 | 133.84 | 774.27 | 289.55 | 484.72 | 0.00 | 0.00 |
September | 1020.01 | 286.11 | 630.82 | 262.76 | 368.05 | 0.00 | 0.00 |
October | 770.62 | 588.07 | 561.98 | 291.73 | 270.25 | 0.00 | 0.00 |
November | 510.40 | 774.79 | 448.50 | 201.31 | 247.19 | 0.00 | 0.00 |
December | 325.17 | 940.19 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Annual Sum or Average | 928.49 | 551.01 | 634.27 | 270.54 | 363.73 | 0.00 | 0.00 |
Minimum of Months | 325.17 | 133.84 | 370.01 | 161.84 | 208.17 | 0.00 | 0.00 |
Maximum of Months | 1486.51 | 1106.42 | 837.74 | 362.70 | 515.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133534E+09 | 0.449840E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.353720E+09 | 0.334280E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.858536E+09 | 0.236245E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.153025E+10 | 0.184348E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.236702E+10 | 0.124352E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.323841E+10 | 0.764019E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.333192E+10 | 0.573932E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.304130E+10 | 0.475487E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.171127E+10 | 0.101536E+10 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.832774E+09 | 0.215977E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.464973E+09 | 0.280624E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.151418E+09 | 0.362859E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.180151E+11 | 0.247141E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133534E+09 | 0.475487E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.333192E+10 | 0.449840E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.814804E+09 | 0.269022E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.124774E+10 | 0.201991E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.200444E+10 | 0.147405E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.281140E+10 | 0.117555E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.351984E+10 | 0.828313E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.400144E+10 | 0.513950E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.415705E+10 | 0.387974E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.387215E+10 | 0.319789E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.268935E+10 | 0.663445E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.193905E+10 | 0.135853E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.119909E+10 | 0.170668E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.834907E+09 | 0.217471E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290913E+11 | 0.153131E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.814804E+09 | 0.319789E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.415705E+10 | 0.269022E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.463915E+10 | 0.380846E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.423429E+10 | 0.297719E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.455055E+10 | 0.232184E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.364095E+10 | 0.190735E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.319596E+10 | 0.131991E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.338408E+10 | 0.813242E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.370705E+10 | 0.597549E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.451482E+10 | 0.497717E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.411807E+10 | 0.104527E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.536027E+10 | 0.211857E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.506181E+10 | 0.261681E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.486811E+10 | 0.321574E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.512751E+11 | 0.232397E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319596E+10 | 0.497717E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.536027E+10 | 0.380846E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.928079E+09 | 0.279960E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.122614E+10 | 0.213921E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.238362E+10 | 0.158104E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.295346E+10 | 0.127018E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.334816E+10 | 0.895468E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.383618E+10 | 0.563014E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.386632E+10 | 0.416314E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.383206E+10 | 0.352059E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.264404E+10 | 0.703260E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.208205E+10 | 0.146240E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.135776E+10 | 0.185280E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.896025E+09 | 0.232815E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293539E+11 | 0.163635E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.896025E+09 | 0.352059E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386632E+10 | 0.279960E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125573E+09 | 0.473492E+10 | 0.741606E+09 | 0.00 | 0.741606E+09 | 0.00 | 0.00 |
February | 0.364163E+09 | 0.345727E+10 | 0.742450E+09 | 0.00 | 0.742450E+09 | 0.00 | 0.00 |
March | 0.924310E+09 | 0.234722E+10 | 0.115404E+10 | 0.00 | 0.115404E+10 | 0.00 | 0.00 |
April | 0.165178E+10 | 0.174834E+10 | 0.135089E+10 | 5991535.14 | 0.134490E+10 | 0.00 | 0.00 |
May | 0.247288E+10 | 0.117527E+10 | 0.166950E+10 | 53280722.79 | 0.161622E+10 | 0.00 | 0.00 |
June | 0.331072E+10 | 0.734191E+09 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
July | 0.339919E+10 | 0.550233E+09 | 0.173355E+10 | 84268260.49 | 0.164928E+10 | 0.00 | 0.00 |
August | 0.308472E+10 | 0.466442E+09 | 0.154171E+10 | 16794318.31 | 0.152491E+10 | 0.00 | 0.00 |
September | 0.170559E+10 | 0.109622E+10 | 0.112779E+10 | 158760.12 | 0.112763E+10 | 0.00 | 0.00 |
October | 0.787675E+09 | 0.241430E+10 | 0.886080E+09 | 0.00 | 0.886080E+09 | 0.00 | 0.00 |
November | 0.399134E+09 | 0.315081E+10 | 0.767428E+09 | 0.00 | 0.767428E+09 | 0.00 | 0.00 |
December | 0.130607E+09 | 0.401482E+10 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.183563E+11 | 0.258900E+11 | 0.141787E+11 | 0.277888E+09 | 0.139008E+11 | 0.00 | 0.00 |
Minimum of Months | 0.125573E+09 | 0.466442E+09 | 0.685560E+09 | 0.00 | 0.685560E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339919E+10 | 0.473492E+10 | 0.177808E+10 | 0.117395E+09 | 0.166069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.799082E+09 | 0.285710E+10 | 0.108578E+10 | 0.489741E+09 | 0.596041E+09 | 0.00 | 0.00 |
February | 0.125296E+10 | 0.211713E+10 | 0.123636E+10 | 0.664286E+09 | 0.572077E+09 | 0.00 | 0.00 |
March | 0.204329E+10 | 0.150489E+10 | 0.172215E+10 | 0.783969E+09 | 0.938179E+09 | 0.00 | 0.00 |
April | 0.288033E+10 | 0.115063E+10 | 0.201534E+10 | 0.918940E+09 | 0.109640E+10 | 0.00 | 0.00 |
May | 0.358756E+10 | 0.809465E+09 | 0.228676E+10 | 0.967035E+09 | 0.131973E+10 | 0.00 | 0.00 |
June | 0.405017E+10 | 0.511015E+09 | 0.229120E+10 | 0.960293E+09 | 0.133090E+10 | 0.00 | 0.00 |
July | 0.420081E+10 | 0.389998E+09 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
August | 0.390265E+10 | 0.331128E+09 | 0.211149E+10 | 0.837701E+09 | 0.127379E+10 | 0.00 | 0.00 |
September | 0.269040E+10 | 0.729511E+09 | 0.167938E+10 | 0.744086E+09 | 0.935293E+09 | 0.00 | 0.00 |
October | 0.190640E+10 | 0.153695E+10 | 0.148041E+10 | 0.770290E+09 | 0.710119E+09 | 0.00 | 0.00 |
November | 0.112992E+10 | 0.194930E+10 | 0.114542E+10 | 0.518639E+09 | 0.626779E+09 | 0.00 | 0.00 |
December | 0.793938E+09 | 0.243982E+10 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292375E+11 | 0.163269E+11 | 0.203880E+11 | 0.909283E+10 | 0.112952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.793938E+09 | 0.331128E+09 | 0.102522E+10 | 0.467335E+09 | 0.557889E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420081E+10 | 0.285710E+10 | 0.230848E+10 | 0.970512E+09 | 0.133796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.467303E+10 | 0.408157E+10 | 0.396613E+10 | 0.276517E+10 | 0.120096E+10 | 0.00 | 0.00 |
February | 0.428541E+10 | 0.314745E+10 | 0.334350E+10 | 0.224123E+10 | 0.110227E+10 | 0.00 | 0.00 |
March | 0.464714E+10 | 0.238834E+10 | 0.332911E+10 | 0.173493E+10 | 0.159418E+10 | 0.00 | 0.00 |
April | 0.377087E+10 | 0.184312E+10 | 0.241286E+10 | 0.785432E+09 | 0.162743E+10 | 0.00 | 0.00 |
May | 0.331209E+10 | 0.125120E+10 | 0.201448E+10 | 0.234135E+09 | 0.178035E+10 | 0.00 | 0.00 |
June | 0.345959E+10 | 0.782062E+09 | 0.180252E+10 | 0.100302E+09 | 0.170222E+10 | 0.00 | 0.00 |
July | 0.377074E+10 | 0.578117E+09 | 0.188306E+10 | 0.140410E+09 | 0.174265E+10 | 0.00 | 0.00 |
August | 0.455019E+10 | 0.507637E+09 | 0.224823E+10 | 0.419973E+09 | 0.182826E+10 | 0.00 | 0.00 |
September | 0.412331E+10 | 0.114301E+10 | 0.239273E+10 | 0.889967E+09 | 0.150277E+10 | 0.00 | 0.00 |
October | 0.534684E+10 | 0.239855E+10 | 0.358440E+10 | 0.232197E+10 | 0.126243E+10 | 0.00 | 0.00 |
November | 0.500825E+10 | 0.299251E+10 | 0.373177E+10 | 0.247633E+10 | 0.125544E+10 | 0.00 | 0.00 |
December | 0.484317E+10 | 0.362493E+10 | 0.390951E+10 | 0.275036E+10 | 0.115915E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.517906E+11 | 0.247385E+11 | 0.346183E+11 | 0.168602E+11 | 0.177581E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331209E+10 | 0.507637E+09 | 0.180252E+10 | 0.100302E+09 | 0.110227E+10 | 0.00 | 0.00 |
Maximum of Months | 0.534684E+10 | 0.408157E+10 | 0.396613E+10 | 0.276517E+10 | 0.182826E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930506E+09 | 0.297442E+10 | 0.111525E+10 | 0.517331E+09 | 0.597922E+09 | 0.00 | 0.00 |
February | 0.124456E+10 | 0.223957E+10 | 0.115640E+10 | 0.540686E+09 | 0.615716E+09 | 0.00 | 0.00 |
March | 0.243152E+10 | 0.162646E+10 | 0.188709E+10 | 0.911882E+09 | 0.975209E+09 | 0.00 | 0.00 |
April | 0.302670E+10 | 0.125682E+10 | 0.205446E+10 | 0.940110E+09 | 0.111435E+10 | 0.00 | 0.00 |
May | 0.341231E+10 | 0.882004E+09 | 0.213362E+10 | 0.808342E+09 | 0.132528E+10 | 0.00 | 0.00 |
June | 0.388725E+10 | 0.563976E+09 | 0.217140E+10 | 0.835325E+09 | 0.133608E+10 | 0.00 | 0.00 |
July | 0.390897E+10 | 0.418279E+09 | 0.211640E+10 | 0.784687E+09 | 0.133171E+10 | 0.00 | 0.00 |
August | 0.386138E+10 | 0.365496E+09 | 0.207377E+10 | 0.775505E+09 | 0.129827E+10 | 0.00 | 0.00 |
September | 0.264557E+10 | 0.774771E+09 | 0.163505E+10 | 0.681069E+09 | 0.953985E+09 | 0.00 | 0.00 |
October | 0.206004E+10 | 0.166152E+10 | 0.150519E+10 | 0.781358E+09 | 0.723836E+09 | 0.00 | 0.00 |
November | 0.131284E+10 | 0.211145E+10 | 0.116250E+10 | 0.521790E+09 | 0.640714E+09 | 0.00 | 0.00 |
December | 0.875631E+09 | 0.259742E+10 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.295973E+11 | 0.174722E+11 | 0.200022E+11 | 0.853156E+10 | 0.114706E+11 | 0.00 | 0.00 |
Minimum of Months | 0.875631E+09 | 0.365496E+09 | 0.991026E+09 | 0.433475E+09 | 0.557551E+09 | 0.00 | 0.00 |
Maximum of Months | 0.390897E+10 | 0.297442E+10 | 0.217140E+10 | 0.940110E+09 | 0.133608E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119057E+09 | 0.475765E+10 | 0.741621E+09 | 0.00 | 0.741621E+09 | 0.00 | 0.00 |
February | 0.335859E+09 | 0.353998E+10 | 0.742465E+09 | 0.00 | 0.742465E+09 | 0.00 | 0.00 |
March | 0.824111E+09 | 0.252335E+10 | 0.115406E+10 | 0.00 | 0.115406E+10 | 0.00 | 0.00 |
April | 0.151533E+10 | 0.193359E+10 | 0.135092E+10 | 5991711.25 | 0.134492E+10 | 0.00 | 0.00 |
May | 0.236991E+10 | 0.128825E+10 | 0.166953E+10 | 53282288.90 | 0.161625E+10 | 0.00 | 0.00 |
June | 0.325752E+10 | 0.780492E+09 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
July | 0.335923E+10 | 0.582161E+09 | 0.173358E+10 | 84270737.43 | 0.164931E+10 | 0.00 | 0.00 |
August | 0.306547E+10 | 0.484229E+09 | 0.154174E+10 | 16794811.96 | 0.152494E+10 | 0.00 | 0.00 |
September | 0.170624E+10 | 0.107483E+10 | 0.112781E+10 | 158764.78 | 0.112766E+10 | 0.00 | 0.00 |
October | 0.798031E+09 | 0.233582E+10 | 0.886097E+09 | 0.00 | 0.886097E+09 | 0.00 | 0.00 |
November | 0.413745E+09 | 0.305231E+10 | 0.767444E+09 | 0.00 | 0.767444E+09 | 0.00 | 0.00 |
December | 0.129471E+09 | 0.393271E+10 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178940E+11 | 0.262854E+11 | 0.141790E+11 | 0.277896E+09 | 0.139011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.119057E+09 | 0.484229E+09 | 0.685574E+09 | 0.00 | 0.685574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.335923E+10 | 0.475765E+10 | 0.177812E+10 | 0.117398E+09 | 0.166072E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.780848E+09 | 0.284850E+10 | 0.108580E+10 | 0.489750E+09 | 0.596049E+09 | 0.00 | 0.00 |
February | 0.121744E+10 | 0.214096E+10 | 0.123638E+10 | 0.664299E+09 | 0.572083E+09 | 0.00 | 0.00 |
March | 0.196675E+10 | 0.156791E+10 | 0.172217E+10 | 0.783984E+09 | 0.938190E+09 | 0.00 | 0.00 |
April | 0.279363E+10 | 0.122539E+10 | 0.201537E+10 | 0.918958E+09 | 0.109642E+10 | 0.00 | 0.00 |
May | 0.351575E+10 | 0.854062E+09 | 0.228680E+10 | 0.967054E+09 | 0.131974E+10 | 0.00 | 0.00 |
June | 0.400670E+10 | 0.524533E+09 | 0.229123E+10 | 0.960312E+09 | 0.133092E+10 | 0.00 | 0.00 |
July | 0.416724E+10 | 0.394480E+09 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
August | 0.388019E+10 | 0.326508E+09 | 0.211153E+10 | 0.837717E+09 | 0.127381E+10 | 0.00 | 0.00 |
September | 0.267933E+10 | 0.699097E+09 | 0.167941E+10 | 0.744101E+09 | 0.935305E+09 | 0.00 | 0.00 |
October | 0.190420E+10 | 0.145940E+10 | 0.148043E+10 | 0.770305E+09 | 0.710127E+09 | 0.00 | 0.00 |
November | 0.113796E+10 | 0.185472E+10 | 0.114544E+10 | 0.518649E+09 | 0.626787E+09 | 0.00 | 0.00 |
December | 0.788659E+09 | 0.236359E+10 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.288387E+11 | 0.162592E+11 | 0.203883E+11 | 0.909301E+10 | 0.112953E+11 | 0.00 | 0.00 |
Minimum of Months | 0.780848E+09 | 0.326508E+09 | 0.102524E+10 | 0.467345E+09 | 0.557896E+09 | 0.00 | 0.00 |
Maximum of Months | 0.416724E+10 | 0.284850E+10 | 0.230851E+10 | 0.970531E+09 | 0.133798E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457988E+10 | 0.403585E+10 | 0.396629E+10 | 0.276528E+10 | 0.120100E+10 | 0.00 | 0.00 |
February | 0.419530E+10 | 0.315452E+10 | 0.334363E+10 | 0.224132E+10 | 0.110230E+10 | 0.00 | 0.00 |
March | 0.451860E+10 | 0.246512E+10 | 0.332924E+10 | 0.173500E+10 | 0.159423E+10 | 0.00 | 0.00 |
April | 0.363282E+10 | 0.199441E+10 | 0.241294E+10 | 0.785465E+09 | 0.162748E+10 | 0.00 | 0.00 |
May | 0.320494E+10 | 0.136788E+10 | 0.201454E+10 | 0.234145E+09 | 0.178040E+10 | 0.00 | 0.00 |
June | 0.340599E+10 | 0.833686E+09 | 0.180257E+10 | 0.100306E+09 | 0.170227E+10 | 0.00 | 0.00 |
July | 0.373547E+10 | 0.608281E+09 | 0.188311E+10 | 0.140416E+09 | 0.174270E+10 | 0.00 | 0.00 |
August | 0.454205E+10 | 0.507702E+09 | 0.224830E+10 | 0.419991E+09 | 0.182831E+10 | 0.00 | 0.00 |
September | 0.411869E+10 | 0.110073E+10 | 0.239282E+10 | 0.890004E+09 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.533146E+10 | 0.226911E+10 | 0.358453E+10 | 0.232207E+10 | 0.126247E+10 | 0.00 | 0.00 |
November | 0.499619E+10 | 0.282453E+10 | 0.373191E+10 | 0.247644E+10 | 0.125548E+10 | 0.00 | 0.00 |
December | 0.479922E+10 | 0.347070E+10 | 0.390966E+10 | 0.275048E+10 | 0.115918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.510606E+11 | 0.246325E+11 | 0.346195E+11 | 0.168609E+11 | 0.177586E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320494E+10 | 0.507702E+09 | 0.180257E+10 | 0.100306E+09 | 0.110230E+10 | 0.00 | 0.00 |
Maximum of Months | 0.533146E+10 | 0.403585E+10 | 0.396629E+10 | 0.276528E+10 | 0.182831E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.909187E+09 | 0.296344E+10 | 0.111527E+10 | 0.517339E+09 | 0.597928E+09 | 0.00 | 0.00 |
February | 0.121204E+10 | 0.226668E+10 | 0.115642E+10 | 0.540695E+09 | 0.615722E+09 | 0.00 | 0.00 |
March | 0.236561E+10 | 0.168478E+10 | 0.188712E+10 | 0.911897E+09 | 0.975218E+09 | 0.00 | 0.00 |
April | 0.294816E+10 | 0.133028E+10 | 0.205449E+10 | 0.940125E+09 | 0.111436E+10 | 0.00 | 0.00 |
May | 0.335546E+10 | 0.928175E+09 | 0.213365E+10 | 0.808356E+09 | 0.132529E+10 | 0.00 | 0.00 |
June | 0.385303E+10 | 0.577747E+09 | 0.217143E+10 | 0.835339E+09 | 0.133609E+10 | 0.00 | 0.00 |
July | 0.388554E+10 | 0.423822E+09 | 0.211643E+10 | 0.784700E+09 | 0.133173E+10 | 0.00 | 0.00 |
August | 0.385002E+10 | 0.358481E+09 | 0.207380E+10 | 0.775518E+09 | 0.129828E+10 | 0.00 | 0.00 |
September | 0.264387E+10 | 0.741606E+09 | 0.163508E+10 | 0.681080E+09 | 0.953995E+09 | 0.00 | 0.00 |
October | 0.206403E+10 | 0.157508E+10 | 0.150521E+10 | 0.781371E+09 | 0.723842E+09 | 0.00 | 0.00 |
November | 0.132295E+10 | 0.200826E+10 | 0.116252E+10 | 0.521798E+09 | 0.640720E+09 | 0.00 | 0.00 |
December | 0.870948E+09 | 0.251821E+10 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292808E+11 | 0.173766E+11 | 0.200024E+11 | 0.853170E+10 | 0.114707E+11 | 0.00 | 0.00 |
Minimum of Months | 0.870948E+09 | 0.358481E+09 | 0.991039E+09 | 0.433482E+09 | 0.557557E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388554E+10 | 0.296344E+10 | 0.217143E+10 | 0.940125E+09 | 0.133609E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 3.96 | 1.39 | -3.0 | 4.56 | -7.8 | 48.74 | 150.20 | 0.00 |
February | 7.94 | 4.18 | -1.3 | 5.19 | -4.0 | 51.84 | 169.20 | 0.00 |
March | 13.76 | 8.97 | 3.80 | 4.89 | 2.25 | 76.95 | 193.22 | 0.00 |
April | 17.21 | 12.54 | 8.82 | 3.95 | 6.45 | 95.37 | 211.82 | 0.00 |
May | 20.84 | 16.44 | 13.69 | 3.50 | 11.46 | 117.34 | 200.00 | 0.00 |
June | 24.80 | 19.35 | 16.45 | 3.85 | 15.08 | 121.81 | 213.08 | 0.00 |
July | 26.06 | 21.68 | 19.85 | 3.24 | 17.64 | 119.92 | 194.46 | 0.00 |
August | 26.55 | 22.42 | 20.72 | 3.39 | 18.21 | 115.12 | 179.15 | 0.00 |
September | 22.53 | 18.74 | 16.82 | 3.06 | 13.44 | 83.74 | 156.58 | 0.02 |
October | 16.03 | 13.02 | 10.77 | 4.05 | 5.85 | 53.01 | 190.38 | 0.00 |
November | 11.94 | 8.22 | 4.17 | 4.16 | 0.30 | 52.20 | 150.38 | 0.00 |
December | 7.70 | 4.64 | 0.26 | 4.69 | -4.1 | 44.81 | 142.03 | 0.00 |
Annual Sum or Average | 16.65 | 12.68 | 9.31 | 4.04 | 6.29 | 81.91 | 179.25 | 0.00 |
Minimum of Months | 3.96 | 1.39 | -3.0 | 3.06 | -7.8 | 44.81 | 142.03 | 0.00 |
Maximum of Months | 26.55 | 22.42 | 20.72 | 5.19 | 18.21 | 121.81 | 213.08 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.10 | 31-JAN-14:00 | 12.97 | 6.70 | 5.70 | 12.22 | 200.50 | 90.50 |
February | 25.00 | 26-FEB-14:00 | 12.75 | 1.70 | 4.10 | 8.15 | 91.50 | 816.00 |
March | 27.80 | 30-MAR-13:00 | 17.87 | 12.20 | 5.70 | 16.30 | 231.50 | 710.50 |
April | 28.90 | 17-APR-14:20 | 16.56 | 8.13 | 2.03 | 13.35 | 125.83 | 887.67 |
May | 30.60 | 19-MAY-13:00 | 18.49 | 11.70 | 4.60 | 15.76 | 140.00 | 875.50 |
June | 34.40 | 06-JUN-14:00 | 22.39 | 17.20 | 8.20 | 22.13 | 251.00 | 561.00 |
July | 36.70 | 08-JUL-14:00 | 23.91 | 18.90 | 2.10 | 24.66 | 274.00 | 567.00 |
August | 35.00 | 01-AUG-14:00 | 23.84 | 19.40 | 2.60 | 26.15 | 306.00 | 508.00 |
September | 31.70 | 07-SEP-15:09 | 23.05 | 19.60 | 4.02 | 22.55 | 218.67 | 591.33 |
October | 30.00 | 10-OCT-15:00 | 20.56 | 16.10 | 3.60 | 17.57 | 97.00 | 561.00 |
November | 24.40 | 05-NOV-15:00 | 17.95 | 14.40 | 2.10 | 14.10 | 117.50 | 361.50 |
December | 22.80 | 12-DEC-14:20 | 16.78 | 13.33 | 5.20 | 13.35 | 144.17 | 433.83 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.10 | 12.75 | 1.70 | 2.03 | 8.15 | 91.50 | 90.50 | |
Maximum of Months | 36.70 | 23.91 | 19.60 | 8.20 | 26.15 | 306.00 | 887.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.7 | 14-JAN-06:10 | -7.8 | -10.6 | 4.95 | -24.7 | 0.00 | 0.00 |
February | -12.8 | 12-FEB-06:00 | -13.8 | -18.3 | 7.20 | -30.1 | 0.00 | 0.00 |
March | 1.10 | 19-MAR-06:00 | -1.5 | -6.1 | 0.00 | -16.2 | 17.00 | 290.50 |
April | 0.00 | 06-APR-04:00 | -1.1 | -2.8 | 3.10 | -16.5 | 0.00 | 0.00 |
May | 7.80 | 11-MAY-05:00 | 5.45 | 2.80 | 4.10 | -7.8 | 21.50 | 204.50 |
June | 11.10 | 10-JUN-04:00 | 8.73 | 6.70 | 0.00 | -2.5 | 0.00 | 0.00 |
July | 17.20 | 28-JUL-22:00 | 16.88 | 16.70 | 4.10 | 14.28 | 0.00 | 0.00 |
August | 18.30 | 25-AUG-05:00 | 17.20 | 16.70 | 3.60 | 5.13 | 0.00 | 0.00 |
September | 11.70 | 29-SEP-03:00 | 11.07 | 10.60 | 2.60 | -2.3 | 0.00 | 0.00 |
October | 2.20 | 26-OCT-04:00 | 1.95 | 1.70 | 3.10 | -13.4 | 0.00 | 0.00 |
November | -3.3 | 22-NOV-05:00 | -4.0 | -5.6 | 5.20 | -20.2 | 0.00 | 0.00 |
December | -5.6 | 18-DEC-07:00 | -7.3 | -11.7 | 2.60 | -22.7 | 17.00 | 320.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -12.8 | -13.8 | -18.3 | 0.00 | -30.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.20 | 16.70 | 7.20 | 14.28 | 21.50 | 320.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.51 | 19-JAN-21:00 | 18.30 | 15.60 | 8.80 | 15.21 | 0.00 | 0.00 |
February | 15.81 | 18-FEB-15:00 | 17.20 | 15.00 | 5.20 | 13.91 | 73.00 | 1.00 |
March | 18.16 | 30-MAR-12:30 | 25.85 | 13.85 | 5.45 | 15.39 | 323.00 | 600.00 |
April | 20.01 | 04-APR-13:00 | 25.00 | 17.80 | 9.30 | 18.64 | 307.00 | 197.50 |
May | 22.34 | 30-MAY-17:00 | 27.80 | 20.00 | 4.10 | 21.96 | 97.50 | 79.50 |
June | 24.32 | 23-JUN-11:39 | 31.13 | 21.87 | 4.83 | 22.98 | 338.17 | 565.17 |
July | 25.06 | 07-JUL-11:00 | 33.30 | 22.20 | 3.60 | 20.75 | 116.50 | 900.00 |
August | 25.13 | 19-AUG-16:00 | 30.00 | 23.30 | 3.10 | 23.66 | 197.00 | 136.50 |
September | 24.10 | 09-SEP-10:00 | 30.60 | 21.70 | 2.60 | 21.27 | 236.00 | 482.00 |
October | 23.20 | 18-OCT-15:00 | 25.60 | 22.20 | 5.70 | 23.82 | 159.00 | 2.00 |
November | 18.88 | 19-NOV-14:00 | 24.40 | 16.10 | 8.20 | 13.91 | 143.00 | 384.50 |
December | 17.57 | 13-DEC-10:00 | 19.40 | 16.70 | 4.60 | 14.47 | 227.50 | 77.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.81 | 17.20 | 13.85 | 2.60 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 25.13 | 33.30 | 23.30 | 9.30 | 23.82 | 338.17 | 900.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.60 | 19-JAN-17:00 | 17.20 | 16.13 | 6.70 | 14.10 | 0.00 | 0.00 |
February | 15.00 | 18-FEB-16:19 | 17.20 | 15.81 | 5.53 | 13.91 | 50.33 | 1.00 |
March | 16.10 | 31-MAR-10:00 | 21.70 | 18.06 | 13.90 | 18.64 | 268.00 | 8.00 |
April | 17.80 | 04-APR-09:20 | 20.77 | 18.74 | 7.53 | 16.79 | 242.00 | 111.50 |
May | 20.60 | 30-MAY-19:00 | 25.00 | 21.79 | 2.60 | 12.41 | 0.00 | 0.00 |
June | 22.80 | 18-JUN-16:00 | 28.30 | 24.23 | 0.00 | 24.66 | 140.50 | 115.50 |
July | 23.30 | 26-JUL-09:00 | 26.10 | 24.10 | 3.60 | 24.66 | 338.00 | 251.50 |
August | 23.90 | 08-AUG-19:00 | 26.10 | 24.51 | 1.50 | 24.83 | 0.00 | 0.00 |
September | 23.30 | 16-SEP-16:00 | 25.60 | 23.89 | 2.10 | 22.13 | 108.00 | 57.50 |
October | 22.20 | 18-OCT-14:00 | 25.00 | 23.04 | 4.60 | 23.32 | 234.50 | 2.00 |
November | 17.20 | 04-NOV-13:00 | 17.80 | 17.48 | 3.60 | 15.02 | 276.50 | 2.50 |
December | 16.70 | 13-DEC-16:19 | 17.03 | 16.82 | 2.93 | 14.10 | 54.00 | 4.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.00 | 17.03 | 15.81 | 0.00 | 12.41 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 28.30 | 24.51 | 13.90 | 24.83 | 338.00 | 251.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 13.74 | 22.89 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 13.65 | 27.55 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 15.17 | 38.46 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 17.98 | 47.59 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 21.32 | 52.44 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 24.28 | 55.84 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 26.07 | 52.33 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 26.20 | 48.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 24.63 | 36.35 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 21.78 | 31.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.45 | 24.33 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 15.51 | 20.76 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.94 | 38.29 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 13.65 | 20.76 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 26.20 | 55.84 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.461469E+10 | -0.436950E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245190759.6 | 60.05 | 0.00 | 0.00 |
February | 0.419690E+10 | -0.397953E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -217377724.9 | 60.05 | 0.00 | 0.00 |
March | 0.478968E+10 | -0.455481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234877478.4 | 60.05 | 0.00 | 0.00 |
April | 0.406892E+10 | -0.384332E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225601177.7 | 60.05 | 0.00 | 0.00 |
May | 0.403265E+10 | -0.380052E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232125268.7 | 60.05 | 0.00 | 0.00 |
June | 0.370654E+10 | -0.348189E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224647057.0 | 60.05 | 0.00 | 0.00 |
July | 0.334706E+10 | -0.311564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231423689.7 | 60.05 | 0.00 | 0.00 |
August | 0.366739E+10 | -0.343530E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232089637.7 | 60.05 | 0.00 | 0.00 |
September | 0.346319E+10 | -0.323908E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224111171.5 | 60.05 | 0.00 | 0.00 |
October | 0.384531E+10 | -0.361240E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232903744.8 | 60.05 | 0.00 | 0.00 |
November | 0.408673E+10 | -0.385962E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227110899.6 | 60.05 | 0.00 | 0.00 |
December | 0.432555E+10 | -0.408649E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -239062078.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.481446E+11 | -0.453781E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.276652E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.334706E+10 | -0.455481E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -245190759.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.478968E+10 | -0.311564E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -217377724.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5920.38 | 33.55 | 265.83 | 271.17 | 1650.66 | 25.57 | 177.00 | 250.00 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6934.78 | 33.58 | 230.83 | 246.83 | 1105.41 | 19.24 | 74.17 | 210.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1633.21 | 18.11 | 6.83 | 317.67 | 957.68 | 20.20 | 123.00 | 283.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:20 | 1344.75 | 17.74 | 0.00 | 324.00 | 770.22 | 19.89 | 103.50 | 279.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1215.20 | 17.92 | 0.00 | 357.83 | 681.12 | 20.08 | 88.50 | 310.33 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:00 | 1129.01 | 17.67 | 0.00 | 358.33 | 638.99 | 19.83 | 89.50 | 310.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1190.49 | 17.84 | 0.00 | 362.33 | 665.84 | 19.97 | 116.50 | 312.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:10 | 1455.23 | 18.47 | 0.00 | 349.17 | 798.32 | 20.59 | 173.00 | 311.33 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1557.93 | 18.58 | 6.50 | 307.67 | 877.00 | 20.45 | 120.83 | 268.00 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-08:20 | 2820.72 | 23.84 | 119.17 | 291.83 | 1066.59 | 19.62 | 82.67 | 254.83 |
November | 299.00 | 0.50 | 0.48 | 01-NOV-08:20 | 5827.00 | 34.49 | 285.50 | 272.50 | 1198.31 | 24.23 | 166.50 | 252.67 |
December | 285.17 | 0.49 | 0.48 | 01-DEC-07:00 | 5579.70 | 34.34 | 269.83 | 267.67 | 1592.15 | 26.53 | 179.17 | 245.17 |
Annual Sum or Average | 4071.00 | 0.51 | 2765.65 | 22.91 | 1184.50 | 3727.00 | 959.12 | 21.18 | 1494.33 | 3289.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 1129.01 | 17.67 | 0.00 | 246.83 | 638.99 | 19.24 | 74.17 | 210.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6934.78 | 34.49 | 285.50 | 362.33 | 1650.66 | 26.53 | 179.17 | 312.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-08:00 | 1397.54 | 19.11 | 71.83 | 240.67 | 712.40 | 19.97 | 55.00 | 178.00 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1855.92 | 18.92 | 60.17 | 222.50 | 1026.20 | 21.06 | 50.00 | 176.67 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2233.61 | 20.54 | 105.50 | 309.50 | 877.58 | 20.09 | 47.50 | 266.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2150.98 | 19.95 | 93.33 | 324.50 | 1159.31 | 21.17 | 67.17 | 287.17 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-06:00 | 2452.55 | 20.31 | 108.50 | 366.17 | 1014.10 | 20.19 | 50.00 | 327.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2476.13 | 20.23 | 110.50 | 368.17 | 1037.98 | 20.90 | 64.00 | 332.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2450.90 | 20.27 | 105.50 | 371.67 | 1038.64 | 20.27 | 51.83 | 330.50 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2246.61 | 20.62 | 102.17 | 350.33 | 1185.56 | 21.91 | 73.50 | 313.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-06:00 | 2074.68 | 19.38 | 67.33 | 302.83 | 1118.49 | 21.63 | 55.33 | 259.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2480.84 | 20.86 | 90.67 | 267.17 | 925.34 | 19.91 | 43.67 | 214.00 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-08:09 | 1694.77 | 21.16 | 97.00 | 246.83 | 915.18 | 21.99 | 75.50 | 200.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1434.68 | 19.72 | 73.17 | 236.17 | 768.26 | 21.40 | 60.00 | 176.83 |
Annual Sum or Average | 4071.00 | 0.51 | 2122.25 | 20.13 | 1085.67 | 3606.50 | 992.83 | 20.86 | 693.50 | 3061.33 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1397.54 | 18.92 | 60.17 | 222.50 | 712.40 | 19.91 | 43.67 | 176.67 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.84 | 21.16 | 110.50 | 371.67 | 1185.56 | 21.99 | 75.50 | 332.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:50 | 498.44 | 14.33 | 0.00 | 211.17 | 301.36 | 16.73 | 0.00 | 87.17 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 529.36 | 14.53 | 0.00 | 190.00 | 329.03 | 16.88 | 0.00 | 110.67 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-08:00 | 675.39 | 16.35 | 0.00 | 299.33 | 412.09 | 18.56 | 0.00 | 225.83 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 806.72 | 17.26 | 0.00 | 327.83 | 483.64 | 19.37 | 0.67 | 270.50 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 1008.63 | 20.32 | 51.83 | 382.33 | 581.94 | 20.46 | 65.17 | 341.83 |
June | 411.67 | 0.49 | 0.48 | 01-JUN-06:40 | 1097.26 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1105.58 | 20.47 | 53.33 | 384.83 | 615.06 | 21.44 | 145.00 | 348.33 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 986.07 | 18.22 | 0.00 | 359.17 | 575.97 | 20.30 | 52.50 | 324.83 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:30 | 749.92 | 17.07 | 0.00 | 302.50 | 454.78 | 19.17 | 0.00 | 218.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 553.98 | 15.06 | 0.00 | 236.33 | 354.52 | 17.45 | 0.00 | 142.67 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 515.74 | 14.64 | 0.00 | 224.00 | 313.81 | 16.98 | 0.00 | 120.33 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 481.59 | 14.41 | 0.00 | 203.00 | 292.19 | 16.85 | 0.00 | 80.83 |
Annual Sum or Average | 4071.00 | 0.52 | 785.86 | 17.33 | 172.00 | 3505.67 | 465.50 | 19.23 | 439.83 | 2635.17 | ||
Minimum of Months | 263.00 | 0.49 | 0.48 | 481.59 | 14.33 | 0.00 | 190.00 | 292.19 | 16.73 | 0.00 | 80.83 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1105.58 | 21.04 | 66.83 | 385.17 | 645.83 | 23.05 | 176.50 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:39 | 1717.65 | 21.12 | 89.67 | 243.33 | 951.84 | 21.82 | 68.00 | 190.67 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1641.64 | 18.88 | 64.00 | 214.00 | 853.54 | 19.70 | 40.33 | 165.00 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2213.33 | 20.88 | 98.17 | 309.33 | 1177.37 | 21.79 | 72.00 | 265.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2359.32 | 18.66 | 78.67 | 330.50 | 1299.47 | 20.02 | 51.83 | 288.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:00 | 2358.91 | 17.03 | 50.83 | 364.00 | 1004.51 | 18.01 | 0.00 | 325.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2480.11 | 14.70 | 1.67 | 367.50 | 1061.85 | 17.97 | 0.00 | 330.67 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2461.49 | 17.01 | 52.00 | 367.17 | 1039.12 | 18.01 | 0.00 | 327.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-07:30 | 2413.60 | 19.51 | 89.00 | 352.67 | 1053.24 | 18.70 | 7.67 | 318.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:09 | 2166.48 | 21.46 | 90.83 | 305.00 | 1144.91 | 22.22 | 62.67 | 256.50 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2341.93 | 20.89 | 92.67 | 262.33 | 899.11 | 19.97 | 42.83 | 209.17 |
November | 299.00 | 0.52 | 0.48 | 01-NOV-09:39 | 1590.18 | 19.46 | 80.83 | 248.00 | 854.44 | 21.74 | 68.33 | 199.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:20 | 1388.01 | 19.35 | 74.17 | 236.50 | 754.13 | 21.33 | 63.33 | 177.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2142.30 | 18.87 | 862.50 | 3600.33 | 1020.79 | 19.92 | 477.00 | 3054.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1388.01 | 14.70 | 1.67 | 214.00 | 754.13 | 17.97 | 0.00 | 165.00 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2480.11 | 21.46 | 98.17 | 367.50 | 1299.47 | 22.22 | 72.00 | 330.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.80 | 33.11 | 258.00 | 269.83 | 1555.30 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.34 | 33.21 | 229.50 | 245.67 | 1055.84 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.96 | 14.21 | 6.67 | 314.67 | 893.23 | 17.61 | 0.33 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.74 | 14.00 | 0.00 | 321.00 | 728.96 | 17.50 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.83 | 14.24 | 0.00 | 355.67 | 651.76 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.73 | 14.05 | 0.00 | 356.17 | 613.77 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.77 | 14.23 | 0.00 | 358.83 | 638.15 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1395.04 | 14.84 | 0.00 | 347.17 | 759.70 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.19 | 14.97 | 6.50 | 304.83 | 825.43 | 18.10 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2717.02 | 21.23 | 117.33 | 290.17 | 984.16 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.98 | 34.08 | 281.17 | 271.67 | 1111.17 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.84 | 32.28 | 249.33 | 263.67 | 1495.07 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.52 | 20.10 | 1148.50 | 3699.33 | 904.89 | 18.86 | 329.83 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.73 | 14.00 | 0.00 | 245.67 | 613.77 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.34 | 34.08 | 281.17 | 358.83 | 1555.30 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.32 | 18.61 | 71.33 | 238.67 | 681.94 | 19.72 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.26 | 18.42 | 60.17 | 219.17 | 985.15 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.55 | 20.07 | 105.33 | 307.50 | 836.12 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.24 | 19.48 | 93.00 | 322.50 | 1111.38 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.81 | 19.85 | 108.33 | 363.17 | 963.64 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2412.05 | 19.78 | 110.33 | 365.50 | 988.18 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2383.04 | 19.82 | 105.33 | 368.83 | 987.46 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.50 | 20.16 | 102.17 | 348.67 | 1136.05 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.65 | 18.88 | 67.33 | 301.00 | 1070.50 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.12 | 20.38 | 90.50 | 264.50 | 880.94 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.64 | 20.69 | 97.00 | 243.83 | 881.95 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.67 | 19.20 | 73.00 | 233.33 | 736.12 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.99 | 19.66 | 1083.83 | 3576.67 | 948.66 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.32 | 18.42 | 60.17 | 219.17 | 681.94 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.12 | 20.69 | 110.33 | 368.83 | 1136.05 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.03 | 10.45 | 0.00 | 205.33 | 291.98 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.45 | 10.76 | 0.00 | 184.33 | 319.62 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.25 | 12.84 | 0.00 | 296.17 | 399.71 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.27 | 13.79 | 0.00 | 325.50 | 468.71 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.34 | 17.27 | 51.83 | 379.83 | 571.59 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1057.03 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.59 | 16.15 | 27.33 | 383.00 | 601.99 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.10 | 14.78 | 0.00 | 357.83 | 555.66 | 18.24 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.09 | 13.75 | 0.00 | 299.33 | 440.23 | 17.22 | 0.00 | 209.83 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.53 | 11.50 | 0.00 | 230.33 | 345.08 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.27 | 10.88 | 0.00 | 218.67 | 303.86 | 14.53 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.14 | 10.49 | 0.00 | 197.67 | 282.77 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.50 | 13.77 | 144.83 | 3462.67 | 451.98 | 17.38 | 174.67 | 2570.50 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.14 | 10.45 | 0.00 | 184.33 | 282.77 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.59 | 18.06 | 65.67 | 384.67 | 622.27 | 21.21 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.90 | 20.73 | 89.17 | 240.67 | 918.99 | 21.71 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.15 | 18.45 | 63.83 | 211.33 | 813.80 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.83 | 18.80 | 77.50 | 306.50 | 1129.42 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.56 | 18.19 | 78.50 | 327.67 | 1251.60 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.09 | 16.52 | 50.83 | 361.67 | 957.87 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.35 | 14.16 | 1.67 | 363.83 | 1014.43 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.73 | 16.50 | 52.00 | 364.83 | 991.75 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.46 | 18.88 | 86.50 | 351.00 | 996.68 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.88 | 19.38 | 75.50 | 301.00 | 1097.64 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.71 | 20.47 | 92.50 | 260.00 | 856.37 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.84 | 19.03 | 80.83 | 245.67 | 820.14 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.25 | 18.93 | 73.67 | 233.33 | 723.46 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.25 | 18.13 | 822.50 | 3567.50 | 976.51 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.25 | 14.16 | 1.67 | 211.33 | 723.46 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.35 | 20.73 | 92.50 | 364.83 | 1251.60 | 22.09 | 72.17 | 327.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.50 | 0.48 | 01-JAN-09:09 | 5799.76 | 33.11 | 258.00 | 269.83 | 1555.23 | 23.28 | 103.33 | 248.83 |
February | 263.00 | 0.51 | 0.48 | 01-FEB-10:30 | 6826.27 | 33.21 | 229.50 | 245.67 | 1055.77 | 18.03 | 25.83 | 213.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 1546.87 | 14.21 | 6.67 | 314.67 | 893.17 | 17.61 | 0.50 | 278.67 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 1284.67 | 14.00 | 0.00 | 321.00 | 728.90 | 17.51 | 0.00 | 276.83 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-07:40 | 1167.76 | 14.24 | 0.00 | 355.67 | 651.71 | 17.72 | 0.00 | 307.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:10 | 1086.67 | 14.05 | 0.00 | 356.17 | 613.72 | 17.52 | 0.00 | 306.33 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:19 | 1144.71 | 14.23 | 0.00 | 358.83 | 638.10 | 17.66 | 0.00 | 308.17 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:19 | 1394.95 | 14.84 | 0.00 | 347.17 | 759.64 | 18.27 | 0.00 | 307.00 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-07:30 | 1484.10 | 14.97 | 6.50 | 304.67 | 825.37 | 18.11 | 0.00 | 265.17 |
October | 293.50 | 0.50 | 0.48 | 01-OCT-10:39 | 2716.95 | 21.23 | 117.33 | 290.17 | 984.10 | 16.84 | 2.00 | 250.83 |
November | 299.00 | 0.51 | 0.48 | 01-NOV-08:20 | 5713.93 | 34.08 | 281.17 | 271.67 | 1111.09 | 21.75 | 82.17 | 249.33 |
December | 285.17 | 0.50 | 0.48 | 01-DEC-07:00 | 5407.81 | 32.29 | 249.33 | 263.67 | 1495.00 | 24.33 | 116.17 | 242.67 |
Annual Sum or Average | 4071.00 | 0.51 | 2684.45 | 20.11 | 1148.50 | 3699.17 | 904.83 | 18.86 | 330.00 | 3254.83 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 1086.67 | 14.00 | 0.00 | 245.67 | 613.72 | 16.84 | 0.00 | 213.83 | |
Maximum of Months | 411.67 | 0.51 | 0.48 | 6826.27 | 34.08 | 281.17 | 358.83 | 1555.23 | 24.33 | 116.17 | 308.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1358.29 | 18.61 | 71.33 | 238.67 | 681.91 | 19.73 | 48.67 | 171.33 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-10:30 | 1806.24 | 18.42 | 60.17 | 219.17 | 985.12 | 20.85 | 48.50 | 173.33 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-08:39 | 2182.51 | 20.07 | 105.33 | 307.50 | 836.07 | 19.88 | 47.33 | 262.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-07:00 | 2090.19 | 19.48 | 93.00 | 322.50 | 1111.33 | 20.99 | 67.17 | 283.17 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-06:00 | 2381.75 | 19.85 | 108.33 | 363.17 | 963.58 | 20.02 | 50.17 | 323.17 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-06:19 | 2411.99 | 19.78 | 110.33 | 365.50 | 988.12 | 20.74 | 64.00 | 329.00 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2382.98 | 19.82 | 105.33 | 368.83 | 987.40 | 20.10 | 51.83 | 328.00 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-06:30 | 2175.44 | 20.16 | 102.17 | 348.67 | 1135.99 | 21.73 | 73.50 | 309.17 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:10 | 2015.61 | 18.88 | 67.33 | 301.00 | 1070.45 | 21.43 | 55.33 | 252.67 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2427.10 | 20.38 | 90.50 | 264.50 | 880.91 | 19.70 | 42.67 | 209.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-08:09 | 1652.61 | 20.69 | 97.00 | 244.00 | 881.91 | 21.77 | 72.83 | 195.33 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-07:49 | 1394.64 | 19.20 | 73.00 | 233.33 | 736.09 | 21.16 | 57.50 | 172.33 |
Annual Sum or Average | 4071.00 | 0.51 | 2064.95 | 19.66 | 1083.83 | 3576.83 | 948.62 | 20.66 | 679.50 | 3008.67 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1358.29 | 18.42 | 60.17 | 219.17 | 681.91 | 19.70 | 42.67 | 171.33 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2427.10 | 20.69 | 110.33 | 368.83 | 1135.99 | 21.77 | 73.50 | 329.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.55 | 0.48 | 01-JAN-10:00 | 481.02 | 10.45 | 0.00 | 205.33 | 291.96 | 14.18 | 0.00 | 78.50 |
February | 263.00 | 0.55 | 0.48 | 01-FEB-13:39 | 511.43 | 10.76 | 0.00 | 184.33 | 319.60 | 14.45 | 0.00 | 106.00 |
March | 351.67 | 0.52 | 0.48 | 01-MAR-09:09 | 652.23 | 12.84 | 0.00 | 296.17 | 399.69 | 16.41 | 0.00 | 219.17 |
April | 369.33 | 0.51 | 0.48 | 01-APR-08:30 | 779.24 | 13.79 | 0.00 | 325.50 | 468.68 | 17.31 | 0.00 | 265.67 |
May | 407.00 | 0.50 | 0.48 | 01-MAY-07:30 | 972.30 | 17.27 | 51.83 | 379.83 | 571.55 | 20.44 | 52.50 | 348.00 |
June | 411.67 | 0.50 | 0.48 | 01-JUN-06:40 | 1056.99 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
July | 411.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1061.55 | 16.15 | 27.33 | 383.00 | 601.95 | 20.57 | 54.00 | 350.50 |
August | 390.50 | 0.50 | 0.48 | 01-AUG-06:00 | 950.06 | 14.78 | 0.00 | 357.83 | 555.62 | 18.25 | 0.00 | 320.33 |
September | 298.50 | 0.52 | 0.48 | 01-SEP-07:40 | 723.07 | 13.76 | 0.00 | 299.33 | 440.20 | 17.22 | 0.00 | 209.50 |
October | 293.50 | 0.54 | 0.48 | 01-OCT-10:39 | 535.52 | 11.50 | 0.00 | 230.17 | 345.06 | 15.24 | 0.00 | 134.50 |
November | 299.00 | 0.55 | 0.48 | 01-NOV-09:50 | 497.25 | 10.88 | 0.00 | 218.67 | 303.84 | 14.54 | 0.00 | 108.50 |
December | 285.17 | 0.55 | 0.48 | 01-DEC-09:30 | 464.12 | 10.49 | 0.00 | 197.67 | 282.75 | 14.27 | 0.00 | 68.50 |
Annual Sum or Average | 4071.00 | 0.52 | 757.47 | 13.78 | 144.83 | 3462.50 | 451.95 | 17.38 | 174.67 | 2570.17 | ||
Minimum of Months | 263.00 | 0.50 | 0.48 | 464.12 | 10.45 | 0.00 | 184.33 | 282.75 | 14.18 | 0.00 | 68.50 | |
Maximum of Months | 411.67 | 0.55 | 0.48 | 1061.55 | 18.07 | 65.67 | 384.67 | 622.23 | 21.22 | 68.17 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 290.67 | 0.52 | 0.48 | 01-JAN-10:50 | 1675.87 | 20.73 | 89.17 | 240.67 | 918.95 | 21.72 | 68.00 | 185.17 |
February | 263.00 | 0.53 | 0.48 | 01-FEB-13:39 | 1591.12 | 18.46 | 63.83 | 211.33 | 813.76 | 19.57 | 40.00 | 161.83 |
March | 351.67 | 0.51 | 0.48 | 01-MAR-09:20 | 2087.79 | 18.80 | 77.50 | 306.50 | 1129.37 | 21.66 | 72.17 | 263.00 |
April | 369.33 | 0.51 | 0.48 | 01-APR-09:00 | 2298.51 | 18.19 | 78.50 | 327.67 | 1251.55 | 19.86 | 51.83 | 285.00 |
May | 407.00 | 0.51 | 0.48 | 01-MAY-08:09 | 2291.03 | 16.52 | 50.83 | 361.67 | 957.81 | 17.82 | 0.00 | 322.50 |
June | 411.67 | 0.51 | 0.48 | 01-JUN-07:30 | 2393.29 | 14.16 | 1.67 | 363.83 | 1014.37 | 17.77 | 0.00 | 327.50 |
July | 411.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2376.67 | 16.51 | 52.00 | 364.83 | 991.69 | 17.81 | 0.00 | 323.67 |
August | 390.50 | 0.51 | 0.48 | 01-AUG-07:40 | 2340.39 | 18.88 | 86.50 | 351.00 | 996.61 | 18.53 | 7.83 | 313.83 |
September | 298.50 | 0.51 | 0.48 | 01-SEP-08:20 | 2062.83 | 19.38 | 75.50 | 301.00 | 1097.58 | 22.09 | 62.67 | 252.00 |
October | 293.50 | 0.52 | 0.48 | 01-OCT-10:39 | 2289.69 | 20.47 | 92.50 | 260.00 | 856.33 | 19.84 | 42.83 | 206.00 |
November | 299.00 | 0.53 | 0.48 | 01-NOV-09:50 | 1545.81 | 19.04 | 80.83 | 245.67 | 820.10 | 21.63 | 68.00 | 196.00 |
December | 285.17 | 0.52 | 0.48 | 01-DEC-09:30 | 1349.22 | 18.93 | 73.67 | 233.33 | 723.43 | 21.22 | 63.00 | 173.00 |
Annual Sum or Average | 4071.00 | 0.51 | 2071.20 | 18.13 | 822.50 | 3567.50 | 976.46 | 19.77 | 476.33 | 3009.50 | ||
Minimum of Months | 263.00 | 0.51 | 0.48 | 1349.22 | 14.16 | 1.67 | 211.33 | 723.43 | 17.77 | 0.00 | 161.83 | |
Maximum of Months | 411.67 | 0.53 | 0.48 | 2393.29 | 20.73 | 92.50 | 364.83 | 1251.55 | 22.09 | 72.17 | 327.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473302E+10 | 14557.79 | 14-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228807E+10 | 16704.31 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139757E+09 | 4262.67 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43880233.76 | 4484.99 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19661458.18 | 3874.17 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360999E+09 | 9514.06 | 22-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112452E+10 | 12616.94 | 18-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.870991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473302E+10 | 16704.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2560594.28 | 20537.30 | 09-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2560594.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2560594.28 | 20537.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412737E+10 | 10526.28 | 19-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265817E+10 | 10501.18 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104489E+10 | 10551.37 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.583051E+09 | 10492.62 | 26-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151542E+09 | 10480.67 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20522924.30 | 5573.67 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19142235.07 | 6298.22 | 14-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.496347E+09 | 10635.92 | 04-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.968799E+09 | 10496.13 | 28-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165968E+10 | 10477.34 | 07-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412737E+10 | 10635.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143254E+10 | 7977.39 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.738902E+09 | 7977.39 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45580059.78 | 7704.03 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6783870.75 | 7977.39 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1519373.22 | 1385.69 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16228478.52 | 7977.39 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322476E+09 | 7977.39 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143254E+10 | 7977.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292626E+10 | 8903.05 | 20-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164801E+10 | 8893.32 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188158E+09 | 8875.41 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42388383.35 | 8817.63 | 27-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3295547.25 | 3379.44 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103217E+09 | 8836.63 | 25-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.918600E+09 | 8870.92 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.582993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292626E+10 | 8903.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150935E+10 | 8056.71 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812200E+09 | 8056.71 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55496435.96 | 7685.54 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8778368.93 | 8056.71 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 577822.00 | 890.25 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31179615.45 | 8056.71 | 21-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.395364E+09 | 8056.71 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150935E+10 | 8056.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.494850E+10 | 14250.38 | 14-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.248725E+10 | 16940.53 | 03-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.260432E+09 | 4707.91 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81443272.71 | 5465.78 | 06-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40181746.18 | 4792.42 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.612257E+09 | 10147.07 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137636E+10 | 13617.02 | 18-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.980644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.494850E+10 | 16940.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185780E+10 | 20482.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763566E+09 | 20482.27 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.309581E+09 | 20482.27 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185780E+10 | 20482.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162875E+10 | 11418.41 | 02-JAN-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829573E+09 | 11362.56 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50250750.70 | 11305.84 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11758473.13 | 11245.32 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22992471.28 | 11322.15 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103636E+09 | 11317.39 | 24-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.564072E+09 | 11334.06 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162875E+10 | 11418.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140305E+10 | 8205.96 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.673576E+09 | 8205.96 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34713052.21 | 7660.61 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4984220.63 | 8205.96 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18323294.37 | 7630.35 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100499E+09 | 8205.96 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532131E+09 | 8205.96 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140305E+10 | 8205.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.287789E+10 | 9615.70 | 02-JAN-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146704E+10 | 9569.52 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93648044.18 | 9526.84 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13884953.30 | 9489.38 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31521034.98 | 9548.18 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281811E+09 | 9525.31 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128848E+10 | 9579.68 | 27-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.605428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.287789E+10 | 9615.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159388E+10 | 8281.80 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801656E+09 | 8281.80 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47846223.12 | 7651.79 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7491598.12 | 8281.80 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18425974.33 | 7465.34 | 26-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149086E+09 | 8281.80 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686782E+09 | 8281.80 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.330517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159388E+10 | 8281.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527383E+10 | 16661.19 | 27-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270119E+10 | 18591.59 | 03-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373515E+09 | 5808.27 | 18-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121386E+09 | 6965.32 | 06-APR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83175916.27 | 6107.72 | 26-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810957E+09 | 12442.77 | 22-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163710E+10 | 14646.14 | 18-DEC-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527383E+10 | 18591.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.570082E+10 | 35177.27 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282833E+10 | 35177.27 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74378450.02 | 34897.98 | 23-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2548689.44 | 4174.71 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 66372853.12 | 35131.04 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.479936E+09 | 35060.65 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.283318E+10 | 35172.79 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.570082E+10 | 35177.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.304194E+10 | 12943.18 | 19-JAN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176702E+10 | 12943.37 | 08-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.257591E+09 | 12837.48 | 23-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78831654.55 | 12809.97 | 07-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1062610.12 | 1109.12 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161664E+09 | 12878.07 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.476777E+09 | 12865.60 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145145E+10 | 12931.79 | 26-DEC-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304194E+10 | 12943.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.256941E+10 | 10409.10 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139902E+10 | 10409.10 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160361E+09 | 10409.10 | 23-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32615380.43 | 10409.10 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124304E+09 | 10409.10 | 26-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.389006E+09 | 10409.10 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127365E+10 | 10409.10 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256941E+10 | 10409.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480028E+10 | 11137.50 | 02-JAN-06:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273456E+10 | 11153.24 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393283E+09 | 11112.79 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92524924.83 | 11055.91 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99146.45 | 330.49 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238280E+09 | 11124.25 | 25-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.917440E+09 | 11096.94 | 24-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265520E+10 | 11151.19 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480028E+10 | 11153.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.276172E+10 | 10492.21 | 02-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156394E+10 | 10492.21 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217532E+09 | 10492.21 | 23-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52051996.12 | 10492.21 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 137454.68 | 175.31 | 11-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133252E+09 | 10492.21 | 26-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.517020E+09 | 10492.21 | 14-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150725E+10 | 10492.21 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.675291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276172E+10 | 10492.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167731E+10 | 0.103141E+10 | 17583.41 | 19-JAN-16:00 | 8903.50 | 0.00 |
February | 0.00 | 0.00 | 0.444469E+10 | 0.368649E+10 | 32000.80 | 28-FEB-15:10 | 32000.80 | 0.00 |
March | 0.00 | 0.00 | 0.139129E+11 | 0.108823E+11 | 49156.38 | 30-MAR-15:20 | 49156.38 | 0.00 |
April | 0.00 | 0.00 | 0.241872E+11 | 0.198645E+11 | 53990.79 | 17-APR-14:20 | 53990.79 | 0.00 |
May | 0.00 | 0.00 | 0.470530E+11 | 0.358614E+11 | 69665.67 | 30-MAY-15:00 | 56089.69 | 0.00 |
June | 0.00 | 0.00 | 0.717438E+11 | 0.538424E+11 | 80061.54 | 26-JUN-14:30 | 57145.40 | 0.00 |
July | 0.00 | 0.00 | 0.827166E+11 | 0.588094E+11 | 87461.74 | 07-JUL-12:05 | 59507.16 | 0.00 |
August | 0.00 | 0.00 | 0.943440E+11 | 0.656504E+11 | 87447.73 | 15-AUG-06:03 | 60317.77 | 0.00 |
September | 0.00 | 0.00 | 0.602471E+11 | 0.444608E+11 | 84160.05 | 07-SEP-16:00 | 62935.28 | 0.00 |
October | 0.00 | 0.00 | 0.266344E+11 | 0.198820E+11 | 68591.09 | 10-OCT-15:50 | 56623.65 | 0.00 |
November | 0.00 | 0.00 | 0.101836E+11 | 0.778658E+10 | 33649.48 | 03-NOV-15:00 | 25932.42 | 0.00 |
December | 0.00 | 0.00 | 0.355990E+10 | 0.237277E+10 | 30052.16 | 12-DEC-14:00 | 23009.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.440705E+12 | 0.324131E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167731E+10 | 0.103141E+10 | 17583.41 | 8903.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.943440E+11 | 0.656504E+11 | 87461.74 | 62935.28 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.159176E+10 | 0.973453E+09 | 16682.00 | 19-JAN-16:00 | 8451.16 | 0.00 |
February | 0.00 | 0.00 | 0.422054E+10 | 0.348363E+10 | 28889.30 | 28-FEB-15:05 | 28889.30 | 0.00 |
March | 0.00 | 0.00 | 0.128808E+11 | 0.100511E+11 | 48503.24 | 30-MAR-15:20 | 48503.24 | 0.00 |
April | 0.00 | 0.00 | 0.230100E+11 | 0.189673E+11 | 54031.56 | 17-APR-15:30 | 54031.56 | 0.00 |
May | 0.00 | 0.00 | 0.438601E+11 | 0.334486E+11 | 66133.26 | 30-MAY-14:05 | 53353.71 | 0.00 |
June | 0.00 | 0.00 | 0.655444E+11 | 0.484133E+11 | 76392.85 | 26-JUN-14:05 | 53159.55 | 0.00 |
July | 0.00 | 0.00 | 0.751332E+11 | 0.522207E+11 | 79567.38 | 07-JUL-12:02 | 55829.75 | 0.00 |
August | 0.00 | 0.00 | 0.839364E+11 | 0.564790E+11 | 87117.64 | 21-AUG-06:03 | 64415.07 | 0.00 |
September | 0.00 | 0.00 | 0.504726E+11 | 0.359543E+11 | 77823.92 | 06-SEP-14:05 | 55719.29 | 0.00 |
October | 0.00 | 0.00 | 0.218047E+11 | 0.157330E+11 | 61061.95 | 11-OCT-14:05 | 45725.94 | 0.00 |
November | 0.00 | 0.00 | 0.836477E+10 | 0.615345E+10 | 27677.67 | 02-NOV-14:05 | 21419.90 | 0.00 |
December | 0.00 | 0.00 | 0.300950E+10 | 0.196385E+10 | 25640.72 | 12-DEC-14:00 | 18257.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393829E+12 | 0.283842E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.159176E+10 | 0.973453E+09 | 16682.00 | 8451.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.839364E+11 | 0.564790E+11 | 87117.64 | 64415.07 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.164393E+10 | 0.993971E+09 | 16914.01 | 19-JAN-16:00 | 8543.67 | 0.00 |
February | 0.00 | 0.00 | 0.432094E+10 | 0.350378E+10 | 27339.87 | 28-FEB-15:30 | 27339.87 | 0.00 |
March | 0.00 | 0.00 | 0.133792E+11 | 0.103114E+11 | 54019.68 | 30-MAR-15:20 | 54019.68 | 0.00 |
April | 0.00 | 0.00 | 0.246039E+11 | 0.202531E+11 | 60406.53 | 17-APR-16:00 | 60406.53 | 0.00 |
May | 0.00 | 0.00 | 0.472397E+11 | 0.365716E+11 | 73808.43 | 30-MAY-15:00 | 60526.83 | 0.00 |
June | 0.00 | 0.00 | 0.704143E+11 | 0.529568E+11 | 81927.81 | 26-JUN-15:00 | 60625.48 | 0.00 |
July | 0.00 | 0.00 | 0.802623E+11 | 0.570548E+11 | 88027.98 | 07-JUL-16:00 | 70008.00 | 0.00 |
August | 0.00 | 0.00 | 0.888859E+11 | 0.611369E+11 | 87621.59 | 01-AUG-15:00 | 69778.63 | 0.00 |
September | 0.00 | 0.00 | 0.519296E+11 | 0.370236E+11 | 83991.59 | 06-SEP-14:00 | 62106.53 | 0.00 |
October | 0.00 | 0.00 | 0.220299E+11 | 0.156982E+11 | 64338.74 | 10-OCT-14:20 | 51285.73 | 0.00 |
November | 0.00 | 0.00 | 0.843414E+10 | 0.604262E+10 | 27609.82 | 02-NOV-14:00 | 19730.72 | 0.00 |
December | 0.00 | 0.00 | 0.304626E+10 | 0.194442E+10 | 26800.92 | 12-DEC-14:00 | 18523.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.416190E+12 | 0.303491E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.164393E+10 | 0.993971E+09 | 16914.01 | 8543.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.888859E+11 | 0.611369E+11 | 88027.98 | 70008.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1622.14 | 5937.98 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1635.70 | 5938.19 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1691.06 | 5844.25 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1473.72 | 5521.79 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1409.90 | 5140.52 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1334.32 | 4712.99 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1154.69 | 4387.46 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1273.65 | 4371.13 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1240.93 | 4647.26 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1339.84 | 5078.23 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1479.94 | 5492.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1516.69 | 5797.90 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1429.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1154.69 | 4371.13 | ||
Maximum of Months | 0.00 | 0.00 | 1691.06 | 5938.19 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.102106E+10 | 0.29 | 1470.05 | 09-JAN-07:01 | 0.63 |
February | 0.101260E+10 | 0.29 | 1803.29 | 28-FEB-15:40 | 0.69 |
March | 0.142218E+10 | 0.31 | 2879.23 | 13-MAR-06:03 | 0.88 |
April | 0.155853E+10 | 0.31 | 3443.44 | 17-APR-06:03 | 0.98 |
May | 0.217506E+10 | 0.36 | 4183.72 | 30-MAY-15:00 | 1.09 |
June | 0.317389E+10 | 0.44 | 8900.36 | 26-JUN-05:12 | 1.75 |
July | 0.355391E+10 | 0.46 | 8964.86 | 17-JUL-06:03 | 1.75 |
August | 0.407623E+10 | 0.50 | 9729.26 | 07-AUG-05:12 | 1.85 |
September | 0.293726E+10 | 0.42 | 8173.30 | 05-SEP-06:03 | 1.65 |
October | 0.196478E+10 | 0.34 | 4391.61 | 10-OCT-16:00 | 1.12 |
November | 0.134110E+10 | 0.30 | 3267.84 | 06-NOV-07:03 | 0.95 |
December | 0.106718E+10 | 0.28 | 1262.37 | 01-DEC-07:01 | 0.59 |
Annual Sum or Average | 0.253038E+11 | 0.36 | |||
Minimum of Months | 0.101260E+10 | 0.28 | 1262.37 | 0.59 | |
Maximum of Months | 0.407623E+10 | 0.50 | 9729.26 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.978913E+09 | 0.28 | 2165.32 | 02-JAN-06:11 | 0.79 |
February | 0.944477E+09 | 0.29 | 2165.32 | 03-FEB-07:01 | 0.79 |
March | 0.123975E+10 | 0.32 | 2785.26 | 30-MAR-14:05 | 0.90 |
April | 0.141267E+10 | 0.32 | 3002.65 | 17-APR-15:50 | 0.94 |
May | 0.197129E+10 | 0.36 | 4228.44 | 30-MAY-06:03 | 1.16 |
June | 0.267873E+10 | 0.43 | 8931.88 | 26-JUN-06:03 | 1.85 |
July | 0.289545E+10 | 0.43 | 8931.88 | 10-JUL-05:12 | 1.85 |
August | 0.317618E+10 | 0.46 | 8931.88 | 07-AUG-06:03 | 1.85 |
September | 0.212647E+10 | 0.38 | 6387.78 | 05-SEP-06:03 | 1.49 |
October | 0.143526E+10 | 0.32 | 3331.41 | 10-OCT-15:30 | 1.00 |
November | 0.103306E+10 | 0.29 | 1870.67 | 06-NOV-15:05 | 0.73 |
December | 0.971319E+09 | 0.28 | 2165.32 | 04-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.208636E+11 | 0.35 | |||
Minimum of Months | 0.944477E+09 | 0.28 | 1870.67 | 0.73 | |
Maximum of Months | 0.317618E+10 | 0.46 | 8931.88 | 1.85 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123047E+10 | 0.34 | 2184.76 | 03-JAN-06:11 | 0.73 |
February | 0.111074E+10 | 0.34 | 2184.76 | 03-FEB-07:01 | 0.73 |
March | 0.129937E+10 | 0.34 | 2888.92 | 30-MAR-16:00 | 0.84 |
April | 0.143895E+10 | 0.33 | 3162.11 | 17-APR-15:40 | 0.89 |
May | 0.198793E+10 | 0.36 | 3944.63 | 30-MAY-15:00 | 1.01 |
June | 0.267610E+10 | 0.41 | 10072.58 | 26-JUN-05:12 | 1.80 |
July | 0.289077E+10 | 0.41 | 7782.53 | 17-JUL-06:03 | 1.53 |
August | 0.312146E+10 | 0.43 | 8859.11 | 07-AUG-05:12 | 1.66 |
September | 0.199857E+10 | 0.36 | 4258.97 | 07-SEP-15:30 | 1.05 |
October | 0.138158E+10 | 0.32 | 2996.82 | 10-OCT-15:30 | 0.86 |
November | 0.110180E+10 | 0.31 | 2184.76 | 22-NOV-06:01 | 0.73 |
December | 0.110800E+10 | 0.31 | 2184.76 | 18-DEC-07:02 | 0.73 |
Annual Sum or Average | 0.213457E+11 | 0.36 | |||
Minimum of Months | 0.110180E+10 | 0.31 | 2184.76 | 0.73 | |
Maximum of Months | 0.312146E+10 | 0.43 | 10072.58 | 1.80 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.23 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:02 | 2.06 | 2.06 | 57.25 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.11 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.18 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.58 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.68 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 57.83 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.90 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.85 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.48 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.49 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.50 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.11 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.48 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.23 | 58.23 | 1622.14 | 5937.98 | 31-JAN-12:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.73 | 57.73 | 1635.70 | 5938.19 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.76 | 57.76 | 1691.06 | 5844.25 | 01-MAR-12:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.88 | 57.88 | 1473.72 | 5521.79 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.44 | 58.44 | 1409.90 | 5140.52 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.21 | 58.21 | 1334.32 | 4712.99 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.33 | 58.33 | 1154.69 | 4387.46 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.38 | 58.38 | 1273.65 | 4371.13 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.34 | 58.34 | 1240.93 | 4647.26 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.50 | 57.50 | 1339.84 | 5078.23 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.07 | 58.07 | 1479.94 | 5492.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.90 | 57.90 | 1516.69 | 5797.90 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 1429.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.50 | 57.50 | 1154.69 | 4371.13 | ||
Maximum of Months | 0.00 | 0.00 | 58.44 | 58.44 | 1691.06 | 5938.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.161665E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102415E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.614131E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.781368E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.129598E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200867E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.232550E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.262987E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.165354E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.847620E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.521457E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.633195E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.159521E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.521457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.262987E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156819E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.900226E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.475159E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.684576E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.119312E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181094E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.207427E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.228740E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.135669E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.652346E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.428054E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.645620E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.140766E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.428054E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.228740E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.257877E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.151737E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.594759E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.753742E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.127967E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.193544E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.220954E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.241111E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.138745E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.724854E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.673469E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.132096E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.173871E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.594759E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257877E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.102106E+10 | 0.167731E+10 | 0.147311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101260E+10 | 0.444469E+10 | 0.814535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142218E+10 | 0.139129E+11 | 0.147388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155853E+10 | 0.241872E+11 | 0.684882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217506E+10 | 0.470530E+11 | 0.151542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317389E+10 | 0.717438E+11 | 20522924.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.355391E+10 | 0.827166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.407623E+10 | 0.943440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293726E+10 | 0.602471E+11 | 19142235.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196478E+10 | 0.266344E+11 | 0.521401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134110E+10 | 0.101836E+11 | 0.148042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106718E+10 | 0.355990E+10 | 0.442064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253038E+11 | 0.440705E+12 | 0.316489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101260E+10 | 0.167731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407623E+10 | 0.943440E+11 | 0.147311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.978913E+09 | 0.159176E+10 | 0.143099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944477E+09 | 0.422054E+10 | 0.702267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123975E+10 | 0.128808E+11 | 0.486890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141267E+10 | 0.230100E+11 | 0.119563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197129E+10 | 0.438601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267873E+10 | 0.655444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289545E+10 | 0.751332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317618E+10 | 0.839364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212647E+10 | 0.504726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143526E+10 | 0.218047E+11 | 0.131445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103306E+10 | 0.836477E+10 | 0.124729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971319E+09 | 0.300950E+10 | 0.475741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208636E+11 | 0.393829E+12 | 0.280751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.944477E+09 | 0.159176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.317618E+10 | 0.839364E+11 | 0.143099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123047E+10 | 0.164393E+10 | 0.241480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111074E+10 | 0.432094E+10 | 0.129941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129937E+10 | 0.133792E+11 | 0.147666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143895E+10 | 0.246039E+11 | 0.379959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198793E+10 | 0.472397E+11 | 1299211.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267610E+10 | 0.704143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289077E+10 | 0.802623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312146E+10 | 0.888859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199857E+10 | 0.519296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138158E+10 | 0.220299E+11 | 0.807049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110180E+10 | 0.843414E+10 | 0.359114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110800E+10 | 0.304626E+10 | 0.113578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213457E+11 | 0.416190E+12 | 0.547560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110180E+10 | 0.164393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312146E+10 | 0.888859E+11 | 0.241480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.102106E+10 | 0.00 | 0.00 | 0.00 | 0.414378E+09 | 0.147311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101260E+10 | 0.00 | 0.00 | 0.00 | 0.108354E+10 | 0.814535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142218E+10 | 0.00 | 0.00 | 0.00 | 0.324525E+10 | 0.147388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155853E+10 | 0.00 | 0.00 | 0.00 | 0.557027E+10 | 0.684882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.217506E+10 | 0.00 | 0.00 | 0.00 | 0.106332E+11 | 0.151542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317389E+10 | 0.00 | 0.00 | 0.00 | 0.168923E+11 | 20522924.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.355391E+10 | 0.00 | 0.00 | 0.00 | 0.197011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.407623E+10 | 0.00 | 0.00 | 0.00 | 0.222225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.293726E+10 | 0.00 | 0.00 | 0.00 | 0.135790E+11 | 19142235.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196478E+10 | 0.00 | 0.00 | 0.00 | 0.599001E+10 | 0.521401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134110E+10 | 0.00 | 0.00 | 0.00 | 0.239304E+10 | 0.148042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106718E+10 | 0.00 | 0.00 | 0.00 | 0.844131E+09 | 0.442064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253038E+11 | 0.00 | 0.00 | 0.00 | 0.102569E+12 | 0.316489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101260E+10 | 0.00 | 0.00 | 0.00 | 0.414378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.407623E+10 | 0.00 | 0.00 | 0.00 | 0.222225E+11 | 0.147311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.978913E+09 | 0.00 | 0.00 | 0.00 | 0.393152E+09 | 0.143099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944477E+09 | 0.00 | 0.00 | 0.00 | 0.103512E+10 | 0.702267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123975E+10 | 0.00 | 0.00 | 0.00 | 0.302495E+10 | 0.486890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141267E+10 | 0.00 | 0.00 | 0.00 | 0.531353E+10 | 0.119563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197129E+10 | 0.00 | 0.00 | 0.00 | 0.995993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267873E+10 | 0.00 | 0.00 | 0.00 | 0.154306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289545E+10 | 0.00 | 0.00 | 0.00 | 0.178473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.317618E+10 | 0.00 | 0.00 | 0.00 | 0.196978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212647E+10 | 0.00 | 0.00 | 0.00 | 0.114404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143526E+10 | 0.00 | 0.00 | 0.00 | 0.495676E+10 | 0.131445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103306E+10 | 0.00 | 0.00 | 0.00 | 0.200020E+10 | 0.124729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971319E+09 | 0.00 | 0.00 | 0.00 | 0.727473E+09 | 0.475741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208636E+11 | 0.00 | 0.00 | 0.00 | 0.918272E+11 | 0.280751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.944477E+09 | 0.00 | 0.00 | 0.00 | 0.393152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.317618E+10 | 0.00 | 0.00 | 0.00 | 0.196978E+11 | 0.143099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123047E+10 | 0.00 | 0.00 | 0.00 | 0.409224E+09 | 0.241480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111074E+10 | 0.00 | 0.00 | 0.00 | 0.106893E+10 | 0.129941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129937E+10 | 0.00 | 0.00 | 0.00 | 0.317156E+10 | 0.147666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143895E+10 | 0.00 | 0.00 | 0.00 | 0.571851E+10 | 0.379959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198793E+10 | 0.00 | 0.00 | 0.00 | 0.108075E+11 | 1299211.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267610E+10 | 0.00 | 0.00 | 0.00 | 0.166783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.289077E+10 | 0.00 | 0.00 | 0.00 | 0.192046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.312146E+10 | 0.00 | 0.00 | 0.00 | 0.209897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199857E+10 | 0.00 | 0.00 | 0.00 | 0.118759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138158E+10 | 0.00 | 0.00 | 0.00 | 0.505991E+10 | 0.807049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110180E+10 | 0.00 | 0.00 | 0.00 | 0.204175E+10 | 0.359114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110800E+10 | 0.00 | 0.00 | 0.00 | 0.743797E+09 | 0.113578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.213457E+11 | 0.00 | 0.00 | 0.00 | 0.977696E+11 | 0.547560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.110180E+10 | 0.00 | 0.00 | 0.00 | 0.409224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.312146E+10 | 0.00 | 0.00 | 0.00 | 0.209897E+11 | 0.241480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.965122E+10 | 0.00 | 0.00 | 4967773.69 | 6753496.89 | 1474738.91 | 0.385723E+10 | 0.00 | 0.33 |
February | 0.510295E+10 | 0.00 | 0.00 | 12782643.39 | 0.00 | 0.00 | 0.652351E+10 | 0.00 | 0.42 |
March | 0.802965E+09 | 0.240447E+09 | 0.00 | 31109096.63 | 11789118.28 | 0.00 | 0.123430E+11 | 0.00 | 0.61 |
April | 0.395758E+09 | 0.477808E+09 | 0.00 | 30092361.07 | 33830949.03 | 0.00 | 0.795339E+10 | 0.00 | 0.64 |
May | 80771582.11 | 0.277393E+10 | 0.00 | 14952883.65 | 43079392.52 | 0.00 | 0.279943E+10 | 0.00 | 0.52 |
June | 53265873.82 | 0.810018E+10 | 0.00 | 6981625.78 | 71600866.99 | 0.00 | 0.130401E+10 | 0.00 | 0.41 |
July | 0.00 | 0.106476E+11 | 0.00 | 0.00 | 0.194737E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 1501.16 | 0.126927E+11 | 0.00 | 264637.02 | 0.147439E+09 | 0.00 | 3529182.37 | 0.00 | 0.30 |
September | 47053832.51 | 0.515427E+10 | 0.00 | 14932933.39 | 99139513.63 | 0.00 | 0.195645E+10 | 0.00 | 0.49 |
October | 0.332269E+09 | 0.154655E+10 | 0.00 | 30945938.39 | 4186044.91 | 0.00 | 0.112863E+11 | 0.00 | 0.61 |
November | 0.900036E+09 | 0.161395E+09 | 0.00 | 31251606.38 | 14492475.65 | 0.00 | 0.130207E+11 | 0.00 | 0.58 |
December | 0.405462E+10 | 28197503.31 | 0.00 | 16085902.59 | 0.00 | 0.00 | 0.878180E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.214209E+11 | 0.418231E+11 | 0.00 | 0.194367E+09 | 0.627049E+09 | 1474738.91 | 0.698293E+11 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.965122E+10 | 0.126927E+11 | 0.00 | 31251606.38 | 0.194737E+09 | 1474738.91 | 0.130207E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120740E+11 | 0.00 | 0.00 | 0.00 | 13412449.86 | 0.547336E+09 | 0.00 | 0.00 | 0.32 |
February | 0.930202E+10 | 0.00 | 0.00 | 1166637.09 | 1984520.29 | 0.135817E+09 | 0.656921E+09 | 0.00 | 0.37 |
March | 0.597424E+10 | 97390276.37 | 0.00 | 7109953.39 | 0.120580E+09 | 0.00 | 0.361719E+10 | 0.00 | 0.45 |
April | 0.235216E+10 | 0.225467E+09 | 0.00 | 11712959.16 | 0.175361E+09 | 0.00 | 0.351597E+10 | 0.00 | 0.45 |
May | 0.476693E+09 | 0.199728E+10 | 0.00 | 7078009.32 | 0.132929E+09 | 0.00 | 0.150144E+10 | 0.00 | 0.37 |
June | 0.189071E+09 | 0.687949E+10 | 0.00 | 3830954.26 | 80145424.78 | 0.00 | 0.760333E+09 | 0.00 | 0.32 |
July | 0.00 | 0.904918E+10 | 0.00 | 0.00 | 0.334271E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 1650437.41 | 0.113146E+11 | 0.00 | 147704.61 | 0.146227E+09 | 0.00 | 3912635.37 | 0.00 | 0.26 |
September | 0.267174E+09 | 0.437934E+10 | 0.00 | 7142787.82 | 0.220494E+09 | 0.00 | 0.989014E+09 | 0.00 | 0.36 |
October | 0.358532E+10 | 0.127410E+10 | 0.00 | 8599524.90 | 18347901.76 | 0.00 | 0.385953E+10 | 0.00 | 0.42 |
November | 0.687881E+10 | 16618075.65 | 0.00 | 3889870.69 | 0.201730E+09 | 0.00 | 0.247370E+10 | 0.00 | 0.40 |
December | 0.101113E+11 | 21314078.05 | 0.00 | 428815.67 | 17038258.02 | 80037481.17 | 0.375633E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.512124E+11 | 0.352548E+11 | 0.00 | 51107216.92 | 0.146252E+10 | 0.763191E+09 | 0.177537E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1984520.29 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.120740E+11 | 0.113146E+11 | 0.00 | 11712959.16 | 0.334271E+09 | 0.547336E+09 | 0.385953E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.916738E+10 | 0.00 | 0.00 | 0.00 | 14874086.37 | 0.283051E+10 | 0.00 | 0.00 | 0.32 |
February | 0.801448E+10 | 0.00 | 0.00 | 571601.27 | 5294103.43 | 0.116016E+10 | 0.317192E+09 | 0.00 | 0.37 |
March | 0.703031E+10 | 0.100097E+09 | 0.00 | 3675835.55 | 0.129396E+09 | 11044546.91 | 0.184081E+10 | 0.00 | 0.44 |
April | 0.269495E+10 | 0.203255E+09 | 0.00 | 10539987.95 | 0.156245E+09 | 0.00 | 0.264079E+10 | 0.00 | 0.46 |
May | 0.537297E+09 | 0.185279E+10 | 0.00 | 5237962.78 | 0.168819E+09 | 0.00 | 0.116151E+10 | 0.00 | 0.36 |
June | 0.279217E+09 | 0.665863E+10 | 0.00 | 3201668.23 | 82265957.90 | 0.00 | 0.575592E+09 | 0.00 | 0.32 |
July | 0.00 | 0.881013E+10 | 0.00 | 0.00 | 0.373937E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.110986E+11 | 0.00 | 0.00 | 0.136323E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.331293E+09 | 0.411088E+10 | 0.00 | 5681524.22 | 0.516531E+09 | 0.00 | 0.665224E+09 | 0.00 | 0.36 |
October | 0.430959E+10 | 0.121834E+10 | 0.00 | 4099529.70 | 0.103687E+09 | 5535957.23 | 0.212734E+10 | 0.00 | 0.39 |
November | 0.763193E+10 | 12653568.95 | 745418.76 | 981162.49 | 0.233290E+09 | 0.126141E+09 | 0.672973E+09 | 29898.76 | 0.39 |
December | 0.891309E+10 | 848908.63 | 0.00 | 97828.31 | 40260547.37 | 0.796545E+09 | 52118971.18 | 0.00 | 0.34 |
Annual Sum or Average | 0.489095E+11 | 0.340662E+11 | 745418.76 | 34087100.52 | 0.196092E+10 | 0.492993E+10 | 0.100535E+11 | 29898.76 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5294103.43 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.916738E+10 | 0.110986E+11 | 745418.76 | 10539987.95 | 0.516531E+09 | 0.283051E+10 | 0.264079E+10 | 29898.76 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487165E+09 | 0.00 | 0.00 | 0.00 | 3141528.47 | 0.234127E+10 | 0.00 | 0.00 | 0.34 |
February | 0.816342E+09 | 0.00 | 243137.76 | 102166.10 | 874506.02 | 0.129337E+10 | 30632122.66 | 514.08 | 0.38 |
March | 0.151103E+10 | 24556722.75 | 0.00 | 572408.89 | 25891189.89 | 0.189849E+09 | 0.175926E+09 | 0.00 | 0.45 |
April | 0.713963E+09 | 70512323.24 | 0.00 | 2087942.72 | 16168972.41 | 41908185.15 | 0.380868E+09 | 0.00 | 0.50 |
May | 0.161527E+09 | 0.530605E+09 | 0.00 | 1104030.29 | 36271712.93 | 0.00 | 0.214276E+09 | 0.00 | 0.43 |
June | 65349487.85 | 0.217197E+10 | 0.00 | 863070.11 | 21497775.11 | 0.00 | 0.132566E+09 | 0.00 | 0.45 |
July | 0.00 | 0.293387E+10 | 0.00 | 0.00 | 52717691.19 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.346756E+10 | 0.00 | 0.00 | 32556148.18 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 99371326.92 | 0.111851E+10 | 0.00 | 1161102.17 | 87249885.29 | 0.00 | 0.123291E+09 | 0.00 | 0.41 |
October | 0.106474E+10 | 0.285465E+09 | 0.00 | 437866.64 | 31280640.24 | 92664462.44 | 0.182756E+09 | 0.00 | 0.39 |
November | 0.134303E+10 | 2350833.53 | 3851719.62 | 53373.11 | 46019805.21 | 0.423624E+09 | 32621170.55 | 11414.32 | 0.39 |
December | 0.908289E+09 | 175655.59 | 0.00 | 1201.30 | 8506997.13 | 0.126906E+10 | 271469.15 | 0.00 | 0.36 |
Annual Sum or Average | 0.717081E+10 | 0.106056E+11 | 4094857.38 | 6383161.32 | 0.362177E+09 | 0.565174E+10 | 0.127321E+10 | 11928.40 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 874506.02 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.151103E+10 | 0.346756E+10 | 3851719.62 | 2087942.72 | 87249885.29 | 0.234127E+10 | 0.380868E+09 | 11414.32 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.596017E+09 | 0.00 | 0.00 | 0.00 | 1987404.50 | 0.116426E+10 | 0.00 | 0.00 | 0.34 |
February | 0.582015E+09 | 0.00 | 153520.29 | 399609.66 | 553232.99 | 0.613232E+09 | 0.168685E+09 | 619.57 | 0.40 |
March | 0.715767E+09 | 25645470.03 | 0.00 | 1539194.31 | 9769642.20 | 75428178.47 | 0.532438E+09 | 0.00 | 0.52 |
April | 0.281985E+09 | 58042805.62 | 0.00 | 3398973.12 | 5730963.91 | 14508972.79 | 0.708458E+09 | 0.00 | 0.73 |
May | 67567215.51 | 0.509355E+09 | 0.00 | 1597506.51 | 17399160.77 | 0.00 | 0.310007E+09 | 0.00 | 0.63 |
June | 29045700.05 | 0.183267E+10 | 0.00 | 1108256.69 | 10132996.90 | 0.00 | 0.193510E+09 | 0.00 | 0.64 |
July | 0.00 | 0.257151E+10 | 0.00 | 0.00 | 31909738.29 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.293282E+10 | 0.00 | 0.00 | 19274060.80 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 55090125.95 | 0.104676E+10 | 0.00 | 1406441.67 | 38588146.18 | 0.00 | 0.151910E+09 | 0.00 | 0.59 |
October | 0.503631E+09 | 0.246621E+09 | 0.00 | 1252507.27 | 12041475.58 | 49525378.32 | 0.499912E+09 | 0.00 | 0.50 |
November | 0.830587E+09 | 2208404.19 | 2442631.00 | 347239.11 | 28787216.39 | 0.175770E+09 | 0.147222E+09 | 6601.08 | 0.40 |
December | 0.816058E+09 | 1441454.01 | 0.00 | 12791.88 | 4051395.50 | 0.543875E+09 | 2115285.41 | 0.00 | 0.35 |
Annual Sum or Average | 0.447776E+10 | 0.922707E+10 | 2596151.29 | 11062520.22 | 0.180225E+09 | 0.263660E+10 | 0.271426E+10 | 7220.65 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 553232.99 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.830587E+09 | 0.293282E+10 | 2442631.00 | 3398973.12 | 38588146.18 | 0.116426E+10 | 0.708458E+09 | 6601.08 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.900067E+09 | 0.00 | 0.00 | 1136212.37 | 3130925.93 | 0.136878E+10 | 0.678278E+09 | 0.00 | 0.36 |
February | 0.832612E+09 | 0.00 | 0.00 | 2220978.84 | 1114384.12 | 0.777314E+09 | 0.880702E+09 | 0.00 | 0.49 |
March | 0.106711E+10 | 60225706.89 | 0.00 | 3992540.72 | 11120933.04 | 0.124650E+09 | 0.128896E+10 | 0.00 | 0.64 |
April | 0.539599E+09 | 89084469.80 | 0.00 | 4468915.90 | 11787592.67 | 37129517.51 | 0.885810E+09 | 0.00 | 0.68 |
May | 0.157013E+09 | 0.602371E+09 | 0.00 | 1471820.97 | 36706495.28 | 0.00 | 0.275477E+09 | 0.00 | 0.49 |
June | 72222202.26 | 0.221550E+10 | 0.00 | 876440.35 | 26721925.66 | 0.00 | 0.131915E+09 | 0.00 | 0.46 |
July | 0.00 | 0.306063E+10 | 0.00 | 0.00 | 53454091.14 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.402400E+10 | 0.00 | 0.00 | 28859132.62 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 90672895.88 | 0.154382E+10 | 0.00 | 2214801.40 | 66790547.62 | 0.00 | 0.229692E+09 | 0.00 | 0.58 |
October | 0.690005E+09 | 0.459391E+09 | 0.00 | 4171164.16 | 18143216.22 | 67131066.64 | 0.142278E+10 | 0.00 | 0.67 |
November | 0.994165E+09 | 11306380.50 | 1372640.61 | 3933867.19 | 41003902.67 | 0.225953E+09 | 0.129275E+10 | 8609.47 | 0.58 |
December | 0.102472E+10 | 5365305.44 | 0.00 | 2278105.90 | 4636875.43 | 0.580994E+09 | 0.947173E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.636819E+10 | 0.120717E+11 | 1372640.61 | 26764847.81 | 0.303470E+09 | 0.318195E+10 | 0.803354E+10 | 8609.47 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1114384.12 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.106711E+10 | 0.402400E+10 | 1372640.61 | 4468915.90 | 66790547.62 | 0.136878E+10 | 0.142278E+10 | 8609.47 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.498853E+09 | 0.00 | 0.00 | 11748.18 | 1990592.63 | 0.127701E+10 | 20738081.91 | 0.00 | 0.35 |
February | 0.561487E+09 | 0.00 | 0.00 | 428572.41 | 708507.60 | 0.712811E+09 | 0.150077E+09 | 0.00 | 0.42 |
March | 0.800560E+09 | 35492250.96 | 0.00 | 1600983.04 | 8393741.02 | 0.107749E+09 | 0.522183E+09 | 0.00 | 0.58 |
April | 0.358442E+09 | 58008023.10 | 0.00 | 3200117.43 | 8495052.94 | 24240072.80 | 0.616673E+09 | 0.00 | 0.74 |
May | 91366927.61 | 0.447214E+09 | 0.00 | 1300201.77 | 17901944.83 | 0.00 | 0.258611E+09 | 0.00 | 0.61 |
June | 45651475.94 | 0.173713E+10 | 0.00 | 811329.91 | 10343064.86 | 0.00 | 0.117083E+09 | 0.00 | 0.59 |
July | 0.00 | 0.236232E+10 | 0.00 | 0.00 | 25718165.92 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.289667E+10 | 0.00 | 0.00 | 7376184.12 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 60212266.47 | 0.967741E+09 | 0.00 | 1236804.17 | 40182175.76 | 0.00 | 0.122101E+09 | 0.00 | 0.55 |
October | 0.572932E+09 | 0.232319E+09 | 0.00 | 1256548.84 | 15254250.47 | 53189439.41 | 0.434181E+09 | 0.00 | 0.51 |
November | 0.756596E+09 | 1900710.96 | 2446242.76 | 644620.16 | 28903412.74 | 0.240443E+09 | 0.246326E+09 | 6578.63 | 0.44 |
December | 0.665763E+09 | 313474.63 | 0.00 | 94395.73 | 5211929.81 | 0.681699E+09 | 43475692.97 | 0.00 | 0.36 |
Annual Sum or Average | 0.441186E+10 | 0.873911E+10 | 2446242.76 | 10585321.64 | 0.170479E+09 | 0.309714E+10 | 0.253145E+10 | 6578.63 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 708507.60 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.800560E+09 | 0.289667E+10 | 2446242.76 | 3200117.43 | 40182175.76 | 0.127701E+10 | 0.616673E+09 | 6578.63 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.741267E+09 | 0.00 | 0.00 | 0.00 | 1420931.17 | 0.213507E+10 | 0.00 | 0.00 | 0.32 |
February | 0.112626E+10 | 0.00 | 0.00 | 17202.85 | 0.00 | 0.113716E+10 | 4284445.51 | 0.00 | 0.37 |
March | 0.182389E+10 | 8463447.14 | 0.00 | 94326.53 | 32988212.45 | 86892075.01 | 43145392.51 | 0.00 | 0.42 |
April | 0.100361E+10 | 22456310.87 | 0.00 | 491634.83 | 53474156.26 | 18911455.82 | 94188530.88 | 0.00 | 0.40 |
May | 0.260620E+09 | 0.363127E+09 | 0.00 | 505278.19 | 58689763.02 | 0.00 | 0.101802E+09 | 0.00 | 0.33 |
June | 76925606.38 | 0.161190E+10 | 0.00 | 664258.83 | 19161439.94 | 0.00 | 0.110267E+09 | 0.00 | 0.34 |
July | 0.00 | 0.226151E+10 | 0.00 | 0.00 | 47875386.24 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 312348.31 | 0.272583E+10 | 0.00 | 5150.86 | 31021147.12 | 0.00 | 172136.74 | 0.00 | 0.30 |
September | 0.107014E+09 | 0.942392E+09 | 0.00 | 1355332.41 | 23117397.34 | 0.00 | 0.165271E+09 | 0.00 | 0.36 |
October | 0.122511E+10 | 0.245889E+09 | 0.00 | 745580.37 | 3415978.47 | 329414.28 | 0.311285E+09 | 0.00 | 0.39 |
November | 0.189497E+10 | 1083565.85 | 0.00 | 191108.20 | 28978457.78 | 41322021.77 | 96735854.86 | 0.00 | 0.39 |
December | 0.186130E+10 | 260447.19 | 0.00 | 1488.64 | 3436014.65 | 0.556555E+09 | 504080.89 | 0.00 | 0.35 |
Annual Sum or Average | 0.101213E+11 | 0.818291E+10 | 0.00 | 4071361.73 | 0.303579E+09 | 0.397624E+10 | 0.927656E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.189497E+10 | 0.272583E+10 | 0.00 | 1355332.41 | 58689763.02 | 0.213507E+10 | 0.311285E+09 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799253E+09 | 0.00 | 0.00 | 0.00 | 897993.13 | 0.102106E+10 | 0.00 | 0.00 | 0.32 |
February | 0.796207E+09 | 0.00 | 0.00 | 328201.91 | 0.00 | 0.501350E+09 | 0.155874E+09 | 0.00 | 0.38 |
March | 0.899316E+09 | 9776122.05 | 0.00 | 958801.70 | 18293466.55 | 29029902.37 | 0.375654E+09 | 0.00 | 0.45 |
April | 0.395435E+09 | 32249569.39 | 0.00 | 2050589.24 | 20624024.29 | 3706212.73 | 0.474263E+09 | 0.00 | 0.54 |
May | 95789224.17 | 0.388084E+09 | 0.00 | 1333859.38 | 24399294.15 | 0.00 | 0.251792E+09 | 0.00 | 0.51 |
June | 31744056.36 | 0.143900E+10 | 0.00 | 1026050.83 | 9891367.91 | 0.00 | 0.184065E+09 | 0.00 | 0.52 |
July | 0.00 | 0.207515E+10 | 0.00 | 0.00 | 30177598.36 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 152582.84 | 0.239469E+10 | 0.00 | 5430.83 | 19604592.81 | 0.00 | 154301.46 | 0.00 | 0.41 |
September | 55293315.29 | 0.866413E+09 | 0.00 | 1640710.69 | 14154123.15 | 0.00 | 0.202297E+09 | 0.00 | 0.54 |
October | 0.495465E+09 | 0.209686E+09 | 0.00 | 2083737.78 | 942824.84 | 398508.26 | 0.793630E+09 | 0.00 | 0.53 |
November | 0.963555E+09 | 3869784.03 | 0.00 | 868938.96 | 15387236.83 | 7620434.22 | 0.391925E+09 | 0.00 | 0.42 |
December | 0.134856E+10 | 1402978.28 | 0.00 | 27568.54 | 933093.59 | 0.170978E+09 | 9701182.39 | 0.00 | 0.35 |
Annual Sum or Average | 0.588077E+10 | 0.742031E+10 | 0.00 | 10323889.85 | 0.155306E+09 | 0.173414E+10 | 0.283936E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.134856E+10 | 0.239469E+10 | 0.00 | 2083737.78 | 30177598.36 | 0.102106E+10 | 0.793630E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.113279E+10 | 0.00 | 0.00 | 122966.32 | 1421195.65 | 0.235328E+10 | 82640571.62 | 0.00 | 0.39 |
February | 0.103978E+10 | 0.00 | 0.00 | 1034380.90 | 0.00 | 0.146521E+10 | 0.300669E+09 | 0.00 | 0.47 |
March | 0.136888E+10 | 44405370.85 | 0.00 | 1291554.59 | 13293861.39 | 0.508772E+09 | 0.395093E+09 | 0.00 | 0.51 |
April | 0.841255E+09 | 49186546.92 | 0.00 | 1627011.23 | 38591079.66 | 0.265046E+09 | 0.164534E+09 | 0.00 | 0.49 |
May | 0.251336E+09 | 0.470025E+09 | 0.00 | 518472.00 | 66453999.97 | 59350268.22 | 87841896.57 | 0.00 | 0.38 |
June | 96045625.24 | 0.191119E+10 | 0.00 | 523309.83 | 63160344.11 | 10682133.41 | 72950882.85 | 0.00 | 0.38 |
July | 0.00 | 0.265849E+10 | 0.00 | 0.00 | 96529257.27 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 489727.05 | 0.363069E+10 | 0.00 | 0.00 | 45969688.39 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.127449E+09 | 0.137240E+10 | 0.00 | 1984912.05 | 40656647.72 | 11716049.05 | 0.198626E+09 | 0.00 | 0.52 |
October | 0.813882E+09 | 0.401340E+09 | 0.00 | 3503708.50 | 6783108.84 | 0.242429E+09 | 0.113449E+10 | 0.00 | 0.63 |
November | 0.119707E+10 | 12243375.72 | 0.00 | 3270516.61 | 20410968.51 | 0.451765E+09 | 0.110215E+10 | 0.00 | 0.57 |
December | 0.152714E+10 | 2269244.83 | 0.00 | 1103716.50 | 1873865.73 | 0.845887E+09 | 0.525066E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.839611E+10 | 0.105522E+11 | 0.00 | 14980548.54 | 0.395144E+09 | 0.621413E+10 | 0.406407E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.152714E+10 | 0.363069E+10 | 0.00 | 3503708.50 | 96529257.27 | 0.235328E+10 | 0.113449E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.714227E+09 | 0.00 | 0.00 | 0.00 | 899860.25 | 0.110946E+10 | 0.00 | 0.00 | 0.32 |
February | 0.809339E+09 | 0.00 | 0.00 | 255736.03 | 0.00 | 0.575283E+09 | 71173166.22 | 0.00 | 0.38 |
March | 0.103567E+10 | 26395283.98 | 0.00 | 872310.94 | 9398944.69 | 20852657.53 | 0.270879E+09 | 0.00 | 0.48 |
April | 0.496047E+09 | 37062511.37 | 0.00 | 1605930.06 | 19525800.11 | 6457165.79 | 0.306386E+09 | 0.00 | 0.52 |
May | 0.123210E+09 | 0.360072E+09 | 0.00 | 867037.98 | 20044321.31 | 0.00 | 0.171864E+09 | 0.00 | 0.47 |
June | 47117109.70 | 0.137848E+10 | 0.00 | 667914.78 | 8316890.64 | 0.00 | 97918152.93 | 0.00 | 0.47 |
July | 0.00 | 0.192832E+10 | 0.00 | 0.00 | 22051585.43 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 152900.09 | 0.238569E+10 | 0.00 | 10235.04 | 11644096.33 | 0.00 | 149198.52 | 0.00 | 0.40 |
September | 56853270.56 | 0.842061E+09 | 0.00 | 1381421.90 | 12620792.69 | 0.00 | 0.152082E+09 | 0.00 | 0.50 |
October | 0.576229E+09 | 0.210654E+09 | 0.00 | 1727776.41 | 944785.17 | 190722.36 | 0.600583E+09 | 0.00 | 0.52 |
November | 0.103632E+10 | 4401364.47 | 0.00 | 894430.35 | 14807783.08 | 17720905.34 | 0.339804E+09 | 0.00 | 0.45 |
December | 0.125149E+10 | 988431.38 | 0.00 | 114034.29 | 1359419.20 | 0.227792E+09 | 56160624.23 | 0.00 | 0.35 |
Annual Sum or Average | 0.614665E+10 | 0.717413E+10 | 0.00 | 8396827.79 | 0.121614E+09 | 0.195775E+10 | 0.206700E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.125149E+10 | 0.238569E+10 | 0.00 | 1727776.41 | 22051585.43 | 0.110946E+10 | 0.600583E+09 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.795672E+09 | 0.00 | 0.00 | 0.00 | 2834813.91 | 0.195882E+10 | 0.00 | 0.00 | 0.32 |
February | 0.119100E+10 | 0.00 | 0.00 | 129306.21 | 419442.07 | 0.966276E+09 | 24478133.14 | 0.00 | 0.37 |
March | 0.174909E+10 | 27096098.40 | 0.00 | 641582.54 | 21999390.44 | 43700912.51 | 0.210329E+09 | 0.00 | 0.45 |
April | 0.793607E+09 | 84989001.73 | 0.00 | 1892763.46 | 12054921.38 | 9659726.76 | 0.394876E+09 | 0.00 | 0.47 |
May | 0.181619E+09 | 0.595430E+09 | 0.00 | 1278242.74 | 19244257.75 | 0.00 | 0.225779E+09 | 0.00 | 0.43 |
June | 68685229.14 | 0.230486E+10 | 0.00 | 871406.66 | 15676533.09 | 0.00 | 0.139845E+09 | 0.00 | 0.45 |
July | 0.00 | 0.309338E+10 | 0.00 | 0.00 | 48332977.40 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 718078.92 | 0.361630E+10 | 0.00 | 7714.70 | 30906033.61 | 0.00 | 382099.10 | 0.00 | 0.39 |
September | 0.121011E+09 | 0.118705E+10 | 0.00 | 1174805.21 | 33193677.74 | 0.00 | 0.131295E+09 | 0.00 | 0.40 |
October | 0.121424E+10 | 0.304221E+09 | 0.00 | 628970.14 | 9874528.98 | 14088188.12 | 0.253855E+09 | 0.00 | 0.40 |
November | 0.171108E+10 | 3521646.88 | 168711.50 | 130463.69 | 42550280.82 | 0.175295E+09 | 76369549.24 | 2068.17 | 0.39 |
December | 0.150758E+10 | 1719890.99 | 0.00 | 12175.35 | 6386140.12 | 0.750659E+09 | 1911761.18 | 0.00 | 0.35 |
Annual Sum or Average | 0.933430E+10 | 0.112186E+11 | 168711.50 | 6767430.68 | 0.243473E+09 | 0.391850E+10 | 0.145912E+10 | 2068.17 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 419442.07 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.174909E+10 | 0.361630E+10 | 168711.50 | 1892763.46 | 48332977.40 | 0.195882E+10 | 0.394876E+09 | 2068.17 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.578930E+09 | 0.00 | 0.00 | 1835.38 | 1792944.99 | 0.885892E+09 | 791223.18 | 0.00 | 0.27 |
February | 0.613827E+09 | 0.00 | 0.00 | 531874.20 | 265286.04 | 0.414043E+09 | 0.196870E+09 | 0.00 | 0.34 |
March | 0.685941E+09 | 24918258.55 | 0.00 | 1704687.84 | 6694857.15 | 15939904.76 | 0.621783E+09 | 0.00 | 0.49 |
April | 0.305695E+09 | 63220049.84 | 0.00 | 3121053.96 | 5097662.10 | 3567984.11 | 0.732239E+09 | 0.00 | 0.66 |
May | 79748089.27 | 0.507585E+09 | 0.00 | 1730826.78 | 10473404.93 | 0.00 | 0.325050E+09 | 0.00 | 0.61 |
June | 31346784.57 | 0.181853E+10 | 0.00 | 1118222.93 | 9689478.34 | 0.00 | 0.201193E+09 | 0.00 | 0.61 |
July | 0.00 | 0.255152E+10 | 0.00 | 0.00 | 29847150.47 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 420412.00 | 0.289113E+10 | 0.00 | 9227.11 | 19547250.71 | 0.00 | 281605.39 | 0.00 | 0.49 |
September | 64338018.08 | 0.991964E+09 | 0.00 | 1364314.93 | 18166989.65 | 0.00 | 0.160085E+09 | 0.00 | 0.54 |
October | 0.494939E+09 | 0.224123E+09 | 0.00 | 1609925.28 | 4402264.10 | 8237452.97 | 0.601683E+09 | 0.00 | 0.48 |
November | 0.810368E+09 | 5948024.80 | 107559.24 | 615479.71 | 20245175.65 | 54389291.86 | 0.247086E+09 | 454.40 | 0.36 |
December | 0.874207E+09 | 1856486.64 | 0.00 | 43517.88 | 2271459.76 | 0.286703E+09 | 16671129.83 | 0.00 | 0.29 |
Annual Sum or Average | 0.453976E+10 | 0.908079E+10 | 107559.24 | 11850966.00 | 0.128494E+09 | 0.166877E+10 | 0.310373E+10 | 454.40 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 265286.04 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.874207E+09 | 0.289113E+10 | 107559.24 | 3121053.96 | 29847150.47 | 0.885892E+09 | 0.732239E+09 | 454.40 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119567E+10 | 0.00 | 0.00 | 1578857.85 | 2832924.64 | 0.101353E+10 | 0.861565E+09 | 0.00 | 0.36 |
February | 0.115883E+10 | 0.00 | 0.00 | 2640949.84 | 419162.53 | 0.482776E+09 | 0.998955E+09 | 0.00 | 0.50 |
March | 0.119837E+10 | 70009545.17 | 0.00 | 4330873.40 | 7373552.73 | 18814672.34 | 0.141977E+10 | 0.00 | 0.65 |
April | 0.621903E+09 | 0.111480E+09 | 0.00 | 4039355.15 | 8811469.95 | 6325682.72 | 0.860341E+09 | 0.00 | 0.64 |
May | 0.187678E+09 | 0.687525E+09 | 0.00 | 1522363.11 | 18517021.28 | 0.00 | 0.263072E+09 | 0.00 | 0.49 |
June | 82639615.31 | 0.236578E+10 | 0.00 | 826288.90 | 15955106.74 | 0.00 | 0.123918E+09 | 0.00 | 0.46 |
July | 0.00 | 0.324925E+10 | 0.00 | 0.00 | 48300765.77 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 609107.89 | 0.422896E+10 | 0.00 | 7394.65 | 30885436.21 | 0.00 | 490111.00 | 0.00 | 0.45 |
September | 0.113975E+09 | 0.162746E+10 | 0.00 | 2083388.27 | 29522708.20 | 0.00 | 0.214671E+09 | 0.00 | 0.56 |
October | 0.789689E+09 | 0.469024E+09 | 0.00 | 4822493.80 | 6478931.92 | 13862341.62 | 0.158685E+10 | 0.00 | 0.71 |
November | 0.115284E+10 | 15093889.24 | 0.00 | 5050290.70 | 33816355.13 | 58284384.97 | 0.164890E+10 | 0.00 | 0.63 |
December | 0.133492E+10 | 9384296.26 | 0.00 | 3039890.75 | 2636643.36 | 0.301094E+09 | 0.121744E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.783712E+10 | 0.128340E+11 | 0.00 | 29942146.42 | 0.205550E+09 | 0.189469E+10 | 0.919597E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 419162.53 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.133492E+10 | 0.422896E+10 | 0.00 | 5050290.70 | 48300765.77 | 0.101353E+10 | 0.164890E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.644103E+09 | 0.00 | 0.00 | 29021.16 | 1797295.04 | 0.107471E+10 | 39391727.65 | 0.00 | 0.33 |
February | 0.786040E+09 | 0.00 | 0.00 | 477162.22 | 265929.68 | 0.508097E+09 | 0.151736E+09 | 0.00 | 0.41 |
March | 0.937438E+09 | 44612822.69 | 0.00 | 1632525.37 | 5485988.73 | 18484596.04 | 0.532187E+09 | 0.00 | 0.58 |
April | 0.414923E+09 | 75237511.81 | 0.00 | 2803167.29 | 5530445.71 | 5509416.00 | 0.571193E+09 | 0.00 | 0.69 |
May | 0.106397E+09 | 0.523298E+09 | 0.00 | 1274290.82 | 6951797.87 | 0.00 | 0.240961E+09 | 0.00 | 0.60 |
June | 51204362.29 | 0.189517E+10 | 0.00 | 748352.02 | 5843301.06 | 0.00 | 0.105149E+09 | 0.00 | 0.60 |
July | 0.00 | 0.255644E+10 | 0.00 | 0.00 | 20922275.72 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 386436.89 | 0.308084E+10 | 0.00 | 6473.83 | 8308672.61 | 0.00 | 310447.93 | 0.00 | 0.51 |
September | 72889843.10 | 0.103051E+10 | 0.00 | 1162407.00 | 17976599.21 | 0.00 | 0.112583E+09 | 0.00 | 0.54 |
October | 0.656753E+09 | 0.248029E+09 | 0.00 | 1442667.72 | 4554196.66 | 9290989.67 | 0.478250E+09 | 0.00 | 0.53 |
November | 0.989145E+09 | 6044854.27 | 107762.95 | 803108.30 | 23468644.36 | 85534587.30 | 0.285188E+09 | 512.74 | 0.45 |
December | 0.983755E+09 | 2066994.50 | 0.00 | 135024.46 | 3270992.05 | 0.392879E+09 | 70501554.41 | 0.00 | 0.36 |
Annual Sum or Average | 0.564303E+10 | 0.946224E+10 | 107762.95 | 10514200.18 | 0.104376E+09 | 0.209450E+10 | 0.258745E+10 | 512.74 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 265929.68 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.989145E+09 | 0.308084E+10 | 107762.95 | 2803167.29 | 23468644.36 | 0.107471E+10 | 0.571193E+09 | 512.74 | 0.69 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.187107E+12 | 0.106504E+11 | 0.00 | 0.188021E+12 | 0.612975E+10 |
February | 0.185298E+12 | 0.873734E+10 | 0.00 | 0.181527E+12 | 0.161737E+11 |
March | 0.266977E+12 | 0.570051E+10 | 0.00 | 0.192667E+12 | 0.496148E+11 |
April | 0.296226E+12 | 0.260127E+10 | 0.00 | 0.124743E+12 | 0.884035E+11 |
May | 0.324886E+12 | -305108086.6 | 0.00 | 0.367682E+11 | 0.169554E+12 |
June | 0.314975E+12 | -0.404255E+10 | 0.00 | -0.178022E+11 | 0.256704E+12 |
July | 0.305366E+12 | -0.578185E+10 | 0.00 | -0.612106E+11 | 0.294865E+12 |
August | 0.284865E+12 | -0.714955E+10 | 0.00 | -0.740823E+11 | 0.330076E+12 |
September | 0.223413E+12 | -0.198194E+10 | 0.00 | -0.294343E+10 | 0.199545E+12 |
October | 0.215441E+12 | 0.277496E+10 | 0.00 | 0.138416E+12 | 0.864757E+11 |
November | 0.159158E+12 | 0.577797E+10 | 0.00 | 0.176685E+12 | 0.334175E+11 |
December | 0.152819E+12 | 0.926032E+10 | 0.00 | 0.207500E+12 | 0.119311E+11 |
Annual Sum or Average | 0.291653E+13 | 0.262418E+11 | 0.00 | 0.109029E+13 | 0.154289E+13 |
Minimum of Months | 0.152819E+12 | -0.714955E+10 | 0.00 | -0.740823E+11 | 0.612975E+10 |
Maximum of Months | 0.324886E+12 | 0.106504E+11 | 0.00 | 0.207500E+12 | 0.330076E+12 |