Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2024-07-03 12:20:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1661.57 | 333.50 | 333.50 |
Net Site Energy | 1661.57 | 333.50 | 333.50 |
Total Source Energy | 5262.19 | 1056.20 | 1056.20 |
Net Source Energy | 5262.19 | 1056.20 | 1056.20 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 10.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 495.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 83.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1661.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 10.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 495.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 83.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 42.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 10.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 495.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 83.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 42.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 126.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 333.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 126.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 333.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1661.570 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1661.570 | 100.00 |
Total On-Site and Utility Electric Sources | 1661.570 | 100.00 |
Total Electricity End Uses | 1661.570 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 65.33 |
Time Setpoint Not Met During Occupied Cooling | 357.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1436.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 04-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71703.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14507.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3198.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 152167.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71703.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14507.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3198.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 34.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1570.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 733.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 161.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 264.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 133.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5262.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 315.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1056.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 6.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 315.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1056.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.48 | 0.302186 | 0.257000 | 0.637388 | 0.805829 | 0.500000 | 0.001261 |
CORE_MID VAV BOX COMPONENT | 1.98 | 0.378996 | 0.322000 | 0.636747 | 1.00 | 0.500000 | 0.001005 |
CORE_TOP VAV BOX COMPONENT | 2.12 | 0.353711 | 0.301000 | 0.637770 | 0.943228 | 0.500000 | 0.001077 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.656375 | 0.240703 | 0.205000 | 0.134557 | 0.641876 | 0.500000 | 0.001583 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.666659 | 0.150034 | 0.128000 | 0.085332 | 0.400092 | 0.500000 | 0.002539 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.802644 | 0.196839 | 0.167000 | 0.134041 | 0.524904 | 0.500000 | 0.001936 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.738390 | 0.135450 | 0.115000 | 0.084915 | 0.361201 | 0.500000 | 0.002813 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.564737 | 0.279762 | 0.238000 | 0.134407 | 0.746031 | 0.500000 | 0.001362 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.597574 | 0.167380 | 0.142000 | 0.084856 | 0.446346 | 0.500000 | 0.002276 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.698087 | 0.226321 | 0.192000 | 0.134033 | 0.603522 | 0.500000 | 0.001683 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.622500 | 0.160667 | 0.137000 | 0.085282 | 0.428446 | 0.500000 | 0.002371 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.566900 | 0.278694 | 0.237000 | 0.134355 | 0.743184 | 0.500000 | 0.001367 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.643939 | 0.414208 | 0.500000 | 0.002453 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.711545 | 0.222040 | 0.189000 | 0.134482 | 0.592108 | 0.500000 | 0.001716 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.671324 | 0.148982 | 0.127000 | 0.085258 | 0.397285 | 0.500000 | 0.002557 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21270.43 |
CORE_MID VAV BOX REHEAT COIL | 21249.03 |
CORE_TOP VAV BOX REHEAT COIL | 26334.68 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 10937.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7138.63 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 10908.58 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7124.27 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7179.05 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4770.90 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7140.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4745.40 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8427.64 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5573.40 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8381.56 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5549.59 |
PACU_VAV_BOT HEATING COIL | 5659.35 |
PACU_VAV_MID HEATING COIL | 7499.15 |
PACU_VAV_TOP HEATING COIL | 6456.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.48 | 1.08 | 4.96 | 1.14 | 4.47 | 4.47 | 0.300000 | 0.254730 | 4.47 |
PACU_VAV_MID | 2.29 | 1.08 | 4.57 | 1.26 | 3.98 | 3.98 | 0.300000 | 0.316872 | 3.98 |
PACU_VAV_TOP | 2.49 | 1.08 | 4.98 | 1.93 | 4.66 | 4.66 | 0.300000 | 0.413382 | 4.66 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.47 |
PACU_VAV_MID_OA_CONTROLLER | 3.98 |
PACU_VAV_TOP_OA_CONTROLLER | 4.66 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.47 | 104629.74 | 0.720075 | 1.49 | 34873.09 | 0.720075 |
PACU_VAV_MID COOLING COIL | 3.98 | 96412.80 | 0.709346 | 1.33 | 32134.39 | 0.709346 |
PACU_VAV_TOP COOLING COIL | 4.66 | 107662.07 | 0.724541 | 1.55 | 35883.77 | 0.724541 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.47 |
PACU_VAV_MID FAN | 3.98 |
PACU_VAV_TOP FAN | 4.66 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.015 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.000 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.258 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7516 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7656 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5610 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27848788E-12 | 0.13637022E-14 | -0.81023097E-13 | 0.79216012E-16 |
43 | 6 | 0.25824895E-07 | 0.27625343E-09 | 0.59397345E-08 | -0.11998209E-12 |
44 | 5 | -0.17554640E-03 | 0.24097886E-05 | -0.90470599E-04 | 0.58795774E-08 |
45 | 4 | 0.27494803 | 0.11927753E-02 | 0.93505830E-01 | -0.31160983E-04 |
46 | 3 | -6.9253412 | 0.37505722E-01 | -2.2377579 | 0.27339040E-01 |
47 | 2 | 39.746130 | 0.13507978 | 14.849253 | -0.32081291 |
48 | 1 | -79.683230 | 0.61641880E-01 | -28.768593 | 1.0602386 |
49 | 0 | 46.824344 | 0.12537427E-02 | 16.300359 | |
50 | 7 | -0.27402251E-12 | 0.13062726E-14 | -0.81664977E-13 | 0.79643054E-16 |
51 | 6 | 0.25995733E-07 | 0.27297844E-09 | 0.59774430E-08 | -0.12089174E-12 |
52 | 5 | -0.17642699E-03 | 0.23783059E-05 | -0.90913883E-04 | 0.59164366E-08 |
53 | 4 | 0.27599802 | 0.11759213E-02 | 0.93882490E-01 | -0.31307097E-04 |
54 | 3 | -6.9461820 | 0.36940511E-01 | -2.2439388 | 0.27441040E-01 |
55 | 2 | 39.814917 | 0.13293308 | 14.874721 | -0.32157873 |
56 | 1 | -79.735998 | 0.60618496E-01 | -28.791459 | 1.0613631 |
57 | 0 | 46.824344 | 0.12320537E-02 | 16.299787 | |
58 | 7 | -0.27749376E-12 | 0.16893975E-14 | -0.84125370E-13 | 0.18079425E-15 |
59 | 6 | 0.22886636E-07 | 0.32835403E-09 | 0.52910653E-08 | -0.10444131E-12 |
60 | 5 | -0.16025164E-03 | 0.29299438E-05 | -0.82748939E-04 | 0.52444335E-08 |
61 | 4 | 0.25649379 | 0.14793778E-02 | 0.86896489E-01 | -0.28615133E-04 |
62 | 3 | -6.5585231 | 0.47340314E-01 | -2.1290029 | 0.25545250E-01 |
63 | 2 | 38.534810 | 0.17312159 | 14.399826 | -0.30733026 |
64 | 1 | -78.753333 | 0.80044855E-01 | -28.364722 | 1.0404251 |
65 | 0 | 46.824351 | 0.16491755E-02 | 16.310723 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4003E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4386E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7537E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.7852E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1459E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1701E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.1361E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9099E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1001 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1090E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3231E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8193E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4025E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4517E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7561E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.7996E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.1484E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1812E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0725E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8337E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8295E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6288E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8510E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3853E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5465E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5614E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3494E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3603E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0998E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1039E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8425E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8791E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4109E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4404E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1149E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1365E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6036E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4634E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0308E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1279E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8540E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.8596E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8417E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8781E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4097E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4376E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1127E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1288E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8177E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2696E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3259E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9526E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6215E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8361E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7302E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7593E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3629E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3915E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3360E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3522E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.7680E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9234E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1064 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1777E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9586E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.6597E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9147E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7413E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6882E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5454E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7400E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3179E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9965E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9420E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3838E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5450E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2035E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1688E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6967E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2027E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2292E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9003E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5453E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7926E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.7675E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9228E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1064 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1771E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9580E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.6592E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9146E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7411E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6880E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5452E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7396E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3177E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9965E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9420E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3839E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5450E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2034E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1687E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6967E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2026E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2291E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9002E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5451E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7924E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34406.18416 | 34406.18416 | 2.48011 | 2.48011 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2998.06619 | 2998.06619 | 0.12715 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27461.33427 | 27461.33427 | 1.97748 | 1.97748 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 9862.95168 | 9862.95168 | 0.41584 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29138.38718 | 29138.38718 | 2.11884 | 2.11884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66300 | 1.65359E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 18597.70950 | 18597.70950 | 0.78914 | 0.78914 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9026.26794 | 9026.26794 | 0.65638 | 0.65638 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8367.49146 | 8367.49146 | 0.32775 | 0.32775 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9167.73921 | 9167.73921 | 0.66666 | 0.66666 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5456.23626 | 5456.23626 | 0.21392 | 0.21392 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11037.74188 | 11037.74188 | 0.80264 | 0.80264 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8346.10856 | 8346.10856 | 0.32689 | 0.32689 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10154.18713 | 10154.18713 | 0.73839 | 0.73839 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5445.61606 | 5445.61606 | 0.21349 | 0.21349 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7766.21345 | 7766.21345 | 0.56474 | 0.56474 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5058.65706 | 5058.65706 | 0.21513 | 0.21513 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8217.84166 | 8217.84166 | 0.59757 | 0.59757 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3360.72029 | 3360.72029 | 0.14296 | 0.14296 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9600.06216 | 9600.06216 | 0.69809 | 0.69809 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5031.38229 | 5031.38229 | 0.21396 | 0.21396 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8560.62493 | 8560.62493 | 0.62250 | 0.62250 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 32.53067 | 1.65338E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3342.87042 | 3342.87042 | 0.14220 | 0.14220 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7795.86929 | 7795.86929 | 0.56690 | 0.56690 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5933.54098 | 5933.54098 | 0.25254 | 0.25254 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8855.35546 | 8855.35546 | 0.64394 | 0.64394 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3923.20869 | 3923.20869 | 0.16701 | 0.16701 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9785.01588 | 9785.01588 | 0.71154 | 0.71154 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5901.25897 | 5901.25897 | 0.25116 | 0.25116 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9231.95564 | 9231.95564 | 0.67132 | 0.67132 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3906.52006 | 3906.52006 | 0.16630 | 0.16630 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 71882.10 | 4.47118 | 4.47118 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9476.24 | 1.13894 | 1.13894 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 65072.88 | 3.98175 | 3.98175 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9272.30 | 1.26171 | 1.26171 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 74225.77 | 4.66206 | 4.66206 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 9018.30 | 1.92721 | 1.92721 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48011 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30219 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63739 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80583 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26081E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21270.43403 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97748 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37900 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63675 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00529E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21249.02665 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11884 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35371 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63777 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94323 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07715E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26334.67692 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65638 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24070 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13456 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64188 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58286E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10937.50310 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66666 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15003 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53324E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40009 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53942E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7138.63217 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80264 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19684 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13404 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52490 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.93559E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10908.57819 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73839 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13545 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49149E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36120 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81284E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7124.27195 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56474 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27976 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13441 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74603 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36187E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7179.04747 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59757 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16738 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14200 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48555E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44635 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27626E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4770.90271 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69809 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22632 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13403 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60352 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68345E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7140.07192 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62250 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16067 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52825E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42845 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37136E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4745.40322 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56690 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27869 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13436 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74318 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36709E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8427.64087 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64394 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41421 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45287E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5573.40493 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71154 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22204 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18900 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13448 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59211 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71590E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8381.55626 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67132 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14898 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52582E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39729 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55736E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5549.58649 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.48150 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07597 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.96301 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.13894 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.47118 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.47118 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.25473 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.28559 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07584 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57118 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26171 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.98175 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.98175 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.31687 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.49145 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07662 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.98290 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.92721 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.66206 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.66206 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.41338 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.47118 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.98175 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.66206 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.47118 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.47118 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104629.73761 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72008 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.49024 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34873.09154 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72008 |
152 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 5659.35004 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.47118 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.98175 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.98175 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96412.80375 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70935 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.32712 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32134.38749 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70935 |
161 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 7499.15403 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.98175 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.66206 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.66206 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107662.06552 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72454 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55387 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35883.76644 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72454 |
170 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 6456.24784 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.66206 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 104259.54 | 355748.32 | 12.40 | 3.18 | 3.55 | 3.74 | 3.90 | 10.85 | 12.12 | 12.77 | 13.29 | 5.1671 | 4.1030 | 2.7638 | 1.1660 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 96178.62 | 328175.07 | 12.47 | 3.20 | 3.57 | 3.77 | 3.91 | 10.90 | 12.20 | 12.86 | 13.35 | 4.6015 | 3.6539 | 2.4578 | 1.0482 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 107233.73 | 365896.69 | 12.37 | 3.17 | 3.54 | 3.73 | 3.89 | 10.83 | 12.09 | 12.74 | 13.27 | 5.3877 | 4.2837 | 2.8801 | 1.2112 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.258 | 1.059 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.015 | 0.881 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.000 | 0.870 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2723244553 | 0.2639860434 | Pass | Pass | 0.2911362505 | 0.4534951693 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9786398933E-002 | 8.7662853478E-002 | Pass | Pass | 0.3389715455 | 1.2944596748 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.2059349671E-002 | 3.4543807442E-002 | Pass | Pass | 0.2203145010 | 0.3981304785 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.1564714091E-002 | 3.5340705752E-002 | Pass | Pass | 0.3661039001 | 0.6348616366 | Fail | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1542995805 | 0.2148980582 | Pass | Pass | 0.2099587358 | 0.4063499930 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1380236365 | 0.2061945035 | Pass | Pass | 0.2023451430 | 0.3997871977 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1319931538 | 0.1915973760 | Pass | Pass | 0.2024307584 | 0.3992390088 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1760210906 | 0.2349177884 | Pass | Pass | 0.2223294654 | 0.4446023636 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3408942217 | 0.5750345612 | Pass | Pass | 0.2437435927 | 0.4698084292 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1935469821 | 0.3308290549 | Pass | Pass | 0.2187918889 | 0.4327896757 | Pass | Fail |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2119773219 | 0.2110674447 | Pass | Pass | 0.2870227552 | 0.4510615304 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2426323354 | 0.2312105519 | Pass | Pass | 0.2945368317 | 0.4626249317 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4128061543 | 0.5430411014 | Pass | Pass | 0.3429237071 | 0.5371573793 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2560994482 | 0.2733538010 | Pass | Pass | 0.2916221601 | 0.4577560095 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1478663247 | 0.2003151020 | Pass | Pass | 0.2093845180 | 0.4057495404 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1916956058 | 0.2424325806 | Pass | Pass | 0.2109459697 | 0.4087145329 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3364755365 | 0.5718833314 | Pass | Pass | 0.2500972306 | 0.4785059081 | Pass | Fail |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1931939881 | 0.3011120485 | Pass | Pass | 0.2313354112 | 0.4487265541 | Pass | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3094.34 | -42.1 | 0.00 | 177.20 | 2638.77 | 5868.23 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.059 | 1.258 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.881 | 1.015 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.870 | 1.000 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 6.66 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.19 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 6.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 6.65 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.50 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.32 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.50 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 6.66 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.19 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.73 | 41.73 | 4.42 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.73 | 62.73 | 4.80 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.73 | 47.05 | 41.64 | |
Exterior Lighting Total | 5686.19 | 50.86 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104629.74 | 75341.28 | 29288.46 | 0.72 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 96412.80 | 68390.01 | 28022.79 | 0.71 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 107662.07 | 78005.53 | 29656.53 | 0.72 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 104259.5 | 3.18 | 10.85 | N/A | N/A | 12.40 | |
PACU_VAV_MID COOLING COIL | 96178.6 | 3.20 | 10.90 | N/A | N/A | 12.47 | |
PACU_VAV_TOP COOLING COIL | 107233.7 | 3.17 | 10.83 | N/A | N/A | 12.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21270.43 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21249.03 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 26334.68 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10937.50 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7138.63 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10908.58 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7124.27 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7179.05 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4770.90 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7140.07 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4745.40 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8427.64 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5573.40 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8381.56 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5549.59 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 5659.35 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 7499.15 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 6456.25 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.47 | 9787.46 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.98 | 8716.10 | 2189.01 | 1.00 | 1.15 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.66 | 10205.31 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104259.54 | 3.18 | 10.85 | 12.40 | 5.1671 | 3.55 | 12.12 | 4.1030 | 3.74 | 12.77 | 2.7638 | 3.90 | 13.29 | 1.1660 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96178.62 | 3.20 | 10.90 | 12.47 | 4.6015 | 3.57 | 12.20 | 3.6539 | 3.77 | 12.86 | 2.4578 | 3.91 | 13.35 | 1.0482 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 107233.73 | 3.17 | 10.83 | 12.37 | 5.3877 | 3.54 | 12.09 | 4.2837 | 3.73 | 12.74 | 2.8801 | 3.89 | 13.27 | 1.2112 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34406.18 | 34406.18 | 34.98 | 2.480 | 2.480 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_MID | 27461.33 | 27461.33 | 27.92 | 1.977 | 1.977 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_TOP | 29138.39 | 29138.39 | 29.63 | 2.119 | 2.119 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00891 | 33.66 | 0.01654 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9026.27 | 9026.27 | 43.53 | 0.656 | 0.656 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00890 | 33.82 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9167.74 | 9167.74 | 69.84 | 0.667 | 0.667 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00875 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11037.74 | 11037.74 | 53.24 | 0.803 | 0.803 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00882 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10154.19 | 10154.19 | 77.36 | 0.738 | 0.738 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00873 | 32.79 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7766.21 | 7766.21 | 37.46 | 0.565 | 0.565 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00890 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8217.84 | 8217.84 | 62.61 | 0.598 | 0.598 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00874 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9600.06 | 9600.06 | 46.30 | 0.698 | 0.698 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00882 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8560.62 | 8560.62 | 65.22 | 0.622 | 0.622 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00873 | 32.53 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7795.87 | 7795.87 | 37.60 | 0.567 | 0.567 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00894 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8855.36 | 8855.36 | 67.46 | 0.644 | 0.644 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00875 | 30.67 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9785.02 | 9785.02 | 47.19 | 0.712 | 0.712 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00885 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9231.96 | 9231.96 | 70.34 | 0.671 | 0.671 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00874 | 32.79 | 0.01653 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2998.07 | 2998.07 | 3.05 | 0.127 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_MID | 9862.95 | 9862.95 | 10.03 | 0.416 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_TOP | 18597.71 | 18597.71 | 18.91 | 0.789 | 0.789 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8367.49 | 8367.49 | 40.36 | 0.328 | 0.328 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00769 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5456.24 | 5456.24 | 41.57 | 0.214 | 0.214 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00770 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8346.11 | 8346.11 | 40.25 | 0.327 | 0.327 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00768 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5445.62 | 5445.62 | 41.49 | 0.213 | 0.213 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00770 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5058.66 | 5058.66 | 24.40 | 0.215 | 0.215 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3360.72 | 3360.72 | 25.60 | 0.143 | 0.143 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5031.38 | 5031.38 | 24.27 | 0.214 | 0.214 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3342.87 | 3342.87 | 25.47 | 0.142 | 0.142 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5933.54 | 5933.54 | 28.62 | 0.253 | 0.253 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3923.21 | 3923.21 | 29.89 | 0.167 | 0.167 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5901.26 | 5901.26 | 28.46 | 0.251 | 0.251 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3906.52 | 3906.52 | 29.76 | 0.166 | 0.166 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 4.60 | 0.00526 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.47 | 4.47 | 1.14 | 1.14 | 4.4712 | 1.1389 | 4.4712 | 0.2547 | 0.3000 |
PACU_VAV_MID | 3.98 | 3.98 | 1.26 | 1.26 | 3.9818 | 1.2617 | 3.9818 | 0.3169 | 0.3000 |
PACU_VAV_TOP | 4.66 | 4.66 | 1.93 | 1.93 | 4.6621 | 1.9272 | 4.6621 | 0.4134 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21270.434 | 21270.434 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21270.43 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00799968 | 51.6724 | 2998.07 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21249.027 | 21249.027 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21249.03 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 9862.95 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 26334.677 | 26334.677 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26334.68 | 26334.68 | 0.789143 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 18597.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 10937.503 | 10937.503 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10937.50 | 10937.50 | 0.327753 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00768727 | 50.6179 | 8367.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7138.632 | 7138.632 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7138.63 | 7138.63 | 0.213916 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00769809 | 50.6890 | 5456.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 10908.578 | 10908.578 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 10908.58 | 10908.58 | 0.326886 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00768457 | 50.6003 | 8346.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7124.272 | 7124.272 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 7124.27 | 7124.27 | 0.213485 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 20.70 | 0.00769590 | 50.6747 | 5445.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7179.047 | 7179.047 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7179.05 | 7179.05 | 0.215127 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782417 | 50.5542 | 5058.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4770.903 | 4770.903 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4770.90 | 4770.90 | 0.142965 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782855 | 50.5822 | 3360.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7140.072 | 7140.072 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7140.07 | 7140.07 | 0.213959 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782275 | 50.5452 | 5031.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4745.403 | 4745.403 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4745.40 | 4745.40 | 0.142200 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782715 | 50.5733 | 3342.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8427.641 | 8427.641 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8427.64 | 8427.64 | 0.252542 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00780600 | 50.4387 | 5933.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5573.405 | 5573.405 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5573.40 | 5573.40 | 0.167012 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00781116 | 50.4717 | 3923.21 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8381.556 | 8381.556 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8381.56 | 8381.56 | 0.251161 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00780430 | 50.4278 | 5901.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5549.586 | 5549.586 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5549.59 | 5549.59 | 0.166299 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00780986 | 50.4634 | 3906.52 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 104629.738 | 75341.279 | 4.471180 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 106714.04 | 79373.08 | 4.471180 | 26.12 | 18.75 | 0.01050416 | 11.02 | 11.02 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 21.3836 | 24.00 | 0.00885993 | 47.6307 | 61386.04 | 0.00 | 107887.30 | 76582.80 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 5659.350 | 5659.350 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5659.35 | 5659.35 | 1.341354 | 9.31 | 7.89 | 0.00603224 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 71.2787 | 21.00 | 0.00792986 | 51.2275 | 14035.54 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 96412.804 | 68390.010 | 3.981753 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 99074.08 | 71703.64 | 3.981753 | 26.37 | 19.02 | 0.01075811 | 11.02 | 11.02 | 0.00850000 | 33.82 | 0.01653623 | 25.11 | 24.0120 | 24.00 | 0.00892368 | 47.9689 | 54562.51 | 0.00 | 99414.54 | 69547.65 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 7499.154 | 7499.154 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7499.15 | 7499.15 | 1.194526 | 7.61 | 6.73 | 0.00574221 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 80.0401 | 19.60 | 0.00755352 | 53.2408 | 17679.87 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 107662.066 | 78005.531 | 4.662064 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 109741.00 | 82062.36 | 4.662064 | 25.98 | 18.65 | 0.01044414 | 11.02 | 11.02 | 0.00850000 | 33.66 | 0.01653594 | 25.07 | 20.5081 | 24.00 | 0.00887044 | 47.6867 | 64044.66 | 0.00 | 111014.04 | 79268.76 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 6456.248 | 6456.248 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6456.25 | 6456.25 | 1.398619 | 8.98 | 7.72 | 0.00601748 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 68.3603 | 19.60 | 0.00763824 | 53.8276 | 25304.85 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21270.434 | 21270.434 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21270.43 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21270.43 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.83 | 0.00799968 | 21.00 | 0.00799968 | 51.6724 | 2998.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21249.027 | 21249.027 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21249.03 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21249.03 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.85 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 9862.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 26334.677 | 26334.677 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26334.68 | 26334.68 | 1.0000 | 0.94947106 | 0.789143 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26334.68 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 18597.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10937.503 | 10937.503 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10937.50 | 10937.50 | 1.0000 | 0.39434099 | 0.327753 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10937.50 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00768727 | 20.70 | 0.00768727 | 50.6179 | 8367.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7138.632 | 7138.632 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7138.63 | 7138.63 | 1.0000 | 0.25737641 | 0.213916 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7138.63 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00769809 | 20.70 | 0.00769809 | 50.6890 | 5456.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10908.578 | 10908.578 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 10908.58 | 10908.58 | 1.0000 | 0.39329813 | 0.326886 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10908.58 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00768457 | 20.70 | 0.00768457 | 50.6003 | 8346.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7124.272 | 7124.272 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 7124.27 | 7124.27 | 1.0000 | 0.25685867 | 0.213485 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7124.27 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 19.48 | 0.00769590 | 20.70 | 0.00769590 | 50.6747 | 5445.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7179.047 | 7179.047 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7179.05 | 7179.05 | 1.0000 | 0.25883355 | 0.215127 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7179.05 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782417 | 21.00 | 0.00782417 | 50.5542 | 5058.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4770.903 | 4770.903 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4770.90 | 4770.90 | 1.0000 | 0.17201024 | 0.142965 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4770.90 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782855 | 21.00 | 0.00782855 | 50.5822 | 3360.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7140.072 | 7140.072 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7140.07 | 7140.07 | 1.0000 | 0.25742832 | 0.213959 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7140.07 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782275 | 21.00 | 0.00782275 | 50.5452 | 5031.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4745.403 | 4745.403 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4745.40 | 4745.40 | 1.0000 | 0.17109088 | 0.142200 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4745.40 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00782715 | 21.00 | 0.00782715 | 50.5733 | 3342.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8427.641 | 8427.641 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8427.64 | 8427.64 | 1.0000 | 0.30385036 | 0.252542 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8427.64 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00780600 | 21.00 | 0.00780600 | 50.4387 | 5933.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5573.405 | 5573.405 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5573.40 | 5573.40 | 1.0000 | 0.20094367 | 0.167012 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5573.40 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00781116 | 21.00 | 0.00781116 | 50.4717 | 3923.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8381.556 | 8381.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8381.56 | 8381.56 | 1.0000 | 0.30218883 | 0.251161 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8381.56 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00780430 | 21.00 | 0.00780430 | 50.4278 | 5901.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5549.586 | 5549.586 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5549.59 | 5549.59 | 1.0000 | 0.20008492 | 0.166299 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5549.59 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00780986 | 21.00 | 0.00780986 | 50.4634 | 3906.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104629.738 | 75341.279 | 4.471180 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3667 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.471180 | 5.37957542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 106714.04 | 79373.08 | 1.0199 | 5.37957542 | 4.471180 | 26.12 | 18.75 | 0.01050416 | 53026.2 | 11.02 | 11.02 | 0.00850000 | 32509.4 | -999.0 | -999.00 | -999.00 | -999.00 | 9787.462 | 96926.58 | 33.90 | 0.01653638 | 25.13 | 0.95610000 | 21.3836 | 24.00 | 0.00885993 | 24.00 | 0.00885993 | 47.6307 | 61386.04 | 0.00 | 107887.30 | 76582.80 | 5.16712285 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.15 | 12.14 | 0.00880930 | 34442.8 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5659.350 | 5659.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.471180 | 5.37957542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5659.35 | 5659.35 | 1.0000 | 1.61387263 | 1.341354 | 9.31 | 7.89 | 0.00603224 | 24546.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5659.35 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 71.2787 | 21.00 | 0.00795581 | 21.00 | 0.00792986 | 51.2275 | 14035.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96412.804 | 68390.010 | 3.981753 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8388 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.981753 | 4.79071288 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 99074.08 | 71703.64 | 1.0276 | 4.79071288 | 3.981753 | 26.37 | 19.02 | 0.01075811 | 53925.8 | 11.02 | 11.02 | 0.00850000 | 32510.3 | -999.0 | -999.00 | -999.00 | -999.00 | 8716.100 | 90357.98 | 33.82 | 0.01653623 | 25.11 | 0.95610000 | 24.0120 | 24.00 | 0.00892368 | 24.00 | 0.00892368 | 47.9689 | 54562.51 | 0.00 | 99414.54 | 69547.65 | 4.60151594 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.86 | 11.85 | 0.00863982 | 33717.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7499.154 | 7499.154 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.981753 | 4.79071288 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7499.15 | 7499.15 | 1.0000 | 1.43721386 | 1.194526 | 7.61 | 6.73 | 0.00574221 | 22086.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7499.15 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 80.0401 | 19.67 | 0.00768736 | 19.60 | 0.00755352 | 53.2408 | 17679.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107662.066 | 78005.531 | 4.662064 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2551 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.662064 | 5.60924054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 109741.00 | 82062.36 | 1.0193 | 5.60924054 | 4.662064 | 25.98 | 18.65 | 0.01044414 | 52733.0 | 11.02 | 11.02 | 0.00850000 | 32509.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10205.308 | 99535.69 | 33.66 | 0.01653594 | 25.07 | 0.95610000 | 20.5081 | 24.00 | 0.00887044 | 24.00 | 0.00887044 | 47.6867 | 64044.66 | 0.00 | 111014.04 | 79268.76 | 5.38771794 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.26 | 12.25 | 0.00887448 | 34717.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6456.248 | 6456.248 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.662064 | 5.60924054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6456.25 | 6456.25 | 1.0000 | 1.68277216 | 1.398619 | 8.98 | 7.72 | 0.00601748 | 24175.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6456.25 | 4.60 | 0.00525715 | 4.60 | 0.95610000 | 68.3603 | 18.45 | 0.00766026 | 19.60 | 0.00763824 | 53.8276 | 25304.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.47 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 3.98 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.66 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 4545.00 | 323.17 | 0.00 |
CORE_MID | 3527.67 | 1389.50 | 0.00 |
CORE_TOP | 3355.50 | 1804.00 | 35.83 |
PERIMETER_TOP_ZN_3 | 3669.67 | 2179.00 | 378.17 |
PERIMETER_TOP_ZN_2 | 3943.33 | 1943.00 | 472.00 |
PERIMETER_TOP_ZN_1 | 4133.33 | 1544.33 | 388.67 |
PERIMETER_TOP_ZN_4 | 3940.17 | 1913.17 | 445.00 |
PERIMETER_BOT_ZN_3 | 3535.67 | 1949.33 | 69.00 |
PERIMETER_BOT_ZN_2 | 4042.67 | 1424.17 | 186.50 |
PERIMETER_BOT_ZN_1 | 4388.00 | 1962.00 | 929.00 |
PERIMETER_BOT_ZN_4 | 4034.83 | 1422.17 | 143.83 |
PERIMETER_MID_ZN_3 | 3660.83 | 1894.33 | 154.83 |
PERIMETER_MID_ZN_2 | 3333.00 | 1486.33 | 306.00 |
PERIMETER_MID_ZN_1 | 4267.00 | 1227.67 | 239.67 |
PERIMETER_MID_ZN_4 | 4003.00 | 1621.33 | 271.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5130.67 | 3263.17 | 1436.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.17 | 18.50 | 0.17 | 14.67 |
PERIMETER_TOP_ZN_2 | 0.17 | 65.17 | 0.17 | 59.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 60.50 | 0.00 | 56.17 |
PERIMETER_TOP_ZN_4 | 0.17 | 57.83 | 0.17 | 39.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 41.50 | 0.00 | 40.83 |
PERIMETER_BOT_ZN_1 | 65.17 | 229.50 | 65.17 | 227.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 37.00 | 0.00 | 25.50 |
PERIMETER_MID_ZN_3 | 0.00 | 1.67 | 0.00 | 1.67 |
PERIMETER_MID_ZN_2 | 0.00 | 53.17 | 0.00 | 52.33 |
PERIMETER_MID_ZN_1 | 0.00 | 47.00 | 0.00 | 46.17 |
PERIMETER_MID_ZN_4 | 0.00 | 45.00 | 0.00 | 32.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 65.33 | 387.00 | 65.33 | 357.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.612 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.474 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.464 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.561 | 0.029 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.714 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.780 | 0.029 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.714 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.484 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.632 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.705 | 1.255 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.622 | 0.016 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.565 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.665 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.799 | 0.025 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.727 | 0.026 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 9630958.19 | 0.00 | 9630958.19 | 0.00 | 9630958.19 | 13393058.27 | 5927.57 | 126.69 | 2705.74 | 2.33 |
CORE_MID | 7457544.39 | 0.00 | 7457544.39 | 0.00 | 7457544.39 | 13393058.27 | 6923.75 | 244.05 | 1592.20 | 2.83 |
CORE_TOP | 7316801.28 | 0.00 | 7316801.28 | 0.00 | 7316801.28 | 13393058.27 | 6904.87 | 230.15 | 1624.98 | 3.33 |
PERIMETER_TOP_ZN_3 | 1863670.50 | 0.00 | 1863670.50 | 189985.33 | 2053655.83 | 2823374.22 | 4670.93 | 195.77 | 3893.30 | 3.33 |
PERIMETER_TOP_ZN_2 | 1499710.34 | 0.00 | 1499710.34 | 126656.12 | 1626366.47 | 1787429.43 | 4365.79 | 86.14 | 4308.07 | 3.33 |
PERIMETER_TOP_ZN_1 | 2588357.75 | 0.00 | 2588357.75 | 189985.33 | 2778343.08 | 2823374.22 | 4378.64 | 253.12 | 4128.24 | 3.33 |
PERIMETER_TOP_ZN_4 | 1499852.40 | 0.00 | 1499852.40 | 126656.12 | 1626508.53 | 1787312.18 | 4487.16 | 197.65 | 4075.19 | 3.33 |
PERIMETER_BOT_ZN_3 | 1608378.74 | 0.00 | 1608378.74 | 101014.83 | 1709393.58 | 2823374.22 | 6337.32 | 214.04 | 2208.64 | 2.33 |
PERIMETER_BOT_ZN_2 | 1326827.87 | 0.00 | 1326827.87 | 67342.82 | 1394170.69 | 1787429.43 | 4748.56 | 111.09 | 3900.34 | 2.33 |
PERIMETER_BOT_ZN_1 | 2336723.87 | 0.00 | 2336723.87 | 4199580.43 | 6536304.31 | 2823374.22 | 4924.25 | 109.61 | 3726.14 | 2.33 |
PERIMETER_BOT_ZN_4 | 1306685.53 | 0.00 | 1306685.53 | 67342.82 | 1374028.35 | 1787312.18 | 5053.60 | 149.32 | 3557.07 | 2.33 |
PERIMETER_MID_ZN_3 | 1876269.08 | 0.00 | 1876269.08 | 158148.70 | 2034417.77 | 2823374.22 | 4714.03 | 219.17 | 3826.81 | 2.83 |
PERIMETER_MID_ZN_2 | 1424454.71 | 0.00 | 1424454.71 | 105431.83 | 1529886.54 | 1601953.02 | 4356.41 | 140.39 | 4263.20 | 911.83 |
PERIMETER_MID_ZN_1 | 2650179.06 | 0.00 | 2650179.06 | 158148.70 | 2808327.76 | 2823374.22 | 4360.82 | 121.76 | 4277.42 | 2.83 |
PERIMETER_MID_ZN_4 | 1525606.26 | 0.00 | 1525606.26 | 105431.83 | 1631038.09 | 1787312.18 | 4483.81 | 97.99 | 4178.20 | 2.83 |
Total Facility | 45912019.97 | 0.00 | 45912019.97 | 5595724.86 | 51507744.83 | 67658168.57 | 7477.34 | 984.02 | 4490.73 | 913.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.4499 | 0.0000 | 0.4499 | 0.0000 | 0.4499 | 0.4247 | 3112.90 | 126.69 | 2703.41 |
CORE_MID | 0.3483 | 0.0000 | 0.3483 | 0.0000 | 0.3483 | 0.4247 | 4109.58 | 244.05 | 1589.37 |
CORE_TOP | 0.3416 | 0.0000 | 0.3416 | 0.0000 | 0.3416 | 0.4247 | 4091.20 | 230.15 | 1621.64 |
PERIMETER_TOP_ZN_3 | 0.0870 | 0.0000 | 0.0870 | 0.0046 | 0.0916 | 0.0895 | 1857.27 | 195.77 | 3889.97 |
PERIMETER_TOP_ZN_2 | 0.0700 | 0.0000 | 0.0700 | 0.0030 | 0.0731 | 0.0567 | 1552.12 | 86.14 | 4304.74 |
PERIMETER_TOP_ZN_1 | 0.1209 | 0.0000 | 0.1209 | 0.0046 | 0.1255 | 0.0895 | 1564.97 | 253.12 | 4124.91 |
PERIMETER_TOP_ZN_4 | 0.0700 | 0.0000 | 0.0700 | 0.0030 | 0.0731 | 0.0567 | 1673.49 | 197.65 | 4071.86 |
PERIMETER_BOT_ZN_3 | 0.0751 | 0.0000 | 0.0751 | 0.0024 | 0.0775 | 0.0895 | 3522.65 | 214.04 | 2206.31 |
PERIMETER_BOT_ZN_2 | 0.0620 | 0.0000 | 0.0620 | 0.0016 | 0.0636 | 0.0567 | 1933.90 | 111.09 | 3898.01 |
PERIMETER_BOT_ZN_1 | 0.1092 | 0.0000 | 0.1092 | 0.1940 | 0.3032 | 0.0895 | 2109.58 | 109.61 | 3723.81 |
PERIMETER_BOT_ZN_4 | 0.0610 | 0.0000 | 0.0610 | 0.0016 | 0.0626 | 0.0567 | 2238.94 | 149.32 | 3554.74 |
PERIMETER_MID_ZN_3 | 0.0876 | 0.0000 | 0.0876 | 0.0038 | 0.0914 | 0.0895 | 1899.86 | 219.17 | 3823.97 |
PERIMETER_MID_ZN_2 | 0.0652 | 0.0000 | 0.0652 | 0.0027 | 0.0679 | 0.0567 | 1542.24 | 140.39 | 3351.37 |
PERIMETER_MID_ZN_1 | 0.1238 | 0.0000 | 0.1238 | 0.0038 | 0.1276 | 0.0895 | 1546.65 | 121.76 | 4274.59 |
PERIMETER_MID_ZN_4 | 0.0712 | 0.0000 | 0.0712 | 0.0025 | 0.0738 | 0.0567 | 1669.65 | 97.99 | 4175.37 |
Total Facility | 2.1430 | 0.0000 | 2.1430 | 0.2276 | 2.3706 | 2.1513 | 4661.51 | 984.02 | 4486.56 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23465156.71 | 0.00 | 23465156.71 | 22614548.33 | 4269.86 | 0.47 | 4489.67 | 2.33 |
PACU_VAV_MID | 21618704.47 | 0.00 | 21618704.47 | 22429071.92 | 4268.06 | 0.45 | 4491.49 | 2.83 |
PACU_VAV_TOP | 21378851.88 | 0.00 | 21378851.88 | 22614548.33 | 4284.60 | 1.26 | 4474.14 | 3.33 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0961 | 0.0000 | 1.0961 | 0.7171 | 1455.19 | 0.47 | 4487.33 |
PACU_VAV_MID | 1.0097 | 0.0000 | 1.0097 | 0.7084 | 1453.90 | 0.45 | 4488.66 |
PACU_VAV_TOP | 0.9983 | 0.0000 | 0.9983 | 0.7171 | 1470.93 | 1.26 | 4470.81 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 266.70 | 1336.09 | 0.00 | 0.00 | 0.00 | 2897.62 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 133.09 | 1296.72 | 0.00 | 0.00 | 0.00 | 3068.73 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 108.74 | 1232.24 | 0.00 | 0.00 | 0.00 | 3148.12 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3151 | 2.1474 | 0.0000 | 0.0000 | 0.0000 | 1.1398 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2659 | 1.7937 | 0.0000 | 0.0000 | 0.0000 | 1.1450 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2887 | 1.7739 | 0.0000 | 0.0000 | 0.0000 | 1.1486 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2220 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1661.57 | 13751.66 | 11-JUN-17:30 | 152167.90 | 30-AUG-16:00 |
Electricity:Building | 951.32 | 13383.13 | 23-APR-17:20 | 65552.31 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 951.32 | 13383.13 | 23-APR-17:20 | 65552.31 | 25-OCT-07:10 |
InteriorLights:Electricity | 231.64 | 905.38 | 23-APR-17:20 | 23853.05 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.64 | 905.38 | 23-APR-17:20 | 23853.05 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 231.64 | 905.38 | 23-APR-17:20 | 23853.05 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.64 | 905.38 | 23-APR-17:20 | 23853.05 | 25-OCT-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.99 | 413.68 | 26-MAR-17:10 | 2364.90 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.66 | 27.57 | 01-JAN-09:00 | 929.66 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.66 | 27.57 | 01-JAN-09:00 | 929.66 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.60 | 261.88 | 23-APR-17:10 | 1483.02 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 574.45 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 574.45 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2357.92 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 922.68 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 922.68 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.60 | 261.87 | 26-FEB-18:10 | 1502.06 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.19 | 17.46 | 01-JAN-09:10 | 593.49 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.19 | 17.46 | 01-JAN-09:10 | 593.49 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.98 | 413.68 | 26-MAR-17:10 | 2360.62 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.65 | 27.57 | 01-JAN-09:00 | 925.37 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.65 | 27.57 | 01-JAN-09:00 | 925.37 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.59 | 261.88 | 26-MAR-17:10 | 1480.30 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 571.73 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 571.73 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.90 | 413.67 | 12-MAR-17:10 | 2353.29 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:50 | 918.06 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:50 | 918.06 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.59 | 261.87 | 26-FEB-18:10 | 1500.05 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 591.49 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:00 | 591.49 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.99 | 413.68 | 26-MAR-17:10 | 2364.89 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.66 | 27.57 | 01-JAN-09:00 | 929.65 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.66 | 27.57 | 01-JAN-09:00 | 929.65 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.60 | 261.88 | 23-APR-17:10 | 1483.01 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 574.44 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-07:50 | 574.44 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2357.91 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 922.67 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:50 | 922.67 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.60 | 261.87 | 26-FEB-18:10 | 1502.05 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.19 | 17.46 | 01-JAN-09:10 | 593.48 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.19 | 17.46 | 01-JAN-09:10 | 593.48 | 25-OCT-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 617.08 | 367.92 | 01-JAN-00:10 | 87620.70 | 30-AUG-16:00 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
ElectricityPurchased:Plant | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
ElectricityNet:Plant | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
Cogeneration:ElectricityNet | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1661.57 | 13751.66 | 28-MAY-17:30 | 152167.90 | 30-AUG-16:00 |
Heating:Electricity | 10.92 | 0.00 | 01-JAN-00:10 | 81172.69 | 06-FEB-07:10 |
General:Heating:Electricity | 10.92 | 0.00 | 01-JAN-00:10 | 81172.69 | 06-FEB-07:10 |
Fans:Electricity | 83.43 | 0.00 | 01-JAN-00:10 | 15400.01 | 10-OCT-14:10 |
General:Fans:Electricity | 83.43 | 0.00 | 01-JAN-00:10 | 15400.01 | 10-OCT-14:10 |
ExteriorLights:Electricity | 50.86 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.86 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 495.84 | 0.00 | 01-JAN-00:10 | 73126.79 | 21-JUL-16:00 |
General:Cooling:Electricity | 495.84 | 0.00 | 01-JAN-00:10 | 73126.79 | 21-JUL-16:00 |
Electricity:Plant | 42.31 | 0.00 | 01-JAN-00:10 | 5362.34 | 23-JAN-12:40 |
WaterSystems:Electricity | 42.16 | 0.00 | 01-JAN-00:10 | 5355.49 | 23-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 42.16 | 0.00 | 01-JAN-00:10 | 5355.49 | 23-JAN-12:40 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 03-JAN-12:10 |
WIRED_LTG_ELECTRICITY | 6.51 | 0.00 | 01-JAN-00:10 | 670.27 | 25-OCT-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3661.46 | 0.00 | 01-JAN-00:10 | 440539.53 | 06-OCT-14:10 |
EnergyTransfer:Building | 1468.18 | 0.00 | 01-JAN-00:10 | 163010.74 | 10-OCT-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 289.16 | 0.00 | 01-JAN-00:10 | 25439.16 | 10-OCT-08:00 |
Heating:EnergyTransfer | 7.79 | 0.00 | 01-JAN-00:10 | 51517.55 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 7.79 | 0.00 | 01-JAN-00:10 | 51517.55 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1460.39 | 0.00 | 01-JAN-00:10 | 163010.74 | 10-OCT-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 289.16 | 0.00 | 01-JAN-00:10 | 25439.16 | 10-OCT-08:00 |
General:Cooling:EnergyTransfer | 1460.39 | 0.00 | 01-JAN-00:10 | 163010.74 | 10-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 289.16 | 0.00 | 01-JAN-00:10 | 25439.16 | 10-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.11 | 0.00 | 01-JAN-00:10 | 10054.03 | 18-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.86 | 0.00 | 01-JAN-00:10 | 6263.84 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.86 | 0.00 | 01-JAN-00:10 | 6263.84 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.26 | 0.00 | 01-JAN-00:10 | 10054.03 | 18-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.26 | 0.00 | 01-JAN-00:10 | 10054.03 | 18-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.70 | 0.00 | 01-JAN-00:10 | 5020.37 | 10-OCT-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.89 | 0.00 | 01-JAN-00:10 | 1953.81 | 31-DEC-11:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.89 | 0.00 | 01-JAN-00:10 | 1953.81 | 31-DEC-11:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.82 | 0.00 | 01-JAN-00:10 | 5020.37 | 10-OCT-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.82 | 0.00 | 01-JAN-00:10 | 5020.37 | 10-OCT-14:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 35.87 | 0.00 | 01-JAN-00:10 | 5299.54 | 10-OCT-14:50 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.44 | 0.00 | 01-JAN-00:10 | 1877.43 | 31-DEC-11:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.44 | 0.00 | 01-JAN-00:10 | 1877.43 | 31-DEC-11:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 35.44 | 0.00 | 01-JAN-00:10 | 5299.54 | 10-OCT-14:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 35.44 | 0.00 | 01-JAN-00:10 | 5299.54 | 10-OCT-14:50 |
EnergyTransfer:Zone:CORE_MID | 203.77 | 0.00 | 01-JAN-00:10 | 20014.47 | 10-OCT-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 203.77 | 0.00 | 01-JAN-00:10 | 20014.47 | 10-OCT-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 203.77 | 0.00 | 01-JAN-00:10 | 20014.47 | 10-OCT-07:40 |
EnergyTransfer:Zone:CORE_TOP | 205.16 | 0.00 | 01-JAN-00:10 | 20700.12 | 10-OCT-13:50 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.09 | 0.00 | 01-JAN-00:10 | 8762.99 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.09 | 0.00 | 01-JAN-00:10 | 8762.99 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 205.07 | 0.00 | 01-JAN-00:10 | 20700.12 | 10-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 205.07 | 0.00 | 01-JAN-00:10 | 20700.12 | 10-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.09 | 0.00 | 01-JAN-00:10 | 7510.52 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.61 | 0.00 | 01-JAN-00:10 | 6324.72 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.61 | 0.00 | 01-JAN-00:10 | 6324.72 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.48 | 0.00 | 01-JAN-00:10 | 7510.52 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.48 | 0.00 | 01-JAN-00:10 | 7510.52 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.10 | 0.00 | 01-JAN-00:10 | 7687.59 | 12-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 3846.69 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.27 | 0.00 | 01-JAN-00:10 | 3846.69 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.83 | 0.00 | 01-JAN-00:10 | 7687.59 | 12-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.83 | 0.00 | 01-JAN-00:10 | 7687.59 | 12-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 73.49 | 0.00 | 01-JAN-00:10 | 11570.03 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 5054.27 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.33 | 0.00 | 01-JAN-00:10 | 5054.27 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 73.16 | 0.00 | 01-JAN-00:10 | 11570.03 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 73.16 | 0.00 | 01-JAN-00:10 | 11570.03 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.06 | 0.00 | 01-JAN-00:10 | 8651.63 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.33 | 0.00 | 01-JAN-00:10 | 3578.02 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.33 | 0.00 | 01-JAN-00:10 | 3578.02 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 0.00 | 01-JAN-00:10 | 8651.63 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.72 | 0.00 | 01-JAN-00:10 | 8651.63 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.56 | 0.00 | 01-JAN-00:10 | 7054.64 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2051.72 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.03 | 0.00 | 01-JAN-00:10 | 2051.72 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.54 | 0.00 | 01-JAN-00:10 | 7054.64 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 52.54 | 0.00 | 01-JAN-00:10 | 7054.64 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.97 | 0.00 | 01-JAN-00:10 | 6903.23 | 11-SEP-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1108.59 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1108.59 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.96 | 0.00 | 01-JAN-00:10 | 6903.23 | 11-SEP-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.96 | 0.00 | 01-JAN-00:10 | 6903.23 | 11-SEP-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 78.09 | 0.00 | 01-JAN-00:10 | 12098.59 | 30-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.75 | 0.00 | 01-JAN-00:10 | 6217.88 | 20-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.75 | 0.00 | 01-JAN-00:10 | 6217.88 | 20-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 76.34 | 0.00 | 01-JAN-00:10 | 12098.59 | 30-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 76.34 | 0.00 | 01-JAN-00:10 | 12098.59 | 30-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.43 | 0.00 | 01-JAN-00:10 | 7317.44 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 971.28 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 971.28 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.43 | 0.00 | 01-JAN-00:10 | 7317.44 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 43.43 | 0.00 | 01-JAN-00:10 | 7317.44 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.65 | 0.00 | 01-JAN-00:10 | 6932.38 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 2902.39 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 2902.39 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.57 | 0.00 | 01-JAN-00:10 | 6932.38 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 53.57 | 0.00 | 01-JAN-00:10 | 6932.38 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 42.87 | 0.00 | 01-JAN-00:10 | 7509.00 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 1734.62 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.04 | 0.00 | 01-JAN-00:10 | 1734.62 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 42.83 | 0.00 | 01-JAN-00:10 | 7509.00 | 12-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 42.83 | 0.00 | 01-JAN-00:10 | 7509.00 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.32 | 0.00 | 01-JAN-00:10 | 10555.04 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2216.71 | 21-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2216.71 | 21-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.28 | 0.00 | 01-JAN-00:10 | 10555.04 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.28 | 0.00 | 01-JAN-00:10 | 10555.04 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.78 | 0.00 | 01-JAN-00:10 | 8071.43 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1536.72 | 21-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.04 | 0.00 | 01-JAN-00:10 | 1536.72 | 21-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.74 | 0.00 | 01-JAN-00:10 | 8071.43 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.74 | 0.00 | 01-JAN-00:10 | 8071.43 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
PlantLoopHeatingDemand:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
EnergyTransfer:HVAC | 2153.85 | 0.00 | 01-JAN-00:10 | 287841.62 | 06-OCT-14:10 |
HeatingCoils:EnergyTransfer | 10.92 | 0.00 | 01-JAN-00:10 | 81172.69 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2142.93 | 0.00 | 01-JAN-00:10 | 287841.62 | 06-OCT-14:10 |
EnergyTransfer:Plant | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 39.42 | 0.00 | 01-JAN-00:10 | 5063.65 | 23-JAN-12:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -289.158 | 0.000 | 0.000 | 32.666 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -49.530 |
CORE_MID | 0.000 | 0.000 | 0.000 | -203.767 | 0.000 | 0.000 | 33.014 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -0.271 |
CORE_TOP | 0.000 | 0.000 | 0.087 | -205.076 | 0.000 | 0.000 | 33.388 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.577 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.609 | -54.483 | 0.000 | 0.000 | 7.129 | 6.661 | 24.333 | 23.803 | 0.000 | 0.208 | 7.469 | 0.000 | -14.831 | 0.000 | -0.898 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.274 | -45.826 | 0.000 | 0.000 | 4.439 | 4.195 | 15.404 | 34.005 | 0.000 | 0.129 | 0.000 | 0.000 | -9.504 | 0.000 | -0.634 | -2.481 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.331 | -73.157 | 0.000 | 0.000 | 6.996 | 6.575 | 24.332 | 58.807 | 0.000 | 0.197 | 0.000 | 0.000 | -14.602 | 0.000 | -1.005 | -8.475 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.335 | -44.720 | 0.000 | 0.000 | 4.482 | 4.195 | 15.403 | 33.440 | 0.000 | 0.131 | 0.000 | 0.000 | -10.045 | 0.000 | -0.640 | -2.580 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.027 | -52.536 | 0.000 | 0.000 | 7.065 | 6.646 | 24.333 | 24.000 | 0.000 | 0.119 | 6.670 | 0.000 | -15.804 | 0.000 | -0.519 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.006 | -44.963 | 0.000 | 0.000 | 4.400 | 4.188 | 15.404 | 34.129 | 0.000 | 0.071 | 0.001 | 0.000 | -10.398 | 0.000 | -0.374 | -2.462 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.749 | -76.335 | 0.000 | 0.000 | 7.005 | 6.567 | 24.332 | 59.169 | 0.000 | 10.674 | 0.002 | 0.000 | -15.891 | 0.000 | -13.067 | -4.203 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.005 | -43.425 | 0.000 | 0.000 | 4.426 | 4.186 | 15.403 | 33.599 | 0.000 | 0.071 | 0.000 | 0.000 | -10.999 | 0.000 | -0.378 | -2.889 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.076 | -53.572 | 0.000 | 0.000 | 7.063 | 6.661 | 24.333 | 23.797 | 0.000 | 0.178 | 8.099 | 0.000 | -15.828 | 0.000 | -0.808 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.037 | -42.829 | 0.000 | 0.000 | 3.249 | 4.195 | 15.404 | 33.870 | 0.000 | 0.107 | 0.001 | 0.000 | -10.106 | 0.000 | -0.569 | -3.357 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.035 | -72.282 | 0.000 | 0.000 | 6.950 | 6.575 | 24.332 | 58.828 | 0.000 | 0.168 | 0.000 | 0.000 | -15.450 | 0.000 | -0.892 | -8.265 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.040 | -43.744 | 0.000 | 0.000 | 4.444 | 4.195 | 15.403 | 33.466 | 0.000 | 0.110 | 0.000 | 0.000 | -10.678 | 0.000 | -0.572 | -2.664 |
TOPFLOOR_PLENUM | 2.858 | -50.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.216 | 48.579 | 0.000 | 0.000 | 0.000 | -1.398 | 0.000 |
MIDFLOOR_PLENUM | 0.886 | -28.818 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.252 | 29.110 | 0.000 | 0.000 | 0.000 | -1.431 | 0.000 |
FIRSTFLOOR_PLENUM | 0.439 | -35.436 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.192 | 35.988 | 0.000 | 0.000 | 0.000 | -1.183 | 0.000 |
Total Facility | 4.183 | -114.508 | 3.612 | -1345.874 | 0.000 | 0.000 | 166.715 | 231.635 | 719.689 | 450.914 | 0.000 | 12.822 | 136.500 | 0.000 | -154.135 | 0.000 | -24.369 | -87.178 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | -41321.10 | 0.00 | 0.00 | 289.94 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 33409.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | -32465.89 | 0.00 | 0.00 | 306.80 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 28921.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-JUL-04:02 | 0.00 | 0.00 | 0.00 | -32263.69 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 29609.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-13:53 | 0.00 | 0.00 | 0.00 | -11104.25 | 0.00 | 0.00 | 26.98 | 27.57 | 478.42 | 3755.08 | 0.00 | 76.33 | 6739.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-08:32 | 0.00 | 0.00 | 0.00 | -12247.31 | 0.00 | 0.00 | 14.93 | 17.46 | 302.86 | 7541.35 | 0.00 | 2.16 | 4368.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-13:41 | 0.00 | 0.00 | 0.00 | -16068.25 | 0.00 | 0.00 | 20.97 | 27.57 | 478.41 | 12179.32 | 0.00 | 0.00 | 3385.63 | 0.00 | -0.00 | 0.00 | -23.66 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:52 | 0.00 | 0.00 | 0.00 | -13070.97 | 0.00 | 0.00 | 12.50 | 17.46 | 302.86 | 6889.47 | 0.00 | 28.05 | 5820.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-AUG-04:02 | 0.00 | 0.00 | 0.00 | -7897.98 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 2.44 | 7489.99 | 0.00 | -153.89 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:52 | 0.00 | 0.00 | 0.00 | -10843.60 | 0.00 | 0.00 | 15.99 | 17.46 | 302.86 | 6627.67 | 0.00 | 15.58 | 3864.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-11:42 | 0.00 | 0.00 | 0.00 | -13142.63 | 0.00 | 0.00 | 23.85 | 27.57 | 478.41 | 10133.55 | 0.00 | 52.54 | 2426.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-16:52 | 0.00 | 0.00 | 0.00 | -11496.05 | 0.00 | 0.00 | 14.79 | 17.46 | 302.86 | 6780.90 | 0.00 | 17.38 | 4362.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-16:33 | 0.00 | 0.00 | 0.00 | -9364.81 | 0.00 | 0.00 | 28.48 | 27.57 | 478.42 | 2221.94 | 0.00 | 61.45 | 6546.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:41 | 0.00 | 0.00 | 0.00 | -12477.33 | 0.00 | 0.00 | 13.93 | 17.46 | 302.86 | 8188.87 | 0.00 | 0.00 | 3957.22 | 0.00 | -0.00 | 0.00 | -3.01 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-11:42 | 0.00 | 0.00 | 0.00 | -13478.57 | 0.00 | 0.00 | 23.12 | 27.57 | 478.41 | 10067.60 | 0.00 | 74.55 | 2807.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 03-SEP-16:21 | 0.00 | 0.00 | 0.00 | -12573.26 | 0.00 | 0.00 | 13.95 | 17.46 | 302.86 | 7376.54 | 0.00 | 29.48 | 4832.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 18-JUL-14:50 | 0.00 | -10053.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 10021.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-OCT-14:20 | 0.00 | -5020.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 4970.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 10-OCT-14:50 | 0.00 | -5299.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 5256.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-04:02 | 0.00 | 8381.43 | 0.00 | -196171.12 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 5.05 | 173945.67 | 0.00 | -2785.93 | 0.00 | -17.99 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-06:12 | 0.00 | 0.00 | 19037.34 | 0.00 | 0.00 | 0.00 | 474.32 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23086.02 |
PERIMETER_TOP_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 9047.74 | 0.00 | 0.00 | 0.00 | 109.23 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2076.59 | 0.00 | -24.17 | -7809.70 |
PERIMETER_TOP_ZN_2 | 06-FEB-06:11 | 0.00 | 0.00 | 5341.50 | 0.00 | 0.00 | 0.00 | 68.89 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1398.46 | 0.00 | -16.22 | -4472.72 |
PERIMETER_TOP_ZN_1 | 06-FEB-06:11 | 0.00 | 0.00 | 8430.13 | 0.00 | 0.00 | 0.00 | 106.57 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2149.01 | 0.00 | -25.42 | -7115.77 |
PERIMETER_TOP_ZN_4 | 07-FEB-06:12 | 0.00 | 0.00 | 5226.01 | 0.00 | 0.00 | 0.00 | 63.62 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1210.31 | 0.00 | -31.98 | -4524.34 |
PERIMETER_BOT_ZN_3 | 07-JAN-07:03 | 0.00 | 0.00 | 4873.13 | 0.00 | 0.00 | 0.00 | 95.27 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2467.11 | 0.00 | -19.83 | -3234.96 |
PERIMETER_BOT_ZN_2 | 07-FEB-07:02 | 0.00 | 0.00 | 3161.07 | 0.00 | 0.00 | 0.00 | 119.76 | 219.59 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1400.87 | 0.00 | -20.90 | -2482.46 |
PERIMETER_BOT_ZN_1 | 21-DEC-07:10 | 0.00 | 0.00 | 6334.46 | 0.00 | 0.00 | 0.00 | 193.30 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 14452.20 | 0.00 | -2957.17 | 0.00 | -19007.53 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JAN-07:01 | 0.00 | 0.00 | 3202.20 | 0.00 | 0.00 | 0.00 | 118.78 | 219.57 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2124.04 | 0.00 | -22.57 | -1797.75 |
PERIMETER_MID_ZN_3 | 06-FEB-06:11 | 0.00 | 0.00 | 6218.22 | 0.00 | 0.00 | 0.00 | 101.59 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2379.50 | 0.00 | -22.87 | -4670.94 |
PERIMETER_MID_ZN_2 | 21-DEC-06:01 | 0.00 | 0.00 | 3946.62 | 0.00 | 0.00 | 0.00 | 62.29 | 28.26 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1939.72 | 0.00 | -31.10 | -2470.15 |
PERIMETER_MID_ZN_1 | 27-JAN-07:01 | 0.00 | 0.00 | 5814.91 | 0.00 | 0.00 | 0.00 | 188.49 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2273.70 | 0.00 | -23.19 | -4691.26 |
PERIMETER_MID_ZN_4 | 10-JAN-06:11 | 0.00 | 0.00 | 4032.90 | 0.00 | 0.00 | 0.00 | 62.72 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1732.46 | 0.00 | -29.25 | -2810.89 |
TOPFLOOR_PLENUM | 06-FEB-07:03 | 8448.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -38.75 | -8410.01 |
MIDFLOOR_PLENUM | 31-DEC-14:23 | 4240.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -0.37 | -4239.66 |
FIRSTFLOOR_PLENUM | 05-JAN-06:02 | 5601.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -55.01 | -5546.68 |
Total Facility | 06-FEB-07:03 | -7668.63 | 14779.68 | 69385.83 | -14779.68 | 0.00 | 0.00 | 4446.92 | 8334.71 | 22496.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23747.97 | 0.00 | -19195.57 | -54052.14 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.9630 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4712 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.5712 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9818 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.9829 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6621 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4815 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2856 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0758 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4915 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4801 | 2.4801 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9775 | 1.9775 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1188 | 2.1188 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6564 | 0.6564 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6667 | 0.6667 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8026 | 0.8026 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7384 | 0.7384 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5647 | 0.5647 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5976 | 0.5976 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6981 | 0.6981 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6225 | 0.6225 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5669 | 0.5669 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6439 | 0.6439 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7115 | 0.7115 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6713 | 0.6713 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.9630 | 4.4712 | 4.9630 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.5712 | 3.9818 | 4.5712 | 1.0758 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.9829 | 4.6621 | 4.9829 | 1.0766 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2401 | 1.2401 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9887 | 0.9887 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0594 | 1.0594 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3282 | 0.3282 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3333 | 0.3333 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4013 | 0.4013 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3692 | 0.3692 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2824 | 0.2824 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2988 | 0.2988 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3490 | 0.3490 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3112 | 0.3112 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2835 | 0.2835 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3220 | 0.3220 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3558 | 0.3558 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3357 | 0.3357 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4815 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2856 | 1.0758 | 1.0758 | 1.0758 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4915 | 1.0766 | 1.0766 | 1.0766 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 65.33 |
Number of hours cooling loads not met | 357.17 |
Number of hours not met | 422.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 10.92 | 81172.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 495.84 | 73126.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.64 | 23853.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.86 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 83.43 | 15400.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 42.16 | 5355.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1661.57 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1661.57 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.49 |
Space Heating | 2.19 |
Space Cooling | 99.52 |
Fans (All) | 16.74 |
Service Water Heating | 8.46 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 333.50 |
Subtotal | 333.50 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.94 |
Space Heating | 0.66 |
Space Cooling | 29.84 |
Fans (All) | 5.02 |
Service Water Heating | 2.54 |
Receptacle Equipment | 43.31 |
Miscellaneous | 4.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1042. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8255.50 | 504.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8652.67 | 107.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8531.50 | 228.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8566.17 | 193.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8485.83 | 274.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8636.83 | 123.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8650.33 | 109.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8607.83 | 152.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8677.67 | 82.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8527.00 | 233.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8575.67 | 184.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8492.00 | 268.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8421.33 | 338.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Min | 8255.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 504.50 | 0.00 | 0.00 | 0.00 |
Average | 8603.14 | 156.86 | 0.00 | 0.00 | 0.00 |
Sum | 154856.50 | 2823.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128163.00 | 141.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24904.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 141.00 | 0.00 | 0.00 | 0.00 |
Average | 34135.25 | 8.08 | 0.00 | 0.00 | 0.00 |
Sum | 614434.50 | 145.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7838.33 | 921.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7573.67 | 1186.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7446.83 | 1313.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7506.67 | 1253.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7380.17 | 1379.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7965.00 | 795.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7699.83 | 1060.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6908.50 | 1851.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7647.17 | 1112.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7541.17 | 1218.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7369.00 | 1391.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7466.67 | 1293.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7316.83 | 1443.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7897.00 | 863.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8211.33 | 548.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8381.50 | 378.50 | 0.00 | 0.00 | 0.00 |
Min | 6908.50 | 27.83 | 0.00 | 0.00 | 0.00 |
Max | 8732.17 | 1851.50 | 0.00 | 0.00 | 0.00 |
Average | 7756.05 | 1003.95 | 0.00 | 0.00 | 0.00 |
Sum | 139608.83 | 18071.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127958.33 | 345.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.33 | 7.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24887.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24886.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24904.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20037.00 | 4872.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24892.17 | 16.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24891.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.00 | 4872.00 | 0.00 | 0.00 | 0.00 |
Average | 33848.04 | 295.30 | 0.00 | 0.00 | 0.00 |
Sum | 609264.67 | 5315.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193510E+11 | 37789.37 | 02-JAN-06:12 | 16.00 | 15.39 | 0.199062E+10 | 2606.71 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.177922E+11 | 35793.68 | 28-FEB-06:13 | 18.47 | 17.93 | 0.180675E+10 | 2606.63 | 21-FEB-10:20 | 18.47 | 17.93 |
March | 0.215574E+11 | 36243.12 | 09-MAR-06:02 | 1.10 | -2.1 | 0.215780E+10 | 2606.66 | 10-MAR-10:30 | 11.90 | 8.26 |
April | 0.222991E+11 | 36930.39 | 28-APR-05:12 | 22.90 | 21.77 | 0.192043E+10 | 2606.71 | 10-APR-13:00 | 22.90 | 21.77 |
May | 0.274070E+11 | 41325.15 | 31-MAY-05:03 | 23.80 | 21.58 | 0.207919E+10 | 2606.59 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.274474E+11 | 39381.40 | 20-JUN-04:02 | 24.50 | 23.30 | 0.207199E+10 | 2606.60 | 01-JUN-13:20 | 24.50 | 23.30 |
July | 0.274407E+11 | 40698.30 | 12-JUL-05:03 | 23.90 | 23.16 | 0.192574E+10 | 2606.60 | 03-JUL-13:20 | 23.90 | 23.16 |
August | 0.290956E+11 | 38877.96 | 01-AUG-04:03 | 23.90 | 22.80 | 0.216163E+10 | 2606.60 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.266778E+11 | 38557.10 | 14-SEP-04:03 | 24.30 | 22.41 | 0.191937E+10 | 2606.59 | 18-SEP-13:20 | 28.47 | 25.99 |
October | 0.268496E+11 | 38085.00 | 24-OCT-04:02 | 25.83 | 25.19 | 0.199676E+10 | 2606.72 | 17-OCT-13:09 | 25.83 | 25.19 |
November | 0.228763E+11 | 37037.26 | 13-NOV-06:12 | 9.60 | 8.03 | 0.197527E+10 | 2606.64 | 09-NOV-10:20 | 9.60 | 8.03 |
December | 0.203618E+11 | 36895.43 | 18-DEC-06:12 | 3.33 | 0.55 | 0.192254E+10 | 2606.70 | 08-DEC-10:00 | 3.33 | 0.55 |
Annual Sum or Average | 0.289156E+12 | 0.239281E+11 | ||||||||
Minimum of Months | 0.177922E+11 | 35793.68 | 1.10 | -2.1 | 0.180675E+10 | 2606.59 | 3.33 | 0.55 | ||
Maximum of Months | 0.290956E+11 | 41325.15 | 25.83 | 25.19 | 0.216163E+10 | 2606.72 | 28.47 | 25.99 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132517E+10 | 5768.91 | 19-JAN-15:05 | 25.00 | 21.42 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.42 |
February | 0.176062E+10 | 6643.88 | 27-FEB-15:00 | 26.10 | 20.43 | 0.00 | 0.00 | 01-FEB-00:10 | 26.10 | 20.43 |
March | 0.234679E+10 | 6509.55 | 29-MAR-14:40 | 26.47 | 21.33 | 0.00 | 0.00 | 01-MAR-00:10 | 26.47 | 21.33 |
April | 0.386909E+10 | 8970.07 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.630582E+10 | 9633.48 | 10-MAY-14:50 | 32.80 | 23.14 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.14 |
June | 0.699357E+10 | 9669.06 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.661400E+10 | 10054.03 | 18-JUL-14:50 | 35.00 | 25.65 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.65 |
August | 0.672863E+10 | 9754.39 | 03-AUG-15:20 | 35.17 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 35.17 | 24.83 |
September | 0.516621E+10 | 9096.37 | 01-SEP-14:05 | 32.20 | 23.03 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 23.03 |
October | 0.504281E+10 | 9286.80 | 05-OCT-15:00 | 34.00 | 24.05 | 0.00 | 0.00 | 01-OCT-00:10 | 34.00 | 24.05 |
November | 0.246458E+10 | 7592.12 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.36 |
December | 0.163810E+10 | 6711.83 | 15-DEC-15:05 | 28.83 | 21.51 | 0.00 | 0.00 | 01-DEC-00:10 | 28.83 | 21.51 |
Annual Sum or Average | 0.502554E+11 | 0.00 | ||||||||
Minimum of Months | 0.132517E+10 | 5768.91 | 25.00 | 20.43 | 0.00 | 0.00 | 25.00 | 20.43 | ||
Maximum of Months | 0.699357E+10 | 10054.03 | 35.17 | 26.19 | 0.00 | 0.00 | 35.17 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696004E+09 | 3267.21 | 04-JAN-07:01 | 1.17 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | -1.3 |
February | 0.863927E+09 | 2965.77 | 17-FEB-07:01 | 1.28 | -1.4 | 0.00 | 0.00 | 01-FEB-00:10 | 1.28 | -1.4 |
March | 0.118467E+10 | 3302.00 | 09-MAR-07:01 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.193988E+10 | 3424.90 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.364521E+10 | 4484.72 | 30-MAY-06:03 | 25.18 | 23.66 | 0.00 | 0.00 | 01-MAY-00:10 | 25.18 | 23.66 |
June | 0.384016E+10 | 4305.57 | 26-JUN-06:03 | 25.10 | 23.76 | 0.00 | 0.00 | 01-JUN-00:10 | 25.10 | 23.76 |
July | 0.384099E+10 | 4515.00 | 10-JUL-12:06 | 31.70 | 25.12 | 0.00 | 0.00 | 01-JUL-00:10 | 31.70 | 25.12 |
August | 0.395646E+10 | 4540.32 | 28-AUG-06:03 | 24.17 | 23.32 | 0.00 | 0.00 | 01-AUG-00:10 | 24.17 | 23.32 |
September | 0.325421E+10 | 4702.84 | 11-SEP-06:03 | 25.08 | 23.81 | 0.00 | 0.00 | 01-SEP-00:10 | 25.08 | 23.81 |
October | 0.317175E+10 | 5020.37 | 10-OCT-14:20 | 30.67 | 22.57 | 0.00 | 0.00 | 01-OCT-00:10 | 30.67 | 22.57 |
November | 0.148329E+10 | 3655.58 | 06-NOV-16:20 | 27.73 | 20.09 | 0.00 | 0.00 | 01-NOV-00:10 | 27.73 | 20.09 |
December | 0.941266E+09 | 2881.41 | 15-DEC-16:10 | 28.00 | 21.24 | 0.00 | 0.00 | 01-DEC-00:10 | 28.00 | 21.24 |
Annual Sum or Average | 0.288178E+11 | 0.00 | ||||||||
Minimum of Months | 0.696004E+09 | 2881.41 | 1.17 | -2.3 | 0.00 | 0.00 | 1.17 | -2.3 | ||
Maximum of Months | 0.395646E+10 | 5020.37 | 32.20 | 25.55 | 0.00 | 0.00 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113212E+10 | 3958.18 | 02-JAN-07:13 | 15.67 | 15.07 | 0.00 | 0.00 | 01-JAN-00:10 | 15.67 | 15.07 |
February | 0.128339E+10 | 3420.94 | 27-FEB-16:20 | 25.13 | 20.45 | 0.00 | 0.00 | 01-FEB-00:10 | 25.13 | 20.45 |
March | 0.167528E+10 | 3059.48 | 09-MAR-07:09 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.239307E+10 | 3722.98 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.404833E+10 | 4622.95 | 30-MAY-11:00 | 30.60 | 25.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.60 | 25.21 |
June | 0.424748E+10 | 4512.73 | 19-JUN-14:05 | 31.05 | 25.15 | 0.00 | 0.00 | 01-JUN-00:10 | 31.05 | 25.15 |
July | 0.428389E+10 | 4972.87 | 05-JUL-12:10 | 32.20 | 26.46 | 0.00 | 0.00 | 01-JUL-00:10 | 32.20 | 26.46 |
August | 0.465828E+10 | 4975.33 | 28-AUG-15:30 | 33.00 | 24.29 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 24.29 |
September | 0.396053E+10 | 4948.32 | 05-SEP-06:10 | 22.82 | 22.82 | 0.00 | 0.00 | 01-SEP-00:10 | 22.82 | 22.82 |
October | 0.393743E+10 | 5299.54 | 10-OCT-14:50 | 30.17 | 22.44 | 0.00 | 0.00 | 01-OCT-00:10 | 30.17 | 22.44 |
November | 0.228759E+10 | 4420.83 | 06-NOV-17:00 | 26.60 | 19.72 | 0.00 | 0.00 | 01-NOV-00:10 | 26.60 | 19.72 |
December | 0.152843E+10 | 3649.36 | 18-DEC-07:06 | 2.50 | 0.21 | 0.00 | 0.00 | 01-DEC-00:10 | 2.50 | 0.21 |
Annual Sum or Average | 0.354358E+11 | 0.00 | ||||||||
Minimum of Months | 0.113212E+10 | 3059.48 | 1.18 | -2.3 | 0.00 | 0.00 | 1.18 | -2.3 | ||
Maximum of Months | 0.465828E+10 | 5299.54 | 33.00 | 26.46 | 0.00 | 0.00 | 33.00 | 26.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128096E+11 | 29741.43 | 02-JAN-06:12 | 16.00 | 15.39 | 0.189365E+10 | 2606.64 | 30-JAN-10:20 | 22.33 | 19.83 |
February | 0.120087E+11 | 14949.51 | 27-FEB-17:00 | 24.40 | 20.28 | 0.174285E+10 | 2606.63 | 27-FEB-10:20 | 24.40 | 20.28 |
March | 0.147220E+11 | 14802.11 | 27-MAR-16:00 | 28.30 | 21.14 | 0.210209E+10 | 2606.62 | 06-MAR-10:20 | 28.30 | 21.14 |
April | 0.156012E+11 | 20017.10 | 24-APR-06:03 | 20.50 | 20.22 | 0.190605E+10 | 2606.66 | 10-APR-13:00 | 20.50 | 20.22 |
May | 0.201959E+11 | 32468.48 | 31-MAY-05:03 | 23.80 | 21.58 | 0.207366E+10 | 2606.60 | 30-MAY-09:20 | 23.80 | 21.58 |
June | 0.203362E+11 | 30030.67 | 13-JUN-04:02 | 23.90 | 21.88 | 0.206719E+10 | 2606.60 | 01-JUN-13:20 | 23.90 | 21.88 |
July | 0.204624E+11 | 29447.20 | 11-JUL-04:02 | 24.60 | 23.70 | 0.192067E+10 | 2606.60 | 03-JUL-13:20 | 24.60 | 23.70 |
August | 0.211572E+11 | 29932.73 | 30-AUG-04:02 | 24.45 | 22.91 | 0.215690E+10 | 2606.60 | 22-AUG-13:20 | 24.45 | 22.91 |
September | 0.191514E+11 | 29834.63 | 06-SEP-04:02 | 24.55 | 23.26 | 0.191398E+10 | 2606.60 | 18-SEP-13:20 | 28.47 | 25.99 |
October | 0.189536E+11 | 30077.27 | 24-OCT-04:02 | 25.83 | 25.19 | 0.198836E+10 | 2606.71 | 17-OCT-13:09 | 25.83 | 25.19 |
November | 0.150872E+11 | 21300.87 | 06-NOV-07:03 | 19.08 | 17.86 | 0.195440E+10 | 2606.67 | 24-NOV-10:20 | 20.87 | 16.31 |
December | 0.132807E+11 | 15240.74 | 15-DEC-17:00 | 28.00 | 21.24 | 0.185980E+10 | 2606.64 | 08-DEC-10:00 | 28.00 | 21.24 |
Annual Sum or Average | 0.203766E+12 | 0.235796E+11 | ||||||||
Minimum of Months | 0.120087E+11 | 14802.11 | 16.00 | 15.39 | 0.174285E+10 | 2606.60 | 20.50 | 16.31 | ||
Maximum of Months | 0.211572E+11 | 32468.48 | 28.30 | 25.19 | 0.215690E+10 | 2606.71 | 28.47 | 25.99 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115988E+11 | 16411.50 | 02-JAN-14:20 | 26.33 | 18.48 | 0.179384E+10 | 2606.65 | 02-JAN-10:20 | 26.33 | 18.48 |
February | 0.112615E+11 | 15743.54 | 27-FEB-16:20 | 25.13 | 20.45 | 0.167907E+10 | 2606.67 | 27-FEB-10:20 | 25.13 | 20.45 |
March | 0.139636E+11 | 15931.97 | 29-MAR-15:50 | 26.70 | 21.22 | 0.204289E+10 | 2606.65 | 06-MAR-10:09 | 26.70 | 21.22 |
April | 0.156628E+11 | 18394.25 | 28-APR-15:50 | 32.38 | 25.18 | 0.189095E+10 | 2606.67 | 12-APR-13:00 | 32.38 | 25.18 |
May | 0.214371E+11 | 31569.46 | 08-MAY-04:02 | 24.32 | 22.06 | 0.207396E+10 | 2606.60 | 26-MAY-13:20 | 27.23 | 24.58 |
June | 0.219178E+11 | 31897.43 | 13-JUN-04:02 | 23.90 | 21.88 | 0.206768E+10 | 2606.60 | 07-JUN-09:20 | 23.90 | 21.88 |
July | 0.218922E+11 | 32264.61 | 11-JUL-04:02 | 24.60 | 23.70 | 0.192175E+10 | 2606.60 | 03-JUL-13:20 | 24.60 | 23.70 |
August | 0.223732E+11 | 31854.25 | 22-AUG-04:02 | 25.67 | 24.57 | 0.215703E+10 | 2606.60 | 22-AUG-13:20 | 31.47 | 25.51 |
September | 0.196878E+11 | 32174.72 | 06-SEP-04:02 | 24.55 | 23.26 | 0.191303E+10 | 2606.60 | 18-SEP-13:20 | 28.47 | 25.99 |
October | 0.190140E+11 | 31797.67 | 23-OCT-04:03 | 24.92 | 24.16 | 0.198172E+10 | 2606.71 | 17-OCT-13:09 | 24.92 | 24.16 |
November | 0.140988E+11 | 17595.59 | 06-NOV-15:00 | 28.30 | 20.44 | 0.191318E+10 | 2606.64 | 13-NOV-14:20 | 23.30 | 17.15 |
December | 0.121672E+11 | 16193.65 | 15-DEC-16:30 | 28.00 | 21.24 | 0.177122E+10 | 2606.63 | 11-DEC-10:20 | 28.00 | 21.24 |
Annual Sum or Average | 0.205075E+12 | 0.232063E+11 | ||||||||
Minimum of Months | 0.112615E+11 | 15743.54 | 23.90 | 18.48 | 0.167907E+10 | 2606.60 | 23.30 | 17.15 | ||
Maximum of Months | 0.223732E+11 | 32264.61 | 32.38 | 25.18 | 0.215703E+10 | 2606.71 | 32.38 | 25.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196136E+10 | 4190.78 | 02-JAN-13:40 | 26.00 | 18.55 | 0.355819E+09 | 549.50 | 02-JAN-10:20 | 26.00 | 18.55 |
February | 0.219631E+10 | 4072.69 | 28-FEB-15:00 | 25.00 | 20.38 | 0.339165E+09 | 549.50 | 27-FEB-10:39 | 25.00 | 20.38 |
March | 0.293272E+10 | 5115.09 | 30-MAR-13:30 | 28.55 | 22.55 | 0.414058E+09 | 549.50 | 06-MAR-10:20 | 28.55 | 22.55 |
April | 0.397509E+10 | 6074.80 | 28-APR-15:10 | 33.12 | 23.52 | 0.393284E+09 | 549.50 | 12-APR-13:00 | 33.12 | 23.52 |
May | 0.654420E+10 | 10872.96 | 07-MAY-15:02 | 32.80 | 23.03 | 0.437877E+09 | 549.49 | 26-MAY-13:20 | 27.23 | 24.58 |
June | 0.709770E+10 | 10849.84 | 11-JUN-17:32 | 32.57 | 21.55 | 0.436560E+09 | 549.49 | 01-JUN-13:20 | 32.57 | 21.55 |
July | 0.694053E+10 | 11104.41 | 23-JUL-13:53 | 33.30 | 26.32 | 0.406221E+09 | 549.49 | 11-JUL-13:20 | 33.30 | 26.32 |
August | 0.690797E+10 | 10989.92 | 20-AUG-15:53 | 32.00 | 26.10 | 0.455314E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.557491E+10 | 10976.82 | 10-SEP-15:12 | 35.17 | 27.19 | 0.403817E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.506939E+10 | 8600.52 | 08-OCT-14:42 | 31.33 | 25.84 | 0.415421E+09 | 549.50 | 02-OCT-09:20 | 31.33 | 25.84 |
November | 0.301976E+10 | 5055.93 | 02-NOV-14:00 | 29.40 | 24.47 | 0.391691E+09 | 549.49 | 13-NOV-14:20 | 23.30 | 17.15 |
December | 0.226412E+10 | 4473.71 | 15-DEC-15:00 | 29.00 | 21.56 | 0.352341E+09 | 549.49 | 01-DEC-14:20 | 29.00 | 21.56 |
Annual Sum or Average | 0.544841E+11 | 0.480157E+10 | ||||||||
Minimum of Months | 0.196136E+10 | 4072.69 | 25.00 | 18.55 | 0.339165E+09 | 549.49 | 23.30 | 17.15 | ||
Maximum of Months | 0.709770E+10 | 11104.41 | 35.17 | 27.19 | 0.455314E+09 | 549.50 | 33.30 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158933E+10 | 4543.12 | 19-JAN-10:20 | 23.57 | 21.08 | 0.243915E+09 | 347.88 | 02-JAN-10:20 | 23.57 | 21.08 |
February | 0.188153E+10 | 4813.96 | 27-FEB-10:30 | 21.90 | 19.28 | 0.228087E+09 | 347.88 | 27-FEB-10:20 | 21.90 | 19.28 |
March | 0.270989E+10 | 7393.70 | 26-MAR-10:33 | 26.63 | 20.14 | 0.274742E+09 | 347.87 | 30-MAR-09:20 | 23.27 | 19.90 |
April | 0.373444E+10 | 11546.78 | 23-APR-11:13 | 26.80 | 20.29 | 0.253145E+09 | 347.88 | 10-APR-13:00 | 26.80 | 20.29 |
May | 0.557761E+10 | 11786.74 | 29-MAY-08:52 | 27.80 | 23.36 | 0.277549E+09 | 347.87 | 09-MAY-09:20 | 27.80 | 23.36 |
June | 0.585219E+10 | 11671.06 | 04-JUN-09:13 | 28.53 | 24.74 | 0.276603E+09 | 347.87 | 01-JUN-13:20 | 28.53 | 24.74 |
July | 0.571036E+10 | 12245.10 | 23-JUL-08:32 | 29.03 | 25.78 | 0.257453E+09 | 347.87 | 24-JUL-09:20 | 30.37 | 25.95 |
August | 0.563074E+10 | 11592.78 | 27-AUG-09:53 | 30.00 | 24.85 | 0.288478E+09 | 347.87 | 25-AUG-13:20 | 30.00 | 24.85 |
September | 0.455405E+10 | 12212.74 | 10-SEP-08:32 | 33.30 | 26.76 | 0.256117E+09 | 347.87 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.429309E+10 | 12103.81 | 09-OCT-10:32 | 29.67 | 22.84 | 0.264656E+09 | 347.89 | 02-OCT-09:30 | 29.67 | 22.84 |
November | 0.253556E+10 | 6404.09 | 11-NOV-09:53 | 24.40 | 21.68 | 0.257750E+09 | 347.87 | 10-NOV-10:00 | 24.40 | 21.68 |
December | 0.175771E+10 | 3736.12 | 16-DEC-10:10 | 24.33 | 21.30 | 0.235582E+09 | 347.87 | 01-DEC-14:20 | 24.33 | 21.30 |
Annual Sum or Average | 0.458265E+11 | 0.311408E+10 | ||||||||
Minimum of Months | 0.158933E+10 | 3736.12 | 21.90 | 19.28 | 0.228087E+09 | 347.87 | 21.90 | 19.28 | ||
Maximum of Months | 0.585219E+10 | 12245.10 | 33.30 | 26.76 | 0.288478E+09 | 347.89 | 30.37 | 25.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452918E+10 | 16068.27 | 01-JAN-13:41 | 25.83 | 18.00 | 0.397167E+09 | 557.04 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.450227E+10 | 14146.62 | 26-FEB-15:43 | 25.60 | 19.95 | 0.363430E+09 | 550.32 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.454424E+10 | 13335.04 | 26-MAR-15:53 | 26.10 | 20.12 | 0.428296E+09 | 549.50 | 24-MAR-13:39 | 26.10 | 20.12 |
April | 0.500000E+10 | 10412.51 | 23-APR-13:53 | 27.70 | 20.99 | 0.395148E+09 | 549.51 | 10-APR-13:00 | 27.70 | 20.99 |
May | 0.669595E+10 | 13346.28 | 07-MAY-14:23 | 33.35 | 23.43 | 0.437839E+09 | 549.49 | 26-MAY-13:20 | 27.23 | 24.58 |
June | 0.686876E+10 | 11347.31 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436415E+09 | 549.49 | 01-JUN-13:20 | 25.22 | 22.37 |
July | 0.689822E+10 | 13425.61 | 23-JUL-13:53 | 33.30 | 26.32 | 0.406140E+09 | 549.49 | 11-JUL-13:20 | 33.30 | 26.32 |
August | 0.764652E+10 | 13587.01 | 27-AUG-14:32 | 32.67 | 23.47 | 0.455415E+09 | 549.49 | 25-AUG-13:20 | 32.67 | 23.47 |
September | 0.698407E+10 | 14195.21 | 17-SEP-13:02 | 31.18 | 26.19 | 0.404309E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.804257E+10 | 14740.46 | 09-OCT-10:32 | 29.67 | 22.84 | 0.418480E+09 | 561.87 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.625286E+10 | 15011.78 | 11-NOV-12:32 | 26.60 | 22.57 | 0.408620E+09 | 577.04 | 06-NOV-14:09 | 26.60 | 22.57 |
December | 0.519357E+10 | 14971.64 | 17-DEC-14:32 | 18.33 | 12.17 | 0.383032E+09 | 560.27 | 15-DEC-14:39 | 18.33 | 12.17 |
Annual Sum or Average | 0.731582E+11 | 0.493429E+10 | ||||||||
Minimum of Months | 0.450227E+10 | 10412.51 | 18.33 | 12.17 | 0.363430E+09 | 549.49 | 18.33 | 12.17 | ||
Maximum of Months | 0.804257E+10 | 16068.27 | 33.35 | 26.32 | 0.455415E+09 | 577.04 | 33.30 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174194E+10 | 12904.11 | 01-JAN-15:42 | 25.00 | 18.55 | 0.234840E+09 | 347.85 | 02-JAN-10:20 | 21.33 | 18.13 |
February | 0.202642E+10 | 12592.56 | 26-FEB-16:23 | 24.95 | 19.89 | 0.220441E+09 | 347.86 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.261140E+10 | 11847.29 | 26-MAR-15:53 | 26.10 | 20.12 | 0.265429E+09 | 347.85 | 06-MAR-10:20 | 26.10 | 20.12 |
April | 0.368459E+10 | 12414.59 | 23-APR-16:32 | 27.37 | 21.80 | 0.250152E+09 | 347.85 | 12-APR-13:00 | 27.37 | 21.80 |
May | 0.509668E+10 | 13071.18 | 29-MAY-16:52 | 30.60 | 23.80 | 0.277356E+09 | 347.85 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.546835E+10 | 13006.15 | 11-JUN-16:52 | 33.30 | 21.96 | 0.276506E+09 | 347.85 | 01-JUN-13:20 | 33.30 | 21.96 |
July | 0.519710E+10 | 12140.39 | 16-JUL-16:02 | 31.32 | 25.35 | 0.257313E+09 | 347.85 | 11-JUL-13:20 | 31.32 | 25.35 |
August | 0.544775E+10 | 12909.69 | 06-AUG-16:42 | 25.67 | 23.43 | 0.288434E+09 | 347.85 | 07-AUG-09:20 | 28.00 | 25.36 |
September | 0.447764E+10 | 13043.28 | 10-SEP-16:32 | 33.50 | 26.81 | 0.255942E+09 | 347.84 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.431218E+10 | 12966.53 | 09-OCT-17:12 | 27.33 | 20.85 | 0.263793E+09 | 347.86 | 02-OCT-09:20 | 27.33 | 20.85 |
November | 0.263565E+10 | 12412.06 | 11-NOV-15:12 | 26.43 | 22.96 | 0.250712E+09 | 347.85 | 06-NOV-10:20 | 26.43 | 22.96 |
December | 0.202185E+10 | 8056.29 | 10-DEC-15:42 | 27.17 | 20.20 | 0.229641E+09 | 347.85 | 11-DEC-10:20 | 23.67 | 21.83 |
Annual Sum or Average | 0.447215E+11 | 0.307056E+10 | ||||||||
Minimum of Months | 0.174194E+10 | 8056.29 | 24.95 | 18.55 | 0.220441E+09 | 347.84 | 21.33 | 18.13 | ||
Maximum of Months | 0.546835E+10 | 13071.18 | 33.50 | 26.81 | 0.288434E+09 | 347.86 | 33.30 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244672E+10 | 3737.68 | 02-JAN-13:30 | 26.00 | 18.64 | 0.371262E+09 | 549.50 | 02-JAN-10:20 | 26.00 | 18.64 |
February | 0.224417E+10 | 3217.51 | 28-FEB-15:00 | 25.00 | 20.38 | 0.345341E+09 | 549.50 | 27-FEB-10:20 | 25.00 | 20.38 |
March | 0.274790E+10 | 3968.74 | 30-MAR-13:10 | 29.12 | 22.70 | 0.418627E+09 | 549.49 | 27-MAR-09:20 | 29.12 | 22.70 |
April | 0.318539E+10 | 4501.31 | 28-APR-15:10 | 33.12 | 23.52 | 0.394617E+09 | 549.50 | 18-APR-09:20 | 33.12 | 23.52 |
May | 0.545593E+10 | 7380.87 | 31-MAY-05:02 | 23.80 | 21.58 | 0.437332E+09 | 549.49 | 30-MAY-09:20 | 23.80 | 21.58 |
June | 0.608258E+10 | 7150.60 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436161E+09 | 549.49 | 01-JUN-13:20 | 25.22 | 22.37 |
July | 0.637297E+10 | 7737.60 | 12-JUL-05:02 | 23.90 | 23.16 | 0.405835E+09 | 549.49 | 11-JUL-13:20 | 23.90 | 23.16 |
August | 0.689919E+10 | 7900.02 | 23-AUG-04:02 | 26.38 | 23.83 | 0.455458E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.577620E+10 | 7330.75 | 11-SEP-04:02 | 24.83 | 23.63 | 0.404287E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.532005E+10 | 6819.11 | 10-OCT-06:03 | 21.92 | 19.97 | 0.419062E+09 | 549.51 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.329549E+10 | 4666.46 | 03-NOV-14:00 | 29.40 | 23.47 | 0.405901E+09 | 549.50 | 10-NOV-10:20 | 23.30 | 18.40 |
December | 0.271009E+10 | 4104.81 | 15-DEC-14:10 | 29.00 | 22.01 | 0.371885E+09 | 549.49 | 11-DEC-10:20 | 29.00 | 22.01 |
Annual Sum or Average | 0.525367E+11 | 0.486577E+10 | ||||||||
Minimum of Months | 0.224417E+10 | 3217.51 | 21.92 | 18.64 | 0.345341E+09 | 549.49 | 22.17 | 15.50 | ||
Maximum of Months | 0.689919E+10 | 7900.02 | 33.12 | 23.83 | 0.455458E+09 | 549.51 | 33.12 | 24.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192432E+10 | 4118.27 | 19-JAN-10:20 | 23.57 | 21.08 | 0.255326E+09 | 347.87 | 02-JAN-10:20 | 23.57 | 21.08 |
February | 0.189417E+10 | 4174.79 | 27-FEB-10:30 | 21.90 | 19.28 | 0.233478E+09 | 347.87 | 21-FEB-10:20 | 21.90 | 19.28 |
March | 0.253238E+10 | 4425.11 | 06-MAR-10:20 | 24.77 | 21.09 | 0.279322E+09 | 347.87 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.318249E+10 | 8822.51 | 23-APR-11:13 | 26.80 | 20.29 | 0.254126E+09 | 347.88 | 10-APR-13:00 | 26.80 | 20.29 |
May | 0.485415E+10 | 10282.55 | 29-MAY-09:32 | 28.53 | 23.16 | 0.277460E+09 | 347.87 | 09-MAY-09:20 | 28.53 | 23.16 |
June | 0.517629E+10 | 9052.94 | 11-JUN-08:13 | 25.93 | 21.07 | 0.276530E+09 | 347.87 | 01-JUN-13:20 | 25.93 | 21.07 |
July | 0.535345E+10 | 10841.49 | 16-JUL-09:52 | 31.10 | 25.83 | 0.257417E+09 | 347.87 | 24-JUL-09:20 | 30.37 | 25.95 |
August | 0.568869E+10 | 10599.15 | 06-AUG-10:32 | 30.67 | 26.61 | 0.288681E+09 | 347.87 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.474006E+10 | 10675.74 | 03-SEP-10:52 | 31.10 | 24.96 | 0.256440E+09 | 347.87 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.458986E+10 | 10834.54 | 09-OCT-09:42 | 28.68 | 22.57 | 0.266184E+09 | 347.88 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.291834E+10 | 5456.20 | 11-NOV-09:23 | 24.40 | 21.68 | 0.261890E+09 | 347.88 | 09-NOV-10:20 | 24.40 | 21.68 |
December | 0.210922E+10 | 3557.04 | 16-DEC-10:10 | 24.33 | 21.30 | 0.246453E+09 | 347.88 | 08-DEC-10:00 | 24.33 | 21.30 |
Annual Sum or Average | 0.449634E+11 | 0.315331E+10 | ||||||||
Minimum of Months | 0.189417E+10 | 3557.04 | 21.90 | 19.28 | 0.233478E+09 | 347.87 | 16.97 | 14.65 | ||
Maximum of Months | 0.568869E+10 | 10841.49 | 31.10 | 26.61 | 0.288681E+09 | 347.88 | 30.37 | 25.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390175E+10 | 12672.68 | 16-JAN-14:52 | 27.00 | 18.67 | 0.389494E+09 | 558.33 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.373617E+10 | 12118.39 | 26-FEB-15:43 | 25.60 | 19.95 | 0.357501E+09 | 570.53 | 02-FEB-13:09 | 25.60 | 19.95 |
March | 0.363218E+10 | 9841.55 | 06-MAR-13:00 | 27.20 | 21.71 | 0.415511E+09 | 549.50 | 13-MAR-13:20 | 19.97 | 10.40 |
April | 0.436256E+10 | 10746.40 | 28-APR-16:10 | 32.02 | 25.39 | 0.390755E+09 | 595.30 | 28-APR-12:09 | 32.02 | 25.39 |
May | 0.718505E+10 | 10977.07 | 19-MAY-12:00 | 32.20 | 23.63 | 0.439729E+09 | 612.73 | 19-MAY-12:09 | 32.30 | 23.64 |
June | 0.770188E+10 | 11127.91 | 28-JUN-12:00 | 32.80 | 25.51 | 0.438905E+09 | 620.76 | 28-JUN-12:09 | 32.80 | 25.64 |
July | 0.792751E+10 | 11688.45 | 21-JUL-16:10 | 35.45 | 25.77 | 0.409300E+09 | 651.58 | 20-JUL-12:09 | 35.45 | 25.77 |
August | 0.935697E+10 | 12158.43 | 30-AUG-16:20 | 35.83 | 23.47 | 0.459930E+09 | 645.20 | 10-AUG-12:09 | 35.83 | 23.47 |
September | 0.810397E+10 | 12294.84 | 03-SEP-13:32 | 31.83 | 24.36 | 0.406630E+09 | 633.02 | 01-SEP-12:09 | 31.83 | 24.36 |
October | 0.909859E+10 | 13142.45 | 09-OCT-11:42 | 30.83 | 23.19 | 0.425950E+09 | 654.94 | 06-OCT-12:09 | 30.83 | 23.19 |
November | 0.639391E+10 | 12907.72 | 11-NOV-14:42 | 26.52 | 22.99 | 0.412223E+09 | 617.49 | 02-NOV-12:09 | 26.52 | 22.99 |
December | 0.493627E+10 | 12882.19 | 17-DEC-14:32 | 18.33 | 12.17 | 0.379971E+09 | 589.89 | 15-DEC-13:09 | 18.33 | 12.17 |
Annual Sum or Average | 0.763368E+11 | 0.492590E+10 | ||||||||
Minimum of Months | 0.363218E+10 | 9841.55 | 18.33 | 12.17 | 0.357501E+09 | 549.50 | 18.33 | 10.40 | ||
Maximum of Months | 0.935697E+10 | 13142.45 | 35.83 | 25.77 | 0.459930E+09 | 654.94 | 35.83 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205619E+10 | 7648.42 | 01-JAN-17:12 | 22.67 | 19.00 | 0.247110E+09 | 347.85 | 30-JAN-10:20 | 22.33 | 19.83 |
February | 0.200563E+10 | 9959.18 | 26-FEB-17:42 | 23.48 | 19.39 | 0.227882E+09 | 347.85 | 22-FEB-10:20 | 23.48 | 19.39 |
March | 0.235752E+10 | 5199.88 | 06-MAR-16:30 | 25.55 | 21.32 | 0.272821E+09 | 347.85 | 06-MAR-10:20 | 25.55 | 21.32 |
April | 0.306989E+10 | 9867.80 | 16-APR-17:33 | 19.00 | 13.42 | 0.252968E+09 | 347.85 | 18-APR-09:20 | 22.73 | 16.40 |
May | 0.437155E+10 | 10862.51 | 29-MAY-16:52 | 30.60 | 23.80 | 0.277215E+09 | 347.85 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.478473E+10 | 10811.46 | 11-JUN-16:52 | 33.30 | 21.96 | 0.276460E+09 | 347.85 | 01-JUN-13:20 | 33.30 | 21.96 |
July | 0.482625E+10 | 9971.44 | 16-JUL-15:52 | 31.70 | 25.48 | 0.257265E+09 | 347.85 | 05-JUL-09:20 | 31.70 | 25.48 |
August | 0.548977E+10 | 10866.01 | 06-AUG-16:32 | 25.33 | 22.97 | 0.288649E+09 | 347.85 | 07-AUG-09:20 | 28.00 | 25.36 |
September | 0.465904E+10 | 11495.89 | 03-SEP-16:52 | 31.10 | 24.95 | 0.256357E+09 | 347.85 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.457710E+10 | 11062.03 | 09-OCT-17:02 | 27.67 | 21.05 | 0.266089E+09 | 347.86 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.289885E+10 | 9633.39 | 11-NOV-15:22 | 26.35 | 22.93 | 0.260192E+09 | 347.85 | 13-NOV-10:20 | 16.83 | 13.24 |
December | 0.232918E+10 | 5865.04 | 10-DEC-15:42 | 27.17 | 20.20 | 0.243751E+09 | 347.85 | 11-DEC-10:20 | 23.67 | 21.83 |
Annual Sum or Average | 0.434257E+11 | 0.312676E+10 | ||||||||
Minimum of Months | 0.200563E+10 | 5199.88 | 19.00 | 13.42 | 0.227882E+09 | 347.85 | 16.83 | 13.24 | ||
Maximum of Months | 0.548977E+10 | 11495.89 | 33.30 | 25.48 | 0.288649E+09 | 347.86 | 33.30 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236298E+10 | 4300.33 | 02-JAN-13:30 | 26.00 | 18.64 | 0.368758E+09 | 549.49 | 18-JAN-10:20 | 22.33 | 19.40 |
February | 0.240281E+10 | 3854.37 | 28-FEB-15:00 | 25.00 | 20.38 | 0.349207E+09 | 549.50 | 27-FEB-10:20 | 25.00 | 20.38 |
March | 0.306281E+10 | 4810.11 | 30-MAR-13:10 | 29.12 | 22.70 | 0.425602E+09 | 549.49 | 06-MAR-10:20 | 29.12 | 22.70 |
April | 0.387035E+10 | 5417.02 | 26-APR-14:40 | 27.90 | 22.48 | 0.398248E+09 | 549.50 | 12-APR-13:20 | 27.90 | 22.48 |
May | 0.615733E+10 | 7739.37 | 22-MAY-04:02 | 26.10 | 22.31 | 0.437891E+09 | 549.49 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.660690E+10 | 7988.61 | 12-JUN-04:02 | 23.90 | 21.28 | 0.436538E+09 | 549.49 | 01-JUN-13:20 | 23.90 | 21.28 |
July | 0.648665E+10 | 9364.66 | 23-JUL-16:33 | 31.87 | 26.63 | 0.406091E+09 | 549.49 | 24-JUL-09:20 | 30.37 | 25.95 |
August | 0.652016E+10 | 8920.11 | 20-AUG-15:53 | 32.00 | 26.10 | 0.455356E+09 | 549.49 | 25-AUG-13:20 | 27.90 | 24.42 |
September | 0.536289E+10 | 8759.88 | 10-SEP-15:12 | 35.17 | 27.19 | 0.404104E+09 | 549.49 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.497835E+10 | 9321.55 | 08-OCT-14:32 | 31.67 | 25.93 | 0.417846E+09 | 549.50 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.317737E+10 | 4655.40 | 01-NOV-13:30 | 29.40 | 24.88 | 0.401756E+09 | 549.50 | 28-NOV-10:20 | 25.13 | 20.31 |
December | 0.258459E+10 | 4191.19 | 11-DEC-13:30 | 26.00 | 22.83 | 0.366271E+09 | 549.49 | 01-DEC-14:20 | 26.00 | 22.83 |
Annual Sum or Average | 0.535732E+11 | 0.486767E+10 | ||||||||
Minimum of Months | 0.236298E+10 | 3854.37 | 23.90 | 18.64 | 0.349207E+09 | 549.49 | 22.17 | 15.50 | ||
Maximum of Months | 0.660690E+10 | 9364.66 | 35.17 | 27.19 | 0.455356E+09 | 549.50 | 30.37 | 25.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163233E+10 | 6444.98 | 03-JAN-13:01 | 12.33 | 5.46 | 0.185500E+09 | 356.45 | 24-JAN-13:09 | 17.00 | 10.00 |
February | 0.185489E+10 | 6044.16 | 13-FEB-13:01 | 12.90 | 4.84 | 0.171735E+09 | 356.46 | 09-FEB-11:09 | 12.90 | 4.84 |
March | 0.263483E+10 | 7555.58 | 26-MAR-10:23 | 26.35 | 20.17 | 0.206111E+09 | 356.45 | 24-MAR-10:09 | 26.35 | 20.17 |
April | 0.348900E+10 | 11743.77 | 23-APR-09:42 | 25.82 | 20.99 | 0.188554E+09 | 356.46 | 10-APR-14:09 | 25.82 | 20.99 |
May | 0.508601E+10 | 12475.11 | 29-MAY-08:41 | 27.62 | 23.19 | 0.206093E+09 | 356.45 | 03-MAY-10:09 | 27.62 | 23.19 |
June | 0.527343E+10 | 11209.80 | 11-JUN-08:13 | 25.93 | 21.07 | 0.205131E+09 | 356.45 | 20-JUN-10:09 | 30.18 | 24.61 |
July | 0.517956E+10 | 11981.15 | 16-JUL-09:52 | 31.10 | 25.83 | 0.191534E+09 | 356.45 | 07-JUL-10:09 | 31.10 | 25.83 |
August | 0.513110E+10 | 11522.28 | 06-AUG-09:52 | 30.00 | 26.94 | 0.213890E+09 | 356.45 | 30-AUG-10:09 | 30.08 | 23.72 |
September | 0.418624E+10 | 12056.43 | 03-SEP-09:42 | 29.98 | 24.61 | 0.190368E+09 | 356.45 | 01-SEP-10:09 | 29.98 | 24.61 |
October | 0.404378E+10 | 11917.34 | 09-OCT-09:42 | 28.68 | 22.57 | 0.197173E+09 | 356.46 | 18-OCT-10:09 | 23.28 | 18.14 |
November | 0.252885E+10 | 7346.35 | 11-NOV-09:33 | 24.40 | 21.68 | 0.192677E+09 | 356.46 | 27-NOV-11:09 | 24.08 | 18.18 |
December | 0.179001E+10 | 5601.75 | 26-DEC-13:01 | 11.97 | 4.34 | 0.179422E+09 | 356.46 | 08-DEC-11:09 | 11.97 | 4.34 |
Annual Sum or Average | 0.428300E+11 | 0.232819E+10 | ||||||||
Minimum of Months | 0.163233E+10 | 5601.75 | 11.97 | 4.34 | 0.171735E+09 | 356.45 | 11.97 | 4.34 | ||
Maximum of Months | 0.527343E+10 | 12475.11 | 31.10 | 26.94 | 0.213890E+09 | 356.46 | 31.10 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501418E+10 | 13033.98 | 01-JAN-13:52 | 26.00 | 17.88 | 0.405723E+09 | 573.62 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.476120E+10 | 13105.45 | 26-FEB-13:32 | 26.43 | 19.30 | 0.370390E+09 | 566.17 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.467526E+10 | 11600.72 | 05-MAR-13:23 | 27.70 | 18.32 | 0.437697E+09 | 549.50 | 24-MAR-13:20 | 24.03 | 15.88 |
April | 0.486102E+10 | 9308.72 | 23-APR-14:23 | 28.25 | 21.28 | 0.399487E+09 | 549.51 | 10-APR-13:00 | 28.25 | 21.28 |
May | 0.629435E+10 | 9592.52 | 08-MAY-04:02 | 24.32 | 22.06 | 0.437905E+09 | 549.49 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.638841E+10 | 9362.91 | 05-JUN-04:02 | 25.22 | 22.37 | 0.436417E+09 | 549.49 | 01-JUN-13:20 | 25.22 | 22.37 |
July | 0.644709E+10 | 10894.66 | 23-JUL-13:53 | 33.30 | 26.32 | 0.406030E+09 | 549.49 | 10-JUL-09:20 | 33.30 | 26.32 |
August | 0.721681E+10 | 11864.85 | 27-AUG-14:32 | 32.67 | 23.47 | 0.455488E+09 | 549.49 | 25-AUG-13:20 | 32.67 | 23.47 |
September | 0.668479E+10 | 12497.08 | 17-SEP-13:02 | 31.18 | 26.19 | 0.404631E+09 | 549.49 | 20-SEP-13:20 | 26.60 | 22.72 |
October | 0.787988E+10 | 13477.46 | 09-OCT-11:42 | 30.83 | 23.19 | 0.420651E+09 | 576.01 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.646274E+10 | 12799.57 | 05-NOV-14:32 | 27.20 | 20.29 | 0.413660E+09 | 594.47 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.559758E+10 | 13302.13 | 17-DEC-14:32 | 18.33 | 12.17 | 0.392089E+09 | 574.61 | 15-DEC-14:39 | 18.33 | 12.17 |
Annual Sum or Average | 0.722833E+11 | 0.498017E+10 | ||||||||
Minimum of Months | 0.467526E+10 | 9308.72 | 18.33 | 12.17 | 0.370390E+09 | 549.49 | 18.33 | 12.17 | ||
Maximum of Months | 0.787988E+10 | 13477.46 | 33.30 | 26.32 | 0.455488E+09 | 594.47 | 33.30 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199285E+10 | 8462.19 | 01-JAN-17:12 | 22.67 | 19.00 | 0.242020E+09 | 347.85 | 18-JAN-10:20 | 22.33 | 19.40 |
February | 0.215131E+10 | 11500.44 | 26-FEB-17:33 | 23.67 | 19.48 | 0.226232E+09 | 347.85 | 27-FEB-10:20 | 21.63 | 19.26 |
March | 0.267418E+10 | 10280.64 | 26-MAR-15:43 | 25.72 | 20.08 | 0.272486E+09 | 347.85 | 27-MAR-09:20 | 22.57 | 20.65 |
April | 0.357124E+10 | 11977.44 | 23-APR-17:42 | 25.78 | 21.36 | 0.253135E+09 | 347.85 | 18-APR-09:20 | 25.78 | 21.36 |
May | 0.479764E+10 | 12039.55 | 29-MAY-16:41 | 30.97 | 23.75 | 0.277396E+09 | 347.85 | 30-MAY-09:20 | 28.17 | 24.25 |
June | 0.509422E+10 | 11855.59 | 11-JUN-16:52 | 33.30 | 21.96 | 0.276539E+09 | 347.85 | 05-JUN-09:20 | 33.30 | 21.96 |
July | 0.485844E+10 | 11865.19 | 30-JUL-15:42 | 27.38 | 24.31 | 0.257280E+09 | 347.85 | 10-JUL-09:20 | 27.38 | 24.31 |
August | 0.514785E+10 | 11721.95 | 06-AUG-16:32 | 25.33 | 22.97 | 0.288471E+09 | 347.85 | 07-AUG-09:20 | 28.00 | 25.36 |
September | 0.428165E+10 | 12574.08 | 03-SEP-16:21 | 31.65 | 24.79 | 0.256129E+09 | 347.85 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.421615E+10 | 12099.83 | 08-OCT-15:52 | 31.00 | 25.22 | 0.265179E+09 | 347.85 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.273583E+10 | 10549.92 | 05-NOV-15:53 | 27.20 | 19.54 | 0.256447E+09 | 347.85 | 28-NOV-10:20 | 25.13 | 20.31 |
December | 0.222319E+10 | 7261.31 | 10-DEC-15:42 | 27.17 | 20.20 | 0.237564E+09 | 347.85 | 11-DEC-10:20 | 23.67 | 21.83 |
Annual Sum or Average | 0.437446E+11 | 0.310888E+10 | ||||||||
Minimum of Months | 0.199285E+10 | 7261.31 | 22.67 | 19.00 | 0.226232E+09 | 347.85 | 21.63 | 15.56 | ||
Maximum of Months | 0.514785E+10 | 12574.08 | 33.30 | 25.22 | 0.288471E+09 | 347.85 | 33.30 | 25.36 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.766775E+09 | 8040.23 | 10-JAN-07:03 | 3.17 |
February | 0.439165E+09 | 8448.68 | 06-FEB-07:03 | 3.90 |
March | 0.497183E+09 | 5304.08 | 13-MAR-06:02 | 5.92 |
April | 0.152243E+09 | 2874.05 | 11-APR-05:03 | 10.63 |
May | 17507909.94 | 4860.27 | 30-MAY-04:02 | 25.60 |
June | 18491729.39 | 4254.60 | 12-JUN-04:02 | 23.90 |
July | 16690893.29 | 4331.69 | 10-JUL-04:02 | 25.40 |
August | 15981013.69 | 3858.95 | 14-AUG-04:02 | 26.10 |
September | 14310179.94 | 4756.97 | 11-SEP-04:02 | 24.83 |
October | 82409001.50 | 3100.37 | 23-OCT-04:03 | 24.92 |
November | 0.244948E+09 | 3098.53 | 15-NOV-06:02 | 7.70 |
December | 0.592213E+09 | 8255.51 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.285792E+10 | |||
Minimum of Months | 14310179.94 | 2874.05 | 0.50 | |
Maximum of Months | 0.766775E+09 | 8448.68 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294544E+09 | 3333.51 | 16-JAN-15:43 | 25.33 |
February | 0.171806E+09 | 3226.65 | 26-FEB-16:12 | 25.13 |
March | 0.109765E+09 | 2234.53 | 26-MAR-15:43 | 25.72 |
April | 9432900.97 | 1664.76 | 09-APR-14:53 | 22.70 |
May | 12155755.40 | 2218.87 | 22-MAY-04:02 | 26.10 |
June | 9600668.59 | 1849.37 | 19-JUN-04:02 | 25.50 |
July | 12200343.50 | 1953.07 | 07-JUL-04:02 | 25.50 |
August | 10521464.72 | 2045.72 | 23-AUG-04:02 | 26.38 |
September | 14397343.53 | 2071.05 | 03-SEP-15:41 | 32.28 |
October | 18934902.58 | 2299.23 | 29-OCT-13:13 | 23.33 |
November | 41495021.65 | 2944.06 | 26-NOV-12:32 | 19.93 |
December | 0.181563E+09 | 4240.00 | 31-DEC-14:23 | 22.50 |
Annual Sum or Average | 0.886416E+09 | |||
Minimum of Months | 9432900.97 | 1664.76 | 19.93 | |
Maximum of Months | 0.294544E+09 | 4240.00 | 32.28 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 90987236.11 | 5601.58 | 05-JAN-06:02 | 0.17 |
February | 59153670.38 | 3855.39 | 17-FEB-06:02 | 1.52 |
March | 41013760.38 | 5057.23 | 09-MAR-06:02 | 1.10 |
April | 12335220.11 | 1910.52 | 10-APR-05:13 | 12.20 |
May | 18196774.59 | 3322.67 | 01-MAY-04:02 | 26.10 |
June | 17190954.62 | 3050.30 | 02-JUN-04:03 | 24.40 |
July | 21189279.88 | 3310.39 | 07-JUL-04:02 | 25.50 |
August | 22904583.66 | 3751.67 | 23-AUG-04:02 | 26.38 |
September | 27028412.20 | 3833.10 | 19-SEP-04:02 | 26.10 |
October | 28528664.72 | 3661.86 | 24-OCT-04:02 | 25.83 |
November | 32758391.19 | 2439.25 | 13-NOV-06:12 | 9.60 |
December | 67450195.62 | 3223.56 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.438737E+09 | |||
Minimum of Months | 12335220.11 | 1910.52 | 0.17 | |
Maximum of Months | 90987236.11 | 5601.58 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30779809.79 | 18126.63 | 26-JAN-07:01 | 7.00 |
February | 30049425.01 | 19037.86 | 06-FEB-06:12 | 3.07 |
March | 10921496.74 | 17502.40 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 15153286.78 | 17277.15 | 22-DEC-07:03 | 10.33 |
Annual Sum or Average | 86904018.33 | |||
Minimum of Months | 0.00 | 0.00 | 3.07 | |
Maximum of Months | 30779809.79 | 19037.86 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250143E+09 | 8719.05 | 10-JAN-06:11 | 3.00 |
February | 0.118462E+09 | 9047.76 | 06-FEB-06:11 | 3.07 |
March | 88461815.79 | 8303.26 | 13-MAR-05:12 | 6.57 |
April | 247720.13 | 2064.33 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 7671064.97 | 7804.74 | 15-NOV-07:01 | 7.80 |
December | 0.144260E+09 | 8710.17 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.609246E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.250143E+09 | 9047.76 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104293E+09 | 5127.42 | 24-JAN-06:12 | 6.67 |
February | 44798214.63 | 5341.56 | 06-FEB-06:11 | 3.07 |
March | 47773961.44 | 4685.51 | 09-MAR-06:02 | 1.10 |
April | 116613.36 | 971.78 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 2201409.55 | 4890.66 | 24-NOV-07:02 | 13.08 |
December | 74636559.85 | 5152.89 | 23-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.273820E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.10 | |
Maximum of Months | 0.104293E+09 | 5341.56 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122878E+09 | 8097.89 | 10-JAN-06:11 | 3.00 |
February | 61030572.34 | 8430.18 | 06-FEB-06:11 | 3.07 |
March | 64916426.40 | 7548.84 | 13-MAR-05:12 | 6.57 |
April | 78176.58 | 651.47 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 2231527.37 | 7287.46 | 15-NOV-07:01 | 7.80 |
December | 79891039.79 | 8074.94 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.331025E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.122878E+09 | 8430.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137446E+09 | 4888.71 | 09-JAN-06:12 | 6.33 |
February | 64369762.81 | 5226.10 | 07-FEB-06:12 | 8.43 |
March | 49886096.67 | 4844.90 | 10-MAR-07:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 3700450.57 | 4384.32 | 24-NOV-07:02 | 13.08 |
December | 79531878.24 | 5198.29 | 23-DEC-06:12 | 6.33 |
Annual Sum or Average | 0.334934E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.33 | |
Maximum of Months | 0.137446E+09 | 5226.10 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8378509.65 | 4873.17 | 07-JAN-07:03 | 4.83 |
February | 9115097.96 | 4746.05 | 06-FEB-06:11 | 3.07 |
March | 6227475.76 | 4678.26 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 3650245.66 | 4643.71 | 21-DEC-07:01 | 0.50 |
Annual Sum or Average | 27371329.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 9115097.96 | 4873.17 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1274678.35 | 2621.47 | 09-JAN-07:01 | 5.00 |
February | 2071974.05 | 3161.07 | 07-FEB-07:02 | 7.88 |
March | 1641333.17 | 3088.91 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 1315991.70 | 2972.42 | 20-DEC-07:01 | 1.83 |
Annual Sum or Average | 6303977.26 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 2071974.05 | 3161.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460049E+09 | 6228.44 | 05-JAN-07:10 | 0.83 |
February | 0.267873E+09 | 6217.41 | 17-FEB-07:10 | 1.28 |
March | 0.415695E+09 | 6160.60 | 09-MAR-07:10 | 1.18 |
April | 85365477.06 | 5017.60 | 03-APR-06:03 | 12.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 7206464.29 | 4713.50 | 27-OCT-06:07 | 14.83 |
November | 0.111516E+09 | 4910.85 | 13-NOV-07:50 | 11.13 |
December | 0.401146E+09 | 6334.53 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.174885E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.50 | |
Maximum of Months | 0.460049E+09 | 6334.53 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1016722.48 | 3202.26 | 09-JAN-07:01 | 5.00 |
February | 2114802.20 | 2494.94 | 17-FEB-07:01 | 1.28 |
March | 1653220.49 | 3109.95 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 703755.23 | 3186.81 | 20-DEC-07:01 | 1.83 |
Annual Sum or Average | 5488500.39 | |||
Minimum of Months | 0.00 | 0.00 | 1.28 | |
Maximum of Months | 2114802.20 | 3202.26 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31973944.51 | 6015.53 | 10-JAN-06:11 | 3.00 |
February | 18526654.61 | 6218.22 | 06-FEB-06:11 | 3.07 |
March | 8558126.16 | 5858.01 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 17120336.70 | 6042.40 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 76179061.98 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 31973944.51 | 6218.22 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14131130.74 | 3829.44 | 25-JAN-07:02 | 9.00 |
February | 7826260.18 | 3869.32 | 17-FEB-07:03 | 1.28 |
March | 4291722.09 | 3594.47 | 14-MAR-06:02 | 7.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 10482792.32 | 3946.65 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 36731905.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 14131130.74 | 3946.65 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13129047.71 | 5814.93 | 27-JAN-07:01 | 5.33 |
February | 7020601.95 | 5717.85 | 18-FEB-07:03 | 6.78 |
March | 4757539.10 | 5354.43 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 9902810.70 | 5780.98 | 30-DEC-07:03 | 6.00 |
Annual Sum or Average | 34809999.46 | |||
Minimum of Months | 0.00 | 0.00 | 5.33 | |
Maximum of Months | 13129047.71 | 5814.93 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17176803.52 | 4032.93 | 10-JAN-06:11 | 3.00 |
February | 9111619.85 | 4021.74 | 06-FEB-06:12 | 3.07 |
March | 4448705.11 | 3387.19 | 11-MAR-07:03 | 6.78 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 9196687.46 | 3727.43 | 26-DEC-07:01 | 5.32 |
Annual Sum or Average | 39933815.94 | |||
Minimum of Months | 0.00 | 0.00 | 3.00 | |
Maximum of Months | 17176803.52 | 4032.93 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596000E+09 | 856.92 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.520268E+09 | 886.73 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598387E+09 | 816.37 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521060E+09 | 839.44 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544709E+09 | 579.96 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.535151E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.506072E+09 | 563.12 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573749E+09 | 582.60 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.527447E+09 | 814.03 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.562530E+09 | 929.66 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.586682E+09 | 892.09 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.589293E+09 | 922.03 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.666135E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.506072E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.598387E+09 | 929.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370412E+09 | 508.06 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325217E+09 | 539.15 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375341E+09 | 476.32 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329117E+09 | 508.70 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346873E+09 | 357.88 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342047E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.322163E+09 | 335.10 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363599E+09 | 354.50 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333122E+09 | 473.32 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.353377E+09 | 573.77 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366042E+09 | 571.12 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367494E+09 | 574.45 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419481E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.322163E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.375341E+09 | 574.45 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.568805E+09 | 830.22 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.505681E+09 | 870.02 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.592204E+09 | 807.23 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522577E+09 | 842.98 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.550109E+09 | 584.04 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.542304E+09 | 546.69 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.510706E+09 | 575.11 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.576306E+09 | 682.40 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525913E+09 | 811.29 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.555520E+09 | 922.68 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.563210E+09 | 865.40 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.562018E+09 | 912.21 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657535E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.505681E+09 | 546.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.592204E+09 | 922.68 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.367139E+09 | 550.15 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.324901E+09 | 565.87 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378582E+09 | 536.89 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.331470E+09 | 544.75 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347984E+09 | 453.34 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342126E+09 | 362.18 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323102E+09 | 423.86 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365563E+09 | 492.34 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335950E+09 | 537.44 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355044E+09 | 593.49 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.361498E+09 | 577.13 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361460E+09 | 584.02 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419482E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323102E+09 | 362.18 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378582E+09 | 593.49 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593656E+09 | 849.85 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.518580E+09 | 880.84 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.596868E+09 | 807.50 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.520364E+09 | 831.63 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544147E+09 | 577.01 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.534675E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.505449E+09 | 559.29 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573038E+09 | 579.75 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.526634E+09 | 805.11 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.561277E+09 | 925.37 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.584139E+09 | 886.16 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.586764E+09 | 917.54 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.664559E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.505449E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.596868E+09 | 925.37 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369563E+09 | 502.29 | 31-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.324582E+09 | 535.17 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374745E+09 | 469.83 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328772E+09 | 503.49 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346429E+09 | 356.42 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.341627E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321803E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363218E+09 | 352.10 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332630E+09 | 466.50 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.352862E+09 | 570.93 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.365072E+09 | 568.41 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.366234E+09 | 571.73 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418754E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.321803E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374745E+09 | 571.73 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.568414E+09 | 821.86 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.505576E+09 | 863.32 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.591200E+09 | 797.91 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.521768E+09 | 835.35 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549174E+09 | 581.32 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.541477E+09 | 542.41 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.509968E+09 | 572.00 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.575514E+09 | 668.29 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525259E+09 | 802.25 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.554631E+09 | 918.06 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.562572E+09 | 858.31 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.561230E+09 | 907.24 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.656678E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.505576E+09 | 542.41 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.591200E+09 | 918.06 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366243E+09 | 546.81 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.324178E+09 | 563.02 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377633E+09 | 533.14 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330936E+09 | 541.26 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347418E+09 | 447.30 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.341494E+09 | 360.55 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.322570E+09 | 369.04 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364976E+09 | 486.90 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335301E+09 | 533.73 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354388E+09 | 591.49 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.360698E+09 | 574.58 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.360555E+09 | 581.73 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418639E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.322570E+09 | 360.55 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.377633E+09 | 591.49 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.595998E+09 | 856.90 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.520249E+09 | 886.72 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598386E+09 | 816.35 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521059E+09 | 839.42 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.544708E+09 | 579.96 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.535151E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.506072E+09 | 563.11 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573748E+09 | 582.59 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.527446E+09 | 814.01 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.562529E+09 | 929.65 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.586680E+09 | 892.08 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.589291E+09 | 922.02 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.666132E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.506072E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.598386E+09 | 929.65 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370412E+09 | 508.06 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325217E+09 | 539.14 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375340E+09 | 476.31 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329116E+09 | 508.69 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346873E+09 | 357.88 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342047E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.322163E+09 | 335.10 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363599E+09 | 354.50 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333121E+09 | 473.31 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.353377E+09 | 573.76 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.366041E+09 | 571.11 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367493E+09 | 574.44 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419480E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.322163E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.375340E+09 | 574.44 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.568805E+09 | 830.21 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.505680E+09 | 870.01 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.592203E+09 | 807.21 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522576E+09 | 842.96 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.550108E+09 | 584.03 | 23-MAY-07:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.542304E+09 | 546.68 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.510705E+09 | 575.11 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.576305E+09 | 682.37 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525912E+09 | 811.27 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.555519E+09 | 922.67 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.563209E+09 | 865.38 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.562017E+09 | 912.20 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657534E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.505680E+09 | 546.68 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.592203E+09 | 922.67 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.367139E+09 | 550.14 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.324900E+09 | 565.86 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378582E+09 | 536.88 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.331470E+09 | 544.74 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347984E+09 | 453.33 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342125E+09 | 362.17 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323101E+09 | 423.84 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365563E+09 | 492.33 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335949E+09 | 537.43 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355043E+09 | 593.48 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.361497E+09 | 577.13 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361459E+09 | 584.02 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419481E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323101E+09 | 362.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378582E+09 | 593.48 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.596000E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1049991.68 | 0.177008E+09 |
February | 0.901968E+09 | 0.520268E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1479244.35 | 0.136429E+09 |
March | 0.107774E+10 | 0.598387E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4121089.13 | 0.148855E+09 |
April | 0.956342E+09 | 0.521060E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873971.11 | 68249142.47 |
May | 0.103597E+10 | 0.544709E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29231404.78 | 12443496.54 |
June | 0.103308E+10 | 0.535151E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26580027.87 | 9389479.32 |
July | 0.959235E+09 | 0.506072E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36438835.66 | 4260808.98 |
August | 0.107774E+10 | 0.573749E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36126050.06 | 12132987.57 |
September | 0.956342E+09 | 0.527447E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32730221.15 | 18828080.78 |
October | 0.994195E+09 | 0.562530E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27182312.86 | 58933238.07 |
November | 0.984487E+09 | 0.586682E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3642907.04 | 92560519.68 |
December | 0.959235E+09 | 0.589293E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2454367.66 | 0.159026E+09 |
Annual Sum or Average | 0.119305E+11 | 0.666135E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207910E+09 | 0.898115E+09 |
Minimum of Months | 0.901968E+09 | 0.506072E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1049991.68 | 4260808.98 |
Maximum of Months | 0.107774E+10 | 0.598387E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36438835.66 | 0.177008E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.370412E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376071.54 | 0.124863E+09 |
February | 0.571020E+09 | 0.325217E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 692801.17 | 96473815.36 |
March | 0.682301E+09 | 0.375341E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1913827.69 | 0.104674E+09 |
April | 0.605444E+09 | 0.329117E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4226954.69 | 48865625.38 |
May | 0.655854E+09 | 0.346873E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18383751.66 | 8928705.34 |
June | 0.654023E+09 | 0.342047E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17255305.61 | 6545229.42 |
July | 0.607275E+09 | 0.322163E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23182746.81 | 3153650.33 |
August | 0.682301E+09 | 0.363599E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23282008.47 | 8440388.91 |
September | 0.605444E+09 | 0.333122E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20437829.93 | 13202594.50 |
October | 0.629407E+09 | 0.353377E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16312242.16 | 41948683.73 |
November | 0.623262E+09 | 0.366042E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1734685.54 | 66275895.50 |
December | 0.607275E+09 | 0.367494E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1154642.09 | 0.110727E+09 |
Annual Sum or Average | 0.755301E+10 | 0.419481E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128953E+09 | 0.634099E+09 |
Minimum of Months | 0.571020E+09 | 0.322163E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376071.54 | 3153650.33 |
Maximum of Months | 0.682301E+09 | 0.375341E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23282008.47 | 0.124863E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.568805E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354407.08 | 0.203393E+09 |
February | 0.901968E+09 | 0.505681E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 843285.75 | 0.155672E+09 |
March | 0.107774E+10 | 0.592204E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2655217.31 | 0.158385E+09 |
April | 0.956342E+09 | 0.522577E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6356514.77 | 72346699.05 |
May | 0.103597E+10 | 0.550109E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29309937.93 | 12405499.39 |
June | 0.103308E+10 | 0.542304E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27030417.69 | 9077350.59 |
July | 0.959235E+09 | 0.510706E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36795185.31 | 4214106.39 |
August | 0.107774E+10 | 0.576306E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35666801.18 | 12389458.07 |
September | 0.956342E+09 | 0.525913E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30918751.45 | 20292653.39 |
October | 0.994195E+09 | 0.555520E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23237826.56 | 68427223.81 |
November | 0.984487E+09 | 0.563210E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2304216.05 | 0.106811E+09 |
December | 0.959235E+09 | 0.562018E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1486618.77 | 0.181399E+09 |
Annual Sum or Average | 0.119305E+11 | 0.657535E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196959E+09 | 0.100481E+10 |
Minimum of Months | 0.901968E+09 | 0.505681E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354407.08 | 4214106.39 |
Maximum of Months | 0.107774E+10 | 0.592204E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36795185.31 | 0.203393E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.367139E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 442162.22 | 0.125309E+09 |
February | 0.570983E+09 | 0.324901E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 742515.12 | 96642360.54 |
March | 0.682256E+09 | 0.378582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2390093.58 | 0.103892E+09 |
April | 0.605404E+09 | 0.331470E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4044032.67 | 50117904.53 |
May | 0.655811E+09 | 0.347984E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18879874.63 | 9268817.56 |
June | 0.653980E+09 | 0.342126E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17064431.26 | 7081399.38 |
July | 0.607235E+09 | 0.323102E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23170528.60 | 3455242.27 |
August | 0.682256E+09 | 0.365563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23363301.47 | 9319520.36 |
September | 0.605404E+09 | 0.335950E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20466510.71 | 14084218.69 |
October | 0.629366E+09 | 0.355044E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16687715.24 | 43755279.10 |
November | 0.623221E+09 | 0.361498E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1982226.43 | 65420698.30 |
December | 0.607235E+09 | 0.361460E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1327297.02 | 0.112044E+09 |
Annual Sum or Average | 0.755252E+10 | 0.419482E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130561E+09 | 0.640391E+09 |
Minimum of Months | 0.570983E+09 | 0.323102E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 442162.22 | 3455242.27 |
Maximum of Months | 0.682256E+09 | 0.378582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23363301.47 | 0.125309E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.593656E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544158.13 | 0.104849E+09 |
February | 0.901968E+09 | 0.518580E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 856484.04 | 79988896.31 |
March | 0.107774E+10 | 0.596868E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2552784.53 | 82704253.94 |
April | 0.956342E+09 | 0.520364E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4174066.66 | 36168756.89 |
May | 0.103597E+10 | 0.544147E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17158291.00 | 4808526.29 |
June | 0.103308E+10 | 0.534675E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15234065.03 | 4311946.40 |
July | 0.959235E+09 | 0.505449E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21233928.18 | 1812492.09 |
August | 0.107774E+10 | 0.573038E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19949003.27 | 6900072.51 |
September | 0.956342E+09 | 0.526634E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18560717.14 | 10662716.02 |
October | 0.994195E+09 | 0.561277E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15181235.71 | 34609960.51 |
November | 0.984487E+09 | 0.584139E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1862403.48 | 56081665.21 |
December | 0.959235E+09 | 0.586764E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230167.50 | 95793790.74 |
Annual Sum or Average | 0.119305E+11 | 0.664559E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118537E+09 | 0.518692E+09 |
Minimum of Months | 0.901968E+09 | 0.505449E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544158.13 | 1812492.09 |
Maximum of Months | 0.107774E+10 | 0.596868E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21233928.18 | 0.104849E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.369563E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194998.85 | 75422415.01 |
February | 0.571020E+09 | 0.324582E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399501.91 | 57427402.90 |
March | 0.682301E+09 | 0.374745E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1137826.66 | 59379257.24 |
April | 0.605444E+09 | 0.328772E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2411468.53 | 26635195.02 |
May | 0.655854E+09 | 0.346429E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10216868.10 | 4055512.93 |
June | 0.654023E+09 | 0.341627E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9551830.95 | 3323373.28 |
July | 0.607275E+09 | 0.321803E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12800426.79 | 1652123.41 |
August | 0.682301E+09 | 0.363218E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12525243.33 | 5207496.51 |
September | 0.605444E+09 | 0.332630E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11127625.82 | 8069957.35 |
October | 0.629407E+09 | 0.352862E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8870327.31 | 25320810.16 |
November | 0.623262E+09 | 0.365072E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 943312.68 | 40429890.52 |
December | 0.607275E+09 | 0.366234E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 634368.96 | 67492735.92 |
Annual Sum or Average | 0.755301E+10 | 0.418754E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70813799.88 | 0.374416E+09 |
Minimum of Months | 0.571020E+09 | 0.321803E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 194998.85 | 1652123.41 |
Maximum of Months | 0.682301E+09 | 0.374745E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12800426.79 | 75422415.01 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.568414E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34480745.37 | 0.330378E+10 |
February | 0.901968E+09 | 0.505576E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58857426.28 | 0.207462E+10 |
March | 0.107774E+10 | 0.591200E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158341E+09 | 0.218014E+10 |
April | 0.956342E+09 | 0.521768E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529193E+09 | 0.708484E+09 |
May | 0.103597E+10 | 0.549174E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171803E+10 | 24422106.65 |
June | 0.103308E+10 | 0.541477E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204442E+10 | 22341240.46 |
July | 0.959235E+09 | 0.509968E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179328E+10 | 10826614.05 |
August | 0.107774E+10 | 0.575514E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193435E+10 | 33584064.06 |
September | 0.956342E+09 | 0.525259E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995209E+09 | 93341613.39 |
October | 0.994195E+09 | 0.554631E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100800E+10 | 0.480052E+09 |
November | 0.984487E+09 | 0.562572E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272993E+09 | 0.148270E+10 |
December | 0.959235E+09 | 0.561230E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126616E+09 | 0.265252E+10 |
Annual Sum or Average | 0.119305E+11 | 0.656678E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106738E+11 | 0.130668E+11 |
Minimum of Months | 0.901968E+09 | 0.505576E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34480745.37 | 10826614.05 |
Maximum of Months | 0.107774E+10 | 0.591200E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204442E+10 | 0.330378E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.366243E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201430.79 | 75523380.13 |
February | 0.570983E+09 | 0.324178E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398493.08 | 57410419.59 |
March | 0.682256E+09 | 0.377633E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1267569.66 | 59169607.47 |
April | 0.605404E+09 | 0.330936E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2237362.86 | 27470396.61 |
May | 0.655811E+09 | 0.347418E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10587537.49 | 4059936.14 |
June | 0.653980E+09 | 0.341494E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9407847.33 | 3664244.70 |
July | 0.607235E+09 | 0.322570E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12829392.53 | 1738621.02 |
August | 0.682256E+09 | 0.364976E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12590551.05 | 5643667.91 |
September | 0.605404E+09 | 0.335301E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11102938.67 | 8523261.15 |
October | 0.629366E+09 | 0.354388E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8952071.23 | 26366605.24 |
November | 0.623221E+09 | 0.360698E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 999115.50 | 40234736.60 |
December | 0.607235E+09 | 0.360555E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661349.38 | 68494171.24 |
Annual Sum or Average | 0.755252E+10 | 0.418639E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71235659.55 | 0.378299E+09 |
Minimum of Months | 0.570983E+09 | 0.322570E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201430.79 | 1738621.02 |
Maximum of Months | 0.682256E+09 | 0.377633E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12829392.53 | 75523380.13 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.595998E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 827335.48 | 0.160570E+09 |
February | 0.901968E+09 | 0.520249E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1203543.26 | 0.124199E+09 |
March | 0.107774E+10 | 0.598386E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3520634.98 | 0.132446E+09 |
April | 0.956342E+09 | 0.521059E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6060596.33 | 59812066.86 |
May | 0.103597E+10 | 0.544708E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24971312.79 | 10529330.71 |
June | 0.103308E+10 | 0.535151E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22838177.54 | 8018911.74 |
July | 0.959235E+09 | 0.506072E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31629945.08 | 3544752.19 |
August | 0.107774E+10 | 0.573748E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30703998.60 | 10349990.06 |
September | 0.956342E+09 | 0.527446E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28165944.78 | 16624925.52 |
October | 0.994195E+09 | 0.562529E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23355133.17 | 52722742.54 |
November | 0.984487E+09 | 0.586680E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3015489.09 | 84368511.15 |
December | 0.959235E+09 | 0.589291E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1969127.43 | 0.144407E+09 |
Annual Sum or Average | 0.119305E+11 | 0.666132E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178261E+09 | 0.807593E+09 |
Minimum of Months | 0.901968E+09 | 0.506072E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 827335.48 | 3544752.19 |
Maximum of Months | 0.107774E+10 | 0.598386E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31629945.08 | 0.160570E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.370412E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 273006.59 | 0.113318E+09 |
February | 0.421807E+09 | 0.325217E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504208.31 | 87718332.85 |
March | 0.502994E+09 | 0.375340E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1551362.03 | 92820523.70 |
April | 0.447140E+09 | 0.329116E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3541638.46 | 42620684.93 |
May | 0.484071E+09 | 0.346873E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15226540.70 | 7642269.29 |
June | 0.482240E+09 | 0.342047E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14435812.57 | 5629810.39 |
July | 0.448971E+09 | 0.322163E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19592362.33 | 2686376.44 |
August | 0.502994E+09 | 0.363599E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19317545.58 | 7272072.51 |
September | 0.447140E+09 | 0.333121E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17007594.26 | 11725316.54 |
October | 0.465148E+09 | 0.353377E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13598378.08 | 37364436.46 |
November | 0.460569E+09 | 0.366041E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401926.27 | 59883123.29 |
December | 0.448971E+09 | 0.367493E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915995.11 | 0.100599E+09 |
Annual Sum or Average | 0.557719E+10 | 0.419480E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107366E+09 | 0.569280E+09 |
Minimum of Months | 0.421807E+09 | 0.322163E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 273006.59 | 2686376.44 |
Maximum of Months | 0.502994E+09 | 0.375340E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19592362.33 | 0.113318E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.568805E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280043.21 | 0.181643E+09 |
February | 0.901968E+09 | 0.505680E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 709062.16 | 0.139617E+09 |
March | 0.107774E+10 | 0.592203E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2235751.06 | 0.139929E+09 |
April | 0.956342E+09 | 0.522576E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5536615.46 | 63040443.52 |
May | 0.103597E+10 | 0.550108E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24961642.83 | 10500069.91 |
June | 0.103308E+10 | 0.542304E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23273638.43 | 7747270.44 |
July | 0.959235E+09 | 0.510705E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31904241.56 | 3509168.06 |
August | 0.107774E+10 | 0.576305E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30163952.67 | 10570587.80 |
September | 0.956342E+09 | 0.525912E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26133693.70 | 17885296.24 |
October | 0.994195E+09 | 0.555519E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19607483.92 | 60300493.97 |
November | 0.984487E+09 | 0.563209E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1908720.10 | 95255822.33 |
December | 0.959235E+09 | 0.562017E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1242970.15 | 0.162224E+09 |
Annual Sum or Average | 0.119305E+11 | 0.657534E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167958E+09 | 0.892221E+09 |
Minimum of Months | 0.901968E+09 | 0.505680E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280043.21 | 3509168.06 |
Maximum of Months | 0.107774E+10 | 0.592203E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31904241.56 | 0.181643E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.367139E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349441.82 | 0.112887E+09 |
February | 0.570983E+09 | 0.324900E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604618.01 | 87398110.71 |
March | 0.682256E+09 | 0.378582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1981072.62 | 92025530.09 |
April | 0.605404E+09 | 0.331470E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3432432.48 | 43711398.58 |
May | 0.655811E+09 | 0.347984E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15943022.16 | 7843963.68 |
June | 0.653980E+09 | 0.342125E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14443351.00 | 6055677.89 |
July | 0.607235E+09 | 0.323101E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19761551.92 | 2884977.65 |
August | 0.682256E+09 | 0.365563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19690803.65 | 7960723.60 |
September | 0.605404E+09 | 0.335949E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17256582.23 | 12401171.33 |
October | 0.629366E+09 | 0.355043E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14068670.04 | 38753935.78 |
November | 0.623221E+09 | 0.361497E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1637583.34 | 59117559.14 |
December | 0.607235E+09 | 0.361459E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1073068.44 | 0.101096E+09 |
Annual Sum or Average | 0.755252E+10 | 0.419481E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110242E+09 | 0.572137E+09 |
Minimum of Months | 0.570983E+09 | 0.323101E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349441.82 | 2884977.65 |
Maximum of Months | 0.682256E+09 | 0.378582E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19761551.92 | 0.112887E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294599.28 | 0.240783E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692260.27 | 0.185110E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2779650.61 | 0.191182E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5735896.30 | 85389817.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27547922.20 | 11715359.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25638787.66 | 9595376.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37563225.00 | 3699262.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34733967.69 | 13124248.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30710171.40 | 22229630.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22907807.01 | 77297376.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2108941.99 | 0.126652E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410778.11 | 0.216088E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192124E+09 | 0.118287E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294599.28 | 3699262.24 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37563225.00 | 0.240783E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650283.24 | 0.287917E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241166.07 | 0.222911E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4214089.84 | 0.234523E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7544718.44 | 0.105900E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35554122.07 | 14841171.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33030220.36 | 12168677.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48681361.81 | 4648239.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45246501.76 | 15865830.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40103302.27 | 27102806.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30462097.44 | 93479030.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3161609.96 | 0.153284E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2170132.47 | 0.258583E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252060E+09 | 0.143122E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650283.24 | 4648239.13 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48681361.81 | 0.287917E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105386.31 | 0.281247E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305974.65 | 0.218350E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1666641.10 | 0.234610E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4344231.08 | 0.109921E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30446177.84 | 13632587.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29574112.11 | 10691730.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43023236.49 | 4281607.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42275090.30 | 14449962.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36791012.92 | 24381757.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23940957.13 | 89974752.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1925192.45 | 0.146123E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1186529.12 | 0.250042E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215585E+09 | 0.139770E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105386.31 | 4281607.73 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43023236.49 | 0.281247E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 856.92 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 | 16-JAN-15:00 | 339.08 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 886.73 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.82 | 20-FEB-15:00 | 461.48 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 816.37 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 | 05-MAR-12:53 | 438.10 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 839.44 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.86 | 29-APR-17:02 | 265.71 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 579.96 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.54 | 07-MAY-14:00 | 58.51 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 | 10-JUN-17:02 | 77.35 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 563.12 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.44 | 16-JUL-15:00 | 51.54 | 31-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 582.60 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.93 | 20-AUG-14:00 | 106.69 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 814.03 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.96 | 09-SEP-17:02 | 121.66 | 05-SEP-02:55 |
October | 1306.65 | 02-OCT-09:09 | 929.66 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.88 | 09-OCT-14:00 | 196.98 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 892.09 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.40 | 05-NOV-12:52 | 303.18 | 12-NOV-07:05 |
December | 1306.65 | 01-DEC-10:09 | 922.03 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 10-DEC-10:53 | 428.72 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 | 51.54 | |||||
Maximum of Months | 1306.65 | 929.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 214.88 | 461.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 508.06 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.14 | 16-JAN-15:00 | 224.80 | 21-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 539.15 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 20-FEB-15:00 | 337.65 | 05-FEB-10:00 |
March | 827.22 | 01-MAR-10:09 | 476.32 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 05-MAR-13:00 | 295.03 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 508.70 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.49 | 29-APR-17:02 | 181.52 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 357.88 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.57 | 07-MAY-13:55 | 48.59 | 14-MAY-12:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.03 | 10-JUN-17:02 | 51.84 | 06-JUN-21:20 |
July | 827.22 | 03-JUL-09:09 | 335.10 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.27 | 22-JUL-18:50 | 53.85 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 354.50 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.17 | 20-AUG-14:00 | 71.59 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 473.32 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.46 | 09-SEP-17:02 | 82.22 | 05-SEP-02:55 |
October | 827.22 | 02-OCT-09:09 | 573.77 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.86 | 09-OCT-13:56 | 133.43 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 571.12 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 05-NOV-12:52 | 238.55 | 12-NOV-08:50 |
December | 827.22 | 01-DEC-10:09 | 574.45 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 10-DEC-15:10 | 286.13 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.86 | 48.59 | |||||
Maximum of Months | 827.22 | 574.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 143.86 | 337.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 830.22 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 19-JAN-12:05 | 384.06 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 870.02 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 02-FEB-13:00 | 482.34 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 807.23 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 26-MAR-13:57 | 450.09 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 842.98 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 29-APR-17:02 | 279.87 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 584.04 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.82 | 07-MAY-13:55 | 62.54 | 14-MAY-11:55 |
June | 1306.65 | 01-JUN-09:09 | 546.69 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.69 | 10-JUN-17:02 | 77.16 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 575.11 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.26 | 22-JUL-18:50 | 52.32 | 31-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 682.40 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.34 | 20-AUG-13:57 | 107.53 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 811.29 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.72 | 09-SEP-17:10 | 124.31 | 05-SEP-02:55 |
October | 1306.65 | 02-OCT-09:09 | 922.68 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.16 | 09-OCT-13:56 | 211.61 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 865.40 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 | 07-NOV-13:00 | 335.98 | 12-NOV-10:55 |
December | 1306.65 | 01-DEC-10:09 | 912.21 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 13-DEC-14:00 | 437.14 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 546.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 52.32 | |||||
Maximum of Months | 1306.65 | 922.68 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 198.16 | 482.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 550.15 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 16-JAN-12:40 | 236.84 | 22-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 565.87 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 02-FEB-13:00 | 307.76 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 536.89 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 | 05-MAR-12:53 | 300.34 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 544.75 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 29-APR-17:08 | 199.75 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 453.34 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 | 21-MAY-14:10 | 39.69 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 362.18 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.39 | 10-JUN-17:08 | 55.59 | 06-JUN-21:20 |
July | 827.17 | 03-JUL-09:09 | 423.86 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.69 | 02-JUL-12:00 | 38.15 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 492.34 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.92 | 20-AUG-13:57 | 74.26 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 537.44 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.50 | 09-SEP-17:07 | 82.67 | 05-SEP-02:55 |
October | 827.17 | 02-OCT-09:09 | 593.49 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.67 | 09-OCT-13:54 | 137.28 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 577.13 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 11-NOV-12:00 | 204.36 | 12-NOV-07:00 |
December | 827.17 | 01-DEC-10:09 | 584.02 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 | 10-DEC-10:53 | 287.24 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 362.18 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 38.15 | |||||
Maximum of Months | 827.17 | 593.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 140.67 | 307.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 849.85 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 16-JAN-15:00 | 204.72 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 880.84 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 | 20-FEB-15:00 | 289.57 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 807.50 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.02 | 05-MAR-12:47 | 245.21 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 831.63 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 29-APR-17:02 | 140.63 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 577.01 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.52 | 21-MAY-14:00 | 23.66 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.72 | 10-JUN-17:02 | 41.02 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 559.29 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.05 | 22-JUL-18:50 | 24.50 | 31-JUL-02:30 |
August | 1306.65 | 01-AUG-09:09 | 579.75 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.54 | 20-AUG-14:00 | 61.64 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 805.11 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.41 | 09-SEP-23:00 | 58.78 | 05-SEP-03:20 |
October | 1306.65 | 02-OCT-09:09 | 925.37 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 | 09-OCT-13:50 | 123.32 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 886.16 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 05-NOV-13:00 | 177.04 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 917.54 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 10-DEC-15:10 | 265.05 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 23.66 | |||||
Maximum of Months | 1306.65 | 925.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 118.95 | 289.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 502.29 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.74 | 16-JAN-15:00 | 140.63 | 22-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 535.17 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | 20-FEB-15:00 | 205.45 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 469.83 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 05-MAR-12:50 | 168.27 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 503.49 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 29-APR-17:02 | 97.55 | 01-APR-21:00 |
May | 827.22 | 01-MAY-09:09 | 356.42 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 | 21-MAY-14:00 | 25.58 | 14-MAY-11:55 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 | 10-JUN-17:02 | 28.49 | 06-JUN-21:20 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.11 | 22-JUL-18:50 | 24.41 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 352.10 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 | 20-AUG-14:00 | 42.76 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 466.50 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 | 09-SEP-23:00 | 43.72 | 05-SEP-03:20 |
October | 827.22 | 02-OCT-09:09 | 570.93 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.36 | 09-OCT-13:44 | 84.92 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 568.41 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 05-NOV-13:00 | 137.02 | 12-NOV-08:20 |
December | 827.22 | 01-DEC-10:09 | 571.73 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 10-DEC-15:10 | 180.19 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 24.41 | |||||
Maximum of Months | 827.22 | 571.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 75.36 | 205.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 821.86 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.23 | 02-JAN-13:00 | 25075.89 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 863.32 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4442.60 | 02-FEB-13:00 | 24433.73 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 797.91 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5219.10 | 30-MAR-12:00 | 24819.20 | 09-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 835.35 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9200.34 | 28-APR-16:03 | 14788.72 | 11-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 581.32 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10113.36 | 25-MAY-16:03 | 1960.05 | 02-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 542.41 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10607.36 | 28-JUN-16:03 | 2346.48 | 07-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 572.00 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13176.58 | 21-JUL-16:02 | 1408.51 | 13-JUL-11:05 |
August | 1306.65 | 01-AUG-09:09 | 668.29 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13531.70 | 30-AUG-16:01 | 2690.72 | 29-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 802.25 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9385.31 | 06-SEP-16:03 | 4037.84 | 07-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 918.06 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9076.28 | 06-OCT-11:02 | 9821.93 | 27-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 858.31 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5428.00 | 02-NOV-11:03 | 17483.11 | 15-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 907.24 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4623.48 | 13-DEC-13:00 | 25563.65 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.41 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2497.23 | 1408.51 | |||||
Maximum of Months | 1306.65 | 918.06 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13531.70 | 25563.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 546.81 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 16-JAN-13:40 | 138.02 | 26-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 563.02 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 02-FEB-13:00 | 194.48 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 533.14 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | 05-MAR-12:43 | 169.76 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 541.26 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 29-APR-17:08 | 102.89 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 447.30 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 21-MAY-14:00 | 20.27 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 360.55 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 | 10-JUN-17:08 | 30.83 | 06-JUN-21:20 |
July | 827.17 | 03-JUL-09:09 | 369.04 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.98 | 02-JUL-12:00 | 20.35 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 486.90 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.82 | 20-AUG-14:00 | 43.99 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 533.73 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 09-SEP-23:00 | 43.60 | 05-SEP-03:20 |
October | 827.17 | 02-OCT-09:09 | 591.49 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 09-OCT-13:44 | 87.14 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 574.58 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 11-NOV-12:10 | 121.93 | 12-NOV-08:00 |
December | 827.17 | 01-DEC-10:09 | 581.73 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 10-DEC-11:50 | 181.06 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 360.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 20.27 | |||||
Maximum of Months | 827.17 | 591.49 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 194.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 856.90 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 16-JAN-14:52 | 307.14 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 886.72 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 20-FEB-15:00 | 431.32 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 816.35 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 05-MAR-12:57 | 383.75 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 839.42 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 | 29-APR-17:02 | 224.45 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 579.96 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.74 | 07-MAY-14:00 | 43.06 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.64 | 10-JUN-17:02 | 66.23 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 563.11 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 | 22-JUL-18:50 | 42.70 | 31-JUL-02:70 |
August | 1306.65 | 01-AUG-09:09 | 582.59 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.81 | 20-AUG-14:00 | 92.54 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 814.01 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.79 | 09-SEP-23:00 | 103.67 | 05-SEP-02:55 |
October | 1306.65 | 02-OCT-09:09 | 929.65 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.43 | 09-OCT-13:50 | 181.28 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 892.08 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 11-NOV-13:00 | 269.11 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 922.02 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 | 10-DEC-15:10 | 393.63 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 42.70 | |||||
Maximum of Months | 1306.65 | 929.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 179.43 | 431.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 508.06 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 16-JAN-14:52 | 203.68 | 21-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 539.14 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 | 20-FEB-15:00 | 314.87 | 05-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 476.31 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 05-MAR-13:00 | 257.82 | 20-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 508.69 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 29-APR-17:02 | 152.26 | 01-APR-18:00 |
May | 805.43 | 01-MAY-07:10 | 357.88 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 | 21-MAY-13:40 | 39.63 | 14-MAY-12:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 | 10-JUN-17:02 | 46.37 | 18-JUN-13:57 |
July | 805.43 | 03-JUL-07:10 | 335.10 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 | 22-JUL-18:50 | 50.52 | 30-JUL-11:00 |
August | 805.43 | 01-AUG-07:10 | 354.50 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.27 | 20-AUG-14:00 | 62.20 | 25-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 473.31 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.48 | 09-SEP-23:00 | 70.22 | 05-SEP-02:55 |
October | 805.43 | 02-OCT-07:10 | 573.76 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.92 | 09-OCT-13:44 | 122.49 | 29-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 571.11 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 | 05-NOV-13:00 | 211.49 | 12-NOV-08:50 |
December | 805.43 | 01-DEC-08:09 | 574.44 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 10-DEC-15:10 | 263.30 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 39.63 | |||||
Maximum of Months | 805.43 | 574.44 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 116.92 | 314.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 830.21 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 19-JAN-12:10 | 324.20 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 870.01 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 02-FEB-13:00 | 449.22 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 807.21 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 | 26-MAR-13:53 | 392.57 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 842.96 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.48 | 29-APR-17:02 | 233.50 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 584.03 | 23-MAY-07:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.09 | 21-MAY-13:40 | 43.51 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 546.68 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 10-JUN-17:02 | 66.03 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 575.11 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.41 | 22-JUL-18:50 | 44.62 | 30-JUL-11:00 |
August | 1306.65 | 01-AUG-09:09 | 682.37 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.63 | 20-AUG-14:00 | 93.24 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 811.27 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.01 | 09-SEP-23:00 | 106.23 | 05-SEP-02:55 |
October | 1306.65 | 02-OCT-09:09 | 922.67 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.27 | 09-OCT-13:58 | 192.65 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 865.38 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 07-NOV-13:00 | 298.46 | 12-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 912.20 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 | 13-DEC-14:00 | 401.97 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 546.68 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 | 43.51 | |||||
Maximum of Months | 1306.65 | 922.67 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 163.27 | 449.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 550.14 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 16-JAN-13:23 | 204.86 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 565.86 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 | 02-FEB-13:00 | 287.59 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 536.88 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 05-MAR-12:53 | 262.06 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 544.74 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 29-APR-17:08 | 166.28 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 453.33 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.54 | 21-MAY-13:40 | 34.65 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 362.17 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.29 | 10-JUN-17:08 | 47.56 | 18-JUN-13:57 |
July | 827.17 | 03-JUL-09:09 | 423.84 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 02-JUL-12:00 | 32.07 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 492.33 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.92 | 20-AUG-14:00 | 64.22 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 537.43 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.54 | 09-SEP-23:00 | 70.58 | 05-SEP-02:55 |
October | 827.17 | 02-OCT-09:09 | 593.48 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 | 09-OCT-13:44 | 125.45 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 577.13 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 | 11-NOV-12:20 | 180.97 | 12-NOV-07:05 |
December | 827.17 | 01-DEC-10:09 | 584.02 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 | 10-DEC-11:50 | 264.01 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 362.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 32.07 | |||||
Maximum of Months | 827.17 | 593.48 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 114.81 | 287.59 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.71 | 16-JAN-14:52 | 444.31 | 26-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 | 02-FEB-13:00 | 638.88 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.24 | 05-MAR-12:53 | 549.63 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.27 | 29-APR-17:02 | 316.72 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 07-MAY-14:00 | 56.91 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.00 | 10-JUN-17:02 | 86.96 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.45 | 22-JUL-18:53 | 47.77 | 31-JUL-02:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.71 | 20-AUG-14:00 | 125.62 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.10 | 09-SEP-17:02 | 122.70 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.27 | 09-OCT-14:00 | 268.43 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.10 | 05-NOV-13:00 | 382.52 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.79 | 10-DEC-14:52 | 590.25 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.71 | 47.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.71 | 638.88 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 | 16-JAN-14:52 | 554.34 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 | 20-FEB-14:55 | 776.30 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.79 | 05-MAR-13:00 | 691.78 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.08 | 29-APR-17:02 | 395.33 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.22 | 07-MAY-14:00 | 72.01 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.60 | 10-JUN-17:02 | 111.66 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.05 | 22-JUL-18:53 | 62.31 | 31-JUL-02:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.88 | 20-AUG-14:00 | 158.46 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.87 | 09-SEP-17:02 | 165.40 | 05-SEP-02:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.80 | 09-OCT-14:00 | 323.21 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 | 05-NOV-13:00 | 479.89 | 12-NOV-07:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 10-DEC-14:52 | 712.02 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 | 62.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.88 | 776.30 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 16-JAN-14:42 | 507.38 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 | 02-FEB-13:00 | 685.88 | 04-FEB-18:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.93 | 26-MAR-14:00 | 679.71 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.11 | 29-APR-17:02 | 438.98 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.80 | 07-MAY-14:00 | 148.94 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.57 | 10-JUN-17:02 | 118.70 | 18-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.93 | 02-JUL-10:53 | 124.33 | 30-JUL-10:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.24 | 20-AUG-14:00 | 152.29 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.89 | 09-SEP-22:53 | 168.95 | 05-SEP-02:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.77 | 08-OCT-13:51 | 292.60 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 28-NOV-13:00 | 452.28 | 12-NOV-07:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 | 13-DEC-14:05 | 667.77 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 | 118.70 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.89 | 685.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 37789.37 | 02-JAN-06:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35793.68 | 28-FEB-06:13 | 1905.79 | 1645.29 | 22231.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 36243.12 | 09-MAR-06:02 | 3176.32 | 1058.67 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36930.39 | 28-APR-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41325.15 | 31-MAY-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39381.40 | 20-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40698.30 | 12-JUL-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38877.96 | 01-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38557.10 | 14-SEP-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38085.00 | 24-OCT-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37037.26 | 13-NOV-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36895.43 | 18-DEC-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35793.68 | 0.00 | 846.94 | 22231.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41325.15 | 3811.58 | 2742.16 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5768.91 | 19-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.22 |
February | 6643.88 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 0.00 |
March | 6509.55 | 29-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
April | 8970.07 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 0.00 |
May | 9633.48 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 0.00 |
June | 9669.06 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
July | 10054.03 | 18-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.35 | 0.00 |
August | 9754.39 | 03-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.42 | 0.00 |
September | 9096.37 | 01-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 0.00 |
October | 9286.80 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 0.00 |
November | 7592.12 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 |
December | 6711.83 | 15-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5768.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10054.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.42 | 8.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3267.21 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.34 |
February | 2965.77 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 |
March | 3302.00 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.20 |
April | 3424.90 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 | 0.00 |
May | 4484.72 | 30-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
June | 4305.57 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 4515.00 | 10-JUL-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 0.00 |
August | 4540.32 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
September | 4702.84 | 11-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
October | 5020.37 | 10-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 0.00 |
November | 3655.58 | 06-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
December | 2881.41 | 15-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2881.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5020.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 133.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3958.18 | 02-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.93 |
February | 3420.94 | 27-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
March | 3059.48 | 09-MAR-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.18 |
April | 3722.98 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 0.00 |
May | 4622.95 | 30-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | 0.00 |
June | 4512.73 | 19-JUN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 | 0.00 |
July | 4972.87 | 05-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 0.00 |
August | 4975.33 | 28-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 | 0.00 |
September | 4948.32 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
October | 5299.54 | 10-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 0.00 |
November | 4420.83 | 06-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3649.36 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3059.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5299.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 105.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 29741.43 | 02-JAN-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14949.51 | 27-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14802.11 | 27-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20017.10 | 24-APR-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32468.48 | 31-MAY-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30030.67 | 13-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29447.20 | 11-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29932.73 | 30-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29834.63 | 06-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30077.27 | 24-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21300.87 | 06-NOV-07:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15240.74 | 15-DEC-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14802.11 | 0.00 | 1058.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32468.48 | 6035.01 | 6581.44 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16411.50 | 02-JAN-14:20 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15743.54 | 27-FEB-16:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15931.97 | 29-MAR-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18394.25 | 28-APR-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31569.46 | 08-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31897.43 | 13-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32264.61 | 11-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31854.25 | 22-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32174.72 | 06-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31797.67 | 23-OCT-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17595.59 | 06-NOV-15:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16193.65 | 15-DEC-16:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 15743.54 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32264.61 | 6198.29 | 4936.01 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4190.78 | 02-JAN-13:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 0.00 |
February | 4072.69 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 0.00 |
March | 5115.09 | 30-MAR-13:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
April | 6074.80 | 28-APR-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 | 0.00 |
May | 10872.96 | 07-MAY-15:02 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 59.93 | 0.00 |
June | 10849.84 | 11-JUN-17:32 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 64.08 | 0.00 |
July | 11104.41 | 23-JUL-13:53 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 0.00 |
August | 10989.92 | 20-AUG-15:53 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 0.00 |
September | 10976.82 | 10-SEP-15:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | 0.00 |
October | 8600.52 | 08-OCT-14:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 130.94 | 0.00 |
November | 5055.93 | 02-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
December | 4473.71 | 15-DEC-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4072.69 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 0.00 | |
Maximum of Months | 11104.41 | 1306.65 | 496.34 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 130.94 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4543.12 | 19-JAN-10:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
February | 4813.96 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
March | 7393.70 | 26-MAR-10:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
April | 11546.78 | 23-APR-11:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
May | 11786.74 | 29-MAY-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 0.00 |
June | 11671.06 | 04-JUN-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 0.00 |
July | 12245.10 | 23-JUL-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
August | 11592.78 | 27-AUG-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 0.00 |
September | 12212.74 | 10-SEP-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 | 0.00 |
October | 12103.81 | 09-OCT-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 0.00 |
November | 6404.09 | 11-NOV-09:53 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
December | 3736.12 | 16-DEC-10:10 | 522.45 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3736.12 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12245.10 | 827.22 | 314.23 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 16.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16068.27 | 01-JAN-13:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
February | 14146.62 | 26-FEB-15:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 |
March | 13335.04 | 26-MAR-15:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
April | 10412.51 | 23-APR-13:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | 0.00 |
May | 13346.28 | 07-MAY-14:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 | 0.00 |
June | 11347.31 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
July | 13425.61 | 23-JUL-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 78.27 | 0.00 |
August | 13587.01 | 27-AUG-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 | 0.00 |
September | 14195.21 | 17-SEP-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 | 0.00 |
October | 14740.46 | 09-OCT-10:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.54 | 0.00 |
November | 15011.78 | 11-NOV-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 |
December | 14971.64 | 17-DEC-14:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10412.51 | 0.00 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16068.27 | 468.72 | 223.18 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 | 226.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12904.11 | 01-JAN-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.11 |
February | 12592.56 | 26-FEB-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
March | 11847.29 | 26-MAR-15:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 |
April | 12414.59 | 23-APR-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
May | 13071.18 | 29-MAY-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 | 0.00 |
June | 13006.15 | 11-JUN-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 | 0.00 |
July | 12140.39 | 16-JUL-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 59.09 | 0.00 |
August | 12909.69 | 06-AUG-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
September | 13043.28 | 10-SEP-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 0.00 |
October | 12966.53 | 09-OCT-17:12 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
November | 12412.06 | 11-NOV-15:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 |
December | 8056.29 | 10-DEC-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8056.29 | 0.00 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13071.18 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.09 | 15.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3737.68 | 02-JAN-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
February | 3217.51 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 |
March | 3968.74 | 30-MAR-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 0.00 |
April | 4501.31 | 28-APR-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 0.00 |
May | 7380.87 | 31-MAY-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 7150.60 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
July | 7737.60 | 12-JUL-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 7900.02 | 23-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 | 0.00 |
September | 7330.75 | 11-SEP-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
October | 6819.11 | 10-OCT-06:03 | 1071.35 | 1387.43 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
November | 4666.46 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 0.00 |
December | 4104.81 | 15-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3217.51 | 0.00 | 223.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7900.02 | 2613.31 | 1387.43 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 6.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4118.27 | 19-JAN-10:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
February | 4174.79 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
March | 4425.11 | 06-MAR-10:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
April | 8822.51 | 23-APR-11:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
May | 10282.55 | 29-MAY-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 0.00 |
June | 9052.94 | 11-JUN-08:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
July | 10841.49 | 16-JUL-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 0.00 |
August | 10599.15 | 06-AUG-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
September | 10675.74 | 03-SEP-10:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 0.00 |
October | 10834.54 | 09-OCT-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
November | 5456.20 | 11-NOV-09:23 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
December | 3557.04 | 16-DEC-10:10 | 522.45 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3557.04 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10841.49 | 827.22 | 314.23 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 8.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12672.68 | 16-JAN-14:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
February | 12118.39 | 26-FEB-15:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
March | 9841.55 | 06-MAR-13:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3711.34 | 0.00 |
April | 10746.40 | 28-APR-16:10 | 1205.27 | 827.24 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8281.50 | 0.00 |
May | 10977.07 | 19-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8169.41 | 0.00 |
June | 11127.91 | 28-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8738.93 | 0.00 |
July | 11688.45 | 21-JUL-16:10 | 2410.55 | 1654.48 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11048.35 | 0.00 |
August | 12158.43 | 30-AUG-16:20 | 1607.03 | 1102.99 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10746.01 | 0.00 |
September | 12294.84 | 03-SEP-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24.10 | 0.00 |
October | 13142.45 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 | 0.00 |
November | 12907.72 | 11-NOV-14:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 |
December | 12882.19 | 17-DEC-14:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9841.55 | 267.84 | 110.30 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13142.45 | 2410.55 | 1654.48 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 11048.35 | 117.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7648.42 | 01-JAN-17:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.28 |
February | 9959.18 | 26-FEB-17:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 |
March | 5199.88 | 06-MAR-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
April | 9867.80 | 16-APR-17:33 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.60 |
May | 10862.51 | 29-MAY-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 0.00 |
June | 10811.46 | 11-JUN-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 18.69 | 0.00 |
July | 9971.44 | 16-JUL-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 | 0.00 |
August | 10866.01 | 06-AUG-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
September | 11495.89 | 03-SEP-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 |
October | 11062.03 | 09-OCT-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
November | 9633.39 | 11-NOV-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 |
December | 5865.04 | 10-DEC-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5199.88 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11495.89 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.84 | 51.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4300.33 | 02-JAN-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
February | 3854.37 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 0.00 |
March | 4810.11 | 30-MAR-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 | 0.00 |
April | 5417.02 | 26-APR-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 | 0.00 |
May | 7739.37 | 22-MAY-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
June | 7988.61 | 12-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 |
July | 9364.66 | 23-JUL-16:33 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 61.45 | 0.00 |
August | 8920.11 | 20-AUG-15:53 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 63.38 | 0.00 |
September | 8759.88 | 10-SEP-15:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | 0.00 |
October | 9321.55 | 08-OCT-14:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.07 | 0.00 |
November | 4655.40 | 01-NOV-13:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
December | 4191.19 | 11-DEC-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3854.37 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9364.66 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.07 | 14.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6444.98 | 03-JAN-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 |
February | 6044.16 | 13-FEB-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 |
March | 7555.58 | 26-MAR-10:23 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
April | 11743.77 | 23-APR-09:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
May | 12475.11 | 29-MAY-08:41 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
June | 11209.80 | 11-JUN-08:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 |
July | 11981.15 | 16-JUL-09:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 | 0.00 |
August | 11522.28 | 06-AUG-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
September | 12056.43 | 03-SEP-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 0.00 |
October | 11917.34 | 09-OCT-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 | 0.00 |
November | 7346.35 | 11-NOV-09:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
December | 5601.75 | 26-DEC-13:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5601.75 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12475.11 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 | 42.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13033.98 | 01-JAN-13:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 |
February | 13105.45 | 26-FEB-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
March | 11600.72 | 05-MAR-13:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 | 0.00 |
April | 9308.72 | 23-APR-14:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 0.00 |
May | 9592.52 | 08-MAY-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.07 |
June | 9362.91 | 05-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
July | 10894.66 | 23-JUL-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 67.69 | 0.00 |
August | 11864.85 | 27-AUG-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 | 0.00 |
September | 12497.08 | 17-SEP-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 35.59 | 0.00 |
October | 13477.46 | 09-OCT-11:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 0.00 |
November | 12799.57 | 05-NOV-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
December | 13302.13 | 17-DEC-14:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9308.72 | 0.00 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13477.46 | 401.76 | 223.18 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 | 188.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8462.19 | 01-JAN-17:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
February | 11500.44 | 26-FEB-17:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 |
March | 10280.64 | 26-MAR-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
April | 11977.44 | 23-APR-17:42 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 |
May | 12039.55 | 29-MAY-16:41 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 0.00 |
June | 11855.59 | 11-JUN-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 0.00 |
July | 11865.19 | 30-JUL-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
August | 11721.95 | 06-AUG-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 |
September | 12574.08 | 03-SEP-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
October | 12099.83 | 08-OCT-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.55 | 0.00 |
November | 10549.92 | 05-NOV-15:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
December | 7261.31 | 10-DEC-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7261.31 | 0.00 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12574.08 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 53.55 | 19.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.111898E+12 | 115521.37 | 19-JAN-15:09 | 0.00 | 0.00 |
February | 0.105250E+12 | 123586.93 | 06-FEB-07:10 | 0.00 | 0.00 |
March | 0.121826E+12 | 115246.05 | 07-MAR-11:30 | 0.00 | 0.00 |
April | 0.125176E+12 | 139973.02 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.159626E+12 | 139841.81 | 30-MAY-10:00 | 0.00 | 0.00 |
June | 0.162990E+12 | 144857.17 | 28-JUN-14:30 | 0.00 | 0.00 |
July | 0.163466E+12 | 151326.70 | 21-JUL-15:50 | 0.00 | 0.00 |
August | 0.172431E+12 | 152167.90 | 30-AUG-15:00 | 0.00 | 0.00 |
September | 0.151730E+12 | 144162.82 | 06-SEP-15:00 | 0.00 | 0.00 |
October | 0.150025E+12 | 147953.02 | 05-OCT-14:00 | 0.00 | 0.00 |
November | 0.121876E+12 | 134055.21 | 02-NOV-15:09 | 0.00 | 0.00 |
December | 0.115276E+12 | 122836.94 | 15-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.166157E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.105250E+12 | 115246.05 | 0.00 | 0.00 | |
Maximum of Months | 0.172431E+12 | 152167.90 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.196152E+11 | 0.517597E+10 | 0.605851E+11 | 0.225724E+10 | 0.408474E+10 | 12379742.02 | 0.377563E+10 | 0.124229E+11 | 0.00 | 0.00 | 0.00 | 0.396884E+10 | 0.00 |
February | 0.176459E+11 | 0.433555E+10 | 0.548702E+11 | 0.204814E+10 | 0.397983E+10 | 11196021.66 | 0.190286E+10 | 0.168773E+11 | 0.00 | 0.00 | 0.00 | 0.357883E+10 | 0.00 |
March | 0.208452E+11 | 0.438227E+10 | 0.627783E+11 | 0.235486E+10 | 0.470078E+10 | 12675672.10 | 0.212018E+10 | 0.205608E+11 | 0.00 | 0.00 | 0.00 | 0.407109E+10 | 0.00 |
April | 0.185035E+11 | 0.384887E+10 | 0.586172E+11 | 0.219182E+10 | 0.553767E+10 | 11960507.72 | 0.153446E+09 | 0.328399E+11 | 0.00 | 0.00 | 0.00 | 0.347153E+10 | 0.00 |
May | 0.198307E+11 | 0.360887E+10 | 0.616817E+11 | 0.230570E+10 | 0.885395E+10 | 12527707.06 | 0.00 | 0.598547E+11 | 0.00 | 0.00 | 0.00 | 0.347771E+10 | 0.00 |
June | 0.196837E+11 | 0.330914E+10 | 0.604966E+11 | 0.226793E+10 | 0.941766E+10 | 12231776.97 | 0.00 | 0.645486E+11 | 0.00 | 0.00 | 0.00 | 0.325430E+10 | 0.00 |
July | 0.184401E+11 | 0.354970E+10 | 0.597911E+11 | 0.222873E+10 | 0.940380E+10 | 12256437.81 | 0.00 | 0.670428E+11 | 0.00 | 0.00 | 0.00 | 0.299747E+10 | 0.00 |
August | 0.206508E+11 | 0.382930E+10 | 0.627783E+11 | 0.235469E+10 | 0.102512E+11 | 12675672.10 | 0.00 | 0.692306E+11 | 0.00 | 0.00 | 0.00 | 0.332338E+10 | 0.00 |
September | 0.185579E+11 | 0.405484E+10 | 0.585950E+11 | 0.219061E+10 | 0.837384E+10 | 11960507.72 | 0.00 | 0.567988E+11 | 0.00 | 0.00 | 0.00 | 0.314702E+10 | 0.00 |
October | 0.193888E+11 | 0.459822E+10 | 0.605962E+11 | 0.225776E+10 | 0.876467E+10 | 12379742.02 | 23187998.46 | 0.509199E+11 | 0.00 | 0.00 | 0.00 | 0.346408E+10 | 0.00 |
November | 0.193820E+11 | 0.487649E+10 | 0.591197E+11 | 0.219991E+10 | 0.554242E+10 | 12059151.09 | 0.258613E+09 | 0.268562E+11 | 0.00 | 0.00 | 0.00 | 0.362875E+10 | 0.00 |
December | 0.190916E+11 | 0.528855E+10 | 0.597800E+11 | 0.222853E+10 | 0.451519E+10 | 12256437.81 | 0.268895E+10 | 0.178912E+11 | 0.00 | 0.00 | 0.00 | 0.377951E+10 | 0.00 |
Annual Sum or Average | 0.231635E+12 | 0.508578E+11 | 0.719689E+12 | 0.268859E+11 | 0.834257E+11 | 0.146559E+09 | 0.109229E+11 | 0.495844E+12 | 0.00 | 0.00 | 0.00 | 0.421625E+11 | 0.00 |
Minimum of Months | 0.176459E+11 | 0.330914E+10 | 0.548702E+11 | 0.204814E+10 | 0.397983E+10 | 11196021.66 | 0.00 | 0.124229E+11 | 0.00 | 0.00 | 0.00 | 0.299747E+10 | 0.00 |
Maximum of Months | 0.208452E+11 | 0.528855E+10 | 0.627783E+11 | 0.235486E+10 | 0.102512E+11 | 12675672.10 | 0.377563E+10 | 0.692306E+11 | 0.00 | 0.00 | 0.00 | 0.407109E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23018.27 | 31-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 8546.29 | 19-JAN-15:30 | 6.85 | 03-JAN-12:09 | 72087.45 | 10-JAN-07:10 |
February | 23373.90 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:09 | 9606.59 | 27-FEB-15:39 | 6.85 | 03-FEB-12:09 | 81172.69 | 06-FEB-07:10 |
March | 22690.00 | 27-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 02-MAR-17:10 | 7777.45 | 06-MAR-15:30 | 6.85 | 13-MAR-06:10 | 59763.12 | 13-MAR-06:10 |
April | 22991.44 | 14-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 11-APR-07:10 | 11117.63 | 28-APR-15:20 | 6.85 | 01-APR-05:10 | 9161.76 | 11-APR-06:10 |
May | 20679.15 | 23-MAY-07:30 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 12057.73 | 30-MAY-10:00 | 6.85 | 29-MAY-16:10 | 0.00 | 01-MAY-00:10 |
June | 19960.43 | 16-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 02-JUN-12:09 | 13070.03 | 12-JUN-15:00 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 20416.95 | 14-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 18-JUL-12:09 | 13715.17 | 05-JUL-14:30 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 21057.46 | 21-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-12:09 | 14507.02 | 30-AUG-15:00 | 6.85 | 30-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 22687.77 | 26-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-11:09 | 14040.97 | 11-SEP-14:30 | 6.85 | 10-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 23853.05 | 25-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-11:09 | 15400.01 | 10-OCT-14:09 | 6.85 | 01-OCT-05:10 | 3937.46 | 27-OCT-06:00 |
November | 23371.10 | 21-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 15-NOV-13:09 | 12287.10 | 06-NOV-15:30 | 6.85 | 15-NOV-17:10 | 17852.76 | 16-NOV-07:10 |
December | 23771.66 | 12-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 05-DEC-08:09 | 10138.81 | 15-DEC-15:30 | 6.85 | 04-DEC-07:10 | 80203.03 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19960.43 | 5686.19 | 41699.26 | 1410.29 | 7777.45 | 6.85 | 0.00 | |||||||
Maximum of Months | 23853.05 | 5686.19 | 41699.26 | 1410.29 | 15400.01 | 6.85 | 81172.69 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 41206.28 | 19-JAN-15:09 | 0.00 | 0.00 | 0.00 | 5355.49 | 23-JAN-12:39 | 0.00 |
February | 41411.98 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 5351.01 | 03-FEB-12:30 | 0.00 |
March | 43244.42 | 30-MAR-12:00 | 0.00 | 0.00 | 0.00 | 5056.31 | 01-MAR-12:20 | 0.00 |
April | 62840.00 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 4958.62 | 03-APR-11:20 | 0.00 |
May | 63586.87 | 30-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4594.07 | 01-MAY-11:00 | 0.00 |
June | 68510.26 | 28-JUN-14:09 | 0.00 | 0.00 | 0.00 | 4236.54 | 01-JUN-11:39 | 0.00 |
July | 73126.79 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 4201.94 | 05-JUL-11:30 | 0.00 |
August | 72141.69 | 03-AUG-15:50 | 0.00 | 0.00 | 0.00 | 4217.20 | 31-AUG-11:20 | 0.00 |
September | 65104.54 | 06-SEP-15:00 | 0.00 | 0.00 | 0.00 | 4362.50 | 27-SEP-11:50 | 0.00 |
October | 69241.22 | 06-OCT-10:00 | 0.00 | 0.00 | 0.00 | 4622.61 | 31-OCT-11:30 | 0.00 |
November | 56749.57 | 02-NOV-14:30 | 0.00 | 0.00 | 0.00 | 4989.71 | 30-NOV-12:30 | 0.00 |
December | 47205.13 | 15-DEC-15:09 | 0.00 | 0.00 | 0.00 | 5343.26 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 41206.28 | 0.00 | 0.00 | 0.00 | 4201.94 | 0.00 | ||
Maximum of Months | 73126.79 | 0.00 | 0.00 | 0.00 | 5355.49 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 115521.37 | 19-JAN-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 8382.35 | 6.85 | 0.00 | 41206.28 | 0.00 |
February | 123586.93 | 06-FEB-07:10 | 8334.71 | 22496.85 | 5686.19 | 974.52 | 3169.05 | 6.85 | 81172.69 | 91.77 | 0.00 |
March | 115246.05 | 07-MAR-11:30 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 7015.45 | 6.85 | 0.00 | 41437.15 | 0.00 |
April | 139973.02 | 28-APR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 10837.45 | 6.85 | 0.00 | 62840.00 | 0.00 |
May | 139841.81 | 30-MAY-10:00 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 12057.73 | 6.85 | 0.00 | 61499.45 | 0.00 |
June | 144857.17 | 28-JUN-14:30 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 11515.56 | 6.85 | 0.00 | 68336.49 | 0.00 |
July | 151326.70 | 21-JUL-15:50 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 12487.85 | 6.85 | 0.00 | 72892.47 | 0.00 |
August | 152167.90 | 30-AUG-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 14507.02 | 6.85 | 0.00 | 71703.39 | 0.00 |
September | 144162.82 | 06-SEP-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13096.29 | 6.85 | 0.00 | 65104.54 | 0.00 |
October | 147953.02 | 05-OCT-14:00 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14387.24 | 6.85 | 0.00 | 68258.58 | 0.00 |
November | 134055.21 | 02-NOV-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 11445.45 | 6.85 | 0.00 | 56311.08 | 0.00 |
December | 122836.94 | 15-DEC-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 9997.07 | 6.85 | 0.00 | 47205.13 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 115246.05 | 8334.71 | 22496.85 | 0.00 | 974.52 | 3169.05 | 6.85 | 0.00 | 91.77 | 0.00 | |
Maximum of Months | 152167.90 | 19671.42 | 41670.51 | 5686.19 | 1410.29 | 14507.02 | 6.85 | 81172.69 | 72892.47 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.24 | 0.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 2.50 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.46 | 2.00 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.41 | 4.83 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.38 | 2.67 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.50 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.39 | 1.17 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.24 | 0.17 | 19.24 | 18.50 | 27.28 | 14.67 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.24 | 0.17 | 19.24 | 6.17 | 27.58 | 4.83 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.21 | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.73 | 2.00 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.86 | 9.17 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.70 | 7.67 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.72 | 13.17 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.66 | 7.83 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.76 | 11.67 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.66 | 7.17 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.21 | 0.17 | 19.21 | 65.17 | 27.69 | 59.67 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.21 | 0.17 | 19.21 | 14.67 | 27.86 | 13.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.90 | 4.50 | 27.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.83 | 1.67 | 27.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 2.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.50 | 3.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.43 | 2.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.41 | 5.50 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.52 | 5.00 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.84 | 8.17 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.99 | 9.67 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.77 | 7.50 | 27.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.94 | 5.00 | 27.94 |
Annual Sum or Average | 0.00 | 0.00 | 60.50 | 27.74 | 56.17 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 1.17 | 27.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.99 | 9.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.72 | 0.83 | 27.72 |
February | 0.17 | 19.28 | 0.17 | 19.28 | 0.67 | 25.03 | 0.67 | 26.18 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.67 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.83 | 2.50 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.06 | 4.00 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.95 | 4.00 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.74 | 7.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 4.17 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.98 | 6.17 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.93 | 5.33 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.63 | 1.50 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.57 | 1.00 | 27.57 |
Annual Sum or Average | 0.17 | 19.28 | 0.17 | 19.28 | 57.83 | 27.81 | 39.33 | 27.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.03 | 0.67 | 26.18 |
Maximum of Months | 0.17 | 19.28 | 0.17 | 19.28 | 12.00 | 28.06 | 7.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.66 | 0.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.65 | 6.17 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 3.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.55 | 8.50 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.50 | 6.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.60 | 10.00 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.54 | 5.83 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 41.50 | 27.57 | 40.83 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.66 | 10.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 18.13 | 17.50 | 18.13 | 5.33 | 19.40 | 5.17 | 20.35 |
February | 9.00 | 18.32 | 9.00 | 18.32 | 2.17 | 19.24 | 2.17 | 19.98 |
March | 14.67 | 18.59 | 14.67 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
April | 2.33 | 19.65 | 2.33 | 19.65 | 2.67 | 21.55 | 2.67 | 22.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 24.93 | 26.00 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 24.99 | 31.33 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 25.36 | 26.50 | 25.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 25.48 | 34.17 | 25.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 26.02 | 20.33 | 26.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 25.66 | 50.17 | 25.64 |
November | 4.17 | 19.68 | 4.17 | 19.68 | 22.00 | 24.26 | 21.67 | 24.97 |
December | 17.50 | 18.83 | 17.50 | 18.83 | 7.50 | 20.30 | 7.50 | 21.33 |
Annual Sum or Average | 65.17 | 18.60 | 65.17 | 18.60 | 229.50 | 23.06 | 227.67 | 24.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 0.00 | 18.59 |
Maximum of Months | 17.50 | 19.68 | 17.50 | 19.68 | 51.00 | 26.02 | 50.17 | 26.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.51 | 0.50 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.60 | 1.17 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.75 | 2.33 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.71 | 2.33 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.50 | 4.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.55 | 3.17 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.76 | 4.50 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.73 | 4.50 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.17 | 27.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
Annual Sum or Average | 0.00 | 0.00 | 37.00 | 27.64 | 25.50 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.76 | 4.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 27.33 | 1.67 | 27.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.46 | 1.00 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.81 | 1.50 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.78 | 8.67 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.57 | 7.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.65 | 10.33 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.56 | 6.33 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.70 | 9.50 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.62 | 6.33 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53.17 | 27.65 | 52.33 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.81 | 10.33 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.86 | 4.83 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.65 | 2.17 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.47 | 1.50 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.37 | 2.67 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.71 | 7.17 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.86 | 9.83 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.80 | 11.67 | 26.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.88 | 5.50 | 27.88 |
Annual Sum or Average | 0.00 | 0.00 | 47.00 | 27.52 | 46.17 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.88 | 11.67 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.67 | 27.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.68 | 0.67 | 27.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.51 | 1.33 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 2.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.95 | 3.00 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 3.17 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.63 | 5.83 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.60 | 3.50 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.95 | 4.33 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.85 | 4.67 | 27.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.51 | 1.50 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.46 | 1.00 | 27.46 |
Annual Sum or Average | 0.00 | 0.00 | 45.00 | 27.76 | 32.00 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.95 | 5.83 | 27.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 98.50 | 23.93 | 163.67 | 24.41 | 0.00 | 24.41 |
February | 79.67 | 23.93 | 229.17 | 24.36 | 0.00 | 24.36 |
March | 67.17 | 23.89 | 248.33 | 24.42 | 0.00 | 24.42 |
April | 0.00 | 0.00 | 391.50 | 24.59 | 0.00 | 24.59 |
May | 0.00 | 0.00 | 508.00 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 496.00 | 24.41 | 0.00 | 24.41 |
July | 0.00 | 0.00 | 497.00 | 24.46 | 0.00 | 24.46 |
August | 0.00 | 0.00 | 514.00 | 24.42 | 0.00 | 24.42 |
September | 0.00 | 0.00 | 484.67 | 24.43 | 0.00 | 24.43 |
October | 0.00 | 0.00 | 449.33 | 24.55 | 0.00 | 24.55 |
November | 2.00 | 24.00 | 327.17 | 24.60 | 0.00 | 24.60 |
December | 75.83 | 23.92 | 236.17 | 24.48 | 0.00 | 24.48 |
Annual Sum or Average | 323.17 | 23.92 | 4545.00 | 24.46 | 0.00 | 24.46 |
Minimum of Months | 0.00 | 0.00 | 163.67 | 24.36 | 0.00 | 24.36 |
Maximum of Months | 98.50 | 24.00 | 514.00 | 24.60 | 0.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 375.50 | 23.04 | 73.33 | 23.25 | 0.00 | 23.25 |
February | 250.33 | 23.06 | 104.50 | 23.40 | 0.00 | 23.40 |
March | 255.00 | 23.15 | 127.17 | 23.54 | 0.00 | 23.54 |
April | 63.50 | 23.53 | 240.00 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 478.33 | 24.30 | 0.00 | 24.30 |
June | 0.00 | 0.00 | 468.50 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 469.67 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 492.33 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 433.83 | 24.30 | 0.00 | 24.30 |
October | 26.33 | 23.40 | 387.67 | 24.30 | 0.00 | 24.30 |
November | 144.50 | 23.45 | 158.67 | 23.91 | 0.00 | 23.91 |
December | 274.33 | 23.09 | 93.67 | 23.40 | 0.00 | 23.40 |
Annual Sum or Average | 1389.50 | 23.14 | 3527.67 | 23.98 | 0.00 | 23.98 |
Minimum of Months | 0.00 | 0.00 | 73.33 | 23.25 | 0.00 | 23.25 |
Maximum of Months | 375.50 | 23.53 | 492.33 | 24.31 | 0.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.67 | 22.29 | 60.50 | 22.48 | 9.67 | 22.44 |
February | 319.67 | 22.53 | 82.83 | 22.73 | 13.67 | 22.65 |
March | 312.17 | 22.80 | 105.33 | 23.10 | 6.17 | 23.06 |
April | 116.50 | 23.36 | 224.17 | 24.00 | 0.00 | 24.00 |
May | 0.00 | 0.00 | 472.00 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 467.67 | 24.29 | 0.00 | 24.29 |
July | 0.00 | 0.00 | 476.33 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 490.17 | 24.30 | 0.00 | 24.30 |
September | 0.00 | 0.00 | 425.67 | 24.33 | 0.00 | 24.33 |
October | 57.33 | 23.27 | 364.33 | 24.21 | 0.00 | 24.21 |
November | 244.00 | 23.12 | 112.00 | 23.45 | 0.00 | 23.45 |
December | 349.67 | 22.51 | 74.50 | 22.75 | 6.33 | 22.72 |
Annual Sum or Average | 1804.00 | 22.68 | 3355.50 | 23.71 | 35.83 | 23.69 |
Minimum of Months | 0.00 | 0.00 | 60.50 | 22.48 | 0.00 | 22.44 |
Maximum of Months | 404.67 | 23.36 | 490.17 | 24.35 | 13.67 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 435.17 | 21.62 | 128.67 | 21.64 | 85.83 | 21.48 |
February | 351.83 | 21.90 | 115.00 | 21.95 | 53.67 | 21.75 |
March | 342.83 | 22.24 | 140.00 | 22.51 | 35.83 | 22.35 |
April | 156.67 | 23.16 | 229.83 | 23.83 | 10.00 | 23.88 |
May | 19.17 | 26.37 | 502.50 | 24.50 | 19.17 | 24.56 |
June | 11.67 | 26.36 | 490.83 | 24.46 | 10.50 | 24.51 |
July | 31.17 | 26.60 | 489.67 | 24.67 | 31.17 | 24.78 |
August | 23.83 | 26.22 | 507.00 | 24.48 | 23.83 | 24.55 |
September | 24.67 | 25.81 | 445.33 | 24.51 | 22.67 | 24.58 |
October | 104.17 | 23.65 | 376.17 | 24.24 | 26.17 | 24.32 |
November | 293.50 | 22.52 | 124.83 | 22.96 | 6.00 | 22.93 |
December | 384.33 | 21.87 | 119.83 | 22.04 | 53.33 | 21.92 |
Annual Sum or Average | 2179.00 | 22.37 | 3669.67 | 23.48 | 378.17 | 23.42 |
Minimum of Months | 11.67 | 21.62 | 115.00 | 21.64 | 6.00 | 21.48 |
Maximum of Months | 435.17 | 26.60 | 507.00 | 24.67 | 85.83 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 388.83 | 22.11 | 118.33 | 22.28 | 46.67 | 22.11 |
February | 285.17 | 22.25 | 137.50 | 22.54 | 36.00 | 22.36 |
March | 250.00 | 22.37 | 192.17 | 23.02 | 28.00 | 22.89 |
April | 109.50 | 23.49 | 307.33 | 24.18 | 16.33 | 24.26 |
May | 48.83 | 26.75 | 506.83 | 24.70 | 48.83 | 24.87 |
June | 35.00 | 26.79 | 492.67 | 24.62 | 34.33 | 24.76 |
July | 65.83 | 26.81 | 492.33 | 24.87 | 65.83 | 25.08 |
August | 46.67 | 26.56 | 509.67 | 24.63 | 46.67 | 24.78 |
September | 58.83 | 26.61 | 462.50 | 24.75 | 58.33 | 24.94 |
October | 105.83 | 24.57 | 398.17 | 24.53 | 47.50 | 24.70 |
November | 211.50 | 22.85 | 184.33 | 23.55 | 5.17 | 23.54 |
December | 337.00 | 22.20 | 141.50 | 22.54 | 38.33 | 22.42 |
Annual Sum or Average | 1943.00 | 23.08 | 3943.33 | 23.91 | 472.00 | 23.97 |
Minimum of Months | 35.00 | 22.11 | 118.33 | 22.28 | 5.17 | 22.11 |
Maximum of Months | 388.83 | 26.81 | 509.67 | 24.87 | 65.83 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.67 | 22.25 | 164.67 | 22.84 | 50.83 | 22.76 |
February | 221.50 | 22.37 | 179.33 | 23.06 | 28.33 | 22.95 |
March | 253.17 | 22.36 | 191.33 | 22.99 | 29.50 | 22.88 |
April | 135.50 | 23.25 | 266.17 | 24.02 | 12.00 | 24.08 |
May | 25.00 | 26.45 | 497.17 | 24.52 | 25.00 | 24.61 |
June | 12.50 | 26.22 | 487.50 | 24.45 | 10.83 | 24.49 |
July | 34.00 | 26.57 | 487.83 | 24.67 | 34.00 | 24.78 |
August | 31.83 | 26.37 | 507.00 | 24.53 | 31.83 | 24.63 |
September | 46.33 | 26.48 | 454.50 | 24.68 | 45.50 | 24.84 |
October | 95.17 | 25.01 | 417.00 | 24.65 | 54.67 | 24.84 |
November | 173.00 | 23.27 | 261.83 | 24.07 | 21.50 | 24.19 |
December | 246.67 | 22.46 | 219.00 | 23.28 | 44.67 | 23.26 |
Annual Sum or Average | 1544.33 | 23.10 | 4133.33 | 24.03 | 388.67 | 24.08 |
Minimum of Months | 12.50 | 22.25 | 164.67 | 22.84 | 10.83 | 22.76 |
Maximum of Months | 269.67 | 26.57 | 507.00 | 24.68 | 54.67 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.50 | 21.83 | 136.00 | 22.03 | 66.17 | 21.87 |
February | 287.50 | 22.05 | 144.67 | 22.41 | 41.67 | 22.22 |
March | 283.17 | 22.31 | 181.00 | 22.82 | 36.67 | 22.70 |
April | 138.00 | 23.55 | 283.17 | 24.15 | 22.17 | 24.26 |
May | 31.67 | 26.58 | 501.50 | 24.59 | 31.67 | 24.70 |
June | 23.67 | 26.69 | 490.67 | 24.56 | 22.50 | 24.66 |
July | 49.50 | 26.71 | 491.50 | 24.78 | 49.50 | 24.94 |
August | 33.50 | 26.42 | 510.67 | 24.57 | 33.50 | 24.67 |
September | 44.67 | 26.35 | 458.17 | 24.66 | 43.67 | 24.80 |
October | 93.33 | 24.36 | 400.83 | 24.46 | 41.67 | 24.60 |
November | 238.00 | 22.68 | 180.33 | 23.39 | 9.00 | 23.41 |
December | 323.67 | 21.99 | 161.67 | 22.47 | 46.83 | 22.36 |
Annual Sum or Average | 1913.17 | 22.76 | 3940.17 | 23.78 | 445.00 | 23.80 |
Minimum of Months | 23.67 | 21.83 | 136.00 | 22.03 | 9.00 | 21.87 |
Maximum of Months | 366.50 | 26.71 | 510.67 | 24.78 | 66.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 415.00 | 22.15 | 48.83 | 22.31 | 5.83 | 22.28 |
February | 349.83 | 22.32 | 70.67 | 22.46 | 16.50 | 22.38 |
March | 368.83 | 22.53 | 80.67 | 22.75 | 7.83 | 22.71 |
April | 183.00 | 23.33 | 196.33 | 23.79 | 8.17 | 23.83 |
May | 10.33 | 26.20 | 493.33 | 24.38 | 10.33 | 24.41 |
June | 1.33 | 26.17 | 487.83 | 24.35 | 1.33 | 24.36 |
July | 4.83 | 26.34 | 493.67 | 24.49 | 4.83 | 24.51 |
August | 0.17 | 26.68 | 513.83 | 24.40 | 0.17 | 24.40 |
September | 2.67 | 25.92 | 482.17 | 24.42 | 2.67 | 24.42 |
October | 46.67 | 23.90 | 405.33 | 24.36 | 8.17 | 24.39 |
November | 227.00 | 23.21 | 173.00 | 23.63 | 0.00 | 23.63 |
December | 339.67 | 22.49 | 90.00 | 22.83 | 3.17 | 22.82 |
Annual Sum or Average | 1949.33 | 22.63 | 3535.67 | 23.72 | 69.00 | 23.71 |
Minimum of Months | 0.17 | 22.15 | 48.83 | 22.31 | 0.00 | 22.28 |
Maximum of Months | 415.00 | 26.68 | 513.83 | 24.49 | 16.50 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 327.83 | 22.80 | 94.67 | 23.15 | 1.83 | 23.14 |
February | 244.17 | 22.80 | 118.33 | 23.22 | 4.83 | 23.18 |
March | 234.50 | 22.76 | 172.83 | 23.43 | 2.83 | 23.41 |
April | 88.83 | 23.63 | 311.33 | 24.24 | 11.33 | 24.28 |
May | 30.33 | 26.80 | 506.17 | 24.62 | 30.33 | 24.73 |
June | 11.50 | 26.91 | 494.17 | 24.51 | 11.50 | 24.56 |
July | 33.17 | 26.92 | 495.50 | 24.75 | 33.17 | 24.88 |
August | 19.83 | 27.00 | 514.00 | 24.58 | 19.83 | 24.67 |
September | 33.17 | 26.92 | 484.83 | 24.69 | 33.17 | 24.83 |
October | 51.67 | 25.58 | 430.50 | 24.67 | 32.33 | 24.80 |
November | 100.50 | 23.44 | 262.33 | 24.16 | 0.50 | 24.16 |
December | 248.67 | 22.80 | 158.00 | 23.39 | 4.83 | 23.39 |
Annual Sum or Average | 1424.17 | 23.36 | 4042.67 | 24.18 | 186.50 | 24.26 |
Minimum of Months | 11.50 | 22.76 | 94.67 | 23.15 | 0.50 | 23.14 |
Maximum of Months | 327.83 | 27.00 | 514.00 | 24.75 | 33.17 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.83 | 22.32 | 183.50 | 23.10 | 41.17 | 23.04 |
February | 204.83 | 22.37 | 199.50 | 23.28 | 23.33 | 23.21 |
March | 284.67 | 22.14 | 191.67 | 22.83 | 38.17 | 22.74 |
April | 174.67 | 23.14 | 269.67 | 23.85 | 46.50 | 23.86 |
May | 109.00 | 24.32 | 501.67 | 24.38 | 109.00 | 24.37 |
June | 102.50 | 24.25 | 493.00 | 24.37 | 102.50 | 24.35 |
July | 124.83 | 24.40 | 494.67 | 24.52 | 124.83 | 24.50 |
August | 116.67 | 24.46 | 514.00 | 24.52 | 116.67 | 24.51 |
September | 121.67 | 24.73 | 485.00 | 24.59 | 121.67 | 24.61 |
October | 119.50 | 25.00 | 450.17 | 24.81 | 96.83 | 24.91 |
November | 117.00 | 23.72 | 342.50 | 24.42 | 50.33 | 24.51 |
December | 229.83 | 22.62 | 262.67 | 23.60 | 58.00 | 23.60 |
Annual Sum or Average | 1962.00 | 23.28 | 4388.00 | 24.10 | 929.00 | 24.12 |
Minimum of Months | 102.50 | 22.14 | 183.50 | 22.83 | 23.33 | 22.74 |
Maximum of Months | 284.67 | 25.00 | 514.00 | 24.81 | 124.83 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 318.33 | 22.56 | 103.00 | 23.00 | 3.00 | 22.99 |
February | 245.83 | 22.63 | 137.83 | 23.13 | 11.00 | 23.07 |
March | 252.33 | 22.68 | 155.17 | 23.26 | 5.00 | 23.22 |
April | 97.17 | 23.72 | 291.50 | 24.25 | 12.33 | 24.31 |
May | 17.17 | 26.60 | 505.50 | 24.50 | 17.17 | 24.56 |
June | 11.67 | 26.85 | 491.00 | 24.49 | 11.67 | 24.55 |
July | 20.00 | 26.85 | 494.33 | 24.66 | 20.00 | 24.74 |
August | 11.00 | 26.97 | 514.00 | 24.54 | 11.00 | 24.59 |
September | 22.00 | 26.86 | 484.67 | 24.62 | 22.00 | 24.72 |
October | 44.17 | 25.35 | 438.00 | 24.62 | 25.00 | 24.72 |
November | 126.67 | 23.44 | 248.50 | 24.06 | 1.17 | 24.07 |
December | 255.83 | 22.80 | 171.33 | 23.44 | 4.50 | 23.45 |
Annual Sum or Average | 1422.17 | 23.13 | 4034.83 | 24.10 | 143.83 | 24.15 |
Minimum of Months | 11.00 | 22.56 | 103.00 | 23.00 | 1.17 | 22.99 |
Maximum of Months | 318.33 | 26.97 | 514.00 | 24.66 | 25.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.67 | 21.97 | 78.33 | 22.16 | 21.33 | 22.09 |
February | 322.17 | 22.27 | 95.17 | 22.44 | 25.00 | 22.31 |
March | 311.67 | 22.55 | 124.83 | 22.90 | 12.17 | 22.83 |
April | 123.33 | 23.50 | 254.00 | 24.03 | 9.83 | 24.07 |
May | 10.33 | 26.21 | 507.83 | 24.45 | 10.33 | 24.48 |
June | 3.00 | 26.38 | 494.00 | 24.41 | 3.00 | 24.42 |
July | 13.67 | 26.31 | 494.67 | 24.56 | 13.67 | 24.60 |
August | 10.83 | 25.95 | 511.00 | 24.42 | 10.83 | 24.45 |
September | 12.00 | 25.82 | 466.67 | 24.44 | 12.00 | 24.48 |
October | 74.00 | 23.80 | 389.33 | 24.31 | 17.50 | 24.36 |
November | 249.50 | 22.95 | 148.33 | 23.40 | 0.17 | 23.40 |
December | 355.17 | 22.28 | 96.67 | 22.56 | 19.00 | 22.51 |
Annual Sum or Average | 1894.33 | 22.58 | 3660.83 | 23.71 | 154.83 | 23.70 |
Minimum of Months | 3.00 | 21.97 | 78.33 | 22.16 | 0.17 | 22.09 |
Maximum of Months | 408.67 | 26.38 | 511.00 | 24.56 | 25.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 307.00 | 22.40 | 79.50 | 22.70 | 15.17 | 22.62 |
February | 222.33 | 22.57 | 103.83 | 23.01 | 9.33 | 22.93 |
March | 201.50 | 22.67 | 153.67 | 23.38 | 10.00 | 23.35 |
April | 76.00 | 23.87 | 262.67 | 24.39 | 15.17 | 24.48 |
May | 41.50 | 26.83 | 430.00 | 24.80 | 41.50 | 24.96 |
June | 22.67 | 26.93 | 417.00 | 24.68 | 22.67 | 24.79 |
July | 51.50 | 26.83 | 421.50 | 24.94 | 51.50 | 25.12 |
August | 35.17 | 26.65 | 432.00 | 24.70 | 35.17 | 24.83 |
September | 46.17 | 26.71 | 401.67 | 24.82 | 46.17 | 25.00 |
October | 78.33 | 25.02 | 343.50 | 24.71 | 41.83 | 24.88 |
November | 155.00 | 23.18 | 176.33 | 23.90 | 2.67 | 23.92 |
December | 249.17 | 22.46 | 111.33 | 22.96 | 14.83 | 22.92 |
Annual Sum or Average | 1486.33 | 23.35 | 3333.00 | 24.16 | 306.00 | 24.26 |
Minimum of Months | 22.67 | 22.40 | 79.50 | 22.70 | 2.67 | 22.62 |
Maximum of Months | 307.00 | 26.93 | 432.00 | 24.94 | 51.50 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 231.67 | 22.67 | 165.83 | 23.46 | 20.67 | 23.51 |
February | 181.17 | 22.76 | 191.17 | 23.55 | 14.83 | 23.53 |
March | 214.00 | 22.63 | 195.00 | 23.40 | 8.67 | 23.35 |
April | 96.83 | 23.54 | 293.17 | 24.19 | 10.00 | 24.24 |
May | 13.00 | 26.37 | 507.50 | 24.46 | 13.00 | 24.51 |
June | 2.67 | 26.20 | 492.17 | 24.39 | 2.67 | 24.40 |
July | 14.67 | 26.29 | 492.67 | 24.55 | 14.67 | 24.60 |
August | 18.50 | 26.36 | 511.67 | 24.48 | 18.50 | 24.54 |
September | 40.17 | 26.61 | 473.33 | 24.66 | 40.17 | 24.80 |
October | 78.83 | 25.51 | 429.67 | 24.74 | 51.17 | 24.92 |
November | 129.83 | 23.81 | 292.83 | 24.37 | 21.50 | 24.50 |
December | 206.33 | 22.91 | 222.00 | 23.79 | 23.83 | 23.88 |
Annual Sum or Average | 1227.67 | 23.36 | 4267.00 | 24.22 | 239.67 | 24.29 |
Minimum of Months | 2.67 | 22.63 | 165.83 | 23.40 | 2.67 | 23.35 |
Maximum of Months | 231.67 | 26.61 | 511.67 | 24.74 | 51.17 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 334.00 | 22.20 | 109.33 | 22.61 | 19.00 | 22.55 |
February | 247.83 | 22.41 | 143.17 | 22.92 | 19.33 | 22.82 |
March | 246.17 | 22.61 | 175.67 | 23.23 | 14.00 | 23.18 |
April | 99.33 | 23.97 | 311.17 | 24.32 | 20.83 | 24.43 |
May | 26.00 | 26.65 | 507.83 | 24.57 | 26.00 | 24.67 |
June | 18.00 | 26.85 | 493.50 | 24.54 | 18.00 | 24.61 |
July | 39.50 | 26.68 | 495.00 | 24.72 | 39.50 | 24.86 |
August | 26.00 | 26.47 | 513.50 | 24.54 | 26.00 | 24.63 |
September | 33.83 | 26.56 | 476.50 | 24.62 | 33.83 | 24.74 |
October | 72.50 | 24.80 | 416.83 | 24.54 | 36.17 | 24.67 |
November | 191.00 | 23.11 | 209.83 | 23.77 | 4.00 | 23.80 |
December | 287.17 | 22.41 | 150.67 | 23.02 | 14.83 | 23.01 |
Annual Sum or Average | 1621.33 | 23.06 | 4003.00 | 24.02 | 271.50 | 24.08 |
Minimum of Months | 18.00 | 22.20 | 109.33 | 22.61 | 4.00 | 22.55 |
Maximum of Months | 334.00 | 26.85 | 513.50 | 24.72 | 39.50 | 24.86 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.30189 | 34.37470 | 0.38563 | 8.42312 |
February | 454.00000 | 24.33295 | 38.61344 | 0.42603 | 9.14864 |
March | 514.00000 | 24.30462 | 38.27702 | 0.42583 | 9.16948 |
April | 485.00000 | 24.48309 | 43.13036 | 0.51897 | 11.00735 |
May | 508.00000 | 24.45283 | 46.53626 | -0.2808 | 7.20493 |
June | 496.00000 | 24.41064 | 46.50299 | -0.2908 | 7.24140 |
July | 497.00000 | 24.46276 | 45.87568 | -0.2797 | 7.14912 |
August | 514.00000 | 24.41717 | 46.59071 | -0.2842 | 7.19404 |
September | 485.00000 | 24.43295 | 46.15486 | -0.2871 | 7.19644 |
October | 502.00000 | 24.49414 | 43.67098 | 0.54945 | 11.68282 |
November | 489.00000 | 24.42895 | 39.82509 | 0.48675 | 10.26556 |
December | 497.00000 | 24.35370 | 37.40326 | 0.43078 | 9.29153 |
Annual Sum or Average | 5943.00000 | 24.40641 | 42.26902 | 0.14711 | 8.73785 |
Minimum of Months | 454.00000 | 24.30189 | 34.37470 | -0.2908 | 7.14912 |
Maximum of Months | 514.00000 | 24.49414 | 46.59071 | 0.54945 | 11.68282 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32502 | 37.33894 | 0.15606 | 6.42234 |
February | 454.00000 | 23.51016 | 40.96417 | 0.23016 | 7.10688 |
March | 514.00000 | 23.65820 | 40.46566 | 0.26988 | 7.36274 |
April | 485.00000 | 24.11458 | 44.36590 | 0.42298 | 9.01356 |
May | 508.00000 | 24.26759 | 47.87716 | -0.3550 | 7.93708 |
June | 496.00000 | 24.24210 | 47.69028 | -0.3604 | 7.98813 |
July | 497.00000 | 24.27894 | 47.35578 | -0.3505 | 7.88511 |
August | 514.00000 | 24.25811 | 48.04671 | -0.3521 | 7.88716 |
September | 485.00000 | 24.25099 | 47.75908 | -0.3626 | 8.05329 |
October | 502.00000 | 24.24826 | 45.14029 | 0.48154 | 10.19104 |
November | 489.00000 | 23.96192 | 41.27306 | 0.36048 | 8.09783 |
December | 497.00000 | 23.56070 | 39.94363 | 0.23786 | 7.14030 |
Annual Sum or Average | 5943.00000 | 23.97567 | 44.03914 | 0.02908 | 7.92595 |
Minimum of Months | 454.00000 | 23.32502 | 37.33894 | -0.3626 | 6.42234 |
Maximum of Months | 514.00000 | 24.27894 | 48.04671 | 0.48154 | 10.19104 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.65080 | 38.47683 | -0.0101 | 6.79135 |
February | 454.00000 | 22.97213 | 41.76688 | 0.09885 | 7.17268 |
March | 514.00000 | 23.30788 | 40.84439 | 0.18163 | 7.20917 |
April | 485.00000 | 23.99270 | 44.03730 | 0.39259 | 8.66082 |
May | 508.00000 | 24.29034 | 47.40725 | -0.3366 | 7.67385 |
June | 496.00000 | 24.27640 | 47.26068 | -0.3346 | 7.61575 |
July | 497.00000 | 24.33217 | 46.93236 | -0.3200 | 7.49398 |
August | 514.00000 | 24.27828 | 47.74052 | -0.3340 | 7.62846 |
September | 485.00000 | 24.26476 | 47.45292 | -0.3536 | 7.96705 |
October | 502.00000 | 24.16829 | 44.91655 | 0.46254 | 10.00816 |
November | 489.00000 | 23.59834 | 41.63892 | 0.26722 | 7.28147 |
December | 497.00000 | 22.97294 | 40.82846 | 0.09147 | 6.98709 |
Annual Sum or Average | 5943.00000 | 23.76367 | 44.12482 | -0.0180 | 7.70895 |
Minimum of Months | 454.00000 | 22.65080 | 38.47683 | -0.3536 | 6.79135 |
Maximum of Months | 514.00000 | 24.33217 | 47.74052 | 0.46254 | 10.00816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.94997 | 42.22837 | -0.1824 | 8.67816 |
February | 454.00000 | 22.36909 | 44.35827 | -0.0461 | 8.66914 |
March | 514.00000 | 22.85756 | 43.14565 | 0.07596 | 8.01765 |
April | 485.00000 | 23.82713 | 46.30990 | 0.37307 | 8.99647 |
May | 508.00000 | 24.41828 | 49.36650 | -0.2376 | 7.02844 |
June | 496.00000 | 24.41012 | 48.38609 | -0.2250 | 6.82808 |
July | 497.00000 | 24.53459 | 48.84223 | -0.1860 | 6.94922 |
August | 514.00000 | 24.38909 | 49.86562 | -0.2364 | 6.99869 |
September | 485.00000 | 24.38046 | 50.23160 | -0.2693 | 7.59853 |
October | 502.00000 | 24.12949 | 48.19599 | 0.48595 | 11.22788 |
November | 489.00000 | 23.14329 | 44.47173 | 0.16544 | 7.43390 |
December | 497.00000 | 22.35416 | 44.59828 | -0.0549 | 8.17663 |
Annual Sum or Average | 5943.00000 | 23.57153 | 46.68120 | -0.0289 | 8.04400 |
Minimum of Months | 454.00000 | 21.94997 | 42.22837 | -0.2693 | 6.82808 |
Maximum of Months | 514.00000 | 24.53459 | 50.23160 | 0.48595 | 11.22788 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.60140 | 41.57855 | -0.0123 | 8.20624 |
February | 454.00000 | 22.94038 | 43.38804 | 0.10849 | 8.47040 |
March | 514.00000 | 23.32177 | 41.87019 | 0.21190 | 9.00060 |
April | 485.00000 | 24.07892 | 45.24669 | 0.47120 | 10.88479 |
May | 508.00000 | 24.50402 | 48.80512 | -0.1480 | 6.96342 |
June | 496.00000 | 24.46484 | 48.03181 | -0.1490 | 6.63248 |
July | 497.00000 | 24.60562 | 48.36400 | -0.1057 | 7.00093 |
August | 514.00000 | 24.44594 | 49.47015 | -0.1650 | 6.78899 |
September | 485.00000 | 24.48163 | 49.63885 | -0.1887 | 7.60428 |
October | 502.00000 | 24.30162 | 47.42203 | 0.55969 | 13.10488 |
November | 489.00000 | 23.64177 | 43.28732 | 0.30288 | 8.64355 |
December | 497.00000 | 22.83478 | 44.04849 | 0.07213 | 8.39589 |
Annual Sum or Average | 5943.00000 | 23.85765 | 45.94618 | 0.07866 | 8.46926 |
Minimum of Months | 454.00000 | 22.60140 | 41.57855 | -0.1887 | 6.63248 |
Maximum of Months | 514.00000 | 24.60562 | 49.63885 | 0.55969 | 13.10488 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19341 | 38.25073 | 0.16021 | 9.70871 |
February | 454.00000 | 23.33284 | 40.99341 | 0.22741 | 9.84474 |
March | 514.00000 | 23.29919 | 41.24100 | 0.20919 | 9.11037 |
April | 485.00000 | 23.96631 | 45.51484 | 0.42575 | 10.09369 |
May | 508.00000 | 24.41491 | 49.35834 | -0.2348 | 7.06799 |
June | 496.00000 | 24.39072 | 48.51853 | -0.2386 | 6.95284 |
July | 497.00000 | 24.52139 | 48.90540 | -0.1917 | 6.99701 |
August | 514.00000 | 24.40618 | 49.64725 | -0.2104 | 6.89944 |
September | 485.00000 | 24.45530 | 49.56069 | -0.2024 | 7.53429 |
October | 502.00000 | 24.38326 | 46.57705 | 0.60274 | 14.24852 |
November | 489.00000 | 23.94521 | 41.15030 | 0.41460 | 10.98355 |
December | 497.00000 | 23.40621 | 40.92824 | 0.24839 | 10.50562 |
Annual Sum or Average | 5943.00000 | 23.97971 | 45.08359 | 0.09880 | 9.15086 |
Minimum of Months | 454.00000 | 23.19341 | 38.25073 | -0.2386 | 6.89944 |
Maximum of Months | 514.00000 | 24.52139 | 49.64725 | 0.60274 | 14.24852 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47082 | 41.44204 | -0.0413 | 8.88403 |
February | 454.00000 | 22.82149 | 43.43846 | 0.08335 | 9.31857 |
March | 514.00000 | 23.13659 | 42.57317 | 0.16597 | 8.92208 |
April | 485.00000 | 24.01328 | 45.82891 | 0.45387 | 10.82175 |
May | 508.00000 | 24.46090 | 49.41628 | -0.1850 | 6.95783 |
June | 496.00000 | 24.45179 | 48.43100 | -0.1719 | 6.83433 |
July | 497.00000 | 24.57746 | 48.87757 | -0.1386 | 7.00887 |
August | 514.00000 | 24.44048 | 49.80488 | -0.1751 | 6.77032 |
September | 485.00000 | 24.45383 | 50.10335 | -0.2029 | 7.54019 |
October | 502.00000 | 24.26420 | 47.83995 | 0.55152 | 12.87599 |
November | 489.00000 | 23.46216 | 43.72587 | 0.26366 | 8.69943 |
December | 497.00000 | 22.77121 | 43.91243 | 0.06386 | 8.86804 |
Annual Sum or Average | 5943.00000 | 23.78304 | 46.30219 | 0.05443 | 8.61431 |
Minimum of Months | 454.00000 | 22.47082 | 41.44204 | -0.2029 | 6.77032 |
Maximum of Months | 514.00000 | 24.57746 | 50.10335 | 0.55152 | 12.87599 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47349 | 40.68116 | -0.0417 | 6.79305 |
February | 454.00000 | 22.69091 | 44.24816 | 0.03599 | 7.10097 |
March | 514.00000 | 22.95454 | 43.62174 | 0.09896 | 6.94435 |
April | 485.00000 | 23.79954 | 47.44703 | 0.35000 | 8.16828 |
May | 508.00000 | 24.32986 | 49.03791 | -0.3102 | 7.46938 |
June | 496.00000 | 24.34243 | 48.05518 | -0.2875 | 7.12466 |
July | 497.00000 | 24.47028 | 47.72361 | -0.2386 | 6.87688 |
August | 514.00000 | 24.40257 | 48.30105 | -0.2470 | 6.85677 |
September | 485.00000 | 24.40548 | 48.29794 | -0.2705 | 7.09915 |
October | 502.00000 | 24.29842 | 46.49492 | 0.51882 | 11.21488 |
November | 489.00000 | 23.68774 | 43.68135 | 0.30247 | 7.67027 |
December | 497.00000 | 22.98635 | 42.93456 | 0.10831 | 7.05253 |
Annual Sum or Average | 5943.00000 | 23.74303 | 45.88585 | 0.00022 | 7.53227 |
Minimum of Months | 454.00000 | 22.47349 | 40.68116 | -0.3102 | 6.79305 |
Maximum of Months | 514.00000 | 24.47028 | 49.03791 | 0.51882 | 11.21488 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30498 | 39.47347 | 0.16600 | 7.19566 |
February | 454.00000 | 23.41184 | 42.86469 | 0.22298 | 7.65672 |
March | 514.00000 | 23.56069 | 42.01348 | 0.26666 | 8.33528 |
April | 485.00000 | 24.14341 | 45.94146 | 0.46940 | 10.32303 |
May | 508.00000 | 24.48559 | 48.34466 | -0.1966 | 6.93558 |
June | 496.00000 | 24.44748 | 47.58564 | -0.1946 | 6.61678 |
July | 497.00000 | 24.60031 | 47.19030 | -0.1385 | 6.68447 |
August | 514.00000 | 24.48861 | 47.88635 | -0.1635 | 6.52786 |
September | 485.00000 | 24.54066 | 47.74861 | -0.1760 | 6.97998 |
October | 502.00000 | 24.47346 | 45.78038 | 0.59731 | 13.34185 |
November | 489.00000 | 24.12616 | 42.36931 | 0.43157 | 9.60782 |
December | 497.00000 | 23.50207 | 42.13594 | 0.24340 | 7.95937 |
Annual Sum or Average | 5943.00000 | 24.09424 | 44.95735 | 0.12561 | 8.17752 |
Minimum of Months | 454.00000 | 23.30498 | 39.47347 | -0.1966 | 6.52786 |
Maximum of Months | 514.00000 | 24.60031 | 48.34466 | 0.59731 | 13.34185 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33609 | 38.44672 | 0.25240 | 9.75015 |
February | 454.00000 | 23.45615 | 43.44803 | 0.30210 | 9.76335 |
March | 514.00000 | 23.09767 | 44.00984 | 0.19748 | 8.93123 |
April | 485.00000 | 23.84687 | 50.30832 | 0.41273 | 9.66853 |
May | 508.00000 | 24.39198 | 56.40609 | -0.2362 | 6.67033 |
June | 496.00000 | 24.39129 | 56.28809 | -0.2261 | 6.48948 |
July | 497.00000 | 24.54620 | 56.52188 | -0.1576 | 6.23032 |
August | 514.00000 | 24.53513 | 56.72021 | -0.1257 | 6.10770 |
September | 485.00000 | 24.55204 | 55.71935 | -0.1217 | 6.35914 |
October | 502.00000 | 24.62227 | 49.70680 | 0.69224 | 16.31963 |
November | 489.00000 | 24.26629 | 43.64741 | 0.54142 | 12.77897 |
December | 497.00000 | 23.63377 | 41.72270 | 0.35802 | 11.28082 |
Annual Sum or Average | 5943.00000 | 24.05885 | 49.45675 | 0.15507 | 9.18430 |
Minimum of Months | 454.00000 | 23.09767 | 38.44672 | -0.2362 | 6.10770 |
Maximum of Months | 514.00000 | 24.62227 | 56.72021 | 0.69224 | 16.31963 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.17421 | 39.38868 | 0.13863 | 7.31291 |
February | 454.00000 | 23.33744 | 42.80450 | 0.20848 | 8.04798 |
March | 514.00000 | 23.44983 | 42.50282 | 0.23529 | 8.02142 |
April | 485.00000 | 24.13977 | 46.31532 | 0.46482 | 10.29607 |
May | 508.00000 | 24.42283 | 48.88706 | -0.2395 | 7.01681 |
June | 496.00000 | 24.43364 | 47.90866 | -0.2172 | 6.78825 |
July | 497.00000 | 24.56596 | 47.59299 | -0.1733 | 6.72912 |
August | 514.00000 | 24.48420 | 48.10113 | -0.1733 | 6.50513 |
September | 485.00000 | 24.52106 | 48.00211 | -0.1874 | 6.88080 |
October | 502.00000 | 24.46213 | 45.96337 | 0.59401 | 13.17362 |
November | 489.00000 | 24.05107 | 42.65529 | 0.41342 | 9.34751 |
December | 497.00000 | 23.51812 | 41.87136 | 0.25263 | 8.17241 |
Annual Sum or Average | 5943.00000 | 24.05046 | 45.18154 | 0.10787 | 8.18508 |
Minimum of Months | 454.00000 | 23.17421 | 39.38868 | -0.2395 | 6.50513 |
Maximum of Months | 514.00000 | 24.56596 | 48.88706 | 0.59401 | 13.17362 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35984 | 41.27284 | -0.0671 | 7.34201 |
February | 454.00000 | 22.76968 | 43.71542 | 0.05875 | 7.62143 |
March | 514.00000 | 23.15279 | 42.78825 | 0.15317 | 7.50502 |
April | 485.00000 | 23.97880 | 46.38031 | 0.40777 | 9.11067 |
May | 508.00000 | 24.41314 | 49.42762 | -0.2537 | 7.04667 |
June | 496.00000 | 24.39403 | 48.43890 | -0.2480 | 6.86800 |
July | 497.00000 | 24.50755 | 48.82110 | -0.2123 | 6.90281 |
August | 514.00000 | 24.38537 | 49.69407 | -0.2533 | 7.02237 |
September | 485.00000 | 24.38641 | 50.03297 | -0.2769 | 7.38992 |
October | 502.00000 | 24.22229 | 47.94029 | 0.50390 | 11.17393 |
November | 489.00000 | 23.49803 | 43.92372 | 0.25452 | 7.42147 |
December | 497.00000 | 22.77149 | 43.67854 | 0.05693 | 7.32756 |
Annual Sum or Average | 5943.00000 | 23.74271 | 46.35943 | 0.00897 | 7.72553 |
Minimum of Months | 454.00000 | 22.35984 | 41.27284 | -0.2769 | 6.86800 |
Maximum of Months | 514.00000 | 24.50755 | 50.03297 | 0.50390 | 11.17393 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.94251 | 40.53086 | 0.07941 | 7.65554 |
February | 385.00000 | 23.24930 | 42.46196 | 0.18161 | 7.95994 |
March | 433.00000 | 23.52558 | 41.38351 | 0.25832 | 8.73647 |
April | 410.00000 | 24.23249 | 45.20690 | 0.49090 | 11.02728 |
May | 430.00000 | 24.60572 | 48.61940 | -0.1523 | 7.12300 |
June | 418.00000 | 24.55290 | 47.74141 | -0.1644 | 6.78743 |
July | 422.00000 | 24.70419 | 48.01747 | -0.1167 | 7.10180 |
August | 433.00000 | 24.53594 | 49.12569 | -0.1747 | 6.92999 |
September | 410.00000 | 24.59327 | 49.24480 | -0.1830 | 7.58374 |
October | 427.00000 | 24.44990 | 47.14052 | 0.57660 | 13.30123 |
November | 417.00000 | 23.89907 | 42.48672 | 0.36093 | 8.96126 |
December | 422.00000 | 23.17348 | 43.07642 | 0.15978 | 8.00345 |
Annual Sum or Average | 5034.00000 | 24.04263 | 45.43505 | 0.10865 | 8.43037 |
Minimum of Months | 385.00000 | 22.94251 | 40.53086 | -0.1830 | 6.78743 |
Maximum of Months | 433.00000 | 24.70419 | 49.24480 | 0.57660 | 13.30123 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55196 | 37.25953 | 0.26053 | 9.33192 |
February | 454.00000 | 23.67560 | 40.38585 | 0.31757 | 9.58219 |
March | 514.00000 | 23.56356 | 40.84844 | 0.27818 | 8.79365 |
April | 485.00000 | 24.10822 | 45.55515 | 0.45728 | 10.17581 |
May | 508.00000 | 24.41567 | 49.39537 | -0.2496 | 7.06502 |
June | 496.00000 | 24.37509 | 48.56430 | -0.2614 | 6.98907 |
July | 497.00000 | 24.49626 | 48.87038 | -0.2175 | 6.94765 |
August | 514.00000 | 24.40762 | 49.44998 | -0.2268 | 6.89881 |
September | 485.00000 | 24.47613 | 49.32411 | -0.2076 | 7.28852 |
October | 502.00000 | 24.46968 | 46.30929 | 0.61721 | 14.24125 |
November | 489.00000 | 24.19041 | 40.85445 | 0.47996 | 11.40452 |
December | 497.00000 | 23.74523 | 40.10482 | 0.34108 | 10.37483 |
Annual Sum or Average | 5943.00000 | 24.12494 | 44.77466 | 0.12990 | 9.07990 |
Minimum of Months | 454.00000 | 23.55196 | 37.25953 | -0.2614 | 6.89881 |
Maximum of Months | 514.00000 | 24.49626 | 49.44998 | 0.61721 | 14.24125 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.87260 | 40.38370 | 0.06971 | 7.84875 |
February | 454.00000 | 23.20794 | 42.76596 | 0.18352 | 8.54653 |
March | 514.00000 | 23.42789 | 42.15941 | 0.24085 | 8.50204 |
April | 485.00000 | 24.16581 | 45.85352 | 0.48746 | 10.94534 |
May | 508.00000 | 24.46401 | 49.43859 | -0.1998 | 6.90427 |
June | 496.00000 | 24.44792 | 48.44061 | -0.1924 | 6.78957 |
July | 497.00000 | 24.56509 | 48.80921 | -0.1616 | 6.89851 |
August | 514.00000 | 24.44191 | 49.60743 | -0.1918 | 6.73820 |
September | 485.00000 | 24.47206 | 49.86840 | -0.2085 | 7.29133 |
October | 502.00000 | 24.35561 | 47.55622 | 0.56784 | 12.83491 |
November | 489.00000 | 23.78448 | 43.21592 | 0.34508 | 8.80671 |
December | 497.00000 | 23.17139 | 42.94236 | 0.17019 | 8.23176 |
Annual Sum or Average | 5943.00000 | 23.95237 | 45.94133 | 0.09086 | 8.35316 |
Minimum of Months | 454.00000 | 22.87260 | 40.38370 | -0.2085 | 6.73820 |
Maximum of Months | 514.00000 | 24.56509 | 49.86840 | 0.56784 | 12.83491 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.210005E+11 | 0.473753E+10 | 268.37 | 0.148543E+11 | 0.614624E+10 | 0.00 | 1.00 | 02-JAN-06:12 | 0.00 | 01-JAN-00:10 | 67392.80 | 19-JAN-15:05 | 51234.15 | 02-JAN-06:12 | 28716.14 | 20-JAN-07:02 | 14638.67 | 19-JAN-12:00 | 0.00 |
February | 0.274149E+11 | 0.613589E+10 | 293.69 | 0.180089E+11 | 0.940602E+10 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 66754.21 | 27-FEB-15:40 | 50001.16 | 27-FEB-15:40 | 22491.80 | 23-FEB-07:02 | 14658.98 | 27-FEB-15:40 | 0.00 |
March | 0.327700E+11 | 0.737171E+10 | 355.30 | 0.226981E+11 | 0.100720E+11 | 0.00 | 1.00 | 06-MAR-07:03 | 0.00 | 01-MAR-00:10 | 67915.32 | 28-MAR-12:00 | 45539.21 | 29-MAR-15:00 | 25593.12 | 07-MAR-13:00 | 15383.73 | 28-MAR-12:00 | 0.00 |
April | 0.513423E+11 | 0.115547E+11 | 395.07 | 0.365291E+11 | 0.148132E+11 | 0.00 | 1.00 | 01-APR-06:05 | 0.00 | 01-APR-00:10 | 83806.87 | 28-APR-16:00 | 58046.85 | 28-APR-15:00 | 30247.02 | 28-APR-06:03 | 21014.21 | 28-APR-16:00 | 0.00 |
May | 0.897685E+11 | 0.210032E+11 | 454.11 | 0.608279E+11 | 0.289406E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:10 | 90049.86 | 25-MAY-06:03 | 76578.91 | 30-MAY-06:03 | 40156.92 | 24-MAY-06:03 | 21811.35 | 30-MAY-12:03 | 0.00 |
June | 0.955414E+11 | 0.226556E+11 | 456.17 | 0.643712E+11 | 0.311702E+11 | 0.00 | 1.00 | 01-JUN-05:12 | 0.00 | 01-JUN-00:10 | 95165.33 | 05-JUN-12:03 | 75033.59 | 05-JUN-04:02 | 40315.38 | 29-JUN-17:00 | 23379.41 | 29-JUN-12:04 | 0.00 |
July | 0.100305E+12 | 0.237672E+11 | 470.85 | 0.648446E+11 | 0.354603E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 103815.81 | 05-JUL-12:02 | 78669.85 | 24-JUL-06:03 | 39499.60 | 12-JUL-12:02 | 25665.71 | 05-JUL-12:02 | 0.00 |
August | 0.106838E+12 | 0.251662E+11 | 480.06 | 0.703772E+11 | 0.364607E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 106080.27 | 22-AUG-06:03 | 78450.25 | 21-AUG-06:03 | 41144.59 | 09-AUG-17:00 | 25180.02 | 03-AUG-16:00 | 0.00 |
September | 0.912555E+11 | 0.208080E+11 | 456.31 | 0.595784E+11 | 0.316770E+11 | 0.00 | 1.00 | 01-SEP-04:23 | 0.00 | 01-SEP-00:10 | 104063.75 | 12-SEP-06:03 | 77352.11 | 11-SEP-04:02 | 39419.85 | 05-SEP-12:02 | 23827.98 | 05-SEP-12:02 | 0.00 |
October | 0.814309E+11 | 0.187162E+11 | 445.38 | 0.565894E+11 | 0.248415E+11 | 0.00 | 1.00 | 02-OCT-07:40 | 0.00 | 01-OCT-00:10 | 112601.47 | 06-OCT-06:03 | 76944.34 | 16-OCT-05:12 | 45776.70 | 24-OCT-12:03 | 24895.08 | 06-OCT-12:02 | 0.00 |
November | 0.450418E+11 | 0.100866E+11 | 388.72 | 0.322342E+11 | 0.128076E+11 | 0.00 | 1.00 | 01-NOV-06:03 | 0.00 | 01-NOV-00:10 | 87752.97 | 07-NOV-13:05 | 59862.18 | 06-NOV-16:00 | 34274.50 | 03-NOV-17:00 | 20005.30 | 07-NOV-13:05 | 0.00 |
December | 0.299646E+11 | 0.671516E+10 | 298.10 | 0.207439E+11 | 0.922075E+10 | 0.00 | 1.00 | 01-DEC-13:40 | 0.00 | 01-DEC-00:10 | 76338.45 | 14-DEC-13:05 | 53836.09 | 15-DEC-15:20 | 28913.87 | 15-DEC-07:03 | 17285.96 | 14-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.772673E+12 | 0.178718E+12 | 4762.12 | 0.521657E+12 | 0.251016E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.210005E+11 | 0.473753E+10 | 268.37 | 0.148543E+11 | 0.614624E+10 | 0.00 | 1.00 | 0.00 | 66754.21 | 45539.21 | 22491.80 | 14638.67 | 0.00 | ||||||
Maximum of Months | 0.106838E+12 | 0.251662E+11 | 480.06 | 0.703772E+11 | 0.364607E+11 | 0.00 | 1.00 | 0.00 | 112601.47 | 78669.85 | 45776.70 | 25665.71 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.167431E+11 | 0.380697E+10 | 252.59 | 0.113033E+11 | 0.543981E+10 | 0.00 | 1.00 | 01-JAN-15:12 | 0.00 | 01-JAN-00:10 | 60941.47 | 19-JAN-15:05 | 41724.17 | 02-JAN-13:30 | 19636.20 | 31-JAN-13:05 | 13173.15 | 19-JAN-15:05 | 0.00 |
February | 0.234135E+11 | 0.528673E+10 | 295.73 | 0.153053E+11 | 0.810825E+10 | 0.00 | 1.00 | 01-FEB-13:05 | 0.00 | 01-FEB-00:10 | 59952.34 | 27-FEB-15:05 | 45047.14 | 27-FEB-15:05 | 18262.80 | 24-FEB-11:05 | 13248.67 | 27-FEB-15:05 | 0.00 |
March | 0.285095E+11 | 0.644994E+10 | 357.92 | 0.196410E+11 | 0.886849E+10 | 0.00 | 1.00 | 06-MAR-09:10 | 0.00 | 01-MAR-00:10 | 61019.68 | 07-MAR-11:05 | 41371.77 | 28-MAR-12:05 | 22065.76 | 07-MAR-11:05 | 13845.16 | 28-MAR-12:05 | 0.00 |
April | 0.456039E+11 | 0.103151E+11 | 402.74 | 0.320025E+11 | 0.136014E+11 | 0.00 | 1.00 | 03-APR-14:05 | 0.00 | 01-APR-00:10 | 79532.09 | 28-APR-16:00 | 53816.60 | 28-APR-15:00 | 26982.11 | 28-APR-16:00 | 19796.26 | 28-APR-16:00 | 0.00 |
May | 0.805346E+11 | 0.187599E+11 | 453.36 | 0.534102E+11 | 0.271244E+11 | 0.00 | 1.00 | 01-MAY-04:02 | 0.00 | 01-MAY-00:10 | 105655.31 | 22-MAY-04:02 | 70053.55 | 30-MAY-04:02 | 36649.87 | 22-MAY-04:02 | 23094.57 | 22-MAY-04:02 | 0.00 |
June | 0.856301E+11 | 0.201649E+11 | 455.12 | 0.561856E+11 | 0.294445E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 84738.05 | 19-JUN-11:00 | 69058.12 | 05-JUN-04:02 | 33298.46 | 29-JUN-15:00 | 21769.34 | 28-JUN-14:05 | 0.00 |
July | 0.891204E+11 | 0.209130E+11 | 464.26 | 0.554281E+11 | 0.336922E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 90533.06 | 05-JUL-12:02 | 69886.02 | 24-JUL-04:02 | 35402.26 | 22-JUL-10:05 | 22656.59 | 20-JUL-12:02 | 0.00 |
August | 0.914769E+11 | 0.213623E+11 | 468.00 | 0.574822E+11 | 0.339947E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 88301.56 | 07-AUG-13:00 | 69843.56 | 28-AUG-04:02 | 36518.58 | 09-AUG-17:20 | 22156.02 | 03-AUG-15:50 | 0.00 |
September | 0.773308E+11 | 0.175423E+11 | 441.44 | 0.478658E+11 | 0.294650E+11 | 0.00 | 1.00 | 01-SEP-04:23 | 0.00 | 01-SEP-00:10 | 99695.07 | 05-SEP-06:03 | 70249.16 | 05-SEP-05:12 | 34108.02 | 16-SEP-13:00 | 21025.37 | 05-SEP-06:03 | 0.00 |
October | 0.687556E+11 | 0.157466E+11 | 432.36 | 0.457135E+11 | 0.230421E+11 | 0.00 | 1.00 | 01-OCT-15:02 | 0.00 | 01-OCT-00:10 | 92464.86 | 06-OCT-14:05 | 70477.29 | 10-OCT-05:12 | 40312.38 | 07-OCT-08:00 | 22485.57 | 06-OCT-12:02 | 0.00 |
November | 0.367745E+11 | 0.830057E+10 | 384.89 | 0.254070E+11 | 0.113676E+11 | 0.00 | 1.00 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 77501.56 | 02-NOV-14:05 | 52808.57 | 06-NOV-15:05 | 27207.29 | 07-NOV-13:05 | 18191.93 | 02-NOV-14:05 | 0.00 |
December | 0.244648E+11 | 0.552788E+10 | 291.00 | 0.163206E+11 | 0.814416E+10 | 0.00 | 1.00 | 01-DEC-15:05 | 0.00 | 01-DEC-00:10 | 66812.78 | 14-DEC-13:05 | 48933.67 | 15-DEC-15:05 | 26853.20 | 12-DEC-15:10 | 15164.85 | 13-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.668358E+12 | 0.154176E+12 | 4699.40 | 0.436065E+12 | 0.232293E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.167431E+11 | 0.380697E+10 | 252.59 | 0.113033E+11 | 0.543981E+10 | 0.00 | 1.00 | 0.00 | 59952.34 | 41371.77 | 18262.80 | 13173.15 | 0.00 | ||||||
Maximum of Months | 0.914769E+11 | 0.213623E+11 | 468.00 | 0.574822E+11 | 0.339947E+11 | 0.00 | 1.00 | 0.00 | 105655.31 | 70477.29 | 40312.38 | 23094.57 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.169007E+11 | 0.387844E+10 | 249.81 | 0.113175E+11 | 0.558319E+10 | 0.00 | 1.00 | 01-JAN-14:21 | 0.00 | 01-JAN-00:10 | 64197.88 | 19-JAN-15:00 | 47635.30 | 01-JAN-15:42 | 19638.73 | 19-JAN-14:50 | 13865.69 | 19-JAN-15:00 | 0.00 |
February | 0.239505E+11 | 0.545470E+10 | 294.39 | 0.156439E+11 | 0.830666E+10 | 0.00 | 1.00 | 01-FEB-13:30 | 0.00 | 01-FEB-00:10 | 62920.96 | 27-FEB-15:30 | 48479.64 | 27-FEB-15:00 | 17536.05 | 24-FEB-10:40 | 13959.26 | 24-FEB-14:10 | 0.00 |
March | 0.295644E+11 | 0.673912E+10 | 357.89 | 0.203494E+11 | 0.921496E+10 | 0.00 | 1.00 | 06-MAR-09:50 | 0.00 | 01-MAR-00:10 | 63267.94 | 28-MAR-12:30 | 47003.23 | 29-MAR-15:00 | 21776.04 | 07-MAR-11:30 | 14643.03 | 30-MAR-13:00 | 0.00 |
April | 0.480969E+11 | 0.109700E+11 | 403.21 | 0.340746E+11 | 0.140223E+11 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 88341.60 | 28-APR-16:00 | 63261.85 | 28-APR-15:20 | 26602.81 | 28-APR-16:00 | 22029.52 | 28-APR-16:00 | 0.00 |
May | 0.857718E+11 | 0.200916E+11 | 456.50 | 0.582360E+11 | 0.275357E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 117640.33 | 22-MAY-04:02 | 80303.18 | 22-MAY-04:02 | 37337.15 | 22-MAY-04:02 | 25758.06 | 22-MAY-04:02 | 0.00 |
June | 0.917887E+11 | 0.217281E+11 | 458.03 | 0.620491E+11 | 0.297397E+11 | 0.00 | 1.00 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 92745.12 | 28-JUN-14:30 | 79097.99 | 05-JUN-04:02 | 32885.77 | 29-JUN-15:00 | 23884.45 | 28-JUN-14:00 | 0.00 |
July | 0.947783E+11 | 0.223626E+11 | 468.89 | 0.607241E+11 | 0.340542E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 95091.60 | 05-JUL-13:50 | 80482.53 | 24-JUL-04:02 | 33650.73 | 12-JUL-10:00 | 25251.61 | 21-JUL-16:00 | 0.00 |
August | 0.967448E+11 | 0.227021E+11 | 470.53 | 0.623405E+11 | 0.344043E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 93819.93 | 07-AUG-13:00 | 80462.56 | 28-AUG-04:02 | 34776.43 | 09-AUG-17:10 | 24821.15 | 03-AUG-15:40 | 0.00 |
September | 0.808982E+11 | 0.184485E+11 | 444.89 | 0.508685E+11 | 0.300297E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 104111.29 | 05-SEP-06:03 | 78157.97 | 11-SEP-04:02 | 34390.46 | 16-SEP-13:00 | 22196.30 | 01-SEP-15:00 | 0.00 |
October | 0.714849E+11 | 0.164571E+11 | 432.08 | 0.479863E+11 | 0.234986E+11 | 0.00 | 1.00 | 01-OCT-14:02 | 0.00 | 01-OCT-00:10 | 97980.26 | 06-OCT-14:00 | 69313.99 | 05-OCT-15:00 | 41374.98 | 07-OCT-08:00 | 23524.30 | 05-OCT-15:00 | 0.00 |
November | 0.371583E+11 | 0.846904E+10 | 383.61 | 0.252298E+11 | 0.119285E+11 | 0.00 | 1.00 | 01-NOV-08:30 | 0.00 | 01-NOV-00:10 | 82609.63 | 02-NOV-14:30 | 57945.27 | 02-NOV-15:00 | 26989.56 | 07-NOV-13:00 | 19399.82 | 02-NOV-14:30 | 0.00 |
December | 0.247625E+11 | 0.564811E+10 | 289.74 | 0.163059E+11 | 0.845656E+10 | 0.00 | 1.00 | 08-DEC-13:10 | 0.00 | 01-DEC-00:10 | 68471.41 | 15-DEC-14:50 | 53355.19 | 15-DEC-15:00 | 26345.38 | 12-DEC-15:00 | 16097.11 | 15-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.701900E+12 | 0.162950E+12 | 4709.58 | 0.465126E+12 | 0.236774E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.169007E+11 | 0.387844E+10 | 249.81 | 0.113175E+11 | 0.558319E+10 | 0.00 | 1.00 | 0.00 | 62920.96 | 47003.23 | 17536.05 | 13865.69 | 0.00 | ||||||
Maximum of Months | 0.967448E+11 | 0.227021E+11 | 470.53 | 0.623405E+11 | 0.344043E+11 | 0.00 | 1.00 | 0.00 | 117640.33 | 80482.53 | 41374.98 | 25758.06 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.99 | 0.00 | 310.99 | 241.03 | 1046.70 | 0.00 | 0.00 | 0.00 |
February | 366.89 | 0.00 | 366.89 | 323.10 | 877.41 | 0.00 | 0.00 | 0.00 |
March | 425.62 | 0.00 | 425.62 | 453.63 | 758.54 | 0.00 | 0.00 | 0.00 |
April | 502.33 | 2.06 | 500.27 | 697.68 | 482.51 | 0.00 | 0.00 | 0.00 |
May | 568.98 | 20.81 | 548.17 | 1149.29 | 143.06 | 0.00 | 0.00 | 0.00 |
June | 647.06 | 44.80 | 602.25 | 1358.79 | 123.15 | 0.00 | 0.00 | 0.00 |
July | 627.93 | 23.92 | 604.00 | 1305.08 | 84.44 | 0.00 | 0.00 | 0.00 |
August | 562.32 | 4.42 | 557.90 | 1181.87 | 115.49 | 0.00 | 0.00 | 0.00 |
September | 485.72 | 0.04 | 485.68 | 938.16 | 163.14 | 0.00 | 0.00 | 0.00 |
October | 422.08 | 0.00 | 422.08 | 761.25 | 306.27 | 0.00 | 0.00 | 0.00 |
November | 320.43 | 0.00 | 320.43 | 359.78 | 675.80 | 0.00 | 0.00 | 0.00 |
December | 289.10 | 0.00 | 289.10 | 256.83 | 892.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.25 | 8.03 | 453.22 | 754.79 | 470.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.10 | 0.00 | 289.10 | 241.03 | 84.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.06 | 44.80 | 604.00 | 1358.79 | 1046.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 533.58 | 271.70 | 261.88 | 646.78 | 653.01 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.84 | 307.31 | 758.73 | 551.20 | 0.00 | 0.00 | 0.00 |
March | 698.92 | 337.07 | 361.85 | 956.96 | 481.31 | 0.00 | 0.00 | 0.00 |
April | 766.99 | 346.89 | 420.10 | 1185.09 | 318.34 | 0.00 | 0.00 | 0.00 |
May | 790.56 | 342.80 | 447.76 | 1455.27 | 96.88 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 317.95 | 483.80 | 1527.28 | 83.45 | 0.00 | 0.00 | 0.00 |
July | 773.01 | 282.88 | 490.13 | 1472.41 | 56.77 | 0.00 | 0.00 | 0.00 |
August | 712.30 | 244.90 | 467.41 | 1360.76 | 78.49 | 0.00 | 0.00 | 0.00 |
September | 630.97 | 216.93 | 414.04 | 1147.79 | 109.95 | 0.00 | 0.00 | 0.00 |
October | 623.53 | 263.13 | 360.40 | 1081.31 | 201.32 | 0.00 | 0.00 | 0.00 |
November | 552.04 | 281.62 | 270.42 | 777.08 | 429.96 | 0.00 | 0.00 | 0.00 |
December | 434.65 | 196.89 | 237.76 | 549.72 | 571.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 659.59 | 282.34 | 377.26 | 1078.30 | 301.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 434.65 | 196.89 | 237.76 | 549.72 | 56.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 801.76 | 346.89 | 490.13 | 1527.28 | 653.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1797.57 | 1281.98 | 515.59 | 2590.85 | 982.19 | 0.00 | 0.00 | 0.00 |
February | 1630.29 | 1055.26 | 575.03 | 2400.88 | 843.13 | 0.00 | 0.00 | 0.00 |
March | 1040.82 | 469.72 | 571.09 | 1573.73 | 750.62 | 0.00 | 0.00 | 0.00 |
April | 771.44 | 180.77 | 590.67 | 1282.31 | 500.24 | 0.00 | 0.00 | 0.00 |
May | 589.44 | 25.05 | 564.39 | 1204.47 | 147.04 | 0.00 | 0.00 | 0.00 |
June | 582.26 | 5.43 | 576.83 | 1226.59 | 127.06 | 0.00 | 0.00 | 0.00 |
July | 609.53 | 11.20 | 598.33 | 1273.61 | 82.39 | 0.00 | 0.00 | 0.00 |
August | 717.08 | 86.07 | 631.01 | 1510.61 | 120.75 | 0.00 | 0.00 | 0.00 |
September | 860.38 | 226.75 | 633.63 | 1674.10 | 172.88 | 0.00 | 0.00 | 0.00 |
October | 1334.89 | 695.35 | 639.54 | 2395.52 | 321.58 | 0.00 | 0.00 | 0.00 |
November | 1698.73 | 1169.59 | 529.14 | 2648.57 | 664.63 | 0.00 | 0.00 | 0.00 |
December | 1756.44 | 1261.38 | 495.06 | 2627.38 | 868.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1113.02 | 536.38 | 576.64 | 1864.75 | 463.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.26 | 5.43 | 495.06 | 1204.47 | 82.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1797.57 | 1281.98 | 639.54 | 2648.57 | 982.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.54 | 306.90 | 260.65 | 737.33 | 685.75 | 0.00 | 0.00 | 0.00 |
February | 642.58 | 325.24 | 317.35 | 864.92 | 582.35 | 0.00 | 0.00 | 0.00 |
March | 633.33 | 280.36 | 352.97 | 880.76 | 506.13 | 0.00 | 0.00 | 0.00 |
April | 786.62 | 361.86 | 424.76 | 1232.88 | 335.86 | 0.00 | 0.00 | 0.00 |
May | 654.16 | 213.10 | 441.07 | 1239.99 | 106.58 | 0.00 | 0.00 | 0.00 |
June | 726.70 | 254.82 | 471.89 | 1404.07 | 93.07 | 0.00 | 0.00 | 0.00 |
July | 663.34 | 184.00 | 479.34 | 1285.29 | 62.89 | 0.00 | 0.00 | 0.00 |
August | 670.72 | 205.32 | 465.41 | 1302.11 | 86.24 | 0.00 | 0.00 | 0.00 |
September | 617.62 | 211.87 | 405.75 | 1136.11 | 118.96 | 0.00 | 0.00 | 0.00 |
October | 632.32 | 273.22 | 359.10 | 1118.44 | 217.00 | 0.00 | 0.00 | 0.00 |
November | 541.97 | 272.37 | 269.60 | 800.14 | 456.69 | 0.00 | 0.00 | 0.00 |
December | 521.33 | 277.24 | 244.09 | 714.10 | 587.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 637.82 | 263.23 | 374.59 | 1060.36 | 318.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 521.33 | 184.00 | 244.09 | 714.10 | 62.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 786.62 | 361.86 | 479.34 | 1404.07 | 685.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 76.08 | 380.13 | 0.00 | 0.00 | 0.00 |
February | 122.29 | 0.00 | 122.29 | 107.26 | 312.64 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 155.35 | 260.96 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.75 | 239.95 | 159.23 | 0.00 | 0.00 | 0.00 |
May | 189.65 | 6.94 | 182.72 | 392.50 | 42.34 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.74 | 461.55 | 37.44 | 0.00 | 0.00 | 0.00 |
July | 209.30 | 7.97 | 201.33 | 442.19 | 26.32 | 0.00 | 0.00 | 0.00 |
August | 187.43 | 1.47 | 185.96 | 395.83 | 40.71 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 314.71 | 59.14 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 253.17 | 111.74 | 0.00 | 0.00 | 0.00 |
November | 106.80 | 0.00 | 106.80 | 114.75 | 251.64 | 0.00 | 0.00 | 0.00 |
December | 96.36 | 0.00 | 96.36 | 80.30 | 331.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.74 | 2.68 | 151.07 | 253.67 | 167.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.36 | 0.00 | 96.36 | 76.08 | 26.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 461.55 | 380.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 76.09 | 380.15 | 0.00 | 0.00 | 0.00 |
February | 122.30 | 0.00 | 122.30 | 107.27 | 312.66 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 155.35 | 260.97 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.76 | 239.96 | 159.24 | 0.00 | 0.00 | 0.00 |
May | 189.66 | 6.94 | 182.72 | 392.52 | 42.34 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.75 | 461.57 | 37.44 | 0.00 | 0.00 | 0.00 |
July | 209.31 | 7.97 | 201.33 | 442.21 | 26.32 | 0.00 | 0.00 | 0.00 |
August | 187.44 | 1.47 | 185.96 | 395.85 | 40.71 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 314.72 | 59.14 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 253.18 | 111.75 | 0.00 | 0.00 | 0.00 |
November | 106.81 | 0.00 | 106.81 | 114.76 | 251.66 | 0.00 | 0.00 | 0.00 |
December | 96.37 | 0.00 | 96.37 | 80.31 | 331.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.75 | 2.68 | 151.07 | 253.68 | 167.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.37 | 0.00 | 96.37 | 76.09 | 26.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 461.57 | 380.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 0.00 | 103.66 | 76.09 | 380.15 | 0.00 | 0.00 | 0.00 |
February | 122.30 | 0.00 | 122.30 | 107.27 | 312.66 | 0.00 | 0.00 | 0.00 |
March | 141.87 | 0.00 | 141.87 | 155.35 | 260.97 | 0.00 | 0.00 | 0.00 |
April | 167.44 | 0.69 | 166.76 | 239.96 | 159.24 | 0.00 | 0.00 | 0.00 |
May | 189.66 | 6.94 | 182.72 | 392.52 | 42.34 | 0.00 | 0.00 | 0.00 |
June | 215.68 | 14.93 | 200.75 | 461.57 | 37.44 | 0.00 | 0.00 | 0.00 |
July | 209.31 | 7.97 | 201.33 | 442.21 | 26.32 | 0.00 | 0.00 | 0.00 |
August | 187.44 | 1.47 | 185.96 | 395.85 | 40.71 | 0.00 | 0.00 | 0.00 |
September | 161.90 | 0.01 | 161.89 | 314.72 | 59.14 | 0.00 | 0.00 | 0.00 |
October | 140.69 | 0.00 | 140.69 | 253.18 | 111.75 | 0.00 | 0.00 | 0.00 |
November | 106.81 | 0.00 | 106.81 | 114.76 | 251.66 | 0.00 | 0.00 | 0.00 |
December | 96.37 | 0.00 | 96.37 | 80.31 | 331.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 153.75 | 2.68 | 151.07 | 253.68 | 167.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.37 | 0.00 | 96.37 | 76.09 | 26.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 215.68 | 14.93 | 201.33 | 461.57 | 380.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 513.27 | 261.36 | 251.91 | 608.87 | 700.95 | 0.00 | 0.00 | 0.00 |
February | 571.55 | 275.93 | 295.62 | 724.74 | 579.75 | 0.00 | 0.00 | 0.00 |
March | 672.33 | 324.24 | 348.08 | 927.79 | 490.86 | 0.00 | 0.00 | 0.00 |
April | 737.80 | 333.69 | 404.12 | 1155.29 | 313.54 | 0.00 | 0.00 | 0.00 |
May | 760.47 | 329.75 | 430.72 | 1419.28 | 89.93 | 0.00 | 0.00 | 0.00 |
June | 771.25 | 305.85 | 465.39 | 1486.47 | 78.29 | 0.00 | 0.00 | 0.00 |
July | 743.59 | 272.11 | 471.48 | 1429.44 | 56.56 | 0.00 | 0.00 | 0.00 |
August | 685.20 | 235.58 | 449.62 | 1314.29 | 84.66 | 0.00 | 0.00 | 0.00 |
September | 606.96 | 208.67 | 398.29 | 1109.18 | 121.06 | 0.00 | 0.00 | 0.00 |
October | 599.80 | 253.11 | 346.69 | 1042.34 | 218.19 | 0.00 | 0.00 | 0.00 |
November | 531.04 | 270.90 | 260.14 | 738.10 | 468.11 | 0.00 | 0.00 | 0.00 |
December | 418.11 | 189.39 | 228.72 | 516.89 | 620.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 634.50 | 271.59 | 362.90 | 1041.07 | 317.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 418.11 | 189.39 | 228.72 | 516.89 | 56.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 771.25 | 333.69 | 471.48 | 1486.47 | 700.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.29 | 10.33 | 9.96 | 24.07 | 27.71 | 0.00 | 0.00 | 0.00 |
February | 22.60 | 10.91 | 11.69 | 28.66 | 22.92 | 0.00 | 0.00 | 0.00 |
March | 26.58 | 12.82 | 13.76 | 36.68 | 19.41 | 0.00 | 0.00 | 0.00 |
April | 29.17 | 13.19 | 15.98 | 45.68 | 12.40 | 0.00 | 0.00 | 0.00 |
May | 30.07 | 13.04 | 17.03 | 56.12 | 3.56 | 0.00 | 0.00 | 0.00 |
June | 30.49 | 12.09 | 18.40 | 58.77 | 3.10 | 0.00 | 0.00 | 0.00 |
July | 29.40 | 10.76 | 18.64 | 56.52 | 2.24 | 0.00 | 0.00 | 0.00 |
August | 27.09 | 9.31 | 17.78 | 51.97 | 3.35 | 0.00 | 0.00 | 0.00 |
September | 24.00 | 8.25 | 15.75 | 43.86 | 4.79 | 0.00 | 0.00 | 0.00 |
October | 23.72 | 10.01 | 13.71 | 41.21 | 8.63 | 0.00 | 0.00 | 0.00 |
November | 21.00 | 10.71 | 10.29 | 29.18 | 18.51 | 0.00 | 0.00 | 0.00 |
December | 16.53 | 7.49 | 9.04 | 20.44 | 24.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25.09 | 10.74 | 14.35 | 41.16 | 12.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.53 | 7.49 | 9.04 | 20.44 | 2.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.49 | 13.19 | 18.64 | 58.77 | 27.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.18 | 427.32 | 171.86 | 865.53 | 366.19 | 0.00 | 0.00 | 0.00 |
February | 543.42 | 351.75 | 191.68 | 804.46 | 309.13 | 0.00 | 0.00 | 0.00 |
March | 346.93 | 156.57 | 190.36 | 533.94 | 260.18 | 0.00 | 0.00 | 0.00 |
April | 257.14 | 60.25 | 196.89 | 436.87 | 166.75 | 0.00 | 0.00 | 0.00 |
May | 196.48 | 8.35 | 188.13 | 409.54 | 44.28 | 0.00 | 0.00 | 0.00 |
June | 194.09 | 1.81 | 192.28 | 415.80 | 38.55 | 0.00 | 0.00 | 0.00 |
July | 203.18 | 3.73 | 199.44 | 429.89 | 26.26 | 0.00 | 0.00 | 0.00 |
August | 239.03 | 28.69 | 210.34 | 503.85 | 44.07 | 0.00 | 0.00 | 0.00 |
September | 286.79 | 75.58 | 211.21 | 559.72 | 65.65 | 0.00 | 0.00 | 0.00 |
October | 444.96 | 231.78 | 213.18 | 798.47 | 122.59 | 0.00 | 0.00 | 0.00 |
November | 566.23 | 389.86 | 176.38 | 881.50 | 253.81 | 0.00 | 0.00 | 0.00 |
December | 585.47 | 420.45 | 165.02 | 876.15 | 327.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.00 | 178.79 | 192.21 | 625.42 | 167.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.09 | 1.81 | 165.02 | 409.54 | 26.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.18 | 427.32 | 213.18 | 881.50 | 366.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.18 | 427.32 | 171.86 | 865.53 | 366.19 | 0.00 | 0.00 | 0.00 |
February | 543.42 | 351.75 | 191.68 | 804.46 | 309.13 | 0.00 | 0.00 | 0.00 |
March | 346.93 | 156.57 | 190.36 | 533.94 | 260.18 | 0.00 | 0.00 | 0.00 |
April | 257.14 | 60.25 | 196.89 | 436.87 | 166.75 | 0.00 | 0.00 | 0.00 |
May | 196.48 | 8.35 | 188.13 | 409.54 | 44.28 | 0.00 | 0.00 | 0.00 |
June | 194.09 | 1.81 | 192.28 | 415.80 | 38.55 | 0.00 | 0.00 | 0.00 |
July | 203.18 | 3.73 | 199.44 | 429.89 | 26.26 | 0.00 | 0.00 | 0.00 |
August | 239.03 | 28.69 | 210.34 | 503.85 | 44.07 | 0.00 | 0.00 | 0.00 |
September | 286.79 | 75.58 | 211.21 | 559.72 | 65.65 | 0.00 | 0.00 | 0.00 |
October | 444.96 | 231.78 | 213.18 | 798.47 | 122.59 | 0.00 | 0.00 | 0.00 |
November | 566.23 | 389.86 | 176.38 | 881.50 | 253.81 | 0.00 | 0.00 | 0.00 |
December | 585.47 | 420.45 | 165.02 | 876.15 | 327.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.00 | 178.79 | 192.21 | 625.42 | 167.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.09 | 1.81 | 165.02 | 409.54 | 26.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.18 | 427.32 | 213.18 | 881.50 | 366.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.14 | 427.29 | 171.85 | 865.48 | 366.17 | 0.00 | 0.00 | 0.00 |
February | 543.39 | 351.72 | 191.66 | 804.41 | 309.11 | 0.00 | 0.00 | 0.00 |
March | 346.91 | 156.56 | 190.35 | 533.90 | 260.17 | 0.00 | 0.00 | 0.00 |
April | 257.13 | 60.25 | 196.88 | 436.84 | 166.74 | 0.00 | 0.00 | 0.00 |
May | 196.46 | 8.35 | 188.12 | 409.52 | 44.28 | 0.00 | 0.00 | 0.00 |
June | 194.07 | 1.81 | 192.26 | 415.77 | 38.55 | 0.00 | 0.00 | 0.00 |
July | 203.16 | 3.73 | 199.43 | 429.87 | 26.26 | 0.00 | 0.00 | 0.00 |
August | 239.01 | 28.69 | 210.32 | 503.82 | 44.07 | 0.00 | 0.00 | 0.00 |
September | 286.77 | 75.58 | 211.20 | 559.68 | 65.64 | 0.00 | 0.00 | 0.00 |
October | 444.93 | 231.76 | 213.16 | 798.42 | 122.58 | 0.00 | 0.00 | 0.00 |
November | 566.20 | 389.83 | 176.37 | 881.44 | 253.79 | 0.00 | 0.00 | 0.00 |
December | 585.43 | 420.43 | 165.01 | 876.09 | 327.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 370.98 | 178.78 | 192.20 | 625.38 | 167.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.07 | 1.81 | 165.01 | 409.52 | 26.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.14 | 427.29 | 213.16 | 881.44 | 366.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 545.95 | 295.22 | 250.73 | 702.49 | 736.37 | 0.00 | 0.00 | 0.00 |
February | 618.14 | 312.86 | 305.27 | 832.36 | 614.54 | 0.00 | 0.00 | 0.00 |
March | 609.24 | 269.69 | 339.54 | 855.97 | 517.92 | 0.00 | 0.00 | 0.00 |
April | 756.69 | 348.09 | 408.60 | 1202.19 | 332.98 | 0.00 | 0.00 | 0.00 |
May | 629.27 | 204.99 | 424.29 | 1209.95 | 97.20 | 0.00 | 0.00 | 0.00 |
June | 699.05 | 245.12 | 453.93 | 1366.98 | 87.23 | 0.00 | 0.00 | 0.00 |
July | 638.10 | 177.00 | 461.10 | 1249.35 | 61.00 | 0.00 | 0.00 | 0.00 |
August | 645.20 | 197.50 | 447.70 | 1257.64 | 91.92 | 0.00 | 0.00 | 0.00 |
September | 594.12 | 203.81 | 390.31 | 1096.82 | 129.44 | 0.00 | 0.00 | 0.00 |
October | 608.26 | 262.82 | 345.44 | 1076.71 | 233.64 | 0.00 | 0.00 | 0.00 |
November | 521.35 | 262.01 | 259.34 | 762.06 | 499.18 | 0.00 | 0.00 | 0.00 |
December | 501.49 | 266.69 | 234.81 | 678.23 | 642.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.55 | 253.21 | 360.34 | 1024.90 | 335.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 501.49 | 177.00 | 234.81 | 678.23 | 61.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 756.69 | 348.09 | 461.10 | 1366.98 | 736.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.59 | 11.67 | 9.91 | 27.78 | 29.12 | 0.00 | 0.00 | 0.00 |
February | 24.44 | 12.37 | 12.07 | 32.91 | 24.30 | 0.00 | 0.00 | 0.00 |
March | 24.09 | 10.66 | 13.43 | 33.84 | 20.48 | 0.00 | 0.00 | 0.00 |
April | 29.92 | 13.76 | 16.16 | 47.53 | 13.17 | 0.00 | 0.00 | 0.00 |
May | 24.88 | 8.10 | 16.78 | 47.84 | 3.84 | 0.00 | 0.00 | 0.00 |
June | 27.64 | 9.69 | 17.95 | 54.05 | 3.45 | 0.00 | 0.00 | 0.00 |
July | 25.23 | 7.00 | 18.23 | 49.40 | 2.41 | 0.00 | 0.00 | 0.00 |
August | 25.51 | 7.81 | 17.70 | 49.73 | 3.63 | 0.00 | 0.00 | 0.00 |
September | 23.49 | 8.06 | 15.43 | 43.37 | 5.12 | 0.00 | 0.00 | 0.00 |
October | 24.05 | 10.39 | 13.66 | 42.57 | 9.24 | 0.00 | 0.00 | 0.00 |
November | 20.61 | 10.36 | 10.25 | 30.13 | 19.74 | 0.00 | 0.00 | 0.00 |
December | 19.83 | 10.54 | 9.28 | 26.82 | 25.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.26 | 10.01 | 14.25 | 40.52 | 13.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.83 | 7.00 | 9.28 | 26.82 | 2.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.92 | 13.76 | 18.23 | 54.05 | 29.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.99 | 0.00 | 310.99 | 226.82 | 1127.74 | 0.00 | 0.00 | 0.00 |
February | 366.89 | 0.00 | 366.89 | 310.63 | 947.36 | 0.00 | 0.00 | 0.00 |
March | 425.62 | 0.00 | 425.62 | 445.85 | 808.21 | 0.00 | 0.00 | 0.00 |
April | 502.33 | 2.06 | 500.27 | 696.88 | 506.20 | 0.00 | 0.00 | 0.00 |
May | 568.98 | 20.81 | 548.17 | 1159.17 | 144.86 | 0.00 | 0.00 | 0.00 |
June | 647.06 | 44.80 | 602.25 | 1371.01 | 123.91 | 0.00 | 0.00 | 0.00 |
July | 627.93 | 23.92 | 604.00 | 1318.79 | 84.15 | 0.00 | 0.00 | 0.00 |
August | 562.32 | 4.42 | 557.90 | 1191.70 | 117.38 | 0.00 | 0.00 | 0.00 |
September | 485.72 | 0.04 | 485.68 | 946.52 | 169.57 | 0.00 | 0.00 | 0.00 |
October | 422.08 | 0.00 | 422.08 | 763.45 | 323.21 | 0.00 | 0.00 | 0.00 |
November | 320.43 | 0.00 | 320.43 | 348.58 | 731.21 | 0.00 | 0.00 | 0.00 |
December | 289.10 | 0.00 | 289.10 | 244.08 | 966.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 461.25 | 8.03 | 453.22 | 754.61 | 501.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 289.10 | 0.00 | 289.10 | 226.82 | 84.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.06 | 44.80 | 604.00 | 1371.01 | 1127.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 533.58 | 271.70 | 261.88 | 629.04 | 702.59 | 0.00 | 0.00 | 0.00 |
February | 594.16 | 286.84 | 307.31 | 743.30 | 592.61 | 0.00 | 0.00 | 0.00 |
March | 698.92 | 337.07 | 361.85 | 948.19 | 510.37 | 0.00 | 0.00 | 0.00 |
April | 766.99 | 346.89 | 420.10 | 1182.03 | 332.14 | 0.00 | 0.00 | 0.00 |
May | 790.56 | 342.80 | 447.76 | 1459.11 | 98.71 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 317.95 | 483.80 | 1531.79 | 84.31 | 0.00 | 0.00 | 0.00 |
July | 773.01 | 282.88 | 490.13 | 1477.93 | 57.11 | 0.00 | 0.00 | 0.00 |
August | 712.30 | 244.90 | 467.41 | 1363.98 | 80.10 | 0.00 | 0.00 | 0.00 |
September | 630.97 | 216.93 | 414.04 | 1149.95 | 114.60 | 0.00 | 0.00 | 0.00 |
October | 623.53 | 263.13 | 360.40 | 1080.28 | 211.77 | 0.00 | 0.00 | 0.00 |
November | 552.04 | 281.62 | 270.42 | 765.73 | 460.69 | 0.00 | 0.00 | 0.00 |
December | 434.65 | 196.89 | 237.76 | 535.67 | 617.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 659.59 | 282.34 | 377.26 | 1074.02 | 320.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 434.65 | 196.89 | 237.76 | 535.67 | 57.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 801.76 | 346.89 | 490.13 | 1531.79 | 702.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1797.57 | 1281.98 | 515.59 | 2575.29 | 1049.88 | 0.00 | 0.00 | 0.00 |
February | 1630.29 | 1055.26 | 575.03 | 2387.21 | 901.27 | 0.00 | 0.00 | 0.00 |
March | 1040.82 | 469.72 | 571.09 | 1567.90 | 795.63 | 0.00 | 0.00 | 0.00 |
April | 771.44 | 180.77 | 590.67 | 1283.99 | 523.42 | 0.00 | 0.00 | 0.00 |
May | 589.44 | 25.05 | 564.39 | 1214.60 | 149.16 | 0.00 | 0.00 | 0.00 |
June | 582.26 | 5.43 | 576.83 | 1238.69 | 127.67 | 0.00 | 0.00 | 0.00 |
July | 609.53 | 11.20 | 598.33 | 1287.54 | 82.35 | 0.00 | 0.00 | 0.00 |
August | 717.08 | 86.07 | 631.01 | 1521.35 | 122.63 | 0.00 | 0.00 | 0.00 |
September | 860.38 | 226.75 | 633.63 | 1683.12 | 179.18 | 0.00 | 0.00 | 0.00 |
October | 1334.89 | 695.35 | 639.54 | 2400.73 | 336.23 | 0.00 | 0.00 | 0.00 |
November | 1698.73 | 1169.59 | 529.14 | 2640.04 | 707.68 | 0.00 | 0.00 | 0.00 |
December | 1756.44 | 1261.38 | 495.06 | 2615.43 | 930.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1113.02 | 536.38 | 576.64 | 1865.44 | 489.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.26 | 5.43 | 495.06 | 1214.60 | 82.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1797.57 | 1281.98 | 639.54 | 2640.04 | 1049.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 567.54 | 306.90 | 260.65 | 728.65 | 736.98 | 0.00 | 0.00 | 0.00 |
February | 642.58 | 325.24 | 317.35 | 857.38 | 626.31 | 0.00 | 0.00 | 0.00 |
March | 633.33 | 280.36 | 352.97 | 877.47 | 538.21 | 0.00 | 0.00 | 0.00 |
April | 786.62 | 361.86 | 424.76 | 1234.65 | 351.68 | 0.00 | 0.00 | 0.00 |
May | 654.16 | 213.10 | 441.07 | 1247.08 | 108.07 | 0.00 | 0.00 | 0.00 |
June | 726.70 | 254.82 | 471.89 | 1412.58 | 93.83 | 0.00 | 0.00 | 0.00 |
July | 663.34 | 184.00 | 479.34 | 1294.55 | 62.97 | 0.00 | 0.00 | 0.00 |
August | 670.72 | 205.32 | 465.41 | 1309.44 | 87.41 | 0.00 | 0.00 | 0.00 |
September | 617.62 | 211.87 | 405.75 | 1141.78 | 123.12 | 0.00 | 0.00 | 0.00 |
October | 632.32 | 273.22 | 359.10 | 1121.00 | 227.46 | 0.00 | 0.00 | 0.00 |
November | 541.97 | 272.37 | 269.60 | 794.46 | 491.16 | 0.00 | 0.00 | 0.00 |
December | 521.33 | 277.24 | 244.09 | 706.43 | 634.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 637.82 | 263.23 | 374.59 | 1061.19 | 338.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 521.33 | 184.00 | 244.09 | 706.43 | 62.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 786.62 | 361.86 | 479.34 | 1412.58 | 736.98 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.645576E+09 | 0.280347E+10 |
February | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.781648E+09 | 0.212263E+10 |
March | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.121500E+10 | 0.203168E+10 |
April | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.180840E+10 | 0.125068E+10 |
May | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.307825E+10 | 0.383184E+09 |
June | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.352198E+10 | 0.319208E+09 |
July | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.349553E+10 | 0.226153E+09 |
August | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.316553E+10 | 0.309334E+09 |
September | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.243172E+10 | 0.422850E+09 |
October | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.203894E+10 | 0.820309E+09 |
November | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.932541E+09 | 0.175167E+10 |
December | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.687892E+09 | 0.238935E+10 |
Annual Sum or Average | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.238030E+11 | 0.148305E+11 |
Minimum of Months | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.645576E+09 | 0.226153E+09 |
Maximum of Months | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.352198E+10 | 0.280347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.173233E+10 | 0.174901E+10 |
February | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.183553E+10 | 0.133347E+10 |
March | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.256312E+10 | 0.128915E+10 |
April | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.307174E+10 | 0.825126E+09 |
May | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.389779E+10 | 0.259479E+09 |
June | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.395871E+10 | 0.216292E+09 |
July | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.394370E+10 | 0.152054E+09 |
August | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.364465E+10 | 0.210216E+09 |
September | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.297507E+10 | 0.284978E+09 |
October | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.289618E+10 | 0.539203E+09 |
November | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.201418E+10 | 0.111446E+10 |
December | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.147238E+10 | 0.153093E+10 |
Annual Sum or Average | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.340054E+11 | 0.950438E+10 |
Minimum of Months | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.147238E+10 | 0.152054E+09 |
Maximum of Months | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.395871E+10 | 0.174901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.693934E+10 | 0.263069E+10 |
February | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.580821E+10 | 0.203970E+10 |
March | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.421508E+10 | 0.201045E+10 |
April | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.332376E+10 | 0.129661E+10 |
May | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.322605E+10 | 0.393834E+09 |
June | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.317933E+10 | 0.329346E+09 |
July | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.341123E+10 | 0.220668E+09 |
August | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.404601E+10 | 0.323415E+09 |
September | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.433927E+10 | 0.448106E+09 |
October | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.641617E+10 | 0.861324E+09 |
November | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.686509E+10 | 0.172271E+10 |
December | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.703718E+10 | 0.232531E+10 |
Annual Sum or Average | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.588067E+11 | 0.146022E+11 |
Minimum of Months | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.317933E+10 | 0.220668E+09 |
Maximum of Months | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.703718E+10 | 0.263069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.197488E+10 | 0.183672E+10 |
February | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.209242E+10 | 0.140881E+10 |
March | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.235902E+10 | 0.135561E+10 |
April | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.319563E+10 | 0.870555E+09 |
May | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.332120E+10 | 0.285461E+09 |
June | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.363935E+10 | 0.241227E+09 |
July | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.344251E+10 | 0.168447E+09 |
August | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.348758E+10 | 0.230977E+09 |
September | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.294480E+10 | 0.308352E+09 |
October | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.299563E+10 | 0.581205E+09 |
November | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.207396E+10 | 0.118375E+10 |
December | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.191265E+10 | 0.157385E+10 |
Annual Sum or Average | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.334396E+11 | 0.100450E+11 |
Minimum of Months | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.191265E+10 | 0.168447E+09 |
Maximum of Months | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.363935E+10 | 0.183672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277636E+09 | 0.00 | 0.277636E+09 | 0.203785E+09 | 0.101814E+10 |
February | 0.295846E+09 | 0.00 | 0.295846E+09 | 0.259490E+09 | 0.756334E+09 |
March | 0.379980E+09 | 0.00 | 0.379980E+09 | 0.416080E+09 | 0.698946E+09 |
April | 0.433993E+09 | 1781259.17 | 0.432212E+09 | 0.621945E+09 | 0.412726E+09 |
May | 0.507966E+09 | 18580228.25 | 0.489386E+09 | 0.105127E+10 | 0.113407E+09 |
June | 0.559031E+09 | 38708565.56 | 0.520323E+09 | 0.119635E+10 | 97035725.76 |
July | 0.560587E+09 | 21357348.22 | 0.539230E+09 | 0.118435E+10 | 70497905.83 |
August | 0.502016E+09 | 3948420.61 | 0.498068E+09 | 0.106020E+10 | 0.109038E+09 |
September | 0.419641E+09 | 32320.61 | 0.419609E+09 | 0.815729E+09 | 0.153295E+09 |
October | 0.376815E+09 | 0.00 | 0.376815E+09 | 0.678093E+09 | 0.299289E+09 |
November | 0.276835E+09 | 0.00 | 0.276835E+09 | 0.297433E+09 | 0.652260E+09 |
December | 0.258095E+09 | 0.00 | 0.258095E+09 | 0.215083E+09 | 0.886888E+09 |
Annual Sum or Average | 0.484844E+10 | 84408142.43 | 0.476403E+10 | 0.799980E+10 | 0.526785E+10 |
Minimum of Months | 0.258095E+09 | 0.00 | 0.258095E+09 | 0.203785E+09 | 70497905.83 |
Maximum of Months | 0.560587E+09 | 38708565.56 | 0.539230E+09 | 0.119635E+10 | 0.101814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277648E+09 | 0.00 | 0.277648E+09 | 0.203792E+09 | 0.101820E+10 |
February | 0.295859E+09 | 0.00 | 0.295859E+09 | 0.259501E+09 | 0.756378E+09 |
March | 0.379995E+09 | 0.00 | 0.379995E+09 | 0.416097E+09 | 0.698987E+09 |
April | 0.434011E+09 | 1781307.06 | 0.432230E+09 | 0.621973E+09 | 0.412748E+09 |
May | 0.507986E+09 | 18580727.69 | 0.489405E+09 | 0.105132E+10 | 0.113411E+09 |
June | 0.559053E+09 | 38709606.06 | 0.520344E+09 | 0.119640E+10 | 97039228.32 |
July | 0.560609E+09 | 21357922.31 | 0.539251E+09 | 0.118441E+10 | 70499882.92 |
August | 0.502036E+09 | 3948526.74 | 0.498087E+09 | 0.106025E+10 | 0.109042E+09 |
September | 0.419658E+09 | 32321.48 | 0.419625E+09 | 0.815766E+09 | 0.153302E+09 |
October | 0.376830E+09 | 0.00 | 0.376830E+09 | 0.678125E+09 | 0.299305E+09 |
November | 0.276846E+09 | 0.00 | 0.276846E+09 | 0.297446E+09 | 0.652296E+09 |
December | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.215091E+09 | 0.886941E+09 |
Annual Sum or Average | 0.484864E+10 | 84410411.34 | 0.476423E+10 | 0.800016E+10 | 0.526815E+10 |
Minimum of Months | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.203792E+09 | 70499882.92 |
Maximum of Months | 0.560609E+09 | 38709606.06 | 0.539251E+09 | 0.119640E+10 | 0.101820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277648E+09 | 0.00 | 0.277648E+09 | 0.203792E+09 | 0.101820E+10 |
February | 0.295859E+09 | 0.00 | 0.295859E+09 | 0.259501E+09 | 0.756378E+09 |
March | 0.379995E+09 | 0.00 | 0.379995E+09 | 0.416097E+09 | 0.698987E+09 |
April | 0.434011E+09 | 1781307.06 | 0.432230E+09 | 0.621973E+09 | 0.412748E+09 |
May | 0.507986E+09 | 18580727.69 | 0.489405E+09 | 0.105132E+10 | 0.113411E+09 |
June | 0.559053E+09 | 38709606.06 | 0.520344E+09 | 0.119640E+10 | 97039228.32 |
July | 0.560609E+09 | 21357922.31 | 0.539251E+09 | 0.118441E+10 | 70499882.92 |
August | 0.502036E+09 | 3948526.74 | 0.498087E+09 | 0.106025E+10 | 0.109042E+09 |
September | 0.419658E+09 | 32321.48 | 0.419625E+09 | 0.815766E+09 | 0.153302E+09 |
October | 0.376830E+09 | 0.00 | 0.376830E+09 | 0.678125E+09 | 0.299305E+09 |
November | 0.276846E+09 | 0.00 | 0.276846E+09 | 0.297446E+09 | 0.652296E+09 |
December | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.215091E+09 | 0.886941E+09 |
Annual Sum or Average | 0.484864E+10 | 84410411.34 | 0.476423E+10 | 0.800016E+10 | 0.526815E+10 |
Minimum of Months | 0.258105E+09 | 0.00 | 0.258105E+09 | 0.203792E+09 | 70499882.92 |
Maximum of Months | 0.560609E+09 | 38709606.06 | 0.539251E+09 | 0.119640E+10 | 0.101820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137475E+10 | 0.700026E+09 | 0.674726E+09 | 0.163080E+10 | 0.187743E+10 |
February | 0.138269E+10 | 0.667522E+09 | 0.715166E+09 | 0.175330E+10 | 0.140253E+10 |
March | 0.180076E+10 | 0.868455E+09 | 0.932307E+09 | 0.248500E+10 | 0.131471E+10 |
April | 0.191238E+10 | 0.864914E+09 | 0.104747E+10 | 0.299451E+10 | 0.812690E+09 |
May | 0.203686E+10 | 0.883215E+09 | 0.115364E+10 | 0.380140E+10 | 0.240862E+09 |
June | 0.199908E+10 | 0.792776E+09 | 0.120630E+10 | 0.385293E+10 | 0.202935E+09 |
July | 0.199164E+10 | 0.728831E+09 | 0.126281E+10 | 0.382862E+10 | 0.151480E+09 |
August | 0.183524E+10 | 0.630966E+09 | 0.120427E+10 | 0.352019E+10 | 0.226740E+09 |
September | 0.157324E+10 | 0.540873E+09 | 0.103237E+10 | 0.287499E+10 | 0.313788E+09 |
October | 0.160651E+10 | 0.677939E+09 | 0.928571E+09 | 0.279179E+10 | 0.584399E+09 |
November | 0.137645E+10 | 0.702179E+09 | 0.674272E+09 | 0.191316E+10 | 0.121335E+10 |
December | 0.111986E+10 | 0.507271E+09 | 0.612592E+09 | 0.138445E+10 | 0.166166E+10 |
Annual Sum or Average | 0.200095E+11 | 0.856497E+10 | 0.114445E+11 | 0.328311E+11 | 0.100026E+11 |
Minimum of Months | 0.111986E+10 | 0.507271E+09 | 0.612592E+09 | 0.138445E+10 | 0.151480E+09 |
Maximum of Months | 0.203686E+10 | 0.883215E+09 | 0.126281E+10 | 0.385293E+10 | 0.187743E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54356471.35 | 27678409.29 | 26678062.06 | 64480283.82 | 74231725.82 |
February | 54670229.54 | 26393225.09 | 28277004.45 | 69323756.69 | 55454731.05 |
March | 71200526.16 | 34337934.61 | 36862591.55 | 98254561.61 | 51982359.90 |
April | 75613838.40 | 34197916.95 | 41415921.45 | 0.118400E+09 | 32133033.97 |
May | 80535422.58 | 34921542.05 | 45613880.53 | 0.150304E+09 | 9523446.98 |
June | 79041780.87 | 31345643.89 | 47696136.98 | 0.152341E+09 | 8023853.25 |
July | 78747816.69 | 28817334.57 | 49930482.12 | 0.151380E+09 | 5989376.36 |
August | 72563678.74 | 24947839.83 | 47615838.90 | 0.139185E+09 | 8965109.99 |
September | 62204597.61 | 21385642.69 | 40818954.92 | 0.113675E+09 | 12406894.25 |
October | 63519959.84 | 26805108.71 | 36714851.13 | 0.110385E+09 | 23106618.36 |
November | 54423616.40 | 27763514.35 | 26660102.05 | 75644603.38 | 47974815.28 |
December | 44278388.28 | 20057044.62 | 24221343.66 | 54739754.98 | 65700698.96 |
Annual Sum or Average | 0.791156E+09 | 0.338651E+09 | 0.452505E+09 | 0.129811E+10 | 0.395493E+09 |
Minimum of Months | 44278388.28 | 20057044.62 | 24221343.66 | 54739754.98 | 5989376.36 |
Maximum of Months | 80535422.58 | 34921542.05 | 49930482.12 | 0.152341E+09 | 74231725.82 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160484E+10 | 0.114453E+10 | 0.460314E+09 | 0.231824E+10 | 0.980800E+09 |
February | 0.131465E+10 | 0.850946E+09 | 0.463701E+09 | 0.194615E+10 | 0.747851E+09 |
March | 0.929226E+09 | 0.419358E+09 | 0.509868E+09 | 0.143009E+10 | 0.696877E+09 |
April | 0.666517E+09 | 0.156180E+09 | 0.510337E+09 | 0.113236E+10 | 0.432210E+09 |
May | 0.526244E+09 | 22364338.43 | 0.503879E+09 | 0.109692E+10 | 0.118605E+09 |
June | 0.503070E+09 | 4689036.20 | 0.498381E+09 | 0.107775E+10 | 99917659.82 |
July | 0.544187E+09 | 10001971.24 | 0.534185E+09 | 0.115143E+10 | 70332353.53 |
August | 0.640205E+09 | 76843168.97 | 0.563362E+09 | 0.134950E+10 | 0.118033E+09 |
September | 0.743358E+09 | 0.195905E+09 | 0.547453E+09 | 0.145078E+10 | 0.170157E+09 |
October | 0.119177E+10 | 0.620796E+09 | 0.570972E+09 | 0.213862E+10 | 0.328346E+09 |
November | 0.146768E+10 | 0.101051E+10 | 0.457169E+09 | 0.228485E+10 | 0.657878E+09 |
December | 0.156813E+10 | 0.112614E+10 | 0.441984E+09 | 0.234667E+10 | 0.875941E+09 |
Annual Sum or Average | 0.116999E+11 | 0.563826E+10 | 0.606161E+10 | 0.197234E+11 | 0.529695E+10 |
Minimum of Months | 0.503070E+09 | 4689036.20 | 0.441984E+09 | 0.107775E+10 | 70332353.53 |
Maximum of Months | 0.160484E+10 | 0.114453E+10 | 0.570972E+09 | 0.234667E+10 | 0.980800E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160484E+10 | 0.114453E+10 | 0.460314E+09 | 0.231824E+10 | 0.980800E+09 |
February | 0.131465E+10 | 0.850946E+09 | 0.463701E+09 | 0.194615E+10 | 0.747851E+09 |
March | 0.929226E+09 | 0.419358E+09 | 0.509868E+09 | 0.143009E+10 | 0.696877E+09 |
April | 0.666517E+09 | 0.156180E+09 | 0.510337E+09 | 0.113236E+10 | 0.432210E+09 |
May | 0.526244E+09 | 22364338.43 | 0.503879E+09 | 0.109692E+10 | 0.118605E+09 |
June | 0.503070E+09 | 4689036.20 | 0.498381E+09 | 0.107775E+10 | 99917659.82 |
July | 0.544187E+09 | 10001971.24 | 0.534185E+09 | 0.115143E+10 | 70332353.53 |
August | 0.640205E+09 | 76843168.97 | 0.563362E+09 | 0.134950E+10 | 0.118033E+09 |
September | 0.743358E+09 | 0.195905E+09 | 0.547453E+09 | 0.145078E+10 | 0.170157E+09 |
October | 0.119177E+10 | 0.620796E+09 | 0.570972E+09 | 0.213862E+10 | 0.328346E+09 |
November | 0.146768E+10 | 0.101051E+10 | 0.457169E+09 | 0.228485E+10 | 0.657878E+09 |
December | 0.156813E+10 | 0.112614E+10 | 0.441984E+09 | 0.234667E+10 | 0.875941E+09 |
Annual Sum or Average | 0.116999E+11 | 0.563826E+10 | 0.606161E+10 | 0.197234E+11 | 0.529695E+10 |
Minimum of Months | 0.503070E+09 | 4689036.20 | 0.441984E+09 | 0.107775E+10 | 70332353.53 |
Maximum of Months | 0.160484E+10 | 0.114453E+10 | 0.570972E+09 | 0.234667E+10 | 0.980800E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160474E+10 | 0.114446E+10 | 0.460285E+09 | 0.231810E+10 | 0.980738E+09 |
February | 0.131456E+10 | 0.850892E+09 | 0.463672E+09 | 0.194603E+10 | 0.747804E+09 |
March | 0.929168E+09 | 0.419332E+09 | 0.509836E+09 | 0.143000E+10 | 0.696833E+09 |
April | 0.666475E+09 | 0.156170E+09 | 0.510305E+09 | 0.113229E+10 | 0.432183E+09 |
May | 0.526210E+09 | 22362925.13 | 0.503848E+09 | 0.109685E+10 | 0.118598E+09 |
June | 0.503039E+09 | 4688739.88 | 0.498350E+09 | 0.107768E+10 | 99911345.59 |
July | 0.544152E+09 | 10001339.17 | 0.534151E+09 | 0.115136E+10 | 70327908.92 |
August | 0.640165E+09 | 76838312.92 | 0.563327E+09 | 0.134942E+10 | 0.118026E+09 |
September | 0.743311E+09 | 0.195893E+09 | 0.547419E+09 | 0.145069E+10 | 0.170146E+09 |
October | 0.119169E+10 | 0.620756E+09 | 0.570936E+09 | 0.213849E+10 | 0.328325E+09 |
November | 0.146758E+10 | 0.101044E+10 | 0.457140E+09 | 0.228470E+10 | 0.657836E+09 |
December | 0.156803E+10 | 0.112607E+10 | 0.441956E+09 | 0.234652E+10 | 0.875886E+09 |
Annual Sum or Average | 0.116991E+11 | 0.563790E+10 | 0.606122E+10 | 0.197221E+11 | 0.529661E+10 |
Minimum of Months | 0.503039E+09 | 4688739.88 | 0.441956E+09 | 0.107768E+10 | 70327908.92 |
Maximum of Months | 0.160474E+10 | 0.114446E+10 | 0.570936E+09 | 0.234652E+10 | 0.980738E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146227E+10 | 0.790712E+09 | 0.671557E+09 | 0.188154E+10 | 0.197228E+10 |
February | 0.149539E+10 | 0.756873E+09 | 0.738521E+09 | 0.201364E+10 | 0.148669E+10 |
March | 0.163178E+10 | 0.722344E+09 | 0.909433E+09 | 0.229262E+10 | 0.138720E+10 |
April | 0.196133E+10 | 0.902246E+09 | 0.105909E+10 | 0.311608E+10 | 0.863083E+09 |
May | 0.168545E+10 | 0.549036E+09 | 0.113641E+10 | 0.324073E+10 | 0.260341E+09 |
June | 0.181194E+10 | 0.635350E+09 | 0.117659E+10 | 0.354321E+10 | 0.226089E+09 |
July | 0.170910E+10 | 0.474075E+09 | 0.123502E+10 | 0.334625E+10 | 0.163387E+09 |
August | 0.172811E+10 | 0.528997E+09 | 0.119912E+10 | 0.336846E+10 | 0.246196E+09 |
September | 0.153997E+10 | 0.528281E+09 | 0.101169E+10 | 0.284297E+10 | 0.335501E+09 |
October | 0.162916E+10 | 0.703941E+09 | 0.925222E+09 | 0.288385E+10 | 0.625789E+09 |
November | 0.135134E+10 | 0.679128E+09 | 0.672214E+09 | 0.197525E+10 | 0.129389E+10 |
December | 0.134320E+10 | 0.714295E+09 | 0.628908E+09 | 0.181658E+10 | 0.171995E+10 |
Annual Sum or Average | 0.193491E+11 | 0.798528E+10 | 0.113638E+11 | 0.323212E+11 | 0.105804E+11 |
Minimum of Months | 0.134320E+10 | 0.474075E+09 | 0.628908E+09 | 0.181658E+10 | 0.163387E+09 |
Maximum of Months | 0.196133E+10 | 0.902246E+09 | 0.123502E+10 | 0.354321E+10 | 0.197228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 57816631.47 | 31263925.13 | 26552706.35 | 74394198.34 | 77982206.40 |
February | 59126367.15 | 29925980.13 | 29200387.02 | 79617265.80 | 58782480.30 |
March | 64518822.28 | 28560742.89 | 35958079.39 | 90648017.74 | 54848790.87 |
April | 77549088.27 | 35673885.36 | 41875202.92 | 0.123207E+09 | 34125516.53 |
May | 66641001.52 | 21708327.14 | 44932674.37 | 0.128135E+09 | 10293642.77 |
June | 71642423.28 | 25121088.99 | 46521334.29 | 0.140095E+09 | 8939354.85 |
July | 67576012.84 | 18744438.16 | 48831574.67 | 0.132307E+09 | 6460152.28 |
August | 68327895.74 | 20916000.03 | 47411895.71 | 0.133186E+09 | 9734354.47 |
September | 60888769.33 | 20887671.24 | 40001098.09 | 0.112408E+09 | 13265382.40 |
October | 64415458.14 | 27833093.60 | 36582364.54 | 0.114024E+09 | 24743124.81 |
November | 53430703.01 | 26852018.34 | 26578684.67 | 78099516.90 | 51159102.34 |
December | 53108910.18 | 28242496.52 | 24866413.65 | 71825596.24 | 68005316.20 |
Annual Sum or Average | 0.765042E+09 | 0.315730E+09 | 0.449312E+09 | 0.127795E+10 | 0.418339E+09 |
Minimum of Months | 53108910.18 | 18744438.16 | 24866413.65 | 71825596.24 | 6460152.28 |
Maximum of Months | 77549088.27 | 35673885.36 | 48831574.67 | 0.140095E+09 | 77982206.40 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.607526E+09 | 0.302053E+10 |
February | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.751482E+09 | 0.229186E+10 |
March | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.119416E+10 | 0.216471E+10 |
April | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.180631E+10 | 0.131208E+10 |
May | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.310473E+10 | 0.387987E+09 |
June | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.355367E+10 | 0.321164E+09 |
July | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.353224E+10 | 0.225388E+09 |
August | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.319186E+10 | 0.314402E+09 |
September | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.245337E+10 | 0.439520E+09 |
October | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.204482E+10 | 0.865690E+09 |
November | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.903517E+09 | 0.189530E+10 |
December | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.653733E+09 | 0.258928E+10 |
Annual Sum or Average | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.237974E+11 | 0.158279E+11 |
Minimum of Months | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.607526E+09 | 0.225388E+09 |
Maximum of Months | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.355367E+10 | 0.302053E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.168483E+10 | 0.188183E+10 |
February | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.179820E+10 | 0.143364E+10 |
March | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.253962E+10 | 0.136698E+10 |
April | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.306381E+10 | 0.860900E+09 |
May | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.390808E+10 | 0.264384E+09 |
June | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.397040E+10 | 0.218520E+09 |
July | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.395849E+10 | 0.152972E+09 |
August | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.365329E+10 | 0.214543E+09 |
September | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.298067E+10 | 0.297053E+09 |
October | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.289342E+10 | 0.567217E+09 |
November | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.198477E+10 | 0.119412E+10 |
December | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.143473E+10 | 0.165359E+10 |
Annual Sum or Average | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.338703E+11 | 0.101058E+11 |
Minimum of Months | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.143473E+10 | 0.152972E+09 |
Maximum of Months | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.397040E+10 | 0.188183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.689765E+10 | 0.281199E+10 |
February | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.577514E+10 | 0.218035E+10 |
March | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.419945E+10 | 0.213101E+10 |
April | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.332810E+10 | 0.135670E+10 |
May | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.325318E+10 | 0.399509E+09 |
June | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.321069E+10 | 0.330931E+09 |
July | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.344855E+10 | 0.220562E+09 |
August | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.407479E+10 | 0.328451E+09 |
September | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.436265E+10 | 0.464422E+09 |
October | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.643010E+10 | 0.900571E+09 |
November | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.684298E+10 | 0.183430E+10 |
December | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.700518E+10 | 0.249147E+10 |
Annual Sum or Average | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.588284E+11 | 0.154503E+11 |
Minimum of Months | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.321069E+10 | 0.220562E+09 |
Maximum of Months | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.700518E+10 | 0.281199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.195161E+10 | 0.197393E+10 |
February | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.207417E+10 | 0.151516E+10 |
March | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.235022E+10 | 0.144155E+10 |
April | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.320022E+10 | 0.911547E+09 |
May | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.334017E+10 | 0.289450E+09 |
June | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.366140E+10 | 0.243212E+09 |
July | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.346733E+10 | 0.168672E+09 |
August | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.350721E+10 | 0.234123E+09 |
September | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.295949E+10 | 0.319114E+09 |
October | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.300249E+10 | 0.609223E+09 |
November | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.205924E+10 | 0.127308E+10 |
December | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.189210E+10 | 0.169896E+10 |
Annual Sum or Average | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.334656E+11 | 0.106780E+11 |
Minimum of Months | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.189210E+10 | 0.168672E+09 |
Maximum of Months | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.366140E+10 | 0.197393E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 241.03 | 1046.70 | 310.99 | 0.00 | 310.99 | 0.00 | 0.00 |
February | 323.10 | 877.41 | 366.89 | 0.00 | 366.89 | 0.00 | 0.00 |
March | 453.63 | 758.54 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 697.68 | 482.51 | 502.33 | 2.06 | 500.27 | 0.00 | 0.00 |
May | 1149.29 | 143.06 | 568.98 | 20.81 | 548.17 | 0.00 | 0.00 |
June | 1358.79 | 123.15 | 647.06 | 44.80 | 602.25 | 0.00 | 0.00 |
July | 1305.08 | 84.44 | 627.93 | 23.92 | 604.00 | 0.00 | 0.00 |
August | 1181.87 | 115.49 | 562.32 | 4.42 | 557.90 | 0.00 | 0.00 |
September | 938.16 | 163.14 | 485.72 | 0.04 | 485.68 | 0.00 | 0.00 |
October | 761.25 | 306.27 | 422.08 | 0.00 | 422.08 | 0.00 | 0.00 |
November | 359.78 | 675.80 | 320.43 | 0.00 | 320.43 | 0.00 | 0.00 |
December | 256.83 | 892.08 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Annual Sum or Average | 754.79 | 470.27 | 461.25 | 8.03 | 453.22 | 0.00 | 0.00 |
Minimum of Months | 241.03 | 84.44 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Maximum of Months | 1358.79 | 1046.70 | 647.06 | 44.80 | 604.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 646.78 | 653.01 | 533.58 | 271.70 | 261.88 | 0.00 | 0.00 |
February | 758.73 | 551.20 | 594.16 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 956.96 | 481.31 | 698.92 | 337.07 | 361.85 | 0.00 | 0.00 |
April | 1185.09 | 318.34 | 766.99 | 346.89 | 420.10 | 0.00 | 0.00 |
May | 1455.27 | 96.88 | 790.56 | 342.80 | 447.76 | 0.00 | 0.00 |
June | 1527.28 | 83.45 | 801.76 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1472.41 | 56.77 | 773.01 | 282.88 | 490.13 | 0.00 | 0.00 |
August | 1360.76 | 78.49 | 712.30 | 244.90 | 467.41 | 0.00 | 0.00 |
September | 1147.79 | 109.95 | 630.97 | 216.93 | 414.04 | 0.00 | 0.00 |
October | 1081.31 | 201.32 | 623.53 | 263.13 | 360.40 | 0.00 | 0.00 |
November | 777.08 | 429.96 | 552.04 | 281.62 | 270.42 | 0.00 | 0.00 |
December | 549.72 | 571.58 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1078.30 | 301.38 | 659.59 | 282.34 | 377.26 | 0.00 | 0.00 |
Minimum of Months | 549.72 | 56.77 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1527.28 | 653.01 | 801.76 | 346.89 | 490.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2590.85 | 982.19 | 1797.57 | 1281.98 | 515.59 | 0.00 | 0.00 |
February | 2400.88 | 843.13 | 1630.29 | 1055.26 | 575.03 | 0.00 | 0.00 |
March | 1573.73 | 750.62 | 1040.82 | 469.72 | 571.09 | 0.00 | 0.00 |
April | 1282.31 | 500.24 | 771.44 | 180.77 | 590.67 | 0.00 | 0.00 |
May | 1204.47 | 147.04 | 589.44 | 25.05 | 564.39 | 0.00 | 0.00 |
June | 1226.59 | 127.06 | 582.26 | 5.43 | 576.83 | 0.00 | 0.00 |
July | 1273.61 | 82.39 | 609.53 | 11.20 | 598.33 | 0.00 | 0.00 |
August | 1510.61 | 120.75 | 717.08 | 86.07 | 631.01 | 0.00 | 0.00 |
September | 1674.10 | 172.88 | 860.38 | 226.75 | 633.63 | 0.00 | 0.00 |
October | 2395.52 | 321.58 | 1334.89 | 695.35 | 639.54 | 0.00 | 0.00 |
November | 2648.57 | 664.63 | 1698.73 | 1169.59 | 529.14 | 0.00 | 0.00 |
December | 2627.38 | 868.17 | 1756.44 | 1261.38 | 495.06 | 0.00 | 0.00 |
Annual Sum or Average | 1864.75 | 463.03 | 1113.02 | 536.38 | 576.64 | 0.00 | 0.00 |
Minimum of Months | 1204.47 | 82.39 | 582.26 | 5.43 | 495.06 | 0.00 | 0.00 |
Maximum of Months | 2648.57 | 982.19 | 1797.57 | 1281.98 | 639.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 737.33 | 685.75 | 567.54 | 306.90 | 260.65 | 0.00 | 0.00 |
February | 864.92 | 582.35 | 642.58 | 325.24 | 317.35 | 0.00 | 0.00 |
March | 880.76 | 506.13 | 633.33 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1232.88 | 335.86 | 786.62 | 361.86 | 424.76 | 0.00 | 0.00 |
May | 1239.99 | 106.58 | 654.16 | 213.10 | 441.07 | 0.00 | 0.00 |
June | 1404.07 | 93.07 | 726.70 | 254.82 | 471.89 | 0.00 | 0.00 |
July | 1285.29 | 62.89 | 663.34 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1302.11 | 86.24 | 670.72 | 205.32 | 465.41 | 0.00 | 0.00 |
September | 1136.11 | 118.96 | 617.62 | 211.87 | 405.75 | 0.00 | 0.00 |
October | 1118.44 | 217.00 | 632.32 | 273.22 | 359.10 | 0.00 | 0.00 |
November | 800.14 | 456.69 | 541.97 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 714.10 | 587.61 | 521.33 | 277.24 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1060.36 | 318.52 | 637.82 | 263.23 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 714.10 | 62.89 | 521.33 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1404.07 | 685.75 | 786.62 | 361.86 | 479.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.26 | 1140.43 | 310.98 | 0.00 | 310.98 | 0.00 | 0.00 |
February | 321.80 | 937.95 | 366.88 | 0.00 | 366.88 | 0.00 | 0.00 |
March | 466.05 | 782.90 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 719.86 | 477.71 | 502.32 | 2.06 | 500.26 | 0.00 | 0.00 |
May | 1177.53 | 127.03 | 568.97 | 20.81 | 548.16 | 0.00 | 0.00 |
June | 1384.70 | 112.31 | 647.04 | 44.80 | 602.24 | 0.00 | 0.00 |
July | 1326.60 | 78.96 | 627.91 | 23.92 | 603.99 | 0.00 | 0.00 |
August | 1187.54 | 122.13 | 562.31 | 4.42 | 557.89 | 0.00 | 0.00 |
September | 944.16 | 177.43 | 485.71 | 0.04 | 485.67 | 0.00 | 0.00 |
October | 759.54 | 335.24 | 422.07 | 0.00 | 422.07 | 0.00 | 0.00 |
November | 344.26 | 754.96 | 320.42 | 0.00 | 320.42 | 0.00 | 0.00 |
December | 240.91 | 993.42 | 289.09 | 0.00 | 289.09 | 0.00 | 0.00 |
Annual Sum or Average | 761.04 | 501.15 | 461.24 | 8.03 | 453.21 | 0.00 | 0.00 |
Minimum of Months | 228.26 | 78.96 | 289.09 | 0.00 | 289.09 | 0.00 | 0.00 |
Maximum of Months | 1384.70 | 1140.43 | 647.04 | 44.80 | 603.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 632.94 | 728.67 | 533.57 | 271.69 | 261.87 | 0.00 | 0.00 |
February | 753.40 | 602.67 | 594.15 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 964.48 | 510.26 | 698.91 | 337.06 | 361.85 | 0.00 | 0.00 |
April | 1200.97 | 325.93 | 766.97 | 346.88 | 420.09 | 0.00 | 0.00 |
May | 1475.40 | 93.48 | 790.54 | 342.79 | 447.75 | 0.00 | 0.00 |
June | 1545.24 | 81.39 | 801.74 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1485.96 | 58.79 | 773.00 | 282.87 | 490.12 | 0.00 | 0.00 |
August | 1366.26 | 88.00 | 712.29 | 244.89 | 467.40 | 0.00 | 0.00 |
September | 1153.04 | 125.85 | 630.96 | 216.92 | 414.04 | 0.00 | 0.00 |
October | 1083.55 | 226.82 | 623.52 | 263.12 | 360.40 | 0.00 | 0.00 |
November | 767.29 | 486.62 | 552.03 | 281.61 | 270.42 | 0.00 | 0.00 |
December | 537.33 | 644.92 | 434.64 | 196.88 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1082.23 | 329.72 | 659.58 | 282.33 | 377.25 | 0.00 | 0.00 |
Minimum of Months | 537.33 | 58.79 | 434.64 | 196.88 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1545.24 | 728.67 | 801.74 | 346.88 | 490.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2596.54 | 1098.54 | 1797.50 | 1281.93 | 515.57 | 0.00 | 0.00 |
February | 2413.34 | 927.38 | 1630.23 | 1055.22 | 575.01 | 0.00 | 0.00 |
March | 1601.77 | 780.54 | 1040.78 | 469.70 | 571.08 | 0.00 | 0.00 |
April | 1310.58 | 500.23 | 771.42 | 180.76 | 590.66 | 0.00 | 0.00 |
May | 1228.60 | 132.84 | 589.42 | 25.05 | 564.37 | 0.00 | 0.00 |
June | 1247.37 | 115.64 | 582.25 | 5.43 | 576.82 | 0.00 | 0.00 |
July | 1289.66 | 78.78 | 609.52 | 11.20 | 598.31 | 0.00 | 0.00 |
August | 1511.51 | 132.20 | 717.06 | 86.07 | 630.99 | 0.00 | 0.00 |
September | 1679.11 | 196.94 | 860.35 | 226.74 | 633.61 | 0.00 | 0.00 |
October | 2395.36 | 367.76 | 1334.84 | 695.32 | 639.52 | 0.00 | 0.00 |
November | 2644.44 | 761.42 | 1698.66 | 1169.54 | 529.12 | 0.00 | 0.00 |
December | 2628.38 | 981.10 | 1756.38 | 1261.33 | 495.04 | 0.00 | 0.00 |
Annual Sum or Average | 1876.23 | 503.88 | 1112.98 | 536.35 | 576.62 | 0.00 | 0.00 |
Minimum of Months | 1228.60 | 78.78 | 582.25 | 5.43 | 495.04 | 0.00 | 0.00 |
Maximum of Months | 2644.44 | 1098.54 | 1797.50 | 1281.93 | 639.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 730.26 | 765.48 | 567.53 | 306.89 | 260.64 | 0.00 | 0.00 |
February | 865.27 | 638.84 | 642.58 | 325.23 | 317.35 | 0.00 | 0.00 |
March | 889.81 | 538.40 | 633.32 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1249.73 | 346.15 | 786.61 | 361.85 | 424.75 | 0.00 | 0.00 |
May | 1257.79 | 101.04 | 654.16 | 213.09 | 441.06 | 0.00 | 0.00 |
June | 1421.03 | 90.67 | 726.69 | 254.81 | 471.88 | 0.00 | 0.00 |
July | 1298.74 | 63.41 | 663.33 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1307.36 | 95.55 | 670.71 | 205.31 | 465.40 | 0.00 | 0.00 |
September | 1140.19 | 134.55 | 617.61 | 211.87 | 405.74 | 0.00 | 0.00 |
October | 1119.28 | 242.88 | 632.31 | 273.21 | 359.10 | 0.00 | 0.00 |
November | 792.19 | 518.92 | 541.96 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 705.05 | 667.55 | 521.32 | 277.23 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1065.42 | 348.77 | 637.81 | 263.22 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 705.05 | 63.41 | 521.32 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1421.03 | 765.48 | 786.61 | 361.85 | 479.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 226.82 | 1127.74 | 310.99 | 0.00 | 310.99 | 0.00 | 0.00 |
February | 310.63 | 947.36 | 366.89 | 0.00 | 366.89 | 0.00 | 0.00 |
March | 445.85 | 808.21 | 425.62 | 0.00 | 425.62 | 0.00 | 0.00 |
April | 696.88 | 506.20 | 502.33 | 2.06 | 500.27 | 0.00 | 0.00 |
May | 1159.17 | 144.86 | 568.98 | 20.81 | 548.17 | 0.00 | 0.00 |
June | 1371.01 | 123.91 | 647.06 | 44.80 | 602.25 | 0.00 | 0.00 |
July | 1318.79 | 84.15 | 627.93 | 23.92 | 604.00 | 0.00 | 0.00 |
August | 1191.70 | 117.38 | 562.32 | 4.42 | 557.90 | 0.00 | 0.00 |
September | 946.52 | 169.57 | 485.72 | 0.04 | 485.68 | 0.00 | 0.00 |
October | 763.45 | 323.21 | 422.08 | 0.00 | 422.08 | 0.00 | 0.00 |
November | 348.58 | 731.21 | 320.43 | 0.00 | 320.43 | 0.00 | 0.00 |
December | 244.08 | 966.73 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Annual Sum or Average | 754.61 | 501.90 | 461.25 | 8.03 | 453.22 | 0.00 | 0.00 |
Minimum of Months | 226.82 | 84.15 | 289.10 | 0.00 | 289.10 | 0.00 | 0.00 |
Maximum of Months | 1371.01 | 1127.74 | 647.06 | 44.80 | 604.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 629.04 | 702.59 | 533.58 | 271.70 | 261.88 | 0.00 | 0.00 |
February | 743.30 | 592.61 | 594.16 | 286.84 | 307.31 | 0.00 | 0.00 |
March | 948.19 | 510.37 | 698.92 | 337.07 | 361.85 | 0.00 | 0.00 |
April | 1182.03 | 332.14 | 766.99 | 346.89 | 420.10 | 0.00 | 0.00 |
May | 1459.11 | 98.71 | 790.56 | 342.80 | 447.76 | 0.00 | 0.00 |
June | 1531.79 | 84.31 | 801.76 | 317.95 | 483.80 | 0.00 | 0.00 |
July | 1477.93 | 57.11 | 773.01 | 282.88 | 490.13 | 0.00 | 0.00 |
August | 1363.98 | 80.10 | 712.30 | 244.90 | 467.41 | 0.00 | 0.00 |
September | 1149.95 | 114.60 | 630.97 | 216.93 | 414.04 | 0.00 | 0.00 |
October | 1080.28 | 211.77 | 623.53 | 263.13 | 360.40 | 0.00 | 0.00 |
November | 765.73 | 460.69 | 552.04 | 281.62 | 270.42 | 0.00 | 0.00 |
December | 535.67 | 617.38 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Annual Sum or Average | 1074.02 | 320.45 | 659.59 | 282.34 | 377.26 | 0.00 | 0.00 |
Minimum of Months | 535.67 | 57.11 | 434.65 | 196.89 | 237.76 | 0.00 | 0.00 |
Maximum of Months | 1531.79 | 702.59 | 801.76 | 346.89 | 490.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2575.29 | 1049.88 | 1797.57 | 1281.98 | 515.59 | 0.00 | 0.00 |
February | 2387.21 | 901.27 | 1630.29 | 1055.26 | 575.03 | 0.00 | 0.00 |
March | 1567.90 | 795.63 | 1040.82 | 469.72 | 571.09 | 0.00 | 0.00 |
April | 1283.99 | 523.42 | 771.44 | 180.77 | 590.67 | 0.00 | 0.00 |
May | 1214.60 | 149.16 | 589.44 | 25.05 | 564.39 | 0.00 | 0.00 |
June | 1238.69 | 127.67 | 582.26 | 5.43 | 576.83 | 0.00 | 0.00 |
July | 1287.54 | 82.35 | 609.53 | 11.20 | 598.33 | 0.00 | 0.00 |
August | 1521.35 | 122.63 | 717.08 | 86.07 | 631.01 | 0.00 | 0.00 |
September | 1683.12 | 179.18 | 860.38 | 226.75 | 633.63 | 0.00 | 0.00 |
October | 2400.73 | 336.23 | 1334.89 | 695.35 | 639.54 | 0.00 | 0.00 |
November | 2640.04 | 707.68 | 1698.73 | 1169.59 | 529.14 | 0.00 | 0.00 |
December | 2615.43 | 930.21 | 1756.44 | 1261.38 | 495.06 | 0.00 | 0.00 |
Annual Sum or Average | 1865.44 | 489.92 | 1113.02 | 536.38 | 576.64 | 0.00 | 0.00 |
Minimum of Months | 1214.60 | 82.35 | 582.26 | 5.43 | 495.06 | 0.00 | 0.00 |
Maximum of Months | 2640.04 | 1049.88 | 1797.57 | 1281.98 | 639.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 728.65 | 736.98 | 567.54 | 306.90 | 260.65 | 0.00 | 0.00 |
February | 857.38 | 626.31 | 642.58 | 325.24 | 317.35 | 0.00 | 0.00 |
March | 877.47 | 538.21 | 633.33 | 280.36 | 352.97 | 0.00 | 0.00 |
April | 1234.65 | 351.68 | 786.62 | 361.86 | 424.76 | 0.00 | 0.00 |
May | 1247.08 | 108.07 | 654.16 | 213.10 | 441.07 | 0.00 | 0.00 |
June | 1412.58 | 93.83 | 726.70 | 254.82 | 471.89 | 0.00 | 0.00 |
July | 1294.55 | 62.97 | 663.34 | 184.00 | 479.34 | 0.00 | 0.00 |
August | 1309.44 | 87.41 | 670.72 | 205.32 | 465.41 | 0.00 | 0.00 |
September | 1141.78 | 123.12 | 617.62 | 211.87 | 405.75 | 0.00 | 0.00 |
October | 1121.00 | 227.46 | 632.32 | 273.22 | 359.10 | 0.00 | 0.00 |
November | 794.46 | 491.16 | 541.97 | 272.37 | 269.60 | 0.00 | 0.00 |
December | 706.43 | 634.32 | 521.33 | 277.24 | 244.09 | 0.00 | 0.00 |
Annual Sum or Average | 1061.19 | 338.60 | 637.82 | 263.23 | 374.59 | 0.00 | 0.00 |
Minimum of Months | 706.43 | 62.97 | 521.33 | 184.00 | 244.09 | 0.00 | 0.00 |
Maximum of Months | 1412.58 | 736.98 | 786.62 | 361.86 | 479.34 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.645576E+09 | 0.280347E+10 | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.00 | 0.00 |
February | 0.781648E+09 | 0.212263E+10 | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.00 | 0.00 |
March | 0.121500E+10 | 0.203168E+10 | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.00 | 0.00 |
April | 0.180840E+10 | 0.125068E+10 | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.00 | 0.00 |
May | 0.307825E+10 | 0.383184E+09 | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.00 | 0.00 |
June | 0.352198E+10 | 0.319208E+09 | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.00 | 0.00 |
July | 0.349553E+10 | 0.226153E+09 | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.00 | 0.00 |
August | 0.316553E+10 | 0.309334E+09 | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.00 | 0.00 |
September | 0.243172E+10 | 0.422850E+09 | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.00 | 0.00 |
October | 0.203894E+10 | 0.820309E+09 | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.00 | 0.00 |
November | 0.932541E+09 | 0.175167E+10 | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.00 | 0.00 |
December | 0.687892E+09 | 0.238935E+10 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.238030E+11 | 0.148305E+11 | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.645576E+09 | 0.226153E+09 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.352198E+10 | 0.280347E+10 | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173233E+10 | 0.174901E+10 | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.00 | 0.00 |
February | 0.183553E+10 | 0.133347E+10 | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.00 | 0.00 |
March | 0.256312E+10 | 0.128915E+10 | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.00 | 0.00 |
April | 0.307174E+10 | 0.825126E+09 | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.00 | 0.00 |
May | 0.389779E+10 | 0.259479E+09 | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.00 | 0.00 |
June | 0.395871E+10 | 0.216292E+09 | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.00 | 0.00 |
July | 0.394370E+10 | 0.152054E+09 | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.00 | 0.00 |
August | 0.364465E+10 | 0.210216E+09 | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.00 | 0.00 |
September | 0.297507E+10 | 0.284978E+09 | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.00 | 0.00 |
October | 0.289618E+10 | 0.539203E+09 | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.00 | 0.00 |
November | 0.201418E+10 | 0.111446E+10 | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.00 | 0.00 |
December | 0.147238E+10 | 0.153093E+10 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.340054E+11 | 0.950438E+10 | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147238E+10 | 0.152054E+09 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.395871E+10 | 0.174901E+10 | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.693934E+10 | 0.263069E+10 | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.00 | 0.00 |
February | 0.580821E+10 | 0.203970E+10 | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.00 | 0.00 |
March | 0.421508E+10 | 0.201045E+10 | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.00 | 0.00 |
April | 0.332376E+10 | 0.129661E+10 | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.00 | 0.00 |
May | 0.322605E+10 | 0.393834E+09 | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.00 | 0.00 |
June | 0.317933E+10 | 0.329346E+09 | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.00 | 0.00 |
July | 0.341123E+10 | 0.220668E+09 | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.00 | 0.00 |
August | 0.404601E+10 | 0.323415E+09 | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.00 | 0.00 |
September | 0.433927E+10 | 0.448106E+09 | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.00 | 0.00 |
October | 0.641617E+10 | 0.861324E+09 | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.686509E+10 | 0.172271E+10 | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.00 | 0.00 |
December | 0.703718E+10 | 0.232531E+10 | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.588067E+11 | 0.146022E+11 | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.317933E+10 | 0.220668E+09 | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.703718E+10 | 0.263069E+10 | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.197488E+10 | 0.183672E+10 | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.00 | 0.00 |
February | 0.209242E+10 | 0.140881E+10 | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.00 | 0.00 |
March | 0.235902E+10 | 0.135561E+10 | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.00 | 0.00 |
April | 0.319563E+10 | 0.870555E+09 | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.00 | 0.00 |
May | 0.332120E+10 | 0.285461E+09 | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.00 | 0.00 |
June | 0.363935E+10 | 0.241227E+09 | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.00 | 0.00 |
July | 0.344251E+10 | 0.168447E+09 | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.00 | 0.00 |
August | 0.348758E+10 | 0.230977E+09 | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.00 | 0.00 |
September | 0.294480E+10 | 0.308352E+09 | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.00 | 0.00 |
October | 0.299563E+10 | 0.581205E+09 | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.00 | 0.00 |
November | 0.207396E+10 | 0.118375E+10 | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.00 | 0.00 |
December | 0.191265E+10 | 0.157385E+10 | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334396E+11 | 0.100450E+11 | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191265E+10 | 0.168447E+09 | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363935E+10 | 0.183672E+10 | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611369E+09 | 0.305454E+10 | 0.832932E+09 | 0.00 | 0.832932E+09 | 0.00 | 0.00 |
February | 0.778491E+09 | 0.226909E+10 | 0.887563E+09 | 0.00 | 0.887563E+09 | 0.00 | 0.00 |
March | 0.124828E+10 | 0.209692E+10 | 0.113997E+10 | 0.00 | 0.113997E+10 | 0.00 | 0.00 |
April | 0.186589E+10 | 0.123822E+10 | 0.130202E+10 | 5343873.29 | 0.129667E+10 | 0.00 | 0.00 |
May | 0.315390E+10 | 0.340230E+09 | 0.152394E+10 | 55741683.63 | 0.146820E+10 | 0.00 | 0.00 |
June | 0.358915E+10 | 0.291114E+09 | 0.167714E+10 | 0.116128E+09 | 0.156101E+10 | 0.00 | 0.00 |
July | 0.355316E+10 | 0.211498E+09 | 0.168181E+10 | 64073192.84 | 0.161773E+10 | 0.00 | 0.00 |
August | 0.318070E+10 | 0.327122E+09 | 0.150609E+10 | 11845474.09 | 0.149424E+10 | 0.00 | 0.00 |
September | 0.244726E+10 | 0.459899E+09 | 0.125896E+10 | 96963.58 | 0.125886E+10 | 0.00 | 0.00 |
October | 0.203434E+10 | 0.897899E+09 | 0.113048E+10 | 0.00 | 0.113048E+10 | 0.00 | 0.00 |
November | 0.892325E+09 | 0.195685E+10 | 0.830528E+09 | 0.00 | 0.830528E+09 | 0.00 | 0.00 |
December | 0.645265E+09 | 0.266077E+10 | 0.774305E+09 | 0.00 | 0.774305E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.240001E+11 | 0.158042E+11 | 0.145457E+11 | 0.253229E+09 | 0.142925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.611369E+09 | 0.211498E+09 | 0.774305E+09 | 0.00 | 0.774305E+09 | 0.00 | 0.00 |
Maximum of Months | 0.358915E+10 | 0.305454E+10 | 0.168181E+10 | 0.116128E+09 | 0.161773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169528E+10 | 0.195166E+10 | 0.142911E+10 | 0.727705E+09 | 0.701404E+09 | 0.00 | 0.00 |
February | 0.182262E+10 | 0.145798E+10 | 0.143736E+10 | 0.693915E+09 | 0.743443E+09 | 0.00 | 0.00 |
March | 0.258325E+10 | 0.136669E+10 | 0.187196E+10 | 0.902793E+09 | 0.969170E+09 | 0.00 | 0.00 |
April | 0.311291E+10 | 0.844823E+09 | 0.198800E+10 | 0.899112E+09 | 0.108888E+10 | 0.00 | 0.00 |
May | 0.395170E+10 | 0.250385E+09 | 0.211739E+10 | 0.918137E+09 | 0.119925E+10 | 0.00 | 0.00 |
June | 0.400527E+10 | 0.210959E+09 | 0.207812E+10 | 0.824122E+09 | 0.125400E+10 | 0.00 | 0.00 |
July | 0.398000E+10 | 0.157469E+09 | 0.207039E+10 | 0.757649E+09 | 0.131274E+10 | 0.00 | 0.00 |
August | 0.365938E+10 | 0.235705E+09 | 0.190780E+10 | 0.655914E+09 | 0.125189E+10 | 0.00 | 0.00 |
September | 0.298867E+10 | 0.326195E+09 | 0.163545E+10 | 0.562259E+09 | 0.107319E+10 | 0.00 | 0.00 |
October | 0.290218E+10 | 0.607506E+09 | 0.167003E+10 | 0.704744E+09 | 0.965286E+09 | 0.00 | 0.00 |
November | 0.198880E+10 | 0.126133E+10 | 0.143087E+10 | 0.729942E+09 | 0.700932E+09 | 0.00 | 0.00 |
December | 0.143919E+10 | 0.172736E+10 | 0.116414E+10 | 0.527328E+09 | 0.636814E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341292E+11 | 0.103981E+11 | 0.208006E+11 | 0.890362E+10 | 0.118970E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143919E+10 | 0.157469E+09 | 0.116414E+10 | 0.527328E+09 | 0.636814E+09 | 0.00 | 0.00 |
Maximum of Months | 0.400527E+10 | 0.195166E+10 | 0.211739E+10 | 0.918137E+09 | 0.131274E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.695458E+10 | 0.294234E+10 | 0.481442E+10 | 0.343351E+10 | 0.138091E+10 | 0.00 | 0.00 |
February | 0.583834E+10 | 0.224351E+10 | 0.394386E+10 | 0.255278E+10 | 0.139107E+10 | 0.00 | 0.00 |
March | 0.429019E+10 | 0.209059E+10 | 0.278762E+10 | 0.125805E+10 | 0.152957E+10 | 0.00 | 0.00 |
April | 0.339702E+10 | 0.129660E+10 | 0.199951E+10 | 0.468529E+09 | 0.153098E+10 | 0.00 | 0.00 |
May | 0.329068E+10 | 0.355809E+09 | 0.157870E+10 | 67091601.99 | 0.151161E+10 | 0.00 | 0.00 |
June | 0.323318E+10 | 0.299747E+09 | 0.150918E+10 | 14066812.28 | 0.149511E+10 | 0.00 | 0.00 |
July | 0.345421E+10 | 0.210993E+09 | 0.163253E+10 | 30005281.65 | 0.160252E+10 | 0.00 | 0.00 |
August | 0.404843E+10 | 0.354092E+09 | 0.192058E+10 | 0.230525E+09 | 0.169005E+10 | 0.00 | 0.00 |
September | 0.435225E+10 | 0.510459E+09 | 0.223003E+10 | 0.587703E+09 | 0.164233E+10 | 0.00 | 0.00 |
October | 0.641573E+10 | 0.985017E+09 | 0.357523E+10 | 0.186235E+10 | 0.171288E+10 | 0.00 | 0.00 |
November | 0.685440E+10 | 0.197359E+10 | 0.440294E+10 | 0.303146E+10 | 0.137148E+10 | 0.00 | 0.00 |
December | 0.703986E+10 | 0.262777E+10 | 0.470428E+10 | 0.337835E+10 | 0.132592E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.591689E+11 | 0.158905E+11 | 0.350989E+11 | 0.169144E+11 | 0.181844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323318E+10 | 0.210993E+09 | 0.150918E+10 | 14066812.28 | 0.132592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.703986E+10 | 0.294234E+10 | 0.481442E+10 | 0.343351E+10 | 0.171288E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195594E+10 | 0.205026E+10 | 0.152009E+10 | 0.821976E+09 | 0.698110E+09 | 0.00 | 0.00 |
February | 0.209326E+10 | 0.154548E+10 | 0.155452E+10 | 0.786799E+09 | 0.767721E+09 | 0.00 | 0.00 |
March | 0.238327E+10 | 0.144205E+10 | 0.169630E+10 | 0.750905E+09 | 0.945391E+09 | 0.00 | 0.00 |
April | 0.323929E+10 | 0.897209E+09 | 0.203888E+10 | 0.937920E+09 | 0.110096E+10 | 0.00 | 0.00 |
May | 0.336886E+10 | 0.270635E+09 | 0.175209E+10 | 0.570745E+09 | 0.118135E+10 | 0.00 | 0.00 |
June | 0.368331E+10 | 0.235029E+09 | 0.188359E+10 | 0.660471E+09 | 0.122311E+10 | 0.00 | 0.00 |
July | 0.347856E+10 | 0.169847E+09 | 0.177667E+10 | 0.492819E+09 | 0.128385E+10 | 0.00 | 0.00 |
August | 0.350165E+10 | 0.255930E+09 | 0.179644E+10 | 0.549913E+09 | 0.124653E+10 | 0.00 | 0.00 |
September | 0.295538E+10 | 0.348766E+09 | 0.160086E+10 | 0.549168E+09 | 0.105169E+10 | 0.00 | 0.00 |
October | 0.299787E+10 | 0.650532E+09 | 0.169358E+10 | 0.731774E+09 | 0.961804E+09 | 0.00 | 0.00 |
November | 0.205335E+10 | 0.134505E+10 | 0.140477E+10 | 0.705980E+09 | 0.698793E+09 | 0.00 | 0.00 |
December | 0.188840E+10 | 0.178796E+10 | 0.139631E+10 | 0.742538E+09 | 0.653775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335991E+11 | 0.109987E+11 | 0.201141E+11 | 0.830101E+10 | 0.118131E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188840E+10 | 0.169847E+09 | 0.139631E+10 | 0.492819E+09 | 0.653775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.368331E+10 | 0.205026E+10 | 0.203888E+10 | 0.937920E+09 | 0.128385E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.607526E+09 | 0.302053E+10 | 0.832949E+09 | 0.00 | 0.832949E+09 | 0.00 | 0.00 |
February | 0.751482E+09 | 0.229186E+10 | 0.887580E+09 | 0.00 | 0.887580E+09 | 0.00 | 0.00 |
March | 0.119416E+10 | 0.216471E+10 | 0.113999E+10 | 0.00 | 0.113999E+10 | 0.00 | 0.00 |
April | 0.180631E+10 | 0.131208E+10 | 0.130204E+10 | 5344030.36 | 0.129670E+10 | 0.00 | 0.00 |
May | 0.310473E+10 | 0.387987E+09 | 0.152397E+10 | 55743322.08 | 0.146823E+10 | 0.00 | 0.00 |
June | 0.355367E+10 | 0.321164E+09 | 0.167717E+10 | 0.116131E+09 | 0.156104E+10 | 0.00 | 0.00 |
July | 0.353224E+10 | 0.225388E+09 | 0.168184E+10 | 64075076.18 | 0.161777E+10 | 0.00 | 0.00 |
August | 0.319186E+10 | 0.314402E+09 | 0.150612E+10 | 11845822.27 | 0.149427E+10 | 0.00 | 0.00 |
September | 0.245337E+10 | 0.439520E+09 | 0.125898E+10 | 96966.43 | 0.125889E+10 | 0.00 | 0.00 |
October | 0.204482E+10 | 0.865690E+09 | 0.113050E+10 | 0.00 | 0.113050E+10 | 0.00 | 0.00 |
November | 0.903517E+09 | 0.189530E+10 | 0.830544E+09 | 0.00 | 0.830544E+09 | 0.00 | 0.00 |
December | 0.653733E+09 | 0.258928E+10 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237974E+11 | 0.158279E+11 | 0.145460E+11 | 0.253236E+09 | 0.142928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.607526E+09 | 0.225388E+09 | 0.774320E+09 | 0.00 | 0.774320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355367E+10 | 0.302053E+10 | 0.168184E+10 | 0.116131E+09 | 0.161777E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168483E+10 | 0.188183E+10 | 0.142913E+10 | 0.727719E+09 | 0.701412E+09 | 0.00 | 0.00 |
February | 0.179820E+10 | 0.143364E+10 | 0.143738E+10 | 0.693929E+09 | 0.743451E+09 | 0.00 | 0.00 |
March | 0.253962E+10 | 0.136698E+10 | 0.187199E+10 | 0.902811E+09 | 0.969182E+09 | 0.00 | 0.00 |
April | 0.306381E+10 | 0.860900E+09 | 0.198803E+10 | 0.899129E+09 | 0.108890E+10 | 0.00 | 0.00 |
May | 0.390808E+10 | 0.264384E+09 | 0.211742E+10 | 0.918155E+09 | 0.119927E+10 | 0.00 | 0.00 |
June | 0.397040E+10 | 0.218520E+09 | 0.207815E+10 | 0.824138E+09 | 0.125401E+10 | 0.00 | 0.00 |
July | 0.395849E+10 | 0.152972E+09 | 0.207042E+10 | 0.757663E+09 | 0.131276E+10 | 0.00 | 0.00 |
August | 0.365329E+10 | 0.214543E+09 | 0.190783E+10 | 0.655927E+09 | 0.125190E+10 | 0.00 | 0.00 |
September | 0.298067E+10 | 0.297053E+09 | 0.163547E+10 | 0.562270E+09 | 0.107320E+10 | 0.00 | 0.00 |
October | 0.289342E+10 | 0.567217E+09 | 0.167006E+10 | 0.704758E+09 | 0.965297E+09 | 0.00 | 0.00 |
November | 0.198477E+10 | 0.119412E+10 | 0.143090E+10 | 0.729957E+09 | 0.700940E+09 | 0.00 | 0.00 |
December | 0.143473E+10 | 0.165359E+10 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.338703E+11 | 0.101058E+11 | 0.208009E+11 | 0.890379E+10 | 0.118971E+11 | 0.00 | 0.00 |
Minimum of Months | 0.143473E+10 | 0.152972E+09 | 0.116416E+10 | 0.527339E+09 | 0.636821E+09 | 0.00 | 0.00 |
Maximum of Months | 0.397040E+10 | 0.188183E+10 | 0.211742E+10 | 0.918155E+09 | 0.131276E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.689765E+10 | 0.281199E+10 | 0.481461E+10 | 0.343365E+10 | 0.138096E+10 | 0.00 | 0.00 |
February | 0.577514E+10 | 0.218035E+10 | 0.394401E+10 | 0.255289E+10 | 0.139112E+10 | 0.00 | 0.00 |
March | 0.419945E+10 | 0.213101E+10 | 0.278772E+10 | 0.125810E+10 | 0.152962E+10 | 0.00 | 0.00 |
April | 0.332810E+10 | 0.135670E+10 | 0.199957E+10 | 0.468549E+09 | 0.153102E+10 | 0.00 | 0.00 |
May | 0.325318E+10 | 0.399509E+09 | 0.157874E+10 | 67094386.23 | 0.151165E+10 | 0.00 | 0.00 |
June | 0.321069E+10 | 0.330931E+09 | 0.150922E+10 | 14067396.04 | 0.149515E+10 | 0.00 | 0.00 |
July | 0.344855E+10 | 0.220562E+09 | 0.163257E+10 | 30006526.85 | 0.160257E+10 | 0.00 | 0.00 |
August | 0.407479E+10 | 0.328451E+09 | 0.192064E+10 | 0.230534E+09 | 0.169010E+10 | 0.00 | 0.00 |
September | 0.436265E+10 | 0.464422E+09 | 0.223010E+10 | 0.587727E+09 | 0.164238E+10 | 0.00 | 0.00 |
October | 0.643010E+10 | 0.900571E+09 | 0.357536E+10 | 0.186243E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.684298E+10 | 0.183430E+10 | 0.440311E+10 | 0.303158E+10 | 0.137152E+10 | 0.00 | 0.00 |
December | 0.700518E+10 | 0.249147E+10 | 0.470446E+10 | 0.337849E+10 | 0.132597E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.588284E+11 | 0.154503E+11 | 0.351001E+11 | 0.169151E+11 | 0.181850E+11 | 0.00 | 0.00 |
Minimum of Months | 0.321069E+10 | 0.220562E+09 | 0.150922E+10 | 14067396.04 | 0.132597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.700518E+10 | 0.281199E+10 | 0.481461E+10 | 0.343365E+10 | 0.171294E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195161E+10 | 0.197393E+10 | 0.152011E+10 | 0.821989E+09 | 0.698116E+09 | 0.00 | 0.00 |
February | 0.207417E+10 | 0.151516E+10 | 0.155454E+10 | 0.786812E+09 | 0.767728E+09 | 0.00 | 0.00 |
March | 0.235022E+10 | 0.144155E+10 | 0.169632E+10 | 0.750917E+09 | 0.945400E+09 | 0.00 | 0.00 |
April | 0.320022E+10 | 0.911547E+09 | 0.203891E+10 | 0.937935E+09 | 0.110097E+10 | 0.00 | 0.00 |
May | 0.334017E+10 | 0.289450E+09 | 0.175211E+10 | 0.570754E+09 | 0.118136E+10 | 0.00 | 0.00 |
June | 0.366140E+10 | 0.243212E+09 | 0.188361E+10 | 0.660482E+09 | 0.122313E+10 | 0.00 | 0.00 |
July | 0.346733E+10 | 0.168672E+09 | 0.177670E+10 | 0.492828E+09 | 0.128387E+10 | 0.00 | 0.00 |
August | 0.350721E+10 | 0.234123E+09 | 0.179646E+10 | 0.549922E+09 | 0.124654E+10 | 0.00 | 0.00 |
September | 0.295949E+10 | 0.319114E+09 | 0.160088E+10 | 0.549177E+09 | 0.105170E+10 | 0.00 | 0.00 |
October | 0.300249E+10 | 0.609223E+09 | 0.169360E+10 | 0.731786E+09 | 0.961814E+09 | 0.00 | 0.00 |
November | 0.205924E+10 | 0.127308E+10 | 0.140479E+10 | 0.705992E+09 | 0.698799E+09 | 0.00 | 0.00 |
December | 0.189210E+10 | 0.169896E+10 | 0.139633E+10 | 0.742550E+09 | 0.653781E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334656E+11 | 0.106780E+11 | 0.201143E+11 | 0.830114E+10 | 0.118132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189210E+10 | 0.168672E+09 | 0.139633E+10 | 0.492828E+09 | 0.653781E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366140E+10 | 0.197393E+10 | 0.203891E+10 | 0.937935E+09 | 0.128387E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.396893E+10 | -0.373481E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234115194.6 | 60.05 | 0.00 | 0.00 |
February | 0.357881E+10 | -0.336766E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -211149561.8 | 60.05 | 0.00 | 0.00 |
March | 0.407116E+10 | -0.383734E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233827346.2 | 60.05 | 0.00 | 0.00 |
April | 0.347148E+10 | -0.324696E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224518675.5 | 60.05 | 0.00 | 0.00 |
May | 0.347767E+10 | -0.324585E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231817877.5 | 60.05 | 0.00 | 0.00 |
June | 0.325430E+10 | -0.302960E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224704577.8 | 60.05 | 0.00 | 0.00 |
July | 0.299739E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231922825.2 | 60.05 | 0.00 | 0.00 |
August | 0.332349E+10 | -0.309126E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232232215.7 | 60.05 | 0.00 | 0.00 |
September | 0.314698E+10 | -0.292240E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224583257.9 | 60.05 | 0.00 | 0.00 |
October | 0.346401E+10 | -0.323242E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231591238.0 | 60.05 | 0.00 | 0.00 |
November | 0.362882E+10 | -0.340406E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224756814.1 | 60.05 | 0.00 | 0.00 |
December | 0.377954E+10 | -0.354630E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233240835.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.421626E+11 | -0.394241E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273846E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.299739E+10 | -0.383734E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234115194.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.407116E+10 | -0.276547E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -211149561.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7752.17 | 36.70 | 297.50 | 296.00 | 1463.51 | 25.13 | 176.33 | 279.17 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3354.93 | 27.25 | 165.50 | 279.00 | 1216.03 | 20.64 | 107.67 | 260.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1553.90 | 18.36 | 0.00 | 319.33 | 924.33 | 20.54 | 111.50 | 281.00 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1220.34 | 17.62 | 0.00 | 322.00 | 712.27 | 19.75 | 87.33 | 282.50 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 1084.81 | 17.86 | 0.00 | 347.83 | 616.06 | 20.03 | 62.67 | 297.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:00 | 1028.54 | 17.50 | 0.00 | 349.00 | 587.18 | 19.67 | 44.83 | 301.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1138.50 | 17.85 | 0.00 | 359.00 | 631.07 | 20.00 | 87.50 | 311.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1329.04 | 18.14 | 0.00 | 345.50 | 724.05 | 20.27 | 134.17 | 307.17 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1571.23 | 18.29 | 0.00 | 316.83 | 845.87 | 20.44 | 154.50 | 281.50 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2660.56 | 21.04 | 39.33 | 313.33 | 1159.99 | 21.60 | 186.83 | 283.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7818.87 | 36.12 | 297.00 | 287.67 | 1313.55 | 22.82 | 143.50 | 268.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7903.44 | 37.49 | 279.33 | 284.17 | 1853.63 | 27.07 | 170.83 | 267.17 |
Annual Sum or Average | 4027.67 | 0.51 | 2993.28 | 23.07 | 1078.67 | 3819.67 | 968.87 | 21.33 | 1467.67 | 3422.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1028.54 | 17.50 | 0.00 | 279.00 | 587.18 | 19.67 | 44.83 | 260.67 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7903.44 | 37.49 | 297.50 | 359.00 | 1853.63 | 27.07 | 186.83 | 311.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1895.54 | 19.70 | 81.50 | 267.33 | 1067.49 | 22.40 | 74.67 | 214.50 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2172.26 | 21.58 | 89.67 | 257.83 | 1160.69 | 22.44 | 66.33 | 223.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2227.11 | 20.17 | 74.33 | 313.00 | 1175.53 | 21.09 | 48.00 | 270.83 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2314.44 | 20.42 | 95.83 | 323.00 | 1236.42 | 21.46 | 68.00 | 289.50 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2610.40 | 21.08 | 106.00 | 356.67 | 1048.11 | 20.58 | 49.50 | 310.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2336.78 | 20.52 | 114.00 | 355.83 | 996.87 | 21.11 | 62.67 | 317.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2257.38 | 20.78 | 112.33 | 362.33 | 978.77 | 20.53 | 53.67 | 314.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2081.18 | 20.69 | 105.17 | 345.83 | 1092.32 | 21.82 | 76.00 | 304.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 1983.51 | 20.76 | 95.00 | 312.50 | 1024.74 | 21.85 | 67.67 | 275.00 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2048.79 | 20.23 | 79.17 | 299.33 | 1068.50 | 21.95 | 58.17 | 266.17 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1721.23 | 20.55 | 84.00 | 261.83 | 890.18 | 21.31 | 57.00 | 224.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1853.89 | 21.40 | 89.17 | 252.83 | 996.52 | 22.12 | 66.50 | 202.33 |
Annual Sum or Average | 4027.67 | 0.51 | 2138.63 | 20.65 | 1126.17 | 3708.33 | 1059.89 | 21.52 | 748.17 | 3212.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1721.23 | 19.70 | 74.33 | 252.83 | 890.18 | 20.53 | 48.00 | 202.33 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2610.40 | 21.58 | 114.00 | 362.33 | 1236.42 | 22.44 | 76.00 | 317.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 515.56 | 14.55 | 0.00 | 247.00 | 336.83 | 17.05 | 0.00 | 149.50 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 595.04 | 15.75 | 0.00 | 245.00 | 390.01 | 18.17 | 0.00 | 177.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 698.48 | 16.85 | 0.00 | 304.00 | 442.33 | 19.06 | 0.00 | 230.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 834.98 | 17.31 | 0.00 | 325.00 | 512.20 | 19.42 | 14.50 | 282.50 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1033.76 | 19.60 | 27.17 | 369.67 | 596.40 | 20.65 | 83.17 | 326.00 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1201.53 | 20.82 | 58.00 | 373.67 | 648.25 | 22.89 | 174.33 | 344.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1174.53 | 19.37 | 23.67 | 376.17 | 643.72 | 21.49 | 142.67 | 339.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1027.59 | 18.04 | 0.00 | 352.67 | 582.48 | 20.14 | 61.83 | 316.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 858.27 | 17.24 | 0.00 | 314.33 | 497.55 | 19.33 | 8.83 | 263.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 735.29 | 16.97 | 0.00 | 294.83 | 453.89 | 19.23 | 0.00 | 240.50 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:50 | 529.45 | 15.13 | 0.00 | 238.50 | 347.87 | 17.63 | 0.00 | 157.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:39 | 515.80 | 14.78 | 0.00 | 238.33 | 338.97 | 17.35 | 0.00 | 138.83 |
Annual Sum or Average | 4027.67 | 0.52 | 835.41 | 17.39 | 108.83 | 3679.17 | 494.05 | 19.53 | 485.33 | 2967.50 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 515.56 | 14.55 | 0.00 | 238.33 | 336.83 | 17.05 | 0.00 | 138.83 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1201.53 | 20.82 | 58.00 | 376.17 | 648.25 | 22.89 | 174.33 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:00 | 2251.14 | 22.57 | 109.33 | 272.17 | 1257.22 | 23.11 | 82.33 | 222.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1977.49 | 20.42 | 79.17 | 263.33 | 1040.03 | 21.18 | 51.33 | 230.00 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2103.07 | 19.41 | 68.83 | 308.50 | 1135.98 | 21.79 | 56.67 | 264.00 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:20 | 2428.10 | 19.12 | 82.00 | 324.67 | 1284.27 | 20.20 | 53.00 | 290.33 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:49 | 2004.58 | 14.74 | 0.00 | 354.00 | 889.67 | 18.06 | 0.00 | 313.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2116.81 | 14.64 | 0.00 | 355.50 | 908.81 | 17.90 | 0.00 | 314.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 1957.50 | 15.18 | 3.67 | 363.17 | 875.55 | 18.18 | 0.00 | 319.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2020.61 | 17.66 | 59.00 | 347.50 | 934.04 | 18.42 | 5.50 | 306.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1856.02 | 19.40 | 80.67 | 311.33 | 971.96 | 20.50 | 52.50 | 275.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:49 | 2415.04 | 22.44 | 108.83 | 307.33 | 1004.36 | 21.72 | 53.50 | 269.83 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1942.14 | 21.35 | 93.50 | 263.83 | 1055.75 | 22.27 | 66.67 | 225.67 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:39 | 2031.78 | 21.46 | 88.00 | 267.50 | 1142.70 | 23.62 | 75.67 | 215.17 |
Annual Sum or Average | 4027.67 | 0.51 | 2091.25 | 18.79 | 773.00 | 3738.83 | 1032.44 | 20.38 | 497.17 | 3246.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1856.02 | 14.64 | 0.00 | 263.33 | 875.55 | 17.90 | 0.00 | 215.17 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2428.10 | 22.57 | 109.33 | 363.17 | 1284.27 | 23.62 | 82.33 | 319.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7617.78 | 36.43 | 297.33 | 295.67 | 1355.13 | 22.68 | 92.17 | 276.50 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3236.74 | 25.18 | 165.33 | 277.83 | 1170.33 | 19.92 | 36.50 | 264.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1474.36 | 14.65 | 0.00 | 316.00 | 865.88 | 18.25 | 0.17 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1169.01 | 14.10 | 0.00 | 319.67 | 678.65 | 17.56 | 0.00 | 279.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:30 | 1044.37 | 14.25 | 0.00 | 344.67 | 592.09 | 17.75 | 0.00 | 293.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:00 | 991.09 | 13.89 | 0.00 | 347.33 | 565.47 | 17.37 | 0.00 | 296.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1096.40 | 14.15 | 0.00 | 356.83 | 606.07 | 17.60 | 0.00 | 306.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1276.43 | 14.46 | 0.00 | 344.00 | 690.97 | 17.87 | 0.00 | 302.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1503.38 | 14.52 | 0.00 | 314.83 | 800.80 | 17.94 | 0.00 | 278.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2555.17 | 17.54 | 39.33 | 312.33 | 1082.64 | 19.00 | 7.17 | 281.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7693.55 | 35.84 | 296.17 | 286.67 | 1214.07 | 20.08 | 46.00 | 267.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7759.60 | 37.28 | 279.33 | 283.33 | 1737.31 | 24.82 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2913.73 | 20.30 | 1077.50 | 3799.17 | 914.33 | 19.06 | 293.00 | 3389.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 991.09 | 13.89 | 0.00 | 277.83 | 565.47 | 17.37 | 0.00 | 264.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7759.60 | 37.28 | 297.33 | 356.83 | 1737.31 | 24.82 | 111.00 | 306.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1843.41 | 19.21 | 81.50 | 264.50 | 1026.57 | 22.19 | 72.33 | 210.83 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2116.59 | 21.10 | 89.67 | 255.67 | 1118.40 | 22.24 | 65.17 | 220.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2163.22 | 19.69 | 74.33 | 310.50 | 1119.60 | 20.90 | 47.83 | 266.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2244.30 | 19.97 | 95.83 | 320.83 | 1186.76 | 21.29 | 68.00 | 286.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2540.02 | 20.63 | 106.00 | 354.17 | 995.74 | 20.37 | 49.17 | 306.17 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2281.06 | 20.08 | 114.00 | 352.83 | 940.91 | 20.16 | 54.00 | 312.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2198.02 | 20.34 | 112.33 | 361.00 | 932.12 | 20.38 | 53.67 | 311.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2007.72 | 20.05 | 103.00 | 344.50 | 1048.00 | 21.65 | 75.83 | 300.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1902.34 | 18.91 | 80.50 | 309.00 | 982.06 | 21.66 | 67.50 | 272.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 1986.68 | 19.74 | 79.17 | 298.33 | 1021.61 | 21.74 | 57.00 | 264.50 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1668.72 | 20.06 | 84.00 | 258.50 | 850.18 | 21.09 | 55.50 | 221.33 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-07:49 | 1802.45 | 20.76 | 87.83 | 250.00 | 960.83 | 21.90 | 62.83 | 199.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2075.89 | 20.04 | 1108.17 | 3679.83 | 1013.46 | 21.25 | 728.83 | 3171.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1668.72 | 18.91 | 74.33 | 250.00 | 850.18 | 20.16 | 47.83 | 199.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2540.02 | 21.10 | 114.00 | 361.00 | 1186.76 | 22.24 | 75.83 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 496.75 | 11.11 | 0.00 | 241.33 | 327.21 | 14.83 | 0.00 | 140.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 573.71 | 12.36 | 0.00 | 242.00 | 379.15 | 16.08 | 0.00 | 171.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 674.19 | 13.61 | 0.00 | 300.17 | 429.66 | 17.17 | 0.00 | 222.67 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:00 | 805.92 | 13.99 | 0.00 | 323.83 | 496.55 | 17.47 | 0.00 | 277.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:00 | 991.15 | 14.88 | 2.17 | 365.00 | 579.10 | 19.63 | 27.50 | 325.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1159.29 | 17.78 | 58.00 | 372.00 | 623.12 | 20.94 | 59.83 | 340.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1132.00 | 15.94 | 23.50 | 374.00 | 618.54 | 19.29 | 24.67 | 335.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 990.30 | 14.47 | 0.00 | 351.00 | 560.94 | 17.92 | 0.00 | 312.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:19 | 827.70 | 13.78 | 0.00 | 312.00 | 480.32 | 17.17 | 0.00 | 256.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:40 | 708.69 | 13.60 | 0.00 | 293.17 | 439.62 | 17.17 | 0.00 | 236.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:00 | 510.09 | 11.64 | 0.00 | 233.33 | 338.00 | 15.42 | 0.00 | 150.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:50 | 496.53 | 11.27 | 0.00 | 232.17 | 329.12 | 15.08 | 0.00 | 128.50 |
Annual Sum or Average | 4027.67 | 0.52 | 804.99 | 13.88 | 83.67 | 3640.00 | 477.71 | 17.52 | 112.00 | 2896.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 496.53 | 11.11 | 0.00 | 232.17 | 327.21 | 14.83 | 0.00 | 128.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1159.29 | 17.78 | 58.00 | 374.00 | 623.12 | 20.94 | 59.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-09:09 | 2200.22 | 22.19 | 109.33 | 270.33 | 1215.59 | 23.00 | 82.17 | 219.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1913.97 | 20.00 | 79.17 | 261.17 | 991.28 | 21.06 | 51.17 | 226.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2045.92 | 18.95 | 68.83 | 306.33 | 1087.44 | 21.66 | 56.67 | 260.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:30 | 2358.98 | 18.66 | 82.00 | 323.00 | 1233.03 | 20.04 | 53.00 | 287.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:49 | 1943.34 | 14.18 | 0.00 | 352.17 | 848.55 | 17.86 | 0.00 | 309.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2062.41 | 14.08 | 0.00 | 354.00 | 861.25 | 17.69 | 0.00 | 309.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:10 | 1900.33 | 14.62 | 3.67 | 361.67 | 835.87 | 17.97 | 0.00 | 315.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 1957.67 | 17.17 | 59.00 | 346.00 | 891.49 | 18.24 | 5.50 | 302.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:49 | 1806.67 | 18.96 | 80.50 | 309.17 | 930.44 | 20.36 | 52.17 | 271.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:00 | 2346.74 | 21.75 | 105.67 | 305.50 | 957.38 | 21.60 | 53.50 | 267.00 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1837.22 | 19.49 | 80.00 | 261.00 | 1015.67 | 22.16 | 66.67 | 222.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1966.19 | 20.71 | 85.00 | 264.83 | 1098.81 | 23.53 | 75.33 | 211.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2027.94 | 18.16 | 753.17 | 3715.17 | 988.04 | 20.23 | 496.17 | 3201.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1806.67 | 14.08 | 0.00 | 261.00 | 835.87 | 17.69 | 0.00 | 211.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2358.98 | 22.19 | 109.33 | 361.67 | 1233.03 | 23.53 | 82.17 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7617.73 | 36.43 | 297.33 | 295.67 | 1355.06 | 22.68 | 92.17 | 276.50 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3236.67 | 25.19 | 165.33 | 277.83 | 1170.26 | 19.92 | 36.50 | 264.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1474.29 | 14.65 | 0.00 | 316.00 | 865.82 | 18.25 | 0.17 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1168.95 | 14.10 | 0.00 | 319.67 | 678.61 | 17.56 | 0.00 | 279.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:30 | 1044.32 | 14.25 | 0.00 | 344.67 | 592.04 | 17.75 | 0.00 | 293.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:00 | 991.03 | 13.89 | 0.00 | 347.33 | 565.43 | 17.37 | 0.00 | 296.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:00 | 1096.34 | 14.15 | 0.00 | 356.83 | 606.03 | 17.60 | 0.00 | 306.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1276.35 | 14.46 | 0.00 | 344.00 | 690.92 | 17.87 | 0.00 | 302.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1503.28 | 14.52 | 0.00 | 314.83 | 800.73 | 17.94 | 0.00 | 278.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2555.07 | 17.54 | 39.33 | 312.33 | 1082.56 | 19.00 | 7.17 | 281.67 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-08:20 | 7693.48 | 35.84 | 296.17 | 286.67 | 1213.99 | 20.08 | 46.00 | 267.33 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7759.56 | 37.28 | 279.33 | 283.33 | 1737.23 | 24.82 | 111.00 | 265.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2913.67 | 20.30 | 1077.50 | 3799.17 | 914.27 | 19.06 | 293.00 | 3389.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 991.03 | 13.89 | 0.00 | 277.83 | 565.43 | 17.37 | 0.00 | 264.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7759.56 | 37.28 | 297.33 | 356.83 | 1737.23 | 24.82 | 111.00 | 306.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1843.40 | 19.21 | 81.50 | 264.50 | 1026.53 | 22.19 | 72.33 | 210.83 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:39 | 2116.57 | 21.10 | 89.67 | 255.67 | 1118.36 | 22.24 | 65.17 | 220.50 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2163.19 | 19.69 | 74.33 | 310.50 | 1119.55 | 20.90 | 47.83 | 266.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:10 | 2244.26 | 19.98 | 95.83 | 320.83 | 1186.71 | 21.29 | 68.00 | 286.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2539.97 | 20.63 | 106.00 | 354.17 | 995.69 | 20.37 | 49.17 | 306.17 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2281.00 | 20.08 | 114.00 | 352.83 | 940.85 | 20.16 | 54.00 | 312.00 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2197.94 | 20.34 | 112.33 | 361.00 | 932.05 | 20.38 | 53.67 | 311.33 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2007.65 | 20.06 | 103.00 | 344.50 | 1047.94 | 21.65 | 75.83 | 300.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1902.27 | 18.91 | 80.50 | 309.00 | 982.00 | 21.66 | 67.50 | 272.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 1986.64 | 19.74 | 79.17 | 298.33 | 1021.55 | 21.74 | 57.00 | 264.50 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-07:49 | 1668.70 | 20.07 | 84.00 | 258.50 | 850.14 | 21.09 | 55.50 | 221.33 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-07:49 | 1802.44 | 20.76 | 87.83 | 250.00 | 960.79 | 21.90 | 62.83 | 199.67 |
Annual Sum or Average | 4027.67 | 0.51 | 2075.85 | 20.04 | 1108.17 | 3679.83 | 1013.41 | 21.25 | 728.83 | 3171.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1668.70 | 18.91 | 74.33 | 250.00 | 850.14 | 20.16 | 47.83 | 199.67 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2539.97 | 21.10 | 114.00 | 361.00 | 1186.71 | 22.24 | 75.83 | 312.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:00 | 496.75 | 11.11 | 0.00 | 241.33 | 327.20 | 14.84 | 0.00 | 140.33 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 573.70 | 12.37 | 0.00 | 242.00 | 379.13 | 16.08 | 0.00 | 171.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 674.18 | 13.61 | 0.00 | 300.17 | 429.63 | 17.17 | 0.00 | 222.67 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:00 | 805.89 | 14.00 | 0.00 | 323.83 | 496.52 | 17.47 | 0.00 | 277.67 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:00 | 991.10 | 14.88 | 2.17 | 365.00 | 579.06 | 19.64 | 27.50 | 325.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:19 | 1159.24 | 17.78 | 58.00 | 372.00 | 623.07 | 20.95 | 59.83 | 340.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:40 | 1131.94 | 15.94 | 23.50 | 374.00 | 618.49 | 19.29 | 24.67 | 335.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 990.25 | 14.47 | 0.00 | 351.00 | 560.90 | 17.92 | 0.00 | 312.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:19 | 827.67 | 13.78 | 0.00 | 312.00 | 480.28 | 17.17 | 0.00 | 256.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:40 | 708.68 | 13.60 | 0.00 | 293.17 | 439.59 | 17.17 | 0.00 | 236.17 |
November | 308.00 | 0.54 | 0.48 | 01-NOV-09:00 | 510.09 | 11.64 | 0.00 | 233.33 | 337.98 | 15.42 | 0.00 | 150.00 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:50 | 496.52 | 11.27 | 0.00 | 232.17 | 329.11 | 15.08 | 0.00 | 128.50 |
Annual Sum or Average | 4027.67 | 0.52 | 804.96 | 13.89 | 83.67 | 3640.00 | 477.67 | 17.52 | 112.00 | 2896.17 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 496.52 | 11.11 | 0.00 | 232.17 | 327.20 | 14.84 | 0.00 | 128.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1159.24 | 17.78 | 58.00 | 374.00 | 623.07 | 20.95 | 59.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-09:09 | 2200.20 | 22.19 | 109.33 | 270.33 | 1215.56 | 23.00 | 82.17 | 219.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 1913.95 | 20.01 | 79.17 | 261.17 | 991.23 | 21.06 | 51.17 | 226.83 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2045.89 | 18.96 | 68.83 | 306.33 | 1087.39 | 21.66 | 56.67 | 260.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:30 | 2358.94 | 18.66 | 82.00 | 323.00 | 1232.98 | 20.04 | 53.00 | 287.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:49 | 1943.29 | 14.18 | 0.00 | 352.17 | 848.49 | 17.86 | 0.00 | 309.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2062.35 | 14.09 | 0.00 | 354.00 | 861.19 | 17.69 | 0.00 | 309.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:10 | 1900.26 | 14.62 | 3.67 | 361.67 | 835.81 | 17.97 | 0.00 | 315.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 1957.60 | 17.17 | 59.00 | 346.00 | 891.43 | 18.24 | 5.50 | 302.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:49 | 1806.61 | 18.97 | 80.50 | 309.17 | 930.38 | 20.36 | 52.17 | 271.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:00 | 2346.71 | 21.75 | 105.67 | 305.50 | 957.32 | 21.60 | 53.50 | 267.00 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1837.20 | 19.49 | 80.00 | 261.00 | 1015.64 | 22.16 | 66.67 | 222.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-08:50 | 1966.18 | 20.71 | 85.00 | 264.83 | 1098.77 | 23.53 | 75.50 | 211.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2027.89 | 18.16 | 753.17 | 3715.17 | 987.99 | 20.23 | 496.33 | 3201.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1806.61 | 14.09 | 0.00 | 261.00 | 835.81 | 17.69 | 0.00 | 211.00 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2358.94 | 22.19 | 109.33 | 361.67 | 1232.98 | 23.53 | 82.17 | 315.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157001E+09 | 5659.35 | 05-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62681159.31 | 5041.72 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39267673.96 | 5034.91 | 09-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112913E+09 | 5659.35 | 21-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157001E+09 | 5659.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.714414E+09 | 7140.07 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442790E+09 | 7140.07 | 03-FEB-17:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.717921E+09 | 7140.07 | 01-MAR-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150373E+09 | 7140.07 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17231218.15 | 6746.46 | 27-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191981E+09 | 7140.07 | 09-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.651671E+09 | 7140.07 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.717921E+09 | 7140.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6118526.88 | 4770.90 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7062640.94 | 4770.90 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22736515.64 | 4770.90 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7264829.36 | 4770.90 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43182512.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22736515.64 | 4770.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61109509.84 | 7179.05 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53638517.77 | 7179.05 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60497371.71 | 7179.05 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24797433.66 | 7179.05 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61109509.84 | 7179.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9429010.28 | 4745.40 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10722388.13 | 4745.40 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24078899.36 | 4745.40 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5209324.96 | 4745.40 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49439622.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24078899.36 | 4745.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283537E+09 | 6962.57 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123894E+09 | 5718.32 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81507121.13 | 5668.48 | 09-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201303E+09 | 6742.80 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690242E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283537E+09 | 6962.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 53026459.04 | 8381.56 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25705900.48 | 8381.56 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 53166684.57 | 8381.56 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36675371.92 | 8381.56 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53166684.57 | 8381.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54248444.31 | 5573.40 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21110751.57 | 5573.40 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30207241.47 | 5573.40 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44266525.01 | 5573.40 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54248444.31 | 5573.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163007E+09 | 8427.64 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74183563.53 | 8427.64 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70413259.44 | 8427.64 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 203702.05 | 1133.24 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98596601.80 | 8427.64 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406404E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163007E+09 | 8427.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 76806231.95 | 5549.59 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33579186.93 | 5549.59 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40522458.30 | 5549.59 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44433935.57 | 5549.59 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76806231.95 | 5549.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426590E+09 | 6456.25 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193704E+09 | 6456.25 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131096E+09 | 6456.25 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1363040.31 | 642.32 | 15-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282233E+09 | 6456.25 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426590E+09 | 6456.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202303E+09 | 26334.68 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135365E+09 | 26334.68 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146861E+09 | 26334.68 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115188E+09 | 26334.68 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.599717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.202303E+09 | 26334.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283881E+09 | 10908.58 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138528E+09 | 10908.58 | 06-FEB-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191095E+09 | 10908.58 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 999457.88 | 1993.94 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 880613.74 | 342.54 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7812522.62 | 10908.58 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207486E+09 | 10908.58 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283881E+09 | 10908.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254949E+09 | 7138.63 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104084E+09 | 7138.63 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124144E+09 | 7138.63 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 284462.94 | 1826.31 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1042078.23 | 807.86 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6734916.27 | 7138.63 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199216E+09 | 7138.63 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254949E+09 | 7138.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.684883E+09 | 10937.50 | 06-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317001E+09 | 10937.50 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246000E+09 | 10937.50 | 15-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1502655.43 | 3412.08 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2856852.51 | 1218.93 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34711329.07 | 10922.56 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437659E+09 | 10937.50 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.684883E+09 | 10937.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344331E+09 | 7124.27 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158813E+09 | 7124.27 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140663E+09 | 7124.27 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 286338.58 | 587.40 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1177235.83 | 408.36 | 28-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15806368.32 | 7124.27 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220040E+09 | 7124.27 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344331E+09 | 7124.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.210005E+11 | 0.148543E+11 | 67392.80 | 19-JAN-15:05 | 46030.86 | 0.00 |
February | 0.00 | 0.00 | 0.274149E+11 | 0.180089E+11 | 66754.21 | 27-FEB-15:40 | 50001.16 | 0.00 |
March | 0.00 | 0.00 | 0.327700E+11 | 0.226981E+11 | 67915.32 | 28-MAR-12:00 | 43773.69 | 0.00 |
April | 0.00 | 0.00 | 0.513423E+11 | 0.365291E+11 | 83806.87 | 28-APR-16:00 | 56885.08 | 0.00 |
May | 0.00 | 0.00 | 0.897685E+11 | 0.608279E+11 | 90049.86 | 25-MAY-06:03 | 52055.90 | 0.00 |
June | 0.00 | 0.00 | 0.955414E+11 | 0.643712E+11 | 95165.33 | 05-JUN-12:03 | 59140.41 | 0.00 |
July | 0.00 | 0.00 | 0.100305E+12 | 0.648446E+11 | 103815.81 | 05-JUL-12:02 | 64480.10 | 0.00 |
August | 0.00 | 0.00 | 0.106838E+12 | 0.703772E+11 | 106080.27 | 22-AUG-06:03 | 76082.93 | 0.00 |
September | 0.00 | 0.00 | 0.912555E+11 | 0.595784E+11 | 104063.75 | 12-SEP-06:03 | 76394.92 | 0.00 |
October | 0.00 | 0.00 | 0.814309E+11 | 0.565894E+11 | 112601.47 | 06-OCT-06:03 | 75007.75 | 0.00 |
November | 0.00 | 0.00 | 0.450418E+11 | 0.322342E+11 | 87752.97 | 07-NOV-13:05 | 53805.48 | 0.00 |
December | 0.00 | 0.00 | 0.299646E+11 | 0.207439E+11 | 76338.45 | 14-DEC-13:05 | 47454.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.772673E+12 | 0.521657E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.210005E+11 | 0.148543E+11 | 66754.21 | 43773.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106838E+12 | 0.703772E+11 | 112601.47 | 76394.92 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.167431E+11 | 0.113033E+11 | 60941.47 | 19-JAN-15:05 | 41321.66 | 0.00 |
February | 0.00 | 0.00 | 0.234135E+11 | 0.153053E+11 | 59952.34 | 27-FEB-15:05 | 45047.14 | 0.00 |
March | 0.00 | 0.00 | 0.285095E+11 | 0.196410E+11 | 61019.68 | 07-MAR-11:05 | 38953.92 | 0.00 |
April | 0.00 | 0.00 | 0.456039E+11 | 0.320025E+11 | 79532.09 | 28-APR-16:00 | 52549.98 | 0.00 |
May | 0.00 | 0.00 | 0.805346E+11 | 0.534102E+11 | 105655.31 | 22-MAY-04:02 | 69005.44 | 0.00 |
June | 0.00 | 0.00 | 0.856301E+11 | 0.561856E+11 | 84738.05 | 19-JUN-11:00 | 54845.95 | 0.00 |
July | 0.00 | 0.00 | 0.891204E+11 | 0.554281E+11 | 90533.06 | 05-JUL-12:02 | 59533.24 | 0.00 |
August | 0.00 | 0.00 | 0.914769E+11 | 0.574822E+11 | 88301.56 | 07-AUG-13:00 | 53442.81 | 0.00 |
September | 0.00 | 0.00 | 0.773308E+11 | 0.478658E+11 | 99695.07 | 05-SEP-06:03 | 66787.66 | 0.00 |
October | 0.00 | 0.00 | 0.687556E+11 | 0.457135E+11 | 92464.86 | 06-OCT-14:05 | 56251.12 | 0.00 |
November | 0.00 | 0.00 | 0.367745E+11 | 0.254070E+11 | 77501.56 | 02-NOV-14:05 | 51302.47 | 0.00 |
December | 0.00 | 0.00 | 0.244648E+11 | 0.163206E+11 | 66812.78 | 14-DEC-13:05 | 42793.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.668358E+12 | 0.436065E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.167431E+11 | 0.113033E+11 | 59952.34 | 38953.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.914769E+11 | 0.574822E+11 | 105655.31 | 69005.44 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.169007E+11 | 0.113175E+11 | 64197.88 | 19-JAN-15:00 | 44584.46 | 0.00 |
February | 0.00 | 0.00 | 0.239505E+11 | 0.156439E+11 | 62920.96 | 27-FEB-15:30 | 48349.27 | 0.00 |
March | 0.00 | 0.00 | 0.295644E+11 | 0.203494E+11 | 63267.94 | 28-MAR-12:30 | 45104.91 | 0.00 |
April | 0.00 | 0.00 | 0.480969E+11 | 0.340746E+11 | 88341.60 | 28-APR-16:00 | 61738.79 | 0.00 |
May | 0.00 | 0.00 | 0.857718E+11 | 0.582360E+11 | 117640.33 | 22-MAY-04:02 | 80303.18 | 0.00 |
June | 0.00 | 0.00 | 0.917887E+11 | 0.620491E+11 | 92745.12 | 28-JUN-14:30 | 64940.73 | 0.00 |
July | 0.00 | 0.00 | 0.947783E+11 | 0.607241E+11 | 95091.60 | 05-JUL-13:50 | 65245.12 | 0.00 |
August | 0.00 | 0.00 | 0.967448E+11 | 0.623405E+11 | 93819.93 | 07-AUG-13:00 | 59144.16 | 0.00 |
September | 0.00 | 0.00 | 0.808982E+11 | 0.508685E+11 | 104111.29 | 05-SEP-06:03 | 72157.56 | 0.00 |
October | 0.00 | 0.00 | 0.714849E+11 | 0.479863E+11 | 97980.26 | 06-OCT-14:00 | 62236.39 | 0.00 |
November | 0.00 | 0.00 | 0.371583E+11 | 0.252298E+11 | 82609.63 | 02-NOV-14:30 | 57540.41 | 0.00 |
December | 0.00 | 0.00 | 0.247625E+11 | 0.163059E+11 | 68471.41 | 15-DEC-14:50 | 53004.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.701900E+12 | 0.465126E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.169007E+11 | 0.113175E+11 | 62920.96 | 44584.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.967448E+11 | 0.623405E+11 | 117640.33 | 80303.18 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1385.48 | 5050.52 | 23-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1383.11 | 5042.61 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1423.55 | 4927.85 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1243.96 | 4652.39 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1203.09 | 4361.03 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1160.06 | 4060.81 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1024.13 | 3861.01 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1145.37 | 3945.85 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1118.91 | 4183.62 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1198.16 | 4514.44 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1304.42 | 4805.32 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1315.27 | 4995.41 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1241.35 | ||||
Minimum of Months | 0.00 | 0.00 | 1024.13 | 3861.01 | ||
Maximum of Months | 0.00 | 0.00 | 1423.55 | 5050.52 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157897E+10 | 0.31 | 3832.37 | 03-JAN-07:01 | 1.00 |
February | 0.150258E+10 | 0.31 | 3623.58 | 27-FEB-15:40 | 0.96 |
March | 0.176844E+10 | 0.33 | 3593.67 | 21-MAR-06:02 | 0.97 |
April | 0.204924E+10 | 0.34 | 3832.37 | 11-APR-06:02 | 1.00 |
May | 0.332191E+10 | 0.43 | 9783.55 | 30-MAY-06:03 | 1.78 |
June | 0.356948E+10 | 0.46 | 9328.63 | 26-JUN-06:03 | 1.73 |
July | 0.366716E+10 | 0.46 | 9783.55 | 07-JUL-06:03 | 1.78 |
August | 0.419614E+10 | 0.50 | 9783.55 | 07-AUG-04:02 | 1.79 |
September | 0.345901E+10 | 0.46 | 9783.55 | 11-SEP-04:02 | 1.79 |
October | 0.360712E+10 | 0.45 | 9783.55 | 11-OCT-05:12 | 1.78 |
November | 0.231063E+10 | 0.36 | 4812.84 | 06-NOV-16:20 | 1.14 |
December | 0.181184E+10 | 0.32 | 4620.51 | 11-DEC-07:03 | 1.11 |
Annual Sum or Average | 0.328425E+11 | 0.39 | |||
Minimum of Months | 0.150258E+10 | 0.31 | 3593.67 | 0.96 | |
Maximum of Months | 0.419614E+10 | 0.50 | 9783.55 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126222E+10 | 0.29 | 2875.52 | 19-JAN-15:05 | 0.90 |
February | 0.124675E+10 | 0.30 | 3286.50 | 27-FEB-15:05 | 0.97 |
March | 0.146871E+10 | 0.32 | 2672.81 | 06-MAR-15:05 | 0.86 |
April | 0.174435E+10 | 0.33 | 3515.20 | 28-APR-15:20 | 1.01 |
May | 0.276132E+10 | 0.41 | 8712.61 | 22-MAY-04:02 | 1.78 |
June | 0.289719E+10 | 0.44 | 8712.61 | 05-JUN-04:02 | 1.78 |
July | 0.285841E+10 | 0.43 | 8712.61 | 05-JUL-04:02 | 1.78 |
August | 0.304077E+10 | 0.44 | 8712.61 | 05-AUG-05:03 | 1.78 |
September | 0.250363E+10 | 0.40 | 8712.61 | 05-SEP-06:03 | 1.78 |
October | 0.265790E+10 | 0.40 | 8712.61 | 07-OCT-05:03 | 1.78 |
November | 0.168034E+10 | 0.33 | 4129.70 | 06-NOV-15:05 | 1.12 |
December | 0.137335E+10 | 0.30 | 3413.56 | 15-DEC-15:05 | 1.00 |
Annual Sum or Average | 0.254949E+11 | 0.37 | |||
Minimum of Months | 0.124675E+10 | 0.29 | 2672.81 | 0.86 | |
Maximum of Months | 0.304077E+10 | 0.44 | 8712.61 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.124355E+10 | 0.30 | 2566.85 | 19-JAN-15:30 | 0.77 |
February | 0.123050E+10 | 0.30 | 2850.99 | 27-FEB-15:30 | 0.82 |
March | 0.146363E+10 | 0.32 | 2509.16 | 29-MAR-15:20 | 0.76 |
April | 0.174408E+10 | 0.33 | 3786.09 | 28-APR-15:30 | 0.96 |
May | 0.277072E+10 | 0.40 | 10201.23 | 22-MAY-04:02 | 1.78 |
June | 0.295100E+10 | 0.42 | 10201.23 | 05-JUN-04:02 | 1.78 |
July | 0.287823E+10 | 0.41 | 10201.23 | 03-JUL-04:02 | 1.78 |
August | 0.301424E+10 | 0.42 | 10201.23 | 07-AUG-04:02 | 1.78 |
September | 0.241121E+10 | 0.38 | 10201.23 | 11-SEP-04:02 | 1.78 |
October | 0.249966E+10 | 0.37 | 8206.16 | 10-OCT-06:03 | 1.55 |
November | 0.155145E+10 | 0.32 | 3639.15 | 02-NOV-15:10 | 0.94 |
December | 0.133000E+10 | 0.30 | 3114.33 | 15-DEC-15:20 | 0.86 |
Annual Sum or Average | 0.250883E+11 | 0.36 | |||
Minimum of Months | 0.123050E+10 | 0.30 | 2509.16 | 0.76 | |
Maximum of Months | 0.301424E+10 | 0.42 | 10201.23 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.48 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.58 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.64 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.70 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.04 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.02 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.16 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.12 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.06 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.64 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.78 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.70 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.58 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.64 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.48 | 58.48 | 1385.48 | 5050.52 | 23-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.08 | 58.08 | 1383.11 | 5042.61 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.12 | 58.12 | 1423.55 | 4927.85 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.22 | 58.22 | 1243.96 | 4652.39 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.69 | 58.69 | 1203.09 | 4361.03 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.46 | 58.46 | 1160.06 | 4060.81 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.54 | 58.54 | 1024.13 | 3861.01 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.55 | 58.55 | 1145.37 | 3945.85 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.51 | 58.51 | 1118.91 | 4183.62 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.75 | 57.75 | 1198.16 | 4514.44 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.29 | 58.29 | 1304.42 | 4805.32 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.17 | 58.17 | 1315.27 | 4995.41 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1241.35 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.75 | 57.75 | 1024.13 | 3861.01 | ||
Maximum of Months | 0.00 | 0.00 | 58.69 | 58.69 | 1423.55 | 5050.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.726457E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.821537E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.100047E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137544E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.243251E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.262250E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.274343E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.293623E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.242670E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.223406E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.125892E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.932886E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215111E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.726457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.293623E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.569982E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.681195E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.819446E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120595E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.215213E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.230621E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.237714E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.244031E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200459E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184045E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.998111E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.732650E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.181282E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.569982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.244031E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.731893E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.773270E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.918261E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.127172E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.228623E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.246791E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.252409E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.257164E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.208597E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.189627E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.100869E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.843993E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.193799E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.731893E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257164E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157897E+10 | 0.210005E+11 | 0.948072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150258E+10 | 0.274149E+11 | 0.576895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176844E+10 | 0.327700E+11 | 0.864502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204924E+10 | 0.513423E+11 | 0.150373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.332191E+10 | 0.897685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356948E+10 | 0.955414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.366716E+10 | 0.100305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419614E+10 | 0.106838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345901E+10 | 0.912555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360712E+10 | 0.814309E+11 | 17231218.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231063E+10 | 0.450418E+11 | 0.191981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181184E+10 | 0.299646E+11 | 0.801855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328425E+11 | 0.772673E+12 | 0.355091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150258E+10 | 0.210005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419614E+10 | 0.106838E+12 | 0.948072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126222E+10 | 0.167431E+11 | 0.630625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124675E+10 | 0.234135E+11 | 0.278474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146871E+10 | 0.285095E+11 | 0.275817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174435E+10 | 0.456039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276132E+10 | 0.805346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289719E+10 | 0.856301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285841E+10 | 0.891204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304077E+10 | 0.914769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250363E+10 | 0.773308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265790E+10 | 0.687556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168034E+10 | 0.367745E+11 | 203702.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137335E+10 | 0.244648E+11 | 0.425276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254949E+11 | 0.668358E+12 | 0.161039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124675E+10 | 0.167431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.304077E+10 | 0.914769E+11 | 0.630625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.124355E+10 | 0.169007E+11 | 0.219694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123050E+10 | 0.239505E+11 | 0.104749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146363E+10 | 0.295644E+11 | 0.979860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174408E+10 | 0.480969E+11 | 3072914.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277072E+10 | 0.857718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295100E+10 | 0.917887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287823E+10 | 0.947783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.301424E+10 | 0.967448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241121E+10 | 0.808982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249966E+10 | 0.714849E+11 | 5956780.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155145E+10 | 0.371583E+11 | 66428176.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133000E+10 | 0.247625E+11 | 0.146182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250883E+11 | 0.701900E+12 | 0.576157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123050E+10 | 0.169007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301424E+10 | 0.967448E+11 | 0.219694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157897E+10 | 0.00 | 0.00 | 0.00 | 0.473753E+10 | 0.948072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150258E+10 | 0.00 | 0.00 | 0.00 | 0.613589E+10 | 0.576895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176844E+10 | 0.00 | 0.00 | 0.00 | 0.737171E+10 | 0.864502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204924E+10 | 0.00 | 0.00 | 0.00 | 0.115547E+11 | 0.150373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.332191E+10 | 0.00 | 0.00 | 0.00 | 0.210032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.356948E+10 | 0.00 | 0.00 | 0.00 | 0.226556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.366716E+10 | 0.00 | 0.00 | 0.00 | 0.237672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.419614E+10 | 0.00 | 0.00 | 0.00 | 0.251662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345901E+10 | 0.00 | 0.00 | 0.00 | 0.208080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.360712E+10 | 0.00 | 0.00 | 0.00 | 0.187162E+11 | 17231218.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231063E+10 | 0.00 | 0.00 | 0.00 | 0.100866E+11 | 0.191981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181184E+10 | 0.00 | 0.00 | 0.00 | 0.671516E+10 | 0.801855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328425E+11 | 0.00 | 0.00 | 0.00 | 0.178718E+12 | 0.355091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150258E+10 | 0.00 | 0.00 | 0.00 | 0.473753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.419614E+10 | 0.00 | 0.00 | 0.00 | 0.251662E+11 | 0.948072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126222E+10 | 0.00 | 0.00 | 0.00 | 0.380697E+10 | 0.630625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124675E+10 | 0.00 | 0.00 | 0.00 | 0.528673E+10 | 0.278474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146871E+10 | 0.00 | 0.00 | 0.00 | 0.644994E+10 | 0.275817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174435E+10 | 0.00 | 0.00 | 0.00 | 0.103151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276132E+10 | 0.00 | 0.00 | 0.00 | 0.187599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.289719E+10 | 0.00 | 0.00 | 0.00 | 0.201649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285841E+10 | 0.00 | 0.00 | 0.00 | 0.209130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.304077E+10 | 0.00 | 0.00 | 0.00 | 0.213623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250363E+10 | 0.00 | 0.00 | 0.00 | 0.175423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265790E+10 | 0.00 | 0.00 | 0.00 | 0.157466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168034E+10 | 0.00 | 0.00 | 0.00 | 0.830057E+10 | 203702.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137335E+10 | 0.00 | 0.00 | 0.00 | 0.552788E+10 | 0.425276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254949E+11 | 0.00 | 0.00 | 0.00 | 0.154176E+12 | 0.161039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124675E+10 | 0.00 | 0.00 | 0.00 | 0.380697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.304077E+10 | 0.00 | 0.00 | 0.00 | 0.213623E+11 | 0.630625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.124355E+10 | 0.00 | 0.00 | 0.00 | 0.387844E+10 | 0.219694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123050E+10 | 0.00 | 0.00 | 0.00 | 0.545470E+10 | 0.104749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146363E+10 | 0.00 | 0.00 | 0.00 | 0.673912E+10 | 0.979860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174408E+10 | 0.00 | 0.00 | 0.00 | 0.109700E+11 | 3072914.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277072E+10 | 0.00 | 0.00 | 0.00 | 0.200916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295100E+10 | 0.00 | 0.00 | 0.00 | 0.217281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.287823E+10 | 0.00 | 0.00 | 0.00 | 0.223626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.301424E+10 | 0.00 | 0.00 | 0.00 | 0.227021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.241121E+10 | 0.00 | 0.00 | 0.00 | 0.184485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249966E+10 | 0.00 | 0.00 | 0.00 | 0.164571E+11 | 5956780.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155145E+10 | 0.00 | 0.00 | 0.00 | 0.846904E+10 | 66428176.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133000E+10 | 0.00 | 0.00 | 0.00 | 0.564811E+10 | 0.146182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250883E+11 | 0.00 | 0.00 | 0.00 | 0.162950E+12 | 0.576157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123050E+10 | 0.00 | 0.00 | 0.00 | 0.387844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.301424E+10 | 0.00 | 0.00 | 0.00 | 0.227021E+11 | 0.219694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.722839E+09 | 0.144369E+10 | 0.00 | 31300433.40 | 192609.91 | 0.00 | 0.113232E+11 | 0.00 | 0.50 |
February | 0.522683E+09 | 0.180170E+10 | 0.00 | 22399459.65 | 25411095.33 | 0.00 | 0.652412E+10 | 0.00 | 0.52 |
March | 0.540112E+09 | 0.286075E+10 | 0.00 | 26951844.92 | 36282659.48 | 0.00 | 0.871342E+10 | 0.00 | 0.58 |
April | 0.207341E+09 | 0.518754E+10 | 0.00 | 11351467.70 | 78246570.99 | 0.00 | 0.223355E+10 | 0.00 | 0.47 |
May | 0.00 | 0.135012E+11 | 0.00 | 0.00 | 0.147196E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.144622E+11 | 0.00 | 0.00 | 0.159931E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.156887E+11 | 0.00 | 0.00 | 0.264261E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.154395E+11 | 0.00 | 0.00 | 0.167763E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.127908E+11 | 0.00 | 0.00 | 0.215731E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 87073811.74 | 0.940456E+10 | 0.00 | 10331348.01 | 0.149904E+09 | 0.00 | 0.219648E+10 | 0.00 | 0.39 |
November | 0.553662E+09 | 0.365515E+10 | 0.00 | 25459084.86 | 27387259.94 | 0.00 | 0.600583E+10 | 0.00 | 0.59 |
December | 0.765712E+09 | 0.281124E+10 | 0.00 | 28151342.65 | 34215061.62 | 0.00 | 0.963845E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.339942E+10 | 0.990471E+11 | 0.00 | 0.155945E+09 | 0.130652E+10 | 0.00 | 0.466351E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.144369E+10 | 0.00 | 0.00 | 192609.91 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.765712E+09 | 0.156887E+11 | 0.00 | 31300433.40 | 0.264261E+09 | 0.00 | 0.113232E+11 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.601382E+10 | 0.976903E+09 | 0.00 | 4642915.57 | 0.205882E+09 | 0.00 | 0.269119E+10 | 0.00 | 0.37 |
February | 0.311704E+10 | 0.122357E+10 | 0.00 | 3725858.31 | 0.249179E+09 | 0.00 | 0.181361E+10 | 0.00 | 0.37 |
March | 0.318985E+10 | 0.197720E+10 | 0.00 | 7455192.79 | 0.316421E+09 | 0.00 | 0.329387E+10 | 0.00 | 0.41 |
April | 0.567187E+09 | 0.403035E+10 | 0.00 | 5011364.34 | 0.199665E+09 | 0.00 | 0.110218E+10 | 0.00 | 0.35 |
May | 0.00 | 0.117608E+11 | 0.00 | 0.00 | 0.147470E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.132133E+11 | 0.00 | 0.00 | 0.158512E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.146987E+11 | 0.00 | 0.00 | 0.263100E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.147822E+11 | 0.00 | 0.00 | 0.167850E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.119648E+11 | 0.00 | 0.00 | 0.216093E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.363521E+09 | 0.878666E+10 | 0.00 | 4820667.92 | 0.151666E+09 | 0.00 | 0.120293E+10 | 0.00 | 0.31 |
November | 0.161023E+10 | 0.320034E+10 | 0.00 | 8434330.08 | 0.134702E+09 | 0.00 | 0.253226E+10 | 0.00 | 0.40 |
December | 0.437766E+10 | 0.217974E+10 | 0.00 | 5292825.43 | 0.226252E+09 | 0.00 | 0.266913E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.192393E+11 | 0.887946E+11 | 0.00 | 39383154.44 | 0.243679E+10 | 0.00 | 0.153052E+11 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.976903E+09 | 0.00 | 0.00 | 0.134702E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.601382E+10 | 0.147822E+11 | 0.00 | 8434330.08 | 0.316421E+09 | 0.00 | 0.329387E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.650695E+10 | 0.814987E+09 | 0.00 | 1720098.94 | 0.381559E+09 | 33975910.29 | 0.130785E+10 | 0.00 | 0.36 |
February | 0.339234E+10 | 0.100443E+10 | 0.00 | 2183326.48 | 0.504988E+09 | 40723823.18 | 0.103851E+10 | 0.00 | 0.36 |
March | 0.382066E+10 | 0.175166E+10 | 0.00 | 4557292.79 | 0.546479E+09 | 12977543.33 | 0.201483E+10 | 0.00 | 0.40 |
April | 0.646999E+09 | 0.374320E+10 | 0.00 | 4428494.47 | 0.495336E+09 | 0.00 | 0.971901E+09 | 0.00 | 0.34 |
May | 0.00 | 0.115497E+11 | 0.00 | 0.00 | 0.139474E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.129388E+11 | 0.00 | 0.00 | 0.148498E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.144716E+11 | 0.00 | 0.00 | 0.254836E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.145384E+11 | 0.00 | 0.00 | 0.163275E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.118190E+11 | 0.00 | 0.00 | 0.220462E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.428226E+09 | 0.863862E+10 | 0.00 | 3349097.96 | 0.212113E+09 | 0.00 | 0.901486E+09 | 0.00 | 0.30 |
November | 0.194232E+10 | 0.299293E+10 | 0.00 | 5230757.49 | 0.431524E+09 | 0.00 | 0.163610E+10 | 0.00 | 0.39 |
December | 0.543090E+10 | 0.188017E+10 | 0.00 | 1780124.54 | 0.549947E+09 | 23200542.59 | 0.755326E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.221684E+11 | 0.861436E+11 | 0.00 | 23249192.68 | 0.404849E+10 | 0.110878E+09 | 0.862600E+10 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.814987E+09 | 0.00 | 0.00 | 0.139474E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.650695E+10 | 0.145384E+11 | 0.00 | 5230757.49 | 0.549947E+09 | 40723823.18 | 0.201483E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129691E+10 | 0.169186E+09 | 0.00 | 32173.52 | 0.101517E+09 | 0.313709E+09 | 35326701.64 | 0.00 | 0.36 |
February | 0.750344E+09 | 0.215556E+09 | 0.00 | 177707.96 | 0.127949E+09 | 0.114533E+09 | 69767254.66 | 0.00 | 0.37 |
March | 0.896647E+09 | 0.463914E+09 | 0.00 | 554701.98 | 0.100246E+09 | 0.124680E+09 | 0.190851E+09 | 0.00 | 0.41 |
April | 0.189535E+09 | 0.100895E+10 | 0.00 | 970040.40 | 0.127332E+09 | 147358.38 | 0.162690E+09 | 0.00 | 0.40 |
May | 0.00 | 0.361960E+10 | 0.00 | 0.00 | 29729230.16 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.436614E+10 | 0.00 | 0.00 | 35585342.73 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.483874E+10 | 0.00 | 0.00 | 50202304.68 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.463604E+10 | 0.00 | 0.00 | 35377204.97 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.344280E+10 | 0.00 | 0.00 | 63191781.93 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.125427E+09 | 0.251147E+10 | 0.00 | 617080.06 | 56715872.13 | 0.00 | 0.150874E+09 | 0.00 | 0.37 |
November | 0.551868E+09 | 0.696242E+09 | 477146.52 | 713289.46 | 0.128710E+09 | 9370107.41 | 0.173246E+09 | 11480.41 | 0.39 |
December | 0.106930E+10 | 0.420818E+09 | 860415.81 | 119065.09 | 0.137782E+09 | 0.199248E+09 | 40816994.00 | 15387.75 | 0.36 |
Annual Sum or Average | 0.488003E+10 | 0.263895E+11 | 1337562.33 | 3184058.48 | 0.994336E+09 | 0.761687E+09 | 0.823572E+09 | 26868.16 | 0.38 |
Minimum of Months | 0.00 | 0.169186E+09 | 0.00 | 0.00 | 29729230.16 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.129691E+10 | 0.483874E+10 | 860415.81 | 970040.40 | 0.137782E+09 | 0.313709E+09 | 0.190851E+09 | 15387.75 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.706403E+09 | 0.169700E+09 | 0.00 | 335586.18 | 43382334.99 | 0.115221E+09 | 0.239314E+09 | 0.00 | 0.38 |
February | 0.363747E+09 | 0.255251E+09 | 0.00 | 627355.14 | 47534975.43 | 36486277.16 | 0.229295E+09 | 0.00 | 0.43 |
March | 0.438877E+09 | 0.496469E+09 | 0.00 | 1429122.74 | 36959067.28 | 63169361.83 | 0.423124E+09 | 0.00 | 0.56 |
April | 77144107.10 | 0.101743E+10 | 0.00 | 1370553.17 | 49577212.61 | 93450.72 | 0.300004E+09 | 0.00 | 0.60 |
May | 0.00 | 0.306380E+10 | 0.00 | 0.00 | 18661290.29 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.358715E+10 | 0.00 | 0.00 | 21158064.87 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.404042E+10 | 0.00 | 0.00 | 28485482.19 | 0.00 | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.380978E+10 | 0.00 | 0.00 | 21929767.56 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.282029E+10 | 0.00 | 0.00 | 32809250.92 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 61233621.23 | 0.214140E+10 | 0.00 | 689622.88 | 29741701.65 | 0.00 | 0.155917E+09 | 0.00 | 0.48 |
November | 0.236376E+09 | 0.631915E+09 | 60993.32 | 1195749.74 | 52052949.90 | 1477327.23 | 0.325817E+09 | 5416.26 | 0.49 |
December | 0.594883E+09 | 0.358374E+09 | 112546.41 | 476006.00 | 64747619.06 | 97658397.94 | 0.162255E+09 | 7979.77 | 0.40 |
Annual Sum or Average | 0.247866E+10 | 0.223920E+11 | 173539.73 | 6123995.86 | 0.447040E+09 | 0.314106E+09 | 0.183573E+10 | 13396.04 | 0.48 |
Minimum of Months | 0.00 | 0.169700E+09 | 0.00 | 0.00 | 18661290.29 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.706403E+09 | 0.404042E+10 | 112546.41 | 1429122.74 | 64747619.06 | 0.115221E+09 | 0.423124E+09 | 7979.77 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.687894E+09 | 0.400555E+09 | 0.00 | 5313541.40 | 49012659.60 | 0.143370E+09 | 0.188872E+10 | 0.00 | 0.63 |
February | 0.414831E+09 | 0.617903E+09 | 0.00 | 3346214.35 | 54244003.37 | 51508688.17 | 0.996757E+09 | 0.00 | 0.62 |
March | 0.636857E+09 | 0.735891E+09 | 0.00 | 2999759.28 | 65619812.79 | 0.104508E+09 | 0.915820E+09 | 0.00 | 0.60 |
April | 0.162984E+09 | 0.126551E+10 | 0.00 | 1619678.06 | 0.115287E+09 | 146793.94 | 0.282896E+09 | 0.00 | 0.50 |
May | 0.00 | 0.366237E+10 | 0.00 | 0.00 | 30224637.87 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.418467E+10 | 0.00 | 0.00 | 35922895.85 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.476674E+10 | 0.00 | 0.00 | 53559475.10 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.507603E+10 | 0.00 | 0.00 | 35373401.64 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.428408E+10 | 0.00 | 0.00 | 48259436.57 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 99031832.46 | 0.373738E+10 | 0.00 | 1483130.75 | 32541998.54 | 0.00 | 0.301138E+09 | 0.00 | 0.57 |
November | 0.267643E+09 | 0.136617E+10 | 36727.99 | 5073001.88 | 67665859.60 | 1639280.57 | 0.118169E+10 | 3110.84 | 0.76 |
December | 0.671050E+09 | 0.982276E+09 | 177747.93 | 4594349.48 | 72181848.49 | 96647748.38 | 0.131830E+10 | 10307.28 | 0.67 |
Annual Sum or Average | 0.294029E+10 | 0.310796E+11 | 214475.92 | 24429675.20 | 0.659893E+09 | 0.397820E+09 | 0.688533E+10 | 13418.11 | 0.53 |
Minimum of Months | 0.00 | 0.400555E+09 | 0.00 | 0.00 | 30224637.87 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.687894E+09 | 0.507603E+10 | 177747.93 | 5313541.40 | 0.115287E+09 | 0.143370E+09 | 0.188872E+10 | 10307.28 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.641103E+09 | 0.181162E+09 | 0.00 | 907939.42 | 43823405.57 | 0.165822E+09 | 0.365499E+09 | 0.00 | 0.43 |
February | 0.365627E+09 | 0.252237E+09 | 0.00 | 872301.16 | 58210707.25 | 61583515.81 | 0.265108E+09 | 0.00 | 0.47 |
March | 0.459569E+09 | 0.387857E+09 | 0.00 | 1594768.25 | 49714389.83 | 73996065.91 | 0.485896E+09 | 0.00 | 0.57 |
April | 92537028.61 | 0.968329E+09 | 0.00 | 1438722.37 | 61581829.97 | 0.00 | 0.229215E+09 | 0.00 | 0.57 |
May | 0.00 | 0.278932E+10 | 0.00 | 0.00 | 13030345.44 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.330492E+10 | 0.00 | 0.00 | 8386278.37 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.360879E+10 | 0.00 | 0.00 | 10904741.23 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.367668E+10 | 0.00 | 0.00 | 11828118.52 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.273786E+10 | 0.00 | 0.00 | 21617826.56 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 70757260.44 | 0.206743E+10 | 0.00 | 679357.15 | 19665507.73 | 0.00 | 0.150374E+09 | 0.00 | 0.49 |
November | 0.284787E+09 | 0.614126E+09 | 79688.12 | 1321978.86 | 62634831.28 | 4949040.24 | 0.319320E+09 | 4907.41 | 0.52 |
December | 0.589247E+09 | 0.403832E+09 | 546019.10 | 756540.12 | 66466194.02 | 0.109953E+09 | 0.226590E+09 | 8833.39 | 0.44 |
Annual Sum or Average | 0.250363E+10 | 0.209926E+11 | 625707.23 | 7571607.33 | 0.427864E+09 | 0.416303E+09 | 0.204200E+10 | 13740.80 | 0.48 |
Minimum of Months | 0.00 | 0.181162E+09 | 0.00 | 0.00 | 8386278.37 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.641103E+09 | 0.367668E+10 | 546019.10 | 1594768.25 | 66466194.02 | 0.165822E+09 | 0.485896E+09 | 8833.39 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168981E+10 | 0.146439E+09 | 0.00 | 112317.42 | 57392680.69 | 23512699.73 | 88593711.16 | 0.00 | 0.35 |
February | 0.969453E+09 | 0.172281E+09 | 0.00 | 140340.22 | 82293492.11 | 18506255.32 | 64047395.78 | 0.00 | 0.36 |
March | 0.116360E+10 | 0.316546E+09 | 0.00 | 238573.77 | 0.107039E+09 | 12436623.74 | 0.112452E+09 | 0.00 | 0.38 |
April | 0.227052E+09 | 0.698993E+09 | 0.00 | 553570.97 | 0.118484E+09 | 0.00 | 82739100.01 | 0.00 | 0.31 |
May | 0.00 | 0.262875E+10 | 0.00 | 0.00 | 31039484.45 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.322698E+10 | 0.00 | 0.00 | 33911412.07 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.370699E+10 | 0.00 | 0.00 | 55725288.00 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.372977E+10 | 0.00 | 0.00 | 35376443.44 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.279874E+10 | 0.00 | 0.00 | 45491541.85 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 0.118443E+09 | 0.202672E+10 | 0.00 | 969652.09 | 31616245.96 | 0.00 | 0.213432E+09 | 0.00 | 0.33 |
November | 0.570073E+09 | 0.610856E+09 | 0.00 | 1152003.29 | 18694306.59 | 0.00 | 0.306206E+09 | 0.00 | 0.39 |
December | 0.137522E+10 | 0.405724E+09 | 0.00 | 225982.75 | 35389822.47 | 9917955.36 | 0.102278E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.611365E+10 | 0.204688E+11 | 0.00 | 3392440.52 | 0.652454E+09 | 64373534.15 | 0.969749E+09 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.146439E+09 | 0.00 | 0.00 | 18694306.59 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.168981E+10 | 0.372977E+10 | 0.00 | 1152003.29 | 0.118484E+09 | 23512699.73 | 0.306206E+09 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.741844E+09 | 0.152481E+09 | 0.00 | 962121.32 | 17675866.20 | 2466784.69 | 0.457699E+09 | 0.00 | 0.38 |
February | 0.428595E+09 | 0.207965E+09 | 0.00 | 874185.10 | 17310869.04 | 3334645.82 | 0.285622E+09 | 0.00 | 0.42 |
March | 0.500298E+09 | 0.394738E+09 | 0.00 | 1347317.69 | 17659868.18 | 4293253.95 | 0.446128E+09 | 0.00 | 0.50 |
April | 88044703.33 | 0.775251E+09 | 0.00 | 1156477.21 | 31628390.11 | 0.00 | 0.233483E+09 | 0.00 | 0.49 |
May | 0.00 | 0.235217E+10 | 0.00 | 0.00 | 19596190.94 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.275776E+10 | 0.00 | 0.00 | 21291545.66 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.317809E+10 | 0.00 | 0.00 | 35181105.71 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.309734E+10 | 0.00 | 0.00 | 22334247.89 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.231109E+10 | 0.00 | 0.00 | 28720223.80 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 45286358.99 | 0.174919E+10 | 0.00 | 1066984.72 | 19956684.07 | 0.00 | 0.225059E+09 | 0.00 | 0.45 |
November | 0.217514E+09 | 0.529821E+09 | 0.00 | 2153398.84 | 4321729.88 | 0.00 | 0.529897E+09 | 0.00 | 0.54 |
December | 0.685333E+09 | 0.333449E+09 | 0.00 | 1014932.34 | 10491878.30 | 4865858.69 | 0.331985E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.270691E+10 | 0.178393E+11 | 0.00 | 8575417.23 | 0.246169E+09 | 14960543.16 | 0.250987E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.152481E+09 | 0.00 | 0.00 | 4321729.88 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.741844E+09 | 0.317809E+10 | 0.00 | 2153398.84 | 35181105.71 | 4865858.69 | 0.529897E+09 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104412E+10 | 0.353659E+09 | 0.00 | 2570790.71 | 17973599.40 | 0.478017E+09 | 0.902653E+09 | 0.00 | 0.52 |
February | 0.672132E+09 | 0.528601E+09 | 0.00 | 1449384.76 | 21623173.49 | 0.270525E+09 | 0.364144E+09 | 0.00 | 0.52 |
March | 0.893983E+09 | 0.645183E+09 | 0.00 | 1024366.01 | 44908757.41 | 0.435570E+09 | 0.234150E+09 | 0.00 | 0.50 |
April | 0.204558E+09 | 0.107115E+10 | 256609.36 | 800377.50 | 0.111702E+09 | 74951400.14 | 94421254.95 | 4282.76 | 0.41 |
May | 0.00 | 0.337475E+10 | 0.00 | 0.00 | 38895793.34 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.400848E+10 | 0.00 | 0.00 | 42327802.07 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.458524E+10 | 0.00 | 0.00 | 55569973.53 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.500824E+10 | 0.00 | 0.00 | 38202927.32 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.393306E+10 | 0.00 | 0.00 | 58802010.30 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.116344E+09 | 0.341012E+10 | 0.00 | 1389104.16 | 36980140.15 | 11530112.92 | 0.256539E+09 | 0.00 | 0.53 |
November | 0.279686E+09 | 0.119712E+10 | 0.00 | 4970390.81 | 23691608.67 | 0.126006E+09 | 0.103425E+10 | 0.00 | 0.73 |
December | 0.807583E+09 | 0.868686E+09 | 0.00 | 3249237.25 | 35269586.37 | 0.453703E+09 | 0.879209E+09 | 0.00 | 0.62 |
Annual Sum or Average | 0.401840E+10 | 0.289843E+11 | 256609.36 | 15453651.20 | 0.525947E+09 | 0.185030E+10 | 0.376537E+10 | 4282.76 | 0.48 |
Minimum of Months | 0.00 | 0.353659E+09 | 0.00 | 0.00 | 17973599.40 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.104412E+10 | 0.500824E+10 | 256609.36 | 4970390.81 | 0.111702E+09 | 0.478017E+09 | 0.103425E+10 | 4282.76 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.862480E+09 | 0.176079E+09 | 0.00 | 1113773.73 | 9953674.30 | 2937000.50 | 0.403172E+09 | 0.00 | 0.41 |
February | 0.492689E+09 | 0.236149E+09 | 0.00 | 830998.67 | 17407899.60 | 5477216.97 | 0.232804E+09 | 0.00 | 0.44 |
March | 0.585621E+09 | 0.327746E+09 | 0.00 | 1207946.66 | 25072151.73 | 5814893.97 | 0.357840E+09 | 0.00 | 0.48 |
April | 91195164.88 | 0.783982E+09 | 0.00 | 993332.34 | 29687202.74 | 0.00 | 0.160363E+09 | 0.00 | 0.46 |
May | 0.00 | 0.212633E+10 | 0.00 | 0.00 | 17505736.03 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.254590E+10 | 0.00 | 0.00 | 11711513.30 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.284561E+10 | 0.00 | 0.00 | 18727580.25 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.301348E+10 | 0.00 | 0.00 | 14620539.09 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.226999E+10 | 0.00 | 0.00 | 18345783.09 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 51747632.59 | 0.171969E+10 | 0.00 | 1016944.51 | 14252036.56 | 0.00 | 0.207484E+09 | 0.00 | 0.45 |
November | 0.254669E+09 | 0.544017E+09 | 0.00 | 1847528.37 | 4074360.84 | 0.00 | 0.445182E+09 | 0.00 | 0.53 |
December | 0.727469E+09 | 0.387931E+09 | 0.00 | 972081.66 | 7903148.12 | 2009847.10 | 0.325505E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.306587E+10 | 0.169769E+11 | 0.00 | 7982605.95 | 0.189262E+09 | 16238958.53 | 0.213235E+10 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.176079E+09 | 0.00 | 0.00 | 4074360.84 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.862480E+09 | 0.301348E+10 | 0.00 | 1847528.37 | 29687202.74 | 5814893.97 | 0.445182E+09 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157986E+10 | 0.198923E+09 | 0.00 | 152346.64 | 68009132.28 | 77506040.63 | 0.119386E+09 | 0.00 | 0.37 |
February | 0.872836E+09 | 0.256796E+09 | 0.00 | 245829.54 | 79351833.49 | 33364796.30 | 0.109912E+09 | 0.00 | 0.37 |
March | 0.103416E+10 | 0.500021E+09 | 0.00 | 621354.22 | 63993827.34 | 28770861.54 | 0.234469E+09 | 0.00 | 0.41 |
April | 0.187363E+09 | 0.108824E+10 | 0.00 | 949546.75 | 61095947.05 | 0.00 | 0.153286E+09 | 0.00 | 0.40 |
May | 0.00 | 0.373718E+10 | 0.00 | 0.00 | 31116548.93 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.454984E+10 | 0.00 | 0.00 | 33576961.91 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.499857E+10 | 0.00 | 0.00 | 55514781.04 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.478262E+10 | 0.00 | 0.00 | 35416756.76 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.351358E+10 | 0.00 | 0.00 | 45596174.94 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.135472E+09 | 0.256924E+10 | 0.00 | 728951.37 | 40734774.65 | 0.00 | 0.174265E+09 | 0.00 | 0.37 |
November | 0.577371E+09 | 0.749132E+09 | 0.00 | 935484.75 | 58835178.67 | 0.00 | 0.239182E+09 | 0.00 | 0.40 |
December | 0.131834E+10 | 0.480079E+09 | 0.00 | 206410.08 | 71469985.36 | 53106642.21 | 79843408.92 | 0.00 | 0.37 |
Annual Sum or Average | 0.570539E+10 | 0.274242E+11 | 0.00 | 3839923.35 | 0.644712E+09 | 0.192748E+09 | 0.111034E+10 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.198923E+09 | 0.00 | 0.00 | 31116548.93 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.157986E+10 | 0.499857E+10 | 0.00 | 949546.75 | 79351833.49 | 77506040.63 | 0.239182E+09 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.669493E+09 | 0.163523E+09 | 0.00 | 762762.65 | 28656421.60 | 27260151.61 | 0.361037E+09 | 0.00 | 0.35 |
February | 0.364426E+09 | 0.247685E+09 | 0.00 | 798969.74 | 21339670.29 | 10577677.12 | 0.266252E+09 | 0.00 | 0.41 |
March | 0.417922E+09 | 0.466463E+09 | 0.00 | 1555717.43 | 18869359.23 | 10202352.66 | 0.493882E+09 | 0.00 | 0.52 |
April | 81687431.92 | 0.981086E+09 | 0.00 | 1300208.47 | 22667117.77 | 0.00 | 0.283300E+09 | 0.00 | 0.56 |
May | 0.00 | 0.299700E+10 | 0.00 | 0.00 | 19719311.30 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.355794E+10 | 0.00 | 0.00 | 21159938.43 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.397800E+10 | 0.00 | 0.00 | 35121475.95 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.372451E+10 | 0.00 | 0.00 | 22406442.89 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.269345E+10 | 0.00 | 0.00 | 28846460.92 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 64984317.70 | 0.204713E+10 | 0.00 | 772297.66 | 21678839.06 | 0.00 | 0.167743E+09 | 0.00 | 0.46 |
November | 0.251966E+09 | 0.595338E+09 | 0.00 | 1446451.39 | 23983995.21 | 0.00 | 0.377199E+09 | 0.00 | 0.48 |
December | 0.606048E+09 | 0.355268E+09 | 0.00 | 763527.33 | 25899315.99 | 22724998.82 | 0.244125E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.245653E+10 | 0.218074E+11 | 0.00 | 7399934.67 | 0.290348E+09 | 70765180.21 | 0.219354E+10 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.163523E+09 | 0.00 | 0.00 | 18869359.23 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.669493E+09 | 0.397800E+10 | 0.00 | 1555717.43 | 35121475.95 | 27260151.61 | 0.493882E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.839854E+09 | 0.425797E+09 | 0.00 | 6261144.50 | 29734016.93 | 29582853.89 | 0.219454E+10 | 0.00 | 0.68 |
February | 0.491346E+09 | 0.671467E+09 | 0.00 | 3712397.06 | 19951838.02 | 15285364.35 | 0.108934E+10 | 0.00 | 0.64 |
March | 0.755653E+09 | 0.789011E+09 | 0.00 | 3096034.20 | 36069179.89 | 10940777.77 | 0.955522E+09 | 0.00 | 0.60 |
April | 0.168456E+09 | 0.137712E+10 | 0.00 | 1522947.63 | 52671947.96 | 0.00 | 0.249177E+09 | 0.00 | 0.50 |
May | 0.00 | 0.379606E+10 | 0.00 | 0.00 | 31145876.98 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.436812E+10 | 0.00 | 0.00 | 33847003.13 | 0.00 | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.494053E+10 | 0.00 | 0.00 | 55567104.98 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.526329E+10 | 0.00 | 0.00 | 35450137.86 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.438831E+10 | 0.00 | 0.00 | 45639150.37 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.105572E+09 | 0.383701E+10 | 0.00 | 1646229.13 | 27535802.10 | 0.00 | 0.326480E+09 | 0.00 | 0.57 |
November | 0.290770E+09 | 0.138827E+10 | 0.00 | 5419600.69 | 26270687.83 | 0.00 | 0.127209E+10 | 0.00 | 0.78 |
December | 0.785095E+09 | 0.103398E+10 | 0.00 | 5485836.45 | 29464675.39 | 22962071.47 | 0.157865E+10 | 0.00 | 0.71 |
Annual Sum or Average | 0.343674E+10 | 0.322790E+11 | 0.00 | 27144189.66 | 0.423347E+09 | 78771067.47 | 0.766579E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.425797E+09 | 0.00 | 0.00 | 19951838.02 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.839854E+09 | 0.526329E+10 | 0.00 | 6261144.50 | 55567104.98 | 29582853.89 | 0.219454E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.815837E+09 | 0.205626E+09 | 0.00 | 1138703.12 | 23606856.98 | 46606785.74 | 0.427172E+09 | 0.00 | 0.44 |
February | 0.450616E+09 | 0.291191E+09 | 0.00 | 958561.89 | 29142518.38 | 19122397.72 | 0.278890E+09 | 0.00 | 0.48 |
March | 0.538044E+09 | 0.423998E+09 | 0.00 | 1611327.57 | 26676505.66 | 16419932.82 | 0.489197E+09 | 0.00 | 0.56 |
April | 89068616.92 | 0.106638E+10 | 0.00 | 1350338.80 | 25658634.73 | 0.00 | 0.200590E+09 | 0.00 | 0.58 |
May | 0.00 | 0.293195E+10 | 0.00 | 0.00 | 14244905.28 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.350969E+10 | 0.00 | 0.00 | 7888842.06 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.378276E+10 | 0.00 | 0.00 | 13282347.04 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.385291E+10 | 0.00 | 0.00 | 13159966.39 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.281872E+10 | 0.00 | 0.00 | 16510011.31 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 76848783.31 | 0.213682E+10 | 0.00 | 774721.00 | 14764628.66 | 0.00 | 0.160678E+09 | 0.00 | 0.49 |
November | 0.308561E+09 | 0.655871E+09 | 0.00 | 1497308.16 | 22359451.47 | 0.00 | 0.345944E+09 | 0.00 | 0.53 |
December | 0.749220E+09 | 0.444718E+09 | 0.00 | 878747.83 | 31160149.66 | 23920098.75 | 0.258145E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.302820E+10 | 0.221206E+11 | 0.00 | 8209708.36 | 0.238455E+09 | 0.106069E+09 | 0.216062E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.205626E+09 | 0.00 | 0.00 | 7888842.06 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.815837E+09 | 0.385291E+10 | 0.00 | 1611327.57 | 31160149.66 | 46606785.74 | 0.489197E+09 | 0.00 | 0.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.230864E+12 | 0.467700E+10 | 0.00 | 0.149170E+12 | 0.670672E+11 |
February | 0.242390E+12 | 0.291159E+10 | 0.00 | 0.106143E+12 | 0.916563E+11 |
March | 0.267465E+12 | 0.261697E+10 | 0.00 | 0.118695E+12 | 0.111405E+12 |
April | 0.296152E+12 | -0.122430E+10 | 0.00 | 0.297726E+11 | 0.177883E+12 |
May | 0.290986E+12 | -0.853508E+10 | 0.00 | -0.746200E+11 | 0.315930E+12 |
June | 0.288613E+12 | -0.863824E+10 | 0.00 | -0.853556E+11 | 0.337509E+12 |
July | 0.298676E+12 | -0.108099E+11 | 0.00 | -0.953795E+11 | 0.351246E+12 |
August | 0.278361E+12 | -0.110449E+11 | 0.00 | -0.949605E+11 | 0.364290E+12 |
September | 0.241186E+12 | -0.925180E+10 | 0.00 | -0.756928E+11 | 0.306283E+12 |
October | 0.251058E+12 | -0.649531E+10 | 0.00 | -0.232300E+11 | 0.272591E+12 |
November | 0.201299E+12 | 0.429323E+09 | 0.00 | 0.844169E+11 | 0.145831E+12 |
December | 0.207287E+12 | 0.326685E+10 | 0.00 | 0.138243E+12 | 0.970831E+11 |
Annual Sum or Average | 0.309434E+13 | -0.420979E+11 | 0.00 | 0.177202E+12 | 0.263877E+13 |
Minimum of Months | 0.201299E+12 | -0.110449E+11 | 0.00 | -0.953795E+11 | 0.670672E+11 |
Maximum of Months | 0.298676E+12 | 0.467700E+10 | 0.00 | 0.149170E+12 | 0.364290E+12 |