Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2024-07-03 12:20:06


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1552.93 311.70 311.70
Net Site Energy 1552.93 311.70 311.70
Total Source Energy 4918.12 987.14 987.14
Net Source Energy 4918.12 987.14 987.14


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 114.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 292.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 232.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 67.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 48.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1552.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 114.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 292.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 232.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 67.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 48.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 114.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 292.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 232.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 51.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 67.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 48.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 104.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 311.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 104.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 311.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1552.928 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1552.928 100.00
     
Total On-Site and Utility Electric Sources 1552.928 100.00
Total Electricity End Uses 1552.928 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 132.17
Time Setpoint Not Met During Occupied Cooling 159.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 1762.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.6636 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 6.6636 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.6636 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.6636 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.6636 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.6636 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.6636 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.6636 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.6636 18.58 8.0700  
Total 4982.19             6.6636 9.29 24.1370  
Conditioned Total 4982.19             6.6636 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 6.6636 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 13-FEB-07:10 - - - - - - - - - - - 05-JAN-12:09
Heating 192831.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8334.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 22496.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 974.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4952.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 1946.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 237229.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 192831.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 8334.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 43.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 15327.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 974.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 4952.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 1946.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 362.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 925.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 736.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 162.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 213.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 152.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4918.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 72.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 185.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 147.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 42.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 30.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 987.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 72.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 185.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 147.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 42.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 30.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 987.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2]
CORE_BOTTOM VAV BOX COMPONENT 2.55 0.293773 0.250000 0.637784 0.783394 0.500000 0.001297
CORE_MID VAV BOX COMPONENT 2.04 0.367614 0.312000 0.636075 0.980303 0.500000 0.001036
CORE_TOP VAV BOX COMPONENT 2.19 0.342347 0.291000 0.637048 0.912925 0.500000 0.001113
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.689999 0.228974 0.195000 0.134550 0.610597 0.500000 0.001664
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.670231 0.149235 0.127000 0.085119 0.397959 0.500000 0.002553
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 0.802968 0.196760 0.167000 0.134096 0.524692 0.500000 0.001936
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.741356 0.134909 0.115000 0.085256 0.359756 0.500000 0.002824
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.552220 0.286103 0.243000 0.134189 0.762941 0.500000 0.001332
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.573002 0.174557 0.148000 0.084804 0.465486 0.500000 0.002183
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.651526 0.242495 0.206000 0.134214 0.646653 0.500000 0.001571
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.594270 0.168299 0.143000 0.084981 0.448798 0.500000 0.002264
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.594862 0.265594 0.226000 0.134439 0.708250 0.500000 0.001435
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.644159       0.414066 0.500000 0.002454
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 0.707101 0.223436 0.190000 0.134349 0.595828 0.500000 0.001705
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.671144 0.149022 0.127000 0.085235 0.397392 0.500000 0.002557
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
CORE_BOTTOM VAV BOX REHEAT COIL 20537.30
CORE_MID VAV BOX REHEAT COIL 20482.27
CORE_TOP VAV BOX REHEAT COIL 35177.27
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16046.65
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 10409.10
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 15909.27
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10492.21
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 12189.64
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 7977.39
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 12065.14
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8056.71
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 12584.22
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 8205.96
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 12455.48
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8281.80
PACU_VAV_BOT HEATING COIL 18409.17
PACU_VAV_MID HEATING COIL 19366.70
PACU_VAV_TOP HEATING COIL 18591.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.46 1.08 4.92 1.68 4.45 4.45 0.300000 0.376905 4.45
PACU_VAV_MID 2.33 1.08 4.66 1.90 4.08 4.08 0.300000 0.466630 4.08
PACU_VAV_TOP 2.55 1.08 5.09 2.73 4.80 4.80 0.300000 0.569538 4.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.45
PACU_VAV_MID_OA_CONTROLLER 4.08
PACU_VAV_TOP_OA_CONTROLLER 4.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.45 98003.87 0.740118 1.48 32664.69 0.740118
PACU_VAV_MID COOLING COIL 4.08 92078.84 0.731799 1.36 30689.88 0.731799
PACU_VAV_TOP COOLING COIL 4.80 103530.70 0.748178 1.60 34506.78 0.748178
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.45
PACU_VAV_MID FAN 4.08
PACU_VAV_TOP FAN 4.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 6.664 89.459 0.000 0.000 0.000 0.000 96.123 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.9622 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.9482 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.202 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.3192 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.3371 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8052
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8206
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5978
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 3.056
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.890
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 3.056
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.890
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
39 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
40 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
41 0 21.361010 0.87247630E-01 5.4456762  
42 7 -0.27384127E-12 0.12865281E-14 -0.83346422E-13 0.81323336E-16
43 6 0.26454352E-07 0.26406074E-09 0.60786733E-08 -0.12333448E-12
44 5 -0.17878666E-03 0.22931636E-05 -0.92101048E-04 0.60153540E-08
45 4 0.27880517 0.11305828E-02 0.94889811E-01 -0.31698392E-04
46 3 -7.0018852 0.35426556E-01 -2.2604600 0.27713709E-01
47 2 39.998753 0.12720283 14.942758 -0.32362551
48 1 -79.877006 0.57894353E-01 -28.852534 1.0643678
49 0 46.824343 0.11744712E-02 16.298269  
50 7 -0.27620064E-12 0.12774393E-14 -0.83964131E-13 0.81942822E-16
51 6 0.26622461E-07 0.26074659E-09 0.61157793E-08 -0.12423095E-12
52 5 -0.17965003E-03 0.22617301E-05 -0.92535175E-04 0.60516003E-08
53 4 0.27982997 0.11139309E-02 0.95257664E-01 -0.31841476E-04
54 3 -7.0222151 0.34872839E-01 -2.2664901 0.27813240E-01
55 2 40.065841 0.12511414 14.967577 -0.32437249
56 1 -79.928458 0.56904129E-01 -28.874810 1.0654641
57 0 46.824343 0.11535943E-02 16.297719  
58 7 -0.27931930E-12 0.13886628E-14 -0.87137092E-13 0.18759942E-15
59 6 0.23561308E-07 0.31712788E-09 0.54400317E-08 -0.10799411E-12
60 5 -0.16378969E-03 0.28142694E-05 -0.84539011E-04 0.53904798E-08
61 4 0.26080053 0.14141629E-02 0.88437074E-01 -0.29205444E-04
62 3 -6.6442204 0.45062581E-01 -2.1544048 0.25964059E-01
63 2 38.817908 0.16418932 14.505027 -0.31048073
64 1 -78.970774 0.75677137E-01 -28.459322 1.0450580
65 0 46.824349 0.15543837E-02 16.308247  
66 7 -0.13059908E-08 -0.16504735E-15 0.90649122E-14 -0.12541312E-15
67 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
68 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
69 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
70 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
71 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
72 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
73 0 0.32650513 0.16166393E-04 60.838472  
74 7 -0.12346633E-08 -0.14425327E-15 0.91357699E-14 -0.10087110E-15
75 6 0.94177090E-05 0.64929528E-08 0.31789869E-02 -0.26668006E-04
76 5 -0.68205191E-03 0.38502154E-05 -0.22310594 0.19506899E-02
77 4 0.15716902E-01 0.17535208E-03 4.8192406 -0.45165923E-01
78 3 -0.13809356 0.13952366E-02 -37.963195 0.39801023
79 2 0.49043520 0.23220647E-02 116.37063 -1.4164235
80 1 -0.70792287 0.70803996E-03 -143.84059 2.0479434
81 0 0.34515858 0.17069463E-04 60.838472  
82 7 -0.13059908E-08 -0.16504702E-15 0.90649122E-14 -0.12541312E-15
83 6 0.89164571E-05 0.61445766E-08 0.31804070E-02 -0.26679919E-04
84 5 -0.64531733E-03 0.36428408E-05 -0.22318667 0.19514025E-02
85 4 0.14868215E-01 0.16589759E-03 4.8205855 -0.45178851E-01
86 3 -0.13063200 0.13198961E-02 -37.970795 0.39809422
87 2 0.46393162 0.21965806E-02 116.38542 -1.4166214
88 1 -0.66966470 0.66967549E-03 -143.84930 2.0480865
89 0 0.32650513 0.16166393E-04 60.838472  
90 7 -0.12345751E-08 -0.14398051E-15 0.92894684E-14 -0.10085648E-15
91 6 0.94183649E-05 0.64934092E-08 0.31789851E-02 -0.26667991E-04
92 5 -0.68209995E-03 0.38504865E-05 -0.22310583 0.19506890E-02
93 4 0.15718012E-01 0.17536444E-03 4.8192388 -0.45165906E-01
94 3 -0.13810332 0.13953351E-02 -37.963185 0.39801012
95 2 0.49046985 0.23222288E-02 116.37061 -1.4164232
96 1 -0.70797289 0.70809005E-03 -143.84058 2.0479432
97 0 0.34518296 0.17070678E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.424_SHGC_EAST_0.249 35 1 VerySmooth 2.409 2.409 1.000 0.250    
2 WINDOW_U_0.424_SHGC_SOUTH_0.249 36 1 VerySmooth 2.409 2.409 1.000 0.250    
3 WINDOW_U_0.424_SHGC_WEST_0.249 37 1 VerySmooth 2.409 2.409 1.000 0.250    
4 WINDOW_U_0.424_SHGC_NORTH_0.249 38 1 VerySmooth 2.409 2.409 1.000 0.250    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.98174E-002 0.16038 0.62134 0.62134 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12245 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.98174E-002 0.16038 0.62134 0.62134 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12245 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.98174E-002 0.16038 0.62134 0.62134 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12245 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.98174E-002 0.16038 0.62134 0.62134 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12245 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9876E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0268E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.5034E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5358E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.3121E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.3378E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9048E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9212E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1007
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5921E-002
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1122
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9771E-002
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6206E-002
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0413E-002
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1945E-002
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.1958E-002
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.9904E-003
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0437E-003
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.5066E-003
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.5545E-003
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.3151E-003
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.3510E-003
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9047E-003
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9210E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.4493E-002
26 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0494E-002
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.2883E-002
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8840E-002
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.1659E-002
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5527E-002
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7535E-002
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7678E-002
33 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7894E-004
34 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8053E-004
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6401E-004
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.6517E-004
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2824E-004
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2868E-004
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3903E-004
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.3960E-004
41 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9303E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9681E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4705E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5013E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1767E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2002E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9047E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9210E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7223E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5417E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1120E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1824E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9625E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.3066E-003
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1945E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1958E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9294E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9674E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4691E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4983E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1741E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1911E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9048E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9212E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8870E-002
66 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3300E-002
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3808E-002
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.0040E-002
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7587E-002
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9122E-002
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7535E-002
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.7679E-002
73 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7839E-004
74 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8175E-004
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4043E-004
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4384E-004
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4155E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4331E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3905E-004
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3961E-004
81 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1088
82 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.6949E-002
83 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1209
84 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.1608E-002
85 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.3084E-002
86 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.9068E-002
87 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.6447E-002
88 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.6997E-002
89 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2765E-002
90 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.9482E-002
91 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1295E-002
92 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7901E-002
93 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.0446E-002
94 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4791E-002
95 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.6836E-002
96 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.7257E-002
97 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.1220E-002
98 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0325E-002
99 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.4696E-002
100 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6078E-002
101 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3197E-002
102 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2232E-002
103 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.6447E-002
104 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6997E-002
105 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.7613E-002
106 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.2607E-002
107 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.2800E-002
108 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9497E-002
109 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6778E-002
110 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8660E-002
111 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.6836E-002
112 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.7257E-002
113 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1088
114 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.6943E-002
115 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1209
116 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.1601E-002
117 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.3079E-002
118 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.9063E-002
119 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.6443E-002
120 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.6995E-002
121 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2764E-002
122 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.9479E-002
123 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1293E-002
124 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7899E-002
125 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.0443E-002
126 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4788E-002
127 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.6832E-002
128 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.7255E-002
129 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.1221E-002
130 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0324E-002
131 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.4696E-002
132 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6077E-002
133 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3196E-002
134 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2231E-002
135 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.6443E-002
136 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6995E-002
137 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.7613E-002
138 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.2606E-002
139 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.2800E-002
140 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9496E-002
141 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6775E-002
142 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8658E-002
143 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.6833E-002
144 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.7255E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 34147.06023 34147.06023 2.55114 2.55114 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 6693.11398 6693.11398 0.29144 0.42469 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 27315.12564 27315.12564 2.03870 2.03870 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 14017.15182 14017.15182 0.61513 0.61513 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 29049.85167 29049.85167 2.18917 2.18917 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 34.02000 1.44726E-002 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 24779.90628 24779.90628 1.09243 1.09243 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 9155.93771 9155.93771 0.69000 0.69000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.11500 1.44727E-002 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 11270.28953 11270.28953 0.49833 0.49833 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 8893.66745 8893.66745 0.67023 0.67023 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 31.26500 1.44675E-002 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 7310.33060 7310.33060 0.32325 0.32325 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 10655.00355 10655.00355 0.80297 0.80297 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 11174.07733 11174.07733 0.49406 0.49406 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 9837.47827 9837.47827 0.74136 0.74136 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.91167 1.44705E-002 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 7368.53526 7368.53526 0.32583 0.32583 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7327.77353 7327.77353 0.55222 0.55222 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 34.30500 1.44731E-002 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 8567.86215 8567.86215 0.37855 0.37855 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 7603.60272 7603.60272 0.57300 0.57300 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.50250 1.44680E-002 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 5606.51686 5606.51686 0.24774 0.24774 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 8645.55172 8645.55172 0.65153 0.65153 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 8480.67417 8480.67417 0.37468 0.37468 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 7885.82876 7885.82876 0.59427 0.59427 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.59500 1.44700E-002 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 5662.06017 5662.06017 0.25020 0.25020 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 7893.54968 7893.54968 0.59486 0.59486 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 34.30500 1.44731E-002 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 8844.85024 8844.85024 0.39080 0.39080 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 8547.75837 8547.75837 0.64416 0.64416 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 31.02750 1.44671E-002 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 5767.00794 5767.00794 0.25484 0.25484 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 9382.93103 9382.93103 0.70710 0.70710 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40000 1.44733E-002 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 8754.68860 8754.68860 0.38680 0.38680 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 8905.84678 8905.84678 0.67114 0.67114 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 5820.12046 5820.12046 0.25719 0.25719 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 69548.22 4.44637 4.44637 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 21099.13 1.67586 1.67586 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00
3 PACU_VAV_MID Cooling Sensible 64540.26 4.08196 4.08196 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 PACU_VAV_MID Heating Sensible 21042.03 1.90476 1.90476 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00
5 PACU_VAV_TOP Cooling Sensible 73814.24 4.80021 4.80021 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 20984.74 2.73390 2.73390 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.55114
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29377
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25000
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63778
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.78339
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.29692E-003
8 Coil:Heating:Electric CORE_BOTTOM VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 20537.30422
9 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.03870
10 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36761
11 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31200
12 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63608
13 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.98030
14 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03641E-003
16 Coil:Heating:Electric CORE_MID VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 20482.26978
17 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.18917
18 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34235
19 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29100
20 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63705
21 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.91292
22 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
23 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.11291E-003
24 Coil:Heating:Electric CORE_TOP VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 35177.26774
25 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.69000
26 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22897
27 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.19500
28 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13455
29 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61060
30 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
31 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.66395E-003
32 Coil:Heating:Electric PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 16046.64759
33 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.67023
34 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14923
35 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12700
36 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.51193E-002
37 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39796
38 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
39 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55302E-003
40 Coil:Heating:Electric PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 10409.09862
41 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.80297
42 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19676
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.16700
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13410
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52469
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.93637E-003
48 Coil:Heating:Electric PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 15909.27491
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.74136
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13491
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11500
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.52559E-002
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35976
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
55 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.82413E-003
56 Coil:Heating:Electric PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 10492.20607
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.55222
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28610
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24300
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13419
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.76294
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.33169E-003
64 Coil:Heating:Electric PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12189.64017
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.57300
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17456
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14800
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48043E-002
69 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46549
70 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.18266E-003
72 Coil:Heating:Electric PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 7977.39003
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.65153
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24249
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20600
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13421
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64665
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.57117E-003
80 Coil:Heating:Electric PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12065.13886
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.59427
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16830
83 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14300
84 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.49807E-002
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44880
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.26383E-003
88 Coil:Heating:Electric PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8056.70686
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.59486
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26559
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22600
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13444
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.70825
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.43452E-003
96 Coil:Heating:Electric PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12584.22426
97 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.64416
98 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41407
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.45371E-003
101 Coil:Heating:Electric PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8205.95606
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.70710
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22344
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.19000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13435
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.59583
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.70519E-003
109 Coil:Heating:Electric PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 12455.47912
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.67114
111 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14902
112 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12700
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.52353E-002
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39739
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.55667E-003
117 Coil:Heating:Electric PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Nominal Capacity [W] 8281.79919
118 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.46108
119 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07597
120 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 4.92215
121 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.67586
122 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.44637
123 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.44637
124 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
125 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.37690
126 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.32798
127 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07513
128 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.65597
129 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.90476
130 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.08196
131 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.08196
132 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
133 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.46663
134 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.54686
135 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07607
136 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.09372
137 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.73390
138 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 4.80021
139 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 4.80021
140 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
141 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.56954
142 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.44637
143 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.08196
144 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 4.80021
145 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.44637
146 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.44637
147 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 98003.86889
148 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74012
149 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.48198
150 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 32664.68950
151 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74012
152 Coil:Heating:Electric PACU_VAV_BOT HEATING COIL Design Size Nominal Capacity [W] 18409.16700
153 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.44637
154 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.08196
155 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.08196
156 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 92078.84181
157 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.73180
158 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.36052
159 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 30689.87798
160 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.73180
161 Coil:Heating:Electric PACU_VAV_MID HEATING COIL Design Size Nominal Capacity [W] 19366.69512
162 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.08196
163 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.80021
164 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.80021
165 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 103530.70087
166 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.74818
167 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.59991
168 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 34506.78260
169 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.74818
170 Coil:Heating:Electric PACU_VAV_TOP HEATING COIL Design Size Nominal Capacity [W] 18591.58984
171 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 4.80021
172 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
173 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
174 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
175 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
176 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 97457.34 332538.26 12.34 3.15 3.53 3.72 3.89 10.76 12.06 12.70 13.27 4.9583 3.9503 2.6595 1.1038
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 91639.28 312686.21 12.39 3.16 3.55 3.74 3.90 10.80 12.11 12.76 13.30 4.5519 3.6218 2.4374 1.0212
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 102873.63 351019.40 12.29 3.14 3.52 3.71 3.88 10.73 12.01 12.64 13.23 5.3528 4.2685 2.8746 1.1835


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_NORTH_0.249 N/A 2.409 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_EAST_0.249 N/A 2.409 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_SOUTH_0.249 N/A 2.409 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.202 1.019   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_WEST_0.249 N/A 2.409 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_NORTH_0.249 N/A 2.409 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_NORTH_0.249 N/A 2.409 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_NORTH_0.249 N/A 2.409 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_EAST_0.249 N/A 2.409 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_EAST_0.249 N/A 2.409 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.337 0.312   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_SOUTH_0.249 N/A 2.409 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_SOUTH_0.249 N/A 2.409 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_SOUTH_0.249 N/A 2.409 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.319 0.296   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.962 0.841   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_WEST_0.249 N/A 2.409 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_WEST_0.249 N/A 2.409 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.337 0.312   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_NORTH_0.249 N/A 2.409 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_EAST_0.249 N/A 2.409 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_SOUTH_0.249 N/A 2.409 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.948 0.830   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.424_SHGC_WEST_0.249 N/A 2.409 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.9654150739E-003 5.5549809222E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.3261322723E-002 2.9906719500E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.8588546140E-003 4.1863616964E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.1276822434E-003 3.8015006788E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 5.4773404050E-003 6.5794786937E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 1.4959612232E-002 1.1143588273E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.3614495067E-002 2.4187691278E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 3.4865674469E-002 2.5955271540E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 3.5382680917E-002 2.7775413398E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 3.5075199706E-002 2.4614006716E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.2703846438E-002 2.0312548890E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.3583467546E-002 2.2070499037E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.4082673473E-002 2.2965863307E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.3606393534E-002 2.0735781370E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.6282249867E-002 2.2309110437E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 2.7541177191E-002 2.4298747236E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 2.8019663975E-002 2.5627789332E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 2.7688608785E-002 2.2777930365E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2916.53 26.24 0.00 1090.34 1542.89 5576.01



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.830 0.948 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.830 0.948 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.019 1.202 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.019 1.202 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.320 0.337 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.841 0.962 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.304 0.319 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.841 0.962 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.320 0.337 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.830 0.948 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.830 0.948 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.830 0.948 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.424_SHGC_NORTH_0.249   65.26 0.00 0.00 65.26 65.26 2.409 0.250 0.275             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.424_SHGC_EAST_0.249   43.51 0.00 0.00 43.51 43.51 2.409 0.250 0.275             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.424_SHGC_SOUTH_0.249   65.26 0.00 0.00 65.26 65.26 2.409 0.250 0.275             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.424_SHGC_WEST_0.249   43.51 0.00 0.00 43.51 43.51 2.409 0.250 0.275             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.424_SHGC_NORTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.424_SHGC_NORTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.424_SHGC_NORTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.424_SHGC_EAST_0.249   41.85 0.00 0.00 41.85 41.85 2.409 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.424_SHGC_EAST_0.249   1.65 0.00 0.00 1.65 1.65 2.409 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.424_SHGC_SOUTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.424_SHGC_SOUTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.424_SHGC_SOUTH_0.249   21.75 0.00 0.00 21.75 21.75 2.409 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.424_SHGC_WEST_0.249   41.85 0.00 0.00 41.85 41.85 2.409 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.424_SHGC_WEST_0.249   1.65 0.00 0.00 1.65 1.65 2.409 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.424_SHGC_NORTH_0.249   65.26 0.00 0.00 65.26 65.26 2.409 0.250 0.275             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.424_SHGC_EAST_0.249   43.51 0.00 0.00 43.51 43.51 2.409 0.250 0.275             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.424_SHGC_SOUTH_0.249   65.26 0.00 0.00 65.26 65.26 2.409 0.250 0.275             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.424_SHGC_WEST_0.249   43.51 0.00 0.00 43.51 43.51 2.409 0.250 0.275             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.409 0.250 0.275                      
North Total or Average             195.79 2.409 0.250 0.275                      
Non-North Total or Average             456.84 2.409 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.16 0.0000 Y 6.78
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.82 0.0000 Y 4.24
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.63 0.0000 Y 6.65
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.98 0.0000 Y 4.27
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.07 0.0000 Y 6.76
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.76 0.0000 Y 4.23
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.59 0.0000 Y 6.64
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.91 0.0000 Y 4.25
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.16 0.0000 Y 6.78
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.82 0.0000 Y 4.24
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.63 0.0000 Y 6.65
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.98 0.0000 Y 4.27
Interior Lighting Total       6.6636 4982.19 33199.39               232.55


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   41.77 41.77 4.42
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.77 62.77 4.80
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.77 47.60 42.13
Exterior Lighting Total 5686.19           51.35



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   98003.87 72534.41 25469.45 0.74 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   92078.84 67383.23 24695.62 0.73 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   103530.70 77459.41 26071.30 0.75 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   97457.3 3.15 10.76 N/A N/A 12.34
PACU_VAV_MID COOLING COIL   91639.3 3.16 10.80 N/A N/A 12.39
PACU_VAV_TOP COOLING COIL   102873.6 3.14 10.73 N/A N/A 12.29
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric   20537.30 1.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric   20482.27 1.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric   35177.27 1.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   16046.65 1.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   10409.10 1.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   15909.27 1.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   10492.21 1.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   12189.64 1.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   7977.39 1.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   12065.14 1.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   8056.71 1.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric   12584.22 1.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric   8205.96 1.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric   12455.48 1.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric   8281.80 1.00
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric   18409.17 1.00
PACU_VAV_MID HEATING COIL Coil:Heating:Electric   19366.70 1.00
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric   18591.59 1.00


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.45 9733.16 2189.01 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 4.08 8935.45 2189.01 1.00 1.15 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 4.80 10507.72 2189.01 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 97457.34 3.15 10.76 12.34 4.9583 3.53 12.06 3.9503 3.72 12.70 2.6595 3.89 13.27 1.1038
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 91639.28 3.16 10.80 12.39 4.5519 3.55 12.11 3.6218 3.74 12.76 2.4374 3.90 13.30 1.0212
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 102873.63 3.14 10.73 12.29 5.3528 3.52 12.01 4.2685 3.71 12.64 2.8746 3.88 13.23 1.1835
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 34147.06 34147.06 34.72 2.551 2.551 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00886 27.37 0.01446 0.425 0.00
CORE_MID 27315.13 27315.13 27.77 2.039 2.039 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00895 27.37 0.01446 0.425 0.00
CORE_TOP 29049.85 29049.85 29.54 2.189 2.189 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 24.00 24.00 0.00891 34.02 0.01447 0.425 0.00
PERIMETER_TOP_ZN_3 9155.94 9155.94 44.16 0.690 0.690 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00888 34.12 0.01447 0.090 0.00
PERIMETER_TOP_ZN_2 8893.67 8893.67 67.75 0.670 0.670 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 24.00 24.00 0.00875 31.26 0.01447 0.057 0.00
PERIMETER_TOP_ZN_1 10655.00 10655.00 51.39 0.803 0.803 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00883 34.40 0.01447 0.090 0.00
PERIMETER_TOP_ZN_4 9837.48 9837.48 74.95 0.741 0.741 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00873 32.91 0.01447 0.057 0.00
PERIMETER_BOT_ZN_3 7327.77 7327.77 35.34 0.552 0.552 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00891 34.30 0.01447 0.090 0.00
PERIMETER_BOT_ZN_2 7603.60 7603.60 57.93 0.573 0.573 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 24.00 24.00 0.00876 31.50 0.01447 0.057 0.00
PERIMETER_BOT_ZN_1 8645.55 8645.55 41.70 0.652 0.652 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00885 34.40 0.01447 0.090 0.00
PERIMETER_BOT_ZN_4 7885.83 7885.83 60.08 0.594 0.594 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00875 32.59 0.01447 0.057 0.00
PERIMETER_MID_ZN_3 7893.55 7893.55 38.07 0.595 0.595 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00892 34.30 0.01447 0.090 0.00
PERIMETER_MID_ZN_2 8547.76 8547.76 65.12 0.644 0.644 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 24.00 24.00 0.00875 31.03 0.01447 0.057 0.00
PERIMETER_MID_ZN_1 9382.93 9382.93 45.25 0.707 0.707 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00885 34.40 0.01447 0.090 0.00
PERIMETER_MID_ZN_4 8905.85 8905.85 67.85 0.671 0.671 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00874 32.75 0.01447 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 6693.11 6693.11 6.81 0.291 0.425 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
CORE_MID 14017.15 14017.15 14.25 0.615 0.615 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
CORE_TOP 24779.91 24779.91 25.19 1.092 1.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 0.425 0.00
PERIMETER_TOP_ZN_3 11270.29 11270.29 54.36 0.498 0.498 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_TOP_ZN_2 7310.33 7310.33 55.69 0.323 0.323 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 -6.30 0.00230 0.057 0.00
PERIMETER_TOP_ZN_1 11174.08 11174.08 53.89 0.494 0.494 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.090 0.00
PERIMETER_TOP_ZN_4 7368.54 7368.54 56.14 0.326 0.326 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.057 0.00
PERIMETER_BOT_ZN_3 8567.86 8567.86 41.32 0.379 0.379 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 -6.30 0.00230 0.090 0.00
PERIMETER_BOT_ZN_2 5606.52 5606.52 42.71 0.248 0.248 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.057 0.00
PERIMETER_BOT_ZN_1 8480.67 8480.67 40.90 0.375 0.375 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00774 -6.30 0.00230 0.090 0.00
PERIMETER_BOT_ZN_4 5662.06 5662.06 43.14 0.250 0.250 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 -6.30 0.00230 0.057 0.00
PERIMETER_MID_ZN_3 8844.85 8844.85 42.66 0.391 0.391 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -6.30 0.00230 0.090 0.00
PERIMETER_MID_ZN_2 5767.01 5767.01 43.94 0.255 0.255 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -6.30 0.00230 0.057 0.00
PERIMETER_MID_ZN_1 8754.69 8754.69 42.22 0.387 0.387 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00769 -6.30 0.00230 0.090 0.00
PERIMETER_MID_ZN_4 5820.12 5820.12 44.34 0.257 0.257 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00770 -6.30 0.00230 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.45 4.45 1.68 1.68 4.4464 1.6759 4.4464 0.3769 0.3000
PACU_VAV_MID 4.08 4.08 1.90 1.90 4.0820 1.9048 4.0820 0.4666 0.3000
PACU_VAV_TOP 4.80 4.80 2.73 2.73 4.8002 2.7339 4.8002 0.5695 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 20537.304 20537.304 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20537.30 13675.49 0.424691 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 6693.11 0.00 -999.00 -999.00
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 20482.270 20482.270 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20482.27 19807.89 0.615132 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 14017.15 0.00 -999.00 -999.00
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 35177.268 35177.268 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 35177.27 35177.27 1.092427 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 24779.91 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 16046.648 16046.648 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16046.65 16046.65 0.498327 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775921 48.3835 11270.29 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 10409.099 10409.099 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10409.10 10409.10 0.323254 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775423 48.3529 7310.33 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 15909.275 15909.275 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15909.27 15909.27 0.494061 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775665 48.3677 11174.08 0.00 -999.00 -999.00
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 10492.206 10492.206 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10492.21 10492.21 0.325835 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775659 48.3674 7368.54 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 12189.640 12189.640 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12189.64 12189.64 0.378548 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00774955 48.3237 8567.86 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 7977.390 7977.390 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7977.39 7977.39 0.247737 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00775705 48.3699 5606.52 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 12065.139 12065.139 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12065.14 12065.14 0.374682 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00774271 48.2816 8480.67 0.00 -999.00 -999.00
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8056.707 8056.707 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8056.71 8056.71 0.250200 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00776354 48.4097 5662.06 0.00 -999.00 -999.00
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 12584.224 12584.224 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12584.22 12584.22 0.390802 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00769671 47.9988 8844.85 0.00 -999.00 -999.00
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 8205.956 8205.956 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8205.96 8205.96 0.254835 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00769853 48.0100 5767.01 0.00 -999.00 -999.00
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 12455.479 12455.479 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12455.48 12455.48 0.386804 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00769012 47.9582 8754.69 0.00 -999.00 -999.00
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 8281.799 8281.799 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8281.80 8281.80 0.257191 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00770389 48.0430 5820.12 0.00 -999.00 -999.00
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 98003.869 72534.414 4.446372 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 98003.84 77795.14 4.446372 26.24 18.07 0.01007986 10.96 10.96 0.00850000 34.40 0.01447326 23.54 21.5029 24.00 0.00887256 46.0252 58856.66 0.00 101055.14 72495.14
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_BOT 18409.167 18409.167 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18409.17 18409.17 1.333912 0.97 0.37 0.00378094 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 71.6764 19.63 0.00748755 50.8195 14377.80 0.00 -999.00 -999.00
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 92078.842 67383.226 4.081959 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 92523.20 72214.24 4.081959 26.43 18.25 0.01023096 10.96 10.96 0.00850000 34.30 0.01447309 23.52 23.4226 24.00 0.00892434 46.2902 53877.58 0.00 94945.65 67367.94
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_MID 19366.695 19366.695 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19366.70 19366.70 1.224588 -0.76 -1.11 0.00344167 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 78.0753 19.41 0.00728046 50.1197 17431.76 0.00 -999.00 -999.00
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 103530.701 77459.406 4.800213 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 103414.01 82845.18 4.800213 26.02 17.92 0.00998823 10.96 10.96 0.00850000 34.12 0.01447274 23.47 19.9179 24.00 0.00886880 46.0061 63512.46 0.00 106754.05 77354.56
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoopHVAC PACU_VAV_TOP 18591.590 18591.590 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 18591.59 18591.59 1.440064 1.73 1.22 0.00406899 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 66.3929 17.66 0.00740220 56.8686 20171.77 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes No unknown No 20537.304 20537.304 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20537.30 13675.49 1.0000 0.49305639 0.424691 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20537.30 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.60 0.00800000 21.00 0.00800000 49.8624 6693.11 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes No unknown No 20482.270 20482.270 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20482.27 19807.89 1.0000 0.71415408 0.615132 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20482.27 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.8624 14017.15 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes No unknown No 35177.268 35177.268 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 35177.27 35177.27 1.0000 1.26828203 1.092427 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 35177.27 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 49.8624 24779.91 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes No unknown No 16046.648 16046.648 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16046.65 16046.65 1.0000 0.57854621 0.498327 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 16046.65 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775921 21.00 0.00775921 48.3835 11270.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes No unknown No 10409.099 10409.099 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10409.10 10409.10 1.0000 0.37528989 0.323254 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10409.10 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775423 21.00 0.00775423 48.3529 7310.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes No unknown No 15909.275 15909.275 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15909.27 15909.27 1.0000 0.57359337 0.494061 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 15909.27 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775665 21.00 0.00775665 48.3677 11174.08 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes No unknown No 10492.206 10492.206 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10492.21 10492.21 1.0000 0.37828624 0.325835 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10492.21 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775659 21.00 0.00775659 48.3674 7368.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes No unknown No 12189.640 12189.640 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12189.64 12189.64 1.0000 0.43948557 0.378548 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12189.64 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00774955 21.00 0.00774955 48.3237 8567.86 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes No unknown No 7977.390 7977.390 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7977.39 7977.39 1.0000 0.28761701 0.247737 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7977.39 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00775705 21.00 0.00775705 48.3699 5606.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes No unknown No 12065.139 12065.139 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12065.14 12065.14 1.0000 0.43499680 0.374682 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12065.14 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00774271 21.00 0.00774271 48.2816 8480.67 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes No unknown No 8056.707 8056.707 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8056.71 8056.71 1.0000 0.29047670 0.250200 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8056.71 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00776354 21.00 0.00776354 48.4097 5662.06 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes No unknown No 12584.224 12584.224 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12584.22 12584.22 1.0000 0.45371192 0.390802 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12584.22 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00769671 21.00 0.00769671 47.9988 8844.85 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes No unknown No 8205.956 8205.956 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8205.96 8205.96 1.0000 0.29585773 0.254835 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8205.96 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00769853 21.00 0.00769853 48.0100 5767.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes No unknown No 12455.479 12455.479 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12455.48 12455.48 1.0000 0.44907014 0.386804 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 12455.48 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00769012 21.00 0.00769012 47.9582 8754.69 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Electric Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes No unknown No 8281.799 8281.799 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8281.80 8281.80 1.0000 0.29859218 0.257191 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8281.80 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00770389 21.00 0.00770389 48.0430 5820.12 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 98003.869 72534.414 4.446372 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.5780 1004.8586 1.1610 PACU_VAV_BOT FAN Fan:VariableVolume 4.446372 5.16213338   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 98003.84 77795.14 1.0000 5.16213338 4.446372 26.24 18.07 0.01007986 52068.6 10.96 10.96 0.00850000 32442.1 -999.0 -999.00 -999.00 -999.00 9733.157 88270.69 34.40 0.01447326 23.54 0.95610000 21.5029 24.00 0.00887256 24.00 0.00887256 46.0252 58856.66 0.00 101055.14 72495.14 4.95826814 26.67 19.44 0.01118466 55322.4 12.35 12.34 0.00892626 34941.2
PACU_VAV_BOT HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 18409.167 18409.167 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_BOT FAN Fan:VariableVolume 4.446372 5.16213338   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18409.17 18409.17 1.0000 1.54864001 1.333912 0.97 0.37 0.00378094 10437.6 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 18409.17 -6.30 0.00229779 -6.30 0.95610000 71.6764 19.37 0.00753422 19.63 0.00748755 50.8195 14377.80 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 92078.842 67383.226 4.081959 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.8588 1004.8586 1.1610 PACU_VAV_MID FAN Fan:VariableVolume 4.081959 4.73905845   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 92523.20 72214.24 1.0048 4.73905845 4.081959 26.43 18.25 0.01023096 52643.0 10.96 10.96 0.00850000 32442.6 -999.0 -999.00 -999.00 -999.00 8935.453 83587.74 34.30 0.01447309 23.52 0.95610000 23.4226 24.00 0.00892434 24.00 0.00892434 46.2902 53877.58 0.00 94945.65 67367.94 4.55190146 26.67 19.44 0.01118466 55322.4 12.17 12.15 0.00880926 34463.9
PACU_VAV_MID HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 19366.695 19366.695 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_MID FAN Fan:VariableVolume 4.081959 4.73905845   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19366.70 19366.70 1.0000 1.42171753 1.224588 -0.76 -1.11 0.00344167 7842.7 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 19366.70 -6.30 0.00229779 -6.30 0.95610000 78.0753 18.99 0.00751506 19.41 0.00728046 50.1197 17431.76 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 103530.701 77459.406 4.800213 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.4076 1004.8586 1.1610 PACU_VAV_TOP FAN Fan:VariableVolume 4.800213 5.57293523   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 103414.01 82845.18 0.9989 5.57293523 4.800213 26.02 17.92 0.00998823 51608.4 10.96 10.96 0.00850000 32441.8 -999.0 -999.00 -999.00 -999.00 10507.720 92906.29 34.12 0.01447274 23.47 0.95610000 19.9179 24.00 0.00886880 24.00 0.00886880 46.0061 63512.46 0.00 106754.05 77354.56 5.35284642 26.67 19.44 0.01118466 55322.4 12.52 12.51 0.00903125 35379.0
PACU_VAV_TOP HEATING COIL Coil:Heating:Electric AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes No unknown No 18591.590 18591.590 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PACU_VAV_TOP FAN Fan:VariableVolume 4.800213 5.57293523   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:30:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 18591.59 18591.59 1.0000 1.67188057 1.440064 1.73 1.22 0.00406899 11931.4 12.80 11.27 0.00800000 33059.8 -999.0 -999.00 -999.00 -999.00 0.000 18591.59 -6.30 0.00229779 -6.30 0.95610000 66.3929 17.60 0.00756808 17.66 0.00740220 56.8686 20171.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialEnthalpy 0.00 4.45 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialEnthalpy 0.00 4.08 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialEnthalpy 0.00 4.80 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area PERIMETER_MID_ZN_2_OA_MULT 1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 3048.67 1675.83 14.83
CORE_MID 2482.83 2822.33 249.83
CORE_TOP 2776.67 3171.50 680.33
PERIMETER_TOP_ZN_3 3412.83 3377.67 1314.33
PERIMETER_TOP_ZN_2 3486.17 3100.33 1177.83
PERIMETER_TOP_ZN_1 3269.00 2850.50 900.00
PERIMETER_TOP_ZN_4 3476.67 3152.50 1204.17
PERIMETER_BOT_ZN_3 3009.67 3426.50 937.33
PERIMETER_BOT_ZN_2 3166.00 2964.33 731.17
PERIMETER_BOT_ZN_1 3006.00 3115.50 777.67
PERIMETER_BOT_ZN_4 3155.83 2988.33 750.50
PERIMETER_MID_ZN_3 3208.50 3184.17 962.50
PERIMETER_MID_ZN_2 2802.00 2535.83 796.83
PERIMETER_MID_ZN_1 3164.83 2565.50 587.00
PERIMETER_MID_ZN_4 3334.50 2945.83 865.50
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4647.17 4072.83 1762.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.17 0.00 0.17 0.00
CORE_TOP 1.00 0.00 0.83 0.00
PERIMETER_TOP_ZN_3 19.00 6.00 9.83 4.17
PERIMETER_TOP_ZN_2 12.83 38.00 2.67 34.00
PERIMETER_TOP_ZN_1 8.83 29.17 2.83 26.50
PERIMETER_TOP_ZN_4 11.83 40.33 3.17 22.33
PERIMETER_BOT_ZN_3 1.33 0.00 1.00 0.00
PERIMETER_BOT_ZN_2 0.33 18.17 0.00 18.17
PERIMETER_BOT_ZN_1 124.50 65.83 124.50 65.83
PERIMETER_BOT_ZN_4 0.33 24.17 0.00 13.50
PERIMETER_MID_ZN_3 2.50 1.33 1.83 1.17
PERIMETER_MID_ZN_2 0.83 30.50 0.33 29.83
PERIMETER_MID_ZN_1 0.83 20.00 0.33 19.83
PERIMETER_MID_ZN_4 0.83 32.67 0.33 19.17
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 143.33 189.00 132.17 159.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.99 52.94 2698.04 0.686 0.000 0.000 0.000
CORE_MID 21.99 52.94 2698.04 0.527 0.000 0.000 0.000
CORE_TOP 21.99 52.94 2698.04 0.519 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.64 11.16 568.77 0.591 0.038 0.000 0.000
PERIMETER_TOP_ZN_2 2.94 7.07 360.08 0.745 0.040 0.000 0.000
PERIMETER_TOP_ZN_1 4.64 11.16 568.77 0.757 0.038 0.000 0.000
PERIMETER_TOP_ZN_4 2.93 7.06 360.05 0.746 0.040 0.000 0.000
PERIMETER_BOT_ZN_3 4.64 11.16 568.77 0.520 0.020 0.000 0.000
PERIMETER_BOT_ZN_2 2.94 7.07 360.08 0.659 0.021 0.000 0.000
PERIMETER_BOT_ZN_1 4.64 11.16 568.77 0.671 0.817 0.000 0.000
PERIMETER_BOT_ZN_4 2.93 7.06 360.05 0.641 0.021 0.000 0.000
PERIMETER_MID_ZN_3 4.64 11.16 568.77 0.588 0.031 0.000 0.000
PERIMETER_MID_ZN_2 2.58 7.07 360.08 0.684 0.035 0.000 0.000
PERIMETER_MID_ZN_1 4.64 11.16 568.77 0.771 0.032 0.000 0.000
PERIMETER_MID_ZN_4 2.93 7.06 360.05 0.743 0.033 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.99 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.94 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.94 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.58 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.64 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.93 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.99 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.99 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.99 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.94 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.93 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.94 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.93 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.58 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.64 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.93 7.06 360.05 131.25 0.0000 0.057
Total Facility   111.05 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 10799014.36 0.00 10799014.36 0.00 10799014.36 13393058.27 5182.36 132.47 3445.18 4.46
CORE_MID 8325935.45 0.00 8325935.45 0.00 8325935.45 13393058.27 5879.76 354.21 2526.03 14.60
CORE_TOP 8219137.37 0.00 8219137.37 0.00 8219137.37 13393058.27 5898.11 414.44 2447.45 70.33
PERIMETER_TOP_ZN_3 1974563.55 0.00 1974563.55 253748.86 2228312.41 2823374.22 4452.46 309.29 3998.25 70.33
PERIMETER_TOP_ZN_2 1571568.34 0.00 1571568.34 169164.89 1740733.22 1787429.43 4343.06 300.19 4116.75 70.33
PERIMETER_TOP_ZN_1 2522504.02 0.00 2522504.02 253748.86 2776252.88 2823374.22 4445.12 426.05 3888.83 70.33
PERIMETER_TOP_ZN_4 1573460.25 0.00 1573460.25 169164.89 1742625.14 1787312.18 4401.98 255.97 4102.05 70.33
PERIMETER_BOT_ZN_3 1733406.74 0.00 1733406.74 134917.23 1868323.97 2823374.22 5868.00 228.11 2663.90 4.46
PERIMETER_BOT_ZN_2 1386621.48 0.00 1386621.48 89944.28 1476565.76 1787429.43 4770.64 206.82 3782.55 4.46
PERIMETER_BOT_ZN_1 2233833.77 0.00 2233833.77 2786735.31 5020569.08 2823374.22 4998.04 157.91 3604.05 4.46
PERIMETER_BOT_ZN_4 1349085.64 0.00 1349085.64 89944.28 1439029.92 1787312.18 4949.31 210.93 3599.76 4.46
PERIMETER_MID_ZN_3 1958137.38 0.00 1958137.38 211226.68 2169364.06 2823374.22 4479.51 259.54 4020.94 14.60
PERIMETER_MID_ZN_2 1444842.23 0.00 1444842.23 140816.94 1585659.17 1601953.02 4311.03 185.86 4263.11 923.60
PERIMETER_MID_ZN_1 2563813.42 0.00 2563813.42 211226.68 2775040.10 2823374.22 4390.47 235.22 4134.31 14.60
PERIMETER_MID_ZN_4 1564918.77 0.00 1564918.77 140816.94 1705735.71 1787312.18 4403.43 160.64 4195.92 14.60
Total Facility 49220842.77 0.00 49220842.77 4651455.83 53872298.60 67658168.57 6467.83 1001.36 4504.40 981.37


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.5045 0.0000 0.5045 0.0000 0.5045 0.4247 2367.36 132.47 3443.18
CORE_MID 0.3883 0.0000 0.3883 0.0000 0.3883 0.4247 3068.79 354.21 2520.00
CORE_TOP 0.3826 0.0000 0.3826 0.0000 0.3826 0.4247 3088.11 414.44 2440.45
PERIMETER_TOP_ZN_3 0.0919 0.0000 0.0919 0.0059 0.0978 0.0895 1642.46 309.29 3991.25
PERIMETER_TOP_ZN_2 0.0732 0.0000 0.0732 0.0039 0.0771 0.0567 1533.25 300.19 4109.56
PERIMETER_TOP_ZN_1 0.1175 0.0000 0.1175 0.0059 0.1234 0.0895 1635.15 426.05 3881.80
PERIMETER_TOP_ZN_4 0.0733 0.0000 0.0733 0.0039 0.0772 0.0567 1592.21 255.97 4094.83
PERIMETER_BOT_ZN_3 0.0810 0.0000 0.0810 0.0031 0.0841 0.0895 3053.00 228.11 2661.90
PERIMETER_BOT_ZN_2 0.0648 0.0000 0.0648 0.0021 0.0669 0.0567 1955.78 206.78 3780.44
PERIMETER_BOT_ZN_1 0.1043 0.0000 0.1043 0.1271 0.2314 0.0895 2183.06 157.91 3602.03
PERIMETER_BOT_ZN_4 0.0630 0.0000 0.0630 0.0021 0.0651 0.0567 2134.42 210.93 3597.65
PERIMETER_MID_ZN_3 0.0913 0.0000 0.0913 0.0049 0.0962 0.0895 1668.61 259.54 4014.85
PERIMETER_MID_ZN_2 0.0672 0.0000 0.0672 0.0035 0.0707 0.0567 1500.35 185.86 3347.79
PERIMETER_MID_ZN_1 0.1196 0.0000 0.1196 0.0049 0.1245 0.0895 1579.52 235.22 4128.26
PERIMETER_MID_ZN_4 0.0730 0.0000 0.0730 0.0033 0.0763 0.0567 1592.75 160.64 4189.60
Total Facility 2.2955 0.0000 2.2955 0.1705 2.4660 2.1513 3652.16 1001.32 4495.53


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 23590282.67 0.00 23590282.67 22614548.33 4233.28 2.09 4524.64 4.46
PACU_VAV_MID 21373990.18 0.00 21373990.18 22429071.92 4220.11 1.98 4537.91 14.60
PACU_VAV_TOP 21378720.08 0.00 21378720.08 22614548.33 4255.68 2.31 4502.00 70.33


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.1019 0.0000 1.1019 0.7171 1418.30 2.09 4522.61
PACU_VAV_MID 0.9969 0.0000 0.9969 0.7084 1409.16 1.98 4531.87
PACU_VAV_TOP 0.9954 0.0000 0.9954 0.7171 1445.68 2.31 4495.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 205.98 2143.16 0.00 0.00 0.00 2221.23 0.00 0.00 0.00
PACU_VAV_MID 0.00 105.99 2070.55 0.00 0.00 0.00 2419.48 0.00 0.00 0.00
PACU_VAV_TOP 0.00 70.44 2097.32 0.00 0.00 0.00 2489.89 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 1.2396 1.8447 0.0000 0.0000 0.0000 1.0584 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 1.1938 1.5942 0.0000 0.0000 0.0000 1.0425 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 1.1894 1.5895 0.0000 0.0000 0.0000 1.0489 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 943
Defaulted Fields 546
Fields with Defaults 2220
Autosized Fields 150
Autosizable Fields 202
Autocalculated Fields 155
Autocalculatable Fields 276



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
Electricity:Building 952.24 13383.13 23-APR-17:20 66677.71 30-OCT-07:10
Electricity:Zone:CORE_BOTTOM 306.02 5243.28 01-JAN-00:10 18955.76 02-JAN-08:10
Electricity:SpaceType:GENERAL 952.24 13383.13 23-APR-17:20 66677.71 30-OCT-07:10
InteriorLights:Electricity 232.55 905.38 23-APR-17:20 24978.45 30-OCT-07:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 232.55 905.38 23-APR-17:20 24978.45 30-OCT-07:10
LightsWired:InteriorLights:Electricity 232.55 905.38 23-APR-17:20 24978.45 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 232.55 905.38 23-APR-17:20 24978.45 30-OCT-07:10
Electricity:Zone:CORE_MID 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:CORE_TOP 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 31.12 413.68 12-MAR-17:10 2473.26 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.78 27.57 01-JAN-11:00 1038.01 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.78 27.57 01-JAN-11:00 1038.01 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 19.64 261.88 23-APR-17:10 1565.70 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.24 17.46 01-JAN-09:10 657.13 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.24 17.46 01-JAN-09:10 657.13 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_1 30.98 413.67 12-MAR-17:10 2473.25 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.65 27.57 01-JAN-09:10 1038.01 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.65 27.57 01-JAN-09:10 1038.01 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 19.67 261.87 26-FEB-18:10 1565.65 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.27 17.46 01-JAN-10:50 657.08 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.27 17.46 01-JAN-10:50 657.08 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_3 31.09 413.68 12-MAR-17:10 2473.16 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.76 27.57 01-JAN-10:50 1037.91 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.76 27.57 01-JAN-10:50 1037.91 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 19.63 261.88 23-APR-17:10 1565.65 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.23 17.46 01-JAN-09:00 657.08 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.23 17.46 01-JAN-09:00 657.08 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_1 30.97 413.67 12-MAR-17:10 2473.15 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.64 27.57 01-JAN-09:10 1037.91 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.64 27.57 01-JAN-09:10 1037.91 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 19.66 261.87 20-FEB-18:10 1565.60 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.25 17.46 01-JAN-10:40 657.03 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.25 17.46 01-JAN-10:40 657.03 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 31.12 413.68 12-MAR-17:10 2473.26 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.78 27.57 01-JAN-11:00 1038.01 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.78 27.57 01-JAN-11:00 1038.01 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 19.64 261.88 23-APR-17:10 1565.70 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.24 17.46 01-JAN-09:10 657.13 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.24 17.46 01-JAN-09:10 657.13 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_1 30.98 413.67 12-MAR-17:10 2473.25 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.65 27.57 01-JAN-09:10 1038.01 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.65 27.57 01-JAN-09:10 1038.01 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 19.67 261.87 26-FEB-18:10 1565.65 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.27 17.46 01-JAN-10:50 657.08 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.27 17.46 01-JAN-10:50 657.08 30-OCT-07:10
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 501.04 367.92 01-JAN-00:10 198758.81 13-FEB-07:10
ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 02-JAN-08:20
ElectricityPurchased:Facility 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
ElectricityPurchased:Plant 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
Cogeneration:ElectricityPurchased 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
General:Cogeneration:ElectricityPurchased 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
ElectricityNet:Plant 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
Cogeneration:ElectricityNet 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
General:Cogeneration:ElectricityNet 1552.93 13760.90 07-MAY-17:30 237229.50 13-FEB-07:10
Heating:Electricity 114.48 0.00 01-JAN-00:10 192831.40 13-FEB-07:10
General:Heating:Electricity 114.48 0.00 01-JAN-00:10 192831.40 13-FEB-07:10
Fans:Electricity 67.51 0.00 01-JAN-00:10 14740.47 02-AUG-15:50
General:Fans:Electricity 67.51 0.00 01-JAN-00:10 14740.47 02-AUG-15:50
ExteriorLights:Electricity 51.35 0.00 01-JAN-07:50 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 51.35 0.00 01-JAN-07:50 5686.19 01-JAN-06:10
Cooling:Electricity 292.17 0.00 01-JAN-00:10 69402.51 07-JUL-16:00
General:Cooling:Electricity 292.17 0.00 01-JAN-00:10 69402.51 07-JUL-16:00
Electricity:Plant 48.29 0.00 01-JAN-00:10 6221.07 31-JAN-12:40
WaterSystems:Electricity 48.14 0.00 01-JAN-00:10 6214.22 31-JAN-12:40
Water Heater:WaterSystems:Electricity 48.14 0.00 01-JAN-00:10 6214.22 31-JAN-12:40
Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 03-JAN-18:10
General:Pumps:Electricity 0.15 0.00 01-JAN-00:10 6.85 03-JAN-18:10
WIRED_LTG_ELECTRICITY 6.53 0.00 01-JAN-00:10 701.89 30-OCT-07:20
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 05-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2575.35 0.00 01-JAN-00:10 405428.55 07-JUL-16:00
EnergyTransfer:Building 1164.78 0.00 01-JAN-00:10 155506.78 02-AUG-15:50
EnergyTransfer:Zone:CORE_BOTTOM 240.16 0.00 01-JAN-00:10 24722.12 05-SEP-07:40
Heating:EnergyTransfer 58.23 0.00 01-JAN-00:10 137878.49 09-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 1349.87 02-JAN-07:10
General:Heating:EnergyTransfer 58.23 0.00 01-JAN-00:10 137878.49 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 1349.87 02-JAN-07:10
Cooling:EnergyTransfer 1106.55 0.00 01-JAN-00:10 155506.78 02-AUG-15:50
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 240.16 0.00 01-JAN-00:10 24722.12 05-SEP-07:40
General:Cooling:EnergyTransfer 1106.55 0.00 01-JAN-00:10 155506.78 02-AUG-15:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 240.16 0.00 01-JAN-00:10 24722.12 05-SEP-07:40
EnergyTransfer:Zone:TOPFLOOR_PLENUM 44.57 0.00 01-JAN-00:10 12080.78 13-FEB-06:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 10.44 0.00 01-JAN-00:10 12080.78 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 10.44 0.00 01-JAN-00:10 12080.78 13-FEB-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 34.13 0.00 01-JAN-00:10 10219.41 01-AUG-14:00
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 34.13 0.00 01-JAN-00:10 10219.41 01-AUG-14:00
EnergyTransfer:Zone:MIDFLOOR_PLENUM 22.75 0.00 01-JAN-00:10 6713.76 09-JAN-07:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 4.15 0.00 01-JAN-00:10 6713.76 09-JAN-07:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 4.15 0.00 01-JAN-00:10 6713.76 09-JAN-07:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 18.60 0.00 01-JAN-00:10 4370.63 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 18.60 0.00 01-JAN-00:10 4370.63 10-JUL-15:30
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 25.24 0.00 01-JAN-00:10 4669.52 10-JUL-15:30
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 2.72 0.00 01-JAN-00:10 3255.68 09-JAN-09:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 2.72 0.00 01-JAN-00:10 3255.68 09-JAN-09:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 22.52 0.00 01-JAN-00:10 4669.52 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 22.52 0.00 01-JAN-00:10 4669.52 10-JUL-15:30
EnergyTransfer:Zone:CORE_MID 169.37 0.00 01-JAN-00:10 18625.36 21-AUG-07:30
Heating:EnergyTransfer:Zone:CORE_MID 0.35 0.00 01-JAN-00:10 13161.30 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.35 0.00 01-JAN-00:10 13161.30 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 169.02 0.00 01-JAN-00:10 18625.36 21-AUG-07:30
General:Cooling:EnergyTransfer:Zone:CORE_MID 169.02 0.00 01-JAN-00:10 18625.36 21-AUG-07:30
EnergyTransfer:Zone:CORE_TOP 165.59 0.00 01-JAN-00:10 26495.83 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_TOP 3.17 0.00 01-JAN-00:10 26495.83 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 3.17 0.00 01-JAN-00:10 26495.83 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 162.42 0.00 01-JAN-00:10 20048.31 10-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 162.42 0.00 01-JAN-00:10 20048.31 10-JUL-14:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.13 0.00 01-JAN-00:10 8838.69 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.62 0.00 01-JAN-00:10 8838.69 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.62 0.00 01-JAN-00:10 8838.69 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 38.51 0.00 01-JAN-00:10 7123.85 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 38.51 0.00 01-JAN-00:10 7123.85 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 37.22 0.00 01-JAN-00:10 8081.49 07-JUL-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.32 0.00 01-JAN-00:10 7486.28 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.32 0.00 01-JAN-00:10 7486.28 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 33.90 0.00 01-JAN-00:10 8081.49 07-JUL-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 33.90 0.00 01-JAN-00:10 8081.49 07-JUL-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 56.01 0.00 01-JAN-00:10 10786.23 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 3.99 0.00 01-JAN-00:10 9808.36 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 3.99 0.00 01-JAN-00:10 9808.36 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 52.01 0.00 01-JAN-00:10 10786.23 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 52.01 0.00 01-JAN-00:10 10786.23 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 37.01 0.00 01-JAN-00:10 8139.67 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.84 0.00 01-JAN-00:10 7294.84 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.84 0.00 01-JAN-00:10 7294.84 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 33.18 0.00 01-JAN-00:10 8139.67 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 33.18 0.00 01-JAN-00:10 8139.67 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 37.88 0.00 01-JAN-00:10 6686.65 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.53 0.00 01-JAN-00:10 6686.65 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.53 0.00 01-JAN-00:10 6686.65 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 35.35 0.00 01-JAN-00:10 5882.27 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 35.35 0.00 01-JAN-00:10 5882.27 10-JUL-15:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 32.92 0.00 01-JAN-00:10 6741.86 07-AUG-09:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.13 0.00 01-JAN-00:10 4694.89 13-FEB-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.13 0.00 01-JAN-00:10 4694.89 13-FEB-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 31.78 0.00 01-JAN-00:10 6741.86 07-AUG-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 31.78 0.00 01-JAN-00:10 6741.86 07-AUG-09:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 54.98 0.00 01-JAN-00:10 10052.71 18-AUG-12:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 7.80 0.00 01-JAN-00:10 10013.74 03-FEB-07:50
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 7.80 0.00 01-JAN-00:10 10013.74 03-FEB-07:50
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 47.18 0.00 01-JAN-00:10 10052.71 18-AUG-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 47.18 0.00 01-JAN-00:10 10052.71 18-AUG-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 31.72 0.00 01-JAN-00:10 6650.37 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.22 0.00 01-JAN-00:10 4721.80 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.22 0.00 01-JAN-00:10 4721.80 09-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 30.50 0.00 01-JAN-00:10 6650.37 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 30.50 0.00 01-JAN-00:10 6650.37 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 41.69 0.00 01-JAN-00:10 7284.94 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.68 0.00 01-JAN-00:10 7284.94 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.68 0.00 01-JAN-00:10 7284.94 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 39.00 0.00 01-JAN-00:10 6370.08 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 39.00 0.00 01-JAN-00:10 6370.08 10-JUL-15:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 33.48 0.00 01-JAN-00:10 7886.98 07-JUL-10:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.33 0.00 01-JAN-00:10 5275.25 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.33 0.00 01-JAN-00:10 5275.25 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 32.15 0.00 01-JAN-00:10 7886.98 07-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 32.15 0.00 01-JAN-00:10 7886.98 07-JUL-10:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 54.41 0.00 01-JAN-00:10 9777.52 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.43 0.00 01-JAN-00:10 7820.13 09-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.43 0.00 01-JAN-00:10 7820.13 09-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 52.98 0.00 01-JAN-00:10 9777.52 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 52.98 0.00 01-JAN-00:10 9777.52 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 34.66 0.00 01-JAN-00:10 7523.88 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.50 0.00 01-JAN-00:10 5308.37 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.50 0.00 01-JAN-00:10 5308.37 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 33.16 0.00 01-JAN-00:10 7523.88 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 33.16 0.00 01-JAN-00:10 7523.88 02-AUG-16:00
PlantLoopHeatingDemand:Facility 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
PlantLoopHeatingDemand:Plant 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
EnergyTransfer:HVAC 1365.20 0.00 01-JAN-00:10 249431.30 07-JUL-16:00
HeatingCoils:EnergyTransfer 114.48 0.00 01-JAN-00:10 192831.40 13-FEB-07:10
CoolingCoils:EnergyTransfer 1250.72 0.00 01-JAN-00:10 249431.30 07-JUL-16:00
EnergyTransfer:Plant 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterSystems:EnergyTransfer 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 45.37 0.00 01-JAN-00:10 5951.33 01-FEB-12:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.002 -240.157 0.000 0.000 32.904 55.599 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -98.770
CORE_MID 0.000 0.000 0.352 -169.024 0.000 0.000 34.018 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -36.370
CORE_TOP 0.000 0.000 3.165 -162.421 0.000 0.000 34.646 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -46.414
PERIMETER_TOP_ZN_3 0.000 0.000 6.621 -38.510 0.000 0.000 7.430 6.784 24.333 18.015 0.000 0.129 2.290 0.000 -24.714 0.000 -2.378 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 3.320 -33.902 0.000 0.000 4.625 4.239 15.404 29.091 0.000 0.080 0.001 0.000 -15.313 0.000 -1.630 -5.914
PERIMETER_TOP_ZN_1 0.000 0.000 3.991 -52.013 0.000 0.000 7.235 6.648 24.332 51.275 0.000 0.121 0.001 0.000 -23.240 0.000 -2.538 -15.812
PERIMETER_TOP_ZN_4 0.000 0.000 3.837 -33.175 0.000 0.000 4.665 4.265 15.403 29.354 0.000 0.080 0.000 0.000 -16.364 0.000 -1.642 -6.423
PERIMETER_BOT_ZN_3 0.000 0.000 2.532 -35.345 0.000 0.000 7.387 6.762 24.333 18.356 0.000 0.075 3.138 0.000 -25.890 0.000 -1.349 -0.000
PERIMETER_BOT_ZN_2 0.000 0.000 1.132 -31.784 0.000 0.000 4.578 4.230 15.404 29.238 0.000 0.045 0.001 0.000 -16.327 0.000 -0.938 -5.577
PERIMETER_BOT_ZN_1 0.000 0.000 7.798 -47.183 0.000 0.000 7.303 6.636 24.332 51.791 0.000 3.908 0.004 0.000 -24.738 0.000 -20.509 -9.338
PERIMETER_BOT_ZN_4 0.000 0.000 1.218 -30.498 0.000 0.000 4.614 4.254 15.403 29.597 0.000 0.044 0.001 0.000 -17.472 0.000 -0.945 -6.215
PERIMETER_MID_ZN_3 0.000 0.000 2.681 -39.003 0.000 0.000 7.348 6.784 24.333 17.894 0.000 0.111 8.253 0.000 -26.285 0.000 -2.117 -0.002
PERIMETER_MID_ZN_2 0.000 0.000 1.335 -32.149 0.000 0.000 3.375 4.239 15.404 28.839 0.000 0.067 0.001 0.000 -16.259 0.000 -1.453 -3.397
PERIMETER_MID_ZN_1 0.000 0.000 1.433 -52.979 0.000 0.000 7.155 6.648 24.332 51.061 0.000 0.104 0.000 0.000 -24.633 0.000 -2.252 -10.869
PERIMETER_MID_ZN_4 0.000 0.000 1.503 -33.158 0.000 0.000 4.613 4.265 15.403 29.281 0.000 0.067 0.002 0.000 -17.377 0.000 -1.458 -3.140
TOPFLOOR_PLENUM 10.443 -34.125 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.122 27.186 0.000 0.000 0.000 -3.627 -0.000
MIDFLOOR_PLENUM 4.148 -18.598 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.157 17.979 0.000 0.000 0.000 -3.686 -0.000
FIRSTFLOOR_PLENUM 2.723 -22.518 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.119 22.717 0.000 0.000 0.000 -3.041 -0.000
Total Facility 17.314 -75.241 40.920 -1031.300 0.000 0.000 171.895 232.552 719.689 383.791 0.000 5.231 81.574 0.000 -248.612 0.000 -49.564 -248.242


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 09-AUG-04:03 0.00 0.00 0.00 -38198.99 0.00 0.00 0.00 211.73 5642.06 0.00 0.00 0.00 32345.20 0.00 -0.00 0.00 0.00 0.00
CORE_MID 07-JUL-04:03 0.00 0.00 0.00 -29326.55 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 26672.76 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUL-05:12 0.00 0.00 0.00 -31467.02 0.00 0.00 335.77 548.43 3025.92 0.00 0.00 0.00 27556.89 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 16-JUL-13:02 0.00 0.00 0.00 -11228.94 0.00 0.00 27.17 27.57 478.42 3550.10 0.00 99.03 7046.65 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 27-AUG-09:22 0.00 0.00 0.00 -11870.59 0.00 0.00 14.97 17.46 302.86 7778.42 0.00 0.00 3760.29 0.00 -0.00 0.00 -3.40 0.00
PERIMETER_TOP_ZN_1 24-SEP-13:43 0.00 0.00 0.00 -13806.25 0.00 0.00 25.25 27.57 478.41 7504.18 0.00 14.85 5755.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 30-JUL-17:22 0.00 0.00 0.00 -12867.95 0.00 0.00 0.00 17.46 244.42 7246.48 0.00 25.72 5333.88 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 17-JUL-06:03 0.00 0.00 0.00 -6796.96 0.00 0.00 147.83 182.63 637.89 514.32 0.00 0.00 5316.19 0.00 -0.00 0.00 -1.90 0.00
PERIMETER_BOT_ZN_2 06-AUG-09:52 0.00 0.00 0.00 -9842.72 0.00 0.00 16.35 17.46 302.86 6600.74 0.00 7.55 2897.77 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 09-OCT-14:53 0.00 0.00 0.00 -11361.03 0.00 0.00 25.40 27.57 478.41 7744.97 0.00 1.40 3083.27 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 04-JUL-17:52 0.00 0.00 0.00 -10451.33 0.00 0.00 0.00 17.46 244.42 5848.57 0.00 16.33 4324.55 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 16-JUL-13:02 0.00 0.00 0.00 -9491.15 0.00 0.00 28.41 27.57 478.42 3616.55 0.00 86.38 5253.82 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 09-JUL-10:12 0.00 0.00 0.00 -11640.54 0.00 0.00 14.75 17.46 302.86 6333.81 0.00 5.68 4965.99 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 11-NOV-13:43 0.00 0.00 0.00 -12248.13 0.00 0.00 25.46 27.57 478.41 12155.96 0.00 0.00 0.00 0.00 -0.00 0.00 -112.69 -326.59
PERIMETER_MID_ZN_4 02-JUL-17:42 0.00 0.00 0.00 -11908.84 0.00 0.00 0.00 17.46 244.42 5983.03 0.00 18.12 5645.81 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 01-AUG-14:05 0.00 -10219.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.46 10179.81 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 10-JUL-15:30 0.00 -4370.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.58 4313.04 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 10-JUL-15:30 0.00 -4669.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.07 4624.43 0.00 -0.00 0.00 0.00 0.00
Total Facility 14-AUG-04:02 0.00 8826.46 0.00 -181336.44 0.00 0.00 0.00 1072.56 15570.33 0.00 0.00 0.00 161272.79 0.00 -5156.74 0.00 -248.96 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 09-JAN-07:01 0.00 0.00 12850.46 0.00 0.00 0.00 886.20 1645.36 10194.85 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25576.87
CORE_MID 09-JAN-06:10 0.00 0.00 14971.79 0.00 0.00 0.00 494.28 211.73 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18703.72
CORE_TOP 09-JAN-05:01 0.00 0.00 30736.76 0.00 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -33390.54
PERIMETER_TOP_ZN_3 12-FEB-07:12 0.00 0.00 10224.84 0.00 0.00 0.00 59.23 57.81 478.42 0.00 0.00 0.00 0.00 0.00 -3772.37 0.00 -846.03 -6201.90
PERIMETER_TOP_ZN_2 12-FEB-06:33 0.00 0.00 9532.28 0.00 0.00 0.00 37.53 36.60 302.86 0.00 0.00 0.00 0.00 0.00 -2450.24 0.00 -644.03 -6814.98
PERIMETER_TOP_ZN_1 12-FEB-07:12 0.00 0.00 11763.04 0.00 0.00 0.00 59.06 57.81 478.41 0.00 0.00 0.00 0.00 0.00 -3667.34 0.00 -854.98 -7835.99
PERIMETER_TOP_ZN_4 12-FEB-06:33 0.00 0.00 9517.89 0.00 0.00 0.00 37.51 36.59 302.86 0.00 0.00 0.00 0.00 0.00 -2538.98 0.00 -644.28 -6711.59
PERIMETER_BOT_ZN_3 13-FEB-05:01 0.00 0.00 7670.41 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3076.14 0.00 -368.40 -4785.31
PERIMETER_BOT_ZN_2 13-FEB-05:01 0.00 0.00 6666.72 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2087.07 0.00 -251.20 -4682.60
PERIMETER_BOT_ZN_1 03-FEB-07:10 0.00 0.00 10282.47 0.00 0.00 0.00 193.30 346.86 637.88 0.00 0.00 0.00 11975.25 0.00 -3883.15 0.00 -19552.60 0.00
PERIMETER_BOT_ZN_4 09-JAN-05:01 0.00 0.00 6661.31 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1731.33 0.00 -166.33 -5117.80
PERIMETER_MID_ZN_3 13-FEB-05:01 0.00 0.00 8508.29 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3002.41 0.00 -558.04 -5507.28
PERIMETER_MID_ZN_2 13-FEB-05:01 0.00 0.00 7133.74 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2011.76 0.00 -375.48 -5100.66
PERIMETER_MID_ZN_1 09-JAN-05:01 0.00 0.00 9878.00 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -2453.20 0.00 -377.16 -7607.07
PERIMETER_MID_ZN_4 13-FEB-05:01 0.00 0.00 7075.12 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1984.21 0.00 -379.59 -5065.47
TOPFLOOR_PLENUM 13-FEB-06:13 13132.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -268.40 -12863.80
MIDFLOOR_PLENUM 09-JAN-07:11 7093.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -166.55 -6926.88
FIRSTFLOOR_PLENUM 09-JAN-08:50 3271.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -91.35 -3180.10
Total Facility 09-JAN-07:01 19723.51 0.00 134213.15 0.00 0.00 0.00 4615.43 8334.71 22496.85 0.00 0.00 0.00 0.00 0.00 -29164.95 0.00 -21114.85 -139103.84



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 4.9222 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.4464 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 4.6560 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.0820 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.0937 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.8002 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.4611 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0760 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.3280 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0751 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.5469 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0761 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5511 2.5511 0.6378 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0387 2.0387 0.6361 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1892 2.1892 0.6370 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6900 0.6900 0.1345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6702 0.6702 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8030 0.8030 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7414 0.7414 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5522 0.5522 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5730 0.5730 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6515 0.6515 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5943 0.5943 0.0850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5949 0.5949 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6442 0.6442 0.0850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7071 0.7071 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6711 0.6711 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 4.9222 4.4464 4.9222 1.0760 0.0000 1.0000
PACU_VAV_MID 4.6560 4.0820 4.6560 1.0751 0.0000 1.0000
PACU_VAV_TOP 5.0937 4.8002 5.0937 1.0761 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2756 1.2756 0.6378 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0194 1.0194 0.6361 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0946 1.0946 0.6370 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3450 0.3450 0.1345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3351 0.3351 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4015 0.4015 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3707 0.3707 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2761 0.2761 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2865 0.2865 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3258 0.3258 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2971 0.2971 0.0850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2974 0.2974 0.1344 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3221 0.3221 0.0850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3536 0.3536 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3356 0.3356 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.4611 1.0760 1.0760 1.0760 0.0000 1.0000
PACU_VAV_MID 2.3280 1.0751 1.0751 1.0751 0.0000 1.0000
PACU_VAV_TOP 2.5469 1.0761 1.0761 1.0761 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 4982.19
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 132.17
Number of hours cooling loads not met 159.67
Number of hours not met 291.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 114.48 192831.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 292.17 69402.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 232.55 24978.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 51.35 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.89 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 67.51 14740.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.15 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 48.14 6214.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1552.93
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 719.69 1552.93


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 46.68
Space Heating 22.98
Space Cooling 58.64
Fans (All) 13.55
Service Water Heating 9.66
Receptacle Equipment 144.45
Miscellaneous (All) 311.70
Subtotal 311.70


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 14.98
Space Heating 7.37
Space Cooling 18.81
Fans (All) 4.35
Service Water Heating 3.10
Receptacle Equipment 46.34
Miscellaneous 5.05


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 1042. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8438.17 321.83 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8741.33 18.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8691.00 69.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8714.83 45.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8670.00 90.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8757.50 2.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8708.00 52.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8739.67 20.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8707.67 52.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8751.33 8.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8691.83 68.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8718.83 41.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8675.50 84.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8565.17 194.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8438.17 0.00 0.00 0.00 0.00
Max 8760.00 321.83 0.00 0.00 0.00
Average 8700.60 59.40 0.00 0.00 0.00
Sum 156610.83 1069.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128201.67 102.33 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 102.33 0.00 0.00 0.00
Average 34137.65 5.69 0.00 0.00 0.00
Sum 614477.67 102.33 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8215.50 544.50 0.00 0.00 0.00
CORE_MID 8756.33 3.67 0.00 0.00 0.00
CORE_TOP 8759.17 0.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8196.17 563.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8113.83 646.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8176.50 583.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8090.17 669.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8401.50 358.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8233.33 526.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8131.67 628.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8179.67 580.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8183.17 576.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8086.67 673.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8157.50 602.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8055.17 704.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8483.00 277.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8587.33 172.67 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8636.17 123.83 0.00 0.00 0.00
Min 8055.17 0.83 0.00 0.00 0.00
Max 8759.17 704.83 0.00 0.00 0.00
Average 8302.38 457.62 0.00 0.00 0.00
Sum 149442.83 8237.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128070.00 234.00 0.00 0.00 0.00
CORE_MID 128302.67 1.33 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24898.83 10.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24898.67 10.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24906.33 2.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 23823.17 1085.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24899.50 9.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24899.33 9.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 1085.83 0.00 0.00 0.00
Average 34067.58 75.75 0.00 0.00 0.00
Sum 613216.50 1363.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:06

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107786E+11 12542.98 31-JAN-17:00 19.40 13.37 0.185219E+10 2606.62 31-JAN-10:30 19.40 13.37
February 0.116082E+11 17952.27 28-FEB-17:00 23.90 12.94 0.174582E+10 2606.66 22-FEB-14:20 23.90 12.94
March 0.183749E+11 28151.29 31-MAR-06:03 17.30 16.12 0.215548E+10 2606.71 08-MAR-10:09 17.30 16.12
April 0.192604E+11 33395.93 17-APR-06:03 13.58 10.46 0.191818E+10 2606.65 07-APR-13:20 13.58 10.46
May 0.236417E+11 37721.18 30-MAY-05:12 19.07 17.52 0.207945E+10 2606.74 11-MAY-09:00 19.07 17.52
June 0.261476E+11 37805.49 19-JUN-05:12 20.93 20.12 0.207263E+10 2606.68 09-JUN-09:00 20.93 20.12
July 0.263923E+11 38064.75 15-JUL-04:03 23.90 20.50 0.192728E+10 2606.59 03-JUL-09:20 23.90 20.50
August 0.286105E+11 38200.51 09-AUG-04:03 24.40 22.40 0.216225E+10 2606.59 21-AUG-09:20 23.50 22.59
September 0.245105E+11 37756.04 18-SEP-05:12 14.40 13.71 0.192094E+10 2606.63 20-SEP-09:20 20.93 15.94
October 0.210686E+11 36589.07 10-OCT-05:12 15.73 14.81 0.199410E+10 2606.63 04-OCT-13:20 15.73 14.81
November 0.168872E+11 31901.86 06-NOV-07:03 9.08 8.50 0.196947E+10 2606.76 16-NOV-10:09 10.68 10.03
December 0.128757E+11 16567.75 14-DEC-17:00 13.90 10.25 0.189270E+10 2606.69 11-DEC-10:20 13.90 10.25
                     
Annual Sum or Average 0.240156E+12         0.236905E+11        
Minimum of Months 0.107786E+11 12542.98   9.08 8.50 0.174582E+10 2606.59   10.68 10.03
Maximum of Months 0.286105E+11 38200.51   24.40 22.40 0.216225E+10 2606.76   23.90 22.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 82185147.30 1033.53 31-JAN-17:30 19.15 13.30 0.00 0.00 01-JAN-00:10 19.15 13.30
February 0.412590E+09 3290.86 28-FEB-16:00 23.30 12.53 0.00 0.00 01-FEB-00:10 23.30 12.53
March 0.139276E+10 6806.97 30-MAR-14:50 27.80 17.21 0.00 0.00 01-MAR-00:10 27.80 17.21
April 0.259834E+10 7768.15 17-APR-15:00 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.426217E+10 8547.19 30-MAY-15:00 30.60 21.44 0.00 0.00 01-MAY-00:10 30.60 21.44
June 0.604215E+10 9146.73 12-JUN-15:00 33.30 22.72 0.00 0.00 01-JUN-00:10 33.30 22.72
July 0.641682E+10 10057.66 07-JUL-15:20 35.20 23.90 0.00 0.00 01-JUL-00:10 35.20 23.90
August 0.669599E+10 10219.41 01-AUG-14:00 33.90 23.66 0.00 0.00 01-AUG-00:10 33.90 23.66
September 0.366605E+10 8776.24 06-SEP-14:20 30.53 23.42 0.00 0.00 01-SEP-00:10 30.53 23.42
October 0.176451E+10 6897.17 10-OCT-14:40 29.07 20.78 0.00 0.00 01-OCT-00:10 29.07 20.78
November 0.609072E+09 2855.23 06-NOV-15:00 20.60 10.48 0.00 0.00 01-NOV-00:10 20.60 10.48
December 0.182713E+09 1712.64 10-DEC-14:23 17.50 8.24 0.00 0.00 01-DEC-00:10 17.50 8.24
                     
Annual Sum or Average 0.341254E+11         0.00        
Minimum of Months 82185147.30 1033.53   17.50 8.24 0.00 0.00   17.50 8.24
Maximum of Months 0.669599E+10 10219.41   35.20 23.90 0.00 0.00   35.20 23.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 39314476.16 1949.63 14-JAN-06:01 -6.7 -7.8 0.00 0.00 01-JAN-00:10 -6.7 -7.8
February 0.150699E+09 1985.06 24-FEB-07:03 3.07 0.07 0.00 0.00 01-FEB-00:10 3.07 0.07
March 0.622550E+09 2352.71 30-MAR-16:00 27.80 17.47 0.00 0.00 01-MAR-00:10 27.80 17.47
April 0.117882E+10 2986.21 06-APR-06:02 1.20 -0.4 0.00 0.00 01-APR-00:10 1.20 -0.4
May 0.213203E+10 3755.48 30-MAY-15:20 29.67 21.52 0.00 0.00 01-MAY-00:10 29.67 21.52
June 0.325329E+10 4041.07 26-JUN-06:03 23.30 21.67 0.00 0.00 01-JUN-00:10 23.30 21.67
July 0.361414E+10 4370.63 10-JUL-15:30 32.50 22.22 0.00 0.00 01-JUL-00:10 32.50 22.22
August 0.390673E+10 4265.27 07-AUG-12:10 30.87 23.75 0.00 0.00 01-AUG-00:10 30.87 23.75
September 0.233750E+10 3840.87 11-SEP-16:00 30.00 22.85 0.00 0.00 01-SEP-00:10 30.00 22.85
October 0.978807E+09 2790.32 11-OCT-16:00 26.10 17.12 0.00 0.00 01-OCT-00:10 26.10 17.12
November 0.279379E+09 1759.20 18-NOV-07:03 3.98 1.87 0.00 0.00 01-NOV-00:10 3.98 1.87
December 0.105064E+09 1944.54 15-DEC-07:03 3.22 0.92 0.00 0.00 01-DEC-00:10 3.22 0.92
                     
Annual Sum or Average 0.185983E+11         0.00        
Minimum of Months 39314476.16 1759.20   -6.7 -7.8 0.00 0.00   -6.7 -7.8
Maximum of Months 0.390673E+10 4370.63   32.50 23.75 0.00 0.00   32.50 23.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 44546774.39 1791.57 21-JAN-07:03 5.00 3.19 0.00 0.00 01-JAN-00:10 5.00 3.19
February 0.210689E+09 2307.85 24-FEB-07:03 3.07 0.07 0.00 0.00 01-FEB-00:10 3.07 0.07
March 0.911623E+09 2450.18 30-MAR-16:00 27.80 17.47 0.00 0.00 01-MAR-00:10 27.80 17.47
April 0.150447E+10 3214.88 06-APR-06:02 1.20 -0.4 0.00 0.00 01-APR-00:10 1.20 -0.4
May 0.247216E+10 4011.85 30-MAY-15:20 29.67 21.52 0.00 0.00 01-MAY-00:10 29.67 21.52
June 0.364309E+10 4220.97 26-JUN-15:30 30.00 23.57 0.00 0.00 01-JUN-00:10 30.00 23.57
July 0.401903E+10 4669.52 10-JUL-15:30 32.50 22.22 0.00 0.00 01-JUL-00:10 32.50 22.22
August 0.447261E+10 4612.76 07-AUG-14:05 31.88 24.30 0.00 0.00 01-AUG-00:10 31.88 24.30
September 0.304226E+10 4521.33 11-SEP-16:00 30.00 22.85 0.00 0.00 01-SEP-00:10 30.00 22.85
October 0.154704E+10 3506.43 10-OCT-16:00 30.00 20.56 0.00 0.00 01-OCT-00:10 30.00 20.56
November 0.516010E+09 2178.47 21-NOV-07:01 -2.8 -3.9 0.00 0.00 01-NOV-00:10 -2.8 -3.9
December 0.134588E+09 1800.91 08-DEC-07:03 4.90 2.14 0.00 0.00 01-DEC-00:10 4.90 2.14
                     
Annual Sum or Average 0.225181E+11         0.00        
Minimum of Months 44546774.39 1791.57   -2.8 -3.9 0.00 0.00   -2.8 -3.9
Maximum of Months 0.447261E+10 4669.52   32.50 24.30 0.00 0.00   32.50 24.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.736296E+10 7765.50 31-JAN-17:00 19.40 13.37 0.156738E+10 2357.33 31-JAN-14:00 19.40 13.37
February 0.834670E+10 10965.02 28-FEB-17:00 23.90 12.94 0.152842E+10 2606.61 28-FEB-14:20 23.90 12.94
March 0.126972E+11 13777.98 30-MAR-16:00 27.80 17.47 0.206430E+10 2606.64 30-MAR-09:20 27.80 17.47
April 0.134998E+11 14688.56 17-APR-16:00 28.90 16.41 0.188625E+10 2606.65 17-APR-09:20 28.90 16.41
May 0.169133E+11 29154.65 30-MAY-05:12 19.07 17.52 0.206589E+10 2606.70 11-MAY-09:00 19.07 17.52
June 0.190881E+11 29085.38 19-JUN-05:12 20.93 20.12 0.206626E+10 2606.67 09-JUN-09:50 20.93 20.12
July 0.196016E+11 29327.65 07-JUL-04:03 25.22 21.53 0.192095E+10 2606.61 03-JUL-09:20 25.22 21.53
August 0.209851E+11 28982.82 22-AUG-05:12 22.80 21.57 0.215766E+10 2606.59 28-AUG-09:20 24.97 21.71
September 0.169293E+11 29082.00 11-SEP-05:12 20.20 19.05 0.191019E+10 2606.65 21-SEP-09:20 21.33 17.87
October 0.136580E+11 15163.47 11-OCT-16:00 26.10 17.12 0.193819E+10 2606.64 10-OCT-09:20 26.10 17.12
November 0.107375E+11 11995.09 06-NOV-17:00 18.90 9.61 0.184453E+10 2606.60 06-NOV-10:20 18.90 9.61
December 0.920378E+10 9045.35 13-DEC-17:00 16.70 16.70 0.162609E+10 2605.57 13-DEC-14:00 16.70 16.70
                     
Annual Sum or Average 0.169023E+12         0.225761E+11        
Minimum of Months 0.736296E+10 7765.50   16.70 9.61 0.152842E+10 2357.33   16.70 9.61
Maximum of Months 0.209851E+11 29327.65   28.90 21.57 0.215766E+10 2606.70   28.90 21.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.521445E+10 7649.93 20-JAN-17:00 16.70 11.48 0.150327E+10 2298.33 31-JAN-14:00 21.10 12.97
February 0.678380E+10 10972.83 28-FEB-17:00 23.90 12.94 0.145059E+10 2606.62 28-FEB-14:20 23.90 12.94
March 0.119458E+11 15787.35 30-MAR-16:00 27.80 17.47 0.196829E+10 2606.62 29-MAR-13:20 27.80 17.47
April 0.131738E+11 16925.89 17-APR-16:00 28.90 16.41 0.184563E+10 2606.63 17-APR-09:20 28.90 16.41
May 0.172158E+11 20401.62 30-MAY-05:12 19.07 17.52 0.205518E+10 2606.67 22-MAY-09:09 19.07 17.52
June 0.200822E+11 31345.86 19-JUN-05:12 20.93 20.12 0.206347E+10 2606.68 09-JUN-09:00 20.93 20.12
July 0.207669E+11 31461.58 24-JUL-05:12 20.60 19.55 0.192021E+10 2606.61 03-JUL-09:20 20.60 19.55
August 0.220737E+11 31289.08 28-AUG-05:12 21.50 20.43 0.215747E+10 2606.64 25-AUG-09:20 21.50 20.43
September 0.165508E+11 31101.72 05-SEP-05:12 21.70 20.50 0.189911E+10 2606.68 25-SEP-09:09 24.78 19.25
October 0.124323E+11 16098.66 11-OCT-15:50 26.28 17.62 0.186395E+10 2606.65 10-OCT-09:20 26.28 17.62
November 0.941162E+10 10804.65 06-NOV-17:00 18.90 9.61 0.170483E+10 2606.51 03-NOV-13:00 18.90 9.61
December 0.676980E+10 8356.46 13-DEC-17:00 16.70 16.70 0.151657E+10 2541.11 13-DEC-14:00 16.70 16.70
                     
Annual Sum or Average 0.162421E+12         0.219486E+11        
Minimum of Months 0.521445E+10 7649.93   16.70 9.61 0.145059E+10 2298.33   16.70 9.61
Maximum of Months 0.220737E+11 31461.58   28.90 20.50 0.215747E+10 2606.68   28.90 20.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.318418E+09 1585.46 31-JAN-16:40 19.60 13.44 0.309090E+09 482.84 31-JAN-14:00 19.60 13.44
February 0.786674E+09 2741.49 28-FEB-15:30 24.15 13.12 0.292934E+09 549.49 28-FEB-14:20 24.15 13.12
March 0.221415E+10 4704.34 30-MAR-15:50 27.80 17.41 0.391454E+09 549.49 29-MAR-13:20 27.80 17.41
April 0.291731E+10 5036.87 19-APR-14:30 26.15 17.54 0.375304E+09 549.49 12-APR-13:00 26.15 17.54
May 0.450914E+10 6495.41 30-MAY-15:00 30.60 21.44 0.429253E+09 549.50 18-MAY-09:20 30.60 21.44
June 0.613378E+10 11151.98 25-JUN-18:12 30.20 22.65 0.434853E+09 549.50 09-JUN-09:00 30.20 22.65
July 0.639171E+10 11229.11 16-JUL-13:02 32.48 24.02 0.405310E+09 549.49 03-JUL-09:20 32.48 24.02
August 0.663649E+10 10825.42 06-AUG-18:02 32.02 22.82 0.455043E+09 549.49 25-AUG-09:20 25.53 18.30
September 0.409761E+10 6252.20 06-SEP-14:30 30.25 23.24 0.396407E+09 549.50 25-SEP-09:20 25.17 19.30
October 0.241885E+10 4476.53 02-OCT-14:40 26.70 20.10 0.371883E+09 549.49 12-OCT-13:20 19.80 11.85
November 0.143789E+10 2139.50 02-NOV-15:30 22.50 16.22 0.334723E+09 549.46 03-NOV-13:00 21.70 17.40
December 0.648790E+09 1712.18 13-DEC-15:00 18.30 16.86 0.304328E+09 524.49 13-DEC-14:00 18.30 16.86
                     
Annual Sum or Average 0.385108E+11         0.450058E+10        
Minimum of Months 0.318418E+09 1585.46   18.30 13.12 0.292934E+09 482.84   18.30 11.85
Maximum of Months 0.663649E+10 11229.11   32.48 24.02 0.455043E+09 549.50   32.48 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359084E+09 1034.84 31-JAN-15:00 21.10 12.97 0.197876E+09 318.33 31-JAN-14:00 21.10 12.97
February 0.713179E+09 2368.19 27-FEB-10:30 13.90 6.16 0.194912E+09 347.87 28-FEB-14:20 25.00 13.71
March 0.182274E+10 3804.27 30-MAR-11:00 22.20 17.83 0.265320E+09 347.88 08-MAR-10:20 22.20 17.83
April 0.278971E+10 7500.16 16-APR-09:43 22.02 14.52 0.249011E+09 347.88 12-APR-13:00 22.02 14.52
May 0.414117E+10 11230.39 07-MAY-09:53 25.00 20.03 0.274880E+09 347.89 11-MAY-09:50 16.73 12.76
June 0.532896E+10 11840.27 04-JUN-09:32 25.93 19.04 0.276101E+09 347.89 09-JUN-09:00 24.40 15.46
July 0.555291E+10 11302.92 09-JUL-08:23 23.90 21.72 0.256999E+09 347.87 17-JUL-09:20 26.67 21.67
August 0.566143E+10 11867.92 27-AUG-09:22 26.10 21.69 0.288442E+09 347.88 25-AUG-09:20 26.10 21.69
September 0.370963E+10 11229.76 04-SEP-09:32 26.13 22.05 0.253018E+09 347.88 15-SEP-09:00 23.90 16.09
October 0.210214E+10 4574.16 11-OCT-10:20 23.73 19.29 0.247215E+09 347.87 10-OCT-09:20 23.73 19.29
November 0.111589E+10 2119.79 06-NOV-10:20 15.33 12.73 0.225056E+09 347.87 08-NOV-10:20 12.80 6.72
December 0.605393E+09 1105.56 13-DEC-13:30 19.45 17.14 0.198947E+09 338.73 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.339022E+11         0.292778E+10        
Minimum of Months 0.359084E+09 1034.84   13.90 6.16 0.194912E+09 318.33   12.80 6.72
Maximum of Months 0.566143E+10 11867.92   26.13 22.05 0.288442E+09 347.89   26.67 21.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122548E+10 4618.09 11-JAN-14:30 6.70 2.05 0.344723E+09 549.47 05-JAN-14:00 6.70 2.05
February 0.183869E+10 13359.10 26-FEB-15:02 24.90 12.68 0.321490E+09 549.50 22-FEB-14:20 24.90 12.68
March 0.362899E+10 9650.27 30-MAR-13:40 27.43 17.97 0.414585E+09 549.51 13-MAR-13:00 27.43 17.97
April 0.408842E+10 11402.83 16-APR-14:23 28.05 15.93 0.382757E+09 549.52 12-APR-13:00 28.05 15.93
May 0.514453E+10 9626.37 29-MAY-13:43 28.40 20.38 0.429139E+09 549.50 18-MAY-09:20 28.40 20.38
June 0.632650E+10 12940.67 25-JUN-14:13 31.83 23.24 0.434149E+09 549.50 09-JUN-09:20 31.83 23.24
July 0.670953E+10 13099.18 09-JUL-13:02 31.88 23.72 0.405302E+09 549.49 03-JUL-09:20 31.88 23.72
August 0.781475E+10 13539.67 27-AUG-13:23 31.70 22.52 0.455293E+09 549.49 25-AUG-09:20 31.70 22.52
September 0.580504E+10 13805.46 24-SEP-13:43 28.40 19.81 0.398330E+09 549.50 25-SEP-09:09 24.78 19.25
October 0.460975E+10 13794.59 09-OCT-13:13 26.47 18.95 0.391594E+09 556.15 10-OCT-13:50 29.22 21.00
November 0.295404E+10 13616.44 11-NOV-14:13 21.10 11.73 0.371947E+09 549.49 14-NOV-14:30 19.15 8.88
December 0.186859E+10 6397.28 08-DEC-14:10 12.80 5.52 0.346645E+09 549.48 08-DEC-14:30 12.80 5.48
                     
Annual Sum or Average 0.520143E+11         0.469595E+10        
Minimum of Months 0.122548E+10 4618.09   6.70 2.05 0.321490E+09 549.47   6.70 2.05
Maximum of Months 0.781475E+10 13805.46   31.88 23.72 0.455293E+09 556.15   31.88 23.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.363507E+09 1117.83 20-JAN-16:40 16.87 11.91 0.200645E+09 334.28 20-JAN-16:49 16.78 11.69
February 0.724512E+09 4429.21 27-FEB-17:00 22.20 11.44 0.190720E+09 347.84 28-FEB-14:20 25.00 13.71
March 0.202660E+10 6427.28 30-MAR-16:00 27.80 17.47 0.252983E+09 347.85 31-MAR-09:20 20.20 17.21
April 0.283907E+10 12029.44 09-APR-17:42 21.20 11.15 0.239691E+09 347.85 12-APR-13:00 28.90 17.10
May 0.398831E+10 12810.52 21-MAY-16:42 26.70 19.84 0.271959E+09 347.85 18-MAY-09:20 26.70 19.84
June 0.505526E+10 12459.78 25-JUN-16:12 33.13 22.15 0.275178E+09 347.85 09-JUN-09:20 33.13 22.15
July 0.522861E+10 12865.24 30-JUL-17:22 30.60 23.73 0.256756E+09 347.85 03-JUL-09:20 30.60 23.73
August 0.551473E+10 12784.04 13-AUG-17:02 31.10 22.35 0.288338E+09 347.85 25-AUG-09:20 25.53 18.30
September 0.354943E+10 11288.25 04-SEP-17:03 28.12 21.99 0.251669E+09 347.85 25-SEP-09:20 25.17 19.30
October 0.214735E+10 11193.70 09-OCT-16:33 27.07 19.44 0.239232E+09 347.84 18-OCT-09:20 21.30 20.48
November 0.117299E+10 4106.00 06-NOV-16:00 20.60 10.48 0.219629E+09 347.84 03-NOV-13:20 20.60 10.48
December 0.565923E+09 1692.97 11-DEC-15:50 21.10 15.67 0.200446E+09 347.83 12-DEC-14:30 22.80 16.62
                     
Annual Sum or Average 0.331763E+11         0.288725E+10        
Minimum of Months 0.363507E+09 1117.83   16.87 10.48 0.190720E+09 334.28   16.78 10.48
Maximum of Months 0.551473E+10 12865.24   33.13 23.73 0.288338E+09 347.85   33.13 23.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.390732E+09 1519.89 31-JAN-16:30 19.70 13.48 0.310149E+09 468.49 31-JAN-14:00 19.70 13.48
February 0.840162E+09 1740.90 28-FEB-15:40 23.87 12.92 0.291713E+09 537.20 28-FEB-14:00 23.87 12.92
March 0.204034E+10 2777.02 30-MAR-16:00 27.80 17.47 0.383829E+09 549.49 29-MAR-13:20 27.80 17.47
April 0.224921E+10 3038.01 19-APR-14:30 26.15 17.54 0.365095E+09 549.49 17-APR-13:20 26.15 17.54
May 0.322953E+10 4601.99 30-MAY-15:00 30.60 21.44 0.427068E+09 549.50 17-MAY-09:20 30.60 21.44
June 0.495395E+10 5373.73 26-JUN-06:03 23.30 21.67 0.434951E+09 549.50 09-JUN-09:20 23.30 21.67
July 0.548768E+10 6795.21 17-JUL-06:03 21.70 19.38 0.405131E+09 549.49 03-JUL-09:20 21.70 19.38
August 0.603156E+10 6610.68 07-AUG-06:03 22.88 22.15 0.455009E+09 549.49 21-AUG-09:20 23.50 22.59
September 0.416701E+10 5570.78 06-SEP-14:30 30.25 23.24 0.402010E+09 549.49 20-SEP-09:20 20.93 15.94
October 0.278486E+10 4137.44 02-OCT-14:30 26.70 20.05 0.394518E+09 549.49 10-OCT-09:20 21.50 18.02
November 0.200776E+10 2182.27 03-NOV-14:00 21.70 17.40 0.361511E+09 549.48 03-NOV-13:20 21.70 17.40
December 0.116233E+10 1710.59 13-DEC-13:30 19.45 17.14 0.312840E+09 524.20 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.353451E+11         0.454382E+10        
Minimum of Months 0.390732E+09 1519.89   19.45 12.92 0.291713E+09 468.49   18.30 12.92
Maximum of Months 0.603156E+10 6795.21   30.60 23.24 0.455009E+09 549.50   30.60 22.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.462794E+09 1016.36 31-JAN-14:50 21.02 13.03 0.200225E+09 313.88 31-JAN-14:00 21.10 12.97
February 0.755584E+09 2124.08 27-FEB-10:30 13.90 6.16 0.195828E+09 347.87 24-FEB-10:20 13.90 6.16
March 0.161391E+10 2765.75 14-MAR-09:30 16.95 13.93 0.265845E+09 347.88 08-MAR-10:20 16.95 13.93
April 0.210389E+10 4392.63 17-APR-10:10 23.27 15.57 0.247896E+09 347.88 17-APR-09:20 23.27 15.57
May 0.318628E+10 5429.81 30-MAY-10:00 27.80 21.16 0.274757E+09 347.89 11-MAY-09:00 27.80 21.16
June 0.454189E+10 9796.58 04-JUN-09:32 25.93 19.04 0.276182E+09 347.88 09-JUN-09:00 24.40 15.46
July 0.495971E+10 9805.12 04-JUL-09:52 27.20 23.54 0.257120E+09 347.87 03-JUL-09:20 27.20 23.54
August 0.532223E+10 9840.91 06-AUG-09:52 29.40 23.75 0.288574E+09 347.87 21-AUG-09:20 23.50 22.59
September 0.384928E+10 9369.92 24-SEP-10:02 26.38 18.55 0.255349E+09 347.88 15-SEP-09:39 26.38 18.55
October 0.249252E+10 4638.36 10-OCT-10:20 24.23 18.95 0.257577E+09 347.87 04-OCT-13:20 24.23 18.95
November 0.150794E+10 2704.54 06-NOV-10:10 14.87 12.62 0.244705E+09 347.87 14-NOV-14:30 19.15 8.88
December 0.988037E+09 1121.75 13-DEC-12:00 20.00 17.41 0.210650E+09 343.82 13-DEC-10:00 20.00 17.41
                     
Annual Sum or Average 0.317841E+11         0.297471E+10        
Minimum of Months 0.462794E+09 1016.36   13.90 6.16 0.195828E+09 313.88   13.90 6.16
Maximum of Months 0.532223E+10 9840.91   29.40 23.75 0.288574E+09 347.89   27.80 23.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.811457E+09 2881.96 28-JAN-14:40 11.67 4.40 0.319920E+09 548.47 31-JAN-14:50 21.02 13.03
February 0.131330E+10 10719.75 26-FEB-15:02 24.90 12.68 0.304472E+09 549.50 28-FEB-10:00 20.60 11.95
March 0.253911E+10 7795.91 30-MAR-16:10 27.62 17.53 0.400179E+09 549.50 13-MAR-13:00 27.62 17.53
April 0.284271E+10 7858.30 17-APR-16:10 28.80 16.45 0.368283E+09 549.50 27-APR-13:20 20.97 11.53
May 0.384491E+10 8761.14 30-MAY-12:00 29.40 21.24 0.419821E+09 549.50 10-MAY-13:20 29.40 21.24
June 0.586525E+10 9446.26 06-JUN-16:30 33.90 21.77 0.432928E+09 575.21 06-JUN-12:09 33.90 21.77
July 0.653966E+10 9852.44 07-JUL-16:50 35.10 23.67 0.405535E+09 598.80 14-JUL-12:09 33.40 24.44
August 0.810014E+10 10810.17 06-AUG-13:53 32.80 24.04 0.457374E+09 624.80 18-AUG-12:09 33.98 23.68
September 0.607834E+10 11114.97 24-SEP-13:23 28.60 19.84 0.401321E+09 602.80 07-SEP-12:09 28.60 19.84
October 0.453797E+10 11360.93 09-OCT-14:53 27.80 19.57 0.398392E+09 596.23 10-OCT-13:00 29.40 21.05
November 0.290139E+10 10851.83 12-NOV-13:33 18.53 10.32 0.379316E+09 549.50 21-NOV-14:09 9.08 3.58
December 0.180969E+10 6665.97 10-DEC-14:33 17.77 8.37 0.340027E+09 549.49 27-DEC-14:20 17.23 8.31
                     
Annual Sum or Average 0.471839E+11         0.462757E+10        
Minimum of Months 0.811457E+09 2881.96   11.67 4.40 0.304472E+09 548.47   9.08 3.58
Maximum of Months 0.810014E+10 11360.93   35.10 24.04 0.457374E+09 624.80   33.98 24.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.423814E+09 1063.90 23-JAN-17:00 10.00 3.54 0.200928E+09 321.07 23-JAN-16:00 10.00 3.54
February 0.728573E+09 3253.24 27-FEB-17:00 22.20 11.44 0.191122E+09 347.84 28-FEB-14:20 25.00 13.71
March 0.171717E+10 4400.69 30-MAR-16:00 27.80 17.47 0.256064E+09 347.84 29-MAR-13:20 27.80 17.47
April 0.207000E+10 4933.52 17-APR-16:00 28.90 16.41 0.239860E+09 347.85 18-APR-09:20 22.93 15.81
May 0.296919E+10 9814.88 29-MAY-17:32 29.60 20.23 0.272911E+09 347.85 17-MAY-09:20 29.60 20.23
June 0.424166E+10 10178.41 11-JUN-16:52 32.20 20.99 0.275863E+09 347.85 09-JUN-09:20 32.20 20.99
July 0.460658E+10 10450.44 04-JUL-17:52 30.60 22.43 0.256912E+09 347.85 03-JUL-09:20 30.60 22.43
August 0.515650E+10 10261.42 13-AUG-16:51 31.10 22.45 0.288550E+09 347.85 21-AUG-09:20 23.50 22.59
September 0.366594E+10 9659.52 04-SEP-16:53 28.30 22.10 0.255278E+09 347.85 20-SEP-09:20 20.93 15.94
October 0.242783E+10 8423.53 09-OCT-15:32 27.80 19.57 0.254866E+09 347.85 10-OCT-09:20 21.50 18.02
November 0.155779E+10 4075.96 06-NOV-16:30 19.75 10.05 0.238937E+09 347.85 09-NOV-14:20 19.60 12.10
December 0.933511E+09 1674.04 11-DEC-16:00 21.10 15.91 0.207584E+09 347.84 12-DEC-14:20 22.80 16.78
                     
Annual Sum or Average 0.304985E+11         0.293887E+10        
Minimum of Months 0.423814E+09 1063.90   10.00 3.54 0.191122E+09 321.07   10.00 3.54
Maximum of Months 0.515650E+10 10450.44   32.20 22.45 0.288550E+09 347.85   32.20 22.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.462320E+09 1603.47 31-JAN-16:40 19.60 13.44 0.311569E+09 490.73 31-JAN-14:00 19.60 13.44
February 0.101958E+10 2754.46 28-FEB-15:00 25.00 13.71 0.298429E+09 549.49 28-FEB-14:20 25.00 13.71
March 0.246559E+10 4188.01 30-MAR-15:50 27.80 17.41 0.406212E+09 549.49 30-MAR-09:20 27.80 17.41
April 0.294942E+10 4588.04 18-APR-14:00 27.20 15.86 0.384477E+09 549.50 17-APR-09:20 27.20 15.86
May 0.434511E+10 5885.79 30-MAY-15:00 30.60 21.44 0.433321E+09 549.50 17-MAY-09:20 30.60 21.44
June 0.580047E+10 7223.07 26-JUN-06:03 23.30 21.67 0.435674E+09 549.50 09-JUN-09:50 23.30 21.67
July 0.601462E+10 9490.82 16-JUL-13:02 32.48 24.02 0.405534E+09 549.49 03-JUL-09:20 32.48 24.02
August 0.628816E+10 7665.52 14-AUG-04:02 24.22 20.90 0.455219E+09 549.49 18-AUG-13:20 34.03 22.77
September 0.410757E+10 5692.11 06-SEP-14:30 30.25 23.24 0.400563E+09 549.50 21-SEP-09:20 21.33 17.87
October 0.270664E+10 4200.87 02-OCT-14:30 26.70 20.05 0.386693E+09 549.49 10-OCT-09:20 21.50 18.02
November 0.182932E+10 2303.64 03-NOV-14:00 21.70 17.40 0.352648E+09 549.48 03-NOV-13:20 21.70 17.40
December 0.101486E+10 1751.04 13-DEC-13:30 19.45 17.14 0.311771E+09 536.70 13-DEC-14:20 18.30 16.86
                     
Annual Sum or Average 0.390037E+11         0.458211E+10        
Minimum of Months 0.462320E+09 1603.47   19.45 13.44 0.298429E+09 490.73   18.30 13.44
Maximum of Months 0.628816E+10 9490.82   32.48 24.02 0.455219E+09 549.50   34.03 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.379169E+09 1153.24 31-JAN-15:05 20.92 13.08 0.149179E+09 345.68 31-JAN-15:09 20.92 13.08
February 0.755113E+09 4439.17 23-FEB-13:02 13.40 6.52 0.147021E+09 356.45 28-FEB-11:09 20.87 12.02
March 0.182905E+10 5452.84 15-MAR-12:02 13.48 6.47 0.200064E+09 356.46 13-MAR-14:09 13.48 6.47
April 0.267525E+10 7112.49 17-APR-10:05 23.27 15.57 0.185817E+09 356.47 12-APR-10:09 23.27 15.57
May 0.384135E+10 11098.79 07-MAY-09:02 23.58 19.38 0.204490E+09 356.48 11-MAY-10:09 17.67 13.57
June 0.487427E+10 11372.45 04-JUN-09:22 25.55 18.85 0.204821E+09 356.46 09-JUN-10:09 24.78 15.66
July 0.507383E+10 11638.71 09-JUL-10:12 28.67 23.11 0.191307E+09 356.45 17-JUL-10:09 27.88 22.09
August 0.519490E+10 11389.29 27-AUG-10:22 28.90 22.36 0.213907E+09 356.45 18-AUG-14:09 28.90 22.36
September 0.352136E+10 10719.74 04-SEP-09:53 26.70 22.31 0.188772E+09 356.47 15-SEP-10:09 24.18 16.24
October 0.216039E+10 6006.36 10-OCT-10:05 23.77 18.74 0.187276E+09 356.45 04-OCT-14:09 23.77 18.74
November 0.117083E+10 4002.33 28-NOV-13:02 15.87 7.11 0.175315E+09 356.45 14-NOV-13:09 15.87 7.11
December 0.674259E+09 3026.34 14-DEC-13:02 13.98 9.85 0.153865E+09 356.45 13-DEC-15:09 13.98 9.85
                     
Annual Sum or Average 0.321498E+11         0.220183E+10        
Minimum of Months 0.379169E+09 1153.24   13.40 6.47 0.147021E+09 345.68   13.48 6.47
Maximum of Months 0.519490E+10 11638.71   28.90 23.11 0.213907E+09 356.48   28.90 22.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152636E+10 4975.37 27-JAN-14:30 3.35 -2.1 0.351448E+09 549.47 26-JAN-14:00 3.35 -2.1
February 0.216203E+10 11197.22 26-FEB-13:13 24.07 12.58 0.328436E+09 549.50 22-FEB-14:20 24.07 12.58
March 0.392213E+10 9054.72 30-MAR-13:40 27.43 17.97 0.427064E+09 549.51 08-MAR-10:20 27.43 17.97
April 0.409874E+10 10131.52 16-APR-13:23 28.60 16.10 0.390567E+09 549.52 12-APR-13:00 28.60 16.10
May 0.494785E+10 7109.09 30-MAY-14:00 30.60 21.03 0.433188E+09 549.50 17-MAY-09:20 30.60 21.03
June 0.596297E+10 9646.92 25-JUN-14:13 31.83 23.24 0.435349E+09 549.50 09-JUN-09:20 31.83 23.24
July 0.629972E+10 11270.98 16-JUL-13:02 32.48 24.02 0.405658E+09 549.49 03-JUL-09:20 32.48 24.02
August 0.740193E+10 11754.95 06-AUG-13:53 32.80 24.04 0.455514E+09 549.49 10-AUG-13:20 30.93 23.78
September 0.575700E+10 12106.46 24-SEP-13:23 28.60 19.84 0.401739E+09 549.73 06-SEP-13:20 28.60 19.84
October 0.496995E+10 12215.17 09-OCT-12:53 26.10 18.71 0.402068E+09 573.73 10-OCT-13:50 29.22 21.00
November 0.350370E+10 12246.65 11-NOV-13:43 21.10 11.67 0.387176E+09 552.93 06-NOV-14:09 21.10 11.67
December 0.242779E+10 6942.27 08-DEC-13:50 12.62 5.51 0.357486E+09 549.49 11-DEC-10:50 14.45 11.70
                     
Annual Sum or Average 0.529802E+11         0.477569E+10        
Minimum of Months 0.152636E+10 4975.37   3.35 -2.1 0.328436E+09 549.47   3.35 -2.1
Maximum of Months 0.740193E+10 12246.65   32.80 24.04 0.455514E+09 573.73   32.48 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.461057E+09 1122.57 20-JAN-16:40 16.87 11.91 0.203335E+09 337.08 23-JAN-16:00 10.00 3.54
February 0.871174E+09 4330.02 27-FEB-17:00 22.20 11.44 0.194727E+09 347.84 28-FEB-14:20 25.00 13.71
March 0.217831E+10 6005.60 30-MAR-16:00 27.80 17.47 0.262199E+09 347.85 30-MAR-09:20 27.80 17.47
April 0.281554E+10 11035.95 09-APR-16:23 21.70 10.70 0.245459E+09 347.85 17-APR-09:20 20.93 14.77
May 0.382625E+10 11412.77 29-MAY-17:32 29.60 20.23 0.274599E+09 347.86 17-MAY-09:20 29.60 20.23
June 0.477214E+10 11741.06 11-JUN-17:02 32.20 20.99 0.275907E+09 347.85 09-JUN-09:20 32.20 20.99
July 0.491647E+10 11907.59 02-JUL-17:42 30.60 22.04 0.256966E+09 347.85 03-JUL-09:20 25.60 20.82
August 0.522795E+10 11682.83 13-AUG-16:51 31.10 22.45 0.288472E+09 347.85 21-AUG-09:20 23.50 22.59
September 0.351782E+10 11098.46 04-SEP-16:53 28.30 22.10 0.254132E+09 347.85 21-SEP-09:20 21.33 17.87
October 0.232957E+10 9576.30 09-OCT-15:32 27.80 19.57 0.247984E+09 347.85 10-OCT-09:20 21.50 18.02
November 0.143533E+10 4237.85 06-NOV-15:50 20.60 10.48 0.230199E+09 347.84 03-NOV-13:20 20.60 10.48
December 0.806996E+09 1918.65 11-DEC-15:40 21.10 15.44 0.205884E+09 347.83 12-DEC-14:30 22.80 16.62
                     
Annual Sum or Average 0.331586E+11         0.293986E+10        
Minimum of Months 0.461057E+09 1122.57   16.87 10.48 0.194727E+09 337.08   10.00 3.54
Maximum of Months 0.522795E+10 11907.59   32.20 22.45 0.288472E+09 347.86   32.20 22.59



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1580947.46 12850.47 09-JAN-07:01 -3.3
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 1580947.46      
Minimum of Months 0.00 0.00   -3.3
Maximum of Months 1580947.46 12850.47   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.328785E+10 12691.46 09-JAN-06:12 -2.6
February 0.207788E+10 13132.21 13-FEB-06:13 -5.6
March 0.719905E+09 4566.47 20-MAR-06:03 5.00
April 0.438407E+09 4554.15 06-APR-06:02 1.20
May 0.167854E+09 2936.91 10-MAY-05:03 8.98
June 75979879.66 2605.93 08-JUN-05:03 11.70
July 23953511.42 3102.93 15-JUL-05:03 23.98
August 22646977.12 4381.81 14-AUG-04:02 24.22
September 0.135910E+09 2526.52 29-SEP-05:03 12.30
October 0.593326E+09 4872.79 26-OCT-06:03 2.20
November 0.101442E+10 9518.13 22-NOV-07:02 -3.2
December 0.188479E+10 12289.21 18-DEC-06:13 -5.0
         
Annual Sum or Average 0.104429E+11      
Minimum of Months 22646977.12 2526.52   -5.6
Maximum of Months 0.328785E+10 13132.21   24.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.150642E+10 7093.44 09-JAN-07:11 -3.3
February 0.843919E+09 6403.01 13-FEB-07:11 -5.6
March 0.223897E+09 2349.88 26-MAR-13:03 17.98
April 53350875.02 2386.10 09-APR-16:23 21.70
May 10492275.64 1511.08 07-MAY-09:02 23.58
June 8881161.49 1645.41 11-JUN-08:23 22.50
July 13070687.64 1880.18 09-JUL-16:11 33.70
August 12163383.21 2108.51 13-AUG-16:11 30.37
September 11476965.96 1836.67 24-SEP-11:23 28.05
October 0.144925E+09 3077.44 09-OCT-15:32 27.80
November 0.429552E+09 3254.63 12-NOV-12:33 17.43
December 0.889387E+09 3522.05 04-DEC-07:03 -3.3
         
Annual Sum or Average 0.414754E+10      
Minimum of Months 8881161.49 1511.08   -5.6
Maximum of Months 0.150642E+10 7093.44   33.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112902E+10 3271.32 09-JAN-08:50 -3.3
February 0.618321E+09 3054.15 13-FEB-08:19 -4.8
March 55483942.34 1543.34 12-MAR-14:30 17.50
April 10321739.75 1628.84 09-APR-16:12 21.70
May 10237034.75 1346.89 14-MAY-09:40 20.77
June 13723815.31 1290.20 11-JUN-07:17 20.57
July 15313659.21 2769.93 07-JUL-04:03 25.22
August 17563604.07 2956.04 09-AUG-04:03 24.40
September 23097860.34 1754.01 17-SEP-11:20 26.13
October 66083101.51 2155.22 09-OCT-15:32 27.80
November 0.158012E+09 2235.08 26-NOV-13:05 17.57
December 0.605798E+09 2106.85 10-DEC-13:13 15.97
         
Annual Sum or Average 0.272298E+10      
Minimum of Months 10237034.75 1290.20   -4.8
Maximum of Months 0.112902E+10 3271.32   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.232536E+09 14971.83 09-JAN-06:10 -2.4
February 87131402.17 14265.67 06-FEB-07:05 0.00
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 31876994.91 14289.93 26-DEC-07:05 3.30
         
Annual Sum or Average 0.351544E+09      
Minimum of Months 0.00 0.00   -2.4
Maximum of Months 0.232536E+09 14971.83   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.173080E+10 30736.77 09-JAN-05:01 -2.2
February 0.754155E+09 30250.88 13-FEB-05:01 -5.1
March 11012620.10 24910.07 23-MAR-06:03 6.10
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 10303565.44 24939.56 31-OCT-06:03 8.22
November 70965589.77 26209.75 22-NOV-06:01 -3.3
December 0.587970E+09 28730.72 26-DEC-06:11 3.30
         
Annual Sum or Average 0.316521E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.173080E+10 30736.77   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.300220E+10 9921.84 09-JAN-04:43 -2.1
February 0.161506E+10 10224.93 12-FEB-07:12 -12.6
March 0.134399E+09 8399.43 23-MAR-05:12 6.10
April 35392836.85 7891.97 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 57855270.99 8421.88 26-OCT-05:12 2.20
November 0.395158E+09 9061.28 22-NOV-05:03 -2.9
December 0.138102E+10 9839.24 18-DEC-05:01 -5.0
         
Annual Sum or Average 0.662108E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.300220E+10 10224.93   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.158559E+10 9197.60 23-JAN-05:01 -1.7
February 0.811010E+09 9532.35 12-FEB-06:33 -12.6
March 61087109.73 7759.98 23-MAR-05:12 6.10
April 15323659.95 7299.37 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 35057459.10 7767.37 26-OCT-05:12 2.20
November 0.170941E+09 8380.89 25-NOV-06:01 0.68
December 0.641074E+09 9226.98 04-DEC-05:01 -2.8
         
Annual Sum or Average 0.332009E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.158559E+10 9532.35   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.187379E+10 11340.65 02-JAN-06:11 3.30
February 0.100336E+10 11763.11 12-FEB-07:12 -12.6
March 87479000.08 9700.52 23-MAR-05:12 6.10
April 29890944.99 9132.60 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 42929048.45 9555.44 26-OCT-05:12 2.20
November 0.206499E+09 10260.26 25-NOV-06:01 0.68
December 0.746788E+09 11271.60 26-DEC-06:11 3.30
         
Annual Sum or Average 0.399074E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.187379E+10 11763.11   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.174604E+10 9136.20 23-JAN-05:01 -1.7
February 0.927653E+09 9517.95 12-FEB-06:33 -12.6
March 73714788.10 7553.27 23-MAR-05:12 6.10
April 19648627.45 7245.10 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 35481342.47 7494.73 26-OCT-05:12 2.20
November 0.234368E+09 8234.10 25-NOV-06:01 0.68
December 0.799725E+09 9168.89 04-DEC-05:01 -2.8
         
Annual Sum or Average 0.383663E+10      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.174604E+10 9517.95   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148647E+10 7537.26 09-JAN-05:01 -2.2
February 0.756988E+09 7670.44 13-FEB-05:01 -5.1
March 29896678.98 6282.17 22-MAR-06:03 5.50
April 9880923.56 6317.55 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 313043.61 2086.96 26-OCT-06:03 2.20
November 15015730.78 6365.58 22-NOV-07:01 -3.2
December 0.233567E+09 6914.21 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.253214E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.148647E+10 7670.44   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.720235E+09 6626.79 09-JAN-05:01 -2.2
February 0.308353E+09 6666.80 13-FEB-05:01 -5.1
March 11514054.25 5404.57 23-MAR-06:03 6.10
April 2370556.27 5420.77 07-APR-06:02 2.80
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 93591.94 568.40 26-OCT-06:03 2.20
November 3363202.94 5411.41 22-NOV-07:01 -3.2
December 85982452.29 5864.14 04-DEC-06:01 -2.9
         
Annual Sum or Average 0.113191E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.720235E+09 6666.80   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279825E+10 10023.36 27-JAN-07:10 -6.7
February 0.171832E+10 10282.79 03-FEB-07:10 -8.9
March 0.685020E+09 8165.35 23-MAR-07:00 6.10
April 0.385582E+09 8572.43 06-APR-06:10 1.20
May 90026572.85 7423.43 11-MAY-06:10 8.17
June 9374579.96 3833.37 08-JUN-06:05 12.07
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 10063043.04 4405.81 14-SEP-06:07 12.30
October 0.338470E+09 8194.29 26-OCT-07:00 2.20
November 0.672697E+09 8992.56 22-NOV-07:10 -3.2
December 0.109097E+10 9381.51 18-DEC-07:10 -5.1
         
Annual Sum or Average 0.779876E+10      
Minimum of Months 0.00 0.00   -8.9
Maximum of Months 0.279825E+10 10282.79   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.748382E+09 6661.60 09-JAN-05:01 -2.2
February 0.351178E+09 6601.39 13-FEB-05:01 -5.1
March 8078407.34 5391.50 23-MAR-06:03 6.10
April 2183707.60 5289.60 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 9997.05 66.65 31-OCT-06:03 8.22
November 6742209.11 5399.04 22-NOV-07:01 -3.2
December 0.101162E+09 5847.71 26-DEC-06:11 3.30
         
Annual Sum or Average 0.121774E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.748382E+09 6661.60   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147226E+10 8349.49 09-JAN-05:01 -2.2
February 0.672305E+09 8508.25 13-FEB-05:01 -5.1
March 15884347.74 6741.06 23-MAR-06:03 6.10
April 3383307.27 6763.94 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 5706029.73 6755.92 31-OCT-06:03 8.22
November 68126055.13 7318.00 22-NOV-06:01 -3.3
December 0.443754E+09 7823.87 04-DEC-05:01 -2.8
         
Annual Sum or Average 0.268142E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.147226E+10 8508.25   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.773159E+09 6946.79 09-JAN-05:01 -2.2
February 0.319966E+09 7133.71 13-FEB-05:01 -5.1
March 9204869.07 5380.40 23-MAR-06:03 6.10
April 1873152.08 5252.96 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 3937940.42 5357.74 26-OCT-06:03 2.20
November 26439835.61 5836.03 22-NOV-06:01 -3.3
December 0.200225E+09 6629.19 04-DEC-05:01 -2.8
         
Annual Sum or Average 0.133481E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.773159E+09 7133.71   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.825798E+09 9878.12 09-JAN-05:01 -2.2
February 0.350082E+09 9769.01 13-FEB-05:01 -5.1
March 9349914.49 7958.02 23-MAR-06:03 6.10
April 2498164.54 7947.55 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 4329089.85 7954.74 31-OCT-06:03 8.22
November 30175774.56 8457.95 22-NOV-06:01 -3.3
December 0.210614E+09 9152.21 26-DEC-06:11 3.30
         
Annual Sum or Average 0.143285E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.825798E+09 9878.12   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.829732E+09 6969.86 09-JAN-05:01 -2.2
February 0.367526E+09 7075.09 13-FEB-05:01 -5.1
March 7836472.69 5374.15 23-MAR-06:03 6.10
April 1675351.68 5616.83 06-APR-06:02 1.20
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 3953091.54 5241.41 26-OCT-06:03 2.20
November 41363124.80 5838.81 22-NOV-06:01 -3.3
December 0.251287E+09 6328.19 26-DEC-06:11 3.30
         
Annual Sum or Average 0.150337E+10      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.829732E+09 7075.09   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.250423E+12    
Minimum of Months 0.420695E+10 4936.01   0.191215E+11 14019.75  
Maximum of Months 0.500524E+10 4936.01   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.621701E+09 950.03 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.560104E+09 1011.44 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.601732E+09 957.97 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.516580E+09 865.53 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.539682E+09 570.89 24-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.531085E+09 562.52 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.503002E+09 675.59 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.571568E+09 823.21 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.532828E+09 904.88 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.598181E+09 1038.01 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.601553E+09 1025.00 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.606438E+09 952.56 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.678446E+10     0.243325E+11    
Minimum of Months 0.503002E+09 562.52   0.185366E+10 1435.25  
Maximum of Months 0.621701E+09 1038.01   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381030E+09 588.12 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.344466E+09 640.12 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.376158E+09 599.64 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.326188E+09 523.41 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.344041E+09 338.93 02-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.338944E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.320160E+09 362.00 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.362229E+09 493.31 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.334437E+09 555.99 29-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.366053E+09 657.13 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.373043E+09 643.36 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.372110E+09 589.92 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.423886E+10     0.154036E+11    
Minimum of Months 0.320160E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.381030E+09 657.13   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.586184E+09 936.67 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.535491E+09 1011.44 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.594583E+09 956.57 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.518448E+09 869.03 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.545919E+09 582.39 24-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.537539E+09 573.92 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.508833E+09 717.72 27-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.574766E+09 833.11 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.529757E+09 896.92 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.573051E+09 1038.01 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.574029E+09 1019.62 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.569357E+09 937.96 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.664796E+10     0.243324E+11    
Minimum of Months 0.508833E+09 573.92   0.185364E+10 1435.24  
Maximum of Months 0.594583E+09 1038.01   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381858E+09 603.40 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.348211E+09 640.07 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.381215E+09 609.51 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.328317E+09 562.94 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.345332E+09 498.57 24-MAY-07:30 0.132212E+10 908.57 01-MAY-07:10
June 0.339498E+09 369.02 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.321841E+09 478.36 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.364292E+09 539.86 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.338538E+09 578.82 29-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.374689E+09 657.08 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.370521E+09 649.87 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.370858E+09 604.32 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.426517E+10     0.154035E+11    
Minimum of Months 0.321841E+09 369.02   0.117344E+10 908.57  
Maximum of Months 0.381858E+09 657.08   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.617943E+09 946.55 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.556860E+09 1010.34 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.599850E+09 954.78 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.515537E+09 858.68 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.539643E+09 567.41 24-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.530785E+09 558.63 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.502609E+09 584.57 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.570834E+09 814.71 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.531435E+09 899.62 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.595446E+09 1037.91 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.598366E+09 1024.39 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.603024E+09 949.19 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.676233E+10     0.243325E+11    
Minimum of Months 0.502609E+09 558.63   0.185366E+10 1435.25  
Maximum of Months 0.617943E+09 1037.91   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.379756E+09 585.72 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.343491E+09 639.54 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.375431E+09 597.68 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.325783E+09 518.60 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.343649E+09 335.77 02-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.338668E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.319779E+09 359.95 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.361880E+09 487.68 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.333853E+09 552.53 29-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.365116E+09 657.08 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.371974E+09 642.79 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.370931E+09 587.60 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.423031E+10     0.154036E+11    
Minimum of Months 0.319779E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.379756E+09 657.08   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.585062E+09 932.51 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.534720E+09 1010.34 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.593664E+09 953.32 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.517286E+09 862.34 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.545008E+09 579.67 24-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.536696E+09 570.78 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.508036E+09 705.22 27-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.573778E+09 825.09 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.528780E+09 891.27 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.571711E+09 1037.91 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.573121E+09 1018.74 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.567917E+09 933.85 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.663578E+10     0.243324E+11    
Minimum of Months 0.508036E+09 570.78   0.185364E+10 1435.24  
Maximum of Months 0.593664E+09 1037.91   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.380588E+09 601.69 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.346907E+09 639.50 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.380229E+09 608.00 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.327745E+09 560.01 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.344782E+09 493.97 24-MAY-07:30 0.132212E+10 908.57 01-MAY-07:10
June 0.338962E+09 367.49 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.321257E+09 472.85 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.363528E+09 536.22 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.337670E+09 576.37 29-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.373494E+09 657.03 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.369535E+09 649.60 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.369753E+09 602.64 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.425445E+10     0.154035E+11    
Minimum of Months 0.321257E+09 367.49   0.117344E+10 908.57  
Maximum of Months 0.380588E+09 657.03   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.621697E+09 950.03 03-JAN-08:09 0.204758E+10 1435.25 02-JAN-08:09
February 0.560101E+09 1011.44 01-FEB-08:09 0.185366E+10 1435.25 01-FEB-08:09
March 0.601731E+09 957.96 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.516580E+09 865.52 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.539682E+09 570.88 24-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.531085E+09 562.51 23-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.503001E+09 675.55 27-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.571567E+09 823.19 24-AUG-07:10 0.212947E+10 1435.25 01-AUG-07:10
September 0.532827E+09 904.86 29-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.598179E+09 1038.01 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.601550E+09 1025.00 01-NOV-07:10 0.200273E+10 1435.25 01-NOV-07:10
December 0.606435E+09 952.55 06-DEC-08:09 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.678443E+10     0.243325E+11    
Minimum of Months 0.503001E+09 562.51   0.185366E+10 1435.25  
Maximum of Months 0.621697E+09 1038.01   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381029E+09 588.11 03-JAN-08:09 0.129621E+10 908.57 02-JAN-08:09
February 0.344464E+09 640.11 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.376158E+09 599.63 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.326188E+09 523.40 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.344041E+09 338.92 02-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.338943E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.320160E+09 362.00 27-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.362228E+09 493.30 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.334436E+09 555.98 29-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.366052E+09 657.13 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.373042E+09 643.36 01-NOV-07:10 0.126781E+10 908.57 01-NOV-07:10
December 0.372109E+09 589.92 06-DEC-08:09 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.423885E+10     0.154036E+11    
Minimum of Months 0.320160E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.381029E+09 657.13   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.586183E+09 936.66 03-JAN-08:09 0.204757E+10 1435.24 02-JAN-08:09
February 0.535489E+09 1011.44 01-FEB-08:09 0.185364E+10 1435.24 01-FEB-08:09
March 0.594582E+09 956.57 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.518447E+09 869.01 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.545918E+09 582.38 24-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.537539E+09 573.91 23-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.508832E+09 717.69 27-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.574765E+09 833.09 24-AUG-07:10 0.212945E+10 1435.24 01-AUG-07:10
September 0.529756E+09 896.91 29-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.573049E+09 1038.01 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.574028E+09 1019.62 01-NOV-07:10 0.200271E+10 1435.24 01-NOV-07:10
December 0.569356E+09 937.95 06-DEC-08:09 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.664795E+10     0.243324E+11    
Minimum of Months 0.508832E+09 573.91   0.185364E+10 1435.24  
Maximum of Months 0.594582E+09 1038.01   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.381857E+09 603.39 03-JAN-08:09 0.129620E+10 908.57 02-JAN-08:09
February 0.348209E+09 640.07 01-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.381215E+09 609.50 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.328317E+09 562.93 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.345332E+09 498.55 24-MAY-07:30 0.132212E+10 908.57 01-MAY-07:10
June 0.339498E+09 369.01 23-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.321841E+09 478.34 27-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.364291E+09 539.84 24-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.338537E+09 578.82 29-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.374688E+09 657.08 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.370520E+09 649.87 01-NOV-07:10 0.126780E+10 908.57 01-NOV-07:10
December 0.370857E+09 604.32 06-DEC-08:09 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.426516E+10     0.154035E+11    
Minimum of Months 0.321841E+09 369.01   0.117344E+10 908.57  
Maximum of Months 0.381857E+09 657.08   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.621701E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.459643E+09
February 0.901968E+09 0.560104E+09 0.185366E+10 0.00 0.00 0.00 0.00 935637.93 0.393051E+09
March 0.107774E+10 0.601732E+09 0.212947E+10 0.00 0.00 0.00 0.00 1146985.63 0.257230E+09
April 0.956342E+09 0.516580E+09 0.197726E+10 0.00 0.00 0.00 0.00 2959132.87 0.163037E+09
May 0.103597E+10 0.539682E+09 0.208852E+10 0.00 0.00 0.00 0.00 7834879.84 0.107104E+09
June 0.103308E+10 0.531085E+09 0.205071E+10 0.00 0.00 0.00 0.00 32877323.45 53607836.89
July 0.959235E+09 0.503002E+09 0.201461E+10 0.00 0.00 0.00 0.00 35438590.33 35715449.75
August 0.107774E+10 0.571568E+09 0.212947E+10 0.00 0.00 0.00 0.00 34526459.12 22595241.08
September 0.956342E+09 0.532828E+09 0.197634E+10 0.00 0.00 0.00 0.00 10166887.46 53812231.23
October 0.994195E+09 0.598181E+09 0.204804E+10 0.00 0.00 0.00 0.00 3083130.50 0.172903E+09
November 0.984487E+09 0.601553E+09 0.200273E+10 0.00 0.00 0.00 0.00 312997.56 0.244229E+09
December 0.959235E+09 0.606438E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.415498E+09
                   
Annual Sum or Average 0.119305E+11 0.678446E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.129282E+09 0.237843E+10
Minimum of Months 0.901968E+09 0.503002E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 22595241.08
Maximum of Months 0.107774E+10 0.621701E+09 0.212947E+10 0.00 0.00 0.00 0.00 35438590.33 0.459643E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.381030E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.310782E+09
February 0.571020E+09 0.344466E+09 0.117344E+10 0.00 0.00 0.00 0.00 198956.27 0.268489E+09
March 0.682301E+09 0.376158E+09 0.134804E+10 0.00 0.00 0.00 0.00 673450.45 0.179549E+09
April 0.605444E+09 0.326188E+09 0.125169E+10 0.00 0.00 0.00 0.00 1521842.90 0.113154E+09
May 0.655854E+09 0.344041E+09 0.132213E+10 0.00 0.00 0.00 0.00 4583455.09 75049950.14
June 0.654023E+09 0.338944E+09 0.129819E+10 0.00 0.00 0.00 0.00 21180831.44 36802663.95
July 0.607275E+09 0.320160E+09 0.127534E+10 0.00 0.00 0.00 0.00 22588017.76 24808582.79
August 0.682301E+09 0.362229E+09 0.134804E+10 0.00 0.00 0.00 0.00 22178341.68 15715748.34
September 0.605444E+09 0.334437E+09 0.125111E+10 0.00 0.00 0.00 0.00 5959827.90 36899883.68
October 0.629407E+09 0.366053E+09 0.129650E+10 0.00 0.00 0.00 0.00 1400863.03 0.120058E+09
November 0.623262E+09 0.373043E+09 0.126781E+10 0.00 0.00 0.00 0.00 164144.19 0.168401E+09
December 0.607275E+09 0.372110E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.280757E+09
                   
Annual Sum or Average 0.755301E+10 0.423886E+10 0.154036E+11 0.00 0.00 0.00 0.00 80449730.70 0.163047E+10
Minimum of Months 0.571020E+09 0.320160E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 15715748.34
Maximum of Months 0.682301E+09 0.381030E+09 0.134804E+10 0.00 0.00 0.00 0.00 22588017.76 0.310782E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.586184E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.489184E+09
February 0.901968E+09 0.535491E+09 0.185364E+10 0.00 0.00 0.00 0.00 51441.17 0.420418E+09
March 0.107774E+10 0.594583E+09 0.212945E+10 0.00 0.00 0.00 0.00 888148.53 0.280962E+09
April 0.956342E+09 0.518448E+09 0.197725E+10 0.00 0.00 0.00 0.00 2208047.74 0.169345E+09
May 0.103597E+10 0.545919E+09 0.208851E+10 0.00 0.00 0.00 0.00 7214300.93 0.108204E+09
June 0.103308E+10 0.537539E+09 0.205070E+10 0.00 0.00 0.00 0.00 32691838.11 53032484.34
July 0.959235E+09 0.508833E+09 0.201460E+10 0.00 0.00 0.00 0.00 35096806.77 35601489.31
August 0.107774E+10 0.574766E+09 0.212945E+10 0.00 0.00 0.00 0.00 33461610.97 23331099.75
September 0.956342E+09 0.529757E+09 0.197632E+10 0.00 0.00 0.00 0.00 8448112.80 56056593.50
October 0.994195E+09 0.573051E+09 0.204803E+10 0.00 0.00 0.00 0.00 1367541.92 0.188549E+09
November 0.984487E+09 0.574029E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.269977E+09
December 0.959235E+09 0.569357E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.443149E+09
                   
Annual Sum or Average 0.119305E+11 0.664796E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.121428E+09 0.253781E+10
Minimum of Months 0.901968E+09 0.508833E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 23331099.75
Maximum of Months 0.107774E+10 0.594583E+09 0.212945E+10 0.00 0.00 0.00 0.00 35096806.77 0.489184E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.381858E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.312009E+09
February 0.570983E+09 0.348211E+09 0.117344E+10 0.00 0.00 0.00 0.00 305362.97 0.268868E+09
March 0.682256E+09 0.381215E+09 0.134804E+10 0.00 0.00 0.00 0.00 597009.54 0.183632E+09
April 0.605404E+09 0.328317E+09 0.125169E+10 0.00 0.00 0.00 0.00 1618494.81 0.114307E+09
May 0.655811E+09 0.345332E+09 0.132212E+10 0.00 0.00 0.00 0.00 4665107.06 74862800.79
June 0.653980E+09 0.339498E+09 0.129818E+10 0.00 0.00 0.00 0.00 21019433.19 37337873.98
July 0.607235E+09 0.321841E+09 0.127533E+10 0.00 0.00 0.00 0.00 22532041.58 24868147.11
August 0.682256E+09 0.364292E+09 0.134804E+10 0.00 0.00 0.00 0.00 21577453.29 16760979.52
September 0.605404E+09 0.338538E+09 0.125110E+10 0.00 0.00 0.00 0.00 6024527.23 37787760.12
October 0.629366E+09 0.374689E+09 0.129649E+10 0.00 0.00 0.00 0.00 1233800.02 0.121067E+09
November 0.623221E+09 0.370521E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.169393E+09
December 0.607235E+09 0.370858E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.281428E+09
                   
Annual Sum or Average 0.755252E+10 0.426517E+10 0.154035E+11 0.00 0.00 0.00 0.00 79573229.69 0.164232E+10
Minimum of Months 0.570983E+09 0.321841E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 16760979.52
Maximum of Months 0.682256E+09 0.381858E+09 0.134804E+10 0.00 0.00 0.00 0.00 22532041.58 0.312009E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.617943E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.263450E+09
February 0.901968E+09 0.556860E+09 0.185366E+10 0.00 0.00 0.00 0.00 543157.41 0.219969E+09
March 0.107774E+10 0.599850E+09 0.212947E+10 0.00 0.00 0.00 0.00 916251.80 0.136941E+09
April 0.956342E+09 0.515537E+09 0.197726E+10 0.00 0.00 0.00 0.00 2332384.01 81746590.77
May 0.103597E+10 0.539643E+09 0.208852E+10 0.00 0.00 0.00 0.00 5000191.99 54117659.02
June 0.103308E+10 0.530785E+09 0.205071E+10 0.00 0.00 0.00 0.00 18875617.29 27234923.74
July 0.959235E+09 0.502609E+09 0.201461E+10 0.00 0.00 0.00 0.00 20708955.42 18335084.12
August 0.107774E+10 0.570834E+09 0.212947E+10 0.00 0.00 0.00 0.00 19748810.37 11550316.94
September 0.956342E+09 0.531435E+09 0.197634E+10 0.00 0.00 0.00 0.00 5631776.97 31580590.50
October 0.994195E+09 0.595446E+09 0.204804E+10 0.00 0.00 0.00 0.00 1589955.88 0.104358E+09
November 0.984487E+09 0.598366E+09 0.200273E+10 0.00 0.00 0.00 0.00 22144.30 0.148853E+09
December 0.959235E+09 0.603024E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.250725E+09
                   
Annual Sum or Average 0.119305E+11 0.676233E+10 0.243325E+11 0.00 0.00 0.00 0.00 75369245.43 0.134886E+10
Minimum of Months 0.901968E+09 0.502609E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 11550316.94
Maximum of Months 0.107774E+10 0.617943E+09 0.212947E+10 0.00 0.00 0.00 0.00 20708955.42 0.263450E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.379756E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.178924E+09
February 0.571020E+09 0.343491E+09 0.117344E+10 0.00 0.00 0.00 0.00 116833.90 0.151578E+09
March 0.682301E+09 0.375431E+09 0.134804E+10 0.00 0.00 0.00 0.00 462212.25 98176808.22
April 0.605444E+09 0.325783E+09 0.125169E+10 0.00 0.00 0.00 0.00 1021759.71 58686111.10
May 0.655854E+09 0.343649E+09 0.132213E+10 0.00 0.00 0.00 0.00 2697119.19 39418523.49
June 0.654023E+09 0.338668E+09 0.129819E+10 0.00 0.00 0.00 0.00 11744976.74 19462543.19
July 0.607275E+09 0.319779E+09 0.127534E+10 0.00 0.00 0.00 0.00 12524997.60 13332695.14
August 0.682301E+09 0.361880E+09 0.134804E+10 0.00 0.00 0.00 0.00 12152116.79 8637148.26
September 0.605444E+09 0.333853E+09 0.125111E+10 0.00 0.00 0.00 0.00 3304424.46 22025335.91
October 0.629407E+09 0.365116E+09 0.129650E+10 0.00 0.00 0.00 0.00 714277.39 73192075.37
November 0.623262E+09 0.371974E+09 0.126781E+10 0.00 0.00 0.00 0.00 1728.76 0.104129E+09
December 0.607275E+09 0.370931E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.170756E+09
                   
Annual Sum or Average 0.755301E+10 0.423031E+10 0.154036E+11 0.00 0.00 0.00 0.00 44740446.78 0.938318E+09
Minimum of Months 0.571020E+09 0.319779E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 8637148.26
Maximum of Months 0.682301E+09 0.379756E+09 0.134804E+10 0.00 0.00 0.00 0.00 12524997.60 0.178924E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.585062E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.431001E+10
February 0.901968E+09 0.534720E+09 0.185364E+10 0.00 0.00 0.00 0.00 620466.68 0.315559E+10
March 0.107774E+10 0.593664E+09 0.212945E+10 0.00 0.00 0.00 0.00 26632563.38 0.228998E+10
April 0.956342E+09 0.517286E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.139995E+09 0.129556E+10
May 0.103597E+10 0.545008E+09 0.208851E+10 0.00 0.00 0.00 0.00 0.333029E+09 0.694500E+09
June 0.103308E+10 0.536696E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.935100E+09 0.261840E+09
July 0.959235E+09 0.508036E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.967039E+09 0.197464E+09
August 0.107774E+10 0.573778E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.107090E+10 0.121436E+09
September 0.956342E+09 0.528780E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.368525E+09 0.464242E+09
October 0.994195E+09 0.571711E+09 0.204803E+10 0.00 0.00 0.00 0.00 66434839.03 0.177626E+10
November 0.984487E+09 0.573121E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.270924E+10
December 0.959235E+09 0.567917E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.323322E+10
                   
Annual Sum or Average 0.119305E+11 0.663578E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.390827E+10 0.205093E+11
Minimum of Months 0.901968E+09 0.508036E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.121436E+09
Maximum of Months 0.107774E+10 0.593664E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.107090E+10 0.431001E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.380588E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.179420E+09
February 0.570983E+09 0.346907E+09 0.117344E+10 0.00 0.00 0.00 0.00 152734.92 0.151307E+09
March 0.682256E+09 0.380229E+09 0.134804E+10 0.00 0.00 0.00 0.00 355549.83 0.100592E+09
April 0.605404E+09 0.327745E+09 0.125169E+10 0.00 0.00 0.00 0.00 956104.89 59767673.30
May 0.655811E+09 0.344782E+09 0.132212E+10 0.00 0.00 0.00 0.00 2624340.69 39495559.39
June 0.653980E+09 0.338962E+09 0.129818E+10 0.00 0.00 0.00 0.00 11538907.00 19846942.54
July 0.607235E+09 0.321257E+09 0.127533E+10 0.00 0.00 0.00 0.00 12467235.22 13333812.38
August 0.682256E+09 0.363528E+09 0.134804E+10 0.00 0.00 0.00 0.00 11754031.99 9286818.83
September 0.605404E+09 0.337670E+09 0.125110E+10 0.00 0.00 0.00 0.00 3239480.08 22590586.16
October 0.629366E+09 0.373494E+09 0.129649E+10 0.00 0.00 0.00 0.00 605478.95 74030329.52
November 0.623221E+09 0.369535E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.104482E+09
December 0.607235E+09 0.369753E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.170568E+09
                   
Annual Sum or Average 0.755252E+10 0.425445E+10 0.154035E+11 0.00 0.00 0.00 0.00 43693863.59 0.944720E+09
Minimum of Months 0.570983E+09 0.321257E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 9286818.83
Maximum of Months 0.682256E+09 0.380588E+09 0.134804E+10 0.00 0.00 0.00 0.00 12467235.22 0.179420E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.621697E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.406266E+09
February 0.901968E+09 0.560101E+09 0.185366E+10 0.00 0.00 0.00 0.00 683133.08 0.345660E+09
March 0.107774E+10 0.601731E+09 0.212947E+10 0.00 0.00 0.00 0.00 955051.13 0.228789E+09
April 0.956342E+09 0.516580E+09 0.197726E+10 0.00 0.00 0.00 0.00 2612539.39 0.142531E+09
May 0.103597E+10 0.539682E+09 0.208852E+10 0.00 0.00 0.00 0.00 6932392.59 92776749.14
June 0.103308E+10 0.531085E+09 0.205071E+10 0.00 0.00 0.00 0.00 28338397.37 46029114.16
July 0.959235E+09 0.503001E+09 0.201461E+10 0.00 0.00 0.00 0.00 30746248.60 30546832.88
August 0.107774E+10 0.571567E+09 0.212947E+10 0.00 0.00 0.00 0.00 29682867.62 19367895.88
September 0.956342E+09 0.532827E+09 0.197634E+10 0.00 0.00 0.00 0.00 8727609.30 48139410.88
October 0.994195E+09 0.598179E+09 0.204804E+10 0.00 0.00 0.00 0.00 2524480.21 0.156640E+09
November 0.984487E+09 0.601550E+09 0.200273E+10 0.00 0.00 0.00 0.00 88406.10 0.223028E+09
December 0.959235E+09 0.606435E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.377405E+09
                   
Annual Sum or Average 0.119305E+11 0.678443E+10 0.243325E+11 0.00 0.00 0.00 0.00 0.111291E+09 0.211718E+10
Minimum of Months 0.901968E+09 0.503001E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 19367895.88
Maximum of Months 0.107774E+10 0.621697E+09 0.212947E+10 0.00 0.00 0.00 0.00 30746248.60 0.406266E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.381029E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.275244E+09
February 0.421807E+09 0.344464E+09 0.117344E+10 0.00 0.00 0.00 0.00 129885.99 0.236814E+09
March 0.502994E+09 0.376158E+09 0.134804E+10 0.00 0.00 0.00 0.00 534534.96 0.159651E+09
April 0.447140E+09 0.326188E+09 0.125169E+10 0.00 0.00 0.00 0.00 1284528.93 98705313.07
May 0.484071E+09 0.344041E+09 0.132213E+10 0.00 0.00 0.00 0.00 3851071.05 64868733.27
June 0.482240E+09 0.338943E+09 0.129819E+10 0.00 0.00 0.00 0.00 17706290.48 31607830.85
July 0.448971E+09 0.320160E+09 0.127534E+10 0.00 0.00 0.00 0.00 19069272.34 21297296.29
August 0.502994E+09 0.362228E+09 0.134804E+10 0.00 0.00 0.00 0.00 18550579.43 13539826.36
September 0.447140E+09 0.334436E+09 0.125111E+10 0.00 0.00 0.00 0.00 4985410.18 33104895.89
October 0.465148E+09 0.366052E+09 0.129650E+10 0.00 0.00 0.00 0.00 1150963.24 0.108483E+09
November 0.460569E+09 0.373042E+09 0.126781E+10 0.00 0.00 0.00 0.00 35335.27 0.154181E+09
December 0.448971E+09 0.372109E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.255969E+09
                   
Annual Sum or Average 0.557719E+10 0.423885E+10 0.154036E+11 0.00 0.00 0.00 0.00 67297871.86 0.145347E+10
Minimum of Months 0.421807E+09 0.320160E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 13539826.36
Maximum of Months 0.502994E+09 0.381029E+09 0.134804E+10 0.00 0.00 0.00 0.00 19069272.34 0.275244E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.586183E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.432864E+09
February 0.901968E+09 0.535489E+09 0.185364E+10 0.00 0.00 0.00 0.00 44394.72 0.370268E+09
March 0.107774E+10 0.594582E+09 0.212945E+10 0.00 0.00 0.00 0.00 755119.13 0.247774E+09
April 0.956342E+09 0.518447E+09 0.197725E+10 0.00 0.00 0.00 0.00 1930219.11 0.147508E+09
May 0.103597E+10 0.545918E+09 0.208851E+10 0.00 0.00 0.00 0.00 6354833.87 93636211.27
June 0.103308E+10 0.537539E+09 0.205070E+10 0.00 0.00 0.00 0.00 28096283.34 45593577.34
July 0.959235E+09 0.508832E+09 0.201460E+10 0.00 0.00 0.00 0.00 30235812.48 30486149.33
August 0.107774E+10 0.574765E+09 0.212945E+10 0.00 0.00 0.00 0.00 28457686.56 20010349.78
September 0.956342E+09 0.529756E+09 0.197632E+10 0.00 0.00 0.00 0.00 7183695.53 49925336.79
October 0.994195E+09 0.573049E+09 0.204803E+10 0.00 0.00 0.00 0.00 1142751.51 0.168659E+09
November 0.984487E+09 0.574028E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.243774E+09
December 0.959235E+09 0.569356E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.401279E+09
                   
Annual Sum or Average 0.119305E+11 0.664795E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.104201E+09 0.225178E+10
Minimum of Months 0.901968E+09 0.508832E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 20010349.78
Maximum of Months 0.107774E+10 0.594582E+09 0.212945E+10 0.00 0.00 0.00 0.00 30235812.48 0.432864E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.381857E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.275634E+09
February 0.570983E+09 0.348209E+09 0.117344E+10 0.00 0.00 0.00 0.00 198663.70 0.236437E+09
March 0.682256E+09 0.381215E+09 0.134804E+10 0.00 0.00 0.00 0.00 501688.61 0.162311E+09
April 0.605404E+09 0.328317E+09 0.125169E+10 0.00 0.00 0.00 0.00 1364851.37 99669906.52
May 0.655811E+09 0.345332E+09 0.132212E+10 0.00 0.00 0.00 0.00 3964008.55 64751771.28
June 0.653980E+09 0.339498E+09 0.129818E+10 0.00 0.00 0.00 0.00 17758182.36 32074925.21
July 0.607235E+09 0.321841E+09 0.127533E+10 0.00 0.00 0.00 0.00 19125576.51 21284994.67
August 0.682256E+09 0.364291E+09 0.134804E+10 0.00 0.00 0.00 0.00 18200015.20 14344927.79
September 0.605404E+09 0.338537E+09 0.125110E+10 0.00 0.00 0.00 0.00 5081050.97 33654458.89
October 0.629366E+09 0.374688E+09 0.129649E+10 0.00 0.00 0.00 0.00 1008226.38 0.108949E+09
November 0.623221E+09 0.370520E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.153942E+09
December 0.607235E+09 0.370857E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.255272E+09
                   
Annual Sum or Average 0.755252E+10 0.426516E+10 0.154035E+11 0.00 0.00 0.00 0.00 67202263.65 0.145833E+10
Minimum of Months 0.570983E+09 0.321841E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 14344927.79
Maximum of Months 0.682256E+09 0.381857E+09 0.134804E+10 0.00 0.00 0.00 0.00 19125576.51 0.275634E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.579287E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 172846.11 0.497144E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 685464.24 0.329763E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2148448.86 0.197942E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6625445.35 0.127423E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 31480760.13 60974303.96
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35490141.74 40337895.58
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32720633.41 25332257.67
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8059040.93 68884149.13
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1558327.89 0.230359E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42948.44 0.330575E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.553024E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118984E+09 0.304105E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25332257.67
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35490141.74 0.579287E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.699787E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 651718.24 0.602451E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1049262.44 0.405309E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3189564.97 0.248876E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9012760.99 0.161639E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40796458.60 77848670.55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45809958.50 51052049.18
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42304271.34 32009329.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11244540.46 83731582.47
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2593341.91 0.275769E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 533005.40 0.391211E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.655877E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157185E+09 0.368556E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32009329.56
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45809958.50 0.699787E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.689671E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 248.37 0.595820E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 405222.89 0.405989E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 898135.06 0.254895E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4659610.99 0.166075E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33233844.73 75617088.44
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37720472.19 51028635.84
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36350123.65 30128517.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7755036.27 80653431.44
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 944128.53 0.270375E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122131.16 0.377473E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.628859E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122089E+09 0.362658E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30128517.56
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37720472.19 0.689671E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 950.03 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 905.40 07-JAN-18:05
February 1306.65 01-FEB-10:09 1011.44 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 62.52 26-FEB-13:20 1089.30 12-FEB-01:00
March 1306.65 01-MAR-10:09 957.97 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 30.65 11-MAR-16:00 648.74 22-MAR-03:00
April 1306.65 03-APR-09:09 865.53 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 55.93 16-APR-11:57 364.85 05-APR-05:00
May 1306.65 01-MAY-09:09 570.89 24-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 56.54 07-MAY-12:20 285.04 10-MAY-04:00
June 1306.65 01-JUN-09:09 562.52 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 175.42 11-JUN-15:00 211.31 07-JUN-03:00
July 1306.65 03-JUL-09:09 675.59 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 157.13 08-JUL-18:53 152.68 28-JUL-22:00
August 1306.65 01-AUG-09:09 823.21 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 175.20 06-AUG-14:08 98.05 23-AUG-05:00
September 1306.65 01-SEP-09:09 904.88 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 65.18 17-SEP-15:00 189.48 29-SEP-05:00
October 1306.65 02-OCT-09:09 1038.01 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 74.99 08-OCT-14:00 383.22 28-OCT-04:00
November 1306.65 01-NOV-09:09 1025.00 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 52.76 19-NOV-15:00 624.60 30-NOV-22:03
December 1306.65 01-DEC-10:09 952.56 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 943.48 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   562.52   1435.25   0.00 0.00 0.00 0.00 0.00   98.05  
Maximum of Months 1306.65   1038.01   1435.25   0.00 0.00 0.00 0.00 175.42   1089.30  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 588.12 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 601.90 07-JAN-18:05
February 827.22 01-FEB-10:09 640.12 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 17.12 26-FEB-15:30 726.19 12-FEB-01:00
March 827.22 01-MAR-10:09 599.64 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 17.64 30-MAR-16:00 429.42 22-MAR-03:00
April 827.22 03-APR-09:09 523.41 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 17.66 16-APR-13:53 242.79 05-APR-05:00
May 827.22 01-MAY-09:09 338.93 02-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 29.05 29-MAY-17:50 189.60 10-MAY-04:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 107.01 25-JUN-16:15 141.44 07-JUN-03:00
July 827.22 03-JUL-09:09 362.00 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 102.94 08-JUL-19:10 102.42 01-JUL-20:00
August 827.22 01-AUG-09:09 493.31 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 120.02 06-AUG-14:08 65.50 23-AUG-05:00
September 827.22 01-SEP-09:09 555.99 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 37.09 17-SEP-15:00 125.61 29-SEP-05:00
October 827.22 02-OCT-09:09 657.13 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 32.12 09-OCT-16:00 255.50 28-OCT-04:00
November 827.22 01-NOV-09:09 643.36 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 31.68 19-NOV-15:00 415.92 30-NOV-22:03
December 827.22 01-DEC-10:09 589.92 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 627.56 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   65.50  
Maximum of Months 827.22   657.13   908.57   0.00 0.00 0.00 0.00 120.02   726.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 936.67 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 916.16 07-JAN-18:05
February 1306.65 01-FEB-10:09 1011.44 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 10.16 28-FEB-15:00 1115.55 11-FEB-18:05
March 1306.65 01-MAR-10:09 956.57 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 26.46 30-MAR-16:00 652.24 22-MAR-03:00
April 1306.65 03-APR-09:09 869.03 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 21.93 16-APR-13:53 365.77 05-APR-05:00
May 1306.65 01-MAY-09:09 582.39 24-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 43.63 29-MAY-17:50 286.40 10-MAY-04:00
June 1306.65 01-JUN-09:09 573.92 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 161.33 11-JUN-15:00 211.72 07-JUN-03:00
July 1306.65 03-JUL-09:09 717.72 27-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 154.50 08-JUL-18:53 152.96 28-JUL-22:00
August 1306.65 01-AUG-09:09 833.11 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 157.88 06-AUG-14:08 98.77 23-AUG-05:00
September 1306.65 01-SEP-09:09 896.92 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 47.01 17-SEP-15:20 190.14 29-SEP-05:00
October 1306.65 02-OCT-09:09 1038.01 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 23.14 09-OCT-15:57 395.99 28-OCT-04:00
November 1306.65 01-NOV-09:09 1019.62 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 624.81 30-NOV-22:03
December 1306.65 01-DEC-10:09 937.96 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 960.40 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   573.92   1435.24   0.00 0.00 0.00 0.00 0.00   98.77  
Maximum of Months 1306.65   1038.01   1435.24   0.00 0.00 0.00 0.00 161.33   1115.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 603.40 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 608.04 07-JAN-18:05
February 827.17 01-FEB-10:09 640.07 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 37.77 26-FEB-12:53 768.64 11-FEB-18:05
March 827.17 01-MAR-10:09 609.51 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 17.64 30-MAR-16:00 431.99 22-MAR-03:00
April 827.17 03-APR-09:09 562.94 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 35.62 16-APR-11:53 241.65 05-APR-05:00
May 827.17 01-MAY-09:09 498.57 24-MAY-07:30 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 36.65 07-MAY-12:20 192.88 10-MAY-04:00
June 827.17 01-JUN-09:09 369.02 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 104.31 25-JUN-15:53 143.12 07-JUN-03:00
July 827.17 03-JUL-09:09 478.36 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 105.14 08-JUL-19:10 103.00 28-JUL-22:00
August 827.17 01-AUG-09:09 539.86 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 116.49 06-AUG-14:08 66.54 25-AUG-05:00
September 827.17 01-SEP-09:09 578.82 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 37.60 24-SEP-12:43 125.50 29-SEP-05:00
October 827.17 02-OCT-09:09 657.08 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 28.30 08-OCT-13:43 257.69 28-OCT-04:00
November 827.17 01-NOV-09:09 649.87 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 416.20 30-NOV-22:03
December 827.17 01-DEC-10:09 604.32 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 626.23 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   369.02   908.57   0.00 0.00 0.00 0.00 0.00   66.54  
Maximum of Months 827.17   657.08   908.57   0.00 0.00 0.00 0.00 116.49   768.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 946.55 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 502.31 07-JAN-18:10
February 1306.65 01-FEB-10:09 1010.34 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 33.76 26-FEB-13:20 611.18 12-FEB-01:00
March 1306.65 01-MAR-10:09 954.78 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 24.02 11-MAR-18:05 367.96 22-MAR-03:00
April 1306.65 03-APR-09:09 858.68 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 36.72 08-APR-17:03 191.79 05-APR-05:00
May 1306.65 01-MAY-09:09 567.41 24-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 41.84 07-MAY-11:53 159.35 10-MAY-04:00
June 1306.65 01-JUN-09:09 558.63 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 109.94 11-JUN-15:00 113.50 07-JUN-03:00
July 1306.65 03-JUL-09:09 584.57 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 98.90 08-JUL-18:53 83.81 28-JUL-22:00
August 1306.65 01-AUG-09:09 814.71 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 103.51 06-AUG-14:00 55.66 25-AUG-05:00
September 1306.65 01-SEP-09:09 899.62 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 40.98 17-SEP-15:00 116.74 29-SEP-05:00
October 1306.65 02-OCT-09:09 1037.91 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 39.95 08-OCT-14:00 233.63 28-OCT-04:00
November 1306.65 01-NOV-09:09 1024.39 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 8.00 19-NOV-15:00 346.83 07-NOV-02:00
December 1306.65 01-DEC-10:09 949.19 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 590.17 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   558.63   1435.25   0.00 0.00 0.00 0.00 0.00   55.66  
Maximum of Months 1306.65   1037.91   1435.25   0.00 0.00 0.00 0.00 109.94   611.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 585.72 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 334.32 07-JAN-18:10
February 827.22 01-FEB-10:09 639.54 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 10.76 26-FEB-16:10 406.69 12-FEB-01:00
March 827.22 01-MAR-10:09 597.68 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 11.57 11-MAR-16:00 249.78 22-MAR-03:00
April 827.22 03-APR-09:09 518.60 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 15.22 08-APR-17:03 127.94 05-APR-05:00
May 827.22 01-MAY-09:09 335.77 02-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 20.41 29-MAY-18:00 108.50 10-MAY-04:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 61.12 11-JUN-15:00 78.21 07-JUN-03:00
July 827.22 03-JUL-09:09 359.95 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 61.12 08-JUL-18:53 55.58 28-JUL-22:00
August 827.22 01-AUG-09:09 487.68 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 68.11 06-AUG-13:58 37.10 25-AUG-05:00
September 827.22 01-SEP-09:09 552.53 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 23.87 17-SEP-15:00 77.67 29-SEP-05:00
October 827.22 02-OCT-09:09 657.08 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 16.00 09-OCT-16:00 159.86 28-OCT-04:00
November 827.22 01-NOV-09:09 642.79 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 1.42 05-NOV-16:00 236.18 07-NOV-02:00
December 827.22 01-DEC-10:09 587.60 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 395.77 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   37.10  
Maximum of Months 827.22   657.08   908.57   0.00 0.00 0.00 0.00 68.11   406.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 932.51 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 23077.89 27-JAN-07:01
February 1306.65 01-FEB-10:09 1010.34 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 108.19 28-FEB-15:00 25029.78 03-FEB-07:01
March 1306.65 01-MAR-10:09 953.32 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 2811.36 30-MAR-16:10 14368.43 06-MAR-07:03
April 1306.65 03-APR-09:09 862.34 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 3713.84 17-APR-16:10 15674.95 06-APR-06:02
May 1306.65 01-MAY-09:09 579.67 24-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 5093.93 19-MAY-16:10 10416.38 11-MAY-06:05
June 1306.65 01-JUN-09:09 570.78 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 7129.21 06-JUN-16:05 7562.93 08-JUN-06:03
July 1306.65 03-JUL-09:09 705.22 27-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 8345.39 07-JUL-16:03 3687.59 03-JUL-06:03
August 1306.65 01-AUG-09:09 825.09 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 7980.75 01-AUG-16:03 3783.04 25-AUG-06:03
September 1306.65 01-SEP-09:09 891.27 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 5344.99 07-SEP-16:03 8138.81 14-SEP-06:02
October 1306.65 02-OCT-09:09 1037.91 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 3829.09 10-OCT-16:05 14932.95 26-OCT-06:03
November 1306.65 01-NOV-09:09 1018.74 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 19623.29 22-NOV-07:01
December 1306.65 01-DEC-10:09 933.85 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 21581.31 18-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   570.78   1435.24   0.00 0.00 0.00 0.00 0.00   3687.59  
Maximum of Months 1306.65   1037.91   1435.24   0.00 0.00 0.00 0.00 8345.39   25029.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 601.69 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 336.55 07-JAN-18:10
February 827.17 01-FEB-10:09 639.50 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 17.75 26-FEB-13:20 417.36 11-FEB-18:05
March 827.17 01-MAR-10:09 608.00 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 9.51 30-MAR-16:00 251.10 22-MAR-03:00
April 827.17 03-APR-09:09 560.01 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 16.75 16-APR-11:33 127.87 05-APR-05:00
May 827.17 01-MAY-09:09 493.97 24-MAY-07:30 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 24.71 07-MAY-11:53 110.46 10-MAY-04:00
June 827.17 01-JUN-09:09 367.49 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 57.54 25-JUN-15:55 79.27 07-JUN-03:00
July 827.17 03-JUL-09:09 472.85 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 55.85 08-JUL-18:53 56.52 28-JUL-22:00
August 827.17 01-AUG-09:09 536.22 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 65.93 06-AUG-13:58 38.78 25-AUG-05:00
September 827.17 01-SEP-09:09 576.37 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 20.70 24-SEP-12:50 77.71 29-SEP-05:00
October 827.17 02-OCT-09:09 657.03 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 14.60 08-OCT-13:53 160.83 28-OCT-04:00
November 827.17 01-NOV-09:09 649.60 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 239.27 07-NOV-02:00
December 827.17 01-DEC-10:09 602.64 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 393.55 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   367.49   908.57   0.00 0.00 0.00 0.00 0.00   38.78  
Maximum of Months 827.17   657.03   908.57   0.00 0.00 0.00 0.00 65.93   417.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 950.03 03-JAN-08:09 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 778.09 07-JAN-18:05
February 1306.65 01-FEB-10:09 1011.44 01-FEB-08:09 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 43.38 26-FEB-13:00 927.28 12-FEB-01:00
March 1306.65 01-MAR-10:09 957.96 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 26.04 11-MAR-16:00 591.24 22-MAR-03:00
April 1306.65 03-APR-09:09 865.52 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 44.03 16-APR-11:53 320.37 05-APR-05:00
May 1306.65 01-MAY-09:09 570.88 24-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 56.13 07-MAY-12:10 254.80 10-MAY-04:00
June 1306.65 01-JUN-09:09 562.51 23-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 157.66 11-JUN-14:53 182.19 07-JUN-03:00
July 1306.65 03-JUL-09:09 675.55 27-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 145.07 08-JUL-18:53 131.84 28-JUL-22:00
August 1306.65 01-AUG-09:09 823.19 24-AUG-07:10 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 156.38 06-AUG-14:00 87.32 25-AUG-05:00
September 1306.65 01-SEP-09:09 904.86 29-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 61.51 17-SEP-15:00 173.95 29-SEP-05:00
October 1306.65 02-OCT-09:09 1038.01 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 62.09 08-OCT-14:00 350.74 28-OCT-04:00
November 1306.65 01-NOV-09:09 1025.00 01-NOV-07:10 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 21.42 19-NOV-15:00 524.48 30-NOV-22:03
December 1306.65 01-DEC-10:09 952.55 06-DEC-08:09 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 871.19 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   562.51   1435.25   0.00 0.00 0.00 0.00 0.00   87.32  
Maximum of Months 1306.65   1038.01   1435.25   0.00 0.00 0.00 0.00 157.66   927.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 588.11 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 516.50 07-JAN-18:05
February 805.43 01-FEB-08:09 640.11 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 14.52 26-FEB-15:30 617.38 11-FEB-19:00
March 805.43 01-MAR-08:09 599.63 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 14.78 30-MAR-16:00 392.00 22-MAR-03:00
April 805.43 03-APR-07:10 523.40 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 17.04 08-APR-17:03 213.31 05-APR-05:00
May 805.43 01-MAY-07:10 338.92 02-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 26.28 29-MAY-18:00 169.54 10-MAY-04:00
June 805.43 01-JUN-07:10 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 89.59 11-JUN-15:10 122.03 07-JUN-03:00
July 805.43 03-JUL-07:10 362.00 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 92.50 08-JUL-18:53 87.45 28-JUL-22:00
August 805.43 01-AUG-07:10 493.30 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 106.07 06-AUG-13:58 57.79 25-AUG-05:00
September 805.43 01-SEP-07:10 555.98 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 35.84 17-SEP-15:00 115.40 29-SEP-05:00
October 805.43 02-OCT-07:10 657.13 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 28.05 09-OCT-16:00 233.88 28-OCT-04:00
November 805.43 01-NOV-07:10 643.36 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 11.34 19-NOV-15:00 349.32 30-NOV-22:03
December 805.43 01-DEC-08:09 589.92 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 579.88 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   314.23   908.57   0.00 0.00 0.00 0.00 0.00   57.79  
Maximum of Months 805.43   657.13   908.57   0.00 0.00 0.00 0.00 106.07   617.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 936.66 03-JAN-08:09 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 786.60 07-JAN-18:05
February 1306.65 01-FEB-10:09 1011.44 01-FEB-08:09 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 8.69 28-FEB-15:00 960.64 11-FEB-19:00
March 1306.65 01-MAR-10:09 956.57 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 22.18 30-MAR-16:00 594.40 22-MAR-03:00
April 1306.65 03-APR-09:09 869.01 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 20.26 16-APR-14:10 321.20 05-APR-05:00
May 1306.65 01-MAY-09:09 582.38 24-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 43.75 07-MAY-12:10 255.95 10-MAY-04:00
June 1306.65 01-JUN-09:09 573.91 23-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 145.17 11-JUN-15:10 182.52 07-JUN-03:00
July 1306.65 03-JUL-09:09 717.69 27-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 142.79 08-JUL-18:53 132.07 28-JUL-22:00
August 1306.65 01-AUG-09:09 833.09 24-AUG-07:10 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 146.96 06-AUG-13:58 87.79 25-AUG-05:00
September 1306.65 01-SEP-09:09 896.91 29-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 38.72 17-SEP-15:20 174.49 29-SEP-05:00
October 1306.65 02-OCT-09:09 1038.01 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 17.83 09-OCT-15:38 360.37 28-OCT-04:00
November 1306.65 01-NOV-09:09 1019.62 01-NOV-07:10 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 538.91 07-NOV-02:00
December 1306.65 01-DEC-10:09 937.95 06-DEC-08:09 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 886.52 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   573.91   1435.24   0.00 0.00 0.00 0.00 0.00   87.79  
Maximum of Months 1306.65   1038.01   1435.24   0.00 0.00 0.00 0.00 146.96   960.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 603.39 03-JAN-08:09 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 521.98 07-JAN-18:05
February 827.17 01-FEB-10:09 640.07 01-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 25.94 26-FEB-13:00 656.59 11-FEB-18:05
March 827.17 01-MAR-10:09 609.50 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 14.78 30-MAR-16:00 393.73 22-MAR-03:00
April 827.17 03-APR-09:09 562.93 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 27.62 16-APR-12:10 212.34 05-APR-05:00
May 827.17 01-MAY-09:09 498.55 24-MAY-07:30 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 36.32 07-MAY-12:10 172.21 10-MAY-04:00
June 827.17 01-JUN-09:09 369.01 23-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 87.17 25-JUN-15:53 123.34 07-JUN-03:00
July 827.17 03-JUL-09:09 478.34 27-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 85.98 08-JUL-19:10 88.79 28-JUL-22:00
August 827.17 01-AUG-09:09 539.84 24-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 103.40 06-AUG-13:58 59.21 25-AUG-05:00
September 827.17 01-SEP-09:09 578.82 29-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 34.08 24-SEP-12:50 115.19 29-SEP-05:00
October 827.17 02-OCT-09:09 657.08 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 22.03 08-OCT-13:43 235.27 28-OCT-04:00
November 827.17 01-NOV-09:09 649.87 01-NOV-07:10 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 349.95 07-NOV-02:00
December 827.17 01-DEC-10:09 604.32 06-DEC-08:09 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 578.07 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   369.01   908.57   0.00 0.00 0.00 0.00 0.00   59.21  
Maximum of Months 827.17   657.08   908.57   0.00 0.00 0.00 0.00 103.40   656.59  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1100.51 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.84 26-FEB-14:53 1352.33 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.46 30-MAR-16:00 855.61 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39.39 16-APR-11:53 442.48 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.83 07-MAY-11:53 358.98 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 192.38 11-JUN-15:00 246.96 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 179.28 08-JUL-18:53 176.08 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 189.96 06-AUG-14:00 119.29 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.16 17-SEP-15:00 249.40 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.99 09-OCT-16:00 512.82 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.25 19-NOV-15:00 756.00 07-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1294.39 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   119.29  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 192.38   1352.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1363.16 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.78 26-FEB-15:02 1672.95 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.35 11-MAR-16:00 1051.26 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.56 16-APR-11:53 562.72 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.41 07-MAY-12:10 455.95 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 259.71 11-JUN-14:53 315.41 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 231.99 08-JUL-18:53 222.71 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 248.10 06-AUG-14:00 150.18 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.81 17-SEP-15:00 308.92 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.85 08-OCT-13:53 617.50 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.21 19-NOV-15:00 929.62 07-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1554.73 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   150.18  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 259.71   1672.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 1451.37 07-JAN-18:05
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.65 26-FEB-14:53 1726.62 11-FEB-18:05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.65 30-MAR-16:00 980.49 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.43 16-APR-13:57 542.42 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.83 19-MAY-13:00 412.86 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 176.27 11-JUN-15:00 311.45 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.84 08-JUL-18:50 242.39 01-JUL-20:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 170.68 06-AUG-13:53 145.11 23-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.04 06-SEP-12:00 269.10 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.42 09-OCT-15:40 576.80 28-OCT-04:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.45 19-NOV-15:00 908.27 30-NOV-22:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1430.00 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   145.11  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.84   1726.62  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 12542.98 31-JAN-17:00 6035.01 4936.01 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
February 17952.27 28-FEB-17:00 6035.01 4936.01 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
March 28151.29 31-MAR-06:03 3811.58 4936.08 30584.54 0.00 0.00 0.00 0.00 0.00 0.00
April 33395.93 17-APR-06:03 5082.11 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
May 37721.18 30-MAY-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
June 37805.49 19-JUN-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
July 38064.75 15-JUL-04:03 0.00 846.94 20126.17 0.00 0.00 0.00 0.00 0.00 0.00
August 38200.51 09-AUG-04:03 0.00 846.94 22568.22 0.00 0.00 0.00 0.00 0.00 0.00
September 37756.04 18-SEP-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
October 36589.07 10-OCT-05:12 2541.06 2193.73 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
November 31901.86 06-NOV-07:03 5082.11 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
December 16567.75 14-DEC-17:00 6035.01 4936.01 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 12542.98   0.00 846.94 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38200.51   6035.01 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1033.53 31-JAN-17:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.21
February 3290.86 28-FEB-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.64
March 6806.97 30-MAR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.44 0.00
April 7768.15 17-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.61 0.00
May 8547.19 30-MAY-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.11 0.00
June 9146.73 12-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.42 0.00
July 10057.66 07-JUL-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.81 0.00
August 10219.41 01-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.37 0.00
September 8776.24 06-SEP-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.66 0.00
October 6897.17 10-OCT-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.15 0.00
November 2855.23 06-NOV-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 60.74
December 1712.64 10-DEC-14:23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.43
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1033.53   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10219.41   0.00 0.00 0.00 0.00 0.00 0.00 0.00 48.42 76.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1949.63 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199.73
February 1985.06 24-FEB-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.52
March 2352.71 30-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.98 0.00
April 2986.21 06-APR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.82
May 3755.48 30-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.94 0.00
June 4041.07 26-JUN-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.69
July 4370.63 10-JUL-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.58 0.00
August 4265.27 07-AUG-12:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24.63 0.00
September 3840.87 11-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.72 0.00
October 2790.32 11-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.46 0.00
November 1759.20 18-NOV-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 121.92
December 1944.54 15-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 178.82
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1759.20   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4370.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.58 199.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1791.57 21-JAN-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.43
February 2307.85 24-FEB-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 92.44
March 2450.18 30-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.46 0.00
April 3214.88 06-APR-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 103.98
May 4011.85 30-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.12 0.00
June 4220.97 26-JUN-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28.92 0.00
July 4669.52 10-JUL-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.07 0.00
August 4612.76 07-AUG-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.28 0.00
September 4521.33 11-SEP-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.74 0.00
October 3506.43 10-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.48 0.00
November 2178.47 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 145.81
December 1800.91 08-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 95.29
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1791.57   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4669.52   0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.07 145.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7765.50 31-JAN-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 10965.02 28-FEB-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 13777.98 30-MAR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14688.56 17-APR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 29154.65 30-MAY-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
June 29085.38 19-JUN-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 29327.65 07-JUL-04:03 0.00 846.94 9768.22 0.00 0.00 0.00 0.00 0.00 0.00
August 28982.82 22-AUG-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 29082.00 11-SEP-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 15163.47 11-OCT-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 11995.09 06-NOV-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 9045.35 13-DEC-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7765.50   0.00 846.94 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 29327.65   6035.01 4936.01 15129.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 7649.93 20-JAN-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 10972.83 28-FEB-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 15787.35 30-MAR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 16925.89 17-APR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 20401.62 30-MAY-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
June 31345.86 19-JUN-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 31461.58 24-JUL-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 31289.08 28-AUG-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 31101.72 05-SEP-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 16098.66 11-OCT-15:50 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 10804.65 06-NOV-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 8356.46 13-DEC-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7649.93   3176.32 2742.16 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31461.58   6035.01 4936.01 15129.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1585.46 31-JAN-16:40 1272.23 558.15 1435.25 0.00 0.00 0.00 0.00 0.00 15.17
February 2741.49 28-FEB-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.90 0.00
March 4704.34 30-MAR-15:50 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 26.15 0.00
April 5036.87 19-APR-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 12.38 0.00
May 6495.41 30-MAY-15:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 22.94 0.00
June 11151.98 25-JUN-18:12 0.00 137.87 1930.52 0.00 0.00 0.00 0.00 53.11 0.00
July 11229.11 16-JUL-13:02 267.84 110.30 1913.66 0.00 0.00 0.00 0.00 99.03 0.00
August 10825.42 06-AUG-18:02 0.00 137.87 1930.52 0.00 0.00 0.00 0.00 81.47 0.00
September 6252.20 06-SEP-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 23.19 0.00
October 4476.53 02-OCT-14:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 14.31 0.00
November 2139.50 02-NOV-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 7.64
December 1712.18 13-DEC-15:00 1306.65 563.80 1435.25 0.00 0.00 0.00 0.00 0.00 16.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1585.46   0.00 110.30 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11229.11   1306.65 563.80 1930.52 0.00 0.00 0.00 0.00 99.03 16.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1034.84 31-JAN-15:00 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 7.81
February 2368.19 27-FEB-10:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 27.00
March 3804.27 30-MAR-11:00 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 7.04
April 7500.16 16-APR-09:43 127.17 52.37 908.57 0.00 0.00 0.00 0.00 0.00 35.79
May 11230.39 07-MAY-09:53 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 27.89
June 11840.27 04-JUN-09:32 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 10.48
July 11302.92 09-JUL-08:23 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 43.50
August 11867.92 27-AUG-09:22 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 3.40
September 11229.76 04-SEP-09:32 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 5.92
October 4574.16 11-OCT-10:20 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 1.19
November 2119.79 06-NOV-10:20 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 38.85
December 1105.56 13-DEC-13:30 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 12.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1034.84   127.17 52.37 908.57 0.00 0.00 0.00 0.00 0.00 1.19
Maximum of Months 11867.92   827.22 314.23 1514.29 0.00 0.00 0.00 0.00 0.00 43.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4618.09 11-JAN-14:30 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 38.81
February 13359.10 26-FEB-15:02 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 36.89
March 9650.27 30-MAR-13:40 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 18.93 0.00
April 11402.83 16-APR-14:23 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 11.11 0.00
May 9626.37 29-MAY-13:43 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 13.47 0.00
June 12940.67 25-JUN-14:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 68.12 0.00
July 13099.18 09-JUL-13:02 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 71.08 0.00
August 13539.67 27-AUG-13:23 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 82.41 0.00
September 13805.46 24-SEP-13:43 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 14.85 0.00
October 13794.59 09-OCT-13:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 14.70
November 13616.44 11-NOV-14:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 124.14
December 6397.28 08-DEC-14:10 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 97.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4618.09   200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13805.46   1306.65 496.34 1913.65 0.00 0.00 0.00 0.00 82.41 124.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1117.83 20-JAN-16:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 24.43
February 4429.21 27-FEB-17:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 2.60
March 6427.28 30-MAR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 17.64 0.00
April 12029.44 09-APR-17:42 0.00 69.82 977.67 0.00 0.00 0.00 0.00 0.00 30.87
May 12810.52 21-MAY-16:42 211.94 87.28 1514.28 0.00 0.00 0.00 0.00 0.00 16.24
June 12459.78 25-JUN-16:12 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 87.97 0.00
July 12865.24 30-JUL-17:22 0.00 87.28 1222.09 0.00 0.00 0.00 0.00 25.72 0.00
August 12784.04 13-AUG-17:02 0.00 104.73 1466.51 0.00 0.00 0.00 0.00 31.51 0.00
September 11288.25 04-SEP-17:03 0.00 69.82 977.67 0.00 0.00 0.00 0.00 6.62 0.00
October 11193.70 09-OCT-16:33 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 1.64 0.00
November 4106.00 06-NOV-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 18.87
December 1692.97 11-DEC-15:50 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 8.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1117.83   0.00 69.82 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12865.24   805.38 314.21 1817.13 0.00 0.00 0.00 0.00 87.97 30.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1519.89 31-JAN-16:30 1272.23 542.94 1435.25 0.00 0.00 0.00 0.00 0.00 7.45
February 1740.90 28-FEB-15:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.38 0.00
March 2777.02 30-MAR-16:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 14.26 0.00
April 3038.01 19-APR-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 6.75 0.00
May 4601.99 30-MAY-15:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 12.29 0.00
June 5373.73 26-JUN-06:03 803.52 886.59 1913.66 0.00 0.00 0.00 0.00 0.00 1.36
July 6795.21 17-JUL-06:03 803.52 547.88 1913.66 0.00 0.00 0.00 0.00 0.00 1.90
August 6610.68 07-AUG-06:03 803.52 996.42 1913.66 0.00 0.00 0.00 0.00 0.00 1.40
September 5570.78 06-SEP-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 12.43 0.00
October 4137.44 02-OCT-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 7.26 0.00
November 2182.27 03-NOV-14:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 3.82
December 1710.59 13-DEC-13:30 1272.23 538.55 1435.25 0.00 0.00 0.00 0.00 0.00 9.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1519.89   803.52 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6795.21   1306.65 996.42 1913.66 0.00 0.00 0.00 0.00 14.26 9.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1016.36 31-JAN-14:50 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 3.72
February 2124.08 27-FEB-10:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 14.28
March 2765.75 14-MAR-09:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 11.08
April 4392.63 17-APR-10:10 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 1.00
May 5429.81 30-MAY-10:00 827.22 314.23 908.57 0.00 0.00 0.00 0.00 4.11 0.00
June 9796.58 04-JUN-09:32 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 3.98
July 9805.12 04-JUL-09:52 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 0.22
August 9840.91 06-AUG-09:52 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 7.55 0.00
September 9369.92 24-SEP-10:02 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 1.78
October 4638.36 10-OCT-10:20 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.31 0.00
November 2704.54 06-NOV-10:10 1654.44 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 20.29
December 1121.75 13-DEC-12:00 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 5.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1016.36   169.56 69.83 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9840.91   1654.44 628.45 1817.15 0.00 0.00 0.00 0.00 7.55 20.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2881.96 28-JAN-14:40 137.54 82.72 558.15 0.00 0.00 0.00 0.00 0.00 16.83
February 10719.75 26-FEB-15:02 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 17.67
March 7795.91 30-MAR-16:10 401.76 275.75 797.35 0.00 0.00 0.00 0.00 2811.36 0.00
April 7858.30 17-APR-16:10 401.76 275.75 797.35 0.00 0.00 0.00 0.00 3713.84 0.00
May 8761.14 30-MAY-12:00 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 4101.66 0.00
June 9446.26 06-JUN-16:30 401.76 275.75 797.35 0.00 0.00 0.00 0.00 6719.02 0.00
July 9852.44 07-JUL-16:50 401.76 275.75 797.35 0.00 0.00 0.00 0.00 7273.21 0.00
August 10810.17 06-AUG-13:53 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 86.60 0.00
September 11114.97 24-SEP-13:23 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 11.28 0.00
October 11360.93 09-OCT-14:53 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 1.40 0.00
November 10851.83 12-NOV-13:33 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 47.47
December 6665.97 10-DEC-14:33 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 47.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2881.96   137.54 82.72 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11360.93   687.71 496.34 1913.65 0.00 0.00 0.00 0.00 7273.21 47.47



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1063.90 23-JAN-17:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 25.79
February 3253.24 27-FEB-17:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 1.34
March 4400.69 30-MAR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 9.51 0.00
April 4933.52 17-APR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 3.57 0.00
May 9814.88 29-MAY-17:32 0.00 87.28 1222.09 0.00 0.00 0.00 0.00 12.65 0.00
June 10178.41 11-JUN-16:52 211.94 87.28 1514.28 0.00 0.00 0.00 0.00 27.19 0.00
July 10450.44 04-JUL-17:52 0.00 104.73 1466.51 0.00 0.00 0.00 0.00 16.33 0.00
August 10261.42 13-AUG-16:51 339.11 139.64 2422.85 0.00 0.00 0.00 0.00 17.96 0.00
September 9659.52 04-SEP-16:53 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 4.34 0.00
October 8423.53 09-OCT-15:32 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 6.33 0.00
November 4075.96 06-NOV-16:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 12.02
December 1674.04 11-DEC-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 4.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1063.90   0.00 69.82 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10450.44   805.38 314.21 2422.85 0.00 0.00 0.00 0.00 27.19 25.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1603.47 31-JAN-16:40 1272.23 558.14 1435.25 0.00 0.00 0.00 0.00 0.00 13.00
February 2754.46 28-FEB-15:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 8.69 0.00
March 4188.01 30-MAR-15:50 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 21.92 0.00
April 4588.04 18-APR-14:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 3.91 0.00
May 5885.79 30-MAY-15:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 19.17 0.00
June 7223.07 26-JUN-06:03 803.52 892.49 1913.66 0.00 0.00 0.00 0.00 0.00 2.80
July 9490.82 16-JUL-13:02 267.84 110.30 1913.66 0.00 0.00 0.00 0.00 86.38 0.00
August 7665.52 14-AUG-04:02 0.00 223.18 2574.02 0.00 0.00 0.00 0.00 0.00 17.07
September 5692.11 06-SEP-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 19.39 0.00
October 4200.87 02-OCT-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 11.26 0.00
November 2303.64 03-NOV-14:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 6.05
December 1751.04 13-DEC-13:30 1272.23 542.86 1435.25 0.00 0.00 0.00 0.00 0.00 15.21
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1603.47   0.00 110.30 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9490.82   1306.65 892.49 2574.02 0.00 0.00 0.00 0.00 86.38 17.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1153.24 31-JAN-15:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 10.28
February 4439.17 23-FEB-13:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 62.32
March 5452.84 15-MAR-12:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 12.77
April 7112.49 17-APR-10:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 1.79
May 11098.79 07-MAY-09:02 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 36.40
June 11372.45 04-JUN-09:22 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 10.43
July 11638.71 09-JUL-10:12 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 5.68 0.00
August 11389.29 27-AUG-10:22 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 3.57 0.00
September 10719.74 04-SEP-09:53 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 1.29
October 6006.36 10-OCT-10:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 0.71
November 4002.33 28-NOV-13:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 25.78
December 3026.34 14-DEC-13:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 16.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1153.24   169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11638.71   4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 5.68 62.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4975.37 27-JAN-14:30 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 57.76
February 11197.22 26-FEB-13:13 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 56.37
March 9054.72 30-MAR-13:40 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 15.88 0.00
April 10131.52 16-APR-13:23 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 12.09 0.00
May 7109.09 30-MAY-14:00 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 21.83 0.00
June 9646.92 25-JUN-14:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 58.94 0.00
July 11270.98 16-JUL-13:02 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 86.57 0.00
August 11754.95 06-AUG-13:53 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 130.75 0.00
September 12106.46 24-SEP-13:23 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 16.23 0.00
October 12215.17 09-OCT-12:53 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 18.84
November 12246.65 11-NOV-13:43 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 112.69
December 6942.27 08-DEC-13:50 1272.23 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 80.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4975.37   200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12246.65   1306.65 496.34 1913.65 0.00 0.00 0.00 0.00 130.75 112.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1122.57 20-JAN-16:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 20.41
February 4330.02 27-FEB-17:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 2.13
March 6005.60 30-MAR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 14.78 0.00
April 11035.95 09-APR-16:23 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 0.00 17.40
May 11412.77 29-MAY-17:32 0.00 87.28 1222.09 0.00 0.00 0.00 0.00 15.99 0.00
June 11741.06 11-JUN-17:02 0.00 87.28 1222.09 0.00 0.00 0.00 0.00 38.42 0.00
July 11907.59 02-JUL-17:42 0.00 104.73 1466.51 0.00 0.00 0.00 0.00 18.12 0.00
August 11682.83 13-AUG-16:51 339.11 139.64 2422.85 0.00 0.00 0.00 0.00 25.62 0.00
September 11098.46 04-SEP-16:53 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 6.37 0.00
October 9576.30 09-OCT-15:32 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 9.42 0.00
November 4237.85 06-NOV-15:50 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 15.60
December 1918.65 11-DEC-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 6.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1122.57   0.00 69.82 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11907.59   805.38 314.21 2422.85 0.00 0.00 0.00 0.00 38.42 20.41



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [] NATURALGAS:FACILITY []
January 0.150365E+12 234037.50 09-JAN-07:10 0.00 0.00
February 0.117999E+12 237229.50 13-FEB-07:10 0.00 0.00
March 0.112079E+12 110404.42 30-MAR-15:20 0.00 0.00
April 0.109335E+12 112870.88 17-APR-15:30 0.00 0.00
May 0.128967E+12 129426.11 30-MAY-15:09 0.00 0.00
June 0.146849E+12 137261.75 19-JUN-15:00 0.00 0.00
July 0.153258E+12 149581.71 07-JUL-15:00 0.00 0.00
August 0.166462E+12 148578.61 01-AUG-15:30 0.00 0.00
September 0.130888E+12 141017.96 07-SEP-15:00 0.00 0.00
October 0.113305E+12 123266.68 10-OCT-15:30 0.00 0.00
November 0.106273E+12 150378.83 22-NOV-07:10 0.00 0.00
December 0.117149E+12 198960.67 18-DEC-07:10 0.00 0.00
           
Annual Sum or Average 0.155293E+13     0.00 0.00
Minimum of Months 0.106273E+12 110404.42   0.00 0.00
Maximum of Months 0.166462E+12 237229.50   0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.198175E+11 0.544208E+10 0.605851E+11 0.225727E+10 0.323044E+10 12379742.02 0.531890E+11 0.121675E+10 0.00 0.00 0.00 0.461464E+10 0.00
February 0.179794E+11 0.447543E+10 0.548702E+11 0.204819E+10 0.306782E+10 11196021.66 0.281621E+11 0.318758E+10 0.00 0.00 0.00 0.419681E+10 0.00
March 0.208723E+11 0.443078E+10 0.627783E+11 0.235485E+10 0.396130E+10 12675672.10 0.343743E+10 0.944176E+10 0.00 0.00 0.00 0.478974E+10 0.00
April 0.184586E+11 0.378945E+10 0.586172E+11 0.219176E+10 0.441015E+10 11960507.72 0.118440E+10 0.166023E+11 0.00 0.00 0.00 0.406894E+10 0.00
May 0.197872E+11 0.345949E+10 0.616817E+11 0.230565E+10 0.613428E+10 12527707.06 0.152841E+09 0.314007E+11 0.00 0.00 0.00 0.403265E+10 0.00
June 0.196404E+11 0.317507E+10 0.604966E+11 0.226788E+10 0.852872E+10 12231776.97 20522924.30 0.490012E+11 0.00 0.00 0.00 0.370649E+10 0.00
July 0.184155E+11 0.336986E+10 0.597911E+11 0.222868E+10 0.934013E+10 12256437.81 0.00 0.567530E+11 0.00 0.00 0.00 0.334719E+10 0.00
August 0.206313E+11 0.373343E+10 0.627783E+11 0.235465E+10 0.103739E+11 12675672.10 0.00 0.629099E+11 0.00 0.00 0.00 0.366739E+10 0.00
September 0.185961E+11 0.405491E+10 0.585950E+11 0.219061E+10 0.706229E+10 11960507.72 19142235.07 0.368953E+11 0.00 0.00 0.00 0.346312E+10 0.00
October 0.196424E+11 0.470282E+10 0.605962E+11 0.225781E+10 0.478162E+10 12379742.02 0.145989E+10 0.160067E+11 0.00 0.00 0.00 0.384536E+10 0.00
November 0.195059E+11 0.511872E+10 0.591197E+11 0.219997E+10 0.347596E+10 12059151.09 0.631885E+10 0.643499E+10 0.00 0.00 0.00 0.408662E+10 0.00
December 0.192055E+11 0.559902E+10 0.597800E+11 0.222855E+10 0.314650E+10 12256437.81 0.205359E+11 0.231540E+10 0.00 0.00 0.00 0.432568E+10 0.00
                           
Annual Sum or Average 0.232552E+12 0.513511E+11 0.719689E+12 0.268859E+11 0.675131E+11 0.146559E+09 0.114480E+12 0.292165E+12 0.00 0.00 0.00 0.481446E+11 0.00
Minimum of Months 0.179794E+11 0.317507E+10 0.548702E+11 0.204819E+10 0.306782E+10 11196021.66 0.00 0.121675E+10 0.00 0.00 0.00 0.334719E+10 0.00
Maximum of Months 0.208723E+11 0.559902E+10 0.627783E+11 0.235485E+10 0.103739E+11 12675672.10 0.531890E+11 0.629099E+11 0.00 0.00 0.00 0.478974E+10 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 24030.94 03-JAN-08:09 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 02-JAN-08:20 5284.91 09-JAN-07:10 6.85 03-JAN-18:10 189309.27 09-JAN-07:10
February 24713.90 01-FEB-08:09 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 03-FEB-12:09 4952.88 13-FEB-07:10 6.85 02-FEB-06:10 192831.40 13-FEB-07:10
March 24169.18 21-MAR-07:10 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 06-MAR-08:09 8273.03 30-MAR-15:00 6.85 06-MAR-08:09 63611.20 23-MAR-06:10
April 23249.44 03-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 06-APR-16:10 9082.29 17-APR-15:50 6.85 01-APR-05:10 56627.80 06-APR-06:10
May 20676.82 24-MAY-07:30 5686.19 01-MAY-05:10 41699.26 01-MAY-07:10 1410.29 01-MAY-07:10 12011.75 30-MAY-14:00 6.85 01-MAY-05:10 11242.41 11-MAY-06:10
June 20258.51 23-JUN-07:10 5686.19 01-JUN-05:10 41699.26 01-JUN-07:10 1410.29 01-JUN-07:10 12467.00 26-JUN-15:30 6.85 01-JUN-05:10 3780.18 08-JUN-06:19
July 21397.89 27-JUL-07:10 5686.19 01-JUL-05:10 41699.26 03-JUL-07:10 1410.29 03-JUL-07:10 14055.10 10-JUL-15:30 6.85 09-JUL-16:19 0.00 01-JUL-00:10
August 22850.66 24-AUG-07:10 5686.19 01-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-11:09 14740.47 02-AUG-15:50 6.85 13-AUG-16:19 0.00 01-AUG-00:10
September 23601.02 29-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 01-SEP-07:10 13835.63 07-SEP-15:30 6.85 01-SEP-05:10 3940.39 29-SEP-06:19
October 24978.45 30-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 24-OCT-11:09 10670.41 10-OCT-15:30 6.85 26-OCT-07:10 58856.18 26-OCT-06:10
November 24819.27 01-NOV-07:10 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 13-NOV-12:09 5729.30 06-NOV-15:30 6.85 13-NOV-12:09 108292.23 22-NOV-07:10
December 24050.81 06-DEC-08:09 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 04-DEC-12:09 3726.56 04-DEC-07:10 6.85 04-DEC-12:09 155843.73 18-DEC-07:10
                             
Annual Sum or Average                            
Minimum of Months 20258.51   5686.19   41699.26   1410.29   3726.56   6.85   0.00  
Maximum of Months 24978.45   5686.19   41699.26   1410.29   14740.47   6.85   192831.40  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 12114.25 19-JAN-15:00 0.00 0.00 0.00 6214.22 31-JAN-12:39 0.00
February 19192.35 28-FEB-15:09 0.00 0.00 0.00 6214.22 02-FEB-12:30 0.00
March 35125.14 30-MAR-15:20 0.00 0.00 0.00 6181.44 03-MAR-12:39 0.00
April 37465.25 17-APR-13:00 0.00 0.00 0.00 5783.50 03-APR-11:50 0.00
May 51535.71 30-MAY-14:00 0.00 0.00 0.00 5375.55 01-MAY-11:50 0.00
June 58805.34 27-JUN-15:00 0.00 0.00 0.00 4970.88 01-JUN-11:50 0.00
July 69402.51 07-JUL-15:00 0.00 0.00 0.00 4599.00 03-JUL-11:30 0.00
August 68069.42 01-AUG-14:00 0.00 0.00 0.00 4595.97 31-AUG-11:39 0.00
September 61088.18 07-SEP-15:00 0.00 0.00 0.00 4957.59 29-SEP-11:50 0.00
October 46065.65 10-OCT-15:00 0.00 0.00 0.00 5361.66 31-OCT-11:39 0.00
November 19125.74 02-NOV-14:09 0.00 0.00 0.00 5776.33 30-NOV-12:00 0.00
December 18138.24 12-DEC-13:00 0.00 0.00 0.00 6057.06 27-DEC-12:50 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 12114.25   0.00 0.00 0.00 4595.97   0.00
Maximum of Months 69402.51   0.00 0.00 0.00 6214.22   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 234037.50 09-JAN-07:10 8334.71 22496.85 5686.19 974.52 5284.91 6.85 189309.27 0.00 0.00
February 237229.50 13-FEB-07:10 8334.71 22496.85 5686.19 974.52 4952.88 6.85 192831.40 0.00 0.00
March 110404.42 30-MAR-15:20 19671.42 41670.51 0.00 1410.29 8116.93 6.85 0.00 35125.14 0.00
April 112870.88 17-APR-15:30 19671.42 41670.51 0.00 1410.29 9064.73 6.85 0.00 36865.12 0.00
May 129426.11 30-MAY-15:09 19671.42 41670.51 0.00 1410.29 11926.99 6.85 0.00 50882.55 0.00
June 137261.75 19-JUN-15:00 19671.42 41670.51 0.00 1410.29 12250.84 6.85 0.00 58580.23 0.00
July 149581.71 07-JUL-15:00 19671.42 41670.51 0.00 1410.29 13946.98 6.85 0.00 69402.51 0.00
August 148578.61 01-AUG-15:30 19671.42 41670.51 0.00 1410.29 14342.03 6.85 0.00 67953.41 0.00
September 141017.96 07-SEP-15:00 19671.42 41670.51 0.00 1410.29 13630.98 6.85 0.00 61088.18 0.00
October 123266.68 10-OCT-15:30 19671.42 41670.51 0.00 1410.29 10670.41 6.85 0.00 45960.31 0.00
November 150378.83 22-NOV-07:10 8334.71 22496.85 5686.19 974.52 2925.11 6.85 108292.23 0.00 0.00
December 198960.67 18-DEC-07:10 8334.71 22496.85 5686.19 974.52 3671.92 6.85 155843.73 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 110404.42   8334.71 22496.85 0.00 974.52 2925.11 6.85 0.00 0.00 0.00
Maximum of Months 237229.50   19671.42 41670.51 5686.19 1410.29 14342.03 6.85 192831.40 69402.51 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.17 0.17 19.17 0.00 19.17 0.00 19.17
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.17 0.17 19.17 0.00 19.17 0.00 19.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.17 0.17 19.17 0.00 19.17 0.00 19.17



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.41 0.50 18.65 0.00 18.65 0.00 18.65
February 0.17 19.22 0.17 19.22 0.00 19.22 0.00 19.22
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
                 
Annual Sum or Average 1.00 18.72 0.83 18.90 0.00 18.90 0.00 18.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 19.43 0.50 19.43 0.00 19.43 0.00 19.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 8.83 17.23 4.67 17.64 0.00 17.64 0.00 17.64
February 7.67 16.50 3.50 16.93 0.00 16.93 0.00 16.93
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.33 27.44 0.83 27.44
July 0.00 0.00 0.00 0.00 3.67 27.54 2.33 27.55
August 0.00 0.00 0.00 0.00 1.00 27.33 1.00 27.33
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.50 18.28 1.67 18.72 0.00 18.72 0.00 18.72
                 
Annual Sum or Average 19.00 17.07 9.83 17.52 6.00 19.24 4.17 20.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8.83 18.28 4.67 18.72 3.67 27.54 2.33 27.55



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.83 15.94 1.33 16.12 0.00 16.12 0.00 16.12
February 5.00 15.47 0.83 15.62 0.00 15.62 0.00 15.62
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.61 0.67 27.61
May 0.00 0.00 0.00 0.00 4.17 27.53 4.17 27.53
June 0.00 0.00 0.00 0.00 8.33 27.70 7.50 27.71
July 0.00 0.00 0.00 0.00 13.50 27.75 11.33 27.78
August 0.00 0.00 0.00 0.00 9.50 27.73 8.50 27.75
September 0.00 0.00 0.00 0.00 1.83 27.60 1.83 27.60
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 17.29 0.50 17.47 0.00 17.47 0.00 17.47
                 
Annual Sum or Average 12.83 15.86 2.67 16.06 38.00 24.33 34.00 25.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.83 17.29 1.33 17.47 13.50 27.75 11.33 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.67 16.87 1.50 17.23 0.00 17.23 0.00 17.23
February 3.50 15.82 1.00 15.90 1.00 18.01 1.00 19.48
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.51 1.00 27.51
May 0.00 0.00 0.00 0.00 1.00 27.42 1.00 27.42
June 0.00 0.00 0.00 0.00 3.00 27.45 2.67 27.45
July 0.00 0.00 0.00 0.00 7.67 27.52 6.33 27.53
August 0.00 0.00 0.00 0.00 6.33 27.68 5.33 27.71
September 0.00 0.00 0.00 0.00 3.17 27.58 3.17 27.58
October 0.00 0.00 0.00 0.00 3.83 27.71 3.83 27.71
November 0.00 0.00 0.00 0.00 2.17 27.52 2.17 27.52
December 0.67 17.93 0.33 18.31 0.00 18.31 0.00 18.31
                 
Annual Sum or Average 8.83 16.53 2.83 16.81 29.17 24.50 26.50 25.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.67 17.93 1.50 18.31 7.67 27.71 6.33 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.50 15.99 1.50 16.15 0.00 16.15 0.00 16.15
February 4.67 15.34 1.33 15.31 0.00 15.31 0.00 15.31
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.83 27.67 2.00 27.68
May 0.00 0.00 0.00 0.00 3.83 27.91 2.00 27.93
June 0.00 0.00 0.00 0.00 7.33 27.97 3.83 28.02
July 0.00 0.00 0.00 0.00 12.00 28.08 6.00 28.10
August 0.00 0.00 0.00 0.00 8.00 28.04 4.33 28.09
September 0.00 0.00 0.00 0.00 4.50 27.67 3.00 27.70
October 0.00 0.00 0.00 0.00 1.83 27.58 1.17 27.61
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 17.90 0.33 18.34 0.00 18.34 0.00 18.34
                 
Annual Sum or Average 11.83 15.84 3.17 15.96 40.33 24.69 22.33 25.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.50 17.90 1.50 18.34 12.00 28.08 6.00 28.10



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.85 0.50 19.09 0.00 19.09 0.00 19.09
February 0.67 18.99 0.50 19.27 0.00 19.27 0.00 19.27
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 18.92 1.00 19.18 0.00 19.18 0.00 19.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 18.99 0.50 19.27 0.00 19.27 0.00 19.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 17.18 0.00 17.18 0.00 17.18 0.00 17.18
February 0.17 17.11 0.00 17.11 0.00 17.11 0.00 17.11
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 27.38 0.67 27.38
June 0.00 0.00 0.00 0.00 3.00 27.58 3.00 27.58
July 0.00 0.00 0.00 0.00 7.33 27.55 7.33 27.55
August 0.00 0.00 0.00 0.00 5.50 27.56 5.50 27.56
September 0.00 0.00 0.00 0.00 1.67 27.48 1.67 27.48
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.15 0.00 17.15 18.17 27.36 18.17 27.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 17.18 0.00 17.18 7.33 27.58 7.33 27.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 45.50 18.13 45.50 18.13 0.00 18.13 0.00 18.13
February 30.17 18.34 30.17 18.34 0.50 18.42 0.50 18.49
March 11.17 19.51 11.17 19.51 0.00 19.51 0.00 19.51
April 4.33 18.70 4.33 18.70 0.00 18.70 0.00 18.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 5.00 24.70 5.00 24.70
July 0.00 0.00 0.00 0.00 14.67 24.92 14.67 24.92
August 0.00 0.00 0.00 0.00 25.00 25.31 25.00 25.31
September 0.00 0.00 0.00 0.00 8.67 25.31 8.67 25.31
October 2.00 19.46 2.00 19.46 9.83 24.17 9.83 24.96
November 10.83 19.49 10.83 19.49 2.17 20.22 2.17 20.83
December 20.50 18.48 20.50 18.48 0.00 18.48 0.00 18.48
                 
Annual Sum or Average 124.50 18.52 124.50 18.52 65.83 19.96 65.83 20.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 45.50 19.51 45.50 19.51 25.00 25.31 25.00 25.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 17.17 0.00 17.17 0.00 17.17 0.00 17.17
February 0.17 17.20 0.00 17.20 0.00 17.20 0.00 17.20
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.28 0.00 27.28
May 0.00 0.00 0.00 0.00 2.00 27.47 1.00 27.47
June 0.00 0.00 0.00 0.00 4.33 27.64 2.33 27.66
July 0.00 0.00 0.00 0.00 7.83 27.78 4.17 27.77
August 0.00 0.00 0.00 0.00 5.83 27.77 3.17 27.79
September 0.00 0.00 0.00 0.00 2.83 27.53 2.00 27.53
October 0.00 0.00 0.00 0.00 1.17 27.56 0.83 27.57
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 17.18 0.00 17.18 24.17 27.54 13.50 27.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 17.20 0.00 17.20 7.83 27.78 4.17 27.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 18.78 1.17 19.06 0.00 19.06 0.00 19.06
February 1.00 18.66 0.67 19.01 0.00 19.01 0.00 19.01
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.33 27.34 1.17 27.35
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.50 18.74 1.83 19.04 1.33 20.99 1.17 22.08
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 18.78 1.17 19.06 1.33 27.34 1.17 27.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.92 0.33 18.36 0.00 18.36 0.00 18.36
February 0.17 16.73 0.00 16.73 0.00 16.73 0.00 16.73
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.60 0.83 27.60
May 0.00 0.00 0.00 0.00 3.67 27.54 3.67 27.54
June 0.00 0.00 0.00 0.00 5.83 27.68 5.67 27.69
July 0.00 0.00 0.00 0.00 10.83 27.66 10.50 27.66
August 0.00 0.00 0.00 0.00 7.17 27.67 7.00 27.68
September 0.00 0.00 0.00 0.00 2.17 27.57 2.17 27.57
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 17.68 0.33 18.12 30.50 27.29 29.83 27.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.92 0.33 18.36 10.83 27.68 10.50 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.96 0.33 18.38 0.17 19.65 0.17 20.60
February 0.17 17.01 0.00 17.01 1.17 26.23 1.17 26.84
March 0.00 0.00 0.00 0.00 0.50 27.30 0.50 27.30
April 0.00 0.00 0.00 0.00 0.67 27.41 0.67 27.41
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 3.00 27.40 3.00 27.40
August 0.00 0.00 0.00 0.00 4.83 27.52 4.67 27.52
September 0.00 0.00 0.00 0.00 2.50 27.51 2.50 27.51
October 0.00 0.00 0.00 0.00 4.50 27.65 4.50 27.65
November 0.00 0.00 0.00 0.00 2.67 27.64 2.67 27.64
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 17.77 0.33 18.18 20.00 27.02 19.83 27.27
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.96 0.33 18.38 4.83 27.65 4.67 27.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 17.90 0.33 18.34 0.00 18.34 0.00 18.34
February 0.17 16.82 0.00 16.82 0.00 16.82 0.00 16.82
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.17 27.60 1.67 27.60
May 0.00 0.00 0.00 0.00 3.17 27.79 1.67 27.81
June 0.00 0.00 0.00 0.00 6.00 27.82 3.33 27.86
July 0.00 0.00 0.00 0.00 10.00 27.95 5.17 27.96
August 0.00 0.00 0.00 0.00 6.17 27.97 3.50 28.01
September 0.00 0.00 0.00 0.00 3.67 27.61 2.67 27.62
October 0.00 0.00 0.00 0.00 1.50 27.58 1.17 27.59
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 17.68 0.33 18.12 32.67 27.50 19.17 27.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 17.90 0.33 18.34 10.00 27.97 5.17 28.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 486.83 22.98 14.83 22.95 14.83 22.91
February 374.50 23.40 9.50 23.44 0.00 23.44
March 160.83 23.96 113.00 24.29 0.00 24.29
April 42.33 23.99 223.50 24.65 0.00 24.65
May 2.00 24.00 419.83 24.55 0.00 24.55
June 0.00 0.00 451.33 24.44 0.00 24.44
July 0.00 0.00 497.00 24.50 0.00 24.50
August 0.00 0.00 514.00 24.42 0.00 24.42
September 0.00 0.00 461.50 24.52 0.00 24.52
October 15.33 23.89 244.67 24.71 0.00 24.71
November 177.00 23.97 81.83 24.26 0.00 24.26
December 417.00 23.73 17.67 23.76 0.00 23.76
             
Annual Sum or Average 1675.83 23.49 3048.67 24.17 14.83 24.16
Minimum of Months 0.00 0.00 9.50 22.95 0.00 22.91
Maximum of Months 486.83 24.00 514.00 24.71 14.83 24.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.30 154.17 21.12 154.17 21.02
February 447.83 21.98 74.00 21.80 74.00 21.66
March 402.50 23.15 34.83 23.23 0.00 23.23
April 216.00 23.43 106.17 23.74 0.00 23.74
May 46.67 23.52 270.67 24.19 0.00 24.19
June 17.67 23.68 396.83 24.26 0.00 24.26
July 5.67 23.29 470.83 24.31 0.00 24.31
August 0.00 0.00 501.67 24.28 0.00 24.28
September 19.00 23.18 349.00 24.30 0.00 24.30
October 236.67 23.16 102.00 23.49 0.00 23.49
November 439.83 22.99 0.00 22.99 0.00 22.99
December 488.50 21.94 22.67 21.90 21.67 21.86
             
Annual Sum or Average 2822.33 22.43 2482.83 23.14 249.83 23.02
Minimum of Months 0.00 0.00 0.00 21.12 0.00 21.02
Maximum of Months 502.00 23.68 501.67 24.31 154.17 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.71 314.50 20.54 314.50 20.47
February 450.83 21.38 141.17 21.13 141.17 20.98
March 441.50 22.62 43.67 22.67 12.33 22.62
April 262.67 23.10 88.50 23.39 0.00 23.39
May 93.17 23.38 260.00 24.02 0.00 24.02
June 28.50 23.49 391.67 24.24 0.00 24.24
July 12.00 23.16 464.83 24.32 0.00 24.32
August 0.00 0.00 494.83 24.30 0.00 24.30
September 67.83 23.14 293.67 24.10 0.00 24.10
October 341.33 22.73 72.00 22.97 0.50 22.97
November 477.50 22.16 33.33 22.06 33.33 21.96
December 494.17 21.17 178.50 20.96 178.50 20.84
             
Annual Sum or Average 3171.50 21.94 2776.67 22.59 680.33 22.36
Minimum of Months 0.00 0.00 33.33 20.54 0.00 20.47
Maximum of Months 502.00 23.49 494.83 24.32 314.50 24.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.16 413.83 20.06 413.83 20.02
February 450.17 20.80 245.83 20.56 245.83 20.44
March 450.50 21.90 110.17 21.84 73.50 21.67
April 283.67 22.53 117.83 22.90 16.67 22.81
May 112.83 23.01 285.17 23.93 0.00 23.93
June 37.67 24.03 411.00 24.34 11.00 24.39
July 32.83 25.26 474.17 24.53 25.17 24.59
August 21.83 25.67 500.33 24.43 18.67 24.49
September 123.67 23.29 294.67 24.05 17.00 24.10
October 385.17 22.09 92.33 22.36 25.17 22.34
November 480.33 21.39 141.50 21.15 141.50 20.99
December 497.00 20.49 326.00 20.30 326.00 20.22
             
Annual Sum or Average 3377.67 21.46 3412.83 22.14 1314.33 21.86
Minimum of Months 21.83 20.16 92.33 20.06 0.00 20.02
Maximum of Months 502.00 25.67 500.33 24.53 413.83 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.37 371.67 20.22 371.67 20.15
February 435.83 21.14 201.67 20.82 201.67 20.65
March 378.83 22.31 93.33 22.36 37.83 22.21
April 180.17 22.63 179.00 23.43 9.33 23.38
May 87.00 23.60 353.50 24.29 12.50 24.37
June 47.17 25.59 451.00 24.55 32.50 24.68
July 70.33 26.17 478.67 24.78 62.50 24.97
August 48.67 26.46 506.17 24.63 47.17 24.78
September 100.00 23.64 343.50 24.27 25.00 24.36
October 297.83 22.24 146.50 22.81 23.17 22.78
November 459.33 21.78 97.00 21.57 90.33 21.39
December 493.17 20.72 264.17 20.46 264.17 20.33
             
Annual Sum or Average 3100.33 21.79 3486.17 22.55 1177.83 22.33
Minimum of Months 47.17 20.37 93.33 20.22 9.33 20.15
Maximum of Months 502.00 26.46 506.17 24.78 371.67 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 479.00 20.99 274.83 20.65 271.17 20.47
February 395.83 21.35 181.00 21.18 162.17 20.98
March 327.67 22.13 131.50 22.43 44.50 22.25
April 218.17 22.56 166.17 23.26 14.17 23.20
May 114.17 23.03 296.50 23.99 1.50 24.00
June 51.00 24.14 403.83 24.35 16.33 24.42
July 45.17 25.72 467.83 24.60 37.83 24.72
August 36.50 26.18 501.50 24.54 33.17 24.65
September 108.67 23.70 327.67 24.28 27.50 24.39
October 267.33 22.37 190.33 23.19 27.00 23.25
November 368.00 21.91 125.67 22.02 74.33 21.83
December 439.00 21.20 202.17 20.91 190.33 20.70
             
Annual Sum or Average 2850.50 21.95 3269.00 22.76 900.00 22.54
Minimum of Months 36.50 20.99 125.67 20.65 1.50 20.47
Maximum of Months 479.00 26.18 501.50 24.60 271.17 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.43 357.33 20.22 357.33 20.13
February 431.00 20.99 219.17 20.75 212.67 20.60
March 370.67 21.95 133.83 22.13 59.33 21.94
April 228.33 22.61 175.33 23.29 17.33 23.28
May 110.67 23.35 325.50 24.12 10.67 24.19
June 54.67 24.70 424.17 24.45 25.00 24.56
July 49.17 25.86 471.17 24.65 42.50 24.78
August 36.50 26.25 503.83 24.56 33.83 24.68
September 116.17 23.73 323.83 24.26 31.50 24.38
October 326.50 22.15 139.17 22.74 24.17 22.75
November 435.67 21.55 129.50 21.37 116.00 21.18
December 491.17 20.76 273.83 20.48 273.83 20.35
             
Annual Sum or Average 3152.50 21.68 3476.67 22.44 1204.17 22.21
Minimum of Months 36.50 20.43 129.50 20.22 10.67 20.13
Maximum of Months 502.00 26.25 503.83 24.65 357.33 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.52 396.00 20.44 396.00 20.41
February 454.00 20.97 210.50 20.77 210.50 20.67
March 488.00 21.89 55.17 21.80 47.50 21.70
April 399.67 22.53 38.33 22.62 7.17 22.58
May 177.17 23.13 212.33 23.73 0.00 23.73
June 26.67 23.71 402.17 24.24 2.67 24.25
July 13.50 24.65 477.33 24.40 8.33 24.42
August 5.83 26.08 509.17 24.35 5.83 24.37
September 56.83 23.95 361.83 24.29 15.83 24.34
October 339.67 22.89 101.67 23.18 6.00 23.21
November 466.17 22.24 34.33 22.19 26.67 22.11
December 497.00 21.07 210.83 20.92 210.83 20.83
             
Annual Sum or Average 3426.50 21.80 3009.67 22.43 937.33 22.20
Minimum of Months 5.83 20.52 34.33 20.44 0.00 20.41
Maximum of Months 502.00 26.08 509.17 24.40 396.00 24.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.77 330.67 20.63 330.67 20.57
February 443.00 21.43 165.50 21.15 165.50 21.00
March 427.50 22.56 52.33 22.60 16.17 22.53
April 262.50 22.90 113.50 23.32 2.83 23.30
May 92.50 23.29 317.50 24.20 2.17 24.21
June 19.33 25.48 451.67 24.46 11.50 24.51
July 36.67 26.20 482.83 24.69 31.67 24.80
August 23.00 26.82 513.00 24.56 23.00 24.65
September 49.83 24.46 415.00 24.47 20.83 24.54
October 207.83 22.98 177.00 23.65 7.33 23.67
November 413.17 22.75 35.17 22.81 7.67 22.77
December 487.00 21.45 111.83 21.28 111.83 21.15
             
Annual Sum or Average 2964.33 22.14 3166.00 22.92 731.17 22.74
Minimum of Months 19.33 20.77 35.17 20.63 2.17 20.57
Maximum of Months 502.00 26.82 513.00 24.69 330.67 24.80



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 489.67 20.90 245.00 20.62 240.00 20.46
February 406.17 21.23 149.67 21.06 135.50 20.85
March 390.17 22.15 84.00 22.37 24.67 22.26
April 323.50 22.48 95.00 22.82 11.67 22.75
May 188.17 22.84 234.83 23.63 13.50 23.62
June 89.00 23.56 401.33 24.15 49.33 24.13
July 75.50 24.05 478.50 24.38 69.17 24.35
August 86.83 24.44 511.00 24.45 85.83 24.45
September 91.83 23.92 405.00 24.39 46.83 24.44
October 213.00 22.82 230.00 23.72 29.83 23.79
November 323.50 22.47 82.83 22.91 8.33 22.87
December 438.17 21.57 88.83 21.51 63.00 21.32
             
Annual Sum or Average 3115.50 22.11 3006.00 22.91 777.67 22.77
Minimum of Months 75.50 20.90 82.83 20.62 8.33 20.46
Maximum of Months 489.67 24.44 511.00 24.45 240.00 24.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.78 324.67 20.61 324.67 20.54
February 440.50 21.26 170.83 21.04 167.83 20.90
March 410.17 22.33 69.50 22.49 17.83 22.43
April 279.17 22.83 111.67 23.25 4.00 23.23
May 107.50 23.31 297.67 24.09 2.50 24.11
June 27.67 24.67 434.00 24.41 10.33 24.46
July 30.00 25.97 481.67 24.59 25.50 24.68
August 20.33 26.74 513.00 24.54 20.33 24.62
September 55.33 24.55 410.83 24.48 24.17 24.56
October 229.33 23.01 167.83 23.61 8.17 23.65
November 401.50 22.56 40.50 22.65 12.00 22.60
December 484.83 21.39 133.67 21.20 133.17 21.08
             
Annual Sum or Average 2988.33 22.05 3155.83 22.85 750.50 22.66
Minimum of Months 20.33 20.78 40.50 20.61 2.50 20.54
Maximum of Months 502.00 26.74 513.00 24.59 324.67 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.47 386.33 20.36 386.33 20.31
February 450.00 21.10 184.33 20.84 184.33 20.69
March 441.17 22.32 72.17 22.35 31.83 22.25
April 258.00 22.85 111.83 23.25 3.83 23.23
May 83.17 23.31 313.83 24.09 0.00 24.09
June 19.17 24.18 425.67 24.34 6.17 24.36
July 18.67 25.03 482.83 24.48 13.83 24.51
August 9.00 25.76 508.50 24.39 9.00 24.42
September 77.83 23.66 331.33 24.22 17.00 24.27
October 358.67 22.58 92.50 22.88 11.67 22.90
November 473.33 21.95 56.67 21.80 56.00 21.68
December 493.17 20.89 242.50 20.70 242.50 20.61
             
Annual Sum or Average 3184.17 21.75 3208.50 22.48 962.50 22.23
Minimum of Months 9.00 20.47 56.67 20.36 0.00 20.31
Maximum of Months 502.00 25.76 508.50 24.48 386.33 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.64 282.83 20.45 282.83 20.37
February 363.33 21.34 143.33 21.08 138.83 20.90
March 310.67 22.59 59.33 22.74 12.83 22.66
April 154.83 22.98 146.83 23.71 4.67 23.71
May 62.50 23.99 298.33 24.48 12.17 24.56
June 31.33 25.95 381.83 24.64 23.83 24.75
July 55.17 26.36 412.83 24.88 50.83 25.05
August 36.00 26.65 430.50 24.71 36.00 24.85
September 66.33 24.23 307.33 24.49 24.83 24.59
October 238.17 22.65 126.33 23.26 12.50 23.28
November 376.67 22.27 47.00 22.20 32.00 22.08
December 413.83 21.11 165.50 20.86 165.50 20.72
             
Annual Sum or Average 2535.83 22.08 2802.00 22.87 796.83 22.69
Minimum of Months 31.33 20.64 47.00 20.45 4.67 20.37
Maximum of Months 427.00 26.65 430.50 24.88 282.83 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 461.67 21.28 230.33 20.98 225.33 20.79
February 386.83 21.68 128.83 21.57 109.00 21.36
March 305.50 22.57 107.17 22.99 12.50 22.92
April 190.00 22.91 167.50 23.61 4.17 23.60
May 79.00 23.25 321.50 24.13 0.00 24.13
June 31.33 24.14 421.17 24.34 8.33 24.38
July 26.33 25.57 482.83 24.54 21.50 24.60
August 27.33 26.52 509.00 24.52 27.33 24.62
September 72.67 24.17 370.33 24.42 25.33 24.51
October 230.50 22.85 209.67 23.63 19.67 23.72
November 339.67 22.48 90.67 22.80 25.50 22.74
December 414.67 21.60 125.83 21.44 108.33 21.24
             
Annual Sum or Average 2565.50 22.24 3164.83 23.13 587.00 22.96
Minimum of Months 26.33 21.28 90.67 20.98 0.00 20.79
Maximum of Months 461.67 26.52 509.00 24.54 225.33 24.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.50 20.75 313.17 20.53 313.17 20.43
February 430.00 21.30 161.50 21.07 155.33 20.89
March 354.33 22.40 100.33 22.70 19.00 22.61
April 195.33 22.96 191.00 23.66 7.00 23.67
May 79.83 23.68 355.00 24.25 8.17 24.30
June 38.33 25.15 440.50 24.48 21.00 24.57
July 40.67 26.03 486.83 24.64 36.17 24.75
August 27.33 26.59 510.00 24.55 27.33 24.65
September 78.67 24.19 370.17 24.41 28.83 24.51
October 293.67 22.66 146.17 23.23 14.00 23.27
November 422.17 22.10 70.33 22.08 46.83 21.94
December 484.00 21.16 189.50 20.92 188.67 20.78
             
Annual Sum or Average 2945.83 21.98 3334.50 22.81 865.50 22.61
Minimum of Months 27.33 20.75 70.33 20.53 7.00 20.43
Maximum of Months 501.50 26.59 510.00 24.64 313.17 24.75



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.01340 26.46485 -0.0577 5.78734
February 454.00000 23.57923 27.42411 0.10637 6.03640
March 514.00000 24.24896 30.68922 0.33459 7.63304
April 485.00000 24.41061 35.75339 0.42626 9.14025
May 508.00000 24.46380 42.45267 -0.3413 8.04551
June 496.00000 24.41527 44.29475 -0.3141 7.60381
July 497.00000 24.49796 45.98036 -0.2721 7.14376
August 514.00000 24.41848 46.29360 -0.2868 7.22703
September 485.00000 24.49029 44.86810 -0.2952 7.47941
October 502.00000 24.40937 37.99889 0.45010 9.54848
November 489.00000 24.27120 28.76922 0.32334 7.48084
December 497.00000 23.80673 28.33763 0.17099 5.97834
           
Annual Sum or Average 5943.00000 24.17244 36.68556 0.01887 7.43331
Minimum of Months 454.00000 23.01340 26.46485 -0.3413 5.78734
Maximum of Months 514.00000 24.49796 46.29360 0.45010 9.54848



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.29553 28.54239 -0.4462 10.03386
February 454.00000 22.00572 29.48520 -0.2486 7.90014
March 514.00000 23.36506 32.82813 0.13034 6.15748
April 485.00000 23.84526 37.40164 0.29273 7.25917
May 508.00000 24.10619 43.42885 -0.4725 10.06107
June 496.00000 24.21838 45.24578 -0.3968 8.68489
July 497.00000 24.29034 47.15499 -0.3547 7.99018
August 514.00000 24.27135 47.50296 -0.3529 7.90882
September 485.00000 24.18956 45.90418 -0.4184 9.12615
October 502.00000 23.68486 40.38691 0.27004 7.10726
November 489.00000 23.09742 31.63705 0.04645 5.84277
December 497.00000 21.97144 31.52512 -0.2419 7.21538
           
Annual Sum or Average 5943.00000 23.37166 38.49244 -0.1829 7.94237
Minimum of Months 454.00000 21.29553 28.54239 -0.4725 5.84277
Maximum of Months 514.00000 24.29034 47.50296 0.29273 10.06107



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.70962 28.86596 -0.6184 14.80320
February 454.00000 21.40110 30.05842 -0.4129 10.90887
March 514.00000 22.81823 33.26868 -0.0042 6.52339
April 485.00000 23.57759 37.32291 0.22563 6.96877
May 508.00000 24.01910 42.87253 -0.5011 10.86326
June 496.00000 24.20977 44.87304 -0.3910 8.68375
July 497.00000 24.30341 46.82903 -0.3394 7.83278
August 514.00000 24.28525 47.21945 -0.3381 7.69604
September 485.00000 24.05925 45.66991 -0.4680 10.28556
October 502.00000 23.15191 41.19420 0.13509 6.59179
November 489.00000 22.20429 32.77194 -0.1739 7.01996
December 497.00000 21.18303 32.70340 -0.4530 10.77262
           
Annual Sum or Average 5943.00000 23.00590 38.70579 -0.2778 9.06535
Minimum of Months 454.00000 20.70962 28.86596 -0.6184 6.52339
Maximum of Months 514.00000 24.30341 47.21945 0.22563 14.80320



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.16432 29.64935 -0.8070 21.53080
February 454.00000 20.83130 31.76168 -0.5867 15.46383
March 514.00000 22.16217 35.83106 -0.1615 8.27015
April 485.00000 23.20727 39.97450 0.14866 7.63093
May 508.00000 23.94733 44.95603 -0.4987 11.78846
June 496.00000 24.26445 46.30263 -0.3214 8.25168
July 497.00000 24.43451 48.90399 -0.2375 7.27323
August 514.00000 24.36005 49.45522 -0.2576 7.15589
September 485.00000 23.97758 48.52334 -0.4739 11.47462
October 502.00000 22.53931 45.31157 -0.0020 7.33127
November 489.00000 21.43757 36.08757 -0.3656 10.04334
December 497.00000 20.49181 33.68090 -0.6590 16.71056
           
Annual Sum or Average 5943.00000 22.66590 40.93960 -0.3504 11.04106
Minimum of Months 454.00000 20.16432 29.64935 -0.8070 7.15589
Maximum of Months 514.00000 24.43451 49.45522 0.14866 21.53080



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.36545 30.39712 -0.7339 18.96259
February 454.00000 21.26432 31.97432 -0.4624 13.41295
March 514.00000 22.77759 35.21181 -0.0008 7.63373
April 485.00000 23.64656 38.81856 0.28352 8.70309
May 508.00000 24.18028 44.06924 -0.3638 9.96898
June 496.00000 24.37764 45.75916 -0.2196 7.48343
July 497.00000 24.54011 48.29589 -0.1366 7.21995
August 514.00000 24.44467 48.95406 -0.1670 6.88576
September 485.00000 24.13419 47.90449 -0.3689 10.20582
October 502.00000 23.03408 44.25454 0.13317 8.05394
November 489.00000 21.92057 36.10611 -0.2369 8.69707
December 497.00000 20.73818 34.27510 -0.5770 14.63517
           
Annual Sum or Average 5943.00000 22.96548 40.56719 -0.2362 10.12561
Minimum of Months 454.00000 20.36545 30.39712 -0.7339 6.88576
Maximum of Months 514.00000 24.54011 48.95406 0.28352 18.96259



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.14589 28.28701 -0.5285 15.78337
February 454.00000 21.76265 30.11839 -0.3293 12.16522
March 514.00000 22.92063 33.71980 0.04215 8.42289
April 485.00000 23.49887 38.73148 0.23978 8.62652
May 508.00000 23.97854 44.65560 -0.4704 11.61037
June 496.00000 24.24571 46.32691 -0.3227 8.54888
July 497.00000 24.44316 48.82770 -0.2258 7.37691
August 514.00000 24.39960 49.07613 -0.2118 7.03163
September 485.00000 24.12368 47.50438 -0.3750 10.43330
October 502.00000 23.24584 42.52367 0.20392 9.22231
November 489.00000 22.54023 33.22140 -0.0738 9.11604
December 497.00000 21.55458 31.71881 -0.3658 12.31831
           
Annual Sum or Average 5943.00000 23.16582 39.63357 -0.2010 10.03669
Minimum of Months 454.00000 21.14589 28.28701 -0.5285 7.03163
Maximum of Months 514.00000 24.44316 49.07613 0.23978 15.78337



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.42660 30.29119 -0.7258 19.44867
February 454.00000 21.16591 32.01760 -0.4909 14.13054
March 514.00000 22.59324 35.29822 -0.0395 8.56065
April 485.00000 23.46959 39.44283 0.24321 8.85494
May 508.00000 24.04207 44.70731 -0.4189 11.02619
June 496.00000 24.30658 46.29117 -0.2585 8.15318
July 497.00000 24.48151 48.93477 -0.1752 7.34448
August 514.00000 24.42674 49.30613 -0.1820 7.01774
September 485.00000 24.09726 48.26102 -0.3902 10.65917
October 502.00000 22.87448 44.77941 0.09703 8.26000
November 489.00000 21.84614 35.96862 -0.2571 9.58037
December 497.00000 20.79294 34.18784 -0.5731 15.08886
           
Annual Sum or Average 5943.00000 22.89050 40.85760 -0.2629 10.64717
Minimum of Months 454.00000 20.42660 30.29119 -0.7258 7.01774
Maximum of Months 514.00000 24.48151 49.30613 0.24321 19.44867



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.52077 29.58024 -0.6943 16.54988
February 454.00000 20.97368 32.19479 -0.5346 13.00150
March 514.00000 21.98713 37.15498 -0.2029 7.43806
April 485.00000 22.79559 42.08377 0.03608 6.53398
May 508.00000 23.78682 46.94160 -0.5945 13.55407
June 496.00000 24.20570 46.60997 -0.3822 8.57645
July 497.00000 24.37039 48.40371 -0.2951 7.35032
August 514.00000 24.32735 48.49788 -0.2971 7.24105
September 485.00000 24.19923 47.94043 -0.3992 9.08025
October 502.00000 23.25938 43.52240 0.17820 6.78975
November 489.00000 22.32310 34.67819 -0.1279 6.79212
December 497.00000 21.07387 33.14026 -0.4735 10.90210
           
Annual Sum or Average 5943.00000 22.83179 40.96435 -0.3148 9.46817
Minimum of Months 454.00000 20.52077 29.58024 -0.6943 6.53398
Maximum of Months 514.00000 24.37039 48.49788 0.17820 16.54988



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.76875 30.38567 -0.6104 14.23278
February 454.00000 21.49727 32.39186 -0.3897 10.89246
March 514.00000 22.81212 36.38614 0.00459 6.69235
April 485.00000 23.50690 40.52580 0.22837 7.47148
May 508.00000 24.14569 45.60523 -0.4204 10.35307
June 496.00000 24.37210 45.85817 -0.2624 7.33627
July 497.00000 24.54340 47.68257 -0.1717 6.91208
August 514.00000 24.45909 47.87967 -0.1888 6.68704
September 485.00000 24.35130 47.30456 -0.2911 7.98212
October 502.00000 23.71896 42.36807 0.30913 8.23491
November 489.00000 22.96940 34.26835 0.03410 6.45814
December 497.00000 21.49929 33.51215 -0.3547 9.07071
           
Annual Sum or Average 5943.00000 23.23255 40.41103 -0.1753 8.51348
Minimum of Months 454.00000 20.76875 30.38567 -0.6104 6.45814
Maximum of Months 514.00000 24.54340 47.87967 0.30913 14.23278



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.01364 26.82528 -0.5007 13.45900
February 454.00000 21.59909 29.26166 -0.3256 11.01717
March 514.00000 22.69391 34.49837 0.00486 7.44910
April 485.00000 23.07456 40.38176 0.12997 7.35720
May 508.00000 23.69610 48.61817 -0.5840 13.99356
June 496.00000 24.15024 50.35258 -0.3687 8.80716
July 497.00000 24.40127 53.04826 -0.2442 6.98722
August 514.00000 24.44862 53.48727 -0.1865 6.43983
September 485.00000 24.29198 49.77377 -0.2889 8.39672
October 502.00000 23.71317 41.90017 0.35007 9.66558
November 489.00000 23.14937 31.48553 0.12133 7.90920
December 497.00000 21.91540 30.14011 -0.2132 8.73691
           
Annual Sum or Average 5943.00000 23.19005 40.91351 -0.1752 9.17878
Minimum of Months 454.00000 21.01364 26.82528 -0.5840 6.43983
Maximum of Months 514.00000 24.44862 53.48727 0.35007 13.99356



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.78084 30.35490 -0.6104 14.51345
February 454.00000 21.35536 32.52178 -0.4257 11.41480
March 514.00000 22.71922 36.26187 -0.0146 7.07890
April 485.00000 23.42660 40.79795 0.20716 7.44565
May 508.00000 24.06149 46.04204 -0.4596 10.81649
June 496.00000 24.32804 46.26950 -0.2920 7.69523
July 497.00000 24.48281 48.18165 -0.2097 6.98826
August 514.00000 24.45223 48.09324 -0.1990 6.73013
September 485.00000 24.35245 47.48576 -0.3001 8.08770
October 502.00000 23.68310 42.62451 0.29805 8.13670
November 489.00000 22.86344 34.22604 0.00981 6.74031
December 497.00000 21.44875 33.55573 -0.3703 9.49698
           
Annual Sum or Average 5943.00000 23.17573 40.59830 -0.1963 8.74727
Minimum of Months 454.00000 20.78084 30.35490 -0.6104 6.73013
Maximum of Months 514.00000 24.48281 48.18165 0.29805 14.51345



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.46978 29.38030 -0.6973 17.19991
February 454.00000 21.12305 31.44815 -0.4857 12.73691
March 514.00000 22.55719 35.47023 -0.0557 6.99787
April 485.00000 23.46380 39.84403 0.21288 7.38005
May 508.00000 24.06649 45.07337 -0.4634 10.35986
June 496.00000 24.29089 46.30698 -0.3245 7.86528
July 497.00000 24.43739 48.76093 -0.2513 7.10399
August 514.00000 24.36271 49.25877 -0.2710 7.12444
September 485.00000 24.12718 48.32944 -0.4227 9.78781
October 502.00000 22.98955 44.33261 0.11472 6.83765
November 489.00000 22.01667 35.17604 -0.2061 7.62120
December 497.00000 20.91437 33.05970 -0.5212 12.43067
           
Annual Sum or Average 5943.00000 22.91518 40.60704 -0.2800 9.42860
Minimum of Months 454.00000 20.46978 29.38030 -0.6973 6.83765
Maximum of Months 514.00000 24.43739 49.25877 0.21288 17.19991



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.63525 29.92422 -0.6406 15.71462
February 385.00000 21.51645 31.57608 -0.3778 11.42284
March 433.00000 23.04425 34.42489 0.06749 7.04122
April 410.00000 23.81607 38.52960 0.31567 8.60422
May 430.00000 24.31772 43.74403 -0.3450 9.37544
June 418.00000 24.47961 45.46563 -0.2241 7.41225
July 422.00000 24.65952 47.89100 -0.1376 7.18578
August 433.00000 24.54032 48.59317 -0.1747 6.99911
September 410.00000 24.31644 47.54696 -0.3277 9.06046
October 427.00000 23.36846 43.25196 0.21567 7.90778
November 417.00000 22.45604 34.82274 -0.0955 7.20531
December 422.00000 21.15981 33.59910 -0.4481 11.19430
           
Annual Sum or Average 5034.00000 23.20240 40.00113 -0.1802 9.07773
Minimum of Months 385.00000 20.63525 29.92422 -0.6406 6.99911
Maximum of Months 433.00000 24.65952 48.59317 0.31567 15.71462



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.54354 27.79247 -0.4041 12.54205
February 454.00000 22.10094 29.65583 -0.2224 10.07311
March 514.00000 23.27577 33.31994 0.13786 7.71709
April 485.00000 23.73600 38.56640 0.29868 8.44308
May 508.00000 24.09898 44.73846 -0.4357 10.13863
June 496.00000 24.28258 46.30110 -0.3234 8.03915
July 497.00000 24.45968 48.64226 -0.2366 7.15430
August 514.00000 24.41067 48.84479 -0.2242 6.95138
September 485.00000 24.26319 47.33874 -0.3287 8.91618
October 502.00000 23.61442 41.66069 0.30217 9.12883
November 489.00000 23.07578 32.22182 0.07301 8.01929
December 497.00000 22.05134 30.81479 -0.2186 9.43629
           
Annual Sum or Average 5943.00000 23.41915 39.23355 -0.1318 8.87020
Minimum of Months 454.00000 21.54354 27.79247 -0.4357 6.95138
Maximum of Months 514.00000 24.45968 48.84479 0.30217 12.54205



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.75641 30.05949 -0.6124 15.42269
February 454.00000 21.47013 31.70437 -0.3887 11.62683
March 514.00000 22.98067 34.90329 0.06341 7.52754
April 485.00000 23.73196 39.24640 0.30706 8.67623
May 508.00000 24.16914 44.76271 -0.3828 9.52449
June 496.00000 24.35115 46.24455 -0.2577 7.60991
July 497.00000 24.50003 48.73645 -0.1858 7.07392
August 514.00000 24.43926 49.06961 -0.1942 6.90483
September 485.00000 24.24308 48.07000 -0.3414 9.07206
October 502.00000 23.30270 43.78475 0.20791 7.92165
November 489.00000 22.40655 34.97848 -0.1033 7.58155
December 497.00000 21.23757 33.52323 -0.4330 11.19353
           
Annual Sum or Average 5943.00000 23.14510 40.49107 -0.1924 9.15747
Minimum of Months 454.00000 20.75641 30.05949 -0.6124 6.90483
Maximum of Months 514.00000 24.50003 49.06961 0.30706 15.42269



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.167731E+10 0.414378E+09 52.83 0.103141E+10 0.645905E+09 0.00 0.59 19-JAN-16:00 0.00 01-JAN-00:10 17583.41 19-JAN-16:00 13671.83 31-JAN-15:10 8679.91 19-JAN-16:00 4147.16 19-JAN-16:00 0.00
February 0.444469E+10 0.108354E+10 132.70 0.368649E+10 0.758200E+09 0.00 0.96 28-FEB-15:10 0.00 01-FEB-00:10 32000.80 28-FEB-15:10 32000.80 28-FEB-15:10 7001.13 18-FEB-16:30 6944.07 28-FEB-15:10 0.00
March 0.139129E+11 0.324525E+10 268.22 0.108823E+11 0.303062E+10 0.00 1.00 13-MAR-15:30 0.00 01-MAR-00:10 49156.38 30-MAR-15:20 49156.38 30-MAR-15:20 12411.94 29-MAR-09:00 11384.20 30-MAR-15:20 0.00
April 0.241872E+11 0.557027E+10 332.65 0.198645E+11 0.432271E+10 0.00 1.00 04-APR-10:05 0.00 01-APR-00:10 53990.79 17-APR-14:20 53990.79 17-APR-14:20 14968.20 04-APR-07:30 12893.81 17-APR-14:20 0.00
May 0.470530E+11 0.106332E+11 413.64 0.358614E+11 0.111917E+11 0.00 1.00 01-MAY-13:40 0.00 01-MAY-00:10 69665.67 30-MAY-15:00 56089.69 30-MAY-15:00 23962.63 23-MAY-06:03 17176.50 30-MAY-15:00 0.00
June 0.717438E+11 0.168923E+11 436.71 0.538424E+11 0.179013E+11 0.00 1.00 01-JUN-05:12 0.00 01-JUN-00:10 80061.54 26-JUN-14:30 71665.51 26-JUN-05:12 30198.38 29-JUN-06:03 19890.03 19-JUN-16:00 0.00
July 0.827166E+11 0.197011E+11 443.69 0.588094E+11 0.239072E+11 0.00 1.00 01-JUL-05:12 0.00 01-JUL-00:10 87461.74 07-JUL-12:05 67320.95 17-JUL-06:03 37230.72 26-JUL-06:03 23404.91 07-JUL-16:00 0.00
August 0.943440E+11 0.222225E+11 469.96 0.656504E+11 0.286936E+11 0.00 1.00 01-AUG-05:12 0.00 01-AUG-00:10 87447.73 15-AUG-06:03 74212.58 07-AUG-05:12 31958.48 29-AUG-06:03 23006.85 01-AUG-15:00 0.00
September 0.602471E+11 0.135790E+11 416.92 0.444608E+11 0.157862E+11 0.00 1.00 01-SEP-05:12 0.00 01-SEP-00:10 84160.05 07-SEP-16:00 64766.93 05-SEP-06:03 25934.01 06-SEP-12:03 21211.32 07-SEP-16:00 0.00
October 0.266344E+11 0.599001E+10 305.86 0.198820E+11 0.675238E+10 0.00 1.00 02-OCT-06:03 0.00 01-OCT-00:10 68591.09 10-OCT-15:50 56862.14 10-OCT-16:00 35243.36 02-OCT-06:03 16690.08 10-OCT-16:00 0.00
November 0.101836E+11 0.239304E+10 223.31 0.778658E+10 0.239706E+10 0.00 0.99 02-NOV-14:10 0.00 01-NOV-00:10 33649.48 03-NOV-15:00 28720.86 02-NOV-14:10 11278.23 02-NOV-10:40 7125.90 03-NOV-15:00 0.00
December 0.355990E+10 0.844131E+09 113.96 0.237277E+10 0.118713E+10 0.00 0.91 12-DEC-14:00 0.00 01-DEC-00:10 30052.16 12-DEC-14:00 23313.42 12-DEC-15:10 15066.03 13-DEC-16:00 6500.11 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.440705E+12 0.102569E+12 3610.46 0.324131E+12 0.116574E+12 0.00                         0.00
Minimum of Months 0.167731E+10 0.414378E+09 52.83 0.103141E+10 0.645905E+09 0.00 0.59   0.00   17583.41   13671.83   7001.13   4147.16   0.00
Maximum of Months 0.943440E+11 0.222225E+11 469.96 0.656504E+11 0.286936E+11 0.00 1.00   0.00   87461.74   74212.58   37230.72   23404.91   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.159176E+10 0.393152E+09 53.37 0.973453E+09 0.618309E+09 0.00 0.59 19-JAN-16:00 0.00 01-JAN-00:10 16682.00 19-JAN-16:00 11189.42 31-JAN-15:05 8230.84 19-JAN-16:00 3929.40 19-JAN-16:00 0.00
February 0.422054E+10 0.103512E+10 136.61 0.348363E+10 0.736902E+09 0.00 0.93 28-FEB-15:05 0.00 01-FEB-00:10 28889.30 28-FEB-15:05 28889.30 28-FEB-15:05 7151.82 18-FEB-16:00 6323.46 28-FEB-15:05 0.00
March 0.128808E+11 0.302495E+10 279.17 0.100511E+11 0.282969E+10 0.00 1.00 29-MAR-14:05 0.00 01-MAR-00:10 48503.24 30-MAR-15:20 48503.24 30-MAR-15:20 11373.36 30-MAR-10:00 11231.62 30-MAR-15:20 0.00
April 0.230100E+11 0.531353E+10 343.94 0.189673E+11 0.404268E+10 0.00 1.00 04-APR-12:05 0.00 01-APR-00:10 54031.56 17-APR-15:30 54031.56 17-APR-15:30 13714.56 21-APR-10:50 12901.29 17-APR-15:30 0.00
May 0.438601E+11 0.995993E+10 429.42 0.334486E+11 0.104116E+11 0.00 1.00 01-MAY-12:03 0.00 01-MAY-00:10 66133.26 30-MAY-14:05 53353.71 30-MAY-14:05 17373.90 31-MAY-13:00 16295.08 30-MAY-14:05 0.00
June 0.655444E+11 0.154306E+11 442.14 0.484133E+11 0.171311E+11 0.00 1.00 01-JUN-07:30 0.00 01-JUN-00:10 76392.85 26-JUN-14:05 68186.78 26-JUN-05:12 24584.33 23-JUN-10:05 18637.25 30-JUN-14:05 0.00
July 0.751332E+11 0.178473E+11 447.62 0.522207E+11 0.229125E+11 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 79567.38 07-JUL-12:02 68703.27 17-JUL-05:12 27484.78 26-JUL-10:40 21569.62 07-JUL-16:00 0.00
August 0.839364E+11 0.196978E+11 467.43 0.564790E+11 0.274574E+11 0.00 1.00 01-AUG-05:12 0.00 01-AUG-00:10 87117.64 21-AUG-06:03 67939.09 07-AUG-05:12 26416.35 24-AUG-14:05 21144.26 01-AUG-15:20 0.00
September 0.504726E+11 0.114404E+11 414.63 0.359543E+11 0.145183E+11 0.00 1.00 01-SEP-08:30 0.00 01-SEP-00:10 77823.92 06-SEP-14:05 55719.29 06-SEP-14:05 23186.43 16-SEP-13:00 19084.77 06-SEP-14:05 0.00
October 0.218047E+11 0.495676E+10 304.78 0.157330E+11 0.607172E+10 0.00 1.00 02-OCT-08:40 0.00 01-OCT-00:10 61061.95 11-OCT-14:05 47831.80 10-OCT-15:30 22752.49 18-OCT-15:00 14530.00 10-OCT-14:05 0.00
November 0.836477E+10 0.200020E+10 220.67 0.615345E+10 0.221133E+10 0.00 0.90 02-NOV-14:05 0.00 01-NOV-00:10 27677.67 02-NOV-14:05 22005.78 08-NOV-15:05 9905.65 27-NOV-18:00 6006.44 02-NOV-14:05 0.00
December 0.300950E+10 0.727473E+09 113.53 0.196385E+10 0.104565E+10 0.00 0.84 12-DEC-14:00 0.00 01-DEC-00:10 25640.72 12-DEC-14:00 18257.59 12-DEC-14:00 10001.77 13-DEC-15:05 5647.64 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.393829E+12 0.918272E+11 3653.31 0.283842E+12 0.109987E+12 0.00                         0.00
Minimum of Months 0.159176E+10 0.393152E+09 53.37 0.973453E+09 0.618309E+09 0.00 0.59   0.00   16682.00   11189.42   7151.82   3929.40   0.00
Maximum of Months 0.839364E+11 0.196978E+11 467.43 0.564790E+11 0.274574E+11 0.00 1.00   0.00   87117.64   68703.27   27484.78   21569.62   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.164393E+10 0.409224E+09 53.33 0.993971E+09 0.649956E+09 0.00 0.54 19-JAN-16:00 0.00 01-JAN-00:10 16914.01 19-JAN-16:00 11462.05 31-JAN-15:00 8370.34 19-JAN-16:00 4037.69 19-JAN-16:00 0.00
February 0.432094E+10 0.106893E+10 135.58 0.350378E+10 0.817164E+09 0.00 0.81 28-FEB-15:30 0.00 01-FEB-00:10 27339.87 28-FEB-15:30 27339.87 28-FEB-15:30 7209.73 18-FEB-16:00 6162.83 28-FEB-15:00 0.00
March 0.133792E+11 0.317156E+10 279.62 0.103114E+11 0.306786E+10 0.00 1.00 29-MAR-14:20 0.00 01-MAR-00:10 54019.68 30-MAR-15:20 54019.68 30-MAR-15:20 11346.90 28-MAR-13:00 12509.32 30-MAR-15:20 0.00
April 0.246039E+11 0.571851E+10 344.17 0.202531E+11 0.435081E+10 0.00 1.00 04-APR-13:05 0.00 01-APR-00:10 60406.53 17-APR-16:00 60406.53 17-APR-16:00 13767.68 21-APR-11:00 14423.78 17-APR-16:00 0.00
May 0.472397E+11 0.108075E+11 433.20 0.365716E+11 0.106681E+11 0.00 1.00 01-MAY-13:40 0.00 01-MAY-00:10 73808.43 30-MAY-15:00 61965.27 16-MAY-16:00 17429.91 31-MAY-13:00 18131.45 30-MAY-15:00 0.00
June 0.704143E+11 0.166783E+11 444.70 0.529568E+11 0.174575E+11 0.00 1.00 01-JUN-09:00 0.00 01-JUN-00:10 81927.81 26-JUN-15:00 76503.04 26-JUN-05:12 24319.17 23-JUN-10:40 20783.56 12-JUN-15:00 0.00
July 0.802623E+11 0.192046E+11 450.95 0.570548E+11 0.232075E+11 0.00 1.00 01-JUL-08:00 0.00 01-JUL-00:10 88027.98 07-JUL-16:00 70008.00 07-JUL-16:00 27477.68 26-JUL-10:50 24427.99 07-JUL-16:00 0.00
August 0.888859E+11 0.209897E+11 469.46 0.611369E+11 0.277490E+11 0.00 1.00 01-AUG-06:03 0.00 01-AUG-00:10 87621.59 01-AUG-15:00 71680.70 07-AUG-05:12 26039.75 24-AUG-14:00 23928.77 01-AUG-15:00 0.00
September 0.519296E+11 0.118759E+11 416.04 0.370236E+11 0.149060E+11 0.00 1.00 01-SEP-10:00 0.00 01-SEP-00:10 83991.59 06-SEP-14:00 63382.09 07-SEP-15:30 24048.98 16-SEP-13:40 20838.36 07-SEP-16:00 0.00
October 0.220299E+11 0.505991E+10 302.47 0.156982E+11 0.633168E+10 0.00 1.00 02-OCT-10:05 0.00 01-OCT-00:10 64338.74 10-OCT-14:20 52263.75 10-OCT-15:30 22797.15 18-OCT-15:00 15273.99 10-OCT-14:00 0.00
November 0.843414E+10 0.204175E+10 220.12 0.604262E+10 0.239152E+10 0.00 0.81 02-NOV-14:10 0.00 01-NOV-00:10 27609.82 02-NOV-14:00 19739.51 02-NOV-14:10 10274.02 27-NOV-18:00 6143.35 02-NOV-14:00 0.00
December 0.304626E+10 0.743797E+09 112.39 0.194442E+10 0.110184E+10 0.00 0.79 12-DEC-14:00 0.00 01-DEC-00:10 26800.92 12-DEC-14:00 18672.54 12-DEC-14:15 9647.65 13-DEC-11:10 5990.50 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.416190E+12 0.977696E+11 3662.05 0.303491E+12 0.112699E+12 0.00                         0.00
Minimum of Months 0.164393E+10 0.409224E+09 53.33 0.993971E+09 0.649956E+09 0.00 0.54   0.00   16914.01   11462.05   7209.73   4037.69   0.00
Maximum of Months 0.888859E+11 0.209897E+11 469.46 0.611369E+11 0.277490E+11 0.00 1.00   0.00   88027.98   76503.04   27477.68   24427.99   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 276.89 0.00 276.89 49.86 1679.51 0.00 0.00 0.00
February 306.91 0.00 306.91 146.21 1381.78 0.00 0.00 0.00
March 430.88 0.00 430.88 320.54 882.04 0.00 0.00 0.00
April 521.19 2.31 518.87 590.37 711.22 0.00 0.00 0.00
May 623.33 19.89 603.44 883.74 464.28 0.00 0.00 0.00
June 686.00 45.29 640.71 1249.39 294.76 0.00 0.00 0.00
July 647.25 31.46 615.78 1244.00 214.28 0.00 0.00 0.00
August 575.62 6.27 569.35 1135.49 177.53 0.00 0.00 0.00
September 435.11 0.06 435.05 660.21 391.73 0.00 0.00 0.00
October 330.83 0.00 330.83 310.92 806.37 0.00 0.00 0.00
November 296.08 0.00 296.08 179.39 1082.65 0.00 0.00 0.00
December 255.96 0.00 255.96 56.53 1354.76 0.00 0.00 0.00
                 
Annual Sum or Average 449.61 8.81 440.80 571.26 783.68 0.00 0.00 0.00
Minimum of Months 255.96 0.00 255.96 49.86 177.53 0.00 0.00 0.00
Maximum of Months 686.00 45.29 640.71 1249.39 1679.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 405.39 182.85 222.54 304.21 1004.41 0.00 0.00 0.00
February 511.07 274.59 236.48 515.77 834.95 0.00 0.00 0.00
March 642.99 292.71 350.28 748.37 550.35 0.00 0.00 0.00
April 777.54 354.54 423.00 1084.64 453.53 0.00 0.00 0.00
May 853.79 361.06 492.74 1314.16 309.26 0.00 0.00 0.00
June 883.96 370.49 513.47 1543.77 198.28 0.00 0.00 0.00
July 861.90 362.35 499.54 1552.06 144.85 0.00 0.00 0.00
August 788.35 312.77 475.59 1445.70 119.40 0.00 0.00 0.00
September 647.92 287.08 360.84 1037.56 255.96 0.00 0.00 0.00
October 552.73 287.60 265.13 723.96 507.22 0.00 0.00 0.00
November 441.91 200.10 241.82 462.61 658.44 0.00 0.00 0.00
December 382.78 174.49 208.29 311.72 811.95 0.00 0.00 0.00
                 
Annual Sum or Average 646.51 288.34 358.17 922.48 485.58 0.00 0.00 0.00
Minimum of Months 382.78 174.49 208.29 304.21 119.40 0.00 0.00 0.00
Maximum of Months 883.96 370.49 513.47 1552.06 1004.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1480.84 1032.44 448.40 1732.06 1421.92 0.00 0.00 0.00
February 1382.12 926.47 455.65 1750.28 1230.65 0.00 0.00 0.00
March 1242.99 647.78 595.22 1698.98 866.88 0.00 0.00 0.00
April 930.92 303.03 627.89 1404.69 735.86 0.00 0.00 0.00
May 752.14 87.42 664.73 1193.23 492.80 0.00 0.00 0.00
June 695.44 38.70 656.74 1305.59 313.75 0.00 0.00 0.00
July 703.07 52.43 650.65 1384.05 223.10 0.00 0.00 0.00
August 839.42 156.81 682.61 1685.64 185.83 0.00 0.00 0.00
September 923.15 343.37 579.79 1588.76 403.27 0.00 0.00 0.00
October 1338.31 866.96 471.35 2001.29 790.98 0.00 0.00 0.00
November 1439.78 955.42 484.37 1952.86 1009.57 0.00 0.00 0.00
December 1459.70 1026.91 432.79 1817.54 1200.62 0.00 0.00 0.00
                 
Annual Sum or Average 1097.78 534.66 563.12 1625.92 736.92 0.00 0.00 0.00
Minimum of Months 695.44 38.70 432.79 1193.23 185.83 0.00 0.00 0.00
Maximum of Months 1480.84 1032.44 682.61 2001.29 1421.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.39 193.15 223.24 346.51 1045.25 0.00 0.00 0.00
February 478.02 223.50 254.51 506.84 884.26 0.00 0.00 0.00
March 704.57 340.46 364.10 889.94 590.29 0.00 0.00 0.00
April 792.63 362.70 429.92 1139.45 490.04 0.00 0.00 0.00
May 796.61 301.81 494.81 1250.06 334.33 0.00 0.00 0.00
June 837.74 322.28 515.47 1480.01 217.21 0.00 0.00 0.00
July 790.18 292.97 497.21 1443.52 155.43 0.00 0.00 0.00
August 774.27 289.55 484.72 1430.73 131.44 0.00 0.00 0.00
September 630.82 262.76 368.05 1020.08 271.32 0.00 0.00 0.00
October 561.98 291.73 270.25 777.35 546.00 0.00 0.00 0.00
November 448.50 201.31 247.19 523.83 714.81 0.00 0.00 0.00
December 370.01 161.84 208.17 334.54 869.23 0.00 0.00 0.00
                 
Annual Sum or Average 634.27 270.54 363.73 930.81 518.88 0.00 0.00 0.00
Minimum of Months 370.01 161.84 208.17 334.54 131.44 0.00 0.00 0.00
Maximum of Months 837.74 362.70 515.47 1480.01 1045.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.29 0.00 92.29 15.63 589.25 0.00 0.00 0.00
February 102.30 0.00 102.30 50.18 476.35 0.00 0.00 0.00
March 143.62 0.00 143.62 115.03 292.11 0.00 0.00 0.00
April 173.72 0.77 172.95 212.42 224.83 0.00 0.00 0.00
May 207.77 6.63 201.14 307.75 146.26 0.00 0.00 0.00
June 228.66 15.10 213.56 425.75 94.41 0.00 0.00 0.00
July 215.74 10.49 205.25 423.02 68.48 0.00 0.00 0.00
August 191.86 2.09 189.77 383.89 58.05 0.00 0.00 0.00
September 145.03 0.02 145.01 219.33 140.97 0.00 0.00 0.00
October 110.27 0.00 110.27 98.03 300.45 0.00 0.00 0.00
November 98.69 0.00 98.69 51.33 405.18 0.00 0.00 0.00
December 85.32 0.00 85.32 16.25 499.63 0.00 0.00 0.00
                 
Annual Sum or Average 149.86 2.94 146.93 194.02 273.64 0.00 0.00 0.00
Minimum of Months 85.32 0.00 85.32 15.63 58.05 0.00 0.00 0.00
Maximum of Months 228.66 15.10 213.56 425.75 589.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.30 0.00 92.30 15.63 589.28 0.00 0.00 0.00
February 102.30 0.00 102.30 50.18 476.37 0.00 0.00 0.00
March 143.63 0.00 143.63 115.03 292.12 0.00 0.00 0.00
April 173.73 0.77 172.96 212.42 224.84 0.00 0.00 0.00
May 207.78 6.63 201.14 307.76 146.27 0.00 0.00 0.00
June 228.67 15.10 213.57 425.77 94.42 0.00 0.00 0.00
July 215.75 10.49 205.26 423.04 68.48 0.00 0.00 0.00
August 191.87 2.09 189.78 383.91 58.05 0.00 0.00 0.00
September 145.04 0.02 145.02 219.34 140.98 0.00 0.00 0.00
October 110.28 0.00 110.28 98.03 300.47 0.00 0.00 0.00
November 98.69 0.00 98.69 51.33 405.20 0.00 0.00 0.00
December 85.32 0.00 85.32 16.25 499.66 0.00 0.00 0.00
                 
Annual Sum or Average 149.87 2.94 146.93 194.03 273.66 0.00 0.00 0.00
Minimum of Months 85.32 0.00 85.32 15.63 58.05 0.00 0.00 0.00
Maximum of Months 228.67 15.10 213.57 425.77 589.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 92.30 0.00 92.30 15.63 589.28 0.00 0.00 0.00
February 102.30 0.00 102.30 50.18 476.37 0.00 0.00 0.00
March 143.63 0.00 143.63 115.03 292.12 0.00 0.00 0.00
April 173.73 0.77 172.96 212.42 224.84 0.00 0.00 0.00
May 207.78 6.63 201.14 307.76 146.27 0.00 0.00 0.00
June 228.67 15.10 213.57 425.77 94.42 0.00 0.00 0.00
July 215.75 10.49 205.26 423.04 68.48 0.00 0.00 0.00
August 191.87 2.09 189.78 383.91 58.05 0.00 0.00 0.00
September 145.04 0.02 145.02 219.34 140.98 0.00 0.00 0.00
October 110.28 0.00 110.28 98.03 300.47 0.00 0.00 0.00
November 98.69 0.00 98.69 51.33 405.20 0.00 0.00 0.00
December 85.32 0.00 85.32 16.25 499.66 0.00 0.00 0.00
                 
Annual Sum or Average 149.87 2.94 146.93 194.03 273.66 0.00 0.00 0.00
Minimum of Months 85.32 0.00 85.32 15.63 58.05 0.00 0.00 0.00
Maximum of Months 228.67 15.10 213.57 425.77 589.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 389.97 175.89 214.07 287.00 1026.15 0.00 0.00 0.00
February 491.62 264.15 227.48 498.23 841.85 0.00 0.00 0.00
March 618.52 281.57 336.95 733.86 540.49 0.00 0.00 0.00
April 747.95 341.04 406.91 1068.97 427.03 0.00 0.00 0.00
May 821.31 347.32 473.99 1288.50 290.72 0.00 0.00 0.00
June 850.33 356.39 493.94 1503.13 189.65 0.00 0.00 0.00
July 829.10 348.57 480.54 1508.75 140.07 0.00 0.00 0.00
August 758.36 300.87 457.49 1401.66 118.93 0.00 0.00 0.00
September 623.27 276.15 347.11 998.48 270.74 0.00 0.00 0.00
October 531.70 276.65 255.04 684.70 552.01 0.00 0.00 0.00
November 425.10 192.48 232.62 419.35 723.44 0.00 0.00 0.00
December 368.22 167.85 200.37 285.15 876.28 0.00 0.00 0.00
                 
Annual Sum or Average 621.91 277.36 344.54 891.85 498.03 0.00 0.00 0.00
Minimum of Months 368.22 167.85 200.37 285.15 118.93 0.00 0.00 0.00
Maximum of Months 850.33 356.39 493.94 1508.75 1026.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.42 6.95 8.46 11.35 40.57 0.00 0.00 0.00
February 19.44 10.44 8.99 19.70 33.29 0.00 0.00 0.00
March 24.46 11.13 13.32 29.02 21.37 0.00 0.00 0.00
April 29.57 13.48 16.09 42.27 16.88 0.00 0.00 0.00
May 32.47 13.73 18.74 50.95 11.49 0.00 0.00 0.00
June 33.62 14.09 19.53 59.43 7.50 0.00 0.00 0.00
July 32.78 13.78 19.00 59.65 5.54 0.00 0.00 0.00
August 29.98 11.90 18.09 55.42 4.70 0.00 0.00 0.00
September 24.64 10.92 13.72 39.48 10.70 0.00 0.00 0.00
October 21.02 10.94 10.08 27.07 21.83 0.00 0.00 0.00
November 16.81 7.61 9.20 16.58 28.60 0.00 0.00 0.00
December 14.56 6.64 7.92 11.27 34.65 0.00 0.00 0.00
                 
Annual Sum or Average 24.59 10.97 13.62 35.26 19.69 0.00 0.00 0.00
Minimum of Months 14.56 6.64 7.92 11.27 4.70 0.00 0.00 0.00
Maximum of Months 33.62 14.09 19.53 59.65 40.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 493.60 344.14 149.47 581.58 507.97 0.00 0.00 0.00
February 460.70 308.82 151.88 590.48 433.69 0.00 0.00 0.00
March 414.32 215.92 198.40 578.36 297.24 0.00 0.00 0.00
April 310.30 101.01 209.29 484.95 237.03 0.00 0.00 0.00
May 250.71 29.14 221.57 412.21 155.72 0.00 0.00 0.00
June 231.81 12.90 218.91 444.92 100.58 0.00 0.00 0.00
July 234.36 17.47 216.88 469.29 71.95 0.00 0.00 0.00
August 279.80 52.27 227.54 566.29 63.18 0.00 0.00 0.00
September 307.71 114.45 193.26 530.27 147.00 0.00 0.00 0.00
October 446.10 288.98 157.12 665.44 298.51 0.00 0.00 0.00
November 479.92 318.47 161.45 644.08 384.85 0.00 0.00 0.00
December 486.56 342.30 144.26 602.76 451.14 0.00 0.00 0.00
                 
Annual Sum or Average 365.92 178.21 187.71 547.44 261.49 0.00 0.00 0.00
Minimum of Months 231.81 12.90 144.26 412.21 63.18 0.00 0.00 0.00
Maximum of Months 493.60 344.14 227.54 665.44 507.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 493.60 344.14 149.47 581.58 507.97 0.00 0.00 0.00
February 460.70 308.82 151.88 590.48 433.69 0.00 0.00 0.00
March 414.32 215.92 198.40 578.36 297.24 0.00 0.00 0.00
April 310.30 101.01 209.29 484.95 237.03 0.00 0.00 0.00
May 250.71 29.14 221.57 412.21 155.72 0.00 0.00 0.00
June 231.81 12.90 218.91 444.92 100.58 0.00 0.00 0.00
July 234.36 17.47 216.88 469.29 71.95 0.00 0.00 0.00
August 279.80 52.27 227.54 566.29 63.18 0.00 0.00 0.00
September 307.71 114.45 193.26 530.27 147.00 0.00 0.00 0.00
October 446.10 288.98 157.12 665.44 298.51 0.00 0.00 0.00
November 479.92 318.47 161.45 644.08 384.85 0.00 0.00 0.00
December 486.56 342.30 144.26 602.76 451.14 0.00 0.00 0.00
                 
Annual Sum or Average 365.92 178.21 187.71 547.44 261.49 0.00 0.00 0.00
Minimum of Months 231.81 12.90 144.26 412.21 63.18 0.00 0.00 0.00
Maximum of Months 493.60 344.14 227.54 665.44 507.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 493.57 344.12 149.46 581.55 507.94 0.00 0.00 0.00
February 460.67 308.80 151.87 590.45 433.66 0.00 0.00 0.00
March 414.30 215.91 198.39 578.32 297.22 0.00 0.00 0.00
April 310.28 101.00 209.28 484.92 237.02 0.00 0.00 0.00
May 250.70 29.14 221.56 412.18 155.71 0.00 0.00 0.00
June 231.80 12.90 218.90 444.89 100.57 0.00 0.00 0.00
July 234.34 17.47 216.87 469.26 71.94 0.00 0.00 0.00
August 279.79 52.26 227.52 566.26 63.17 0.00 0.00 0.00
September 307.69 114.45 193.25 530.24 146.99 0.00 0.00 0.00
October 446.07 288.96 157.11 665.40 298.49 0.00 0.00 0.00
November 479.89 318.45 161.44 644.04 384.82 0.00 0.00 0.00
December 486.53 342.27 144.25 602.72 451.11 0.00 0.00 0.00
                 
Annual Sum or Average 365.90 178.20 187.69 547.40 261.47 0.00 0.00 0.00
Minimum of Months 231.80 12.90 144.25 412.18 63.17 0.00 0.00 0.00
Maximum of Months 493.57 344.12 227.52 665.40 507.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 400.55 185.80 214.75 334.20 1068.28 0.00 0.00 0.00
February 459.83 215.00 244.83 494.88 890.54 0.00 0.00 0.00
March 677.76 327.51 350.25 873.30 584.15 0.00 0.00 0.00
April 762.47 348.90 413.57 1123.30 466.44 0.00 0.00 0.00
May 766.30 290.32 475.98 1225.55 316.78 0.00 0.00 0.00
June 805.87 310.01 495.86 1442.67 209.31 0.00 0.00 0.00
July 760.12 281.83 478.29 1403.93 150.23 0.00 0.00 0.00
August 744.81 278.53 466.28 1386.84 131.27 0.00 0.00 0.00
September 606.82 252.76 354.05 981.85 287.54 0.00 0.00 0.00
October 540.60 280.63 259.97 739.88 596.74 0.00 0.00 0.00
November 431.44 193.65 237.79 487.23 783.62 0.00 0.00 0.00
December 355.93 155.69 200.25 314.49 932.88 0.00 0.00 0.00
                 
Annual Sum or Average 610.14 260.24 349.90 902.83 532.97 0.00 0.00 0.00
Minimum of Months 355.93 155.69 200.25 314.49 131.27 0.00 0.00 0.00
Maximum of Months 805.87 348.90 495.86 1442.67 1068.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.84 7.35 8.49 13.21 42.24 0.00 0.00 0.00
February 18.18 8.50 9.68 19.57 35.21 0.00 0.00 0.00
March 26.80 12.95 13.85 34.53 23.10 0.00 0.00 0.00
April 30.15 13.80 16.35 44.41 18.44 0.00 0.00 0.00
May 30.30 11.48 18.82 48.46 12.53 0.00 0.00 0.00
June 31.86 12.26 19.61 57.04 8.28 0.00 0.00 0.00
July 30.05 11.14 18.91 55.51 5.94 0.00 0.00 0.00
August 29.45 11.01 18.44 54.83 5.19 0.00 0.00 0.00
September 23.99 9.99 14.00 38.82 11.37 0.00 0.00 0.00
October 21.37 11.10 10.28 29.25 23.59 0.00 0.00 0.00
November 17.06 7.66 9.40 19.26 30.98 0.00 0.00 0.00
December 14.07 6.16 7.92 12.43 36.89 0.00 0.00 0.00
                 
Annual Sum or Average 24.12 10.29 13.83 35.70 21.07 0.00 0.00 0.00
Minimum of Months 14.07 6.16 7.92 12.43 5.19 0.00 0.00 0.00
Maximum of Months 31.86 13.80 19.61 57.04 42.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 276.89 0.00 276.89 44.45 1776.30 0.00 0.00 0.00
February 306.91 0.00 306.91 138.83 1463.28 0.00 0.00 0.00
March 430.88 0.00 430.88 307.69 942.11 0.00 0.00 0.00
April 521.19 2.31 518.87 584.62 745.98 0.00 0.00 0.00
May 623.33 19.89 603.44 884.82 480.98 0.00 0.00 0.00
June 686.00 45.29 640.71 1256.76 301.12 0.00 0.00 0.00
July 647.25 31.46 615.78 1254.19 217.35 0.00 0.00 0.00
August 575.62 6.27 569.35 1144.51 180.79 0.00 0.00 0.00
September 435.11 0.06 435.05 658.27 414.67 0.00 0.00 0.00
October 330.83 0.00 330.83 297.95 872.09 0.00 0.00 0.00
November 296.08 0.00 296.08 159.62 1177.59 0.00 0.00 0.00
December 255.96 0.00 255.96 48.34 1468.31 0.00 0.00 0.00
                 
Annual Sum or Average 449.61 8.81 440.80 567.41 833.50 0.00 0.00 0.00
Minimum of Months 255.96 0.00 255.96 44.45 180.79 0.00 0.00 0.00
Maximum of Months 686.00 45.29 640.71 1256.76 1776.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 405.39 182.85 222.54 291.54 1063.51 0.00 0.00 0.00
February 511.07 274.59 236.48 503.24 884.99 0.00 0.00 0.00
March 642.99 292.71 350.28 734.30 585.39 0.00 0.00 0.00
April 777.54 354.54 423.00 1077.79 472.76 0.00 0.00 0.00
May 853.79 361.06 492.74 1312.63 318.87 0.00 0.00 0.00
June 883.96 370.49 513.47 1545.79 202.37 0.00 0.00 0.00
July 861.90 362.35 499.54 1555.87 147.28 0.00 0.00 0.00
August 788.35 312.77 475.59 1448.70 121.90 0.00 0.00 0.00
September 647.92 287.08 360.84 1033.69 269.71 0.00 0.00 0.00
October 552.73 287.60 265.13 710.95 544.88 0.00 0.00 0.00
November 441.91 200.10 241.82 439.03 715.56 0.00 0.00 0.00
December 382.78 174.49 208.29 294.45 882.46 0.00 0.00 0.00
                 
Annual Sum or Average 646.51 288.34 358.17 914.47 515.57 0.00 0.00 0.00
Minimum of Months 382.78 174.49 208.29 291.54 121.90 0.00 0.00 0.00
Maximum of Months 883.96 370.49 513.47 1555.87 1063.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1480.84 1032.44 448.40 1709.93 1506.81 0.00 0.00 0.00
February 1382.12 926.47 455.65 1734.17 1303.95 0.00 0.00 0.00
March 1242.99 647.78 595.22 1687.05 920.37 0.00 0.00 0.00
April 930.92 303.03 627.89 1401.55 769.45 0.00 0.00 0.00
May 752.14 87.42 664.73 1196.59 510.71 0.00 0.00 0.00
June 695.44 38.70 656.74 1314.04 321.64 0.00 0.00 0.00
July 703.07 52.43 650.65 1394.67 227.11 0.00 0.00 0.00
August 839.42 156.81 682.61 1695.81 189.55 0.00 0.00 0.00
September 923.15 343.37 579.79 1589.00 424.66 0.00 0.00 0.00
October 1338.31 866.96 471.35 1990.54 847.19 0.00 0.00 0.00
November 1439.78 955.42 484.37 1927.54 1089.71 0.00 0.00 0.00
December 1459.70 1026.91 432.79 1791.82 1295.81 0.00 0.00 0.00
                 
Annual Sum or Average 1097.78 534.66 563.12 1619.12 781.09 0.00 0.00 0.00
Minimum of Months 695.44 38.70 432.79 1196.59 189.55 0.00 0.00 0.00
Maximum of Months 1480.84 1032.44 682.61 1990.54 1506.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.39 193.15 223.24 339.45 1106.42 0.00 0.00 0.00
February 478.02 223.50 254.51 501.01 936.96 0.00 0.00 0.00
March 704.57 340.46 364.10 883.22 629.03 0.00 0.00 0.00
April 792.63 362.70 429.92 1137.41 513.22 0.00 0.00 0.00
May 796.61 301.81 494.81 1252.79 346.54 0.00 0.00 0.00
June 837.74 322.28 515.47 1486.51 222.90 0.00 0.00 0.00
July 790.18 292.97 497.21 1450.69 158.24 0.00 0.00 0.00
August 774.27 289.55 484.72 1437.43 133.84 0.00 0.00 0.00
September 630.82 262.76 368.05 1020.01 286.11 0.00 0.00 0.00
October 561.98 291.73 270.25 770.62 588.07 0.00 0.00 0.00
November 448.50 201.31 247.19 510.40 774.79 0.00 0.00 0.00
December 370.01 161.84 208.17 325.17 940.19 0.00 0.00 0.00
                 
Annual Sum or Average 634.27 270.54 363.73 928.49 551.01 0.00 0.00 0.00
Minimum of Months 370.01 161.84 208.17 325.17 133.84 0.00 0.00 0.00
Maximum of Months 837.74 362.70 515.47 1486.51 1106.42 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.741621E+09 0.00 0.741621E+09 0.133534E+09 0.449840E+10
February 0.742465E+09 0.00 0.742465E+09 0.353720E+09 0.334280E+10
March 0.115406E+10 0.00 0.115406E+10 0.858536E+09 0.236245E+10
April 0.135092E+10 5991711.25 0.134492E+10 0.153025E+10 0.184348E+10
May 0.166953E+10 53282288.90 0.161625E+10 0.236702E+10 0.124352E+10
June 0.177812E+10 0.117398E+09 0.166072E+10 0.323841E+10 0.764019E+09
July 0.173358E+10 84270737.43 0.164931E+10 0.333192E+10 0.573932E+09
August 0.154174E+10 16794811.96 0.152494E+10 0.304130E+10 0.475487E+09
September 0.112781E+10 158764.78 0.112766E+10 0.171127E+10 0.101536E+10
October 0.886097E+09 0.00 0.886097E+09 0.832774E+09 0.215977E+10
November 0.767444E+09 0.00 0.767444E+09 0.464973E+09 0.280624E+10
December 0.685574E+09 0.00 0.685574E+09 0.151418E+09 0.362859E+10
           
Annual Sum or Average 0.141790E+11 0.277896E+09 0.139011E+11 0.180151E+11 0.247141E+11
Minimum of Months 0.685574E+09 0.00 0.685574E+09 0.133534E+09 0.475487E+09
Maximum of Months 0.177812E+10 0.117398E+09 0.166072E+10 0.333192E+10 0.449840E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108580E+10 0.489750E+09 0.596049E+09 0.814804E+09 0.269022E+10
February 0.123638E+10 0.664299E+09 0.572083E+09 0.124774E+10 0.201991E+10
March 0.172217E+10 0.783984E+09 0.938190E+09 0.200444E+10 0.147405E+10
April 0.201537E+10 0.918958E+09 0.109642E+10 0.281140E+10 0.117555E+10
May 0.228680E+10 0.967054E+09 0.131974E+10 0.351984E+10 0.828313E+09
June 0.229123E+10 0.960312E+09 0.133092E+10 0.400144E+10 0.513950E+09
July 0.230851E+10 0.970531E+09 0.133798E+10 0.415705E+10 0.387974E+09
August 0.211153E+10 0.837717E+09 0.127381E+10 0.387215E+10 0.319789E+09
September 0.167941E+10 0.744101E+09 0.935305E+09 0.268935E+10 0.663445E+09
October 0.148043E+10 0.770305E+09 0.710127E+09 0.193905E+10 0.135853E+10
November 0.114544E+10 0.518649E+09 0.626787E+09 0.119909E+10 0.170668E+10
December 0.102524E+10 0.467345E+09 0.557896E+09 0.834907E+09 0.217471E+10
           
Annual Sum or Average 0.203883E+11 0.909301E+10 0.112953E+11 0.290913E+11 0.153131E+11
Minimum of Months 0.102524E+10 0.467345E+09 0.557896E+09 0.814804E+09 0.319789E+09
Maximum of Months 0.230851E+10 0.970531E+09 0.133798E+10 0.415705E+10 0.269022E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.396629E+10 0.276528E+10 0.120100E+10 0.463915E+10 0.380846E+10
February 0.334363E+10 0.224132E+10 0.110230E+10 0.423429E+10 0.297719E+10
March 0.332924E+10 0.173500E+10 0.159423E+10 0.455055E+10 0.232184E+10
April 0.241294E+10 0.785465E+09 0.162748E+10 0.364095E+10 0.190735E+10
May 0.201454E+10 0.234145E+09 0.178040E+10 0.319596E+10 0.131991E+10
June 0.180257E+10 0.100306E+09 0.170227E+10 0.338408E+10 0.813242E+09
July 0.188311E+10 0.140416E+09 0.174270E+10 0.370705E+10 0.597549E+09
August 0.224830E+10 0.419991E+09 0.182831E+10 0.451482E+10 0.497717E+09
September 0.239282E+10 0.890004E+09 0.150281E+10 0.411807E+10 0.104527E+10
October 0.358453E+10 0.232207E+10 0.126247E+10 0.536027E+10 0.211857E+10
November 0.373191E+10 0.247644E+10 0.125548E+10 0.506181E+10 0.261681E+10
December 0.390966E+10 0.275048E+10 0.115918E+10 0.486811E+10 0.321574E+10
           
Annual Sum or Average 0.346195E+11 0.168609E+11 0.177586E+11 0.512751E+11 0.232397E+11
Minimum of Months 0.180257E+10 0.100306E+09 0.110230E+10 0.319596E+10 0.497717E+09
Maximum of Months 0.396629E+10 0.276528E+10 0.182831E+10 0.536027E+10 0.380846E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111527E+10 0.517339E+09 0.597928E+09 0.928079E+09 0.279960E+10
February 0.115642E+10 0.540695E+09 0.615722E+09 0.122614E+10 0.213921E+10
March 0.188712E+10 0.911897E+09 0.975218E+09 0.238362E+10 0.158104E+10
April 0.205449E+10 0.940125E+09 0.111436E+10 0.295346E+10 0.127018E+10
May 0.213365E+10 0.808356E+09 0.132529E+10 0.334816E+10 0.895468E+09
June 0.217143E+10 0.835339E+09 0.133609E+10 0.383618E+10 0.563014E+09
July 0.211643E+10 0.784700E+09 0.133173E+10 0.386632E+10 0.416314E+09
August 0.207380E+10 0.775518E+09 0.129828E+10 0.383206E+10 0.352059E+09
September 0.163508E+10 0.681080E+09 0.953995E+09 0.264404E+10 0.703260E+09
October 0.150521E+10 0.781371E+09 0.723842E+09 0.208205E+10 0.146240E+10
November 0.116252E+10 0.521798E+09 0.640720E+09 0.135776E+10 0.185280E+10
December 0.991039E+09 0.433482E+09 0.557557E+09 0.896025E+09 0.232815E+10
           
Annual Sum or Average 0.200024E+11 0.853170E+10 0.114707E+11 0.293539E+11 0.163635E+11
Minimum of Months 0.991039E+09 0.433482E+09 0.557557E+09 0.896025E+09 0.352059E+09
Maximum of Months 0.217143E+10 0.940125E+09 0.133609E+10 0.386632E+10 0.279960E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247195E+09 0.00 0.247195E+09 41857480.59 0.157824E+10
February 0.247477E+09 0.00 0.247477E+09 0.121385E+09 0.115237E+10
March 0.384670E+09 0.00 0.384670E+09 0.308097E+09 0.782376E+09
April 0.450284E+09 1997142.59 0.448287E+09 0.550580E+09 0.582756E+09
May 0.556484E+09 17759922.67 0.538724E+09 0.824272E+09 0.391741E+09
June 0.592679E+09 39130827.43 0.553548E+09 0.110354E+10 0.244722E+09
July 0.577834E+09 28088916.80 0.549745E+09 0.113303E+10 0.183405E+09
August 0.513888E+09 5598005.79 0.508290E+09 0.102821E+10 0.155476E+09
September 0.375920E+09 52919.09 0.375867E+09 0.568514E+09 0.365395E+09
October 0.295352E+09 0.00 0.295352E+09 0.262552E+09 0.804734E+09
November 0.255803E+09 0.00 0.255803E+09 0.133043E+09 0.105023E+10
December 0.228514E+09 0.00 0.228514E+09 43535784.92 0.133822E+10
           
Annual Sum or Average 0.472610E+10 92627734.38 0.463347E+10 0.611861E+10 0.862966E+10
Minimum of Months 0.228514E+09 0.00 0.228514E+09 41857480.59 0.155476E+09
Maximum of Months 0.592679E+09 39130827.43 0.553548E+09 0.113303E+10 0.157824E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247205E+09 0.00 0.247205E+09 41857891.39 0.157834E+10
February 0.247487E+09 0.00 0.247487E+09 0.121389E+09 0.115245E+10
March 0.384685E+09 0.00 0.384685E+09 0.308107E+09 0.782423E+09
April 0.450302E+09 1997196.27 0.448305E+09 0.550602E+09 0.582790E+09
May 0.556506E+09 17760400.06 0.538746E+09 0.824306E+09 0.391763E+09
June 0.592703E+09 39131879.28 0.553571E+09 0.110359E+10 0.244734E+09
July 0.577857E+09 28089671.84 0.549767E+09 0.113308E+10 0.183414E+09
August 0.513909E+09 5598156.26 0.508311E+09 0.102825E+10 0.155483E+09
September 0.375935E+09 52920.51 0.375882E+09 0.568538E+09 0.365414E+09
October 0.295364E+09 0.00 0.295364E+09 0.262562E+09 0.804782E+09
November 0.255813E+09 0.00 0.255813E+09 0.133046E+09 0.105029E+10
December 0.228523E+09 0.00 0.228523E+09 43535633.21 0.133830E+10
           
Annual Sum or Average 0.472629E+10 92630224.23 0.463366E+10 0.611887E+10 0.863018E+10
Minimum of Months 0.228523E+09 0.00 0.228523E+09 41857891.39 0.155483E+09
Maximum of Months 0.592703E+09 39131879.28 0.553571E+09 0.113308E+10 0.157834E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.247205E+09 0.00 0.247205E+09 41857891.39 0.157834E+10
February 0.247487E+09 0.00 0.247487E+09 0.121389E+09 0.115245E+10
March 0.384685E+09 0.00 0.384685E+09 0.308107E+09 0.782423E+09
April 0.450302E+09 1997196.27 0.448305E+09 0.550602E+09 0.582790E+09
May 0.556506E+09 17760400.06 0.538746E+09 0.824306E+09 0.391763E+09
June 0.592703E+09 39131879.28 0.553571E+09 0.110359E+10 0.244734E+09
July 0.577857E+09 28089671.84 0.549767E+09 0.113308E+10 0.183414E+09
August 0.513909E+09 5598156.26 0.508311E+09 0.102825E+10 0.155483E+09
September 0.375935E+09 52920.51 0.375882E+09 0.568538E+09 0.365414E+09
October 0.295364E+09 0.00 0.295364E+09 0.262562E+09 0.804782E+09
November 0.255813E+09 0.00 0.255813E+09 0.133046E+09 0.105029E+10
December 0.228523E+09 0.00 0.228523E+09 43535633.21 0.133830E+10
           
Annual Sum or Average 0.472629E+10 92630224.23 0.463366E+10 0.611887E+10 0.863018E+10
Minimum of Months 0.228523E+09 0.00 0.228523E+09 41857891.39 0.155483E+09
Maximum of Months 0.592703E+09 39131879.28 0.553571E+09 0.113308E+10 0.157834E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.104448E+10 0.471113E+09 0.573371E+09 0.768689E+09 0.274843E+10
February 0.118934E+10 0.639020E+09 0.550317E+09 0.120531E+10 0.203660E+10
March 0.165665E+10 0.754150E+09 0.902495E+09 0.196557E+10 0.144765E+10
April 0.193869E+10 0.883988E+09 0.105470E+10 0.277078E+10 0.110686E+10
May 0.219979E+10 0.930254E+09 0.126953E+10 0.345111E+10 0.778677E+09
June 0.220405E+10 0.923768E+09 0.128028E+10 0.389612E+10 0.491578E+09
July 0.222067E+10 0.933599E+09 0.128707E+10 0.404103E+10 0.375165E+09
August 0.203118E+10 0.805839E+09 0.122534E+10 0.375422E+10 0.318534E+09
September 0.161550E+10 0.715785E+09 0.899719E+09 0.258807E+10 0.701763E+09
October 0.142410E+10 0.740991E+09 0.683110E+09 0.183389E+10 0.147849E+10
November 0.110185E+10 0.498912E+09 0.602939E+09 0.108694E+10 0.187516E+10
December 0.986230E+09 0.449560E+09 0.536670E+09 0.763740E+09 0.234702E+10
           
Annual Sum or Average 0.196125E+11 0.874698E+10 0.108656E+11 0.281255E+11 0.157059E+11
Minimum of Months 0.986230E+09 0.449560E+09 0.536670E+09 0.763740E+09 0.318534E+09
Maximum of Months 0.222067E+10 0.933599E+09 0.128707E+10 0.404103E+10 0.274843E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41297968.64 18627401.67 22670566.97 30393278.02 0.108671E+09
February 47025321.95 25266263.70 21759058.25 47656731.28 80525353.48
March 65502272.49 29818417.68 35683854.81 77717006.05 57238931.46
April 76654026.86 34952094.60 41701932.26 0.109554E+09 43764313.64
May 86977579.04 36781404.46 50196174.57 0.136454E+09 30788191.58
June 87146182.83 36524961.51 50621221.33 0.154049E+09 19436561.15
July 87803420.16 36913651.60 50889768.56 0.159779E+09 14833669.13
August 80311103.59 31862138.09 48448965.50 0.148438E+09 12594535.31
September 63875563.18 28301493.83 35574069.35 0.102330E+09 27747095.57
October 56307668.25 29298132.82 27009535.43 72510302.08 58458278.74
November 43566232.40 19726548.35 23839684.04 42976724.71 74141968.65
December 38994650.79 17775203.84 21219446.95 30197604.17 92799138.74
           
Annual Sum or Average 0.775462E+09 0.345848E+09 0.429614E+09 0.111206E+10 0.620999E+09
Minimum of Months 38994650.79 17775203.84 21219446.95 30197604.17 12594535.31
Maximum of Months 87803420.16 36913651.60 50889768.56 0.159779E+09 0.108671E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132207E+10 0.921741E+09 0.400330E+09 0.155771E+10 0.136055E+10
February 0.111452E+10 0.747093E+09 0.367430E+09 0.142850E+10 0.104917E+10
March 0.110973E+10 0.578322E+09 0.531406E+09 0.154908E+10 0.796130E+09
April 0.804304E+09 0.261816E+09 0.542488E+09 0.125698E+10 0.614385E+09
May 0.671509E+09 78046639.51 0.593462E+09 0.110405E+10 0.417075E+09
June 0.600853E+09 33434677.84 0.567418E+09 0.115322E+10 0.260693E+09
July 0.627698E+09 46804225.75 0.580894E+09 0.125694E+10 0.192710E+09
August 0.749425E+09 0.139994E+09 0.609431E+09 0.151676E+10 0.169216E+09
September 0.797594E+09 0.296662E+09 0.500933E+09 0.137447E+10 0.381012E+09
October 0.119482E+10 0.774006E+09 0.420819E+09 0.178232E+10 0.799534E+09
November 0.124395E+10 0.825462E+09 0.418487E+09 0.166945E+10 0.997525E+09
December 0.130320E+10 0.916806E+09 0.386390E+09 0.161442E+10 0.120833E+10
           
Annual Sum or Average 0.115397E+11 0.562019E+10 0.591949E+10 0.172639E+11 0.824634E+10
Minimum of Months 0.600853E+09 33434677.84 0.367430E+09 0.110405E+10 0.169216E+09
Maximum of Months 0.132207E+10 0.921741E+09 0.609431E+09 0.178232E+10 0.136055E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132207E+10 0.921741E+09 0.400330E+09 0.155771E+10 0.136055E+10
February 0.111452E+10 0.747093E+09 0.367430E+09 0.142850E+10 0.104917E+10
March 0.110973E+10 0.578322E+09 0.531406E+09 0.154908E+10 0.796130E+09
April 0.804304E+09 0.261816E+09 0.542488E+09 0.125698E+10 0.614385E+09
May 0.671509E+09 78046639.51 0.593462E+09 0.110405E+10 0.417075E+09
June 0.600853E+09 33434677.84 0.567418E+09 0.115322E+10 0.260693E+09
July 0.627698E+09 46804225.75 0.580894E+09 0.125694E+10 0.192710E+09
August 0.749425E+09 0.139994E+09 0.609431E+09 0.151676E+10 0.169216E+09
September 0.797594E+09 0.296662E+09 0.500933E+09 0.137447E+10 0.381012E+09
October 0.119482E+10 0.774006E+09 0.420819E+09 0.178232E+10 0.799534E+09
November 0.124395E+10 0.825462E+09 0.418487E+09 0.166945E+10 0.997525E+09
December 0.130320E+10 0.916806E+09 0.386390E+09 0.161442E+10 0.120833E+10
           
Annual Sum or Average 0.115397E+11 0.562019E+10 0.591949E+10 0.172639E+11 0.824634E+10
Minimum of Months 0.600853E+09 33434677.84 0.367430E+09 0.110405E+10 0.169216E+09
Maximum of Months 0.132207E+10 0.921741E+09 0.609431E+09 0.178232E+10 0.136055E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.132199E+10 0.921683E+09 0.400305E+09 0.155761E+10 0.136047E+10
February 0.111445E+10 0.747046E+09 0.367407E+09 0.142841E+10 0.104911E+10
March 0.110966E+10 0.578285E+09 0.531372E+09 0.154898E+10 0.796080E+09
April 0.804253E+09 0.261800E+09 0.542454E+09 0.125691E+10 0.614346E+09
May 0.671466E+09 78041707.40 0.593424E+09 0.110398E+10 0.417049E+09
June 0.600815E+09 33432564.96 0.567382E+09 0.115315E+10 0.260676E+09
July 0.627659E+09 46801267.99 0.580857E+09 0.125686E+10 0.192697E+09
August 0.749378E+09 0.139985E+09 0.609393E+09 0.151667E+10 0.169205E+09
September 0.797544E+09 0.296643E+09 0.500901E+09 0.137438E+10 0.380988E+09
October 0.119475E+10 0.773957E+09 0.420792E+09 0.178221E+10 0.799484E+09
November 0.124387E+10 0.825410E+09 0.418461E+09 0.166935E+10 0.997462E+09
December 0.130311E+10 0.916748E+09 0.386365E+09 0.161432E+10 0.120826E+10
           
Annual Sum or Average 0.115389E+11 0.561983E+10 0.591911E+10 0.172628E+11 0.824582E+10
Minimum of Months 0.600815E+09 33432564.96 0.367407E+09 0.110398E+10 0.169205E+09
Maximum of Months 0.132199E+10 0.921683E+09 0.609393E+09 0.178221E+10 0.136047E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.107283E+10 0.497654E+09 0.575180E+09 0.895114E+09 0.286128E+10
February 0.111242E+10 0.520121E+09 0.592297E+09 0.119722E+10 0.215439E+10
March 0.181531E+10 0.877198E+09 0.938116E+09 0.233904E+10 0.156459E+10
April 0.197632E+10 0.904353E+09 0.107197E+10 0.291158E+10 0.120901E+10
May 0.205247E+10 0.777597E+09 0.127487E+10 0.328252E+10 0.848457E+09
June 0.208881E+10 0.803554E+09 0.128526E+10 0.373940E+10 0.542525E+09
July 0.203590E+10 0.754841E+09 0.128106E+10 0.376029E+10 0.402370E+09
August 0.199490E+10 0.746009E+09 0.124889E+10 0.371451E+10 0.351595E+09
September 0.157286E+10 0.655165E+09 0.917700E+09 0.254494E+10 0.745302E+09
October 0.144794E+10 0.751639E+09 0.696304E+09 0.198169E+10 0.159832E+10
November 0.111829E+10 0.501943E+09 0.616344E+09 0.126291E+10 0.203114E+10
December 0.953332E+09 0.416987E+09 0.536345E+09 0.842326E+09 0.249862E+10
           
Annual Sum or Average 0.192414E+11 0.820706E+10 0.110343E+11 0.284715E+11 0.168076E+11
Minimum of Months 0.953332E+09 0.416987E+09 0.536345E+09 0.842326E+09 0.351595E+09
Maximum of Months 0.208881E+10 0.904353E+09 0.128526E+10 0.376029E+10 0.286128E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42418767.26 19676731.62 22742035.64 35391856.49 0.113133E+09
February 43983894.94 20565053.16 23418841.78 47336871.58 85182602.97
March 71775721.37 34683525.60 37092195.77 92483188.46 61862605.75
April 78141703.59 35757173.75 42384529.84 0.115121E+09 47803307.39
May 81152613.96 30745385.62 50407228.33 0.129787E+09 33547203.82
June 82589595.18 31771686.60 50817908.58 0.147852E+09 21450943.60
July 80497582.55 29845636.76 50651945.78 0.148678E+09 15909319.05
August 78876146.14 29496422.79 49379723.36 0.146868E+09 13901710.17
September 62189492.73 25904536.92 36284955.81 0.100624E+09 29468558.31
October 57250228.41 29719041.32 27531187.09 78353924.69 63196154.86
November 44215952.03 19846317.65 24369634.38 49934173.01 80309445.70
December 37693793.36 16487250.69 21206542.66 33304677.61 98793271.23
           
Annual Sum or Average 0.760785E+09 0.324499E+09 0.436287E+09 0.112574E+10 0.664558E+09
Minimum of Months 37693793.36 16487250.69 21206542.66 33304677.61 13901710.17
Maximum of Months 82589595.18 35757173.75 50817908.58 0.148678E+09 0.113133E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.741621E+09 0.00 0.741621E+09 0.119057E+09 0.475765E+10
February 0.742465E+09 0.00 0.742465E+09 0.335859E+09 0.353998E+10
March 0.115406E+10 0.00 0.115406E+10 0.824111E+09 0.252335E+10
April 0.135092E+10 5991711.25 0.134492E+10 0.151533E+10 0.193359E+10
May 0.166953E+10 53282288.90 0.161625E+10 0.236991E+10 0.128825E+10
June 0.177812E+10 0.117398E+09 0.166072E+10 0.325752E+10 0.780492E+09
July 0.173358E+10 84270737.43 0.164931E+10 0.335923E+10 0.582161E+09
August 0.154174E+10 16794811.96 0.152494E+10 0.306547E+10 0.484229E+09
September 0.112781E+10 158764.78 0.112766E+10 0.170624E+10 0.107483E+10
October 0.886097E+09 0.00 0.886097E+09 0.798031E+09 0.233582E+10
November 0.767444E+09 0.00 0.767444E+09 0.413745E+09 0.305231E+10
December 0.685574E+09 0.00 0.685574E+09 0.129471E+09 0.393271E+10
           
Annual Sum or Average 0.141790E+11 0.277896E+09 0.139011E+11 0.178940E+11 0.262854E+11
Minimum of Months 0.685574E+09 0.00 0.685574E+09 0.119057E+09 0.484229E+09
Maximum of Months 0.177812E+10 0.117398E+09 0.166072E+10 0.335923E+10 0.475765E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.108580E+10 0.489750E+09 0.596049E+09 0.780848E+09 0.284850E+10
February 0.123638E+10 0.664299E+09 0.572083E+09 0.121744E+10 0.214096E+10
March 0.172217E+10 0.783984E+09 0.938190E+09 0.196675E+10 0.156791E+10
April 0.201537E+10 0.918958E+09 0.109642E+10 0.279363E+10 0.122539E+10
May 0.228680E+10 0.967054E+09 0.131974E+10 0.351575E+10 0.854062E+09
June 0.229123E+10 0.960312E+09 0.133092E+10 0.400670E+10 0.524533E+09
July 0.230851E+10 0.970531E+09 0.133798E+10 0.416724E+10 0.394480E+09
August 0.211153E+10 0.837717E+09 0.127381E+10 0.388019E+10 0.326508E+09
September 0.167941E+10 0.744101E+09 0.935305E+09 0.267933E+10 0.699097E+09
October 0.148043E+10 0.770305E+09 0.710127E+09 0.190420E+10 0.145940E+10
November 0.114544E+10 0.518649E+09 0.626787E+09 0.113796E+10 0.185472E+10
December 0.102524E+10 0.467345E+09 0.557896E+09 0.788659E+09 0.236359E+10
           
Annual Sum or Average 0.203883E+11 0.909301E+10 0.112953E+11 0.288387E+11 0.162592E+11
Minimum of Months 0.102524E+10 0.467345E+09 0.557896E+09 0.780848E+09 0.326508E+09
Maximum of Months 0.230851E+10 0.970531E+09 0.133798E+10 0.416724E+10 0.284850E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.396629E+10 0.276528E+10 0.120100E+10 0.457988E+10 0.403585E+10
February 0.334363E+10 0.224132E+10 0.110230E+10 0.419530E+10 0.315452E+10
March 0.332924E+10 0.173500E+10 0.159423E+10 0.451860E+10 0.246512E+10
April 0.241294E+10 0.785465E+09 0.162748E+10 0.363282E+10 0.199441E+10
May 0.201454E+10 0.234145E+09 0.178040E+10 0.320494E+10 0.136788E+10
June 0.180257E+10 0.100306E+09 0.170227E+10 0.340599E+10 0.833686E+09
July 0.188311E+10 0.140416E+09 0.174270E+10 0.373547E+10 0.608281E+09
August 0.224830E+10 0.419991E+09 0.182831E+10 0.454205E+10 0.507702E+09
September 0.239282E+10 0.890004E+09 0.150281E+10 0.411869E+10 0.110073E+10
October 0.358453E+10 0.232207E+10 0.126247E+10 0.533146E+10 0.226911E+10
November 0.373191E+10 0.247644E+10 0.125548E+10 0.499619E+10 0.282453E+10
December 0.390966E+10 0.275048E+10 0.115918E+10 0.479922E+10 0.347070E+10
           
Annual Sum or Average 0.346195E+11 0.168609E+11 0.177586E+11 0.510606E+11 0.246325E+11
Minimum of Months 0.180257E+10 0.100306E+09 0.110230E+10 0.320494E+10 0.507702E+09
Maximum of Months 0.396629E+10 0.276528E+10 0.182831E+10 0.533146E+10 0.403585E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111527E+10 0.517339E+09 0.597928E+09 0.909187E+09 0.296344E+10
February 0.115642E+10 0.540695E+09 0.615722E+09 0.121204E+10 0.226668E+10
March 0.188712E+10 0.911897E+09 0.975218E+09 0.236561E+10 0.168478E+10
April 0.205449E+10 0.940125E+09 0.111436E+10 0.294816E+10 0.133028E+10
May 0.213365E+10 0.808356E+09 0.132529E+10 0.335546E+10 0.928175E+09
June 0.217143E+10 0.835339E+09 0.133609E+10 0.385303E+10 0.577747E+09
July 0.211643E+10 0.784700E+09 0.133173E+10 0.388554E+10 0.423822E+09
August 0.207380E+10 0.775518E+09 0.129828E+10 0.385002E+10 0.358481E+09
September 0.163508E+10 0.681080E+09 0.953995E+09 0.264387E+10 0.741606E+09
October 0.150521E+10 0.781371E+09 0.723842E+09 0.206403E+10 0.157508E+10
November 0.116252E+10 0.521798E+09 0.640720E+09 0.132295E+10 0.200826E+10
December 0.991039E+09 0.433482E+09 0.557557E+09 0.870948E+09 0.251821E+10
           
Annual Sum or Average 0.200024E+11 0.853170E+10 0.114707E+11 0.292808E+11 0.173766E+11
Minimum of Months 0.991039E+09 0.433482E+09 0.557557E+09 0.870948E+09 0.358481E+09
Maximum of Months 0.217143E+10 0.940125E+09 0.133609E+10 0.388554E+10 0.296344E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 49.86 1679.51 276.89 0.00 276.89 0.00 0.00
February 146.21 1381.78 306.91 0.00 306.91 0.00 0.00
March 320.54 882.04 430.88 0.00 430.88 0.00 0.00
April 590.37 711.22 521.19 2.31 518.87 0.00 0.00
May 883.74 464.28 623.33 19.89 603.44 0.00 0.00
June 1249.39 294.76 686.00 45.29 640.71 0.00 0.00
July 1244.00 214.28 647.25 31.46 615.78 0.00 0.00
August 1135.49 177.53 575.62 6.27 569.35 0.00 0.00
September 660.21 391.73 435.11 0.06 435.05 0.00 0.00
October 310.92 806.37 330.83 0.00 330.83 0.00 0.00
November 179.39 1082.65 296.08 0.00 296.08 0.00 0.00
December 56.53 1354.76 255.96 0.00 255.96 0.00 0.00
               
Annual Sum or Average 571.26 783.68 449.61 8.81 440.80 0.00 0.00
Minimum of Months 49.86 177.53 255.96 0.00 255.96 0.00 0.00
Maximum of Months 1249.39 1679.51 686.00 45.29 640.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 304.21 1004.41 405.39 182.85 222.54 0.00 0.00
February 515.77 834.95 511.07 274.59 236.48 0.00 0.00
March 748.37 550.35 642.99 292.71 350.28 0.00 0.00
April 1084.64 453.53 777.54 354.54 423.00 0.00 0.00
May 1314.16 309.26 853.79 361.06 492.74 0.00 0.00
June 1543.77 198.28 883.96 370.49 513.47 0.00 0.00
July 1552.06 144.85 861.90 362.35 499.54 0.00 0.00
August 1445.70 119.40 788.35 312.77 475.59 0.00 0.00
September 1037.56 255.96 647.92 287.08 360.84 0.00 0.00
October 723.96 507.22 552.73 287.60 265.13 0.00 0.00
November 462.61 658.44 441.91 200.10 241.82 0.00 0.00
December 311.72 811.95 382.78 174.49 208.29 0.00 0.00
               
Annual Sum or Average 922.48 485.58 646.51 288.34 358.17 0.00 0.00
Minimum of Months 304.21 119.40 382.78 174.49 208.29 0.00 0.00
Maximum of Months 1552.06 1004.41 883.96 370.49 513.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1732.06 1421.92 1480.84 1032.44 448.40 0.00 0.00
February 1750.28 1230.65 1382.12 926.47 455.65 0.00 0.00
March 1698.98 866.88 1242.99 647.78 595.22 0.00 0.00
April 1404.69 735.86 930.92 303.03 627.89 0.00 0.00
May 1193.23 492.80 752.14 87.42 664.73 0.00 0.00
June 1305.59 313.75 695.44 38.70 656.74 0.00 0.00
July 1384.05 223.10 703.07 52.43 650.65 0.00 0.00
August 1685.64 185.83 839.42 156.81 682.61 0.00 0.00
September 1588.76 403.27 923.15 343.37 579.79 0.00 0.00
October 2001.29 790.98 1338.31 866.96 471.35 0.00 0.00
November 1952.86 1009.57 1439.78 955.42 484.37 0.00 0.00
December 1817.54 1200.62 1459.70 1026.91 432.79 0.00 0.00
               
Annual Sum or Average 1625.92 736.92 1097.78 534.66 563.12 0.00 0.00
Minimum of Months 1193.23 185.83 695.44 38.70 432.79 0.00 0.00
Maximum of Months 2001.29 1421.92 1480.84 1032.44 682.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 346.51 1045.25 416.39 193.15 223.24 0.00 0.00
February 506.84 884.26 478.02 223.50 254.51 0.00 0.00
March 889.94 590.29 704.57 340.46 364.10 0.00 0.00
April 1139.45 490.04 792.63 362.70 429.92 0.00 0.00
May 1250.06 334.33 796.61 301.81 494.81 0.00 0.00
June 1480.01 217.21 837.74 322.28 515.47 0.00 0.00
July 1443.52 155.43 790.18 292.97 497.21 0.00 0.00
August 1430.73 131.44 774.27 289.55 484.72 0.00 0.00
September 1020.08 271.32 630.82 262.76 368.05 0.00 0.00
October 777.35 546.00 561.98 291.73 270.25 0.00 0.00
November 523.83 714.81 448.50 201.31 247.19 0.00 0.00
December 334.54 869.23 370.01 161.84 208.17 0.00 0.00
               
Annual Sum or Average 930.81 518.88 634.27 270.54 363.73 0.00 0.00
Minimum of Months 334.54 131.44 370.01 161.84 208.17 0.00 0.00
Maximum of Months 1480.01 1045.25 837.74 362.70 515.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.88 1767.82 276.88 0.00 276.88 0.00 0.00
February 150.53 1429.09 306.90 0.00 306.90 0.00 0.00
March 345.10 876.35 430.87 0.00 430.87 0.00 0.00
April 637.26 674.51 521.18 2.31 518.86 0.00 0.00
May 923.27 438.79 623.32 19.89 603.43 0.00 0.00
June 1277.28 283.25 685.99 45.29 640.70 0.00 0.00
July 1269.11 205.43 647.23 31.46 615.77 0.00 0.00
August 1151.70 174.15 575.61 6.27 569.34 0.00 0.00
September 658.02 422.93 435.10 0.06 435.04 0.00 0.00
October 294.08 901.40 330.82 0.00 330.82 0.00 0.00
November 153.99 1215.59 296.08 0.00 296.08 0.00 0.00
December 48.76 1498.96 255.96 0.00 255.96 0.00 0.00
               
Annual Sum or Average 582.08 820.97 449.60 8.81 440.79 0.00 0.00
Minimum of Months 46.88 174.15 255.96 0.00 255.96 0.00 0.00
Maximum of Months 1277.28 1767.82 685.99 45.29 640.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 298.34 1066.72 405.38 182.85 222.54 0.00 0.00
February 517.92 875.13 511.06 274.59 236.47 0.00 0.00
March 762.88 561.86 642.98 292.70 350.28 0.00 0.00
April 1111.24 443.91 777.52 354.53 423.00 0.00 0.00
May 1339.44 302.22 853.78 361.05 492.73 0.00 0.00
June 1562.57 197.15 883.95 370.48 513.47 0.00 0.00
July 1568.40 145.61 861.89 362.35 499.54 0.00 0.00
August 1457.08 123.63 788.34 312.76 475.58 0.00 0.00
September 1037.96 281.45 647.91 287.07 360.84 0.00 0.00
October 711.77 573.83 552.72 287.59 265.13 0.00 0.00
November 435.93 752.04 441.91 200.09 241.81 0.00 0.00
December 296.42 910.92 382.78 174.48 208.29 0.00 0.00
               
Annual Sum or Average 927.12 517.72 646.50 288.33 358.17 0.00 0.00
Minimum of Months 296.42 123.63 382.78 174.48 208.29 0.00 0.00
Maximum of Months 1568.40 1066.72 883.95 370.48 513.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1744.71 1523.88 1480.78 1032.39 448.39 0.00 0.00
February 1771.42 1301.03 1382.07 926.44 455.63 0.00 0.00
March 1735.04 891.70 1242.95 647.75 595.20 0.00 0.00
April 1454.81 711.08 930.89 303.02 627.87 0.00 0.00
May 1236.59 467.14 752.12 87.42 664.71 0.00 0.00
June 1334.72 301.72 695.42 38.70 656.72 0.00 0.00
July 1407.83 215.84 703.05 52.42 650.63 0.00 0.00
August 1698.85 189.53 839.39 156.80 682.59 0.00 0.00
September 1590.78 440.98 923.12 343.35 579.77 0.00 0.00
October 1996.28 895.52 1338.26 866.92 471.34 0.00 0.00
November 1932.20 1154.52 1439.73 955.38 484.35 0.00 0.00
December 1808.23 1353.39 1459.64 1026.87 432.78 0.00 0.00
               
Annual Sum or Average 1642.27 784.45 1097.74 534.63 563.11 0.00 0.00
Minimum of Months 1236.59 189.53 695.42 38.70 432.78 0.00 0.00
Maximum of Months 1996.28 1523.88 1480.78 1032.39 682.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 347.41 1110.52 416.39 193.15 223.24 0.00 0.00
February 514.45 925.75 478.01 223.50 254.51 0.00 0.00
March 907.83 607.25 704.56 340.46 364.10 0.00 0.00
April 1167.71 484.88 792.62 362.70 429.92 0.00 0.00
May 1274.01 329.30 796.60 301.80 494.80 0.00 0.00
June 1499.71 217.58 837.73 322.27 515.46 0.00 0.00
July 1459.44 156.17 790.17 292.97 497.21 0.00 0.00
August 1441.67 136.46 774.26 289.54 484.72 0.00 0.00
September 1020.67 298.91 630.81 262.76 368.05 0.00 0.00
October 769.13 620.34 561.97 291.73 270.25 0.00 0.00
November 506.50 814.60 448.50 201.31 247.19 0.00 0.00
December 326.92 969.76 370.01 161.84 208.17 0.00 0.00
               
Annual Sum or Average 938.52 554.04 634.27 270.53 363.73 0.00 0.00
Minimum of Months 326.92 136.46 370.01 161.84 208.17 0.00 0.00
Maximum of Months 1499.71 1110.52 837.73 362.70 515.46 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 44.45 1776.30 276.89 0.00 276.89 0.00 0.00
February 138.83 1463.28 306.91 0.00 306.91 0.00 0.00
March 307.69 942.11 430.88 0.00 430.88 0.00 0.00
April 584.62 745.98 521.19 2.31 518.87 0.00 0.00
May 884.82 480.98 623.33 19.89 603.44 0.00 0.00
June 1256.76 301.12 686.00 45.29 640.71 0.00 0.00
July 1254.19 217.35 647.25 31.46 615.78 0.00 0.00
August 1144.51 180.79 575.62 6.27 569.35 0.00 0.00
September 658.27 414.67 435.11 0.06 435.05 0.00 0.00
October 297.95 872.09 330.83 0.00 330.83 0.00 0.00
November 159.62 1177.59 296.08 0.00 296.08 0.00 0.00
December 48.34 1468.31 255.96 0.00 255.96 0.00 0.00
               
Annual Sum or Average 567.41 833.50 449.61 8.81 440.80 0.00 0.00
Minimum of Months 44.45 180.79 255.96 0.00 255.96 0.00 0.00
Maximum of Months 1256.76 1776.30 686.00 45.29 640.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 291.54 1063.51 405.39 182.85 222.54 0.00 0.00
February 503.24 884.99 511.07 274.59 236.48 0.00 0.00
March 734.30 585.39 642.99 292.71 350.28 0.00 0.00
April 1077.79 472.76 777.54 354.54 423.00 0.00 0.00
May 1312.63 318.87 853.79 361.06 492.74 0.00 0.00
June 1545.79 202.37 883.96 370.49 513.47 0.00 0.00
July 1555.87 147.28 861.90 362.35 499.54 0.00 0.00
August 1448.70 121.90 788.35 312.77 475.59 0.00 0.00
September 1033.69 269.71 647.92 287.08 360.84 0.00 0.00
October 710.95 544.88 552.73 287.60 265.13 0.00 0.00
November 439.03 715.56 441.91 200.10 241.82 0.00 0.00
December 294.45 882.46 382.78 174.49 208.29 0.00 0.00
               
Annual Sum or Average 914.47 515.57 646.51 288.34 358.17 0.00 0.00
Minimum of Months 291.54 121.90 382.78 174.49 208.29 0.00 0.00
Maximum of Months 1555.87 1063.51 883.96 370.49 513.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1709.93 1506.81 1480.84 1032.44 448.40 0.00 0.00
February 1734.17 1303.95 1382.12 926.47 455.65 0.00 0.00
March 1687.05 920.37 1242.99 647.78 595.22 0.00 0.00
April 1401.55 769.45 930.92 303.03 627.89 0.00 0.00
May 1196.59 510.71 752.14 87.42 664.73 0.00 0.00
June 1314.04 321.64 695.44 38.70 656.74 0.00 0.00
July 1394.67 227.11 703.07 52.43 650.65 0.00 0.00
August 1695.81 189.55 839.42 156.81 682.61 0.00 0.00
September 1589.00 424.66 923.15 343.37 579.79 0.00 0.00
October 1990.54 847.19 1338.31 866.96 471.35 0.00 0.00
November 1927.54 1089.71 1439.78 955.42 484.37 0.00 0.00
December 1791.82 1295.81 1459.70 1026.91 432.79 0.00 0.00
               
Annual Sum or Average 1619.12 781.09 1097.78 534.66 563.12 0.00 0.00
Minimum of Months 1196.59 189.55 695.44 38.70 432.79 0.00 0.00
Maximum of Months 1990.54 1506.81 1480.84 1032.44 682.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 339.45 1106.42 416.39 193.15 223.24 0.00 0.00
February 501.01 936.96 478.02 223.50 254.51 0.00 0.00
March 883.22 629.03 704.57 340.46 364.10 0.00 0.00
April 1137.41 513.22 792.63 362.70 429.92 0.00 0.00
May 1252.79 346.54 796.61 301.81 494.81 0.00 0.00
June 1486.51 222.90 837.74 322.28 515.47 0.00 0.00
July 1450.69 158.24 790.18 292.97 497.21 0.00 0.00
August 1437.43 133.84 774.27 289.55 484.72 0.00 0.00
September 1020.01 286.11 630.82 262.76 368.05 0.00 0.00
October 770.62 588.07 561.98 291.73 270.25 0.00 0.00
November 510.40 774.79 448.50 201.31 247.19 0.00 0.00
December 325.17 940.19 370.01 161.84 208.17 0.00 0.00
               
Annual Sum or Average 928.49 551.01 634.27 270.54 363.73 0.00 0.00
Minimum of Months 325.17 133.84 370.01 161.84 208.17 0.00 0.00
Maximum of Months 1486.51 1106.42 837.74 362.70 515.47 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.133534E+09 0.449840E+10 0.741621E+09 0.00 0.741621E+09 0.00 0.00
February 0.353720E+09 0.334280E+10 0.742465E+09 0.00 0.742465E+09 0.00 0.00
March 0.858536E+09 0.236245E+10 0.115406E+10 0.00 0.115406E+10 0.00 0.00
April 0.153025E+10 0.184348E+10 0.135092E+10 5991711.25 0.134492E+10 0.00 0.00
May 0.236702E+10 0.124352E+10 0.166953E+10 53282288.90 0.161625E+10 0.00 0.00
June 0.323841E+10 0.764019E+09 0.177812E+10 0.117398E+09 0.166072E+10 0.00 0.00
July 0.333192E+10 0.573932E+09 0.173358E+10 84270737.43 0.164931E+10 0.00 0.00
August 0.304130E+10 0.475487E+09 0.154174E+10 16794811.96 0.152494E+10 0.00 0.00
September 0.171127E+10 0.101536E+10 0.112781E+10 158764.78 0.112766E+10 0.00 0.00
October 0.832774E+09 0.215977E+10 0.886097E+09 0.00 0.886097E+09 0.00 0.00
November 0.464973E+09 0.280624E+10 0.767444E+09 0.00 0.767444E+09 0.00 0.00
December 0.151418E+09 0.362859E+10 0.685574E+09 0.00 0.685574E+09 0.00 0.00
               
Annual Sum or Average 0.180151E+11 0.247141E+11 0.141790E+11 0.277896E+09 0.139011E+11 0.00 0.00
Minimum of Months 0.133534E+09 0.475487E+09 0.685574E+09 0.00 0.685574E+09 0.00 0.00
Maximum of Months 0.333192E+10 0.449840E+10 0.177812E+10 0.117398E+09 0.166072E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.814804E+09 0.269022E+10 0.108580E+10 0.489750E+09 0.596049E+09 0.00 0.00
February 0.124774E+10 0.201991E+10 0.123638E+10 0.664299E+09 0.572083E+09 0.00 0.00
March 0.200444E+10 0.147405E+10 0.172217E+10 0.783984E+09 0.938190E+09 0.00 0.00
April 0.281140E+10 0.117555E+10 0.201537E+10 0.918958E+09 0.109642E+10 0.00 0.00
May 0.351984E+10 0.828313E+09 0.228680E+10 0.967054E+09 0.131974E+10 0.00 0.00
June 0.400144E+10 0.513950E+09 0.229123E+10 0.960312E+09 0.133092E+10 0.00 0.00
July 0.415705E+10 0.387974E+09 0.230851E+10 0.970531E+09 0.133798E+10 0.00 0.00
August 0.387215E+10 0.319789E+09 0.211153E+10 0.837717E+09 0.127381E+10 0.00 0.00
September 0.268935E+10 0.663445E+09 0.167941E+10 0.744101E+09 0.935305E+09 0.00 0.00
October 0.193905E+10 0.135853E+10 0.148043E+10 0.770305E+09 0.710127E+09 0.00 0.00
November 0.119909E+10 0.170668E+10 0.114544E+10 0.518649E+09 0.626787E+09 0.00 0.00
December 0.834907E+09 0.217471E+10 0.102524E+10 0.467345E+09 0.557896E+09 0.00 0.00
               
Annual Sum or Average 0.290913E+11 0.153131E+11 0.203883E+11 0.909301E+10 0.112953E+11 0.00 0.00
Minimum of Months 0.814804E+09 0.319789E+09 0.102524E+10 0.467345E+09 0.557896E+09 0.00 0.00
Maximum of Months 0.415705E+10 0.269022E+10 0.230851E+10 0.970531E+09 0.133798E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.463915E+10 0.380846E+10 0.396629E+10 0.276528E+10 0.120100E+10 0.00 0.00
February 0.423429E+10 0.297719E+10 0.334363E+10 0.224132E+10 0.110230E+10 0.00 0.00
March 0.455055E+10 0.232184E+10 0.332924E+10 0.173500E+10 0.159423E+10 0.00 0.00
April 0.364095E+10 0.190735E+10 0.241294E+10 0.785465E+09 0.162748E+10 0.00 0.00
May 0.319596E+10 0.131991E+10 0.201454E+10 0.234145E+09 0.178040E+10 0.00 0.00
June 0.338408E+10 0.813242E+09 0.180257E+10 0.100306E+09 0.170227E+10 0.00 0.00
July 0.370705E+10 0.597549E+09 0.188311E+10 0.140416E+09 0.174270E+10 0.00 0.00
August 0.451482E+10 0.497717E+09 0.224830E+10 0.419991E+09 0.182831E+10 0.00 0.00
September 0.411807E+10 0.104527E+10 0.239282E+10 0.890004E+09 0.150281E+10 0.00 0.00
October 0.536027E+10 0.211857E+10 0.358453E+10 0.232207E+10 0.126247E+10 0.00 0.00
November 0.506181E+10 0.261681E+10 0.373191E+10 0.247644E+10 0.125548E+10 0.00 0.00
December 0.486811E+10 0.321574E+10 0.390966E+10 0.275048E+10 0.115918E+10 0.00 0.00
               
Annual Sum or Average 0.512751E+11 0.232397E+11 0.346195E+11 0.168609E+11 0.177586E+11 0.00 0.00
Minimum of Months 0.319596E+10 0.497717E+09 0.180257E+10 0.100306E+09 0.110230E+10 0.00 0.00
Maximum of Months 0.536027E+10 0.380846E+10 0.396629E+10 0.276528E+10 0.182831E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.928079E+09 0.279960E+10 0.111527E+10 0.517339E+09 0.597928E+09 0.00 0.00
February 0.122614E+10 0.213921E+10 0.115642E+10 0.540695E+09 0.615722E+09 0.00 0.00
March 0.238362E+10 0.158104E+10 0.188712E+10 0.911897E+09 0.975218E+09 0.00 0.00
April 0.295346E+10 0.127018E+10 0.205449E+10 0.940125E+09 0.111436E+10 0.00 0.00
May 0.334816E+10 0.895468E+09 0.213365E+10 0.808356E+09 0.132529E+10 0.00 0.00
June 0.383618E+10 0.563014E+09 0.217143E+10 0.835339E+09 0.133609E+10 0.00 0.00
July 0.386632E+10 0.416314E+09 0.211643E+10 0.784700E+09 0.133173E+10 0.00 0.00
August 0.383206E+10 0.352059E+09 0.207380E+10 0.775518E+09 0.129828E+10 0.00 0.00
September 0.264404E+10 0.703260E+09 0.163508E+10 0.681080E+09 0.953995E+09 0.00 0.00
October 0.208205E+10 0.146240E+10 0.150521E+10 0.781371E+09 0.723842E+09 0.00 0.00
November 0.135776E+10 0.185280E+10 0.116252E+10 0.521798E+09 0.640720E+09 0.00 0.00
December 0.896025E+09 0.232815E+10 0.991039E+09 0.433482E+09 0.557557E+09 0.00 0.00
               
Annual Sum or Average 0.293539E+11 0.163635E+11 0.200024E+11 0.853170E+10 0.114707E+11 0.00 0.00
Minimum of Months 0.896025E+09 0.352059E+09 0.991039E+09 0.433482E+09 0.557557E+09 0.00 0.00
Maximum of Months 0.386632E+10 0.279960E+10 0.217143E+10 0.940125E+09 0.133609E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.125573E+09 0.473492E+10 0.741606E+09 0.00 0.741606E+09 0.00 0.00
February 0.364163E+09 0.345727E+10 0.742450E+09 0.00 0.742450E+09 0.00 0.00
March 0.924310E+09 0.234722E+10 0.115404E+10 0.00 0.115404E+10 0.00 0.00
April 0.165178E+10 0.174834E+10 0.135089E+10 5991535.14 0.134490E+10 0.00 0.00
May 0.247288E+10 0.117527E+10 0.166950E+10 53280722.79 0.161622E+10 0.00 0.00
June 0.331072E+10 0.734191E+09 0.177808E+10 0.117395E+09 0.166069E+10 0.00 0.00
July 0.339919E+10 0.550233E+09 0.173355E+10 84268260.49 0.164928E+10 0.00 0.00
August 0.308472E+10 0.466442E+09 0.154171E+10 16794318.31 0.152491E+10 0.00 0.00
September 0.170559E+10 0.109622E+10 0.112779E+10 158760.12 0.112763E+10 0.00 0.00
October 0.787675E+09 0.241430E+10 0.886080E+09 0.00 0.886080E+09 0.00 0.00
November 0.399134E+09 0.315081E+10 0.767428E+09 0.00 0.767428E+09 0.00 0.00
December 0.130607E+09 0.401482E+10 0.685560E+09 0.00 0.685560E+09 0.00 0.00
               
Annual Sum or Average 0.183563E+11 0.258900E+11 0.141787E+11 0.277888E+09 0.139008E+11 0.00 0.00
Minimum of Months 0.125573E+09 0.466442E+09 0.685560E+09 0.00 0.685560E+09 0.00 0.00
Maximum of Months 0.339919E+10 0.473492E+10 0.177808E+10 0.117395E+09 0.166069E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.799082E+09 0.285710E+10 0.108578E+10 0.489741E+09 0.596041E+09 0.00 0.00
February 0.125296E+10 0.211713E+10 0.123636E+10 0.664286E+09 0.572077E+09 0.00 0.00
March 0.204329E+10 0.150489E+10 0.172215E+10 0.783969E+09 0.938179E+09 0.00 0.00
April 0.288033E+10 0.115063E+10 0.201534E+10 0.918940E+09 0.109640E+10 0.00 0.00
May 0.358756E+10 0.809465E+09 0.228676E+10 0.967035E+09 0.131973E+10 0.00 0.00
June 0.405017E+10 0.511015E+09 0.229120E+10 0.960293E+09 0.133090E+10 0.00 0.00
July 0.420081E+10 0.389998E+09 0.230848E+10 0.970512E+09 0.133796E+10 0.00 0.00
August 0.390265E+10 0.331128E+09 0.211149E+10 0.837701E+09 0.127379E+10 0.00 0.00
September 0.269040E+10 0.729511E+09 0.167938E+10 0.744086E+09 0.935293E+09 0.00 0.00
October 0.190640E+10 0.153695E+10 0.148041E+10 0.770290E+09 0.710119E+09 0.00 0.00
November 0.112992E+10 0.194930E+10 0.114542E+10 0.518639E+09 0.626779E+09 0.00 0.00
December 0.793938E+09 0.243982E+10 0.102522E+10 0.467335E+09 0.557889E+09 0.00 0.00
               
Annual Sum or Average 0.292375E+11 0.163269E+11 0.203880E+11 0.909283E+10 0.112952E+11 0.00 0.00
Minimum of Months 0.793938E+09 0.331128E+09 0.102522E+10 0.467335E+09 0.557889E+09 0.00 0.00
Maximum of Months 0.420081E+10 0.285710E+10 0.230848E+10 0.970512E+09 0.133796E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.467303E+10 0.408157E+10 0.396613E+10 0.276517E+10 0.120096E+10 0.00 0.00
February 0.428541E+10 0.314745E+10 0.334350E+10 0.224123E+10 0.110227E+10 0.00 0.00
March 0.464714E+10 0.238834E+10 0.332911E+10 0.173493E+10 0.159418E+10 0.00 0.00
April 0.377087E+10 0.184312E+10 0.241286E+10 0.785432E+09 0.162743E+10 0.00 0.00
May 0.331209E+10 0.125120E+10 0.201448E+10 0.234135E+09 0.178035E+10 0.00 0.00
June 0.345959E+10 0.782062E+09 0.180252E+10 0.100302E+09 0.170222E+10 0.00 0.00
July 0.377074E+10 0.578117E+09 0.188306E+10 0.140410E+09 0.174265E+10 0.00 0.00
August 0.455019E+10 0.507637E+09 0.224823E+10 0.419973E+09 0.182826E+10 0.00 0.00
September 0.412331E+10 0.114301E+10 0.239273E+10 0.889967E+09 0.150277E+10 0.00 0.00
October 0.534684E+10 0.239855E+10 0.358440E+10 0.232197E+10 0.126243E+10 0.00 0.00
November 0.500825E+10 0.299251E+10 0.373177E+10 0.247633E+10 0.125544E+10 0.00 0.00
December 0.484317E+10 0.362493E+10 0.390951E+10 0.275036E+10 0.115915E+10 0.00 0.00
               
Annual Sum or Average 0.517906E+11 0.247385E+11 0.346183E+11 0.168602E+11 0.177581E+11 0.00 0.00
Minimum of Months 0.331209E+10 0.507637E+09 0.180252E+10 0.100302E+09 0.110227E+10 0.00 0.00
Maximum of Months 0.534684E+10 0.408157E+10 0.396613E+10 0.276517E+10 0.182826E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.930506E+09 0.297442E+10 0.111525E+10 0.517331E+09 0.597922E+09 0.00 0.00
February 0.124456E+10 0.223957E+10 0.115640E+10 0.540686E+09 0.615716E+09 0.00 0.00
March 0.243152E+10 0.162646E+10 0.188709E+10 0.911882E+09 0.975209E+09 0.00 0.00
April 0.302670E+10 0.125682E+10 0.205446E+10 0.940110E+09 0.111435E+10 0.00 0.00
May 0.341231E+10 0.882004E+09 0.213362E+10 0.808342E+09 0.132528E+10 0.00 0.00
June 0.388725E+10 0.563976E+09 0.217140E+10 0.835325E+09 0.133608E+10 0.00 0.00
July 0.390897E+10 0.418279E+09 0.211640E+10 0.784687E+09 0.133171E+10 0.00 0.00
August 0.386138E+10 0.365496E+09 0.207377E+10 0.775505E+09 0.129827E+10 0.00 0.00
September 0.264557E+10 0.774771E+09 0.163505E+10 0.681069E+09 0.953985E+09 0.00 0.00
October 0.206004E+10 0.166152E+10 0.150519E+10 0.781358E+09 0.723836E+09 0.00 0.00
November 0.131284E+10 0.211145E+10 0.116250E+10 0.521790E+09 0.640714E+09 0.00 0.00
December 0.875631E+09 0.259742E+10 0.991026E+09 0.433475E+09 0.557551E+09 0.00 0.00
               
Annual Sum or Average 0.295973E+11 0.174722E+11 0.200022E+11 0.853156E+10 0.114706E+11 0.00 0.00
Minimum of Months 0.875631E+09 0.365496E+09 0.991026E+09 0.433475E+09 0.557551E+09 0.00 0.00
Maximum of Months 0.390897E+10 0.297442E+10 0.217140E+10 0.940110E+09 0.133608E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.119057E+09 0.475765E+10 0.741621E+09 0.00 0.741621E+09 0.00 0.00
February 0.335859E+09 0.353998E+10 0.742465E+09 0.00 0.742465E+09 0.00 0.00
March 0.824111E+09 0.252335E+10 0.115406E+10 0.00 0.115406E+10 0.00 0.00
April 0.151533E+10 0.193359E+10 0.135092E+10 5991711.25 0.134492E+10 0.00 0.00
May 0.236991E+10 0.128825E+10 0.166953E+10 53282288.90 0.161625E+10 0.00 0.00
June 0.325752E+10 0.780492E+09 0.177812E+10 0.117398E+09 0.166072E+10 0.00 0.00
July 0.335923E+10 0.582161E+09 0.173358E+10 84270737.43 0.164931E+10 0.00 0.00
August 0.306547E+10 0.484229E+09 0.154174E+10 16794811.96 0.152494E+10 0.00 0.00
September 0.170624E+10 0.107483E+10 0.112781E+10 158764.78 0.112766E+10 0.00 0.00
October 0.798031E+09 0.233582E+10 0.886097E+09 0.00 0.886097E+09 0.00 0.00
November 0.413745E+09 0.305231E+10 0.767444E+09 0.00 0.767444E+09 0.00 0.00
December 0.129471E+09 0.393271E+10 0.685574E+09 0.00 0.685574E+09 0.00 0.00
               
Annual Sum or Average 0.178940E+11 0.262854E+11 0.141790E+11 0.277896E+09 0.139011E+11 0.00 0.00
Minimum of Months 0.119057E+09 0.484229E+09 0.685574E+09 0.00 0.685574E+09 0.00 0.00
Maximum of Months 0.335923E+10 0.475765E+10 0.177812E+10 0.117398E+09 0.166072E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.780848E+09 0.284850E+10 0.108580E+10 0.489750E+09 0.596049E+09 0.00 0.00
February 0.121744E+10 0.214096E+10 0.123638E+10 0.664299E+09 0.572083E+09 0.00 0.00
March 0.196675E+10 0.156791E+10 0.172217E+10 0.783984E+09 0.938190E+09 0.00 0.00
April 0.279363E+10 0.122539E+10 0.201537E+10 0.918958E+09 0.109642E+10 0.00 0.00
May 0.351575E+10 0.854062E+09 0.228680E+10 0.967054E+09 0.131974E+10 0.00 0.00
June 0.400670E+10 0.524533E+09 0.229123E+10 0.960312E+09 0.133092E+10 0.00 0.00
July 0.416724E+10 0.394480E+09 0.230851E+10 0.970531E+09 0.133798E+10 0.00 0.00
August 0.388019E+10 0.326508E+09 0.211153E+10 0.837717E+09 0.127381E+10 0.00 0.00
September 0.267933E+10 0.699097E+09 0.167941E+10 0.744101E+09 0.935305E+09 0.00 0.00
October 0.190420E+10 0.145940E+10 0.148043E+10 0.770305E+09 0.710127E+09 0.00 0.00
November 0.113796E+10 0.185472E+10 0.114544E+10 0.518649E+09 0.626787E+09 0.00 0.00
December 0.788659E+09 0.236359E+10 0.102524E+10 0.467345E+09 0.557896E+09 0.00 0.00
               
Annual Sum or Average 0.288387E+11 0.162592E+11 0.203883E+11 0.909301E+10 0.112953E+11 0.00 0.00
Minimum of Months 0.780848E+09 0.326508E+09 0.102524E+10 0.467345E+09 0.557896E+09 0.00 0.00
Maximum of Months 0.416724E+10 0.284850E+10 0.230851E+10 0.970531E+09 0.133798E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.457988E+10 0.403585E+10 0.396629E+10 0.276528E+10 0.120100E+10 0.00 0.00
February 0.419530E+10 0.315452E+10 0.334363E+10 0.224132E+10 0.110230E+10 0.00 0.00
March 0.451860E+10 0.246512E+10 0.332924E+10 0.173500E+10 0.159423E+10 0.00 0.00
April 0.363282E+10 0.199441E+10 0.241294E+10 0.785465E+09 0.162748E+10 0.00 0.00
May 0.320494E+10 0.136788E+10 0.201454E+10 0.234145E+09 0.178040E+10 0.00 0.00
June 0.340599E+10 0.833686E+09 0.180257E+10 0.100306E+09 0.170227E+10 0.00 0.00
July 0.373547E+10 0.608281E+09 0.188311E+10 0.140416E+09 0.174270E+10 0.00 0.00
August 0.454205E+10 0.507702E+09 0.224830E+10 0.419991E+09 0.182831E+10 0.00 0.00
September 0.411869E+10 0.110073E+10 0.239282E+10 0.890004E+09 0.150281E+10 0.00 0.00
October 0.533146E+10 0.226911E+10 0.358453E+10 0.232207E+10 0.126247E+10 0.00 0.00
November 0.499619E+10 0.282453E+10 0.373191E+10 0.247644E+10 0.125548E+10 0.00 0.00
December 0.479922E+10 0.347070E+10 0.390966E+10 0.275048E+10 0.115918E+10 0.00 0.00
               
Annual Sum or Average 0.510606E+11 0.246325E+11 0.346195E+11 0.168609E+11 0.177586E+11 0.00 0.00
Minimum of Months 0.320494E+10 0.507702E+09 0.180257E+10 0.100306E+09 0.110230E+10 0.00 0.00
Maximum of Months 0.533146E+10 0.403585E+10 0.396629E+10 0.276528E+10 0.182831E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.909187E+09 0.296344E+10 0.111527E+10 0.517339E+09 0.597928E+09 0.00 0.00
February 0.121204E+10 0.226668E+10 0.115642E+10 0.540695E+09 0.615722E+09 0.00 0.00
March 0.236561E+10 0.168478E+10 0.188712E+10 0.911897E+09 0.975218E+09 0.00 0.00
April 0.294816E+10 0.133028E+10 0.205449E+10 0.940125E+09 0.111436E+10 0.00 0.00
May 0.335546E+10 0.928175E+09 0.213365E+10 0.808356E+09 0.132529E+10 0.00 0.00
June 0.385303E+10 0.577747E+09 0.217143E+10 0.835339E+09 0.133609E+10 0.00 0.00
July 0.388554E+10 0.423822E+09 0.211643E+10 0.784700E+09 0.133173E+10 0.00 0.00
August 0.385002E+10 0.358481E+09 0.207380E+10 0.775518E+09 0.129828E+10 0.00 0.00
September 0.264387E+10 0.741606E+09 0.163508E+10 0.681080E+09 0.953995E+09 0.00 0.00
October 0.206403E+10 0.157508E+10 0.150521E+10 0.781371E+09 0.723842E+09 0.00 0.00
November 0.132295E+10 0.200826E+10 0.116252E+10 0.521798E+09 0.640720E+09 0.00 0.00
December 0.870948E+09 0.251821E+10 0.991039E+09 0.433482E+09 0.557557E+09 0.00 0.00
               
Annual Sum or Average 0.292808E+11 0.173766E+11 0.200024E+11 0.853170E+10 0.114707E+11 0.00 0.00
Minimum of Months 0.870948E+09 0.358481E+09 0.991039E+09 0.433482E+09 0.557557E+09 0.00 0.00
Maximum of Months 0.388554E+10 0.296344E+10 0.217143E+10 0.940125E+09 0.133609E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.461469E+10 -0.436950E+10 0.00 0.00 744.00 0.00 -245190759.6 60.05 0.00 0.00
February 0.419690E+10 -0.397953E+10 0.00 0.00 672.00 0.00 -217377724.9 60.05 0.00 0.00
March 0.478968E+10 -0.455481E+10 0.00 0.00 744.00 0.00 -234877478.4 60.05 0.00 0.00
April 0.406892E+10 -0.384332E+10 0.00 0.00 720.00 0.00 -225601177.7 60.05 0.00 0.00
May 0.403265E+10 -0.380052E+10 0.00 0.00 744.00 0.00 -232125268.7 60.05 0.00 0.00
June 0.370654E+10 -0.348189E+10 0.00 0.00 720.00 0.00 -224647057.0 60.05 0.00 0.00
July 0.334706E+10 -0.311564E+10 0.00 0.00 744.00 0.00 -231423689.7 60.05 0.00 0.00
August 0.366739E+10 -0.343530E+10 0.00 0.00 744.00 0.00 -232089637.7 60.05 0.00 0.00
September 0.346319E+10 -0.323908E+10 0.00 0.00 720.00 0.00 -224111171.5 60.05 0.00 0.00
October 0.384531E+10 -0.361240E+10 0.00 0.00 744.00 0.00 -232903744.8 60.05 0.00 0.00
November 0.408673E+10 -0.385962E+10 0.00 0.00 720.00 0.00 -227110899.6 60.05 0.00 0.00
December 0.432555E+10 -0.408649E+10 0.00 0.00 744.00 0.00 -239062078.6 60.05 0.00 0.00
                     
Annual Sum or Average 0.481446E+11 -0.453781E+11 0.00 0.00 8760.00 0.00 -0.276652E+10 60.05 0.00 0.00
Minimum of Months 0.334706E+10 -0.455481E+10 0.00 0.00 672.00 0.00 -245190759.6 60.05 0.00 0.00
Maximum of Months 0.478968E+10 -0.311564E+10 0.00 0.00 744.00 0.00 -217377724.9 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.50 0.48 01-JAN-09:09 5920.38 33.55 265.83 271.17 1650.66 25.57 177.00 250.00
February 263.00 0.51 0.48 01-FEB-10:30 6934.78 33.58 230.83 246.83 1105.41 19.24 74.17 210.83
March 351.67 0.51 0.48 01-MAR-08:39 1633.21 18.11 6.83 317.67 957.68 20.20 123.00 283.00
April 369.33 0.51 0.48 01-APR-08:20 1344.75 17.74 0.00 324.00 770.22 19.89 103.50 279.83
May 407.00 0.51 0.48 01-MAY-07:40 1215.20 17.92 0.00 357.83 681.12 20.08 88.50 310.33
June 411.67 0.51 0.48 01-JUN-06:00 1129.01 17.67 0.00 358.33 638.99 19.83 89.50 310.67
July 411.00 0.51 0.48 01-JUL-07:19 1190.49 17.84 0.00 362.33 665.84 19.97 116.50 312.50
August 390.50 0.51 0.48 01-AUG-07:10 1455.23 18.47 0.00 349.17 798.32 20.59 173.00 311.33
September 298.50 0.51 0.48 01-SEP-07:30 1557.93 18.58 6.50 307.67 877.00 20.45 120.83 268.00
October 293.50 0.50 0.48 01-OCT-08:20 2820.72 23.84 119.17 291.83 1066.59 19.62 82.67 254.83
November 299.00 0.50 0.48 01-NOV-08:20 5827.00 34.49 285.50 272.50 1198.31 24.23 166.50 252.67
December 285.17 0.49 0.48 01-DEC-07:00 5579.70 34.34 269.83 267.67 1592.15 26.53 179.17 245.17
                         
Annual Sum or Average 4071.00 0.51     2765.65 22.91 1184.50 3727.00 959.12 21.18 1494.33 3289.17
Minimum of Months 263.00 0.49 0.48   1129.01 17.67 0.00 246.83 638.99 19.24 74.17 210.83
Maximum of Months 411.67 0.51 0.48   6934.78 34.49 285.50 362.33 1650.66 26.53 179.17 312.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-08:00 1397.54 19.11 71.83 240.67 712.40 19.97 55.00 178.00
February 263.00 0.53 0.48 01-FEB-10:30 1855.92 18.92 60.17 222.50 1026.20 21.06 50.00 176.67
March 351.67 0.51 0.48 01-MAR-08:39 2233.61 20.54 105.50 309.50 877.58 20.09 47.50 266.67
April 369.33 0.51 0.48 01-APR-07:00 2150.98 19.95 93.33 324.50 1159.31 21.17 67.17 287.17
May 407.00 0.50 0.48 01-MAY-06:00 2452.55 20.31 108.50 366.17 1014.10 20.19 50.00 327.17
June 411.67 0.51 0.48 01-JUN-06:19 2476.13 20.23 110.50 368.17 1037.98 20.90 64.00 332.00
July 411.00 0.51 0.48 01-JUL-05:00 2450.90 20.27 105.50 371.67 1038.64 20.27 51.83 330.50
August 390.50 0.51 0.48 01-AUG-06:30 2246.61 20.62 102.17 350.33 1185.56 21.91 73.50 313.00
September 298.50 0.51 0.48 01-SEP-06:00 2074.68 19.38 67.33 302.83 1118.49 21.63 55.33 259.00
October 293.50 0.52 0.48 01-OCT-07:49 2480.84 20.86 90.67 267.17 925.34 19.91 43.67 214.00
November 299.00 0.52 0.48 01-NOV-08:09 1694.77 21.16 97.00 246.83 915.18 21.99 75.50 200.33
December 285.17 0.52 0.48 01-DEC-07:49 1434.68 19.72 73.17 236.17 768.26 21.40 60.00 176.83
                         
Annual Sum or Average 4071.00 0.51     2122.25 20.13 1085.67 3606.50 992.83 20.86 693.50 3061.33
Minimum of Months 263.00 0.50 0.48   1397.54 18.92 60.17 222.50 712.40 19.91 43.67 176.67
Maximum of Months 411.67 0.53 0.48   2480.84 21.16 110.50 371.67 1185.56 21.99 75.50 332.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-10:50 498.44 14.33 0.00 211.17 301.36 16.73 0.00 87.17
February 263.00 0.55 0.48 01-FEB-13:39 529.36 14.53 0.00 190.00 329.03 16.88 0.00 110.67
March 351.67 0.52 0.48 01-MAR-08:00 675.39 16.35 0.00 299.33 412.09 18.56 0.00 225.83
April 369.33 0.51 0.48 01-APR-08:30 806.72 17.26 0.00 327.83 483.64 19.37 0.67 270.50
May 407.00 0.50 0.48 01-MAY-07:30 1008.63 20.32 51.83 382.33 581.94 20.46 65.17 341.83
June 411.67 0.49 0.48 01-JUN-06:40 1097.26 21.04 66.83 385.17 645.83 23.05 176.50 363.33
July 411.00 0.50 0.48 01-JUL-06:10 1105.58 20.47 53.33 384.83 615.06 21.44 145.00 348.33
August 390.50 0.50 0.48 01-AUG-06:00 986.07 18.22 0.00 359.17 575.97 20.30 52.50 324.83
September 298.50 0.52 0.48 01-SEP-07:30 749.92 17.07 0.00 302.50 454.78 19.17 0.00 218.83
October 293.50 0.54 0.48 01-OCT-10:39 553.98 15.06 0.00 236.33 354.52 17.45 0.00 142.67
November 299.00 0.55 0.48 01-NOV-09:50 515.74 14.64 0.00 224.00 313.81 16.98 0.00 120.33
December 285.17 0.55 0.48 01-DEC-09:30 481.59 14.41 0.00 203.00 292.19 16.85 0.00 80.83
                         
Annual Sum or Average 4071.00 0.52     785.86 17.33 172.00 3505.67 465.50 19.23 439.83 2635.17
Minimum of Months 263.00 0.49 0.48   481.59 14.33 0.00 190.00 292.19 16.73 0.00 80.83
Maximum of Months 411.67 0.55 0.48   1105.58 21.04 66.83 385.17 645.83 23.05 176.50 363.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-10:39 1717.65 21.12 89.67 243.33 951.84 21.82 68.00 190.67
February 263.00 0.53 0.48 01-FEB-13:39 1641.64 18.88 64.00 214.00 853.54 19.70 40.33 165.00
March 351.67 0.51 0.48 01-MAR-09:20 2213.33 20.88 98.17 309.33 1177.37 21.79 72.00 265.67
April 369.33 0.51 0.48 01-APR-09:00 2359.32 18.66 78.67 330.50 1299.47 20.02 51.83 288.67
May 407.00 0.50 0.48 01-MAY-07:00 2358.91 17.03 50.83 364.00 1004.51 18.01 0.00 325.50
June 411.67 0.51 0.48 01-JUN-07:30 2480.11 14.70 1.67 367.50 1061.85 17.97 0.00 330.67
July 411.00 0.51 0.48 01-JUL-07:30 2461.49 17.01 52.00 367.17 1039.12 18.01 0.00 327.50
August 390.50 0.50 0.48 01-AUG-07:30 2413.60 19.51 89.00 352.67 1053.24 18.70 7.67 318.83
September 298.50 0.51 0.48 01-SEP-08:09 2166.48 21.46 90.83 305.00 1144.91 22.22 62.67 256.50
October 293.50 0.52 0.48 01-OCT-10:39 2341.93 20.89 92.67 262.33 899.11 19.97 42.83 209.17
November 299.00 0.52 0.48 01-NOV-09:39 1590.18 19.46 80.83 248.00 854.44 21.74 68.33 199.00
December 285.17 0.52 0.48 01-DEC-09:20 1388.01 19.35 74.17 236.50 754.13 21.33 63.33 177.33
                         
Annual Sum or Average 4071.00 0.51     2142.30 18.87 862.50 3600.33 1020.79 19.92 477.00 3054.50
Minimum of Months 263.00 0.50 0.48   1388.01 14.70 1.67 214.00 754.13 17.97 0.00 165.00
Maximum of Months 411.67 0.53 0.48   2480.11 21.46 98.17 367.50 1299.47 22.22 72.00 330.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.50 0.48 01-JAN-09:09 5799.80 33.11 258.00 269.83 1555.30 23.28 103.33 248.83
February 263.00 0.51 0.48 01-FEB-10:30 6826.34 33.21 229.50 245.67 1055.84 18.03 25.83 213.83
March 351.67 0.51 0.48 01-MAR-08:39 1546.96 14.21 6.67 314.67 893.23 17.61 0.33 278.67
April 369.33 0.51 0.48 01-APR-08:30 1284.74 14.00 0.00 321.00 728.96 17.50 0.00 276.83
May 407.00 0.51 0.48 01-MAY-07:40 1167.83 14.24 0.00 355.67 651.76 17.72 0.00 307.17
June 411.67 0.51 0.48 01-JUN-07:10 1086.73 14.05 0.00 356.17 613.77 17.52 0.00 306.33
July 411.00 0.51 0.48 01-JUL-07:19 1144.77 14.23 0.00 358.83 638.15 17.66 0.00 308.17
August 390.50 0.51 0.48 01-AUG-07:19 1395.04 14.84 0.00 347.17 759.70 18.27 0.00 307.00
September 298.50 0.51 0.48 01-SEP-07:30 1484.19 14.97 6.50 304.83 825.43 18.10 0.00 265.17
October 293.50 0.50 0.48 01-OCT-10:39 2717.02 21.23 117.33 290.17 984.16 16.84 2.00 250.83
November 299.00 0.51 0.48 01-NOV-08:20 5713.98 34.08 281.17 271.67 1111.17 21.75 82.17 249.33
December 285.17 0.50 0.48 01-DEC-07:00 5407.84 32.28 249.33 263.67 1495.07 24.33 116.17 242.67
                         
Annual Sum or Average 4071.00 0.51     2684.52 20.10 1148.50 3699.33 904.89 18.86 329.83 3254.83
Minimum of Months 263.00 0.50 0.48   1086.73 14.00 0.00 245.67 613.77 16.84 0.00 213.83
Maximum of Months 411.67 0.51 0.48   6826.34 34.08 281.17 358.83 1555.30 24.33 116.17 308.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-09:09 1358.32 18.61 71.33 238.67 681.94 19.72 48.67 171.33
February 263.00 0.53 0.48 01-FEB-10:30 1806.26 18.42 60.17 219.17 985.15 20.85 48.50 173.33
March 351.67 0.51 0.48 01-MAR-08:39 2182.55 20.07 105.33 307.50 836.12 19.88 47.33 262.17
April 369.33 0.51 0.48 01-APR-07:00 2090.24 19.48 93.00 322.50 1111.38 20.99 67.17 283.17
May 407.00 0.51 0.48 01-MAY-06:00 2381.81 19.85 108.33 363.17 963.64 20.02 50.17 323.17
June 411.67 0.51 0.48 01-JUN-06:19 2412.05 19.78 110.33 365.50 988.18 20.74 64.00 329.00
July 411.00 0.51 0.48 01-JUL-05:00 2383.04 19.82 105.33 368.83 987.46 20.10 51.83 328.00
August 390.50 0.51 0.48 01-AUG-06:30 2175.50 20.16 102.17 348.67 1136.05 21.73 73.50 309.17
September 298.50 0.52 0.48 01-SEP-07:10 2015.65 18.88 67.33 301.00 1070.50 21.43 55.33 252.67
October 293.50 0.52 0.48 01-OCT-07:00 2427.12 20.38 90.50 264.50 880.94 19.70 42.67 209.00
November 299.00 0.53 0.48 01-NOV-08:09 1652.64 20.69 97.00 243.83 881.95 21.77 72.83 195.33
December 285.17 0.52 0.48 01-DEC-07:49 1394.67 19.20 73.00 233.33 736.12 21.16 57.50 172.33
                         
Annual Sum or Average 4071.00 0.51     2064.99 19.66 1083.83 3576.67 948.66 20.66 679.50 3008.67
Minimum of Months 263.00 0.51 0.48   1358.32 18.42 60.17 219.17 681.94 19.70 42.67 171.33
Maximum of Months 411.67 0.53 0.48   2427.12 20.69 110.33 368.83 1136.05 21.77 73.50 329.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-10:00 481.03 10.45 0.00 205.33 291.98 14.18 0.00 78.50
February 263.00 0.55 0.48 01-FEB-13:39 511.45 10.76 0.00 184.33 319.62 14.45 0.00 106.00
March 351.67 0.52 0.48 01-MAR-09:09 652.25 12.84 0.00 296.17 399.71 16.41 0.00 219.17
April 369.33 0.51 0.48 01-APR-08:30 779.27 13.79 0.00 325.50 468.71 17.31 0.00 265.67
May 407.00 0.50 0.48 01-MAY-07:30 972.34 17.27 51.83 379.83 571.59 20.44 52.50 348.00
June 411.67 0.50 0.48 01-JUN-06:40 1057.03 18.06 65.67 384.67 622.27 21.21 68.17 361.00
July 411.00 0.50 0.48 01-JUL-06:10 1061.59 16.15 27.33 383.00 601.99 20.57 54.00 350.50
August 390.50 0.50 0.48 01-AUG-06:00 950.10 14.78 0.00 357.83 555.66 18.24 0.00 320.33
September 298.50 0.52 0.48 01-SEP-07:40 723.09 13.75 0.00 299.33 440.23 17.22 0.00 209.83
October 293.50 0.54 0.48 01-OCT-10:39 535.53 11.50 0.00 230.33 345.08 15.24 0.00 134.50
November 299.00 0.55 0.48 01-NOV-09:50 497.27 10.88 0.00 218.67 303.86 14.53 0.00 108.50
December 285.17 0.55 0.48 01-DEC-09:30 464.14 10.49 0.00 197.67 282.77 14.27 0.00 68.50
                         
Annual Sum or Average 4071.00 0.52     757.50 13.77 144.83 3462.67 451.98 17.38 174.67 2570.50
Minimum of Months 263.00 0.50 0.48   464.14 10.45 0.00 184.33 282.77 14.18 0.00 68.50
Maximum of Months 411.67 0.55 0.48   1061.59 18.06 65.67 384.67 622.27 21.21 68.17 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-10:50 1675.90 20.73 89.17 240.67 918.99 21.71 68.00 185.17
February 263.00 0.53 0.48 01-FEB-13:39 1591.15 18.45 63.83 211.33 813.80 19.57 40.00 161.83
March 351.67 0.51 0.48 01-MAR-09:20 2087.83 18.80 77.50 306.50 1129.42 21.66 72.17 263.00
April 369.33 0.51 0.48 01-APR-09:00 2298.56 18.19 78.50 327.67 1251.60 19.86 51.83 285.00
May 407.00 0.51 0.48 01-MAY-08:09 2291.09 16.52 50.83 361.67 957.87 17.82 0.00 322.50
June 411.67 0.51 0.48 01-JUN-07:30 2393.35 14.16 1.67 363.83 1014.43 17.77 0.00 327.50
July 411.00 0.51 0.48 01-JUL-07:30 2376.73 16.50 52.00 364.83 991.75 17.81 0.00 323.67
August 390.50 0.51 0.48 01-AUG-07:40 2340.46 18.88 86.50 351.00 996.68 18.53 7.83 313.83
September 298.50 0.51 0.48 01-SEP-08:20 2062.88 19.38 75.50 301.00 1097.64 22.09 62.67 252.00
October 293.50 0.52 0.48 01-OCT-10:39 2289.71 20.47 92.50 260.00 856.37 19.84 42.83 206.00
November 299.00 0.53 0.48 01-NOV-09:50 1545.84 19.03 80.83 245.67 820.14 21.63 68.00 196.00
December 285.17 0.52 0.48 01-DEC-09:30 1349.25 18.93 73.67 233.33 723.46 21.22 63.00 173.00
                         
Annual Sum or Average 4071.00 0.51     2071.25 18.13 822.50 3567.50 976.51 19.77 476.33 3009.50
Minimum of Months 263.00 0.51 0.48   1349.25 14.16 1.67 211.33 723.46 17.77 0.00 161.83
Maximum of Months 411.67 0.53 0.48   2393.35 20.73 92.50 364.83 1251.60 22.09 72.17 327.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.50 0.48 01-JAN-09:09 5799.76 33.11 258.00 269.83 1555.23 23.28 103.33 248.83
February 263.00 0.51 0.48 01-FEB-10:30 6826.27 33.21 229.50 245.67 1055.77 18.03 25.83 213.83
March 351.67 0.51 0.48 01-MAR-08:39 1546.87 14.21 6.67 314.67 893.17 17.61 0.50 278.67
April 369.33 0.51 0.48 01-APR-08:30 1284.67 14.00 0.00 321.00 728.90 17.51 0.00 276.83
May 407.00 0.51 0.48 01-MAY-07:40 1167.76 14.24 0.00 355.67 651.71 17.72 0.00 307.17
June 411.67 0.51 0.48 01-JUN-07:10 1086.67 14.05 0.00 356.17 613.72 17.52 0.00 306.33
July 411.00 0.51 0.48 01-JUL-07:19 1144.71 14.23 0.00 358.83 638.10 17.66 0.00 308.17
August 390.50 0.51 0.48 01-AUG-07:19 1394.95 14.84 0.00 347.17 759.64 18.27 0.00 307.00
September 298.50 0.51 0.48 01-SEP-07:30 1484.10 14.97 6.50 304.67 825.37 18.11 0.00 265.17
October 293.50 0.50 0.48 01-OCT-10:39 2716.95 21.23 117.33 290.17 984.10 16.84 2.00 250.83
November 299.00 0.51 0.48 01-NOV-08:20 5713.93 34.08 281.17 271.67 1111.09 21.75 82.17 249.33
December 285.17 0.50 0.48 01-DEC-07:00 5407.81 32.29 249.33 263.67 1495.00 24.33 116.17 242.67
                         
Annual Sum or Average 4071.00 0.51     2684.45 20.11 1148.50 3699.17 904.83 18.86 330.00 3254.83
Minimum of Months 263.00 0.50 0.48   1086.67 14.00 0.00 245.67 613.72 16.84 0.00 213.83
Maximum of Months 411.67 0.51 0.48   6826.27 34.08 281.17 358.83 1555.23 24.33 116.17 308.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-09:09 1358.29 18.61 71.33 238.67 681.91 19.73 48.67 171.33
February 263.00 0.53 0.48 01-FEB-10:30 1806.24 18.42 60.17 219.17 985.12 20.85 48.50 173.33
March 351.67 0.51 0.48 01-MAR-08:39 2182.51 20.07 105.33 307.50 836.07 19.88 47.33 262.17
April 369.33 0.51 0.48 01-APR-07:00 2090.19 19.48 93.00 322.50 1111.33 20.99 67.17 283.17
May 407.00 0.51 0.48 01-MAY-06:00 2381.75 19.85 108.33 363.17 963.58 20.02 50.17 323.17
June 411.67 0.51 0.48 01-JUN-06:19 2411.99 19.78 110.33 365.50 988.12 20.74 64.00 329.00
July 411.00 0.51 0.48 01-JUL-05:00 2382.98 19.82 105.33 368.83 987.40 20.10 51.83 328.00
August 390.50 0.51 0.48 01-AUG-06:30 2175.44 20.16 102.17 348.67 1135.99 21.73 73.50 309.17
September 298.50 0.52 0.48 01-SEP-07:10 2015.61 18.88 67.33 301.00 1070.45 21.43 55.33 252.67
October 293.50 0.52 0.48 01-OCT-07:00 2427.10 20.38 90.50 264.50 880.91 19.70 42.67 209.00
November 299.00 0.53 0.48 01-NOV-08:09 1652.61 20.69 97.00 244.00 881.91 21.77 72.83 195.33
December 285.17 0.52 0.48 01-DEC-07:49 1394.64 19.20 73.00 233.33 736.09 21.16 57.50 172.33
                         
Annual Sum or Average 4071.00 0.51     2064.95 19.66 1083.83 3576.83 948.62 20.66 679.50 3008.67
Minimum of Months 263.00 0.51 0.48   1358.29 18.42 60.17 219.17 681.91 19.70 42.67 171.33
Maximum of Months 411.67 0.53 0.48   2427.10 20.69 110.33 368.83 1135.99 21.77 73.50 329.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.55 0.48 01-JAN-10:00 481.02 10.45 0.00 205.33 291.96 14.18 0.00 78.50
February 263.00 0.55 0.48 01-FEB-13:39 511.43 10.76 0.00 184.33 319.60 14.45 0.00 106.00
March 351.67 0.52 0.48 01-MAR-09:09 652.23 12.84 0.00 296.17 399.69 16.41 0.00 219.17
April 369.33 0.51 0.48 01-APR-08:30 779.24 13.79 0.00 325.50 468.68 17.31 0.00 265.67
May 407.00 0.50 0.48 01-MAY-07:30 972.30 17.27 51.83 379.83 571.55 20.44 52.50 348.00
June 411.67 0.50 0.48 01-JUN-06:40 1056.99 18.07 65.67 384.67 622.23 21.22 68.17 361.00
July 411.00 0.50 0.48 01-JUL-06:10 1061.55 16.15 27.33 383.00 601.95 20.57 54.00 350.50
August 390.50 0.50 0.48 01-AUG-06:00 950.06 14.78 0.00 357.83 555.62 18.25 0.00 320.33
September 298.50 0.52 0.48 01-SEP-07:40 723.07 13.76 0.00 299.33 440.20 17.22 0.00 209.50
October 293.50 0.54 0.48 01-OCT-10:39 535.52 11.50 0.00 230.17 345.06 15.24 0.00 134.50
November 299.00 0.55 0.48 01-NOV-09:50 497.25 10.88 0.00 218.67 303.84 14.54 0.00 108.50
December 285.17 0.55 0.48 01-DEC-09:30 464.12 10.49 0.00 197.67 282.75 14.27 0.00 68.50
                         
Annual Sum or Average 4071.00 0.52     757.47 13.78 144.83 3462.50 451.95 17.38 174.67 2570.17
Minimum of Months 263.00 0.50 0.48   464.12 10.45 0.00 184.33 282.75 14.18 0.00 68.50
Maximum of Months 411.67 0.55 0.48   1061.55 18.07 65.67 384.67 622.23 21.22 68.17 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.52 0.48 01-JAN-10:50 1675.87 20.73 89.17 240.67 918.95 21.72 68.00 185.17
February 263.00 0.53 0.48 01-FEB-13:39 1591.12 18.46 63.83 211.33 813.76 19.57 40.00 161.83
March 351.67 0.51 0.48 01-MAR-09:20 2087.79 18.80 77.50 306.50 1129.37 21.66 72.17 263.00
April 369.33 0.51 0.48 01-APR-09:00 2298.51 18.19 78.50 327.67 1251.55 19.86 51.83 285.00
May 407.00 0.51 0.48 01-MAY-08:09 2291.03 16.52 50.83 361.67 957.81 17.82 0.00 322.50
June 411.67 0.51 0.48 01-JUN-07:30 2393.29 14.16 1.67 363.83 1014.37 17.77 0.00 327.50
July 411.00 0.51 0.48 01-JUL-07:30 2376.67 16.51 52.00 364.83 991.69 17.81 0.00 323.67
August 390.50 0.51 0.48 01-AUG-07:40 2340.39 18.88 86.50 351.00 996.61 18.53 7.83 313.83
September 298.50 0.51 0.48 01-SEP-08:20 2062.83 19.38 75.50 301.00 1097.58 22.09 62.67 252.00
October 293.50 0.52 0.48 01-OCT-10:39 2289.69 20.47 92.50 260.00 856.33 19.84 42.83 206.00
November 299.00 0.53 0.48 01-NOV-09:50 1545.81 19.04 80.83 245.67 820.10 21.63 68.00 196.00
December 285.17 0.52 0.48 01-DEC-09:30 1349.22 18.93 73.67 233.33 723.43 21.22 63.00 173.00
                         
Annual Sum or Average 4071.00 0.51     2071.20 18.13 822.50 3567.50 976.46 19.77 476.33 3009.50
Minimum of Months 263.00 0.51 0.48   1349.22 14.16 1.67 211.33 723.43 17.77 0.00 161.83
Maximum of Months 411.67 0.53 0.48   2393.29 20.73 92.50 364.83 1251.55 22.09 72.17 327.50



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.473302E+10 14557.79 14-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.228807E+10 16704.31 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.139757E+09 4262.67 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 43880233.76 4484.99 06-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 19661458.18 3874.17 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.360999E+09 9514.06 22-NOV-07:04 0.00 0.00 0.00 0.00 0.00
December 0.112452E+10 12616.94 18-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.870991E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.473302E+10 16704.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2560594.28 20537.30 09-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2560594.28     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2560594.28 20537.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.412737E+10 10526.28 19-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.265817E+10 10501.18 17-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.104489E+10 10551.37 13-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.583051E+09 10492.62 26-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.151542E+09 10480.67 11-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 20522924.30 5573.67 08-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 19142235.07 6298.22 14-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.496347E+09 10635.92 04-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.968799E+09 10496.13 28-NOV-07:07 0.00 0.00 0.00 0.00 0.00
December 0.165968E+10 10477.34 07-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.117295E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.412737E+10 10635.92   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.143254E+10 7977.39 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.738902E+09 7977.39 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 45580059.78 7704.03 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 6783870.75 7977.39 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1519373.22 1385.69 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 16228478.52 7977.39 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.322476E+09 7977.39 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.256403E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143254E+10 7977.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.292626E+10 8903.05 20-JAN-07:03 0.00 0.00 0.00 0.00 0.00
February 0.164801E+10 8893.32 11-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.188158E+09 8875.41 24-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 42388383.35 8817.63 27-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3295547.25 3379.44 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.103217E+09 8836.63 25-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.918600E+09 8870.92 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.582993E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292626E+10 8903.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.150935E+10 8056.71 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.812200E+09 8056.71 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 55496435.96 7685.54 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 8778368.93 8056.71 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 577822.00 890.25 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 31179615.45 8056.71 21-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.395364E+09 8056.71 01-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.281294E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150935E+10 8056.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.494850E+10 14250.38 14-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.248725E+10 16940.53 03-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.260432E+09 4707.91 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 81443272.71 5465.78 06-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 40181746.18 4792.42 26-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.612257E+09 10147.07 22-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.137636E+10 13617.02 18-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.980644E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.494850E+10 16940.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185780E+10 20482.27 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.763566E+09 20482.27 03-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.309581E+09 20482.27 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.293094E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185780E+10 20482.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.162875E+10 11418.41 02-JAN-06:23 0.00 0.00 0.00 0.00 0.00
February 0.829573E+09 11362.56 11-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 50250750.70 11305.84 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 11758473.13 11245.32 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 22992471.28 11322.15 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.103636E+09 11317.39 24-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.564072E+09 11334.06 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.321103E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162875E+10 11418.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.140305E+10 8205.96 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.673576E+09 8205.96 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 34713052.21 7660.61 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 4984220.63 8205.96 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 18323294.37 7630.35 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.100499E+09 8205.96 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.532131E+09 8205.96 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.276728E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140305E+10 8205.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.287789E+10 9615.70 02-JAN-06:16 0.00 0.00 0.00 0.00 0.00
February 0.146704E+10 9569.52 08-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 93648044.18 9526.84 22-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 13884953.30 9489.38 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 31521034.98 9548.18 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.281811E+09 9525.31 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.128848E+10 9579.68 27-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.605428E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.287789E+10 9615.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.159388E+10 8281.80 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.801656E+09 8281.80 01-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 47846223.12 7651.79 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 7491598.12 8281.80 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 18425974.33 7465.34 26-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.149086E+09 8281.80 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.686782E+09 8281.80 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.330517E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159388E+10 8281.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.527383E+10 16661.19 27-JAN-07:06 0.00 0.00 0.00 0.00 0.00
February 0.270119E+10 18591.59 03-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.373515E+09 5808.27 18-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 0.121386E+09 6965.32 06-APR-06:13 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 83175916.27 6107.72 26-OCT-06:08 0.00 0.00 0.00 0.00 0.00
November 0.810957E+09 12442.77 22-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.163710E+10 14646.14 18-DEC-07:35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.110012E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.527383E+10 18591.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.570082E+10 35177.27 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.282833E+10 35177.27 02-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 74378450.02 34897.98 23-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 2548689.44 4174.71 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 66372853.12 35131.04 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.479936E+09 35060.65 27-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.283318E+10 35172.79 26-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119856E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.570082E+10 35177.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.304194E+10 12943.18 19-JAN-06:12 0.00 0.00 0.00 0.00 0.00
February 0.176702E+10 12943.37 08-FEB-06:12 0.00 0.00 0.00 0.00 0.00
March 0.257591E+09 12837.48 23-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 78831654.55 12809.97 07-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 1062610.12 1109.12 11-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.161664E+09 12878.07 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.476777E+09 12865.60 22-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.145145E+10 12931.79 26-DEC-06:16 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.723635E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.304194E+10 12943.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.256941E+10 10409.10 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.139902E+10 10409.10 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.160361E+09 10409.10 23-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 32615380.43 10409.10 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.124304E+09 10409.10 26-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.389006E+09 10409.10 14-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.127365E+10 10409.10 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.594838E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.256941E+10 10409.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.480028E+10 11137.50 02-JAN-06:37 0.00 0.00 0.00 0.00 0.00
February 0.273456E+10 11153.24 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.393283E+09 11112.79 24-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 92524924.83 11055.91 26-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 99146.45 330.49 11-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.238280E+09 11124.25 25-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.917440E+09 11096.94 24-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.265520E+10 11151.19 12-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118317E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.480028E+10 11153.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.276172E+10 10492.21 02-JAN-06:11 0.00 0.00 0.00 0.00 0.00
February 0.156394E+10 10492.21 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.217532E+09 10492.21 23-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 52051996.12 10492.21 06-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 137454.68 175.31 11-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.133252E+09 10492.21 26-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.517020E+09 10492.21 14-NOV-06:12 0.00 0.00 0.00 0.00 0.00
December 0.150725E+10 10492.21 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.675291E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.276172E+10 10492.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.167731E+10 0.103141E+10 17583.41 19-JAN-16:00 8903.50 0.00
February 0.00 0.00 0.444469E+10 0.368649E+10 32000.80 28-FEB-15:10 32000.80 0.00
March 0.00 0.00 0.139129E+11 0.108823E+11 49156.38 30-MAR-15:20 49156.38 0.00
April 0.00 0.00 0.241872E+11 0.198645E+11 53990.79 17-APR-14:20 53990.79 0.00
May 0.00 0.00 0.470530E+11 0.358614E+11 69665.67 30-MAY-15:00 56089.69 0.00
June 0.00 0.00 0.717438E+11 0.538424E+11 80061.54 26-JUN-14:30 57145.40 0.00
July 0.00 0.00 0.827166E+11 0.588094E+11 87461.74 07-JUL-12:05 59507.16 0.00
August 0.00 0.00 0.943440E+11 0.656504E+11 87447.73 15-AUG-06:03 60317.77 0.00
September 0.00 0.00 0.602471E+11 0.444608E+11 84160.05 07-SEP-16:00 62935.28 0.00
October 0.00 0.00 0.266344E+11 0.198820E+11 68591.09 10-OCT-15:50 56623.65 0.00
November 0.00 0.00 0.101836E+11 0.778658E+10 33649.48 03-NOV-15:00 25932.42 0.00
December 0.00 0.00 0.355990E+10 0.237277E+10 30052.16 12-DEC-14:00 23009.57 0.00
                 
Annual Sum or Average 0.00 0.00 0.440705E+12 0.324131E+12       0.00
Minimum of Months 0.00 0.00 0.167731E+10 0.103141E+10 17583.41   8903.50 0.00
Maximum of Months 0.00 0.00 0.943440E+11 0.656504E+11 87461.74   62935.28 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.159176E+10 0.973453E+09 16682.00 19-JAN-16:00 8451.16 0.00
February 0.00 0.00 0.422054E+10 0.348363E+10 28889.30 28-FEB-15:05 28889.30 0.00
March 0.00 0.00 0.128808E+11 0.100511E+11 48503.24 30-MAR-15:20 48503.24 0.00
April 0.00 0.00 0.230100E+11 0.189673E+11 54031.56 17-APR-15:30 54031.56 0.00
May 0.00 0.00 0.438601E+11 0.334486E+11 66133.26 30-MAY-14:05 53353.71 0.00
June 0.00 0.00 0.655444E+11 0.484133E+11 76392.85 26-JUN-14:05 53159.55 0.00
July 0.00 0.00 0.751332E+11 0.522207E+11 79567.38 07-JUL-12:02 55829.75 0.00
August 0.00 0.00 0.839364E+11 0.564790E+11 87117.64 21-AUG-06:03 64415.07 0.00
September 0.00 0.00 0.504726E+11 0.359543E+11 77823.92 06-SEP-14:05 55719.29 0.00
October 0.00 0.00 0.218047E+11 0.157330E+11 61061.95 11-OCT-14:05 45725.94 0.00
November 0.00 0.00 0.836477E+10 0.615345E+10 27677.67 02-NOV-14:05 21419.90 0.00
December 0.00 0.00 0.300950E+10 0.196385E+10 25640.72 12-DEC-14:00 18257.59 0.00
                 
Annual Sum or Average 0.00 0.00 0.393829E+12 0.283842E+12       0.00
Minimum of Months 0.00 0.00 0.159176E+10 0.973453E+09 16682.00   8451.16 0.00
Maximum of Months 0.00 0.00 0.839364E+11 0.564790E+11 87117.64   64415.07 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.164393E+10 0.993971E+09 16914.01 19-JAN-16:00 8543.67 0.00
February 0.00 0.00 0.432094E+10 0.350378E+10 27339.87 28-FEB-15:30 27339.87 0.00
March 0.00 0.00 0.133792E+11 0.103114E+11 54019.68 30-MAR-15:20 54019.68 0.00
April 0.00 0.00 0.246039E+11 0.202531E+11 60406.53 17-APR-16:00 60406.53 0.00
May 0.00 0.00 0.472397E+11 0.365716E+11 73808.43 30-MAY-15:00 60526.83 0.00
June 0.00 0.00 0.704143E+11 0.529568E+11 81927.81 26-JUN-15:00 60625.48 0.00
July 0.00 0.00 0.802623E+11 0.570548E+11 88027.98 07-JUL-16:00 70008.00 0.00
August 0.00 0.00 0.888859E+11 0.611369E+11 87621.59 01-AUG-15:00 69778.63 0.00
September 0.00 0.00 0.519296E+11 0.370236E+11 83991.59 06-SEP-14:00 62106.53 0.00
October 0.00 0.00 0.220299E+11 0.156982E+11 64338.74 10-OCT-14:20 51285.73 0.00
November 0.00 0.00 0.843414E+10 0.604262E+10 27609.82 02-NOV-14:00 19730.72 0.00
December 0.00 0.00 0.304626E+10 0.194442E+10 26800.92 12-DEC-14:00 18523.85 0.00
                 
Annual Sum or Average 0.00 0.00 0.416190E+12 0.303491E+12       0.00
Minimum of Months 0.00 0.00 0.164393E+10 0.993971E+09 16914.01   8543.67 0.00
Maximum of Months 0.00 0.00 0.888859E+11 0.611369E+11 88027.98   70008.00 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 1622.14 5937.98 31-JAN-12:15
February 0.00 0.00 01-FEB-00:10 1635.70 5938.19 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 1691.06 5844.25 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 1473.72 5521.79 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 1409.90 5140.52 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 1334.32 4712.99 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 1154.69 4387.46 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 1273.65 4371.13 31-AUG-11:50
September 0.00 0.00 01-SEP-00:10 1240.93 4647.26 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 1339.84 5078.23 31-OCT-11:17
November 0.00 0.00 01-NOV-00:10 1479.94 5492.35 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 1516.69 5797.90 29-DEC-13:00
             
Annual Sum or Average 0.00     1429.90    
Minimum of Months 0.00 0.00   1154.69 4371.13  
Maximum of Months 0.00 0.00   1691.06 5938.19  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.102106E+10 0.29 1470.05 09-JAN-07:01 0.63
February 0.101260E+10 0.29 1803.29 28-FEB-15:40 0.69
March 0.142218E+10 0.31 2879.23 13-MAR-06:03 0.88
April 0.155853E+10 0.31 3443.44 17-APR-06:03 0.98
May 0.217506E+10 0.36 4183.72 30-MAY-15:00 1.09
June 0.317389E+10 0.44 8900.36 26-JUN-05:12 1.75
July 0.355391E+10 0.46 8964.86 17-JUL-06:03 1.75
August 0.407623E+10 0.50 9729.26 07-AUG-05:12 1.85
September 0.293726E+10 0.42 8173.30 05-SEP-06:03 1.65
October 0.196478E+10 0.34 4391.61 10-OCT-16:00 1.12
November 0.134110E+10 0.30 3267.84 06-NOV-07:03 0.95
December 0.106718E+10 0.28 1262.37 01-DEC-07:01 0.59
           
Annual Sum or Average 0.253038E+11 0.36      
Minimum of Months 0.101260E+10 0.28 1262.37   0.59
Maximum of Months 0.407623E+10 0.50 9729.26   1.85



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.978913E+09 0.28 2165.32 02-JAN-06:11 0.79
February 0.944477E+09 0.29 2165.32 03-FEB-07:01 0.79
March 0.123975E+10 0.32 2785.26 30-MAR-14:05 0.90
April 0.141267E+10 0.32 3002.65 17-APR-15:50 0.94
May 0.197129E+10 0.36 4228.44 30-MAY-06:03 1.16
June 0.267873E+10 0.43 8931.88 26-JUN-06:03 1.85
July 0.289545E+10 0.43 8931.88 10-JUL-05:12 1.85
August 0.317618E+10 0.46 8931.88 07-AUG-06:03 1.85
September 0.212647E+10 0.38 6387.78 05-SEP-06:03 1.49
October 0.143526E+10 0.32 3331.41 10-OCT-15:30 1.00
November 0.103306E+10 0.29 1870.67 06-NOV-15:05 0.73
December 0.971319E+09 0.28 2165.32 04-DEC-07:01 0.79
           
Annual Sum or Average 0.208636E+11 0.35      
Minimum of Months 0.944477E+09 0.28 1870.67   0.73
Maximum of Months 0.317618E+10 0.46 8931.88   1.85



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.123047E+10 0.34 2184.76 03-JAN-06:11 0.73
February 0.111074E+10 0.34 2184.76 03-FEB-07:01 0.73
March 0.129937E+10 0.34 2888.92 30-MAR-16:00 0.84
April 0.143895E+10 0.33 3162.11 17-APR-15:40 0.89
May 0.198793E+10 0.36 3944.63 30-MAY-15:00 1.01
June 0.267610E+10 0.41 10072.58 26-JUN-05:12 1.80
July 0.289077E+10 0.41 7782.53 17-JUL-06:03 1.53
August 0.312146E+10 0.43 8859.11 07-AUG-05:12 1.66
September 0.199857E+10 0.36 4258.97 07-SEP-15:30 1.05
October 0.138158E+10 0.32 2996.82 10-OCT-15:30 0.86
November 0.110180E+10 0.31 2184.76 22-NOV-06:01 0.73
December 0.110800E+10 0.31 2184.76 18-DEC-07:02 0.73
           
Annual Sum or Average 0.213457E+11 0.36      
Minimum of Months 0.110180E+10 0.31 2184.76   0.73
Maximum of Months 0.312146E+10 0.43 10072.58   1.80



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:10 2.06 2.06 58.23 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:02 2.06 2.06 57.25 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:03 2.06 2.06 57.11 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 57.18 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.58 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.68 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:03 2.06 2.06 57.83 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.90 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.85 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.48 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:03 2.06 2.06 57.49 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:01 2.06 2.06 57.50 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 57.11 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.48 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 58.23 58.23 1622.14 5937.98 31-JAN-12:15
February 0.00 0.00 01-FEB-00:10 57.73 57.73 1635.70 5938.19 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 57.76 57.76 1691.06 5844.25 01-MAR-12:15
April 0.00 0.00 01-APR-00:10 57.88 57.88 1473.72 5521.79 03-APR-11:30
May 0.00 0.00 01-MAY-00:10 58.44 58.44 1409.90 5140.52 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 58.21 58.21 1334.32 4712.99 01-JUN-11:30
July 0.00 0.00 01-JUL-00:10 58.33 58.33 1154.69 4387.46 03-JUL-11:40
August 0.00 0.00 01-AUG-00:10 58.38 58.38 1273.65 4371.13 31-AUG-11:50
September 0.00 0.00 01-SEP-00:10 58.34 58.34 1240.93 4647.26 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 57.50 57.50 1339.84 5078.23 31-OCT-11:17
November 0.00 0.00 01-NOV-00:10 58.07 58.07 1479.94 5492.35 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 57.90 57.90 1516.69 5797.90 29-DEC-13:00
                 
Annual Sum or Average 0.00         1429.90    
Minimum of Months 0.00 0.00   57.50 57.50 1154.69 4371.13  
Maximum of Months 0.00 0.00   58.44 58.44 1691.06 5938.19  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.161665E+11 0.00 0.00
February 0.00 0.00 0.00 0.102415E+11 0.00 0.00
March 0.00 0.00 0.00 0.614131E+10 0.00 0.00
April 0.00 0.00 0.00 0.781368E+10 0.00 0.00
May 0.00 0.00 0.00 0.129598E+11 0.00 0.00
June 0.00 0.00 0.00 0.200867E+11 0.00 0.00
July 0.00 0.00 0.00 0.232550E+11 0.00 0.00
August 0.00 0.00 0.00 0.262987E+11 0.00 0.00
September 0.00 0.00 0.00 0.165354E+11 0.00 0.00
October 0.00 0.00 0.00 0.847620E+10 0.00 0.00
November 0.00 0.00 0.00 0.521457E+10 0.00 0.00
December 0.00 0.00 0.00 0.633195E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.159521E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.521457E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.262987E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.156819E+11 0.00 0.00
February 0.00 0.00 0.00 0.900226E+10 0.00 0.00
March 0.00 0.00 0.00 0.475159E+10 0.00 0.00
April 0.00 0.00 0.00 0.684576E+10 0.00 0.00
May 0.00 0.00 0.00 0.119312E+11 0.00 0.00
June 0.00 0.00 0.00 0.181094E+11 0.00 0.00
July 0.00 0.00 0.00 0.207427E+11 0.00 0.00
August 0.00 0.00 0.00 0.228740E+11 0.00 0.00
September 0.00 0.00 0.00 0.135669E+11 0.00 0.00
October 0.00 0.00 0.00 0.652346E+10 0.00 0.00
November 0.00 0.00 0.00 0.428054E+10 0.00 0.00
December 0.00 0.00 0.00 0.645620E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.140766E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.428054E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.228740E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.257877E+11 0.00 0.00
February 0.00 0.00 0.00 0.151737E+11 0.00 0.00
March 0.00 0.00 0.00 0.594759E+10 0.00 0.00
April 0.00 0.00 0.00 0.753742E+10 0.00 0.00
May 0.00 0.00 0.00 0.127967E+11 0.00 0.00
June 0.00 0.00 0.00 0.193544E+11 0.00 0.00
July 0.00 0.00 0.00 0.220954E+11 0.00 0.00
August 0.00 0.00 0.00 0.241111E+11 0.00 0.00
September 0.00 0.00 0.00 0.138745E+11 0.00 0.00
October 0.00 0.00 0.00 0.724854E+10 0.00 0.00
November 0.00 0.00 0.00 0.673469E+10 0.00 0.00
December 0.00 0.00 0.00 0.132096E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.173871E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.594759E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.257877E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.102106E+10 0.167731E+10 0.147311E+11 0.00 0.00 0.00 0.00 0.00
February 0.101260E+10 0.444469E+10 0.814535E+10 0.00 0.00 0.00 0.00 0.00
March 0.142218E+10 0.139129E+11 0.147388E+10 0.00 0.00 0.00 0.00 0.00
April 0.155853E+10 0.241872E+11 0.684882E+09 0.00 0.00 0.00 0.00 0.00
May 0.217506E+10 0.470530E+11 0.151542E+09 0.00 0.00 0.00 0.00 0.00
June 0.317389E+10 0.717438E+11 20522924.30 0.00 0.00 0.00 0.00 0.00
July 0.355391E+10 0.827166E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.407623E+10 0.943440E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293726E+10 0.602471E+11 19142235.07 0.00 0.00 0.00 0.00 0.00
October 0.196478E+10 0.266344E+11 0.521401E+09 0.00 0.00 0.00 0.00 0.00
November 0.134110E+10 0.101836E+11 0.148042E+10 0.00 0.00 0.00 0.00 0.00
December 0.106718E+10 0.355990E+10 0.442064E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.253038E+11 0.440705E+12 0.316489E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.101260E+10 0.167731E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.407623E+10 0.943440E+11 0.147311E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.978913E+09 0.159176E+10 0.143099E+11 0.00 0.00 0.00 0.00 0.00
February 0.944477E+09 0.422054E+10 0.702267E+10 0.00 0.00 0.00 0.00 0.00
March 0.123975E+10 0.128808E+11 0.486890E+09 0.00 0.00 0.00 0.00 0.00
April 0.141267E+10 0.230100E+11 0.119563E+09 0.00 0.00 0.00 0.00 0.00
May 0.197129E+10 0.438601E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.267873E+10 0.655444E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.289545E+10 0.751332E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.317618E+10 0.839364E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.212647E+10 0.504726E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143526E+10 0.218047E+11 0.131445E+09 0.00 0.00 0.00 0.00 0.00
November 0.103306E+10 0.836477E+10 0.124729E+10 0.00 0.00 0.00 0.00 0.00
December 0.971319E+09 0.300950E+10 0.475741E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.208636E+11 0.393829E+12 0.280751E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.944477E+09 0.159176E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.317618E+10 0.839364E+11 0.143099E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.123047E+10 0.164393E+10 0.241480E+11 0.00 0.00 0.00 0.00 0.00
February 0.111074E+10 0.432094E+10 0.129941E+11 0.00 0.00 0.00 0.00 0.00
March 0.129937E+10 0.133792E+11 0.147666E+10 0.00 0.00 0.00 0.00 0.00
April 0.143895E+10 0.246039E+11 0.379959E+09 0.00 0.00 0.00 0.00 0.00
May 0.198793E+10 0.472397E+11 1299211.26 0.00 0.00 0.00 0.00 0.00
June 0.267610E+10 0.704143E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.289077E+10 0.802623E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.312146E+10 0.888859E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.199857E+10 0.519296E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138158E+10 0.220299E+11 0.807049E+09 0.00 0.00 0.00 0.00 0.00
November 0.110180E+10 0.843414E+10 0.359114E+10 0.00 0.00 0.00 0.00 0.00
December 0.110800E+10 0.304626E+10 0.113578E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.213457E+11 0.416190E+12 0.547560E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.110180E+10 0.164393E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.312146E+10 0.888859E+11 0.241480E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.102106E+10 0.00 0.00 0.00 0.414378E+09 0.147311E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.101260E+10 0.00 0.00 0.00 0.108354E+10 0.814535E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142218E+10 0.00 0.00 0.00 0.324525E+10 0.147388E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.155853E+10 0.00 0.00 0.00 0.557027E+10 0.684882E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.217506E+10 0.00 0.00 0.00 0.106332E+11 0.151542E+09 0.00 0.00 0.00 0.00 0.00 0.00
June 0.317389E+10 0.00 0.00 0.00 0.168923E+11 20522924.30 0.00 0.00 0.00 0.00 0.00 0.00
July 0.355391E+10 0.00 0.00 0.00 0.197011E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.407623E+10 0.00 0.00 0.00 0.222225E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293726E+10 0.00 0.00 0.00 0.135790E+11 19142235.07 0.00 0.00 0.00 0.00 0.00 0.00
October 0.196478E+10 0.00 0.00 0.00 0.599001E+10 0.521401E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134110E+10 0.00 0.00 0.00 0.239304E+10 0.148042E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.106718E+10 0.00 0.00 0.00 0.844131E+09 0.442064E+10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.253038E+11 0.00 0.00 0.00 0.102569E+12 0.316489E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.101260E+10 0.00 0.00 0.00 0.414378E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.407623E+10 0.00 0.00 0.00 0.222225E+11 0.147311E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.978913E+09 0.00 0.00 0.00 0.393152E+09 0.143099E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.944477E+09 0.00 0.00 0.00 0.103512E+10 0.702267E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.123975E+10 0.00 0.00 0.00 0.302495E+10 0.486890E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141267E+10 0.00 0.00 0.00 0.531353E+10 0.119563E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.197129E+10 0.00 0.00 0.00 0.995993E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.267873E+10 0.00 0.00 0.00 0.154306E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.289545E+10 0.00 0.00 0.00 0.178473E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.317618E+10 0.00 0.00 0.00 0.196978E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.212647E+10 0.00 0.00 0.00 0.114404E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143526E+10 0.00 0.00 0.00 0.495676E+10 0.131445E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.103306E+10 0.00 0.00 0.00 0.200020E+10 0.124729E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.971319E+09 0.00 0.00 0.00 0.727473E+09 0.475741E+10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.208636E+11 0.00 0.00 0.00 0.918272E+11 0.280751E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.944477E+09 0.00 0.00 0.00 0.393152E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.317618E+10 0.00 0.00 0.00 0.196978E+11 0.143099E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.123047E+10 0.00 0.00 0.00 0.409224E+09 0.241480E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.111074E+10 0.00 0.00 0.00 0.106893E+10 0.129941E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.129937E+10 0.00 0.00 0.00 0.317156E+10 0.147666E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143895E+10 0.00 0.00 0.00 0.571851E+10 0.379959E+09 0.00 0.00 0.00 0.00 0.00 0.00
May 0.198793E+10 0.00 0.00 0.00 0.108075E+11 1299211.26 0.00 0.00 0.00 0.00 0.00 0.00
June 0.267610E+10 0.00 0.00 0.00 0.166783E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.289077E+10 0.00 0.00 0.00 0.192046E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.312146E+10 0.00 0.00 0.00 0.209897E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.199857E+10 0.00 0.00 0.00 0.118759E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138158E+10 0.00 0.00 0.00 0.505991E+10 0.807049E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.110180E+10 0.00 0.00 0.00 0.204175E+10 0.359114E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.110800E+10 0.00 0.00 0.00 0.743797E+09 0.113578E+11 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.213457E+11 0.00 0.00 0.00 0.977696E+11 0.547560E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.110180E+10 0.00 0.00 0.00 0.409224E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.312146E+10 0.00 0.00 0.00 0.209897E+11 0.241480E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.965122E+10 0.00 0.00 4967773.69 6753496.89 1474738.91 0.385723E+10 0.00 0.33
February 0.510295E+10 0.00 0.00 12782643.39 0.00 0.00 0.652351E+10 0.00 0.42
March 0.802965E+09 0.240447E+09 0.00 31109096.63 11789118.28 0.00 0.123430E+11 0.00 0.61
April 0.395758E+09 0.477808E+09 0.00 30092361.07 33830949.03 0.00 0.795339E+10 0.00 0.64
May 80771582.11 0.277393E+10 0.00 14952883.65 43079392.52 0.00 0.279943E+10 0.00 0.52
June 53265873.82 0.810018E+10 0.00 6981625.78 71600866.99 0.00 0.130401E+10 0.00 0.41
July 0.00 0.106476E+11 0.00 0.00 0.194737E+09 0.00 0.00 0.00 0.29
August 1501.16 0.126927E+11 0.00 264637.02 0.147439E+09 0.00 3529182.37 0.00 0.30
September 47053832.51 0.515427E+10 0.00 14932933.39 99139513.63 0.00 0.195645E+10 0.00 0.49
October 0.332269E+09 0.154655E+10 0.00 30945938.39 4186044.91 0.00 0.112863E+11 0.00 0.61
November 0.900036E+09 0.161395E+09 0.00 31251606.38 14492475.65 0.00 0.130207E+11 0.00 0.58
December 0.405462E+10 28197503.31 0.00 16085902.59 0.00 0.00 0.878180E+10 0.00 0.41
                   
Annual Sum or Average 0.214209E+11 0.418231E+11 0.00 0.194367E+09 0.627049E+09 1474738.91 0.698293E+11 0.00 0.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.965122E+10 0.126927E+11 0.00 31251606.38 0.194737E+09 1474738.91 0.130207E+11 0.00 0.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.120740E+11 0.00 0.00 0.00 13412449.86 0.547336E+09 0.00 0.00 0.32
February 0.930202E+10 0.00 0.00 1166637.09 1984520.29 0.135817E+09 0.656921E+09 0.00 0.37
March 0.597424E+10 97390276.37 0.00 7109953.39 0.120580E+09 0.00 0.361719E+10 0.00 0.45
April 0.235216E+10 0.225467E+09 0.00 11712959.16 0.175361E+09 0.00 0.351597E+10 0.00 0.45
May 0.476693E+09 0.199728E+10 0.00 7078009.32 0.132929E+09 0.00 0.150144E+10 0.00 0.37
June 0.189071E+09 0.687949E+10 0.00 3830954.26 80145424.78 0.00 0.760333E+09 0.00 0.32
July 0.00 0.904918E+10 0.00 0.00 0.334271E+09 0.00 0.00 0.00 0.24
August 1650437.41 0.113146E+11 0.00 147704.61 0.146227E+09 0.00 3912635.37 0.00 0.26
September 0.267174E+09 0.437934E+10 0.00 7142787.82 0.220494E+09 0.00 0.989014E+09 0.00 0.36
October 0.358532E+10 0.127410E+10 0.00 8599524.90 18347901.76 0.00 0.385953E+10 0.00 0.42
November 0.687881E+10 16618075.65 0.00 3889870.69 0.201730E+09 0.00 0.247370E+10 0.00 0.40
December 0.101113E+11 21314078.05 0.00 428815.67 17038258.02 80037481.17 0.375633E+09 0.00 0.35
                   
Annual Sum or Average 0.512124E+11 0.352548E+11 0.00 51107216.92 0.146252E+10 0.763191E+09 0.177537E+11 0.00 0.36
Minimum of Months 0.00 0.00 0.00 0.00 1984520.29 0.00 0.00 0.00 0.24
Maximum of Months 0.120740E+11 0.113146E+11 0.00 11712959.16 0.334271E+09 0.547336E+09 0.385953E+10 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.916738E+10 0.00 0.00 0.00 14874086.37 0.283051E+10 0.00 0.00 0.32
February 0.801448E+10 0.00 0.00 571601.27 5294103.43 0.116016E+10 0.317192E+09 0.00 0.37
March 0.703031E+10 0.100097E+09 0.00 3675835.55 0.129396E+09 11044546.91 0.184081E+10 0.00 0.44
April 0.269495E+10 0.203255E+09 0.00 10539987.95 0.156245E+09 0.00 0.264079E+10 0.00 0.46
May 0.537297E+09 0.185279E+10 0.00 5237962.78 0.168819E+09 0.00 0.116151E+10 0.00 0.36
June 0.279217E+09 0.665863E+10 0.00 3201668.23 82265957.90 0.00 0.575592E+09 0.00 0.32
July 0.00 0.881013E+10 0.00 0.00 0.373937E+09 0.00 0.00 0.00 0.24
August 0.00 0.110986E+11 0.00 0.00 0.136323E+09 0.00 0.00 0.00 0.26
September 0.331293E+09 0.411088E+10 0.00 5681524.22 0.516531E+09 0.00 0.665224E+09 0.00 0.36
October 0.430959E+10 0.121834E+10 0.00 4099529.70 0.103687E+09 5535957.23 0.212734E+10 0.00 0.39
November 0.763193E+10 12653568.95 745418.76 981162.49 0.233290E+09 0.126141E+09 0.672973E+09 29898.76 0.39
December 0.891309E+10 848908.63 0.00 97828.31 40260547.37 0.796545E+09 52118971.18 0.00 0.34
                   
Annual Sum or Average 0.489095E+11 0.340662E+11 745418.76 34087100.52 0.196092E+10 0.492993E+10 0.100535E+11 29898.76 0.35
Minimum of Months 0.00 0.00 0.00 0.00 5294103.43 0.00 0.00 0.00 0.24
Maximum of Months 0.916738E+10 0.110986E+11 745418.76 10539987.95 0.516531E+09 0.283051E+10 0.264079E+10 29898.76 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.487165E+09 0.00 0.00 0.00 3141528.47 0.234127E+10 0.00 0.00 0.34
February 0.816342E+09 0.00 243137.76 102166.10 874506.02 0.129337E+10 30632122.66 514.08 0.38
March 0.151103E+10 24556722.75 0.00 572408.89 25891189.89 0.189849E+09 0.175926E+09 0.00 0.45
April 0.713963E+09 70512323.24 0.00 2087942.72 16168972.41 41908185.15 0.380868E+09 0.00 0.50
May 0.161527E+09 0.530605E+09 0.00 1104030.29 36271712.93 0.00 0.214276E+09 0.00 0.43
June 65349487.85 0.217197E+10 0.00 863070.11 21497775.11 0.00 0.132566E+09 0.00 0.45
July 0.00 0.293387E+10 0.00 0.00 52717691.19 0.00 0.00 0.00 0.36
August 0.00 0.346756E+10 0.00 0.00 32556148.18 0.00 0.00 0.00 0.38
September 99371326.92 0.111851E+10 0.00 1161102.17 87249885.29 0.00 0.123291E+09 0.00 0.41
October 0.106474E+10 0.285465E+09 0.00 437866.64 31280640.24 92664462.44 0.182756E+09 0.00 0.39
November 0.134303E+10 2350833.53 3851719.62 53373.11 46019805.21 0.423624E+09 32621170.55 11414.32 0.39
December 0.908289E+09 175655.59 0.00 1201.30 8506997.13 0.126906E+10 271469.15 0.00 0.36
                   
Annual Sum or Average 0.717081E+10 0.106056E+11 4094857.38 6383161.32 0.362177E+09 0.565174E+10 0.127321E+10 11928.40 0.40
Minimum of Months 0.00 0.00 0.00 0.00 874506.02 0.00 0.00 0.00 0.34
Maximum of Months 0.151103E+10 0.346756E+10 3851719.62 2087942.72 87249885.29 0.234127E+10 0.380868E+09 11414.32 0.50



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.596017E+09 0.00 0.00 0.00 1987404.50 0.116426E+10 0.00 0.00 0.34
February 0.582015E+09 0.00 153520.29 399609.66 553232.99 0.613232E+09 0.168685E+09 619.57 0.40
March 0.715767E+09 25645470.03 0.00 1539194.31 9769642.20 75428178.47 0.532438E+09 0.00 0.52
April 0.281985E+09 58042805.62 0.00 3398973.12 5730963.91 14508972.79 0.708458E+09 0.00 0.73
May 67567215.51 0.509355E+09 0.00 1597506.51 17399160.77 0.00 0.310007E+09 0.00 0.63
June 29045700.05 0.183267E+10 0.00 1108256.69 10132996.90 0.00 0.193510E+09 0.00 0.64
July 0.00 0.257151E+10 0.00 0.00 31909738.29 0.00 0.00 0.00 0.49
August 0.00 0.293282E+10 0.00 0.00 19274060.80 0.00 0.00 0.00 0.51
September 55090125.95 0.104676E+10 0.00 1406441.67 38588146.18 0.00 0.151910E+09 0.00 0.59
October 0.503631E+09 0.246621E+09 0.00 1252507.27 12041475.58 49525378.32 0.499912E+09 0.00 0.50
November 0.830587E+09 2208404.19 2442631.00 347239.11 28787216.39 0.175770E+09 0.147222E+09 6601.08 0.40
December 0.816058E+09 1441454.01 0.00 12791.88 4051395.50 0.543875E+09 2115285.41 0.00 0.35
                   
Annual Sum or Average 0.447776E+10 0.922707E+10 2596151.29 11062520.22 0.180225E+09 0.263660E+10 0.271426E+10 7220.65 0.51
Minimum of Months 0.00 0.00 0.00 0.00 553232.99 0.00 0.00 0.00 0.34
Maximum of Months 0.830587E+09 0.293282E+10 2442631.00 3398973.12 38588146.18 0.116426E+10 0.708458E+09 6601.08 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.900067E+09 0.00 0.00 1136212.37 3130925.93 0.136878E+10 0.678278E+09 0.00 0.36
February 0.832612E+09 0.00 0.00 2220978.84 1114384.12 0.777314E+09 0.880702E+09 0.00 0.49
March 0.106711E+10 60225706.89 0.00 3992540.72 11120933.04 0.124650E+09 0.128896E+10 0.00 0.64
April 0.539599E+09 89084469.80 0.00 4468915.90 11787592.67 37129517.51 0.885810E+09 0.00 0.68
May 0.157013E+09 0.602371E+09 0.00 1471820.97 36706495.28 0.00 0.275477E+09 0.00 0.49
June 72222202.26 0.221550E+10 0.00 876440.35 26721925.66 0.00 0.131915E+09 0.00 0.46
July 0.00 0.306063E+10 0.00 0.00 53454091.14 0.00 0.00 0.00 0.37
August 0.00 0.402400E+10 0.00 0.00 28859132.62 0.00 0.00 0.00 0.44
September 90672895.88 0.154382E+10 0.00 2214801.40 66790547.62 0.00 0.229692E+09 0.00 0.58
October 0.690005E+09 0.459391E+09 0.00 4171164.16 18143216.22 67131066.64 0.142278E+10 0.00 0.67
November 0.994165E+09 11306380.50 1372640.61 3933867.19 41003902.67 0.225953E+09 0.129275E+10 8609.47 0.58
December 0.102472E+10 5365305.44 0.00 2278105.90 4636875.43 0.580994E+09 0.947173E+09 0.00 0.43
                   
Annual Sum or Average 0.636819E+10 0.120717E+11 1372640.61 26764847.81 0.303470E+09 0.318195E+10 0.803354E+10 8609.47 0.52
Minimum of Months 0.00 0.00 0.00 0.00 1114384.12 0.00 0.00 0.00 0.36
Maximum of Months 0.106711E+10 0.402400E+10 1372640.61 4468915.90 66790547.62 0.136878E+10 0.142278E+10 8609.47 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.498853E+09 0.00 0.00 11748.18 1990592.63 0.127701E+10 20738081.91 0.00 0.35
February 0.561487E+09 0.00 0.00 428572.41 708507.60 0.712811E+09 0.150077E+09 0.00 0.42
March 0.800560E+09 35492250.96 0.00 1600983.04 8393741.02 0.107749E+09 0.522183E+09 0.00 0.58
April 0.358442E+09 58008023.10 0.00 3200117.43 8495052.94 24240072.80 0.616673E+09 0.00 0.74
May 91366927.61 0.447214E+09 0.00 1300201.77 17901944.83 0.00 0.258611E+09 0.00 0.61
June 45651475.94 0.173713E+10 0.00 811329.91 10343064.86 0.00 0.117083E+09 0.00 0.59
July 0.00 0.236232E+10 0.00 0.00 25718165.92 0.00 0.00 0.00 0.45
August 0.00 0.289667E+10 0.00 0.00 7376184.12 0.00 0.00 0.00 0.49
September 60212266.47 0.967741E+09 0.00 1236804.17 40182175.76 0.00 0.122101E+09 0.00 0.55
October 0.572932E+09 0.232319E+09 0.00 1256548.84 15254250.47 53189439.41 0.434181E+09 0.00 0.51
November 0.756596E+09 1900710.96 2446242.76 644620.16 28903412.74 0.240443E+09 0.246326E+09 6578.63 0.44
December 0.665763E+09 313474.63 0.00 94395.73 5211929.81 0.681699E+09 43475692.97 0.00 0.36
                   
Annual Sum or Average 0.441186E+10 0.873911E+10 2446242.76 10585321.64 0.170479E+09 0.309714E+10 0.253145E+10 6578.63 0.51
Minimum of Months 0.00 0.00 0.00 0.00 708507.60 0.00 0.00 0.00 0.35
Maximum of Months 0.800560E+09 0.289667E+10 2446242.76 3200117.43 40182175.76 0.127701E+10 0.616673E+09 6578.63 0.74



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.741267E+09 0.00 0.00 0.00 1420931.17 0.213507E+10 0.00 0.00 0.32
February 0.112626E+10 0.00 0.00 17202.85 0.00 0.113716E+10 4284445.51 0.00 0.37
March 0.182389E+10 8463447.14 0.00 94326.53 32988212.45 86892075.01 43145392.51 0.00 0.42
April 0.100361E+10 22456310.87 0.00 491634.83 53474156.26 18911455.82 94188530.88 0.00 0.40
May 0.260620E+09 0.363127E+09 0.00 505278.19 58689763.02 0.00 0.101802E+09 0.00 0.33
June 76925606.38 0.161190E+10 0.00 664258.83 19161439.94 0.00 0.110267E+09 0.00 0.34
July 0.00 0.226151E+10 0.00 0.00 47875386.24 0.00 0.00 0.00 0.27
August 312348.31 0.272583E+10 0.00 5150.86 31021147.12 0.00 172136.74 0.00 0.30
September 0.107014E+09 0.942392E+09 0.00 1355332.41 23117397.34 0.00 0.165271E+09 0.00 0.36
October 0.122511E+10 0.245889E+09 0.00 745580.37 3415978.47 329414.28 0.311285E+09 0.00 0.39
November 0.189497E+10 1083565.85 0.00 191108.20 28978457.78 41322021.77 96735854.86 0.00 0.39
December 0.186130E+10 260447.19 0.00 1488.64 3436014.65 0.556555E+09 504080.89 0.00 0.35
                   
Annual Sum or Average 0.101213E+11 0.818291E+10 0.00 4071361.73 0.303579E+09 0.397624E+10 0.927656E+09 0.00 0.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.189497E+10 0.272583E+10 0.00 1355332.41 58689763.02 0.213507E+10 0.311285E+09 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.799253E+09 0.00 0.00 0.00 897993.13 0.102106E+10 0.00 0.00 0.32
February 0.796207E+09 0.00 0.00 328201.91 0.00 0.501350E+09 0.155874E+09 0.00 0.38
March 0.899316E+09 9776122.05 0.00 958801.70 18293466.55 29029902.37 0.375654E+09 0.00 0.45
April 0.395435E+09 32249569.39 0.00 2050589.24 20624024.29 3706212.73 0.474263E+09 0.00 0.54
May 95789224.17 0.388084E+09 0.00 1333859.38 24399294.15 0.00 0.251792E+09 0.00 0.51
June 31744056.36 0.143900E+10 0.00 1026050.83 9891367.91 0.00 0.184065E+09 0.00 0.52
July 0.00 0.207515E+10 0.00 0.00 30177598.36 0.00 0.00 0.00 0.39
August 152582.84 0.239469E+10 0.00 5430.83 19604592.81 0.00 154301.46 0.00 0.41
September 55293315.29 0.866413E+09 0.00 1640710.69 14154123.15 0.00 0.202297E+09 0.00 0.54
October 0.495465E+09 0.209686E+09 0.00 2083737.78 942824.84 398508.26 0.793630E+09 0.00 0.53
November 0.963555E+09 3869784.03 0.00 868938.96 15387236.83 7620434.22 0.391925E+09 0.00 0.42
December 0.134856E+10 1402978.28 0.00 27568.54 933093.59 0.170978E+09 9701182.39 0.00 0.35
                   
Annual Sum or Average 0.588077E+10 0.742031E+10 0.00 10323889.85 0.155306E+09 0.173414E+10 0.283936E+10 0.00 0.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
Maximum of Months 0.134856E+10 0.239469E+10 0.00 2083737.78 30177598.36 0.102106E+10 0.793630E+09 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113279E+10 0.00 0.00 122966.32 1421195.65 0.235328E+10 82640571.62 0.00 0.39
February 0.103978E+10 0.00 0.00 1034380.90 0.00 0.146521E+10 0.300669E+09 0.00 0.47
March 0.136888E+10 44405370.85 0.00 1291554.59 13293861.39 0.508772E+09 0.395093E+09 0.00 0.51
April 0.841255E+09 49186546.92 0.00 1627011.23 38591079.66 0.265046E+09 0.164534E+09 0.00 0.49
May 0.251336E+09 0.470025E+09 0.00 518472.00 66453999.97 59350268.22 87841896.57 0.00 0.38
June 96045625.24 0.191119E+10 0.00 523309.83 63160344.11 10682133.41 72950882.85 0.00 0.38
July 0.00 0.265849E+10 0.00 0.00 96529257.27 0.00 0.00 0.00 0.32
August 489727.05 0.363069E+10 0.00 0.00 45969688.39 0.00 0.00 0.00 0.39
September 0.127449E+09 0.137240E+10 0.00 1984912.05 40656647.72 11716049.05 0.198626E+09 0.00 0.52
October 0.813882E+09 0.401340E+09 0.00 3503708.50 6783108.84 0.242429E+09 0.113449E+10 0.00 0.63
November 0.119707E+10 12243375.72 0.00 3270516.61 20410968.51 0.451765E+09 0.110215E+10 0.00 0.57
December 0.152714E+10 2269244.83 0.00 1103716.50 1873865.73 0.845887E+09 0.525066E+09 0.00 0.42
                   
Annual Sum or Average 0.839611E+10 0.105522E+11 0.00 14980548.54 0.395144E+09 0.621413E+10 0.406407E+10 0.00 0.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
Maximum of Months 0.152714E+10 0.363069E+10 0.00 3503708.50 96529257.27 0.235328E+10 0.113449E+10 0.00 0.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.714227E+09 0.00 0.00 0.00 899860.25 0.110946E+10 0.00 0.00 0.32
February 0.809339E+09 0.00 0.00 255736.03 0.00 0.575283E+09 71173166.22 0.00 0.38
March 0.103567E+10 26395283.98 0.00 872310.94 9398944.69 20852657.53 0.270879E+09 0.00 0.48
April 0.496047E+09 37062511.37 0.00 1605930.06 19525800.11 6457165.79 0.306386E+09 0.00 0.52
May 0.123210E+09 0.360072E+09 0.00 867037.98 20044321.31 0.00 0.171864E+09 0.00 0.47
June 47117109.70 0.137848E+10 0.00 667914.78 8316890.64 0.00 97918152.93 0.00 0.47
July 0.00 0.192832E+10 0.00 0.00 22051585.43 0.00 0.00 0.00 0.36
August 152900.09 0.238569E+10 0.00 10235.04 11644096.33 0.00 149198.52 0.00 0.40
September 56853270.56 0.842061E+09 0.00 1381421.90 12620792.69 0.00 0.152082E+09 0.00 0.50
October 0.576229E+09 0.210654E+09 0.00 1727776.41 944785.17 190722.36 0.600583E+09 0.00 0.52
November 0.103632E+10 4401364.47 0.00 894430.35 14807783.08 17720905.34 0.339804E+09 0.00 0.45
December 0.125149E+10 988431.38 0.00 114034.29 1359419.20 0.227792E+09 56160624.23 0.00 0.35
                   
Annual Sum or Average 0.614665E+10 0.717413E+10 0.00 8396827.79 0.121614E+09 0.195775E+10 0.206700E+10 0.00 0.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.32
Maximum of Months 0.125149E+10 0.238569E+10 0.00 1727776.41 22051585.43 0.110946E+10 0.600583E+09 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.795672E+09 0.00 0.00 0.00 2834813.91 0.195882E+10 0.00 0.00 0.32
February 0.119100E+10 0.00 0.00 129306.21 419442.07 0.966276E+09 24478133.14 0.00 0.37
March 0.174909E+10 27096098.40 0.00 641582.54 21999390.44 43700912.51 0.210329E+09 0.00 0.45
April 0.793607E+09 84989001.73 0.00 1892763.46 12054921.38 9659726.76 0.394876E+09 0.00 0.47
May 0.181619E+09 0.595430E+09 0.00 1278242.74 19244257.75 0.00 0.225779E+09 0.00 0.43
June 68685229.14 0.230486E+10 0.00 871406.66 15676533.09 0.00 0.139845E+09 0.00 0.45
July 0.00 0.309338E+10 0.00 0.00 48332977.40 0.00 0.00 0.00 0.36
August 718078.92 0.361630E+10 0.00 7714.70 30906033.61 0.00 382099.10 0.00 0.39
September 0.121011E+09 0.118705E+10 0.00 1174805.21 33193677.74 0.00 0.131295E+09 0.00 0.40
October 0.121424E+10 0.304221E+09 0.00 628970.14 9874528.98 14088188.12 0.253855E+09 0.00 0.40
November 0.171108E+10 3521646.88 168711.50 130463.69 42550280.82 0.175295E+09 76369549.24 2068.17 0.39
December 0.150758E+10 1719890.99 0.00 12175.35 6386140.12 0.750659E+09 1911761.18 0.00 0.35
                   
Annual Sum or Average 0.933430E+10 0.112186E+11 168711.50 6767430.68 0.243473E+09 0.391850E+10 0.145912E+10 2068.17 0.40
Minimum of Months 0.00 0.00 0.00 0.00 419442.07 0.00 0.00 0.00 0.32
Maximum of Months 0.174909E+10 0.361630E+10 168711.50 1892763.46 48332977.40 0.195882E+10 0.394876E+09 2068.17 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.578930E+09 0.00 0.00 1835.38 1792944.99 0.885892E+09 791223.18 0.00 0.27
February 0.613827E+09 0.00 0.00 531874.20 265286.04 0.414043E+09 0.196870E+09 0.00 0.34
March 0.685941E+09 24918258.55 0.00 1704687.84 6694857.15 15939904.76 0.621783E+09 0.00 0.49
April 0.305695E+09 63220049.84 0.00 3121053.96 5097662.10 3567984.11 0.732239E+09 0.00 0.66
May 79748089.27 0.507585E+09 0.00 1730826.78 10473404.93 0.00 0.325050E+09 0.00 0.61
June 31346784.57 0.181853E+10 0.00 1118222.93 9689478.34 0.00 0.201193E+09 0.00 0.61
July 0.00 0.255152E+10 0.00 0.00 29847150.47 0.00 0.00 0.00 0.47
August 420412.00 0.289113E+10 0.00 9227.11 19547250.71 0.00 281605.39 0.00 0.49
September 64338018.08 0.991964E+09 0.00 1364314.93 18166989.65 0.00 0.160085E+09 0.00 0.54
October 0.494939E+09 0.224123E+09 0.00 1609925.28 4402264.10 8237452.97 0.601683E+09 0.00 0.48
November 0.810368E+09 5948024.80 107559.24 615479.71 20245175.65 54389291.86 0.247086E+09 454.40 0.36
December 0.874207E+09 1856486.64 0.00 43517.88 2271459.76 0.286703E+09 16671129.83 0.00 0.29
                   
Annual Sum or Average 0.453976E+10 0.908079E+10 107559.24 11850966.00 0.128494E+09 0.166877E+10 0.310373E+10 454.40 0.47
Minimum of Months 0.00 0.00 0.00 0.00 265286.04 0.00 0.00 0.00 0.27
Maximum of Months 0.874207E+09 0.289113E+10 107559.24 3121053.96 29847150.47 0.885892E+09 0.732239E+09 454.40 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.119567E+10 0.00 0.00 1578857.85 2832924.64 0.101353E+10 0.861565E+09 0.00 0.36
February 0.115883E+10 0.00 0.00 2640949.84 419162.53 0.482776E+09 0.998955E+09 0.00 0.50
March 0.119837E+10 70009545.17 0.00 4330873.40 7373552.73 18814672.34 0.141977E+10 0.00 0.65
April 0.621903E+09 0.111480E+09 0.00 4039355.15 8811469.95 6325682.72 0.860341E+09 0.00 0.64
May 0.187678E+09 0.687525E+09 0.00 1522363.11 18517021.28 0.00 0.263072E+09 0.00 0.49
June 82639615.31 0.236578E+10 0.00 826288.90 15955106.74 0.00 0.123918E+09 0.00 0.46
July 0.00 0.324925E+10 0.00 0.00 48300765.77 0.00 0.00 0.00 0.38
August 609107.89 0.422896E+10 0.00 7394.65 30885436.21 0.00 490111.00 0.00 0.45
September 0.113975E+09 0.162746E+10 0.00 2083388.27 29522708.20 0.00 0.214671E+09 0.00 0.56
October 0.789689E+09 0.469024E+09 0.00 4822493.80 6478931.92 13862341.62 0.158685E+10 0.00 0.71
November 0.115284E+10 15093889.24 0.00 5050290.70 33816355.13 58284384.97 0.164890E+10 0.00 0.63
December 0.133492E+10 9384296.26 0.00 3039890.75 2636643.36 0.301094E+09 0.121744E+10 0.00 0.47
                   
Annual Sum or Average 0.783712E+10 0.128340E+11 0.00 29942146.42 0.205550E+09 0.189469E+10 0.919597E+10 0.00 0.52
Minimum of Months 0.00 0.00 0.00 0.00 419162.53 0.00 0.00 0.00 0.36
Maximum of Months 0.133492E+10 0.422896E+10 0.00 5050290.70 48300765.77 0.101353E+10 0.164890E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.644103E+09 0.00 0.00 29021.16 1797295.04 0.107471E+10 39391727.65 0.00 0.33
February 0.786040E+09 0.00 0.00 477162.22 265929.68 0.508097E+09 0.151736E+09 0.00 0.41
March 0.937438E+09 44612822.69 0.00 1632525.37 5485988.73 18484596.04 0.532187E+09 0.00 0.58
April 0.414923E+09 75237511.81 0.00 2803167.29 5530445.71 5509416.00 0.571193E+09 0.00 0.69
May 0.106397E+09 0.523298E+09 0.00 1274290.82 6951797.87 0.00 0.240961E+09 0.00 0.60
June 51204362.29 0.189517E+10 0.00 748352.02 5843301.06 0.00 0.105149E+09 0.00 0.60
July 0.00 0.255644E+10 0.00 0.00 20922275.72 0.00 0.00 0.00 0.46
August 386436.89 0.308084E+10 0.00 6473.83 8308672.61 0.00 310447.93 0.00 0.51
September 72889843.10 0.103051E+10 0.00 1162407.00 17976599.21 0.00 0.112583E+09 0.00 0.54
October 0.656753E+09 0.248029E+09 0.00 1442667.72 4554196.66 9290989.67 0.478250E+09 0.00 0.53
November 0.989145E+09 6044854.27 107762.95 803108.30 23468644.36 85534587.30 0.285188E+09 512.74 0.45
December 0.983755E+09 2066994.50 0.00 135024.46 3270992.05 0.392879E+09 70501554.41 0.00 0.36
                   
Annual Sum or Average 0.564303E+10 0.946224E+10 107762.95 10514200.18 0.104376E+09 0.209450E+10 0.258745E+10 512.74 0.51
Minimum of Months 0.00 0.00 0.00 0.00 265929.68 0.00 0.00 0.00 0.33
Maximum of Months 0.989145E+09 0.308084E+10 107762.95 2803167.29 23468644.36 0.107471E+10 0.571193E+09 512.74 0.69



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:06

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.187107E+12 0.106504E+11 0.00 0.188021E+12 0.612975E+10
February 0.185298E+12 0.873734E+10 0.00 0.181527E+12 0.161737E+11
March 0.266977E+12 0.570051E+10 0.00 0.192667E+12 0.496148E+11
April 0.296226E+12 0.260127E+10 0.00 0.124743E+12 0.884035E+11
May 0.324886E+12 -305108086.6 0.00 0.367682E+11 0.169554E+12
June 0.314975E+12 -0.404255E+10 0.00 -0.178022E+11 0.256704E+12
July 0.305366E+12 -0.578185E+10 0.00 -0.612106E+11 0.294865E+12
August 0.284865E+12 -0.714955E+10 0.00 -0.740823E+11 0.330076E+12
September 0.223413E+12 -0.198194E+10 0.00 -0.294343E+10 0.199545E+12
October 0.215441E+12 0.277496E+10 0.00 0.138416E+12 0.864757E+11
November 0.159158E+12 0.577797E+10 0.00 0.176685E+12 0.334175E+11
December 0.152819E+12 0.926032E+10 0.00 0.207500E+12 0.119311E+11
           
Annual Sum or Average 0.291653E+13 0.262418E+11 0.00 0.109029E+13 0.154289E+13
Minimum of Months 0.152819E+12 -0.714955E+10 0.00 -0.740823E+11 0.612975E+10
Maximum of Months 0.324886E+12 0.106504E+11 0.00 0.207500E+12 0.330076E+12