Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:21:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2209.36 | 443.45 | 443.45 |
Net Site Energy | 2209.36 | 443.45 | 443.45 |
Total Source Energy | 5164.05 | 1036.50 | 1036.50 |
Net Source Energy | 5164.05 | 1036.50 | 1036.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 879.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 139.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1329.38 | 879.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 879.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 139.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 94.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 4.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 879.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 139.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 94.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 4.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.00 | 176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 266.83 | 176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 60.00 | 176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 266.83 | 176.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1329.383 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1329.383 | 100.00 |
Total On-Site and Utility Electric Sources | 1329.383 | 100.00 |
Total Electricity End Uses | 1329.383 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 700.83 |
Time Setpoint Not Met During Occupied Cooling | 117.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3009.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-07:19 | 02-FEB-07:00 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 338062.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41699.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32937.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3542.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 172252.15 | 338062.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 338062.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 72984.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 32937.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 3542.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 953.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 442.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 736.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 162.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 300.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4210.16 | 953.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 191.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 845.04 | 191.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 191.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 845.04 | 191.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.66 | 0.281317 | 0.239000 | 0.636718 | 0.750179 | 0.500000 | 0.001354 | 0.000136 | 0.636718 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.15 | 0.349329 | 0.297000 | 0.637188 | 0.931543 | 0.500000 | 0.001091 | 0.000232 | 0.825623 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.24 | 0.335243 | 0.285000 | 0.637135 | 0.893980 | 0.500000 | 0.001136 | 0.000409 | 1.46 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.694762 | 0.227404 | 0.195000 | 0.135479 | 0.606411 | 0.500000 | 0.001675 | 0.000194 | 0.694762 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.846899 | 0.118104 | 0.100000 | 0.084690 | 0.314943 | 0.500000 | 0.003226 | 0.000126 | 0.450024 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.02 | 0.154868 | 0.132000 | 0.134662 | 0.412982 | 0.500000 | 0.002460 | 0.000192 | 0.687403 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.922413 | 0.108428 | 0.092000 | 0.084862 | 0.300000 | 0.500000 | 0.003514 | 0.000127 | 0.454601 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.535930 | 0.294799 | 0.251000 | 0.134518 | 0.786131 | 0.500000 | 0.001292 | 0.000149 | 0.534500 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.686808 | 0.145633 | 0.124000 | 0.085164 | 0.388354 | 0.500000 | 0.002616 | 0.000097 | 0.348328 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.810634 | 0.194899 | 0.166000 | 0.134565 | 0.519730 | 0.500000 | 0.001955 | 0.000148 | 0.528264 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.729178 | 0.137162 | 0.117000 | 0.085314 | 0.365764 | 0.500000 | 0.002778 | 0.000099 | 0.352427 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.598749 | 0.263870 | 0.224000 | 0.134120 | 0.703652 | 0.500000 | 0.001444 | 0.000152 | 0.541979 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.833112 | 0.320155 | 0.500000 | 0.003173 | 0.000099 | 0.352736 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.929331 | 0.170006 | 0.145000 | 0.134753 | 0.453349 | 0.500000 | 0.002241 | 0.000150 | 0.535214 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.854994 | 0.116978 | 0.099000 | 0.084644 | 0.311940 | 0.500000 | 0.003257 | 0.000100 | 0.356847 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15567.38 | 0.000136 | 371.19 |
CORE_MID VAV BOX REHEAT COIL | 26494.78 | 0.000232 | 699.87 |
CORE_TOP VAV BOX REHEAT COIL | 46753.30 | 0.000409 | 1233.66 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22201.42 | 0.000194 | 585.32 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14380.25 | 0.000126 | 379.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21966.56 | 0.000192 | 579.13 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14526.32 | 0.000127 | 382.97 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17086.81 | 0.000149 | 450.56 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11134.74 | 0.000097 | 293.60 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16887.81 | 0.000148 | 445.32 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11265.56 | 0.000099 | 297.05 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17325.22 | 0.000152 | 456.84 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11275.22 | 0.000099 | 297.30 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 17109.33 | 0.000150 | 451.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11406.44 | 0.000100 | 300.76 |
PACU_VAV_BOT HEATING COIL | 40043.05 | 0.000350 | 630.53 |
PACU_VAV_MID HEATING COIL | 40875.48 | 0.000358 | 637.07 |
PACU_VAV_TOP HEATING COIL | 39577.50 | 0.000346 | 629.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.71 | 1.08 | 5.43 | 2.19 | 4.73 | 4.73 | 0.300000 | 0.462567 | 4.73 |
PACU_VAV_MID | 2.68 | 1.08 | 5.36 | 2.61 | 4.43 | 4.43 | 0.300000 | 0.589485 | 4.43 |
PACU_VAV_TOP | 2.86 | 1.08 | 5.72 | 3.75 | 5.11 | 5.11 | 0.300000 | 0.732689 | 5.11 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.73 |
PACU_VAV_MID_OA_CONTROLLER | 4.43 |
PACU_VAV_TOP_OA_CONTROLLER | 5.11 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.73 | 99739.25 | 0.755656 | 1.58 | 33243.09 | 0.755656 |
PACU_VAV_MID COOLING COIL | 4.43 | 95277.64 | 0.749079 | 1.48 | 31756.04 | 0.749079 |
PACU_VAV_TOP COOLING COIL | 5.11 | 106227.47 | 0.762006 | 1.70 | 35405.61 | 0.762006 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.73 |
PACU_VAV_MID FAN | 4.43 |
PACU_VAV_TOP FAN | 5.11 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000350 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000358 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000346 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003463 | 0.415597 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003463 | 1032.67 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 395877.16 | 395877.16 | 0.003463 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2394E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2460E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3767E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3823E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2411E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2870E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3624E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3867E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1708 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2019E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1948 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1049 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1170 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0052E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8200E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8082E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2396E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2471E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.3768E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3836E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2426E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2948E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3621E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3864E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.7422E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4954E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3751E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2027E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4302E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7446E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6593E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6671E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9282E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9549E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6202E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6395E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2150E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2217E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0914E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0997E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6891E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7473E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9172E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9641E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3994E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4341E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3621E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3864E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4956E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5757E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4661E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9646E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1861E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3440E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8200E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8082E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6889E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7478E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9165E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9629E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3980E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4286E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3624E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3867E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6951E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9834E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0577E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5557E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5985E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3517E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6593E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6671E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2657E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3430E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7826E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8682E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7100E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7406E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0916E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0999E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1701 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1107 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1908 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1254 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1254 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3337E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4952E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5650E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.4859E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3484E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1427E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0692E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2537E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6396E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5541E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6039E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1179E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.3521E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0190E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6319E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7391E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9541E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4952E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5650E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4730E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8600E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8687E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4523E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4470E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2637E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5542E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6040E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1701 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1106 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1908 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1254 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1254 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3329E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4947E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5647E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.4858E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3481E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1425E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0689E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2533E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6392E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5536E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6036E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1181E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.3520E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0191E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6317E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7389E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9540E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4947E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5647E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4730E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8598E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8687E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4521E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4466E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2634E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5536E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6037E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 35274.61881 | 35274.61881 | 2.66409 | 2.66409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9452.46139 | 9452.46139 | 0.42520 | 0.42520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28433.47653 | 28433.47653 | 2.14542 | 2.14542 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18565.65196 | 18565.65196 | 0.82562 | 0.82562 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29348.06217 | 29348.06217 | 2.23556 | 2.23556 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 31.09400 | 1.53649E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 32728.28642 | 32728.28642 | 1.46036 | 1.46036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9021.47673 | 9021.47673 | 0.68724 | 0.68724 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15533.35511 | 15533.35511 | 0.69476 | 0.69476 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11117.40899 | 11117.40899 | 0.84690 | 0.84690 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10061.17233 | 10061.17233 | 0.45002 | 0.45002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13391.90586 | 13391.90586 | 1.02017 | 1.02017 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15369.15603 | 15369.15603 | 0.68740 | 0.68740 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12108.72065 | 12108.72065 | 0.92241 | 0.92241 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10163.29706 | 10163.29706 | 0.45460 | 0.45460 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7035.38733 | 7035.38733 | 0.53593 | 0.53593 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11955.82463 | 11955.82463 | 0.53450 | 0.53450 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9016.13194 | 9016.13194 | 0.68681 | 0.68681 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7790.96370 | 7790.96370 | 0.34833 | 0.34833 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10641.62366 | 10641.62366 | 0.81063 | 0.81063 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11816.70732 | 11816.70732 | 0.52826 | 0.52826 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9572.36282 | 9572.36282 | 0.72918 | 0.72918 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7882.41881 | 7882.41881 | 0.35243 | 0.35243 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7859.89117 | 7859.89117 | 0.59875 | 0.59875 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 12123.59784 | 12123.59784 | 0.54198 | 0.54198 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10936.55376 | 10936.55376 | 0.83311 | 0.83311 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53537E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7889.89997 | 7889.89997 | 0.35274 | 0.35274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 12199.58747 | 12199.58747 | 0.92933 | 0.92933 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11972.66309 | 11972.66309 | 0.53521 | 0.53521 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11223.80617 | 11223.80617 | 0.85499 | 0.85499 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7981.63943 | 7981.63943 | 0.35685 | 0.35685 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 69072.16 | 4.73058 | 4.73058 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 42784.33 | 2.18821 | 2.18821 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 65132.54 | 4.43167 | 4.43167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 42943.00 | 2.61240 | 2.61240 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73866.48 | 5.11424 | 5.11424 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 42997.75 | 3.74715 | 3.74715 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.66409 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28132 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63672 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75018 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35434E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36190E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63672 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15567.38110 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36190E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 371.18778 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.14542 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34933 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63719 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93154 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09066E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.31788E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.82562 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26494.77626 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31788E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 699.86708 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23556 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33524 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63713 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89398 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13649E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.09018E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.46036 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 46753.29876 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.09018E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1233.66338 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69476 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22740 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13548 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60641 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67543E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94228E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69476 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22201.42002 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94228E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 585.32333 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84690 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11810 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46899E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31494 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22598E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25805E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14380.25233 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25805E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 379.11854 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02017 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15487 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13466 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41298 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46015E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92173E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68740 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21966.56430 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92173E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 579.13499 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92241 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10843 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.20000E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48620E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.51386E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27083E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45460 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14526.32224 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27083E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 382.96739 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53593 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29480 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78613 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29241E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49483E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53450 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17086.80514 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49483E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.56038 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68681 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14563 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51642E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38835 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61617E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.74116E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34833 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11134.73926 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.74116E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 293.60426 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81063 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19490 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16600 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13457 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51973 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95486E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47742E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52826 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16887.80718 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47742E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 445.31695 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72918 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13716 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53139E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36576 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77775E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.85560E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35243 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11265.55878 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.85560E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.05124 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59875 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26387 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22400 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13412 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70365 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44389E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51569E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54198 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17325.22315 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51569E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 456.83911 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83311 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32015 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17346E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.86405E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35274 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11275.21819 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.86405E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 297.30328 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92933 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17001 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14500 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13475 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45335 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24110E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49680E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53521 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17109.32919 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49680E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 451.15047 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85499 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11698 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.90000E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46444E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31194 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25703E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.97885E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35685 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11406.43982 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.97885E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.76085 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.71332 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07628 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.42664 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.18821 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.73058 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.73058 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.46257 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.68080 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07568 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.36160 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.61240 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.43167 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.43167 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.58948 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.85990 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07683 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.71980 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.74715 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.11424 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.11424 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.73269 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.73058 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.43167 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.11424 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.73058 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.73058 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99739.25020 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75566 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.57670 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33243.09209 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75566 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 40043.04690 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50314E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 630.53095 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.73058 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.50314E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.43167 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.43167 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95277.64108 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74908 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.47707 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31756.03777 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74908 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 40875.48062 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.57597E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 637.07461 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.43167 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.57597E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.11424 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.11424 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106227.46636 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76201 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.70458 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35405.61454 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76201 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 39577.49905 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.46241E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 629.63933 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.11424 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.46241E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.46331E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.41560 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.46331E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1032.66902 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 395877.16230 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 395877.16000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.46331E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14748.97 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25111.74 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 44303.81 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21034.90 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13624.64 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20812.41 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13763.02 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16189.56 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10550.00 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16001.04 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10673.93 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16415.40 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10683.06 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16210.87 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10807.38 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 28075.39 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 28008.15 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 28381.10 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 99024.15 | 337884.44 | 12.26 | 3.13 | 3.51 | 3.70 | 3.87 | 10.69 | 11.98 | 12.61 | 13.22 | 5.2188 | 4.1601 | 2.8006 | 1.1493 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 94662.04 | 323000.30 | 12.30 | 3.14 | 3.52 | 3.71 | 3.88 | 10.72 | 12.03 | 12.66 | 13.25 | 4.8890 | 3.8979 | 2.6243 | 1.0815 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 105407.13 | 359664.07 | 12.22 | 3.13 | 3.50 | 3.68 | 3.87 | 10.66 | 11.94 | 12.57 | 13.20 | 5.6420 | 4.5040 | 3.0335 | 1.2347 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.0484163575E-002 | 3.0656384535E-002 | Pass | Pass | 0.4898602019 | 0.4934142874 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1246321185 | 8.4005415980E-002 | Pass | Pass | 0.4941337029 | 0.4810409764 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3452919436E-002 | 3.3408829676E-002 | Pass | Pass | 0.4927741291 | 0.4687252545 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7637243779E-002 | 3.7097184352E-002 | Pass | Pass | 0.4943751445 | 0.4691010572 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1358645529E-003 | 7.0307356735E-003 | Pass | Pass | 0.4951860164 | 0.4885401126 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1036559645 | 0.1023851025 | Pass | Pass | 29.1500618748 | 78.5627180609 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4126695675 | 0.4001888324 | Pass | Pass | 29.1876291868 | 134.3493993403 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4335439451 | 0.4273940327 | Pass | Pass | 97.5721966404 | 247.0898582962 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3918431192 | 0.3997683694 | Pass | Pass | 102.1020902317 | 392.7862084133 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4416884263 | 0.4281815327 | Pass | Pass | 88.5835596630 | 229.6404854984 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2928661715 | 0.2772316135 | Pass | Pass | 67.8861795734 | 312.2660906895 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3066681484 | 0.2934445372 | Pass | Pass | 27.2308889275 | 67.4962611103 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2562996923 | 0.2631392009 | Pass | Pass | 21.7266470551 | 56.2322287588 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3150980336 | 0.2958181475 | Pass | Pass | 27.7469628719 | 68.6022108669 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3016783003 | 0.2841145822 | Pass | Pass | 28.1254242222 | 70.8186462019 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3078095895 | 0.2996791957 | Pass | Pass | 27.9901891336 | 67.0708644351 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2648483053 | 0.2767622051 | Pass | Pass | 26.0564739559 | 66.1526566191 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3145075863 | 0.2985471178 | Pass | Pass | 27.3032129835 | 65.8408597996 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3609.81 | 130.66 | 0.00 | 1753.75 | 998.36 | 6492.57 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 195.79 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.12 | 0.0000 | Y | 6.77 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 4.25 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.05 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.92 | 0.0000 | Y | 4.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.69 | 0.0000 | Y | 6.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.82 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.12 | 0.0000 | Y | 6.77 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.86 | 0.0000 | Y | 4.25 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.62 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.24 | 42.24 | 4.47 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.63 | 62.93 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.63 | 47.43 | 41.98 | |
Exterior Lighting Total | 5686.19 | 51.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 395877.16 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99739.25 | 75368.54 | 24370.71 | 0.76 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95277.64 | 71370.50 | 23907.14 | 0.75 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106227.47 | 80945.96 | 25281.51 | 0.76 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 99024.2 | 3.13 | 10.69 | N/A | N/A | 12.26 | |
PACU_VAV_MID COOLING COIL | 94662.0 | 3.14 | 10.72 | N/A | N/A | 12.30 | |
PACU_VAV_TOP COOLING COIL | 105407.1 | 3.13 | 10.66 | N/A | N/A | 12.22 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15567.38 | 14748.97 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 26494.78 | 25111.74 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 46753.30 | 44303.81 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22201.42 | 21034.90 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14380.25 | 13624.64 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21966.56 | 20812.41 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14526.32 | 13763.02 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17086.81 | 16189.56 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11134.74 | 10550.00 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16887.81 | 16001.04 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11265.56 | 10673.93 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17325.22 | 16415.40 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11275.22 | 10683.06 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17109.33 | 16210.87 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11406.44 | 10807.38 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 40043.05 | 28075.39 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 40875.48 | 28008.15 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 39577.50 | 28381.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.73 | 10943.66 | 2313.39 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.43 | 10252.16 | 2313.39 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.11 | 11754.89 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003463 | 1032.67 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 99024.15 | 3.13 | 10.69 | 12.26 | 5.2188 | 3.51 | 11.98 | 4.1601 | 3.70 | 12.61 | 2.8006 | 3.87 | 13.22 | 1.1493 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94662.04 | 3.14 | 10.72 | 12.30 | 4.8890 | 3.52 | 12.03 | 3.8979 | 3.71 | 12.66 | 2.6243 | 3.88 | 13.25 | 1.0815 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105407.13 | 3.13 | 10.66 | 12.22 | 5.6420 | 3.50 | 11.94 | 4.5040 | 3.68 | 12.57 | 3.0335 | 3.87 | 13.20 | 1.2347 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 35274.62 | 35274.62 | 35.87 | 2.664 | 2.664 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 28433.48 | 28433.48 | 28.91 | 2.145 | 2.145 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 29348.06 | 29348.06 | 29.84 | 2.236 | 2.236 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 31.09 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9021.48 | 9021.48 | 43.51 | 0.687 | 0.687 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00898 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11117.41 | 11117.41 | 84.70 | 0.847 | 0.847 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00876 | 25.67 | 0.01535 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13391.91 | 13391.91 | 64.59 | 1.020 | 1.020 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00883 | 30.93 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12108.72 | 12108.72 | 92.25 | 0.922 | 0.922 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00874 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7035.39 | 7035.39 | 33.93 | 0.536 | 0.536 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00900 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9016.13 | 9016.13 | 68.69 | 0.687 | 0.687 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00875 | 26.27 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10641.62 | 10641.62 | 51.32 | 0.811 | 0.811 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00883 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9572.36 | 9572.36 | 72.93 | 0.729 | 0.729 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00874 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7859.89 | 7859.89 | 37.91 | 0.599 | 0.599 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00901 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10936.55 | 10936.55 | 83.32 | 0.833 | 0.833 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00874 | 25.03 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 12199.59 | 12199.59 | 58.84 | 0.929 | 0.929 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00883 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11223.81 | 11223.81 | 85.51 | 0.855 | 0.855 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00873 | 29.54 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9452.46 | 9452.46 | 9.61 | 0.425 | 0.425 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 18565.65 | 18565.65 | 18.88 | 0.826 | 0.826 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 32728.29 | 32728.29 | 33.28 | 1.460 | 1.460 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15533.36 | 15533.36 | 74.92 | 0.695 | 0.695 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10061.17 | 10061.17 | 76.65 | 0.450 | 0.450 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15369.16 | 15369.16 | 74.13 | 0.687 | 0.687 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10163.30 | 10163.30 | 77.43 | 0.455 | 0.455 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11955.82 | 11955.82 | 57.66 | 0.534 | 0.534 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7790.96 | 7790.96 | 59.35 | 0.348 | 0.348 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11816.71 | 11816.71 | 56.99 | 0.528 | 0.528 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7882.42 | 7882.42 | 60.05 | 0.352 | 0.352 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 12123.60 | 12123.60 | 58.47 | 0.542 | 0.542 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7889.90 | 7889.90 | 60.11 | 0.353 | 0.353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11972.66 | 11972.66 | 57.74 | 0.535 | 0.535 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7981.64 | 7981.64 | 60.81 | 0.357 | 0.357 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.73 | 4.73 | 2.19 | 2.19 | 4.7306 | 2.1882 | 4.7306 | 0.4626 | 0.3000 |
PACU_VAV_MID | 4.43 | 4.43 | 2.61 | 2.61 | 4.4317 | 2.6124 | 4.4317 | 0.5895 | 0.3000 |
PACU_VAV_TOP | 5.11 | 5.11 | 3.75 | 3.75 | 5.1142 | 3.7472 | 5.1142 | 0.7327 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15567.381 | 15567.381 | 0.636718 | 0.00013619 | 371.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 15567.38 | 15567.38 | 0.636718 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 9452.46 | 0.00 | 15618.03 | 15618.03 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26494.776 | 26494.776 | 0.825623 | 0.00023179 | 699.867 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26494.78 | 26494.78 | 0.825623 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 18565.65 | 0.00 | 26589.82 | 26589.82 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 46753.299 | 46753.299 | 1.460360 | 0.00040902 | 1233.663 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46753.30 | 46753.30 | 1.460360 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 32728.29 | 0.00 | 46911.41 | 46911.41 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22201.420 | 22201.420 | 0.694762 | 0.00019423 | 585.323 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22201.42 | 22132.69 | 0.694762 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774891 | 47.8042 | 15533.36 | 0.00 | 22272.91 | 22272.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14380.252 | 14380.252 | 0.450024 | 0.00012580 | 379.119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14380.25 | 14380.25 | 0.450024 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774186 | 47.7614 | 10061.17 | 0.00 | 14426.52 | 14426.52 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21966.564 | 21966.564 | 0.687403 | 0.00019217 | 579.135 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21966.56 | 21966.56 | 0.687403 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774627 | 47.7882 | 15369.16 | 0.00 | 22037.33 | 22037.33 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14526.322 | 14526.322 | 0.454601 | 0.00012708 | 382.967 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14526.32 | 14526.32 | 0.454601 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774440 | 47.7769 | 10163.30 | 0.00 | 14573.04 | 14573.04 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17086.805 | 17086.805 | 0.534500 | 0.00014948 | 450.560 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17086.81 | 17072.86 | 0.534500 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00782059 | 48.2392 | 11955.82 | 0.00 | 17142.41 | 17142.41 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11134.739 | 11134.739 | 0.348328 | 0.00009741 | 293.604 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11134.74 | 11134.74 | 0.348328 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781745 | 48.2201 | 7790.96 | 0.00 | 11170.92 | 11170.92 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16887.807 | 16887.807 | 0.528264 | 0.00014774 | 445.317 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16887.81 | 16887.81 | 0.528264 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781810 | 48.2239 | 11816.71 | 0.00 | 16942.79 | 16942.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11265.559 | 11265.559 | 0.352427 | 0.00009856 | 297.051 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11265.56 | 11265.56 | 0.352427 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00781986 | 48.2347 | 7882.42 | 0.00 | 11302.15 | 11302.15 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17325.223 | 17325.223 | 0.541979 | 0.00015157 | 456.839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17325.22 | 17325.22 | 0.541979 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772921 | 47.6837 | 12123.60 | 0.00 | 17381.54 | 17381.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11275.218 | 11275.218 | 0.352736 | 0.00009864 | 297.303 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11275.22 | 11275.22 | 0.352736 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772359 | 47.6496 | 7889.90 | 0.00 | 11311.82 | 11311.82 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 17109.329 | 17109.329 | 0.535214 | 0.00014968 | 451.150 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17109.33 | 17109.33 | 0.535214 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772553 | 47.6613 | 11972.66 | 0.00 | 17164.97 | 17164.97 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11406.440 | 11406.440 | 0.356847 | 0.00009979 | 300.761 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11406.44 | 11406.44 | 0.356847 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00772694 | 47.6700 | 7981.64 | 0.00 | 11443.45 | 11443.45 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 99739.250 | 75368.537 | 4.730580 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 101325.97 | 78572.43 | 4.730580 | 25.45 | 17.78 | 0.01018977 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 20.2111 | 24.00 | 0.00887842 | 45.5627 | 62085.64 | 0.00 | 102844.56 | 74836.20 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 40043.047 | 40043.047 | 1.419174 | 0.00035031 | 630.531 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40043.05 | 40043.05 | 1.419174 | -11.65 | -11.65 | 0.00273060 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 67.3702 | 18.30 | 0.00762722 | 55.6474 | 15583.07 | 0.00 | 33952.21 | 33952.21 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95277.641 | 71370.500 | 4.431666 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 97073.18 | 74065.75 | 4.431666 | 25.55 | 17.92 | 0.01032492 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 21.5743 | 24.00 | 0.00893559 | 45.8524 | 58083.97 | 0.00 | 98244.04 | 70932.12 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 40875.481 | 40875.481 | 1.329500 | 0.00035760 | 637.075 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40875.48 | 40875.48 | 1.329500 | -13.84 | -13.84 | 0.00236373 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 71.9143 | 17.38 | 0.00711425 | 55.0450 | 15737.38 | 0.00 | 33863.50 | 33863.50 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 106227.466 | 80945.957 | 5.114242 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 107696.71 | 84312.94 | 5.114242 | 25.35 | 17.68 | 0.01010668 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 18.6949 | 24.00 | 0.00889356 | 45.6398 | 66955.04 | 0.00 | 109534.78 | 80353.18 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 39577.499 | 39577.499 | 1.534273 | 0.00034624 | 629.639 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39577.50 | 39577.50 | 1.534273 | -9.55 | -9.55 | 0.00304925 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 62.3162 | 16.10 | 0.00762177 | 63.9117 | 15366.90 | 0.00 | 34328.18 | 34328.18 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15567.381 | 15567.381 | 0.636718 | 0.00013619 | 371.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 3.8548 | 3.932377 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 15567.38 | 15567.38 | 1.0000 | 0.73130669 | 0.636718 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.13617635 | 60.00 | 32.22 | 27.78 | 0.000 | 15567.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 9452.46 | 0.00 | 15618.03 | 15618.03 | 0.73130669 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.74 | 19.26 | 0.00800000 | 54416.2 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 26494.776 | 26494.776 | 0.825623 | 0.00023179 | 699.867 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 6.5606 | 6.692676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26494.78 | 26494.78 | 1.0000 | 0.94827437 | 0.825623 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.23176422 | 60.00 | 32.22 | 27.78 | 0.000 | 26494.78 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 18565.65 | 0.00 | 26589.82 | 26589.82 | 0.94827437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61100.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 46753.299 | 46753.299 | 1.460360 | 0.00040902 | 1233.663 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 11.5771 | 11.810052 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46753.30 | 46753.30 | 1.0000 | 1.67730499 | 1.460360 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.40897653 | 60.00 | 32.22 | 27.78 | 0.000 | 46753.30 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 32728.29 | 0.00 | 46911.41 | 46911.41 | 1.67730499 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61028.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22201.420 | 22201.420 | 0.694762 | 0.00019423 | 585.323 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 5.4975 | 5.608159 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22201.42 | 22132.69 | 1.0000 | 0.79797258 | 0.694762 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.19420789 | 60.00 | 32.22 | 27.78 | 0.000 | 22201.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774891 | 21.00 | 0.00774891 | 47.8042 | 15533.36 | 0.00 | 22272.91 | 22272.91 | 0.79797258 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14380.252 | 14380.252 | 0.450024 | 0.00012580 | 379.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 3.5608 | 3.632504 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14380.25 | 14380.25 | 1.0000 | 0.51687807 | 0.450024 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12579189 | 60.00 | 32.22 | 27.78 | 0.000 | 14380.25 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774186 | 21.00 | 0.00774186 | 47.7614 | 10061.17 | 0.00 | 14426.52 | 14426.52 | 0.51687807 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21966.564 | 21966.564 | 0.687403 | 0.00019217 | 579.135 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 5.4394 | 5.548833 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21966.56 | 21966.56 | 1.0000 | 0.78952100 | 0.687403 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.19215348 | 60.00 | 32.22 | 27.78 | 0.000 | 21966.56 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774627 | 21.00 | 0.00774627 | 47.7882 | 15369.16 | 0.00 | 22037.33 | 22037.33 | 0.78952100 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14526.322 | 14526.322 | 0.454601 | 0.00012708 | 382.967 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 3.5970 | 3.669401 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14526.32 | 14526.32 | 1.0000 | 0.52213463 | 0.454601 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.12706964 | 60.00 | 32.22 | 27.78 | 0.000 | 14526.32 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774440 | 21.00 | 0.00774440 | 47.7769 | 10163.30 | 0.00 | 14573.04 | 14573.04 | 0.52213463 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60970.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17086.805 | 17086.805 | 0.534500 | 0.00014948 | 450.560 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 4.2310 | 4.316189 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17086.81 | 17072.86 | 1.0000 | 0.61390255 | 0.534500 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14946758 | 60.00 | 32.22 | 27.78 | 0.000 | 17086.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00782059 | 21.00 | 0.00782059 | 48.2392 | 11955.82 | 0.00 | 17142.41 | 17142.41 | 0.61390255 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11134.739 | 11134.739 | 0.348328 | 0.00009741 | 293.604 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 2.7572 | 2.812675 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11134.74 | 11134.74 | 1.0000 | 0.40007382 | 0.348328 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09740162 | 60.00 | 32.22 | 27.78 | 0.000 | 11134.74 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781745 | 21.00 | 0.00781745 | 48.2201 | 7790.96 | 0.00 | 11170.92 | 11170.92 | 0.40007382 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16887.807 | 16887.807 | 0.528264 | 0.00014774 | 445.317 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 4.1818 | 4.265921 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16887.81 | 16887.81 | 1.0000 | 0.60674116 | 0.528264 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14772683 | 60.00 | 32.22 | 27.78 | 0.000 | 16887.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781810 | 21.00 | 0.00781810 | 48.2239 | 11816.71 | 0.00 | 16942.79 | 16942.79 | 0.60674116 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60984.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11265.559 | 11265.559 | 0.352427 | 0.00009856 | 297.051 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 2.7896 | 2.845721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11265.56 | 11265.56 | 1.0000 | 0.40478169 | 0.352427 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09854597 | 60.00 | 32.22 | 27.78 | 0.000 | 11265.56 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00781986 | 21.00 | 0.00781986 | 48.2347 | 7882.42 | 0.00 | 11302.15 | 11302.15 | 0.40478169 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17325.223 | 17325.223 | 0.541979 | 0.00015157 | 456.839 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 4.2901 | 4.376414 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17325.22 | 17325.22 | 1.0000 | 0.62249267 | 0.541979 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.15155315 | 60.00 | 32.22 | 27.78 | 0.000 | 17325.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772921 | 21.00 | 0.00772921 | 47.6837 | 12123.60 | 0.00 | 17381.54 | 17381.54 | 0.62249267 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11275.218 | 11275.218 | 0.352736 | 0.00009864 | 297.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 2.7920 | 2.848161 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11275.22 | 11275.22 | 1.0000 | 0.40513669 | 0.352736 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09863047 | 60.00 | 32.22 | 27.78 | 0.000 | 11275.22 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772359 | 21.00 | 0.00772359 | 47.6496 | 7889.90 | 0.00 | 11311.82 | 11311.82 | 0.40513669 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17109.329 | 17109.329 | 0.535214 | 0.00014968 | 451.150 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 4.2366 | 4.321878 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17109.33 | 17109.33 | 1.0000 | 0.61472328 | 0.535214 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.14966461 | 60.00 | 32.22 | 27.78 | 0.000 | 17109.33 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772553 | 21.00 | 0.00772553 | 47.6613 | 11972.66 | 0.00 | 17164.97 | 17164.97 | 0.61472328 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11406.440 | 11406.440 | 0.356847 | 0.00009979 | 300.761 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 2.8245 | 2.881308 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11406.44 | 11406.44 | 1.0000 | 0.40985903 | 0.356847 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09977833 | 60.00 | 32.22 | 27.78 | 0.000 | 11406.44 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772694 | 21.00 | 0.00772694 | 47.6700 | 7981.64 | 0.00 | 11443.45 | 11443.45 | 0.40985903 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.3 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99739.250 | 75368.537 | 4.730580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7823 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.730580 | 5.43333474 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 101325.97 | 78572.43 | 1.0159 | 5.43333474 | 4.730580 | 25.45 | 17.78 | 0.01018977 | 51543.8 | 10.83 | 10.83 | 0.00850000 | 32314.2 | -999.0 | -999.00 | -999.00 | -999.00 | 10943.659 | 90382.31 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 20.2111 | 24.00 | 0.00887842 | 24.00 | 0.00887842 | 45.5627 | 62085.64 | 0.00 | 102844.56 | 74836.20 | 5.21875909 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.63 | 12.61 | 0.00908043 | 35615.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 40043.047 | 40043.047 | 1.419174 | 0.00035031 | 630.531 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.730580 | 5.43333474 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 9.9155 | 10.115018 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40043.05 | 40043.05 | 1.0000 | 1.63000042 | 1.419174 | -11.65 | -11.65 | 0.00273060 | -4933.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.35027831 | 60.00 | 32.22 | 27.78 | 0.000 | 40043.05 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 67.3702 | 18.40 | 0.00762237 | 18.30 | 0.00762722 | 55.6474 | 15583.07 | 0.00 | 33952.21 | 33952.21 | 1.63000042 | 2.80 | 0.13 | 0.00273060 | 9656.8 | 23.43 | 10.62 | 0.00273060 | 30486.4 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95277.641 | 71370.500 | 4.431666 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.0335 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.431666 | 5.09001580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 97073.18 | 74065.75 | 1.0188 | 5.09001580 | 4.431666 | 25.55 | 17.92 | 0.01032492 | 51990.7 | 10.83 | 10.83 | 0.00850000 | 32314.7 | -999.0 | -999.00 | -999.00 | -999.00 | 10252.157 | 86821.02 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 21.5743 | 24.00 | 0.00893559 | 24.00 | 0.00893559 | 45.8524 | 58083.97 | 0.00 | 98244.04 | 70932.12 | 4.88899866 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.46 | 12.45 | 0.00899436 | 35227.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 40875.481 | 40875.481 | 1.329500 | 0.00035760 | 637.075 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.431666 | 5.09001580 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 10.1216 | 10.325294 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40875.48 | 40875.48 | 1.0000 | 1.52700474 | 1.329500 | -13.84 | -13.84 | 0.00236373 | -8055.2 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.35756006 | 60.00 | 32.22 | 27.78 | 0.000 | 40875.48 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 71.9143 | 17.81 | 0.00749089 | 17.38 | 0.00711425 | 55.0450 | 15737.38 | 0.00 | 33863.50 | 33863.50 | 1.52700474 | 2.80 | -0.62 | 0.00236373 | 8737.4 | 24.77 | 10.81 | 0.00236373 | 30913.8 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106227.466 | 80945.957 | 5.114242 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6278 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.114242 | 5.87399211 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 107696.71 | 84312.94 | 1.0138 | 5.87399211 | 5.114242 | 25.35 | 17.68 | 0.01010668 | 51223.5 | 10.85 | 10.85 | 0.00850000 | 32326.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11754.888 | 95941.82 | 31.20 | 0.01536508 | 23.13 | 0.95610000 | 18.6949 | 24.00 | 0.00889356 | 24.00 | 0.00889356 | 45.6398 | 66955.04 | 0.00 | 109534.78 | 80353.18 | 5.64201383 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.73 | 12.72 | 0.00915676 | 35908.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 39577.499 | 39577.499 | 1.534273 | 0.00034624 | 629.639 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.114242 | 5.87399211 | 4197.9300 | 999.8980 | 3.46295282 | 54.44 | 82.22 | 27.78 | 403844.35 | 9.8002 | 9.997419 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39577.50 | 39577.50 | 1.0000 | 1.76219763 | 1.534273 | -9.55 | -9.55 | 0.00304925 | -2024.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.34620591 | 60.00 | 32.22 | 27.78 | 0.000 | 39577.50 | -26.20 | 0.00036134 | -26.20 | 0.95610000 | 62.3162 | 17.98 | 0.00749414 | 16.10 | 0.00762177 | 63.9117 | 15366.90 | 0.00 | 34328.18 | 34328.18 | 1.76219763 | 2.80 | 0.59 | 0.00304925 | 10455.4 | 22.08 | 10.38 | 0.00304925 | 29935.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.73 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.43 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.11 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2582.50 | 2804.17 | 413.00 |
CORE_MID | 3077.00 | 3500.67 | 1270.17 |
CORE_TOP | 3549.33 | 3757.17 | 1885.17 |
PERIMETER_TOP_ZN_3 | 4079.67 | 4058.83 | 2565.67 |
PERIMETER_TOP_ZN_2 | 4074.50 | 3891.67 | 2426.00 |
PERIMETER_TOP_ZN_1 | 3771.83 | 3719.00 | 2065.33 |
PERIMETER_TOP_ZN_4 | 4104.50 | 3918.00 | 2456.50 |
PERIMETER_BOT_ZN_3 | 3824.67 | 4107.33 | 2366.50 |
PERIMETER_BOT_ZN_2 | 3924.67 | 3791.00 | 2170.67 |
PERIMETER_BOT_ZN_1 | 3707.83 | 4032.67 | 2196.67 |
PERIMETER_BOT_ZN_4 | 3888.00 | 3816.17 | 2158.50 |
PERIMETER_MID_ZN_3 | 3887.17 | 3843.50 | 2190.50 |
PERIMETER_MID_ZN_2 | 3348.50 | 3204.83 | 1874.33 |
PERIMETER_MID_ZN_1 | 3608.00 | 3444.83 | 1713.50 |
PERIMETER_MID_ZN_4 | 3904.83 | 3698.83 | 2100.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5084.33 | 4634.00 | 3009.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.50 | 0.83 | 2.50 | 0.83 |
CORE_MID | 12.00 | 0.17 | 11.00 | 0.17 |
CORE_TOP | 33.67 | 0.00 | 28.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 312.50 | 6.00 | 195.67 | 3.50 |
PERIMETER_TOP_ZN_2 | 179.67 | 34.33 | 72.50 | 31.67 |
PERIMETER_TOP_ZN_1 | 159.00 | 30.67 | 65.67 | 27.50 |
PERIMETER_TOP_ZN_4 | 199.17 | 36.83 | 94.83 | 21.83 |
PERIMETER_BOT_ZN_3 | 229.50 | 0.50 | 192.00 | 0.50 |
PERIMETER_BOT_ZN_2 | 86.67 | 19.67 | 58.17 | 19.50 |
PERIMETER_BOT_ZN_1 | 626.17 | 29.83 | 608.83 | 29.50 |
PERIMETER_BOT_ZN_4 | 102.50 | 26.67 | 76.67 | 16.00 |
PERIMETER_MID_ZN_3 | 172.67 | 1.67 | 123.33 | 0.83 |
PERIMETER_MID_ZN_2 | 79.00 | 31.00 | 35.00 | 30.00 |
PERIMETER_MID_ZN_1 | 63.67 | 29.50 | 33.17 | 28.33 |
PERIMETER_MID_ZN_4 | 101.33 | 34.33 | 57.33 | 20.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 859.33 | 142.00 | 700.83 | 117.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.885 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.654 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.640 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.777 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.107 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.044 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.075 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.642 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.946 | 0.031 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.884 | 0.851 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.902 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.751 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.011 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.031 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.032 | 0.049 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14031095.30 | 0.00 | 14031095.30 | 0.00 | 14031095.30 | 13393058.27 | 5302.66 | 518.12 | 2939.22 | 234.08 |
CORE_MID | 10440444.80 | 0.00 | 10440444.80 | 0.00 | 10440444.80 | 13393058.27 | 5327.34 | 954.76 | 2477.90 | 282.69 |
CORE_TOP | 10219962.01 | 0.00 | 10219962.01 | 0.00 | 10219962.01 | 13393058.27 | 5512.96 | 934.43 | 2312.61 | 102.86 |
PERIMETER_TOP_ZN_3 | 2611114.01 | 0.00 | 2611114.01 | 375619.99 | 2986734.00 | 2823374.22 | 4366.47 | 408.51 | 3985.02 | 102.86 |
PERIMETER_TOP_ZN_2 | 2341574.18 | 0.00 | 2341574.18 | 250411.82 | 2591986.01 | 1787429.43 | 4499.72 | 1014.77 | 3245.51 | 102.86 |
PERIMETER_TOP_ZN_1 | 3489753.35 | 0.00 | 3489753.35 | 375619.99 | 3865373.34 | 2823374.22 | 4452.62 | 810.78 | 3496.60 | 102.86 |
PERIMETER_TOP_ZN_4 | 2295397.65 | 0.00 | 2295397.65 | 250411.82 | 2545809.47 | 1787312.18 | 4428.08 | 961.52 | 3370.40 | 102.86 |
PERIMETER_BOT_ZN_3 | 2164802.98 | 0.00 | 2164802.98 | 199714.28 | 2364517.26 | 2823374.22 | 5668.41 | 448.17 | 2643.42 | 234.08 |
PERIMETER_BOT_ZN_2 | 2004624.79 | 0.00 | 2004624.79 | 133142.05 | 2137766.84 | 1787429.43 | 5250.70 | 470.89 | 3038.41 | 234.08 |
PERIMETER_BOT_ZN_1 | 2975642.10 | 0.00 | 2975642.10 | 2957967.51 | 5933609.61 | 2823374.22 | 4863.21 | 405.45 | 3491.34 | 234.08 |
PERIMETER_BOT_ZN_4 | 1922149.05 | 0.00 | 1922149.05 | 133142.05 | 2055291.10 | 1787312.18 | 5260.01 | 430.00 | 3069.99 | 234.08 |
PERIMETER_MID_ZN_3 | 2525000.60 | 0.00 | 2525000.60 | 312674.11 | 2837674.71 | 2823374.22 | 4631.41 | 988.71 | 3139.88 | 282.69 |
PERIMETER_MID_ZN_2 | 2147473.45 | 0.00 | 2147473.45 | 208448.16 | 2355921.61 | 1601953.02 | 4377.83 | 756.83 | 3625.34 | 1191.69 |
PERIMETER_MID_ZN_1 | 3449390.29 | 0.00 | 3449390.29 | 312674.11 | 3762064.41 | 2823374.22 | 4444.54 | 769.69 | 3545.77 | 282.69 |
PERIMETER_MID_ZN_4 | 2201022.08 | 0.00 | 2201022.08 | 208448.16 | 2409470.23 | 1787312.18 | 4602.02 | 1119.32 | 3038.66 | 282.69 |
Total Facility | 64819446.65 | 0.00 | 64819446.65 | 5718274.06 | 70537720.70 | 67658168.57 | 6648.49 | 1726.13 | 4668.05 | 1291.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6485 | 0.0000 | 0.6485 | 0.0000 | 0.6485 | 0.4247 | 2537.69 | 518.12 | 2887.19 |
CORE_MID | 0.4804 | 0.0000 | 0.4804 | 0.0000 | 0.4804 | 0.4247 | 2568.26 | 954.60 | 2420.15 |
CORE_TOP | 0.4702 | 0.0000 | 0.4702 | 0.0000 | 0.4702 | 0.4247 | 2764.68 | 934.43 | 2243.89 |
PERIMETER_TOP_ZN_3 | 0.1204 | 0.0000 | 0.1204 | 0.0086 | 0.1291 | 0.0895 | 1618.19 | 408.51 | 3916.30 |
PERIMETER_TOP_ZN_2 | 0.1084 | 0.0000 | 0.1084 | 0.0058 | 0.1142 | 0.0567 | 1751.44 | 1014.77 | 3176.78 |
PERIMETER_TOP_ZN_1 | 0.1615 | 0.0000 | 0.1615 | 0.0086 | 0.1701 | 0.0895 | 1704.34 | 810.78 | 3427.88 |
PERIMETER_TOP_ZN_4 | 0.1053 | 0.0000 | 0.1053 | 0.0058 | 0.1111 | 0.0567 | 1679.88 | 961.52 | 3301.59 |
PERIMETER_BOT_ZN_3 | 0.0996 | 0.0000 | 0.0996 | 0.0046 | 0.1042 | 0.0895 | 2903.35 | 448.17 | 2591.48 |
PERIMETER_BOT_ZN_2 | 0.0927 | 0.0000 | 0.0927 | 0.0031 | 0.0957 | 0.0567 | 2485.97 | 470.87 | 2986.16 |
PERIMETER_BOT_ZN_1 | 0.1375 | 0.0000 | 0.1375 | 0.1335 | 0.2710 | 0.0895 | 2098.15 | 405.45 | 3439.39 |
PERIMETER_BOT_ZN_4 | 0.0884 | 0.0000 | 0.0884 | 0.0031 | 0.0915 | 0.0567 | 2495.26 | 429.98 | 3017.76 |
PERIMETER_MID_ZN_3 | 0.1164 | 0.0000 | 0.1164 | 0.0072 | 0.1236 | 0.0895 | 1872.33 | 988.54 | 3082.13 |
PERIMETER_MID_ZN_2 | 0.0990 | 0.0000 | 0.0990 | 0.0051 | 0.1041 | 0.0567 | 1619.04 | 756.64 | 2658.32 |
PERIMETER_MID_ZN_1 | 0.1596 | 0.0000 | 0.1596 | 0.0072 | 0.1667 | 0.0895 | 1685.45 | 769.53 | 3488.02 |
PERIMETER_MID_ZN_4 | 0.1011 | 0.0000 | 0.1011 | 0.0048 | 0.1059 | 0.0567 | 1843.30 | 1119.16 | 2980.54 |
Total Facility | 2.9890 | 0.0000 | 2.9890 | 0.1972 | 3.1862 | 2.1513 | 3863.52 | 1725.90 | 4578.62 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 30470845.45 | 0.00 | 30470845.45 | 22614548.33 | 4115.94 | 3.86 | 4640.20 | 234.08 |
PACU_VAV_MID | 27390579.67 | 0.00 | 27390579.67 | 22429071.92 | 4082.29 | 4.47 | 4673.23 | 282.53 |
PACU_VAV_TOP | 27647134.41 | 0.00 | 27647134.41 | 22614548.33 | 4070.57 | 1.00 | 4688.44 | 102.86 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4071 | 0.0000 | 1.4071 | 0.7171 | 1351.39 | 3.86 | 4587.75 |
PACU_VAV_MID | 1.2621 | 0.0000 | 1.2621 | 0.7084 | 1323.63 | 4.47 | 4614.90 |
PACU_VAV_TOP | 1.2741 | 0.0000 | 1.2741 | 0.7171 | 1322.37 | 1.00 | 4619.63 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 534.76 | 2401.54 | 0.00 | 0.00 | 0.00 | 2098.38 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 155.78 | 2460.68 | 0.00 | 0.00 | 0.00 | 2514.73 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 155.88 | 2235.17 | 0.00 | 0.00 | 0.00 | 2514.56 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2518 | 2.5400 | 0.0000 | 0.0000 | 0.0000 | 1.0432 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2236 | 2.2100 | 0.0000 | 0.0000 | 0.0000 | 0.9931 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2064 | 2.2743 | 0.0000 | 0.0000 | 0.0000 | 1.0089 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1005 |
Defaulted Fields | 578 |
Fields with Defaults | 2423 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
Electricity:Building | 952.31 | 13383.13 | 09-APR-17:20 | 66674.30 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 952.31 | 13383.13 | 09-APR-17:20 | 66674.30 | 02-JAN-16:40 |
InteriorLights:Electricity | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.62 | 905.38 | 09-APR-17:20 | 25003.79 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.11 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.67 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.09 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.66 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.11 | 413.68 | 26-MAR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.77 | 27.57 | 01-JAN-10:00 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.67 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-09:40 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.00 | 413.67 | 26-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 17.46 | 01-JAN-09:50 | 658.71 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 261.50 | 368.53 | 18-JUN-18:00 | 107331.88 | 04-AUG-07:20 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 03-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 03-JAN-12:20 |
ElectricityPurchased:Facility | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
ElectricityPurchased:Plant | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
Cogeneration:ElectricityPurchased | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
General:Cogeneration:ElectricityPurchased | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
ElectricityNet:Plant | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
Cogeneration:ElectricityNet | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
General:Cogeneration:ElectricityNet | 1329.38 | 13751.66 | 04-JUL-18:40 | 172252.15 | 04-AUG-07:20 |
Fans:Electricity | 94.85 | 0.00 | 01-JAN-00:40 | 32937.52 | 04-AUG-07:20 |
General:Fans:Electricity | 94.85 | 0.00 | 01-JAN-00:40 | 32937.52 | 04-AUG-07:20 |
ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.26 | 0.00 | 01-JAN-08:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 139.77 | 0.00 | 01-JAN-00:10 | 75245.03 | 04-AUG-15:30 |
General:Cooling:Electricity | 139.77 | 0.00 | 01-JAN-00:10 | 75245.03 | 04-AUG-15:30 |
Electricity:Plant | 64.31 | 0.00 | 01-JAN-00:40 | 8404.16 | 03-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 59.81 | 0.00 | 01-JAN-00:10 | 7590.58 | 01-MAR-12:50 |
Water Heater:WaterSystems:Electricity | 59.81 | 0.00 | 01-JAN-00:10 | 7590.58 | 01-MAR-12:50 |
Pumps:Electricity | 4.50 | 0.00 | 01-JAN-00:40 | 1072.99 | 30-JAN-07:40 |
General:Pumps:Electricity | 4.50 | 0.00 | 01-JAN-00:40 | 1072.99 | 30-JAN-07:40 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:50 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 879.98 | 0.00 | 01-JAN-00:40 | 338062.50 | 02-FEB-08:00 |
NaturalGas:Plant | 879.98 | 0.00 | 01-JAN-00:40 | 338062.50 | 02-FEB-08:00 |
Heating:NaturalGas | 879.98 | 0.00 | 01-JAN-00:40 | 338062.50 | 02-FEB-08:00 |
Boiler:Heating:NaturalGas | 879.98 | 0.00 | 01-JAN-00:40 | 338062.50 | 02-FEB-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3071.15 | 0.00 | 01-JAN-00:40 | 661169.21 | 30-JAN-07:10 |
EnergyTransfer:Building | 1110.57 | 0.00 | 01-JAN-00:40 | 166031.35 | 26-JUN-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 197.56 | 0.00 | 01-JAN-00:40 | 25419.84 | 04-AUG-08:00 |
Heating:EnergyTransfer | 289.25 | 0.00 | 01-JAN-00:40 | 158069.98 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.30 | 0.00 | 01-JAN-00:10 | 8816.63 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 289.25 | 0.00 | 01-JAN-00:40 | 158069.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.30 | 0.00 | 01-JAN-00:10 | 8816.63 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 821.32 | 0.00 | 01-JAN-00:40 | 166031.35 | 26-JUN-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 197.26 | 0.00 | 01-JAN-00:40 | 25419.84 | 04-AUG-08:00 |
General:Cooling:EnergyTransfer | 821.32 | 0.00 | 01-JAN-00:40 | 166031.35 | 26-JUN-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 197.26 | 0.00 | 01-JAN-00:40 | 25419.84 | 04-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.81 | 0.00 | 01-JAN-00:40 | 17249.65 | 02-FEB-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.99 | 0.00 | 01-JAN-00:40 | 17249.65 | 02-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 35.99 | 0.00 | 01-JAN-00:40 | 17249.65 | 02-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.82 | 0.00 | 01-JAN-00:10 | 10854.93 | 26-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.82 | 0.00 | 01-JAN-00:10 | 10854.93 | 26-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.86 | 0.00 | 01-JAN-00:40 | 9426.61 | 02-JAN-08:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.61 | 0.00 | 01-JAN-00:40 | 9426.61 | 02-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.61 | 0.00 | 01-JAN-00:40 | 9426.61 | 02-JAN-08:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.25 | 0.00 | 01-JAN-00:10 | 5373.92 | 26-JUN-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.25 | 0.00 | 01-JAN-00:10 | 5373.92 | 26-JUN-07:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.79 | 0.00 | 01-JAN-00:40 | 8015.16 | 02-JAN-08:50 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.44 | 0.00 | 01-JAN-00:40 | 8015.16 | 02-JAN-08:50 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 10.44 | 0.00 | 01-JAN-00:40 | 8015.16 | 02-JAN-08:50 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:10 | 5574.55 | 26-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.34 | 0.00 | 01-JAN-00:10 | 5574.55 | 26-JUN-14:50 |
EnergyTransfer:Zone:CORE_MID | 130.49 | 0.00 | 01-JAN-00:40 | 19959.72 | 26-JUN-08:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 4.45 | 0.00 | 01-JAN-00:20 | 15791.69 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 4.45 | 0.00 | 01-JAN-00:20 | 15791.69 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 126.04 | 0.00 | 01-JAN-00:40 | 19959.72 | 26-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 126.04 | 0.00 | 01-JAN-00:40 | 19959.72 | 26-JUN-08:10 |
EnergyTransfer:Zone:CORE_TOP | 130.62 | 0.00 | 01-JAN-00:40 | 23816.57 | 11-DEC-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 18.80 | 0.00 | 01-JAN-00:40 | 23816.57 | 11-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 18.80 | 0.00 | 01-JAN-00:40 | 23816.57 | 11-DEC-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 111.82 | 0.00 | 01-JAN-00:10 | 20553.61 | 26-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 111.82 | 0.00 | 01-JAN-00:10 | 20553.61 | 26-JUN-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.05 | 0.00 | 01-JAN-00:40 | 9608.85 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.40 | 0.00 | 01-JAN-00:40 | 9608.85 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.40 | 0.00 | 01-JAN-00:40 | 9608.85 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.64 | 0.00 | 01-JAN-00:10 | 7362.05 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 24.64 | 0.00 | 01-JAN-00:10 | 7362.05 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.07 | 0.00 | 01-JAN-00:40 | 9358.77 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.13 | 0.00 | 01-JAN-00:40 | 8262.05 | 02-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.13 | 0.00 | 01-JAN-00:40 | 8262.05 | 02-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.94 | 0.00 | 01-JAN-00:20 | 9358.77 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 24.94 | 0.00 | 01-JAN-00:20 | 9358.77 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.64 | 0.00 | 01-JAN-00:40 | 13682.64 | 07-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 20.49 | 0.00 | 01-JAN-00:40 | 11368.00 | 02-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 20.49 | 0.00 | 01-JAN-00:40 | 11368.00 | 02-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.15 | 0.00 | 01-JAN-00:20 | 13682.64 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.15 | 0.00 | 01-JAN-00:20 | 13682.64 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.14 | 0.00 | 01-JAN-00:40 | 9728.17 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.86 | 0.00 | 01-JAN-00:40 | 8465.54 | 02-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.86 | 0.00 | 01-JAN-00:40 | 8465.54 | 02-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.28 | 0.00 | 01-JAN-00:20 | 9728.17 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.28 | 0.00 | 01-JAN-00:20 | 9728.17 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 39.68 | 0.00 | 01-JAN-00:40 | 7185.15 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.81 | 0.00 | 01-JAN-00:40 | 7185.15 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.81 | 0.00 | 01-JAN-00:40 | 7185.15 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.87 | 0.00 | 01-JAN-00:10 | 5568.25 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.87 | 0.00 | 01-JAN-00:10 | 5568.25 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 32.83 | 0.00 | 01-JAN-00:40 | 7772.70 | 26-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.44 | 0.00 | 01-JAN-00:40 | 6113.06 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 10.44 | 0.00 | 01-JAN-00:40 | 6113.06 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.39 | 0.00 | 01-JAN-00:20 | 7772.70 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.39 | 0.00 | 01-JAN-00:20 | 7772.70 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 61.09 | 0.00 | 01-JAN-00:40 | 12805.64 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.04 | 0.00 | 01-JAN-00:40 | 12805.64 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 31.04 | 0.00 | 01-JAN-00:40 | 12805.64 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 30.05 | 0.00 | 01-JAN-00:20 | 12015.71 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 30.05 | 0.00 | 01-JAN-00:20 | 12015.71 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.84 | 0.00 | 01-JAN-00:40 | 7657.79 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.74 | 0.00 | 01-JAN-00:40 | 6296.77 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 10.74 | 0.00 | 01-JAN-00:40 | 6296.77 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.10 | 0.00 | 01-JAN-00:20 | 7657.79 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.10 | 0.00 | 01-JAN-00:20 | 7657.79 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 43.18 | 0.00 | 01-JAN-00:40 | 7822.41 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 17.15 | 0.00 | 01-JAN-00:40 | 7822.41 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 17.15 | 0.00 | 01-JAN-00:40 | 7822.41 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.03 | 0.00 | 01-JAN-00:20 | 6803.33 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 26.03 | 0.00 | 01-JAN-00:20 | 6803.33 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.45 | 0.00 | 01-JAN-00:40 | 9534.30 | 26-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.75 | 0.00 | 01-JAN-00:40 | 7036.31 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 9.75 | 0.00 | 01-JAN-00:40 | 7036.31 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.70 | 0.00 | 01-JAN-00:20 | 9534.30 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.70 | 0.00 | 01-JAN-00:20 | 9534.30 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.17 | 0.00 | 01-JAN-00:40 | 12670.55 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.68 | 0.00 | 01-JAN-00:40 | 9482.09 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 10.68 | 0.00 | 01-JAN-00:40 | 9482.09 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.48 | 0.00 | 01-JAN-00:20 | 12670.55 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.48 | 0.00 | 01-JAN-00:20 | 12670.55 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.32 | 0.00 | 01-JAN-00:40 | 9279.41 | 05-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.19 | 0.00 | 01-JAN-00:40 | 7086.53 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.19 | 0.00 | 01-JAN-00:40 | 7086.53 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.13 | 0.00 | 01-JAN-00:20 | 9279.41 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.13 | 0.00 | 01-JAN-00:20 | 9279.41 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 701.79 | 0.00 | 01-JAN-00:40 | 271562.56 | 02-FEB-08:00 |
PlantLoopHeatingDemand:Plant | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
EnergyTransfer:HVAC | 1263.52 | 0.00 | 01-JAN-00:40 | 353741.11 | 04-AUG-07:10 |
HeatingCoils:EnergyTransfer | 644.82 | 0.00 | 01-JAN-00:40 | 269151.72 | 02-FEB-08:00 |
PlantLoopHeatingDemand:HVAC | 644.82 | 0.00 | 01-JAN-00:40 | 269151.72 | 02-FEB-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 644.82 | 0.00 | 01-JAN-00:40 | 269151.72 | 02-FEB-08:00 |
CoolingCoils:EnergyTransfer | 618.70 | 0.00 | 01-JAN-00:10 | 353741.11 | 04-AUG-07:10 |
EnergyTransfer:Plant | 697.06 | 0.00 | 01-JAN-00:40 | 270271.97 | 02-FEB-08:00 |
WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 56.97 | 0.00 | 01-JAN-00:10 | 7270.37 | 21-FEB-12:10 |
Boilers:EnergyTransfer | 640.09 | 0.00 | 01-JAN-00:40 | 267861.13 | 02-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.297 | -197.264 | 0.000 | 0.000 | 33.524 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -142.579 |
CORE_MID | 0.000 | 0.000 | 4.446 | -126.042 | 0.000 | 0.000 | 34.761 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -84.189 |
CORE_TOP | 0.000 | 0.000 | 18.797 | -111.820 | 0.000 | 0.000 | 35.409 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -113.410 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 29.404 | -24.643 | 0.000 | 0.000 | 7.635 | 6.774 | 24.333 | 17.194 | 0.000 | 0.047 | 0.001 | 0.000 | -40.952 | 0.000 | -6.985 | -12.806 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 17.125 | -24.943 | 0.000 | 0.000 | 4.757 | 4.263 | 15.404 | 32.503 | 0.000 | 0.029 | 0.000 | 0.000 | -25.519 | 0.000 | -4.725 | -18.893 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 20.493 | -41.149 | 0.000 | 0.000 | 7.426 | 6.671 | 24.332 | 67.095 | 0.000 | 0.044 | 0.001 | 0.000 | -37.308 | 0.000 | -7.227 | -40.378 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 17.856 | -25.281 | 0.000 | 0.000 | 4.792 | 4.246 | 15.403 | 33.930 | 0.000 | 0.029 | 0.000 | 0.000 | -26.409 | 0.000 | -4.743 | -19.823 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 18.809 | -20.869 | 0.000 | 0.000 | 7.621 | 6.757 | 24.333 | 17.568 | 0.000 | 0.031 | 0.000 | 0.000 | -41.704 | 0.000 | -3.826 | -8.718 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 10.435 | -22.394 | 0.000 | 0.000 | 4.735 | 4.256 | 15.404 | 32.715 | 0.000 | 0.017 | 0.000 | 0.000 | -26.324 | 0.000 | -2.614 | -16.230 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 31.039 | -30.048 | 0.000 | 0.000 | 7.720 | 6.663 | 24.332 | 68.104 | 0.000 | 1.070 | 0.001 | 0.000 | -38.140 | 0.000 | -48.069 | -22.670 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 10.741 | -22.101 | 0.000 | 0.000 | 4.760 | 4.239 | 15.403 | 34.213 | 0.000 | 0.016 | 0.001 | 0.000 | -27.276 | 0.000 | -2.626 | -17.370 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 17.155 | -26.025 | 0.000 | 0.000 | 7.549 | 6.774 | 24.333 | 16.973 | 0.000 | 0.041 | 1.905 | 0.000 | -42.660 | 0.000 | -6.043 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 9.747 | -24.703 | 0.000 | 0.000 | 3.480 | 4.263 | 15.404 | 32.253 | 0.000 | 0.025 | 0.000 | 0.000 | -26.550 | 0.000 | -4.086 | -9.831 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 10.682 | -43.484 | 0.000 | 0.000 | 7.333 | 6.671 | 24.332 | 66.795 | 0.000 | 0.037 | 0.000 | 0.000 | -38.940 | 0.000 | -6.261 | -27.167 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.192 | -26.131 | 0.000 | 0.000 | 4.737 | 4.246 | 15.403 | 33.791 | 0.000 | 0.024 | 0.000 | 0.000 | -27.514 | 0.000 | -4.100 | -10.650 |
TOPFLOOR_PLENUM | 35.985 | -23.823 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.037 | 0.000 | 0.000 | 0.000 | 0.000 | -10.550 | -1.649 |
MIDFLOOR_PLENUM | 15.605 | -13.254 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.058 | 7.887 | 0.000 | 0.000 | 0.000 | -10.296 | -0.000 |
FIRSTFLOOR_PLENUM | 10.445 | -17.344 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.045 | 15.151 | 0.000 | 0.000 | 0.000 | -8.297 | -0.000 |
Total Facility | 62.035 | -54.421 | 227.218 | -766.894 | 0.000 | 0.000 | 176.239 | 232.618 | 719.689 | 453.133 | 0.000 | 1.550 | 24.948 | 0.000 | -399.296 | 0.000 | -130.449 | -546.367 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-JUL-05:12 | 0.00 | 0.00 | 0.00 | -39410.92 | 0.00 | 0.00 | 313.17 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 31138.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-JUN-05:14 | 0.00 | 0.00 | 0.00 | -33399.01 | 0.00 | 0.00 | 318.80 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 29505.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-SEP-05:12 | 0.00 | 0.00 | 0.00 | -31906.57 | 0.00 | 0.00 | 328.95 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 28003.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-18:32 | 0.00 | 0.00 | 0.00 | -11149.86 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 3843.08 | 0.00 | 99.41 | 6793.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:22 | 0.00 | 0.00 | 0.00 | -14528.98 | 0.00 | 0.00 | 12.82 | 17.46 | 302.86 | 9895.18 | 0.00 | 0.00 | 4320.89 | 0.00 | -0.00 | 0.00 | -20.22 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:31 | 0.00 | 0.00 | 0.00 | -18832.34 | 0.00 | 0.00 | 21.70 | 27.57 | 478.41 | 13943.32 | 0.00 | 0.00 | 4456.23 | 0.00 | -0.00 | 0.00 | -94.89 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-16:21 | 0.00 | 0.00 | 0.00 | -16901.18 | 0.00 | 0.00 | 13.14 | 17.46 | 302.86 | 12444.81 | 0.00 | 0.00 | 4165.26 | 0.00 | -0.00 | 0.00 | -42.34 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7074.47 | 0.00 | 0.00 | 144.48 | 165.45 | 637.89 | 2877.64 | 0.00 | 0.00 | 3257.92 | 0.00 | -0.00 | 0.00 | -8.90 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -12329.97 | 0.00 | 0.00 | 15.16 | 17.46 | 302.86 | 10357.36 | 0.00 | 0.00 | 1654.75 | 0.00 | -0.00 | 0.00 | -17.62 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:31 | 0.00 | 0.00 | 0.00 | -14561.33 | 0.00 | 0.00 | 23.89 | 27.57 | 478.41 | 14053.24 | 0.00 | 0.00 | 25.27 | 0.00 | -0.00 | 0.00 | -47.05 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 | -12946.03 | 0.00 | 0.00 | 14.57 | 17.46 | 302.86 | 10333.09 | 0.00 | 0.00 | 2295.83 | 0.00 | -0.00 | 0.00 | -17.77 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:21 | 0.00 | 0.00 | 0.00 | -9682.65 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4042.37 | 0.00 | 78.41 | 5148.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:11 | 0.00 | 0.00 | 0.00 | -15717.75 | 0.00 | 0.00 | 12.97 | 17.46 | 302.86 | 10259.20 | 0.00 | 0.00 | 5163.59 | 0.00 | -0.00 | 0.00 | -38.32 | 0.00 |
PERIMETER_MID_ZN_1 | 16-APR-13:52 | 0.00 | 0.00 | 0.00 | -16288.35 | 0.00 | 0.00 | 23.45 | 27.57 | 478.41 | 11861.20 | 0.00 | 0.00 | 3912.48 | 0.00 | -0.00 | 0.00 | -14.76 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -15909.84 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 10365.14 | 0.00 | 33.42 | 5249.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:30 | 0.00 | -10854.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 | 10811.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -6289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6316.83 | 0.00 | -0.00 | 0.00 | -27.43 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -6334.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6355.48 | 0.00 | -0.00 | 0.00 | -21.04 | 0.00 |
Total Facility | 03-JUL-05:12 | 0.00 | 456.47 | 0.00 | -181842.60 | 0.00 | 0.00 | 1633.17 | 2221.99 | 19712.35 | 10135.81 | 0.00 | 0.00 | 150260.21 | 0.00 | -1412.82 | 0.00 | -1164.57 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 10615.97 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16469.76 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 18424.45 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21078.24 |
CORE_TOP | 11-DEC-00:02 | 0.00 | 0.00 | 25839.90 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28493.69 |
PERIMETER_TOP_ZN_3 | 11-DEC-01:22 | 0.00 | 0.00 | 10436.88 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3944.49 | 0.00 | -889.68 | -6162.16 |
PERIMETER_TOP_ZN_2 | 11-DEC-01:22 | 0.00 | 0.00 | 9740.97 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2556.72 | 0.00 | -599.00 | -6939.40 |
PERIMETER_TOP_ZN_1 | 11-DEC-01:22 | 0.00 | 0.00 | 12955.03 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3868.93 | 0.00 | -901.76 | -8743.78 |
PERIMETER_TOP_ZN_4 | 11-DEC-01:22 | 0.00 | 0.00 | 10231.10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2631.24 | 0.00 | -599.26 | -7354.76 |
PERIMETER_BOT_ZN_3 | 02-FEB-04:42 | 0.00 | 0.00 | 7675.53 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5563.84 | 0.00 | -583.69 | -2087.44 |
PERIMETER_BOT_ZN_2 | 11-DEC-01:22 | 0.00 | 0.00 | 7133.09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2659.68 | 0.00 | -330.61 | -4496.95 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:06 | 0.00 | 0.00 | 13937.59 | 0.00 | 0.00 | 0.00 | 225.76 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 30230.04 | 0.00 | -5560.52 | 0.00 | -39817.60 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-DEC-01:22 | 0.00 | 0.00 | 7418.56 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2722.36 | 0.00 | -330.17 | -4720.18 |
PERIMETER_MID_ZN_3 | 02-FEB-05:11 | 0.00 | 0.00 | 8358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5646.90 | 0.00 | -791.92 | -2478.95 |
PERIMETER_MID_ZN_2 | 02-FEB-05:11 | 0.00 | 0.00 | 8253.92 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3663.09 | 0.00 | -530.32 | -4414.67 |
PERIMETER_MID_ZN_1 | 02-FEB-05:11 | 0.00 | 0.00 | 10545.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5534.02 | 0.00 | -797.86 | -4772.84 |
PERIMETER_MID_ZN_4 | 02-FEB-05:11 | 0.00 | 0.00 | 8425.50 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3766.32 | 0.00 | -530.08 | -4483.24 |
TOPFLOOR_PLENUM | 04-FEB-06:10 | 18094.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -180.16 | -17914.46 |
MIDFLOOR_PLENUM | 11-DEC-08:19 | 9981.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -268.92 | -9712.81 |
FIRSTFLOOR_PLENUM | 02-JAN-08:45 | 8065.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -218.58 | -7846.57 |
Total Facility | 02-JAN-05:01 | 14608.74 | 0.00 | 154844.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21497.44 | 0.00 | -6159.48 | -158438.95 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4266 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7306 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3616 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4317 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7198 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1142 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7133 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0763 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6808 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8599 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0768 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6641 | 2.6641 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1454 | 2.1454 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2356 | 2.2356 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6948 | 0.6948 | 0.1355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8469 | 0.8469 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0202 | 1.0202 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9224 | 0.9224 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5359 | 0.5359 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6868 | 0.6868 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8106 | 0.8106 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7292 | 0.7292 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5987 | 0.5987 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8331 | 0.8331 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9293 | 0.9293 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8550 | 0.8550 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4266 | 4.7306 | 5.4266 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3616 | 4.4317 | 5.3616 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7198 | 5.1142 | 5.7198 | 1.0768 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3320 | 1.3320 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0727 | 1.0727 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1178 | 1.1178 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3474 | 0.3474 | 0.1355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4234 | 0.4234 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5101 | 0.5101 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4612 | 0.4612 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2680 | 0.2680 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3434 | 0.3434 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4053 | 0.4053 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3646 | 0.3646 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2994 | 0.2994 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4166 | 0.4166 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4647 | 0.4647 | 0.1348 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4275 | 0.4275 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7133 | 1.0763 | 1.0763 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6808 | 1.0757 | 1.0757 | 1.0757 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8599 | 1.0768 | 1.0768 | 1.0768 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 700.83 |
Number of hours cooling loads not met | 117.33 |
Number of hours not met | 818.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 879.98 | 338062.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 139.77 | 75245.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.62 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.26 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 94.85 | 32937.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 4.50 | 1072.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.81 | 7590.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1329.38 |
Natural Gas | 0.00 | 879.98 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2209.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.69 |
Space Heating | 0.00 |
Space Cooling | 28.05 |
Fans (All) | 19.04 |
Service Water Heating | 12.00 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 266.83 |
Subtotal | 266.83 |
Natural Gas [MJ/m2] | |
Space Heating | 176.63 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 176.63 |
Subtotal | 176.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.53 |
Space Heating | 39.83 |
Space Cooling | 6.33 |
Fans (All) | 4.29 |
Service Water Heating | 2.71 |
Receptacle Equipment | 32.57 |
Miscellaneous | 3.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 807. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8549.67 | 210.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.17 | 3.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8642.17 | 117.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8677.67 | 82.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8625.67 | 134.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8692.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8670.50 | 89.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8648.67 | 111.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8634.50 | 125.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8605.00 | 155.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8549.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 210.33 | 0.00 | 0.00 | 0.00 |
Average | 8689.98 | 70.02 | 0.00 | 0.00 | 0.00 |
Sum | 156419.67 | 1260.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128243.00 | 61.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 61.00 | 0.00 | 0.00 | 0.00 |
Average | 34139.94 | 3.39 | 0.00 | 0.00 | 0.00 |
Sum | 614519.00 | 61.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8125.83 | 634.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8382.00 | 378.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8463.33 | 296.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8336.00 | 424.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8248.83 | 511.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8281.33 | 478.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8220.17 | 539.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8484.33 | 275.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8299.33 | 460.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8286.50 | 473.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8233.50 | 526.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8298.00 | 462.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8195.50 | 564.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8241.33 | 518.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8150.50 | 609.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7946.50 | 813.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8323.00 | 437.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8342.17 | 417.83 | 0.00 | 0.00 | 0.00 |
Min | 7946.50 | 275.67 | 0.00 | 0.00 | 0.00 |
Max | 8484.33 | 813.50 | 0.00 | 0.00 | 0.00 |
Average | 8269.90 | 490.10 | 0.00 | 0.00 | 0.00 |
Sum | 148858.17 | 8821.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127890.00 | 414.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128119.83 | 184.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128158.67 | 145.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24876.50 | 32.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14001.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24877.83 | 31.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14002.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24884.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14004.83 | 11.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24421.17 | 487.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14008.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24885.17 | 23.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10127.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24883.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14010.00 | 6.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128158.67 | 487.83 | 0.00 | 0.00 | 0.00 |
Average | 34063.95 | 79.38 | 0.00 | 0.00 | 0.00 |
Sum | 613151.17 | 1428.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819883E+10 | 9343.94 | 19-JAN-11:50 | -25.1 | -25.3 | 0.163697E+10 | 2606.57 | 13-JAN-14:20 | -25.1 | -25.3 |
February | 0.774616E+10 | 10537.27 | 24-FEB-17:00 | 7.20 | 5.13 | 0.162113E+10 | 2606.64 | 24-FEB-14:20 | 7.20 | 5.13 |
March | 0.112483E+11 | 15627.72 | 24-MAR-16:00 | 10.60 | 5.50 | 0.210108E+10 | 2606.65 | 17-MAR-09:09 | 10.60 | 5.50 |
April | 0.140211E+11 | 37800.83 | 17-APR-05:12 | 11.13 | 9.50 | 0.190497E+10 | 2606.67 | 11-APR-13:09 | 11.13 | 9.50 |
May | 0.208567E+11 | 39405.27 | 30-MAY-05:12 | 14.60 | 14.60 | 0.207804E+10 | 2606.71 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.244396E+11 | 39282.62 | 19-JUN-05:12 | 11.87 | 10.77 | 0.207284E+10 | 2638.05 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.254081E+11 | 39417.00 | 10-JUL-05:12 | 17.20 | 16.74 | 0.192805E+10 | 2607.92 | 03-JUL-09:09 | 17.20 | 16.74 |
August | 0.266114E+11 | 39230.08 | 21-AUG-05:12 | 15.93 | 15.21 | 0.216385E+10 | 2854.07 | 04-AUG-07:49 | 15.93 | 15.21 |
September | 0.224657E+11 | 39342.58 | 12-SEP-05:12 | 15.93 | 15.59 | 0.191992E+10 | 2606.65 | 21-SEP-13:09 | 12.80 | 11.83 |
October | 0.163664E+11 | 37057.84 | 23-OCT-05:01 | -2.7 | -3.7 | 0.199159E+10 | 2606.66 | 20-OCT-09:20 | -2.7 | -3.7 |
November | 0.116157E+11 | 30178.00 | 06-NOV-07:02 | 10.60 | 9.72 | 0.190720E+10 | 2606.66 | 01-NOV-09:20 | 10.60 | 9.72 |
December | 0.828584E+10 | 10445.92 | 07-DEC-16:10 | -5.4 | -8.6 | 0.174422E+10 | 2606.64 | 08-DEC-10:20 | -5.0 | -5.5 |
Annual Sum or Average | 0.197264E+12 | 0.230699E+11 | ||||||||
Minimum of Months | 0.774616E+10 | 9343.94 | -25.1 | -25.3 | 0.162113E+10 | 2606.57 | -25.1 | -25.3 | ||
Maximum of Months | 0.266114E+11 | 39417.00 | 17.20 | 16.74 | 0.216385E+10 | 2854.07 | 25.37 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 6466090.14 | 421.30 | 24-FEB-15:10 | 8.30 | 5.66 | 0.00 | 0.00 | 01-FEB-00:10 | 8.30 | 5.66 |
March | 0.158107E+09 | 2364.50 | 24-MAR-14:30 | 13.05 | 6.50 | 0.00 | 0.00 | 01-MAR-00:10 | 13.05 | 6.50 |
April | 0.123111E+10 | 8487.62 | 18-APR-14:40 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.284987E+10 | 9526.15 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.523841E+10 | 10854.93 | 26-JUN-13:30 | 31.40 | 21.76 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 21.76 |
July | 0.576510E+10 | 10438.78 | 05-JUL-13:50 | 27.12 | 19.90 | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 19.90 |
August | 0.533037E+10 | 10721.94 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.282122E+10 | 9633.87 | 07-SEP-15:10 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.371182E+09 | 4179.78 | 20-OCT-15:00 | 23.30 | 13.36 | 0.00 | 0.00 | 01-OCT-00:10 | 23.30 | 13.36 |
November | 51857586.17 | 2127.28 | 03-NOV-14:30 | 16.10 | 10.04 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 10.04 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.238237E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.576510E+10 | 10854.93 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12447209.71 | 3362.26 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 13115307.62 | 2884.77 | 01-FEB-05:01 | -30.2 | -30.4 | 0.00 | 0.00 | 01-FEB-00:10 | -30.2 | -30.4 |
March | 48464782.35 | 2342.37 | 21-MAR-05:01 | -7.2 | -8.2 | 0.00 | 0.00 | 01-MAR-00:10 | -7.2 | -8.2 |
April | 0.498989E+09 | 3888.54 | 17-APR-15:20 | 19.40 | 11.61 | 0.00 | 0.00 | 01-APR-00:10 | 19.40 | 11.61 |
May | 0.128079E+10 | 4284.80 | 30-MAY-15:40 | 27.80 | 19.59 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.59 |
June | 0.295880E+10 | 6012.47 | 26-JUN-08:10 | 25.37 | 22.03 | 0.00 | 0.00 | 01-JUN-00:10 | 25.37 | 22.03 |
July | 0.341022E+10 | 6290.05 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.317535E+10 | 4657.14 | 04-AUG-15:30 | 33.90 | 25.83 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.83 |
September | 0.168776E+10 | 4498.86 | 11-SEP-14:20 | 28.70 | 20.20 | 0.00 | 0.00 | 01-SEP-00:10 | 28.70 | 20.20 |
October | 0.118807E+09 | 2343.65 | 26-OCT-06:02 | -0.9 | -2.2 | 0.00 | 0.00 | 01-OCT-00:10 | -0.9 | -2.2 |
November | 42679103.87 | 2417.02 | 25-NOV-05:01 | -15.3 | -15.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.3 | -15.7 |
December | 6857513.26 | 2838.22 | 09-DEC-05:01 | -22.8 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.132543E+11 | 0.00 | ||||||||
Minimum of Months | 6857513.26 | 2342.37 | -30.2 | -30.4 | 0.00 | 0.00 | -30.2 | -30.4 | ||
Maximum of Months | 0.341022E+10 | 6290.05 | 33.90 | 25.83 | 0.00 | 0.00 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110991E+09 | 3088.80 | 07-JAN-05:01 | -25.7 | -26.0 | 0.00 | 0.00 | 01-JAN-00:10 | -25.7 | -26.0 |
February | 0.115161E+09 | 4290.83 | 02-FEB-17:10 | -29.6 | -29.9 | 0.00 | 0.00 | 01-FEB-00:10 | -29.6 | -29.9 |
March | 0.189102E+09 | 3141.68 | 30-MAR-06:02 | 1.10 | 0.61 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | 0.61 |
April | 0.701492E+09 | 3735.49 | 18-APR-15:20 | 27.20 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 20.26 |
May | 0.175236E+10 | 4359.46 | 30-MAY-16:00 | 27.80 | 19.90 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 19.90 |
June | 0.340239E+10 | 6076.47 | 26-JUN-12:10 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.396237E+10 | 6335.12 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.401137E+10 | 4884.19 | 04-AUG-16:00 | 33.90 | 26.33 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.33 |
September | 0.246840E+10 | 5491.33 | 05-SEP-06:06 | 7.35 | 6.75 | 0.00 | 0.00 | 01-SEP-00:10 | 7.35 | 6.75 |
October | 0.395144E+09 | 2369.56 | 27-OCT-06:02 | 0.25 | -1.1 | 0.00 | 0.00 | 01-OCT-00:10 | 0.25 | -1.1 |
November | 0.157052E+09 | 2142.30 | 28-NOV-05:01 | -21.1 | -21.4 | 0.00 | 0.00 | 01-NOV-00:10 | -21.1 | -21.4 |
December | 77792026.03 | 2817.83 | 08-DEC-17:10 | -19.2 | -19.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.2 | -19.4 |
Annual Sum or Average | 0.173436E+11 | 0.00 | ||||||||
Minimum of Months | 77792026.03 | 2142.30 | -29.6 | -29.9 | 0.00 | 0.00 | -29.6 | -29.9 | ||
Maximum of Months | 0.401137E+10 | 6335.12 | 33.90 | 26.33 | 0.00 | 0.00 | 33.90 | 26.33 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357970E+10 | 6721.44 | 05-JAN-17:01 | -20.7 | -21.2 | 0.148936E+10 | 2342.98 | 13-JAN-14:00 | 3.90 | 1.72 |
February | 0.443411E+10 | 6125.03 | 04-FEB-17:01 | -20.1 | -20.6 | 0.141831E+10 | 2381.60 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.710525E+10 | 8912.85 | 24-MAR-16:00 | 10.60 | 5.50 | 0.187690E+10 | 2606.57 | 24-MAR-13:20 | 10.60 | 5.50 |
April | 0.936783E+10 | 27603.91 | 17-APR-06:02 | 10.00 | 8.65 | 0.180149E+10 | 2606.66 | 13-APR-09:20 | 10.00 | 8.65 |
May | 0.140235E+11 | 30690.17 | 30-MAY-05:12 | 14.60 | 14.60 | 0.206334E+10 | 2606.68 | 09-MAY-13:09 | 14.60 | 14.60 |
June | 0.171415E+11 | 33403.06 | 26-JUN-05:14 | 21.47 | 20.15 | 0.206567E+10 | 2606.84 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.180651E+11 | 31221.02 | 31-JUL-05:12 | 17.07 | 15.19 | 0.192222E+10 | 2607.94 | 03-JUL-09:09 | 17.07 | 15.19 |
August | 0.182887E+11 | 30876.39 | 14-AUG-05:12 | 15.77 | 15.05 | 0.215778E+10 | 2725.68 | 04-AUG-07:30 | 15.77 | 15.05 |
September | 0.142537E+11 | 30627.43 | 18-SEP-05:12 | 17.20 | 13.61 | 0.190489E+10 | 2606.67 | 06-SEP-09:20 | 17.20 | 13.61 |
October | 0.888352E+10 | 10561.92 | 20-OCT-16:00 | 21.30 | 12.72 | 0.192542E+10 | 2606.65 | 20-OCT-09:20 | 21.30 | 12.72 |
November | 0.642419E+10 | 10242.67 | 03-NOV-16:00 | 15.00 | 9.33 | 0.171045E+10 | 2606.63 | 03-NOV-09:20 | 15.00 | 9.33 |
December | 0.447475E+10 | 6456.00 | 08-DEC-17:01 | -19.2 | -19.4 | 0.149745E+10 | 2322.56 | 07-DEC-14:00 | -19.2 | -19.4 |
Annual Sum or Average | 0.126042E+12 | 0.218333E+11 | ||||||||
Minimum of Months | 0.357970E+10 | 6125.03 | -20.7 | -21.2 | 0.141831E+10 | 2322.56 | -19.2 | -19.4 | ||
Maximum of Months | 0.182887E+11 | 33403.06 | 21.47 | 20.15 | 0.215778E+10 | 2725.68 | 25.37 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184688E+10 | 7163.29 | 07-JAN-17:03 | -20.1 | -20.6 | 0.146144E+10 | 2247.89 | 13-JAN-14:00 | 3.90 | 1.72 |
February | 0.271191E+10 | 7051.66 | 04-FEB-17:03 | -20.1 | -20.6 | 0.135974E+10 | 2352.61 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.549827E+10 | 8584.11 | 24-MAR-16:00 | 10.60 | 5.50 | 0.176694E+10 | 2606.56 | 24-MAR-13:20 | 10.60 | 5.50 |
April | 0.833512E+10 | 18077.20 | 17-APR-06:02 | 10.00 | 8.65 | 0.172594E+10 | 2606.66 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.134356E+11 | 24257.66 | 30-MAY-06:02 | 15.18 | 15.13 | 0.204412E+10 | 2606.69 | 09-MAY-13:09 | 15.18 | 15.13 |
June | 0.171282E+11 | 31614.11 | 27-JUN-05:12 | 20.57 | 19.04 | 0.205870E+10 | 2606.67 | 09-JUN-09:20 | 20.57 | 19.04 |
July | 0.180791E+11 | 31173.39 | 05-JUL-05:12 | 18.33 | 17.79 | 0.191989E+10 | 2606.66 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.178671E+11 | 31167.67 | 28-AUG-05:12 | 18.50 | 18.02 | 0.215328E+10 | 2667.62 | 04-AUG-07:30 | 18.50 | 18.02 |
September | 0.128169E+11 | 31903.81 | 11-SEP-05:12 | 19.80 | 17.33 | 0.187193E+10 | 2606.73 | 06-SEP-09:39 | 19.80 | 17.33 |
October | 0.734425E+10 | 10050.55 | 20-OCT-16:00 | 21.30 | 12.72 | 0.179677E+10 | 2606.60 | 12-OCT-13:20 | 21.30 | 12.72 |
November | 0.450828E+10 | 9156.11 | 03-NOV-16:00 | 15.00 | 9.33 | 0.160134E+10 | 2606.55 | 03-NOV-13:20 | 15.00 | 9.33 |
December | 0.224881E+10 | 6909.69 | 09-DEC-17:03 | -19.4 | -19.8 | 0.142498E+10 | 2200.04 | 01-DEC-14:00 | -19.4 | -19.8 |
Annual Sum or Average | 0.111820E+12 | 0.211851E+11 | ||||||||
Minimum of Months | 0.184688E+10 | 6909.69 | -20.1 | -20.6 | 0.135974E+10 | 2200.04 | -19.4 | -19.8 | ||
Maximum of Months | 0.180791E+11 | 31903.81 | 21.30 | 19.04 | 0.215328E+10 | 2667.62 | 23.27 | 19.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19321176.61 | 1407.48 | 07-JAN-17:03 | -20.1 | -20.6 | 0.297685E+09 | 406.85 | 02-JAN-10:39 | -20.1 | -20.6 |
February | 49848512.03 | 1411.94 | 04-FEB-17:01 | -20.1 | -20.6 | 0.271235E+09 | 435.96 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.494810E+09 | 1317.50 | 28-MAR-15:30 | 16.40 | 10.50 | 0.346493E+09 | 530.76 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.140875E+10 | 5683.24 | 18-APR-15:00 | 28.30 | 20.65 | 0.336984E+09 | 549.50 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.316875E+10 | 6128.73 | 31-MAY-14:50 | 29.90 | 19.65 | 0.422339E+09 | 549.51 | 09-MAY-09:20 | 29.90 | 19.65 |
June | 0.497465E+10 | 11150.25 | 25-JUN-18:32 | 29.97 | 21.56 | 0.431105E+09 | 549.69 | 26-JUN-13:39 | 31.50 | 21.88 |
July | 0.522680E+10 | 9624.82 | 02-JUL-16:41 | 28.98 | 21.21 | 0.404668E+09 | 549.50 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.490815E+10 | 6741.31 | 04-AUG-15:20 | 33.90 | 25.66 | 0.452042E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.288518E+10 | 6124.00 | 11-SEP-14:00 | 28.90 | 20.23 | 0.379829E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.105290E+10 | 1802.04 | 20-OCT-15:30 | 22.30 | 13.06 | 0.344337E+09 | 549.46 | 02-OCT-13:00 | 22.30 | 13.06 |
November | 0.444067E+09 | 1438.56 | 25-NOV-17:01 | -19.6 | -20.1 | 0.316622E+09 | 529.66 | 03-NOV-13:00 | -19.6 | -20.1 |
December | 9649901.48 | 1260.09 | 09-DEC-17:03 | -19.4 | -19.8 | 0.292023E+09 | 406.83 | 12-DEC-14:50 | -15.7 | -16.2 |
Annual Sum or Average | 0.246429E+11 | 0.429536E+10 | ||||||||
Minimum of Months | 9649901.48 | 1260.09 | -20.1 | -20.6 | 0.271235E+09 | 406.83 | -20.1 | -20.6 | ||
Maximum of Months | 0.522680E+10 | 11150.25 | 33.90 | 25.66 | 0.452042E+09 | 549.69 | 31.50 | 21.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36613839.92 | 885.30 | 07-JAN-17:03 | -20.1 | -20.6 | 0.192555E+09 | 277.44 | 12-JAN-10:50 | -0.5 | -1.6 |
February | 0.114384E+09 | 967.82 | 24-FEB-10:05 | 4.60 | 1.53 | 0.178233E+09 | 347.88 | 24-FEB-10:09 | 4.60 | 1.53 |
March | 0.577787E+09 | 3026.59 | 28-MAR-09:40 | 9.07 | 5.68 | 0.234772E+09 | 347.88 | 28-MAR-09:39 | 9.07 | 5.68 |
April | 0.152183E+10 | 7945.89 | 18-APR-09:30 | 24.20 | 19.59 | 0.225429E+09 | 347.88 | 13-APR-09:20 | 24.20 | 19.59 |
May | 0.331412E+10 | 10343.96 | 14-MAY-09:43 | 16.93 | 13.50 | 0.274121E+09 | 348.40 | 31-MAY-09:50 | 27.02 | 19.46 |
June | 0.495331E+10 | 14501.70 | 25-JUN-09:12 | 26.67 | 21.38 | 0.273928E+09 | 348.48 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.529389E+10 | 14533.14 | 02-JUL-09:22 | 26.15 | 21.26 | 0.256944E+09 | 348.58 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.480970E+10 | 8825.15 | 27-AUG-09:32 | 23.87 | 19.50 | 0.287419E+09 | 353.43 | 04-AUG-07:30 | 23.87 | 19.50 |
September | 0.309300E+10 | 14197.10 | 03-SEP-09:22 | 17.75 | 12.99 | 0.248057E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.882380E+09 | 3287.79 | 20-OCT-09:30 | 13.70 | 9.50 | 0.235388E+09 | 347.88 | 20-OCT-09:20 | 13.70 | 9.50 |
November | 0.320728E+09 | 1197.25 | 03-NOV-10:30 | 13.60 | 11.28 | 0.203293E+09 | 347.86 | 03-NOV-13:20 | 15.77 | 10.85 |
December | 25129743.77 | 833.84 | 09-DEC-17:03 | -19.4 | -19.8 | 0.186168E+09 | 273.85 | 05-DEC-10:09 | -19.4 | -19.8 |
Annual Sum or Average | 0.249429E+11 | 0.279631E+10 | ||||||||
Minimum of Months | 25129743.77 | 833.84 | -20.1 | -20.6 | 0.178233E+09 | 273.85 | -19.4 | -19.8 | ||
Maximum of Months | 0.529389E+10 | 14533.14 | 26.67 | 21.38 | 0.287419E+09 | 353.43 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.620307E+09 | 4948.06 | 12-JAN-12:30 | 1.95 | 0.38 | 0.325509E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.881407E+09 | 8276.89 | 24-FEB-13:45 | 7.62 | 4.99 | 0.302823E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.168064E+10 | 8967.39 | 24-MAR-13:30 | 12.75 | 6.50 | 0.381439E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.297141E+10 | 16925.15 | 16-APR-13:22 | 27.25 | 20.22 | 0.354668E+09 | 549.89 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.442772E+10 | 11901.49 | 14-MAY-15:02 | 21.70 | 15.20 | 0.425521E+09 | 550.14 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.604664E+10 | 16165.86 | 11-JUN-15:22 | 33.05 | 24.40 | 0.430859E+09 | 550.04 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.669954E+10 | 16921.79 | 30-JUL-13:12 | 26.87 | 20.18 | 0.404646E+09 | 550.07 | 05-JUL-13:00 | 26.87 | 20.18 |
August | 0.723617E+10 | 12939.74 | 27-AUG-15:32 | 27.03 | 20.38 | 0.452666E+09 | 550.25 | 21-AUG-13:50 | 27.03 | 20.38 |
September | 0.582298E+10 | 18831.58 | 04-SEP-13:31 | 21.50 | 14.11 | 0.389370E+09 | 561.27 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.300261E+10 | 16931.47 | 01-OCT-13:32 | 18.90 | 12.26 | 0.380302E+09 | 549.64 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.110554E+10 | 10674.45 | 03-NOV-13:30 | 15.85 | 10.76 | 0.338287E+09 | 549.59 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 0.654143E+09 | 6131.63 | 01-DEC-13:25 | -0.9 | -3.3 | 0.318214E+09 | 549.49 | 20-DEC-14:20 | -6.9 | -8.3 |
Annual Sum or Average | 0.411491E+11 | 0.450430E+10 | ||||||||
Minimum of Months | 0.620307E+09 | 4948.06 | -0.9 | -3.3 | 0.302823E+09 | 549.49 | -6.9 | -8.3 | ||
Maximum of Months | 0.723617E+10 | 18831.58 | 33.05 | 24.40 | 0.452666E+09 | 561.27 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57741363.29 | 986.49 | 31-JAN-16:30 | -20.3 | -20.7 | 0.192454E+09 | 327.58 | 12-JAN-16:10 | -20.3 | -20.7 |
February | 0.153127E+09 | 2946.52 | 24-FEB-16:30 | 7.75 | 5.51 | 0.177783E+09 | 347.83 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.588368E+09 | 3498.84 | 23-MAR-16:00 | 17.20 | 10.15 | 0.226679E+09 | 347.83 | 28-MAR-13:50 | 16.52 | 10.22 |
April | 0.181695E+10 | 15454.10 | 16-APR-16:42 | 28.40 | 20.34 | 0.219486E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.312759E+10 | 16903.16 | 14-MAY-16:21 | 21.70 | 15.50 | 0.268181E+09 | 347.86 | 09-MAY-09:20 | 21.70 | 15.50 |
June | 0.478806E+10 | 16198.00 | 25-JUN-17:11 | 31.50 | 21.73 | 0.272912E+09 | 347.86 | 09-JUN-09:20 | 31.50 | 21.73 |
July | 0.524291E+10 | 16132.67 | 02-JUL-16:41 | 28.98 | 21.21 | 0.256402E+09 | 347.86 | 19-JUL-09:20 | 21.47 | 17.08 |
August | 0.493817E+10 | 14726.08 | 05-AUG-17:04 | 25.32 | 17.94 | 0.286621E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.302674E+10 | 16641.97 | 04-SEP-16:51 | 22.20 | 14.41 | 0.241926E+09 | 347.86 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.109866E+10 | 5776.54 | 20-OCT-15:30 | 22.30 | 13.06 | 0.226026E+09 | 347.84 | 02-OCT-13:20 | 22.30 | 13.06 |
November | 0.369828E+09 | 3863.81 | 03-NOV-15:30 | 15.55 | 9.47 | 0.204016E+09 | 347.83 | 03-NOV-13:20 | 15.55 | 9.47 |
December | 73163827.24 | 835.70 | 09-DEC-17:03 | -19.4 | -19.8 | 0.188288E+09 | 325.45 | 01-DEC-15:00 | -19.4 | -19.8 |
Annual Sum or Average | 0.252813E+11 | 0.276077E+10 | ||||||||
Minimum of Months | 57741363.29 | 835.70 | -20.3 | -20.7 | 0.177783E+09 | 325.45 | -20.3 | -20.7 | ||
Maximum of Months | 0.524291E+10 | 16903.16 | 31.50 | 21.73 | 0.286621E+09 | 347.86 | 31.50 | 21.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14643623.09 | 1169.64 | 07-JAN-17:03 | -20.1 | -20.6 | 0.295757E+09 | 406.82 | 18-JAN-14:30 | -16.9 | -17.2 |
February | 26445164.25 | 1027.97 | 04-FEB-17:03 | -20.1 | -20.6 | 0.269032E+09 | 408.86 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.382338E+09 | 1109.20 | 28-MAR-15:30 | 16.40 | 10.50 | 0.340508E+09 | 475.46 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.939714E+09 | 3236.37 | 18-APR-15:00 | 28.30 | 20.65 | 0.323503E+09 | 549.50 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.207080E+10 | 4018.73 | 31-MAY-15:00 | 30.00 | 19.70 | 0.412660E+09 | 549.50 | 09-MAY-13:20 | 30.00 | 19.70 |
June | 0.370951E+10 | 5974.63 | 30-JUN-06:03 | 21.38 | 19.39 | 0.430837E+09 | 549.50 | 01-JUN-13:20 | 21.38 | 19.39 |
July | 0.428096E+10 | 7077.35 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404611E+09 | 549.71 | 03-JUL-13:00 | 19.60 | 18.69 |
August | 0.437274E+10 | 5568.25 | 04-AUG-15:30 | 33.90 | 25.83 | 0.453725E+09 | 573.88 | 04-AUG-07:49 | 33.90 | 25.83 |
September | 0.293411E+10 | 6054.01 | 11-SEP-06:03 | 19.50 | 17.29 | 0.391787E+09 | 549.50 | 15-SEP-09:20 | 15.73 | 12.07 |
October | 0.145192E+10 | 1613.11 | 02-OCT-15:00 | 18.30 | 14.84 | 0.367022E+09 | 549.49 | 03-OCT-13:20 | 12.97 | 9.14 |
November | 0.673516E+09 | 1277.47 | 03-NOV-15:10 | 15.92 | 9.56 | 0.327872E+09 | 532.72 | 03-NOV-13:00 | 15.92 | 9.56 |
December | 11995960.06 | 1127.08 | 09-DEC-17:03 | -19.4 | -19.8 | 0.292710E+09 | 406.79 | 26-DEC-14:09 | -3.2 | -3.9 |
Annual Sum or Average | 0.208687E+11 | 0.431002E+10 | ||||||||
Minimum of Months | 11995960.06 | 1027.97 | -20.1 | -20.6 | 0.269032E+09 | 406.79 | -16.9 | -17.2 | ||
Maximum of Months | 0.437274E+10 | 7077.35 | 33.90 | 25.83 | 0.453725E+09 | 573.88 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35855901.19 | 788.18 | 07-JAN-17:03 | -20.1 | -20.6 | 0.192499E+09 | 275.05 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 96693955.42 | 759.53 | 04-FEB-17:03 | -20.1 | -20.6 | 0.176525E+09 | 320.50 | 24-FEB-10:20 | 4.80 | 1.70 |
March | 0.479675E+09 | 1503.27 | 28-MAR-09:50 | 9.53 | 5.99 | 0.230432E+09 | 347.88 | 22-MAR-09:20 | 9.53 | 5.99 |
April | 0.105810E+10 | 5466.11 | 18-APR-09:30 | 24.20 | 19.59 | 0.221084E+09 | 347.88 | 13-APR-09:20 | 24.20 | 19.59 |
May | 0.235841E+10 | 6297.69 | 31-MAY-09:20 | 26.47 | 19.61 | 0.273705E+09 | 347.88 | 09-MAY-09:20 | 26.47 | 19.61 |
June | 0.408934E+10 | 11318.18 | 25-JUN-09:12 | 26.67 | 21.38 | 0.274682E+09 | 368.75 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.472119E+10 | 12322.22 | 02-JUL-09:11 | 25.97 | 21.17 | 0.257139E+09 | 349.45 | 03-JUL-09:09 | 25.18 | 21.66 |
August | 0.459096E+10 | 11373.23 | 20-AUG-08:52 | 20.60 | 18.33 | 0.288092E+09 | 372.41 | 04-AUG-07:49 | 20.60 | 18.33 |
September | 0.324731E+10 | 11303.31 | 04-SEP-10:12 | 18.67 | 13.05 | 0.253171E+09 | 347.98 | 05-SEP-09:30 | 21.95 | 14.90 |
October | 0.117430E+10 | 2873.06 | 20-OCT-09:40 | 14.20 | 9.74 | 0.251273E+09 | 347.88 | 20-OCT-09:20 | 14.20 | 9.74 |
November | 0.485705E+09 | 1395.18 | 04-NOV-08:50 | 5.03 | 2.41 | 0.212206E+09 | 347.87 | 03-NOV-13:20 | 5.03 | 2.41 |
December | 56709400.43 | 736.23 | 09-DEC-17:03 | -19.4 | -19.8 | 0.187147E+09 | 285.54 | 05-DEC-10:09 | -19.4 | -19.8 |
Annual Sum or Average | 0.223942E+11 | 0.281795E+10 | ||||||||
Minimum of Months | 35855901.19 | 736.23 | -20.1 | -20.6 | 0.176525E+09 | 275.05 | -19.4 | -19.8 | ||
Maximum of Months | 0.472119E+10 | 12322.22 | 26.67 | 21.38 | 0.288092E+09 | 372.41 | 26.47 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82092165.21 | 1275.25 | 07-JAN-17:03 | -20.1 | -20.6 | 0.260229E+09 | 497.27 | 13-JAN-14:50 | 3.90 | 1.72 |
February | 0.186147E+09 | 1974.46 | 24-FEB-14:30 | 8.05 | 5.40 | 0.255120E+09 | 549.51 | 24-FEB-14:20 | 8.05 | 5.40 |
March | 0.586597E+09 | 4210.48 | 24-MAR-14:00 | 13.30 | 6.51 | 0.337974E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.132541E+10 | 9638.58 | 18-APR-12:00 | 27.80 | 20.94 | 0.325744E+09 | 549.57 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.243146E+10 | 10099.91 | 31-MAY-12:00 | 29.40 | 19.85 | 0.401513E+09 | 549.51 | 03-MAY-13:20 | 29.40 | 19.85 |
June | 0.442062E+10 | 11535.13 | 26-JUN-16:10 | 31.60 | 21.99 | 0.420865E+09 | 562.38 | 26-JUN-12:09 | 31.60 | 21.99 |
July | 0.562246E+10 | 13780.87 | 30-JUL-13:42 | 27.12 | 19.61 | 0.402537E+09 | 549.74 | 17-JUL-13:00 | 27.12 | 19.61 |
August | 0.666506E+10 | 11494.66 | 04-AUG-12:00 | 31.10 | 26.10 | 0.451302E+09 | 574.06 | 04-AUG-12:09 | 31.20 | 26.19 |
September | 0.534003E+10 | 14560.69 | 04-SEP-13:31 | 21.50 | 14.11 | 0.387090E+09 | 608.39 | 07-SEP-12:09 | 30.78 | 18.58 |
October | 0.231086E+10 | 13359.34 | 01-OCT-13:32 | 18.90 | 12.26 | 0.376065E+09 | 549.57 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.867407E+09 | 8361.52 | 05-NOV-14:43 | 15.50 | 10.67 | 0.318240E+09 | 549.50 | 01-NOV-13:39 | 15.50 | 10.67 |
December | 0.209979E+09 | 1303.79 | 02-DEC-12:40 | 5.40 | 2.84 | 0.273794E+09 | 519.37 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.300481E+11 | 0.421047E+10 | ||||||||
Minimum of Months | 82092165.21 | 1275.25 | -20.1 | -20.6 | 0.255120E+09 | 497.27 | 3.90 | 1.72 | ||
Maximum of Months | 0.666506E+10 | 14560.69 | 31.60 | 26.10 | 0.451302E+09 | 608.39 | 31.60 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35113053.27 | 783.70 | 07-JAN-17:03 | -20.1 | -20.6 | 0.191717E+09 | 301.82 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.107378E+09 | 1673.67 | 24-FEB-16:30 | 7.75 | 5.51 | 0.176157E+09 | 338.67 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.441721E+09 | 1760.64 | 23-MAR-16:00 | 17.20 | 10.15 | 0.223421E+09 | 346.85 | 24-MAR-13:00 | 13.30 | 6.51 |
April | 0.120808E+10 | 8898.54 | 15-APR-17:04 | 29.72 | 18.80 | 0.218879E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.210457E+10 | 12087.38 | 14-MAY-16:21 | 21.70 | 15.50 | 0.267425E+09 | 347.86 | 09-MAY-09:20 | 21.70 | 15.50 |
June | 0.387272E+10 | 12389.15 | 25-JUN-17:11 | 31.50 | 21.73 | 0.273562E+09 | 347.86 | 20-JUN-13:00 | 31.50 | 21.73 |
July | 0.463817E+10 | 12635.22 | 02-JUL-17:51 | 28.30 | 21.02 | 0.257049E+09 | 348.05 | 03-JUL-09:09 | 25.18 | 21.66 |
August | 0.467640E+10 | 11986.31 | 13-AUG-16:21 | 25.30 | 20.50 | 0.288081E+09 | 348.58 | 22-AUG-09:30 | 24.75 | 22.24 |
September | 0.308878E+10 | 12945.47 | 04-SEP-16:51 | 22.20 | 14.41 | 0.250731E+09 | 347.85 | 20-SEP-09:20 | 17.20 | 10.73 |
October | 0.132433E+10 | 5003.56 | 11-OCT-16:00 | 17.80 | 11.96 | 0.243554E+09 | 347.84 | 19-OCT-13:20 | 17.33 | 9.97 |
November | 0.525421E+09 | 3225.90 | 03-NOV-15:40 | 15.37 | 9.43 | 0.213223E+09 | 347.84 | 07-NOV-14:30 | 13.05 | 11.26 |
December | 78419561.80 | 754.00 | 01-DEC-15:50 | -1.6 | -4.0 | 0.188493E+09 | 313.77 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.221011E+11 | 0.279229E+10 | ||||||||
Minimum of Months | 35113053.27 | 754.00 | -20.1 | -20.6 | 0.176157E+09 | 301.82 | -1.7 | -4.1 | ||
Maximum of Months | 0.467640E+10 | 12945.47 | 31.50 | 21.73 | 0.288081E+09 | 348.58 | 31.50 | 22.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33763037.18 | 1251.86 | 07-JAN-17:01 | -20.1 | -20.6 | 0.300592E+09 | 417.76 | 13-JAN-14:50 | 3.90 | 1.72 |
February | 0.103770E+09 | 1228.01 | 04-FEB-17:01 | -20.1 | -20.6 | 0.274216E+09 | 443.09 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.708092E+09 | 1317.70 | 28-MAR-15:30 | 16.40 | 10.50 | 0.355191E+09 | 539.30 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.163337E+10 | 5279.76 | 18-APR-15:00 | 28.30 | 20.65 | 0.349688E+09 | 549.49 | 18-APR-09:20 | 28.30 | 20.65 |
May | 0.327884E+10 | 7415.42 | 30-MAY-06:02 | 15.18 | 15.13 | 0.429283E+09 | 549.50 | 09-MAY-09:20 | 15.18 | 15.13 |
June | 0.491823E+10 | 9682.36 | 25-JUN-18:21 | 30.25 | 21.63 | 0.434234E+09 | 557.20 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.519603E+10 | 9541.94 | 02-JUL-19:12 | 26.47 | 20.76 | 0.405334E+09 | 550.42 | 03-JUL-13:20 | 29.07 | 24.32 |
August | 0.495198E+10 | 6269.07 | 04-AUG-07:25 | 24.75 | 24.18 | 0.453964E+09 | 568.37 | 04-AUG-07:30 | 24.75 | 24.18 |
September | 0.310208E+10 | 7464.23 | 11-SEP-06:03 | 19.50 | 17.29 | 0.391302E+09 | 550.50 | 11-SEP-13:20 | 28.50 | 20.29 |
October | 0.144188E+10 | 2146.44 | 02-OCT-14:50 | 18.15 | 14.79 | 0.366356E+09 | 549.49 | 02-OCT-13:20 | 18.15 | 14.79 |
November | 0.643253E+09 | 1532.54 | 03-NOV-13:10 | 15.68 | 10.94 | 0.327994E+09 | 542.76 | 07-NOV-14:30 | 13.05 | 11.26 |
December | 14152018.79 | 1072.35 | 09-DEC-17:03 | -19.4 | -19.8 | 0.293458E+09 | 406.79 | 12-DEC-14:00 | -15.6 | -16.1 |
Annual Sum or Average | 0.260254E+11 | 0.438161E+10 | ||||||||
Minimum of Months | 14152018.79 | 1072.35 | -20.1 | -20.6 | 0.274216E+09 | 406.79 | -15.6 | -16.1 | ||
Maximum of Months | 0.519603E+10 | 9682.36 | 30.25 | 24.18 | 0.453964E+09 | 568.37 | 29.07 | 24.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39586989.53 | 794.53 | 07-JAN-17:01 | -20.1 | -20.6 | 0.141843E+09 | 297.35 | 13-JAN-11:09 | 2.48 | 0.68 |
February | 0.142353E+09 | 2242.13 | 24-FEB-11:05 | 5.68 | 2.52 | 0.132283E+09 | 356.45 | 24-FEB-11:09 | 5.68 | 2.52 |
March | 0.628336E+09 | 5150.79 | 24-MAR-12:02 | 11.78 | 6.31 | 0.177443E+09 | 356.46 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.157924E+10 | 8391.18 | 18-APR-10:05 | 25.78 | 20.58 | 0.171722E+09 | 356.46 | 06-APR-12:09 | 25.78 | 20.58 |
May | 0.327289E+10 | 11970.74 | 21-MAY-08:62 | 11.05 | 7.09 | 0.204054E+09 | 356.47 | 04-MAY-10:09 | 11.05 | 7.09 |
June | 0.472696E+10 | 15487.23 | 25-JUN-08:21 | 25.00 | 20.84 | 0.204151E+09 | 377.18 | 26-JUN-08:09 | 25.37 | 22.03 |
July | 0.509618E+10 | 15706.49 | 02-JUL-08:31 | 25.03 | 20.84 | 0.191325E+09 | 356.46 | 18-JUL-10:09 | 22.30 | 15.22 |
August | 0.464783E+10 | 14269.24 | 27-AUG-09:22 | 23.60 | 19.50 | 0.213318E+09 | 360.66 | 04-AUG-07:30 | 23.60 | 19.50 |
September | 0.313086E+10 | 11558.91 | 04-SEP-09:02 | 16.47 | 13.08 | 0.186506E+09 | 356.46 | 21-SEP-12:09 | 12.30 | 11.36 |
October | 0.100429E+10 | 5444.21 | 23-OCT-12:01 | 6.78 | 2.68 | 0.181990E+09 | 356.46 | 23-OCT-12:09 | 6.78 | 2.68 |
November | 0.376199E+09 | 3776.43 | 01-NOV-12:02 | 13.22 | 8.53 | 0.155071E+09 | 356.45 | 03-NOV-10:09 | 13.07 | 11.22 |
December | 57996910.32 | 690.99 | 09-DEC-17:03 | -19.4 | -19.8 | 0.137427E+09 | 294.92 | 05-DEC-09:00 | -19.4 | -19.8 |
Annual Sum or Average | 0.247027E+11 | 0.209713E+10 | ||||||||
Minimum of Months | 39586989.53 | 690.99 | -20.1 | -20.6 | 0.132283E+09 | 294.92 | -19.4 | -19.8 | ||
Maximum of Months | 0.509618E+10 | 15706.49 | 25.78 | 20.84 | 0.213318E+09 | 377.18 | 25.78 | 22.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.730237E+09 | 5679.52 | 12-JAN-12:30 | 1.95 | 0.38 | 0.332379E+09 | 549.50 | 03-JAN-14:20 | 1.95 | 0.38 |
February | 0.107405E+10 | 8511.93 | 24-FEB-13:35 | 7.43 | 4.81 | 0.310589E+09 | 549.50 | 24-FEB-14:20 | 7.97 | 5.32 |
March | 0.202565E+10 | 9089.54 | 24-MAR-13:05 | 12.38 | 6.48 | 0.392395E+09 | 549.55 | 24-MAR-13:20 | 12.57 | 6.49 |
April | 0.322812E+10 | 16289.56 | 16-APR-13:52 | 27.80 | 20.59 | 0.366680E+09 | 550.38 | 18-APR-13:20 | 27.57 | 20.63 |
May | 0.453609E+10 | 11265.69 | 29-MAY-12:23 | 24.45 | 18.92 | 0.431303E+09 | 550.71 | 30-MAY-13:20 | 26.70 | 19.86 |
June | 0.595676E+10 | 15480.87 | 25-JUN-13:02 | 31.78 | 22.68 | 0.434088E+09 | 550.78 | 30-JUN-13:20 | 29.40 | 21.96 |
July | 0.662985E+10 | 16093.83 | 30-JUL-13:42 | 27.12 | 19.61 | 0.405543E+09 | 550.91 | 17-JUL-13:20 | 27.12 | 19.61 |
August | 0.724103E+10 | 15952.81 | 13-AUG-13:12 | 25.37 | 19.81 | 0.454516E+09 | 551.56 | 29-AUG-13:50 | 23.80 | 16.18 |
September | 0.606841E+10 | 15829.59 | 04-SEP-13:02 | 21.20 | 14.03 | 0.397763E+09 | 571.31 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.367061E+10 | 15635.73 | 01-OCT-12:43 | 18.63 | 12.19 | 0.396085E+09 | 549.71 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.145900E+10 | 10934.10 | 03-NOV-13:05 | 15.68 | 10.94 | 0.352732E+09 | 549.63 | 03-NOV-13:30 | 15.85 | 10.76 |
December | 0.864734E+09 | 6706.28 | 01-DEC-13:14 | -0.9 | -3.3 | 0.323407E+09 | 549.49 | 28-DEC-14:20 | -4.8 | -6.0 |
Annual Sum or Average | 0.434845E+11 | 0.459748E+10 | ||||||||
Minimum of Months | 0.730237E+09 | 5679.52 | -0.9 | -3.3 | 0.310589E+09 | 549.49 | -4.8 | -6.0 | ||
Maximum of Months | 0.724103E+10 | 16289.56 | 31.78 | 22.68 | 0.454516E+09 | 571.31 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82171872.01 | 896.69 | 31-JAN-16:30 | -20.3 | -20.7 | 0.193792E+09 | 335.08 | 12-JAN-16:10 | -20.3 | -20.7 |
February | 0.218960E+09 | 3008.41 | 24-FEB-16:30 | 7.75 | 5.51 | 0.179817E+09 | 347.83 | 24-FEB-14:50 | 7.75 | 5.51 |
March | 0.741970E+09 | 3805.45 | 21-MAR-16:00 | -0.6 | -4.1 | 0.232480E+09 | 347.84 | 28-MAR-13:20 | 15.97 | 9.97 |
April | 0.195949E+10 | 14776.77 | 16-APR-17:52 | 26.70 | 19.84 | 0.227623E+09 | 347.85 | 18-APR-09:20 | 23.73 | 19.27 |
May | 0.317335E+10 | 14139.84 | 14-MAY-16:32 | 21.70 | 15.60 | 0.272373E+09 | 347.86 | 08-MAY-13:00 | 21.70 | 15.60 |
June | 0.471003E+10 | 15912.26 | 25-JUN-17:41 | 31.20 | 21.79 | 0.274943E+09 | 347.86 | 20-JUN-13:00 | 31.20 | 21.79 |
July | 0.517104E+10 | 15053.57 | 02-JUL-16:32 | 29.07 | 21.24 | 0.256943E+09 | 348.12 | 03-JUL-09:09 | 25.18 | 21.66 |
August | 0.493165E+10 | 15422.84 | 13-AUG-16:31 | 25.20 | 20.49 | 0.287748E+09 | 347.87 | 08-AUG-09:09 | 25.20 | 20.49 |
September | 0.314871E+10 | 13862.56 | 04-SEP-16:22 | 22.20 | 14.41 | 0.248810E+09 | 347.86 | 06-SEP-09:20 | 23.73 | 17.58 |
October | 0.138512E+10 | 5830.36 | 11-OCT-16:00 | 17.80 | 11.96 | 0.238372E+09 | 347.84 | 04-OCT-13:20 | 17.80 | 11.96 |
November | 0.507877E+09 | 4046.65 | 03-NOV-15:30 | 15.55 | 9.47 | 0.211988E+09 | 347.84 | 07-NOV-14:00 | 13.30 | 11.35 |
December | 0.100782E+09 | 819.18 | 01-DEC-15:50 | -1.6 | -4.0 | 0.190187E+09 | 336.04 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.261311E+11 | 0.281508E+10 | ||||||||
Minimum of Months | 82171872.01 | 819.18 | -20.3 | -20.7 | 0.179817E+09 | 335.08 | -20.3 | -20.7 | ||
Maximum of Months | 0.517104E+10 | 15912.26 | 31.20 | 21.79 | 0.287748E+09 | 348.12 | 31.20 | 21.79 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260430E+09 | 10615.99 | 02-JAN-05:01 | -4.5 |
February | 27670960.95 | 7572.26 | 06-FEB-06:01 | -15.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 2316532.51 | 5974.54 | 27-NOV-07:01 | -9.4 |
December | 6106054.08 | 6130.51 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.296523E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.260430E+09 | 10615.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102401E+11 | 16900.96 | 31-JAN-06:12 | -30.6 |
February | 0.639864E+10 | 18094.59 | 04-FEB-06:10 | -30.7 |
March | 0.330091E+10 | 14919.10 | 06-MAR-06:08 | -14.1 |
April | 0.142235E+10 | 12498.19 | 03-APR-05:13 | -7.2 |
May | 0.383724E+09 | 4971.87 | 21-MAY-08:62 | 11.05 |
June | 0.195662E+09 | 4431.85 | 19-JUN-05:12 | 11.87 |
July | 0.110915E+09 | 3679.79 | 31-JUL-05:12 | 17.07 |
August | 0.176399E+09 | 2950.93 | 20-AUG-07:07 | 16.97 |
September | 0.597796E+09 | 5497.51 | 30-SEP-06:03 | 0.60 |
October | 0.127292E+10 | 8044.52 | 23-OCT-06:01 | -3.0 |
November | 0.411905E+10 | 15529.37 | 28-NOV-06:10 | -18.2 |
December | 0.776665E+10 | 16540.40 | 11-DEC-06:10 | -22.1 |
Annual Sum or Average | 0.359851E+11 | |||
Minimum of Months | 0.110915E+09 | 2950.93 | -30.7 | |
Maximum of Months | 0.102401E+11 | 18094.59 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.417512E+10 | 9745.07 | 02-JAN-08:06 | -7.4 |
February | 0.262176E+10 | 9485.19 | 06-FEB-08:10 | -14.8 |
March | 0.170468E+10 | 7478.07 | 06-MAR-07:16 | -12.6 |
April | 0.759984E+09 | 6601.03 | 03-APR-06:11 | -7.0 |
May | 96056346.04 | 3806.54 | 21-MAY-08:62 | 11.05 |
June | 34630985.42 | 4180.77 | 11-JUN-15:11 | 33.13 |
July | 36038178.70 | 3838.57 | 02-JUL-15:11 | 29.40 |
August | 24501748.09 | 3867.01 | 13-AUG-15:11 | 25.93 |
September | 0.165952E+09 | 4181.19 | 04-SEP-15:42 | 22.20 |
October | 0.867532E+09 | 5922.78 | 29-OCT-12:03 | 11.88 |
November | 0.188585E+10 | 8974.51 | 27-NOV-08:61 | -9.4 |
December | 0.323306E+10 | 9981.61 | 11-DEC-08:19 | -21.7 |
Annual Sum or Average | 0.156052E+11 | |||
Minimum of Months | 24501748.09 | 3806.54 | -21.7 | |
Maximum of Months | 0.417512E+10 | 9981.61 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296264E+10 | 8065.14 | 02-JAN-08:45 | -8.1 |
February | 0.186082E+10 | 5642.47 | 06-FEB-06:12 | -15.0 |
March | 0.121261E+10 | 3459.17 | 06-MAR-09:00 | -10.0 |
April | 0.438009E+09 | 3303.80 | 21-APR-05:03 | 0.60 |
May | 30240434.85 | 2013.14 | 14-MAY-16:21 | 21.70 |
June | 22259461.84 | 2184.68 | 22-JUN-05:12 | 9.97 |
July | 35603208.12 | 2397.38 | 30-JUL-13:42 | 27.12 |
August | 25218653.15 | 2299.72 | 13-AUG-15:02 | 26.02 |
September | 62774159.68 | 3610.03 | 29-SEP-05:03 | 0.92 |
October | 0.271400E+09 | 6832.89 | 23-OCT-05:01 | -2.7 |
November | 0.124220E+10 | 5618.18 | 27-NOV-07:01 | -9.4 |
December | 0.228051E+10 | 5284.45 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.104443E+11 | |||
Minimum of Months | 22259461.84 | 2013.14 | -21.7 | |
Maximum of Months | 0.296264E+10 | 8065.14 | 27.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206862E+10 | 18424.47 | 02-JAN-05:01 | -4.5 |
February | 0.883414E+09 | 17130.62 | 06-FEB-05:11 | -14.6 |
March | 0.130079E+09 | 15162.26 | 06-MAR-06:02 | -14.1 |
April | 25150015.53 | 14232.40 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.396332E+09 | 17073.92 | 27-NOV-05:01 | -9.4 |
December | 0.942844E+09 | 17121.88 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.444644E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.206862E+10 | 18424.47 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685694E+10 | 25353.19 | 17-JAN-05:01 | -6.8 |
February | 0.370604E+10 | 25128.36 | 06-FEB-05:01 | -14.5 |
March | 0.125116E+10 | 24715.16 | 06-MAR-05:01 | -15.4 |
April | 0.257640E+09 | 23541.29 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1712522.87 | 11416.82 | 30-SEP-06:03 | 0.60 |
October | 50184846.50 | 19591.66 | 16-OCT-06:02 | -0.4 |
November | 0.211556E+10 | 25472.01 | 27-NOV-05:01 | -9.4 |
December | 0.455820E+10 | 25839.85 | 11-DEC-00:02 | -21.7 |
Annual Sum or Average | 0.187974E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.685694E+10 | 25839.85 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.949134E+10 | 10180.56 | 29-JAN-16:42 | -21.6 |
February | 0.567636E+10 | 10425.51 | 02-FEB-03:02 | -35.0 |
March | 0.256245E+10 | 10091.56 | 06-MAR-04:22 | -15.9 |
April | 0.642750E+09 | 9592.03 | 03-APR-04:01 | -6.8 |
May | 7037210.16 | 7425.59 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 54202270.63 | 8134.05 | 30-SEP-05:02 | 0.10 |
October | 0.390770E+09 | 8605.16 | 16-OCT-05:01 | 0.48 |
November | 0.339221E+10 | 10181.10 | 26-NOV-01:42 | -24.4 |
December | 0.718673E+10 | 10436.91 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.294039E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.949134E+10 | 10436.91 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569269E+10 | 9415.64 | 29-JAN-04:42 | -19.5 |
February | 0.318691E+10 | 9709.05 | 02-FEB-03:02 | -35.0 |
March | 0.132187E+10 | 9297.40 | 06-MAR-04:22 | -15.9 |
April | 0.333354E+09 | 8782.31 | 03-APR-04:01 | -6.8 |
May | 1067230.05 | 5798.44 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 23860987.92 | 6951.69 | 30-SEP-05:02 | 0.10 |
October | 0.185831E+09 | 7516.85 | 16-OCT-05:01 | 0.48 |
November | 0.201759E+10 | 9421.33 | 26-NOV-01:42 | -24.4 |
December | 0.436220E+10 | 9740.99 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.171254E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.569269E+10 | 9740.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652355E+10 | 12608.57 | 29-JAN-04:42 | -19.5 |
February | 0.360608E+10 | 12840.43 | 02-FEB-03:02 | -35.0 |
March | 0.182140E+10 | 12466.03 | 06-MAR-04:22 | -15.9 |
April | 0.519587E+09 | 11901.48 | 03-APR-04:01 | -6.8 |
May | 7219102.00 | 8728.64 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 37827669.80 | 9660.71 | 30-SEP-05:02 | 0.10 |
October | 0.239190E+09 | 10300.27 | 16-OCT-05:01 | 0.48 |
November | 0.236708E+10 | 12649.66 | 27-NOV-01:02 | -11.6 |
December | 0.537098E+10 | 12955.07 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.204929E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.652355E+10 | 12955.07 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584870E+10 | 9833.92 | 29-JAN-04:42 | -19.5 |
February | 0.332648E+10 | 10196.42 | 02-FEB-03:02 | -35.0 |
March | 0.148782E+10 | 9684.42 | 06-MAR-04:22 | -15.9 |
April | 0.361093E+09 | 9193.61 | 03-APR-04:01 | -6.8 |
May | 5639717.18 | 6292.35 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 36333916.29 | 7291.37 | 30-SEP-05:02 | 0.10 |
October | 0.226312E+09 | 7904.46 | 16-OCT-05:01 | 0.48 |
November | 0.208295E+10 | 9835.61 | 26-NOV-01:42 | -24.4 |
December | 0.448043E+10 | 10231.13 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.178557E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.584870E+10 | 10231.13 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668398E+10 | 7543.88 | 30-JAN-05:11 | -28.0 |
February | 0.416427E+10 | 7675.56 | 02-FEB-04:42 | -35.9 |
March | 0.192030E+10 | 7224.17 | 06-MAR-05:01 | -15.4 |
April | 0.484363E+09 | 6973.33 | 03-APR-04:01 | -6.8 |
May | 4019735.09 | 5771.31 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 663557.80 | 3194.60 | 30-SEP-06:03 | 0.60 |
October | 13922764.63 | 5764.82 | 16-OCT-06:02 | -0.4 |
November | 0.144881E+10 | 7224.90 | 28-NOV-05:01 | -21.1 |
December | 0.408832E+10 | 7589.03 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.188086E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 0.668398E+10 | 7675.56 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397804E+10 | 7123.15 | 30-JAN-05:11 | -28.0 |
February | 0.218867E+10 | 7110.31 | 02-FEB-04:42 | -35.9 |
March | 0.858781E+09 | 6725.95 | 06-MAR-05:01 | -15.4 |
April | 0.195807E+09 | 6435.23 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 2501501.06 | 4815.14 | 27-OCT-06:02 | 0.25 |
November | 0.797092E+09 | 6753.17 | 28-NOV-05:01 | -21.1 |
December | 0.241463E+10 | 7133.10 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.104355E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 0.397804E+10 | 7133.10 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844390E+10 | 13593.68 | 30-JAN-07:07 | -29.0 |
February | 0.539984E+10 | 13938.04 | 02-FEB-07:06 | -36.7 |
March | 0.404848E+10 | 11193.31 | 06-MAR-07:50 | -12.3 |
April | 0.186739E+10 | 10401.08 | 03-APR-06:50 | -6.8 |
May | 0.472159E+09 | 8130.49 | 02-MAY-06:10 | 2.30 |
June | 0.150984E+09 | 6968.13 | 02-JUN-06:30 | 7.50 |
July | 1022685.19 | 2837.91 | 12-JUL-06:08 | 14.18 |
August | 16540123.47 | 6778.06 | 07-AUG-06:06 | 8.87 |
September | 0.325234E+09 | 8228.98 | 29-SEP-06:10 | 0.10 |
October | 0.859647E+09 | 8588.10 | 23-OCT-06:10 | -3.0 |
November | 0.314178E+10 | 11756.43 | 28-NOV-08:00 | -16.7 |
December | 0.631204E+10 | 12137.01 | 11-DEC-07:06 | -21.7 |
Annual Sum or Average | 0.310390E+11 | |||
Minimum of Months | 1022685.19 | 2837.91 | -36.7 | |
Maximum of Months | 0.844390E+10 | 13938.04 | 14.18 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407629E+10 | 7366.97 | 30-JAN-05:11 | -28.0 |
February | 0.222177E+10 | 7373.90 | 02-FEB-04:42 | -35.9 |
March | 0.966482E+09 | 6953.65 | 06-MAR-05:01 | -15.4 |
April | 0.172836E+09 | 6708.74 | 03-APR-04:01 | -6.8 |
May | 1214030.27 | 4821.97 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 520561.12 | 2430.83 | 30-SEP-06:03 | 0.60 |
October | 2973529.63 | 4951.02 | 16-OCT-06:02 | -0.4 |
November | 0.835509E+09 | 7020.51 | 28-NOV-05:01 | -21.1 |
December | 0.246359E+10 | 7418.56 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.107412E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 0.407629E+10 | 7418.56 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.627974E+10 | 8245.51 | 30-JAN-05:11 | -28.0 |
February | 0.341298E+10 | 8358.39 | 02-FEB-05:11 | -36.3 |
March | 0.117584E+10 | 8019.17 | 06-MAR-04:22 | -15.9 |
April | 0.206066E+09 | 7580.46 | 03-APR-04:01 | -6.8 |
May | 154867.17 | 1290.56 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3702533.84 | 6087.17 | 30-SEP-06:03 | 0.60 |
October | 39968081.89 | 6364.63 | 16-OCT-05:01 | 0.48 |
November | 0.177631E+10 | 7979.45 | 26-NOV-04:52 | -25.0 |
December | 0.426000E+10 | 8147.20 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.171548E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.627974E+10 | 8358.39 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362769E+10 | 8108.44 | 30-JAN-05:11 | -28.0 |
February | 0.182889E+10 | 8254.04 | 02-FEB-05:11 | -36.3 |
March | 0.591826E+09 | 7722.80 | 06-MAR-04:22 | -15.9 |
April | 0.102984E+09 | 7238.33 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 1971453.41 | 4735.96 | 30-SEP-06:03 | 0.60 |
October | 20492874.68 | 5316.80 | 23-OCT-06:01 | -3.0 |
November | 0.102397E+10 | 7694.74 | 26-NOV-04:52 | -25.0 |
December | 0.254882E+10 | 7975.02 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.974665E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.362769E+10 | 8254.04 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383314E+10 | 10408.35 | 30-JAN-05:11 | -28.0 |
February | 0.183771E+10 | 10545.40 | 02-FEB-05:11 | -36.3 |
March | 0.753600E+09 | 9922.13 | 06-MAR-05:01 | -15.4 |
April | 0.148365E+09 | 9436.23 | 03-APR-04:01 | -6.8 |
May | 99467.40 | 828.90 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2655456.04 | 6666.39 | 30-SEP-06:03 | 0.60 |
October | 21872393.84 | 7373.95 | 23-OCT-06:01 | -3.0 |
November | 0.109907E+10 | 9884.36 | 27-NOV-05:01 | -9.4 |
December | 0.298600E+10 | 10289.71 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.106825E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.383314E+10 | 10545.40 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377343E+10 | 8260.47 | 30-JAN-05:11 | -28.0 |
February | 0.191726E+10 | 8425.63 | 02-FEB-05:11 | -36.3 |
March | 0.657042E+09 | 7807.51 | 06-MAR-05:01 | -15.4 |
April | 0.103121E+09 | 7399.43 | 03-APR-04:01 | -6.8 |
May | 172725.55 | 1439.38 | 02-MAY-06:02 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 3159034.25 | 5201.83 | 30-SEP-06:03 | 0.60 |
October | 24714011.62 | 5640.63 | 16-OCT-05:01 | 0.48 |
November | 0.107596E+10 | 7740.22 | 26-NOV-04:52 | -25.0 |
December | 0.263742E+10 | 8134.41 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.101923E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.377343E+10 | 8425.63 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642017E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539419E+09 | 861.30 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.592169E+09 | 713.39 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512743E+09 | 582.71 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533475E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527908E+09 | 558.23 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496726E+09 | 558.93 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557382E+09 | 534.75 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521304E+09 | 582.95 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570537E+09 | 999.89 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.623687E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.656333E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677370E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496726E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.656333E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.398674E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.337524E+09 | 553.80 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373966E+09 | 466.11 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324567E+09 | 359.10 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340086E+09 | 341.17 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.336131E+09 | 342.18 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315866E+09 | 342.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354445E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330215E+09 | 359.51 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356917E+09 | 579.16 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389859E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.404503E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426275E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315866E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.404503E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616006E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523399E+09 | 831.79 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588084E+09 | 584.36 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512537E+09 | 581.52 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536636E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530959E+09 | 561.32 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498829E+09 | 562.21 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559943E+09 | 525.40 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519788E+09 | 579.33 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558641E+09 | 938.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.605018E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.621366E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667121E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498829E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.621366E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396450E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335403E+09 | 512.03 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373339E+09 | 446.22 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324148E+09 | 433.72 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337859E+09 | 333.72 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.334102E+09 | 359.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314619E+09 | 360.66 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.353064E+09 | 350.85 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328486E+09 | 441.39 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358849E+09 | 634.82 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387129E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402382E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424583E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314619E+09 | 333.72 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402382E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639234E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.537659E+09 | 852.01 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.590993E+09 | 700.68 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511725E+09 | 579.93 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533017E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527600E+09 | 554.27 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496470E+09 | 555.00 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557037E+09 | 529.71 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.520565E+09 | 580.19 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.569030E+09 | 998.04 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.621405E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.652612E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.675735E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496470E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.652612E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397625E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.336523E+09 | 549.03 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373400E+09 | 460.16 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324219E+09 | 356.93 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.339828E+09 | 338.98 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335934E+09 | 339.30 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315643E+09 | 339.93 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354181E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329875E+09 | 357.52 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356370E+09 | 575.10 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389128E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402963E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425569E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315643E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402963E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.614957E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.522849E+09 | 823.41 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587526E+09 | 581.59 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.511867E+09 | 578.67 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536077E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530488E+09 | 557.54 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498444E+09 | 558.48 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559349E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519211E+09 | 576.36 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558152E+09 | 933.42 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.604107E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.619735E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.666276E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498444E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.619735E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.395478E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334708E+09 | 506.99 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.372963E+09 | 437.07 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323606E+09 | 426.88 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337598E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333782E+09 | 357.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314450E+09 | 358.72 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352792E+09 | 348.56 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328042E+09 | 434.76 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358085E+09 | 633.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.386254E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400977E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423874E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314450E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.400977E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642015E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.539417E+09 | 861.30 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.592168E+09 | 713.37 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512742E+09 | 582.70 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.533474E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.527908E+09 | 558.22 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.496726E+09 | 558.92 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.557381E+09 | 534.74 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.521303E+09 | 582.95 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.570535E+09 | 999.89 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.623685E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.656328E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677368E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.496726E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.656328E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.398673E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.337523E+09 | 553.80 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373966E+09 | 466.10 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324567E+09 | 359.09 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340085E+09 | 341.17 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.336131E+09 | 342.18 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315866E+09 | 342.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354445E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330214E+09 | 359.51 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356916E+09 | 579.16 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389858E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.404490E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426273E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315866E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.404490E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616005E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.523399E+09 | 831.77 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588084E+09 | 584.35 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512536E+09 | 581.52 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.536635E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.530958E+09 | 561.31 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498826E+09 | 562.20 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.559943E+09 | 525.39 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.519788E+09 | 579.33 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558640E+09 | 938.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.605017E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.621412E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667124E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498826E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.621412E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396449E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335402E+09 | 512.02 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373338E+09 | 446.23 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324147E+09 | 433.70 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337859E+09 | 333.71 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.334102E+09 | 359.34 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314619E+09 | 360.65 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.353064E+09 | 350.85 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.328486E+09 | 441.37 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358848E+09 | 634.82 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387128E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.402380E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424582E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314619E+09 | 333.71 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402380E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642017E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129072E+10 |
February | 0.901968E+09 | 0.539419E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.945760E+09 |
March | 0.107774E+10 | 0.592169E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819292E+09 |
April | 0.956342E+09 | 0.512743E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4212865.04 | 0.517153E+09 |
May | 0.103597E+10 | 0.533475E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1586106.90 | 0.296755E+09 |
June | 0.103308E+10 | 0.527908E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20230833.70 | 0.173731E+09 |
July | 0.959235E+09 | 0.496726E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6944199.49 | 0.126957E+09 |
August | 0.107774E+10 | 0.557382E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7818562.03 | 0.171201E+09 |
September | 0.956342E+09 | 0.521304E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5765591.41 | 0.264295E+09 |
October | 0.994195E+09 | 0.570537E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490716E+09 |
November | 0.984487E+09 | 0.623687E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807131E+09 |
December | 0.959235E+09 | 0.656333E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108125E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677370E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46558158.56 | 0.698496E+10 |
Minimum of Months | 0.901968E+09 | 0.496726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126957E+09 |
Maximum of Months | 0.107774E+10 | 0.656333E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20230833.70 | 0.129072E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.398674E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862516E+09 |
February | 0.571020E+09 | 0.337524E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634138E+09 |
March | 0.682301E+09 | 0.373966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554847E+09 |
April | 0.605444E+09 | 0.324567E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2610439.10 | 0.356882E+09 |
May | 0.655854E+09 | 0.340086E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057279.52 | 0.204547E+09 |
June | 0.654023E+09 | 0.336131E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12891863.54 | 0.118461E+09 |
July | 0.607275E+09 | 0.315866E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4366036.91 | 87370202.53 |
August | 0.682301E+09 | 0.354445E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5107109.18 | 0.116937E+09 |
September | 0.605444E+09 | 0.330215E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3417977.90 | 0.183934E+09 |
October | 0.629407E+09 | 0.356917E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340394E+09 |
November | 0.623262E+09 | 0.389859E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541785E+09 |
December | 0.607275E+09 | 0.404503E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723537E+09 |
Annual Sum or Average | 0.755301E+10 | 0.426275E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29450706.15 | 0.472535E+10 |
Minimum of Months | 0.571020E+09 | 0.315866E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87370202.53 |
Maximum of Months | 0.682301E+09 | 0.404503E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12891863.54 | 0.862516E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.616006E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130893E+10 |
February | 0.901968E+09 | 0.523399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.973077E+09 |
March | 0.107774E+10 | 0.588084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853196E+09 |
April | 0.956342E+09 | 0.512537E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3579332.23 | 0.542311E+09 |
May | 0.103597E+10 | 0.536636E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1585984.20 | 0.304542E+09 |
June | 0.103308E+10 | 0.530959E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19502285.84 | 0.174572E+09 |
July | 0.959235E+09 | 0.498829E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6533945.71 | 0.128934E+09 |
August | 0.107774E+10 | 0.559943E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7630907.18 | 0.177843E+09 |
September | 0.956342E+09 | 0.519788E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4913316.49 | 0.283009E+09 |
October | 0.994195E+09 | 0.558641E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535859E+09 |
November | 0.984487E+09 | 0.605018E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834779E+09 |
December | 0.959235E+09 | 0.621366E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110962E+10 |
Annual Sum or Average | 0.119305E+11 | 0.667121E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43745771.65 | 0.722667E+10 |
Minimum of Months | 0.901968E+09 | 0.498829E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128934E+09 |
Maximum of Months | 0.107774E+10 | 0.621366E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19502285.84 | 0.130893E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.396450E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863040E+09 |
February | 0.570983E+09 | 0.335403E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637153E+09 |
March | 0.682256E+09 | 0.373339E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555701E+09 |
April | 0.605404E+09 | 0.324148E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2225367.35 | 0.360883E+09 |
May | 0.655811E+09 | 0.337859E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1057453.27 | 0.205610E+09 |
June | 0.653980E+09 | 0.334102E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12590075.18 | 0.119305E+09 |
July | 0.607235E+09 | 0.314619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4319570.27 | 90195157.20 |
August | 0.682256E+09 | 0.353064E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5127642.71 | 0.120569E+09 |
September | 0.605404E+09 | 0.328486E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3303860.59 | 0.185630E+09 |
October | 0.629366E+09 | 0.358849E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338088E+09 |
November | 0.623221E+09 | 0.387129E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542525E+09 |
December | 0.607235E+09 | 0.402382E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724101E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424583E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28623969.36 | 0.474280E+10 |
Minimum of Months | 0.570983E+09 | 0.314619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90195157.20 |
Maximum of Months | 0.682256E+09 | 0.402382E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12590075.18 | 0.863040E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.639234E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694954E+09 |
February | 0.901968E+09 | 0.537659E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516914E+09 |
March | 0.107774E+10 | 0.590993E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443704E+09 |
April | 0.956342E+09 | 0.511725E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4158336.60 | 0.272826E+09 |
May | 0.103597E+10 | 0.533017E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 873592.30 | 0.151191E+09 |
June | 0.103308E+10 | 0.527600E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13285559.56 | 90493887.07 |
July | 0.959235E+09 | 0.496470E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4451502.00 | 65823818.25 |
August | 0.107774E+10 | 0.557037E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4419177.00 | 92858561.12 |
September | 0.956342E+09 | 0.520565E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3772690.46 | 0.149254E+09 |
October | 0.994195E+09 | 0.569030E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290696E+09 |
November | 0.984487E+09 | 0.621405E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461620E+09 |
December | 0.959235E+09 | 0.652612E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596070E+09 |
Annual Sum or Average | 0.119305E+11 | 0.675735E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30960857.92 | 0.382641E+10 |
Minimum of Months | 0.901968E+09 | 0.496470E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65823818.25 |
Maximum of Months | 0.107774E+10 | 0.652612E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13285559.56 | 0.694954E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.397625E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465482E+09 |
February | 0.571020E+09 | 0.336523E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347727E+09 |
March | 0.682301E+09 | 0.373400E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302577E+09 |
April | 0.605444E+09 | 0.324219E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2066817.27 | 0.191597E+09 |
May | 0.655854E+09 | 0.339828E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 573996.68 | 0.109200E+09 |
June | 0.654023E+09 | 0.335934E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7440212.38 | 63926358.40 |
July | 0.607275E+09 | 0.315643E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2445719.03 | 47343417.29 |
August | 0.682301E+09 | 0.354181E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2789502.98 | 65250147.53 |
September | 0.605444E+09 | 0.329875E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1910987.58 | 0.106135E+09 |
October | 0.629407E+09 | 0.356370E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204294E+09 |
November | 0.623262E+09 | 0.389128E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310776E+09 |
December | 0.607275E+09 | 0.402963E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399399E+09 |
Annual Sum or Average | 0.755301E+10 | 0.425569E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17227235.92 | 0.261371E+10 |
Minimum of Months | 0.571020E+09 | 0.315643E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47343417.29 |
Maximum of Months | 0.682301E+09 | 0.402963E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7440212.38 | 0.465482E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.614957E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895675E+10 |
February | 0.901968E+09 | 0.522849E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682056E+10 |
March | 0.107774E+10 | 0.587526E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595777E+10 |
April | 0.956342E+09 | 0.511867E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21375736.53 | 0.371501E+10 |
May | 0.103597E+10 | 0.536077E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67291404.14 | 0.209073E+10 |
June | 0.103308E+10 | 0.530488E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259966E+09 | 0.114747E+10 |
July | 0.959235E+09 | 0.498444E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228729E+09 | 0.556844E+09 |
August | 0.107774E+10 | 0.559349E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323820E+09 | 0.830379E+09 |
September | 0.956342E+09 | 0.519211E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168805E+09 | 0.189672E+10 |
October | 0.994195E+09 | 0.558152E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373853E+10 |
November | 0.984487E+09 | 0.604107E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518961E+10 |
December | 0.959235E+09 | 0.619735E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716872E+10 |
Annual Sum or Average | 0.119305E+11 | 0.666276E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106999E+10 | 0.480691E+11 |
Minimum of Months | 0.901968E+09 | 0.498444E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556844E+09 |
Maximum of Months | 0.107774E+10 | 0.619735E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323820E+09 | 0.895675E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.395478E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465472E+09 |
February | 0.570983E+09 | 0.334708E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349042E+09 |
March | 0.682256E+09 | 0.372963E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302910E+09 |
April | 0.605404E+09 | 0.323606E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1365277.77 | 0.195722E+09 |
May | 0.655811E+09 | 0.337598E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 574804.11 | 0.109303E+09 |
June | 0.653980E+09 | 0.333782E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7272858.32 | 64424263.12 |
July | 0.607235E+09 | 0.314450E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2415505.61 | 49918371.07 |
August | 0.682256E+09 | 0.352792E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2795134.80 | 68089282.30 |
September | 0.605404E+09 | 0.328042E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1790694.56 | 0.107355E+09 |
October | 0.629366E+09 | 0.358085E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202873E+09 |
November | 0.623221E+09 | 0.386254E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311421E+09 |
December | 0.607235E+09 | 0.400977E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399526E+09 |
Annual Sum or Average | 0.755252E+10 | 0.423874E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16214275.17 | 0.262606E+10 |
Minimum of Months | 0.570983E+09 | 0.314450E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49918371.07 |
Maximum of Months | 0.682256E+09 | 0.400977E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7272858.32 | 0.465472E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642015E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108700E+10 |
February | 0.901968E+09 | 0.539417E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812018E+09 |
March | 0.107774E+10 | 0.592168E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712471E+09 |
April | 0.956342E+09 | 0.512742E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4050394.51 | 0.454824E+09 |
May | 0.103597E+10 | 0.533474E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1334041.21 | 0.256703E+09 |
June | 0.103308E+10 | 0.527908E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17428158.03 | 0.150539E+09 |
July | 0.959235E+09 | 0.496726E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5994000.24 | 0.109125E+09 |
August | 0.107774E+10 | 0.557381E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6620917.28 | 0.148370E+09 |
September | 0.956342E+09 | 0.521303E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5157095.69 | 0.233716E+09 |
October | 0.994195E+09 | 0.570535E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445889E+09 |
November | 0.984487E+09 | 0.623685E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708201E+09 |
December | 0.959235E+09 | 0.656328E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924595E+09 |
Annual Sum or Average | 0.119305E+11 | 0.677368E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40584606.97 | 0.604346E+10 |
Minimum of Months | 0.901968E+09 | 0.496726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109125E+09 |
Maximum of Months | 0.107774E+10 | 0.656328E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17428158.03 | 0.108700E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.398673E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725766E+09 |
February | 0.421807E+09 | 0.337523E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544447E+09 |
March | 0.502994E+09 | 0.373966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483777E+09 |
April | 0.447140E+09 | 0.324567E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2289996.41 | 0.313421E+09 |
May | 0.484071E+09 | 0.340085E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 853234.85 | 0.176611E+09 |
June | 0.482240E+09 | 0.336131E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10944420.06 | 0.102769E+09 |
July | 0.448971E+09 | 0.315866E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3580949.18 | 75138381.86 |
August | 0.502994E+09 | 0.354445E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4092393.87 | 0.101360E+09 |
September | 0.447140E+09 | 0.330214E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2805872.30 | 0.161834E+09 |
October | 0.465148E+09 | 0.356916E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308583E+09 |
November | 0.460569E+09 | 0.389858E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475108E+09 |
December | 0.448971E+09 | 0.404490E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617665E+09 |
Annual Sum or Average | 0.557719E+10 | 0.426273E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24566866.67 | 0.408648E+10 |
Minimum of Months | 0.421807E+09 | 0.315866E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75138381.86 |
Maximum of Months | 0.502994E+09 | 0.404490E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10944420.06 | 0.725766E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.616005E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110957E+10 |
February | 0.901968E+09 | 0.523399E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838744E+09 |
March | 0.107774E+10 | 0.588084E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743408E+09 |
April | 0.956342E+09 | 0.512536E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3134703.73 | 0.475403E+09 |
May | 0.103597E+10 | 0.536635E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1333851.15 | 0.262907E+09 |
June | 0.103308E+10 | 0.530958E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16732640.66 | 0.151224E+09 |
July | 0.959235E+09 | 0.498826E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5563515.93 | 0.110826E+09 |
August | 0.107774E+10 | 0.559943E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6419321.65 | 0.153814E+09 |
September | 0.956342E+09 | 0.519788E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4120051.32 | 0.248319E+09 |
October | 0.994195E+09 | 0.558640E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480925E+09 |
November | 0.984487E+09 | 0.605017E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733364E+09 |
December | 0.959235E+09 | 0.621412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952398E+09 |
Annual Sum or Average | 0.119305E+11 | 0.667124E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37304084.43 | 0.626090E+10 |
Minimum of Months | 0.901968E+09 | 0.498826E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110826E+09 |
Maximum of Months | 0.107774E+10 | 0.621412E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16732640.66 | 0.110957E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.396449E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726807E+09 |
February | 0.570983E+09 | 0.335402E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546861E+09 |
March | 0.682256E+09 | 0.373338E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483330E+09 |
April | 0.605404E+09 | 0.324147E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1894396.75 | 0.316328E+09 |
May | 0.655811E+09 | 0.337859E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 889393.04 | 0.177630E+09 |
June | 0.653980E+09 | 0.334102E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10701311.04 | 0.103317E+09 |
July | 0.607235E+09 | 0.314619E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3653260.53 | 77598386.74 |
August | 0.682256E+09 | 0.353064E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4310530.76 | 0.104341E+09 |
September | 0.605404E+09 | 0.328486E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2776919.95 | 0.163355E+09 |
October | 0.629366E+09 | 0.358848E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305851E+09 |
November | 0.623221E+09 | 0.387128E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475815E+09 |
December | 0.607235E+09 | 0.402380E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618723E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424582E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24225812.06 | 0.409996E+10 |
Minimum of Months | 0.570983E+09 | 0.314619E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77598386.74 |
Maximum of Months | 0.682256E+09 | 0.402380E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10701311.04 | 0.726807E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145701E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110513E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982995E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5065893.44 | 0.632210E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235250.08 | 0.348737E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21959747.04 | 0.201489E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6016601.87 | 0.147245E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6201928.38 | 0.203407E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4758944.19 | 0.328179E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639036E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988385E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126329E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45238365.00 | 0.829711E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147245E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21959747.04 | 0.145701E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182521E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137503E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121852E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6232143.08 | 0.786819E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1581014.83 | 0.444571E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27929765.55 | 0.256378E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7712117.46 | 0.186974E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8121140.17 | 0.256604E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6735513.19 | 0.407293E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770927E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120467E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156310E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58311694.27 | 0.102961E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186974E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27929765.55 | 0.182521E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189909E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141400E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125138E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2721596.17 | 0.806008E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1182134.13 | 0.467071E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18322623.56 | 0.264670E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3798486.73 | 0.196981E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6420479.34 | 0.266584E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4436457.14 | 0.412705E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763441E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120961E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159817E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36881777.06 | 0.105497E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196981E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18322623.56 | 0.189909E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2528.45 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 861.30 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1769.38 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 713.39 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1342.33 | 20-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 582.71 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.56 | 15-APR-17:01 | 991.23 | 03-APR-00:10 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 31-MAY-13:00 | 701.07 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 558.23 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.50 | 11-JUN-15:25 | 579.54 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 558.93 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 | 02-JUL-15:25 | 266.12 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 534.75 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 | 04-AUG-16:40 | 350.36 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 582.95 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.93 | 17-SEP-14:30 | 523.71 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 999.89 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 723.36 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1936.81 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2965.33 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.12 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 256.50 | 2965.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1685.66 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 553.80 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1179.16 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 466.11 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 929.59 | 05-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 359.10 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.86 | 15-APR-17:01 | 660.63 | 03-APR-00:10 |
May | 827.22 | 01-MAY-09:09 | 341.17 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 31-MAY-13:00 | 472.19 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 342.18 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.22 | 11-JUN-15:23 | 387.68 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 342.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 | 02-JUL-15:25 | 183.15 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 04-AUG-16:40 | 239.56 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 359.51 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 06-SEP-16:00 | 349.51 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 579.16 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 484.71 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.63 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1976.89 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.15 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 174.22 | 1976.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2617.35 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 831.79 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1770.72 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 584.36 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1519.73 | 05-MAR-14:30 |
April | 1306.65 | 03-APR-09:09 | 581.52 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.32 | 15-APR-17:01 | 992.03 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.39 | 31-MAY-13:00 | 712.39 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 561.32 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.95 | 11-JUN-15:25 | 582.24 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 562.21 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 | 02-JUL-15:25 | 268.56 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 525.40 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 | 04-AUG-16:40 | 371.20 | 06-AUG-13:40 |
September | 1306.65 | 01-SEP-09:09 | 579.33 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 | 06-SEP-16:00 | 541.84 | 24-SEP-13:30 |
October | 1306.65 | 02-OCT-09:09 | 938.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 748.71 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1938.68 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2965.62 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.56 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 264.95 | 2965.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1685.63 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 512.03 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1178.81 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 446.22 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 905.29 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 433.72 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.55 | 15-APR-17:10 | 660.66 | 03-APR-00:10 |
May | 827.17 | 01-MAY-09:09 | 333.72 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 31-MAY-13:00 | 471.03 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 359.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.30 | 11-JUN-14:53 | 384.13 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 360.66 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.69 | 02-JUL-14:44 | 185.85 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 350.85 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.48 | 04-AUG-16:40 | 240.30 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 441.39 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 06-SEP-16:00 | 372.00 | 24-SEP-16:20 |
October | 827.17 | 02-OCT-09:09 | 634.82 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 486.58 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.49 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1976.84 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 333.72 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.85 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 170.30 | 1976.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1342.58 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 852.01 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 943.51 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 700.68 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 744.78 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 579.93 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.60 | 15-APR-17:01 | 562.08 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.98 | 31-MAY-13:00 | 373.25 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 554.27 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.11 | 18-JUN-15:51 | 328.48 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 555.00 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.75 | 02-JUL-16:00 | 138.35 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 529.71 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 | 04-AUG-16:40 | 193.82 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 580.19 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 | 17-SEP-14:50 | 300.73 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 998.04 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 447.76 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1035.25 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1586.26 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.35 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 161.60 | 1586.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 909.69 | 29-JAN-11:00 |
February | 827.22 | 01-FEB-10:09 | 549.03 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 629.11 | 10-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 460.16 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 506.17 | 05-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 356.93 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 15-APR-17:01 | 374.45 | 02-APR-23:55 |
May | 827.22 | 01-MAY-09:09 | 338.98 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 31-MAY-13:00 | 262.56 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 339.30 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 11-JUN-14:58 | 226.33 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 339.93 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.70 | 02-JUL-15:53 | 96.43 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 04-AUG-16:40 | 133.83 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 357.52 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 10-SEP-14:52 | 205.67 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 575.10 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 306.89 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 690.06 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1056.15 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.43 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 1056.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43441.51 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 823.41 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 50001.78 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 581.59 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27434.72 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 578.67 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.16 | 18-APR-12:00 | 22971.58 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.25 | 31-MAY-12:00 | 14646.18 | 02-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 557.54 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5792.74 | 26-JUN-16:10 | 11080.81 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 558.48 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4458.30 | 26-JUL-16:10 | 8246.64 | 24-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6557.06 | 04-AUG-16:05 | 11236.35 | 07-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 576.36 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5225.25 | 07-SEP-16:05 | 16432.93 | 29-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 933.42 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 19420.08 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 31531.32 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 35371.70 | 08-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8246.64 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6557.06 | 50001.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 895.02 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 506.99 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 628.97 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 437.07 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 505.85 | 12-MAR-16:00 |
April | 827.17 | 03-APR-09:09 | 426.88 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.61 | 15-APR-17:06 | 372.01 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 31-MAY-13:00 | 256.33 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 357.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.48 | 11-JUN-14:55 | 220.78 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 358.72 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 | 02-JUL-15:53 | 101.50 | 09-JUL-10:00 |
August | 827.17 | 01-AUG-09:09 | 348.56 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 04-AUG-16:40 | 138.30 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 434.76 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 06-SEP-16:00 | 205.52 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 633.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 306.78 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 690.06 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1055.04 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.50 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 93.48 | 1055.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2103.34 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 861.30 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1479.43 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 713.37 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1180.56 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 582.70 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.88 | 15-APR-17:01 | 874.60 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 31-MAY-13:00 | 618.55 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 558.22 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 11-JUN-15:14 | 519.85 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 558.92 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 | 02-JUL-16:00 | 226.97 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 534.74 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 04-AUG-16:40 | 306.05 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 582.95 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 17-SEP-14:50 | 460.73 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 999.89 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 674.26 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1618.12 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2466.84 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.97 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 2466.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1412.87 | 29-JAN-11:00 |
February | 805.43 | 01-FEB-08:09 | 553.80 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 985.92 | 10-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 466.10 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 834.40 | 05-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 359.09 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.61 | 15-APR-17:01 | 581.11 | 02-APR-23:55 |
May | 805.43 | 01-MAY-07:10 | 341.17 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 31-MAY-13:00 | 415.78 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 342.18 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.23 | 11-JUN-15:14 | 347.73 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 342.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 02-JUL-15:53 | 162.14 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 04-AUG-16:40 | 209.11 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 359.51 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 | 06-SEP-16:00 | 307.74 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 579.16 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 451.87 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1078.34 | 20-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.56 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.14 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 148.23 | 1644.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2269.57 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 831.77 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1480.38 | 10-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 584.35 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1329.64 | 05-MAR-13:55 |
April | 1306.65 | 03-APR-09:09 | 581.52 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.99 | 15-APR-17:10 | 879.19 | 02-APR-23:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 31-MAY-13:00 | 626.97 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 561.31 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.68 | 18-JUN-16:05 | 522.07 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 562.20 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.03 | 02-JUL-15:53 | 233.16 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 525.39 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.72 | 04-AUG-16:40 | 311.61 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 579.33 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.81 | 06-SEP-16:00 | 464.41 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 938.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 694.96 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1619.99 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2466.77 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.16 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 214.68 | 2466.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1402.24 | 29-JAN-11:00 |
February | 827.17 | 01-FEB-10:09 | 512.02 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 985.71 | 10-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 446.23 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 798.91 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 433.70 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.39 | 15-APR-17:10 | 579.46 | 02-APR-23:55 |
May | 827.17 | 01-MAY-09:09 | 333.71 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 | 31-MAY-13:00 | 415.12 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 359.34 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.31 | 11-JUN-14:53 | 344.72 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 360.65 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 02-JUL-15:53 | 158.37 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 350.85 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 04-AUG-16:40 | 209.74 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 441.37 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.20 | 06-SEP-16:00 | 315.32 | 24-SEP-16:10 |
October | 827.17 | 02-OCT-09:09 | 634.82 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 452.96 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1078.33 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.52 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 333.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.37 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 142.31 | 1644.52 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2829.42 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1951.79 | 04-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1639.90 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.19 | 15-APR-17:01 | 1275.90 | 02-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 | 31-MAY-13:00 | 857.33 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.95 | 18-JUN-15:51 | 727.31 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.43 | 02-JUL-15:00 | 296.68 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.69 | 04-AUG-16:40 | 404.05 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.19 | 17-SEP-15:00 | 637.02 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 989.73 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2091.00 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3430.28 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.95 | 3430.28 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3525.21 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2470.95 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2044.01 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.51 | 15-APR-17:01 | 1525.30 | 02-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.98 | 31-MAY-13:00 | 1086.90 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.23 | 11-JUN-15:00 | 915.59 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 | 02-JUL-15:00 | 372.79 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 | 04-AUG-16:40 | 508.70 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.45 | 17-SEP-15:00 | 806.81 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1198.35 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2577.93 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4285.12 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.79 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.23 | 4285.12 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3696.96 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2557.40 | 10-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2083.60 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.49 | 15-APR-17:01 | 1491.28 | 02-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | 31-MAY-13:00 | 1062.56 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.09 | 11-JUN-15:00 | 879.09 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.69 | 25-JUL-16:00 | 399.01 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.29 | 03-AUG-16:00 | 530.31 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | 06-SEP-16:00 | 786.12 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1085.37 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2784.66 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4324.58 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 399.01 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.09 | 4324.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9343.94 | 19-JAN-11:50 | 6035.01 | 4936.01 | 13987.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10537.27 | 24-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15627.72 | 24-MAR-16:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37800.83 | 17-APR-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39405.27 | 30-MAY-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39282.62 | 19-JUN-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39417.00 | 10-JUL-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39230.08 | 21-AUG-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39342.58 | 12-SEP-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37057.84 | 23-OCT-05:01 | 5082.11 | 1693.87 | 59282.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30178.00 | 06-NOV-07:02 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10445.92 | 07-DEC-16:10 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9343.94 | 2541.06 | 1693.87 | 13987.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39417.00 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.46 |
February | 421.30 | 24-FEB-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 |
March | 2364.50 | 24-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.63 |
April | 8487.62 | 18-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 | 0.00 |
May | 9526.15 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 | 0.00 |
June | 10854.93 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 | 0.00 |
July | 10438.78 | 05-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 0.00 |
August | 10721.94 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.95 | 0.00 |
September | 9633.87 | 07-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 0.00 |
October | 4179.78 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 |
November | 2127.28 | 03-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.26 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10854.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.95 | 814.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3362.26 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 807.86 |
February | 2884.77 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.39 |
March | 2342.37 | 21-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.28 |
April | 3888.54 | 17-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
May | 4284.80 | 30-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 0.00 |
June | 6012.47 | 26-JUN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 0.00 |
July | 6290.05 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
August | 4657.14 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 | 0.00 |
September | 4498.86 | 11-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 0.00 |
October | 2343.65 | 26-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.43 |
November | 2417.02 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.23 |
December | 2838.22 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3375.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2342.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6290.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 | 3375.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3088.80 | 07-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.70 |
February | 4290.83 | 02-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.32 |
March | 3141.68 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.00 |
April | 3735.49 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 | 0.00 |
May | 4359.46 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 0.00 |
June | 6076.47 | 26-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 0.00 |
July | 6335.12 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
August | 4884.19 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 0.00 |
September | 5491.33 | 05-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.43 |
October | 2369.56 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.99 |
November | 2142.30 | 28-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.52 |
December | 2817.83 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2142.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6335.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 | 675.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6721.44 | 05-JAN-17:01 | 19057.92 | 27422.23 | 37824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6125.03 | 04-FEB-17:01 | 2223.42 | 1919.51 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8912.85 | 24-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27603.91 | 17-APR-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30690.17 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33403.06 | 26-JUN-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31221.02 | 31-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30876.39 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30627.43 | 18-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10561.92 | 20-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10242.67 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6456.00 | 08-DEC-17:01 | 19057.92 | 27422.23 | 37824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6125.03 | 2223.42 | 1919.51 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33403.06 | 19057.92 | 27422.23 | 37824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7163.29 | 07-JAN-17:03 | 2223.42 | 1919.51 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7051.66 | 04-FEB-17:03 | 2223.42 | 1919.51 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8584.11 | 24-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18077.20 | 17-APR-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24257.66 | 30-MAY-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31614.11 | 27-JUN-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31173.39 | 05-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31167.67 | 28-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31903.81 | 11-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10050.55 | 20-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9156.11 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6909.69 | 09-DEC-17:03 | 2223.42 | 1919.51 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6909.69 | 2223.42 | 1919.51 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31903.81 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1407.48 | 07-JAN-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 |
February | 1411.94 | 04-FEB-17:01 | 468.72 | 355.68 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.10 |
March | 1317.50 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.55 |
April | 5683.24 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 | 0.00 |
May | 6128.73 | 31-MAY-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 0.00 |
June | 11150.25 | 25-JUN-18:32 | 0.00 | 165.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 99.41 | 0.00 |
July | 9624.82 | 02-JUL-16:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 0.00 |
August | 6741.31 | 04-AUG-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 42.76 | 0.00 |
September | 6124.00 | 11-SEP-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 0.00 |
October | 1802.04 | 20-OCT-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
November | 1438.56 | 25-NOV-17:01 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.88 |
December | 1260.09 | 09-DEC-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1260.09 | 0.00 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11150.25 | 1306.65 | 496.34 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 99.41 | 543.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 885.30 | 07-JAN-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.75 |
February | 967.82 | 24-FEB-10:05 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.90 |
March | 3026.59 | 28-MAR-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.07 |
April | 7945.89 | 18-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
May | 10343.96 | 14-MAY-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.85 |
June | 14501.70 | 25-JUN-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.12 |
July | 14533.14 | 02-JUL-09:22 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 |
August | 8825.15 | 27-AUG-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 |
September | 14197.10 | 03-SEP-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.24 |
October | 3287.79 | 20-OCT-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.26 |
November | 1197.25 | 03-NOV-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
December | 833.84 | 09-DEC-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 833.84 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14533.14 | 1654.44 | 628.45 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 366.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4948.06 | 12-JAN-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.17 |
February | 8276.89 | 24-FEB-13:45 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 |
March | 8967.39 | 24-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.36 |
April | 16925.15 | 16-APR-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 0.00 |
May | 11901.49 | 14-MAY-15:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.93 |
June | 16165.86 | 11-JUN-15:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 239.80 | 0.00 |
July | 16921.79 | 30-JUL-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
August | 12939.74 | 27-AUG-15:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 | 0.00 |
September | 18831.58 | 04-SEP-13:31 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
October | 16931.47 | 01-OCT-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.68 |
November | 10674.45 | 03-NOV-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.77 |
December | 6131.63 | 01-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4948.06 | 267.84 | 110.30 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18831.58 | 2544.47 | 992.69 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 239.80 | 260.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 986.49 | 31-JAN-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.70 |
February | 2946.52 | 24-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 |
March | 3498.84 | 23-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 |
April | 15454.10 | 16-APR-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 34.86 | 0.00 |
May | 16903.16 | 14-MAY-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 |
June | 16198.00 | 25-JUN-17:11 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 0.00 |
July | 16132.67 | 02-JUL-16:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 |
August | 14726.08 | 05-AUG-17:04 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
September | 16641.97 | 04-SEP-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 |
October | 5776.54 | 20-OCT-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
November | 3863.81 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 |
December | 835.70 | 09-DEC-17:03 | 296.72 | 256.16 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 835.70 | 0.00 | 104.73 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16903.16 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 366.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1169.64 | 07-JAN-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.83 |
February | 1027.97 | 04-FEB-17:03 | 468.72 | 353.06 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.54 |
March | 1109.20 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.20 |
April | 3236.37 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
May | 4018.73 | 31-MAY-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
June | 5974.63 | 30-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
July | 7077.35 | 05-JUL-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
August | 5568.25 | 04-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
September | 6054.01 | 11-SEP-06:03 | 1071.35 | 754.64 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
October | 1613.11 | 02-OCT-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.89 |
November | 1277.47 | 03-NOV-15:10 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 |
December | 1127.08 | 09-DEC-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1027.97 | 468.72 | 353.06 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7077.35 | 1272.23 | 754.64 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 292.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 788.18 | 07-JAN-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.04 |
February | 759.53 | 04-FEB-17:03 | 296.74 | 225.36 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.66 |
March | 1503.27 | 28-MAR-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.05 |
April | 5466.11 | 18-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
May | 6297.69 | 31-MAY-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
June | 11318.18 | 25-JUN-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
July | 12322.22 | 02-JUL-09:11 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 |
August | 11373.23 | 20-AUG-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.59 |
September | 11303.31 | 04-SEP-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 |
October | 2873.06 | 20-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
November | 1395.18 | 04-NOV-08:50 | 508.69 | 209.49 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 |
December | 736.23 | 09-DEC-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 736.23 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12322.22 | 827.22 | 314.23 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 196.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1275.25 | 07-JAN-17:03 | 468.72 | 404.65 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 |
February | 1974.46 | 24-FEB-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.80 |
March | 4210.48 | 24-MAR-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1184.57 |
April | 9638.58 | 18-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 2908.16 | 0.00 |
May | 10099.91 | 31-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.25 | 0.00 |
June | 11535.13 | 26-JUN-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 5792.74 | 0.00 |
July | 13780.87 | 30-JUL-13:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
August | 11494.66 | 04-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4780.83 | 0.00 |
September | 14560.69 | 04-SEP-13:31 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 |
October | 13359.34 | 01-OCT-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 |
November | 8361.52 | 05-NOV-14:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.76 |
December | 1303.79 | 02-DEC-12:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1275.25 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14560.69 | 1306.65 | 496.34 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5792.74 | 1749.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 783.70 | 07-JAN-17:03 | 296.72 | 256.16 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 |
February | 1673.67 | 24-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.68 |
March | 1760.64 | 23-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.77 |
April | 8898.54 | 15-APR-17:04 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 | 0.00 |
May | 12087.38 | 14-MAY-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
June | 12389.15 | 25-JUN-17:11 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 58.44 | 0.00 |
July | 12635.22 | 02-JUL-17:51 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 | 0.00 |
August | 11986.31 | 13-AUG-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 |
September | 12945.47 | 04-SEP-16:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.77 |
October | 5003.56 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.19 |
November | 3225.90 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 |
December | 754.00 | 01-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 754.00 | 0.00 | 122.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12945.47 | 805.38 | 314.21 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 58.44 | 67.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1251.86 | 07-JAN-17:01 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.30 |
February | 1228.01 | 04-FEB-17:01 | 468.72 | 355.68 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.14 |
March | 1317.70 | 28-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.72 |
April | 5279.76 | 18-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.04 | 0.00 |
May | 7415.42 | 30-MAY-06:02 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 |
June | 9682.36 | 25-JUN-18:21 | 0.00 | 220.59 | 3088.82 | 0.00 | 0.00 | 0.00 | 0.00 | 78.41 | 0.00 |
July | 9541.94 | 02-JUL-19:12 | 0.00 | 186.98 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
August | 6269.07 | 04-AUG-07:25 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
September | 7464.23 | 11-SEP-06:03 | 1071.35 | 759.27 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 |
October | 2146.44 | 02-OCT-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 |
November | 1532.54 | 03-NOV-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 |
December | 1072.35 | 09-DEC-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1072.35 | 0.00 | 186.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9682.36 | 2613.31 | 992.69 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 78.41 | 459.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 794.53 | 07-JAN-17:01 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.23 |
February | 2242.13 | 24-FEB-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 |
March | 5150.79 | 24-MAR-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.68 |
April | 8391.18 | 18-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 0.00 |
May | 11970.74 | 21-MAY-08:62 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 |
June | 15487.23 | 25-JUN-08:21 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 |
July | 15706.49 | 02-JUL-08:31 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.42 |
August | 14269.24 | 27-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
September | 11558.91 | 04-SEP-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 |
October | 5444.21 | 23-OCT-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 |
November | 3776.43 | 01-NOV-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.32 |
December | 690.99 | 09-DEC-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 690.99 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15706.49 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 307.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5679.52 | 12-JAN-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.93 |
February | 8511.93 | 24-FEB-13:35 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 |
March | 9089.54 | 24-MAR-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.47 |
April | 16289.56 | 16-APR-13:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 |
May | 11265.69 | 29-MAY-12:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 |
June | 15480.87 | 25-JUN-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 0.00 |
July | 16093.83 | 30-JUL-13:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 |
August | 15952.81 | 13-AUG-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.29 |
September | 15829.59 | 04-SEP-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 |
October | 15635.73 | 01-OCT-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.18 |
November | 10934.10 | 03-NOV-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.12 |
December | 6706.28 | 01-DEC-13:14 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5679.52 | 200.88 | 82.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16289.56 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 111.78 | 232.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 896.69 | 31-JAN-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.59 |
February | 3008.41 | 24-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
March | 3805.45 | 21-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.72 |
April | 14776.77 | 16-APR-17:52 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
May | 14139.84 | 14-MAY-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 |
June | 15912.26 | 25-JUN-17:41 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 0.00 |
July | 15053.57 | 02-JUL-16:32 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 0.00 |
August | 15422.84 | 13-AUG-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 |
September | 13862.56 | 04-SEP-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 |
October | 5830.36 | 11-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 |
November | 4046.65 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 |
December | 819.18 | 01-DEC-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 819.18 | 0.00 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15912.26 | 805.38 | 314.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 33.42 | 146.59 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.101348E+12 | 82940.38 | 18-JAN-16:00 | 0.257172E+12 | 329167.05 | 30-JAN-07:40 |
February | 0.897658E+11 | 75755.08 | 06-FEB-08:09 | 0.169334E+12 | 338062.50 | 02-FEB-07:00 |
March | 0.101125E+12 | 76474.83 | 23-MAR-15:00 | 0.983882E+11 | 268578.78 | 06-MAR-07:19 |
April | 0.974100E+11 | 137719.46 | 18-APR-15:09 | 0.386126E+11 | 226196.03 | 03-APR-06:10 |
May | 0.110291E+12 | 139846.98 | 30-MAY-15:30 | 0.264933E+10 | 86683.21 | 02-MAY-06:10 |
June | 0.133271E+12 | 165329.75 | 26-JUN-07:49 | 0.565624E+09 | 37378.41 | 05-JUN-06:10 |
July | 0.142918E+12 | 167392.95 | 05-JUL-10:50 | 6920452.90 | 1995.68 | 12-JUL-06:10 |
August | 0.147202E+12 | 172252.15 | 04-AUG-07:19 | 56376709.54 | 11871.52 | 16-AUG-06:10 |
September | 0.113449E+12 | 145200.74 | 11-SEP-09:50 | 0.385637E+10 | 92377.88 | 29-SEP-06:10 |
October | 0.977132E+11 | 97561.59 | 20-OCT-15:20 | 0.211274E+11 | 120928.42 | 16-OCT-06:10 |
November | 0.962004E+11 | 82437.08 | 27-NOV-16:00 | 0.956374E+11 | 284871.07 | 28-NOV-07:30 |
December | 0.986903E+11 | 83210.92 | 11-DEC-16:00 | 0.192572E+12 | 309223.14 | 11-DEC-07:19 |
Annual Sum or Average | 0.132938E+13 | 0.879979E+12 | ||||
Minimum of Months | 0.897658E+11 | 75755.08 | 6920452.90 | 1995.68 | ||
Maximum of Months | 0.147202E+12 | 172252.15 | 0.257172E+12 | 338062.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.200662E+11 | 0.602207E+10 | 0.605851E+11 | 0.225729E+10 | 0.566217E+10 | 0.123585E+10 | 0.00 | 356866.04 | 0.00 | 0.00 | 0.00 | 0.551923E+10 | 0.00 |
February | 0.178241E+11 | 0.477907E+10 | 0.548702E+11 | 0.204818E+10 | 0.432223E+10 | 0.817475E+09 | 0.00 | 1429018.12 | 0.00 | 0.00 | 0.00 | 0.510312E+10 | 0.00 |
March | 0.207957E+11 | 0.441157E+10 | 0.627783E+11 | 0.235484E+10 | 0.418138E+10 | 0.520461E+09 | 0.00 | 0.123179E+09 | 0.00 | 0.00 | 0.00 | 0.595944E+10 | 0.00 |
April | 0.184126E+11 | 0.348415E+10 | 0.586172E+11 | 0.219172E+10 | 0.520796E+10 | 0.202832E+09 | 0.00 | 0.411358E+10 | 0.00 | 0.00 | 0.00 | 0.517986E+10 | 0.00 |
May | 0.197068E+11 | 0.302042E+10 | 0.616817E+11 | 0.230556E+10 | 0.788544E+10 | 29114941.45 | 0.00 | 0.104251E+11 | 0.00 | 0.00 | 0.00 | 0.523721E+10 | 0.00 |
June | 0.195872E+11 | 0.270375E+10 | 0.604966E+11 | 0.226781E+10 | 0.137653E+11 | 16493158.32 | 0.00 | 0.295675E+11 | 0.00 | 0.00 | 0.00 | 0.486625E+10 | 0.00 |
July | 0.183333E+11 | 0.287876E+10 | 0.597911E+11 | 0.222859E+10 | 0.154019E+11 | 12300727.08 | 0.00 | 0.399101E+11 | 0.00 | 0.00 | 0.00 | 0.436206E+10 | 0.00 |
August | 0.204886E+11 | 0.333052E+10 | 0.627783E+11 | 0.235449E+10 | 0.155216E+11 | 13032797.29 | 0.00 | 0.380321E+11 | 0.00 | 0.00 | 0.00 | 0.468288E+10 | 0.00 |
September | 0.184905E+11 | 0.388110E+10 | 0.585950E+11 | 0.219054E+10 | 0.970146E+10 | 32749284.92 | 0.00 | 0.162722E+11 | 0.00 | 0.00 | 0.00 | 0.428534E+10 | 0.00 |
October | 0.194442E+11 | 0.491326E+10 | 0.605962E+11 | 0.225783E+10 | 0.450187E+10 | 0.115219E+09 | 0.00 | 0.124940E+10 | 0.00 | 0.00 | 0.00 | 0.463517E+10 | 0.00 |
November | 0.197669E+11 | 0.558954E+10 | 0.591197E+11 | 0.219998E+10 | 0.409215E+10 | 0.504692E+09 | 0.00 | 72660847.08 | 0.00 | 0.00 | 0.00 | 0.485470E+10 | 0.00 |
December | 0.197018E+11 | 0.625066E+10 | 0.597800E+11 | 0.222860E+10 | 0.460413E+10 | 0.100021E+10 | 0.00 | 191472.61 | 0.00 | 0.00 | 0.00 | 0.512473E+10 | 0.00 |
Annual Sum or Average | 0.232618E+12 | 0.512649E+11 | 0.719689E+12 | 0.268854E+11 | 0.948476E+11 | 0.450043E+10 | 0.00 | 0.139768E+12 | 0.00 | 0.00 | 0.00 | 0.598100E+11 | 0.00 |
Minimum of Months | 0.178241E+11 | 0.270375E+10 | 0.548702E+11 | 0.204818E+10 | 0.409215E+10 | 12300727.08 | 0.00 | 191472.61 | 0.00 | 0.00 | 0.00 | 0.428534E+10 | 0.00 |
Maximum of Months | 0.207957E+11 | 0.625066E+10 | 0.627783E+11 | 0.235484E+10 | 0.155216E+11 | 0.123585E+10 | 0.00 | 0.399101E+11 | 0.00 | 0.00 | 0.00 | 0.595944E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.257172E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.169334E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.983882E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.264933E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.565624E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6920452.90 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 56376709.54 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.385637E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.211274E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.956374E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.192572E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.879979E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 6920452.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257172E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 03-JAN-12:20 | 8247.25 | 02-JAN-07:10 | 1072.99 | 30-JAN-07:40 | 0.00 | 01-JAN-00:10 |
February | 23035.24 | 14-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-17:19 | 8247.25 | 06-FEB-07:10 | 1063.80 | 02-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 21170.50 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 02-MAR-13:20 | 6986.88 | 06-MAR-07:10 | 933.12 | 06-MAR-07:40 | 0.00 | 01-MAR-00:10 |
April | 20664.51 | 10-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-12:20 | 23833.62 | 18-APR-15:09 | 887.29 | 03-APR-06:40 | 0.00 | 01-APR-00:10 |
May | 19750.06 | 24-MAY-15:00 | 3328.83 | 01-MAY-19:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 25980.82 | 30-MAY-15:20 | 391.73 | 02-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 20258.61 | 13-JUN-07:10 | 3328.83 | 01-JUN-19:40 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-16:10 | 30386.42 | 26-JUN-10:50 | 183.54 | 02-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 20264.44 | 20-JUL-07:10 | 3328.83 | 01-JUL-19:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 06-JUL-07:10 | 31317.51 | 05-JUL-14:39 | 19.53 | 12-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 19947.32 | 31-AUG-07:10 | 5686.19 | 08-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 04-AUG-07:49 | 32937.52 | 04-AUG-07:19 | 78.88 | 16-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 20673.01 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-07:10 | 25090.34 | 07-SEP-15:00 | 459.24 | 29-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 24253.07 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-11:09 | 10455.85 | 20-OCT-15:39 | 643.15 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 06-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 7631.36 | 03-NOV-14:50 | 997.27 | 28-NOV-07:00 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-08:20 | 7661.58 | 11-DEC-07:10 | 1036.02 | 11-DEC-07:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19750.06 | 3328.83 | 41699.26 | 1410.29 | 6986.88 | 19.53 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 32937.52 | 1072.99 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 132.22 | 23-JAN-06:49 | 0.00 | 0.00 | 0.00 | 7487.96 | 31-JAN-12:20 | 0.00 |
February | 325.82 | 24-FEB-15:09 | 0.00 | 0.00 | 0.00 | 7586.17 | 17-FEB-12:30 | 0.00 |
March | 5572.13 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 7590.58 | 01-MAR-12:50 | 0.00 |
April | 46557.81 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 7211.19 | 03-APR-11:00 | 0.00 |
May | 48067.08 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6951.93 | 01-MAY-11:00 | 0.00 |
June | 71598.23 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 6526.50 | 02-JUN-11:39 | 0.00 |
July | 69973.29 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 6165.00 | 06-JUL-11:00 | 0.00 |
August | 75245.03 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 5807.06 | 01-AUG-11:30 | 0.00 |
September | 58842.17 | 06-SEP-14:09 | 0.00 | 0.00 | 0.00 | 5839.87 | 29-SEP-11:00 | 0.00 |
October | 20646.15 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6263.90 | 31-OCT-11:20 | 0.00 |
November | 4081.62 | 03-NOV-13:39 | 0.00 | 0.00 | 0.00 | 6719.41 | 30-NOV-12:39 | 0.00 |
December | 60.37 | 20-DEC-05:30 | 0.00 | 0.00 | 0.00 | 7176.75 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 60.37 | 0.00 | 0.00 | 0.00 | 5807.06 | 0.00 | ||
Maximum of Months | 75245.03 | 0.00 | 0.00 | 0.00 | 7590.58 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 82940.38 | 18-JAN-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2722.20 | 855.59 | 0.00 | 0.00 | 0.00 |
February | 75755.08 | 06-FEB-08:09 | 20268.05 | 41699.26 | 0.00 | 1410.29 | 7075.92 | 955.64 | 0.00 | 0.00 | 0.00 |
March | 76474.83 | 23-MAR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 4142.12 | 6.85 | 0.00 | 4115.18 | 0.00 |
April | 137719.46 | 18-APR-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 23833.62 | 6.91 | 0.00 | 45744.07 | 0.00 |
May | 139846.98 | 30-MAY-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 25954.12 | 6.91 | 0.00 | 46133.81 | 0.00 |
June | 165329.75 | 26-JUN-07:49 | 19671.42 | 41699.26 | 0.00 | 1410.29 | 27148.80 | 6.85 | 0.00 | 71598.23 | 0.00 |
July | 167392.95 | 05-JUL-10:50 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 29872.95 | 6.85 | 0.00 | 69973.29 | 0.00 |
August | 172252.15 | 04-AUG-07:19 | 19671.42 | 41699.26 | 0.00 | 1410.29 | 32937.52 | 6.85 | 0.00 | 72984.07 | 0.00 |
September | 145200.74 | 11-SEP-09:50 | 19671.42 | 38918.51 | 0.00 | 1410.29 | 23964.98 | 6.85 | 0.00 | 57048.86 | 0.00 |
October | 97561.59 | 20-OCT-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 10343.98 | 6.85 | 0.00 | 19726.08 | 0.00 |
November | 82437.08 | 27-NOV-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2535.67 | 780.82 | 0.00 | 0.00 | 0.00 |
December | 83210.92 | 11-DEC-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 3155.52 | 900.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 75755.08 | 19671.42 | 38918.51 | 0.00 | 1410.29 | 2535.67 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 172252.15 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 32937.52 | 955.64 | 0.00 | 72984.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 329167.05 | 30-JAN-07:40 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 338062.50 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 268578.78 | 06-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 226196.03 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 86683.21 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 37378.41 | 05-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 1995.68 | 12-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 11871.52 | 16-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 92377.88 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 120928.42 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 284871.07 | 28-NOV-07:30 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 309223.14 | 11-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1995.68 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 338062.50 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 19.43 | 2.50 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.01 | 0.83 | 25.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.43 | 2.50 | 19.43 | 0.83 | 20.23 | 0.83 | 20.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.43 | 2.50 | 19.43 | 0.83 | 25.01 | 0.83 | 25.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 19.30 | 6.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 1.83 | 19.50 | 1.67 | 19.62 | 0.00 | 19.62 | 0.00 | 19.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.73 | 0.17 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.87 | 1.00 | 19.87 | 0.00 | 19.87 | 0.00 | 19.87 |
December | 2.50 | 19.62 | 2.33 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
Annual Sum or Average | 12.00 | 19.44 | 11.00 | 19.55 | 0.17 | 19.59 | 0.17 | 19.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 19.87 | 6.00 | 19.87 | 0.17 | 24.73 | 0.17 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 18.91 | 12.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 7.33 | 19.25 | 6.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 1.50 | 18.99 | 1.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
April | 0.17 | 19.18 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.50 | 19.02 | 3.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 6.50 | 18.95 | 5.50 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 33.67 | 19.01 | 28.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.67 | 19.25 | 12.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.33 | 17.18 | 79.33 | 17.70 | 0.00 | 17.70 | 0.00 | 17.70 |
February | 81.67 | 17.77 | 58.83 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
March | 12.33 | 16.84 | 5.33 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
April | 2.50 | 17.17 | 1.00 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.49 | 2.67 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 0.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25.83 | 16.80 | 14.00 | 17.34 | 0.00 | 17.34 | 0.00 | 17.34 |
December | 62.83 | 17.08 | 37.17 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
Annual Sum or Average | 312.50 | 17.27 | 195.67 | 17.79 | 6.00 | 17.90 | 3.50 | 17.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.33 | 17.77 | 79.33 | 18.23 | 4.33 | 27.49 | 2.67 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 75.83 | 16.06 | 31.33 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
February | 42.33 | 16.88 | 21.83 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
March | 7.50 | 15.92 | 1.17 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
April | 2.00 | 15.81 | 0.17 | 16.09 | 2.00 | 21.54 | 2.00 | 23.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.72 | 5.00 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.96 | 7.00 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.96 | 9.00 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.66 | 4.17 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 4.50 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.50 | 15.38 | 5.17 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
December | 36.50 | 15.76 | 12.83 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
Annual Sum or Average | 179.67 | 16.12 | 72.50 | 16.67 | 34.33 | 18.01 | 31.67 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.83 | 16.88 | 31.33 | 17.54 | 10.17 | 27.96 | 9.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.33 | 16.43 | 28.67 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
February | 34.17 | 16.82 | 16.33 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
March | 6.00 | 16.31 | 1.50 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
April | 1.33 | 15.97 | 0.17 | 16.34 | 2.17 | 23.19 | 1.83 | 24.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.47 | 2.67 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.84 | 4.33 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 5.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.67 | 5.50 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.99 | 5.83 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.67 | 27.55 |
November | 16.17 | 16.01 | 6.67 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
December | 33.00 | 16.26 | 12.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 159.00 | 16.42 | 65.67 | 17.02 | 30.67 | 18.31 | 27.50 | 19.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 | 0.00 | 16.48 |
Maximum of Months | 68.33 | 16.82 | 28.67 | 17.45 | 6.67 | 27.99 | 5.83 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 84.17 | 16.43 | 40.83 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
February | 53.33 | 17.42 | 33.67 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
March | 7.50 | 15.76 | 1.67 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
April | 1.50 | 15.08 | 0.00 | 15.08 | 3.00 | 23.77 | 1.67 | 24.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.95 | 3.33 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.35 | 4.00 | 28.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.39 | 5.50 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.00 | 3.67 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 3.67 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.17 | 15.21 | 4.67 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
December | 37.50 | 15.68 | 14.00 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
Annual Sum or Average | 199.17 | 16.43 | 94.83 | 16.99 | 36.83 | 18.24 | 21.83 | 18.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.17 | 17.42 | 40.83 | 18.01 | 11.00 | 28.39 | 5.50 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.83 | 18.76 | 89.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 83.50 | 18.39 | 69.33 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
March | 4.50 | 19.16 | 4.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
April | 0.33 | 18.25 | 0.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.70 | 0.50 | 24.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.00 | 19.24 | 4.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
December | 29.33 | 19.01 | 24.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 229.50 | 18.68 | 192.00 | 18.95 | 0.50 | 18.96 | 0.50 | 18.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.83 | 19.24 | 89.50 | 19.41 | 0.50 | 24.70 | 0.50 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.50 | 18.02 | 25.67 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
February | 36.17 | 18.37 | 26.50 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 0.67 | 18.31 | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
April | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.31 | 5.83 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.69 | 7.17 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.00 | 2.33 | 27.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.61 | 3.50 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.99 | 0.83 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
December | 9.00 | 17.57 | 4.83 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
Annual Sum or Average | 86.67 | 18.13 | 58.17 | 18.67 | 19.67 | 19.73 | 19.50 | 20.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.50 | 18.99 | 26.50 | 19.39 | 7.33 | 27.69 | 7.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.00 | 16.64 | 188.33 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
February | 121.17 | 16.56 | 115.67 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
March | 70.33 | 17.43 | 70.17 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
April | 35.17 | 18.26 | 35.17 | 18.26 | 0.83 | 18.37 | 0.83 | 18.48 |
May | 5.00 | 19.38 | 5.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
June | 0.17 | 20.43 | 0.17 | 20.43 | 2.00 | 26.43 | 2.00 | 26.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.57 | 3.00 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.82 | 3.83 | 26.82 |
September | 4.83 | 19.55 | 4.83 | 19.55 | 17.83 | 23.60 | 17.50 | 24.44 |
October | 15.50 | 19.09 | 15.50 | 19.09 | 1.83 | 19.56 | 1.83 | 19.98 |
November | 58.33 | 17.48 | 58.00 | 17.48 | 0.50 | 17.52 | 0.50 | 17.57 |
December | 117.67 | 16.84 | 116.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
Annual Sum or Average | 626.17 | 17.03 | 608.83 | 17.04 | 29.83 | 17.26 | 29.50 | 17.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 | 0.00 | 16.59 |
Maximum of Months | 198.00 | 20.43 | 188.33 | 20.43 | 17.83 | 27.57 | 17.50 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.17 | 18.41 | 34.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 43.33 | 18.72 | 35.83 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
March | 0.50 | 17.69 | 0.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
April | 0.17 | 17.13 | 0.00 | 17.13 | 1.33 | 26.61 | 0.83 | 27.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.51 | 1.50 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.97 | 3.00 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.90 | 5.00 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.65 | 2.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.78 | 2.83 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 18.55 | 0.67 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 10.17 | 17.61 | 5.83 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
Annual Sum or Average | 102.50 | 18.45 | 76.67 | 18.89 | 26.67 | 20.05 | 16.00 | 20.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.17 | 18.72 | 35.83 | 19.04 | 9.83 | 27.97 | 5.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.83 | 18.13 | 52.83 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 57.50 | 18.54 | 44.67 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 3.17 | 18.36 | 2.17 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 0.33 | 18.21 | 0.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.35 | 0.67 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.62 | 0.17 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.33 | 17.09 | 6.00 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
December | 26.50 | 17.47 | 17.50 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
Annual Sum or Average | 172.67 | 18.10 | 123.33 | 18.55 | 1.67 | 18.60 | 0.83 | 18.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.83 | 18.54 | 52.83 | 18.95 | 1.33 | 27.35 | 0.67 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 16.82 | 14.17 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
February | 25.67 | 17.66 | 14.33 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
March | 1.00 | 16.24 | 0.17 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
April | 0.17 | 17.05 | 0.00 | 17.05 | 1.50 | 26.41 | 1.50 | 26.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.76 | 5.33 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.59 | 7.50 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.95 | 8.50 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.59 | 3.67 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.91 | 3.50 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.67 | 15.65 | 1.67 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
December | 13.50 | 16.10 | 4.67 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
Annual Sum or Average | 79.00 | 16.86 | 35.00 | 17.52 | 31.00 | 19.71 | 30.00 | 21.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.00 | 17.66 | 14.33 | 18.38 | 8.83 | 27.95 | 8.50 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.67 | 17.45 | 15.17 | 18.07 | 0.00 | 18.07 | 0.00 | 18.07 |
February | 16.83 | 17.99 | 10.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
March | 0.50 | 17.61 | 0.17 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
April | 0.17 | 17.14 | 0.00 | 17.14 | 2.17 | 27.01 | 2.00 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.41 | 2.00 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.67 | 4.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.71 | 5.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.60 | 5.33 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.96 | 5.83 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.65 | 2.67 | 27.65 |
November | 6.00 | 16.43 | 2.17 | 17.01 | 0.50 | 17.61 | 0.50 | 18.15 |
December | 11.50 | 16.75 | 5.00 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Annual Sum or Average | 63.67 | 17.37 | 33.17 | 17.99 | 29.50 | 20.26 | 28.33 | 21.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 0.00 | 17.31 |
Maximum of Months | 28.67 | 17.99 | 15.17 | 18.56 | 6.00 | 27.96 | 5.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.00 | 17.36 | 23.67 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
February | 36.50 | 18.30 | 25.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 0.67 | 16.92 | 0.17 | 17.41 | 0.00 | 17.41 | 0.00 | 17.41 |
April | 0.17 | 17.02 | 0.00 | 17.02 | 2.67 | 27.42 | 1.67 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.96 | 2.67 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.29 | 3.67 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.24 | 5.33 | 28.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.90 | 3.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.93 | 3.67 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
November | 6.67 | 15.41 | 1.83 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
December | 15.33 | 16.06 | 5.83 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
Annual Sum or Average | 101.33 | 17.37 | 57.33 | 17.97 | 34.33 | 19.77 | 20.83 | 20.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 | 0.00 | 15.57 |
Maximum of Months | 42.00 | 18.30 | 25.83 | 18.83 | 10.67 | 28.29 | 5.33 | 28.33 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.62 | 227.17 | 21.38 | 227.17 | 21.24 |
February | 454.00 | 22.57 | 93.17 | 22.27 | 93.17 | 22.06 |
March | 465.50 | 23.50 | 3.50 | 23.50 | 2.00 | 23.49 |
April | 290.50 | 23.89 | 60.83 | 24.03 | 0.00 | 24.03 |
May | 28.67 | 24.02 | 313.67 | 24.57 | 0.00 | 24.57 |
June | 0.00 | 0.00 | 455.17 | 24.45 | 0.00 | 24.45 |
July | 0.00 | 0.00 | 493.33 | 24.53 | 0.00 | 24.53 |
August | 1.67 | 24.64 | 506.83 | 24.45 | 1.67 | 24.45 |
September | 24.17 | 24.03 | 279.00 | 24.68 | 0.00 | 24.68 |
October | 184.50 | 24.03 | 36.00 | 24.23 | 0.00 | 24.23 |
November | 356.17 | 23.35 | 49.17 | 23.31 | 24.33 | 23.20 |
December | 497.00 | 22.62 | 64.67 | 22.44 | 64.67 | 22.30 |
Annual Sum or Average | 2804.17 | 22.92 | 2582.50 | 23.43 | 413.00 | 23.25 |
Minimum of Months | 0.00 | 0.00 | 3.50 | 21.38 | 0.00 | 21.24 |
Maximum of Months | 502.00 | 24.64 | 506.83 | 24.68 | 227.17 | 24.68 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 443.00 | 20.54 | 443.00 | 20.51 |
February | 454.00 | 21.14 | 248.67 | 20.94 | 248.67 | 20.85 |
March | 510.50 | 22.19 | 93.33 | 21.97 | 93.33 | 21.82 |
April | 383.67 | 22.80 | 62.67 | 22.84 | 24.17 | 22.75 |
May | 112.00 | 23.70 | 215.50 | 24.06 | 0.00 | 24.06 |
June | 20.67 | 23.46 | 382.83 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 480.50 | 24.33 | 0.00 | 24.33 |
August | 0.83 | 24.16 | 485.83 | 24.28 | 0.83 | 24.28 |
September | 121.33 | 23.57 | 203.33 | 24.11 | 0.00 | 24.11 |
October | 447.67 | 23.31 | 1.17 | 23.31 | 0.00 | 23.31 |
November | 451.00 | 21.95 | 136.50 | 21.65 | 136.50 | 21.46 |
December | 497.00 | 20.98 | 323.67 | 20.81 | 323.67 | 20.73 |
Annual Sum or Average | 3500.67 | 21.94 | 3077.00 | 22.32 | 1270.17 | 22.04 |
Minimum of Months | 0.00 | 0.00 | 1.17 | 20.54 | 0.00 | 20.51 |
Maximum of Months | 510.50 | 24.16 | 485.83 | 24.33 | 443.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.16 | 475.33 | 20.12 | 475.33 | 20.11 |
February | 454.00 | 20.55 | 353.17 | 20.42 | 353.17 | 20.36 |
March | 514.00 | 21.55 | 227.00 | 21.26 | 227.00 | 21.11 |
April | 400.00 | 22.17 | 115.83 | 22.08 | 75.67 | 21.87 |
May | 166.50 | 23.37 | 183.50 | 23.80 | 0.00 | 23.80 |
June | 50.17 | 23.25 | 356.00 | 24.16 | 0.00 | 24.16 |
July | 3.83 | 23.49 | 461.50 | 24.30 | 0.00 | 24.30 |
August | 14.83 | 23.61 | 453.00 | 24.21 | 2.17 | 24.21 |
September | 189.17 | 23.13 | 172.83 | 23.70 | 0.67 | 23.69 |
October | 485.50 | 22.42 | 41.33 | 22.28 | 41.33 | 22.17 |
November | 480.17 | 21.19 | 250.33 | 20.86 | 250.33 | 20.70 |
December | 497.00 | 20.35 | 459.50 | 20.29 | 459.50 | 20.27 |
Annual Sum or Average | 3757.17 | 21.41 | 3549.33 | 21.77 | 1885.17 | 21.46 |
Minimum of Months | 3.83 | 20.16 | 41.33 | 20.12 | 0.00 | 20.11 |
Maximum of Months | 514.00 | 23.61 | 475.33 | 24.30 | 475.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.52 | 498.33 | 19.51 | 498.33 | 19.51 |
February | 454.00 | 19.73 | 438.17 | 19.71 | 438.17 | 19.70 |
March | 514.00 | 20.74 | 352.50 | 20.55 | 352.50 | 20.47 |
April | 421.00 | 21.34 | 200.50 | 21.20 | 166.50 | 20.99 |
May | 226.83 | 22.85 | 183.67 | 23.41 | 6.17 | 23.38 |
June | 99.17 | 23.64 | 361.83 | 24.19 | 26.33 | 24.28 |
July | 45.33 | 24.67 | 454.17 | 24.40 | 27.67 | 24.46 |
August | 62.33 | 23.55 | 407.83 | 24.12 | 24.17 | 24.13 |
September | 255.17 | 22.43 | 176.67 | 23.05 | 19.83 | 22.95 |
October | 493.00 | 21.35 | 169.67 | 21.07 | 169.67 | 20.90 |
November | 489.00 | 20.34 | 339.33 | 20.08 | 339.33 | 19.97 |
December | 497.00 | 19.72 | 497.00 | 19.72 | 497.00 | 19.72 |
Annual Sum or Average | 4058.83 | 20.82 | 4079.67 | 21.20 | 2565.67 | 20.91 |
Minimum of Months | 45.33 | 19.52 | 169.67 | 19.51 | 6.17 | 19.51 |
Maximum of Months | 514.00 | 24.67 | 498.33 | 24.40 | 498.33 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 486.67 | 19.67 | 486.67 | 19.66 |
February | 454.00 | 20.00 | 405.67 | 19.90 | 405.67 | 19.87 |
March | 501.00 | 21.10 | 273.83 | 20.78 | 273.83 | 20.63 |
April | 381.83 | 21.77 | 189.83 | 21.77 | 129.50 | 21.55 |
May | 157.17 | 23.51 | 259.50 | 24.12 | 23.67 | 24.25 |
June | 90.17 | 24.39 | 391.17 | 24.42 | 41.67 | 24.58 |
July | 71.33 | 25.99 | 473.83 | 24.71 | 63.83 | 24.88 |
August | 67.17 | 24.95 | 449.33 | 24.38 | 48.67 | 24.50 |
September | 211.17 | 22.98 | 223.33 | 23.70 | 33.33 | 23.76 |
October | 473.83 | 21.89 | 105.50 | 21.62 | 103.33 | 21.42 |
November | 485.00 | 20.52 | 322.50 | 20.24 | 322.50 | 20.12 |
December | 497.00 | 19.84 | 493.33 | 19.83 | 493.33 | 19.83 |
Annual Sum or Average | 3891.67 | 21.15 | 4074.50 | 21.56 | 2426.00 | 21.29 |
Minimum of Months | 67.17 | 19.69 | 105.50 | 19.67 | 23.67 | 19.66 |
Maximum of Months | 502.00 | 25.99 | 493.33 | 24.71 | 493.33 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.50 | 20.06 | 419.17 | 19.85 | 419.17 | 19.77 |
February | 437.67 | 20.49 | 332.67 | 20.24 | 326.67 | 20.11 |
March | 456.00 | 21.22 | 269.50 | 20.98 | 254.17 | 20.80 |
April | 349.00 | 21.54 | 208.67 | 21.69 | 132.00 | 21.44 |
May | 187.00 | 22.95 | 230.00 | 23.72 | 15.67 | 23.75 |
June | 107.33 | 23.71 | 354.67 | 24.22 | 30.67 | 24.33 |
July | 68.33 | 25.10 | 448.33 | 24.53 | 45.50 | 24.65 |
August | 81.33 | 24.49 | 432.50 | 24.34 | 45.67 | 24.44 |
September | 215.17 | 23.03 | 237.33 | 23.75 | 35.33 | 23.82 |
October | 380.33 | 21.90 | 152.50 | 21.99 | 90.00 | 21.78 |
November | 460.17 | 20.88 | 280.17 | 20.57 | 266.00 | 20.37 |
December | 482.17 | 20.32 | 406.33 | 20.11 | 404.50 | 20.03 |
Annual Sum or Average | 3719.00 | 21.33 | 3771.83 | 21.74 | 2065.33 | 21.45 |
Minimum of Months | 68.33 | 20.06 | 152.50 | 19.85 | 15.67 | 19.77 |
Maximum of Months | 494.50 | 25.10 | 448.33 | 24.53 | 419.17 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 488.00 | 19.67 | 488.00 | 19.66 |
February | 449.83 | 20.04 | 396.17 | 19.92 | 396.17 | 19.87 |
March | 487.83 | 20.95 | 310.83 | 20.70 | 308.67 | 20.59 |
April | 362.50 | 21.47 | 212.33 | 21.57 | 141.67 | 21.33 |
May | 201.33 | 23.12 | 235.33 | 23.76 | 24.50 | 23.84 |
June | 109.00 | 23.82 | 381.33 | 24.27 | 36.17 | 24.39 |
July | 70.83 | 25.37 | 459.50 | 24.60 | 51.00 | 24.74 |
August | 78.83 | 24.38 | 450.50 | 24.31 | 45.50 | 24.40 |
September | 236.50 | 22.77 | 218.67 | 23.47 | 35.50 | 23.49 |
October | 442.33 | 21.51 | 157.67 | 21.31 | 138.50 | 21.11 |
November | 480.00 | 20.48 | 322.33 | 20.22 | 319.00 | 20.09 |
December | 497.00 | 19.88 | 471.83 | 19.82 | 471.83 | 19.80 |
Annual Sum or Average | 3918.00 | 21.05 | 4104.50 | 21.48 | 2456.50 | 21.21 |
Minimum of Months | 70.83 | 19.70 | 157.67 | 19.67 | 24.50 | 19.66 |
Maximum of Months | 502.00 | 25.37 | 488.00 | 24.60 | 488.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.59 | 502.00 | 19.59 | 502.00 | 19.59 |
February | 454.00 | 19.88 | 449.00 | 19.88 | 449.00 | 19.87 |
March | 514.00 | 20.71 | 378.17 | 20.60 | 378.17 | 20.55 |
April | 460.00 | 21.26 | 217.33 | 21.09 | 200.33 | 20.95 |
May | 357.67 | 22.82 | 94.00 | 23.06 | 6.33 | 23.03 |
June | 89.33 | 23.08 | 309.17 | 23.98 | 4.00 | 23.98 |
July | 11.50 | 24.28 | 456.33 | 24.30 | 7.67 | 24.30 |
August | 28.00 | 23.87 | 439.83 | 24.18 | 10.83 | 24.19 |
September | 212.17 | 22.99 | 171.67 | 23.57 | 1.00 | 23.56 |
October | 492.67 | 22.16 | 28.83 | 22.08 | 28.83 | 22.01 |
November | 489.00 | 21.00 | 281.33 | 20.71 | 281.33 | 20.57 |
December | 497.00 | 20.03 | 497.00 | 20.03 | 497.00 | 20.03 |
Annual Sum or Average | 4107.33 | 21.05 | 3824.67 | 21.35 | 2366.50 | 21.06 |
Minimum of Months | 11.50 | 19.59 | 28.83 | 19.59 | 1.00 | 19.59 |
Maximum of Months | 514.00 | 24.28 | 502.00 | 24.30 | 502.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 490.33 | 19.83 | 490.33 | 19.83 |
February | 454.00 | 20.20 | 416.33 | 20.14 | 416.33 | 20.12 |
March | 514.00 | 21.16 | 285.33 | 20.90 | 285.33 | 20.78 |
April | 403.33 | 21.70 | 167.83 | 21.65 | 122.00 | 21.43 |
May | 190.67 | 23.24 | 199.17 | 23.94 | 6.33 | 23.97 |
June | 83.33 | 24.21 | 391.50 | 24.38 | 25.33 | 24.49 |
July | 40.67 | 26.65 | 487.50 | 24.68 | 40.67 | 24.82 |
August | 22.83 | 25.72 | 494.83 | 24.40 | 20.67 | 24.46 |
September | 149.83 | 23.54 | 235.33 | 24.20 | 13.50 | 24.30 |
October | 449.00 | 22.84 | 14.00 | 22.83 | 7.67 | 22.79 |
November | 484.33 | 21.24 | 254.33 | 20.90 | 254.33 | 20.74 |
December | 497.00 | 20.17 | 488.17 | 20.16 | 488.17 | 20.16 |
Annual Sum or Average | 3791.00 | 21.36 | 3924.67 | 21.78 | 2170.67 | 21.49 |
Minimum of Months | 22.83 | 19.85 | 14.00 | 19.83 | 6.33 | 19.83 |
Maximum of Months | 514.00 | 26.65 | 494.83 | 24.68 | 490.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 18.53 | 482.00 | 18.47 | 482.00 | 18.45 |
February | 451.50 | 19.49 | 372.67 | 19.27 | 372.67 | 19.19 |
March | 493.67 | 20.56 | 297.33 | 20.27 | 294.00 | 20.13 |
April | 411.83 | 21.20 | 205.50 | 21.16 | 160.17 | 20.95 |
May | 321.67 | 22.43 | 124.33 | 22.96 | 9.83 | 22.91 |
June | 164.33 | 22.94 | 311.00 | 23.83 | 45.33 | 23.87 |
July | 98.17 | 24.05 | 455.00 | 24.33 | 77.00 | 24.34 |
August | 94.33 | 23.84 | 470.00 | 24.25 | 67.67 | 24.28 |
September | 184.50 | 22.95 | 246.83 | 23.94 | 24.83 | 24.05 |
October | 365.33 | 22.33 | 74.50 | 22.55 | 18.50 | 22.44 |
November | 453.00 | 20.73 | 250.67 | 20.47 | 229.83 | 20.24 |
December | 492.33 | 19.56 | 418.00 | 19.39 | 414.83 | 19.31 |
Annual Sum or Average | 4032.67 | 20.83 | 3707.83 | 21.21 | 2196.67 | 20.87 |
Minimum of Months | 94.33 | 18.53 | 74.50 | 18.47 | 9.83 | 18.45 |
Maximum of Months | 502.00 | 24.05 | 482.00 | 24.33 | 482.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 492.00 | 19.81 | 492.00 | 19.80 |
February | 454.00 | 20.24 | 406.00 | 20.16 | 406.00 | 20.12 |
March | 511.83 | 21.08 | 311.00 | 20.85 | 311.00 | 20.74 |
April | 398.67 | 21.74 | 163.00 | 21.68 | 122.33 | 21.48 |
May | 239.00 | 23.02 | 171.17 | 23.59 | 8.83 | 23.60 |
June | 87.50 | 23.72 | 374.83 | 24.26 | 17.33 | 24.34 |
July | 35.67 | 26.35 | 484.67 | 24.64 | 33.50 | 24.76 |
August | 21.50 | 25.81 | 489.67 | 24.42 | 21.00 | 24.48 |
September | 162.00 | 23.40 | 240.83 | 24.09 | 15.83 | 24.17 |
October | 430.17 | 22.61 | 32.67 | 22.65 | 10.67 | 22.60 |
November | 476.83 | 21.21 | 251.67 | 20.88 | 249.50 | 20.70 |
December | 497.00 | 20.19 | 470.50 | 20.15 | 470.50 | 20.13 |
Annual Sum or Average | 3816.17 | 21.31 | 3888.00 | 21.73 | 2158.50 | 21.44 |
Minimum of Months | 21.50 | 19.83 | 32.67 | 19.81 | 8.83 | 19.80 |
Maximum of Months | 511.83 | 26.35 | 492.00 | 24.64 | 492.00 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 493.67 | 19.68 | 493.67 | 19.68 |
February | 454.00 | 20.04 | 412.83 | 19.99 | 412.83 | 19.98 |
March | 514.00 | 21.07 | 300.00 | 20.83 | 300.00 | 20.72 |
April | 409.50 | 21.73 | 137.50 | 21.68 | 97.00 | 21.47 |
May | 186.67 | 23.21 | 193.17 | 23.72 | 0.50 | 23.71 |
June | 58.00 | 23.80 | 389.00 | 24.28 | 12.50 | 24.33 |
July | 13.00 | 25.04 | 478.67 | 24.40 | 12.00 | 24.42 |
August | 30.00 | 24.01 | 452.33 | 24.23 | 14.00 | 24.24 |
September | 208.17 | 22.89 | 183.00 | 23.54 | 3.83 | 23.51 |
October | 483.33 | 22.03 | 60.17 | 21.88 | 57.33 | 21.75 |
November | 487.83 | 20.88 | 289.83 | 20.56 | 289.83 | 20.42 |
December | 497.00 | 19.98 | 497.00 | 19.98 | 497.00 | 19.98 |
Annual Sum or Average | 3843.50 | 21.08 | 3887.17 | 21.50 | 2190.50 | 21.19 |
Minimum of Months | 13.00 | 19.69 | 60.17 | 19.68 | 0.50 | 19.68 |
Maximum of Months | 514.00 | 25.04 | 497.00 | 24.40 | 497.00 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.64 | 413.33 | 19.61 | 413.33 | 19.60 |
February | 385.00 | 20.16 | 329.67 | 20.04 | 329.67 | 20.00 |
March | 419.33 | 21.33 | 208.50 | 21.00 | 208.50 | 20.84 |
April | 314.33 | 22.08 | 131.33 | 22.22 | 74.83 | 22.04 |
May | 119.50 | 23.95 | 223.17 | 24.39 | 22.50 | 24.55 |
June | 72.67 | 24.87 | 343.17 | 24.60 | 36.50 | 24.76 |
July | 52.67 | 26.59 | 415.00 | 24.85 | 52.67 | 25.03 |
August | 38.33 | 25.53 | 400.33 | 24.50 | 31.50 | 24.60 |
September | 161.67 | 23.39 | 190.83 | 24.08 | 19.33 | 24.19 |
October | 382.83 | 22.37 | 38.33 | 22.27 | 31.17 | 22.14 |
November | 409.50 | 20.90 | 244.00 | 20.57 | 243.50 | 20.42 |
December | 422.00 | 19.92 | 410.83 | 19.90 | 410.83 | 19.89 |
Annual Sum or Average | 3204.83 | 21.34 | 3348.50 | 21.78 | 1874.33 | 21.50 |
Minimum of Months | 38.33 | 19.64 | 38.33 | 19.61 | 19.33 | 19.60 |
Maximum of Months | 427.00 | 26.59 | 415.00 | 24.85 | 413.33 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 492.50 | 20.37 | 395.50 | 20.12 | 395.50 | 20.02 |
February | 430.50 | 20.87 | 295.50 | 20.60 | 288.17 | 20.46 |
March | 446.67 | 21.60 | 219.17 | 21.36 | 200.17 | 21.15 |
April | 336.67 | 22.01 | 161.33 | 22.24 | 79.83 | 22.04 |
May | 145.67 | 23.28 | 240.00 | 24.00 | 6.67 | 24.05 |
June | 73.83 | 24.21 | 374.83 | 24.36 | 23.17 | 24.47 |
July | 43.00 | 25.93 | 474.17 | 24.58 | 37.17 | 24.69 |
August | 50.83 | 25.27 | 470.83 | 24.43 | 36.00 | 24.53 |
September | 171.83 | 23.56 | 253.67 | 24.16 | 26.67 | 24.29 |
October | 346.67 | 22.57 | 102.50 | 22.83 | 29.17 | 22.75 |
November | 434.50 | 21.31 | 234.83 | 21.07 | 209.17 | 20.83 |
December | 472.17 | 20.61 | 385.67 | 20.41 | 381.83 | 20.31 |
Annual Sum or Average | 3444.83 | 21.63 | 3608.00 | 22.11 | 1713.50 | 21.81 |
Minimum of Months | 43.00 | 20.37 | 102.50 | 20.12 | 6.67 | 20.02 |
Maximum of Months | 492.50 | 25.93 | 474.17 | 24.58 | 395.50 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.86 | 479.00 | 19.81 | 479.00 | 19.79 |
February | 449.83 | 20.35 | 369.67 | 20.20 | 369.67 | 20.14 |
March | 485.33 | 21.30 | 254.67 | 21.02 | 252.33 | 20.87 |
April | 350.50 | 21.94 | 160.67 | 22.11 | 87.50 | 21.91 |
May | 159.00 | 23.50 | 247.17 | 24.04 | 15.67 | 24.14 |
June | 75.83 | 24.31 | 402.00 | 24.40 | 27.00 | 24.51 |
July | 45.33 | 26.17 | 480.83 | 24.65 | 41.83 | 24.77 |
August | 45.67 | 25.14 | 476.33 | 24.41 | 32.67 | 24.49 |
September | 189.83 | 23.25 | 231.17 | 23.93 | 20.83 | 24.01 |
October | 425.17 | 22.21 | 70.50 | 22.17 | 45.67 | 22.03 |
November | 473.33 | 21.00 | 270.67 | 20.69 | 265.67 | 20.52 |
December | 497.00 | 20.14 | 462.17 | 20.07 | 462.17 | 20.04 |
Annual Sum or Average | 3698.83 | 21.32 | 3904.83 | 21.79 | 2100.00 | 21.50 |
Minimum of Months | 45.33 | 19.86 | 70.50 | 19.81 | 15.67 | 19.79 |
Maximum of Months | 502.00 | 26.17 | 480.83 | 24.65 | 479.00 | 24.77 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62474 | 13.92552 | -0.4983 | 11.54651 |
February | 454.00000 | 22.57080 | 17.40482 | -0.2465 | 7.91603 |
March | 514.00000 | 23.60976 | 21.64527 | 0.05270 | 5.87173 |
April | 485.00000 | 24.10485 | 28.11751 | 0.25243 | 6.92316 |
May | 508.00000 | 24.41808 | 40.74379 | -0.3963 | 8.98581 |
June | 496.00000 | 24.41446 | 47.57685 | -0.3063 | 7.50372 |
July | 497.00000 | 24.52397 | 51.59059 | -0.2325 | 6.78204 |
August | 514.00000 | 24.44334 | 50.73102 | -0.2619 | 7.01716 |
September | 485.00000 | 24.45426 | 37.34017 | -0.3805 | 8.87607 |
October | 502.00000 | 24.32301 | 26.94801 | 0.31503 | 7.26977 |
November | 489.00000 | 23.62024 | 23.46093 | 0.08009 | 6.82159 |
December | 497.00000 | 22.61931 | 15.79731 | -0.2463 | 7.23350 |
Annual Sum or Average | 5943.00000 | 23.73513 | 31.40314 | -0.1557 | 7.72595 |
Minimum of Months | 454.00000 | 21.62474 | 13.92552 | -0.4983 | 5.87173 |
Maximum of Months | 514.00000 | 24.52397 | 51.59059 | 0.31503 | 11.54651 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60849 | 14.69510 | -0.7480 | 18.18171 |
February | 454.00000 | 21.14311 | 18.69371 | -0.5745 | 13.24856 |
March | 514.00000 | 22.20060 | 23.82776 | -0.2648 | 8.21272 |
April | 485.00000 | 23.08283 | 30.45362 | 0.02191 | 6.86451 |
May | 508.00000 | 24.04540 | 42.28142 | -0.5311 | 11.50511 |
June | 496.00000 | 24.21438 | 48.92151 | -0.3924 | 8.65019 |
July | 497.00000 | 24.31684 | 52.91684 | -0.3181 | 7.43202 |
August | 514.00000 | 24.26870 | 52.05543 | -0.3455 | 7.77439 |
September | 485.00000 | 24.10042 | 38.87429 | -0.5263 | 11.84594 |
October | 502.00000 | 23.39009 | 29.60963 | 0.08424 | 5.78216 |
November | 489.00000 | 22.11146 | 25.78449 | -0.2743 | 9.70722 |
December | 497.00000 | 20.98148 | 17.00343 | -0.6259 | 14.41760 |
Annual Sum or Average | 5943.00000 | 22.88516 | 33.05720 | -0.3735 | 10.27727 |
Minimum of Months | 454.00000 | 20.60849 | 14.69510 | -0.7480 | 5.78216 |
Maximum of Months | 514.00000 | 24.31684 | 52.91684 | 0.08424 | 18.18171 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16316 | 14.90653 | -0.8899 | 23.85980 |
February | 454.00000 | 20.54879 | 19.28647 | -0.7469 | 18.72429 |
March | 514.00000 | 21.55192 | 24.38633 | -0.4394 | 11.20041 |
April | 485.00000 | 22.51848 | 31.24735 | -0.1196 | 8.48523 |
May | 508.00000 | 23.85777 | 42.70342 | -0.5977 | 13.64719 |
June | 496.00000 | 24.12640 | 49.26682 | -0.4193 | 9.49382 |
July | 497.00000 | 24.27661 | 53.14121 | -0.3279 | 7.61236 |
August | 514.00000 | 24.18991 | 52.32817 | -0.3732 | 8.20466 |
September | 485.00000 | 23.78852 | 39.64459 | -0.6447 | 15.85404 |
October | 502.00000 | 22.46690 | 31.09003 | -0.1441 | 6.94186 |
November | 489.00000 | 21.24382 | 26.82092 | -0.5054 | 14.18885 |
December | 497.00000 | 20.34828 | 17.50901 | -0.8141 | 20.83751 |
Annual Sum or Average | 5943.00000 | 22.43865 | 33.65614 | -0.5002 | 13.20236 |
Minimum of Months | 454.00000 | 20.16316 | 14.90653 | -0.8899 | 6.94186 |
Maximum of Months | 514.00000 | 24.27661 | 53.14121 | -0.1196 | 23.85980 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.51634 | 14.93763 | -1.1440 | 34.57496 |
February | 454.00000 | 19.73219 | 20.14982 | -1.0102 | 29.14943 |
March | 514.00000 | 20.74334 | 26.18162 | -0.6623 | 16.83600 |
April | 485.00000 | 21.71237 | 33.11186 | -0.3153 | 12.15577 |
May | 508.00000 | 23.55716 | 43.77693 | -0.6863 | 17.78916 |
June | 496.00000 | 24.07114 | 50.10986 | -0.3995 | 10.62378 |
July | 497.00000 | 24.31042 | 53.96811 | -0.2781 | 7.64256 |
August | 514.00000 | 24.08807 | 53.41007 | -0.3777 | 8.91098 |
September | 485.00000 | 23.29065 | 41.65727 | -0.8018 | 23.04170 |
October | 502.00000 | 21.39663 | 33.62980 | -0.3985 | 10.62123 |
November | 489.00000 | 20.33797 | 28.68452 | -0.7574 | 21.56519 |
December | 497.00000 | 19.71741 | 18.20556 | -1.0525 | 30.48057 |
Annual Sum or Average | 5943.00000 | 21.89129 | 34.94737 | -0.6542 | 18.51353 |
Minimum of Months | 454.00000 | 19.51634 | 14.93763 | -1.1440 | 7.64256 |
Maximum of Months | 514.00000 | 24.31042 | 53.96811 | -0.2781 | 34.57496 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69170 | 15.85417 | -1.0797 | 31.91394 |
February | 454.00000 | 20.00298 | 20.92045 | -0.9175 | 25.82139 |
March | 514.00000 | 21.17057 | 26.42425 | -0.5328 | 14.69108 |
April | 485.00000 | 22.30062 | 32.54034 | -0.1491 | 11.64143 |
May | 508.00000 | 23.98696 | 42.54142 | -0.4803 | 13.28237 |
June | 496.00000 | 24.20892 | 49.50988 | -0.2706 | 9.65783 |
July | 497.00000 | 24.48190 | 53.17560 | -0.1290 | 7.44093 |
August | 514.00000 | 24.22903 | 52.66439 | -0.2538 | 7.80938 |
September | 485.00000 | 23.70009 | 40.56925 | -0.6008 | 18.37728 |
October | 502.00000 | 22.01345 | 33.39458 | -0.2395 | 8.83206 |
November | 489.00000 | 20.54641 | 29.37435 | -0.6958 | 19.74422 |
December | 497.00000 | 19.83647 | 18.94121 | -1.0076 | 28.63680 |
Annual Sum or Average | 5943.00000 | 22.19914 | 34.78118 | -0.5267 | 16.39323 |
Minimum of Months | 454.00000 | 19.69170 | 15.85417 | -1.0797 | 7.44093 |
Maximum of Months | 514.00000 | 24.48190 | 53.17560 | -0.1290 | 31.91394 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11856 | 15.11433 | -0.9189 | 27.52991 |
February | 454.00000 | 20.62061 | 19.41118 | -0.7282 | 21.43935 |
March | 514.00000 | 21.55923 | 24.56679 | -0.4275 | 13.70964 |
April | 485.00000 | 22.33142 | 31.38790 | -0.1339 | 12.19296 |
May | 508.00000 | 23.74849 | 42.88553 | -0.5847 | 16.10120 |
June | 496.00000 | 24.06993 | 49.91180 | -0.3681 | 10.73611 |
July | 497.00000 | 24.35304 | 53.62402 | -0.2193 | 7.87629 |
August | 514.00000 | 24.18635 | 52.65413 | -0.2780 | 8.45850 |
September | 485.00000 | 23.71507 | 39.97136 | -0.5702 | 18.34524 |
October | 502.00000 | 22.49166 | 30.64648 | -0.0980 | 9.39444 |
November | 489.00000 | 21.09757 | 27.62101 | -0.5413 | 17.42340 |
December | 497.00000 | 20.44256 | 17.47844 | -0.8254 | 24.22467 |
Annual Sum or Average | 5943.00000 | 22.40971 | 33.90074 | -0.4726 | 15.55674 |
Minimum of Months | 454.00000 | 20.11856 | 15.11433 | -0.9189 | 7.87629 |
Maximum of Months | 514.00000 | 24.35304 | 53.62402 | -0.0980 | 27.52991 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70006 | 15.55497 | -1.0825 | 32.20206 |
February | 454.00000 | 20.07566 | 20.55146 | -0.9060 | 25.91098 |
March | 514.00000 | 21.10773 | 26.28920 | -0.5562 | 15.30795 |
April | 485.00000 | 22.17494 | 32.44057 | -0.1710 | 12.40390 |
May | 508.00000 | 23.72590 | 43.46092 | -0.5793 | 16.36176 |
June | 496.00000 | 24.11961 | 50.00023 | -0.3130 | 10.55258 |
July | 497.00000 | 24.40859 | 53.64403 | -0.1642 | 7.91668 |
August | 514.00000 | 24.19325 | 53.02575 | -0.2637 | 8.28973 |
September | 485.00000 | 23.52131 | 41.32061 | -0.6678 | 20.76744 |
October | 502.00000 | 21.82864 | 33.06848 | -0.2782 | 10.11992 |
November | 489.00000 | 20.55695 | 29.22713 | -0.6939 | 20.12825 |
December | 497.00000 | 19.87774 | 18.83533 | -0.9999 | 28.63598 |
Annual Sum or Average | 5943.00000 | 22.12483 | 34.91064 | -0.5536 | 17.29459 |
Minimum of Months | 454.00000 | 19.70006 | 15.55497 | -1.0825 | 7.91668 |
Maximum of Months | 514.00000 | 24.40859 | 53.64403 | -0.1642 | 32.20206 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.59050 | 15.02307 | -1.1043 | 32.47819 |
February | 454.00000 | 19.88340 | 20.32605 | -0.9654 | 26.71017 |
March | 514.00000 | 20.70858 | 26.62141 | -0.6773 | 16.09002 |
April | 485.00000 | 21.40156 | 34.41619 | -0.4086 | 11.31490 |
May | 508.00000 | 23.18647 | 45.91568 | -0.8579 | 22.74543 |
June | 496.00000 | 23.98354 | 50.46324 | -0.4781 | 11.05484 |
July | 497.00000 | 24.26213 | 53.76609 | -0.3344 | 7.76782 |
August | 514.00000 | 24.15204 | 52.86030 | -0.3786 | 8.32509 |
September | 485.00000 | 23.66687 | 40.77094 | -0.6753 | 17.02394 |
October | 502.00000 | 22.19777 | 32.60205 | -0.1891 | 6.95995 |
November | 489.00000 | 20.99869 | 28.01775 | -0.5628 | 15.16655 |
December | 497.00000 | 20.03448 | 18.40897 | -0.9346 | 24.99258 |
Annual Sum or Average | 5943.00000 | 22.02249 | 35.06340 | -0.6284 | 16.65057 |
Minimum of Months | 454.00000 | 19.59050 | 15.02307 | -1.1043 | 6.95995 |
Maximum of Months | 514.00000 | 24.26213 | 53.76609 | -0.1891 | 32.47819 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85038 | 15.84360 | -1.0275 | 29.17036 |
February | 454.00000 | 20.19948 | 20.98122 | -0.8645 | 22.71048 |
March | 514.00000 | 21.15778 | 26.98086 | -0.5395 | 13.47654 |
April | 485.00000 | 22.15013 | 33.63402 | -0.2047 | 10.05416 |
May | 508.00000 | 23.93576 | 43.71524 | -0.5512 | 13.90716 |
June | 496.00000 | 24.22764 | 49.32665 | -0.3107 | 9.07109 |
July | 497.00000 | 24.50471 | 52.55933 | -0.1576 | 6.91890 |
August | 514.00000 | 24.31976 | 51.88252 | -0.2385 | 6.98100 |
September | 485.00000 | 24.09097 | 39.48005 | -0.4636 | 12.77909 |
October | 502.00000 | 22.98165 | 31.85748 | 0.00638 | 6.31985 |
November | 489.00000 | 21.26535 | 28.62348 | -0.4878 | 13.88987 |
December | 497.00000 | 20.17464 | 19.18966 | -0.8869 | 23.15993 |
Annual Sum or Average | 5943.00000 | 22.42223 | 34.62847 | -0.4747 | 13.96961 |
Minimum of Months | 454.00000 | 19.85038 | 15.84360 | -1.0275 | 6.31985 |
Maximum of Months | 514.00000 | 24.50471 | 52.55933 | 0.00638 | 29.17036 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 18.52828 | 13.48665 | -1.2048 | 37.22925 |
February | 454.00000 | 19.51124 | 17.94202 | -0.9188 | 26.22418 |
March | 514.00000 | 20.70331 | 23.50835 | -0.5918 | 16.23156 |
April | 485.00000 | 21.68372 | 31.20483 | -0.2833 | 11.94498 |
May | 508.00000 | 23.13312 | 44.70900 | -0.8105 | 22.34139 |
June | 496.00000 | 23.79666 | 51.20850 | -0.4874 | 12.82713 |
July | 497.00000 | 24.28347 | 54.98246 | -0.2655 | 7.76398 |
August | 514.00000 | 24.20203 | 53.43354 | -0.2712 | 7.88511 |
September | 485.00000 | 23.84369 | 38.85899 | -0.4979 | 15.72098 |
October | 502.00000 | 22.89813 | 28.71929 | 0.04592 | 7.58694 |
November | 489.00000 | 21.04823 | 25.36267 | -0.4771 | 15.64367 |
December | 497.00000 | 19.61984 | 16.04230 | -0.9264 | 26.84882 |
Annual Sum or Average | 5943.00000 | 21.95585 | 33.43015 | -0.5554 | 17.29454 |
Minimum of Months | 454.00000 | 18.52828 | 13.48665 | -1.2048 | 7.58694 |
Maximum of Months | 514.00000 | 24.28347 | 54.98246 | 0.04592 | 37.22925 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83050 | 15.63114 | -1.0361 | 29.63188 |
February | 454.00000 | 20.24474 | 20.85112 | -0.8557 | 22.81768 |
March | 514.00000 | 21.09402 | 26.93828 | -0.5618 | 14.02222 |
April | 485.00000 | 22.18425 | 33.23284 | -0.1899 | 10.13489 |
May | 508.00000 | 23.67112 | 44.65297 | -0.6536 | 16.80237 |
June | 496.00000 | 24.15438 | 49.74766 | -0.3480 | 9.70613 |
July | 497.00000 | 24.50063 | 52.74431 | -0.1674 | 6.95147 |
August | 514.00000 | 24.34121 | 51.96017 | -0.2294 | 6.92751 |
September | 485.00000 | 24.01255 | 39.91453 | -0.5003 | 13.80189 |
October | 502.00000 | 22.82632 | 31.63125 | -0.0254 | 6.63425 |
November | 489.00000 | 21.28344 | 28.47154 | -0.4831 | 14.11556 |
December | 497.00000 | 20.18994 | 19.14249 | -0.8837 | 23.25699 |
Annual Sum or Average | 5943.00000 | 22.37730 | 34.70154 | -0.4924 | 14.50585 |
Minimum of Months | 454.00000 | 19.83050 | 15.63114 | -1.0361 | 6.63425 |
Maximum of Months | 514.00000 | 24.50063 | 52.74431 | -0.0254 | 29.63188 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69393 | 15.35432 | -1.0541 | 30.57625 |
February | 454.00000 | 20.04420 | 20.15428 | -0.8941 | 24.00141 |
March | 514.00000 | 21.06956 | 25.89425 | -0.5501 | 13.72481 |
April | 485.00000 | 22.12263 | 32.54785 | -0.2005 | 9.54222 |
May | 508.00000 | 23.78865 | 43.23662 | -0.6064 | 14.44487 |
June | 496.00000 | 24.20067 | 49.62386 | -0.3611 | 9.09843 |
July | 497.00000 | 24.37168 | 53.51910 | -0.2630 | 7.14147 |
August | 514.00000 | 24.19556 | 52.91378 | -0.3428 | 7.92803 |
September | 485.00000 | 23.65530 | 40.74604 | -0.6702 | 17.40866 |
October | 502.00000 | 22.10069 | 32.51713 | -0.2107 | 7.57661 |
November | 489.00000 | 20.88526 | 28.00318 | -0.5908 | 16.49402 |
December | 497.00000 | 19.97809 | 18.35123 | -0.9396 | 25.49544 |
Annual Sum or Average | 5943.00000 | 22.19290 | 34.53258 | -0.5546 | 15.20900 |
Minimum of Months | 454.00000 | 19.69393 | 15.35432 | -1.0541 | 7.14147 |
Maximum of Months | 514.00000 | 24.37168 | 53.51910 | -0.2005 | 30.57625 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.64125 | 15.83848 | -1.0458 | 30.44814 |
February | 385.00000 | 20.15967 | 20.62587 | -0.8424 | 22.50752 |
March | 433.00000 | 21.41872 | 25.93297 | -0.4482 | 12.45115 |
April | 410.00000 | 22.63664 | 31.58207 | -0.0584 | 10.10557 |
May | 430.00000 | 24.15766 | 41.87464 | -0.4322 | 11.82331 |
June | 418.00000 | 24.37756 | 48.72180 | -0.2400 | 8.79844 |
July | 422.00000 | 24.61953 | 52.34972 | -0.1111 | 7.29023 |
August | 433.00000 | 24.36445 | 51.99753 | -0.2318 | 7.38588 |
September | 410.00000 | 23.97643 | 39.54842 | -0.5124 | 15.10756 |
October | 427.00000 | 22.56782 | 31.71609 | -0.0928 | 7.11980 |
November | 417.00000 | 20.95380 | 28.13798 | -0.5669 | 16.16493 |
December | 422.00000 | 19.91787 | 18.83176 | -0.9379 | 25.61249 |
Annual Sum or Average | 5034.00000 | 22.41366 | 34.02823 | -0.4577 | 14.50560 |
Minimum of Months | 385.00000 | 19.64125 | 15.83848 | -1.0458 | 7.11980 |
Maximum of Months | 433.00000 | 24.61953 | 52.34972 | -0.0584 | 30.44814 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.43541 | 15.20347 | -0.8057 | 23.18184 |
February | 454.00000 | 21.04486 | 19.14972 | -0.5926 | 16.86995 |
March | 514.00000 | 21.94436 | 24.07996 | -0.3068 | 11.11454 |
April | 485.00000 | 22.73286 | 30.75632 | -0.0228 | 10.03313 |
May | 508.00000 | 23.95923 | 42.35905 | -0.5117 | 13.01955 |
June | 496.00000 | 24.20379 | 49.36350 | -0.3294 | 9.09601 |
July | 497.00000 | 24.42397 | 53.08995 | -0.2031 | 7.18857 |
August | 514.00000 | 24.29037 | 52.14623 | -0.2459 | 7.48628 |
September | 485.00000 | 24.01745 | 39.12787 | -0.4585 | 13.87859 |
October | 502.00000 | 23.10437 | 29.52263 | 0.06862 | 7.93119 |
November | 489.00000 | 21.68972 | 26.73584 | -0.3674 | 13.83017 |
December | 497.00000 | 20.80214 | 17.30240 | -0.6960 | 19.73474 |
Annual Sum or Average | 5943.00000 | 22.73429 | 33.36397 | -0.3713 | 12.73853 |
Minimum of Months | 454.00000 | 20.43541 | 15.20347 | -0.8057 | 7.18857 |
Maximum of Months | 514.00000 | 24.42397 | 53.08995 | 0.06862 | 23.18184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.85632 | 16.05973 | -0.9972 | 28.52010 |
February | 454.00000 | 20.38060 | 20.53793 | -0.7920 | 21.30012 |
March | 514.00000 | 21.45285 | 25.94181 | -0.4418 | 12.44219 |
April | 485.00000 | 22.58779 | 31.78846 | -0.0574 | 10.04659 |
May | 508.00000 | 23.95088 | 42.87896 | -0.5023 | 13.09960 |
June | 496.00000 | 24.25415 | 49.44806 | -0.2744 | 8.90132 |
July | 497.00000 | 24.48148 | 53.12650 | -0.1473 | 7.24967 |
August | 514.00000 | 24.29620 | 52.50457 | -0.2317 | 7.35116 |
September | 485.00000 | 23.86596 | 40.39278 | -0.5434 | 15.58887 |
October | 502.00000 | 22.50826 | 31.84659 | -0.0975 | 7.57128 |
November | 489.00000 | 21.10579 | 28.54510 | -0.5275 | 15.56144 |
December | 497.00000 | 20.13862 | 19.08499 | -0.8872 | 23.94681 |
Annual Sum or Average | 5943.00000 | 22.42284 | 34.47063 | -0.4560 | 14.23169 |
Minimum of Months | 454.00000 | 19.85632 | 16.05973 | -0.9972 | 7.24967 |
Maximum of Months | 514.00000 | 24.48148 | 53.12650 | -0.0574 | 28.52010 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.195209E+12 | 0.00 | 611.58 | 260778.11 | 30-JAN-07:40 | 0.00 | 42.85 | 56.71 | 1.07 | 0.00 | 0.18 | 0.66 | 30-JAN-07:40 |
February | 0.124038E+12 | 0.00 | 475.99 | 269064.77 | 02-FEB-07:25 | 0.00 | 39.00 | 53.43 | 0.67 | 0.00 | 0.13 | 0.68 | 02-FEB-07:25 |
March | 0.676131E+11 | 0.00 | 429.36 | 214954.49 | 31-MAR-06:01 | 0.00 | 33.37 | 47.58 | 0.29 | 0.00 | 0.06 | 0.54 | 31-MAR-06:01 |
April | 0.253997E+11 | 0.00 | 284.56 | 211979.90 | 01-APR-06:03 | 0.00 | 32.74 | 43.43 | 0.10 | 0.00 | 0.02 | 0.54 | 01-APR-06:03 |
May | 0.169177E+10 | 0.00 | 81.16 | 148382.02 | 02-MAY-06:02 | 0.00 | 41.81 | 44.00 | 0.01 | 0.00 | 0.00 | 0.37 | 02-MAY-06:02 |
June | 0.361042E+09 | 0.00 | 95.68 | 24080.45 | 05-JUN-06:03 | 0.00 | 40.46 | 43.16 | 0.00 | 0.00 | 0.00 | 0.06 | 05-JUN-06:03 |
July | 4184274.85 | 0.00 | 111.72 | 5411.67 | 12-JUL-06:08 | 0.00 | 38.06 | 41.37 | 0.00 | 0.00 | 0.00 | 0.01 | 12-JUL-06:08 |
August | 33974955.68 | 0.00 | 98.21 | 15448.19 | 07-AUG-06:06 | 0.00 | 37.45 | 40.42 | 0.00 | 0.00 | 0.00 | 0.04 | 07-AUG-06:06 |
September | 0.250008E+10 | 0.00 | 126.16 | 156883.42 | 30-SEP-06:03 | 0.00 | 34.54 | 39.12 | 0.01 | 0.00 | 0.00 | 0.40 | 30-SEP-06:03 |
October | 0.135196E+11 | 0.00 | 257.82 | 187367.70 | 26-OCT-06:02 | 0.00 | 29.06 | 39.25 | 0.05 | 0.00 | 0.01 | 0.47 | 26-OCT-06:02 |
November | 0.675246E+11 | 0.00 | 383.72 | 236919.90 | 20-NOV-06:11 | 0.00 | 36.25 | 48.14 | 0.33 | 0.00 | 0.07 | 0.60 | 20-NOV-06:11 |
December | 0.142195E+12 | 0.00 | 531.89 | 246142.23 | 11-DEC-07:06 | 0.00 | 40.87 | 54.12 | 0.73 | 0.00 | 0.13 | 0.62 | 11-DEC-07:06 |
Annual Sum or Average | 0.640090E+12 | 0.00 | 3487.84 | 0.00 | 37.20 | 45.86 | 0.27 | 0.00 | 0.05 | ||||
Minimum of Months | 4184274.85 | 0.00 | 81.16 | 5411.67 | 0.00 | 29.06 | 39.12 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.195209E+12 | 0.00 | 611.58 | 269064.77 | 0.00 | 42.85 | 56.71 | 1.07 | 0.00 | 0.18 | 0.68 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.155883E+09 | 40989878.70 | 14.48 | 0.137587E+09 | 18295555.51 | 0.00 | 0.25 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 6915.83 | 25-MAR-15:00 | 6128.47 | 25-MAR-15:00 | 957.73 | 25-MAR-15:50 | 1777.35 | 25-MAR-15:00 | 0.00 |
April | 0.589341E+10 | 0.139525E+10 | 108.50 | 0.474135E+10 | 0.115206E+10 | 0.00 | 1.00 | 18-APR-08:30 | 0.00 | 01-APR-00:10 | 65277.30 | 18-APR-15:00 | 55086.54 | 18-APR-15:00 | 23019.94 | 18-APR-09:30 | 15164.41 | 18-APR-15:00 | 0.00 |
May | 0.149747E+11 | 0.349264E+10 | 243.01 | 0.115096E+11 | 0.346508E+10 | 0.00 | 1.00 | 04-MAY-14:20 | 0.00 | 01-MAY-00:10 | 72108.60 | 30-MAY-11:00 | 58828.56 | 31-MAY-15:00 | 30529.26 | 30-MAY-10:05 | 15656.15 | 31-MAY-15:00 | 0.00 |
June | 0.440994E+11 | 0.999994E+10 | 346.70 | 0.327892E+11 | 0.113102E+11 | 0.00 | 1.00 | 08-JUN-15:20 | 0.00 | 01-JUN-00:10 | 116263.10 | 26-JUN-08:00 | 70627.66 | 26-JUN-14:50 | 67351.43 | 26-JUN-07:10 | 24238.07 | 26-JUN-08:00 | 0.00 |
July | 0.634313E+11 | 0.140074E+11 | 438.35 | 0.428386E+11 | 0.205927E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 114123.92 | 03-JUL-08:50 | 68700.41 | 03-JUL-14:40 | 66477.77 | 07-JUL-06:03 | 23908.85 | 03-JUL-08:50 | 0.00 |
August | 0.623417E+11 | 0.138363E+11 | 425.03 | 0.430778E+11 | 0.192640E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 117222.66 | 03-AUG-05:12 | 69914.71 | 04-AUG-16:00 | 84556.34 | 04-AUG-07:00 | 25008.20 | 04-AUG-14:30 | 0.00 |
September | 0.261917E+11 | 0.607354E+10 | 282.23 | 0.231846E+11 | 0.300711E+10 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 100078.63 | 11-SEP-09:50 | 66388.15 | 06-SEP-15:20 | 44827.79 | 11-SEP-06:03 | 21371.96 | 11-SEP-09:50 | 0.00 |
October | 0.255696E+10 | 0.625454E+09 | 102.67 | 0.235062E+10 | 0.206348E+09 | 0.00 | 1.00 | 20-OCT-14:05 | 0.00 | 01-OCT-00:10 | 37371.28 | 20-OCT-15:00 | 37371.28 | 20-OCT-15:00 | 4875.44 | 02-OCT-15:00 | 7846.92 | 20-OCT-15:00 | 0.00 |
November | 0.149123E+09 | 39113474.65 | 14.29 | 0.132387E+09 | 16736047.14 | 0.00 | 0.31 | 01-NOV-11:00 | 0.00 | 01-NOV-00:10 | 8891.31 | 01-NOV-11:00 | 8189.82 | 01-NOV-11:00 | 1230.28 | 01-NOV-11:02 | 2248.77 | 01-NOV-11:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.219794E+12 | 0.495106E+11 | 1975.26 | 0.160762E+12 | 0.590325E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.634313E+11 | 0.140074E+11 | 438.35 | 0.430778E+11 | 0.205927E+11 | 0.00 | 1.00 | 0.00 | 117222.66 | 70627.66 | 84556.34 | 25008.20 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.163671E+09 | 42821749.45 | 12.39 | 0.137359E+09 | 26312416.35 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7395.82 | 25-MAR-15:00 | 7022.60 | 25-MAR-15:00 | 2470.92 | 19-MAR-14:33 | 1887.96 | 25-MAR-15:00 | 0.00 |
April | 0.552866E+10 | 0.129132E+10 | 86.03 | 0.439873E+10 | 0.112993E+10 | 0.00 | 1.00 | 15-APR-13:10 | 0.00 | 01-APR-00:10 | 68982.07 | 18-APR-12:30 | 56049.28 | 18-APR-15:00 | 24163.14 | 18-APR-09:30 | 15689.60 | 18-APR-12:30 | 0.00 |
May | 0.144963E+11 | 0.336913E+10 | 244.01 | 0.109598E+11 | 0.353650E+10 | 0.00 | 1.00 | 04-MAY-13:50 | 0.00 | 01-MAY-00:10 | 72018.43 | 30-MAY-11:00 | 58367.80 | 31-MAY-14:05 | 32455.15 | 30-MAY-10:05 | 15597.31 | 31-MAY-14:05 | 0.00 |
June | 0.417255E+11 | 0.947185E+10 | 350.81 | 0.312394E+11 | 0.104860E+11 | 0.00 | 1.00 | 08-JUN-13:00 | 0.00 | 01-JUN-00:10 | 111062.33 | 26-JUN-08:00 | 67212.52 | 26-JUN-14:05 | 64432.18 | 26-JUN-07:10 | 23153.83 | 26-JUN-08:00 | 0.00 |
July | 0.569730E+11 | 0.126176E+11 | 439.85 | 0.387335E+11 | 0.182395E+11 | 0.00 | 1.00 | 01-JUL-08:40 | 0.00 | 01-JUL-00:10 | 109018.85 | 03-JUL-08:50 | 64162.58 | 03-JUL-15:00 | 61884.77 | 05-JUL-06:03 | 22839.34 | 03-JUL-08:50 | 0.00 |
August | 0.533461E+11 | 0.119068E+11 | 424.55 | 0.372520E+11 | 0.160941E+11 | 0.00 | 1.00 | 01-AUG-06:03 | 0.00 | 01-AUG-00:10 | 111978.97 | 03-AUG-05:12 | 67732.50 | 04-AUG-15:10 | 79794.45 | 04-AUG-07:05 | 24002.28 | 04-AUG-14:05 | 0.00 |
September | 0.215811E+11 | 0.501917E+10 | 242.72 | 0.191454E+11 | 0.243573E+10 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 85320.80 | 11-SEP-09:50 | 63687.14 | 07-SEP-16:00 | 42103.87 | 11-SEP-06:03 | 19116.36 | 06-SEP-14:05 | 0.00 |
October | 0.130215E+10 | 0.320003E+09 | 52.40 | 0.111588E+10 | 0.186275E+09 | 0.00 | 0.93 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29867.68 | 20-OCT-15:00 | 29867.68 | 20-OCT-15:00 | 4385.74 | 02-OCT-15:00 | 6402.99 | 20-OCT-15:00 | 0.00 |
November | 80672418.90 | 20913243.73 | 5.67 | 69431082.53 | 11241336.37 | 0.00 | 0.27 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 7351.70 | 03-NOV-13:30 | 6342.41 | 03-NOV-14:05 | 1468.78 | 03-NOV-12:50 | 1877.41 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.195197E+12 | 0.440595E+11 | 1858.41 | 0.143051E+12 | 0.521456E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.569730E+11 | 0.126176E+11 | 439.85 | 0.387335E+11 | 0.182395E+11 | 0.00 | 1.00 | 0.00 | 111978.97 | 67732.50 | 79794.45 | 24002.28 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1316785.42 | 356866.04 | 0.76 | 1314326.24 | 2459.18 | 0.00 | 0.03 | 23-JAN-06:50 | 0.00 | 01-JAN-00:03 | 978.55 | 23-JAN-06:50 | 978.55 | 23-JAN-06:50 | 8.20 | 22-JAN-16:05 | 264.43 | 23-JAN-06:50 | 0.00 |
February | 5287012.81 | 1429018.12 | 1.89 | 4516826.43 | 770186.39 | 0.00 | 0.04 | 24-FEB-15:10 | 0.00 | 01-FEB-00:05 | 1207.97 | 24-FEB-15:10 | 1025.13 | 24-FEB-15:10 | 184.06 | 24-FEB-15:30 | 325.82 | 24-FEB-15:10 | 0.00 |
March | 0.149864E+09 | 39367865.84 | 11.66 | 0.122739E+09 | 27125587.66 | 0.00 | 0.25 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7422.87 | 25-MAR-15:00 | 6618.91 | 25-MAR-15:00 | 2739.79 | 19-MAR-13:55 | 1906.82 | 25-MAR-15:00 | 0.00 |
April | 0.609646E+10 | 0.142701E+10 | 89.18 | 0.482867E+10 | 0.126779E+10 | 0.00 | 1.00 | 15-APR-13:05 | 0.00 | 01-APR-00:10 | 79892.76 | 16-APR-14:42 | 62725.62 | 18-APR-14:50 | 29063.14 | 16-APR-14:02 | 18091.89 | 16-APR-14:42 | 0.00 |
May | 0.152803E+11 | 0.356335E+10 | 243.39 | 0.116058E+11 | 0.367446E+10 | 0.00 | 1.00 | 04-MAY-13:40 | 0.00 | 01-MAY-00:10 | 71780.40 | 30-MAY-14:00 | 65736.95 | 31-MAY-15:00 | 28616.04 | 30-MAY-10:00 | 17135.76 | 31-MAY-15:00 | 0.00 |
June | 0.442858E+11 | 0.100957E+11 | 350.89 | 0.335003E+11 | 0.107855E+11 | 0.00 | 1.00 | 08-JUN-15:10 | 0.00 | 01-JUN-00:10 | 120132.05 | 26-JUN-06:03 | 78837.84 | 11-JUN-15:22 | 71394.69 | 26-JUN-06:03 | 25065.44 | 26-JUN-06:03 | 0.00 |
July | 0.597810E+11 | 0.132851E+11 | 439.17 | 0.406238E+11 | 0.191572E+11 | 0.00 | 1.00 | 01-JUL-12:30 | 0.00 | 01-JUL-00:10 | 112236.33 | 05-JUL-11:00 | 72878.37 | 02-JUL-15:22 | 65910.46 | 05-JUL-06:03 | 23831.12 | 05-JUL-11:00 | 0.00 |
August | 0.547269E+11 | 0.122891E+11 | 425.26 | 0.386420E+11 | 0.160849E+11 | 0.00 | 1.00 | 01-AUG-07:30 | 0.00 | 01-AUG-00:10 | 124848.20 | 04-AUG-06:03 | 78675.38 | 04-AUG-15:20 | 89014.86 | 04-AUG-07:10 | 26302.69 | 04-AUG-15:30 | 0.00 |
September | 0.221112E+11 | 0.517952E+10 | 237.98 | 0.195077E+11 | 0.260345E+10 | 0.00 | 1.00 | 01-SEP-12:00 | 0.00 | 01-SEP-00:10 | 84665.35 | 11-SEP-10:00 | 71668.78 | 07-SEP-16:00 | 32371.70 | 11-SEP-10:00 | 20301.05 | 06-SEP-14:00 | 0.00 |
October | 0.122110E+10 | 0.303946E+09 | 50.27 | 0.101330E+10 | 0.207802E+09 | 0.00 | 0.83 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29019.45 | 20-OCT-15:00 | 29019.45 | 20-OCT-15:00 | 4416.60 | 02-OCT-15:00 | 6396.23 | 20-OCT-15:00 | 0.00 |
November | 47591183.26 | 12634128.69 | 5.64 | 40391708.55 | 7199474.71 | 0.00 | 0.15 | 03-NOV-13:40 | 0.00 | 01-NOV-00:10 | 4503.76 | 03-NOV-13:40 | 3807.35 | 03-NOV-13:50 | 843.40 | 03-NOV-13:05 | 1183.41 | 03-NOV-13:40 | 0.00 |
December | 705184.89 | 191472.61 | 0.63 | 683814.40 | 21370.49 | 0.00 | 0.02 | 04-DEC-06:06 | 0.00 | 01-DEC-00:10 | 700.62 | 04-DEC-06:06 | 700.62 | 04-DEC-06:06 | 26.72 | 14-DEC-05:04 | 189.75 | 04-DEC-06:06 | 0.00 |
Annual Sum or Average | 0.203707E+12 | 0.461977E+11 | 1856.72 | 0.149891E+12 | 0.538162E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 705184.89 | 191472.61 | 0.63 | 683814.40 | 2459.18 | 0.00 | 0.02 | 0.00 | 700.62 | 700.62 | 8.20 | 189.75 | 0.00 | ||||||
Maximum of Months | 0.597810E+11 | 0.132851E+11 | 439.17 | 0.406238E+11 | 0.191572E+11 | 0.00 | 1.00 | 0.00 | 124848.20 | 78837.84 | 89014.86 | 26302.69 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.88 | 2883.10 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 30.70 | 2307.41 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 224.83 | 1480.50 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 449.61 | 1024.74 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 913.75 | 609.78 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1384.44 | 420.21 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1356.26 | 366.72 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1129.63 | 430.38 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 683.40 | 743.09 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 264.29 | 1116.77 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 66.43 | 1720.58 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.49 | 2535.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 545.21 | 1298.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.49 | 366.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1384.44 | 2883.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 230.23 | 1738.22 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 403.60 | 1371.36 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 724.73 | 911.82 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1102.09 | 662.16 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1610.28 | 414.38 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1973.16 | 284.61 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2043.00 | 248.01 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1725.13 | 288.61 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1421.72 | 482.01 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 686.56 | 705.42 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 245.55 | 1069.15 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 161.07 | 1565.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1030.65 | 809.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 161.07 | 248.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2043.00 | 1738.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2017.96 | 2359.26 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2253.99 | 1900.18 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2053.78 | 1387.85 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2058.34 | 1050.07 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1802.27 | 667.57 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1949.06 | 452.07 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2156.26 | 392.57 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2469.32 | 462.38 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2794.11 | 756.67 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2561.20 | 1083.06 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1648.39 | 1536.44 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1776.41 | 2187.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2127.57 | 1183.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1648.39 | 392.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2794.11 | 2359.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 237.90 | 1778.97 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 497.34 | 1419.90 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 686.15 | 940.54 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1346.14 | 688.78 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1476.79 | 436.44 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1935.13 | 304.94 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2138.90 | 270.64 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1880.35 | 310.31 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1392.16 | 503.14 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 769.93 | 734.69 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 308.37 | 1093.89 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 207.72 | 1598.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1075.92 | 837.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 207.72 | 270.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2138.90 | 1778.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.04 | 0.00 | 121.04 | 0.68 | 963.19 | 0.00 | 0.00 | 0.00 |
February | 153.46 | 0.00 | 153.46 | 10.24 | 774.20 | 0.00 | 0.00 | 0.00 |
March | 229.99 | 0.00 | 229.99 | 80.83 | 494.12 | 0.00 | 0.00 | 0.00 |
April | 265.51 | 1.31 | 264.20 | 162.09 | 333.93 | 0.00 | 0.00 | 0.00 |
May | 346.22 | 13.01 | 333.21 | 321.99 | 193.19 | 0.00 | 0.00 | 0.00 |
June | 404.66 | 36.73 | 367.93 | 472.41 | 136.76 | 0.00 | 0.00 | 0.00 |
July | 379.50 | 25.38 | 354.12 | 460.27 | 120.74 | 0.00 | 0.00 | 0.00 |
August | 317.76 | 5.63 | 312.13 | 380.11 | 146.32 | 0.00 | 0.00 | 0.00 |
September | 243.63 | 0.06 | 243.57 | 226.47 | 262.38 | 0.00 | 0.00 | 0.00 |
October | 181.14 | 0.00 | 181.14 | 81.23 | 405.18 | 0.00 | 0.00 | 0.00 |
November | 126.71 | 0.00 | 126.71 | 19.29 | 610.08 | 0.00 | 0.00 | 0.00 |
December | 82.19 | 0.00 | 82.19 | 0.08 | 868.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.10 | 6.87 | 231.23 | 185.68 | 440.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.19 | 0.00 | 82.19 | 0.08 | 120.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.66 | 36.73 | 367.93 | 472.41 | 963.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.68 | 963.25 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.24 | 774.26 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 80.83 | 494.15 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 162.09 | 333.95 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 322.00 | 193.20 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 472.43 | 136.77 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 460.29 | 120.74 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 380.12 | 146.33 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 226.48 | 262.40 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 81.23 | 405.20 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 19.29 | 610.12 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.08 | 868.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 185.69 | 440.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.08 | 120.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 472.43 | 963.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.05 | 0.00 | 121.05 | 0.68 | 963.25 | 0.00 | 0.00 | 0.00 |
February | 153.47 | 0.00 | 153.47 | 10.24 | 774.26 | 0.00 | 0.00 | 0.00 |
March | 230.00 | 0.00 | 230.00 | 80.83 | 494.15 | 0.00 | 0.00 | 0.00 |
April | 265.52 | 1.31 | 264.21 | 162.09 | 333.95 | 0.00 | 0.00 | 0.00 |
May | 346.24 | 13.01 | 333.22 | 322.00 | 193.20 | 0.00 | 0.00 | 0.00 |
June | 404.67 | 36.73 | 367.94 | 472.43 | 136.77 | 0.00 | 0.00 | 0.00 |
July | 379.52 | 25.39 | 354.13 | 460.29 | 120.74 | 0.00 | 0.00 | 0.00 |
August | 317.77 | 5.63 | 312.14 | 380.12 | 146.33 | 0.00 | 0.00 | 0.00 |
September | 243.64 | 0.06 | 243.58 | 226.48 | 262.40 | 0.00 | 0.00 | 0.00 |
October | 181.15 | 0.00 | 181.15 | 81.23 | 405.20 | 0.00 | 0.00 | 0.00 |
November | 126.72 | 0.00 | 126.72 | 19.29 | 610.12 | 0.00 | 0.00 | 0.00 |
December | 82.20 | 0.00 | 82.20 | 0.08 | 868.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.11 | 6.87 | 231.24 | 185.69 | 440.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.20 | 0.00 | 82.20 | 0.08 | 120.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 404.67 | 36.73 | 367.94 | 472.43 | 963.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.03 | 205.35 | 293.68 | 224.50 | 1685.31 | 0.00 | 0.00 | 0.00 |
February | 661.47 | 290.86 | 370.61 | 392.53 | 1341.53 | 0.00 | 0.00 | 0.00 |
March | 898.73 | 356.73 | 542.00 | 711.92 | 888.06 | 0.00 | 0.00 | 0.00 |
April | 1103.55 | 483.28 | 620.27 | 1084.20 | 636.82 | 0.00 | 0.00 | 0.00 |
May | 1385.98 | 605.61 | 780.37 | 1574.39 | 395.02 | 0.00 | 0.00 | 0.00 |
June | 1525.23 | 664.21 | 861.02 | 1916.10 | 276.96 | 0.00 | 0.00 | 0.00 |
July | 1541.62 | 711.33 | 830.28 | 1978.87 | 244.85 | 0.00 | 0.00 | 0.00 |
August | 1299.55 | 560.26 | 739.29 | 1667.27 | 290.79 | 0.00 | 0.00 | 0.00 |
September | 1159.08 | 547.73 | 611.36 | 1365.56 | 501.47 | 0.00 | 0.00 | 0.00 |
October | 738.65 | 308.53 | 430.12 | 641.45 | 752.11 | 0.00 | 0.00 | 0.00 |
November | 435.81 | 141.56 | 294.25 | 225.92 | 1100.55 | 0.00 | 0.00 | 0.00 |
December | 337.58 | 144.97 | 192.62 | 153.29 | 1551.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 967.03 | 418.97 | 548.06 | 997.94 | 802.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.58 | 141.56 | 192.62 | 153.29 | 244.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1541.62 | 711.33 | 861.02 | 1978.87 | 1685.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.73 | 8.12 | 11.61 | 8.88 | 66.64 | 0.00 | 0.00 | 0.00 |
February | 26.15 | 11.50 | 14.65 | 15.52 | 53.04 | 0.00 | 0.00 | 0.00 |
March | 35.53 | 14.10 | 21.43 | 28.15 | 35.11 | 0.00 | 0.00 | 0.00 |
April | 43.63 | 19.11 | 24.53 | 42.87 | 25.18 | 0.00 | 0.00 | 0.00 |
May | 54.80 | 23.95 | 30.86 | 62.25 | 15.62 | 0.00 | 0.00 | 0.00 |
June | 60.31 | 26.26 | 34.04 | 75.76 | 10.95 | 0.00 | 0.00 | 0.00 |
July | 60.95 | 28.13 | 32.83 | 78.24 | 9.68 | 0.00 | 0.00 | 0.00 |
August | 51.38 | 22.15 | 29.23 | 65.92 | 11.50 | 0.00 | 0.00 | 0.00 |
September | 45.83 | 21.66 | 24.17 | 53.99 | 19.83 | 0.00 | 0.00 | 0.00 |
October | 29.21 | 12.20 | 17.01 | 25.36 | 29.74 | 0.00 | 0.00 | 0.00 |
November | 17.23 | 5.60 | 11.63 | 8.93 | 43.51 | 0.00 | 0.00 | 0.00 |
December | 13.35 | 5.73 | 7.62 | 6.06 | 61.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.24 | 16.57 | 21.67 | 39.46 | 31.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.35 | 5.60 | 7.62 | 6.06 | 9.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.95 | 28.13 | 34.04 | 78.24 | 66.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 691.57 | 777.43 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 769.79 | 640.97 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 702.38 | 466.01 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 703.10 | 347.60 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 620.06 | 214.59 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 662.85 | 147.88 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 727.61 | 131.96 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 829.03 | 161.64 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 934.08 | 272.37 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 852.40 | 401.17 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 550.21 | 546.73 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 599.23 | 742.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 719.87 | 403.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 550.21 | 131.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 934.08 | 777.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.79 | 515.15 | 237.64 | 691.57 | 777.43 | 0.00 | 0.00 | 0.00 |
February | 806.60 | 544.94 | 261.66 | 769.79 | 640.97 | 0.00 | 0.00 | 0.00 |
March | 701.92 | 369.61 | 332.31 | 702.38 | 466.01 | 0.00 | 0.00 | 0.00 |
April | 632.39 | 295.65 | 336.74 | 703.10 | 347.60 | 0.00 | 0.00 | 0.00 |
May | 523.91 | 142.04 | 381.87 | 620.06 | 214.59 | 0.00 | 0.00 | 0.00 |
June | 508.64 | 103.56 | 405.08 | 662.85 | 147.88 | 0.00 | 0.00 | 0.00 |
July | 538.43 | 135.67 | 402.76 | 727.61 | 131.96 | 0.00 | 0.00 | 0.00 |
August | 606.63 | 217.55 | 389.08 | 829.03 | 161.64 | 0.00 | 0.00 | 0.00 |
September | 735.11 | 387.34 | 347.77 | 934.08 | 272.37 | 0.00 | 0.00 | 0.00 |
October | 767.61 | 481.56 | 286.04 | 852.40 | 401.17 | 0.00 | 0.00 | 0.00 |
November | 579.16 | 362.56 | 216.59 | 550.21 | 546.73 | 0.00 | 0.00 | 0.00 |
December | 617.59 | 467.81 | 149.77 | 599.23 | 742.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.63 | 334.09 | 312.54 | 719.87 | 403.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.64 | 103.56 | 149.77 | 550.21 | 131.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.60 | 544.94 | 405.08 | 934.08 | 777.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 752.74 | 515.12 | 237.62 | 691.53 | 777.38 | 0.00 | 0.00 | 0.00 |
February | 806.55 | 544.91 | 261.64 | 769.74 | 640.92 | 0.00 | 0.00 | 0.00 |
March | 701.88 | 369.58 | 332.29 | 702.33 | 465.99 | 0.00 | 0.00 | 0.00 |
April | 632.35 | 295.63 | 336.71 | 703.05 | 347.58 | 0.00 | 0.00 | 0.00 |
May | 523.88 | 142.03 | 381.85 | 620.02 | 214.57 | 0.00 | 0.00 | 0.00 |
June | 508.61 | 103.55 | 405.05 | 662.81 | 147.87 | 0.00 | 0.00 | 0.00 |
July | 538.40 | 135.66 | 402.74 | 727.56 | 131.95 | 0.00 | 0.00 | 0.00 |
August | 606.59 | 217.54 | 389.06 | 828.98 | 161.63 | 0.00 | 0.00 | 0.00 |
September | 735.06 | 387.32 | 347.75 | 934.02 | 272.35 | 0.00 | 0.00 | 0.00 |
October | 767.56 | 481.53 | 286.02 | 852.34 | 401.15 | 0.00 | 0.00 | 0.00 |
November | 579.12 | 362.54 | 216.58 | 550.17 | 546.70 | 0.00 | 0.00 | 0.00 |
December | 617.55 | 467.78 | 149.76 | 599.19 | 742.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 646.59 | 334.07 | 312.52 | 719.82 | 403.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 508.61 | 103.55 | 149.76 | 550.17 | 131.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 806.55 | 544.91 | 405.05 | 934.02 | 777.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.92 | 200.25 | 294.67 | 234.57 | 1722.68 | 0.00 | 0.00 | 0.00 |
February | 725.71 | 357.61 | 368.10 | 487.92 | 1387.15 | 0.00 | 0.00 | 0.00 |
March | 866.35 | 322.33 | 544.02 | 678.71 | 916.36 | 0.00 | 0.00 | 0.00 |
April | 1263.75 | 624.90 | 638.85 | 1319.01 | 669.79 | 0.00 | 0.00 | 0.00 |
May | 1267.40 | 506.30 | 761.11 | 1447.54 | 415.86 | 0.00 | 0.00 | 0.00 |
June | 1487.15 | 644.49 | 842.66 | 1879.93 | 297.48 | 0.00 | 0.00 | 0.00 |
July | 1596.74 | 758.48 | 838.27 | 2070.59 | 270.82 | 0.00 | 0.00 | 0.00 |
August | 1395.96 | 640.65 | 755.31 | 1817.49 | 316.22 | 0.00 | 0.00 | 0.00 |
September | 1129.99 | 536.35 | 593.64 | 1337.31 | 524.51 | 0.00 | 0.00 | 0.00 |
October | 787.42 | 350.08 | 437.34 | 727.29 | 783.73 | 0.00 | 0.00 | 0.00 |
November | 471.32 | 174.29 | 297.03 | 289.17 | 1126.31 | 0.00 | 0.00 | 0.00 |
December | 362.47 | 170.87 | 191.60 | 201.28 | 1584.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 988.48 | 440.63 | 547.85 | 1043.63 | 832.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 362.47 | 170.87 | 191.60 | 201.28 | 270.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1596.74 | 758.48 | 842.66 | 2070.59 | 1722.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.57 | 7.92 | 11.65 | 9.27 | 68.11 | 0.00 | 0.00 | 0.00 |
February | 28.69 | 14.14 | 14.55 | 19.29 | 54.85 | 0.00 | 0.00 | 0.00 |
March | 34.25 | 12.74 | 21.51 | 26.84 | 36.23 | 0.00 | 0.00 | 0.00 |
April | 49.97 | 24.71 | 25.26 | 52.15 | 26.48 | 0.00 | 0.00 | 0.00 |
May | 50.11 | 20.02 | 30.09 | 57.23 | 16.44 | 0.00 | 0.00 | 0.00 |
June | 58.80 | 25.48 | 33.32 | 74.33 | 11.76 | 0.00 | 0.00 | 0.00 |
July | 63.13 | 29.99 | 33.14 | 81.87 | 10.71 | 0.00 | 0.00 | 0.00 |
August | 55.19 | 25.33 | 29.86 | 71.86 | 12.50 | 0.00 | 0.00 | 0.00 |
September | 44.68 | 21.21 | 23.47 | 52.88 | 20.74 | 0.00 | 0.00 | 0.00 |
October | 31.13 | 13.84 | 17.29 | 28.76 | 30.99 | 0.00 | 0.00 | 0.00 |
November | 18.64 | 6.89 | 11.74 | 11.43 | 44.53 | 0.00 | 0.00 | 0.00 |
December | 14.33 | 6.76 | 7.58 | 7.96 | 62.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.08 | 17.42 | 21.66 | 41.26 | 32.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.33 | 6.76 | 7.58 | 7.96 | 10.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.13 | 29.99 | 33.32 | 81.87 | 68.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 363.15 | 0.00 | 363.15 | 1.55 | 2940.93 | 0.00 | 0.00 | 0.00 |
February | 460.40 | 0.00 | 460.40 | 26.82 | 2385.26 | 0.00 | 0.00 | 0.00 |
March | 690.00 | 0.00 | 690.00 | 213.90 | 1549.54 | 0.00 | 0.00 | 0.00 |
April | 796.55 | 3.92 | 792.63 | 439.43 | 1087.07 | 0.00 | 0.00 | 0.00 |
May | 1038.72 | 39.04 | 999.68 | 905.16 | 635.59 | 0.00 | 0.00 | 0.00 |
June | 1214.03 | 110.19 | 1103.84 | 1381.88 | 436.18 | 0.00 | 0.00 | 0.00 |
July | 1138.57 | 76.16 | 1062.41 | 1356.96 | 377.99 | 0.00 | 0.00 | 0.00 |
August | 953.32 | 16.90 | 936.42 | 1127.46 | 446.99 | 0.00 | 0.00 | 0.00 |
September | 730.92 | 0.18 | 730.74 | 672.13 | 787.64 | 0.00 | 0.00 | 0.00 |
October | 543.45 | 0.00 | 543.45 | 240.03 | 1206.19 | 0.00 | 0.00 | 0.00 |
November | 380.15 | 0.00 | 380.15 | 56.25 | 1819.74 | 0.00 | 0.00 | 0.00 |
December | 246.59 | 0.00 | 246.59 | 0.19 | 2618.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 714.32 | 20.61 | 693.71 | 538.20 | 1352.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.59 | 0.00 | 246.59 | 0.19 | 377.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1214.03 | 110.19 | 1103.84 | 1381.88 | 2940.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.77 | 213.48 | 305.30 | 227.32 | 1770.39 | 0.00 | 0.00 | 0.00 |
February | 687.63 | 302.36 | 385.27 | 396.23 | 1417.77 | 0.00 | 0.00 | 0.00 |
March | 934.28 | 370.84 | 563.44 | 711.37 | 955.30 | 0.00 | 0.00 | 0.00 |
April | 1147.21 | 502.40 | 644.81 | 1092.01 | 700.71 | 0.00 | 0.00 | 0.00 |
May | 1440.80 | 629.56 | 811.23 | 1604.80 | 430.00 | 0.00 | 0.00 | 0.00 |
June | 1585.56 | 690.49 | 895.07 | 1970.04 | 295.27 | 0.00 | 0.00 | 0.00 |
July | 1602.59 | 739.47 | 863.12 | 2042.01 | 255.40 | 0.00 | 0.00 | 0.00 |
August | 1350.96 | 582.43 | 768.53 | 1722.15 | 299.03 | 0.00 | 0.00 | 0.00 |
September | 1204.93 | 569.39 | 635.54 | 1412.94 | 508.28 | 0.00 | 0.00 | 0.00 |
October | 767.87 | 320.73 | 447.13 | 663.42 | 759.79 | 0.00 | 0.00 | 0.00 |
November | 453.05 | 147.16 | 305.89 | 232.70 | 1129.43 | 0.00 | 0.00 | 0.00 |
December | 350.93 | 150.70 | 200.23 | 157.01 | 1613.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1005.28 | 435.54 | 569.74 | 1022.73 | 841.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 350.93 | 147.16 | 200.23 | 157.01 | 255.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1602.59 | 739.47 | 895.07 | 2042.01 | 1770.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2258.40 | 1545.48 | 712.93 | 2007.30 | 2416.22 | 0.00 | 0.00 | 0.00 |
February | 2419.84 | 1634.86 | 784.98 | 2238.23 | 1973.20 | 0.00 | 0.00 | 0.00 |
March | 2105.80 | 1108.85 | 996.96 | 2039.10 | 1454.90 | 0.00 | 0.00 | 0.00 |
April | 1897.19 | 886.97 | 1010.22 | 2050.17 | 1111.11 | 0.00 | 0.00 | 0.00 |
May | 1571.76 | 426.12 | 1145.63 | 1799.20 | 695.82 | 0.00 | 0.00 | 0.00 |
June | 1525.94 | 310.69 | 1215.25 | 1949.64 | 470.62 | 0.00 | 0.00 | 0.00 |
July | 1615.31 | 407.02 | 1208.30 | 2159.37 | 405.59 | 0.00 | 0.00 | 0.00 |
August | 1819.92 | 652.67 | 1167.25 | 2471.12 | 480.46 | 0.00 | 0.00 | 0.00 |
September | 2205.36 | 1162.04 | 1043.32 | 2786.94 | 798.04 | 0.00 | 0.00 | 0.00 |
October | 2302.86 | 1444.72 | 858.14 | 2537.07 | 1162.73 | 0.00 | 0.00 | 0.00 |
November | 1737.50 | 1087.71 | 649.79 | 1624.63 | 1625.08 | 0.00 | 0.00 | 0.00 |
December | 1852.79 | 1403.47 | 449.32 | 1763.69 | 2264.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1939.91 | 1002.29 | 937.62 | 2118.07 | 1234.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1525.94 | 310.69 | 449.32 | 1624.63 | 405.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2419.84 | 1634.86 | 1215.25 | 2786.94 | 2416.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 514.49 | 208.17 | 306.32 | 236.37 | 1814.37 | 0.00 | 0.00 | 0.00 |
February | 754.42 | 371.75 | 382.66 | 492.93 | 1468.41 | 0.00 | 0.00 | 0.00 |
March | 900.62 | 335.08 | 565.54 | 678.08 | 985.46 | 0.00 | 0.00 | 0.00 |
April | 1313.73 | 649.62 | 664.11 | 1340.80 | 729.83 | 0.00 | 0.00 | 0.00 |
May | 1317.53 | 526.32 | 791.21 | 1474.12 | 455.31 | 0.00 | 0.00 | 0.00 |
June | 1545.97 | 669.98 | 875.98 | 1935.80 | 317.23 | 0.00 | 0.00 | 0.00 |
July | 1659.90 | 788.48 | 871.42 | 2141.37 | 279.54 | 0.00 | 0.00 | 0.00 |
August | 1451.17 | 665.99 | 785.18 | 1881.46 | 322.30 | 0.00 | 0.00 | 0.00 |
September | 1174.68 | 557.56 | 617.12 | 1385.95 | 531.90 | 0.00 | 0.00 | 0.00 |
October | 818.57 | 363.93 | 454.64 | 753.75 | 792.16 | 0.00 | 0.00 | 0.00 |
November | 489.97 | 181.19 | 308.78 | 298.24 | 1155.97 | 0.00 | 0.00 | 0.00 |
December | 376.81 | 177.63 | 199.18 | 204.89 | 1650.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1027.58 | 458.06 | 569.51 | 1071.50 | 872.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 376.81 | 177.63 | 199.18 | 204.89 | 279.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.90 | 788.48 | 875.98 | 2141.37 | 1814.37 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 5032677.72 | 0.772210E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 74262018.65 | 0.558208E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.602197E+09 | 0.396538E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.116540E+10 | 0.265613E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.244739E+10 | 0.163325E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.358848E+10 | 0.108918E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.363262E+10 | 0.982228E+09 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.302559E+10 | 0.115273E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.177138E+10 | 0.192609E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.707862E+09 | 0.299114E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.172199E+09 | 0.445974E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 1304893.01 | 0.679183E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.171937E+11 | 0.409519E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 1304893.01 | 0.982228E+09 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.363262E+10 | 0.772210E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.616658E+09 | 0.465564E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.976379E+09 | 0.331761E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.194111E+10 | 0.244222E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.285662E+10 | 0.171633E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.431298E+10 | 0.110987E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.511443E+10 | 0.737701E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.547196E+10 | 0.664279E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.462060E+10 | 0.773007E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.368509E+10 | 0.124936E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.183888E+10 | 0.188941E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.636466E+09 | 0.277124E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.431404E+09 | 0.419233E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.325026E+11 | 0.255190E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.431404E+09 | 0.664279E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.547196E+10 | 0.465564E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.540490E+10 | 0.631904E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.545285E+10 | 0.459692E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.550085E+10 | 0.371722E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.533521E+10 | 0.272179E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.482721E+10 | 0.178801E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.505198E+10 | 0.117176E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.577532E+10 | 0.105147E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.661382E+10 | 0.123844E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.724234E+10 | 0.196129E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.685993E+10 | 0.290088E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.427262E+10 | 0.398245E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.475795E+10 | 0.585837E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.670950E+11 | 0.373077E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.427262E+10 | 0.105147E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.724234E+10 | 0.631904E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.637188E+09 | 0.476479E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.120316E+10 | 0.343502E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.183779E+10 | 0.251915E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.348920E+10 | 0.178531E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.395543E+10 | 0.116895E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.501586E+10 | 0.790402E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.572884E+10 | 0.724879E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.503632E+10 | 0.831125E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.360848E+10 | 0.130414E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.206219E+10 | 0.196780E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.799286E+09 | 0.283536E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.556370E+09 | 0.428186E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.339301E+11 | 0.264088E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.556370E+09 | 0.724879E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.572884E+10 | 0.476479E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324202E+09 | 0.00 | 0.324202E+09 | 1829953.81 | 0.257980E+10 |
February | 0.371248E+09 | 0.00 | 0.371248E+09 | 24766442.21 | 0.187295E+10 |
March | 0.616000E+09 | 0.00 | 0.616000E+09 | 0.216496E+09 | 0.132344E+10 |
April | 0.688190E+09 | 3390682.39 | 0.684800E+09 | 0.420129E+09 | 0.865545E+09 |
May | 0.927327E+09 | 34856080.88 | 0.892471E+09 | 0.862410E+09 | 0.517430E+09 |
June | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.122448E+10 | 0.354492E+09 |
July | 0.101647E+10 | 67990399.01 | 0.948475E+09 | 0.123278E+10 | 0.323382E+09 |
August | 0.851080E+09 | 15083510.68 | 0.835996E+09 | 0.101807E+10 | 0.391897E+09 |
September | 0.631484E+09 | 156579.94 | 0.631328E+09 | 0.587009E+09 | 0.680095E+09 |
October | 0.485171E+09 | 0.00 | 0.485171E+09 | 0.217557E+09 | 0.108523E+10 |
November | 0.328434E+09 | 0.00 | 0.328434E+09 | 49987870.54 | 0.158134E+10 |
December | 0.220144E+09 | 0.00 | 0.220144E+09 | 212476.46 | 0.232528E+10 |
Annual Sum or Average | 0.750862E+10 | 0.216676E+09 | 0.729194E+10 | 0.585574E+10 | 0.139009E+11 |
Minimum of Months | 0.220144E+09 | 0.00 | 0.220144E+09 | 212476.46 | 0.323382E+09 |
Maximum of Months | 0.104887E+10 | 95198633.35 | 0.953672E+09 | 0.123278E+10 | 0.257980E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1829554.68 | 0.257997E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 24765434.69 | 0.187308E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.216496E+09 | 0.132353E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.420142E+09 | 0.865603E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.862437E+09 | 0.517461E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.122453E+10 | 0.354513E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123283E+10 | 0.323400E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.101811E+10 | 0.391920E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.587031E+09 | 0.680135E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.217559E+09 | 0.108530E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 49987012.28 | 0.158144E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 212426.80 | 0.232543E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.585593E+10 | 0.139018E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 212426.80 | 0.323400E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123283E+10 | 0.257997E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.324215E+09 | 0.00 | 0.324215E+09 | 1829554.68 | 0.257997E+10 |
February | 0.371263E+09 | 0.00 | 0.371263E+09 | 24765434.69 | 0.187308E+10 |
March | 0.616024E+09 | 0.00 | 0.616024E+09 | 0.216496E+09 | 0.132353E+10 |
April | 0.688218E+09 | 3390773.53 | 0.684827E+09 | 0.420142E+09 | 0.865603E+09 |
May | 0.927363E+09 | 34857017.82 | 0.892506E+09 | 0.862437E+09 | 0.517461E+09 |
June | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.122453E+10 | 0.354513E+09 |
July | 0.101651E+10 | 67992226.61 | 0.948514E+09 | 0.123283E+10 | 0.323400E+09 |
August | 0.851113E+09 | 15083916.13 | 0.836030E+09 | 0.101811E+10 | 0.391920E+09 |
September | 0.631510E+09 | 156584.15 | 0.631353E+09 | 0.587031E+09 | 0.680135E+09 |
October | 0.485190E+09 | 0.00 | 0.485190E+09 | 0.217559E+09 | 0.108530E+10 |
November | 0.328447E+09 | 0.00 | 0.328447E+09 | 49987012.28 | 0.158144E+10 |
December | 0.220152E+09 | 0.00 | 0.220152E+09 | 212426.80 | 0.232543E+10 |
Annual Sum or Average | 0.750891E+10 | 0.216682E+09 | 0.729223E+10 | 0.585593E+10 | 0.139018E+11 |
Minimum of Months | 0.220152E+09 | 0.00 | 0.220152E+09 | 212426.80 | 0.323400E+09 |
Maximum of Months | 0.104891E+10 | 95201192.32 | 0.953710E+09 | 0.123283E+10 | 0.257997E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133661E+10 | 0.550017E+09 | 0.786592E+09 | 0.601306E+09 | 0.451393E+10 |
February | 0.160022E+10 | 0.703645E+09 | 0.896572E+09 | 0.949613E+09 | 0.324543E+10 |
March | 0.240716E+10 | 0.955469E+09 | 0.145169E+10 | 0.190681E+10 | 0.237859E+10 |
April | 0.286041E+10 | 0.125266E+10 | 0.160775E+10 | 0.281025E+10 | 0.165063E+10 |
May | 0.371220E+10 | 0.162206E+10 | 0.209014E+10 | 0.421685E+10 | 0.105802E+10 |
June | 0.395339E+10 | 0.172163E+10 | 0.223176E+10 | 0.496653E+10 | 0.717873E+09 |
July | 0.412906E+10 | 0.190524E+10 | 0.222383E+10 | 0.530022E+10 | 0.655815E+09 |
August | 0.348072E+10 | 0.150061E+10 | 0.198011E+10 | 0.446562E+10 | 0.778858E+09 |
September | 0.300435E+10 | 0.141970E+10 | 0.158464E+10 | 0.353954E+10 | 0.129982E+10 |
October | 0.197840E+10 | 0.826358E+09 | 0.115204E+10 | 0.171805E+10 | 0.201445E+10 |
November | 0.112962E+10 | 0.366919E+09 | 0.762698E+09 | 0.585579E+09 | 0.285263E+10 |
December | 0.904179E+09 | 0.388275E+09 | 0.515904E+09 | 0.410565E+09 | 0.415678E+10 |
Annual Sum or Average | 0.304963E+11 | 0.132126E+11 | 0.172837E+11 | 0.314709E+11 | 0.253228E+11 |
Minimum of Months | 0.904179E+09 | 0.366919E+09 | 0.515904E+09 | 0.410565E+09 | 0.655815E+09 |
Maximum of Months | 0.412906E+10 | 0.190524E+10 | 0.223176E+10 | 0.530022E+10 | 0.451393E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52848333.44 | 21747177.24 | 31101156.20 | 23775115.31 | 0.178477E+09 |
February | 63271121.83 | 27821483.10 | 35449638.73 | 37546860.60 | 0.128322E+09 |
March | 95176819.75 | 37778372.49 | 57398447.26 | 75393412.83 | 94047184.07 |
April | 0.113098E+09 | 49529090.55 | 63569016.08 | 0.111115E+09 | 65264383.47 |
May | 0.146777E+09 | 64134625.01 | 82642305.37 | 0.166731E+09 | 41833244.20 |
June | 0.156314E+09 | 68071882.56 | 88241725.46 | 0.196372E+09 | 28384033.77 |
July | 0.163259E+09 | 75331340.01 | 87928116.42 | 0.209566E+09 | 25930345.10 |
August | 0.137625E+09 | 59332787.70 | 78291826.23 | 0.176566E+09 | 30795332.81 |
September | 0.118789E+09 | 56133846.95 | 62655254.45 | 0.139950E+09 | 51393785.15 |
October | 78223966.07 | 32673432.69 | 45550533.38 | 67930190.08 | 79649413.69 |
November | 44664048.95 | 14507661.16 | 30156387.79 | 23153286.04 | 0.112791E+09 |
December | 35750404.86 | 15352039.08 | 20398365.78 | 16233368.62 | 0.164356E+09 |
Annual Sum or Average | 0.120580E+10 | 0.522414E+09 | 0.683383E+09 | 0.124433E+10 | 0.100124E+10 |
Minimum of Months | 35750404.86 | 14507661.16 | 20398365.78 | 16233368.62 | 25930345.10 |
Maximum of Months | 0.163259E+09 | 75331340.01 | 88241725.46 | 0.209566E+09 | 0.178477E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.185231E+10 | 0.208228E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.186227E+10 | 0.155062E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188125E+10 | 0.124817E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182243E+10 | 0.900992E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166076E+10 | 0.574753E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.171811E+10 | 0.383308E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.194883E+10 | 0.353438E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222047E+10 | 0.432941E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242113E+10 | 0.705986E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228306E+10 | 0.107450E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.142614E+10 | 0.141712E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160498E+10 | 0.198965E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227017E+11 | 0.127138E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.142614E+10 | 0.353438E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242113E+10 | 0.208228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201627E+10 | 0.137977E+10 | 0.636494E+09 | 0.185231E+10 | 0.208228E+10 |
February | 0.195132E+10 | 0.131833E+10 | 0.632997E+09 | 0.186227E+10 | 0.155062E+10 |
March | 0.188003E+10 | 0.989958E+09 | 0.890072E+09 | 0.188125E+10 | 0.124817E+10 |
April | 0.163915E+10 | 0.766329E+09 | 0.872818E+09 | 0.182243E+10 | 0.900992E+09 |
May | 0.140325E+10 | 0.380436E+09 | 0.102281E+10 | 0.166076E+10 | 0.574753E+09 |
June | 0.131839E+10 | 0.268430E+09 | 0.104996E+10 | 0.171811E+10 | 0.383308E+09 |
July | 0.144213E+10 | 0.363376E+09 | 0.107876E+10 | 0.194883E+10 | 0.353438E+09 |
August | 0.162480E+10 | 0.582689E+09 | 0.104211E+10 | 0.222047E+10 | 0.432941E+09 |
September | 0.190540E+10 | 0.100398E+10 | 0.901415E+09 | 0.242113E+10 | 0.705986E+09 |
October | 0.205596E+10 | 0.128982E+10 | 0.766136E+09 | 0.228306E+10 | 0.107450E+10 |
November | 0.150117E+10 | 0.939761E+09 | 0.561413E+09 | 0.142614E+10 | 0.141712E+10 |
December | 0.165414E+10 | 0.125299E+10 | 0.401152E+09 | 0.160498E+10 | 0.198965E+10 |
Annual Sum or Average | 0.203920E+11 | 0.105359E+11 | 0.985614E+10 | 0.227017E+11 | 0.127138E+11 |
Minimum of Months | 0.131839E+10 | 0.268430E+09 | 0.401152E+09 | 0.142614E+10 | 0.353438E+09 |
Maximum of Months | 0.205596E+10 | 0.137977E+10 | 0.107876E+10 | 0.242113E+10 | 0.208228E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201614E+10 | 0.137968E+10 | 0.636454E+09 | 0.185219E+10 | 0.208215E+10 |
February | 0.195120E+10 | 0.131824E+10 | 0.632957E+09 | 0.186215E+10 | 0.155053E+10 |
March | 0.187991E+10 | 0.989895E+09 | 0.890015E+09 | 0.188113E+10 | 0.124809E+10 |
April | 0.163904E+10 | 0.766281E+09 | 0.872762E+09 | 0.182231E+10 | 0.900935E+09 |
May | 0.140316E+10 | 0.380412E+09 | 0.102275E+10 | 0.166065E+10 | 0.574717E+09 |
June | 0.131831E+10 | 0.268413E+09 | 0.104990E+10 | 0.171800E+10 | 0.383283E+09 |
July | 0.144204E+10 | 0.363353E+09 | 0.107869E+10 | 0.194870E+10 | 0.353416E+09 |
August | 0.162470E+10 | 0.582652E+09 | 0.104205E+10 | 0.222033E+10 | 0.432914E+09 |
September | 0.190528E+10 | 0.100392E+10 | 0.901358E+09 | 0.242098E+10 | 0.705941E+09 |
October | 0.205583E+10 | 0.128974E+10 | 0.766088E+09 | 0.228291E+10 | 0.107443E+10 |
November | 0.150108E+10 | 0.939702E+09 | 0.561378E+09 | 0.142605E+10 | 0.141703E+10 |
December | 0.165404E+10 | 0.125291E+10 | 0.401126E+09 | 0.160487E+10 | 0.198952E+10 |
Annual Sum or Average | 0.203907E+11 | 0.105352E+11 | 0.985552E+10 | 0.227003E+11 | 0.127130E+11 |
Minimum of Months | 0.131831E+10 | 0.268413E+09 | 0.401126E+09 | 0.142605E+10 | 0.353416E+09 |
Maximum of Months | 0.205583E+10 | 0.137968E+10 | 0.107869E+10 | 0.242098E+10 | 0.208215E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132559E+10 | 0.536349E+09 | 0.789243E+09 | 0.628269E+09 | 0.461404E+10 |
February | 0.175564E+10 | 0.865125E+09 | 0.890516E+09 | 0.118038E+10 | 0.335580E+10 |
March | 0.232043E+10 | 0.863325E+09 | 0.145711E+10 | 0.181785E+10 | 0.245438E+10 |
April | 0.327563E+10 | 0.161974E+10 | 0.165589E+10 | 0.341887E+10 | 0.173610E+10 |
May | 0.339461E+10 | 0.135606E+10 | 0.203855E+10 | 0.387709E+10 | 0.111384E+10 |
June | 0.385469E+10 | 0.167052E+10 | 0.218416E+10 | 0.487279E+10 | 0.771059E+09 |
July | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.554587E+10 | 0.725373E+09 |
August | 0.373893E+10 | 0.171592E+10 | 0.202301E+10 | 0.486797E+10 | 0.846969E+09 |
September | 0.292893E+10 | 0.139021E+10 | 0.153871E+10 | 0.346630E+10 | 0.135954E+10 |
October | 0.210903E+10 | 0.937648E+09 | 0.117138E+10 | 0.194798E+10 | 0.209913E+10 |
November | 0.122167E+10 | 0.451772E+09 | 0.769899E+09 | 0.749539E+09 | 0.291938E+10 |
December | 0.970846E+09 | 0.457669E+09 | 0.513176E+09 | 0.539105E+09 | 0.424314E+10 |
Annual Sum or Average | 0.311727E+11 | 0.138958E+11 | 0.172769E+11 | 0.329120E+11 | 0.262388E+11 |
Minimum of Months | 0.970846E+09 | 0.451772E+09 | 0.513176E+09 | 0.539105E+09 | 0.725373E+09 |
Maximum of Months | 0.427672E+10 | 0.203150E+10 | 0.224522E+10 | 0.554587E+10 | 0.461404E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52412564.45 | 21206694.15 | 31205870.30 | 24841069.20 | 0.182435E+09 |
February | 69416280.03 | 34206148.70 | 35210131.33 | 46670822.84 | 0.132685E+09 |
March | 91747546.41 | 34134985.47 | 57612560.94 | 71875812.84 | 97044113.36 |
April | 0.129515E+09 | 64042755.41 | 65472401.82 | 0.135178E+09 | 68643668.26 |
May | 0.134220E+09 | 53617326.43 | 80602273.03 | 0.153296E+09 | 44040305.21 |
June | 0.152410E+09 | 66050663.64 | 86359703.28 | 0.192665E+09 | 30486977.66 |
July | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219278E+09 | 28680570.78 |
August | 0.147833E+09 | 67845650.47 | 79987783.28 | 0.192475E+09 | 33488377.87 |
September | 0.115807E+09 | 54967644.38 | 60839120.57 | 0.137054E+09 | 53755052.05 |
October | 83388869.09 | 37073632.29 | 46315236.80 | 77021166.63 | 82997726.46 |
November | 48303623.31 | 17862585.56 | 30441037.76 | 29635963.27 | 0.115430E+09 |
December | 38386251.97 | 18095774.92 | 20290477.05 | 21315634.87 | 0.167770E+09 |
Annual Sum or Average | 0.123254E+10 | 0.549427E+09 | 0.683110E+09 | 0.130131E+10 | 0.103746E+10 |
Minimum of Months | 38386251.97 | 17862585.56 | 20290477.05 | 21315634.87 | 28680570.78 |
Maximum of Months | 0.169097E+09 | 80323503.52 | 88773639.56 | 0.219278E+09 | 0.182435E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.972653E+09 | 0.00 | 0.972653E+09 | 4158907.45 | 0.787699E+10 |
February | 0.111380E+10 | 0.00 | 0.111380E+10 | 64882234.98 | 0.577043E+10 |
March | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.572909E+09 | 0.415030E+10 |
April | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.113901E+10 | 0.281767E+10 |
May | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.242438E+10 | 0.170237E+10 |
June | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.358182E+10 | 0.113058E+10 |
July | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.363448E+10 | 0.101241E+10 |
August | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.301979E+10 | 0.119722E+10 |
September | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.174217E+10 | 0.204156E+10 |
October | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.642888E+09 | 0.323066E+10 |
November | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.145797E+09 | 0.471677E+10 |
December | 0.660462E+09 | 0.00 | 0.660462E+09 | 506964.68 | 0.701267E+10 |
Annual Sum or Average | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.169728E+11 | 0.426596E+11 |
Minimum of Months | 0.660462E+09 | 0.00 | 0.660462E+09 | 506964.68 | 0.101241E+10 |
Maximum of Months | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.363448E+10 | 0.787699E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.608857E+09 | 0.474182E+10 |
February | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.958571E+09 | 0.342986E+10 |
March | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.190534E+10 | 0.255866E+10 |
April | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.283048E+10 | 0.181624E+10 |
May | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.429830E+10 | 0.115170E+10 |
June | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.510635E+10 | 0.765352E+09 |
July | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.546933E+10 | 0.684054E+09 |
August | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.461262E+10 | 0.800927E+09 |
September | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.366233E+10 | 0.131747E+10 |
October | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.177691E+10 | 0.203503E+10 |
November | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.603152E+09 | 0.292748E+10 |
December | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.420527E+09 | 0.432161E+10 |
Annual Sum or Average | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.322528E+11 | 0.265502E+11 |
Minimum of Months | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.420527E+09 | 0.684054E+09 |
Maximum of Months | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.546933E+10 | 0.474182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.537635E+10 | 0.647161E+10 |
February | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.541472E+10 | 0.477357E+10 |
March | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.546153E+10 | 0.389680E+10 |
April | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.531403E+10 | 0.288000E+10 |
May | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.481899E+10 | 0.186369E+10 |
June | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.505347E+10 | 0.121985E+10 |
July | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.578367E+10 | 0.108633E+10 |
August | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.661866E+10 | 0.128687E+10 |
September | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.722374E+10 | 0.206853E+10 |
October | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.679530E+10 | 0.311425E+10 |
November | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.421104E+10 | 0.421220E+10 |
December | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.472387E+10 | 0.606584E+10 |
Annual Sum or Average | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.667954E+11 | 0.389395E+11 |
Minimum of Months | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.421104E+10 | 0.108633E+10 |
Maximum of Months | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.722374E+10 | 0.647161E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.633088E+09 | 0.485961E+10 |
February | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.119250E+10 | 0.355239E+10 |
March | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.181616E+10 | 0.263947E+10 |
April | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.347535E+10 | 0.189172E+10 |
May | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.394829E+10 | 0.121950E+10 |
June | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.501760E+10 | 0.822264E+09 |
July | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573544E+10 | 0.748724E+09 |
August | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.503930E+10 | 0.863252E+09 |
September | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.359239E+10 | 0.137870E+10 |
October | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.201883E+10 | 0.212172E+10 |
November | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.773034E+09 | 0.299628E+10 |
December | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.548773E+09 | 0.442006E+10 |
Annual Sum or Average | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.337908E+11 | 0.275137E+11 |
Minimum of Months | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.548773E+09 | 0.748724E+09 |
Maximum of Months | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.573544E+10 | 0.485961E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.88 | 2883.10 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 30.70 | 2307.41 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 224.83 | 1480.50 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 449.61 | 1024.74 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 913.75 | 609.78 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1384.44 | 420.21 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1356.26 | 366.72 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1129.63 | 430.38 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 683.40 | 743.09 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 264.29 | 1116.77 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 66.43 | 1720.58 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.49 | 2535.78 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 545.21 | 1298.58 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.49 | 366.72 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1384.44 | 2883.10 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 230.23 | 1738.22 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 403.60 | 1371.36 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 724.73 | 911.82 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1102.09 | 662.16 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1610.28 | 414.38 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1973.16 | 284.61 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2043.00 | 248.01 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1725.13 | 288.61 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1421.72 | 482.01 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 686.56 | 705.42 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 245.55 | 1069.15 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 161.07 | 1565.24 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1030.65 | 809.20 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 161.07 | 248.01 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2043.00 | 1738.22 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2017.96 | 2359.26 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2253.99 | 1900.18 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2053.78 | 1387.85 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2058.34 | 1050.07 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1802.27 | 667.57 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1949.06 | 452.07 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2156.26 | 392.57 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2469.32 | 462.38 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2794.11 | 756.67 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2561.20 | 1083.06 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1648.39 | 1536.44 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1776.41 | 2187.26 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2127.57 | 1183.02 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1648.39 | 392.57 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2794.11 | 2359.26 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 237.90 | 1778.97 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 497.34 | 1419.90 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 686.15 | 940.54 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1346.14 | 688.78 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1476.79 | 436.44 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1935.13 | 304.94 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2138.90 | 270.64 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1880.35 | 310.31 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1392.16 | 503.14 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 769.93 | 734.69 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 308.37 | 1093.89 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 207.72 | 1598.66 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1075.92 | 837.42 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 207.72 | 270.64 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2138.90 | 1778.97 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.05 | 2889.68 | 363.14 | 0.00 | 363.14 | 0.00 | 0.00 |
February | 30.71 | 2322.71 | 460.39 | 0.00 | 460.39 | 0.00 | 0.00 |
March | 242.49 | 1482.41 | 689.98 | 0.00 | 689.98 | 0.00 | 0.00 |
April | 486.27 | 1001.83 | 796.54 | 3.92 | 792.61 | 0.00 | 0.00 |
May | 965.98 | 579.58 | 1038.70 | 39.04 | 999.66 | 0.00 | 0.00 |
June | 1417.26 | 410.31 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
July | 1380.84 | 362.22 | 1138.54 | 76.16 | 1062.39 | 0.00 | 0.00 |
August | 1140.34 | 438.97 | 953.30 | 16.89 | 936.40 | 0.00 | 0.00 |
September | 679.43 | 787.18 | 730.90 | 0.18 | 730.72 | 0.00 | 0.00 |
October | 243.68 | 1215.59 | 543.44 | 0.00 | 543.44 | 0.00 | 0.00 |
November | 57.86 | 1830.33 | 380.14 | 0.00 | 380.14 | 0.00 | 0.00 |
December | 0.24 | 2604.59 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Annual Sum or Average | 557.07 | 1322.44 | 714.31 | 20.61 | 693.70 | 0.00 | 0.00 |
Minimum of Months | 0.24 | 362.22 | 246.58 | 0.00 | 246.58 | 0.00 | 0.00 |
Maximum of Months | 1417.26 | 2889.68 | 1214.00 | 110.19 | 1103.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 233.38 | 1751.94 | 518.76 | 213.47 | 305.29 | 0.00 | 0.00 |
February | 408.05 | 1394.58 | 687.62 | 302.36 | 385.26 | 0.00 | 0.00 |
March | 740.07 | 923.18 | 934.26 | 370.84 | 563.43 | 0.00 | 0.00 |
April | 1127.07 | 662.00 | 1147.19 | 502.39 | 644.80 | 0.00 | 0.00 |
May | 1636.64 | 410.64 | 1440.78 | 629.55 | 811.22 | 0.00 | 0.00 |
June | 1991.86 | 287.91 | 1585.54 | 690.47 | 895.06 | 0.00 | 0.00 |
July | 2057.12 | 254.53 | 1602.57 | 739.46 | 863.11 | 0.00 | 0.00 |
August | 1733.19 | 302.29 | 1350.94 | 582.42 | 768.52 | 0.00 | 0.00 |
September | 1419.56 | 521.30 | 1204.91 | 569.38 | 635.53 | 0.00 | 0.00 |
October | 666.81 | 781.85 | 767.85 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 234.85 | 1144.07 | 453.04 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 159.35 | 1613.33 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1037.39 | 834.73 | 1005.27 | 435.53 | 569.73 | 0.00 | 0.00 |
Minimum of Months | 159.35 | 254.53 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2057.12 | 1751.94 | 1602.57 | 739.46 | 895.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2074.67 | 2332.25 | 2258.31 | 1545.41 | 712.90 | 0.00 | 0.00 |
February | 2309.31 | 1922.86 | 2419.74 | 1634.79 | 784.95 | 0.00 | 0.00 |
March | 2107.09 | 1398.01 | 2105.72 | 1108.80 | 996.92 | 0.00 | 0.00 |
April | 2109.25 | 1042.79 | 1897.12 | 886.94 | 1010.18 | 0.00 | 0.00 |
May | 1860.13 | 643.75 | 1571.70 | 426.11 | 1145.60 | 0.00 | 0.00 |
June | 1988.51 | 443.63 | 1525.89 | 310.68 | 1215.21 | 0.00 | 0.00 |
July | 2182.78 | 395.87 | 1615.26 | 407.00 | 1208.26 | 0.00 | 0.00 |
August | 2487.03 | 484.91 | 1819.86 | 652.64 | 1167.22 | 0.00 | 0.00 |
September | 2802.17 | 817.10 | 2205.28 | 1161.99 | 1043.28 | 0.00 | 0.00 |
October | 2557.13 | 1203.49 | 2302.77 | 1444.66 | 858.11 | 0.00 | 0.00 |
November | 1650.59 | 1640.15 | 1737.43 | 1087.66 | 649.77 | 0.00 | 0.00 |
December | 1797.65 | 2228.50 | 1852.72 | 1403.41 | 449.31 | 0.00 | 0.00 |
Annual Sum or Average | 2159.55 | 1209.43 | 1939.84 | 1002.25 | 937.59 | 0.00 | 0.00 |
Minimum of Months | 1650.59 | 395.87 | 1525.89 | 310.68 | 449.31 | 0.00 | 0.00 |
Maximum of Months | 2802.17 | 2332.25 | 2419.74 | 1634.79 | 1215.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.84 | 1790.80 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 507.21 | 1442.00 | 754.41 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 705.54 | 952.59 | 900.60 | 335.07 | 565.53 | 0.00 | 0.00 |
April | 1371.16 | 696.27 | 1313.71 | 649.61 | 664.11 | 0.00 | 0.00 |
May | 1504.77 | 432.30 | 1317.52 | 526.31 | 791.20 | 0.00 | 0.00 |
June | 1954.26 | 309.24 | 1545.95 | 669.97 | 875.97 | 0.00 | 0.00 |
July | 2152.46 | 281.53 | 1659.88 | 788.47 | 871.41 | 0.00 | 0.00 |
August | 1889.35 | 328.73 | 1451.15 | 665.98 | 785.17 | 0.00 | 0.00 |
September | 1390.18 | 545.25 | 1174.67 | 557.55 | 617.11 | 0.00 | 0.00 |
October | 756.05 | 814.71 | 818.55 | 363.92 | 454.64 | 0.00 | 0.00 |
November | 300.61 | 1170.84 | 489.96 | 181.19 | 308.77 | 0.00 | 0.00 |
December | 209.24 | 1646.85 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Annual Sum or Average | 1084.90 | 864.92 | 1027.56 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 209.24 | 281.53 | 376.80 | 177.63 | 199.17 | 0.00 | 0.00 |
Maximum of Months | 2152.46 | 1790.80 | 1659.88 | 788.47 | 875.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.55 | 2940.93 | 363.15 | 0.00 | 363.15 | 0.00 | 0.00 |
February | 26.82 | 2385.26 | 460.40 | 0.00 | 460.40 | 0.00 | 0.00 |
March | 213.90 | 1549.54 | 690.00 | 0.00 | 690.00 | 0.00 | 0.00 |
April | 439.43 | 1087.07 | 796.55 | 3.92 | 792.63 | 0.00 | 0.00 |
May | 905.16 | 635.59 | 1038.72 | 39.04 | 999.68 | 0.00 | 0.00 |
June | 1381.88 | 436.18 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
July | 1356.96 | 377.99 | 1138.57 | 76.16 | 1062.41 | 0.00 | 0.00 |
August | 1127.46 | 446.99 | 953.32 | 16.90 | 936.42 | 0.00 | 0.00 |
September | 672.13 | 787.64 | 730.92 | 0.18 | 730.74 | 0.00 | 0.00 |
October | 240.03 | 1206.19 | 543.45 | 0.00 | 543.45 | 0.00 | 0.00 |
November | 56.25 | 1819.74 | 380.15 | 0.00 | 380.15 | 0.00 | 0.00 |
December | 0.19 | 2618.23 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Annual Sum or Average | 538.20 | 1352.73 | 714.32 | 20.61 | 693.71 | 0.00 | 0.00 |
Minimum of Months | 0.19 | 377.99 | 246.59 | 0.00 | 246.59 | 0.00 | 0.00 |
Maximum of Months | 1381.88 | 2940.93 | 1214.03 | 110.19 | 1103.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 227.32 | 1770.39 | 518.77 | 213.48 | 305.30 | 0.00 | 0.00 |
February | 396.23 | 1417.77 | 687.63 | 302.36 | 385.27 | 0.00 | 0.00 |
March | 711.37 | 955.30 | 934.28 | 370.84 | 563.44 | 0.00 | 0.00 |
April | 1092.01 | 700.71 | 1147.21 | 502.40 | 644.81 | 0.00 | 0.00 |
May | 1604.80 | 430.00 | 1440.80 | 629.56 | 811.23 | 0.00 | 0.00 |
June | 1970.04 | 295.27 | 1585.56 | 690.49 | 895.07 | 0.00 | 0.00 |
July | 2042.01 | 255.40 | 1602.59 | 739.47 | 863.12 | 0.00 | 0.00 |
August | 1722.15 | 299.03 | 1350.96 | 582.43 | 768.53 | 0.00 | 0.00 |
September | 1412.94 | 508.28 | 1204.93 | 569.39 | 635.54 | 0.00 | 0.00 |
October | 663.42 | 759.79 | 767.87 | 320.73 | 447.13 | 0.00 | 0.00 |
November | 232.70 | 1129.43 | 453.05 | 147.16 | 305.89 | 0.00 | 0.00 |
December | 157.01 | 1613.50 | 350.93 | 150.70 | 200.23 | 0.00 | 0.00 |
Annual Sum or Average | 1022.73 | 841.90 | 1005.28 | 435.54 | 569.74 | 0.00 | 0.00 |
Minimum of Months | 157.01 | 255.40 | 350.93 | 147.16 | 200.23 | 0.00 | 0.00 |
Maximum of Months | 2042.01 | 1770.39 | 1602.59 | 739.47 | 895.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2007.30 | 2416.22 | 2258.40 | 1545.48 | 712.93 | 0.00 | 0.00 |
February | 2238.23 | 1973.20 | 2419.84 | 1634.86 | 784.98 | 0.00 | 0.00 |
March | 2039.10 | 1454.90 | 2105.80 | 1108.85 | 996.96 | 0.00 | 0.00 |
April | 2050.17 | 1111.11 | 1897.19 | 886.97 | 1010.22 | 0.00 | 0.00 |
May | 1799.20 | 695.82 | 1571.76 | 426.12 | 1145.63 | 0.00 | 0.00 |
June | 1949.64 | 470.62 | 1525.94 | 310.69 | 1215.25 | 0.00 | 0.00 |
July | 2159.37 | 405.59 | 1615.31 | 407.02 | 1208.30 | 0.00 | 0.00 |
August | 2471.12 | 480.46 | 1819.92 | 652.67 | 1167.25 | 0.00 | 0.00 |
September | 2786.94 | 798.04 | 2205.36 | 1162.04 | 1043.32 | 0.00 | 0.00 |
October | 2537.07 | 1162.73 | 2302.86 | 1444.72 | 858.14 | 0.00 | 0.00 |
November | 1624.63 | 1625.08 | 1737.50 | 1087.71 | 649.79 | 0.00 | 0.00 |
December | 1763.69 | 2264.73 | 1852.79 | 1403.47 | 449.32 | 0.00 | 0.00 |
Annual Sum or Average | 2118.07 | 1234.76 | 1939.91 | 1002.29 | 937.62 | 0.00 | 0.00 |
Minimum of Months | 1624.63 | 405.59 | 1525.94 | 310.69 | 449.32 | 0.00 | 0.00 |
Maximum of Months | 2786.94 | 2416.22 | 2419.84 | 1634.86 | 1215.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.37 | 1814.37 | 514.49 | 208.17 | 306.32 | 0.00 | 0.00 |
February | 492.93 | 1468.41 | 754.42 | 371.75 | 382.66 | 0.00 | 0.00 |
March | 678.08 | 985.46 | 900.62 | 335.08 | 565.54 | 0.00 | 0.00 |
April | 1340.80 | 729.83 | 1313.73 | 649.62 | 664.11 | 0.00 | 0.00 |
May | 1474.12 | 455.31 | 1317.53 | 526.32 | 791.21 | 0.00 | 0.00 |
June | 1935.80 | 317.23 | 1545.97 | 669.98 | 875.98 | 0.00 | 0.00 |
July | 2141.37 | 279.54 | 1659.90 | 788.48 | 871.42 | 0.00 | 0.00 |
August | 1881.46 | 322.30 | 1451.17 | 665.99 | 785.18 | 0.00 | 0.00 |
September | 1385.95 | 531.90 | 1174.68 | 557.56 | 617.12 | 0.00 | 0.00 |
October | 753.75 | 792.16 | 818.57 | 363.93 | 454.64 | 0.00 | 0.00 |
November | 298.24 | 1155.97 | 489.97 | 181.19 | 308.78 | 0.00 | 0.00 |
December | 204.89 | 1650.26 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Annual Sum or Average | 1071.50 | 872.45 | 1027.58 | 458.06 | 569.51 | 0.00 | 0.00 |
Minimum of Months | 204.89 | 279.54 | 376.81 | 177.63 | 199.18 | 0.00 | 0.00 |
Maximum of Months | 2141.37 | 1814.37 | 1659.90 | 788.48 | 875.98 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5032677.72 | 0.772210E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 74262018.65 | 0.558208E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.602197E+09 | 0.396538E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.116540E+10 | 0.265613E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.244739E+10 | 0.163325E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.358848E+10 | 0.108918E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.363262E+10 | 0.982228E+09 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.302559E+10 | 0.115273E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.177138E+10 | 0.192609E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.707862E+09 | 0.299114E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.172199E+09 | 0.445974E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 1304893.01 | 0.679183E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171937E+11 | 0.409519E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 1304893.01 | 0.982228E+09 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363262E+10 | 0.772210E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.616658E+09 | 0.465564E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.976379E+09 | 0.331761E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.194111E+10 | 0.244222E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.285662E+10 | 0.171633E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.431298E+10 | 0.110987E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.511443E+10 | 0.737701E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.547196E+10 | 0.664279E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.462060E+10 | 0.773007E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.368509E+10 | 0.124936E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.183888E+10 | 0.188941E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.636466E+09 | 0.277124E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.431404E+09 | 0.419233E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.325026E+11 | 0.255190E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.431404E+09 | 0.664279E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.547196E+10 | 0.465564E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.540490E+10 | 0.631904E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.545285E+10 | 0.459692E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.550085E+10 | 0.371722E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.533521E+10 | 0.272179E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.482721E+10 | 0.178801E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.505198E+10 | 0.117176E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.577532E+10 | 0.105147E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.661382E+10 | 0.123844E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.724234E+10 | 0.196129E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.685993E+10 | 0.290088E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.427262E+10 | 0.398245E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.475795E+10 | 0.585837E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.670950E+11 | 0.373077E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.427262E+10 | 0.105147E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.724234E+10 | 0.631904E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.637188E+09 | 0.476479E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.120316E+10 | 0.343502E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.183779E+10 | 0.251915E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.348920E+10 | 0.178531E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.395543E+10 | 0.116895E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.501586E+10 | 0.790402E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.572884E+10 | 0.724879E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.503632E+10 | 0.831125E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.360848E+10 | 0.130414E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.206219E+10 | 0.196780E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.799286E+09 | 0.283536E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.556370E+09 | 0.428186E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339301E+11 | 0.264088E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.556370E+09 | 0.724879E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.572884E+10 | 0.476479E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5489063.18 | 0.773973E+10 | 0.972632E+09 | 0.00 | 0.972632E+09 | 0.00 | 0.00 |
February | 74297311.60 | 0.561911E+10 | 0.111377E+10 | 0.00 | 0.111377E+10 | 0.00 | 0.00 |
March | 0.649488E+09 | 0.397049E+10 | 0.184805E+10 | 0.00 | 0.184805E+10 | 0.00 | 0.00 |
April | 0.126041E+10 | 0.259675E+10 | 0.206463E+10 | 10172229.45 | 0.205445E+10 | 0.00 | 0.00 |
May | 0.258728E+10 | 0.155235E+10 | 0.278205E+10 | 0.104570E+09 | 0.267748E+10 | 0.00 | 0.00 |
June | 0.367354E+10 | 0.106352E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
July | 0.369845E+10 | 0.970181E+09 | 0.304948E+10 | 0.203975E+09 | 0.284550E+10 | 0.00 | 0.00 |
August | 0.305430E+10 | 0.117574E+10 | 0.255331E+10 | 45251342.94 | 0.250806E+10 | 0.00 | 0.00 |
September | 0.176107E+10 | 0.204036E+10 | 0.189450E+10 | 469748.23 | 0.189403E+10 | 0.00 | 0.00 |
October | 0.652675E+09 | 0.325583E+10 | 0.145555E+10 | 0.00 | 0.145555E+10 | 0.00 | 0.00 |
November | 0.149962E+09 | 0.474422E+10 | 0.985328E+09 | 0.00 | 0.985328E+09 | 0.00 | 0.00 |
December | 637330.05 | 0.697614E+10 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175676E+11 | 0.417044E+11 | 0.225264E+11 | 0.650039E+09 | 0.218764E+11 | 0.00 | 0.00 |
Minimum of Months | 637330.05 | 0.970181E+09 | 0.660448E+09 | 0.00 | 0.660448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.369845E+10 | 0.773973E+10 | 0.314669E+10 | 0.285601E+09 | 0.286109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.625082E+09 | 0.469241E+10 | 0.138946E+10 | 0.571764E+09 | 0.817694E+09 | 0.00 | 0.00 |
February | 0.987160E+09 | 0.337376E+10 | 0.166349E+10 | 0.731466E+09 | 0.932021E+09 | 0.00 | 0.00 |
March | 0.198220E+10 | 0.247263E+10 | 0.250233E+10 | 0.993247E+09 | 0.150909E+10 | 0.00 | 0.00 |
April | 0.292136E+10 | 0.171589E+10 | 0.297351E+10 | 0.130219E+10 | 0.167132E+10 | 0.00 | 0.00 |
May | 0.438358E+10 | 0.109986E+10 | 0.385897E+10 | 0.168619E+10 | 0.217278E+10 | 0.00 | 0.00 |
June | 0.516291E+10 | 0.746257E+09 | 0.410971E+10 | 0.178971E+10 | 0.232000E+10 | 0.00 | 0.00 |
July | 0.550978E+10 | 0.681746E+09 | 0.429232E+10 | 0.198057E+10 | 0.231176E+10 | 0.00 | 0.00 |
August | 0.464218E+10 | 0.809653E+09 | 0.361835E+10 | 0.155994E+10 | 0.205840E+10 | 0.00 | 0.00 |
September | 0.367949E+10 | 0.135122E+10 | 0.312313E+10 | 0.147584E+10 | 0.164730E+10 | 0.00 | 0.00 |
October | 0.178598E+10 | 0.209410E+10 | 0.205662E+10 | 0.859031E+09 | 0.119759E+10 | 0.00 | 0.00 |
November | 0.608733E+09 | 0.296542E+10 | 0.117428E+10 | 0.381427E+09 | 0.792854E+09 | 0.00 | 0.00 |
December | 0.426798E+09 | 0.432114E+10 | 0.939929E+09 | 0.403627E+09 | 0.536302E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327153E+11 | 0.263241E+11 | 0.317021E+11 | 0.137350E+11 | 0.179671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426798E+09 | 0.681746E+09 | 0.939929E+09 | 0.381427E+09 | 0.536302E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550978E+10 | 0.469241E+10 | 0.429232E+10 | 0.198057E+10 | 0.232000E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.555680E+10 | 0.624671E+10 | 0.604867E+10 | 0.413923E+10 | 0.190944E+10 | 0.00 | 0.00 |
February | 0.558669E+10 | 0.465177E+10 | 0.585385E+10 | 0.395490E+10 | 0.189895E+10 | 0.00 | 0.00 |
March | 0.564362E+10 | 0.374444E+10 | 0.563997E+10 | 0.296981E+10 | 0.267016E+10 | 0.00 | 0.00 |
April | 0.546717E+10 | 0.270292E+10 | 0.491734E+10 | 0.229894E+10 | 0.261840E+10 | 0.00 | 0.00 |
May | 0.498216E+10 | 0.172422E+10 | 0.420965E+10 | 0.114128E+10 | 0.306837E+10 | 0.00 | 0.00 |
June | 0.515421E+10 | 0.114990E+10 | 0.395510E+10 | 0.805273E+09 | 0.314983E+10 | 0.00 | 0.00 |
July | 0.584635E+10 | 0.106029E+10 | 0.432631E+10 | 0.109011E+10 | 0.323620E+10 | 0.00 | 0.00 |
August | 0.666127E+10 | 0.129880E+10 | 0.487430E+10 | 0.174803E+10 | 0.312627E+10 | 0.00 | 0.00 |
September | 0.726323E+10 | 0.211791E+10 | 0.571608E+10 | 0.301189E+10 | 0.270419E+10 | 0.00 | 0.00 |
October | 0.684902E+10 | 0.322342E+10 | 0.616774E+10 | 0.386938E+10 | 0.229836E+10 | 0.00 | 0.00 |
November | 0.427834E+10 | 0.425128E+10 | 0.450343E+10 | 0.281922E+10 | 0.168420E+10 | 0.00 | 0.00 |
December | 0.481483E+10 | 0.596882E+10 | 0.496233E+10 | 0.375890E+10 | 0.120343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.681037E+11 | 0.381405E+11 | 0.611747E+11 | 0.316070E+11 | 0.295678E+11 | 0.00 | 0.00 |
Minimum of Months | 0.427834E+10 | 0.106029E+10 | 0.395510E+10 | 0.805273E+09 | 0.120343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.726323E+10 | 0.624671E+10 | 0.616774E+10 | 0.413923E+10 | 0.323620E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.653111E+09 | 0.479647E+10 | 0.137800E+10 | 0.557556E+09 | 0.820449E+09 | 0.00 | 0.00 |
February | 0.122705E+10 | 0.348849E+10 | 0.182506E+10 | 0.899331E+09 | 0.925726E+09 | 0.00 | 0.00 |
March | 0.188972E+10 | 0.255143E+10 | 0.241218E+10 | 0.897460E+09 | 0.151472E+10 | 0.00 | 0.00 |
April | 0.355404E+10 | 0.180474E+10 | 0.340515E+10 | 0.168378E+10 | 0.172137E+10 | 0.00 | 0.00 |
May | 0.403039E+10 | 0.115788E+10 | 0.352883E+10 | 0.140968E+10 | 0.211915E+10 | 0.00 | 0.00 |
June | 0.506545E+10 | 0.801546E+09 | 0.400710E+10 | 0.173657E+10 | 0.227052E+10 | 0.00 | 0.00 |
July | 0.576514E+10 | 0.754053E+09 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
August | 0.506044E+10 | 0.880457E+09 | 0.388676E+10 | 0.178376E+10 | 0.210300E+10 | 0.00 | 0.00 |
September | 0.360336E+10 | 0.141330E+10 | 0.304473E+10 | 0.144518E+10 | 0.159955E+10 | 0.00 | 0.00 |
October | 0.202500E+10 | 0.218213E+10 | 0.219242E+10 | 0.974722E+09 | 0.121770E+10 | 0.00 | 0.00 |
November | 0.779175E+09 | 0.303481E+10 | 0.126997E+10 | 0.469634E+09 | 0.800340E+09 | 0.00 | 0.00 |
December | 0.560421E+09 | 0.441091E+10 | 0.100923E+10 | 0.475765E+09 | 0.533467E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.342133E+11 | 0.272762E+11 | 0.324052E+11 | 0.144453E+11 | 0.179600E+11 | 0.00 | 0.00 |
Minimum of Months | 0.560421E+09 | 0.754053E+09 | 0.100923E+10 | 0.469634E+09 | 0.533467E+09 | 0.00 | 0.00 |
Maximum of Months | 0.576514E+10 | 0.479647E+10 | 0.444582E+10 | 0.211183E+10 | 0.233399E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4158907.45 | 0.787699E+10 | 0.972653E+09 | 0.00 | 0.972653E+09 | 0.00 | 0.00 |
February | 64882234.98 | 0.577043E+10 | 0.111380E+10 | 0.00 | 0.111380E+10 | 0.00 | 0.00 |
March | 0.572909E+09 | 0.415030E+10 | 0.184809E+10 | 0.00 | 0.184809E+10 | 0.00 | 0.00 |
April | 0.113901E+10 | 0.281767E+10 | 0.206467E+10 | 10172528.45 | 0.205450E+10 | 0.00 | 0.00 |
May | 0.242438E+10 | 0.170237E+10 | 0.278211E+10 | 0.104573E+09 | 0.267754E+10 | 0.00 | 0.00 |
June | 0.358182E+10 | 0.113058E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
July | 0.363448E+10 | 0.101241E+10 | 0.304954E+10 | 0.203981E+09 | 0.284556E+10 | 0.00 | 0.00 |
August | 0.301979E+10 | 0.119722E+10 | 0.255336E+10 | 45252673.04 | 0.250811E+10 | 0.00 | 0.00 |
September | 0.174217E+10 | 0.204156E+10 | 0.189454E+10 | 469762.04 | 0.189407E+10 | 0.00 | 0.00 |
October | 0.642888E+09 | 0.323066E+10 | 0.145558E+10 | 0.00 | 0.145558E+10 | 0.00 | 0.00 |
November | 0.145797E+09 | 0.471677E+10 | 0.985350E+09 | 0.00 | 0.985350E+09 | 0.00 | 0.00 |
December | 506964.68 | 0.701267E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169728E+11 | 0.426596E+11 | 0.225269E+11 | 0.650058E+09 | 0.218769E+11 | 0.00 | 0.00 |
Minimum of Months | 506964.68 | 0.101241E+10 | 0.660462E+09 | 0.00 | 0.660462E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363448E+10 | 0.787699E+10 | 0.314676E+10 | 0.285609E+09 | 0.286115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.608857E+09 | 0.474182E+10 | 0.138948E+10 | 0.571775E+09 | 0.817705E+09 | 0.00 | 0.00 |
February | 0.958571E+09 | 0.342986E+10 | 0.166351E+10 | 0.731481E+09 | 0.932034E+09 | 0.00 | 0.00 |
March | 0.190534E+10 | 0.255866E+10 | 0.250237E+10 | 0.993267E+09 | 0.150911E+10 | 0.00 | 0.00 |
April | 0.283048E+10 | 0.181624E+10 | 0.297356E+10 | 0.130222E+10 | 0.167134E+10 | 0.00 | 0.00 |
May | 0.429830E+10 | 0.115170E+10 | 0.385903E+10 | 0.168622E+10 | 0.217281E+10 | 0.00 | 0.00 |
June | 0.510635E+10 | 0.765352E+09 | 0.410977E+10 | 0.178974E+10 | 0.232003E+10 | 0.00 | 0.00 |
July | 0.546933E+10 | 0.684054E+09 | 0.429239E+10 | 0.198061E+10 | 0.231178E+10 | 0.00 | 0.00 |
August | 0.461262E+10 | 0.800927E+09 | 0.361840E+10 | 0.155997E+10 | 0.205843E+10 | 0.00 | 0.00 |
September | 0.366233E+10 | 0.131747E+10 | 0.312318E+10 | 0.147587E+10 | 0.164732E+10 | 0.00 | 0.00 |
October | 0.177691E+10 | 0.203503E+10 | 0.205665E+10 | 0.859048E+09 | 0.119760E+10 | 0.00 | 0.00 |
November | 0.603152E+09 | 0.292748E+10 | 0.117430E+10 | 0.381434E+09 | 0.792865E+09 | 0.00 | 0.00 |
December | 0.420527E+09 | 0.432161E+10 | 0.939944E+09 | 0.403635E+09 | 0.536309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.322528E+11 | 0.265502E+11 | 0.317026E+11 | 0.137353E+11 | 0.179673E+11 | 0.00 | 0.00 |
Minimum of Months | 0.420527E+09 | 0.684054E+09 | 0.939944E+09 | 0.381434E+09 | 0.536309E+09 | 0.00 | 0.00 |
Maximum of Months | 0.546933E+10 | 0.474182E+10 | 0.429239E+10 | 0.198061E+10 | 0.232003E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.537635E+10 | 0.647161E+10 | 0.604891E+10 | 0.413940E+10 | 0.190951E+10 | 0.00 | 0.00 |
February | 0.541472E+10 | 0.477357E+10 | 0.585407E+10 | 0.395506E+10 | 0.189902E+10 | 0.00 | 0.00 |
March | 0.546153E+10 | 0.389680E+10 | 0.564018E+10 | 0.296993E+10 | 0.267025E+10 | 0.00 | 0.00 |
April | 0.531403E+10 | 0.288000E+10 | 0.491751E+10 | 0.229903E+10 | 0.261848E+10 | 0.00 | 0.00 |
May | 0.481899E+10 | 0.186369E+10 | 0.420979E+10 | 0.114133E+10 | 0.306846E+10 | 0.00 | 0.00 |
June | 0.505347E+10 | 0.121985E+10 | 0.395523E+10 | 0.805306E+09 | 0.314992E+10 | 0.00 | 0.00 |
July | 0.578367E+10 | 0.108633E+10 | 0.432645E+10 | 0.109015E+10 | 0.323630E+10 | 0.00 | 0.00 |
August | 0.661866E+10 | 0.128687E+10 | 0.487447E+10 | 0.174810E+10 | 0.312637E+10 | 0.00 | 0.00 |
September | 0.722374E+10 | 0.206853E+10 | 0.571629E+10 | 0.301201E+10 | 0.270427E+10 | 0.00 | 0.00 |
October | 0.679530E+10 | 0.311425E+10 | 0.616797E+10 | 0.386954E+10 | 0.229844E+10 | 0.00 | 0.00 |
November | 0.421104E+10 | 0.421220E+10 | 0.450361E+10 | 0.281934E+10 | 0.168426E+10 | 0.00 | 0.00 |
December | 0.472387E+10 | 0.606584E+10 | 0.496252E+10 | 0.375905E+10 | 0.120347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.667954E+11 | 0.389395E+11 | 0.611770E+11 | 0.316083E+11 | 0.295687E+11 | 0.00 | 0.00 |
Minimum of Months | 0.421104E+10 | 0.108633E+10 | 0.395523E+10 | 0.805306E+09 | 0.120347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.722374E+10 | 0.647161E+10 | 0.616797E+10 | 0.413940E+10 | 0.323630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633088E+09 | 0.485961E+10 | 0.137802E+10 | 0.557565E+09 | 0.820458E+09 | 0.00 | 0.00 |
February | 0.119250E+10 | 0.355239E+10 | 0.182508E+10 | 0.899346E+09 | 0.925736E+09 | 0.00 | 0.00 |
March | 0.181616E+10 | 0.263947E+10 | 0.241221E+10 | 0.897475E+09 | 0.151474E+10 | 0.00 | 0.00 |
April | 0.347535E+10 | 0.189172E+10 | 0.340519E+10 | 0.168381E+10 | 0.172138E+10 | 0.00 | 0.00 |
May | 0.394829E+10 | 0.121950E+10 | 0.352888E+10 | 0.140970E+10 | 0.211917E+10 | 0.00 | 0.00 |
June | 0.501760E+10 | 0.822264E+09 | 0.400715E+10 | 0.173660E+10 | 0.227055E+10 | 0.00 | 0.00 |
July | 0.573544E+10 | 0.748724E+09 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
August | 0.503930E+10 | 0.863252E+09 | 0.388681E+10 | 0.178379E+10 | 0.210302E+10 | 0.00 | 0.00 |
September | 0.359239E+10 | 0.137870E+10 | 0.304477E+10 | 0.144521E+10 | 0.159957E+10 | 0.00 | 0.00 |
October | 0.201883E+10 | 0.212172E+10 | 0.219245E+10 | 0.974738E+09 | 0.121771E+10 | 0.00 | 0.00 |
November | 0.773034E+09 | 0.299628E+10 | 0.126999E+10 | 0.469642E+09 | 0.800349E+09 | 0.00 | 0.00 |
December | 0.548773E+09 | 0.442006E+10 | 0.100925E+10 | 0.475773E+09 | 0.533472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.337908E+11 | 0.275137E+11 | 0.324057E+11 | 0.144455E+11 | 0.179602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.548773E+09 | 0.748724E+09 | 0.100925E+10 | 0.469642E+09 | 0.533472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.573544E+10 | 0.485961E+10 | 0.444587E+10 | 0.211186E+10 | 0.233401E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.551932E+10 | -0.526312E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -256205676.8 | 60.05 | 0.00 | 0.00 |
February | 0.510317E+10 | -0.487798E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -225197034.3 | 60.05 | 0.00 | 0.00 |
March | 0.595930E+10 | -0.571793E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -241367268.8 | 60.05 | 0.00 | 0.00 |
April | 0.517998E+10 | -0.495087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229104680.5 | 60.05 | 0.00 | 0.00 |
May | 0.523712E+10 | -0.500407E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233052634.9 | 60.05 | 0.00 | 0.00 |
June | 0.486621E+10 | -0.464127E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224941737.0 | 60.05 | 0.00 | 0.00 |
July | 0.436212E+10 | -0.413070E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231420198.1 | 60.05 | 0.00 | 0.00 |
August | 0.468286E+10 | -0.445094E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231915049.8 | 60.05 | 0.00 | 0.00 |
September | 0.428531E+10 | -0.406062E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224683593.4 | 60.05 | 0.00 | 0.00 |
October | 0.463523E+10 | -0.440059E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234645596.4 | 60.05 | 0.00 | 0.00 |
November | 0.485464E+10 | -0.462151E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -233124976.3 | 60.05 | 0.00 | 0.00 |
December | 0.512484E+10 | -0.487588E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -248955370.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.598101E+11 | -0.569955E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.281461E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.428531E+10 | -0.571793E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -256205676.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.595930E+10 | -0.406062E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224683593.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7173.57 | 37.33 | 205.17 | 243.67 | 5918.12 | 38.14 | 202.83 | 221.00 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8488.30 | 37.55 | 222.33 | 255.33 | 2483.37 | 28.91 | 193.33 | 237.67 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7738.37 | 30.40 | 270.33 | 327.00 | 1484.78 | 21.70 | 208.00 | 293.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2331.30 | 19.15 | 9.50 | 346.67 | 1394.56 | 21.38 | 166.67 | 301.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1795.27 | 18.76 | 0.00 | 395.33 | 1005.10 | 20.96 | 210.17 | 351.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 1829.58 | 19.00 | 0.00 | 396.00 | 1039.59 | 21.22 | 234.00 | 354.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1900.00 | 19.30 | 2.33 | 406.00 | 1090.27 | 21.51 | 251.83 | 366.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2109.23 | 19.20 | 3.17 | 378.67 | 1187.54 | 21.40 | 252.00 | 345.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3065.24 | 20.95 | 46.50 | 332.67 | 1510.84 | 21.92 | 215.00 | 303.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7307.99 | 33.26 | 293.33 | 305.83 | 1966.05 | 23.12 | 204.17 | 283.00 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5114.54 | 32.64 | 233.50 | 247.83 | 2785.27 | 31.00 | 227.67 | 226.00 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6237.10 | 36.22 | 168.83 | 219.17 | 5730.91 | 39.69 | 184.33 | 185.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4126.55 | 25.32 | 1455.00 | 3854.17 | 1949.07 | 24.49 | 2550.00 | 3469.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1795.27 | 18.76 | 0.00 | 219.17 | 1005.10 | 20.96 | 166.67 | 185.50 | |
Maximum of Months | 428.67 | 0.50 | 0.48 | 8488.30 | 37.55 | 293.33 | 406.00 | 5918.12 | 39.69 | 252.00 | 366.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 1884.87 | 22.26 | 66.17 | 229.00 | 964.71 | 22.74 | 94.33 | 185.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2331.30 | 23.30 | 78.50 | 241.50 | 1290.26 | 23.97 | 95.67 | 205.50 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:49 | 2957.87 | 21.74 | 103.33 | 320.83 | 1269.19 | 22.76 | 110.83 | 281.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:40 | 3481.23 | 21.43 | 77.33 | 347.67 | 2086.32 | 23.66 | 78.50 | 311.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3633.41 | 22.20 | 136.33 | 403.00 | 1567.50 | 22.21 | 81.50 | 361.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3284.43 | 20.96 | 95.67 | 404.50 | 1808.27 | 22.98 | 79.00 | 374.00 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4146.90 | 22.47 | 123.33 | 414.33 | 1811.64 | 22.64 | 73.17 | 380.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3295.14 | 21.25 | 110.83 | 381.00 | 1501.79 | 22.59 | 84.50 | 356.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3330.24 | 22.26 | 95.17 | 330.33 | 1883.19 | 23.52 | 101.67 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:30 | 2087.77 | 20.97 | 88.67 | 291.67 | 1148.28 | 23.05 | 111.50 | 261.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:40 | 1643.47 | 21.35 | 82.00 | 234.17 | 876.79 | 22.41 | 85.00 | 191.67 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1477.51 | 21.82 | 64.17 | 197.67 | 793.86 | 23.28 | 74.50 | 129.17 |
Annual Sum or Average | 3807.33 | 0.50 | 2972.75 | 21.79 | 1121.50 | 3795.67 | 1481.74 | 22.92 | 1070.17 | 3337.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1477.51 | 20.96 | 64.17 | 197.67 | 793.86 | 22.21 | 73.17 | 129.17 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4146.90 | 23.30 | 136.33 | 414.33 | 2086.32 | 23.97 | 111.50 | 380.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 659.94 | 15.79 | 0.00 | 211.67 | 404.37 | 18.30 | 0.50 | 134.00 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-08:00 | 695.93 | 16.16 | 0.00 | 226.50 | 434.22 | 18.63 | 0.00 | 164.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 943.38 | 17.67 | 0.00 | 317.67 | 550.12 | 19.88 | 8.00 | 263.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1111.14 | 18.63 | 0.00 | 349.00 | 686.60 | 20.80 | 89.00 | 292.33 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-05:00 | 1259.71 | 19.97 | 31.33 | 413.83 | 716.86 | 22.06 | 179.33 | 378.67 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1522.18 | 22.72 | 96.50 | 413.83 | 890.45 | 24.08 | 266.67 | 392.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1430.34 | 20.80 | 55.50 | 424.17 | 846.33 | 22.95 | 247.83 | 396.67 |
August | 410.83 | 0.49 | 0.48 | 01-AUG-05:49 | 1184.09 | 18.94 | 0.17 | 390.50 | 694.25 | 21.08 | 154.83 | 359.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 982.80 | 18.33 | 0.00 | 330.33 | 605.89 | 20.53 | 30.17 | 284.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:19 | 773.47 | 16.69 | 0.00 | 281.83 | 459.50 | 19.00 | 0.00 | 226.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:20 | 656.02 | 15.68 | 0.00 | 221.67 | 374.26 | 17.95 | 0.00 | 142.83 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:09 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 |
Annual Sum or Average | 3807.33 | 0.50 | 1047.75 | 18.49 | 183.50 | 3753.33 | 620.83 | 20.65 | 976.33 | 3100.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 481.23 | 14.36 | 0.00 | 172.33 | 304.10 | 17.03 | 0.00 | 65.17 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1522.18 | 22.72 | 96.50 | 424.17 | 890.45 | 24.08 | 266.67 | 396.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:50 | 2047.84 | 23.86 | 84.17 | 228.17 | 1187.38 | 24.35 | 94.50 | 185.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-08:00 | 2333.26 | 21.49 | 63.33 | 239.83 | 1320.39 | 23.60 | 84.00 | 208.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2532.25 | 21.43 | 94.50 | 323.17 | 1370.47 | 22.60 | 110.83 | 286.17 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4544.84 | 22.41 | 84.50 | 349.83 | 1894.47 | 21.81 | 51.83 | 301.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2718.55 | 17.76 | 50.50 | 402.67 | 1479.66 | 18.88 | 2.00 | 367.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:40 | 3474.50 | 18.23 | 50.33 | 405.50 | 1593.50 | 19.32 | 0.67 | 369.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3857.60 | 18.72 | 56.00 | 412.33 | 1712.69 | 19.54 | 5.83 | 380.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3239.17 | 20.13 | 84.67 | 386.33 | 1827.65 | 21.57 | 62.00 | 353.67 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3369.61 | 22.48 | 97.00 | 334.00 | 1985.55 | 23.86 | 90.50 | 301.67 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-07:30 | 2143.47 | 21.00 | 86.67 | 292.83 | 1171.44 | 22.87 | 97.50 | 260.33 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1697.18 | 21.16 | 83.83 | 235.50 | 924.62 | 22.10 | 78.00 | 194.33 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-08:00 | 1555.45 | 20.81 | 55.00 | 201.17 | 891.44 | 22.91 | 64.17 | 126.33 |
Annual Sum or Average | 3807.33 | 0.50 | 2919.37 | 20.46 | 890.50 | 3811.33 | 1501.23 | 21.60 | 741.83 | 3334.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1555.45 | 17.76 | 50.33 | 201.17 | 891.44 | 18.88 | 0.67 | 126.33 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4544.84 | 23.86 | 97.00 | 412.33 | 1985.55 | 24.35 | 110.83 | 380.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.50 | 36.98 | 205.17 | 243.00 | 5762.31 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.74 | 37.32 | 222.33 | 254.33 | 2338.74 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.58 | 29.51 | 251.50 | 325.50 | 1382.71 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.95 | 15.48 | 0.00 | 345.00 | 1304.34 | 19.03 | 29.50 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.95 | 15.00 | 0.00 | 393.17 | 953.34 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.34 | 15.45 | 0.00 | 393.17 | 990.42 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1818.04 | 15.77 | 0.00 | 404.67 | 1036.50 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.48 | 15.52 | 0.00 | 376.17 | 1120.05 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.44 | 17.47 | 26.00 | 330.83 | 1408.27 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.20 | 32.70 | 290.83 | 304.00 | 1851.41 | 20.35 | 37.00 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.82 | 32.23 | 228.83 | 246.50 | 2682.88 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.15 | 35.39 | 167.50 | 217.33 | 5581.35 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.77 | 22.94 | 1392.17 | 3833.67 | 1859.09 | 22.37 | 834.50 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.95 | 15.00 | 0.00 | 217.33 | 953.34 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.74 | 37.32 | 290.83 | 404.67 | 5762.31 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.03 | 21.71 | 65.67 | 226.83 | 922.12 | 22.50 | 86.67 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.93 | 20.83 | 62.83 | 239.00 | 1239.91 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.22 | 21.26 | 101.17 | 318.83 | 1212.62 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.60 | 20.96 | 77.33 | 346.17 | 1974.74 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.58 | 21.76 | 135.83 | 401.17 | 1500.37 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.21 | 20.50 | 95.67 | 402.33 | 1720.22 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.51 | 22.02 | 123.33 | 412.50 | 1736.99 | 22.47 | 70.83 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.51 | 20.79 | 110.67 | 379.67 | 1434.73 | 22.41 | 77.50 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.12 | 21.80 | 95.17 | 327.67 | 1810.53 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.16 | 20.48 | 88.17 | 289.67 | 1100.56 | 22.84 | 98.33 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.34 | 20.89 | 81.17 | 231.67 | 843.16 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.91 | 21.33 | 64.00 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.07 | 21.20 | 1101.00 | 3768.67 | 1415.29 | 22.52 | 961.33 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.91 | 20.48 | 62.83 | 193.17 | 732.51 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.51 | 22.02 | 135.83 | 412.50 | 1974.74 | 23.76 | 98.33 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.11 | 12.16 | 0.00 | 208.83 | 390.41 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.88 | 12.67 | 0.00 | 224.83 | 420.40 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.06 | 14.15 | 0.00 | 315.00 | 531.70 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.15 | 15.46 | 0.00 | 347.33 | 666.05 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.69 | 15.43 | 3.17 | 411.83 | 692.06 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.50 | 19.31 | 75.50 | 412.50 | 859.04 | 22.28 | 111.83 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.26 | 17.69 | 30.67 | 422.67 | 817.66 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.95 | 15.59 | 0.00 | 388.83 | 671.05 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.06 | 15.19 | 0.00 | 327.67 | 586.90 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.30 | 13.11 | 0.00 | 279.00 | 444.10 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.98 | 11.82 | 0.00 | 219.17 | 360.75 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.33 | 14.94 | 109.33 | 3723.67 | 600.00 | 18.54 | 274.50 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.95 | 10.47 | 0.00 | 166.00 | 293.89 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.50 | 19.31 | 75.50 | 422.67 | 859.04 | 22.28 | 111.83 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.72 | 23.50 | 84.17 | 226.33 | 1144.95 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.91 | 21.08 | 63.33 | 238.00 | 1264.79 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.63 | 21.02 | 94.00 | 320.50 | 1318.44 | 22.47 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.73 | 21.97 | 84.50 | 347.83 | 1810.44 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.20 | 17.26 | 49.83 | 400.83 | 1419.11 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.18 | 17.74 | 50.33 | 403.33 | 1519.64 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.51 | 18.23 | 56.00 | 410.50 | 1630.93 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.76 | 19.67 | 84.50 | 384.00 | 1747.67 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.62 | 22.06 | 97.00 | 332.67 | 1882.86 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.45 | 20.28 | 83.00 | 290.50 | 1120.33 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1598.00 | 19.49 | 70.17 | 233.00 | 888.57 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.96 | 20.40 | 55.00 | 198.83 | 855.64 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.85 | 19.91 | 871.83 | 3786.33 | 1435.22 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.96 | 17.26 | 49.83 | 198.83 | 855.64 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.73 | 23.50 | 97.00 | 410.50 | 1882.86 | 24.27 | 105.67 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6969.51 | 36.98 | 205.17 | 243.00 | 5762.19 | 37.76 | 200.17 | 219.33 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 8300.71 | 37.32 | 222.33 | 254.33 | 2338.62 | 26.89 | 105.67 | 235.83 |
March | 334.33 | 0.49 | 0.48 | 01-MAR-07:00 | 7595.45 | 29.51 | 251.50 | 325.50 | 1382.60 | 18.89 | 14.33 | 290.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 2208.84 | 15.48 | 0.00 | 345.00 | 1304.25 | 19.03 | 29.67 | 296.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:40 | 1717.85 | 15.00 | 0.00 | 393.17 | 953.26 | 18.48 | 2.83 | 348.50 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 1753.25 | 15.46 | 0.00 | 393.17 | 990.35 | 18.94 | 2.17 | 352.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.94 | 15.78 | 0.00 | 404.67 | 1036.42 | 19.27 | 10.67 | 362.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2011.36 | 15.53 | 0.00 | 376.17 | 1119.96 | 19.01 | 18.67 | 342.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 2927.32 | 17.47 | 26.00 | 330.83 | 1408.17 | 19.46 | 44.50 | 300.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7158.12 | 32.70 | 290.83 | 304.00 | 1851.31 | 20.35 | 37.17 | 280.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4975.78 | 32.24 | 228.83 | 246.50 | 2682.78 | 29.91 | 184.83 | 224.50 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6046.18 | 35.39 | 167.50 | 217.33 | 5581.28 | 39.49 | 184.17 | 181.50 |
Annual Sum or Average | 3807.33 | 0.50 | 4002.69 | 22.94 | 1392.17 | 3833.67 | 1858.99 | 22.37 | 834.83 | 3434.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1717.85 | 15.00 | 0.00 | 217.33 | 953.26 | 18.48 | 2.17 | 181.50 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8300.71 | 37.32 | 290.83 | 404.67 | 5762.19 | 39.49 | 200.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1828.01 | 21.71 | 65.67 | 226.83 | 922.08 | 22.50 | 86.83 | 179.67 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-07:49 | 2188.91 | 20.83 | 62.83 | 239.00 | 1239.86 | 23.76 | 89.17 | 203.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:49 | 2885.16 | 21.26 | 101.17 | 318.83 | 1212.55 | 22.56 | 94.50 | 279.00 |
April | 285.17 | 0.50 | 0.48 | 01-APR-06:49 | 3384.56 | 20.96 | 77.33 | 346.17 | 1974.67 | 22.63 | 64.67 | 308.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3546.50 | 21.76 | 135.83 | 401.17 | 1500.29 | 22.02 | 79.50 | 358.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3183.14 | 20.50 | 95.67 | 402.33 | 1720.13 | 22.19 | 68.33 | 368.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 4044.45 | 22.02 | 123.33 | 412.50 | 1736.91 | 22.47 | 71.00 | 376.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3207.45 | 20.79 | 110.67 | 379.67 | 1434.65 | 22.41 | 77.67 | 353.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3238.09 | 21.80 | 95.17 | 327.67 | 1810.45 | 23.32 | 91.00 | 294.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2026.12 | 20.48 | 88.17 | 289.67 | 1100.50 | 22.84 | 98.50 | 258.67 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1598.30 | 20.90 | 81.17 | 231.67 | 843.11 | 22.01 | 76.83 | 186.17 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-07:00 | 1432.90 | 21.33 | 64.00 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2888.03 | 21.20 | 1101.00 | 3768.67 | 1415.22 | 22.52 | 962.00 | 3289.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1432.90 | 20.48 | 62.83 | 193.17 | 732.48 | 21.81 | 64.00 | 123.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4044.45 | 22.02 | 135.83 | 412.50 | 1974.67 | 23.76 | 98.50 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 634.10 | 12.17 | 0.00 | 208.83 | 390.39 | 15.89 | 0.00 | 127.67 |
February | 226.83 | 0.53 | 0.48 | 01-FEB-09:09 | 669.87 | 12.67 | 0.00 | 224.83 | 420.38 | 16.38 | 0.00 | 159.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 910.02 | 14.15 | 0.00 | 315.00 | 531.66 | 17.63 | 0.00 | 257.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:10 | 1072.12 | 15.46 | 0.00 | 347.33 | 666.01 | 18.97 | 13.00 | 285.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1209.64 | 15.43 | 3.17 | 411.83 | 692.01 | 19.98 | 45.50 | 375.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1457.46 | 19.32 | 75.50 | 412.50 | 858.98 | 22.28 | 112.00 | 390.67 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1379.22 | 17.69 | 30.67 | 422.67 | 817.61 | 21.06 | 91.50 | 394.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1141.91 | 15.59 | 0.00 | 388.83 | 671.00 | 19.10 | 12.67 | 356.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 947.04 | 15.19 | 0.00 | 327.67 | 586.87 | 18.67 | 0.00 | 276.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:19 | 745.27 | 13.11 | 0.00 | 279.00 | 444.07 | 16.68 | 0.00 | 219.83 |
November | 254.83 | 0.53 | 0.48 | 01-NOV-08:20 | 631.95 | 11.82 | 0.00 | 219.17 | 360.72 | 15.37 | 0.00 | 134.33 |
December | 186.17 | 0.55 | 0.48 | 01-DEC-09:50 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1008.30 | 14.94 | 109.33 | 3723.67 | 599.96 | 18.54 | 274.67 | 3035.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 461.94 | 10.47 | 0.00 | 166.00 | 293.88 | 14.39 | 0.00 | 58.50 | |
Maximum of Months | 428.67 | 0.55 | 0.48 | 1457.46 | 19.32 | 75.50 | 422.67 | 858.98 | 22.28 | 112.00 | 394.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:50 | 1992.70 | 23.50 | 84.17 | 226.33 | 1144.90 | 24.27 | 93.83 | 179.17 |
February | 226.83 | 0.51 | 0.48 | 01-FEB-09:09 | 2262.89 | 21.08 | 63.33 | 238.00 | 1264.74 | 23.51 | 82.00 | 205.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2465.57 | 21.02 | 94.00 | 320.50 | 1318.37 | 22.48 | 105.67 | 282.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4342.69 | 21.98 | 84.50 | 347.83 | 1810.36 | 21.67 | 49.33 | 296.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2637.14 | 17.26 | 49.83 | 400.83 | 1419.04 | 18.70 | 0.50 | 364.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:49 | 3334.11 | 17.74 | 50.33 | 403.33 | 1519.56 | 19.14 | 0.00 | 367.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:00 | 3749.44 | 18.23 | 56.00 | 410.50 | 1630.84 | 19.37 | 3.67 | 378.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3146.70 | 19.68 | 84.50 | 384.00 | 1747.59 | 21.42 | 59.83 | 351.00 |
September | 326.50 | 0.49 | 0.48 | 01-SEP-06:49 | 3281.59 | 22.06 | 97.00 | 332.67 | 1882.79 | 23.72 | 87.50 | 298.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2059.41 | 20.28 | 83.00 | 290.50 | 1120.27 | 22.76 | 95.67 | 257.50 |
November | 254.83 | 0.51 | 0.48 | 01-NOV-08:30 | 1597.96 | 19.49 | 70.17 | 233.00 | 888.52 | 21.99 | 77.33 | 190.83 |
December | 186.17 | 0.52 | 0.48 | 01-DEC-09:09 | 1509.95 | 20.40 | 55.00 | 198.83 | 855.61 | 22.83 | 63.17 | 120.67 |
Annual Sum or Average | 3807.33 | 0.50 | 2821.80 | 19.91 | 871.83 | 3786.33 | 1435.15 | 21.47 | 718.50 | 3290.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1509.95 | 17.26 | 49.83 | 198.83 | 855.61 | 18.70 | 0.00 | 120.67 | |
Maximum of Months | 428.67 | 0.52 | 0.48 | 4342.69 | 23.50 | 97.00 | 410.50 | 1882.79 | 24.27 | 105.67 | 378.17 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285074E+11 | 31819.51 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190935E+11 | 32839.29 | 01-FEB-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128177E+11 | 28154.64 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.504661E+10 | 21769.56 | 03-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195638E+09 | 7916.77 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8166343.72 | 2908.51 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 991910.56 | 5.36 | 03-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 902267.80 | 5.42 | 21-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330627E+09 | 9795.50 | 29-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.242783E+10 | 13555.89 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109568E+11 | 29211.23 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220443E+11 | 30426.81 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 902267.80 | 5.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285074E+11 | 32839.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107863E+10 | 13295.30 | 30-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.659068E+09 | 13705.77 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22273995.94 | 13177.91 | 27-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122418E+09 | 13180.50 | 26-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107863E+10 | 13705.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105828E+11 | 10649.76 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.689245E+10 | 11022.20 | 01-FEB-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504722E+10 | 9332.65 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253995E+10 | 9695.51 | 20-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.631614E+09 | 9400.68 | 22-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213497E+09 | 9602.95 | 02-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2790888.95 | 3683.02 | 12-JUL-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28583017.50 | 9334.15 | 16-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.436204E+09 | 9352.51 | 27-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112224E+10 | 9574.44 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392321E+10 | 9709.70 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.767832E+10 | 10144.92 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2790888.95 | 3683.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105828E+11 | 11022.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.566077E+10 | 7959.81 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347663E+10 | 8240.22 | 01-FEB-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129788E+10 | 6969.23 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376253E+09 | 6900.02 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79655.72 | 65.09 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8151318.01 | 6885.63 | 27-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120021E+10 | 7252.61 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342600E+10 | 7580.01 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.566077E+10 | 8240.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.896539E+10 | 8408.06 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.575899E+10 | 8699.62 | 01-FEB-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.287492E+10 | 7375.80 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.919900E+09 | 7377.82 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14662570.71 | 7289.93 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3732886.94 | 4087.78 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54231341.06 | 7569.16 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212029E+10 | 7721.05 | 25-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554824E+10 | 8012.46 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.896539E+10 | 8699.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595622E+10 | 8249.39 | 30-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352590E+10 | 8540.31 | 01-FEB-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145196E+10 | 7222.45 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340414E+09 | 7156.16 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3687592.27 | 6920.51 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2719725.33 | 3109.92 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11011429.31 | 7144.09 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124277E+10 | 7516.16 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349014E+10 | 7855.37 | 09-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595622E+10 | 8540.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271898E+11 | 33733.49 | 30-JAN-08:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187083E+11 | 34824.58 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128201E+11 | 26117.15 | 06-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.564385E+10 | 20155.64 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.348879E+09 | 7877.11 | 02-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48583117.35 | 3459.47 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 774458.85 | 5.16 | 05-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 758385.20 | 1083.24 | 07-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.620604E+09 | 10591.37 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359352E+10 | 15266.08 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111376E+11 | 30480.05 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214405E+11 | 31738.55 | 11-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 758385.20 | 5.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271898E+11 | 34824.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.611915E+10 | 19368.57 | 30-JAN-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324030E+10 | 19875.65 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.588223E+09 | 18969.23 | 01-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87662969.40 | 18974.14 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120301E+10 | 19017.06 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308517E+10 | 18981.56 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611915E+10 | 19875.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519996E+10 | 11305.23 | 30-JAN-08:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275932E+10 | 11699.01 | 02-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120281E+10 | 10016.06 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283596E+09 | 10009.77 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 342195.51 | 1673.42 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7142820.27 | 9018.17 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56558776.15 | 9939.41 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158208E+10 | 10181.96 | 28-NOV-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410926E+10 | 10604.14 | 09-DEC-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519996E+10 | 11699.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.492947E+10 | 8701.88 | 31-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285675E+10 | 9121.73 | 02-FEB-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.896451E+09 | 7686.96 | 06-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182964E+09 | 7687.08 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4015768.24 | 6666.86 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52023999.91 | 7657.92 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141743E+10 | 7751.84 | 25-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342901E+10 | 8250.45 | 11-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492947E+10 | 9121.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.830772E+10 | 9034.92 | 30-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.500215E+10 | 9496.57 | 02-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185647E+10 | 7912.83 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.395763E+09 | 7907.83 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 415012.27 | 2130.71 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11640546.68 | 7863.88 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115500E+09 | 7861.91 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.248165E+10 | 8195.78 | 25-NOV-08:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570274E+10 | 8466.80 | 11-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.830772E+10 | 9496.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.532625E+10 | 8999.21 | 30-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316704E+10 | 9468.83 | 02-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103228E+10 | 7843.38 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198303E+09 | 7840.78 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 633511.19 | 1969.07 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8878710.90 | 7793.02 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64063790.02 | 7809.12 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151535E+10 | 8100.97 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359145E+10 | 8423.14 | 11-DEC-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.532625E+10 | 9468.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293242E+11 | 32355.42 | 06-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199395E+11 | 33285.72 | 02-FEB-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135808E+11 | 26657.92 | 06-MAR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.605089E+10 | 20736.78 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.442753E+09 | 10736.68 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102835E+09 | 4438.09 | 03-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 761026.76 | 5.59 | 05-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4634309.56 | 2151.87 | 07-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.824178E+09 | 14732.87 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411721E+10 | 16446.10 | 14-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122397E+11 | 29610.05 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234873E+11 | 30909.54 | 08-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 761026.76 | 5.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.293242E+11 | 33285.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132066E+11 | 29316.46 | 30-JAN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790258E+10 | 28127.78 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286061E+10 | 25661.97 | 14-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.634987E+09 | 25645.72 | 05-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8114670.18 | 15312.02 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173636E+09 | 25643.63 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.415426E+10 | 25662.80 | 20-NOV-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.879494E+10 | 26072.80 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132066E+11 | 29316.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.844930E+10 | 13532.12 | 06-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488052E+10 | 13866.52 | 01-FEB-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248622E+10 | 11851.77 | 15-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.812758E+09 | 11832.65 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16908024.04 | 11805.32 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66155685.65 | 11782.88 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.398619E+09 | 11803.77 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309674E+10 | 12182.24 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689431E+10 | 12712.95 | 09-DEC-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.844930E+10 | 13866.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.752348E+10 | 9999.84 | 06-JAN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452567E+10 | 10447.63 | 02-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179939E+10 | 8738.03 | 11-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.519953E+09 | 8734.66 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2403016.00 | 8039.59 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40174015.13 | 8728.60 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315936E+09 | 8723.03 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263380E+10 | 8996.55 | 25-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.563987E+10 | 9597.59 | 08-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.752348E+10 | 10447.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122320E+11 | 11050.35 | 30-JAN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765105E+10 | 11557.60 | 02-FEB-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352223E+10 | 9570.85 | 08-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101599E+10 | 9525.67 | 28-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16832385.83 | 9475.42 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103460E+09 | 9500.73 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.722324E+09 | 9520.49 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.439728E+10 | 10130.36 | 25-NOV-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900500E+10 | 10444.17 | 08-DEC-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122320E+11 | 11557.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.799503E+10 | 10665.39 | 30-JAN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.487863E+10 | 11163.35 | 02-FEB-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203528E+10 | 9146.79 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.560391E+09 | 9142.95 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12298993.68 | 9123.39 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66157411.40 | 9106.05 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388799E+09 | 9122.36 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272605E+10 | 9552.31 | 25-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.577081E+10 | 10055.34 | 08-DEC-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.799503E+10 | 11163.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155883E+09 | 0.137587E+09 | 6915.83 | 25-MAR-15:00 | 6128.47 | 0.00 |
April | 0.00 | 0.00 | 0.589341E+10 | 0.474135E+10 | 65277.30 | 18-APR-15:00 | 55086.54 | 0.00 |
May | 0.00 | 0.00 | 0.149747E+11 | 0.115096E+11 | 72108.60 | 30-MAY-11:00 | 45201.41 | 0.00 |
June | 0.00 | 0.00 | 0.440994E+11 | 0.327892E+11 | 116263.10 | 26-JUN-08:00 | 53173.03 | 0.00 |
July | 0.00 | 0.00 | 0.634313E+11 | 0.428386E+11 | 114123.92 | 03-JUL-08:50 | 54280.19 | 0.00 |
August | 0.00 | 0.00 | 0.623417E+11 | 0.430778E+11 | 117222.66 | 03-AUG-05:12 | 39011.48 | 0.00 |
September | 0.00 | 0.00 | 0.261917E+11 | 0.231846E+11 | 100078.63 | 11-SEP-09:50 | 59202.51 | 0.00 |
October | 0.00 | 0.00 | 0.255696E+10 | 0.235062E+10 | 37371.28 | 20-OCT-15:00 | 37371.28 | 0.00 |
November | 0.00 | 0.00 | 0.149123E+09 | 0.132387E+09 | 8891.31 | 01-NOV-11:00 | 8189.82 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219794E+12 | 0.160762E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.634313E+11 | 0.430778E+11 | 117222.66 | 59202.51 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163671E+09 | 0.137359E+09 | 7395.82 | 25-MAR-15:00 | 7022.60 | 0.00 |
April | 0.00 | 0.00 | 0.552866E+10 | 0.439873E+10 | 68982.07 | 18-APR-12:30 | 49019.54 | 0.00 |
May | 0.00 | 0.00 | 0.144963E+11 | 0.109598E+11 | 72018.43 | 30-MAY-11:00 | 44986.99 | 0.00 |
June | 0.00 | 0.00 | 0.417255E+11 | 0.312394E+11 | 111062.33 | 26-JUN-08:00 | 50596.01 | 0.00 |
July | 0.00 | 0.00 | 0.569730E+11 | 0.387335E+11 | 109018.85 | 03-JUL-08:50 | 51633.93 | 0.00 |
August | 0.00 | 0.00 | 0.533461E+11 | 0.372520E+11 | 111978.97 | 03-AUG-05:12 | 37275.54 | 0.00 |
September | 0.00 | 0.00 | 0.215811E+11 | 0.191454E+11 | 85320.80 | 11-SEP-09:50 | 51157.37 | 0.00 |
October | 0.00 | 0.00 | 0.130215E+10 | 0.111588E+10 | 29867.68 | 20-OCT-15:00 | 29867.68 | 0.00 |
November | 0.00 | 0.00 | 80672418.90 | 69431082.53 | 7351.70 | 03-NOV-13:30 | 6146.99 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195197E+12 | 0.143051E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.569730E+11 | 0.387335E+11 | 111978.97 | 51633.93 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1316785.42 | 1314326.24 | 978.55 | 23-JAN-06:50 | 978.55 | 0.00 |
February | 0.00 | 0.00 | 5287012.81 | 4516826.43 | 1207.97 | 24-FEB-15:10 | 1025.13 | 0.00 |
March | 0.00 | 0.00 | 0.149864E+09 | 0.122739E+09 | 7422.87 | 25-MAR-15:00 | 6618.91 | 0.00 |
April | 0.00 | 0.00 | 0.609646E+10 | 0.482867E+10 | 79892.76 | 16-APR-14:42 | 54408.03 | 0.00 |
May | 0.00 | 0.00 | 0.152803E+11 | 0.116058E+11 | 71780.40 | 30-MAY-14:00 | 62872.89 | 0.00 |
June | 0.00 | 0.00 | 0.442858E+11 | 0.335003E+11 | 120132.05 | 26-JUN-06:03 | 48737.36 | 0.00 |
July | 0.00 | 0.00 | 0.597810E+11 | 0.406238E+11 | 112236.33 | 05-JUL-11:00 | 59420.63 | 0.00 |
August | 0.00 | 0.00 | 0.547269E+11 | 0.386420E+11 | 124848.20 | 04-AUG-06:03 | 36242.11 | 0.00 |
September | 0.00 | 0.00 | 0.221112E+11 | 0.195077E+11 | 84665.35 | 11-SEP-10:00 | 52293.64 | 0.00 |
October | 0.00 | 0.00 | 0.122110E+10 | 0.101330E+10 | 29019.45 | 20-OCT-15:00 | 29019.45 | 0.00 |
November | 0.00 | 0.00 | 47591183.26 | 40391708.55 | 4503.76 | 03-NOV-13:40 | 3778.25 | 0.00 |
December | 0.00 | 0.00 | 705184.89 | 683814.40 | 700.62 | 04-DEC-06:06 | 700.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.203707E+12 | 0.149891E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 705184.89 | 683814.40 | 700.62 | 700.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.597810E+11 | 0.406238E+11 | 124848.20 | 62872.89 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 72882.58 | 260778.11 | 30-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 51272.45 | 269064.77 | 02-FEB-07:25 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25243.85 | 214954.49 | 31-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9799.25 | 211979.90 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 631.64 | 148382.02 | 02-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 139.29 | 24080.45 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.56 | 5411.67 | 12-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 12.68 | 15448.19 | 07-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 964.54 | 156883.42 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 5047.64 | 187367.70 | 26-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26051.17 | 236919.90 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 53089.51 | 246142.23 | 11-DEC-07:06 |
Annual Sum or Average | 0.00 | 20297.12 | ||||
Minimum of Months | 0.00 | 0.00 | 1.56 | 5411.67 | ||
Maximum of Months | 0.00 | 0.00 | 72882.58 | 269064.77 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1955.34 | 7209.53 | 31-JAN-12:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 2006.59 | 7256.35 | 21-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2124.75 | 7245.52 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1900.47 | 7041.26 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1858.67 | 6708.64 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1781.01 | 6265.21 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1533.17 | 5851.66 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1652.33 | 5617.77 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1557.45 | 5750.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1633.73 | 6122.64 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1773.50 | 6552.32 | 30-NOV-12:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1811.04 | 6933.69 | 29-DEC-12:16 |
Annual Sum or Average | 0.00 | 1797.80 | ||||
Minimum of Months | 0.00 | 0.00 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 2124.75 | 7256.35 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174603E+10 | 0.40 | 2685.17 | 02-JAN-05:01 | 0.85 |
February | 0.136035E+10 | 0.37 | 2685.17 | 01-FEB-07:01 | 0.86 |
March | 0.141930E+10 | 0.35 | 1988.88 | 24-MAR-14:30 | 0.73 |
April | 0.178053E+10 | 0.35 | 7460.87 | 18-APR-14:50 | 1.54 |
May | 0.275599E+10 | 0.40 | 8392.48 | 30-MAY-15:30 | 1.66 |
June | 0.491245E+10 | 0.55 | 10939.28 | 26-JUN-05:12 | 1.97 |
July | 0.582892E+10 | 0.59 | 10939.28 | 03-JUL-08:50 | 1.96 |
August | 0.616070E+10 | 0.61 | 10939.28 | 03-AUG-05:12 | 1.96 |
September | 0.400291E+10 | 0.49 | 10939.28 | 11-SEP-06:03 | 1.97 |
October | 0.186577E+10 | 0.34 | 5070.33 | 23-OCT-06:01 | 1.23 |
November | 0.142817E+10 | 0.33 | 3651.51 | 06-NOV-07:02 | 1.01 |
December | 0.138062E+10 | 0.35 | 2685.17 | 11-DEC-07:01 | 0.86 |
Annual Sum or Average | 0.346417E+11 | 0.43 | |||
Minimum of Months | 0.136035E+10 | 0.33 | 1988.88 | 0.73 | |
Maximum of Months | 0.616070E+10 | 0.61 | 10939.28 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169169E+10 | 0.42 | 2832.17 | 02-JAN-05:01 | 0.91 |
February | 0.129693E+10 | 0.37 | 2832.17 | 01-FEB-06:01 | 0.91 |
March | 0.126203E+10 | 0.35 | 2832.17 | 01-MAR-06:01 | 0.91 |
April | 0.169739E+10 | 0.36 | 8509.92 | 18-APR-15:10 | 1.75 |
May | 0.264767E+10 | 0.42 | 9058.39 | 30-MAY-14:05 | 1.82 |
June | 0.458618E+10 | 0.55 | 10248.06 | 12-JUN-06:03 | 1.97 |
July | 0.501398E+10 | 0.56 | 10248.06 | 03-JUL-05:12 | 1.97 |
August | 0.494236E+10 | 0.56 | 10248.06 | 03-AUG-06:03 | 1.96 |
September | 0.303146E+10 | 0.45 | 10248.06 | 11-SEP-06:03 | 1.97 |
October | 0.131999E+10 | 0.32 | 3543.05 | 20-OCT-15:20 | 1.03 |
November | 0.120307E+10 | 0.34 | 2832.17 | 13-NOV-07:01 | 0.91 |
December | 0.139405E+10 | 0.37 | 2832.17 | 01-DEC-07:01 | 0.91 |
Annual Sum or Average | 0.300868E+11 | 0.42 | |||
Minimum of Months | 0.120307E+10 | 0.32 | 2832.17 | 0.91 | |
Maximum of Months | 0.501398E+10 | 0.56 | 10248.06 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.222445E+10 | 0.51 | 2729.91 | 02-JAN-05:01 | 0.82 |
February | 0.166495E+10 | 0.45 | 2729.91 | 01-FEB-05:01 | 0.83 |
March | 0.150004E+10 | 0.41 | 2729.91 | 01-MAR-06:01 | 0.83 |
April | 0.173004E+10 | 0.39 | 7965.95 | 18-APR-14:50 | 1.53 |
May | 0.248178E+10 | 0.41 | 8665.32 | 30-MAY-15:20 | 1.61 |
June | 0.426663E+10 | 0.51 | 11750.19 | 26-JUN-05:12 | 1.95 |
July | 0.455905E+10 | 0.51 | 10415.41 | 03-JUL-15:20 | 1.81 |
August | 0.441851E+10 | 0.50 | 11750.19 | 04-AUG-07:15 | 1.94 |
September | 0.266709E+10 | 0.42 | 9679.54 | 07-SEP-16:00 | 1.73 |
October | 0.131611E+10 | 0.34 | 2861.80 | 20-OCT-15:00 | 0.84 |
November | 0.146091E+10 | 0.40 | 2729.91 | 10-NOV-07:01 | 0.82 |
December | 0.182945E+10 | 0.45 | 2729.91 | 01-DEC-06:01 | 0.82 |
Annual Sum or Average | 0.301190E+11 | 0.44 | |||
Minimum of Months | 0.131611E+10 | 0.34 | 2729.91 | 0.82 | |
Maximum of Months | 0.455905E+10 | 0.51 | 11750.19 | 1.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.122348E+10 | 0.111214E+10 | 1067.47 | 03-JAN-07:16 | 970.33 | 970.33 | 43.15 | 3.45 |
February | 0.806279E+09 | 0.732907E+09 | 1067.47 | 01-FEB-07:01 | 970.33 | 970.33 | 43.97 | 3.46 |
March | 0.507785E+09 | 0.461577E+09 | 940.59 | 06-MAR-07:19 | 855.00 | 855.00 | 43.05 | 3.03 |
April | 0.190872E+09 | 0.173502E+09 | 886.15 | 03-APR-06:01 | 805.51 | 805.51 | 45.85 | 2.75 |
May | 16587234.39 | 15077796.06 | 705.60 | 02-MAY-06:02 | 641.39 | 641.39 | 32.42 | 1.29 |
June | 4261381.35 | 3873595.65 | 179.69 | 02-JUN-06:10 | 163.34 | 163.34 | 38.40 | 0.20 |
July | 44289.27 | 40258.95 | 57.08 | 12-JUL-06:08 | 51.88 | 51.88 | 38.43 | 0.06 |
August | 357125.19 | 324626.80 | 147.14 | 07-AUG-06:06 | 133.75 | 133.75 | 37.14 | 0.16 |
September | 20788777.20 | 18896998.47 | 786.96 | 30-SEP-06:03 | 715.35 | 715.35 | 39.01 | 1.79 |
October | 0.102839E+09 | 93480479.66 | 829.83 | 27-OCT-06:02 | 754.32 | 754.32 | 40.54 | 2.26 |
November | 0.492633E+09 | 0.447804E+09 | 1004.82 | 25-NOV-07:15 | 913.38 | 913.38 | 43.41 | 3.26 |
December | 0.987953E+09 | 0.898050E+09 | 1041.45 | 11-DEC-07:06 | 946.68 | 946.68 | 42.51 | 3.37 |
Annual Sum or Average | 0.435387E+10 | 0.395767E+10 | ||||||
Minimum of Months | 44289.27 | 40258.95 | 57.08 | 51.88 | 51.88 | 32.42 | 0.06 | |
Maximum of Months | 0.122348E+10 | 0.111214E+10 | 1067.47 | 970.33 | 970.33 | 45.85 | 3.46 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 57.87 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.71 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.68 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.77 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.83 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.90 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.01 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.25 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.11 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 56.97 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.04 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.68 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.11 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 40.77 | 40.77 | 72882.58 | 260778.11 | 30-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 43.48 | 60.00 | 51272.45 | 269064.77 | 02-FEB-07:25 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 45.66 | 45.66 | 25243.85 | 214954.49 | 31-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.33 | 29.33 | 9799.25 | 211979.90 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.44 | 22.44 | 631.64 | 148382.02 | 02-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.58 | 47.58 | 139.29 | 24080.45 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 38.69 | 38.69 | 1.56 | 5411.67 | 12-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 37.43 | 37.43 | 12.68 | 15448.19 | 07-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 36.82 | 36.82 | 964.54 | 156883.42 | 30-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.22 | 23.22 | 5047.64 | 187367.70 | 26-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.68 | 32.68 | 26051.17 | 236919.90 | 20-NOV-06:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 37.41 | 37.41 | 53089.51 | 246142.23 | 11-DEC-07:06 |
Annual Sum or Average | 0.00 | 20297.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.44 | 22.44 | 1.56 | 5411.67 | ||
Maximum of Months | 0.00 | 0.00 | 47.58 | 60.00 | 72882.58 | 269064.77 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.88 | 57.88 | 1955.34 | 7209.53 | 31-JAN-12:11 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 57.23 | 57.23 | 2006.59 | 7256.35 | 21-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.21 | 57.21 | 2124.75 | 7245.52 | 01-MAR-12:25 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.28 | 57.28 | 1900.47 | 7041.26 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.95 | 57.95 | 1858.67 | 6708.64 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.60 | 57.60 | 1781.01 | 6265.21 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.75 | 57.75 | 1533.17 | 5851.66 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.85 | 57.85 | 1652.33 | 5617.77 | 01-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 1557.45 | 5750.24 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.90 | 56.90 | 1633.73 | 6122.64 | 31-OCT-11:17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.66 | 57.66 | 1773.50 | 6552.32 | 30-NOV-12:12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 1811.04 | 6933.69 | 29-DEC-12:16 |
Annual Sum or Average | 0.00 | 1797.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.90 | 56.90 | 1533.17 | 5617.77 | ||
Maximum of Months | 0.00 | 0.00 | 57.95 | 57.95 | 2124.75 | 7256.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.607512E+11 | 0.00 | 0.00 | 0.174603E+10 | 0.00 | 0.00 |
February | 0.394065E+11 | 0.00 | 0.00 | 0.136035E+10 | 0.00 | 0.00 |
March | 0.234897E+11 | 0.00 | 0.00 | 0.146029E+10 | 0.00 | 0.00 |
April | 0.922313E+10 | 0.00 | 0.00 | 0.317578E+10 | 0.00 | 0.00 |
May | 0.845603E+09 | 0.00 | 0.00 | 0.624863E+10 | 0.00 | 0.00 |
June | 0.221664E+09 | 0.00 | 0.00 | 0.149124E+11 | 0.00 | 0.00 |
July | 3782799.51 | 0.00 | 0.00 | 0.198364E+11 | 0.00 | 0.00 |
August | 29485285.30 | 0.00 | 0.00 | 0.199970E+11 | 0.00 | 0.00 |
September | 0.773363E+09 | 0.00 | 0.00 | 0.100765E+11 | 0.00 | 0.00 |
October | 0.362347E+10 | 0.00 | 0.00 | 0.249122E+10 | 0.00 | 0.00 |
November | 0.194655E+11 | 0.00 | 0.00 | 0.146729E+10 | 0.00 | 0.00 |
December | 0.423094E+11 | 0.00 | 0.00 | 0.138062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.200143E+12 | 0.00 | 0.00 | 0.841524E+11 | 0.00 | 0.00 |
Minimum of Months | 3782799.51 | 0.00 | 0.00 | 0.136035E+10 | 0.00 | 0.00 |
Maximum of Months | 0.607512E+11 | 0.00 | 0.00 | 0.199970E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.570723E+11 | 0.00 | 0.00 | 0.169169E+10 | 0.00 | 0.00 |
February | 0.357339E+11 | 0.00 | 0.00 | 0.129693E+10 | 0.00 | 0.00 |
March | 0.183963E+11 | 0.00 | 0.00 | 0.130486E+10 | 0.00 | 0.00 |
April | 0.679214E+10 | 0.00 | 0.00 | 0.298871E+10 | 0.00 | 0.00 |
May | 0.350269E+09 | 0.00 | 0.00 | 0.601680E+10 | 0.00 | 0.00 |
June | 48583117.35 | 0.00 | 0.00 | 0.140580E+11 | 0.00 | 0.00 |
July | 774458.85 | 0.00 | 0.00 | 0.176315E+11 | 0.00 | 0.00 |
August | 758385.20 | 0.00 | 0.00 | 0.168491E+11 | 0.00 | 0.00 |
September | 0.652282E+09 | 0.00 | 0.00 | 0.805063E+10 | 0.00 | 0.00 |
October | 0.388167E+10 | 0.00 | 0.00 | 0.164000E+10 | 0.00 | 0.00 |
November | 0.193371E+11 | 0.00 | 0.00 | 0.122398E+10 | 0.00 | 0.00 |
December | 0.413581E+11 | 0.00 | 0.00 | 0.139405E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.183624E+12 | 0.00 | 0.00 | 0.741464E+11 | 0.00 | 0.00 |
Minimum of Months | 758385.20 | 0.00 | 0.00 | 0.122398E+10 | 0.00 | 0.00 |
Maximum of Months | 0.570723E+11 | 0.00 | 0.00 | 0.176315E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.787306E+11 | 0.00 | 0.00 | 0.222480E+10 | 0.00 | 0.00 |
February | 0.497779E+11 | 0.00 | 0.00 | 0.166638E+10 | 0.00 | 0.00 |
March | 0.262845E+11 | 0.00 | 0.00 | 0.153941E+10 | 0.00 | 0.00 |
April | 0.959497E+10 | 0.00 | 0.00 | 0.315705E+10 | 0.00 | 0.00 |
May | 0.491195E+09 | 0.00 | 0.00 | 0.604513E+10 | 0.00 | 0.00 |
June | 0.102835E+09 | 0.00 | 0.00 | 0.143623E+11 | 0.00 | 0.00 |
July | 761026.76 | 0.00 | 0.00 | 0.178441E+11 | 0.00 | 0.00 |
August | 4634309.56 | 0.00 | 0.00 | 0.167076E+11 | 0.00 | 0.00 |
September | 0.110824E+10 | 0.00 | 0.00 | 0.784660E+10 | 0.00 | 0.00 |
October | 0.611653E+10 | 0.00 | 0.00 | 0.162006E+10 | 0.00 | 0.00 |
November | 0.292479E+11 | 0.00 | 0.00 | 0.147355E+10 | 0.00 | 0.00 |
December | 0.595922E+11 | 0.00 | 0.00 | 0.182964E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.261052E+12 | 0.00 | 0.00 | 0.763167E+11 | 0.00 | 0.00 |
Minimum of Months | 761026.76 | 0.00 | 0.00 | 0.147355E+10 | 0.00 | 0.00 |
Maximum of Months | 0.787306E+11 | 0.00 | 0.00 | 0.178441E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174603E+10 | 0.00 | 0.607512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136035E+10 | 0.00 | 0.394065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141930E+10 | 0.155883E+09 | 0.234897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178053E+10 | 0.589341E+10 | 0.922313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275599E+10 | 0.149747E+11 | 0.845603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491245E+10 | 0.440994E+11 | 0.221664E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.582892E+10 | 0.634313E+11 | 3782799.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.616070E+10 | 0.623417E+11 | 29485285.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400291E+10 | 0.261917E+11 | 0.773363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186577E+10 | 0.255696E+10 | 0.362347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142817E+10 | 0.149123E+09 | 0.194655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138062E+10 | 0.00 | 0.423094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346417E+11 | 0.219794E+12 | 0.200143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136035E+10 | 0.00 | 3782799.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616070E+10 | 0.634313E+11 | 0.607512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169169E+10 | 0.00 | 0.570723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129693E+10 | 0.00 | 0.357339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126203E+10 | 0.163671E+09 | 0.183963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169739E+10 | 0.552866E+10 | 0.679214E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264767E+10 | 0.144963E+11 | 0.350269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458618E+10 | 0.417255E+11 | 48583117.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.501398E+10 | 0.569730E+11 | 774458.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.494236E+10 | 0.533461E+11 | 758385.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303146E+10 | 0.215811E+11 | 0.652282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131999E+10 | 0.130215E+10 | 0.388167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120307E+10 | 80672418.90 | 0.193371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139405E+10 | 0.00 | 0.413581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300868E+11 | 0.195197E+12 | 0.183624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120307E+10 | 0.00 | 758385.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.501398E+10 | 0.569730E+11 | 0.570723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.222445E+10 | 1316785.42 | 0.787306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166495E+10 | 5287012.81 | 0.497779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150004E+10 | 0.149864E+09 | 0.262845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173004E+10 | 0.609646E+10 | 0.959497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248178E+10 | 0.152803E+11 | 0.491195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.426663E+10 | 0.442858E+11 | 0.102835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455905E+10 | 0.597810E+11 | 761026.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.441851E+10 | 0.547269E+11 | 4634309.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266709E+10 | 0.221112E+11 | 0.110824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131611E+10 | 0.122110E+10 | 0.611653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146091E+10 | 47591183.26 | 0.292479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182945E+10 | 705184.89 | 0.595922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301190E+11 | 0.203707E+12 | 0.261052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131611E+10 | 705184.89 | 761026.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.455905E+10 | 0.597810E+11 | 0.787306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174603E+10 | 0.607512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136035E+10 | 0.394065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141930E+10 | 0.234897E+11 | 0.00 | 0.00 | 40989878.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178053E+10 | 0.922313E+10 | 0.00 | 0.00 | 0.139525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.275599E+10 | 0.845603E+09 | 0.00 | 0.00 | 0.349264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491245E+10 | 0.221664E+09 | 0.00 | 0.00 | 0.999994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.582892E+10 | 3782799.51 | 0.00 | 0.00 | 0.140074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.616070E+10 | 29485285.30 | 0.00 | 0.00 | 0.138363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400291E+10 | 0.773363E+09 | 0.00 | 0.00 | 0.607354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186577E+10 | 0.362347E+10 | 0.00 | 0.00 | 0.625454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142817E+10 | 0.194655E+11 | 0.00 | 0.00 | 39113474.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138062E+10 | 0.423094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346417E+11 | 0.200143E+12 | 0.00 | 0.00 | 0.495106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136035E+10 | 3782799.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616070E+10 | 0.607512E+11 | 0.00 | 0.00 | 0.140074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169169E+10 | 0.570723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129693E+10 | 0.357339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126203E+10 | 0.183963E+11 | 0.00 | 0.00 | 42821749.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169739E+10 | 0.679214E+10 | 0.00 | 0.00 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.264767E+10 | 0.350269E+09 | 0.00 | 0.00 | 0.336913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.458618E+10 | 48583117.35 | 0.00 | 0.00 | 0.947185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.501398E+10 | 774458.85 | 0.00 | 0.00 | 0.126176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.494236E+10 | 758385.20 | 0.00 | 0.00 | 0.119068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303146E+10 | 0.652282E+09 | 0.00 | 0.00 | 0.501917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131999E+10 | 0.388167E+10 | 0.00 | 0.00 | 0.320003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.120307E+10 | 0.193371E+11 | 0.00 | 0.00 | 20913243.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139405E+10 | 0.413581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300868E+11 | 0.183624E+12 | 0.00 | 0.00 | 0.440595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120307E+10 | 758385.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.501398E+10 | 0.570723E+11 | 0.00 | 0.00 | 0.126176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.222445E+10 | 0.787306E+11 | 0.00 | 0.00 | 356866.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166495E+10 | 0.497779E+11 | 0.00 | 0.00 | 1429018.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150004E+10 | 0.262845E+11 | 0.00 | 0.00 | 39367865.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173004E+10 | 0.959497E+10 | 0.00 | 0.00 | 0.142701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248178E+10 | 0.491195E+09 | 0.00 | 0.00 | 0.356335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.426663E+10 | 0.102835E+09 | 0.00 | 0.00 | 0.100957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455905E+10 | 761026.76 | 0.00 | 0.00 | 0.132851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.441851E+10 | 4634309.56 | 0.00 | 0.00 | 0.122891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266709E+10 | 0.110824E+10 | 0.00 | 0.00 | 0.517952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131611E+10 | 0.611653E+10 | 0.00 | 0.00 | 0.303946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146091E+10 | 0.292479E+11 | 0.00 | 0.00 | 12634128.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182945E+10 | 0.595922E+11 | 0.00 | 0.00 | 191472.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301190E+11 | 0.261052E+12 | 0.00 | 0.00 | 0.461977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131611E+10 | 761026.76 | 0.00 | 0.00 | 191472.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.455905E+10 | 0.787306E+11 | 0.00 | 0.00 | 0.132851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195064E+11 | 0.00 | 0.00 | 413538.62 | 0.00 | 0.805616E+09 | 0.529591E+09 | 0.00 | 0.26 |
February | 0.137401E+11 | 0.00 | 0.00 | 2385443.12 | 0.00 | 85503292.08 | 0.354034E+10 | 0.00 | 0.28 |
March | 0.746489E+10 | 0.00 | 0.00 | 17298610.18 | 0.00 | 0.00 | 0.118609E+11 | 0.00 | 0.38 |
April | 0.191495E+10 | 0.253512E+09 | 0.00 | 25667691.86 | 25204420.73 | 0.00 | 0.143736E+11 | 0.00 | 0.47 |
May | 0.631238E+09 | 0.283396E+09 | 0.00 | 38641409.26 | 53430351.47 | 0.00 | 0.164607E+11 | 0.00 | 0.87 |
June | 0.192574E+09 | 0.310331E+10 | 0.00 | 30642480.09 | 0.192602E+09 | 0.00 | 0.104365E+11 | 0.00 | 0.96 |
July | 0.289017E+09 | 0.540179E+10 | 0.00 | 21183614.64 | 0.536014E+09 | 0.00 | 0.416152E+10 | 0.00 | 0.95 |
August | 0.364460E+09 | 0.554245E+10 | 0.00 | 29309458.03 | 0.199042E+09 | 0.00 | 0.639566E+10 | 0.00 | 1.01 |
September | 0.730622E+09 | 0.549101E+09 | 0.00 | 38682221.95 | 93452702.05 | 0.00 | 0.149872E+11 | 0.00 | 0.85 |
October | 0.688548E+09 | 0.00 | 0.00 | 37655078.01 | 3888482.94 | 0.00 | 0.187191E+11 | 0.00 | 0.54 |
November | 0.677229E+10 | 0.00 | 0.00 | 18385940.06 | 0.00 | 5142547.46 | 0.120531E+11 | 0.00 | 0.42 |
December | 0.150237E+11 | 0.00 | 0.00 | 3597632.44 | 0.00 | 16001072.90 | 0.422147E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.673188E+11 | 0.151336E+11 | 0.00 | 0.263863E+09 | 0.110363E+10 | 0.912263E+09 | 0.117740E+12 | 0.00 | 0.61 |
Minimum of Months | 0.192574E+09 | 0.00 | 0.00 | 413538.62 | 0.00 | 0.00 | 0.529591E+09 | 0.00 | 0.26 |
Maximum of Months | 0.195064E+11 | 0.554245E+10 | 0.00 | 38682221.95 | 0.536014E+09 | 0.805616E+09 | 0.187191E+11 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765572E+10 | 0.00 | 0.00 | 0.27 |
February | 0.144061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272676E+10 | 0.00 | 0.00 | 0.28 |
March | 0.143703E+11 | 0.00 | 0.00 | 1671633.30 | 2082754.91 | 0.321541E+09 | 0.176375E+10 | 0.00 | 0.32 |
April | 0.749532E+10 | 0.139348E+09 | 0.00 | 7770323.71 | 86431037.65 | 57232649.94 | 0.554459E+10 | 0.00 | 0.38 |
May | 0.209661E+10 | 0.203633E+09 | 0.00 | 20417431.69 | 0.107196E+09 | 0.00 | 0.983135E+10 | 0.00 | 0.62 |
June | 0.879118E+09 | 0.235532E+10 | 0.00 | 18488734.20 | 0.232148E+09 | 0.00 | 0.634317E+10 | 0.00 | 0.67 |
July | 0.496180E+09 | 0.401705E+10 | 0.00 | 12982288.43 | 0.506821E+09 | 0.00 | 0.259466E+10 | 0.00 | 0.68 |
August | 0.684841E+09 | 0.388798E+10 | 0.00 | 18140357.44 | 0.215850E+09 | 0.00 | 0.389672E+10 | 0.00 | 0.70 |
September | 0.235491E+10 | 0.403905E+09 | 0.00 | 18725639.70 | 65267966.01 | 0.00 | 0.794851E+10 | 0.00 | 0.56 |
October | 0.681069E+10 | 0.00 | 0.00 | 7976691.98 | 5253934.22 | 0.00 | 0.570215E+10 | 0.00 | 0.35 |
November | 0.111372E+11 | 0.00 | 0.00 | 3019952.14 | 0.00 | 0.116982E+10 | 0.255947E+10 | 537.20 | 0.31 |
December | 0.151411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350244E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.898392E+11 | 0.110072E+11 | 0.00 | 0.109193E+09 | 0.122105E+10 | 0.154335E+11 | 0.461844E+11 | 537.20 | 0.45 |
Minimum of Months | 0.496180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.151411E+11 | 0.401705E+10 | 0.00 | 20417431.69 | 0.506821E+09 | 0.765572E+10 | 0.983135E+10 | 537.20 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.667323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127400E+11 | 0.00 | 0.00 | 0.25 |
February | 0.855669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716198E+10 | 0.00 | 0.00 | 0.26 |
March | 0.122807E+11 | 0.00 | 0.00 | 593109.20 | 346199.23 | 0.236896E+10 | 0.869735E+09 | 0.00 | 0.31 |
April | 0.852603E+10 | 0.154317E+09 | 0.00 | 5022172.18 | 0.107081E+09 | 0.421075E+09 | 0.328916E+10 | 0.00 | 0.37 |
May | 0.289001E+10 | 0.162199E+09 | 0.00 | 17493272.00 | 68300411.99 | 0.00 | 0.849555E+10 | 0.00 | 0.60 |
June | 0.110445E+10 | 0.223296E+10 | 0.00 | 16242427.97 | 0.341796E+09 | 0.00 | 0.573534E+10 | 0.00 | 0.68 |
July | 0.554276E+09 | 0.410032E+10 | 0.00 | 11229893.89 | 0.623537E+09 | 0.00 | 0.238474E+10 | 0.00 | 0.72 |
August | 0.817437E+09 | 0.361479E+10 | 0.00 | 15976342.85 | 0.311942E+09 | 0.00 | 0.327895E+10 | 0.00 | 0.70 |
September | 0.333822E+10 | 0.343428E+09 | 0.00 | 12508975.22 | 75752084.01 | 1036896.12 | 0.542223E+10 | 0.00 | 0.52 |
October | 0.876646E+10 | 0.00 | 0.00 | 2362467.83 | 3015270.26 | 88684397.16 | 0.236277E+10 | 0.00 | 0.33 |
November | 0.842867E+10 | 0.00 | 564304.76 | 734595.17 | 12084.55 | 0.397213E+10 | 0.982722E+09 | 336908.33 | 0.29 |
December | 0.818675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849733E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.701230E+11 | 0.106080E+11 | 564304.76 | 82163256.32 | 0.153178E+10 | 0.352511E+11 | 0.328212E+11 | 336908.33 | 0.44 |
Minimum of Months | 0.554276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.122807E+11 | 0.410032E+10 | 564304.76 | 17493272.00 | 0.623537E+09 | 0.127400E+11 | 0.849555E+10 | 336908.33 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703221E+10 | 0.00 | 0.00 | 0.42 |
February | 0.196912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478714E+10 | 0.00 | 0.00 | 0.36 |
March | 0.116829E+10 | 0.00 | 0.00 | 19424.45 | 73614.84 | 0.232533E+10 | 30928126.70 | 0.00 | 0.33 |
April | 0.146886E+10 | 49283409.13 | 0.00 | 698799.40 | 21210478.16 | 0.733713E+09 | 0.392155E+09 | 0.00 | 0.38 |
May | 0.864699E+09 | 52248884.50 | 0.00 | 3828874.27 | 12720015.29 | 11854121.99 | 0.164595E+10 | 0.00 | 0.67 |
June | 0.338064E+09 | 0.740505E+09 | 0.00 | 4104706.52 | 66412448.48 | 0.00 | 0.131910E+10 | 0.00 | 0.89 |
July | 0.135757E+09 | 0.129520E+10 | 0.00 | 3006396.00 | 0.103799E+09 | 0.00 | 0.611846E+09 | 0.00 | 0.93 |
August | 0.227794E+09 | 0.110889E+10 | 0.00 | 3704381.25 | 65055243.62 | 0.00 | 0.712107E+09 | 0.00 | 0.86 |
September | 0.999473E+09 | 0.102790E+09 | 0.00 | 2110893.62 | 15206684.86 | 68312803.30 | 0.755717E+09 | 0.00 | 0.55 |
October | 0.173023E+10 | 0.00 | 0.00 | 145822.99 | 641158.64 | 0.509512E+09 | 0.135945E+09 | 0.00 | 0.33 |
November | 0.833325E+09 | 0.00 | 191567.98 | 9281.86 | 2569.63 | 0.252454E+10 | 17638562.76 | 120166.87 | 0.33 |
December | 43897844.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492963E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.811665E+10 | 0.334892E+10 | 191567.98 | 17628580.36 | 0.285121E+09 | 0.229222E+11 | 0.562139E+10 | 120166.87 | 0.53 |
Minimum of Months | 43897844.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.173023E+10 | 0.129520E+10 | 191567.98 | 4104706.52 | 0.103799E+09 | 0.703221E+10 | 0.164595E+10 | 120166.87 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428230E+10 | 0.00 | 0.00 | 0.40 |
February | 0.337928E+09 | 0.00 | 0.00 | 12465.26 | 0.00 | 0.288644E+10 | 9145409.29 | 0.00 | 0.36 |
March | 0.929900E+09 | 0.00 | 0.00 | 469921.50 | 46017.86 | 0.106161E+10 | 0.277784E+09 | 0.00 | 0.34 |
April | 0.802759E+09 | 82691699.51 | 0.00 | 1658850.00 | 6440428.54 | 0.350955E+09 | 0.929587E+09 | 0.00 | 0.53 |
May | 0.343119E+09 | 69095381.50 | 0.00 | 5341647.92 | 1869399.39 | 1151949.74 | 0.222508E+10 | 0.00 | 1.08 |
June | 0.158484E+09 | 0.717797E+09 | 0.00 | 5020187.26 | 28391770.58 | 0.00 | 0.160209E+10 | 0.00 | 1.44 |
July | 58421793.00 | 0.119918E+10 | 0.00 | 4242041.71 | 41247988.61 | 0.00 | 0.820357E+09 | 0.00 | 1.59 |
August | 99723922.12 | 0.101595E+10 | 0.00 | 4888037.84 | 25164293.84 | 0.00 | 0.954760E+09 | 0.00 | 1.37 |
September | 0.446196E+09 | 0.111564E+09 | 0.00 | 3957603.49 | 4751148.14 | 22395880.76 | 0.120751E+10 | 0.00 | 0.91 |
October | 0.104984E+10 | 0.00 | 0.00 | 476520.15 | 400798.90 | 0.196306E+09 | 0.305771E+09 | 0.00 | 0.35 |
November | 0.550822E+09 | 0.00 | 146277.33 | 50460.05 | 926.75 | 0.146752E+10 | 37772567.48 | 84137.59 | 0.32 |
December | 0.138780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315647E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.503096E+10 | 0.319627E+10 | 146277.33 | 26117735.18 | 0.108313E+09 | 0.134252E+11 | 0.836986E+10 | 84137.59 | 0.76 |
Minimum of Months | 58421793.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.104984E+10 | 0.119918E+10 | 146277.33 | 5341647.92 | 41247988.61 | 0.428230E+10 | 0.222508E+10 | 84137.59 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106039E+10 | 0.00 | 0.00 | 701945.28 | 0.00 | 0.420743E+10 | 0.520979E+09 | 0.00 | 0.35 |
February | 0.113809E+10 | 0.00 | 0.00 | 1197183.37 | 0.00 | 0.258693E+10 | 0.741507E+09 | 0.00 | 0.35 |
March | 0.136976E+10 | 58279.95 | 0.00 | 2928427.33 | 31901.98 | 0.145122E+10 | 0.168630E+10 | 0.00 | 0.45 |
April | 0.123591E+10 | 0.143211E+09 | 0.00 | 3915769.40 | 10479478.27 | 0.546799E+09 | 0.206696E+10 | 0.00 | 0.62 |
May | 0.698336E+09 | 83608600.51 | 0.00 | 6523075.80 | 6896855.30 | 13247854.29 | 0.271440E+10 | 0.00 | 0.93 |
June | 0.337318E+09 | 0.874148E+09 | 0.00 | 4989777.73 | 63479316.94 | 0.00 | 0.162526E+10 | 0.00 | 1.06 |
July | 0.142897E+09 | 0.160582E+10 | 0.00 | 4030106.80 | 84311429.46 | 0.00 | 0.767974E+09 | 0.00 | 1.16 |
August | 0.200508E+09 | 0.147097E+10 | 0.00 | 6443345.60 | 39386343.30 | 0.00 | 0.120224E+10 | 0.00 | 1.22 |
September | 0.721653E+09 | 0.226867E+09 | 0.00 | 7080156.41 | 5339291.55 | 41929974.47 | 0.219900E+10 | 0.00 | 1.02 |
October | 0.127953E+10 | 854288.74 | 0.00 | 5322643.62 | 45088.31 | 0.230014E+09 | 0.268143E+10 | 0.00 | 0.64 |
November | 0.118143E+10 | 0.00 | 211506.04 | 1252256.02 | 2811.26 | 0.159691E+10 | 0.768711E+09 | 121886.81 | 0.39 |
December | 0.601191E+09 | 0.00 | 0.00 | 1311741.00 | 0.00 | 0.365566E+10 | 0.919126E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.996702E+10 | 0.440554E+10 | 211506.04 | 45696428.34 | 0.209973E+09 | 0.143301E+11 | 0.178939E+11 | 121886.81 | 0.72 |
Minimum of Months | 0.142897E+09 | 0.00 | 0.00 | 701945.28 | 0.00 | 0.00 | 0.520979E+09 | 0.00 | 0.35 |
Maximum of Months | 0.136976E+10 | 0.160582E+10 | 211506.04 | 7080156.41 | 84311429.46 | 0.420743E+10 | 0.271440E+10 | 121886.81 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239749E+09 | 0.00 | 0.00 | 124.88 | 0.00 | 0.487014E+10 | 2583546.65 | 0.00 | 0.46 |
February | 0.356830E+09 | 0.00 | 0.00 | 95107.02 | 0.00 | 0.331644E+10 | 77228376.37 | 0.00 | 0.41 |
March | 0.824868E+09 | 0.00 | 0.00 | 602105.26 | 46111.39 | 0.123569E+10 | 0.385835E+09 | 0.00 | 0.37 |
April | 0.767975E+09 | 62871576.18 | 0.00 | 2371456.19 | 7937424.59 | 0.374606E+09 | 0.127289E+10 | 0.00 | 0.60 |
May | 0.424712E+09 | 55333334.15 | 0.00 | 5229034.43 | 5233002.92 | 10208085.24 | 0.186982E+10 | 0.00 | 1.00 |
June | 0.209891E+09 | 0.653670E+09 | 0.00 | 4078139.72 | 24404208.05 | 0.00 | 0.128756E+10 | 0.00 | 1.31 |
July | 79964094.74 | 0.132921E+10 | 0.00 | 3784729.95 | 30459578.93 | 0.00 | 0.596004E+09 | 0.00 | 1.40 |
August | 0.124488E+09 | 0.999139E+09 | 0.00 | 4647963.74 | 21768623.84 | 0.00 | 0.812028E+09 | 0.00 | 1.32 |
September | 0.545073E+09 | 0.120326E+09 | 0.00 | 3239669.43 | 5628627.01 | 43215900.87 | 0.928823E+09 | 0.00 | 0.85 |
October | 0.956789E+09 | 0.00 | 0.00 | 1196845.96 | 401613.54 | 0.237065E+09 | 0.685443E+09 | 0.00 | 0.44 |
November | 0.594801E+09 | 0.00 | 145434.74 | 124601.86 | 1947.77 | 0.151915E+10 | 84285548.55 | 84751.94 | 0.35 |
December | 0.243276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317515E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.536842E+10 | 0.322055E+10 | 145434.74 | 25369778.43 | 95881138.04 | 0.147817E+11 | 0.800249E+10 | 84751.94 | 0.74 |
Minimum of Months | 79964094.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.956789E+09 | 0.132921E+10 | 145434.74 | 5229034.43 | 30459578.93 | 0.487014E+10 | 0.186982E+10 | 84751.94 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 97707594.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680554E+10 | 0.00 | 0.00 | 0.39 |
February | 0.131037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460585E+10 | 0.00 | 0.00 | 0.33 |
March | 0.100789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256560E+10 | 0.00 | 0.00 | 0.31 |
April | 0.132246E+10 | 16536617.33 | 0.00 | 112946.50 | 21351889.22 | 0.938755E+09 | 66910045.18 | 0.00 | 0.30 |
May | 0.129343E+10 | 39845914.84 | 0.00 | 1134192.03 | 12108526.12 | 9729601.11 | 0.504820E+09 | 0.00 | 0.44 |
June | 0.429392E+09 | 0.564911E+09 | 0.00 | 2767365.71 | 43070526.32 | 0.00 | 0.835691E+09 | 0.00 | 0.64 |
July | 0.130536E+09 | 0.969842E+09 | 0.00 | 2411531.34 | 0.118045E+09 | 0.00 | 0.472661E+09 | 0.00 | 0.71 |
August | 0.211642E+09 | 0.100792E+10 | 0.00 | 3192240.59 | 51851331.27 | 0.00 | 0.670336E+09 | 0.00 | 0.73 |
September | 0.928367E+09 | 0.105680E+09 | 0.00 | 2387725.64 | 20838515.34 | 2398519.06 | 0.900071E+09 | 0.00 | 0.52 |
October | 0.206969E+10 | 0.00 | 0.00 | 197606.49 | 821512.87 | 45423221.67 | 0.167053E+09 | 0.00 | 0.30 |
November | 0.122672E+10 | 0.00 | 0.00 | 8461.64 | 0.00 | 0.200049E+10 | 38570331.91 | 0.00 | 0.31 |
December | 70005862.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466643E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.891888E+10 | 0.270473E+10 | 0.00 | 12212069.94 | 0.268088E+09 | 0.216402E+11 | 0.365611E+10 | 0.00 | 0.44 |
Minimum of Months | 70005862.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.206969E+10 | 0.100792E+10 | 0.00 | 3192240.59 | 0.118045E+09 | 0.680554E+10 | 0.900071E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461234E+10 | 0.00 | 0.00 | 0.42 |
February | 0.356469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327262E+10 | 0.00 | 0.00 | 0.38 |
March | 0.102230E+10 | 0.00 | 0.00 | 112459.73 | 0.00 | 0.115310E+10 | 85848065.19 | 0.00 | 0.32 |
April | 0.874250E+09 | 44678486.73 | 0.00 | 845077.58 | 3551911.47 | 0.389153E+09 | 0.401933E+09 | 0.00 | 0.38 |
May | 0.434323E+09 | 57006847.71 | 0.00 | 3317894.19 | 4251792.58 | 0.00 | 0.131957E+10 | 0.00 | 0.73 |
June | 0.166655E+09 | 0.608009E+09 | 0.00 | 4042935.51 | 16834206.77 | 0.00 | 0.124850E+10 | 0.00 | 1.14 |
July | 52770875.38 | 0.101377E+10 | 0.00 | 3597721.39 | 55604937.16 | 0.00 | 0.684889E+09 | 0.00 | 1.29 |
August | 94870379.28 | 0.980069E+09 | 0.00 | 4445638.08 | 24050899.10 | 0.00 | 0.948167E+09 | 0.00 | 1.24 |
September | 0.346476E+09 | 0.118728E+09 | 0.00 | 4481311.43 | 9937058.16 | 0.00 | 0.144179E+10 | 0.00 | 0.89 |
October | 0.972715E+09 | 0.00 | 0.00 | 1083668.33 | 520103.53 | 5254139.93 | 0.590863E+09 | 0.00 | 0.33 |
November | 0.803233E+09 | 0.00 | 0.00 | 104502.48 | 0.00 | 0.114991E+10 | 0.109060E+09 | 0.00 | 0.31 |
December | 0.305835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296456E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.556996E+10 | 0.282227E+10 | 0.00 | 22031208.71 | 0.114751E+09 | 0.135469E+11 | 0.683062E+10 | 0.00 | 0.65 |
Minimum of Months | 52770875.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.102230E+10 | 0.101377E+10 | 0.00 | 4481311.43 | 55604937.16 | 0.461234E+10 | 0.144179E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961455E+10 | 0.00 | 0.00 | 0.56 |
February | 0.474705E+09 | 0.00 | 0.00 | 50503.26 | 0.00 | 0.610380E+10 | 37539975.13 | 0.00 | 0.46 |
March | 0.962434E+09 | 0.00 | 0.00 | 312417.50 | 0.00 | 0.401156E+10 | 0.184265E+09 | 0.00 | 0.45 |
April | 0.894384E+09 | 98517536.75 | 0.00 | 782795.03 | 4345494.38 | 0.193378E+10 | 0.367968E+09 | 0.00 | 0.43 |
May | 0.124762E+10 | 72921011.33 | 0.00 | 1469626.61 | 10375268.16 | 0.314057E+09 | 0.497701E+09 | 0.00 | 0.53 |
June | 0.538562E+09 | 0.734479E+09 | 0.00 | 2394486.42 | 48474818.59 | 0.114407E+09 | 0.633573E+09 | 0.00 | 0.70 |
July | 0.188568E+09 | 0.128988E+10 | 0.00 | 2481741.14 | 0.121600E+09 | 1561911.65 | 0.434501E+09 | 0.00 | 0.84 |
August | 0.242570E+09 | 0.146963E+10 | 0.00 | 4589550.04 | 44660188.39 | 19040217.82 | 0.885576E+09 | 0.00 | 1.01 |
September | 0.797875E+09 | 0.253269E+09 | 0.00 | 5439804.27 | 10304860.74 | 0.218499E+09 | 0.152071E+10 | 0.00 | 0.87 |
October | 0.138466E+10 | 869561.77 | 0.00 | 2823923.98 | 179123.85 | 0.632953E+09 | 0.142831E+10 | 0.00 | 0.49 |
November | 0.111802E+10 | 0.00 | 0.00 | 655225.65 | 0.00 | 0.318113E+10 | 0.375444E+09 | 0.00 | 0.45 |
December | 0.623752E+09 | 0.00 | 0.00 | 5450.14 | 0.00 | 0.665189E+10 | 12207321.64 | 0.00 | 0.47 |
Annual Sum or Average | 0.876469E+10 | 0.391956E+10 | 0.00 | 21005524.03 | 0.239939E+09 | 0.327972E+11 | 0.637780E+10 | 0.00 | 0.61 |
Minimum of Months | 0.188568E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1561911.65 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.138466E+10 | 0.146963E+10 | 0.00 | 5439804.27 | 0.121600E+09 | 0.961455E+10 | 0.152071E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507556E+10 | 0.00 | 0.00 | 0.46 |
February | 0.344010E+09 | 0.00 | 0.00 | 18723.86 | 0.00 | 0.334522E+10 | 16205036.51 | 0.00 | 0.38 |
March | 0.872554E+09 | 0.00 | 0.00 | 194705.93 | 0.00 | 0.130886E+10 | 0.119989E+09 | 0.00 | 0.32 |
April | 0.891380E+09 | 34727877.26 | 0.00 | 1120504.32 | 6422307.75 | 0.346392E+09 | 0.527576E+09 | 0.00 | 0.40 |
May | 0.569188E+09 | 46826654.65 | 0.00 | 2709899.36 | 7159128.44 | 2688342.86 | 0.922365E+09 | 0.00 | 0.64 |
June | 0.222884E+09 | 0.546207E+09 | 0.00 | 3350991.72 | 19508790.88 | 0.00 | 0.950743E+09 | 0.00 | 1.02 |
July | 69219179.00 | 0.109501E+10 | 0.00 | 3116616.55 | 34361138.03 | 0.00 | 0.486472E+09 | 0.00 | 1.14 |
August | 88850977.74 | 0.987775E+09 | 0.00 | 4190333.81 | 17249546.02 | 0.00 | 0.824646E+09 | 0.00 | 1.21 |
September | 0.423831E+09 | 0.130510E+09 | 0.00 | 3501732.31 | 9040298.16 | 1565348.12 | 0.113391E+10 | 0.00 | 0.82 |
October | 0.104482E+10 | 0.00 | 0.00 | 1355177.64 | 521017.51 | 11181323.43 | 0.691603E+09 | 0.00 | 0.38 |
November | 0.826489E+09 | 0.00 | 0.00 | 144594.73 | 0.00 | 0.116117E+10 | 0.151339E+09 | 0.00 | 0.32 |
December | 0.307788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304905E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.582712E+10 | 0.284106E+10 | 0.00 | 19703280.23 | 94262226.79 | 0.143017E+11 | 0.582485E+10 | 0.00 | 0.62 |
Minimum of Months | 69219179.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.104482E+10 | 0.109501E+10 | 0.00 | 4190333.81 | 34361138.03 | 0.507556E+10 | 0.113391E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638621E+10 | 0.00 | 0.00 | 0.37 |
February | 0.475351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431859E+10 | 0.00 | 0.00 | 0.33 |
March | 0.174232E+10 | 0.00 | 0.00 | 36748.83 | 438392.48 | 0.174251E+10 | 40820249.20 | 0.00 | 0.32 |
April | 0.179316E+10 | 51060915.79 | 0.00 | 831341.69 | 12942579.43 | 0.412196E+09 | 0.452481E+09 | 0.00 | 0.38 |
May | 0.766832E+09 | 65012086.17 | 0.00 | 4232109.14 | 21558182.23 | 288668.03 | 0.181467E+10 | 0.00 | 0.68 |
June | 0.254458E+09 | 0.783791E+09 | 0.00 | 4582381.91 | 48069487.09 | 0.00 | 0.143213E+10 | 0.00 | 0.87 |
July | 0.110606E+09 | 0.125082E+10 | 0.00 | 3261604.17 | 99410308.36 | 0.00 | 0.640401E+09 | 0.00 | 0.88 |
August | 0.204552E+09 | 0.119297E+10 | 0.00 | 3828025.60 | 43964056.41 | 0.00 | 0.771020E+09 | 0.00 | 0.84 |
September | 0.946194E+09 | 0.122900E+09 | 0.00 | 2643198.25 | 13780008.96 | 12277722.90 | 0.102140E+10 | 0.00 | 0.56 |
October | 0.212714E+10 | 0.00 | 0.00 | 347155.29 | 1105883.95 | 0.105799E+09 | 0.263498E+09 | 0.00 | 0.33 |
November | 0.118821E+10 | 0.00 | 0.00 | 44589.43 | 0.00 | 0.203987E+10 | 89222434.17 | 149.92 | 0.32 |
December | 90303578.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457132E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.983964E+10 | 0.346656E+10 | 0.00 | 19807154.30 | 0.241269E+09 | 0.195891E+11 | 0.652565E+10 | 149.92 | 0.52 |
Minimum of Months | 90303578.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.212714E+10 | 0.125082E+10 | 0.00 | 4582381.91 | 99410308.36 | 0.638621E+10 | 0.181467E+10 | 149.92 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147795E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380902E+10 | 0.00 | 0.00 | 0.35 |
February | 0.449843E+09 | 0.00 | 0.00 | 31265.51 | 0.00 | 0.257642E+10 | 18332082.44 | 0.00 | 0.32 |
March | 0.920853E+09 | 0.00 | 0.00 | 593589.91 | 277762.63 | 0.788091E+09 | 0.354698E+09 | 0.00 | 0.30 |
April | 0.832204E+09 | 66051150.14 | 0.00 | 1901007.10 | 4962541.61 | 0.166954E+09 | 0.986155E+09 | 0.00 | 0.49 |
May | 0.304761E+09 | 80742171.65 | 0.00 | 5427848.41 | 4613555.05 | 0.00 | 0.222252E+10 | 0.00 | 1.04 |
June | 0.124138E+09 | 0.707722E+09 | 0.00 | 5100162.52 | 21962384.30 | 0.00 | 0.157248E+10 | 0.00 | 1.33 |
July | 46194708.94 | 0.109737E+10 | 0.00 | 4255017.30 | 49837063.05 | 0.00 | 0.814853E+09 | 0.00 | 1.43 |
August | 97230836.34 | 0.998619E+09 | 0.00 | 4772296.06 | 23101261.68 | 0.00 | 0.994954E+09 | 0.00 | 1.27 |
September | 0.388150E+09 | 0.115864E+09 | 0.00 | 4359766.63 | 5668990.83 | 4028455.96 | 0.140193E+10 | 0.00 | 0.89 |
October | 0.935363E+09 | 7102.37 | 0.00 | 965181.46 | 693578.52 | 48929396.26 | 0.549521E+09 | 0.00 | 0.33 |
November | 0.613578E+09 | 0.00 | 0.00 | 145361.51 | 0.00 | 0.108682E+10 | 0.114307E+09 | 208.61 | 0.27 |
December | 0.262137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260005E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.512225E+10 | 0.306637E+10 | 0.00 | 27551496.43 | 0.111117E+09 | 0.110803E+11 | 0.902975E+10 | 208.61 | 0.70 |
Minimum of Months | 46194708.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.935363E+09 | 0.109737E+10 | 0.00 | 5427848.41 | 49837063.05 | 0.380902E+10 | 0.222252E+10 | 208.61 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121592E+10 | 0.00 | 0.00 | 1080720.06 | 0.00 | 0.381762E+10 | 0.761375E+09 | 0.00 | 0.34 |
February | 0.151226E+10 | 0.00 | 0.00 | 1505013.22 | 0.00 | 0.219245E+10 | 0.919834E+09 | 0.00 | 0.36 |
March | 0.163459E+10 | 249442.36 | 0.00 | 3604351.97 | 284015.38 | 0.116787E+10 | 0.197565E+10 | 0.00 | 0.48 |
April | 0.149452E+10 | 0.135337E+09 | 0.00 | 4265504.07 | 8462763.36 | 0.304688E+09 | 0.212779E+10 | 0.00 | 0.62 |
May | 0.652813E+09 | 0.109770E+09 | 0.00 | 6748786.82 | 12463974.61 | 290030.82 | 0.275936E+10 | 0.00 | 0.93 |
June | 0.281991E+09 | 0.924676E+09 | 0.00 | 5304598.78 | 48119513.98 | 0.00 | 0.164559E+10 | 0.00 | 1.01 |
July | 0.123273E+09 | 0.152626E+10 | 0.00 | 4041523.07 | 89968414.57 | 0.00 | 0.724745E+09 | 0.00 | 1.06 |
August | 0.185607E+09 | 0.156678E+10 | 0.00 | 6058823.13 | 31421533.52 | 0.00 | 0.117742E+10 | 0.00 | 1.16 |
September | 0.648377E+09 | 0.257737E+09 | 0.00 | 7516883.86 | 8638429.22 | 9002960.53 | 0.249598E+10 | 0.00 | 1.02 |
October | 0.133409E+10 | 1705634.37 | 0.00 | 6996190.55 | 146258.31 | 60039072.09 | 0.327497E+10 | 0.00 | 0.70 |
November | 0.148017E+10 | 0.00 | 0.00 | 1925442.15 | 0.00 | 0.121074E+10 | 0.115697E+10 | 232.70 | 0.41 |
December | 0.786047E+09 | 0.00 | 0.00 | 1803941.82 | 0.00 | 0.329661E+10 | 0.125286E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.113497E+11 | 0.452251E+10 | 0.00 | 50851779.50 | 0.199505E+09 | 0.120593E+11 | 0.202725E+11 | 232.70 | 0.71 |
Minimum of Months | 0.123273E+09 | 0.00 | 0.00 | 1080720.06 | 0.00 | 0.00 | 0.724745E+09 | 0.00 | 0.34 |
Maximum of Months | 0.163459E+10 | 0.156678E+10 | 0.00 | 7516883.86 | 89968414.57 | 0.381762E+10 | 0.327497E+10 | 232.70 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321458E+09 | 0.00 | 0.00 | 2743.71 | 0.00 | 0.439269E+10 | 5887678.60 | 0.00 | 0.41 |
February | 0.577313E+09 | 0.00 | 0.00 | 114964.95 | 0.00 | 0.310641E+10 | 92041129.23 | 0.00 | 0.39 |
March | 0.109432E+10 | 0.00 | 0.00 | 710900.28 | 276674.25 | 0.952110E+09 | 0.447776E+09 | 0.00 | 0.37 |
April | 0.968000E+09 | 55953488.60 | 0.00 | 2546986.02 | 6391891.68 | 0.187641E+09 | 0.130518E+10 | 0.00 | 0.60 |
May | 0.381505E+09 | 73037477.64 | 0.00 | 5166636.42 | 9013324.37 | 182181.53 | 0.188292E+10 | 0.00 | 1.00 |
June | 0.161043E+09 | 0.691751E+09 | 0.00 | 4310014.87 | 17758239.86 | 0.00 | 0.129363E+10 | 0.00 | 1.25 |
July | 69626943.16 | 0.124489E+10 | 0.00 | 3694718.77 | 28898716.16 | 0.00 | 0.551925E+09 | 0.00 | 1.26 |
August | 0.113212E+09 | 0.107549E+10 | 0.00 | 4401020.74 | 15701889.52 | 0.00 | 0.804601E+09 | 0.00 | 1.26 |
September | 0.505311E+09 | 0.142915E+09 | 0.00 | 3410319.74 | 5716789.92 | 10892029.87 | 0.108537E+10 | 0.00 | 0.85 |
October | 0.110989E+10 | 7074.54 | 0.00 | 1574213.71 | 690860.83 | 63936178.33 | 0.847739E+09 | 0.00 | 0.46 |
November | 0.818468E+09 | 0.00 | 0.00 | 190871.78 | 0.00 | 0.118988E+10 | 0.176483E+09 | 214.09 | 0.34 |
December | 0.332506E+09 | 0.00 | 0.00 | 2489.27 | 0.00 | 0.283766E+10 | 6185293.30 | 0.00 | 0.33 |
Annual Sum or Average | 0.645265E+10 | 0.328404E+10 | 0.00 | 26125880.25 | 84448386.58 | 0.127414E+11 | 0.849973E+10 | 214.09 | 0.71 |
Minimum of Months | 69626943.16 | 0.00 | 0.00 | 2489.27 | 0.00 | 0.00 | 5887678.60 | 0.00 | 0.33 |
Maximum of Months | 0.110989E+10 | 0.124489E+10 | 0.00 | 5166636.42 | 28898716.16 | 0.439269E+10 | 0.188292E+10 | 214.09 | 1.26 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.208939E+12 | 0.247249E+11 | 0.00 | 0.160934E+12 | 0.619653E+11 |
February | 0.227121E+12 | 0.188256E+11 | 0.00 | 0.147158E+12 | 0.453029E+11 |
March | 0.326418E+12 | 0.169841E+11 | 0.00 | 0.171732E+12 | 0.313677E+11 |
April | 0.378934E+12 | 0.104190E+11 | 0.00 | 0.178921E+12 | 0.348450E+11 |
May | 0.428867E+12 | 0.592233E+10 | 0.00 | 0.207608E+12 | 0.561339E+11 |
June | 0.441916E+12 | 0.119428E+10 | 0.00 | 0.100420E+12 | 0.159883E+12 |
July | 0.444009E+12 | -351605107.2 | 0.00 | 0.322828E+11 | 0.220098E+12 |
August | 0.388804E+12 | 0.750234E+09 | 0.00 | 0.745095E+11 | 0.208469E+12 |
September | 0.279426E+12 | 0.494675E+10 | 0.00 | 0.167232E+12 | 0.875125E+11 |
October | 0.221720E+12 | 0.107035E+11 | 0.00 | 0.200381E+12 | 0.139374E+11 |
November | 0.142970E+12 | 0.157635E+11 | 0.00 | 0.160141E+12 | 0.284628E+11 |
December | 0.120686E+12 | 0.207724E+11 | 0.00 | 0.152428E+12 | 0.503781E+11 |
Annual Sum or Average | 0.360981E+13 | 0.130655E+12 | 0.00 | 0.175375E+13 | 0.998356E+12 |
Minimum of Months | 0.120686E+12 | -351605107.2 | 0.00 | 0.322828E+11 | 0.139374E+11 |
Maximum of Months | 0.444009E+12 | 0.247249E+11 | 0.00 | 0.207608E+12 | 0.220098E+12 |