Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:20:12
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1331.11 | 267.17 | 267.17 |
Net Site Energy | 1331.11 | 267.17 | 267.17 |
Total Source Energy | 4191.90 | 841.38 | 841.38 |
Net Source Energy | 4191.90 | 841.38 | 841.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 11.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 154.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1319.72 | 11.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 11.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 154.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 11.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 154.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 87.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 48.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.31 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 264.89 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 58.31 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 264.89 | 2.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1319.718 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1319.718 | 100.00 |
Total On-Site and Utility Electric Sources | 1319.718 | 100.00 |
Total Electricity End Uses | 1319.718 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 37.50 |
Time Setpoint Not Met During Occupied Cooling | 150.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 507.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-10:00 | 03-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 10-FEB-12:09 |
Heating | 0.00 | 83717.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 58112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41666.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13267.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4476.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 138612.09 | 83717.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 83717.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 58112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 53.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13267.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4476.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 488.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 736.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 158.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 276.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 154.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4179.55 | 12.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 55.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 838.90 | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 97.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 55.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 838.90 | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.53 | 0.295660 | 0.251000 | 0.636249 | 0.788426 | 0.500000 | 0.001289 | 0.000084 | 0.636249 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.01 | 0.372330 | 0.316000 | 0.636069 | 0.992880 | 0.500000 | 0.001023 | 0.000143 | 0.636069 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.08 | 0.360415 | 0.306000 | 0.636303 | 0.961107 | 0.500000 | 0.001057 | 0.000237 | 0.819480 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.600793 | 0.262972 | 0.224000 | 0.134578 | 0.701258 | 0.500000 | 0.001449 | 0.000102 | 0.337212 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.654366 | 0.152853 | 0.130000 | 0.085068 | 0.407608 | 0.500000 | 0.002493 | 0.000067 | 0.220373 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.819551 | 0.192778 | 0.164000 | 0.134406 | 0.514075 | 0.500000 | 0.001976 | 0.000102 | 0.337665 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.732732 | 0.136496 | 0.116000 | 0.084997 | 0.363990 | 0.500000 | 0.002791 | 0.000066 | 0.219956 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.473756 | 0.333488 | 0.283000 | 0.134073 | 0.889300 | 0.500000 | 0.001142 | 0.000069 | 0.238510 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.553598 | 0.180676 | 0.154000 | 0.085254 | 0.481802 | 0.500000 | 0.002109 | 0.000046 | 0.159333 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.667059 | 0.236848 | 0.201000 | 0.134079 | 0.631595 | 0.500000 | 0.001609 | 0.000069 | 0.239666 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.591877 | 0.168980 | 0.144000 | 0.085230 | 0.450612 | 0.500000 | 0.002255 | 0.000046 | 0.158577 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.524784 | 0.301060 | 0.256000 | 0.134345 | 0.802828 | 0.500000 | 0.001266 | 0.000075 | 0.259625 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.645144 | 0.413434 | 0.500000 | 0.002457 | 0.000050 | 0.172356 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.739476 | 0.213654 | 0.182000 | 0.134585 | 0.569743 | 0.500000 | 0.001783 | 0.000075 | 0.260368 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.673283 | 0.148549 | 0.126000 | 0.084834 | 0.396130 | 0.500000 | 0.002565 | 0.000049 | 0.171642 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 9619.60 | 0.000084 | 204.61 |
CORE_MID VAV BOX REHEAT COIL | 16384.92 | 0.000143 | 393.59 |
CORE_TOP VAV BOX REHEAT COIL | 27060.24 | 0.000237 | 714.83 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11655.64 | 0.000102 | 312.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7611.86 | 0.000067 | 204.30 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11670.93 | 0.000102 | 313.32 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7597.80 | 0.000066 | 203.93 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7861.21 | 0.000069 | 207.49 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5250.53 | 0.000046 | 138.57 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7899.16 | 0.000069 | 208.48 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5225.72 | 0.000046 | 137.91 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8554.99 | 0.000075 | 225.77 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5678.55 | 0.000050 | 149.85 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8579.39 | 0.000075 | 226.41 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5655.10 | 0.000049 | 149.23 |
PACU_VAV_BOT HEATING COIL | 7029.49 | 0.000061 | 124.62 |
PACU_VAV_MID HEATING COIL | 8407.96 | 0.000074 | 147.56 |
PACU_VAV_TOP HEATING COIL | 6318.08 | 0.000055 | 112.59 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.41 | 1.07 | 4.82 | 1.22 | 4.28 | 4.28 | 0.300000 | 0.285318 | 4.28 |
PACU_VAV_MID | 2.30 | 1.07 | 4.60 | 1.30 | 3.93 | 3.93 | 0.300000 | 0.330347 | 3.93 |
PACU_VAV_TOP | 2.44 | 1.08 | 4.89 | 2.00 | 4.52 | 4.52 | 0.300000 | 0.441370 | 4.52 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.28 |
PACU_VAV_MID_OA_CONTROLLER | 3.93 |
PACU_VAV_TOP_OA_CONTROLLER | 4.52 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.28 | 76127.74 | 0.800055 | 1.43 | 25373.37 | 0.800055 |
PACU_VAV_MID COOLING COIL | 3.93 | 70563.62 | 0.800771 | 1.31 | 23518.85 | 0.800771 |
PACU_VAV_TOP COOLING COIL | 4.52 | 79957.63 | 0.800208 | 1.51 | 26649.88 | 0.800208 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.28 |
PACU_VAV_MID FAN | 3.93 |
PACU_VAV_TOP FAN | 4.52 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000061 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000074 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000055 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001470 | 0.176433 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.001470 | 438.40 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 168061.17 | 168061.17 | 0.001470 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9622 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9482 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.202 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8052 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8206 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5978 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27384127E-12 | 0.12865281E-14 | -0.83346422E-13 | 0.81323336E-16 |
43 | 6 | 0.26454352E-07 | 0.26406074E-09 | 0.60786733E-08 | -0.12333448E-12 |
44 | 5 | -0.17878666E-03 | 0.22931636E-05 | -0.92101048E-04 | 0.60153540E-08 |
45 | 4 | 0.27880517 | 0.11305828E-02 | 0.94889811E-01 | -0.31698392E-04 |
46 | 3 | -7.0018852 | 0.35426556E-01 | -2.2604600 | 0.27713709E-01 |
47 | 2 | 39.998753 | 0.12720283 | 14.942758 | -0.32362551 |
48 | 1 | -79.877006 | 0.57894353E-01 | -28.852534 | 1.0643678 |
49 | 0 | 46.824343 | 0.11744712E-02 | 16.298269 | |
50 | 7 | -0.27620064E-12 | 0.12774393E-14 | -0.83964131E-13 | 0.81942822E-16 |
51 | 6 | 0.26622461E-07 | 0.26074659E-09 | 0.61157793E-08 | -0.12423095E-12 |
52 | 5 | -0.17965003E-03 | 0.22617301E-05 | -0.92535175E-04 | 0.60516003E-08 |
53 | 4 | 0.27982997 | 0.11139309E-02 | 0.95257664E-01 | -0.31841476E-04 |
54 | 3 | -7.0222151 | 0.34872839E-01 | -2.2664901 | 0.27813240E-01 |
55 | 2 | 40.065841 | 0.12511414 | 14.967577 | -0.32437249 |
56 | 1 | -79.928458 | 0.56904129E-01 | -28.874810 | 1.0654641 |
57 | 0 | 46.824343 | 0.11535943E-02 | 16.297719 | |
58 | 7 | -0.27931930E-12 | 0.13886628E-14 | -0.87137092E-13 | 0.18759942E-15 |
59 | 6 | 0.23561308E-07 | 0.31712788E-09 | 0.54400317E-08 | -0.10799411E-12 |
60 | 5 | -0.16378969E-03 | 0.28142694E-05 | -0.84539011E-04 | 0.53904798E-08 |
61 | 4 | 0.26080053 | 0.14141629E-02 | 0.88437074E-01 | -0.29205444E-04 |
62 | 3 | -6.6442204 | 0.45062581E-01 | -2.1544048 | 0.25964059E-01 |
63 | 2 | 38.817908 | 0.16418932 | 14.505027 | -0.31048073 |
64 | 1 | -78.970774 | 0.75677137E-01 | -28.459322 | 1.0450580 |
65 | 0 | 46.824349 | 0.15543837E-02 | 16.308247 | |
66 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
75 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
76 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
77 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
78 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
79 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
80 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
81 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
82 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
83 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
84 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
85 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
86 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
87 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
88 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
89 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
90 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
91 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
92 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
93 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
94 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
95 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
96 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
97 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.424_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.409 | 2.409 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98174E-002 | 0.16038 | 0.62134 | 0.62134 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2596E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3063E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8441E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8848E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4129E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4452E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9048E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9212E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1049 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8915E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1175 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3547E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7984E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1427E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1945E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1958E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2582E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3009E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8425E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8788E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4116E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4409E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9047E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9210E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3040E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5262E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8840E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2434E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2347E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1353E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7535E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7678E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0505E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0673E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7300E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7421E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7081E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7122E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3903E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3960E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9488E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9862E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4780E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5072E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1646E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1839E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9047E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9210E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7451E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5619E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1216E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1934E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9474E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2401E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1945E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9492E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9865E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4785E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5082E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1655E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1867E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9212E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7498E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7326E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4291E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4963E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6380E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3195E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7535E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7679E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3516E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3965E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1014E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1495E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9640E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9841E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3905E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3961E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.0090E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1154 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5558E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3127E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0189E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.6447E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6997E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1653E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4479E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7672E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1779E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1395E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0793E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6836E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7257E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1454E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0548E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4790E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6195E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3034E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2150E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6447E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6997E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5978E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6462E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.2958E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4208E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5314E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2563E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6836E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7257E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1048 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.0084E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1154 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5550E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3122E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0184E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.6443E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6995E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1653E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4477E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7671E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1777E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1392E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0791E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6832E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7255E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1455E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0547E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4791E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6194E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3033E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2149E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6443E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6995E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5977E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6460E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.2957E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4206E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5311E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2560E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6833E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7255E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34539.40823 | 34539.40823 | 2.53485 | 2.53485 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3332.45307 | 3332.45307 | 0.14377 | 0.42469 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27455.51374 | 27455.51374 | 2.01288 | 2.01288 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 10099.53319 | 10099.53319 | 0.43356 | 0.43356 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28087.94804 | 28087.94804 | 2.07942 | 2.07942 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.23349E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 18962.47160 | 18962.47160 | 0.81948 | 0.81948 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8115.40371 | 8115.40371 | 0.60079 | 0.60079 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 8449.31856 | 8449.31856 | 0.33721 | 0.33721 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8839.10933 | 8839.10933 | 0.65437 | 0.65437 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 5516.47776 | 5516.47776 | 0.22037 | 0.22037 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 11070.37775 | 11070.37775 | 0.81955 | 0.81955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 8460.30300 | 8460.30300 | 0.33767 | 0.33767 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9897.67159 | 9897.67159 | 0.73273 | 0.73273 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 5506.39320 | 5506.39320 | 0.21996 | 0.21996 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6399.36701 | 6399.36701 | 0.47376 | 0.47376 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 5505.32460 | 5505.32460 | 0.23851 | 0.23851 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7477.91896 | 7477.91896 | 0.55360 | 0.55360 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.22614E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3676.69920 | 3676.69920 | 0.15933 | 0.15933 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9010.49487 | 9010.49487 | 0.66706 | 0.66706 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 5531.85222 | 5531.85222 | 0.23967 | 0.23967 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7994.98928 | 7994.98928 | 0.59188 | 0.59188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.23151E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3659.35211 | 3659.35211 | 0.15858 | 0.15858 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7088.66626 | 7088.66626 | 0.52478 | 0.52478 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30000 | 8.23349E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5990.78740 | 5990.78740 | 0.25963 | 0.25963 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8714.54034 | 8714.54034 | 0.64514 | 0.64514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12317 | 8.22530E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3976.25065 | 3976.25065 | 0.17236 | 0.17236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9988.70898 | 9988.70898 | 0.73948 | 0.73948 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.23290E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6007.84854 | 6007.84854 | 0.26037 | 0.26037 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9094.62535 | 9094.62535 | 0.67328 | 0.67328 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3959.85063 | 3959.85063 | 0.17164 | 0.17164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 65190.67 | 4.27865 | 4.27865 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 9722.64 | 1.22078 | 1.22078 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 60516.89 | 3.92786 | 3.92786 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 9844.05 | 1.29755 | 1.29755 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 68403.72 | 4.52219 | 4.52219 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 9813.89 | 1.99596 | 1.99596 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53485 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29566 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63625 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78843 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28864E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.41565E-005 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63625 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9619.60369 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.41565E-005 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 204.61469 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.01288 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37233 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63607 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99288 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02329E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43342E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63607 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16384.91834 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43342E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.59053 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07942 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36042 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63630 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96111 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05711E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.36735E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81948 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27060.24315 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.36735E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 714.82762 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60079 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26297 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13458 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70126 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44883E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01969E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33721 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11655.63677 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01969E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 312.91422 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65437 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15285 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50676E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40761 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49259E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.65918E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22037 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7611.85602 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.65918E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 204.30497 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81955 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19278 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13441 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51408 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97636E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02102E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33767 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11670.93339 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02102E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 313.32164 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73273 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13650 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49969E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36399 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79128E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.64689E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21996 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7597.80343 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.64689E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 203.93086 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47376 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33349 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88930 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14247E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.87733E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23851 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7861.21059 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.87733E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 207.48507 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55360 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18068 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52541E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48180 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10875E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.59340E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15933 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5250.53330 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59340E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 138.56764 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66706 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23685 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63159 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60863E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.91053E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23967 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7899.16213 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.91053E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 208.48497 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59188 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16898 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14400 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52303E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45061 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25471E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.57169E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15858 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5225.71819 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.57169E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 137.91377 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52478 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30106 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13434 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80283 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26553E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.48428E-005 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25963 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8554.98814 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.48428E-005 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 225.77002 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64514 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41343 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45746E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.96785E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17236 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5678.55397 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96785E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.85006 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73948 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21365 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18200 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13458 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56974 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78326E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.50563E-005 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26037 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8579.39323 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.50563E-005 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 226.41313 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67328 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14855 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48336E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39613 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56482E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.94733E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.17164 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5655.09738 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.94733E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.23187 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.41057 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07488 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.82115 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22078 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.27865 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.27865 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28532 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.29778 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07499 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.59556 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.29755 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.92786 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.92786 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33035 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.44343 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07535 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.88686 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99596 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.52219 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.52219 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.44137 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.27865 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.92786 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.52219 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.27865 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.27865 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 76127.73742 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80006 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.42608 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25373.37488 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80006 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 7029.48690 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.14970E-005 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 124.62338 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.27865 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.14970E-005 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.92786 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.92786 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 70563.62018 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80077 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.30915 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 23518.85461 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80077 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 8407.95794 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.35565E-005 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 147.55722 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.92786 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.35565E-005 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.52219 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.52219 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 79957.63400 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80021 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.50725 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26649.87941 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80021 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 6318.07729 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.52733E-005 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 112.58776 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.52219 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.52733E-005 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.47027E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.17643 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.47027E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 438.39752 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 168061.17383 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 168061.17000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47027E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 9118.54 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 15522.10 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 25646.42 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 11055.05 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7219.65 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 11069.56 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7206.32 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7449.29 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4975.33 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7485.25 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4951.82 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 8106.54 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5380.83 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 8129.66 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5358.60 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 6250.94 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 7337.60 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 5671.46 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 75065.40 | 256133.77 | 11.78 | 3.05 | 3.37 | 3.54 | 3.75 | 10.39 | 11.50 | 12.09 | 12.80 | 4.8567 | 3.8553 | 2.5879 | 1.0504 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 69608.37 | 237513.61 | 11.80 | 3.05 | 3.38 | 3.55 | 3.76 | 10.41 | 11.52 | 12.12 | 12.83 | 4.4585 | 3.5426 | 2.3788 | 0.9600 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 78819.98 | 268944.92 | 11.76 | 3.04 | 3.37 | 3.54 | 3.74 | 10.38 | 11.48 | 12.08 | 12.78 | 5.1332 | 4.0730 | 2.7338 | 1.1116 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.202 | 1.019 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.962 | 0.841 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_NORTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_EAST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_SOUTH_0.249 | N/A | 2.409 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.948 | 0.830 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.424_SHGC_WEST_0.249 | N/A | 2.409 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8971234723E-003 | 4.9723748787E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.7632557057E-002 | 4.4694198503E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.9546930471E-003 | 6.5029741951E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.3925998412E-003 | 5.9707113276E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.9759976021E-003 | 5.5751673510E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8192720741E-002 | 1.0930410369E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0810724176E-002 | 2.0770701083E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.6653370027E-002 | 8.6920824599E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.1062949930E-002 | 7.3620040312E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.5720020207E-002 | 3.4607284220E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1156542830E-002 | 1.7340903653E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.4912499605E-002 | 7.5966444292E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.4865328339E-002 | 5.9454823053E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.2141227626E-002 | 3.0344452552E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3906924143E-002 | 1.8649009766E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.5132051411E-002 | 8.9211821148E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8180331166E-002 | 7.4476132938E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7657732844E-002 | 3.3742711415E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3522.24 | 35.53 | 0.00 | 2080.45 | 845.86 | 6484.10 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.019 | 1.202 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.841 | 0.962 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.830 | 0.948 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.424_SHGC_NORTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.424_SHGC_EAST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.424_SHGC_EAST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.424_SHGC_WEST_0.249 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.424_SHGC_WEST_0.249 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.409 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.424_SHGC_NORTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.424_SHGC_EAST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.424_SHGC_SOUTH_0.249 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.424_SHGC_WEST_0.249 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.409 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 195.79 | 2.409 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.409 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.04 | 0.0000 | Y | 6.75 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 4.25 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 6.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 4.24 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.98 | 0.0000 | Y | 6.74 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.87 | 0.0000 | Y | 4.25 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 6.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.76 | 0.0000 | Y | 4.23 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.04 | 0.0000 | Y | 6.75 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.91 | 0.0000 | Y | 4.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.68 | 0.0000 | Y | 6.66 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 4.24 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.48 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.14 | 42.14 | 4.46 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.75 | 62.95 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.75 | 46.20 | 40.89 | |
Exterior Lighting Total | 5686.19 | 50.17 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 168061.17 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 76127.74 | 60906.39 | 15221.35 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 70563.62 | 56505.33 | 14058.29 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 79957.63 | 63982.75 | 15974.88 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 75065.4 | 3.05 | 10.39 | N/A | N/A | 11.78 | |
PACU_VAV_MID COOLING COIL | 69608.4 | 3.05 | 10.41 | N/A | N/A | 11.80 | |
PACU_VAV_TOP COOLING COIL | 78820.0 | 3.04 | 10.38 | N/A | N/A | 11.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9619.60 | 9118.54 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 16384.92 | 15522.10 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 27060.24 | 25646.42 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11655.64 | 11055.05 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7611.86 | 7219.65 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11670.93 | 11069.56 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7597.80 | 7206.32 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7861.21 | 7449.29 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5250.53 | 4975.33 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7899.16 | 7485.25 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5225.72 | 4951.82 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8554.99 | 8106.54 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5678.55 | 5380.83 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8579.39 | 8129.66 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5655.10 | 5358.60 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 7029.49 | 6250.94 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 8407.96 | 7337.60 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 6318.08 | 5671.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.28 | 9366.02 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.93 | 8598.12 | 2189.01 | 1.00 | 1.15 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.52 | 9899.13 | 2189.01 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001470 | 438.40 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 75065.40 | 3.05 | 10.39 | 11.78 | 4.8567 | 3.37 | 11.50 | 3.8553 | 3.54 | 12.09 | 2.5879 | 3.75 | 12.80 | 1.0504 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 69608.37 | 3.05 | 10.41 | 11.80 | 4.4585 | 3.38 | 11.52 | 3.5426 | 3.55 | 12.12 | 2.3788 | 3.76 | 12.83 | 0.9600 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 78819.98 | 3.04 | 10.38 | 11.76 | 5.1332 | 3.37 | 11.48 | 4.0730 | 3.54 | 12.08 | 2.7338 | 3.74 | 12.78 | 1.1116 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34539.41 | 34539.41 | 35.12 | 2.535 | 2.535 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_MID | 27455.51 | 27455.51 | 27.92 | 2.013 | 2.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 24.71 | 0.00822 | 0.425 | 0.00 |
CORE_TOP | 28087.95 | 28087.95 | 28.56 | 2.079 | 2.079 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00893 | 31.30 | 0.00823 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8115.40 | 8115.40 | 39.14 | 0.601 | 0.601 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00880 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8839.11 | 8839.11 | 67.34 | 0.654 | 0.654 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00867 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 11070.38 | 11070.38 | 53.39 | 0.820 | 0.820 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00872 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9897.67 | 9897.67 | 75.41 | 0.733 | 0.733 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00866 | 30.41 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6399.37 | 6399.37 | 30.86 | 0.474 | 0.474 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00889 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7477.92 | 7477.92 | 56.97 | 0.554 | 0.554 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00871 | 26.66 | 0.00823 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9010.49 | 9010.49 | 43.46 | 0.667 | 0.667 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00877 | 31.00 | 0.00823 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7994.99 | 7994.99 | 60.91 | 0.592 | 0.592 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00870 | 30.05 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7088.67 | 7088.67 | 34.19 | 0.525 | 0.525 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00884 | 31.30 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8714.54 | 8714.54 | 66.39 | 0.645 | 0.645 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00868 | 26.12 | 0.00823 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9988.71 | 9988.71 | 48.18 | 0.739 | 0.739 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00875 | 30.93 | 0.00823 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9094.63 | 9094.63 | 69.29 | 0.673 | 0.673 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00867 | 30.41 | 0.00823 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3332.45 | 3332.45 | 3.39 | 0.144 | 0.425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_MID | 10099.53 | 10099.53 | 10.27 | 0.434 | 0.434 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
CORE_TOP | 18962.47 | 18962.47 | 19.28 | 0.819 | 0.819 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8449.32 | 8449.32 | 40.75 | 0.337 | 0.337 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00764 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 5516.48 | 5516.48 | 42.03 | 0.220 | 0.220 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00766 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 8460.30 | 8460.30 | 40.80 | 0.338 | 0.338 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00764 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 5506.39 | 5506.39 | 41.95 | 0.220 | 0.220 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 21.00 | 20.70 | 0.00765 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5505.32 | 5505.32 | 26.55 | 0.239 | 0.239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3676.70 | 3676.70 | 28.01 | 0.159 | 0.159 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 5531.85 | 5531.85 | 26.68 | 0.240 | 0.240 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3659.35 | 3659.35 | 27.88 | 0.159 | 0.159 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5990.79 | 5990.79 | 28.89 | 0.260 | 0.260 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3976.25 | 3976.25 | 30.29 | 0.172 | 0.172 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 3.80 | 0.00506 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6007.85 | 6007.85 | 28.98 | 0.260 | 0.260 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3959.85 | 3959.85 | 30.17 | 0.172 | 0.172 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 3.80 | 0.00506 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.28 | 4.28 | 1.22 | 1.22 | 4.2787 | 1.2208 | 4.2787 | 0.2853 | 0.3000 |
PACU_VAV_MID | 3.93 | 3.93 | 1.30 | 1.30 | 3.9279 | 1.2976 | 3.9279 | 0.3303 | 0.3000 |
PACU_VAV_TOP | 4.52 | 4.52 | 2.00 | 2.00 | 4.5222 | 1.9960 | 4.5222 | 0.4414 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 9619.604 | 9619.604 | 0.636249 | 0.00008416 | 204.615 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9619.60 | 9619.60 | 0.636249 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00799959 | 50.7532 | 3332.45 | 0.00 | 9653.49 | 9653.49 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 16384.918 | 16384.918 | 0.636069 | 0.00014334 | 393.591 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16384.92 | 16384.92 | 0.636069 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 10099.53 | 0.00 | 16438.04 | 16438.04 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 27060.243 | 27060.243 | 0.819480 | 0.00023673 | 714.828 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27060.24 | 27060.24 | 0.819480 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 18962.47 | 0.00 | 27157.48 | 27157.48 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 11655.637 | 11655.637 | 0.337212 | 0.00010197 | 312.914 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11655.64 | 11655.64 | 0.337212 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00763815 | 49.4053 | 8449.32 | 0.00 | 11707.01 | 11707.01 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7611.856 | 7611.856 | 0.220373 | 0.00006659 | 204.305 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7611.86 | 7611.86 | 0.220373 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00765565 | 49.5178 | 5516.48 | 0.00 | 7645.41 | 7645.41 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 11670.933 | 11670.933 | 0.337665 | 0.00010210 | 313.322 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 11670.93 | 11670.93 | 0.337665 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00763985 | 49.4162 | 8460.30 | 0.00 | 11722.38 | 11722.38 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7597.803 | 7597.803 | 0.219956 | 0.00006647 | 203.931 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 7597.80 | 7597.80 | 0.219956 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 20.70 | 0.00765300 | 49.5008 | 5506.39 | 0.00 | 7631.30 | 7631.30 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7861.211 | 7861.211 | 0.238510 | 0.00006877 | 207.485 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7861.21 | 7861.21 | 0.238510 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781043 | 49.5697 | 5505.32 | 0.00 | 7888.18 | 7888.18 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5250.533 | 5250.533 | 0.159333 | 0.00004593 | 138.568 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5250.53 | 5250.53 | 0.159333 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781773 | 49.6155 | 3676.70 | 0.00 | 5268.46 | 5268.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7899.162 | 7899.162 | 0.239666 | 0.00006911 | 208.485 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7899.16 | 7899.16 | 0.239666 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781186 | 49.5786 | 5531.85 | 0.00 | 7926.25 | 7926.25 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5225.718 | 5225.718 | 0.158577 | 0.00004572 | 137.914 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5225.72 | 5225.72 | 0.158577 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00781633 | 49.6067 | 3659.35 | 0.00 | 5243.57 | 5243.57 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 8554.988 | 8554.988 | 0.259625 | 0.00007484 | 225.770 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8554.99 | 8554.99 | 0.259625 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776775 | 49.3027 | 5990.79 | 0.00 | 8584.15 | 8584.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5678.554 | 5678.554 | 0.172356 | 0.00004968 | 149.850 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5678.55 | 5678.55 | 0.172356 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777569 | 49.3524 | 3976.25 | 0.00 | 5697.84 | 5697.84 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 8579.393 | 8579.393 | 0.260368 | 0.00007506 | 226.413 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8579.39 | 8579.39 | 0.260368 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776880 | 49.3092 | 6007.85 | 0.00 | 8608.63 | 8608.63 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5655.097 | 5655.097 | 0.171642 | 0.00004947 | 149.232 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5655.10 | 5655.10 | 0.171642 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00777419 | 49.3431 | 3959.85 | 0.00 | 5674.31 | 5674.31 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 76127.737 | 60906.391 | 4.278654 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 76053.01 | 73367.78 | 4.278654 | 25.63 | 16.94 | 0.00870982 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 22.3458 | 24.00 | 0.00884689 | 46.7158 | 57794.66 | 0.00 | 78497.92 | 61169.44 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 7029.487 | 7029.487 | 1.283596 | 0.00006150 | 124.623 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7029.49 | 7029.49 | 1.283596 | 8.19 | 6.94 | 0.00579514 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 74.4860 | 21.00 | 0.00791743 | 50.2390 | 15094.28 | 0.00 | 7567.74 | 7567.74 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 70563.620 | 56505.331 | 3.927857 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 70568.03 | 67989.61 | 3.927857 | 25.78 | 17.00 | 0.00871961 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 24.3415 | 24.00 | 0.00887604 | 46.8675 | 53047.50 | 0.00 | 72760.56 | 56738.52 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 8407.958 | 8407.958 | 1.178357 | 0.00007356 | 147.557 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8407.96 | 8407.96 | 1.178357 | 6.79 | 5.95 | 0.00554057 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 81.1384 | 19.60 | 0.00746194 | 51.6686 | 18145.44 | 0.00 | 8883.09 | 8883.09 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 79957.634 | 63982.750 | 4.522193 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 79826.11 | 77107.01 | 4.522193 | 25.54 | 16.90 | 0.00870095 | 10.99 | 10.99 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 21.1424 | 24.00 | 0.00882634 | 46.6087 | 61058.23 | 0.00 | 82447.05 | 64263.40 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 6318.077 | 6318.077 | 1.356658 | 0.00005527 | 112.588 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6318.08 | 6318.08 | 1.356658 | 8.88 | 7.39 | 0.00589894 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 70.4747 | 19.06 | 0.00788958 | 56.4526 | 18057.32 | 0.00 | 6866.25 | 6866.25 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 9619.604 | 9619.604 | 0.636249 | 0.00008416 | 204.615 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 5.6109 | 5.723870 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9619.60 | 9619.60 | 1.0000 | 0.75190500 | 0.636249 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.08414790 | 60.00 | 32.22 | 27.78 | 0.000 | 9619.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.80 | 0.00799959 | 21.00 | 0.00799959 | 50.7532 | 3332.45 | 0.00 | 9653.49 | 9653.49 | 0.75190500 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.39 | 16.45 | 0.00800000 | 45898.5 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 16384.918 | 16384.918 | 0.636069 | 0.00014334 | 393.591 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 9.5570 | 9.749378 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16384.92 | 16384.92 | 1.0000 | 0.75169322 | 0.636069 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.14332779 | 60.00 | 32.22 | 27.78 | 0.000 | 16384.92 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 10099.53 | 0.00 | 16438.04 | 16438.04 | 0.75169322 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.25 | 19.42 | 0.00800000 | 54927.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 27060.243 | 27060.243 | 0.819480 | 0.00023673 | 714.828 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 15.7838 | 16.101425 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 27060.24 | 27060.24 | 1.0000 | 0.96844354 | 0.819480 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.23671066 | 60.00 | 32.22 | 27.78 | 0.000 | 27060.24 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 18962.47 | 0.00 | 27157.48 | 27157.48 | 0.96844354 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61102.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11655.637 | 11655.637 | 0.337212 | 0.00010197 | 312.914 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 6.7985 | 6.935354 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11655.64 | 11655.64 | 1.0000 | 0.39851001 | 0.337212 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10195819 | 60.00 | 32.22 | 27.78 | 0.000 | 11655.64 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00763815 | 20.70 | 0.00763815 | 49.4053 | 8449.32 | 0.00 | 11707.01 | 11707.01 | 0.39851001 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.61 | 21.65 | 0.00800000 | 62436.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7611.856 | 7611.856 | 0.220373 | 0.00006659 | 204.305 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.4399 | 4.529217 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7611.86 | 7611.86 | 1.0000 | 0.26043197 | 0.220373 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06658504 | 60.00 | 32.22 | 27.78 | 0.000 | 7611.86 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00765565 | 20.70 | 0.00765565 | 49.5178 | 5516.48 | 0.00 | 7645.41 | 7645.41 | 0.26043197 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.59 | 21.65 | 0.00800000 | 62416.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11670.933 | 11670.933 | 0.337665 | 0.00010210 | 313.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 6.8075 | 6.944455 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 11670.93 | 11670.93 | 1.0000 | 0.39904530 | 0.337665 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10209200 | 60.00 | 32.22 | 27.78 | 0.000 | 11670.93 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00763985 | 20.70 | 0.00763985 | 49.4162 | 8460.30 | 0.00 | 11722.38 | 11722.38 | 0.39904530 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.61 | 21.65 | 0.00800000 | 62435.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7597.803 | 7597.803 | 0.219956 | 0.00006647 | 203.931 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.4317 | 4.520856 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | Sensible | 7597.80 | 7597.80 | 1.0000 | 0.25993953 | 0.219956 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06646212 | 60.00 | 32.22 | 27.78 | 0.000 | 7597.80 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 19.48 | 0.00765300 | 20.70 | 0.00765300 | 49.5008 | 5506.39 | 0.00 | 7631.30 | 7631.30 | 0.25993953 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 41.59 | 21.65 | 0.00800000 | 62417.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7861.211 | 7861.211 | 0.238510 | 0.00006877 | 207.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.5853 | 4.677589 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7861.21 | 7861.21 | 1.0000 | 0.28186596 | 0.238510 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06876628 | 60.00 | 32.22 | 27.78 | 0.000 | 7861.21 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781043 | 21.00 | 0.00781043 | 49.5697 | 5505.32 | 0.00 | 7888.18 | 7888.18 | 0.28186596 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61045.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5250.533 | 5250.533 | 0.159333 | 0.00004593 | 138.568 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 3.0625 | 3.124180 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5250.53 | 5250.53 | 1.0000 | 0.18829629 | 0.159333 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04592927 | 60.00 | 32.22 | 27.78 | 0.000 | 5250.53 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781773 | 21.00 | 0.00781773 | 49.6155 | 3676.70 | 0.00 | 5268.46 | 5268.46 | 0.18829629 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61039.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7899.162 | 7899.162 | 0.239666 | 0.00006911 | 208.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.6074 | 4.700171 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7899.16 | 7899.16 | 1.0000 | 0.28323197 | 0.239666 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06909827 | 60.00 | 32.22 | 27.78 | 0.000 | 7899.16 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781186 | 21.00 | 0.00781186 | 49.5786 | 5531.85 | 0.00 | 7926.25 | 7926.25 | 0.28323197 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5225.718 | 5225.718 | 0.158577 | 0.00004572 | 137.914 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 3.0481 | 3.109414 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5225.72 | 5225.72 | 1.0000 | 0.18740331 | 0.158577 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04571220 | 60.00 | 32.22 | 27.78 | 0.000 | 5225.72 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00781633 | 21.00 | 0.00781633 | 49.6067 | 3659.35 | 0.00 | 5243.57 | 5243.57 | 0.18740331 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61039.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8554.988 | 8554.988 | 0.259625 | 0.00007484 | 225.770 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.9900 | 5.090401 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8554.99 | 8554.99 | 1.0000 | 0.30681946 | 0.259625 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07483513 | 60.00 | 32.22 | 27.78 | 0.000 | 8554.99 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00776775 | 21.00 | 0.00776775 | 49.3027 | 5990.79 | 0.00 | 8584.15 | 8584.15 | 0.30681946 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61037.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5678.554 | 5678.554 | 0.172356 | 0.00004968 | 149.850 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 3.3122 | 3.378861 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5678.55 | 5678.55 | 1.0000 | 0.20368625 | 0.172356 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04967340 | 60.00 | 32.22 | 27.78 | 0.000 | 5678.55 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00777569 | 21.00 | 0.00777569 | 49.3524 | 3976.25 | 0.00 | 5697.84 | 5697.84 | 0.20368625 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8579.393 | 8579.393 | 0.260368 | 0.00007506 | 226.413 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 5.0042 | 5.104923 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8579.39 | 8579.39 | 1.0000 | 0.30769758 | 0.260368 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.07504862 | 60.00 | 32.22 | 27.78 | 0.000 | 8579.39 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00776880 | 21.00 | 0.00776880 | 49.3092 | 6007.85 | 0.00 | 8608.63 | 8608.63 | 0.30769758 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61037.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5655.097 | 5655.097 | 0.171642 | 0.00004947 | 149.232 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 3.2985 | 3.364904 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5655.10 | 5655.10 | 1.0000 | 0.20284250 | 0.171642 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04946821 | 60.00 | 32.22 | 27.78 | 0.000 | 5655.10 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00777419 | 21.00 | 0.00777419 | 49.3431 | 3959.85 | 0.00 | 5674.31 | 5674.31 | 0.20284250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.8 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 76127.737 | 60906.391 | 4.278654 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0311 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.278654 | 5.05642180 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 76053.01 | 73367.78 | 0.9990 | 5.05642180 | 4.278654 | 25.63 | 16.94 | 0.00870982 | 47952.1 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9366.020 | 66686.99 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 22.3458 | 24.00 | 0.00884689 | 24.00 | 0.00884689 | 46.7158 | 57794.66 | 0.00 | 78497.92 | 61169.44 | 4.85673137 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.36 | 13.97 | 0.00978576 | 39159.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 7029.487 | 7029.487 | 1.283596 | 0.00006150 | 124.623 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.278654 | 5.05642180 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.1002 | 4.182695 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7029.49 | 7029.49 | 1.0000 | 1.51692654 | 1.283596 | 8.19 | 6.94 | 0.00579514 | 22809.5 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.06149074 | 60.00 | 32.22 | 27.78 | 0.000 | 7029.49 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 74.4860 | 21.00 | 0.00794592 | 21.00 | 0.00791743 | 50.2390 | 15094.28 | 0.00 | 7567.74 | 7567.74 | 1.51692654 | 2.80 | 2.80 | 0.00579514 | 17337.0 | 7.71 | 6.85 | 0.00579514 | 22325.9 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 70563.620 | 56505.331 | 3.927857 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0493 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.927857 | 4.64185775 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 70568.03 | 67989.61 | 1.0001 | 4.64185775 | 3.927857 | 25.78 | 17.00 | 0.00871961 | 48126.1 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 8598.122 | 61969.91 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 24.3415 | 24.00 | 0.00887604 | 24.00 | 0.00887604 | 46.8675 | 53047.50 | 0.00 | 72760.56 | 56738.52 | 4.45853946 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.23 | 13.91 | 0.00977571 | 39003.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 8407.958 | 8407.958 | 1.178357 | 0.00007356 | 147.557 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.927857 | 4.64185775 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 4.9042 | 5.002915 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8407.96 | 8407.96 | 1.0000 | 1.39255732 | 1.178357 | 6.79 | 5.95 | 0.00554057 | 20750.9 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.07354898 | 60.00 | 32.22 | 27.78 | 0.000 | 8407.96 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 81.1384 | 19.66 | 0.00761461 | 19.60 | 0.00746194 | 51.6686 | 18145.44 | 0.00 | 8883.09 | 8883.09 | 1.39255732 | 2.80 | 2.80 | 0.00554057 | 16699.0 | 9.08 | 7.22 | 0.00554057 | 23078.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 79957.634 | 63982.750 | 4.522193 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0146 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.522193 | 5.34423167 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 79826.11 | 77107.01 | 0.9984 | 5.34423167 | 4.522193 | 25.54 | 16.90 | 0.00870095 | 47840.5 | 10.99 | 10.99 | 0.00850000 | 32470.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9899.131 | 69926.98 | 31.30 | 0.00823349 | 18.45 | 0.95610000 | 21.1424 | 24.00 | 0.00882634 | 24.00 | 0.00882634 | 46.6087 | 61058.23 | 0.00 | 82447.05 | 64263.40 | 5.13317492 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.43 | 14.00 | 0.00979577 | 39260.8 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 6318.077 | 6318.077 | 1.356658 | 0.00005527 | 112.588 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.522193 | 5.34423167 | 4197.9300 | 999.8980 | 1.47012248 | 54.44 | 82.22 | 27.78 | 171443.47 | 3.6852 | 3.759391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6318.08 | 6318.08 | 1.0000 | 1.60326950 | 1.356658 | 8.88 | 7.39 | 0.00589894 | 23771.5 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.05526766 | 60.00 | 32.22 | 27.78 | 0.000 | 6318.08 | 3.80 | 0.00505843 | 3.80 | 0.95610000 | 70.4747 | 21.00 | 0.00790517 | 19.06 | 0.00788958 | 56.4526 | 18057.32 | 0.00 | 6866.25 | 6866.25 | 1.60326950 | 2.80 | 2.80 | 0.00589894 | 17597.2 | 7.02 | 6.63 | 0.00589894 | 21879.8 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.28 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 3.93 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.52 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3987.50 | 284.67 | 12.00 |
CORE_MID | 2495.83 | 1571.17 | 0.83 |
CORE_TOP | 1966.33 | 2518.83 | 1.50 |
PERIMETER_TOP_ZN_3 | 1762.17 | 3369.00 | 159.17 |
PERIMETER_TOP_ZN_2 | 2371.67 | 2600.00 | 142.50 |
PERIMETER_TOP_ZN_1 | 2694.33 | 2337.83 | 149.00 |
PERIMETER_TOP_ZN_4 | 2532.67 | 2794.67 | 260.00 |
PERIMETER_BOT_ZN_3 | 1375.50 | 3423.50 | 5.33 |
PERIMETER_BOT_ZN_2 | 2420.50 | 2232.83 | 35.83 |
PERIMETER_BOT_ZN_1 | 2490.17 | 2388.00 | 107.33 |
PERIMETER_BOT_ZN_4 | 2609.67 | 2273.50 | 62.00 |
PERIMETER_MID_ZN_3 | 1869.33 | 2858.83 | 11.83 |
PERIMETER_MID_ZN_2 | 2126.50 | 1939.33 | 74.17 |
PERIMETER_MID_ZN_1 | 3005.50 | 1765.00 | 80.50 |
PERIMETER_MID_ZN_4 | 2728.50 | 2246.17 | 117.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4779.17 | 4089.33 | 507.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 15.17 | 0.00 | 15.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 27.67 | 0.00 | 27.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 33.17 | 0.00 | 27.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 8.33 | 0.00 | 8.33 |
PERIMETER_BOT_ZN_1 | 37.50 | 38.67 | 37.50 | 38.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 18.33 | 0.00 | 15.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 16.67 | 0.00 | 16.67 |
PERIMETER_MID_ZN_1 | 0.00 | 35.33 | 0.00 | 35.33 |
PERIMETER_MID_ZN_4 | 0.00 | 30.50 | 0.00 | 25.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 37.50 | 161.33 | 37.50 | 150.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 1.419 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 0.907 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.872 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.898 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 1.340 | 0.027 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 1.502 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 1.436 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.772 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 1.199 | 0.015 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 1.161 | 0.812 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 1.250 | 0.015 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.900 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 1.228 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 1.508 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 1.426 | 0.023 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.18 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.96 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.60 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.68 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.96 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.18 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.96 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.60 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.68 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.96 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 112.00 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 22278181.56 | 0.00 | 22278181.56 | 0.00 | 22278181.56 | 13393058.27 | 3973.40 | 28.43 | 4758.17 | 31.50 |
CORE_MID | 14282097.18 | 0.00 | 14282097.18 | 0.00 | 14282097.18 | 13393058.27 | 4103.42 | 171.43 | 4485.15 | 37.17 |
CORE_TOP | 13754476.54 | 0.00 | 13754476.54 | 0.00 | 13754476.54 | 13393058.27 | 4088.81 | 251.57 | 4419.62 | 41.58 |
PERIMETER_TOP_ZN_3 | 2984877.34 | 0.00 | 2984877.34 | 149098.74 | 3133976.08 | 2823374.22 | 4002.90 | 180.71 | 4576.39 | 41.58 |
PERIMETER_TOP_ZN_2 | 2812196.72 | 0.00 | 2812196.72 | 99398.56 | 2911595.28 | 1787429.43 | 3944.76 | 207.36 | 4607.89 | 41.58 |
PERIMETER_TOP_ZN_1 | 4982520.99 | 0.00 | 4982520.99 | 149098.74 | 5131619.73 | 2823374.22 | 3932.76 | 205.34 | 4621.90 | 41.58 |
PERIMETER_TOP_ZN_4 | 3017319.45 | 0.00 | 3017319.45 | 99398.56 | 3116718.01 | 1787312.18 | 3966.50 | 233.12 | 4560.38 | 41.58 |
PERIMETER_BOT_ZN_3 | 2565713.12 | 0.00 | 2565713.12 | 79275.26 | 2644988.38 | 2823374.22 | 4352.33 | 29.26 | 4378.41 | 31.50 |
PERIMETER_BOT_ZN_2 | 2513985.69 | 0.00 | 2513985.69 | 52849.85 | 2566835.54 | 1787429.43 | 4165.29 | 34.19 | 4560.52 | 31.50 |
PERIMETER_BOT_ZN_1 | 3854233.00 | 0.00 | 3854233.00 | 2726356.63 | 6580589.64 | 2823374.22 | 4073.62 | 26.41 | 4659.96 | 31.50 |
PERIMETER_BOT_ZN_4 | 2620197.19 | 0.00 | 2620197.19 | 52849.85 | 2673047.04 | 1787312.18 | 4181.07 | 34.57 | 4544.36 | 31.50 |
PERIMETER_MID_ZN_3 | 2989146.06 | 0.00 | 2989146.06 | 124113.44 | 3113259.51 | 2823374.22 | 3998.90 | 146.22 | 4614.88 | 37.17 |
PERIMETER_MID_ZN_2 | 2650822.39 | 0.00 | 2650822.39 | 82741.80 | 2733564.19 | 1601953.02 | 3904.24 | 102.49 | 4753.27 | 946.17 |
PERIMETER_MID_ZN_1 | 4999137.99 | 0.00 | 4999137.99 | 124113.44 | 5123251.44 | 2823374.22 | 3900.01 | 95.40 | 4764.59 | 37.17 |
PERIMETER_MID_ZN_4 | 2992275.49 | 0.00 | 2992275.49 | 82741.80 | 3075017.29 | 1787312.18 | 3945.36 | 180.22 | 4634.42 | 37.17 |
Total Facility | 89297180.71 | 0.00 | 89297180.71 | 3822036.67 | 93119217.38 | 67658168.57 | 4519.15 | 334.38 | 4973.66 | 959.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 1.0379 | 0.0000 | 1.0379 | 0.0000 | 1.0379 | 0.4247 | 1187.90 | 28.43 | 4726.67 |
CORE_MID | 0.6636 | 0.0000 | 0.6636 | 0.0000 | 0.6636 | 0.4247 | 1323.59 | 171.43 | 4447.98 |
CORE_TOP | 0.6384 | 0.0000 | 0.6384 | 0.0000 | 0.6384 | 0.4247 | 1313.39 | 251.57 | 4378.04 |
PERIMETER_TOP_ZN_3 | 0.1386 | 0.0000 | 0.1386 | 0.0040 | 0.1426 | 0.0895 | 1227.48 | 180.71 | 4534.80 |
PERIMETER_TOP_ZN_2 | 0.1308 | 0.0000 | 0.1308 | 0.0027 | 0.1335 | 0.0567 | 1169.34 | 207.36 | 4566.31 |
PERIMETER_TOP_ZN_1 | 0.2319 | 0.0000 | 0.2319 | 0.0040 | 0.2360 | 0.0895 | 1157.35 | 205.34 | 4580.31 |
PERIMETER_TOP_ZN_4 | 0.1401 | 0.0000 | 0.1401 | 0.0027 | 0.1428 | 0.0567 | 1191.08 | 233.12 | 4518.80 |
PERIMETER_BOT_ZN_3 | 0.1192 | 0.0000 | 0.1192 | 0.0021 | 0.1213 | 0.0895 | 1566.83 | 29.26 | 4346.91 |
PERIMETER_BOT_ZN_2 | 0.1171 | 0.0000 | 0.1171 | 0.0014 | 0.1185 | 0.0567 | 1379.79 | 34.19 | 4529.02 |
PERIMETER_BOT_ZN_1 | 0.1794 | 0.0000 | 0.1794 | 0.1259 | 0.3053 | 0.0895 | 1288.12 | 26.41 | 4628.46 |
PERIMETER_BOT_ZN_4 | 0.1219 | 0.0000 | 0.1219 | 0.0014 | 0.1233 | 0.0567 | 1395.57 | 34.57 | 4512.86 |
PERIMETER_MID_ZN_3 | 0.1389 | 0.0000 | 0.1389 | 0.0033 | 0.1422 | 0.0895 | 1219.07 | 146.22 | 4577.71 |
PERIMETER_MID_ZN_2 | 0.1199 | 0.0000 | 0.1199 | 0.0023 | 0.1222 | 0.0567 | 1124.40 | 102.49 | 3807.11 |
PERIMETER_MID_ZN_1 | 0.2328 | 0.0000 | 0.2328 | 0.0033 | 0.2362 | 0.0895 | 1120.18 | 95.40 | 4727.43 |
PERIMETER_MID_ZN_4 | 0.1391 | 0.0000 | 0.1391 | 0.0022 | 0.1413 | 0.0567 | 1165.53 | 180.22 | 4597.26 |
Total Facility | 4.1497 | 0.0000 | 4.1497 | 0.1554 | 4.3051 | 2.1513 | 1722.81 | 334.38 | 4922.91 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 47250232.33 | 0.00 | 47250232.33 | 22614548.33 | 3869.61 | 2.33 | 4888.06 | 31.50 |
PACU_VAV_MID | 38983987.54 | 0.00 | 38983987.54 | 22429071.92 | 3826.62 | 3.28 | 4930.11 | 37.17 |
PACU_VAV_TOP | 38478295.04 | 0.00 | 38478295.04 | 22614548.33 | 3868.46 | 2.87 | 4888.66 | 41.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 2.2004 | 0.0000 | 2.2004 | 0.7171 | 1084.11 | 2.33 | 4856.56 |
PACU_VAV_MID | 1.8124 | 0.0000 | 1.8124 | 0.7084 | 1046.78 | 3.28 | 4892.94 |
PACU_VAV_TOP | 1.7875 | 0.0000 | 1.7875 | 0.7171 | 1093.05 | 2.87 | 4847.08 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 154.41 | 4542.64 | 0.00 | 0.00 | 0.00 | 200.87 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 53.49 | 4542.47 | 0.00 | 0.00 | 0.00 | 352.26 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 51.00 | 4500.14 | 0.00 | 0.00 | 0.00 | 392.38 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3286 | 2.8027 | 0.0000 | 0.0000 | 0.0000 | 1.1450 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.3232 | 2.2923 | 0.0000 | 0.0000 | 0.0000 | 1.0631 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.3095 | 2.2757 | 0.0000 | 0.0000 | 0.0000 | 1.0494 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1005 |
Defaulted Fields | 578 |
Fields with Defaults | 2423 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
Electricity:Building | 952.17 | 13383.13 | 21-MAY-17:20 | 66674.30 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 952.17 | 13383.13 | 21-MAY-17:20 | 66674.30 | 02-JAN-16:50 |
InteriorLights:Electricity | 232.48 | 905.38 | 21-MAY-17:20 | 25003.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.48 | 905.38 | 21-MAY-17:20 | 25003.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 232.48 | 905.38 | 21-MAY-17:20 | 25003.79 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.48 | 905.38 | 21-MAY-17:20 | 25003.79 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.09 | 413.68 | 16-APR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.75 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.75 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.66 | 261.88 | 14-MAY-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.99 | 413.67 | 16-APR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:50 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:50 | 658.71 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.07 | 413.68 | 16-APR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.74 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.74 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.65 | 261.88 | 30-APR-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.99 | 413.67 | 16-APR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.63 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.23 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.23 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.09 | 413.68 | 16-APR-17:10 | 2475.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.75 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.75 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.66 | 261.88 | 14-MAY-17:10 | 1567.33 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.25 | 17.46 | 01-JAN-07:20 | 658.76 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.99 | 413.67 | 16-APR-17:10 | 2475.79 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.66 | 27.57 | 01-JAN-07:20 | 1040.56 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:50 | 658.71 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:50 | 658.71 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 268.35 | 367.92 | 01-JAN-00:10 | 72790.59 | 16-OCT-11:00 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 05-JAN-17:10 |
ElectricityPurchased:Facility | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
ElectricityPurchased:Plant | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
Cogeneration:ElectricityPurchased | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
General:Cogeneration:ElectricityPurchased | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
ElectricityNet:Plant | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
Cogeneration:ElectricityNet | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
General:Cogeneration:ElectricityNet | 1319.72 | 13755.55 | 04-JUL-17:40 | 138612.09 | 16-OCT-11:00 |
Fans:Electricity | 87.33 | 0.00 | 01-JAN-00:10 | 19814.48 | 16-OCT-16:00 |
General:Fans:Electricity | 87.33 | 0.00 | 01-JAN-00:10 | 19814.48 | 16-OCT-16:00 |
ExteriorLights:Electricity | 50.17 | 0.00 | 01-JAN-07:00 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.17 | 0.00 | 01-JAN-07:00 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 154.13 | 0.00 | 01-JAN-00:10 | 58112.61 | 16-OCT-11:00 |
General:Cooling:Electricity | 154.13 | 0.00 | 01-JAN-00:10 | 58112.61 | 16-OCT-11:00 |
Electricity:Plant | 49.04 | 0.00 | 01-JAN-00:10 | 5770.57 | 03-FEB-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 48.82 | 0.00 | 01-JAN-00:10 | 5763.72 | 03-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 48.82 | 0.00 | 01-JAN-00:10 | 5763.72 | 03-FEB-13:00 |
Pumps:Electricity | 0.21 | 0.00 | 01-JAN-00:10 | 329.73 | 03-JAN-07:10 |
General:Pumps:Electricity | 0.21 | 0.00 | 01-JAN-00:10 | 329.73 | 03-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 6.53 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-17:00 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 11.39 | 0.00 | 01-JAN-00:10 | 83717.04 | 03-JAN-07:10 |
NaturalGas:Plant | 11.39 | 0.00 | 01-JAN-00:10 | 83717.04 | 03-JAN-07:10 |
Heating:NaturalGas | 11.39 | 0.00 | 01-JAN-00:10 | 83717.04 | 03-JAN-07:10 |
Boiler:Heating:NaturalGas | 11.39 | 0.00 | 01-JAN-00:10 | 83717.04 | 03-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 10-FEB-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1808.07 | 0.00 | 01-JAN-00:10 | 357136.51 | 31-JUL-16:00 |
EnergyTransfer:Building | 1059.53 | 0.00 | 01-JAN-00:10 | 155245.65 | 16-OCT-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 250.63 | 0.00 | 01-JAN-00:10 | 24324.38 | 02-OCT-07:40 |
Heating:EnergyTransfer | 9.54 | 0.00 | 01-JAN-00:10 | 33730.89 | 03-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 9.54 | 0.00 | 01-JAN-00:10 | 33730.89 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1049.99 | 0.00 | 01-JAN-00:10 | 155245.65 | 16-OCT-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 250.63 | 0.00 | 01-JAN-00:10 | 24324.38 | 02-OCT-07:40 |
General:Cooling:EnergyTransfer | 1049.99 | 0.00 | 01-JAN-00:10 | 155245.65 | 16-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 250.63 | 0.00 | 01-JAN-00:10 | 24324.38 | 02-OCT-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 36.99 | 0.00 | 01-JAN-00:10 | 9095.53 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.30 | 0.00 | 01-JAN-00:10 | 4626.48 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.30 | 0.00 | 01-JAN-00:10 | 4626.48 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.70 | 0.00 | 01-JAN-00:10 | 9095.53 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.70 | 0.00 | 01-JAN-00:10 | 9095.53 | 16-OCT-13:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.84 | 0.00 | 01-JAN-00:10 | 4479.23 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.44 | 0.00 | 01-JAN-00:10 | 2236.38 | 02-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.44 | 0.00 | 01-JAN-00:10 | 2236.38 | 02-JAN-11:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.40 | 0.00 | 01-JAN-00:10 | 4479.23 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.40 | 0.00 | 01-JAN-00:10 | 4479.23 | 16-OCT-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.11 | 0.00 | 01-JAN-00:10 | 4543.30 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.50 | 0.00 | 01-JAN-00:10 | 1635.39 | 08-JAN-11:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.50 | 0.00 | 01-JAN-00:10 | 1635.39 | 08-JAN-11:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.61 | 0.00 | 01-JAN-00:10 | 4543.30 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.61 | 0.00 | 01-JAN-00:10 | 4543.30 | 16-OCT-16:00 |
EnergyTransfer:Zone:CORE_MID | 157.61 | 0.00 | 01-JAN-00:10 | 17300.29 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 157.61 | 0.00 | 01-JAN-00:10 | 17300.29 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 157.61 | 0.00 | 01-JAN-00:10 | 17300.29 | 16-OCT-14:00 |
EnergyTransfer:Zone:CORE_TOP | 147.21 | 0.00 | 01-JAN-00:10 | 18980.04 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.01 | 0.00 | 01-JAN-00:10 | 6402.26 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.01 | 0.00 | 01-JAN-00:10 | 6402.26 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 147.20 | 0.00 | 01-JAN-00:10 | 18980.04 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 147.20 | 0.00 | 01-JAN-00:10 | 18980.04 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.99 | 0.00 | 01-JAN-00:10 | 5805.38 | 16-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.25 | 0.00 | 01-JAN-00:10 | 3928.14 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.25 | 0.00 | 01-JAN-00:10 | 3928.14 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.73 | 0.00 | 01-JAN-00:10 | 5805.38 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.73 | 0.00 | 01-JAN-00:10 | 5805.38 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.31 | 0.00 | 01-JAN-00:10 | 6527.82 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 2396.47 | 03-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 2396.47 | 03-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.25 | 0.00 | 01-JAN-00:10 | 6527.82 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.25 | 0.00 | 01-JAN-00:10 | 6527.82 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.70 | 0.00 | 01-JAN-00:10 | 11734.37 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.10 | 0.00 | 01-JAN-00:10 | 3057.94 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.10 | 0.00 | 01-JAN-00:10 | 3057.94 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.60 | 0.00 | 01-JAN-00:10 | 11734.37 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 54.60 | 0.00 | 01-JAN-00:10 | 11734.37 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.33 | 0.00 | 01-JAN-00:10 | 7731.49 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.14 | 0.00 | 01-JAN-00:10 | 2466.91 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.14 | 0.00 | 01-JAN-00:10 | 2466.91 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.19 | 0.00 | 01-JAN-00:10 | 7731.49 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.19 | 0.00 | 01-JAN-00:10 | 7731.49 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.20 | 0.00 | 01-JAN-00:10 | 4570.14 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1651.17 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1651.17 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.19 | 0.00 | 01-JAN-00:10 | 4570.14 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.19 | 0.00 | 01-JAN-00:10 | 4570.14 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.82 | 0.00 | 01-JAN-00:10 | 5810.41 | 16-OCT-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 512.88 | 30-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 512.88 | 30-MAR-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.82 | 0.00 | 01-JAN-00:10 | 5810.41 | 16-OCT-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.82 | 0.00 | 01-JAN-00:10 | 5810.41 | 16-OCT-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 44.28 | 0.00 | 01-JAN-00:10 | 11678.93 | 16-OCT-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.70 | 0.00 | 01-JAN-00:10 | 4834.10 | 30-MAR-06:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.70 | 0.00 | 01-JAN-00:10 | 4834.10 | 30-MAR-06:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.58 | 0.00 | 01-JAN-00:10 | 11678.93 | 16-OCT-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 42.58 | 0.00 | 01-JAN-00:10 | 11678.93 | 16-OCT-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.99 | 0.00 | 01-JAN-00:10 | 6388.52 | 16-OCT-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 561.58 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 561.58 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.99 | 0.00 | 01-JAN-00:10 | 6388.52 | 16-OCT-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.99 | 0.00 | 01-JAN-00:10 | 6388.52 | 16-OCT-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.22 | 0.00 | 01-JAN-00:10 | 5342.42 | 16-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1918.92 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.01 | 0.00 | 01-JAN-00:10 | 1918.92 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.21 | 0.00 | 01-JAN-00:10 | 5342.42 | 16-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.21 | 0.00 | 01-JAN-00:10 | 5342.42 | 16-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.60 | 0.00 | 01-JAN-00:10 | 6576.65 | 16-OCT-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 788.01 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 788.01 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.59 | 0.00 | 01-JAN-00:10 | 6576.65 | 16-OCT-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.59 | 0.00 | 01-JAN-00:10 | 6576.65 | 16-OCT-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.73 | 0.00 | 01-JAN-00:10 | 10777.88 | 16-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1122.92 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1122.92 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.73 | 0.00 | 01-JAN-00:10 | 10777.88 | 16-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.73 | 0.00 | 01-JAN-00:10 | 10777.88 | 16-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.98 | 0.00 | 01-JAN-00:10 | 7285.60 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1322.33 | 03-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1322.33 | 03-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.97 | 0.00 | 01-JAN-00:10 | 7285.60 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.97 | 0.00 | 01-JAN-00:10 | 7285.60 | 29-SEP-15:30 |
PlantLoopHeatingDemand:Facility | 53.50 | 0.00 | 01-JAN-00:10 | 62567.25 | 03-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
EnergyTransfer:HVAC | 695.12 | 0.00 | 01-JAN-00:10 | 228712.98 | 31-JUL-16:00 |
HeatingCoils:EnergyTransfer | 7.43 | 0.00 | 01-JAN-00:10 | 60760.71 | 03-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 7.43 | 0.00 | 01-JAN-00:10 | 60760.71 | 03-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 7.43 | 0.00 | 01-JAN-00:10 | 60760.71 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 687.69 | 0.00 | 01-JAN-00:10 | 228705.95 | 31-JUL-16:00 |
EnergyTransfer:Plant | 53.42 | 0.00 | 01-JAN-00:10 | 65464.32 | 03-JAN-07:10 |
WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 46.07 | 0.00 | 01-JAN-00:10 | 5453.65 | 02-FEB-12:10 |
Boilers:EnergyTransfer | 7.35 | 0.00 | 01-JAN-00:10 | 63657.77 | 03-JAN-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -250.628 | 0.000 | 0.000 | 32.660 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -88.053 |
CORE_MID | 0.000 | 0.000 | 0.000 | -157.612 | 0.000 | 0.000 | 32.879 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -46.291 |
CORE_TOP | 0.000 | 0.000 | 0.012 | -147.201 | 0.000 | 0.000 | 33.258 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.094 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.253 | -30.732 | 0.000 | 0.000 | 7.159 | 6.754 | 24.333 | 13.511 | 0.000 | 0.013 | 4.289 | 0.000 | -24.264 | 0.000 | -1.315 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.064 | -30.246 | 0.000 | 0.000 | 4.438 | 4.254 | 15.404 | 29.250 | 0.000 | 0.007 | 0.001 | 0.000 | -15.884 | 0.000 | -0.921 | -6.366 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.096 | -54.601 | 0.000 | 0.000 | 7.021 | 6.661 | 24.332 | 57.426 | 0.000 | 0.010 | 0.004 | 0.000 | -24.666 | 0.000 | -1.423 | -14.857 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.141 | -32.189 | 0.000 | 0.000 | 4.502 | 4.236 | 15.403 | 33.277 | 0.000 | 0.008 | 0.000 | 0.000 | -16.560 | 0.000 | -0.930 | -7.888 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.009 | -27.194 | 0.000 | 0.000 | 7.105 | 6.739 | 24.333 | 13.784 | 0.000 | 0.007 | 1.118 | 0.000 | -25.169 | 0.000 | -0.732 | -0.001 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.001 | -27.822 | 0.000 | 0.000 | 4.408 | 4.248 | 15.404 | 29.374 | 0.000 | 0.004 | 0.001 | 0.000 | -16.792 | 0.000 | -0.522 | -8.303 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.704 | -42.576 | 0.000 | 0.000 | 7.073 | 6.655 | 24.332 | 57.995 | 0.000 | 0.337 | 0.001 | 0.000 | -26.036 | 0.000 | -17.671 | -11.815 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.001 | -28.988 | 0.000 | 0.000 | 4.437 | 4.229 | 15.403 | 33.555 | 0.000 | 0.004 | 0.000 | 0.000 | -17.661 | 0.000 | -0.530 | -10.451 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.012 | -32.205 | 0.000 | 0.000 | 7.051 | 6.754 | 24.333 | 13.193 | 0.000 | 0.011 | 7.934 | 0.000 | -25.909 | 0.000 | -1.173 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.002 | -29.594 | 0.000 | 0.000 | 3.249 | 4.254 | 15.404 | 28.929 | 0.000 | 0.006 | 0.000 | 0.000 | -16.845 | 0.000 | -0.819 | -4.586 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.003 | -56.726 | 0.000 | 0.000 | 6.956 | 6.661 | 24.332 | 57.186 | 0.000 | 0.009 | 0.002 | 0.000 | -26.124 | 0.000 | -1.256 | -11.041 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.006 | -32.969 | 0.000 | 0.000 | 4.439 | 4.235 | 15.403 | 33.152 | 0.000 | 0.006 | 0.000 | 0.000 | -17.624 | 0.000 | -0.825 | -5.824 |
TOPFLOOR_PLENUM | 5.297 | -31.698 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.011 | 28.520 | 0.000 | 0.000 | 0.000 | -2.130 | -0.000 |
MIDFLOOR_PLENUM | 1.442 | -14.400 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.014 | 15.019 | 0.000 | 0.000 | 0.000 | -2.075 | -0.000 |
FIRSTFLOOR_PLENUM | 0.498 | -22.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.010 | 23.788 | 0.000 | 0.000 | 0.000 | -1.685 | -0.000 |
Total Facility | 7.237 | -68.709 | 2.303 | -981.284 | 0.000 | 0.000 | 166.636 | 232.476 | 719.689 | 400.633 | 0.000 | 0.457 | 80.678 | 0.000 | -253.533 | 0.000 | -34.007 | -272.569 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -38374.57 | 0.00 | 0.00 | 313.46 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 30102.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -29721.39 | 0.00 | 0.00 | 327.76 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 25819.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-OCT-05:12 | 0.00 | 0.00 | 0.00 | -23220.30 | 0.00 | 0.00 | 341.07 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 19304.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | -5806.19 | 0.00 | 0.00 | 757.17 | 496.34 | 1435.25 | 2520.51 | 0.00 | 47.62 | 549.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:53 | 0.00 | 0.00 | 0.00 | -11206.73 | 0.00 | 0.00 | 16.09 | 17.46 | 302.86 | 4828.98 | 0.00 | 0.00 | 6063.81 | 0.00 | -0.00 | 0.00 | -22.47 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:42 | 0.00 | 0.00 | 0.00 | -14494.53 | 0.00 | 0.00 | 21.56 | 27.57 | 478.41 | 11304.81 | 0.00 | 96.39 | 2565.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 27-AUG-16:02 | 0.00 | 0.00 | 0.00 | -12982.07 | 0.00 | 0.00 | 15.16 | 17.46 | 302.86 | 7200.17 | 0.00 | 0.00 | 5502.34 | 0.00 | -0.00 | 0.00 | -55.91 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -4570.42 | 0.00 | 0.00 | 737.21 | 496.34 | 1435.25 | 2835.31 | 0.00 | 30.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -964.62 |
PERIMETER_BOT_ZN_2 | 15-OCT-09:43 | 0.00 | 0.00 | 0.00 | -9257.51 | 0.00 | 0.00 | 16.94 | 17.46 | 302.86 | 5212.64 | 0.00 | 21.02 | 3686.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -12009.29 | 0.00 | 0.00 | 25.46 | 27.57 | 478.41 | 12180.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -44.40 | -658.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-16:12 | 0.00 | 0.00 | 0.00 | -9024.24 | 0.00 | 0.00 | 17.09 | 17.46 | 302.86 | 6687.67 | 0.00 | 0.00 | 2035.60 | 0.00 | -0.00 | 0.00 | -36.43 | 0.00 |
PERIMETER_MID_ZN_3 | 16-OCT-12:30 | 0.00 | 0.00 | 0.00 | -5342.74 | 0.00 | 0.00 | 737.21 | 496.34 | 1435.25 | 2818.61 | 0.00 | 48.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -192.98 |
PERIMETER_MID_ZN_2 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -11356.16 | 0.00 | 0.00 | 15.80 | 17.46 | 302.86 | 6570.95 | 0.00 | 0.00 | 4466.88 | 0.00 | -0.00 | 0.00 | -17.79 | 0.00 |
PERIMETER_MID_ZN_1 | 19-NOV-12:42 | 0.00 | 0.00 | 0.00 | -13801.88 | 0.00 | 0.00 | 23.65 | 27.57 | 478.41 | 12408.90 | 0.00 | 0.00 | 884.32 | 0.00 | -0.00 | 0.00 | -20.98 | 0.00 |
PERIMETER_MID_ZN_4 | 30-JUL-16:12 | 0.00 | 0.00 | 0.00 | -11856.49 | 0.00 | 0.00 | 15.61 | 17.46 | 302.86 | 6645.18 | 0.00 | 0.00 | 4928.77 | 0.00 | -0.00 | 0.00 | -53.39 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:05 | 0.00 | -9104.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 9047.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4479.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 4465.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 16-OCT-16:00 | 0.00 | -4543.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 4533.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-OCT-14:05 | 0.00 | -17244.87 | 0.00 | -138998.18 | 0.00 | 0.00 | 17579.32 | 19671.42 | 41659.26 | 58067.80 | 0.00 | 1019.82 | 18245.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-07:03 | 0.00 | 0.00 | 13315.39 | 0.00 | 0.00 | 0.00 | 916.90 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18903.57 |
PERIMETER_TOP_ZN_3 | 03-JAN-06:12 | 0.00 | 0.00 | 5781.35 | 0.00 | 0.00 | 0.00 | 103.81 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2099.46 | 0.00 | -22.10 | -4517.11 |
PERIMETER_TOP_ZN_2 | 03-JAN-06:12 | 0.00 | 0.00 | 4543.75 | 0.00 | 0.00 | 0.00 | 65.79 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1398.98 | 0.00 | -14.80 | -3672.77 |
PERIMETER_TOP_ZN_1 | 03-JAN-06:12 | 0.00 | 0.00 | 6307.56 | 0.00 | 0.00 | 0.00 | 102.21 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2133.72 | 0.00 | -22.80 | -5006.73 |
PERIMETER_TOP_ZN_4 | 03-JAN-06:12 | 0.00 | 0.00 | 4611.56 | 0.00 | 0.00 | 0.00 | 65.43 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1396.79 | 0.00 | -14.96 | -3742.22 |
PERIMETER_BOT_ZN_3 | 09-JAN-07:02 | 0.00 | 0.00 | 3561.07 | 0.00 | 0.00 | 0.00 | 191.17 | 300.71 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2225.25 | 0.00 | -26.29 | -2439.29 |
PERIMETER_BOT_ZN_2 | 30-MAR-06:02 | 0.00 | 0.00 | 2564.33 | 0.00 | 0.00 | 0.00 | 121.07 | 165.89 | 403.81 | 3167.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.84 | -6398.92 |
PERIMETER_BOT_ZN_1 | 30-MAR-06:10 | 0.00 | 0.00 | 4982.86 | 0.00 | 0.00 | 0.00 | 193.30 | 330.35 | 637.88 | 0.00 | 0.00 | 0.00 | 6027.15 | 0.00 | -1844.33 | 0.00 | -10327.21 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-MAR-06:02 | 0.00 | 0.00 | 2405.80 | 0.00 | 0.00 | 0.00 | 119.14 | 213.22 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1286.13 | 0.00 | -24.17 | -1831.67 |
PERIMETER_MID_ZN_3 | 02-JAN-07:03 | 0.00 | 0.00 | 3844.44 | 0.00 | 0.00 | 0.00 | 193.09 | 303.91 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1228.79 | 0.00 | -28.98 | -3721.56 |
PERIMETER_MID_ZN_2 | 30-MAR-06:02 | 0.00 | 0.00 | 2807.04 | 0.00 | 0.00 | 0.00 | 121.75 | 167.98 | 403.81 | 3141.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -37.17 | -6605.23 |
PERIMETER_MID_ZN_1 | 30-MAR-06:02 | 0.00 | 0.00 | 4139.57 | 0.00 | 0.00 | 0.00 | 190.63 | 331.17 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1893.23 | 0.00 | -55.95 | -3350.08 |
PERIMETER_MID_ZN_4 | 02-JAN-07:03 | 0.00 | 0.00 | 2826.79 | 0.00 | 0.00 | 0.00 | 122.24 | 196.29 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -819.99 | 0.00 | -19.45 | -2709.68 |
TOPFLOOR_PLENUM | 03-JAN-07:02 | 6126.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8.73 | -6117.63 |
MIDFLOOR_PLENUM | 08-JAN-12:23 | 3959.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -103.91 | -3855.26 |
FIRSTFLOOR_PLENUM | 13-NOV-06:12 | 3426.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.29 | -3375.66 |
Total Facility | 03-JAN-07:02 | -9040.06 | 11910.66 | 57131.10 | -11910.66 | 0.00 | 0.00 | 4374.21 | 7557.70 | 22496.85 | 5667.86 | 0.00 | 0.00 | 0.00 | 0.00 | -10699.47 | 0.00 | -13822.33 | -63665.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.8211 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2787 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.5956 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9279 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.8869 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5222 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4106 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0749 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2978 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4434 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0754 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5349 | 2.5349 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0129 | 2.0129 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0794 | 2.0794 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6008 | 0.6008 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6544 | 0.6544 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8196 | 0.8196 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7327 | 0.7327 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4738 | 0.4738 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5536 | 0.5536 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6671 | 0.6671 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5919 | 0.5919 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5248 | 0.5248 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6451 | 0.6451 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7395 | 0.7395 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6733 | 0.6733 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.8211 | 4.2787 | 4.8211 | 1.0749 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.5956 | 3.9279 | 4.5956 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.8869 | 4.5222 | 4.8869 | 1.0754 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2674 | 1.2674 | 0.6362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0064 | 1.0064 | 0.6361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0397 | 1.0397 | 0.6363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3004 | 0.3004 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3272 | 0.3272 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4098 | 0.4098 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3664 | 0.3664 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2369 | 0.2369 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2768 | 0.2768 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3335 | 0.3335 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2959 | 0.2959 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2624 | 0.2624 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3226 | 0.3226 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3697 | 0.3697 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3366 | 0.3366 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4106 | 1.0749 | 1.0749 | 1.0749 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2978 | 1.0750 | 1.0750 | 1.0750 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4434 | 1.0754 | 1.0754 | 1.0754 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 37.50 |
Number of hours cooling loads not met | 150.83 |
Number of hours not met | 188.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 11.39 | 83717.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 154.13 | 58112.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.48 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.17 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 87.33 | 19814.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.21 | 329.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 48.82 | 5763.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1319.72 |
Natural Gas | 0.00 | 11.39 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1331.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.66 |
Space Heating | 0.00 |
Space Cooling | 30.94 |
Fans (All) | 17.53 |
Service Water Heating | 9.80 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 264.89 |
Subtotal | 264.89 |
Natural Gas [MJ/m2] | |
Space Heating | 2.29 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 2.29 |
Subtotal | 2.29 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 17.46 |
Space Heating | 0.86 |
Space Cooling | 11.58 |
Fans (All) | 6.56 |
Service Water Heating | 3.67 |
Receptacle Equipment | 54.07 |
Miscellaneous | 5.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1042. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8680.83 | 79.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8702.17 | 57.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8674.00 | 86.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8703.00 | 57.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.50 | 73.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8709.00 | 51.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8671.00 | 89.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8653.50 | 106.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8653.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 106.50 | 0.00 | 0.00 | 0.00 |
Average | 8718.18 | 41.82 | 0.00 | 0.00 | 0.00 |
Sum | 156927.17 | 752.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128291.00 | 13.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Average | 34142.61 | 0.72 | 0.00 | 0.00 | 0.00 |
Sum | 614567.00 | 13.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7689.50 | 1070.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8333.67 | 426.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8623.00 | 137.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8726.00 | 34.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8609.67 | 150.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8630.50 | 129.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8552.00 | 208.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8537.33 | 222.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8570.83 | 189.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8379.83 | 380.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8696.17 | 63.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8514.00 | 246.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8563.67 | 196.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8400.67 | 359.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8202.50 | 557.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8598.00 | 162.00 | 0.00 | 0.00 | 0.00 |
Min | 7689.50 | 26.17 | 0.00 | 0.00 | 0.00 |
Max | 8733.83 | 1070.50 | 0.00 | 0.00 | 0.00 |
Average | 8504.21 | 255.79 | 0.00 | 0.00 | 0.00 |
Sum | 153075.83 | 4604.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127775.83 | 528.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128127.00 | 177.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128240.33 | 63.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14013.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24687.17 | 221.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128240.33 | 528.17 | 0.00 | 0.00 | 0.00 |
Average | 34088.11 | 55.22 | 0.00 | 0.00 | 0.00 |
Sum | 613586.00 | 994.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:12
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182992E+11 | 34797.51 | 17-JAN-07:03 | 15.33 | 13.25 | 0.199336E+10 | 2606.76 | 10-JAN-14:09 | 15.33 | 13.25 |
February | 0.166921E+11 | 33865.51 | 21-FEB-07:02 | 8.67 | 7.39 | 0.180801E+10 | 2606.82 | 01-FEB-14:09 | 8.67 | 7.39 |
March | 0.193723E+11 | 33915.48 | 24-MAR-06:02 | 12.17 | 12.17 | 0.215930E+10 | 2606.73 | 01-MAR-14:09 | 12.17 | 12.17 |
April | 0.197068E+11 | 34614.44 | 28-APR-06:02 | 14.17 | 12.31 | 0.191868E+10 | 2606.80 | 13-APR-09:00 | 14.17 | 12.31 |
May | 0.215521E+11 | 36681.44 | 08-MAY-05:12 | 14.00 | 12.84 | 0.207841E+10 | 2606.83 | 03-MAY-13:00 | 14.00 | 12.84 |
June | 0.225746E+11 | 37063.11 | 26-JUN-05:12 | 17.33 | 15.20 | 0.207235E+10 | 2606.65 | 23-JUN-09:20 | 17.33 | 15.20 |
July | 0.233447E+11 | 38266.40 | 31-JUL-05:12 | 17.00 | 16.37 | 0.192665E+10 | 2606.64 | 11-JUL-09:20 | 17.00 | 16.37 |
August | 0.251694E+11 | 37763.10 | 21-AUG-05:12 | 16.83 | 15.53 | 0.216185E+10 | 2606.63 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.222216E+11 | 38375.37 | 05-SEP-05:12 | 16.00 | 14.76 | 0.192019E+10 | 2606.68 | 21-SEP-09:39 | 20.33 | 18.35 |
October | 0.230773E+11 | 38266.77 | 02-OCT-05:12 | 19.07 | 17.72 | 0.199649E+10 | 2606.77 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.198200E+11 | 37175.94 | 13-NOV-06:12 | 11.33 | 10.63 | 0.197570E+10 | 2606.91 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.187964E+11 | 33962.94 | 08-DEC-07:02 | 11.37 | 11.15 | 0.192339E+10 | 2607.05 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.250627E+12 | 0.239344E+11 | ||||||||
Minimum of Months | 0.166921E+11 | 33865.51 | 8.67 | 7.39 | 0.180801E+10 | 2606.63 | 8.67 | 7.39 | ||
Maximum of Months | 0.251694E+11 | 38375.37 | 19.07 | 17.72 | 0.216185E+10 | 2607.05 | 22.00 | 18.35 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112678E+10 | 5010.38 | 18-JAN-15:05 | 22.83 | 14.90 | 0.00 | 0.00 | 01-JAN-00:10 | 22.83 | 14.90 |
February | 0.104627E+10 | 4696.98 | 01-FEB-14:05 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.149096E+10 | 6212.53 | 23-MAR-14:30 | 22.50 | 17.35 | 0.00 | 0.00 | 01-MAR-00:10 | 22.50 | 17.35 |
April | 0.286899E+10 | 7805.75 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.282348E+10 | 6964.59 | 03-MAY-13:30 | 23.50 | 15.91 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 15.91 |
June | 0.376159E+10 | 6858.15 | 27-JUN-13:30 | 23.50 | 18.58 | 0.00 | 0.00 | 01-JUN-00:10 | 23.50 | 18.58 |
July | 0.474063E+10 | 8310.92 | 31-JUL-13:30 | 27.50 | 21.02 | 0.00 | 0.00 | 01-JUL-00:10 | 27.50 | 21.02 |
August | 0.497069E+10 | 8048.16 | 14-AUG-13:05 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.343774E+10 | 8970.78 | 29-SEP-14:05 | 33.83 | 17.79 | 0.00 | 0.00 | 01-SEP-00:10 | 33.83 | 17.79 |
October | 0.294020E+10 | 9104.29 | 16-OCT-13:05 | 33.75 | 16.65 | 0.00 | 0.00 | 01-OCT-00:10 | 33.75 | 16.65 |
November | 0.135688E+10 | 4457.36 | 10-NOV-14:05 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.113366E+10 | 4533.27 | 19-DEC-14:10 | 22.83 | 9.79 | 0.00 | 0.00 | 01-DEC-00:10 | 22.83 | 9.79 |
Annual Sum or Average | 0.316979E+11 | 0.00 | ||||||||
Minimum of Months | 0.104627E+10 | 4457.36 | 19.00 | 9.79 | 0.00 | 0.00 | 19.00 | 9.79 | ||
Maximum of Months | 0.497069E+10 | 9104.29 | 33.83 | 21.02 | 0.00 | 0.00 | 33.83 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420184E+09 | 1685.25 | 18-JAN-15:40 | 22.33 | 15.21 | 0.00 | 0.00 | 01-JAN-00:10 | 22.33 | 15.21 |
February | 0.424849E+09 | 1466.03 | 02-FEB-15:30 | 18.50 | 13.23 | 0.00 | 0.00 | 01-FEB-00:10 | 18.50 | 13.23 |
March | 0.484425E+09 | 1903.94 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.102257E+10 | 2364.45 | 26-APR-15:50 | 22.17 | 16.38 | 0.00 | 0.00 | 01-APR-00:10 | 22.17 | 16.38 |
May | 0.113350E+10 | 2251.38 | 03-MAY-15:50 | 21.17 | 15.06 | 0.00 | 0.00 | 01-MAY-00:10 | 21.17 | 15.06 |
June | 0.169347E+10 | 2603.48 | 26-JUN-16:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.00 | 17.40 |
July | 0.224556E+10 | 3333.63 | 31-JUL-15:20 | 25.33 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 25.33 | 20.29 |
August | 0.245374E+10 | 3175.02 | 14-AUG-15:50 | 25.17 | 18.63 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 18.63 |
September | 0.175919E+10 | 3629.88 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.169689E+10 | 4479.23 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.617036E+09 | 1493.31 | 10-NOV-15:20 | 18.67 | 15.74 | 0.00 | 0.00 | 01-NOV-00:10 | 18.67 | 15.74 |
December | 0.448341E+09 | 1706.37 | 19-DEC-15:50 | 21.17 | 8.50 | 0.00 | 0.00 | 01-DEC-00:10 | 21.17 | 8.50 |
Annual Sum or Average | 0.143997E+11 | 0.00 | ||||||||
Minimum of Months | 0.420184E+09 | 1466.03 | 18.50 | 8.50 | 0.00 | 0.00 | 18.50 | 8.50 | ||
Maximum of Months | 0.245374E+10 | 4479.23 | 32.00 | 20.29 | 0.00 | 0.00 | 32.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106185E+10 | 2566.47 | 18-JAN-15:40 | 22.33 | 15.21 | 0.00 | 0.00 | 01-JAN-00:10 | 22.33 | 15.21 |
February | 0.954173E+09 | 2096.05 | 03-FEB-16:00 | 21.00 | 10.02 | 0.00 | 0.00 | 01-FEB-00:10 | 21.00 | 10.02 |
March | 0.104612E+10 | 2440.42 | 23-MAR-16:00 | 21.00 | 17.19 | 0.00 | 0.00 | 01-MAR-00:10 | 21.00 | 17.19 |
April | 0.165285E+10 | 2805.57 | 26-APR-15:30 | 22.50 | 16.32 | 0.00 | 0.00 | 01-APR-00:10 | 22.50 | 16.32 |
May | 0.182154E+10 | 2601.60 | 03-MAY-15:50 | 21.17 | 15.06 | 0.00 | 0.00 | 01-MAY-00:10 | 21.17 | 15.06 |
June | 0.230410E+10 | 2968.95 | 26-JUN-16:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-JUN-00:10 | 22.00 | 17.40 |
July | 0.287227E+10 | 3781.76 | 31-JUL-15:20 | 25.33 | 20.29 | 0.00 | 0.00 | 01-JUL-00:10 | 25.33 | 20.29 |
August | 0.317447E+10 | 3694.94 | 14-AUG-15:20 | 25.67 | 19.05 | 0.00 | 0.00 | 01-AUG-00:10 | 25.67 | 19.05 |
September | 0.251394E+10 | 3802.20 | 29-SEP-16:00 | 32.00 | 16.86 | 0.00 | 0.00 | 01-SEP-00:10 | 32.00 | 16.86 |
October | 0.255836E+10 | 4543.30 | 16-OCT-16:00 | 29.00 | 15.43 | 0.00 | 0.00 | 01-OCT-00:10 | 29.00 | 15.43 |
November | 0.147626E+10 | 2463.30 | 13-NOV-15:10 | 17.83 | 13.90 | 0.00 | 0.00 | 01-NOV-00:10 | 17.83 | 13.90 |
December | 0.117502E+10 | 2499.46 | 19-DEC-16:10 | 20.67 | 8.11 | 0.00 | 0.00 | 01-DEC-00:10 | 20.67 | 8.11 |
Annual Sum or Average | 0.226110E+11 | 0.00 | ||||||||
Minimum of Months | 0.954173E+09 | 2096.05 | 17.83 | 8.11 | 0.00 | 0.00 | 17.83 | 8.11 | ||
Maximum of Months | 0.317447E+10 | 4543.30 | 32.00 | 20.29 | 0.00 | 0.00 | 32.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105914E+11 | 12898.18 | 19-JAN-16:20 | 18.67 | 14.64 | 0.195250E+10 | 2606.72 | 10-JAN-14:09 | 18.67 | 14.64 |
February | 0.988413E+10 | 12575.44 | 03-FEB-17:00 | 18.00 | 9.93 | 0.177895E+10 | 2606.86 | 01-FEB-14:09 | 18.00 | 9.93 |
March | 0.114132E+11 | 13091.12 | 24-MAR-16:00 | 18.00 | 14.96 | 0.212900E+10 | 2606.68 | 01-MAR-14:09 | 18.00 | 14.96 |
April | 0.125744E+11 | 14001.53 | 27-APR-16:00 | 18.00 | 14.37 | 0.190147E+10 | 2606.73 | 13-APR-09:00 | 18.00 | 14.37 |
May | 0.136915E+11 | 14037.36 | 04-MAY-16:00 | 22.00 | 15.83 | 0.206450E+10 | 2606.78 | 03-MAY-13:00 | 22.00 | 15.83 |
June | 0.147898E+11 | 14618.34 | 26-JUN-16:00 | 22.00 | 17.40 | 0.206380E+10 | 2606.65 | 23-JUN-09:20 | 22.00 | 17.40 |
July | 0.157984E+11 | 28335.01 | 31-JUL-05:12 | 17.00 | 16.37 | 0.191944E+10 | 2606.64 | 13-JUL-09:20 | 17.00 | 16.37 |
August | 0.169185E+11 | 23282.27 | 21-AUG-06:03 | 16.58 | 15.13 | 0.215543E+10 | 2606.63 | 02-AUG-09:20 | 16.58 | 15.13 |
September | 0.143604E+11 | 18215.88 | 25-SEP-06:03 | 17.17 | 16.43 | 0.191171E+10 | 2606.66 | 21-SEP-09:20 | 17.17 | 16.43 |
October | 0.148547E+11 | 29724.56 | 02-OCT-05:12 | 19.07 | 17.72 | 0.198639E+10 | 2606.71 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.117505E+11 | 13226.71 | 01-NOV-16:00 | 16.80 | 12.58 | 0.195645E+10 | 2606.82 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.109846E+11 | 12885.64 | 19-DEC-16:20 | 20.33 | 7.94 | 0.189586E+10 | 2606.95 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.157612E+12 | 0.237155E+11 | ||||||||
Minimum of Months | 0.988413E+10 | 12575.44 | 16.58 | 7.94 | 0.177895E+10 | 2606.63 | 16.58 | 9.93 | ||
Maximum of Months | 0.169185E+11 | 29724.56 | 22.00 | 17.72 | 0.215543E+10 | 2606.95 | 22.00 | 17.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.912400E+10 | 12603.54 | 18-JAN-15:50 | 22.17 | 15.30 | 0.188039E+10 | 2606.69 | 10-JAN-14:39 | 22.17 | 15.30 |
February | 0.870126E+10 | 12353.06 | 02-FEB-16:00 | 18.00 | 13.25 | 0.172498E+10 | 2606.87 | 01-FEB-14:09 | 18.00 | 13.25 |
March | 0.102301E+11 | 13692.14 | 23-MAR-16:00 | 21.00 | 17.19 | 0.206458E+10 | 2606.69 | 01-MAR-14:09 | 21.00 | 17.19 |
April | 0.119620E+11 | 15217.93 | 27-APR-15:20 | 18.80 | 14.83 | 0.187998E+10 | 2606.71 | 13-APR-13:00 | 18.80 | 14.83 |
May | 0.130719E+11 | 15435.38 | 03-MAY-15:20 | 21.67 | 15.26 | 0.204646E+10 | 2606.79 | 03-MAY-13:00 | 21.67 | 15.26 |
June | 0.146570E+11 | 16110.37 | 26-JUN-14:00 | 22.00 | 17.40 | 0.205448E+10 | 2606.64 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.159034E+11 | 17239.36 | 31-JUL-14:00 | 27.00 | 20.84 | 0.191447E+10 | 2606.65 | 13-JUL-09:20 | 27.00 | 20.84 |
August | 0.168633E+11 | 16817.86 | 14-AUG-14:00 | 25.00 | 20.20 | 0.214941E+10 | 2606.65 | 18-AUG-13:20 | 25.33 | 20.30 |
September | 0.136623E+11 | 16903.56 | 29-SEP-14:40 | 33.33 | 17.61 | 0.190041E+10 | 2606.67 | 13-SEP-09:09 | 33.33 | 17.61 |
October | 0.136532E+11 | 23219.59 | 02-OCT-05:12 | 19.07 | 17.72 | 0.196981E+10 | 2606.70 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.100154E+11 | 12529.68 | 01-NOV-16:00 | 16.80 | 12.58 | 0.191585E+10 | 2606.81 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.935660E+10 | 12524.86 | 19-DEC-16:00 | 21.00 | 8.28 | 0.183494E+10 | 2606.93 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.147200E+12 | 0.233358E+11 | ||||||||
Minimum of Months | 0.870126E+10 | 12353.06 | 16.80 | 8.28 | 0.172498E+10 | 2606.64 | 18.00 | 10.62 | ||
Maximum of Months | 0.168633E+11 | 23219.59 | 33.33 | 20.84 | 0.214941E+10 | 2606.93 | 33.33 | 20.84 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153312E+10 | 2746.76 | 18-JAN-14:50 | 23.27 | 14.80 | 0.371146E+09 | 549.50 | 13-JAN-14:20 | 23.27 | 14.80 |
February | 0.150415E+10 | 2392.01 | 03-FEB-15:00 | 23.00 | 8.84 | 0.344432E+09 | 549.54 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.184116E+10 | 3010.22 | 23-MAR-15:20 | 21.67 | 17.34 | 0.411408E+09 | 549.50 | 09-MAR-14:20 | 21.67 | 17.34 |
April | 0.240773E+10 | 4120.33 | 26-APR-14:00 | 26.00 | 16.74 | 0.386264E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.283221E+10 | 4423.25 | 04-MAY-13:50 | 23.00 | 16.67 | 0.424739E+09 | 549.53 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.353224E+10 | 4284.12 | 26-JUN-16:00 | 22.00 | 17.40 | 0.430482E+09 | 549.50 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.396163E+10 | 4922.40 | 31-JUL-14:00 | 27.00 | 20.84 | 0.402346E+09 | 549.50 | 13-JUL-09:20 | 27.00 | 20.84 |
August | 0.395683E+10 | 4691.29 | 18-AUG-15:00 | 27.00 | 20.85 | 0.450598E+09 | 549.50 | 18-AUG-13:20 | 27.00 | 20.85 |
September | 0.296949E+10 | 5572.82 | 29-SEP-13:50 | 34.33 | 17.92 | 0.395404E+09 | 549.50 | 13-SEP-09:20 | 34.33 | 17.92 |
October | 0.287777E+10 | 5805.90 | 16-OCT-13:10 | 33.75 | 16.65 | 0.407158E+09 | 549.50 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.173250E+10 | 2490.50 | 10-NOV-14:10 | 19.83 | 15.69 | 0.385635E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.158327E+10 | 2716.47 | 05-DEC-15:00 | 25.00 | 13.22 | 0.361826E+09 | 549.54 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.307321E+11 | 0.477144E+10 | ||||||||
Minimum of Months | 0.150415E+10 | 2392.01 | 19.83 | 8.84 | 0.344432E+09 | 549.50 | 18.00 | 8.84 | ||
Maximum of Months | 0.396163E+10 | 5805.90 | 34.33 | 20.85 | 0.450598E+09 | 549.54 | 34.33 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136259E+10 | 3235.60 | 20-JAN-10:00 | 19.00 | 14.77 | 0.253639E+09 | 347.88 | 10-JAN-14:20 | 19.00 | 14.77 |
February | 0.137707E+10 | 3081.00 | 02-FEB-10:10 | 17.17 | 12.19 | 0.228817E+09 | 347.90 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.177276E+10 | 4845.81 | 23-MAR-09:30 | 20.50 | 15.62 | 0.274139E+09 | 347.88 | 01-MAR-14:09 | 20.50 | 15.62 |
April | 0.272689E+10 | 9839.31 | 30-APR-09:32 | 24.00 | 16.06 | 0.251328E+09 | 347.91 | 13-APR-09:00 | 24.00 | 16.06 |
May | 0.275320E+10 | 6324.42 | 28-MAY-09:03 | 19.33 | 14.45 | 0.272942E+09 | 347.90 | 03-MAY-13:00 | 19.33 | 14.45 |
June | 0.335029E+10 | 10642.53 | 25-JUN-09:02 | 22.17 | 16.55 | 0.273842E+09 | 347.89 | 22-JUN-09:50 | 22.17 | 16.55 |
July | 0.405557E+10 | 11211.69 | 23-JUL-09:53 | 25.00 | 20.21 | 0.255930E+09 | 347.88 | 17-JUL-09:39 | 25.00 | 20.21 |
August | 0.427685E+10 | 11097.90 | 13-AUG-09:13 | 24.00 | 19.51 | 0.286964E+09 | 347.88 | 18-AUG-13:20 | 25.33 | 20.30 |
September | 0.293495E+10 | 10219.20 | 10-SEP-08:43 | 21.50 | 17.28 | 0.252641E+09 | 347.89 | 13-SEP-09:09 | 22.17 | 18.15 |
October | 0.268248E+10 | 11102.19 | 15-OCT-08:43 | 32.33 | 15.60 | 0.262748E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.156184E+10 | 2833.52 | 01-NOV-09:30 | 15.00 | 12.66 | 0.255905E+09 | 347.90 | 29-NOV-14:50 | 18.67 | 10.63 |
December | 0.139146E+10 | 3220.52 | 05-DEC-09:50 | 25.67 | 12.88 | 0.246012E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.302460E+11 | 0.311491E+10 | ||||||||
Minimum of Months | 0.136259E+10 | 2833.52 | 15.00 | 12.19 | 0.228817E+09 | 347.88 | 17.17 | 10.63 | ||
Maximum of Months | 0.427685E+10 | 11211.69 | 32.33 | 20.21 | 0.286964E+09 | 347.91 | 25.33 | 20.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490128E+10 | 14120.79 | 22-JAN-14:32 | 17.33 | 12.40 | 0.405412E+09 | 550.00 | 20-JAN-14:09 | 17.33 | 12.40 |
February | 0.365147E+10 | 14039.20 | 20-FEB-13:23 | 17.00 | 10.63 | 0.363323E+09 | 549.81 | 03-FEB-14:00 | 17.00 | 10.63 |
March | 0.361084E+10 | 10764.89 | 19-MAR-13:03 | 19.83 | 15.06 | 0.428798E+09 | 549.73 | 22-MAR-13:00 | 21.00 | 16.53 |
April | 0.394718E+10 | 8042.68 | 30-APR-13:33 | 24.00 | 16.71 | 0.390803E+09 | 549.53 | 13-APR-13:39 | 24.00 | 16.71 |
May | 0.329153E+10 | 5846.92 | 04-MAY-12:40 | 23.33 | 16.64 | 0.424312E+09 | 549.54 | 03-MAY-13:50 | 23.33 | 16.64 |
June | 0.367609E+10 | 5253.79 | 30-JUN-13:10 | 23.00 | 17.85 | 0.429272E+09 | 549.50 | 27-JUN-09:20 | 23.00 | 17.85 |
July | 0.436756E+10 | 7302.93 | 31-JUL-12:40 | 28.00 | 21.19 | 0.401989E+09 | 549.50 | 13-JUL-09:20 | 28.00 | 21.19 |
August | 0.547472E+10 | 8285.15 | 30-AUG-13:00 | 24.00 | 18.12 | 0.451396E+09 | 549.51 | 14-AUG-13:30 | 24.00 | 18.12 |
September | 0.539269E+10 | 11457.36 | 10-SEP-14:43 | 22.17 | 17.57 | 0.398766E+09 | 569.14 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.608198E+10 | 14494.59 | 15-OCT-12:42 | 32.00 | 16.02 | 0.415364E+09 | 586.82 | 16-OCT-13:09 | 33.75 | 16.65 |
November | 0.503004E+10 | 14166.39 | 19-NOV-12:52 | 27.00 | 14.96 | 0.406264E+09 | 549.93 | 28-NOV-14:50 | 23.33 | 10.84 |
December | 0.517530E+10 | 14054.77 | 03-DEC-13:43 | 16.83 | 12.84 | 0.393508E+09 | 550.74 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.546007E+11 | 0.490920E+10 | ||||||||
Minimum of Months | 0.329153E+10 | 5253.79 | 16.83 | 10.63 | 0.363323E+09 | 549.50 | 17.00 | 9.79 | ||
Maximum of Months | 0.608198E+10 | 14494.59 | 32.00 | 21.19 | 0.451396E+09 | 586.82 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149792E+10 | 4744.61 | 18-JAN-15:00 | 23.00 | 14.79 | 0.241362E+09 | 347.86 | 10-JAN-14:20 | 23.00 | 14.79 |
February | 0.151273E+10 | 5108.21 | 22-FEB-15:40 | 16.60 | 12.17 | 0.221582E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.192066E+10 | 10041.75 | 19-MAR-16:23 | 17.50 | 14.74 | 0.264318E+09 | 347.85 | 10-MAR-14:00 | 17.50 | 14.74 |
April | 0.282317E+10 | 11719.68 | 30-APR-16:53 | 22.00 | 15.83 | 0.246492E+09 | 347.87 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.295343E+10 | 11892.59 | 21-MAY-16:33 | 18.33 | 13.84 | 0.269703E+09 | 347.89 | 03-MAY-13:00 | 18.33 | 13.84 |
June | 0.365921E+10 | 11655.98 | 25-JUN-15:13 | 21.00 | 16.52 | 0.272750E+09 | 347.85 | 27-JUN-09:20 | 23.00 | 18.04 |
July | 0.416065E+10 | 12942.28 | 16-JUL-16:02 | 20.83 | 16.47 | 0.255297E+09 | 347.85 | 13-JUL-09:20 | 20.83 | 16.47 |
August | 0.429942E+10 | 12984.76 | 27-AUG-16:02 | 21.67 | 17.87 | 0.286135E+09 | 347.85 | 18-AUG-13:20 | 21.67 | 17.87 |
September | 0.321726E+10 | 12829.47 | 04-SEP-16:02 | 19.67 | 15.96 | 0.251920E+09 | 347.85 | 13-SEP-09:20 | 22.33 | 18.21 |
October | 0.278434E+10 | 12380.61 | 15-OCT-15:22 | 30.50 | 15.19 | 0.259218E+09 | 347.86 | 25-OCT-13:00 | 24.00 | 11.58 |
November | 0.181499E+10 | 4830.11 | 10-NOV-14:50 | 19.17 | 15.85 | 0.247353E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.154499E+10 | 4764.23 | 19-DEC-15:30 | 21.50 | 8.94 | 0.234748E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.321888E+11 | 0.305088E+10 | ||||||||
Minimum of Months | 0.149792E+10 | 4744.61 | 16.60 | 8.94 | 0.221582E+09 | 347.85 | 16.60 | 11.58 | ||
Maximum of Months | 0.429942E+10 | 12984.76 | 30.50 | 17.87 | 0.286135E+09 | 347.91 | 24.00 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166493E+10 | 2223.46 | 18-JAN-14:10 | 24.33 | 14.82 | 0.381131E+09 | 549.49 | 18-JAN-10:20 | 24.33 | 14.82 |
February | 0.150082E+10 | 1846.81 | 01-FEB-13:10 | 23.17 | 14.41 | 0.347829E+09 | 549.51 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.175568E+10 | 1904.80 | 23-MAR-15:20 | 21.67 | 17.34 | 0.414592E+09 | 549.49 | 22-MAR-13:20 | 21.67 | 17.34 |
April | 0.194769E+10 | 2716.99 | 26-APR-14:00 | 26.00 | 16.74 | 0.388397E+09 | 549.50 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.232092E+10 | 3124.08 | 04-MAY-14:10 | 22.83 | 16.63 | 0.427715E+09 | 549.52 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.275216E+10 | 3096.38 | 26-JUN-16:00 | 22.00 | 17.40 | 0.431482E+09 | 549.50 | 23-JUN-09:20 | 22.00 | 17.40 |
July | 0.321777E+10 | 3690.02 | 31-JUL-13:10 | 27.83 | 21.13 | 0.402962E+09 | 549.50 | 11-JUL-09:20 | 27.83 | 21.13 |
August | 0.321938E+10 | 3565.64 | 18-AUG-15:00 | 27.00 | 20.85 | 0.451610E+09 | 549.49 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.259144E+10 | 4180.65 | 29-SEP-13:10 | 35.67 | 18.16 | 0.398673E+09 | 549.50 | 21-SEP-09:20 | 35.67 | 18.16 |
October | 0.271629E+10 | 4570.14 | 16-OCT-12:30 | 35.05 | 17.21 | 0.412986E+09 | 549.50 | 31-OCT-13:20 | 26.67 | 16.70 |
November | 0.179570E+10 | 2026.92 | 02-NOV-13:30 | 17.50 | 11.04 | 0.396870E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.171120E+10 | 1964.91 | 05-DEC-15:00 | 25.00 | 13.22 | 0.371477E+09 | 549.50 | 06-DEC-14:00 | 19.00 | 12.39 |
Annual Sum or Average | 0.271940E+11 | 0.482572E+10 | ||||||||
Minimum of Months | 0.150082E+10 | 1846.81 | 17.50 | 11.04 | 0.347829E+09 | 549.49 | 18.00 | 10.62 | ||
Maximum of Months | 0.321938E+10 | 4570.14 | 35.67 | 21.13 | 0.451610E+09 | 549.52 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149447E+10 | 2971.90 | 20-JAN-09:50 | 18.67 | 14.64 | 0.259081E+09 | 347.88 | 10-JAN-14:09 | 18.67 | 14.64 |
February | 0.134500E+10 | 2797.29 | 21-FEB-10:00 | 17.00 | 11.03 | 0.232224E+09 | 347.89 | 01-FEB-14:09 | 17.00 | 11.03 |
March | 0.163802E+10 | 3877.99 | 23-MAR-09:30 | 20.50 | 15.62 | 0.278141E+09 | 347.88 | 23-MAR-09:00 | 22.00 | 16.42 |
April | 0.232249E+10 | 5567.13 | 30-APR-08:43 | 21.33 | 15.18 | 0.252836E+09 | 347.91 | 13-APR-09:00 | 21.33 | 15.18 |
May | 0.238761E+10 | 4345.85 | 24-MAY-06:03 | 16.17 | 7.74 | 0.274432E+09 | 347.90 | 03-MAY-13:00 | 16.17 | 7.74 |
June | 0.276917E+10 | 5011.62 | 05-JUN-06:03 | 13.67 | 12.25 | 0.274463E+09 | 347.88 | 02-JUN-09:00 | 13.67 | 12.25 |
July | 0.353989E+10 | 8810.05 | 23-JUL-09:53 | 25.00 | 20.21 | 0.256419E+09 | 347.88 | 13-JUL-09:20 | 25.00 | 20.21 |
August | 0.378287E+10 | 8215.79 | 13-AUG-09:13 | 24.00 | 19.51 | 0.287619E+09 | 347.88 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.268218E+10 | 5597.84 | 10-SEP-09:53 | 23.00 | 17.85 | 0.254289E+09 | 347.88 | 12-SEP-09:20 | 21.67 | 16.41 |
October | 0.264795E+10 | 9257.65 | 15-OCT-09:43 | 31.33 | 16.43 | 0.264591E+09 | 347.90 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.169653E+10 | 2881.55 | 20-NOV-09:30 | 14.50 | 13.02 | 0.259745E+09 | 347.90 | 06-NOV-10:00 | 14.50 | 13.02 |
December | 0.151574E+10 | 2957.17 | 05-DEC-09:50 | 25.67 | 12.88 | 0.250740E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.278219E+11 | 0.314458E+10 | ||||||||
Minimum of Months | 0.134500E+10 | 2797.29 | 13.67 | 7.74 | 0.232224E+09 | 347.88 | 13.67 | 7.74 | ||
Maximum of Months | 0.378287E+10 | 9257.65 | 31.33 | 20.21 | 0.287619E+09 | 347.91 | 25.00 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406617E+10 | 11531.99 | 22-JAN-14:32 | 17.33 | 12.40 | 0.405474E+09 | 550.17 | 20-JAN-14:09 | 17.33 | 12.40 |
February | 0.270331E+10 | 11178.97 | 20-FEB-13:43 | 17.00 | 10.89 | 0.358085E+09 | 549.74 | 22-FEB-14:00 | 17.80 | 12.45 |
March | 0.238306E+10 | 6602.92 | 23-MAR-14:00 | 23.00 | 17.27 | 0.414682E+09 | 549.52 | 01-MAR-14:09 | 23.00 | 17.27 |
April | 0.258897E+10 | 6492.27 | 26-APR-12:00 | 26.00 | 17.28 | 0.384972E+09 | 549.52 | 13-APR-09:00 | 26.00 | 17.28 |
May | 0.214906E+10 | 4105.50 | 04-MAY-12:30 | 23.50 | 16.62 | 0.412798E+09 | 549.54 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.238543E+10 | 3579.85 | 27-JUN-13:00 | 24.00 | 18.72 | 0.419152E+09 | 549.50 | 12-JUN-13:20 | 24.00 | 18.72 |
July | 0.325770E+10 | 8302.70 | 31-JUL-12:00 | 28.00 | 21.19 | 0.397964E+09 | 549.50 | 11-JUL-09:20 | 28.00 | 21.19 |
August | 0.427401E+10 | 8159.93 | 18-AUG-12:00 | 28.00 | 21.20 | 0.448492E+09 | 549.50 | 23-AUG-09:20 | 21.67 | 16.23 |
September | 0.439475E+10 | 11317.50 | 29-SEP-12:00 | 36.00 | 18.21 | 0.398171E+09 | 690.58 | 29-SEP-12:09 | 36.00 | 18.21 |
October | 0.558955E+10 | 12011.07 | 29-OCT-12:32 | 22.33 | 15.66 | 0.418214E+09 | 717.26 | 16-OCT-12:09 | 22.33 | 15.66 |
November | 0.424609E+10 | 11932.18 | 19-NOV-12:23 | 26.50 | 15.22 | 0.405893E+09 | 551.22 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.453709E+10 | 11652.26 | 25-DEC-13:53 | 22.00 | 9.96 | 0.393322E+09 | 565.59 | 19-DEC-13:09 | 22.00 | 9.96 |
Annual Sum or Average | 0.425752E+11 | 0.485722E+10 | ||||||||
Minimum of Months | 0.214906E+10 | 3579.85 | 17.00 | 9.96 | 0.358085E+09 | 549.50 | 17.33 | 9.22 | ||
Maximum of Months | 0.558955E+10 | 12011.07 | 36.00 | 21.20 | 0.448492E+09 | 717.26 | 36.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150455E+10 | 3675.63 | 18-JAN-15:30 | 22.50 | 15.11 | 0.251042E+09 | 347.86 | 10-JAN-14:20 | 22.50 | 15.11 |
February | 0.139990E+10 | 4143.76 | 22-FEB-16:30 | 15.00 | 12.17 | 0.228552E+09 | 347.87 | 01-FEB-14:09 | 15.00 | 12.17 |
March | 0.168927E+10 | 5382.14 | 19-MAR-16:23 | 17.50 | 14.74 | 0.271884E+09 | 347.85 | 01-MAR-14:20 | 17.50 | 14.74 |
April | 0.234147E+10 | 8659.71 | 30-APR-16:42 | 22.00 | 15.83 | 0.251315E+09 | 347.86 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.252525E+10 | 5894.46 | 28-MAY-16:22 | 19.50 | 14.42 | 0.273755E+09 | 347.88 | 03-MAY-13:00 | 19.50 | 14.42 |
June | 0.304762E+10 | 7215.70 | 25-JUN-15:13 | 21.00 | 16.52 | 0.274562E+09 | 347.85 | 23-JUN-09:20 | 21.00 | 16.52 |
July | 0.365028E+10 | 8301.57 | 04-JUL-17:42 | 18.17 | 15.02 | 0.256459E+09 | 347.85 | 11-JUL-09:20 | 19.67 | 16.12 |
August | 0.380265E+10 | 9009.66 | 06-AUG-17:33 | 21.67 | 19.02 | 0.287589E+09 | 347.85 | 21-AUG-09:20 | 20.00 | 16.42 |
September | 0.296320E+10 | 9024.15 | 10-SEP-16:12 | 21.67 | 16.73 | 0.254820E+09 | 347.86 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.268730E+10 | 7958.25 | 15-OCT-15:43 | 30.17 | 14.99 | 0.263920E+09 | 347.86 | 10-OCT-09:20 | 30.17 | 14.99 |
November | 0.181496E+10 | 4088.46 | 07-NOV-15:40 | 19.00 | 14.59 | 0.257013E+09 | 347.89 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.156204E+10 | 3967.01 | 19-DEC-15:30 | 21.50 | 8.94 | 0.244624E+09 | 347.90 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.289885E+11 | 0.311554E+10 | ||||||||
Minimum of Months | 0.139990E+10 | 3675.63 | 15.00 | 8.94 | 0.228552E+09 | 347.85 | 15.00 | 12.17 | ||
Maximum of Months | 0.380265E+10 | 9024.15 | 30.17 | 19.02 | 0.287589E+09 | 347.90 | 30.17 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181016E+10 | 2743.07 | 18-JAN-14:10 | 24.33 | 14.82 | 0.386660E+09 | 549.50 | 24-JAN-14:30 | 24.50 | 15.08 |
February | 0.170299E+10 | 2457.83 | 03-FEB-15:00 | 23.00 | 8.84 | 0.358582E+09 | 549.53 | 01-FEB-14:09 | 23.00 | 8.84 |
March | 0.204027E+10 | 2844.49 | 23-MAR-15:20 | 21.67 | 17.34 | 0.427543E+09 | 549.50 | 09-MAR-14:20 | 21.67 | 17.34 |
April | 0.248815E+10 | 3739.90 | 26-APR-14:00 | 26.00 | 16.74 | 0.394028E+09 | 549.51 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.291667E+10 | 4059.40 | 04-MAY-14:10 | 22.83 | 16.63 | 0.431091E+09 | 549.53 | 03-MAY-13:00 | 22.83 | 16.63 |
June | 0.352088E+10 | 3964.07 | 26-JUN-16:00 | 22.00 | 17.40 | 0.433411E+09 | 549.50 | 23-JUN-09:20 | 22.00 | 17.40 |
July | 0.388891E+10 | 4492.99 | 31-JUL-13:10 | 27.83 | 21.13 | 0.403801E+09 | 549.50 | 13-JUL-09:20 | 27.83 | 21.13 |
August | 0.390796E+10 | 4296.93 | 07-AUG-14:00 | 26.00 | 19.99 | 0.452755E+09 | 549.50 | 02-AUG-09:20 | 26.00 | 19.99 |
September | 0.305711E+10 | 5040.65 | 29-SEP-13:10 | 35.67 | 18.16 | 0.399904E+09 | 549.50 | 21-SEP-09:20 | 35.67 | 18.16 |
October | 0.304309E+10 | 5342.42 | 16-OCT-12:30 | 35.05 | 17.21 | 0.413852E+09 | 549.50 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.198077E+10 | 2541.33 | 01-NOV-14:00 | 17.00 | 13.47 | 0.399773E+09 | 549.52 | 29-NOV-14:00 | 18.00 | 10.62 |
December | 0.184809E+10 | 2721.47 | 05-DEC-15:00 | 25.00 | 13.22 | 0.378155E+09 | 549.54 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.322050E+11 | 0.487955E+10 | ||||||||
Minimum of Months | 0.170299E+10 | 2457.83 | 17.00 | 8.84 | 0.358582E+09 | 549.50 | 18.00 | 8.84 | ||
Maximum of Months | 0.390796E+10 | 5342.42 | 35.67 | 21.13 | 0.452755E+09 | 549.54 | 35.67 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146911E+10 | 4174.38 | 20-JAN-11:05 | 21.17 | 15.50 | 0.190623E+09 | 356.46 | 05-JAN-11:09 | 21.17 | 15.50 |
February | 0.142348E+10 | 4518.04 | 14-FEB-13:02 | 16.17 | 13.10 | 0.172526E+09 | 356.47 | 02-FEB-13:09 | 16.17 | 13.10 |
March | 0.180623E+10 | 5913.06 | 23-MAR-10:05 | 22.00 | 16.49 | 0.206134E+09 | 356.47 | 23-MAR-10:09 | 22.00 | 16.49 |
April | 0.263922E+10 | 6693.16 | 30-APR-10:23 | 25.50 | 16.81 | 0.187346E+09 | 356.49 | 13-APR-10:09 | 25.50 | 16.81 |
May | 0.265916E+10 | 7332.94 | 28-MAY-08:53 | 19.00 | 14.25 | 0.203483E+09 | 356.48 | 03-MAY-14:09 | 19.00 | 14.25 |
June | 0.313381E+10 | 7187.80 | 18-JUN-09:53 | 22.00 | 16.85 | 0.203509E+09 | 356.47 | 02-JUN-10:09 | 22.00 | 16.85 |
July | 0.380180E+10 | 11360.66 | 23-JUL-09:02 | 25.00 | 19.70 | 0.190558E+09 | 356.46 | 12-JUL-10:09 | 25.00 | 19.70 |
August | 0.401377E+10 | 10293.83 | 20-AUG-08:53 | 22.00 | 18.63 | 0.212943E+09 | 356.46 | 16-AUG-12:09 | 22.00 | 18.63 |
September | 0.281747E+10 | 7480.64 | 29-SEP-12:02 | 36.00 | 18.21 | 0.188377E+09 | 356.46 | 12-SEP-10:09 | 36.00 | 18.21 |
October | 0.266282E+10 | 11002.71 | 15-OCT-08:23 | 31.00 | 15.00 | 0.196039E+09 | 356.49 | 30-OCT-12:09 | 24.33 | 16.19 |
November | 0.166969E+10 | 4313.71 | 01-NOV-12:02 | 18.00 | 13.26 | 0.191659E+09 | 356.47 | 30-NOV-15:09 | 20.50 | 12.92 |
December | 0.149750E+10 | 4722.00 | 01-DEC-13:02 | 15.17 | 11.65 | 0.185077E+09 | 356.48 | 20-DEC-15:09 | 18.67 | 12.31 |
Annual Sum or Average | 0.295941E+11 | 0.232827E+10 | ||||||||
Minimum of Months | 0.142348E+10 | 4174.38 | 15.17 | 11.65 | 0.172526E+09 | 356.46 | 16.17 | 12.31 | ||
Maximum of Months | 0.401377E+10 | 11360.66 | 36.00 | 19.70 | 0.212943E+09 | 356.49 | 36.00 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540176E+10 | 12907.47 | 22-JAN-14:32 | 17.33 | 12.40 | 0.412281E+09 | 563.39 | 18-JAN-14:09 | 17.33 | 12.40 |
February | 0.397518E+10 | 11526.07 | 19-FEB-14:03 | 16.00 | 13.03 | 0.371057E+09 | 549.99 | 16-FEB-14:20 | 16.00 | 13.03 |
March | 0.388466E+10 | 10119.03 | 19-MAR-13:13 | 19.67 | 15.00 | 0.439896E+09 | 550.17 | 24-MAR-13:20 | 19.00 | 15.88 |
April | 0.399833E+10 | 7126.88 | 26-APR-13:00 | 27.00 | 17.13 | 0.396986E+09 | 549.53 | 13-APR-13:39 | 27.00 | 17.13 |
May | 0.336398E+10 | 5424.31 | 04-MAY-12:30 | 23.50 | 16.62 | 0.430750E+09 | 549.54 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.363869E+10 | 4782.12 | 30-JUN-12:40 | 23.33 | 17.95 | 0.432690E+09 | 549.50 | 23-JUN-09:20 | 23.33 | 17.95 |
July | 0.425230E+10 | 6802.48 | 31-JUL-12:40 | 28.00 | 21.19 | 0.403708E+09 | 549.50 | 13-JUL-09:20 | 28.00 | 21.19 |
August | 0.535404E+10 | 7801.60 | 30-AUG-12:50 | 23.83 | 17.97 | 0.453384E+09 | 550.53 | 29-AUG-13:20 | 23.83 | 17.97 |
September | 0.541220E+10 | 10493.61 | 29-SEP-12:04 | 36.00 | 18.21 | 0.402138E+09 | 576.26 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.626231E+10 | 13552.14 | 29-OCT-12:32 | 22.33 | 15.66 | 0.419622E+09 | 596.90 | 16-OCT-13:09 | 22.33 | 15.66 |
November | 0.548066E+10 | 13801.75 | 19-NOV-12:42 | 26.83 | 15.05 | 0.411749E+09 | 551.11 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.570162E+10 | 12962.98 | 03-DEC-13:43 | 16.83 | 12.84 | 0.399997E+09 | 565.67 | 19-DEC-14:09 | 22.83 | 9.79 |
Annual Sum or Average | 0.567257E+11 | 0.497426E+10 | ||||||||
Minimum of Months | 0.336398E+10 | 4782.12 | 16.00 | 12.40 | 0.371057E+09 | 549.50 | 16.00 | 9.79 | ||
Maximum of Months | 0.626231E+10 | 13801.75 | 36.00 | 21.19 | 0.453384E+09 | 596.90 | 35.33 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170120E+10 | 4664.52 | 18-JAN-15:00 | 23.00 | 14.79 | 0.250118E+09 | 347.85 | 10-JAN-14:20 | 23.00 | 14.79 |
February | 0.165891E+10 | 5116.94 | 22-FEB-15:40 | 16.60 | 12.17 | 0.229712E+09 | 347.88 | 01-FEB-14:09 | 16.60 | 12.17 |
March | 0.205374E+10 | 6322.93 | 23-MAR-15:50 | 21.17 | 17.23 | 0.273737E+09 | 347.85 | 10-MAR-14:00 | 21.17 | 17.23 |
April | 0.284621E+10 | 11429.37 | 30-APR-15:53 | 22.00 | 15.83 | 0.251153E+09 | 347.87 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.298040E+10 | 11105.61 | 21-MAY-16:33 | 18.33 | 13.84 | 0.273666E+09 | 347.89 | 03-MAY-13:00 | 18.33 | 13.84 |
June | 0.360454E+10 | 10516.10 | 25-JUN-15:13 | 21.00 | 16.52 | 0.274719E+09 | 347.85 | 23-JUN-09:20 | 21.00 | 16.52 |
July | 0.404303E+10 | 11860.37 | 30-JUL-16:12 | 21.67 | 18.54 | 0.256252E+09 | 347.85 | 13-JUL-09:20 | 21.67 | 18.54 |
August | 0.421031E+10 | 11519.44 | 27-AUG-15:32 | 22.00 | 18.09 | 0.287334E+09 | 347.85 | 02-AUG-09:20 | 22.00 | 18.09 |
September | 0.324016E+10 | 11432.16 | 10-SEP-16:12 | 21.67 | 16.73 | 0.254322E+09 | 347.85 | 21-SEP-09:20 | 19.67 | 17.71 |
October | 0.288270E+10 | 9725.57 | 15-OCT-15:02 | 30.83 | 15.40 | 0.263118E+09 | 347.86 | 03-OCT-13:00 | 30.83 | 15.40 |
November | 0.199778E+10 | 4795.48 | 07-NOV-15:30 | 19.00 | 14.51 | 0.255437E+09 | 347.90 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.175023E+10 | 4727.41 | 18-DEC-15:30 | 22.00 | 8.99 | 0.243745E+09 | 347.91 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.329692E+11 | 0.311331E+10 | ||||||||
Minimum of Months | 0.165891E+10 | 4664.52 | 16.60 | 8.99 | 0.229712E+09 | 347.85 | 16.60 | 12.17 | ||
Maximum of Months | 0.421031E+10 | 11860.37 | 30.83 | 18.54 | 0.287334E+09 | 347.91 | 30.83 | 18.54 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.821903E+09 | 6126.40 | 03-JAN-07:02 | 3.67 |
February | 0.624547E+09 | 3149.25 | 09-FEB-06:03 | 6.45 |
March | 0.727961E+09 | 3967.12 | 30-MAR-06:02 | 5.58 |
April | 0.390404E+09 | 3417.96 | 30-APR-07:40 | 17.33 |
May | 0.339318E+09 | 2956.53 | 19-MAY-05:03 | 8.67 |
June | 0.181400E+09 | 2885.33 | 18-JUN-07:03 | 18.17 |
July | 0.112713E+09 | 2420.45 | 06-JUL-05:03 | 14.33 |
August | 0.135665E+09 | 2833.71 | 06-AUG-07:10 | 19.50 |
September | 0.233058E+09 | 3033.74 | 10-SEP-07:30 | 18.50 |
October | 0.349546E+09 | 2904.66 | 30-OCT-05:03 | 10.83 |
November | 0.598787E+09 | 3172.25 | 24-NOV-06:03 | 8.92 |
December | 0.781818E+09 | 3291.79 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 0.529712E+10 | |||
Minimum of Months | 0.112713E+09 | 2420.45 | 3.67 | |
Maximum of Months | 0.821903E+09 | 6126.40 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379540E+09 | 3959.05 | 08-JAN-12:23 | 17.00 |
February | 0.220680E+09 | 3194.25 | 20-FEB-15:33 | 17.00 |
March | 0.294832E+09 | 2502.20 | 19-MAR-12:33 | 20.33 |
April | 46805115.42 | 2623.32 | 02-APR-15:32 | 19.67 |
May | 26855471.85 | 2071.25 | 21-MAY-15:53 | 19.00 |
June | 13056905.76 | 1481.73 | 25-JUN-15:13 | 21.00 |
July | 21308020.88 | 1800.98 | 23-JUL-08:22 | 24.00 |
August | 17098637.07 | 1568.56 | 20-AUG-09:32 | 22.00 |
September | 20790029.63 | 2079.82 | 10-SEP-14:13 | 22.67 |
October | 40337455.94 | 3312.55 | 15-OCT-09:43 | 31.33 |
November | 0.118959E+09 | 3317.87 | 05-NOV-11:13 | 17.33 |
December | 0.241622E+09 | 3952.24 | 24-DEC-11:23 | 16.00 |
Annual Sum or Average | 0.144188E+10 | |||
Minimum of Months | 13056905.76 | 1481.73 | 16.00 | |
Maximum of Months | 0.379540E+09 | 3959.05 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104722E+09 | 2634.36 | 08-JAN-13:13 | 17.00 |
February | 53746953.87 | 2177.30 | 19-FEB-11:20 | 16.00 |
March | 56371653.58 | 1988.60 | 12-MAR-11:33 | 19.67 |
April | 22878732.59 | 1855.90 | 29-APR-05:13 | 12.00 |
May | 26755054.97 | 2681.63 | 30-MAY-05:12 | 11.00 |
June | 21004958.01 | 2427.62 | 05-JUN-05:12 | 12.33 |
July | 29902041.46 | 2167.82 | 06-JUL-05:12 | 14.67 |
August | 25283401.35 | 2057.24 | 29-AUG-05:12 | 15.87 |
September | 28776389.75 | 2398.65 | 18-SEP-05:12 | 15.00 |
October | 37688234.42 | 2565.46 | 10-OCT-05:12 | 11.67 |
November | 37724625.44 | 3425.96 | 13-NOV-06:12 | 11.33 |
December | 53639527.35 | 2678.77 | 25-DEC-11:13 | 21.67 |
Annual Sum or Average | 0.498493E+09 | |||
Minimum of Months | 21004958.01 | 1855.90 | 11.00 | |
Maximum of Months | 0.104722E+09 | 3425.96 | 21.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11731549.61 | 13315.77 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 340161.28 | 2834.68 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 12071710.89 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 11731549.61 | 13315.77 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117529E+09 | 5781.35 | 03-JAN-06:12 | 4.33 |
February | 23438124.62 | 5119.12 | 06-FEB-07:03 | 9.50 |
March | 48251320.42 | 5487.53 | 30-MAR-05:12 | 5.03 |
April | 3319486.41 | 5110.41 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 304999.60 | 3558.33 | 30-OCT-06:01 | 10.50 |
November | 11508066.46 | 5122.07 | 24-NOV-07:02 | 8.75 |
December | 49022561.96 | 5115.08 | 14-DEC-07:03 | 8.17 |
Annual Sum or Average | 0.253373E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 0.117529E+09 | 5781.35 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34721769.75 | 4543.79 | 03-JAN-06:12 | 4.33 |
February | 7270972.40 | 3788.34 | 10-FEB-07:03 | 7.57 |
March | 10669124.22 | 4249.66 | 30-MAR-05:12 | 5.03 |
April | 558308.19 | 3514.23 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 90951.50 | 1061.10 | 30-OCT-06:01 | 10.50 |
November | 1099725.66 | 2758.64 | 24-NOV-07:02 | 8.75 |
December | 9713425.14 | 3759.53 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 64124276.86 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 34721769.75 | 4543.79 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42243504.02 | 6307.57 | 03-JAN-06:12 | 4.33 |
February | 9947553.51 | 5518.53 | 11-FEB-07:03 | 8.08 |
March | 28379950.15 | 6051.62 | 30-MAR-05:12 | 5.03 |
April | 2903441.76 | 5587.94 | 01-APR-06:03 | 7.67 |
May | 129978.97 | 433.26 | 15-MAY-06:05 | 11.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 1163282.08 | 3313.33 | 24-NOV-07:02 | 8.75 |
December | 11592414.91 | 5508.91 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 96360125.40 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 42243504.02 | 6307.57 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66093503.90 | 4611.60 | 03-JAN-06:12 | 4.33 |
February | 12570412.81 | 3848.85 | 06-FEB-07:03 | 9.50 |
March | 26954549.00 | 4239.92 | 30-MAR-05:12 | 5.03 |
April | 2303547.22 | 3848.34 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 5490355.50 | 3859.93 | 24-NOV-07:02 | 8.75 |
December | 27215175.15 | 3849.70 | 14-DEC-07:03 | 8.17 |
Annual Sum or Average | 0.140628E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.33 | |
Maximum of Months | 66093503.90 | 4611.60 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5608217.34 | 3561.11 | 09-JAN-07:02 | 3.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2647713.27 | 3470.98 | 30-MAR-06:02 | 5.58 |
April | 209736.58 | 1398.24 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 58572.62 | 390.48 | 26-DEC-07:03 | 7.67 |
Annual Sum or Average | 8524239.80 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 5608217.34 | 3561.11 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 278198.48 | 2318.32 | 03-JAN-07:02 | 3.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 348870.39 | 2564.38 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 627068.87 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 348870.39 | 2564.38 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234106E+09 | 4576.35 | 10-JAN-07:10 | 4.67 |
February | 0.246642E+09 | 4330.07 | 10-FEB-07:10 | 7.57 |
March | 0.451191E+09 | 4983.25 | 30-MAR-06:10 | 5.58 |
April | 0.196233E+09 | 3992.01 | 19-APR-06:10 | 10.33 |
May | 0.163524E+09 | 3938.69 | 15-MAY-06:15 | 11.67 |
June | 46936377.12 | 3720.02 | 01-JUN-06:10 | 13.17 |
July | 175103.84 | 1149.96 | 17-JUL-06:10 | 15.12 |
August | 595850.00 | 941.05 | 28-AUG-06:10 | 14.00 |
September | 13010598.43 | 3698.40 | 20-SEP-06:08 | 12.17 |
October | 43510706.23 | 3954.88 | 12-OCT-06:10 | 9.67 |
November | 0.106644E+09 | 4008.48 | 30-NOV-07:10 | 8.67 |
December | 0.201058E+09 | 4437.21 | 13-DEC-07:10 | 7.17 |
Annual Sum or Average | 0.170363E+10 | |||
Minimum of Months | 175103.84 | 941.05 | 4.67 | |
Maximum of Months | 0.451191E+09 | 4983.25 | 15.12 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 936266.37 | 2357.56 | 03-JAN-07:02 | 3.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 341303.09 | 2405.83 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 1277569.46 | |||
Minimum of Months | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 936266.37 | 2405.83 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8791071.70 | 3844.39 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 2313325.59 | 3815.88 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 598788.03 | 1948.81 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 11703185.31 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 8791071.70 | 3844.39 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1621521.57 | 2802.04 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 484482.58 | 2807.13 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 2106004.15 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 1621521.57 | 2807.13 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1970699.89 | 4114.50 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 1025783.10 | 4139.65 | 30-MAR-06:02 | 5.58 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 2996482.99 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 1970699.89 | 4139.65 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4877521.94 | 2826.75 | 02-JAN-07:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 1022974.69 | 2755.69 | 30-MAR-06:02 | 5.58 |
April | 36475.20 | 243.17 | 01-APR-06:03 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 202163.31 | 1347.76 | 13-DEC-07:03 | 7.17 |
Annual Sum or Average | 6139135.14 | |||
Minimum of Months | 0.00 | 0.00 | 5.58 | |
Maximum of Months | 4877521.94 | 2826.75 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618672E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.525043E+09 | 921.23 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602906E+09 | 695.51 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.517778E+09 | 580.27 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.546517E+09 | 566.09 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.540168E+09 | 553.50 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.507292E+09 | 537.34 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571191E+09 | 567.44 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.530792E+09 | 739.80 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579253E+09 | 759.77 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.605764E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.608253E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.675363E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.507292E+09 | 537.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.618672E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.384943E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.330400E+09 | 585.99 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379348E+09 | 441.49 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328191E+09 | 370.87 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347689E+09 | 342.96 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344107E+09 | 336.66 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323027E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362734E+09 | 341.18 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334278E+09 | 422.98 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361717E+09 | 502.78 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.380234E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.377630E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425430E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323027E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.384943E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594751E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.514332E+09 | 913.55 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597776E+09 | 584.17 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518486E+09 | 577.95 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549757E+09 | 569.13 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545082E+09 | 560.74 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.511460E+09 | 546.98 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.573796E+09 | 569.00 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.528822E+09 | 724.72 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.560359E+09 | 706.68 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.585976E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.580366E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.666096E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.511460E+09 | 546.98 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.597776E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.382247E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.328524E+09 | 571.59 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379392E+09 | 471.08 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328315E+09 | 369.13 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347096E+09 | 366.45 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342741E+09 | 361.61 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321586E+09 | 356.56 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362458E+09 | 368.05 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335733E+09 | 491.79 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359422E+09 | 495.84 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373557E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.374432E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423550E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321586E+09 | 356.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.382247E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.616341E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.523762E+09 | 916.66 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601849E+09 | 682.01 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.517242E+09 | 577.38 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.546118E+09 | 562.49 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.539679E+09 | 549.26 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.506999E+09 | 532.32 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.570796E+09 | 563.91 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.529944E+09 | 728.24 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.576737E+09 | 747.86 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.603759E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.605993E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.673922E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.506999E+09 | 532.32 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.616341E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.384283E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.329836E+09 | 583.75 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378881E+09 | 432.37 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.327846E+09 | 369.37 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347394E+09 | 340.05 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.343851E+09 | 333.72 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.322787E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362366E+09 | 338.15 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333900E+09 | 369.61 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.360756E+09 | 498.04 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.379477E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.376773E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424815E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.322787E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.384283E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594145E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.514557E+09 | 908.59 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597266E+09 | 581.40 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.517933E+09 | 574.92 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549214E+09 | 565.71 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.544496E+09 | 556.94 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.511096E+09 | 542.55 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.573278E+09 | 565.56 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.528120E+09 | 712.46 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.559807E+09 | 693.35 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.585573E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.579880E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.665537E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.511096E+09 | 542.55 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.597266E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.381433E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.327976E+09 | 568.73 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378916E+09 | 465.34 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.327928E+09 | 367.59 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.346756E+09 | 364.78 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342428E+09 | 359.74 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321287E+09 | 354.52 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362131E+09 | 366.46 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335187E+09 | 486.78 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.358465E+09 | 490.85 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373005E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.373143E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.422865E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321287E+09 | 354.52 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.381433E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618671E+09 | 1040.56 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.525042E+09 | 921.22 | 27-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602878E+09 | 695.48 | 16-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.517778E+09 | 580.27 | 21-APR-15:00 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.546517E+09 | 566.09 | 09-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.540167E+09 | 553.49 | 09-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.507291E+09 | 537.32 | 12-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.571191E+09 | 567.43 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.530791E+09 | 739.77 | 18-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579251E+09 | 759.78 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.605763E+09 | 1040.56 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.608252E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.675359E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.507291E+09 | 537.32 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.618671E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.384943E+09 | 658.76 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.330400E+09 | 585.99 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379347E+09 | 441.49 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328191E+09 | 370.87 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347682E+09 | 342.95 | 09-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344107E+09 | 336.65 | 16-JUN-14:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323027E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362734E+09 | 341.17 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334278E+09 | 422.96 | 21-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.361716E+09 | 502.77 | 20-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.380234E+09 | 658.76 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.377630E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425429E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323027E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.384943E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594750E+09 | 1040.56 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.514332E+09 | 913.54 | 27-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597775E+09 | 584.16 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.518486E+09 | 577.94 | 21-APR-15:00 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.549757E+09 | 569.12 | 09-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545081E+09 | 560.73 | 09-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.511460E+09 | 546.97 | 12-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.573796E+09 | 568.99 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.528822E+09 | 724.69 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.560358E+09 | 706.66 | 24-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.585976E+09 | 1040.56 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.580366E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.666096E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.511460E+09 | 546.97 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.597775E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.382247E+09 | 658.71 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.328524E+09 | 571.58 | 27-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379391E+09 | 471.07 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328311E+09 | 369.12 | 05-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.347096E+09 | 366.45 | 09-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.342741E+09 | 361.60 | 09-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.321586E+09 | 356.55 | 12-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.362458E+09 | 368.05 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335732E+09 | 491.78 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359421E+09 | 495.83 | 24-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.373557E+09 | 658.71 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.374432E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423550E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.321586E+09 | 356.55 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.382247E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.618672E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318836.30 | 0.135849E+09 |
February | 0.901968E+09 | 0.525043E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27066.37 | 0.160929E+09 |
March | 0.107774E+10 | 0.602906E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34630.03 | 0.176804E+09 |
April | 0.956342E+09 | 0.517778E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 361849.96 | 0.106190E+09 |
May | 0.103597E+10 | 0.546517E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130069E+09 |
June | 0.103308E+10 | 0.540168E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14665.01 | 70708579.03 |
July | 0.959235E+09 | 0.507292E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1138891.32 | 51135516.67 |
August | 0.107774E+10 | 0.571191E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1162159.86 | 61986379.29 |
September | 0.956342E+09 | 0.530792E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1832098.79 | 59988037.12 |
October | 0.994195E+09 | 0.579253E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6770794.34 | 91517658.99 |
November | 0.984487E+09 | 0.605764E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 737681.95 | 0.131852E+09 |
December | 0.959235E+09 | 0.608253E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 422190.66 | 0.138169E+09 |
Annual Sum or Average | 0.119305E+11 | 0.675363E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12820864.58 | 0.131520E+10 |
Minimum of Months | 0.901968E+09 | 0.507292E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51135516.67 |
Maximum of Months | 0.107774E+10 | 0.618672E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6770794.34 | 0.176804E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.384943E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109542.75 | 94463468.75 |
February | 0.571020E+09 | 0.330400E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16614.00 | 0.111669E+09 |
March | 0.682301E+09 | 0.379348E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122402E+09 |
April | 0.605444E+09 | 0.328191E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78110.10 | 75573932.52 |
May | 0.655854E+09 | 0.347689E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90989905.96 |
June | 0.654023E+09 | 0.344107E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9774.97 | 49043442.26 |
July | 0.607275E+09 | 0.323027E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 706875.82 | 37103637.11 |
August | 0.682301E+09 | 0.362734E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 735206.82 | 44409006.73 |
September | 0.605444E+09 | 0.334278E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220582.44 | 42825292.40 |
October | 0.629407E+09 | 0.361717E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978661.51 | 64500701.16 |
November | 0.623262E+09 | 0.380234E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137942.66 | 91711401.20 |
December | 0.607275E+09 | 0.377630E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78547.08 | 96471660.29 |
Annual Sum or Average | 0.755301E+10 | 0.425430E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7071858.15 | 0.921163E+09 |
Minimum of Months | 0.571020E+09 | 0.323027E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37103637.11 |
Maximum of Months | 0.682301E+09 | 0.384943E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3978661.51 | 0.122402E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.594751E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142235.36 | 0.151621E+09 |
February | 0.901968E+09 | 0.514332E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24905.61 | 0.176586E+09 |
March | 0.107774E+10 | 0.597776E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186636E+09 |
April | 0.956342E+09 | 0.518486E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124650.42 | 0.113623E+09 |
May | 0.103597E+10 | 0.549757E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132140E+09 |
June | 0.103308E+10 | 0.545082E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14665.68 | 70378675.94 |
July | 0.959235E+09 | 0.511460E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1119947.48 | 52230391.56 |
August | 0.107774E+10 | 0.573796E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102688.68 | 65517281.33 |
September | 0.956342E+09 | 0.528822E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1816003.46 | 67330727.36 |
October | 0.994195E+09 | 0.560359E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5839508.51 | 0.102914E+09 |
November | 0.984487E+09 | 0.585976E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52789.70 | 0.147133E+09 |
December | 0.959235E+09 | 0.580366E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98761.31 | 0.157145E+09 |
Annual Sum or Average | 0.119305E+11 | 0.666096E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10336156.20 | 0.142326E+10 |
Minimum of Months | 0.901968E+09 | 0.511460E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52230391.56 |
Maximum of Months | 0.107774E+10 | 0.597776E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5839508.51 | 0.186636E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.382247E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159594.16 | 94139266.43 |
February | 0.570983E+09 | 0.328524E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17506.69 | 0.112137E+09 |
March | 0.682256E+09 | 0.379392E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11259.69 | 0.121903E+09 |
April | 0.605404E+09 | 0.328315E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217980.55 | 76951601.08 |
May | 0.655811E+09 | 0.347096E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92595266.66 |
June | 0.653980E+09 | 0.342741E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9778.43 | 49922535.78 |
July | 0.607235E+09 | 0.321586E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 767484.47 | 37798695.33 |
August | 0.682256E+09 | 0.362458E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 756187.38 | 45302335.40 |
September | 0.605404E+09 | 0.335733E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1217301.51 | 44530720.27 |
October | 0.629366E+09 | 0.359422E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265899.61 | 65703000.27 |
November | 0.623221E+09 | 0.373557E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 359717.65 | 92386414.80 |
December | 0.607235E+09 | 0.374432E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164208.87 | 96466867.47 |
Annual Sum or Average | 0.755252E+10 | 0.423550E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7946919.00 | 0.929837E+09 |
Minimum of Months | 0.570983E+09 | 0.321586E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37798695.33 |
Maximum of Months | 0.682256E+09 | 0.382247E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4265899.61 | 0.121903E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.616341E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160891.53 | 78855016.76 |
February | 0.901968E+09 | 0.523762E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15322.42 | 91158979.65 |
March | 0.107774E+10 | 0.601849E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31131.89 | 97932893.70 |
April | 0.956342E+09 | 0.517242E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215748.94 | 57104816.66 |
May | 0.103597E+10 | 0.546118E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 69978612.69 |
June | 0.103308E+10 | 0.539679E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8670.05 | 37051409.88 |
July | 0.959235E+09 | 0.506999E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 681710.49 | 26330506.34 |
August | 0.107774E+10 | 0.570796E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 707771.95 | 32821511.48 |
September | 0.956342E+09 | 0.529944E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 983632.05 | 32337066.46 |
October | 0.994195E+09 | 0.576737E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3828651.80 | 51705697.01 |
November | 0.984487E+09 | 0.603759E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392847.67 | 76198708.17 |
December | 0.959235E+09 | 0.605993E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193366.29 | 80130830.07 |
Annual Sum or Average | 0.119305E+11 | 0.673922E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7219764.70 | 0.731606E+09 |
Minimum of Months | 0.901968E+09 | 0.506999E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 | 26330506.34 |
Maximum of Months | 0.107774E+10 | 0.616341E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3828651.80 | 97932893.70 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.384283E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52984.29 | 55890228.89 |
February | 0.571020E+09 | 0.329836E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9276.76 | 64141494.08 |
March | 0.682301E+09 | 0.378881E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 68943491.66 |
April | 0.605444E+09 | 0.327846E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42663.72 | 41578517.84 |
May | 0.655854E+09 | 0.347394E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 49670203.49 |
June | 0.654023E+09 | 0.343851E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5777.81 | 26112824.45 |
July | 0.607275E+09 | 0.322787E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 385905.32 | 19757196.09 |
August | 0.682301E+09 | 0.362366E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 403648.46 | 24389531.81 |
September | 0.605444E+09 | 0.333900E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654855.00 | 23510566.38 |
October | 0.629407E+09 | 0.360756E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2195116.55 | 36975458.49 |
November | 0.623262E+09 | 0.379477E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85692.24 | 53654281.04 |
December | 0.607275E+09 | 0.376773E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40948.99 | 56980036.26 |
Annual Sum or Average | 0.755301E+10 | 0.424815E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3876899.06 | 0.521604E+09 |
Minimum of Months | 0.571020E+09 | 0.322787E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 19757196.09 |
Maximum of Months | 0.682301E+09 | 0.384283E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2195116.55 | 68943491.66 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.594145E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4890128.99 | 0.211828E+10 |
February | 0.901968E+09 | 0.514557E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2703727.97 | 0.193733E+10 |
March | 0.107774E+10 | 0.597266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.245090E+10 |
April | 0.956342E+09 | 0.517933E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8277624.14 | 0.150307E+10 |
May | 0.103597E+10 | 0.549214E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631.37 | 0.146454E+10 |
June | 0.103308E+10 | 0.544496E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1440636.47 | 0.102833E+10 |
July | 0.959235E+09 | 0.511096E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52412436.52 | 0.629228E+09 |
August | 0.107774E+10 | 0.573278E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53618791.23 | 0.734855E+09 |
September | 0.956342E+09 | 0.528120E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78261587.19 | 0.100280E+10 |
October | 0.994195E+09 | 0.559807E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129263E+09 | 0.984415E+09 |
November | 0.984487E+09 | 0.585573E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 293795.40 | 0.191068E+10 |
December | 0.959235E+09 | 0.579880E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6334162.23 | 0.190618E+10 |
Annual Sum or Average | 0.119305E+11 | 0.665537E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337498E+09 | 0.176706E+11 |
Minimum of Months | 0.901968E+09 | 0.511096E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 0.629228E+09 |
Maximum of Months | 0.107774E+10 | 0.597266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129263E+09 | 0.245090E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.381433E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61160.58 | 55504080.71 |
February | 0.570983E+09 | 0.327976E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9278.80 | 64618739.01 |
March | 0.682256E+09 | 0.378916E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5493.65 | 68936628.93 |
April | 0.605404E+09 | 0.327928E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101746.68 | 42758694.08 |
May | 0.655811E+09 | 0.346756E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 | 51279636.67 |
June | 0.653980E+09 | 0.342428E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5783.39 | 27051960.61 |
July | 0.607235E+09 | 0.321287E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430130.99 | 20552756.97 |
August | 0.682256E+09 | 0.362131E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429820.54 | 25210292.25 |
September | 0.605404E+09 | 0.335187E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653164.11 | 24827668.71 |
October | 0.629366E+09 | 0.358465E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2306422.82 | 37982333.65 |
November | 0.623221E+09 | 0.373005E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 168190.29 | 54280071.64 |
December | 0.607235E+09 | 0.373143E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48782.60 | 57037512.77 |
Annual Sum or Average | 0.755252E+10 | 0.422865E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4219988.43 | 0.530040E+09 |
Minimum of Months | 0.570983E+09 | 0.321287E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 | 20552756.97 |
Maximum of Months | 0.682256E+09 | 0.381433E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2306422.82 | 68936628.93 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.618671E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187220.47 | 0.124255E+09 |
February | 0.901968E+09 | 0.525042E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21261.69 | 0.146607E+09 |
March | 0.107774E+10 | 0.602878E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22219.28 | 0.157667E+09 |
April | 0.956342E+09 | 0.517778E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 275085.39 | 92767085.11 |
May | 0.103597E+10 | 0.546517E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113057E+09 |
June | 0.103308E+10 | 0.540167E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12832.63 | 60398375.15 |
July | 0.959235E+09 | 0.507291E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 958020.01 | 43052376.49 |
August | 0.107774E+10 | 0.571191E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021943.43 | 53577591.77 |
September | 0.956342E+09 | 0.530791E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1532303.02 | 52172995.09 |
October | 0.994195E+09 | 0.579251E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5738058.26 | 82170003.90 |
November | 0.984487E+09 | 0.605763E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 550543.34 | 0.119813E+09 |
December | 0.959235E+09 | 0.608252E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193595.44 | 0.127150E+09 |
Annual Sum or Average | 0.119305E+11 | 0.675359E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10513082.96 | 0.117269E+10 |
Minimum of Months | 0.901968E+09 | 0.507291E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43052376.49 |
Maximum of Months | 0.107774E+10 | 0.618671E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5738058.26 | 0.157667E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.384943E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57503.22 | 86047675.93 |
February | 0.421807E+09 | 0.330400E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10068.35 | 0.101335E+09 |
March | 0.502994E+09 | 0.379347E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 0.108922E+09 |
April | 0.447140E+09 | 0.328191E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57288.99 | 65882720.82 |
May | 0.484071E+09 | 0.347682E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78973486.37 |
June | 0.482240E+09 | 0.344107E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5223.27 | 42148540.57 |
July | 0.448971E+09 | 0.323027E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 536046.24 | 31456224.37 |
August | 0.502994E+09 | 0.362734E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544040.48 | 38446642.56 |
September | 0.447140E+09 | 0.334278E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 989062.70 | 37231079.37 |
October | 0.465148E+09 | 0.361716E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3271715.54 | 57582885.72 |
November | 0.460569E+09 | 0.380234E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94586.09 | 82873866.95 |
December | 0.448971E+09 | 0.377630E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43209.27 | 88312883.88 |
Annual Sum or Average | 0.557719E+10 | 0.425429E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5608761.62 | 0.819213E+09 |
Minimum of Months | 0.421807E+09 | 0.323027E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31456224.37 |
Maximum of Months | 0.502994E+09 | 0.384943E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3271715.54 | 0.108922E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.594750E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103829.34 | 0.136278E+09 |
February | 0.901968E+09 | 0.514332E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21237.73 | 0.158519E+09 |
March | 0.107774E+10 | 0.597775E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165294E+09 |
April | 0.956342E+09 | 0.518486E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99604.67 | 98709903.49 |
May | 0.103597E+10 | 0.549757E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114651E+09 |
June | 0.103308E+10 | 0.545081E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12833.17 | 60117222.44 |
July | 0.959235E+09 | 0.511460E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 933197.81 | 43941942.55 |
August | 0.107774E+10 | 0.573796E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 932679.09 | 56439466.95 |
September | 0.956342E+09 | 0.528822E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1512284.67 | 58104959.37 |
October | 0.994195E+09 | 0.560358E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832296.99 | 91120859.95 |
November | 0.984487E+09 | 0.585976E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46033.52 | 0.131252E+09 |
December | 0.959235E+09 | 0.580366E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79017.04 | 0.141425E+09 |
Annual Sum or Average | 0.119305E+11 | 0.666096E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8573014.02 | 0.125585E+10 |
Minimum of Months | 0.901968E+09 | 0.511460E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43941942.55 |
Maximum of Months | 0.107774E+10 | 0.597775E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4832296.99 | 0.165294E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.382247E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93954.96 | 85567455.12 |
February | 0.570983E+09 | 0.328524E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14176.32 | 0.101505E+09 |
March | 0.682256E+09 | 0.379391E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5223.56 | 0.108281E+09 |
April | 0.605404E+09 | 0.328311E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164232.58 | 66919025.17 |
May | 0.655811E+09 | 0.347096E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80327348.17 |
June | 0.653980E+09 | 0.342741E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8556.48 | 42713133.02 |
July | 0.607235E+09 | 0.321586E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 642876.24 | 32060384.54 |
August | 0.682256E+09 | 0.362458E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 654725.75 | 39169446.48 |
September | 0.605404E+09 | 0.335732E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1017903.84 | 38564835.69 |
October | 0.629366E+09 | 0.359421E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560885.98 | 58565768.43 |
November | 0.623221E+09 | 0.373557E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261115.22 | 83303254.01 |
December | 0.607235E+09 | 0.374432E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70345.26 | 88101168.45 |
Annual Sum or Average | 0.755252E+10 | 0.423550E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6493996.19 | 0.825077E+09 |
Minimum of Months | 0.570983E+09 | 0.321586E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32060384.54 |
Maximum of Months | 0.682256E+09 | 0.382247E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3560885.98 | 0.108281E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107063.98 | 0.181561E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16894.56 | 0.211845E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222860E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150540.25 | 0.131687E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156516E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2600.75 | 83508654.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 784550.11 | 61690697.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 728536.61 | 77434374.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1685788.24 | 76055657.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6194822.64 | 0.120312E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293912.54 | 0.174398E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66545.76 | 0.187617E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10031255.44 | 0.168548E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61690697.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6194822.64 | 0.222860E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285288.61 | 0.219363E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29195.83 | 0.257523E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2474.24 | 0.275299E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316387.38 | 0.163761E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195447E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3856.48 | 0.105311E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046847.93 | 77668574.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993153.04 | 97335258.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2209856.78 | 94173899.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8332593.51 | 0.148149E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609933.75 | 0.213455E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155765.85 | 0.227727E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13985353.39 | 0.207521E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77668574.04 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8332593.51 | 0.275299E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298086.80 | 0.211971E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4107.67 | 0.252870E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277901E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26980.79 | 0.178337E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213296E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121125E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479437.04 | 94464541.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351423.96 | 0.106459E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2114984.66 | 0.105388E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7411148.61 | 0.146727E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265194.95 | 0.206753E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84878.82 | 0.215107E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11036243.31 | 0.213040E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94464541.02 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7411148.61 | 0.277901E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 | 15-JAN-10:00 | 294.25 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 921.23 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 01-FEB-12:00 | 310.74 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 695.51 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 11-MAR-11:05 | 342.70 | 28-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 580.27 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 | 30-APR-10:40 | 212.12 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 566.09 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 213.62 | 20-MAY-17:55 |
June | 1306.65 | 01-JUN-09:09 | 553.50 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 29-JUN-11:00 | 145.34 | 06-JUN-21:10 |
July | 1306.65 | 03-JUL-09:09 | 537.34 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 | 23-JUL-10:53 | 127.70 | 16-JUL-18:00 |
August | 1306.65 | 01-AUG-09:09 | 567.44 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 17-AUG-14:00 | 106.01 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 739.80 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 | 29-SEP-14:00 | 123.53 | 04-SEP-18:00 |
October | 1306.65 | 02-OCT-09:09 | 759.77 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.33 | 15-OCT-09:00 | 220.03 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 19-NOV-13:00 | 281.57 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.85 | 25-DEC-11:53 | 275.30 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 537.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.01 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 156.33 | 342.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 15-JAN-10:00 | 195.98 | 27-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 585.99 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 01-FEB-12:00 | 206.00 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 441.49 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 228.25 | 28-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 370.87 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 26-APR-13:00 | 142.36 | 16-APR-12:00 |
May | 827.22 | 01-MAY-09:09 | 342.96 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 146.82 | 29-MAY-13:00 |
June | 827.22 | 01-JUN-09:09 | 336.66 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 29-JUN-11:00 | 104.00 | 04-JUN-13:45 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 31-JUL-13:00 | 86.78 | 02-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 341.18 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 17-AUG-14:00 | 74.47 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 422.98 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 29-SEP-14:00 | 90.64 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 502.78 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 15-OCT-12:46 | 148.83 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 19-NOV-13:00 | 188.58 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 17-DEC-13:00 | 184.05 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.47 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 82.13 | 228.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 15-JAN-10:00 | 302.64 | 06-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 913.55 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 01-FEB-12:00 | 313.62 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 584.17 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 344.23 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 577.95 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 | 26-APR-13:00 | 224.62 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 569.13 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 217.39 | 07-MAY-15:00 |
June | 1306.65 | 01-JUN-09:09 | 560.74 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 29-JUN-11:00 | 146.82 | 04-JUN-13:45 |
July | 1306.65 | 03-JUL-09:09 | 546.98 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 31-JUL-13:00 | 124.79 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 569.00 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 17-AUG-14:00 | 113.47 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 724.72 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.30 | 29-SEP-14:00 | 160.33 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 706.68 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.81 | 15-OCT-12:58 | 234.53 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 18-NOV-13:05 | 294.13 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 05-DEC-10:00 | 284.24 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 546.98 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 117.81 | 344.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 15-JAN-10:00 | 197.13 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 571.59 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 01-FEB-12:00 | 207.22 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 471.08 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 11-MAR-11:05 | 229.57 | 28-MAR-21:10 |
April | 827.17 | 03-APR-09:09 | 369.13 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 30-APR-10:40 | 181.00 | 16-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 366.45 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 180.87 | 07-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 361.61 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 29-JUN-11:00 | 130.69 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 356.56 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.85 | 23-JUL-10:53 | 118.20 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 368.05 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 17-AUG-14:00 | 96.58 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 491.79 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 29-SEP-14:00 | 127.41 | 03-SEP-16:30 |
October | 827.17 | 02-OCT-09:09 | 495.84 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.84 | 15-OCT-09:00 | 151.16 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 19-NOV-12:32 | 190.42 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 25-DEC-11:53 | 185.41 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 356.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.58 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 102.84 | 229.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 15-JAN-10:00 | 172.41 | 02-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 916.66 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 01-FEB-12:00 | 175.95 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 682.01 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 11-MAR-14:00 | 192.00 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 577.38 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.18 | 30-APR-10:53 | 115.51 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 562.49 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 116.89 | 20-MAY-18:00 |
June | 1306.65 | 01-JUN-09:09 | 549.26 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 29-JUN-11:00 | 77.54 | 07-JUN-01:00 |
July | 1306.65 | 03-JUL-09:09 | 532.32 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | 23-JUL-10:53 | 61.59 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 563.91 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 06-AUG-12:53 | 55.91 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 728.24 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 29-SEP-14:00 | 65.63 | 04-SEP-17:55 |
October | 1306.65 | 02-OCT-09:09 | 747.86 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 15-OCT-08:52 | 127.20 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 19-NOV-12:52 | 170.75 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 25-DEC-12:00 | 157.32 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.32 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 192.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-JAN-15:00 | 120.58 | 02-JAN-03:00 |
February | 827.22 | 01-FEB-10:09 | 583.75 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 01-FEB-12:00 | 118.98 | 25-FEB-03:00 |
March | 827.22 | 01-MAR-10:09 | 432.37 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 128.48 | 28-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 369.37 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 26-APR-13:00 | 79.61 | 21-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 340.05 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 77.23 | 20-MAY-18:00 |
June | 827.22 | 01-JUN-09:09 | 333.72 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 29-JUN-11:00 | 53.41 | 04-JUN-13:55 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.21 | 31-JUL-13:00 | 45.07 | 02-JUL-19:00 |
August | 827.22 | 01-AUG-09:09 | 338.15 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 17-AUG-14:00 | 38.51 | 21-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 369.61 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 29-SEP-14:00 | 52.27 | 03-SEP-07:00 |
October | 827.22 | 02-OCT-09:09 | 498.04 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 | 15-OCT-12:50 | 89.08 | 30-OCT-03:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.69 | 19-NOV-12:50 | 116.90 | 23-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 05-DEC-10:00 | 107.38 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 | 128.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1442.91 | 18-JAN-13:00 | 14541.24 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 908.59 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.07 | 01-FEB-12:10 | 11569.01 | 09-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 581.40 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 11855.88 | 30-MAR-06:02 |
April | 1306.65 | 03-APR-09:09 | 574.92 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1591.01 | 26-APR-11:05 | 9132.06 | 03-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 565.71 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.15 | 03-MAY-12:00 | 7926.54 | 15-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 556.94 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.39 | 29-JUN-11:10 | 6565.05 | 01-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 542.55 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3162.56 | 19-JUL-12:00 | 5943.37 | 17-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 565.56 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3167.66 | 18-AUG-12:00 | 6904.49 | 28-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 712.46 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8483.00 | 29-SEP-11:02 | 7763.77 | 20-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 693.35 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8567.80 | 16-OCT-11:02 | 9965.00 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.25 | 28-NOV-14:00 | 10892.32 | 24-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.79 | 19-DEC-13:00 | 13141.81 | 22-DEC-07:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.55 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5943.37 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8567.80 | 14541.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 15-JAN-10:00 | 116.29 | 02-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 568.73 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 01-FEB-12:00 | 119.45 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 465.34 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 11-MAR-12:20 | 129.82 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 367.59 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 30-APR-10:53 | 92.28 | 16-APR-18:10 |
May | 827.17 | 01-MAY-09:09 | 364.78 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 102.54 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 359.74 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 29-JUN-11:00 | 67.69 | 03-JUN-17:10 |
July | 827.17 | 03-JUL-09:09 | 354.52 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 23-JUL-10:53 | 61.81 | 09-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 366.46 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 06-AUG-12:43 | 45.73 | 26-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 486.78 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 29-SEP-14:00 | 64.53 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 490.85 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 15-OCT-08:52 | 90.10 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 19-NOV-12:42 | 118.95 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 25-DEC-12:00 | 108.08 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 354.52 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 129.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 15-JAN-10:00 | 264.83 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 921.22 | 27-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 01-FEB-12:00 | 281.69 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 695.48 | 16-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 11-MAR-13:05 | 303.07 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 580.27 | 21-APR-15:00 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 | 30-APR-11:15 | 187.04 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 566.09 | 09-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 177.53 | 20-MAY-17:55 |
June | 1306.65 | 01-JUN-09:09 | 553.49 | 09-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 29-JUN-11:00 | 124.99 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 537.32 | 12-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 31-JUL-13:00 | 100.71 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 567.43 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 06-AUG-13:00 | 89.86 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 739.77 | 18-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 | 29-SEP-14:00 | 108.17 | 04-SEP-17:55 |
October | 1306.65 | 02-OCT-09:09 | 759.78 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 15-OCT-08:52 | 200.61 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.53 | 19-NOV-13:00 | 264.41 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 25-DEC-11:53 | 246.87 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 537.32 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.86 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 303.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 13-JAN-14:00 | 176.27 | 27-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 585.99 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 01-FEB-12:00 | 186.78 | 25-FEB-03:00 |
March | 805.43 | 01-MAR-08:09 | 441.49 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 11-MAR-13:10 | 201.45 | 28-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 370.87 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 26-APR-13:00 | 125.09 | 21-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 342.95 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 118.67 | 07-MAY-17:55 |
June | 805.43 | 01-JUN-07:10 | 336.65 | 16-JUN-14:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 29-JUN-11:00 | 83.19 | 06-JUN-21:20 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 | 31-JUL-13:00 | 70.38 | 02-JUL-19:00 |
August | 805.43 | 01-AUG-07:10 | 341.17 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 17-AUG-14:10 | 59.98 | 21-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 422.96 | 21-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.61 | 29-SEP-14:10 | 83.80 | 03-SEP-07:00 |
October | 805.43 | 02-OCT-07:10 | 502.77 | 20-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.14 | 15-OCT-12:26 | 135.35 | 30-OCT-03:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 19-NOV-13:00 | 176.93 | 23-NOV-07:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 | 05-DEC-10:00 | 164.78 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 66.14 | 201.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 | 14-JAN-11:00 | 270.13 | 27-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 913.54 | 27-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 | 01-FEB-12:00 | 283.73 | 25-FEB-03:00 |
March | 1306.65 | 01-MAR-10:09 | 584.16 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 306.28 | 28-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 577.94 | 21-APR-15:00 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 26-APR-13:00 | 187.24 | 21-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 569.12 | 09-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 177.88 | 07-MAY-17:55 |
June | 1306.65 | 01-JUN-09:09 | 560.73 | 09-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 29-JUN-11:00 | 124.61 | 06-JUN-21:20 |
July | 1306.65 | 03-JUL-09:09 | 546.97 | 12-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 31-JUL-13:00 | 101.06 | 02-JUL-19:00 |
August | 1306.65 | 01-AUG-09:09 | 568.99 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 | 17-AUG-14:00 | 90.74 | 21-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 724.69 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 | 29-SEP-14:00 | 127.78 | 03-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 706.66 | 24-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 | 15-OCT-12:46 | 212.27 | 30-OCT-03:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 18-NOV-13:10 | 273.93 | 23-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 05-DEC-10:00 | 253.53 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 546.97 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.74 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 | 306.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 15-JAN-10:00 | 177.20 | 27-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 571.58 | 27-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 01-FEB-12:00 | 187.72 | 25-FEB-03:00 |
March | 827.17 | 01-MAR-10:09 | 471.07 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 | 11-MAR-11:05 | 204.06 | 28-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 369.12 | 05-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 | 30-APR-11:10 | 149.82 | 16-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 366.45 | 09-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 148.19 | 20-MAY-18:00 |
June | 827.17 | 01-JUN-09:09 | 361.60 | 09-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 29-JUN-11:00 | 107.44 | 03-JUN-17:07 |
July | 827.17 | 03-JUL-09:09 | 356.55 | 12-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 23-JUL-10:50 | 95.71 | 09-JUL-17:20 |
August | 827.17 | 01-AUG-09:09 | 368.05 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.03 | 17-AUG-14:00 | 75.50 | 27-AUG-18:10 |
September | 827.17 | 01-SEP-09:09 | 491.78 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 29-SEP-14:00 | 104.12 | 03-SEP-16:40 |
October | 827.17 | 02-OCT-09:09 | 495.83 | 24-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.15 | 15-OCT-08:52 | 137.32 | 30-OCT-03:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 19-NOV-12:23 | 178.19 | 23-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 25-DEC-11:53 | 165.85 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 356.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.15 | 204.06 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 15-JAN-10:00 | 393.45 | 02-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 01-FEB-12:00 | 406.72 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 429.15 | 28-MAR-21:15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 30-APR-11:00 | 262.25 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 246.72 | 20-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 29-JUN-11:00 | 170.73 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 31-JUL-13:00 | 135.30 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 17-AUG-14:00 | 123.57 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 29-SEP-13:40 | 155.28 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 15-OCT-08:52 | 289.09 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 19-NOV-12:54 | 392.78 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | 05-DEC-10:00 | 353.38 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.75 | 429.15 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.36 | 15-JAN-10:00 | 471.79 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 01-FEB-12:00 | 504.71 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 | 11-MAR-11:00 | 535.63 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | 30-APR-10:53 | 324.71 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 309.54 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 29-JUN-11:00 | 218.12 | 06-JUN-21:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 23-JUL-10:53 | 171.75 | 02-JUL-19:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 06-AUG-13:00 | 156.17 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.24 | 29-SEP-13:40 | 192.72 | 04-SEP-17:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.94 | 15-OCT-08:52 | 355.88 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.06 | 19-NOV-13:00 | 483.76 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 04-DEC-10:00 | 441.25 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.17 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.94 | 535.63 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 | 15-JAN-10:00 | 438.49 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 01-FEB-12:00 | 468.44 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 538.28 | 28-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 26-APR-13:00 | 362.72 | 16-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 387.86 | 07-MAY-15:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 278.55 | 04-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 31-JUL-13:00 | 237.55 | 09-JUL-16:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.10 | 17-AUG-14:00 | 192.89 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.29 | 29-SEP-13:30 | 246.60 | 03-SEP-16:33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.21 | 15-OCT-08:52 | 325.41 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 19-NOV-09:53 | 401.68 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.24 | 04-DEC-10:00 | 417.64 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.21 | 538.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34797.51 | 17-JAN-07:03 | 5082.11 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33865.51 | 21-FEB-07:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33915.48 | 24-MAR-06:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34614.44 | 28-APR-06:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36681.44 | 08-MAY-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37063.11 | 26-JUN-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38266.40 | 31-JUL-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37763.10 | 21-AUG-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38375.37 | 05-SEP-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38266.77 | 02-OCT-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37175.94 | 13-NOV-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33962.94 | 08-DEC-07:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33865.51 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38375.37 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5010.38 | 18-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
February | 4696.98 | 01-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 |
March | 6212.53 | 23-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
April | 7805.75 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
May | 6964.59 | 03-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
June | 6858.15 | 27-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 |
July | 8310.92 | 31-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 | 0.00 |
August | 8048.16 | 14-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 8970.78 | 29-SEP-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 0.00 |
October | 9104.29 | 16-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.52 | 0.00 |
November | 4457.36 | 10-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.38 |
December | 4533.27 | 19-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4457.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9104.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 46.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1685.25 | 18-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
February | 1466.03 | 02-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 |
March | 1903.94 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 |
April | 2364.45 | 26-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 |
May | 2251.38 | 03-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 |
June | 2603.48 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
July | 3333.63 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
August | 3175.02 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.25 | 0.00 |
September | 3629.88 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 | 0.00 |
October | 4479.23 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.95 | 0.00 |
November | 1493.31 | 10-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 |
December | 1706.37 | 19-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1466.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4479.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 | 41.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2566.47 | 18-JAN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 |
February | 2096.05 | 03-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 |
March | 2440.42 | 23-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
April | 2805.57 | 26-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 |
May | 2601.60 | 03-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
June | 2968.95 | 26-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 |
July | 3781.76 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
August | 3694.94 | 14-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 0.00 |
September | 3802.20 | 29-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 0.00 |
October | 4543.30 | 16-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 0.00 |
November | 2463.30 | 13-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
December | 2499.46 | 19-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2096.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4543.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 30.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12898.18 | 19-JAN-16:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12575.44 | 03-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13091.12 | 24-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14001.53 | 27-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14037.36 | 04-MAY-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14618.34 | 26-JUN-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28335.01 | 31-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23282.27 | 21-AUG-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18215.88 | 25-SEP-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29724.56 | 02-OCT-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13226.71 | 01-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12885.64 | 19-DEC-16:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12575.44 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29724.56 | 6035.01 | 6581.44 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12603.54 | 18-JAN-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12353.06 | 02-FEB-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13692.14 | 23-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15217.93 | 27-APR-15:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15435.38 | 03-MAY-15:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16110.37 | 26-JUN-14:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17239.36 | 31-JUL-14:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16817.86 | 14-AUG-14:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16903.56 | 29-SEP-14:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23219.59 | 02-OCT-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12529.68 | 01-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12524.86 | 19-DEC-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 12353.06 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23219.59 | 6198.29 | 4936.01 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2746.76 | 18-JAN-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 |
February | 2392.01 | 03-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
March | 3010.22 | 23-MAR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 |
April | 4120.33 | 26-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
May | 4423.25 | 04-MAY-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
June | 4284.12 | 26-JUN-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 |
July | 4922.40 | 31-JUL-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 |
August | 4691.29 | 18-AUG-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 | 0.00 |
September | 5572.82 | 29-SEP-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 | 0.00 |
October | 5805.90 | 16-OCT-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 | 0.00 |
November | 2490.50 | 10-NOV-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.10 |
December | 2716.47 | 05-DEC-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2392.01 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5805.90 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 | 22.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3235.60 | 20-JAN-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
February | 3081.00 | 02-FEB-10:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
March | 4845.81 | 23-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
April | 9839.31 | 30-APR-09:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
May | 6324.42 | 28-MAY-09:03 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 |
June | 10642.53 | 25-JUN-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.70 |
July | 11211.69 | 23-JUL-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 |
August | 11097.90 | 13-AUG-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 |
September | 10219.20 | 10-SEP-08:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 |
October | 11102.19 | 15-OCT-08:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 | 0.00 |
November | 2833.52 | 01-NOV-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 |
December | 3220.52 | 05-DEC-09:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2833.52 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11211.69 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 | 67.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14120.79 | 22-JAN-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.73 |
February | 14039.20 | 20-FEB-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.63 |
March | 10764.89 | 19-MAR-13:03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.75 |
April | 8042.68 | 30-APR-13:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 |
May | 5846.92 | 04-MAY-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
June | 5253.79 | 30-JUN-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 |
July | 7302.93 | 31-JUL-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 0.00 |
August | 8285.15 | 30-AUG-13:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
September | 11457.36 | 10-SEP-14:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.18 |
October | 14494.59 | 15-OCT-12:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 96.39 | 0.00 |
November | 14166.39 | 19-NOV-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 |
December | 14054.77 | 03-DEC-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5253.79 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14494.59 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 96.39 | 239.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4744.61 | 18-JAN-15:00 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 |
February | 5108.21 | 22-FEB-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
March | 10041.75 | 19-MAR-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 |
April | 11719.68 | 30-APR-16:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 |
May | 11892.59 | 21-MAY-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.84 |
June | 11655.98 | 25-JUN-15:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.77 |
July | 12942.28 | 16-JUL-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.32 |
August | 12984.76 | 27-AUG-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 |
September | 12829.47 | 04-SEP-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 |
October | 12380.61 | 15-OCT-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
November | 4830.11 | 10-NOV-14:50 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 |
December | 4764.23 | 19-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4744.61 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12984.76 | 827.17 | 314.21 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 104.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2223.46 | 18-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
February | 1846.81 | 01-FEB-13:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.44 |
March | 1904.80 | 23-MAR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
April | 2716.99 | 26-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
May | 3124.08 | 04-MAY-14:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 |
June | 3096.38 | 26-JUN-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
July | 3690.02 | 31-JUL-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 0.00 |
August | 3565.64 | 18-AUG-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 0.00 |
September | 4180.65 | 29-SEP-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 0.00 |
October | 4570.14 | 16-OCT-12:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 0.00 |
November | 2026.92 | 02-NOV-13:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 |
December | 1964.91 | 05-DEC-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1846.81 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4570.14 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 19.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2971.90 | 20-JAN-09:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
February | 2797.29 | 21-FEB-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3877.99 | 23-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
April | 5567.13 | 30-APR-08:43 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
May | 4345.85 | 24-MAY-06:03 | 678.26 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
June | 5011.62 | 05-JUN-06:03 | 678.26 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 |
July | 8810.05 | 23-JUL-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.52 |
August | 8215.79 | 13-AUG-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 |
September | 5597.84 | 10-SEP-09:53 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 |
October | 9257.65 | 15-OCT-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 0.00 |
November | 2881.55 | 20-NOV-09:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 |
December | 2957.17 | 05-DEC-09:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2797.29 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9257.65 | 827.22 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 22.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11531.99 | 22-JAN-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.72 |
February | 11178.97 | 20-FEB-13:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.72 |
March | 6602.92 | 23-MAR-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.00 |
April | 6492.27 | 26-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1588.62 | 0.00 |
May | 4105.50 | 04-MAY-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.78 |
June | 3579.85 | 27-JUN-13:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 0.00 |
July | 8302.70 | 31-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3155.10 | 0.00 |
August | 8159.93 | 18-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3167.66 | 0.00 |
September | 11317.50 | 29-SEP-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6959.66 | 0.00 |
October | 12011.07 | 29-OCT-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 |
November | 11932.18 | 19-NOV-12:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
December | 11652.26 | 25-DEC-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3579.85 | 200.88 | 82.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12011.07 | 1306.65 | 496.34 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 6959.66 | 122.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3675.63 | 18-JAN-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
February | 4143.76 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
March | 5382.14 | 19-MAR-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.36 |
April | 8659.71 | 30-APR-16:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 |
May | 5894.46 | 28-MAY-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
June | 7215.70 | 25-JUN-15:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 |
July | 8301.57 | 04-JUL-17:42 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 |
August | 9009.66 | 06-AUG-17:33 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 |
September | 9024.15 | 10-SEP-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 |
October | 7958.25 | 15-OCT-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 |
November | 4088.46 | 07-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
December | 3967.01 | 19-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3675.63 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9024.15 | 805.38 | 314.21 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 51.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2743.07 | 18-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 |
February | 2457.83 | 03-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
March | 2844.49 | 23-MAR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
April | 3739.90 | 26-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 0.00 |
May | 4059.40 | 04-MAY-14:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
June | 3964.07 | 26-JUN-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
July | 4492.99 | 31-JUL-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 | 0.00 |
August | 4296.93 | 07-AUG-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 0.00 |
September | 5040.65 | 29-SEP-13:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 40.10 | 0.00 |
October | 5342.42 | 16-OCT-12:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 0.00 |
November | 2541.33 | 01-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
December | 2721.47 | 05-DEC-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2457.83 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5342.42 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 15.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4174.38 | 20-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 |
February | 4518.04 | 14-FEB-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
March | 5913.06 | 23-MAR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
April | 6693.16 | 30-APR-10:23 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 |
May | 7332.94 | 28-MAY-08:53 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 |
June | 7187.80 | 18-JUN-09:53 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.47 |
July | 11360.66 | 23-JUL-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 |
August | 10293.83 | 20-AUG-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.56 |
September | 7480.64 | 29-SEP-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 | 0.00 |
October | 11002.71 | 15-OCT-08:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 0.00 |
November | 4313.71 | 01-NOV-12:02 | 3221.71 | 1256.91 | 3634.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
December | 4722.00 | 01-DEC-13:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4174.38 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11360.66 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 55.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12907.47 | 22-JAN-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.21 |
February | 11526.07 | 19-FEB-14:03 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.99 |
March | 10119.03 | 19-MAR-13:13 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.58 |
April | 7126.88 | 26-APR-13:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 10.16 | 0.00 |
May | 5424.31 | 04-MAY-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
June | 4782.12 | 30-JUN-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
July | 6802.48 | 31-JUL-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 0.00 |
August | 7801.60 | 30-AUG-12:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 10493.61 | 29-SEP-12:04 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 | 0.00 |
October | 13552.14 | 29-OCT-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 |
November | 13801.75 | 19-NOV-12:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 |
December | 12962.98 | 03-DEC-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4782.12 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13801.75 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 | 156.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4664.52 | 18-JAN-15:00 | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
February | 5116.94 | 22-FEB-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 |
March | 6322.93 | 23-MAR-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
April | 11429.37 | 30-APR-15:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 |
May | 11105.61 | 21-MAY-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.75 |
June | 10516.10 | 25-JUN-15:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 |
July | 11860.37 | 30-JUL-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.39 |
August | 11519.44 | 27-AUG-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 |
September | 11432.16 | 10-SEP-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.74 |
October | 9725.57 | 15-OCT-15:02 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 0.00 |
November | 4795.48 | 07-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
December | 4727.41 | 18-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4664.52 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11860.37 | 827.17 | 314.21 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 | 86.75 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.102857E+12 | 96058.08 | 18-JAN-15:39 | 0.322484E+10 | 83717.04 | 03-JAN-07:10 |
February | 0.907424E+11 | 95311.15 | 01-FEB-11:00 | 0.136870E+10 | 38335.46 | 10-FEB-07:10 |
March | 0.103984E+12 | 104443.00 | 23-MAR-15:09 | 0.301177E+10 | 67268.28 | 30-MAR-06:10 |
April | 0.101992E+12 | 110852.08 | 26-APR-14:09 | 0.594808E+09 | 29595.68 | 01-APR-06:10 |
May | 0.107078E+12 | 99448.78 | 04-MAY-14:09 | 0.427697E+09 | 11507.10 | 15-MAY-06:10 |
June | 0.113918E+12 | 111732.30 | 29-JUN-15:00 | 0.132553E+09 | 10340.85 | 12-JUN-06:19 |
July | 0.124202E+12 | 132754.91 | 31-JUL-15:00 | 5441093.74 | 695.11 | 17-JUL-06:10 |
August | 0.135398E+12 | 127481.01 | 07-AUG-10:39 | 9064721.51 | 1478.21 | 28-AUG-06:00 |
September | 0.115115E+12 | 130599.91 | 29-SEP-15:00 | 45885855.22 | 11642.07 | 20-SEP-06:19 |
October | 0.120392E+12 | 138612.09 | 16-OCT-10:00 | 0.135355E+09 | 13136.63 | 12-OCT-06:19 |
November | 0.101741E+12 | 94191.16 | 28-NOV-13:00 | 0.496921E+09 | 29957.78 | 24-NOV-07:10 |
December | 0.102297E+12 | 101726.46 | 05-DEC-16:40 | 0.193878E+10 | 44316.08 | 15-DEC-07:10 |
Annual Sum or Average | 0.131972E+13 | 0.113918E+11 | ||||
Minimum of Months | 0.907424E+11 | 94191.16 | 5441093.74 | 695.11 | ||
Maximum of Months | 0.135398E+12 | 138612.09 | 0.322484E+10 | 83717.04 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.198500E+11 | 0.540114E+10 | 0.605851E+11 | 0.225717E+10 | 0.522406E+10 | 30338842.62 | 0.00 | 0.525465E+10 | 0.00 | 0.00 | 0.00 | 0.425496E+10 | 0.00 |
February | 0.177136E+11 | 0.445154E+10 | 0.548702E+11 | 0.204808E+10 | 0.467178E+10 | 19227833.81 | 0.00 | 0.309788E+10 | 0.00 | 0.00 | 0.00 | 0.387006E+10 | 0.00 |
March | 0.208914E+11 | 0.430939E+10 | 0.627783E+11 | 0.235491E+10 | 0.528813E+10 | 30446067.95 | 0.00 | 0.381208E+10 | 0.00 | 0.00 | 0.00 | 0.451948E+10 | 0.00 |
April | 0.184697E+11 | 0.359693E+10 | 0.586172E+11 | 0.219179E+10 | 0.669039E+10 | 15860596.30 | 0.00 | 0.840717E+10 | 0.00 | 0.00 | 0.00 | 0.400322E+10 | 0.00 |
May | 0.198357E+11 | 0.333646E+10 | 0.616817E+11 | 0.230571E+10 | 0.690812E+10 | 15501320.37 | 0.00 | 0.881067E+10 | 0.00 | 0.00 | 0.00 | 0.418431E+10 | 0.00 |
June | 0.197158E+11 | 0.308539E+10 | 0.604966E+11 | 0.226796E+10 | 0.828609E+10 | 13128431.30 | 0.00 | 0.159898E+11 | 0.00 | 0.00 | 0.00 | 0.406343E+10 | 0.00 |
July | 0.184451E+11 | 0.324182E+10 | 0.597911E+11 | 0.222873E+10 | 0.101392E+11 | 12285485.81 | 0.00 | 0.265477E+11 | 0.00 | 0.00 | 0.00 | 0.379565E+10 | 0.00 |
August | 0.206245E+11 | 0.354124E+10 | 0.627783E+11 | 0.235466E+10 | 0.115145E+11 | 12723311.57 | 0.00 | 0.304048E+11 | 0.00 | 0.00 | 0.00 | 0.416774E+10 | 0.00 |
September | 0.185796E+11 | 0.391239E+10 | 0.585950E+11 | 0.219063E+10 | 0.893040E+10 | 12220895.08 | 0.00 | 0.190853E+11 | 0.00 | 0.00 | 0.00 | 0.380974E+10 | 0.00 |
October | 0.194900E+11 | 0.467103E+10 | 0.605962E+11 | 0.225779E+10 | 0.851220E+10 | 13262077.46 | 0.00 | 0.208357E+11 | 0.00 | 0.00 | 0.00 | 0.401633E+10 | 0.00 |
November | 0.195875E+11 | 0.507096E+10 | 0.591197E+11 | 0.219986E+10 | 0.587705E+10 | 14962666.34 | 0.00 | 0.582813E+10 | 0.00 | 0.00 | 0.00 | 0.404293E+10 | 0.00 |
December | 0.192735E+11 | 0.555125E+10 | 0.597800E+11 | 0.222845E+10 | 0.528790E+10 | 23653221.83 | 0.00 | 0.605770E+10 | 0.00 | 0.00 | 0.00 | 0.409424E+10 | 0.00 |
Annual Sum or Average | 0.232476E+12 | 0.501696E+11 | 0.719689E+12 | 0.268858E+11 | 0.873299E+11 | 0.213611E+09 | 0.00 | 0.154131E+12 | 0.00 | 0.00 | 0.00 | 0.488221E+11 | 0.00 |
Minimum of Months | 0.177136E+11 | 0.308539E+10 | 0.548702E+11 | 0.204808E+10 | 0.467178E+10 | 12220895.08 | 0.00 | 0.309788E+10 | 0.00 | 0.00 | 0.00 | 0.379565E+10 | 0.00 |
Maximum of Months | 0.208914E+11 | 0.555125E+10 | 0.627783E+11 | 0.235491E+10 | 0.115145E+11 | 30446067.95 | 0.00 | 0.304048E+11 | 0.00 | 0.00 | 0.00 | 0.451948E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.322484E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.136870E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.301177E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.594808E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.427697E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132553E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5441093.74 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 9064721.51 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 45885855.22 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135355E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.496921E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.193878E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113918E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5441093.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.322484E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:49 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 05-JAN-17:10 | 11812.86 | 18-JAN-15:39 | 329.73 | 03-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 23770.48 | 27-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 07-FEB-17:10 | 10945.87 | 03-FEB-15:20 | 191.29 | 09-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 21113.95 | 16-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 06-MAR-12:09 | 13124.55 | 23-MAR-15:20 | 286.67 | 30-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 20454.34 | 21-APR-15:00 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 14-APR-16:10 | 14989.61 | 26-APR-14:30 | 155.91 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 20330.32 | 09-MAY-07:10 | 3328.83 | 01-MAY-18:30 | 41699.26 | 01-MAY-07:10 | 1410.29 | 12-MAY-16:10 | 13065.30 | 03-MAY-15:20 | 79.15 | 15-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 20205.54 | 09-JUN-07:10 | 3328.83 | 01-JUN-18:49 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-07:10 | 14288.00 | 26-JUN-15:39 | 69.81 | 13-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 20061.84 | 12-JUL-07:10 | 3328.83 | 01-JUL-18:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-07:19 | 19522.50 | 31-JUL-14:30 | 10.48 | 17-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 20333.44 | 21-AUG-07:10 | 5686.19 | 08-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:19 | 18733.53 | 14-AUG-14:00 | 14.28 | 28-AUG-06:00 | 0.00 | 01-AUG-00:10 |
September | 21815.85 | 21-SEP-07:30 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 06-SEP-07:19 | 17873.50 | 29-SEP-15:00 | 69.67 | 20-SEP-06:19 | 0.00 | 01-SEP-00:10 |
October | 21753.71 | 24-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 30-OCT-07:10 | 19814.48 | 16-OCT-15:00 | 84.06 | 12-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 06-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 13-NOV-08:09 | 10903.68 | 13-NOV-15:09 | 162.67 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 08-DEC-17:10 | 10772.08 | 19-DEC-16:10 | 221.03 | 22-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20061.84 | 3328.83 | 41699.26 | 1410.29 | 10772.08 | 10.48 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 19814.48 | 329.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 23654.25 | 18-JAN-13:09 | 0.00 | 0.00 | 0.00 | 5763.63 | 30-JAN-12:00 | 0.00 |
February | 21263.88 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 5763.72 | 03-FEB-12:00 | 0.00 |
March | 24661.06 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 | 5757.20 | 01-MAR-12:00 | 0.00 |
April | 30114.23 | 26-APR-14:09 | 0.00 | 0.00 | 0.00 | 5456.28 | 03-APR-11:20 | 0.00 |
May | 21583.19 | 03-MAY-12:00 | 0.00 | 0.00 | 0.00 | 5388.51 | 01-MAY-11:20 | 0.00 |
June | 33402.83 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 5358.79 | 01-JUN-11:00 | 0.00 |
July | 48238.05 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 5258.39 | 05-JUL-11:50 | 0.00 |
August | 45720.66 | 07-AUG-10:39 | 0.00 | 0.00 | 0.00 | 5237.84 | 30-AUG-11:30 | 0.00 |
September | 52654.99 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 5351.64 | 28-SEP-11:39 | 0.00 |
October | 58112.61 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 5381.97 | 31-OCT-11:30 | 0.00 |
November | 22521.55 | 28-NOV-13:00 | 0.00 | 0.00 | 0.00 | 5411.02 | 30-NOV-12:20 | 0.00 |
December | 23520.01 | 05-DEC-15:09 | 0.00 | 0.00 | 0.00 | 5752.55 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 21263.88 | 0.00 | 0.00 | 0.00 | 5237.84 | 0.00 | ||
Maximum of Months | 58112.61 | 0.00 | 0.00 | 0.00 | 5763.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 96058.08 | 18-JAN-15:39 | 19856.06 | 41659.26 | 0.00 | 1410.29 | 11812.86 | 6.85 | 0.00 | 18101.93 | 0.00 |
February | 95311.15 | 01-FEB-11:00 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 6849.40 | 6.85 | 0.00 | 21263.88 | 0.00 |
March | 104443.00 | 23-MAR-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13039.25 | 6.90 | 0.00 | 24413.80 | 0.00 |
April | 110852.08 | 26-APR-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14792.94 | 6.91 | 0.00 | 30114.23 | 0.00 |
May | 99448.78 | 04-MAY-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 12447.70 | 6.91 | 0.00 | 21349.20 | 0.00 |
June | 111732.30 | 29-JUN-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13586.32 | 6.89 | 0.00 | 31488.01 | 0.00 |
July | 132754.91 | 31-JUL-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 17864.41 | 6.89 | 0.00 | 48238.05 | 0.00 |
August | 127481.01 | 07-AUG-10:39 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 14967.57 | 6.87 | 0.00 | 45720.66 | 0.00 |
September | 130599.91 | 29-SEP-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 17873.50 | 6.85 | 0.00 | 46060.83 | 0.00 |
October | 138612.09 | 16-OCT-10:00 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 13267.69 | 6.85 | 0.00 | 58112.61 | 0.00 |
November | 94191.16 | 28-NOV-13:00 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 6616.60 | 6.85 | 0.00 | 22521.55 | 0.00 |
December | 101726.46 | 05-DEC-16:40 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 8070.08 | 6.85 | 0.00 | 15635.25 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 94191.16 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 6616.60 | 6.85 | 0.00 | 15635.25 | 0.00 | |
Maximum of Months | 138612.09 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 17873.50 | 6.91 | 0.00 | 58112.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 83717.04 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 38335.46 | 10-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 67268.28 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 29595.68 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 11507.10 | 15-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10340.85 | 12-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 695.11 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1478.21 | 28-AUG-06:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 11642.07 | 20-SEP-06:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 13136.63 | 12-OCT-06:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 29957.78 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 44316.08 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 695.11 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 83717.04 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.65 | 5.17 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.60 | 3.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.58 | 1.83 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.17 | 27.59 | 15.17 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.65 | 5.17 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.60 | 2.33 | 27.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.50 | 2.67 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.40 | 1.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 2.83 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.27 | 9.17 | 27.27 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 4.00 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.57 | 4.33 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 27.67 | 27.45 | 27.50 | 27.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.70 | 9.17 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.55 | 0.67 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.68 | 3.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.61 | 3.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 2.83 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.84 | 6.17 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.91 | 3.67 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 2.83 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.79 | 3.33 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.17 | 27.77 | 27.00 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.91 | 6.17 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 3.17 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.39 | 2.17 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 1.00 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.33 | 27.41 | 8.33 | 27.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.52 | 3.17 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 19.76 | 10.50 | 19.76 | 2.67 | 20.63 | 2.67 | 21.32 |
February | 4.33 | 19.98 | 4.33 | 19.98 | 1.50 | 21.08 | 1.50 | 21.89 |
March | 15.50 | 19.66 | 15.50 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
April | 1.00 | 20.39 | 1.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
May | 0.17 | 20.36 | 0.17 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 25.27 | 4.33 | 25.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 25.92 | 21.33 | 25.92 |
November | 0.33 | 20.35 | 0.33 | 20.35 | 4.00 | 26.53 | 4.00 | 27.01 |
December | 5.67 | 19.97 | 5.67 | 19.97 | 4.83 | 22.21 | 4.83 | 23.42 |
Annual Sum or Average | 37.50 | 19.80 | 37.50 | 19.80 | 38.67 | 22.04 | 38.67 | 23.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.50 | 20.39 | 15.50 | 20.39 | 21.33 | 26.53 | 21.33 | 27.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.40 | 1.33 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.42 | 1.33 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.17 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.54 | 4.33 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.57 | 2.67 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.50 | 2.33 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.65 | 1.83 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 18.33 | 27.52 | 15.00 | 27.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.65 | 4.33 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.56 | 1.17 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.50 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 2.17 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.68 | 4.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.62 | 3.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.58 | 1.67 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.65 | 1.50 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.67 | 27.61 | 16.67 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.68 | 4.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.62 | 3.50 | 27.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.54 | 3.83 | 27.54 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.50 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.37 | 2.33 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.60 | 13.50 | 26.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.70 | 5.00 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.67 | 5.67 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 35.33 | 27.21 | 35.33 | 27.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.70 | 13.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.50 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.60 | 3.33 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.58 | 3.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.63 | 2.83 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.76 | 5.50 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.79 | 3.50 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.71 | 3.00 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.69 | 3.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 30.50 | 27.69 | 25.33 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.79 | 5.50 | 27.82 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 96.17 | 24.11 | 189.50 | 24.63 | 12.00 | 24.64 |
February | 32.00 | 24.00 | 188.67 | 24.68 | 0.00 | 24.68 |
March | 13.33 | 24.00 | 248.17 | 24.63 | 0.00 | 24.63 |
April | 10.33 | 24.01 | 345.67 | 24.53 | 0.00 | 24.53 |
May | 0.00 | 0.00 | 366.67 | 24.58 | 0.00 | 24.58 |
June | 0.00 | 0.00 | 468.00 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 497.00 | 24.48 | 0.00 | 24.48 |
August | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 453.50 | 24.49 | 0.00 | 24.49 |
October | 5.00 | 24.00 | 331.50 | 24.70 | 0.00 | 24.70 |
November | 48.67 | 24.00 | 247.67 | 24.64 | 0.00 | 24.64 |
December | 79.17 | 24.01 | 137.17 | 24.63 | 0.00 | 24.63 |
Annual Sum or Average | 284.67 | 24.04 | 3987.50 | 24.55 | 12.00 | 24.55 |
Minimum of Months | 0.00 | 0.00 | 137.17 | 24.40 | 0.00 | 24.40 |
Maximum of Months | 96.17 | 24.11 | 514.00 | 24.70 | 12.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.50 | 23.44 | 32.83 | 23.52 | 0.83 | 23.52 |
February | 249.00 | 23.48 | 20.17 | 23.54 | 0.00 | 23.54 |
March | 249.50 | 23.51 | 59.33 | 23.65 | 0.00 | 23.65 |
April | 88.83 | 23.40 | 159.33 | 23.96 | 0.00 | 23.96 |
May | 74.50 | 23.57 | 179.17 | 24.12 | 0.00 | 24.12 |
June | 1.83 | 23.55 | 346.00 | 24.26 | 0.00 | 24.26 |
July | 0.00 | 0.00 | 477.83 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 509.50 | 24.20 | 0.00 | 24.20 |
September | 0.33 | 23.54 | 381.83 | 24.25 | 0.00 | 24.25 |
October | 72.67 | 23.79 | 220.50 | 24.24 | 0.00 | 24.24 |
November | 203.17 | 23.70 | 84.17 | 23.94 | 0.00 | 23.94 |
December | 340.83 | 23.61 | 25.17 | 23.66 | 0.00 | 23.66 |
Annual Sum or Average | 1571.17 | 23.55 | 2495.83 | 23.99 | 0.83 | 23.99 |
Minimum of Months | 0.00 | 0.00 | 20.17 | 23.52 | 0.00 | 23.52 |
Maximum of Months | 340.83 | 23.79 | 509.50 | 24.26 | 0.83 | 24.26 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.50 | 22.85 | 15.33 | 22.88 | 1.50 | 22.87 |
February | 348.33 | 22.97 | 9.00 | 22.99 | 0.00 | 22.99 |
March | 359.33 | 23.05 | 37.67 | 23.14 | 0.00 | 23.14 |
April | 181.50 | 23.15 | 114.67 | 23.51 | 0.00 | 23.51 |
May | 171.00 | 23.30 | 128.67 | 23.67 | 0.00 | 23.67 |
June | 51.50 | 23.34 | 283.33 | 24.05 | 0.00 | 24.05 |
July | 8.83 | 23.40 | 423.67 | 24.19 | 0.00 | 24.19 |
August | 9.50 | 23.42 | 449.17 | 24.14 | 0.00 | 24.14 |
September | 60.50 | 23.39 | 292.83 | 24.03 | 0.00 | 24.03 |
October | 169.50 | 23.51 | 173.67 | 23.87 | 0.00 | 23.87 |
November | 332.50 | 23.24 | 31.17 | 23.32 | 0.00 | 23.32 |
December | 427.83 | 23.02 | 7.17 | 23.04 | 0.00 | 23.04 |
Annual Sum or Average | 2518.83 | 23.10 | 1966.33 | 23.57 | 1.50 | 23.57 |
Minimum of Months | 8.83 | 22.85 | 7.17 | 22.88 | 0.00 | 22.87 |
Maximum of Months | 427.83 | 23.51 | 449.17 | 24.19 | 1.50 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 455.83 | 22.02 | 60.50 | 21.86 | 55.00 | 21.70 |
February | 403.33 | 22.17 | 21.33 | 22.09 | 19.50 | 22.01 |
March | 428.67 | 22.28 | 47.17 | 22.29 | 20.50 | 22.21 |
April | 279.67 | 22.68 | 89.00 | 22.98 | 3.00 | 22.96 |
May | 244.67 | 22.92 | 123.67 | 23.33 | 0.00 | 23.33 |
June | 120.83 | 23.20 | 260.33 | 23.83 | 0.00 | 23.83 |
July | 45.17 | 23.22 | 377.33 | 24.10 | 0.00 | 24.10 |
August | 82.83 | 23.23 | 355.67 | 23.95 | 0.00 | 23.95 |
September | 170.17 | 23.07 | 221.00 | 23.65 | 0.00 | 23.65 |
October | 249.33 | 23.00 | 137.50 | 23.43 | 0.00 | 23.43 |
November | 406.17 | 22.45 | 24.17 | 22.40 | 16.67 | 22.33 |
December | 482.33 | 22.17 | 44.50 | 22.01 | 44.50 | 21.88 |
Annual Sum or Average | 3369.00 | 22.48 | 1762.17 | 22.93 | 159.17 | 22.85 |
Minimum of Months | 45.17 | 22.02 | 21.33 | 21.86 | 0.00 | 21.70 |
Maximum of Months | 482.33 | 23.23 | 377.33 | 24.10 | 55.00 | 24.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 380.50 | 22.49 | 50.17 | 22.45 | 24.50 | 22.32 |
February | 328.83 | 22.39 | 47.33 | 22.50 | 11.00 | 22.43 |
March | 305.67 | 22.34 | 100.50 | 22.73 | 9.33 | 22.67 |
April | 184.83 | 22.83 | 228.33 | 23.67 | 3.50 | 23.68 |
May | 169.50 | 23.01 | 216.17 | 23.82 | 0.83 | 23.83 |
June | 102.50 | 23.50 | 317.00 | 24.10 | 8.17 | 24.15 |
July | 58.83 | 24.97 | 416.17 | 24.50 | 28.17 | 24.63 |
August | 59.33 | 24.49 | 415.67 | 24.31 | 20.83 | 24.42 |
September | 119.50 | 23.22 | 294.17 | 23.97 | 5.00 | 24.01 |
October | 149.00 | 23.11 | 209.17 | 23.89 | 2.50 | 23.91 |
November | 312.83 | 22.77 | 50.67 | 22.91 | 6.67 | 22.86 |
December | 428.67 | 22.72 | 26.33 | 22.60 | 22.00 | 22.49 |
Annual Sum or Average | 2600.00 | 22.80 | 2371.67 | 23.48 | 142.50 | 23.47 |
Minimum of Months | 58.83 | 22.34 | 26.33 | 22.45 | 0.83 | 22.32 |
Maximum of Months | 428.67 | 24.97 | 416.17 | 24.50 | 28.17 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 259.83 | 22.44 | 168.17 | 23.04 | 25.67 | 22.95 |
February | 262.00 | 22.34 | 126.50 | 22.95 | 15.00 | 22.93 |
March | 303.33 | 22.36 | 137.83 | 22.87 | 15.67 | 22.84 |
April | 215.50 | 22.70 | 192.67 | 23.47 | 3.00 | 23.46 |
May | 232.50 | 22.82 | 150.00 | 23.40 | 0.00 | 23.40 |
June | 144.83 | 23.13 | 247.50 | 23.77 | 0.00 | 23.77 |
July | 68.17 | 23.42 | 356.50 | 24.13 | 3.67 | 24.16 |
August | 76.17 | 23.58 | 379.17 | 24.11 | 8.50 | 24.16 |
September | 121.50 | 23.48 | 302.83 | 24.11 | 13.33 | 24.19 |
October | 164.67 | 23.77 | 276.50 | 24.26 | 29.67 | 24.44 |
November | 232.50 | 22.83 | 184.00 | 23.56 | 12.67 | 23.58 |
December | 256.83 | 22.61 | 172.67 | 23.26 | 21.83 | 23.19 |
Annual Sum or Average | 2337.83 | 22.79 | 2694.33 | 23.59 | 149.00 | 23.60 |
Minimum of Months | 68.17 | 22.34 | 126.50 | 22.87 | 0.00 | 22.84 |
Maximum of Months | 303.33 | 23.77 | 379.17 | 24.26 | 29.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 380.50 | 22.11 | 94.83 | 22.15 | 44.83 | 21.98 |
February | 329.67 | 22.18 | 81.00 | 22.44 | 18.00 | 22.35 |
March | 351.67 | 22.31 | 115.17 | 22.64 | 19.00 | 22.58 |
April | 222.83 | 22.93 | 189.00 | 23.59 | 16.00 | 23.67 |
May | 211.50 | 23.14 | 207.33 | 23.77 | 13.67 | 23.87 |
June | 113.83 | 23.60 | 323.83 | 24.08 | 14.67 | 24.18 |
July | 70.17 | 24.82 | 411.17 | 24.44 | 30.00 | 24.58 |
August | 70.00 | 24.20 | 415.17 | 24.24 | 19.17 | 24.34 |
September | 126.00 | 23.49 | 298.50 | 24.07 | 14.50 | 24.16 |
October | 203.00 | 23.28 | 221.17 | 23.89 | 14.33 | 23.99 |
November | 328.83 | 22.51 | 101.67 | 22.82 | 14.67 | 22.75 |
December | 386.67 | 22.25 | 73.83 | 22.23 | 41.17 | 22.07 |
Annual Sum or Average | 2794.67 | 22.68 | 2532.67 | 23.36 | 260.00 | 23.36 |
Minimum of Months | 70.00 | 22.11 | 73.83 | 22.15 | 13.67 | 21.98 |
Maximum of Months | 386.67 | 24.82 | 415.17 | 24.44 | 44.83 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.50 | 22.49 | 5.33 | 22.48 | 3.50 | 22.47 |
February | 438.33 | 22.56 | 0.00 | 22.56 | 0.00 | 22.56 |
March | 472.83 | 22.57 | 11.17 | 22.59 | 1.00 | 22.59 |
April | 335.50 | 22.96 | 30.50 | 23.05 | 0.00 | 23.05 |
May | 275.83 | 23.20 | 42.17 | 23.33 | 0.00 | 23.33 |
June | 120.83 | 23.34 | 198.67 | 23.82 | 0.00 | 23.82 |
July | 22.17 | 23.42 | 381.83 | 24.11 | 0.00 | 24.11 |
August | 45.50 | 23.32 | 355.83 | 24.00 | 0.00 | 24.00 |
September | 137.33 | 23.32 | 202.33 | 23.78 | 0.00 | 23.78 |
October | 230.33 | 23.39 | 130.67 | 23.67 | 0.00 | 23.67 |
November | 397.33 | 22.95 | 16.17 | 23.00 | 0.00 | 23.00 |
December | 487.00 | 22.63 | 0.83 | 22.63 | 0.83 | 22.62 |
Annual Sum or Average | 3423.50 | 22.83 | 1375.50 | 23.19 | 5.33 | 23.19 |
Minimum of Months | 22.17 | 22.49 | 0.00 | 22.48 | 0.00 | 22.47 |
Maximum of Months | 487.00 | 23.42 | 381.83 | 24.11 | 3.50 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.67 | 23.06 | 36.17 | 23.16 | 0.83 | 23.16 |
February | 329.00 | 22.86 | 19.83 | 22.96 | 0.00 | 22.96 |
March | 311.00 | 22.80 | 67.33 | 23.09 | 1.00 | 23.09 |
April | 168.33 | 23.18 | 203.00 | 23.86 | 0.50 | 23.86 |
May | 151.83 | 23.32 | 206.33 | 23.98 | 0.00 | 23.98 |
June | 70.00 | 23.37 | 310.50 | 24.13 | 1.00 | 24.13 |
July | 19.50 | 25.70 | 456.50 | 24.46 | 12.67 | 24.52 |
August | 13.33 | 26.11 | 471.83 | 24.34 | 10.17 | 24.39 |
September | 53.83 | 23.52 | 336.83 | 24.17 | 2.50 | 24.19 |
October | 93.17 | 23.52 | 238.83 | 24.20 | 0.67 | 24.20 |
November | 281.33 | 23.37 | 65.50 | 23.57 | 6.50 | 23.59 |
December | 394.83 | 23.22 | 7.83 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 2232.83 | 23.17 | 2420.50 | 23.79 | 35.83 | 23.81 |
Minimum of Months | 13.33 | 22.80 | 7.83 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 394.83 | 26.11 | 471.83 | 24.46 | 12.67 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 227.50 | 22.78 | 168.83 | 23.54 | 6.83 | 23.54 |
February | 277.17 | 22.52 | 101.17 | 23.11 | 1.33 | 23.13 |
March | 342.17 | 22.24 | 95.50 | 22.64 | 7.67 | 22.58 |
April | 258.50 | 22.75 | 143.33 | 23.35 | 0.00 | 23.35 |
May | 327.17 | 22.76 | 77.17 | 23.07 | 0.00 | 23.07 |
June | 234.33 | 22.90 | 140.83 | 23.36 | 0.50 | 23.36 |
July | 77.83 | 22.91 | 337.17 | 23.94 | 15.00 | 23.93 |
August | 62.17 | 22.82 | 413.00 | 23.98 | 22.50 | 23.96 |
September | 71.83 | 22.91 | 350.83 | 24.12 | 10.67 | 24.13 |
October | 108.17 | 23.81 | 311.50 | 24.44 | 32.83 | 24.54 |
November | 177.33 | 23.05 | 186.00 | 23.91 | 6.33 | 23.96 |
December | 223.83 | 22.97 | 164.83 | 23.76 | 3.67 | 23.79 |
Annual Sum or Average | 2388.00 | 22.77 | 2490.17 | 23.61 | 107.33 | 23.62 |
Minimum of Months | 62.17 | 22.24 | 77.17 | 22.64 | 0.00 | 22.58 |
Maximum of Months | 342.17 | 23.81 | 413.00 | 24.44 | 32.83 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 369.33 | 22.83 | 43.67 | 22.96 | 0.83 | 22.96 |
February | 335.50 | 22.82 | 45.00 | 23.01 | 0.00 | 23.01 |
March | 353.67 | 22.83 | 73.50 | 23.07 | 0.00 | 23.07 |
April | 161.50 | 23.19 | 186.83 | 23.85 | 1.67 | 23.86 |
May | 145.00 | 23.36 | 209.00 | 23.99 | 1.50 | 24.00 |
June | 47.67 | 23.64 | 343.67 | 24.20 | 4.50 | 24.23 |
July | 19.00 | 26.90 | 474.50 | 24.49 | 19.00 | 24.58 |
August | 16.33 | 26.38 | 489.67 | 24.34 | 13.83 | 24.40 |
September | 29.67 | 24.40 | 372.50 | 24.34 | 8.00 | 24.39 |
October | 125.67 | 23.74 | 255.67 | 24.22 | 6.17 | 24.26 |
November | 290.50 | 23.32 | 89.50 | 23.57 | 6.50 | 23.61 |
December | 379.67 | 22.99 | 26.17 | 23.09 | 0.00 | 23.09 |
Annual Sum or Average | 2273.50 | 23.12 | 2609.67 | 23.78 | 62.00 | 23.82 |
Minimum of Months | 16.33 | 22.82 | 26.17 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 379.67 | 26.90 | 489.67 | 24.49 | 19.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.50 | 22.55 | 19.67 | 22.53 | 9.33 | 22.49 |
February | 378.83 | 22.71 | 2.50 | 22.72 | 0.00 | 22.72 |
March | 406.33 | 22.77 | 31.33 | 22.85 | 1.00 | 22.84 |
April | 248.67 | 23.09 | 86.00 | 23.34 | 0.00 | 23.34 |
May | 196.83 | 23.30 | 126.50 | 23.64 | 0.00 | 23.64 |
June | 55.50 | 23.39 | 298.00 | 24.04 | 0.00 | 24.04 |
July | 10.50 | 23.44 | 436.50 | 24.19 | 0.00 | 24.19 |
August | 17.33 | 23.40 | 427.17 | 24.09 | 0.00 | 24.09 |
September | 90.00 | 23.33 | 258.33 | 23.92 | 0.00 | 23.92 |
October | 194.00 | 23.38 | 163.67 | 23.77 | 0.00 | 23.77 |
November | 368.67 | 22.98 | 18.17 | 23.04 | 0.00 | 23.04 |
December | 464.67 | 22.75 | 1.50 | 22.75 | 1.50 | 22.74 |
Annual Sum or Average | 2858.83 | 22.89 | 1869.33 | 23.38 | 11.83 | 23.38 |
Minimum of Months | 10.50 | 22.55 | 1.50 | 22.53 | 0.00 | 22.49 |
Maximum of Months | 464.67 | 23.44 | 436.50 | 24.19 | 9.33 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 306.67 | 22.85 | 35.83 | 22.94 | 5.83 | 22.89 |
February | 267.50 | 22.82 | 36.50 | 23.04 | 0.00 | 23.04 |
March | 248.50 | 22.76 | 90.33 | 23.19 | 1.50 | 23.18 |
April | 146.67 | 23.25 | 177.33 | 23.95 | 3.50 | 23.98 |
May | 128.50 | 23.43 | 187.17 | 24.12 | 3.00 | 24.15 |
June | 52.33 | 23.96 | 277.00 | 24.32 | 8.67 | 24.39 |
July | 31.67 | 26.04 | 381.33 | 24.62 | 23.83 | 24.75 |
August | 23.50 | 26.05 | 387.50 | 24.45 | 17.83 | 24.55 |
September | 63.67 | 23.73 | 269.67 | 24.24 | 7.17 | 24.29 |
October | 101.17 | 23.47 | 204.83 | 24.20 | 2.33 | 24.22 |
November | 248.50 | 23.16 | 63.50 | 23.44 | 0.00 | 23.44 |
December | 320.67 | 23.03 | 15.50 | 23.09 | 0.50 | 23.09 |
Annual Sum or Average | 1939.33 | 23.16 | 2126.50 | 23.83 | 74.17 | 23.87 |
Minimum of Months | 23.50 | 22.76 | 15.50 | 22.94 | 0.00 | 22.89 |
Maximum of Months | 320.67 | 26.05 | 387.50 | 24.62 | 23.83 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 217.50 | 23.00 | 172.50 | 23.67 | 8.67 | 23.72 |
February | 235.67 | 22.94 | 131.83 | 23.54 | 6.67 | 23.61 |
March | 257.17 | 22.81 | 147.67 | 23.35 | 4.00 | 23.37 |
April | 172.33 | 23.10 | 201.50 | 23.79 | 0.00 | 23.79 |
May | 190.00 | 23.22 | 166.33 | 23.72 | 0.00 | 23.72 |
June | 81.00 | 23.35 | 273.17 | 23.98 | 0.00 | 23.98 |
July | 15.17 | 23.65 | 415.67 | 24.23 | 1.00 | 24.24 |
August | 13.50 | 23.79 | 445.33 | 24.21 | 1.50 | 24.22 |
September | 59.00 | 23.96 | 357.00 | 24.30 | 10.50 | 24.37 |
October | 114.33 | 24.35 | 312.17 | 24.52 | 29.83 | 24.68 |
November | 191.50 | 23.46 | 202.50 | 24.06 | 10.17 | 24.14 |
December | 217.83 | 23.22 | 179.83 | 23.90 | 8.17 | 23.97 |
Annual Sum or Average | 1765.00 | 23.22 | 3005.50 | 23.95 | 80.50 | 24.00 |
Minimum of Months | 13.50 | 22.81 | 131.83 | 23.35 | 0.00 | 23.37 |
Maximum of Months | 257.17 | 24.35 | 445.33 | 24.52 | 29.83 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 347.83 | 22.66 | 69.00 | 22.85 | 7.17 | 22.81 |
February | 304.50 | 22.78 | 71.67 | 23.09 | 0.00 | 23.09 |
March | 308.33 | 22.79 | 108.00 | 23.16 | 2.83 | 23.17 |
April | 166.33 | 23.30 | 204.50 | 23.91 | 11.17 | 24.00 |
May | 149.67 | 23.52 | 229.17 | 24.06 | 11.50 | 24.15 |
June | 57.83 | 24.15 | 358.00 | 24.26 | 13.50 | 24.34 |
July | 31.33 | 26.54 | 460.17 | 24.52 | 28.00 | 24.64 |
August | 25.17 | 25.91 | 472.17 | 24.34 | 18.00 | 24.43 |
September | 57.50 | 24.09 | 353.17 | 24.29 | 12.17 | 24.37 |
October | 151.33 | 23.72 | 256.17 | 24.18 | 12.83 | 24.26 |
November | 287.17 | 23.07 | 102.67 | 23.43 | 0.33 | 23.43 |
December | 359.17 | 22.85 | 43.83 | 23.03 | 0.00 | 23.03 |
Annual Sum or Average | 2246.17 | 23.12 | 2728.50 | 23.78 | 117.50 | 23.85 |
Minimum of Months | 25.17 | 22.66 | 43.83 | 22.85 | 0.00 | 22.81 |
Maximum of Months | 359.17 | 26.54 | 472.17 | 24.52 | 28.00 | 24.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38575 | 36.34041 | 0.41289 | 8.89169 |
February | 454.00000 | 24.36381 | 38.23390 | 0.42265 | 8.97664 |
March | 514.00000 | 24.34165 | 41.00065 | 0.43826 | 9.25333 |
April | 485.00000 | 24.41550 | 43.69058 | 0.48855 | 10.23973 |
May | 508.00000 | 24.42529 | 42.93084 | -0.3706 | 8.36886 |
June | 496.00000 | 24.41246 | 47.92799 | -0.3242 | 7.68161 |
July | 497.00000 | 24.47526 | 51.50683 | -0.2671 | 7.00940 |
August | 514.00000 | 24.40343 | 52.80242 | -0.2743 | 7.03336 |
September | 485.00000 | 24.46224 | 48.88731 | -0.2956 | 7.39906 |
October | 502.00000 | 24.47993 | 40.33078 | 0.50116 | 10.69934 |
November | 489.00000 | 24.45215 | 36.36545 | 0.44568 | 9.66361 |
December | 497.00000 | 24.37105 | 31.84627 | 0.38541 | 8.45111 |
Annual Sum or Average | 5943.00000 | 24.41574 | 42.69772 | 0.12725 | 8.63320 |
Minimum of Months | 454.00000 | 24.34165 | 31.84627 | -0.3706 | 7.00940 |
Maximum of Months | 514.00000 | 24.47993 | 52.80242 | 0.50116 | 10.69934 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.72152 | 38.70827 | 0.24278 | 6.69131 |
February | 454.00000 | 23.75227 | 40.82088 | 0.26823 | 6.78390 |
March | 514.00000 | 23.80185 | 43.62337 | 0.30017 | 7.15696 |
April | 485.00000 | 23.96952 | 45.46522 | 0.37312 | 8.17675 |
May | 508.00000 | 24.05975 | 44.56437 | -0.5144 | 10.83296 |
June | 496.00000 | 24.15496 | 49.32080 | -0.4333 | 9.14389 |
July | 497.00000 | 24.22193 | 52.95130 | -0.3718 | 8.07902 |
August | 514.00000 | 24.19513 | 54.25880 | -0.3678 | 7.99183 |
September | 485.00000 | 24.18138 | 50.40576 | -0.4148 | 8.82156 |
October | 502.00000 | 24.17050 | 41.89665 | 0.41206 | 8.83536 |
November | 489.00000 | 23.97116 | 38.43835 | 0.31586 | 7.44701 |
December | 497.00000 | 23.77158 | 33.92911 | 0.22931 | 6.42159 |
Annual Sum or Average | 5943.00000 | 23.99913 | 44.57058 | 0.00050 | 8.04170 |
Minimum of Months | 454.00000 | 23.72152 | 33.92911 | -0.5144 | 6.42159 |
Maximum of Months | 514.00000 | 24.22193 | 54.25880 | 0.41206 | 10.83296 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.08902 | 40.22395 | 0.08457 | 6.27563 |
February | 454.00000 | 23.20171 | 42.41067 | 0.13131 | 6.12654 |
March | 514.00000 | 23.33046 | 44.93829 | 0.18206 | 6.46490 |
April | 485.00000 | 23.70099 | 46.17002 | 0.30744 | 7.49314 |
May | 508.00000 | 23.82378 | 45.08051 | -0.5970 | 13.16016 |
June | 496.00000 | 24.01861 | 49.43234 | -0.4785 | 10.11634 |
July | 497.00000 | 24.14493 | 52.94376 | -0.3940 | 8.44607 |
August | 514.00000 | 24.10060 | 54.39996 | -0.3976 | 8.48061 |
September | 485.00000 | 23.99934 | 50.78364 | -0.4809 | 10.18716 |
October | 502.00000 | 23.92973 | 42.50381 | 0.34845 | 8.00164 |
November | 489.00000 | 23.49308 | 39.88447 | 0.19360 | 6.49655 |
December | 497.00000 | 23.15506 | 35.59740 | 0.07558 | 5.91618 |
Annual Sum or Average | 5943.00000 | 23.66871 | 45.39693 | -0.0879 | 8.11434 |
Minimum of Months | 454.00000 | 23.08902 | 35.59740 | -0.5970 | 5.91618 |
Maximum of Months | 514.00000 | 24.14493 | 54.39996 | 0.34845 | 13.16016 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.20310 | 42.30455 | -0.1345 | 7.47566 |
February | 454.00000 | 22.37276 | 45.20512 | -0.0669 | 6.66260 |
March | 514.00000 | 22.55707 | 47.77840 | -0.0015 | 6.79194 |
April | 485.00000 | 23.23955 | 48.36721 | 0.19719 | 6.99874 |
May | 508.00000 | 23.51511 | 46.73747 | -0.6981 | 16.88984 |
June | 496.00000 | 23.86334 | 50.56342 | -0.5209 | 11.51635 |
July | 497.00000 | 24.06157 | 53.87333 | -0.4103 | 9.15730 |
August | 514.00000 | 23.92500 | 55.88577 | -0.4517 | 9.90836 |
September | 485.00000 | 23.70075 | 52.73778 | -0.5823 | 13.20977 |
October | 502.00000 | 23.55489 | 44.31964 | 0.25814 | 7.57979 |
November | 489.00000 | 22.70724 | 42.62238 | 0.00323 | 6.56776 |
December | 497.00000 | 22.22565 | 38.01602 | -0.1509 | 7.06047 |
Annual Sum or Average | 5943.00000 | 23.16608 | 47.39378 | -0.2151 | 9.17579 |
Minimum of Months | 454.00000 | 22.20310 | 38.01602 | -0.6981 | 6.56776 |
Maximum of Months | 514.00000 | 24.06157 | 55.88577 | 0.25814 | 16.88984 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86520 | 41.13025 | 0.03810 | 7.08012 |
February | 454.00000 | 22.85359 | 44.06673 | 0.06428 | 6.83807 |
March | 514.00000 | 23.06727 | 46.38946 | 0.14141 | 7.50286 |
April | 485.00000 | 23.71535 | 46.48546 | 0.34866 | 8.99792 |
May | 508.00000 | 23.85542 | 45.55949 | -0.5406 | 13.36035 |
June | 496.00000 | 24.02255 | 49.92446 | -0.4161 | 10.26960 |
July | 497.00000 | 24.29703 | 52.79459 | -0.2610 | 8.27795 |
August | 514.00000 | 24.15312 | 54.60712 | -0.2961 | 8.39764 |
September | 485.00000 | 23.92868 | 51.72957 | -0.4546 | 11.08578 |
October | 502.00000 | 23.90054 | 43.29614 | 0.36787 | 8.96092 |
November | 489.00000 | 23.24660 | 41.28542 | 0.14741 | 6.82608 |
December | 497.00000 | 22.89153 | 36.92610 | 0.02196 | 6.56156 |
Annual Sum or Average | 5943.00000 | 23.57136 | 46.20922 | -0.0716 | 8.69334 |
Minimum of Months | 454.00000 | 22.85359 | 36.92610 | -0.5406 | 6.56156 |
Maximum of Months | 514.00000 | 24.29703 | 54.60712 | 0.36787 | 13.36035 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32195 | 38.21319 | 0.19777 | 8.86597 |
February | 454.00000 | 23.16014 | 42.07361 | 0.16619 | 8.34359 |
March | 514.00000 | 23.09094 | 45.28846 | 0.15903 | 8.17038 |
April | 485.00000 | 23.56635 | 46.65315 | 0.30501 | 8.72091 |
May | 508.00000 | 23.54793 | 46.38374 | -0.6736 | 16.83702 |
June | 496.00000 | 23.81145 | 50.67941 | -0.5344 | 12.14601 |
July | 497.00000 | 24.07356 | 53.74236 | -0.3952 | 9.37964 |
August | 514.00000 | 24.03576 | 55.03756 | -0.3713 | 9.16361 |
September | 485.00000 | 24.00169 | 50.96891 | -0.4084 | 10.82217 |
October | 502.00000 | 24.05782 | 42.18915 | 0.44168 | 11.00372 |
November | 489.00000 | 23.62560 | 38.76951 | 0.28605 | 9.08189 |
December | 497.00000 | 23.46511 | 33.92684 | 0.21361 | 8.86928 |
Annual Sum or Average | 5943.00000 | 23.64890 | 45.36555 | -0.0539 | 10.13613 |
Minimum of Months | 454.00000 | 23.09094 | 33.92684 | -0.6736 | 8.17038 |
Maximum of Months | 514.00000 | 24.07356 | 55.03756 | 0.44168 | 16.83702 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.59286 | 41.52086 | -0.0223 | 7.73502 |
February | 454.00000 | 22.73189 | 44.36460 | 0.04059 | 7.40772 |
March | 514.00000 | 22.87123 | 46.88298 | 0.09860 | 7.69536 |
April | 485.00000 | 23.58639 | 47.32463 | 0.32278 | 9.31548 |
May | 508.00000 | 23.73274 | 46.16564 | -0.5710 | 15.16077 |
June | 496.00000 | 23.98492 | 50.24374 | -0.4143 | 10.57972 |
July | 497.00000 | 24.23096 | 53.29646 | -0.2791 | 8.62346 |
August | 514.00000 | 24.09897 | 55.14175 | -0.3147 | 8.77361 |
September | 485.00000 | 23.97164 | 51.78698 | -0.4277 | 11.10336 |
October | 502.00000 | 23.81652 | 43.74399 | 0.35242 | 9.39989 |
November | 489.00000 | 23.06328 | 41.64362 | 0.11290 | 7.46522 |
December | 497.00000 | 22.66999 | 37.17315 | -0.0264 | 7.38603 |
Annual Sum or Average | 5943.00000 | 23.45054 | 46.63545 | -0.0959 | 9.23598 |
Minimum of Months | 454.00000 | 22.59286 | 37.17315 | -0.5710 | 7.38603 |
Maximum of Months | 514.00000 | 24.23096 | 55.14175 | 0.35242 | 15.16077 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.61503 | 41.86916 | -0.0294 | 6.17204 |
February | 454.00000 | 22.60516 | 44.90932 | -0.0139 | 5.69037 |
March | 514.00000 | 22.67783 | 47.79223 | 0.02321 | 5.95086 |
April | 485.00000 | 23.27720 | 49.16553 | 0.19219 | 6.39439 |
May | 508.00000 | 23.58149 | 47.41194 | -0.6974 | 15.97461 |
June | 496.00000 | 23.86510 | 51.40153 | -0.5504 | 11.73994 |
July | 497.00000 | 24.06099 | 54.21457 | -0.4399 | 9.26522 |
August | 514.00000 | 23.94562 | 56.05141 | -0.4732 | 9.93061 |
September | 485.00000 | 23.81563 | 52.80324 | -0.5588 | 11.97801 |
October | 502.00000 | 23.76797 | 44.06328 | 0.30437 | 7.46457 |
November | 489.00000 | 23.15096 | 41.95708 | 0.10950 | 6.01413 |
December | 497.00000 | 22.65537 | 37.47010 | -0.0440 | 5.77263 |
Annual Sum or Average | 5943.00000 | 23.33953 | 47.45450 | -0.1837 | 8.55722 |
Minimum of Months | 454.00000 | 22.60516 | 37.47010 | -0.6974 | 5.69037 |
Maximum of Months | 514.00000 | 24.06099 | 56.05141 | 0.30437 | 15.97461 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.38239 | 40.27877 | 0.16794 | 6.51559 |
February | 454.00000 | 23.20758 | 43.46824 | 0.14502 | 6.29338 |
March | 514.00000 | 23.33903 | 46.05879 | 0.19874 | 7.00633 |
April | 485.00000 | 23.87910 | 46.63103 | 0.37242 | 8.67228 |
May | 508.00000 | 23.97816 | 45.85428 | -0.5190 | 11.89504 |
June | 496.00000 | 24.06949 | 50.43830 | -0.4310 | 9.94526 |
July | 497.00000 | 24.35825 | 52.76225 | -0.2703 | 7.63176 |
August | 514.00000 | 24.24520 | 54.29002 | -0.2924 | 7.67934 |
September | 485.00000 | 24.09750 | 51.47114 | -0.4122 | 9.41155 |
October | 502.00000 | 24.12573 | 42.82861 | 0.41932 | 9.22880 |
November | 489.00000 | 23.69604 | 40.34636 | 0.25894 | 6.98653 |
December | 497.00000 | 23.40407 | 36.02251 | 0.14844 | 6.09476 |
Annual Sum or Average | 5943.00000 | 23.81909 | 45.89939 | -0.0199 | 8.12620 |
Minimum of Months | 454.00000 | 23.20758 | 36.02251 | -0.5190 | 6.09476 |
Maximum of Months | 514.00000 | 24.35825 | 54.29002 | 0.41932 | 11.89504 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65014 | 37.10711 | 0.30035 | 8.68357 |
February | 454.00000 | 23.24392 | 41.17083 | 0.20224 | 7.64966 |
March | 514.00000 | 22.90495 | 44.87212 | 0.13093 | 7.42835 |
April | 485.00000 | 23.43993 | 47.18715 | 0.27315 | 7.74299 |
May | 508.00000 | 23.25143 | 47.22631 | -0.7702 | 19.11904 |
June | 496.00000 | 23.48782 | 52.45902 | -0.6525 | 15.05310 |
July | 497.00000 | 23.92300 | 55.67692 | -0.4581 | 10.21817 |
August | 514.00000 | 23.97451 | 56.70515 | -0.4003 | 9.27015 |
September | 485.00000 | 24.07143 | 51.44320 | -0.3830 | 9.67376 |
October | 502.00000 | 24.25545 | 41.86279 | 0.49674 | 11.53044 |
November | 489.00000 | 23.88314 | 37.85635 | 0.37031 | 9.33095 |
December | 497.00000 | 23.79245 | 32.74028 | 0.31421 | 8.78897 |
Annual Sum or Average | 5943.00000 | 23.65733 | 45.57406 | -0.0513 | 10.40531 |
Minimum of Months | 454.00000 | 22.90495 | 32.74028 | -0.7702 | 7.42835 |
Maximum of Months | 514.00000 | 24.25545 | 56.70515 | 0.49674 | 19.11904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16879 | 40.77761 | 0.11857 | 6.51563 |
February | 454.00000 | 23.17148 | 43.57894 | 0.13862 | 6.42316 |
March | 514.00000 | 23.22706 | 46.25892 | 0.17338 | 6.82689 |
April | 485.00000 | 23.88350 | 46.86420 | 0.37363 | 8.90372 |
May | 508.00000 | 23.99145 | 45.87182 | -0.5085 | 11.90698 |
June | 496.00000 | 24.12225 | 50.25990 | -0.3999 | 9.31272 |
July | 497.00000 | 24.36611 | 52.85971 | -0.2626 | 7.46042 |
August | 514.00000 | 24.24469 | 54.47479 | -0.2922 | 7.59351 |
September | 485.00000 | 24.21690 | 51.02209 | -0.3598 | 8.63728 |
October | 502.00000 | 24.13706 | 42.97760 | 0.42372 | 9.53570 |
November | 489.00000 | 23.64956 | 40.50213 | 0.25208 | 7.19038 |
December | 497.00000 | 23.26642 | 36.33543 | 0.11748 | 6.20979 |
Annual Sum or Average | 5943.00000 | 23.79049 | 46.01199 | -0.0210 | 8.05509 |
Minimum of Months | 454.00000 | 23.16879 | 36.33543 | -0.5085 | 6.20979 |
Maximum of Months | 514.00000 | 24.36611 | 54.47479 | 0.42372 | 11.90698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76140 | 41.06951 | 0.00896 | 6.34357 |
February | 454.00000 | 22.92310 | 43.78171 | 0.06952 | 5.94634 |
March | 514.00000 | 23.02250 | 46.58916 | 0.11539 | 6.33312 |
April | 485.00000 | 23.53545 | 47.61013 | 0.26857 | 7.09084 |
May | 508.00000 | 23.77128 | 46.13397 | -0.6105 | 13.53760 |
June | 496.00000 | 24.01205 | 50.33074 | -0.4723 | 10.00642 |
July | 497.00000 | 24.15523 | 53.73638 | -0.3832 | 8.32048 |
August | 514.00000 | 24.04394 | 55.54642 | -0.4150 | 8.82558 |
September | 485.00000 | 23.91135 | 52.15779 | -0.5092 | 10.87106 |
October | 502.00000 | 23.83278 | 43.67729 | 0.32811 | 7.85027 |
November | 489.00000 | 23.23300 | 41.28697 | 0.13421 | 6.23292 |
December | 497.00000 | 22.83052 | 36.67252 | 0.00071 | 5.87671 |
Annual Sum or Average | 5943.00000 | 23.50662 | 46.58044 | -0.1243 | 8.12253 |
Minimum of Months | 454.00000 | 22.76140 | 36.67252 | -0.6105 | 5.87671 |
Maximum of Months | 514.00000 | 24.15523 | 55.54642 | 0.32811 | 13.53760 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.22161 | 40.19746 | 0.13326 | 6.68225 |
February | 385.00000 | 23.24250 | 42.95324 | 0.16178 | 6.62784 |
March | 433.00000 | 23.36620 | 45.22525 | 0.21507 | 7.32794 |
April | 410.00000 | 23.92706 | 46.04141 | 0.39094 | 9.20349 |
May | 430.00000 | 24.05773 | 45.13891 | -0.4819 | 11.54685 |
June | 418.00000 | 24.17382 | 49.67400 | -0.3840 | 9.41637 |
July | 422.00000 | 24.43251 | 52.49914 | -0.2422 | 7.84819 |
August | 433.00000 | 24.28526 | 54.30853 | -0.2773 | 7.92575 |
September | 410.00000 | 24.11640 | 51.24113 | -0.4060 | 9.67661 |
October | 427.00000 | 24.12355 | 43.05236 | 0.41797 | 9.47882 |
November | 417.00000 | 23.58692 | 40.41760 | 0.23527 | 7.00336 |
December | 422.00000 | 23.29130 | 35.69419 | 0.12460 | 6.21850 |
Annual Sum or Average | 5034.00000 | 23.82207 | 45.55301 | -0.0109 | 8.25505 |
Minimum of Months | 385.00000 | 23.22161 | 35.69419 | -0.4819 | 6.21850 |
Maximum of Months | 433.00000 | 24.43251 | 54.30853 | 0.41797 | 11.54685 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.72372 | 37.21538 | 0.30636 | 8.84816 |
February | 454.00000 | 23.58633 | 40.83681 | 0.27583 | 8.29613 |
March | 514.00000 | 23.47933 | 44.15887 | 0.25853 | 7.99306 |
April | 485.00000 | 23.83119 | 45.96874 | 0.36846 | 8.82533 |
May | 508.00000 | 23.79970 | 45.79336 | -0.5877 | 13.41349 |
June | 496.00000 | 23.96651 | 50.42913 | -0.4843 | 10.44753 |
July | 497.00000 | 24.17299 | 53.57736 | -0.3675 | 8.37983 |
August | 514.00000 | 24.14953 | 54.70426 | -0.3384 | 8.07424 |
September | 485.00000 | 24.18309 | 50.49939 | -0.3465 | 8.90943 |
October | 502.00000 | 24.27299 | 41.66442 | 0.49668 | 11.46209 |
November | 489.00000 | 23.98275 | 37.80057 | 0.38106 | 9.50651 |
December | 497.00000 | 23.87255 | 32.86656 | 0.32253 | 8.99791 |
Annual Sum or Average | 5943.00000 | 23.91966 | 44.66822 | 0.02073 | 9.44028 |
Minimum of Months | 454.00000 | 23.47933 | 32.86656 | -0.5877 | 7.99306 |
Maximum of Months | 514.00000 | 24.27299 | 54.70426 | 0.49668 | 13.41349 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11239 | 40.35584 | 0.11214 | 6.92624 |
February | 454.00000 | 23.24461 | 43.00090 | 0.16835 | 6.96281 |
March | 514.00000 | 23.30922 | 45.67375 | 0.20854 | 7.40497 |
April | 485.00000 | 23.86799 | 46.53042 | 0.38954 | 9.45681 |
May | 508.00000 | 23.98344 | 45.50512 | -0.4867 | 11.92564 |
June | 496.00000 | 24.13453 | 49.94047 | -0.3672 | 9.04890 |
July | 497.00000 | 24.33444 | 53.07728 | -0.2516 | 7.72153 |
August | 514.00000 | 24.21174 | 54.77064 | -0.2821 | 7.78545 |
September | 485.00000 | 24.16169 | 51.20347 | -0.3628 | 9.11576 |
October | 502.00000 | 24.07397 | 43.11649 | 0.41700 | 9.72586 |
November | 489.00000 | 23.54464 | 40.41704 | 0.23387 | 7.37076 |
December | 497.00000 | 23.22069 | 35.90091 | 0.11316 | 6.60730 |
Annual Sum or Average | 5943.00000 | 23.76970 | 45.82333 | -0.0112 | 8.34734 |
Minimum of Months | 454.00000 | 23.11239 | 35.90091 | -0.4867 | 6.60730 |
Maximum of Months | 514.00000 | 24.33444 | 54.77064 | 0.41700 | 11.92564 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.213585E+10 | 0.00 | 98.29 | 113882.71 | 03-JAN-07:02 | 0.00 | 35.90 | 39.18 | 0.01 | 0.00 | 0.00 | 0.68 | 03-JAN-07:02 |
February | 0.873639E+09 | 0.00 | 70.37 | 52997.37 | 10-FEB-07:03 | 0.00 | 36.15 | 38.68 | 0.00 | 0.00 | 0.00 | 0.32 | 10-FEB-07:03 |
March | 0.195936E+10 | 0.00 | 109.79 | 102501.08 | 30-MAR-06:02 | 0.00 | 37.73 | 41.14 | 0.01 | 0.00 | 0.00 | 0.61 | 30-MAR-06:02 |
April | 0.359053E+09 | 0.00 | 44.61 | 45920.44 | 01-APR-06:03 | 0.00 | 39.52 | 40.79 | 0.00 | 0.00 | 0.00 | 0.27 | 01-APR-06:03 |
May | 0.257103E+09 | 0.00 | 28.48 | 7496.36 | 08-MAY-06:06 | 0.00 | 39.72 | 40.53 | 0.00 | 0.00 | 0.00 | 0.04 | 08-MAY-06:06 |
June | 79683399.92 | 0.00 | 97.54 | 6950.41 | 12-JUN-06:08 | 0.00 | 36.16 | 39.58 | 0.00 | 0.00 | 0.00 | 0.04 | 12-JUN-06:08 |
July | 3316484.13 | 0.00 | 177.68 | 1965.20 | 17-JUL-06:10 | 0.00 | 33.40 | 39.75 | 0.00 | 0.00 | 0.00 | 0.01 | 17-JUL-06:10 |
August | 5466380.42 | 0.00 | 221.94 | 1646.69 | 28-AUG-06:10 | 0.00 | 33.58 | 41.47 | 0.00 | 0.00 | 0.00 | 0.01 | 28-AUG-06:10 |
September | 27587550.61 | 0.00 | 100.81 | 7960.57 | 20-SEP-06:05 | 0.00 | 35.58 | 38.98 | 0.00 | 0.00 | 0.00 | 0.05 | 20-SEP-06:05 |
October | 81775392.27 | 0.00 | 67.96 | 12852.94 | 30-OCT-06:01 | 0.00 | 39.45 | 41.27 | 0.00 | 0.00 | 0.00 | 0.08 | 30-OCT-06:01 |
November | 0.307286E+09 | 0.00 | 31.91 | 39446.94 | 24-NOV-07:02 | 0.00 | 34.85 | 35.92 | 0.00 | 0.00 | 0.00 | 0.23 | 24-NOV-07:02 |
December | 0.126005E+10 | 0.00 | 78.72 | 61745.96 | 15-DEC-07:03 | 0.00 | 34.67 | 37.24 | 0.01 | 0.00 | 0.00 | 0.37 | 15-DEC-07:03 |
Annual Sum or Average | 0.735018E+10 | 0.00 | 1128.10 | 0.00 | 36.39 | 39.56 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3316484.13 | 0.00 | 28.48 | 1646.69 | 0.00 | 33.40 | 35.92 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.213585E+10 | 0.00 | 221.94 | 113882.71 | 0.00 | 39.72 | 41.47 | 0.01 | 0.00 | 0.00 | 0.68 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.907798E+10 | 0.208386E+10 | 216.81 | 0.840486E+10 | 0.673121E+09 | 0.00 | 1.00 | 13-JAN-11:30 | 0.00 | 01-JAN-00:10 | 38684.32 | 18-JAN-13:05 | 38684.32 | 18-JAN-13:05 | 7105.88 | 17-JAN-07:03 | 8510.55 | 18-JAN-13:05 | 0.00 |
February | 0.507054E+10 | 0.119547E+10 | 162.31 | 0.441147E+10 | 0.659064E+09 | 0.00 | 1.00 | 01-FEB-09:50 | 0.00 | 01-FEB-00:10 | 36788.80 | 01-FEB-12:00 | 36788.80 | 01-FEB-12:00 | 5032.62 | 11-FEB-14:00 | 8141.71 | 01-FEB-12:00 | 0.00 |
March | 0.602393E+10 | 0.139867E+10 | 164.74 | 0.477600E+10 | 0.124793E+10 | 0.00 | 1.00 | 10-MAR-11:40 | 0.00 | 01-MAR-00:10 | 40542.85 | 23-MAR-15:00 | 32668.79 | 23-MAR-14:10 | 11432.71 | 23-MAR-16:00 | 8554.95 | 23-MAR-15:00 | 0.00 |
April | 0.129201E+11 | 0.293444E+10 | 253.87 | 0.108142E+11 | 0.210595E+10 | 0.00 | 1.00 | 04-APR-11:00 | 0.00 | 01-APR-00:10 | 45709.54 | 26-APR-14:10 | 43494.60 | 26-APR-14:10 | 12705.41 | 27-APR-06:03 | 10008.82 | 26-APR-14:10 | 0.00 |
May | 0.138023E+11 | 0.316875E+10 | 307.76 | 0.117396E+11 | 0.206272E+10 | 0.00 | 1.00 | 02-MAY-10:50 | 0.00 | 01-MAY-00:10 | 35382.19 | 04-MAY-14:05 | 34355.90 | 03-MAY-13:00 | 13389.44 | 05-MAY-06:03 | 7430.68 | 04-MAY-14:05 | 0.00 |
June | 0.257263E+11 | 0.569707E+10 | 388.71 | 0.193792E+11 | 0.634701E+10 | 0.00 | 1.00 | 05-JUN-10:05 | 0.00 | 01-JUN-00:10 | 55277.05 | 28-JUN-11:00 | 38234.83 | 26-JUN-10:40 | 25064.98 | 30-JUN-06:03 | 11709.68 | 28-JUN-11:00 | 0.00 |
July | 0.438886E+11 | 0.954636E+10 | 426.76 | 0.292030E+11 | 0.146856E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 81125.16 | 31-JUL-16:00 | 52070.05 | 31-JUL-14:10 | 35616.44 | 31-JUL-16:00 | 17106.67 | 31-JUL-16:00 | 0.00 |
August | 0.506293E+11 | 0.109665E+11 | 442.81 | 0.327449E+11 | 0.178844E+11 | 0.00 | 1.00 | 01-AUG-05:12 | 0.00 | 01-AUG-00:10 | 79256.09 | 07-AUG-10:40 | 51471.66 | 14-AUG-11:00 | 42283.97 | 07-AUG-06:03 | 16862.14 | 07-AUG-10:40 | 0.00 |
September | 0.312910E+11 | 0.700650E+10 | 377.02 | 0.225048E+11 | 0.878620E+10 | 0.00 | 1.00 | 01-SEP-10:05 | 0.00 | 01-SEP-00:10 | 59377.90 | 29-SEP-14:50 | 59377.90 | 29-SEP-14:50 | 33899.86 | 22-SEP-10:20 | 17065.54 | 29-SEP-13:00 | 0.00 |
October | 0.345931E+11 | 0.781257E+10 | 385.58 | 0.275062E+11 | 0.708686E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 73356.23 | 04-OCT-11:00 | 66262.23 | 16-OCT-11:00 | 38205.48 | 05-OCT-06:03 | 20095.77 | 16-OCT-11:00 | 0.00 |
November | 0.973521E+10 | 0.223464E+10 | 233.40 | 0.868681E+10 | 0.104840E+10 | 0.00 | 1.00 | 08-NOV-10:20 | 0.00 | 01-NOV-00:10 | 37507.71 | 28-NOV-14:00 | 37507.71 | 28-NOV-14:00 | 12950.19 | 10-NOV-07:03 | 8099.16 | 28-NOV-14:00 | 0.00 |
December | 0.106875E+11 | 0.240210E+10 | 216.19 | 0.104010E+11 | 0.286537E+09 | 0.00 | 1.00 | 04-DEC-09:30 | 0.00 | 01-DEC-00:10 | 39898.01 | 05-DEC-15:10 | 39898.01 | 05-DEC-15:10 | 5845.29 | 07-DEC-13:05 | 8545.85 | 05-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.253446E+12 | 0.564469E+11 | 3575.97 | 0.190572E+12 | 0.628738E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.507054E+10 | 0.119547E+10 | 162.31 | 0.441147E+10 | 0.286537E+09 | 0.00 | 1.00 | 0.00 | 35382.19 | 32668.79 | 5032.62 | 7430.68 | 0.00 | ||||||
Maximum of Months | 0.506293E+11 | 0.109665E+11 | 442.81 | 0.327449E+11 | 0.178844E+11 | 0.00 | 1.00 | 0.00 | 81125.16 | 66262.23 | 42283.97 | 20095.77 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.708186E+10 | 0.164551E+10 | 202.44 | 0.639559E+10 | 0.686267E+09 | 0.00 | 1.00 | 13-JAN-13:05 | 0.00 | 01-JAN-00:10 | 34815.17 | 18-JAN-13:05 | 34815.17 | 18-JAN-13:05 | 7483.92 | 20-JAN-13:30 | 7659.86 | 18-JAN-13:05 | 0.00 |
February | 0.411690E+10 | 0.979743E+09 | 157.25 | 0.351656E+10 | 0.600341E+09 | 0.00 | 1.00 | 01-FEB-11:05 | 0.00 | 01-FEB-00:10 | 29576.22 | 01-FEB-12:00 | 29576.22 | 01-FEB-12:00 | 7137.69 | 01-FEB-14:00 | 6547.44 | 01-FEB-12:00 | 0.00 |
March | 0.522792E+10 | 0.121297E+10 | 152.64 | 0.408858E+10 | 0.113934E+10 | 0.00 | 1.00 | 10-MAR-13:05 | 0.00 | 01-MAR-00:10 | 38988.18 | 23-MAR-14:05 | 31213.89 | 23-MAR-14:05 | 10048.01 | 23-MAR-15:50 | 8221.68 | 23-MAR-14:05 | 0.00 |
April | 0.116608E+11 | 0.266515E+10 | 262.50 | 0.978612E+10 | 0.187471E+10 | 0.00 | 1.00 | 04-APR-12:05 | 0.00 | 01-APR-00:10 | 44164.79 | 26-APR-14:05 | 41741.22 | 26-APR-14:05 | 6360.38 | 13-APR-16:00 | 9670.16 | 26-APR-14:05 | 0.00 |
May | 0.119286E+11 | 0.275853E+10 | 310.76 | 0.101080E+11 | 0.182061E+10 | 0.00 | 1.00 | 02-MAY-12:30 | 0.00 | 01-MAY-00:10 | 32884.69 | 04-MAY-14:05 | 32879.78 | 04-MAY-12:05 | 9807.50 | 05-MAY-15:00 | 6910.62 | 04-MAY-12:05 | 0.00 |
June | 0.224074E+11 | 0.498499E+10 | 393.26 | 0.169729E+11 | 0.543446E+10 | 0.00 | 1.00 | 05-JUN-14:05 | 0.00 | 01-JUN-00:10 | 49740.14 | 29-JUN-12:05 | 34295.49 | 26-JUN-10:05 | 18053.45 | 28-JUN-12:05 | 10537.68 | 29-JUN-12:05 | 0.00 |
July | 0.376416E+11 | 0.822664E+10 | 433.94 | 0.252711E+11 | 0.123705E+11 | 0.00 | 1.00 | 02-JUL-08:43 | 0.00 | 01-JUL-00:10 | 71206.02 | 31-JUL-16:00 | 48141.59 | 31-JUL-14:05 | 31235.46 | 31-JUL-16:00 | 15018.72 | 31-JUL-16:00 | 0.00 |
August | 0.433594E+11 | 0.942590E+10 | 448.32 | 0.283769E+11 | 0.149825E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.00 | 01-AUG-00:10 | 67379.79 | 07-AUG-10:40 | 46570.29 | 17-AUG-14:05 | 28966.78 | 07-AUG-10:05 | 14340.73 | 07-AUG-10:40 | 0.00 |
September | 0.264619E+11 | 0.596850E+10 | 379.51 | 0.192074E+11 | 0.725446E+10 | 0.00 | 1.00 | 01-SEP-10:30 | 0.00 | 01-SEP-00:10 | 58640.99 | 29-SEP-12:02 | 58640.99 | 29-SEP-12:02 | 28705.41 | 22-SEP-10:05 | 17245.22 | 29-SEP-12:02 | 0.00 |
October | 0.284701E+11 | 0.649220E+10 | 384.83 | 0.227494E+11 | 0.572067E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 64333.60 | 03-OCT-13:40 | 63120.99 | 16-OCT-12:02 | 33622.11 | 02-OCT-06:03 | 18375.74 | 16-OCT-12:02 | 0.00 |
November | 0.806360E+10 | 0.186941E+10 | 231.14 | 0.709374E+10 | 0.969861E+09 | 0.00 | 1.00 | 08-NOV-11:05 | 0.00 | 01-NOV-00:10 | 32914.91 | 28-NOV-14:00 | 32914.91 | 28-NOV-14:00 | 8552.61 | 20-NOV-13:05 | 7108.28 | 28-NOV-14:00 | 0.00 |
December | 0.831444E+10 | 0.189725E+10 | 207.64 | 0.801526E+10 | 0.299178E+09 | 0.00 | 1.00 | 04-DEC-13:05 | 0.00 | 01-DEC-00:10 | 35908.96 | 05-DEC-15:05 | 35908.96 | 05-DEC-15:05 | 6571.82 | 07-DEC-13:05 | 7691.96 | 05-DEC-15:05 | 0.00 |
Annual Sum or Average | 0.214734E+12 | 0.481268E+11 | 3564.24 | 0.161582E+12 | 0.531528E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.411690E+10 | 0.979743E+09 | 152.64 | 0.351656E+10 | 0.299178E+09 | 0.00 | 1.00 | 0.00 | 29576.22 | 29576.22 | 6360.38 | 6547.44 | 0.00 | ||||||
Maximum of Months | 0.433594E+11 | 0.942590E+10 | 448.32 | 0.283769E+11 | 0.149825E+11 | 0.00 | 1.00 | 0.00 | 71206.02 | 63120.99 | 33622.11 | 18375.74 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.643515E+10 | 0.152528E+10 | 199.28 | 0.565146E+10 | 0.783690E+09 | 0.00 | 1.00 | 13-JAN-13:40 | 0.00 | 01-JAN-00:10 | 36402.34 | 18-JAN-13:40 | 36402.34 | 18-JAN-13:40 | 7266.58 | 20-JAN-13:10 | 7874.45 | 18-JAN-13:40 | 0.00 |
February | 0.380421E+10 | 0.922659E+09 | 153.86 | 0.315536E+10 | 0.648859E+09 | 0.00 | 1.00 | 01-FEB-11:50 | 0.00 | 01-FEB-00:10 | 29692.85 | 01-FEB-12:00 | 29692.85 | 01-FEB-12:00 | 7141.95 | 01-FEB-14:00 | 6574.72 | 01-FEB-12:00 | 0.00 |
March | 0.512209E+10 | 0.120044E+10 | 149.53 | 0.390606E+10 | 0.121603E+10 | 0.00 | 1.00 | 22-MAR-12:20 | 0.00 | 01-MAR-00:10 | 39080.44 | 23-MAR-15:00 | 31576.08 | 23-MAR-14:00 | 10786.49 | 23-MAR-15:50 | 8248.01 | 23-MAR-15:00 | 0.00 |
April | 0.121929E+11 | 0.280758E+10 | 262.35 | 0.990945E+10 | 0.228342E+10 | 0.00 | 1.00 | 04-APR-12:20 | 0.00 | 01-APR-00:10 | 50211.10 | 26-APR-14:00 | 48027.98 | 26-APR-14:00 | 7042.17 | 13-APR-16:00 | 11128.35 | 26-APR-13:50 | 0.00 |
May | 0.123880E+11 | 0.288339E+10 | 312.53 | 0.101875E+11 | 0.220059E+10 | 0.00 | 1.00 | 02-MAY-12:50 | 0.00 | 01-MAY-00:10 | 35861.13 | 03-MAY-14:00 | 35542.53 | 03-MAY-13:00 | 9511.85 | 05-MAY-15:00 | 7534.36 | 03-MAY-14:00 | 0.00 |
June | 0.237543E+11 | 0.530769E+10 | 395.50 | 0.175472E+11 | 0.620706E+10 | 0.00 | 1.00 | 13-JUN-13:50 | 0.00 | 01-JUN-00:10 | 54686.75 | 29-JUN-13:00 | 35743.48 | 27-JUN-13:00 | 19940.46 | 29-JUN-13:00 | 11586.70 | 29-JUN-13:00 | 0.00 |
July | 0.399854E+11 | 0.877470E+10 | 435.78 | 0.264984E+11 | 0.134870E+11 | 0.00 | 1.00 | 03-JUL-09:30 | 0.00 | 01-JUL-00:10 | 82712.48 | 31-JUL-15:30 | 53847.33 | 31-JUL-14:00 | 34175.71 | 31-JUL-15:30 | 17676.69 | 31-JUL-15:30 | 0.00 |
August | 0.458979E+11 | 0.100124E+11 | 448.81 | 0.295371E+11 | 0.163608E+11 | 0.00 | 1.00 | 01-AUG-10:00 | 0.00 | 01-AUG-00:10 | 81297.99 | 14-AUG-13:20 | 52034.50 | 17-AUG-14:00 | 32990.46 | 14-AUG-14:00 | 17532.18 | 14-AUG-13:20 | 0.00 |
September | 0.268353E+11 | 0.611028E+10 | 379.72 | 0.192538E+11 | 0.758150E+10 | 0.00 | 1.00 | 01-SEP-11:00 | 0.00 | 01-SEP-00:10 | 65252.41 | 29-SEP-13:40 | 65252.41 | 29-SEP-13:40 | 26078.03 | 22-SEP-11:40 | 19036.46 | 29-SEP-13:00 | 0.00 |
October | 0.282935E+11 | 0.653089E+10 | 383.81 | 0.223665E+11 | 0.592694E+10 | 0.00 | 1.00 | 01-OCT-11:33 | 0.00 | 01-OCT-00:10 | 71880.60 | 03-OCT-13:10 | 67317.67 | 16-OCT-13:05 | 28815.89 | 03-OCT-13:30 | 19723.33 | 16-OCT-11:00 | 0.00 |
November | 0.726060E+10 | 0.172408E+10 | 226.17 | 0.622550E+10 | 0.103510E+10 | 0.00 | 1.00 | 10-NOV-13:05 | 0.00 | 01-NOV-00:10 | 33861.31 | 28-NOV-14:00 | 33861.31 | 28-NOV-14:00 | 7690.24 | 20-NOV-13:05 | 7314.12 | 28-NOV-14:00 | 0.00 |
December | 0.753901E+10 | 0.175835E+10 | 204.14 | 0.721006E+10 | 0.328947E+09 | 0.00 | 1.00 | 05-DEC-11:30 | 0.00 | 01-DEC-00:10 | 36470.05 | 05-DEC-15:00 | 36470.05 | 05-DEC-15:00 | 6745.00 | 07-DEC-13:00 | 7876.42 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.219508E+12 | 0.495577E+11 | 3551.45 | 0.161448E+12 | 0.580600E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.380421E+10 | 0.922659E+09 | 149.53 | 0.315536E+10 | 0.328947E+09 | 0.00 | 1.00 | 0.00 | 29692.85 | 29692.85 | 6745.00 | 6574.72 | 0.00 | ||||||
Maximum of Months | 0.458979E+11 | 0.100124E+11 | 448.81 | 0.295371E+11 | 0.163608E+11 | 0.00 | 1.00 | 0.00 | 82712.48 | 67317.67 | 34175.71 | 19723.33 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 291.61 | 0.00 | 291.61 | 194.11 | 1037.89 | 0.00 | 0.00 | 0.00 |
February | 366.04 | 0.00 | 366.04 | 229.98 | 943.76 | 0.00 | 0.00 | 0.00 |
March | 448.56 | 0.00 | 448.56 | 328.63 | 973.10 | 0.00 | 0.00 | 0.00 |
April | 516.79 | 1.99 | 514.80 | 447.29 | 778.06 | 0.00 | 0.00 | 0.00 |
May | 621.02 | 28.92 | 592.10 | 571.17 | 684.02 | 0.00 | 0.00 | 0.00 |
June | 661.73 | 64.70 | 597.03 | 722.07 | 538.99 | 0.00 | 0.00 | 0.00 |
July | 626.55 | 52.52 | 574.04 | 752.98 | 484.44 | 0.00 | 0.00 | 0.00 |
August | 520.33 | 10.42 | 509.91 | 604.53 | 508.05 | 0.00 | 0.00 | 0.00 |
September | 440.41 | 0.07 | 440.34 | 471.56 | 608.74 | 0.00 | 0.00 | 0.00 |
October | 349.34 | 0.00 | 349.34 | 409.60 | 679.88 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 0.00 | 316.31 | 219.63 | 958.41 | 0.00 | 0.00 | 0.00 |
December | 271.46 | 0.00 | 271.46 | 175.11 | 1048.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.88 | 13.29 | 439.59 | 428.43 | 769.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 271.46 | 0.00 | 271.46 | 175.11 | 484.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.73 | 64.70 | 597.03 | 752.98 | 1048.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.39 | 280.46 | 243.94 | 639.64 | 660.09 | 0.00 | 0.00 | 0.00 |
February | 553.18 | 253.42 | 299.76 | 630.99 | 604.61 | 0.00 | 0.00 | 0.00 |
March | 671.95 | 299.39 | 372.57 | 797.43 | 622.47 | 0.00 | 0.00 | 0.00 |
April | 859.08 | 430.85 | 428.24 | 1151.43 | 511.91 | 0.00 | 0.00 | 0.00 |
May | 810.73 | 338.34 | 472.39 | 1043.27 | 470.04 | 0.00 | 0.00 | 0.00 |
June | 805.68 | 349.57 | 456.11 | 1108.46 | 376.45 | 0.00 | 0.00 | 0.00 |
July | 912.90 | 453.64 | 459.25 | 1349.72 | 339.64 | 0.00 | 0.00 | 0.00 |
August | 901.56 | 478.88 | 422.68 | 1351.39 | 345.92 | 0.00 | 0.00 | 0.00 |
September | 656.41 | 300.79 | 355.62 | 931.22 | 399.99 | 0.00 | 0.00 | 0.00 |
October | 581.04 | 298.64 | 282.40 | 842.59 | 440.56 | 0.00 | 0.00 | 0.00 |
November | 529.69 | 269.10 | 260.58 | 642.91 | 613.42 | 0.00 | 0.00 | 0.00 |
December | 505.31 | 280.76 | 224.56 | 616.29 | 665.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 693.59 | 336.82 | 356.77 | 927.50 | 503.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.31 | 253.42 | 224.56 | 616.29 | 339.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 912.90 | 478.88 | 472.39 | 1351.39 | 665.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1924.40 | 1411.64 | 512.77 | 2821.33 | 1012.79 | 0.00 | 0.00 | 0.00 |
February | 1512.48 | 931.61 | 580.87 | 2087.08 | 926.88 | 0.00 | 0.00 | 0.00 |
March | 1205.80 | 582.46 | 623.34 | 1639.11 | 975.20 | 0.00 | 0.00 | 0.00 |
April | 1007.47 | 384.16 | 623.31 | 1458.54 | 817.80 | 0.00 | 0.00 | 0.00 |
May | 717.40 | 88.29 | 629.11 | 840.59 | 745.58 | 0.00 | 0.00 | 0.00 |
June | 629.35 | 38.00 | 591.35 | 737.98 | 584.70 | 0.00 | 0.00 | 0.00 |
July | 666.65 | 75.05 | 591.61 | 910.39 | 520.28 | 0.00 | 0.00 | 0.00 |
August | 856.45 | 270.15 | 586.30 | 1352.70 | 542.09 | 0.00 | 0.00 | 0.00 |
September | 1191.75 | 603.90 | 587.85 | 1888.64 | 629.87 | 0.00 | 0.00 | 0.00 |
October | 1515.63 | 1013.24 | 502.39 | 2408.16 | 683.94 | 0.00 | 0.00 | 0.00 |
November | 1842.09 | 1300.49 | 541.60 | 2688.41 | 937.18 | 0.00 | 0.00 | 0.00 |
December | 2055.88 | 1564.79 | 491.09 | 3027.88 | 1018.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.39 | 687.82 | 571.57 | 1820.96 | 782.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.35 | 38.00 | 491.09 | 737.98 | 520.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.88 | 1564.79 | 629.11 | 3027.88 | 1018.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.13 | 251.74 | 247.39 | 633.64 | 691.97 | 0.00 | 0.00 | 0.00 |
February | 595.46 | 274.89 | 320.57 | 718.83 | 629.73 | 0.00 | 0.00 | 0.00 |
March | 682.56 | 301.98 | 380.59 | 833.62 | 645.97 | 0.00 | 0.00 | 0.00 |
April | 940.95 | 489.95 | 451.00 | 1291.42 | 538.50 | 0.00 | 0.00 | 0.00 |
May | 924.31 | 426.94 | 497.37 | 1229.19 | 490.51 | 0.00 | 0.00 | 0.00 |
June | 979.20 | 489.58 | 489.62 | 1376.20 | 386.75 | 0.00 | 0.00 | 0.00 |
July | 1036.56 | 554.66 | 481.91 | 1536.20 | 349.05 | 0.00 | 0.00 | 0.00 |
August | 972.50 | 527.05 | 445.45 | 1461.87 | 362.32 | 0.00 | 0.00 | 0.00 |
September | 832.64 | 445.53 | 387.11 | 1211.43 | 415.08 | 0.00 | 0.00 | 0.00 |
October | 636.51 | 347.51 | 289.00 | 949.31 | 462.38 | 0.00 | 0.00 | 0.00 |
November | 574.96 | 300.75 | 274.22 | 744.62 | 637.07 | 0.00 | 0.00 | 0.00 |
December | 507.79 | 272.36 | 235.44 | 656.69 | 698.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 765.88 | 390.74 | 375.14 | 1055.21 | 525.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 499.13 | 251.74 | 235.44 | 633.64 | 349.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1036.56 | 554.66 | 497.37 | 1536.20 | 698.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 61.67 | 368.59 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 77.10 | 328.21 | 0.00 | 0.00 | 0.00 |
March | 149.51 | 0.00 | 149.51 | 112.78 | 333.37 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.59 | 155.63 | 262.30 | 0.00 | 0.00 | 0.00 |
May | 207.00 | 9.64 | 197.36 | 196.66 | 231.48 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.00 | 249.87 | 179.81 | 0.00 | 0.00 | 0.00 |
July | 208.84 | 17.50 | 191.34 | 258.96 | 162.58 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.96 | 207.77 | 170.68 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.77 | 160.58 | 208.66 | 0.00 | 0.00 | 0.00 |
October | 116.44 | 0.00 | 116.44 | 136.92 | 237.25 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 70.33 | 340.73 | 0.00 | 0.00 | 0.00 |
December | 90.48 | 0.00 | 90.48 | 55.18 | 372.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.95 | 4.43 | 146.52 | 145.70 | 266.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.48 | 0.00 | 90.48 | 55.18 | 162.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.00 | 258.96 | 372.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 61.67 | 368.61 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 77.10 | 328.23 | 0.00 | 0.00 | 0.00 |
March | 149.52 | 0.00 | 149.52 | 112.78 | 333.39 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.60 | 155.64 | 262.31 | 0.00 | 0.00 | 0.00 |
May | 207.01 | 9.64 | 197.37 | 196.67 | 231.49 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.01 | 249.88 | 179.82 | 0.00 | 0.00 | 0.00 |
July | 208.85 | 17.50 | 191.35 | 258.97 | 162.59 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.97 | 207.78 | 170.69 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.78 | 160.58 | 208.68 | 0.00 | 0.00 | 0.00 |
October | 116.45 | 0.00 | 116.45 | 136.93 | 237.26 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 70.33 | 340.74 | 0.00 | 0.00 | 0.00 |
December | 90.49 | 0.00 | 90.49 | 55.19 | 372.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.96 | 4.43 | 146.53 | 145.70 | 266.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.49 | 0.00 | 90.49 | 55.19 | 162.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.01 | 258.97 | 372.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 97.20 | 0.00 | 97.20 | 61.67 | 368.61 | 0.00 | 0.00 | 0.00 |
February | 122.01 | 0.00 | 122.01 | 77.10 | 328.23 | 0.00 | 0.00 | 0.00 |
March | 149.52 | 0.00 | 149.52 | 112.78 | 333.39 | 0.00 | 0.00 | 0.00 |
April | 172.26 | 0.66 | 171.60 | 155.64 | 262.31 | 0.00 | 0.00 | 0.00 |
May | 207.01 | 9.64 | 197.37 | 196.67 | 231.49 | 0.00 | 0.00 | 0.00 |
June | 220.57 | 21.56 | 199.01 | 249.88 | 179.82 | 0.00 | 0.00 | 0.00 |
July | 208.85 | 17.50 | 191.35 | 258.97 | 162.59 | 0.00 | 0.00 | 0.00 |
August | 173.44 | 3.47 | 169.97 | 207.78 | 170.69 | 0.00 | 0.00 | 0.00 |
September | 146.80 | 0.02 | 146.78 | 160.58 | 208.68 | 0.00 | 0.00 | 0.00 |
October | 116.45 | 0.00 | 116.45 | 136.93 | 237.26 | 0.00 | 0.00 | 0.00 |
November | 105.43 | 0.00 | 105.43 | 70.33 | 340.74 | 0.00 | 0.00 | 0.00 |
December | 90.49 | 0.00 | 90.49 | 55.19 | 372.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 150.96 | 4.43 | 146.53 | 145.70 | 266.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.49 | 0.00 | 90.49 | 55.19 | 162.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 220.57 | 21.56 | 199.01 | 258.97 | 372.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 504.44 | 269.79 | 234.65 | 604.98 | 688.57 | 0.00 | 0.00 | 0.00 |
February | 532.13 | 243.77 | 288.36 | 605.88 | 617.53 | 0.00 | 0.00 | 0.00 |
March | 646.38 | 287.99 | 358.39 | 770.40 | 627.05 | 0.00 | 0.00 | 0.00 |
April | 826.40 | 414.45 | 411.94 | 1118.37 | 512.61 | 0.00 | 0.00 | 0.00 |
May | 779.88 | 325.46 | 454.42 | 1014.54 | 468.19 | 0.00 | 0.00 | 0.00 |
June | 775.03 | 336.27 | 438.76 | 1081.63 | 368.90 | 0.00 | 0.00 | 0.00 |
July | 878.16 | 436.38 | 441.78 | 1312.11 | 338.41 | 0.00 | 0.00 | 0.00 |
August | 867.26 | 460.66 | 406.60 | 1312.17 | 346.62 | 0.00 | 0.00 | 0.00 |
September | 631.43 | 289.34 | 342.09 | 902.43 | 404.88 | 0.00 | 0.00 | 0.00 |
October | 558.93 | 287.28 | 271.66 | 812.27 | 451.29 | 0.00 | 0.00 | 0.00 |
November | 509.53 | 258.86 | 250.67 | 610.92 | 637.19 | 0.00 | 0.00 | 0.00 |
December | 486.08 | 270.07 | 216.01 | 582.58 | 691.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 667.20 | 324.00 | 343.20 | 896.01 | 512.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 486.08 | 243.77 | 216.01 | 582.58 | 338.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 878.16 | 460.66 | 454.42 | 1312.17 | 691.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.95 | 10.67 | 9.28 | 23.92 | 27.23 | 0.00 | 0.00 | 0.00 |
February | 21.04 | 9.64 | 11.40 | 23.96 | 24.42 | 0.00 | 0.00 | 0.00 |
March | 25.56 | 11.39 | 14.17 | 30.46 | 24.79 | 0.00 | 0.00 | 0.00 |
April | 32.67 | 16.39 | 16.29 | 44.22 | 20.27 | 0.00 | 0.00 | 0.00 |
May | 30.84 | 12.87 | 17.97 | 40.11 | 18.51 | 0.00 | 0.00 | 0.00 |
June | 30.64 | 13.30 | 17.35 | 42.77 | 14.59 | 0.00 | 0.00 | 0.00 |
July | 34.72 | 17.25 | 17.47 | 51.88 | 13.38 | 0.00 | 0.00 | 0.00 |
August | 34.29 | 18.21 | 16.08 | 51.88 | 13.71 | 0.00 | 0.00 | 0.00 |
September | 24.97 | 11.44 | 13.53 | 35.68 | 16.01 | 0.00 | 0.00 | 0.00 |
October | 22.10 | 11.36 | 10.74 | 32.12 | 17.84 | 0.00 | 0.00 | 0.00 |
November | 20.15 | 10.24 | 9.91 | 24.16 | 25.19 | 0.00 | 0.00 | 0.00 |
December | 19.22 | 10.68 | 8.54 | 23.03 | 27.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.38 | 12.81 | 13.57 | 35.43 | 20.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 19.22 | 9.64 | 8.54 | 23.03 | 13.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.72 | 18.21 | 17.97 | 51.88 | 27.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.46 | 470.54 | 170.92 | 939.48 | 372.95 | 0.00 | 0.00 | 0.00 |
February | 504.15 | 310.53 | 193.62 | 700.75 | 331.66 | 0.00 | 0.00 | 0.00 |
March | 401.93 | 194.15 | 207.78 | 554.62 | 337.48 | 0.00 | 0.00 | 0.00 |
April | 335.82 | 128.05 | 207.77 | 495.27 | 278.51 | 0.00 | 0.00 | 0.00 |
May | 239.13 | 29.43 | 209.70 | 291.43 | 249.04 | 0.00 | 0.00 | 0.00 |
June | 209.78 | 12.67 | 197.12 | 258.32 | 191.10 | 0.00 | 0.00 | 0.00 |
July | 222.22 | 25.01 | 197.20 | 312.88 | 173.38 | 0.00 | 0.00 | 0.00 |
August | 285.48 | 90.05 | 195.43 | 459.24 | 184.35 | 0.00 | 0.00 | 0.00 |
September | 397.24 | 201.30 | 195.95 | 635.43 | 221.91 | 0.00 | 0.00 | 0.00 |
October | 505.20 | 337.74 | 167.46 | 805.53 | 247.42 | 0.00 | 0.00 | 0.00 |
November | 614.02 | 433.49 | 180.53 | 897.42 | 343.21 | 0.00 | 0.00 | 0.00 |
December | 685.28 | 521.59 | 163.69 | 1009.00 | 374.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.79 | 229.27 | 190.52 | 613.02 | 275.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.78 | 12.67 | 163.69 | 258.32 | 173.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.28 | 521.59 | 209.70 | 1009.00 | 374.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.46 | 470.54 | 170.92 | 939.48 | 372.95 | 0.00 | 0.00 | 0.00 |
February | 504.15 | 310.53 | 193.62 | 700.75 | 331.66 | 0.00 | 0.00 | 0.00 |
March | 401.93 | 194.15 | 207.78 | 554.62 | 337.48 | 0.00 | 0.00 | 0.00 |
April | 335.82 | 128.05 | 207.77 | 495.27 | 278.51 | 0.00 | 0.00 | 0.00 |
May | 239.13 | 29.43 | 209.70 | 291.43 | 249.04 | 0.00 | 0.00 | 0.00 |
June | 209.78 | 12.67 | 197.12 | 258.32 | 191.10 | 0.00 | 0.00 | 0.00 |
July | 222.22 | 25.01 | 197.20 | 312.88 | 173.38 | 0.00 | 0.00 | 0.00 |
August | 285.48 | 90.05 | 195.43 | 459.24 | 184.35 | 0.00 | 0.00 | 0.00 |
September | 397.24 | 201.30 | 195.95 | 635.43 | 221.91 | 0.00 | 0.00 | 0.00 |
October | 505.20 | 337.74 | 167.46 | 805.53 | 247.42 | 0.00 | 0.00 | 0.00 |
November | 614.02 | 433.49 | 180.53 | 897.42 | 343.21 | 0.00 | 0.00 | 0.00 |
December | 685.28 | 521.59 | 163.69 | 1009.00 | 374.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.79 | 229.27 | 190.52 | 613.02 | 275.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.78 | 12.67 | 163.69 | 258.32 | 173.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.28 | 521.59 | 209.70 | 1009.00 | 374.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 641.42 | 470.51 | 170.91 | 939.42 | 372.93 | 0.00 | 0.00 | 0.00 |
February | 504.12 | 310.51 | 193.61 | 700.71 | 331.64 | 0.00 | 0.00 | 0.00 |
March | 401.90 | 194.14 | 207.76 | 554.58 | 337.46 | 0.00 | 0.00 | 0.00 |
April | 335.80 | 128.04 | 207.76 | 495.24 | 278.49 | 0.00 | 0.00 | 0.00 |
May | 239.12 | 29.43 | 209.69 | 291.41 | 249.02 | 0.00 | 0.00 | 0.00 |
June | 209.77 | 12.66 | 197.10 | 258.30 | 191.08 | 0.00 | 0.00 | 0.00 |
July | 222.20 | 25.01 | 197.19 | 312.86 | 173.37 | 0.00 | 0.00 | 0.00 |
August | 285.46 | 90.04 | 195.42 | 459.21 | 184.34 | 0.00 | 0.00 | 0.00 |
September | 397.22 | 201.28 | 195.94 | 635.39 | 221.90 | 0.00 | 0.00 | 0.00 |
October | 505.17 | 337.72 | 167.45 | 805.48 | 247.40 | 0.00 | 0.00 | 0.00 |
November | 613.98 | 433.46 | 180.52 | 897.37 | 343.19 | 0.00 | 0.00 | 0.00 |
December | 685.24 | 521.55 | 163.68 | 1008.94 | 374.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.76 | 229.26 | 190.51 | 612.98 | 275.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.77 | 12.66 | 163.68 | 258.30 | 173.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.24 | 521.55 | 209.69 | 1008.94 | 374.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.14 | 242.16 | 237.98 | 606.33 | 723.46 | 0.00 | 0.00 | 0.00 |
February | 572.81 | 264.43 | 308.37 | 695.13 | 647.83 | 0.00 | 0.00 | 0.00 |
March | 656.59 | 290.49 | 366.11 | 810.53 | 655.77 | 0.00 | 0.00 | 0.00 |
April | 905.15 | 471.31 | 433.84 | 1257.12 | 544.27 | 0.00 | 0.00 | 0.00 |
May | 889.14 | 410.69 | 478.45 | 1197.57 | 495.33 | 0.00 | 0.00 | 0.00 |
June | 941.95 | 470.95 | 470.99 | 1344.06 | 385.02 | 0.00 | 0.00 | 0.00 |
July | 997.13 | 533.55 | 463.57 | 1495.07 | 351.51 | 0.00 | 0.00 | 0.00 |
August | 935.50 | 507.00 | 428.50 | 1422.21 | 365.85 | 0.00 | 0.00 | 0.00 |
September | 800.96 | 428.58 | 372.38 | 1176.06 | 425.58 | 0.00 | 0.00 | 0.00 |
October | 612.30 | 334.29 | 278.01 | 917.54 | 477.39 | 0.00 | 0.00 | 0.00 |
November | 553.09 | 289.30 | 263.78 | 713.94 | 668.46 | 0.00 | 0.00 | 0.00 |
December | 488.47 | 261.99 | 226.48 | 628.13 | 730.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.74 | 375.87 | 360.87 | 1023.56 | 538.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 480.14 | 242.16 | 226.48 | 606.33 | 351.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 997.13 | 533.55 | 478.45 | 1495.07 | 730.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.98 | 9.57 | 9.41 | 23.97 | 28.60 | 0.00 | 0.00 | 0.00 |
February | 22.65 | 10.46 | 12.19 | 27.48 | 25.61 | 0.00 | 0.00 | 0.00 |
March | 25.96 | 11.49 | 14.48 | 32.05 | 25.93 | 0.00 | 0.00 | 0.00 |
April | 35.79 | 18.64 | 17.15 | 49.71 | 21.52 | 0.00 | 0.00 | 0.00 |
May | 35.16 | 16.24 | 18.92 | 47.35 | 19.58 | 0.00 | 0.00 | 0.00 |
June | 37.24 | 18.62 | 18.62 | 53.14 | 15.22 | 0.00 | 0.00 | 0.00 |
July | 39.43 | 21.10 | 18.33 | 59.11 | 13.90 | 0.00 | 0.00 | 0.00 |
August | 36.99 | 20.05 | 16.94 | 56.23 | 14.47 | 0.00 | 0.00 | 0.00 |
September | 31.67 | 16.95 | 14.72 | 46.50 | 16.83 | 0.00 | 0.00 | 0.00 |
October | 24.21 | 13.22 | 10.99 | 36.28 | 18.88 | 0.00 | 0.00 | 0.00 |
November | 21.87 | 11.44 | 10.43 | 28.23 | 26.43 | 0.00 | 0.00 | 0.00 |
December | 19.31 | 10.36 | 8.95 | 24.84 | 28.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.13 | 14.86 | 14.27 | 40.47 | 21.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.98 | 9.57 | 8.95 | 23.97 | 13.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.43 | 21.10 | 18.92 | 59.11 | 28.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 291.61 | 0.00 | 291.61 | 175.37 | 1123.67 | 0.00 | 0.00 | 0.00 |
February | 366.04 | 0.00 | 366.04 | 211.37 | 1022.19 | 0.00 | 0.00 | 0.00 |
March | 448.56 | 0.00 | 448.56 | 312.27 | 1040.71 | 0.00 | 0.00 | 0.00 |
April | 516.79 | 1.99 | 514.80 | 439.44 | 823.59 | 0.00 | 0.00 | 0.00 |
May | 621.02 | 28.92 | 592.10 | 560.53 | 720.05 | 0.00 | 0.00 | 0.00 |
June | 661.73 | 64.70 | 597.03 | 719.79 | 563.49 | 0.00 | 0.00 | 0.00 |
July | 626.55 | 52.52 | 574.04 | 755.14 | 504.63 | 0.00 | 0.00 | 0.00 |
August | 520.33 | 10.42 | 509.91 | 604.78 | 531.66 | 0.00 | 0.00 | 0.00 |
September | 440.41 | 0.07 | 440.34 | 467.23 | 644.26 | 0.00 | 0.00 | 0.00 |
October | 349.34 | 0.00 | 349.34 | 401.40 | 724.44 | 0.00 | 0.00 | 0.00 |
November | 316.31 | 0.00 | 316.31 | 201.98 | 1034.87 | 0.00 | 0.00 | 0.00 |
December | 271.46 | 0.00 | 271.46 | 155.90 | 1137.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.88 | 13.29 | 439.59 | 418.35 | 821.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 271.46 | 0.00 | 271.46 | 155.90 | 504.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.73 | 64.70 | 597.03 | 755.14 | 1137.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 524.39 | 280.46 | 243.94 | 621.02 | 709.35 | 0.00 | 0.00 | 0.00 |
February | 553.18 | 253.42 | 299.76 | 613.86 | 650.56 | 0.00 | 0.00 | 0.00 |
March | 671.95 | 299.39 | 372.57 | 782.28 | 661.66 | 0.00 | 0.00 | 0.00 |
April | 859.08 | 430.85 | 428.24 | 1143.69 | 538.05 | 0.00 | 0.00 | 0.00 |
May | 810.73 | 338.34 | 472.39 | 1035.03 | 492.44 | 0.00 | 0.00 | 0.00 |
June | 805.68 | 349.57 | 456.11 | 1104.36 | 392.21 | 0.00 | 0.00 | 0.00 |
July | 912.90 | 453.64 | 459.25 | 1349.03 | 352.53 | 0.00 | 0.00 | 0.00 |
August | 901.56 | 478.88 | 422.68 | 1349.71 | 360.43 | 0.00 | 0.00 | 0.00 |
September | 656.41 | 300.79 | 355.62 | 926.07 | 421.71 | 0.00 | 0.00 | 0.00 |
October | 581.04 | 298.64 | 282.40 | 834.45 | 466.25 | 0.00 | 0.00 | 0.00 |
November | 529.69 | 269.10 | 260.58 | 626.64 | 656.37 | 0.00 | 0.00 | 0.00 |
December | 505.31 | 280.76 | 224.56 | 596.90 | 715.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 693.59 | 336.82 | 356.77 | 917.35 | 534.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.31 | 253.42 | 224.56 | 596.90 | 352.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 912.90 | 478.88 | 472.39 | 1349.71 | 715.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1924.40 | 1411.64 | 512.77 | 2802.91 | 1082.39 | 0.00 | 0.00 | 0.00 |
February | 1512.48 | 931.61 | 580.87 | 2070.94 | 994.33 | 0.00 | 0.00 | 0.00 |
March | 1205.80 | 582.46 | 623.34 | 1625.56 | 1037.33 | 0.00 | 0.00 | 0.00 |
April | 1007.47 | 384.16 | 623.31 | 1454.23 | 861.74 | 0.00 | 0.00 | 0.00 |
May | 717.40 | 88.29 | 629.11 | 834.82 | 785.24 | 0.00 | 0.00 | 0.00 |
June | 629.35 | 38.00 | 591.35 | 736.92 | 611.31 | 0.00 | 0.00 | 0.00 |
July | 666.65 | 75.05 | 591.61 | 913.37 | 541.40 | 0.00 | 0.00 | 0.00 |
August | 856.45 | 270.15 | 586.30 | 1355.95 | 565.98 | 0.00 | 0.00 | 0.00 |
September | 1191.75 | 603.90 | 587.85 | 1888.25 | 663.11 | 0.00 | 0.00 | 0.00 |
October | 1515.63 | 1013.24 | 502.39 | 2403.23 | 722.21 | 0.00 | 0.00 | 0.00 |
November | 1842.09 | 1300.49 | 541.60 | 2673.70 | 998.42 | 0.00 | 0.00 | 0.00 |
December | 2055.88 | 1564.79 | 491.09 | 3009.12 | 1087.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1259.39 | 687.82 | 571.57 | 1813.35 | 828.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.35 | 38.00 | 491.09 | 736.92 | 541.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.88 | 1564.79 | 629.11 | 3009.12 | 1087.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.13 | 251.74 | 247.39 | 622.58 | 746.33 | 0.00 | 0.00 | 0.00 |
February | 595.46 | 274.89 | 320.57 | 708.11 | 679.49 | 0.00 | 0.00 | 0.00 |
March | 682.56 | 301.98 | 380.59 | 825.02 | 689.64 | 0.00 | 0.00 | 0.00 |
April | 940.95 | 489.95 | 451.00 | 1289.30 | 567.93 | 0.00 | 0.00 | 0.00 |
May | 924.31 | 426.94 | 497.37 | 1227.17 | 516.39 | 0.00 | 0.00 | 0.00 |
June | 979.20 | 489.58 | 489.62 | 1378.36 | 404.28 | 0.00 | 0.00 | 0.00 |
July | 1036.56 | 554.66 | 481.91 | 1540.68 | 363.45 | 0.00 | 0.00 | 0.00 |
August | 972.50 | 527.05 | 445.45 | 1465.61 | 378.35 | 0.00 | 0.00 | 0.00 |
September | 832.64 | 445.53 | 387.11 | 1211.61 | 437.76 | 0.00 | 0.00 | 0.00 |
October | 636.51 | 347.51 | 289.00 | 946.11 | 490.71 | 0.00 | 0.00 | 0.00 |
November | 574.96 | 300.75 | 274.22 | 735.01 | 685.25 | 0.00 | 0.00 | 0.00 |
December | 507.79 | 272.36 | 235.44 | 645.33 | 753.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 765.88 | 390.74 | 375.14 | 1051.24 | 558.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 499.13 | 251.74 | 235.44 | 622.58 | 363.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1036.56 | 554.66 | 497.37 | 1540.68 | 753.97 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.519910E+09 | 0.277987E+10 |
February | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.556378E+09 | 0.228315E+10 |
March | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.880211E+09 | 0.260636E+10 |
April | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.115938E+10 | 0.201672E+10 |
May | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.152983E+10 | 0.183207E+10 |
June | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.187160E+10 | 0.139707E+10 |
July | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.201679E+10 | 0.129752E+10 |
August | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.161916E+10 | 0.136076E+10 |
September | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.122227E+10 | 0.157784E+10 |
October | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.109708E+10 | 0.182100E+10 |
November | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.569270E+09 | 0.248420E+10 |
December | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.469021E+09 | 0.280790E+10 |
Annual Sum or Average | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.135109E+11 | 0.242645E+11 |
Minimum of Months | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.469021E+09 | 0.129752E+10 |
Maximum of Months | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.201679E+10 | 0.280790E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.171321E+10 | 0.176797E+10 |
February | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.152649E+10 | 0.146268E+10 |
March | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.213583E+10 | 0.166722E+10 |
April | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.298452E+10 | 0.132686E+10 |
May | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.279430E+10 | 0.125897E+10 |
June | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.287313E+10 | 0.975763E+09 |
July | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.361510E+10 | 0.909681E+09 |
August | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.361957E+10 | 0.926501E+09 |
September | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.241371E+10 | 0.103678E+10 |
October | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.225681E+10 | 0.117999E+10 |
November | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.166641E+10 | 0.159000E+10 |
December | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.165068E+10 | 0.178113E+10 |
Annual Sum or Average | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.292497E+11 | 0.158835E+11 |
Minimum of Months | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.152649E+10 | 0.909681E+09 |
Maximum of Months | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.361957E+10 | 0.178113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.755665E+10 | 0.271265E+10 |
February | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.504908E+10 | 0.224231E+10 |
March | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.439018E+10 | 0.261197E+10 |
April | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.378054E+10 | 0.211973E+10 |
May | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.225142E+10 | 0.199697E+10 |
June | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.191286E+10 | 0.151555E+10 |
July | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.243838E+10 | 0.139351E+10 |
August | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.362307E+10 | 0.145194E+10 |
September | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.489535E+10 | 0.163261E+10 |
October | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.645002E+10 | 0.183187E+10 |
November | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.696835E+10 | 0.242917E+10 |
December | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.810987E+10 | 0.272775E+10 |
Annual Sum or Average | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.574258E+11 | 0.246660E+11 |
Minimum of Months | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.191286E+10 | 0.139351E+10 |
Maximum of Months | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.810987E+10 | 0.272775E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.169713E+10 | 0.185337E+10 |
February | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.173900E+10 | 0.152343E+10 |
March | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.223277E+10 | 0.173017E+10 |
April | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.334735E+10 | 0.139579E+10 |
May | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.329227E+10 | 0.131379E+10 |
June | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.356710E+10 | 0.100245E+10 |
July | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.411455E+10 | 0.934888E+09 |
August | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.391547E+10 | 0.970441E+09 |
September | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.314003E+10 | 0.107589E+10 |
October | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.254263E+10 | 0.123843E+10 |
November | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.193005E+10 | 0.165129E+10 |
December | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.175887E+10 | 0.187009E+10 |
Annual Sum or Average | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.332772E+11 | 0.165600E+11 |
Minimum of Months | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.169713E+10 | 0.934888E+09 |
Maximum of Months | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.411455E+10 | 0.187009E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260334E+09 | 0.00 | 0.260334E+09 | 0.165169E+09 | 0.987228E+09 |
February | 0.295164E+09 | 0.00 | 0.295164E+09 | 0.186515E+09 | 0.794010E+09 |
March | 0.400455E+09 | 0.00 | 0.400455E+09 | 0.302059E+09 | 0.892897E+09 |
April | 0.446488E+09 | 1718463.26 | 0.444769E+09 | 0.403394E+09 | 0.679875E+09 |
May | 0.554420E+09 | 25816832.63 | 0.528603E+09 | 0.526736E+09 | 0.619998E+09 |
June | 0.571706E+09 | 55893851.50 | 0.515812E+09 | 0.647662E+09 | 0.466071E+09 |
July | 0.559359E+09 | 46883561.74 | 0.512476E+09 | 0.693595E+09 | 0.435450E+09 |
August | 0.464529E+09 | 9301741.30 | 0.455227E+09 | 0.556502E+09 | 0.457139E+09 |
September | 0.380493E+09 | 59638.15 | 0.380434E+09 | 0.416212E+09 | 0.540857E+09 |
October | 0.311880E+09 | 0.00 | 0.311880E+09 | 0.366736E+09 | 0.635448E+09 |
November | 0.273276E+09 | 0.00 | 0.273276E+09 | 0.182284E+09 | 0.883160E+09 |
December | 0.242349E+09 | 0.00 | 0.242349E+09 | 0.147807E+09 | 0.997074E+09 |
Annual Sum or Average | 0.476046E+10 | 0.139674E+09 | 0.462078E+10 | 0.459467E+10 | 0.838921E+10 |
Minimum of Months | 0.242349E+09 | 0.00 | 0.242349E+09 | 0.147807E+09 | 0.435450E+09 |
Maximum of Months | 0.571706E+09 | 55893851.50 | 0.528603E+09 | 0.693595E+09 | 0.997074E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260345E+09 | 0.00 | 0.260345E+09 | 0.165174E+09 | 0.987285E+09 |
February | 0.295176E+09 | 0.00 | 0.295176E+09 | 0.186519E+09 | 0.794057E+09 |
March | 0.400471E+09 | 0.00 | 0.400471E+09 | 0.302067E+09 | 0.892952E+09 |
April | 0.446507E+09 | 1718509.46 | 0.444789E+09 | 0.403410E+09 | 0.679916E+09 |
May | 0.554443E+09 | 25817526.59 | 0.528625E+09 | 0.526752E+09 | 0.620035E+09 |
June | 0.571730E+09 | 55895353.94 | 0.515834E+09 | 0.647684E+09 | 0.466099E+09 |
July | 0.559383E+09 | 46884821.98 | 0.512499E+09 | 0.693623E+09 | 0.435475E+09 |
August | 0.464550E+09 | 9301991.33 | 0.455248E+09 | 0.556527E+09 | 0.457165E+09 |
September | 0.380510E+09 | 59639.75 | 0.380450E+09 | 0.416230E+09 | 0.540888E+09 |
October | 0.311894E+09 | 0.00 | 0.311894E+09 | 0.366753E+09 | 0.635484E+09 |
November | 0.273287E+09 | 0.00 | 0.273287E+09 | 0.182290E+09 | 0.883211E+09 |
December | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.147812E+09 | 0.997132E+09 |
Annual Sum or Average | 0.476066E+10 | 0.139678E+09 | 0.462098E+10 | 0.459484E+10 | 0.838970E+10 |
Minimum of Months | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.147812E+09 | 0.435475E+09 |
Maximum of Months | 0.571730E+09 | 55895353.94 | 0.528625E+09 | 0.693623E+09 | 0.997132E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.260345E+09 | 0.00 | 0.260345E+09 | 0.165174E+09 | 0.987285E+09 |
February | 0.295176E+09 | 0.00 | 0.295176E+09 | 0.186519E+09 | 0.794057E+09 |
March | 0.400471E+09 | 0.00 | 0.400471E+09 | 0.302067E+09 | 0.892952E+09 |
April | 0.446507E+09 | 1718509.46 | 0.444789E+09 | 0.403410E+09 | 0.679916E+09 |
May | 0.554443E+09 | 25817526.59 | 0.528625E+09 | 0.526752E+09 | 0.620035E+09 |
June | 0.571730E+09 | 55895353.94 | 0.515834E+09 | 0.647684E+09 | 0.466099E+09 |
July | 0.559383E+09 | 46884821.98 | 0.512499E+09 | 0.693623E+09 | 0.435475E+09 |
August | 0.464550E+09 | 9301991.33 | 0.455248E+09 | 0.556527E+09 | 0.457165E+09 |
September | 0.380510E+09 | 59639.75 | 0.380450E+09 | 0.416230E+09 | 0.540888E+09 |
October | 0.311894E+09 | 0.00 | 0.311894E+09 | 0.366753E+09 | 0.635484E+09 |
November | 0.273287E+09 | 0.00 | 0.273287E+09 | 0.182290E+09 | 0.883211E+09 |
December | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.147812E+09 | 0.997132E+09 |
Annual Sum or Average | 0.476066E+10 | 0.139678E+09 | 0.462098E+10 | 0.459484E+10 | 0.838970E+10 |
Minimum of Months | 0.242359E+09 | 0.00 | 0.242359E+09 | 0.147812E+09 | 0.435475E+09 |
Maximum of Months | 0.571730E+09 | 55895353.94 | 0.528625E+09 | 0.693623E+09 | 0.997132E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135109E+10 | 0.722593E+09 | 0.628499E+09 | 0.162038E+10 | 0.184427E+10 |
February | 0.128733E+10 | 0.589736E+09 | 0.697598E+09 | 0.146575E+10 | 0.149394E+10 |
March | 0.173128E+10 | 0.771360E+09 | 0.959917E+09 | 0.206344E+10 | 0.167949E+10 |
April | 0.214202E+10 | 0.107426E+10 | 0.106776E+10 | 0.289881E+10 | 0.132869E+10 |
May | 0.208884E+10 | 0.871716E+09 | 0.121712E+10 | 0.271733E+10 | 0.125399E+10 |
June | 0.200887E+10 | 0.871607E+09 | 0.113726E+10 | 0.280358E+10 | 0.956183E+09 |
July | 0.235207E+10 | 0.116880E+10 | 0.118327E+10 | 0.351436E+10 | 0.906389E+09 |
August | 0.232286E+10 | 0.123382E+10 | 0.108904E+10 | 0.351450E+10 | 0.928395E+09 |
September | 0.163667E+10 | 0.749981E+09 | 0.886691E+09 | 0.233911E+10 | 0.104945E+10 |
October | 0.149704E+10 | 0.769439E+09 | 0.727605E+09 | 0.217557E+10 | 0.120874E+10 |
November | 0.132071E+10 | 0.670972E+09 | 0.649736E+09 | 0.158350E+10 | 0.165161E+10 |
December | 0.130193E+10 | 0.723362E+09 | 0.578566E+09 | 0.156037E+10 | 0.185195E+10 |
Annual Sum or Average | 0.210407E+11 | 0.102176E+11 | 0.108231E+11 | 0.282567E+11 | 0.161531E+11 |
Minimum of Months | 0.128733E+10 | 0.589736E+09 | 0.578566E+09 | 0.146575E+10 | 0.906389E+09 |
Maximum of Months | 0.235207E+10 | 0.123382E+10 | 0.121712E+10 | 0.351450E+10 | 0.185195E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 53420946.35 | 28570678.17 | 24850268.18 | 64068459.97 | 72920925.33 |
February | 50900029.87 | 23317617.75 | 27582412.12 | 57954441.84 | 59068906.63 |
March | 68453131.60 | 30498874.53 | 37954257.08 | 81586594.06 | 66405699.23 |
April | 84693429.20 | 42475266.96 | 42218162.25 | 0.114616E+09 | 52535013.94 |
May | 82590686.80 | 34466861.00 | 48123825.80 | 0.107441E+09 | 49581554.25 |
June | 79428758.87 | 34462562.24 | 44966196.63 | 0.110851E+09 | 37806596.72 |
July | 92998785.53 | 46213353.89 | 46785431.64 | 0.138955E+09 | 35837802.26 |
August | 91843830.39 | 48784140.54 | 43059689.84 | 0.138960E+09 | 36707918.32 |
September | 64712538.24 | 29653592.71 | 35058945.53 | 92486223.55 | 41494169.20 |
October | 59191794.02 | 30422932.67 | 28768861.35 | 86020228.90 | 47792572.71 |
November | 52219614.40 | 26529622.89 | 25689991.51 | 62610004.38 | 65303047.54 |
December | 51477071.96 | 28601093.78 | 22875978.19 | 61695653.40 | 73224489.89 |
Annual Sum or Average | 0.831931E+09 | 0.403997E+09 | 0.427934E+09 | 0.111725E+10 | 0.638679E+09 |
Minimum of Months | 50900029.87 | 23317617.75 | 22875978.19 | 57954441.84 | 35837802.26 |
Maximum of Months | 92998785.53 | 48784140.54 | 48123825.80 | 0.138960E+09 | 73224489.89 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171808E+10 | 0.126029E+10 | 0.457791E+09 | 0.251629E+10 | 0.998914E+09 |
February | 0.121964E+10 | 0.751233E+09 | 0.468409E+09 | 0.169526E+10 | 0.802359E+09 |
March | 0.107652E+10 | 0.520007E+09 | 0.556513E+09 | 0.148549E+10 | 0.903909E+09 |
April | 0.870447E+09 | 0.331907E+09 | 0.538540E+09 | 0.128373E+10 | 0.721893E+09 |
May | 0.640488E+09 | 78819929.33 | 0.561669E+09 | 0.780563E+09 | 0.667019E+09 |
June | 0.543755E+09 | 32829474.14 | 0.510925E+09 | 0.669561E+09 | 0.495323E+09 |
July | 0.595185E+09 | 66999882.23 | 0.528186E+09 | 0.838024E+09 | 0.464378E+09 |
August | 0.764632E+09 | 0.241186E+09 | 0.523445E+09 | 0.123004E+10 | 0.493755E+09 |
September | 0.102966E+10 | 0.521760E+09 | 0.507898E+09 | 0.164704E+10 | 0.575199E+09 |
October | 0.135313E+10 | 0.904602E+09 | 0.448528E+09 | 0.215752E+10 | 0.662687E+09 |
November | 0.159154E+10 | 0.112360E+10 | 0.467940E+09 | 0.232612E+10 | 0.889599E+09 |
December | 0.183546E+10 | 0.139702E+10 | 0.438437E+09 | 0.270250E+10 | 0.100379E+10 |
Annual Sum or Average | 0.132385E+11 | 0.723025E+10 | 0.600828E+10 | 0.193321E+11 | 0.867883E+10 |
Minimum of Months | 0.543755E+09 | 32829474.14 | 0.438437E+09 | 0.669561E+09 | 0.464378E+09 |
Maximum of Months | 0.183546E+10 | 0.139702E+10 | 0.561669E+09 | 0.270250E+10 | 0.100379E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171808E+10 | 0.126029E+10 | 0.457791E+09 | 0.251629E+10 | 0.998914E+09 |
February | 0.121964E+10 | 0.751233E+09 | 0.468409E+09 | 0.169526E+10 | 0.802359E+09 |
March | 0.107652E+10 | 0.520007E+09 | 0.556513E+09 | 0.148549E+10 | 0.903909E+09 |
April | 0.870447E+09 | 0.331907E+09 | 0.538540E+09 | 0.128373E+10 | 0.721893E+09 |
May | 0.640488E+09 | 78819929.33 | 0.561669E+09 | 0.780563E+09 | 0.667019E+09 |
June | 0.543755E+09 | 32829474.14 | 0.510925E+09 | 0.669561E+09 | 0.495323E+09 |
July | 0.595185E+09 | 66999882.23 | 0.528186E+09 | 0.838024E+09 | 0.464378E+09 |
August | 0.764632E+09 | 0.241186E+09 | 0.523445E+09 | 0.123004E+10 | 0.493755E+09 |
September | 0.102966E+10 | 0.521760E+09 | 0.507898E+09 | 0.164704E+10 | 0.575199E+09 |
October | 0.135313E+10 | 0.904602E+09 | 0.448528E+09 | 0.215752E+10 | 0.662687E+09 |
November | 0.159154E+10 | 0.112360E+10 | 0.467940E+09 | 0.232612E+10 | 0.889599E+09 |
December | 0.183546E+10 | 0.139702E+10 | 0.438437E+09 | 0.270250E+10 | 0.100379E+10 |
Annual Sum or Average | 0.132385E+11 | 0.723025E+10 | 0.600828E+10 | 0.193321E+11 | 0.867883E+10 |
Minimum of Months | 0.543755E+09 | 32829474.14 | 0.438437E+09 | 0.669561E+09 | 0.464378E+09 |
Maximum of Months | 0.183546E+10 | 0.139702E+10 | 0.561669E+09 | 0.270250E+10 | 0.100379E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171797E+10 | 0.126021E+10 | 0.457763E+09 | 0.251613E+10 | 0.998851E+09 |
February | 0.121956E+10 | 0.751185E+09 | 0.468379E+09 | 0.169515E+10 | 0.802308E+09 |
March | 0.107645E+10 | 0.519974E+09 | 0.556477E+09 | 0.148539E+10 | 0.903852E+09 |
April | 0.870392E+09 | 0.331886E+09 | 0.538506E+09 | 0.128365E+10 | 0.721847E+09 |
May | 0.640448E+09 | 78814948.36 | 0.561633E+09 | 0.780513E+09 | 0.666977E+09 |
June | 0.543720E+09 | 32827399.51 | 0.510893E+09 | 0.669519E+09 | 0.495291E+09 |
July | 0.595148E+09 | 66995648.21 | 0.528152E+09 | 0.837971E+09 | 0.464349E+09 |
August | 0.764583E+09 | 0.241171E+09 | 0.523412E+09 | 0.122996E+10 | 0.493724E+09 |
September | 0.102959E+10 | 0.521727E+09 | 0.507866E+09 | 0.164693E+10 | 0.575163E+09 |
October | 0.135305E+10 | 0.904545E+09 | 0.448500E+09 | 0.215739E+10 | 0.662645E+09 |
November | 0.159144E+10 | 0.112353E+10 | 0.467910E+09 | 0.232597E+10 | 0.889543E+09 |
December | 0.183534E+10 | 0.139693E+10 | 0.438410E+09 | 0.270233E+10 | 0.100373E+10 |
Annual Sum or Average | 0.132377E+11 | 0.722979E+10 | 0.600790E+10 | 0.193309E+11 | 0.867828E+10 |
Minimum of Months | 0.543720E+09 | 32827399.51 | 0.438410E+09 | 0.669519E+09 | 0.464349E+09 |
Maximum of Months | 0.183534E+10 | 0.139693E+10 | 0.561633E+09 | 0.270233E+10 | 0.100373E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128601E+10 | 0.648601E+09 | 0.637405E+09 | 0.162399E+10 | 0.193771E+10 |
February | 0.138574E+10 | 0.639720E+09 | 0.746019E+09 | 0.168167E+10 | 0.156722E+10 |
March | 0.175862E+10 | 0.778037E+09 | 0.980579E+09 | 0.217094E+10 | 0.175642E+10 |
April | 0.234615E+10 | 0.122163E+10 | 0.112452E+10 | 0.325844E+10 | 0.141075E+10 |
May | 0.238147E+10 | 0.109999E+10 | 0.128148E+10 | 0.320758E+10 | 0.132668E+10 |
June | 0.244152E+10 | 0.122071E+10 | 0.122081E+10 | 0.348380E+10 | 0.997971E+09 |
July | 0.267070E+10 | 0.142906E+10 | 0.124164E+10 | 0.400439E+10 | 0.941476E+09 |
August | 0.250564E+10 | 0.135795E+10 | 0.114769E+10 | 0.380924E+10 | 0.979903E+09 |
September | 0.207609E+10 | 0.111088E+10 | 0.965207E+09 | 0.304836E+10 | 0.110310E+10 |
October | 0.163997E+10 | 0.895354E+09 | 0.744621E+09 | 0.245753E+10 | 0.127865E+10 |
November | 0.143360E+10 | 0.749872E+09 | 0.683729E+09 | 0.185052E+10 | 0.173266E+10 |
December | 0.130832E+10 | 0.701720E+09 | 0.606601E+09 | 0.168239E+10 | 0.195646E+10 |
Annual Sum or Average | 0.232338E+11 | 0.118535E+11 | 0.113803E+11 | 0.322788E+11 | 0.169890E+11 |
Minimum of Months | 0.128601E+10 | 0.639720E+09 | 0.606601E+09 | 0.162399E+10 | 0.941476E+09 |
Maximum of Months | 0.267070E+10 | 0.142906E+10 | 0.128148E+10 | 0.400439E+10 | 0.195646E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50847388.40 | 25645034.41 | 25202353.99 | 64210814.14 | 76615317.41 |
February | 54790705.92 | 25293858.53 | 29496847.39 | 66491303.42 | 61966560.81 |
March | 69533916.73 | 30762785.10 | 38771131.64 | 85836549.62 | 69447153.28 |
April | 92764216.28 | 48301985.15 | 44462231.13 | 0.128836E+09 | 55779828.51 |
May | 94161049.55 | 43492648.38 | 50668401.16 | 0.126824E+09 | 52455779.85 |
June | 96535428.04 | 48265674.06 | 48269753.98 | 0.137746E+09 | 39458848.15 |
July | 0.105597E+09 | 56503714.35 | 49093129.74 | 0.158329E+09 | 37225096.62 |
August | 99070456.15 | 53691856.15 | 45378600.00 | 0.150613E+09 | 38744482.55 |
September | 82086361.34 | 43923044.09 | 38163317.25 | 0.120529E+09 | 43615682.96 |
October | 64842956.12 | 35401356.91 | 29441599.21 | 97168113.97 | 50556626.99 |
November | 56683134.85 | 29649156.44 | 27033978.40 | 73167641.42 | 68507628.74 |
December | 51729684.55 | 27745281.96 | 23984402.59 | 66520112.23 | 77356711.74 |
Annual Sum or Average | 0.918642E+09 | 0.468676E+09 | 0.449966E+09 | 0.127627E+10 | 0.671730E+09 |
Minimum of Months | 50847388.40 | 25293858.53 | 23984402.59 | 64210814.14 | 37225096.62 |
Maximum of Months | 0.105597E+09 | 56503714.35 | 50668401.16 | 0.158329E+09 | 77356711.74 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.469706E+09 | 0.300964E+10 |
February | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.511338E+09 | 0.247289E+10 |
March | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.836376E+09 | 0.278745E+10 |
April | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.113903E+10 | 0.213474E+10 |
May | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.150132E+10 | 0.192858E+10 |
June | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.186570E+10 | 0.146057E+10 |
July | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.202256E+10 | 0.135159E+10 |
August | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.161985E+10 | 0.142401E+10 |
September | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.121106E+10 | 0.166993E+10 |
October | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.107510E+10 | 0.194034E+10 |
November | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.523529E+09 | 0.268239E+10 |
December | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.417550E+09 | 0.304702E+10 |
Annual Sum or Average | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.131931E+11 | 0.259091E+11 |
Minimum of Months | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.417550E+09 | 0.135159E+10 |
Maximum of Months | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.202256E+10 | 0.304702E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.166334E+10 | 0.189992E+10 |
February | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.148505E+10 | 0.157384E+10 |
March | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.209527E+10 | 0.177219E+10 |
April | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.296443E+10 | 0.139463E+10 |
May | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.277221E+10 | 0.131896E+10 |
June | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.286251E+10 | 0.101661E+10 |
July | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.361324E+10 | 0.944217E+09 |
August | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.361507E+10 | 0.965364E+09 |
September | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.240037E+10 | 0.109307E+10 |
October | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.223500E+10 | 0.124881E+10 |
November | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.162425E+10 | 0.170131E+10 |
December | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.159872E+10 | 0.191582E+10 |
Annual Sum or Average | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.289295E+11 | 0.168447E+11 |
Minimum of Months | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.148505E+10 | 0.944217E+09 |
Maximum of Months | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.361507E+10 | 0.191582E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.750731E+10 | 0.289908E+10 |
February | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.501001E+10 | 0.240549E+10 |
March | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.435391E+10 | 0.277839E+10 |
April | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.376935E+10 | 0.223363E+10 |
May | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.223597E+10 | 0.210319E+10 |
June | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.191009E+10 | 0.158451E+10 |
July | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.244637E+10 | 0.145010E+10 |
August | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.363179E+10 | 0.151593E+10 |
September | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.489436E+10 | 0.171877E+10 |
October | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.643682E+10 | 0.193438E+10 |
November | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.693022E+10 | 0.258790E+10 |
December | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.805963E+10 | 0.291265E+10 |
Annual Sum or Average | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.571858E+11 | 0.261240E+11 |
Minimum of Months | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.191009E+10 | 0.145010E+10 |
Maximum of Months | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.805963E+10 | 0.291265E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.166753E+10 | 0.199896E+10 |
February | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.171306E+10 | 0.164382E+10 |
March | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.220973E+10 | 0.184713E+10 |
April | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.334187E+10 | 0.147208E+10 |
May | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.328685E+10 | 0.138310E+10 |
June | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.357270E+10 | 0.104790E+10 |
July | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.412656E+10 | 0.973474E+09 |
August | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.392548E+10 | 0.101336E+10 |
September | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.314049E+10 | 0.113468E+10 |
October | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.253406E+10 | 0.131433E+10 |
November | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.190514E+10 | 0.177616E+10 |
December | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.172845E+10 | 0.201943E+10 |
Annual Sum or Average | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.331519E+11 | 0.176244E+11 |
Minimum of Months | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.166753E+10 | 0.973474E+09 |
Maximum of Months | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.412656E+10 | 0.201943E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.11 | 1037.89 | 291.61 | 0.00 | 291.61 | 0.00 | 0.00 |
February | 229.98 | 943.76 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 328.63 | 973.10 | 448.56 | 0.00 | 448.56 | 0.00 | 0.00 |
April | 447.29 | 778.06 | 516.79 | 1.99 | 514.80 | 0.00 | 0.00 |
May | 571.17 | 684.02 | 621.02 | 28.92 | 592.10 | 0.00 | 0.00 |
June | 722.07 | 538.99 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
July | 752.98 | 484.44 | 626.55 | 52.52 | 574.04 | 0.00 | 0.00 |
August | 604.53 | 508.05 | 520.33 | 10.42 | 509.91 | 0.00 | 0.00 |
September | 471.56 | 608.74 | 440.41 | 0.07 | 440.34 | 0.00 | 0.00 |
October | 409.60 | 679.88 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 219.63 | 958.41 | 316.31 | 0.00 | 316.31 | 0.00 | 0.00 |
December | 175.11 | 1048.35 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 428.43 | 769.42 | 452.88 | 13.29 | 439.59 | 0.00 | 0.00 |
Minimum of Months | 175.11 | 484.44 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 752.98 | 1048.35 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 639.64 | 660.09 | 524.39 | 280.46 | 243.94 | 0.00 | 0.00 |
February | 630.99 | 604.61 | 553.18 | 253.42 | 299.76 | 0.00 | 0.00 |
March | 797.43 | 622.47 | 671.95 | 299.39 | 372.57 | 0.00 | 0.00 |
April | 1151.43 | 511.91 | 859.08 | 430.85 | 428.24 | 0.00 | 0.00 |
May | 1043.27 | 470.04 | 810.73 | 338.34 | 472.39 | 0.00 | 0.00 |
June | 1108.46 | 376.45 | 805.68 | 349.57 | 456.11 | 0.00 | 0.00 |
July | 1349.72 | 339.64 | 912.90 | 453.64 | 459.25 | 0.00 | 0.00 |
August | 1351.39 | 345.92 | 901.56 | 478.88 | 422.68 | 0.00 | 0.00 |
September | 931.22 | 399.99 | 656.41 | 300.79 | 355.62 | 0.00 | 0.00 |
October | 842.59 | 440.56 | 581.04 | 298.64 | 282.40 | 0.00 | 0.00 |
November | 642.91 | 613.42 | 529.69 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 616.29 | 665.00 | 505.31 | 280.76 | 224.56 | 0.00 | 0.00 |
Annual Sum or Average | 927.50 | 503.66 | 693.59 | 336.82 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 616.29 | 339.64 | 505.31 | 253.42 | 224.56 | 0.00 | 0.00 |
Maximum of Months | 1351.39 | 665.00 | 912.90 | 478.88 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2821.33 | 1012.79 | 1924.40 | 1411.64 | 512.77 | 0.00 | 0.00 |
February | 2087.08 | 926.88 | 1512.48 | 931.61 | 580.87 | 0.00 | 0.00 |
March | 1639.11 | 975.20 | 1205.80 | 582.46 | 623.34 | 0.00 | 0.00 |
April | 1458.54 | 817.80 | 1007.47 | 384.16 | 623.31 | 0.00 | 0.00 |
May | 840.59 | 745.58 | 717.40 | 88.29 | 629.11 | 0.00 | 0.00 |
June | 737.98 | 584.70 | 629.35 | 38.00 | 591.35 | 0.00 | 0.00 |
July | 910.39 | 520.28 | 666.65 | 75.05 | 591.61 | 0.00 | 0.00 |
August | 1352.70 | 542.09 | 856.45 | 270.15 | 586.30 | 0.00 | 0.00 |
September | 1888.64 | 629.87 | 1191.75 | 603.90 | 587.85 | 0.00 | 0.00 |
October | 2408.16 | 683.94 | 1515.63 | 1013.24 | 502.39 | 0.00 | 0.00 |
November | 2688.41 | 937.18 | 1842.09 | 1300.49 | 541.60 | 0.00 | 0.00 |
December | 3027.88 | 1018.43 | 2055.88 | 1564.79 | 491.09 | 0.00 | 0.00 |
Annual Sum or Average | 1820.96 | 782.15 | 1259.39 | 687.82 | 571.57 | 0.00 | 0.00 |
Minimum of Months | 737.98 | 520.28 | 629.35 | 38.00 | 491.09 | 0.00 | 0.00 |
Maximum of Months | 3027.88 | 1018.43 | 2055.88 | 1564.79 | 629.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 633.64 | 691.97 | 499.13 | 251.74 | 247.39 | 0.00 | 0.00 |
February | 718.83 | 629.73 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 833.62 | 645.97 | 682.56 | 301.98 | 380.59 | 0.00 | 0.00 |
April | 1291.42 | 538.50 | 940.95 | 489.95 | 451.00 | 0.00 | 0.00 |
May | 1229.19 | 490.51 | 924.31 | 426.94 | 497.37 | 0.00 | 0.00 |
June | 1376.20 | 386.75 | 979.20 | 489.58 | 489.62 | 0.00 | 0.00 |
July | 1536.20 | 349.05 | 1036.56 | 554.66 | 481.91 | 0.00 | 0.00 |
August | 1461.87 | 362.32 | 972.50 | 527.05 | 445.45 | 0.00 | 0.00 |
September | 1211.43 | 415.08 | 832.64 | 445.53 | 387.11 | 0.00 | 0.00 |
October | 949.31 | 462.38 | 636.51 | 347.51 | 289.00 | 0.00 | 0.00 |
November | 744.62 | 637.07 | 574.96 | 300.75 | 274.22 | 0.00 | 0.00 |
December | 656.69 | 698.21 | 507.79 | 272.36 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1055.21 | 525.12 | 765.88 | 390.74 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 633.64 | 349.05 | 499.13 | 251.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 1536.20 | 698.21 | 1036.56 | 554.66 | 497.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.00 | 1105.81 | 291.60 | 0.00 | 291.60 | 0.00 | 0.00 |
February | 231.30 | 984.67 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 338.33 | 1000.15 | 448.55 | 0.00 | 448.55 | 0.00 | 0.00 |
April | 466.90 | 786.92 | 516.78 | 1.99 | 514.79 | 0.00 | 0.00 |
May | 589.99 | 694.47 | 621.01 | 28.92 | 592.09 | 0.00 | 0.00 |
June | 749.63 | 539.46 | 661.72 | 64.69 | 597.02 | 0.00 | 0.00 |
July | 776.90 | 487.75 | 626.54 | 52.51 | 574.03 | 0.00 | 0.00 |
August | 623.34 | 512.05 | 520.32 | 10.42 | 509.90 | 0.00 | 0.00 |
September | 481.74 | 626.02 | 440.40 | 0.07 | 440.33 | 0.00 | 0.00 |
October | 410.78 | 711.77 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 210.98 | 1022.22 | 316.30 | 0.00 | 316.30 | 0.00 | 0.00 |
December | 165.56 | 1116.84 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 437.10 | 798.09 | 452.87 | 13.29 | 439.58 | 0.00 | 0.00 |
Minimum of Months | 165.56 | 487.75 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 776.90 | 1116.84 | 661.72 | 64.69 | 597.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 628.90 | 715.80 | 524.38 | 280.45 | 243.93 | 0.00 | 0.00 |
February | 629.84 | 641.95 | 553.17 | 253.41 | 299.76 | 0.00 | 0.00 |
March | 800.86 | 651.84 | 671.94 | 299.38 | 372.56 | 0.00 | 0.00 |
April | 1162.59 | 532.88 | 859.07 | 430.84 | 428.23 | 0.00 | 0.00 |
May | 1054.65 | 486.70 | 810.72 | 338.33 | 472.39 | 0.00 | 0.00 |
June | 1124.40 | 383.48 | 805.67 | 349.56 | 456.11 | 0.00 | 0.00 |
July | 1363.99 | 351.79 | 912.88 | 453.63 | 459.25 | 0.00 | 0.00 |
August | 1364.05 | 360.33 | 901.55 | 478.87 | 422.68 | 0.00 | 0.00 |
September | 938.12 | 420.89 | 656.40 | 300.79 | 355.61 | 0.00 | 0.00 |
October | 844.38 | 469.14 | 581.03 | 298.63 | 282.40 | 0.00 | 0.00 |
November | 635.07 | 662.39 | 529.68 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 605.61 | 718.78 | 505.30 | 280.75 | 224.55 | 0.00 | 0.00 |
Annual Sum or Average | 931.44 | 532.46 | 693.58 | 336.81 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 605.61 | 351.79 | 505.30 | 253.41 | 224.55 | 0.00 | 0.00 |
Maximum of Months | 1364.05 | 718.78 | 912.88 | 478.87 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2818.37 | 1118.83 | 1924.33 | 1411.58 | 512.75 | 0.00 | 0.00 |
February | 2102.21 | 994.97 | 1512.42 | 931.57 | 580.85 | 0.00 | 0.00 |
March | 1663.82 | 1012.42 | 1205.75 | 582.43 | 623.32 | 0.00 | 0.00 |
April | 1485.77 | 835.51 | 1007.44 | 384.14 | 623.30 | 0.00 | 0.00 |
May | 874.27 | 747.09 | 717.38 | 88.28 | 629.10 | 0.00 | 0.00 |
June | 774.94 | 573.28 | 629.33 | 38.00 | 591.34 | 0.00 | 0.00 |
July | 938.63 | 520.13 | 666.64 | 75.04 | 591.59 | 0.00 | 0.00 |
August | 1377.70 | 553.03 | 856.42 | 270.14 | 586.28 | 0.00 | 0.00 |
September | 1906.25 | 665.73 | 1191.71 | 603.88 | 587.83 | 0.00 | 0.00 |
October | 2416.53 | 742.24 | 1515.57 | 1013.20 | 502.37 | 0.00 | 0.00 |
November | 2692.21 | 1029.61 | 1842.02 | 1300.44 | 541.59 | 0.00 | 0.00 |
December | 3026.93 | 1124.29 | 2055.80 | 1564.73 | 491.07 | 0.00 | 0.00 |
Annual Sum or Average | 1839.01 | 825.59 | 1259.35 | 687.79 | 571.55 | 0.00 | 0.00 |
Minimum of Months | 774.94 | 520.13 | 629.33 | 38.00 | 491.07 | 0.00 | 0.00 |
Maximum of Months | 3026.93 | 1124.29 | 2055.80 | 1564.73 | 629.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 630.30 | 752.06 | 499.12 | 251.73 | 247.39 | 0.00 | 0.00 |
February | 722.62 | 673.44 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 842.58 | 681.70 | 682.55 | 301.97 | 380.58 | 0.00 | 0.00 |
April | 1306.82 | 565.79 | 940.94 | 489.94 | 450.99 | 0.00 | 0.00 |
May | 1244.92 | 514.91 | 924.30 | 426.93 | 497.37 | 0.00 | 0.00 |
June | 1397.20 | 400.24 | 979.19 | 489.57 | 489.62 | 0.00 | 0.00 |
July | 1554.18 | 365.41 | 1036.55 | 554.65 | 481.90 | 0.00 | 0.00 |
August | 1478.44 | 380.32 | 972.49 | 527.05 | 445.44 | 0.00 | 0.00 |
September | 1222.56 | 442.41 | 832.63 | 445.53 | 387.10 | 0.00 | 0.00 |
October | 953.81 | 496.27 | 636.51 | 347.50 | 289.00 | 0.00 | 0.00 |
November | 742.16 | 694.89 | 574.96 | 300.74 | 274.21 | 0.00 | 0.00 |
December | 652.97 | 759.34 | 507.78 | 272.35 | 235.43 | 0.00 | 0.00 |
Annual Sum or Average | 1064.03 | 560.02 | 765.87 | 390.73 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 630.30 | 365.41 | 499.12 | 251.73 | 235.43 | 0.00 | 0.00 |
Maximum of Months | 1554.18 | 759.34 | 1036.55 | 554.65 | 497.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 175.37 | 1123.67 | 291.61 | 0.00 | 291.61 | 0.00 | 0.00 |
February | 211.37 | 1022.19 | 366.04 | 0.00 | 366.04 | 0.00 | 0.00 |
March | 312.27 | 1040.71 | 448.56 | 0.00 | 448.56 | 0.00 | 0.00 |
April | 439.44 | 823.59 | 516.79 | 1.99 | 514.80 | 0.00 | 0.00 |
May | 560.53 | 720.05 | 621.02 | 28.92 | 592.10 | 0.00 | 0.00 |
June | 719.79 | 563.49 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
July | 755.14 | 504.63 | 626.55 | 52.52 | 574.04 | 0.00 | 0.00 |
August | 604.78 | 531.66 | 520.33 | 10.42 | 509.91 | 0.00 | 0.00 |
September | 467.23 | 644.26 | 440.41 | 0.07 | 440.34 | 0.00 | 0.00 |
October | 401.40 | 724.44 | 349.34 | 0.00 | 349.34 | 0.00 | 0.00 |
November | 201.98 | 1034.87 | 316.31 | 0.00 | 316.31 | 0.00 | 0.00 |
December | 155.90 | 1137.63 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Annual Sum or Average | 418.35 | 821.57 | 452.88 | 13.29 | 439.59 | 0.00 | 0.00 |
Minimum of Months | 155.90 | 504.63 | 271.46 | 0.00 | 271.46 | 0.00 | 0.00 |
Maximum of Months | 755.14 | 1137.63 | 661.73 | 64.70 | 597.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 621.02 | 709.35 | 524.39 | 280.46 | 243.94 | 0.00 | 0.00 |
February | 613.86 | 650.56 | 553.18 | 253.42 | 299.76 | 0.00 | 0.00 |
March | 782.28 | 661.66 | 671.95 | 299.39 | 372.57 | 0.00 | 0.00 |
April | 1143.69 | 538.05 | 859.08 | 430.85 | 428.24 | 0.00 | 0.00 |
May | 1035.03 | 492.44 | 810.73 | 338.34 | 472.39 | 0.00 | 0.00 |
June | 1104.36 | 392.21 | 805.68 | 349.57 | 456.11 | 0.00 | 0.00 |
July | 1349.03 | 352.53 | 912.90 | 453.64 | 459.25 | 0.00 | 0.00 |
August | 1349.71 | 360.43 | 901.56 | 478.88 | 422.68 | 0.00 | 0.00 |
September | 926.07 | 421.71 | 656.41 | 300.79 | 355.62 | 0.00 | 0.00 |
October | 834.45 | 466.25 | 581.04 | 298.64 | 282.40 | 0.00 | 0.00 |
November | 626.64 | 656.37 | 529.69 | 269.10 | 260.58 | 0.00 | 0.00 |
December | 596.90 | 715.28 | 505.31 | 280.76 | 224.56 | 0.00 | 0.00 |
Annual Sum or Average | 917.35 | 534.14 | 693.59 | 336.82 | 356.77 | 0.00 | 0.00 |
Minimum of Months | 596.90 | 352.53 | 505.31 | 253.42 | 224.56 | 0.00 | 0.00 |
Maximum of Months | 1349.71 | 715.28 | 912.90 | 478.88 | 472.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2802.91 | 1082.39 | 1924.40 | 1411.64 | 512.77 | 0.00 | 0.00 |
February | 2070.94 | 994.33 | 1512.48 | 931.61 | 580.87 | 0.00 | 0.00 |
March | 1625.56 | 1037.33 | 1205.80 | 582.46 | 623.34 | 0.00 | 0.00 |
April | 1454.23 | 861.74 | 1007.47 | 384.16 | 623.31 | 0.00 | 0.00 |
May | 834.82 | 785.24 | 717.40 | 88.29 | 629.11 | 0.00 | 0.00 |
June | 736.92 | 611.31 | 629.35 | 38.00 | 591.35 | 0.00 | 0.00 |
July | 913.37 | 541.40 | 666.65 | 75.05 | 591.61 | 0.00 | 0.00 |
August | 1355.95 | 565.98 | 856.45 | 270.15 | 586.30 | 0.00 | 0.00 |
September | 1888.25 | 663.11 | 1191.75 | 603.90 | 587.85 | 0.00 | 0.00 |
October | 2403.23 | 722.21 | 1515.63 | 1013.24 | 502.39 | 0.00 | 0.00 |
November | 2673.70 | 998.42 | 1842.09 | 1300.49 | 541.60 | 0.00 | 0.00 |
December | 3009.12 | 1087.46 | 2055.88 | 1564.79 | 491.09 | 0.00 | 0.00 |
Annual Sum or Average | 1813.35 | 828.39 | 1259.39 | 687.82 | 571.57 | 0.00 | 0.00 |
Minimum of Months | 736.92 | 541.40 | 629.35 | 38.00 | 491.09 | 0.00 | 0.00 |
Maximum of Months | 3009.12 | 1087.46 | 2055.88 | 1564.79 | 629.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 622.58 | 746.33 | 499.13 | 251.74 | 247.39 | 0.00 | 0.00 |
February | 708.11 | 679.49 | 595.46 | 274.89 | 320.57 | 0.00 | 0.00 |
March | 825.02 | 689.64 | 682.56 | 301.98 | 380.59 | 0.00 | 0.00 |
April | 1289.30 | 567.93 | 940.95 | 489.95 | 451.00 | 0.00 | 0.00 |
May | 1227.17 | 516.39 | 924.31 | 426.94 | 497.37 | 0.00 | 0.00 |
June | 1378.36 | 404.28 | 979.20 | 489.58 | 489.62 | 0.00 | 0.00 |
July | 1540.68 | 363.45 | 1036.56 | 554.66 | 481.91 | 0.00 | 0.00 |
August | 1465.61 | 378.35 | 972.50 | 527.05 | 445.45 | 0.00 | 0.00 |
September | 1211.61 | 437.76 | 832.64 | 445.53 | 387.11 | 0.00 | 0.00 |
October | 946.11 | 490.71 | 636.51 | 347.51 | 289.00 | 0.00 | 0.00 |
November | 735.01 | 685.25 | 574.96 | 300.75 | 274.22 | 0.00 | 0.00 |
December | 645.33 | 753.97 | 507.79 | 272.36 | 235.44 | 0.00 | 0.00 |
Annual Sum or Average | 1051.24 | 558.87 | 765.88 | 390.74 | 375.14 | 0.00 | 0.00 |
Minimum of Months | 622.58 | 363.45 | 499.13 | 251.74 | 235.44 | 0.00 | 0.00 |
Maximum of Months | 1540.68 | 753.97 | 1036.56 | 554.66 | 497.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519910E+09 | 0.277987E+10 | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.00 | 0.00 |
February | 0.556378E+09 | 0.228315E+10 | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.00 | 0.00 |
March | 0.880211E+09 | 0.260636E+10 | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.00 | 0.00 |
April | 0.115938E+10 | 0.201672E+10 | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.00 | 0.00 |
May | 0.152983E+10 | 0.183207E+10 | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.00 | 0.00 |
June | 0.187160E+10 | 0.139707E+10 | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.00 | 0.00 |
July | 0.201679E+10 | 0.129752E+10 | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.00 | 0.00 |
August | 0.161916E+10 | 0.136076E+10 | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.00 | 0.00 |
September | 0.122227E+10 | 0.157784E+10 | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.00 | 0.00 |
October | 0.109708E+10 | 0.182100E+10 | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.00 | 0.00 |
November | 0.569270E+09 | 0.248420E+10 | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.00 | 0.00 |
December | 0.469021E+09 | 0.280790E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135109E+11 | 0.242645E+11 | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.469021E+09 | 0.129752E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Maximum of Months | 0.201679E+10 | 0.280790E+10 | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.171321E+10 | 0.176797E+10 | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.00 | 0.00 |
February | 0.152649E+10 | 0.146268E+10 | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.00 | 0.00 |
March | 0.213583E+10 | 0.166722E+10 | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.00 | 0.00 |
April | 0.298452E+10 | 0.132686E+10 | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.00 | 0.00 |
May | 0.279430E+10 | 0.125897E+10 | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.00 | 0.00 |
June | 0.287313E+10 | 0.975763E+09 | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.00 | 0.00 |
July | 0.361510E+10 | 0.909681E+09 | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.00 | 0.00 |
August | 0.361957E+10 | 0.926501E+09 | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.00 | 0.00 |
September | 0.241371E+10 | 0.103678E+10 | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.00 | 0.00 |
October | 0.225681E+10 | 0.117999E+10 | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.00 | 0.00 |
November | 0.166641E+10 | 0.159000E+10 | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.00 | 0.00 |
December | 0.165068E+10 | 0.178113E+10 | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.292497E+11 | 0.158835E+11 | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152649E+10 | 0.909681E+09 | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361957E+10 | 0.178113E+10 | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755665E+10 | 0.271265E+10 | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.00 | 0.00 |
February | 0.504908E+10 | 0.224231E+10 | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.00 | 0.00 |
March | 0.439018E+10 | 0.261197E+10 | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.00 | 0.00 |
April | 0.378054E+10 | 0.211973E+10 | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.00 | 0.00 |
May | 0.225142E+10 | 0.199697E+10 | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.00 | 0.00 |
June | 0.191286E+10 | 0.151555E+10 | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.00 | 0.00 |
July | 0.243838E+10 | 0.139351E+10 | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.00 | 0.00 |
August | 0.362307E+10 | 0.145194E+10 | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.00 | 0.00 |
September | 0.489535E+10 | 0.163261E+10 | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.00 | 0.00 |
October | 0.645002E+10 | 0.183187E+10 | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.00 | 0.00 |
November | 0.696835E+10 | 0.242917E+10 | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.00 | 0.00 |
December | 0.810987E+10 | 0.272775E+10 | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574258E+11 | 0.246660E+11 | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191286E+10 | 0.139351E+10 | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.810987E+10 | 0.272775E+10 | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.169713E+10 | 0.185337E+10 | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.00 | 0.00 |
February | 0.173900E+10 | 0.152343E+10 | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.00 | 0.00 |
March | 0.223277E+10 | 0.173017E+10 | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.00 | 0.00 |
April | 0.334735E+10 | 0.139579E+10 | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.00 | 0.00 |
May | 0.329227E+10 | 0.131379E+10 | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.00 | 0.00 |
June | 0.356710E+10 | 0.100245E+10 | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.00 | 0.00 |
July | 0.411455E+10 | 0.934888E+09 | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.00 | 0.00 |
August | 0.391547E+10 | 0.970441E+09 | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.00 | 0.00 |
September | 0.314003E+10 | 0.107589E+10 | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.00 | 0.00 |
October | 0.254263E+10 | 0.123843E+10 | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.00 | 0.00 |
November | 0.193005E+10 | 0.165129E+10 | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.00 | 0.00 |
December | 0.175887E+10 | 0.187009E+10 | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.332772E+11 | 0.165600E+11 | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169713E+10 | 0.934888E+09 | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.411455E+10 | 0.187009E+10 | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495516E+09 | 0.296180E+10 | 0.781025E+09 | 0.00 | 0.781025E+09 | 0.00 | 0.00 |
February | 0.559554E+09 | 0.238212E+10 | 0.885517E+09 | 0.00 | 0.885517E+09 | 0.00 | 0.00 |
March | 0.906192E+09 | 0.267880E+10 | 0.120140E+10 | 0.00 | 0.120140E+10 | 0.00 | 0.00 |
April | 0.121021E+10 | 0.203971E+10 | 0.133950E+10 | 5155482.18 | 0.133435E+10 | 0.00 | 0.00 |
May | 0.158024E+10 | 0.186007E+10 | 0.166331E+10 | 77451885.80 | 0.158585E+10 | 0.00 | 0.00 |
June | 0.194303E+10 | 0.139827E+10 | 0.171517E+10 | 0.167685E+09 | 0.154748E+10 | 0.00 | 0.00 |
July | 0.208084E+10 | 0.130640E+10 | 0.167813E+10 | 0.140653E+09 | 0.153747E+10 | 0.00 | 0.00 |
August | 0.166956E+10 | 0.137147E+10 | 0.139363E+10 | 27905723.97 | 0.136572E+10 | 0.00 | 0.00 |
September | 0.124867E+10 | 0.162263E+10 | 0.114151E+10 | 178917.66 | 0.114133E+10 | 0.00 | 0.00 |
October | 0.110024E+10 | 0.190642E+10 | 0.935668E+09 | 0.00 | 0.935668E+09 | 0.00 | 0.00 |
November | 0.546865E+09 | 0.264958E+10 | 0.819851E+09 | 0.00 | 0.819851E+09 | 0.00 | 0.00 |
December | 0.443432E+09 | 0.299134E+10 | 0.727067E+09 | 0.00 | 0.727067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.137844E+11 | 0.251686E+11 | 0.142818E+11 | 0.419030E+09 | 0.138627E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443432E+09 | 0.130640E+10 | 0.727067E+09 | 0.00 | 0.727067E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208084E+10 | 0.299134E+10 | 0.171517E+10 | 0.167685E+09 | 0.158585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168445E+10 | 0.191719E+10 | 0.140451E+10 | 0.751164E+09 | 0.653349E+09 | 0.00 | 0.00 |
February | 0.152370E+10 | 0.155301E+10 | 0.133823E+10 | 0.613053E+09 | 0.725181E+09 | 0.00 | 0.00 |
March | 0.214503E+10 | 0.174590E+10 | 0.179973E+10 | 0.801859E+09 | 0.997871E+09 | 0.00 | 0.00 |
April | 0.301343E+10 | 0.138122E+10 | 0.222671E+10 | 0.111674E+10 | 0.110998E+10 | 0.00 | 0.00 |
May | 0.282478E+10 | 0.130357E+10 | 0.217143E+10 | 0.906183E+09 | 0.126524E+10 | 0.00 | 0.00 |
June | 0.291443E+10 | 0.993989E+09 | 0.208829E+10 | 0.906070E+09 | 0.118223E+10 | 0.00 | 0.00 |
July | 0.365331E+10 | 0.942227E+09 | 0.244507E+10 | 0.121501E+10 | 0.123006E+10 | 0.00 | 0.00 |
August | 0.365346E+10 | 0.965103E+09 | 0.241470E+10 | 0.128260E+10 | 0.113210E+10 | 0.00 | 0.00 |
September | 0.243159E+10 | 0.109094E+10 | 0.170138E+10 | 0.779635E+09 | 0.921749E+09 | 0.00 | 0.00 |
October | 0.226159E+10 | 0.125653E+10 | 0.155624E+10 | 0.799862E+09 | 0.756374E+09 | 0.00 | 0.00 |
November | 0.164611E+10 | 0.171691E+10 | 0.137293E+10 | 0.697501E+09 | 0.675426E+09 | 0.00 | 0.00 |
December | 0.162207E+10 | 0.192518E+10 | 0.135341E+10 | 0.751963E+09 | 0.601442E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.293740E+11 | 0.167918E+11 | 0.218726E+11 | 0.106216E+11 | 0.112510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.152370E+10 | 0.942227E+09 | 0.133823E+10 | 0.613053E+09 | 0.601442E+09 | 0.00 | 0.00 |
Maximum of Months | 0.365346E+10 | 0.192518E+10 | 0.244507E+10 | 0.128260E+10 | 0.126524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754872E+10 | 0.299668E+10 | 0.515412E+10 | 0.378078E+10 | 0.137335E+10 | 0.00 | 0.00 |
February | 0.508566E+10 | 0.240703E+10 | 0.365885E+10 | 0.225365E+10 | 0.140520E+10 | 0.00 | 0.00 |
March | 0.445637E+10 | 0.271167E+10 | 0.322949E+10 | 0.155999E+10 | 0.166950E+10 | 0.00 | 0.00 |
April | 0.385111E+10 | 0.216563E+10 | 0.261129E+10 | 0.995700E+09 | 0.161559E+10 | 0.00 | 0.00 |
May | 0.234164E+10 | 0.200102E+10 | 0.192142E+10 | 0.236455E+09 | 0.168497E+10 | 0.00 | 0.00 |
June | 0.200864E+10 | 0.148594E+10 | 0.163123E+10 | 98486347.79 | 0.153274E+10 | 0.00 | 0.00 |
July | 0.251402E+10 | 0.139311E+10 | 0.178552E+10 | 0.200995E+09 | 0.158452E+10 | 0.00 | 0.00 |
August | 0.369003E+10 | 0.148123E+10 | 0.229385E+10 | 0.723543E+09 | 0.157030E+10 | 0.00 | 0.00 |
September | 0.494100E+10 | 0.172556E+10 | 0.308891E+10 | 0.156525E+10 | 0.152366E+10 | 0.00 | 0.00 |
October | 0.647243E+10 | 0.198802E+10 | 0.405931E+10 | 0.271375E+10 | 0.134556E+10 | 0.00 | 0.00 |
November | 0.697821E+10 | 0.266874E+10 | 0.477452E+10 | 0.337073E+10 | 0.140379E+10 | 0.00 | 0.00 |
December | 0.810734E+10 | 0.301131E+10 | 0.550625E+10 | 0.419097E+10 | 0.131528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579952E+11 | 0.260359E+11 | 0.397148E+11 | 0.216903E+11 | 0.180245E+11 | 0.00 | 0.00 |
Minimum of Months | 0.200864E+10 | 0.139311E+10 | 0.163123E+10 | 98486347.79 | 0.131528E+10 | 0.00 | 0.00 |
Maximum of Months | 0.810734E+10 | 0.301131E+10 | 0.550625E+10 | 0.419097E+10 | 0.168497E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168820E+10 | 0.201433E+10 | 0.133685E+10 | 0.674246E+09 | 0.662607E+09 | 0.00 | 0.00 |
February | 0.174816E+10 | 0.162919E+10 | 0.144053E+10 | 0.665014E+09 | 0.775516E+09 | 0.00 | 0.00 |
March | 0.225677E+10 | 0.182586E+10 | 0.182815E+10 | 0.808800E+09 | 0.101935E+10 | 0.00 | 0.00 |
April | 0.338728E+10 | 0.146653E+10 | 0.243891E+10 | 0.126993E+10 | 0.116898E+10 | 0.00 | 0.00 |
May | 0.333440E+10 | 0.137914E+10 | 0.247563E+10 | 0.114349E+10 | 0.133215E+10 | 0.00 | 0.00 |
June | 0.362155E+10 | 0.103743E+10 | 0.253806E+10 | 0.126898E+10 | 0.126908E+10 | 0.00 | 0.00 |
July | 0.416272E+10 | 0.978701E+09 | 0.277630E+10 | 0.148557E+10 | 0.129073E+10 | 0.00 | 0.00 |
August | 0.395985E+10 | 0.101865E+10 | 0.260471E+10 | 0.141164E+10 | 0.119307E+10 | 0.00 | 0.00 |
September | 0.316889E+10 | 0.114672E+10 | 0.215817E+10 | 0.115480E+10 | 0.100337E+10 | 0.00 | 0.00 |
October | 0.255469E+10 | 0.132921E+10 | 0.170482E+10 | 0.930755E+09 | 0.774063E+09 | 0.00 | 0.00 |
November | 0.192369E+10 | 0.180116E+10 | 0.149028E+10 | 0.779521E+09 | 0.710763E+09 | 0.00 | 0.00 |
December | 0.174891E+10 | 0.203382E+10 | 0.136005E+10 | 0.729465E+09 | 0.630585E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335551E+11 | 0.176607E+11 | 0.241525E+11 | 0.123222E+11 | 0.118303E+11 | 0.00 | 0.00 |
Minimum of Months | 0.168820E+10 | 0.978701E+09 | 0.133685E+10 | 0.665014E+09 | 0.630585E+09 | 0.00 | 0.00 |
Maximum of Months | 0.416272E+10 | 0.203382E+10 | 0.277630E+10 | 0.148557E+10 | 0.133215E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.469706E+09 | 0.300964E+10 | 0.781040E+09 | 0.00 | 0.781040E+09 | 0.00 | 0.00 |
February | 0.511338E+09 | 0.247289E+10 | 0.885535E+09 | 0.00 | 0.885535E+09 | 0.00 | 0.00 |
March | 0.836376E+09 | 0.278745E+10 | 0.120142E+10 | 0.00 | 0.120142E+10 | 0.00 | 0.00 |
April | 0.113903E+10 | 0.213474E+10 | 0.133953E+10 | 5155633.71 | 0.133437E+10 | 0.00 | 0.00 |
May | 0.150132E+10 | 0.192858E+10 | 0.166334E+10 | 77454162.39 | 0.158589E+10 | 0.00 | 0.00 |
June | 0.186570E+10 | 0.146057E+10 | 0.171520E+10 | 0.167689E+09 | 0.154751E+10 | 0.00 | 0.00 |
July | 0.202256E+10 | 0.135159E+10 | 0.167816E+10 | 0.140657E+09 | 0.153750E+10 | 0.00 | 0.00 |
August | 0.161985E+10 | 0.142401E+10 | 0.139365E+10 | 27906544.22 | 0.136575E+10 | 0.00 | 0.00 |
September | 0.121106E+10 | 0.166993E+10 | 0.114153E+10 | 178922.92 | 0.114135E+10 | 0.00 | 0.00 |
October | 0.107510E+10 | 0.194034E+10 | 0.935685E+09 | 0.00 | 0.935685E+09 | 0.00 | 0.00 |
November | 0.523529E+09 | 0.268239E+10 | 0.819867E+09 | 0.00 | 0.819867E+09 | 0.00 | 0.00 |
December | 0.417550E+09 | 0.304702E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131931E+11 | 0.259091E+11 | 0.142820E+11 | 0.419042E+09 | 0.138630E+11 | 0.00 | 0.00 |
Minimum of Months | 0.417550E+09 | 0.135159E+10 | 0.727081E+09 | 0.00 | 0.727081E+09 | 0.00 | 0.00 |
Maximum of Months | 0.202256E+10 | 0.304702E+10 | 0.171520E+10 | 0.167689E+09 | 0.158589E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166334E+10 | 0.189992E+10 | 0.140453E+10 | 0.751178E+09 | 0.653357E+09 | 0.00 | 0.00 |
February | 0.148505E+10 | 0.157384E+10 | 0.133826E+10 | 0.613065E+09 | 0.725190E+09 | 0.00 | 0.00 |
March | 0.209527E+10 | 0.177219E+10 | 0.179976E+10 | 0.801874E+09 | 0.997884E+09 | 0.00 | 0.00 |
April | 0.296443E+10 | 0.139463E+10 | 0.222674E+10 | 0.111676E+10 | 0.110999E+10 | 0.00 | 0.00 |
May | 0.277221E+10 | 0.131896E+10 | 0.217146E+10 | 0.906200E+09 | 0.126526E+10 | 0.00 | 0.00 |
June | 0.286251E+10 | 0.101661E+10 | 0.208833E+10 | 0.906087E+09 | 0.118224E+10 | 0.00 | 0.00 |
July | 0.361324E+10 | 0.944217E+09 | 0.244511E+10 | 0.121504E+10 | 0.123007E+10 | 0.00 | 0.00 |
August | 0.361507E+10 | 0.965364E+09 | 0.241474E+10 | 0.128263E+10 | 0.113211E+10 | 0.00 | 0.00 |
September | 0.240037E+10 | 0.109307E+10 | 0.170141E+10 | 0.779650E+09 | 0.921759E+09 | 0.00 | 0.00 |
October | 0.223500E+10 | 0.124881E+10 | 0.155626E+10 | 0.799878E+09 | 0.756383E+09 | 0.00 | 0.00 |
November | 0.162425E+10 | 0.170131E+10 | 0.137295E+10 | 0.697515E+09 | 0.675434E+09 | 0.00 | 0.00 |
December | 0.159872E+10 | 0.191582E+10 | 0.135343E+10 | 0.751978E+09 | 0.601449E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.289295E+11 | 0.168447E+11 | 0.218730E+11 | 0.106219E+11 | 0.112511E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148505E+10 | 0.944217E+09 | 0.133826E+10 | 0.613065E+09 | 0.601449E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361507E+10 | 0.191582E+10 | 0.244511E+10 | 0.128263E+10 | 0.126526E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.750731E+10 | 0.289908E+10 | 0.515432E+10 | 0.378093E+10 | 0.137339E+10 | 0.00 | 0.00 |
February | 0.501001E+10 | 0.240549E+10 | 0.365899E+10 | 0.225374E+10 | 0.140524E+10 | 0.00 | 0.00 |
March | 0.435391E+10 | 0.277839E+10 | 0.322961E+10 | 0.156005E+10 | 0.166956E+10 | 0.00 | 0.00 |
April | 0.376935E+10 | 0.223363E+10 | 0.261137E+10 | 0.995742E+09 | 0.161563E+10 | 0.00 | 0.00 |
May | 0.223597E+10 | 0.210319E+10 | 0.192148E+10 | 0.236465E+09 | 0.168502E+10 | 0.00 | 0.00 |
June | 0.191009E+10 | 0.158451E+10 | 0.163127E+10 | 98490434.89 | 0.153278E+10 | 0.00 | 0.00 |
July | 0.244637E+10 | 0.145010E+10 | 0.178557E+10 | 0.201004E+09 | 0.158456E+10 | 0.00 | 0.00 |
August | 0.363179E+10 | 0.151593E+10 | 0.229392E+10 | 0.723573E+09 | 0.157034E+10 | 0.00 | 0.00 |
September | 0.489436E+10 | 0.171877E+10 | 0.308902E+10 | 0.156531E+10 | 0.152371E+10 | 0.00 | 0.00 |
October | 0.643682E+10 | 0.193438E+10 | 0.405946E+10 | 0.271386E+10 | 0.134560E+10 | 0.00 | 0.00 |
November | 0.693022E+10 | 0.258790E+10 | 0.477471E+10 | 0.337087E+10 | 0.140384E+10 | 0.00 | 0.00 |
December | 0.805963E+10 | 0.291265E+10 | 0.550647E+10 | 0.419114E+10 | 0.131533E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.571858E+11 | 0.261240E+11 | 0.397162E+11 | 0.216912E+11 | 0.180250E+11 | 0.00 | 0.00 |
Minimum of Months | 0.191009E+10 | 0.145010E+10 | 0.163127E+10 | 98490434.89 | 0.131533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.805963E+10 | 0.291265E+10 | 0.550647E+10 | 0.419114E+10 | 0.168502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166753E+10 | 0.199896E+10 | 0.133687E+10 | 0.674258E+09 | 0.662614E+09 | 0.00 | 0.00 |
February | 0.171306E+10 | 0.164382E+10 | 0.144055E+10 | 0.665024E+09 | 0.775524E+09 | 0.00 | 0.00 |
March | 0.220973E+10 | 0.184713E+10 | 0.182817E+10 | 0.808813E+09 | 0.101936E+10 | 0.00 | 0.00 |
April | 0.334187E+10 | 0.147208E+10 | 0.243894E+10 | 0.126995E+10 | 0.116899E+10 | 0.00 | 0.00 |
May | 0.328685E+10 | 0.138310E+10 | 0.247567E+10 | 0.114351E+10 | 0.133216E+10 | 0.00 | 0.00 |
June | 0.357270E+10 | 0.104790E+10 | 0.253809E+10 | 0.126900E+10 | 0.126909E+10 | 0.00 | 0.00 |
July | 0.412656E+10 | 0.973474E+09 | 0.277633E+10 | 0.148559E+10 | 0.129074E+10 | 0.00 | 0.00 |
August | 0.392548E+10 | 0.101336E+10 | 0.260474E+10 | 0.141166E+10 | 0.119308E+10 | 0.00 | 0.00 |
September | 0.314049E+10 | 0.113468E+10 | 0.215820E+10 | 0.115482E+10 | 0.100338E+10 | 0.00 | 0.00 |
October | 0.253406E+10 | 0.131433E+10 | 0.170484E+10 | 0.930770E+09 | 0.774070E+09 | 0.00 | 0.00 |
November | 0.190514E+10 | 0.177616E+10 | 0.149030E+10 | 0.779534E+09 | 0.710770E+09 | 0.00 | 0.00 |
December | 0.172845E+10 | 0.201943E+10 | 0.136007E+10 | 0.729477E+09 | 0.630591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.331519E+11 | 0.176244E+11 | 0.241528E+11 | 0.123224E+11 | 0.118304E+11 | 0.00 | 0.00 |
Minimum of Months | 0.166753E+10 | 0.973474E+09 | 0.133687E+10 | 0.665024E+09 | 0.630591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.412656E+10 | 0.201943E+10 | 0.277633E+10 | 0.148559E+10 | 0.133216E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.425505E+10 | -0.402133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233717268.1 | 60.05 | 0.00 | 0.00 |
February | 0.387008E+10 | -0.365887E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -211215772.6 | 60.05 | 0.00 | 0.00 |
March | 0.451941E+10 | -0.428537E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -234037724.8 | 60.05 | 0.00 | 0.00 |
April | 0.400331E+10 | -0.377777E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225547869.6 | 60.05 | 0.00 | 0.00 |
May | 0.418417E+10 | -0.395126E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232905768.9 | 60.05 | 0.00 | 0.00 |
June | 0.406356E+10 | -0.383830E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225261825.4 | 60.05 | 0.00 | 0.00 |
July | 0.379555E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231927017.1 | 60.05 | 0.00 | 0.00 |
August | 0.416782E+10 | -0.393536E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232464238.1 | 60.05 | 0.00 | 0.00 |
September | 0.380962E+10 | -0.358509E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224535622.2 | 60.05 | 0.00 | 0.00 |
October | 0.401643E+10 | -0.378454E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231895708.2 | 60.05 | 0.00 | 0.00 |
November | 0.404281E+10 | -0.381753E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225282311.8 | 60.05 | 0.00 | 0.00 |
December | 0.409430E+10 | -0.386073E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233571777.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.488221E+11 | -0.460798E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.274236E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.379555E+10 | -0.428537E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -234037724.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.451941E+10 | -0.356362E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -211215772.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7832.42 | 37.26 | 285.00 | 280.00 | 1727.28 | 25.87 | 168.33 | 265.17 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6938.87 | 35.51 | 275.33 | 274.67 | 1228.26 | 21.05 | 138.17 | 244.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:00 | 2038.98 | 18.81 | 11.17 | 315.00 | 998.96 | 20.30 | 148.17 | 286.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1322.42 | 18.00 | 0.00 | 332.50 | 812.61 | 20.19 | 92.50 | 296.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1129.36 | 17.83 | 0.00 | 364.00 | 654.31 | 19.99 | 59.67 | 320.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 998.22 | 17.49 | 0.00 | 355.17 | 595.83 | 19.68 | 20.50 | 308.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 1005.78 | 17.53 | 0.00 | 364.50 | 620.46 | 19.75 | 24.17 | 328.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1133.72 | 17.65 | 0.00 | 353.67 | 710.58 | 19.84 | 48.00 | 315.67 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1617.09 | 18.45 | 11.00 | 308.67 | 947.17 | 20.19 | 87.67 | 277.50 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3495.50 | 24.53 | 115.83 | 303.00 | 1184.76 | 20.85 | 83.17 | 276.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7573.72 | 36.89 | 292.67 | 279.17 | 1551.51 | 25.54 | 179.17 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:10 | 7695.12 | 37.38 | 286.17 | 281.00 | 2197.90 | 28.82 | 181.17 | 271.50 |
Annual Sum or Average | 4065.67 | 0.51 | 3247.95 | 23.84 | 1277.17 | 3811.33 | 1051.64 | 21.60 | 1230.67 | 3460.50 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 998.22 | 17.49 | 0.00 | 274.67 | 595.83 | 19.68 | 20.50 | 244.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7832.42 | 37.38 | 292.67 | 364.50 | 2197.90 | 28.82 | 181.17 | 328.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1711.29 | 21.62 | 85.00 | 264.67 | 876.70 | 22.17 | 61.17 | 222.50 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-06:00 | 1838.67 | 20.32 | 70.83 | 266.83 | 986.49 | 22.44 | 55.83 | 220.50 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:40 | 2279.31 | 21.60 | 106.50 | 315.83 | 1255.39 | 22.50 | 77.67 | 274.17 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2266.40 | 19.28 | 77.33 | 336.50 | 1230.04 | 21.78 | 65.17 | 305.00 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2224.65 | 20.06 | 99.50 | 376.33 | 1216.95 | 21.33 | 69.33 | 328.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2214.66 | 19.23 | 88.83 | 367.00 | 947.49 | 19.38 | 36.33 | 321.67 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2443.17 | 19.72 | 99.67 | 375.83 | 1295.37 | 20.90 | 68.67 | 337.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-06:49 | 2459.74 | 20.45 | 102.17 | 362.17 | 1261.43 | 21.46 | 69.67 | 324.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2556.09 | 20.46 | 92.83 | 311.00 | 977.13 | 20.47 | 43.83 | 272.17 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2330.35 | 20.93 | 88.83 | 281.83 | 963.48 | 20.41 | 42.67 | 233.67 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1948.07 | 21.87 | 95.17 | 262.50 | 1058.65 | 22.48 | 68.50 | 228.33 |
December | 297.00 | 0.51 | 0.48 | 01-DEC-07:10 | 1689.01 | 21.24 | 86.17 | 263.83 | 874.95 | 21.70 | 63.33 | 220.00 |
Annual Sum or Average | 4065.67 | 0.51 | 2187.88 | 20.49 | 1092.83 | 3784.33 | 1093.28 | 21.37 | 722.17 | 3288.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1689.01 | 19.23 | 70.83 | 262.50 | 874.95 | 19.38 | 36.33 | 220.00 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2556.09 | 21.87 | 106.50 | 376.33 | 1295.37 | 22.50 | 77.67 | 337.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:39 | 524.21 | 15.16 | 0.00 | 232.67 | 341.95 | 17.77 | 0.00 | 151.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 628.73 | 16.00 | 0.00 | 246.67 | 387.82 | 18.32 | 0.00 | 171.83 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-07:00 | 737.31 | 16.41 | 0.00 | 305.50 | 442.33 | 18.54 | 0.00 | 248.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 816.63 | 17.64 | 0.00 | 335.83 | 521.05 | 19.83 | 6.00 | 295.83 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1025.83 | 18.30 | 0.00 | 381.17 | 599.53 | 20.48 | 72.00 | 352.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1084.76 | 20.13 | 42.50 | 374.17 | 648.57 | 22.22 | 125.50 | 341.00 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:40 | 1015.34 | 20.05 | 45.17 | 384.33 | 599.68 | 20.58 | 100.83 | 361.00 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 838.05 | 17.74 | 0.00 | 364.67 | 537.53 | 19.92 | 29.67 | 337.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 729.23 | 16.91 | 0.00 | 303.67 | 468.48 | 19.17 | 0.00 | 257.00 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 556.60 | 15.40 | 0.00 | 258.00 | 365.40 | 17.84 | 0.00 | 170.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:40 | 532.80 | 14.81 | 0.00 | 236.67 | 344.35 | 17.28 | 0.00 | 159.83 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 476.51 | 14.42 | 0.00 | 225.67 | 316.69 | 17.10 | 0.00 | 130.17 |
Annual Sum or Average | 4065.67 | 0.52 | 771.63 | 17.13 | 87.67 | 3649.00 | 477.90 | 19.25 | 334.00 | 2975.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 476.51 | 14.42 | 0.00 | 225.67 | 316.69 | 17.10 | 0.00 | 130.17 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1084.76 | 20.13 | 45.17 | 384.33 | 648.57 | 22.22 | 125.50 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:39 | 2224.16 | 22.52 | 105.17 | 251.33 | 841.22 | 21.22 | 50.50 | 209.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-08:39 | 1998.84 | 20.27 | 73.50 | 252.83 | 1100.46 | 22.51 | 60.00 | 213.67 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2273.72 | 21.00 | 100.17 | 309.17 | 1235.50 | 21.93 | 71.67 | 266.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 3145.38 | 19.47 | 82.33 | 330.33 | 1189.84 | 17.70 | 0.00 | 297.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-07:10 | 2922.63 | 17.04 | 52.50 | 365.17 | 1199.28 | 17.85 | 0.00 | 328.17 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2493.51 | 14.27 | 0.00 | 360.67 | 1359.22 | 17.81 | 0.00 | 323.17 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2631.09 | 14.38 | 5.67 | 369.83 | 1403.31 | 17.72 | 0.00 | 341.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:30 | 3238.01 | 19.13 | 88.17 | 352.83 | 1327.46 | 17.90 | 7.00 | 323.67 |
September | 328.83 | 0.50 | 0.48 | 01-SEP-07:19 | 2798.59 | 21.85 | 101.83 | 303.83 | 1499.81 | 22.47 | 71.83 | 269.33 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2078.48 | 20.51 | 81.83 | 284.17 | 1093.65 | 21.08 | 52.50 | 237.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2171.83 | 22.40 | 104.33 | 253.50 | 1194.15 | 22.95 | 75.17 | 213.17 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:20 | 1973.67 | 22.38 | 104.67 | 245.50 | 1096.13 | 22.96 | 80.17 | 197.17 |
Annual Sum or Average | 4065.67 | 0.51 | 2538.89 | 19.30 | 900.17 | 3679.17 | 1225.34 | 20.09 | 468.83 | 3220.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1973.67 | 14.27 | 0.00 | 245.50 | 841.22 | 17.70 | 0.00 | 197.17 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3238.01 | 22.52 | 105.17 | 369.83 | 1499.81 | 22.96 | 80.17 | 341.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7679.41 | 36.96 | 284.83 | 279.00 | 1605.83 | 23.48 | 97.33 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6821.35 | 35.28 | 275.33 | 274.00 | 1176.54 | 21.68 | 61.00 | 251.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1950.24 | 15.05 | 11.17 | 314.00 | 937.43 | 17.95 | 5.33 | 282.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1260.39 | 14.39 | 0.00 | 331.50 | 769.02 | 17.96 | 0.00 | 293.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1085.92 | 14.28 | 0.00 | 361.33 | 627.65 | 17.76 | 0.00 | 315.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 962.08 | 14.02 | 0.00 | 353.50 | 574.94 | 17.53 | 0.00 | 303.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 967.85 | 14.17 | 0.00 | 362.50 | 598.20 | 17.71 | 0.00 | 323.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1083.49 | 14.22 | 0.00 | 351.33 | 676.93 | 17.76 | 0.00 | 311.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1536.74 | 14.77 | 11.00 | 307.00 | 886.05 | 17.80 | 2.00 | 274.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3387.63 | 21.86 | 115.67 | 302.50 | 1093.29 | 18.18 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7433.59 | 36.65 | 292.67 | 278.50 | 1440.58 | 23.10 | 92.67 | 269.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7537.30 | 37.03 | 285.67 | 279.33 | 2069.65 | 26.75 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3163.52 | 21.30 | 1276.33 | 3794.50 | 991.19 | 19.53 | 415.33 | 3432.17 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 962.08 | 14.02 | 0.00 | 274.00 | 574.94 | 17.53 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7679.41 | 37.03 | 292.67 | 362.50 | 2069.65 | 26.75 | 143.00 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1660.04 | 21.12 | 85.00 | 263.50 | 836.82 | 21.95 | 56.83 | 218.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-06:00 | 1784.26 | 19.82 | 70.83 | 264.83 | 943.46 | 22.23 | 54.83 | 216.33 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:49 | 2223.24 | 21.15 | 106.50 | 313.33 | 1210.03 | 22.31 | 77.67 | 269.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2196.50 | 18.79 | 77.33 | 334.67 | 1174.99 | 21.60 | 65.17 | 301.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2159.87 | 19.59 | 99.33 | 375.33 | 1170.45 | 21.15 | 69.33 | 323.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2157.25 | 18.76 | 88.83 | 363.83 | 902.00 | 19.20 | 36.33 | 316.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2374.83 | 19.24 | 99.17 | 372.83 | 1243.39 | 20.73 | 68.67 | 334.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2342.57 | 18.65 | 85.67 | 357.67 | 1207.00 | 21.29 | 69.67 | 322.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2502.44 | 19.99 | 92.83 | 309.50 | 932.73 | 20.27 | 43.83 | 268.33 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2248.50 | 20.00 | 85.00 | 278.50 | 921.03 | 20.19 | 42.67 | 229.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1831.29 | 19.64 | 79.50 | 258.33 | 1018.21 | 22.27 | 66.33 | 223.83 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-07:10 | 1640.23 | 20.74 | 86.17 | 261.67 | 835.00 | 21.47 | 58.83 | 215.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2117.35 | 19.72 | 1056.17 | 3754.00 | 1047.01 | 21.17 | 710.17 | 3239.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1640.23 | 18.65 | 70.83 | 258.33 | 835.00 | 19.20 | 36.33 | 215.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2502.44 | 21.15 | 106.50 | 375.33 | 1243.39 | 22.31 | 77.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-08:50 | 504.49 | 11.55 | 0.00 | 228.50 | 331.81 | 15.46 | 0.00 | 140.33 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 606.04 | 12.52 | 0.00 | 244.00 | 375.70 | 16.14 | 0.00 | 163.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:09 | 711.77 | 13.06 | 0.00 | 303.17 | 428.44 | 16.49 | 0.00 | 240.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 788.81 | 14.36 | 0.00 | 334.83 | 506.71 | 17.95 | 0.00 | 292.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 990.55 | 14.75 | 0.00 | 380.17 | 579.71 | 18.35 | 0.00 | 348.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1047.42 | 16.94 | 42.50 | 373.67 | 627.25 | 20.21 | 41.17 | 338.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 980.48 | 16.99 | 45.17 | 382.67 | 580.49 | 18.56 | 0.00 | 358.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 809.59 | 14.48 | 0.00 | 364.00 | 522.83 | 18.11 | 0.00 | 333.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 704.16 | 13.61 | 0.00 | 301.50 | 455.61 | 17.20 | 0.00 | 252.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 537.86 | 11.96 | 0.00 | 253.50 | 356.01 | 15.72 | 0.00 | 161.50 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-07:49 | 513.14 | 11.39 | 0.00 | 232.33 | 334.19 | 15.08 | 0.00 | 149.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 458.19 | 10.88 | 0.00 | 219.00 | 307.38 | 14.77 | 0.00 | 118.67 |
Annual Sum or Average | 4065.67 | 0.52 | 744.74 | 13.77 | 87.67 | 3617.33 | 463.50 | 17.18 | 41.17 | 2898.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 458.19 | 10.88 | 0.00 | 219.00 | 307.38 | 14.77 | 0.00 | 118.67 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1047.42 | 16.99 | 45.17 | 382.67 | 627.25 | 20.21 | 41.17 | 358.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2172.20 | 22.13 | 105.17 | 248.50 | 801.37 | 21.11 | 49.33 | 207.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 1938.76 | 19.84 | 73.50 | 251.00 | 1053.72 | 22.40 | 60.00 | 210.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2215.63 | 20.59 | 100.17 | 307.17 | 1188.40 | 21.81 | 71.67 | 263.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 3069.55 | 19.00 | 82.33 | 329.00 | 1130.42 | 17.54 | 0.00 | 294.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2844.04 | 16.54 | 52.50 | 363.17 | 1144.46 | 17.67 | 0.00 | 323.67 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2420.05 | 13.73 | 0.00 | 359.50 | 1300.74 | 17.62 | 0.00 | 320.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2550.16 | 13.86 | 5.67 | 368.00 | 1343.45 | 17.54 | 0.00 | 339.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:40 | 3154.91 | 18.67 | 88.17 | 350.00 | 1267.83 | 17.74 | 7.00 | 321.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:19 | 2728.90 | 21.43 | 101.83 | 302.33 | 1440.28 | 22.35 | 71.83 | 266.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2018.18 | 20.08 | 81.83 | 280.67 | 1044.04 | 20.96 | 52.50 | 234.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2107.96 | 21.74 | 101.83 | 251.83 | 1150.51 | 22.85 | 75.00 | 209.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:30 | 1856.15 | 20.22 | 88.17 | 239.83 | 1056.57 | 22.86 | 79.17 | 193.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2465.55 | 18.70 | 881.17 | 3651.00 | 1173.02 | 19.94 | 466.50 | 3184.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1856.15 | 13.73 | 0.00 | 239.83 | 801.37 | 17.54 | 0.00 | 193.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3154.91 | 22.13 | 105.17 | 368.00 | 1440.28 | 22.86 | 79.17 | 339.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.49 | 0.48 | 01-JAN-07:19 | 7679.38 | 36.96 | 284.83 | 279.00 | 1605.75 | 23.48 | 97.33 | 264.67 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 6821.27 | 35.28 | 275.33 | 274.00 | 1176.46 | 21.68 | 61.00 | 251.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 1950.15 | 15.05 | 11.17 | 314.00 | 937.36 | 17.95 | 5.33 | 282.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:00 | 1260.33 | 14.39 | 0.00 | 331.50 | 768.97 | 17.96 | 0.00 | 293.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:40 | 1085.87 | 14.28 | 0.00 | 361.33 | 627.60 | 17.76 | 0.00 | 315.67 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:40 | 962.04 | 14.02 | 0.00 | 353.50 | 574.90 | 17.53 | 0.00 | 303.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:19 | 967.82 | 14.18 | 0.00 | 362.50 | 598.16 | 17.71 | 0.00 | 323.50 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:10 | 1083.45 | 14.22 | 0.00 | 351.33 | 676.89 | 17.76 | 0.00 | 311.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1536.68 | 14.78 | 11.00 | 307.00 | 885.99 | 17.80 | 2.00 | 274.67 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3387.56 | 21.86 | 115.67 | 302.50 | 1093.23 | 18.18 | 14.00 | 272.83 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7433.54 | 36.65 | 292.67 | 278.50 | 1440.50 | 23.10 | 92.67 | 269.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7537.29 | 37.03 | 285.67 | 279.33 | 2069.58 | 26.75 | 143.00 | 270.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3163.47 | 21.30 | 1276.33 | 3794.50 | 991.13 | 19.53 | 415.33 | 3432.17 | ||
Minimum of Months | 279.67 | 0.49 | 0.48 | 962.04 | 14.02 | 0.00 | 274.00 | 574.90 | 17.53 | 0.00 | 251.50 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7679.38 | 37.03 | 292.67 | 362.50 | 2069.58 | 26.75 | 143.00 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.51 | 0.48 | 01-JAN-07:19 | 1660.03 | 21.13 | 85.00 | 263.50 | 836.78 | 21.95 | 56.83 | 218.50 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-06:00 | 1784.24 | 19.82 | 70.83 | 264.83 | 943.42 | 22.23 | 54.83 | 216.33 |
March | 338.17 | 0.51 | 0.48 | 01-MAR-06:49 | 2223.19 | 21.15 | 106.50 | 313.33 | 1209.97 | 22.31 | 77.67 | 269.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-05:00 | 2196.47 | 18.80 | 77.33 | 334.67 | 1174.94 | 21.60 | 65.17 | 301.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:10 | 2159.82 | 19.59 | 99.33 | 375.33 | 1170.40 | 21.15 | 69.33 | 323.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2157.21 | 18.76 | 88.83 | 363.83 | 901.95 | 19.20 | 36.33 | 316.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:19 | 2374.80 | 19.24 | 99.17 | 372.83 | 1243.34 | 20.73 | 68.67 | 334.67 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2342.55 | 18.65 | 85.67 | 357.67 | 1206.95 | 21.29 | 69.67 | 322.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2502.41 | 19.99 | 92.83 | 309.50 | 932.68 | 20.27 | 43.83 | 268.33 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2248.49 | 20.00 | 85.00 | 278.50 | 920.99 | 20.19 | 42.67 | 229.83 |
November | 300.00 | 0.52 | 0.48 | 01-NOV-06:40 | 1831.28 | 19.64 | 79.50 | 258.33 | 1018.17 | 22.27 | 66.33 | 223.83 |
December | 297.00 | 0.52 | 0.48 | 01-DEC-07:10 | 1640.22 | 20.74 | 86.17 | 261.67 | 834.97 | 21.47 | 58.83 | 215.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2117.32 | 19.72 | 1056.17 | 3754.00 | 1046.96 | 21.17 | 710.17 | 3239.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1640.22 | 18.65 | 70.83 | 258.33 | 834.97 | 19.20 | 36.33 | 215.33 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 2502.41 | 21.15 | 106.50 | 375.33 | 1243.34 | 22.31 | 77.67 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.54 | 0.48 | 01-JAN-08:50 | 504.48 | 11.55 | 0.00 | 228.50 | 331.79 | 15.46 | 0.00 | 140.33 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 606.03 | 12.53 | 0.00 | 244.00 | 375.68 | 16.14 | 0.00 | 163.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:09 | 711.75 | 13.06 | 0.00 | 303.17 | 428.41 | 16.49 | 0.00 | 240.83 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 788.80 | 14.36 | 0.00 | 334.83 | 506.68 | 17.95 | 0.00 | 292.33 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:30 | 990.52 | 14.75 | 0.00 | 380.17 | 579.67 | 18.35 | 0.00 | 348.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1047.39 | 16.94 | 42.50 | 373.67 | 627.22 | 20.21 | 41.17 | 338.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 980.46 | 17.00 | 45.17 | 382.67 | 580.46 | 18.56 | 0.00 | 358.50 |
August | 390.67 | 0.50 | 0.48 | 01-AUG-07:10 | 809.58 | 14.48 | 0.00 | 364.00 | 522.81 | 18.11 | 0.00 | 333.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 704.14 | 13.62 | 0.00 | 301.50 | 455.59 | 17.20 | 0.00 | 252.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 537.85 | 11.96 | 0.00 | 253.50 | 355.99 | 15.72 | 0.00 | 161.50 |
November | 300.00 | 0.55 | 0.48 | 01-NOV-07:49 | 513.13 | 11.40 | 0.00 | 232.33 | 334.17 | 15.09 | 0.00 | 149.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:20 | 458.19 | 10.88 | 0.00 | 219.00 | 307.37 | 14.77 | 0.00 | 118.67 |
Annual Sum or Average | 4065.67 | 0.52 | 744.72 | 13.77 | 87.67 | 3617.33 | 463.47 | 17.18 | 41.17 | 2897.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 458.19 | 10.88 | 0.00 | 219.00 | 307.37 | 14.77 | 0.00 | 118.67 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 1047.39 | 17.00 | 45.17 | 382.67 | 627.22 | 20.21 | 41.17 | 358.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2172.19 | 22.13 | 105.17 | 248.50 | 801.33 | 21.11 | 49.33 | 207.00 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:39 | 1938.74 | 19.84 | 73.50 | 251.00 | 1053.67 | 22.40 | 60.00 | 210.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-08:09 | 2215.59 | 20.60 | 100.17 | 307.17 | 1188.34 | 21.81 | 71.67 | 263.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 3069.53 | 19.00 | 82.33 | 329.00 | 1130.37 | 17.54 | 0.00 | 294.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:10 | 2843.99 | 16.54 | 52.50 | 363.17 | 1144.40 | 17.67 | 0.00 | 323.67 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:00 | 2420.01 | 13.73 | 0.00 | 359.50 | 1300.68 | 17.62 | 0.00 | 320.83 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-06:30 | 2550.13 | 13.86 | 5.67 | 368.00 | 1343.39 | 17.54 | 0.00 | 339.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:40 | 3154.89 | 18.67 | 88.17 | 350.00 | 1267.78 | 17.74 | 7.00 | 321.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:19 | 2728.87 | 21.43 | 101.83 | 302.33 | 1440.23 | 22.35 | 71.83 | 266.83 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 2018.16 | 20.08 | 81.83 | 280.67 | 1044.00 | 20.96 | 52.50 | 234.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-07:49 | 2107.95 | 21.75 | 101.83 | 251.83 | 1150.47 | 22.85 | 75.00 | 209.83 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-08:30 | 1856.15 | 20.22 | 88.17 | 239.83 | 1056.53 | 22.86 | 79.17 | 193.33 |
Annual Sum or Average | 4065.67 | 0.51 | 2465.52 | 18.70 | 881.17 | 3651.00 | 1172.97 | 19.94 | 466.50 | 3184.67 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1856.15 | 13.73 | 0.00 | 239.83 | 801.33 | 17.54 | 0.00 | 193.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 3154.89 | 22.13 | 105.17 | 368.00 | 1440.23 | 22.86 | 79.17 | 339.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196520E+09 | 5077.68 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22401244.49 | 2974.24 | 09-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147914E+09 | 4611.07 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3244365.48 | 2722.04 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 46074.20 | 3.82 | 04-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 383506.67 | 3.94 | 21-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 953912.07 | 4.37 | 24-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1173074.55 | 4.62 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 507846.55 | 4.38 | 28-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 392738.07 | 20.75 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 795105.46 | 1299.61 | 30-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88733637.76 | 4439.43 | 22-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.463066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 46074.20 | 3.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196520E+09 | 5077.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346429E+09 | 6016.96 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.378894E+09 | 5887.93 | 10-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.674225E+09 | 5890.18 | 22-MAR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.301825E+09 | 5890.07 | 20-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.254344E+09 | 5880.43 | 18-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82878877.60 | 5881.58 | 13-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 761463.88 | 2027.73 | 17-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2834545.59 | 1823.78 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23094258.25 | 5830.89 | 20-SEP-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71872524.80 | 5872.72 | 25-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170140E+09 | 5877.29 | 17-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306689E+09 | 6101.62 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 761463.88 | 1823.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674225E+09 | 6101.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 617072.99 | 4309.98 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 630599.72 | 4240.56 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1247672.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 630599.72 | 4309.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22763391.49 | 4954.67 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 223530.02 | 517.57 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9223533.97 | 4876.13 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 912822.83 | 2253.62 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 347496.40 | 1294.00 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33470774.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22763391.49 | 4954.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4197495.35 | 4412.32 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1711646.63 | 3681.17 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29609.51 | 197.40 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5938751.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4197495.35 | 4412.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405540E+09 | 6354.23 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107337E+09 | 3682.66 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352550E+09 | 5152.54 | 30-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9130805.19 | 3306.61 | 01-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32336.23 | 3.41 | 04-MAY-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 318777.60 | 3.67 | 21-JUN-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 793707.80 | 3.92 | 24-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 958190.49 | 4.02 | 17-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 415429.76 | 3.89 | 25-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1481947.61 | 1106.35 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15801537.65 | 2246.08 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249758E+09 | 4995.13 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 32336.23 | 3.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405540E+09 | 6354.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5738358.22 | 6423.13 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3663056.58 | 6354.14 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21681.61 | 144.54 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9423096.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5738358.22 | 6423.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6388454.62 | 4772.04 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 876175.49 | 4720.24 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7264630.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6388454.62 | 4772.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30066750.70 | 5406.03 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 210711.62 | 182.13 | 27-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7181149.36 | 5348.68 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 166022.33 | 813.69 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2180500.13 | 2817.32 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39805134.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30066750.70 | 5406.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14695871.43 | 4837.33 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3685666.64 | 4784.72 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 228164.40 | 791.53 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 961312.83 | 1895.94 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19571015.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14695871.43 | 4837.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.520527E+09 | 4891.35 | 03-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212657E+09 | 4502.42 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.495935E+09 | 4725.22 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22316727.17 | 4177.57 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2416884.98 | 952.85 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 309183.23 | 3.87 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 779673.75 | 4.26 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 967670.81 | 4.44 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352828.31 | 4.05 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9427993.67 | 2209.92 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68631547.43 | 3544.02 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381802E+09 | 4696.67 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 309183.23 | 3.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.520527E+09 | 4891.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61230830.84 | 19335.28 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5878602.32 | 7712.33 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67109433.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61230830.84 | 19335.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 91250462.86 | 8319.64 | 28-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28728289.77 | 8072.93 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69448924.97 | 8205.64 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8118192.67 | 8031.42 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 639699.02 | 1305.34 | 15-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1741810.44 | 4259.29 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24748311.83 | 8157.26 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91250462.86 | 8319.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 73867760.75 | 5973.07 | 28-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21405108.63 | 5767.88 | 11-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 27237081.05 | 5891.09 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1241266.15 | 5173.97 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 240817.92 | 1611.19 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2157573.03 | 3608.85 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22829275.38 | 5855.88 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73867760.75 | 5973.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246978E+09 | 7272.77 | 03-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71683535.94 | 6914.54 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113406E+09 | 7027.65 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9902888.14 | 6879.45 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1627443.74 | 4559.24 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33428006.15 | 6895.44 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125370E+09 | 6986.27 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.602396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246978E+09 | 7272.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136867E+09 | 6267.50 | 28-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38650202.28 | 6080.00 | 09-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 63353876.22 | 6181.37 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6873189.37 | 6048.80 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96447.41 | 321.49 | 13-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88891.10 | 253.73 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16545041.83 | 6059.71 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70705155.32 | 6144.15 | 22-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.333180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136867E+09 | 6267.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.907798E+10 | 0.840486E+10 | 38684.32 | 18-JAN-13:05 | 38684.32 | 0.00 |
February | 0.00 | 0.00 | 0.507054E+10 | 0.441147E+10 | 36788.80 | 01-FEB-12:00 | 36788.80 | 0.00 |
March | 0.00 | 0.00 | 0.602393E+10 | 0.477600E+10 | 40542.85 | 23-MAR-15:00 | 30046.14 | 0.00 |
April | 0.00 | 0.00 | 0.129201E+11 | 0.108142E+11 | 45709.54 | 26-APR-14:10 | 43494.60 | 0.00 |
May | 0.00 | 0.00 | 0.138023E+11 | 0.117396E+11 | 35382.19 | 04-MAY-14:05 | 32784.05 | 0.00 |
June | 0.00 | 0.00 | 0.257263E+11 | 0.193792E+11 | 55277.05 | 28-JUN-11:00 | 35068.60 | 0.00 |
July | 0.00 | 0.00 | 0.438886E+11 | 0.292030E+11 | 81125.16 | 31-JUL-16:00 | 45508.72 | 0.00 |
August | 0.00 | 0.00 | 0.506293E+11 | 0.327449E+11 | 79256.09 | 07-AUG-10:40 | 45930.90 | 0.00 |
September | 0.00 | 0.00 | 0.312910E+11 | 0.225048E+11 | 59377.90 | 29-SEP-14:50 | 59377.90 | 0.00 |
October | 0.00 | 0.00 | 0.345931E+11 | 0.275062E+11 | 73356.23 | 04-OCT-11:00 | 41476.84 | 0.00 |
November | 0.00 | 0.00 | 0.973521E+10 | 0.868681E+10 | 37507.71 | 28-NOV-14:00 | 37507.71 | 0.00 |
December | 0.00 | 0.00 | 0.106875E+11 | 0.104010E+11 | 39898.01 | 05-DEC-15:10 | 39898.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253446E+12 | 0.190572E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.507054E+10 | 0.441147E+10 | 35382.19 | 30046.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.506293E+11 | 0.327449E+11 | 81125.16 | 59377.90 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.708186E+10 | 0.639559E+10 | 34815.17 | 18-JAN-13:05 | 34815.17 | 0.00 |
February | 0.00 | 0.00 | 0.411690E+10 | 0.351656E+10 | 29576.22 | 01-FEB-12:00 | 29576.22 | 0.00 |
March | 0.00 | 0.00 | 0.522792E+10 | 0.408858E+10 | 38988.18 | 23-MAR-14:05 | 31213.89 | 0.00 |
April | 0.00 | 0.00 | 0.116608E+11 | 0.978612E+10 | 44164.79 | 26-APR-14:05 | 41741.22 | 0.00 |
May | 0.00 | 0.00 | 0.119286E+11 | 0.101080E+11 | 32884.69 | 04-MAY-14:05 | 31070.93 | 0.00 |
June | 0.00 | 0.00 | 0.224074E+11 | 0.169729E+11 | 49740.14 | 29-JUN-12:05 | 31804.55 | 0.00 |
July | 0.00 | 0.00 | 0.376416E+11 | 0.252711E+11 | 71206.02 | 31-JUL-16:00 | 39970.56 | 0.00 |
August | 0.00 | 0.00 | 0.433594E+11 | 0.283769E+11 | 67379.79 | 07-AUG-10:40 | 39402.79 | 0.00 |
September | 0.00 | 0.00 | 0.264619E+11 | 0.192074E+11 | 58640.99 | 29-SEP-12:02 | 58640.99 | 0.00 |
October | 0.00 | 0.00 | 0.284701E+11 | 0.227494E+11 | 64333.60 | 03-OCT-13:40 | 38288.94 | 0.00 |
November | 0.00 | 0.00 | 0.806360E+10 | 0.709374E+10 | 32914.91 | 28-NOV-14:00 | 32914.91 | 0.00 |
December | 0.00 | 0.00 | 0.831444E+10 | 0.801526E+10 | 35908.96 | 05-DEC-15:05 | 35908.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214734E+12 | 0.161582E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.411690E+10 | 0.351656E+10 | 29576.22 | 29576.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.433594E+11 | 0.283769E+11 | 71206.02 | 58640.99 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.643515E+10 | 0.565146E+10 | 36402.34 | 18-JAN-13:40 | 36402.34 | 0.00 |
February | 0.00 | 0.00 | 0.380421E+10 | 0.315536E+10 | 29692.85 | 01-FEB-12:00 | 29692.85 | 0.00 |
March | 0.00 | 0.00 | 0.512209E+10 | 0.390606E+10 | 39080.44 | 23-MAR-15:00 | 28987.56 | 0.00 |
April | 0.00 | 0.00 | 0.121929E+11 | 0.990945E+10 | 50211.10 | 26-APR-14:00 | 48027.98 | 0.00 |
May | 0.00 | 0.00 | 0.123880E+11 | 0.101875E+11 | 35861.13 | 03-MAY-14:00 | 33385.31 | 0.00 |
June | 0.00 | 0.00 | 0.237543E+11 | 0.175472E+11 | 54686.75 | 29-JUN-13:00 | 34746.29 | 0.00 |
July | 0.00 | 0.00 | 0.399854E+11 | 0.264984E+11 | 82712.48 | 31-JUL-15:30 | 48536.77 | 0.00 |
August | 0.00 | 0.00 | 0.458979E+11 | 0.295371E+11 | 81297.99 | 14-AUG-13:20 | 49280.67 | 0.00 |
September | 0.00 | 0.00 | 0.268353E+11 | 0.192538E+11 | 65252.41 | 29-SEP-13:40 | 65252.41 | 0.00 |
October | 0.00 | 0.00 | 0.282935E+11 | 0.223665E+11 | 71880.60 | 03-OCT-13:10 | 43387.44 | 0.00 |
November | 0.00 | 0.00 | 0.726060E+10 | 0.622550E+10 | 33861.31 | 28-NOV-14:00 | 33861.31 | 0.00 |
December | 0.00 | 0.00 | 0.753901E+10 | 0.721006E+10 | 36470.05 | 05-DEC-15:00 | 36470.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219508E+12 | 0.161448E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.380421E+10 | 0.315536E+10 | 29692.85 | 28987.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.458979E+11 | 0.295371E+11 | 82712.48 | 65252.41 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 797.44 | 113882.71 | 03-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 361.13 | 52997.37 | 10-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 731.54 | 102501.08 | 30-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 138.52 | 45920.44 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 95.99 | 7496.36 | 08-MAY-06:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 30.74 | 6950.41 | 12-JUN-06:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.24 | 1965.20 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2.04 | 1646.69 | 28-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10.64 | 7960.57 | 20-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.53 | 12852.94 | 30-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 118.55 | 39446.94 | 24-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 470.45 | 61745.96 | 15-DEC-07:03 |
Annual Sum or Average | 0.00 | 233.07 | ||||
Minimum of Months | 0.00 | 0.00 | 1.24 | 1646.69 | ||
Maximum of Months | 0.00 | 0.00 | 797.44 | 113882.71 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1492.31 | 5440.35 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1503.33 | 5440.51 | 02-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1590.60 | 5413.55 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1448.47 | 5315.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1466.10 | 5198.27 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1471.63 | 5065.37 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1321.73 | 4962.73 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1460.09 | 4952.97 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1374.23 | 5036.79 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1404.02 | 5169.40 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1463.72 | 5298.07 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1432.51 | 5394.36 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||
Minimum of Months | 0.00 | 0.00 | 1321.73 | 4952.97 | ||
Maximum of Months | 0.00 | 0.00 | 1590.60 | 5440.51 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.229030E+10 | 0.35 | 5017.07 | 18-JAN-15:40 | 1.23 |
February | 0.196892E+10 | 0.35 | 4346.07 | 03-FEB-15:10 | 1.14 |
March | 0.218545E+10 | 0.35 | 4664.80 | 23-MAR-15:20 | 1.17 |
April | 0.260626E+10 | 0.38 | 5178.21 | 26-APR-14:20 | 1.25 |
May | 0.276771E+10 | 0.39 | 4575.60 | 03-MAY-15:20 | 1.16 |
June | 0.319776E+10 | 0.43 | 5210.41 | 26-JUN-16:00 | 1.25 |
July | 0.396245E+10 | 0.47 | 7204.98 | 31-JUL-14:30 | 1.53 |
August | 0.449448E+10 | 0.51 | 7078.87 | 14-AUG-15:00 | 1.52 |
September | 0.362257E+10 | 0.45 | 6655.96 | 11-SEP-14:30 | 1.46 |
October | 0.358296E+10 | 0.44 | 8061.07 | 16-OCT-07:50 | 1.66 |
November | 0.261248E+10 | 0.38 | 5064.23 | 13-NOV-15:10 | 1.23 |
December | 0.230803E+10 | 0.35 | 4742.43 | 19-DEC-16:10 | 1.20 |
Annual Sum or Average | 0.355994E+11 | 0.41 | |||
Minimum of Months | 0.196892E+10 | 0.35 | 4346.07 | 1.14 | |
Maximum of Months | 0.449448E+10 | 0.51 | 8061.07 | 1.66 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154553E+10 | 0.31 | 3821.10 | 19-JAN-15:05 | 1.09 |
February | 0.142120E+10 | 0.32 | 3781.94 | 03-FEB-15:05 | 1.10 |
March | 0.160922E+10 | 0.33 | 4390.85 | 23-MAR-15:20 | 1.19 |
April | 0.212020E+10 | 0.37 | 5269.40 | 26-APR-14:05 | 1.33 |
May | 0.215023E+10 | 0.37 | 4457.93 | 03-MAY-14:05 | 1.20 |
June | 0.261815E+10 | 0.41 | 4634.67 | 26-JUN-14:05 | 1.23 |
July | 0.317624E+10 | 0.44 | 6578.07 | 31-JUL-14:05 | 1.53 |
August | 0.363343E+10 | 0.48 | 6169.60 | 14-AUG-14:05 | 1.47 |
September | 0.280509E+10 | 0.42 | 6513.29 | 29-SEP-16:00 | 1.52 |
October | 0.263011E+10 | 0.40 | 7157.22 | 16-OCT-16:00 | 1.62 |
November | 0.176709E+10 | 0.34 | 3914.51 | 10-NOV-15:05 | 1.11 |
December | 0.157649E+10 | 0.32 | 3725.60 | 19-DEC-15:50 | 1.09 |
Annual Sum or Average | 0.270530E+11 | 0.38 | |||
Minimum of Months | 0.142120E+10 | 0.31 | 3725.60 | 1.09 | |
Maximum of Months | 0.363343E+10 | 0.48 | 7157.22 | 1.62 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138823E+10 | 0.30 | 3249.01 | 18-JAN-15:30 | 0.92 |
February | 0.128165E+10 | 0.31 | 3152.60 | 03-FEB-15:00 | 0.91 |
March | 0.149346E+10 | 0.33 | 4068.91 | 23-MAR-15:20 | 1.04 |
April | 0.196393E+10 | 0.35 | 4917.02 | 26-APR-14:20 | 1.17 |
May | 0.199018E+10 | 0.35 | 4290.96 | 03-MAY-15:00 | 1.08 |
June | 0.247019E+10 | 0.39 | 4531.50 | 30-JUN-16:00 | 1.11 |
July | 0.300053E+10 | 0.41 | 6136.40 | 31-JUL-14:40 | 1.34 |
August | 0.338664E+10 | 0.44 | 5776.96 | 14-AUG-15:00 | 1.29 |
September | 0.250274E+10 | 0.38 | 6888.27 | 29-SEP-16:00 | 1.44 |
October | 0.229913E+10 | 0.36 | 7501.32 | 16-OCT-16:00 | 1.53 |
November | 0.149747E+10 | 0.31 | 3242.79 | 10-NOV-14:50 | 0.91 |
December | 0.140339E+10 | 0.30 | 3287.81 | 19-DEC-15:40 | 0.93 |
Annual Sum or Average | 0.246775E+11 | 0.35 | |||
Minimum of Months | 0.128165E+10 | 0.30 | 3152.60 | 0.91 | |
Maximum of Months | 0.338664E+10 | 0.44 | 7501.32 | 1.53 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 17959100.60 | 16324822.45 | 389.17 | 03-JAN-07:02 | 353.76 | 353.76 | 38.08 | 1.24 |
February | 8031812.15 | 7300917.24 | 288.43 | 09-FEB-07:03 | 262.18 | 262.18 | 37.32 | 0.50 |
March | 17770395.85 | 16153289.83 | 353.49 | 30-MAR-06:02 | 321.32 | 321.32 | 34.80 | 0.97 |
April | 3900088.58 | 3545180.51 | 276.27 | 01-APR-06:03 | 251.13 | 251.13 | 36.02 | 0.46 |
May | 2973613.31 | 2703014.50 | 76.07 | 15-MAY-06:05 | 69.15 | 69.15 | 39.58 | 0.08 |
June | 896654.33 | 815058.78 | 63.00 | 02-JUN-06:08 | 57.27 | 57.27 | 43.87 | 0.07 |
July | 29047.99 | 26404.63 | 17.04 | 17-JUL-06:10 | 15.49 | 15.49 | 33.61 | 0.02 |
August | 47639.47 | 43304.28 | 14.37 | 28-AUG-06:10 | 13.07 | 13.07 | 33.70 | 0.01 |
September | 260387.35 | 236692.10 | 62.82 | 20-SEP-06:20 | 57.10 | 57.10 | 35.79 | 0.07 |
October | 882335.44 | 802042.92 | 106.00 | 30-OCT-06:01 | 96.36 | 96.36 | 35.06 | 0.12 |
November | 2903515.25 | 2639295.37 | 246.11 | 24-NOV-07:02 | 223.72 | 223.72 | 34.65 | 0.37 |
December | 11396784.01 | 10359676.67 | 303.60 | 13-DEC-07:03 | 275.97 | 275.97 | 38.14 | 0.56 |
Annual Sum or Average | 67051374.34 | 60949699.27 | ||||||
Minimum of Months | 29047.99 | 26404.63 | 14.37 | 13.07 | 13.07 | 33.61 | 0.01 | |
Maximum of Months | 17959100.60 | 16324822.45 | 389.17 | 353.76 | 353.76 | 43.87 | 1.24 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.36 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.32 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.33 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 57.30 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.56 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.51 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.48 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.58 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.56 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.36 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.45 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.39 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.30 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.36 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 797.44 | 113882.71 | 03-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 35.82 | 35.82 | 361.13 | 52997.37 | 10-FEB-07:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 35.29 | 35.29 | 731.54 | 102501.08 | 30-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.89 | 37.89 | 138.52 | 45920.44 | 01-APR-06:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 35.24 | 35.24 | 95.99 | 7496.36 | 08-MAY-06:06 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 42.12 | 42.12 | 30.74 | 6950.41 | 12-JUN-06:08 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 33.20 | 33.20 | 1.24 | 1965.20 | 17-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.36 | 33.36 | 2.04 | 1646.69 | 28-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 32.23 | 32.23 | 10.64 | 7960.57 | 20-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 41.68 | 41.68 | 30.53 | 12852.94 | 30-OCT-06:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35.01 | 35.01 | 118.55 | 39446.94 | 24-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 37.87 | 37.87 | 470.45 | 61745.96 | 15-DEC-07:03 |
Annual Sum or Average | 0.00 | 233.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 32.23 | 32.23 | 1.24 | 1646.69 | ||
Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 797.44 | 113882.71 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.36 | 58.36 | 1492.31 | 5440.35 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.92 | 57.92 | 1503.33 | 5440.51 | 02-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.93 | 57.93 | 1590.60 | 5413.55 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.97 | 57.97 | 1448.47 | 5315.63 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.43 | 58.43 | 1466.10 | 5198.27 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.07 | 58.07 | 1471.63 | 5065.37 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.11 | 58.11 | 1321.73 | 4962.73 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.13 | 58.13 | 1460.09 | 4952.97 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.12 | 58.12 | 1374.23 | 5036.79 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.29 | 57.29 | 1404.02 | 5169.40 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.03 | 58.03 | 1463.72 | 5298.07 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.98 | 57.98 | 1432.51 | 5394.36 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1452.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.29 | 57.29 | 1321.73 | 4952.97 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 1590.60 | 5440.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.570526E+09 | 0.00 | 0.00 | 0.437417E+10 | 0.00 | 0.00 |
February | 0.401519E+09 | 0.00 | 0.00 | 0.316440E+10 | 0.00 | 0.00 |
March | 0.833705E+09 | 0.00 | 0.00 | 0.358412E+10 | 0.00 | 0.00 |
April | 0.306012E+09 | 0.00 | 0.00 | 0.554070E+10 | 0.00 | 0.00 |
May | 0.254390E+09 | 0.00 | 0.00 | 0.593646E+10 | 0.00 | 0.00 |
June | 83262384.26 | 0.00 | 0.00 | 0.889483E+10 | 0.00 | 0.00 |
July | 1715375.95 | 0.00 | 0.00 | 0.135088E+11 | 0.00 | 0.00 |
August | 4007620.14 | 0.00 | 0.00 | 0.154610E+11 | 0.00 | 0.00 |
September | 23602104.80 | 0.00 | 0.00 | 0.106291E+11 | 0.00 | 0.00 |
October | 72265262.87 | 0.00 | 0.00 | 0.113955E+11 | 0.00 | 0.00 |
November | 0.170936E+09 | 0.00 | 0.00 | 0.484712E+10 | 0.00 | 0.00 |
December | 0.395770E+09 | 0.00 | 0.00 | 0.471013E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.311771E+10 | 0.00 | 0.00 | 0.920463E+11 | 0.00 | 0.00 |
Minimum of Months | 1715375.95 | 0.00 | 0.00 | 0.316440E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833705E+09 | 0.00 | 0.00 | 0.154610E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.462430E+09 | 0.00 | 0.00 | 0.319104E+10 | 0.00 | 0.00 |
February | 0.107548E+09 | 0.00 | 0.00 | 0.240095E+10 | 0.00 | 0.00 |
March | 0.367957E+09 | 0.00 | 0.00 | 0.282219E+10 | 0.00 | 0.00 |
April | 9546673.54 | 0.00 | 0.00 | 0.478535E+10 | 0.00 | 0.00 |
May | 32336.23 | 0.00 | 0.00 | 0.490877E+10 | 0.00 | 0.00 |
June | 318777.60 | 0.00 | 0.00 | 0.760313E+10 | 0.00 | 0.00 |
July | 793707.80 | 0.00 | 0.00 | 0.114029E+11 | 0.00 | 0.00 |
August | 958190.49 | 0.00 | 0.00 | 0.130593E+11 | 0.00 | 0.00 |
September | 415429.76 | 0.00 | 0.00 | 0.877359E+10 | 0.00 | 0.00 |
October | 1481947.61 | 0.00 | 0.00 | 0.912231E+10 | 0.00 | 0.00 |
November | 15801537.65 | 0.00 | 0.00 | 0.363650E+10 | 0.00 | 0.00 |
December | 0.252900E+09 | 0.00 | 0.00 | 0.347374E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122018E+10 | 0.00 | 0.00 | 0.751798E+11 | 0.00 | 0.00 |
Minimum of Months | 32336.23 | 0.00 | 0.00 | 0.240095E+10 | 0.00 | 0.00 |
Maximum of Months | 0.462430E+09 | 0.00 | 0.00 | 0.130593E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.113072E+10 | 0.00 | 0.00 | 0.291350E+10 | 0.00 | 0.00 |
February | 0.373124E+09 | 0.00 | 0.00 | 0.220431E+10 | 0.00 | 0.00 |
March | 0.775260E+09 | 0.00 | 0.00 | 0.269390E+10 | 0.00 | 0.00 |
April | 48452263.51 | 0.00 | 0.00 | 0.477151E+10 | 0.00 | 0.00 |
May | 3153031.40 | 0.00 | 0.00 | 0.487357E+10 | 0.00 | 0.00 |
June | 309183.23 | 0.00 | 0.00 | 0.777788E+10 | 0.00 | 0.00 |
July | 779673.75 | 0.00 | 0.00 | 0.117752E+11 | 0.00 | 0.00 |
August | 967670.81 | 0.00 | 0.00 | 0.133990E+11 | 0.00 | 0.00 |
September | 352828.31 | 0.00 | 0.00 | 0.861302E+10 | 0.00 | 0.00 |
October | 11385146.42 | 0.00 | 0.00 | 0.883002E+10 | 0.00 | 0.00 |
November | 0.122504E+09 | 0.00 | 0.00 | 0.322155E+10 | 0.00 | 0.00 |
December | 0.625455E+09 | 0.00 | 0.00 | 0.316174E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.309246E+10 | 0.00 | 0.00 | 0.742353E+11 | 0.00 | 0.00 |
Minimum of Months | 309183.23 | 0.00 | 0.00 | 0.220431E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113072E+10 | 0.00 | 0.00 | 0.133990E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.229030E+10 | 0.907798E+10 | 0.570526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196892E+10 | 0.507054E+10 | 0.401519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218545E+10 | 0.602393E+10 | 0.833705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260626E+10 | 0.129201E+11 | 0.306012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276771E+10 | 0.138023E+11 | 0.254390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.319776E+10 | 0.257263E+11 | 83262384.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.396245E+10 | 0.438886E+11 | 1715375.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.449448E+10 | 0.506293E+11 | 4007620.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.362257E+10 | 0.312910E+11 | 23602104.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358296E+10 | 0.345931E+11 | 72265262.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261248E+10 | 0.973521E+10 | 0.170936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230803E+10 | 0.106875E+11 | 0.395770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355994E+11 | 0.253446E+12 | 0.311771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196892E+10 | 0.507054E+10 | 1715375.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449448E+10 | 0.506293E+11 | 0.833705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154553E+10 | 0.708186E+10 | 0.462430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142120E+10 | 0.411690E+10 | 0.107548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160922E+10 | 0.522792E+10 | 0.367957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212020E+10 | 0.116608E+11 | 9546673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215023E+10 | 0.119286E+11 | 32336.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261815E+10 | 0.224074E+11 | 318777.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.317624E+10 | 0.376416E+11 | 793707.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363343E+10 | 0.433594E+11 | 958190.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280509E+10 | 0.264619E+11 | 415429.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263011E+10 | 0.284701E+11 | 1481947.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176709E+10 | 0.806360E+10 | 15801537.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157649E+10 | 0.831444E+10 | 0.252900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270530E+11 | 0.214734E+12 | 0.122018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142120E+10 | 0.411690E+10 | 32336.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363343E+10 | 0.433594E+11 | 0.462430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138823E+10 | 0.643515E+10 | 0.113072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128165E+10 | 0.380421E+10 | 0.373124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149346E+10 | 0.512209E+10 | 0.775260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196393E+10 | 0.121929E+11 | 48452263.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199018E+10 | 0.123880E+11 | 3153031.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247019E+10 | 0.237543E+11 | 309183.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300053E+10 | 0.399854E+11 | 779673.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338664E+10 | 0.458979E+11 | 967670.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250274E+10 | 0.268353E+11 | 352828.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229913E+10 | 0.282935E+11 | 11385146.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149747E+10 | 0.726060E+10 | 0.122504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140339E+10 | 0.753901E+10 | 0.625455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246775E+11 | 0.219508E+12 | 0.309246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128165E+10 | 0.380421E+10 | 309183.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338664E+10 | 0.458979E+11 | 0.113072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.229030E+10 | 0.570526E+09 | 0.00 | 0.00 | 0.208386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196892E+10 | 0.401519E+09 | 0.00 | 0.00 | 0.119547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218545E+10 | 0.833705E+09 | 0.00 | 0.00 | 0.139867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260626E+10 | 0.306012E+09 | 0.00 | 0.00 | 0.293444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276771E+10 | 0.254390E+09 | 0.00 | 0.00 | 0.316875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.319776E+10 | 83262384.26 | 0.00 | 0.00 | 0.569707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.396245E+10 | 1715375.95 | 0.00 | 0.00 | 0.954636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.449448E+10 | 4007620.14 | 0.00 | 0.00 | 0.109665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.362257E+10 | 23602104.80 | 0.00 | 0.00 | 0.700650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.358296E+10 | 72265262.87 | 0.00 | 0.00 | 0.781257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261248E+10 | 0.170936E+09 | 0.00 | 0.00 | 0.223464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230803E+10 | 0.395770E+09 | 0.00 | 0.00 | 0.240210E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355994E+11 | 0.311771E+10 | 0.00 | 0.00 | 0.564469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196892E+10 | 1715375.95 | 0.00 | 0.00 | 0.119547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.449448E+10 | 0.833705E+09 | 0.00 | 0.00 | 0.109665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154553E+10 | 0.462430E+09 | 0.00 | 0.00 | 0.164551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142120E+10 | 0.107548E+09 | 0.00 | 0.00 | 0.979743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160922E+10 | 0.367957E+09 | 0.00 | 0.00 | 0.121297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.212020E+10 | 9546673.54 | 0.00 | 0.00 | 0.266515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.215023E+10 | 32336.23 | 0.00 | 0.00 | 0.275853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.261815E+10 | 318777.60 | 0.00 | 0.00 | 0.498499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.317624E+10 | 793707.80 | 0.00 | 0.00 | 0.822664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363343E+10 | 958190.49 | 0.00 | 0.00 | 0.942590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.280509E+10 | 415429.76 | 0.00 | 0.00 | 0.596850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263011E+10 | 1481947.61 | 0.00 | 0.00 | 0.649220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176709E+10 | 15801537.65 | 0.00 | 0.00 | 0.186941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157649E+10 | 0.252900E+09 | 0.00 | 0.00 | 0.189725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270530E+11 | 0.122018E+10 | 0.00 | 0.00 | 0.481268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142120E+10 | 32336.23 | 0.00 | 0.00 | 0.979743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363343E+10 | 0.462430E+09 | 0.00 | 0.00 | 0.942590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138823E+10 | 0.113072E+10 | 0.00 | 0.00 | 0.152528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128165E+10 | 0.373124E+09 | 0.00 | 0.00 | 0.922659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149346E+10 | 0.775260E+09 | 0.00 | 0.00 | 0.120044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.196393E+10 | 48452263.51 | 0.00 | 0.00 | 0.280758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199018E+10 | 3153031.40 | 0.00 | 0.00 | 0.288339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.247019E+10 | 309183.23 | 0.00 | 0.00 | 0.530769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.300053E+10 | 779673.75 | 0.00 | 0.00 | 0.877470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.338664E+10 | 967670.81 | 0.00 | 0.00 | 0.100124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250274E+10 | 352828.31 | 0.00 | 0.00 | 0.611028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229913E+10 | 11385146.42 | 0.00 | 0.00 | 0.653089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149747E+10 | 0.122504E+09 | 0.00 | 0.00 | 0.172408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140339E+10 | 0.625455E+09 | 0.00 | 0.00 | 0.175835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246775E+11 | 0.309246E+10 | 0.00 | 0.00 | 0.495577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128165E+10 | 309183.23 | 0.00 | 0.00 | 0.922659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.338664E+10 | 0.113072E+10 | 0.00 | 0.00 | 0.100124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.851750E+09 | 30191120.14 | 0.00 | 39041256.16 | 0.00 | 0.00 | 0.160190E+11 | 0.00 | 0.78 |
February | 0.801109E+09 | 5107890.08 | 0.00 | 35488836.10 | 0.00 | 0.00 | 0.164455E+11 | 0.00 | 0.82 |
March | 0.612507E+09 | 0.00 | 0.00 | 41739338.08 | 13840613.61 | 0.00 | 0.193746E+11 | 0.00 | 0.84 |
April | 0.527853E+09 | 10378673.16 | 0.00 | 39357612.38 | 17910046.36 | 0.00 | 0.159738E+11 | 0.00 | 0.96 |
May | 0.639390E+09 | 17055364.59 | 0.00 | 43363385.42 | 0.00 | 0.00 | 0.173354E+11 | 0.00 | 1.05 |
June | 0.375038E+09 | 0.297099E+09 | 0.00 | 41410139.39 | 18375252.46 | 0.00 | 0.121170E+11 | 0.00 | 1.16 |
July | 0.408928E+09 | 0.224834E+10 | 0.00 | 27815466.63 | 0.171930E+09 | 0.00 | 0.528410E+10 | 0.00 | 1.08 |
August | 0.177604E+09 | 0.276986E+10 | 0.00 | 26839117.08 | 0.220682E+09 | 0.00 | 0.500960E+10 | 0.00 | 1.15 |
September | 0.375704E+09 | 0.679837E+09 | 0.00 | 36566371.95 | 28196191.49 | 0.00 | 0.992553E+10 | 0.00 | 1.08 |
October | 0.387529E+09 | 0.135454E+10 | 0.00 | 32902887.16 | 0.130142E+09 | 0.00 | 0.977322E+10 | 0.00 | 0.96 |
November | 0.621459E+09 | 1714721.02 | 0.00 | 42867534.16 | 5532211.99 | 0.00 | 0.182389E+11 | 0.00 | 0.94 |
December | 0.102603E+10 | 1845974.69 | 0.00 | 39740473.43 | 0.00 | 0.00 | 0.155017E+11 | 0.00 | 0.77 |
Annual Sum or Average | 0.680490E+10 | 0.741597E+10 | 0.00 | 0.447132E+09 | 0.606608E+09 | 0.00 | 0.160998E+12 | 0.00 | 0.97 |
Minimum of Months | 0.177604E+09 | 0.00 | 0.00 | 26839117.08 | 0.00 | 0.00 | 0.500960E+10 | 0.00 | 0.77 |
Maximum of Months | 0.102603E+10 | 0.276986E+10 | 0.00 | 43363385.42 | 0.220682E+09 | 0.00 | 0.193746E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.438985E+10 | 3111176.65 | 0.00 | 12648913.91 | 19484046.33 | 0.00 | 0.590896E+10 | 0.00 | 0.47 |
February | 0.362978E+10 | 6027650.85 | 0.00 | 12784319.55 | 0.00 | 0.00 | 0.701998E+10 | 0.00 | 0.50 |
March | 0.405918E+10 | 0.00 | 0.00 | 15083028.84 | 18754093.24 | 0.00 | 0.828103E+10 | 0.00 | 0.51 |
April | 0.203460E+10 | 2940262.64 | 0.00 | 19213343.93 | 39818529.44 | 0.00 | 0.857518E+10 | 0.00 | 0.62 |
May | 0.187278E+10 | 12780678.64 | 0.00 | 22336076.63 | 41361.86 | 0.00 | 0.973950E+10 | 0.00 | 0.67 |
June | 0.902974E+09 | 0.182687E+09 | 0.00 | 23744324.83 | 28283798.77 | 0.00 | 0.736675E+10 | 0.00 | 0.77 |
July | 0.691850E+09 | 0.143685E+10 | 0.00 | 16129366.81 | 0.174789E+09 | 0.00 | 0.319492E+10 | 0.00 | 0.74 |
August | 0.450323E+09 | 0.177712E+10 | 0.00 | 15646168.67 | 0.233370E+09 | 0.00 | 0.300063E+10 | 0.00 | 0.78 |
September | 0.809030E+09 | 0.462628E+09 | 0.00 | 19966942.93 | 39599317.62 | 0.00 | 0.581098E+10 | 0.00 | 0.70 |
October | 0.103803E+10 | 0.893525E+09 | 0.00 | 17056709.28 | 0.132742E+09 | 0.00 | 0.542804E+10 | 0.00 | 0.63 |
November | 0.256194E+10 | 894071.40 | 0.00 | 17825852.90 | 9553681.69 | 0.00 | 0.870751E+10 | 0.00 | 0.56 |
December | 0.400788E+10 | 1228170.92 | 0.00 | 14054224.05 | 734861.53 | 0.00 | 0.614930E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.264482E+11 | 0.477980E+10 | 0.00 | 0.206489E+09 | 0.697171E+09 | 0.00 | 0.791828E+11 | 0.00 | 0.62 |
Minimum of Months | 0.450323E+09 | 0.00 | 0.00 | 12648913.91 | 0.00 | 0.00 | 0.300063E+10 | 0.00 | 0.47 |
Maximum of Months | 0.438985E+10 | 0.177712E+10 | 0.00 | 23744324.83 | 0.233370E+09 | 0.00 | 0.973950E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.561427E+10 | 478319.38 | 0.00 | 7262711.34 | 12561956.89 | 26219735.31 | 0.358531E+10 | 0.00 | 0.43 |
February | 0.482761E+10 | 1391038.44 | 0.00 | 8258065.32 | 0.00 | 0.00 | 0.477321E+10 | 0.00 | 0.46 |
March | 0.556464E+10 | 0.00 | 0.00 | 9718616.44 | 10497438.27 | 720628.60 | 0.579446E+10 | 0.00 | 0.48 |
April | 0.292090E+10 | 393251.28 | 0.00 | 16321675.84 | 16319972.75 | 0.00 | 0.739311E+10 | 0.00 | 0.60 |
May | 0.285490E+10 | 4489738.17 | 0.00 | 19005561.33 | 0.00 | 0.00 | 0.847188E+10 | 0.00 | 0.65 |
June | 0.138396E+10 | 95036323.85 | 0.00 | 21855839.73 | 4452641.32 | 0.00 | 0.688098E+10 | 0.00 | 0.77 |
July | 0.891471E+09 | 0.118858E+10 | 0.00 | 15085349.01 | 0.136269E+09 | 0.00 | 0.288371E+10 | 0.00 | 0.75 |
August | 0.595275E+09 | 0.157218E+10 | 0.00 | 14992808.54 | 0.196600E+09 | 0.00 | 0.254908E+10 | 0.00 | 0.80 |
September | 0.145060E+10 | 0.326553E+09 | 0.00 | 17040084.87 | 26879725.10 | 0.00 | 0.478434E+10 | 0.00 | 0.67 |
October | 0.198439E+10 | 0.778595E+09 | 0.00 | 12144914.08 | 0.128908E+09 | 0.00 | 0.362829E+10 | 0.00 | 0.59 |
November | 0.416583E+10 | 0.00 | 0.00 | 11284586.95 | 2234772.17 | 0.00 | 0.565504E+10 | 0.00 | 0.50 |
December | 0.520261E+10 | 29979.83 | 0.00 | 8013865.98 | 173652.87 | 0.00 | 0.368141E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.374564E+11 | 0.396773E+10 | 0.00 | 0.160984E+09 | 0.534897E+09 | 26940363.91 | 0.600808E+11 | 0.00 | 0.60 |
Minimum of Months | 0.595275E+09 | 0.00 | 0.00 | 7262711.34 | 0.00 | 0.00 | 0.254908E+10 | 0.00 | 0.43 |
Maximum of Months | 0.561427E+10 | 0.157218E+10 | 0.00 | 21855839.73 | 0.196600E+09 | 26219735.31 | 0.847188E+10 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139991E+10 | 91245.81 | 0.00 | 636124.93 | 2656847.49 | 0.152043E+09 | 0.298536E+09 | 0.00 | 0.41 |
February | 0.134879E+10 | 295534.04 | 0.00 | 802676.37 | 0.00 | 39958381.05 | 0.489262E+09 | 0.00 | 0.43 |
March | 0.158820E+10 | 0.00 | 0.00 | 1097918.40 | 2220202.85 | 56048611.37 | 0.648438E+09 | 0.00 | 0.45 |
April | 0.951140E+09 | 200997.72 | 0.00 | 2859860.56 | 3346132.38 | 5692951.83 | 0.116533E+10 | 0.00 | 0.59 |
May | 0.829350E+09 | 1117025.48 | 0.00 | 3909609.47 | 0.00 | 0.00 | 0.162752E+10 | 0.00 | 0.68 |
June | 0.422153E+09 | 25466579.10 | 0.00 | 5193038.01 | 941731.37 | 0.00 | 0.151351E+10 | 0.00 | 0.88 |
July | 0.243466E+09 | 0.341950E+09 | 0.00 | 3330909.56 | 28820818.53 | 0.00 | 0.619054E+09 | 0.00 | 0.88 |
August | 0.229034E+09 | 0.415062E+09 | 0.00 | 2830599.19 | 43844809.50 | 0.00 | 0.429957E+09 | 0.00 | 0.89 |
September | 0.506378E+09 | 86749929.15 | 0.00 | 3079686.46 | 9187526.39 | 0.00 | 0.770588E+09 | 0.00 | 0.69 |
October | 0.648360E+09 | 0.200041E+09 | 0.00 | 1904349.70 | 28664863.82 | 445456.88 | 0.482560E+09 | 0.00 | 0.59 |
November | 0.125666E+10 | 0.00 | 0.00 | 1123539.51 | 472653.18 | 17059831.29 | 0.587278E+09 | 0.00 | 0.44 |
December | 0.141298E+10 | 5694.88 | 0.00 | 611717.44 | 36727.49 | 84224676.78 | 0.266087E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.108364E+11 | 0.107098E+10 | 0.00 | 27380029.61 | 0.120192E+09 | 0.355473E+09 | 0.889812E+10 | 0.00 | 0.61 |
Minimum of Months | 0.229034E+09 | 0.00 | 0.00 | 611717.44 | 0.00 | 0.00 | 0.266087E+09 | 0.00 | 0.41 |
Maximum of Months | 0.158820E+10 | 0.415062E+09 | 0.00 | 5193038.01 | 43844809.50 | 0.152043E+09 | 0.162752E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.631327E+09 | 1648362.28 | 0.00 | 1549172.04 | 196558.32 | 42049756.87 | 0.690622E+09 | 0.00 | 0.50 |
February | 0.660959E+09 | 276849.92 | 0.00 | 1707556.75 | 0.00 | 11100802.11 | 0.854975E+09 | 0.00 | 0.57 |
March | 0.759585E+09 | 11618.71 | 0.00 | 2483383.79 | 1400061.85 | 11318226.67 | 0.110113E+10 | 0.00 | 0.64 |
April | 0.425727E+09 | 1512769.12 | 0.00 | 4593788.45 | 1437493.89 | 640039.40 | 0.179142E+10 | 0.00 | 1.03 |
May | 0.408544E+09 | 1444985.79 | 0.00 | 4743049.09 | 0.00 | 0.00 | 0.186402E+10 | 0.00 | 1.03 |
June | 0.232494E+09 | 25193353.31 | 0.00 | 5672666.79 | 336384.56 | 0.00 | 0.145679E+10 | 0.00 | 1.30 |
July | 0.117233E+09 | 0.346849E+09 | 0.00 | 4654129.20 | 5393131.51 | 0.00 | 0.740408E+09 | 0.00 | 1.42 |
August | 0.106279E+09 | 0.509563E+09 | 0.00 | 3796460.92 | 11150421.83 | 0.00 | 0.567905E+09 | 0.00 | 1.51 |
September | 0.259040E+09 | 79945735.48 | 0.00 | 3983951.72 | 5020979.37 | 0.00 | 0.926477E+09 | 0.00 | 1.05 |
October | 0.288067E+09 | 0.180111E+09 | 0.00 | 2615676.36 | 16326935.16 | 94469.23 | 0.715253E+09 | 0.00 | 0.81 |
November | 0.566469E+09 | 0.00 | 0.00 | 2125847.89 | 298767.48 | 998504.63 | 0.940323E+09 | 0.00 | 0.59 |
December | 0.684157E+09 | 36719.65 | 0.00 | 1549910.04 | 0.00 | 11541866.71 | 0.553171E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.513988E+10 | 0.114659E+10 | 0.00 | 39475593.04 | 41560733.97 | 77743665.62 | 0.122025E+11 | 0.00 | 0.91 |
Minimum of Months | 0.106279E+09 | 0.00 | 0.00 | 1549172.04 | 0.00 | 0.00 | 0.553171E+09 | 0.00 | 0.49 |
Maximum of Months | 0.759585E+09 | 0.509563E+09 | 0.00 | 5672666.79 | 16326935.16 | 42049756.87 | 0.186402E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.736540E+09 | 13886896.80 | 0.00 | 8379901.18 | 310561.42 | 48677828.61 | 0.359194E+10 | 0.00 | 1.09 |
February | 0.841405E+09 | 1123776.08 | 0.00 | 6280375.70 | 0.00 | 17486226.52 | 0.285877E+10 | 0.00 | 0.93 |
March | 0.107137E+10 | 2456241.14 | 0.00 | 5769573.37 | 524873.42 | 32314624.87 | 0.261594E+10 | 0.00 | 0.84 |
April | 0.756509E+09 | 1793611.34 | 0.00 | 6283110.61 | 2572959.18 | 5557968.23 | 0.241534E+10 | 0.00 | 0.95 |
May | 0.828231E+09 | 1478903.92 | 0.00 | 4864651.54 | 0.00 | 283784.83 | 0.194929E+10 | 0.00 | 0.79 |
June | 0.475658E+09 | 29801178.48 | 0.00 | 5278651.39 | 940532.61 | 0.00 | 0.148671E+10 | 0.00 | 0.92 |
July | 0.268991E+09 | 0.403306E+09 | 0.00 | 3465822.40 | 25324509.34 | 0.00 | 0.624439E+09 | 0.00 | 0.96 |
August | 0.199768E+09 | 0.624161E+09 | 0.00 | 4236018.45 | 34716991.84 | 0.00 | 0.608588E+09 | 0.00 | 1.22 |
September | 0.360358E+09 | 0.152489E+09 | 0.00 | 7393196.87 | 7912114.95 | 0.00 | 0.166680E+10 | 0.00 | 1.21 |
October | 0.405013E+09 | 0.450544E+09 | 0.00 | 6744734.41 | 5936367.45 | 0.00 | 0.150867E+10 | 0.00 | 1.13 |
November | 0.689372E+09 | 774894.45 | 0.00 | 8877387.58 | 74942.38 | 806670.94 | 0.361581E+10 | 0.00 | 1.16 |
December | 0.745405E+09 | 246704.05 | 0.00 | 9364493.05 | 0.00 | 10911211.19 | 0.317724E+10 | 0.00 | 1.09 |
Annual Sum or Average | 0.737862E+10 | 0.168206E+10 | 0.00 | 76937916.56 | 78313852.61 | 0.116038E+09 | 0.261195E+11 | 0.00 | 1.02 |
Minimum of Months | 0.199768E+09 | 246704.05 | 0.00 | 3465822.40 | 0.00 | 0.00 | 0.608588E+09 | 0.00 | 0.79 |
Maximum of Months | 0.107137E+10 | 0.624161E+09 | 0.00 | 9364493.05 | 34716991.84 | 48677828.61 | 0.361581E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723598E+09 | 3201589.48 | 0.00 | 1665927.96 | 578559.92 | 88827083.81 | 0.773416E+09 | 0.00 | 0.57 |
February | 0.706472E+09 | 366165.95 | 0.00 | 1960845.68 | 0.00 | 23149047.37 | 0.972567E+09 | 0.00 | 0.63 |
March | 0.778797E+09 | 0.00 | 0.00 | 2755251.20 | 1402240.09 | 35212884.85 | 0.134618E+10 | 0.00 | 0.71 |
April | 0.422953E+09 | 1047231.61 | 0.00 | 5094711.69 | 1653589.87 | 4588634.75 | 0.191396E+10 | 0.00 | 1.07 |
May | 0.384441E+09 | 714162.03 | 0.00 | 5427625.30 | 0.00 | 0.00 | 0.209255E+10 | 0.00 | 1.10 |
June | 0.198427E+09 | 20774615.04 | 0.00 | 6317530.40 | 466461.19 | 0.00 | 0.175192E+10 | 0.00 | 1.42 |
July | 0.112103E+09 | 0.386847E+09 | 0.00 | 4676380.18 | 13474776.60 | 0.00 | 0.775489E+09 | 0.00 | 1.45 |
August | 95906330.94 | 0.440145E+09 | 0.00 | 4010098.20 | 20647355.33 | 0.00 | 0.571709E+09 | 0.00 | 1.52 |
September | 0.206419E+09 | 78175888.08 | 0.00 | 4733628.60 | 4090645.36 | 0.00 | 0.115533E+10 | 0.00 | 1.16 |
October | 0.324862E+09 | 0.179935E+09 | 0.00 | 2743553.15 | 12742960.68 | 0.00 | 0.655402E+09 | 0.00 | 0.85 |
November | 0.663713E+09 | 47850.48 | 0.00 | 2387148.53 | 256467.53 | 8647823.39 | 0.107047E+10 | 0.00 | 0.69 |
December | 0.726894E+09 | 3596.78 | 0.00 | 1722896.80 | 23196.42 | 51996573.47 | 0.683434E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.534459E+10 | 0.111126E+10 | 0.00 | 43495597.70 | 55336253.01 | 0.212422E+09 | 0.137624E+11 | 0.00 | 0.98 |
Minimum of Months | 95906330.94 | 0.00 | 0.00 | 1665927.96 | 0.00 | 0.00 | 0.571709E+09 | 0.00 | 0.57 |
Maximum of Months | 0.778797E+09 | 0.440145E+09 | 0.00 | 6317530.40 | 20647355.33 | 88827083.81 | 0.209255E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164354E+10 | 343952.34 | 0.00 | 563203.19 | 3804629.42 | 13646713.53 | 0.255269E+09 | 0.00 | 0.39 |
February | 0.163191E+10 | 485724.34 | 0.00 | 278274.74 | 0.00 | 0.00 | 0.254925E+09 | 0.00 | 0.41 |
March | 0.188987E+10 | 0.00 | 0.00 | 447567.52 | 2916549.46 | 4131110.44 | 0.289021E+09 | 0.00 | 0.42 |
April | 0.114261E+10 | 453494.73 | 0.00 | 1600417.22 | 4591275.01 | 282426.51 | 0.644179E+09 | 0.00 | 0.48 |
May | 0.976766E+09 | 2146087.27 | 0.00 | 2655520.05 | 0.00 | 0.00 | 0.104080E+10 | 0.00 | 0.56 |
June | 0.520170E+09 | 42789472.48 | 0.00 | 3457271.46 | 3872106.69 | 0.00 | 0.968218E+09 | 0.00 | 0.69 |
July | 0.246716E+09 | 0.350155E+09 | 0.00 | 2309669.41 | 36229768.70 | 0.00 | 0.464006E+09 | 0.00 | 0.71 |
August | 0.287153E+09 | 0.391960E+09 | 0.00 | 1609481.31 | 46993542.43 | 0.00 | 0.297795E+09 | 0.00 | 0.70 |
September | 0.576528E+09 | 95113313.09 | 0.00 | 2205143.18 | 8818211.79 | 0.00 | 0.561049E+09 | 0.00 | 0.60 |
October | 0.659487E+09 | 0.202873E+09 | 0.00 | 1651965.37 | 28599624.64 | 0.00 | 0.456438E+09 | 0.00 | 0.54 |
November | 0.130205E+10 | 84782.93 | 0.00 | 1121975.76 | 1277056.22 | 0.00 | 0.624362E+09 | 0.00 | 0.44 |
December | 0.166355E+10 | 140760.33 | 0.00 | 389500.73 | 25629.47 | 261799.17 | 0.184209E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.125404E+11 | 0.108655E+10 | 0.00 | 18289989.94 | 0.137128E+09 | 18322049.65 | 0.604027E+10 | 0.00 | 0.53 |
Minimum of Months | 0.246716E+09 | 0.00 | 0.00 | 278274.74 | 0.00 | 0.00 | 0.184209E+09 | 0.00 | 0.39 |
Maximum of Months | 0.188987E+10 | 0.391960E+09 | 0.00 | 3457271.46 | 46993542.43 | 13646713.53 | 0.104080E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.688351E+09 | 2962359.43 | 0.00 | 1885007.33 | 0.00 | 491990.67 | 0.776519E+09 | 0.00 | 0.50 |
February | 0.749445E+09 | 535661.82 | 0.00 | 1607218.42 | 0.00 | 0.00 | 0.735667E+09 | 0.00 | 0.53 |
March | 0.810157E+09 | 0.00 | 0.00 | 2180046.13 | 1854572.78 | 478109.96 | 0.908349E+09 | 0.00 | 0.58 |
April | 0.456782E+09 | 1897133.24 | 0.00 | 3819113.83 | 2348224.10 | 0.00 | 0.140428E+10 | 0.00 | 0.87 |
May | 0.424763E+09 | 2841160.18 | 0.00 | 4007361.74 | 0.00 | 0.00 | 0.147867E+10 | 0.00 | 0.89 |
June | 0.245291E+09 | 46738902.43 | 0.00 | 4322110.79 | 1882342.02 | 0.00 | 0.109288E+10 | 0.00 | 1.08 |
July | 95939875.75 | 0.391362E+09 | 0.00 | 3625963.83 | 15510685.21 | 0.00 | 0.631911E+09 | 0.00 | 1.21 |
August | 74320199.50 | 0.525678E+09 | 0.00 | 2968513.77 | 19118366.17 | 0.00 | 0.530040E+09 | 0.00 | 1.28 |
September | 0.224638E+09 | 94548206.20 | 0.00 | 3448848.75 | 5253007.34 | 0.00 | 0.838799E+09 | 0.00 | 0.96 |
October | 0.244003E+09 | 0.184698E+09 | 0.00 | 2708011.40 | 17889247.53 | 0.00 | 0.772864E+09 | 0.00 | 0.77 |
November | 0.579789E+09 | 161415.67 | 0.00 | 2549656.57 | 741288.65 | 0.00 | 0.106340E+10 | 0.00 | 0.62 |
December | 0.710648E+09 | 220946.53 | 0.00 | 1880128.31 | 0.00 | 0.00 | 0.652794E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.530413E+10 | 0.125164E+10 | 0.00 | 35001980.87 | 64597733.79 | 970100.63 | 0.108862E+11 | 0.00 | 0.82 |
Minimum of Months | 74320199.50 | 0.00 | 0.00 | 1607218.42 | 0.00 | 0.00 | 0.530040E+09 | 0.00 | 0.49 |
Maximum of Months | 0.810157E+09 | 0.525678E+09 | 0.00 | 4322110.79 | 19118366.17 | 491990.67 | 0.147867E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.860216E+09 | 20337787.63 | 0.00 | 6228077.57 | 0.00 | 0.257230E+09 | 0.253701E+10 | 0.00 | 0.88 |
February | 0.108564E+10 | 2020902.80 | 0.00 | 3637822.19 | 0.00 | 0.245885E+09 | 0.155907E+10 | 0.00 | 0.72 |
March | 0.141244E+10 | 2376025.62 | 0.00 | 2504398.23 | 1098159.02 | 0.446311E+09 | 0.984975E+09 | 0.00 | 0.62 |
April | 0.106910E+10 | 2985504.56 | 0.00 | 2963396.79 | 3654838.44 | 0.192756E+09 | 0.958636E+09 | 0.00 | 0.66 |
May | 0.125733E+10 | 2245364.65 | 0.00 | 1783132.28 | 127530.03 | 0.155405E+09 | 0.616765E+09 | 0.00 | 0.57 |
June | 0.857850E+09 | 46232011.31 | 0.00 | 1872723.44 | 3978149.99 | 49742561.72 | 0.435708E+09 | 0.00 | 0.63 |
July | 0.363307E+09 | 0.409066E+09 | 0.00 | 1437929.08 | 37375058.79 | 381253.89 | 0.292084E+09 | 0.00 | 0.70 |
August | 0.251167E+09 | 0.605550E+09 | 0.00 | 1906429.56 | 47095139.30 | 3246670.97 | 0.362692E+09 | 0.00 | 0.90 |
September | 0.416030E+09 | 0.186253E+09 | 0.00 | 4602771.56 | 6103876.14 | 16927886.65 | 0.107770E+10 | 0.00 | 0.97 |
October | 0.386620E+09 | 0.449553E+09 | 0.00 | 5648346.85 | 7610842.44 | 59501445.07 | 0.124985E+10 | 0.00 | 0.96 |
November | 0.740123E+09 | 2519090.19 | 0.00 | 6853073.46 | 223211.34 | 0.118694E+09 | 0.274082E+10 | 0.00 | 0.98 |
December | 0.774242E+09 | 826839.90 | 0.00 | 7882773.77 | 0.00 | 0.202047E+09 | 0.240946E+10 | 0.00 | 0.90 |
Annual Sum or Average | 0.947407E+10 | 0.172997E+10 | 0.00 | 47320874.78 | 0.107267E+09 | 0.174813E+10 | 0.152248E+11 | 0.00 | 0.79 |
Minimum of Months | 0.251167E+09 | 826839.90 | 0.00 | 1437929.08 | 0.00 | 381253.89 | 0.292084E+09 | 0.00 | 0.57 |
Maximum of Months | 0.141244E+10 | 0.605550E+09 | 0.00 | 7882773.77 | 47095139.30 | 0.446311E+09 | 0.274082E+10 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.837737E+09 | 3878692.71 | 0.00 | 1503632.86 | 591493.31 | 2710067.44 | 0.665272E+09 | 0.00 | 0.52 |
February | 0.793460E+09 | 608897.99 | 0.00 | 1552918.93 | 0.00 | 0.00 | 0.731997E+09 | 0.00 | 0.55 |
March | 0.876738E+09 | 0.00 | 0.00 | 2041199.20 | 1854055.41 | 525690.19 | 0.933977E+09 | 0.00 | 0.60 |
April | 0.409053E+09 | 2045157.82 | 0.00 | 3989895.35 | 1594688.71 | 0.00 | 0.145095E+10 | 0.00 | 0.88 |
May | 0.359683E+09 | 1946094.87 | 0.00 | 4466390.37 | 0.00 | 0.00 | 0.164469E+10 | 0.00 | 0.94 |
June | 0.184028E+09 | 44517267.32 | 0.00 | 4879861.15 | 1540801.03 | 0.00 | 0.133162E+10 | 0.00 | 1.18 |
July | 85112307.08 | 0.427246E+09 | 0.00 | 3706821.37 | 14629002.93 | 0.00 | 0.666450E+09 | 0.00 | 1.25 |
August | 72066959.83 | 0.469225E+09 | 0.00 | 2979466.69 | 19499373.77 | 0.00 | 0.527958E+09 | 0.00 | 1.28 |
September | 0.152620E+09 | 96634941.01 | 0.00 | 4134041.67 | 3447075.48 | 0.00 | 0.105455E+10 | 0.00 | 1.06 |
October | 0.259540E+09 | 0.192192E+09 | 0.00 | 2586620.95 | 12977108.90 | 0.00 | 0.676221E+09 | 0.00 | 0.78 |
November | 0.635512E+09 | 268417.13 | 0.00 | 2463739.72 | 741081.85 | 0.00 | 0.106467E+10 | 0.00 | 0.66 |
December | 0.829677E+09 | 188054.25 | 0.00 | 1634564.20 | 16292.70 | 0.00 | 0.576048E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.549523E+10 | 0.123875E+10 | 0.00 | 35939152.45 | 56890974.08 | 3235757.63 | 0.113244E+11 | 0.00 | 0.85 |
Minimum of Months | 72066959.83 | 0.00 | 0.00 | 1503632.86 | 0.00 | 0.00 | 0.527958E+09 | 0.00 | 0.50 |
Maximum of Months | 0.876738E+09 | 0.469225E+09 | 0.00 | 4879861.15 | 19499373.77 | 2710067.44 | 0.164469E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154630E+10 | 535475.96 | 0.00 | 961173.12 | 4159860.76 | 25176261.82 | 0.404213E+09 | 0.00 | 0.42 |
February | 0.135995E+10 | 1277526.99 | 0.00 | 1142355.22 | 0.00 | 0.00 | 0.639096E+09 | 0.00 | 0.44 |
March | 0.157621E+10 | 0.00 | 0.00 | 1481894.93 | 3961066.67 | 4383340.65 | 0.795755E+09 | 0.00 | 0.47 |
April | 0.930220E+09 | 1399996.15 | 0.00 | 3077095.83 | 7682799.83 | 0.00 | 0.117505E+10 | 0.00 | 0.60 |
May | 0.766519E+09 | 3251027.05 | 0.00 | 4263713.37 | 8736.07 | 0.00 | 0.167257E+10 | 0.00 | 0.69 |
June | 0.355379E+09 | 49160264.45 | 0.00 | 5266014.15 | 5943930.72 | 0.00 | 0.151715E+10 | 0.00 | 0.87 |
July | 0.195104E+09 | 0.411227E+09 | 0.00 | 3261017.16 | 36917407.61 | 0.00 | 0.652459E+09 | 0.00 | 0.85 |
August | 0.203843E+09 | 0.469864E+09 | 0.00 | 2501615.94 | 49290264.40 | 0.00 | 0.477120E+09 | 0.00 | 0.84 |
September | 0.472915E+09 | 0.124237E+09 | 0.00 | 3048511.25 | 10641101.26 | 0.00 | 0.818139E+09 | 0.00 | 0.70 |
October | 0.614757E+09 | 0.231733E+09 | 0.00 | 2232875.98 | 27236019.81 | 0.00 | 0.604193E+09 | 0.00 | 0.60 |
November | 0.121537E+10 | 149403.90 | 0.00 | 1714749.60 | 2017840.57 | 0.00 | 0.805693E+09 | 0.00 | 0.47 |
December | 0.150691E+10 | 199084.17 | 0.00 | 950273.84 | 155210.68 | 1154351.49 | 0.386933E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.107435E+11 | 0.129303E+10 | 0.00 | 29901290.40 | 0.148014E+09 | 30713953.97 | 0.994838E+10 | 0.00 | 0.61 |
Minimum of Months | 0.195104E+09 | 0.00 | 0.00 | 950273.84 | 0.00 | 0.00 | 0.386933E+09 | 0.00 | 0.42 |
Maximum of Months | 0.157621E+10 | 0.469864E+09 | 0.00 | 5266014.15 | 49290264.40 | 25176261.82 | 0.167257E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.655725E+09 | 2743273.36 | 0.00 | 1957102.99 | 14233.97 | 4071613.44 | 0.801003E+09 | 0.00 | 0.50 |
February | 0.637352E+09 | 1224455.47 | 0.00 | 1988946.26 | 0.00 | 0.00 | 0.915764E+09 | 0.00 | 0.55 |
March | 0.683041E+09 | 225379.77 | 0.00 | 2756221.36 | 2296364.27 | 631637.80 | 0.115809E+10 | 0.00 | 0.62 |
April | 0.400592E+09 | 2476447.10 | 0.00 | 4581492.14 | 4439451.47 | 0.00 | 0.170161E+10 | 0.00 | 0.97 |
May | 0.354479E+09 | 3427925.00 | 0.00 | 4780857.74 | 5537.66 | 0.00 | 0.178302E+10 | 0.00 | 0.97 |
June | 0.198652E+09 | 43949019.49 | 0.00 | 5262490.98 | 2403588.56 | 0.00 | 0.135540E+10 | 0.00 | 1.20 |
July | 94215057.92 | 0.378571E+09 | 0.00 | 4243964.44 | 14094289.68 | 0.00 | 0.737359E+09 | 0.00 | 1.29 |
August | 81722285.69 | 0.509199E+09 | 0.00 | 3401066.11 | 18453714.82 | 0.00 | 0.609848E+09 | 0.00 | 1.35 |
September | 0.219296E+09 | 99618259.24 | 0.00 | 3743105.13 | 4518768.40 | 0.00 | 0.926067E+09 | 0.00 | 0.99 |
October | 0.263855E+09 | 0.181882E+09 | 0.00 | 2812571.28 | 17030544.19 | 0.00 | 0.822040E+09 | 0.00 | 0.78 |
November | 0.559283E+09 | 276483.37 | 0.00 | 2572057.43 | 1126764.38 | 0.00 | 0.105908E+10 | 0.00 | 0.60 |
December | 0.657196E+09 | 262114.71 | 0.00 | 2002905.23 | 0.00 | 0.00 | 0.697373E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.480541E+10 | 0.122386E+10 | 0.00 | 40102781.08 | 64383257.40 | 4703251.24 | 0.125666E+11 | 0.00 | 0.86 |
Minimum of Months | 81722285.69 | 225379.77 | 0.00 | 1957102.99 | 0.00 | 0.00 | 0.609848E+09 | 0.00 | 0.49 |
Maximum of Months | 0.683041E+09 | 0.509199E+09 | 0.00 | 5262490.98 | 18453714.82 | 4071613.44 | 0.178302E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.782323E+09 | 25279114.83 | 0.00 | 9611291.23 | 0.00 | 4419433.12 | 0.374592E+10 | 0.00 | 1.12 |
February | 0.861118E+09 | 4724666.76 | 0.00 | 7016216.51 | 0.00 | 0.00 | 0.297475E+10 | 0.00 | 0.98 |
March | 0.106986E+10 | 4084160.90 | 0.00 | 6394015.13 | 1172778.91 | 3255797.31 | 0.266831E+10 | 0.00 | 0.87 |
April | 0.739822E+09 | 7678470.60 | 0.00 | 6398834.45 | 5065350.15 | 0.00 | 0.226936E+10 | 0.00 | 0.95 |
May | 0.767194E+09 | 4347498.54 | 0.00 | 5175386.76 | 8751.67 | 0.00 | 0.193348E+10 | 0.00 | 0.80 |
June | 0.436973E+09 | 57516117.95 | 0.00 | 5187958.52 | 5954542.88 | 0.00 | 0.142652E+10 | 0.00 | 0.90 |
July | 0.212928E+09 | 0.490576E+09 | 0.00 | 3192121.53 | 32921614.67 | 0.00 | 0.640181E+09 | 0.00 | 0.92 |
August | 0.167297E+09 | 0.707913E+09 | 0.00 | 3430605.31 | 45704779.08 | 0.00 | 0.624298E+09 | 0.00 | 1.13 |
September | 0.326629E+09 | 0.234977E+09 | 0.00 | 6584052.05 | 5315133.53 | 0.00 | 0.159270E+10 | 0.00 | 1.21 |
October | 0.354266E+09 | 0.510920E+09 | 0.00 | 7059076.46 | 5130838.98 | 0.00 | 0.159725E+10 | 0.00 | 1.11 |
November | 0.652774E+09 | 4783236.63 | 0.00 | 10005881.95 | 261191.57 | 0.00 | 0.378433E+10 | 0.00 | 1.21 |
December | 0.740875E+09 | 1772035.88 | 0.00 | 10753007.23 | 0.00 | 0.00 | 0.340776E+10 | 0.00 | 1.14 |
Annual Sum or Average | 0.711206E+10 | 0.205457E+10 | 0.00 | 80808447.15 | 0.101535E+09 | 7675230.42 | 0.266649E+11 | 0.00 | 1.03 |
Minimum of Months | 0.167297E+09 | 1772035.88 | 0.00 | 3192121.53 | 0.00 | 0.00 | 0.624298E+09 | 0.00 | 0.80 |
Maximum of Months | 0.106986E+10 | 0.707913E+09 | 0.00 | 10753007.23 | 45704779.08 | 4419433.12 | 0.378433E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.809146E+09 | 5844306.73 | 0.00 | 1983878.45 | 686766.06 | 15107570.26 | 0.824739E+09 | 0.00 | 0.59 |
February | 0.711720E+09 | 1463711.28 | 0.00 | 2276766.99 | 0.00 | 0.00 | 0.104796E+10 | 0.00 | 0.66 |
March | 0.762538E+09 | 0.00 | 0.00 | 3065223.02 | 2501264.90 | 2744850.04 | 0.139473E+10 | 0.00 | 0.73 |
April | 0.389752E+09 | 5318852.13 | 0.00 | 5122911.57 | 2601344.28 | 212275.52 | 0.181948E+10 | 0.00 | 1.06 |
May | 0.342017E+09 | 2473087.77 | 0.00 | 5566414.08 | 0.00 | 0.00 | 0.201846E+10 | 0.00 | 1.10 |
June | 0.176137E+09 | 45467085.77 | 0.00 | 6019518.44 | 2491655.38 | 0.00 | 0.163371E+10 | 0.00 | 1.39 |
July | 98081649.82 | 0.465441E+09 | 0.00 | 4129664.75 | 14181948.50 | 0.00 | 0.720350E+09 | 0.00 | 1.38 |
August | 85410379.72 | 0.514722E+09 | 0.00 | 3223724.25 | 19098011.35 | 0.00 | 0.556653E+09 | 0.00 | 1.42 |
September | 0.183506E+09 | 0.117776E+09 | 0.00 | 4460073.94 | 3917334.96 | 0.00 | 0.111517E+10 | 0.00 | 1.16 |
October | 0.289313E+09 | 0.214789E+09 | 0.00 | 2835166.52 | 10629358.60 | 0.00 | 0.712343E+09 | 0.00 | 0.85 |
November | 0.627103E+09 | 647695.33 | 0.00 | 2829945.08 | 1029713.00 | 0.00 | 0.118173E+10 | 0.00 | 0.72 |
December | 0.788418E+09 | 307094.18 | 0.00 | 2095183.20 | 98009.72 | 175934.03 | 0.753471E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.526314E+10 | 0.137425E+10 | 0.00 | 43608470.28 | 57235406.74 | 18240629.85 | 0.137788E+11 | 0.00 | 0.97 |
Minimum of Months | 85410379.72 | 0.00 | 0.00 | 1983878.45 | 0.00 | 0.00 | 0.556653E+09 | 0.00 | 0.59 |
Maximum of Months | 0.809146E+09 | 0.514722E+09 | 0.00 | 6019518.44 | 19098011.35 | 15107570.26 | 0.201846E+10 | 0.00 | 1.42 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:12
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.189170E+12 | 0.436880E+10 | 0.00 | 0.201327E+12 | 0.289386E+11 |
February | 0.220153E+12 | 0.460382E+10 | 0.00 | 0.202211E+12 | 0.165846E+11 |
March | 0.295825E+12 | 0.520120E+10 | 0.00 | 0.210121E+12 | 0.212384E+11 |
April | 0.371568E+12 | 0.305294E+10 | 0.00 | 0.199297E+12 | 0.454168E+11 |
May | 0.385375E+12 | 0.335347E+10 | 0.00 | 0.208206E+12 | 0.471002E+11 |
June | 0.377741E+12 | 0.186072E+10 | 0.00 | 0.161855E+12 | 0.879306E+11 |
July | 0.403484E+12 | 0.567404E+09 | 0.00 | 0.941572E+11 | 0.148065E+12 |
August | 0.376955E+12 | 0.556425E+09 | 0.00 | 0.711179E+11 | 0.170295E+12 |
September | 0.303757E+12 | 0.141902E+10 | 0.00 | 0.138532E+12 | 0.103692E+12 |
October | 0.221076E+12 | 0.198235E+10 | 0.00 | 0.147425E+12 | 0.112246E+12 |
November | 0.202628E+12 | 0.413368E+10 | 0.00 | 0.223540E+12 | 0.310772E+11 |
December | 0.174508E+12 | 0.443149E+10 | 0.00 | 0.222614E+12 | 0.332774E+11 |
Annual Sum or Average | 0.352224E+13 | 0.355313E+11 | 0.00 | 0.208040E+13 | 0.845862E+12 |
Minimum of Months | 0.174508E+12 | 0.556425E+09 | 0.00 | 0.711179E+11 | 0.165846E+11 |
Maximum of Months | 0.403484E+12 | 0.520120E+10 | 0.00 | 0.223540E+12 | 0.170295E+12 |