Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:20:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1736.44 | 348.53 | 348.53 |
Net Site Energy | 1736.44 | 348.53 | 348.53 |
Total Source Energy | 4758.04 | 955.01 | 955.01 |
Net Source Energy | 4758.04 | 955.01 | 955.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 355.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 52.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1380.58 | 355.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 355.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 97.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 52.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 355.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 198.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 97.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 52.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 70.34 | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.10 | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 70.34 | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.10 | 71.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1380.576 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1380.576 | 100.00 |
Total On-Site and Utility Electric Sources | 1380.576 | 100.00 |
Total Electricity End Uses | 1380.576 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 326.17 |
Time Setpoint Not Met During Occupied Cooling | 127.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2451.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 19-JUN-10:50 | 02-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 04-JAN-12:09 |
Heating | 0.00 | 254141.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71586.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41666.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26169.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4464.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 164976.42 | 254141.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 254141.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 71586.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 53.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26169.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4464.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 385.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 628.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 737.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 307.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 167.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4372.28 | 385.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 877.58 | 77.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 77.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 877.58 | 77.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.49 | 0.300674 | 0.256000 | 0.638100 | 0.801799 | 0.500000 | 0.001267 | 0.000121 | 0.638100 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.01 | 0.373702 | 0.318000 | 0.637745 | 0.996538 | 0.500000 | 0.001020 | 0.000187 | 0.637745 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.16 | 0.347328 | 0.295000 | 0.636543 | 0.926208 | 0.500000 | 0.001097 | 0.000323 | 1.10 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.684478 | 0.230821 | 0.196000 | 0.134158 | 0.615522 | 0.500000 | 0.001651 | 0.000152 | 0.520341 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.759282 | 0.131732 | 0.112000 | 0.085040 | 0.351285 | 0.500000 | 0.002892 | 0.000099 | 0.337751 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.935578 | 0.168871 | 0.144000 | 0.134723 | 0.450322 | 0.500000 | 0.002256 | 0.000151 | 0.515878 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.821623 | 0.121729 | 0.103000 | 0.084627 | 0.324610 | 0.500000 | 0.003130 | 0.000100 | 0.340453 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.542850 | 0.291041 | 0.247000 | 0.134084 | 0.776109 | 0.500000 | 0.001309 | 0.000116 | 0.394724 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.628493 | 0.159145 | 0.135000 | 0.084847 | 0.424388 | 0.500000 | 0.002394 | 0.000076 | 0.257889 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.756820 | 0.208757 | 0.177000 | 0.133957 | 0.556686 | 0.500000 | 0.001825 | 0.000115 | 0.390875 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.646151 | 0.154786 | 0.132000 | 0.085292 | 0.412763 | 0.500000 | 0.002461 | 0.000076 | 0.260381 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.593254 | 0.266314 | 0.226000 | 0.134075 | 0.710170 | 0.500000 | 0.001431 | 0.000120 | 0.409689 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.734811 | 0.362984 | 0.500000 | 0.002799 | 0.000078 | 0.267207 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.843277 | 0.187354 | 0.159000 | 0.134081 | 0.499612 | 0.500000 | 0.002034 | 0.000119 | 0.405594 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.754414 | 0.132573 | 0.113000 | 0.085249 | 0.353529 | 0.500000 | 0.002874 | 0.000079 | 0.269636 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 13831.85 | 0.000121 | 314.99 |
CORE_MID VAV BOX REHEAT COIL | 21377.61 | 0.000187 | 563.86 |
CORE_TOP VAV BOX REHEAT COIL | 36964.01 | 0.000323 | 975.76 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17431.18 | 0.000152 | 459.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11313.96 | 0.000099 | 298.33 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17281.91 | 0.000151 | 455.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11404.33 | 0.000100 | 300.71 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13230.09 | 0.000116 | 348.95 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8643.15 | 0.000076 | 227.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13101.35 | 0.000115 | 345.55 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8726.54 | 0.000076 | 230.16 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13730.35 | 0.000120 | 362.13 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8954.60 | 0.000078 | 236.16 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13593.39 | 0.000119 | 358.52 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9035.83 | 0.000079 | 238.30 |
PACU_VAV_BOT HEATING COIL | 24091.94 | 0.000211 | 399.80 |
PACU_VAV_MID HEATING COIL | 24852.52 | 0.000217 | 408.71 |
PACU_VAV_TOP HEATING COIL | 24085.32 | 0.000211 | 402.39 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.53 | 1.08 | 5.07 | 1.73 | 4.53 | 4.53 | 0.300000 | 0.381671 | 4.53 |
PACU_VAV_MID | 2.47 | 1.08 | 4.93 | 1.99 | 4.22 | 4.22 | 0.300000 | 0.470470 | 4.22 |
PACU_VAV_TOP | 2.68 | 1.08 | 5.36 | 2.82 | 4.91 | 4.91 | 0.300000 | 0.573504 | 4.91 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.53 |
PACU_VAV_MID_OA_CONTROLLER | 4.22 |
PACU_VAV_TOP_OA_CONTROLLER | 4.91 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.53 | 97145.01 | 0.749731 | 1.51 | 32378.43 | 0.749731 |
PACU_VAV_MID COOLING COIL | 4.22 | 92267.96 | 0.743372 | 1.41 | 30752.91 | 0.743372 |
PACU_VAV_TOP COOLING COIL | 4.91 | 103652.34 | 0.755223 | 1.64 | 34547.33 | 0.755223 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.53 |
PACU_VAV_MID FAN | 4.22 |
PACU_VAV_TOP FAN | 4.91 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000211 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000217 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000211 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002551 | 0.306178 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.002551 | 760.79 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 291649.93 | 291649.93 | 0.002551 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1187E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2249E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8114E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8556E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1563 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9739E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1765 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9275E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1119 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6836E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1124E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1190E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2194E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2251E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8115E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8575E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7428E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9320E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2596E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5853E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6333E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3432E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1671E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1914E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7866E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8041E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6390E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6450E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3163E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3697E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6519E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1524E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1828E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0803E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3362E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1402E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7783E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9035E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2280E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3164E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3700E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6094E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6517E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1521E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1813E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4526E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7922E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9000E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4113E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3865E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2276E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9946E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0637E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5721E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6477E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4945E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5233E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1550 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.6090E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1720 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1070 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1194 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9373E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5226E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8067E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0667E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4757E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.4791E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2519E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6586E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0538E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.6548E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3959E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4190E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7955E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2420E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6743E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7191E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3111E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2399E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1418E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1550 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.6081E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1720 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1069 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1194 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9365E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5225E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8064E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0666E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4754E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.4787E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2515E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6588E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0537E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.6549E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3958E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4187E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7954E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2419E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6741E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7190E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3109E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2395E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1415E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34591.35140 | 34591.35140 | 2.49258 | 2.49258 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7409.99283 | 7409.99283 | 0.31065 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27859.05600 | 27859.05600 | 2.00549 | 2.00549 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 14959.32706 | 14959.32706 | 0.63340 | 0.63340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29684.39741 | 29684.39741 | 2.15777 | 2.15777 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 25885.50925 | 25885.50925 | 1.10080 | 1.10080 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9416.00339 | 9416.00339 | 0.68448 | 0.68448 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12199.11042 | 12199.11042 | 0.52034 | 0.52034 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10445.11451 | 10445.11451 | 0.75928 | 0.75928 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7917.92000 | 7917.92000 | 0.33775 | 0.33775 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12870.30447 | 12870.30447 | 0.93558 | 0.93558 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12094.75580 | 12094.75580 | 0.51588 | 0.51588 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11302.72930 | 11302.72930 | 0.82162 | 0.82162 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 7981.10084 | 7981.10084 | 0.34045 | 0.34045 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7467.84872 | 7467.84872 | 0.54285 | 0.54285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9260.82583 | 9260.82583 | 0.39472 | 0.39472 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8646.07695 | 8646.07695 | 0.62849 | 0.62849 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6049.83709 | 6049.83709 | 0.25789 | 0.25789 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10411.40835 | 10411.40835 | 0.75682 | 0.75682 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9170.86390 | 9170.86390 | 0.39088 | 0.39088 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8889.00083 | 8889.00083 | 0.64615 | 0.64615 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6108.11305 | 6108.11305 | 0.26038 | 0.26038 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8161.12948 | 8161.12948 | 0.59325 | 0.59325 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9611.42238 | 9611.42238 | 0.40969 | 0.40969 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10108.55908 | 10108.55908 | 0.73481 | 0.73481 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6268.16927 | 6268.16927 | 0.26721 | 0.26721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11600.64339 | 11600.64339 | 0.84328 | 0.84328 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9515.68990 | 9515.68990 | 0.40559 | 0.40559 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10378.22951 | 10378.22951 | 0.75441 | 0.75441 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6324.94528 | 6324.94528 | 0.26964 | 0.26964 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 70708.32 | 4.52892 | 4.52892 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 26798.41 | 1.72856 | 1.72856 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66520.79 | 4.22031 | 4.22031 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 27122.50 | 1.98553 | 1.98553 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 75830.89 | 4.90881 | 4.90881 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 27095.11 | 2.81523 | 2.81523 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49258 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30067 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63810 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80180 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26715E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21007E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63810 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13831.84725 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21007E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 314.99321 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00549 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37370 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63775 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99654 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01953E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87021E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63775 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21377.61106 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87021E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.86453 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15777 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34733 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63654 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92621 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09695E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23377E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10080 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36964.00846 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23377E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 975.75741 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68448 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23082 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13416 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61552 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65063E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52496E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52034 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17431.17515 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52496E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.63954 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75928 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13173 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50396E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35129 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89223E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.89795E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33775 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11313.96075 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.89795E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.32924 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93558 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16887 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13472 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45032 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25616E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51190E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51588 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17281.90566 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51190E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 455.70641 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82162 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12173 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46272E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32461 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12991E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.97701E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34045 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11404.33477 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.97701E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.71050 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54285 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29104 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77611 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30909E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15743E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39472 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13230.08829 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15743E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 348.94665 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62849 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15915 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13500 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48465E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42439 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39404E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.56141E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25789 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8643.15359 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.56141E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.95810 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75682 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20876 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17700 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13396 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55669 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82509E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14616E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39088 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13101.34761 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14616E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 345.55404 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64615 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15479 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52919E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41276 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46146E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.63436E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26038 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8726.54418 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.63436E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.15557 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59325 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26631 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71017 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43064E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20119E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40969 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13730.35226 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20119E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.12519 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73481 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36298 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79902E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.83388E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26721 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8954.60292 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.83388E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 236.16204 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84328 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18735 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15900 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13408 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49961 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03358E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18921E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40559 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13593.38810 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18921E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 358.51610 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75441 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13257 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52488E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35353 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87388E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.90494E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26964 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9035.82933 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.90494E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 238.30235 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.53345 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07628 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.06689 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72856 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.52892 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.52892 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.38167 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.46562 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07639 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.93125 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.98553 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.22031 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.22031 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.47047 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.67937 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07509 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.35873 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.81523 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.90881 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.90881 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.57350 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.52892 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.22031 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.90881 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.52892 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.52892 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97145.01318 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74973 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.50949 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32378.43289 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74973 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 24091.94136 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10767E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 399.80413 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.52892 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.10767E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.22031 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.22031 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 92267.96008 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74337 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.40663 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 30752.91109 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74337 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 24852.51989 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17421E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 408.71466 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.22031 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.17421E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.90881 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.90881 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103652.34222 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75522 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63611 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34547.32566 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75522 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 24085.31841 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10709E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 402.39498 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.90881 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.10709E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.55148E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.30618 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.55148E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 760.78611 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 291649.92903 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 291649.93000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.55148E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 13106.98 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 20254.30 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 35026.91 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16514.35 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10718.84 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16372.95 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10804.44 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12534.79 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8188.87 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12412.84 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8267.87 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13008.66 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8483.88 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 12878.92 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8560.83 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 18858.92 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 19098.52 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 19111.95 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 96509.31 | 329303.43 | 12.20 | 3.14 | 3.49 | 3.68 | 3.86 | 10.72 | 11.92 | 12.55 | 13.16 | 5.2357 | 4.1736 | 2.8043 | 1.1521 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 91726.99 | 312985.49 | 12.24 | 3.15 | 3.51 | 3.69 | 3.86 | 10.75 | 11.96 | 12.60 | 13.19 | 4.8789 | 3.8879 | 2.6137 | 1.0790 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 102914.88 | 351160.16 | 12.16 | 3.13 | 3.48 | 3.66 | 3.85 | 10.69 | 11.88 | 12.50 | 13.13 | 5.6749 | 4.5162 | 3.0437 | 1.2430 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.7535330831E-002 | 3.2459765239E-002 | Pass | Pass | 0.4872651015 | 0.4921773440 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1482529787 | 0.1106691600 | Pass | Pass | 0.5105028335 | 0.4923857093 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.0970188070E-002 | 4.3855941058E-002 | Pass | Pass | 0.4880290314 | 0.4817332768 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.5115921835E-002 | 4.2716749073E-002 | Pass | Pass | 0.4857669238 | 0.4774362466 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.1154691980E-002 | 8.6810756375E-003 | Pass | Pass | 0.4892158913 | 0.4904805330 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1030431848 | 0.1223349263 | Pass | Pass | 9.2436008162 | 43.1454242110 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5326921321 | 0.4878752952 | Pass | Pass | 4.0989353769 | 23.6203550929 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4592675382 | 0.5042601480 | Pass | Pass | 15.7549144516 | 111.4673260895 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4012900636 | 0.4332563352 | Pass | Pass | 5.2200889731 | 54.2899405076 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5236834215 | 0.5185883948 | Pass | Pass | 11.4326307116 | 51.6246031570 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3314720027 | 0.3071831765 | Pass | Pass | 9.2229451125 | 40.7574003985 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2470280956 | 0.2977148167 | Pass | Pass | 15.1604911848 | 99.3503131779 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1819157698 | 0.1849847005 | Pass | Pass | 9.1771831048 | 87.9270585944 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3076358380 | 0.3241520111 | Pass | Pass | 13.6853973452 | 80.8491043570 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3779084707 | 0.3529364646 | Pass | Pass | 11.1374094903 | 73.2121946329 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3214356190 | 0.3648384298 | Pass | Pass | 11.7473233502 | 68.4599512023 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2889474757 | 0.2950163692 | Pass | Pass | 1.1948989907 | 3.8318431814 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3646819415 | 0.3802838784 | Pass | Pass | 21.0541039799 | 125.6432700159 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3575.20 | 73.75 | 0.00 | 1513.35 | 1181.32 | 6343.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.14 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.06 | 0.0000 | Y | 4.28 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 6.69 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 4.24 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.08 | 0.0000 | Y | 6.76 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.81 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.14 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.06 | 0.0000 | Y | 4.28 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.80 | 0.0000 | Y | 6.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.85 | 0.0000 | Y | 4.24 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.74 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.43 | 42.43 | 4.49 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.64 | 63.04 | 4.82 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.64 | 46.90 | 41.51 | |
Exterior Lighting Total | 5686.19 | 50.82 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 291649.93 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97145.01 | 72832.59 | 24312.42 | 0.75 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 92267.96 | 68589.42 | 23678.54 | 0.74 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103652.34 | 78280.68 | 25371.66 | 0.76 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 96509.3 | 3.14 | 10.72 | N/A | N/A | 12.20 | |
PACU_VAV_MID COOLING COIL | 91727.0 | 3.15 | 10.75 | N/A | N/A | 12.24 | |
PACU_VAV_TOP COOLING COIL | 102914.9 | 3.13 | 10.69 | N/A | N/A | 12.16 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 13831.85 | 13106.98 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 21377.61 | 20254.30 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 36964.01 | 35026.91 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17431.18 | 16514.35 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11313.96 | 10718.84 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17281.91 | 16372.95 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11404.33 | 10804.44 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13230.09 | 12534.79 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8643.15 | 8188.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13101.35 | 12412.84 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8726.54 | 8267.87 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13730.35 | 13008.66 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8954.60 | 8483.88 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13593.39 | 12878.92 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9035.83 | 8560.83 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 24091.94 | 18858.92 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 24852.52 | 19098.52 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 24085.32 | 19111.95 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.53 | 9913.86 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.22 | 9238.31 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.91 | 10745.45 | 2189.01 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002551 | 760.79 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96509.31 | 3.14 | 10.72 | 12.20 | 5.2357 | 3.49 | 11.92 | 4.1736 | 3.68 | 12.55 | 2.8043 | 3.86 | 13.16 | 1.1521 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 91726.99 | 3.15 | 10.75 | 12.24 | 4.8789 | 3.51 | 11.96 | 3.8879 | 3.69 | 12.60 | 2.6137 | 3.86 | 13.19 | 1.0790 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102914.88 | 3.13 | 10.69 | 12.16 | 5.6749 | 3.48 | 11.88 | 4.5162 | 3.66 | 12.50 | 3.0437 | 3.85 | 13.13 | 1.2430 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34591.35 | 34591.35 | 35.17 | 2.493 | 2.493 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 27859.06 | 27859.06 | 28.33 | 2.005 | 2.005 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 29684.40 | 29684.40 | 30.18 | 2.158 | 2.158 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00890 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9416.00 | 9416.00 | 45.41 | 0.684 | 0.684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10445.11 | 10445.11 | 79.57 | 0.759 | 0.759 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00874 | 28.45 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12870.30 | 12870.30 | 62.07 | 0.936 | 0.936 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00880 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11302.73 | 11302.73 | 86.11 | 0.822 | 0.822 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00872 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7467.85 | 7467.85 | 36.02 | 0.543 | 0.543 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00893 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8646.08 | 8646.08 | 65.87 | 0.628 | 0.628 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00874 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10411.41 | 10411.41 | 50.21 | 0.757 | 0.757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00881 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8889.00 | 8889.00 | 67.72 | 0.646 | 0.646 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00873 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8161.13 | 8161.13 | 39.36 | 0.593 | 0.593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10108.56 | 10108.56 | 77.01 | 0.735 | 0.735 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00873 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11600.64 | 11600.64 | 55.95 | 0.843 | 0.843 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00881 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10378.23 | 10378.23 | 79.07 | 0.754 | 0.754 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7409.99 | 7409.99 | 7.53 | 0.311 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 14959.33 | 14959.33 | 15.21 | 0.633 | 0.633 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 25885.51 | 25885.51 | 26.32 | 1.101 | 1.101 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12199.11 | 12199.11 | 58.84 | 0.520 | 0.520 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7917.92 | 7917.92 | 60.32 | 0.338 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12094.76 | 12094.76 | 58.33 | 0.516 | 0.516 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 7981.10 | 7981.10 | 60.81 | 0.340 | 0.340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9260.83 | 9260.83 | 44.67 | 0.395 | 0.395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6049.84 | 6049.84 | 46.09 | 0.258 | 0.258 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9170.86 | 9170.86 | 44.23 | 0.391 | 0.391 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6108.11 | 6108.11 | 46.54 | 0.260 | 0.260 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9611.42 | 9611.42 | 46.36 | 0.410 | 0.410 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6268.17 | 6268.17 | 47.75 | 0.267 | 0.267 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9515.69 | 9515.69 | 45.89 | 0.406 | 0.406 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6324.95 | 6324.95 | 48.19 | 0.270 | 0.270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.53 | 4.53 | 1.73 | 1.73 | 4.5289 | 1.7286 | 4.5289 | 0.3817 | 0.3000 |
PACU_VAV_MID | 4.22 | 4.22 | 1.99 | 1.99 | 4.2203 | 1.9855 | 4.2203 | 0.4705 | 0.3000 |
PACU_VAV_TOP | 4.91 | 4.91 | 2.82 | 2.82 | 4.9088 | 2.8152 | 4.9088 | 0.5735 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 13831.847 | 13831.847 | 0.638100 | 0.00012101 | 314.993 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13831.85 | 13831.85 | 0.638100 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 7409.99 | 0.00 | 13878.90 | 13878.90 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21377.611 | 21377.611 | 0.637745 | 0.00018702 | 563.865 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21377.61 | 21377.61 | 0.637745 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 14959.33 | 0.00 | 21448.33 | 21448.33 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 36964.008 | 36964.008 | 1.100802 | 0.00032338 | 975.757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36964.01 | 36964.01 | 1.100802 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 25885.51 | 0.00 | 37091.89 | 37091.89 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17431.175 | 17431.175 | 0.520341 | 0.00015250 | 459.640 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17431.18 | 17431.18 | 0.520341 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763256 | 49.3528 | 12199.11 | 0.00 | 17487.88 | 17487.88 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11313.961 | 11313.961 | 0.337751 | 0.00009898 | 298.329 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11313.96 | 11313.96 | 0.337751 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762492 | 49.3042 | 7917.92 | 0.00 | 11350.72 | 11350.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17281.906 | 17281.906 | 0.515878 | 0.00015119 | 455.706 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17281.91 | 17281.91 | 0.515878 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762889 | 49.3294 | 12094.76 | 0.00 | 17338.15 | 17338.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11404.335 | 11404.335 | 0.340453 | 0.00009977 | 300.710 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11404.33 | 11404.33 | 0.340453 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762828 | 49.3256 | 7981.10 | 0.00 | 11441.38 | 11441.38 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13230.088 | 13230.088 | 0.394724 | 0.00011574 | 348.947 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13230.09 | 13230.09 | 0.394724 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00765220 | 49.4773 | 9260.83 | 0.00 | 13273.74 | 13273.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8643.154 | 8643.154 | 0.257889 | 0.00007561 | 227.958 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8643.15 | 8643.15 | 0.257889 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00765957 | 49.5244 | 6049.84 | 0.00 | 8671.62 | 8671.62 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13101.348 | 13101.348 | 0.390875 | 0.00011462 | 345.554 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13101.35 | 13101.35 | 0.390875 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764300 | 49.4187 | 9170.86 | 0.00 | 13144.60 | 13144.60 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8726.544 | 8726.544 | 0.260381 | 0.00007634 | 230.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8726.54 | 8726.54 | 0.260381 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766750 | 49.5749 | 6108.11 | 0.00 | 8755.27 | 8755.27 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13730.352 | 13730.352 | 0.409689 | 0.00012012 | 362.125 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13730.35 | 13730.35 | 0.409689 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00756476 | 48.9198 | 9611.42 | 0.00 | 13775.54 | 13775.54 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8954.603 | 8954.603 | 0.267207 | 0.00007834 | 236.162 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8954.60 | 8954.60 | 0.267207 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00756399 | 48.9149 | 6268.17 | 0.00 | 8984.02 | 8984.02 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13593.388 | 13593.388 | 0.405594 | 0.00011892 | 358.516 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13593.39 | 13593.39 | 0.405594 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00755734 | 48.8724 | 9515.69 | 0.00 | 13638.15 | 13638.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9035.829 | 9035.829 | 0.269636 | 0.00007905 | 238.302 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9035.83 | 9035.83 | 0.269636 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00757013 | 48.9541 | 6324.95 | 0.00 | 9065.50 | 9065.50 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 97145.013 | 72832.593 | 4.528922 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 98993.98 | 78543.47 | 4.528922 | 25.71 | 18.19 | 0.00997199 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 21.1110 | 24.00 | 0.00886207 | 47.6591 | 62303.78 | 0.00 | 100169.55 | 73941.25 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 24091.941 | 24091.941 | 1.358676 | 0.00021077 | 399.804 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24091.94 | 24091.94 | 1.358676 | -1.86 | -1.86 | 0.00323460 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 70.3700 | 19.37 | 0.00681014 | 48.7706 | 14034.99 | 0.00 | 22819.68 | 22819.68 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 92267.960 | 68589.424 | 4.220313 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 94312.75 | 73740.89 | 4.220313 | 25.83 | 18.33 | 0.01009101 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 22.6547 | 24.00 | 0.00891081 | 47.9178 | 58050.35 | 0.00 | 95140.65 | 69654.42 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 24852.520 | 24852.520 | 1.266094 | 0.00021742 | 408.715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24852.52 | 24852.52 | 1.266094 | -3.43 | -3.43 | 0.00290746 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 75.5157 | 17.74 | 0.00721388 | 57.1609 | 15016.37 | 0.00 | 23106.67 | 23106.67 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 103652.342 | 78280.679 | 4.908813 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 105366.86 | 84436.64 | 4.908813 | 25.58 | 18.08 | 0.00988841 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 19.4772 | 24.00 | 0.00886452 | 47.6724 | 67506.65 | 0.00 | 106879.48 | 79466.15 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 24085.318 | 24085.318 | 1.472644 | 0.00021071 | 402.395 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24085.32 | 24085.32 | 1.472644 | -0.72 | -0.72 | 0.00356635 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 64.9240 | 17.41 | 0.00709179 | 57.3832 | 19374.80 | 0.00 | 23128.22 | 23128.22 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 13831.847 | 13831.847 | 0.638100 | 0.00012101 | 314.993 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 4.6491 | 4.742620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13831.85 | 13831.85 | 1.0000 | 0.76801419 | 0.638100 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.12099469 | 60.00 | 32.22 | 27.78 | 0.000 | 13831.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 7409.99 | 0.00 | 13878.90 | 13878.90 | 0.76801419 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.52 | 18.21 | 0.00800000 | 51131.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 21377.611 | 21377.611 | 0.637745 | 0.00018702 | 563.865 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 7.1853 | 7.329887 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21377.61 | 21377.61 | 1.0000 | 0.76758719 | 0.637745 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.18700159 | 60.00 | 32.22 | 27.78 | 0.000 | 21377.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 14959.33 | 0.00 | 21448.33 | 21448.33 | 0.76758719 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.4 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 36964.008 | 36964.008 | 1.100802 | 0.00032338 | 975.757 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 12.4241 | 12.674102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36964.01 | 36964.01 | 1.0000 | 1.32492019 | 1.100802 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.32334428 | 60.00 | 32.22 | 27.78 | 0.000 | 36964.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 25885.51 | 0.00 | 37091.89 | 37091.89 | 1.32492019 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61055.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17431.175 | 17431.175 | 0.520341 | 0.00015250 | 459.640 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 5.8588 | 5.976746 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17431.18 | 17431.18 | 1.0000 | 0.62627970 | 0.520341 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.15247997 | 60.00 | 32.22 | 27.78 | 0.000 | 17431.18 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763256 | 21.00 | 0.00763256 | 49.3528 | 12199.11 | 0.00 | 17487.88 | 17487.88 | 0.62627970 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11313.961 | 11313.961 | 0.337751 | 0.00009898 | 298.329 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 3.8028 | 3.879295 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11313.96 | 11313.96 | 1.0000 | 0.40651565 | 0.337751 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09896937 | 60.00 | 32.22 | 27.78 | 0.000 | 11313.96 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00762492 | 21.00 | 0.00762492 | 49.3042 | 7917.92 | 0.00 | 11350.72 | 11350.72 | 0.40651565 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17281.906 | 17281.906 | 0.515878 | 0.00015119 | 455.706 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 5.8087 | 5.925565 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17281.91 | 17281.91 | 1.0000 | 0.62090793 | 0.515878 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.15117423 | 60.00 | 32.22 | 27.78 | 0.000 | 17281.91 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00762889 | 21.00 | 0.00762889 | 49.3294 | 12094.76 | 0.00 | 17338.15 | 17338.15 | 0.62090793 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11404.335 | 11404.335 | 0.340453 | 0.00009977 | 300.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 3.8331 | 3.910282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11404.33 | 11404.33 | 1.0000 | 0.40976803 | 0.340453 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09975992 | 60.00 | 32.22 | 27.78 | 0.000 | 11404.33 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00762828 | 21.00 | 0.00762828 | 49.3256 | 7981.10 | 0.00 | 11441.38 | 11441.38 | 0.40976803 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13230.088 | 13230.088 | 0.394724 | 0.00011574 | 348.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 4.4468 | 4.536291 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13230.09 | 13230.09 | 1.0000 | 0.47508738 | 0.394724 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11573078 | 60.00 | 32.22 | 27.78 | 0.000 | 13230.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00765220 | 21.00 | 0.00765220 | 49.4773 | 9260.83 | 0.00 | 13273.74 | 13273.74 | 0.47508738 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8643.154 | 8643.154 | 0.257889 | 0.00007561 | 227.958 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 2.9051 | 2.963537 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8643.15 | 8643.15 | 1.0000 | 0.31039341 | 0.257889 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07560636 | 60.00 | 32.22 | 27.78 | 0.000 | 8643.15 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00765957 | 21.00 | 0.00765957 | 49.5244 | 6049.84 | 0.00 | 8671.62 | 8671.62 | 0.31039341 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13101.348 | 13101.348 | 0.390875 | 0.00011462 | 345.554 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 4.4035 | 4.492148 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13101.35 | 13101.35 | 1.0000 | 0.47045557 | 0.390875 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11460461 | 60.00 | 32.22 | 27.78 | 0.000 | 13101.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764300 | 21.00 | 0.00764300 | 49.4187 | 9170.86 | 0.00 | 13144.60 | 13144.60 | 0.47045557 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8726.544 | 8726.544 | 0.260381 | 0.00007634 | 230.156 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 2.9331 | 2.992130 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8726.54 | 8726.54 | 1.0000 | 0.31339383 | 0.260381 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07633583 | 60.00 | 32.22 | 27.78 | 0.000 | 8726.54 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766750 | 21.00 | 0.00766750 | 49.5749 | 6108.11 | 0.00 | 8755.27 | 8755.27 | 0.31339383 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13730.352 | 13730.352 | 0.409689 | 0.00012012 | 362.125 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 4.6149 | 4.707820 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13730.35 | 13730.35 | 1.0000 | 0.49309944 | 0.409689 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.12010686 | 60.00 | 32.22 | 27.78 | 0.000 | 13730.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00756476 | 21.00 | 0.00756476 | 48.9198 | 9611.42 | 0.00 | 13775.54 | 13775.54 | 0.49309944 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8954.603 | 8954.603 | 0.267207 | 0.00007834 | 236.162 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 3.0098 | 3.070326 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8954.60 | 8954.60 | 1.0000 | 0.32160903 | 0.267207 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07833078 | 60.00 | 32.22 | 27.78 | 0.000 | 8954.60 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00756399 | 21.00 | 0.00756399 | 48.9149 | 6268.17 | 0.00 | 8984.02 | 8984.02 | 0.32160903 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13593.388 | 13593.388 | 0.405594 | 0.00011892 | 358.516 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 4.5689 | 4.660858 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13593.39 | 13593.39 | 1.0000 | 0.48817105 | 0.405594 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11890876 | 60.00 | 32.22 | 27.78 | 0.000 | 13593.39 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00755734 | 21.00 | 0.00755734 | 48.8724 | 9515.69 | 0.00 | 13638.15 | 13638.15 | 0.48817105 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9035.829 | 9035.829 | 0.269636 | 0.00007905 | 238.302 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 3.0371 | 3.098176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9035.83 | 9035.83 | 1.0000 | 0.32453195 | 0.269636 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07904131 | 60.00 | 32.22 | 27.78 | 0.000 | 9035.83 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00757013 | 21.00 | 0.00757013 | 48.9541 | 6324.95 | 0.00 | 9065.50 | 9065.50 | 0.32453195 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.9 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97145.013 | 72832.593 | 4.528922 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3774 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.528922 | 5.45098729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 98993.98 | 78543.47 | 1.0190 | 5.45098729 | 4.528922 | 25.71 | 18.19 | 0.00997199 | 51249.3 | 11.02 | 11.02 | 0.00850000 | 32508.3 | -999.0 | -999.00 | -999.00 | -999.00 | 9913.859 | 89080.12 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 21.1110 | 24.00 | 0.00886207 | 24.00 | 0.00886207 | 47.6591 | 62303.78 | 0.00 | 100169.55 | 73941.25 | 5.23571450 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.85 | 12.83 | 0.00922055 | 36190.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24091.941 | 24091.941 | 1.358676 | 0.00021077 | 399.804 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.528922 | 5.45098729 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 8.0976 | 8.260568 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24091.94 | 24091.94 | 1.0000 | 1.63529619 | 1.358676 | -1.86 | -1.86 | 0.00323460 | 6208.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.21074531 | 60.00 | 32.22 | 27.78 | 0.000 | 24091.94 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 70.3700 | 19.13 | 0.00734494 | 19.37 | 0.00681014 | 48.7706 | 14034.99 | 0.00 | 22819.68 | 22819.68 | 1.63529619 | 2.80 | 0.86 | 0.00323460 | 10919.9 | 16.60 | 8.10 | 0.00323460 | 24874.4 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 92267.960 | 68589.424 | 4.220313 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5987 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.220313 | 5.07954699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 94312.75 | 73740.89 | 1.0222 | 5.07954699 | 4.220313 | 25.83 | 18.33 | 0.01009101 | 51680.8 | 11.02 | 11.02 | 0.00850000 | 32508.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9238.311 | 85074.44 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 22.6547 | 24.00 | 0.00891081 | 24.00 | 0.00891081 | 47.9178 | 58050.35 | 0.00 | 95140.65 | 69654.42 | 4.87894329 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.70 | 12.69 | 0.00913656 | 35822.1 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24852.520 | 24852.520 | 1.266094 | 0.00021742 | 408.715 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.220313 | 5.07954699 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 8.3532 | 8.521353 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24852.52 | 24852.52 | 1.0000 | 1.52386410 | 1.266094 | -3.43 | -3.43 | 0.00290746 | 3806.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.21739851 | 60.00 | 32.22 | 27.78 | 0.000 | 24852.52 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 75.5157 | 18.99 | 0.00723639 | 17.74 | 0.00721388 | 57.1609 | 15016.37 | 0.00 | 23106.67 | 23106.67 | 1.52386410 | 2.80 | 0.39 | 0.00290746 | 10100.1 | 17.81 | 8.29 | 0.00290746 | 25263.3 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103652.342 | 78280.679 | 4.908813 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2221 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.908813 | 5.90822257 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 105366.86 | 84436.64 | 1.0165 | 5.90822257 | 4.908813 | 25.58 | 18.08 | 0.00988841 | 50901.3 | 11.02 | 11.02 | 0.00850000 | 32508.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10745.445 | 94621.41 | 32.10 | 0.01411964 | 23.13 | 0.95610000 | 19.4772 | 24.00 | 0.00886452 | 24.00 | 0.00886452 | 47.6724 | 67506.65 | 0.00 | 106879.48 | 79466.15 | 5.67489244 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.97 | 12.95 | 0.00929068 | 36488.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24085.318 | 24085.318 | 1.472644 | 0.00021071 | 402.395 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.908813 | 5.90822257 | 4197.9300 | 999.8980 | 2.55122053 | 54.44 | 82.22 | 27.78 | 297519.50 | 8.0954 | 8.258297 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24085.32 | 24085.32 | 1.0000 | 1.77246677 | 1.472644 | -0.72 | -0.72 | 0.00356635 | 8188.1 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.21068738 | 60.00 | 32.22 | 27.78 | 0.000 | 24085.32 | -10.70 | 0.00150390 | -10.70 | 0.95610000 | 64.9240 | 17.74 | 0.00738387 | 17.41 | 0.00709179 | 57.3832 | 19374.80 | 0.00 | 23128.22 | 23128.22 | 1.77246677 | 2.80 | 1.34 | 0.00356635 | 11751.3 | 15.70 | 8.06 | 0.00356635 | 24800.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.53 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.22 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2612.67 | 2304.17 | 42.50 |
CORE_MID | 2474.00 | 3048.17 | 360.00 |
CORE_TOP | 2989.00 | 3320.00 | 1052.33 |
PERIMETER_TOP_ZN_3 | 3767.17 | 3649.33 | 1977.33 |
PERIMETER_TOP_ZN_2 | 3778.33 | 3442.50 | 1751.67 |
PERIMETER_TOP_ZN_1 | 3586.00 | 3185.83 | 1442.33 |
PERIMETER_TOP_ZN_4 | 3822.17 | 3461.17 | 1824.17 |
PERIMETER_BOT_ZN_3 | 3477.33 | 3607.00 | 1618.50 |
PERIMETER_BOT_ZN_2 | 3438.83 | 3211.00 | 1226.00 |
PERIMETER_BOT_ZN_1 | 3320.17 | 3457.50 | 1326.50 |
PERIMETER_BOT_ZN_4 | 3507.67 | 3274.83 | 1326.33 |
PERIMETER_MID_ZN_3 | 3469.33 | 3422.33 | 1507.17 |
PERIMETER_MID_ZN_2 | 2984.67 | 2814.83 | 1206.00 |
PERIMETER_MID_ZN_1 | 3319.50 | 2931.67 | 997.67 |
PERIMETER_MID_ZN_4 | 3540.50 | 3237.50 | 1373.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4954.00 | 4231.67 | 2451.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.83 | 0.33 | 2.83 | 0.17 |
CORE_MID | 5.17 | 0.00 | 4.50 | 0.00 |
CORE_TOP | 9.67 | 0.00 | 8.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 51.50 | 7.00 | 31.33 | 6.33 |
PERIMETER_TOP_ZN_2 | 31.17 | 40.50 | 10.50 | 39.50 |
PERIMETER_TOP_ZN_1 | 25.33 | 34.33 | 11.67 | 32.50 |
PERIMETER_TOP_ZN_4 | 31.83 | 34.83 | 14.00 | 24.50 |
PERIMETER_BOT_ZN_3 | 26.83 | 0.00 | 21.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 9.17 | 22.67 | 4.17 | 22.67 |
PERIMETER_BOT_ZN_1 | 309.83 | 38.00 | 307.67 | 37.50 |
PERIMETER_BOT_ZN_4 | 12.67 | 21.67 | 7.50 | 16.33 |
PERIMETER_MID_ZN_3 | 20.83 | 1.00 | 14.50 | 1.00 |
PERIMETER_MID_ZN_2 | 10.50 | 35.67 | 4.50 | 35.33 |
PERIMETER_MID_ZN_1 | 10.33 | 33.00 | 4.67 | 32.50 |
PERIMETER_MID_ZN_4 | 14.00 | 30.67 | 7.67 | 21.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 350.67 | 144.33 | 326.17 | 127.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.800 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.584 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.571 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.655 | 0.048 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.905 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.986 | 0.048 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.914 | 0.050 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.559 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.798 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.819 | 0.832 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.781 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.652 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.833 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.997 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.911 | 0.042 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12603952.44 | 0.00 | 12603952.44 | 0.00 | 12603952.44 | 13393058.27 | 5171.31 | 341.27 | 3247.42 | 35.38 |
CORE_MID | 9232462.05 | 0.00 | 9232462.05 | 0.00 | 9232462.05 | 13393058.27 | 5687.83 | 811.59 | 2260.58 | 32.86 |
CORE_TOP | 9037243.60 | 0.00 | 9037243.60 | 0.00 | 9037243.60 | 13393058.27 | 5746.52 | 917.87 | 2095.61 | 46.23 |
PERIMETER_TOP_ZN_3 | 2184029.00 | 0.00 | 2184029.00 | 313577.76 | 2497606.76 | 2823374.22 | 4668.94 | 913.20 | 3177.86 | 46.23 |
PERIMETER_TOP_ZN_2 | 1905908.49 | 0.00 | 1905908.49 | 209050.58 | 2114959.07 | 1787429.43 | 4558.67 | 822.28 | 3379.04 | 46.23 |
PERIMETER_TOP_ZN_1 | 3278759.00 | 0.00 | 3278759.00 | 313577.76 | 3592336.76 | 2823374.22 | 4384.60 | 625.75 | 3749.65 | 46.23 |
PERIMETER_TOP_ZN_4 | 1926860.50 | 0.00 | 1926860.50 | 209050.58 | 2135911.09 | 1787312.18 | 4607.29 | 1031.86 | 3120.85 | 46.23 |
PERIMETER_BOT_ZN_3 | 1866375.74 | 0.00 | 1866375.74 | 166727.58 | 2033103.32 | 2823374.22 | 6319.09 | 508.74 | 1932.17 | 35.38 |
PERIMETER_BOT_ZN_2 | 1680559.16 | 0.00 | 1680559.16 | 111151.05 | 1791710.20 | 1787429.43 | 5448.52 | 514.39 | 2797.09 | 35.38 |
PERIMETER_BOT_ZN_1 | 2732871.51 | 0.00 | 2732871.51 | 2860908.58 | 5593780.10 | 2823374.22 | 5239.85 | 501.90 | 3018.24 | 35.38 |
PERIMETER_BOT_ZN_4 | 1646688.60 | 0.00 | 1646688.60 | 111151.05 | 1757839.65 | 1787312.18 | 5421.20 | 355.49 | 2983.31 | 35.38 |
PERIMETER_MID_ZN_3 | 2172009.85 | 0.00 | 2172009.85 | 261029.36 | 2433039.22 | 2823374.22 | 4779.38 | 1029.17 | 2951.45 | 32.86 |
PERIMETER_MID_ZN_2 | 1764405.99 | 0.00 | 1764405.99 | 174018.53 | 1938424.51 | 1601953.02 | 4439.62 | 559.35 | 3761.04 | 941.86 |
PERIMETER_MID_ZN_1 | 3314337.96 | 0.00 | 3314337.96 | 261029.36 | 3575367.32 | 2823374.22 | 4398.54 | 983.32 | 3378.14 | 32.86 |
PERIMETER_MID_ZN_4 | 1918821.87 | 0.00 | 1918821.87 | 174018.53 | 2092840.40 | 1787312.18 | 4588.47 | 692.50 | 3479.04 | 32.86 |
Total Facility | 57265285.76 | 0.00 | 57265285.76 | 5165290.72 | 62430576.48 | 67658168.57 | 6796.60 | 1625.21 | 4425.24 | 996.16 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5873 | 0.0000 | 0.5873 | 0.0000 | 0.5873 | 0.4247 | 2369.06 | 341.27 | 3232.67 |
CORE_MID | 0.4300 | 0.0000 | 0.4300 | 0.0000 | 0.4300 | 0.4247 | 2883.54 | 811.59 | 2247.87 |
CORE_TOP | 0.4206 | 0.0000 | 0.4206 | 0.0000 | 0.4206 | 0.4247 | 2945.36 | 917.87 | 2079.77 |
PERIMETER_TOP_ZN_3 | 0.1017 | 0.0000 | 0.1017 | 0.0075 | 0.1092 | 0.0895 | 1867.77 | 913.20 | 3162.03 |
PERIMETER_TOP_ZN_2 | 0.0888 | 0.0000 | 0.0888 | 0.0050 | 0.0938 | 0.0567 | 1757.51 | 822.28 | 3363.21 |
PERIMETER_TOP_ZN_1 | 0.1528 | 0.0000 | 0.1528 | 0.0075 | 0.1603 | 0.0895 | 1583.43 | 625.75 | 3733.82 |
PERIMETER_TOP_ZN_4 | 0.0897 | 0.0000 | 0.0897 | 0.0050 | 0.0946 | 0.0567 | 1806.13 | 1031.86 | 3105.01 |
PERIMETER_BOT_ZN_3 | 0.0869 | 0.0000 | 0.0869 | 0.0040 | 0.0908 | 0.0895 | 3516.84 | 508.74 | 1917.42 |
PERIMETER_BOT_ZN_2 | 0.0783 | 0.0000 | 0.0783 | 0.0026 | 0.0810 | 0.0567 | 2646.32 | 514.39 | 2782.29 |
PERIMETER_BOT_ZN_1 | 0.1274 | 0.0000 | 0.1274 | 0.1299 | 0.2573 | 0.0895 | 2437.60 | 501.90 | 3003.49 |
PERIMETER_BOT_ZN_4 | 0.0767 | 0.0000 | 0.0767 | 0.0026 | 0.0793 | 0.0567 | 2619.02 | 355.46 | 2968.51 |
PERIMETER_MID_ZN_3 | 0.1012 | 0.0000 | 0.1012 | 0.0062 | 0.1074 | 0.0895 | 1975.08 | 1029.17 | 2938.74 |
PERIMETER_MID_ZN_2 | 0.0818 | 0.0000 | 0.0818 | 0.0044 | 0.0862 | 0.0567 | 1635.50 | 559.31 | 2839.20 |
PERIMETER_MID_ZN_1 | 0.1546 | 0.0000 | 0.1546 | 0.0062 | 0.1608 | 0.0895 | 1594.25 | 983.32 | 3365.43 |
PERIMETER_MID_ZN_4 | 0.0894 | 0.0000 | 0.0894 | 0.0041 | 0.0935 | 0.0567 | 1784.37 | 692.48 | 3466.15 |
Total Facility | 2.6671 | 0.0000 | 2.6671 | 0.1851 | 2.8521 | 2.1513 | 3986.27 | 1625.12 | 4400.22 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29741245.45 | 0.00 | 29741245.45 | 22614548.33 | 4196.43 | 1.28 | 4562.29 | 35.38 |
PACU_VAV_MID | 26657944.12 | 0.00 | 26657944.12 | 22429071.92 | 4191.33 | 2.58 | 4566.10 | 32.86 |
PACU_VAV_TOP | 26557644.37 | 0.00 | 26557644.37 | 22614548.33 | 4211.87 | 1.00 | 4547.13 | 46.06 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3858 | 0.0000 | 1.3858 | 0.7171 | 1394.18 | 1.28 | 4547.54 |
PACU_VAV_MID | 1.2420 | 0.0000 | 1.2420 | 0.7084 | 1387.03 | 2.58 | 4553.39 |
PACU_VAV_TOP | 1.2366 | 0.0000 | 1.2366 | 0.7171 | 1410.70 | 1.00 | 4531.30 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 339.06 | 1829.71 | 0.00 | 0.00 | 0.00 | 2540.22 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 89.69 | 1825.99 | 0.00 | 0.00 | 0.00 | 2799.17 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 71.40 | 1801.99 | 0.00 | 0.00 | 0.00 | 2851.93 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3545 | 2.7289 | 0.0000 | 0.0000 | 0.0000 | 1.1347 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2782 | 2.3544 | 0.0000 | 0.0000 | 0.0000 | 1.0883 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2291 | 2.3544 | 0.0000 | 0.0000 | 0.0000 | 1.0977 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1005 |
Defaulted Fields | 578 |
Fields with Defaults | 2423 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
Electricity:Building | 952.43 | 13383.13 | 16-APR-17:20 | 66674.30 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 952.43 | 13383.13 | 16-APR-17:20 | 66674.30 | 02-JAN-16:40 |
InteriorLights:Electricity | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.74 | 905.38 | 16-APR-17:20 | 25003.79 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.11 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.02 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.10 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.76 | 27.57 | 01-JAN-08:40 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.27 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.27 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.01 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.68 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.68 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.64 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.11 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.78 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.68 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.28 | 17.46 | 01-JAN-07:50 | 658.76 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.02 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.69 | 27.57 | 01-JAN-07:50 | 1040.56 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.65 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.24 | 17.46 | 01-JAN-08:40 | 658.71 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 322.54 | 368.53 | 30-APR-17:30 | 99342.94 | 19-JUN-10:30 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:20 |
ElectricityPurchased:Facility | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
ElectricityPurchased:Plant | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
Cogeneration:ElectricityPurchased | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
General:Cogeneration:ElectricityPurchased | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
ElectricityNet:Plant | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
Cogeneration:ElectricityNet | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
General:Cogeneration:ElectricityNet | 1380.58 | 13751.79 | 23-APR-17:20 | 164976.42 | 19-JUN-10:50 |
Fans:Electricity | 97.16 | 0.00 | 01-JAN-00:40 | 28910.06 | 30-MAY-14:40 |
General:Fans:Electricity | 97.16 | 0.00 | 01-JAN-00:40 | 28910.06 | 30-MAY-14:40 |
ExteriorLights:Electricity | 50.82 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.82 | 0.00 | 01-JAN-07:30 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 198.49 | 0.00 | 01-JAN-00:10 | 75124.01 | 19-JUN-12:10 |
General:Cooling:Electricity | 198.49 | 0.00 | 01-JAN-00:10 | 75124.01 | 19-JUN-12:10 |
Electricity:Plant | 54.79 | 0.00 | 01-JAN-00:40 | 7289.48 | 06-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 52.85 | 0.00 | 01-JAN-00:10 | 6688.41 | 06-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 52.85 | 0.00 | 01-JAN-00:10 | 6688.41 | 06-FEB-12:50 |
Pumps:Electricity | 1.94 | 0.00 | 01-JAN-00:40 | 793.27 | 02-JAN-07:20 |
General:Pumps:Electricity | 1.94 | 0.00 | 01-JAN-00:40 | 793.27 | 02-JAN-07:20 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:50 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 355.87 | 0.00 | 01-JAN-00:40 | 254141.50 | 02-JAN-07:20 |
NaturalGas:Plant | 355.87 | 0.00 | 01-JAN-00:40 | 254141.50 | 02-JAN-07:20 |
Heating:NaturalGas | 355.87 | 0.00 | 01-JAN-00:40 | 254141.50 | 02-JAN-07:20 |
Boiler:Heating:NaturalGas | 355.87 | 0.00 | 01-JAN-00:40 | 254141.50 | 02-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 04-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2517.73 | 0.00 | 01-JAN-00:40 | 535117.46 | 02-JAN-07:20 |
EnergyTransfer:Building | 1099.86 | 0.00 | 01-JAN-00:40 | 171127.74 | 14-AUG-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 221.87 | 0.00 | 01-JAN-00:40 | 27351.74 | 05-SEP-07:20 |
Heating:EnergyTransfer | 99.28 | 0.00 | 01-JAN-00:40 | 144268.53 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.19 | 0.00 | 01-JAN-00:10 | 7164.54 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 99.28 | 0.00 | 01-JAN-00:40 | 144268.53 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.19 | 0.00 | 01-JAN-00:10 | 7164.54 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 1000.58 | 0.00 | 01-JAN-00:40 | 171127.74 | 14-AUG-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 221.69 | 0.00 | 01-JAN-00:40 | 27351.74 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1000.58 | 0.00 | 01-JAN-00:40 | 171127.74 | 14-AUG-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 221.69 | 0.00 | 01-JAN-00:40 | 27351.74 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 48.28 | 0.00 | 01-JAN-00:40 | 12967.67 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.99 | 0.00 | 01-JAN-00:40 | 12967.67 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 15.99 | 0.00 | 01-JAN-00:40 | 12967.67 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.29 | 0.00 | 01-JAN-00:10 | 12110.44 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 32.29 | 0.00 | 01-JAN-00:10 | 12110.44 | 19-JUN-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.68 | 0.00 | 01-JAN-00:40 | 9054.94 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.40 | 0.00 | 01-JAN-00:40 | 9054.94 | 02-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.40 | 0.00 | 01-JAN-00:40 | 9054.94 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.29 | 0.00 | 01-JAN-00:10 | 5673.60 | 14-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.29 | 0.00 | 01-JAN-00:10 | 5673.60 | 14-AUG-14:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 29.00 | 0.00 | 01-JAN-00:40 | 7645.41 | 02-JAN-09:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.82 | 0.00 | 01-JAN-00:40 | 7645.41 | 02-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.82 | 0.00 | 01-JAN-00:40 | 7645.41 | 02-JAN-09:00 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.18 | 0.00 | 01-JAN-00:10 | 5773.21 | 14-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 23.18 | 0.00 | 01-JAN-00:10 | 5773.21 | 14-AUG-15:50 |
EnergyTransfer:Zone:CORE_MID | 148.01 | 0.00 | 01-JAN-00:40 | 19940.73 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.88 | 0.00 | 01-JAN-00:20 | 15029.87 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.88 | 0.00 | 01-JAN-00:20 | 15029.87 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 147.13 | 0.00 | 01-JAN-00:40 | 19940.73 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 147.13 | 0.00 | 01-JAN-00:40 | 19940.73 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 141.82 | 0.00 | 01-JAN-00:40 | 21419.21 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.07 | 0.00 | 01-JAN-00:40 | 21419.21 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.07 | 0.00 | 01-JAN-00:40 | 21419.21 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 136.74 | 0.00 | 01-JAN-00:20 | 20810.25 | 14-AUG-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 136.74 | 0.00 | 01-JAN-00:20 | 20810.25 | 14-AUG-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.30 | 0.00 | 01-JAN-00:40 | 8664.88 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.64 | 0.00 | 01-JAN-00:40 | 8664.88 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 10.64 | 0.00 | 01-JAN-00:40 | 8664.88 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.66 | 0.00 | 01-JAN-00:10 | 7893.23 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.66 | 0.00 | 01-JAN-00:10 | 7893.23 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 35.74 | 0.00 | 01-JAN-00:40 | 9451.21 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.46 | 0.00 | 01-JAN-00:40 | 6852.29 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.46 | 0.00 | 01-JAN-00:40 | 6852.29 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.29 | 0.00 | 01-JAN-00:10 | 9451.21 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.29 | 0.00 | 01-JAN-00:10 | 9451.21 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.58 | 0.00 | 01-JAN-00:40 | 13176.88 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 0.00 | 01-JAN-00:40 | 9600.43 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 0.00 | 01-JAN-00:40 | 9600.43 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.90 | 0.00 | 01-JAN-00:10 | 13176.88 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 51.90 | 0.00 | 01-JAN-00:10 | 13176.88 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 36.90 | 0.00 | 01-JAN-00:40 | 9807.66 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.32 | 0.00 | 01-JAN-00:40 | 7096.66 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.32 | 0.00 | 01-JAN-00:40 | 7096.66 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.58 | 0.00 | 01-JAN-00:10 | 9807.66 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.58 | 0.00 | 01-JAN-00:10 | 9807.66 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.59 | 0.00 | 01-JAN-00:40 | 6589.27 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.76 | 0.00 | 01-JAN-00:40 | 6589.27 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.76 | 0.00 | 01-JAN-00:40 | 6589.27 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 28.84 | 0.00 | 01-JAN-00:10 | 6173.70 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 28.84 | 0.00 | 01-JAN-00:10 | 6173.70 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.77 | 0.00 | 01-JAN-00:40 | 7526.23 | 22-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.07 | 0.00 | 01-JAN-00:40 | 5054.80 | 02-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.07 | 0.00 | 01-JAN-00:40 | 5054.80 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.70 | 0.00 | 01-JAN-00:10 | 7526.23 | 22-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.70 | 0.00 | 01-JAN-00:10 | 7526.23 | 22-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.55 | 0.00 | 01-JAN-00:40 | 12347.95 | 19-JUN-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 12.39 | 0.00 | 01-JAN-00:40 | 10500.89 | 02-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 12.39 | 0.00 | 01-JAN-00:40 | 10500.89 | 02-JAN-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.16 | 0.00 | 01-JAN-00:20 | 12347.95 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.16 | 0.00 | 01-JAN-00:20 | 12347.95 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.85 | 0.00 | 01-JAN-00:40 | 7836.19 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.42 | 0.00 | 01-JAN-00:40 | 5279.69 | 02-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.42 | 0.00 | 01-JAN-00:40 | 5279.69 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.42 | 0.00 | 01-JAN-00:10 | 7836.19 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.42 | 0.00 | 01-JAN-00:10 | 7836.19 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 37.55 | 0.00 | 01-JAN-00:40 | 7137.41 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.61 | 0.00 | 01-JAN-00:40 | 7070.28 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.61 | 0.00 | 01-JAN-00:40 | 7070.28 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.94 | 0.00 | 01-JAN-00:10 | 7137.41 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 32.94 | 0.00 | 01-JAN-00:10 | 7137.41 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.78 | 0.00 | 01-JAN-00:40 | 9288.14 | 26-JUN-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.31 | 0.00 | 01-JAN-00:40 | 5651.46 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.31 | 0.00 | 01-JAN-00:40 | 5651.46 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.46 | 0.00 | 01-JAN-00:10 | 9288.14 | 26-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 29.46 | 0.00 | 01-JAN-00:10 | 9288.14 | 26-JUN-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 56.61 | 0.00 | 01-JAN-00:40 | 12181.71 | 28-SEP-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.58 | 0.00 | 01-JAN-00:40 | 7952.32 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.58 | 0.00 | 01-JAN-00:40 | 7952.32 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.03 | 0.00 | 01-JAN-00:10 | 12181.71 | 28-SEP-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 54.03 | 0.00 | 01-JAN-00:10 | 12181.71 | 28-SEP-12:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.96 | 0.00 | 01-JAN-00:40 | 9326.54 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.70 | 0.00 | 01-JAN-00:40 | 5725.62 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.70 | 0.00 | 01-JAN-00:40 | 5725.62 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.27 | 0.00 | 01-JAN-00:10 | 9326.54 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 31.27 | 0.00 | 01-JAN-00:10 | 9326.54 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 298.29 | 0.00 | 01-JAN-00:40 | 204680.97 | 02-JAN-08:10 |
PlantLoopHeatingDemand:Plant | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
EnergyTransfer:HVAC | 1121.51 | 0.00 | 01-JAN-00:40 | 282133.78 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 248.24 | 0.00 | 01-JAN-00:40 | 202568.74 | 02-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 248.24 | 0.00 | 01-JAN-00:40 | 202568.74 | 02-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 248.24 | 0.00 | 01-JAN-00:40 | 202568.74 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 873.27 | 0.00 | 01-JAN-00:10 | 282128.39 | 16-AUG-12:30 |
EnergyTransfer:Plant | 296.37 | 0.00 | 01-JAN-00:40 | 203821.42 | 02-JAN-08:10 |
WaterSystems:EnergyTransfer | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 50.06 | 0.00 | 01-JAN-00:10 | 6459.49 | 09-FEB-12:10 |
Boilers:EnergyTransfer | 246.31 | 0.00 | 01-JAN-00:40 | 201438.61 | 02-JAN-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.186 | -221.690 | 0.000 | 0.000 | 32.917 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -117.436 |
CORE_MID | 0.000 | 0.000 | 0.882 | -147.133 | 0.000 | 0.000 | 34.072 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -58.844 |
CORE_TOP | 0.000 | 0.000 | 5.074 | -136.745 | 0.000 | 0.000 | 34.733 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.086 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 10.637 | -31.665 | 0.000 | 0.000 | 7.489 | 6.780 | 24.333 | 18.724 | 0.000 | 0.062 | 0.000 | 0.000 | -28.016 | 0.000 | -4.217 | -4.126 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.456 | -30.287 | 0.000 | 0.000 | 4.667 | 4.279 | 15.404 | 33.316 | 0.000 | 0.040 | 0.001 | 0.000 | -17.806 | 0.000 | -2.866 | -12.203 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 6.681 | -51.901 | 0.000 | 0.000 | 7.269 | 6.690 | 24.332 | 67.928 | 0.000 | 0.060 | 0.001 | 0.000 | -26.726 | 0.000 | -4.426 | -29.908 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.324 | -30.576 | 0.000 | 0.000 | 4.697 | 4.244 | 15.403 | 33.933 | 0.000 | 0.040 | 0.001 | 0.000 | -18.339 | 0.000 | -2.882 | -12.845 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.755 | -28.839 | 0.000 | 0.000 | 7.455 | 6.765 | 24.333 | 18.995 | 0.000 | 0.037 | 0.002 | 0.000 | -29.329 | 0.000 | -2.377 | -1.793 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.066 | -28.703 | 0.000 | 0.000 | 4.629 | 4.272 | 15.404 | 33.451 | 0.000 | 0.022 | 0.001 | 0.000 | -18.965 | 0.000 | -1.638 | -10.538 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 12.392 | -43.159 | 0.000 | 0.000 | 7.435 | 6.682 | 24.332 | 68.627 | 0.000 | 1.979 | 0.005 | 0.000 | -28.423 | 0.000 | -31.778 | -18.089 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.422 | -28.424 | 0.000 | 0.000 | 4.659 | 4.237 | 15.403 | 34.137 | 0.000 | 0.022 | 0.000 | 0.000 | -19.552 | 0.000 | -1.646 | -11.257 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 4.608 | -32.944 | 0.000 | 0.000 | 7.413 | 6.780 | 24.333 | 18.541 | 0.000 | 0.052 | 4.679 | 0.000 | -29.740 | 0.000 | -3.722 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.314 | -29.463 | 0.000 | 0.000 | 3.407 | 4.279 | 15.404 | 33.070 | 0.000 | 0.033 | 0.000 | 0.000 | -18.886 | 0.000 | -2.532 | -7.625 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.581 | -54.026 | 0.000 | 0.000 | 7.185 | 6.690 | 24.332 | 67.686 | 0.000 | 0.050 | 0.002 | 0.000 | -28.334 | 0.000 | -3.904 | -22.260 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.697 | -31.267 | 0.000 | 0.000 | 4.647 | 4.244 | 15.403 | 33.814 | 0.000 | 0.033 | 0.000 | 0.000 | -19.453 | 0.000 | -2.541 | -7.578 |
TOPFLOOR_PLENUM | 15.988 | -32.290 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.060 | 22.720 | 0.000 | 0.000 | 0.000 | -6.478 | -0.001 |
MIDFLOOR_PLENUM | 8.395 | -18.287 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.070 | 16.242 | 0.000 | 0.000 | 0.000 | -6.421 | -0.000 |
FIRSTFLOOR_PLENUM | 5.822 | -23.176 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.055 | 22.544 | 0.000 | 0.000 | 0.000 | -5.245 | -0.001 |
Total Facility | 30.205 | -73.753 | 69.074 | -926.821 | 0.000 | 0.000 | 172.675 | 232.739 | 719.689 | 462.221 | 0.000 | 2.614 | 66.197 | 0.000 | -283.570 | 0.000 | -82.673 | -388.590 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | -42082.66 | 0.00 | 0.00 | 283.97 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 34176.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | -33041.44 | 0.00 | 0.00 | 300.24 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 29503.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-05:03 | 0.00 | 0.00 | 0.00 | -35603.35 | 0.00 | 0.00 | 301.98 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 32063.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:12 | 0.00 | 0.00 | 0.00 | -11370.65 | 0.00 | 0.00 | 26.93 | 27.57 | 478.42 | 2957.51 | 0.00 | 54.22 | 7826.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 28-MAY-08:42 | 0.00 | 0.00 | 0.00 | -13904.85 | 0.00 | 0.00 | 14.91 | 17.46 | 302.86 | 9514.54 | 0.00 | 0.00 | 4162.90 | 0.00 | -0.00 | 0.00 | -107.81 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-12:02 | 0.00 | 0.00 | 0.00 | -17241.12 | 0.00 | 0.00 | 23.78 | 27.57 | 478.41 | 13983.51 | 0.00 | 0.00 | 2961.27 | 0.00 | -0.00 | 0.00 | -233.43 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUN-15:42 | 0.00 | 0.00 | 0.00 | -14906.11 | 0.00 | 0.00 | 14.25 | 17.46 | 302.86 | 8387.56 | 0.00 | 0.00 | 6266.16 | 0.00 | -0.00 | 0.00 | -82.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | -7516.18 | 0.00 | 0.00 | 144.48 | 165.45 | 637.89 | 2890.26 | 0.00 | 0.00 | 3682.78 | 0.00 | -0.00 | 0.00 | -4.68 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-SEP-08:32 | 0.00 | 0.00 | 0.00 | -11226.96 | 0.00 | 0.00 | 16.28 | 17.46 | 302.86 | 10617.90 | 0.00 | 0.00 | 336.18 | 0.00 | -0.00 | 0.00 | -63.72 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -13885.58 | 0.00 | 0.00 | 25.06 | 27.57 | 478.41 | 12075.68 | 0.00 | 0.00 | 1332.00 | 0.00 | -0.00 | 0.00 | -53.14 | 0.00 |
PERIMETER_BOT_ZN_4 | 10-SEP-16:31 | 0.00 | 0.00 | 0.00 | -12030.07 | 0.00 | 0.00 | 14.85 | 17.46 | 302.86 | 10038.76 | 0.00 | 0.00 | 1705.04 | 0.00 | -0.00 | 0.00 | -48.90 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-16:02 | 0.00 | 0.00 | 0.00 | -9858.76 | 0.00 | 0.00 | 28.32 | 27.57 | 478.42 | 2866.19 | 0.00 | 0.84 | 6457.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -14338.54 | 0.00 | 0.00 | 13.38 | 17.46 | 302.86 | 9820.62 | 0.00 | 0.00 | 4209.96 | 0.00 | -0.00 | 0.00 | -25.74 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:32 | 0.00 | 0.00 | 0.00 | -15967.14 | 0.00 | 0.00 | 23.10 | 27.57 | 478.41 | 13035.13 | 0.00 | 0.00 | 2512.55 | 0.00 | -0.00 | 0.00 | -109.62 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-16:31 | 0.00 | 0.00 | 0.00 | -14333.28 | 0.00 | 0.00 | 13.58 | 17.46 | 302.86 | 9953.96 | 0.00 | 0.00 | 4128.12 | 0.00 | -0.00 | 0.00 | -82.69 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:30 | 0.00 | -12109.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.46 | 12044.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-10:10 | 0.00 | -5680.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 5665.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:08 | 0.00 | -6570.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 | 6508.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JUN-05:02 | 0.00 | 10107.14 | 0.00 | -206128.96 | 0.00 | 0.00 | 1517.04 | 1072.56 | 19712.35 | 17189.66 | 0.00 | 0.00 | 156716.49 | 0.00 | 0.00 | 0.00 | -186.29 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:02 | 0.00 | 0.00 | 8513.45 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14367.24 |
CORE_MID | 02-JAN-05:02 | 0.00 | 0.00 | 16050.69 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18704.48 |
CORE_TOP | 02-JAN-04:42 | 0.00 | 0.00 | 23247.80 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25901.59 |
PERIMETER_TOP_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 9554.17 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3023.20 | 0.00 | -1003.50 | -6086.91 |
PERIMETER_TOP_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 8257.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1966.90 | 0.00 | -676.79 | -5968.36 |
PERIMETER_TOP_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 11173.36 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2975.64 | 0.00 | -1018.42 | -7738.73 |
PERIMETER_TOP_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 8658.38 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2016.17 | 0.00 | -676.77 | -6319.58 |
PERIMETER_BOT_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 7186.67 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3077.46 | 0.00 | -548.16 | -4120.49 |
PERIMETER_BOT_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 6268.54 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2018.89 | 0.00 | -370.39 | -4233.41 |
PERIMETER_BOT_ZN_1 | 02-JAN-07:50 | 0.00 | 0.00 | 10500.50 | 0.00 | 0.00 | 0.00 | 255.44 | 165.45 | 637.88 | 297.52 | 0.00 | 0.00 | 7952.54 | 0.00 | -0.00 | 0.00 | -19809.34 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 6428.20 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2057.11 | 0.00 | -368.92 | -4356.31 |
PERIMETER_MID_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 7770.24 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3088.71 | 0.00 | -851.97 | -4389.01 |
PERIMETER_MID_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 7043.41 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2011.14 | 0.00 | -574.30 | -4812.13 |
PERIMETER_MID_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 9169.59 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3041.60 | 0.00 | -864.05 | -5823.38 |
PERIMETER_MID_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 7185.56 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2059.80 | 0.00 | -573.48 | -4906.44 |
TOPFLOOR_PLENUM | 02-JAN-06:10 | 14446.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -162.94 | -14283.55 |
MIDFLOOR_PLENUM | 02-JAN-08:19 | 9185.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -148.49 | -9036.79 |
FIRSTFLOOR_PLENUM | 02-JAN-12:01 | 7702.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -81.30 | -7621.49 |
Total Facility | 02-JAN-05:22 | 19019.62 | 0.00 | 140585.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31511.02 | 0.00 | -4651.32 | -140085.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.0669 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5289 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9312 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2203 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.3587 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9088 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5334 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0763 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4656 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0764 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6794 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0751 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4926 | 2.4926 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0055 | 2.0055 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1578 | 2.1578 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6845 | 0.6845 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7593 | 0.7593 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9356 | 0.9356 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8216 | 0.8216 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5429 | 0.5429 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6285 | 0.6285 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7568 | 0.7568 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6462 | 0.6462 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5933 | 0.5933 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7348 | 0.7348 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8433 | 0.8433 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7544 | 0.7544 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.0669 | 4.5289 | 5.0669 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9312 | 4.2203 | 4.9312 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.3587 | 4.9088 | 5.3587 | 1.0751 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2463 | 1.2463 | 0.6381 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0027 | 1.0027 | 0.6377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0789 | 1.0789 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3422 | 0.3422 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3796 | 0.3796 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4678 | 0.4678 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4108 | 0.4108 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2714 | 0.2714 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3142 | 0.3142 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3784 | 0.3784 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3231 | 0.3231 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2966 | 0.2966 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3674 | 0.3674 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4216 | 0.4216 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3772 | 0.3772 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5334 | 1.0763 | 1.0763 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4656 | 1.0764 | 1.0764 | 1.0764 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6794 | 1.0751 | 1.0751 | 1.0751 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 326.17 |
Number of hours cooling loads not met | 127.67 |
Number of hours not met | 453.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 355.87 | 254141.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 198.49 | 75124.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.74 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.82 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 97.16 | 28910.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.94 | 793.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 52.85 | 6688.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1380.58 |
Natural Gas | 0.00 | 355.87 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1736.44 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.71 |
Space Heating | 0.00 |
Space Cooling | 39.84 |
Fans (All) | 19.50 |
Service Water Heating | 10.61 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 277.10 |
Subtotal | 277.10 |
Natural Gas [MJ/m2] | |
Space Heating | 71.43 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 71.43 |
Subtotal | 71.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.40 |
Space Heating | 20.49 |
Space Cooling | 11.43 |
Fans (All) | 5.60 |
Service Water Heating | 3.04 |
Receptacle Equipment | 41.45 |
Miscellaneous | 4.59 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 917. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8470.83 | 289.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8653.33 | 106.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8670.17 | 89.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8616.83 | 143.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8711.17 | 48.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8658.67 | 101.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8651.83 | 108.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8674.17 | 85.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8603.17 | 156.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8612.67 | 147.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8470.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 289.17 | 0.00 | 0.00 | 0.00 |
Average | 8680.39 | 79.61 | 0.00 | 0.00 | 0.00 |
Sum | 156247.00 | 1433.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128196.67 | 107.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128303.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.00 | 107.33 | 0.00 | 0.00 | 0.00 |
Average | 34137.15 | 6.19 | 0.00 | 0.00 | 0.00 |
Sum | 614468.67 | 111.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7879.50 | 880.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8230.17 | 529.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8366.33 | 393.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8076.83 | 683.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8029.67 | 730.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8045.00 | 715.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7986.17 | 773.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8168.67 | 591.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8035.17 | 724.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7794.17 | 965.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7948.33 | 811.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8025.17 | 734.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7939.67 | 820.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7973.50 | 786.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7912.33 | 847.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7548.83 | 1211.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7956.67 | 803.33 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7979.00 | 781.00 | 0.00 | 0.00 | 0.00 |
Min | 7548.83 | 393.67 | 0.00 | 0.00 | 0.00 |
Max | 8366.33 | 1211.17 | 0.00 | 0.00 | 0.00 |
Average | 7994.18 | 765.82 | 0.00 | 0.00 | 0.00 |
Sum | 143895.17 | 13784.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127832.67 | 471.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128047.67 | 256.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128125.17 | 178.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24753.67 | 155.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 13918.17 | 97.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24773.50 | 135.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13902.17 | 113.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24777.17 | 131.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 13945.50 | 70.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 23503.83 | 1405.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13927.50 | 88.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24871.83 | 37.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10128.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24874.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13968.17 | 47.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128125.17 | 1405.17 | 0.00 | 0.00 | 0.00 |
Average | 33963.89 | 179.44 | 0.00 | 0.00 | 0.00 |
Sum | 611350.00 | 3230.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:15
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.852114E+10 | 11522.87 | 27-JAN-16:30 | 5.00 | 2.53 | 0.184464E+10 | 2606.62 | 20-JAN-10:09 | 5.00 | 2.53 |
February | 0.895963E+10 | 12520.24 | 24-FEB-17:00 | 6.70 | 1.42 | 0.174665E+10 | 2606.64 | 01-FEB-10:20 | 6.70 | 1.42 |
March | 0.137913E+11 | 19429.98 | 30-MAR-06:02 | 2.20 | 1.02 | 0.214810E+10 | 2606.67 | 27-MAR-09:09 | 2.20 | 1.02 |
April | 0.160984E+11 | 37171.87 | 10-APR-05:12 | 15.20 | 13.76 | 0.191464E+10 | 2606.67 | 05-APR-09:39 | 15.20 | 13.76 |
May | 0.220916E+11 | 38477.86 | 31-MAY-05:12 | 16.67 | 15.21 | 0.207775E+10 | 2606.78 | 15-MAY-13:00 | 16.67 | 15.21 |
June | 0.255936E+11 | 42078.18 | 19-JUN-05:03 | 24.08 | 22.05 | 0.207358E+10 | 2606.66 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.264389E+11 | 41737.61 | 25-JUL-05:03 | 23.90 | 23.41 | 0.192760E+10 | 2606.66 | 12-JUL-13:50 | 23.90 | 23.41 |
August | 0.285498E+11 | 39530.03 | 01-AUG-04:03 | 23.90 | 20.81 | 0.216325E+10 | 2606.67 | 08-AUG-13:20 | 26.50 | 16.97 |
September | 0.242541E+11 | 41334.96 | 01-SEP-05:03 | 24.08 | 21.83 | 0.192118E+10 | 2606.73 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.223609E+11 | 38374.05 | 16-OCT-05:12 | 8.90 | 8.42 | 0.199602E+10 | 2606.74 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.143777E+11 | 33391.69 | 03-NOV-06:02 | 8.40 | 6.00 | 0.196538E+10 | 2606.70 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.106519E+11 | 14189.31 | 21-DEC-16:10 | 2.62 | -2.3 | 0.189800E+10 | 2606.63 | 04-DEC-10:09 | 2.62 | -2.3 |
Annual Sum or Average | 0.221689E+12 | 0.236768E+11 | ||||||||
Minimum of Months | 0.852114E+10 | 11522.87 | 2.20 | -2.3 | 0.174665E+10 | 2606.62 | 2.20 | -2.3 | ||
Maximum of Months | 0.285498E+11 | 42078.18 | 24.08 | 23.41 | 0.216325E+10 | 2606.78 | 26.50 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1009519.57 | 169.18 | 17-JAN-14:50 | 10.68 | 5.08 | 0.00 | 0.00 | 01-JAN-00:10 | 10.68 | 5.08 |
February | 17074528.13 | 501.96 | 18-FEB-15:00 | 6.70 | 3.14 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 3.14 |
March | 0.471451E+09 | 3065.84 | 03-MAR-14:30 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.147390E+10 | 7491.27 | 07-APR-13:20 | 26.50 | 16.25 | 0.00 | 0.00 | 01-APR-00:10 | 26.50 | 16.25 |
May | 0.341206E+10 | 10992.83 | 30-MAY-14:10 | 29.22 | 16.98 | 0.00 | 0.00 | 01-MAY-00:10 | 29.22 | 16.98 |
June | 0.584982E+10 | 12110.44 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.716645E+10 | 11305.41 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.773133E+10 | 10846.89 | 01-AUG-14:40 | 30.97 | 22.94 | 0.00 | 0.00 | 01-AUG-00:10 | 30.97 | 22.94 |
September | 0.385305E+10 | 9569.14 | 01-SEP-14:40 | 30.77 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 30.77 | 17.43 |
October | 0.211998E+10 | 6823.68 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.190340E+09 | 2531.94 | 02-NOV-14:20 | 16.30 | 8.82 | 0.00 | 0.00 | 01-NOV-00:10 | 16.30 | 8.82 |
December | 4107976.29 | 914.17 | 17-DEC-14:50 | 12.20 | 5.47 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.47 |
Annual Sum or Average | 0.322906E+11 | 0.00 | ||||||||
Minimum of Months | 1009519.57 | 169.18 | 6.70 | 3.14 | 0.00 | 0.00 | 6.70 | 3.14 | ||
Maximum of Months | 0.773133E+10 | 12110.44 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5822184.33 | 2084.51 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 7334511.97 | 1903.77 | 03-FEB-06:01 | -7.8 | -9.5 | 0.00 | 0.00 | 01-FEB-00:10 | -7.8 | -9.5 |
March | 0.112322E+09 | 1981.98 | 08-MAR-07:02 | 1.10 | 1.10 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | 1.10 |
April | 0.537661E+09 | 2528.44 | 10-APR-15:50 | 20.00 | 11.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.21 |
May | 0.160759E+10 | 5315.43 | 30-MAY-14:20 | 29.03 | 17.03 | 0.00 | 0.00 | 01-MAY-00:10 | 29.03 | 17.03 |
June | 0.336423E+10 | 5294.37 | 19-JUN-12:05 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.423704E+10 | 5522.99 | 10-JUL-14:20 | 32.97 | 20.94 | 0.00 | 0.00 | 01-JUL-00:10 | 32.97 | 20.94 |
August | 0.460772E+10 | 5680.26 | 14-AUG-10:10 | 27.88 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 23.11 |
September | 0.250502E+10 | 5508.67 | 05-SEP-06:10 | 20.78 | 18.13 | 0.00 | 0.00 | 01-SEP-00:10 | 20.78 | 18.13 |
October | 0.119528E+10 | 3327.17 | 04-OCT-15:50 | 22.98 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 22.98 | 19.12 |
November | 0.100603E+09 | 1763.95 | 18-NOV-07:03 | 2.88 | 1.89 | 0.00 | 0.00 | 01-NOV-00:10 | 2.88 | 1.89 |
December | 6055820.09 | 1537.56 | 23-DEC-06:11 | 2.93 | 2.42 | 0.00 | 0.00 | 01-DEC-00:10 | 2.93 | 2.42 |
Annual Sum or Average | 0.182867E+11 | 0.00 | ||||||||
Minimum of Months | 5822184.33 | 1537.56 | -7.8 | -9.6 | 0.00 | 0.00 | -7.8 | -9.6 | ||
Maximum of Months | 0.460772E+10 | 5680.26 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 54789907.65 | 1711.86 | 25-JAN-06:11 | 3.30 | 0.42 | 0.00 | 0.00 | 01-JAN-00:10 | 3.30 | 0.42 |
February | 70054770.76 | 2026.50 | 14-FEB-06:01 | -4.4 | -6.7 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -6.7 |
March | 0.278745E+09 | 2610.53 | 16-MAR-06:02 | 1.20 | -1.9 | 0.00 | 0.00 | 01-MAR-00:10 | 1.20 | -1.9 |
April | 0.876665E+09 | 2995.07 | 10-APR-15:50 | 20.00 | 11.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.21 |
May | 0.209904E+10 | 5805.21 | 30-MAY-12:10 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.384191E+10 | 6571.43 | 19-JUN-12:08 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.469296E+10 | 6166.85 | 10-JUL-12:10 | 31.28 | 20.14 | 0.00 | 0.00 | 01-JUL-00:10 | 31.28 | 20.14 |
August | 0.524975E+10 | 5773.21 | 14-AUG-15:50 | 27.88 | 22.79 | 0.00 | 0.00 | 01-AUG-00:10 | 27.88 | 22.79 |
September | 0.336708E+10 | 6437.57 | 05-SEP-06:10 | 20.78 | 18.13 | 0.00 | 0.00 | 01-SEP-00:10 | 20.78 | 18.13 |
October | 0.221145E+10 | 4070.73 | 16-OCT-06:06 | 9.18 | 8.72 | 0.00 | 0.00 | 01-OCT-00:10 | 9.18 | 8.72 |
November | 0.357098E+09 | 1926.57 | 03-NOV-06:06 | 8.40 | 6.00 | 0.00 | 0.00 | 01-NOV-00:10 | 8.40 | 6.00 |
December | 76122325.77 | 2238.98 | 20-DEC-07:02 | 1.78 | 1.02 | 0.00 | 0.00 | 01-DEC-00:10 | 1.78 | 1.02 |
Annual Sum or Average | 0.231757E+11 | 0.00 | ||||||||
Minimum of Months | 54789907.65 | 1711.86 | -4.4 | -6.7 | 0.00 | 0.00 | -4.4 | -6.7 | ||
Maximum of Months | 0.524975E+10 | 6571.43 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.552235E+10 | 6562.40 | 31-JAN-08:20 | -8.1 | -10.5 | 0.159885E+10 | 2435.18 | 20-JAN-14:00 | -8.1 | -10.5 |
February | 0.581966E+10 | 6206.43 | 24-FEB-17:00 | 6.70 | 1.42 | 0.149223E+10 | 2455.28 | 24-FEB-14:00 | 6.70 | 1.42 |
March | 0.857644E+10 | 10302.86 | 29-MAR-16:00 | 7.20 | 4.88 | 0.199126E+10 | 2606.63 | 29-MAR-09:09 | 7.20 | 4.88 |
April | 0.101781E+11 | 14408.19 | 10-APR-16:00 | 20.00 | 11.13 | 0.185966E+10 | 2606.66 | 17-APR-09:30 | 13.30 | 12.22 |
May | 0.146819E+11 | 29732.86 | 31-MAY-05:12 | 16.67 | 15.21 | 0.206505E+10 | 2606.74 | 15-MAY-13:00 | 16.67 | 15.21 |
June | 0.180536E+11 | 33039.64 | 19-JUN-05:03 | 24.08 | 22.05 | 0.206852E+10 | 2606.73 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.192762E+11 | 32910.52 | 25-JUL-05:03 | 23.90 | 23.41 | 0.192331E+10 | 2606.72 | 17-JUL-09:20 | 23.90 | 23.41 |
August | 0.204535E+11 | 32892.65 | 14-AUG-05:14 | 22.57 | 20.98 | 0.215935E+10 | 2608.71 | 14-AUG-09:20 | 27.40 | 22.88 |
September | 0.161483E+11 | 32959.60 | 05-SEP-05:14 | 20.60 | 18.00 | 0.191420E+10 | 2609.50 | 05-SEP-09:20 | 24.07 | 19.46 |
October | 0.135872E+11 | 25778.90 | 16-OCT-06:01 | 9.18 | 8.72 | 0.198055E+10 | 2606.72 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.806280E+10 | 11757.78 | 03-NOV-16:00 | 15.00 | 10.26 | 0.182467E+10 | 2606.67 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.677269E+10 | 6398.39 | 21-DEC-16:20 | 2.43 | -2.4 | 0.164492E+10 | 2536.16 | 21-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.147133E+12 | 0.225226E+11 | ||||||||
Minimum of Months | 0.552235E+10 | 6206.43 | -8.1 | -10.5 | 0.149223E+10 | 2435.18 | -8.1 | -10.5 | ||
Maximum of Months | 0.204535E+11 | 33039.64 | 24.08 | 23.41 | 0.215935E+10 | 2609.50 | 27.40 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372293E+10 | 6200.03 | 14-JAN-17:02 | -6.0 | -6.6 | 0.151947E+10 | 2338.33 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.393074E+10 | 5929.08 | 24-FEB-16:50 | 6.88 | 1.49 | 0.140414E+10 | 2374.73 | 02-FEB-14:00 | 6.88 | 1.49 |
March | 0.747255E+10 | 9958.99 | 29-MAR-16:00 | 7.20 | 4.88 | 0.187194E+10 | 2606.63 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.932976E+10 | 15147.83 | 10-APR-15:40 | 20.00 | 11.28 | 0.179831E+10 | 2606.66 | 07-APR-13:20 | 20.00 | 11.28 |
May | 0.142744E+11 | 31938.10 | 30-MAY-05:12 | 18.53 | 14.51 | 0.204935E+10 | 2606.74 | 15-MAY-13:00 | 18.53 | 14.51 |
June | 0.184972E+11 | 35599.32 | 19-JUN-05:03 | 24.08 | 22.05 | 0.206678E+10 | 2606.67 | 23-JUN-09:20 | 27.80 | 18.74 |
July | 0.201842E+11 | 32238.73 | 24-JUL-05:12 | 20.97 | 20.39 | 0.192352E+10 | 2606.65 | 14-JUL-09:00 | 20.97 | 20.39 |
August | 0.211350E+11 | 33001.52 | 07-AUG-05:12 | 19.40 | 16.84 | 0.215857E+10 | 2606.69 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.154125E+11 | 32343.60 | 05-SEP-05:12 | 20.60 | 18.00 | 0.190646E+10 | 2606.68 | 19-SEP-09:50 | 19.72 | 15.05 |
October | 0.118554E+11 | 15938.64 | 04-OCT-15:20 | 23.53 | 19.12 | 0.194364E+10 | 2606.71 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.637379E+10 | 10603.70 | 03-NOV-16:00 | 15.00 | 10.26 | 0.170378E+10 | 2606.65 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.455594E+10 | 5879.23 | 21-DEC-16:25 | 2.25 | -2.5 | 0.151467E+10 | 2385.04 | 20-DEC-14:00 | 2.25 | -2.5 |
Annual Sum or Average | 0.136745E+12 | 0.218607E+11 | ||||||||
Minimum of Months | 0.372293E+10 | 5879.23 | -6.0 | -6.6 | 0.140414E+10 | 2338.33 | 2.25 | -2.5 | ||
Maximum of Months | 0.211350E+11 | 35599.32 | 24.08 | 22.05 | 0.215857E+10 | 2606.74 | 27.80 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127904E+09 | 1263.78 | 14-JAN-17:02 | -6.0 | -6.6 | 0.305148E+09 | 430.29 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.154835E+09 | 1011.16 | 24-FEB-15:50 | 7.88 | 1.88 | 0.278080E+09 | 438.06 | 24-FEB-14:00 | 7.88 | 1.88 |
March | 0.876797E+09 | 1869.48 | 28-MAR-14:00 | 13.30 | 8.41 | 0.359811E+09 | 549.49 | 28-MAR-13:20 | 13.30 | 8.41 |
April | 0.173190E+10 | 4141.85 | 07-APR-15:20 | 25.60 | 16.01 | 0.358088E+09 | 549.50 | 07-APR-13:20 | 25.60 | 16.01 |
May | 0.350940E+10 | 8670.43 | 30-MAY-06:03 | 20.47 | 15.45 | 0.426549E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.548112E+10 | 9609.30 | 26-JUN-05:12 | 20.97 | 17.23 | 0.435636E+09 | 549.51 | 23-JUN-09:20 | 20.97 | 17.23 |
July | 0.639941E+10 | 10667.57 | 16-JUL-14:32 | 30.40 | 21.51 | 0.406180E+09 | 549.51 | 07-JUL-13:00 | 30.40 | 21.51 |
August | 0.637112E+10 | 11370.72 | 13-AUG-15:12 | 30.40 | 20.77 | 0.455024E+09 | 549.51 | 29-AUG-09:09 | 23.77 | 18.41 |
September | 0.377246E+10 | 6831.09 | 05-SEP-06:03 | 20.78 | 18.13 | 0.398414E+09 | 549.51 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.231781E+10 | 4237.95 | 04-OCT-13:50 | 24.50 | 18.89 | 0.394092E+09 | 549.50 | 02-OCT-13:20 | 24.50 | 18.89 |
November | 0.763256E+09 | 1665.10 | 03-NOV-14:00 | 17.80 | 10.67 | 0.329035E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.158835E+09 | 1005.53 | 20-DEC-14:10 | 9.72 | 5.77 | 0.295841E+09 | 439.48 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.316648E+11 | 0.444190E+10 | ||||||||
Minimum of Months | 0.127904E+09 | 1005.53 | -6.0 | -6.6 | 0.278080E+09 | 430.29 | 7.80 | 1.88 | ||
Maximum of Months | 0.639941E+10 | 11370.72 | 30.40 | 21.51 | 0.455024E+09 | 549.52 | 30.40 | 21.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175120E+09 | 949.78 | 31-JAN-09:20 | -7.4 | -10.0 | 0.196915E+09 | 317.74 | 19-JAN-10:30 | -7.4 | -10.0 |
February | 0.259564E+09 | 950.23 | 09-FEB-09:10 | -7.0 | -8.9 | 0.181967E+09 | 331.16 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.927087E+09 | 3792.05 | 29-MAR-09:30 | 6.15 | 3.19 | 0.248718E+09 | 347.88 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.187602E+10 | 6372.89 | 28-APR-08:40 | 15.53 | 8.75 | 0.238715E+09 | 347.89 | 26-APR-09:00 | 15.53 | 8.75 |
May | 0.361277E+10 | 13905.17 | 28-MAY-08:42 | 20.40 | 12.77 | 0.273146E+09 | 348.41 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.478965E+10 | 13495.49 | 04-JUN-09:42 | 24.22 | 12.91 | 0.276234E+09 | 348.41 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.552629E+10 | 13396.40 | 02-JUL-08:32 | 25.20 | 21.54 | 0.257501E+09 | 348.95 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.616843E+10 | 12869.15 | 13-AUG-09:12 | 28.17 | 19.21 | 0.288473E+09 | 348.50 | 02-AUG-09:00 | 28.17 | 19.21 |
September | 0.362821E+10 | 13228.12 | 04-SEP-09:12 | 24.47 | 18.42 | 0.254107E+09 | 348.59 | 06-SEP-09:50 | 26.52 | 19.55 |
October | 0.237649E+10 | 5592.22 | 05-OCT-09:10 | 19.08 | 16.88 | 0.258290E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.681257E+09 | 2177.73 | 03-NOV-09:30 | 13.05 | 8.24 | 0.220091E+09 | 347.88 | 07-NOV-10:20 | 10.37 | 7.28 |
December | 0.266378E+09 | 805.75 | 20-DEC-10:00 | 8.30 | 5.00 | 0.192328E+09 | 327.03 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.302873E+11 | 0.288648E+10 | ||||||||
Minimum of Months | 0.175120E+09 | 805.75 | -7.4 | -10.0 | 0.181967E+09 | 317.74 | -7.4 | -10.0 | ||
Maximum of Months | 0.616843E+10 | 13905.17 | 28.17 | 21.54 | 0.288473E+09 | 348.95 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.882299E+09 | 6090.25 | 19-JAN-13:25 | 9.40 | 3.94 | 0.339532E+09 | 549.50 | 30-JAN-14:39 | 2.80 | -1.1 |
February | 0.117524E+10 | 6581.89 | 02-FEB-13:50 | 5.78 | -0.8 | 0.314572E+09 | 549.50 | 17-FEB-14:09 | 6.60 | 2.15 |
March | 0.265097E+10 | 9195.06 | 03-MAR-13:30 | 14.70 | 8.33 | 0.398314E+09 | 549.51 | 23-MAR-13:00 | 5.00 | 1.08 |
April | 0.317878E+10 | 10204.97 | 07-APR-12:30 | 26.15 | 15.90 | 0.370457E+09 | 549.87 | 07-APR-13:30 | 26.40 | 16.17 |
May | 0.462256E+10 | 15809.46 | 28-MAY-13:23 | 25.30 | 14.63 | 0.427121E+09 | 550.15 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.630169E+10 | 15210.02 | 04-JUN-14:22 | 24.15 | 13.65 | 0.435511E+09 | 549.78 | 19-JUN-13:30 | 34.70 | 23.81 |
July | 0.748372E+10 | 16161.70 | 04-JUL-12:13 | 28.13 | 19.53 | 0.406303E+09 | 550.02 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.917756E+10 | 16365.57 | 13-AUG-12:32 | 30.93 | 19.36 | 0.455419E+09 | 550.64 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.681593E+10 | 16787.45 | 04-SEP-12:32 | 26.10 | 18.14 | 0.401059E+09 | 565.76 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.627913E+10 | 17240.59 | 15-OCT-12:02 | 20.10 | 13.52 | 0.408719E+09 | 555.26 | 04-OCT-13:09 | 20.10 | 13.52 |
November | 0.219594E+10 | 11058.80 | 02-NOV-13:00 | 15.60 | 8.21 | 0.368298E+09 | 549.63 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.113769E+10 | 6376.71 | 21-DEC-13:25 | 3.05 | -1.7 | 0.336431E+09 | 549.49 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.519015E+11 | 0.466174E+10 | ||||||||
Minimum of Months | 0.882299E+09 | 6090.25 | 3.05 | -1.7 | 0.314572E+09 | 549.49 | 2.80 | -1.7 | ||
Maximum of Months | 0.917756E+10 | 17240.59 | 30.93 | 19.53 | 0.455419E+09 | 565.76 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181759E+09 | 1304.47 | 19-JAN-15:40 | 8.50 | 3.16 | 0.199235E+09 | 345.71 | 19-JAN-14:00 | 8.50 | 3.16 |
February | 0.258442E+09 | 2181.19 | 24-FEB-15:30 | 8.05 | 2.04 | 0.183780E+09 | 347.83 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.109631E+10 | 5637.81 | 29-MAR-16:00 | 7.20 | 4.88 | 0.237926E+09 | 347.85 | 29-MAR-13:20 | 7.20 | 4.88 |
April | 0.194280E+10 | 9103.78 | 09-APR-16:33 | 16.47 | 13.91 | 0.229867E+09 | 347.85 | 07-APR-13:20 | 16.47 | 13.91 |
May | 0.344557E+10 | 12042.38 | 14-MAY-15:23 | 13.60 | 9.19 | 0.270506E+09 | 347.88 | 15-MAY-13:00 | 17.80 | 11.36 |
June | 0.500902E+10 | 14908.02 | 04-JUN-15:42 | 22.48 | 14.39 | 0.275936E+09 | 347.86 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.550860E+10 | 14737.62 | 02-JUL-16:32 | 24.60 | 20.65 | 0.257351E+09 | 347.86 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.615537E+10 | 14420.34 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288353E+09 | 347.86 | 08-AUG-13:50 | 30.00 | 20.46 |
September | 0.359694E+10 | 14292.21 | 10-SEP-16:02 | 23.22 | 12.85 | 0.252877E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.252554E+10 | 12281.42 | 15-OCT-14:42 | 20.68 | 12.94 | 0.251982E+09 | 347.85 | 12-OCT-13:00 | 20.68 | 12.94 |
November | 0.645491E+09 | 3750.63 | 03-NOV-15:30 | 16.10 | 10.65 | 0.213843E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.210658E+09 | 1129.06 | 08-DEC-15:30 | 6.40 | 2.12 | 0.193406E+09 | 340.11 | 21-DEC-14:00 | 3.30 | -1.8 |
Annual Sum or Average | 0.305765E+11 | 0.285506E+10 | ||||||||
Minimum of Months | 0.181759E+09 | 1129.06 | 6.40 | 2.04 | 0.183780E+09 | 340.11 | 3.30 | -1.8 | ||
Maximum of Months | 0.615537E+10 | 14908.02 | 30.00 | 20.65 | 0.288353E+09 | 347.88 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220198E+09 | 1121.84 | 14-JAN-17:02 | -6.0 | -6.6 | 0.305958E+09 | 430.89 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.190209E+09 | 983.34 | 24-FEB-14:10 | 9.22 | 3.12 | 0.279204E+09 | 433.84 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.937215E+09 | 1283.00 | 28-MAR-14:00 | 13.30 | 8.41 | 0.354602E+09 | 520.01 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.144903E+10 | 2351.89 | 10-APR-14:00 | 20.60 | 10.45 | 0.352294E+09 | 549.50 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.256343E+10 | 4645.46 | 30-MAY-14:00 | 29.40 | 16.93 | 0.423498E+09 | 549.51 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.431557E+10 | 7516.16 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435328E+09 | 549.50 | 05-JUN-09:20 | 21.97 | 17.81 |
July | 0.541921E+10 | 7511.53 | 17-JUL-06:03 | 22.48 | 19.71 | 0.405637E+09 | 549.57 | 03-JUL-13:09 | 22.48 | 19.71 |
August | 0.570682E+10 | 7369.34 | 14-AUG-06:03 | 23.48 | 21.76 | 0.455019E+09 | 549.50 | 08-AUG-13:20 | 23.48 | 21.76 |
September | 0.377203E+10 | 6746.44 | 05-SEP-06:03 | 20.78 | 18.13 | 0.402058E+09 | 549.51 | 19-SEP-09:39 | 19.43 | 14.80 |
October | 0.258030E+10 | 3820.36 | 05-OCT-14:00 | 23.30 | 18.86 | 0.409183E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.120404E+10 | 1702.81 | 03-NOV-14:00 | 17.80 | 10.67 | 0.351481E+09 | 549.49 | 03-NOV-13:20 | 17.80 | 10.67 |
December | 0.481114E+09 | 1061.73 | 20-DEC-14:00 | 10.00 | 5.91 | 0.300958E+09 | 455.50 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.288392E+11 | 0.447522E+10 | ||||||||
Minimum of Months | 0.190209E+09 | 983.34 | -6.0 | -6.6 | 0.279204E+09 | 430.89 | 7.80 | 2.95 | ||
Maximum of Months | 0.570682E+10 | 7516.16 | 29.40 | 21.76 | 0.455019E+09 | 549.57 | 29.40 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252750E+09 | 875.99 | 31-JAN-09:00 | -7.8 | -10.3 | 0.198742E+09 | 315.87 | 27-JAN-10:39 | -7.8 | -10.3 |
February | 0.308993E+09 | 855.79 | 09-FEB-08:50 | -7.3 | -9.1 | 0.183459E+09 | 321.30 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.929370E+09 | 2487.70 | 29-MAR-09:30 | 6.15 | 3.19 | 0.249374E+09 | 347.88 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.156746E+10 | 4358.94 | 28-APR-09:10 | 16.28 | 8.96 | 0.240211E+09 | 347.88 | 26-APR-09:00 | 16.28 | 8.96 |
May | 0.284884E+10 | 10958.53 | 28-MAY-08:42 | 20.40 | 12.77 | 0.272765E+09 | 348.16 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.404135E+10 | 11206.67 | 25-JUN-09:12 | 25.77 | 23.51 | 0.276252E+09 | 348.17 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.489315E+10 | 10109.40 | 09-JUL-09:32 | 29.43 | 25.37 | 0.257404E+09 | 348.51 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.580847E+10 | 9142.61 | 13-AUG-09:52 | 28.90 | 19.41 | 0.288640E+09 | 348.43 | 03-AUG-09:50 | 28.90 | 19.41 |
September | 0.376142E+10 | 11225.31 | 10-SEP-08:32 | 19.63 | 13.49 | 0.255711E+09 | 348.08 | 06-SEP-09:30 | 19.63 | 13.49 |
October | 0.277327E+10 | 5059.45 | 05-OCT-09:20 | 19.27 | 16.99 | 0.263764E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.102501E+10 | 2500.71 | 03-NOV-09:30 | 13.05 | 8.24 | 0.235842E+09 | 347.88 | 07-NOV-10:20 | 10.37 | 7.28 |
December | 0.493305E+09 | 854.13 | 20-DEC-10:00 | 8.30 | 5.00 | 0.201788E+09 | 342.68 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.287034E+11 | 0.292395E+10 | ||||||||
Minimum of Months | 0.252750E+09 | 854.13 | -7.8 | -10.3 | 0.183459E+09 | 315.87 | -7.8 | -10.3 | ||
Maximum of Months | 0.580847E+10 | 11225.31 | 29.43 | 25.37 | 0.288640E+09 | 348.51 | 30.60 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371596E+09 | 1668.87 | 19-JAN-14:30 | 9.15 | 3.65 | 0.304288E+09 | 549.50 | 19-JAN-14:09 | 9.15 | 3.65 |
February | 0.437228E+09 | 2652.15 | 25-FEB-13:10 | 2.88 | -1.9 | 0.280848E+09 | 549.50 | 02-FEB-14:50 | 2.88 | -1.9 |
March | 0.120165E+10 | 5911.60 | 03-MAR-13:20 | 14.60 | 8.23 | 0.368111E+09 | 549.51 | 07-MAR-14:09 | 10.00 | 5.05 |
April | 0.181432E+10 | 7128.03 | 07-APR-12:00 | 25.60 | 15.40 | 0.349511E+09 | 549.51 | 12-APR-13:09 | 11.28 | 2.93 |
May | 0.284647E+10 | 10778.66 | 30-MAY-12:00 | 29.40 | 17.58 | 0.409404E+09 | 555.11 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.503918E+10 | 12347.95 | 19-JUN-12:00 | 36.70 | 24.28 | 0.433323E+09 | 640.33 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.709515E+10 | 11763.78 | 07-JUL-12:00 | 33.90 | 23.31 | 0.406454E+09 | 606.81 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.923330E+10 | 13094.98 | 20-AUG-11:43 | 26.60 | 15.57 | 0.456617E+09 | 611.55 | 18-AUG-12:09 | 26.60 | 15.57 |
September | 0.662290E+10 | 13885.58 | 10-SEP-13:12 | 24.07 | 14.06 | 0.402344E+09 | 596.45 | 01-SEP-12:09 | 24.07 | 14.06 |
October | 0.591228E+10 | 13544.82 | 15-OCT-13:43 | 21.02 | 13.40 | 0.411909E+09 | 572.84 | 04-OCT-13:20 | 21.02 | 13.40 |
November | 0.179535E+10 | 10315.01 | 06-NOV-13:07 | 12.98 | 7.45 | 0.357004E+09 | 549.63 | 02-NOV-13:00 | 12.98 | 7.45 |
December | 0.790077E+09 | 5750.72 | 17-DEC-12:53 | 12.20 | 4.95 | 0.315270E+09 | 549.51 | 15-DEC-14:09 | 12.20 | 4.95 |
Annual Sum or Average | 0.431595E+11 | 0.449508E+10 | ||||||||
Minimum of Months | 0.371596E+09 | 1668.87 | 2.88 | -1.9 | 0.280848E+09 | 549.50 | 2.88 | -1.9 | ||
Maximum of Months | 0.923330E+10 | 13885.58 | 36.70 | 24.28 | 0.456617E+09 | 640.33 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240769E+09 | 936.44 | 20-JAN-16:00 | 7.20 | 3.80 | 0.198956E+09 | 338.68 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.274260E+09 | 1381.59 | 22-FEB-16:30 | 3.85 | -0.7 | 0.183433E+09 | 338.68 | 22-FEB-16:00 | 3.30 | -0.7 |
March | 0.100260E+10 | 3611.01 | 27-MAR-16:50 | 21.28 | 15.57 | 0.240484E+09 | 347.84 | 28-MAR-13:20 | 13.70 | 8.60 |
April | 0.154162E+10 | 5714.93 | 10-APR-16:00 | 20.00 | 11.13 | 0.233123E+09 | 347.85 | 07-APR-13:20 | 20.00 | 11.13 |
May | 0.260972E+10 | 6968.43 | 30-MAY-16:00 | 28.30 | 17.60 | 0.270845E+09 | 347.87 | 15-MAY-13:00 | 28.30 | 17.60 |
June | 0.424192E+10 | 11379.15 | 04-JUN-15:42 | 22.48 | 14.39 | 0.276237E+09 | 347.86 | 22-JUN-09:20 | 25.77 | 16.91 |
July | 0.487232E+10 | 11218.71 | 02-JUL-16:32 | 24.60 | 20.65 | 0.257347E+09 | 347.86 | 12-JUL-13:50 | 28.40 | 19.35 |
August | 0.578238E+10 | 11162.49 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288644E+09 | 347.86 | 08-AUG-13:20 | 30.00 | 20.46 |
September | 0.367904E+10 | 12029.15 | 10-SEP-16:31 | 22.97 | 12.76 | 0.255386E+09 | 347.86 | 19-SEP-09:20 | 18.87 | 14.31 |
October | 0.281982E+10 | 8310.17 | 15-OCT-15:02 | 20.40 | 12.73 | 0.262814E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.928078E+09 | 3533.51 | 03-NOV-15:30 | 16.10 | 10.65 | 0.228435E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.431692E+09 | 1010.70 | 21-DEC-15:30 | 3.05 | -2.0 | 0.198309E+09 | 338.68 | 18-DEC-15:00 | 3.05 | -2.0 |
Annual Sum or Average | 0.284242E+11 | 0.289401E+10 | ||||||||
Minimum of Months | 0.240769E+09 | 936.44 | 3.05 | -2.0 | 0.183433E+09 | 338.68 | 3.05 | -2.0 | ||
Maximum of Months | 0.578238E+10 | 12029.15 | 30.00 | 20.65 | 0.288644E+09 | 347.87 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258208E+09 | 1077.90 | 14-JAN-17:02 | -6.0 | -6.6 | 0.307796E+09 | 451.32 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.296386E+09 | 1071.07 | 24-FEB-15:40 | 7.97 | 1.96 | 0.281940E+09 | 456.59 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.123418E+10 | 1920.31 | 28-MAR-14:00 | 13.30 | 8.41 | 0.372882E+09 | 549.49 | 28-MAR-13:20 | 13.30 | 8.41 |
April | 0.194473E+10 | 3685.36 | 10-APR-14:00 | 20.60 | 10.45 | 0.370908E+09 | 549.50 | 07-APR-13:20 | 20.60 | 10.45 |
May | 0.356906E+10 | 8177.15 | 30-MAY-06:03 | 20.47 | 15.45 | 0.431846E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.534446E+10 | 8911.16 | 19-JUN-05:03 | 24.08 | 22.05 | 0.436077E+09 | 550.29 | 19-JUN-13:20 | 34.80 | 23.85 |
July | 0.611919E+10 | 9858.99 | 09-JUL-16:02 | 27.12 | 24.30 | 0.406249E+09 | 550.41 | 25-JUL-13:20 | 28.53 | 24.38 |
August | 0.613982E+10 | 8246.63 | 15-AUG-05:03 | 24.40 | 22.15 | 0.455344E+09 | 550.06 | 14-AUG-09:20 | 24.40 | 22.15 |
September | 0.388325E+10 | 7983.07 | 01-SEP-05:02 | 24.08 | 21.83 | 0.401578E+09 | 550.16 | 05-SEP-09:20 | 24.07 | 19.46 |
October | 0.260875E+10 | 4073.82 | 05-OCT-14:00 | 23.30 | 18.86 | 0.406468E+09 | 549.51 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.110514E+10 | 1997.18 | 03-NOV-14:00 | 17.80 | 10.67 | 0.345398E+09 | 549.50 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.440800E+09 | 1094.97 | 20-DEC-14:00 | 10.00 | 5.91 | 0.300584E+09 | 465.12 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.329440E+11 | 0.451707E+10 | ||||||||
Minimum of Months | 0.258208E+09 | 1071.07 | -6.0 | -6.6 | 0.281940E+09 | 451.32 | 7.80 | 1.96 | ||
Maximum of Months | 0.613982E+10 | 9858.99 | 27.12 | 24.30 | 0.455344E+09 | 550.41 | 34.80 | 24.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220888E+09 | 936.74 | 31-JAN-09:30 | -7.2 | -9.9 | 0.147709E+09 | 334.77 | 19-JAN-11:09 | -7.2 | -9.9 |
February | 0.282668E+09 | 1673.67 | 22-FEB-11:05 | 2.38 | -2.1 | 0.138349E+09 | 352.45 | 22-FEB-11:09 | 2.38 | -2.1 |
March | 0.102455E+10 | 6522.24 | 29-MAR-12:01 | 7.80 | 5.26 | 0.189023E+09 | 356.45 | 21-MAR-12:09 | 7.80 | 5.26 |
April | 0.191367E+10 | 6811.01 | 07-APR-10:05 | 21.97 | 14.06 | 0.179792E+09 | 356.47 | 26-APR-10:09 | 16.57 | 12.62 |
May | 0.346690E+10 | 12890.65 | 29-MAY-08:32 | 25.37 | 16.74 | 0.203714E+09 | 356.47 | 15-MAY-14:09 | 25.37 | 16.74 |
June | 0.447826E+10 | 13816.99 | 25-JUN-08:32 | 25.20 | 23.38 | 0.204948E+09 | 356.46 | 02-JUN-12:09 | 25.20 | 23.38 |
July | 0.516420E+10 | 14337.61 | 02-JUL-09:01 | 25.68 | 21.69 | 0.191651E+09 | 356.46 | 11-JUL-10:09 | 25.18 | 17.11 |
August | 0.575883E+10 | 12381.67 | 13-AUG-09:12 | 28.17 | 19.21 | 0.213976E+09 | 356.90 | 14-AUG-10:09 | 27.88 | 23.11 |
September | 0.353865E+10 | 13741.09 | 10-SEP-08:32 | 19.63 | 13.49 | 0.189372E+09 | 356.47 | 19-SEP-10:09 | 20.00 | 15.38 |
October | 0.249005E+10 | 6605.21 | 15-OCT-09:33 | 17.93 | 12.69 | 0.193731E+09 | 356.46 | 02-OCT-10:09 | 17.93 | 12.69 |
November | 0.792463E+09 | 5417.89 | 01-NOV-12:02 | 12.88 | 7.12 | 0.170065E+09 | 356.45 | 09-NOV-15:09 | 13.80 | 12.65 |
December | 0.331892E+09 | 1629.88 | 20-DEC-11:05 | 8.90 | 5.16 | 0.148032E+09 | 351.58 | 20-DEC-11:09 | 8.90 | 5.16 |
Annual Sum or Average | 0.294630E+11 | 0.217036E+10 | ||||||||
Minimum of Months | 0.220888E+09 | 936.74 | -7.2 | -9.9 | 0.138349E+09 | 334.77 | -7.2 | -9.9 | ||
Maximum of Months | 0.575883E+10 | 14337.61 | 28.17 | 23.38 | 0.213976E+09 | 356.90 | 27.88 | 23.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119532E+10 | 6416.64 | 19-JAN-13:25 | 9.40 | 3.94 | 0.346585E+09 | 549.50 | 30-JAN-14:50 | 2.80 | -1.0 |
February | 0.150702E+10 | 7042.84 | 02-FEB-13:40 | 5.97 | -0.5 | 0.323912E+09 | 549.50 | 17-FEB-14:09 | 6.60 | 2.15 |
March | 0.309303E+10 | 9221.08 | 29-MAR-12:50 | 7.80 | 5.26 | 0.411722E+09 | 550.81 | 03-MAR-14:09 | 7.80 | 5.26 |
April | 0.341500E+10 | 9645.09 | 07-APR-12:30 | 26.15 | 15.90 | 0.381257E+09 | 550.39 | 10-APR-13:20 | 20.20 | 10.17 |
May | 0.463182E+10 | 14754.16 | 29-MAY-11:53 | 28.90 | 18.44 | 0.432248E+09 | 550.57 | 30-MAY-13:20 | 29.80 | 17.64 |
June | 0.611481E+10 | 10803.26 | 19-JUN-05:02 | 24.08 | 22.05 | 0.436133E+09 | 550.31 | 19-JUN-13:20 | 34.80 | 23.85 |
July | 0.718310E+10 | 14636.22 | 09-JUL-13:22 | 31.70 | 25.11 | 0.406433E+09 | 550.92 | 17-JUL-13:20 | 28.50 | 22.01 |
August | 0.883600E+10 | 14825.59 | 20-AUG-11:43 | 26.60 | 15.57 | 0.455904E+09 | 561.76 | 30-AUG-13:20 | 27.77 | 15.58 |
September | 0.689650E+10 | 15966.82 | 10-SEP-12:32 | 23.53 | 13.85 | 0.403741E+09 | 581.18 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.675346E+10 | 15691.04 | 15-OCT-12:12 | 20.20 | 13.39 | 0.415649E+09 | 572.39 | 04-OCT-13:20 | 20.20 | 13.39 |
November | 0.276509E+10 | 11360.51 | 02-NOV-12:40 | 15.40 | 8.14 | 0.383112E+09 | 549.71 | 06-NOV-14:09 | 13.80 | 8.03 |
December | 0.163591E+10 | 9828.05 | 17-DEC-12:53 | 12.20 | 4.95 | 0.348403E+09 | 549.49 | 14-DEC-14:09 | 12.20 | 4.95 |
Annual Sum or Average | 0.540271E+11 | 0.474510E+10 | ||||||||
Minimum of Months | 0.119532E+10 | 6416.64 | 5.97 | -0.5 | 0.323912E+09 | 549.49 | 2.80 | -1.0 | ||
Maximum of Months | 0.883600E+10 | 15966.82 | 31.70 | 25.11 | 0.455904E+09 | 581.18 | 34.80 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278202E+09 | 1573.94 | 20-JAN-15:50 | 7.30 | 3.83 | 0.201857E+09 | 347.75 | 19-JAN-14:00 | 7.30 | 3.83 |
February | 0.366296E+09 | 2569.67 | 24-FEB-15:30 | 8.05 | 2.04 | 0.187084E+09 | 347.83 | 17-FEB-14:50 | 8.05 | 2.04 |
March | 0.134043E+10 | 5682.56 | 29-MAR-15:50 | 7.20 | 4.93 | 0.246215E+09 | 347.84 | 23-MAR-13:00 | 7.20 | 4.93 |
April | 0.207025E+10 | 13208.72 | 09-APR-17:02 | 15.92 | 13.68 | 0.237779E+09 | 347.85 | 07-APR-13:20 | 15.92 | 13.68 |
May | 0.344140E+10 | 11787.63 | 29-MAY-14:32 | 25.77 | 17.17 | 0.273790E+09 | 347.88 | 15-MAY-13:00 | 25.77 | 17.17 |
June | 0.487002E+10 | 13510.50 | 18-JUN-15:52 | 25.60 | 22.09 | 0.276284E+09 | 347.87 | 26-JUN-09:20 | 25.37 | 19.69 |
July | 0.529771E+10 | 14255.44 | 02-JUL-17:01 | 24.13 | 20.51 | 0.257420E+09 | 347.87 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.593649E+10 | 13174.20 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288553E+09 | 348.22 | 14-AUG-09:20 | 27.40 | 22.88 |
September | 0.365177E+10 | 14332.57 | 10-SEP-16:31 | 22.97 | 12.76 | 0.254718E+09 | 348.29 | 05-SEP-09:20 | 22.97 | 12.76 |
October | 0.274661E+10 | 11955.05 | 15-OCT-15:32 | 19.80 | 12.41 | 0.259113E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.878903E+09 | 3923.50 | 03-NOV-15:30 | 16.10 | 10.65 | 0.223951E+09 | 347.85 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.389098E+09 | 1446.04 | 08-DEC-15:30 | 6.40 | 2.12 | 0.198262E+09 | 347.83 | 21-DEC-14:50 | 3.30 | -1.8 |
Annual Sum or Average | 0.312672E+11 | 0.290503E+10 | ||||||||
Minimum of Months | 0.278202E+09 | 1446.04 | 6.40 | 2.04 | 0.187084E+09 | 347.75 | 3.30 | -1.8 | ||
Maximum of Months | 0.593649E+10 | 14332.57 | 30.00 | 22.09 | 0.288553E+09 | 348.29 | 27.97 | 22.88 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186112E+09 | 8513.47 | 02-JAN-05:02 | -12.1 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.186112E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.1 | |
Maximum of Months | 0.186112E+09 | 8513.47 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432144E+10 | 14446.47 | 02-JAN-06:10 | -11.7 |
February | 0.349036E+10 | 13509.70 | 06-FEB-05:06 | -13.2 |
March | 0.159764E+10 | 10652.74 | 20-MAR-06:12 | -0.6 |
April | 0.803946E+09 | 7864.75 | 03-APR-06:01 | 2.38 |
May | 0.247801E+09 | 3449.14 | 30-MAY-05:12 | 18.53 |
June | 55754855.08 | 4964.75 | 19-JUN-05:02 | 24.08 |
July | 24109449.83 | 4407.39 | 25-JUL-05:02 | 23.90 |
August | 50697649.91 | 3695.96 | 01-AUG-05:03 | 23.90 |
September | 0.175559E+09 | 3405.91 | 01-SEP-05:02 | 24.08 |
October | 0.534611E+09 | 3369.34 | 19-OCT-05:03 | 5.37 |
November | 0.172650E+10 | 11606.79 | 24-NOV-06:08 | -4.4 |
December | 0.295924E+10 | 11003.41 | 11-DEC-06:09 | 1.70 |
Annual Sum or Average | 0.159877E+11 | |||
Minimum of Months | 24109449.83 | 3369.34 | -13.2 | |
Maximum of Months | 0.432144E+10 | 14446.47 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232089E+10 | 9185.20 | 02-JAN-08:19 | -10.9 |
February | 0.173013E+10 | 6512.51 | 06-FEB-07:20 | -13.1 |
March | 0.110904E+10 | 3450.94 | 01-MAR-11:05 | 13.90 |
April | 0.409580E+09 | 3406.32 | 16-APR-15:43 | 21.20 |
May | 74565029.13 | 2515.65 | 21-MAY-07:53 | 17.20 |
June | 18212033.75 | 2438.25 | 19-JUN-05:02 | 24.08 |
July | 27656857.73 | 3035.10 | 09-JUL-14:41 | 27.95 |
August | 19486807.82 | 2855.19 | 20-AUG-14:23 | 28.35 |
September | 25938199.70 | 3926.81 | 10-SEP-09:52 | 21.70 |
October | 0.133528E+09 | 4419.14 | 29-OCT-12:53 | 11.70 |
November | 0.996054E+09 | 4105.31 | 24-NOV-07:12 | -4.2 |
December | 0.153017E+10 | 5606.81 | 17-DEC-12:53 | 12.20 |
Annual Sum or Average | 0.839525E+10 | |||
Minimum of Months | 18212033.75 | 2438.25 | -13.1 | |
Maximum of Months | 0.232089E+10 | 9185.20 | 28.35 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186070E+10 | 7702.78 | 02-JAN-12:01 | -7.0 |
February | 0.122978E+10 | 2880.71 | 06-FEB-09:00 | -12.2 |
March | 0.642068E+09 | 2893.82 | 13-MAR-07:16 | 0.00 |
April | 0.164278E+09 | 2301.50 | 10-APR-05:12 | 15.20 |
May | 24831021.15 | 1969.35 | 19-MAY-05:13 | 16.03 |
June | 22600225.45 | 2704.55 | 19-JUN-05:02 | 24.08 |
July | 30959459.13 | 3063.35 | 18-JUL-04:02 | 24.40 |
August | 29848604.36 | 3518.50 | 22-AUG-04:02 | 25.92 |
September | 37135024.00 | 3442.84 | 01-SEP-05:02 | 24.08 |
October | 56575873.21 | 3314.21 | 02-OCT-05:12 | 10.60 |
November | 0.564785E+09 | 4518.13 | 06-NOV-06:12 | 5.00 |
December | 0.115855E+10 | 3127.31 | 17-DEC-12:10 | 12.20 |
Annual Sum or Average | 0.582212E+10 | |||
Minimum of Months | 22600225.45 | 1969.35 | -12.2 | |
Maximum of Months | 0.186070E+10 | 7702.78 | 25.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700144E+09 | 16050.71 | 02-JAN-05:02 | -12.1 |
February | 0.132631E+09 | 12687.89 | 06-FEB-06:02 | -12.9 |
March | 3405177.37 | 10675.50 | 20-MAR-06:01 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 13485103.47 | 11069.77 | 24-NOV-07:01 | -4.3 |
December | 32124139.72 | 11160.56 | 11-DEC-07:01 | 1.70 |
Annual Sum or Average | 0.881790E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.700144E+09 | 16050.71 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236188E+10 | 23247.76 | 02-JAN-04:42 | -12.1 |
February | 0.137829E+10 | 21887.58 | 06-FEB-05:01 | -13.2 |
March | 0.198022E+09 | 18824.15 | 20-MAR-05:01 | -1.5 |
April | 23541144.15 | 17411.71 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.400806E+09 | 19621.59 | 24-NOV-06:01 | -4.4 |
December | 0.711303E+09 | 19870.65 | 26-DEC-06:11 | 6.30 |
Annual Sum or Average | 0.507384E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.236188E+10 | 23247.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369289E+10 | 9554.28 | 02-JAN-00:02 | -10.7 |
February | 0.297026E+10 | 9279.78 | 05-FEB-23:33 | -12.9 |
March | 0.734546E+09 | 8162.36 | 20-MAR-04:02 | -0.8 |
April | 0.137626E+09 | 7868.77 | 03-APR-05:11 | 2.60 |
May | 897518.48 | 4430.79 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 17534723.89 | 6688.99 | 31-OCT-06:02 | 5.68 |
November | 0.911171E+09 | 8717.38 | 24-NOV-05:01 | -4.0 |
December | 0.217253E+10 | 8980.72 | 31-DEC-22:33 | -7.6 |
Annual Sum or Average | 0.106375E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.369289E+10 | 9554.28 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201222E+10 | 8257.98 | 02-JAN-00:02 | -10.7 |
February | 0.145047E+10 | 7886.93 | 05-FEB-23:33 | -12.9 |
March | 0.327958E+09 | 6784.28 | 20-MAR-04:02 | -0.8 |
April | 65052702.98 | 6422.03 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 8435029.08 | 5144.16 | 31-OCT-06:02 | 5.68 |
November | 0.451725E+09 | 7381.88 | 24-NOV-05:01 | -4.0 |
December | 0.113990E+10 | 7559.40 | 31-DEC-23:13 | -8.0 |
Annual Sum or Average | 0.545577E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.201222E+10 | 8257.98 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244553E+10 | 11173.46 | 02-JAN-00:02 | -10.7 |
February | 0.175409E+10 | 10631.88 | 05-FEB-23:33 | -12.9 |
March | 0.477853E+09 | 9215.22 | 13-MAR-04:02 | -0.1 |
April | 0.117233E+09 | 8840.40 | 03-APR-05:11 | 2.60 |
May | 1438575.33 | 5682.84 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 7019181.65 | 7328.60 | 28-OCT-06:03 | 3.90 |
November | 0.515101E+09 | 10044.29 | 24-NOV-05:01 | -4.0 |
December | 0.136274E+10 | 10171.15 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.668100E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.244553E+10 | 11173.46 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223379E+10 | 8658.46 | 02-JAN-00:02 | -10.7 |
February | 0.173422E+10 | 8268.17 | 05-FEB-23:33 | -12.9 |
March | 0.401655E+09 | 6973.30 | 13-MAR-04:02 | -0.1 |
April | 84835357.03 | 6537.03 | 03-APR-05:11 | 2.60 |
May | 807876.23 | 3311.71 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 9374203.19 | 5271.10 | 31-OCT-06:02 | 5.68 |
November | 0.556341E+09 | 7692.13 | 24-NOV-05:01 | -4.0 |
December | 0.130247E+10 | 7764.18 | 11-DEC-05:51 | 1.70 |
Annual Sum or Average | 0.632349E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.223379E+10 | 8658.46 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214620E+10 | 7186.72 | 02-JAN-00:02 | -10.7 |
February | 0.165252E+10 | 6824.39 | 06-FEB-05:01 | -13.2 |
March | 0.289494E+09 | 5780.77 | 20-MAR-05:01 | -1.5 |
April | 30106364.55 | 5551.69 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.136926E+09 | 5754.67 | 24-NOV-06:01 | -4.4 |
December | 0.499881E+09 | 5702.09 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.475513E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.214620E+10 | 7186.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108427E+10 | 6268.56 | 02-JAN-00:02 | -10.7 |
February | 0.629229E+09 | 5780.81 | 06-FEB-05:01 | -13.2 |
March | 81845960.75 | 4699.68 | 20-MAR-05:01 | -1.5 |
April | 7240579.42 | 4368.61 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 41305141.04 | 4563.46 | 24-NOV-06:01 | -4.4 |
December | 0.222620E+09 | 4636.02 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.206651E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.108427E+10 | 6268.56 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349101E+10 | 10500.89 | 02-JAN-07:50 | -11.2 |
February | 0.277517E+10 | 9239.28 | 06-FEB-07:10 | -13.2 |
March | 0.170202E+10 | 8206.97 | 17-MAR-06:10 | -1.1 |
April | 0.830441E+09 | 7548.37 | 03-APR-06:10 | 2.38 |
May | 0.257574E+09 | 6259.28 | 01-MAY-06:10 | 7.67 |
June | 161642.66 | 1225.24 | 02-JUN-06:10 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 2652718.14 | 3982.39 | 20-SEP-06:07 | 12.48 |
October | 0.156647E+09 | 6093.05 | 27-OCT-06:10 | 5.68 |
November | 0.108904E+10 | 8030.03 | 24-NOV-07:10 | -4.3 |
December | 0.208828E+10 | 8293.64 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.123930E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.349101E+10 | 10500.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121565E+10 | 6428.22 | 02-JAN-00:02 | -10.7 |
February | 0.789469E+09 | 5994.28 | 06-FEB-05:01 | -13.2 |
March | 84216611.79 | 4679.97 | 01-MAR-06:11 | 4.07 |
April | 10560996.86 | 4202.88 | 03-APR-06:01 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 62512295.20 | 4630.51 | 24-NOV-06:01 | -4.4 |
December | 0.259103E+09 | 4713.16 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.242151E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.121565E+10 | 6428.22 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201948E+10 | 7770.33 | 02-JAN-00:02 | -10.7 |
February | 0.138399E+10 | 7332.16 | 06-FEB-05:11 | -13.1 |
March | 0.178909E+09 | 6171.00 | 13-MAR-05:01 | -0.6 |
April | 17814732.98 | 5895.79 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.275880E+09 | 6558.50 | 24-NOV-05:01 | -4.0 |
December | 0.732080E+09 | 6448.02 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.460815E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.201948E+10 | 7770.33 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107906E+10 | 7043.45 | 02-JAN-00:02 | -10.7 |
February | 0.630580E+09 | 6542.81 | 06-FEB-05:11 | -13.1 |
March | 80033493.12 | 5163.85 | 20-MAR-05:01 | -1.5 |
April | 5627914.05 | 4768.49 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.133621E+09 | 5587.80 | 24-NOV-05:01 | -4.0 |
December | 0.384811E+09 | 5519.94 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.231373E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.107906E+10 | 7043.45 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122833E+10 | 9169.65 | 02-JAN-00:02 | -10.7 |
February | 0.686526E+09 | 8564.93 | 06-FEB-05:11 | -13.1 |
March | 0.102122E+09 | 6884.45 | 13-MAR-05:01 | -0.6 |
April | 13326585.43 | 6486.08 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.125734E+09 | 7226.46 | 24-NOV-06:01 | -4.4 |
December | 0.424673E+09 | 7391.16 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.258071E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.122833E+10 | 9169.65 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120719E+10 | 7185.61 | 02-JAN-00:02 | -10.7 |
February | 0.780540E+09 | 6662.71 | 06-FEB-05:11 | -13.1 |
March | 95137606.43 | 5194.13 | 13-MAR-05:01 | -0.6 |
April | 9978855.13 | 4717.69 | 03-APR-05:11 | 2.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.163967E+09 | 5620.79 | 24-NOV-06:01 | -4.4 |
December | 0.439892E+09 | 5586.97 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.269670E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.120719E+10 | 7185.61 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644244E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.540313E+09 | 944.20 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602358E+09 | 751.52 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512788E+09 | 554.47 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541448E+09 | 553.83 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530653E+09 | 540.92 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.499456E+09 | 536.99 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564589E+09 | 563.49 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523330E+09 | 666.11 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.567236E+09 | 825.61 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.617021E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.636201E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677964E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.499456E+09 | 536.99 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.644244E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.402565E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.339440E+09 | 604.38 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380303E+09 | 531.51 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325197E+09 | 341.63 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344962E+09 | 351.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338406E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.318275E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358725E+09 | 341.64 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330945E+09 | 359.20 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357658E+09 | 527.10 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388459E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.394262E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427920E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.318275E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402565E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620050E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.526134E+09 | 938.14 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596151E+09 | 674.69 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.513467E+09 | 551.23 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543718E+09 | 555.10 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533869E+09 | 545.61 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.502314E+09 | 542.14 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566536E+09 | 563.47 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521669E+09 | 581.87 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.559325E+09 | 794.60 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601635E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.605552E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.669042E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.502314E+09 | 542.14 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.620050E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397171E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335319E+09 | 589.25 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377105E+09 | 469.58 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324691E+09 | 362.38 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341884E+09 | 358.03 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335905E+09 | 352.44 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316481E+09 | 352.06 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.357096E+09 | 363.28 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330361E+09 | 447.97 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355388E+09 | 507.61 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382830E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389820E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424405E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316481E+09 | 352.06 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.397171E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.641569E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538491E+09 | 940.52 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.601060E+09 | 739.73 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512239E+09 | 550.36 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541075E+09 | 549.67 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530240E+09 | 536.13 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.498993E+09 | 532.02 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564288E+09 | 559.80 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522407E+09 | 583.18 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.565999E+09 | 817.37 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.615321E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.632889E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.676457E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.498993E+09 | 532.02 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.641569E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.401317E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.338640E+09 | 602.69 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379737E+09 | 527.65 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324833E+09 | 338.94 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344702E+09 | 348.95 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338143E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.317966E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358480E+09 | 338.63 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330505E+09 | 357.25 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357051E+09 | 523.04 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387679E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.393000E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427205E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.317966E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.401317E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.618776E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.525562E+09 | 934.14 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595550E+09 | 584.21 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512927E+09 | 546.93 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543330E+09 | 551.02 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533335E+09 | 541.10 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.501808E+09 | 537.47 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566180E+09 | 559.77 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520903E+09 | 579.02 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.558835E+09 | 784.77 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.600854E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.604161E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668222E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.501808E+09 | 537.47 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.618776E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.395748E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334608E+09 | 586.98 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376640E+09 | 463.79 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324305E+09 | 360.76 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341672E+09 | 356.00 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335671E+09 | 350.18 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316218E+09 | 349.80 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.356833E+09 | 361.47 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329949E+09 | 441.55 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355046E+09 | 502.98 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382028E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.388292E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.423701E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316218E+09 | 349.80 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.395748E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.644240E+09 | 1040.56 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.540311E+09 | 944.19 | 15-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.602357E+09 | 751.50 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.512787E+09 | 554.46 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.541447E+09 | 553.82 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.530653E+09 | 540.91 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.499456E+09 | 536.98 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.564589E+09 | 563.48 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523329E+09 | 666.07 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.567235E+09 | 825.59 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.617019E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.636198E+09 | 1040.56 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.677962E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.499456E+09 | 536.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.644240E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.402563E+09 | 658.76 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.339439E+09 | 604.37 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380302E+09 | 531.50 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.325197E+09 | 341.62 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.344962E+09 | 351.28 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.338406E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.318273E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.358756E+09 | 341.63 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330945E+09 | 359.20 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.357658E+09 | 527.09 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388458E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.394250E+09 | 658.76 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427921E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.318273E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.402563E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.620049E+09 | 1040.56 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.526133E+09 | 938.13 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596133E+09 | 674.66 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.513466E+09 | 551.22 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.543718E+09 | 555.09 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.533868E+09 | 545.60 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.502314E+09 | 542.13 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.566536E+09 | 563.46 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521668E+09 | 581.86 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.559325E+09 | 794.58 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601635E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.605551E+09 | 1040.56 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.669039E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.502314E+09 | 542.13 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.620049E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397170E+09 | 658.71 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335319E+09 | 589.24 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377105E+09 | 469.56 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324690E+09 | 362.37 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341884E+09 | 358.03 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335903E+09 | 352.44 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.316481E+09 | 352.05 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.357096E+09 | 363.28 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330361E+09 | 447.95 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355388E+09 | 507.59 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.382829E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389819E+09 | 658.71 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424404E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.316481E+09 | 352.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.397170E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.644244E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726646E+09 |
February | 0.901968E+09 | 0.540313E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647858E+09 |
March | 0.107774E+10 | 0.602358E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530011E+09 |
April | 0.956342E+09 | 0.512788E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281917.86 | 0.355037E+09 |
May | 0.103597E+10 | 0.541448E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1199350.92 | 0.218635E+09 |
June | 0.103308E+10 | 0.530653E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9063722.72 | 0.115629E+09 |
July | 0.959235E+09 | 0.499456E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21466209.45 | 42483042.76 |
August | 0.107774E+10 | 0.564589E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26248093.90 | 51895262.68 |
September | 0.956342E+09 | 0.523330E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3242386.57 | 0.118420E+09 |
October | 0.994195E+09 | 0.567236E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48854.95 | 0.288760E+09 |
November | 0.984487E+09 | 0.617021E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512642E+09 |
December | 0.959235E+09 | 0.636201E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608965E+09 |
Annual Sum or Average | 0.119305E+11 | 0.677964E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61550536.36 | 0.421698E+10 |
Minimum of Months | 0.901968E+09 | 0.499456E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42483042.76 |
Maximum of Months | 0.107774E+10 | 0.644244E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26248093.90 | 0.726646E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.402565E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485314E+09 |
February | 0.571020E+09 | 0.339440E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437565E+09 |
March | 0.682301E+09 | 0.380303E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360597E+09 |
April | 0.605444E+09 | 0.325197E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187846.23 | 0.246394E+09 |
May | 0.655854E+09 | 0.344962E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 693469.88 | 0.149958E+09 |
June | 0.654023E+09 | 0.338406E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5905773.86 | 78729593.30 |
July | 0.607275E+09 | 0.318275E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13861708.05 | 29398223.51 |
August | 0.682301E+09 | 0.358725E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17022096.45 | 36265261.96 |
September | 0.605444E+09 | 0.330945E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2150124.91 | 83259622.27 |
October | 0.629407E+09 | 0.357658E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32565.02 | 0.200453E+09 |
November | 0.623262E+09 | 0.388459E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348383E+09 |
December | 0.607275E+09 | 0.394262E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409223E+09 |
Annual Sum or Average | 0.755301E+10 | 0.427920E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39853584.40 | 0.286554E+10 |
Minimum of Months | 0.571020E+09 | 0.318275E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29398223.51 |
Maximum of Months | 0.682301E+09 | 0.402565E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17022096.45 | 0.485314E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.620050E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747765E+09 |
February | 0.901968E+09 | 0.526134E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682390E+09 |
March | 0.107774E+10 | 0.596151E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556355E+09 |
April | 0.956342E+09 | 0.513467E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281655.69 | 0.371829E+09 |
May | 0.103597E+10 | 0.543718E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1046943.27 | 0.222172E+09 |
June | 0.103308E+10 | 0.533869E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8896802.68 | 0.116276E+09 |
July | 0.959235E+09 | 0.502314E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20981828.28 | 43556785.19 |
August | 0.107774E+10 | 0.566536E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25435836.93 | 54698338.30 |
September | 0.956342E+09 | 0.521669E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3216166.38 | 0.127765E+09 |
October | 0.994195E+09 | 0.559325E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45918.22 | 0.317849E+09 |
November | 0.984487E+09 | 0.601635E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542964E+09 |
December | 0.959235E+09 | 0.605552E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642798E+09 |
Annual Sum or Average | 0.119305E+11 | 0.669042E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59905151.44 | 0.442642E+10 |
Minimum of Months | 0.901968E+09 | 0.502314E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43556785.19 |
Maximum of Months | 0.107774E+10 | 0.620050E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25435836.93 | 0.747765E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.397171E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487628E+09 |
February | 0.570983E+09 | 0.335319E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438427E+09 |
March | 0.682256E+09 | 0.377105E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365279E+09 |
April | 0.605404E+09 | 0.324691E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187859.41 | 0.246560E+09 |
May | 0.655811E+09 | 0.341884E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 788869.25 | 0.151180E+09 |
June | 0.653980E+09 | 0.335905E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5875873.13 | 81338900.79 |
July | 0.607235E+09 | 0.316481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13831405.52 | 31905831.96 |
August | 0.682256E+09 | 0.357096E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16842258.54 | 37863066.78 |
September | 0.605404E+09 | 0.330361E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2149378.12 | 83367060.52 |
October | 0.629366E+09 | 0.355388E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32587.20 | 0.202477E+09 |
November | 0.623221E+09 | 0.382830E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344848E+09 |
December | 0.607235E+09 | 0.389820E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410816E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424405E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39708231.17 | 0.288169E+10 |
Minimum of Months | 0.570983E+09 | 0.316481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31905831.96 |
Maximum of Months | 0.682256E+09 | 0.397171E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16842258.54 | 0.487628E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.641569E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409770E+09 |
February | 0.901968E+09 | 0.538491E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363033E+09 |
March | 0.107774E+10 | 0.601060E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291987E+09 |
April | 0.956342E+09 | 0.512239E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173692.31 | 0.193218E+09 |
May | 0.103597E+10 | 0.541075E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058421.11 | 0.113446E+09 |
June | 0.103308E+10 | 0.530240E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5553049.57 | 59125745.85 |
July | 0.959235E+09 | 0.498993E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13022459.14 | 19778944.11 |
August | 0.107774E+10 | 0.564288E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14897295.08 | 26788276.62 |
September | 0.956342E+09 | 0.522407E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1799847.89 | 66713399.97 |
October | 0.994195E+09 | 0.565999E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29313.28 | 0.169065E+09 |
November | 0.984487E+09 | 0.615321E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307427E+09 |
December | 0.959235E+09 | 0.632889E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357037E+09 |
Annual Sum or Average | 0.119305E+11 | 0.676457E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36534078.38 | 0.237739E+10 |
Minimum of Months | 0.901968E+09 | 0.498993E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19778944.11 |
Maximum of Months | 0.107774E+10 | 0.641569E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14897295.08 | 0.409770E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.401317E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274621E+09 |
February | 0.571020E+09 | 0.338640E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247365E+09 |
March | 0.682301E+09 | 0.379737E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201895E+09 |
April | 0.605444E+09 | 0.324833E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103153.47 | 0.136508E+09 |
May | 0.655854E+09 | 0.344702E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387415.11 | 80261035.47 |
June | 0.654023E+09 | 0.338143E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3309036.80 | 41892983.96 |
July | 0.607275E+09 | 0.317966E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7684700.04 | 14931079.88 |
August | 0.682301E+09 | 0.358480E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9209786.03 | 20102869.10 |
September | 0.605444E+09 | 0.330505E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1165347.46 | 48121293.88 |
October | 0.629407E+09 | 0.357051E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19540.11 | 0.118577E+09 |
November | 0.623262E+09 | 0.387679E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211279E+09 |
December | 0.607275E+09 | 0.393000E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241946E+09 |
Annual Sum or Average | 0.755301E+10 | 0.427205E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21878979.02 | 0.163750E+10 |
Minimum of Months | 0.571020E+09 | 0.317966E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14931079.88 |
Maximum of Months | 0.682301E+09 | 0.401317E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9209786.03 | 0.274621E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.618776E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514168E+10 |
February | 0.901968E+09 | 0.525562E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513706E+10 |
March | 0.107774E+10 | 0.595550E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466229E+10 |
April | 0.956342E+09 | 0.512927E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10879715.61 | 0.276948E+10 |
May | 0.103597E+10 | 0.543330E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44400260.31 | 0.168515E+10 |
June | 0.103308E+10 | 0.533335E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314880E+09 | 0.573712E+09 |
July | 0.959235E+09 | 0.501808E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666030E+09 | 78974688.95 |
August | 0.107774E+10 | 0.566180E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808799E+09 | 0.190521E+09 |
September | 0.956342E+09 | 0.520903E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132090E+09 | 0.806263E+09 |
October | 0.994195E+09 | 0.558835E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1612995.36 | 0.215656E+10 |
November | 0.984487E+09 | 0.600854E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390723E+10 |
December | 0.959235E+09 | 0.604161E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466900E+10 |
Annual Sum or Average | 0.119305E+11 | 0.668222E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197869E+10 | 0.317779E+11 |
Minimum of Months | 0.901968E+09 | 0.501808E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78974688.95 |
Maximum of Months | 0.107774E+10 | 0.618776E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.808799E+09 | 0.514168E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.395748E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275528E+09 |
February | 0.570983E+09 | 0.334608E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246984E+09 |
March | 0.682256E+09 | 0.376640E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204736E+09 |
April | 0.605404E+09 | 0.324305E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103432.03 | 0.137023E+09 |
May | 0.655811E+09 | 0.341672E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 520922.93 | 81357454.20 |
June | 0.653980E+09 | 0.335671E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3253270.10 | 44192637.42 |
July | 0.607235E+09 | 0.316218E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7682004.06 | 16834808.84 |
August | 0.682256E+09 | 0.356833E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9146801.12 | 21211117.75 |
September | 0.605404E+09 | 0.329949E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164224.99 | 48272184.77 |
October | 0.629366E+09 | 0.355046E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19551.80 | 0.120397E+09 |
November | 0.623221E+09 | 0.382028E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208098E+09 |
December | 0.607235E+09 | 0.388292E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241862E+09 |
Annual Sum or Average | 0.755252E+10 | 0.423701E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21890207.02 | 0.164650E+10 |
Minimum of Months | 0.570983E+09 | 0.316218E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16834808.84 |
Maximum of Months | 0.682256E+09 | 0.395748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9146801.12 | 0.275528E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.644240E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633181E+09 |
February | 0.901968E+09 | 0.540311E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566298E+09 |
March | 0.107774E+10 | 0.602357E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468383E+09 |
April | 0.956342E+09 | 0.512787E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238403.81 | 0.314581E+09 |
May | 0.103597E+10 | 0.541447E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1104729.01 | 0.189299E+09 |
June | 0.103308E+10 | 0.530653E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7799793.55 | 98981706.98 |
July | 0.959235E+09 | 0.499456E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18284229.05 | 35806153.37 |
August | 0.107774E+10 | 0.564589E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22275189.41 | 44861727.72 |
September | 0.956342E+09 | 0.523329E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2729459.71 | 0.104199E+09 |
October | 0.994195E+09 | 0.567235E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43189.84 | 0.258291E+09 |
November | 0.984487E+09 | 0.617019E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463992E+09 |
December | 0.959235E+09 | 0.636198E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543733E+09 |
Annual Sum or Average | 0.119305E+11 | 0.677962E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52474994.38 | 0.372161E+10 |
Minimum of Months | 0.901968E+09 | 0.499456E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35806153.37 |
Maximum of Months | 0.107774E+10 | 0.644240E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22275189.41 | 0.633181E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.402563E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423104E+09 |
February | 0.421807E+09 | 0.339439E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383920E+09 |
March | 0.502994E+09 | 0.380302E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319284E+09 |
April | 0.447140E+09 | 0.325197E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142996.14 | 0.217743E+09 |
May | 0.484071E+09 | 0.344962E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570555.45 | 0.130089E+09 |
June | 0.482240E+09 | 0.338406E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4803048.59 | 67885590.37 |
July | 0.448971E+09 | 0.318273E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11376668.20 | 25034631.11 |
August | 0.502994E+09 | 0.358756E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13912734.46 | 31434172.28 |
September | 0.447140E+09 | 0.330945E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1707491.57 | 73223427.58 |
October | 0.465148E+09 | 0.357658E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16313.53 | 0.178372E+09 |
November | 0.460569E+09 | 0.388458E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315535E+09 |
December | 0.448971E+09 | 0.394250E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366539E+09 |
Annual Sum or Average | 0.557719E+10 | 0.427921E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32529807.95 | 0.253216E+10 |
Minimum of Months | 0.421807E+09 | 0.318273E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25034631.11 |
Maximum of Months | 0.502994E+09 | 0.402563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13912734.46 | 0.423104E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.620049E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653841E+09 |
February | 0.901968E+09 | 0.526133E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599477E+09 |
March | 0.107774E+10 | 0.596133E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490600E+09 |
April | 0.956342E+09 | 0.513466E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238184.48 | 0.328129E+09 |
May | 0.103597E+10 | 0.543718E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 885595.99 | 0.192548E+09 |
June | 0.103308E+10 | 0.533868E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7520107.94 | 99998217.68 |
July | 0.959235E+09 | 0.502314E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17728016.16 | 37029111.06 |
August | 0.107774E+10 | 0.566536E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21369555.26 | 47339399.59 |
September | 0.956342E+09 | 0.521668E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2687594.79 | 0.111969E+09 |
October | 0.994195E+09 | 0.559325E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29053.65 | 0.279792E+09 |
November | 0.984487E+09 | 0.601635E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489236E+09 |
December | 0.959235E+09 | 0.605551E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574468E+09 |
Annual Sum or Average | 0.119305E+11 | 0.669039E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50458108.27 | 0.390443E+10 |
Minimum of Months | 0.901968E+09 | 0.502314E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37029111.06 |
Maximum of Months | 0.107774E+10 | 0.620049E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21369555.26 | 0.653841E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.397170E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424950E+09 |
February | 0.570983E+09 | 0.335319E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383375E+09 |
March | 0.682256E+09 | 0.377105E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322181E+09 |
April | 0.605404E+09 | 0.324690E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 158940.54 | 0.217780E+09 |
May | 0.655811E+09 | 0.341884E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 695380.11 | 0.130944E+09 |
June | 0.653980E+09 | 0.335903E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4963382.81 | 69924613.10 |
July | 0.607235E+09 | 0.316481E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11640801.22 | 27180770.80 |
August | 0.682256E+09 | 0.357096E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14195704.15 | 32733597.58 |
September | 0.605404E+09 | 0.330361E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1807442.93 | 73192968.83 |
October | 0.629366E+09 | 0.355388E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28812.86 | 0.179778E+09 |
November | 0.623221E+09 | 0.382829E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311777E+09 |
December | 0.607235E+09 | 0.389819E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366904E+09 |
Annual Sum or Average | 0.755252E+10 | 0.424404E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33490464.62 | 0.254072E+10 |
Minimum of Months | 0.570983E+09 | 0.316481E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27180770.80 |
Maximum of Months | 0.682256E+09 | 0.397170E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14195704.15 | 0.424950E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879122E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797740E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659433E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209566.90 | 0.441016E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183879.47 | 0.258550E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7892471.29 | 0.133656E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19459326.45 | 45243853.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23479561.36 | 60357193.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2284325.21 | 0.147964E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2372.76 | 0.370789E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668496E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782834E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54511503.44 | 0.524520E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45243853.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23479561.36 | 0.879122E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107401E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976651E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.812166E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271610.54 | 0.545165E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1472166.73 | 0.327587E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10088425.18 | 0.169989E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24856408.65 | 57809636.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30462382.79 | 76091578.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2970621.03 | 0.183121E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5440.12 | 0.456186E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802694E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939515E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70127055.03 | 0.642098E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57809636.35 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30462382.79 | 0.107401E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108095E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984019E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823193E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61750.66 | 0.558851E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571720.70 | 0.348553E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8399071.37 | 0.183121E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20656608.52 | 66037694.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27981270.51 | 76594153.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2553432.28 | 0.188779E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459603E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785060E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922843E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60223854.05 | 0.647761E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66037694.92 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27981270.51 | 0.108095E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1229.13 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 944.20 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1322.43 | 06-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 751.52 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 997.47 | 21-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 554.47 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 07-APR-13:00 | 792.62 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 553.83 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.25 | 29-MAY-11:53 | 462.38 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 540.92 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.36 | 19-JUN-21:03 | 282.47 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 536.99 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.95 | 09-JUL-13:52 | 136.87 | 02-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 563.49 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.11 | 04-AUG-21:03 | 178.19 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 666.11 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.13 | 14-SEP-14:00 | 236.03 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 825.61 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 | 25-OCT-11:00 | 659.01 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 998.73 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1313.58 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.87 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 157.11 | 1322.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 819.33 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 604.38 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 881.59 | 06-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 531.51 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 694.46 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 341.63 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 07-APR-13:00 | 527.89 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 351.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 29-MAY-11:53 | 309.29 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 19-JUN-21:03 | 188.37 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 09-JUL-13:52 | 97.23 | 02-JUL-18:30 |
August | 827.22 | 01-AUG-09:09 | 341.64 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.40 | 04-AUG-21:03 | 124.89 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 359.20 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 14-SEP-14:00 | 177.68 | 10-SEP-08:00 |
October | 827.22 | 02-OCT-09:09 | 527.10 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 25-OCT-11:00 | 486.37 | 08-OCT-08:20 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 666.38 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 883.61 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 104.40 | 883.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1273.24 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 938.14 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1322.54 | 06-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 674.69 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1040.16 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 551.23 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 07-APR-13:00 | 804.38 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 555.10 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 | 29-MAY-11:53 | 468.69 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 545.61 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.28 | 19-JUN-21:03 | 282.67 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 542.14 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.52 | 09-JUL-13:52 | 140.64 | 02-JUL-18:33 |
August | 1306.65 | 01-AUG-09:09 | 563.47 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.61 | 04-AUG-21:03 | 179.49 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 581.87 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.07 | 14-SEP-14:00 | 248.27 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 794.60 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 25-OCT-11:00 | 692.64 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1025.73 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1323.43 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.14 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.64 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 156.61 | 1323.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 821.55 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 589.25 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 881.59 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 469.58 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 670.26 | 21-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 362.38 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 07-APR-13:00 | 536.15 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 358.03 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 | 29-MAY-11:53 | 316.01 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 352.44 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 19-JUN-21:03 | 214.49 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 352.06 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 09-JUL-13:52 | 126.49 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 363.28 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.88 | 04-AUG-21:03 | 121.51 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 447.97 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.42 | 14-SEP-14:00 | 169.38 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 507.61 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 25-OCT-11:00 | 448.28 | 17-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 665.56 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 884.95 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 352.06 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.51 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 103.88 | 884.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 713.84 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 940.52 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 702.85 | 06-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 739.73 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 532.30 | 21-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 550.36 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 07-APR-13:00 | 443.54 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 549.67 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.62 | 29-MAY-12:10 | 251.14 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 536.13 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.24 | 19-JUN-21:03 | 151.28 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 532.02 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 09-JUL-13:52 | 71.22 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 559.80 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 | 04-AUG-21:03 | 101.91 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 583.18 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.65 | 14-SEP-14:00 | 138.14 | 17-SEP-10:00 |
October | 1306.65 | 02-OCT-09:09 | 817.37 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 | 25-OCT-11:00 | 401.37 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 600.71 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 740.85 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.22 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 | 740.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 481.55 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 602.69 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 498.93 | 05-FEB-08:40 |
March | 827.22 | 01-MAR-10:09 | 527.65 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 391.55 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 338.94 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 07-APR-13:00 | 303.28 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 348.95 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.13 | 29-MAY-12:06 | 176.24 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | 19-JUN-21:03 | 105.12 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.04 | 09-JUL-13:52 | 50.35 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 338.63 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 04-AUG-21:03 | 73.70 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 357.25 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 14-SEP-14:00 | 94.52 | 17-SEP-10:00 |
October | 827.22 | 02-OCT-09:09 | 523.04 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 25-OCT-11:00 | 296.90 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 408.44 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 498.49 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.35 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 | 498.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 26260.09 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 934.14 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 28737.45 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 584.21 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 21962.31 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 546.93 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1695.26 | 07-APR-17:00 | 15231.11 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 551.02 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.24 | 30-MAY-12:00 | 10756.82 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 541.10 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9150.27 | 19-JUN-11:02 | 7138.41 | 02-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 537.47 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7105.47 | 07-JUL-11:03 | 2596.71 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 559.77 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7329.31 | 24-AUG-16:05 | 4779.68 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 579.02 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4413.34 | 14-SEP-16:10 | 9821.47 | 11-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 784.77 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 657.51 | 25-OCT-11:10 | 13676.04 | 31-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 21590.13 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 22149.56 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 537.47 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.71 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9150.27 | 28737.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 482.13 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 586.98 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 471.48 | 06-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 463.79 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 361.42 | 21-MAR-21:10 |
April | 827.17 | 03-APR-09:09 | 360.76 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 07-APR-13:00 | 313.09 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 356.00 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.86 | 29-MAY-11:53 | 178.17 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 350.18 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.39 | 19-JUN-21:03 | 110.61 | 02-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 349.80 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.67 | 09-JUL-13:52 | 59.37 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 361.47 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 | 04-AUG-21:03 | 73.48 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 441.55 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 14-SEP-14:00 | 97.30 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 502.98 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 25-OCT-11:00 | 275.10 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.61 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 500.14 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 349.80 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.41 | 500.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1096.47 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 944.19 | 15-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1099.81 | 06-FEB-00:58 |
March | 1306.65 | 01-MAR-10:09 | 751.50 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 837.95 | 21-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 554.46 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 07-APR-13:00 | 706.27 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 553.82 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 29-MAY-12:00 | 413.83 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 540.91 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.33 | 19-JUN-21:03 | 243.39 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 536.98 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 09-JUL-13:52 | 114.72 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 563.48 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.47 | 04-AUG-21:03 | 160.06 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 666.07 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.88 | 14-SEP-14:00 | 211.69 | 17-SEP-10:00 |
October | 1306.65 | 02-OCT-09:09 | 825.59 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 25-OCT-11:00 | 596.25 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 903.57 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1087.62 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.72 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 131.47 | 1099.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 732.41 | 31-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 604.37 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 771.35 | 05-FEB-09:00 |
March | 805.43 | 01-MAR-08:09 | 531.50 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 633.12 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 341.62 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 07-APR-13:00 | 470.53 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 351.28 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 | 29-MAY-11:55 | 276.79 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 | 19-JUN-21:03 | 162.65 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.82 | 09-JUL-13:26 | 78.01 | 11-JUL-05:00 |
August | 805.43 | 01-AUG-07:10 | 341.63 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 04-AUG-21:03 | 112.00 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 359.20 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 14-SEP-14:10 | 142.90 | 10-SEP-07:50 |
October | 805.43 | 02-OCT-07:10 | 527.09 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 25-OCT-11:00 | 448.47 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 604.39 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 729.46 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 771.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1135.36 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 938.13 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1136.26 | 05-FEB-10:00 |
March | 1306.65 | 01-MAR-10:09 | 674.66 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 947.68 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 551.22 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 07-APR-13:00 | 715.68 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 555.09 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 | 29-MAY-11:55 | 418.97 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 545.60 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.26 | 19-JUN-21:03 | 243.70 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 542.13 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.55 | 09-JUL-13:50 | 113.03 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 563.46 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.04 | 04-AUG-21:03 | 161.15 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 581.86 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.83 | 14-SEP-14:00 | 219.85 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 794.58 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 25-OCT-11:00 | 643.00 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 928.56 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1150.23 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 542.13 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.03 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 131.04 | 1150.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 733.46 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 589.24 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 733.20 | 06-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 469.56 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 566.78 | 21-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 362.37 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 07-APR-13:00 | 476.94 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 358.03 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.46 | 29-MAY-12:00 | 282.13 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 352.44 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 | 19-JUN-21:03 | 176.65 | 03-JUN-19:00 |
July | 827.17 | 03-JUL-09:09 | 352.05 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.99 | 09-JUL-13:26 | 98.02 | 02-JUL-17:40 |
August | 827.17 | 01-AUG-09:09 | 363.28 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 04-AUG-21:03 | 109.05 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 447.95 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.59 | 14-SEP-14:00 | 144.94 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 507.59 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.23 | 25-OCT-11:00 | 400.01 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 602.90 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 734.24 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 352.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.02 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 734.24 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1581.55 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1565.31 | 06-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1158.85 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.69 | 07-APR-13:00 | 998.12 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.30 | 29-MAY-11:53 | 580.64 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.05 | 19-JUN-21:03 | 326.89 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.01 | 09-JUL-14:00 | 149.31 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 12-AUG-18:55 | 218.34 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.45 | 14-SEP-14:00 | 293.46 | 30-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 25-OCT-11:00 | 858.10 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1320.85 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1629.12 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 1629.12 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1941.42 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1900.50 | 06-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1451.30 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 07-APR-13:00 | 1260.66 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.11 | 29-MAY-12:00 | 728.84 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.90 | 19-JUN-21:03 | 418.52 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.09 | 09-JUL-13:52 | 190.09 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.76 | 12-AUG-19:00 | 274.53 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.35 | 14-SEP-14:00 | 364.63 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 25-OCT-11:00 | 1050.99 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1613.80 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1944.38 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.76 | 1944.38 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1873.92 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1885.75 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1511.50 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 | 08-APR-10:00 | 1194.04 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 | 30-MAY-13:00 | 695.31 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.04 | 19-JUN-21:03 | 412.53 | 03-JUN-18:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.43 | 07-JUL-22:00 | 247.30 | 02-JUL-18:33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.95 | 04-AUG-21:03 | 245.47 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 | 14-SEP-14:00 | 353.43 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 996.44 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1514.46 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1901.43 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.47 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.95 | 1901.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11522.87 | 27-JAN-16:30 | 12070.02 | 9872.03 | 27982.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12520.24 | 24-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19429.98 | 30-MAR-06:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37171.87 | 10-APR-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38477.86 | 31-MAY-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42078.18 | 19-JUN-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41737.61 | 25-JUL-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39530.03 | 01-AUG-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41334.96 | 01-SEP-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38374.05 | 16-OCT-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33391.69 | 03-NOV-06:02 | 6352.64 | 8226.80 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14189.31 | 21-DEC-16:10 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11522.87 | 0.00 | 846.94 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42078.18 | 12070.02 | 9872.03 | 50974.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 169.18 | 17-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 |
February | 501.96 | 18-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 |
March | 3065.84 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.03 |
April | 7491.27 | 07-APR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 0.00 |
May | 10992.83 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 0.00 |
June | 12110.44 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.46 | 0.00 |
July | 11305.41 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 | 0.00 |
August | 10846.89 | 01-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | 0.00 |
September | 9569.14 | 01-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 0.00 |
October | 6823.68 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
November | 2531.94 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.88 |
December | 914.17 | 17-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 169.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12110.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.27 | 359.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2084.51 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892.84 |
February | 1903.77 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.17 |
March | 1981.98 | 08-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.83 |
April | 2528.44 | 10-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.18 |
May | 5315.43 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 | 0.00 |
June | 5294.37 | 19-JUN-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.84 | 0.00 |
July | 5522.99 | 10-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.39 | 0.00 |
August | 5680.26 | 14-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 | 0.00 |
September | 5508.67 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 |
October | 3327.17 | 04-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
November | 1763.95 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.42 |
December | 1537.56 | 23-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1537.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5680.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.84 | 892.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1711.86 | 25-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.60 |
February | 2026.50 | 14-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.82 |
March | 2610.53 | 16-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.12 |
April | 2995.07 | 10-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.72 |
May | 5805.21 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 | 0.00 |
June | 6571.43 | 19-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 | 0.00 |
July | 6166.85 | 10-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 0.00 |
August | 5773.21 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 0.00 |
September | 6437.57 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 |
October | 4070.73 | 16-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.82 |
November | 1926.57 | 03-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 |
December | 2238.98 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1711.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6571.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.04 | 169.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6562.40 | 31-JAN-08:20 | 60350.08 | 49360.15 | 68083.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6206.43 | 24-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10302.86 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14408.19 | 10-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29732.86 | 31-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33039.64 | 19-JUN-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32910.52 | 25-JUL-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32892.65 | 14-AUG-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32959.60 | 05-SEP-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25778.90 | 16-OCT-06:01 | 10164.22 | 13162.88 | 24207.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11757.78 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6398.39 | 21-DEC-16:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6206.43 | 3176.32 | 1270.40 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33039.64 | 60350.08 | 49360.15 | 68083.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6200.03 | 14-JAN-17:02 | 1905.79 | 1645.29 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5929.08 | 24-FEB-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9958.99 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15147.83 | 10-APR-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31938.10 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35599.32 | 19-JUN-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32238.73 | 24-JUL-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33001.52 | 07-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32343.60 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15938.64 | 04-OCT-15:20 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10603.70 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5879.23 | 21-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5879.23 | 1905.79 | 1270.40 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35599.32 | 12070.02 | 9872.03 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1263.78 | 14-JAN-17:02 | 401.76 | 346.84 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.39 |
February | 1011.16 | 24-FEB-15:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.35 |
March | 1869.48 | 28-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.85 |
April | 4141.85 | 07-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 | 0.00 |
May | 8670.43 | 30-MAY-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
June | 9609.30 | 26-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.54 |
July | 10667.57 | 16-JUL-14:32 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 | 0.00 |
August | 11370.72 | 13-AUG-15:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 | 0.00 |
September | 6831.09 | 05-SEP-06:03 | 1071.35 | 733.39 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
October | 4237.95 | 04-OCT-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 0.00 |
November | 1665.10 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
December | 1005.53 | 20-DEC-14:10 | 1306.65 | 534.28 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1005.53 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11370.72 | 1306.65 | 733.39 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 58.88 | 337.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 949.78 | 31-JAN-09:20 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.87 |
February | 950.23 | 09-FEB-09:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.35 |
March | 3792.05 | 29-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.51 |
April | 6372.89 | 28-APR-08:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.04 |
May | 13905.17 | 28-MAY-08:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.81 |
June | 13495.49 | 04-JUN-09:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 |
July | 13396.40 | 02-JUL-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
August | 12869.15 | 13-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 0.00 |
September | 13228.12 | 04-SEP-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.01 |
October | 5592.22 | 05-OCT-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
November | 2177.73 | 03-NOV-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 |
December | 805.75 | 20-DEC-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 805.75 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13905.17 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 165.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6090.25 | 19-JAN-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.40 |
February | 6581.89 | 02-FEB-13:50 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.70 |
March | 9195.06 | 03-MAR-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.55 |
April | 10204.97 | 07-APR-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 |
May | 15809.46 | 28-MAY-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 |
June | 15210.02 | 04-JUN-14:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.46 |
July | 16161.70 | 04-JUL-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 | 0.00 |
August | 16365.57 | 13-AUG-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 0.00 |
September | 16787.45 | 04-SEP-12:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 |
October | 17240.59 | 15-OCT-12:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.43 |
November | 11058.80 | 02-NOV-13:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 |
December | 6376.71 | 21-DEC-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6090.25 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17240.59 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 61.88 | 233.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1304.47 | 19-JAN-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.61 |
February | 2181.19 | 24-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.22 |
March | 5637.81 | 29-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.09 |
April | 9103.78 | 09-APR-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 |
May | 12042.38 | 14-MAY-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.05 |
June | 14908.02 | 04-JUN-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.17 |
July | 14737.62 | 02-JUL-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.82 |
August | 14420.34 | 13-AUG-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
September | 14292.21 | 10-SEP-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 |
October | 12281.42 | 15-OCT-14:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.54 |
November | 3750.63 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.42 |
December | 1129.06 | 08-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1129.06 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14908.02 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 197.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1121.84 | 14-JAN-17:02 | 401.76 | 346.84 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.88 |
February | 983.34 | 24-FEB-14:10 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.82 |
March | 1283.00 | 28-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 |
April | 2351.89 | 10-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
May | 4645.46 | 30-MAY-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
June | 7516.16 | 26-JUN-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 |
July | 7511.53 | 17-JUL-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 |
August | 7369.34 | 14-AUG-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
September | 6746.44 | 05-SEP-06:03 | 1071.35 | 727.79 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
October | 3820.36 | 05-OCT-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
November | 1702.81 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 |
December | 1061.73 | 20-DEC-14:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 983.34 | 401.76 | 346.84 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7516.16 | 1306.65 | 727.79 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 179.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 875.99 | 31-JAN-09:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 |
February | 855.79 | 09-FEB-08:50 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 |
March | 2487.70 | 29-MAR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
April | 4358.94 | 28-APR-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 |
May | 10958.53 | 28-MAY-08:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 |
June | 11206.67 | 25-JUN-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 |
July | 10109.40 | 09-JUL-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 0.00 |
August | 9142.61 | 13-AUG-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 | 0.00 |
September | 11225.31 | 10-SEP-08:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.72 |
October | 5059.45 | 05-OCT-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
November | 2500.71 | 03-NOV-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
December | 854.13 | 20-DEC-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 854.13 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11225.31 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 99.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1668.87 | 19-JAN-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.51 |
February | 2652.15 | 25-FEB-13:10 | 267.84 | 165.44 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 |
March | 5911.60 | 03-MAR-13:20 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.01 |
April | 7128.03 | 07-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1295.86 | 0.00 |
May | 10778.66 | 30-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4031.24 | 0.00 |
June | 12347.95 | 19-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8352.81 | 0.00 |
July | 11763.78 | 07-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6717.23 | 0.00 |
August | 13094.98 | 20-AUG-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
September | 13885.58 | 10-SEP-13:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 |
October | 13544.82 | 15-OCT-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.83 |
November | 10315.01 | 06-NOV-13:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.12 |
December | 5750.72 | 17-DEC-12:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1668.87 | 200.88 | 82.72 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13885.58 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 8352.81 | 1730.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 936.44 | 20-JAN-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.21 |
February | 1381.59 | 22-FEB-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.32 |
March | 3611.01 | 27-MAR-16:50 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 |
April | 5714.93 | 10-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
May | 6968.43 | 30-MAY-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 0.00 |
June | 11379.15 | 04-JUN-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 |
July | 11218.71 | 02-JUL-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 |
August | 11162.49 | 13-AUG-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | 0.00 |
September | 12029.15 | 10-SEP-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 |
October | 8310.17 | 15-OCT-15:02 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.75 |
November | 3533.51 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
December | 1010.70 | 21-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 936.44 | 169.55 | 69.82 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12029.15 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 | 83.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1077.90 | 14-JAN-17:02 | 401.76 | 346.84 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.74 |
February | 1071.07 | 24-FEB-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.88 |
March | 1920.31 | 28-MAR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
April | 3685.36 | 10-APR-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 |
May | 8177.15 | 30-MAY-06:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
June | 8911.16 | 19-JUN-05:03 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 |
July | 9858.99 | 09-JUL-16:02 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
August | 8246.63 | 15-AUG-05:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 7983.07 | 01-SEP-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
October | 4073.82 | 05-OCT-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
November | 1997.18 | 03-NOV-14:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 |
December | 1094.97 | 20-DEC-14:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1071.07 | 401.76 | 165.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9858.99 | 1306.65 | 496.35 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 281.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 936.74 | 31-JAN-09:30 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 |
February | 1673.67 | 22-FEB-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 |
March | 6522.24 | 29-MAR-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.14 |
April | 6811.01 | 07-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
May | 12890.65 | 29-MAY-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 |
June | 13816.99 | 25-JUN-08:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.09 |
July | 14337.61 | 02-JUL-09:01 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.74 |
August | 12381.67 | 13-AUG-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 0.00 |
September | 13741.09 | 10-SEP-08:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.30 |
October | 6605.21 | 15-OCT-09:33 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.16 |
November | 5417.89 | 01-NOV-12:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.51 |
December | 1629.88 | 20-DEC-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 936.74 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14337.61 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 134.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6416.64 | 19-JAN-13:25 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.01 |
February | 7042.84 | 02-FEB-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 |
March | 9221.08 | 29-MAR-12:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.93 |
April | 9645.09 | 07-APR-12:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
May | 14754.16 | 29-MAY-11:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 | 0.00 |
June | 10803.26 | 19-JUN-05:02 | 803.52 | 267.81 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 |
July | 14636.22 | 09-JUL-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 | 0.00 |
August | 14825.59 | 20-AUG-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
September | 15966.82 | 10-SEP-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.62 |
October | 15691.04 | 15-OCT-12:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.83 |
November | 11360.51 | 02-NOV-12:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.86 |
December | 9828.05 | 17-DEC-12:53 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6416.64 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15966.82 | 2544.47 | 992.69 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 66.69 | 206.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1573.94 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 |
February | 2569.67 | 24-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.11 |
March | 5682.56 | 29-MAR-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 |
April | 13208.72 | 09-APR-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 |
May | 11787.63 | 29-MAY-14:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 |
June | 13510.50 | 18-JUN-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
July | 14255.44 | 02-JUL-17:01 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
August | 13174.20 | 13-AUG-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 0.00 |
September | 14332.57 | 10-SEP-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.69 |
October | 11955.05 | 15-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 |
November | 3923.50 | 03-NOV-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
December | 1446.04 | 08-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1446.04 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14332.57 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 | 124.67 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.980150E+11 | 81891.74 | 02-JAN-16:00 | 0.105024E+12 | 254141.50 | 02-JAN-07:19 |
February | 0.876441E+11 | 74789.15 | 15-FEB-16:00 | 0.898746E+11 | 239921.86 | 06-FEB-07:19 |
March | 0.100067E+12 | 87557.84 | 27-MAR-15:00 | 0.429827E+11 | 155041.54 | 20-MAR-06:10 |
April | 0.957132E+11 | 111258.51 | 07-APR-14:30 | 0.117950E+11 | 113365.11 | 03-APR-06:10 |
May | 0.111025E+12 | 153679.58 | 30-MAY-14:09 | 0.717645E+09 | 36140.29 | 01-MAY-06:10 |
June | 0.139729E+12 | 164976.42 | 19-JUN-10:50 | 3419693.85 | 621.61 | 02-JUN-06:10 |
July | 0.156692E+12 | 156280.39 | 07-JUL-14:39 | 4940812.69 | 12.80 | 21-JUL-12:50 |
August | 0.165441E+12 | 158779.78 | 16-AUG-15:09 | 5039548.53 | 13.84 | 31-AUG-08:39 |
September | 0.124074E+12 | 138353.67 | 05-SEP-15:20 | 17758062.44 | 4361.50 | 20-SEP-06:10 |
October | 0.110877E+12 | 117767.11 | 04-OCT-15:30 | 0.176795E+10 | 54405.84 | 28-OCT-06:10 |
November | 0.954545E+11 | 85533.95 | 06-NOV-16:00 | 0.320034E+11 | 183217.37 | 24-NOV-07:10 |
December | 0.958433E+11 | 81666.32 | 21-DEC-16:30 | 0.716710E+11 | 164849.39 | 11-DEC-07:10 |
Annual Sum or Average | 0.138058E+13 | 0.355868E+12 | ||||
Minimum of Months | 0.876441E+11 | 74789.15 | 3419693.85 | 12.80 | ||
Maximum of Months | 0.165441E+12 | 164976.42 | 0.105024E+12 | 254141.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.200980E+11 | 0.583101E+10 | 0.605851E+11 | 0.225727E+10 | 0.373684E+10 | 0.538335E+09 | 0.00 | 292019.88 | 0.00 | 0.00 | 0.00 | 0.496805E+10 | 0.00 |
February | 0.178406E+11 | 0.466989E+10 | 0.548702E+11 | 0.204811E+10 | 0.319320E+10 | 0.470816E+09 | 0.00 | 66320.38 | 0.00 | 0.00 | 0.00 | 0.455126E+10 | 0.00 |
March | 0.208805E+11 | 0.435457E+10 | 0.627783E+11 | 0.235489E+10 | 0.387550E+10 | 0.230441E+09 | 0.00 | 0.340359E+09 | 0.00 | 0.00 | 0.00 | 0.525238E+10 | 0.00 |
April | 0.184198E+11 | 0.349082E+10 | 0.586172E+11 | 0.219173E+10 | 0.489512E+10 | 70568627.58 | 0.00 | 0.351460E+10 | 0.00 | 0.00 | 0.00 | 0.451332E+10 | 0.00 |
May | 0.197790E+11 | 0.313503E+10 | 0.616817E+11 | 0.230564E+10 | 0.807886E+10 | 18147478.13 | 0.00 | 0.115067E+11 | 0.00 | 0.00 | 0.00 | 0.452027E+10 | 0.00 |
June | 0.196162E+11 | 0.283034E+10 | 0.604966E+11 | 0.226784E+10 | 0.132899E+11 | 12256278.24 | 0.00 | 0.370352E+11 | 0.00 | 0.00 | 0.00 | 0.418105E+10 | 0.00 |
July | 0.183642E+11 | 0.300505E+10 | 0.597911E+11 | 0.222863E+10 | 0.165176E+11 | 12288472.19 | 0.00 | 0.530064E+11 | 0.00 | 0.00 | 0.00 | 0.376686E+10 | 0.00 |
August | 0.205553E+11 | 0.336878E+10 | 0.627783E+11 | 0.235457E+10 | 0.180769E+11 | 12705882.03 | 0.00 | 0.542054E+11 | 0.00 | 0.00 | 0.00 | 0.408941E+10 | 0.00 |
September | 0.185096E+11 | 0.386937E+10 | 0.585950E+11 | 0.219055E+10 | 0.106658E+11 | 12060147.57 | 0.00 | 0.264271E+11 | 0.00 | 0.00 | 0.00 | 0.380414E+10 | 0.00 |
October | 0.194288E+11 | 0.483138E+10 | 0.605962E+11 | 0.225782E+10 | 0.779143E+10 | 21853353.24 | 0.00 | 0.117810E+11 | 0.00 | 0.00 | 0.00 | 0.416817E+10 | 0.00 |
November | 0.197204E+11 | 0.542578E+10 | 0.591197E+11 | 0.219990E+10 | 0.374679E+10 | 0.169870E+09 | 0.00 | 0.676716E+09 | 0.00 | 0.00 | 0.00 | 0.439532E+10 | 0.00 |
December | 0.195263E+11 | 0.601184E+10 | 0.597800E+11 | 0.222855E+10 | 0.328820E+10 | 0.368562E+09 | 0.00 | 33918.08 | 0.00 | 0.00 | 0.00 | 0.463979E+10 | 0.00 |
Annual Sum or Average | 0.232739E+12 | 0.508239E+11 | 0.719689E+12 | 0.268855E+11 | 0.971561E+11 | 0.193790E+10 | 0.00 | 0.198494E+12 | 0.00 | 0.00 | 0.00 | 0.528500E+11 | 0.00 |
Minimum of Months | 0.178406E+11 | 0.283034E+10 | 0.548702E+11 | 0.204811E+10 | 0.319320E+10 | 12060147.57 | 0.00 | 33918.08 | 0.00 | 0.00 | 0.00 | 0.376686E+10 | 0.00 |
Maximum of Months | 0.208805E+11 | 0.601184E+10 | 0.627783E+11 | 0.235489E+10 | 0.180769E+11 | 0.538335E+09 | 0.00 | 0.542054E+11 | 0.00 | 0.00 | 0.00 | 0.525238E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.105024E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.898746E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.429827E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.717645E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3419693.85 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4940812.69 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 5039548.53 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 17758062.44 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.176795E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.320034E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.716710E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.355868E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3419693.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.105024E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:40 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:20 | 7034.72 | 02-JAN-06:19 | 793.27 | 02-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 24009.70 | 15-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 02-FEB-17:10 | 6094.16 | 06-FEB-07:10 | 756.03 | 06-FEB-07:10 | 0.00 | 01-FEB-00:10 |
March | 21339.46 | 02-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-08:09 | 6290.49 | 29-MAR-15:20 | 621.83 | 20-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 20132.52 | 21-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-11:09 | 15135.18 | 10-APR-14:30 | 529.18 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 20181.62 | 08-MAY-07:10 | 3328.83 | 01-MAY-18:49 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-16:10 | 28910.06 | 30-MAY-14:39 | 242.96 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 20056.07 | 29-JUN-07:10 | 3328.83 | 01-JUN-19:19 | 41699.26 | 01-JUN-07:10 | 1410.29 | 19-JUN-12:09 | 27668.40 | 19-JUN-10:30 | 11.49 | 02-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 20032.37 | 24-JUL-07:10 | 3328.83 | 01-JUL-19:30 | 41699.26 | 03-JUL-07:10 | 1410.29 | 07-JUL-11:09 | 28001.63 | 17-JUL-14:30 | 6.93 | 05-JUL-11:50 | 0.00 | 01-JUL-00:10 |
August | 20291.44 | 16-AUG-07:10 | 5686.19 | 16-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-12:09 | 27375.06 | 14-AUG-15:39 | 6.93 | 10-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 20877.95 | 27-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 11-SEP-07:10 | 23471.32 | 05-SEP-15:30 | 30.57 | 20-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 22695.91 | 31-OCT-15:00 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 06-OCT-12:09 | 16872.23 | 04-OCT-15:50 | 256.52 | 31-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 06-NOV-16:49 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-12:09 | 8052.98 | 03-NOV-14:30 | 658.85 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-16:30 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-08:09 | 4698.75 | 11-DEC-07:10 | 630.83 | 11-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20032.37 | 3328.83 | 41699.26 | 1410.29 | 4698.75 | 6.93 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 28910.06 | 793.27 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 330.55 | 03-JAN-07:30 | 0.00 | 0.00 | 0.00 | 6685.10 | 31-JAN-12:39 | 0.00 |
February | 31.17 | 12-FEB-09:00 | 0.00 | 0.00 | 0.00 | 6688.41 | 06-FEB-12:50 | 0.00 |
March | 15089.99 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6672.98 | 01-MAR-12:30 | 0.00 |
April | 31211.97 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 6264.98 | 03-APR-11:20 | 0.00 |
May | 60577.33 | 30-MAY-14:09 | 0.00 | 0.00 | 0.00 | 5957.22 | 02-MAY-11:20 | 0.00 |
June | 75124.01 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 5527.67 | 02-JUN-11:39 | 0.00 |
July | 65342.91 | 07-JUL-14:09 | 0.00 | 0.00 | 0.00 | 5279.11 | 03-JUL-11:00 | 0.00 |
August | 69163.72 | 04-AUG-14:09 | 0.00 | 0.00 | 0.00 | 5003.76 | 31-AUG-11:20 | 0.00 |
September | 54742.34 | 07-SEP-14:09 | 0.00 | 0.00 | 0.00 | 5364.93 | 28-SEP-11:20 | 0.00 |
October | 39183.20 | 04-OCT-14:09 | 0.00 | 0.00 | 0.00 | 5779.08 | 31-OCT-11:50 | 0.00 |
November | 7186.75 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6204.80 | 29-NOV-12:20 | 0.00 |
December | 32.37 | 31-DEC-09:50 | 0.00 | 0.00 | 0.00 | 6525.10 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31.17 | 0.00 | 0.00 | 0.00 | 5003.76 | 0.00 | ||
Maximum of Months | 75124.01 | 0.00 | 0.00 | 0.00 | 6688.41 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 81891.74 | 02-JAN-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2501.57 | 619.64 | 0.00 | 0.00 | 0.00 |
February | 74789.15 | 15-FEB-16:00 | 24009.70 | 41670.51 | 0.00 | 1410.29 | 2287.49 | 293.54 | 0.00 | 0.00 | 0.00 |
March | 87557.84 | 27-MAR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 4755.05 | 6.85 | 0.00 | 15089.99 | 0.00 |
April | 111258.51 | 07-APR-14:30 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 13744.67 | 6.85 | 0.00 | 31211.97 | 0.00 |
May | 153679.58 | 30-MAY-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 27146.85 | 6.85 | 0.00 | 60577.33 | 0.00 |
June | 164976.42 | 19-JUN-10:50 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 26169.81 | 6.90 | 0.00 | 71586.47 | 0.00 |
July | 156280.39 | 07-JUL-14:39 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 25631.92 | 6.91 | 0.00 | 64730.29 | 0.00 |
August | 158779.78 | 16-AUG-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 24930.03 | 6.92 | 0.00 | 67223.13 | 0.00 |
September | 138353.67 | 05-SEP-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 22845.47 | 6.90 | 0.00 | 48858.55 | 0.00 |
October | 117767.11 | 04-OCT-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 15285.24 | 6.91 | 0.00 | 35499.96 | 0.00 |
November | 85533.95 | 06-NOV-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 3897.21 | 6.85 | 0.00 | 3274.49 | 0.00 |
December | 81666.32 | 21-DEC-16:30 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2728.48 | 187.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 74789.15 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 2287.49 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 164976.42 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 27146.85 | 619.64 | 0.00 | 71586.47 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 254141.50 | 02-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 239921.86 | 06-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 155041.54 | 20-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 113365.11 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 36140.29 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 621.61 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 12.80 | 21-JUL-12:50 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 13.84 | 31-AUG-08:39 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 4361.50 | 20-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 54405.84 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 183217.37 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 164849.39 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 12.80 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 254141.50 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.40 | 2.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.79 | 0.17 | 26.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 19.40 | 2.83 | 19.40 | 0.33 | 19.81 | 0.17 | 20.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.40 | 2.83 | 19.40 | 0.33 | 26.79 | 0.17 | 26.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 19.09 | 4.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.17 | 19.09 | 4.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.09 | 4.50 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 18.77 | 5.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 2.83 | 19.45 | 2.67 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.18 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 0.17 | 19.16 | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Annual Sum or Average | 9.67 | 18.99 | 8.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 19.45 | 5.33 | 19.52 | 0.00 | 19.52 | 0.00 | 19.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 16.97 | 15.33 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
February | 19.33 | 17.83 | 12.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
March | 0.83 | 18.50 | 0.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 0.17 | 19.38 | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.83 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.40 | 4.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.49 | 1.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.50 | 18.08 | 1.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
December | 3.67 | 17.59 | 2.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
Annual Sum or Average | 51.50 | 17.42 | 31.33 | 17.93 | 7.00 | 18.67 | 6.33 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.00 | 19.38 | 15.33 | 19.38 | 4.50 | 27.49 | 4.17 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.33 | 15.97 | 6.00 | 16.38 | 0.00 | 16.38 | 0.00 | 16.38 |
February | 10.83 | 16.68 | 3.67 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
March | 0.67 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.83 | 7.33 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.64 | 5.67 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.82 | 12.67 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 7.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.85 | 6.33 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
November | 1.17 | 17.38 | 0.33 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
December | 2.17 | 16.03 | 0.50 | 16.34 | 0.00 | 16.34 | 0.00 | 16.34 |
Annual Sum or Average | 31.17 | 16.30 | 10.50 | 16.78 | 40.50 | 22.21 | 39.50 | 24.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.33 | 17.38 | 6.00 | 17.81 | 13.33 | 27.85 | 12.67 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 16.49 | 6.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
February | 8.67 | 17.53 | 4.50 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.71 | 4.00 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.52 | 4.00 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.73 | 9.00 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.97 | 5.17 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.18 | 5.83 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.72 | 4.17 | 27.72 |
November | 0.67 | 18.16 | 0.33 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
December | 1.00 | 16.69 | 0.33 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
Annual Sum or Average | 25.33 | 16.90 | 11.67 | 17.47 | 34.33 | 22.45 | 32.50 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.00 | 18.16 | 6.50 | 18.54 | 9.67 | 28.18 | 9.00 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.67 | 16.06 | 7.67 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
February | 12.17 | 17.23 | 5.50 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
March | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.64 | 1.33 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.80 | 4.33 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.09 | 3.67 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.04 | 7.50 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.03 | 3.83 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.24 | 3.17 | 28.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.79 | 0.67 | 27.79 |
November | 1.00 | 17.79 | 0.33 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
December | 1.83 | 16.04 | 0.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
Annual Sum or Average | 31.83 | 16.57 | 14.00 | 17.05 | 34.83 | 21.78 | 24.50 | 23.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 0.00 | 16.41 |
Maximum of Months | 16.67 | 17.79 | 7.67 | 18.18 | 10.83 | 28.24 | 7.50 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 18.14 | 15.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
February | 6.67 | 19.47 | 6.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.83 | 18.47 | 21.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 19.47 | 15.00 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.17 | 16.42 | 3.33 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
February | 1.00 | 19.36 | 0.83 | 19.59 | 0.00 | 19.59 | 0.00 | 19.59 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.57 | 3.83 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.66 | 6.33 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.58 | 4.83 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.66 | 5.83 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9.17 | 16.74 | 4.17 | 17.35 | 22.67 | 23.82 | 22.67 | 25.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.17 | 19.36 | 3.33 | 19.59 | 6.33 | 27.66 | 6.33 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.83 | 17.80 | 80.67 | 17.83 | 0.00 | 17.83 | 0.00 | 17.83 |
February | 67.17 | 17.61 | 67.17 | 17.61 | 0.00 | 17.61 | 0.00 | 17.61 |
March | 48.83 | 18.61 | 48.83 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
April | 20.33 | 19.31 | 20.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 1.67 | 20.04 | 1.67 | 20.04 | 0.67 | 21.27 | 0.67 | 22.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.69 | 1.00 | 25.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.26 | 6.67 | 26.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 25.74 | 13.00 | 25.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.54 | 10.17 | 26.53 |
October | 3.17 | 20.26 | 3.17 | 20.26 | 5.83 | 23.78 | 5.83 | 25.01 |
November | 31.33 | 19.07 | 31.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 54.50 | 18.38 | 54.50 | 18.38 | 0.17 | 18.39 | 0.17 | 18.41 |
Annual Sum or Average | 309.83 | 18.25 | 307.67 | 18.26 | 38.00 | 18.73 | 37.50 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 | 17.61 |
Maximum of Months | 82.83 | 20.26 | 80.67 | 20.26 | 13.17 | 26.54 | 13.00 | 26.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 16.87 | 5.33 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
February | 2.50 | 19.51 | 2.17 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.54 | 0.17 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.43 | 2.17 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.68 | 2.83 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.72 | 4.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.80 | 2.67 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 3.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12.67 | 17.39 | 7.50 | 17.97 | 21.67 | 23.02 | 16.33 | 24.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 19.51 | 5.33 | 19.69 | 7.00 | 27.86 | 4.83 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.00 | 17.03 | 8.67 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
February | 6.50 | 19.14 | 5.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.16 | 0.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
December | 0.17 | 19.37 | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 20.83 | 17.72 | 14.50 | 18.17 | 1.00 | 18.42 | 1.00 | 18.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.00 | 19.37 | 8.67 | 19.37 | 1.00 | 27.31 | 1.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 16.23 | 3.67 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
February | 1.50 | 17.79 | 0.67 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.50 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.84 | 6.50 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.67 | 4.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.74 | 11.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.73 | 6.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.85 | 6.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.38 | 0.67 | 27.38 |
November | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.50 | 16.50 | 4.50 | 17.01 | 35.67 | 24.58 | 35.33 | 25.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 19.40 | 3.67 | 19.40 | 11.50 | 27.85 | 11.33 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.00 | 16.37 | 3.17 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
February | 2.33 | 18.63 | 1.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.58 | 3.17 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.41 | 2.67 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.61 | 7.33 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.84 | 5.00 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.51 | 7.67 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.73 | 5.67 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
Annual Sum or Average | 10.33 | 16.88 | 4.67 | 17.50 | 33.00 | 24.46 | 32.50 | 25.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.00 | 18.63 | 3.17 | 19.05 | 7.83 | 27.84 | 7.67 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 16.66 | 5.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
February | 3.33 | 18.81 | 2.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.50 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.69 | 4.00 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.97 | 3.17 | 28.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.94 | 6.00 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.99 | 3.17 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.11 | 3.17 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.67 | 0.83 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 14.00 | 17.17 | 7.67 | 17.73 | 30.67 | 23.69 | 21.83 | 24.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 18.81 | 5.33 | 19.27 | 9.17 | 28.11 | 6.00 | 28.14 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.83 | 22.85 | 42.50 | 22.62 | 42.50 | 22.41 |
February | 454.00 | 23.52 | 0.00 | 23.52 | 0.00 | 23.52 |
March | 397.50 | 23.96 | 9.33 | 23.97 | 0.00 | 23.97 |
April | 153.50 | 24.03 | 75.83 | 24.43 | 0.00 | 24.43 |
May | 16.50 | 24.00 | 268.67 | 24.64 | 0.00 | 24.64 |
June | 0.00 | 0.00 | 447.33 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 497.00 | 24.51 | 0.00 | 24.51 |
August | 0.00 | 0.00 | 485.17 | 24.49 | 0.00 | 24.49 |
September | 0.00 | 0.00 | 405.67 | 24.59 | 0.00 | 24.59 |
October | 38.00 | 24.01 | 303.67 | 24.55 | 0.00 | 24.55 |
November | 251.00 | 23.89 | 77.50 | 24.22 | 0.00 | 24.22 |
December | 494.83 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
Annual Sum or Average | 2304.17 | 23.59 | 2612.67 | 24.08 | 42.50 | 24.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.62 | 0.00 | 22.41 |
Maximum of Months | 498.83 | 24.03 | 497.00 | 24.64 | 42.50 | 24.64 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.26 | 180.50 | 21.00 | 180.50 | 20.84 |
February | 454.00 | 21.73 | 108.67 | 21.57 | 108.67 | 21.46 |
March | 507.00 | 22.84 | 2.17 | 22.83 | 2.17 | 22.83 |
April | 352.17 | 23.25 | 19.67 | 23.32 | 0.00 | 23.32 |
May | 111.50 | 23.72 | 165.33 | 24.08 | 0.00 | 24.08 |
June | 0.00 | 0.00 | 417.83 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 497.00 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 466.17 | 24.35 | 0.00 | 24.35 |
September | 26.50 | 23.77 | 331.00 | 24.34 | 0.00 | 24.34 |
October | 167.67 | 23.76 | 212.17 | 24.05 | 0.00 | 24.05 |
November | 430.33 | 22.78 | 28.67 | 22.69 | 23.83 | 22.60 |
December | 497.00 | 21.93 | 44.83 | 21.83 | 44.83 | 21.73 |
Annual Sum or Average | 3048.17 | 22.40 | 2474.00 | 23.02 | 360.00 | 22.87 |
Minimum of Months | 0.00 | 0.00 | 2.17 | 21.00 | 0.00 | 20.84 |
Maximum of Months | 507.00 | 23.77 | 497.00 | 24.35 | 180.50 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.63 | 312.17 | 20.42 | 312.17 | 20.33 |
February | 454.00 | 20.98 | 287.67 | 20.80 | 287.67 | 20.73 |
March | 510.17 | 22.09 | 61.33 | 21.92 | 61.33 | 21.79 |
April | 382.50 | 22.70 | 30.00 | 22.69 | 13.50 | 22.62 |
May | 163.50 | 23.48 | 136.17 | 23.84 | 0.00 | 23.84 |
June | 9.83 | 23.72 | 407.17 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 491.83 | 24.37 | 0.00 | 24.37 |
August | 1.33 | 23.74 | 447.17 | 24.36 | 0.00 | 24.36 |
September | 67.83 | 23.47 | 289.83 | 24.16 | 0.00 | 24.16 |
October | 260.00 | 23.21 | 146.50 | 23.54 | 0.00 | 23.54 |
November | 471.83 | 21.99 | 102.67 | 21.72 | 101.17 | 21.52 |
December | 497.00 | 21.02 | 276.50 | 20.81 | 276.50 | 20.71 |
Annual Sum or Average | 3320.00 | 21.80 | 2989.00 | 22.34 | 1052.33 | 22.05 |
Minimum of Months | 0.00 | 0.00 | 30.00 | 20.42 | 0.00 | 20.33 |
Maximum of Months | 510.17 | 23.74 | 491.83 | 24.37 | 312.17 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 441.50 | 19.90 | 441.50 | 19.88 |
February | 454.00 | 20.15 | 414.83 | 20.10 | 414.83 | 20.09 |
March | 511.00 | 21.10 | 235.50 | 20.85 | 235.50 | 20.72 |
April | 406.33 | 21.93 | 94.00 | 21.82 | 68.00 | 21.62 |
May | 217.17 | 23.12 | 141.00 | 23.61 | 7.50 | 23.63 |
June | 32.33 | 24.66 | 416.33 | 24.35 | 15.50 | 24.40 |
July | 50.83 | 26.15 | 496.50 | 24.66 | 50.83 | 24.79 |
August | 33.67 | 25.51 | 451.33 | 24.48 | 24.17 | 24.56 |
September | 130.00 | 23.28 | 261.17 | 23.96 | 6.33 | 23.98 |
October | 326.00 | 22.39 | 135.50 | 22.61 | 33.67 | 22.46 |
November | 489.00 | 21.05 | 218.67 | 20.75 | 218.67 | 20.59 |
December | 497.00 | 20.18 | 460.83 | 20.14 | 460.83 | 20.13 |
Annual Sum or Average | 3649.33 | 21.24 | 3767.17 | 21.74 | 1977.33 | 21.45 |
Minimum of Months | 32.33 | 19.97 | 94.00 | 19.90 | 6.33 | 19.88 |
Maximum of Months | 511.00 | 26.15 | 496.50 | 24.66 | 460.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 401.67 | 19.94 | 401.67 | 19.89 |
February | 454.00 | 20.45 | 351.50 | 20.30 | 351.50 | 20.24 |
March | 486.83 | 21.52 | 160.33 | 21.17 | 160.33 | 20.96 |
April | 335.83 | 22.13 | 121.83 | 22.39 | 41.67 | 22.21 |
May | 176.50 | 23.57 | 235.83 | 24.13 | 30.50 | 24.26 |
June | 40.00 | 26.01 | 450.50 | 24.53 | 32.67 | 24.65 |
July | 78.33 | 26.57 | 496.50 | 24.86 | 78.33 | 25.07 |
August | 46.50 | 26.50 | 482.00 | 24.63 | 44.17 | 24.79 |
September | 112.33 | 24.13 | 333.67 | 24.37 | 29.83 | 24.51 |
October | 248.17 | 22.69 | 183.00 | 23.16 | 21.17 | 23.05 |
November | 465.00 | 21.31 | 177.33 | 20.96 | 175.67 | 20.75 |
December | 497.00 | 20.38 | 384.17 | 20.24 | 384.17 | 20.19 |
Annual Sum or Average | 3442.50 | 21.55 | 3778.33 | 22.13 | 1751.67 | 21.87 |
Minimum of Months | 40.00 | 20.08 | 121.83 | 19.94 | 21.17 | 19.89 |
Maximum of Months | 502.00 | 26.57 | 496.50 | 24.86 | 401.67 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.33 | 20.57 | 323.17 | 20.23 | 323.17 | 20.08 |
February | 424.00 | 21.02 | 278.50 | 20.72 | 274.17 | 20.56 |
March | 419.50 | 21.46 | 181.33 | 21.30 | 150.33 | 21.09 |
April | 334.33 | 22.00 | 127.83 | 22.23 | 52.33 | 22.04 |
May | 205.00 | 23.22 | 201.50 | 23.81 | 19.83 | 23.89 |
June | 46.17 | 24.92 | 424.67 | 24.40 | 24.17 | 24.49 |
July | 65.17 | 26.36 | 493.67 | 24.74 | 65.17 | 24.91 |
August | 46.50 | 26.10 | 467.67 | 24.60 | 38.50 | 24.74 |
September | 104.50 | 24.13 | 341.67 | 24.36 | 28.33 | 24.51 |
October | 193.00 | 22.83 | 266.50 | 23.62 | 28.00 | 23.58 |
November | 401.17 | 21.50 | 171.50 | 21.31 | 138.17 | 21.07 |
December | 459.17 | 20.92 | 308.00 | 20.66 | 300.17 | 20.50 |
Annual Sum or Average | 3185.83 | 21.75 | 3586.00 | 22.36 | 1442.33 | 22.10 |
Minimum of Months | 46.17 | 20.57 | 127.83 | 20.23 | 19.83 | 20.08 |
Maximum of Months | 487.33 | 26.36 | 493.67 | 24.74 | 323.17 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 392.67 | 20.01 | 392.67 | 19.94 |
February | 453.50 | 20.50 | 352.50 | 20.30 | 352.50 | 20.22 |
March | 457.17 | 21.29 | 204.67 | 21.07 | 192.00 | 20.90 |
April | 357.00 | 21.98 | 123.67 | 22.11 | 60.50 | 21.92 |
May | 201.00 | 23.42 | 219.83 | 23.93 | 31.67 | 24.05 |
June | 45.33 | 25.33 | 437.67 | 24.48 | 29.33 | 24.58 |
July | 68.83 | 26.43 | 495.83 | 24.80 | 68.83 | 24.97 |
August | 45.33 | 26.10 | 472.67 | 24.61 | 38.33 | 24.74 |
September | 113.00 | 23.73 | 312.33 | 24.20 | 21.50 | 24.31 |
October | 257.50 | 22.47 | 206.33 | 23.01 | 34.17 | 22.88 |
November | 463.50 | 21.11 | 202.00 | 20.80 | 200.67 | 20.63 |
December | 497.00 | 20.42 | 402.00 | 20.27 | 402.00 | 20.22 |
Annual Sum or Average | 3461.17 | 21.46 | 3822.17 | 22.04 | 1824.17 | 21.77 |
Minimum of Months | 45.33 | 20.18 | 123.67 | 20.01 | 21.50 | 19.94 |
Maximum of Months | 502.00 | 26.43 | 495.83 | 24.80 | 402.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 417.50 | 20.22 | 417.50 | 20.20 |
February | 454.00 | 20.48 | 411.50 | 20.45 | 411.50 | 20.44 |
March | 514.00 | 21.15 | 215.67 | 20.99 | 215.67 | 20.91 |
April | 456.50 | 22.08 | 35.83 | 21.99 | 33.00 | 21.89 |
May | 321.83 | 23.20 | 76.83 | 23.39 | 11.00 | 23.40 |
June | 20.50 | 24.30 | 397.17 | 24.25 | 6.33 | 24.27 |
July | 14.00 | 25.75 | 496.67 | 24.45 | 14.00 | 24.48 |
August | 12.83 | 26.12 | 468.00 | 24.40 | 12.50 | 24.44 |
September | 75.00 | 23.60 | 308.67 | 24.16 | 0.50 | 24.16 |
October | 257.33 | 23.16 | 152.33 | 23.50 | 0.00 | 23.50 |
November | 482.00 | 21.89 | 113.67 | 21.63 | 113.00 | 21.46 |
December | 497.00 | 20.70 | 383.50 | 20.63 | 383.50 | 20.61 |
Annual Sum or Average | 3607.00 | 21.53 | 3477.33 | 22.03 | 1618.50 | 21.75 |
Minimum of Months | 12.83 | 20.29 | 35.83 | 20.22 | 0.00 | 20.20 |
Maximum of Months | 514.00 | 26.12 | 496.67 | 24.45 | 417.50 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 369.83 | 20.32 | 369.83 | 20.26 |
February | 454.00 | 20.83 | 312.33 | 20.69 | 312.33 | 20.62 |
March | 508.50 | 21.83 | 96.17 | 21.61 | 96.17 | 21.45 |
April | 353.50 | 22.46 | 63.00 | 22.69 | 9.83 | 22.63 |
May | 197.33 | 23.36 | 189.83 | 23.97 | 18.00 | 24.01 |
June | 13.33 | 26.18 | 457.67 | 24.43 | 11.67 | 24.48 |
July | 42.83 | 26.62 | 497.00 | 24.73 | 42.83 | 24.87 |
August | 30.33 | 26.71 | 501.50 | 24.60 | 30.33 | 24.71 |
September | 50.17 | 24.96 | 389.50 | 24.54 | 20.17 | 24.64 |
October | 147.83 | 23.50 | 239.83 | 23.99 | 0.83 | 23.99 |
November | 414.17 | 22.11 | 75.50 | 21.94 | 67.33 | 21.77 |
December | 497.00 | 21.07 | 246.67 | 20.87 | 246.67 | 20.77 |
Annual Sum or Average | 3211.00 | 21.81 | 3438.83 | 22.50 | 1226.00 | 22.27 |
Minimum of Months | 13.33 | 20.46 | 63.00 | 20.32 | 0.83 | 20.26 |
Maximum of Months | 508.50 | 26.71 | 501.50 | 24.73 | 369.83 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 20.22 | 322.17 | 19.94 | 322.17 | 19.82 |
February | 444.67 | 20.68 | 269.00 | 20.41 | 263.33 | 20.25 |
March | 478.83 | 21.34 | 117.67 | 21.07 | 111.17 | 20.86 |
April | 390.33 | 21.84 | 76.17 | 21.94 | 34.50 | 21.79 |
May | 314.17 | 22.71 | 99.33 | 23.14 | 16.67 | 23.14 |
June | 96.00 | 23.76 | 404.67 | 24.19 | 71.67 | 24.16 |
July | 98.67 | 24.64 | 494.83 | 24.52 | 98.67 | 24.54 |
August | 63.50 | 25.19 | 491.33 | 24.56 | 60.67 | 24.64 |
September | 94.50 | 24.18 | 392.67 | 24.47 | 50.67 | 24.54 |
October | 125.33 | 23.33 | 318.50 | 24.22 | 16.67 | 24.29 |
November | 382.67 | 21.72 | 99.67 | 21.73 | 57.67 | 21.53 |
December | 469.50 | 21.00 | 234.17 | 20.80 | 222.67 | 20.62 |
Annual Sum or Average | 3457.50 | 21.65 | 3320.17 | 22.34 | 1326.50 | 22.11 |
Minimum of Months | 63.50 | 20.22 | 76.17 | 19.94 | 16.67 | 19.82 |
Maximum of Months | 499.33 | 25.19 | 494.83 | 24.56 | 322.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.48 | 366.00 | 20.34 | 366.00 | 20.28 |
February | 454.00 | 20.82 | 331.17 | 20.66 | 331.17 | 20.60 |
March | 491.67 | 21.74 | 115.00 | 21.57 | 110.17 | 21.43 |
April | 375.50 | 22.37 | 62.83 | 22.50 | 20.00 | 22.43 |
May | 216.83 | 23.31 | 174.00 | 23.82 | 16.83 | 23.84 |
June | 22.67 | 25.91 | 453.67 | 24.47 | 17.83 | 24.55 |
July | 38.83 | 26.63 | 497.00 | 24.71 | 38.83 | 24.84 |
August | 24.67 | 26.68 | 500.17 | 24.59 | 24.67 | 24.68 |
September | 52.67 | 24.50 | 368.00 | 24.45 | 14.50 | 24.53 |
October | 153.00 | 23.46 | 250.17 | 23.99 | 1.17 | 23.99 |
November | 446.00 | 21.99 | 94.17 | 21.78 | 89.67 | 21.61 |
December | 497.00 | 20.99 | 295.50 | 20.83 | 295.50 | 20.75 |
Annual Sum or Average | 3274.83 | 21.76 | 3507.67 | 22.43 | 1326.33 | 22.19 |
Minimum of Months | 22.67 | 20.48 | 62.83 | 20.34 | 1.17 | 20.28 |
Maximum of Months | 502.00 | 26.68 | 500.17 | 24.71 | 366.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 391.83 | 20.15 | 391.83 | 20.10 |
February | 454.00 | 20.51 | 371.83 | 20.43 | 371.83 | 20.40 |
March | 510.33 | 21.52 | 127.00 | 21.32 | 127.00 | 21.19 |
April | 397.50 | 22.41 | 43.50 | 22.42 | 18.83 | 22.33 |
May | 164.17 | 23.41 | 147.83 | 23.84 | 0.00 | 23.84 |
June | 12.33 | 25.12 | 435.83 | 24.36 | 9.17 | 24.38 |
July | 32.67 | 26.08 | 497.00 | 24.61 | 32.67 | 24.70 |
August | 17.67 | 26.26 | 472.83 | 24.47 | 17.17 | 24.53 |
September | 88.00 | 23.60 | 303.17 | 24.16 | 5.33 | 24.17 |
October | 267.83 | 22.94 | 147.17 | 23.32 | 2.50 | 23.30 |
November | 478.83 | 21.61 | 143.67 | 21.32 | 143.17 | 21.14 |
December | 497.00 | 20.57 | 387.67 | 20.49 | 387.67 | 20.45 |
Annual Sum or Average | 3422.33 | 21.51 | 3469.33 | 22.09 | 1507.17 | 21.81 |
Minimum of Months | 12.33 | 20.25 | 43.50 | 20.15 | 0.00 | 20.10 |
Maximum of Months | 510.33 | 26.26 | 497.00 | 24.61 | 391.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.26 | 311.50 | 20.08 | 311.50 | 20.00 |
February | 385.00 | 20.81 | 256.17 | 20.60 | 256.17 | 20.51 |
March | 409.50 | 21.84 | 82.33 | 21.61 | 81.00 | 21.43 |
April | 280.00 | 22.52 | 75.00 | 22.89 | 8.83 | 22.84 |
May | 120.17 | 23.92 | 200.83 | 24.37 | 18.17 | 24.51 |
June | 26.00 | 26.38 | 391.83 | 24.62 | 24.33 | 24.72 |
July | 71.00 | 26.61 | 422.00 | 24.98 | 71.00 | 25.19 |
August | 38.67 | 26.72 | 413.17 | 24.75 | 38.67 | 24.90 |
September | 70.67 | 24.67 | 294.83 | 24.60 | 25.83 | 24.74 |
October | 188.33 | 23.19 | 167.17 | 23.71 | 5.50 | 23.73 |
November | 376.50 | 21.70 | 107.67 | 21.42 | 102.83 | 21.22 |
December | 422.00 | 20.79 | 262.17 | 20.58 | 262.17 | 20.48 |
Annual Sum or Average | 2814.83 | 21.83 | 2984.67 | 22.46 | 1206.00 | 22.23 |
Minimum of Months | 26.00 | 20.26 | 75.00 | 20.08 | 5.50 | 20.00 |
Maximum of Months | 427.00 | 26.72 | 422.00 | 24.98 | 311.50 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.00 | 20.90 | 269.83 | 20.56 | 267.33 | 20.39 |
February | 410.50 | 21.43 | 213.83 | 21.16 | 205.67 | 20.97 |
March | 408.00 | 21.97 | 95.17 | 21.93 | 63.33 | 21.77 |
April | 321.67 | 22.52 | 93.33 | 22.84 | 15.17 | 22.76 |
May | 150.50 | 23.48 | 211.83 | 24.03 | 6.00 | 24.08 |
June | 28.33 | 25.46 | 444.83 | 24.43 | 19.67 | 24.50 |
July | 57.83 | 26.42 | 497.00 | 24.74 | 57.83 | 24.90 |
August | 35.67 | 26.70 | 485.83 | 24.61 | 35.67 | 24.75 |
September | 71.67 | 24.78 | 372.67 | 24.52 | 27.83 | 24.66 |
October | 152.83 | 23.51 | 289.50 | 24.14 | 12.17 | 24.22 |
November | 372.50 | 22.04 | 121.33 | 22.00 | 73.67 | 21.78 |
December | 443.17 | 21.37 | 224.33 | 21.14 | 213.33 | 20.96 |
Annual Sum or Average | 2931.67 | 22.10 | 3319.50 | 22.80 | 997.67 | 22.58 |
Minimum of Months | 28.33 | 20.90 | 93.33 | 20.56 | 6.00 | 20.39 |
Maximum of Months | 479.00 | 26.70 | 497.00 | 24.74 | 267.33 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 342.33 | 20.26 | 342.33 | 20.18 |
February | 452.50 | 20.88 | 305.50 | 20.65 | 305.50 | 20.56 |
March | 449.33 | 21.75 | 107.50 | 21.61 | 94.50 | 21.46 |
April | 339.33 | 22.47 | 86.00 | 22.71 | 21.00 | 22.63 |
May | 138.83 | 23.72 | 234.17 | 24.15 | 16.17 | 24.26 |
June | 31.83 | 25.94 | 455.00 | 24.51 | 25.67 | 24.61 |
July | 60.83 | 26.49 | 497.00 | 24.79 | 60.83 | 24.96 |
August | 32.83 | 26.65 | 489.17 | 24.61 | 32.83 | 24.73 |
September | 77.00 | 24.26 | 345.33 | 24.38 | 20.17 | 24.49 |
October | 206.67 | 23.07 | 225.17 | 23.67 | 5.17 | 23.68 |
November | 449.33 | 21.66 | 130.50 | 21.39 | 126.83 | 21.20 |
December | 497.00 | 20.86 | 322.83 | 20.66 | 322.83 | 20.58 |
Annual Sum or Average | 3237.50 | 21.76 | 3540.50 | 22.42 | 1373.83 | 22.18 |
Minimum of Months | 31.83 | 20.47 | 86.00 | 20.26 | 5.17 | 20.18 |
Maximum of Months | 502.00 | 26.65 | 497.00 | 24.79 | 342.33 | 24.96 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.86156 | 23.51631 | -0.1350 | 7.68865 |
February | 454.00000 | 23.51522 | 19.41346 | 0.00753 | 5.43758 |
March | 514.00000 | 24.06066 | 26.62700 | 0.22184 | 6.25099 |
April | 485.00000 | 24.29146 | 32.50145 | 0.34839 | 7.86881 |
May | 508.00000 | 24.39832 | 39.63636 | -0.3973 | 8.81894 |
June | 496.00000 | 24.45065 | 49.30945 | -0.2716 | 7.13675 |
July | 497.00000 | 24.51056 | 52.29735 | -0.2213 | 6.62154 |
August | 514.00000 | 24.46035 | 49.25502 | -0.2516 | 7.01302 |
September | 485.00000 | 24.49725 | 45.08418 | -0.2928 | 7.47977 |
October | 502.00000 | 24.46490 | 38.58982 | 0.47869 | 10.29304 |
November | 489.00000 | 24.19703 | 29.60876 | 0.28764 | 7.38767 |
December | 497.00000 | 23.78636 | 22.12678 | 0.10154 | 5.38093 |
Annual Sum or Average | 5943.00000 | 24.12820 | 35.78725 | -0.0114 | 7.29512 |
Minimum of Months | 454.00000 | 22.86156 | 19.41346 | -0.3973 | 5.38093 |
Maximum of Months | 514.00000 | 24.51056 | 52.29735 | 0.47869 | 10.29304 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25963 | 25.65250 | -0.4934 | 12.07201 |
February | 454.00000 | 21.72667 | 21.50564 | -0.3961 | 9.01044 |
March | 514.00000 | 22.85787 | 29.55681 | -0.0542 | 5.83991 |
April | 485.00000 | 23.49998 | 34.74794 | 0.16059 | 6.41677 |
May | 508.00000 | 24.08484 | 41.28927 | -0.5183 | 11.07126 |
June | 496.00000 | 24.27432 | 50.31762 | -0.3512 | 7.90869 |
July | 497.00000 | 24.35378 | 53.86923 | -0.2862 | 7.04373 |
August | 514.00000 | 24.32336 | 50.63876 | -0.3151 | 7.50087 |
September | 485.00000 | 24.26292 | 46.19634 | -0.3983 | 8.76818 |
October | 502.00000 | 24.05422 | 40.06992 | 0.36042 | 8.30774 |
November | 489.00000 | 22.94271 | 32.66505 | -0.0110 | 6.72857 |
December | 497.00000 | 21.93283 | 25.05754 | -0.3178 | 7.81362 |
Annual Sum or Average | 5943.00000 | 23.30914 | 37.75316 | -0.2179 | 8.20537 |
Minimum of Months | 454.00000 | 21.25963 | 21.50564 | -0.5183 | 5.83991 |
Maximum of Months | 514.00000 | 24.35378 | 53.86923 | 0.36042 | 12.07201 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63038 | 26.48369 | -0.6674 | 16.71574 |
February | 454.00000 | 20.97690 | 21.72538 | -0.6030 | 13.90210 |
March | 514.00000 | 22.09902 | 30.61535 | -0.2422 | 7.64917 |
April | 485.00000 | 22.99743 | 35.81148 | 0.03739 | 6.70709 |
May | 508.00000 | 23.93101 | 41.78239 | -0.5707 | 12.65716 |
June | 496.00000 | 24.24701 | 49.97300 | -0.3569 | 8.00762 |
July | 497.00000 | 24.37090 | 53.26690 | -0.2725 | 6.91988 |
August | 514.00000 | 24.31443 | 50.20007 | -0.3130 | 7.49057 |
September | 485.00000 | 24.13084 | 46.05976 | -0.4509 | 9.92046 |
October | 502.00000 | 23.61741 | 41.06220 | 0.24771 | 7.55397 |
November | 489.00000 | 22.05920 | 34.28817 | -0.2355 | 8.63322 |
December | 497.00000 | 21.01820 | 25.92366 | -0.5600 | 12.80787 |
Annual Sum or Average | 5943.00000 | 22.88044 | 38.22223 | -0.3308 | 9.88879 |
Minimum of Months | 454.00000 | 20.63038 | 21.72538 | -0.6674 | 6.70709 |
Maximum of Months | 514.00000 | 24.37090 | 53.26690 | 0.24771 | 16.71574 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97282 | 28.09014 | -0.8755 | 23.82894 |
February | 454.00000 | 20.15022 | 22.90856 | -0.8500 | 22.35263 |
March | 514.00000 | 21.11187 | 32.88939 | -0.4877 | 12.01526 |
April | 485.00000 | 22.27906 | 37.78735 | -0.1308 | 8.29210 |
May | 508.00000 | 23.72514 | 42.89223 | -0.6245 | 15.30672 |
June | 496.00000 | 24.26493 | 51.26508 | -0.3051 | 7.77361 |
July | 497.00000 | 24.50728 | 55.13711 | -0.1613 | 6.61984 |
August | 514.00000 | 24.34598 | 51.52926 | -0.2530 | 7.32440 |
September | 485.00000 | 23.94847 | 48.03698 | -0.4958 | 11.78926 |
October | 502.00000 | 22.94445 | 43.45464 | 0.09203 | 7.94041 |
November | 489.00000 | 21.05431 | 36.44587 | -0.4890 | 13.02178 |
December | 497.00000 | 20.18004 | 27.96414 | -0.8017 | 20.32483 |
Annual Sum or Average | 5943.00000 | 22.39127 | 39.99193 | -0.4459 | 12.98452 |
Minimum of Months | 454.00000 | 19.97282 | 22.90856 | -0.8755 | 6.61984 |
Maximum of Months | 514.00000 | 24.50728 | 55.13711 | 0.09203 | 23.82894 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08442 | 28.94997 | -0.8241 | 22.33612 |
February | 454.00000 | 20.45481 | 23.63411 | -0.7450 | 19.05945 |
March | 514.00000 | 21.65486 | 32.71580 | -0.3354 | 10.49258 |
April | 485.00000 | 22.80624 | 36.61817 | 0.02198 | 8.57331 |
May | 508.00000 | 23.97878 | 42.13113 | -0.4744 | 12.85754 |
June | 496.00000 | 24.35792 | 50.88345 | -0.2149 | 7.33453 |
July | 497.00000 | 24.59339 | 54.62829 | -0.0665 | 6.86379 |
August | 514.00000 | 24.42512 | 50.95628 | -0.1347 | 6.78596 |
September | 485.00000 | 24.18004 | 47.23245 | -0.3580 | 10.10156 |
October | 502.00000 | 23.40314 | 42.10918 | 0.23006 | 8.70909 |
November | 489.00000 | 21.44042 | 36.52443 | -0.3798 | 11.80404 |
December | 497.00000 | 20.38453 | 28.68359 | -0.7298 | 18.22695 |
Annual Sum or Average | 5943.00000 | 22.66395 | 39.70786 | -0.3315 | 11.87750 |
Minimum of Months | 454.00000 | 20.08442 | 23.63411 | -0.8241 | 6.78596 |
Maximum of Months | 514.00000 | 24.59339 | 54.62829 | 0.23006 | 22.33612 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67779 | 27.03539 | -0.6601 | 19.28717 |
February | 454.00000 | 21.24634 | 21.43519 | -0.5357 | 15.78580 |
March | 514.00000 | 21.94496 | 30.59623 | -0.2482 | 10.31702 |
April | 485.00000 | 22.70985 | 36.11385 | 0.00059 | 8.86447 |
May | 508.00000 | 23.79064 | 42.40917 | -0.5690 | 14.79571 |
June | 496.00000 | 24.27260 | 51.10017 | -0.2783 | 7.85702 |
July | 497.00000 | 24.52756 | 54.85785 | -0.1223 | 6.79069 |
August | 514.00000 | 24.40196 | 50.89101 | -0.1565 | 6.98362 |
September | 485.00000 | 24.17992 | 46.71634 | -0.3260 | 10.01885 |
October | 502.00000 | 23.70655 | 40.36339 | 0.34848 | 10.67461 |
November | 489.00000 | 21.96888 | 34.11172 | -0.2320 | 10.67044 |
December | 497.00000 | 21.20465 | 26.32594 | -0.5168 | 15.21418 |
Annual Sum or Average | 5943.00000 | 22.89873 | 38.62382 | -0.2732 | 11.41277 |
Minimum of Months | 454.00000 | 20.67779 | 21.43519 | -0.6601 | 6.79069 |
Maximum of Months | 514.00000 | 24.52756 | 54.85785 | 0.34848 | 19.28717 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.17779 | 28.76316 | -0.8115 | 22.13347 |
February | 454.00000 | 20.50345 | 23.35800 | -0.7471 | 19.94526 |
March | 514.00000 | 21.60088 | 32.34355 | -0.3480 | 11.00805 |
April | 485.00000 | 22.56801 | 37.35947 | -0.0318 | 9.01195 |
May | 508.00000 | 23.84969 | 42.77155 | -0.5259 | 14.11944 |
June | 496.00000 | 24.32849 | 51.03983 | -0.2162 | 7.60707 |
July | 497.00000 | 24.56858 | 54.91803 | -0.0789 | 6.93657 |
August | 514.00000 | 24.42209 | 51.18035 | -0.1390 | 6.94503 |
September | 485.00000 | 24.07549 | 47.70150 | -0.3961 | 10.83608 |
October | 502.00000 | 23.27981 | 42.55751 | 0.20588 | 9.09236 |
November | 489.00000 | 21.25811 | 36.76432 | -0.4291 | 12.44283 |
December | 497.00000 | 20.41802 | 28.62812 | -0.7316 | 18.57662 |
Annual Sum or Average | 5943.00000 | 22.60446 | 39.90194 | -0.3514 | 12.33301 |
Minimum of Months | 454.00000 | 20.17779 | 23.35800 | -0.8115 | 6.93657 |
Maximum of Months | 514.00000 | 24.56858 | 54.91803 | 0.20588 | 22.13347 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29396 | 27.94456 | -0.7733 | 19.41187 |
February | 454.00000 | 20.48027 | 22.99215 | -0.7527 | 17.92828 |
March | 514.00000 | 21.14705 | 33.13837 | -0.4731 | 10.61983 |
April | 485.00000 | 22.19953 | 38.79736 | -0.1566 | 7.18814 |
May | 508.00000 | 23.53293 | 43.97099 | -0.7298 | 17.48804 |
June | 496.00000 | 24.20105 | 51.79891 | -0.3684 | 8.22249 |
July | 497.00000 | 24.41184 | 54.51286 | -0.2372 | 6.67157 |
August | 514.00000 | 24.32280 | 51.00024 | -0.2897 | 7.27636 |
September | 485.00000 | 24.13643 | 47.67595 | -0.4348 | 9.62470 |
October | 502.00000 | 23.57178 | 42.19436 | 0.24486 | 7.40924 |
November | 489.00000 | 21.91457 | 35.18265 | -0.2521 | 8.45878 |
December | 497.00000 | 20.70399 | 27.37632 | -0.6277 | 13.80613 |
Annual Sum or Average | 5943.00000 | 22.59134 | 39.83977 | -0.4026 | 11.14463 |
Minimum of Months | 454.00000 | 20.29396 | 22.99215 | -0.7733 | 6.67157 |
Maximum of Months | 514.00000 | 24.41184 | 54.51286 | 0.24486 | 19.41187 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.45504 | 28.79557 | -0.7118 | 17.64037 |
February | 454.00000 | 20.83498 | 23.74374 | -0.6335 | 14.57097 |
March | 514.00000 | 21.85116 | 33.00980 | -0.2816 | 8.39451 |
April | 485.00000 | 22.95729 | 37.14883 | 0.04895 | 7.39421 |
May | 508.00000 | 23.94846 | 42.56858 | -0.5284 | 13.13572 |
June | 496.00000 | 24.35314 | 51.14923 | -0.2560 | 7.23539 |
July | 497.00000 | 24.56992 | 53.80178 | -0.1170 | 6.46082 |
August | 514.00000 | 24.46062 | 50.19504 | -0.1461 | 6.40553 |
September | 485.00000 | 24.37670 | 46.72801 | -0.2880 | 8.13856 |
October | 502.00000 | 24.00548 | 40.68504 | 0.38400 | 9.08535 |
November | 489.00000 | 22.41899 | 34.83549 | -0.1175 | 7.75742 |
December | 497.00000 | 21.06863 | 27.98380 | -0.5226 | 11.66783 |
Annual Sum or Average | 5943.00000 | 22.95637 | 39.33760 | -0.2623 | 9.79929 |
Minimum of Months | 454.00000 | 20.45504 | 23.74374 | -0.7118 | 6.40553 |
Maximum of Months | 514.00000 | 24.56992 | 53.80178 | 0.38400 | 17.64037 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.24758 | 25.30051 | -0.6982 | 18.43895 |
February | 454.00000 | 20.78419 | 20.03361 | -0.5740 | 15.24663 |
March | 514.00000 | 21.52767 | 29.76257 | -0.3072 | 9.52279 |
April | 485.00000 | 22.33341 | 36.06854 | -0.0763 | 7.99786 |
May | 508.00000 | 23.32533 | 43.63875 | -0.7428 | 19.29826 |
June | 496.00000 | 24.17911 | 53.79739 | -0.3314 | 8.22325 |
July | 497.00000 | 24.49550 | 57.43109 | -0.1535 | 6.32008 |
August | 514.00000 | 24.45014 | 52.35809 | -0.1478 | 6.45606 |
September | 485.00000 | 24.33334 | 47.70310 | -0.2517 | 8.26965 |
October | 502.00000 | 24.12899 | 39.68656 | 0.48414 | 11.58376 |
November | 489.00000 | 22.27530 | 31.73836 | -0.0969 | 8.46832 |
December | 497.00000 | 21.23792 | 24.05849 | -0.4321 | 11.91144 |
Annual Sum or Average | 5943.00000 | 22.79039 | 38.60515 | -0.2762 | 10.96762 |
Minimum of Months | 454.00000 | 20.24758 | 20.03361 | -0.7428 | 6.32008 |
Maximum of Months | 514.00000 | 24.49550 | 57.43109 | 0.48414 | 19.29826 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48316 | 28.68052 | -0.7116 | 17.79073 |
February | 454.00000 | 20.81755 | 23.62720 | -0.6471 | 15.35873 |
March | 514.00000 | 21.84433 | 32.57943 | -0.2832 | 8.60163 |
April | 485.00000 | 22.78855 | 37.65386 | 0.00830 | 7.41195 |
May | 508.00000 | 23.87106 | 43.08195 | -0.5661 | 13.75475 |
June | 496.00000 | 24.36908 | 51.05899 | -0.2406 | 7.15647 |
July | 497.00000 | 24.56488 | 53.95266 | -0.1207 | 6.47795 |
August | 514.00000 | 24.47287 | 50.34300 | -0.1443 | 6.40791 |
September | 485.00000 | 24.31622 | 47.03931 | -0.3128 | 8.31925 |
October | 502.00000 | 24.00265 | 40.80797 | 0.38488 | 9.21554 |
November | 489.00000 | 22.16946 | 35.33937 | -0.1809 | 8.14970 |
December | 497.00000 | 20.99291 | 28.00752 | -0.5458 | 12.22458 |
Annual Sum or Average | 5943.00000 | 22.90637 | 39.46396 | -0.2779 | 10.04407 |
Minimum of Months | 454.00000 | 20.48316 | 23.62720 | -0.7116 | 6.40791 |
Maximum of Months | 514.00000 | 24.56488 | 53.95266 | 0.38488 | 17.79073 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25444 | 27.82017 | -0.7699 | 19.67652 |
February | 454.00000 | 20.51098 | 22.62775 | -0.7237 | 17.40148 |
March | 514.00000 | 21.53779 | 32.27906 | -0.3603 | 9.19719 |
April | 485.00000 | 22.70849 | 36.95259 | -0.0196 | 7.02230 |
May | 508.00000 | 23.91391 | 42.27872 | -0.5618 | 12.72964 |
June | 496.00000 | 24.30237 | 51.35637 | -0.2974 | 7.41831 |
July | 497.00000 | 24.51367 | 55.30775 | -0.1711 | 6.52960 |
August | 514.00000 | 24.36979 | 51.64809 | -0.2529 | 7.10539 |
September | 485.00000 | 24.11145 | 47.85035 | -0.4368 | 9.92056 |
October | 502.00000 | 23.42927 | 42.27873 | 0.21267 | 7.49793 |
November | 489.00000 | 21.65651 | 35.35316 | -0.3185 | 9.63828 |
December | 497.00000 | 20.57326 | 27.41240 | -0.6621 | 15.15578 |
Annual Sum or Average | 5943.00000 | 22.67304 | 39.55588 | -0.3614 | 10.73121 |
Minimum of Months | 454.00000 | 20.25444 | 22.62775 | -0.7699 | 6.52960 |
Maximum of Months | 514.00000 | 24.51367 | 55.30775 | 0.21267 | 19.67652 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.26299 | 28.34993 | -0.7495 | 19.50179 |
February | 385.00000 | 20.81075 | 23.05487 | -0.6302 | 15.23917 |
March | 433.00000 | 21.96630 | 31.86925 | -0.2420 | 8.53381 |
April | 410.00000 | 23.11684 | 35.80268 | 0.09969 | 7.85020 |
May | 430.00000 | 24.16051 | 41.33056 | -0.4278 | 11.33746 |
June | 418.00000 | 24.47310 | 50.45925 | -0.2044 | 7.20356 |
July | 422.00000 | 24.71090 | 54.41633 | -0.0630 | 6.95515 |
August | 433.00000 | 24.53625 | 50.89467 | -0.1329 | 6.81874 |
September | 410.00000 | 24.36675 | 46.92598 | -0.3091 | 9.07153 |
October | 427.00000 | 23.74448 | 40.84298 | 0.30715 | 8.65762 |
November | 417.00000 | 21.93806 | 35.20414 | -0.2395 | 9.20021 |
December | 422.00000 | 20.78560 | 27.96003 | -0.5973 | 13.96712 |
Annual Sum or Average | 5034.00000 | 22.91889 | 39.03140 | -0.2637 | 10.33544 |
Minimum of Months | 385.00000 | 20.26299 | 23.05487 | -0.7495 | 6.81874 |
Maximum of Months | 433.00000 | 24.71090 | 54.41633 | 0.30715 | 19.50179 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.05154 | 26.54040 | -0.5389 | 15.49537 |
February | 454.00000 | 21.72440 | 20.93708 | -0.3897 | 12.11274 |
March | 514.00000 | 22.40847 | 29.81553 | -0.1171 | 8.14542 |
April | 485.00000 | 23.11263 | 35.25583 | 0.10513 | 7.86321 |
May | 508.00000 | 23.98736 | 41.75929 | -0.5054 | 12.16273 |
June | 496.00000 | 24.32766 | 51.13496 | -0.2666 | 7.39029 |
July | 497.00000 | 24.54355 | 54.95692 | -0.1302 | 6.63103 |
August | 514.00000 | 24.43613 | 50.96450 | -0.1554 | 6.70414 |
September | 485.00000 | 24.32498 | 46.57392 | -0.2744 | 8.56225 |
October | 502.00000 | 24.04993 | 39.53857 | 0.44009 | 10.95933 |
November | 489.00000 | 22.55692 | 32.88567 | -0.0680 | 8.58696 |
December | 497.00000 | 21.71743 | 25.52599 | -0.3576 | 11.38269 |
Annual Sum or Average | 5943.00000 | 23.19760 | 38.11933 | -0.1873 | 9.65414 |
Minimum of Months | 454.00000 | 21.05154 | 20.93708 | -0.5389 | 6.63103 |
Maximum of Months | 514.00000 | 24.54355 | 54.95692 | 0.44009 | 15.49537 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47121 | 28.47957 | -0.7044 | 18.23352 |
February | 454.00000 | 20.88905 | 23.01870 | -0.6175 | 15.40862 |
March | 514.00000 | 22.04556 | 31.62721 | -0.2192 | 8.57404 |
April | 485.00000 | 22.99256 | 36.46715 | 0.07716 | 7.88599 |
May | 508.00000 | 24.03945 | 42.09565 | -0.4645 | 11.58663 |
June | 496.00000 | 24.37881 | 51.07688 | -0.2061 | 7.15273 |
July | 497.00000 | 24.58528 | 55.03114 | -0.0867 | 6.73865 |
August | 514.00000 | 24.45183 | 51.29604 | -0.1387 | 6.67507 |
September | 485.00000 | 24.22904 | 47.50696 | -0.3412 | 9.14614 |
October | 502.00000 | 23.71513 | 41.47132 | 0.31592 | 8.91209 |
November | 489.00000 | 21.85160 | 35.59391 | -0.2618 | 9.30837 |
December | 497.00000 | 20.85516 | 27.98087 | -0.5853 | 13.73463 |
Annual Sum or Average | 5943.00000 | 22.89089 | 39.42402 | -0.2671 | 10.24432 |
Minimum of Months | 454.00000 | 20.47121 | 23.01870 | -0.7044 | 6.67507 |
Maximum of Months | 514.00000 | 24.58528 | 55.03114 | 0.31592 | 18.23352 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.756303E+11 | 0.00 | 464.59 | 201585.14 | 02-JAN-07:10 | 0.00 | 37.40 | 51.24 | 0.36 | 0.00 | 0.10 | 0.69 | 02-JAN-07:10 |
February | 0.639737E+11 | 0.00 | 400.04 | 190375.98 | 06-FEB-07:07 | 0.00 | 37.45 | 50.62 | 0.33 | 0.00 | 0.09 | 0.65 | 06-FEB-07:07 |
March | 0.282730E+11 | 0.00 | 351.64 | 189371.78 | 08-MAR-07:02 | 0.00 | 32.12 | 44.66 | 0.11 | 0.00 | 0.04 | 0.65 | 08-MAR-07:02 |
April | 0.764197E+10 | 0.00 | 189.46 | 177375.87 | 04-APR-06:02 | 0.00 | 34.14 | 41.56 | 0.03 | 0.00 | 0.01 | 0.61 | 04-APR-06:02 |
May | 0.434497E+09 | 0.00 | 38.63 | 42715.90 | 01-MAY-06:03 | 0.00 | 42.84 | 43.77 | 0.00 | 0.00 | 0.00 | 0.15 | 01-MAY-06:03 |
June | 2056330.98 | 0.00 | 88.20 | 1372.05 | 02-JUN-06:10 | 0.00 | 40.26 | 42.69 | 0.00 | 0.00 | 0.00 | 0.00 | 02-JUN-06:10 |
July | 2969419.99 | 0.00 | 164.37 | 7.69 | 21-JUL-12:50 | 0.00 | 38.37 | 43.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21-JUL-12:50 |
August | 3033631.12 | 0.00 | 163.19 | 8.35 | 18-AUG-05:03 | 0.00 | 36.45 | 41.59 | 0.00 | 0.00 | 0.00 | 0.00 | 18-AUG-05:03 |
September | 10926708.80 | 0.00 | 62.77 | 11599.79 | 20-SEP-06:07 | 0.00 | 34.92 | 37.08 | 0.00 | 0.00 | 0.00 | 0.04 | 20-SEP-06:07 |
October | 0.117541E+10 | 0.00 | 81.11 | 79075.88 | 28-OCT-06:03 | 0.00 | 34.16 | 36.99 | 0.00 | 0.00 | 0.00 | 0.27 | 28-OCT-06:03 |
November | 0.210967E+11 | 0.00 | 268.86 | 171558.92 | 28-NOV-07:02 | 0.00 | 32.85 | 42.94 | 0.08 | 0.00 | 0.03 | 0.59 | 28-NOV-07:02 |
December | 0.480649E+11 | 0.00 | 396.13 | 173717.93 | 20-DEC-07:02 | 0.00 | 34.52 | 47.99 | 0.19 | 0.00 | 0.06 | 0.60 | 20-DEC-07:02 |
Annual Sum or Average | 0.246309E+12 | 0.00 | 2668.98 | 0.00 | 36.29 | 43.66 | 0.09 | 0.00 | 0.03 | ||||
Minimum of Months | 2056330.98 | 0.00 | 38.63 | 7.69 | 0.00 | 32.12 | 36.99 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.756303E+11 | 0.00 | 464.59 | 201585.14 | 0.00 | 42.84 | 51.24 | 0.36 | 0.00 | 0.10 | 0.69 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 736095.72 | 198332.88 | 0.17 | 736095.72 | 0.00 | 0.00 | 0.05 | 03-JAN-07:30 | 0.00 | 01-JAN-00:02 | 1226.83 | 03-JAN-07:30 | 1226.83 | 03-JAN-07:30 | 0.00 | 03-JAN-07:30 | 330.55 | 03-JAN-07:30 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.489143E+09 | 0.118218E+09 | 20.52 | 0.351457E+09 | 0.137686E+09 | 0.00 | 0.76 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 23589.45 | 27-MAR-16:00 | 20782.34 | 27-MAR-16:00 | 7545.96 | 27-MAR-13:00 | 5312.00 | 27-MAR-16:00 | 0.00 |
April | 0.554220E+10 | 0.131376E+10 | 134.68 | 0.517548E+10 | 0.366717E+09 | 0.00 | 1.00 | 07-APR-12:05 | 0.00 | 01-APR-00:10 | 44559.45 | 07-APR-14:30 | 44559.45 | 07-APR-14:30 | 9347.73 | 10-APR-06:03 | 9840.78 | 07-APR-14:20 | 0.00 |
May | 0.167382E+11 | 0.391089E+10 | 291.42 | 0.142010E+11 | 0.253718E+10 | 0.00 | 1.00 | 19-MAY-06:03 | 0.00 | 01-MAY-00:10 | 83326.16 | 30-MAY-14:20 | 83326.16 | 30-MAY-14:20 | 23567.42 | 31-MAY-06:03 | 19987.62 | 30-MAY-14:10 | 0.00 |
June | 0.575169E+11 | 0.128617E+11 | 427.44 | 0.449539E+11 | 0.125629E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 106642.34 | 27-JUN-06:03 | 80260.93 | 19-JUN-05:02 | 48485.46 | 27-JUN-06:03 | 25721.11 | 19-JUN-12:03 | 0.00 |
July | 0.816836E+11 | 0.185043E+11 | 452.38 | 0.612578E+11 | 0.204258E+11 | 0.00 | 1.00 | 01-JUL-05:13 | 0.00 | 01-JUL-00:10 | 107107.39 | 22-JUL-06:03 | 82740.99 | 10-JUL-06:03 | 47824.21 | 28-JUL-06:03 | 23022.94 | 07-JUL-06:03 | 0.00 |
August | 0.839288E+11 | 0.192574E+11 | 465.35 | 0.672388E+11 | 0.166900E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 106478.47 | 16-AUG-06:03 | 84622.39 | 22-AUG-15:50 | 40661.21 | 16-AUG-06:03 | 23434.46 | 16-AUG-12:03 | 0.00 |
September | 0.441044E+11 | 0.978636E+10 | 393.21 | 0.359953E+11 | 0.810904E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 105843.13 | 07-SEP-06:03 | 79659.50 | 05-SEP-05:12 | 45378.44 | 06-SEP-05:12 | 22670.36 | 01-SEP-06:03 | 0.00 |
October | 0.213509E+11 | 0.474378E+10 | 268.46 | 0.156262E+11 | 0.572476E+10 | 0.00 | 1.00 | 02-OCT-12:20 | 0.00 | 01-OCT-00:10 | 65552.26 | 25-OCT-10:30 | 51969.05 | 04-OCT-15:00 | 34313.24 | 06-OCT-06:03 | 13952.09 | 25-OCT-10:30 | 0.00 |
November | 0.199548E+10 | 0.494540E+09 | 73.64 | 0.188735E+10 | 0.108136E+09 | 0.00 | 0.68 | 06-NOV-15:30 | 0.00 | 01-NOV-00:10 | 20588.25 | 06-NOV-15:30 | 20588.25 | 06-NOV-15:30 | 5810.00 | 10-NOV-07:03 | 4740.67 | 06-NOV-15:30 | 0.00 |
December | 53423.69 | 14493.98 | 0.03 | 46324.01 | 7099.68 | 0.00 | 0.02 | 19-DEC-17:02 | 0.00 | 01-DEC-00:10 | 445.20 | 19-DEC-17:02 | 386.03 | 19-DEC-17:02 | 59.16 | 19-DEC-17:02 | 120.78 | 19-DEC-17:02 | 0.00 |
Annual Sum or Average | 0.313350E+12 | 0.709911E+11 | 2527.29 | 0.246688E+12 | 0.666623E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.839288E+11 | 0.192574E+11 | 465.35 | 0.672388E+11 | 0.204258E+11 | 0.00 | 1.00 | 0.00 | 107107.39 | 84622.39 | 48485.46 | 25721.11 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 71919.24 | 19527.77 | 0.06 | 71919.24 | -0.0 | 0.00 | 0.02 | 02-JAN-06:02 | 0.00 | 01-JAN-00:02 | 384.82 | 02-JAN-06:02 | 384.82 | 02-JAN-06:02 | 0.00 | 01-JAN-00:02 | 104.44 | 02-JAN-06:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.403471E+09 | 97666017.80 | 14.75 | 0.277275E+09 | 0.126196E+09 | 0.00 | 0.71 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 20879.94 | 27-MAR-16:00 | 17497.44 | 27-MAR-16:00 | 7042.45 | 27-MAR-12:55 | 4757.98 | 27-MAR-16:00 | 0.00 |
April | 0.440934E+10 | 0.104296E+10 | 101.62 | 0.400729E+10 | 0.402055E+09 | 0.00 | 1.00 | 07-APR-12:00 | 0.00 | 01-APR-00:10 | 47447.30 | 07-APR-14:05 | 47447.30 | 07-APR-14:05 | 5759.86 | 09-APR-17:02 | 10503.41 | 07-APR-14:05 | 0.00 |
May | 0.158416E+11 | 0.369838E+10 | 296.12 | 0.136287E+11 | 0.221289E+10 | 0.00 | 1.00 | 22-MAY-10:05 | 0.00 | 01-MAY-00:10 | 81476.65 | 30-MAY-14:05 | 81476.65 | 30-MAY-14:05 | 23500.58 | 31-MAY-06:03 | 19565.55 | 30-MAY-14:05 | 0.00 |
June | 0.521287E+11 | 0.117015E+11 | 431.94 | 0.406926E+11 | 0.114361E+11 | 0.00 | 1.00 | 01-JUN-06:03 | 0.00 | 01-JUN-00:10 | 101065.34 | 27-JUN-06:03 | 74513.93 | 19-JUN-05:02 | 47859.41 | 20-JUN-06:03 | 26678.02 | 19-JUN-12:02 | 0.00 |
July | 0.736428E+11 | 0.166793E+11 | 448.35 | 0.544320E+11 | 0.192108E+11 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 104544.68 | 22-JUL-05:03 | 76224.69 | 10-JUL-06:03 | 44831.92 | 22-JUL-05:03 | 22104.22 | 22-JUL-06:03 | 0.00 |
August | 0.736657E+11 | 0.169097E+11 | 455.32 | 0.586608E+11 | 0.150049E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 101931.90 | 17-AUG-06:03 | 80856.50 | 22-AUG-15:10 | 38891.80 | 17-AUG-06:03 | 22448.20 | 04-AUG-14:05 | 0.00 |
September | 0.367149E+11 | 0.821656E+10 | 387.28 | 0.294937E+11 | 0.722117E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 100031.36 | 01-SEP-05:02 | 74240.10 | 05-SEP-05:12 | 32063.52 | 07-SEP-06:03 | 21207.54 | 01-SEP-05:02 | 0.00 |
October | 0.159847E+11 | 0.357261E+10 | 231.92 | 0.113497E+11 | 0.463496E+10 | 0.00 | 1.00 | 02-OCT-12:50 | 0.00 | 01-OCT-00:10 | 59693.46 | 04-OCT-14:05 | 47532.59 | 04-OCT-14:05 | 23012.89 | 24-OCT-09:00 | 12747.04 | 04-OCT-14:05 | 0.00 |
November | 0.377169E+09 | 97578632.25 | 25.17 | 0.318967E+09 | 58201397.29 | 0.00 | 0.36 | 03-NOV-14:05 | 0.00 | 01-NOV-00:10 | 9666.88 | 03-NOV-14:05 | 9666.88 | 03-NOV-14:05 | 2984.39 | 10-NOV-10:00 | 2414.69 | 03-NOV-14:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.273168E+12 | 0.620163E+11 | 2392.51 | 0.212861E+12 | 0.603073E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.736657E+11 | 0.169097E+11 | 455.32 | 0.586608E+11 | 0.192108E+11 | 0.00 | 1.00 | 0.00 | 104544.68 | 81476.65 | 47859.41 | 26678.02 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 272738.50 | 74159.23 | 0.39 | 258185.14 | 14553.36 | 0.00 | 0.01 | 10-JAN-05:30 | 0.00 | 01-JAN-00:02 | 241.46 | 10-JAN-05:30 | 225.54 | 11-JAN-05:43 | 23.08 | 10-JAN-05:30 | 65.64 | 10-JAN-05:30 | 0.00 |
February | 244378.48 | 66320.38 | 0.22 | 237730.92 | 6647.56 | 0.00 | 0.02 | 07-FEB-06:07 | 0.00 | 01-FEB-00:10 | 681.59 | 07-FEB-06:07 | 681.59 | 07-FEB-06:07 | 12.32 | 12-FEB-10:00 | 184.60 | 07-FEB-06:07 | 0.00 |
March | 0.504191E+09 | 0.124475E+09 | 18.67 | 0.363888E+09 | 0.140303E+09 | 0.00 | 0.67 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 21771.32 | 27-MAR-16:00 | 17092.58 | 27-MAR-16:00 | 7409.59 | 27-MAR-13:00 | 5020.01 | 27-MAR-16:00 | 0.00 |
April | 0.487899E+10 | 0.115787E+10 | 104.26 | 0.441621E+10 | 0.462783E+09 | 0.00 | 1.00 | 07-APR-11:50 | 0.00 | 01-APR-00:10 | 50639.15 | 07-APR-14:30 | 50639.15 | 07-APR-14:30 | 6365.17 | 09-APR-11:50 | 11164.73 | 07-APR-14:30 | 0.00 |
May | 0.165986E+11 | 0.389747E+10 | 295.03 | 0.142944E+11 | 0.230416E+10 | 0.00 | 1.00 | 28-MAY-13:23 | 0.00 | 01-MAY-00:10 | 89190.45 | 30-MAY-14:10 | 89190.45 | 30-MAY-14:10 | 15129.18 | 19-MAY-12:07 | 21512.67 | 30-MAY-14:00 | 0.00 |
June | 0.551948E+11 | 0.124721E+11 | 433.51 | 0.432559E+11 | 0.119390E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 106727.10 | 19-JUN-06:03 | 81874.86 | 19-JUN-05:02 | 32854.99 | 20-JUN-05:12 | 26541.12 | 19-JUN-12:05 | 0.00 |
July | 0.783791E+11 | 0.178228E+11 | 449.52 | 0.587698E+11 | 0.196092E+11 | 0.00 | 1.00 | 01-JUL-09:00 | 0.00 | 01-JUL-00:10 | 117797.06 | 22-JUL-05:03 | 83340.25 | 31-JUL-05:12 | 55322.59 | 22-JUL-05:03 | 24749.49 | 22-JUL-05:03 | 0.00 |
August | 0.782557E+11 | 0.180383E+11 | 455.91 | 0.629747E+11 | 0.152810E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 112810.70 | 05-AUG-06:03 | 92091.41 | 22-AUG-14:50 | 41273.11 | 17-AUG-05:03 | 24984.63 | 05-AUG-06:03 | 0.00 |
September | 0.372832E+11 | 0.842421E+10 | 387.33 | 0.296068E+11 | 0.767641E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 86422.62 | 01-SEP-14:20 | 86422.62 | 01-SEP-14:20 | 25818.02 | 07-SEP-12:30 | 21691.55 | 01-SEP-14:20 | 0.00 |
October | 0.153328E+11 | 0.346460E+10 | 224.44 | 0.107015E+11 | 0.463127E+10 | 0.00 | 1.00 | 03-OCT-10:50 | 0.00 | 01-OCT-00:10 | 62151.59 | 04-OCT-14:00 | 51598.30 | 04-OCT-15:00 | 22994.41 | 24-OCT-10:00 | 13322.69 | 04-OCT-13:50 | 0.00 |
November | 0.323417E+09 | 84597696.86 | 24.50 | 0.260058E+09 | 63358797.80 | 0.00 | 0.28 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 8151.04 | 03-NOV-14:00 | 8151.04 | 03-NOV-14:00 | 2211.03 | 10-NOV-10:00 | 2079.05 | 03-NOV-14:00 | 0.00 |
December | 71455.10 | 19424.10 | 0.08 | 64129.42 | 7325.68 | 0.00 | 0.01 | 31-DEC-09:50 | 0.00 | 01-DEC-00:10 | 238.18 | 31-DEC-09:50 | 213.76 | 31-DEC-09:50 | 24.42 | 31-DEC-09:50 | 64.75 | 31-DEC-09:50 | 0.00 |
Annual Sum or Average | 0.286751E+12 | 0.654865E+11 | 2393.85 | 0.224644E+12 | 0.621075E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 71455.10 | 19424.10 | 0.08 | 64129.42 | 6647.56 | 0.00 | 0.01 | 0.00 | 238.18 | 213.76 | 12.32 | 64.75 | 0.00 | ||||||
Maximum of Months | 0.783791E+11 | 0.180383E+11 | 455.91 | 0.629747E+11 | 0.196092E+11 | 0.00 | 1.00 | 0.00 | 117797.06 | 92091.41 | 55322.59 | 26541.12 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 27.21 | 1690.36 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 50.09 | 1758.31 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 239.71 | 1180.64 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 486.91 | 849.58 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 937.65 | 537.57 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1304.91 | 295.15 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1444.77 | 166.96 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1267.15 | 223.77 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 731.25 | 446.07 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 444.82 | 808.66 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 128.56 | 1197.68 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 18.06 | 1565.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 593.73 | 888.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 18.06 | 166.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1444.77 | 1758.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 293.09 | 1050.45 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 512.33 | 1060.49 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 801.72 | 764.85 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1110.25 | 555.20 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1527.97 | 368.28 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1593.37 | 202.26 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1731.92 | 113.55 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1943.04 | 150.97 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1286.05 | 291.56 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1042.35 | 528.34 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 476.00 | 757.37 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 314.44 | 965.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1056.46 | 564.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 293.09 | 113.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1943.04 | 1060.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1697.63 | 1519.18 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2273.20 | 1546.63 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2165.12 | 1157.59 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1733.46 | 880.27 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1604.22 | 578.57 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1737.43 | 316.24 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2017.20 | 171.83 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2719.76 | 237.85 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2620.16 | 460.00 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3352.17 | 816.63 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 2007.90 | 1135.92 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1914.45 | 1397.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2153.99 | 847.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1604.22 | 171.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3352.17 | 1546.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 288.71 | 1073.97 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 469.61 | 1106.57 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 900.40 | 762.06 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1110.03 | 571.66 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1457.44 | 381.00 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1802.00 | 214.09 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1810.52 | 121.20 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2007.60 | 163.11 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1273.02 | 305.67 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1136.49 | 544.87 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 330.47 | 776.71 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 274.12 | 993.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1076.02 | 581.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 274.12 | 121.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2007.60 | 1106.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.23 | 0.00 | 109.23 | 8.36 | 588.02 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 16.51 | 607.94 | 0.00 | 0.00 | 0.00 |
March | 207.29 | 0.00 | 207.29 | 83.79 | 402.14 | 0.00 | 0.00 | 0.00 |
April | 248.98 | 0.71 | 248.27 | 169.20 | 285.18 | 0.00 | 0.00 | 0.00 |
May | 330.32 | 11.01 | 319.31 | 325.89 | 173.89 | 0.00 | 0.00 | 0.00 |
June | 350.30 | 18.82 | 331.48 | 444.45 | 95.63 | 0.00 | 0.00 | 0.00 |
July | 338.53 | 12.24 | 326.29 | 490.52 | 52.49 | 0.00 | 0.00 | 0.00 |
August | 299.92 | 3.57 | 296.35 | 427.03 | 74.57 | 0.00 | 0.00 | 0.00 |
September | 226.09 | 0.04 | 226.05 | 243.97 | 157.71 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 143.13 | 294.25 | 0.00 | 0.00 | 0.00 |
November | 137.24 | 0.00 | 137.24 | 36.95 | 444.20 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.54 | 564.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.46 | 3.89 | 220.57 | 200.77 | 310.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.54 | 52.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.30 | 18.82 | 331.48 | 490.52 | 607.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.36 | 588.06 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 16.51 | 607.98 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 83.79 | 402.16 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 169.20 | 285.20 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 325.90 | 173.90 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 444.47 | 95.64 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 490.54 | 52.50 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 427.05 | 74.58 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 243.98 | 157.72 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 143.14 | 294.27 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 36.95 | 444.23 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.54 | 564.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 200.78 | 310.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.54 | 52.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 490.54 | 607.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.24 | 0.00 | 109.24 | 8.36 | 588.06 | 0.00 | 0.00 | 0.00 |
February | 149.48 | 0.00 | 149.48 | 16.51 | 607.98 | 0.00 | 0.00 | 0.00 |
March | 207.30 | 0.00 | 207.30 | 83.79 | 402.16 | 0.00 | 0.00 | 0.00 |
April | 248.99 | 0.71 | 248.28 | 169.20 | 285.20 | 0.00 | 0.00 | 0.00 |
May | 330.33 | 11.01 | 319.33 | 325.90 | 173.90 | 0.00 | 0.00 | 0.00 |
June | 350.32 | 18.82 | 331.49 | 444.47 | 95.64 | 0.00 | 0.00 | 0.00 |
July | 338.55 | 12.24 | 326.30 | 490.54 | 52.50 | 0.00 | 0.00 | 0.00 |
August | 299.94 | 3.57 | 296.37 | 427.05 | 74.58 | 0.00 | 0.00 | 0.00 |
September | 226.10 | 0.04 | 226.06 | 243.98 | 157.72 | 0.00 | 0.00 | 0.00 |
October | 195.67 | 0.00 | 195.67 | 143.14 | 294.27 | 0.00 | 0.00 | 0.00 |
November | 137.25 | 0.00 | 137.25 | 36.95 | 444.23 | 0.00 | 0.00 | 0.00 |
December | 95.28 | 0.00 | 95.28 | 4.54 | 564.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 224.47 | 3.89 | 220.58 | 200.78 | 310.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 95.28 | 0.00 | 95.28 | 4.54 | 52.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 350.32 | 18.82 | 331.49 | 490.54 | 607.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 439.00 | 176.00 | 263.00 | 280.57 | 1063.00 | 0.00 | 0.00 | 0.00 |
February | 680.80 | 317.59 | 363.21 | 491.38 | 1072.04 | 0.00 | 0.00 | 0.00 |
March | 868.49 | 369.37 | 499.12 | 779.42 | 767.09 | 0.00 | 0.00 | 0.00 |
April | 1042.25 | 456.54 | 585.71 | 1079.20 | 553.06 | 0.00 | 0.00 | 0.00 |
May | 1264.03 | 505.18 | 758.85 | 1492.18 | 354.49 | 0.00 | 0.00 | 0.00 |
June | 1171.49 | 424.07 | 747.42 | 1549.77 | 195.52 | 0.00 | 0.00 | 0.00 |
July | 1176.62 | 424.61 | 752.01 | 1681.56 | 109.45 | 0.00 | 0.00 | 0.00 |
August | 1324.90 | 597.39 | 727.50 | 1878.79 | 153.58 | 0.00 | 0.00 | 0.00 |
September | 988.12 | 443.33 | 544.79 | 1239.19 | 305.11 | 0.00 | 0.00 | 0.00 |
October | 895.80 | 406.01 | 489.80 | 994.25 | 564.85 | 0.00 | 0.00 | 0.00 |
November | 553.98 | 212.73 | 341.25 | 440.74 | 820.84 | 0.00 | 0.00 | 0.00 |
December | 431.58 | 202.64 | 228.94 | 293.56 | 1016.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 904.52 | 378.38 | 526.14 | 1020.37 | 578.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 431.58 | 176.00 | 228.94 | 280.57 | 109.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1324.90 | 597.39 | 758.85 | 1878.79 | 1072.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.36 | 6.96 | 10.40 | 11.09 | 42.03 | 0.00 | 0.00 | 0.00 |
February | 26.92 | 12.56 | 14.36 | 19.43 | 42.39 | 0.00 | 0.00 | 0.00 |
March | 34.34 | 14.60 | 19.73 | 30.82 | 30.33 | 0.00 | 0.00 | 0.00 |
April | 41.21 | 18.05 | 23.16 | 42.67 | 21.87 | 0.00 | 0.00 | 0.00 |
May | 49.98 | 19.97 | 30.00 | 59.00 | 14.02 | 0.00 | 0.00 | 0.00 |
June | 46.32 | 16.77 | 29.55 | 61.28 | 7.73 | 0.00 | 0.00 | 0.00 |
July | 46.52 | 16.79 | 29.73 | 66.49 | 4.33 | 0.00 | 0.00 | 0.00 |
August | 52.39 | 23.62 | 28.76 | 74.29 | 6.07 | 0.00 | 0.00 | 0.00 |
September | 39.07 | 17.53 | 21.54 | 49.00 | 12.06 | 0.00 | 0.00 | 0.00 |
October | 35.42 | 16.05 | 19.37 | 39.31 | 22.33 | 0.00 | 0.00 | 0.00 |
November | 21.90 | 8.41 | 13.49 | 17.43 | 32.46 | 0.00 | 0.00 | 0.00 |
December | 17.06 | 8.01 | 9.05 | 11.61 | 40.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.76 | 14.96 | 20.80 | 40.34 | 22.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.06 | 6.96 | 9.05 | 11.09 | 4.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.39 | 23.62 | 30.00 | 74.29 | 42.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 575.33 | 532.37 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 768.34 | 546.24 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 734.61 | 402.71 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 589.77 | 298.39 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 551.52 | 187.62 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 589.85 | 103.81 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 681.08 | 56.08 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 911.91 | 84.07 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 876.03 | 168.61 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1117.77 | 307.84 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 667.39 | 423.98 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 639.61 | 510.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 725.40 | 300.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 551.52 | 56.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1117.77 | 546.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.09 | 370.03 | 195.07 | 575.33 | 532.37 | 0.00 | 0.00 | 0.00 |
February | 745.34 | 493.35 | 251.99 | 768.34 | 546.24 | 0.00 | 0.00 | 0.00 |
March | 672.44 | 373.21 | 299.23 | 734.61 | 402.71 | 0.00 | 0.00 | 0.00 |
April | 521.79 | 206.33 | 315.46 | 589.77 | 298.39 | 0.00 | 0.00 | 0.00 |
May | 457.27 | 95.38 | 361.89 | 551.52 | 187.62 | 0.00 | 0.00 | 0.00 |
June | 429.14 | 65.60 | 363.54 | 589.85 | 103.81 | 0.00 | 0.00 | 0.00 |
July | 449.82 | 78.13 | 371.69 | 681.08 | 56.08 | 0.00 | 0.00 | 0.00 |
August | 600.69 | 222.80 | 377.88 | 911.91 | 84.07 | 0.00 | 0.00 | 0.00 |
September | 651.76 | 337.11 | 314.64 | 876.03 | 168.61 | 0.00 | 0.00 | 0.00 |
October | 892.85 | 559.88 | 332.97 | 1117.77 | 307.84 | 0.00 | 0.00 | 0.00 |
November | 619.11 | 371.81 | 247.31 | 667.39 | 423.98 | 0.00 | 0.00 | 0.00 |
December | 612.48 | 434.82 | 177.66 | 639.61 | 510.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.80 | 299.73 | 301.07 | 725.40 | 300.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.14 | 65.60 | 177.66 | 551.52 | 56.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.85 | 559.88 | 377.88 | 1117.77 | 546.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 565.06 | 370.00 | 195.06 | 575.30 | 532.34 | 0.00 | 0.00 | 0.00 |
February | 745.29 | 493.32 | 251.97 | 768.29 | 546.20 | 0.00 | 0.00 | 0.00 |
March | 672.40 | 373.19 | 299.21 | 734.56 | 402.68 | 0.00 | 0.00 | 0.00 |
April | 521.76 | 206.32 | 315.44 | 589.74 | 298.37 | 0.00 | 0.00 | 0.00 |
May | 457.24 | 95.37 | 361.87 | 551.49 | 187.61 | 0.00 | 0.00 | 0.00 |
June | 429.11 | 65.59 | 363.52 | 589.82 | 103.80 | 0.00 | 0.00 | 0.00 |
July | 449.79 | 78.13 | 371.67 | 681.04 | 56.08 | 0.00 | 0.00 | 0.00 |
August | 600.65 | 222.79 | 377.86 | 911.85 | 84.07 | 0.00 | 0.00 | 0.00 |
September | 651.71 | 337.09 | 314.62 | 875.98 | 168.60 | 0.00 | 0.00 | 0.00 |
October | 892.79 | 559.84 | 332.95 | 1117.70 | 307.82 | 0.00 | 0.00 | 0.00 |
November | 619.07 | 371.78 | 247.29 | 667.35 | 423.95 | 0.00 | 0.00 | 0.00 |
December | 612.44 | 434.79 | 177.65 | 639.57 | 510.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 600.77 | 299.71 | 301.06 | 725.36 | 300.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 429.11 | 65.59 | 177.65 | 551.49 | 56.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 892.79 | 559.84 | 377.86 | 1117.70 | 546.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 433.40 | 177.52 | 255.88 | 279.89 | 1084.58 | 0.00 | 0.00 | 0.00 |
February | 639.11 | 280.70 | 358.41 | 457.50 | 1116.94 | 0.00 | 0.00 | 0.00 |
March | 943.72 | 435.69 | 508.03 | 876.63 | 768.62 | 0.00 | 0.00 | 0.00 |
April | 1031.44 | 441.32 | 590.11 | 1080.82 | 571.88 | 0.00 | 0.00 | 0.00 |
May | 1201.52 | 456.29 | 745.23 | 1423.76 | 369.11 | 0.00 | 0.00 | 0.00 |
June | 1315.03 | 530.39 | 784.64 | 1751.32 | 210.85 | 0.00 | 0.00 | 0.00 |
July | 1231.60 | 463.78 | 767.82 | 1757.96 | 118.89 | 0.00 | 0.00 | 0.00 |
August | 1362.48 | 630.74 | 731.74 | 1941.22 | 167.34 | 0.00 | 0.00 | 0.00 |
September | 967.25 | 422.69 | 544.57 | 1226.21 | 319.89 | 0.00 | 0.00 | 0.00 |
October | 958.96 | 466.32 | 492.64 | 1085.28 | 585.42 | 0.00 | 0.00 | 0.00 |
November | 450.32 | 130.15 | 320.18 | 305.08 | 837.13 | 0.00 | 0.00 | 0.00 |
December | 400.55 | 173.32 | 227.23 | 259.83 | 1042.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 913.19 | 384.96 | 528.24 | 1041.30 | 596.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.55 | 130.15 | 227.23 | 259.83 | 118.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1362.48 | 630.74 | 784.64 | 1941.22 | 1116.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.14 | 7.02 | 10.12 | 11.07 | 42.88 | 0.00 | 0.00 | 0.00 |
February | 25.27 | 11.10 | 14.17 | 18.09 | 44.16 | 0.00 | 0.00 | 0.00 |
March | 37.31 | 17.23 | 20.09 | 34.66 | 30.39 | 0.00 | 0.00 | 0.00 |
April | 40.78 | 17.45 | 23.33 | 42.73 | 22.61 | 0.00 | 0.00 | 0.00 |
May | 47.51 | 18.04 | 29.47 | 56.29 | 14.59 | 0.00 | 0.00 | 0.00 |
June | 51.99 | 20.97 | 31.02 | 69.25 | 8.34 | 0.00 | 0.00 | 0.00 |
July | 48.70 | 18.34 | 30.36 | 69.51 | 4.70 | 0.00 | 0.00 | 0.00 |
August | 53.87 | 24.94 | 28.93 | 76.75 | 6.62 | 0.00 | 0.00 | 0.00 |
September | 38.24 | 16.71 | 21.53 | 48.48 | 12.65 | 0.00 | 0.00 | 0.00 |
October | 37.92 | 18.44 | 19.48 | 42.91 | 23.15 | 0.00 | 0.00 | 0.00 |
November | 17.81 | 5.15 | 12.66 | 12.06 | 33.10 | 0.00 | 0.00 | 0.00 |
December | 15.84 | 6.85 | 8.98 | 10.27 | 41.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.11 | 15.22 | 20.89 | 41.17 | 23.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.84 | 5.15 | 8.98 | 10.27 | 4.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.87 | 24.94 | 31.02 | 76.75 | 44.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.71 | 0.00 | 327.71 | 23.21 | 1773.83 | 0.00 | 0.00 | 0.00 |
February | 448.46 | 0.00 | 448.46 | 44.27 | 1854.83 | 0.00 | 0.00 | 0.00 |
March | 621.90 | 0.00 | 621.90 | 226.71 | 1259.51 | 0.00 | 0.00 | 0.00 |
April | 746.98 | 2.12 | 744.86 | 472.41 | 907.75 | 0.00 | 0.00 | 0.00 |
May | 991.01 | 33.02 | 957.99 | 931.23 | 561.30 | 0.00 | 0.00 | 0.00 |
June | 1050.95 | 56.47 | 994.48 | 1308.18 | 304.88 | 0.00 | 0.00 | 0.00 |
July | 1015.65 | 36.73 | 978.92 | 1451.97 | 170.74 | 0.00 | 0.00 | 0.00 |
August | 899.81 | 10.71 | 889.10 | 1271.41 | 231.48 | 0.00 | 0.00 | 0.00 |
September | 678.31 | 0.13 | 678.18 | 727.48 | 471.31 | 0.00 | 0.00 | 0.00 |
October | 587.03 | 0.00 | 587.03 | 428.46 | 868.42 | 0.00 | 0.00 | 0.00 |
November | 411.74 | 0.00 | 411.74 | 112.22 | 1299.40 | 0.00 | 0.00 | 0.00 |
December | 285.85 | 0.00 | 285.85 | 13.53 | 1676.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 673.41 | 11.66 | 661.75 | 587.92 | 943.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 285.85 | 0.00 | 285.85 | 13.53 | 170.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1050.95 | 56.47 | 994.48 | 1451.97 | 1854.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.37 | 182.97 | 273.40 | 285.79 | 1103.11 | 0.00 | 0.00 | 0.00 |
February | 707.73 | 330.16 | 377.57 | 498.89 | 1120.29 | 0.00 | 0.00 | 0.00 |
March | 902.84 | 383.99 | 518.86 | 788.35 | 816.11 | 0.00 | 0.00 | 0.00 |
April | 1083.48 | 474.60 | 608.88 | 1098.16 | 590.43 | 0.00 | 0.00 | 0.00 |
May | 1314.03 | 525.17 | 788.86 | 1522.82 | 383.47 | 0.00 | 0.00 | 0.00 |
June | 1217.83 | 440.84 | 776.98 | 1592.94 | 208.92 | 0.00 | 0.00 | 0.00 |
July | 1223.16 | 441.41 | 781.75 | 1734.12 | 116.44 | 0.00 | 0.00 | 0.00 |
August | 1377.31 | 621.03 | 756.28 | 1943.72 | 156.18 | 0.00 | 0.00 | 0.00 |
September | 1027.20 | 460.87 | 566.34 | 1281.52 | 306.78 | 0.00 | 0.00 | 0.00 |
October | 931.23 | 422.07 | 509.17 | 1030.20 | 563.87 | 0.00 | 0.00 | 0.00 |
November | 575.90 | 221.15 | 354.75 | 458.58 | 820.23 | 0.00 | 0.00 | 0.00 |
December | 448.66 | 210.66 | 237.99 | 302.93 | 1035.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 940.30 | 393.35 | 546.95 | 1048.63 | 598.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 448.66 | 182.97 | 237.99 | 285.79 | 116.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1377.31 | 621.03 | 788.86 | 1943.72 | 1120.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1695.32 | 1110.10 | 585.21 | 1685.46 | 1599.52 | 0.00 | 0.00 | 0.00 |
February | 2236.06 | 1480.09 | 755.97 | 2253.47 | 1635.62 | 0.00 | 0.00 | 0.00 |
March | 2017.35 | 1119.66 | 897.69 | 2151.83 | 1233.83 | 0.00 | 0.00 | 0.00 |
April | 1565.39 | 619.00 | 946.39 | 1722.28 | 936.93 | 0.00 | 0.00 | 0.00 |
May | 1371.84 | 286.14 | 1085.69 | 1601.56 | 604.56 | 0.00 | 0.00 | 0.00 |
June | 1287.43 | 196.80 | 1090.63 | 1742.20 | 327.20 | 0.00 | 0.00 | 0.00 |
July | 1349.48 | 234.40 | 1115.08 | 2025.59 | 176.26 | 0.00 | 0.00 | 0.00 |
August | 1802.08 | 668.42 | 1133.66 | 2726.72 | 246.11 | 0.00 | 0.00 | 0.00 |
September | 1955.30 | 1011.36 | 943.94 | 2619.56 | 483.34 | 0.00 | 0.00 | 0.00 |
October | 2678.59 | 1679.67 | 998.92 | 3342.84 | 867.96 | 0.00 | 0.00 | 0.00 |
November | 1857.37 | 1115.44 | 741.93 | 1984.34 | 1225.18 | 0.00 | 0.00 | 0.00 |
December | 1837.47 | 1304.48 | 532.99 | 1893.55 | 1496.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1802.44 | 899.21 | 903.23 | 2146.31 | 898.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1287.43 | 196.80 | 532.99 | 1601.56 | 176.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2678.59 | 1679.67 | 1133.66 | 3342.84 | 1635.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.54 | 184.54 | 266.00 | 284.34 | 1127.62 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 291.80 | 372.58 | 463.10 | 1168.07 | 0.00 | 0.00 | 0.00 |
March | 981.04 | 452.92 | 528.12 | 891.25 | 812.79 | 0.00 | 0.00 | 0.00 |
April | 1072.24 | 458.78 | 613.45 | 1101.65 | 609.67 | 0.00 | 0.00 | 0.00 |
May | 1249.05 | 474.34 | 774.71 | 1455.65 | 398.08 | 0.00 | 0.00 | 0.00 |
June | 1367.04 | 551.37 | 815.68 | 1806.05 | 221.53 | 0.00 | 0.00 | 0.00 |
July | 1280.31 | 482.12 | 798.18 | 1816.54 | 124.36 | 0.00 | 0.00 | 0.00 |
August | 1416.37 | 655.69 | 760.68 | 2012.18 | 168.57 | 0.00 | 0.00 | 0.00 |
September | 1005.51 | 439.41 | 566.10 | 1271.78 | 321.77 | 0.00 | 0.00 | 0.00 |
October | 996.89 | 484.76 | 512.13 | 1127.46 | 582.52 | 0.00 | 0.00 | 0.00 |
November | 468.13 | 135.29 | 332.84 | 317.41 | 841.11 | 0.00 | 0.00 | 0.00 |
December | 416.40 | 180.18 | 236.22 | 267.01 | 1064.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 949.31 | 400.18 | 549.13 | 1072.22 | 616.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 416.40 | 135.29 | 236.22 | 267.01 | 124.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1416.37 | 655.69 | 815.68 | 2012.18 | 1168.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 72890164.09 | 0.452746E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.121176E+09 | 0.425371E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.642048E+09 | 0.316224E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.126206E+10 | 0.220210E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.251139E+10 | 0.143983E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.338234E+10 | 0.765029E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.386968E+10 | 0.447198E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.339393E+10 | 0.599332E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.189541E+10 | 0.115621E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.119140E+10 | 0.216591E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.333235E+09 | 0.310438E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 48378190.66 | 0.419256E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.187239E+11 | 0.280160E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 48378190.66 | 0.447198E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.386968E+10 | 0.452746E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.785026E+09 | 0.281353E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.123944E+10 | 0.256553E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.214733E+10 | 0.204858E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.287776E+10 | 0.143909E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.409250E+10 | 0.986406E+09 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.413001E+10 | 0.524264E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.463877E+10 | 0.304120E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.520425E+10 | 0.404353E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.333344E+10 | 0.755733E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.279184E+10 | 0.141512E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.123380E+10 | 0.196310E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.842207E+09 | 0.258594E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.333164E+11 | 0.178058E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.785026E+09 | 0.304120E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.520425E+10 | 0.281353E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.454695E+10 | 0.406897E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.549932E+10 | 0.374162E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.579906E+10 | 0.310049E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.449313E+10 | 0.228165E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.429674E+10 | 0.154965E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.450342E+10 | 0.819683E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.540288E+10 | 0.460217E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.728462E+10 | 0.637045E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.679145E+10 | 0.119231E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.897846E+10 | 0.218725E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.520449E+10 | 0.294432E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.512766E+10 | 0.374258E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.679282E+11 | 0.267258E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.429674E+10 | 0.460217E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.897846E+10 | 0.406897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.773277E+09 | 0.287652E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.113609E+10 | 0.267703E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.241162E+10 | 0.204109E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.287721E+10 | 0.148173E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.390359E+10 | 0.102047E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.467080E+10 | 0.554915E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.484929E+10 | 0.324615E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.537716E+10 | 0.436877E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.329967E+10 | 0.792304E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.304397E+10 | 0.145938E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.856570E+09 | 0.201324E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.734208E+09 | 0.266124E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.339335E+11 | 0.183394E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.734208E+09 | 0.324615E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.537716E+10 | 0.287652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292566E+09 | 0.00 | 0.292566E+09 | 22391010.02 | 0.157495E+10 |
February | 0.361619E+09 | 0.00 | 0.361619E+09 | 39937361.29 | 0.147074E+10 |
March | 0.555204E+09 | 0.00 | 0.555204E+09 | 0.224423E+09 | 0.107708E+10 |
April | 0.645364E+09 | 1835613.72 | 0.643528E+09 | 0.438561E+09 | 0.739181E+09 |
May | 0.884732E+09 | 29479770.21 | 0.855252E+09 | 0.872860E+09 | 0.465759E+09 |
June | 0.907981E+09 | 48789636.46 | 0.859192E+09 | 0.115202E+10 | 0.247885E+09 |
July | 0.906725E+09 | 32790217.14 | 0.873935E+09 | 0.131381E+10 | 0.140596E+09 |
August | 0.803315E+09 | 9560583.93 | 0.793755E+09 | 0.114375E+10 | 0.199737E+09 |
September | 0.586032E+09 | 109739.98 | 0.585922E+09 | 0.632361E+09 | 0.408794E+09 |
October | 0.524074E+09 | 0.00 | 0.524074E+09 | 0.383367E+09 | 0.788121E+09 |
November | 0.355730E+09 | 0.00 | 0.355730E+09 | 95783307.80 | 0.115136E+10 |
December | 0.255195E+09 | 0.00 | 0.255195E+09 | 12171345.84 | 0.151186E+10 |
Annual Sum or Average | 0.707854E+10 | 0.122566E+09 | 0.695597E+10 | 0.633144E+10 | 0.977607E+10 |
Minimum of Months | 0.255195E+09 | 0.00 | 0.255195E+09 | 12171345.84 | 0.140596E+09 |
Maximum of Months | 0.907981E+09 | 48789636.46 | 0.873935E+09 | 0.131381E+10 | 0.157495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 22389616.17 | 0.157505E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 39936407.32 | 0.147083E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.224426E+09 | 0.107715E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.438573E+09 | 0.739227E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.872888E+09 | 0.465787E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115206E+10 | 0.247899E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131386E+10 | 0.140603E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114380E+10 | 0.199746E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.632385E+09 | 0.408817E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.383379E+09 | 0.788168E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 95782871.42 | 0.115144E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 12170570.00 | 0.151196E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.633166E+10 | 0.977668E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 12170570.00 | 0.140603E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131386E+10 | 0.157505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292577E+09 | 0.00 | 0.292577E+09 | 22389616.17 | 0.157505E+10 |
February | 0.361633E+09 | 0.00 | 0.361633E+09 | 39936407.32 | 0.147083E+10 |
March | 0.555226E+09 | 0.00 | 0.555226E+09 | 0.224426E+09 | 0.107715E+10 |
April | 0.645390E+09 | 1835663.06 | 0.643554E+09 | 0.438573E+09 | 0.739227E+09 |
May | 0.884767E+09 | 29480562.63 | 0.855286E+09 | 0.872888E+09 | 0.465787E+09 |
June | 0.908017E+09 | 48790947.93 | 0.859226E+09 | 0.115206E+10 | 0.247899E+09 |
July | 0.906761E+09 | 32791098.55 | 0.873970E+09 | 0.131386E+10 | 0.140603E+09 |
August | 0.803349E+09 | 9560840.92 | 0.793788E+09 | 0.114380E+10 | 0.199746E+09 |
September | 0.586056E+09 | 109742.93 | 0.585946E+09 | 0.632385E+09 | 0.408817E+09 |
October | 0.524095E+09 | 0.00 | 0.524095E+09 | 0.383379E+09 | 0.788168E+09 |
November | 0.355744E+09 | 0.00 | 0.355744E+09 | 95782871.42 | 0.115144E+10 |
December | 0.255205E+09 | 0.00 | 0.255205E+09 | 12170570.00 | 0.151196E+10 |
Annual Sum or Average | 0.707882E+10 | 0.122569E+09 | 0.695625E+10 | 0.633166E+10 | 0.977668E+10 |
Minimum of Months | 0.255205E+09 | 0.00 | 0.255205E+09 | 12170570.00 | 0.140603E+09 |
Maximum of Months | 0.908017E+09 | 48790947.93 | 0.873970E+09 | 0.131386E+10 | 0.157505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117583E+10 | 0.471411E+09 | 0.704419E+09 | 0.751469E+09 | 0.284713E+10 |
February | 0.164699E+10 | 0.768321E+09 | 0.878673E+09 | 0.118876E+10 | 0.259349E+10 |
March | 0.232617E+10 | 0.989331E+09 | 0.133684E+10 | 0.208760E+10 | 0.205458E+10 |
April | 0.270151E+10 | 0.118334E+10 | 0.151817E+10 | 0.279728E+10 | 0.143354E+10 |
May | 0.338558E+10 | 0.135308E+10 | 0.203250E+10 | 0.399666E+10 | 0.949472E+09 |
June | 0.303650E+10 | 0.109919E+10 | 0.193731E+10 | 0.401700E+10 | 0.506781E+09 |
July | 0.315145E+10 | 0.113728E+10 | 0.201418E+10 | 0.450389E+10 | 0.293155E+09 |
August | 0.354861E+10 | 0.160006E+10 | 0.194855E+10 | 0.503215E+10 | 0.411336E+09 |
September | 0.256120E+10 | 0.114910E+10 | 0.141209E+10 | 0.321198E+10 | 0.790836E+09 |
October | 0.239931E+10 | 0.108745E+10 | 0.131187E+10 | 0.266299E+10 | 0.151291E+10 |
November | 0.143592E+10 | 0.551408E+09 | 0.884517E+09 | 0.114241E+10 | 0.212763E+10 |
December | 0.115596E+10 | 0.542764E+09 | 0.613192E+09 | 0.786274E+09 | 0.272272E+10 |
Annual Sum or Average | 0.285250E+11 | 0.119327E+11 | 0.165923E+11 | 0.321785E+11 | 0.182436E+11 |
Minimum of Months | 0.115596E+10 | 0.471411E+09 | 0.613192E+09 | 0.751469E+09 | 0.293155E+09 |
Maximum of Months | 0.354861E+10 | 0.160006E+10 | 0.203250E+10 | 0.503215E+10 | 0.284713E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 46491248.53 | 18639173.47 | 27852075.06 | 29712416.09 | 0.112573E+09 |
February | 65120688.91 | 30378734.06 | 34741954.85 | 47002370.02 | 0.102544E+09 |
March | 91974516.67 | 39117249.61 | 52857267.06 | 82541941.85 | 81236190.30 |
April | 0.106815E+09 | 46788213.91 | 60027079.77 | 0.110602E+09 | 56680715.97 |
May | 0.133863E+09 | 53499380.13 | 80363332.10 | 0.158024E+09 | 37541257.00 |
June | 0.120060E+09 | 43460819.36 | 76599620.23 | 0.158829E+09 | 20037669.70 |
July | 0.124606E+09 | 44966859.13 | 79638710.84 | 0.178080E+09 | 11591076.27 |
August | 0.140309E+09 | 63265002.36 | 77043847.34 | 0.198967E+09 | 16263853.66 |
September | 0.101267E+09 | 45434569.04 | 55832907.16 | 0.126999E+09 | 31268930.21 |
October | 94866683.40 | 42996643.49 | 51870039.91 | 0.105292E+09 | 59818919.60 |
November | 56775167.18 | 21802171.41 | 34972995.77 | 45169672.97 | 84124462.31 |
December | 45705453.17 | 21460412.81 | 24245040.36 | 31088569.70 | 0.107654E+09 |
Annual Sum or Average | 0.112785E+10 | 0.471809E+09 | 0.656045E+09 | 0.127231E+10 | 0.721334E+09 |
Minimum of Months | 45705453.17 | 18639173.47 | 24245040.36 | 29712416.09 | 11591076.27 |
Maximum of Months | 0.140309E+09 | 63265002.36 | 80363332.10 | 0.198967E+09 | 0.112573E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154097E+10 | 0.142591E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.185876E+10 | 0.132146E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.196758E+10 | 0.107861E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.152869E+10 | 0.773416E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.147719E+10 | 0.502531E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.152890E+10 | 0.269073E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182422E+10 | 0.150209E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244246E+10 | 0.225175E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227067E+10 | 0.437029E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299384E+10 | 0.824531E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.172987E+10 | 0.109896E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171313E+10 | 0.136759E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.228763E+11 | 0.947450E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.147719E+10 | 0.150209E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299384E+10 | 0.142591E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151355E+10 | 0.991081E+09 | 0.522470E+09 | 0.154097E+10 | 0.142591E+10 |
February | 0.180313E+10 | 0.119352E+10 | 0.609607E+09 | 0.185876E+10 | 0.132146E+10 |
March | 0.180106E+10 | 0.999616E+09 | 0.801445E+09 | 0.196758E+10 | 0.107861E+10 |
April | 0.135248E+10 | 0.534808E+09 | 0.817672E+09 | 0.152869E+10 | 0.773416E+09 |
May | 0.122476E+10 | 0.255463E+09 | 0.969297E+09 | 0.147719E+10 | 0.502531E+09 |
June | 0.111232E+10 | 0.170029E+09 | 0.942296E+09 | 0.152890E+10 | 0.269073E+09 |
July | 0.120480E+10 | 0.209272E+09 | 0.995531E+09 | 0.182422E+10 | 0.150209E+09 |
August | 0.160888E+10 | 0.596755E+09 | 0.101212E+10 | 0.244246E+10 | 0.225175E+09 |
September | 0.168935E+10 | 0.873796E+09 | 0.815553E+09 | 0.227067E+10 | 0.437029E+09 |
October | 0.239140E+10 | 0.149958E+10 | 0.891826E+09 | 0.299384E+10 | 0.824531E+09 |
November | 0.160474E+10 | 0.963721E+09 | 0.641020E+09 | 0.172987E+10 | 0.109896E+10 |
December | 0.164046E+10 | 0.116462E+10 | 0.475845E+09 | 0.171313E+10 | 0.136759E+10 |
Annual Sum or Average | 0.189469E+11 | 0.945226E+10 | 0.949469E+10 | 0.228763E+11 | 0.947450E+10 |
Minimum of Months | 0.111232E+10 | 0.170029E+09 | 0.475845E+09 | 0.147719E+10 | 0.150209E+09 |
Maximum of Months | 0.239140E+10 | 0.149958E+10 | 0.101212E+10 | 0.299384E+10 | 0.142591E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151345E+10 | 0.991018E+09 | 0.522437E+09 | 0.154087E+10 | 0.142582E+10 |
February | 0.180302E+10 | 0.119345E+10 | 0.609569E+09 | 0.185864E+10 | 0.132138E+10 |
March | 0.180095E+10 | 0.999553E+09 | 0.801394E+09 | 0.196746E+10 | 0.107855E+10 |
April | 0.135240E+10 | 0.534774E+09 | 0.817621E+09 | 0.152860E+10 | 0.773367E+09 |
May | 0.122468E+10 | 0.255447E+09 | 0.969236E+09 | 0.147710E+10 | 0.502499E+09 |
June | 0.111225E+10 | 0.170018E+09 | 0.942237E+09 | 0.152880E+10 | 0.269056E+09 |
July | 0.120473E+10 | 0.209259E+09 | 0.995468E+09 | 0.182410E+10 | 0.150200E+09 |
August | 0.160878E+10 | 0.596718E+09 | 0.101206E+10 | 0.244231E+10 | 0.225161E+09 |
September | 0.168924E+10 | 0.873741E+09 | 0.815501E+09 | 0.227053E+10 | 0.437001E+09 |
October | 0.239125E+10 | 0.149948E+10 | 0.891770E+09 | 0.299365E+10 | 0.824478E+09 |
November | 0.160464E+10 | 0.963660E+09 | 0.640979E+09 | 0.172977E+10 | 0.109889E+10 |
December | 0.164036E+10 | 0.116454E+10 | 0.475815E+09 | 0.171303E+10 | 0.136750E+10 |
Annual Sum or Average | 0.189457E+11 | 0.945166E+10 | 0.949409E+10 | 0.228749E+11 | 0.947390E+10 |
Minimum of Months | 0.111225E+10 | 0.170018E+09 | 0.475815E+09 | 0.147710E+10 | 0.150200E+09 |
Maximum of Months | 0.239125E+10 | 0.149948E+10 | 0.101206E+10 | 0.299365E+10 | 0.142582E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116081E+10 | 0.475470E+09 | 0.685340E+09 | 0.749645E+09 | 0.290493E+10 |
February | 0.154612E+10 | 0.679061E+09 | 0.867062E+09 | 0.110679E+10 | 0.270211E+10 |
March | 0.252765E+10 | 0.116694E+10 | 0.136071E+10 | 0.234796E+10 | 0.205868E+10 |
April | 0.267349E+10 | 0.114391E+10 | 0.152958E+10 | 0.280149E+10 | 0.148232E+10 |
May | 0.321816E+10 | 0.122213E+10 | 0.199603E+10 | 0.381341E+10 | 0.988637E+09 |
June | 0.340856E+10 | 0.137476E+10 | 0.203379E+10 | 0.453941E+10 | 0.546523E+09 |
July | 0.329871E+10 | 0.124219E+10 | 0.205652E+10 | 0.470851E+10 | 0.318440E+09 |
August | 0.364927E+10 | 0.168936E+10 | 0.195990E+10 | 0.519936E+10 | 0.448217E+09 |
September | 0.250712E+10 | 0.109560E+10 | 0.141152E+10 | 0.317834E+10 | 0.829146E+09 |
October | 0.256847E+10 | 0.124898E+10 | 0.131949E+10 | 0.290682E+10 | 0.156799E+10 |
November | 0.116724E+10 | 0.337339E+09 | 0.829900E+09 | 0.790766E+09 | 0.216984E+10 |
December | 0.107284E+10 | 0.464221E+09 | 0.608622E+09 | 0.695924E+09 | 0.279132E+10 |
Annual Sum or Average | 0.287984E+11 | 0.121400E+11 | 0.166585E+11 | 0.328384E+11 | 0.188082E+11 |
Minimum of Months | 0.107284E+10 | 0.337339E+09 | 0.608622E+09 | 0.695924E+09 | 0.318440E+09 |
Maximum of Months | 0.364927E+10 | 0.168936E+10 | 0.205652E+10 | 0.519936E+10 | 0.290493E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45897219.76 | 18799578.49 | 27097641.27 | 29640132.60 | 0.114858E+09 |
February | 61132159.56 | 26849383.05 | 34282776.51 | 43761232.92 | 0.106839E+09 |
March | 99940809.17 | 46139769.68 | 53801039.48 | 92835712.23 | 81398278.75 |
April | 0.105707E+09 | 45229190.01 | 60477938.52 | 0.110768E+09 | 58609633.98 |
May | 0.127243E+09 | 48321638.08 | 78921059.36 | 0.150778E+09 | 39089809.53 |
June | 0.134771E+09 | 54356766.41 | 80414196.70 | 0.179484E+09 | 21609004.14 |
July | 0.130428E+09 | 49114806.49 | 81312788.21 | 0.186170E+09 | 12590808.58 |
August | 0.144288E+09 | 66795753.60 | 77492599.82 | 0.205577E+09 | 17722060.30 |
September | 99128965.29 | 43318956.13 | 55810009.16 | 0.125668E+09 | 32783682.17 |
October | 0.101555E+09 | 49383479.05 | 52171383.98 | 0.114933E+09 | 61997042.25 |
November | 46151441.29 | 13338037.77 | 32813403.52 | 31266048.18 | 85793356.48 |
December | 42419103.52 | 18354807.59 | 24064295.94 | 27516096.76 | 0.110366E+09 |
Annual Sum or Average | 0.113866E+10 | 0.480002E+09 | 0.658659E+09 | 0.129840E+10 | 0.743657E+09 |
Minimum of Months | 42419103.52 | 13338037.77 | 24064295.94 | 27516096.76 | 12590808.58 |
Maximum of Months | 0.144288E+09 | 66795753.60 | 81312788.21 | 0.205577E+09 | 0.114858E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.877739E+09 | 0.00 | 0.877739E+09 | 62165234.45 | 0.475104E+10 |
February | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.107105E+09 | 0.448721E+10 |
March | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.607215E+09 | 0.337346E+10 |
April | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.122448E+10 | 0.235288E+10 |
May | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.249421E+10 | 0.150337E+10 |
June | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.339080E+10 | 0.790251E+09 |
July | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.388895E+10 | 0.457312E+09 |
August | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.340534E+10 | 0.619993E+09 |
September | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.188563E+10 | 0.122163E+10 |
October | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.114759E+10 | 0.232597E+10 |
November | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.290870E+09 | 0.336806E+10 |
December | 0.765622E+09 | 0.00 | 0.765622E+09 | 36243139.54 | 0.448906E+10 |
Annual Sum or Average | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.185406E+11 | 0.297402E+11 |
Minimum of Months | 0.765622E+09 | 0.00 | 0.765622E+09 | 36243139.54 | 0.457312E+09 |
Maximum of Months | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.388895E+10 | 0.475104E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.765460E+09 | 0.295456E+10 |
February | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.120692E+10 | 0.271021E+10 |
March | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.211150E+10 | 0.218586E+10 |
April | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.284643E+10 | 0.153040E+10 |
May | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.407873E+10 | 0.102709E+10 |
June | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.412890E+10 | 0.541521E+09 |
July | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.464466E+10 | 0.311862E+09 |
August | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.520605E+10 | 0.418322E+09 |
September | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.332170E+10 | 0.795182E+09 |
October | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.275928E+10 | 0.151028E+10 |
November | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.118864E+10 | 0.212604E+10 |
December | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.811379E+09 | 0.277458E+10 |
Annual Sum or Average | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.330696E+11 | 0.188859E+11 |
Minimum of Months | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.765460E+09 | 0.311862E+09 |
Maximum of Months | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.520605E+10 | 0.295456E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.451433E+10 | 0.428416E+10 |
February | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.545159E+10 | 0.395689E+10 |
March | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.576346E+10 | 0.330470E+10 |
April | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.446416E+10 | 0.242853E+10 |
May | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.428961E+10 | 0.161926E+10 |
June | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.451579E+10 | 0.848107E+09 |
July | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.542534E+10 | 0.472086E+09 |
August | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.730325E+10 | 0.659190E+09 |
September | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.678989E+10 | 0.125283E+10 |
October | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.895346E+10 | 0.232475E+10 |
November | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.514342E+10 | 0.317567E+10 |
December | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.507168E+10 | 0.400808E+10 |
Annual Sum or Average | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.676860E+11 | 0.283342E+11 |
Minimum of Months | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.428961E+10 | 0.472086E+09 |
Maximum of Months | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.895346E+10 | 0.428416E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.761585E+09 | 0.302023E+10 |
February | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.112033E+10 | 0.282579E+10 |
March | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.238712E+10 | 0.217698E+10 |
April | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.285547E+10 | 0.158027E+10 |
May | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.389880E+10 | 0.106621E+10 |
June | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.468127E+10 | 0.574194E+09 |
July | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.486541E+10 | 0.333073E+09 |
August | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.538943E+10 | 0.451490E+09 |
September | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.329645E+10 | 0.834032E+09 |
October | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.301978E+10 | 0.156023E+10 |
November | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.822730E+09 | 0.218015E+10 |
December | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.715167E+09 | 0.285071E+10 |
Annual Sum or Average | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.338135E+11 | 0.194533E+11 |
Minimum of Months | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.715167E+09 | 0.333073E+09 |
Maximum of Months | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.538943E+10 | 0.302023E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.21 | 1690.36 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 50.09 | 1758.31 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 239.71 | 1180.64 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 486.91 | 849.58 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 937.65 | 537.57 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1304.91 | 295.15 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1444.77 | 166.96 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1267.15 | 223.77 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 731.25 | 446.07 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 444.82 | 808.66 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 128.56 | 1197.68 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 18.06 | 1565.32 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 593.73 | 888.38 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 18.06 | 166.96 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1444.77 | 1758.31 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.09 | 1050.45 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 512.33 | 1060.49 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 801.72 | 764.85 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1110.25 | 555.20 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1527.97 | 368.28 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1593.37 | 202.26 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1731.92 | 113.55 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1943.04 | 150.97 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1286.05 | 291.56 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1042.35 | 528.34 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 476.00 | 757.37 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 314.44 | 965.48 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1056.46 | 564.62 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 293.09 | 113.55 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1943.04 | 1060.49 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1697.63 | 1519.18 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2273.20 | 1546.63 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2165.12 | 1157.59 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1733.46 | 880.27 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1604.22 | 578.57 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1737.43 | 316.24 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2017.20 | 171.83 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2719.76 | 237.85 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2620.16 | 460.00 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3352.17 | 816.63 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 2007.90 | 1135.92 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1914.45 | 1397.32 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2153.99 | 847.47 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1604.22 | 171.83 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3352.17 | 1546.63 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.71 | 1073.97 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 469.61 | 1106.57 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 900.40 | 762.06 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1110.03 | 571.66 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1457.44 | 381.00 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1802.00 | 214.09 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1810.52 | 121.20 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2007.60 | 163.11 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1273.02 | 305.67 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1136.49 | 544.87 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 330.47 | 776.71 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 274.12 | 993.59 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1076.02 | 581.54 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 274.12 | 121.20 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2007.60 | 1106.57 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.08 | 1764.14 | 327.70 | 0.00 | 327.70 | 0.00 | 0.00 |
February | 49.52 | 1823.91 | 448.45 | 0.00 | 448.45 | 0.00 | 0.00 |
March | 251.37 | 1206.46 | 621.88 | 0.00 | 621.88 | 0.00 | 0.00 |
April | 507.60 | 855.57 | 746.97 | 2.12 | 744.84 | 0.00 | 0.00 |
May | 977.69 | 521.70 | 990.99 | 33.02 | 957.97 | 0.00 | 0.00 |
June | 1333.39 | 286.91 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
July | 1471.60 | 157.48 | 1015.62 | 36.73 | 978.90 | 0.00 | 0.00 |
August | 1281.12 | 223.73 | 899.80 | 10.71 | 889.09 | 0.00 | 0.00 |
September | 731.92 | 473.16 | 678.30 | 0.13 | 678.17 | 0.00 | 0.00 |
October | 429.41 | 882.79 | 587.02 | 0.00 | 587.02 | 0.00 | 0.00 |
November | 110.86 | 1332.65 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 13.63 | 1693.47 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Annual Sum or Average | 602.32 | 930.03 | 673.39 | 11.66 | 661.73 | 0.00 | 0.00 |
Minimum of Months | 13.63 | 157.48 | 285.84 | 0.00 | 285.84 | 0.00 | 0.00 |
Maximum of Months | 1471.60 | 1823.91 | 1050.93 | 56.47 | 994.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.66 | 1105.03 | 456.36 | 182.96 | 273.40 | 0.00 | 0.00 |
February | 510.81 | 1114.43 | 707.72 | 330.15 | 377.57 | 0.00 | 0.00 |
March | 810.24 | 797.42 | 902.83 | 383.98 | 518.85 | 0.00 | 0.00 |
April | 1121.87 | 574.93 | 1083.46 | 474.59 | 608.87 | 0.00 | 0.00 |
May | 1551.18 | 368.51 | 1314.01 | 525.15 | 788.85 | 0.00 | 0.00 |
June | 1611.05 | 203.25 | 1217.81 | 440.84 | 776.97 | 0.00 | 0.00 |
July | 1748.05 | 113.78 | 1223.14 | 441.40 | 781.74 | 0.00 | 0.00 |
August | 1953.08 | 159.65 | 1377.28 | 621.02 | 756.27 | 0.00 | 0.00 |
September | 1288.19 | 317.17 | 1027.19 | 460.86 | 566.33 | 0.00 | 0.00 |
October | 1033.56 | 587.19 | 931.22 | 422.06 | 509.16 | 0.00 | 0.00 |
November | 458.17 | 853.30 | 575.89 | 221.15 | 354.74 | 0.00 | 0.00 |
December | 305.17 | 1056.74 | 448.65 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1060.72 | 601.37 | 940.29 | 393.35 | 546.94 | 0.00 | 0.00 |
Minimum of Months | 291.66 | 113.78 | 448.65 | 182.96 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1953.08 | 1114.43 | 1377.28 | 621.02 | 788.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1725.96 | 1597.09 | 1695.25 | 1110.06 | 585.19 | 0.00 | 0.00 |
February | 2304.96 | 1638.68 | 2235.98 | 1480.03 | 755.95 | 0.00 | 0.00 |
March | 2203.78 | 1208.10 | 2017.28 | 1119.62 | 897.66 | 0.00 | 0.00 |
April | 1769.28 | 895.14 | 1565.34 | 618.98 | 946.36 | 0.00 | 0.00 |
May | 1654.53 | 562.86 | 1371.79 | 286.13 | 1085.66 | 0.00 | 0.00 |
June | 1769.52 | 311.42 | 1287.39 | 196.79 | 1090.60 | 0.00 | 0.00 |
July | 2043.21 | 168.24 | 1349.44 | 234.39 | 1115.04 | 0.00 | 0.00 |
August | 2735.68 | 252.21 | 1802.02 | 668.39 | 1133.63 | 0.00 | 0.00 |
September | 2628.04 | 505.81 | 1955.22 | 1011.32 | 943.91 | 0.00 | 0.00 |
October | 3353.25 | 923.51 | 2678.49 | 1679.60 | 998.89 | 0.00 | 0.00 |
November | 2002.13 | 1271.92 | 1857.30 | 1115.39 | 741.91 | 0.00 | 0.00 |
December | 1918.79 | 1531.76 | 1837.40 | 1304.43 | 532.97 | 0.00 | 0.00 |
Annual Sum or Average | 2176.16 | 901.28 | 1802.37 | 899.17 | 903.20 | 0.00 | 0.00 |
Minimum of Months | 1654.53 | 168.24 | 1287.39 | 196.79 | 532.97 | 0.00 | 0.00 |
Maximum of Months | 3353.25 | 1638.68 | 2678.49 | 1679.60 | 1133.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.95 | 1127.46 | 450.53 | 184.54 | 265.99 | 0.00 | 0.00 |
February | 475.59 | 1161.11 | 664.37 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 911.29 | 799.01 | 981.03 | 452.91 | 528.12 | 0.00 | 0.00 |
April | 1123.55 | 594.49 | 1072.22 | 458.77 | 613.45 | 0.00 | 0.00 |
May | 1480.06 | 383.71 | 1249.03 | 474.33 | 774.70 | 0.00 | 0.00 |
June | 1820.56 | 219.19 | 1367.03 | 551.36 | 815.67 | 0.00 | 0.00 |
July | 1827.46 | 123.59 | 1280.29 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2017.97 | 173.96 | 1416.35 | 655.68 | 760.68 | 0.00 | 0.00 |
September | 1274.70 | 332.53 | 1005.50 | 439.40 | 566.10 | 0.00 | 0.00 |
October | 1128.19 | 608.57 | 996.87 | 484.75 | 512.12 | 0.00 | 0.00 |
November | 317.14 | 870.23 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 270.10 | 1083.36 | 416.39 | 180.17 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1082.47 | 619.98 | 949.30 | 400.18 | 549.12 | 0.00 | 0.00 |
Minimum of Months | 270.10 | 123.59 | 416.39 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2017.97 | 1161.11 | 1416.35 | 655.68 | 815.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.21 | 1773.83 | 327.71 | 0.00 | 327.71 | 0.00 | 0.00 |
February | 44.27 | 1854.83 | 448.46 | 0.00 | 448.46 | 0.00 | 0.00 |
March | 226.71 | 1259.51 | 621.90 | 0.00 | 621.90 | 0.00 | 0.00 |
April | 472.41 | 907.75 | 746.98 | 2.12 | 744.86 | 0.00 | 0.00 |
May | 931.23 | 561.30 | 991.01 | 33.02 | 957.99 | 0.00 | 0.00 |
June | 1308.18 | 304.88 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
July | 1451.97 | 170.74 | 1015.65 | 36.73 | 978.92 | 0.00 | 0.00 |
August | 1271.41 | 231.48 | 899.81 | 10.71 | 889.10 | 0.00 | 0.00 |
September | 727.48 | 471.31 | 678.31 | 0.13 | 678.18 | 0.00 | 0.00 |
October | 428.46 | 868.42 | 587.03 | 0.00 | 587.03 | 0.00 | 0.00 |
November | 112.22 | 1299.40 | 411.74 | 0.00 | 411.74 | 0.00 | 0.00 |
December | 13.53 | 1676.02 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Annual Sum or Average | 587.92 | 943.06 | 673.41 | 11.66 | 661.75 | 0.00 | 0.00 |
Minimum of Months | 13.53 | 170.74 | 285.85 | 0.00 | 285.85 | 0.00 | 0.00 |
Maximum of Months | 1451.97 | 1854.83 | 1050.95 | 56.47 | 994.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 285.79 | 1103.11 | 456.37 | 182.97 | 273.40 | 0.00 | 0.00 |
February | 498.89 | 1120.29 | 707.73 | 330.16 | 377.57 | 0.00 | 0.00 |
March | 788.35 | 816.11 | 902.84 | 383.99 | 518.86 | 0.00 | 0.00 |
April | 1098.16 | 590.43 | 1083.48 | 474.60 | 608.88 | 0.00 | 0.00 |
May | 1522.82 | 383.47 | 1314.03 | 525.17 | 788.86 | 0.00 | 0.00 |
June | 1592.94 | 208.92 | 1217.83 | 440.84 | 776.98 | 0.00 | 0.00 |
July | 1734.12 | 116.44 | 1223.16 | 441.41 | 781.75 | 0.00 | 0.00 |
August | 1943.72 | 156.18 | 1377.31 | 621.03 | 756.28 | 0.00 | 0.00 |
September | 1281.52 | 306.78 | 1027.20 | 460.87 | 566.34 | 0.00 | 0.00 |
October | 1030.20 | 563.87 | 931.23 | 422.07 | 509.17 | 0.00 | 0.00 |
November | 458.58 | 820.23 | 575.90 | 221.15 | 354.75 | 0.00 | 0.00 |
December | 302.93 | 1035.91 | 448.66 | 210.66 | 237.99 | 0.00 | 0.00 |
Annual Sum or Average | 1048.63 | 598.87 | 940.30 | 393.35 | 546.95 | 0.00 | 0.00 |
Minimum of Months | 285.79 | 116.44 | 448.66 | 182.97 | 237.99 | 0.00 | 0.00 |
Maximum of Months | 1943.72 | 1120.29 | 1377.31 | 621.03 | 788.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1685.46 | 1599.52 | 1695.32 | 1110.10 | 585.21 | 0.00 | 0.00 |
February | 2253.47 | 1635.62 | 2236.06 | 1480.09 | 755.97 | 0.00 | 0.00 |
March | 2151.83 | 1233.83 | 2017.35 | 1119.66 | 897.69 | 0.00 | 0.00 |
April | 1722.28 | 936.93 | 1565.39 | 619.00 | 946.39 | 0.00 | 0.00 |
May | 1601.56 | 604.56 | 1371.84 | 286.14 | 1085.69 | 0.00 | 0.00 |
June | 1742.20 | 327.20 | 1287.43 | 196.80 | 1090.63 | 0.00 | 0.00 |
July | 2025.59 | 176.26 | 1349.48 | 234.40 | 1115.08 | 0.00 | 0.00 |
August | 2726.72 | 246.11 | 1802.08 | 668.42 | 1133.66 | 0.00 | 0.00 |
September | 2619.56 | 483.34 | 1955.30 | 1011.36 | 943.94 | 0.00 | 0.00 |
October | 3342.84 | 867.96 | 2678.59 | 1679.67 | 998.92 | 0.00 | 0.00 |
November | 1984.34 | 1225.18 | 1857.37 | 1115.44 | 741.93 | 0.00 | 0.00 |
December | 1893.55 | 1496.44 | 1837.47 | 1304.48 | 532.99 | 0.00 | 0.00 |
Annual Sum or Average | 2146.31 | 898.47 | 1802.44 | 899.21 | 903.23 | 0.00 | 0.00 |
Minimum of Months | 1601.56 | 176.26 | 1287.43 | 196.80 | 532.99 | 0.00 | 0.00 |
Maximum of Months | 3342.84 | 1635.62 | 2678.59 | 1679.67 | 1133.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 284.34 | 1127.62 | 450.54 | 184.54 | 266.00 | 0.00 | 0.00 |
February | 463.10 | 1168.07 | 664.38 | 291.80 | 372.58 | 0.00 | 0.00 |
March | 891.25 | 812.79 | 981.04 | 452.92 | 528.12 | 0.00 | 0.00 |
April | 1101.65 | 609.67 | 1072.24 | 458.78 | 613.45 | 0.00 | 0.00 |
May | 1455.65 | 398.08 | 1249.05 | 474.34 | 774.71 | 0.00 | 0.00 |
June | 1806.05 | 221.53 | 1367.04 | 551.37 | 815.68 | 0.00 | 0.00 |
July | 1816.54 | 124.36 | 1280.31 | 482.12 | 798.18 | 0.00 | 0.00 |
August | 2012.18 | 168.57 | 1416.37 | 655.69 | 760.68 | 0.00 | 0.00 |
September | 1271.78 | 321.77 | 1005.51 | 439.41 | 566.10 | 0.00 | 0.00 |
October | 1127.46 | 582.52 | 996.89 | 484.76 | 512.13 | 0.00 | 0.00 |
November | 317.41 | 841.11 | 468.13 | 135.29 | 332.84 | 0.00 | 0.00 |
December | 267.01 | 1064.33 | 416.40 | 180.18 | 236.22 | 0.00 | 0.00 |
Annual Sum or Average | 1072.22 | 616.86 | 949.31 | 400.18 | 549.13 | 0.00 | 0.00 |
Minimum of Months | 267.01 | 124.36 | 416.40 | 135.29 | 236.22 | 0.00 | 0.00 |
Maximum of Months | 2012.18 | 1168.07 | 1416.37 | 655.69 | 815.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 72890164.09 | 0.452746E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.121176E+09 | 0.425371E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.642048E+09 | 0.316224E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.126206E+10 | 0.220210E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.251139E+10 | 0.143983E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.338234E+10 | 0.765029E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.386968E+10 | 0.447198E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.339393E+10 | 0.599332E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.189541E+10 | 0.115621E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.119140E+10 | 0.216591E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.333235E+09 | 0.310438E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 48378190.66 | 0.419256E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187239E+11 | 0.280160E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 48378190.66 | 0.447198E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386968E+10 | 0.452746E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785026E+09 | 0.281353E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.123944E+10 | 0.256553E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.214733E+10 | 0.204858E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.287776E+10 | 0.143909E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.409250E+10 | 0.986406E+09 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.413001E+10 | 0.524264E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.463877E+10 | 0.304120E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.520425E+10 | 0.404353E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.333344E+10 | 0.755733E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.279184E+10 | 0.141512E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.123380E+10 | 0.196310E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.842207E+09 | 0.258594E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333164E+11 | 0.178058E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.785026E+09 | 0.304120E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520425E+10 | 0.281353E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.454695E+10 | 0.406897E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.549932E+10 | 0.374162E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.579906E+10 | 0.310049E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.449313E+10 | 0.228165E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.429674E+10 | 0.154965E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.450342E+10 | 0.819683E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.540288E+10 | 0.460217E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.728462E+10 | 0.637045E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.679145E+10 | 0.119231E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.897846E+10 | 0.218725E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.520449E+10 | 0.294432E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.512766E+10 | 0.374258E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.679282E+11 | 0.267258E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.429674E+10 | 0.460217E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.897846E+10 | 0.406897E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773277E+09 | 0.287652E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.113609E+10 | 0.267703E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.241162E+10 | 0.204109E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.287721E+10 | 0.148173E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.390359E+10 | 0.102047E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.467080E+10 | 0.554915E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.484929E+10 | 0.324615E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.537716E+10 | 0.436877E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.329967E+10 | 0.792304E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.304397E+10 | 0.145938E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.856570E+09 | 0.201324E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.734208E+09 | 0.266124E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.339335E+11 | 0.183394E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.734208E+09 | 0.324615E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.537716E+10 | 0.287652E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 67170242.37 | 0.472506E+10 | 0.877720E+09 | 0.00 | 0.877720E+09 | 0.00 | 0.00 |
February | 0.119810E+09 | 0.441241E+10 | 0.108489E+10 | 0.00 | 0.108489E+10 | 0.00 | 0.00 |
March | 0.673274E+09 | 0.323138E+10 | 0.166566E+10 | 0.00 | 0.166566E+10 | 0.00 | 0.00 |
April | 0.131571E+10 | 0.221764E+10 | 0.193614E+10 | 5506939.83 | 0.193064E+10 | 0.00 | 0.00 |
May | 0.261864E+10 | 0.139733E+10 | 0.265427E+10 | 88440895.47 | 0.256582E+10 | 0.00 | 0.00 |
June | 0.345615E+10 | 0.743683E+09 | 0.272402E+10 | 0.146372E+09 | 0.257764E+10 | 0.00 | 0.00 |
July | 0.394154E+10 | 0.421802E+09 | 0.272025E+10 | 98372414.25 | 0.262187E+10 | 0.00 | 0.00 |
August | 0.343136E+10 | 0.599230E+09 | 0.241001E+10 | 28682265.77 | 0.238133E+10 | 0.00 | 0.00 |
September | 0.189713E+10 | 0.122643E+10 | 0.175814E+10 | 329225.84 | 0.175781E+10 | 0.00 | 0.00 |
October | 0.115012E+10 | 0.236446E+10 | 0.157226E+10 | 0.00 | 0.157226E+10 | 0.00 | 0.00 |
November | 0.287349E+09 | 0.345424E+10 | 0.106722E+10 | 0.00 | 0.106722E+10 | 0.00 | 0.00 |
December | 36512485.84 | 0.453579E+10 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189948E+11 | 0.293294E+11 | 0.212362E+11 | 0.367703E+09 | 0.208685E+11 | 0.00 | 0.00 |
Minimum of Months | 36512485.84 | 0.421802E+09 | 0.765605E+09 | 0.00 | 0.765605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.394154E+10 | 0.472506E+10 | 0.272402E+10 | 0.146372E+09 | 0.262187E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.781182E+09 | 0.295970E+10 | 0.122232E+10 | 0.490050E+09 | 0.732271E+09 | 0.00 | 0.00 |
February | 0.123576E+10 | 0.269603E+10 | 0.171212E+10 | 0.798700E+09 | 0.913415E+09 | 0.00 | 0.00 |
March | 0.217014E+10 | 0.213581E+10 | 0.241814E+10 | 0.102845E+10 | 0.138969E+10 | 0.00 | 0.00 |
April | 0.290789E+10 | 0.149022E+10 | 0.280833E+10 | 0.123013E+10 | 0.157820E+10 | 0.00 | 0.00 |
May | 0.415469E+10 | 0.987013E+09 | 0.351944E+10 | 0.140657E+10 | 0.211287E+10 | 0.00 | 0.00 |
June | 0.417583E+10 | 0.526819E+09 | 0.315656E+10 | 0.114265E+10 | 0.201391E+10 | 0.00 | 0.00 |
July | 0.468197E+10 | 0.304746E+09 | 0.327606E+10 | 0.118224E+10 | 0.209381E+10 | 0.00 | 0.00 |
August | 0.523112E+10 | 0.427600E+09 | 0.368892E+10 | 0.166333E+10 | 0.202559E+10 | 0.00 | 0.00 |
September | 0.333898E+10 | 0.822105E+09 | 0.266247E+10 | 0.119454E+10 | 0.146793E+10 | 0.00 | 0.00 |
October | 0.276829E+10 | 0.157272E+10 | 0.249418E+10 | 0.113044E+10 | 0.136374E+10 | 0.00 | 0.00 |
November | 0.118757E+10 | 0.221175E+10 | 0.149270E+10 | 0.573210E+09 | 0.919490E+09 | 0.00 | 0.00 |
December | 0.817363E+09 | 0.283037E+10 | 0.120166E+10 | 0.564225E+09 | 0.637437E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.334508E+11 | 0.189649E+11 | 0.296529E+11 | 0.124045E+11 | 0.172484E+11 | 0.00 | 0.00 |
Minimum of Months | 0.781182E+09 | 0.304746E+09 | 0.120166E+10 | 0.490050E+09 | 0.637437E+09 | 0.00 | 0.00 |
Maximum of Months | 0.523112E+10 | 0.295970E+10 | 0.368892E+10 | 0.166333E+10 | 0.211287E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.462282E+10 | 0.427764E+10 | 0.454055E+10 | 0.297318E+10 | 0.156738E+10 | 0.00 | 0.00 |
February | 0.557616E+10 | 0.396430E+10 | 0.540927E+10 | 0.358049E+10 | 0.182878E+10 | 0.00 | 0.00 |
March | 0.590262E+10 | 0.323578E+10 | 0.540307E+10 | 0.299879E+10 | 0.240428E+10 | 0.00 | 0.00 |
April | 0.458598E+10 | 0.232020E+10 | 0.405736E+10 | 0.160439E+10 | 0.245297E+10 | 0.00 | 0.00 |
May | 0.443149E+10 | 0.150756E+10 | 0.367420E+10 | 0.766374E+09 | 0.290783E+10 | 0.00 | 0.00 |
June | 0.458660E+10 | 0.807201E+09 | 0.333690E+10 | 0.510075E+09 | 0.282683E+10 | 0.00 | 0.00 |
July | 0.547254E+10 | 0.450618E+09 | 0.361433E+10 | 0.627803E+09 | 0.298653E+10 | 0.00 | 0.00 |
August | 0.732724E+10 | 0.675511E+09 | 0.482653E+10 | 0.179023E+10 | 0.303630E+10 | 0.00 | 0.00 |
September | 0.681188E+10 | 0.131106E+10 | 0.506794E+10 | 0.262133E+10 | 0.244661E+10 | 0.00 | 0.00 |
October | 0.898134E+10 | 0.247354E+10 | 0.717406E+10 | 0.449864E+10 | 0.267542E+10 | 0.00 | 0.00 |
November | 0.518952E+10 | 0.329681E+10 | 0.481412E+10 | 0.289110E+10 | 0.192302E+10 | 0.00 | 0.00 |
December | 0.513929E+10 | 0.410267E+10 | 0.492128E+10 | 0.349377E+10 | 0.142751E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.686275E+11 | 0.284229E+11 | 0.568396E+11 | 0.283562E+11 | 0.284835E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443149E+10 | 0.450618E+09 | 0.333690E+10 | 0.510075E+09 | 0.142751E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898134E+10 | 0.427764E+10 | 0.717406E+10 | 0.449864E+10 | 0.303630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.779285E+09 | 0.301979E+10 | 0.120671E+10 | 0.494269E+09 | 0.712437E+09 | 0.00 | 0.00 |
February | 0.115055E+10 | 0.280895E+10 | 0.160726E+10 | 0.705911E+09 | 0.901345E+09 | 0.00 | 0.00 |
March | 0.244079E+10 | 0.214008E+10 | 0.262759E+10 | 0.121308E+10 | 0.141451E+10 | 0.00 | 0.00 |
April | 0.291225E+10 | 0.154093E+10 | 0.277920E+10 | 0.118914E+10 | 0.159005E+10 | 0.00 | 0.00 |
May | 0.396418E+10 | 0.102773E+10 | 0.334540E+10 | 0.127045E+10 | 0.207495E+10 | 0.00 | 0.00 |
June | 0.471889E+10 | 0.568132E+09 | 0.354333E+10 | 0.142912E+10 | 0.211421E+10 | 0.00 | 0.00 |
July | 0.489468E+10 | 0.331031E+09 | 0.342914E+10 | 0.129130E+10 | 0.213783E+10 | 0.00 | 0.00 |
August | 0.540493E+10 | 0.465939E+09 | 0.379356E+10 | 0.175616E+10 | 0.203739E+10 | 0.00 | 0.00 |
September | 0.330401E+10 | 0.861930E+09 | 0.260625E+10 | 0.113892E+10 | 0.146733E+10 | 0.00 | 0.00 |
October | 0.302175E+10 | 0.162999E+10 | 0.267003E+10 | 0.129837E+10 | 0.137166E+10 | 0.00 | 0.00 |
November | 0.822032E+09 | 0.225563E+10 | 0.121339E+10 | 0.350677E+09 | 0.862713E+09 | 0.00 | 0.00 |
December | 0.723441E+09 | 0.290168E+10 | 0.111526E+10 | 0.482575E+09 | 0.632686E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.341368E+11 | 0.195518E+11 | 0.299371E+11 | 0.126200E+11 | 0.173171E+11 | 0.00 | 0.00 |
Minimum of Months | 0.723441E+09 | 0.331031E+09 | 0.111526E+10 | 0.350677E+09 | 0.632686E+09 | 0.00 | 0.00 |
Maximum of Months | 0.540493E+10 | 0.301979E+10 | 0.379356E+10 | 0.175616E+10 | 0.213783E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 62165234.45 | 0.475104E+10 | 0.877739E+09 | 0.00 | 0.877739E+09 | 0.00 | 0.00 |
February | 0.107105E+09 | 0.448721E+10 | 0.108491E+10 | 0.00 | 0.108491E+10 | 0.00 | 0.00 |
March | 0.607215E+09 | 0.337346E+10 | 0.166569E+10 | 0.00 | 0.166569E+10 | 0.00 | 0.00 |
April | 0.122448E+10 | 0.235288E+10 | 0.193618E+10 | 5507101.70 | 0.193068E+10 | 0.00 | 0.00 |
May | 0.249421E+10 | 0.150337E+10 | 0.265432E+10 | 88443495.07 | 0.256588E+10 | 0.00 | 0.00 |
June | 0.339080E+10 | 0.790251E+09 | 0.272407E+10 | 0.146376E+09 | 0.257770E+10 | 0.00 | 0.00 |
July | 0.388895E+10 | 0.457312E+09 | 0.272030E+10 | 98375305.77 | 0.262193E+10 | 0.00 | 0.00 |
August | 0.340534E+10 | 0.619993E+09 | 0.241006E+10 | 28683108.84 | 0.238138E+10 | 0.00 | 0.00 |
September | 0.188563E+10 | 0.122163E+10 | 0.175818E+10 | 329235.52 | 0.175785E+10 | 0.00 | 0.00 |
October | 0.114759E+10 | 0.232597E+10 | 0.157230E+10 | 0.00 | 0.157230E+10 | 0.00 | 0.00 |
November | 0.290870E+09 | 0.336806E+10 | 0.106724E+10 | 0.00 | 0.106724E+10 | 0.00 | 0.00 |
December | 36243139.54 | 0.448906E+10 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185406E+11 | 0.297402E+11 | 0.212366E+11 | 0.367714E+09 | 0.208689E+11 | 0.00 | 0.00 |
Minimum of Months | 36243139.54 | 0.457312E+09 | 0.765622E+09 | 0.00 | 0.765622E+09 | 0.00 | 0.00 |
Maximum of Months | 0.388895E+10 | 0.475104E+10 | 0.272407E+10 | 0.146376E+09 | 0.262193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.765460E+09 | 0.295456E+10 | 0.122234E+10 | 0.490060E+09 | 0.732281E+09 | 0.00 | 0.00 |
February | 0.120692E+10 | 0.271021E+10 | 0.171214E+10 | 0.798716E+09 | 0.913427E+09 | 0.00 | 0.00 |
March | 0.211150E+10 | 0.218586E+10 | 0.241818E+10 | 0.102847E+10 | 0.138971E+10 | 0.00 | 0.00 |
April | 0.284643E+10 | 0.153040E+10 | 0.280837E+10 | 0.123015E+10 | 0.157822E+10 | 0.00 | 0.00 |
May | 0.407873E+10 | 0.102709E+10 | 0.351950E+10 | 0.140660E+10 | 0.211289E+10 | 0.00 | 0.00 |
June | 0.412890E+10 | 0.541521E+09 | 0.315661E+10 | 0.114267E+10 | 0.201394E+10 | 0.00 | 0.00 |
July | 0.464466E+10 | 0.311862E+09 | 0.327611E+10 | 0.118227E+10 | 0.209384E+10 | 0.00 | 0.00 |
August | 0.520605E+10 | 0.418322E+09 | 0.368898E+10 | 0.166336E+10 | 0.202562E+10 | 0.00 | 0.00 |
September | 0.332170E+10 | 0.795182E+09 | 0.266251E+10 | 0.119456E+10 | 0.146794E+10 | 0.00 | 0.00 |
October | 0.275928E+10 | 0.151028E+10 | 0.249422E+10 | 0.113046E+10 | 0.136375E+10 | 0.00 | 0.00 |
November | 0.118864E+10 | 0.212604E+10 | 0.149272E+10 | 0.573221E+09 | 0.919503E+09 | 0.00 | 0.00 |
December | 0.811379E+09 | 0.277458E+10 | 0.120168E+10 | 0.564236E+09 | 0.637445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330696E+11 | 0.188859E+11 | 0.296533E+11 | 0.124048E+11 | 0.172486E+11 | 0.00 | 0.00 |
Minimum of Months | 0.765460E+09 | 0.311862E+09 | 0.120168E+10 | 0.490060E+09 | 0.637445E+09 | 0.00 | 0.00 |
Maximum of Months | 0.520605E+10 | 0.295456E+10 | 0.368898E+10 | 0.166336E+10 | 0.211289E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.451433E+10 | 0.428416E+10 | 0.454073E+10 | 0.297330E+10 | 0.156743E+10 | 0.00 | 0.00 |
February | 0.545159E+10 | 0.395689E+10 | 0.540948E+10 | 0.358064E+10 | 0.182885E+10 | 0.00 | 0.00 |
March | 0.576346E+10 | 0.330470E+10 | 0.540327E+10 | 0.299891E+10 | 0.240436E+10 | 0.00 | 0.00 |
April | 0.446416E+10 | 0.242853E+10 | 0.405750E+10 | 0.160446E+10 | 0.245304E+10 | 0.00 | 0.00 |
May | 0.428961E+10 | 0.161926E+10 | 0.367432E+10 | 0.766406E+09 | 0.290792E+10 | 0.00 | 0.00 |
June | 0.451579E+10 | 0.848107E+09 | 0.333701E+10 | 0.510096E+09 | 0.282691E+10 | 0.00 | 0.00 |
July | 0.542534E+10 | 0.472086E+09 | 0.361445E+10 | 0.627829E+09 | 0.298662E+10 | 0.00 | 0.00 |
August | 0.730325E+10 | 0.659190E+09 | 0.482670E+10 | 0.179030E+10 | 0.303640E+10 | 0.00 | 0.00 |
September | 0.678989E+10 | 0.125283E+10 | 0.506813E+10 | 0.262144E+10 | 0.244668E+10 | 0.00 | 0.00 |
October | 0.895346E+10 | 0.232475E+10 | 0.717434E+10 | 0.449882E+10 | 0.267551E+10 | 0.00 | 0.00 |
November | 0.514342E+10 | 0.317567E+10 | 0.481431E+10 | 0.289122E+10 | 0.192309E+10 | 0.00 | 0.00 |
December | 0.507168E+10 | 0.400808E+10 | 0.492147E+10 | 0.349392E+10 | 0.142756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.676860E+11 | 0.283342E+11 | 0.568417E+11 | 0.283574E+11 | 0.284844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.428961E+10 | 0.472086E+09 | 0.333701E+10 | 0.510096E+09 | 0.142756E+10 | 0.00 | 0.00 |
Maximum of Months | 0.895346E+10 | 0.428416E+10 | 0.717434E+10 | 0.449882E+10 | 0.303640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.761585E+09 | 0.302023E+10 | 0.120672E+10 | 0.494277E+09 | 0.712445E+09 | 0.00 | 0.00 |
February | 0.112033E+10 | 0.282579E+10 | 0.160728E+10 | 0.705922E+09 | 0.901354E+09 | 0.00 | 0.00 |
March | 0.238712E+10 | 0.217698E+10 | 0.262763E+10 | 0.121310E+10 | 0.141452E+10 | 0.00 | 0.00 |
April | 0.285547E+10 | 0.158027E+10 | 0.277923E+10 | 0.118916E+10 | 0.159007E+10 | 0.00 | 0.00 |
May | 0.389880E+10 | 0.106621E+10 | 0.334544E+10 | 0.127047E+10 | 0.207497E+10 | 0.00 | 0.00 |
June | 0.468127E+10 | 0.574194E+09 | 0.354337E+10 | 0.142914E+10 | 0.211423E+10 | 0.00 | 0.00 |
July | 0.486541E+10 | 0.333073E+09 | 0.342918E+10 | 0.129132E+10 | 0.213786E+10 | 0.00 | 0.00 |
August | 0.538943E+10 | 0.451490E+09 | 0.379360E+10 | 0.175619E+10 | 0.203741E+10 | 0.00 | 0.00 |
September | 0.329645E+10 | 0.834032E+09 | 0.260628E+10 | 0.113894E+10 | 0.146734E+10 | 0.00 | 0.00 |
October | 0.301978E+10 | 0.156023E+10 | 0.267006E+10 | 0.129839E+10 | 0.137168E+10 | 0.00 | 0.00 |
November | 0.822730E+09 | 0.218015E+10 | 0.121341E+10 | 0.350683E+09 | 0.862723E+09 | 0.00 | 0.00 |
December | 0.715167E+09 | 0.285071E+10 | 0.111528E+10 | 0.482583E+09 | 0.632693E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.338135E+11 | 0.194533E+11 | 0.299375E+11 | 0.126202E+11 | 0.173173E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715167E+09 | 0.333073E+09 | 0.111528E+10 | 0.350683E+09 | 0.632693E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538943E+10 | 0.302023E+10 | 0.379360E+10 | 0.175619E+10 | 0.213786E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.496809E+10 | -0.472086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -247231204.4 | 60.05 | 0.00 | 0.00 |
February | 0.455126E+10 | -0.433271E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -218547794.9 | 60.05 | 0.00 | 0.00 |
March | 0.525240E+10 | -0.501498E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -237414376.7 | 60.05 | 0.00 | 0.00 |
April | 0.451331E+10 | -0.428603E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227273358.6 | 60.05 | 0.00 | 0.00 |
May | 0.452028E+10 | -0.428732E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232960288.4 | 60.05 | 0.00 | 0.00 |
June | 0.418108E+10 | -0.395667E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224406871.0 | 60.05 | 0.00 | 0.00 |
July | 0.376683E+10 | -0.353550E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231328120.5 | 60.05 | 0.00 | 0.00 |
August | 0.408938E+10 | -0.385767E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231714793.0 | 60.05 | 0.00 | 0.00 |
September | 0.380408E+10 | -0.358006E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224021426.1 | 60.05 | 0.00 | 0.00 |
October | 0.416817E+10 | -0.393596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232212271.4 | 60.05 | 0.00 | 0.00 |
November | 0.439543E+10 | -0.416705E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -228388231.7 | 60.05 | 0.00 | 0.00 |
December | 0.463972E+10 | -0.439982E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -239898323.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.528500E+11 | -0.500746E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277540E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.376683E+10 | -0.501498E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -247231204.4 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.525240E+10 | -0.353550E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -218547794.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6502.60 | 36.69 | 196.17 | 241.50 | 3388.99 | 33.30 | 185.67 | 196.67 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9259.17 | 37.54 | 210.00 | 258.33 | 2126.96 | 26.55 | 176.83 | 233.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-06:00 | 3276.47 | 21.57 | 57.00 | 318.33 | 1592.25 | 21.71 | 170.17 | 285.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 2073.87 | 18.95 | 1.83 | 339.00 | 1227.90 | 21.18 | 149.83 | 299.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1803.96 | 18.85 | 0.00 | 390.67 | 1014.36 | 21.02 | 225.17 | 347.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:40 | 1718.13 | 18.83 | 0.00 | 382.50 | 978.98 | 21.06 | 208.00 | 340.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:40 | 1896.16 | 19.09 | 1.00 | 390.33 | 1057.77 | 21.32 | 237.83 | 344.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2107.07 | 19.07 | 7.83 | 370.67 | 1223.37 | 21.27 | 238.00 | 340.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3805.78 | 21.30 | 36.50 | 323.83 | 1466.81 | 21.48 | 178.50 | 289.50 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 10128.99 | 36.12 | 283.50 | 307.00 | 2052.87 | 23.60 | 258.83 | 289.00 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6447.57 | 36.31 | 235.17 | 257.17 | 2274.92 | 29.45 | 223.33 | 236.00 |
December | 211.17 | 0.50 | 0.48 | 01-DEC-07:30 | 6063.17 | 36.57 | 198.50 | 243.33 | 5410.95 | 39.04 | 208.00 | 214.67 |
Annual Sum or Average | 3472.67 | 0.50 | 4187.37 | 25.32 | 1227.50 | 3822.67 | 1789.52 | 24.15 | 2460.17 | 3415.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1718.13 | 18.83 | 0.00 | 241.50 | 978.98 | 21.02 | 149.83 | 196.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10128.99 | 37.54 | 283.50 | 390.67 | 5410.95 | 39.04 | 258.83 | 347.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1978.73 | 21.31 | 61.00 | 221.17 | 1125.41 | 23.69 | 88.67 | 158.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:40 | 2816.44 | 24.01 | 80.67 | 245.50 | 1626.39 | 24.64 | 92.17 | 207.17 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2919.56 | 21.40 | 71.50 | 313.50 | 1635.57 | 22.57 | 77.67 | 260.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3823.68 | 22.28 | 80.67 | 341.33 | 1557.02 | 22.91 | 53.33 | 302.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:40 | 3178.29 | 21.15 | 99.17 | 396.67 | 1725.36 | 22.44 | 73.50 | 354.83 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2835.16 | 20.46 | 80.67 | 387.17 | 1588.14 | 22.72 | 69.83 | 353.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:49 | 2929.24 | 21.08 | 89.67 | 396.00 | 1588.94 | 22.48 | 69.50 | 358.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3910.50 | 23.17 | 128.17 | 373.17 | 1632.37 | 22.85 | 82.67 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3397.81 | 22.17 | 82.67 | 320.67 | 1492.55 | 22.75 | 64.17 | 285.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3017.01 | 23.06 | 91.17 | 293.50 | 1597.73 | 23.88 | 137.67 | 265.33 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 2042.55 | 22.03 | 73.33 | 244.50 | 1050.61 | 22.55 | 114.17 | 200.67 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1895.84 | 23.20 | 81.17 | 221.17 | 1103.75 | 24.08 | 91.33 | 157.33 |
Annual Sum or Average | 3472.67 | 0.51 | 2983.12 | 22.03 | 1019.83 | 3754.33 | 1511.35 | 23.03 | 1014.67 | 3250.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1895.84 | 20.46 | 61.00 | 221.17 | 1050.61 | 22.44 | 53.33 | 157.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3910.50 | 24.01 | 128.17 | 396.67 | 1725.36 | 24.64 | 137.67 | 358.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:39 | 634.71 | 15.57 | 0.00 | 207.50 | 385.93 | 17.99 | 0.00 | 118.00 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 688.41 | 16.52 | 0.00 | 230.33 | 443.21 | 19.04 | 0.00 | 162.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:19 | 911.03 | 17.40 | 0.00 | 308.00 | 564.74 | 19.64 | 13.33 | 237.50 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1025.43 | 18.38 | 0.00 | 344.00 | 638.11 | 20.58 | 51.17 | 295.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1322.13 | 19.16 | 7.50 | 403.67 | 759.55 | 21.28 | 168.33 | 363.17 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-04:00 | 1491.61 | 22.44 | 74.50 | 401.83 | 837.60 | 23.66 | 239.00 | 373.33 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1468.07 | 20.28 | 26.83 | 407.50 | 829.27 | 23.22 | 244.50 | 371.50 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1208.24 | 18.79 | 0.00 | 377.83 | 726.71 | 20.97 | 164.67 | 350.00 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 940.22 | 17.95 | 0.00 | 320.17 | 590.55 | 20.22 | 27.50 | 269.67 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 854.25 | 17.60 | 0.00 | 289.17 | 548.00 | 20.01 | 0.00 | 243.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 707.70 | 16.27 | 0.00 | 233.83 | 421.69 | 18.60 | 0.00 | 155.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:39 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1043.72 | 18.29 | 108.83 | 3719.83 | 622.82 | 20.54 | 908.50 | 3030.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 512.50 | 14.57 | 0.00 | 196.00 | 321.08 | 17.16 | 0.00 | 89.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1491.61 | 22.44 | 74.50 | 407.50 | 837.60 | 23.66 | 244.50 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-08:39 | 1970.59 | 23.24 | 73.33 | 228.67 | 1113.66 | 23.83 | 78.83 | 162.50 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2197.29 | 21.43 | 57.00 | 244.33 | 1186.09 | 23.37 | 76.00 | 204.50 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3178.88 | 23.68 | 95.83 | 317.00 | 1797.95 | 24.57 | 92.50 | 272.33 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3617.58 | 21.96 | 76.83 | 340.17 | 1503.45 | 21.51 | 40.33 | 299.67 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:10 | 3412.56 | 19.22 | 69.33 | 395.17 | 1516.69 | 19.00 | 0.00 | 357.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3301.34 | 15.87 | 1.83 | 391.17 | 1787.28 | 19.18 | 2.50 | 351.83 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 3106.44 | 18.53 | 49.00 | 397.17 | 1665.56 | 19.30 | 6.17 | 355.83 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3988.07 | 20.31 | 86.33 | 373.33 | 1740.05 | 19.43 | 19.50 | 346.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3220.56 | 22.40 | 85.33 | 322.17 | 1683.18 | 23.13 | 68.50 | 284.67 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3451.04 | 24.12 | 109.33 | 303.50 | 1464.97 | 23.44 | 119.17 | 275.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1669.38 | 21.05 | 68.83 | 245.33 | 913.53 | 23.40 | 99.67 | 203.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:39 | 1561.79 | 21.16 | 67.50 | 220.17 | 890.50 | 23.26 | 76.33 | 162.67 |
Annual Sum or Average | 3472.67 | 0.50 | 3026.26 | 20.80 | 840.50 | 3778.17 | 1491.57 | 21.57 | 679.50 | 3277.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1561.79 | 15.87 | 1.83 | 220.17 | 890.50 | 19.00 | 0.00 | 162.50 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3988.07 | 24.12 | 109.33 | 397.17 | 1797.95 | 24.57 | 119.17 | 357.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.56 | 36.47 | 196.17 | 238.33 | 3258.62 | 32.19 | 144.00 | 194.00 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.85 | 37.27 | 210.00 | 256.83 | 2002.17 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.97 | 18.16 | 45.83 | 318.33 | 1479.48 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.95 | 15.24 | 0.00 | 338.33 | 1152.51 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.85 | 15.23 | 0.00 | 389.17 | 964.77 | 18.66 | 0.50 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.46 | 15.22 | 0.00 | 380.33 | 935.04 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.89 | 15.42 | 0.00 | 388.67 | 1007.82 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.75 | 15.51 | 0.00 | 368.67 | 1154.27 | 19.00 | 19.33 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.97 | 17.87 | 29.50 | 322.33 | 1365.47 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.84 | 35.44 | 281.00 | 306.17 | 1907.88 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.79 | 35.30 | 228.83 | 255.83 | 2152.12 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.17 | 35.73 | 195.50 | 239.17 | 5278.82 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.83 | 22.74 | 1186.83 | 3802.17 | 1699.27 | 22.02 | 689.67 | 3377.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.46 | 15.22 | 0.00 | 238.33 | 935.04 | 18.66 | 0.00 | 194.00 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.84 | 37.27 | 281.00 | 389.17 | 5278.82 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.04 | 20.83 | 61.00 | 218.83 | 1081.84 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.16 | 23.56 | 80.67 | 243.50 | 1572.21 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.96 | 19.56 | 58.83 | 311.00 | 1573.44 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.76 | 21.83 | 80.67 | 338.83 | 1485.02 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.31 | 20.70 | 99.17 | 395.67 | 1656.52 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.88 | 19.99 | 80.67 | 385.00 | 1526.79 | 22.55 | 69.00 | 351.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.36 | 20.58 | 89.17 | 394.33 | 1524.45 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3767.85 | 21.40 | 111.67 | 371.00 | 1554.94 | 22.54 | 74.17 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.24 | 21.69 | 82.67 | 319.67 | 1400.88 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.16 | 22.58 | 91.17 | 291.00 | 1532.35 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.18 | 21.37 | 72.00 | 242.17 | 1002.42 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.84 | 20.40 | 64.00 | 214.83 | 1064.80 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2883.09 | 21.15 | 971.67 | 3725.83 | 1447.10 | 22.76 | 925.00 | 3203.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.84 | 19.56 | 58.83 | 214.83 | 1002.42 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3767.85 | 23.56 | 111.67 | 395.67 | 1656.52 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.06 | 12.00 | 0.00 | 203.17 | 372.57 | 15.62 | 0.00 | 112.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.60 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.27 | 14.16 | 0.00 | 306.50 | 547.39 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.39 | 15.16 | 0.00 | 342.50 | 619.11 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.56 | 15.68 | 3.00 | 401.83 | 732.99 | 19.16 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.32 | 18.89 | 62.67 | 398.83 | 807.88 | 21.82 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.99 | 15.75 | 0.00 | 405.00 | 799.54 | 21.32 | 63.17 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.38 | 15.59 | 0.00 | 377.50 | 703.61 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.59 | 14.77 | 0.00 | 317.83 | 572.88 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.12 | 14.41 | 0.00 | 286.67 | 530.68 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.86 | 12.60 | 0.00 | 230.83 | 406.95 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.99 | 14.78 | 65.67 | 3687.67 | 602.17 | 18.51 | 184.67 | 2971.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.15 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.32 | 18.89 | 62.67 | 405.00 | 807.88 | 21.82 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.28 | 20.59 | 57.17 | 224.50 | 1070.81 | 23.70 | 77.00 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.10 | 21.00 | 57.00 | 242.83 | 1100.33 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.28 | 23.30 | 95.83 | 316.17 | 1729.71 | 24.39 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.55 | 21.53 | 76.83 | 337.83 | 1431.94 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.85 | 18.75 | 69.17 | 393.50 | 1452.61 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.87 | 15.34 | 1.83 | 389.50 | 1714.55 | 19.00 | 1.50 | 347.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.69 | 18.05 | 49.00 | 395.33 | 1596.86 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.14 | 19.86 | 86.33 | 371.17 | 1664.28 | 19.28 | 14.83 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.61 | 21.99 | 85.33 | 320.83 | 1615.36 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.70 | 23.74 | 109.33 | 302.17 | 1395.36 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.51 | 20.64 | 68.83 | 243.67 | 874.07 | 23.11 | 94.33 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.50 | 20.77 | 67.50 | 218.00 | 820.02 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.74 | 20.23 | 824.17 | 3755.50 | 1424.33 | 21.26 | 634.17 | 3224.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.50 | 15.34 | 1.83 | 218.00 | 820.02 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.14 | 23.74 | 109.33 | 395.33 | 1729.71 | 24.39 | 115.83 | 353.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.50 | 0.48 | 01-JAN-07:49 | 6326.55 | 36.47 | 196.17 | 238.33 | 3258.51 | 32.19 | 144.00 | 193.83 |
February | 216.00 | 0.49 | 0.48 | 01-FEB-07:40 | 9075.80 | 37.27 | 210.00 | 256.83 | 2002.06 | 24.94 | 80.00 | 233.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3153.85 | 18.16 | 45.83 | 318.33 | 1479.37 | 19.19 | 40.50 | 279.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 1969.85 | 15.25 | 0.00 | 338.33 | 1152.43 | 18.82 | 7.67 | 295.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:00 | 1727.75 | 15.24 | 0.00 | 389.17 | 964.70 | 18.67 | 0.83 | 342.50 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:49 | 1648.37 | 15.22 | 0.00 | 380.33 | 934.97 | 18.73 | 0.00 | 335.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:49 | 1817.78 | 15.42 | 0.00 | 388.67 | 1007.74 | 18.91 | 1.83 | 341.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 2007.65 | 15.51 | 0.00 | 368.67 | 1154.19 | 19.00 | 19.50 | 335.83 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:19 | 3670.85 | 17.87 | 29.50 | 322.33 | 1365.37 | 18.97 | 20.33 | 287.00 |
October | 305.50 | 0.49 | 0.48 | 01-OCT-14:39 | 9929.75 | 35.44 | 281.00 | 306.17 | 1907.75 | 20.87 | 46.33 | 287.33 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:49 | 6268.75 | 35.30 | 228.83 | 255.83 | 2152.00 | 27.59 | 121.17 | 234.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5883.19 | 35.73 | 195.50 | 239.17 | 5278.73 | 38.86 | 208.00 | 212.00 |
Annual Sum or Average | 3472.67 | 0.50 | 4061.74 | 22.74 | 1186.83 | 3802.17 | 1699.18 | 22.02 | 690.17 | 3377.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 1648.37 | 15.22 | 0.00 | 238.33 | 934.97 | 18.67 | 0.00 | 193.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9929.75 | 37.27 | 281.00 | 389.17 | 5278.73 | 38.86 | 208.00 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-07:49 | 1921.02 | 20.83 | 61.00 | 218.83 | 1081.80 | 23.47 | 82.50 | 156.00 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2748.14 | 23.56 | 80.67 | 243.50 | 1572.16 | 24.44 | 82.67 | 202.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:49 | 2742.93 | 19.56 | 58.83 | 311.00 | 1573.37 | 22.36 | 67.83 | 252.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:10 | 3732.71 | 21.83 | 80.67 | 338.83 | 1484.95 | 22.73 | 52.00 | 298.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3083.25 | 20.70 | 99.17 | 395.67 | 1656.44 | 22.27 | 72.83 | 351.00 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2751.81 | 19.99 | 80.67 | 385.00 | 1526.72 | 22.56 | 69.00 | 351.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2838.80 | 20.62 | 89.67 | 394.33 | 1524.37 | 22.31 | 67.00 | 354.67 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:30 | 3815.01 | 22.74 | 128.17 | 372.00 | 1554.86 | 22.54 | 74.33 | 344.33 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-05:49 | 3312.20 | 21.70 | 82.67 | 319.67 | 1400.81 | 21.70 | 49.00 | 281.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2932.14 | 22.59 | 91.17 | 291.00 | 1532.29 | 23.67 | 119.67 | 261.67 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-06:49 | 1976.15 | 21.37 | 72.00 | 242.17 | 1002.36 | 22.32 | 102.00 | 197.00 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-07:30 | 1757.83 | 20.40 | 64.00 | 214.83 | 1064.76 | 23.86 | 86.33 | 152.17 |
Annual Sum or Average | 3472.67 | 0.51 | 2888.39 | 21.30 | 988.67 | 3726.83 | 1447.03 | 22.76 | 925.17 | 3203.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1757.83 | 19.56 | 58.83 | 214.83 | 1002.36 | 21.70 | 49.00 | 152.17 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3815.01 | 23.56 | 128.17 | 395.67 | 1656.44 | 24.44 | 119.67 | 354.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.54 | 0.48 | 01-JAN-08:50 | 610.05 | 12.00 | 0.00 | 203.17 | 372.54 | 15.62 | 0.00 | 112.17 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:39 | 662.22 | 13.10 | 0.00 | 226.67 | 429.58 | 16.87 | 0.00 | 157.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:30 | 878.25 | 14.16 | 0.00 | 306.50 | 547.36 | 17.66 | 0.00 | 229.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 989.37 | 15.16 | 0.00 | 342.50 | 619.08 | 18.71 | 0.00 | 291.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1274.51 | 15.68 | 3.00 | 401.83 | 732.94 | 19.17 | 36.67 | 359.00 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1434.27 | 18.89 | 62.83 | 398.83 | 807.83 | 21.83 | 76.67 | 371.50 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1411.94 | 15.75 | 0.00 | 405.00 | 799.49 | 21.32 | 63.33 | 368.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:49 | 1165.35 | 15.59 | 0.00 | 377.50 | 703.57 | 19.10 | 8.17 | 346.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 906.57 | 14.77 | 0.00 | 317.83 | 572.84 | 18.32 | 0.00 | 263.83 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 821.11 | 14.41 | 0.00 | 286.67 | 530.65 | 18.03 | 0.00 | 239.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:30 | 680.84 | 12.61 | 0.00 | 230.83 | 406.92 | 16.20 | 0.00 | 146.83 |
December | 211.17 | 0.56 | 0.48 | 01-DEC-08:50 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 |
Annual Sum or Average | 3472.67 | 0.51 | 1004.96 | 14.78 | 65.83 | 3687.67 | 602.13 | 18.51 | 184.83 | 2970.83 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 492.02 | 10.88 | 0.00 | 190.33 | 310.14 | 14.69 | 0.00 | 84.17 | |
Maximum of Months | 389.17 | 0.56 | 0.48 | 1434.27 | 18.89 | 62.83 | 405.00 | 807.83 | 21.83 | 76.67 | 371.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:39 | 1832.26 | 20.59 | 57.17 | 224.50 | 1070.77 | 23.70 | 77.17 | 158.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-08:39 | 2128.09 | 21.01 | 57.00 | 242.83 | 1100.28 | 22.17 | 66.50 | 199.67 |
March | 275.00 | 0.50 | 0.48 | 01-MAR-07:30 | 3094.25 | 23.30 | 95.83 | 316.17 | 1729.64 | 24.40 | 88.83 | 265.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 3526.51 | 21.53 | 76.83 | 337.83 | 1431.87 | 21.36 | 38.83 | 297.17 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3325.77 | 18.75 | 69.17 | 393.50 | 1452.53 | 18.82 | 0.00 | 353.17 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3198.79 | 15.34 | 1.83 | 389.50 | 1714.46 | 19.00 | 1.50 | 347.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-05:00 | 3008.61 | 18.05 | 49.00 | 395.33 | 1596.77 | 19.13 | 4.50 | 352.33 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-06:10 | 3842.09 | 19.86 | 86.33 | 371.17 | 1664.20 | 19.28 | 15.00 | 344.17 |
September | 285.33 | 0.50 | 0.48 | 01-SEP-06:40 | 3136.57 | 21.99 | 85.33 | 320.83 | 1615.29 | 23.01 | 66.50 | 280.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3358.68 | 23.74 | 109.33 | 302.17 | 1395.29 | 23.33 | 115.83 | 272.83 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:30 | 1619.48 | 20.64 | 68.83 | 243.67 | 874.02 | 23.11 | 94.50 | 197.83 |
December | 211.17 | 0.53 | 0.48 | 01-DEC-08:50 | 1513.49 | 20.77 | 67.50 | 218.00 | 819.98 | 21.77 | 65.50 | 155.33 |
Annual Sum or Average | 3472.67 | 0.50 | 2932.70 | 20.23 | 824.17 | 3755.50 | 1424.26 | 21.26 | 634.67 | 3223.83 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1513.49 | 15.34 | 1.83 | 218.00 | 819.98 | 18.82 | 0.00 | 155.33 | |
Maximum of Months | 389.17 | 0.53 | 0.48 | 3842.09 | 23.74 | 109.33 | 395.33 | 1729.64 | 24.40 | 115.83 | 353.17 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108618E+11 | 18763.86 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109858E+11 | 18720.21 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.613315E+10 | 17059.47 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118914E+10 | 9089.25 | 03-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4639353.12 | 2058.13 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 795647.89 | 5.38 | 19-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1601386.42 | 5.45 | 12-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1517261.44 | 5.30 | 04-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 558834.02 | 4.75 | 01-SEP-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76712243.30 | 6206.26 | 28-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355764E+10 | 17123.96 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.864137E+10 | 17288.71 | 22-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 558834.02 | 4.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109858E+11 | 18763.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.631615E+09 | 11476.68 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.631615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.631615E+09 | 11476.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.461129E+10 | 8614.66 | 31-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372653E+10 | 8911.95 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232376E+10 | 8160.15 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119369E+10 | 8468.49 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.363523E+09 | 8118.03 | 17-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1226188.07 | 2100.89 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10244531.56 | 5112.84 | 20-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221215E+09 | 8117.87 | 02-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149759E+10 | 8418.64 | 06-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284184E+10 | 8176.46 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.461129E+10 | 8911.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172381E+10 | 6324.31 | 31-JAN-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112274E+10 | 6606.12 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211548E+09 | 5984.02 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43045068.13 | 5968.47 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133882E+09 | 6010.68 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.552069E+09 | 5996.14 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172381E+10 | 6606.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326166E+10 | 7292.62 | 31-JAN-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271316E+10 | 7545.23 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.754268E+09 | 6836.97 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132177E+09 | 6827.62 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349699E+09 | 6904.42 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123936E+10 | 6850.76 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326166E+10 | 7545.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189601E+10 | 6456.36 | 02-JAN-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137386E+10 | 6736.89 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225625E+09 | 6095.79 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49250241.65 | 6079.79 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181342E+09 | 6122.93 | 24-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.643135E+09 | 6108.12 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189601E+10 | 6736.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112770E+11 | 19768.84 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112631E+11 | 19540.73 | 06-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.667370E+10 | 18421.62 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178740E+10 | 10308.07 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21262511.70 | 3408.53 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 609927.34 | 4.98 | 26-JUN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1309629.85 | 5.10 | 10-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1306562.94 | 5.01 | 03-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 377293.59 | 5.05 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303026E+09 | 6742.14 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.428546E+10 | 16091.62 | 22-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.915003E+10 | 18493.61 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 377293.59 | 4.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112770E+11 | 19768.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195459E+10 | 17698.60 | 02-JAN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.722381E+09 | 16777.38 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18567650.27 | 16595.61 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94867220.24 | 16697.62 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194341E+09 | 16681.96 | 26-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195459E+10 | 17698.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190675E+10 | 8969.27 | 14-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118768E+10 | 9414.03 | 06-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234686E+09 | 8680.68 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45777614.87 | 8667.29 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271335E+09 | 8669.46 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.863607E+09 | 8691.71 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190675E+10 | 9414.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161194E+10 | 6959.42 | 02-JAN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103380E+10 | 6978.28 | 06-FEB-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180278E+09 | 6574.91 | 20-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22593909.67 | 6535.59 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2128.55 | 3.55 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.261897E+09 | 6566.29 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.735963E+09 | 6584.33 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161194E+10 | 6978.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.310280E+10 | 7751.06 | 02-JAN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232007E+10 | 8000.55 | 06-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451806E+09 | 7322.97 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60137925.12 | 7296.11 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 100079.48 | 80.34 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.567607E+09 | 7391.99 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151862E+10 | 7316.96 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310280E+10 | 8000.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185469E+10 | 7101.56 | 02-JAN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132587E+10 | 7334.34 | 06-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213641E+09 | 6667.95 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35907094.81 | 6647.39 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335016E+09 | 6678.71 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880984E+09 | 6697.13 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.464611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185469E+10 | 7334.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116933E+11 | 19127.38 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116098E+11 | 19075.17 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708555E+10 | 16310.83 | 23-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211915E+10 | 11216.52 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40002235.78 | 4551.56 | 01-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 689452.86 | 5.51 | 19-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1439990.71 | 5.94 | 10-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1410692.79 | 5.66 | 04-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1738829.83 | 610.74 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471678E+09 | 8990.81 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466893E+10 | 16865.24 | 24-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.972754E+10 | 16301.94 | 15-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 689452.86 | 5.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116933E+11 | 19127.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537683E+10 | 23858.26 | 02-JAN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.376959E+10 | 24523.47 | 06-FEB-08:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.561270E+09 | 22933.95 | 07-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101908E+09 | 22891.01 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111056E+10 | 22923.70 | 28-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246272E+10 | 22925.96 | 04-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537683E+10 | 24523.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344528E+10 | 10851.14 | 14-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252611E+10 | 11330.21 | 06-FEB-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.829662E+09 | 10315.31 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263038E+09 | 10309.53 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4079769.35 | 7376.64 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19603312.79 | 10282.26 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.854335E+09 | 10312.14 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206077E+10 | 10320.96 | 11-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344528E+10 | 11330.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282176E+10 | 7912.21 | 14-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.208185E+10 | 7891.69 | 07-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.585036E+09 | 7521.36 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157088E+09 | 7516.02 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8000.56 | 40.00 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19349485.32 | 7516.10 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.723097E+09 | 7518.44 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170620E+10 | 7524.07 | 04-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.809439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.282176E+10 | 7912.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.507416E+10 | 9477.45 | 31-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421427E+10 | 9702.51 | 06-FEB-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132698E+10 | 8849.07 | 22-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312870E+09 | 8800.75 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2707179.13 | 5680.56 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 47065517.98 | 8782.33 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148488E+10 | 9002.16 | 24-NOV-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328281E+10 | 9138.09 | 22-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.507416E+10 | 9702.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309700E+10 | 8383.78 | 02-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249775E+10 | 8689.80 | 06-FEB-08:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700486E+09 | 7858.19 | 01-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182971E+09 | 7852.90 | 03-APR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2400013.01 | 4244.30 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25954586.80 | 7844.15 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.889609E+09 | 7855.29 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193538E+10 | 7861.26 | 04-DEC-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309700E+10 | 8689.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 736095.72 | 736095.72 | 1226.83 | 03-JAN-07:30 | 1226.83 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.489143E+09 | 0.351457E+09 | 23589.45 | 27-MAR-16:00 | 20782.34 | 0.00 |
April | 0.00 | 0.00 | 0.554220E+10 | 0.517548E+10 | 44559.45 | 07-APR-14:30 | 44559.45 | 0.00 |
May | 0.00 | 0.00 | 0.167382E+11 | 0.142010E+11 | 83326.16 | 30-MAY-14:20 | 83326.16 | 0.00 |
June | 0.00 | 0.00 | 0.575169E+11 | 0.449539E+11 | 106642.34 | 27-JUN-06:03 | 58156.88 | 0.00 |
July | 0.00 | 0.00 | 0.816836E+11 | 0.612578E+11 | 107107.39 | 22-JUL-06:03 | 65610.20 | 0.00 |
August | 0.00 | 0.00 | 0.839288E+11 | 0.672388E+11 | 106478.47 | 16-AUG-06:03 | 65817.25 | 0.00 |
September | 0.00 | 0.00 | 0.441044E+11 | 0.359953E+11 | 105843.13 | 07-SEP-06:03 | 67968.44 | 0.00 |
October | 0.00 | 0.00 | 0.213509E+11 | 0.156262E+11 | 65552.26 | 25-OCT-10:30 | 47066.59 | 0.00 |
November | 0.00 | 0.00 | 0.199548E+10 | 0.188735E+10 | 20588.25 | 06-NOV-15:30 | 20588.25 | 0.00 |
December | 0.00 | 0.00 | 53423.69 | 46324.01 | 445.20 | 19-DEC-17:02 | 386.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.313350E+12 | 0.246688E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.839288E+11 | 0.672388E+11 | 107107.39 | 83326.16 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 71919.24 | 71919.24 | 384.82 | 02-JAN-06:02 | 384.82 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.403471E+09 | 0.277275E+09 | 20879.94 | 27-MAR-16:00 | 17497.44 | 0.00 |
April | 0.00 | 0.00 | 0.440934E+10 | 0.400729E+10 | 47447.30 | 07-APR-14:05 | 47447.30 | 0.00 |
May | 0.00 | 0.00 | 0.158416E+11 | 0.136287E+11 | 81476.65 | 30-MAY-14:05 | 81476.65 | 0.00 |
June | 0.00 | 0.00 | 0.521287E+11 | 0.406926E+11 | 101065.34 | 27-JUN-06:03 | 61649.20 | 0.00 |
July | 0.00 | 0.00 | 0.736428E+11 | 0.544320E+11 | 104544.68 | 22-JUL-05:03 | 59712.76 | 0.00 |
August | 0.00 | 0.00 | 0.736657E+11 | 0.586608E+11 | 101931.90 | 17-AUG-06:03 | 63040.10 | 0.00 |
September | 0.00 | 0.00 | 0.367149E+11 | 0.294937E+11 | 100031.36 | 01-SEP-05:02 | 69069.31 | 0.00 |
October | 0.00 | 0.00 | 0.159847E+11 | 0.113497E+11 | 59693.46 | 04-OCT-14:05 | 47532.59 | 0.00 |
November | 0.00 | 0.00 | 0.377169E+09 | 0.318967E+09 | 9666.88 | 03-NOV-14:05 | 9666.88 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.273168E+12 | 0.212861E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.736657E+11 | 0.586608E+11 | 104544.68 | 81476.65 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 272738.50 | 258185.14 | 241.46 | 10-JAN-05:30 | 218.39 | 0.00 |
February | 0.00 | 0.00 | 244378.48 | 237730.92 | 681.59 | 07-FEB-06:07 | 681.59 | 0.00 |
March | 0.00 | 0.00 | 0.504191E+09 | 0.363888E+09 | 21771.32 | 27-MAR-16:00 | 17092.58 | 0.00 |
April | 0.00 | 0.00 | 0.487899E+10 | 0.441621E+10 | 50639.15 | 07-APR-14:30 | 50639.15 | 0.00 |
May | 0.00 | 0.00 | 0.165986E+11 | 0.142944E+11 | 89190.45 | 30-MAY-14:10 | 89190.45 | 0.00 |
June | 0.00 | 0.00 | 0.551948E+11 | 0.432559E+11 | 106727.10 | 19-JUN-06:03 | 76937.02 | 0.00 |
July | 0.00 | 0.00 | 0.783791E+11 | 0.587698E+11 | 117797.06 | 22-JUL-05:03 | 62474.47 | 0.00 |
August | 0.00 | 0.00 | 0.782557E+11 | 0.629747E+11 | 112810.70 | 05-AUG-06:03 | 72096.87 | 0.00 |
September | 0.00 | 0.00 | 0.372832E+11 | 0.296068E+11 | 86422.62 | 01-SEP-14:20 | 86422.62 | 0.00 |
October | 0.00 | 0.00 | 0.153328E+11 | 0.107015E+11 | 62151.59 | 04-OCT-14:00 | 50849.74 | 0.00 |
November | 0.00 | 0.00 | 0.323417E+09 | 0.260058E+09 | 8151.04 | 03-NOV-14:00 | 8151.04 | 0.00 |
December | 0.00 | 0.00 | 71455.10 | 64129.42 | 238.18 | 31-DEC-09:50 | 213.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.286751E+12 | 0.224644E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 71455.10 | 64129.42 | 238.18 | 213.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783791E+11 | 0.629747E+11 | 117797.06 | 89190.45 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 28237.10 | 201585.14 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26444.15 | 190375.98 | 06-FEB-07:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10555.93 | 189371.78 | 08-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2948.29 | 177375.87 | 04-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 162.22 | 42715.90 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.79 | 1372.05 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1.11 | 7.69 | 21-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1.13 | 8.35 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 4.22 | 11599.79 | 20-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 438.85 | 79075.88 | 28-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 8139.14 | 171558.92 | 28-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17945.38 | 173717.93 | 20-DEC-07:02 |
Annual Sum or Average | 0.00 | 7810.42 | ||||
Minimum of Months | 0.00 | 0.00 | 0.79 | 7.69 | ||
Maximum of Months | 0.00 | 0.00 | 28237.10 | 201585.14 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1753.16 | 6437.56 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1781.51 | 6446.41 | 08-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1862.65 | 6396.64 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1644.31 | 6126.43 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1591.41 | 5771.08 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1517.24 | 5345.02 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1311.24 | 4990.77 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1431.13 | 4874.10 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1372.29 | 5103.58 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1460.48 | 5503.62 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1598.39 | 5916.29 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1633.52 | 6246.30 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1578.63 | ||||
Minimum of Months | 0.00 | 0.00 | 1311.24 | 4874.10 | ||
Maximum of Months | 0.00 | 0.00 | 1862.65 | 6446.41 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.119920E+10 | 0.30 | 2304.03 | 02-JAN-05:02 | 0.75 |
February | 0.101881E+10 | 0.28 | 1363.47 | 01-FEB-07:01 | 0.58 |
March | 0.139491E+10 | 0.30 | 2831.89 | 30-MAR-06:02 | 0.84 |
April | 0.179517E+10 | 0.31 | 5237.26 | 10-APR-15:20 | 1.20 |
May | 0.291947E+10 | 0.39 | 9909.89 | 30-MAY-14:40 | 1.78 |
June | 0.489617E+10 | 0.52 | 9909.89 | 19-JUN-05:02 | 1.78 |
July | 0.613564E+10 | 0.58 | 9909.89 | 07-JUL-06:03 | 1.78 |
August | 0.668488E+10 | 0.62 | 9909.89 | 02-AUG-06:03 | 1.78 |
September | 0.440276E+10 | 0.49 | 9909.89 | 01-SEP-05:02 | 1.78 |
October | 0.343482E+10 | 0.41 | 7176.11 | 16-OCT-15:30 | 1.45 |
November | 0.151865E+10 | 0.29 | 3885.00 | 01-NOV-06:03 | 1.00 |
December | 0.113242E+10 | 0.28 | 1483.94 | 22-DEC-08:04 | 0.60 |
Annual Sum or Average | 0.365329E+11 | 0.40 | |||
Minimum of Months | 0.101881E+10 | 0.28 | 1363.47 | 0.58 | |
Maximum of Months | 0.668488E+10 | 0.62 | 9909.89 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111515E+10 | 0.30 | 2360.50 | 03-JAN-06:12 | 0.79 |
February | 0.962694E+09 | 0.29 | 2360.50 | 01-FEB-07:01 | 0.79 |
March | 0.119462E+10 | 0.30 | 2501.04 | 29-MAR-12:01 | 0.81 |
April | 0.156133E+10 | 0.32 | 5656.00 | 10-APR-14:05 | 1.32 |
May | 0.265665E+10 | 0.39 | 9234.62 | 30-MAY-06:03 | 1.78 |
June | 0.432149E+10 | 0.51 | 9234.62 | 19-JUN-05:02 | 1.78 |
July | 0.529303E+10 | 0.55 | 9234.62 | 03-JUL-05:12 | 1.78 |
August | 0.580775E+10 | 0.59 | 9234.62 | 02-AUG-06:03 | 1.78 |
September | 0.330076E+10 | 0.43 | 9234.62 | 01-SEP-05:02 | 1.78 |
October | 0.234213E+10 | 0.36 | 6287.61 | 04-OCT-15:50 | 1.39 |
November | 0.108251E+10 | 0.28 | 2863.40 | 03-NOV-14:05 | 0.87 |
December | 0.990383E+09 | 0.27 | 2360.50 | 07-DEC-07:01 | 0.79 |
Annual Sum or Average | 0.306285E+11 | 0.38 | |||
Minimum of Months | 0.962694E+09 | 0.27 | 2360.50 | 0.79 | |
Maximum of Months | 0.580775E+10 | 0.59 | 9234.62 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142249E+10 | 0.37 | 2370.19 | 01-JAN-02:62 | 0.73 |
February | 0.121169E+10 | 0.35 | 2370.19 | 01-FEB-06:01 | 0.73 |
March | 0.128597E+10 | 0.33 | 2370.19 | 01-MAR-06:11 | 0.72 |
April | 0.153862E+10 | 0.33 | 4911.01 | 07-APR-14:50 | 1.09 |
May | 0.250273E+10 | 0.38 | 9930.04 | 30-MAY-14:20 | 1.70 |
June | 0.407227E+10 | 0.46 | 10741.15 | 19-JUN-05:02 | 1.78 |
July | 0.508889E+10 | 0.51 | 10741.15 | 31-JUL-05:12 | 1.78 |
August | 0.558423E+10 | 0.53 | 10285.09 | 14-AUG-14:50 | 1.73 |
September | 0.296232E+10 | 0.40 | 8420.38 | 05-SEP-15:10 | 1.52 |
October | 0.201448E+10 | 0.34 | 5691.00 | 04-OCT-15:40 | 1.19 |
November | 0.114563E+10 | 0.31 | 2370.19 | 13-NOV-07:03 | 0.72 |
December | 0.116540E+10 | 0.32 | 2370.19 | 01-DEC-07:03 | 0.73 |
Annual Sum or Average | 0.299947E+11 | 0.38 | |||
Minimum of Months | 0.114563E+10 | 0.31 | 2370.19 | 0.72 | |
Maximum of Months | 0.558423E+10 | 0.53 | 10741.15 | 1.78 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.525955E+09 | 0.478093E+09 | 786.42 | 02-JAN-07:01 | 714.86 | 714.86 | 41.95 | 2.55 |
February | 0.459620E+09 | 0.417795E+09 | 749.50 | 06-FEB-07:01 | 681.30 | 681.30 | 42.39 | 2.43 |
March | 0.217765E+09 | 0.197948E+09 | 681.70 | 23-MAR-06:01 | 619.67 | 619.67 | 41.72 | 2.18 |
April | 58608119.85 | 53274780.94 | 627.05 | 03-APR-06:01 | 569.99 | 569.99 | 39.36 | 1.83 |
May | 5619771.07 | 5108371.90 | 378.94 | 01-MAY-06:03 | 344.45 | 344.45 | 40.87 | 0.53 |
June | 24501.27 | 22271.66 | 16.99 | 02-JUN-06:10 | 15.44 | 15.44 | 41.32 | 0.02 |
July | 32034.38 | 29119.25 | 0.08 | 05-JUL-11:50 | 0.08 | 0.08 | 39.37 | 0.00 |
August | 30209.93 | 27460.83 | 0.08 | 18-AUG-05:03 | 0.07 | 0.07 | 36.36 | 0.00 |
September | 99639.84 | 90572.62 | 102.97 | 20-SEP-06:07 | 93.60 | 93.60 | 35.40 | 0.11 |
October | 9473611.22 | 8611512.60 | 423.27 | 28-OCT-06:03 | 384.76 | 384.76 | 30.32 | 0.64 |
November | 0.157811E+09 | 0.143450E+09 | 696.18 | 24-NOV-07:01 | 632.83 | 632.83 | 43.53 | 2.25 |
December | 0.356306E+09 | 0.323882E+09 | 681.24 | 22-DEC-07:01 | 619.24 | 619.24 | 42.04 | 2.18 |
Annual Sum or Average | 0.179134E+10 | 0.162833E+10 | ||||||
Minimum of Months | 24501.27 | 22271.66 | 0.08 | 0.07 | 0.07 | 30.32 | 0.00 | |
Maximum of Months | 0.525955E+09 | 0.478093E+09 | 786.42 | 714.86 | 714.86 | 43.53 | 2.55 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:03 | 2.06 | 2.06 | 58.09 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 57.16 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 56.75 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.87 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.36 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.46 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.68 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:02 | 2.06 | 2.06 | 57.76 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.33 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.28 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 56.99 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.75 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.33 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 45.82 | 45.82 | 28237.10 | 201585.14 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 42.25 | 42.25 | 26444.15 | 190375.98 | 06-FEB-07:07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.12 | 33.12 | 10555.93 | 189371.78 | 08-MAR-07:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.75 | 25.75 | 2948.29 | 177375.87 | 04-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 39.16 | 39.16 | 162.22 | 42715.90 | 01-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 41.50 | 41.50 | 0.79 | 1372.05 | 02-JUN-06:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 39.56 | 39.56 | 1.11 | 7.69 | 21-JUL-12:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 37.46 | 37.46 | 1.13 | 8.35 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35.63 | 35.63 | 4.22 | 11599.79 | 20-SEP-06:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 32.68 | 32.68 | 438.85 | 79075.88 | 28-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 33.89 | 33.89 | 8139.14 | 171558.92 | 28-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30.96 | 30.96 | 17945.38 | 173717.93 | 20-DEC-07:02 |
Annual Sum or Average | 0.00 | 7810.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.75 | 25.75 | 0.79 | 7.69 | ||
Maximum of Months | 0.00 | 0.00 | 45.82 | 45.82 | 28237.10 | 201585.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 58.09 | 58.09 | 1753.16 | 6437.56 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.54 | 57.54 | 1781.51 | 6446.41 | 08-FEB-12:13 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.55 | 57.55 | 1862.65 | 6396.64 | 01-MAR-12:13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.65 | 57.65 | 1644.31 | 6126.43 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.25 | 58.25 | 1591.41 | 5771.08 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.96 | 57.96 | 1517.24 | 5345.02 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.09 | 58.09 | 1311.24 | 4990.77 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.16 | 58.16 | 1431.13 | 4874.10 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.15 | 58.15 | 1372.29 | 5103.58 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.25 | 57.25 | 1460.48 | 5503.62 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.90 | 57.90 | 1598.39 | 5916.29 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.74 | 57.74 | 1633.52 | 6246.30 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1578.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.25 | 57.25 | 1311.24 | 4874.10 | ||
Maximum of Months | 0.00 | 0.00 | 58.25 | 58.25 | 1862.65 | 6446.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.229862E+11 | 0.00 | 0.00 | 0.119940E+10 | 0.00 | 0.00 |
February | 0.199221E+11 | 0.00 | 0.00 | 0.101881E+10 | 0.00 | 0.00 |
March | 0.964836E+10 | 0.00 | 0.00 | 0.151313E+10 | 0.00 | 0.00 |
April | 0.260730E+10 | 0.00 | 0.00 | 0.310893E+10 | 0.00 | 0.00 |
May | 0.368162E+09 | 0.00 | 0.00 | 0.683037E+10 | 0.00 | 0.00 |
June | 2021835.96 | 0.00 | 0.00 | 0.177578E+11 | 0.00 | 0.00 |
July | 1601386.42 | 0.00 | 0.00 | 0.246400E+11 | 0.00 | 0.00 |
August | 1517261.44 | 0.00 | 0.00 | 0.259423E+11 | 0.00 | 0.00 |
September | 10803365.59 | 0.00 | 0.00 | 0.141891E+11 | 0.00 | 0.00 |
October | 0.297927E+09 | 0.00 | 0.00 | 0.817860E+10 | 0.00 | 0.00 |
November | 0.572015E+10 | 0.00 | 0.00 | 0.201318E+10 | 0.00 | 0.00 |
December | 0.139178E+11 | 0.00 | 0.00 | 0.113243E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.754839E+11 | 0.00 | 0.00 | 0.107524E+12 | 0.00 | 0.00 |
Minimum of Months | 1517261.44 | 0.00 | 0.00 | 0.101881E+10 | 0.00 | 0.00 |
Maximum of Months | 0.229862E+11 | 0.00 | 0.00 | 0.259423E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.217077E+11 | 0.00 | 0.00 | 0.111517E+10 | 0.00 | 0.00 |
February | 0.178529E+11 | 0.00 | 0.00 | 0.962694E+09 | 0.00 | 0.00 |
March | 0.777268E+10 | 0.00 | 0.00 | 0.129229E+10 | 0.00 | 0.00 |
April | 0.195182E+10 | 0.00 | 0.00 | 0.260430E+10 | 0.00 | 0.00 |
May | 21262511.70 | 0.00 | 0.00 | 0.635503E+10 | 0.00 | 0.00 |
June | 609927.34 | 0.00 | 0.00 | 0.160229E+11 | 0.00 | 0.00 |
July | 1309629.85 | 0.00 | 0.00 | 0.219723E+11 | 0.00 | 0.00 |
August | 1306562.94 | 0.00 | 0.00 | 0.227175E+11 | 0.00 | 0.00 |
September | 377293.59 | 0.00 | 0.00 | 0.115173E+11 | 0.00 | 0.00 |
October | 0.303128E+09 | 0.00 | 0.00 | 0.591474E+10 | 0.00 | 0.00 |
November | 0.581618E+10 | 0.00 | 0.00 | 0.118009E+10 | 0.00 | 0.00 |
December | 0.133436E+11 | 0.00 | 0.00 | 0.990383E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.687729E+11 | 0.00 | 0.00 | 0.926448E+11 | 0.00 | 0.00 |
Minimum of Months | 377293.59 | 0.00 | 0.00 | 0.962694E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217077E+11 | 0.00 | 0.00 | 0.227175E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.315083E+11 | 0.00 | 0.00 | 0.142256E+10 | 0.00 | 0.00 |
February | 0.266994E+11 | 0.00 | 0.00 | 0.121176E+10 | 0.00 | 0.00 |
March | 0.110890E+11 | 0.00 | 0.00 | 0.141044E+10 | 0.00 | 0.00 |
April | 0.313702E+10 | 0.00 | 0.00 | 0.269649E+10 | 0.00 | 0.00 |
May | 49197197.83 | 0.00 | 0.00 | 0.640020E+10 | 0.00 | 0.00 |
June | 689452.86 | 0.00 | 0.00 | 0.165443E+11 | 0.00 | 0.00 |
July | 1439990.71 | 0.00 | 0.00 | 0.229117E+11 | 0.00 | 0.00 |
August | 1410692.79 | 0.00 | 0.00 | 0.236225E+11 | 0.00 | 0.00 |
September | 1738829.83 | 0.00 | 0.00 | 0.113865E+11 | 0.00 | 0.00 |
October | 0.583650E+09 | 0.00 | 0.00 | 0.547908E+10 | 0.00 | 0.00 |
November | 0.973141E+10 | 0.00 | 0.00 | 0.123023E+10 | 0.00 | 0.00 |
December | 0.211754E+11 | 0.00 | 0.00 | 0.116542E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103979E+12 | 0.00 | 0.00 | 0.954812E+11 | 0.00 | 0.00 |
Minimum of Months | 689452.86 | 0.00 | 0.00 | 0.116542E+10 | 0.00 | 0.00 |
Maximum of Months | 0.315083E+11 | 0.00 | 0.00 | 0.236225E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.119920E+10 | 736095.72 | 0.229862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101881E+10 | 0.00 | 0.199221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139491E+10 | 0.489143E+09 | 0.964836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179517E+10 | 0.554220E+10 | 0.260730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291947E+10 | 0.167382E+11 | 0.368162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.489617E+10 | 0.575169E+11 | 2021835.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.613564E+10 | 0.816836E+11 | 1601386.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668488E+10 | 0.839288E+11 | 1517261.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.440276E+10 | 0.441044E+11 | 10803365.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343482E+10 | 0.213509E+11 | 0.297927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151865E+10 | 0.199548E+10 | 0.572015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113242E+10 | 53423.69 | 0.139178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365329E+11 | 0.313350E+12 | 0.754839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101881E+10 | 0.00 | 1517261.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668488E+10 | 0.839288E+11 | 0.229862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111515E+10 | 71919.24 | 0.217077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962694E+09 | 0.00 | 0.178529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119462E+10 | 0.403471E+09 | 0.777268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156133E+10 | 0.440934E+10 | 0.195182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265665E+10 | 0.158416E+11 | 21262511.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432149E+10 | 0.521287E+11 | 609927.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.529303E+10 | 0.736428E+11 | 1309629.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.580775E+10 | 0.736657E+11 | 1306562.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330076E+10 | 0.367149E+11 | 377293.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234213E+10 | 0.159847E+11 | 0.303128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108251E+10 | 0.377169E+09 | 0.581618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990383E+09 | 0.00 | 0.133436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306285E+11 | 0.273168E+12 | 0.687729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962694E+09 | 0.00 | 377293.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580775E+10 | 0.736657E+11 | 0.217077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142249E+10 | 272738.50 | 0.315083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121169E+10 | 244378.48 | 0.266994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128597E+10 | 0.504191E+09 | 0.110890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153862E+10 | 0.487899E+10 | 0.313702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250273E+10 | 0.165986E+11 | 49197197.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407227E+10 | 0.551948E+11 | 689452.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.508889E+10 | 0.783791E+11 | 1439990.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558423E+10 | 0.782557E+11 | 1410692.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296232E+10 | 0.372832E+11 | 1738829.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201448E+10 | 0.153328E+11 | 0.583650E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114563E+10 | 0.323417E+09 | 0.973141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116540E+10 | 71455.10 | 0.211754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299947E+11 | 0.286751E+12 | 0.103979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114563E+10 | 71455.10 | 689452.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.558423E+10 | 0.783791E+11 | 0.315083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.119920E+10 | 0.229862E+11 | 0.00 | 0.00 | 198332.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101881E+10 | 0.199221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139491E+10 | 0.964836E+10 | 0.00 | 0.00 | 0.118218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179517E+10 | 0.260730E+10 | 0.00 | 0.00 | 0.131376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291947E+10 | 0.368162E+09 | 0.00 | 0.00 | 0.391089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.489617E+10 | 2021835.96 | 0.00 | 0.00 | 0.128617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.613564E+10 | 1601386.42 | 0.00 | 0.00 | 0.185043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.668488E+10 | 1517261.44 | 0.00 | 0.00 | 0.192574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.440276E+10 | 10803365.59 | 0.00 | 0.00 | 0.978636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343482E+10 | 0.297927E+09 | 0.00 | 0.00 | 0.474378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151865E+10 | 0.572015E+10 | 0.00 | 0.00 | 0.494540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113242E+10 | 0.139178E+11 | 0.00 | 0.00 | 14493.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.365329E+11 | 0.754839E+11 | 0.00 | 0.00 | 0.709911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.101881E+10 | 1517261.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.668488E+10 | 0.229862E+11 | 0.00 | 0.00 | 0.192574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111515E+10 | 0.217077E+11 | 0.00 | 0.00 | 19527.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962694E+09 | 0.178529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119462E+10 | 0.777268E+10 | 0.00 | 0.00 | 97666017.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156133E+10 | 0.195182E+10 | 0.00 | 0.00 | 0.104296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265665E+10 | 21262511.70 | 0.00 | 0.00 | 0.369838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.432149E+10 | 609927.34 | 0.00 | 0.00 | 0.117015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.529303E+10 | 1309629.85 | 0.00 | 0.00 | 0.166793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.580775E+10 | 1306562.94 | 0.00 | 0.00 | 0.169097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330076E+10 | 377293.59 | 0.00 | 0.00 | 0.821656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234213E+10 | 0.303128E+09 | 0.00 | 0.00 | 0.357261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108251E+10 | 0.581618E+10 | 0.00 | 0.00 | 97578632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.990383E+09 | 0.133436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306285E+11 | 0.687729E+11 | 0.00 | 0.00 | 0.620163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.962694E+09 | 377293.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.580775E+10 | 0.217077E+11 | 0.00 | 0.00 | 0.169097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142249E+10 | 0.315083E+11 | 0.00 | 0.00 | 74159.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121169E+10 | 0.266994E+11 | 0.00 | 0.00 | 66320.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128597E+10 | 0.110890E+11 | 0.00 | 0.00 | 0.124475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153862E+10 | 0.313702E+10 | 0.00 | 0.00 | 0.115787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250273E+10 | 49197197.83 | 0.00 | 0.00 | 0.389747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.407227E+10 | 689452.86 | 0.00 | 0.00 | 0.124721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.508889E+10 | 1439990.71 | 0.00 | 0.00 | 0.178228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558423E+10 | 1410692.79 | 0.00 | 0.00 | 0.180383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.296232E+10 | 1738829.83 | 0.00 | 0.00 | 0.842421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201448E+10 | 0.583650E+09 | 0.00 | 0.00 | 0.346460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114563E+10 | 0.973141E+10 | 0.00 | 0.00 | 84597696.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116540E+10 | 0.211754E+11 | 0.00 | 0.00 | 19424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299947E+11 | 0.103979E+12 | 0.00 | 0.00 | 0.654865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114563E+10 | 689452.86 | 0.00 | 0.00 | 19424.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.558423E+10 | 0.315083E+11 | 0.00 | 0.00 | 0.180383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959937E+10 | 0.00 | 0.00 | 6289021.20 | 0.00 | 0.611846E+09 | 0.517507E+10 | 0.00 | 0.30 |
February | 0.792411E+10 | 0.00 | 0.00 | 8938185.40 | 0.00 | 0.00 | 0.766476E+10 | 0.00 | 0.31 |
March | 0.198512E+10 | 0.00 | 0.00 | 29291598.33 | 0.00 | 0.00 | 0.170633E+11 | 0.00 | 0.44 |
April | 0.790667E+09 | 6191758.30 | 0.00 | 33021585.40 | 0.00 | 0.00 | 0.157430E+11 | 0.00 | 0.58 |
May | 0.674468E+09 | 0.108853E+09 | 0.00 | 40291199.60 | 0.00 | 0.00 | 0.168721E+11 | 0.00 | 0.95 |
June | 0.186427E+09 | 0.330397E+10 | 0.00 | 17338181.66 | 40208461.65 | 0.00 | 0.361957E+10 | 0.00 | 0.65 |
July | 5925209.16 | 0.813895E+10 | 0.00 | 1303153.44 | 0.108815E+09 | 0.00 | 0.141475E+09 | 0.00 | 0.29 |
August | 0.104959E+09 | 0.635748E+10 | 0.00 | 13850286.90 | 88300936.61 | 0.00 | 0.162034E+10 | 0.00 | 0.53 |
September | 0.519935E+09 | 0.205177E+10 | 0.00 | 28421720.48 | 14775439.97 | 0.00 | 0.852048E+10 | 0.00 | 0.80 |
October | 0.927675E+09 | 0.177778E+09 | 0.00 | 43238124.17 | 0.00 | 0.00 | 0.153120E+11 | 0.00 | 0.84 |
November | 0.203427E+10 | 0.00 | 0.00 | 29982561.90 | 0.00 | 0.00 | 0.156074E+11 | 0.00 | 0.48 |
December | 0.465089E+10 | 0.00 | 0.00 | 16651275.98 | 0.00 | 0.00 | 0.119822E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.294038E+11 | 0.201450E+11 | 0.00 | 0.268617E+09 | 0.252099E+09 | 0.611846E+09 | 0.119322E+12 | 0.00 | 0.54 |
Minimum of Months | 5925209.16 | 0.00 | 0.00 | 1303153.44 | 0.00 | 0.00 | 0.141475E+09 | 0.00 | 0.29 |
Maximum of Months | 0.959937E+10 | 0.813895E+10 | 0.00 | 43238124.17 | 0.108815E+09 | 0.611846E+09 | 0.170633E+11 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130829E+11 | 0.00 | 0.00 | 293.25 | 0.00 | 0.122127E+10 | 12060572.06 | 0.00 | 0.28 |
February | 0.133969E+11 | 0.00 | 0.00 | 6038.74 | 0.00 | 0.446727E+09 | 67860422.35 | 0.00 | 0.28 |
March | 0.109287E+11 | 0.00 | 0.00 | 3015226.23 | 0.00 | 5451992.14 | 0.318874E+10 | 0.00 | 0.33 |
April | 0.502449E+10 | 3927176.11 | 0.00 | 11520567.91 | 0.00 | 0.00 | 0.691172E+10 | 0.00 | 0.42 |
May | 0.195645E+10 | 79428536.14 | 0.00 | 21814648.64 | 0.00 | 0.00 | 0.968182E+10 | 0.00 | 0.64 |
June | 0.293774E+09 | 0.252958E+10 | 0.00 | 11009213.25 | 39334444.18 | 0.00 | 0.235970E+10 | 0.00 | 0.46 |
July | 7265237.83 | 0.670954E+10 | 0.00 | 1007709.29 | 0.105241E+09 | 0.00 | 0.104785E+09 | 0.00 | 0.24 |
August | 0.129888E+09 | 0.538310E+10 | 0.00 | 9223082.67 | 88692689.70 | 0.00 | 0.107619E+10 | 0.00 | 0.41 |
September | 0.776922E+09 | 0.166338E+10 | 0.00 | 15611920.47 | 17622292.76 | 0.00 | 0.493469E+10 | 0.00 | 0.54 |
October | 0.208211E+10 | 0.140716E+09 | 0.00 | 19788682.09 | 415802.77 | 0.00 | 0.825204E+10 | 0.00 | 0.54 |
November | 0.855867E+10 | 0.00 | 0.00 | 5414302.99 | 0.00 | 24619151.42 | 0.381019E+10 | 0.00 | 0.34 |
December | 0.132614E+11 | 0.00 | 0.00 | 107851.60 | 0.00 | 71780600.75 | 0.339524E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.694995E+11 | 0.165097E+11 | 0.00 | 98519537.14 | 0.251306E+09 | 0.176985E+10 | 0.407393E+11 | 0.00 | 0.40 |
Minimum of Months | 7265237.83 | 0.00 | 0.00 | 293.25 | 0.00 | 0.00 | 12060572.06 | 0.00 | 0.24 |
Maximum of Months | 0.133969E+11 | 0.670954E+10 | 0.00 | 21814648.64 | 0.105241E+09 | 0.122127E+10 | 0.968182E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.987845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349179E+10 | 0.00 | 0.00 | 0.27 |
February | 0.104865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253156E+10 | 0.00 | 0.00 | 0.28 |
March | 0.116600E+11 | 0.00 | 0.00 | 1411560.99 | 0.00 | 0.353584E+09 | 0.143844E+10 | 0.00 | 0.32 |
April | 0.617646E+10 | 2017419.03 | 0.00 | 8547580.34 | 0.00 | 39628998.03 | 0.502693E+10 | 0.00 | 0.41 |
May | 0.275441E+10 | 74152979.37 | 0.00 | 18840228.88 | 0.00 | 0.00 | 0.876913E+10 | 0.00 | 0.62 |
June | 0.426396E+09 | 0.251185E+10 | 0.00 | 10818194.25 | 36594909.97 | 0.00 | 0.233091E+10 | 0.00 | 0.48 |
July | 8313051.22 | 0.663138E+10 | 0.00 | 1095687.79 | 97520210.67 | 0.00 | 97770920.87 | 0.00 | 0.25 |
August | 0.148255E+09 | 0.528635E+10 | 0.00 | 8883000.33 | 83234842.29 | 0.00 | 0.984120E+09 | 0.00 | 0.42 |
September | 0.140153E+10 | 0.167916E+10 | 0.00 | 12012094.96 | 17728075.73 | 0.00 | 0.378559E+10 | 0.00 | 0.52 |
October | 0.342592E+10 | 0.103749E+09 | 0.00 | 12495957.14 | 828070.65 | 0.00 | 0.552603E+10 | 0.00 | 0.50 |
November | 0.871311E+10 | 0.00 | 0.00 | 1997351.19 | 0.00 | 0.692101E+09 | 0.178105E+10 | 0.00 | 0.32 |
December | 0.111611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149153E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.662404E+11 | 0.162887E+11 | 0.00 | 76101655.86 | 0.235906E+09 | 0.860020E+10 | 0.297400E+11 | 0.00 | 0.39 |
Minimum of Months | 8313051.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.116600E+11 | 0.663138E+10 | 0.00 | 18840228.88 | 97520210.67 | 0.349179E+10 | 0.876913E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.414820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274116E+10 | 0.00 | 0.00 | 0.30 |
February | 0.497048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256354E+10 | 0.00 | 0.00 | 0.30 |
March | 0.183167E+10 | 0.00 | 0.00 | 83366.48 | 0.00 | 0.943502E+09 | 79454812.49 | 0.00 | 0.32 |
April | 0.143686E+10 | 538445.98 | 0.00 | 1408944.07 | 0.00 | 0.229420E+09 | 0.704679E+09 | 0.00 | 0.42 |
May | 0.755207E+09 | 23474253.52 | 0.00 | 4487160.41 | 0.00 | 1220127.53 | 0.192665E+10 | 0.00 | 0.72 |
June | 91869817.13 | 0.797941E+09 | 0.00 | 3046410.41 | 8021820.46 | 0.00 | 0.639127E+09 | 0.00 | 0.65 |
July | 1387910.30 | 0.218182E+10 | 0.00 | 328434.05 | 20731953.88 | 0.00 | 27087491.27 | 0.00 | 0.38 |
August | 35588946.67 | 0.172034E+10 | 0.00 | 2448129.34 | 18450443.00 | 0.00 | 0.255920E+09 | 0.00 | 0.58 |
September | 0.394412E+09 | 0.435563E+09 | 0.00 | 2559069.22 | 6913330.32 | 0.00 | 0.749020E+09 | 0.00 | 0.58 |
October | 0.101130E+10 | 23267541.81 | 0.00 | 1847835.31 | 1836222.66 | 36002522.21 | 0.719999E+09 | 0.00 | 0.48 |
November | 0.135951E+10 | 0.00 | 0.00 | 54453.14 | 0.00 | 0.939183E+09 | 71976703.02 | 0.00 | 0.31 |
December | 0.648227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209989E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.847790E+10 | 0.518294E+10 | 0.00 | 16263802.42 | 55953770.31 | 0.955392E+10 | 0.517391E+10 | 0.00 | 0.45 |
Minimum of Months | 1387910.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.183167E+10 | 0.218182E+10 | 0.00 | 4487160.41 | 20731953.88 | 0.274116E+10 | 0.192665E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.506488E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145947E+10 | 0.00 | 0.00 | 0.30 |
February | 0.704380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114308E+10 | 0.00 | 0.00 | 0.29 |
March | 0.111832E+10 | 0.00 | 0.00 | 896592.60 | 0.00 | 0.367029E+09 | 0.534983E+09 | 0.00 | 0.36 |
April | 0.692682E+09 | 1102044.28 | 0.00 | 2884890.61 | 0.00 | 0.115118E+09 | 0.139523E+10 | 0.00 | 0.65 |
May | 0.355784E+09 | 24920906.43 | 0.00 | 5984778.99 | 0.00 | 0.00 | 0.238712E+10 | 0.00 | 1.13 |
June | 36209985.41 | 0.655514E+09 | 0.00 | 3545382.67 | 5084854.59 | 0.00 | 0.770319E+09 | 0.00 | 0.94 |
July | 493351.83 | 0.181963E+10 | 0.00 | 397634.13 | 13141527.08 | 0.00 | 38418772.09 | 0.00 | 0.53 |
August | 15251700.72 | 0.156169E+10 | 0.00 | 2899658.13 | 11119847.90 | 0.00 | 0.327800E+09 | 0.00 | 0.92 |
September | 0.165935E+09 | 0.360055E+09 | 0.00 | 3819895.82 | 4114436.86 | 0.00 | 0.100789E+10 | 0.00 | 0.88 |
October | 0.435984E+09 | 20530735.20 | 0.00 | 3220979.43 | 449292.61 | 11741646.74 | 0.122810E+10 | 0.00 | 0.75 |
November | 0.845543E+09 | 0.00 | 0.00 | 405894.41 | 0.00 | 0.418360E+09 | 0.293378E+09 | 0.00 | 0.33 |
December | 0.712730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102584E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.558980E+10 | 0.444345E+10 | 0.00 | 24055706.77 | 33909959.03 | 0.454064E+10 | 0.798324E+10 | 0.00 | 0.62 |
Minimum of Months | 493351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.111832E+10 | 0.181963E+10 | 0.00 | 5984778.99 | 13141527.08 | 0.145947E+10 | 0.238712E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.886387E+09 | 0.00 | 0.00 | 1358010.59 | 0.00 | 0.166888E+10 | 0.896280E+09 | 0.00 | 0.33 |
February | 0.103428E+10 | 0.00 | 0.00 | 1947811.29 | 0.00 | 0.132065E+10 | 0.126373E+10 | 0.00 | 0.36 |
March | 0.150489E+10 | 0.00 | 0.00 | 4994458.63 | 0.00 | 0.465693E+09 | 0.268918E+10 | 0.00 | 0.55 |
April | 0.115734E+10 | 1397120.05 | 0.00 | 5074560.92 | 0.00 | 0.189944E+09 | 0.232610E+10 | 0.00 | 0.69 |
May | 0.705911E+09 | 29427146.36 | 0.00 | 6825061.52 | 0.00 | 2441080.56 | 0.281769E+10 | 0.00 | 0.94 |
June | 0.106830E+09 | 0.897180E+09 | 0.00 | 3713654.00 | 8286900.73 | 0.00 | 0.759985E+09 | 0.00 | 0.75 |
July | 4247947.95 | 0.249251E+10 | 0.00 | 386498.48 | 21178345.49 | 0.00 | 25255293.04 | 0.00 | 0.43 |
August | 32700026.26 | 0.227486E+10 | 0.00 | 4205348.70 | 18023026.65 | 0.00 | 0.396334E+09 | 0.00 | 0.84 |
September | 0.265873E+09 | 0.643554E+09 | 0.00 | 7805688.83 | 6573367.14 | 0.00 | 0.194760E+10 | 0.00 | 1.06 |
October | 0.529570E+09 | 63156651.42 | 0.00 | 10209004.35 | 137748.99 | 12615390.97 | 0.392568E+10 | 0.00 | 1.20 |
November | 0.113498E+10 | 0.00 | 0.00 | 3471977.33 | 0.00 | 0.492673E+09 | 0.199296E+10 | 0.00 | 0.52 |
December | 0.102687E+10 | 0.00 | 0.00 | 1711264.29 | 0.00 | 0.125409E+10 | 0.102328E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.838987E+10 | 0.640209E+10 | 0.00 | 51703338.93 | 54199388.99 | 0.540698E+10 | 0.200641E+11 | 0.00 | 0.67 |
Minimum of Months | 4247947.95 | 0.00 | 0.00 | 386498.48 | 0.00 | 0.00 | 25255293.04 | 0.00 | 0.33 |
Maximum of Months | 0.150489E+10 | 0.249251E+10 | 0.00 | 10209004.35 | 21178345.49 | 0.166888E+10 | 0.392568E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.445156E+09 | 0.00 | 0.00 | 32471.85 | 0.00 | 0.157236E+10 | 39919776.00 | 0.00 | 0.31 |
February | 0.507627E+09 | 0.00 | 0.00 | 120390.52 | 0.00 | 0.143004E+10 | 0.123256E+09 | 0.00 | 0.32 |
March | 0.102546E+10 | 0.00 | 0.00 | 1454899.75 | 0.00 | 0.453382E+09 | 0.845251E+09 | 0.00 | 0.43 |
April | 0.764536E+09 | 408296.41 | 0.00 | 3072047.59 | 0.00 | 0.131765E+09 | 0.137839E+10 | 0.00 | 0.68 |
May | 0.377129E+09 | 22518354.25 | 0.00 | 5656422.86 | 0.00 | 1472765.05 | 0.219023E+10 | 0.00 | 1.10 |
June | 58546927.19 | 0.691030E+09 | 0.00 | 3119451.65 | 3750105.50 | 0.00 | 0.603274E+09 | 0.00 | 0.94 |
July | 2134296.57 | 0.185177E+10 | 0.00 | 260395.84 | 5854231.84 | 0.00 | 16830204.66 | 0.00 | 0.50 |
August | 21008733.70 | 0.161889E+10 | 0.00 | 2532005.78 | 6579491.31 | 0.00 | 0.227910E+09 | 0.00 | 0.89 |
September | 0.206235E+09 | 0.397453E+09 | 0.00 | 3558775.70 | 3294872.40 | 0.00 | 0.868264E+09 | 0.00 | 0.87 |
October | 0.510285E+09 | 31778763.39 | 0.00 | 3089238.25 | 104511.47 | 17935568.73 | 0.121729E+10 | 0.00 | 0.78 |
November | 0.809741E+09 | 0.00 | 0.00 | 406378.80 | 0.00 | 0.538276E+09 | 0.278952E+09 | 0.00 | 0.35 |
December | 0.514137E+09 | 0.00 | 0.00 | 19081.12 | 0.00 | 0.120366E+10 | 30139383.09 | 0.00 | 0.29 |
Annual Sum or Average | 0.524200E+10 | 0.461385E+10 | 0.00 | 23321559.72 | 19583212.52 | 0.534889E+10 | 0.781970E+10 | 0.00 | 0.62 |
Minimum of Months | 2134296.57 | 0.00 | 0.00 | 19081.12 | 0.00 | 0.00 | 16830204.66 | 0.00 | 0.29 |
Maximum of Months | 0.102546E+10 | 0.185177E+10 | 0.00 | 5656422.86 | 6579491.31 | 0.157236E+10 | 0.219023E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.666718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253654E+10 | 0.00 | 0.00 | 0.29 |
February | 0.662120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250408E+10 | 0.00 | 0.00 | 0.29 |
March | 0.207156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791226E+09 | 0.00 | 0.00 | 0.31 |
April | 0.178009E+10 | 510695.52 | 0.00 | 403432.65 | 174699.99 | 89305821.20 | 0.203182E+09 | 0.00 | 0.33 |
May | 0.104973E+10 | 19500958.18 | 0.00 | 2263934.17 | 0.00 | 0.00 | 0.934819E+09 | 0.00 | 0.53 |
June | 83243166.59 | 0.597650E+09 | 0.00 | 2131044.88 | 8895602.16 | 0.00 | 0.459183E+09 | 0.00 | 0.48 |
July | 1572898.79 | 0.168234E+10 | 0.00 | 227088.70 | 22865234.01 | 0.00 | 23011056.16 | 0.00 | 0.28 |
August | 49225219.86 | 0.139453E+10 | 0.00 | 2011840.13 | 18554685.46 | 0.00 | 0.221729E+09 | 0.00 | 0.47 |
September | 0.320984E+09 | 0.360300E+09 | 0.00 | 2844638.52 | 3104764.82 | 0.00 | 0.859883E+09 | 0.00 | 0.55 |
October | 0.924413E+09 | 28647877.07 | 0.00 | 2385877.99 | 25253.42 | 0.00 | 0.929163E+09 | 0.00 | 0.48 |
November | 0.179621E+10 | 0.00 | 0.00 | 166608.46 | 0.00 | 0.386399E+09 | 0.173440E+09 | 0.00 | 0.29 |
December | 0.146705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142886E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.108729E+11 | 0.408347E+10 | 0.00 | 12434465.51 | 53620239.85 | 0.773640E+10 | 0.380441E+10 | 0.00 | 0.38 |
Minimum of Months | 1572898.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.207156E+10 | 0.168234E+10 | 0.00 | 2844638.52 | 22865234.01 | 0.253654E+10 | 0.934819E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.745329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130550E+10 | 0.00 | 0.00 | 0.29 |
February | 0.908578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104668E+10 | 0.00 | 0.00 | 0.29 |
March | 0.134751E+10 | 0.00 | 0.00 | 505481.89 | 0.00 | 0.219854E+09 | 0.317879E+09 | 0.00 | 0.32 |
April | 0.813373E+09 | 1164514.67 | 0.00 | 2042778.76 | 0.00 | 29526527.89 | 0.896011E+09 | 0.00 | 0.49 |
May | 0.424599E+09 | 23437643.41 | 0.00 | 4137681.76 | 0.00 | 0.00 | 0.164162E+10 | 0.00 | 0.89 |
June | 30652645.67 | 0.524503E+09 | 0.00 | 2732013.21 | 5459606.85 | 0.00 | 0.614242E+09 | 0.00 | 0.75 |
July | 874811.71 | 0.148681E+10 | 0.00 | 285936.71 | 14627550.75 | 0.00 | 32143829.27 | 0.00 | 0.41 |
August | 19816111.04 | 0.133919E+10 | 0.00 | 2534765.32 | 11741148.08 | 0.00 | 0.307352E+09 | 0.00 | 0.78 |
September | 0.110135E+09 | 0.321792E+09 | 0.00 | 4070320.85 | 1964652.19 | 0.00 | 0.114065E+10 | 0.00 | 0.87 |
October | 0.341289E+09 | 27991014.34 | 0.00 | 4245168.92 | 0.00 | 0.00 | 0.155107E+10 | 0.00 | 0.80 |
November | 0.107995E+10 | 0.00 | 0.00 | 901474.64 | 0.00 | 0.135842E+09 | 0.426891E+09 | 0.00 | 0.33 |
December | 0.118262E+10 | 0.00 | 0.00 | 3465.22 | 0.00 | 0.649645E+09 | 6185077.67 | 0.00 | 0.27 |
Annual Sum or Average | 0.700473E+10 | 0.372489E+10 | 0.00 | 21459087.27 | 33792957.86 | 0.338704E+10 | 0.693404E+10 | 0.00 | 0.54 |
Minimum of Months | 874811.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.134751E+10 | 0.148681E+10 | 0.00 | 4245168.92 | 14627550.75 | 0.130550E+10 | 0.164162E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.923426E+09 | 0.00 | 0.00 | 35815.35 | 0.00 | 0.337432E+10 | 47134241.52 | 0.00 | 0.39 |
February | 0.951483E+09 | 0.00 | 0.00 | 109799.70 | 0.00 | 0.315543E+10 | 0.125478E+09 | 0.00 | 0.39 |
March | 0.153894E+10 | 0.00 | 0.00 | 794086.11 | 0.00 | 0.178653E+10 | 0.507928E+09 | 0.00 | 0.41 |
April | 0.136154E+10 | 2327870.51 | 0.00 | 1612355.46 | 0.00 | 0.725134E+09 | 0.578698E+09 | 0.00 | 0.46 |
May | 0.115510E+10 | 29002251.09 | 0.00 | 2313626.79 | 295242.99 | 0.180979E+09 | 0.886707E+09 | 0.00 | 0.61 |
June | 0.134508E+09 | 0.730084E+09 | 0.00 | 2103031.18 | 21395977.48 | 547025.99 | 0.419189E+09 | 0.00 | 0.53 |
July | 6620367.48 | 0.221565E+10 | 0.00 | 261603.02 | 26810793.88 | 0.00 | 16227484.37 | 0.00 | 0.36 |
August | 62844261.72 | 0.223111E+10 | 0.00 | 3222796.37 | 21882284.46 | 0.00 | 0.294860E+09 | 0.00 | 0.72 |
September | 0.275744E+09 | 0.592417E+09 | 0.00 | 6671892.89 | 7951864.24 | 5150062.86 | 0.167982E+10 | 0.00 | 0.95 |
October | 0.483504E+09 | 77208122.52 | 0.00 | 9167784.12 | 24289.41 | 0.108132E+09 | 0.319643E+10 | 0.00 | 1.05 |
November | 0.145929E+10 | 0.00 | 0.00 | 1874280.21 | 0.00 | 0.996378E+09 | 0.975074E+09 | 0.00 | 0.45 |
December | 0.132892E+10 | 0.00 | 0.00 | 372238.05 | 0.00 | 0.225183E+10 | 0.298514E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.968190E+10 | 0.587779E+10 | 0.00 | 28539309.25 | 78360452.47 | 0.125844E+11 | 0.902606E+10 | 0.00 | 0.56 |
Minimum of Months | 6620367.48 | 0.00 | 0.00 | 35815.35 | 0.00 | 0.00 | 16227484.37 | 0.00 | 0.36 |
Maximum of Months | 0.153894E+10 | 0.223111E+10 | 0.00 | 9167784.12 | 26810793.88 | 0.337432E+10 | 0.319643E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.682490E+09 | 0.00 | 0.00 | 6222.15 | 0.00 | 0.142032E+10 | 8853764.68 | 0.00 | 0.30 |
February | 0.724497E+09 | 0.00 | 0.00 | 39712.54 | 0.00 | 0.129894E+10 | 45121804.00 | 0.00 | 0.30 |
March | 0.135061E+10 | 0.00 | 0.00 | 769779.77 | 0.00 | 0.230488E+09 | 0.414249E+09 | 0.00 | 0.35 |
April | 0.905870E+09 | 751747.72 | 0.00 | 1901657.05 | 0.00 | 39699096.70 | 0.764282E+09 | 0.00 | 0.48 |
May | 0.460843E+09 | 21385049.19 | 0.00 | 3612550.07 | 0.00 | 0.00 | 0.140532E+10 | 0.00 | 0.83 |
June | 44523429.55 | 0.588930E+09 | 0.00 | 2315002.41 | 4421899.98 | 0.00 | 0.473458E+09 | 0.00 | 0.75 |
July | 1264754.14 | 0.154454E+10 | 0.00 | 194729.31 | 8532164.33 | 0.00 | 16020971.51 | 0.00 | 0.40 |
August | 25027762.69 | 0.141896E+10 | 0.00 | 2093004.31 | 8107587.21 | 0.00 | 0.208957E+09 | 0.00 | 0.74 |
September | 0.149055E+09 | 0.353543E+09 | 0.00 | 3481103.26 | 1658932.19 | 0.00 | 0.942316E+09 | 0.00 | 0.84 |
October | 0.358925E+09 | 38463120.79 | 0.00 | 3966427.90 | 0.00 | 0.00 | 0.143008E+10 | 0.00 | 0.79 |
November | 0.109765E+10 | 0.00 | 0.00 | 569860.79 | 0.00 | 0.205261E+09 | 0.301657E+09 | 0.00 | 0.32 |
December | 0.110664E+10 | 0.00 | 0.00 | 17650.05 | 0.00 | 0.718898E+09 | 23512557.33 | 0.00 | 0.28 |
Annual Sum or Average | 0.690740E+10 | 0.396657E+10 | 0.00 | 18967699.59 | 22720583.71 | 0.391360E+10 | 0.603383E+10 | 0.00 | 0.53 |
Minimum of Months | 1264754.14 | 0.00 | 0.00 | 6222.15 | 0.00 | 0.00 | 8853764.68 | 0.00 | 0.28 |
Maximum of Months | 0.135061E+10 | 0.154454E+10 | 0.00 | 3966427.90 | 8532164.33 | 0.142032E+10 | 0.143008E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240942E+10 | 0.00 | 0.00 | 0.29 |
February | 0.931336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212321E+10 | 0.00 | 0.00 | 0.29 |
March | 0.241554E+10 | 0.00 | 0.00 | 109593.66 | 0.00 | 0.442353E+09 | 87852392.10 | 0.00 | 0.32 |
April | 0.162748E+10 | 1165669.41 | 0.00 | 1527468.80 | 0.00 | 35489301.75 | 0.769321E+09 | 0.00 | 0.43 |
May | 0.625775E+09 | 25865122.79 | 0.00 | 4950140.45 | 0.00 | 0.00 | 0.201410E+10 | 0.00 | 0.73 |
June | 68672989.35 | 0.829680E+09 | 0.00 | 2966184.17 | 8269415.47 | 0.00 | 0.617368E+09 | 0.00 | 0.63 |
July | 1716239.29 | 0.225695E+10 | 0.00 | 287543.40 | 22125134.98 | 0.00 | 27527710.30 | 0.00 | 0.38 |
August | 37881133.32 | 0.179180E+10 | 0.00 | 2329799.96 | 18651433.71 | 0.00 | 0.250999E+09 | 0.00 | 0.56 |
September | 0.323133E+09 | 0.442247E+09 | 0.00 | 2928449.72 | 3754153.60 | 0.00 | 0.875143E+09 | 0.00 | 0.59 |
October | 0.990880E+09 | 35330017.17 | 0.00 | 2360692.25 | 0.00 | 0.00 | 0.935890E+09 | 0.00 | 0.50 |
November | 0.177476E+10 | 0.00 | 0.00 | 209275.97 | 0.00 | 0.520815E+09 | 0.203788E+09 | 0.00 | 0.32 |
December | 0.137333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151796E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.109228E+11 | 0.538304E+10 | 0.00 | 17669148.37 | 52800137.75 | 0.704925E+10 | 0.578199E+10 | 0.00 | 0.44 |
Minimum of Months | 1716239.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.241554E+10 | 0.225695E+10 | 0.00 | 4950140.45 | 22125134.98 | 0.240942E+10 | 0.201410E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.608396E+09 | 0.00 | 0.00 | 158.80 | 0.00 | 0.109931E+10 | 1602757.75 | 0.00 | 0.25 |
February | 0.732025E+09 | 0.00 | 0.00 | 28636.68 | 0.00 | 0.847207E+09 | 25730454.99 | 0.00 | 0.24 |
March | 0.110698E+10 | 0.00 | 0.00 | 1139021.69 | 0.00 | 0.161286E+09 | 0.635223E+09 | 0.00 | 0.33 |
April | 0.692512E+09 | 1403780.43 | 0.00 | 2992618.15 | 0.00 | 15451984.04 | 0.138756E+10 | 0.00 | 0.62 |
May | 0.286219E+09 | 23639363.84 | 0.00 | 5870381.02 | 0.00 | 0.00 | 0.226750E+10 | 0.00 | 1.07 |
June | 25475679.25 | 0.638622E+09 | 0.00 | 3194602.70 | 5277951.96 | 0.00 | 0.711885E+09 | 0.00 | 0.85 |
July | 854380.60 | 0.178008E+10 | 0.00 | 338790.82 | 14120929.66 | 0.00 | 38410655.84 | 0.00 | 0.49 |
August | 16750417.05 | 0.152639E+10 | 0.00 | 2679708.09 | 11854255.85 | 0.00 | 0.320183E+09 | 0.00 | 0.85 |
September | 0.132311E+09 | 0.341005E+09 | 0.00 | 3994196.67 | 2403867.54 | 0.00 | 0.105045E+10 | 0.00 | 0.84 |
October | 0.420317E+09 | 28175120.89 | 0.00 | 3572855.76 | 0.00 | 0.00 | 0.134059E+10 | 0.00 | 0.74 |
November | 0.852430E+09 | 0.00 | 0.00 | 669757.36 | 0.00 | 0.242185E+09 | 0.393779E+09 | 0.00 | 0.30 |
December | 0.821360E+09 | 0.00 | 0.00 | 11977.02 | 0.00 | 0.699295E+09 | 7331346.41 | 0.00 | 0.24 |
Annual Sum or Average | 0.569563E+10 | 0.433931E+10 | 0.00 | 24492704.76 | 33657005.01 | 0.306474E+10 | 0.818024E+10 | 0.00 | 0.57 |
Minimum of Months | 854380.60 | 0.00 | 0.00 | 158.80 | 0.00 | 0.00 | 1602757.75 | 0.00 | 0.24 |
Maximum of Months | 0.110698E+10 | 0.178008E+10 | 0.00 | 5870381.02 | 14120929.66 | 0.109931E+10 | 0.226750E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126194E+10 | 0.00 | 0.00 | 1807602.03 | 0.00 | 0.126540E+10 | 0.117144E+10 | 0.00 | 0.34 |
February | 0.137838E+10 | 0.00 | 0.00 | 2517457.16 | 0.00 | 0.982741E+09 | 0.159892E+10 | 0.00 | 0.38 |
March | 0.177691E+10 | 0.00 | 0.00 | 5711701.68 | 0.00 | 0.211620E+09 | 0.286558E+10 | 0.00 | 0.57 |
April | 0.127313E+10 | 3002788.48 | 0.00 | 5322447.70 | 0.00 | 35302708.29 | 0.240070E+10 | 0.00 | 0.71 |
May | 0.611619E+09 | 33581387.09 | 0.00 | 6919704.88 | 0.00 | 0.00 | 0.274987E+10 | 0.00 | 0.94 |
June | 82333980.72 | 0.950695E+09 | 0.00 | 3442342.69 | 8269765.63 | 0.00 | 0.693152E+09 | 0.00 | 0.72 |
July | 1716311.96 | 0.261327E+10 | 0.00 | 321703.51 | 22186837.27 | 0.00 | 26609694.40 | 0.00 | 0.43 |
August | 36038687.65 | 0.241129E+10 | 0.00 | 3705125.77 | 18691105.80 | 0.00 | 0.350658E+09 | 0.00 | 0.79 |
September | 0.235303E+09 | 0.667725E+09 | 0.00 | 8107960.44 | 3704952.09 | 0.00 | 0.192811E+10 | 0.00 | 1.06 |
October | 0.478267E+09 | 97100486.84 | 0.00 | 11164740.60 | 0.00 | 0.00 | 0.413909E+10 | 0.00 | 1.22 |
November | 0.134066E+10 | 0.00 | 0.00 | 4618148.81 | 0.00 | 0.218197E+09 | 0.253873E+10 | 0.00 | 0.58 |
December | 0.143151E+10 | 0.00 | 0.00 | 2566334.33 | 0.00 | 0.808946E+09 | 0.152105E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.990780E+10 | 0.677666E+10 | 0.00 | 56205269.62 | 52852660.80 | 0.352221E+10 | 0.219839E+11 | 0.00 | 0.68 |
Minimum of Months | 1716311.96 | 0.00 | 0.00 | 321703.51 | 0.00 | 0.00 | 26609694.40 | 0.00 | 0.34 |
Maximum of Months | 0.177691E+10 | 0.261327E+10 | 0.00 | 11164740.60 | 22186837.27 | 0.126540E+10 | 0.413909E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.663516E+09 | 0.00 | 0.00 | 49858.56 | 0.00 | 0.134939E+10 | 56569676.40 | 0.00 | 0.30 |
February | 0.767394E+09 | 0.00 | 0.00 | 156965.15 | 0.00 | 0.116467E+10 | 0.154084E+09 | 0.00 | 0.31 |
March | 0.130981E+10 | 0.00 | 0.00 | 1604164.73 | 0.00 | 0.208592E+09 | 0.889478E+09 | 0.00 | 0.44 |
April | 0.838145E+09 | 1004716.35 | 0.00 | 3178640.40 | 0.00 | 28423471.64 | 0.142761E+10 | 0.00 | 0.70 |
May | 0.316747E+09 | 26353652.88 | 0.00 | 5668165.13 | 0.00 | 0.00 | 0.212692E+10 | 0.00 | 1.09 |
June | 44415437.04 | 0.739840E+09 | 0.00 | 2793620.30 | 3924596.10 | 0.00 | 0.547605E+09 | 0.00 | 0.90 |
July | 1091231.69 | 0.195940E+10 | 0.00 | 228068.19 | 6421160.91 | 0.00 | 17731630.92 | 0.00 | 0.51 |
August | 23122872.80 | 0.172314E+10 | 0.00 | 2269478.09 | 7022007.63 | 0.00 | 0.207130E+09 | 0.00 | 0.85 |
September | 0.177804E+09 | 0.409118E+09 | 0.00 | 3513721.05 | 1843007.75 | 0.00 | 0.896304E+09 | 0.00 | 0.87 |
October | 0.485171E+09 | 46427965.15 | 0.00 | 3504304.28 | 0.00 | 0.00 | 0.134550E+10 | 0.00 | 0.81 |
November | 0.108020E+10 | 0.00 | 0.00 | 584790.86 | 0.00 | 0.306319E+09 | 0.361732E+09 | 0.00 | 0.36 |
December | 0.974477E+09 | 0.00 | 0.00 | 51516.01 | 0.00 | 0.827029E+09 | 56643283.16 | 0.00 | 0.29 |
Annual Sum or Average | 0.668189E+10 | 0.490529E+10 | 0.00 | 23603292.75 | 19210772.39 | 0.388443E+10 | 0.808731E+10 | 0.00 | 0.62 |
Minimum of Months | 1091231.69 | 0.00 | 0.00 | 49858.56 | 0.00 | 0.00 | 17731630.92 | 0.00 | 0.29 |
Maximum of Months | 0.130981E+10 | 0.195940E+10 | 0.00 | 5668165.13 | 7022007.63 | 0.134939E+10 | 0.212692E+10 | 0.00 | 1.09 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:15
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.133360E+12 | 0.147543E+11 | 0.00 | 0.139639E+12 | 0.293954E+11 |
February | 0.206815E+12 | 0.139567E+11 | 0.00 | 0.146920E+12 | 0.259012E+11 |
March | 0.335627E+12 | 0.121988E+11 | 0.00 | 0.190649E+12 | 0.164469E+11 |
April | 0.353857E+12 | 0.779402E+10 | 0.00 | 0.196893E+12 | 0.224982E+11 |
May | 0.448544E+12 | 0.438045E+10 | 0.00 | 0.199374E+12 | 0.609683E+11 |
June | 0.431233E+12 | -944018436.0 | 0.00 | 0.382092E+11 | 0.201877E+12 |
July | 0.422966E+12 | -0.560686E+10 | 0.00 | -0.425504E+11 | 0.286714E+12 |
August | 0.409996E+12 | -0.372853E+10 | 0.00 | -0.797565E+10 | 0.290058E+12 |
September | 0.292449E+12 | 0.798567E+09 | 0.00 | 0.998735E+11 | 0.144536E+12 |
October | 0.287349E+12 | 0.574043E+10 | 0.00 | 0.204733E+12 | 0.650419E+11 |
November | 0.144873E+12 | 0.113307E+11 | 0.00 | 0.190102E+12 | 0.142796E+11 |
December | 0.108133E+12 | 0.130749E+11 | 0.00 | 0.157481E+12 | 0.236063E+11 |
Annual Sum or Average | 0.357520E+13 | 0.737495E+11 | 0.00 | 0.151335E+13 | 0.118132E+13 |
Minimum of Months | 0.108133E+12 | -0.560686E+10 | 0.00 | -0.425504E+11 | 0.142796E+11 |
Maximum of Months | 0.448544E+12 | 0.147543E+11 | 0.00 | 0.204733E+12 | 0.290058E+12 |