Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:20:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1467.48 | 294.55 | 294.55 |
Net Site Energy | 1467.48 | 294.55 | 294.55 |
Total Source Energy | 4155.95 | 834.16 | 834.16 |
Net Source Energy | 4155.95 | 834.16 | 834.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 235.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 69.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1231.50 | 235.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 235.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 69.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 74.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 235.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 69.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 233.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 74.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 54.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 40.02 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 247.18 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 40.02 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 247.18 | 47.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1231.495 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1231.495 | 100.00 |
Total On-Site and Utility Electric Sources | 1231.495 | 100.00 |
Total Electricity End Uses | 1231.495 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 304.33 |
Time Setpoint Not Met During Occupied Cooling | 74.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1651.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:20 | 26-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:20 |
Heating | 0.00 | 184170.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52126.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26940.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 146002.71 | 184170.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 184170.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 52126.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26940.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4176.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 220.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 740.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 163.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 234.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 171.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3900.15 | 255.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 51.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 782.82 | 51.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 51.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 44.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 34.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 782.82 | 51.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.57 | 0.291911 | 0.248000 | 0.636717 | 0.778430 | 0.500000 | 0.001305 | 0.000103 | 0.636717 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.366223 | 0.311000 | 0.636443 | 0.976596 | 0.500000 | 0.001040 | 0.000162 | 0.636443 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.10 | 0.356307 | 0.303000 | 0.637329 | 0.950153 | 0.500000 | 0.001069 | 0.000271 | 0.934970 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.595401 | 0.265353 | 0.226000 | 0.134561 | 0.707609 | 0.500000 | 0.001436 | 0.000122 | 0.421640 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.778355 | 0.128504 | 0.109000 | 0.084841 | 0.342678 | 0.500000 | 0.002965 | 0.000080 | 0.275654 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.16 | 0.135621 | 0.115000 | 0.133969 | 0.361657 | 0.500000 | 0.002809 | 0.000121 | 0.419151 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.853474 | 0.117186 | 0.100000 | 0.085347 | 0.312496 | 0.500000 | 0.003251 | 0.000079 | 0.274230 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.474311 | 0.333097 | 0.283000 | 0.134230 | 0.888259 | 0.500000 | 0.001144 | 0.000091 | 0.312876 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.643169 | 0.155514 | 0.132000 | 0.084898 | 0.414704 | 0.500000 | 0.002450 | 0.000060 | 0.207380 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.955336 | 0.165378 | 0.141000 | 0.134702 | 0.441008 | 0.500000 | 0.002304 | 0.000090 | 0.310527 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.713759 | 0.140125 | 0.119000 | 0.084937 | 0.373666 | 0.500000 | 0.002719 | 0.000060 | 0.205855 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.523706 | 0.301680 | 0.256000 | 0.134069 | 0.804480 | 0.500000 | 0.001263 | 0.000095 | 0.326818 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.778788 | 0.342487 | 0.500000 | 0.002967 | 0.000062 | 0.215423 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.08 | 0.146153 | 0.124000 | 0.134044 | 0.389741 | 0.500000 | 0.002607 | 0.000094 | 0.324297 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.796206 | 0.125615 | 0.107000 | 0.085194 | 0.334973 | 0.500000 | 0.003033 | 0.000062 | 0.214049 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 11759.97 | 0.000103 | 259.17 |
CORE_MID VAV BOX REHEAT COIL | 18531.25 | 0.000162 | 463.71 |
CORE_TOP VAV BOX REHEAT COIL | 30985.99 | 0.000271 | 818.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13936.97 | 0.000122 | 367.59 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9110.86 | 0.000080 | 240.29 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13854.88 | 0.000121 | 365.42 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9063.91 | 0.000079 | 239.05 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10348.74 | 0.000091 | 273.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6858.54 | 0.000060 | 180.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10271.19 | 0.000090 | 270.99 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6808.23 | 0.000060 | 179.61 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10808.77 | 0.000095 | 285.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7123.89 | 0.000062 | 187.93 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10725.60 | 0.000094 | 282.96 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7078.55 | 0.000062 | 186.74 |
PACU_VAV_BOT HEATING COIL | 15705.18 | 0.000137 | 269.27 |
PACU_VAV_MID HEATING COIL | 16818.90 | 0.000147 | 285.67 |
PACU_VAV_TOP HEATING COIL | 16468.64 | 0.000144 | 282.40 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.68 | 1.08 | 5.35 | 1.46 | 4.66 | 4.66 | 0.300000 | 0.313639 | 4.66 |
PACU_VAV_MID | 2.61 | 1.07 | 5.23 | 1.60 | 4.33 | 4.33 | 0.300000 | 0.370794 | 4.33 |
PACU_VAV_TOP | 2.75 | 1.08 | 5.50 | 2.33 | 4.90 | 4.90 | 0.300000 | 0.474657 | 4.90 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.66 |
PACU_VAV_MID_OA_CONTROLLER | 4.33 |
PACU_VAV_TOP_OA_CONTROLLER | 4.90 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.66 | 81077.86 | 0.800742 | 1.55 | 27023.25 | 0.800742 |
PACU_VAV_MID COOLING COIL | 4.33 | 75862.03 | 0.800005 | 1.44 | 25284.81 | 0.800005 |
PACU_VAV_TOP COOLING COIL | 4.90 | 84840.33 | 0.800474 | 1.63 | 28277.28 | 0.800474 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.66 |
PACU_VAV_MID FAN | 4.33 |
PACU_VAV_TOP FAN | 4.90 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000137 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000147 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000144 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.001979 | 0.237531 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.001979 | 590.21 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 226260.06 | 226260.06 | 0.001979 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8668 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8532 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.101 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9196 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9381 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6745 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29350128E-12 | 0.14024199E-14 | -0.85558835E-13 | 0.14795563E-15 |
43 | 6 | 0.27596652E-07 | 0.24107488E-09 | 0.63308017E-08 | -0.12943591E-12 |
44 | 5 | -0.18463709E-03 | 0.20772830E-05 | -0.95040309E-04 | 0.62615177E-08 |
45 | 4 | 0.28572581 | 0.10171039E-02 | 0.97375121E-01 | -0.32667087E-04 |
46 | 3 | -7.1391205 | 0.31676816E-01 | -2.3011695 | 0.28385744E-01 |
47 | 2 | 40.451560 | 0.11313072 | 15.110175 | -0.32866754 |
48 | 1 | -80.224209 | 0.51250674E-01 | -29.002757 | 1.0717664 |
49 | 0 | 46.824341 | 0.10349526E-02 | 16.294583 | |
50 | 7 | -0.29575366E-12 | 0.13916748E-14 | -0.86470795E-13 | 0.14800413E-15 |
51 | 6 | 0.27759747E-07 | 0.23770535E-09 | 0.63667993E-08 | -0.13030888E-12 |
52 | 5 | -0.18546937E-03 | 0.20460315E-05 | -0.95457978E-04 | 0.62966404E-08 |
53 | 4 | 0.28670590 | 0.10008406E-02 | 0.97727300E-01 | -0.32804728E-04 |
54 | 3 | -7.1585449 | 0.31143840E-01 | -2.3069324 | 0.28480895E-01 |
55 | 2 | 40.515639 | 0.11114407 | 15.133849 | -0.32938113 |
56 | 1 | -80.273331 | 0.50317938E-01 | -29.023991 | 1.0728132 |
57 | 0 | 46.824340 | 0.10154678E-02 | 16.294067 | |
58 | 7 | -0.28281898E-12 | 0.14025464E-14 | -0.82622143E-13 | 0.19904483E-15 |
59 | 6 | 0.24787521E-07 | 0.29557932E-09 | 0.57107416E-08 | -0.11447606E-12 |
60 | 5 | -0.17017937E-03 | 0.25981591E-05 | -0.87765911E-04 | 0.56555961E-08 |
61 | 4 | 0.26851995 | 0.12946983E-02 | 0.91201294E-01 | -0.30269387E-04 |
62 | 3 | -6.7976835 | 0.40953066E-01 | -2.1999024 | 0.26714449E-01 |
63 | 2 | 39.324706 | 0.14826279 | 14.693101 | -0.31612152 |
64 | 1 | -79.359856 | 0.67961194E-01 | -28.628348 | 1.0533482 |
65 | 0 | 46.824347 | 0.13883650E-02 | 16.303898 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 35 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 36 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
3 | WINDOW_U_0.363_SHGC_WEST_0.359 | 37 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 | ||
4 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 38 | 1 | VerySmooth | 2.062 | 2.062 | 1.000 | 0.360 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62716E-002 | 0.27216 | 0.52063 | 0.52063 | 0.39490 | 0.13813 | 0.18098 | 0.00000 | 0.84000 | 0.84000 | 0.11617 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2573E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2641E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4284E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6471E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6944E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1337E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1567E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1623 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9225E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1866 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1161 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1060 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7045E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5658E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7130E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2572E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2644E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4224E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4288E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6472E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6962E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1335E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1565E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2304E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2846E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8309E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9927E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8970E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5043E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3611E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5268E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5254E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5531E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1996E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2197E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8087E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8154E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8245E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8324E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6869E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7449E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9509E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3474E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3809E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1335E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1565E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6058E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6401E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5557E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0181E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2282E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3531E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5658E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7130E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6871E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.7454E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9039E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9508E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3472E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3794E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1337E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1567E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.9163E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1214E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4250E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7806E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6747E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3962E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3611E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5268E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3487E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.4506E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9713E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0906E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6797E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7106E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8247E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8326E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1612 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1154 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1821 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1336 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1142 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.9166E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.2056E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4300E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.9837E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1443E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6075E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8659E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7319E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4067E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2614E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4669E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2170E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4103E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0968E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6778E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7687E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9509E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.2056E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4300E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6810E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9904E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2167E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6662E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5169E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3039E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2615E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.4670E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1613 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1154 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1821 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1336 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1142 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.9159E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.2051E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4297E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.9837E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1440E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6075E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8657E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7315E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4064E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2609E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4667E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2172E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4102E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0969E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6777E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7684E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9507E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.2051E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4297E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6810E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9902E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.2167E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6659E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5165E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3036E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2610E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.4667E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 35135.98406 | 35135.98406 | 2.56741 | 2.56741 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5440.44009 | 5440.44009 | 0.23236 | 0.42469 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28034.56172 | 28034.56172 | 2.04644 | 2.04644 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12214.43268 | 12214.43268 | 0.52325 | 0.52325 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28537.10226 | 28537.10226 | 2.10340 | 2.10340 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21706.23749 | 21706.23749 | 0.93497 | 0.93497 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8078.00370 | 8078.00370 | 0.59540 | 0.59540 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9754.38077 | 9754.38077 | 0.42164 | 0.42164 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10560.29281 | 10560.29281 | 0.77835 | 0.77835 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6376.43691 | 6376.43691 | 0.27565 | 0.27565 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15805.33482 | 15805.33482 | 1.16495 | 1.16495 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9696.99442 | 9696.99442 | 0.41915 | 0.41915 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11579.47229 | 11579.47229 | 0.85347 | 0.85347 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6343.61614 | 6343.61614 | 0.27423 | 0.27423 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6435.11725 | 6435.11725 | 0.47431 | 0.47431 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 7245.44767 | 7245.44767 | 0.31288 | 0.31288 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8726.19066 | 8726.19066 | 0.64317 | 0.64317 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.81033E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4801.56001 | 4801.56001 | 0.20738 | 0.20738 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12961.43090 | 12961.43090 | 0.95534 | 0.95534 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 7191.22331 | 7191.22331 | 0.31053 | 0.31053 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9683.88380 | 9683.88380 | 0.71376 | 0.71376 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.81750E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4766.39869 | 4766.39869 | 0.20586 | 0.20586 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7105.28388 | 7105.28388 | 0.52371 | 0.52371 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7567.64939 | 7567.64939 | 0.32682 | 0.32682 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10566.16824 | 10566.16824 | 0.77879 | 0.77879 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4987.43258 | 4987.43258 | 0.21542 | 0.21542 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14666.42763 | 14666.42763 | 1.08100 | 1.08100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7509.52675 | 7509.52675 | 0.32430 | 0.32430 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10802.48173 | 10802.48173 | 0.79621 | 0.79621 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4955.74736 | 4955.74736 | 0.21405 | 0.21405 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 68393.76 | 4.65928 | 4.65928 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 19175.52 | 1.46133 | 1.46133 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63935.23 | 4.32542 | 4.32542 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 19233.83 | 1.60384 | 1.60384 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 71560.94 | 4.89963 | 4.89963 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 19311.54 | 2.32564 | 2.32564 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.56741 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29191 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63672 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77843 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30519E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02881E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63672 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11759.97324 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02881E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.17119 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04644 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36622 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63644 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97660 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04035E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62119E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63644 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18531.25083 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62119E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 463.70760 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10340 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35631 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63733 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95015 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06930E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71079E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93497 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30985.98789 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71079E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 818.23875 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59540 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26535 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13456 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70761 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43582E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21927E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42164 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13936.97109 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21927E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 367.58698 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77835 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12850 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48407E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34268 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96489E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.97058E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27565 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9110.86475 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.97058E-005 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 240.29089 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16495 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13562 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13397 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36166 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80929E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21208E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41915 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13854.87512 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21208E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.42379 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85347 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11719 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.53474E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31250 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25124E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.92951E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27423 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9063.91319 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.92951E-005 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 239.05373 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47431 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33310 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13423 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88826 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14381E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.05353E-005 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31288 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10348.74081 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.05353E-005 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 273.03061 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64317 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15551 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13200 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48983E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41470 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44994E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.00015E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20738 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6858.53866 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.00015E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 180.93893 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95534 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16538 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14100 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13470 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44101 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30381E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.98568E-005 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31053 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10271.18579 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.98568E-005 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.98621 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71376 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14012 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49374E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37367 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71901E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.95614E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20586 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6808.23224 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95614E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 179.61330 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52371 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30168 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13407 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80448 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26293E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.45598E-005 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32682 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10808.76588 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.45598E-005 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.15403 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77879 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34249 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96653E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.23229E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21542 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7123.88896 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.23229E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 187.93152 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08100 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14615 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13404 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38974 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60686E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.38323E-005 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32430 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10725.60307 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.38323E-005 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.96257 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79621 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12561 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51940E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33497 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03308E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.19263E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21405 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7078.55140 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.19263E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 186.73680 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.67699 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07549 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.35398 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46133 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.65928 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.65928 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.31364 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.61307 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07464 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.22614 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60384 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.32542 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.32542 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.37079 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.74779 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07605 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.49557 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.32564 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.89963 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.89963 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.47466 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.65928 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.32542 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.89963 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.65928 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.65928 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 81077.85697 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80074 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55294 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27023.24973 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80074 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 15705.17518 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37396E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 269.26719 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.65928 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37396E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.32542 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.32542 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 75862.03064 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80001 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.44166 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25284.81481 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80001 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 16818.90041 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47139E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 285.66846 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.32542 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.47139E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.89963 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.89963 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 84840.32951 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80047 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.63305 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28277.28183 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80047 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 16468.63988 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44075E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 282.39842 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.89963 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.44075E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.97942E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.23753 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.97942E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 590.21276 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 226260.05841 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 226260.06000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.97942E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 11145.49 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 17551.17 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 29364.85 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13204.85 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8632.21 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13127.08 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8587.73 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9805.67 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6498.56 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9732.19 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6450.90 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10241.46 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6749.93 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10162.68 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6706.98 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 13111.84 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 13788.27 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 13753.60 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 79867.25 | 272518.36 | 11.71 | 3.03 | 3.35 | 3.52 | 3.73 | 10.35 | 11.43 | 12.02 | 12.71 | 5.3121 | 4.2112 | 2.8247 | 1.1558 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 74755.68 | 255076.97 | 11.73 | 3.04 | 3.36 | 3.53 | 3.73 | 10.37 | 11.45 | 12.04 | 12.74 | 4.9315 | 3.9108 | 2.6239 | 1.0715 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 83554.88 | 285101.07 | 11.70 | 3.03 | 3.35 | 3.52 | 3.72 | 10.34 | 11.42 | 12.01 | 12.70 | 5.5861 | 4.4267 | 2.9694 | 1.2179 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.101 | 0.945 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.867 | 0.767 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_NORTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_EAST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_SOUTH_0.359 | N/A | 2.062 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.853 | 0.757 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.363_SHGC_WEST_0.359 | N/A | 2.062 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.6503708339E-002 | 5.7469674910E-002 | Pass | Pass | 0.1048019956 | 0.2962851361 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.6702256649E-002 | 5.1166969821E-002 | Pass | Pass | 0.4109584340 | 0.4734005224 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.8232429965E-002 | 3.4031709264E-002 | Pass | Pass | 0.2913367119 | 0.4148561188 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0190518208E-002 | 4.2007528083E-002 | Pass | Pass | 0.1301841685 | 0.3426984095 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.2725479213E-002 | 1.7644966653E-002 | Pass | Pass | 0.6271601234 | 1.2689121640 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.8428229633E-002 | 2.0314809283E-002 | Pass | Pass | 14.1440669645 | 49.1742754546 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2282334132 | 0.2112440963 | Pass | Pass | 22.5503038374 | 53.0974818570 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2346937474 | 0.2193157187 | Pass | Pass | 23.9341383883 | 56.8192015923 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2185780551 | 0.2052332872 | Pass | Pass | 23.0995464235 | 54.6959879220 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2386836708 | 0.2219641073 | Pass | Pass | 23.7134012976 | 56.2959910406 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.8452373722E-002 | 0.1350563403 | Pass | Pass | 0.6410378164 | 2.7579044798 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1127473355 | 0.1567151047 | Pass | Pass | 0.5379692839 | 2.1575737525 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.5596668660E-002 | 0.1273165107 | Pass | Pass | 0.7228154679 | 3.2421696141 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1147583903 | 0.1598848524 | Pass | Pass | 0.5517830040 | 2.2290598446 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1197208136 | 0.1335235917 | Pass | Pass | 126.0327044439 | 1366.8839025929 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1288458795 | 0.1445488561 | Pass | Pass | 4.6202382582 | 25.9877792785 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1193594262 | 0.1310718964 | Pass | Pass | 15.7277761430 | 143.1696929404 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1303475155 | 0.1464586026 | Pass | Pass | 3.2238271465 | 11.5242910166 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3035.47 | 77.43 | 0.00 | 2340.55 | 451.44 | 5904.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.945 | 1.101 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.867 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.757 | 0.853 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.363_SHGC_NORTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.363_SHGC_EAST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.363_SHGC_EAST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.363_SHGC_WEST_0.359 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.363_SHGC_WEST_0.359 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.062 | 0.360 | 0.396 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.363_SHGC_NORTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.363_SHGC_EAST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.363_SHGC_SOUTH_0.359 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.363_SHGC_WEST_0.359 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.062 | 0.360 | 0.396 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
North Total or Average | 195.79 | 2.062 | 0.360 | 0.396 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.062 | 0.360 | 0.396 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.71 | 0.0000 | Y | 6.93 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.43 | 0.0000 | Y | 4.34 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.38 | 0.0000 | Y | 4.33 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.62 | 0.0000 | Y | 6.90 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.37 | 0.0000 | Y | 4.33 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.11 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.32 | 0.0000 | Y | 4.32 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.71 | 0.0000 | Y | 6.93 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.43 | 0.0000 | Y | 4.34 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.16 | 0.0000 | Y | 6.78 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.38 | 0.0000 | Y | 4.33 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 233.88 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.59 | 42.59 | 4.51 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.55 | 63.07 | 4.83 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.55 | 47.80 | 42.30 | |
Exterior Lighting Total | 5686.19 | 51.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 226260.06 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 81077.86 | 64922.48 | 16155.38 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 75862.03 | 60690.03 | 15172.00 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 84840.33 | 67912.45 | 16927.88 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 79867.2 | 3.03 | 10.35 | N/A | N/A | 11.71 | |
PACU_VAV_MID COOLING COIL | 74755.7 | 3.04 | 10.37 | N/A | N/A | 11.73 | |
PACU_VAV_TOP COOLING COIL | 83554.9 | 3.03 | 10.34 | N/A | N/A | 11.70 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 11759.97 | 11145.49 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 18531.25 | 17551.17 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 30985.99 | 29364.85 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13936.97 | 13204.85 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9110.86 | 8632.21 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13854.88 | 13127.08 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9063.91 | 8587.73 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10348.74 | 9805.67 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6858.54 | 6498.56 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10271.19 | 9732.19 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6808.23 | 6450.90 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10808.77 | 10241.46 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7123.89 | 6749.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10725.60 | 10162.68 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7078.55 | 6706.98 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 15705.18 | 13111.84 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 16818.90 | 13788.27 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 16468.64 | 13753.60 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.66 | 10199.21 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.33 | 9468.40 | 2189.01 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.90 | 10725.34 | 2189.01 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.001979 | 590.21 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 79867.25 | 3.03 | 10.35 | 11.71 | 5.3121 | 3.35 | 11.43 | 4.2112 | 3.52 | 12.02 | 2.8247 | 3.73 | 12.71 | 1.1558 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 74755.68 | 3.04 | 10.37 | 11.73 | 4.9315 | 3.36 | 11.45 | 3.9108 | 3.53 | 12.04 | 2.6239 | 3.73 | 12.74 | 1.0715 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 83554.88 | 3.03 | 10.34 | 11.70 | 5.5861 | 3.35 | 11.42 | 4.4267 | 3.52 | 12.01 | 2.9694 | 3.72 | 12.70 | 1.2179 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 35135.98 | 35135.98 | 35.72 | 2.567 | 2.567 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_MID | 28034.56 | 28034.56 | 28.50 | 2.046 | 2.046 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00881 | 0.425 | 0.00 |
CORE_TOP | 28537.10 | 28537.10 | 29.01 | 2.103 | 2.103 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 29.19 | 0.00882 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8078.00 | 8078.00 | 38.96 | 0.595 | 0.595 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 29.30 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10560.29 | 10560.29 | 80.45 | 0.778 | 0.778 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00865 | 23.68 | 0.00881 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15805.33 | 15805.33 | 76.23 | 1.165 | 1.165 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00866 | 29.14 | 0.00882 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11579.47 | 11579.47 | 88.22 | 0.853 | 0.853 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 27.94 | 0.00882 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6435.12 | 6435.12 | 31.04 | 0.474 | 0.474 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8726.19 | 8726.19 | 66.48 | 0.643 | 0.643 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00869 | 22.36 | 0.00881 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12961.43 | 12961.43 | 62.51 | 0.955 | 0.955 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00870 | 29.31 | 0.00882 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9683.88 | 9683.88 | 73.78 | 0.714 | 0.714 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 26.90 | 0.00882 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7105.28 | 7105.28 | 34.27 | 0.524 | 0.524 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10566.17 | 10566.17 | 80.50 | 0.779 | 0.779 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00865 | 23.35 | 0.00881 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 14666.43 | 14666.43 | 70.74 | 1.081 | 1.081 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 29.05 | 0.00882 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10802.48 | 10802.48 | 82.30 | 0.796 | 0.796 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00865 | 27.94 | 0.00882 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5440.44 | 5440.44 | 5.53 | 0.232 | 0.425 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_MID | 12214.43 | 12214.43 | 12.42 | 0.523 | 0.523 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
CORE_TOP | 21706.24 | 21706.24 | 22.07 | 0.935 | 0.935 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9754.38 | 9754.38 | 47.05 | 0.422 | 0.422 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6376.44 | 6376.44 | 48.58 | 0.276 | 0.276 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9696.99 | 9696.99 | 46.77 | 0.419 | 0.419 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6343.62 | 6343.62 | 48.33 | 0.274 | 0.274 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7245.45 | 7245.45 | 34.95 | 0.313 | 0.313 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4801.56 | 4801.56 | 36.58 | 0.207 | 0.207 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7191.22 | 7191.22 | 34.68 | 0.311 | 0.311 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4766.40 | 4766.40 | 36.31 | 0.206 | 0.206 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7567.65 | 7567.65 | 36.50 | 0.327 | 0.327 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4987.43 | 4987.43 | 38.00 | 0.215 | 0.215 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -4.20 | 0.00269 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7509.53 | 7509.53 | 36.22 | 0.324 | 0.324 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -4.20 | 0.00269 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4955.75 | 4955.75 | 37.76 | 0.214 | 0.214 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -4.20 | 0.00269 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.66 | 4.66 | 1.46 | 1.46 | 4.6593 | 1.4613 | 4.6593 | 0.3136 | 0.3000 |
PACU_VAV_MID | 4.33 | 4.33 | 1.60 | 1.60 | 4.3254 | 1.6038 | 4.3254 | 0.3708 | 0.3000 |
PACU_VAV_TOP | 4.90 | 4.90 | 2.33 | 2.33 | 4.8996 | 2.3256 | 4.8996 | 0.4747 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 11759.973 | 11759.973 | 0.636717 | 0.00010288 | 259.171 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11759.97 | 11759.97 | 0.636717 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 5440.44 | 0.00 | 11800.57 | 11800.57 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 18531.251 | 18531.251 | 0.636443 | 0.00016212 | 463.708 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18531.25 | 18531.25 | 0.636443 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 12214.43 | 0.00 | 18588.99 | 18588.99 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30985.988 | 30985.988 | 0.934970 | 0.00027108 | 818.239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 30985.99 | 30985.99 | 0.934970 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 21706.24 | 0.00 | 31095.24 | 31095.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13936.971 | 13936.971 | 0.421640 | 0.00012193 | 367.587 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13936.97 | 13936.97 | 0.421640 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776788 | 49.5217 | 9754.38 | 0.00 | 13982.93 | 13982.93 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9110.865 | 9110.865 | 0.275654 | 0.00007971 | 240.291 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9110.86 | 9110.86 | 0.275654 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776794 | 49.5221 | 6376.44 | 0.00 | 9140.85 | 9140.85 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13854.875 | 13854.875 | 0.419151 | 0.00012121 | 365.424 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13854.88 | 13854.88 | 0.419151 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776560 | 49.5073 | 9696.99 | 0.00 | 13900.58 | 13900.58 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9063.913 | 9063.913 | 0.274230 | 0.00007930 | 239.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9063.91 | 9063.91 | 0.274230 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776605 | 49.5102 | 6343.62 | 0.00 | 9093.75 | 9093.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10348.741 | 10348.741 | 0.312876 | 0.00009054 | 273.031 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10348.74 | 10348.74 | 0.312876 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00770725 | 49.1402 | 7245.45 | 0.00 | 10383.46 | 10383.46 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6858.539 | 6858.539 | 0.207380 | 0.00006000 | 180.939 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6858.54 | 6858.54 | 0.207380 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772094 | 49.2264 | 4801.56 | 0.00 | 6881.48 | 6881.48 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10271.186 | 10271.186 | 0.310527 | 0.00008986 | 270.986 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10271.19 | 10271.19 | 0.310527 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00770240 | 49.1097 | 7191.22 | 0.00 | 10305.66 | 10305.66 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6808.232 | 6808.232 | 0.205855 | 0.00005956 | 179.613 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6808.23 | 6808.23 | 0.205855 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771641 | 49.1978 | 4766.40 | 0.00 | 6831.02 | 6831.02 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10808.766 | 10808.766 | 0.326818 | 0.00009456 | 285.154 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10808.77 | 10808.77 | 0.326818 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00764471 | 48.7470 | 7567.65 | 0.00 | 10844.94 | 10844.94 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7123.889 | 7123.889 | 0.215423 | 0.00006232 | 187.932 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7123.89 | 7123.89 | 0.215423 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765912 | 48.8376 | 4987.43 | 0.00 | 7147.66 | 7147.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10725.603 | 10725.603 | 0.324297 | 0.00009383 | 282.963 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10725.60 | 10725.60 | 0.324297 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00763873 | 48.7093 | 7509.53 | 0.00 | 10761.51 | 10761.51 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7078.551 | 7078.551 | 0.214049 | 0.00006193 | 186.737 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7078.55 | 7078.55 | 0.214049 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765395 | 48.8051 | 4955.75 | 0.00 | 7102.18 | 7102.18 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 81077.857 | 64922.476 | 4.659277 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 81904.65 | 77391.61 | 4.659277 | 25.11 | 16.90 | 0.00882066 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.5203 | 24.00 | 0.00882045 | 46.7835 | 63211.73 | 0.00 | 83602.15 | 65333.93 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 15705.175 | 15705.175 | 1.397783 | 0.00013740 | 269.267 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15705.18 | 15705.18 | 1.397783 | 3.38 | 2.50 | 0.00423406 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 68.4012 | 19.72 | 0.00750669 | 51.8237 | 13291.14 | 0.00 | 15870.48 | 15870.48 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 75862.031 | 60690.033 | 4.325424 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 76695.45 | 72254.20 | 4.325424 | 25.19 | 16.95 | 0.00884009 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 22.1042 | 24.00 | 0.00884536 | 46.9138 | 58683.18 | 0.00 | 78223.94 | 61074.78 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 16818.900 | 16818.900 | 1.297627 | 0.00014714 | 285.668 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16818.90 | 16818.90 | 1.297627 | 1.93 | 1.29 | 0.00394671 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 73.6806 | 19.64 | 0.00721389 | 50.0736 | 17190.45 | 0.00 | 16687.93 | 16687.93 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 84840.330 | 67912.452 | 4.899629 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 85664.08 | 81093.85 | 4.899629 | 25.05 | 16.87 | 0.00880870 | 10.99 | 10.99 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 19.5137 | 24.00 | 0.00880560 | 46.7058 | 66428.68 | 0.00 | 87481.77 | 68346.33 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 16468.640 | 16468.640 | 1.469889 | 0.00014407 | 282.398 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 16468.64 | 16468.64 | 1.469889 | 3.41 | 2.74 | 0.00439802 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 65.0457 | 17.60 | 0.00739579 | 58.3067 | 18797.77 | 0.00 | 16647.64 | 16647.64 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 11759.973 | 11759.973 | 0.636717 | 0.00010288 | 259.171 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 5.0950 | 5.197547 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11759.97 | 11759.97 | 1.0000 | 0.75577720 | 0.636717 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.10287088 | 60.00 | 32.22 | 27.78 | 0.000 | 11759.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.67 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 5440.44 | 0.00 | 11800.57 | 11800.57 | 0.75577720 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.11 | 17.40 | 0.00800000 | 48673.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 18531.251 | 18531.251 | 0.636443 | 0.00016212 | 463.708 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 8.0287 | 8.190244 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18531.25 | 18531.25 | 1.0000 | 0.75545250 | 0.636443 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.16210293 | 60.00 | 32.22 | 27.78 | 0.000 | 18531.25 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 12214.43 | 0.00 | 18588.99 | 18588.99 | 0.75545250 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.93 | 20.26 | 0.00800000 | 57666.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 30985.988 | 30985.988 | 0.934970 | 0.00027108 | 818.239 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 13.4247 | 13.694855 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 30985.99 | 30985.99 | 1.0000 | 1.10980093 | 0.934970 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.27105129 | 60.00 | 32.22 | 27.78 | 0.000 | 30985.99 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 21706.24 | 0.00 | 31095.24 | 31095.24 | 1.10980093 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.26 | 0.00800000 | 61078.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13936.971 | 13936.971 | 0.421640 | 0.00012193 | 367.587 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 6.0382 | 6.159713 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13936.97 | 13936.97 | 1.0000 | 0.50048280 | 0.421640 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12191427 | 60.00 | 32.22 | 27.78 | 0.000 | 13936.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776788 | 21.00 | 0.00776788 | 49.5217 | 9754.38 | 0.00 | 13982.93 | 13982.93 | 0.50048280 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9110.865 | 9110.865 | 0.275654 | 0.00007971 | 240.291 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 3.9473 | 4.026723 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9110.86 | 9110.86 | 1.0000 | 0.32719826 | 0.275654 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07969769 | 60.00 | 32.22 | 27.78 | 0.000 | 9110.86 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776794 | 21.00 | 0.00776794 | 49.5221 | 6376.44 | 0.00 | 9140.85 | 9140.85 | 0.32719826 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13854.875 | 13854.875 | 0.419151 | 0.00012121 | 365.424 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 6.0026 | 6.123429 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13854.88 | 13854.88 | 1.0000 | 0.49752848 | 0.419151 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12119613 | 60.00 | 32.22 | 27.78 | 0.000 | 13854.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776560 | 21.00 | 0.00776560 | 49.5073 | 9696.99 | 0.00 | 13900.58 | 13900.58 | 0.49752848 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9063.913 | 9063.913 | 0.274230 | 0.00007930 | 239.054 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 3.9269 | 4.005971 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9063.91 | 9063.91 | 1.0000 | 0.32550868 | 0.274230 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07928698 | 60.00 | 32.22 | 27.78 | 0.000 | 9063.91 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776605 | 21.00 | 0.00776605 | 49.5102 | 6343.62 | 0.00 | 9093.75 | 9093.75 | 0.32550868 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10348.741 | 10348.741 | 0.312876 | 0.00009054 | 273.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 4.4836 | 4.573826 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10348.74 | 10348.74 | 1.0000 | 0.37138092 | 0.312876 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09052606 | 60.00 | 32.22 | 27.78 | 0.000 | 10348.74 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00770725 | 21.00 | 0.00770725 | 49.1402 | 7245.45 | 0.00 | 10383.46 | 10383.46 | 0.37138092 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.9 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6858.539 | 6858.539 | 0.207380 | 0.00006000 | 180.939 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 2.9715 | 3.031264 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6858.54 | 6858.54 | 1.0000 | 0.24615846 | 0.207380 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05999537 | 60.00 | 32.22 | 27.78 | 0.000 | 6858.54 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772094 | 21.00 | 0.00772094 | 49.2264 | 4801.56 | 0.00 | 6881.48 | 6881.48 | 0.24615846 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10271.186 | 10271.186 | 0.310527 | 0.00008986 | 270.986 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 4.4500 | 4.539549 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10271.19 | 10271.19 | 1.0000 | 0.36859258 | 0.310527 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08984765 | 60.00 | 32.22 | 27.78 | 0.000 | 10271.19 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00770240 | 21.00 | 0.00770240 | 49.1097 | 7191.22 | 0.00 | 10305.66 | 10305.66 | 0.36859258 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61019.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6808.232 | 6808.232 | 0.205855 | 0.00005956 | 179.613 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 2.9497 | 3.009030 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6808.23 | 6808.23 | 1.0000 | 0.24434838 | 0.205855 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05955531 | 60.00 | 32.22 | 27.78 | 0.000 | 6808.23 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771641 | 21.00 | 0.00771641 | 49.1978 | 4766.40 | 0.00 | 6831.02 | 6831.02 | 0.24434838 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10808.766 | 10808.766 | 0.326818 | 0.00009456 | 285.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 4.6829 | 4.777143 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10808.77 | 10808.77 | 1.0000 | 0.38792950 | 0.326818 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09455015 | 60.00 | 32.22 | 27.78 | 0.000 | 10808.77 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764471 | 21.00 | 0.00764471 | 48.7470 | 7567.65 | 0.00 | 10844.94 | 10844.94 | 0.38792950 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61015.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7123.889 | 7123.889 | 0.215423 | 0.00006232 | 187.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 3.0864 | 3.148540 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7123.89 | 7123.89 | 1.0000 | 0.25570517 | 0.215423 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06231653 | 60.00 | 32.22 | 27.78 | 0.000 | 7123.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765912 | 21.00 | 0.00765912 | 48.8376 | 4987.43 | 0.00 | 7147.66 | 7147.66 | 0.25570517 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61012.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10725.603 | 10725.603 | 0.324297 | 0.00009383 | 282.963 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 4.6469 | 4.740387 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10725.60 | 10725.60 | 1.0000 | 0.38493727 | 0.324297 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09382268 | 60.00 | 32.22 | 27.78 | 0.000 | 10725.60 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00763873 | 21.00 | 0.00763873 | 48.7093 | 7509.53 | 0.00 | 10761.51 | 10761.51 | 0.38493727 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7078.551 | 7078.551 | 0.214049 | 0.00006193 | 186.737 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 3.0668 | 3.128502 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7078.55 | 7078.55 | 1.0000 | 0.25407396 | 0.214049 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06191994 | 60.00 | 32.22 | 27.78 | 0.000 | 7078.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765395 | 21.00 | 0.00765395 | 48.8051 | 4955.75 | 0.00 | 7102.18 | 7102.18 | 0.25407396 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61013.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 81077.857 | 64922.476 | 4.659277 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2372 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.659277 | 5.53051936 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 81904.65 | 77391.61 | 1.0102 | 5.53051936 | 4.659277 | 25.11 | 16.90 | 0.00882066 | 47700.3 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10199.209 | 71705.44 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 20.5203 | 24.00 | 0.00882045 | 24.00 | 0.00882045 | 46.7835 | 63211.73 | 0.00 | 83602.15 | 65333.93 | 5.31210565 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.65 | 14.12 | 0.00983631 | 39584.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15705.175 | 15705.175 | 1.397783 | 0.00013740 | 269.267 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.659277 | 5.53051936 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 6.8043 | 6.941205 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15705.18 | 15705.18 | 1.0000 | 1.65915581 | 1.397783 | 3.38 | 2.50 | 0.00423406 | 14012.1 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.13738171 | 60.00 | 32.22 | 27.78 | 0.000 | 15705.18 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 68.4012 | 19.79 | 0.00757577 | 19.72 | 0.00750669 | 51.8237 | 13291.14 | 0.00 | 15870.48 | 15870.48 | 1.65915581 | 2.80 | 2.27 | 0.00423406 | 13424.7 | 12.25 | 7.19 | 0.00423406 | 22990.1 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 75862.031 | 60690.033 | 4.325424 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2733 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.325424 | 5.13423892 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 76695.45 | 72254.20 | 1.0110 | 5.13423892 | 4.325424 | 25.19 | 16.95 | 0.00884009 | 47837.2 | 10.99 | 10.99 | 0.00850000 | 32479.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9468.402 | 67227.05 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 22.1042 | 24.00 | 0.00884536 | 24.00 | 0.00884536 | 46.9138 | 58683.18 | 0.00 | 78223.94 | 61074.78 | 4.93147529 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.56 | 14.08 | 0.00982122 | 39460.2 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16818.900 | 16818.900 | 1.297627 | 0.00014714 | 285.668 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.325424 | 5.13423892 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 7.2868 | 7.433438 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16818.90 | 16818.90 | 1.0000 | 1.54027167 | 1.297627 | 1.93 | 1.29 | 0.00394671 | 11827.4 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.14712407 | 60.00 | 32.22 | 27.78 | 0.000 | 16818.90 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 73.6806 | 19.10 | 0.00746396 | 19.64 | 0.00721389 | 50.0736 | 17190.45 | 0.00 | 16687.93 | 16687.93 | 1.54027167 | 2.80 | 1.87 | 0.00394671 | 12704.6 | 13.50 | 7.46 | 0.00394671 | 23539.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 84840.330 | 67912.452 | 4.899629 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2149 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.899629 | 5.81581478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 85664.08 | 81093.85 | 1.0097 | 5.81581478 | 4.899629 | 25.05 | 16.87 | 0.00880870 | 47615.1 | 10.99 | 10.99 | 0.00850000 | 32479.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10725.342 | 74938.73 | 29.40 | 0.00882150 | 18.34 | 0.95610000 | 19.5137 | 24.00 | 0.00880560 | 24.00 | 0.00880560 | 46.7058 | 66428.68 | 0.00 | 87481.77 | 68346.33 | 5.58613406 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.71 | 14.15 | 0.00984159 | 39661.9 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16468.640 | 16468.640 | 1.469889 | 0.00014407 | 282.398 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.899629 | 5.81581478 | 4197.9300 | 999.8980 | 1.97921977 | 54.44 | 82.22 | 27.78 | 230813.63 | 7.1350 | 7.278633 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 16468.64 | 16468.64 | 1.0000 | 1.74474443 | 1.469889 | 3.41 | 2.74 | 0.00439802 | 14450.2 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.14406015 | 60.00 | 32.22 | 27.78 | 0.000 | 16468.64 | -4.20 | 0.00269032 | -4.20 | 0.95610000 | 65.0457 | 17.56 | 0.00757585 | 17.60 | 0.00739579 | 58.3067 | 18797.77 | 0.00 | 16647.64 | 16647.64 | 1.74474443 | 2.80 | 2.50 | 0.00439802 | 13835.6 | 12.22 | 7.38 | 0.00439802 | 23377.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.66 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.33 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1992.17 | 2019.67 | 32.00 |
CORE_MID | 1273.17 | 3237.00 | 172.00 |
CORE_TOP | 1508.00 | 3815.00 | 656.50 |
PERIMETER_TOP_ZN_3 | 2246.83 | 4272.33 | 1442.33 |
PERIMETER_TOP_ZN_2 | 2587.67 | 3841.83 | 1305.50 |
PERIMETER_TOP_ZN_1 | 2510.33 | 3701.17 | 1119.33 |
PERIMETER_TOP_ZN_4 | 2571.67 | 3999.17 | 1372.83 |
PERIMETER_BOT_ZN_3 | 1647.17 | 4287.00 | 994.17 |
PERIMETER_BOT_ZN_2 | 2161.83 | 3646.67 | 845.67 |
PERIMETER_BOT_ZN_1 | 2111.83 | 3844.00 | 854.83 |
PERIMETER_BOT_ZN_4 | 2215.67 | 3675.83 | 871.00 |
PERIMETER_MID_ZN_3 | 1841.33 | 3921.50 | 926.50 |
PERIMETER_MID_ZN_2 | 1920.67 | 3098.83 | 799.50 |
PERIMETER_MID_ZN_1 | 2236.50 | 3308.50 | 678.17 |
PERIMETER_MID_ZN_4 | 2223.83 | 3643.83 | 878.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4158.50 | 4669.00 | 1651.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 2.33 | 0.00 | 2.33 | 0.00 |
CORE_MID | 3.33 | 0.00 | 3.33 | 0.00 |
CORE_TOP | 5.83 | 0.00 | 5.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 20.83 | 0.00 | 18.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 9.17 | 13.50 | 7.33 | 13.50 |
PERIMETER_TOP_ZN_1 | 6.67 | 16.50 | 5.83 | 15.83 |
PERIMETER_TOP_ZN_4 | 7.67 | 22.50 | 6.17 | 13.67 |
PERIMETER_BOT_ZN_3 | 5.33 | 0.00 | 5.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 3.33 | 9.50 | 3.17 | 9.50 |
PERIMETER_BOT_ZN_1 | 293.83 | 8.67 | 293.83 | 8.50 |
PERIMETER_BOT_ZN_4 | 3.33 | 15.33 | 3.00 | 7.83 |
PERIMETER_MID_ZN_3 | 5.17 | 0.00 | 5.17 | 0.00 |
PERIMETER_MID_ZN_2 | 2.50 | 12.50 | 2.33 | 12.50 |
PERIMETER_MID_ZN_1 | 2.33 | 16.83 | 2.33 | 16.83 |
PERIMETER_MID_ZN_4 | 2.67 | 21.50 | 2.50 | 13.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 307.33 | 92.67 | 304.33 | 74.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 1.013 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.701 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.674 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.723 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 1.054 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 1.152 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 1.055 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.628 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.937 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.928 | 0.829 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.920 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.732 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.966 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 1.169 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 1.054 | 0.031 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.63 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.89 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.53 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.56 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.89 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.63 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.89 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.53 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.56 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.89 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.20 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15977466.67 | 0.00 | 15977466.67 | 0.00 | 15977466.67 | 13393058.27 | 4508.33 | 329.49 | 3922.19 | 43.81 |
CORE_MID | 11096764.94 | 0.00 | 11096764.94 | 0.00 | 11096764.94 | 13393058.27 | 4542.07 | 1109.58 | 3108.35 | 50.42 |
CORE_TOP | 10692349.76 | 0.00 | 10692349.76 | 0.00 | 10692349.76 | 13393058.27 | 4598.25 | 1207.89 | 2953.86 | 51.27 |
PERIMETER_TOP_ZN_3 | 2418676.44 | 0.00 | 2418676.44 | 242662.85 | 2661339.29 | 2823374.22 | 4432.88 | 1130.61 | 3196.51 | 51.27 |
PERIMETER_TOP_ZN_2 | 2225182.14 | 0.00 | 2225182.14 | 161774.26 | 2386956.40 | 1787429.43 | 4408.91 | 1329.71 | 3021.38 | 51.27 |
PERIMETER_TOP_ZN_1 | 3839729.50 | 0.00 | 3839729.50 | 242662.85 | 4082392.35 | 2823374.22 | 4359.63 | 1330.67 | 3069.70 | 51.27 |
PERIMETER_TOP_ZN_4 | 2244347.11 | 0.00 | 2244347.11 | 161774.26 | 2406121.37 | 1787312.18 | 4363.51 | 931.96 | 3464.53 | 51.27 |
PERIMETER_BOT_ZN_3 | 2098926.74 | 0.00 | 2098926.74 | 129022.55 | 2227949.28 | 2823374.22 | 5611.20 | 409.31 | 2739.49 | 43.81 |
PERIMETER_BOT_ZN_2 | 1976516.15 | 0.00 | 1976516.15 | 86014.52 | 2062530.66 | 1787429.43 | 5351.81 | 436.18 | 2972.01 | 43.81 |
PERIMETER_BOT_ZN_1 | 3100602.18 | 0.00 | 3100602.18 | 2835943.55 | 5936545.73 | 2823374.22 | 5017.56 | 327.34 | 3415.10 | 43.81 |
PERIMETER_BOT_ZN_4 | 1948755.69 | 0.00 | 1948755.69 | 86014.52 | 2034770.21 | 1787312.18 | 5427.77 | 415.52 | 2916.71 | 43.81 |
PERIMETER_MID_ZN_3 | 2445886.95 | 0.00 | 2445886.95 | 201998.19 | 2647885.14 | 2823374.22 | 4538.39 | 1199.26 | 3022.35 | 50.42 |
PERIMETER_MID_ZN_2 | 2072328.24 | 0.00 | 2072328.24 | 134664.65 | 2206992.89 | 1601953.02 | 4301.98 | 959.27 | 3498.75 | 959.42 |
PERIMETER_MID_ZN_1 | 3890880.79 | 0.00 | 3890880.79 | 201998.19 | 4092878.97 | 2823374.22 | 4292.77 | 1164.40 | 3302.83 | 50.42 |
PERIMETER_MID_ZN_4 | 2235700.80 | 0.00 | 2235700.80 | 134664.65 | 2370365.45 | 1787312.18 | 4431.77 | 909.79 | 3418.44 | 50.42 |
Total Facility | 68264114.08 | 0.00 | 68264114.08 | 4619195.04 | 72883309.12 | 67658168.57 | 5857.08 | 1667.58 | 4497.24 | 986.39 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7430 | 0.0000 | 0.7430 | 0.0000 | 0.7430 | 0.4247 | 1725.30 | 329.49 | 3888.21 |
CORE_MID | 0.5145 | 0.0000 | 0.5145 | 0.0000 | 0.5145 | 0.4247 | 1764.15 | 1109.58 | 3069.27 |
CORE_TOP | 0.4951 | 0.0000 | 0.4951 | 0.0000 | 0.4951 | 0.4247 | 1824.66 | 1207.89 | 2910.44 |
PERIMETER_TOP_ZN_3 | 0.1121 | 0.0000 | 0.1121 | 0.0055 | 0.1176 | 0.0895 | 1659.29 | 1130.61 | 3153.10 |
PERIMETER_TOP_ZN_2 | 0.1034 | 0.0000 | 0.1034 | 0.0037 | 0.1071 | 0.0567 | 1635.33 | 1329.71 | 2977.96 |
PERIMETER_TOP_ZN_1 | 0.1785 | 0.0000 | 0.1785 | 0.0055 | 0.1840 | 0.0895 | 1586.05 | 1330.67 | 3026.28 |
PERIMETER_TOP_ZN_4 | 0.1035 | 0.0000 | 0.1035 | 0.0037 | 0.1071 | 0.0567 | 1589.93 | 931.96 | 3421.11 |
PERIMETER_BOT_ZN_3 | 0.0973 | 0.0000 | 0.0973 | 0.0029 | 0.1002 | 0.0895 | 2828.18 | 409.31 | 2705.51 |
PERIMETER_BOT_ZN_2 | 0.0919 | 0.0000 | 0.0919 | 0.0020 | 0.0938 | 0.0567 | 2568.80 | 436.18 | 2938.01 |
PERIMETER_BOT_ZN_1 | 0.1441 | 0.0000 | 0.1441 | 0.1295 | 0.2736 | 0.0895 | 2234.53 | 327.34 | 3381.12 |
PERIMETER_BOT_ZN_4 | 0.0902 | 0.0000 | 0.0902 | 0.0020 | 0.0921 | 0.0567 | 2644.76 | 415.52 | 2882.72 |
PERIMETER_MID_ZN_3 | 0.1134 | 0.0000 | 0.1134 | 0.0046 | 0.1180 | 0.0895 | 1760.47 | 1199.26 | 2983.27 |
PERIMETER_MID_ZN_2 | 0.0947 | 0.0000 | 0.0947 | 0.0033 | 0.0980 | 0.0567 | 1524.06 | 959.27 | 2550.67 |
PERIMETER_MID_ZN_1 | 0.1810 | 0.0000 | 0.1810 | 0.0046 | 0.1856 | 0.0895 | 1514.85 | 1164.40 | 3263.75 |
PERIMETER_MID_ZN_4 | 0.1033 | 0.0000 | 0.1033 | 0.0031 | 0.1064 | 0.0567 | 1653.85 | 909.79 | 3379.36 |
Total Facility | 3.1658 | 0.0000 | 3.1658 | 0.1702 | 3.3360 | 2.1513 | 3059.91 | 1667.58 | 4442.92 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 35367767.39 | 0.00 | 35367767.39 | 22614548.33 | 4080.97 | 4.04 | 4674.99 | 43.81 |
PACU_VAV_MID | 30632710.76 | 0.00 | 30632710.76 | 22429071.92 | 4064.52 | 2.54 | 4692.94 | 50.42 |
PACU_VAV_TOP | 30180048.77 | 0.00 | 30180048.77 | 22614548.33 | 4098.16 | 3.42 | 4658.42 | 51.27 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.6436 | 0.0000 | 1.6436 | 0.7171 | 1297.94 | 4.04 | 4641.02 |
PACU_VAV_MID | 1.4209 | 0.0000 | 1.4209 | 0.7084 | 1286.61 | 2.54 | 4653.86 |
PACU_VAV_TOP | 1.3982 | 0.0000 | 1.3982 | 0.7171 | 1324.58 | 3.42 | 4615.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 325.61 | 3057.80 | 0.00 | 0.00 | 0.00 | 1400.45 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 35.82 | 2913.56 | 0.00 | 0.00 | 0.00 | 1874.06 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 32.00 | 2820.26 | 0.00 | 0.00 | 0.00 | 1968.46 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3274 | 2.5788 | 0.0000 | 0.0000 | 0.0000 | 1.1187 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2395 | 2.2627 | 0.0000 | 0.0000 | 0.0000 | 1.0261 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1614 | 2.2538 | 0.0000 | 0.0000 | 0.0000 | 1.0336 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1005 |
Defaulted Fields | 578 |
Fields with Defaults | 2423 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
Electricity:Building | 953.57 | 13383.13 | 23-APR-17:20 | 66674.30 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 953.57 | 13383.13 | 23-APR-17:20 | 66674.30 | 02-JAN-16:30 |
InteriorLights:Electricity | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 233.88 | 905.38 | 23-APR-17:20 | 25003.79 | 02-JAN-16:30 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.26 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.74 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.12 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.73 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.24 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.90 | 27.57 | 08-JAN-10:20 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.90 | 27.57 | 08-JAN-10:20 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.73 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.33 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.10 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.77 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.77 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.72 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.32 | 17.46 | 01-JAN-10:30 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.32 | 17.46 | 01-JAN-10:30 | 658.71 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.26 | 413.68 | 19-MAR-17:10 | 2475.80 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.93 | 27.57 | 08-JAN-10:30 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.74 | 261.88 | 09-APR-17:10 | 1567.33 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.34 | 17.46 | 01-JAN-09:50 | 658.76 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.12 | 413.67 | 19-MAR-17:10 | 2475.79 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.78 | 27.57 | 01-JAN-09:50 | 1040.56 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.73 | 261.87 | 19-MAR-17:10 | 1567.28 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.33 | 17.46 | 01-JAN-13:00 | 658.71 | 02-JAN-16:30 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 170.70 | 367.92 | 01-JAN-00:10 | 80491.03 | 10-AUG-15:10 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-08:10 |
ElectricityPurchased:Facility | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
ElectricityPurchased:Plant | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
Cogeneration:ElectricityPurchased | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
ElectricityNet:Plant | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
Cogeneration:ElectricityNet | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
General:Cogeneration:ElectricityNet | 1231.50 | 13751.66 | 04-JUN-17:40 | 146002.71 | 10-AUG-15:20 |
Fans:Electricity | 74.09 | 0.00 | 01-JAN-00:10 | 28025.63 | 31-JUL-15:10 |
General:Fans:Electricity | 74.09 | 0.00 | 01-JAN-00:10 | 28025.63 | 31-JUL-15:10 |
ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.64 | 0.00 | 01-JAN-08:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 69.72 | 0.00 | 01-JAN-00:10 | 52760.88 | 29-AUG-15:30 |
General:Cooling:Electricity | 69.72 | 0.00 | 01-JAN-00:10 | 52760.88 | 29-AUG-15:30 |
Electricity:Plant | 55.59 | 0.00 | 01-JAN-00:10 | 6854.44 | 13-FEB-12:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 54.28 | 0.00 | 01-JAN-00:10 | 6514.69 | 10-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 54.28 | 0.00 | 01-JAN-00:10 | 6514.69 | 10-FEB-12:50 |
Pumps:Electricity | 1.31 | 0.00 | 01-JAN-00:10 | 552.05 | 26-DEC-07:10 |
General:Pumps:Electricity | 1.31 | 0.00 | 01-JAN-00:10 | 552.05 | 26-DEC-07:10 |
WIRED_LTG_ELECTRICITY | 6.57 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-16:40 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 235.98 | 0.00 | 01-JAN-00:10 | 184170.64 | 26-DEC-07:20 |
NaturalGas:Plant | 235.98 | 0.00 | 01-JAN-00:10 | 184170.64 | 26-DEC-07:20 |
Heating:NaturalGas | 235.98 | 0.00 | 01-JAN-00:10 | 184170.64 | 26-DEC-07:20 |
Boiler:Heating:NaturalGas | 235.98 | 0.00 | 01-JAN-00:10 | 184170.64 | 26-DEC-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1579.89 | 0.00 | 01-JAN-00:10 | 394997.00 | 26-DEC-07:20 |
EnergyTransfer:Building | 896.24 | 0.00 | 01-JAN-00:10 | 156441.60 | 31-JUL-14:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 207.56 | 0.00 | 01-JAN-00:10 | 24449.68 | 14-AUG-07:40 |
Heating:EnergyTransfer | 69.45 | 0.00 | 01-JAN-00:10 | 122432.42 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 4899.21 | 02-JAN-06:20 |
General:Heating:EnergyTransfer | 69.45 | 0.00 | 01-JAN-00:10 | 122432.42 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.09 | 0.00 | 01-JAN-00:10 | 4899.21 | 02-JAN-06:20 |
Cooling:EnergyTransfer | 826.79 | 0.00 | 01-JAN-00:10 | 156441.60 | 31-JUL-14:50 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 207.47 | 0.00 | 01-JAN-00:10 | 24449.68 | 14-AUG-07:40 |
General:Cooling:EnergyTransfer | 826.79 | 0.00 | 01-JAN-00:10 | 156441.60 | 31-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 207.47 | 0.00 | 01-JAN-00:10 | 24449.68 | 14-AUG-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.17 | 0.00 | 01-JAN-00:10 | 10201.19 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 13.74 | 0.00 | 01-JAN-00:10 | 10201.19 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 13.74 | 0.00 | 01-JAN-00:10 | 10201.19 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.43 | 0.00 | 01-JAN-00:10 | 9937.18 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.43 | 0.00 | 01-JAN-00:10 | 9937.18 | 10-AUG-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.58 | 0.00 | 01-JAN-00:10 | 8455.01 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.01 | 0.00 | 01-JAN-00:10 | 8455.01 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.01 | 0.00 | 01-JAN-00:10 | 8455.01 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.57 | 0.00 | 01-JAN-00:10 | 4700.60 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.57 | 0.00 | 01-JAN-00:10 | 4700.60 | 14-AUG-15:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 20.77 | 0.00 | 01-JAN-00:10 | 6980.36 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.81 | 0.00 | 01-JAN-00:10 | 6980.36 | 02-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 4.81 | 0.00 | 01-JAN-00:10 | 6980.36 | 02-JAN-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.96 | 0.00 | 01-JAN-00:10 | 5170.10 | 14-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.96 | 0.00 | 01-JAN-00:10 | 5170.10 | 14-AUG-15:00 |
EnergyTransfer:Zone:CORE_MID | 132.03 | 0.00 | 01-JAN-00:10 | 17520.99 | 14-AUG-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.54 | 0.00 | 01-JAN-00:10 | 12189.20 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.54 | 0.00 | 01-JAN-00:10 | 12189.20 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_MID | 131.48 | 0.00 | 01-JAN-00:10 | 17520.99 | 14-AUG-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 131.48 | 0.00 | 01-JAN-00:10 | 17520.99 | 14-AUG-07:40 |
EnergyTransfer:Zone:CORE_TOP | 119.86 | 0.00 | 01-JAN-00:10 | 18814.88 | 24-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.76 | 0.00 | 01-JAN-00:10 | 18719.73 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 2.76 | 0.00 | 01-JAN-00:10 | 18719.73 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 117.09 | 0.00 | 01-JAN-00:10 | 18814.88 | 24-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 117.09 | 0.00 | 01-JAN-00:10 | 18814.88 | 24-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.84 | 0.00 | 01-JAN-00:10 | 6674.07 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.10 | 0.00 | 01-JAN-00:10 | 6674.07 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 6.10 | 0.00 | 01-JAN-00:10 | 6674.07 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.75 | 0.00 | 01-JAN-00:10 | 6285.20 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 22.75 | 0.00 | 01-JAN-00:10 | 6285.20 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.49 | 0.00 | 01-JAN-00:10 | 9031.25 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.61 | 0.00 | 01-JAN-00:10 | 5616.98 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 3.61 | 0.00 | 01-JAN-00:10 | 5616.98 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.88 | 0.00 | 01-JAN-00:10 | 9031.25 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.88 | 0.00 | 01-JAN-00:10 | 9031.25 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 46.11 | 0.00 | 01-JAN-00:10 | 13825.10 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.49 | 0.00 | 01-JAN-00:10 | 8538.30 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 4.49 | 0.00 | 01-JAN-00:10 | 8538.30 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.62 | 0.00 | 01-JAN-00:10 | 13825.10 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 41.62 | 0.00 | 01-JAN-00:10 | 13825.10 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.23 | 0.00 | 01-JAN-00:10 | 9729.86 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.81 | 0.00 | 01-JAN-00:10 | 5731.68 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 3.81 | 0.00 | 01-JAN-00:10 | 5731.68 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.42 | 0.00 | 01-JAN-00:10 | 9729.86 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 23.42 | 0.00 | 01-JAN-00:10 | 9729.86 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 23.57 | 0.00 | 01-JAN-00:10 | 5160.51 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.26 | 0.00 | 01-JAN-00:10 | 5160.51 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.26 | 0.00 | 01-JAN-00:10 | 5160.51 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.31 | 0.00 | 01-JAN-00:10 | 4871.17 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.31 | 0.00 | 01-JAN-00:10 | 4871.17 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 23.19 | 0.00 | 01-JAN-00:10 | 7389.52 | 24-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 4436.65 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.33 | 0.00 | 01-JAN-00:10 | 4436.65 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.86 | 0.00 | 01-JAN-00:10 | 7389.52 | 24-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.86 | 0.00 | 01-JAN-00:10 | 7389.52 | 24-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 41.05 | 0.00 | 01-JAN-00:10 | 12897.11 | 10-AUG-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.30 | 0.00 | 01-JAN-00:10 | 8149.57 | 26-DEC-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 11.30 | 0.00 | 01-JAN-00:10 | 8149.57 | 26-DEC-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.75 | 0.00 | 01-JAN-00:10 | 12897.11 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 29.75 | 0.00 | 01-JAN-00:10 | 12897.11 | 10-AUG-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.27 | 0.00 | 01-JAN-00:10 | 7955.31 | 31-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.33 | 0.00 | 01-JAN-00:10 | 4528.55 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.33 | 0.00 | 01-JAN-00:10 | 4528.55 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.94 | 0.00 | 01-JAN-00:10 | 7955.31 | 31-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.94 | 0.00 | 01-JAN-00:10 | 7955.31 | 31-JUL-17:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.47 | 0.00 | 01-JAN-00:10 | 5781.74 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.11 | 0.00 | 01-JAN-00:10 | 5502.70 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.11 | 0.00 | 01-JAN-00:10 | 5502.70 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.36 | 0.00 | 01-JAN-00:10 | 5781.74 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.36 | 0.00 | 01-JAN-00:10 | 5781.74 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.30 | 0.00 | 01-JAN-00:10 | 9061.08 | 31-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.31 | 0.00 | 01-JAN-00:10 | 4727.48 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.31 | 0.00 | 01-JAN-00:10 | 4727.48 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.00 | 0.00 | 01-JAN-00:10 | 9061.08 | 31-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.00 | 0.00 | 01-JAN-00:10 | 9061.08 | 31-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 46.37 | 0.00 | 01-JAN-00:10 | 13640.78 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.51 | 0.00 | 01-JAN-00:10 | 7031.93 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.51 | 0.00 | 01-JAN-00:10 | 7031.93 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 44.86 | 0.00 | 01-JAN-00:10 | 13640.78 | 04-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 44.86 | 0.00 | 01-JAN-00:10 | 13640.78 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.36 | 0.00 | 01-JAN-00:10 | 9266.87 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.33 | 0.00 | 01-JAN-00:10 | 4726.58 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.33 | 0.00 | 01-JAN-00:10 | 4726.58 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.03 | 0.00 | 01-JAN-00:10 | 9266.87 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.03 | 0.00 | 01-JAN-00:10 | 9266.87 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 214.47 | 0.00 | 01-JAN-00:10 | 149614.58 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 470.45 | 0.00 | 01-JAN-00:10 | 212659.49 | 31-JUL-14:30 |
HeatingCoils:EnergyTransfer | 162.98 | 0.00 | 01-JAN-00:10 | 147577.39 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 162.98 | 0.00 | 01-JAN-00:10 | 147577.39 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 162.98 | 0.00 | 01-JAN-00:10 | 147577.39 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 307.46 | 0.00 | 01-JAN-00:10 | 212646.48 | 31-JUL-14:30 |
EnergyTransfer:Plant | 213.21 | 0.00 | 01-JAN-00:10 | 147967.20 | 26-DEC-07:20 |
WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.49 | 0.00 | 01-JAN-00:10 | 6247.39 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 161.72 | 0.00 | 01-JAN-00:10 | 145930.02 | 26-DEC-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.089 | -207.467 | 0.000 | 0.000 | 32.860 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -131.504 |
CORE_MID | 0.000 | 0.000 | 0.542 | -131.484 | 0.000 | 0.000 | 33.966 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.047 |
CORE_TOP | 0.000 | 0.000 | 2.765 | -117.090 | 0.000 | 0.000 | 34.760 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -91.458 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 6.096 | -22.745 | 0.000 | 0.000 | 7.546 | 6.927 | 24.333 | 13.857 | 0.000 | 0.008 | 0.001 | 0.000 | -28.335 | 0.000 | -3.182 | -4.505 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 3.607 | -22.883 | 0.000 | 0.000 | 4.709 | 4.339 | 15.404 | 26.280 | 0.000 | 0.005 | 0.000 | 0.000 | -18.367 | 0.000 | -2.154 | -10.940 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 4.492 | -41.620 | 0.000 | 0.000 | 7.378 | 6.784 | 24.332 | 56.860 | 0.000 | 0.007 | 0.001 | 0.000 | -28.182 | 0.000 | -3.316 | -26.735 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 3.811 | -23.418 | 0.000 | 0.000 | 4.746 | 4.331 | 15.403 | 28.391 | 0.000 | 0.005 | 0.000 | 0.000 | -18.949 | 0.000 | -2.176 | -12.146 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.259 | -21.315 | 0.000 | 0.000 | 7.488 | 6.904 | 24.333 | 14.041 | 0.000 | 0.005 | 0.000 | 0.000 | -29.690 | 0.000 | -1.781 | -2.244 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.329 | -21.864 | 0.000 | 0.000 | 4.663 | 4.329 | 15.404 | 26.342 | 0.000 | 0.003 | 0.001 | 0.000 | -19.460 | 0.000 | -1.221 | -9.524 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 11.303 | -29.746 | 0.000 | 0.000 | 7.539 | 6.770 | 24.332 | 57.409 | 0.000 | 0.383 | 0.000 | 0.000 | -29.689 | 0.000 | -32.749 | -15.553 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.334 | -21.939 | 0.000 | 0.000 | 4.687 | 4.321 | 15.403 | 28.541 | 0.000 | 0.003 | 0.002 | 0.000 | -20.153 | 0.000 | -1.235 | -10.961 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.107 | -25.358 | 0.000 | 0.000 | 7.426 | 6.927 | 24.333 | 13.549 | 0.000 | 0.008 | 4.091 | 0.000 | -30.262 | 0.000 | -2.820 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.307 | -22.998 | 0.000 | 0.000 | 3.428 | 4.339 | 15.404 | 25.968 | 0.000 | 0.004 | 0.002 | 0.000 | -19.568 | 0.000 | -1.909 | -5.975 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.513 | -44.857 | 0.000 | 0.000 | 7.263 | 6.784 | 24.332 | 56.508 | 0.000 | 0.006 | 0.001 | 0.000 | -29.975 | 0.000 | -2.931 | -18.644 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.326 | -25.030 | 0.000 | 0.000 | 4.671 | 4.331 | 15.403 | 28.204 | 0.000 | 0.004 | 0.001 | 0.000 | -20.197 | 0.000 | -1.924 | -6.789 |
TOPFLOOR_PLENUM | 13.740 | -20.434 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.005 | 11.593 | 0.000 | 0.000 | 0.000 | -4.904 | -0.001 |
MIDFLOOR_PLENUM | 7.009 | -10.575 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.009 | 8.409 | 0.000 | 0.000 | 0.000 | -4.853 | -0.001 |
FIRSTFLOOR_PLENUM | 4.815 | -15.960 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.007 | 15.093 | 0.000 | 0.000 | 0.000 | -3.954 | -0.000 |
Total Facility | 25.564 | -46.969 | 43.881 | -779.815 | 0.000 | 0.000 | 173.133 | 233.882 | 719.689 | 375.950 | 0.000 | 0.461 | 39.196 | 0.000 | -292.827 | 0.000 | -71.109 | -421.029 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 28-AUG-05:12 | 0.00 | 0.00 | 0.00 | -39446.24 | 0.00 | 0.00 | 313.03 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 31174.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -30634.21 | 0.00 | 0.00 | 325.07 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 26734.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-AUG-06:02 | 0.00 | 0.00 | 0.00 | -27856.74 | 0.00 | 0.00 | 711.92 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 22473.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6845.78 | 0.00 | 0.00 | 148.57 | 165.45 | 637.89 | 2185.84 | 0.00 | 0.00 | 3722.98 | 0.00 | -0.00 | 0.00 | -14.94 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-JUL-09:12 | 0.00 | 0.00 | 0.00 | -14416.35 | 0.00 | 0.00 | 14.19 | 17.46 | 302.86 | 9590.43 | 0.00 | 0.00 | 4541.80 | 0.00 | -0.00 | 0.00 | -50.38 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-12:02 | 0.00 | 0.00 | 0.00 | -21364.54 | 0.00 | 0.00 | 22.85 | 27.57 | 478.41 | 15829.61 | 0.00 | 0.00 | 5085.88 | 0.00 | -0.00 | 0.00 | -79.79 | 0.00 |
PERIMETER_TOP_ZN_4 | 10-SEP-16:41 | 0.00 | 0.00 | 0.00 | -15916.06 | 0.00 | 0.00 | 13.42 | 17.46 | 302.86 | 10125.35 | 0.00 | 0.00 | 5501.97 | 0.00 | -0.00 | 0.00 | -44.99 | 0.00 |
PERIMETER_BOT_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -4890.89 | 0.00 | 0.00 | 151.30 | 165.45 | 637.89 | 2238.72 | 0.00 | 0.00 | 1705.36 | 0.00 | -0.00 | 0.00 | -7.82 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-09:32 | 0.00 | 0.00 | 0.00 | -11483.21 | 0.00 | 0.00 | 15.84 | 17.46 | 302.86 | 9063.62 | 0.00 | 0.00 | 2116.22 | 0.00 | -0.00 | 0.00 | -32.78 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:52 | 0.00 | 0.00 | 0.00 | -16934.32 | 0.00 | 0.00 | 25.24 | 27.57 | 478.41 | 12609.00 | 0.00 | 0.00 | 3804.78 | 0.00 | -0.00 | 0.00 | -10.69 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-AUG-18:32 | 0.00 | 0.00 | 0.00 | -12967.75 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 6630.29 | 0.00 | 0.00 | 6111.62 | 0.00 | -0.00 | 0.00 | -36.04 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7053.14 | 0.00 | 0.00 | 144.67 | 165.45 | 637.89 | 2149.22 | 0.00 | 0.00 | 3968.93 | 0.00 | -0.00 | 0.00 | -13.03 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-08:12 | 0.00 | 0.00 | 0.00 | -14450.40 | 0.00 | 0.00 | 14.09 | 17.46 | 302.86 | 11266.13 | 0.00 | 0.00 | 2934.03 | 0.00 | -0.00 | 0.00 | -84.16 | 0.00 |
PERIMETER_MID_ZN_1 | 13-AUG-12:52 | 0.00 | 0.00 | 0.00 | -19703.37 | 0.00 | 0.00 | 23.17 | 27.57 | 478.41 | 12505.56 | 0.00 | 0.00 | 6693.28 | 0.00 | -0.00 | 0.00 | -24.62 | 0.00 |
PERIMETER_MID_ZN_4 | 07-MAY-16:41 | 0.00 | 0.00 | 0.00 | -15138.32 | 0.00 | 0.00 | 13.44 | 17.46 | 302.86 | 11059.46 | 0.00 | 0.00 | 3808.99 | 0.00 | -0.00 | 0.00 | -63.88 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -9936.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 9920.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -4760.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4796.23 | 0.00 | -0.00 | 0.00 | -35.36 | 0.00 |
FIRSTFLOOR_PLENUM | 14-AUG-06:13 | 0.00 | -5293.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5320.98 | 0.00 | -0.00 | 0.00 | -27.44 | 0.00 |
Total Facility | 24-JUL-06:03 | 0.00 | -3934.17 | 0.00 | -159632.81 | 0.00 | 0.00 | 3551.81 | 6557.23 | 22496.85 | 30666.85 | 0.00 | 0.00 | 105668.13 | 0.00 | -148.49 | 0.00 | -5225.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:11 | 0.00 | 0.00 | 5569.77 | 0.00 | 0.00 | 0.00 | 494.18 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14022.73 |
CORE_MID | 02-JAN-06:11 | 0.00 | 0.00 | 13223.89 | 0.00 | 0.00 | 0.00 | 524.41 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17322.65 |
CORE_TOP | 02-JAN-06:11 | 0.00 | 0.00 | 20223.67 | 0.00 | 0.00 | 0.00 | 536.32 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24334.33 |
PERIMETER_TOP_ZN_3 | 26-DEC-05:01 | 0.00 | 0.00 | 7319.35 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1742.70 | 0.00 | 0.00 | -6136.09 |
PERIMETER_TOP_ZN_2 | 26-DEC-05:01 | 0.00 | 0.00 | 6721.05 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.84 | 0.00 | 0.00 | -5915.36 |
PERIMETER_TOP_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 10117.83 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1751.64 | 0.00 | 0.00 | -8925.63 |
PERIMETER_TOP_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 6968.33 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.81 | 0.00 | 0.00 | -6162.67 |
PERIMETER_BOT_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 5539.49 | 0.00 | 0.00 | 0.00 | 112.89 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1092.93 | 0.00 | -34.89 | -5278.06 |
PERIMETER_BOT_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5125.01 | 0.00 | 0.00 | 0.00 | 71.45 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -741.97 | 0.00 | -23.58 | -4907.92 |
PERIMETER_BOT_ZN_1 | 26-DEC-07:40 | 0.00 | 0.00 | 8148.85 | 0.00 | 0.00 | 0.00 | 230.11 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 7176.28 | 0.00 | -2133.42 | 0.00 | -14406.57 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5310.40 | 0.00 | 0.00 | 0.00 | 71.45 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -726.24 | 0.00 | -23.62 | -5108.99 |
PERIMETER_MID_ZN_3 | 02-JAN-06:11 | 0.00 | 0.00 | 5952.67 | 0.00 | 0.00 | 0.00 | 113.18 | 115.61 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1094.99 | 0.00 | -54.78 | -5669.57 |
PERIMETER_MID_ZN_2 | 02-JAN-06:11 | 0.00 | 0.00 | 5638.14 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.33 | 0.00 | -37.11 | -5403.35 |
PERIMETER_MID_ZN_1 | 02-JAN-06:11 | 0.00 | 0.00 | 8251.57 | 0.00 | 0.00 | 0.00 | 113.18 | 115.61 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1121.42 | 0.00 | -55.50 | -7941.33 |
PERIMETER_MID_ZN_4 | 02-JAN-06:11 | 0.00 | 0.00 | 5659.58 | 0.00 | 0.00 | 0.00 | 71.65 | 73.19 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -728.81 | 0.00 | -37.12 | -5442.29 |
TOPFLOOR_PLENUM | 21-FEB-06:10 | 11226.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -54.52 | -11171.75 |
MIDFLOOR_PLENUM | 02-JAN-08:40 | 8632.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -76.44 | -8556.56 |
FIRSTFLOOR_PLENUM | 02-JAN-08:10 | 7118.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -49.05 | -7069.79 |
Total Facility | 02-JAN-06:11 | 7708.68 | 0.00 | 118493.19 | 0.00 | 0.00 | 0.00 | 2663.17 | 2778.13 | 19712.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10958.32 | 0.00 | -1866.03 | -138531.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.3540 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6593 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.2261 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3254 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.4956 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8996 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6770 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6131 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0746 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7478 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5674 | 2.5674 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0464 | 2.0464 | 0.6364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1034 | 2.1034 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5954 | 0.5954 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7784 | 0.7784 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1649 | 1.1649 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8535 | 0.8535 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4743 | 0.4743 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6432 | 0.6432 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9553 | 0.9553 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7138 | 0.7138 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5237 | 0.5237 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7788 | 0.7788 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0810 | 1.0810 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7962 | 0.7962 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.3540 | 4.6593 | 5.3540 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.2261 | 4.3254 | 5.2261 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.4956 | 4.8996 | 5.4956 | 1.0760 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2837 | 1.2837 | 0.6367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0232 | 1.0232 | 0.6364 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0517 | 1.0517 | 0.6373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2977 | 0.2977 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3892 | 0.3892 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5825 | 0.5825 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4267 | 0.4267 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2372 | 0.2372 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3216 | 0.3216 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4777 | 0.4777 | 0.1347 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3569 | 0.3569 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2619 | 0.2619 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3894 | 0.3894 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5405 | 0.5405 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3981 | 0.3981 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6770 | 1.0755 | 1.0755 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6131 | 1.0746 | 1.0746 | 1.0746 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7478 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 304.33 |
Number of hours cooling loads not met | 74.33 |
Number of hours not met | 378.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 235.98 | 184170.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 69.72 | 52760.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 233.88 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.64 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 74.09 | 28025.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1.31 | 552.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 54.28 | 6514.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1231.50 |
Natural Gas | 0.00 | 235.98 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1467.48 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.94 |
Space Heating | 0.00 |
Space Cooling | 13.99 |
Fans (All) | 14.87 |
Service Water Heating | 10.89 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 247.18 |
Subtotal | 247.18 |
Natural Gas [MJ/m2] | |
Space Heating | 47.37 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 47.37 |
Subtotal | 47.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 15.94 |
Space Heating | 16.08 |
Space Cooling | 4.75 |
Fans (All) | 5.05 |
Service Water Heating | 3.70 |
Receptacle Equipment | 49.04 |
Miscellaneous | 5.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 862. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8717.33 | 42.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8697.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 62.67 | 0.00 | 0.00 | 0.00 |
Average | 8743.34 | 16.66 | 0.00 | 0.00 | 0.00 |
Sum | 157380.17 | 299.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128276.33 | 27.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 27.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.80 | 1.54 | 0.00 | 0.00 | 0.00 |
Sum | 614552.33 | 27.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8585.33 | 174.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8753.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8703.67 | 56.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8725.83 | 34.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8720.83 | 39.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8585.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 174.67 | 0.00 | 0.00 | 0.00 |
Average | 8729.58 | 30.42 | 0.00 | 0.00 | 0.00 |
Sum | 157132.50 | 547.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128209.50 | 94.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128296.67 | 7.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128299.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128299.33 | 94.50 | 0.00 | 0.00 | 0.00 |
Average | 34137.42 | 5.92 | 0.00 | 0.00 | 0.00 |
Sum | 614473.50 | 106.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862208E+10 | 11135.99 | 12-JAN-17:00 | 7.20 | 5.41 | 0.187432E+10 | 2606.62 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.991251E+10 | 14787.18 | 28-FEB-17:00 | 14.40 | 10.82 | 0.178338E+10 | 2606.65 | 08-FEB-10:09 | 14.40 | 10.82 |
March | 0.154513E+11 | 18718.85 | 20-MAR-06:03 | 6.70 | 4.63 | 0.215454E+10 | 2606.66 | 09-MAR-14:09 | 6.70 | 4.63 |
April | 0.170474E+11 | 35561.64 | 28-APR-06:02 | 11.10 | 10.22 | 0.191742E+10 | 2606.66 | 27-APR-13:20 | 11.10 | 10.22 |
May | 0.216730E+11 | 38168.83 | 08-MAY-05:12 | 9.60 | 9.49 | 0.207809E+10 | 2606.68 | 05-MAY-09:09 | 9.60 | 9.49 |
June | 0.231929E+11 | 39242.96 | 12-JUN-05:12 | 14.40 | 13.42 | 0.207247E+10 | 2606.70 | 05-JUN-13:00 | 14.40 | 13.42 |
July | 0.237631E+11 | 39349.53 | 17-JUL-05:12 | 14.07 | 12.34 | 0.192806E+10 | 2606.65 | 20-JUL-13:20 | 26.30 | 16.68 |
August | 0.257854E+11 | 39453.18 | 28-AUG-05:12 | 14.87 | 13.94 | 0.216302E+10 | 2606.85 | 09-AUG-09:00 | 14.87 | 13.94 |
September | 0.215577E+11 | 39311.09 | 05-SEP-05:12 | 10.77 | 9.27 | 0.192080E+10 | 2606.66 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.177550E+11 | 38096.49 | 10-OCT-05:12 | 12.20 | 11.16 | 0.199411E+10 | 2606.65 | 05-OCT-09:00 | 12.20 | 11.16 |
November | 0.125837E+11 | 28994.82 | 06-NOV-07:03 | 12.20 | 8.82 | 0.196299E+10 | 2606.63 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.101233E+11 | 13627.36 | 06-DEC-15:50 | 3.58 | 3.15 | 0.188510E+10 | 2606.65 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.207467E+12 | 0.237343E+11 | ||||||||
Minimum of Months | 0.862208E+10 | 11135.99 | 3.58 | 3.15 | 0.178338E+10 | 2606.62 | 5.60 | 3.25 | ||
Maximum of Months | 0.257854E+11 | 39453.18 | 14.87 | 13.94 | 0.216302E+10 | 2606.85 | 26.30 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 | 4.99 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 47759164.40 | 1823.93 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.394721E+09 | 2914.98 | 14-MAR-15:10 | 16.28 | 10.42 | 0.00 | 0.00 | 01-MAR-00:10 | 16.28 | 10.42 |
April | 0.142774E+10 | 8433.97 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.270702E+10 | 8836.77 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.352724E+10 | 8637.11 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.470201E+10 | 9838.89 | 24-JUL-13:40 | 29.03 | 18.20 | 0.00 | 0.00 | 01-JUL-00:10 | 29.03 | 18.20 |
August | 0.457390E+10 | 9937.18 | 10-AUG-14:40 | 29.93 | 18.99 | 0.00 | 0.00 | 01-AUG-00:10 | 29.93 | 18.99 |
September | 0.238330E+10 | 7763.91 | 14-SEP-14:40 | 23.90 | 17.01 | 0.00 | 0.00 | 01-SEP-00:10 | 23.90 | 17.01 |
October | 0.626073E+09 | 5440.22 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 43254109.45 | 2302.28 | 04-NOV-14:30 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 1424304.53 | 293.71 | 02-DEC-15:05 | 11.52 | 5.36 | 0.00 | 0.00 | 01-DEC-00:10 | 11.52 | 5.36 |
Annual Sum or Average | 0.204344E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 5.92 | 4.99 | 0.00 | 0.00 | 5.92 | 4.99 | ||
Maximum of Months | 0.470201E+10 | 9937.18 | 29.93 | 18.99 | 0.00 | 0.00 | 29.93 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4968117.85 | 1613.35 | 14-JAN-06:11 | 2.20 | 1.14 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.14 |
February | 40866239.89 | 1852.09 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.154986E+09 | 2786.69 | 01-MAR-07:01 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.485201E+09 | 2961.05 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.110539E+10 | 3365.66 | 15-MAY-15:20 | 23.50 | 12.70 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 12.70 |
June | 0.179259E+10 | 3363.03 | 28-JUN-15:40 | 26.10 | 16.04 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.04 |
July | 0.245945E+10 | 4626.37 | 31-JUL-15:10 | 28.40 | 18.96 | 0.00 | 0.00 | 01-JUL-00:10 | 28.40 | 18.96 |
August | 0.273638E+10 | 4760.82 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.137058E+10 | 3757.16 | 11-SEP-15:30 | 23.30 | 15.99 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.99 |
October | 0.367011E+09 | 2309.86 | 04-OCT-15:40 | 21.30 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.43 |
November | 51993612.81 | 2105.67 | 10-NOV-07:02 | 4.08 | 3.61 | 0.00 | 0.00 | 01-NOV-00:10 | 4.08 | 3.61 |
December | 5503382.76 | 1317.10 | 07-DEC-07:03 | 6.10 | 3.18 | 0.00 | 0.00 | 01-DEC-00:10 | 6.10 | 3.18 |
Annual Sum or Average | 0.105749E+11 | 0.00 | ||||||||
Minimum of Months | 4968117.85 | 1317.10 | -0.1 | -1.7 | 0.00 | 0.00 | -0.1 | -1.7 | ||
Maximum of Months | 0.273638E+10 | 4760.82 | 28.40 | 18.96 | 0.00 | 0.00 | 28.40 | 18.96 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79525239.63 | 2274.79 | 13-JAN-06:11 | 3.13 | 2.22 | 0.00 | 0.00 | 01-JAN-00:10 | 3.13 | 2.22 |
February | 0.138925E+09 | 2735.38 | 10-FEB-07:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 0.60 | -0.1 |
March | 0.401829E+09 | 3354.60 | 01-MAR-07:01 | -0.1 | -1.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -1.7 |
April | 0.950286E+09 | 3362.13 | 27-APR-16:00 | 27.20 | 16.90 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 16.90 |
May | 0.182193E+10 | 4003.94 | 08-MAY-06:08 | 9.90 | 9.62 | 0.00 | 0.00 | 01-MAY-00:10 | 9.90 | 9.62 |
June | 0.249887E+10 | 3778.63 | 28-JUN-16:00 | 26.10 | 16.29 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.29 |
July | 0.316351E+10 | 5044.63 | 31-JUL-15:50 | 28.80 | 19.14 | 0.00 | 0.00 | 01-JUL-00:10 | 28.80 | 19.14 |
August | 0.355523E+10 | 5293.39 | 14-AUG-06:13 | 15.73 | 13.91 | 0.00 | 0.00 | 01-AUG-00:10 | 15.73 | 13.91 |
September | 0.218361E+10 | 4559.15 | 11-SEP-15:50 | 23.30 | 16.09 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 16.09 |
October | 0.858447E+09 | 3169.28 | 04-OCT-15:40 | 21.30 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 21.30 | 11.43 |
November | 0.200741E+09 | 2510.15 | 16-NOV-07:02 | 3.48 | 2.25 | 0.00 | 0.00 | 01-NOV-00:10 | 3.48 | 2.25 |
December | 0.107178E+09 | 2372.83 | 07-DEC-07:03 | 6.10 | 3.18 | 0.00 | 0.00 | 01-DEC-00:10 | 6.10 | 3.18 |
Annual Sum or Average | 0.159601E+11 | 0.00 | ||||||||
Minimum of Months | 79525239.63 | 2274.79 | -0.1 | -1.7 | 0.00 | 0.00 | -0.1 | -1.7 | ||
Maximum of Months | 0.355523E+10 | 5293.39 | 28.80 | 19.14 | 0.00 | 0.00 | 28.80 | 19.14 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578408E+10 | 6199.75 | 06-JAN-08:20 | -2.6 | -2.6 | 0.162256E+10 | 2420.62 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.644146E+10 | 7995.20 | 28-FEB-17:00 | 14.40 | 10.82 | 0.158008E+10 | 2606.49 | 28-FEB-14:20 | 14.40 | 10.82 |
March | 0.904932E+10 | 9486.92 | 02-MAR-17:00 | 12.80 | 8.57 | 0.205885E+10 | 2606.63 | 31-MAR-13:09 | 8.98 | 7.53 |
April | 0.102917E+11 | 14268.91 | 27-APR-16:00 | 27.20 | 16.90 | 0.188385E+10 | 2606.66 | 14-APR-09:20 | 27.20 | 16.90 |
May | 0.137143E+11 | 24101.37 | 08-MAY-06:02 | 9.90 | 9.62 | 0.206362E+10 | 2606.66 | 05-MAY-09:09 | 9.90 | 9.62 |
June | 0.152711E+11 | 29913.98 | 12-JUN-05:12 | 14.40 | 13.42 | 0.206448E+10 | 2606.68 | 09-JUN-13:09 | 14.40 | 13.42 |
July | 0.160723E+11 | 30043.78 | 31-JUL-05:12 | 17.40 | 14.58 | 0.192096E+10 | 2606.65 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.174057E+11 | 30634.56 | 14-AUG-05:12 | 15.33 | 13.50 | 0.215638E+10 | 2606.78 | 09-AUG-09:00 | 15.33 | 13.50 |
September | 0.134325E+11 | 27553.24 | 11-SEP-06:01 | 12.07 | 10.69 | 0.190897E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.101503E+11 | 13837.17 | 04-OCT-16:00 | 21.10 | 11.40 | 0.194520E+10 | 2606.65 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.740880E+10 | 8786.26 | 06-NOV-17:00 | 11.70 | 10.80 | 0.179096E+10 | 2606.60 | 06-NOV-14:09 | 11.70 | 10.80 |
December | 0.646313E+10 | 6294.40 | 06-DEC-16:10 | 2.93 | 2.59 | 0.163258E+10 | 2539.83 | 06-DEC-14:00 | 2.93 | 2.59 |
Annual Sum or Average | 0.131485E+12 | 0.226285E+11 | ||||||||
Minimum of Months | 0.578408E+10 | 6199.75 | -2.6 | -2.6 | 0.158008E+10 | 2420.62 | 2.93 | 2.59 | ||
Maximum of Months | 0.174057E+11 | 30634.56 | 27.20 | 16.90 | 0.215638E+10 | 2606.78 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392436E+10 | 5764.07 | 06-JAN-10:30 | -0.9 | -0.9 | 0.153413E+10 | 2294.12 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.508057E+10 | 7018.64 | 28-FEB-17:00 | 14.40 | 10.82 | 0.147338E+10 | 2600.90 | 28-FEB-14:00 | 14.40 | 10.82 |
March | 0.797562E+10 | 8525.16 | 02-MAR-17:00 | 12.80 | 8.57 | 0.193421E+10 | 2606.61 | 02-MAR-14:20 | 12.80 | 8.57 |
April | 0.936607E+10 | 15649.88 | 27-APR-15:40 | 27.20 | 17.03 | 0.182419E+10 | 2606.66 | 27-APR-13:20 | 27.20 | 17.03 |
May | 0.127324E+11 | 16782.74 | 15-MAY-15:30 | 23.60 | 12.74 | 0.204097E+10 | 2606.66 | 05-MAY-09:09 | 23.60 | 12.74 |
June | 0.146322E+11 | 16988.44 | 28-JUN-15:50 | 26.10 | 16.17 | 0.205441E+10 | 2606.68 | 09-JUN-13:09 | 26.10 | 16.17 |
July | 0.157355E+11 | 24132.02 | 24-JUL-06:03 | 17.48 | 14.11 | 0.191448E+10 | 2606.65 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.167320E+11 | 27857.89 | 14-AUG-06:02 | 15.47 | 13.75 | 0.214942E+10 | 2606.77 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.120463E+11 | 16585.34 | 11-SEP-15:40 | 23.30 | 16.04 | 0.188616E+10 | 2606.65 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.858826E+10 | 13717.33 | 04-OCT-16:00 | 21.10 | 11.40 | 0.185624E+10 | 2606.62 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.584557E+10 | 6457.03 | 02-NOV-16:00 | 13.30 | 10.88 | 0.165633E+10 | 2564.87 | 06-NOV-14:00 | 11.10 | 10.22 |
December | 0.443213E+10 | 5844.71 | 05-DEC-16:15 | 6.10 | 4.53 | 0.151035E+10 | 2380.42 | 05-DEC-14:00 | 6.10 | 4.53 |
Annual Sum or Average | 0.117091E+12 | 0.218343E+11 | ||||||||
Minimum of Months | 0.392436E+10 | 5764.07 | -0.9 | -0.9 | 0.147338E+10 | 2294.12 | 6.10 | 4.53 | ||
Maximum of Months | 0.167320E+11 | 27857.89 | 27.20 | 17.03 | 0.214942E+10 | 2606.77 | 27.20 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159520E+09 | 1011.57 | 11-JAN-16:20 | 13.67 | 10.10 | 0.306018E+09 | 439.37 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.450753E+09 | 1286.30 | 28-FEB-15:00 | 13.90 | 10.81 | 0.287075E+09 | 522.35 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.119500E+10 | 1370.43 | 10-MAR-14:50 | 16.20 | 11.59 | 0.370800E+09 | 549.41 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.175165E+10 | 4484.14 | 27-APR-15:20 | 27.20 | 17.16 | 0.362533E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.282617E+10 | 4836.91 | 15-MAY-14:30 | 23.30 | 13.06 | 0.419292E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.352034E+10 | 5131.32 | 21-JUN-15:30 | 24.70 | 15.68 | 0.428969E+09 | 549.51 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.405560E+10 | 6845.41 | 24-JUL-06:03 | 17.48 | 14.11 | 0.401500E+09 | 549.50 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.412266E+10 | 5618.25 | 09-AUG-15:20 | 28.47 | 18.71 | 0.449725E+09 | 549.53 | 09-AUG-09:00 | 28.47 | 18.71 |
September | 0.243959E+10 | 4265.78 | 12-SEP-14:50 | 24.40 | 16.68 | 0.385009E+09 | 549.49 | 15-SEP-09:20 | 16.70 | 14.42 |
October | 0.140660E+10 | 2690.04 | 04-OCT-15:20 | 21.50 | 11.47 | 0.359763E+09 | 549.49 | 03-OCT-13:20 | 21.50 | 11.47 |
November | 0.617589E+09 | 1229.15 | 02-NOV-14:40 | 13.67 | 11.26 | 0.317653E+09 | 502.26 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.200186E+09 | 949.64 | 05-DEC-15:10 | 9.35 | 6.62 | 0.295819E+09 | 425.52 | 05-DEC-14:00 | 9.35 | 6.62 |
Annual Sum or Average | 0.227457E+11 | 0.438416E+10 | ||||||||
Minimum of Months | 0.159520E+09 | 949.64 | 9.35 | 6.62 | 0.287075E+09 | 425.52 | 9.35 | 6.62 | ||
Maximum of Months | 0.412266E+10 | 6845.41 | 28.47 | 18.71 | 0.449725E+09 | 549.53 | 28.47 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148456E+09 | 700.34 | 05-JAN-09:20 | 0.53 | 0.46 | 0.194505E+09 | 282.87 | 11-JAN-14:00 | 14.40 | 10.49 |
February | 0.377219E+09 | 861.28 | 27-FEB-15:50 | 19.50 | 12.39 | 0.188818E+09 | 343.44 | 27-FEB-14:00 | 19.50 | 12.39 |
March | 0.987938E+09 | 2829.59 | 14-MAR-09:50 | 9.63 | 7.44 | 0.251096E+09 | 347.88 | 02-MAR-10:20 | 9.63 | 7.44 |
April | 0.191755E+10 | 6790.76 | 27-APR-09:10 | 17.98 | 12.34 | 0.242305E+09 | 347.88 | 20-APR-09:00 | 17.98 | 12.34 |
May | 0.279394E+10 | 10335.23 | 14-MAY-10:23 | 19.75 | 12.55 | 0.269774E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.374716E+10 | 12374.51 | 25-JUN-08:62 | 15.78 | 11.63 | 0.273888E+09 | 347.88 | 09-JUN-13:09 | 15.78 | 11.63 |
July | 0.405738E+10 | 14418.06 | 30-JUL-09:12 | 21.13 | 15.97 | 0.255472E+09 | 348.43 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.434949E+10 | 13288.98 | 13-AUG-09:02 | 21.20 | 16.02 | 0.286474E+09 | 348.41 | 08-AUG-09:00 | 21.20 | 16.02 |
September | 0.259087E+10 | 13470.85 | 10-SEP-09:22 | 16.65 | 13.51 | 0.248268E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.125558E+10 | 4886.95 | 04-OCT-09:20 | 16.13 | 10.66 | 0.238654E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.453186E+09 | 853.72 | 02-NOV-10:40 | 12.43 | 10.47 | 0.204987E+09 | 337.33 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.204440E+09 | 696.17 | 05-DEC-10:30 | 7.50 | 5.28 | 0.189277E+09 | 297.70 | 05-DEC-10:50 | 8.03 | 5.37 |
Annual Sum or Average | 0.228832E+11 | 0.284352E+10 | ||||||||
Minimum of Months | 0.148456E+09 | 696.17 | 0.53 | 0.46 | 0.188818E+09 | 282.87 | 8.03 | 5.37 | ||
Maximum of Months | 0.434949E+10 | 14418.06 | 21.20 | 16.02 | 0.286474E+09 | 348.43 | 23.30 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.588139E+09 | 6823.43 | 20-JAN-13:30 | 6.70 | 4.72 | 0.323618E+09 | 549.49 | 20-JAN-14:50 | 7.12 | 4.90 |
February | 0.132522E+10 | 8997.67 | 27-FEB-14:30 | 19.15 | 11.80 | 0.315693E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.17 |
March | 0.277706E+10 | 10200.60 | 01-MAR-13:35 | 11.33 | 6.09 | 0.400363E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.361409E+10 | 12120.98 | 27-APR-13:05 | 26.10 | 16.37 | 0.376943E+09 | 550.01 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.449590E+10 | 19530.11 | 14-MAY-15:02 | 23.30 | 12.38 | 0.421988E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.489759E+10 | 10750.92 | 25-JUN-13:23 | 21.10 | 13.16 | 0.428820E+09 | 549.51 | 09-JUN-13:09 | 21.10 | 13.16 |
July | 0.604195E+10 | 20415.85 | 30-JUL-11:52 | 26.10 | 17.22 | 0.401701E+09 | 550.02 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.687647E+10 | 19467.08 | 13-AUG-13:02 | 26.62 | 18.46 | 0.450730E+09 | 550.36 | 29-AUG-13:30 | 29.30 | 20.07 |
September | 0.555178E+10 | 21361.29 | 10-SEP-12:02 | 19.60 | 13.52 | 0.391130E+09 | 550.28 | 15-SEP-13:50 | 21.70 | 16.50 |
October | 0.344315E+10 | 20189.24 | 08-OCT-13:32 | 19.27 | 14.01 | 0.381372E+09 | 549.82 | 04-OCT-13:00 | 19.27 | 14.01 |
November | 0.117961E+10 | 9418.60 | 04-NOV-13:30 | 20.85 | 16.00 | 0.340201E+09 | 549.49 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.829982E+09 | 6970.43 | 05-DEC-12:30 | 10.30 | 6.13 | 0.319502E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.416209E+11 | 0.455206E+10 | ||||||||
Minimum of Months | 0.588139E+09 | 6823.43 | 6.70 | 4.72 | 0.315693E+09 | 549.49 | 7.12 | 4.90 | ||
Maximum of Months | 0.687647E+10 | 21361.29 | 26.62 | 18.46 | 0.450730E+09 | 550.36 | 29.30 | 20.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154725E+09 | 792.99 | 20-JAN-15:50 | 5.87 | 4.23 | 0.196045E+09 | 317.10 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.389206E+09 | 3637.83 | 27-FEB-15:30 | 19.70 | 12.30 | 0.188371E+09 | 347.83 | 28-FEB-14:50 | 13.98 | 10.93 |
March | 0.105609E+10 | 5342.15 | 14-MAR-16:00 | 17.20 | 10.94 | 0.240609E+09 | 347.84 | 01-MAR-14:20 | 17.20 | 10.94 |
April | 0.187098E+10 | 8288.79 | 26-APR-16:00 | 24.40 | 14.49 | 0.231952E+09 | 347.85 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.299996E+10 | 15720.52 | 14-MAY-15:41 | 23.30 | 12.14 | 0.266077E+09 | 347.85 | 05-MAY-09:20 | 23.30 | 12.14 |
June | 0.343515E+10 | 13189.20 | 18-JUN-17:02 | 17.12 | 12.23 | 0.271387E+09 | 347.85 | 05-JUN-13:00 | 17.12 | 12.23 |
July | 0.454341E+10 | 15595.88 | 30-JUL-17:51 | 26.70 | 17.68 | 0.254585E+09 | 347.86 | 20-JUL-13:20 | 26.70 | 17.68 |
August | 0.432518E+10 | 15071.36 | 06-AUG-16:42 | 23.47 | 15.19 | 0.285100E+09 | 347.87 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.274120E+10 | 15914.83 | 10-SEP-16:41 | 22.20 | 14.22 | 0.245401E+09 | 347.85 | 05-SEP-09:20 | 22.20 | 14.22 |
October | 0.127104E+10 | 6730.77 | 04-OCT-16:00 | 21.10 | 11.40 | 0.231238E+09 | 347.85 | 25-OCT-13:20 | 13.50 | 10.37 |
November | 0.444036E+09 | 2844.55 | 04-NOV-15:30 | 20.55 | 15.94 | 0.204198E+09 | 347.84 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.187260E+09 | 984.24 | 05-DEC-15:30 | 8.05 | 5.82 | 0.191134E+09 | 338.68 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.234182E+11 | 0.280610E+10 | ||||||||
Minimum of Months | 0.154725E+09 | 792.99 | 5.87 | 4.23 | 0.188371E+09 | 317.10 | 5.60 | 4.08 | ||
Maximum of Months | 0.454341E+10 | 15914.83 | 26.70 | 17.68 | 0.285100E+09 | 347.87 | 26.70 | 17.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282278E+09 | 989.47 | 11-JAN-16:20 | 13.67 | 10.10 | 0.307733E+09 | 436.73 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.580163E+09 | 1193.94 | 28-FEB-14:20 | 14.23 | 11.32 | 0.287732E+09 | 496.25 | 28-FEB-14:30 | 14.15 | 11.19 |
March | 0.133074E+10 | 1238.95 | 10-MAR-14:50 | 16.20 | 11.59 | 0.371007E+09 | 510.23 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.156547E+10 | 2710.20 | 27-APR-16:00 | 27.20 | 16.90 | 0.360262E+09 | 549.50 | 27-APR-13:20 | 27.20 | 16.90 |
May | 0.228909E+10 | 3176.98 | 05-MAY-15:30 | 24.70 | 17.20 | 0.422600E+09 | 549.50 | 05-MAY-09:20 | 24.70 | 17.20 |
June | 0.285400E+10 | 3901.26 | 21-JUN-15:30 | 24.70 | 15.68 | 0.431206E+09 | 549.50 | 09-JUN-13:20 | 24.70 | 15.68 |
July | 0.337895E+10 | 4890.93 | 24-JUL-06:03 | 17.48 | 14.11 | 0.403005E+09 | 549.50 | 20-JUL-13:20 | 17.48 | 14.11 |
August | 0.357221E+10 | 4466.03 | 09-AUG-15:30 | 28.70 | 18.83 | 0.452143E+09 | 549.52 | 09-AUG-09:00 | 28.70 | 18.83 |
September | 0.229907E+10 | 3358.73 | 12-SEP-15:20 | 24.40 | 16.82 | 0.393529E+09 | 549.49 | 05-SEP-09:20 | 24.40 | 16.82 |
October | 0.163354E+10 | 2123.50 | 04-OCT-15:30 | 21.40 | 11.45 | 0.378855E+09 | 549.49 | 03-OCT-13:20 | 21.40 | 11.45 |
November | 0.105330E+10 | 1264.79 | 06-NOV-12:00 | 13.90 | 10.05 | 0.334182E+09 | 514.05 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.475866E+09 | 980.28 | 14-DEC-13:40 | 9.63 | 7.19 | 0.300538E+09 | 434.18 | 14-DEC-14:09 | 8.90 | 6.73 |
Annual Sum or Average | 0.213147E+11 | 0.444279E+10 | ||||||||
Minimum of Months | 0.282278E+09 | 980.28 | 9.63 | 7.19 | 0.287732E+09 | 434.18 | 8.90 | 6.73 | ||
Maximum of Months | 0.357221E+10 | 4890.93 | 28.70 | 18.83 | 0.452143E+09 | 549.52 | 28.70 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234655E+09 | 715.65 | 05-JAN-09:00 | -0.6 | -0.6 | 0.195993E+09 | 282.91 | 20-JAN-10:00 | 5.60 | 3.25 |
February | 0.468962E+09 | 797.96 | 27-FEB-15:40 | 19.60 | 12.34 | 0.190124E+09 | 326.44 | 27-FEB-14:00 | 19.60 | 12.34 |
March | 0.102781E+10 | 1691.41 | 14-MAR-10:00 | 10.00 | 7.75 | 0.253637E+09 | 347.88 | 02-MAR-10:20 | 10.00 | 7.75 |
April | 0.165423E+10 | 5104.60 | 27-APR-09:30 | 18.35 | 12.60 | 0.244682E+09 | 347.88 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.235779E+10 | 8604.73 | 15-MAY-06:02 | 11.97 | 9.44 | 0.272255E+09 | 347.89 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.331698E+10 | 8708.61 | 19-JUN-06:02 | 11.88 | 9.64 | 0.275114E+09 | 347.88 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.363150E+10 | 9679.98 | 23-JUL-08:42 | 18.72 | 13.76 | 0.256280E+09 | 348.16 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.412904E+10 | 11483.94 | 13-AUG-09:32 | 22.10 | 16.37 | 0.287574E+09 | 348.19 | 14-AUG-09:00 | 21.10 | 15.94 |
September | 0.253250E+10 | 7092.62 | 10-SEP-07:43 | 14.03 | 12.57 | 0.252563E+09 | 347.88 | 11-SEP-09:00 | 18.90 | 14.30 |
October | 0.142812E+10 | 4135.43 | 04-OCT-08:30 | 14.75 | 10.13 | 0.249749E+09 | 347.88 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.711579E+09 | 987.59 | 02-NOV-10:30 | 12.25 | 10.40 | 0.217303E+09 | 341.00 | 02-NOV-09:00 | 12.25 | 10.40 |
December | 0.370743E+09 | 751.10 | 05-DEC-10:30 | 7.50 | 5.28 | 0.194528E+09 | 314.11 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.218639E+11 | 0.288980E+10 | ||||||||
Minimum of Months | 0.234655E+09 | 715.65 | -0.6 | -0.6 | 0.190124E+09 | 282.91 | 5.60 | 3.25 | ||
Maximum of Months | 0.412904E+10 | 11483.94 | 22.10 | 16.37 | 0.287574E+09 | 348.19 | 26.10 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244505E+09 | 2013.26 | 20-JAN-13:30 | 6.70 | 4.72 | 0.301453E+09 | 549.50 | 20-JAN-14:09 | 6.78 | 4.76 |
February | 0.702261E+09 | 5411.93 | 27-FEB-15:00 | 20.00 | 12.17 | 0.297062E+09 | 549.51 | 07-FEB-14:09 | 20.00 | 12.17 |
March | 0.155355E+10 | 7540.01 | 02-MAR-13:07 | 12.38 | 7.47 | 0.375730E+09 | 549.51 | 24-MAR-13:20 | 8.67 | 2.76 |
April | 0.213805E+10 | 9334.72 | 27-APR-13:40 | 26.10 | 16.65 | 0.357873E+09 | 549.51 | 27-APR-13:20 | 26.10 | 16.65 |
May | 0.273051E+10 | 8674.11 | 14-MAY-13:32 | 22.60 | 12.25 | 0.405706E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.320560E+10 | 7193.27 | 28-JUN-13:30 | 24.70 | 15.69 | 0.417576E+09 | 549.52 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.461701E+10 | 10999.94 | 31-JUL-16:10 | 28.80 | 19.11 | 0.397243E+09 | 549.58 | 31-JUL-13:00 | 28.80 | 19.11 |
August | 0.601095E+10 | 16934.41 | 13-AUG-12:52 | 26.50 | 18.40 | 0.446778E+09 | 549.93 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.443990E+10 | 16269.06 | 10-SEP-15:43 | 22.30 | 14.46 | 0.386205E+09 | 549.95 | 15-SEP-13:00 | 21.70 | 16.45 |
October | 0.268078E+10 | 11342.32 | 04-OCT-13:30 | 20.85 | 11.31 | 0.377715E+09 | 549.68 | 03-OCT-13:00 | 20.85 | 11.31 |
November | 0.920057E+09 | 6973.80 | 04-NOV-13:40 | 20.93 | 15.98 | 0.325014E+09 | 549.50 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.503246E+09 | 4236.03 | 05-DEC-12:00 | 10.00 | 6.07 | 0.303068E+09 | 549.50 | 06-DEC-14:09 | 5.08 | 4.26 |
Annual Sum or Average | 0.297464E+11 | 0.439142E+10 | ||||||||
Minimum of Months | 0.244505E+09 | 2013.26 | 6.70 | 4.72 | 0.297062E+09 | 549.50 | 5.08 | 2.76 | ||
Maximum of Months | 0.601095E+10 | 16934.41 | 28.80 | 19.11 | 0.446778E+09 | 549.95 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226325E+09 | 738.68 | 20-JAN-15:50 | 5.87 | 4.23 | 0.196749E+09 | 301.99 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.476011E+09 | 2308.01 | 27-FEB-15:40 | 19.60 | 12.34 | 0.189097E+09 | 347.83 | 27-FEB-14:39 | 19.60 | 12.34 |
March | 0.103859E+10 | 3128.21 | 02-MAR-16:30 | 13.05 | 8.47 | 0.245107E+09 | 347.84 | 02-MAR-14:20 | 13.05 | 8.47 |
April | 0.154521E+10 | 5938.90 | 26-APR-17:30 | 23.60 | 13.73 | 0.236794E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.248535E+10 | 12791.22 | 07-MAY-17:21 | 21.40 | 16.06 | 0.271231E+09 | 347.85 | 05-MAY-09:20 | 21.40 | 16.06 |
June | 0.296579E+10 | 7562.62 | 25-JUN-18:03 | 21.42 | 13.27 | 0.274127E+09 | 347.85 | 28-JUN-13:00 | 25.00 | 15.65 |
July | 0.407406E+10 | 12691.24 | 23-JUL-18:01 | 25.82 | 15.89 | 0.256451E+09 | 347.85 | 03-JUL-09:20 | 25.82 | 15.89 |
August | 0.402960E+10 | 12968.28 | 06-AUG-18:32 | 22.47 | 15.07 | 0.287431E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.262614E+10 | 11671.08 | 10-SEP-17:42 | 20.87 | 13.88 | 0.252429E+09 | 347.86 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.140478E+10 | 5937.01 | 04-OCT-16:00 | 21.10 | 11.40 | 0.245984E+09 | 347.85 | 05-OCT-09:20 | 12.43 | 7.97 |
November | 0.710401E+09 | 2394.64 | 04-NOV-15:30 | 20.55 | 15.94 | 0.215239E+09 | 347.83 | 10-NOV-14:00 | 10.00 | 6.84 |
December | 0.357375E+09 | 849.93 | 05-DEC-15:40 | 7.40 | 5.40 | 0.194570E+09 | 334.84 | 05-DEC-15:39 | 7.40 | 5.40 |
Annual Sum or Average | 0.219396E+11 | 0.286521E+10 | ||||||||
Minimum of Months | 0.226325E+09 | 738.68 | 5.87 | 4.23 | 0.189097E+09 | 301.99 | 5.60 | 4.08 | ||
Maximum of Months | 0.407406E+10 | 12968.28 | 25.82 | 16.06 | 0.287431E+09 | 347.88 | 25.82 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373177E+09 | 1067.15 | 11-JAN-16:20 | 13.67 | 10.10 | 0.309669E+09 | 457.61 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.739529E+09 | 1320.56 | 28-FEB-15:00 | 13.90 | 10.81 | 0.295326E+09 | 534.87 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.152025E+10 | 1452.75 | 10-MAR-14:30 | 16.40 | 11.76 | 0.391619E+09 | 549.46 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.193473E+10 | 4132.24 | 27-APR-15:20 | 27.20 | 17.16 | 0.377437E+09 | 549.50 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.298965E+10 | 4456.88 | 15-MAY-14:30 | 23.30 | 13.06 | 0.428560E+09 | 549.50 | 05-MAY-09:20 | 23.30 | 13.06 |
June | 0.364064E+10 | 4787.17 | 21-JUN-15:30 | 24.70 | 15.68 | 0.433094E+09 | 549.50 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.410302E+10 | 7053.20 | 24-JUL-06:03 | 17.48 | 14.11 | 0.403781E+09 | 550.33 | 24-JUL-13:20 | 28.67 | 18.27 |
August | 0.422237E+10 | 6803.41 | 14-AUG-06:02 | 15.47 | 13.75 | 0.452852E+09 | 549.53 | 09-AUG-09:00 | 15.47 | 13.75 |
September | 0.264459E+10 | 4117.97 | 12-SEP-14:40 | 24.40 | 16.65 | 0.395245E+09 | 549.50 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.170521E+10 | 2762.54 | 04-OCT-15:20 | 21.50 | 11.47 | 0.381489E+09 | 549.49 | 12-OCT-13:20 | 14.27 | 10.74 |
November | 0.994173E+09 | 1281.79 | 02-NOV-14:10 | 14.22 | 11.35 | 0.333171E+09 | 521.76 | 02-NOV-13:00 | 14.22 | 11.35 |
December | 0.491309E+09 | 1023.22 | 05-DEC-15:20 | 8.70 | 6.23 | 0.302084E+09 | 447.63 | 05-DEC-14:00 | 8.70 | 6.23 |
Annual Sum or Average | 0.253587E+11 | 0.450433E+10 | ||||||||
Minimum of Months | 0.373177E+09 | 1023.22 | 8.70 | 6.23 | 0.295326E+09 | 447.63 | 8.70 | 6.23 | ||
Maximum of Months | 0.422237E+10 | 7053.20 | 27.20 | 17.16 | 0.452852E+09 | 550.33 | 28.67 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219705E+09 | 738.53 | 06-JAN-09:30 | -1.7 | -1.7 | 0.145803E+09 | 303.68 | 20-JAN-11:09 | 5.60 | 3.32 |
February | 0.431128E+09 | 2271.91 | 27-FEB-15:05 | 19.90 | 12.22 | 0.144549E+09 | 356.46 | 08-FEB-11:09 | 19.90 | 12.22 |
March | 0.106983E+10 | 5759.01 | 01-MAR-13:01 | 10.78 | 5.75 | 0.192533E+09 | 356.46 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.195233E+10 | 7483.17 | 27-APR-10:05 | 19.27 | 13.13 | 0.182801E+09 | 356.46 | 20-APR-10:09 | 19.27 | 13.13 |
May | 0.276022E+10 | 12054.46 | 14-MAY-07:53 | 14.40 | 10.27 | 0.201948E+09 | 356.47 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.365696E+10 | 11247.59 | 25-JUN-10:23 | 18.60 | 13.07 | 0.203691E+09 | 356.46 | 07-JUN-10:09 | 18.60 | 13.07 |
July | 0.389908E+10 | 13326.73 | 30-JUL-08:42 | 20.22 | 15.61 | 0.190478E+09 | 356.46 | 07-JUL-12:09 | 20.22 | 15.61 |
August | 0.423932E+10 | 14452.68 | 13-AUG-08:12 | 19.97 | 15.36 | 0.212862E+09 | 356.51 | 09-AUG-10:09 | 19.97 | 15.36 |
September | 0.259719E+10 | 11613.30 | 10-SEP-10:13 | 17.77 | 13.72 | 0.186735E+09 | 356.46 | 11-SEP-10:09 | 19.08 | 14.37 |
October | 0.135465E+10 | 6024.50 | 04-OCT-10:05 | 17.48 | 10.97 | 0.183450E+09 | 356.46 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.535119E+09 | 4219.32 | 02-NOV-12:02 | 13.48 | 11.00 | 0.159792E+09 | 356.45 | 02-NOV-10:09 | 13.48 | 11.00 |
December | 0.282486E+09 | 805.02 | 05-DEC-11:10 | 8.58 | 5.53 | 0.144258E+09 | 329.74 | 05-DEC-11:09 | 8.58 | 5.53 |
Annual Sum or Average | 0.229980E+11 | 0.214890E+10 | ||||||||
Minimum of Months | 0.219705E+09 | 738.53 | -1.7 | -1.7 | 0.144258E+09 | 303.68 | 5.60 | 3.32 | ||
Maximum of Months | 0.423932E+10 | 14452.68 | 20.22 | 15.61 | 0.212862E+09 | 356.51 | 20.22 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.846543E+09 | 7326.19 | 20-JAN-13:12 | 6.70 | 4.72 | 0.332465E+09 | 549.49 | 20-JAN-14:39 | 7.03 | 4.87 |
February | 0.174087E+10 | 9148.82 | 27-FEB-14:10 | 18.58 | 11.55 | 0.325431E+09 | 549.50 | 08-FEB-10:09 | 18.58 | 11.55 |
March | 0.324581E+10 | 10560.37 | 01-MAR-13:30 | 11.15 | 5.98 | 0.416963E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.57 |
April | 0.388847E+10 | 11676.62 | 02-APR-13:13 | 18.90 | 11.02 | 0.387657E+09 | 550.62 | 27-APR-13:20 | 26.10 | 16.46 |
May | 0.466599E+10 | 18230.10 | 14-MAY-13:13 | 22.40 | 12.22 | 0.429928E+09 | 549.51 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.497869E+10 | 14409.13 | 11-JUN-13:13 | 21.87 | 15.28 | 0.433081E+09 | 549.52 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.601439E+10 | 15934.47 | 23-JUL-14:32 | 27.40 | 16.28 | 0.404199E+09 | 550.84 | 31-JUL-13:20 | 27.57 | 18.47 |
August | 0.693169E+10 | 19704.87 | 13-AUG-12:52 | 26.50 | 18.40 | 0.453557E+09 | 550.87 | 14-AUG-13:20 | 25.93 | 17.49 |
September | 0.577514E+10 | 18631.10 | 10-SEP-12:52 | 20.60 | 14.10 | 0.398642E+09 | 550.61 | 12-SEP-13:20 | 23.33 | 16.02 |
October | 0.392905E+10 | 13640.78 | 04-OCT-12:50 | 20.60 | 11.27 | 0.396964E+09 | 550.17 | 04-OCT-13:20 | 20.77 | 11.28 |
November | 0.162217E+10 | 9543.99 | 04-NOV-13:30 | 20.85 | 16.00 | 0.357788E+09 | 549.49 | 24-NOV-10:30 | 5.85 | 4.21 |
December | 0.121860E+10 | 7942.13 | 05-DEC-12:30 | 10.30 | 6.13 | 0.330550E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.448574E+11 | 0.466722E+10 | ||||||||
Minimum of Months | 0.846543E+09 | 7326.19 | 6.70 | 4.72 | 0.325431E+09 | 549.49 | 5.85 | 4.21 | ||
Maximum of Months | 0.693169E+10 | 19704.87 | 27.40 | 18.40 | 0.453557E+09 | 550.87 | 27.57 | 18.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285419E+09 | 819.91 | 20-JAN-15:50 | 5.87 | 4.23 | 0.199091E+09 | 325.29 | 20-JAN-15:00 | 5.60 | 4.08 |
February | 0.593231E+09 | 3741.77 | 27-FEB-15:30 | 19.70 | 12.30 | 0.193621E+09 | 347.84 | 03-FEB-14:00 | 19.70 | 12.30 |
March | 0.128617E+10 | 5250.05 | 14-MAR-16:00 | 17.20 | 10.94 | 0.252797E+09 | 347.84 | 02-MAR-14:20 | 17.20 | 10.94 |
April | 0.199637E+10 | 8026.26 | 26-APR-16:00 | 24.40 | 14.49 | 0.240911E+09 | 347.85 | 28-APR-09:20 | 11.70 | 11.07 |
May | 0.309803E+10 | 15139.28 | 07-MAY-16:41 | 21.78 | 16.19 | 0.271800E+09 | 347.85 | 05-MAY-09:20 | 21.78 | 16.19 |
June | 0.348472E+10 | 14535.62 | 18-JUN-16:52 | 17.20 | 12.22 | 0.274201E+09 | 347.86 | 28-JUN-13:50 | 24.90 | 15.66 |
July | 0.451078E+10 | 14296.98 | 30-JUL-18:01 | 26.32 | 17.50 | 0.256059E+09 | 347.86 | 31-JUL-09:20 | 22.57 | 17.16 |
August | 0.435580E+10 | 14672.82 | 06-AUG-18:22 | 22.80 | 15.13 | 0.287058E+09 | 347.88 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.287762E+10 | 13348.76 | 10-SEP-16:12 | 22.20 | 14.38 | 0.251345E+09 | 347.85 | 22-SEP-09:20 | 14.83 | 14.31 |
October | 0.149070E+10 | 6687.43 | 04-OCT-16:00 | 21.10 | 11.40 | 0.244086E+09 | 347.85 | 04-OCT-09:20 | 21.10 | 11.40 |
November | 0.681796E+09 | 2970.17 | 04-NOV-15:30 | 20.55 | 15.94 | 0.214154E+09 | 347.84 | 08-NOV-14:00 | 9.40 | 8.82 |
December | 0.370134E+09 | 1321.47 | 05-DEC-15:30 | 8.05 | 5.82 | 0.195977E+09 | 347.72 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.250308E+11 | 0.288110E+10 | ||||||||
Minimum of Months | 0.285419E+09 | 819.91 | 5.87 | 4.23 | 0.193621E+09 | 325.29 | 5.60 | 4.08 | ||
Maximum of Months | 0.451078E+10 | 15139.28 | 26.32 | 17.50 | 0.287058E+09 | 347.88 | 24.90 | 17.16 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89024118.18 | 5569.78 | 02-JAN-06:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 89024118.18 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 89024118.18 | 5569.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312853E+10 | 10981.20 | 09-JAN-06:09 | -1.5 |
February | 0.188361E+10 | 11226.24 | 21-FEB-06:10 | 1.70 |
March | 0.120938E+10 | 6561.20 | 06-MAR-07:04 | 6.70 |
April | 0.682776E+09 | 4056.23 | 19-APR-06:02 | 2.48 |
May | 0.432784E+09 | 3231.34 | 11-MAY-05:03 | 5.10 |
June | 0.260482E+09 | 3129.49 | 25-JUN-08:62 | 15.78 |
July | 0.195757E+09 | 3654.40 | 30-JUL-07:52 | 18.30 |
August | 0.230271E+09 | 3580.32 | 06-AUG-08:62 | 14.38 |
September | 0.435600E+09 | 3991.95 | 10-SEP-08:62 | 14.68 |
October | 0.888954E+09 | 3955.14 | 16-OCT-06:03 | 6.60 |
November | 0.170076E+10 | 9486.92 | 24-NOV-07:06 | 1.20 |
December | 0.269121E+10 | 10700.37 | 18-DEC-06:18 | 3.53 |
Annual Sum or Average | 0.137401E+11 | |||
Minimum of Months | 0.195757E+09 | 3129.49 | -1.5 | |
Maximum of Months | 0.312853E+10 | 11226.24 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.176611E+10 | 8632.56 | 02-JAN-08:40 | 6.70 |
February | 0.111841E+10 | 6004.15 | 21-FEB-07:12 | 1.50 |
March | 0.796745E+09 | 2503.35 | 14-MAR-10:05 | 10.28 |
April | 0.311416E+09 | 3441.63 | 02-APR-13:13 | 18.90 |
May | 66156481.50 | 3973.31 | 29-MAY-17:02 | 16.60 |
June | 23590341.64 | 2778.20 | 25-JUN-15:43 | 21.70 |
July | 30710213.11 | 3930.82 | 23-JUL-14:32 | 27.40 |
August | 23202226.09 | 4386.81 | 13-AUG-10:12 | 23.43 |
September | 60826268.90 | 5088.91 | 10-SEP-10:13 | 17.77 |
October | 0.429381E+09 | 4456.55 | 29-OCT-12:53 | 11.10 |
November | 0.978700E+09 | 2652.34 | 24-NOV-11:10 | 6.20 |
December | 0.140393E+10 | 6444.94 | 26-DEC-07:20 | -1.5 |
Annual Sum or Average | 0.700918E+10 | |||
Minimum of Months | 23202226.09 | 2503.35 | -1.5 | |
Maximum of Months | 0.176611E+10 | 8632.56 | 27.40 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152033E+10 | 7118.78 | 02-JAN-08:10 | 6.70 |
February | 0.820996E+09 | 2657.63 | 16-FEB-08:18 | 2.60 |
March | 0.330966E+09 | 2647.41 | 06-MAR-08:08 | 6.78 |
April | 68363755.79 | 1845.54 | 29-APR-05:13 | 8.50 |
May | 28082307.06 | 2962.01 | 01-MAY-05:12 | 12.20 |
June | 30811069.81 | 2571.56 | 19-JUN-05:12 | 11.30 |
July | 34533686.69 | 2506.42 | 05-JUL-05:12 | 11.87 |
August | 24819731.00 | 2821.16 | 13-AUG-14:52 | 28.10 |
September | 31896404.67 | 2972.15 | 10-SEP-15:43 | 22.30 |
October | 0.133307E+09 | 3151.77 | 10-OCT-05:12 | 12.20 |
November | 0.653768E+09 | 2905.00 | 24-NOV-08:18 | 2.23 |
December | 0.113649E+10 | 2711.95 | 05-DEC-08:06 | 4.08 |
Annual Sum or Average | 0.481436E+10 | |||
Minimum of Months | 24819731.00 | 1845.54 | 2.23 | |
Maximum of Months | 0.152033E+10 | 7118.78 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444015E+09 | 13223.89 | 02-JAN-06:11 | 6.10 |
February | 29810201.34 | 9716.34 | 21-FEB-06:01 | 1.70 |
March | 774356.59 | 6452.97 | 06-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 4012767.18 | 8758.54 | 27-NOV-07:03 | 11.70 |
December | 63570787.87 | 10271.18 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.542184E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.444015E+09 | 13223.89 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133711E+10 | 20223.67 | 02-JAN-06:11 | 6.10 |
February | 0.429307E+09 | 18419.00 | 21-FEB-06:01 | 1.70 |
March | 49994411.75 | 15815.39 | 06-MAR-06:11 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 6380443.40 | 14047.34 | 23-OCT-06:03 | 10.40 |
November | 0.225630E+09 | 16492.87 | 27-NOV-06:11 | 11.70 |
December | 0.716556E+09 | 19193.77 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.276498E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.133711E+10 | 20223.67 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223936E+10 | 7314.55 | 17-JAN-05:01 | 1.60 |
February | 0.107138E+10 | 7237.51 | 21-FEB-06:01 | 1.70 |
March | 0.250083E+09 | 6560.47 | 06-MAR-06:11 | 6.70 |
April | 50234126.77 | 5737.78 | 18-APR-05:13 | 3.30 |
May | 1287593.12 | 5378.81 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 905290.89 | 2283.92 | 27-SEP-06:03 | 8.40 |
October | 70528608.11 | 5844.87 | 30-OCT-05:12 | 7.20 |
November | 0.706350E+09 | 6790.98 | 24-NOV-06:11 | 1.83 |
December | 0.170631E+10 | 7319.33 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.609644E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.223936E+10 | 7319.33 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135507E+10 | 6712.82 | 17-JAN-05:01 | 1.60 |
February | 0.598684E+09 | 6617.23 | 21-FEB-06:01 | 1.70 |
March | 0.122188E+09 | 5774.47 | 06-MAR-06:11 | 6.70 |
April | 20925737.17 | 4489.11 | 18-APR-06:02 | 3.40 |
May | 1045893.18 | 4025.77 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 615419.02 | 1552.88 | 28-SEP-06:03 | 8.40 |
October | 44663998.32 | 4785.74 | 16-OCT-05:12 | 7.03 |
November | 0.425476E+09 | 6084.56 | 24-NOV-06:11 | 1.83 |
December | 0.103787E+10 | 6721.01 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.360653E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.135507E+10 | 6721.01 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167762E+10 | 10110.33 | 17-JAN-05:01 | 1.60 |
February | 0.710466E+09 | 9917.98 | 21-FEB-06:01 | 1.70 |
March | 0.181423E+09 | 8669.01 | 06-MAR-06:11 | 6.70 |
April | 43103245.28 | 6814.36 | 18-APR-06:02 | 3.40 |
May | 1582397.83 | 6035.78 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 651228.99 | 1752.72 | 27-SEP-06:03 | 8.40 |
October | 50759906.39 | 6957.54 | 16-OCT-05:12 | 7.03 |
November | 0.521403E+09 | 9090.40 | 24-NOV-06:11 | 1.83 |
December | 0.130519E+10 | 10117.77 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.449221E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.167762E+10 | 10117.77 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140529E+10 | 6957.73 | 17-JAN-05:01 | 1.60 |
February | 0.637951E+09 | 6840.83 | 21-FEB-06:01 | 1.70 |
March | 0.157814E+09 | 5942.24 | 06-MAR-06:11 | 6.70 |
April | 33565770.65 | 4530.98 | 18-APR-06:02 | 3.40 |
May | 1139908.71 | 4136.37 | 18-MAY-06:03 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 409338.42 | 1149.99 | 28-SEP-06:03 | 8.40 |
October | 45803468.49 | 4805.46 | 16-OCT-05:12 | 7.03 |
November | 0.452409E+09 | 6258.20 | 24-NOV-06:11 | 1.83 |
December | 0.107708E+10 | 6968.28 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.381147E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.140529E+10 | 6968.28 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124630E+10 | 5539.48 | 02-JAN-06:11 | 6.10 |
February | 0.404970E+09 | 5000.31 | 21-FEB-06:01 | 1.70 |
March | 44847483.93 | 4460.99 | 06-MAR-06:11 | 6.70 |
April | 4134015.26 | 4199.80 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 659395.29 | 2628.70 | 30-OCT-06:03 | 7.20 |
November | 74358304.02 | 4463.75 | 24-NOV-06:11 | 1.83 |
December | 0.484009E+09 | 4975.37 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.225928E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.124630E+10 | 5539.48 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758122E+09 | 5125.00 | 02-JAN-06:11 | 6.10 |
February | 0.191509E+09 | 4326.00 | 21-FEB-06:01 | 1.70 |
March | 15058719.39 | 3665.23 | 06-MAR-06:11 | 6.70 |
April | 1157283.56 | 3328.43 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 59309.55 | 395.40 | 31-OCT-06:03 | 10.18 |
November | 45508306.72 | 3728.52 | 24-NOV-06:11 | 1.83 |
December | 0.317763E+09 | 4396.19 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.132918E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.758122E+09 | 5125.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298390E+10 | 7951.60 | 17-JAN-08:00 | 1.70 |
February | 0.160731E+10 | 7668.55 | 17-FEB-07:10 | 1.20 |
March | 0.108879E+10 | 7099.13 | 01-MAR-07:10 | -0.1 |
April | 0.616442E+09 | 6818.05 | 19-APR-06:10 | 2.48 |
May | 0.397748E+09 | 6083.12 | 18-MAY-06:10 | 5.68 |
June | 0.187880E+09 | 5100.23 | 15-JUN-06:20 | 9.80 |
July | 25444458.84 | 4682.07 | 03-JUL-06:07 | 11.88 |
August | 45241274.96 | 4853.23 | 03-AUG-06:06 | 11.82 |
September | 0.171187E+09 | 5444.39 | 28-SEP-06:10 | 8.40 |
October | 0.565550E+09 | 5901.08 | 16-OCT-07:00 | 6.10 |
November | 0.140386E+10 | 7596.89 | 24-NOV-07:10 | 1.20 |
December | 0.221052E+10 | 8149.57 | 26-DEC-07:40 | -1.3 |
Annual Sum or Average | 0.113039E+11 | |||
Minimum of Months | 25444458.84 | 4682.07 | -1.3 | |
Maximum of Months | 0.298390E+10 | 8149.57 | 11.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.762978E+09 | 5310.39 | 02-JAN-06:11 | 6.10 |
February | 0.197855E+09 | 4384.74 | 21-FEB-06:01 | 1.70 |
March | 19667416.02 | 3743.73 | 06-MAR-06:11 | 6.70 |
April | 1774297.11 | 3351.23 | 19-APR-06:02 | 2.48 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 47089011.51 | 3760.66 | 24-NOV-06:11 | 1.83 |
December | 0.304595E+09 | 4507.61 | 26-DEC-06:01 | -0.8 |
Annual Sum or Average | 0.133396E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.8 | |
Maximum of Months | 0.762978E+09 | 5310.39 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104560E+10 | 5952.65 | 02-JAN-06:11 | 6.10 |
February | 0.316163E+09 | 5331.48 | 21-FEB-06:01 | 1.70 |
March | 30412297.06 | 4844.31 | 06-MAR-06:11 | 6.70 |
April | 1992197.89 | 4434.70 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 3598840.73 | 4408.29 | 30-OCT-06:03 | 7.20 |
November | 0.147477E+09 | 5021.57 | 24-NOV-06:11 | 1.83 |
December | 0.561627E+09 | 5689.24 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.210687E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.104560E+10 | 5952.65 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.640802E+09 | 5638.12 | 02-JAN-06:11 | 6.10 |
February | 0.182217E+09 | 4760.58 | 21-FEB-06:01 | 1.70 |
March | 15185628.31 | 4076.60 | 06-MAR-06:11 | 6.70 |
April | 922529.78 | 3448.49 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2568224.15 | 3305.12 | 30-OCT-06:03 | 7.20 |
November | 94709665.46 | 4353.91 | 24-NOV-06:11 | 1.83 |
December | 0.370474E+09 | 5307.15 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.130688E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.640802E+09 | 5638.12 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.744161E+09 | 8251.55 | 02-JAN-06:11 | 6.10 |
February | 0.206053E+09 | 7018.71 | 21-FEB-06:01 | 1.70 |
March | 19822552.34 | 6002.87 | 06-MAR-06:11 | 6.70 |
April | 1618446.21 | 5161.38 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 1476922.82 | 3453.76 | 16-OCT-06:03 | 6.60 |
November | 0.100413E+09 | 6344.89 | 24-NOV-06:11 | 1.83 |
December | 0.439480E+09 | 7611.13 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.151302E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.744161E+09 | 8251.55 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649867E+09 | 5659.56 | 02-JAN-06:11 | 6.10 |
February | 0.190417E+09 | 4760.95 | 21-FEB-06:01 | 1.70 |
March | 19468259.44 | 4075.14 | 06-MAR-06:11 | 6.70 |
April | 1625772.51 | 3439.13 | 18-APR-06:02 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 2027643.32 | 2723.31 | 16-OCT-06:03 | 6.60 |
November | 98138525.24 | 4333.24 | 24-NOV-06:11 | 1.83 |
December | 0.364302E+09 | 5314.08 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.132585E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.649867E+09 | 5659.56 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.679453E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.554537E+09 | 945.17 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.605089E+09 | 830.87 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511857E+09 | 667.05 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.538145E+09 | 541.21 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526145E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494536E+09 | 579.72 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558699E+09 | 574.20 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.528768E+09 | 837.22 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.592366E+09 | 1027.50 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.655754E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.681304E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.692665E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494536E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.681304E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416641E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346117E+09 | 604.68 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380850E+09 | 502.99 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324117E+09 | 354.45 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342443E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335286E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315061E+09 | 339.83 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355534E+09 | 353.24 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332304E+09 | 508.51 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369493E+09 | 648.37 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.405418E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415515E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433878E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315061E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416641E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642314E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534339E+09 | 922.83 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597697E+09 | 821.38 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512097E+09 | 583.86 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540637E+09 | 542.27 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529261E+09 | 530.72 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.499149E+09 | 574.59 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.562266E+09 | 572.97 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525585E+09 | 830.09 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.576811E+09 | 1025.02 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.626358E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.637362E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.678387E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.499149E+09 | 530.72 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.642314E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416537E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342850E+09 | 582.59 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380693E+09 | 534.11 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324033E+09 | 454.12 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341100E+09 | 352.78 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333466E+09 | 346.71 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314874E+09 | 468.46 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354428E+09 | 462.90 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334504E+09 | 537.17 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369899E+09 | 650.62 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.403893E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415132E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433141E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314874E+09 | 346.71 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416537E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.675308E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.551908E+09 | 941.40 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.603183E+09 | 822.79 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511139E+09 | 583.20 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.537733E+09 | 536.46 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.525872E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494165E+09 | 576.91 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558123E+09 | 571.03 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.527671E+09 | 829.44 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.589639E+09 | 1027.00 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.652193E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.677239E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.690417E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494165E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.677239E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415134E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.345084E+09 | 602.99 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380122E+09 | 497.81 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323766E+09 | 352.14 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342135E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335012E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314770E+09 | 336.35 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355113E+09 | 350.85 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331724E+09 | 503.55 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.368473E+09 | 648.02 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.404154E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.413878E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.432936E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314770E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415134E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.639961E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.533044E+09 | 917.32 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.596618E+09 | 812.84 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.511517E+09 | 581.12 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540106E+09 | 537.57 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.528748E+09 | 525.50 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.498606E+09 | 571.49 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.561629E+09 | 569.72 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524892E+09 | 821.97 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.575517E+09 | 1024.40 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.624566E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.635200E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.677040E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.498606E+09 | 525.50 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.639961E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414945E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.341758E+09 | 580.25 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379854E+09 | 530.30 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323551E+09 | 447.91 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.340819E+09 | 350.54 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333103E+09 | 344.24 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314379E+09 | 462.96 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354011E+09 | 457.02 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333740E+09 | 533.46 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.368822E+09 | 650.37 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.402363E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.413301E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.432064E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314379E+09 | 344.24 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414945E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.679449E+09 | 1040.56 | 02-JAN-16:30 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.554534E+09 | 945.17 | 02-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.605087E+09 | 830.85 | 22-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.511856E+09 | 667.02 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.538145E+09 | 541.20 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.526145E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494536E+09 | 579.71 | 12-JUL-08:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.558698E+09 | 574.19 | 02-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.528767E+09 | 837.21 | 25-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.592363E+09 | 1027.50 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.655749E+09 | 1040.56 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.681299E+09 | 1040.56 | 01-DEC-16:19 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.692663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494536E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.681299E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416639E+09 | 658.76 | 02-JAN-16:30 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.346115E+09 | 604.67 | 02-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380849E+09 | 502.98 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324116E+09 | 354.45 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.342443E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.335285E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.315061E+09 | 339.83 | 12-JUL-08:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.355534E+09 | 353.24 | 02-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332303E+09 | 508.50 | 25-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369492E+09 | 648.37 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.405416E+09 | 658.76 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415513E+09 | 658.76 | 01-DEC-16:19 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433877E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.315061E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416639E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.642312E+09 | 1040.56 | 02-JAN-16:30 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.534338E+09 | 922.82 | 02-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.597695E+09 | 821.36 | 22-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.512096E+09 | 583.85 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.540636E+09 | 542.25 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.529261E+09 | 530.71 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.499148E+09 | 574.59 | 12-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.562266E+09 | 572.96 | 02-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.525584E+09 | 830.07 | 25-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.576809E+09 | 1025.02 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.626356E+09 | 1040.56 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.637360E+09 | 1040.56 | 01-DEC-16:19 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.678386E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.499148E+09 | 530.71 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.642312E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.416535E+09 | 658.71 | 02-JAN-16:30 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.342848E+09 | 582.59 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380692E+09 | 534.10 | 22-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324032E+09 | 454.11 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.341100E+09 | 352.77 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.333465E+09 | 346.70 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314873E+09 | 468.44 | 12-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.354427E+09 | 462.89 | 28-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334503E+09 | 537.16 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.369898E+09 | 650.62 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.403861E+09 | 658.71 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.415130E+09 | 658.71 | 01-DEC-16:19 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.433136E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314873E+09 | 346.70 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.416535E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.679453E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367904E+09 |
February | 0.901968E+09 | 0.554537E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332157E+09 |
March | 0.107774E+10 | 0.605089E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332177E+09 |
April | 0.956342E+09 | 0.511857E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736373.57 | 0.326997E+09 |
May | 0.103597E+10 | 0.538145E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19006.54 | 0.266268E+09 |
June | 0.103308E+10 | 0.526145E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210034.55 | 0.223621E+09 |
July | 0.959235E+09 | 0.494536E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2684230.16 | 0.188067E+09 |
August | 0.107774E+10 | 0.558699E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4736719.88 | 0.152281E+09 |
September | 0.956342E+09 | 0.528768E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19426.29 | 0.121904E+09 |
October | 0.994195E+09 | 0.592366E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266162E+09 |
November | 0.984487E+09 | 0.655754E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290848E+09 |
December | 0.959235E+09 | 0.681304E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313549E+09 |
Annual Sum or Average | 0.119305E+11 | 0.692665E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8405790.98 | 0.318193E+10 |
Minimum of Months | 0.901968E+09 | 0.494536E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121904E+09 |
Maximum of Months | 0.107774E+10 | 0.681304E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4736719.88 | 0.367904E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.416641E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245279E+09 |
February | 0.571020E+09 | 0.346117E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225147E+09 |
March | 0.682301E+09 | 0.380850E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225317E+09 |
April | 0.605444E+09 | 0.324117E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387416.54 | 0.223285E+09 |
May | 0.655854E+09 | 0.342443E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12672.58 | 0.181270E+09 |
June | 0.654023E+09 | 0.335286E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140027.20 | 0.152963E+09 |
July | 0.607275E+09 | 0.315061E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1282126.32 | 0.128197E+09 |
August | 0.682301E+09 | 0.355534E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2984934.78 | 0.104401E+09 |
September | 0.605444E+09 | 0.332304E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951.80 | 83217236.06 |
October | 0.629407E+09 | 0.369493E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180962E+09 |
November | 0.623262E+09 | 0.405418E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194416E+09 |
December | 0.607275E+09 | 0.415515E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209304E+09 |
Annual Sum or Average | 0.755301E+10 | 0.433878E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4820129.21 | 0.215376E+10 |
Minimum of Months | 0.571020E+09 | 0.315061E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83217236.06 |
Maximum of Months | 0.682301E+09 | 0.416641E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2984934.78 | 0.245279E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642314E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378470E+09 |
February | 0.901968E+09 | 0.534339E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356000E+09 |
March | 0.107774E+10 | 0.597697E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348508E+09 |
April | 0.956342E+09 | 0.512097E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430801.30 | 0.340402E+09 |
May | 0.103597E+10 | 0.540637E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19002.71 | 0.273707E+09 |
June | 0.103308E+10 | 0.529261E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 210020.04 | 0.228411E+09 |
July | 0.959235E+09 | 0.499149E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1870376.86 | 0.193435E+09 |
August | 0.107774E+10 | 0.562266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4444920.68 | 0.158176E+09 |
September | 0.956342E+09 | 0.525585E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19380.29 | 0.128885E+09 |
October | 0.994195E+09 | 0.576811E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284232E+09 |
November | 0.984487E+09 | 0.626358E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300956E+09 |
December | 0.959235E+09 | 0.637362E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325073E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678387E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6994501.89 | 0.331625E+10 |
Minimum of Months | 0.901968E+09 | 0.499149E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128885E+09 |
Maximum of Months | 0.107774E+10 | 0.642314E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4444920.68 | 0.378470E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.416537E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246088E+09 |
February | 0.570983E+09 | 0.342850E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226397E+09 |
March | 0.682256E+09 | 0.380693E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226702E+09 |
April | 0.605404E+09 | 0.324033E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 197502.17 | 0.224532E+09 |
May | 0.655811E+09 | 0.341100E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12672.91 | 0.184968E+09 |
June | 0.653980E+09 | 0.333466E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140021.92 | 0.153943E+09 |
July | 0.607235E+09 | 0.314874E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1260944.98 | 0.132459E+09 |
August | 0.682256E+09 | 0.354428E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2993913.96 | 0.106969E+09 |
September | 0.605404E+09 | 0.334504E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12951.60 | 85850034.32 |
October | 0.629366E+09 | 0.369899E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182550E+09 |
November | 0.623221E+09 | 0.403893E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195118E+09 |
December | 0.607235E+09 | 0.415132E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210158E+09 |
Annual Sum or Average | 0.755252E+10 | 0.433141E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4618007.54 | 0.217573E+10 |
Minimum of Months | 0.570983E+09 | 0.314874E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85850034.32 |
Maximum of Months | 0.682256E+09 | 0.416537E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2993913.96 | 0.246088E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.675308E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209017E+09 |
February | 0.901968E+09 | 0.551908E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189376E+09 |
March | 0.107774E+10 | 0.603183E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183635E+09 |
April | 0.956342E+09 | 0.511139E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 463650.73 | 0.176875E+09 |
May | 0.103597E+10 | 0.537733E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11815.83 | 0.142847E+09 |
June | 0.103308E+10 | 0.525872E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118677.43 | 0.119967E+09 |
July | 0.959235E+09 | 0.494165E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2069944.49 | 0.100974E+09 |
August | 0.107774E+10 | 0.558123E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2758697.84 | 82469579.00 |
September | 0.956342E+09 | 0.527671E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11771.71 | 67548302.79 |
October | 0.994195E+09 | 0.589639E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154367E+09 |
November | 0.984487E+09 | 0.652193E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171528E+09 |
December | 0.959235E+09 | 0.677239E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182771E+09 |
Annual Sum or Average | 0.119305E+11 | 0.690417E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5434558.04 | 0.178137E+10 |
Minimum of Months | 0.901968E+09 | 0.494165E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67548302.79 |
Maximum of Months | 0.107774E+10 | 0.677239E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2758697.84 | 0.209017E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.415134E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139381E+09 |
February | 0.571020E+09 | 0.345084E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128778E+09 |
March | 0.682301E+09 | 0.380122E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126523E+09 |
April | 0.605444E+09 | 0.323766E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 223547.87 | 0.123885E+09 |
May | 0.655854E+09 | 0.342135E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.06 | 99220342.68 |
June | 0.654023E+09 | 0.335012E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79117.91 | 84204669.05 |
July | 0.607275E+09 | 0.314770E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 774778.79 | 70206034.93 |
August | 0.682301E+09 | 0.355113E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1624936.36 | 58188570.33 |
September | 0.605444E+09 | 0.331724E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.71 | 46946263.28 |
October | 0.629407E+09 | 0.368473E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106189E+09 |
November | 0.623262E+09 | 0.404154E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115143E+09 |
December | 0.607275E+09 | 0.413878E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122247E+09 |
Annual Sum or Average | 0.755301E+10 | 0.432936E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2718105.71 | 0.122091E+10 |
Minimum of Months | 0.571020E+09 | 0.314770E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46946263.28 |
Maximum of Months | 0.682301E+09 | 0.415134E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1624936.36 | 0.139381E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.639961E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397769E+10 |
February | 0.901968E+09 | 0.533044E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349309E+10 |
March | 0.107774E+10 | 0.596618E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371412E+10 |
April | 0.956342E+09 | 0.511517E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14199079.69 | 0.279850E+10 |
May | 0.103597E+10 | 0.540106E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1604613.35 | 0.247457E+10 |
June | 0.103308E+10 | 0.528748E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15758900.29 | 0.190031E+10 |
July | 0.959235E+09 | 0.498606E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93264204.14 | 0.122717E+10 |
August | 0.107774E+10 | 0.561629E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254742E+09 | 0.117810E+10 |
September | 0.956342E+09 | 0.524892E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3499200.74 | 0.178310E+10 |
October | 0.994195E+09 | 0.575517E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282922E+10 |
November | 0.984487E+09 | 0.624566E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351902E+10 |
December | 0.959235E+09 | 0.635200E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385442E+10 |
Annual Sum or Average | 0.119305E+11 | 0.677040E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383068E+09 | 0.327493E+11 |
Minimum of Months | 0.901968E+09 | 0.498606E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117810E+10 |
Maximum of Months | 0.107774E+10 | 0.639961E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254742E+09 | 0.397769E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.414945E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139803E+09 |
February | 0.570983E+09 | 0.341758E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129087E+09 |
March | 0.682256E+09 | 0.379854E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127033E+09 |
April | 0.605404E+09 | 0.323551E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122615.64 | 0.123942E+09 |
May | 0.655811E+09 | 0.340819E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7877.47 | 0.102273E+09 |
June | 0.653980E+09 | 0.333103E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79118.13 | 84598041.67 |
July | 0.607235E+09 | 0.314379E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 727189.26 | 74075068.18 |
August | 0.682256E+09 | 0.354011E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1622871.32 | 60086998.34 |
September | 0.605404E+09 | 0.333740E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7847.67 | 48818288.89 |
October | 0.629366E+09 | 0.368822E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107142E+09 |
November | 0.623221E+09 | 0.402363E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115447E+09 |
December | 0.607235E+09 | 0.413301E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122587E+09 |
Annual Sum or Average | 0.755252E+10 | 0.432064E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2567519.48 | 0.123489E+10 |
Minimum of Months | 0.570983E+09 | 0.314379E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48818288.89 |
Maximum of Months | 0.682256E+09 | 0.414945E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1622871.32 | 0.139803E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.679449E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325374E+09 |
February | 0.901968E+09 | 0.554534E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297369E+09 |
March | 0.107774E+10 | 0.605087E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296956E+09 |
April | 0.956342E+09 | 0.511856E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638055.95 | 0.288562E+09 |
May | 0.103597E+10 | 0.538145E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17144.62 | 0.231294E+09 |
June | 0.103308E+10 | 0.526145E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180270.54 | 0.192626E+09 |
July | 0.959235E+09 | 0.494536E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2668200.91 | 0.161825E+09 |
August | 0.107774E+10 | 0.558698E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042746.81 | 0.132028E+09 |
September | 0.956342E+09 | 0.528767E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17284.91 | 0.107378E+09 |
October | 0.994195E+09 | 0.592363E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240875E+09 |
November | 0.984487E+09 | 0.655749E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263466E+09 |
December | 0.959235E+09 | 0.681299E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281951E+09 |
Annual Sum or Average | 0.119305E+11 | 0.692663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7563703.74 | 0.281970E+10 |
Minimum of Months | 0.901968E+09 | 0.494536E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107378E+09 |
Maximum of Months | 0.107774E+10 | 0.681299E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042746.81 | 0.325374E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.416639E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216917E+09 |
February | 0.421807E+09 | 0.346115E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201866E+09 |
March | 0.502994E+09 | 0.380849E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201512E+09 |
April | 0.447140E+09 | 0.324116E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 333689.62 | 0.196789E+09 |
May | 0.484071E+09 | 0.342443E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10695.21 | 0.157377E+09 |
June | 0.482240E+09 | 0.335285E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115715.41 | 0.131768E+09 |
July | 0.448971E+09 | 0.315061E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124420.64 | 0.110412E+09 |
August | 0.502994E+09 | 0.355534E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2430529.76 | 90481860.80 |
September | 0.447140E+09 | 0.332303E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10966.45 | 73253137.74 |
October | 0.465148E+09 | 0.369492E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163578E+09 |
November | 0.460569E+09 | 0.405416E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176456E+09 |
December | 0.448971E+09 | 0.415513E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188446E+09 |
Annual Sum or Average | 0.557719E+10 | 0.433877E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4026017.10 | 0.190886E+10 |
Minimum of Months | 0.421807E+09 | 0.315061E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73253137.74 |
Maximum of Months | 0.502994E+09 | 0.416639E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2430529.76 | 0.216917E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.642312E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335295E+09 |
February | 0.901968E+09 | 0.534338E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317832E+09 |
March | 0.107774E+10 | 0.597695E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309808E+09 |
April | 0.956342E+09 | 0.512096E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387659.32 | 0.298890E+09 |
May | 0.103597E+10 | 0.540636E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17141.15 | 0.237333E+09 |
June | 0.103308E+10 | 0.529261E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180256.95 | 0.196780E+09 |
July | 0.959235E+09 | 0.499148E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1600260.34 | 0.166279E+09 |
August | 0.107774E+10 | 0.562266E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3738854.74 | 0.136858E+09 |
September | 0.956342E+09 | 0.525584E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17158.95 | 0.112772E+09 |
October | 0.994195E+09 | 0.576809E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254530E+09 |
November | 0.984487E+09 | 0.626356E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272140E+09 |
December | 0.959235E+09 | 0.637360E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292147E+09 |
Annual Sum or Average | 0.119305E+11 | 0.678386E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5941331.47 | 0.293066E+10 |
Minimum of Months | 0.901968E+09 | 0.499148E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112772E+09 |
Maximum of Months | 0.107774E+10 | 0.642312E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3738854.74 | 0.335295E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.416535E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217580E+09 |
February | 0.570983E+09 | 0.342848E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202323E+09 |
March | 0.682256E+09 | 0.380692E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202077E+09 |
April | 0.605404E+09 | 0.324032E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167243.89 | 0.197578E+09 |
May | 0.655811E+09 | 0.341100E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11428.76 | 0.160421E+09 |
June | 0.653980E+09 | 0.333465E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120181.14 | 0.132598E+09 |
July | 0.607235E+09 | 0.314873E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1103484.06 | 0.113931E+09 |
August | 0.682256E+09 | 0.354427E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513259.54 | 92601475.44 |
September | 0.605404E+09 | 0.334503E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11523.19 | 75174050.91 |
October | 0.629366E+09 | 0.369898E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164464E+09 |
November | 0.623221E+09 | 0.403861E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176573E+09 |
December | 0.607235E+09 | 0.415130E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188904E+09 |
Annual Sum or Average | 0.755252E+10 | 0.433136E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3927120.59 | 0.192422E+10 |
Minimum of Months | 0.570983E+09 | 0.314873E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75174050.91 |
Maximum of Months | 0.682256E+09 | 0.416535E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2513259.54 | 0.217580E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456532E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423831E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418054E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533200.48 | 0.398582E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1254.93 | 0.316610E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82666.11 | 0.262550E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2198073.72 | 0.221111E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3775212.68 | 0.182695E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.56 | 0.150278E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343416E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377285E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403240E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6590759.48 | 0.395418E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150278E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3775212.68 | 0.456532E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551445E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510835E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514331E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 861753.75 | 0.496996E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.30 | 0.399485E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106070.51 | 0.332718E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2954253.78 | 0.279170E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4955840.92 | 0.230331E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.02 | 0.187453E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416957E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450802E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482083E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8880024.28 | 0.485261E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187453E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4955840.92 | 0.551445E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548068E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509667E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512859E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366368.74 | 0.509607E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420120E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33099.33 | 0.352548E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1092989.26 | 0.298064E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3547907.65 | 0.238457E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191289E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413401E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439757E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470579E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5040364.98 | 0.490442E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191289E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3547907.65 | 0.548068E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 625.02 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 945.17 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 572.64 | 16-FEB-22:03 |
March | 1306.65 | 01-MAR-10:09 | 830.87 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 560.98 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 667.05 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 | 01-APR-17:03 | 604.40 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 541.21 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 447.31 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 595.14 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 579.72 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.84 | 23-JUL-13:53 | 298.01 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 574.20 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 08-AUG-17:00 | 420.71 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 837.22 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 280.61 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.50 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 529.77 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 593.28 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 479.93 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.61 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 | 625.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 414.09 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 604.68 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 381.42 | 16-FEB-22:03 |
March | 827.22 | 01-MAR-10:09 | 502.99 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 380.54 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 354.45 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 01-APR-17:03 | 408.46 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 298.05 | 22-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 395.40 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 339.83 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.41 | 23-JUL-15:36 | 202.14 | 02-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 353.24 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 08-AUG-17:00 | 281.21 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 508.51 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 186.68 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 648.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 352.74 | 31-OCT-21:05 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 393.32 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 318.51 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.68 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.71 | 414.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 627.00 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 922.83 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 614.65 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 821.38 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 586.05 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.86 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 | 01-APR-17:30 | 615.87 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 542.27 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 05-MAY-16:00 | 449.73 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 530.72 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 28-JUN-16:00 | 594.45 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 574.59 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 | 23-JUL-15:36 | 301.04 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 572.97 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 08-AUG-17:00 | 427.28 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 830.09 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 14-SEP-17:00 | 282.98 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1025.02 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 529.77 | 31-OCT-21:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 593.18 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 482.71 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 530.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.98 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 | 627.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 414.07 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 582.59 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 381.33 | 16-FEB-22:03 |
March | 827.17 | 01-MAR-10:09 | 534.11 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 379.39 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 454.12 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 01-APR-16:00 | 403.20 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 352.78 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 05-MAY-16:00 | 299.69 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 346.71 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 | 28-JUN-16:00 | 393.91 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 468.46 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 23-JUL-15:54 | 201.77 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 462.90 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 08-AUG-17:00 | 288.85 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 537.17 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 | 14-SEP-17:00 | 186.90 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.62 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 352.52 | 31-OCT-21:05 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 392.58 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 319.07 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 346.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.90 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 414.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 356.26 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 941.40 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 327.36 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 822.79 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 310.05 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.20 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 01-APR-17:03 | 327.86 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 536.46 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 05-MAY-16:00 | 251.01 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 28-JUN-16:00 | 338.04 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 576.91 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.45 | 23-JUL-15:50 | 168.61 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 571.03 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.13 | 13-AUG-15:00 | 232.43 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 829.44 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 14-SEP-17:00 | 159.99 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.00 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 288.96 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 341.35 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 269.11 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.99 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 59.82 | 356.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 236.37 | 12-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 602.99 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 217.19 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 497.81 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 217.80 | 28-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 352.14 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 | 01-APR-17:03 | 230.41 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 167.19 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 230.50 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 336.35 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 23-JUL-16:10 | 113.19 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 350.85 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 161.50 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 503.55 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 106.91 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 648.02 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 193.07 | 31-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 226.48 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 178.88 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.91 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 | 236.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 19095.72 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 917.32 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 17687.39 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 812.84 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 17246.14 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 581.12 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2392.06 | 27-APR-16:10 | 14871.96 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 537.57 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.33 | 05-MAY-16:10 | 12307.50 | 11-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 525.50 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2152.84 | 28-JUN-17:00 | 9655.18 | 13-JUN-11:01 |
July | 1306.65 | 03-JUL-09:09 | 571.49 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.74 | 31-JUL-16:10 | 8681.59 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 569.72 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.56 | 10-AUG-17:00 | 9727.09 | 01-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 821.97 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 802.43 | 14-SEP-17:00 | 10386.14 | 27-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1024.40 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12296.05 | 13-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 16150.31 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 18578.10 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 525.50 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8681.59 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6055.56 | 19095.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 236.38 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 580.25 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 216.38 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 530.30 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 213.57 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 447.91 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 | 01-APR-16:00 | 220.70 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 350.54 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 05-MAY-16:00 | 168.95 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 344.24 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 28-JUN-16:00 | 225.60 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 462.96 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 23-JUL-13:43 | 117.30 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 457.02 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 08-AUG-17:00 | 167.25 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 533.46 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 14-SEP-17:00 | 107.11 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 193.91 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 226.00 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 179.19 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 344.24 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.11 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 | 236.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 557.29 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 945.17 | 02-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 511.35 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 830.85 | 22-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 503.58 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 667.02 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.56 | 01-APR-17:03 | 530.70 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 541.20 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 392.14 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 529.53 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 579.71 | 12-JUL-08:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.57 | 23-JUL-16:00 | 265.49 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 574.19 | 02-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 13-AUG-15:00 | 366.30 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 837.21 | 25-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 250.17 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1027.50 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 449.20 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.39 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 418.76 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.17 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 75.56 | 557.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 369.32 | 12-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 604.67 | 02-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 338.77 | 16-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 502.98 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 340.49 | 28-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 354.45 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 01-APR-17:03 | 358.05 | 07-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 260.19 | 22-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 352.18 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 339.83 | 12-JUL-08:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 23-JUL-16:00 | 176.31 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 353.24 | 02-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 08-AUG-17:00 | 244.97 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 508.50 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 166.51 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 648.37 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.70 | 31-OCT-21:10 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 347.68 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 277.90 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.51 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 39.59 | 369.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-16:30 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 559.33 | 12-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 922.82 | 02-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 552.50 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 821.36 | 22-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 522.62 | 28-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 583.85 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 01-APR-17:30 | 539.56 | 07-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 542.25 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 | 05-MAY-16:00 | 392.13 | 22-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 530.71 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.03 | 28-JUN-16:00 | 529.07 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 574.59 | 12-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 23-JUL-15:56 | 267.87 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 572.96 | 02-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | 08-AUG-17:00 | 371.68 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 830.07 | 25-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 14-SEP-17:00 | 251.95 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 1025.02 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 449.57 | 31-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.91 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:19 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 422.40 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 530.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.95 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 559.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-16:30 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 369.22 | 12-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 582.59 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 337.50 | 16-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 534.10 | 22-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 339.74 | 28-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 454.11 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 01-APR-16:00 | 353.99 | 07-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 352.77 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 | 05-MAY-16:00 | 261.26 | 22-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 346.70 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 28-JUN-16:00 | 350.61 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 468.44 | 12-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 23-JUL-14:35 | 179.47 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 462.89 | 28-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 08-AUG-17:00 | 251.05 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 537.16 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 | 14-SEP-17:00 | 166.57 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 650.62 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.25 | 31-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 346.90 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:19 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 278.63 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 346.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.57 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 369.22 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 791.09 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 734.23 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 713.87 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 | 01-APR-17:03 | 738.42 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 05-MAY-16:00 | 552.37 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 28-JUN-15:00 | 740.90 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.71 | 23-JUL-13:53 | 371.56 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.94 | 13-AUG-15:20 | 502.96 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 14-SEP-17:00 | 343.64 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 644.00 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 743.39 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 592.34 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.64 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.10 | 791.09 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 971.65 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 890.81 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 886.62 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.04 | 01-APR-17:03 | 933.79 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 05-MAY-16:00 | 690.14 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28-JUN-15:00 | 933.38 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.62 | 23-JUL-13:53 | 465.27 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.11 | 13-AUG-15:20 | 639.84 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 14-SEP-17:00 | 422.87 | 30-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 783.32 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 901.80 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 726.92 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.04 | 971.65 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 941.77 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 854.09 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 843.90 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 01-APR-17:03 | 925.18 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 670.19 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 28-JUN-17:00 | 885.67 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 24-JUL-14:00 | 442.45 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 | 08-AUG-17:00 | 629.65 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 419.65 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 796.79 | 31-OCT-21:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 895.76 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 745.55 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 941.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11135.99 | 12-JAN-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14787.18 | 28-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18718.85 | 20-MAR-06:03 | 5082.11 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35561.64 | 28-APR-06:02 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38168.83 | 08-MAY-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39242.96 | 12-JUN-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39349.53 | 17-JUL-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39453.18 | 28-AUG-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39311.09 | 05-SEP-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38096.49 | 10-OCT-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28994.82 | 06-NOV-07:03 | 5082.11 | 6581.44 | 40779.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13627.36 | 06-DEC-15:50 | 6035.01 | 4936.01 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 11135.99 | 2541.06 | 2193.73 | 13979.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39453.18 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.28 |
February | 1823.93 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
March | 2914.98 | 14-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 |
April | 8433.97 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.64 | 0.00 |
May | 8836.77 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
June | 8637.11 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 |
July | 9838.89 | 24-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
August | 9937.18 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 |
September | 7763.91 | 14-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
October | 5440.22 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.14 |
November | 2302.28 | 04-NOV-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
December | 293.71 | 02-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9937.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 410.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1613.35 | 14-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 |
February | 1852.09 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.45 |
March | 2786.69 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 |
April | 2961.05 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 | 0.00 |
May | 3365.66 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
June | 3363.03 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 0.00 |
July | 4626.37 | 31-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 0.00 |
August | 4760.82 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 |
September | 3757.16 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
October | 2309.86 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
November | 2105.67 | 10-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.47 |
December | 1317.10 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1317.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4760.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 79.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2274.79 | 13-JAN-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.00 |
February | 2735.38 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
March | 3354.60 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.41 |
April | 3362.13 | 27-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 0.00 |
May | 4003.94 | 08-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.94 |
June | 3778.63 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 |
July | 5044.63 | 31-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 0.00 |
August | 5293.39 | 14-AUG-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 |
September | 4559.15 | 11-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
October | 3169.28 | 04-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 |
November | 2510.15 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 |
December | 2372.83 | 07-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2274.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5293.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 | 127.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6199.75 | 06-JAN-08:20 | 48280.06 | 39488.12 | 54466.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7995.20 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9486.92 | 02-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14268.91 | 27-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24101.37 | 08-MAY-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29913.98 | 12-JUN-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30043.78 | 31-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30634.56 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27553.24 | 11-SEP-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13837.17 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8786.26 | 06-NOV-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6294.40 | 06-DEC-16:10 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6199.75 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30634.56 | 48280.06 | 39488.12 | 54466.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5764.07 | 06-JAN-10:30 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7018.64 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8525.16 | 02-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15649.88 | 27-APR-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16782.74 | 15-MAY-15:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16988.44 | 28-JUN-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24132.02 | 24-JUL-06:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27857.89 | 14-AUG-06:02 | 6352.64 | 8226.80 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16585.34 | 11-SEP-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13717.33 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6457.03 | 02-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5844.71 | 05-DEC-16:15 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5764.07 | 5082.11 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27857.89 | 12070.02 | 9872.03 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1011.57 | 11-JAN-16:20 | 1272.23 | 966.90 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.48 |
February | 1286.30 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1370.43 | 10-MAR-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 |
April | 4484.14 | 27-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 | 0.00 |
May | 4836.91 | 15-MAY-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
June | 5131.32 | 21-JUN-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 0.00 |
July | 6845.41 | 24-JUL-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 |
August | 5618.25 | 09-AUG-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 0.00 |
September | 4265.78 | 12-SEP-14:50 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 0.00 |
October | 2690.04 | 04-OCT-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
November | 1229.15 | 02-NOV-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 |
December | 949.64 | 05-DEC-15:10 | 1272.23 | 697.95 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 949.64 | 1071.35 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6845.41 | 1306.65 | 966.90 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 50.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 700.34 | 05-JAN-09:20 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.36 |
February | 861.28 | 27-FEB-15:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
March | 2829.59 | 14-MAR-09:50 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 |
April | 6790.76 | 27-APR-09:10 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 |
May | 10335.23 | 14-MAY-10:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.24 |
June | 12374.51 | 25-JUN-08:62 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.19 |
July | 14418.06 | 30-JUL-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.38 |
August | 13288.98 | 13-AUG-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.03 |
September | 13470.85 | 10-SEP-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.54 |
October | 4886.95 | 04-OCT-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 |
November | 853.72 | 02-NOV-10:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 |
December | 696.17 | 05-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 696.17 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | |
Maximum of Months | 14418.06 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6823.43 | 20-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
February | 8997.67 | 27-FEB-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
March | 10200.60 | 01-MAR-13:35 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 |
April | 12120.98 | 27-APR-13:05 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 0.00 |
May | 19530.11 | 14-MAY-15:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.36 |
June | 10750.92 | 25-JUN-13:23 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 |
July | 20415.85 | 30-JUL-11:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 |
August | 19467.08 | 13-AUG-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 |
September | 21361.29 | 10-SEP-12:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.79 |
October | 20189.24 | 08-OCT-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.32 |
November | 9418.60 | 04-NOV-13:30 | 275.09 | 165.44 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6970.43 | 05-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6823.43 | 200.88 | 82.72 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21361.29 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 | 113.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 792.99 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 |
February | 3637.83 | 27-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 |
March | 5342.15 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
April | 8288.79 | 26-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
May | 15720.52 | 14-MAY-15:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 |
June | 13189.20 | 18-JUN-17:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 |
July | 15595.88 | 30-JUL-17:51 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 |
August | 15071.36 | 06-AUG-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.15 |
September | 15914.83 | 10-SEP-16:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.99 |
October | 6730.77 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
November | 2844.55 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
December | 984.24 | 05-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 792.99 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15914.83 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 138.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.47 | 11-JAN-16:20 | 1272.23 | 964.06 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.28 |
February | 1193.94 | 28-FEB-14:20 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
March | 1238.95 | 10-MAR-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
April | 2710.20 | 27-APR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 | 0.00 |
May | 3176.98 | 05-MAY-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
June | 3901.26 | 21-JUN-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.27 | 0.00 |
July | 4890.93 | 24-JUL-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
August | 4466.03 | 09-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 0.00 |
September | 3358.73 | 12-SEP-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
October | 2123.50 | 04-OCT-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
November | 1264.79 | 06-NOV-12:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 |
December | 980.28 | 14-DEC-13:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 980.28 | 1071.35 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4890.93 | 1306.65 | 964.06 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 | 84.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 715.65 | 05-JAN-09:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.76 |
February | 797.96 | 27-FEB-15:40 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
March | 1691.41 | 14-MAR-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
April | 5104.60 | 27-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
May | 8604.73 | 15-MAY-06:02 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 |
June | 8708.61 | 19-JUN-06:02 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.71 |
July | 9679.98 | 23-JUL-08:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.79 |
August | 11483.94 | 13-AUG-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 |
September | 7092.62 | 10-SEP-07:43 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4135.43 | 04-OCT-08:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
November | 987.59 | 02-NOV-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
December | 751.10 | 05-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 715.65 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11483.94 | 1017.38 | 628.46 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2013.26 | 20-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1954.97 |
February | 5411.93 | 27-FEB-15:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.29 |
March | 7540.01 | 02-MAR-13:07 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.45 |
April | 9334.72 | 27-APR-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 221.82 | 0.00 |
May | 8674.11 | 14-MAY-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 |
June | 7193.27 | 28-JUN-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 75.22 | 0.00 |
July | 10999.94 | 31-JUL-16:10 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.74 | 0.00 |
August | 16934.41 | 13-AUG-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 |
September | 16269.06 | 10-SEP-15:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 |
October | 11342.32 | 04-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.37 |
November | 6973.80 | 04-NOV-13:40 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4236.03 | 05-DEC-12:00 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2013.26 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16934.41 | 7633.40 | 2978.07 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3809.74 | 1954.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 738.68 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 |
February | 2308.01 | 27-FEB-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 |
March | 3128.21 | 02-MAR-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
April | 5938.90 | 26-APR-17:30 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 12791.22 | 07-MAY-17:21 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 |
June | 7562.62 | 25-JUN-18:03 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 |
July | 12691.24 | 23-JUL-18:01 | 0.00 | 139.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 |
August | 12968.28 | 06-AUG-18:32 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 |
September | 11671.08 | 10-SEP-17:42 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.11 |
October | 5937.01 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 |
November | 2394.64 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
December | 849.93 | 05-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 738.68 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | |
Maximum of Months | 12968.28 | 805.38 | 314.21 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1067.15 | 11-JAN-16:20 | 1272.23 | 966.89 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 |
February | 1320.56 | 28-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1452.75 | 10-MAR-14:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 |
April | 4132.24 | 27-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 0.00 |
May | 4456.88 | 15-MAY-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
June | 4787.17 | 21-JUN-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 0.00 |
July | 7053.20 | 24-JUL-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
August | 6803.41 | 14-AUG-06:02 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
September | 4117.97 | 12-SEP-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 | 0.00 |
October | 2762.54 | 04-OCT-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
November | 1281.79 | 02-NOV-14:10 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
December | 1023.22 | 05-DEC-15:20 | 1272.23 | 728.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1023.22 | 1071.35 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7053.20 | 2544.47 | 992.69 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 43.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 738.53 | 06-JAN-09:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2271.91 | 27-FEB-15:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 |
March | 5759.01 | 01-MAR-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
April | 7483.17 | 27-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
May | 12054.46 | 14-MAY-07:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.77 |
June | 11247.59 | 25-JUN-10:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.94 |
July | 13326.73 | 30-JUL-08:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.25 |
August | 14452.68 | 13-AUG-08:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.16 |
September | 11613.30 | 10-SEP-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.42 |
October | 6024.50 | 04-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.11 |
November | 4219.32 | 02-NOV-12:02 | 4027.14 | 1571.14 | 4542.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 |
December | 805.02 | 05-DEC-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 738.53 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14452.68 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7326.19 | 20-JAN-13:12 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
February | 9148.82 | 27-FEB-14:10 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
March | 10560.37 | 01-MAR-13:30 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
April | 11676.62 | 02-APR-13:13 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.44 |
May | 18230.10 | 14-MAY-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.96 |
June | 14409.13 | 11-JUN-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 |
July | 15934.47 | 23-JUL-14:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 0.00 |
August | 19704.87 | 13-AUG-12:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
September | 18631.10 | 10-SEP-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.58 |
October | 13640.78 | 04-OCT-12:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
November | 9543.99 | 04-NOV-13:30 | 275.09 | 165.44 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7942.13 | 05-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7326.19 | 200.88 | 82.72 | 1116.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19704.87 | 6361.16 | 2481.72 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 131.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 819.91 | 20-JAN-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 |
February | 3741.77 | 27-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 |
March | 5250.05 | 14-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 |
April | 8026.26 | 26-APR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
May | 15139.28 | 07-MAY-16:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.88 |
June | 14535.62 | 18-JUN-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.17 |
July | 14296.98 | 30-JUL-18:01 | 0.00 | 122.19 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 |
August | 14672.82 | 06-AUG-18:22 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.61 |
September | 13348.76 | 10-SEP-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.12 |
October | 6687.43 | 04-OCT-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
November | 2970.17 | 04-NOV-15:30 | 84.78 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
December | 1321.47 | 05-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 819.91 | 0.00 | 52.37 | 353.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15139.28 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 130.17 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.981934E+11 | 81477.08 | 13-JAN-16:49 | 0.741803E+11 | 174322.99 | 17-JAN-07:19 |
February | 0.876421E+11 | 80265.56 | 27-FEB-15:09 | 0.413501E+11 | 166800.46 | 21-FEB-07:19 |
March | 0.100024E+12 | 78011.66 | 14-MAR-15:00 | 0.169904E+11 | 101877.81 | 01-MAR-07:10 |
April | 0.952830E+11 | 121700.57 | 27-APR-15:09 | 0.659458E+10 | 80716.45 | 19-APR-06:10 |
May | 0.103502E+12 | 116669.63 | 15-MAY-15:20 | 0.208619E+10 | 47032.77 | 18-MAY-06:10 |
June | 0.107452E+12 | 122219.03 | 28-JUN-15:39 | 0.520036E+09 | 18947.60 | 15-JUN-06:10 |
July | 0.115873E+12 | 144206.19 | 31-JUL-15:09 | 86991631.25 | 8133.01 | 13-JUL-06:19 |
August | 0.129635E+12 | 146002.71 | 10-AUG-15:20 | 0.124710E+09 | 14595.83 | 03-AUG-06:19 |
September | 0.103892E+12 | 122936.54 | 12-SEP-15:20 | 0.615135E+09 | 32237.25 | 28-SEP-06:10 |
October | 0.980517E+11 | 103202.80 | 04-OCT-15:20 | 0.489338E+10 | 67831.74 | 16-OCT-06:10 |
November | 0.953444E+11 | 81592.31 | 06-NOV-16:49 | 0.301708E+11 | 133814.00 | 24-NOV-07:10 |
December | 0.966017E+11 | 81581.04 | 06-DEC-16:19 | 0.583706E+11 | 184170.64 | 26-DEC-07:19 |
Annual Sum or Average | 0.123150E+13 | 0.235983E+12 | ||||
Minimum of Months | 0.876421E+11 | 78011.66 | 86991631.25 | 8133.01 | ||
Maximum of Months | 0.129635E+12 | 146002.71 | 0.741803E+11 | 184170.64 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.203678E+11 | 0.628818E+10 | 0.605851E+11 | 0.225730E+10 | 0.348918E+10 | 0.375839E+09 | 0.00 | 393395.59 | 0.00 | 0.00 | 0.00 | 0.482959E+10 | 0.00 |
February | 0.179483E+11 | 0.491554E+10 | 0.548702E+11 | 0.204820E+10 | 0.308666E+10 | 0.218963E+09 | 0.00 | 0.143047E+09 | 0.00 | 0.00 | 0.00 | 0.441110E+10 | 0.00 |
March | 0.209041E+11 | 0.442863E+10 | 0.627783E+11 | 0.235488E+10 | 0.399625E+10 | 98583079.83 | 0.00 | 0.316829E+09 | 0.00 | 0.00 | 0.00 | 0.514662E+10 | 0.00 |
April | 0.184074E+11 | 0.340219E+10 | 0.586172E+11 | 0.219172E+10 | 0.496088E+10 | 46593451.78 | 0.00 | 0.313095E+10 | 0.00 | 0.00 | 0.00 | 0.452604E+10 | 0.00 |
May | 0.197496E+11 | 0.290318E+10 | 0.616817E+11 | 0.230561E+10 | 0.700303E+10 | 24546461.97 | 0.00 | 0.515706E+10 | 0.00 | 0.00 | 0.00 | 0.467742E+10 | 0.00 |
June | 0.195722E+11 | 0.254241E+10 | 0.604966E+11 | 0.226779E+10 | 0.868723E+10 | 15941530.66 | 0.00 | 0.939217E+10 | 0.00 | 0.00 | 0.00 | 0.447766E+10 | 0.00 |
July | 0.183254E+11 | 0.273940E+10 | 0.597911E+11 | 0.222857E+10 | 0.109673E+11 | 12758274.74 | 0.00 | 0.176800E+11 | 0.00 | 0.00 | 0.00 | 0.412888E+10 | 0.00 |
August | 0.205063E+11 | 0.320959E+10 | 0.627783E+11 | 0.235451E+10 | 0.125773E+11 | 13595439.59 | 0.00 | 0.236892E+11 | 0.00 | 0.00 | 0.00 | 0.450660E+10 | 0.00 |
September | 0.185536E+11 | 0.386004E+10 | 0.585950E+11 | 0.219058E+10 | 0.794615E+10 | 15987927.51 | 0.00 | 0.860696E+10 | 0.00 | 0.00 | 0.00 | 0.412372E+10 | 0.00 |
October | 0.196323E+11 | 0.500879E+10 | 0.605962E+11 | 0.225785E+10 | 0.477795E+10 | 37605655.01 | 0.00 | 0.135507E+10 | 0.00 | 0.00 | 0.00 | 0.438590E+10 | 0.00 |
November | 0.200207E+11 | 0.580107E+10 | 0.591197E+11 | 0.220000E+10 | 0.332318E+10 | 0.158813E+09 | 0.00 | 0.247777E+09 | 0.00 | 0.00 | 0.00 | 0.447313E+10 | 0.00 |
December | 0.198945E+11 | 0.653724E+10 | 0.597800E+11 | 0.222861E+10 | 0.327351E+10 | 0.294596E+09 | 0.00 | 1851434.03 | 0.00 | 0.00 | 0.00 | 0.459138E+10 | 0.00 |
Annual Sum or Average | 0.233882E+12 | 0.516363E+11 | 0.719689E+12 | 0.268856E+11 | 0.740886E+11 | 0.131382E+10 | 0.00 | 0.697212E+11 | 0.00 | 0.00 | 0.00 | 0.542780E+11 | 0.00 |
Minimum of Months | 0.179483E+11 | 0.254241E+10 | 0.548702E+11 | 0.204820E+10 | 0.308666E+10 | 12758274.74 | 0.00 | 393395.59 | 0.00 | 0.00 | 0.00 | 0.412372E+10 | 0.00 |
Maximum of Months | 0.209041E+11 | 0.653724E+10 | 0.627783E+11 | 0.235488E+10 | 0.125773E+11 | 0.375839E+09 | 0.00 | 0.236892E+11 | 0.00 | 0.00 | 0.00 | 0.514662E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.741803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.413501E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.169904E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.659458E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.208619E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.520036E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 86991631.25 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.124710E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.615135E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.489338E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.301708E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.583706E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.235983E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 86991631.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.741803E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-16:30 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-08:09 | 7625.96 | 02-JAN-06:30 | 548.81 | 09-JAN-07:49 | 0.00 | 01-JAN-00:10 |
February | 23928.11 | 02-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 02-FEB-08:09 | 5953.31 | 21-FEB-07:10 | 537.74 | 21-FEB-07:00 | 0.00 | 01-FEB-00:10 |
March | 22850.42 | 22-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 02-MAR-12:09 | 5706.79 | 02-MAR-15:09 | 443.71 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
April | 20891.34 | 03-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-11:09 | 19294.33 | 27-APR-14:30 | 356.41 | 19-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 20047.80 | 17-MAY-07:10 | 3328.83 | 01-MAY-19:19 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-11:09 | 21096.46 | 15-MAY-14:30 | 225.48 | 18-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 19864.35 | 29-JUN-07:10 | 3328.83 | 01-JUN-19:00 | 41699.26 | 01-JUN-07:10 | 1410.29 | 06-JUN-16:10 | 19862.33 | 28-JUN-15:20 | 106.90 | 15-JUN-06:10 | 0.00 | 01-JUN-00:10 |
July | 20633.80 | 12-JUL-08:20 | 3328.83 | 01-JUL-20:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 12-JUL-11:09 | 28025.63 | 31-JUL-15:09 | 55.90 | 13-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 20471.70 | 28-AUG-07:30 | 5686.19 | 16-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-11:09 | 27911.00 | 14-AUG-15:20 | 88.90 | 18-AUG-06:19 | 0.00 | 01-AUG-00:10 |
September | 22922.38 | 25-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:09 | 23292.44 | 11-SEP-15:30 | 152.69 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 24860.84 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 10-OCT-16:10 | 16215.22 | 04-OCT-15:39 | 301.95 | 16-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 06-NOV-16:49 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 02-NOV-11:09 | 4206.25 | 24-NOV-07:10 | 489.23 | 24-NOV-07:19 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-16:19 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 04-DEC-12:09 | 6576.16 | 26-DEC-07:10 | 552.05 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19864.35 | 3328.83 | 41699.26 | 1410.29 | 4206.25 | 55.90 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 28025.63 | 552.05 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 288.38 | 02-JAN-10:30 | 0.00 | 0.00 | 0.00 | 6449.73 | 25-JAN-12:39 | 0.00 |
February | 8959.71 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 6514.69 | 10-FEB-12:50 | 0.00 |
March | 7944.05 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 6438.04 | 01-MAR-12:20 | 0.00 |
April | 36030.71 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 6250.82 | 03-APR-11:20 | 0.00 |
May | 29143.87 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 6200.04 | 01-MAY-11:50 | 0.00 |
June | 35237.25 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 | 5815.83 | 01-JUN-11:50 | 0.00 |
July | 50977.60 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 5765.13 | 05-JUL-11:00 | 0.00 |
August | 52760.88 | 29-AUG-15:30 | 0.00 | 0.00 | 0.00 | 5694.33 | 29-AUG-11:30 | 0.00 |
September | 34329.63 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 5776.61 | 29-SEP-11:30 | 0.00 |
October | 20559.51 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 5828.87 | 31-OCT-11:20 | 0.00 |
November | 12689.83 | 04-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6212.28 | 30-NOV-12:30 | 0.00 |
December | 931.80 | 05-DEC-11:00 | 0.00 | 0.00 | 0.00 | 6261.77 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 288.38 | 0.00 | 0.00 | 0.00 | 5694.33 | 0.00 | ||
Maximum of Months | 52760.88 | 0.00 | 0.00 | 0.00 | 6514.69 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 81477.08 | 13-JAN-16:49 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2449.55 | 274.59 | 0.00 | 0.00 | 0.00 |
February | 80265.56 | 27-FEB-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 4694.35 | 6.85 | 0.00 | 8959.71 | 0.00 |
March | 78011.66 | 14-MAR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 5400.13 | 6.85 | 0.00 | 4871.67 | 0.00 |
April | 121700.57 | 27-APR-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 18491.75 | 6.85 | 0.00 | 35839.50 | 0.00 |
May | 116669.63 | 15-MAY-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 20844.84 | 6.85 | 0.00 | 28496.46 | 0.00 |
June | 122219.03 | 28-JUN-15:39 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 19755.08 | 6.85 | 0.00 | 35173.66 | 0.00 |
July | 144206.19 | 31-JUL-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 28025.63 | 6.90 | 0.00 | 49189.50 | 0.00 |
August | 146002.71 | 10-AUG-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 26940.71 | 6.90 | 0.00 | 52126.51 | 0.00 |
September | 122936.54 | 12-SEP-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 22166.83 | 6.90 | 0.00 | 33754.61 | 0.00 |
October | 103202.80 | 04-OCT-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 15963.78 | 6.85 | 0.00 | 19904.50 | 0.00 |
November | 81592.31 | 06-NOV-16:49 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 3206.61 | 6.85 | 0.00 | 0.00 | 0.00 |
December | 81581.04 | 06-DEC-16:19 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 2660.90 | 199.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 78011.66 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 2449.55 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 146002.71 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 28025.63 | 274.59 | 0.00 | 52126.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 174322.99 | 17-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 166800.46 | 21-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 101877.81 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 80716.45 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 47032.77 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18947.60 | 15-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 8133.01 | 13-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 14595.83 | 03-AUG-06:19 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 32237.25 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 67831.74 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 133814.00 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 184170.64 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 8133.01 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 184170.64 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.58 | 2.33 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.58 | 2.33 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.58 | 2.33 | 19.58 | 0.00 | 19.58 | 0.00 | 19.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.22 | 3.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 19.22 | 3.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.22 | 3.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 19.27 | 4.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
February | 0.67 | 18.74 | 0.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 19.57 | 1.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Annual Sum or Average | 5.83 | 19.27 | 5.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.57 | 4.00 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.67 | 18.73 | 9.33 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
February | 4.17 | 18.51 | 3.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
March | 0.17 | 19.27 | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.11 | 0.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 5.33 | 19.19 | 5.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 20.83 | 18.82 | 18.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.67 | 19.27 | 9.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.46 | 4.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 1.33 | 17.67 | 1.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.70 | 1.17 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.61 | 2.33 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.81 | 5.00 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 3.83 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.71 | 1.17 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.08 | 0.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 2.50 | 18.98 | 2.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 9.17 | 18.50 | 7.33 | 18.78 | 13.50 | 22.83 | 13.50 | 24.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.17 | 19.08 | 4.00 | 19.20 | 5.00 | 27.91 | 5.00 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 19.15 | 3.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.83 | 18.54 | 0.67 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.64 | 2.83 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.67 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.82 | 3.83 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.00 | 3.33 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.23 | 1.67 | 28.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
November | 0.17 | 19.13 | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 1.67 | 19.23 | 1.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 6.67 | 19.09 | 5.83 | 19.28 | 16.50 | 24.13 | 15.83 | 25.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.23 | 3.50 | 19.36 | 4.17 | 28.23 | 3.83 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.33 | 18.45 | 3.50 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 1.17 | 18.12 | 0.83 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.10 | 3.17 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.83 | 2.33 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.29 | 3.33 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.27 | 2.00 | 28.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.80 | 2.33 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.13 | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
December | 2.00 | 18.90 | 1.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 7.67 | 18.53 | 6.17 | 18.84 | 22.50 | 24.57 | 13.67 | 25.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 19.13 | 3.50 | 19.18 | 6.17 | 28.29 | 3.33 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 19.38 | 4.83 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.17 | 19.17 | 0.17 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.75 | 0.33 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Annual Sum or Average | 5.33 | 19.40 | 5.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 19.75 | 4.83 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.18 | 3.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.83 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.83 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.68 | 2.83 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.58 | 3.83 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 3.33 | 19.19 | 3.17 | 19.30 | 9.50 | 24.22 | 9.50 | 25.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.35 | 3.00 | 19.35 | 3.83 | 27.68 | 3.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 18.36 | 72.50 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
February | 42.33 | 18.57 | 42.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
March | 35.17 | 19.21 | 35.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
April | 17.67 | 19.31 | 17.67 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 7.17 | 19.90 | 7.17 | 19.90 | 0.83 | 20.31 | 0.83 | 20.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.54 | 2.17 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.83 | 27.66 |
September | 2.00 | 20.06 | 2.00 | 20.06 | 2.00 | 22.66 | 1.83 | 23.89 |
October | 13.50 | 19.98 | 13.50 | 19.98 | 0.67 | 20.16 | 0.67 | 20.33 |
November | 42.17 | 19.09 | 42.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
December | 61.33 | 18.57 | 61.33 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
Annual Sum or Average | 293.83 | 18.82 | 293.83 | 18.82 | 8.67 | 18.95 | 8.50 | 19.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.36 | 0.00 | 18.36 |
Maximum of Months | 72.50 | 20.06 | 72.50 | 20.06 | 2.83 | 27.66 | 2.83 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.97 | 2.83 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.69 | 1.83 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.61 | 0.67 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.02 | 2.00 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.88 | 1.67 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.60 | 1.67 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.36 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 3.33 | 18.99 | 3.00 | 19.20 | 15.33 | 25.29 | 7.83 | 25.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.36 | 2.83 | 19.36 | 4.50 | 28.02 | 2.00 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.00 | 19.33 | 4.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.76 | 1.00 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Annual Sum or Average | 5.17 | 19.41 | 5.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.00 | 19.76 | 4.00 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.32 | 2.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.84 | 1.17 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.50 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.03 | 3.50 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 3.83 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.78 | 1.50 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 2.50 | 19.40 | 2.33 | 19.47 | 12.50 | 25.53 | 12.50 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.90 | 2.00 | 19.90 | 3.83 | 28.03 | 3.83 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.42 | 2.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.48 | 1.17 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.57 | 2.67 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.46 | 1.83 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.77 | 3.50 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.89 | 3.50 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.00 | 2.33 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.70 | 1.00 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
December | 0.17 | 19.36 | 0.17 | 19.36 | 0.17 | 21.99 | 0.17 | 23.31 |
Annual Sum or Average | 2.33 | 19.42 | 2.33 | 19.42 | 16.83 | 25.91 | 16.83 | 26.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.42 | 2.17 | 19.42 | 3.50 | 28.00 | 3.50 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.39 | 2.17 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.00 | 3.00 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.84 | 2.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.19 | 3.17 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.17 | 2.00 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.76 | 2.50 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.90 | 0.33 | 19.90 | 0.00 | 19.90 | 0.00 | 19.90 |
Annual Sum or Average | 2.67 | 19.45 | 2.50 | 19.52 | 21.50 | 26.37 | 13.17 | 26.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.90 | 2.17 | 19.90 | 5.83 | 28.19 | 3.17 | 28.20 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.07 | 32.00 | 22.88 | 32.00 | 22.70 |
February | 406.33 | 23.75 | 0.00 | 23.75 | 0.00 | 23.75 |
March | 259.67 | 24.02 | 12.50 | 24.08 | 0.00 | 24.08 |
April | 70.33 | 24.01 | 107.67 | 24.78 | 0.00 | 24.78 |
May | 0.00 | 0.00 | 210.17 | 24.91 | 0.00 | 24.91 |
June | 0.00 | 0.00 | 265.50 | 24.77 | 0.00 | 24.77 |
July | 0.00 | 0.00 | 400.67 | 24.66 | 0.00 | 24.66 |
August | 0.00 | 0.00 | 467.00 | 24.49 | 0.00 | 24.49 |
September | 0.00 | 0.00 | 344.83 | 24.69 | 0.00 | 24.69 |
October | 20.67 | 24.00 | 114.33 | 25.28 | 0.00 | 25.28 |
November | 269.00 | 23.88 | 37.50 | 24.03 | 0.00 | 24.03 |
December | 491.67 | 23.69 | 0.00 | 23.69 | 0.00 | 23.69 |
Annual Sum or Average | 2019.67 | 23.63 | 1992.17 | 24.15 | 32.00 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.88 | 0.00 | 22.70 |
Maximum of Months | 502.00 | 24.02 | 467.00 | 25.28 | 32.00 | 25.28 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.42 | 110.50 | 21.19 | 110.50 | 21.03 |
February | 450.00 | 22.18 | 34.83 | 22.07 | 34.83 | 21.97 |
March | 503.17 | 23.24 | 0.00 | 23.24 | 0.00 | 23.24 |
April | 322.33 | 23.56 | 29.50 | 23.67 | 0.00 | 23.67 |
May | 136.33 | 23.72 | 70.00 | 24.01 | 0.00 | 24.01 |
June | 22.67 | 23.75 | 132.67 | 24.49 | 0.00 | 24.49 |
July | 0.67 | 23.69 | 289.67 | 24.45 | 0.00 | 24.45 |
August | 6.00 | 23.68 | 366.00 | 24.33 | 0.00 | 24.33 |
September | 43.33 | 23.51 | 198.50 | 24.32 | 0.00 | 24.32 |
October | 307.33 | 23.32 | 14.83 | 23.40 | 0.00 | 23.40 |
November | 446.17 | 22.54 | 1.00 | 22.54 | 1.00 | 22.53 |
December | 497.00 | 21.89 | 25.67 | 21.82 | 25.67 | 21.75 |
Annual Sum or Average | 3237.00 | 22.57 | 1273.17 | 22.95 | 172.00 | 22.85 |
Minimum of Months | 0.67 | 21.42 | 0.00 | 21.19 | 0.00 | 21.03 |
Maximum of Months | 503.17 | 23.75 | 366.00 | 24.49 | 110.50 | 24.49 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 240.17 | 20.48 | 240.17 | 20.35 |
February | 451.67 | 21.36 | 132.67 | 21.10 | 132.67 | 20.93 |
March | 510.83 | 22.47 | 24.17 | 22.39 | 24.17 | 22.31 |
April | 376.50 | 23.06 | 19.67 | 23.13 | 0.00 | 23.13 |
May | 224.33 | 23.39 | 51.17 | 23.57 | 0.00 | 23.57 |
June | 94.00 | 23.54 | 95.83 | 23.97 | 0.00 | 23.97 |
July | 41.50 | 23.62 | 255.00 | 24.24 | 0.00 | 24.24 |
August | 41.00 | 23.49 | 308.83 | 24.17 | 0.00 | 24.17 |
September | 158.00 | 23.33 | 120.33 | 23.73 | 0.00 | 23.73 |
October | 429.67 | 22.79 | 0.67 | 22.79 | 0.00 | 22.79 |
November | 488.50 | 21.76 | 72.50 | 21.57 | 72.50 | 21.42 |
December | 497.00 | 21.03 | 187.00 | 20.81 | 187.00 | 20.68 |
Annual Sum or Average | 3815.00 | 22.07 | 1508.00 | 22.19 | 656.50 | 21.96 |
Minimum of Months | 41.00 | 20.74 | 0.67 | 20.48 | 0.00 | 20.35 |
Maximum of Months | 510.83 | 23.62 | 308.83 | 24.24 | 240.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 395.33 | 19.96 | 395.33 | 19.92 |
February | 454.00 | 20.53 | 260.00 | 20.31 | 260.00 | 20.21 |
March | 513.33 | 21.45 | 124.00 | 21.22 | 124.00 | 21.06 |
April | 416.50 | 22.32 | 48.00 | 22.27 | 30.17 | 22.16 |
May | 280.00 | 22.81 | 58.50 | 23.05 | 1.00 | 23.04 |
June | 155.83 | 23.22 | 103.83 | 23.66 | 0.00 | 23.66 |
July | 101.83 | 23.37 | 255.83 | 24.02 | 0.00 | 24.02 |
August | 119.33 | 23.29 | 281.67 | 23.93 | 0.00 | 23.93 |
September | 266.17 | 22.80 | 87.83 | 23.15 | 0.00 | 23.15 |
October | 477.33 | 21.90 | 41.50 | 21.76 | 41.50 | 21.64 |
November | 489.00 | 20.82 | 218.17 | 20.57 | 218.17 | 20.44 |
December | 497.00 | 20.27 | 372.17 | 20.16 | 372.17 | 20.11 |
Annual Sum or Average | 4272.33 | 21.45 | 2246.83 | 21.47 | 1442.33 | 21.20 |
Minimum of Months | 101.83 | 20.08 | 41.50 | 19.96 | 0.00 | 19.92 |
Maximum of Months | 513.33 | 23.37 | 395.33 | 24.02 | 395.33 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 363.67 | 19.98 | 363.67 | 19.92 |
February | 454.00 | 20.83 | 226.17 | 20.56 | 226.17 | 20.42 |
March | 498.17 | 21.86 | 88.33 | 21.59 | 88.33 | 21.39 |
April | 301.50 | 22.43 | 82.33 | 22.64 | 19.17 | 22.53 |
May | 209.83 | 22.85 | 147.17 | 23.51 | 4.50 | 23.53 |
June | 108.67 | 23.44 | 231.00 | 24.13 | 6.50 | 24.19 |
July | 89.83 | 24.16 | 333.33 | 24.38 | 18.50 | 24.49 |
August | 86.33 | 23.96 | 360.50 | 24.25 | 15.00 | 24.34 |
September | 206.00 | 22.87 | 174.83 | 23.56 | 3.83 | 23.59 |
October | 400.67 | 21.97 | 55.83 | 21.94 | 35.33 | 21.81 |
November | 487.83 | 20.96 | 188.33 | 20.68 | 188.33 | 20.52 |
December | 497.00 | 20.34 | 336.17 | 20.19 | 336.17 | 20.12 |
Annual Sum or Average | 3841.83 | 21.51 | 2587.67 | 21.80 | 1305.50 | 21.53 |
Minimum of Months | 86.33 | 20.13 | 55.83 | 19.98 | 3.83 | 19.92 |
Maximum of Months | 502.00 | 24.16 | 363.67 | 24.38 | 363.67 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 20.52 | 308.83 | 20.25 | 308.17 | 20.13 |
February | 404.00 | 21.07 | 198.00 | 20.88 | 181.67 | 20.70 |
March | 408.00 | 21.69 | 117.83 | 21.61 | 84.17 | 21.41 |
April | 297.67 | 22.33 | 113.33 | 22.70 | 23.83 | 22.60 |
May | 237.33 | 22.86 | 151.67 | 23.48 | 9.83 | 23.55 |
June | 156.00 | 23.27 | 190.67 | 23.92 | 6.17 | 23.97 |
July | 113.83 | 23.71 | 297.33 | 24.24 | 13.00 | 24.33 |
August | 115.50 | 23.69 | 332.33 | 24.17 | 13.00 | 24.26 |
September | 200.17 | 22.99 | 210.67 | 23.71 | 7.50 | 23.77 |
October | 349.83 | 22.08 | 120.33 | 22.46 | 30.50 | 22.36 |
November | 451.17 | 21.15 | 184.83 | 21.01 | 160.50 | 20.81 |
December | 470.83 | 20.66 | 284.50 | 20.42 | 281.00 | 20.30 |
Annual Sum or Average | 3701.17 | 21.69 | 2510.33 | 22.04 | 1119.33 | 21.77 |
Minimum of Months | 113.83 | 20.52 | 113.33 | 20.25 | 6.17 | 20.13 |
Maximum of Months | 496.83 | 23.71 | 332.33 | 24.24 | 308.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 372.33 | 20.01 | 372.33 | 19.95 |
February | 443.83 | 20.75 | 233.33 | 20.49 | 232.50 | 20.36 |
March | 472.33 | 21.56 | 116.33 | 21.36 | 107.33 | 21.19 |
April | 342.17 | 22.25 | 89.67 | 22.46 | 28.83 | 22.36 |
May | 247.33 | 22.95 | 138.00 | 23.50 | 14.50 | 23.61 |
June | 150.17 | 23.33 | 196.67 | 23.94 | 8.17 | 24.01 |
July | 108.17 | 23.87 | 317.00 | 24.30 | 16.17 | 24.40 |
August | 110.83 | 23.62 | 327.50 | 24.15 | 11.00 | 24.22 |
September | 220.33 | 23.00 | 175.33 | 23.62 | 10.83 | 23.71 |
October | 424.17 | 21.93 | 69.33 | 21.96 | 38.17 | 21.83 |
November | 480.83 | 20.91 | 197.33 | 20.67 | 194.17 | 20.52 |
December | 497.00 | 20.39 | 338.83 | 20.22 | 338.83 | 20.15 |
Annual Sum or Average | 3999.17 | 21.52 | 2571.67 | 21.77 | 1372.83 | 21.51 |
Minimum of Months | 108.17 | 20.17 | 69.33 | 20.01 | 8.17 | 19.95 |
Maximum of Months | 502.00 | 23.87 | 372.33 | 24.30 | 372.33 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 360.50 | 20.32 | 360.50 | 20.27 |
February | 454.00 | 20.82 | 219.33 | 20.66 | 219.33 | 20.58 |
March | 514.00 | 21.56 | 58.67 | 21.45 | 58.67 | 21.36 |
April | 455.50 | 22.43 | 7.17 | 22.43 | 3.83 | 22.41 |
May | 351.00 | 23.16 | 25.67 | 23.23 | 0.00 | 23.23 |
June | 169.00 | 23.48 | 56.17 | 23.68 | 0.00 | 23.68 |
July | 65.67 | 23.62 | 215.33 | 24.10 | 0.00 | 24.10 |
August | 72.00 | 23.50 | 272.83 | 24.05 | 0.00 | 24.05 |
September | 240.50 | 23.24 | 79.17 | 23.48 | 0.00 | 23.48 |
October | 477.33 | 22.57 | 0.50 | 22.57 | 0.00 | 22.57 |
November | 489.00 | 21.48 | 79.00 | 21.34 | 79.00 | 21.23 |
December | 497.00 | 20.72 | 272.83 | 20.61 | 272.83 | 20.55 |
Annual Sum or Average | 4287.00 | 21.81 | 1647.17 | 21.83 | 994.17 | 21.61 |
Minimum of Months | 65.67 | 20.42 | 0.50 | 20.32 | 0.00 | 20.27 |
Maximum of Months | 514.00 | 23.62 | 360.50 | 24.10 | 360.50 | 24.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.47 | 332.33 | 20.34 | 332.33 | 20.29 |
February | 454.00 | 21.14 | 165.67 | 20.94 | 165.67 | 20.83 |
March | 512.50 | 22.16 | 28.33 | 22.06 | 28.33 | 21.98 |
April | 319.67 | 22.83 | 49.17 | 23.01 | 1.67 | 23.00 |
May | 213.67 | 23.20 | 108.67 | 23.66 | 0.50 | 23.66 |
June | 73.83 | 23.52 | 223.00 | 24.27 | 0.83 | 24.28 |
July | 34.00 | 24.63 | 349.50 | 24.48 | 10.00 | 24.54 |
August | 38.50 | 24.52 | 386.17 | 24.38 | 11.17 | 24.45 |
September | 144.00 | 23.34 | 203.83 | 23.97 | 3.17 | 23.99 |
October | 374.17 | 22.73 | 23.17 | 22.85 | 0.00 | 22.85 |
November | 483.33 | 21.65 | 62.83 | 21.50 | 62.83 | 21.38 |
December | 497.00 | 20.85 | 229.17 | 20.68 | 229.17 | 20.60 |
Annual Sum or Average | 3646.67 | 21.85 | 2161.83 | 22.23 | 845.67 | 22.01 |
Minimum of Months | 34.00 | 20.47 | 23.17 | 20.34 | 0.00 | 20.29 |
Maximum of Months | 512.50 | 24.63 | 386.17 | 24.48 | 332.33 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 20.32 | 320.00 | 20.11 | 320.00 | 20.01 |
February | 427.17 | 21.04 | 138.83 | 20.80 | 134.00 | 20.61 |
March | 458.50 | 21.60 | 53.00 | 21.47 | 44.17 | 21.31 |
April | 356.33 | 22.15 | 74.17 | 22.40 | 15.50 | 22.29 |
May | 305.67 | 22.56 | 88.17 | 23.02 | 2.00 | 23.01 |
June | 206.33 | 22.82 | 125.17 | 23.50 | 0.17 | 23.50 |
July | 90.33 | 23.07 | 302.50 | 24.15 | 5.50 | 24.19 |
August | 83.33 | 23.18 | 343.33 | 24.15 | 9.50 | 24.21 |
September | 153.67 | 22.74 | 233.83 | 23.81 | 6.83 | 23.87 |
October | 330.17 | 22.29 | 95.00 | 22.85 | 3.83 | 22.86 |
November | 454.67 | 21.23 | 96.00 | 21.18 | 75.17 | 21.00 |
December | 479.33 | 20.69 | 241.83 | 20.47 | 238.17 | 20.34 |
Annual Sum or Average | 3844.00 | 21.58 | 2111.83 | 21.97 | 854.83 | 21.73 |
Minimum of Months | 83.33 | 20.32 | 53.00 | 20.11 | 0.17 | 20.01 |
Maximum of Months | 498.50 | 23.18 | 343.33 | 24.15 | 320.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.50 | 333.67 | 20.36 | 333.67 | 20.30 |
February | 452.33 | 21.11 | 168.17 | 20.90 | 168.17 | 20.78 |
March | 492.50 | 21.95 | 39.67 | 21.85 | 38.17 | 21.76 |
April | 360.33 | 22.67 | 49.67 | 22.88 | 2.00 | 22.87 |
May | 218.17 | 23.34 | 118.17 | 23.78 | 3.67 | 23.81 |
June | 96.83 | 23.53 | 184.67 | 24.12 | 1.33 | 24.14 |
July | 31.83 | 24.73 | 369.83 | 24.52 | 9.67 | 24.58 |
August | 33.83 | 24.27 | 389.83 | 24.35 | 8.17 | 24.40 |
September | 118.50 | 23.50 | 224.17 | 24.13 | 5.50 | 24.17 |
October | 393.17 | 22.71 | 32.67 | 22.87 | 0.00 | 22.87 |
November | 479.33 | 21.60 | 67.50 | 21.49 | 63.00 | 21.37 |
December | 497.00 | 20.85 | 237.67 | 20.69 | 237.67 | 20.61 |
Annual Sum or Average | 3675.83 | 21.83 | 2215.67 | 22.22 | 871.00 | 22.00 |
Minimum of Months | 31.83 | 20.50 | 32.67 | 20.36 | 0.00 | 20.30 |
Maximum of Months | 502.00 | 24.73 | 389.83 | 24.52 | 333.67 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 324.67 | 20.25 | 324.67 | 20.18 |
February | 454.00 | 20.96 | 182.67 | 20.73 | 182.67 | 20.60 |
March | 512.33 | 22.04 | 36.17 | 21.93 | 36.17 | 21.84 |
April | 398.50 | 22.82 | 20.50 | 22.88 | 1.83 | 22.87 |
May | 239.17 | 23.26 | 62.33 | 23.47 | 0.00 | 23.47 |
June | 96.50 | 23.52 | 113.33 | 23.95 | 0.00 | 23.95 |
July | 38.50 | 23.65 | 280.67 | 24.22 | 0.00 | 24.22 |
August | 45.00 | 23.45 | 317.83 | 24.13 | 0.00 | 24.13 |
September | 199.33 | 23.23 | 115.83 | 23.61 | 0.00 | 23.61 |
October | 450.17 | 22.51 | 7.17 | 22.54 | 1.00 | 22.53 |
November | 489.00 | 21.38 | 114.50 | 21.18 | 114.50 | 21.04 |
December | 497.00 | 20.67 | 265.67 | 20.52 | 265.67 | 20.45 |
Annual Sum or Average | 3921.50 | 21.79 | 1841.33 | 21.92 | 926.50 | 21.68 |
Minimum of Months | 38.50 | 20.41 | 7.17 | 20.25 | 0.00 | 20.18 |
Maximum of Months | 512.33 | 23.65 | 324.67 | 24.22 | 324.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.36 | 272.50 | 20.17 | 272.50 | 20.09 |
February | 383.83 | 21.19 | 137.83 | 20.93 | 137.83 | 20.78 |
March | 411.50 | 22.25 | 29.83 | 22.12 | 29.67 | 22.01 |
April | 253.17 | 22.88 | 59.83 | 23.18 | 1.33 | 23.17 |
May | 168.83 | 23.30 | 117.00 | 23.85 | 4.17 | 23.90 |
June | 74.50 | 23.84 | 200.17 | 24.38 | 7.67 | 24.45 |
July | 33.83 | 24.94 | 288.50 | 24.62 | 12.67 | 24.71 |
August | 41.67 | 24.70 | 312.33 | 24.47 | 14.50 | 24.57 |
September | 145.83 | 23.36 | 163.33 | 23.96 | 5.00 | 24.01 |
October | 327.00 | 22.51 | 26.00 | 22.66 | 1.00 | 22.65 |
November | 409.67 | 21.43 | 95.83 | 21.20 | 95.67 | 21.04 |
December | 422.00 | 20.70 | 217.50 | 20.50 | 217.50 | 20.41 |
Annual Sum or Average | 3098.83 | 21.83 | 1920.67 | 22.19 | 799.50 | 21.95 |
Minimum of Months | 33.83 | 20.36 | 26.00 | 20.17 | 1.00 | 20.09 |
Maximum of Months | 427.00 | 24.94 | 312.33 | 24.62 | 272.50 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.83 | 20.88 | 236.67 | 20.62 | 233.17 | 20.47 |
February | 389.17 | 21.48 | 128.50 | 21.39 | 105.83 | 21.20 |
March | 390.33 | 22.26 | 61.83 | 22.35 | 22.83 | 22.26 |
April | 266.67 | 22.82 | 101.83 | 23.30 | 2.00 | 23.29 |
May | 202.83 | 23.35 | 157.17 | 23.84 | 7.67 | 23.91 |
June | 111.33 | 23.60 | 209.33 | 24.15 | 4.83 | 24.19 |
July | 60.17 | 24.28 | 327.17 | 24.44 | 12.00 | 24.51 |
August | 50.33 | 24.35 | 361.50 | 24.35 | 13.17 | 24.43 |
September | 134.83 | 23.46 | 244.00 | 24.08 | 8.00 | 24.14 |
October | 317.33 | 22.71 | 105.17 | 23.20 | 3.33 | 23.23 |
November | 438.17 | 21.72 | 105.83 | 21.70 | 75.83 | 21.53 |
December | 458.50 | 21.09 | 197.50 | 20.90 | 189.50 | 20.75 |
Annual Sum or Average | 3308.50 | 22.05 | 2236.50 | 22.54 | 678.17 | 22.34 |
Minimum of Months | 50.33 | 20.88 | 61.83 | 20.62 | 2.00 | 20.47 |
Maximum of Months | 488.83 | 24.35 | 361.50 | 24.44 | 233.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.50 | 294.83 | 20.31 | 294.83 | 20.22 |
February | 439.33 | 21.16 | 154.33 | 20.92 | 153.00 | 20.77 |
March | 464.33 | 22.14 | 46.00 | 22.08 | 35.33 | 21.97 |
April | 317.83 | 22.79 | 70.83 | 23.10 | 3.00 | 23.10 |
May | 206.83 | 23.46 | 145.50 | 23.90 | 13.00 | 24.01 |
June | 96.17 | 23.66 | 208.17 | 24.17 | 5.67 | 24.23 |
July | 52.17 | 24.57 | 345.67 | 24.49 | 14.33 | 24.57 |
August | 48.00 | 24.18 | 366.00 | 24.33 | 10.33 | 24.39 |
September | 154.00 | 23.49 | 210.00 | 24.03 | 10.83 | 24.11 |
October | 393.67 | 22.55 | 39.17 | 22.74 | 0.67 | 22.74 |
November | 472.50 | 21.44 | 107.17 | 21.27 | 101.33 | 21.12 |
December | 497.00 | 20.82 | 236.17 | 20.61 | 236.17 | 20.51 |
Annual Sum or Average | 3643.83 | 21.86 | 2223.83 | 22.23 | 878.50 | 22.02 |
Minimum of Months | 48.00 | 20.50 | 39.17 | 20.31 | 0.67 | 20.22 |
Maximum of Months | 502.00 | 24.57 | 366.00 | 24.49 | 294.83 | 24.57 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07165 | 31.12831 | -0.0355 | 6.57919 |
February | 454.00000 | 23.81090 | 30.97198 | 0.16904 | 5.92828 |
March | 514.00000 | 24.20583 | 29.77086 | 0.29315 | 6.90824 |
April | 485.00000 | 24.38290 | 33.02166 | 0.38303 | 8.34076 |
May | 508.00000 | 24.41199 | 36.30337 | -0.4222 | 9.21108 |
June | 496.00000 | 24.41781 | 38.16248 | -0.3848 | 8.60915 |
July | 497.00000 | 24.53311 | 42.20307 | -0.3119 | 7.71779 |
August | 514.00000 | 24.44798 | 45.39216 | -0.3085 | 7.58016 |
September | 485.00000 | 24.49254 | 43.04820 | -0.3364 | 8.07107 |
October | 502.00000 | 24.41603 | 35.88552 | 0.41137 | 8.82431 |
November | 489.00000 | 24.10677 | 35.61796 | 0.29117 | 7.10551 |
December | 497.00000 | 23.69353 | 31.11070 | 0.13439 | 5.60668 |
Annual Sum or Average | 5943.00000 | 24.16809 | 36.08526 | -0.0119 | 7.55123 |
Minimum of Months | 454.00000 | 23.07165 | 29.77086 | -0.4222 | 5.60668 |
Maximum of Months | 514.00000 | 24.53311 | 45.39216 | 0.41137 | 9.21108 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.41550 | 34.10391 | -0.4027 | 9.91540 |
February | 454.00000 | 22.19823 | 34.41956 | -0.1936 | 6.93819 |
March | 514.00000 | 23.25624 | 32.92591 | 0.06959 | 5.61699 |
April | 485.00000 | 23.78010 | 34.83314 | 0.23120 | 6.52199 |
May | 508.00000 | 24.05156 | 37.86991 | -0.5653 | 12.03420 |
June | 496.00000 | 24.17087 | 39.40069 | -0.4916 | 10.28617 |
July | 497.00000 | 24.28248 | 43.27223 | -0.4187 | 8.96709 |
August | 514.00000 | 24.23904 | 46.43650 | -0.4052 | 8.69898 |
September | 485.00000 | 24.15970 | 44.66028 | -0.4753 | 10.07212 |
October | 502.00000 | 23.66296 | 38.84089 | 0.22393 | 6.50876 |
November | 489.00000 | 22.67291 | 39.66670 | -0.0400 | 6.14584 |
December | 497.00000 | 21.88938 | 34.85239 | -0.2726 | 7.25952 |
Annual Sum or Average | 5943.00000 | 23.32360 | 38.46491 | -0.2293 | 8.25958 |
Minimum of Months | 454.00000 | 21.41550 | 32.92591 | -0.5653 | 5.61699 |
Maximum of Months | 514.00000 | 24.28248 | 46.43650 | 0.23120 | 12.03420 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74064 | 35.08173 | -0.5849 | 14.23959 |
February | 454.00000 | 21.37437 | 35.56517 | -0.4045 | 10.39987 |
March | 514.00000 | 22.48436 | 34.31595 | -0.1196 | 6.39026 |
April | 485.00000 | 23.30037 | 35.82869 | 0.11274 | 6.18484 |
May | 508.00000 | 23.79293 | 38.51618 | -0.6586 | 14.95473 |
June | 496.00000 | 24.03587 | 39.63441 | -0.5411 | 11.49455 |
July | 497.00000 | 24.17379 | 43.35143 | -0.4565 | 9.70288 |
August | 514.00000 | 24.12476 | 46.49526 | -0.4490 | 9.56281 |
September | 485.00000 | 23.86714 | 45.53201 | -0.5859 | 12.87428 |
October | 502.00000 | 22.97426 | 40.65396 | 0.05173 | 6.06859 |
November | 489.00000 | 21.76071 | 41.62831 | -0.2700 | 8.11814 |
December | 497.00000 | 21.03118 | 36.27170 | -0.4979 | 11.30506 |
Annual Sum or Average | 5943.00000 | 22.81653 | 39.42733 | -0.3672 | 10.10749 |
Minimum of Months | 454.00000 | 20.74064 | 34.31595 | -0.6586 | 6.06859 |
Maximum of Months | 514.00000 | 24.17379 | 46.49526 | 0.11274 | 14.95473 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07712 | 36.88378 | -0.7830 | 20.44307 |
February | 454.00000 | 20.53008 | 37.53629 | -0.6304 | 15.92383 |
March | 514.00000 | 21.45373 | 37.23667 | -0.3629 | 9.34716 |
April | 485.00000 | 22.56812 | 37.99590 | -0.0558 | 7.02958 |
May | 508.00000 | 23.38495 | 40.14225 | -0.7850 | 20.27052 |
June | 496.00000 | 23.84183 | 40.70308 | -0.5941 | 13.49991 |
July | 497.00000 | 24.03900 | 44.00396 | -0.4837 | 10.80564 |
August | 514.00000 | 23.95099 | 47.61486 | -0.4951 | 11.10589 |
September | 485.00000 | 23.37970 | 47.91817 | -0.7498 | 18.73893 |
October | 502.00000 | 22.00697 | 44.07576 | -0.1737 | 7.26443 |
November | 489.00000 | 20.81522 | 44.29773 | -0.5107 | 12.41314 |
December | 497.00000 | 20.26565 | 38.45962 | -0.7183 | 17.45349 |
Annual Sum or Average | 5943.00000 | 22.20642 | 41.42557 | -0.5281 | 13.67279 |
Minimum of Months | 454.00000 | 20.07712 | 36.88378 | -0.7850 | 7.02958 |
Maximum of Months | 514.00000 | 24.03900 | 47.91817 | -0.0558 | 20.44307 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.12943 | 37.80011 | -0.7594 | 19.63968 |
February | 454.00000 | 20.82630 | 38.01560 | -0.5482 | 13.91781 |
March | 514.00000 | 21.92471 | 37.17406 | -0.2380 | 8.56288 |
April | 485.00000 | 23.07670 | 36.71111 | 0.09399 | 7.40986 |
May | 508.00000 | 23.64908 | 39.39637 | -0.6483 | 17.04619 |
June | 496.00000 | 24.06682 | 39.78442 | -0.4466 | 11.21959 |
July | 497.00000 | 24.23312 | 43.38599 | -0.3489 | 9.44106 |
August | 514.00000 | 24.13932 | 46.82742 | -0.3520 | 9.37799 |
September | 485.00000 | 23.63437 | 47.08944 | -0.6112 | 15.82054 |
October | 502.00000 | 22.39927 | 43.47805 | -0.0660 | 7.31955 |
November | 489.00000 | 20.96247 | 44.98799 | -0.4669 | 11.82173 |
December | 497.00000 | 20.34115 | 39.34463 | -0.6882 | 16.66654 |
Annual Sum or Average | 5943.00000 | 22.46193 | 41.18180 | -0.4227 | 12.33741 |
Minimum of Months | 454.00000 | 20.12943 | 36.71111 | -0.7594 | 7.31955 |
Maximum of Months | 514.00000 | 24.23312 | 47.08944 | 0.09399 | 19.63968 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.55864 | 36.03598 | -0.6443 | 17.21101 |
February | 454.00000 | 21.41843 | 35.46548 | -0.3919 | 12.39489 |
March | 514.00000 | 22.18795 | 34.87527 | -0.1574 | 8.84320 |
April | 485.00000 | 23.07283 | 35.79314 | 0.10108 | 8.12039 |
May | 508.00000 | 23.56760 | 38.98914 | -0.6743 | 18.42249 |
June | 496.00000 | 23.91682 | 40.02656 | -0.5270 | 13.12500 |
July | 497.00000 | 24.14386 | 43.35311 | -0.3894 | 10.42066 |
August | 514.00000 | 24.07387 | 46.66733 | -0.3754 | 10.16844 |
September | 485.00000 | 23.71314 | 45.94206 | -0.5444 | 15.03234 |
October | 502.00000 | 22.76122 | 41.14760 | 0.04328 | 8.24667 |
November | 489.00000 | 21.41501 | 42.76517 | -0.3519 | 11.04572 |
December | 497.00000 | 20.85264 | 37.14207 | -0.5534 | 14.86579 |
Annual Sum or Average | 5943.00000 | 22.65028 | 39.87546 | -0.3724 | 12.32466 |
Minimum of Months | 454.00000 | 20.55864 | 34.87527 | -0.6743 | 8.12039 |
Maximum of Months | 514.00000 | 24.14386 | 46.66733 | 0.10108 | 18.42249 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16586 | 37.69208 | -0.7523 | 19.59963 |
February | 454.00000 | 20.82695 | 37.78509 | -0.5501 | 14.56906 |
March | 514.00000 | 21.77360 | 37.09470 | -0.2741 | 9.16820 |
April | 485.00000 | 22.83452 | 37.46860 | 0.03455 | 7.85022 |
May | 508.00000 | 23.55720 | 39.83633 | -0.6724 | 18.68223 |
June | 496.00000 | 23.91577 | 40.63141 | -0.5136 | 12.82454 |
July | 497.00000 | 24.17494 | 43.57057 | -0.3529 | 10.09889 |
August | 514.00000 | 24.06321 | 47.27143 | -0.3846 | 10.30747 |
September | 485.00000 | 23.63392 | 47.18069 | -0.6068 | 16.23652 |
October | 502.00000 | 22.28721 | 43.73823 | -0.0925 | 7.51665 |
November | 489.00000 | 20.96616 | 44.93080 | -0.4681 | 11.94231 |
December | 497.00000 | 20.39459 | 39.20937 | -0.6785 | 16.67051 |
Annual Sum or Average | 5943.00000 | 22.39559 | 41.38556 | -0.4422 | 12.94212 |
Minimum of Months | 454.00000 | 20.16586 | 37.09470 | -0.7523 | 7.51665 |
Maximum of Months | 514.00000 | 24.17494 | 47.27143 | 0.03455 | 19.59963 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42335 | 36.66059 | -0.6793 | 16.07309 |
February | 454.00000 | 20.82059 | 37.42277 | -0.5431 | 12.37027 |
March | 514.00000 | 21.55811 | 37.02456 | -0.3329 | 7.98453 |
April | 485.00000 | 22.52981 | 39.05332 | -0.0687 | 6.17493 |
May | 508.00000 | 23.43493 | 40.72633 | -0.7930 | 19.38500 |
June | 496.00000 | 23.88436 | 41.22952 | -0.6061 | 13.17500 |
July | 497.00000 | 24.08924 | 44.44100 | -0.4911 | 10.36896 |
August | 514.00000 | 24.03479 | 47.96478 | -0.4851 | 10.32449 |
September | 485.00000 | 23.65640 | 47.44301 | -0.6641 | 15.07534 |
October | 502.00000 | 22.64819 | 42.49895 | -0.0168 | 5.79844 |
November | 489.00000 | 21.48009 | 42.97694 | -0.3209 | 8.32311 |
December | 497.00000 | 20.72039 | 37.83227 | -0.5717 | 12.30958 |
Annual Sum or Average | 5943.00000 | 22.45251 | 41.29356 | -0.4645 | 11.44816 |
Minimum of Months | 454.00000 | 20.42335 | 36.66059 | -0.7930 | 5.79844 |
Maximum of Months | 514.00000 | 24.08924 | 47.96478 | -0.0168 | 19.38500 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47338 | 37.64815 | -0.6575 | 15.44202 |
February | 454.00000 | 21.13669 | 37.95504 | -0.4552 | 10.62454 |
March | 514.00000 | 22.16112 | 36.94437 | -0.1786 | 6.84472 |
April | 485.00000 | 23.28087 | 37.36338 | 0.13518 | 6.68692 |
May | 508.00000 | 23.79464 | 39.56544 | -0.6241 | 14.96886 |
June | 496.00000 | 24.17969 | 39.81667 | -0.4318 | 10.08379 |
July | 497.00000 | 24.32446 | 43.54745 | -0.3400 | 8.54082 |
August | 514.00000 | 24.25408 | 46.84599 | -0.3238 | 8.28890 |
September | 485.00000 | 23.95590 | 46.31400 | -0.5074 | 11.92789 |
October | 502.00000 | 23.09252 | 41.67560 | 0.10415 | 6.33820 |
November | 489.00000 | 21.67390 | 43.63281 | -0.2683 | 7.93872 |
December | 497.00000 | 20.84501 | 38.71020 | -0.5334 | 11.60178 |
Annual Sum or Average | 5943.00000 | 22.77670 | 40.84986 | -0.3398 | 9.93820 |
Minimum of Months | 454.00000 | 20.47338 | 36.94437 | -0.6575 | 6.33820 |
Maximum of Months | 514.00000 | 24.32446 | 46.84599 | 0.13518 | 15.44202 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35454 | 34.24657 | -0.6490 | 15.93293 |
February | 454.00000 | 21.24132 | 34.13906 | -0.3863 | 10.69876 |
March | 514.00000 | 21.88952 | 33.74606 | -0.1950 | 7.80144 |
April | 485.00000 | 22.74790 | 36.00468 | 0.04021 | 7.31023 |
May | 508.00000 | 23.25690 | 39.41826 | -0.7714 | 20.51384 |
June | 496.00000 | 23.66956 | 40.59240 | -0.6128 | 14.99389 |
July | 497.00000 | 24.09500 | 43.78382 | -0.4174 | 10.43623 |
August | 514.00000 | 24.05428 | 47.10169 | -0.3792 | 9.78507 |
September | 485.00000 | 23.80305 | 45.36414 | -0.4944 | 13.19927 |
October | 502.00000 | 23.04146 | 39.10649 | 0.14106 | 7.69472 |
November | 489.00000 | 21.48453 | 40.23089 | -0.2781 | 9.06804 |
December | 497.00000 | 20.83267 | 35.03661 | -0.5011 | 12.44651 |
Annual Sum or Average | 5943.00000 | 22.54926 | 39.09590 | -0.3759 | 11.67254 |
Minimum of Months | 454.00000 | 20.35454 | 33.74606 | -0.7714 | 7.31023 |
Maximum of Months | 514.00000 | 24.09500 | 47.10169 | 0.14106 | 20.51384 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49615 | 37.59389 | -0.6524 | 15.37981 |
February | 454.00000 | 21.11740 | 37.86015 | -0.4597 | 11.07915 |
March | 514.00000 | 22.04187 | 36.91040 | -0.2074 | 7.20046 |
April | 485.00000 | 23.07818 | 37.93773 | 0.08252 | 6.76458 |
May | 508.00000 | 23.83975 | 39.52854 | -0.6061 | 14.64827 |
June | 496.00000 | 24.08391 | 40.49581 | -0.4820 | 10.88490 |
July | 497.00000 | 24.37890 | 43.25085 | -0.3056 | 8.14941 |
August | 514.00000 | 24.25493 | 46.99409 | -0.3323 | 8.39508 |
September | 485.00000 | 24.06215 | 45.97119 | -0.4702 | 11.16301 |
October | 502.00000 | 23.05267 | 41.84962 | 0.09364 | 6.37924 |
November | 489.00000 | 21.65452 | 43.64039 | -0.2732 | 8.06190 |
December | 497.00000 | 20.85345 | 38.67445 | -0.5314 | 11.68583 |
Annual Sum or Average | 5943.00000 | 22.75520 | 40.90785 | -0.3451 | 9.97890 |
Minimum of Months | 454.00000 | 20.49615 | 36.91040 | -0.6524 | 6.37924 |
Maximum of Months | 514.00000 | 24.37890 | 46.99409 | 0.09364 | 15.37981 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40626 | 36.47323 | -0.6689 | 16.15157 |
February | 454.00000 | 20.95641 | 36.86860 | -0.4956 | 11.95225 |
March | 514.00000 | 22.04580 | 36.19560 | -0.2063 | 6.97686 |
April | 485.00000 | 23.04966 | 37.06652 | 0.06395 | 6.28292 |
May | 508.00000 | 23.70165 | 39.32749 | -0.6759 | 15.72227 |
June | 496.00000 | 24.00956 | 40.27865 | -0.5351 | 11.45461 |
July | 497.00000 | 24.17067 | 43.77051 | -0.4390 | 9.42383 |
August | 514.00000 | 24.09786 | 47.32879 | -0.4430 | 9.56576 |
September | 485.00000 | 23.74731 | 46.80528 | -0.6204 | 14.00972 |
October | 502.00000 | 22.67952 | 42.38354 | -0.0049 | 6.08382 |
November | 489.00000 | 21.38396 | 43.10306 | -0.3454 | 9.01818 |
December | 497.00000 | 20.66881 | 37.74389 | -0.5810 | 12.86266 |
Annual Sum or Average | 5943.00000 | 22.58940 | 40.63275 | -0.4125 | 10.78378 |
Minimum of Months | 454.00000 | 20.40626 | 36.19560 | -0.6759 | 6.08382 |
Maximum of Months | 514.00000 | 24.17067 | 47.32879 | 0.06395 | 16.15157 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.35529 | 37.24433 | -0.6732 | 16.43659 |
February | 385.00000 | 21.19516 | 37.04327 | -0.4333 | 10.97511 |
March | 433.00000 | 22.33750 | 35.85604 | -0.1268 | 6.90289 |
April | 410.00000 | 23.40155 | 35.62113 | 0.16963 | 7.09086 |
May | 430.00000 | 23.89005 | 38.37863 | -0.5785 | 14.23919 |
June | 418.00000 | 24.22235 | 39.29650 | -0.4089 | 10.12137 |
July | 422.00000 | 24.40353 | 42.81412 | -0.3126 | 8.64650 |
August | 433.00000 | 24.28810 | 46.25744 | -0.3192 | 8.63159 |
September | 410.00000 | 23.93243 | 45.84642 | -0.5178 | 12.60969 |
October | 427.00000 | 22.90519 | 41.76200 | 0.06074 | 6.56798 |
November | 417.00000 | 21.47098 | 43.60612 | -0.3196 | 9.00134 |
December | 422.00000 | 20.69967 | 38.48627 | -0.5671 | 12.78696 |
Annual Sum or Average | 5034.00000 | 22.76774 | 40.20172 | -0.3354 | 10.33057 |
Minimum of Months | 385.00000 | 20.35529 | 35.62113 | -0.6732 | 6.56798 |
Maximum of Months | 433.00000 | 24.40353 | 46.25744 | 0.16963 | 16.43659 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.97343 | 35.43831 | -0.5148 | 13.48817 |
February | 454.00000 | 21.89616 | 34.62760 | -0.2498 | 9.66441 |
March | 514.00000 | 22.71666 | 33.79798 | -0.0156 | 7.21428 |
April | 485.00000 | 23.47833 | 34.93114 | 0.20453 | 7.71215 |
May | 508.00000 | 23.86107 | 38.23833 | -0.5728 | 14.18723 |
June | 496.00000 | 24.09073 | 39.61326 | -0.4676 | 10.94875 |
July | 497.00000 | 24.28540 | 43.08920 | -0.3439 | 8.89851 |
August | 514.00000 | 24.21247 | 46.40190 | -0.3277 | 8.69377 |
September | 485.00000 | 24.01605 | 45.03240 | -0.4354 | 11.28220 |
October | 502.00000 | 23.31119 | 39.67500 | 0.18645 | 7.85343 |
November | 489.00000 | 22.01405 | 41.43983 | -0.1826 | 8.57945 |
December | 497.00000 | 21.34691 | 36.19203 | -0.4012 | 11.00576 |
Annual Sum or Average | 5943.00000 | 23.02585 | 39.06663 | -0.2607 | 9.96392 |
Minimum of Months | 454.00000 | 20.97343 | 33.79798 | -0.5728 | 7.21428 |
Maximum of Months | 514.00000 | 24.28540 | 46.40190 | 0.20453 | 14.18723 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50420 | 37.31221 | -0.6367 | 15.46283 |
February | 454.00000 | 21.25684 | 37.07041 | -0.4157 | 11.03280 |
March | 514.00000 | 22.33898 | 35.97702 | -0.1241 | 7.07033 |
April | 485.00000 | 23.29620 | 36.51627 | 0.14946 | 7.25278 |
May | 508.00000 | 23.86644 | 38.98634 | -0.5665 | 14.26232 |
June | 496.00000 | 24.09007 | 40.15518 | -0.4539 | 10.66054 |
July | 497.00000 | 24.31502 | 43.27724 | -0.3075 | 8.62904 |
August | 514.00000 | 24.20851 | 46.95816 | -0.3344 | 8.78698 |
September | 485.00000 | 23.96626 | 46.10480 | -0.4886 | 12.07830 |
October | 502.00000 | 22.92185 | 42.07697 | 0.06803 | 6.62702 |
November | 489.00000 | 21.53397 | 43.69149 | -0.3038 | 8.82610 |
December | 497.00000 | 20.81556 | 38.47433 | -0.5388 | 12.30785 |
Annual Sum or Average | 5943.00000 | 22.77150 | 40.56889 | -0.3292 | 10.24377 |
Minimum of Months | 454.00000 | 20.50420 | 35.97702 | -0.6367 | 6.62702 |
Maximum of Months | 514.00000 | 24.31502 | 46.95816 | 0.14946 | 15.46283 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.526211E+11 | 0.00 | 424.28 | 150171.43 | 25-JAN-07:02 | 0.00 | 37.23 | 50.49 | 0.22 | 0.00 | 0.09 | 0.66 | 25-JAN-07:02 |
February | 0.281409E+11 | 0.00 | 326.61 | 153710.22 | 09-FEB-07:01 | 0.00 | 34.18 | 46.40 | 0.13 | 0.00 | 0.05 | 0.68 | 09-FEB-07:01 |
March | 0.112648E+11 | 0.00 | 292.96 | 152296.43 | 01-MAR-07:01 | 0.00 | 31.00 | 42.04 | 0.04 | 0.00 | 0.02 | 0.67 | 01-MAR-07:01 |
April | 0.439876E+10 | 0.00 | 174.17 | 124764.09 | 19-APR-06:02 | 0.00 | 29.96 | 36.82 | 0.02 | 0.00 | 0.01 | 0.55 | 19-APR-06:02 |
May | 0.135780E+10 | 0.00 | 79.29 | 64550.75 | 18-MAY-06:03 | 0.00 | 34.37 | 37.05 | 0.00 | 0.00 | 0.00 | 0.29 | 18-MAY-06:03 |
June | 0.313523E+09 | 0.00 | 26.37 | 11443.85 | 15-JUN-06:05 | 0.00 | 41.49 | 42.19 | 0.00 | 0.00 | 0.00 | 0.05 | 15-JUN-06:05 |
July | 52338127.33 | 0.00 | 62.34 | 9902.67 | 27-JUL-06:08 | 0.00 | 34.82 | 37.01 | 0.00 | 0.00 | 0.00 | 0.04 | 27-JUL-06:08 |
August | 74935531.34 | 0.00 | 116.94 | 10031.54 | 03-AUG-06:06 | 0.00 | 40.85 | 43.93 | 0.00 | 0.00 | 0.00 | 0.04 | 03-AUG-06:06 |
September | 0.382376E+09 | 0.00 | 69.81 | 30429.29 | 28-SEP-06:03 | 0.00 | 40.68 | 42.64 | 0.00 | 0.00 | 0.00 | 0.13 | 28-SEP-06:03 |
October | 0.315233E+10 | 0.00 | 155.39 | 116650.49 | 30-OCT-06:03 | 0.00 | 31.68 | 37.36 | 0.01 | 0.00 | 0.01 | 0.52 | 30-OCT-06:03 |
November | 0.199345E+11 | 0.00 | 307.02 | 143128.52 | 16-NOV-07:02 | 0.00 | 33.27 | 44.77 | 0.08 | 0.00 | 0.03 | 0.63 | 16-NOV-07:02 |
December | 0.400314E+11 | 0.00 | 384.08 | 146442.86 | 26-DEC-07:12 | 0.00 | 34.52 | 47.70 | 0.16 | 0.00 | 0.07 | 0.65 | 26-DEC-07:12 |
Annual Sum or Average | 0.161725E+12 | 0.00 | 2419.25 | 0.00 | 35.34 | 42.34 | 0.06 | 0.00 | 0.02 | ||||
Minimum of Months | 52338127.33 | 0.00 | 26.37 | 9902.67 | 0.00 | 29.96 | 36.82 | 0.00 | 0.00 | 0.00 | 0.04 | ||
Maximum of Months | 0.526211E+11 | 0.00 | 424.28 | 153710.22 | 0.00 | 41.49 | 50.49 | 0.22 | 0.00 | 0.09 | 0.68 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1258189.69 | 338915.97 | 0.33 | 1125441.30 | 132748.39 | 0.00 | 0.05 | 02-JAN-10:30 | 0.00 | 01-JAN-00:05 | 1070.81 | 02-JAN-10:30 | 959.52 | 02-JAN-10:30 | 111.29 | 02-JAN-10:30 | 288.38 | 02-JAN-10:30 | 0.00 |
February | 0.200641E+09 | 50082578.59 | 9.33 | 0.184550E+09 | 16091291.65 | 0.00 | 0.53 | 27-FEB-15:10 | 0.00 | 01-FEB-00:10 | 12969.88 | 27-FEB-15:10 | 12969.88 | 27-FEB-15:10 | 1251.39 | 27-FEB-17:13 | 3104.14 | 27-FEB-15:10 | 0.00 |
March | 0.530421E+09 | 0.137868E+09 | 54.30 | 0.476885E+09 | 53536247.75 | 0.00 | 0.45 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 10915.52 | 18-MAR-16:00 | 10915.52 | 18-MAR-16:00 | 1375.26 | 09-MAR-12:00 | 2663.64 | 18-MAR-16:00 | 0.00 |
April | 0.639404E+10 | 0.149428E+10 | 148.63 | 0.619764E+10 | 0.196397E+09 | 0.00 | 1.00 | 26-APR-12:10 | 0.00 | 01-APR-00:10 | 51578.74 | 27-APR-15:00 | 51578.74 | 27-APR-15:00 | 4113.06 | 28-APR-13:00 | 11763.75 | 27-APR-15:00 | 0.00 |
May | 0.800266E+10 | 0.183288E+10 | 178.24 | 0.721387E+10 | 0.788788E+09 | 0.00 | 1.00 | 03-MAY-15:50 | 0.00 | 01-MAY-00:10 | 47197.76 | 15-MAY-16:00 | 47197.76 | 15-MAY-16:00 | 6409.79 | 07-MAY-17:21 | 9928.28 | 15-MAY-16:00 | 0.00 |
June | 0.143724E+11 | 0.326573E+10 | 268.19 | 0.134310E+11 | 0.941381E+09 | 0.00 | 1.00 | 09-JUN-13:20 | 0.00 | 01-JUN-00:10 | 52946.67 | 28-JUN-15:30 | 52946.67 | 28-JUN-15:30 | 10094.15 | 12-JUN-06:02 | 11737.78 | 28-JUN-15:30 | 0.00 |
July | 0.276307E+11 | 0.618611E+10 | 353.97 | 0.245183E+11 | 0.311234E+10 | 0.00 | 1.00 | 06-JUL-14:05 | 0.00 | 01-JUL-00:10 | 72039.91 | 31-JUL-15:50 | 67015.11 | 24-JUL-15:00 | 17354.32 | 31-JUL-06:03 | 17649.22 | 24-JUL-15:00 | 0.00 |
August | 0.375451E+11 | 0.846185E+10 | 376.66 | 0.329391E+11 | 0.460594E+10 | 0.00 | 1.00 | 01-AUG-15:50 | 0.00 | 01-AUG-00:10 | 71006.32 | 10-AUG-15:40 | 67254.75 | 10-AUG-15:50 | 17160.10 | 30-AUG-13:00 | 17819.57 | 10-AUG-15:50 | 0.00 |
September | 0.139503E+11 | 0.311537E+10 | 233.51 | 0.117035E+11 | 0.224679E+10 | 0.00 | 1.00 | 08-SEP-13:30 | 0.00 | 01-SEP-00:10 | 58396.42 | 12-SEP-16:00 | 54909.94 | 12-SEP-15:20 | 15156.14 | 14-SEP-13:00 | 12454.47 | 12-SEP-16:00 | 0.00 |
October | 0.266424E+10 | 0.632768E+09 | 87.57 | 0.252042E+10 | 0.143822E+09 | 0.00 | 1.00 | 04-OCT-13:05 | 0.00 | 01-OCT-00:10 | 35126.82 | 04-OCT-15:00 | 35126.82 | 04-OCT-15:00 | 2667.09 | 08-OCT-14:00 | 7373.66 | 04-OCT-15:00 | 0.00 |
November | 0.362717E+09 | 86041694.28 | 12.71 | 0.252449E+09 | 0.110268E+09 | 0.00 | 0.73 | 04-NOV-15:00 | 0.00 | 01-NOV-00:10 | 18890.90 | 04-NOV-15:00 | 14516.46 | 04-NOV-15:00 | 5290.35 | 04-NOV-16:00 | 4284.00 | 04-NOV-15:00 | 0.00 |
December | 6678546.16 | 1769724.90 | 0.90 | 6169609.10 | 508937.06 | 0.00 | 0.16 | 05-DEC-12:00 | 0.00 | 01-DEC-00:10 | 3550.29 | 05-DEC-12:00 | 3369.61 | 05-DEC-12:00 | 413.80 | 05-DEC-12:02 | 931.80 | 05-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.111661E+12 | 0.252651E+11 | 1724.36 | 0.994451E+11 | 0.122160E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1258189.69 | 338915.97 | 0.33 | 1125441.30 | 132748.39 | 0.00 | 0.05 | 0.00 | 1070.81 | 959.52 | 111.29 | 288.38 | 0.00 | ||||||
Maximum of Months | 0.375451E+11 | 0.846185E+10 | 376.66 | 0.329391E+11 | 0.460594E+10 | 0.00 | 1.00 | 0.00 | 72039.91 | 67254.75 | 17354.32 | 17819.57 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 203097.43 | 54479.62 | 0.04 | 163444.72 | 39652.71 | 0.00 | 0.07 | 11-JAN-07:05 | 0.00 | 01-JAN-00:05 | 1353.98 | 11-JAN-07:05 | 1089.63 | 11-JAN-07:05 | 264.35 | 11-JAN-07:05 | 363.20 | 11-JAN-07:05 | 0.00 |
February | 0.182989E+09 | 45717435.15 | 8.04 | 0.167667E+09 | 15322261.10 | 0.00 | 0.56 | 27-FEB-15:05 | 0.00 | 01-FEB-00:10 | 12920.73 | 27-FEB-15:05 | 12920.73 | 27-FEB-15:05 | 1214.30 | 27-FEB-17:13 | 3068.30 | 27-FEB-15:05 | 0.00 |
March | 0.279433E+09 | 71371477.28 | 23.08 | 0.249260E+09 | 30172849.88 | 0.00 | 0.49 | 18-MAR-14:05 | 0.00 | 01-MAR-00:10 | 11221.09 | 18-MAR-14:05 | 11221.09 | 18-MAR-14:05 | 1204.21 | 09-MAR-12:00 | 2710.37 | 18-MAR-14:05 | 0.00 |
April | 0.343582E+10 | 0.792603E+09 | 75.42 | 0.330552E+10 | 0.130299E+09 | 0.00 | 1.00 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 50319.97 | 27-APR-14:05 | 50319.97 | 27-APR-14:05 | 4256.11 | 28-APR-13:00 | 11298.07 | 27-APR-15:00 | 0.00 |
May | 0.712293E+10 | 0.162291E+10 | 163.64 | 0.640224E+10 | 0.720686E+09 | 0.00 | 1.00 | 03-MAY-15:20 | 0.00 | 01-MAY-00:10 | 44026.64 | 04-MAY-15:00 | 44026.64 | 04-MAY-15:00 | 7422.13 | 07-MAY-16:01 | 9368.79 | 04-MAY-15:00 | 0.00 |
June | 0.130912E+11 | 0.298318E+10 | 272.87 | 0.122071E+11 | 0.884044E+09 | 0.00 | 1.00 | 09-JUN-13:00 | 0.00 | 01-JUN-00:10 | 49084.63 | 28-JUN-15:30 | 49084.63 | 28-JUN-15:30 | 9245.26 | 12-JUN-06:02 | 10881.91 | 28-JUN-15:30 | 0.00 |
July | 0.247676E+11 | 0.556146E+10 | 357.50 | 0.219924E+11 | 0.277523E+10 | 0.00 | 1.00 | 06-JUL-14:05 | 0.00 | 01-JUL-00:10 | 67971.42 | 31-JUL-14:05 | 60862.30 | 31-JUL-14:05 | 17404.82 | 31-JUL-06:03 | 15877.90 | 31-JUL-14:05 | 0.00 |
August | 0.327368E+11 | 0.741084E+10 | 378.24 | 0.287115E+11 | 0.402525E+10 | 0.00 | 1.00 | 04-AUG-14:00 | 0.00 | 01-AUG-00:10 | 67015.65 | 10-AUG-14:05 | 61082.37 | 10-AUG-15:10 | 16137.16 | 30-AUG-13:00 | 16602.53 | 29-AUG-15:30 | 0.00 |
September | 0.121953E+11 | 0.273499E+10 | 233.84 | 0.101700E+11 | 0.202524E+10 | 0.00 | 1.00 | 08-SEP-13:00 | 0.00 | 01-SEP-00:10 | 54286.94 | 13-SEP-14:05 | 49397.74 | 12-SEP-14:05 | 15244.36 | 14-SEP-13:00 | 11441.02 | 13-SEP-14:05 | 0.00 |
October | 0.158148E+10 | 0.374436E+09 | 59.25 | 0.148336E+10 | 98118696.90 | 0.00 | 1.00 | 04-OCT-13:10 | 0.00 | 01-OCT-00:10 | 31703.47 | 04-OCT-15:00 | 31703.47 | 04-OCT-15:00 | 2495.61 | 01-OCT-13:25 | 6655.52 | 04-OCT-15:00 | 0.00 |
November | 0.340540E+09 | 79783181.58 | 8.77 | 0.239897E+09 | 0.100643E+09 | 0.00 | 0.77 | 04-NOV-14:05 | 0.00 | 01-NOV-00:10 | 18844.83 | 04-NOV-14:05 | 14933.29 | 04-NOV-14:05 | 4815.39 | 04-NOV-16:00 | 4226.75 | 04-NOV-14:05 | 0.00 |
December | 235862.49 | 63114.19 | 0.04 | 161238.58 | 74623.91 | 0.00 | 0.08 | 29-DEC-07:05 | 0.00 | 01-DEC-00:10 | 1572.42 | 29-DEC-07:05 | 1074.92 | 29-DEC-07:05 | 497.49 | 29-DEC-07:05 | 420.76 | 29-DEC-07:05 | 0.00 |
Annual Sum or Average | 0.957345E+11 | 0.216774E+11 | 1580.73 | 0.849293E+11 | 0.108051E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 203097.43 | 54479.62 | 0.04 | 161238.58 | 39652.71 | 0.00 | 0.07 | 0.00 | 1353.98 | 1074.92 | 264.35 | 363.20 | 0.00 | ||||||
Maximum of Months | 0.327368E+11 | 0.741084E+10 | 378.24 | 0.287115E+11 | 0.402525E+10 | 0.00 | 1.00 | 0.00 | 67971.42 | 61082.37 | 17404.82 | 16602.53 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.187718E+09 | 47247022.02 | 8.00 | 0.166529E+09 | 21188580.80 | 0.00 | 0.48 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 12047.39 | 27-FEB-15:00 | 12047.39 | 27-FEB-15:00 | 1414.89 | 27-FEB-17:05 | 2923.19 | 27-FEB-15:00 | 0.00 |
March | 0.421801E+09 | 0.107590E+09 | 28.27 | 0.384852E+09 | 36949161.79 | 0.00 | 0.45 | 01-MAR-15:00 | 0.00 | 01-MAR-00:10 | 11377.32 | 01-MAR-15:00 | 11377.32 | 01-MAR-15:00 | 1329.15 | 09-MAR-12:00 | 2777.46 | 01-MAR-15:00 | 0.00 |
April | 0.364843E+10 | 0.844071E+09 | 73.25 | 0.348248E+10 | 0.165942E+09 | 0.00 | 1.00 | 26-APR-13:05 | 0.00 | 01-APR-00:10 | 57162.53 | 27-APR-14:40 | 57162.53 | 27-APR-14:40 | 4043.58 | 28-APR-13:00 | 12968.88 | 27-APR-15:00 | 0.00 |
May | 0.744064E+10 | 0.170126E+10 | 162.58 | 0.661351E+10 | 0.827125E+09 | 0.00 | 1.00 | 03-MAY-15:50 | 0.00 | 01-MAY-00:10 | 47729.89 | 04-MAY-15:00 | 47729.89 | 04-MAY-15:00 | 6706.77 | 07-MAY-16:12 | 10157.66 | 04-MAY-15:00 | 0.00 |
June | 0.137330E+11 | 0.314326E+10 | 271.00 | 0.127004E+11 | 0.103258E+10 | 0.00 | 1.00 | 09-JUN-13:05 | 0.00 | 01-JUN-00:10 | 56945.21 | 28-JUN-15:20 | 56945.21 | 28-JUN-15:20 | 5390.05 | 12-JUN-12:40 | 12623.16 | 28-JUN-15:20 | 0.00 |
July | 0.263174E+11 | 0.593238E+10 | 356.02 | 0.231729E+11 | 0.314444E+10 | 0.00 | 1.00 | 06-JUL-14:40 | 0.00 | 01-JUL-00:10 | 74463.78 | 31-JUL-14:40 | 67737.06 | 31-JUL-14:50 | 13207.91 | 31-JUL-10:30 | 17713.48 | 24-JUL-15:00 | 0.00 |
August | 0.343100E+11 | 0.781647E+10 | 377.72 | 0.299547E+11 | 0.435537E+10 | 0.00 | 1.00 | 06-AUG-15:22 | 0.00 | 01-AUG-00:10 | 74478.81 | 10-AUG-14:50 | 69963.55 | 10-AUG-15:20 | 16116.48 | 30-AUG-13:00 | 18371.98 | 29-AUG-15:20 | 0.00 |
September | 0.122129E+11 | 0.275660E+10 | 230.25 | 0.100581E+11 | 0.215482E+10 | 0.00 | 1.00 | 08-SEP-14:00 | 0.00 | 01-SEP-00:10 | 53643.15 | 14-SEP-13:30 | 49884.37 | 12-SEP-15:20 | 14681.18 | 14-SEP-13:00 | 11315.44 | 14-SEP-13:30 | 0.00 |
October | 0.144981E+10 | 0.347861E+09 | 55.89 | 0.134149E+10 | 0.108313E+09 | 0.00 | 1.00 | 04-OCT-14:20 | 0.00 | 01-OCT-00:10 | 31099.77 | 04-OCT-15:00 | 31099.77 | 04-OCT-15:00 | 4238.19 | 08-OCT-13:32 | 6530.33 | 04-OCT-15:00 | 0.00 |
November | 0.346211E+09 | 81951757.03 | 7.71 | 0.235736E+09 | 0.110475E+09 | 0.00 | 0.70 | 04-NOV-14:20 | 0.00 | 01-NOV-00:10 | 18724.29 | 04-NOV-14:20 | 14028.89 | 04-NOV-14:20 | 5358.19 | 04-NOV-13:00 | 4284.07 | 04-NOV-14:20 | 0.00 |
December | 68427.90 | 18594.94 | 0.08 | 51442.45 | 16985.45 | 0.00 | 0.01 | 18-DEC-06:10 | 0.00 | 01-DEC-00:10 | 228.09 | 18-DEC-06:10 | 171.47 | 18-DEC-06:10 | 56.62 | 18-DEC-06:10 | 61.98 | 18-DEC-06:10 | 0.00 |
Annual Sum or Average | 0.100068E+12 | 0.227787E+11 | 1570.77 | 0.881107E+11 | 0.119572E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.343100E+11 | 0.781647E+10 | 377.72 | 0.299547E+11 | 0.435537E+10 | 0.00 | 1.00 | 0.00 | 74478.81 | 69963.55 | 16116.48 | 18371.98 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 11.97 | 1381.90 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 85.44 | 1231.56 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 245.84 | 1032.74 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 516.88 | 843.63 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 822.10 | 692.05 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 950.58 | 538.16 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1021.23 | 485.57 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 842.93 | 473.98 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 490.23 | 698.42 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 207.16 | 914.54 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 45.35 | 1119.49 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 6.70 | 1389.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 439.40 | 898.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 6.70 | 473.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1021.23 | 1389.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 97.73 | 875.15 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 319.15 | 778.29 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 593.84 | 663.45 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1110.64 | 546.41 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1237.99 | 467.61 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1591.82 | 369.03 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1548.85 | 326.71 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1575.90 | 318.06 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1038.72 | 452.28 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 565.59 | 592.31 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 166.84 | 721.05 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 121.75 | 889.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 833.34 | 582.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 97.73 | 318.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1591.82 | 889.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 958.23 | 1257.39 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1675.21 | 1152.02 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1874.74 | 1028.48 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2088.70 | 889.45 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1924.67 | 751.10 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1795.54 | 597.85 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2163.51 | 542.53 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2405.68 | 522.86 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2505.15 | 718.38 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2079.08 | 913.66 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1041.88 | 1066.55 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1118.42 | 1298.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1803.01 | 893.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 958.23 | 522.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2505.15 | 1298.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 121.56 | 882.36 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 352.05 | 789.35 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 579.63 | 677.99 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1050.98 | 574.27 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1474.44 | 490.32 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1447.90 | 388.95 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1962.21 | 357.92 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1648.21 | 347.69 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1236.49 | 478.61 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 569.11 | 609.40 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 174.82 | 725.02 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 142.78 | 899.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 900.27 | 600.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 121.56 | 347.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1962.21 | 899.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.47 | 484.58 | 0.00 | 0.00 | 0.00 |
February | 124.59 | 0.00 | 124.59 | 27.62 | 430.97 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 83.94 | 353.80 | 0.00 | 0.00 | 0.00 |
April | 259.76 | 0.92 | 258.84 | 178.63 | 283.28 | 0.00 | 0.00 | 0.00 |
May | 334.25 | 9.93 | 324.32 | 281.21 | 232.69 | 0.00 | 0.00 | 0.00 |
June | 351.46 | 23.21 | 328.25 | 323.68 | 180.66 | 0.00 | 0.00 | 0.00 |
July | 334.04 | 26.19 | 307.85 | 346.21 | 163.45 | 0.00 | 0.00 | 0.00 |
August | 270.41 | 7.31 | 263.10 | 284.56 | 160.99 | 0.00 | 0.00 | 0.00 |
September | 210.04 | 0.06 | 209.98 | 163.88 | 243.19 | 0.00 | 0.00 | 0.00 |
October | 143.91 | 0.00 | 143.91 | 64.93 | 330.29 | 0.00 | 0.00 | 0.00 |
November | 90.65 | 0.00 | 90.65 | 12.42 | 410.24 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.41 | 498.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.63 | 5.68 | 198.95 | 148.41 | 313.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.41 | 160.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.46 | 26.19 | 328.25 | 346.21 | 498.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.47 | 484.61 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 27.62 | 430.99 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 83.94 | 353.83 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 178.64 | 283.29 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 281.21 | 232.71 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 323.69 | 180.67 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 346.23 | 163.46 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 284.58 | 161.00 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 163.89 | 243.21 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 64.93 | 330.31 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 12.42 | 410.27 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.41 | 498.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 148.41 | 313.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.41 | 161.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 346.23 | 498.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 80.07 | 0.00 | 80.07 | 3.47 | 484.61 | 0.00 | 0.00 | 0.00 |
February | 124.60 | 0.00 | 124.60 | 27.62 | 430.99 | 0.00 | 0.00 | 0.00 |
March | 183.57 | 0.00 | 183.57 | 83.94 | 353.83 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 0.92 | 258.85 | 178.64 | 283.29 | 0.00 | 0.00 | 0.00 |
May | 334.26 | 9.93 | 324.33 | 281.21 | 232.71 | 0.00 | 0.00 | 0.00 |
June | 351.47 | 23.21 | 328.26 | 323.69 | 180.67 | 0.00 | 0.00 | 0.00 |
July | 334.05 | 26.19 | 307.86 | 346.23 | 163.46 | 0.00 | 0.00 | 0.00 |
August | 270.42 | 7.31 | 263.11 | 284.58 | 161.00 | 0.00 | 0.00 | 0.00 |
September | 210.05 | 0.06 | 209.99 | 163.89 | 243.21 | 0.00 | 0.00 | 0.00 |
October | 143.92 | 0.00 | 143.92 | 64.93 | 330.31 | 0.00 | 0.00 | 0.00 |
November | 90.66 | 0.00 | 90.66 | 12.42 | 410.27 | 0.00 | 0.00 | 0.00 |
December | 68.04 | 0.00 | 68.04 | 1.41 | 498.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.64 | 5.68 | 198.96 | 148.41 | 313.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.04 | 0.00 | 68.04 | 1.41 | 161.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.47 | 26.19 | 328.26 | 346.23 | 498.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 247.55 | 62.76 | 184.78 | 91.25 | 885.24 | 0.00 | 0.00 | 0.00 |
February | 454.22 | 161.21 | 293.01 | 303.72 | 789.27 | 0.00 | 0.00 | 0.00 |
March | 678.19 | 245.51 | 432.68 | 574.60 | 666.10 | 0.00 | 0.00 | 0.00 |
April | 1051.30 | 436.83 | 614.47 | 1076.31 | 544.65 | 0.00 | 0.00 | 0.00 |
May | 1118.68 | 388.94 | 729.74 | 1201.84 | 463.01 | 0.00 | 0.00 | 0.00 |
June | 1339.75 | 582.93 | 756.82 | 1543.07 | 367.81 | 0.00 | 0.00 | 0.00 |
July | 1247.62 | 560.00 | 687.62 | 1500.18 | 324.48 | 0.00 | 0.00 | 0.00 |
August | 1226.23 | 613.43 | 612.80 | 1522.86 | 320.68 | 0.00 | 0.00 | 0.00 |
September | 906.62 | 418.14 | 488.48 | 999.30 | 462.89 | 0.00 | 0.00 | 0.00 |
October | 590.93 | 251.09 | 339.84 | 535.20 | 625.31 | 0.00 | 0.00 | 0.00 |
November | 289.64 | 81.77 | 207.87 | 151.79 | 764.12 | 0.00 | 0.00 | 0.00 |
December | 237.57 | 76.48 | 161.09 | 111.73 | 921.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 783.80 | 323.97 | 459.83 | 803.52 | 593.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 237.57 | 62.76 | 161.09 | 91.25 | 320.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1339.75 | 613.43 | 756.82 | 1543.07 | 921.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.79 | 2.48 | 7.31 | 3.61 | 35.00 | 0.00 | 0.00 | 0.00 |
February | 17.96 | 6.37 | 11.59 | 12.01 | 31.21 | 0.00 | 0.00 | 0.00 |
March | 26.81 | 9.71 | 17.11 | 22.72 | 26.34 | 0.00 | 0.00 | 0.00 |
April | 41.57 | 17.27 | 24.30 | 42.56 | 21.53 | 0.00 | 0.00 | 0.00 |
May | 44.23 | 15.38 | 28.85 | 47.52 | 18.31 | 0.00 | 0.00 | 0.00 |
June | 52.97 | 23.05 | 29.92 | 61.01 | 14.54 | 0.00 | 0.00 | 0.00 |
July | 49.33 | 22.14 | 27.19 | 59.32 | 12.83 | 0.00 | 0.00 | 0.00 |
August | 48.48 | 24.25 | 24.23 | 60.21 | 12.68 | 0.00 | 0.00 | 0.00 |
September | 35.85 | 16.53 | 19.31 | 39.51 | 18.30 | 0.00 | 0.00 | 0.00 |
October | 23.36 | 9.93 | 13.44 | 21.16 | 24.72 | 0.00 | 0.00 | 0.00 |
November | 11.45 | 3.23 | 8.22 | 6.00 | 30.21 | 0.00 | 0.00 | 0.00 |
December | 9.39 | 3.02 | 6.37 | 4.42 | 36.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.99 | 12.81 | 18.18 | 31.77 | 23.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.39 | 2.48 | 6.37 | 3.61 | 12.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.97 | 24.25 | 29.92 | 61.01 | 36.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 321.93 | 438.41 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 562.24 | 407.20 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 633.58 | 358.51 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 707.82 | 303.32 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 654.19 | 253.72 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 610.60 | 201.49 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 729.92 | 185.87 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 808.50 | 182.42 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 838.54 | 256.34 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 693.55 | 334.95 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 346.38 | 386.84 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 372.73 | 462.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 606.82 | 313.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 321.93 | 182.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 838.54 | 462.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.78 | 210.08 | 143.71 | 321.93 | 438.41 | 0.00 | 0.00 | 0.00 |
February | 544.07 | 336.78 | 207.28 | 562.24 | 407.20 | 0.00 | 0.00 | 0.00 |
March | 585.26 | 312.11 | 273.15 | 633.58 | 358.51 | 0.00 | 0.00 | 0.00 |
April | 617.92 | 268.30 | 349.63 | 707.82 | 303.32 | 0.00 | 0.00 | 0.00 |
May | 565.01 | 168.32 | 396.69 | 654.19 | 253.72 | 0.00 | 0.00 | 0.00 |
June | 516.93 | 138.79 | 378.14 | 610.60 | 201.49 | 0.00 | 0.00 | 0.00 |
July | 563.74 | 206.47 | 357.27 | 729.92 | 185.87 | 0.00 | 0.00 | 0.00 |
August | 605.66 | 282.43 | 323.23 | 808.50 | 182.42 | 0.00 | 0.00 | 0.00 |
September | 671.05 | 370.57 | 300.48 | 838.54 | 256.34 | 0.00 | 0.00 | 0.00 |
October | 607.86 | 375.31 | 232.55 | 693.55 | 334.95 | 0.00 | 0.00 | 0.00 |
November | 359.38 | 205.96 | 153.43 | 346.38 | 386.84 | 0.00 | 0.00 | 0.00 |
December | 376.02 | 243.34 | 132.68 | 372.73 | 462.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.33 | 259.39 | 270.94 | 606.82 | 313.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.78 | 138.79 | 132.68 | 321.93 | 182.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.05 | 375.31 | 396.69 | 838.54 | 462.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 353.76 | 210.07 | 143.70 | 321.91 | 438.38 | 0.00 | 0.00 | 0.00 |
February | 544.03 | 336.76 | 207.27 | 562.20 | 407.18 | 0.00 | 0.00 | 0.00 |
March | 585.22 | 312.09 | 273.13 | 633.54 | 358.49 | 0.00 | 0.00 | 0.00 |
April | 617.88 | 268.28 | 349.60 | 707.77 | 303.30 | 0.00 | 0.00 | 0.00 |
May | 564.98 | 168.31 | 396.67 | 654.15 | 253.70 | 0.00 | 0.00 | 0.00 |
June | 516.90 | 138.78 | 378.12 | 610.56 | 201.48 | 0.00 | 0.00 | 0.00 |
July | 563.70 | 206.46 | 357.25 | 729.87 | 185.86 | 0.00 | 0.00 | 0.00 |
August | 605.63 | 282.41 | 323.21 | 808.45 | 182.41 | 0.00 | 0.00 | 0.00 |
September | 671.01 | 370.55 | 300.46 | 838.49 | 256.32 | 0.00 | 0.00 | 0.00 |
October | 607.82 | 375.28 | 232.54 | 693.50 | 334.93 | 0.00 | 0.00 | 0.00 |
November | 359.36 | 205.94 | 153.42 | 346.36 | 386.81 | 0.00 | 0.00 | 0.00 |
December | 376.00 | 243.32 | 132.67 | 372.71 | 462.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.30 | 259.38 | 270.92 | 606.78 | 313.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 353.76 | 138.78 | 132.67 | 321.91 | 182.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 671.01 | 375.28 | 396.67 | 838.49 | 462.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.10 | 76.99 | 184.11 | 116.66 | 893.82 | 0.00 | 0.00 | 0.00 |
February | 468.13 | 175.94 | 292.20 | 339.64 | 802.67 | 0.00 | 0.00 | 0.00 |
March | 655.97 | 221.41 | 434.57 | 563.36 | 682.54 | 0.00 | 0.00 | 0.00 |
April | 998.00 | 381.57 | 616.42 | 1023.47 | 571.32 | 0.00 | 0.00 | 0.00 |
May | 1284.19 | 521.69 | 762.49 | 1432.05 | 491.77 | 0.00 | 0.00 | 0.00 |
June | 1235.04 | 479.52 | 755.51 | 1407.79 | 388.16 | 0.00 | 0.00 | 0.00 |
July | 1525.72 | 801.99 | 723.73 | 1900.34 | 363.12 | 0.00 | 0.00 | 0.00 |
August | 1262.13 | 644.48 | 617.65 | 1594.53 | 353.56 | 0.00 | 0.00 | 0.00 |
September | 1027.82 | 493.17 | 534.65 | 1190.80 | 494.40 | 0.00 | 0.00 | 0.00 |
October | 585.14 | 238.42 | 346.72 | 540.32 | 645.10 | 0.00 | 0.00 | 0.00 |
November | 291.40 | 82.19 | 209.21 | 161.40 | 769.15 | 0.00 | 0.00 | 0.00 |
December | 244.97 | 83.95 | 161.03 | 135.16 | 932.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.11 | 351.44 | 470.67 | 870.60 | 614.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 244.97 | 76.99 | 161.03 | 116.66 | 353.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1525.72 | 801.99 | 762.49 | 1900.34 | 932.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.32 | 3.04 | 7.28 | 4.61 | 35.34 | 0.00 | 0.00 | 0.00 |
February | 18.51 | 6.96 | 11.55 | 13.43 | 31.74 | 0.00 | 0.00 | 0.00 |
March | 25.94 | 8.75 | 17.18 | 22.27 | 26.99 | 0.00 | 0.00 | 0.00 |
April | 39.46 | 15.09 | 24.37 | 40.47 | 22.59 | 0.00 | 0.00 | 0.00 |
May | 50.78 | 20.63 | 30.15 | 56.62 | 19.44 | 0.00 | 0.00 | 0.00 |
June | 48.83 | 18.96 | 29.87 | 55.66 | 15.35 | 0.00 | 0.00 | 0.00 |
July | 60.33 | 31.71 | 28.62 | 75.14 | 14.36 | 0.00 | 0.00 | 0.00 |
August | 49.90 | 25.48 | 24.42 | 63.05 | 13.98 | 0.00 | 0.00 | 0.00 |
September | 40.64 | 19.50 | 21.14 | 47.08 | 19.55 | 0.00 | 0.00 | 0.00 |
October | 23.14 | 9.43 | 13.71 | 21.36 | 25.51 | 0.00 | 0.00 | 0.00 |
November | 11.52 | 3.25 | 8.27 | 6.38 | 30.41 | 0.00 | 0.00 | 0.00 |
December | 9.69 | 3.32 | 6.37 | 5.34 | 36.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.51 | 13.90 | 18.61 | 34.42 | 24.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.69 | 3.04 | 6.37 | 4.61 | 13.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.33 | 31.71 | 30.15 | 75.14 | 36.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 240.22 | 0.00 | 240.22 | 9.14 | 1467.83 | 0.00 | 0.00 | 0.00 |
February | 373.79 | 0.00 | 373.79 | 74.87 | 1321.38 | 0.00 | 0.00 | 0.00 |
March | 550.72 | 0.00 | 550.72 | 227.36 | 1111.92 | 0.00 | 0.00 | 0.00 |
April | 779.33 | 2.76 | 776.56 | 499.86 | 897.62 | 0.00 | 0.00 | 0.00 |
May | 1002.80 | 29.79 | 973.01 | 809.91 | 727.62 | 0.00 | 0.00 | 0.00 |
June | 1054.42 | 69.63 | 984.79 | 944.32 | 560.67 | 0.00 | 0.00 | 0.00 |
July | 1002.17 | 78.57 | 923.59 | 1018.37 | 504.54 | 0.00 | 0.00 | 0.00 |
August | 811.26 | 21.93 | 789.33 | 838.22 | 494.99 | 0.00 | 0.00 | 0.00 |
September | 630.16 | 0.19 | 629.97 | 478.80 | 742.50 | 0.00 | 0.00 | 0.00 |
October | 431.76 | 0.00 | 431.76 | 188.20 | 995.34 | 0.00 | 0.00 | 0.00 |
November | 271.97 | 0.00 | 271.97 | 36.14 | 1219.50 | 0.00 | 0.00 | 0.00 |
December | 204.13 | 0.00 | 204.13 | 3.97 | 1492.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 613.91 | 17.03 | 596.88 | 429.64 | 959.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.13 | 0.00 | 204.13 | 3.97 | 494.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.42 | 78.57 | 984.79 | 1018.37 | 1492.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 257.34 | 65.24 | 192.09 | 91.91 | 929.09 | 0.00 | 0.00 | 0.00 |
February | 472.19 | 167.59 | 304.60 | 304.75 | 834.49 | 0.00 | 0.00 | 0.00 |
March | 705.01 | 255.22 | 449.79 | 576.98 | 712.95 | 0.00 | 0.00 | 0.00 |
April | 1092.89 | 454.11 | 638.78 | 1096.59 | 578.05 | 0.00 | 0.00 | 0.00 |
May | 1162.93 | 404.32 | 758.61 | 1228.74 | 489.88 | 0.00 | 0.00 | 0.00 |
June | 1392.74 | 605.99 | 786.75 | 1587.04 | 383.45 | 0.00 | 0.00 | 0.00 |
July | 1296.96 | 582.15 | 714.81 | 1544.67 | 338.26 | 0.00 | 0.00 | 0.00 |
August | 1274.74 | 637.70 | 637.04 | 1571.32 | 330.71 | 0.00 | 0.00 | 0.00 |
September | 942.48 | 434.68 | 507.80 | 1028.78 | 478.55 | 0.00 | 0.00 | 0.00 |
October | 614.31 | 261.02 | 353.28 | 549.43 | 641.72 | 0.00 | 0.00 | 0.00 |
November | 301.10 | 85.00 | 216.10 | 155.14 | 785.70 | 0.00 | 0.00 | 0.00 |
December | 246.97 | 79.51 | 167.46 | 114.32 | 955.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 814.80 | 336.78 | 478.02 | 823.45 | 620.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 246.97 | 65.24 | 167.46 | 91.91 | 330.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1392.74 | 637.70 | 786.75 | 1587.04 | 955.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1061.37 | 630.25 | 431.13 | 942.37 | 1335.50 | 0.00 | 0.00 | 0.00 |
February | 1632.23 | 1010.37 | 621.86 | 1653.49 | 1231.64 | 0.00 | 0.00 | 0.00 |
March | 1755.81 | 936.35 | 819.45 | 1858.08 | 1102.25 | 0.00 | 0.00 | 0.00 |
April | 1853.80 | 804.91 | 1048.89 | 2076.67 | 940.69 | 0.00 | 0.00 | 0.00 |
May | 1695.06 | 504.98 | 1190.09 | 1918.43 | 788.56 | 0.00 | 0.00 | 0.00 |
June | 1550.82 | 416.37 | 1134.44 | 1794.45 | 623.58 | 0.00 | 0.00 | 0.00 |
July | 1691.23 | 619.42 | 1071.81 | 2164.69 | 563.55 | 0.00 | 0.00 | 0.00 |
August | 1817.02 | 847.31 | 969.71 | 2405.98 | 545.10 | 0.00 | 0.00 | 0.00 |
September | 2013.18 | 1111.74 | 901.44 | 2497.07 | 758.43 | 0.00 | 0.00 | 0.00 |
October | 1823.60 | 1125.94 | 697.66 | 2061.61 | 985.07 | 0.00 | 0.00 | 0.00 |
November | 1078.17 | 617.88 | 460.29 | 1021.23 | 1156.09 | 0.00 | 0.00 | 0.00 |
December | 1128.08 | 730.02 | 398.05 | 1101.99 | 1392.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1591.01 | 778.19 | 812.82 | 1791.86 | 950.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.37 | 416.37 | 398.05 | 942.37 | 545.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2013.18 | 1125.94 | 1190.09 | 2497.07 | 1392.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.43 | 80.04 | 191.39 | 117.13 | 936.93 | 0.00 | 0.00 | 0.00 |
February | 486.65 | 182.90 | 303.75 | 342.28 | 845.56 | 0.00 | 0.00 | 0.00 |
March | 681.92 | 230.17 | 451.75 | 567.63 | 728.69 | 0.00 | 0.00 | 0.00 |
April | 1037.47 | 396.66 | 640.80 | 1041.12 | 609.21 | 0.00 | 0.00 | 0.00 |
May | 1334.98 | 542.33 | 792.65 | 1469.85 | 515.27 | 0.00 | 0.00 | 0.00 |
June | 1283.89 | 498.49 | 785.40 | 1447.30 | 405.97 | 0.00 | 0.00 | 0.00 |
July | 1586.07 | 833.72 | 752.35 | 1963.69 | 372.10 | 0.00 | 0.00 | 0.00 |
August | 1312.06 | 669.97 | 642.08 | 1648.15 | 362.61 | 0.00 | 0.00 | 0.00 |
September | 1068.47 | 512.67 | 555.79 | 1230.75 | 506.38 | 0.00 | 0.00 | 0.00 |
October | 608.28 | 247.85 | 360.44 | 556.95 | 661.04 | 0.00 | 0.00 | 0.00 |
November | 302.92 | 85.44 | 217.48 | 165.84 | 788.30 | 0.00 | 0.00 | 0.00 |
December | 254.66 | 87.27 | 167.40 | 138.11 | 964.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.63 | 365.34 | 489.29 | 894.36 | 640.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.66 | 80.04 | 167.40 | 117.13 | 362.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1586.07 | 833.72 | 792.65 | 1963.69 | 964.94 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 32059367.27 | 0.370127E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.206707E+09 | 0.297939E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.658464E+09 | 0.276610E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.133976E+10 | 0.218668E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.220191E+10 | 0.185358E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.246391E+10 | 0.139492E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.273526E+10 | 0.130054E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.225770E+10 | 0.126951E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.127067E+10 | 0.181031E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.554862E+09 | 0.244950E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.117557E+09 | 0.290172E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 17938774.49 | 0.372138E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.138568E+11 | 0.283349E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 17938774.49 | 0.126951E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.273526E+10 | 0.372138E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.261768E+09 | 0.234399E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.772079E+09 | 0.188283E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.159055E+10 | 0.177698E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.287879E+10 | 0.141629E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.331583E+10 | 0.125244E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.412600E+10 | 0.956524E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.414843E+10 | 0.875051E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.422090E+10 | 0.851890E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.269236E+10 | 0.117232E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.151487E+10 | 0.158646E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.432439E+09 | 0.186895E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.326086E+09 | 0.238278E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.262801E+11 | 0.183665E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.261768E+09 | 0.851890E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.422090E+10 | 0.238278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.256653E+10 | 0.336778E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.405266E+10 | 0.278696E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.502131E+10 | 0.275467E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.541392E+10 | 0.230546E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.515504E+10 | 0.201175E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465405E+10 | 0.154961E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.579475E+10 | 0.145310E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644337E+10 | 0.140042E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.649334E+10 | 0.186204E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.556861E+10 | 0.244715E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.270055E+10 | 0.276451E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.299557E+10 | 0.347840E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.568597E+11 | 0.281819E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.256653E+10 | 0.140042E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.649334E+10 | 0.347840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.325589E+09 | 0.236332E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.851691E+09 | 0.190959E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.155247E+10 | 0.181592E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.272415E+10 | 0.148850E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.394915E+10 | 0.131328E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375296E+10 | 0.100816E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.525558E+10 | 0.958650E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441456E+10 | 0.931240E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.320499E+10 | 0.124057E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.152430E+10 | 0.163222E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.453129E+09 | 0.187924E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.382423E+09 | 0.240797E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.283910E+11 | 0.189486E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.325589E+09 | 0.931240E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.525558E+10 | 0.240797E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214460E+09 | 0.00 | 0.214460E+09 | 9286299.12 | 0.129791E+10 |
February | 0.301411E+09 | 0.00 | 0.301411E+09 | 66822708.06 | 0.104260E+10 |
March | 0.491662E+09 | 0.00 | 0.491662E+09 | 0.224828E+09 | 0.947625E+09 |
April | 0.673308E+09 | 2388428.59 | 0.670920E+09 | 0.463019E+09 | 0.734254E+09 |
May | 0.895257E+09 | 26596794.15 | 0.868661E+09 | 0.753181E+09 | 0.623249E+09 |
June | 0.910975E+09 | 60156990.47 | 0.850818E+09 | 0.838984E+09 | 0.468281E+09 |
July | 0.894693E+09 | 70148169.12 | 0.824545E+09 | 0.927299E+09 | 0.437798E+09 |
August | 0.724260E+09 | 19578934.08 | 0.704681E+09 | 0.762178E+09 | 0.431202E+09 |
September | 0.544432E+09 | 160544.72 | 0.544271E+09 | 0.424785E+09 | 0.630354E+09 |
October | 0.385461E+09 | 0.00 | 0.385461E+09 | 0.173903E+09 | 0.884660E+09 |
November | 0.234970E+09 | 0.00 | 0.234970E+09 | 32193398.15 | 0.106335E+10 |
December | 0.182235E+09 | 0.00 | 0.182235E+09 | 3773467.59 | 0.133506E+10 |
Annual Sum or Average | 0.645312E+10 | 0.179030E+09 | 0.627410E+10 | 0.468025E+10 | 0.989634E+10 |
Minimum of Months | 0.182235E+09 | 0.00 | 0.182235E+09 | 3773467.59 | 0.431202E+09 |
Maximum of Months | 0.910975E+09 | 70148169.12 | 0.868661E+09 | 0.927299E+09 | 0.133506E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9285410.11 | 0.129799E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 66821561.76 | 0.104266E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.224831E+09 | 0.947685E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.463031E+09 | 0.734301E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.753202E+09 | 0.623288E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.839010E+09 | 0.468309E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.927333E+09 | 0.437824E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.762207E+09 | 0.431227E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.424797E+09 | 0.630392E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.173905E+09 | 0.884715E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 32192153.46 | 0.106342E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 3773046.31 | 0.133515E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.468039E+10 | 0.989696E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 3773046.31 | 0.431227E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.927333E+09 | 0.133515E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.214468E+09 | 0.00 | 0.214468E+09 | 9285410.11 | 0.129799E+10 |
February | 0.301422E+09 | 0.00 | 0.301422E+09 | 66821561.76 | 0.104266E+10 |
March | 0.491681E+09 | 0.00 | 0.491681E+09 | 0.224831E+09 | 0.947685E+09 |
April | 0.673334E+09 | 2388492.79 | 0.670946E+09 | 0.463031E+09 | 0.734301E+09 |
May | 0.895292E+09 | 26597509.08 | 0.868695E+09 | 0.753202E+09 | 0.623288E+09 |
June | 0.911011E+09 | 60158607.51 | 0.850852E+09 | 0.839010E+09 | 0.468309E+09 |
July | 0.894729E+09 | 70150054.72 | 0.824579E+09 | 0.927333E+09 | 0.437824E+09 |
August | 0.724290E+09 | 19579460.37 | 0.704710E+09 | 0.762207E+09 | 0.431227E+09 |
September | 0.544454E+09 | 160549.03 | 0.544293E+09 | 0.424797E+09 | 0.630392E+09 |
October | 0.385475E+09 | 0.00 | 0.385475E+09 | 0.173905E+09 | 0.884715E+09 |
November | 0.234979E+09 | 0.00 | 0.234979E+09 | 32192153.46 | 0.106342E+10 |
December | 0.182242E+09 | 0.00 | 0.182242E+09 | 3773046.31 | 0.133515E+10 |
Annual Sum or Average | 0.645338E+10 | 0.179035E+09 | 0.627434E+10 | 0.468039E+10 | 0.989696E+10 |
Minimum of Months | 0.182242E+09 | 0.00 | 0.182242E+09 | 3773046.31 | 0.431227E+09 |
Maximum of Months | 0.911011E+09 | 70150054.72 | 0.868695E+09 | 0.927333E+09 | 0.133515E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.663026E+09 | 0.168099E+09 | 0.494928E+09 | 0.244392E+09 | 0.237101E+10 |
February | 0.109885E+10 | 0.390005E+09 | 0.708849E+09 | 0.734759E+09 | 0.190940E+10 |
March | 0.181645E+10 | 0.657569E+09 | 0.115888E+10 | 0.153900E+10 | 0.178408E+10 |
April | 0.272498E+10 | 0.113226E+10 | 0.159271E+10 | 0.278980E+10 | 0.141173E+10 |
May | 0.299628E+10 | 0.104173E+10 | 0.195454E+10 | 0.321900E+10 | 0.124014E+10 |
June | 0.347262E+10 | 0.151096E+10 | 0.196167E+10 | 0.399965E+10 | 0.953371E+09 |
July | 0.334161E+10 | 0.149990E+10 | 0.184171E+10 | 0.401809E+10 | 0.869095E+09 |
August | 0.328434E+10 | 0.164301E+10 | 0.164133E+10 | 0.407882E+10 | 0.858897E+09 |
September | 0.234995E+10 | 0.108382E+10 | 0.126614E+10 | 0.259019E+10 | 0.119980E+10 |
October | 0.158275E+10 | 0.672519E+09 | 0.910234E+09 | 0.143347E+10 | 0.167484E+10 |
November | 0.750753E+09 | 0.211944E+09 | 0.538809E+09 | 0.393436E+09 | 0.198059E+10 |
December | 0.636312E+09 | 0.204847E+09 | 0.431465E+09 | 0.299263E+09 | 0.246736E+10 |
Annual Sum or Average | 0.247179E+11 | 0.102167E+11 | 0.145013E+11 | 0.253399E+11 | 0.187203E+11 |
Minimum of Months | 0.636312E+09 | 0.168099E+09 | 0.431465E+09 | 0.244392E+09 | 0.858897E+09 |
Maximum of Months | 0.347262E+10 | 0.164301E+10 | 0.196167E+10 | 0.407882E+10 | 0.246736E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 26215457.77 | 6646464.26 | 19568993.51 | 9663026.36 | 93747770.03 |
February | 43447695.55 | 15420448.04 | 28027247.51 | 29051702.04 | 75496112.59 |
March | 71820864.26 | 25999666.84 | 45821197.41 | 60850592.22 | 70541042.49 |
April | 0.107743E+09 | 44768711.23 | 62974500.44 | 0.110306E+09 | 55818466.28 |
May | 0.118470E+09 | 41189145.54 | 77280911.26 | 0.127276E+09 | 49033925.97 |
June | 0.137304E+09 | 59741882.25 | 77562527.03 | 0.158142E+09 | 37695446.64 |
July | 0.132124E+09 | 59304779.97 | 72819649.84 | 0.158872E+09 | 34363224.73 |
August | 0.129860E+09 | 64963042.56 | 64896715.45 | 0.161273E+09 | 33960027.02 |
September | 92915081.92 | 42853079.58 | 50062002.35 | 0.102414E+09 | 47438992.22 |
October | 62580638.09 | 26590795.31 | 35989842.77 | 56678093.25 | 66221533.97 |
November | 29684100.24 | 8380085.62 | 21304014.63 | 15556101.99 | 78310688.16 |
December | 25159213.77 | 8099466.92 | 17059746.85 | 11832571.64 | 97557014.70 |
Annual Sum or Average | 0.977325E+09 | 0.403958E+09 | 0.573367E+09 | 0.100192E+10 | 0.740184E+09 |
Minimum of Months | 25159213.77 | 6646464.26 | 17059746.85 | 9663026.36 | 33960027.02 |
Maximum of Months | 0.137304E+09 | 64963042.56 | 77562527.03 | 0.161273E+09 | 97557014.70 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.862266E+09 | 0.117424E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136017E+10 | 0.985100E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.169699E+10 | 0.960237E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183466E+10 | 0.786208E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175219E+10 | 0.679557E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158267E+10 | 0.522261E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195501E+10 | 0.497837E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216548E+10 | 0.488596E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217349E+10 | 0.664421E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.185759E+10 | 0.897136E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.897813E+09 | 0.100268E+10 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.998324E+09 | 0.123812E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191367E+11 | 0.989639E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.862266E+09 | 0.488596E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217349E+10 | 0.123812E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947578E+09 | 0.562675E+09 | 0.384903E+09 | 0.862266E+09 | 0.117424E+10 |
February | 0.131621E+10 | 0.814748E+09 | 0.501459E+09 | 0.136017E+10 | 0.985100E+09 |
March | 0.156756E+10 | 0.835959E+09 | 0.731600E+09 | 0.169699E+10 | 0.960237E+09 |
April | 0.160166E+10 | 0.695428E+09 | 0.906231E+09 | 0.183466E+10 | 0.786208E+09 |
May | 0.151333E+10 | 0.450834E+09 | 0.106250E+10 | 0.175219E+10 | 0.679557E+09 |
June | 0.133989E+10 | 0.359740E+09 | 0.980149E+09 | 0.158267E+10 | 0.522261E+09 |
July | 0.150991E+10 | 0.553007E+09 | 0.956908E+09 | 0.195501E+10 | 0.497837E+09 |
August | 0.162221E+10 | 0.756459E+09 | 0.865751E+09 | 0.216548E+10 | 0.488596E+09 |
September | 0.173936E+10 | 0.960528E+09 | 0.778832E+09 | 0.217349E+10 | 0.664421E+09 |
October | 0.162808E+10 | 0.100522E+10 | 0.622864E+09 | 0.185759E+10 | 0.897136E+09 |
November | 0.931525E+09 | 0.533841E+09 | 0.397684E+09 | 0.897813E+09 | 0.100268E+10 |
December | 0.100713E+10 | 0.651752E+09 | 0.355377E+09 | 0.998324E+09 | 0.123812E+10 |
Annual Sum or Average | 0.167244E+11 | 0.818019E+10 | 0.854426E+10 | 0.191367E+11 | 0.989639E+10 |
Minimum of Months | 0.931525E+09 | 0.359740E+09 | 0.355377E+09 | 0.862266E+09 | 0.488596E+09 |
Maximum of Months | 0.173936E+10 | 0.100522E+10 | 0.106250E+10 | 0.217349E+10 | 0.123812E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.947518E+09 | 0.562639E+09 | 0.384879E+09 | 0.862211E+09 | 0.117417E+10 |
February | 0.131612E+10 | 0.814697E+09 | 0.501427E+09 | 0.136008E+10 | 0.985038E+09 |
March | 0.156746E+10 | 0.835906E+09 | 0.731554E+09 | 0.169688E+10 | 0.960176E+09 |
April | 0.160156E+10 | 0.695384E+09 | 0.906174E+09 | 0.183455E+10 | 0.786158E+09 |
May | 0.151324E+10 | 0.450805E+09 | 0.106243E+10 | 0.175208E+10 | 0.679514E+09 |
June | 0.133981E+10 | 0.359718E+09 | 0.980087E+09 | 0.158257E+10 | 0.522228E+09 |
July | 0.150982E+10 | 0.552972E+09 | 0.956847E+09 | 0.195489E+10 | 0.497806E+09 |
August | 0.162211E+10 | 0.756411E+09 | 0.865696E+09 | 0.216535E+10 | 0.488565E+09 |
September | 0.173925E+10 | 0.960467E+09 | 0.778782E+09 | 0.217335E+10 | 0.664379E+09 |
October | 0.162798E+10 | 0.100515E+10 | 0.622825E+09 | 0.185747E+10 | 0.897080E+09 |
November | 0.931466E+09 | 0.533807E+09 | 0.397659E+09 | 0.897756E+09 | 0.100262E+10 |
December | 0.100707E+10 | 0.651711E+09 | 0.355355E+09 | 0.998261E+09 | 0.123804E+10 |
Annual Sum or Average | 0.167234E+11 | 0.817967E+10 | 0.854372E+10 | 0.191355E+11 | 0.989577E+10 |
Minimum of Months | 0.931466E+09 | 0.359718E+09 | 0.355355E+09 | 0.862211E+09 | 0.488565E+09 |
Maximum of Months | 0.173925E+10 | 0.100515E+10 | 0.106243E+10 | 0.217335E+10 | 0.123804E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699333E+09 | 0.206220E+09 | 0.493113E+09 | 0.312469E+09 | 0.239402E+10 |
February | 0.113251E+10 | 0.425627E+09 | 0.706881E+09 | 0.821660E+09 | 0.194181E+10 |
March | 0.175696E+10 | 0.593020E+09 | 0.116394E+10 | 0.150890E+10 | 0.182813E+10 |
April | 0.258680E+10 | 0.989031E+09 | 0.159777E+10 | 0.265284E+10 | 0.148086E+10 |
May | 0.343957E+10 | 0.139731E+10 | 0.204226E+10 | 0.383561E+10 | 0.131715E+10 |
June | 0.320122E+10 | 0.124292E+10 | 0.195829E+10 | 0.364900E+10 | 0.100610E+10 |
July | 0.408649E+10 | 0.214806E+10 | 0.193843E+10 | 0.508987E+10 | 0.972582E+09 |
August | 0.338050E+10 | 0.172618E+10 | 0.165433E+10 | 0.427079E+10 | 0.946963E+09 |
September | 0.266410E+10 | 0.127829E+10 | 0.138581E+10 | 0.308657E+10 | 0.128147E+10 |
October | 0.156724E+10 | 0.638572E+09 | 0.928664E+09 | 0.144720E+10 | 0.172784E+10 |
November | 0.755297E+09 | 0.213025E+09 | 0.542273E+09 | 0.418338E+09 | 0.199363E+10 |
December | 0.656139E+09 | 0.224842E+09 | 0.431298E+09 | 0.362023E+09 | 0.249636E+10 |
Annual Sum or Average | 0.259262E+11 | 0.110831E+11 | 0.148431E+11 | 0.274553E+11 | 0.193869E+11 |
Minimum of Months | 0.656139E+09 | 0.206220E+09 | 0.431298E+09 | 0.312469E+09 | 0.946963E+09 |
Maximum of Months | 0.408649E+10 | 0.214806E+10 | 0.204226E+10 | 0.508987E+10 | 0.249636E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 27650915.06 | 8153722.29 | 19497192.77 | 12354671.65 | 94657381.76 |
February | 44778247.18 | 16828866.23 | 27949380.95 | 32487535.69 | 76777418.79 |
March | 69468548.27 | 23447401.83 | 46021146.44 | 59660417.24 | 72282498.59 |
April | 0.102280E+09 | 39105269.61 | 63174340.74 | 0.104891E+09 | 58552016.51 |
May | 0.135997E+09 | 55248024.25 | 80749036.80 | 0.151656E+09 | 52078985.71 |
June | 0.126573E+09 | 49143820.67 | 77429023.39 | 0.144278E+09 | 39780408.49 |
July | 0.161576E+09 | 84932032.48 | 76643484.53 | 0.201248E+09 | 38454995.23 |
August | 0.133662E+09 | 68251229.16 | 65410395.83 | 0.168863E+09 | 37442052.15 |
September | 0.105336E+09 | 50542232.62 | 54793546.51 | 0.122040E+09 | 50668270.38 |
October | 61966936.11 | 25248478.46 | 36718457.65 | 57220722.19 | 68317204.82 |
November | 29863697.12 | 8422773.34 | 21440923.78 | 16540623.97 | 78826529.70 |
December | 25943078.99 | 8890003.39 | 17053075.60 | 14314000.34 | 98703962.12 |
Annual Sum or Average | 0.102509E+10 | 0.438214E+09 | 0.586880E+09 | 0.108555E+10 | 0.766542E+09 |
Minimum of Months | 25943078.99 | 8153722.29 | 17053075.60 | 12354671.65 | 37442052.15 |
Maximum of Months | 0.161576E+09 | 84932032.48 | 80749036.80 | 0.201248E+09 | 98703962.12 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643410E+09 | 0.00 | 0.643410E+09 | 24487282.78 | 0.393143E+10 |
February | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.181135E+09 | 0.319668E+10 |
March | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.608958E+09 | 0.297818E+10 |
April | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.129563E+10 | 0.232662E+10 |
May | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.216927E+10 | 0.194886E+10 |
June | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.244768E+10 | 0.145326E+10 |
July | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.272759E+10 | 0.135136E+10 |
August | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.224508E+10 | 0.132578E+10 |
September | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.124106E+10 | 0.192457E+10 |
October | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.504071E+09 | 0.266591E+10 |
November | 0.704943E+09 | 0.00 | 0.704943E+09 | 93668483.90 | 0.316094E+10 |
December | 0.546732E+09 | 0.00 | 0.546732E+09 | 10634844.69 | 0.399814E+10 |
Annual Sum or Average | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.135493E+11 | 0.302617E+11 |
Minimum of Months | 0.546732E+09 | 0.00 | 0.546732E+09 | 10634844.69 | 0.132578E+10 |
Maximum of Months | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.272759E+10 | 0.399814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.246181E+09 | 0.248847E+10 |
February | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.737260E+09 | 0.201880E+10 |
March | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.154538E+10 | 0.190958E+10 |
April | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.284236E+10 | 0.149830E+10 |
May | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.329106E+10 | 0.131210E+10 |
June | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.411361E+10 | 0.993905E+09 |
July | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.413724E+10 | 0.905993E+09 |
August | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.420862E+10 | 0.885768E+09 |
September | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.266660E+10 | 0.124039E+10 |
October | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.147159E+10 | 0.171879E+10 |
November | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.402122E+09 | 0.203653E+10 |
December | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.306183E+09 | 0.255974E+10 |
Annual Sum or Average | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.259682E+11 | 0.195684E+11 |
Minimum of Months | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.246181E+09 | 0.885768E+09 |
Maximum of Months | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.420862E+10 | 0.255974E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.252404E+10 | 0.357701E+10 |
February | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.400013E+10 | 0.297958E+10 |
March | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.497668E+10 | 0.295227E+10 |
April | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.538273E+10 | 0.243827E+10 |
May | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.513831E+10 | 0.211207E+10 |
June | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.465121E+10 | 0.161631E+10 |
July | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.579791E+10 | 0.150940E+10 |
August | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.644417E+10 | 0.146000E+10 |
September | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.647241E+10 | 0.196585E+10 |
October | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.552181E+10 | 0.263842E+10 |
November | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.264703E+10 | 0.299658E+10 |
December | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.295158E+10 | 0.372963E+10 |
Annual Sum or Average | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.565080E+11 | 0.299754E+11 |
Minimum of Months | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.252404E+10 | 0.146000E+10 |
Maximum of Months | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.647241E+10 | 0.372963E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.313710E+09 | 0.250948E+10 |
February | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.828053E+09 | 0.204559E+10 |
March | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.152034E+10 | 0.195173E+10 |
April | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.269858E+10 | 0.157906E+10 |
May | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.393684E+10 | 0.138011E+10 |
June | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.375140E+10 | 0.105226E+10 |
July | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.525955E+10 | 0.996633E+09 |
August | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.441440E+10 | 0.971202E+09 |
September | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.319010E+10 | 0.131253E+10 |
October | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.149173E+10 | 0.177054E+10 |
November | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.429863E+09 | 0.204327E+10 |
December | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.369926E+09 | 0.258450E+10 |
Annual Sum or Average | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.282045E+11 | 0.201969E+11 |
Minimum of Months | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.313710E+09 | 0.971202E+09 |
Maximum of Months | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.525955E+10 | 0.258450E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.97 | 1381.90 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 85.44 | 1231.56 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 245.84 | 1032.74 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 516.88 | 843.63 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 822.10 | 692.05 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 950.58 | 538.16 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1021.23 | 485.57 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 842.93 | 473.98 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 490.23 | 698.42 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 207.16 | 914.54 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 45.35 | 1119.49 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 6.70 | 1389.40 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 439.40 | 898.49 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 6.70 | 473.98 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1021.23 | 1389.40 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.73 | 875.15 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 319.15 | 778.29 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 593.84 | 663.45 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1110.64 | 546.41 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1237.99 | 467.61 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1591.82 | 369.03 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1548.85 | 326.71 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1575.90 | 318.06 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1038.72 | 452.28 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 565.59 | 592.31 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 166.84 | 721.05 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 121.75 | 889.63 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 833.34 | 582.40 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 97.73 | 318.06 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1591.82 | 889.63 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 958.23 | 1257.39 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1675.21 | 1152.02 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1874.74 | 1028.48 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2088.70 | 889.45 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1924.67 | 751.10 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1795.54 | 597.85 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2163.51 | 542.53 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2405.68 | 522.86 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2505.15 | 718.38 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2079.08 | 913.66 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1041.88 | 1066.55 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1118.42 | 1298.68 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1803.01 | 893.64 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 958.23 | 522.86 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2505.15 | 1298.68 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.56 | 882.36 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 352.05 | 789.35 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 579.63 | 677.99 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1050.98 | 574.27 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1474.44 | 490.32 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1447.90 | 388.95 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1962.21 | 357.92 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1648.21 | 347.69 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1236.49 | 478.61 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 569.11 | 609.40 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 174.82 | 725.02 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 142.78 | 899.03 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 900.27 | 600.86 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 121.56 | 347.69 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1962.21 | 899.03 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.40 | 1453.81 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 82.86 | 1292.96 | 373.78 | 0.00 | 373.78 | 0.00 | 0.00 |
March | 251.83 | 1061.45 | 550.71 | 0.00 | 550.71 | 0.00 | 0.00 |
April | 535.91 | 849.87 | 779.31 | 2.76 | 776.55 | 0.00 | 0.00 |
May | 843.63 | 698.11 | 1002.78 | 29.79 | 972.99 | 0.00 | 0.00 |
June | 971.07 | 542.01 | 1054.40 | 69.63 | 984.77 | 0.00 | 0.00 |
July | 1038.67 | 490.38 | 1002.15 | 78.57 | 923.57 | 0.00 | 0.00 |
August | 853.72 | 483.00 | 811.25 | 21.93 | 789.32 | 0.00 | 0.00 |
September | 491.66 | 729.61 | 630.15 | 0.19 | 629.96 | 0.00 | 0.00 |
October | 194.78 | 990.92 | 431.75 | 0.00 | 431.75 | 0.00 | 0.00 |
November | 37.26 | 1230.78 | 271.96 | 0.00 | 271.96 | 0.00 | 0.00 |
December | 4.23 | 1495.43 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Annual Sum or Average | 445.24 | 941.47 | 613.90 | 17.03 | 596.87 | 0.00 | 0.00 |
Minimum of Months | 4.23 | 483.00 | 204.12 | 0.00 | 204.12 | 0.00 | 0.00 |
Maximum of Months | 1038.67 | 1495.43 | 1054.40 | 78.57 | 984.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.85 | 920.24 | 257.33 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 315.73 | 820.48 | 472.18 | 167.59 | 304.59 | 0.00 | 0.00 |
March | 597.32 | 692.44 | 705.00 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1118.87 | 566.18 | 1092.87 | 454.10 | 638.77 | 0.00 | 0.00 |
May | 1249.36 | 481.32 | 1162.91 | 404.32 | 758.60 | 0.00 | 0.00 |
June | 1604.09 | 382.36 | 1392.72 | 605.98 | 786.74 | 0.00 | 0.00 |
July | 1559.50 | 337.31 | 1296.95 | 582.14 | 714.80 | 0.00 | 0.00 |
August | 1583.07 | 333.35 | 1274.72 | 637.68 | 637.03 | 0.00 | 0.00 |
September | 1038.81 | 481.19 | 942.47 | 434.67 | 507.79 | 0.00 | 0.00 |
October | 556.36 | 650.04 | 614.30 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 157.79 | 794.33 | 301.09 | 85.00 | 216.09 | 0.00 | 0.00 |
December | 116.15 | 957.63 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 835.29 | 617.09 | 814.79 | 336.78 | 478.01 | 0.00 | 0.00 |
Minimum of Months | 94.85 | 333.35 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1604.09 | 957.63 | 1392.72 | 637.68 | 786.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 965.78 | 1315.21 | 1061.33 | 630.22 | 431.11 | 0.00 | 0.00 |
February | 1686.68 | 1221.58 | 1632.17 | 1010.33 | 621.84 | 0.00 | 0.00 |
March | 1900.71 | 1075.51 | 1755.74 | 936.31 | 819.43 | 0.00 | 0.00 |
April | 2123.41 | 909.94 | 1853.73 | 804.88 | 1048.86 | 0.00 | 0.00 |
May | 1962.54 | 761.14 | 1695.00 | 504.96 | 1190.05 | 0.00 | 0.00 |
June | 1831.75 | 604.46 | 1550.77 | 416.36 | 1134.41 | 0.00 | 0.00 |
July | 2189.71 | 557.60 | 1691.18 | 619.39 | 1071.78 | 0.00 | 0.00 |
August | 2425.45 | 547.25 | 1816.95 | 847.27 | 969.68 | 0.00 | 0.00 |
September | 2515.56 | 768.99 | 2013.11 | 1111.70 | 901.41 | 0.00 | 0.00 |
October | 2080.59 | 1004.84 | 1823.53 | 1125.89 | 697.64 | 0.00 | 0.00 |
November | 1039.11 | 1160.48 | 1078.13 | 617.86 | 460.27 | 0.00 | 0.00 |
December | 1118.17 | 1386.76 | 1128.03 | 729.99 | 398.04 | 0.00 | 0.00 |
Annual Sum or Average | 1820.42 | 941.42 | 1590.95 | 778.16 | 812.79 | 0.00 | 0.00 |
Minimum of Months | 965.78 | 547.25 | 1061.33 | 416.36 | 398.04 | 0.00 | 0.00 |
Maximum of Months | 2515.56 | 1386.76 | 2013.11 | 1125.89 | 1190.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.28 | 929.17 | 271.42 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 353.07 | 834.40 | 486.64 | 182.89 | 303.75 | 0.00 | 0.00 |
March | 585.63 | 709.53 | 681.91 | 230.16 | 451.75 | 0.00 | 0.00 |
April | 1063.94 | 593.91 | 1037.45 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1488.67 | 511.21 | 1334.96 | 542.32 | 792.64 | 0.00 | 0.00 |
June | 1463.45 | 403.50 | 1283.87 | 498.48 | 785.39 | 0.00 | 0.00 |
July | 1975.48 | 377.48 | 1586.04 | 833.70 | 752.34 | 0.00 | 0.00 |
August | 1657.58 | 367.53 | 1312.04 | 669.96 | 642.08 | 0.00 | 0.00 |
September | 1237.89 | 513.94 | 1068.45 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 561.69 | 670.61 | 608.27 | 247.84 | 360.43 | 0.00 | 0.00 |
November | 167.78 | 799.56 | 302.92 | 85.43 | 217.48 | 0.00 | 0.00 |
December | 140.51 | 968.89 | 254.66 | 87.27 | 167.39 | 0.00 | 0.00 |
Annual Sum or Average | 905.02 | 639.06 | 854.62 | 365.34 | 489.28 | 0.00 | 0.00 |
Minimum of Months | 121.28 | 367.53 | 254.66 | 80.04 | 167.39 | 0.00 | 0.00 |
Maximum of Months | 1975.48 | 968.89 | 1586.04 | 833.70 | 792.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.14 | 1467.83 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
February | 74.87 | 1321.38 | 373.79 | 0.00 | 373.79 | 0.00 | 0.00 |
March | 227.36 | 1111.92 | 550.72 | 0.00 | 550.72 | 0.00 | 0.00 |
April | 499.86 | 897.62 | 779.33 | 2.76 | 776.56 | 0.00 | 0.00 |
May | 809.91 | 727.62 | 1002.80 | 29.79 | 973.01 | 0.00 | 0.00 |
June | 944.32 | 560.67 | 1054.42 | 69.63 | 984.79 | 0.00 | 0.00 |
July | 1018.37 | 504.54 | 1002.17 | 78.57 | 923.59 | 0.00 | 0.00 |
August | 838.22 | 494.99 | 811.26 | 21.93 | 789.33 | 0.00 | 0.00 |
September | 478.80 | 742.50 | 630.16 | 0.19 | 629.97 | 0.00 | 0.00 |
October | 188.20 | 995.34 | 431.76 | 0.00 | 431.76 | 0.00 | 0.00 |
November | 36.14 | 1219.50 | 271.97 | 0.00 | 271.97 | 0.00 | 0.00 |
December | 3.97 | 1492.73 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Annual Sum or Average | 429.64 | 959.59 | 613.91 | 17.03 | 596.88 | 0.00 | 0.00 |
Minimum of Months | 3.97 | 494.99 | 204.13 | 0.00 | 204.13 | 0.00 | 0.00 |
Maximum of Months | 1018.37 | 1492.73 | 1054.42 | 78.57 | 984.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.91 | 929.09 | 257.34 | 65.24 | 192.09 | 0.00 | 0.00 |
February | 304.75 | 834.49 | 472.19 | 167.59 | 304.60 | 0.00 | 0.00 |
March | 576.98 | 712.95 | 705.01 | 255.22 | 449.79 | 0.00 | 0.00 |
April | 1096.59 | 578.05 | 1092.89 | 454.11 | 638.78 | 0.00 | 0.00 |
May | 1228.74 | 489.88 | 1162.93 | 404.32 | 758.61 | 0.00 | 0.00 |
June | 1587.04 | 383.45 | 1392.74 | 605.99 | 786.75 | 0.00 | 0.00 |
July | 1544.67 | 338.26 | 1296.96 | 582.15 | 714.81 | 0.00 | 0.00 |
August | 1571.32 | 330.71 | 1274.74 | 637.70 | 637.04 | 0.00 | 0.00 |
September | 1028.78 | 478.55 | 942.48 | 434.68 | 507.80 | 0.00 | 0.00 |
October | 549.43 | 641.72 | 614.31 | 261.02 | 353.28 | 0.00 | 0.00 |
November | 155.14 | 785.70 | 301.10 | 85.00 | 216.10 | 0.00 | 0.00 |
December | 114.32 | 955.70 | 246.97 | 79.51 | 167.46 | 0.00 | 0.00 |
Annual Sum or Average | 823.45 | 620.51 | 814.80 | 336.78 | 478.02 | 0.00 | 0.00 |
Minimum of Months | 91.91 | 330.71 | 246.97 | 65.24 | 167.46 | 0.00 | 0.00 |
Maximum of Months | 1587.04 | 955.70 | 1392.74 | 637.70 | 786.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 942.37 | 1335.50 | 1061.37 | 630.25 | 431.13 | 0.00 | 0.00 |
February | 1653.49 | 1231.64 | 1632.23 | 1010.37 | 621.86 | 0.00 | 0.00 |
March | 1858.08 | 1102.25 | 1755.81 | 936.35 | 819.45 | 0.00 | 0.00 |
April | 2076.67 | 940.69 | 1853.80 | 804.91 | 1048.89 | 0.00 | 0.00 |
May | 1918.43 | 788.56 | 1695.06 | 504.98 | 1190.09 | 0.00 | 0.00 |
June | 1794.45 | 623.58 | 1550.82 | 416.37 | 1134.44 | 0.00 | 0.00 |
July | 2164.69 | 563.55 | 1691.23 | 619.42 | 1071.81 | 0.00 | 0.00 |
August | 2405.98 | 545.10 | 1817.02 | 847.31 | 969.71 | 0.00 | 0.00 |
September | 2497.07 | 758.43 | 2013.18 | 1111.74 | 901.44 | 0.00 | 0.00 |
October | 2061.61 | 985.07 | 1823.60 | 1125.94 | 697.66 | 0.00 | 0.00 |
November | 1021.23 | 1156.09 | 1078.17 | 617.88 | 460.29 | 0.00 | 0.00 |
December | 1101.99 | 1392.48 | 1128.08 | 730.02 | 398.05 | 0.00 | 0.00 |
Annual Sum or Average | 1791.86 | 950.51 | 1591.01 | 778.19 | 812.82 | 0.00 | 0.00 |
Minimum of Months | 942.37 | 545.10 | 1061.37 | 416.37 | 398.05 | 0.00 | 0.00 |
Maximum of Months | 2497.07 | 1392.48 | 2013.18 | 1125.94 | 1190.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.13 | 936.93 | 271.43 | 80.04 | 191.39 | 0.00 | 0.00 |
February | 342.28 | 845.56 | 486.65 | 182.90 | 303.75 | 0.00 | 0.00 |
March | 567.63 | 728.69 | 681.92 | 230.17 | 451.75 | 0.00 | 0.00 |
April | 1041.12 | 609.21 | 1037.47 | 396.66 | 640.80 | 0.00 | 0.00 |
May | 1469.85 | 515.27 | 1334.98 | 542.33 | 792.65 | 0.00 | 0.00 |
June | 1447.30 | 405.97 | 1283.89 | 498.49 | 785.40 | 0.00 | 0.00 |
July | 1963.69 | 372.10 | 1586.07 | 833.72 | 752.35 | 0.00 | 0.00 |
August | 1648.15 | 362.61 | 1312.06 | 669.97 | 642.08 | 0.00 | 0.00 |
September | 1230.75 | 506.38 | 1068.47 | 512.67 | 555.79 | 0.00 | 0.00 |
October | 556.95 | 661.04 | 608.28 | 247.85 | 360.44 | 0.00 | 0.00 |
November | 165.84 | 788.30 | 302.92 | 85.44 | 217.48 | 0.00 | 0.00 |
December | 138.11 | 964.94 | 254.66 | 87.27 | 167.40 | 0.00 | 0.00 |
Annual Sum or Average | 894.36 | 640.44 | 854.63 | 365.34 | 489.29 | 0.00 | 0.00 |
Minimum of Months | 117.13 | 362.61 | 254.66 | 80.04 | 167.40 | 0.00 | 0.00 |
Maximum of Months | 1963.69 | 964.94 | 1586.07 | 833.72 | 792.65 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32059367.27 | 0.370127E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.206707E+09 | 0.297939E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.658464E+09 | 0.276610E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.133976E+10 | 0.218668E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.220191E+10 | 0.185358E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.246391E+10 | 0.139492E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.273526E+10 | 0.130054E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.225770E+10 | 0.126951E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.127067E+10 | 0.181031E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.554862E+09 | 0.244950E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 0.117557E+09 | 0.290172E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 17938774.49 | 0.372138E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138568E+11 | 0.283349E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 17938774.49 | 0.126951E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273526E+10 | 0.372138E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261768E+09 | 0.234399E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.772079E+09 | 0.188283E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.159055E+10 | 0.177698E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.287879E+10 | 0.141629E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.331583E+10 | 0.125244E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.412600E+10 | 0.956524E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.414843E+10 | 0.875051E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.422090E+10 | 0.851890E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.269236E+10 | 0.117232E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.151487E+10 | 0.158646E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.432439E+09 | 0.186895E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.326086E+09 | 0.238278E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262801E+11 | 0.183665E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261768E+09 | 0.851890E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422090E+10 | 0.238278E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256653E+10 | 0.336778E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.405266E+10 | 0.278696E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.502131E+10 | 0.275467E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.541392E+10 | 0.230546E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.515504E+10 | 0.201175E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465405E+10 | 0.154961E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.579475E+10 | 0.145310E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644337E+10 | 0.140042E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.649334E+10 | 0.186204E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.556861E+10 | 0.244715E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.270055E+10 | 0.276451E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.299557E+10 | 0.347840E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.568597E+11 | 0.281819E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256653E+10 | 0.140042E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649334E+10 | 0.347840E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325589E+09 | 0.236332E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.851691E+09 | 0.190959E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.155247E+10 | 0.181592E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.272415E+10 | 0.148850E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.394915E+10 | 0.131328E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375296E+10 | 0.100816E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.525558E+10 | 0.958650E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441456E+10 | 0.931240E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.320499E+10 | 0.124057E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.152430E+10 | 0.163222E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.453129E+09 | 0.187924E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.382423E+09 | 0.240797E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.283910E+11 | 0.189486E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.325589E+09 | 0.931240E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.525558E+10 | 0.240797E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27857119.35 | 0.389389E+10 | 0.643395E+09 | 0.00 | 0.643395E+09 | 0.00 | 0.00 |
February | 0.200466E+09 | 0.312792E+10 | 0.904256E+09 | 0.00 | 0.904256E+09 | 0.00 | 0.00 |
March | 0.674490E+09 | 0.284300E+10 | 0.147502E+10 | 0.00 | 0.147502E+10 | 0.00 | 0.00 |
April | 0.138908E+10 | 0.220286E+10 | 0.201998E+10 | 7165414.18 | 0.201281E+10 | 0.00 | 0.00 |
May | 0.225959E+10 | 0.186982E+10 | 0.268584E+10 | 79791812.30 | 0.260605E+10 | 0.00 | 0.00 |
June | 0.251700E+10 | 0.140490E+10 | 0.273300E+10 | 0.180474E+09 | 0.255252E+10 | 0.00 | 0.00 |
July | 0.278196E+10 | 0.131345E+10 | 0.268415E+10 | 0.210448E+09 | 0.247370E+10 | 0.00 | 0.00 |
August | 0.228659E+10 | 0.129366E+10 | 0.217284E+10 | 58737854.82 | 0.211410E+10 | 0.00 | 0.00 |
September | 0.127438E+10 | 0.189114E+10 | 0.163334E+10 | 481642.78 | 0.163286E+10 | 0.00 | 0.00 |
October | 0.521712E+09 | 0.265409E+10 | 0.115641E+10 | 0.00 | 0.115641E+10 | 0.00 | 0.00 |
November | 96577705.07 | 0.319019E+10 | 0.704927E+09 | 0.00 | 0.704927E+09 | 0.00 | 0.00 |
December | 11319560.20 | 0.400535E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.140410E+11 | 0.296903E+11 | 0.193599E+11 | 0.537099E+09 | 0.188228E+11 | 0.00 | 0.00 |
Minimum of Months | 11319560.20 | 0.129366E+10 | 0.546720E+09 | 0.00 | 0.546720E+09 | 0.00 | 0.00 |
Maximum of Months | 0.278196E+10 | 0.400535E+10 | 0.273300E+10 | 0.210448E+09 | 0.260605E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254055E+09 | 0.246476E+10 | 0.689242E+09 | 0.174745E+09 | 0.514497E+09 | 0.00 | 0.00 |
February | 0.763811E+09 | 0.198490E+10 | 0.114230E+10 | 0.405425E+09 | 0.736876E+09 | 0.00 | 0.00 |
March | 0.159985E+10 | 0.185462E+10 | 0.188827E+10 | 0.683568E+09 | 0.120470E+10 | 0.00 | 0.00 |
April | 0.290011E+10 | 0.146755E+10 | 0.283272E+10 | 0.117703E+10 | 0.165569E+10 | 0.00 | 0.00 |
May | 0.334627E+10 | 0.128917E+10 | 0.311475E+10 | 0.108292E+10 | 0.203182E+10 | 0.00 | 0.00 |
June | 0.415779E+10 | 0.991067E+09 | 0.360993E+10 | 0.157070E+10 | 0.203923E+10 | 0.00 | 0.00 |
July | 0.417696E+10 | 0.903458E+09 | 0.347374E+10 | 0.155921E+10 | 0.191453E+10 | 0.00 | 0.00 |
August | 0.424009E+10 | 0.892857E+09 | 0.341420E+10 | 0.170797E+10 | 0.170623E+10 | 0.00 | 0.00 |
September | 0.269260E+10 | 0.124724E+10 | 0.244287E+10 | 0.112667E+10 | 0.131620E+10 | 0.00 | 0.00 |
October | 0.149015E+10 | 0.174106E+10 | 0.164533E+10 | 0.699110E+09 | 0.946224E+09 | 0.00 | 0.00 |
November | 0.408992E+09 | 0.205890E+10 | 0.780437E+09 | 0.220324E+09 | 0.560113E+09 | 0.00 | 0.00 |
December | 0.311095E+09 | 0.256491E+10 | 0.661471E+09 | 0.212946E+09 | 0.448525E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263418E+11 | 0.194605E+11 | 0.256953E+11 | 0.106206E+11 | 0.150746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254055E+09 | 0.892857E+09 | 0.661471E+09 | 0.174745E+09 | 0.448525E+09 | 0.00 | 0.00 |
Maximum of Months | 0.424009E+10 | 0.256491E+10 | 0.360993E+10 | 0.170797E+10 | 0.203923E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258674E+10 | 0.352265E+10 | 0.284267E+10 | 0.168799E+10 | 0.115468E+10 | 0.00 | 0.00 |
February | 0.408041E+10 | 0.295524E+10 | 0.394854E+10 | 0.244419E+10 | 0.150435E+10 | 0.00 | 0.00 |
March | 0.509086E+10 | 0.288065E+10 | 0.470258E+10 | 0.250782E+10 | 0.219475E+10 | 0.00 | 0.00 |
April | 0.550387E+10 | 0.235857E+10 | 0.480488E+10 | 0.208624E+10 | 0.271864E+10 | 0.00 | 0.00 |
May | 0.525647E+10 | 0.203863E+10 | 0.453990E+10 | 0.135247E+10 | 0.318743E+10 | 0.00 | 0.00 |
June | 0.474791E+10 | 0.156675E+10 | 0.401958E+10 | 0.107920E+10 | 0.294039E+10 | 0.00 | 0.00 |
July | 0.586492E+10 | 0.149348E+10 | 0.452965E+10 | 0.165899E+10 | 0.287066E+10 | 0.00 | 0.00 |
August | 0.649632E+10 | 0.146576E+10 | 0.486653E+10 | 0.226933E+10 | 0.259720E+10 | 0.00 | 0.00 |
September | 0.652033E+10 | 0.199322E+10 | 0.521797E+10 | 0.288152E+10 | 0.233645E+10 | 0.00 | 0.00 |
October | 0.557266E+10 | 0.269135E+10 | 0.488414E+10 | 0.301559E+10 | 0.186855E+10 | 0.00 | 0.00 |
November | 0.269338E+10 | 0.300797E+10 | 0.279452E+10 | 0.160149E+10 | 0.119303E+10 | 0.00 | 0.00 |
December | 0.299491E+10 | 0.371428E+10 | 0.302132E+10 | 0.195522E+10 | 0.106611E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.574088E+11 | 0.296886E+11 | 0.501723E+11 | 0.245400E+11 | 0.256322E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258674E+10 | 0.146576E+10 | 0.279452E+10 | 0.107920E+10 | 0.106611E+10 | 0.00 | 0.00 |
Maximum of Months | 0.652033E+10 | 0.371428E+10 | 0.521797E+10 | 0.301559E+10 | 0.318743E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.324824E+09 | 0.248868E+10 | 0.726984E+09 | 0.214374E+09 | 0.512610E+09 | 0.00 | 0.00 |
February | 0.854147E+09 | 0.201859E+10 | 0.117729E+10 | 0.442456E+09 | 0.734831E+09 | 0.00 | 0.00 |
March | 0.156856E+10 | 0.190041E+10 | 0.182643E+10 | 0.616467E+09 | 0.120996E+10 | 0.00 | 0.00 |
April | 0.275773E+10 | 0.153942E+10 | 0.268908E+10 | 0.102814E+10 | 0.166095E+10 | 0.00 | 0.00 |
May | 0.398726E+10 | 0.136923E+10 | 0.357557E+10 | 0.145255E+10 | 0.212301E+10 | 0.00 | 0.00 |
June | 0.379327E+10 | 0.104588E+10 | 0.332779E+10 | 0.129206E+10 | 0.203572E+10 | 0.00 | 0.00 |
July | 0.529111E+10 | 0.101104E+10 | 0.424806E+10 | 0.223299E+10 | 0.201507E+10 | 0.00 | 0.00 |
August | 0.443965E+10 | 0.984405E+09 | 0.351416E+10 | 0.179443E+10 | 0.171974E+10 | 0.00 | 0.00 |
September | 0.320860E+10 | 0.133214E+10 | 0.276943E+10 | 0.132883E+10 | 0.144060E+10 | 0.00 | 0.00 |
October | 0.150442E+10 | 0.179616E+10 | 0.162920E+10 | 0.663820E+09 | 0.965383E+09 | 0.00 | 0.00 |
November | 0.434879E+09 | 0.207246E+10 | 0.785161E+09 | 0.221447E+09 | 0.563714E+09 | 0.00 | 0.00 |
December | 0.376337E+09 | 0.259507E+10 | 0.682082E+09 | 0.233732E+09 | 0.448351E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285408E+11 | 0.201535E+11 | 0.269512E+11 | 0.115213E+11 | 0.154299E+11 | 0.00 | 0.00 |
Minimum of Months | 0.324824E+09 | 0.984405E+09 | 0.682082E+09 | 0.214374E+09 | 0.448351E+09 | 0.00 | 0.00 |
Maximum of Months | 0.529111E+10 | 0.259507E+10 | 0.424806E+10 | 0.223299E+10 | 0.212301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24487282.78 | 0.393143E+10 | 0.643410E+09 | 0.00 | 0.643410E+09 | 0.00 | 0.00 |
February | 0.181135E+09 | 0.319668E+10 | 0.904276E+09 | 0.00 | 0.904276E+09 | 0.00 | 0.00 |
March | 0.608958E+09 | 0.297818E+10 | 0.147506E+10 | 0.00 | 0.147506E+10 | 0.00 | 0.00 |
April | 0.129563E+10 | 0.232662E+10 | 0.202002E+10 | 7165624.79 | 0.201285E+10 | 0.00 | 0.00 |
May | 0.216927E+10 | 0.194886E+10 | 0.268590E+10 | 79794157.67 | 0.260611E+10 | 0.00 | 0.00 |
June | 0.244768E+10 | 0.145326E+10 | 0.273305E+10 | 0.180480E+09 | 0.255258E+10 | 0.00 | 0.00 |
July | 0.272759E+10 | 0.135136E+10 | 0.268421E+10 | 0.210454E+09 | 0.247375E+10 | 0.00 | 0.00 |
August | 0.224508E+10 | 0.132578E+10 | 0.217288E+10 | 58739581.33 | 0.211414E+10 | 0.00 | 0.00 |
September | 0.124106E+10 | 0.192457E+10 | 0.163337E+10 | 481656.94 | 0.163289E+10 | 0.00 | 0.00 |
October | 0.504071E+09 | 0.266591E+10 | 0.115644E+10 | 0.00 | 0.115644E+10 | 0.00 | 0.00 |
November | 93668483.90 | 0.316094E+10 | 0.704943E+09 | 0.00 | 0.704943E+09 | 0.00 | 0.00 |
December | 10634844.69 | 0.399814E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135493E+11 | 0.302617E+11 | 0.193603E+11 | 0.537115E+09 | 0.188232E+11 | 0.00 | 0.00 |
Minimum of Months | 10634844.69 | 0.132578E+10 | 0.546732E+09 | 0.00 | 0.546732E+09 | 0.00 | 0.00 |
Maximum of Months | 0.272759E+10 | 0.399814E+10 | 0.273305E+10 | 0.210454E+09 | 0.260611E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246181E+09 | 0.248847E+10 | 0.689252E+09 | 0.174748E+09 | 0.514504E+09 | 0.00 | 0.00 |
February | 0.737260E+09 | 0.201880E+10 | 0.114232E+10 | 0.405433E+09 | 0.736886E+09 | 0.00 | 0.00 |
March | 0.154538E+10 | 0.190958E+10 | 0.188830E+10 | 0.683582E+09 | 0.120472E+10 | 0.00 | 0.00 |
April | 0.284236E+10 | 0.149830E+10 | 0.283277E+10 | 0.117706E+10 | 0.165571E+10 | 0.00 | 0.00 |
May | 0.329106E+10 | 0.131210E+10 | 0.311479E+10 | 0.108294E+10 | 0.203185E+10 | 0.00 | 0.00 |
June | 0.411361E+10 | 0.993905E+09 | 0.360998E+10 | 0.157073E+10 | 0.203925E+10 | 0.00 | 0.00 |
July | 0.413724E+10 | 0.905993E+09 | 0.347379E+10 | 0.155924E+10 | 0.191455E+10 | 0.00 | 0.00 |
August | 0.420862E+10 | 0.885768E+09 | 0.341425E+10 | 0.170800E+10 | 0.170625E+10 | 0.00 | 0.00 |
September | 0.266660E+10 | 0.124039E+10 | 0.244291E+10 | 0.112669E+10 | 0.131622E+10 | 0.00 | 0.00 |
October | 0.147159E+10 | 0.171879E+10 | 0.164536E+10 | 0.699123E+09 | 0.946237E+09 | 0.00 | 0.00 |
November | 0.402122E+09 | 0.203653E+10 | 0.780449E+09 | 0.220329E+09 | 0.560121E+09 | 0.00 | 0.00 |
December | 0.306183E+09 | 0.255974E+10 | 0.661482E+09 | 0.212951E+09 | 0.448531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.259682E+11 | 0.195684E+11 | 0.256957E+11 | 0.106208E+11 | 0.150748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.246181E+09 | 0.885768E+09 | 0.661482E+09 | 0.174748E+09 | 0.448531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.420862E+10 | 0.255974E+10 | 0.360998E+10 | 0.170800E+10 | 0.203925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252404E+10 | 0.357701E+10 | 0.284278E+10 | 0.168806E+10 | 0.115473E+10 | 0.00 | 0.00 |
February | 0.400013E+10 | 0.297958E+10 | 0.394869E+10 | 0.244429E+10 | 0.150440E+10 | 0.00 | 0.00 |
March | 0.497668E+10 | 0.295227E+10 | 0.470276E+10 | 0.250793E+10 | 0.219483E+10 | 0.00 | 0.00 |
April | 0.538273E+10 | 0.243827E+10 | 0.480505E+10 | 0.208633E+10 | 0.271872E+10 | 0.00 | 0.00 |
May | 0.513831E+10 | 0.211207E+10 | 0.454006E+10 | 0.135253E+10 | 0.318753E+10 | 0.00 | 0.00 |
June | 0.465121E+10 | 0.161631E+10 | 0.401972E+10 | 0.107924E+10 | 0.294047E+10 | 0.00 | 0.00 |
July | 0.579791E+10 | 0.150940E+10 | 0.452980E+10 | 0.165905E+10 | 0.287075E+10 | 0.00 | 0.00 |
August | 0.644417E+10 | 0.146000E+10 | 0.486670E+10 | 0.226942E+10 | 0.259728E+10 | 0.00 | 0.00 |
September | 0.647241E+10 | 0.196585E+10 | 0.521816E+10 | 0.288164E+10 | 0.233652E+10 | 0.00 | 0.00 |
October | 0.552181E+10 | 0.263842E+10 | 0.488433E+10 | 0.301571E+10 | 0.186862E+10 | 0.00 | 0.00 |
November | 0.264703E+10 | 0.299658E+10 | 0.279463E+10 | 0.160156E+10 | 0.119307E+10 | 0.00 | 0.00 |
December | 0.295158E+10 | 0.372963E+10 | 0.302144E+10 | 0.195530E+10 | 0.106615E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.565080E+11 | 0.299754E+11 | 0.501741E+11 | 0.245411E+11 | 0.256331E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252404E+10 | 0.146000E+10 | 0.279463E+10 | 0.107924E+10 | 0.106615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.647241E+10 | 0.372963E+10 | 0.521816E+10 | 0.301571E+10 | 0.318753E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.313710E+09 | 0.250948E+10 | 0.726993E+09 | 0.214377E+09 | 0.512616E+09 | 0.00 | 0.00 |
February | 0.828053E+09 | 0.204559E+10 | 0.117730E+10 | 0.442463E+09 | 0.734839E+09 | 0.00 | 0.00 |
March | 0.152034E+10 | 0.195173E+10 | 0.182646E+10 | 0.616478E+09 | 0.120998E+10 | 0.00 | 0.00 |
April | 0.269858E+10 | 0.157906E+10 | 0.268912E+10 | 0.102815E+10 | 0.166096E+10 | 0.00 | 0.00 |
May | 0.393684E+10 | 0.138011E+10 | 0.357561E+10 | 0.145258E+10 | 0.212303E+10 | 0.00 | 0.00 |
June | 0.375140E+10 | 0.105226E+10 | 0.332783E+10 | 0.129209E+10 | 0.203574E+10 | 0.00 | 0.00 |
July | 0.525955E+10 | 0.996633E+09 | 0.424812E+10 | 0.223303E+10 | 0.201509E+10 | 0.00 | 0.00 |
August | 0.441440E+10 | 0.971202E+09 | 0.351421E+10 | 0.179446E+10 | 0.171975E+10 | 0.00 | 0.00 |
September | 0.319010E+10 | 0.131253E+10 | 0.276947E+10 | 0.132885E+10 | 0.144062E+10 | 0.00 | 0.00 |
October | 0.149173E+10 | 0.177054E+10 | 0.162922E+10 | 0.663831E+09 | 0.965393E+09 | 0.00 | 0.00 |
November | 0.429863E+09 | 0.204327E+10 | 0.785171E+09 | 0.221451E+09 | 0.563720E+09 | 0.00 | 0.00 |
December | 0.369926E+09 | 0.258450E+10 | 0.682091E+09 | 0.233735E+09 | 0.448356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282045E+11 | 0.201969E+11 | 0.269516E+11 | 0.115215E+11 | 0.154301E+11 | 0.00 | 0.00 |
Minimum of Months | 0.313710E+09 | 0.971202E+09 | 0.682091E+09 | 0.214377E+09 | 0.448356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.525955E+10 | 0.258450E+10 | 0.424812E+10 | 0.223303E+10 | 0.212303E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.482973E+10 | -0.458408E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -245643482.3 | 60.05 | 0.00 | 0.00 |
February | 0.441110E+10 | -0.419457E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -216529522.0 | 60.05 | 0.00 | 0.00 |
March | 0.514654E+10 | -0.491064E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -235900998.4 | 60.05 | 0.00 | 0.00 |
April | 0.452608E+10 | -0.429981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226268527.3 | 60.05 | 0.00 | 0.00 |
May | 0.467739E+10 | -0.444432E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233072698.0 | 60.05 | 0.00 | 0.00 |
June | 0.447758E+10 | -0.425257E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225010380.2 | 60.05 | 0.00 | 0.00 |
July | 0.412891E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231469946.4 | 60.05 | 0.00 | 0.00 |
August | 0.450668E+10 | -0.427461E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232070014.6 | 60.05 | 0.00 | 0.00 |
September | 0.412371E+10 | -0.389919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224514902.7 | 60.05 | 0.00 | 0.00 |
October | 0.438594E+10 | -0.415238E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233561287.5 | 60.05 | 0.00 | 0.00 |
November | 0.447300E+10 | -0.424363E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229364627.9 | 60.05 | 0.00 | 0.00 |
December | 0.459149E+10 | -0.435083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -240657761.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.542781E+11 | -0.515041E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.277406E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.412371E+10 | -0.491064E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -245643482.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514654E+10 | -0.389744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -216529522.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.50 | 0.48 | 01-JAN-09:50 | 2744.45 | 32.28 | 222.33 | 218.83 | 2191.41 | 33.53 | 225.83 | 187.33 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:30 | 4676.02 | 33.24 | 243.17 | 243.33 | 2064.71 | 29.38 | 222.17 | 221.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7743.27 | 33.05 | 208.83 | 311.67 | 1686.13 | 21.83 | 155.83 | 267.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2183.74 | 18.64 | 2.83 | 344.33 | 1216.73 | 20.87 | 212.67 | 307.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1995.02 | 18.53 | 4.83 | 384.83 | 1093.07 | 20.71 | 209.50 | 343.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1742.44 | 18.10 | 0.00 | 393.83 | 1003.97 | 20.32 | 190.50 | 343.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1552.52 | 16.89 | 0.00 | 392.83 | 913.22 | 19.11 | 150.83 | 337.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1846.74 | 17.94 | 2.67 | 372.67 | 1111.28 | 20.18 | 159.50 | 326.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2983.68 | 20.78 | 41.67 | 319.00 | 1478.49 | 21.66 | 186.50 | 287.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7195.48 | 34.58 | 220.50 | 284.67 | 1968.69 | 23.02 | 157.50 | 256.17 |
November | 242.67 | 0.50 | 0.48 | 01-NOV-08:09 | 3058.65 | 31.81 | 224.67 | 224.17 | 2456.87 | 33.15 | 229.50 | 193.17 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3686.25 | 35.42 | 149.50 | 206.83 | 3141.89 | 36.90 | 149.67 | 167.17 |
Annual Sum or Average | 3714.00 | 0.51 | 3101.84 | 23.95 | 1321.00 | 3697.00 | 1520.01 | 23.68 | 2250.00 | 3236.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1552.52 | 16.89 | 0.00 | 206.83 | 913.22 | 19.11 | 149.67 | 167.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7743.27 | 35.42 | 243.17 | 393.83 | 3141.89 | 36.90 | 229.50 | 343.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 911.09 | 18.95 | 61.50 | 198.67 | 567.91 | 21.21 | 75.67 | 128.67 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1469.22 | 19.69 | 68.33 | 226.67 | 787.99 | 21.90 | 79.83 | 178.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2659.52 | 22.08 | 79.00 | 302.00 | 1191.45 | 23.02 | 90.67 | 252.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2796.72 | 21.11 | 105.50 | 346.33 | 1584.43 | 23.20 | 103.83 | 306.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2887.52 | 21.03 | 132.50 | 390.83 | 1263.95 | 21.35 | 91.67 | 349.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 3031.04 | 20.26 | 89.00 | 402.67 | 1682.49 | 22.31 | 77.67 | 355.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2859.15 | 20.72 | 148.50 | 406.33 | 1302.06 | 21.66 | 101.67 | 370.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3343.46 | 22.20 | 116.33 | 377.50 | 1464.14 | 21.98 | 74.00 | 337.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2730.18 | 21.78 | 82.67 | 322.83 | 1531.78 | 23.01 | 77.67 | 284.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2444.16 | 21.98 | 83.00 | 270.50 | 1096.07 | 22.64 | 89.17 | 224.67 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1135.34 | 20.34 | 79.17 | 207.17 | 596.33 | 21.16 | 71.67 | 143.50 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1069.58 | 21.49 | 56.33 | 182.00 | 582.30 | 22.14 | 57.00 | 104.17 |
Annual Sum or Average | 3714.00 | 0.51 | 2458.32 | 20.98 | 1101.83 | 3633.50 | 1218.50 | 22.12 | 990.50 | 3035.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 911.09 | 18.95 | 56.33 | 182.00 | 567.91 | 21.16 | 57.00 | 104.17 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3343.46 | 22.20 | 148.50 | 406.33 | 1682.49 | 23.20 | 103.83 | 370.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 02-JAN-10:00 | 490.08 | 14.23 | 0.00 | 176.83 | 269.03 | 16.43 | 0.00 | 45.33 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 620.74 | 15.47 | 0.00 | 213.83 | 353.27 | 17.73 | 0.00 | 126.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 834.48 | 17.01 | 0.00 | 297.33 | 497.24 | 19.27 | 4.00 | 214.67 |
April | 379.50 | 0.50 | 0.48 | 01-APR-07:10 | 980.20 | 17.76 | 0.00 | 347.83 | 570.78 | 19.89 | 31.83 | 300.33 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1222.56 | 20.01 | 40.00 | 399.33 | 700.78 | 22.06 | 162.17 | 366.67 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:19 | 1281.10 | 21.20 | 60.83 | 412.67 | 757.07 | 23.27 | 193.50 | 383.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1083.92 | 20.32 | 79.33 | 423.50 | 651.77 | 22.39 | 180.00 | 382.17 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 951.82 | 17.84 | 0.00 | 390.67 | 584.43 | 20.03 | 53.83 | 344.67 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 906.39 | 17.88 | 0.00 | 313.17 | 553.58 | 20.10 | 16.50 | 254.83 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:09 | 675.74 | 16.03 | 0.00 | 258.50 | 412.10 | 18.37 | 0.33 | 163.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-09:00 | 527.98 | 14.57 | 0.00 | 189.67 | 289.61 | 16.71 | 0.00 | 64.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 456.51 | 14.21 | 0.00 | 151.17 | 269.27 | 16.68 | 0.00 | 35.50 |
Annual Sum or Average | 3714.00 | 0.52 | 904.42 | 17.80 | 180.17 | 3574.50 | 533.52 | 19.97 | 642.17 | 2682.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 456.51 | 14.21 | 0.00 | 151.17 | 269.03 | 16.43 | 0.00 | 35.50 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1281.10 | 21.20 | 79.33 | 423.50 | 757.07 | 23.27 | 193.50 | 383.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-10:30 | 1020.26 | 18.86 | 65.17 | 199.50 | 560.81 | 21.16 | 68.33 | 136.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-09:20 | 1467.67 | 19.86 | 66.67 | 228.83 | 768.83 | 21.67 | 71.67 | 181.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2351.12 | 22.14 | 78.17 | 304.67 | 1270.38 | 23.10 | 93.67 | 251.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2820.83 | 20.83 | 105.50 | 344.17 | 1239.75 | 20.75 | 59.67 | 305.83 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2912.82 | 17.71 | 52.50 | 390.33 | 1579.16 | 18.62 | 11.67 | 354.67 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2981.49 | 17.33 | 42.83 | 401.67 | 1352.65 | 18.42 | 1.17 | 361.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:10 | 3282.06 | 16.47 | 58.83 | 402.67 | 1444.99 | 17.24 | 4.67 | 360.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3109.00 | 19.27 | 75.83 | 380.00 | 1798.21 | 20.73 | 54.50 | 341.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3432.57 | 22.97 | 100.50 | 314.67 | 1944.62 | 23.91 | 95.67 | 270.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2348.42 | 22.32 | 87.33 | 272.00 | 1070.48 | 23.22 | 84.83 | 224.33 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1090.60 | 18.82 | 63.33 | 208.50 | 583.82 | 20.51 | 59.83 | 140.17 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:00 | 1090.76 | 20.31 | 48.67 | 182.00 | 585.68 | 21.07 | 49.83 | 100.67 |
Annual Sum or Average | 3714.00 | 0.51 | 2524.17 | 19.42 | 845.33 | 3629.00 | 1271.95 | 20.49 | 655.50 | 3028.50 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1020.26 | 16.47 | 42.83 | 182.00 | 560.81 | 17.24 | 1.17 | 100.67 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3432.57 | 22.97 | 105.50 | 402.67 | 1944.62 | 23.91 | 95.67 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.31 | 30.49 | 207.17 | 216.17 | 2123.85 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.28 | 32.09 | 231.50 | 240.50 | 1973.39 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.42 | 32.25 | 207.67 | 309.83 | 1574.26 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.41 | 14.68 | 0.00 | 342.83 | 1140.44 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.79 | 14.64 | 0.00 | 382.67 | 1033.46 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.73 | 14.46 | 0.00 | 392.00 | 952.27 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.39 | 13.10 | 0.00 | 389.33 | 863.25 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.18 | 14.23 | 0.00 | 369.33 | 1040.53 | 17.80 | 5.67 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.76 | 17.24 | 27.00 | 317.83 | 1375.12 | 19.08 | 29.67 | 282.67 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.68 | 33.75 | 218.00 | 282.33 | 1850.18 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.99 | 30.64 | 215.33 | 222.17 | 2389.04 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.89 | 34.93 | 149.17 | 204.83 | 3041.51 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.81 | 21.19 | 1255.83 | 3669.83 | 1443.68 | 21.56 | 847.17 | 3189.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.39 | 13.10 | 0.00 | 204.83 | 863.25 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.42 | 34.93 | 231.50 | 392.00 | 3041.51 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.63 | 18.45 | 61.33 | 197.00 | 546.64 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.96 | 19.19 | 68.00 | 225.50 | 754.71 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.99 | 21.61 | 79.00 | 300.00 | 1137.92 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.69 | 20.65 | 105.33 | 344.50 | 1525.45 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.61 | 20.60 | 132.33 | 388.33 | 1209.34 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.69 | 19.80 | 89.00 | 400.67 | 1614.57 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.71 | 20.13 | 146.50 | 404.00 | 1243.00 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3196.03 | 20.22 | 98.50 | 373.50 | 1398.18 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.31 | 21.30 | 82.67 | 319.67 | 1474.21 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.30 | 21.29 | 81.00 | 267.83 | 1047.40 | 22.42 | 76.83 | 221.17 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.37 | 18.45 | 65.67 | 203.67 | 572.12 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.38 | 21.01 | 56.33 | 178.83 | 556.71 | 21.88 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.52 | 20.24 | 1065.67 | 3603.50 | 1167.51 | 21.81 | 909.33 | 2982.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.63 | 18.45 | 56.33 | 178.83 | 546.64 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3196.03 | 21.61 | 146.50 | 404.00 | 1614.57 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.86 | 10.05 | 0.00 | 172.50 | 258.54 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 598.02 | 11.55 | 0.00 | 210.33 | 340.49 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.54 | 13.48 | 0.00 | 293.00 | 480.87 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.73 | 14.26 | 0.00 | 346.00 | 551.71 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.28 | 16.05 | 26.67 | 397.83 | 676.44 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.96 | 18.31 | 59.00 | 411.00 | 732.10 | 21.51 | 73.17 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.28 | 15.66 | 44.67 | 420.83 | 631.63 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.73 | 14.48 | 0.00 | 389.17 | 567.23 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.52 | 14.66 | 0.00 | 311.17 | 535.98 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.67 | 12.50 | 0.00 | 255.67 | 398.59 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.67 | 10.41 | 0.00 | 184.00 | 278.51 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.08 | 10.25 | 0.00 | 145.00 | 259.03 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.66 | 14.06 | 130.33 | 3536.50 | 515.85 | 17.78 | 212.67 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.08 | 10.05 | 0.00 | 145.00 | 258.54 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.96 | 18.31 | 59.00 | 420.83 | 732.10 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.65 | 18.46 | 64.83 | 197.67 | 538.11 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.40 | 19.45 | 66.50 | 227.17 | 721.52 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.33 | 21.74 | 78.17 | 302.17 | 1215.08 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.70 | 20.40 | 105.50 | 342.00 | 1185.20 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2827.03 | 17.22 | 52.33 | 389.67 | 1514.42 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.82 | 16.84 | 42.83 | 398.50 | 1290.58 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.66 | 15.98 | 58.83 | 399.00 | 1377.42 | 17.07 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.21 | 18.82 | 75.83 | 376.67 | 1722.52 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.71 | 22.57 | 100.50 | 312.67 | 1840.65 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.19 | 21.93 | 87.33 | 269.00 | 991.96 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.57 | 18.40 | 62.83 | 206.83 | 559.45 | 20.38 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.11 | 19.91 | 48.67 | 180.50 | 560.32 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.21 | 18.98 | 844.17 | 3601.83 | 1211.87 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.65 | 15.98 | 42.83 | 180.50 | 538.11 | 17.07 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.71 | 22.57 | 105.50 | 399.00 | 1840.65 | 23.51 | 91.33 | 358.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.51 | 0.48 | 01-JAN-09:50 | 2628.29 | 30.49 | 207.17 | 216.17 | 2123.78 | 33.20 | 222.50 | 182.50 |
February | 259.50 | 0.50 | 0.48 | 01-FEB-08:39 | 4546.23 | 32.09 | 231.50 | 240.50 | 1973.30 | 27.94 | 157.17 | 219.00 |
March | 247.00 | 0.50 | 0.48 | 01-MAR-07:30 | 7587.32 | 32.25 | 207.67 | 309.83 | 1574.14 | 18.97 | 12.33 | 263.33 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 2076.28 | 14.68 | 0.00 | 342.83 | 1140.35 | 18.19 | 10.50 | 302.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:10 | 1906.67 | 14.64 | 0.00 | 382.67 | 1033.37 | 18.09 | 3.33 | 339.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:00 | 1665.64 | 14.46 | 0.00 | 392.00 | 952.20 | 17.92 | 0.00 | 340.00 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-05:30 | 1481.30 | 13.10 | 0.00 | 389.33 | 863.19 | 16.60 | 1.00 | 331.67 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:00 | 1751.09 | 14.23 | 0.00 | 369.33 | 1040.46 | 17.80 | 5.83 | 322.17 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2846.65 | 17.25 | 27.00 | 317.83 | 1375.02 | 19.08 | 29.67 | 282.50 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:49 | 7032.63 | 33.75 | 218.00 | 282.33 | 1850.07 | 20.32 | 28.33 | 254.50 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:09 | 2948.96 | 30.64 | 215.33 | 222.17 | 2388.97 | 32.83 | 227.00 | 189.67 |
December | 160.33 | 0.50 | 0.48 | 01-DEC-09:39 | 3551.91 | 34.93 | 149.17 | 204.83 | 3041.45 | 36.50 | 149.67 | 161.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2992.73 | 21.19 | 1255.83 | 3669.83 | 1443.60 | 21.56 | 847.33 | 3189.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 1481.30 | 13.10 | 0.00 | 204.83 | 863.19 | 16.60 | 0.00 | 161.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 7587.32 | 34.93 | 231.50 | 392.00 | 3041.45 | 36.50 | 227.00 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-09:50 | 881.60 | 18.45 | 61.33 | 197.00 | 546.60 | 20.98 | 72.50 | 124.00 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-08:30 | 1425.92 | 19.19 | 68.00 | 225.50 | 754.66 | 21.67 | 74.33 | 174.83 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:30 | 2589.95 | 21.61 | 79.00 | 300.00 | 1137.86 | 22.82 | 80.50 | 248.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2721.63 | 20.65 | 105.33 | 344.50 | 1525.38 | 23.02 | 95.33 | 303.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-06:00 | 2816.53 | 20.60 | 132.33 | 388.33 | 1209.26 | 21.17 | 85.17 | 344.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:10 | 2941.63 | 19.81 | 89.00 | 400.83 | 1614.50 | 22.11 | 75.83 | 351.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-04:00 | 2778.66 | 20.14 | 146.50 | 404.00 | 1242.95 | 20.67 | 87.17 | 365.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:30 | 3195.99 | 20.23 | 98.50 | 373.50 | 1398.12 | 21.80 | 71.33 | 332.83 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2656.27 | 21.30 | 82.67 | 319.67 | 1474.15 | 22.80 | 67.67 | 280.33 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:40 | 2374.28 | 21.29 | 81.00 | 267.83 | 1047.35 | 22.42 | 76.83 | 221.00 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-07:00 | 1081.33 | 18.45 | 65.67 | 203.67 | 572.09 | 20.92 | 67.83 | 137.83 |
December | 160.33 | 0.53 | 0.48 | 01-DEC-09:39 | 1034.36 | 21.01 | 56.33 | 178.83 | 556.68 | 21.89 | 54.83 | 98.33 |
Annual Sum or Average | 3714.00 | 0.51 | 2383.47 | 20.24 | 1065.67 | 3603.67 | 1167.45 | 21.81 | 909.33 | 2981.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 881.60 | 18.45 | 56.33 | 178.83 | 546.60 | 20.67 | 54.83 | 98.33 | |
Maximum of Months | 471.00 | 0.53 | 0.48 | 3195.99 | 21.61 | 146.50 | 404.00 | 1614.50 | 23.02 | 95.33 | 365.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.56 | 0.48 | 02-JAN-11:09 | 471.83 | 10.05 | 0.00 | 172.50 | 258.52 | 13.60 | 0.00 | 33.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:20 | 597.99 | 11.55 | 0.00 | 210.33 | 340.46 | 15.12 | 0.00 | 120.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 804.51 | 13.48 | 0.00 | 293.00 | 480.83 | 17.02 | 0.00 | 205.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:10 | 945.69 | 14.26 | 0.00 | 346.00 | 551.68 | 17.70 | 0.17 | 294.67 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:10 | 1176.23 | 16.06 | 26.67 | 397.83 | 676.39 | 19.98 | 51.33 | 362.00 |
June | 375.17 | 0.50 | 0.48 | 01-JUN-05:30 | 1236.93 | 18.31 | 59.00 | 411.00 | 732.06 | 21.51 | 73.33 | 380.67 |
July | 471.00 | 0.51 | 0.48 | 01-JUL-04:00 | 1043.25 | 15.66 | 44.67 | 420.83 | 631.59 | 20.52 | 86.50 | 378.33 |
August | 366.67 | 0.50 | 0.48 | 01-AUG-05:49 | 919.70 | 14.48 | 0.00 | 389.17 | 567.20 | 18.09 | 1.50 | 339.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 873.50 | 14.66 | 0.00 | 311.17 | 535.95 | 18.16 | 0.00 | 247.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:20 | 650.65 | 12.50 | 0.00 | 255.67 | 398.56 | 16.11 | 0.00 | 156.00 |
November | 242.67 | 0.55 | 0.48 | 01-NOV-10:09 | 508.64 | 10.42 | 0.00 | 184.00 | 278.48 | 13.91 | 0.00 | 53.00 |
December | 160.33 | 0.57 | 0.48 | 01-DEC-10:09 | 438.06 | 10.25 | 0.00 | 145.00 | 259.01 | 14.04 | 0.00 | 28.67 |
Annual Sum or Average | 3714.00 | 0.52 | 871.63 | 14.06 | 130.33 | 3536.50 | 515.82 | 17.78 | 212.83 | 2599.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 438.06 | 10.05 | 0.00 | 145.00 | 258.52 | 13.60 | 0.00 | 28.67 | |
Maximum of Months | 471.00 | 0.57 | 0.48 | 1236.93 | 18.31 | 59.00 | 420.83 | 732.06 | 21.51 | 86.50 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.53 | 0.48 | 01-JAN-12:00 | 989.62 | 18.46 | 64.83 | 197.67 | 538.07 | 21.05 | 67.50 | 129.83 |
February | 259.50 | 0.52 | 0.48 | 01-FEB-09:20 | 1422.37 | 19.45 | 66.50 | 227.17 | 721.47 | 20.56 | 60.67 | 175.67 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-08:20 | 2286.28 | 21.75 | 78.17 | 302.17 | 1215.01 | 22.90 | 91.33 | 245.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:30 | 2709.64 | 20.41 | 105.50 | 342.00 | 1185.12 | 20.61 | 55.00 | 303.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:30 | 2826.95 | 17.22 | 52.33 | 389.67 | 1514.34 | 18.45 | 8.33 | 351.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:10 | 2862.76 | 16.84 | 42.83 | 398.50 | 1290.51 | 18.24 | 0.83 | 358.83 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-06:19 | 3151.60 | 15.98 | 58.83 | 399.00 | 1377.35 | 17.08 | 4.00 | 357.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:19 | 3022.18 | 18.82 | 75.83 | 376.67 | 1722.46 | 20.58 | 54.17 | 337.50 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:49 | 3341.68 | 22.57 | 100.50 | 312.67 | 1840.58 | 23.51 | 90.83 | 266.00 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-08:30 | 2285.16 | 21.93 | 87.33 | 269.00 | 991.91 | 21.85 | 73.50 | 218.83 |
November | 242.67 | 0.52 | 0.48 | 01-NOV-09:50 | 1057.54 | 18.41 | 62.83 | 206.83 | 559.41 | 20.39 | 58.50 | 132.67 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:00 | 1056.10 | 19.91 | 48.67 | 180.50 | 560.29 | 20.96 | 49.67 | 94.00 |
Annual Sum or Average | 3714.00 | 0.51 | 2441.16 | 18.98 | 844.17 | 3601.83 | 1211.81 | 20.17 | 614.33 | 2971.00 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 989.62 | 15.98 | 42.83 | 180.50 | 538.07 | 17.08 | 0.83 | 94.00 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 3341.68 | 22.57 | 105.50 | 399.00 | 1840.58 | 23.51 | 91.33 | 358.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.716907E+10 | 11647.36 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468387E+10 | 11498.36 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169081E+10 | 10613.99 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.518884E+09 | 8141.04 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48692973.02 | 4064.70 | 18-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 381884.38 | 5.51 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 962797.96 | 5.32 | 09-AUG-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 573580.58 | 667.73 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159342E+09 | 3323.13 | 31-OCT-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302535E+10 | 10716.28 | 13-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595720E+10 | 11663.95 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.716907E+10 | 11663.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354830E+09 | 9669.16 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354830E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.354830E+09 | 9669.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.433848E+10 | 8373.28 | 06-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240995E+10 | 8118.77 | 09-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161656E+10 | 7954.48 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.910715E+09 | 8147.18 | 26-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.603478E+09 | 8242.22 | 11-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.292130E+09 | 7999.20 | 08-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 53931858.55 | 7268.18 | 03-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70321293.09 | 7922.78 | 03-AUG-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258965E+09 | 7997.29 | 27-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839929E+09 | 7969.96 | 11-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214732E+10 | 7985.27 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331428E+10 | 8264.86 | 26-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 53931858.55 | 7268.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433848E+10 | 8373.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134877E+10 | 5480.35 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.480422E+09 | 5404.79 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 54496115.96 | 5296.50 | 24-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4194362.23 | 5272.42 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 371096.23 | 948.27 | 31-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185447E+09 | 5295.97 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.736369E+09 | 5489.86 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134877E+10 | 5489.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221566E+10 | 5894.90 | 06-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.966280E+09 | 5739.60 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177807E+09 | 5639.17 | 02-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18816042.82 | 5629.54 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3589863.87 | 3497.85 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322990E+09 | 5635.48 | 18-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121334E+10 | 5870.15 | 26-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221566E+10 | 5894.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137061E+10 | 5699.72 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492630E+09 | 5620.98 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72677561.56 | 5504.67 | 06-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7965324.50 | 5489.62 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 182023.57 | 73.66 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190626E+09 | 5507.09 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.738638E+09 | 5709.54 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.287333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137061E+10 | 5709.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.756921E+10 | 12916.90 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.513369E+10 | 12822.56 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268460E+10 | 11214.65 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113311E+10 | 8567.92 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.267352E+09 | 4812.88 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6781226.95 | 1137.89 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 329370.35 | 4.83 | 31-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 832631.53 | 4.78 | 14-AUG-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34015869.11 | 2436.59 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.620615E+09 | 5072.00 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380651E+10 | 11643.94 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658365E+10 | 12685.95 | 26-DEC-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 329370.35 | 4.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.756921E+10 | 12916.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123006E+10 | 14482.03 | 03-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155595E+09 | 14449.33 | 21-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3221339.44 | 10466.88 | 06-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31917999.16 | 14490.72 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.337619E+09 | 14479.17 | 27-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123006E+10 | 14490.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138620E+10 | 8697.83 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.468103E+09 | 8628.38 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59787517.88 | 8523.16 | 08-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7700394.67 | 8508.75 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8146976.91 | 4461.27 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311730E+09 | 8563.06 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.944963E+09 | 8563.26 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138620E+10 | 8697.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111026E+10 | 5969.11 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.403631E+09 | 5921.42 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41739372.88 | 5853.17 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3717528.00 | 5838.91 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10036727.78 | 5237.01 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265778E+09 | 5877.20 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750724E+09 | 5957.94 | 26-DEC-13:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111026E+10 | 5969.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.191396E+10 | 6184.65 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758587E+09 | 6112.47 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95284308.64 | 6072.38 | 06-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9559240.01 | 6044.22 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15886528.72 | 6052.43 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.456041E+09 | 6071.96 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128630E+10 | 6275.08 | 26-DEC-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191396E+10 | 6275.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119689E+10 | 5997.39 | 06-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439518E+09 | 5949.47 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60995734.90 | 5883.97 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7110171.46 | 5880.77 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10229093.36 | 3698.25 | 16-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.288893E+09 | 5903.92 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.803131E+09 | 5904.05 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119689E+10 | 5997.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.792022E+10 | 12318.62 | 06-JAN-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540835E+10 | 11795.85 | 08-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315651E+10 | 12434.98 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146131E+10 | 11714.94 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.426415E+09 | 5859.04 | 18-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23234118.52 | 2015.19 | 15-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 318829.78 | 5.05 | 31-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 775474.35 | 4.96 | 29-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80797884.14 | 3430.15 | 27-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.923272E+09 | 5892.63 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418961E+10 | 11722.85 | 24-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.702305E+10 | 12447.18 | 26-DEC-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.306139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 318829.78 | 4.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.792022E+10 | 12447.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.370176E+10 | 20662.14 | 03-JAN-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142285E+10 | 20672.24 | 23-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149650E+09 | 20665.20 | 13-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 452174.48 | 3792.38 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29111042.60 | 20503.72 | 23-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.923048E+09 | 20668.56 | 27-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243859E+10 | 20662.54 | 28-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370176E+10 | 20672.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.258373E+10 | 10216.30 | 30-JAN-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122955E+10 | 10215.15 | 22-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375832E+09 | 10428.27 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102722E+09 | 10189.96 | 20-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5162897.91 | 8916.47 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2792458.07 | 2624.53 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135354E+09 | 10189.92 | 27-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.994269E+09 | 10215.14 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208393E+10 | 10438.16 | 26-DEC-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.258373E+10 | 10438.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207840E+10 | 7097.88 | 06-JAN-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101569E+10 | 6952.98 | 09-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.253419E+09 | 6907.41 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45119238.08 | 6745.51 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3540049.92 | 6008.28 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1055673.27 | 2103.33 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107893E+09 | 6759.46 | 30-OCT-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.782237E+09 | 6766.14 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165416E+10 | 6922.74 | 26-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.207840E+10 | 7097.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.338694E+10 | 7770.96 | 07-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180940E+10 | 7659.02 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.536627E+09 | 7461.30 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122182E+09 | 7310.29 | 18-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4679813.71 | 7298.66 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4461838.22 | 3158.94 | 27-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197858E+09 | 7306.86 | 13-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133163E+10 | 7413.96 | 13-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274588E+10 | 7576.64 | 26-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338694E+10 | 7770.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214337E+10 | 7470.88 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108861E+10 | 7030.47 | 13-FEB-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327915E+09 | 7174.54 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78818297.98 | 7010.16 | 20-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3421303.13 | 6380.11 | 18-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2242256.11 | 1704.36 | 28-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123554E+09 | 7009.92 | 17-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.835690E+09 | 7027.18 | 28-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172449E+10 | 7190.58 | 26-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214337E+10 | 7470.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1258189.69 | 1125441.30 | 1070.81 | 02-JAN-10:30 | 959.52 | 0.00 |
February | 0.00 | 0.00 | 0.200641E+09 | 0.184550E+09 | 12969.88 | 27-FEB-15:10 | 12969.88 | 0.00 |
March | 0.00 | 0.00 | 0.530421E+09 | 0.476885E+09 | 10915.52 | 18-MAR-16:00 | 10915.52 | 0.00 |
April | 0.00 | 0.00 | 0.639404E+10 | 0.619764E+10 | 51578.74 | 27-APR-15:00 | 51578.74 | 0.00 |
May | 0.00 | 0.00 | 0.800266E+10 | 0.721387E+10 | 47197.76 | 15-MAY-16:00 | 47197.76 | 0.00 |
June | 0.00 | 0.00 | 0.143724E+11 | 0.134310E+11 | 52946.67 | 28-JUN-15:30 | 52946.67 | 0.00 |
July | 0.00 | 0.00 | 0.276307E+11 | 0.245183E+11 | 72039.91 | 31-JUL-15:50 | 65857.24 | 0.00 |
August | 0.00 | 0.00 | 0.375451E+11 | 0.329391E+11 | 71006.32 | 10-AUG-15:40 | 67198.63 | 0.00 |
September | 0.00 | 0.00 | 0.139503E+11 | 0.117035E+11 | 58396.42 | 12-SEP-16:00 | 54336.93 | 0.00 |
October | 0.00 | 0.00 | 0.266424E+10 | 0.252042E+10 | 35126.82 | 04-OCT-15:00 | 35126.82 | 0.00 |
November | 0.00 | 0.00 | 0.362717E+09 | 0.252449E+09 | 18890.90 | 04-NOV-15:00 | 14516.46 | 0.00 |
December | 0.00 | 0.00 | 6678546.16 | 6169609.10 | 3550.29 | 05-DEC-12:00 | 3369.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111661E+12 | 0.994451E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1258189.69 | 1125441.30 | 1070.81 | 959.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.375451E+11 | 0.329391E+11 | 72039.91 | 67198.63 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 203097.43 | 163444.72 | 1353.98 | 11-JAN-07:05 | 1089.63 | 0.00 |
February | 0.00 | 0.00 | 0.182989E+09 | 0.167667E+09 | 12920.73 | 27-FEB-15:05 | 12920.73 | 0.00 |
March | 0.00 | 0.00 | 0.279433E+09 | 0.249260E+09 | 11221.09 | 18-MAR-14:05 | 11221.09 | 0.00 |
April | 0.00 | 0.00 | 0.343582E+10 | 0.330552E+10 | 50319.97 | 27-APR-14:05 | 50319.97 | 0.00 |
May | 0.00 | 0.00 | 0.712293E+10 | 0.640224E+10 | 44026.64 | 04-MAY-15:00 | 44026.64 | 0.00 |
June | 0.00 | 0.00 | 0.130912E+11 | 0.122071E+11 | 49084.63 | 28-JUN-15:30 | 49084.63 | 0.00 |
July | 0.00 | 0.00 | 0.247676E+11 | 0.219924E+11 | 67971.42 | 31-JUL-14:05 | 60862.30 | 0.00 |
August | 0.00 | 0.00 | 0.327368E+11 | 0.287115E+11 | 67015.65 | 10-AUG-14:05 | 60549.30 | 0.00 |
September | 0.00 | 0.00 | 0.121953E+11 | 0.101700E+11 | 54286.94 | 13-SEP-14:05 | 41905.70 | 0.00 |
October | 0.00 | 0.00 | 0.158148E+10 | 0.148336E+10 | 31703.47 | 04-OCT-15:00 | 31703.47 | 0.00 |
November | 0.00 | 0.00 | 0.340540E+09 | 0.239897E+09 | 18844.83 | 04-NOV-14:05 | 14933.29 | 0.00 |
December | 0.00 | 0.00 | 235862.49 | 161238.58 | 1572.42 | 29-DEC-07:05 | 1074.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.957345E+11 | 0.849293E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 203097.43 | 161238.58 | 1353.98 | 1074.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.327368E+11 | 0.287115E+11 | 67971.42 | 60862.30 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.187718E+09 | 0.166529E+09 | 12047.39 | 27-FEB-15:00 | 12047.39 | 0.00 |
March | 0.00 | 0.00 | 0.421801E+09 | 0.384852E+09 | 11377.32 | 01-MAR-15:00 | 11377.32 | 0.00 |
April | 0.00 | 0.00 | 0.364843E+10 | 0.348248E+10 | 57162.53 | 27-APR-14:40 | 57162.53 | 0.00 |
May | 0.00 | 0.00 | 0.744064E+10 | 0.661351E+10 | 47729.89 | 04-MAY-15:00 | 47729.89 | 0.00 |
June | 0.00 | 0.00 | 0.137330E+11 | 0.127004E+11 | 56945.21 | 28-JUN-15:20 | 56945.21 | 0.00 |
July | 0.00 | 0.00 | 0.263174E+11 | 0.231729E+11 | 74463.78 | 31-JUL-14:40 | 67734.67 | 0.00 |
August | 0.00 | 0.00 | 0.343100E+11 | 0.299547E+11 | 74478.81 | 10-AUG-14:50 | 69282.63 | 0.00 |
September | 0.00 | 0.00 | 0.122129E+11 | 0.100581E+11 | 53643.15 | 14-SEP-13:30 | 42360.83 | 0.00 |
October | 0.00 | 0.00 | 0.144981E+10 | 0.134149E+10 | 31099.77 | 04-OCT-15:00 | 31099.77 | 0.00 |
November | 0.00 | 0.00 | 0.346211E+09 | 0.235736E+09 | 18724.29 | 04-NOV-14:20 | 14028.89 | 0.00 |
December | 0.00 | 0.00 | 68427.90 | 51442.45 | 228.09 | 18-DEC-06:10 | 171.47 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100068E+12 | 0.881107E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.343100E+11 | 0.299547E+11 | 74478.81 | 69282.63 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 19646.46 | 150171.43 | 25-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11632.31 | 153710.22 | 09-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 4205.80 | 152296.43 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1697.05 | 124764.09 | 19-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 506.94 | 64550.75 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 120.96 | 11443.85 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.54 | 9902.67 | 27-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.98 | 10031.54 | 03-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 147.52 | 30429.29 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1176.95 | 116650.49 | 30-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 7690.77 | 143128.52 | 16-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14946.00 | 146442.86 | 26-DEC-07:12 |
Annual Sum or Average | 0.00 | 5128.26 | ||||
Minimum of Months | 0.00 | 0.00 | 19.54 | 9902.67 | ||
Maximum of Months | 0.00 | 0.00 | 19646.46 | 153710.22 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1702.15 | 6226.75 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1724.48 | 6234.21 | 10-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1823.75 | 6212.93 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1649.61 | 6074.28 | 03-APR-11:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1649.95 | 5885.01 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1631.24 | 5653.23 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1446.19 | 5455.82 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1586.59 | 5376.20 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1495.25 | 5493.63 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1541.18 | 5706.34 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1627.90 | 5930.79 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1615.25 | 6114.33 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1623.90 | ||||
Minimum of Months | 0.00 | 0.00 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 1823.75 | 6234.21 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116777E+10 | 0.29 | 2511.88 | 02-JAN-06:11 | 0.78 |
February | 0.108009E+10 | 0.29 | 1730.04 | 27-FEB-15:30 | 0.64 |
March | 0.154017E+10 | 0.31 | 2566.15 | 20-MAR-06:03 | 0.79 |
April | 0.189459E+10 | 0.32 | 6241.33 | 27-APR-14:50 | 1.32 |
May | 0.266116E+10 | 0.38 | 7097.49 | 15-MAY-14:50 | 1.44 |
June | 0.332059E+10 | 0.43 | 6910.61 | 28-JUN-15:20 | 1.41 |
July | 0.420661E+10 | 0.46 | 10195.13 | 31-JUL-15:10 | 1.80 |
August | 0.493518E+10 | 0.51 | 10195.13 | 14-AUG-15:10 | 1.80 |
September | 0.321734E+10 | 0.41 | 9395.93 | 11-SEP-15:50 | 1.71 |
October | 0.200387E+10 | 0.32 | 6643.87 | 04-OCT-15:40 | 1.39 |
November | 0.127696E+10 | 0.28 | 3270.86 | 06-NOV-07:03 | 0.90 |
December | 0.114338E+10 | 0.28 | 1462.08 | 01-DEC-07:01 | 0.60 |
Annual Sum or Average | 0.284477E+11 | 0.36 | |||
Minimum of Months | 0.108009E+10 | 0.28 | 1462.08 | 0.60 | |
Maximum of Months | 0.493518E+10 | 0.51 | 10195.13 | 1.80 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.104464E+10 | 0.29 | 2607.82 | 02-JAN-06:11 | 0.83 |
February | 0.933967E+09 | 0.28 | 2607.82 | 06-FEB-07:01 | 0.83 |
March | 0.120034E+10 | 0.30 | 2306.34 | 01-MAR-13:01 | 0.78 |
April | 0.156121E+10 | 0.32 | 6700.44 | 27-APR-14:05 | 1.45 |
May | 0.225394E+10 | 0.37 | 7324.18 | 15-MAY-14:05 | 1.54 |
June | 0.280011E+10 | 0.41 | 6499.87 | 28-JUN-14:05 | 1.42 |
July | 0.350439E+10 | 0.44 | 9091.34 | 31-JUL-14:30 | 1.76 |
August | 0.400212E+10 | 0.48 | 9464.61 | 14-AUG-06:02 | 1.81 |
September | 0.250974E+10 | 0.38 | 7996.17 | 11-SEP-15:00 | 1.62 |
October | 0.143292E+10 | 0.30 | 5577.98 | 04-OCT-15:10 | 1.30 |
November | 0.967647E+09 | 0.28 | 2607.82 | 24-NOV-07:01 | 0.83 |
December | 0.984471E+09 | 0.28 | 2607.82 | 11-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.231955E+11 | 0.34 | |||
Minimum of Months | 0.933967E+09 | 0.28 | 2306.34 | 0.78 | |
Maximum of Months | 0.400212E+10 | 0.48 | 9464.61 | 1.81 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127677E+10 | 0.35 | 2506.27 | 02-JAN-06:11 | 0.76 |
February | 0.107260E+10 | 0.32 | 2506.27 | 01-FEB-07:03 | 0.76 |
March | 0.125574E+10 | 0.33 | 2506.27 | 06-MAR-06:11 | 0.76 |
April | 0.150508E+10 | 0.32 | 6453.32 | 27-APR-14:30 | 1.31 |
May | 0.208793E+10 | 0.36 | 6981.26 | 15-MAY-14:40 | 1.39 |
June | 0.256653E+10 | 0.39 | 6558.24 | 28-JUN-15:20 | 1.33 |
July | 0.325634E+10 | 0.41 | 8955.66 | 31-JUL-14:50 | 1.61 |
August | 0.363996E+10 | 0.44 | 8892.66 | 10-AUG-15:10 | 1.60 |
September | 0.221907E+10 | 0.36 | 7189.18 | 11-SEP-14:50 | 1.40 |
October | 0.134117E+10 | 0.31 | 4747.24 | 04-OCT-15:00 | 1.09 |
November | 0.107857E+10 | 0.31 | 2506.27 | 10-NOV-07:02 | 0.76 |
December | 0.114565E+10 | 0.31 | 2506.27 | 01-DEC-07:01 | 0.76 |
Annual Sum or Average | 0.224454E+11 | 0.35 | |||
Minimum of Months | 0.107260E+10 | 0.31 | 2506.27 | 0.76 | |
Maximum of Months | 0.363996E+10 | 0.44 | 8955.66 | 1.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.363459E+09 | 0.330384E+09 | 544.02 | 17-JAN-08:10 | 494.51 | 494.51 | 44.30 | 1.76 |
February | 0.207766E+09 | 0.188860E+09 | 543.71 | 18-FEB-07:03 | 494.23 | 494.23 | 41.13 | 1.76 |
March | 85907407.72 | 78089833.62 | 492.85 | 06-MAR-07:02 | 448.00 | 448.00 | 39.72 | 1.47 |
April | 34632944.06 | 31481346.15 | 465.72 | 18-APR-06:02 | 423.34 | 423.34 | 35.43 | 1.19 |
May | 12018754.91 | 10925048.22 | 360.60 | 18-MAY-06:03 | 327.78 | 327.78 | 33.45 | 0.58 |
June | 3709753.69 | 3372166.10 | 100.07 | 15-JUN-06:05 | 90.96 | 90.96 | 35.48 | 0.11 |
July | 501836.93 | 456169.77 | 81.92 | 03-JUL-06:07 | 74.47 | 74.47 | 37.38 | 0.09 |
August | 919767.49 | 836068.64 | 82.23 | 21-AUG-06:06 | 74.75 | 74.75 | 47.44 | 0.09 |
September | 4027419.78 | 3660924.58 | 196.26 | 27-SEP-06:03 | 178.40 | 178.40 | 36.61 | 0.24 |
October | 25225912.99 | 22930354.91 | 459.03 | 16-OCT-06:03 | 417.26 | 417.26 | 35.54 | 1.12 |
November | 0.146753E+09 | 0.133399E+09 | 523.16 | 24-NOV-07:01 | 475.55 | 475.55 | 42.57 | 1.67 |
December | 0.282339E+09 | 0.256646E+09 | 548.68 | 26-DEC-07:01 | 498.75 | 498.75 | 42.53 | 1.78 |
Annual Sum or Average | 0.116726E+10 | 0.106104E+10 | ||||||
Minimum of Months | 501836.93 | 456169.77 | 81.92 | 74.47 | 74.47 | 33.45 | 0.09 | |
Maximum of Months | 0.363459E+09 | 0.330384E+09 | 548.68 | 498.75 | 498.75 | 47.44 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.14 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:05 | 2.06 | 2.06 | 56.83 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 56.93 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.91 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 57.22 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 57.21 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.22 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.36 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.35 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.20 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 57.10 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.07 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.83 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.20 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 40.08 | 40.08 | 19646.46 | 150171.43 | 25-JAN-07:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 33.11 | 33.11 | 11632.31 | 153710.22 | 09-FEB-07:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.73 | 27.73 | 4205.80 | 152296.43 | 01-MAR-07:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.28 | 25.28 | 1697.05 | 124764.09 | 19-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.78 | 31.78 | 506.94 | 64550.75 | 18-MAY-06:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.14 | 47.14 | 120.96 | 11443.85 | 15-JUN-06:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 37.33 | 37.33 | 19.54 | 9902.67 | 27-JUL-06:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.10 | 33.10 | 27.98 | 10031.54 | 03-AUG-06:06 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 39.08 | 39.08 | 147.52 | 30429.29 | 28-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42.28 | 42.28 | 1176.95 | 116650.49 | 30-OCT-06:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.74 | 29.74 | 7690.77 | 143128.52 | 16-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 35.80 | 35.80 | 14946.00 | 146442.86 | 26-DEC-07:12 |
Annual Sum or Average | 0.00 | 5128.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.28 | 25.28 | 19.54 | 9902.67 | ||
Maximum of Months | 0.00 | 0.00 | 47.14 | 47.14 | 19646.46 | 153710.22 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.14 | 58.14 | 1702.15 | 6226.75 | 31-JAN-12:17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.61 | 57.61 | 1724.48 | 6234.21 | 10-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 1823.75 | 6212.93 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 1649.61 | 6074.28 | 03-APR-11:25 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 1649.95 | 5885.01 | 01-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 1631.24 | 5653.23 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 1446.19 | 5455.82 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.96 | 57.96 | 1586.59 | 5376.20 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 1495.25 | 5493.63 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.03 | 57.03 | 1541.18 | 5706.34 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 1627.90 | 5930.79 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 1615.25 | 6114.33 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 1623.90 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.03 | 57.03 | 1446.19 | 5376.20 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 1823.75 | 6234.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.167974E+11 | 0.00 | 0.00 | 0.116811E+10 | 0.00 | 0.00 |
February | 0.903316E+10 | 0.00 | 0.00 | 0.113017E+10 | 0.00 | 0.00 |
March | 0.361235E+10 | 0.00 | 0.00 | 0.167803E+10 | 0.00 | 0.00 |
April | 0.146057E+10 | 0.00 | 0.00 | 0.338887E+10 | 0.00 | 0.00 |
May | 0.652171E+09 | 0.00 | 0.00 | 0.449405E+10 | 0.00 | 0.00 |
June | 0.292130E+09 | 0.00 | 0.00 | 0.658633E+10 | 0.00 | 0.00 |
July | 54313742.93 | 0.00 | 0.00 | 0.103927E+11 | 0.00 | 0.00 |
August | 71284091.05 | 0.00 | 0.00 | 0.133970E+11 | 0.00 | 0.00 |
September | 0.259538E+09 | 0.00 | 0.00 | 0.633271E+10 | 0.00 | 0.00 |
October | 0.100341E+10 | 0.00 | 0.00 | 0.263663E+10 | 0.00 | 0.00 |
November | 0.587173E+10 | 0.00 | 0.00 | 0.136301E+10 | 0.00 | 0.00 |
December | 0.119598E+11 | 0.00 | 0.00 | 0.114515E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.510679E+11 | 0.00 | 0.00 | 0.537128E+11 | 0.00 | 0.00 |
Minimum of Months | 54313742.93 | 0.00 | 0.00 | 0.113017E+10 | 0.00 | 0.00 |
Maximum of Months | 0.167974E+11 | 0.00 | 0.00 | 0.133970E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.144066E+11 | 0.00 | 0.00 | 0.104469E+10 | 0.00 | 0.00 |
February | 0.735912E+10 | 0.00 | 0.00 | 0.979684E+09 | 0.00 | 0.00 |
March | 0.294562E+10 | 0.00 | 0.00 | 0.127171E+10 | 0.00 | 0.00 |
April | 0.116120E+10 | 0.00 | 0.00 | 0.235381E+10 | 0.00 | 0.00 |
May | 0.267352E+09 | 0.00 | 0.00 | 0.387684E+10 | 0.00 | 0.00 |
June | 6781226.95 | 0.00 | 0.00 | 0.578328E+10 | 0.00 | 0.00 |
July | 329370.35 | 0.00 | 0.00 | 0.906586E+10 | 0.00 | 0.00 |
August | 832631.53 | 0.00 | 0.00 | 0.114130E+11 | 0.00 | 0.00 |
September | 34015869.11 | 0.00 | 0.00 | 0.524473E+10 | 0.00 | 0.00 |
October | 0.664914E+09 | 0.00 | 0.00 | 0.180735E+10 | 0.00 | 0.00 |
November | 0.516087E+10 | 0.00 | 0.00 | 0.104743E+10 | 0.00 | 0.00 |
December | 0.107064E+11 | 0.00 | 0.00 | 0.984534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427140E+11 | 0.00 | 0.00 | 0.448729E+11 | 0.00 | 0.00 |
Minimum of Months | 329370.35 | 0.00 | 0.00 | 0.979684E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144066E+11 | 0.00 | 0.00 | 0.114130E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.218144E+11 | 0.00 | 0.00 | 0.127677E+10 | 0.00 | 0.00 |
February | 0.119745E+11 | 0.00 | 0.00 | 0.111985E+10 | 0.00 | 0.00 |
March | 0.479996E+10 | 0.00 | 0.00 | 0.136333E+10 | 0.00 | 0.00 |
April | 0.181060E+10 | 0.00 | 0.00 | 0.234915E+10 | 0.00 | 0.00 |
May | 0.443219E+09 | 0.00 | 0.00 | 0.378919E+10 | 0.00 | 0.00 |
June | 23234118.52 | 0.00 | 0.00 | 0.570979E+10 | 0.00 | 0.00 |
July | 318829.78 | 0.00 | 0.00 | 0.918872E+10 | 0.00 | 0.00 |
August | 775474.35 | 0.00 | 0.00 | 0.114564E+11 | 0.00 | 0.00 |
September | 91350109.82 | 0.00 | 0.00 | 0.497567E+10 | 0.00 | 0.00 |
October | 0.151704E+10 | 0.00 | 0.00 | 0.168903E+10 | 0.00 | 0.00 |
November | 0.905648E+10 | 0.00 | 0.00 | 0.116052E+10 | 0.00 | 0.00 |
December | 0.176701E+11 | 0.00 | 0.00 | 0.114567E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.692020E+11 | 0.00 | 0.00 | 0.452241E+11 | 0.00 | 0.00 |
Minimum of Months | 318829.78 | 0.00 | 0.00 | 0.111985E+10 | 0.00 | 0.00 |
Maximum of Months | 0.218144E+11 | 0.00 | 0.00 | 0.114564E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116777E+10 | 1258189.69 | 0.167974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108009E+10 | 0.200641E+09 | 0.903316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154017E+10 | 0.530421E+09 | 0.361235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189459E+10 | 0.639404E+10 | 0.146057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266116E+10 | 0.800266E+10 | 0.652171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332059E+10 | 0.143724E+11 | 0.292130E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.420661E+10 | 0.276307E+11 | 54313742.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.493518E+10 | 0.375451E+11 | 71284091.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321734E+10 | 0.139503E+11 | 0.259538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200387E+10 | 0.266424E+10 | 0.100341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127696E+10 | 0.362717E+09 | 0.587173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114338E+10 | 6678546.16 | 0.119598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284477E+11 | 0.111661E+12 | 0.510679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108009E+10 | 1258189.69 | 54313742.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.493518E+10 | 0.375451E+11 | 0.167974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.104464E+10 | 203097.43 | 0.144066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933967E+09 | 0.182989E+09 | 0.735912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120034E+10 | 0.279433E+09 | 0.294562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156121E+10 | 0.343582E+10 | 0.116120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225394E+10 | 0.712293E+10 | 0.267352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280011E+10 | 0.130912E+11 | 6781226.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350439E+10 | 0.247676E+11 | 329370.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400212E+10 | 0.327368E+11 | 832631.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250974E+10 | 0.121953E+11 | 34015869.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143292E+10 | 0.158148E+10 | 0.664914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967647E+09 | 0.340540E+09 | 0.516087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.984471E+09 | 235862.49 | 0.107064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231955E+11 | 0.957345E+11 | 0.427140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.933967E+09 | 203097.43 | 329370.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400212E+10 | 0.327368E+11 | 0.144066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127677E+10 | 0.00 | 0.218144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107260E+10 | 0.187718E+09 | 0.119745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125574E+10 | 0.421801E+09 | 0.479996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150508E+10 | 0.364843E+10 | 0.181060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208793E+10 | 0.744064E+10 | 0.443219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256653E+10 | 0.137330E+11 | 23234118.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325634E+10 | 0.263174E+11 | 318829.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363996E+10 | 0.343100E+11 | 775474.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.221907E+10 | 0.122129E+11 | 91350109.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134117E+10 | 0.144981E+10 | 0.151704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107857E+10 | 0.346211E+09 | 0.905648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114565E+10 | 68427.90 | 0.176701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224454E+11 | 0.100068E+12 | 0.692020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107260E+10 | 0.00 | 318829.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363996E+10 | 0.343100E+11 | 0.218144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116777E+10 | 0.167974E+11 | 0.00 | 0.00 | 338915.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108009E+10 | 0.903316E+10 | 0.00 | 0.00 | 50082578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154017E+10 | 0.361235E+10 | 0.00 | 0.00 | 0.137868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189459E+10 | 0.146057E+10 | 0.00 | 0.00 | 0.149428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266116E+10 | 0.652171E+09 | 0.00 | 0.00 | 0.183288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332059E+10 | 0.292130E+09 | 0.00 | 0.00 | 0.326573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.420661E+10 | 54313742.93 | 0.00 | 0.00 | 0.618611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.493518E+10 | 71284091.05 | 0.00 | 0.00 | 0.846185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.321734E+10 | 0.259538E+09 | 0.00 | 0.00 | 0.311537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.200387E+10 | 0.100341E+10 | 0.00 | 0.00 | 0.632768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127696E+10 | 0.587173E+10 | 0.00 | 0.00 | 86041694.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114338E+10 | 0.119598E+11 | 0.00 | 0.00 | 1769724.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284477E+11 | 0.510679E+11 | 0.00 | 0.00 | 0.252651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.108009E+10 | 54313742.93 | 0.00 | 0.00 | 338915.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.493518E+10 | 0.167974E+11 | 0.00 | 0.00 | 0.846185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.104464E+10 | 0.144066E+11 | 0.00 | 0.00 | 54479.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.933967E+09 | 0.735912E+10 | 0.00 | 0.00 | 45717435.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120034E+10 | 0.294562E+10 | 0.00 | 0.00 | 71371477.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156121E+10 | 0.116120E+10 | 0.00 | 0.00 | 0.792603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225394E+10 | 0.267352E+09 | 0.00 | 0.00 | 0.162291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.280011E+10 | 6781226.95 | 0.00 | 0.00 | 0.298318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350439E+10 | 329370.35 | 0.00 | 0.00 | 0.556146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400212E+10 | 832631.53 | 0.00 | 0.00 | 0.741084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.250974E+10 | 34015869.11 | 0.00 | 0.00 | 0.273499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143292E+10 | 0.664914E+09 | 0.00 | 0.00 | 0.374436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.967647E+09 | 0.516087E+10 | 0.00 | 0.00 | 79783181.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.984471E+09 | 0.107064E+11 | 0.00 | 0.00 | 63114.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231955E+11 | 0.427140E+11 | 0.00 | 0.00 | 0.216774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.933967E+09 | 329370.35 | 0.00 | 0.00 | 54479.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400212E+10 | 0.144066E+11 | 0.00 | 0.00 | 0.741084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.127677E+10 | 0.218144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107260E+10 | 0.119745E+11 | 0.00 | 0.00 | 47247022.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125574E+10 | 0.479996E+10 | 0.00 | 0.00 | 0.107590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150508E+10 | 0.181060E+10 | 0.00 | 0.00 | 0.844071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208793E+10 | 0.443219E+09 | 0.00 | 0.00 | 0.170126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256653E+10 | 23234118.52 | 0.00 | 0.00 | 0.314326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.325634E+10 | 318829.78 | 0.00 | 0.00 | 0.593238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.363996E+10 | 775474.35 | 0.00 | 0.00 | 0.781647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.221907E+10 | 91350109.82 | 0.00 | 0.00 | 0.275660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134117E+10 | 0.151704E+10 | 0.00 | 0.00 | 0.347861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107857E+10 | 0.905648E+10 | 0.00 | 0.00 | 81951757.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114565E+10 | 0.176701E+11 | 0.00 | 0.00 | 18594.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224454E+11 | 0.692020E+11 | 0.00 | 0.00 | 0.227787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107260E+10 | 318829.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.363996E+10 | 0.218144E+11 | 0.00 | 0.00 | 0.781647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773309E+10 | 0.00 | 0.00 | 6892783.05 | 0.00 | 0.210284E+09 | 0.545117E+10 | 0.00 | 0.30 |
February | 0.345389E+10 | 0.00 | 0.00 | 15798687.48 | 0.00 | 0.00 | 0.100879E+11 | 0.00 | 0.37 |
March | 0.914824E+09 | 0.00 | 0.00 | 34619339.63 | 0.00 | 0.00 | 0.177137E+11 | 0.00 | 0.51 |
April | 0.588327E+09 | 11398282.69 | 0.00 | 37789889.27 | 0.00 | 0.00 | 0.163724E+11 | 0.00 | 0.55 |
May | 0.777302E+09 | 5947970.90 | 0.00 | 45976414.57 | 0.00 | 0.00 | 0.214732E+11 | 0.00 | 0.92 |
June | 0.619959E+09 | 8478286.52 | 0.00 | 48447330.28 | 1343954.26 | 0.00 | 0.204021E+11 | 0.00 | 1.10 |
July | 0.601362E+09 | 0.145998E+09 | 0.00 | 44340347.90 | 12019632.70 | 0.00 | 0.146454E+11 | 0.00 | 1.05 |
August | 0.390155E+09 | 0.413820E+09 | 0.00 | 43531628.13 | 14498648.47 | 0.00 | 0.128313E+11 | 0.00 | 1.02 |
September | 0.652138E+09 | 7289016.94 | 0.00 | 45437183.41 | 0.00 | 0.00 | 0.188341E+11 | 0.00 | 1.01 |
October | 0.599668E+09 | 0.00 | 0.00 | 38399351.21 | 0.00 | 0.00 | 0.193870E+11 | 0.00 | 0.67 |
November | 0.198430E+10 | 0.00 | 0.00 | 22997533.53 | 0.00 | 0.00 | 0.138585E+11 | 0.00 | 0.43 |
December | 0.509253E+10 | 0.00 | 0.00 | 13409432.01 | 0.00 | 0.00 | 0.915357E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.234075E+11 | 0.592932E+09 | 0.00 | 0.397640E+09 | 27862235.43 | 0.210284E+09 | 0.180210E+12 | 0.00 | 0.69 |
Minimum of Months | 0.390155E+09 | 0.00 | 0.00 | 6892783.05 | 0.00 | 0.00 | 0.545117E+10 | 0.00 | 0.30 |
Maximum of Months | 0.773309E+10 | 0.413820E+09 | 0.00 | 48447330.28 | 14498648.47 | 0.210284E+09 | 0.214732E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551163E+09 | 0.00 | 0.00 | 0.29 |
February | 0.100888E+11 | 0.00 | 0.00 | 641230.22 | 0.00 | 47204684.99 | 0.858370E+09 | 0.00 | 0.30 |
March | 0.752265E+10 | 0.00 | 0.00 | 6072863.43 | 0.00 | 547010.06 | 0.521991E+10 | 0.00 | 0.34 |
April | 0.413467E+10 | 4994189.11 | 0.00 | 13419145.70 | 4573824.42 | 0.00 | 0.807272E+10 | 0.00 | 0.41 |
May | 0.224174E+10 | 4189721.41 | 0.00 | 23580500.49 | 0.00 | 0.00 | 0.123421E+11 | 0.00 | 0.60 |
June | 0.121301E+10 | 4783740.16 | 0.00 | 28364571.95 | 1234226.49 | 0.00 | 0.126630E+11 | 0.00 | 0.73 |
July | 0.108935E+10 | 0.102501E+09 | 0.00 | 26621396.73 | 9289984.53 | 0.00 | 0.908884E+10 | 0.00 | 0.71 |
August | 0.776501E+09 | 0.302718E+09 | 0.00 | 25932222.33 | 11031100.27 | 0.00 | 0.794305E+10 | 0.00 | 0.69 |
September | 0.170625E+10 | 4414696.95 | 0.00 | 23315556.73 | 0.00 | 0.00 | 0.103888E+11 | 0.00 | 0.64 |
October | 0.461719E+10 | 0.00 | 0.00 | 11832904.97 | 0.00 | 0.00 | 0.786191E+10 | 0.00 | 0.42 |
November | 0.912719E+10 | 0.00 | 0.00 | 2394869.38 | 0.00 | 3318247.42 | 0.224609E+10 | 0.00 | 0.31 |
December | 0.117194E+11 | 0.00 | 0.00 | 86209.70 | 0.00 | 0.107433E+09 | 0.217869E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.660822E+11 | 0.423601E+09 | 0.00 | 0.162261E+09 | 26129135.71 | 0.709666E+09 | 0.769027E+11 | 0.00 | 0.48 |
Minimum of Months | 0.776501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.118454E+11 | 0.302718E+09 | 0.00 | 28364571.95 | 11031100.27 | 0.551163E+09 | 0.126630E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.946198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213255E+10 | 0.00 | 0.00 | 0.28 |
February | 0.938729E+10 | 0.00 | 0.00 | 170817.97 | 0.00 | 0.718125E+09 | 0.171337E+09 | 0.00 | 0.30 |
March | 0.959861E+10 | 0.00 | 0.00 | 1965713.84 | 0.00 | 58661171.38 | 0.216026E+10 | 0.00 | 0.33 |
April | 0.551719E+10 | 1233783.47 | 0.00 | 9102046.46 | 53527.91 | 0.00 | 0.591657E+10 | 0.00 | 0.40 |
May | 0.339243E+10 | 1165444.85 | 0.00 | 19223162.94 | 0.00 | 0.00 | 0.104451E+11 | 0.00 | 0.57 |
June | 0.194743E+10 | 1581466.12 | 0.00 | 24345502.68 | 757601.64 | 0.00 | 0.114548E+11 | 0.00 | 0.71 |
July | 0.157886E+10 | 84186888.01 | 0.00 | 22967666.33 | 10907986.38 | 0.00 | 0.826569E+10 | 0.00 | 0.71 |
August | 0.120151E+10 | 0.229993E+09 | 0.00 | 22240071.76 | 29048358.95 | 0.00 | 0.659234E+10 | 0.00 | 0.68 |
September | 0.294276E+10 | 938235.12 | 0.00 | 16712555.97 | 0.00 | 0.00 | 0.773550E+10 | 0.00 | 0.59 |
October | 0.648765E+10 | 0.00 | 0.00 | 5699625.95 | 0.00 | 2859729.68 | 0.432580E+10 | 0.00 | 0.38 |
November | 0.938042E+10 | 0.00 | 0.00 | 405400.90 | 0.00 | 0.293240E+09 | 0.631303E+09 | 0.00 | 0.30 |
December | 0.971836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135750E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.706145E+11 | 0.319099E+09 | 0.00 | 0.122833E+09 | 40767474.89 | 0.456294E+10 | 0.576987E+11 | 0.00 | 0.46 |
Minimum of Months | 0.120151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.971836E+10 | 0.229993E+09 | 0.00 | 24345502.68 | 29048358.95 | 0.213255E+10 | 0.114548E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.572097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197166E+10 | 0.00 | 0.00 | 0.29 |
February | 0.991482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122217E+10 | 0.00 | 0.00 | 0.30 |
March | 0.207650E+10 | 0.00 | 0.00 | 35038.08 | 0.00 | 0.321542E+09 | 83745373.34 | 0.00 | 0.33 |
April | 0.154558E+10 | 347044.33 | 0.00 | 1208079.58 | 11301.47 | 74384260.14 | 0.725907E+09 | 0.00 | 0.39 |
May | 0.101628E+10 | 533673.09 | 0.00 | 3989918.69 | 0.00 | 2601703.00 | 0.203116E+10 | 0.00 | 0.63 |
June | 0.576575E+09 | 480656.47 | 0.00 | 5684807.72 | 159954.10 | 0.00 | 0.249696E+10 | 0.00 | 0.83 |
July | 0.433301E+09 | 26012062.01 | 0.00 | 5668924.18 | 2303027.13 | 0.00 | 0.192649E+10 | 0.00 | 0.86 |
August | 0.393469E+09 | 69918857.62 | 0.00 | 4840169.99 | 5808646.88 | 0.00 | 0.133363E+10 | 0.00 | 0.76 |
September | 0.993603E+09 | 259766.41 | 0.00 | 2799277.74 | 0.00 | 618889.31 | 0.117415E+10 | 0.00 | 0.59 |
October | 0.173530E+10 | 0.00 | 0.00 | 406088.22 | 0.00 | 0.113039E+09 | 0.322133E+09 | 0.00 | 0.36 |
November | 0.127546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921966E+09 | 0.00 | 0.00 | 0.30 |
December | 0.662598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173926E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.122722E+11 | 97552059.93 | 0.00 | 24632304.22 | 8282929.58 | 0.636725E+10 | 0.100942E+11 | 0.00 | 0.49 |
Minimum of Months | 0.393469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.207650E+10 | 69918857.62 | 0.00 | 5684807.72 | 5808646.88 | 0.197166E+10 | 0.249696E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114808E+10 | 0.00 | 0.00 | 0.30 |
February | 0.724245E+09 | 0.00 | 0.00 | 15186.37 | 0.00 | 0.659378E+09 | 21745941.62 | 0.00 | 0.30 |
March | 0.110049E+10 | 0.00 | 0.00 | 725640.87 | 0.00 | 0.148710E+09 | 0.450916E+09 | 0.00 | 0.35 |
April | 0.690722E+09 | 309992.13 | 0.00 | 3078339.99 | 0.00 | 26122588.36 | 0.155634E+10 | 0.00 | 0.62 |
May | 0.489559E+09 | 483869.61 | 0.00 | 5152592.39 | 0.00 | 1653620.65 | 0.244935E+10 | 0.00 | 0.95 |
June | 0.248378E+09 | 336585.20 | 0.00 | 7363862.76 | 100851.30 | 0.00 | 0.316961E+10 | 0.00 | 1.38 |
July | 0.196319E+09 | 22819485.57 | 0.00 | 7506196.09 | 429261.64 | 0.00 | 0.222734E+10 | 0.00 | 1.37 |
August | 0.157344E+09 | 64142226.07 | 0.00 | 6928176.13 | 815613.47 | 0.00 | 0.170904E+10 | 0.00 | 1.33 |
September | 0.483869E+09 | 299320.42 | 0.00 | 4409123.91 | 0.00 | 390210.64 | 0.171654E+10 | 0.00 | 0.97 |
October | 0.877469E+09 | 0.00 | 0.00 | 1283890.94 | 0.00 | 62352347.90 | 0.762881E+09 | 0.00 | 0.45 |
November | 0.859968E+09 | 0.00 | 0.00 | 8343.31 | 0.00 | 0.516649E+09 | 14763367.83 | 0.00 | 0.30 |
December | 0.541254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100203E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.685680E+10 | 88391479.00 | 0.00 | 36471352.76 | 1345726.40 | 0.356537E+10 | 0.140785E+11 | 0.00 | 0.72 |
Minimum of Months | 0.157344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.110049E+10 | 64142226.07 | 0.00 | 7506196.09 | 815613.47 | 0.114808E+10 | 0.316961E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101433E+10 | 0.00 | 0.00 | 346410.04 | 0.00 | 0.140060E+10 | 0.226324E+09 | 0.00 | 0.30 |
February | 0.108056E+10 | 0.00 | 0.00 | 2058801.58 | 0.00 | 0.734149E+09 | 0.105326E+10 | 0.00 | 0.40 |
March | 0.146967E+10 | 0.00 | 0.00 | 4750972.70 | 0.00 | 0.228728E+09 | 0.244313E+10 | 0.00 | 0.56 |
April | 0.101335E+10 | 958672.63 | 0.00 | 6341940.36 | 0.00 | 65630266.60 | 0.318012E+10 | 0.00 | 0.76 |
May | 0.829714E+09 | 1011000.12 | 0.00 | 8414979.40 | 0.00 | 2805611.65 | 0.392554E+10 | 0.00 | 1.00 |
June | 0.536563E+09 | 615939.09 | 0.00 | 8790066.65 | 159250.61 | 0.00 | 0.368197E+10 | 0.00 | 1.15 |
July | 0.405577E+09 | 48224861.93 | 0.00 | 9327204.47 | 301815.03 | 0.00 | 0.286936E+10 | 0.00 | 1.26 |
August | 0.335964E+09 | 0.145674E+09 | 0.00 | 8807692.86 | 757827.48 | 0.00 | 0.215232E+10 | 0.00 | 1.21 |
September | 0.708014E+09 | 1427427.94 | 0.00 | 10191041.02 | 0.00 | 616167.40 | 0.359113E+10 | 0.00 | 1.33 |
October | 0.117686E+10 | 0.00 | 0.00 | 5489445.65 | 0.00 | 81484785.13 | 0.307526E+10 | 0.00 | 0.76 |
November | 0.131782E+10 | 0.00 | 0.00 | 1135807.55 | 0.00 | 0.663994E+09 | 0.470656E+09 | 0.00 | 0.36 |
December | 0.941477E+09 | 0.00 | 0.00 | 1025734.67 | 0.00 | 0.122905E+10 | 0.532184E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.108299E+11 | 0.197912E+09 | 0.00 | 66680096.95 | 1218893.12 | 0.440706E+10 | 0.272012E+11 | 0.00 | 0.79 |
Minimum of Months | 0.335964E+09 | 0.00 | 0.00 | 346410.04 | 0.00 | 0.00 | 0.226324E+09 | 0.00 | 0.30 |
Maximum of Months | 0.146967E+10 | 0.145674E+09 | 0.00 | 10191041.02 | 757827.48 | 0.140060E+10 | 0.392554E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.456261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120001E+10 | 0.00 | 0.00 | 0.30 |
February | 0.639887E+09 | 0.00 | 0.00 | 161163.75 | 0.00 | 0.697891E+09 | 0.121610E+09 | 0.00 | 0.32 |
March | 0.109936E+10 | 0.00 | 0.00 | 951490.62 | 0.00 | 0.203310E+09 | 0.578075E+09 | 0.00 | 0.40 |
April | 0.809035E+09 | 508233.25 | 0.00 | 2648196.99 | 0.00 | 52700824.42 | 0.133095E+10 | 0.00 | 0.63 |
May | 0.515132E+09 | 426331.67 | 0.00 | 6202897.67 | 0.00 | 3402759.13 | 0.242917E+10 | 0.00 | 1.05 |
June | 0.324973E+09 | 1207608.51 | 0.00 | 6345144.30 | 101453.62 | 0.00 | 0.236273E+10 | 0.00 | 1.26 |
July | 0.238686E+09 | 45438304.81 | 0.00 | 7880879.69 | 370356.68 | 0.00 | 0.201450E+10 | 0.00 | 1.48 |
August | 0.213343E+09 | 96774598.51 | 0.00 | 5800211.65 | 1667913.61 | 0.00 | 0.128338E+10 | 0.00 | 1.13 |
September | 0.492204E+09 | 502816.97 | 0.00 | 4746730.35 | 0.00 | 392541.12 | 0.160087E+10 | 0.00 | 1.03 |
October | 0.963872E+09 | 0.00 | 0.00 | 1185168.23 | 0.00 | 73229363.68 | 0.712640E+09 | 0.00 | 0.48 |
November | 0.801651E+09 | 0.00 | 0.00 | 73408.06 | 0.00 | 0.561947E+09 | 43130861.23 | 0.00 | 0.31 |
December | 0.492413E+09 | 0.00 | 0.00 | 5124.98 | 0.00 | 0.105371E+10 | 6319637.18 | 0.00 | 0.29 |
Annual Sum or Average | 0.704682E+10 | 0.144858E+09 | 0.00 | 36000416.31 | 2139723.91 | 0.384660E+10 | 0.124834E+11 | 0.00 | 0.73 |
Minimum of Months | 0.213343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.109936E+10 | 96774598.51 | 0.00 | 7880879.69 | 1667913.61 | 0.120001E+10 | 0.242917E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.886414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179750E+10 | 0.00 | 0.00 | 0.29 |
February | 0.137703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939593E+09 | 0.00 | 0.00 | 0.29 |
March | 0.233387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118710E+09 | 0.00 | 0.00 | 0.31 |
April | 0.171714E+10 | 950912.70 | 0.00 | 303784.99 | 712174.47 | 9787739.88 | 0.208146E+09 | 0.00 | 0.30 |
May | 0.116740E+10 | 986939.59 | 0.00 | 2456131.99 | 0.00 | 0.00 | 0.125821E+10 | 0.00 | 0.50 |
June | 0.600482E+09 | 1295717.98 | 0.00 | 4307169.86 | 283326.95 | 0.00 | 0.186526E+10 | 0.00 | 0.66 |
July | 0.376615E+09 | 25939558.43 | 0.00 | 4765241.97 | 2533929.88 | 0.00 | 0.157632E+10 | 0.00 | 0.70 |
August | 0.366626E+09 | 75125778.84 | 0.00 | 4116007.68 | 3056545.85 | 0.00 | 0.122559E+10 | 0.00 | 0.64 |
September | 0.962403E+09 | 906349.58 | 0.00 | 2551038.52 | 2568.38 | 0.00 | 0.111082E+10 | 0.00 | 0.54 |
October | 0.187097E+10 | 0.00 | 0.00 | 457333.04 | 0.00 | 372645.71 | 0.324800E+09 | 0.00 | 0.35 |
November | 0.196332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329541E+09 | 0.00 | 0.00 | 0.29 |
December | 0.129541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125044E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.149177E+11 | 0.105205E+09 | 0.00 | 18956708.06 | 6588545.53 | 0.444594E+10 | 0.756914E+10 | 0.00 | 0.43 |
Minimum of Months | 0.366626E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.233387E+10 | 75125778.84 | 0.00 | 4765241.97 | 3056545.85 | 0.179750E+10 | 0.186526E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.673129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105790E+10 | 0.00 | 0.00 | 0.29 |
February | 0.104426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428218E+09 | 0.00 | 0.00 | 0.30 |
March | 0.131536E+10 | 0.00 | 0.00 | 396222.02 | 0.00 | 27108004.60 | 0.264247E+09 | 0.00 | 0.32 |
April | 0.737458E+09 | 1222708.59 | 0.00 | 2380582.62 | 450438.82 | 2368705.40 | 0.893010E+09 | 0.00 | 0.42 |
May | 0.499246E+09 | 1134190.08 | 0.00 | 4089640.96 | 0.00 | 0.00 | 0.185157E+10 | 0.00 | 0.79 |
June | 0.233225E+09 | 1146684.25 | 0.00 | 6409939.11 | 179199.71 | 0.00 | 0.265145E+10 | 0.00 | 1.21 |
July | 0.150158E+09 | 28980678.05 | 0.00 | 6413103.35 | 1373044.65 | 0.00 | 0.192749E+10 | 0.00 | 1.18 |
August | 0.127505E+09 | 82152674.21 | 0.00 | 6268719.05 | 738751.76 | 0.00 | 0.166649E+10 | 0.00 | 1.19 |
September | 0.407879E+09 | 1143877.86 | 0.00 | 4433962.40 | 0.00 | 0.00 | 0.171663E+10 | 0.00 | 0.93 |
October | 0.908026E+09 | 0.00 | 0.00 | 1563421.14 | 0.00 | 94994.91 | 0.849410E+09 | 0.00 | 0.45 |
November | 0.124491E+10 | 0.00 | 0.00 | 19836.24 | 0.00 | 0.183213E+09 | 26146067.78 | 0.00 | 0.29 |
December | 0.919455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708398E+09 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.826062E+10 | 0.115781E+09 | 0.00 | 31975426.88 | 2741434.94 | 0.240730E+10 | 0.118464E+11 | 0.00 | 0.64 |
Minimum of Months | 0.127505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.131536E+10 | 82152674.21 | 0.00 | 6413103.35 | 1373044.65 | 0.105790E+10 | 0.265145E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.630955E+09 | 0.00 | 0.00 | 17299.49 | 0.00 | 0.343502E+10 | 22106446.33 | 0.00 | 0.43 |
February | 0.110078E+10 | 0.00 | 0.00 | 321158.27 | 0.00 | 0.201400E+10 | 0.203492E+09 | 0.00 | 0.42 |
March | 0.164776E+10 | 0.00 | 0.00 | 1142094.04 | 0.00 | 0.116354E+10 | 0.696156E+09 | 0.00 | 0.45 |
April | 0.129585E+10 | 5412118.78 | 0.00 | 1906482.69 | 0.00 | 0.605487E+09 | 0.750216E+09 | 0.00 | 0.44 |
May | 0.130774E+10 | 2205590.05 | 0.00 | 3176330.28 | 0.00 | 0.381982E+09 | 0.134719E+10 | 0.00 | 0.67 |
June | 0.936213E+09 | 1998517.22 | 0.00 | 4219607.89 | 284323.82 | 0.184233E+09 | 0.156868E+10 | 0.00 | 0.78 |
July | 0.499577E+09 | 55894206.21 | 0.00 | 5849230.76 | 2051138.18 | 38892720.79 | 0.167323E+10 | 0.00 | 0.91 |
August | 0.473317E+09 | 0.182191E+09 | 0.00 | 6009796.79 | 1154386.50 | 39514805.23 | 0.139816E+10 | 0.00 | 0.95 |
September | 0.823792E+09 | 4723649.99 | 0.00 | 7346723.83 | 0.00 | 0.156719E+09 | 0.228395E+10 | 0.00 | 1.07 |
October | 0.128582E+10 | 0.00 | 0.00 | 3357319.79 | 0.00 | 0.532493E+09 | 0.182653E+10 | 0.00 | 0.63 |
November | 0.140111E+10 | 0.00 | 0.00 | 377508.16 | 0.00 | 0.170867E+10 | 0.118133E+09 | 0.00 | 0.42 |
December | 0.854524E+09 | 0.00 | 0.00 | 250343.68 | 0.00 | 0.283661E+10 | 0.170203E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.122574E+11 | 0.252425E+09 | 0.00 | 33973895.66 | 3489848.51 | 0.130972E+11 | 0.120581E+11 | 0.00 | 0.63 |
Minimum of Months | 0.473317E+09 | 0.00 | 0.00 | 17299.49 | 0.00 | 38892720.79 | 22106446.33 | 0.00 | 0.41 |
Maximum of Months | 0.164776E+10 | 0.182191E+09 | 0.00 | 7346723.83 | 2051138.18 | 0.343502E+10 | 0.228395E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.628537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110781E+10 | 0.00 | 0.00 | 0.29 |
February | 0.980986E+09 | 0.00 | 0.00 | 74348.67 | 0.00 | 0.443373E+09 | 61108965.73 | 0.00 | 0.30 |
March | 0.131503E+10 | 0.00 | 0.00 | 469726.13 | 0.00 | 60456816.39 | 0.290031E+09 | 0.00 | 0.34 |
April | 0.813495E+09 | 2030403.61 | 0.00 | 1698369.03 | 156886.47 | 6065162.41 | 0.713405E+09 | 0.00 | 0.41 |
May | 0.462767E+09 | 971562.51 | 0.00 | 4772807.12 | 0.00 | 0.00 | 0.184329E+10 | 0.00 | 0.84 |
June | 0.258245E+09 | 3345901.09 | 0.00 | 5385032.11 | 179282.05 | 0.00 | 0.198052E+10 | 0.00 | 1.06 |
July | 0.147772E+09 | 46451065.36 | 0.00 | 6274587.32 | 422469.11 | 0.00 | 0.183463E+10 | 0.00 | 1.28 |
August | 0.150837E+09 | 0.104442E+09 | 0.00 | 5407161.10 | 1437936.69 | 0.00 | 0.131520E+10 | 0.00 | 1.03 |
September | 0.357076E+09 | 1653583.98 | 0.00 | 4601294.58 | 0.00 | 0.00 | 0.161314E+10 | 0.00 | 0.95 |
October | 0.959650E+09 | 0.00 | 0.00 | 1314785.87 | 0.00 | 0.00 | 0.734937E+09 | 0.00 | 0.46 |
November | 0.122893E+10 | 0.00 | 0.00 | 62239.13 | 0.00 | 0.186890E+09 | 42563210.73 | 0.00 | 0.30 |
December | 0.909401E+09 | 0.00 | 0.00 | 2523.88 | 0.00 | 0.717697E+09 | 4291878.73 | 0.00 | 0.28 |
Annual Sum or Average | 0.821272E+10 | 0.158894E+09 | 0.00 | 30062874.94 | 2196574.32 | 0.252229E+10 | 0.104331E+11 | 0.00 | 0.63 |
Minimum of Months | 0.147772E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.131503E+10 | 0.104442E+09 | 0.00 | 6274587.32 | 1437936.69 | 0.110781E+10 | 0.198052E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156607E+10 | 0.00 | 0.00 | 0.29 |
February | 0.165905E+10 | 0.00 | 0.00 | 6148.42 | 0.00 | 0.642182E+09 | 23495908.59 | 0.00 | 0.30 |
March | 0.238999E+10 | 0.00 | 0.00 | 89527.51 | 0.00 | 70825638.80 | 0.140548E+09 | 0.00 | 0.33 |
April | 0.149883E+10 | 1418525.92 | 0.00 | 1568852.58 | 963490.04 | 5025079.47 | 0.907555E+09 | 0.00 | 0.39 |
May | 0.856517E+09 | 1851339.61 | 0.00 | 4612046.35 | 0.00 | 0.00 | 0.225053E+10 | 0.00 | 0.64 |
June | 0.433073E+09 | 1520992.89 | 0.00 | 6337937.00 | 259993.57 | 0.00 | 0.267639E+10 | 0.00 | 0.84 |
July | 0.308925E+09 | 32547021.00 | 0.00 | 6152142.61 | 1956963.53 | 0.00 | 0.204321E+10 | 0.00 | 0.85 |
August | 0.297095E+09 | 92643643.19 | 0.00 | 5283716.19 | 2323734.86 | 0.00 | 0.155339E+10 | 0.00 | 0.76 |
September | 0.840954E+09 | 1171458.18 | 0.00 | 3515103.22 | 0.00 | 0.00 | 0.147426E+10 | 0.00 | 0.62 |
October | 0.182132E+10 | 0.00 | 0.00 | 762021.53 | 0.00 | 5426718.97 | 0.518753E+09 | 0.00 | 0.37 |
November | 0.193767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429886E+09 | 0.00 | 0.00 | 0.30 |
December | 0.135848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119823E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.144719E+11 | 0.131153E+09 | 0.00 | 28327495.40 | 5504181.99 | 0.391765E+10 | 0.115881E+11 | 0.00 | 0.50 |
Minimum of Months | 0.297095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.238999E+10 | 92643643.19 | 0.00 | 6337937.00 | 2323734.86 | 0.156607E+10 | 0.267639E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.578338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837231E+09 | 0.00 | 0.00 | 0.24 |
February | 0.839217E+09 | 0.00 | 0.00 | 64786.47 | 0.00 | 0.335496E+09 | 53629946.55 | 0.00 | 0.25 |
March | 0.103064E+10 | 0.00 | 0.00 | 1043046.85 | 0.00 | 27197672.28 | 0.585475E+09 | 0.00 | 0.32 |
April | 0.573381E+09 | 1735686.56 | 0.00 | 3350867.49 | 2209.09 | 2731839.89 | 0.163996E+10 | 0.00 | 0.59 |
May | 0.420249E+09 | 1570783.84 | 0.00 | 5215346.33 | 0.00 | 0.00 | 0.234846E+10 | 0.00 | 0.91 |
June | 0.209287E+09 | 1055583.03 | 0.00 | 7375783.27 | 164619.24 | 0.00 | 0.300961E+10 | 0.00 | 1.30 |
July | 0.150425E+09 | 27217201.16 | 0.00 | 7304590.86 | 1037489.27 | 0.00 | 0.212887E+10 | 0.00 | 1.28 |
August | 0.128602E+09 | 78712627.60 | 0.00 | 6785373.51 | 711321.87 | 0.00 | 0.176775E+10 | 0.00 | 1.25 |
September | 0.384576E+09 | 1030891.18 | 0.00 | 4683748.31 | 395.14 | 0.00 | 0.179691E+10 | 0.00 | 0.94 |
October | 0.790971E+09 | 0.00 | 0.00 | 1630612.95 | 0.00 | 3730582.49 | 0.918921E+09 | 0.00 | 0.44 |
November | 0.956152E+09 | 0.00 | 0.00 | 59836.94 | 0.00 | 0.251696E+09 | 43726803.09 | 0.00 | 0.25 |
December | 0.708963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662476E+09 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.677080E+10 | 0.111323E+09 | 0.00 | 37513992.98 | 1916034.60 | 0.212056E+10 | 0.142933E+11 | 0.00 | 0.67 |
Minimum of Months | 0.128602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.103064E+10 | 78712627.60 | 0.00 | 7375783.27 | 1037489.27 | 0.837231E+09 | 0.300961E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142308E+10 | 0.00 | 0.00 | 593359.93 | 0.00 | 0.102209E+10 | 0.364355E+09 | 0.00 | 0.31 |
February | 0.149664E+10 | 0.00 | 0.00 | 2567209.88 | 0.00 | 0.404285E+09 | 0.124976E+10 | 0.00 | 0.42 |
March | 0.167913E+10 | 0.00 | 0.00 | 5611395.72 | 0.00 | 41643961.64 | 0.276256E+10 | 0.00 | 0.60 |
April | 0.100302E+10 | 8121619.51 | 0.00 | 6800127.50 | 0.00 | 4493940.47 | 0.329795E+10 | 0.00 | 0.77 |
May | 0.731107E+09 | 3467695.45 | 0.00 | 8918293.60 | 0.00 | 0.00 | 0.392700E+10 | 0.00 | 1.02 |
June | 0.448113E+09 | 1908634.65 | 0.00 | 9198124.67 | 259946.29 | 0.00 | 0.364066E+10 | 0.00 | 1.15 |
July | 0.329035E+09 | 56154010.98 | 0.00 | 9116977.07 | 1598077.16 | 0.00 | 0.276432E+10 | 0.00 | 1.22 |
August | 0.273593E+09 | 0.182973E+09 | 0.00 | 8735987.00 | 769366.53 | 0.00 | 0.223992E+10 | 0.00 | 1.16 |
September | 0.590345E+09 | 5976971.80 | 0.00 | 10763470.88 | 0.00 | 0.00 | 0.370128E+10 | 0.00 | 1.35 |
October | 0.120691E+10 | 0.00 | 0.00 | 6557448.66 | 0.00 | 2327110.76 | 0.346598E+10 | 0.00 | 0.82 |
November | 0.178291E+10 | 0.00 | 0.00 | 1600553.19 | 0.00 | 0.260217E+09 | 0.702068E+09 | 0.00 | 0.38 |
December | 0.148295E+10 | 0.00 | 0.00 | 1437564.61 | 0.00 | 0.792733E+09 | 0.737006E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.124468E+11 | 0.258602E+09 | 0.00 | 71900512.68 | 2627389.98 | 0.252779E+10 | 0.288529E+11 | 0.00 | 0.80 |
Minimum of Months | 0.273593E+09 | 0.00 | 0.00 | 593359.93 | 0.00 | 0.00 | 0.364355E+09 | 0.00 | 0.31 |
Maximum of Months | 0.178291E+10 | 0.182973E+09 | 0.00 | 10763470.88 | 1598077.16 | 0.102209E+10 | 0.392700E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.762895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.941813E+09 | 0.00 | 0.00 | 0.30 |
February | 0.102421E+10 | 0.00 | 0.00 | 220886.08 | 0.00 | 0.364884E+09 | 0.155363E+09 | 0.00 | 0.32 |
March | 0.129856E+10 | 0.00 | 0.00 | 1127777.77 | 0.00 | 48098357.40 | 0.650052E+09 | 0.00 | 0.42 |
April | 0.777521E+09 | 3707487.09 | 0.00 | 2867104.28 | 100924.30 | 4843889.15 | 0.141408E+10 | 0.00 | 0.62 |
May | 0.437410E+09 | 1586103.85 | 0.00 | 6572588.31 | 0.00 | 0.00 | 0.243770E+10 | 0.00 | 1.06 |
June | 0.255013E+09 | 3904834.07 | 0.00 | 6652162.29 | 165212.99 | 0.00 | 0.236109E+10 | 0.00 | 1.24 |
July | 0.179304E+09 | 54173191.06 | 0.00 | 6933817.77 | 310211.84 | 0.00 | 0.194569E+10 | 0.00 | 1.41 |
August | 0.168390E+09 | 0.123935E+09 | 0.00 | 5842192.31 | 1220686.19 | 0.00 | 0.136229E+10 | 0.00 | 1.11 |
September | 0.403416E+09 | 2159565.56 | 0.00 | 5099906.05 | 0.00 | 0.00 | 0.172781E+10 | 0.00 | 1.06 |
October | 0.998380E+09 | 0.00 | 0.00 | 1521863.00 | 0.00 | 3207497.67 | 0.878939E+09 | 0.00 | 0.51 |
November | 0.118861E+10 | 0.00 | 0.00 | 114865.31 | 0.00 | 0.270375E+09 | 65604560.94 | 0.00 | 0.32 |
December | 0.916022E+09 | 0.00 | 0.00 | 19718.98 | 0.00 | 0.708850E+09 | 22665352.52 | 0.00 | 0.29 |
Annual Sum or Average | 0.840974E+10 | 0.189466E+09 | 0.00 | 36972882.17 | 1797035.30 | 0.234207E+10 | 0.130213E+11 | 0.00 | 0.72 |
Minimum of Months | 0.168390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.129856E+10 | 0.123935E+09 | 0.00 | 6933817.77 | 1220686.19 | 0.941813E+09 | 0.243770E+10 | 0.00 | 1.41 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.644905E+11 | 0.929941E+10 | 0.00 | 0.141711E+12 | 0.215610E+11 |
February | 0.126341E+12 | 0.839670E+10 | 0.00 | 0.153724E+12 | 0.139236E+11 |
March | 0.220771E+12 | 0.851911E+10 | 0.00 | 0.196182E+12 | 0.727406E+10 |
April | 0.339673E+12 | 0.744259E+10 | 0.00 | 0.217698E+12 | 0.188051E+11 |
May | 0.442037E+12 | 0.611550E+10 | 0.00 | 0.235865E+12 | 0.284517E+11 |
June | 0.443640E+12 | 0.481181E+10 | 0.00 | 0.219863E+12 | 0.507952E+11 |
July | 0.469731E+12 | 0.345747E+10 | 0.00 | 0.216517E+12 | 0.964303E+11 |
August | 0.369953E+12 | 0.264751E+10 | 0.00 | 0.169482E+12 | 0.128331E+12 |
September | 0.264927E+12 | 0.346261E+10 | 0.00 | 0.225939E+12 | 0.471982E+11 |
October | 0.170540E+12 | 0.676682E+10 | 0.00 | 0.223453E+12 | 0.879164E+10 |
November | 0.728724E+11 | 0.800378E+10 | 0.00 | 0.182054E+12 | 0.115335E+11 |
December | 0.504951E+11 | 0.850785E+10 | 0.00 | 0.158062E+12 | 0.183480E+11 |
Annual Sum or Average | 0.303547E+13 | 0.774311E+11 | 0.00 | 0.234055E+13 | 0.451443E+12 |
Minimum of Months | 0.504951E+11 | 0.264751E+10 | 0.00 | 0.141711E+12 | 0.727406E+10 |