Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:20:08
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2289.05 | 459.45 | 459.45 |
Net Site Energy | 2289.05 | 459.45 | 459.45 |
Total Source Energy | 5141.07 | 1031.89 | 1031.89 |
Net Source Energy | 5141.07 | 1031.89 | 1031.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 48.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 68.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1276.88 | 1012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 48.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 88.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 68.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1012.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 48.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 56.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 88.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 5.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 68.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 42.42 | 203.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.29 | 203.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 59.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 42.42 | 203.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 154.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 256.29 | 203.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1276.878 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1276.878 | 100.00 |
Total On-Site and Utility Electric Sources | 1276.878 | 100.00 |
Total Electricity End Uses | 1276.878 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.19 | 0.04 |
Air to Air Heat Recovery for Heating | 481.72 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 481.91 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1240.33 |
Time Setpoint Not Met During Occupied Cooling | 71.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3379.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-JUL-15:39 | 27-FEB-07:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 373684.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40888.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26908.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5769.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 138533.96 | 373684.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 373684.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 40888.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26908.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 5769.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1097.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 153.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 764.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 177.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 215.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4043.87 | 1097.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 811.67 | 220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 30.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 153.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 35.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 13.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 811.67 | 220.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.63 | 0.284641 | 0.242000 | 0.637182 | 0.759043 | 0.500000 | 0.001339 | 0.000142 | 0.637182 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.14 | 0.350507 | 0.298000 | 0.637185 | 0.934684 | 0.500000 | 0.001087 | 0.000237 | 0.817835 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.08 | 0.360672 | 0.307000 | 0.637927 | 0.961793 | 0.500000 | 0.001056 | 0.000436 | 1.51 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.663888 | 0.237979 | 0.219000 | 0.145392 | 0.634611 | 0.500000 | 0.001601 | 0.000192 | 0.663888 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.834623 | 0.119841 | 0.102000 | 0.085132 | 0.319575 | 0.500000 | 0.003179 | 0.000125 | 0.433667 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.31 | 0.120476 | 0.102000 | 0.133762 | 0.321270 | 0.500000 | 0.003162 | 0.000191 | 0.660905 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.866570 | 0.115415 | 0.098000 | 0.084924 | 0.307774 | 0.500000 | 0.003301 | 0.000125 | 0.432004 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.529905 | 0.298151 | 0.257000 | 0.136186 | 0.795069 | 0.500000 | 0.001278 | 0.000153 | 0.529905 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.682186 | 0.146620 | 0.125000 | 0.085273 | 0.390985 | 0.500000 | 0.002599 | 0.000101 | 0.349092 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.06 | 0.148590 | 0.126000 | 0.133972 | 0.396241 | 0.500000 | 0.002564 | 0.000152 | 0.527853 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.715044 | 0.139873 | 0.119000 | 0.085090 | 0.372994 | 0.500000 | 0.002724 | 0.000100 | 0.347748 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.589223 | 0.268135 | 0.228000 | 0.134343 | 0.715028 | 0.500000 | 0.001421 | 0.000145 | 0.503129 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.830902 | 0.321006 | 0.500000 | 0.003165 | 0.000096 | 0.330966 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.24 | 0.127037 | 0.108000 | 0.134316 | 0.338764 | 0.500000 | 0.002999 | 0.000144 | 0.500389 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.821456 | 0.121754 | 0.103000 | 0.084610 | 0.324676 | 0.500000 | 0.003129 | 0.000095 | 0.329574 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16225.47 | 0.000142 | 387.97 |
CORE_MID VAV BOX REHEAT COIL | 27089.41 | 0.000237 | 715.60 |
CORE_TOP VAV BOX REHEAT COIL | 49881.18 | 0.000436 | 1316.14 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21900.58 | 0.000192 | 577.45 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14305.37 | 0.000125 | 377.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21802.31 | 0.000191 | 574.86 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14250.57 | 0.000125 | 375.73 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17485.92 | 0.000153 | 461.11 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11518.65 | 0.000101 | 303.74 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17418.33 | 0.000152 | 459.33 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11474.37 | 0.000100 | 302.57 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16604.53 | 0.000145 | 437.89 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10921.95 | 0.000096 | 288.02 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16514.26 | 0.000144 | 435.51 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10876.10 | 0.000095 | 286.81 |
PACU_VAV_BOT HEATING COIL | 59078.83 | 0.000517 | 866.04 |
PACU_VAV_MID HEATING COIL | 59984.14 | 0.000525 | 861.76 |
PACU_VAV_TOP HEATING COIL | 59023.41 | 0.000516 | 873.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.81 | 1.08 | 5.62 | 2.18 | 4.80 | 4.80 | 0.300000 | 0.453875 | 4.80 |
PACU_VAV_MID | 2.81 | 1.08 | 5.62 | 2.48 | 4.53 | 4.53 | 0.300000 | 0.547981 | 4.53 |
PACU_VAV_TOP | 2.88 | 1.09 | 5.75 | 3.70 | 4.96 | 4.96 | 0.300000 | 0.745860 | 4.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.80 |
PACU_VAV_MID_OA_CONTROLLER | 4.53 |
PACU_VAV_TOP_OA_CONTROLLER | 4.96 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 0.956100 |
PACU_VAV_MID OA HEAT RECOVERY | 0.956100 |
PACU_VAV_TOP OA HEAT RECOVERY | 0.956100 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.80 | 79482.22 | 0.800655 | 1.60 | 26491.42 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.53 | 74973.65 | 0.800655 | 1.51 | 24988.72 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 4.96 | 82121.95 | 0.800655 | 1.65 | 27371.24 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.80 |
PACU_VAV_MID FAN | 4.53 |
PACU_VAV_TOP FAN | 4.96 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000517 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000525 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000516 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003992 | 0.479087 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003992 | 1190.43 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 456355.37 | 456355.37 | 0.003992 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6761 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.6631 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.8981 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.245 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.274 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8794 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.32863397E-12 | 0.12532498E-14 | -0.10432781E-12 | 0.10000009E-15 |
43 | 6 | 0.29860290E-07 | 0.19244976E-09 | 0.68304209E-08 | -0.14159436E-12 |
44 | 5 | -0.19612469E-03 | 0.16345755E-05 | -0.10079517E-03 | 0.67484823E-08 |
45 | 4 | 0.29915968 | 0.79015507E-03 | 0.10220689 | -0.34563380E-04 |
46 | 3 | -7.4051490 | 0.24331082E-01 | -2.3801101 | 0.29689509E-01 |
47 | 2 | 41.328906 | 0.86029560E-01 | 15.433920 | -0.33843907 |
48 | 1 | -80.896497 | 0.38634018E-01 | -29.293000 | 1.0860931 |
49 | 0 | 46.824336 | 0.77350051E-03 | 16.287644 | |
50 | 7 | -0.32990843E-12 | 0.11750686E-14 | -0.10494268E-12 | 0.10070323E-15 |
51 | 6 | 0.30013254E-07 | 0.18902410E-09 | 0.68641830E-08 | -0.14241961E-12 |
52 | 5 | -0.19689619E-03 | 0.16039916E-05 | -0.10118091E-03 | 0.67813509E-08 |
53 | 4 | 0.30005484 | 0.77472963E-03 | 0.10252920 | -0.34690470E-04 |
54 | 3 | -7.4228592 | 0.23838592E-01 | -2.3853666 | 0.29776351E-01 |
55 | 2 | 41.387294 | 0.84233400E-01 | 15.455437 | -0.33908948 |
56 | 1 | -80.941219 | 0.37805857E-01 | -29.312279 | 1.0870462 |
57 | 0 | 46.824336 | 0.75649625E-03 | 16.287191 | |
58 | 7 | -0.28528047E-12 | 0.14314274E-14 | -0.82259378E-13 | 0.81732043E-16 |
59 | 6 | 0.27222731E-07 | 0.24871836E-09 | 0.62482715E-08 | -0.12743522E-12 |
60 | 5 | -0.18272614E-03 | 0.21485338E-05 | -0.94080885E-04 | 0.61809713E-08 |
61 | 4 | 0.28347135 | 0.10543336E-02 | 0.96565215E-01 | -0.32350904E-04 |
62 | 3 | -7.0944292 | 0.32900988E-01 | -2.2879113 | 0.28166852E-01 |
63 | 2 | 40.304118 | 0.11770635 | 15.055686 | -0.32702567 |
64 | 1 | -80.111171 | 0.53403795E-01 | -28.953874 | 1.0693576 |
65 | 0 | 46.824341 | 0.10800274E-02 | 16.295775 | |
66 | 7 | -0.22718025E-08 | -0.85076432E-15 | 0.54602610E-14 | -0.81699313E-16 |
67 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
68 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
69 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
70 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
71 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
72 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
73 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
74 | 7 | -0.21518248E-08 | -0.72352508E-15 | 0.47198691E-14 | -0.69590188E-16 |
75 | 6 | 0.55239907E-05 | 0.37570600E-08 | 0.31901221E-02 | -0.26761418E-04 |
76 | 5 | -0.39518120E-03 | 0.22239456E-05 | -0.22373891 | 0.19562768E-02 |
77 | 4 | 0.90771213E-02 | 0.10121852E-03 | 4.8297846 | -0.45267278E-01 |
78 | 3 | -0.79671013E-01 | 0.80474906E-03 | -38.022767 | 0.39866868 |
79 | 2 | 0.28284274 | 0.13386367E-02 | 116.48658 | -1.4179745 |
80 | 1 | -0.40820825 | 0.40769430E-03 | -143.90886 | 2.0490654 |
81 | 0 | 0.19901349 | 0.99021926E-05 | 60.838472 | |
82 | 7 | -0.22718025E-08 | -0.85076409E-15 | 0.54602611E-14 | -0.81699316E-16 |
83 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
84 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
85 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
86 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
87 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
88 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
89 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
90 | 7 | -0.21516764E-08 | -0.72282083E-15 | 0.50090186E-14 | -0.71315031E-16 |
91 | 6 | 0.55243484E-05 | 0.37573175E-08 | 0.31901211E-02 | -0.26761409E-04 |
92 | 5 | -0.39520780E-03 | 0.22240973E-05 | -0.22373885 | 0.19562763E-02 |
93 | 4 | 0.90777390E-02 | 0.10122544E-03 | 4.8297836 | -0.45267268E-01 |
94 | 3 | -0.79676455E-01 | 0.80480411E-03 | -38.022761 | 0.39866862 |
95 | 2 | 0.28286209 | 0.13387285E-02 | 116.48657 | -1.4179743 |
96 | 1 | -0.40823619 | 0.40772215E-03 | -143.90885 | 2.0490653 |
97 | 0 | 0.19902711 | 0.99029315E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 35 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 36 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
3 | WINDOW_U_0.262_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 | ||
4 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 38 | 1 | VerySmooth | 1.488 | 1.488 | 1.000 | 0.400 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.47720E-002 | 0.31332 | 0.49252 | 0.49252 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.00957E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4670E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4746E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7334E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7402E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3365E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3814E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5636E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5883E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1611 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1088 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1884 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1319 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5051E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2487E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0604E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8980E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4676E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4790E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7342E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7455E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3400E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3980E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5633E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5880E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1057 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5105E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1101 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7858E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2097E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1934E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9382E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7963E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.1439E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1778E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.4403E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.4664E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8209E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8298E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3268E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3352E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9917E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0654E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0720E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1371E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0531E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0959E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5633E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5880E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 6.2847E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5557E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0236E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8218E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1357E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7054E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0604E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8980E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.9909E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0691E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0695E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.1335E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0499E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0831E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5636E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.5883E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.6340E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6960E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.8841E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2247E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6703E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4090E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9383E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7963E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0787E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1765E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5284E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6452E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8541E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8803E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3270E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3354E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1756 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1303 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2049 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1568 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1048 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4448E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.7665E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.6893E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1016 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.2782E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1059 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.5428E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0043E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0716E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.8278E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7301E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.0388E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.5246E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6949E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.6608E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7749E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4190E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7665E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6893E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3585E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5436E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6445E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0946E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.5160E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3198E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8279E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7302E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1756 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1303 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2050 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1568 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1047 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4443E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.7660E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.6889E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1016 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.2778E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1059 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.5423E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0039E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0711E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.8273E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7298E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.0390E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.5244E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6950E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.6606E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7746E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4188E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7660E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6889E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3587E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5434E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6446E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0944E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.5156E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3195E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8273E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7299E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 35983.85986 | 35983.85986 | 2.63298 | 2.63298 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9909.58368 | 9909.58368 | 0.43180 | 0.43180 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29248.59347 | 29248.59347 | 2.13820 | 2.13820 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18982.85397 | 18982.85397 | 0.81784 | 0.81784 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28426.50396 | 28426.50396 | 2.07794 | 2.07794 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 34916.36302 | 34916.36302 | 1.50974 | 1.50974 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8306.63278 | 8306.63278 | 0.61305 | 0.61305 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15320.24153 | 15320.24153 | 0.66389 | 0.66389 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11309.03202 | 11309.03202 | 0.83462 | 0.83462 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10006.94318 | 10006.94318 | 0.43367 | 0.43367 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 17769.17169 | 17769.17169 | 1.31139 | 1.31139 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15251.54277 | 15251.54277 | 0.66091 | 0.66091 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11741.90920 | 11741.90920 | 0.86657 | 0.86657 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9968.63099 | 9968.63099 | 0.43200 | 0.43200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7077.05529 | 7077.05529 | 0.52231 | 0.52231 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 21.07600 | 6.99765E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12233.53221 | 12233.53221 | 0.52990 | 0.52990 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9243.47288 | 9243.47288 | 0.68219 | 0.68219 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8058.47100 | 8058.47100 | 0.34909 | 0.34909 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 14407.06155 | 14407.06155 | 1.06327 | 1.06327 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12186.27991 | 12186.27991 | 0.52785 | 0.52785 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9688.69501 | 9688.69501 | 0.71504 | 0.71504 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 8027.51416 | 8027.51416 | 0.34775 | 0.34775 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7983.79226 | 7983.79226 | 0.58922 | 0.58922 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11617.62177 | 11617.62177 | 0.50313 | 0.50313 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11258.59983 | 11258.59983 | 0.83090 | 0.83090 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7641.49075 | 7641.49075 | 0.33097 | 0.33097 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 16851.52016 | 16851.52016 | 1.24367 | 1.24367 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11554.51272 | 11554.51272 | 0.50039 | 0.50039 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11130.58945 | 11130.58945 | 0.82146 | 0.82146 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7609.43678 | 7609.43678 | 0.32957 | 0.32957 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 67842.71 | 4.80152 | 4.80152 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 61971.30 | 2.17929 | 2.17929 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64182.85 | 4.52916 | 4.52916 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 61866.38 | 2.48189 | 2.48189 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 69745.32 | 4.96099 | 4.96099 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 62216.06 | 3.70020 | 3.70020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63298 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28464 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63718 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75904 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33853E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41947E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63718 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16225.46549 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41947E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 387.96828 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13820 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35051 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63719 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93468 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08700E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.36990E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81784 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27089.40896 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.36990E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 715.59581 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07794 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36067 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63793 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96179 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05636E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.36382E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.50974 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 49881.17888 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36382E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1316.13706 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66389 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23798 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14539 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63461 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60098E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91596E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66389 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21900.57704 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91596E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.44557 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83462 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11984 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51315E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31958 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17922E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25150E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43367 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14305.36918 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25150E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 377.17785 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31139 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12048 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13376 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32127 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16245E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.90736E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.66091 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21802.31042 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.90736E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 574.85626 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86657 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11542 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.80000E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49239E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30777 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30113E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24670E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43200 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14250.56792 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24670E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 375.73384 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52990 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29815 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13619 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79507 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27788E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52974E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52990 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17485.92088 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52974E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 461.10884 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68219 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14662 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52732E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39099 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59856E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00770E-004 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34909 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11518.65081 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00770E-004 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 303.74098 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06327 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14859 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13397 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39624 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56410E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.52383E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52785 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17418.32961 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52383E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 459.32787 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71504 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13987 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11900 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50903E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37299 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72390E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00383E-004 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34775 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11474.36972 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00383E-004 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.57419 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58922 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26814 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13434 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71503 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42092E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45264E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50313 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16604.52943 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45264E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 437.89230 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83090 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32101 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16505E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.55500E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33097 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10921.94922 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.55500E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 288.02305 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24367 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12704 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10800 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13432 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33876 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99914E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44474E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50039 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16514.25656 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44474E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 435.51367 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82146 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12175 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.46099E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32468 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12927E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.51489E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32957 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10876.09884 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.51489E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 286.81491 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81169 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07770 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62339 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.17929 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.80152 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.80152 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.45387 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81173 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07521 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.62346 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.48189 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.52916 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.52916 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.54798 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.87721 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08714 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75441 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.70020 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.96099 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.96099 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.74586 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.80152 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.52916 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.96099 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.80152 |
236 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.80152 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 79482.22169 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.60035 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26491.42449 |
242 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 59078.83189 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16847E-004 |
245 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 866.04496 |
246 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.80152 |
247 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.16847E-004 |
248 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.52916 |
249 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.52916 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 74973.64525 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.50957 |
254 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 24988.71596 |
255 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 59984.14240 |
257 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.24767E-004 |
258 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 861.76381 |
259 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.52916 |
260 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.24767E-004 |
261 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.96099 |
262 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 0.95610 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.96099 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 82121.94571 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65350 |
267 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27371.24450 |
268 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
269 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 59023.40984 |
270 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16363E-004 |
271 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 873.14840 |
272 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.96099 |
273 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.16363E-004 |
274 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.99240E-003 |
275 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.47909 |
276 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.99240E-003 |
277 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1190.43000 |
278 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
279 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 456355.36708 |
280 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 456355.37000 |
281 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.99240E-003 |
282 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
283 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
284 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
285 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
286 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15371.23 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 25673.89 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 47264.50 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20748.95 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13553.08 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20655.87 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13501.17 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16566.86 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10913.17 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16502.83 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10871.22 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15731.97 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10347.95 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15646.46 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10304.51 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 37463.13 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 37099.71 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 37844.33 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 78114.53 | 266537.84 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 5.4671 | 4.3243 | 2.8979 | 1.2077 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 73683.54 | 251418.66 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 5.1570 | 4.0791 | 2.7335 | 1.1392 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 80708.83 | 275389.96 | 11.58 | 3.01 | 3.31 | 3.48 | 3.68 | 10.26 | 11.30 | 11.88 | 12.55 | 5.6487 | 4.4680 | 2.9941 | 1.2478 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.898 | 0.792 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.196 | 0.187 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.676 | 0.614 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.196 | 0.187 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_NORTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_EAST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_SOUTH_0.399 | N/A | 1.488 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.663 | 0.603 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.262_SHGC_WEST_0.399 | N/A | 1.488 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.7611981427E-002 | 1.7554418769E-002 | Pass | Pass | 0.5231318272 | 0.5014594432 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2049490061 | 0.1256555653 | Pass | Pass | 0.5270101061 | 0.5157836573 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.0789163422E-002 | 5.9562462534E-002 | Pass | Pass | 0.4896932209 | 0.4868071020 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.5437514801E-002 | 5.1848267961E-002 | Pass | Pass | 0.4894969504 | 0.4865980741 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.5816144655E-002 | 6.6324046388E-002 | Pass | Pass | 0.8051646279 | 0.7955410078 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2117842703 | 0.1932414619 | Pass | Pass | 0.6810114130 | 0.6358760779 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6954627535 | 0.5620434495 | Pass | Pass | 0.6311539336 | 0.5612660721 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7159768255 | 0.6410145058 | Pass | Pass | 0.6175276647 | 0.5705059729 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6777535695 | 0.6091669250 | Pass | Pass | 0.6176466944 | 0.5813878596 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7132052792 | 0.6396529975 | Pass | Pass | 0.6128390629 | 0.5772481838 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5630911753 | 0.4535937102 | Pass | Pass | 0.6372380324 | 0.5734932258 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5867765917 | 0.5288490474 | Pass | Pass | 0.6455436817 | 0.5737022542 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5458520026 | 0.4933662494 | Pass | Pass | 0.6462449916 | 0.5842723391 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5847887389 | 0.5279686846 | Pass | Pass | 0.6379112260 | 0.5790022912 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5144518757 | 0.4352862200 | Pass | Pass | 0.6703151667 | 0.5741323464 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5349088789 | 0.4844831162 | Pass | Pass | 0.6299835661 | 0.6245233738 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4988962074 | 0.4541054519 | Pass | Pass | 0.6399173748 | 0.6358781198 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5328099752 | 0.4825683186 | Pass | Pass | 0.6310090639 | 0.6244287616 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2353.18 | 125.15 | 0.00 | 2593.74 | 525.49 | 5597.57 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.792 | 0.898 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.614 | 0.676 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.603 | 0.663 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.262_SHGC_NORTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.262_SHGC_EAST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.262_SHGC_EAST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.262_SHGC_WEST_0.399 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.262_SHGC_WEST_0.399 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.488 | 0.400 | 0.440 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.262_SHGC_NORTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.262_SHGC_EAST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.262_SHGC_SOUTH_0.399 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.262_SHGC_WEST_0.399 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.488 | 0.400 | 0.440 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
North Total or Average | 195.79 | 1.488 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.488 | 0.400 | 0.440 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.85 | 0.0000 | Y | 7.74 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.44 | 0.0000 | Y | 4.83 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.82 | 0.0000 | Y | 7.48 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.32 | 0.0000 | Y | 4.81 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.76 | 0.0000 | Y | 7.72 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.38 | 0.0000 | Y | 4.82 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.75 | 0.0000 | Y | 7.46 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.24 | 0.0000 | Y | 4.80 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.85 | 0.0000 | Y | 7.74 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.44 | 0.0000 | Y | 4.83 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 28.82 | 0.0000 | Y | 7.48 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 29.32 | 0.0000 | Y | 4.81 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 241.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 44.84 | 44.84 | 4.75 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.06 | 63.95 | 4.89 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.06 | 52.41 | 46.38 | |
Exterior Lighting Total | 5686.19 | 56.02 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 456355.37 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 79482.22 | 63637.86 | 15844.36 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 74973.65 | 60028.04 | 14945.60 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 82121.95 | 65751.37 | 16370.58 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 78114.5 | 3.01 | 10.26 | N/A | N/A | 11.58 | |
PACU_VAV_MID COOLING COIL | 73683.5 | 3.01 | 10.26 | N/A | N/A | 11.58 | |
PACU_VAV_TOP COOLING COIL | 80708.8 | 3.01 | 10.26 | N/A | N/A | 11.58 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16225.47 | 15371.23 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 27089.41 | 25673.89 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 49881.18 | 47264.50 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21900.58 | 20748.95 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14305.37 | 13553.08 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21802.31 | 20655.87 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14250.57 | 13501.17 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17485.92 | 16566.86 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11518.65 | 10913.17 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17418.33 | 16502.83 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11474.37 | 10871.22 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16604.53 | 15731.97 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10921.95 | 10347.95 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16514.26 | 15646.46 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10876.10 | 10304.51 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 59078.83 | 37463.13 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 59984.14 | 37099.71 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 59023.41 | 37844.33 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.80 | 11036.11 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.53 | 10477.69 | 2313.39 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.96 | 11402.64 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003992 | 1190.43 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 78114.53 | 3.01 | 10.26 | 11.58 | 5.4671 | 3.31 | 11.30 | 4.3243 | 3.48 | 11.88 | 2.8979 | 3.68 | 12.55 | 1.2077 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 73683.54 | 3.01 | 10.26 | 11.58 | 5.1570 | 3.31 | 11.30 | 4.0791 | 3.48 | 11.88 | 2.7335 | 3.68 | 12.55 | 1.1392 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80708.83 | 3.01 | 10.26 | 11.58 | 5.6487 | 3.31 | 11.30 | 4.4680 | 3.48 | 11.88 | 2.9941 | 3.68 | 12.55 | 1.2478 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 35983.86 | 35983.86 | 36.59 | 2.633 | 2.633 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00884 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 29248.59 | 29248.59 | 29.74 | 2.138 | 2.138 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 28426.50 | 28426.50 | 28.90 | 2.078 | 2.078 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 19.85 | 0.00700 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8306.63 | 8306.63 | 40.06 | 0.613 | 0.613 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00877 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11309.03 | 11309.03 | 86.16 | 0.835 | 0.835 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00863 | 22.37 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 17769.17 | 17769.17 | 85.70 | 1.311 | 1.311 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00863 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11741.91 | 11741.91 | 89.46 | 0.867 | 0.867 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00862 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7077.06 | 7077.06 | 34.13 | 0.522 | 0.522 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 24.00 | 24.00 | 0.00884 | 21.08 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9243.47 | 9243.47 | 70.42 | 0.682 | 0.682 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00866 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 14407.06 | 14407.06 | 69.49 | 1.063 | 1.063 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00867 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9688.70 | 9688.70 | 73.82 | 0.715 | 0.715 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00866 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7983.79 | 7983.79 | 38.51 | 0.589 | 0.589 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00879 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 11258.60 | 11258.60 | 85.77 | 0.831 | 0.831 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00863 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 16851.52 | 16851.52 | 81.28 | 1.244 | 1.244 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00864 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11130.59 | 11130.59 | 84.80 | 0.821 | 0.821 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00863 | 24.70 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9909.58 | 9909.58 | 10.08 | 0.432 | 0.432 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 18982.85 | 18982.85 | 19.30 | 0.818 | 0.818 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 34916.36 | 34916.36 | 35.50 | 1.510 | 1.510 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15320.24 | 15320.24 | 73.89 | 0.664 | 0.664 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10006.94 | 10006.94 | 76.24 | 0.434 | 0.434 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15251.54 | 15251.54 | 73.56 | 0.661 | 0.661 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9968.63 | 9968.63 | 75.95 | 0.432 | 0.432 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12233.53 | 12233.53 | 59.00 | 0.530 | 0.530 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8058.47 | 8058.47 | 61.39 | 0.349 | 0.349 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12186.28 | 12186.28 | 58.77 | 0.528 | 0.528 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8027.51 | 8027.51 | 61.16 | 0.348 | 0.348 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11617.62 | 11617.62 | 56.03 | 0.503 | 0.503 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7641.49 | 7641.49 | 58.22 | 0.331 | 0.331 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11554.51 | 11554.51 | 55.73 | 0.500 | 0.500 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7609.44 | 7609.44 | 57.98 | 0.330 | 0.330 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.80 | 4.80 | 2.18 | 2.18 | 4.8015 | 2.1793 | 4.8015 | 0.4539 | 0.3000 |
PACU_VAV_MID | 4.53 | 4.53 | 2.48 | 2.48 | 4.5292 | 2.4819 | 4.5292 | 0.5480 | 0.3000 |
PACU_VAV_TOP | 4.96 | 4.96 | 3.70 | 3.70 | 4.9610 | 3.7002 | 4.9610 | 0.7459 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16225.465 | 16225.465 | 0.637182 | 0.00014195 | 387.968 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 16225.47 | 16225.47 | 0.637182 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 9909.58 | 0.00 | 16278.18 | 16278.18 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27089.409 | 27089.409 | 0.817835 | 0.00023699 | 715.596 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27089.41 | 27089.41 | 0.817835 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 18982.85 | 0.00 | 27186.73 | 27186.73 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 49881.179 | 49881.179 | 1.509735 | 0.00043638 | 1316.137 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 49881.18 | 49881.18 | 1.509735 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 34916.36 | 0.00 | 50049.43 | 50049.43 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21900.577 | 21900.577 | 0.663888 | 0.00019160 | 577.446 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21900.58 | 21828.33 | 0.663888 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798414 | 50.8137 | 15320.24 | 0.00 | 21971.49 | 21971.49 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14305.369 | 14305.369 | 0.433667 | 0.00012515 | 377.178 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14305.37 | 14305.37 | 0.433667 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798382 | 50.8117 | 10006.94 | 0.00 | 14351.64 | 14351.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21802.310 | 21802.310 | 0.660905 | 0.00019074 | 574.856 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21802.31 | 21802.31 | 0.660905 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798407 | 50.8132 | 15251.54 | 0.00 | 21872.92 | 21872.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14250.568 | 14250.568 | 0.432004 | 0.00012467 | 375.734 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14250.57 | 14250.57 | 0.432004 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798376 | 50.8113 | 9968.63 | 0.00 | 14296.66 | 14296.66 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17485.921 | 17485.921 | 0.529905 | 0.00015297 | 461.109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17485.92 | 17423.02 | 0.529905 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798914 | 50.8449 | 12233.53 | 0.00 | 17542.99 | 17542.99 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11518.651 | 11518.651 | 0.349092 | 0.00010077 | 303.741 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11518.65 | 11518.65 | 0.349092 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798909 | 50.8447 | 8058.47 | 0.00 | 11556.18 | 11556.18 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17418.330 | 17418.330 | 0.527853 | 0.00015238 | 459.328 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17418.33 | 17418.33 | 0.527853 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798908 | 50.8446 | 12186.28 | 0.00 | 17475.19 | 17475.19 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11474.370 | 11474.370 | 0.347748 | 0.00010038 | 302.574 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11474.37 | 11474.37 | 0.347748 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798904 | 50.8443 | 8027.51 | 0.00 | 11511.76 | 11511.76 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16604.529 | 16604.529 | 0.503129 | 0.00014526 | 437.892 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16604.53 | 16604.53 | 0.503129 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798210 | 50.8008 | 11617.62 | 0.00 | 16658.91 | 16658.91 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10921.949 | 10921.949 | 0.330966 | 0.00009555 | 288.023 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10921.95 | 10921.95 | 0.330966 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798198 | 50.8001 | 7641.49 | 0.00 | 10957.66 | 10957.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16514.257 | 16514.257 | 0.500389 | 0.00014447 | 435.514 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16514.26 | 16514.26 | 0.500389 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798198 | 50.8001 | 11554.51 | 0.00 | 16568.36 | 16568.36 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10876.099 | 10876.099 | 0.329574 | 0.00009515 | 286.815 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10876.10 | 10876.10 | 0.329574 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798189 | 50.7996 | 7609.44 | 0.00 | 10911.66 | 10911.66 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 79482.222 | 63637.859 | 4.801521 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80736.44 | 80736.44 | 4.801521 | 24.68 | 16.42 | 0.00844648 | 10.90 | 10.90 | 0.00844648 | 27.40 | 0.00700714 | 16.15 | 19.9124 | 24.00 | 0.00880493 | 46.6412 | 64973.83 | 0.00 | 81956.84 | 63994.04 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 59078.832 | 59078.832 | 1.440456 | 0.00051685 | 866.045 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59078.83 | 59078.83 | 1.440456 | -21.63 | -21.63 | 0.00272471 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 66.3748 | 18.26 | 0.00797611 | 60.1795 | 16376.41 | 0.00 | 45315.69 | 45315.69 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 74973.645 | 60028.043 | 4.529158 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 76156.72 | 76156.72 | 4.529158 | 24.72 | 16.43 | 0.00843622 | 10.89 | 10.89 | 0.00843622 | 27.40 | 0.00700714 | 16.15 | 21.1099 | 24.00 | 0.00881950 | 46.7172 | 61256.53 | 0.00 | 77307.89 | 60364.02 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 59984.142 | 59984.142 | 1.358747 | 0.00052477 | 861.764 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59984.14 | 59984.14 | 1.358747 | -24.26 | -24.26 | 0.00240533 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 70.3663 | 17.60 | 0.00794021 | 62.4463 | 17640.06 | 0.00 | 44868.57 | 44868.57 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 82121.946 | 65751.368 | 4.960987 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 83461.76 | 83461.76 | 4.960987 | 24.64 | 16.41 | 0.00844561 | 10.90 | 10.90 | 0.00844561 | 27.30 | 0.00700699 | 16.11 | 19.2724 | 24.00 | 0.00879030 | 46.5646 | 67024.38 | 0.00 | 84678.75 | 66119.38 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 59023.410 | 59023.410 | 1.488296 | 0.00051636 | 873.148 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59023.41 | 59023.41 | 1.488296 | -20.49 | -20.49 | 0.00288928 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 64.2413 | 15.77 | 0.00797287 | 70.4484 | 16067.29 | 0.00 | 45780.28 | 45780.28 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16225.465 | 16225.465 | 0.637182 | 0.00014195 | 387.968 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.4853 | 3.555445 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 16225.47 | 16225.47 | 1.0000 | 0.75534052 | 0.637182 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14193297 | 60.00 | 32.22 | 27.78 | 0.000 | 16225.47 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 9909.58 | 0.00 | 16278.18 | 16278.18 | 0.75534052 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.93 | 19.32 | 0.00800000 | 54610.6 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 27089.409 | 27089.409 | 0.817835 | 0.00023699 | 715.596 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 5.8189 | 5.936034 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27089.41 | 27089.41 | 1.0000 | 0.96949399 | 0.817835 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.23696579 | 60.00 | 32.22 | 27.78 | 0.000 | 27089.41 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 18982.85 | 0.00 | 27186.73 | 27186.73 | 0.96949399 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61102.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 49881.179 | 49881.179 | 1.509735 | 0.00043638 | 1316.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 10.7147 | 10.930337 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 49881.18 | 49881.18 | 1.0000 | 1.78969970 | 1.509735 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.43633780 | 60.00 | 32.22 | 27.78 | 0.000 | 49881.18 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 34916.36 | 0.00 | 50049.43 | 50049.43 | 1.78969970 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21900.577 | 21900.577 | 0.663888 | 0.00019160 | 577.446 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 4.7043 | 4.799018 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21900.58 | 21828.33 | 1.0000 | 0.78699923 | 0.663888 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19157626 | 60.00 | 32.22 | 27.78 | 0.000 | 21900.58 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798414 | 21.00 | 0.00798414 | 50.8137 | 15320.24 | 0.00 | 21971.49 | 21971.49 | 0.78699923 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14305.369 | 14305.369 | 0.433667 | 0.00012515 | 377.178 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.0729 | 3.134699 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14305.37 | 14305.37 | 1.0000 | 0.51408646 | 0.433667 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12513684 | 60.00 | 32.22 | 27.78 | 0.000 | 14305.37 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798382 | 21.00 | 0.00798382 | 50.8117 | 10006.94 | 0.00 | 14351.64 | 14351.64 | 0.51408646 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21802.310 | 21802.310 | 0.660905 | 0.00019074 | 574.856 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 4.6832 | 4.777485 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21802.31 | 21802.31 | 1.0000 | 0.78346306 | 0.660905 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19071667 | 60.00 | 32.22 | 27.78 | 0.000 | 21802.31 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798407 | 21.00 | 0.00798407 | 50.8132 | 15251.54 | 0.00 | 21872.92 | 21872.92 | 0.78346306 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14250.568 | 14250.568 | 0.432004 | 0.00012467 | 375.734 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.0611 | 3.122691 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14250.57 | 14250.57 | 1.0000 | 0.51211445 | 0.432004 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.12465747 | 60.00 | 32.22 | 27.78 | 0.000 | 14250.57 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798376 | 21.00 | 0.00798376 | 50.8113 | 9968.63 | 0.00 | 14296.66 | 14296.66 | 0.51211445 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17485.921 | 17485.921 | 0.529905 | 0.00015297 | 461.109 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.7561 | 3.831646 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17485.92 | 17423.02 | 1.0000 | 0.62816998 | 0.529905 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15295886 | 60.00 | 32.22 | 27.78 | 0.000 | 17485.92 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798914 | 21.00 | 0.00798914 | 50.8449 | 12233.53 | 0.00 | 17542.99 | 17542.99 | 0.62816998 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11518.651 | 11518.651 | 0.349092 | 0.00010077 | 303.741 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 2.4743 | 2.524053 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11518.65 | 11518.65 | 1.0000 | 0.41382726 | 0.349092 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10075990 | 60.00 | 32.22 | 27.78 | 0.000 | 11518.65 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798909 | 21.00 | 0.00798909 | 50.8447 | 8058.47 | 0.00 | 11556.18 | 11556.18 | 0.41382726 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17418.330 | 17418.330 | 0.527853 | 0.00015238 | 459.328 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.7415 | 3.816835 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17418.33 | 17418.33 | 1.0000 | 0.62573756 | 0.527853 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.15236760 | 60.00 | 32.22 | 27.78 | 0.000 | 17418.33 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798908 | 21.00 | 0.00798908 | 50.8446 | 12186.28 | 0.00 | 17475.19 | 17475.19 | 0.62573756 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11474.370 | 11474.370 | 0.347748 | 0.00010038 | 302.574 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 2.4647 | 2.514350 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11474.37 | 11474.37 | 1.0000 | 0.41223376 | 0.347748 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.10037255 | 60.00 | 32.22 | 27.78 | 0.000 | 11474.37 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798904 | 21.00 | 0.00798904 | 50.8443 | 8027.51 | 0.00 | 11511.76 | 11511.76 | 0.41223376 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16604.529 | 16604.529 | 0.503129 | 0.00014526 | 437.892 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.5667 | 3.638509 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16604.53 | 16604.53 | 1.0000 | 0.59642908 | 0.503129 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14524885 | 60.00 | 32.22 | 27.78 | 0.000 | 16604.53 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798210 | 21.00 | 0.00798210 | 50.8008 | 11617.62 | 0.00 | 16658.91 | 16658.91 | 0.59642908 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10921.949 | 10921.949 | 0.330966 | 0.00009555 | 288.023 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 2.3461 | 2.393299 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10921.95 | 10921.95 | 1.0000 | 0.39233969 | 0.330966 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09554023 | 60.00 | 32.22 | 27.78 | 0.000 | 10921.95 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798198 | 21.00 | 0.00798198 | 50.8001 | 7641.49 | 0.00 | 10957.66 | 10957.66 | 0.39233969 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16514.257 | 16514.257 | 0.500389 | 0.00014447 | 435.514 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 3.5473 | 3.618727 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16514.26 | 16514.26 | 1.0000 | 0.59318046 | 0.500389 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.14445918 | 60.00 | 32.22 | 27.78 | 0.000 | 16514.26 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798198 | 21.00 | 0.00798198 | 50.8001 | 11554.51 | 0.00 | 16568.36 | 16568.36 | 0.59318046 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10876.099 | 10876.099 | 0.329574 | 0.00009515 | 286.815 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 2.3362 | 2.383252 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10876.10 | 10876.10 | 1.0000 | 0.39068972 | 0.329574 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09513915 | 60.00 | 32.22 | 27.78 | 0.000 | 10876.10 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798189 | 21.00 | 0.00798189 | 50.7996 | 7609.44 | 0.00 | 10911.66 | 10911.66 | 0.39068972 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.1 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 79482.222 | 63637.859 | 4.801521 | -999.0 | -999.000 | -999.0000 | 1.03461 | 1.00000 | 1020.5416 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.801521 | 5.69191168 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 80736.44 | 80736.44 | 1.0158 | 5.69191168 | 4.801521 | 24.68 | 16.42 | 0.00844648 | 46308.0 | 10.90 | 10.90 | 0.00844648 | 32248.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11036.111 | 69700.33 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 19.9124 | 24.00 | 0.00880493 | 24.00 | 0.00880493 | 46.6412 | 64973.83 | 0.00 | 81956.84 | 63994.04 | 5.46712419 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59078.832 | 59078.832 | 1.440456 | 0.00051685 | 866.045 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.801521 | 5.69191168 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 12.6904 | 12.945795 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59078.83 | 59078.83 | 1.0000 | 1.70757350 | 1.440456 | -21.63 | -21.63 | 0.00272471 | -15030.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.51679467 | 60.00 | 32.22 | 27.78 | 0.000 | 59078.83 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 66.3748 | 18.38 | 0.00797585 | 18.26 | 0.00797611 | 60.1795 | 16376.41 | 0.00 | 45315.69 | 45315.69 | 1.70757350 | 2.80 | 0.12 | 0.00272471 | 9642.1 | 29.08 | 12.97 | 0.00272471 | 36180.1 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 74973.645 | 60028.043 | 4.529158 | -999.0 | -999.000 | -999.0000 | 1.03072 | 1.00000 | 1020.5225 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.529158 | 5.36904175 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 76156.72 | 76156.72 | 1.0158 | 5.36904175 | 4.529158 | 24.72 | 16.43 | 0.00843622 | 46323.9 | 10.89 | 10.89 | 0.00843622 | 32209.7 | -999.0 | -999.00 | -999.00 | -999.00 | 10477.693 | 65679.03 | 27.40 | 0.00700714 | 16.15 | 0.95610000 | 21.1099 | 24.00 | 0.00881950 | 24.00 | 0.00881950 | 46.7172 | 61256.53 | 0.00 | 77307.89 | 60364.02 | 5.15700519 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59984.142 | 59984.142 | 1.358747 | 0.00052477 | 861.764 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.529158 | 5.36904175 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 12.8849 | 13.144174 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59984.14 | 59984.14 | 1.0000 | 1.61071253 | 1.358747 | -24.26 | -24.26 | 0.00240533 | -18471.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.52471391 | 60.00 | 32.22 | 27.78 | 0.000 | 59984.14 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 70.3663 | 17.62 | 0.00796371 | 17.60 | 0.00794021 | 62.4463 | 17640.06 | 0.00 | 44868.57 | 44868.57 | 1.61071253 | 2.80 | -0.56 | 0.00240533 | 8841.7 | 30.40 | 13.18 | 0.00240533 | 36698.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 82121.946 | 65751.368 | 4.960987 | -999.0 | -999.000 | -999.0000 | 1.03807 | 1.00000 | 1020.5400 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.960987 | 5.88094862 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 83461.76 | 83461.76 | 1.0163 | 5.88094862 | 4.960987 | 24.64 | 16.41 | 0.00844561 | 46264.6 | 10.90 | 10.90 | 0.00844561 | 32246.0 | -999.0 | -999.00 | -999.00 | -999.00 | 11402.637 | 72059.12 | 27.30 | 0.00700699 | 16.11 | 0.95610000 | 19.2724 | 24.00 | 0.00879030 | 24.00 | 0.00879030 | 46.5646 | 67024.38 | 0.00 | 84678.75 | 66119.38 | 5.64869560 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 59023.410 | 59023.410 | 1.488296 | 0.00051636 | 873.148 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.960987 | 5.88094862 | 4197.9300 | 999.8980 | 3.99198857 | 54.44 | 82.22 | 27.78 | 465539.70 | 12.6785 | 12.933651 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:40:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59023.41 | 59023.41 | 1.0000 | 1.76428459 | 1.488296 | -20.49 | -20.49 | 0.00288928 | -13476.2 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 0.51630986 | 60.00 | 32.22 | 27.78 | 0.000 | 59023.41 | -41.90 | 0.00006450 | -41.90 | 0.95610000 | 64.2413 | 17.97 | 0.00796404 | 15.77 | 0.00797287 | 70.4484 | 16067.29 | 0.00 | 45780.28 | 45780.28 | 1.76428459 | 2.80 | 0.36 | 0.00288928 | 10054.5 | 28.49 | 12.90 | 0.00288928 | 36002.9 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.80 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.53 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1929.00 | 3521.67 | 883.67 |
CORE_MID | 2638.67 | 4107.17 | 2025.33 |
CORE_TOP | 3166.83 | 4387.17 | 2679.83 |
PERIMETER_TOP_ZN_3 | 3802.67 | 4527.17 | 3180.00 |
PERIMETER_TOP_ZN_2 | 4030.33 | 4064.67 | 2931.17 |
PERIMETER_TOP_ZN_1 | 3847.33 | 4052.33 | 2755.83 |
PERIMETER_TOP_ZN_4 | 3906.50 | 4301.33 | 3062.83 |
PERIMETER_BOT_ZN_3 | 3509.50 | 4651.50 | 3070.67 |
PERIMETER_BOT_ZN_2 | 3881.17 | 3976.00 | 2771.33 |
PERIMETER_BOT_ZN_1 | 3766.00 | 4218.33 | 2788.17 |
PERIMETER_BOT_ZN_4 | 3677.33 | 4284.00 | 2897.00 |
PERIMETER_MID_ZN_3 | 3615.50 | 4323.00 | 2898.33 |
PERIMETER_MID_ZN_2 | 3290.33 | 3356.33 | 2295.83 |
PERIMETER_MID_ZN_1 | 3673.50 | 3802.33 | 2438.33 |
PERIMETER_MID_ZN_4 | 3739.83 | 4093.17 | 2784.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5184.33 | 4918.67 | 3379.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 7.83 | 0.00 | 7.67 | 0.00 |
CORE_MID | 22.33 | 0.00 | 21.50 | 0.00 |
CORE_TOP | 58.17 | 0.00 | 48.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 427.00 | 0.00 | 257.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 267.00 | 13.17 | 103.00 | 12.83 |
PERIMETER_TOP_ZN_1 | 222.17 | 20.83 | 83.50 | 19.67 |
PERIMETER_TOP_ZN_4 | 266.67 | 19.83 | 103.83 | 7.50 |
PERIMETER_BOT_ZN_3 | 335.67 | 0.00 | 285.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 125.33 | 9.17 | 78.17 | 8.83 |
PERIMETER_BOT_ZN_1 | 1206.50 | 12.17 | 1154.17 | 11.67 |
PERIMETER_BOT_ZN_4 | 133.00 | 7.50 | 85.17 | 1.50 |
PERIMETER_MID_ZN_3 | 181.33 | 0.67 | 125.33 | 0.00 |
PERIMETER_MID_ZN_2 | 93.00 | 17.17 | 40.00 | 15.83 |
PERIMETER_MID_ZN_1 | 72.00 | 22.83 | 30.67 | 22.17 |
PERIMETER_MID_ZN_4 | 96.67 | 20.83 | 43.67 | 7.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1459.00 | 100.83 | 1240.33 | 71.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.831 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.655 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.616 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.805 | 0.024 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.199 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.220 | 0.024 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.017 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.658 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.062 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.122 | 0.856 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.862 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.781 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.092 | 0.023 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.242 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.004 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13184243.53 | 0.00 | 13184243.53 | 0.00 | 13184243.53 | 13393058.27 | 5887.57 | 352.35 | 2520.08 | 413.10 |
CORE_MID | 10450466.09 | 0.00 | 10450466.09 | 0.00 | 10450466.09 | 13393058.27 | 5726.69 | 968.53 | 2064.79 | 347.06 |
CORE_TOP | 9806595.51 | 0.00 | 9806595.51 | 0.00 | 9806595.51 | 13393058.27 | 6268.70 | 746.13 | 1745.17 | 86.42 |
PERIMETER_TOP_ZN_3 | 2695860.93 | 0.00 | 2695860.93 | 166682.89 | 2862543.83 | 2823374.22 | 4424.99 | 50.53 | 4284.48 | 86.42 |
PERIMETER_TOP_ZN_2 | 2528465.53 | 0.00 | 2528465.53 | 111121.26 | 2639586.79 | 1787429.43 | 4717.41 | 713.29 | 3329.30 | 86.42 |
PERIMETER_TOP_ZN_1 | 4061872.32 | 0.00 | 4061872.32 | 166682.89 | 4228555.21 | 2823374.22 | 5048.83 | 651.31 | 3059.86 | 86.42 |
PERIMETER_TOP_ZN_4 | 2164415.63 | 0.00 | 2164415.63 | 111121.26 | 2275536.89 | 1787312.18 | 4874.20 | 699.08 | 3186.72 | 86.42 |
PERIMETER_BOT_ZN_3 | 2216993.50 | 0.00 | 2216993.50 | 88623.85 | 2305617.35 | 2823374.22 | 5520.75 | 201.42 | 3037.84 | 413.10 |
PERIMETER_BOT_ZN_2 | 2248281.84 | 0.00 | 2248281.84 | 59082.21 | 2307364.05 | 1787429.43 | 5274.33 | 356.70 | 3128.98 | 413.10 |
PERIMETER_BOT_ZN_1 | 3775246.31 | 0.00 | 3775246.31 | 2926570.99 | 6701817.30 | 2823374.22 | 4916.98 | 353.00 | 3490.01 | 413.10 |
PERIMETER_BOT_ZN_4 | 1835080.41 | 0.00 | 1835080.41 | 59082.21 | 1894162.62 | 1787312.18 | 5411.15 | 355.30 | 2993.55 | 413.10 |
PERIMETER_MID_ZN_3 | 2623483.29 | 0.00 | 2623483.29 | 138750.27 | 2762233.56 | 2823374.22 | 4921.06 | 918.85 | 2920.09 | 347.06 |
PERIMETER_MID_ZN_2 | 2400077.23 | 0.00 | 2400077.23 | 92499.62 | 2492576.86 | 1601953.02 | 4532.67 | 819.27 | 3408.06 | 1256.06 |
PERIMETER_MID_ZN_1 | 4143206.68 | 0.00 | 4143206.68 | 138750.27 | 4281956.94 | 2823374.22 | 4767.81 | 965.79 | 3026.39 | 347.06 |
PERIMETER_MID_ZN_4 | 2144075.44 | 0.00 | 2144075.44 | 92499.62 | 2236575.06 | 1787312.18 | 4973.97 | 906.18 | 2879.86 | 347.06 |
Total Facility | 66278364.23 | 0.00 | 66278364.23 | 4151467.34 | 70429831.57 | 67658168.57 | 7191.27 | 1591.56 | 4669.11 | 1450.77 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6082 | 0.0000 | 0.6082 | 0.0000 | 0.6082 | 0.4247 | 3116.29 | 352.30 | 2474.42 |
CORE_MID | 0.4803 | 0.0000 | 0.4803 | 0.0000 | 0.4803 | 0.4247 | 2971.10 | 967.86 | 2004.04 |
CORE_TOP | 0.4521 | 0.0000 | 0.4521 | 0.0000 | 0.4521 | 0.4247 | 3508.92 | 745.96 | 1688.12 |
PERIMETER_TOP_ZN_3 | 0.1246 | 0.0000 | 0.1246 | 0.0037 | 0.1283 | 0.0895 | 1666.04 | 50.53 | 4226.42 |
PERIMETER_TOP_ZN_2 | 0.1173 | 0.0000 | 0.1173 | 0.0025 | 0.1198 | 0.0567 | 1958.10 | 713.13 | 3271.77 |
PERIMETER_TOP_ZN_1 | 0.1885 | 0.0000 | 0.1885 | 0.0037 | 0.1922 | 0.0895 | 2288.94 | 651.31 | 3002.75 |
PERIMETER_TOP_ZN_4 | 0.0995 | 0.0000 | 0.0995 | 0.0025 | 0.1020 | 0.0567 | 2114.53 | 699.00 | 3129.47 |
PERIMETER_BOT_ZN_3 | 0.1019 | 0.0000 | 0.1019 | 0.0020 | 0.1039 | 0.0895 | 2749.30 | 201.25 | 2992.45 |
PERIMETER_BOT_ZN_2 | 0.1039 | 0.0000 | 0.1039 | 0.0013 | 0.1053 | 0.0567 | 2503.58 | 356.56 | 3082.85 |
PERIMETER_BOT_ZN_1 | 0.1746 | 0.0000 | 0.1746 | 0.1346 | 0.3093 | 0.0895 | 2145.62 | 352.87 | 3444.51 |
PERIMETER_BOT_ZN_4 | 0.0844 | 0.0000 | 0.0844 | 0.0013 | 0.0857 | 0.0567 | 2639.90 | 355.16 | 2947.94 |
PERIMETER_MID_ZN_3 | 0.1208 | 0.0000 | 0.1208 | 0.0031 | 0.1240 | 0.0895 | 2166.34 | 918.27 | 2858.39 |
PERIMETER_MID_ZN_2 | 0.1069 | 0.0000 | 0.1069 | 0.0022 | 0.1091 | 0.0567 | 1778.49 | 818.69 | 2436.82 |
PERIMETER_MID_ZN_1 | 0.1918 | 0.0000 | 0.1918 | 0.0031 | 0.1950 | 0.0895 | 2012.31 | 965.13 | 2965.56 |
PERIMETER_MID_ZN_4 | 0.0983 | 0.0000 | 0.0983 | 0.0021 | 0.1003 | 0.0567 | 2219.14 | 905.40 | 2818.46 |
Total Facility | 3.0532 | 0.0000 | 3.0532 | 0.1623 | 3.2155 | 2.1513 | 4397.27 | 1590.29 | 4585.40 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32686270.62 | 0.00 | 32686270.62 | 22614548.33 | 4161.03 | 1.34 | 4597.63 | 413.10 |
PACU_VAV_MID | 30580409.53 | 0.00 | 30580409.53 | 22429071.92 | 4122.11 | 2.35 | 4635.53 | 346.81 |
PACU_VAV_TOP | 29872040.11 | 0.00 | 29872040.11 | 22614548.33 | 4162.60 | 1.81 | 4595.59 | 86.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5080 | 0.0000 | 1.5080 | 0.7171 | 1391.98 | 1.34 | 4549.68 |
PACU_VAV_MID | 1.4085 | 0.0000 | 1.4085 | 0.7084 | 1373.22 | 2.19 | 4567.59 |
PACU_VAV_TOP | 1.3799 | 0.0000 | 1.3799 | 0.7171 | 1405.77 | 1.64 | 4535.59 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 975.13 | 2375.14 | 0.00 | 0.00 | 0.00 | 1923.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 183.67 | 2460.91 | 0.00 | 0.00 | 0.00 | 2585.28 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 202.66 | 1955.65 | 0.00 | 0.00 | 0.00 | 2651.34 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.3335 | 2.7679 | 0.0000 | 0.0000 | 0.0000 | 1.1603 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2918 | 2.5555 | 0.0000 | 0.0000 | 0.0000 | 1.0568 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.2963 | 2.6920 | 0.0000 | 0.0000 | 0.0000 | 1.0968 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1011 |
Defaulted Fields | 578 |
Fields with Defaults | 2483 |
Autosized Fields | 197 |
Autosizable Fields | 253 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1276.88 | 13751.66 | 02-APR-17:30 | 138533.96 | 11-JUL-15:40 |
Electricity:Building | 961.01 | 13383.13 | 02-APR-17:20 | 66703.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 961.01 | 13383.13 | 02-APR-17:20 | 66703.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 241.33 | 905.38 | 02-APR-17:20 | 25003.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 32.07 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 20.24 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.81 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 20.22 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 32.05 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.72 | 27.57 | 12-FEB-11:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 7.72 | 27.57 | 12-FEB-11:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 20.23 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.82 | 17.46 | 16-JAN-12:00 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.82 | 17.46 | 16-JAN-12:00 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.79 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 27.57 | 15-JAN-11:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 7.46 | 27.57 | 15-JAN-11:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 20.20 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 17.46 | 05-FEB-11:50 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.80 | 17.46 | 05-FEB-11:50 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 32.07 | 413.68 | 02-APR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 7.74 | 27.57 | 12-FEB-11:30 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 20.24 | 261.88 | 02-APR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.83 | 17.46 | 16-JAN-12:10 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.81 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 7.48 | 27.57 | 15-JAN-12:00 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 20.22 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.81 | 17.46 | 05-FEB-12:10 | 658.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 185.85 | 368.53 | 23-APR-17:40 | 71434.02 | 30-JUN-14:30 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 19-JAN-12:20 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 19-JAN-12:20 |
ElectricityPurchased:Facility | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
ElectricityPurchased:Plant | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
Cogeneration:ElectricityPurchased | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
General:Cogeneration:ElectricityPurchased | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
ElectricityNet:Plant | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
Cogeneration:ElectricityNet | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
General:Cogeneration:ElectricityNet | 1276.88 | 13751.66 | 10-JUN-19:00 | 138533.96 | 11-JUL-15:40 |
Fans:Electricity | 88.94 | 0.00 | 01-JAN-00:40 | 27801.25 | 12-JUL-15:20 |
General:Fans:Electricity | 88.94 | 0.00 | 01-JAN-00:40 | 27801.25 | 12-JUL-15:20 |
ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 56.02 | 0.00 | 01-JAN-11:20 | 5686.19 | 01-JAN-06:10 |
HeatRecovery:Electricity | 21.61 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
General:HeatRecovery:Electricity | 21.61 | 0.00 | 01-JAN-00:10 | 2208.01 | 02-JAN-08:30 |
Cooling:Electricity | 48.42 | 0.00 | 01-JAN-00:10 | 43248.51 | 30-JUN-14:30 |
General:Cooling:Electricity | 48.42 | 0.00 | 01-JAN-00:10 | 43248.51 | 30-JUN-14:30 |
Electricity:Plant | 74.00 | 0.00 | 01-JAN-00:40 | 8815.41 | 27-FEB-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 68.06 | 0.00 | 01-JAN-00:10 | 8345.65 | 06-APR-12:00 |
Water Heater:WaterSystems:Electricity | 68.06 | 0.00 | 01-JAN-00:10 | 8345.65 | 06-APR-12:00 |
Pumps:Electricity | 5.93 | 0.00 | 01-JAN-00:40 | 1229.54 | 27-FEB-08:00 |
General:Pumps:Electricity | 5.93 | 0.00 | 01-JAN-00:40 | 1229.54 | 27-FEB-08:00 |
WIRED_LTG_ELECTRICITY | 6.78 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1012.17 | 0.00 | 01-JAN-00:40 | 373684.17 | 27-FEB-08:00 |
NaturalGas:Plant | 1012.17 | 0.00 | 01-JAN-00:40 | 373684.17 | 27-FEB-08:00 |
Heating:NaturalGas | 1012.17 | 0.00 | 01-JAN-00:40 | 373684.17 | 27-FEB-08:00 |
Boiler:Heating:NaturalGas | 1012.17 | 0.00 | 01-JAN-00:40 | 373684.17 | 27-FEB-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3495.29 | 0.00 | 01-JAN-00:40 | 747193.82 | 27-FEB-08:00 |
EnergyTransfer:Building | 1224.66 | 0.00 | 01-JAN-00:40 | 169520.94 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 181.31 | 0.00 | 01-JAN-00:40 | 24743.22 | 24-JUL-07:40 |
Heating:EnergyTransfer | 513.32 | 0.00 | 01-JAN-00:40 | 169520.94 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.72 | 0.00 | 01-JAN-00:10 | 9813.25 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 513.32 | 0.00 | 01-JAN-00:40 | 169520.94 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.72 | 0.00 | 01-JAN-00:10 | 9813.25 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 711.34 | 0.00 | 01-JAN-00:40 | 152497.99 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 180.60 | 0.00 | 01-JAN-00:40 | 24743.22 | 24-JUL-07:40 |
General:Cooling:EnergyTransfer | 711.34 | 0.00 | 01-JAN-00:40 | 152497.99 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 180.60 | 0.00 | 01-JAN-00:40 | 24743.22 | 24-JUL-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.30 | 0.00 | 01-JAN-00:40 | 17409.29 | 12-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.34 | 0.00 | 01-JAN-00:40 | 17409.29 | 12-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.34 | 0.00 | 01-JAN-00:40 | 17409.29 | 12-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.96 | 0.00 | 01-JAN-00:10 | 7915.46 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.96 | 0.00 | 01-JAN-00:10 | 7915.46 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 34.39 | 0.00 | 01-JAN-00:40 | 10974.82 | 02-JAN-09:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.12 | 0.00 | 01-JAN-00:40 | 10974.82 | 02-JAN-09:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.12 | 0.00 | 01-JAN-00:40 | 10974.82 | 02-JAN-09:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.27 | 0.00 | 01-JAN-00:10 | 4679.53 | 24-JUL-06:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 11.27 | 0.00 | 01-JAN-00:10 | 4679.53 | 24-JUL-06:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.04 | 0.00 | 01-JAN-00:40 | 8383.13 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.47 | 0.00 | 01-JAN-00:40 | 8383.13 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.47 | 0.00 | 01-JAN-00:40 | 8383.13 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.58 | 0.00 | 01-JAN-00:10 | 4921.38 | 24-JUL-06:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 16.58 | 0.00 | 01-JAN-00:10 | 4921.38 | 24-JUL-06:20 |
EnergyTransfer:Zone:CORE_MID | 121.07 | 0.00 | 01-JAN-00:40 | 18556.20 | 24-JUL-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 9.77 | 0.00 | 01-JAN-00:40 | 17786.75 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 9.77 | 0.00 | 01-JAN-00:40 | 17786.75 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 111.30 | 0.00 | 01-JAN-00:20 | 18556.20 | 24-JUL-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 111.30 | 0.00 | 01-JAN-00:20 | 18556.20 | 24-JUL-07:30 |
EnergyTransfer:Zone:CORE_TOP | 128.38 | 0.00 | 01-JAN-00:40 | 24169.62 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 37.45 | 0.00 | 01-JAN-00:40 | 24169.62 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 37.45 | 0.00 | 01-JAN-00:40 | 24169.62 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 90.92 | 0.00 | 01-JAN-00:20 | 18093.90 | 24-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 90.92 | 0.00 | 01-JAN-00:20 | 18093.90 | 24-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.83 | 0.00 | 01-JAN-00:40 | 9238.07 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.33 | 0.00 | 01-JAN-00:40 | 9238.07 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.33 | 0.00 | 01-JAN-00:40 | 9238.07 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.51 | 0.00 | 01-JAN-00:10 | 6359.24 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.51 | 0.00 | 01-JAN-00:10 | 6359.24 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.69 | 0.00 | 01-JAN-00:40 | 10533.48 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.49 | 0.00 | 01-JAN-00:40 | 8113.13 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 28.49 | 0.00 | 01-JAN-00:40 | 8113.13 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.20 | 0.00 | 01-JAN-00:10 | 10533.48 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 23.20 | 0.00 | 01-JAN-00:10 | 10533.48 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.61 | 0.00 | 01-JAN-00:40 | 15047.22 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.06 | 0.00 | 01-JAN-00:40 | 12404.27 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.06 | 0.00 | 01-JAN-00:40 | 12404.27 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.56 | 0.00 | 01-JAN-00:10 | 15047.22 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.56 | 0.00 | 01-JAN-00:10 | 15047.22 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.03 | 0.00 | 01-JAN-00:40 | 8423.00 | 11-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.10 | 0.00 | 01-JAN-00:40 | 8194.60 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.10 | 0.00 | 01-JAN-00:40 | 8194.60 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.93 | 0.00 | 01-JAN-00:10 | 8423.00 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 17.93 | 0.00 | 01-JAN-00:10 | 8423.00 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 49.64 | 0.00 | 01-JAN-00:40 | 7203.94 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.46 | 0.00 | 01-JAN-00:40 | 7203.94 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.46 | 0.00 | 01-JAN-00:40 | 7203.94 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 16.17 | 0.00 | 01-JAN-00:10 | 5319.42 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 16.17 | 0.00 | 01-JAN-00:10 | 5319.42 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.72 | 0.00 | 01-JAN-00:40 | 8051.97 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.73 | 0.00 | 01-JAN-00:40 | 6172.71 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.73 | 0.00 | 01-JAN-00:40 | 6172.71 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.00 | 0.00 | 01-JAN-00:10 | 8051.97 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.00 | 0.00 | 01-JAN-00:10 | 8051.97 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.20 | 0.00 | 01-JAN-00:40 | 17872.56 | 27-FEB-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 62.03 | 0.00 | 01-JAN-00:40 | 17872.56 | 27-FEB-07:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 62.03 | 0.00 | 01-JAN-00:40 | 17872.56 | 27-FEB-07:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.18 | 0.00 | 01-JAN-00:10 | 11736.28 | 11-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.18 | 0.00 | 01-JAN-00:10 | 11736.28 | 11-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.37 | 0.00 | 01-JAN-00:40 | 6741.13 | 31-JUL-18:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.17 | 0.00 | 01-JAN-00:40 | 6302.45 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.17 | 0.00 | 01-JAN-00:40 | 6302.45 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 15.21 | 0.00 | 01-JAN-00:10 | 6741.13 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 15.21 | 0.00 | 01-JAN-00:10 | 6741.13 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 49.01 | 0.00 | 01-JAN-00:40 | 7455.64 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.48 | 0.00 | 01-JAN-00:40 | 7455.64 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 27.48 | 0.00 | 01-JAN-00:40 | 7455.64 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.53 | 0.00 | 01-JAN-00:10 | 6806.71 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 21.53 | 0.00 | 01-JAN-00:10 | 6806.71 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.95 | 0.00 | 01-JAN-00:40 | 10465.07 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.00 | 0.00 | 01-JAN-00:40 | 6206.70 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 17.00 | 0.00 | 01-JAN-00:40 | 6206.70 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.95 | 0.00 | 01-JAN-00:10 | 10465.07 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 23.95 | 0.00 | 01-JAN-00:10 | 10465.07 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 64.71 | 0.00 | 01-JAN-00:40 | 14725.37 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 21.70 | 0.00 | 01-JAN-00:40 | 9327.44 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 21.70 | 0.00 | 01-JAN-00:40 | 9327.44 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.00 | 0.00 | 01-JAN-00:10 | 14725.37 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.00 | 0.00 | 01-JAN-00:10 | 14725.37 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.38 | 0.00 | 01-JAN-00:40 | 8133.68 | 06-JUL-17:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 17.91 | 0.00 | 01-JAN-00:40 | 6162.21 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 17.91 | 0.00 | 01-JAN-00:40 | 6162.21 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.48 | 0.00 | 01-JAN-00:10 | 8133.68 | 06-JUL-17:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.48 | 0.00 | 01-JAN-00:10 | 8133.68 | 06-JUL-17:50 |
PlantLoopHeatingDemand:Facility | 822.16 | 0.00 | 01-JAN-00:40 | 299991.66 | 27-FEB-08:00 |
PlantLoopHeatingDemand:Plant | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 03-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 03-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 03-JAN-12:10 |
EnergyTransfer:HVAC | 1454.64 | 0.00 | 01-JAN-00:40 | 297436.24 | 27-FEB-08:00 |
HeatingCoils:EnergyTransfer | 756.99 | 0.00 | 01-JAN-00:40 | 297436.24 | 27-FEB-08:00 |
PlantLoopHeatingDemand:HVAC | 756.99 | 0.00 | 01-JAN-00:40 | 297436.24 | 27-FEB-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 756.99 | 0.00 | 01-JAN-00:40 | 297436.24 | 27-FEB-08:00 |
HeatRecoveryForHeating:EnergyTransfer | 481.72 | 0.00 | 01-JAN-00:10 | 111322.25 | 07-NOV-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 13214.17 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 215.73 | 0.00 | 01-JAN-00:10 | 189808.50 | 30-JUN-12:30 |
EnergyTransfer:Plant | 816.00 | 0.00 | 01-JAN-00:40 | 298535.09 | 27-FEB-08:00 |
WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 03-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 65.17 | 0.00 | 01-JAN-00:10 | 7666.26 | 03-JAN-12:10 |
Boilers:EnergyTransfer | 750.83 | 0.00 | 01-JAN-00:40 | 295979.68 | 27-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.718 | -180.597 | 0.000 | 0.000 | 34.215 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -160.359 |
CORE_MID | 0.000 | 0.000 | 9.773 | -111.301 | 0.000 | 0.000 | 35.568 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -105.064 |
CORE_TOP | 0.000 | 0.000 | 37.452 | -90.923 | 0.000 | 0.000 | 36.151 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -153.704 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 46.325 | -19.508 | 0.000 | 0.000 | 7.743 | 7.742 | 24.333 | 14.704 | 0.000 | 0.002 | 0.001 | 0.000 | -48.526 | 0.000 | -3.839 | -28.975 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 28.489 | -23.203 | 0.000 | 0.000 | 4.822 | 4.834 | 15.404 | 33.607 | 0.000 | 0.001 | 0.000 | 0.000 | -30.963 | 0.000 | -2.597 | -30.393 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 38.057 | -39.554 | 0.000 | 0.000 | 7.584 | 7.475 | 24.332 | 66.134 | 0.000 | 0.002 | 0.001 | 0.000 | -44.467 | 0.000 | -3.953 | -55.610 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 30.102 | -17.930 | 0.000 | 0.000 | 4.876 | 4.814 | 15.403 | 23.390 | 0.000 | 0.001 | 0.000 | 0.000 | -31.785 | 0.000 | -2.608 | -26.262 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 33.465 | -16.175 | 0.000 | 0.000 | 7.742 | 7.719 | 24.333 | 14.987 | 0.000 | 0.001 | 0.001 | 0.000 | -49.155 | 0.000 | -2.072 | -20.844 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 20.727 | -20.997 | 0.000 | 0.000 | 4.808 | 4.823 | 15.404 | 33.719 | 0.000 | 0.001 | 0.000 | 0.000 | -31.575 | 0.000 | -1.420 | -25.489 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 62.025 | -25.175 | 0.000 | 0.000 | 8.019 | 7.457 | 24.332 | 66.767 | 0.000 | 0.081 | 0.001 | 0.000 | -44.443 | 0.000 | -70.260 | -28.803 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 22.168 | -15.206 | 0.000 | 0.000 | 4.855 | 4.801 | 15.403 | 23.557 | 0.000 | 0.001 | 0.000 | 0.000 | -32.375 | 0.000 | -1.419 | -21.785 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 27.476 | -21.529 | 0.000 | 0.000 | 7.667 | 7.742 | 24.333 | 14.458 | 0.000 | 0.002 | 0.001 | 0.000 | -50.027 | 0.000 | -3.307 | -6.814 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 17.002 | -23.947 | 0.000 | 0.000 | 3.537 | 4.834 | 15.404 | 33.371 | 0.000 | 0.001 | 0.000 | 0.000 | -31.852 | 0.000 | -2.235 | -16.114 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 21.705 | -43.003 | 0.000 | 0.000 | 7.511 | 7.475 | 24.332 | 65.834 | 0.000 | 0.002 | 0.001 | 0.000 | -45.889 | 0.000 | -3.403 | -34.564 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 17.907 | -19.477 | 0.000 | 0.000 | 4.833 | 4.814 | 15.403 | 23.251 | 0.000 | 0.001 | 0.000 | 0.000 | -32.756 | 0.000 | -2.242 | -11.734 |
TOPFLOOR_PLENUM | 60.343 | -14.961 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -5.821 | -39.562 |
MIDFLOOR_PLENUM | 23.119 | -11.274 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -5.593 | -6.254 |
FIRSTFLOOR_PLENUM | 16.466 | -16.578 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 4.561 | 0.000 | 0.000 | 0.000 | -4.450 | -0.001 |
Total Facility | 99.927 | -42.813 | 413.389 | -668.524 | 0.000 | 0.000 | 179.931 | 241.325 | 719.689 | 413.778 | 0.000 | 0.100 | 4.567 | 0.000 | -473.815 | 0.000 | -115.220 | -772.331 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-05:12 | 0.00 | 0.00 | 0.00 | -40208.70 | 0.00 | 0.00 | 313.93 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 31935.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -31663.14 | 0.00 | 0.00 | 685.34 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 26306.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-06:03 | 0.00 | 0.00 | 0.00 | -29835.78 | 0.00 | 0.00 | 693.16 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 24471.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -10447.99 | 0.00 | 0.00 | 63.34 | 55.15 | 637.89 | 7864.13 | 0.00 | 0.00 | 1856.23 | 0.00 | -0.00 | 0.00 | -28.75 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:41 | 0.00 | 0.00 | 0.00 | -16062.64 | 0.00 | 0.00 | 12.94 | 17.46 | 302.86 | 11123.55 | 0.00 | 0.00 | 4651.19 | 0.00 | -0.00 | 0.00 | -45.35 | 0.00 |
PERIMETER_TOP_ZN_1 | 23-JUL-12:21 | 0.00 | 0.00 | 0.00 | -25380.92 | 0.00 | 0.00 | 19.90 | 27.57 | 478.41 | 17749.50 | 0.00 | 0.00 | 7125.35 | 0.00 | -0.00 | 0.00 | -19.82 | 0.00 |
PERIMETER_TOP_ZN_4 | 21-MAY-17:22 | 0.00 | 0.00 | 0.00 | -15285.26 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 10225.44 | 0.00 | 0.00 | 4914.44 | 0.00 | -0.00 | 0.00 | -116.49 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-05:14 | 0.00 | 0.00 | 0.00 | -8475.42 | 0.00 | 0.00 | 63.57 | 55.15 | 637.89 | 7919.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14.13 | -186.54 |
PERIMETER_BOT_ZN_2 | 14-MAY-09:31 | 0.00 | 0.00 | 0.00 | -11050.78 | 0.00 | 0.00 | 16.18 | 17.46 | 302.86 | 11231.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -55.65 | -462.03 |
PERIMETER_BOT_ZN_1 | 27-AUG-13:41 | 0.00 | 0.00 | 0.00 | -18276.13 | 0.00 | 0.00 | 23.89 | 27.57 | 478.41 | 16204.60 | 0.00 | 0.00 | 1584.04 | 0.00 | -0.00 | 0.00 | -42.38 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:42 | 0.00 | 0.00 | 0.00 | -9708.50 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 9472.87 | 0.00 | 0.00 | 29.48 | 0.00 | -0.00 | 0.00 | -55.73 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUL-05:12 | 0.00 | 0.00 | 0.00 | -9403.68 | 0.00 | 0.00 | 62.58 | 55.15 | 637.89 | 7852.74 | 0.00 | 0.00 | 819.57 | 0.00 | -0.00 | 0.00 | -24.25 | 0.00 |
PERIMETER_MID_ZN_2 | 09-JUL-07:42 | 0.00 | 0.00 | 0.00 | -14541.61 | 0.00 | 0.00 | 15.00 | 17.46 | 302.86 | 8711.77 | 0.00 | 0.00 | 5595.85 | 0.00 | -0.00 | 0.00 | -101.31 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:12 | 0.00 | 0.00 | 0.00 | -22037.38 | 0.00 | 0.00 | 19.70 | 27.57 | 478.41 | 17495.50 | 0.00 | 0.00 | 4034.87 | 0.00 | -0.00 | 0.00 | -18.67 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -14997.75 | 0.00 | 0.00 | 13.88 | 17.46 | 302.86 | 10666.35 | 0.00 | 0.00 | 4160.07 | 0.00 | -0.00 | 0.00 | -162.87 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -7916.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 7911.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -6181.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6208.31 | 0.00 | -0.00 | 0.00 | -27.14 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-06:13 | 0.00 | -6091.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6111.96 | 0.00 | -0.00 | 0.00 | -20.90 | 0.00 |
Total Facility | 24-JUL-06:02 | 0.00 | -7483.93 | 0.00 | -189141.29 | 0.00 | 0.00 | 3493.10 | 6557.23 | 22496.85 | 28515.09 | 0.00 | 0.00 | 143978.97 | 0.00 | 0.00 | 0.00 | -8416.01 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 11876.35 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17730.14 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 19030.01 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21683.79 |
CORE_TOP | 01-JAN-22:42 | 0.00 | 0.00 | 26297.09 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28340.37 |
PERIMETER_TOP_ZN_3 | 21-FEB-02:62 | 0.00 | 0.00 | 10090.96 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3271.27 | 0.00 | -394.20 | -6984.93 |
PERIMETER_TOP_ZN_2 | 13-NOV-05:11 | 0.00 | 0.00 | 9574.72 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1918.73 | 0.00 | -148.34 | -7861.80 |
PERIMETER_TOP_ZN_1 | 13-NOV-05:11 | 0.00 | 0.00 | 14735.50 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2839.84 | 0.00 | -223.24 | -12231.86 |
PERIMETER_TOP_ZN_4 | 13-NOV-05:11 | 0.00 | 0.00 | 9723.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1888.64 | 0.00 | -148.49 | -8040.90 |
PERIMETER_BOT_ZN_3 | 01-JAN-19:22 | 0.00 | 0.00 | 7896.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2475.19 | 0.00 | -337.39 | -5514.45 |
PERIMETER_BOT_ZN_2 | 01-JAN-19:22 | 0.00 | 0.00 | 7560.24 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1647.91 | 0.00 | -227.12 | -5957.89 |
PERIMETER_BOT_ZN_1 | 27-FEB-07:10 | 0.00 | 0.00 | 18468.31 | 0.00 | 0.00 | 0.00 | 221.62 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 22522.19 | 0.00 | -4236.18 | 0.00 | -37960.68 | 0.00 |
PERIMETER_BOT_ZN_4 | 01-JAN-20:02 | 0.00 | 0.00 | 7718.01 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1658.26 | 0.00 | -206.64 | -6125.79 |
PERIMETER_MID_ZN_3 | 01-JAN-19:22 | 0.00 | 0.00 | 8267.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2514.66 | 0.00 | -530.82 | -5652.54 |
PERIMETER_MID_ZN_2 | 01-JAN-19:22 | 0.00 | 0.00 | 8158.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1674.66 | 0.00 | -357.97 | -6398.63 |
PERIMETER_MID_ZN_1 | 01-JAN-19:22 | 0.00 | 0.00 | 12227.49 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2462.65 | 0.00 | -538.04 | -9657.53 |
PERIMETER_MID_ZN_4 | 01-JAN-19:22 | 0.00 | 0.00 | 8090.65 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1679.42 | 0.00 | -358.05 | -6325.85 |
TOPFLOOR_PLENUM | 29-NOV-06:09 | 18049.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18049.70 |
MIDFLOOR_PLENUM | 02-JAN-09:00 | 10975.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -184.84 | -10790.51 |
FIRSTFLOOR_PLENUM | 02-JAN-08:40 | 8383.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -125.99 | -8257.45 |
Total Facility | 02-JAN-05:01 | 20405.15 | 0.00 | 161488.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25674.30 | 0.00 | -2086.95 | -170775.07 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6234 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8015 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6235 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5292 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7544 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9610 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8117 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0777 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.8117 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0752 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8772 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0871 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6330 | 2.6330 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1382 | 2.1382 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0779 | 2.0779 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6639 | 0.6639 | 0.1454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8346 | 0.8346 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3114 | 1.3114 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8666 | 0.8666 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5299 | 0.5299 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6822 | 0.6822 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0633 | 1.0633 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7150 | 0.7150 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5892 | 0.5892 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8309 | 0.8309 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2437 | 1.2437 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8215 | 0.8215 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6234 | 4.8015 | 5.6234 | 1.0777 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6235 | 4.5292 | 5.6235 | 1.0752 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7544 | 4.9610 | 5.7544 | 1.0871 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3165 | 1.3165 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0691 | 1.0691 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0390 | 1.0390 | 0.6379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3319 | 0.3319 | 0.1454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4173 | 0.4173 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6557 | 0.6557 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4333 | 0.4333 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2650 | 0.2650 | 0.1362 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3411 | 0.3411 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5316 | 0.5316 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3575 | 0.3575 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2946 | 0.2946 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4155 | 0.4155 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6218 | 0.6218 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4107 | 0.4107 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8117 | 1.0777 | 1.0777 | 1.0777 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.8117 | 1.0752 | 1.0752 | 1.0752 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8772 | 1.0871 | 1.0871 | 1.0871 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1240.33 |
Number of hours cooling loads not met | 71.67 |
Number of hours not met | 1312.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1012.17 | 373684.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 48.42 | 43248.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 241.33 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 56.02 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 88.94 | 27801.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 5.93 | 1229.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 21.61 | 2208.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 68.06 | 8345.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1276.88 |
Natural Gas | 0.00 | 1012.17 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2289.05 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 48.44 |
Space Heating | 0.00 |
Space Cooling | 9.72 |
Fans (All) | 17.85 |
Service Water Heating | 13.66 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 256.29 |
Subtotal | 256.29 |
Natural Gas [MJ/m2] | |
Space Heating | 203.16 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 203.16 |
Subtotal | 203.16 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.54 |
Space Heating | 44.22 |
Space Cooling | 2.12 |
Fans (All) | 3.89 |
Service Water Heating | 2.97 |
Receptacle Equipment | 31.44 |
Miscellaneous | 4.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 807. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8705.83 | 54.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8705.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 54.17 | 0.00 | 0.00 | 0.00 |
Average | 8749.23 | 10.77 | 0.00 | 0.00 | 0.00 |
Sum | 157486.17 | 193.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128282.67 | 21.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 21.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.15 | 1.19 | 0.00 | 0.00 | 0.00 |
Sum | 614558.67 | 21.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8681.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 78.83 | 0.00 | 0.00 | 0.00 |
Average | 8749.13 | 10.87 | 0.00 | 0.00 | 0.00 |
Sum | 157484.33 | 195.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128263.17 | 40.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128297.33 | 6.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 40.83 | 0.00 | 0.00 | 0.00 |
Average | 34140.69 | 2.64 | 0.00 | 0.00 | 0.00 |
Sum | 614532.50 | 47.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:08
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.724126E+10 | 9582.50 | 11-JAN-17:01 | -34.5 | -34.6 | 0.159178E+10 | 2414.84 | 27-JAN-16:00 | -12.2 | -12.5 |
February | 0.757447E+10 | 7080.52 | 10-FEB-17:00 | -0.6 | -2.2 | 0.154877E+10 | 2546.40 | 17-FEB-14:00 | -11.1 | -12.7 |
March | 0.936805E+10 | 10938.26 | 23-MAR-16:00 | -1.7 | -4.1 | 0.202106E+10 | 2606.63 | 31-MAR-09:09 | -17.5 | -18.6 |
April | 0.141572E+11 | 37688.30 | 24-APR-05:03 | -3.4 | -6.0 | 0.190310E+10 | 2606.63 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.227349E+11 | 38654.28 | 15-MAY-05:12 | 7.07 | 1.92 | 0.207822E+10 | 2606.67 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.255037E+11 | 39360.29 | 05-JUN-05:12 | 10.77 | 8.82 | 0.207391E+10 | 2606.67 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.250643E+11 | 40131.24 | 03-JUL-05:12 | 10.60 | 9.99 | 0.192855E+10 | 2607.01 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.254280E+11 | 40211.72 | 14-AUG-05:12 | 11.10 | 10.22 | 0.216306E+10 | 2606.66 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.177753E+11 | 38082.04 | 08-SEP-05:03 | 1.60 | 0.93 | 0.191752E+10 | 2606.71 | 26-SEP-13:09 | 3.98 | 0.82 |
October | 0.105385E+11 | 15582.81 | 05-OCT-16:00 | 11.10 | 5.87 | 0.194218E+10 | 2606.63 | 02-OCT-09:09 | 11.10 | 5.87 |
November | 0.750099E+10 | 7509.95 | 29-NOV-09:20 | -29.6 | -29.8 | 0.168328E+10 | 2537.91 | 03-NOV-15:50 | -29.6 | -29.8 |
December | 0.771010E+10 | 8631.25 | 15-DEC-11:10 | -33.3 | -33.5 | 0.152729E+10 | 2328.53 | 22-DEC-16:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.180597E+12 | 0.223787E+11 | ||||||||
Minimum of Months | 0.724126E+10 | 7080.52 | -34.5 | -34.6 | 0.152729E+10 | 2328.53 | -29.6 | -29.8 | ||
Maximum of Months | 0.255037E+11 | 40211.72 | 11.10 | 10.22 | 0.216306E+10 | 2607.01 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 3921476.06 | 566.47 | 22-MAR-17:25 | 4.20 | 1.06 | 0.00 | 0.00 | 01-MAR-00:10 | 4.20 | 1.06 |
April | 0.655368E+09 | 3997.40 | 20-APR-15:20 | 13.70 | 6.18 | 0.00 | 0.00 | 01-APR-00:10 | 13.70 | 6.18 |
May | 0.250547E+10 | 6869.55 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.443031E+10 | 7812.94 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.431583E+10 | 7915.46 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.271162E+10 | 6740.21 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.337093E+09 | 2859.05 | 07-SEP-15:30 | 16.65 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.65 | 8.91 |
October | 1686380.76 | 410.88 | 03-OCT-16:35 | 11.30 | 5.55 | 0.00 | 0.00 | 01-OCT-00:10 | 11.30 | 5.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.149613E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.443031E+10 | 7915.46 | 26.95 | 16.10 | 0.00 | 0.00 | 26.95 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8453759.21 | 3207.14 | 11-JAN-05:01 | -27.4 | -27.5 | 0.00 | 0.00 | 01-JAN-00:10 | -27.4 | -27.5 |
February | 6384039.59 | 2978.59 | 25-FEB-05:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-FEB-00:10 | -24.4 | -24.9 |
March | 7583436.48 | 3363.99 | 01-MAR-05:01 | -28.3 | -28.7 | 0.00 | 0.00 | 01-MAR-00:10 | -28.3 | -28.7 |
April | 0.258048E+09 | 2089.82 | 07-APR-06:01 | -5.1 | -6.0 | 0.00 | 0.00 | 01-APR-00:10 | -5.1 | -6.0 |
May | 0.174473E+10 | 3536.47 | 31-MAY-15:30 | 21.65 | 10.77 | 0.00 | 0.00 | 01-MAY-00:10 | 21.65 | 10.77 |
June | 0.342071E+10 | 5056.55 | 05-JUN-06:13 | 11.30 | 8.88 | 0.00 | 0.00 | 01-JUN-00:10 | 11.30 | 8.88 |
July | 0.328187E+10 | 6181.04 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.225747E+10 | 3806.19 | 11-AUG-15:40 | 25.20 | 14.55 | 0.00 | 0.00 | 01-AUG-00:10 | 25.20 | 14.55 |
September | 0.260678E+09 | 2019.69 | 29-SEP-06:01 | -4.6 | -5.0 | 0.00 | 0.00 | 01-SEP-00:10 | -4.6 | -5.0 |
October | 15537262.61 | 1946.06 | 27-OCT-04:01 | -17.7 | -18.2 | 0.00 | 0.00 | 01-OCT-00:10 | -17.7 | -18.2 |
November | 5183225.34 | 3194.42 | 30-NOV-05:11 | -27.8 | -28.0 | 0.00 | 0.00 | 01-NOV-00:10 | -27.8 | -28.0 |
December | 7309770.63 | 3293.08 | 09-DEC-05:01 | -24.2 | -24.5 | 0.00 | 0.00 | 01-DEC-00:10 | -24.2 | -24.5 |
Annual Sum or Average | 0.112739E+11 | 0.00 | ||||||||
Minimum of Months | 5183225.34 | 1946.06 | -28.3 | -28.7 | 0.00 | 0.00 | -28.3 | -28.7 | ||
Maximum of Months | 0.342071E+10 | 6181.04 | 25.20 | 14.55 | 0.00 | 0.00 | 25.20 | 14.55 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265057E+09 | 5079.46 | 12-JAN-07:10 | -38.3 | -38.4 | 0.00 | 0.00 | 01-JAN-00:10 | -38.3 | -38.4 |
February | 0.213989E+09 | 4136.52 | 18-FEB-05:02 | -23.9 | -24.3 | 0.00 | 0.00 | 01-FEB-00:10 | -23.9 | -24.3 |
March | 0.317598E+09 | 4905.80 | 31-MAR-06:10 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.702607E+09 | 3420.97 | 12-APR-06:01 | -5.8 | -7.6 | 0.00 | 0.00 | 01-APR-00:10 | -5.8 | -7.6 |
May | 0.240594E+10 | 4258.85 | 22-MAY-06:08 | 5.05 | 2.54 | 0.00 | 0.00 | 01-MAY-00:10 | 5.05 | 2.54 |
June | 0.384241E+10 | 5382.84 | 12-JUN-06:15 | 10.37 | 7.65 | 0.00 | 0.00 | 01-JUN-00:10 | 10.37 | 7.65 |
July | 0.388821E+10 | 6090.95 | 24-JUL-06:13 | 14.47 | 13.19 | 0.00 | 0.00 | 01-JUL-00:10 | 14.47 | 13.19 |
August | 0.318924E+10 | 5549.95 | 28-AUG-06:05 | 5.87 | 5.03 | 0.00 | 0.00 | 01-AUG-00:10 | 5.87 | 5.03 |
September | 0.929861E+09 | 3170.23 | 11-SEP-06:07 | 5.50 | 4.95 | 0.00 | 0.00 | 01-SEP-00:10 | 5.50 | 4.95 |
October | 0.220171E+09 | 3124.00 | 27-OCT-16:10 | -11.4 | -12.2 | 0.00 | 0.00 | 01-OCT-00:10 | -11.4 | -12.2 |
November | 0.300527E+09 | 3768.94 | 30-NOV-17:10 | -27.0 | -27.2 | 0.00 | 0.00 | 01-NOV-00:10 | -27.0 | -27.2 |
December | 0.302877E+09 | 3936.56 | 15-DEC-07:10 | -33.4 | -33.5 | 0.00 | 0.00 | 01-DEC-00:10 | -33.4 | -33.5 |
Annual Sum or Average | 0.165785E+11 | 0.00 | ||||||||
Minimum of Months | 0.213989E+09 | 3124.00 | -38.3 | -38.4 | 0.00 | 0.00 | -38.3 | -38.4 | ||
Maximum of Months | 0.388821E+10 | 6090.95 | 14.47 | 13.19 | 0.00 | 0.00 | 14.47 | 13.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255346E+10 | 4809.76 | 11-JAN-17:00 | -34.4 | -34.5 | 0.146490E+10 | 2065.31 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.352961E+10 | 5366.96 | 09-FEB-17:00 | -2.2 | -2.6 | 0.137344E+10 | 2268.11 | 09-FEB-14:00 | -2.2 | -2.6 |
March | 0.603127E+10 | 6029.85 | 23-MAR-16:00 | -1.7 | -4.1 | 0.175163E+10 | 2457.28 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.907764E+10 | 12603.85 | 21-APR-16:00 | 14.40 | 5.45 | 0.179466E+10 | 2606.64 | 14-APR-09:09 | 14.40 | 5.45 |
May | 0.154156E+11 | 27689.37 | 15-MAY-06:01 | 8.07 | 2.53 | 0.206773E+10 | 2606.66 | 16-MAY-09:20 | 6.33 | 4.90 |
June | 0.183273E+11 | 31622.93 | 05-JUN-06:03 | 11.20 | 8.82 | 0.206860E+10 | 2606.65 | 29-JUN-09:20 | 19.63 | 14.92 |
July | 0.177465E+11 | 31665.11 | 24-JUL-06:03 | 14.18 | 13.06 | 0.192269E+10 | 2606.91 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.167989E+11 | 31294.25 | 14-AUG-05:12 | 11.10 | 10.22 | 0.215565E+10 | 2606.65 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.101925E+11 | 12720.72 | 01-SEP-16:00 | 15.60 | 10.82 | 0.186282E+10 | 2607.49 | 07-SEP-09:30 | 6.40 | 3.63 |
October | 0.619783E+10 | 7447.29 | 05-OCT-16:00 | 11.10 | 5.87 | 0.168130E+10 | 2606.54 | 05-OCT-13:20 | 11.10 | 5.87 |
November | 0.308850E+10 | 5123.38 | 30-NOV-17:01 | -27.0 | -27.2 | 0.147353E+10 | 2129.60 | 02-NOV-13:00 | -27.0 | -27.2 |
December | 0.234145E+10 | 5241.92 | 22-DEC-13:01 | -26.2 | -26.4 | 0.140932E+10 | 2012.59 | 21-DEC-14:00 | -26.2 | -26.4 |
Annual Sum or Average | 0.111301E+12 | 0.210263E+11 | ||||||||
Minimum of Months | 0.234145E+10 | 4809.76 | -34.4 | -34.5 | 0.137344E+10 | 2012.59 | -27.0 | -27.2 | ||
Maximum of Months | 0.183273E+11 | 31665.11 | 15.60 | 13.06 | 0.215565E+10 | 2607.49 | 19.63 | 14.92 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.787366E+09 | 4025.53 | 20-JAN-17:00 | -11.1 | -11.2 | 0.144787E+10 | 1929.44 | 09-JAN-10:09 | -11.1 | -11.2 |
February | 0.162762E+10 | 4990.93 | 09-FEB-15:50 | 0.50 | -0.6 | 0.132590E+10 | 2155.90 | 09-FEB-14:00 | 0.50 | -0.6 |
March | 0.382484E+10 | 5853.65 | 22-MAR-16:00 | 5.60 | 2.61 | 0.164500E+10 | 2353.98 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 0.741775E+10 | 12386.79 | 21-APR-16:00 | 14.40 | 5.45 | 0.169624E+10 | 2607.66 | 21-APR-09:00 | 14.40 | 5.45 |
May | 0.139124E+11 | 16467.57 | 31-MAY-15:50 | 22.02 | 10.78 | 0.205160E+10 | 2606.66 | 16-MAY-09:20 | 22.02 | 10.78 |
June | 0.175933E+11 | 26791.75 | 12-JUN-06:01 | 10.18 | 7.56 | 0.206564E+10 | 2606.64 | 27-JUN-09:20 | 13.90 | 13.13 |
July | 0.169543E+11 | 29837.10 | 24-JUL-06:03 | 14.18 | 13.06 | 0.191968E+10 | 2606.86 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.150191E+11 | 16469.57 | 01-AUG-14:00 | 19.40 | 14.22 | 0.214405E+10 | 2606.65 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.810042E+10 | 11719.60 | 01-SEP-16:00 | 15.60 | 10.82 | 0.176746E+10 | 2606.67 | 01-SEP-09:20 | 15.60 | 10.82 |
October | 0.397287E+10 | 6188.13 | 04-OCT-16:00 | 10.00 | 4.57 | 0.154744E+10 | 2494.88 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.103081E+10 | 4246.20 | 02-NOV-16:00 | -8.9 | -9.4 | 0.143563E+10 | 1945.78 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.682296E+09 | 3993.45 | 23-DEC-17:02 | -2.6 | -3.4 | 0.139702E+10 | 1929.37 | 04-DEC-10:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.909230E+11 | 0.204435E+11 | ||||||||
Minimum of Months | 0.682296E+09 | 3993.45 | -11.1 | -11.2 | 0.132590E+10 | 1929.37 | -13.9 | -14.6 | ||
Maximum of Months | 0.175933E+11 | 29837.10 | 22.02 | 14.22 | 0.214405E+10 | 2607.66 | 22.02 | 13.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6223750.06 | 872.11 | 21-JAN-17:02 | -5.5 | -5.8 | 0.300081E+09 | 406.82 | 10-JAN-14:09 | -5.5 | -5.8 |
February | 6771049.62 | 876.56 | 11-FEB-17:03 | -1.2 | -2.7 | 0.273869E+09 | 406.84 | 24-FEB-10:50 | -24.6 | -25.1 |
March | 0.102828E+09 | 1144.49 | 22-MAR-16:00 | 5.60 | 2.61 | 0.331700E+09 | 447.90 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.112671E+10 | 2352.77 | 28-APR-15:20 | 12.20 | 4.90 | 0.329149E+09 | 549.49 | 21-APR-13:20 | 12.20 | 4.90 |
May | 0.316462E+10 | 9240.61 | 31-MAY-05:12 | 12.43 | 7.84 | 0.427928E+09 | 549.50 | 19-MAY-13:20 | 12.43 | 7.84 |
June | 0.525115E+10 | 10239.82 | 29-JUN-05:12 | 12.57 | 11.17 | 0.435724E+09 | 549.50 | 27-JUN-09:20 | 12.57 | 11.17 |
July | 0.488239E+10 | 10448.88 | 11-JUL-05:12 | 15.37 | 12.05 | 0.404856E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.343913E+10 | 4720.60 | 02-AUG-15:30 | 22.75 | 14.69 | 0.445240E+09 | 549.50 | 07-AUG-09:20 | 11.87 | 11.33 |
September | 0.130418E+10 | 2330.82 | 01-SEP-16:00 | 15.60 | 10.82 | 0.340229E+09 | 549.49 | 01-SEP-13:20 | 15.60 | 10.82 |
October | 0.211820E+09 | 1208.07 | 04-OCT-15:40 | 10.37 | 4.66 | 0.309502E+09 | 468.39 | 04-OCT-13:00 | 10.37 | 4.66 |
November | 5129885.16 | 869.94 | 04-NOV-16:02 | -9.6 | -11.3 | 0.298890E+09 | 406.85 | 17-NOV-10:30 | -25.0 | -25.3 |
December | 7503520.74 | 872.85 | 23-DEC-17:02 | -2.6 | -3.4 | 0.290220E+09 | 406.92 | 12-DEC-14:09 | -2.6 | -3.4 |
Annual Sum or Average | 0.195084E+11 | 0.418739E+10 | ||||||||
Minimum of Months | 5129885.16 | 869.94 | -9.6 | -11.3 | 0.273869E+09 | 406.82 | -25.0 | -25.3 | ||
Maximum of Months | 0.525115E+10 | 10448.88 | 22.75 | 14.69 | 0.445240E+09 | 549.54 | 17.38 | 14.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4170856.81 | 510.59 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192284E+09 | 257.59 | 03-JAN-14:00 | -5.5 | -5.8 |
February | 16361939.94 | 586.63 | 09-FEB-11:35 | -2.2 | -2.5 | 0.174938E+09 | 260.72 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.353222E+09 | 1911.96 | 22-MAR-10:30 | 2.25 | 0.43 | 0.223722E+09 | 347.88 | 27-MAR-09:50 | -9.8 | -11.9 |
April | 0.154023E+10 | 5927.14 | 22-APR-09:20 | 8.87 | 3.75 | 0.232746E+09 | 348.33 | 21-APR-09:00 | 8.87 | 3.75 |
May | 0.467277E+10 | 14998.68 | 21-MAY-10:02 | 12.88 | 5.99 | 0.275580E+09 | 348.35 | 11-MAY-09:00 | 12.88 | 5.99 |
June | 0.552939E+10 | 12479.65 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276298E+09 | 348.41 | 07-JUN-09:50 | 12.40 | 9.24 |
July | 0.543729E+10 | 16062.09 | 23-JUL-09:41 | 20.63 | 14.69 | 0.256986E+09 | 348.74 | 07-JUL-09:50 | 20.63 | 14.69 |
August | 0.408394E+10 | 11450.88 | 10-AUG-06:01 | 10.78 | 7.96 | 0.286835E+09 | 348.32 | 10-AUG-09:00 | 17.80 | 11.30 |
September | 0.129709E+10 | 5622.78 | 10-SEP-09:02 | 11.38 | 6.43 | 0.232211E+09 | 347.88 | 01-SEP-09:20 | 11.38 | 6.43 |
October | 0.260686E+09 | 1807.47 | 03-OCT-09:50 | 3.43 | 2.35 | 0.202523E+09 | 347.87 | 03-OCT-09:20 | 3.43 | 2.35 |
November | 3535958.69 | 509.35 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190808E+09 | 257.58 | 27-NOV-14:09 | -23.9 | -24.2 |
December | 4817190.25 | 510.92 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185650E+09 | 257.62 | 27-DEC-14:50 | -23.9 | -24.1 |
Annual Sum or Average | 0.232035E+11 | 0.273058E+10 | ||||||||
Minimum of Months | 3535958.69 | 509.35 | -9.6 | -11.3 | 0.174938E+09 | 257.58 | -23.9 | -24.2 | ||
Maximum of Months | 0.552939E+10 | 16062.09 | 20.63 | 14.69 | 0.286835E+09 | 348.74 | 20.63 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28165998.63 | 991.17 | 25-JAN-13:30 | -19.8 | -20.0 | 0.304199E+09 | 435.89 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.304408E+09 | 3881.92 | 15-FEB-13:50 | -8.5 | -9.4 | 0.288223E+09 | 549.49 | 09-FEB-14:00 | -8.5 | -9.4 |
March | 0.149252E+10 | 8104.49 | 31-MAR-13:50 | -11.2 | -13.1 | 0.375292E+09 | 549.49 | 01-MAR-14:20 | -11.2 | -13.1 |
April | 0.435099E+10 | 15685.11 | 23-APR-15:43 | 8.40 | 2.69 | 0.366084E+09 | 549.92 | 21-APR-09:00 | 8.40 | 2.69 |
May | 0.660696E+10 | 24145.17 | 21-MAY-13:21 | 15.00 | 7.02 | 0.428923E+09 | 550.22 | 12-MAY-13:50 | 15.00 | 7.02 |
June | 0.776575E+10 | 17878.95 | 11-JUN-14:13 | 17.57 | 10.82 | 0.435146E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.768062E+10 | 25377.78 | 23-JUL-12:21 | 24.45 | 15.55 | 0.404656E+09 | 550.00 | 12-JUL-13:00 | 24.45 | 15.55 |
August | 0.710664E+10 | 22392.41 | 27-AUG-13:12 | 18.33 | 13.81 | 0.449489E+09 | 549.85 | 25-AUG-13:00 | 18.33 | 13.81 |
September | 0.320823E+10 | 16758.20 | 10-SEP-11:43 | 15.40 | 8.26 | 0.365742E+09 | 549.51 | 08-SEP-13:09 | 15.40 | 8.26 |
October | 0.925469E+09 | 9207.85 | 03-OCT-13:30 | 10.85 | 6.24 | 0.332114E+09 | 549.50 | 30-OCT-13:20 | -11.8 | -12.9 |
November | 77495282.71 | 1745.47 | 08-NOV-13:40 | -13.5 | -14.3 | 0.303742E+09 | 549.50 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 7837856.37 | 804.69 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293343E+09 | 406.92 | 27-DEC-14:39 | -23.9 | -24.1 |
Annual Sum or Average | 0.395551E+11 | 0.434695E+10 | ||||||||
Minimum of Months | 7837856.37 | 804.69 | -19.8 | -20.0 | 0.288223E+09 | 406.92 | -23.9 | -24.1 | ||
Maximum of Months | 0.776575E+10 | 25377.78 | 24.45 | 15.55 | 0.449489E+09 | 550.22 | 24.45 | 15.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4219790.34 | 509.06 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192218E+09 | 257.54 | 02-JAN-14:09 | -5.5 | -5.8 |
February | 14432922.90 | 573.34 | 09-FEB-15:30 | 0.30 | -0.8 | 0.174781E+09 | 260.40 | 09-FEB-14:00 | 0.30 | -0.8 |
March | 0.180378E+09 | 1055.85 | 31-MAR-16:50 | -9.4 | -11.7 | 0.214052E+09 | 338.67 | 22-MAR-15:00 | -9.4 | -11.7 |
April | 0.163451E+10 | 8591.62 | 22-APR-17:08 | 14.13 | 6.18 | 0.216981E+09 | 347.85 | 27-APR-13:20 | 10.77 | 4.21 |
May | 0.307361E+10 | 15284.33 | 21-MAY-17:22 | 16.10 | 7.39 | 0.269896E+09 | 347.85 | 19-MAY-09:20 | 16.10 | 7.39 |
June | 0.453037E+10 | 14012.88 | 10-JUN-17:05 | 21.20 | 10.81 | 0.275544E+09 | 347.85 | 27-JUN-09:20 | 13.90 | 13.13 |
July | 0.404362E+10 | 14039.57 | 23-JUL-14:21 | 25.30 | 15.39 | 0.256054E+09 | 347.88 | 19-JUL-09:09 | 25.30 | 15.39 |
August | 0.316970E+10 | 12269.91 | 27-AUG-17:12 | 20.93 | 12.63 | 0.282465E+09 | 347.85 | 07-AUG-09:20 | 20.93 | 12.63 |
September | 0.109638E+10 | 6447.64 | 02-SEP-17:43 | 16.70 | 10.38 | 0.220433E+09 | 347.85 | 08-SEP-13:20 | 11.47 | 7.77 |
October | 0.174355E+09 | 1021.15 | 03-OCT-15:00 | 12.80 | 6.92 | 0.198063E+09 | 338.67 | 03-OCT-15:00 | 11.70 | 6.37 |
November | 3915335.13 | 508.80 | 04-NOV-16:02 | -9.6 | -11.3 | 0.190816E+09 | 257.56 | 09-NOV-10:39 | -24.6 | -24.9 |
December | 4870542.69 | 509.41 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185649E+09 | 257.60 | 27-DEC-14:39 | -23.9 | -24.1 |
Annual Sum or Average | 0.179304E+11 | 0.267695E+10 | ||||||||
Minimum of Months | 3915335.13 | 508.80 | -9.6 | -11.7 | 0.174781E+09 | 257.54 | -24.6 | -24.9 | ||
Maximum of Months | 0.453037E+10 | 15284.33 | 25.30 | 15.39 | 0.282465E+09 | 347.88 | 25.30 | 15.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8805160.92 | 821.18 | 21-JAN-17:02 | -5.5 | -5.8 | 0.294199E+09 | 406.81 | 18-JAN-14:39 | -5.5 | -5.8 |
February | 6974253.19 | 820.76 | 11-FEB-17:03 | -1.2 | -2.7 | 0.269778E+09 | 406.81 | 22-FEB-14:30 | -17.2 | -18.0 |
March | 38103596.65 | 898.85 | 22-MAR-15:30 | 5.60 | 2.42 | 0.330963E+09 | 410.24 | 22-MAR-13:00 | 5.60 | 2.42 |
April | 0.849265E+09 | 1273.88 | 28-APR-16:00 | 12.20 | 5.13 | 0.315366E+09 | 513.30 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.217133E+10 | 3883.97 | 31-MAY-06:02 | 14.08 | 8.75 | 0.420840E+09 | 549.50 | 19-MAY-13:20 | 14.08 | 8.75 |
June | 0.382789E+10 | 7695.83 | 29-JUN-05:12 | 12.57 | 11.17 | 0.435124E+09 | 549.50 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.401076E+10 | 8476.62 | 11-JUL-05:14 | 15.37 | 12.05 | 0.404761E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.317762E+10 | 6994.86 | 02-AUG-06:01 | 11.28 | 10.30 | 0.449957E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.156438E+10 | 1906.06 | 01-SEP-13:50 | 14.82 | 10.69 | 0.362395E+09 | 549.49 | 13-SEP-13:20 | 11.87 | 8.91 |
October | 0.494168E+09 | 1187.74 | 06-OCT-15:00 | 10.60 | 4.90 | 0.316497E+09 | 491.57 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 7755494.63 | 831.92 | 04-NOV-16:02 | -9.6 | -11.3 | 0.299688E+09 | 406.83 | 30-NOV-14:00 | -26.1 | -26.4 |
December | 17764051.95 | 823.86 | 23-DEC-17:02 | -2.6 | -3.4 | 0.288844E+09 | 406.83 | 07-DEC-10:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.161748E+11 | 0.418841E+10 | ||||||||
Minimum of Months | 6974253.19 | 820.76 | -9.6 | -11.3 | 0.269778E+09 | 406.81 | -26.1 | -26.4 | ||
Maximum of Months | 0.401076E+10 | 8476.62 | 15.37 | 12.05 | 0.449957E+09 | 549.54 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6106783.42 | 513.39 | 21-JAN-17:02 | -5.5 | -5.8 | 0.191123E+09 | 257.56 | 04-JAN-14:09 | -5.5 | -5.8 |
February | 11662102.47 | 557.29 | 15-FEB-10:40 | -16.3 | -16.5 | 0.174544E+09 | 258.80 | 15-FEB-10:50 | -16.0 | -16.2 |
March | 0.280065E+09 | 1375.02 | 31-MAR-09:25 | -17.0 | -18.1 | 0.219751E+09 | 347.88 | 31-MAR-09:00 | -16.1 | -17.3 |
April | 0.121456E+10 | 3975.47 | 22-APR-08:30 | 6.65 | 2.48 | 0.230419E+09 | 347.88 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.379776E+10 | 11050.59 | 14-MAY-09:31 | 15.73 | 8.25 | 0.275917E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.460436E+10 | 10038.51 | 13-JUN-05:12 | 12.40 | 9.24 | 0.276226E+09 | 348.13 | 08-JUN-09:09 | 12.40 | 9.24 |
July | 0.488656E+10 | 10119.34 | 07-JUL-05:12 | 15.57 | 11.80 | 0.257155E+09 | 348.40 | 07-JUL-09:50 | 21.93 | 14.83 |
August | 0.407741E+10 | 9311.04 | 25-AUG-06:01 | 7.98 | 7.08 | 0.287779E+09 | 348.21 | 11-AUG-09:09 | 7.98 | 7.08 |
September | 0.163682E+10 | 7856.91 | 10-SEP-09:53 | 12.80 | 7.13 | 0.243945E+09 | 347.88 | 08-SEP-13:20 | 12.80 | 7.13 |
October | 0.466419E+09 | 2325.01 | 03-OCT-09:30 | 2.50 | 1.67 | 0.211413E+09 | 347.88 | 13-OCT-09:30 | -7.8 | -8.6 |
November | 4998563.28 | 519.99 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191099E+09 | 257.58 | 28-NOV-14:39 | -25.4 | -25.6 |
December | 9955541.11 | 514.61 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185625E+09 | 257.60 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.209967E+11 | 0.274500E+10 | ||||||||
Minimum of Months | 4998563.28 | 513.39 | -17.0 | -18.1 | 0.174544E+09 | 257.56 | -25.4 | -25.6 | ||
Maximum of Months | 0.488656E+10 | 11050.59 | 15.73 | 11.80 | 0.287779E+09 | 348.40 | 21.93 | 14.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8585042.29 | 806.89 | 28-JAN-17:01 | -21.8 | -22.5 | 0.226626E+09 | 406.66 | 19-JAN-14:50 | -21.8 | -22.5 |
February | 67846258.81 | 1080.29 | 18-FEB-13:40 | -14.3 | -15.7 | 0.236369E+09 | 438.87 | 09-FEB-14:09 | -14.3 | -15.7 |
March | 0.225523E+09 | 1299.35 | 11-MAR-13:50 | -3.8 | -5.8 | 0.314592E+09 | 509.42 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.193265E+10 | 9018.29 | 23-APR-14:12 | 9.63 | 3.53 | 0.339633E+09 | 549.51 | 24-APR-13:09 | 4.40 | -1.0 |
May | 0.360995E+10 | 14816.26 | 14-MAY-12:11 | 18.17 | 9.44 | 0.413398E+09 | 549.51 | 05-MAY-13:20 | 18.17 | 9.44 |
June | 0.507343E+10 | 12302.18 | 04-JUN-14:32 | 19.23 | 11.76 | 0.427486E+09 | 549.53 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.587148E+10 | 18182.20 | 23-JUL-13:52 | 25.00 | 15.26 | 0.399540E+09 | 549.66 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.548411E+10 | 18276.49 | 27-AUG-13:41 | 19.13 | 14.11 | 0.442281E+09 | 549.55 | 25-AUG-13:00 | 19.13 | 14.11 |
September | 0.234939E+10 | 14338.75 | 10-SEP-11:13 | 14.80 | 7.99 | 0.353562E+09 | 549.51 | 08-SEP-13:09 | 14.80 | 7.99 |
October | 0.529821E+09 | 5982.29 | 03-OCT-13:40 | 11.13 | 6.36 | 0.308394E+09 | 549.51 | 13-OCT-13:09 | 0.18 | -2.9 |
November | 14757075.64 | 864.63 | 25-NOV-13:40 | -17.6 | -18.0 | 0.244697E+09 | 406.72 | 09-NOV-14:00 | -17.6 | -18.0 |
December | 7779518.06 | 801.29 | 23-DEC-17:02 | -2.6 | -3.4 | 0.204909E+09 | 382.54 | 21-DEC-10:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.251753E+11 | 0.391149E+10 | ||||||||
Minimum of Months | 7779518.06 | 801.29 | -21.8 | -22.5 | 0.204909E+09 | 382.54 | -21.8 | -22.5 | ||
Maximum of Months | 0.587148E+10 | 18276.49 | 25.00 | 15.26 | 0.442281E+09 | 549.66 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6107090.03 | 511.60 | 21-JAN-17:02 | -5.5 | -5.8 | 0.191029E+09 | 257.54 | 18-JAN-14:30 | -5.5 | -5.8 |
February | 5562265.02 | 511.95 | 11-FEB-17:03 | -1.2 | -2.7 | 0.173919E+09 | 257.54 | 13-FEB-10:20 | -15.5 | -15.8 |
March | 0.102127E+09 | 756.65 | 31-MAR-17:13 | -9.4 | -11.7 | 0.211543E+09 | 293.42 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.120143E+10 | 5348.47 | 21-APR-18:20 | 14.03 | 5.87 | 0.217015E+09 | 347.85 | 21-APR-13:20 | 14.03 | 5.87 |
May | 0.218444E+10 | 7674.89 | 28-MAY-18:42 | 16.70 | 8.41 | 0.270122E+09 | 347.86 | 16-MAY-09:20 | 16.70 | 8.41 |
June | 0.355049E+10 | 8446.39 | 12-JUN-06:01 | 10.18 | 7.56 | 0.275594E+09 | 347.85 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.343189E+10 | 7716.65 | 10-JUL-06:02 | 12.15 | 10.14 | 0.256387E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.306752E+10 | 9709.30 | 27-AUG-17:42 | 20.68 | 12.29 | 0.286257E+09 | 347.85 | 21-AUG-09:20 | 20.68 | 12.29 |
September | 0.129524E+10 | 3668.92 | 08-SEP-16:00 | 14.40 | 9.03 | 0.235413E+09 | 347.86 | 01-SEP-09:20 | 14.40 | 9.03 |
October | 0.344817E+09 | 972.34 | 03-OCT-15:10 | 12.62 | 6.83 | 0.203001E+09 | 338.67 | 03-OCT-15:50 | 11.88 | 6.46 |
November | 6221767.09 | 519.41 | 04-NOV-16:02 | -9.6 | -11.3 | 0.191111E+09 | 257.55 | 13-NOV-14:39 | -12.8 | -13.2 |
December | 10004953.87 | 513.24 | 23-DEC-17:02 | -2.6 | -3.4 | 0.185651E+09 | 257.59 | 12-DEC-14:30 | -2.6 | -3.4 |
Annual Sum or Average | 0.152059E+11 | 0.269704E+10 | ||||||||
Minimum of Months | 5562265.02 | 511.60 | -9.6 | -11.7 | 0.173919E+09 | 257.54 | -15.5 | -15.8 | ||
Maximum of Months | 0.355049E+10 | 9709.30 | 20.68 | 12.29 | 0.286257E+09 | 347.88 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7761120.39 | 821.16 | 21-JAN-17:02 | -5.5 | -5.8 | 0.302231E+09 | 406.83 | 03-JAN-14:50 | -5.5 | -5.8 |
February | 17904318.04 | 826.56 | 11-FEB-17:03 | -1.2 | -2.7 | 0.275344E+09 | 406.79 | 28-FEB-10:39 | -25.4 | -25.7 |
March | 0.228900E+09 | 1110.17 | 22-MAR-16:00 | 5.60 | 2.61 | 0.335274E+09 | 468.38 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.138214E+10 | 2593.20 | 28-APR-15:20 | 12.20 | 4.90 | 0.347085E+09 | 549.49 | 24-APR-13:20 | 12.20 | 4.90 |
May | 0.348658E+10 | 8833.07 | 31-MAY-05:12 | 12.43 | 7.84 | 0.434112E+09 | 549.50 | 16-MAY-09:20 | 12.43 | 7.84 |
June | 0.545720E+10 | 9340.16 | 19-JUN-05:12 | 8.73 | 7.50 | 0.436351E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.506842E+10 | 9404.39 | 11-JUL-05:12 | 15.37 | 12.05 | 0.405680E+09 | 549.56 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.376367E+10 | 7853.55 | 02-AUG-06:01 | 11.28 | 10.30 | 0.451583E+09 | 549.50 | 18-AUG-13:20 | 13.33 | 12.00 |
September | 0.163617E+10 | 2744.08 | 01-SEP-13:40 | 14.63 | 10.60 | 0.365658E+09 | 549.50 | 01-SEP-09:20 | 14.63 | 10.60 |
October | 0.465456E+09 | 1230.52 | 04-OCT-15:50 | 10.18 | 4.62 | 0.317013E+09 | 504.78 | 06-OCT-13:00 | 10.60 | 4.48 |
November | 5911765.33 | 821.05 | 04-NOV-16:02 | -9.6 | -11.3 | 0.300777E+09 | 406.80 | 17-NOV-10:30 | -25.0 | -25.3 |
December | 8826577.63 | 819.77 | 23-DEC-17:02 | -2.6 | -3.4 | 0.292346E+09 | 406.91 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.215289E+11 | 0.426346E+10 | ||||||||
Minimum of Months | 5911765.33 | 819.77 | -9.6 | -11.3 | 0.275344E+09 | 406.79 | -25.4 | -25.7 | ||
Maximum of Months | 0.545720E+10 | 9404.39 | 15.37 | 12.05 | 0.451583E+09 | 549.56 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6087441.81 | 517.03 | 21-JAN-17:02 | -5.5 | -5.8 | 0.141007E+09 | 250.80 | 10-JAN-16:00 | -5.5 | -5.8 |
February | 42885390.75 | 677.69 | 15-FEB-11:10 | -14.9 | -15.2 | 0.128787E+09 | 287.77 | 15-FEB-11:09 | -14.9 | -15.2 |
March | 0.432316E+09 | 7493.04 | 31-MAR-12:01 | -12.6 | -14.4 | 0.170147E+09 | 356.46 | 31-MAR-12:09 | -12.6 | -14.4 |
April | 0.177402E+10 | 7813.69 | 28-APR-12:01 | 9.27 | 4.21 | 0.175951E+09 | 356.46 | 28-APR-10:09 | 9.27 | 4.21 |
May | 0.480631E+10 | 14136.17 | 21-MAY-08:52 | 12.20 | 5.72 | 0.205173E+09 | 356.46 | 19-MAY-14:09 | 12.20 | 5.72 |
June | 0.545221E+10 | 14461.13 | 04-JUN-09:22 | 16.70 | 11.16 | 0.205026E+09 | 356.46 | 13-JUN-12:09 | 22.98 | 13.18 |
July | 0.534609E+10 | 14542.12 | 09-JUL-07:42 | 15.92 | 12.35 | 0.191421E+09 | 356.47 | 20-JUL-12:09 | 25.10 | 14.82 |
August | 0.419241E+10 | 10955.46 | 25-AUG-06:01 | 7.98 | 7.08 | 0.213034E+09 | 356.47 | 24-AUG-12:09 | 7.98 | 7.08 |
September | 0.152796E+10 | 11811.02 | 10-SEP-09:53 | 12.80 | 7.13 | 0.179489E+09 | 356.46 | 01-SEP-10:09 | 12.80 | 7.13 |
October | 0.355288E+09 | 6310.95 | 03-OCT-12:01 | 8.17 | 5.20 | 0.154406E+09 | 356.46 | 05-OCT-12:09 | 8.17 | 4.19 |
November | 5025558.66 | 516.77 | 04-NOV-16:02 | -9.6 | -11.3 | 0.139954E+09 | 250.77 | 27-NOV-16:49 | -25.0 | -25.2 |
December | 6146129.96 | 515.81 | 23-DEC-17:02 | -2.6 | -3.4 | 0.136176E+09 | 250.78 | 12-DEC-13:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.239467E+11 | 0.204057E+10 | ||||||||
Minimum of Months | 5025558.66 | 515.81 | -14.9 | -15.2 | 0.128787E+09 | 250.77 | -25.0 | -25.2 | ||
Maximum of Months | 0.545221E+10 | 14542.12 | 16.70 | 12.35 | 0.213034E+09 | 356.47 | 25.10 | 14.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65760658.97 | 1142.08 | 25-JAN-13:30 | -19.8 | -20.0 | 0.305620E+09 | 477.91 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.466958E+09 | 4776.41 | 15-FEB-13:40 | -8.7 | -9.6 | 0.294139E+09 | 549.50 | 13-FEB-14:20 | -8.7 | -9.6 |
March | 0.197833E+10 | 9240.13 | 31-MAR-13:30 | -11.4 | -13.3 | 0.384873E+09 | 549.50 | 01-MAR-14:20 | -11.4 | -13.3 |
April | 0.498654E+10 | 18060.67 | 23-APR-11:43 | 10.00 | 3.76 | 0.376704E+09 | 550.46 | 21-APR-13:20 | 10.00 | 3.76 |
May | 0.695158E+10 | 20988.26 | 21-MAY-13:32 | 15.20 | 7.14 | 0.434262E+09 | 550.72 | 30-MAY-13:20 | 17.80 | 9.05 |
June | 0.790899E+10 | 21885.39 | 04-JUN-14:42 | 19.32 | 11.73 | 0.436116E+09 | 549.68 | 16-JUN-13:50 | 19.40 | 10.55 |
July | 0.777949E+10 | 22038.79 | 23-JUL-13:12 | 25.00 | 15.26 | 0.405729E+09 | 550.94 | 20-JUL-13:20 | 25.00 | 15.26 |
August | 0.748695E+10 | 21347.37 | 27-AUG-13:32 | 18.87 | 14.02 | 0.453290E+09 | 550.86 | 24-AUG-13:20 | 18.87 | 14.02 |
September | 0.389505E+10 | 19305.37 | 10-SEP-11:13 | 14.80 | 7.99 | 0.382881E+09 | 549.77 | 07-SEP-09:30 | 14.80 | 7.99 |
October | 0.133131E+10 | 10068.08 | 03-OCT-13:30 | 10.85 | 6.24 | 0.345117E+09 | 549.49 | 30-OCT-13:20 | -11.8 | -12.9 |
November | 0.142496E+09 | 2861.31 | 08-NOV-13:30 | -13.6 | -14.4 | 0.306439E+09 | 549.49 | 08-NOV-14:20 | -13.5 | -14.2 |
December | 9916408.72 | 820.15 | 23-DEC-17:02 | -2.6 | -3.4 | 0.293915E+09 | 406.84 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.430034E+11 | 0.441909E+10 | ||||||||
Minimum of Months | 9916408.72 | 820.15 | -19.8 | -20.0 | 0.293915E+09 | 406.84 | -18.9 | -19.2 | ||
Maximum of Months | 0.790899E+10 | 22038.79 | 25.00 | 15.26 | 0.453290E+09 | 550.94 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5741748.53 | 516.28 | 21-JAN-17:02 | -5.5 | -5.8 | 0.192662E+09 | 257.55 | 13-JAN-14:30 | -5.5 | -5.8 |
February | 31778357.87 | 615.33 | 09-FEB-15:10 | 0.10 | -1.0 | 0.175369E+09 | 272.36 | 09-FEB-14:00 | 0.10 | -1.0 |
March | 0.290122E+09 | 1504.36 | 31-MAR-16:00 | -9.4 | -11.8 | 0.217112E+09 | 338.67 | 22-MAR-15:00 | -9.4 | -11.8 |
April | 0.191690E+10 | 8974.56 | 22-APR-17:08 | 14.13 | 6.18 | 0.226646E+09 | 347.85 | 14-APR-13:20 | 14.13 | 6.18 |
May | 0.329705E+10 | 12290.28 | 29-MAY-16:33 | 13.30 | 7.99 | 0.274280E+09 | 347.86 | 16-MAY-09:20 | 13.30 | 7.99 |
June | 0.463685E+10 | 14997.35 | 11-JUN-16:41 | 18.90 | 11.02 | 0.276147E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.413775E+10 | 12128.15 | 30-JUL-15:42 | 17.30 | 11.77 | 0.256728E+09 | 347.89 | 19-JUL-09:09 | 17.30 | 11.77 |
August | 0.340724E+10 | 14040.78 | 27-AUG-16:12 | 20.77 | 12.71 | 0.285985E+09 | 347.85 | 21-AUG-09:20 | 20.77 | 12.71 |
September | 0.140660E+10 | 6946.32 | 02-SEP-17:43 | 16.70 | 10.38 | 0.234171E+09 | 347.86 | 01-SEP-09:20 | 16.70 | 10.38 |
October | 0.333926E+09 | 1434.07 | 03-OCT-15:00 | 12.80 | 6.92 | 0.203209E+09 | 338.67 | 03-OCT-15:50 | 11.88 | 6.46 |
November | 7094175.90 | 577.90 | 08-NOV-15:40 | -15.4 | -15.8 | 0.191181E+09 | 258.47 | 08-NOV-15:50 | -15.7 | -16.1 |
December | 6074621.70 | 515.51 | 23-DEC-17:02 | -2.6 | -3.4 | 0.186010E+09 | 257.58 | 12-DEC-14:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.194771E+11 | 0.271950E+10 | ||||||||
Minimum of Months | 5741748.53 | 515.51 | -15.4 | -15.8 | 0.175369E+09 | 257.55 | -15.7 | -16.1 | ||
Maximum of Months | 0.463685E+10 | 14997.35 | 20.77 | 12.71 | 0.285985E+09 | 347.89 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558019E+09 | 11876.36 | 02-JAN-05:01 | -15.6 |
February | 53100373.49 | 7605.11 | 27-FEB-06:03 | -35.9 |
March | 3217747.51 | 6255.21 | 01-MAR-07:01 | -28.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 25333550.42 | 7478.72 | 27-NOV-06:03 | -26.7 |
December | 78352362.17 | 7779.41 | 11-DEC-06:03 | -18.3 |
Annual Sum or Average | 0.718023E+09 | |||
Minimum of Months | 0.00 | 0.00 | -35.9 | |
Maximum of Months | 0.558019E+09 | 11876.36 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123208E+11 | 17879.86 | 12-JAN-06:13 | -38.3 |
February | 0.893196E+10 | 17728.67 | 27-FEB-05:10 | -36.1 |
March | 0.614862E+10 | 17802.01 | 01-MAR-06:09 | -28.4 |
April | 0.191922E+10 | 15796.33 | 03-APR-05:06 | -21.2 |
May | 0.438552E+09 | 5876.70 | 21-MAY-07:22 | 8.05 |
June | 0.100824E+09 | 6099.19 | 07-JUN-05:12 | 7.40 |
July | 0.113653E+09 | 5976.99 | 06-JUL-05:12 | 9.23 |
August | 0.356386E+09 | 3694.21 | 31-AUG-07:35 | 1.27 |
September | 0.128963E+10 | 7855.92 | 28-SEP-06:01 | -2.8 |
October | 0.458570E+10 | 14777.57 | 31-OCT-05:13 | -18.1 |
November | 0.110606E+11 | 18049.69 | 29-NOV-06:09 | -28.9 |
December | 0.130770E+11 | 17968.64 | 06-DEC-06:10 | -28.7 |
Annual Sum or Average | 0.603429E+11 | |||
Minimum of Months | 0.100824E+09 | 3694.21 | -38.3 | |
Maximum of Months | 0.130770E+11 | 18049.69 | 9.23 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489419E+10 | 10974.96 | 02-JAN-08:45 | -15.4 |
February | 0.338624E+10 | 10399.36 | 21-FEB-08:10 | -22.8 |
March | 0.254886E+10 | 8222.84 | 06-MAR-07:25 | -20.6 |
April | 0.916606E+09 | 6248.18 | 09-APR-13:33 | 2.03 |
May | 70981978.73 | 6246.85 | 28-MAY-13:32 | 13.70 |
June | 33815553.23 | 4347.92 | 04-JUN-14:42 | 19.32 |
July | 36190314.73 | 4676.45 | 23-JUL-11:12 | 23.17 |
August | 33169552.61 | 4931.13 | 27-AUG-16:12 | 20.77 |
September | 0.477200E+09 | 6735.26 | 10-SEP-11:13 | 14.80 |
October | 0.192577E+10 | 8633.03 | 30-OCT-06:25 | -15.3 |
November | 0.399708E+10 | 10592.43 | 13-NOV-08:07 | -16.6 |
December | 0.479860E+10 | 10477.81 | 04-DEC-08:23 | -20.2 |
Annual Sum or Average | 0.231187E+11 | |||
Minimum of Months | 33169552.61 | 4347.92 | -22.8 | |
Maximum of Months | 0.489419E+10 | 10974.96 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375100E+10 | 8383.13 | 02-JAN-08:40 | -15.2 |
February | 0.262558E+10 | 5707.55 | 21-FEB-07:01 | -23.2 |
March | 0.180209E+10 | 4205.56 | 06-MAR-07:01 | -20.9 |
April | 0.467660E+09 | 5032.54 | 24-APR-05:03 | -3.4 |
May | 33059558.42 | 3233.28 | 27-MAY-05:03 | 0.10 |
June | 26515615.48 | 3177.95 | 16-JUN-05:12 | 9.60 |
July | 32763804.98 | 4126.61 | 06-JUL-05:12 | 9.23 |
August | 31394927.82 | 3806.09 | 31-AUG-05:03 | -1.2 |
September | 0.205821E+09 | 4941.46 | 07-SEP-05:03 | 1.78 |
October | 0.135603E+10 | 3603.25 | 30-OCT-11:01 | -15.6 |
November | 0.276323E+10 | 6015.55 | 13-NOV-07:01 | -17.1 |
December | 0.337000E+10 | 6203.10 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.164651E+11 | |||
Minimum of Months | 26515615.48 | 3177.95 | -23.2 | |
Maximum of Months | 0.375100E+10 | 8383.13 | 9.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309372E+10 | 19030.02 | 02-JAN-05:01 | -15.6 |
February | 0.148624E+10 | 17871.49 | 21-FEB-05:01 | -22.9 |
March | 0.296420E+09 | 15882.22 | 06-MAR-06:02 | -21.1 |
April | 13844541.57 | 13779.55 | 03-APR-06:01 | -21.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 0.191346E+09 | 15881.10 | 30-OCT-05:01 | -14.5 |
November | 0.181538E+10 | 17951.86 | 13-NOV-05:01 | -20.2 |
December | 0.287644E+10 | 17988.41 | 04-DEC-05:11 | -19.8 |
Annual Sum or Average | 0.977340E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.309372E+10 | 19030.02 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.953141E+10 | 26297.03 | 01-JAN-22:42 | -15.0 |
February | 0.581207E+10 | 26035.22 | 21-FEB-04:42 | -22.8 |
March | 0.268475E+10 | 25260.23 | 06-MAR-05:01 | -20.2 |
April | 0.374386E+09 | 23570.14 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 41928796.99 | 20099.34 | 28-SEP-06:01 | -2.8 |
October | 0.191176E+10 | 25275.64 | 30-OCT-04:01 | -14.4 |
November | 0.757946E+10 | 26091.18 | 27-NOV-04:22 | -25.9 |
December | 0.951639E+10 | 25976.46 | 04-DEC-04:32 | -20.0 |
Annual Sum or Average | 0.374522E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.953141E+10 | 26297.03 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101431E+11 | 10053.97 | 01-JAN-19:22 | -14.4 |
February | 0.750225E+10 | 10091.00 | 21-FEB-02:62 | -23.8 |
March | 0.478989E+10 | 9729.95 | 06-MAR-04:23 | -20.0 |
April | 0.907446E+09 | 9441.38 | 03-APR-03:43 | -21.1 |
May | 200127.96 | 667.09 | 27-MAY-06:05 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 2449830.13 | 7320.93 | 31-AUG-06:02 | -1.5 |
September | 0.263980E+09 | 8271.83 | 25-SEP-05:01 | -1.2 |
October | 0.339465E+10 | 9684.40 | 30-OCT-03:23 | -13.9 |
November | 0.891808E+10 | 10073.11 | 27-NOV-04:22 | -25.9 |
December | 0.104030E+11 | 10054.02 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.463250E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.104030E+11 | 10091.00 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675197E+10 | 9502.77 | 29-JAN-01:02 | -25.1 |
February | 0.442957E+10 | 9526.90 | 21-FEB-02:62 | -23.8 |
March | 0.208008E+10 | 9052.52 | 06-MAR-04:23 | -20.0 |
April | 0.373804E+09 | 8503.32 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1173394.17 | 5841.68 | 31-AUG-06:02 | -1.5 |
September | 0.113972E+09 | 7329.05 | 30-SEP-05:01 | -4.5 |
October | 0.185023E+10 | 9002.87 | 30-OCT-03:23 | -13.9 |
November | 0.586390E+10 | 9574.96 | 13-NOV-05:11 | -19.8 |
December | 0.702396E+10 | 9506.97 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.284887E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.1 | |
Maximum of Months | 0.702396E+10 | 9574.96 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.931212E+10 | 14635.40 | 01-JAN-19:22 | -14.4 |
February | 0.532491E+10 | 14598.30 | 20-FEB-08:42 | -25.0 |
March | 0.268055E+10 | 13922.16 | 06-MAR-04:23 | -20.0 |
April | 0.524900E+09 | 13100.11 | 03-APR-04:01 | -21.1 |
May | 444128.45 | 1480.43 | 27-MAY-06:05 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 973135.82 | 4674.20 | 30-AUG-06:02 | 0.10 |
September | 0.153846E+09 | 11173.07 | 25-SEP-05:01 | -1.2 |
October | 0.230719E+10 | 13858.16 | 30-OCT-03:23 | -13.9 |
November | 0.751317E+10 | 14735.86 | 13-NOV-05:11 | -19.8 |
December | 0.102392E+11 | 14654.25 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.380573E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.0 | |
Maximum of Months | 0.102392E+11 | 14735.86 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.683750E+10 | 9647.23 | 29-JAN-19:42 | -22.7 |
February | 0.480822E+10 | 9678.01 | 21-FEB-02:62 | -23.8 |
March | 0.279003E+10 | 9199.81 | 06-MAR-04:23 | -20.0 |
April | 0.465434E+09 | 8599.90 | 03-APR-04:01 | -21.1 |
May | 533057.20 | 1485.70 | 27-MAY-06:05 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1069716.92 | 4286.24 | 31-AUG-06:02 | -1.5 |
September | 0.154483E+09 | 7429.31 | 30-SEP-05:01 | -4.5 |
October | 0.214737E+10 | 9147.06 | 30-OCT-03:23 | -13.9 |
November | 0.585763E+10 | 9724.15 | 13-NOV-05:11 | -19.8 |
December | 0.703933E+10 | 9653.57 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.301016E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.8 | |
Maximum of Months | 0.703933E+10 | 9724.15 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794061E+10 | 7896.29 | 01-JAN-19:22 | -14.4 |
February | 0.623667E+10 | 7795.48 | 21-FEB-02:62 | -23.8 |
March | 0.435769E+10 | 7513.51 | 06-MAR-05:01 | -20.2 |
April | 0.690372E+09 | 7319.82 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 15856579.08 | 5961.98 | 28-SEP-06:01 | -2.8 |
October | 0.128502E+10 | 7198.24 | 30-OCT-04:01 | -14.4 |
November | 0.552239E+10 | 7652.90 | 13-NOV-05:11 | -19.8 |
December | 0.741592E+10 | 7638.49 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.334645E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.8 | |
Maximum of Months | 0.794061E+10 | 7896.29 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553698E+10 | 7560.23 | 01-JAN-19:22 | -14.4 |
February | 0.378713E+10 | 7391.36 | 27-FEB-00:12 | -30.6 |
March | 0.161858E+10 | 7083.88 | 06-MAR-05:01 | -20.2 |
April | 0.185242E+09 | 6477.93 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 5565729.27 | 5095.96 | 28-SEP-06:01 | -2.8 |
October | 0.634665E+09 | 6729.88 | 30-OCT-04:01 | -14.4 |
November | 0.372860E+10 | 7313.50 | 13-NOV-05:11 | -19.8 |
December | 0.523001E+10 | 7256.33 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.207268E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.553698E+10 | 7560.23 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134880E+11 | 17653.05 | 12-JAN-07:10 | -38.3 |
February | 0.929762E+10 | 18468.80 | 27-FEB-07:10 | -34.9 |
March | 0.669450E+10 | 16425.00 | 01-MAR-07:11 | -28.7 |
April | 0.183682E+10 | 14593.58 | 03-APR-06:10 | -21.5 |
May | 0.550967E+09 | 8382.56 | 04-MAY-06:10 | 4.18 |
June | 0.117214E+09 | 7616.60 | 02-JUN-06:08 | 7.15 |
July | 82289884.46 | 7610.77 | 05-JUL-06:07 | 8.30 |
August | 0.250078E+09 | 8913.91 | 31-AUG-06:10 | -1.5 |
September | 0.108060E+10 | 10338.39 | 29-SEP-07:00 | -5.6 |
October | 0.423061E+10 | 14249.31 | 31-OCT-07:00 | -19.4 |
November | 0.108714E+11 | 16262.65 | 29-NOV-08:00 | -28.9 |
December | 0.135252E+11 | 17068.11 | 15-DEC-17:10 | -29.9 |
Annual Sum or Average | 0.620254E+11 | |||
Minimum of Months | 82289884.46 | 7610.77 | -38.3 | |
Maximum of Months | 0.135252E+11 | 18468.80 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562400E+10 | 7718.01 | 01-JAN-20:02 | -14.5 |
February | 0.415505E+10 | 7568.82 | 21-FEB-02:62 | -23.8 |
March | 0.239320E+10 | 7260.22 | 06-MAR-05:01 | -20.2 |
April | 0.205684E+09 | 6104.41 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 8714246.61 | 5184.43 | 28-SEP-06:01 | -2.8 |
October | 0.806798E+09 | 6904.50 | 30-OCT-04:01 | -14.4 |
November | 0.372755E+10 | 7461.82 | 13-NOV-05:11 | -19.8 |
December | 0.524649E+10 | 7400.45 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.221675E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.8 | |
Maximum of Months | 0.562400E+10 | 7718.01 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673993E+10 | 8267.29 | 01-JAN-19:22 | -14.4 |
February | 0.446373E+10 | 8118.77 | 27-FEB-00:12 | -30.6 |
March | 0.242328E+10 | 7837.12 | 06-MAR-05:01 | -20.2 |
April | 0.282481E+09 | 7525.09 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 25887330.05 | 6154.09 | 28-SEP-06:01 | -2.8 |
October | 0.142527E+10 | 7788.48 | 30-OCT-04:11 | -14.4 |
November | 0.534784E+10 | 8123.45 | 27-NOV-04:22 | -25.9 |
December | 0.676785E+10 | 8122.16 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.274763E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.676785E+10 | 8267.29 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448256E+10 | 8158.57 | 01-JAN-19:22 | -14.4 |
February | 0.254906E+10 | 7954.71 | 27-FEB-00:12 | -30.6 |
March | 0.969578E+09 | 7632.24 | 01-MAR-05:01 | -28.3 |
April | 0.109455E+09 | 7029.93 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14780654.88 | 5273.40 | 28-SEP-06:01 | -2.8 |
October | 0.773698E+09 | 7556.66 | 30-OCT-04:11 | -14.4 |
November | 0.351576E+10 | 7980.73 | 27-NOV-04:22 | -25.9 |
December | 0.458732E+10 | 7974.96 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.170022E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.458732E+10 | 8158.57 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594531E+10 | 12227.47 | 01-JAN-19:22 | -14.4 |
February | 0.286455E+10 | 11778.70 | 26-FEB-08:52 | -26.7 |
March | 0.113424E+10 | 11390.13 | 06-MAR-05:01 | -20.2 |
April | 0.134216E+09 | 9553.05 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 16851634.35 | 7962.18 | 28-SEP-06:01 | -2.8 |
October | 0.860836E+09 | 11311.97 | 30-OCT-04:11 | -14.4 |
November | 0.421323E+10 | 11935.01 | 27-NOV-04:22 | -25.9 |
December | 0.653545E+10 | 11949.56 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.217047E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.653545E+10 | 12227.47 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455860E+10 | 8090.64 | 01-JAN-19:22 | -14.4 |
February | 0.282979E+10 | 7872.92 | 27-FEB-00:12 | -30.6 |
March | 0.135182E+10 | 7571.46 | 06-MAR-05:01 | -20.2 |
April | 0.131953E+09 | 6663.68 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 17660713.04 | 5244.19 | 28-SEP-06:01 | -2.8 |
October | 0.906262E+09 | 7503.54 | 30-OCT-04:11 | -14.4 |
November | 0.350718E+10 | 7920.05 | 27-NOV-04:22 | -25.9 |
December | 0.460396E+10 | 7908.44 | 03-DEC-23:52 | -22.2 |
Annual Sum or Average | 0.179072E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.460396E+10 | 8090.64 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910813E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.680428E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.633234E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.492170E+09 | 577.90 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516884E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.506059E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478662E+09 | 525.87 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.548034E+09 | 543.08 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.535883E+09 | 987.44 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.670391E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.845374E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.924150E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.774208E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478662E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.924150E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557671E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.415364E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.395043E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.312187E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.332290E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324553E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306994E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349967E+09 | 344.78 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336864E+09 | 556.95 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.412701E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511112E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578924E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.483367E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306994E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578924E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849388E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.628688E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.614060E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.494622E+09 | 577.69 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522879E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511570E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483491E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.550493E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527227E+09 | 944.98 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.634941E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.767295E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.890487E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.747514E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483491E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.890487E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562383E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.410074E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.393653E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313505E+09 | 461.13 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326402E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320180E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302630E+09 | 342.36 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345518E+09 | 342.48 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336094E+09 | 626.76 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.410152E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511505E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.581462E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.481356E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302630E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.581462E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.907302E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.676747E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.631134E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.491556E+09 | 574.88 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516572E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.505820E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478297E+09 | 496.34 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.547616E+09 | 538.56 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.534147E+09 | 984.55 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.665711E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.840735E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.923077E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.771871E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478297E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.923077E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.556024E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.413902E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.394173E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.311854E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.331981E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324263E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306711E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349587E+09 | 342.17 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336274E+09 | 550.48 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.411655E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.508745E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578044E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.482321E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306711E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578044E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.846435E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.626031E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.613256E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.493993E+09 | 574.65 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522453E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511185E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483067E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.549922E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526299E+09 | 939.38 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.633149E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.764577E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.886612E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.745698E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483067E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.886612E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.560598E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.407554E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.392707E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313042E+09 | 455.12 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326237E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320067E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302327E+09 | 339.76 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345145E+09 | 339.88 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335154E+09 | 625.23 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.408797E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.508965E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.580746E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.480134E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302327E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.580746E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910811E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.680425E+09 | 1040.56 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.633233E+09 | 1040.56 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.492169E+09 | 577.90 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.516883E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.506058E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.478662E+09 | 525.86 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.548033E+09 | 543.07 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.535881E+09 | 987.44 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.670387E+09 | 1040.56 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.845370E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.924149E+09 | 1040.56 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.774206E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.478662E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.924149E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.557670E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.415352E+09 | 658.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.395043E+09 | 658.76 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.312187E+09 | 314.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.332290E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.324552E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.306994E+09 | 314.23 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.349966E+09 | 344.77 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336863E+09 | 556.96 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.412700E+09 | 658.76 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511110E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.578924E+09 | 658.76 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.483365E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.306994E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.578924E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849387E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.628688E+09 | 1040.56 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.614059E+09 | 1040.56 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.494621E+09 | 577.68 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.522879E+09 | 496.34 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.511570E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.483488E+09 | 496.34 | 03-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.550493E+09 | 496.34 | 01-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527226E+09 | 944.99 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.634940E+09 | 1040.56 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.767295E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.890488E+09 | 1040.56 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.747513E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.483488E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.890488E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562381E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.410073E+09 | 658.71 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.393653E+09 | 658.71 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.313505E+09 | 461.11 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.326402E+09 | 314.21 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.320180E+09 | 314.21 | 01-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.302628E+09 | 342.35 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.345518E+09 | 342.48 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.336093E+09 | 626.76 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.410151E+09 | 658.71 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.511503E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.581462E+09 | 658.71 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.481355E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.302628E+09 | 314.21 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.581462E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.910813E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424291E+09 |
February | 0.901968E+09 | 0.680428E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340863E+09 |
March | 0.107774E+10 | 0.633234E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502217E+09 |
April | 0.956342E+09 | 0.492170E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566787E+09 |
May | 0.103597E+10 | 0.516884E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351702E+09 |
June | 0.103308E+10 | 0.506059E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453545.60 | 0.212144E+09 |
July | 0.959235E+09 | 0.478662E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401039.74 | 0.157235E+09 |
August | 0.107774E+10 | 0.548034E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206567.31 | 0.182011E+09 |
September | 0.956342E+09 | 0.535883E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206840E+09 |
October | 0.994195E+09 | 0.670391E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431576E+09 |
November | 0.984487E+09 | 0.845374E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155875E+09 |
December | 0.959235E+09 | 0.924150E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307607E+09 |
Annual Sum or Average | 0.119305E+11 | 0.774208E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2061152.65 | 0.383915E+10 |
Minimum of Months | 0.901968E+09 | 0.478662E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155875E+09 |
Maximum of Months | 0.107774E+10 | 0.924150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401039.74 | 0.566787E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.557671E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283085E+09 |
February | 0.571020E+09 | 0.415364E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227456E+09 |
March | 0.682301E+09 | 0.395043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338506E+09 |
April | 0.605444E+09 | 0.312187E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389768E+09 |
May | 0.655854E+09 | 0.332290E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241861E+09 |
June | 0.654023E+09 | 0.324553E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302369.22 | 0.143358E+09 |
July | 0.607275E+09 | 0.306994E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869935.85 | 0.106946E+09 |
August | 0.682301E+09 | 0.349967E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137714.70 | 0.124237E+09 |
September | 0.605444E+09 | 0.336864E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143035E+09 |
October | 0.629407E+09 | 0.412701E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289952E+09 |
November | 0.623262E+09 | 0.511112E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103898E+09 |
December | 0.607275E+09 | 0.578924E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205140E+09 |
Annual Sum or Average | 0.755301E+10 | 0.483367E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1310019.76 | 0.259724E+10 |
Minimum of Months | 0.571020E+09 | 0.306994E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103898E+09 |
Maximum of Months | 0.682301E+09 | 0.578924E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869935.85 | 0.389768E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.849388E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425334E+09 |
February | 0.901968E+09 | 0.628688E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343941E+09 |
March | 0.107774E+10 | 0.614060E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519457E+09 |
April | 0.956342E+09 | 0.494622E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606664E+09 |
May | 0.103597E+10 | 0.522879E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364967E+09 |
June | 0.103308E+10 | 0.511570E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453530.05 | 0.214545E+09 |
July | 0.959235E+09 | 0.483491E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198614.24 | 0.161011E+09 |
August | 0.107774E+10 | 0.550493E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 206297.44 | 0.189965E+09 |
September | 0.956342E+09 | 0.527227E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219070E+09 |
October | 0.994195E+09 | 0.634941E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443242E+09 |
November | 0.984487E+09 | 0.767295E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156336E+09 |
December | 0.959235E+09 | 0.890487E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308086E+09 |
Annual Sum or Average | 0.119305E+11 | 0.747514E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1858441.73 | 0.395262E+10 |
Minimum of Months | 0.901968E+09 | 0.483491E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156336E+09 |
Maximum of Months | 0.107774E+10 | 0.890487E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1198614.24 | 0.606664E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.562383E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283083E+09 |
February | 0.570983E+09 | 0.410074E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227410E+09 |
March | 0.682256E+09 | 0.393653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337616E+09 |
April | 0.605404E+09 | 0.313505E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398213E+09 |
May | 0.655811E+09 | 0.326402E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243995E+09 |
June | 0.653980E+09 | 0.320180E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 302372.02 | 0.144338E+09 |
July | 0.607235E+09 | 0.302630E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 765630.67 | 0.108317E+09 |
August | 0.682256E+09 | 0.345518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137716.71 | 0.125502E+09 |
September | 0.605404E+09 | 0.336094E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141564E+09 |
October | 0.629366E+09 | 0.410152E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288668E+09 |
November | 0.623221E+09 | 0.511505E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103930E+09 |
December | 0.607235E+09 | 0.581462E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205140E+09 |
Annual Sum or Average | 0.755252E+10 | 0.481356E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1205719.40 | 0.260778E+10 |
Minimum of Months | 0.570983E+09 | 0.302630E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103930E+09 |
Maximum of Months | 0.682256E+09 | 0.581462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 765630.67 | 0.398213E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.907302E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227300E+09 |
February | 0.901968E+09 | 0.676747E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182293E+09 |
March | 0.107774E+10 | 0.631134E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271371E+09 |
April | 0.956342E+09 | 0.491556E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302688E+09 |
May | 0.103597E+10 | 0.516572E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182886E+09 |
June | 0.103308E+10 | 0.505820E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249891.43 | 0.110276E+09 |
July | 0.959235E+09 | 0.478297E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 874882.13 | 82193976.67 |
August | 0.107774E+10 | 0.547616E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 116948.45 | 99200820.03 |
September | 0.956342E+09 | 0.534147E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117430E+09 |
October | 0.994195E+09 | 0.665711E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245250E+09 |
November | 0.984487E+09 | 0.840735E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85304636.74 |
December | 0.959235E+09 | 0.923077E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166045E+09 |
Annual Sum or Average | 0.119305E+11 | 0.771871E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1241722.01 | 0.207224E+10 |
Minimum of Months | 0.901968E+09 | 0.478297E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82193976.67 |
Maximum of Months | 0.107774E+10 | 0.923077E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 874882.13 | 0.302688E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.556024E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151625E+09 |
February | 0.571020E+09 | 0.413902E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121802E+09 |
March | 0.682301E+09 | 0.394173E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183777E+09 |
April | 0.605444E+09 | 0.311854E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212924E+09 |
May | 0.655854E+09 | 0.331981E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130950E+09 |
June | 0.654023E+09 | 0.324263E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166595.14 | 76458445.27 |
July | 0.607275E+09 | 0.306711E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 494953.16 | 57779909.44 |
August | 0.682301E+09 | 0.349587E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77965.50 | 68929968.25 |
September | 0.605444E+09 | 0.336274E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82381926.60 |
October | 0.629407E+09 | 0.411655E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166329E+09 |
November | 0.623262E+09 | 0.508745E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56737948.25 |
December | 0.607275E+09 | 0.578044E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110542E+09 |
Annual Sum or Average | 0.755301E+10 | 0.482321E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 739513.80 | 0.142024E+10 |
Minimum of Months | 0.571020E+09 | 0.306711E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56737948.25 |
Maximum of Months | 0.682301E+09 | 0.578044E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 494953.16 | 0.212924E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.846435E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989558E+10 |
February | 0.901968E+09 | 0.626031E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785035E+10 |
March | 0.107774E+10 | 0.613256E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875401E+10 |
April | 0.956342E+09 | 0.493993E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503889E+10 |
May | 0.103597E+10 | 0.522453E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307424E+10 |
June | 0.103308E+10 | 0.511185E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28762199.75 | 0.180044E+10 |
July | 0.959235E+09 | 0.483067E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42370241.21 | 0.136835E+10 |
August | 0.107774E+10 | 0.549922E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9957763.21 | 0.250982E+10 |
September | 0.956342E+09 | 0.526299E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381489E+10 |
October | 0.994195E+09 | 0.633149E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635489E+10 |
November | 0.984487E+09 | 0.764577E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.977513E+10 |
December | 0.959235E+09 | 0.886612E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100236E+11 |
Annual Sum or Average | 0.119305E+11 | 0.745698E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81090204.17 | 0.702601E+11 |
Minimum of Months | 0.901968E+09 | 0.483067E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136835E+10 |
Maximum of Months | 0.107774E+10 | 0.886612E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42370241.21 | 0.100236E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.560598E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151614E+09 |
February | 0.570983E+09 | 0.407554E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121648E+09 |
March | 0.682256E+09 | 0.392707E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182389E+09 |
April | 0.605404E+09 | 0.313042E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217064E+09 |
May | 0.655811E+09 | 0.326237E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129967E+09 |
June | 0.653980E+09 | 0.320067E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166598.86 | 76770673.60 |
July | 0.607235E+09 | 0.302327E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430395.37 | 57609079.23 |
August | 0.682256E+09 | 0.345145E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77967.71 | 69158317.95 |
September | 0.605404E+09 | 0.335154E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81163521.95 |
October | 0.629366E+09 | 0.408797E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164400E+09 |
November | 0.623221E+09 | 0.508965E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56775263.18 |
December | 0.607235E+09 | 0.580746E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110542E+09 |
Annual Sum or Average | 0.755252E+10 | 0.480134E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 674961.95 | 0.141910E+10 |
Minimum of Months | 0.570983E+09 | 0.302327E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56775263.18 |
Maximum of Months | 0.682256E+09 | 0.580746E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 430395.37 | 0.217064E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.910811E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357293E+09 |
February | 0.901968E+09 | 0.680425E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288239E+09 |
March | 0.107774E+10 | 0.633233E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432206E+09 |
April | 0.956342E+09 | 0.492169E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496218E+09 |
May | 0.103597E+10 | 0.516883E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304793E+09 |
June | 0.103308E+10 | 0.506058E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 384373.01 | 0.181779E+09 |
July | 0.959235E+09 | 0.478662E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220631.79 | 0.134093E+09 |
August | 0.107774E+10 | 0.548033E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177484.91 | 0.157747E+09 |
September | 0.956342E+09 | 0.535881E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184347E+09 |
October | 0.994195E+09 | 0.670387E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378279E+09 |
November | 0.984487E+09 | 0.845370E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132269E+09 |
December | 0.959235E+09 | 0.924149E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259820E+09 |
Annual Sum or Average | 0.119305E+11 | 0.774206E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1782489.71 | 0.330708E+10 |
Minimum of Months | 0.901968E+09 | 0.478662E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132269E+09 |
Maximum of Months | 0.107774E+10 | 0.924149E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220631.79 | 0.496218E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.557670E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237859E+09 |
February | 0.421807E+09 | 0.415352E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192119E+09 |
March | 0.502994E+09 | 0.395043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292259E+09 |
April | 0.447140E+09 | 0.312187E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340695E+09 |
May | 0.484071E+09 | 0.332290E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208809E+09 |
June | 0.482240E+09 | 0.324552E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245991.36 | 0.122767E+09 |
July | 0.448971E+09 | 0.306994E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 741783.69 | 91297826.99 |
August | 0.502994E+09 | 0.349966E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118320.23 | 0.107356E+09 |
September | 0.447140E+09 | 0.336863E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126761E+09 |
October | 0.465148E+09 | 0.412700E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254889E+09 |
November | 0.460569E+09 | 0.511110E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87912661.17 |
December | 0.448971E+09 | 0.578924E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172757E+09 |
Annual Sum or Average | 0.557719E+10 | 0.483365E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1106095.28 | 0.223548E+10 |
Minimum of Months | 0.421807E+09 | 0.306994E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87912661.17 |
Maximum of Months | 0.502994E+09 | 0.578924E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 741783.69 | 0.340695E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.849387E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358158E+09 |
February | 0.901968E+09 | 0.628688E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292210E+09 |
March | 0.107774E+10 | 0.614059E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448833E+09 |
April | 0.956342E+09 | 0.494621E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528317E+09 |
May | 0.103597E+10 | 0.522879E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314577E+09 |
June | 0.103308E+10 | 0.511570E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 384348.55 | 0.183384E+09 |
July | 0.959235E+09 | 0.483488E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1044558.41 | 0.137156E+09 |
August | 0.107774E+10 | 0.550493E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176979.19 | 0.163559E+09 |
September | 0.956342E+09 | 0.527226E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193264E+09 |
October | 0.994195E+09 | 0.634940E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390446E+09 |
November | 0.984487E+09 | 0.767295E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133056E+09 |
December | 0.959235E+09 | 0.890488E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260137E+09 |
Annual Sum or Average | 0.119305E+11 | 0.747513E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1605886.14 | 0.340310E+10 |
Minimum of Months | 0.901968E+09 | 0.483488E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133056E+09 |
Maximum of Months | 0.107774E+10 | 0.890488E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1044558.41 | 0.528317E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.562381E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238087E+09 |
February | 0.570983E+09 | 0.410073E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192122E+09 |
March | 0.682256E+09 | 0.393653E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290851E+09 |
April | 0.605404E+09 | 0.313505E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347255E+09 |
May | 0.655811E+09 | 0.326402E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210470E+09 |
June | 0.653980E+09 | 0.320180E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 256255.86 | 0.123459E+09 |
July | 0.607235E+09 | 0.302628E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 649136.01 | 92197564.24 |
August | 0.682256E+09 | 0.345518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118327.65 | 0.108276E+09 |
September | 0.605404E+09 | 0.336093E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125490E+09 |
October | 0.629366E+09 | 0.410151E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253171E+09 |
November | 0.623221E+09 | 0.511503E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88082972.42 |
December | 0.607235E+09 | 0.581462E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172967E+09 |
Annual Sum or Average | 0.755252E+10 | 0.481355E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1023719.52 | 0.224243E+10 |
Minimum of Months | 0.570983E+09 | 0.302628E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88082972.42 |
Maximum of Months | 0.682256E+09 | 0.581462E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 649136.01 | 0.347255E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467806E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381351E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584497E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681729E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408289E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253252.41 | 0.238389E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987300.53 | 0.176609E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55719.53 | 0.213697E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254854E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523110E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177591E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341680E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296272.47 | 0.444960E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176609E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987300.53 | 0.681729E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591776E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482508E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735460E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855339E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519782E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319810.59 | 0.304665E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297287.66 | 0.225235E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73074.74 | 0.270281E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314857E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639268E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222003E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431711E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1690172.98 | 0.559288E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222003E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297287.66 | 0.855339E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619925E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503412E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758827E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.884063E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548892E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216025.62 | 0.328401E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855027.04 | 0.245627E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18979.47 | 0.284702E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319519E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647081E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229031E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451156E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1090032.13 | 0.582064E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229031E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 855027.04 | 0.884063E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1913.23 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1134.15 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 849.57 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 577.90 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1211.09 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 579.88 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30-JUN-15:00 | 561.73 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 525.87 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 21-JUL-16:00 | 427.28 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 543.08 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 11-AUG-16:00 | 448.29 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 987.44 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 347.88 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 703.80 | 21-OCT-04:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 604.82 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 646.46 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.88 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 1913.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1275.52 | 28-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 756.09 | 25-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 566.66 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 807.96 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 388.91 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 30-JUN-15:00 | 374.51 | 24-JUN-21:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 21-JUL-16:00 | 287.09 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 344.78 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 11-AUG-16:00 | 299.02 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 556.95 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 235.38 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.81 | 21-OCT-04:05 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.07 | 09-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 430.64 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.38 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 1275.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1913.31 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1134.13 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 913.20 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 577.69 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1332.60 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 588.68 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30-JUN-15:00 | 562.91 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 21-JUL-16:00 | 436.19 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 11-AUG-16:00 | 451.79 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 944.98 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 355.84 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 708.39 | 21-OCT-04:05 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 605.39 | 09-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 646.69 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.84 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 65.01 | 1913.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1275.55 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 756.09 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 566.78 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 461.13 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 992.66 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 389.26 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 30-JUN-15:00 | 373.75 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 342.36 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 21-JUL-16:00 | 291.12 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 342.48 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 11-AUG-16:00 | 298.98 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 626.76 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 231.44 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 473.90 | 21-OCT-04:05 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 403.17 | 09-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 430.73 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.44 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.34 | 1275.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1010.21 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 602.25 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 451.46 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 574.88 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 649.87 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 312.94 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 30-JUN-15:00 | 311.72 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 21-JUL-16:00 | 224.08 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 538.56 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 | 11-AUG-16:00 | 253.49 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 984.55 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 201.66 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 393.30 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 331.80 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 346.36 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.66 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 | 1010.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 672.49 | 28-JAN-23:55 |
February | 827.22 | 01-FEB-10:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 401.50 | 25-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 301.49 | 14-MAR-21:02 |
April | 827.22 | 03-APR-09:09 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 439.50 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 217.11 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 30-JUN-15:00 | 210.19 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 21-JUL-16:00 | 154.06 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 342.17 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 11-AUG-16:00 | 171.80 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 550.48 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 140.73 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 263.18 | 21-OCT-04:03 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 220.49 | 10-NOV-01:55 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 230.91 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.73 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 672.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 53099.15 | 12-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 48668.88 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 43445.00 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 574.65 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 37809.03 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 15075.18 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.47 | 21-JUN-17:00 | 12271.41 | 01-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.80 | 21-JUL-16:10 | 11879.88 | 17-JUL-06:01 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.89 | 11-AUG-16:20 | 19721.71 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 939.38 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20768.23 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34677.98 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 43525.73 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 48205.02 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11879.88 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3924.80 | 53099.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 672.77 | 28-JAN-23:55 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 401.50 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 301.32 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 455.12 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 519.99 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 210.94 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 | 30-JUN-15:00 | 207.89 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 339.76 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 21-JUL-16:00 | 155.16 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 339.88 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 11-AUG-16:00 | 171.35 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 625.23 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 137.65 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 261.52 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 220.89 | 10-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 230.91 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.65 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 672.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1591.67 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 945.57 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 709.28 | 14-MAR-21:02 |
April | 1306.65 | 03-APR-09:09 | 577.90 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1045.06 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 509.84 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 30-JUN-15:00 | 503.29 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 525.86 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 21-JUL-16:00 | 367.26 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 543.07 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 11-AUG-16:00 | 394.81 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 987.44 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 316.38 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 601.83 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 512.94 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 539.66 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.38 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 1591.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1061.10 | 28-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 658.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 629.26 | 25-FEB-00:55 |
March | 805.43 | 01-MAR-08:09 | 658.76 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 473.22 | 14-MAR-21:02 |
April | 805.43 | 03-APR-07:10 | 314.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 698.39 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 341.63 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 30-JUN-15:00 | 336.05 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 314.23 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 21-JUL-16:00 | 246.80 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 344.77 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 11-AUG-16:00 | 263.18 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 556.96 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 213.68 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 658.76 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 401.00 | 21-OCT-04:03 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.51 | 10-NOV-01:55 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 358.13 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.68 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 1061.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1591.66 | 28-JAN-23:55 |
February | 1306.65 | 01-FEB-10:09 | 1040.56 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 952.00 | 25-FEB-00:55 |
March | 1306.65 | 01-MAR-10:09 | 1040.56 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 798.71 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 577.68 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1143.92 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 516.38 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 30-JUN-15:00 | 498.72 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 496.34 | 03-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 21-JUL-16:00 | 374.87 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 496.34 | 01-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 | 11-AUG-16:00 | 397.16 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 944.99 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 322.92 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 616.27 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 517.50 | 10-NOV-01:55 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 541.04 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.92 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 1591.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1061.11 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 658.71 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 628.45 | 25-FEB-00:55 |
March | 827.17 | 01-MAR-10:09 | 658.71 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 473.22 | 14-MAR-21:02 |
April | 827.17 | 03-APR-09:09 | 461.11 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 849.97 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 314.21 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 341.57 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 314.21 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 30-JUN-15:00 | 330.70 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 342.35 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 21-JUL-16:00 | 250.30 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 342.48 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 11-AUG-16:00 | 262.99 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 626.76 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 210.55 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 400.07 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 341.31 | 10-NOV-01:55 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 358.62 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.55 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 1061.11 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2155.68 | 28-JAN-23:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1285.80 | 25-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 916.02 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1453.34 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 691.37 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.41 | 30-JUN-15:00 | 674.41 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 | 21-JUL-16:00 | 458.98 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 11-AUG-16:00 | 539.47 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 421.51 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 849.80 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 705.94 | 10-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 733.88 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.51 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 | 2155.68 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2709.45 | 28-JAN-23:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1641.28 | 25-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1152.11 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1816.71 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 881.62 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 30-JUN-15:00 | 842.80 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 | 21-JUL-16:00 | 577.77 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 | 11-AUG-16:00 | 683.26 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 504.85 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1045.78 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 889.54 | 10-NOV-01:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 936.10 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.76 | 2709.45 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2774.37 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1706.79 | 25-FEB-00:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1239.89 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1992.15 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 875.93 | 26-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.47 | 30-JUN-15:00 | 856.75 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 21-JUL-16:00 | 666.65 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 11-AUG-16:00 | 668.83 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 542.63 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1037.74 | 21-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 898.21 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 960.44 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 2774.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9582.50 | 11-JAN-17:01 | 19057.92 | 27422.23 | 109850.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7080.52 | 10-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10938.26 | 23-MAR-16:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37688.30 | 24-APR-05:03 | 2541.06 | 846.94 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38654.28 | 15-MAY-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39360.29 | 05-JUN-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40131.24 | 03-JUL-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40211.72 | 14-AUG-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38082.04 | 08-SEP-05:03 | 2541.06 | 846.94 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15582.81 | 05-OCT-16:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7509.95 | 29-NOV-09:20 | 6035.01 | 4936.01 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8631.25 | 15-DEC-11:10 | 6035.01 | 4936.01 | 13987.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7080.52 | 2541.06 | 846.94 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40211.72 | 19057.92 | 27422.23 | 109850.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.30 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.18 |
March | 566.47 | 22-MAR-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 |
April | 3997.40 | 20-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.34 |
May | 6869.55 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
June | 7812.94 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 0.00 |
July | 7915.46 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 0.00 |
August | 6740.21 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
September | 2859.05 | 07-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 |
October | 410.88 | 03-OCT-16:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.13 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.94 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7915.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 549.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3207.14 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2978.59 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.45 |
March | 3363.99 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2089.82 | 07-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.24 |
May | 3536.47 | 31-MAY-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.07 |
June | 5056.55 | 05-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.15 |
July | 6181.04 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.14 |
August | 3806.19 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
September | 2019.69 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 |
October | 1946.06 | 27-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 945.38 |
November | 3194.42 | 30-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3293.08 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1946.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6181.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 1158.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5079.46 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4136.52 | 18-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.84 |
March | 4905.80 | 31-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3420.97 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 |
May | 4258.85 | 22-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 |
June | 5382.84 | 12-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.99 |
July | 6090.95 | 24-JUL-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 |
August | 5549.95 | 28-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 |
September | 3170.23 | 11-SEP-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.62 |
October | 3124.00 | 27-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 |
November | 3768.94 | 30-NOV-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3936.56 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3124.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6090.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4809.76 | 11-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5366.96 | 09-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6029.85 | 23-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12603.85 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27689.37 | 15-MAY-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31622.93 | 05-JUN-06:03 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31665.11 | 24-JUL-06:03 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31294.25 | 14-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12720.72 | 01-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7447.29 | 05-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5123.38 | 30-NOV-17:01 | 19057.92 | 27422.23 | 37824.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5241.92 | 22-DEC-13:01 | 60350.08 | 49360.15 | 68083.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4809.76 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31665.11 | 60350.08 | 49360.15 | 68083.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4025.53 | 20-JAN-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4990.93 | 09-FEB-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5853.65 | 22-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12386.79 | 21-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16467.57 | 31-MAY-15:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26791.75 | 12-JUN-06:01 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29837.10 | 24-JUL-06:03 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16469.57 | 01-AUG-14:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11719.60 | 01-SEP-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6188.13 | 04-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4246.20 | 02-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3993.45 | 23-DEC-17:02 | 1588.16 | 1371.08 | 11347.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 3993.45 | 1588.16 | 1371.08 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29837.10 | 8893.70 | 11517.52 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 872.11 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 |
February | 876.56 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 |
March | 1144.49 | 22-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2352.77 | 28-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 |
May | 9240.61 | 31-MAY-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
June | 10239.82 | 29-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
July | 10448.88 | 11-JUL-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
August | 4720.60 | 02-AUG-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
September | 2330.82 | 01-SEP-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 |
October | 1208.07 | 04-OCT-15:40 | 1272.23 | 553.68 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 |
November | 869.94 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 872.85 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 869.94 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10448.88 | 1272.23 | 553.68 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 510.59 | 21-JAN-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
February | 586.63 | 09-FEB-11:35 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
March | 1911.96 | 22-MAR-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.65 |
April | 5927.14 | 22-APR-09:20 | 261.23 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.31 |
May | 14998.68 | 21-MAY-10:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.95 |
June | 12479.65 | 13-JUN-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 |
July | 16062.09 | 23-JUL-09:41 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.35 |
August | 11450.88 | 10-AUG-06:01 | 1186.95 | 733.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.02 |
September | 5622.78 | 10-SEP-09:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.03 |
October | 1807.47 | 03-OCT-09:50 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 |
November | 509.35 | 04-NOV-16:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 510.92 | 23-DEC-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 509.35 | 211.95 | 87.28 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16062.09 | 1654.44 | 733.21 | 2826.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 991.17 | 25-JAN-13:30 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 |
February | 3881.92 | 15-FEB-13:50 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8104.49 | 31-MAR-13:50 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.31 |
April | 15685.11 | 23-APR-15:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.88 |
May | 24145.17 | 21-MAY-13:21 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.27 |
June | 17878.95 | 11-JUN-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.17 |
July | 25377.78 | 23-JUL-12:21 | 535.68 | 220.59 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
August | 22392.41 | 27-AUG-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.77 |
September | 16758.20 | 10-SEP-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.76 |
October | 9207.85 | 03-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
November | 1745.47 | 08-NOV-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.80 |
December | 804.69 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 804.69 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25377.78 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 509.06 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
February | 573.34 | 09-FEB-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 |
March | 1055.85 | 31-MAR-16:50 | 254.33 | 174.56 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.67 |
April | 8591.62 | 22-APR-17:08 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.80 |
May | 15284.33 | 21-MAY-17:22 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.49 |
June | 14012.88 | 10-JUN-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.52 |
July | 14039.57 | 23-JUL-14:21 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
August | 12269.91 | 27-AUG-17:12 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.18 |
September | 6447.64 | 02-SEP-17:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 |
October | 1021.15 | 03-OCT-15:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.05 |
November | 508.80 | 04-NOV-16:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 509.41 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 508.80 | 0.00 | 52.37 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15284.33 | 805.38 | 314.21 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 821.18 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
February | 820.76 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 |
March | 898.85 | 22-MAR-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1273.88 | 28-APR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 |
May | 3883.97 | 31-MAY-06:02 | 1339.19 | 827.25 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
June | 7695.83 | 29-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
July | 8476.62 | 11-JUL-05:14 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 |
August | 6994.86 | 02-AUG-06:01 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
September | 1906.06 | 01-SEP-13:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 |
October | 1187.74 | 06-OCT-15:00 | 1272.23 | 546.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 |
November | 831.92 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 823.86 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 820.76 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8476.62 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 513.39 | 21-JAN-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
February | 557.29 | 15-FEB-10:40 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 |
March | 1375.02 | 31-MAR-09:25 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
April | 3975.47 | 22-APR-08:30 | 254.35 | 104.74 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.79 |
May | 11050.59 | 14-MAY-09:31 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.65 |
June | 10038.51 | 13-JUN-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
July | 10119.34 | 07-JUL-05:12 | 423.91 | 174.57 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
August | 9311.04 | 25-AUG-06:01 | 1356.51 | 837.95 | 3230.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7856.91 | 10-SEP-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 |
October | 2325.01 | 03-OCT-09:30 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 |
November | 519.99 | 04-NOV-16:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 514.61 | 23-DEC-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 513.39 | 169.56 | 69.83 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11050.59 | 1654.44 | 837.95 | 3230.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 806.89 | 28-JAN-17:01 | 468.72 | 404.65 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.98 |
February | 1080.29 | 18-FEB-13:40 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.24 |
March | 1299.35 | 11-MAR-13:50 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.29 |
April | 9018.29 | 23-APR-14:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.17 |
May | 14816.26 | 14-MAY-12:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 |
June | 12302.18 | 04-JUN-14:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 |
July | 18182.20 | 23-JUL-13:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
August | 18276.49 | 27-AUG-13:41 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 |
September | 14338.75 | 10-SEP-11:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.04 |
October | 5982.29 | 03-OCT-13:40 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.88 |
November | 864.63 | 25-NOV-13:40 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
December | 801.29 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 801.29 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | |
Maximum of Months | 18276.49 | 1306.65 | 496.34 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1437.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 511.60 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
February | 511.95 | 11-FEB-17:03 | 169.55 | 146.38 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.85 |
March | 756.65 | 31-MAR-17:13 | 254.33 | 314.21 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 |
April | 5348.47 | 21-APR-18:20 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 |
May | 7674.89 | 28-MAY-18:42 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
June | 8446.39 | 12-JUN-06:01 | 1186.87 | 733.16 | 2826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 |
July | 7716.65 | 10-JUL-06:02 | 1017.32 | 628.42 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 |
August | 9709.30 | 27-AUG-17:42 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 |
September | 3668.92 | 08-SEP-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
October | 972.34 | 03-OCT-15:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 |
November | 519.41 | 04-NOV-16:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 513.24 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 511.60 | 0.00 | 87.28 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9709.30 | 1186.87 | 733.16 | 2826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 821.16 | 21-JAN-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 |
February | 826.56 | 11-FEB-17:03 | 267.84 | 231.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
March | 1110.17 | 22-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2593.20 | 28-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 |
May | 8833.07 | 31-MAY-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
June | 9340.16 | 19-JUN-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
July | 9404.39 | 11-JUL-05:12 | 669.60 | 275.74 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
August | 7853.55 | 02-AUG-06:01 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
September | 2744.08 | 01-SEP-13:40 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 |
October | 1230.52 | 04-OCT-15:50 | 1272.23 | 562.53 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 |
November | 821.05 | 04-NOV-16:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 819.77 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 819.77 | 267.84 | 231.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9404.39 | 1874.87 | 1158.15 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 517.03 | 21-JAN-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
February | 677.69 | 15-FEB-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 |
March | 7493.04 | 31-MAR-12:01 | 8054.28 | 3142.27 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 |
April | 7813.69 | 28-APR-12:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 |
May | 14136.17 | 21-MAY-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.80 |
June | 14461.13 | 04-JUN-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 |
July | 14542.12 | 09-JUL-07:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.31 |
August | 10955.46 | 25-AUG-06:01 | 1356.51 | 837.95 | 3230.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11811.02 | 10-SEP-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.82 |
October | 6310.95 | 03-OCT-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 |
November | 516.77 | 04-NOV-16:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 515.81 | 23-DEC-17:02 | 211.95 | 182.98 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 515.81 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14542.12 | 8054.28 | 3142.27 | 9085.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1142.08 | 25-JAN-13:30 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.68 |
February | 4776.41 | 15-FEB-13:40 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9240.13 | 31-MAR-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 |
April | 18060.67 | 23-APR-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.91 |
May | 20988.26 | 21-MAY-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.18 |
June | 21885.39 | 04-JUN-14:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.52 |
July | 22038.79 | 23-JUL-13:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
August | 21347.37 | 27-AUG-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.70 |
September | 19305.37 | 10-SEP-11:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.80 |
October | 10068.08 | 03-OCT-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.98 |
November | 2861.31 | 08-NOV-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.66 |
December | 820.15 | 23-DEC-17:02 | 334.80 | 289.04 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 820.15 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22038.79 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 516.28 | 21-JAN-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
February | 615.33 | 09-FEB-15:10 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 |
March | 1504.36 | 31-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.78 |
April | 8974.56 | 22-APR-17:08 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.34 |
May | 12290.28 | 29-MAY-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.64 |
June | 14997.35 | 11-JUN-16:41 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 |
July | 12128.15 | 30-JUL-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.49 |
August | 14040.78 | 27-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.41 |
September | 6946.32 | 02-SEP-17:43 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.64 |
October | 1434.07 | 03-OCT-15:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 |
November | 577.90 | 08-NOV-15:40 | 805.38 | 581.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
December | 515.51 | 23-DEC-17:02 | 211.94 | 182.97 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 515.51 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | |
Maximum of Months | 14997.35 | 805.38 | 581.47 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.34 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.110516E+12 | 90700.17 | 02-JAN-08:20 | 0.236236E+12 | 372570.44 | 12-JAN-07:19 |
February | 0.957699E+11 | 89223.00 | 27-FEB-08:09 | 0.156904E+12 | 373684.17 | 27-FEB-07:00 |
March | 0.105362E+12 | 86367.32 | 01-MAR-08:09 | 0.887066E+11 | 344856.15 | 01-MAR-07:19 |
April | 0.957252E+11 | 88654.69 | 21-APR-14:09 | 0.157272E+11 | 181585.22 | 03-APR-06:10 |
May | 0.104690E+12 | 112284.91 | 31-MAY-15:30 | 0.134000E+10 | 22244.44 | 01-MAY-06:19 |
June | 0.116976E+12 | 137023.36 | 30-JUN-14:30 | 0.268010E+09 | 16050.74 | 02-JUN-06:19 |
July | 0.119452E+12 | 138533.96 | 11-JUL-15:39 | 0.203808E+09 | 20412.51 | 05-JUL-06:19 |
August | 0.115470E+12 | 132401.59 | 11-AUG-15:50 | 0.618893E+09 | 32495.45 | 31-AUG-06:10 |
September | 0.964772E+11 | 91664.84 | 07-SEP-15:20 | 0.543886E+10 | 94760.27 | 28-SEP-06:10 |
October | 0.101313E+12 | 84805.44 | 30-OCT-07:10 | 0.541240E+11 | 197748.94 | 30-OCT-06:19 |
November | 0.105162E+12 | 89216.77 | 27-NOV-08:09 | 0.195227E+12 | 348177.52 | 27-NOV-07:19 |
December | 0.109966E+12 | 89166.90 | 04-DEC-08:20 | 0.257376E+12 | 356788.65 | 15-DEC-07:19 |
Annual Sum or Average | 0.127688E+13 | 0.101217E+13 | ||||
Minimum of Months | 0.957252E+11 | 84805.44 | 0.203808E+09 | 16050.74 | ||
Maximum of Months | 0.119452E+12 | 138533.96 | 0.257376E+12 | 373684.17 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.225434E+11 | 0.882650E+10 | 0.605851E+11 | 0.225746E+10 | 0.617843E+10 | 0.134028E+10 | 0.00 | 2954182.78 | 0.00 | 0.00 | 0.285363E+10 | 0.592820E+10 | 0.00 |
February | 0.190142E+11 | 0.607552E+10 | 0.548702E+11 | 0.204829E+10 | 0.482895E+10 | 0.932689E+09 | 0.00 | 3635703.09 | 0.00 | 0.00 | 0.261516E+10 | 0.538126E+10 | 0.00 |
March | 0.211190E+11 | 0.473450E+10 | 0.627783E+11 | 0.235496E+10 | 0.436771E+10 | 0.558714E+09 | 0.00 | 10098018.32 | 0.00 | 0.00 | 0.309209E+10 | 0.634656E+10 | 0.00 |
April | 0.182286E+11 | 0.291276E+10 | 0.586172E+11 | 0.219149E+10 | 0.493310E+10 | 0.110596E+09 | 0.00 | 0.936369E+09 | 0.00 | 0.00 | 0.207694E+10 | 0.571808E+10 | 0.00 |
May | 0.195583E+11 | 0.175545E+10 | 0.616817E+11 | 0.230537E+10 | 0.945063E+10 | 23852973.86 | 0.00 | 0.342699E+10 | 0.00 | 0.00 | 0.410027E+09 | 0.607758E+10 | 0.00 |
June | 0.193872E+11 | 0.925713E+09 | 0.604966E+11 | 0.226756E+10 | 0.142428E+11 | 14703630.22 | 0.00 | 0.136600E+11 | 0.00 | 0.00 | 0.159287E+09 | 0.582223E+10 | 0.00 |
July | 0.181701E+11 | 0.131570E+10 | 0.597911E+11 | 0.222839E+10 | 0.140198E+11 | 13942106.85 | 0.00 | 0.183559E+11 | 0.00 | 0.00 | 0.247374E+09 | 0.530911E+10 | 0.00 |
August | 0.203959E+11 | 0.241310E+10 | 0.627783E+11 | 0.235437E+10 | 0.112297E+11 | 17830479.44 | 0.00 | 0.103215E+11 | 0.00 | 0.00 | 0.245511E+09 | 0.571426E+10 | 0.00 |
September | 0.185972E+11 | 0.381882E+10 | 0.585950E+11 | 0.219062E+10 | 0.484175E+10 | 46435687.04 | 0.00 | 0.165005E+10 | 0.00 | 0.00 | 0.159349E+10 | 0.514383E+10 | 0.00 |
October | 0.202884E+11 | 0.580314E+10 | 0.605962E+11 | 0.225795E+10 | 0.382401E+10 | 0.355350E+09 | 0.00 | 44725839.29 | 0.00 | 0.00 | 0.272494E+10 | 0.541827E+10 | 0.00 |
November | 0.216482E+11 | 0.774574E+10 | 0.591197E+11 | 0.220012E+10 | 0.502924E+10 | 0.113295E+10 | 0.00 | 2325842.06 | 0.00 | 0.00 | 0.276619E+10 | 0.551718E+10 | 0.00 |
December | 0.223748E+11 | 0.969307E+10 | 0.597800E+11 | 0.222881E+10 | 0.599277E+10 | 0.138591E+10 | 0.00 | 2130583.19 | 0.00 | 0.00 | 0.282183E+10 | 0.568617E+10 | 0.00 |
Annual Sum or Average | 0.241325E+12 | 0.560200E+11 | 0.719689E+12 | 0.268854E+11 | 0.889389E+11 | 0.593326E+10 | 0.00 | 0.484167E+11 | 0.00 | 0.00 | 0.216065E+11 | 0.680627E+11 | 0.00 |
Minimum of Months | 0.181701E+11 | 0.925713E+09 | 0.548702E+11 | 0.204829E+10 | 0.382401E+10 | 13942106.85 | 0.00 | 2130583.19 | 0.00 | 0.00 | 0.159287E+09 | 0.514383E+10 | 0.00 |
Maximum of Months | 0.225434E+11 | 0.969307E+10 | 0.627783E+11 | 0.235496E+10 | 0.142428E+11 | 0.138591E+10 | 0.00 | 0.183559E+11 | 0.00 | 0.00 | 0.309209E+10 | 0.634656E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.236236E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.156904E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.887066E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.157272E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.134000E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.268010E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203808E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.618893E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.543886E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.541240E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.195227E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.257376E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101217E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.203808E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257376E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 19-JAN-12:20 | 8772.42 | 02-JAN-07:10 | 1201.51 | 12-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 25003.79 | 01-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 02-FEB-13:20 | 8772.42 | 27-FEB-07:10 | 1229.54 | 27-FEB-07:00 | 0.00 | 01-FEB-00:10 |
March | 25003.79 | 01-MAR-08:09 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:20 | 7813.01 | 06-MAR-07:10 | 1160.31 | 01-MAR-07:40 | 0.00 | 01-MAR-00:10 |
April | 20588.77 | 04-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 06-APR-07:19 | 13165.80 | 21-APR-15:00 | 931.51 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 19671.42 | 01-MAY-07:10 | 3328.83 | 01-MAY-21:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 01-MAY-12:09 | 21227.95 | 31-MAY-14:50 | 163.45 | 05-MAY-06:30 | 0.00 | 01-MAY-00:10 |
June | 19671.42 | 01-JUN-07:10 | 3328.83 | 01-JUN-22:49 | 41699.26 | 01-JUN-07:10 | 1410.29 | 05-JUN-07:10 | 25383.92 | 20-JUN-15:30 | 153.07 | 02-JUN-06:19 | 0.00 | 01-JUN-00:10 |
July | 19753.26 | 25-JUL-07:10 | 3328.83 | 11-JUL-22:00 | 41699.26 | 03-JUL-07:10 | 1410.29 | 05-JUL-11:09 | 27801.25 | 12-JUL-15:20 | 152.03 | 05-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 19896.12 | 18-AUG-15:00 | 5686.19 | 24-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-07:10 | 25110.25 | 10-AUG-15:50 | 227.41 | 30-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 24139.64 | 28-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-12:09 | 10646.02 | 08-SEP-15:30 | 561.13 | 28-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 25003.79 | 03-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-12:09 | 7477.26 | 30-OCT-06:10 | 941.68 | 30-OCT-06:19 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 02-NOV-11:20 | 8532.57 | 27-NOV-07:10 | 1174.06 | 28-NOV-07:49 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-08:09 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 15-DEC-13:50 | 8772.42 | 04-DEC-07:10 | 1181.94 | 05-DEC-07:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19671.42 | 3328.83 | 41699.26 | 1410.29 | 7477.26 | 152.03 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 27801.25 | 1229.54 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 486.82 | 07-JAN-07:10 | 0.00 | 0.00 | 2208.01 | 02-JAN-08:30 | 7772.11 | 02-JAN-12:00 | 0.00 |
February | 728.33 | 11-FEB-07:10 | 0.00 | 0.00 | 2208.01 | 01-FEB-13:30 | 7771.55 | 27-FEB-12:30 | 0.00 |
March | 767.74 | 18-MAR-06:10 | 0.00 | 0.00 | 2208.01 | 01-MAR-08:30 | 7770.58 | 06-MAR-12:00 | 0.00 |
April | 10530.70 | 21-APR-14:09 | 0.00 | 0.00 | 2208.01 | 01-APR-16:10 | 8345.65 | 06-APR-11:00 | 0.00 |
May | 23813.72 | 31-MAY-15:00 | 0.00 | 0.00 | 2208.01 | 05-MAY-07:19 | 7768.91 | 01-MAY-11:20 | 0.00 |
June | 43248.51 | 30-JUN-14:30 | 0.00 | 0.00 | 2208.01 | 20-JUN-15:50 | 7700.56 | 01-JUN-11:50 | 0.00 |
July | 41113.09 | 11-JUL-15:00 | 0.00 | 0.00 | 2208.01 | 11-JUL-12:50 | 7248.83 | 05-JUL-11:20 | 0.00 |
August | 37151.49 | 11-AUG-15:50 | 0.00 | 0.00 | 2208.01 | 30-AUG-06:19 | 7176.81 | 01-AUG-11:00 | 0.00 |
September | 13162.03 | 07-SEP-15:20 | 0.00 | 0.00 | 2208.01 | 02-SEP-09:09 | 7161.75 | 29-SEP-11:50 | 0.00 |
October | 2895.79 | 03-OCT-14:39 | 0.00 | 0.00 | 2208.01 | 02-OCT-07:10 | 7228.94 | 31-OCT-11:39 | 0.00 |
November | 594.67 | 04-NOV-06:10 | 0.00 | 0.00 | 2208.01 | 01-NOV-07:30 | 7672.33 | 30-NOV-12:39 | 0.00 |
December | 676.43 | 23-DEC-07:19 | 0.00 | 0.00 | 2208.01 | 01-DEC-19:10 | 7770.57 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 486.82 | 0.00 | 0.00 | 2208.01 | 7161.75 | 0.00 | |||
Maximum of Months | 43248.51 | 0.00 | 0.00 | 2208.01 | 8345.65 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 90700.17 | 02-JAN-08:20 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 8772.42 | 963.34 | 0.00 | 0.00 | 0.00 |
February | 89223.00 | 27-FEB-08:09 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 7573.16 | 1190.60 | 0.00 | 0.00 | 0.00 |
March | 86367.32 | 01-MAR-08:09 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 4681.89 | 1054.82 | 0.00 | 0.00 | 0.00 |
April | 88654.69 | 21-APR-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 10767.82 | 6.85 | 0.00 | 10530.70 | 0.00 |
May | 112284.91 | 31-MAY-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 20873.66 | 6.85 | 0.00 | 22808.55 | 0.00 |
June | 137023.36 | 30-JUN-14:30 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 24567.22 | 6.88 | 0.00 | 43248.51 | 0.00 |
July | 138533.96 | 11-JUL-15:39 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 26908.89 | 6.88 | 0.00 | 40888.38 | 0.00 |
August | 132401.59 | 11-AUG-15:50 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 24868.40 | 6.85 | 0.00 | 37151.49 | 0.00 |
September | 91664.84 | 07-SEP-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 10337.84 | 6.85 | 0.00 | 13162.03 | 0.00 |
October | 84805.44 | 30-OCT-07:10 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 3617.14 | 920.66 | 0.00 | 0.00 | 0.00 |
November | 89216.77 | 27-NOV-08:09 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 7573.16 | 1111.69 | 0.00 | 0.00 | 0.00 |
December | 89166.90 | 04-DEC-08:20 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 7573.16 | 955.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 84805.44 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 3617.14 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 138533.96 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 26908.89 | 1190.60 | 0.00 | 43248.51 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 372570.44 | 12-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 373684.17 | 27-FEB-07:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 344856.15 | 01-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 181585.22 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 22244.44 | 01-MAY-06:19 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 16050.74 | 02-JUN-06:19 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 20412.51 | 05-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 32495.45 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 94760.27 | 28-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 197748.94 | 30-OCT-06:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 348177.52 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 356788.65 | 15-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 16050.74 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 373684.17 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 19.73 | 7.67 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.83 | 19.73 | 7.67 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 19.73 | 7.67 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 19.18 | 8.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 3.50 | 19.73 | 3.50 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
March | 0.17 | 19.22 | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
November | 3.67 | 19.75 | 3.67 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
December | 6.17 | 19.71 | 6.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Annual Sum or Average | 22.33 | 19.51 | 21.50 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 19.75 | 8.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.67 | 18.85 | 12.83 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 10.33 | 18.86 | 8.67 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
March | 3.00 | 18.99 | 2.50 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
April | 0.17 | 19.15 | 0.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.33 | 19.12 | 2.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 13.00 | 18.93 | 10.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
December | 13.67 | 18.95 | 11.50 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 58.17 | 18.91 | 48.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.67 | 19.15 | 12.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.17 | 17.11 | 67.50 | 17.59 | 0.00 | 17.59 | 0.00 | 17.59 |
February | 76.00 | 16.76 | 44.50 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
March | 36.17 | 17.86 | 21.83 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
April | 4.33 | 17.63 | 2.33 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16.00 | 16.96 | 8.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
November | 85.67 | 16.93 | 51.67 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
December | 102.67 | 16.99 | 61.50 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
Annual Sum or Average | 427.00 | 17.05 | 257.33 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.17 | 17.86 | 67.50 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.83 | 15.65 | 29.67 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
February | 47.83 | 15.66 | 17.50 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
March | 15.17 | 16.30 | 3.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 1.83 | 15.86 | 0.17 | 16.11 | 0.17 | 16.97 | 0.17 | 17.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.14 | 3.17 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.58 | 2.50 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.86 | 5.67 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
October | 9.50 | 15.50 | 1.50 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
November | 56.50 | 15.58 | 23.67 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
December | 69.33 | 15.58 | 27.00 | 15.89 | 0.00 | 15.89 | 0.00 | 15.89 |
Annual Sum or Average | 267.00 | 15.65 | 103.00 | 15.98 | 13.17 | 16.39 | 12.83 | 16.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 0.00 | 15.69 |
Maximum of Months | 69.33 | 16.30 | 29.67 | 16.81 | 6.00 | 28.14 | 5.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.67 | 15.69 | 25.83 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 37.67 | 15.82 | 11.83 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
March | 10.00 | 16.48 | 2.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
April | 0.67 | 17.19 | 0.17 | 17.57 | 1.33 | 23.86 | 1.33 | 25.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.87 | 5.67 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.79 | 4.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.99 | 5.50 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 2.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.65 | 0.33 | 27.65 |
October | 7.00 | 15.79 | 1.50 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
November | 45.33 | 15.77 | 17.17 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
December | 61.83 | 15.65 | 24.83 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
Annual Sum or Average | 222.17 | 15.76 | 83.50 | 16.10 | 20.83 | 16.86 | 19.67 | 17.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 0.00 | 15.95 |
Maximum of Months | 61.83 | 17.19 | 25.83 | 17.57 | 5.83 | 27.99 | 5.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.00 | 15.58 | 28.67 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
February | 51.00 | 15.62 | 20.67 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
March | 15.00 | 16.23 | 3.17 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
April | 1.00 | 16.72 | 0.17 | 17.05 | 1.00 | 21.92 | 0.50 | 22.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.87 | 2.00 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.97 | 1.83 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.72 | 2.17 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.83 | 0.83 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.48 | 0.17 | 27.48 |
October | 10.33 | 15.49 | 2.17 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
November | 54.33 | 15.56 | 22.67 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
December | 69.00 | 15.54 | 26.33 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
Annual Sum or Average | 266.67 | 15.61 | 103.83 | 15.91 | 19.83 | 16.52 | 7.50 | 16.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 0.00 | 15.62 |
Maximum of Months | 69.00 | 16.72 | 28.67 | 17.05 | 5.67 | 27.97 | 2.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.00 | 18.74 | 107.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 82.83 | 18.54 | 68.17 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 23.00 | 19.23 | 20.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
April | 1.67 | 19.62 | 1.50 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 19.11 | 0.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 34.33 | 19.18 | 29.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 67.83 | 19.25 | 58.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 335.67 | 18.88 | 285.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 125.00 | 19.62 | 107.17 | 19.76 | 0.00 | 19.76 | 0.00 | 19.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.50 | 17.61 | 39.50 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
February | 27.50 | 17.38 | 15.50 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
March | 5.17 | 18.81 | 3.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
April | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.67 | 3.00 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.66 | 4.17 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
October | 0.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
November | 13.17 | 17.98 | 6.83 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
December | 22.67 | 17.92 | 13.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
Annual Sum or Average | 125.33 | 17.70 | 78.17 | 18.21 | 9.17 | 18.62 | 8.83 | 18.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 | 0.00 | 17.09 |
Maximum of Months | 56.50 | 18.81 | 39.50 | 19.24 | 4.50 | 27.67 | 4.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.00 | 16.34 | 267.17 | 16.39 | 0.00 | 16.39 | 0.00 | 16.39 |
February | 164.67 | 16.52 | 156.33 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
March | 105.00 | 16.37 | 103.33 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
April | 31.00 | 17.57 | 31.00 | 17.57 | 1.17 | 17.75 | 1.17 | 17.93 |
May | 5.33 | 20.09 | 5.33 | 20.09 | 2.50 | 21.50 | 2.50 | 22.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.43 | 2.33 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 3.33 | 27.75 |
August | 2.17 | 19.14 | 2.17 | 19.14 | 2.17 | 22.05 | 1.83 | 23.35 |
September | 21.33 | 19.20 | 21.33 | 19.20 | 0.50 | 19.29 | 0.50 | 19.39 |
October | 67.33 | 17.15 | 67.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
November | 209.33 | 16.52 | 205.33 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
December | 310.33 | 16.54 | 295.00 | 16.57 | 0.00 | 16.57 | 0.00 | 16.57 |
Annual Sum or Average | 1206.50 | 16.60 | 1154.17 | 16.62 | 12.17 | 16.68 | 11.67 | 16.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 0.00 | 16.37 |
Maximum of Months | 310.33 | 20.09 | 295.00 | 20.09 | 3.50 | 27.75 | 3.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 17.58 | 41.83 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
February | 34.50 | 17.49 | 21.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
March | 5.33 | 18.83 | 3.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.17 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.44 | 0.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.56 | 0.50 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 0.33 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.33 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
October | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
November | 12.50 | 18.06 | 6.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
December | 21.83 | 17.85 | 12.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
Annual Sum or Average | 133.00 | 17.70 | 85.17 | 18.18 | 7.50 | 18.49 | 1.50 | 18.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 0.00 | 17.04 |
Maximum of Months | 58.67 | 18.83 | 41.83 | 19.26 | 2.50 | 27.77 | 0.50 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 61.00 | 17.35 | 40.67 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
February | 34.33 | 17.81 | 23.67 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
March | 9.33 | 19.11 | 7.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
April | 0.67 | 19.03 | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.17 | 18.88 | 2.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
November | 30.17 | 18.27 | 20.67 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
December | 42.67 | 18.26 | 30.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
Annual Sum or Average | 181.33 | 17.93 | 125.33 | 18.35 | 0.67 | 18.37 | 0.00 | 18.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.00 | 19.11 | 40.67 | 19.37 | 0.67 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.00 | 16.03 | 18.17 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
February | 16.17 | 16.76 | 7.33 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
March | 1.67 | 17.36 | 0.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
April | 0.17 | 17.14 | 0.00 | 17.14 | 0.67 | 25.44 | 0.67 | 26.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.12 | 3.67 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.58 | 2.83 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.78 | 6.17 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
October | 0.83 | 17.02 | 0.17 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
November | 14.50 | 16.70 | 5.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
December | 21.67 | 16.62 | 8.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 93.00 | 16.43 | 40.00 | 16.86 | 17.17 | 18.11 | 15.83 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | 0.00 | 16.35 |
Maximum of Months | 38.00 | 17.36 | 18.17 | 17.68 | 6.83 | 28.12 | 6.17 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.33 | 16.27 | 14.00 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
February | 10.50 | 16.87 | 5.17 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
March | 1.00 | 17.74 | 0.33 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.71 | 2.50 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.92 | 5.83 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.76 | 4.00 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.94 | 5.50 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.86 | 3.67 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.67 | 27.68 |
October | 0.67 | 17.16 | 0.17 | 17.59 | 0.00 | 17.59 | 0.00 | 17.59 |
November | 11.50 | 17.03 | 3.83 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
December | 18.00 | 16.86 | 7.17 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
Annual Sum or Average | 72.00 | 16.66 | 30.67 | 17.11 | 22.83 | 19.07 | 22.17 | 20.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 0.00 | 16.66 |
Maximum of Months | 30.33 | 17.74 | 14.00 | 18.14 | 5.83 | 27.94 | 5.83 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.83 | 15.98 | 19.50 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
February | 18.83 | 16.84 | 10.00 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
March | 1.83 | 17.66 | 0.50 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.60 | 0.50 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.87 | 2.17 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.90 | 1.83 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.67 | 2.00 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.84 | 0.83 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.33 | 27.39 |
October | 0.83 | 17.01 | 0.17 | 17.38 | 0.00 | 17.38 | 0.00 | 17.38 |
November | 13.67 | 16.82 | 4.83 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
December | 21.67 | 16.63 | 8.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 96.67 | 16.45 | 43.67 | 16.86 | 20.83 | 18.27 | 7.67 | 18.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.28 | 0.00 | 16.28 |
Maximum of Months | 39.83 | 17.66 | 19.50 | 18.09 | 5.83 | 27.90 | 2.17 | 27.89 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.27 | 272.00 | 21.04 | 272.00 | 20.92 |
February | 454.00 | 22.00 | 146.50 | 21.73 | 146.50 | 21.57 |
March | 514.00 | 23.01 | 15.33 | 22.95 | 15.33 | 22.90 |
April | 396.33 | 23.90 | 10.67 | 23.96 | 0.00 | 23.96 |
May | 67.33 | 24.01 | 62.17 | 24.99 | 0.00 | 24.99 |
June | 0.00 | 0.00 | 226.67 | 25.00 | 0.00 | 25.00 |
July | 0.00 | 0.00 | 391.50 | 24.70 | 0.00 | 24.70 |
August | 9.67 | 24.00 | 288.17 | 24.76 | 0.00 | 24.76 |
September | 121.33 | 23.99 | 66.17 | 24.70 | 0.00 | 24.70 |
October | 471.00 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
November | 489.00 | 22.02 | 126.67 | 21.81 | 126.67 | 21.67 |
December | 497.00 | 21.33 | 323.17 | 21.20 | 323.17 | 21.14 |
Annual Sum or Average | 3521.67 | 22.49 | 1929.00 | 22.70 | 883.67 | 22.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.04 | 0.00 | 20.92 |
Maximum of Months | 514.00 | 24.01 | 391.50 | 25.00 | 323.17 | 25.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.42 | 466.83 | 20.38 | 466.83 | 20.37 |
February | 454.00 | 20.78 | 320.00 | 20.64 | 320.00 | 20.58 |
March | 514.00 | 21.49 | 200.17 | 21.30 | 200.17 | 21.19 |
April | 477.33 | 23.08 | 34.17 | 22.95 | 34.17 | 22.83 |
May | 274.33 | 23.91 | 4.17 | 23.94 | 0.00 | 23.94 |
June | 12.33 | 24.00 | 154.00 | 24.75 | 0.00 | 24.75 |
July | 0.00 | 0.00 | 299.83 | 24.56 | 0.00 | 24.56 |
August | 52.00 | 23.85 | 154.33 | 24.47 | 0.00 | 24.47 |
September | 333.17 | 23.36 | 1.00 | 23.37 | 0.00 | 23.37 |
October | 502.00 | 21.91 | 99.83 | 21.70 | 99.83 | 21.55 |
November | 489.00 | 20.67 | 415.33 | 20.61 | 415.33 | 20.58 |
December | 497.00 | 20.48 | 489.00 | 20.48 | 489.00 | 20.47 |
Annual Sum or Average | 4107.17 | 21.65 | 2638.67 | 21.58 | 2025.33 | 21.33 |
Minimum of Months | 0.00 | 0.00 | 1.00 | 20.38 | 0.00 | 20.37 |
Maximum of Months | 514.00 | 24.00 | 489.00 | 24.75 | 489.00 | 24.75 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 502.00 | 20.05 | 502.00 | 20.05 |
February | 454.00 | 20.22 | 416.00 | 20.17 | 416.00 | 20.16 |
March | 514.00 | 20.82 | 367.50 | 20.68 | 367.50 | 20.62 |
April | 485.00 | 22.38 | 109.17 | 22.03 | 109.17 | 21.79 |
May | 352.00 | 23.70 | 1.00 | 23.71 | 0.00 | 23.71 |
June | 28.33 | 23.88 | 114.33 | 24.50 | 0.00 | 24.50 |
July | 3.83 | 23.68 | 264.33 | 24.50 | 0.00 | 24.50 |
August | 112.83 | 23.56 | 107.33 | 24.06 | 0.00 | 24.06 |
September | 447.17 | 22.81 | 16.83 | 22.73 | 16.83 | 22.66 |
October | 502.00 | 20.95 | 282.83 | 20.74 | 282.83 | 20.63 |
November | 489.00 | 20.11 | 488.50 | 20.11 | 488.50 | 20.11 |
December | 497.00 | 20.06 | 497.00 | 20.06 | 497.00 | 20.06 |
Annual Sum or Average | 4387.17 | 21.22 | 3166.83 | 21.07 | 2679.83 | 20.84 |
Minimum of Months | 3.83 | 20.05 | 1.00 | 20.05 | 0.00 | 20.05 |
Maximum of Months | 514.00 | 23.88 | 502.00 | 24.50 | 502.00 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.59 | 502.00 | 19.59 | 502.00 | 19.59 |
February | 454.00 | 19.73 | 454.00 | 19.73 | 454.00 | 19.73 |
March | 514.00 | 20.15 | 490.00 | 20.12 | 490.00 | 20.12 |
April | 485.00 | 21.42 | 214.67 | 21.03 | 214.67 | 20.82 |
May | 373.00 | 23.46 | 4.33 | 23.44 | 3.00 | 23.43 |
June | 35.17 | 23.70 | 181.50 | 24.42 | 0.00 | 24.42 |
July | 18.50 | 23.59 | 337.67 | 24.44 | 0.00 | 24.44 |
August | 178.17 | 23.15 | 105.50 | 23.56 | 3.33 | 23.53 |
September | 479.33 | 21.92 | 97.00 | 21.69 | 97.00 | 21.53 |
October | 502.00 | 20.25 | 430.00 | 20.16 | 430.00 | 20.13 |
November | 489.00 | 19.65 | 489.00 | 19.65 | 489.00 | 19.65 |
December | 497.00 | 19.58 | 497.00 | 19.58 | 497.00 | 19.58 |
Annual Sum or Average | 4527.17 | 20.70 | 3802.67 | 20.65 | 3180.00 | 20.42 |
Minimum of Months | 18.50 | 19.58 | 4.33 | 19.58 | 0.00 | 19.58 |
Maximum of Months | 514.00 | 23.70 | 502.00 | 24.44 | 502.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.84 | 447.33 | 19.83 | 447.33 | 19.83 |
March | 512.83 | 20.62 | 390.83 | 20.42 | 390.83 | 20.33 |
April | 403.33 | 22.01 | 152.50 | 21.64 | 140.50 | 21.37 |
May | 173.17 | 23.69 | 132.83 | 24.14 | 8.83 | 24.23 |
June | 29.33 | 24.45 | 305.67 | 24.47 | 6.33 | 24.52 |
July | 32.83 | 25.97 | 411.67 | 24.67 | 22.67 | 24.78 |
August | 90.83 | 23.44 | 257.83 | 24.09 | 4.00 | 24.09 |
September | 379.50 | 22.20 | 78.50 | 22.14 | 57.50 | 21.96 |
October | 500.83 | 20.49 | 365.17 | 20.30 | 365.17 | 20.22 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4064.67 | 20.73 | 4030.33 | 20.96 | 2931.17 | 20.70 |
Minimum of Months | 29.33 | 19.68 | 78.50 | 19.68 | 4.00 | 19.68 |
Maximum of Months | 512.83 | 25.97 | 502.00 | 24.67 | 502.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 499.00 | 19.73 | 499.00 | 19.73 |
February | 453.00 | 20.20 | 405.67 | 20.07 | 405.67 | 20.02 |
March | 470.67 | 20.94 | 326.00 | 20.62 | 326.00 | 20.49 |
April | 332.67 | 21.97 | 183.67 | 21.95 | 115.67 | 21.66 |
May | 238.00 | 23.39 | 128.50 | 23.82 | 15.00 | 23.88 |
June | 68.33 | 24.30 | 266.33 | 24.42 | 14.17 | 24.52 |
July | 56.00 | 24.91 | 365.83 | 24.58 | 22.00 | 24.70 |
August | 127.00 | 23.43 | 251.00 | 24.09 | 12.33 | 24.13 |
September | 336.17 | 22.14 | 120.83 | 22.36 | 49.33 | 22.18 |
October | 482.50 | 20.74 | 323.50 | 20.49 | 319.67 | 20.38 |
November | 489.00 | 19.82 | 480.00 | 19.79 | 480.00 | 19.78 |
December | 497.00 | 19.70 | 497.00 | 19.70 | 497.00 | 19.70 |
Annual Sum or Average | 4052.33 | 20.91 | 3847.33 | 21.09 | 2755.83 | 20.82 |
Minimum of Months | 56.00 | 19.70 | 120.83 | 19.70 | 12.33 | 19.70 |
Maximum of Months | 502.00 | 24.91 | 499.00 | 24.58 | 499.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 502.00 | 19.70 | 502.00 | 19.70 |
February | 454.00 | 19.82 | 449.83 | 19.82 | 449.83 | 19.82 |
March | 514.00 | 20.38 | 441.00 | 20.27 | 441.00 | 20.22 |
April | 404.33 | 21.67 | 189.00 | 21.37 | 165.17 | 21.11 |
May | 274.00 | 23.29 | 59.17 | 23.53 | 8.00 | 23.53 |
June | 56.67 | 23.97 | 234.17 | 24.45 | 6.67 | 24.51 |
July | 40.67 | 24.36 | 352.50 | 24.49 | 10.17 | 24.56 |
August | 145.33 | 23.18 | 192.67 | 23.85 | 7.00 | 23.86 |
September | 422.33 | 22.01 | 91.67 | 21.86 | 78.50 | 21.68 |
October | 502.00 | 20.34 | 408.50 | 20.21 | 408.50 | 20.16 |
November | 489.00 | 19.73 | 489.00 | 19.73 | 489.00 | 19.73 |
December | 497.00 | 19.68 | 497.00 | 19.68 | 497.00 | 19.68 |
Annual Sum or Average | 4301.33 | 20.73 | 3906.50 | 20.82 | 3062.83 | 20.58 |
Minimum of Months | 40.67 | 19.68 | 59.17 | 19.68 | 6.67 | 19.68 |
Maximum of Months | 514.00 | 24.36 | 502.00 | 24.49 | 502.00 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.55 | 502.00 | 19.55 | 502.00 | 19.55 |
February | 454.00 | 19.69 | 454.00 | 19.69 | 454.00 | 19.69 |
March | 514.00 | 20.27 | 509.67 | 20.26 | 509.67 | 20.26 |
April | 485.00 | 21.14 | 262.33 | 20.91 | 262.33 | 20.79 |
May | 502.50 | 23.32 | 0.00 | 23.32 | 0.00 | 23.32 |
June | 81.67 | 23.85 | 86.33 | 24.18 | 0.00 | 24.18 |
July | 6.50 | 23.64 | 275.50 | 24.45 | 0.00 | 24.45 |
August | 140.00 | 23.46 | 77.00 | 23.83 | 0.00 | 23.83 |
September | 477.83 | 22.60 | 27.33 | 22.50 | 27.33 | 22.41 |
October | 502.00 | 20.80 | 329.33 | 20.66 | 329.33 | 20.60 |
November | 489.00 | 19.88 | 489.00 | 19.88 | 489.00 | 19.88 |
December | 497.00 | 19.69 | 497.00 | 19.69 | 497.00 | 19.69 |
Annual Sum or Average | 4651.50 | 20.91 | 3509.50 | 20.74 | 3070.67 | 20.52 |
Minimum of Months | 6.50 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Maximum of Months | 514.00 | 23.85 | 509.67 | 24.45 | 509.67 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.92 | 454.00 | 19.92 | 454.00 | 19.92 |
March | 514.00 | 20.68 | 420.50 | 20.55 | 420.50 | 20.50 |
April | 447.50 | 22.23 | 132.83 | 21.90 | 128.00 | 21.65 |
May | 183.50 | 23.73 | 95.67 | 24.13 | 2.17 | 24.16 |
June | 18.67 | 23.89 | 271.83 | 24.45 | 0.50 | 24.46 |
July | 19.00 | 26.14 | 426.00 | 24.64 | 13.83 | 24.71 |
August | 39.00 | 23.75 | 294.17 | 24.36 | 0.50 | 24.36 |
September | 311.83 | 22.86 | 44.17 | 23.09 | 9.83 | 23.03 |
October | 500.50 | 21.22 | 254.00 | 20.96 | 254.00 | 20.83 |
November | 489.00 | 19.93 | 489.00 | 19.93 | 489.00 | 19.93 |
December | 497.00 | 19.79 | 497.00 | 19.79 | 497.00 | 19.79 |
Annual Sum or Average | 3976.00 | 20.90 | 3881.17 | 21.12 | 2771.33 | 20.84 |
Minimum of Months | 18.67 | 19.74 | 44.17 | 19.74 | 0.50 | 19.74 |
Maximum of Months | 514.00 | 26.14 | 502.00 | 24.64 | 502.00 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.47 | 502.00 | 17.47 | 502.00 | 17.47 |
February | 454.00 | 18.67 | 440.33 | 18.63 | 440.33 | 18.62 |
March | 514.00 | 19.85 | 420.33 | 19.64 | 420.33 | 19.56 |
April | 395.17 | 21.70 | 144.33 | 21.49 | 116.00 | 21.18 |
May | 287.50 | 22.83 | 60.67 | 23.23 | 3.67 | 23.22 |
June | 89.17 | 22.89 | 198.67 | 24.04 | 1.83 | 24.06 |
July | 59.33 | 23.24 | 371.67 | 24.37 | 11.00 | 24.43 |
August | 118.67 | 22.81 | 269.50 | 24.00 | 7.83 | 24.02 |
September | 322.17 | 22.06 | 95.17 | 22.43 | 23.50 | 22.28 |
October | 490.33 | 20.64 | 278.50 | 20.29 | 276.83 | 20.12 |
November | 489.00 | 18.12 | 487.83 | 18.12 | 487.83 | 18.12 |
December | 497.00 | 17.17 | 497.00 | 17.17 | 497.00 | 17.17 |
Annual Sum or Average | 4218.33 | 19.76 | 3766.00 | 19.88 | 2788.17 | 19.49 |
Minimum of Months | 59.33 | 17.17 | 60.67 | 17.17 | 1.83 | 17.17 |
Maximum of Months | 514.00 | 23.24 | 502.00 | 24.37 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.85 | 454.00 | 19.85 | 454.00 | 19.85 |
March | 514.00 | 20.41 | 482.83 | 20.37 | 482.83 | 20.35 |
April | 434.33 | 21.97 | 151.83 | 21.63 | 146.00 | 21.41 |
May | 352.00 | 23.47 | 15.50 | 23.57 | 0.00 | 23.57 |
June | 51.17 | 23.81 | 190.67 | 24.44 | 1.00 | 24.45 |
July | 9.83 | 23.75 | 354.33 | 24.47 | 0.50 | 24.48 |
August | 85.17 | 23.60 | 207.17 | 24.22 | 1.00 | 24.23 |
September | 393.50 | 22.78 | 23.17 | 22.76 | 13.83 | 22.70 |
October | 502.00 | 20.92 | 309.83 | 20.74 | 309.83 | 20.66 |
November | 489.00 | 19.93 | 489.00 | 19.93 | 489.00 | 19.93 |
December | 497.00 | 19.80 | 497.00 | 19.80 | 497.00 | 19.80 |
Annual Sum or Average | 4284.00 | 20.94 | 3677.33 | 20.96 | 2897.00 | 20.71 |
Minimum of Months | 9.83 | 19.74 | 15.50 | 19.74 | 0.00 | 19.74 |
Maximum of Months | 514.00 | 23.81 | 502.00 | 24.47 | 502.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 502.00 | 19.79 | 502.00 | 19.79 |
February | 454.00 | 19.92 | 450.33 | 19.92 | 450.33 | 19.92 |
March | 514.00 | 20.46 | 459.50 | 20.41 | 459.50 | 20.39 |
April | 485.00 | 22.05 | 143.50 | 21.66 | 143.50 | 21.42 |
May | 314.50 | 23.78 | 1.33 | 23.79 | 0.00 | 23.79 |
June | 8.00 | 23.93 | 209.83 | 24.60 | 0.00 | 24.60 |
July | 0.67 | 23.81 | 369.17 | 24.53 | 0.00 | 24.53 |
August | 102.00 | 23.51 | 136.83 | 24.03 | 0.00 | 24.03 |
September | 454.83 | 22.61 | 28.50 | 22.50 | 28.50 | 22.41 |
October | 502.00 | 20.71 | 328.50 | 20.54 | 328.50 | 20.47 |
November | 489.00 | 19.84 | 489.00 | 19.84 | 489.00 | 19.84 |
December | 497.00 | 19.78 | 497.00 | 19.78 | 497.00 | 19.78 |
Annual Sum or Average | 4323.00 | 20.93 | 3615.50 | 20.92 | 2898.33 | 20.67 |
Minimum of Months | 0.67 | 19.78 | 1.33 | 19.78 | 0.00 | 19.78 |
Maximum of Months | 514.00 | 23.93 | 502.00 | 24.60 | 502.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.64 | 427.00 | 19.64 | 427.00 | 19.64 |
February | 385.00 | 19.87 | 374.17 | 19.85 | 374.17 | 19.84 |
March | 431.17 | 20.90 | 280.33 | 20.66 | 280.33 | 20.55 |
April | 333.67 | 22.40 | 88.67 | 22.19 | 71.33 | 21.94 |
May | 139.33 | 24.07 | 128.33 | 24.51 | 9.83 | 24.61 |
June | 11.50 | 25.82 | 260.17 | 24.68 | 7.00 | 24.74 |
July | 23.67 | 26.91 | 363.33 | 24.85 | 23.00 | 24.97 |
August | 45.00 | 23.81 | 234.33 | 24.40 | 3.17 | 24.43 |
September | 295.33 | 22.73 | 49.00 | 22.95 | 15.00 | 22.88 |
October | 425.67 | 20.92 | 246.00 | 20.67 | 246.00 | 20.55 |
November | 417.00 | 19.68 | 417.00 | 19.68 | 417.00 | 19.68 |
December | 422.00 | 19.61 | 422.00 | 19.61 | 422.00 | 19.61 |
Annual Sum or Average | 3356.33 | 20.85 | 3290.33 | 21.12 | 2295.83 | 20.83 |
Minimum of Months | 11.50 | 19.61 | 49.00 | 19.61 | 3.17 | 19.61 |
Maximum of Months | 431.17 | 26.91 | 427.00 | 24.85 | 427.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 494.33 | 19.89 | 494.33 | 19.88 |
February | 449.50 | 20.54 | 366.67 | 20.36 | 366.67 | 20.29 |
March | 452.50 | 21.25 | 261.17 | 20.98 | 254.50 | 20.82 |
April | 304.50 | 22.47 | 143.50 | 22.59 | 66.00 | 22.34 |
May | 198.83 | 23.81 | 133.67 | 24.20 | 10.67 | 24.30 |
June | 31.67 | 25.16 | 296.33 | 24.56 | 13.17 | 24.65 |
July | 24.67 | 26.54 | 401.83 | 24.67 | 21.17 | 24.78 |
August | 81.33 | 24.00 | 279.33 | 24.38 | 10.33 | 24.45 |
September | 299.00 | 22.80 | 104.00 | 23.15 | 14.50 | 23.08 |
October | 472.33 | 21.29 | 230.50 | 21.01 | 224.83 | 20.85 |
November | 489.00 | 20.06 | 465.17 | 20.01 | 465.17 | 19.99 |
December | 497.00 | 19.84 | 497.00 | 19.84 | 497.00 | 19.84 |
Annual Sum or Average | 3802.33 | 21.14 | 3673.50 | 21.38 | 2438.33 | 21.09 |
Minimum of Months | 24.67 | 19.84 | 104.00 | 19.84 | 10.33 | 19.84 |
Maximum of Months | 502.00 | 26.54 | 497.00 | 24.67 | 497.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 502.00 | 19.84 | 502.00 | 19.84 |
February | 454.00 | 19.98 | 441.17 | 19.96 | 441.17 | 19.96 |
March | 514.00 | 20.70 | 398.67 | 20.55 | 398.67 | 20.49 |
April | 390.50 | 22.24 | 130.00 | 22.00 | 103.50 | 21.74 |
May | 229.33 | 23.70 | 57.67 | 23.97 | 3.50 | 24.01 |
June | 23.83 | 24.67 | 265.33 | 24.61 | 6.33 | 24.66 |
July | 12.33 | 26.05 | 392.83 | 24.58 | 9.00 | 24.63 |
August | 94.33 | 23.65 | 220.17 | 24.21 | 4.17 | 24.24 |
September | 384.83 | 22.63 | 36.50 | 22.62 | 20.83 | 22.53 |
October | 502.00 | 20.81 | 310.17 | 20.61 | 310.17 | 20.52 |
November | 489.00 | 19.88 | 488.33 | 19.88 | 488.33 | 19.87 |
December | 497.00 | 19.82 | 497.00 | 19.82 | 497.00 | 19.82 |
Annual Sum or Average | 4093.17 | 20.93 | 3739.83 | 21.06 | 2784.67 | 20.80 |
Minimum of Months | 12.33 | 19.82 | 36.50 | 19.82 | 3.50 | 19.82 |
Maximum of Months | 514.00 | 26.05 | 502.00 | 24.61 | 502.00 | 24.66 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27057 | 15.40307 | -0.5857 | 13.70597 |
February | 454.00000 | 21.99870 | 17.06816 | -0.3905 | 9.50383 |
March | 514.00000 | 23.01003 | 18.08514 | -0.1347 | 6.20419 |
April | 485.00000 | 24.09310 | 16.87539 | 0.17259 | 6.06307 |
May | 508.00000 | 24.41161 | 21.10071 | -0.5186 | 11.06404 |
June | 496.00000 | 24.46814 | 32.76956 | -0.3850 | 8.79325 |
July | 497.00000 | 24.54894 | 40.83813 | -0.3020 | 7.72271 |
August | 514.00000 | 24.45297 | 36.27726 | -0.3745 | 8.63925 |
September | 485.00000 | 24.38706 | 27.62475 | -0.5240 | 11.42467 |
October | 502.00000 | 23.68965 | 22.54914 | 0.07788 | 5.80730 |
November | 489.00000 | 22.01522 | 15.84406 | -0.3964 | 9.12362 |
December | 497.00000 | 21.33481 | 12.84787 | -0.5793 | 12.51854 |
Annual Sum or Average | 5943.00000 | 23.31706 | 23.17489 | -0.3282 | 9.20828 |
Minimum of Months | 454.00000 | 21.27057 | 12.84787 | -0.5857 | 5.80730 |
Maximum of Months | 514.00000 | 24.54894 | 40.83813 | 0.17259 | 13.70597 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41829 | 18.07943 | -0.7872 | 19.65589 |
February | 454.00000 | 20.77736 | 20.37305 | -0.6670 | 15.77138 |
March | 514.00000 | 21.49294 | 21.33225 | -0.4631 | 10.40120 |
April | 485.00000 | 23.11379 | 18.63343 | -0.0517 | 6.51420 |
May | 508.00000 | 24.10701 | 21.88335 | -0.6398 | 13.90696 |
June | 496.00000 | 24.28620 | 33.62689 | -0.4654 | 9.85922 |
July | 497.00000 | 24.34092 | 41.81195 | -0.3918 | 8.58833 |
August | 514.00000 | 24.22826 | 37.36054 | -0.4779 | 10.15770 |
September | 485.00000 | 23.65311 | 30.19053 | -0.7879 | 19.31029 |
October | 502.00000 | 21.90517 | 27.12850 | -0.3210 | 8.51877 |
November | 489.00000 | 20.67466 | 19.10713 | -0.7085 | 16.49422 |
December | 497.00000 | 20.48278 | 14.82020 | -0.7925 | 19.17153 |
Annual Sum or Average | 5943.00000 | 22.47039 | 25.42095 | -0.5453 | 13.16057 |
Minimum of Months | 454.00000 | 20.41829 | 14.82020 | -0.7925 | 6.51420 |
Maximum of Months | 514.00000 | 24.34092 | 41.81195 | -0.0517 | 19.65589 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05283 | 18.40133 | -0.9177 | 24.91814 |
February | 454.00000 | 20.22298 | 21.08634 | -0.8365 | 22.03919 |
March | 514.00000 | 20.82012 | 21.81216 | -0.6558 | 15.47516 |
April | 485.00000 | 22.38166 | 19.55806 | -0.2369 | 8.77966 |
May | 508.00000 | 23.86327 | 22.47246 | -0.7328 | 17.03004 |
June | 496.00000 | 24.21178 | 33.61348 | -0.4956 | 10.39888 |
July | 497.00000 | 24.27381 | 41.87052 | -0.4216 | 9.01511 |
August | 514.00000 | 24.05904 | 37.82612 | -0.5502 | 11.96670 |
September | 485.00000 | 22.89962 | 32.29385 | -1.0577 | 30.52242 |
October | 502.00000 | 20.95360 | 28.47655 | -0.5747 | 13.78176 |
November | 489.00000 | 20.10647 | 19.56438 | -0.8887 | 23.63244 |
December | 497.00000 | 20.05541 | 15.18635 | -0.9381 | 25.42873 |
Annual Sum or Average | 5943.00000 | 22.00758 | 26.06776 | -0.6907 | 17.68193 |
Minimum of Months | 454.00000 | 20.05283 | 15.18635 | -1.0577 | 8.77966 |
Maximum of Months | 514.00000 | 24.27381 | 41.87052 | -0.2369 | 30.52242 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.59241 | 18.32022 | -1.1384 | 34.10320 |
February | 454.00000 | 19.73079 | 21.54917 | -1.0551 | 30.79393 |
March | 514.00000 | 20.14986 | 22.70027 | -0.8868 | 23.70837 |
April | 485.00000 | 21.42453 | 20.64082 | -0.4751 | 13.46619 |
May | 508.00000 | 23.63343 | 23.08743 | -0.8028 | 19.90606 |
June | 496.00000 | 24.22126 | 33.69441 | -0.4502 | 9.72885 |
July | 497.00000 | 24.31518 | 41.86508 | -0.3753 | 8.54500 |
August | 514.00000 | 23.79943 | 38.99004 | -0.6312 | 14.90536 |
September | 485.00000 | 21.94668 | 34.81294 | -1.3847 | 45.74810 |
October | 502.00000 | 20.24850 | 29.43598 | -0.8001 | 20.74086 |
November | 489.00000 | 19.64952 | 19.72055 | -1.1091 | 32.85447 |
December | 497.00000 | 19.57904 | 14.85930 | -1.1687 | 35.30445 |
Annual Sum or Average | 5943.00000 | 21.54240 | 26.69309 | -0.8540 | 24.04095 |
Minimum of Months | 454.00000 | 19.57904 | 14.85930 | -1.3847 | 8.54500 |
Maximum of Months | 514.00000 | 24.31518 | 41.86508 | -0.3753 | 45.74810 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70248 | 18.79249 | -1.1147 | 33.04308 |
February | 454.00000 | 19.84214 | 22.57608 | -1.0055 | 28.80206 |
March | 514.00000 | 20.63082 | 23.52353 | -0.7184 | 18.89410 |
April | 485.00000 | 22.38838 | 19.78457 | -0.2087 | 10.59943 |
May | 508.00000 | 24.07179 | 21.71596 | -0.5330 | 13.42558 |
June | 496.00000 | 24.31703 | 33.22563 | -0.3191 | 8.36592 |
July | 497.00000 | 24.46059 | 41.19175 | -0.2204 | 7.68375 |
August | 514.00000 | 24.09235 | 37.81985 | -0.4451 | 10.75644 |
September | 485.00000 | 22.68517 | 34.08628 | -1.1081 | 34.61664 |
October | 502.00000 | 20.49821 | 30.28764 | -0.7164 | 18.65000 |
November | 489.00000 | 19.73093 | 20.32492 | -1.0884 | 31.95842 |
December | 497.00000 | 19.67733 | 15.22681 | -1.1514 | 34.49465 |
Annual Sum or Average | 5943.00000 | 21.85969 | 26.59198 | -0.7160 | 20.82387 |
Minimum of Months | 454.00000 | 19.67733 | 15.22681 | -1.1514 | 7.68375 |
Maximum of Months | 514.00000 | 24.46059 | 41.19175 | -0.2087 | 34.61664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73785 | 18.52532 | -1.0860 | 31.92936 |
February | 454.00000 | 20.20934 | 21.56131 | -0.8832 | 24.91835 |
March | 514.00000 | 21.20225 | 21.43424 | -0.5596 | 16.78571 |
April | 485.00000 | 22.70408 | 17.98766 | -0.0990 | 11.05579 |
May | 508.00000 | 23.85327 | 21.79112 | -0.6269 | 17.13095 |
June | 496.00000 | 24.23849 | 33.19570 | -0.3725 | 9.43612 |
July | 497.00000 | 24.36131 | 41.35387 | -0.2788 | 8.46191 |
August | 514.00000 | 24.04640 | 37.53417 | -0.4449 | 11.97674 |
September | 485.00000 | 22.81367 | 32.42167 | -1.0329 | 32.46707 |
October | 502.00000 | 20.86227 | 28.63043 | -0.6134 | 16.75010 |
November | 489.00000 | 19.81638 | 20.03163 | -1.0359 | 30.04711 |
December | 497.00000 | 19.69579 | 14.94178 | -1.1384 | 33.94851 |
Annual Sum or Average | 5943.00000 | 21.97822 | 25.83353 | -0.6787 | 20.32582 |
Minimum of Months | 454.00000 | 19.69579 | 14.94178 | -1.1384 | 8.46191 |
Maximum of Months | 514.00000 | 24.36131 | 41.35387 | -0.0990 | 33.94851 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.70056 | 18.71048 | -1.1183 | 33.17920 |
February | 454.00000 | 19.82447 | 22.35555 | -1.0252 | 29.56150 |
March | 514.00000 | 20.38410 | 23.64391 | -0.8097 | 21.56053 |
April | 485.00000 | 22.09095 | 20.19277 | -0.2798 | 12.23606 |
May | 508.00000 | 23.73447 | 23.08195 | -0.7206 | 18.80582 |
June | 496.00000 | 24.25196 | 33.82378 | -0.3898 | 9.52622 |
July | 497.00000 | 24.33622 | 42.07897 | -0.3277 | 8.51619 |
August | 514.00000 | 23.91653 | 38.92818 | -0.5468 | 13.40366 |
September | 485.00000 | 22.29023 | 34.87062 | -1.2524 | 40.57497 |
October | 502.00000 | 20.33964 | 30.48535 | -0.7685 | 19.98550 |
November | 489.00000 | 19.73443 | 20.29286 | -1.0876 | 31.92729 |
December | 497.00000 | 19.67863 | 15.21117 | -1.1517 | 34.50378 |
Annual Sum or Average | 5943.00000 | 21.70747 | 27.02543 | -0.7874 | 22.71012 |
Minimum of Months | 454.00000 | 19.67863 | 15.21117 | -1.2524 | 8.51619 |
Maximum of Months | 514.00000 | 24.33622 | 42.07897 | -0.2798 | 40.57497 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.54897 | 16.46962 | -1.1400 | 33.93787 |
February | 454.00000 | 19.68975 | 19.12177 | -1.0744 | 31.30013 |
March | 514.00000 | 20.26547 | 21.13206 | -0.8836 | 22.86439 |
April | 485.00000 | 21.14247 | 21.26780 | -0.5574 | 13.25680 |
May | 508.00000 | 23.33197 | 24.79980 | -0.9452 | 24.76949 |
June | 496.00000 | 24.14132 | 34.55308 | -0.5282 | 11.13118 |
July | 497.00000 | 24.26193 | 42.49132 | -0.4221 | 9.02847 |
August | 514.00000 | 23.96112 | 38.99034 | -0.5867 | 13.00748 |
September | 485.00000 | 22.61957 | 32.97124 | -1.1451 | 34.19014 |
October | 502.00000 | 20.79953 | 27.20967 | -0.6289 | 14.68361 |
November | 489.00000 | 19.87807 | 17.86925 | -1.0156 | 28.39829 |
December | 497.00000 | 19.68917 | 13.58219 | -1.1168 | 32.65691 |
Annual Sum or Average | 5943.00000 | 21.62914 | 25.93982 | -0.8347 | 22.34167 |
Minimum of Months | 454.00000 | 19.54897 | 13.58219 | -1.1451 | 9.02847 |
Maximum of Months | 514.00000 | 24.26193 | 42.49132 | -0.4221 | 34.19014 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.74032 | 16.67797 | -1.1069 | 32.43962 |
February | 454.00000 | 19.91534 | 19.84578 | -1.0091 | 28.43331 |
March | 514.00000 | 20.68089 | 22.06821 | -0.7255 | 17.86392 |
April | 485.00000 | 22.40634 | 20.27399 | -0.2181 | 9.30476 |
May | 508.00000 | 24.11203 | 22.20696 | -0.5601 | 13.20322 |
June | 496.00000 | 24.30798 | 33.64705 | -0.3662 | 8.61191 |
July | 497.00000 | 24.48792 | 41.42872 | -0.2346 | 7.34890 |
August | 514.00000 | 24.25297 | 37.53181 | -0.3910 | 9.10391 |
September | 485.00000 | 23.40923 | 31.61701 | -0.8465 | 23.24766 |
October | 502.00000 | 21.22384 | 27.72514 | -0.5095 | 12.55879 |
November | 489.00000 | 19.93172 | 18.64837 | -1.0041 | 27.92647 |
December | 497.00000 | 19.79392 | 13.92283 | -1.1040 | 32.10550 |
Annual Sum or Average | 5943.00000 | 22.03979 | 25.52595 | -0.6701 | 18.40669 |
Minimum of Months | 454.00000 | 19.74032 | 13.92283 | -1.1069 | 7.34890 |
Maximum of Months | 514.00000 | 24.48792 | 41.42872 | -0.2181 | 32.43962 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.46722 | 14.81069 | -1.5277 | 50.77378 |
February | 454.00000 | 18.67087 | 16.51190 | -1.2059 | 36.87604 |
March | 514.00000 | 19.85215 | 17.17139 | -0.8424 | 23.14154 |
April | 485.00000 | 22.23267 | 16.90538 | -0.1890 | 10.36986 |
May | 508.00000 | 23.52475 | 22.21614 | -0.7516 | 20.16767 |
June | 496.00000 | 24.03762 | 33.91501 | -0.4711 | 11.24602 |
July | 497.00000 | 24.23981 | 41.80437 | -0.3335 | 9.19313 |
August | 514.00000 | 23.98484 | 37.45064 | -0.4433 | 11.67527 |
September | 485.00000 | 22.88901 | 29.56619 | -0.9428 | 28.50446 |
October | 502.00000 | 20.71852 | 23.41013 | -0.5837 | 15.84382 |
November | 489.00000 | 18.12113 | 15.14848 | -1.3319 | 42.24602 |
December | 497.00000 | 17.17074 | 12.20169 | -1.6063 | 54.08801 |
Annual Sum or Average | 5943.00000 | 21.09668 | 23.49890 | -0.8494 | 26.05854 |
Minimum of Months | 454.00000 | 17.17074 | 12.20169 | -1.6063 | 9.19313 |
Maximum of Months | 514.00000 | 24.23981 | 41.80437 | -0.1890 | 54.08801 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73579 | 16.58618 | -1.1111 | 32.61446 |
February | 454.00000 | 19.85105 | 19.67850 | -1.0381 | 29.68880 |
March | 514.00000 | 20.41019 | 22.12539 | -0.8250 | 20.89884 |
April | 485.00000 | 22.19977 | 20.55404 | -0.2676 | 9.88650 |
May | 508.00000 | 23.73037 | 24.00534 | -0.7662 | 18.96372 |
June | 496.00000 | 24.24633 | 34.29847 | -0.4374 | 9.81672 |
July | 497.00000 | 24.34975 | 42.40387 | -0.3497 | 8.25448 |
August | 514.00000 | 24.14331 | 38.48114 | -0.4748 | 10.63766 |
September | 485.00000 | 23.05666 | 32.60163 | -0.9808 | 27.98531 |
October | 502.00000 | 20.91706 | 28.16691 | -0.5933 | 14.04153 |
November | 489.00000 | 19.93435 | 18.62389 | -1.0036 | 27.90692 |
December | 497.00000 | 19.79528 | 13.89895 | -1.1044 | 32.11921 |
Annual Sum or Average | 5943.00000 | 21.88106 | 26.01862 | -0.7438 | 20.14008 |
Minimum of Months | 454.00000 | 19.73579 | 13.89895 | -1.1111 | 8.25448 |
Maximum of Months | 514.00000 | 24.34975 | 42.40387 | -0.2676 | 32.61446 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78556 | 18.79504 | -1.0411 | 29.86412 |
February | 454.00000 | 19.92131 | 21.72700 | -0.9553 | 26.56161 |
March | 514.00000 | 20.46204 | 22.74442 | -0.7650 | 18.78542 |
April | 485.00000 | 22.04541 | 20.12707 | -0.3078 | 9.89997 |
May | 508.00000 | 23.94510 | 22.44063 | -0.6897 | 15.60059 |
June | 496.00000 | 24.30032 | 33.62256 | -0.4188 | 9.11498 |
July | 497.00000 | 24.39899 | 41.75687 | -0.3410 | 7.99950 |
August | 514.00000 | 24.05208 | 38.34292 | -0.5365 | 11.79995 |
September | 485.00000 | 22.70176 | 33.06541 | -1.1115 | 33.03859 |
October | 502.00000 | 20.70838 | 28.90502 | -0.6409 | 15.52644 |
November | 489.00000 | 19.83888 | 20.35737 | -1.0009 | 28.16509 |
December | 497.00000 | 19.78066 | 15.41060 | -1.0660 | 30.68238 |
Annual Sum or Average | 5943.00000 | 21.84594 | 26.49341 | -0.7374 | 19.65924 |
Minimum of Months | 454.00000 | 19.78066 | 15.41060 | -1.1115 | 7.99950 |
Maximum of Months | 514.00000 | 24.39899 | 41.75687 | -0.3078 | 33.03859 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.63541 | 18.88964 | -1.0748 | 31.42385 |
February | 385.00000 | 19.87123 | 22.34497 | -0.9489 | 26.37606 |
March | 433.00000 | 20.91259 | 23.04196 | -0.6197 | 15.51568 |
April | 410.00000 | 22.78805 | 18.63572 | -0.1027 | 8.73761 |
May | 430.00000 | 24.30209 | 21.12650 | -0.4647 | 11.60248 |
June | 418.00000 | 24.44243 | 32.99686 | -0.2948 | 8.08653 |
July | 422.00000 | 24.61762 | 40.93388 | -0.1862 | 7.47727 |
August | 433.00000 | 24.27477 | 37.09125 | -0.3914 | 9.49662 |
September | 410.00000 | 23.22811 | 31.87169 | -0.9094 | 26.17946 |
October | 427.00000 | 20.93022 | 29.25494 | -0.5747 | 14.47825 |
November | 417.00000 | 19.67747 | 20.85147 | -1.0334 | 29.65985 |
December | 422.00000 | 19.60583 | 15.51051 | -1.1061 | 32.55818 |
Annual Sum or Average | 5034.00000 | 22.03801 | 26.08223 | -0.6400 | 18.38174 |
Minimum of Months | 385.00000 | 19.60583 | 15.51051 | -1.1061 | 7.47727 |
Maximum of Months | 433.00000 | 24.61762 | 40.93388 | -0.1027 | 32.55818 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.90024 | 18.90136 | -0.9948 | 28.06437 |
February | 454.00000 | 20.56978 | 21.19972 | -0.7550 | 20.24266 |
March | 514.00000 | 21.61874 | 20.89938 | -0.4212 | 13.15713 |
April | 485.00000 | 23.17376 | 17.27348 | 0.03501 | 9.18234 |
May | 508.00000 | 24.11260 | 21.29142 | -0.5305 | 13.35378 |
June | 496.00000 | 24.32700 | 33.11130 | -0.3393 | 8.56353 |
July | 497.00000 | 24.45623 | 41.20604 | -0.2432 | 7.70186 |
August | 514.00000 | 24.22575 | 37.05180 | -0.3726 | 9.75373 |
September | 485.00000 | 23.38938 | 30.66692 | -0.8131 | 22.94258 |
October | 502.00000 | 21.45671 | 27.50972 | -0.4325 | 12.26763 |
November | 489.00000 | 20.06183 | 20.32131 | -0.9194 | 25.16520 |
December | 497.00000 | 19.84461 | 15.52975 | -1.0457 | 29.83291 |
Annual Sum or Average | 5943.00000 | 22.27666 | 25.46443 | -0.5675 | 16.62214 |
Minimum of Months | 454.00000 | 19.84461 | 15.52975 | -1.0457 | 7.70186 |
Maximum of Months | 514.00000 | 24.45623 | 41.20604 | 0.03501 | 29.83291 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83903 | 19.37852 | -1.0312 | 29.43994 |
February | 454.00000 | 19.98256 | 22.59614 | -0.9321 | 25.68255 |
March | 514.00000 | 20.70490 | 23.48759 | -0.6880 | 17.10974 |
April | 485.00000 | 22.63565 | 19.42840 | -0.1297 | 9.34397 |
May | 508.00000 | 24.02396 | 22.39576 | -0.6146 | 14.58485 |
June | 496.00000 | 24.34289 | 33.68501 | -0.3554 | 8.67501 |
July | 497.00000 | 24.42872 | 41.89338 | -0.2916 | 7.77681 |
August | 514.00000 | 24.13059 | 38.25150 | -0.4638 | 10.71109 |
September | 485.00000 | 22.95677 | 32.93670 | -1.0056 | 29.30597 |
October | 502.00000 | 20.81447 | 29.78075 | -0.6084 | 14.94873 |
November | 489.00000 | 19.87616 | 21.22460 | -0.9882 | 27.67547 |
December | 497.00000 | 19.81951 | 15.99968 | -1.0604 | 30.45264 |
Annual Sum or Average | 5943.00000 | 21.97997 | 26.80533 | -0.6785 | 18.71670 |
Minimum of Months | 454.00000 | 19.81951 | 15.99968 | -1.0604 | 7.77681 |
Maximum of Months | 514.00000 | 24.42872 | 41.89338 | -0.1297 | 30.45264 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.178423E+12 | 0.00 | 605.29 | 296186.77 | 12-JAN-07:12 | 0.00 | 43.84 | 56.85 | 1.00 | 0.00 | 0.15 | 0.65 | 12-JAN-07:12 |
February | 0.115827E+12 | 0.00 | 520.15 | 296050.97 | 27-FEB-07:55 | 0.00 | 42.82 | 56.04 | 0.71 | 0.00 | 0.10 | 0.65 | 27-FEB-07:55 |
March | 0.621082E+11 | 0.00 | 493.10 | 275329.34 | 01-MAR-07:15 | 0.00 | 38.47 | 52.06 | 0.32 | 0.00 | 0.05 | 0.60 | 01-MAR-07:15 |
April | 0.103554E+11 | 0.00 | 259.55 | 237474.67 | 17-APR-05:01 | 0.00 | 36.53 | 44.66 | 0.05 | 0.00 | 0.01 | 0.52 | 17-APR-05:01 |
May | 0.807078E+09 | 0.00 | 56.15 | 15943.95 | 30-MAY-06:05 | 0.00 | 43.82 | 45.12 | 0.00 | 0.00 | 0.00 | 0.03 | 30-MAY-06:05 |
June | 0.161042E+09 | 0.00 | 29.35 | 11911.65 | 15-JUN-06:06 | 0.00 | 43.30 | 44.03 | 0.00 | 0.00 | 0.00 | 0.03 | 15-JUN-06:06 |
July | 0.122487E+09 | 0.00 | 46.53 | 13424.42 | 05-JUL-06:05 | 0.00 | 42.42 | 43.52 | 0.00 | 0.00 | 0.00 | 0.03 | 05-JUL-06:05 |
August | 0.373956E+09 | 0.00 | 37.96 | 56394.85 | 31-AUG-06:02 | 0.00 | 43.25 | 44.08 | 0.00 | 0.00 | 0.00 | 0.12 | 31-AUG-06:02 |
September | 0.338852E+10 | 0.00 | 172.57 | 195742.60 | 27-SEP-06:02 | 0.00 | 38.98 | 44.27 | 0.02 | 0.00 | 0.00 | 0.43 | 27-SEP-06:02 |
October | 0.369184E+11 | 0.00 | 414.36 | 213149.95 | 20-OCT-05:01 | 0.00 | 34.99 | 47.44 | 0.18 | 0.00 | 0.03 | 0.47 | 20-OCT-05:01 |
November | 0.146201E+12 | 0.00 | 571.62 | 277636.36 | 27-NOV-07:11 | 0.00 | 43.79 | 56.57 | 0.85 | 0.00 | 0.12 | 0.61 | 27-NOV-07:11 |
December | 0.196141E+12 | 0.00 | 615.01 | 285333.23 | 15-DEC-07:25 | 0.00 | 44.11 | 57.00 | 1.14 | 0.00 | 0.16 | 0.63 | 15-DEC-07:25 |
Annual Sum or Average | 0.750826E+12 | 0.00 | 3821.64 | 0.00 | 41.36 | 49.27 | 0.35 | 0.00 | 0.05 | ||||
Minimum of Months | 0.122487E+09 | 0.00 | 29.35 | 11911.65 | 0.00 | 34.99 | 43.52 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.196141E+12 | 0.00 | 615.01 | 296186.77 | 0.00 | 44.11 | 57.00 | 1.14 | 0.00 | 0.16 | 0.65 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 3920017.34 | 1036651.15 | 0.90 | 3920017.34 | 0.00 | 0.00 | 0.30 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 6704.31 | 19-JAN-07:01 | 6704.31 | 19-JAN-07:01 | 0.00 | 05-JAN-07:11 | 1702.18 | 19-JAN-07:01 | 0.00 |
February | 5907676.62 | 1586272.32 | 3.21 | 5731697.21 | 175979.41 | 0.00 | 0.30 | 07-FEB-07:01 | 0.00 | 01-FEB-00:10 | 6768.27 | 07-FEB-07:01 | 6768.27 | 07-FEB-07:01 | 76.35 | 09-FEB-13:01 | 1717.31 | 07-FEB-07:01 | 0.00 |
March | 20543412.56 | 5541032.79 | 9.86 | 20109286.62 | 434125.95 | 0.00 | 0.13 | 18-MAR-06:03 | 0.00 | 01-MAR-00:05 | 2819.75 | 18-MAR-06:03 | 2819.75 | 18-MAR-06:03 | 168.05 | 21-MAR-17:13 | 745.21 | 18-MAR-06:03 | 0.00 |
April | 0.254399E+10 | 0.607262E+09 | 101.88 | 0.254375E+10 | 246035.48 | 0.00 | 0.98 | 21-APR-16:00 | 0.00 | 01-APR-00:10 | 26562.89 | 21-APR-16:00 | 26562.89 | 21-APR-16:00 | 207.97 | 29-APR-06:10 | 5615.49 | 21-APR-16:00 | 0.00 |
May | 0.605972E+10 | 0.144981E+10 | 200.84 | 0.604325E+10 | 16463924.00 | 0.00 | 1.00 | 31-MAY-14:05 | 0.00 | 01-MAY-00:10 | 37088.99 | 31-MAY-16:00 | 37088.99 | 31-MAY-16:00 | 424.09 | 14-MAY-15:00 | 7784.36 | 31-MAY-16:00 | 0.00 |
June | 0.203208E+11 | 0.455382E+10 | 318.16 | 0.194842E+11 | 0.836568E+09 | 0.00 | 1.00 | 09-JUN-12:05 | 0.00 | 01-JUN-00:10 | 61330.00 | 30-JUN-14:30 | 56402.75 | 20-JUN-15:50 | 15685.94 | 30-JUN-06:02 | 14172.02 | 30-JUN-14:30 | 0.00 |
July | 0.289050E+11 | 0.634604E+10 | 338.68 | 0.266282E+11 | 0.227678E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 64342.43 | 11-JUL-15:40 | 61544.03 | 12-JUL-16:00 | 34352.36 | 03-JUL-15:00 | 14252.66 | 11-JUL-16:00 | 0.00 |
August | 0.169721E+11 | 0.379339E+10 | 282.31 | 0.158860E+11 | 0.108609E+10 | 0.00 | 1.00 | 01-AUG-13:00 | 0.00 | 01-AUG-00:10 | 59660.43 | 11-AUG-15:50 | 59660.43 | 11-AUG-15:50 | 7963.81 | 03-AUG-15:00 | 13030.35 | 11-AUG-16:00 | 0.00 |
September | 0.524854E+10 | 0.124952E+10 | 174.53 | 0.506043E+10 | 0.188108E+09 | 0.00 | 1.00 | 07-SEP-14:20 | 0.00 | 01-SEP-00:10 | 30483.77 | 07-SEP-16:00 | 30483.77 | 07-SEP-16:00 | 1572.91 | 05-SEP-16:04 | 6400.48 | 07-SEP-16:00 | 0.00 |
October | 50401342.05 | 13484149.75 | 17.42 | 48225530.85 | 2175811.20 | 0.00 | 0.18 | 05-OCT-14:10 | 0.00 | 01-OCT-00:10 | 3918.02 | 05-OCT-14:10 | 3918.02 | 05-OCT-14:10 | 200.21 | 03-OCT-06:03 | 1023.63 | 05-OCT-14:10 | 0.00 |
November | 2902143.84 | 777138.89 | 1.34 | 2876945.62 | 25198.22 | 0.00 | 0.19 | 15-NOV-07:01 | 0.00 | 01-NOV-00:10 | 4111.75 | 15-NOV-07:01 | 4111.75 | 15-NOV-07:01 | 16.52 | 02-NOV-16:00 | 1072.08 | 15-NOV-07:01 | 0.00 |
December | 2273236.48 | 603426.75 | 0.42 | 2273236.48 | 0.00 | 0.00 | 0.22 | 29-DEC-07:01 | 0.00 | 01-DEC-00:05 | 4809.37 | 29-DEC-07:01 | 4809.37 | 29-DEC-07:01 | 0.00 | 23-DEC-07:03 | 1244.94 | 29-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.801360E+11 | 0.180229E+11 | 1449.55 | 0.757289E+11 | 0.440707E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2273236.48 | 603426.75 | 0.42 | 2273236.48 | 0.00 | 0.00 | 0.13 | 0.00 | 2819.75 | 2819.75 | 0.00 | 745.21 | 0.00 | ||||||
Maximum of Months | 0.289050E+11 | 0.634604E+10 | 338.68 | 0.266282E+11 | 0.227678E+10 | 0.00 | 1.00 | 0.00 | 64342.43 | 61544.03 | 34352.36 | 14252.66 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 5277805.70 | 1372091.08 | 0.50 | 5277805.70 | 0.00 | 0.00 | 0.28 | 19-JAN-07:11 | 0.00 | 01-JAN-00:02 | 6027.61 | 19-JAN-07:11 | 6027.61 | 19-JAN-07:11 | 0.00 | 06-JAN-07:01 | 1535.25 | 19-JAN-07:11 | 0.00 |
February | 6063631.50 | 1555980.30 | 0.65 | 6024295.45 | 39336.05 | 0.00 | 0.38 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 8314.17 | 09-FEB-07:01 | 8314.17 | 09-FEB-07:01 | 73.06 | 08-FEB-13:01 | 2066.78 | 09-FEB-07:01 | 0.00 |
March | 13259086.12 | 3465724.38 | 4.39 | 13117325.06 | 141761.05 | 0.00 | 0.43 | 21-MAR-06:01 | 0.00 | 01-MAR-00:05 | 9482.94 | 21-MAR-06:01 | 9482.94 | 21-MAR-06:01 | 76.80 | 22-MAR-09:10 | 2328.73 | 21-MAR-06:01 | 0.00 |
April | 0.465738E+09 | 0.117311E+09 | 58.67 | 0.465529E+09 | 209436.70 | 0.00 | 0.70 | 25-APR-15:50 | 0.00 | 01-APR-00:10 | 16659.43 | 25-APR-15:50 | 16659.43 | 25-APR-15:50 | 61.90 | 29-APR-09:10 | 3807.49 | 25-APR-15:50 | 0.00 |
May | 0.422810E+10 | 0.999790E+09 | 161.88 | 0.421650E+10 | 11603704.36 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 37453.38 | 31-MAY-16:00 | 37453.38 | 31-MAY-16:00 | 382.15 | 14-MAY-15:05 | 7859.65 | 31-MAY-16:00 | 0.00 |
June | 0.201830E+11 | 0.450844E+10 | 325.85 | 0.193494E+11 | 0.833566E+09 | 0.00 | 1.00 | 04-JUN-14:42 | 0.00 | 01-JUN-00:10 | 64767.20 | 30-JUN-12:05 | 56539.80 | 29-JUN-14:05 | 16676.93 | 30-JUN-06:02 | 14256.72 | 30-JUN-12:05 | 0.00 |
July | 0.270192E+11 | 0.594119E+10 | 347.00 | 0.248654E+11 | 0.215380E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 60445.25 | 11-JUL-15:30 | 57089.05 | 21-JUL-14:05 | 31878.84 | 03-JUL-15:00 | 13299.77 | 11-JUL-16:00 | 0.00 |
August | 0.146386E+11 | 0.328062E+10 | 272.10 | 0.135766E+11 | 0.106199E+10 | 0.00 | 1.00 | 01-AUG-12:40 | 0.00 | 01-AUG-00:10 | 54804.23 | 11-AUG-15:20 | 54804.23 | 11-AUG-15:20 | 7034.64 | 04-AUG-10:40 | 11771.14 | 11-AUG-15:40 | 0.00 |
September | 0.507592E+09 | 0.129288E+09 | 57.78 | 0.486531E+09 | 21061368.54 | 0.00 | 0.69 | 07-SEP-12:04 | 0.00 | 01-SEP-00:10 | 16414.20 | 07-SEP-12:04 | 16414.20 | 07-SEP-12:04 | 533.21 | 02-SEP-17:55 | 3760.35 | 07-SEP-12:04 | 0.00 |
October | 64221229.25 | 16658713.21 | 7.70 | 62183871.24 | 2037358.00 | 0.00 | 0.42 | 18-OCT-06:01 | 0.00 | 01-OCT-00:10 | 9313.38 | 18-OCT-06:01 | 9313.38 | 18-OCT-06:01 | 307.71 | 03-OCT-06:03 | 2291.12 | 18-OCT-06:01 | 0.00 |
November | 4751974.15 | 1239745.58 | 0.60 | 4751974.15 | -0.0 | 0.00 | 0.28 | 04-NOV-06:03 | 0.00 | 01-NOV-00:10 | 6009.41 | 04-NOV-06:03 | 6009.41 | 04-NOV-06:03 | 0.00 | 02-NOV-06:01 | 1530.92 | 04-NOV-06:03 | 0.00 |
December | 3596013.61 | 956607.77 | 0.84 | 3590929.89 | 5083.72 | 0.00 | 0.18 | 21-DEC-07:11 | 0.00 | 01-DEC-00:05 | 3727.83 | 21-DEC-07:11 | 3727.83 | 21-DEC-07:11 | 8.36 | 23-DEC-14:10 | 973.59 | 21-DEC-07:11 | 0.00 |
Annual Sum or Average | 0.671394E+11 | 0.150019E+11 | 1237.96 | 0.630550E+11 | 0.408446E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 3596013.61 | 956607.77 | 0.50 | 3590929.89 | -0.0 | 0.00 | 0.18 | 0.00 | 3727.83 | 3727.83 | 0.00 | 973.59 | 0.00 | ||||||
Maximum of Months | 0.270192E+11 | 0.594119E+10 | 347.00 | 0.248654E+11 | 0.215380E+10 | 0.00 | 1.00 | 0.00 | 64767.20 | 57089.05 | 31878.84 | 14256.72 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2019319.21 | 545440.54 | 0.90 | 2019319.21 | 0.00 | 0.00 | 0.08 | 19-JAN-07:11 | 0.00 | 01-JAN-00:02 | 1691.41 | 19-JAN-07:11 | 1691.41 | 19-JAN-07:11 | 0.00 | 02-JAN-06:40 | 452.65 | 19-JAN-07:11 | 0.00 |
February | 1835220.85 | 493450.46 | 0.91 | 1816875.86 | 18344.99 | 0.00 | 0.16 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 3686.55 | 09-FEB-07:01 | 3686.55 | 09-FEB-07:01 | 39.03 | 09-FEB-12:17 | 966.68 | 09-FEB-07:01 | 0.00 |
March | 4042724.20 | 1091261.15 | 3.49 | 3899369.45 | 143354.75 | 0.00 | 0.19 | 23-MAR-06:01 | 0.00 | 01-MAR-00:05 | 4345.69 | 23-MAR-06:01 | 4345.69 | 23-MAR-06:01 | 48.93 | 22-MAR-10:40 | 1131.96 | 23-MAR-06:01 | 0.00 |
April | 0.872535E+09 | 0.211796E+09 | 71.95 | 0.871687E+09 | 847907.73 | 0.00 | 0.93 | 21-APR-14:10 | 0.00 | 01-APR-00:10 | 25728.69 | 21-APR-14:10 | 25728.69 | 21-APR-14:10 | 57.38 | 19-APR-06:03 | 5516.36 | 21-APR-14:10 | 0.00 |
May | 0.410337E+10 | 0.977390E+09 | 165.73 | 0.408437E+10 | 19000175.61 | 0.00 | 1.00 | 12-MAY-13:00 | 0.00 | 01-MAY-00:10 | 38926.35 | 31-MAY-16:00 | 38926.35 | 31-MAY-16:00 | 532.72 | 31-MAY-06:02 | 8169.71 | 31-MAY-16:00 | 0.00 |
June | 0.204598E+11 | 0.459772E+10 | 322.07 | 0.195972E+11 | 0.862595E+09 | 0.00 | 1.00 | 12-JUN-12:50 | 0.00 | 01-JUN-00:10 | 67300.40 | 30-JUN-12:30 | 61125.23 | 29-JUN-14:30 | 14184.31 | 30-JUN-06:02 | 15084.38 | 30-JUN-14:30 | 0.00 |
July | 0.274544E+11 | 0.606867E+10 | 345.45 | 0.252798E+11 | 0.217458E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 66405.71 | 23-JUL-14:21 | 66405.71 | 23-JUL-14:21 | 31294.68 | 03-JUL-15:00 | 14422.49 | 23-JUL-14:21 | 0.00 |
August | 0.143789E+11 | 0.324750E+10 | 268.67 | 0.132466E+11 | 0.113232E+10 | 0.00 | 1.00 | 02-AUG-12:05 | 0.00 | 01-AUG-00:10 | 57074.56 | 11-AUG-15:50 | 57074.56 | 11-AUG-15:50 | 6859.20 | 03-AUG-14:40 | 12432.70 | 11-AUG-15:50 | 0.00 |
September | 0.112088E+10 | 0.271249E+09 | 60.63 | 0.109214E+10 | 28741965.87 | 0.00 | 0.88 | 07-SEP-15:20 | 0.00 | 01-SEP-00:10 | 23939.64 | 07-SEP-15:20 | 23939.64 | 07-SEP-15:20 | 858.78 | 09-SEP-16:10 | 5209.88 | 07-SEP-15:20 | 0.00 |
October | 55821273.52 | 14582976.33 | 7.90 | 52373300.61 | 3447972.91 | 0.00 | 0.28 | 02-OCT-06:03 | 0.00 | 01-OCT-00:10 | 6468.86 | 02-OCT-06:03 | 6468.86 | 02-OCT-06:03 | 321.16 | 03-OCT-15:20 | 1649.81 | 02-OCT-06:03 | 0.00 |
November | 1142847.18 | 308957.58 | 0.56 | 1140953.94 | 1893.23 | 0.00 | 0.05 | 13-NOV-06:40 | 0.00 | 01-NOV-00:10 | 1010.15 | 13-NOV-06:40 | 1010.15 | 13-NOV-06:40 | 18.93 | 02-NOV-04:07 | 272.25 | 13-NOV-06:40 | 0.00 |
December | 2111713.43 | 570548.67 | 0.82 | 2111713.43 | -0.0 | 0.00 | 0.05 | 01-DEC-06:20 | 0.00 | 01-DEC-00:05 | 1038.45 | 01-DEC-06:20 | 1038.45 | 01-DEC-06:20 | 0.00 | 09-DEC-06:20 | 279.79 | 01-DEC-06:20 | 0.00 |
Annual Sum or Average | 0.684569E+11 | 0.153919E+11 | 1249.09 | 0.642352E+11 | 0.422170E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1142847.18 | 308957.58 | 0.56 | 1140953.94 | -0.0 | 0.00 | 0.05 | 0.00 | 1010.15 | 1010.15 | 0.00 | 272.25 | 0.00 | ||||||
Maximum of Months | 0.274544E+11 | 0.606867E+10 | 345.45 | 0.252798E+11 | 0.217458E+10 | 0.00 | 1.00 | 0.00 | 67300.40 | 66405.71 | 31294.68 | 15084.38 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 2955.23 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2638.69 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 44.03 | 1943.73 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 357.40 | 1041.88 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1023.98 | 475.65 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1699.15 | 222.28 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1457.53 | 271.00 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 758.62 | 449.10 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 200.82 | 888.49 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 21.06 | 1644.18 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2890.32 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3114.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 466.25 | 1538.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 222.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1699.15 | 3114.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.29 | 1912.79 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 211.13 | 1591.14 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 960.81 | 1164.92 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1438.07 | 647.64 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2468.58 | 346.53 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2344.36 | 171.37 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2283.17 | 196.14 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1729.97 | 305.36 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 898.53 | 563.20 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 369.30 | 998.36 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.92 | 1855.59 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2065.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1065.67 | 981.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 171.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2468.58 | 2065.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 291.45 | 2655.52 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1449.13 | 2128.44 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2856.36 | 1631.04 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3861.65 | 1082.47 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3254.62 | 602.28 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3049.46 | 324.94 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3013.08 | 345.24 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3085.92 | 505.24 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2274.20 | 864.12 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1425.14 | 1388.97 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 558.74 | 2470.83 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 26.46 | 2962.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2097.10 | 1410.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 26.46 | 324.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3861.65 | 2962.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1950.63 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 46.23 | 1654.07 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 386.60 | 1190.74 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1522.70 | 694.12 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1561.65 | 367.61 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1860.37 | 200.26 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1568.66 | 216.55 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1223.60 | 321.16 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 577.82 | 575.50 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 105.68 | 1040.23 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 12.10 | 1851.08 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2072.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 741.69 | 1007.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 200.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1860.37 | 2072.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 987.93 | 0.00 | 0.00 | 0.00 |
February | 58.88 | 0.00 | 58.88 | 0.00 | 879.16 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.38 | 648.90 | 0.00 | 0.00 | 0.00 |
April | 284.56 | 5.89 | 278.67 | 128.02 | 344.42 | 0.00 | 0.00 | 0.00 |
May | 435.34 | 68.05 | 367.28 | 354.77 | 153.73 | 0.00 | 0.00 | 0.00 |
June | 568.86 | 125.78 | 443.08 | 577.44 | 71.68 | 0.00 | 0.00 | 0.00 |
July | 477.28 | 76.79 | 400.49 | 492.44 | 89.40 | 0.00 | 0.00 | 0.00 |
August | 304.74 | 16.45 | 288.30 | 253.41 | 153.38 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.94 | 316.66 | 0.00 | 0.00 | 0.00 |
October | 82.89 | 0.00 | 82.89 | 5.48 | 578.85 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.75 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1048.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.06 | 24.53 | 191.52 | 158.41 | 519.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 71.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.86 | 125.78 | 443.08 | 577.44 | 1048.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 987.99 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 879.22 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.38 | 648.94 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 128.02 | 344.44 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 354.77 | 153.74 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 577.46 | 71.69 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 492.46 | 89.41 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 253.41 | 153.39 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.94 | 316.68 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.48 | 578.89 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.81 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1048.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 158.41 | 519.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 71.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 577.46 | 1048.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.32 | 0.00 | 13.32 | 0.00 | 987.99 | 0.00 | 0.00 | 0.00 |
February | 58.89 | 0.00 | 58.89 | 0.00 | 879.22 | 0.00 | 0.00 | 0.00 |
March | 157.49 | 0.00 | 157.49 | 15.38 | 648.94 | 0.00 | 0.00 | 0.00 |
April | 284.57 | 5.89 | 278.68 | 128.02 | 344.44 | 0.00 | 0.00 | 0.00 |
May | 435.35 | 68.06 | 367.30 | 354.77 | 153.74 | 0.00 | 0.00 | 0.00 |
June | 568.88 | 125.78 | 443.09 | 577.46 | 71.69 | 0.00 | 0.00 | 0.00 |
July | 477.29 | 76.79 | 400.50 | 492.46 | 89.41 | 0.00 | 0.00 | 0.00 |
August | 304.76 | 16.45 | 288.31 | 253.41 | 153.39 | 0.00 | 0.00 | 0.00 |
September | 170.34 | 0.15 | 170.19 | 62.94 | 316.68 | 0.00 | 0.00 | 0.00 |
October | 82.90 | 0.00 | 82.90 | 5.48 | 578.89 | 0.00 | 0.00 | 0.00 |
November | 25.73 | 0.00 | 25.73 | 0.00 | 984.81 | 0.00 | 0.00 | 0.00 |
December | 4.04 | 0.00 | 4.04 | 0.00 | 1048.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 216.07 | 24.53 | 191.53 | 158.41 | 519.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 4.04 | 0.00 | 4.04 | 0.00 | 71.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 568.88 | 125.78 | 443.09 | 577.46 | 1048.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 66.88 | 20.62 | 46.27 | 6.25 | 1847.18 | 0.00 | 0.00 | 0.00 |
February | 372.10 | 177.07 | 195.03 | 204.14 | 1534.44 | 0.00 | 0.00 | 0.00 |
March | 1065.35 | 540.18 | 525.17 | 931.65 | 1131.14 | 0.00 | 0.00 | 0.00 |
April | 1465.12 | 742.49 | 722.63 | 1395.09 | 634.24 | 0.00 | 0.00 | 0.00 |
May | 2131.40 | 1202.84 | 928.56 | 2389.21 | 338.56 | 0.00 | 0.00 | 0.00 |
June | 1959.17 | 915.12 | 1044.05 | 2270.72 | 164.93 | 0.00 | 0.00 | 0.00 |
July | 1861.37 | 903.79 | 957.57 | 2205.20 | 193.19 | 0.00 | 0.00 | 0.00 |
August | 1473.91 | 718.49 | 755.43 | 1665.67 | 307.86 | 0.00 | 0.00 | 0.00 |
September | 910.99 | 399.47 | 511.52 | 852.94 | 587.50 | 0.00 | 0.00 | 0.00 |
October | 480.30 | 192.58 | 287.72 | 346.97 | 1024.18 | 0.00 | 0.00 | 0.00 |
November | 101.41 | 34.91 | 66.50 | 8.33 | 1823.54 | 0.00 | 0.00 | 0.00 |
December | 14.42 | 3.31 | 11.11 | 0.00 | 2005.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 995.68 | 489.74 | 505.94 | 1028.55 | 963.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.42 | 3.31 | 11.11 | 0.00 | 164.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2131.40 | 1202.84 | 1044.05 | 2389.21 | 2005.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.64 | 0.82 | 1.83 | 0.25 | 73.04 | 0.00 | 0.00 | 0.00 |
February | 14.71 | 7.00 | 7.71 | 8.07 | 60.67 | 0.00 | 0.00 | 0.00 |
March | 42.12 | 21.36 | 20.76 | 36.84 | 44.72 | 0.00 | 0.00 | 0.00 |
April | 57.93 | 29.36 | 28.57 | 55.16 | 25.08 | 0.00 | 0.00 | 0.00 |
May | 84.27 | 47.56 | 36.71 | 94.47 | 13.39 | 0.00 | 0.00 | 0.00 |
June | 77.46 | 36.18 | 41.28 | 89.78 | 6.52 | 0.00 | 0.00 | 0.00 |
July | 73.60 | 35.74 | 37.86 | 87.19 | 7.64 | 0.00 | 0.00 | 0.00 |
August | 58.28 | 28.41 | 29.87 | 65.86 | 12.17 | 0.00 | 0.00 | 0.00 |
September | 36.02 | 15.79 | 20.22 | 33.72 | 23.23 | 0.00 | 0.00 | 0.00 |
October | 18.99 | 7.61 | 11.38 | 13.72 | 40.50 | 0.00 | 0.00 | 0.00 |
November | 4.01 | 1.38 | 2.63 | 0.33 | 72.10 | 0.00 | 0.00 | 0.00 |
December | 0.57 | 0.13 | 0.44 | 0.00 | 79.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.37 | 19.36 | 20.00 | 40.67 | 38.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.57 | 0.13 | 0.44 | 0.00 | 6.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 84.27 | 47.56 | 41.28 | 94.47 | 79.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 101.10 | 856.07 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 492.41 | 697.37 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 968.95 | 543.66 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1299.01 | 373.01 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1096.91 | 203.56 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1027.32 | 108.59 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1011.60 | 118.03 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.05 | 178.01 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 757.80 | 310.33 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.58 | 488.51 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 190.39 | 818.51 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 10.70 | 954.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.74 | 469.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 10.70 | 108.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1299.01 | 954.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.94 | 106.42 | 54.52 | 101.10 | 856.07 | 0.00 | 0.00 | 0.00 |
February | 553.55 | 386.16 | 167.39 | 492.41 | 697.37 | 0.00 | 0.00 | 0.00 |
March | 948.30 | 644.05 | 304.25 | 968.95 | 543.66 | 0.00 | 0.00 | 0.00 |
April | 1154.14 | 718.78 | 435.36 | 1299.01 | 373.01 | 0.00 | 0.00 | 0.00 |
May | 948.19 | 490.45 | 457.73 | 1096.91 | 203.56 | 0.00 | 0.00 | 0.00 |
June | 864.65 | 352.81 | 511.84 | 1027.32 | 108.59 | 0.00 | 0.00 | 0.00 |
July | 833.84 | 362.11 | 471.73 | 1011.60 | 118.03 | 0.00 | 0.00 | 0.00 |
August | 866.10 | 477.63 | 388.47 | 1033.05 | 178.01 | 0.00 | 0.00 | 0.00 |
September | 701.50 | 423.31 | 278.19 | 757.80 | 310.33 | 0.00 | 0.00 | 0.00 |
October | 506.22 | 322.15 | 184.07 | 473.58 | 488.51 | 0.00 | 0.00 | 0.00 |
November | 271.98 | 190.51 | 81.47 | 190.39 | 818.51 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.16 | 14.15 | 10.70 | 954.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.62 | 375.13 | 279.49 | 705.74 | 469.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.16 | 14.15 | 10.70 | 108.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.14 | 718.78 | 511.84 | 1299.01 | 954.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 160.93 | 106.41 | 54.52 | 101.09 | 856.02 | 0.00 | 0.00 | 0.00 |
February | 553.52 | 386.13 | 167.38 | 492.38 | 697.32 | 0.00 | 0.00 | 0.00 |
March | 948.24 | 644.01 | 304.23 | 968.89 | 543.63 | 0.00 | 0.00 | 0.00 |
April | 1154.06 | 718.74 | 435.33 | 1298.93 | 372.99 | 0.00 | 0.00 | 0.00 |
May | 948.13 | 490.42 | 457.70 | 1096.84 | 203.55 | 0.00 | 0.00 | 0.00 |
June | 864.60 | 352.79 | 511.81 | 1027.25 | 108.59 | 0.00 | 0.00 | 0.00 |
July | 833.78 | 362.08 | 471.70 | 1011.54 | 118.02 | 0.00 | 0.00 | 0.00 |
August | 866.05 | 477.60 | 388.45 | 1032.98 | 178.00 | 0.00 | 0.00 | 0.00 |
September | 701.46 | 423.29 | 278.17 | 757.75 | 310.32 | 0.00 | 0.00 | 0.00 |
October | 506.19 | 322.13 | 184.06 | 473.55 | 488.48 | 0.00 | 0.00 | 0.00 |
November | 271.96 | 190.50 | 81.46 | 190.38 | 818.46 | 0.00 | 0.00 | 0.00 |
December | 48.30 | 34.15 | 14.14 | 10.70 | 954.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 654.58 | 375.10 | 279.48 | 705.70 | 469.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 48.30 | 34.15 | 14.14 | 10.70 | 108.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1154.06 | 718.74 | 511.81 | 1298.93 | 954.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 35.24 | 6.06 | 29.18 | 0.00 | 1883.83 | 0.00 | 0.00 | 0.00 |
February | 208.55 | 71.81 | 136.75 | 45.41 | 1593.68 | 0.00 | 0.00 | 0.00 |
March | 628.57 | 269.82 | 358.75 | 379.88 | 1151.96 | 0.00 | 0.00 | 0.00 |
April | 1495.90 | 776.49 | 719.41 | 1480.60 | 684.01 | 0.00 | 0.00 | 0.00 |
May | 1454.71 | 664.02 | 790.69 | 1521.30 | 355.56 | 0.00 | 0.00 | 0.00 |
June | 1593.97 | 681.22 | 912.75 | 1806.69 | 192.29 | 0.00 | 0.00 | 0.00 |
July | 1333.10 | 505.35 | 827.74 | 1520.71 | 211.02 | 0.00 | 0.00 | 0.00 |
August | 1095.48 | 464.60 | 630.88 | 1179.65 | 323.87 | 0.00 | 0.00 | 0.00 |
September | 662.57 | 277.65 | 384.91 | 546.58 | 599.14 | 0.00 | 0.00 | 0.00 |
October | 258.54 | 77.16 | 181.38 | 96.87 | 1060.25 | 0.00 | 0.00 | 0.00 |
November | 103.00 | 36.93 | 66.06 | 11.24 | 1820.01 | 0.00 | 0.00 | 0.00 |
December | 9.25 | 0.91 | 8.34 | 0.00 | 2012.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.82 | 320.01 | 421.80 | 718.56 | 987.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.25 | 0.91 | 8.34 | 0.00 | 192.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1593.97 | 776.49 | 912.75 | 1806.69 | 2012.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.39 | 0.24 | 1.15 | 0.00 | 74.48 | 0.00 | 0.00 | 0.00 |
February | 8.25 | 2.84 | 5.41 | 1.80 | 63.01 | 0.00 | 0.00 | 0.00 |
March | 24.85 | 10.67 | 14.18 | 15.02 | 45.55 | 0.00 | 0.00 | 0.00 |
April | 59.15 | 30.70 | 28.44 | 58.54 | 27.05 | 0.00 | 0.00 | 0.00 |
May | 57.52 | 26.25 | 31.26 | 60.15 | 14.06 | 0.00 | 0.00 | 0.00 |
June | 63.02 | 26.93 | 36.09 | 71.43 | 7.60 | 0.00 | 0.00 | 0.00 |
July | 52.71 | 19.98 | 32.73 | 60.13 | 8.34 | 0.00 | 0.00 | 0.00 |
August | 43.31 | 18.37 | 24.94 | 46.64 | 12.81 | 0.00 | 0.00 | 0.00 |
September | 26.20 | 10.98 | 15.22 | 21.61 | 23.69 | 0.00 | 0.00 | 0.00 |
October | 10.22 | 3.05 | 7.17 | 3.83 | 41.92 | 0.00 | 0.00 | 0.00 |
November | 4.07 | 1.46 | 2.61 | 0.44 | 71.96 | 0.00 | 0.00 | 0.00 |
December | 0.37 | 0.04 | 0.33 | 0.00 | 79.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.33 | 12.65 | 16.68 | 28.41 | 39.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.37 | 0.04 | 0.33 | 0.00 | 7.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.02 | 30.70 | 36.09 | 71.43 | 79.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 39.96 | 0.00 | 39.96 | 0.00 | 3008.39 | 0.00 | 0.00 | 0.00 |
February | 176.66 | 0.00 | 176.66 | 0.00 | 2698.45 | 0.00 | 0.00 | 0.00 |
March | 472.48 | 0.00 | 472.48 | 39.91 | 2012.35 | 0.00 | 0.00 | 0.00 |
April | 853.72 | 17.68 | 836.04 | 337.71 | 1103.80 | 0.00 | 0.00 | 0.00 |
May | 1306.08 | 204.17 | 1101.90 | 1003.51 | 495.67 | 0.00 | 0.00 | 0.00 |
June | 1706.65 | 377.36 | 1329.29 | 1692.42 | 229.44 | 0.00 | 0.00 | 0.00 |
July | 1431.90 | 230.38 | 1201.52 | 1451.21 | 279.78 | 0.00 | 0.00 | 0.00 |
August | 914.28 | 49.35 | 864.93 | 746.59 | 469.83 | 0.00 | 0.00 | 0.00 |
September | 511.03 | 0.45 | 510.58 | 182.34 | 956.50 | 0.00 | 0.00 | 0.00 |
October | 248.69 | 0.00 | 248.69 | 15.65 | 1728.95 | 0.00 | 0.00 | 0.00 |
November | 77.18 | 0.00 | 77.18 | 0.00 | 2954.69 | 0.00 | 0.00 | 0.00 |
December | 12.12 | 0.00 | 12.12 | 0.00 | 3170.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 648.20 | 73.60 | 574.60 | 458.46 | 1586.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.12 | 0.00 | 12.12 | 0.00 | 229.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1706.65 | 377.36 | 1329.29 | 1692.42 | 3170.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.53 | 21.43 | 48.10 | 6.22 | 1943.57 | 0.00 | 0.00 | 0.00 |
February | 386.82 | 184.08 | 202.74 | 207.66 | 1626.21 | 0.00 | 0.00 | 0.00 |
March | 1107.49 | 561.55 | 545.95 | 948.47 | 1207.64 | 0.00 | 0.00 | 0.00 |
April | 1523.07 | 771.86 | 751.22 | 1420.12 | 681.48 | 0.00 | 0.00 | 0.00 |
May | 2215.71 | 1250.43 | 965.29 | 2458.03 | 359.13 | 0.00 | 0.00 | 0.00 |
June | 2036.67 | 951.32 | 1085.34 | 2339.07 | 176.39 | 0.00 | 0.00 | 0.00 |
July | 1935.00 | 939.55 | 995.45 | 2278.19 | 202.03 | 0.00 | 0.00 | 0.00 |
August | 1532.21 | 746.91 | 785.31 | 1722.39 | 317.36 | 0.00 | 0.00 | 0.00 |
September | 947.02 | 415.27 | 531.75 | 881.93 | 601.21 | 0.00 | 0.00 | 0.00 |
October | 499.30 | 200.20 | 299.10 | 358.66 | 1051.54 | 0.00 | 0.00 | 0.00 |
November | 105.42 | 36.29 | 69.13 | 8.61 | 1893.71 | 0.00 | 0.00 | 0.00 |
December | 14.99 | 3.44 | 11.55 | 0.00 | 2097.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1035.06 | 509.11 | 525.95 | 1058.18 | 1010.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.99 | 3.44 | 11.55 | 0.00 | 176.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.71 | 1250.43 | 1085.34 | 2458.03 | 2097.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.83 | 319.27 | 163.57 | 287.79 | 2704.85 | 0.00 | 0.00 | 0.00 |
February | 1660.68 | 1158.50 | 502.19 | 1435.55 | 2185.37 | 0.00 | 0.00 | 0.00 |
March | 2844.95 | 1932.19 | 912.76 | 2838.39 | 1693.57 | 0.00 | 0.00 | 0.00 |
April | 3462.47 | 2156.39 | 1306.08 | 3845.12 | 1136.65 | 0.00 | 0.00 | 0.00 |
May | 2844.60 | 1471.39 | 1373.21 | 3247.83 | 629.83 | 0.00 | 0.00 | 0.00 |
June | 2594.00 | 1058.45 | 1535.55 | 3048.39 | 336.61 | 0.00 | 0.00 | 0.00 |
July | 2501.55 | 1086.34 | 1415.21 | 3011.75 | 357.59 | 0.00 | 0.00 | 0.00 |
August | 2598.35 | 1432.92 | 1165.43 | 3081.47 | 527.07 | 0.00 | 0.00 | 0.00 |
September | 2104.55 | 1269.97 | 834.58 | 2254.76 | 919.74 | 0.00 | 0.00 | 0.00 |
October | 1518.69 | 966.47 | 552.22 | 1403.38 | 1464.55 | 0.00 | 0.00 | 0.00 |
November | 815.96 | 571.54 | 244.41 | 550.90 | 2531.97 | 0.00 | 0.00 | 0.00 |
December | 144.90 | 102.47 | 42.44 | 26.00 | 3015.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1963.89 | 1125.40 | 838.49 | 2087.58 | 1455.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 144.90 | 102.47 | 42.44 | 26.00 | 336.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3462.47 | 2156.39 | 1535.55 | 3845.12 | 3015.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.63 | 6.30 | 30.33 | 0.00 | 1983.87 | 0.00 | 0.00 | 0.00 |
February | 216.80 | 74.65 | 142.16 | 45.10 | 1691.68 | 0.00 | 0.00 | 0.00 |
March | 653.44 | 280.50 | 372.94 | 380.93 | 1233.95 | 0.00 | 0.00 | 0.00 |
April | 1555.07 | 807.21 | 747.86 | 1510.39 | 732.11 | 0.00 | 0.00 | 0.00 |
May | 1512.25 | 690.28 | 821.96 | 1554.76 | 385.51 | 0.00 | 0.00 | 0.00 |
June | 1657.01 | 708.17 | 948.85 | 1858.96 | 207.72 | 0.00 | 0.00 | 0.00 |
July | 1385.83 | 525.34 | 860.48 | 1567.13 | 224.58 | 0.00 | 0.00 | 0.00 |
August | 1138.81 | 482.97 | 655.83 | 1219.03 | 336.08 | 0.00 | 0.00 | 0.00 |
September | 688.77 | 288.64 | 400.14 | 565.06 | 616.75 | 0.00 | 0.00 | 0.00 |
October | 268.77 | 80.21 | 188.55 | 99.60 | 1094.41 | 0.00 | 0.00 | 0.00 |
November | 107.07 | 38.39 | 68.68 | 11.58 | 1891.47 | 0.00 | 0.00 | 0.00 |
December | 9.62 | 0.95 | 8.67 | 0.00 | 2106.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 771.16 | 332.67 | 438.49 | 737.28 | 1038.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.62 | 0.95 | 8.67 | 0.00 | 207.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.01 | 807.21 | 948.85 | 1858.96 | 2106.62 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.791529E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.638351E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.117930E+09 | 0.520608E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.926373E+09 | 0.270055E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.274263E+10 | 0.127399E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.440418E+10 | 0.576157E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.390384E+10 | 0.725838E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.203189E+10 | 0.120287E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.520519E+09 | 0.230298E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 56419422.30 | 0.440377E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.749171E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.834319E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.147038E+11 | 0.485259E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.576157E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.440418E+10 | 0.834319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16857590.31 | 0.512323E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.510755E+09 | 0.384928E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.257342E+10 | 0.312013E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.372748E+10 | 0.167869E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.661184E+10 | 0.928138E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.607657E+10 | 0.444185E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.611524E+10 | 0.525351E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.463356E+10 | 0.817868E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.232900E+10 | 0.145983E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.989146E+09 | 0.267399E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 23115069.36 | 0.480968E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.553270E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.336070E+11 | 0.309631E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.444185E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.661184E+10 | 0.553270E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.780632E+09 | 0.711256E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.350574E+10 | 0.514912E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.765046E+10 | 0.436859E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.100094E+11 | 0.280577E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.871719E+10 | 0.161314E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.790420E+10 | 0.842239E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.807022E+10 | 0.924685E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.826534E+10 | 0.135324E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.589473E+10 | 0.223980E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.381710E+10 | 0.372022E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.144825E+10 | 0.640440E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70883387.70 | 0.793370E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.661341E+11 | 0.444675E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 70883387.70 | 0.842239E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.100094E+11 | 0.793370E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.522458E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.111832E+09 | 0.400152E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.103547E+10 | 0.318927E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.394683E+10 | 0.179916E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.418272E+10 | 0.984619E+09 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.482208E+10 | 0.519079E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.420150E+10 | 0.580020E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.327730E+10 | 0.860183E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.149771E+10 | 0.149169E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.283056E+09 | 0.278617E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 31371074.34 | 0.479800E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.555075E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.233899E+11 | 0.317850E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.519079E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.482208E+10 | 0.555075E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35677821.11 | 0.00 | 35677821.11 | 0.00 | 0.264606E+10 |
February | 0.142450E+09 | 0.00 | 0.142450E+09 | 0.00 | 0.212687E+10 |
March | 0.421814E+09 | 0.00 | 0.421814E+09 | 41192235.87 | 0.173800E+10 |
April | 0.737577E+09 | 15275674.84 | 0.722302E+09 | 0.331825E+09 | 0.892733E+09 |
May | 0.116601E+10 | 0.182278E+09 | 0.983730E+09 | 0.950206E+09 | 0.411752E+09 |
June | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.149673E+10 | 0.185804E+09 |
July | 0.127834E+10 | 0.205670E+09 | 0.107267E+10 | 0.131896E+10 | 0.239452E+09 |
August | 0.816226E+09 | 44054132.18 | 0.772172E+09 | 0.678728E+09 | 0.410819E+09 |
September | 0.441512E+09 | 389190.75 | 0.441123E+09 | 0.163145E+09 | 0.820771E+09 |
October | 0.222024E+09 | 0.00 | 0.222024E+09 | 14682495.49 | 0.155040E+10 |
November | 66679304.90 | 0.00 | 66679304.90 | 0.00 | 0.255248E+10 |
December | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.280920E+10 |
Annual Sum or Average | 0.681360E+10 | 0.773689E+09 | 0.603991E+10 | 0.499546E+10 | 0.163844E+11 |
Minimum of Months | 10822788.22 | 0.00 | 10822788.22 | 0.00 | 0.185804E+09 |
Maximum of Months | 0.147447E+10 | 0.326021E+09 | 0.114845E+10 | 0.149673E+10 | 0.280920E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.264622E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.212701E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41190478.35 | 0.173812E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.331830E+09 | 0.892792E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.950229E+09 | 0.411778E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.149677E+10 | 0.185815E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.131900E+10 | 0.239467E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.678746E+09 | 0.410844E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.163146E+09 | 0.820824E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 14681865.86 | 0.155050E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.255263E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.280938E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.499559E+10 | 0.163854E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.185815E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.149677E+10 | 0.280938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35679076.65 | 0.00 | 35679076.65 | 0.00 | 0.264622E+10 |
February | 0.142456E+09 | 0.00 | 0.142456E+09 | 0.00 | 0.212701E+10 |
March | 0.421831E+09 | 0.00 | 0.421831E+09 | 41190478.35 | 0.173812E+10 |
April | 0.737606E+09 | 15276085.46 | 0.722330E+09 | 0.331830E+09 | 0.892792E+09 |
May | 0.116605E+10 | 0.182283E+09 | 0.983768E+09 | 0.950229E+09 | 0.411778E+09 |
June | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.149677E+10 | 0.185815E+09 |
July | 0.127838E+10 | 0.205676E+09 | 0.107271E+10 | 0.131900E+10 | 0.239467E+09 |
August | 0.816257E+09 | 44055316.37 | 0.772202E+09 | 0.678746E+09 | 0.410844E+09 |
September | 0.441529E+09 | 389201.21 | 0.441139E+09 | 0.163146E+09 | 0.820824E+09 |
October | 0.222032E+09 | 0.00 | 0.222032E+09 | 14681865.86 | 0.155050E+10 |
November | 66681651.46 | 0.00 | 66681651.46 | 0.00 | 0.255263E+10 |
December | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.280938E+10 |
Annual Sum or Average | 0.681385E+10 | 0.773710E+09 | 0.604014E+10 | 0.499559E+10 | 0.163854E+11 |
Minimum of Months | 10823155.80 | 0.00 | 10823155.80 | 0.00 | 0.185815E+09 |
Maximum of Months | 0.147453E+10 | 0.326030E+09 | 0.114850E+10 | 0.149677E+10 | 0.280938E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.179138E+09 | 55218116.69 | 0.123919E+09 | 16734398.24 | 0.494750E+10 |
February | 0.900183E+09 | 0.428378E+09 | 0.471805E+09 | 0.493849E+09 | 0.371211E+10 |
March | 0.285343E+10 | 0.144681E+10 | 0.140662E+10 | 0.249534E+10 | 0.302964E+10 |
April | 0.379759E+10 | 0.192452E+10 | 0.187306E+10 | 0.361607E+10 | 0.164394E+10 |
May | 0.570875E+10 | 0.322170E+10 | 0.248705E+10 | 0.639926E+10 | 0.906793E+09 |
June | 0.507816E+10 | 0.237199E+10 | 0.270617E+10 | 0.588570E+10 | 0.427509E+09 |
July | 0.498549E+10 | 0.242072E+10 | 0.256477E+10 | 0.590641E+10 | 0.517436E+09 |
August | 0.394773E+10 | 0.192439E+10 | 0.202333E+10 | 0.446133E+10 | 0.824572E+09 |
September | 0.236128E+10 | 0.103542E+10 | 0.132586E+10 | 0.221083E+10 | 0.152281E+10 |
October | 0.128644E+10 | 0.515813E+09 | 0.770629E+09 | 0.929337E+09 | 0.274316E+10 |
November | 0.262854E+09 | 90488299.20 | 0.172366E+09 | 21600211.30 | 0.472662E+10 |
December | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.537242E+10 |
Annual Sum or Average | 0.313997E+11 | 0.154443E+11 | 0.159553E+11 | 0.324365E+11 | 0.303745E+11 |
Minimum of Months | 38623368.56 | 8872006.07 | 29751362.49 | 0.00 | 0.427509E+09 |
Maximum of Months | 0.570875E+10 | 0.322170E+10 | 0.270617E+10 | 0.639926E+10 | 0.537242E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 7082936.28 | 2183274.62 | 4899661.66 | 661663.04 | 0.195620E+09 |
February | 35592418.46 | 16937678.99 | 18654739.47 | 19526326.11 | 0.146774E+09 |
March | 0.112822E+09 | 57205554.86 | 55616515.73 | 98663429.22 | 0.119789E+09 |
April | 0.150153E+09 | 76093951.76 | 74059270.83 | 0.142976E+09 | 64999848.23 |
May | 0.225719E+09 | 0.127383E+09 | 98335906.32 | 0.253021E+09 | 35853793.16 |
June | 0.200786E+09 | 93786470.86 | 0.107000E+09 | 0.232715E+09 | 16903318.49 |
July | 0.197122E+09 | 95713028.32 | 0.101409E+09 | 0.233534E+09 | 20458936.73 |
August | 0.156090E+09 | 76088825.43 | 80000707.63 | 0.176397E+09 | 32602817.24 |
September | 93362824.18 | 40939699.31 | 52423124.87 | 87414332.31 | 60210560.80 |
October | 50864781.68 | 20394799.44 | 30469982.24 | 36745147.38 | 0.108462E+09 |
November | 10393016.29 | 3577825.88 | 6815190.41 | 854052.91 | 0.186886E+09 |
December | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 0.212421E+09 |
Annual Sum or Average | 0.124151E+10 | 0.610655E+09 | 0.630860E+09 | 0.128251E+10 | 0.120098E+10 |
Minimum of Months | 1527133.22 | 350791.13 | 1176342.09 | 0.00 | 16903318.49 |
Maximum of Months | 0.225719E+09 | 0.127383E+09 | 0.107000E+09 | 0.253021E+09 | 0.212421E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.270778E+09 | 0.229290E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.119123E+10 | 0.168707E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259524E+10 | 0.145615E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.336704E+10 | 0.966851E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.293795E+10 | 0.545213E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266280E+10 | 0.281473E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.270948E+10 | 0.316137E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276692E+10 | 0.476790E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196422E+10 | 0.804388E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126843E+10 | 0.130843E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.493497E+09 | 0.212158E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 28651387.25 | 0.255776E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222562E+11 | 0.148147E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 28651387.25 | 0.281473E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.336704E+10 | 0.255776E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431067E+09 | 0.285037E+09 | 0.146030E+09 | 0.270778E+09 | 0.229290E+10 |
February | 0.133915E+10 | 0.934194E+09 | 0.404956E+09 | 0.119123E+10 | 0.168707E+10 |
March | 0.253992E+10 | 0.172502E+10 | 0.814901E+09 | 0.259524E+10 | 0.145615E+10 |
April | 0.299152E+10 | 0.186308E+10 | 0.112844E+10 | 0.336704E+10 | 0.966851E+09 |
May | 0.253962E+10 | 0.131363E+10 | 0.122599E+10 | 0.293795E+10 | 0.545213E+09 |
June | 0.224119E+10 | 0.914485E+09 | 0.132670E+10 | 0.266280E+10 | 0.281473E+09 |
July | 0.223335E+10 | 0.969863E+09 | 0.126349E+10 | 0.270948E+10 | 0.316137E+09 |
August | 0.231977E+10 | 0.127929E+10 | 0.104048E+10 | 0.276692E+10 | 0.476790E+09 |
September | 0.181830E+10 | 0.109723E+10 | 0.721067E+09 | 0.196422E+10 | 0.804388E+09 |
October | 0.135586E+10 | 0.862846E+09 | 0.493016E+09 | 0.126843E+10 | 0.130843E+10 |
November | 0.704973E+09 | 0.493802E+09 | 0.211171E+09 | 0.493497E+09 | 0.212158E+10 |
December | 0.129368E+09 | 91482228.09 | 37886262.73 | 28651387.25 | 0.255776E+10 |
Annual Sum or Average | 0.206441E+11 | 0.118300E+11 | 0.881412E+10 | 0.222562E+11 | 0.148147E+11 |
Minimum of Months | 0.129368E+09 | 91482228.09 | 37886262.73 | 28651387.25 | 0.281473E+09 |
Maximum of Months | 0.299152E+10 | 0.186308E+10 | 0.132670E+10 | 0.336704E+10 | 0.255776E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431039E+09 | 0.285019E+09 | 0.146020E+09 | 0.270760E+09 | 0.229276E+10 |
February | 0.133907E+10 | 0.934135E+09 | 0.404930E+09 | 0.119115E+10 | 0.168696E+10 |
March | 0.253976E+10 | 0.172491E+10 | 0.814849E+09 | 0.259508E+10 | 0.145606E+10 |
April | 0.299133E+10 | 0.186296E+10 | 0.112837E+10 | 0.336683E+10 | 0.966790E+09 |
May | 0.253946E+10 | 0.131355E+10 | 0.122591E+10 | 0.293777E+10 | 0.545179E+09 |
June | 0.224104E+10 | 0.914427E+09 | 0.132662E+10 | 0.266264E+10 | 0.281455E+09 |
July | 0.223321E+10 | 0.969802E+09 | 0.126341E+10 | 0.270930E+10 | 0.316117E+09 |
August | 0.231962E+10 | 0.127921E+10 | 0.104042E+10 | 0.276675E+10 | 0.476760E+09 |
September | 0.181818E+10 | 0.109716E+10 | 0.721022E+09 | 0.196410E+10 | 0.804337E+09 |
October | 0.135578E+10 | 0.862792E+09 | 0.492985E+09 | 0.126835E+10 | 0.130834E+10 |
November | 0.704928E+09 | 0.493771E+09 | 0.211157E+09 | 0.493466E+09 | 0.212145E+10 |
December | 0.129360E+09 | 91476446.93 | 37883868.53 | 28649576.64 | 0.255760E+10 |
Annual Sum or Average | 0.206428E+11 | 0.118292E+11 | 0.881357E+10 | 0.222548E+11 | 0.148138E+11 |
Minimum of Months | 0.129360E+09 | 91476446.93 | 37883868.53 | 28649576.64 | 0.281455E+09 |
Maximum of Months | 0.299133E+10 | 0.186296E+10 | 0.132662E+10 | 0.336683E+10 | 0.255760E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 94379988.23 | 16233130.55 | 78146857.69 | 0.00 | 0.504565E+10 |
February | 0.504535E+09 | 0.173715E+09 | 0.330821E+09 | 0.109859E+09 | 0.385544E+10 |
March | 0.168357E+10 | 0.722693E+09 | 0.960879E+09 | 0.101748E+10 | 0.308542E+10 |
April | 0.387737E+10 | 0.201267E+10 | 0.186470E+10 | 0.383771E+10 | 0.177296E+10 |
May | 0.389630E+10 | 0.177851E+10 | 0.211779E+10 | 0.407465E+10 | 0.952322E+09 |
June | 0.413156E+10 | 0.176572E+10 | 0.236584E+10 | 0.468294E+10 | 0.498427E+09 |
July | 0.357057E+10 | 0.135354E+10 | 0.221703E+10 | 0.407308E+10 | 0.565196E+09 |
August | 0.293413E+10 | 0.124438E+10 | 0.168975E+10 | 0.315958E+10 | 0.867447E+09 |
September | 0.171738E+10 | 0.719680E+09 | 0.997697E+09 | 0.141675E+10 | 0.155298E+10 |
October | 0.692479E+09 | 0.206670E+09 | 0.485809E+09 | 0.259468E+09 | 0.283976E+10 |
November | 0.266966E+09 | 95726814.84 | 0.171239E+09 | 29139615.19 | 0.471748E+10 |
December | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.539068E+10 |
Annual Sum or Average | 0.233940E+11 | 0.100920E+11 | 0.133020E+11 | 0.226607E+11 | 0.311438E+11 |
Minimum of Months | 24777092.81 | 2448507.06 | 22328585.75 | 0.00 | 0.498427E+09 |
Maximum of Months | 0.413156E+10 | 0.201267E+10 | 0.236584E+10 | 0.468294E+10 | 0.539068E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3731689.67 | 641841.29 | 3089848.39 | 0.00 | 0.199500E+09 |
February | 19948822.89 | 6868508.39 | 13080314.50 | 4343687.52 | 0.152441E+09 |
March | 66566767.86 | 28574556.87 | 37992210.99 | 40229979.98 | 0.121995E+09 |
April | 0.153307E+09 | 79579087.00 | 73728338.57 | 0.151739E+09 | 70101171.73 |
May | 0.154056E+09 | 70320337.58 | 83735270.13 | 0.161108E+09 | 37653964.26 |
June | 0.163358E+09 | 69814733.93 | 93543143.14 | 0.185159E+09 | 19707349.04 |
July | 0.141177E+09 | 53517485.69 | 87659226.27 | 0.161045E+09 | 22347358.56 |
August | 0.116012E+09 | 49201345.84 | 66811020.47 | 0.124927E+09 | 34298065.58 |
September | 67903320.69 | 28455387.71 | 39447932.98 | 56016727.21 | 61403296.95 |
October | 27379904.01 | 8171502.04 | 19208401.96 | 10259076.16 | 0.112282E+09 |
November | 10555562.71 | 3784939.80 | 6770622.91 | 1152141.02 | 0.186525E+09 |
December | 979661.29 | 96811.45 | 882849.84 | 0.00 | 0.213143E+09 |
Annual Sum or Average | 0.924976E+09 | 0.399027E+09 | 0.525949E+09 | 0.895979E+09 | 0.123140E+10 |
Minimum of Months | 979661.29 | 96811.45 | 882849.84 | 0.00 | 19707349.04 |
Maximum of Months | 0.163358E+09 | 79579087.00 | 93543143.14 | 0.185159E+09 | 0.213143E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.805766E+10 |
February | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.652809E+10 |
March | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.106907E+09 | 0.538987E+10 |
April | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.875357E+09 | 0.286106E+10 |
May | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.268781E+10 | 0.132761E+10 |
June | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.438676E+10 | 0.594716E+09 |
July | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.388692E+10 | 0.749365E+09 |
August | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.199967E+10 | 0.125840E+10 |
September | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.472616E+09 | 0.247924E+10 |
October | 0.666103E+09 | 0.00 | 0.666103E+09 | 41923626.64 | 0.463083E+10 |
November | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.765855E+10 |
December | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.849187E+10 |
Annual Sum or Average | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.144580E+11 | 0.500273E+11 |
Minimum of Months | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.594716E+09 |
Maximum of Months | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.438676E+10 | 0.849187E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 16667704.40 | 0.520565E+10 |
February | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.502361E+09 | 0.393413E+10 |
March | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.254039E+10 | 0.323455E+10 |
April | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.368096E+10 | 0.176639E+10 |
May | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.658359E+10 | 0.961888E+09 |
June | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.606286E+10 | 0.457207E+09 |
July | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.610191E+10 | 0.541116E+09 |
August | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.461324E+10 | 0.850029E+09 |
September | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.228597E+10 | 0.155833E+10 |
October | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.960629E+09 | 0.281646E+10 |
November | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 22318253.14 | 0.490850E+10 |
December | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.561754E+10 |
Annual Sum or Average | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.333709E+11 | 0.318518E+11 |
Minimum of Months | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.457207E+09 |
Maximum of Months | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.658359E+10 | 0.561754E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.770825E+09 | 0.724467E+10 |
February | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.347289E+10 | 0.528686E+10 |
March | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.760235E+10 | 0.453605E+10 |
April | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.996655E+10 | 0.294619E+10 |
May | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.869899E+10 | 0.168694E+10 |
June | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.790143E+10 | 0.872495E+09 |
July | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.806668E+10 | 0.957771E+09 |
August | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.825340E+10 | 0.141170E+10 |
September | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.584434E+10 | 0.238398E+10 |
October | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.375882E+10 | 0.392265E+10 |
November | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.142794E+10 | 0.656286E+10 |
December | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69650185.71 | 0.807657E+10 |
Annual Sum or Average | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.658339E+11 | 0.458887E+11 |
Minimum of Months | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 69650185.71 | 0.872495E+09 |
Maximum of Months | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.996655E+10 | 0.807657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.531361E+10 |
February | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.109096E+09 | 0.409250E+10 |
March | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.102027E+10 | 0.330501E+10 |
April | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.391494E+10 | 0.189763E+10 |
May | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.416426E+10 | 0.103255E+10 |
June | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.481843E+10 | 0.538415E+09 |
July | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.419741E+10 | 0.601523E+09 |
August | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.326506E+10 | 0.900143E+09 |
September | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.146463E+10 | 0.159863E+10 |
October | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.266767E+09 | 0.293126E+10 |
November | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 30015285.23 | 0.490268E+10 |
December | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.564236E+10 |
Annual Sum or Average | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.232509E+11 | 0.327563E+11 |
Minimum of Months | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.538415E+09 |
Maximum of Months | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.481843E+10 | 0.564236E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2955.23 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2638.69 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 44.03 | 1943.73 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 357.40 | 1041.88 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1023.98 | 475.65 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1699.15 | 222.28 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1457.53 | 271.00 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 758.62 | 449.10 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 200.82 | 888.49 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 21.06 | 1644.18 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2890.32 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3114.99 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 466.25 | 1538.75 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 222.28 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1699.15 | 3114.99 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.29 | 1912.79 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 211.13 | 1591.14 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 960.81 | 1164.92 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1438.07 | 647.64 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2468.58 | 346.53 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2344.36 | 171.37 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2283.17 | 196.14 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1729.97 | 305.36 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 898.53 | 563.20 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 369.30 | 998.36 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.92 | 1855.59 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2065.67 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1065.67 | 981.83 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 171.37 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2468.58 | 2065.67 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.45 | 2655.52 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1449.13 | 2128.44 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2856.36 | 1631.04 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3861.65 | 1082.47 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3254.62 | 602.28 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3049.46 | 324.94 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3013.08 | 345.24 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3085.92 | 505.24 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2274.20 | 864.12 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1425.14 | 1388.97 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 558.74 | 2470.83 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 26.46 | 2962.10 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2097.10 | 1410.05 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 26.46 | 324.94 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3861.65 | 2962.10 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1950.63 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 46.23 | 1654.07 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 386.60 | 1190.74 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1522.70 | 694.12 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1561.65 | 367.61 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1860.37 | 200.26 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1568.66 | 216.55 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1223.60 | 321.16 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 577.82 | 575.50 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 105.68 | 1040.23 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 12.10 | 1851.08 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2072.41 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 741.69 | 1007.90 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 200.26 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1860.37 | 2072.41 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2963.90 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2637.60 | 176.65 | 0.00 | 176.65 | 0.00 | 0.00 |
March | 46.14 | 1946.78 | 472.47 | 0.00 | 472.47 | 0.00 | 0.00 |
April | 384.06 | 1033.30 | 853.70 | 17.68 | 836.02 | 0.00 | 0.00 |
May | 1064.32 | 461.21 | 1306.05 | 204.17 | 1101.88 | 0.00 | 0.00 |
June | 1732.35 | 215.06 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
July | 1477.36 | 268.21 | 1431.86 | 230.37 | 1201.49 | 0.00 | 0.00 |
August | 760.24 | 460.17 | 914.25 | 49.34 | 864.91 | 0.00 | 0.00 |
September | 188.83 | 950.01 | 511.02 | 0.45 | 510.57 | 0.00 | 0.00 |
October | 16.44 | 1736.64 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2954.38 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3146.64 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 475.22 | 1558.70 | 648.19 | 73.60 | 574.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 215.06 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1732.35 | 3146.64 | 1706.61 | 377.35 | 1329.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.49 | 1920.22 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 212.21 | 1595.11 | 386.81 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 968.49 | 1175.86 | 1107.47 | 561.53 | 545.94 | 0.00 | 0.00 |
April | 1450.25 | 659.31 | 1523.05 | 771.84 | 751.21 | 0.00 | 0.00 |
May | 2483.68 | 351.94 | 2215.68 | 1250.40 | 965.27 | 0.00 | 0.00 |
June | 2360.50 | 171.46 | 2036.63 | 951.30 | 1085.33 | 0.00 | 0.00 |
July | 2292.39 | 200.83 | 1934.96 | 939.53 | 995.44 | 0.00 | 0.00 |
August | 1731.53 | 320.03 | 1532.19 | 746.89 | 785.29 | 0.00 | 0.00 |
September | 886.67 | 610.73 | 947.01 | 415.26 | 531.74 | 0.00 | 0.00 |
October | 360.69 | 1064.67 | 499.29 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.66 | 1895.64 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2085.14 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1069.22 | 1001.25 | 1035.05 | 509.10 | 525.94 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 171.46 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2483.68 | 2085.14 | 2215.68 | 1250.40 | 1085.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.28 | 2568.16 | 482.82 | 319.25 | 163.56 | 0.00 | 0.00 |
February | 1477.19 | 2092.06 | 1660.62 | 1158.45 | 502.17 | 0.00 | 0.00 |
March | 2906.79 | 1630.96 | 2844.83 | 1932.11 | 912.73 | 0.00 | 0.00 |
April | 3896.95 | 1119.02 | 3462.34 | 2156.30 | 1306.04 | 0.00 | 0.00 |
May | 3290.65 | 610.66 | 2844.50 | 1471.33 | 1373.17 | 0.00 | 0.00 |
June | 3081.88 | 325.77 | 2593.91 | 1058.41 | 1535.50 | 0.00 | 0.00 |
July | 3034.74 | 354.09 | 2501.46 | 1086.29 | 1415.16 | 0.00 | 0.00 |
August | 3099.08 | 534.03 | 2598.26 | 1432.87 | 1165.39 | 0.00 | 0.00 |
September | 2273.36 | 930.98 | 2104.47 | 1269.92 | 834.55 | 0.00 | 0.00 |
October | 1420.71 | 1465.50 | 1518.63 | 966.43 | 552.20 | 0.00 | 0.00 |
November | 571.16 | 2455.48 | 815.92 | 571.52 | 244.41 | 0.00 | 0.00 |
December | 32.09 | 2864.82 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Annual Sum or Average | 2117.18 | 1409.29 | 1963.82 | 1125.35 | 838.46 | 0.00 | 0.00 |
Minimum of Months | 32.09 | 325.77 | 144.90 | 102.46 | 42.43 | 0.00 | 0.00 |
Maximum of Months | 3896.95 | 2864.82 | 3462.34 | 2156.30 | 1535.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1958.31 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 47.21 | 1656.70 | 216.80 | 74.65 | 142.15 | 0.00 | 0.00 |
March | 394.90 | 1197.51 | 653.43 | 280.49 | 372.94 | 0.00 | 0.00 |
April | 1539.14 | 711.06 | 1555.05 | 807.20 | 747.85 | 0.00 | 0.00 |
May | 1581.45 | 369.61 | 1512.23 | 690.27 | 821.95 | 0.00 | 0.00 |
June | 1878.13 | 199.90 | 1656.99 | 708.15 | 948.84 | 0.00 | 0.00 |
July | 1580.84 | 219.36 | 1385.81 | 525.33 | 860.47 | 0.00 | 0.00 |
August | 1226.29 | 336.67 | 1138.79 | 482.97 | 655.82 | 0.00 | 0.00 |
September | 568.20 | 622.83 | 688.77 | 288.63 | 400.13 | 0.00 | 0.00 |
October | 100.70 | 1102.17 | 268.76 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.69 | 1891.98 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2092.23 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 746.98 | 1026.61 | 771.15 | 332.67 | 438.48 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 199.90 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1878.13 | 2092.23 | 1656.99 | 807.20 | 948.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3008.39 | 39.96 | 0.00 | 39.96 | 0.00 | 0.00 |
February | 0.00 | 2698.45 | 176.66 | 0.00 | 176.66 | 0.00 | 0.00 |
March | 39.91 | 2012.35 | 472.48 | 0.00 | 472.48 | 0.00 | 0.00 |
April | 337.71 | 1103.80 | 853.72 | 17.68 | 836.04 | 0.00 | 0.00 |
May | 1003.51 | 495.67 | 1306.08 | 204.17 | 1101.90 | 0.00 | 0.00 |
June | 1692.42 | 229.44 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
July | 1451.21 | 279.78 | 1431.90 | 230.38 | 1201.52 | 0.00 | 0.00 |
August | 746.59 | 469.83 | 914.28 | 49.35 | 864.93 | 0.00 | 0.00 |
September | 182.34 | 956.50 | 511.03 | 0.45 | 510.58 | 0.00 | 0.00 |
October | 15.65 | 1728.95 | 248.69 | 0.00 | 248.69 | 0.00 | 0.00 |
November | 0.00 | 2954.69 | 77.18 | 0.00 | 77.18 | 0.00 | 0.00 |
December | 0.00 | 3170.50 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Annual Sum or Average | 458.46 | 1586.35 | 648.20 | 73.60 | 574.60 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 229.44 | 12.12 | 0.00 | 12.12 | 0.00 | 0.00 |
Maximum of Months | 1692.42 | 3170.50 | 1706.65 | 377.36 | 1329.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.22 | 1943.57 | 69.53 | 21.43 | 48.10 | 0.00 | 0.00 |
February | 207.66 | 1626.21 | 386.82 | 184.08 | 202.74 | 0.00 | 0.00 |
March | 948.47 | 1207.64 | 1107.49 | 561.55 | 545.95 | 0.00 | 0.00 |
April | 1420.12 | 681.48 | 1523.07 | 771.86 | 751.22 | 0.00 | 0.00 |
May | 2458.03 | 359.13 | 2215.71 | 1250.43 | 965.29 | 0.00 | 0.00 |
June | 2339.07 | 176.39 | 2036.67 | 951.32 | 1085.34 | 0.00 | 0.00 |
July | 2278.19 | 202.03 | 1935.00 | 939.55 | 995.45 | 0.00 | 0.00 |
August | 1722.39 | 317.36 | 1532.21 | 746.91 | 785.31 | 0.00 | 0.00 |
September | 881.93 | 601.21 | 947.02 | 415.27 | 531.75 | 0.00 | 0.00 |
October | 358.66 | 1051.54 | 499.30 | 200.20 | 299.10 | 0.00 | 0.00 |
November | 8.61 | 1893.71 | 105.42 | 36.29 | 69.13 | 0.00 | 0.00 |
December | 0.00 | 2097.35 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Annual Sum or Average | 1058.18 | 1010.01 | 1035.06 | 509.11 | 525.95 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 176.39 | 14.99 | 3.44 | 11.55 | 0.00 | 0.00 |
Maximum of Months | 2458.03 | 2097.35 | 2215.71 | 1250.43 | 1085.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 287.79 | 2704.85 | 482.83 | 319.27 | 163.57 | 0.00 | 0.00 |
February | 1435.55 | 2185.37 | 1660.68 | 1158.50 | 502.19 | 0.00 | 0.00 |
March | 2838.39 | 1693.57 | 2844.95 | 1932.19 | 912.76 | 0.00 | 0.00 |
April | 3845.12 | 1136.65 | 3462.47 | 2156.39 | 1306.08 | 0.00 | 0.00 |
May | 3247.83 | 629.83 | 2844.60 | 1471.39 | 1373.21 | 0.00 | 0.00 |
June | 3048.39 | 336.61 | 2594.00 | 1058.45 | 1535.55 | 0.00 | 0.00 |
July | 3011.75 | 357.59 | 2501.55 | 1086.34 | 1415.21 | 0.00 | 0.00 |
August | 3081.47 | 527.07 | 2598.35 | 1432.92 | 1165.43 | 0.00 | 0.00 |
September | 2254.76 | 919.74 | 2104.55 | 1269.97 | 834.58 | 0.00 | 0.00 |
October | 1403.38 | 1464.55 | 1518.69 | 966.47 | 552.22 | 0.00 | 0.00 |
November | 550.90 | 2531.97 | 815.96 | 571.54 | 244.41 | 0.00 | 0.00 |
December | 26.00 | 3015.45 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Annual Sum or Average | 2087.58 | 1455.12 | 1963.89 | 1125.40 | 838.49 | 0.00 | 0.00 |
Minimum of Months | 26.00 | 336.61 | 144.90 | 102.47 | 42.44 | 0.00 | 0.00 |
Maximum of Months | 3845.12 | 3015.45 | 3462.47 | 2156.39 | 1535.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1983.87 | 36.63 | 6.30 | 30.33 | 0.00 | 0.00 |
February | 45.10 | 1691.68 | 216.80 | 74.65 | 142.16 | 0.00 | 0.00 |
March | 380.93 | 1233.95 | 653.44 | 280.50 | 372.94 | 0.00 | 0.00 |
April | 1510.39 | 732.11 | 1555.07 | 807.21 | 747.86 | 0.00 | 0.00 |
May | 1554.76 | 385.51 | 1512.25 | 690.28 | 821.96 | 0.00 | 0.00 |
June | 1858.96 | 207.72 | 1657.01 | 708.17 | 948.85 | 0.00 | 0.00 |
July | 1567.13 | 224.58 | 1385.83 | 525.34 | 860.48 | 0.00 | 0.00 |
August | 1219.03 | 336.08 | 1138.81 | 482.97 | 655.83 | 0.00 | 0.00 |
September | 565.06 | 616.75 | 688.77 | 288.64 | 400.14 | 0.00 | 0.00 |
October | 99.60 | 1094.41 | 268.77 | 80.21 | 188.55 | 0.00 | 0.00 |
November | 11.58 | 1891.47 | 107.07 | 38.39 | 68.68 | 0.00 | 0.00 |
December | 0.00 | 2106.62 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Annual Sum or Average | 737.28 | 1038.70 | 771.16 | 332.67 | 438.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 207.72 | 9.62 | 0.95 | 8.67 | 0.00 | 0.00 |
Maximum of Months | 1858.96 | 2106.62 | 1657.01 | 807.21 | 948.85 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.791529E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.638351E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.117930E+09 | 0.520608E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.926373E+09 | 0.270055E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.274263E+10 | 0.127399E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.440418E+10 | 0.576157E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.390384E+10 | 0.725838E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.203189E+10 | 0.120287E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.520519E+09 | 0.230298E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 56419422.30 | 0.440377E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.749171E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.834319E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.147038E+11 | 0.485259E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.576157E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.440418E+10 | 0.834319E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16857590.31 | 0.512323E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.510755E+09 | 0.384928E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.257342E+10 | 0.312013E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.372748E+10 | 0.167869E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.661184E+10 | 0.928138E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.607657E+10 | 0.444185E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.611524E+10 | 0.525351E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.463356E+10 | 0.817868E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.232900E+10 | 0.145983E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.989146E+09 | 0.267399E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 23115069.36 | 0.480968E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.553270E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.336070E+11 | 0.309631E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.444185E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.661184E+10 | 0.553270E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.780632E+09 | 0.711256E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.350574E+10 | 0.514912E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.765046E+10 | 0.436859E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.100094E+11 | 0.280577E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.871719E+10 | 0.161314E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.790420E+10 | 0.842239E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.807022E+10 | 0.924685E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.826534E+10 | 0.135324E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.589473E+10 | 0.223980E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.381710E+10 | 0.372022E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.144825E+10 | 0.640440E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 70883387.70 | 0.793370E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.661341E+11 | 0.444675E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 70883387.70 | 0.842239E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.100094E+11 | 0.793370E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.522458E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.111832E+09 | 0.400152E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.103547E+10 | 0.318927E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.394683E+10 | 0.179916E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.418272E+10 | 0.984619E+09 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.482208E+10 | 0.519079E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.420150E+10 | 0.580020E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.327730E+10 | 0.860183E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.149771E+10 | 0.149169E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.283056E+09 | 0.278617E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 31371074.34 | 0.479800E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.555075E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.233899E+11 | 0.317850E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.519079E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.482208E+10 | 0.555075E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.793851E+10 | 0.107036E+09 | 0.00 | 0.107036E+09 | 0.00 | 0.00 |
February | 0.00 | 0.638089E+10 | 0.427362E+09 | 0.00 | 0.427362E+09 | 0.00 | 0.00 |
March | 0.123573E+09 | 0.521424E+10 | 0.126548E+10 | 0.00 | 0.126548E+10 | 0.00 | 0.00 |
April | 0.995485E+09 | 0.267832E+10 | 0.221279E+10 | 45827845.76 | 0.216696E+10 | 0.00 | 0.00 |
May | 0.285066E+10 | 0.123531E+10 | 0.349811E+10 | 0.546845E+09 | 0.295127E+10 | 0.00 | 0.00 |
June | 0.449026E+10 | 0.557435E+09 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
July | 0.395695E+10 | 0.718385E+09 | 0.383510E+10 | 0.617022E+09 | 0.321808E+10 | 0.00 | 0.00 |
August | 0.203622E+10 | 0.123251E+10 | 0.244874E+10 | 0.132165E+09 | 0.231658E+10 | 0.00 | 0.00 |
September | 0.489436E+09 | 0.246242E+10 | 0.132457E+10 | 1167593.16 | 0.132340E+10 | 0.00 | 0.00 |
October | 44046227.22 | 0.465141E+10 | 0.666088E+09 | 0.00 | 0.666088E+09 | 0.00 | 0.00 |
November | 0.00 | 0.765775E+10 | 0.200043E+09 | 0.00 | 0.200043E+09 | 0.00 | 0.00 |
December | 0.00 | 0.842796E+10 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.149866E+11 | 0.491551E+11 | 0.204413E+11 | 0.232111E+10 | 0.181202E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.557435E+09 | 32469099.83 | 0.00 | 32469099.83 | 0.00 | 0.00 |
Maximum of Months | 0.449026E+10 | 0.842796E+10 | 0.442353E+10 | 0.978081E+09 | 0.344545E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17396061.28 | 0.514312E+10 | 0.186220E+09 | 57401391.31 | 0.128819E+09 | 0.00 | 0.00 |
February | 0.513375E+09 | 0.385889E+10 | 0.935775E+09 | 0.445316E+09 | 0.490460E+09 | 0.00 | 0.00 |
March | 0.259400E+10 | 0.314943E+10 | 0.296625E+10 | 0.150402E+10 | 0.146224E+10 | 0.00 | 0.00 |
April | 0.375905E+10 | 0.170894E+10 | 0.394774E+10 | 0.200062E+10 | 0.194712E+10 | 0.00 | 0.00 |
May | 0.665228E+10 | 0.942647E+09 | 0.593447E+10 | 0.334908E+10 | 0.258539E+10 | 0.00 | 0.00 |
June | 0.611842E+10 | 0.444412E+09 | 0.527895E+10 | 0.246578E+10 | 0.281317E+10 | 0.00 | 0.00 |
July | 0.613995E+10 | 0.537895E+09 | 0.518261E+10 | 0.251643E+10 | 0.266618E+10 | 0.00 | 0.00 |
August | 0.463773E+10 | 0.857174E+09 | 0.410382E+10 | 0.200048E+10 | 0.210333E+10 | 0.00 | 0.00 |
September | 0.229825E+10 | 0.158302E+10 | 0.245464E+10 | 0.107636E+10 | 0.137828E+10 | 0.00 | 0.00 |
October | 0.966082E+09 | 0.285162E+10 | 0.133731E+10 | 0.536208E+09 | 0.801099E+09 | 0.00 | 0.00 |
November | 22454264.21 | 0.491350E+10 | 0.273247E+09 | 94066125.08 | 0.179181E+09 | 0.00 | 0.00 |
December | 0.00 | 0.558484E+10 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.337190E+11 | 0.315755E+11 | 0.326412E+11 | 0.160550E+11 | 0.165862E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.444412E+09 | 40150501.78 | 9222797.20 | 30927704.58 | 0.00 | 0.00 |
Maximum of Months | 0.665228E+10 | 0.558484E+10 | 0.593447E+10 | 0.334908E+10 | 0.281317E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.812316E+09 | 0.687856E+10 | 0.129317E+10 | 0.855092E+09 | 0.438080E+09 | 0.00 | 0.00 |
February | 0.357361E+10 | 0.506111E+10 | 0.401737E+10 | 0.280252E+10 | 0.121484E+10 | 0.00 | 0.00 |
March | 0.778556E+10 | 0.436836E+10 | 0.761960E+10 | 0.517495E+10 | 0.244465E+10 | 0.00 | 0.00 |
April | 0.101009E+11 | 0.290049E+10 | 0.897437E+10 | 0.558912E+10 | 0.338525E+10 | 0.00 | 0.00 |
May | 0.881367E+10 | 0.163560E+10 | 0.761871E+10 | 0.394082E+10 | 0.367789E+10 | 0.00 | 0.00 |
June | 0.798824E+10 | 0.844401E+09 | 0.672341E+10 | 0.274340E+10 | 0.398002E+10 | 0.00 | 0.00 |
July | 0.812825E+10 | 0.948392E+09 | 0.669991E+10 | 0.290953E+10 | 0.379038E+10 | 0.00 | 0.00 |
August | 0.830059E+10 | 0.143034E+10 | 0.695917E+10 | 0.383779E+10 | 0.312138E+10 | 0.00 | 0.00 |
September | 0.589255E+10 | 0.241311E+10 | 0.545478E+10 | 0.329163E+10 | 0.216316E+10 | 0.00 | 0.00 |
October | 0.380522E+10 | 0.392519E+10 | 0.406750E+10 | 0.258848E+10 | 0.147902E+10 | 0.00 | 0.00 |
November | 0.148046E+10 | 0.636461E+10 | 0.211487E+10 | 0.148137E+10 | 0.633498E+09 | 0.00 | 0.00 |
December | 85952351.13 | 0.767313E+10 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.667673E+11 | 0.444433E+11 | 0.619310E+11 | 0.354891E+11 | 0.264418E+11 | 0.00 | 0.00 |
Minimum of Months | 85952351.13 | 0.844401E+09 | 0.388097E+09 | 0.274441E+09 | 0.113656E+09 | 0.00 | 0.00 |
Maximum of Months | 0.101009E+11 | 0.767313E+10 | 0.897437E+10 | 0.558912E+10 | 0.398002E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.524515E+10 | 98111677.91 | 16874971.83 | 81236706.08 | 0.00 | 0.00 |
February | 0.114203E+09 | 0.400788E+10 | 0.524484E+09 | 0.180583E+09 | 0.343901E+09 | 0.00 | 0.00 |
March | 0.105771E+10 | 0.320741E+10 | 0.175014E+10 | 0.751268E+09 | 0.998871E+09 | 0.00 | 0.00 |
April | 0.398945E+10 | 0.184306E+10 | 0.403068E+10 | 0.209225E+10 | 0.193843E+10 | 0.00 | 0.00 |
May | 0.423576E+10 | 0.989976E+09 | 0.405035E+10 | 0.184883E+10 | 0.220152E+10 | 0.00 | 0.00 |
June | 0.486810E+10 | 0.518134E+09 | 0.429492E+10 | 0.183553E+10 | 0.245939E+10 | 0.00 | 0.00 |
July | 0.423413E+10 | 0.587544E+09 | 0.371175E+10 | 0.140706E+10 | 0.230469E+10 | 0.00 | 0.00 |
August | 0.328451E+10 | 0.901745E+09 | 0.305014E+10 | 0.129358E+10 | 0.175656E+10 | 0.00 | 0.00 |
September | 0.147276E+10 | 0.161438E+10 | 0.178528E+10 | 0.748135E+09 | 0.103714E+10 | 0.00 | 0.00 |
October | 0.269727E+09 | 0.295204E+10 | 0.719858E+09 | 0.214841E+09 | 0.505017E+09 | 0.00 | 0.00 |
November | 30291756.21 | 0.490400E+10 | 0.277522E+09 | 99511754.63 | 0.178010E+09 | 0.00 | 0.00 |
December | 0.00 | 0.560382E+10 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.235566E+11 | 0.323751E+11 | 0.243190E+11 | 0.104910E+11 | 0.138280E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.518134E+09 | 25756754.09 | 2545318.51 | 23211435.58 | 0.00 | 0.00 |
Maximum of Months | 0.486810E+10 | 0.560382E+10 | 0.429492E+10 | 0.209225E+10 | 0.245939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.805766E+10 | 0.107039E+09 | 0.00 | 0.107039E+09 | 0.00 | 0.00 |
February | 0.00 | 0.652809E+10 | 0.427372E+09 | 0.00 | 0.427372E+09 | 0.00 | 0.00 |
March | 0.106907E+09 | 0.538987E+10 | 0.126550E+10 | 0.00 | 0.126550E+10 | 0.00 | 0.00 |
April | 0.875357E+09 | 0.286106E+10 | 0.221284E+10 | 45829192.81 | 0.216701E+10 | 0.00 | 0.00 |
May | 0.268781E+10 | 0.132761E+10 | 0.349819E+10 | 0.546861E+09 | 0.295133E+10 | 0.00 | 0.00 |
June | 0.438676E+10 | 0.594716E+09 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
July | 0.388692E+10 | 0.749365E+09 | 0.383519E+10 | 0.617040E+09 | 0.321815E+10 | 0.00 | 0.00 |
August | 0.199967E+10 | 0.125840E+10 | 0.244879E+10 | 0.132169E+09 | 0.231663E+10 | 0.00 | 0.00 |
September | 0.472616E+09 | 0.247924E+10 | 0.132460E+10 | 1167627.48 | 0.132343E+10 | 0.00 | 0.00 |
October | 41923626.64 | 0.463083E+10 | 0.666103E+09 | 0.00 | 0.666103E+09 | 0.00 | 0.00 |
November | 0.00 | 0.765855E+10 | 0.200047E+09 | 0.00 | 0.200047E+09 | 0.00 | 0.00 |
December | 0.00 | 0.849187E+10 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.144580E+11 | 0.500273E+11 | 0.204418E+11 | 0.232118E+10 | 0.181206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.594716E+09 | 32469900.88 | 0.00 | 32469900.88 | 0.00 | 0.00 |
Maximum of Months | 0.438676E+10 | 0.849187E+10 | 0.442363E+10 | 0.978110E+09 | 0.344552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 16667704.40 | 0.520565E+10 | 0.186224E+09 | 57402514.18 | 0.128821E+09 | 0.00 | 0.00 |
February | 0.502361E+09 | 0.393413E+10 | 0.935792E+09 | 0.445324E+09 | 0.490467E+09 | 0.00 | 0.00 |
March | 0.254039E+10 | 0.323455E+10 | 0.296630E+10 | 0.150404E+10 | 0.146226E+10 | 0.00 | 0.00 |
April | 0.368096E+10 | 0.176639E+10 | 0.394781E+10 | 0.200066E+10 | 0.194715E+10 | 0.00 | 0.00 |
May | 0.658359E+10 | 0.961888E+09 | 0.593457E+10 | 0.334914E+10 | 0.258543E+10 | 0.00 | 0.00 |
June | 0.606286E+10 | 0.457207E+09 | 0.527904E+10 | 0.246583E+10 | 0.281321E+10 | 0.00 | 0.00 |
July | 0.610191E+10 | 0.541116E+09 | 0.518269E+10 | 0.251648E+10 | 0.266621E+10 | 0.00 | 0.00 |
August | 0.461324E+10 | 0.850029E+09 | 0.410388E+10 | 0.200052E+10 | 0.210336E+10 | 0.00 | 0.00 |
September | 0.228597E+10 | 0.155833E+10 | 0.245468E+10 | 0.107638E+10 | 0.137830E+10 | 0.00 | 0.00 |
October | 0.960629E+09 | 0.281646E+10 | 0.133733E+10 | 0.536219E+09 | 0.801112E+09 | 0.00 | 0.00 |
November | 22318253.14 | 0.490850E+10 | 0.273252E+09 | 94067965.17 | 0.179184E+09 | 0.00 | 0.00 |
December | 0.00 | 0.561754E+10 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Annual Sum or Average | 0.333709E+11 | 0.318518E+11 | 0.326417E+11 | 0.160553E+11 | 0.165864E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.457207E+09 | 40151185.17 | 9222977.62 | 30928207.55 | 0.00 | 0.00 |
Maximum of Months | 0.658359E+10 | 0.561754E+10 | 0.593457E+10 | 0.334914E+10 | 0.281321E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.770825E+09 | 0.724467E+10 | 0.129323E+10 | 0.855128E+09 | 0.438097E+09 | 0.00 | 0.00 |
February | 0.347289E+10 | 0.528686E+10 | 0.401753E+10 | 0.280264E+10 | 0.121489E+10 | 0.00 | 0.00 |
March | 0.760235E+10 | 0.453605E+10 | 0.761990E+10 | 0.517517E+10 | 0.244474E+10 | 0.00 | 0.00 |
April | 0.996655E+10 | 0.294619E+10 | 0.897472E+10 | 0.558935E+10 | 0.338536E+10 | 0.00 | 0.00 |
May | 0.869899E+10 | 0.168694E+10 | 0.761899E+10 | 0.394098E+10 | 0.367801E+10 | 0.00 | 0.00 |
June | 0.790143E+10 | 0.872495E+09 | 0.672366E+10 | 0.274351E+10 | 0.398014E+10 | 0.00 | 0.00 |
July | 0.806668E+10 | 0.957771E+09 | 0.670015E+10 | 0.290965E+10 | 0.379050E+10 | 0.00 | 0.00 |
August | 0.825340E+10 | 0.141170E+10 | 0.695943E+10 | 0.383795E+10 | 0.312148E+10 | 0.00 | 0.00 |
September | 0.584434E+10 | 0.238398E+10 | 0.545499E+10 | 0.329176E+10 | 0.216323E+10 | 0.00 | 0.00 |
October | 0.375882E+10 | 0.392265E+10 | 0.406766E+10 | 0.258859E+10 | 0.147907E+10 | 0.00 | 0.00 |
November | 0.142794E+10 | 0.656286E+10 | 0.211496E+10 | 0.148144E+10 | 0.633523E+09 | 0.00 | 0.00 |
December | 69650185.71 | 0.807657E+10 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.658339E+11 | 0.458887E+11 | 0.619333E+11 | 0.354906E+11 | 0.264427E+11 | 0.00 | 0.00 |
Minimum of Months | 69650185.71 | 0.872495E+09 | 0.388113E+09 | 0.274452E+09 | 0.113661E+09 | 0.00 | 0.00 |
Maximum of Months | 0.996655E+10 | 0.807657E+10 | 0.897472E+10 | 0.558935E+10 | 0.398014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.531361E+10 | 98112947.39 | 16875249.29 | 81237698.10 | 0.00 | 0.00 |
February | 0.109096E+09 | 0.409250E+10 | 0.524491E+09 | 0.180586E+09 | 0.343905E+09 | 0.00 | 0.00 |
March | 0.102027E+10 | 0.330501E+10 | 0.175016E+10 | 0.751280E+09 | 0.998882E+09 | 0.00 | 0.00 |
April | 0.391494E+10 | 0.189763E+10 | 0.403074E+10 | 0.209229E+10 | 0.193845E+10 | 0.00 | 0.00 |
May | 0.416426E+10 | 0.103255E+10 | 0.405040E+10 | 0.184886E+10 | 0.220155E+10 | 0.00 | 0.00 |
June | 0.481843E+10 | 0.538415E+09 | 0.429498E+10 | 0.183556E+10 | 0.245941E+10 | 0.00 | 0.00 |
July | 0.419741E+10 | 0.601523E+09 | 0.371179E+10 | 0.140708E+10 | 0.230472E+10 | 0.00 | 0.00 |
August | 0.326506E+10 | 0.900143E+09 | 0.305018E+10 | 0.129360E+10 | 0.175658E+10 | 0.00 | 0.00 |
September | 0.146463E+10 | 0.159863E+10 | 0.178530E+10 | 0.748147E+09 | 0.103716E+10 | 0.00 | 0.00 |
October | 0.266767E+09 | 0.293126E+10 | 0.719868E+09 | 0.214845E+09 | 0.505023E+09 | 0.00 | 0.00 |
November | 30015285.23 | 0.490268E+10 | 0.277525E+09 | 99513390.80 | 0.178012E+09 | 0.00 | 0.00 |
December | 0.00 | 0.564236E+10 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.232509E+11 | 0.327563E+11 | 0.243193E+11 | 0.104912E+11 | 0.138281E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.538415E+09 | 25757088.73 | 2545360.36 | 23211728.37 | 0.00 | 0.00 |
Maximum of Months | 0.481843E+10 | 0.564236E+10 | 0.429498E+10 | 0.209229E+10 | 0.245941E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.592824E+10 | -0.566902E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -259222132.8 | 60.05 | 0.00 | 0.00 |
February | 0.538134E+10 | -0.515214E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -229201579.4 | 60.05 | 0.00 | 0.00 |
March | 0.634657E+10 | -0.610038E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -246184347.3 | 60.05 | 0.00 | 0.00 |
April | 0.571794E+10 | -0.548883E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229108455.0 | 60.05 | 0.00 | 0.00 |
May | 0.607767E+10 | -0.584474E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232932911.9 | 60.05 | 0.00 | 0.00 |
June | 0.582226E+10 | -0.559779E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224470382.2 | 60.05 | 0.00 | 0.00 |
July | 0.530898E+10 | -0.507786E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231112987.0 | 60.05 | 0.00 | 0.00 |
August | 0.571438E+10 | -0.548231E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232078727.2 | 60.05 | 0.00 | 0.00 |
September | 0.514383E+10 | -0.491783E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -226003745.1 | 60.05 | 0.00 | 0.00 |
October | 0.541827E+10 | -0.517772E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -240546339.0 | 60.05 | 0.00 | 0.00 |
November | 0.551709E+10 | -0.527198E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -245105056.0 | 60.05 | 0.00 | 0.00 |
December | 0.568617E+10 | -0.542781E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -258352313.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.680627E+11 | -0.652084E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.285432E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.514383E+10 | -0.610038E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -259222132.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.634657E+10 | -0.491783E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -224470382.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.61 | 0.48 | 10-JAN-10:00 | 628.12 | 11.79 | 5.83 | 65.33 | 539.44 | 22.88 | 45.50 | 42.33 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2627.31 | 32.59 | 169.33 | 172.00 | 2310.45 | 35.94 | 191.17 | 156.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5962.17 | 32.46 | 277.33 | 298.33 | 5205.57 | 33.91 | 286.67 | 281.17 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:30 | 8380.75 | 30.96 | 285.50 | 381.17 | 1682.82 | 21.17 | 255.50 | 337.83 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 4087.88 | 21.29 | 123.33 | 451.50 | 1214.76 | 19.90 | 272.83 | 393.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:10 | 1983.04 | 17.35 | 8.17 | 474.33 | 1105.06 | 19.65 | 286.00 | 409.17 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2362.03 | 17.96 | 23.00 | 471.33 | 1130.43 | 19.69 | 274.17 | 398.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:49 | 5983.27 | 26.49 | 248.17 | 404.83 | 1288.14 | 20.29 | 240.00 | 353.33 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4860.00 | 30.47 | 274.67 | 316.50 | 1697.09 | 21.83 | 198.67 | 278.83 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:49 | 2695.35 | 31.14 | 222.50 | 234.33 | 2251.68 | 33.46 | 238.00 | 209.67 |
November | 135.83 | 0.55 | 0.48 | 01-NOV-09:00 | 931.72 | 21.39 | 55.83 | 116.67 | 847.59 | 31.80 | 105.17 | 90.67 |
December | 71.17 | 0.77 | 0.48 | 05-DEC-11:20 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 |
Annual Sum or Average | 4053.17 | 0.54 | 3998.16 | 24.28 | 1693.67 | 3393.33 | 1685.25 | 23.33 | 2393.67 | 2951.67 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 179.75 | 6.06 | 0.00 | 7.00 | 123.19 | 10.09 | 0.00 | 0.33 | |
Maximum of Months | 583.50 | 0.77 | 0.48 | 8380.75 | 32.59 | 285.50 | 474.33 | 5205.57 | 35.94 | 286.67 | 409.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.70 | 0.48 | 16-JAN-11:00 | 285.98 | 10.33 | 1.67 | 29.83 | 174.87 | 13.23 | 4.67 | 12.00 |
February | 205.83 | 0.59 | 0.48 | 01-FEB-12:20 | 938.97 | 16.95 | 45.67 | 140.00 | 637.64 | 21.56 | 79.83 | 96.83 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:20 | 2386.78 | 21.20 | 113.00 | 277.17 | 1552.97 | 23.76 | 154.17 | 238.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3087.86 | 22.83 | 135.50 | 385.17 | 1899.56 | 24.11 | 183.00 | 344.50 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4047.70 | 22.19 | 181.33 | 460.00 | 2129.07 | 23.33 | 195.50 | 417.33 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:39 | 3496.86 | 21.68 | 195.83 | 493.83 | 1563.95 | 22.22 | 203.33 | 434.83 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:49 | 3484.70 | 21.74 | 198.83 | 478.67 | 1823.58 | 22.84 | 215.17 | 424.67 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2868.91 | 21.06 | 146.67 | 406.50 | 1480.53 | 22.36 | 170.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2228.83 | 21.05 | 131.17 | 298.00 | 1172.91 | 22.16 | 141.33 | 252.17 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1176.10 | 19.69 | 95.50 | 209.50 | 690.70 | 20.70 | 83.00 | 151.67 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-09:00 | 388.22 | 15.83 | 33.83 | 67.00 | 228.87 | 18.34 | 35.83 | 19.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2720.71 | 20.57 | 1279.00 | 3245.67 | 1453.34 | 22.04 | 1466.00 | 2749.50 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 97.58 | 6.08 | 0.00 | 0.00 | 56.81 | 8.43 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 4047.70 | 22.83 | 198.83 | 493.83 | 2129.07 | 24.11 | 215.17 | 434.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.79 | 0.52 | 31-JAN-11:30 | 167.46 | 7.85 | 0.00 | 4.33 | 97.38 | 10.35 | 0.00 | 0.00 |
February | 205.83 | 0.62 | 0.48 | 11-FEB-12:20 | 368.20 | 12.17 | 0.00 | 106.50 | 216.92 | 14.68 | 0.00 | 23.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 677.10 | 15.55 | 0.00 | 268.83 | 401.64 | 17.91 | 7.00 | 196.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:40 | 891.96 | 17.88 | 0.00 | 394.33 | 553.01 | 20.22 | 56.50 | 337.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1100.12 | 21.51 | 130.33 | 498.50 | 657.34 | 23.68 | 215.17 | 467.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1185.97 | 21.59 | 140.67 | 516.17 | 673.50 | 22.89 | 231.00 | 463.67 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 919.26 | 19.42 | 64.17 | 422.17 | 525.60 | 19.68 | 71.17 | 360.50 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 661.48 | 15.64 | 0.00 | 293.33 | 382.37 | 17.86 | 5.17 | 198.33 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-08:09 | 461.32 | 13.61 | 0.00 | 186.00 | 256.46 | 15.89 | 0.00 | 29.67 |
November | 135.83 | 0.73 | 0.48 | 01-NOV-13:30 | 223.61 | 9.68 | 0.00 | 23.33 | 128.30 | 12.40 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 874.56 | 17.89 | 488.50 | 3248.50 | 511.18 | 19.84 | 883.17 | 2575.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 66.17 | 3.36 | 0.00 | 0.00 | 38.84 | 5.50 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 1305.26 | 21.93 | 153.33 | 535.00 | 760.31 | 24.31 | 297.17 | 499.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.72 | 0.48 | 23-JAN-13:20 | 241.30 | 9.89 | 1.67 | 20.67 | 144.92 | 12.74 | 1.83 | 4.17 |
February | 205.83 | 0.56 | 0.48 | 02-FEB-11:09 | 802.73 | 19.52 | 61.50 | 151.17 | 497.05 | 21.80 | 69.83 | 82.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1800.71 | 20.96 | 97.83 | 288.17 | 1090.89 | 23.20 | 118.33 | 252.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3478.80 | 22.73 | 139.50 | 384.67 | 1768.81 | 22.76 | 148.50 | 343.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2761.43 | 19.46 | 117.83 | 479.17 | 1380.71 | 20.19 | 78.33 | 433.33 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2919.10 | 18.89 | 111.33 | 506.17 | 1480.15 | 19.90 | 79.17 | 451.50 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2527.98 | 18.82 | 114.50 | 498.17 | 1311.24 | 19.78 | 90.00 | 437.83 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2292.88 | 20.07 | 117.50 | 419.83 | 1387.76 | 21.65 | 121.00 | 371.83 |
September | 356.33 | 0.52 | 0.48 | 01-SEP-06:00 | 1830.48 | 21.90 | 120.17 | 312.83 | 1112.14 | 22.95 | 114.17 | 256.83 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 920.17 | 19.46 | 82.67 | 214.83 | 531.89 | 20.85 | 65.50 | 137.50 |
November | 135.83 | 0.64 | 0.48 | 01-NOV-10:30 | 374.94 | 15.40 | 33.83 | 64.50 | 250.34 | 20.06 | 45.17 | 24.33 |
December | 71.17 | 0.90 | 0.71 | 04-DEC-11:30 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2197.80 | 19.40 | 998.33 | 3340.17 | 1184.54 | 20.72 | 931.83 | 2795.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 84.88 | 5.41 | 0.00 | 0.00 | 48.96 | 7.76 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.71 | 3478.80 | 22.73 | 139.50 | 506.17 | 1768.81 | 23.20 | 148.50 | 451.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.03 | 7.16 | 5.50 | 61.33 | 434.82 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.01 | 29.41 | 153.17 | 168.50 | 2214.90 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.24 | 31.76 | 272.33 | 297.00 | 5074.25 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.56 | 29.76 | 283.67 | 378.33 | 1557.11 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.66 | 18.43 | 114.67 | 447.00 | 1133.74 | 17.35 | 12.67 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.72 | 13.48 | 0.00 | 470.67 | 1037.98 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.85 | 14.19 | 15.67 | 467.33 | 1060.15 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.49 | 24.67 | 238.50 | 402.00 | 1198.87 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.88 | 29.45 | 267.17 | 314.83 | 1602.68 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.99 | 28.57 | 204.50 | 231.50 | 2174.45 | 32.70 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.64 | 7.78 | 0.00 | 112.00 | 783.61 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.30 | 21.36 | 1555.17 | 3354.83 | 1597.60 | 20.81 | 922.83 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.36 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.56 | 31.76 | 283.67 | 470.67 | 5074.25 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.26 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.49 | 16.44 | 45.67 | 137.83 | 611.40 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.03 | 20.76 | 112.67 | 275.17 | 1427.40 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.42 | 20.71 | 109.67 | 382.00 | 1827.71 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.61 | 21.76 | 181.33 | 457.50 | 2050.65 | 23.15 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3409.86 | 21.22 | 194.83 | 491.00 | 1497.87 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3362.23 | 20.41 | 173.00 | 476.33 | 1749.34 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.24 | 20.61 | 146.17 | 404.50 | 1417.89 | 22.17 | 151.00 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.16 | 20.38 | 128.00 | 294.50 | 1122.92 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.20 | 17.57 | 73.17 | 207.00 | 663.02 | 20.47 | 81.00 | 147.67 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.30 | 33.83 | 63.50 | 219.25 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2626.65 | 19.68 | 1200.00 | 3216.00 | 1389.96 | 21.64 | 1332.33 | 2708.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.61 | 21.76 | 194.83 | 491.00 | 2050.65 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.01 | 7.46 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.16 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.76 | 11.93 | 0.00 | 264.83 | 387.13 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.77 | 14.48 | 0.00 | 392.67 | 534.62 | 18.22 | 1.83 | 331.50 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.99 | 18.88 | 128.67 | 496.83 | 634.19 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.89 | 18.94 | 137.00 | 514.50 | 646.95 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.48 | 16.33 | 62.33 | 419.83 | 527.69 | 19.56 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.51 | 11.96 | 0.00 | 290.00 | 368.43 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.75 | 9.55 | 0.00 | 179.00 | 246.38 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.77 | 5.54 | 0.00 | 18.83 | 122.71 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.97 | 14.71 | 478.00 | 3210.50 | 494.62 | 17.85 | 461.67 | 2521.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 37.00 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.46 | 19.27 | 150.00 | 532.50 | 730.92 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.37 | 1.33 | 18.83 | 138.78 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.63 | 16.69 | 44.67 | 146.50 | 477.88 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.06 | 20.48 | 96.17 | 286.33 | 1024.83 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.46 | 22.31 | 139.50 | 383.00 | 1701.11 | 22.62 | 145.00 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.88 | 18.99 | 117.83 | 475.67 | 1324.73 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.77 | 18.40 | 111.33 | 502.67 | 1424.23 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.06 | 18.35 | 114.50 | 492.33 | 1261.54 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.41 | 19.43 | 114.50 | 416.83 | 1339.98 | 21.49 | 117.17 | 366.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.20 | 20.01 | 103.67 | 310.33 | 1073.49 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.19 | 19.08 | 82.50 | 211.67 | 511.77 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.23 | 15.03 | 33.83 | 61.00 | 239.82 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.11 | 18.68 | 959.83 | 3305.17 | 1137.89 | 20.48 | 889.67 | 2742.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.49 | 5.13 | 0.00 | 0.00 | 46.73 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.46 | 22.31 | 139.50 | 502.67 | 1701.11 | 22.82 | 145.00 | 446.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 571.05 | 7.16 | 5.50 | 61.33 | 434.81 | 11.81 | 6.00 | 38.17 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 2456.05 | 29.41 | 153.17 | 168.50 | 2214.86 | 35.68 | 190.50 | 154.50 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5783.23 | 31.76 | 272.33 | 297.00 | 5074.15 | 33.50 | 281.00 | 279.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 8215.50 | 29.76 | 283.67 | 378.33 | 1557.00 | 18.46 | 33.00 | 332.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-05:30 | 3977.57 | 18.43 | 114.67 | 447.00 | 1133.65 | 17.35 | 12.83 | 389.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-05:19 | 1886.61 | 13.48 | 0.00 | 470.67 | 1037.90 | 17.01 | 9.83 | 403.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2262.74 | 14.19 | 15.67 | 467.33 | 1060.06 | 17.01 | 11.83 | 394.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 5863.40 | 24.67 | 238.50 | 402.00 | 1198.77 | 17.50 | 12.33 | 349.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 4728.84 | 29.45 | 267.17 | 314.83 | 1602.59 | 19.12 | 39.50 | 274.33 |
October | 265.50 | 0.52 | 0.48 | 01-OCT-07:00 | 2544.97 | 28.57 | 204.50 | 231.50 | 2174.40 | 32.71 | 232.00 | 208.50 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 693.67 | 7.78 | 0.00 | 112.00 | 783.59 | 28.40 | 94.17 | 84.83 |
December | 71.17 | 0.79 | 0.48 | 05-DEC-11:30 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3870.24 | 21.36 | 1555.17 | 3354.83 | 1597.52 | 20.81 | 923.00 | 2908.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 164.37 | 2.18 | 0.00 | 4.33 | 115.60 | 5.95 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.79 | 0.48 | 8215.50 | 31.76 | 283.67 | 470.67 | 5074.15 | 35.68 | 281.00 | 403.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.71 | 0.48 | 16-JAN-12:09 | 274.91 | 9.69 | 1.67 | 26.67 | 167.25 | 12.88 | 2.17 | 10.50 |
February | 205.83 | 0.59 | 0.48 | 02-FEB-10:09 | 904.48 | 16.44 | 45.67 | 137.83 | 611.37 | 21.34 | 76.83 | 92.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 2308.02 | 20.76 | 112.67 | 275.17 | 1427.35 | 22.14 | 127.83 | 234.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 2908.41 | 20.72 | 109.67 | 382.00 | 1827.65 | 23.91 | 172.33 | 340.67 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 3949.58 | 21.76 | 181.33 | 457.50 | 2050.57 | 23.16 | 184.00 | 413.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-03:49 | 3410.55 | 21.26 | 195.83 | 491.00 | 1497.79 | 22.01 | 183.00 | 431.17 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-03:00 | 3396.93 | 21.33 | 198.17 | 476.33 | 1749.26 | 22.08 | 184.17 | 419.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 2788.20 | 20.61 | 146.17 | 404.50 | 1417.82 | 22.17 | 151.17 | 354.17 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:19 | 2138.13 | 20.38 | 128.00 | 294.50 | 1122.87 | 21.95 | 134.83 | 247.83 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-07:49 | 1078.18 | 17.57 | 73.17 | 207.00 | 662.98 | 20.47 | 81.00 | 147.50 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-09:00 | 374.43 | 15.31 | 33.83 | 63.50 | 219.24 | 18.08 | 35.17 | 16.50 |
December | 71.17 | 0.88 | 0.55 | 04-DEC-11:30 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 2631.55 | 19.82 | 1226.17 | 3216.00 | 1389.90 | 21.64 | 1332.50 | 2707.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 93.53 | 5.55 | 0.00 | 0.00 | 54.13 | 8.12 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.88 | 0.55 | 3949.58 | 21.76 | 198.17 | 491.00 | 2050.57 | 23.91 | 184.17 | 431.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.80 | 0.52 | 31-JAN-11:30 | 159.74 | 4.04 | 0.00 | 2.67 | 93.00 | 7.47 | 0.00 | 0.00 |
February | 205.83 | 0.63 | 0.48 | 12-FEB-11:30 | 352.51 | 8.25 | 0.00 | 98.83 | 208.14 | 11.95 | 0.00 | 18.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:00 | 650.74 | 11.93 | 0.00 | 264.83 | 387.10 | 15.55 | 0.00 | 186.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 857.76 | 14.49 | 0.00 | 392.67 | 534.59 | 18.22 | 1.83 | 331.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1059.97 | 18.88 | 128.67 | 496.83 | 634.15 | 21.97 | 133.67 | 464.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:00 | 1142.86 | 18.94 | 137.00 | 514.50 | 646.90 | 20.45 | 105.50 | 458.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-04:00 | 885.45 | 16.34 | 62.33 | 419.83 | 527.66 | 19.57 | 68.17 | 357.67 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-06:49 | 636.49 | 11.96 | 0.00 | 290.00 | 368.40 | 15.50 | 0.00 | 185.67 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 443.73 | 9.55 | 0.00 | 179.00 | 246.36 | 13.15 | 0.00 | 23.67 |
November | 135.83 | 0.74 | 0.48 | 06-NOV-13:09 | 213.76 | 5.55 | 0.00 | 18.83 | 122.70 | 9.37 | 0.00 | 0.00 |
December | 71.17 | 0.92 | 0.78 | 04-DEC-11:30 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 841.95 | 14.71 | 478.00 | 3210.50 | 494.59 | 17.85 | 461.67 | 2521.17 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 62.92 | 0.81 | 0.00 | 0.00 | 36.99 | 3.10 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.78 | 1257.43 | 19.27 | 150.00 | 532.50 | 730.88 | 22.48 | 152.50 | 495.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 23-JAN-13:20 | 232.25 | 9.38 | 1.33 | 18.83 | 138.77 | 12.72 | 1.83 | 3.50 |
February | 205.83 | 0.57 | 0.48 | 02-FEB-11:20 | 735.62 | 16.70 | 44.67 | 146.50 | 477.86 | 21.72 | 70.00 | 77.00 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:00 | 1742.04 | 20.49 | 96.17 | 286.33 | 1024.79 | 21.95 | 103.67 | 246.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 3391.45 | 22.31 | 139.50 | 383.00 | 1701.04 | 22.62 | 145.17 | 339.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-06:40 | 2690.85 | 18.99 | 117.83 | 475.67 | 1324.67 | 20.02 | 75.33 | 428.83 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 2847.72 | 18.40 | 111.33 | 502.67 | 1424.16 | 19.71 | 70.00 | 446.33 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2453.01 | 18.35 | 114.50 | 492.33 | 1261.48 | 19.60 | 83.83 | 432.00 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2219.37 | 19.43 | 114.50 | 416.83 | 1339.92 | 21.49 | 117.50 | 365.83 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 1748.17 | 20.01 | 103.67 | 310.33 | 1073.44 | 22.82 | 112.33 | 253.17 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 893.17 | 19.08 | 82.50 | 211.67 | 511.74 | 20.74 | 65.17 | 127.33 |
November | 135.83 | 0.65 | 0.48 | 01-NOV-10:39 | 360.22 | 15.03 | 33.83 | 61.00 | 239.81 | 20.02 | 45.33 | 22.83 |
December | 71.17 | 0.90 | 0.72 | 04-DEC-11:30 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2132.08 | 18.68 | 959.83 | 3305.17 | 1137.84 | 20.48 | 890.17 | 2742.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 81.48 | 5.13 | 0.00 | 0.00 | 46.72 | 7.83 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.72 | 3391.45 | 22.31 | 139.50 | 502.67 | 1701.04 | 22.82 | 145.17 | 446.33 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136426E+11 | 44615.07 | 11-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.851469E+10 | 43284.32 | 27-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.276005E+10 | 42178.37 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115295E+09 | 13025.80 | 14-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17650988.78 | 6962.94 | 27-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 117185.73 | 4.70 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 250576.07 | 5.11 | 07-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7677708.80 | 9168.99 | 31-AUG-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 47830058.20 | 9189.31 | 09-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.402371E+09 | 5328.62 | 31-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127505E+11 | 43076.70 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201087E+11 | 44125.94 | 15-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.583678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 117185.73 | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201087E+11 | 44615.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187648E+10 | 13720.24 | 17-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408422E+09 | 13687.12 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21712151.02 | 13686.73 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330577E+09 | 13689.55 | 13-NOV-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.785614E+09 | 13690.29 | 26-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187648E+10 | 13720.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153546E+11 | 12283.68 | 11-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108943E+11 | 11874.04 | 27-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.797440E+10 | 11541.18 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233662E+10 | 11417.12 | 24-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.760696E+09 | 11456.00 | 17-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167453E+09 | 11061.91 | 07-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117836E+09 | 10998.26 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.343121E+09 | 11447.50 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148406E+10 | 11431.60 | 15-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.526524E+10 | 10918.92 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126909E+11 | 11810.96 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153811E+11 | 12132.75 | 15-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.727703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.117836E+09 | 10918.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153811E+11 | 12283.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.732975E+10 | 8009.30 | 11-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498271E+10 | 7742.41 | 27-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233203E+10 | 7525.59 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.322252E+09 | 7108.23 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16770470.99 | 7091.09 | 28-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103643E+10 | 7108.99 | 13-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496712E+10 | 7701.31 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694601E+10 | 7910.96 | 15-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.732975E+10 | 8009.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.990047E+10 | 8393.35 | 11-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.779058E+10 | 8116.74 | 27-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.586026E+10 | 7893.52 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118182E+10 | 7811.37 | 24-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81979505.33 | 7473.36 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206539E+10 | 7477.00 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719020E+10 | 8074.30 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.950087E+10 | 8291.46 | 15-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.990047E+10 | 8393.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.749643E+10 | 8179.33 | 11-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.544231E+10 | 7906.06 | 27-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332559E+10 | 7685.14 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366288E+09 | 7261.78 | 07-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32202473.70 | 7260.76 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128332E+10 | 7268.29 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.497994E+10 | 7864.10 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699230E+10 | 8078.63 | 15-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749643E+10 | 8179.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135937E+11 | 47533.24 | 12-JAN-09:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.835897E+10 | 45853.22 | 27-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.303951E+10 | 44092.35 | 01-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146324E+09 | 5757.53 | 03-APR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14834614.58 | 4102.24 | 26-MAY-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 989372.48 | 753.17 | 02-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1128729.48 | 849.46 | 05-JUL-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10015400.88 | 2782.57 | 30-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16365454.16 | 5314.59 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.769905E+09 | 5762.59 | 26-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125952E+11 | 44299.25 | 27-NOV-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188606E+11 | 46146.53 | 15-DEC-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.574075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 989372.48 | 753.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188606E+11 | 47533.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.729258E+10 | 19486.67 | 20-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405612E+10 | 19486.26 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130812E+10 | 19483.21 | 10-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63748033.70 | 19467.70 | 04-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.822363E+09 | 19474.54 | 24-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504867E+10 | 19484.81 | 03-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713367E+10 | 19473.72 | 20-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.729258E+10 | 19486.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.784494E+10 | 13045.45 | 12-JAN-09:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396233E+10 | 12536.18 | 27-FEB-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175587E+10 | 12007.06 | 01-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235330E+09 | 11545.38 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45664103.01 | 11477.87 | 28-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142151E+10 | 11552.90 | 18-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569428E+10 | 12071.43 | 27-NOV-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848401E+10 | 12623.96 | 15-DEC-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.848401E+10 | 13045.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.585518E+10 | 8708.84 | 12-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337218E+10 | 8361.60 | 27-FEB-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143953E+10 | 7980.21 | 01-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186318E+09 | 7680.90 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37959490.90 | 7641.08 | 26-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116488E+10 | 7684.67 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.457564E+10 | 8097.18 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592300E+10 | 8447.33 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225547E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592300E+10 | 8708.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.853830E+10 | 8858.87 | 12-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.582877E+10 | 8541.37 | 27-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360233E+10 | 8236.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513155E+09 | 7850.49 | 03-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98620600.05 | 7835.98 | 28-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223831E+10 | 7858.55 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.689236E+10 | 8292.65 | 29-NOV-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858776E+10 | 8597.84 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.362996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.858776E+10 | 8858.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.598746E+10 | 8641.55 | 12-JAN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.379625E+10 | 8326.18 | 27-FEB-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202861E+10 | 7918.71 | 01-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235238E+09 | 7614.19 | 05-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53064688.18 | 7569.65 | 28-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141075E+10 | 7625.53 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.460591E+10 | 8034.75 | 29-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595855E+10 | 8382.12 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.598746E+10 | 8641.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181323E+11 | 47033.87 | 12-JAN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116389E+11 | 44916.58 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.490571E+10 | 44350.37 | 01-MAR-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.440529E+09 | 8564.55 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7194314.32 | 2800.48 | 22-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1315618.87 | 2512.27 | 01-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 639762.12 | 890.02 | 05-JUL-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3740006.97 | 1610.32 | 09-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 60080481.39 | 4609.04 | 26-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185752E+10 | 8487.27 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167259E+11 | 44556.92 | 29-NOV-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235392E+11 | 45924.81 | 15-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.773130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 639762.12 | 890.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235392E+11 | 47033.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155145E+11 | 26760.33 | 12-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101395E+11 | 26422.34 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574194E+10 | 25874.43 | 22-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.930258E+09 | 25861.94 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158952E+09 | 25861.08 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.430280E+10 | 25881.71 | 03-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130549E+11 | 25860.46 | 13-NOV-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157892E+11 | 26034.14 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.656321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157892E+11 | 26760.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117714E+11 | 15397.27 | 12-JAN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678417E+10 | 14608.87 | 22-FEB-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.367379E+10 | 14436.98 | 01-MAR-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.772196E+09 | 13564.67 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2500524.35 | 2344.33 | 27-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4362789.33 | 6021.76 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.284031E+09 | 13545.08 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317438E+10 | 13581.08 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.953547E+10 | 14510.28 | 29-NOV-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129365E+11 | 14999.31 | 15-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129365E+11 | 15397.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.855932E+10 | 9988.72 | 12-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556637E+10 | 9471.26 | 22-FEB-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.283434E+10 | 9352.56 | 01-MAR-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.544173E+09 | 8779.19 | 03-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1721101.22 | 8221.81 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191999E+09 | 8762.22 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251651E+10 | 8786.80 | 27-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.736720E+10 | 9407.04 | 29-NOV-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888746E+10 | 9776.19 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.888746E+10 | 9988.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124401E+11 | 10631.49 | 12-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.922651E+10 | 10291.01 | 27-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.635061E+10 | 9975.74 | 01-MAR-08:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137601E+10 | 9392.96 | 05-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2691467.00 | 1606.91 | 27-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7799642.96 | 9354.79 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.540525E+09 | 9397.56 | 29-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463261E+10 | 9401.42 | 20-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110104E+11 | 10122.97 | 29-NOV-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128878E+11 | 10408.22 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.584750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128878E+11 | 10631.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.871444E+10 | 10145.19 | 12-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604249E+10 | 9815.89 | 27-FEB-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373023E+10 | 9498.37 | 01-MAR-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.692208E+09 | 8910.69 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2780892.63 | 2033.71 | 27-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4333516.47 | 5516.77 | 31-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.291269E+09 | 8897.70 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289016E+10 | 8922.97 | 27-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.738012E+10 | 9553.76 | 29-NOV-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.892182E+10 | 9929.08 | 15-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.892182E+10 | 10145.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3920017.34 | 3920017.34 | 6704.31 | 19-JAN-07:01 | 6704.31 | 0.00 |
February | 0.00 | 0.00 | 5907676.62 | 5731697.21 | 6768.27 | 07-FEB-07:01 | 6768.27 | 0.00 |
March | 0.00 | 0.00 | 20543412.56 | 20109286.62 | 2819.75 | 18-MAR-06:03 | 2819.75 | 0.00 |
April | 0.00 | 0.00 | 0.254399E+10 | 0.254375E+10 | 26562.89 | 21-APR-16:00 | 26562.89 | 0.00 |
May | 0.00 | 0.00 | 0.605972E+10 | 0.604325E+10 | 37088.99 | 31-MAY-16:00 | 37088.99 | 0.00 |
June | 0.00 | 0.00 | 0.203208E+11 | 0.194842E+11 | 61330.00 | 30-JUN-14:30 | 56359.13 | 0.00 |
July | 0.00 | 0.00 | 0.289050E+11 | 0.266282E+11 | 64342.43 | 11-JUL-15:40 | 60673.51 | 0.00 |
August | 0.00 | 0.00 | 0.169721E+11 | 0.158860E+11 | 59660.43 | 11-AUG-15:50 | 59660.43 | 0.00 |
September | 0.00 | 0.00 | 0.524854E+10 | 0.506043E+10 | 30483.77 | 07-SEP-16:00 | 30483.77 | 0.00 |
October | 0.00 | 0.00 | 50401342.05 | 48225530.85 | 3918.02 | 05-OCT-14:10 | 3918.02 | 0.00 |
November | 0.00 | 0.00 | 2902143.84 | 2876945.62 | 4111.75 | 15-NOV-07:01 | 4111.75 | 0.00 |
December | 0.00 | 0.00 | 2273236.48 | 2273236.48 | 4809.37 | 29-DEC-07:01 | 4809.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.801360E+11 | 0.757289E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2273236.48 | 2273236.48 | 2819.75 | 2819.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.289050E+11 | 0.266282E+11 | 64342.43 | 60673.51 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5277805.70 | 5277805.70 | 6027.61 | 19-JAN-07:11 | 6027.61 | 0.00 |
February | 0.00 | 0.00 | 6063631.50 | 6024295.45 | 8314.17 | 09-FEB-07:01 | 8314.17 | 0.00 |
March | 0.00 | 0.00 | 13259086.12 | 13117325.06 | 9482.94 | 21-MAR-06:01 | 9482.94 | 0.00 |
April | 0.00 | 0.00 | 0.465738E+09 | 0.465529E+09 | 16659.43 | 25-APR-15:50 | 16659.43 | 0.00 |
May | 0.00 | 0.00 | 0.422810E+10 | 0.421650E+10 | 37453.38 | 31-MAY-16:00 | 37453.38 | 0.00 |
June | 0.00 | 0.00 | 0.201830E+11 | 0.193494E+11 | 64767.20 | 30-JUN-12:05 | 55784.71 | 0.00 |
July | 0.00 | 0.00 | 0.270192E+11 | 0.248654E+11 | 60445.25 | 11-JUL-15:30 | 56718.59 | 0.00 |
August | 0.00 | 0.00 | 0.146386E+11 | 0.135766E+11 | 54804.23 | 11-AUG-15:20 | 54804.23 | 0.00 |
September | 0.00 | 0.00 | 0.507592E+09 | 0.486531E+09 | 16414.20 | 07-SEP-12:04 | 16414.20 | 0.00 |
October | 0.00 | 0.00 | 64221229.25 | 62183871.24 | 9313.38 | 18-OCT-06:01 | 9313.38 | 0.00 |
November | 0.00 | 0.00 | 4751974.15 | 4751974.15 | 6009.41 | 04-NOV-06:03 | 6009.41 | 0.00 |
December | 0.00 | 0.00 | 3596013.61 | 3590929.89 | 3727.83 | 21-DEC-07:11 | 3727.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.671394E+11 | 0.630550E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 3596013.61 | 3590929.89 | 3727.83 | 3727.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.270192E+11 | 0.248654E+11 | 64767.20 | 56718.59 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2019319.21 | 2019319.21 | 1691.41 | 19-JAN-07:11 | 1691.41 | 0.00 |
February | 0.00 | 0.00 | 1835220.85 | 1816875.86 | 3686.55 | 09-FEB-07:01 | 3686.55 | 0.00 |
March | 0.00 | 0.00 | 4042724.20 | 3899369.45 | 4345.69 | 23-MAR-06:01 | 4345.69 | 0.00 |
April | 0.00 | 0.00 | 0.872535E+09 | 0.871687E+09 | 25728.69 | 21-APR-14:10 | 25728.69 | 0.00 |
May | 0.00 | 0.00 | 0.410337E+10 | 0.408437E+10 | 38926.35 | 31-MAY-16:00 | 38926.35 | 0.00 |
June | 0.00 | 0.00 | 0.204598E+11 | 0.195972E+11 | 67300.40 | 30-JUN-12:30 | 59815.60 | 0.00 |
July | 0.00 | 0.00 | 0.274544E+11 | 0.252798E+11 | 66405.71 | 23-JUL-14:21 | 66405.71 | 0.00 |
August | 0.00 | 0.00 | 0.143789E+11 | 0.132466E+11 | 57074.56 | 11-AUG-15:50 | 57074.56 | 0.00 |
September | 0.00 | 0.00 | 0.112088E+10 | 0.109214E+10 | 23939.64 | 07-SEP-15:20 | 23939.64 | 0.00 |
October | 0.00 | 0.00 | 55821273.52 | 52373300.61 | 6468.86 | 02-OCT-06:03 | 6468.86 | 0.00 |
November | 0.00 | 0.00 | 1142847.18 | 1140953.94 | 1010.15 | 13-NOV-06:40 | 1010.15 | 0.00 |
December | 0.00 | 0.00 | 2111713.43 | 2111713.43 | 1038.45 | 01-DEC-06:20 | 1038.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.684569E+11 | 0.642352E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1142847.18 | 1140953.94 | 1010.15 | 1010.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.274544E+11 | 0.252798E+11 | 67300.40 | 66405.71 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 66615.61 | 296186.77 | 12-JAN-07:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 47878.03 | 296050.97 | 27-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 23188.55 | 275329.34 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3995.12 | 237474.67 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 301.33 | 15943.95 | 30-MAY-06:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 62.13 | 11911.65 | 15-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 45.73 | 13424.42 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 139.62 | 56394.85 | 31-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1307.30 | 195742.60 | 27-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13783.74 | 213149.95 | 20-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56404.73 | 277636.36 | 27-NOV-07:11 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 73230.49 | 285333.23 | 15-DEC-07:25 |
Annual Sum or Average | 0.00 | 23808.55 | ||||
Minimum of Months | 0.00 | 0.00 | 45.73 | 11911.65 | ||
Maximum of Months | 0.00 | 0.00 | 73230.49 | 296186.77 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2106.65 | 7651.70 | 30-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2119.74 | 7651.73 | 17-FEB-12:19 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 2267.31 | 7651.66 | 02-MAR-12:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2107.71 | 9281.87 | 24-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2172.08 | 7651.58 | 04-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2149.54 | 7461.23 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1886.34 | 7150.85 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2036.91 | 6936.47 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1887.74 | 6889.75 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1923.50 | 7094.14 | 31-OCT-11:25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2024.11 | 7375.22 | 30-NOV-12:19 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2016.79 | 7651.70 | 29-DEC-12:16 |
Annual Sum or Average | 0.00 | 2057.87 | ||||
Minimum of Months | 0.00 | 0.00 | 1886.34 | 6889.75 | ||
Maximum of Months | 0.00 | 0.00 | 2267.31 | 9281.87 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.221647E+10 | 0.44 | 2834.41 | 02-JAN-05:01 | 0.84 |
February | 0.168187E+10 | 0.41 | 2834.41 | 01-FEB-07:01 | 0.84 |
March | 0.144228E+10 | 0.35 | 2834.41 | 01-MAR-07:01 | 0.85 |
April | 0.168254E+10 | 0.33 | 5115.49 | 24-APR-06:01 | 1.19 |
May | 0.324199E+10 | 0.42 | 6454.69 | 31-MAY-15:20 | 1.37 |
June | 0.486763E+10 | 0.53 | 9943.65 | 12-JUN-06:01 | 1.79 |
July | 0.516679E+10 | 0.52 | 9961.81 | 12-JUL-15:20 | 1.79 |
August | 0.445927E+10 | 0.49 | 9344.17 | 11-AUG-15:50 | 1.71 |
September | 0.202749E+10 | 0.34 | 4666.85 | 06-SEP-06:03 | 1.12 |
October | 0.129308E+10 | 0.30 | 1943.90 | 03-OCT-14:20 | 0.69 |
November | 0.158186E+10 | 0.35 | 2834.41 | 13-NOV-06:02 | 0.84 |
December | 0.207292E+10 | 0.42 | 2834.41 | 01-DEC-07:01 | 0.85 |
Annual Sum or Average | 0.317342E+11 | 0.41 | |||
Minimum of Months | 0.129308E+10 | 0.30 | 1943.90 | 0.69 | |
Maximum of Months | 0.516679E+10 | 0.53 | 9961.81 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176326E+10 | 0.41 | 3071.26 | 02-JAN-07:03 | 0.91 |
February | 0.137679E+10 | 0.39 | 3071.26 | 02-FEB-07:01 | 0.91 |
March | 0.129441E+10 | 0.34 | 3071.26 | 01-MAR-06:01 | 0.92 |
April | 0.167523E+10 | 0.34 | 5084.34 | 21-APR-15:30 | 1.23 |
May | 0.337079E+10 | 0.45 | 7889.15 | 31-MAY-14:05 | 1.61 |
June | 0.497453E+10 | 0.56 | 10473.50 | 05-JUN-06:01 | 1.92 |
July | 0.469586E+10 | 0.52 | 10473.50 | 10-JUL-06:02 | 1.92 |
August | 0.368898E+10 | 0.46 | 10393.94 | 01-AUG-06:01 | 1.91 |
September | 0.148428E+10 | 0.33 | 4339.65 | 08-SEP-12:01 | 1.11 |
October | 0.112986E+10 | 0.31 | 3071.26 | 10-OCT-06:01 | 0.91 |
November | 0.144253E+10 | 0.37 | 3071.26 | 01-NOV-06:01 | 0.91 |
December | 0.166771E+10 | 0.39 | 3071.26 | 01-DEC-06:03 | 0.92 |
Annual Sum or Average | 0.285642E+11 | 0.41 | |||
Minimum of Months | 0.112986E+10 | 0.31 | 3071.26 | 0.91 | |
Maximum of Months | 0.497453E+10 | 0.56 | 10473.50 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.219870E+10 | 0.47 | 2866.75 | 01-JAN-00:42 | 0.83 |
February | 0.177029E+10 | 0.46 | 2866.75 | 01-FEB-05:01 | 0.83 |
March | 0.163103E+10 | 0.41 | 2866.75 | 01-MAR-05:01 | 0.84 |
April | 0.157532E+10 | 0.35 | 4237.78 | 21-APR-15:40 | 1.04 |
May | 0.283785E+10 | 0.41 | 7289.25 | 31-MAY-14:50 | 1.44 |
June | 0.440063E+10 | 0.50 | 9678.92 | 22-JUN-06:02 | 1.72 |
July | 0.415719E+10 | 0.47 | 11398.08 | 24-JUL-06:02 | 1.90 |
August | 0.308147E+10 | 0.42 | 7849.22 | 10-AUG-15:30 | 1.51 |
September | 0.132999E+10 | 0.33 | 2866.75 | 25-SEP-06:02 | 0.83 |
October | 0.140106E+10 | 0.37 | 2866.75 | 03-OCT-06:02 | 0.83 |
November | 0.200486E+10 | 0.47 | 2866.75 | 01-NOV-05:01 | 0.83 |
December | 0.225214E+10 | 0.48 | 2866.75 | 01-DEC-05:01 | 0.84 |
Annual Sum or Average | 0.286405E+11 | 0.43 | |||
Minimum of Months | 0.132999E+10 | 0.33 | 2866.75 | 0.83 | |
Maximum of Months | 0.440063E+10 | 0.50 | 11398.08 | 1.90 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.132790E+10 | 0.120707E+10 | 1224.96 | 12-JAN-07:04 | 1113.49 | 1113.49 | 42.08 | 3.94 |
February | 0.921493E+09 | 0.837637E+09 | 1223.10 | 27-FEB-07:55 | 1111.80 | 1111.80 | 42.02 | 3.94 |
March | 0.546039E+09 | 0.496349E+09 | 1160.89 | 01-MAR-07:15 | 1055.25 | 1055.25 | 42.51 | 3.77 |
April | 98635746.32 | 89659893.41 | 939.55 | 03-APR-06:01 | 854.05 | 854.05 | 46.31 | 2.39 |
May | 11325266.80 | 10294667.52 | 184.72 | 26-MAY-16:03 | 167.91 | 167.91 | 46.94 | 0.20 |
June | 2471853.25 | 2246914.61 | 155.14 | 01-JUN-06:05 | 141.02 | 141.02 | 46.44 | 0.17 |
July | 1685669.03 | 1532273.15 | 145.17 | 05-JUL-06:20 | 131.96 | 131.96 | 41.38 | 0.16 |
August | 5154807.33 | 4685719.87 | 513.36 | 31-AUG-06:02 | 466.65 | 466.65 | 40.20 | 0.68 |
September | 34475179.32 | 31337938.00 | 906.72 | 30-SEP-06:03 | 824.21 | 824.21 | 40.90 | 2.06 |
October | 0.342971E+09 | 0.311760E+09 | 937.98 | 31-OCT-06:01 | 852.62 | 852.62 | 45.97 | 2.38 |
November | 0.112089E+10 | 0.101889E+10 | 1170.58 | 28-NOV-07:50 | 1064.06 | 1064.06 | 42.85 | 3.80 |
December | 0.137365E+10 | 0.124865E+10 | 1186.06 | 15-DEC-07:25 | 1078.13 | 1078.13 | 42.23 | 3.84 |
Annual Sum or Average | 0.578670E+10 | 0.526011E+10 | ||||||
Minimum of Months | 1685669.03 | 1532273.15 | 145.17 | 131.96 | 131.96 | 40.20 | 0.16 | |
Maximum of Months | 0.137365E+10 | 0.124865E+10 | 1224.96 | 1113.49 | 1113.49 | 46.94 | 3.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:02 | 2.06 | 2.06 | 57.66 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.54 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.49 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:01 | 2.06 | 2.06 | 56.50 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 56.38 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.39 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 56.34 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 56.65 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 56.70 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 57.74 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:01 | 2.06 | 2.06 | 56.79 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:02 | 2.06 | 2.06 | 56.57 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.34 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 57.74 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 45.32 | 45.32 | 66615.61 | 296186.77 | 12-JAN-07:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 45.01 | 45.01 | 47878.03 | 296050.97 | 27-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 42.66 | 60.00 | 23188.55 | 275329.34 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36.94 | 36.94 | 3995.12 | 237474.67 | 17-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 36.70 | 36.70 | 301.33 | 15943.95 | 30-MAY-06:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 46.66 | 46.66 | 62.13 | 11911.65 | 15-JUN-06:06 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 40.27 | 40.27 | 45.73 | 13424.42 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 44.58 | 44.58 | 139.62 | 56394.85 | 31-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40.90 | 40.90 | 1307.30 | 195742.60 | 27-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.56 | 23.56 | 13783.74 | 213149.95 | 20-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 43.59 | 43.59 | 56404.73 | 277636.36 | 27-NOV-07:11 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 43.39 | 43.39 | 73230.49 | 285333.23 | 15-DEC-07:25 |
Annual Sum or Average | 0.00 | 23808.55 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.56 | 23.56 | 45.73 | 11911.65 | ||
Maximum of Months | 0.00 | 0.00 | 46.66 | 60.00 | 73230.49 | 296186.77 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.65 | 57.65 | 2106.65 | 7651.70 | 30-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.06 | 57.06 | 2119.74 | 7651.73 | 17-FEB-12:19 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.06 | 57.06 | 2267.31 | 7651.66 | 02-MAR-12:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.06 | 57.06 | 2107.71 | 9281.87 | 24-APR-11:06 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.66 | 57.66 | 2172.08 | 7651.58 | 04-MAY-11:17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 2149.54 | 7461.23 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.24 | 57.24 | 1886.34 | 7150.85 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.33 | 57.33 | 2036.91 | 6936.47 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.37 | 57.37 | 1887.74 | 6889.75 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.27 | 56.27 | 1923.50 | 7094.14 | 31-OCT-11:25 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 2024.11 | 7375.22 | 30-NOV-12:19 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.17 | 57.17 | 2016.79 | 7651.70 | 29-DEC-12:16 |
Annual Sum or Average | 0.00 | 2057.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.27 | 56.27 | 1886.34 | 6889.75 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 2267.31 | 9281.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.556003E+11 | 0.00 | 0.00 | 0.221751E+10 | 0.00 | 0.00 |
February | 0.380330E+11 | 0.00 | 0.00 | 0.168346E+10 | 0.00 | 0.00 |
March | 0.222740E+11 | 0.00 | 0.00 | 0.144782E+10 | 0.00 | 0.00 |
April | 0.432227E+10 | 0.00 | 0.00 | 0.228980E+10 | 0.00 | 0.00 |
May | 0.778347E+09 | 0.00 | 0.00 | 0.469179E+10 | 0.00 | 0.00 |
June | 0.167570E+09 | 0.00 | 0.00 | 0.942145E+10 | 0.00 | 0.00 |
July | 0.118087E+09 | 0.00 | 0.00 | 0.115128E+11 | 0.00 | 0.00 |
August | 0.350799E+09 | 0.00 | 0.00 | 0.825266E+10 | 0.00 | 0.00 |
September | 0.166284E+10 | 0.00 | 0.00 | 0.327701E+10 | 0.00 | 0.00 |
October | 0.100527E+11 | 0.00 | 0.00 | 0.130657E+10 | 0.00 | 0.00 |
November | 0.429093E+11 | 0.00 | 0.00 | 0.158264E+10 | 0.00 | 0.00 |
December | 0.597146E+11 | 0.00 | 0.00 | 0.207352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.235984E+12 | 0.00 | 0.00 | 0.497571E+11 | 0.00 | 0.00 |
Minimum of Months | 0.118087E+09 | 0.00 | 0.00 | 0.130657E+10 | 0.00 | 0.00 |
Maximum of Months | 0.597146E+11 | 0.00 | 0.00 | 0.115128E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.491122E+11 | 0.00 | 0.00 | 0.176464E+10 | 0.00 | 0.00 |
February | 0.293746E+11 | 0.00 | 0.00 | 0.137834E+10 | 0.00 | 0.00 |
March | 0.131740E+11 | 0.00 | 0.00 | 0.129787E+10 | 0.00 | 0.00 |
April | 0.138011E+10 | 0.00 | 0.00 | 0.179255E+10 | 0.00 | 0.00 |
May | 14834614.58 | 0.00 | 0.00 | 0.437058E+10 | 0.00 | 0.00 |
June | 989372.48 | 0.00 | 0.00 | 0.948297E+10 | 0.00 | 0.00 |
July | 1128729.48 | 0.00 | 0.00 | 0.106371E+11 | 0.00 | 0.00 |
August | 10015400.88 | 0.00 | 0.00 | 0.696959E+10 | 0.00 | 0.00 |
September | 0.251674E+09 | 0.00 | 0.00 | 0.161356E+10 | 0.00 | 0.00 |
October | 0.782772E+10 | 0.00 | 0.00 | 0.114652E+10 | 0.00 | 0.00 |
November | 0.394121E+11 | 0.00 | 0.00 | 0.144377E+10 | 0.00 | 0.00 |
December | 0.549475E+11 | 0.00 | 0.00 | 0.166866E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.195507E+12 | 0.00 | 0.00 | 0.435661E+11 | 0.00 | 0.00 |
Minimum of Months | 989372.48 | 0.00 | 0.00 | 0.114652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.549475E+11 | 0.00 | 0.00 | 0.106371E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.751321E+11 | 0.00 | 0.00 | 0.219924E+10 | 0.00 | 0.00 |
February | 0.493979E+11 | 0.00 | 0.00 | 0.177079E+10 | 0.00 | 0.00 |
March | 0.272366E+11 | 0.00 | 0.00 | 0.163212E+10 | 0.00 | 0.00 |
April | 0.475537E+10 | 0.00 | 0.00 | 0.178712E+10 | 0.00 | 0.00 |
May | 15167198.30 | 0.00 | 0.00 | 0.381524E+10 | 0.00 | 0.00 |
June | 1315618.87 | 0.00 | 0.00 | 0.899835E+10 | 0.00 | 0.00 |
July | 639762.12 | 0.00 | 0.00 | 0.102259E+11 | 0.00 | 0.00 |
August | 21957056.96 | 0.00 | 0.00 | 0.632897E+10 | 0.00 | 0.00 |
September | 0.152686E+10 | 0.00 | 0.00 | 0.160124E+10 | 0.00 | 0.00 |
October | 0.193740E+11 | 0.00 | 0.00 | 0.141565E+10 | 0.00 | 0.00 |
November | 0.650740E+11 | 0.00 | 0.00 | 0.200516E+10 | 0.00 | 0.00 |
December | 0.829619E+11 | 0.00 | 0.00 | 0.225271E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.325498E+12 | 0.00 | 0.00 | 0.440324E+11 | 0.00 | 0.00 |
Minimum of Months | 639762.12 | 0.00 | 0.00 | 0.141565E+10 | 0.00 | 0.00 |
Maximum of Months | 0.829619E+11 | 0.00 | 0.00 | 0.102259E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.221647E+10 | 3920017.34 | 0.556003E+11 | 0.290596E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168187E+10 | 5907676.62 | 0.380330E+11 | 0.246294E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144228E+10 | 20543412.56 | 0.222740E+11 | 0.278746E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168254E+10 | 0.254399E+10 | 0.432227E+10 | 0.866137E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324199E+10 | 0.605972E+10 | 0.778347E+09 | 0.399923E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.486763E+10 | 0.203208E+11 | 0.167570E+09 | 55353603.62 | 5393913.95 | 0.00 | 0.00 | 0.00 |
July | 0.516679E+10 | 0.289050E+11 | 0.118087E+09 | 0.126210E+09 | 60609230.96 | 0.00 | 0.00 | 0.00 |
August | 0.445927E+10 | 0.169721E+11 | 0.350799E+09 | 77060682.48 | 138558.50 | 0.00 | 0.00 | 0.00 |
September | 0.202749E+10 | 0.524854E+10 | 0.166284E+10 | 0.358813E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129308E+10 | 50401342.05 | 0.100527E+11 | 0.187046E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158186E+10 | 2902143.84 | 0.429093E+11 | 0.276076E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207292E+10 | 2273236.48 | 0.597146E+11 | 0.259095E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317342E+11 | 0.801360E+11 | 0.235984E+12 | 0.166693E+12 | 66141703.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129308E+10 | 2273236.48 | 0.118087E+09 | 55353603.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.516679E+10 | 0.289050E+11 | 0.597146E+11 | 0.290596E+11 | 60609230.96 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176326E+10 | 5277805.70 | 0.491122E+11 | 0.251527E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137679E+10 | 6063631.50 | 0.293746E+11 | 0.219657E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129441E+10 | 13259086.12 | 0.131740E+11 | 0.268736E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167523E+10 | 0.465738E+09 | 0.138011E+10 | 0.916434E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337079E+10 | 0.422810E+10 | 14834614.58 | 0.684844E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.497453E+10 | 0.201830E+11 | 989372.48 | 70551532.45 | 6626429.82 | 0.00 | 0.00 | 0.00 |
July | 0.469586E+10 | 0.270192E+11 | 1128729.48 | 0.156522E+09 | 62121406.81 | 0.00 | 0.00 | 0.00 |
August | 0.368898E+10 | 0.146386E+11 | 10015400.88 | 0.303407E+09 | 35273.56 | 0.00 | 0.00 | 0.00 |
September | 0.148428E+10 | 0.507592E+09 | 0.251674E+09 | 0.523980E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112986E+10 | 64221229.25 | 0.782772E+10 | 0.185835E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144253E+10 | 4751974.15 | 0.394121E+11 | 0.244124E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166771E+10 | 3596013.61 | 0.549475E+11 | 0.223609E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285642E+11 | 0.671394E+11 | 0.195507E+12 | 0.154968E+12 | 68783110.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112986E+10 | 3596013.61 | 989372.48 | 70551532.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.497453E+10 | 0.270192E+11 | 0.549475E+11 | 0.268736E+11 | 62121406.81 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.219870E+10 | 2019319.21 | 0.751321E+11 | 0.257950E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177029E+10 | 1835220.85 | 0.493979E+11 | 0.223855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163103E+10 | 4042724.20 | 0.272366E+11 | 0.269140E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157532E+10 | 0.872535E+09 | 0.475537E+10 | 0.984219E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283785E+10 | 0.410337E+10 | 15167198.30 | 0.102222E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440063E+10 | 0.204598E+11 | 1315618.87 | 49384587.89 | 6257164.08 | 0.00 | 0.00 | 0.00 |
July | 0.415719E+10 | 0.274544E+11 | 639762.12 | 0.133015E+09 | 47939333.38 | 0.00 | 0.00 | 0.00 |
August | 0.308147E+10 | 0.143789E+11 | 21957056.96 | 0.568787E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132999E+10 | 0.112088E+10 | 0.152686E+10 | 0.615744E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140106E+10 | 55821273.52 | 0.193740E+11 | 0.191796E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200486E+10 | 1142847.18 | 0.650740E+11 | 0.249545E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225214E+10 | 2111713.43 | 0.829619E+11 | 0.230619E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286405E+11 | 0.684569E+11 | 0.325498E+12 | 0.160063E+12 | 54196497.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132999E+10 | 1142847.18 | 639762.12 | 49384587.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440063E+10 | 0.274544E+11 | 0.829619E+11 | 0.269140E+11 | 47939333.38 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.221647E+10 | 0.556003E+11 | 0.00 | 0.00 | 1036651.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168187E+10 | 0.380330E+11 | 0.00 | 0.00 | 1586272.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144228E+10 | 0.222740E+11 | 0.00 | 0.00 | 5541032.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168254E+10 | 0.432227E+10 | 0.00 | 0.00 | 0.607262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.324199E+10 | 0.778347E+09 | 0.00 | 0.00 | 0.144981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.486763E+10 | 0.167570E+09 | 0.00 | 0.00 | 0.455382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.516679E+10 | 0.118087E+09 | 0.00 | 0.00 | 0.634604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.445927E+10 | 0.350799E+09 | 0.00 | 0.00 | 0.379339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202749E+10 | 0.166284E+10 | 0.00 | 0.00 | 0.124952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129308E+10 | 0.100527E+11 | 0.00 | 0.00 | 13484149.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158186E+10 | 0.429093E+11 | 0.00 | 0.00 | 777138.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207292E+10 | 0.597146E+11 | 0.00 | 0.00 | 603426.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317342E+11 | 0.235984E+12 | 0.00 | 0.00 | 0.180229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129308E+10 | 0.118087E+09 | 0.00 | 0.00 | 603426.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.516679E+10 | 0.597146E+11 | 0.00 | 0.00 | 0.634604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176326E+10 | 0.491122E+11 | 0.00 | 0.00 | 1372091.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137679E+10 | 0.293746E+11 | 0.00 | 0.00 | 1555980.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129441E+10 | 0.131740E+11 | 0.00 | 0.00 | 3465724.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167523E+10 | 0.138011E+10 | 0.00 | 0.00 | 0.117311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.337079E+10 | 14834614.58 | 0.00 | 0.00 | 0.999790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.497453E+10 | 989372.48 | 0.00 | 0.00 | 0.450844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.469586E+10 | 1128729.48 | 0.00 | 0.00 | 0.594119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.368898E+10 | 10015400.88 | 0.00 | 0.00 | 0.328062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148428E+10 | 0.251674E+09 | 0.00 | 0.00 | 0.129288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112986E+10 | 0.782772E+10 | 0.00 | 0.00 | 16658713.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144253E+10 | 0.394121E+11 | 0.00 | 0.00 | 1239745.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166771E+10 | 0.549475E+11 | 0.00 | 0.00 | 956607.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285642E+11 | 0.195507E+12 | 0.00 | 0.00 | 0.150019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112986E+10 | 989372.48 | 0.00 | 0.00 | 956607.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.497453E+10 | 0.549475E+11 | 0.00 | 0.00 | 0.594119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.219870E+10 | 0.751321E+11 | 0.00 | 0.00 | 545440.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177029E+10 | 0.493979E+11 | 0.00 | 0.00 | 493450.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163103E+10 | 0.272366E+11 | 0.00 | 0.00 | 1091261.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157532E+10 | 0.475537E+10 | 0.00 | 0.00 | 0.211796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283785E+10 | 15167198.30 | 0.00 | 0.00 | 0.977390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.440063E+10 | 1315618.87 | 0.00 | 0.00 | 0.459772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.415719E+10 | 639762.12 | 0.00 | 0.00 | 0.606867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.308147E+10 | 21957056.96 | 0.00 | 0.00 | 0.324750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132999E+10 | 0.152686E+10 | 0.00 | 0.00 | 0.271249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140106E+10 | 0.193740E+11 | 0.00 | 0.00 | 14582976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200486E+10 | 0.650740E+11 | 0.00 | 0.00 | 308957.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.225214E+10 | 0.829619E+11 | 0.00 | 0.00 | 570548.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286405E+11 | 0.325498E+12 | 0.00 | 0.00 | 0.153919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132999E+10 | 639762.12 | 0.00 | 0.00 | 308957.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.440063E+10 | 0.829619E+11 | 0.00 | 0.00 | 0.606867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957289E+09 | 0.00 | 0.00 | 0.24 |
February | 0.900642E+10 | 0.00 | 0.00 | 520548.33 | 0.00 | 0.397328E+09 | 0.491757E+09 | 0.00 | 0.26 |
March | 0.707278E+10 | 0.00 | 0.00 | 6539209.55 | 0.00 | 9259550.23 | 0.324407E+10 | 0.00 | 0.31 |
April | 0.182687E+10 | 0.00 | 0.00 | 31253686.69 | 0.00 | 0.00 | 0.129963E+11 | 0.00 | 0.40 |
May | 0.120372E+10 | 0.00 | 0.00 | 47539271.33 | 0.00 | 0.00 | 0.236041E+11 | 0.00 | 0.89 |
June | 0.876623E+09 | 5704912.37 | 0.00 | 53463418.41 | 0.00 | 0.00 | 0.208687E+11 | 0.00 | 1.20 |
July | 0.106909E+10 | 59856121.45 | 0.00 | 50170133.96 | 7225881.87 | 0.00 | 0.160271E+11 | 0.00 | 1.12 |
August | 0.806716E+09 | 39449.21 | 0.00 | 56738089.21 | 0.00 | 0.00 | 0.224344E+11 | 0.00 | 1.08 |
September | 0.792193E+09 | 0.00 | 0.00 | 40690633.05 | 0.00 | 0.00 | 0.170267E+11 | 0.00 | 0.49 |
October | 0.355685E+10 | 0.00 | 0.00 | 15983591.21 | 0.00 | 0.00 | 0.764822E+10 | 0.00 | 0.34 |
November | 0.112230E+11 | 0.00 | 0.00 | 238191.62 | 0.00 | 99979786.07 | 0.302020E+09 | 0.00 | 0.25 |
December | 0.139490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133908E+09 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.619625E+11 | 65600483.02 | 0.00 | 0.303137E+09 | 7225881.87 | 0.159776E+10 | 0.124643E+12 | 0.00 | 0.57 |
Minimum of Months | 0.792193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.139490E+11 | 59856121.45 | 0.00 | 56738089.21 | 7225881.87 | 0.957289E+09 | 0.236041E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.689510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567450E+10 | 0.00 | 0.00 | 0.26 |
February | 0.630777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411729E+10 | 0.00 | 0.00 | 0.28 |
March | 0.902519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717293E+09 | 0.00 | 0.00 | 0.30 |
April | 0.558365E+10 | 0.00 | 0.00 | 8928350.74 | 0.00 | 24404194.02 | 0.540872E+10 | 0.00 | 0.33 |
May | 0.227485E+10 | 0.00 | 0.00 | 28047287.86 | 0.00 | 0.00 | 0.156565E+11 | 0.00 | 0.65 |
June | 0.149493E+10 | 5217121.52 | 0.00 | 35137187.37 | 0.00 | 0.00 | 0.141267E+11 | 0.00 | 0.86 |
July | 0.158322E+10 | 40378657.87 | 0.00 | 32524952.62 | 8898224.78 | 0.00 | 0.104947E+11 | 0.00 | 0.80 |
August | 0.147330E+10 | 175782.02 | 0.00 | 33428602.19 | 0.00 | 0.00 | 0.141070E+11 | 0.00 | 0.73 |
September | 0.454724E+10 | 0.00 | 0.00 | 12846093.07 | 0.00 | 0.00 | 0.796322E+10 | 0.00 | 0.39 |
October | 0.743369E+10 | 0.00 | 0.00 | 813817.81 | 0.00 | 0.257146E+09 | 0.779656E+09 | 0.00 | 0.28 |
November | 0.832717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442544E+10 | 0.00 | 0.00 | 0.27 |
December | 0.845554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692694E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.634016E+11 | 45771561.41 | 0.00 | 0.151726E+09 | 8898224.78 | 0.221430E+11 | 0.685365E+11 | 0.00 | 0.45 |
Minimum of Months | 0.147330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.902519E+10 | 40378657.87 | 0.00 | 35137187.37 | 8898224.78 | 0.692694E+10 | 0.156565E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.943280E+10 | 0.00 | 0.00 | 0.24 |
February | 0.249337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649323E+10 | 0.00 | 0.00 | 0.26 |
March | 0.563908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298139E+10 | 0.00 | 0.00 | 0.29 |
April | 0.608842E+10 | 0.00 | 0.00 | 4294868.46 | 0.00 | 0.307510E+09 | 0.295456E+10 | 0.00 | 0.30 |
May | 0.316394E+10 | 0.00 | 0.00 | 22310810.41 | 0.00 | 0.00 | 0.130674E+11 | 0.00 | 0.60 |
June | 0.156261E+10 | 10410238.22 | 0.00 | 31966646.54 | 0.00 | 0.00 | 0.132824E+11 | 0.00 | 0.84 |
July | 0.171044E+10 | 36688657.59 | 0.00 | 28852269.77 | 10341678.29 | 0.00 | 0.951454E+10 | 0.00 | 0.77 |
August | 0.203247E+10 | 469013.99 | 0.00 | 25979705.59 | 0.00 | 0.00 | 0.114857E+11 | 0.00 | 0.67 |
September | 0.583062E+10 | 0.00 | 0.00 | 5281348.45 | 0.00 | 54254841.82 | 0.380379E+10 | 0.00 | 0.33 |
October | 0.534934E+10 | 0.00 | 0.00 | 21610.30 | 0.00 | 0.175685E+10 | 0.132489E+09 | 0.00 | 0.28 |
November | 0.174914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918526E+10 | 0.00 | 0.00 | 0.25 |
December | 0.898183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121694E+11 | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.378550E+11 | 47567909.81 | 0.00 | 0.118707E+09 | 10341678.29 | 0.423807E+11 | 0.542409E+11 | 0.00 | 0.42 |
Minimum of Months | 0.898183E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.608842E+10 | 36688657.59 | 0.00 | 31966646.54 | 10341678.29 | 0.121694E+11 | 0.132824E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17815207.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428993E+10 | 0.00 | 0.00 | 0.41 |
February | 18024178.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313065E+10 | 0.00 | 0.00 | 0.38 |
March | 0.262704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210466E+10 | 0.00 | 0.00 | 0.35 |
April | 0.141397E+10 | 0.00 | 0.00 | 280140.54 | 0.00 | 0.428331E+09 | 0.238467E+09 | 0.00 | 0.32 |
May | 0.912048E+09 | 0.00 | 0.00 | 4735977.73 | 0.00 | 318696.12 | 0.278670E+10 | 0.00 | 0.67 |
June | 0.273070E+09 | 3850322.10 | 0.00 | 10419705.22 | 0.00 | 0.00 | 0.401383E+10 | 0.00 | 1.18 |
July | 0.370261E+09 | 11466988.32 | 0.00 | 8747810.02 | 2352761.61 | 0.00 | 0.266615E+10 | 0.00 | 1.05 |
August | 0.715896E+09 | 121234.20 | 0.00 | 5318961.64 | 0.00 | 3560389.52 | 0.231167E+10 | 0.00 | 0.75 |
September | 0.161512E+10 | 0.00 | 0.00 | 250371.69 | 0.00 | 0.231360E+09 | 0.258199E+09 | 0.00 | 0.34 |
October | 0.445638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133693E+10 | 0.00 | 0.00 | 0.32 |
November | 13876423.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412159E+10 | 0.00 | 0.00 | 0.40 |
December | 21435911.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538686E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.607985E+10 | 15438544.62 | 0.00 | 29752966.84 | 2352761.61 | 0.210342E+11 | 0.122750E+11 | 0.00 | 0.55 |
Minimum of Months | 13876423.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.161512E+10 | 11466988.32 | 0.00 | 10419705.22 | 2352761.61 | 0.538686E+10 | 0.401383E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10434042.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327189E+10 | 0.00 | 0.00 | 0.45 |
February | 37098621.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190387E+10 | 0.00 | 0.00 | 0.36 |
March | 0.418184E+09 | 0.00 | 0.00 | 168120.21 | 0.00 | 0.967424E+09 | 60003396.85 | 0.00 | 0.33 |
April | 0.509670E+09 | 0.00 | 0.00 | 2760640.61 | 0.00 | 0.135075E+09 | 0.126594E+10 | 0.00 | 0.45 |
May | 0.280853E+09 | 0.00 | 0.00 | 10124596.44 | 0.00 | 0.00 | 0.508384E+10 | 0.00 | 1.44 |
June | 0.110568E+09 | 3047665.12 | 0.00 | 11905219.73 | 0.00 | 0.00 | 0.479230E+10 | 0.00 | 1.95 |
July | 0.136523E+09 | 8822579.46 | 0.00 | 11656885.67 | 1309037.73 | 0.00 | 0.347217E+10 | 0.00 | 1.85 |
August | 0.219556E+09 | 84480.92 | 0.00 | 8369859.44 | 0.00 | 530033.12 | 0.354085E+10 | 0.00 | 1.34 |
September | 0.690533E+09 | 0.00 | 0.00 | 1711842.03 | 0.00 | 69095287.00 | 0.839931E+09 | 0.00 | 0.40 |
October | 0.394427E+09 | 0.00 | 0.00 | 44193.11 | 0.00 | 0.658837E+09 | 14812916.34 | 0.00 | 0.30 |
November | 8129305.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280310E+10 | 0.00 | 0.00 | 0.42 |
December | 12551429.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376825E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.282853E+10 | 11954725.50 | 0.00 | 46741357.24 | 1309037.73 | 0.135781E+11 | 0.190698E+11 | 0.00 | 0.82 |
Minimum of Months | 8129305.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.690533E+09 | 8822579.46 | 0.00 | 11905219.73 | 1309037.73 | 0.376825E+10 | 0.508384E+10 | 0.00 | 1.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72604314.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426857E+10 | 0.00 | 0.00 | 0.39 |
February | 0.322036E+09 | 0.00 | 0.00 | 243500.84 | 0.00 | 0.236399E+10 | 80012777.38 | 0.00 | 0.34 |
March | 0.577247E+09 | 0.00 | 0.00 | 3064944.03 | 0.00 | 0.121804E+10 | 0.108666E+10 | 0.00 | 0.42 |
April | 0.577825E+09 | 0.00 | 0.00 | 9737405.19 | 0.00 | 0.192818E+09 | 0.460752E+10 | 0.00 | 0.75 |
May | 0.604906E+09 | 0.00 | 0.00 | 13783050.25 | 0.00 | 293204.37 | 0.707342E+10 | 0.00 | 1.42 |
June | 0.294359E+09 | 5729020.74 | 0.00 | 14999484.73 | 0.00 | 0.00 | 0.579805E+10 | 0.00 | 1.77 |
July | 0.339077E+09 | 22119202.97 | 0.00 | 14948622.93 | 1474416.64 | 0.00 | 0.388995E+10 | 0.00 | 1.64 |
August | 0.440905E+09 | 163265.23 | 0.00 | 14114578.20 | 0.00 | 401911.39 | 0.531398E+10 | 0.00 | 1.51 |
September | 0.921952E+09 | 0.00 | 0.00 | 5683677.14 | 0.00 | 97168859.38 | 0.274170E+10 | 0.00 | 0.59 |
October | 0.601275E+09 | 0.00 | 0.00 | 1267675.00 | 0.00 | 0.812290E+09 | 0.536780E+09 | 0.00 | 0.34 |
November | 0.122854E+09 | 0.00 | 0.00 | 16193.81 | 0.00 | 0.361158E+10 | 9134231.76 | 0.00 | 0.36 |
December | 19721303.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535287E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.489476E+10 | 28011488.94 | 0.00 | 77859132.13 | 1474416.64 | 0.179180E+11 | 0.311372E+11 | 0.00 | 0.83 |
Minimum of Months | 19721303.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.921952E+09 | 22119202.97 | 0.00 | 14999484.73 | 1474416.64 | 0.535287E+10 | 0.707342E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 10408591.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343285E+10 | 0.00 | 0.00 | 0.47 |
February | 31216946.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215843E+10 | 0.00 | 0.00 | 0.39 |
March | 0.270869E+09 | 0.00 | 0.00 | 45554.63 | 0.00 | 0.124676E+10 | 24918710.96 | 0.00 | 0.34 |
April | 0.544891E+09 | 0.00 | 0.00 | 2904506.28 | 0.00 | 0.189789E+09 | 0.151092E+10 | 0.00 | 0.52 |
May | 0.418505E+09 | 0.00 | 0.00 | 6128926.33 | 0.00 | 558878.85 | 0.302250E+10 | 0.00 | 1.03 |
June | 0.176139E+09 | 3917501.19 | 0.00 | 8817048.48 | 0.00 | 0.00 | 0.309106E+10 | 0.00 | 1.60 |
July | 0.213196E+09 | 14910396.04 | 0.00 | 7213285.09 | 603873.76 | 0.00 | 0.190701E+10 | 0.00 | 1.35 |
August | 0.348251E+09 | 127422.13 | 0.00 | 5675234.16 | 0.00 | 1059363.78 | 0.209753E+10 | 0.00 | 1.08 |
September | 0.784890E+09 | 0.00 | 0.00 | 1092039.80 | 0.00 | 0.109400E+09 | 0.629472E+09 | 0.00 | 0.39 |
October | 0.295181E+09 | 0.00 | 0.00 | 8232.84 | 0.00 | 0.779713E+09 | 6494039.99 | 0.00 | 0.31 |
November | 10274274.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283768E+10 | 0.00 | 0.00 | 0.43 |
December | 12520813.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380258E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.311634E+10 | 18955319.37 | 0.00 | 31884827.61 | 603873.76 | 0.145588E+11 | 0.122899E+11 | 0.00 | 0.70 |
Minimum of Months | 10274274.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.784890E+09 | 14910396.04 | 0.00 | 8817048.48 | 603873.76 | 0.380258E+10 | 0.309106E+10 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51623142.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393504E+10 | 0.00 | 0.00 | 0.37 |
February | 38611394.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313360E+10 | 0.00 | 0.00 | 0.37 |
March | 0.143996E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240857E+10 | 0.00 | 0.00 | 0.34 |
April | 0.142320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616311E+09 | 0.00 | 0.00 | 0.27 |
May | 0.140977E+10 | 0.00 | 0.00 | 1736952.57 | 0.00 | 0.00 | 0.115647E+10 | 0.00 | 0.44 |
June | 0.285040E+09 | 1097838.94 | 0.00 | 7357728.96 | 0.00 | 0.00 | 0.285313E+10 | 0.00 | 0.86 |
July | 0.321038E+09 | 9675355.80 | 0.00 | 7238524.07 | 1544394.95 | 0.00 | 0.220175E+10 | 0.00 | 0.85 |
August | 0.610860E+09 | 5628.03 | 0.00 | 5173828.52 | 0.00 | 0.00 | 0.223985E+10 | 0.00 | 0.67 |
September | 0.170736E+10 | 0.00 | 0.00 | 436547.14 | 0.00 | 35506074.18 | 0.281906E+09 | 0.00 | 0.27 |
October | 0.918601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101459E+10 | 0.00 | 0.00 | 0.28 |
November | 38076848.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354554E+10 | 0.00 | 0.00 | 0.34 |
December | 0.119345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484642E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.706752E+10 | 10778822.78 | 0.00 | 21943581.26 | 1544394.95 | 0.195356E+11 | 0.873309E+10 | 0.00 | 0.45 |
Minimum of Months | 38076848.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.170736E+10 | 9675355.80 | 0.00 | 7357728.96 | 1544394.95 | 0.484642E+10 | 0.285313E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33211705.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358216E+10 | 0.00 | 0.00 | 0.47 |
February | 46798853.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239892E+10 | 0.00 | 0.00 | 0.40 |
March | 0.444615E+09 | 0.00 | 0.00 | 32763.27 | 0.00 | 0.114632E+10 | 14986580.60 | 0.00 | 0.32 |
April | 0.744119E+09 | 0.00 | 0.00 | 1704238.09 | 0.00 | 0.157065E+09 | 0.715024E+09 | 0.00 | 0.32 |
May | 0.289507E+09 | 0.00 | 0.00 | 8070816.57 | 0.00 | 0.00 | 0.391330E+10 | 0.00 | 1.13 |
June | 0.116953E+09 | 1397683.92 | 0.00 | 9781078.45 | 0.00 | 0.00 | 0.391980E+10 | 0.00 | 1.63 |
July | 0.126930E+09 | 9977051.09 | 0.00 | 10191033.16 | 691320.89 | 0.00 | 0.303527E+10 | 0.00 | 1.64 |
August | 0.163553E+09 | 4672.98 | 0.00 | 8715119.79 | 0.00 | 0.00 | 0.354355E+10 | 0.00 | 1.30 |
September | 0.723734E+09 | 0.00 | 0.00 | 2571842.44 | 0.00 | 12156994.22 | 0.100192E+10 | 0.00 | 0.36 |
October | 0.632903E+09 | 0.00 | 0.00 | 111393.50 | 0.00 | 0.521699E+09 | 76619820.59 | 0.00 | 0.28 |
November | 24042151.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264334E+10 | 0.00 | 0.00 | 0.37 |
December | 70445813.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386472E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.341681E+10 | 11379408.00 | 0.00 | 41178285.26 | 691320.89 | 0.143264E+11 | 0.162205E+11 | 0.00 | 0.73 |
Minimum of Months | 24042151.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.744119E+09 | 9977051.09 | 0.00 | 10191033.16 | 691320.89 | 0.386472E+10 | 0.391980E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40733443.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810727E+10 | 0.00 | 0.00 | 0.78 |
February | 0.135701E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567535E+10 | 0.00 | 0.00 | 0.67 |
March | 0.359416E+09 | 0.00 | 0.00 | 1541.93 | 0.00 | 0.371579E+10 | 4216017.88 | 0.00 | 0.53 |
April | 0.969502E+09 | 0.00 | 0.00 | 2475981.25 | 0.00 | 0.110942E+10 | 0.114552E+10 | 0.00 | 0.43 |
May | 0.106416E+10 | 0.00 | 0.00 | 5503220.50 | 0.00 | 0.387812E+09 | 0.284438E+10 | 0.00 | 0.80 |
June | 0.533485E+09 | 2407046.13 | 0.00 | 8550135.96 | 0.00 | 84801900.77 | 0.312317E+10 | 0.00 | 1.14 |
July | 0.520628E+09 | 21252492.54 | 0.00 | 10042860.33 | 540327.24 | 69309094.79 | 0.236318E+10 | 0.00 | 1.22 |
August | 0.624546E+09 | 9827.68 | 0.00 | 9805442.89 | 0.00 | 0.179570E+09 | 0.342924E+10 | 0.00 | 1.18 |
September | 0.112566E+10 | 0.00 | 0.00 | 2957518.71 | 0.00 | 0.797904E+09 | 0.122945E+10 | 0.00 | 0.43 |
October | 0.560497E+09 | 0.00 | 0.00 | 336956.84 | 0.00 | 0.234631E+10 | 0.209990E+09 | 0.00 | 0.45 |
November | 49287299.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788586E+10 | 0.00 | 0.00 | 0.75 |
December | 50951969.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105794E+11 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 0.603457E+10 | 23669366.36 | 0.00 | 39673658.40 | 540327.24 | 0.409388E+11 | 0.143491E+11 | 0.00 | 0.77 |
Minimum of Months | 40733443.77 | 0.00 | 0.00 | 0.00 | 0.00 | 69309094.79 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.112566E+10 | 21252492.54 | 0.00 | 10042860.33 | 540327.24 | 0.105794E+11 | 0.342924E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33108578.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377249E+10 | 0.00 | 0.00 | 0.49 |
February | 34831989.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265834E+10 | 0.00 | 0.00 | 0.43 |
March | 0.225738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152359E+10 | 0.00 | 0.00 | 0.34 |
April | 0.795685E+09 | 0.00 | 0.00 | 1486229.55 | 0.00 | 0.180735E+09 | 0.677668E+09 | 0.00 | 0.34 |
May | 0.533153E+09 | 0.00 | 0.00 | 3531136.34 | 0.00 | 0.00 | 0.183957E+10 | 0.00 | 0.70 |
June | 0.182620E+09 | 816379.96 | 0.00 | 6690957.76 | 0.00 | 0.00 | 0.237557E+10 | 0.00 | 1.24 |
July | 0.214607E+09 | 12464474.18 | 0.00 | 5952580.74 | 846271.65 | 0.00 | 0.162170E+10 | 0.00 | 1.12 |
August | 0.286632E+09 | 6156.53 | 0.00 | 5672600.17 | 0.00 | 0.00 | 0.212201E+10 | 0.00 | 1.01 |
September | 0.846363E+09 | 0.00 | 0.00 | 1364335.29 | 0.00 | 19021089.37 | 0.578607E+09 | 0.00 | 0.31 |
October | 0.612419E+09 | 0.00 | 0.00 | 7865.08 | 0.00 | 0.601374E+09 | 7089245.61 | 0.00 | 0.28 |
November | 27767932.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267741E+10 | 0.00 | 0.00 | 0.38 |
December | 71451811.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393141E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.386438E+10 | 13287010.68 | 0.00 | 24705704.93 | 846271.65 | 0.153644E+11 | 0.922221E+10 | 0.00 | 0.59 |
Minimum of Months | 27767932.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.846363E+09 | 12464474.18 | 0.00 | 6690957.76 | 846271.65 | 0.393141E+10 | 0.237557E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24577480.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398527E+10 | 0.00 | 0.00 | 0.35 |
February | 77362676.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288440E+10 | 0.00 | 0.00 | 0.33 |
March | 0.503945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180416E+10 | 0.00 | 0.00 | 0.31 |
April | 0.149454E+10 | 0.00 | 0.00 | 672740.69 | 0.00 | 0.224358E+09 | 0.462495E+09 | 0.00 | 0.31 |
May | 0.608965E+09 | 0.00 | 0.00 | 6245632.16 | 0.00 | 0.00 | 0.342011E+10 | 0.00 | 0.72 |
June | 0.230910E+09 | 1732667.05 | 0.00 | 11481732.38 | 0.00 | 0.00 | 0.426994E+10 | 0.00 | 1.21 |
July | 0.288360E+09 | 12548757.28 | 0.00 | 9750904.20 | 1876085.69 | 0.00 | 0.293810E+10 | 0.00 | 1.07 |
August | 0.478278E+09 | 45335.35 | 0.00 | 6789854.36 | 0.00 | 0.00 | 0.287973E+10 | 0.00 | 0.80 |
September | 0.160272E+10 | 0.00 | 0.00 | 969133.97 | 0.00 | 38621494.57 | 0.688521E+09 | 0.00 | 0.35 |
October | 0.816581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101185E+10 | 0.00 | 0.00 | 0.29 |
November | 19492328.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363272E+10 | 0.00 | 0.00 | 0.34 |
December | 29205832.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478285E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.617494E+10 | 14326759.68 | 0.00 | 35909997.77 | 1876085.69 | 0.183642E+11 | 0.146589E+11 | 0.00 | 0.54 |
Minimum of Months | 19492328.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.160272E+10 | 12548757.28 | 0.00 | 11481732.38 | 1876085.69 | 0.478285E+10 | 0.426994E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17864492.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302013E+10 | 0.00 | 0.00 | 0.39 |
February | 97010824.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170932E+10 | 0.00 | 0.00 | 0.30 |
March | 0.471673E+09 | 0.00 | 0.00 | 363430.95 | 0.00 | 0.773223E+09 | 0.120889E+09 | 0.00 | 0.28 |
April | 0.522728E+09 | 0.00 | 0.00 | 3462472.11 | 0.00 | 78159559.79 | 0.158592E+10 | 0.00 | 0.47 |
May | 0.236366E+09 | 0.00 | 0.00 | 10656518.36 | 0.00 | 0.00 | 0.525637E+10 | 0.00 | 1.45 |
June | 0.117704E+09 | 1612398.82 | 0.00 | 12040935.78 | 0.00 | 0.00 | 0.466719E+10 | 0.00 | 1.88 |
July | 0.122043E+09 | 9968592.91 | 0.00 | 11637993.91 | 1089662.36 | 0.00 | 0.343584E+10 | 0.00 | 1.77 |
August | 0.173085E+09 | 31758.30 | 0.00 | 9046156.89 | 0.00 | 0.00 | 0.372617E+10 | 0.00 | 1.33 |
September | 0.629451E+09 | 0.00 | 0.00 | 2502043.86 | 0.00 | 18269661.24 | 0.123147E+10 | 0.00 | 0.43 |
October | 0.417502E+09 | 0.00 | 0.00 | 166411.31 | 0.00 | 0.497118E+09 | 89090931.42 | 0.00 | 0.25 |
November | 15389764.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246192E+10 | 0.00 | 0.00 | 0.34 |
December | 19570000.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338534E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.284039E+10 | 11612750.03 | 0.00 | 49875963.15 | 1089662.36 | 0.119435E+11 | 0.201129E+11 | 0.00 | 0.78 |
Minimum of Months | 15389764.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.629451E+09 | 9968592.91 | 0.00 | 12040935.78 | 1089662.36 | 0.338534E+10 | 0.525637E+10 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394511E+10 | 0.00 | 0.00 | 0.35 |
February | 0.489812E+09 | 0.00 | 0.00 | 550623.37 | 0.00 | 0.218847E+10 | 0.168583E+09 | 0.00 | 0.33 |
March | 0.842290E+09 | 0.00 | 0.00 | 4306090.58 | 0.00 | 0.984726E+09 | 0.135770E+10 | 0.00 | 0.45 |
April | 0.737711E+09 | 0.00 | 0.00 | 11267824.07 | 0.00 | 0.102560E+09 | 0.522821E+10 | 0.00 | 0.83 |
May | 0.546348E+09 | 0.00 | 0.00 | 14676562.87 | 0.00 | 0.00 | 0.731512E+10 | 0.00 | 1.47 |
June | 0.283274E+09 | 3722123.25 | 0.00 | 15706056.97 | 0.00 | 0.00 | 0.581384E+10 | 0.00 | 1.77 |
July | 0.316047E+09 | 25549108.60 | 0.00 | 15242730.54 | 997520.40 | 0.00 | 0.390772E+10 | 0.00 | 1.62 |
August | 0.360670E+09 | 59873.52 | 0.00 | 15462999.65 | 0.00 | 0.00 | 0.564635E+10 | 0.00 | 1.56 |
September | 0.964221E+09 | 0.00 | 0.00 | 7320546.29 | 0.00 | 25004213.78 | 0.379528E+10 | 0.00 | 0.73 |
October | 0.884911E+09 | 0.00 | 0.00 | 1902471.57 | 0.00 | 0.659951E+09 | 0.783304E+09 | 0.00 | 0.35 |
November | 0.238462E+09 | 0.00 | 0.00 | 84713.29 | 0.00 | 0.326961E+10 | 26168894.17 | 0.00 | 0.33 |
December | 30577892.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478508E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.584874E+10 | 29331105.37 | 0.00 | 86520619.20 | 997520.40 | 0.159605E+11 | 0.340423E+11 | 0.00 | 0.85 |
Minimum of Months | 30577892.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.964221E+09 | 25549108.60 | 0.00 | 15706056.97 | 997520.40 | 0.478508E+10 | 0.731512E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 16305705.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311451E+10 | 0.00 | 0.00 | 0.40 |
February | 80384685.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202986E+10 | 0.00 | 0.00 | 0.35 |
March | 0.434476E+09 | 0.00 | 0.00 | 164224.30 | 0.00 | 0.105742E+10 | 48371971.60 | 0.00 | 0.32 |
April | 0.650071E+09 | 0.00 | 0.00 | 3427330.65 | 0.00 | 0.102003E+09 | 0.173195E+10 | 0.00 | 0.56 |
May | 0.350374E+09 | 0.00 | 0.00 | 6778259.88 | 0.00 | 0.00 | 0.329323E+10 | 0.00 | 1.09 |
June | 0.168106E+09 | 1133409.86 | 0.00 | 9351813.92 | 0.00 | 0.00 | 0.316385E+10 | 0.00 | 1.61 |
July | 0.200170E+09 | 15254713.27 | 0.00 | 7571268.26 | 780674.68 | 0.00 | 0.199549E+10 | 0.00 | 1.34 |
August | 0.293838E+09 | 46045.39 | 0.00 | 6481511.69 | 0.00 | 0.00 | 0.238302E+10 | 0.00 | 1.13 |
September | 0.823142E+09 | 0.00 | 0.00 | 1743553.92 | 0.00 | 28639285.34 | 0.102886E+10 | 0.00 | 0.46 |
October | 0.538411E+09 | 0.00 | 0.00 | 20292.83 | 0.00 | 0.607853E+09 | 22747662.17 | 0.00 | 0.29 |
November | 18475058.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250362E+10 | 0.00 | 0.00 | 0.36 |
December | 19148763.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337616E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.359290E+10 | 16434168.53 | 0.00 | 35538255.44 | 780674.68 | 0.128201E+11 | 0.136675E+11 | 0.00 | 0.69 |
Minimum of Months | 16305705.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.823142E+09 | 15254713.27 | 0.00 | 9351813.92 | 780674.68 | 0.337616E+10 | 0.329323E+10 | 0.00 | 1.61 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:08
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.953060E+10 | 0.157798E+11 | 0.00 | 0.190659E+12 | 0.578266E+11 |
February | 0.458622E+11 | 0.128045E+11 | 0.00 | 0.167102E+12 | 0.410954E+11 |
March | 0.205312E+12 | 0.162956E+11 | 0.00 | 0.202427E+12 | 0.266463E+11 |
April | 0.351813E+12 | 0.129333E+11 | 0.00 | 0.218802E+12 | 0.101905E+11 |
May | 0.427489E+12 | 0.783621E+10 | 0.00 | 0.274056E+12 | 0.183511E+11 |
June | 0.436583E+12 | 0.436094E+10 | 0.00 | 0.236522E+12 | 0.747305E+11 |
July | 0.396649E+12 | 0.335839E+10 | 0.00 | 0.241072E+12 | 0.101816E+12 |
August | 0.300054E+12 | 0.501217E+10 | 0.00 | 0.245018E+12 | 0.565561E+11 |
September | 0.146033E+12 | 0.702574E+10 | 0.00 | 0.230365E+12 | 0.105774E+11 |
October | 0.657278E+11 | 0.129306E+11 | 0.00 | 0.195757E+12 | 0.174208E+11 |
November | 0.591940E+10 | 0.125002E+11 | 0.00 | 0.193389E+12 | 0.490372E+11 |
December | -0.187281E+11 | 0.143101E+11 | 0.00 | 0.198572E+12 | 0.612460E+11 |
Annual Sum or Average | 0.235318E+13 | 0.125148E+12 | 0.00 | 0.259374E+13 | 0.525494E+12 |
Minimum of Months | -0.187281E+11 | 0.335839E+10 | 0.00 | 0.167102E+12 | 0.101905E+11 |