Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930

Simulation Timestamp: 2024-07-03 12:20:02


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1467.48 294.55 294.55
Net Site Energy 1467.48 294.55 294.55
Total Source Energy 4155.95 834.16 834.16
Net Source Energy 4155.95 834.16 834.16


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 235.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 69.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 233.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 74.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1231.50 235.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 235.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 69.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 233.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 74.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 235.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 69.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 233.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 51.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 74.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 54.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 57.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 40.02 47.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 247.18 47.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 57.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 40.02 47.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 247.18 47.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1231.495 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1231.495 100.00
     
Total On-Site and Utility Electric Sources 1231.495 100.00
Total Electricity End Uses 1231.495 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 304.33
Time Setpoint Not Met During Occupied Cooling 74.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 1651.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
RunPeriod RUNPERIOD 1
Weather File Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Latitude [deg] 47.47
Longitude [deg] -122.3
Elevation [m] 122.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.6636 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 6.6636 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.6636 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.6636 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.6636 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.6636 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.6636 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.6636 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.6636 18.58 8.0700  
Total 4982.19             6.6636 9.29 24.1370  
Conditioned Total 4982.19             6.6636 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 6.6636 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 10-AUG-15:20 26-DEC-07:19 - - - - - - - - - - 02-JAN-12:20
Heating 0.00 184170.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 52126.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 19671.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41670.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 26940.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4176.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 146002.71 184170.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 184170.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 52126.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 19671.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 57.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 26940.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4176.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 255.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 220.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 740.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 163.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 234.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 171.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3900.15 255.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 51.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 44.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 148.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 47.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 782.82 51.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 51.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 44.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 148.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 47.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 34.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 782.82 51.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 2.57 0.291911 0.248000 0.636717 0.778430 0.500000 0.001305 0.000103 0.636717 12.80 0.008000
CORE_MID VAV BOX COMPONENT 2.05 0.366223 0.311000 0.636443 0.976596 0.500000 0.001040 0.000162 0.636443 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 2.10 0.356307 0.303000 0.637329 0.950153 0.500000 0.001069 0.000271 0.934970 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.595401 0.265353 0.226000 0.134561 0.707609 0.500000 0.001436 0.000122 0.421640 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.778355 0.128504 0.109000 0.084841 0.342678 0.500000 0.002965 0.000080 0.275654 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.16 0.135621 0.115000 0.133969 0.361657 0.500000 0.002809 0.000121 0.419151 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 0.853474 0.117186 0.100000 0.085347 0.312496 0.500000 0.003251 0.000079 0.274230 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.474311 0.333097 0.283000 0.134230 0.888259 0.500000 0.001144 0.000091 0.312876 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.643169 0.155514 0.132000 0.084898 0.414704 0.500000 0.002450 0.000060 0.207380 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.955336 0.165378 0.141000 0.134702 0.441008 0.500000 0.002304 0.000090 0.310527 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.713759 0.140125 0.119000 0.084937 0.373666 0.500000 0.002719 0.000060 0.205855 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.523706 0.301680 0.256000 0.134069 0.804480 0.500000 0.001263 0.000095 0.326818 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.778788       0.342487 0.500000 0.002967 0.000062 0.215423 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 1.08 0.146153 0.124000 0.134044 0.389741 0.500000 0.002607 0.000094 0.324297 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 0.796206 0.125615 0.107000 0.085194 0.334973 0.500000 0.003033 0.000062 0.214049 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 11759.97 0.000103 259.17
CORE_MID VAV BOX REHEAT COIL 18531.25 0.000162 463.71
CORE_TOP VAV BOX REHEAT COIL 30985.99 0.000271 818.24
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 13936.97 0.000122 367.59
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 9110.86 0.000080 240.29
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 13854.88 0.000121 365.42
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 9063.91 0.000079 239.05
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 10348.74 0.000091 273.03
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6858.54 0.000060 180.94
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 10271.19 0.000090 270.99
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 6808.23 0.000060 179.61
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 10808.77 0.000095 285.15
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 7123.89 0.000062 187.93
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 10725.60 0.000094 282.96
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 7078.55 0.000062 186.74
PACU_VAV_BOT HEATING COIL 15705.18 0.000137 269.27
PACU_VAV_MID HEATING COIL 16818.90 0.000147 285.67
PACU_VAV_TOP HEATING COIL 16468.64 0.000144 282.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 2.68 1.08 5.35 1.46 4.66 4.66 0.300000 0.313639 4.66
PACU_VAV_MID 2.61 1.07 5.23 1.60 4.33 4.33 0.300000 0.370794 4.33
PACU_VAV_TOP 2.75 1.08 5.50 2.33 4.90 4.90 0.300000 0.474657 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 4.66
PACU_VAV_MID_OA_CONTROLLER 4.33
PACU_VAV_TOP_OA_CONTROLLER 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 4.66 81077.86 0.800742 1.55 27023.25 0.800742
PACU_VAV_MID COOLING COIL 4.33 75862.03 0.800005 1.44 25284.81 0.800005
PACU_VAV_TOP COOLING COIL 4.90 84840.33 0.800474 1.63 28277.28 0.800474
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 4.66
PACU_VAV_MID FAN 4.33
PACU_VAV_TOP FAN 4.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000137
PACU_VAV_MID_HEATC_CONTROLLER 0.000147
PACU_VAV_TOP_HEATC_CONTROLLER 0.000144
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.001979 0.237531
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.001979 590.21 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 226260.06 226260.06 0.001979
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 11.40 8.10 5.40 4.50 5.80 8.30 10.90 13.00 15.60 17.70 18.80 15.10


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 47.47 -122.32 -8.00 122.00 99868 1.1870


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 11.22 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 6.664 89.459 0.000 0.000 0.000 0.000 96.123 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.8668 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.8532 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.101 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.2365 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.2366 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.9196
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9381
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6745
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.383
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.151
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.383
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 4.150
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
39 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
40 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
41 0 21.357363 0.71091016E-01 5.4032014  
42 7 -0.29350128E-12 0.14024199E-14 -0.85558835E-13 0.14795563E-15
43 6 0.27596652E-07 0.24107488E-09 0.63308017E-08 -0.12943591E-12
44 5 -0.18463709E-03 0.20772830E-05 -0.95040309E-04 0.62615177E-08
45 4 0.28572581 0.10171039E-02 0.97375121E-01 -0.32667087E-04
46 3 -7.1391205 0.31676816E-01 -2.3011695 0.28385744E-01
47 2 40.451560 0.11313072 15.110175 -0.32866754
48 1 -80.224209 0.51250674E-01 -29.002757 1.0717664
49 0 46.824341 0.10349526E-02 16.294583  
50 7 -0.29575366E-12 0.13916748E-14 -0.86470795E-13 0.14800413E-15
51 6 0.27759747E-07 0.23770535E-09 0.63667993E-08 -0.13030888E-12
52 5 -0.18546937E-03 0.20460315E-05 -0.95457978E-04 0.62966404E-08
53 4 0.28670590 0.10008406E-02 0.97727300E-01 -0.32804728E-04
54 3 -7.1585449 0.31143840E-01 -2.3069324 0.28480895E-01
55 2 40.515639 0.11114407 15.133849 -0.32938113
56 1 -80.273331 0.50317938E-01 -29.023991 1.0728132
57 0 46.824340 0.10154678E-02 16.294067  
58 7 -0.28281898E-12 0.14025464E-14 -0.82622143E-13 0.19904483E-15
59 6 0.24787521E-07 0.29557932E-09 0.57107416E-08 -0.11447606E-12
60 5 -0.17017937E-03 0.25981591E-05 -0.87765911E-04 0.56555961E-08
61 4 0.26851995 0.12946983E-02 0.91201294E-01 -0.30269387E-04
62 3 -6.7976835 0.40953066E-01 -2.1999024 0.26714449E-01
63 2 39.324706 0.14826279 14.693101 -0.31612152
64 1 -79.359856 0.67961194E-01 -28.628348 1.0533482
65 0 46.824347 0.13883650E-02 16.303898  
66 7 -0.18778705E-08 -0.48456698E-15 0.68415356E-14 -0.90766841E-16
67 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
68 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
69 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
70 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
71 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
72 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
73 0 0.22781756 0.11275910E-04 60.838472  
74 7 -0.17777358E-08 -0.41207670E-15 0.60771148E-14 -0.79247013E-16
75 6 0.66205355E-05 0.45347915E-08 0.31869553E-02 -0.26734852E-04
76 5 -0.47643654E-03 0.26865296E-05 -0.22355891 0.19546881E-02
77 4 0.10961386E-01 0.12229770E-03 4.8267865 -0.45238458E-01
78 3 -0.96263561E-01 0.97262436E-03 -38.005829 0.39848146
79 2 0.34182167 0.16181264E-02 116.45361 -1.4175335
80 1 -0.49337445 0.49308431E-03 -143.88945 2.0487464
81 0 0.24054552 0.11921404E-04 60.838472  
82 7 -0.18778705E-08 -0.48456747E-15 0.68415356E-14 -0.90766840E-16
83 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
84 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
85 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
86 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
87 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
88 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
89 0 0.22781756 0.11275910E-04 60.838472  
90 7 -0.17776120E-08 -0.41258204E-15 0.60425363E-14 -0.82023253E-16
91 6 0.66209765E-05 0.45351028E-08 0.31869540E-02 -0.26734841E-04
92 5 -0.47646911E-03 0.26867147E-05 -0.22355884 0.19546874E-02
93 4 0.10962140E-01 0.12230614E-03 4.8267853 -0.45238446E-01
94 3 -0.96270204E-01 0.97269154E-03 -38.005822 0.39848139
95 2 0.34184528 0.16182383E-02 116.45360 -1.4175333
96 1 -0.49340854 0.49311848E-03 -143.88944 2.0487463
97 0 0.24056214 0.11922214E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.359 35 1 VerySmooth 2.062 2.062 1.000 0.360    
2 WINDOW_U_0.363_SHGC_SOUTH_0.359 36 1 VerySmooth 2.062 2.062 1.000 0.360    
3 WINDOW_U_0.363_SHGC_WEST_0.359 37 1 VerySmooth 2.062 2.062 1.000 0.360    
4 WINDOW_U_0.363_SHGC_NORTH_0.359 38 1 VerySmooth 2.062 2.062 1.000 0.360    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.27216 0.52063 0.52063 0.39490 0.13813 0.18098 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2573E-002
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2641E-002
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.4224E-002
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4284E-002
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6471E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.6944E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1337E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1567E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1623
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.9225E-002
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1866
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1161
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1060
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7045E-002
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5658E-002
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7130E-002
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2572E-002
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2644E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.4224E-002
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.4288E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.6472E-003
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.6962E-003
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1335E-003
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1565E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.2304E-002
26 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.2846E-002
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8309E-002
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9927E-002
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8970E-002
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5043E-002
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.3611E-002
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5268E-002
33 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5254E-004
34 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.5531E-004
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.1996E-004
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.2197E-004
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8087E-004
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8154E-004
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8245E-004
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8324E-004
41 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6869E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.7449E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.9039E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9509E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3474E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3809E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1335E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1565E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6058E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6401E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.5557E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0181E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.2282E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3531E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.5658E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7130E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6871E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.7454E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.9039E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9508E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3472E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3794E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1337E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.1567E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.9163E-002
66 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1214E-002
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.4250E-002
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7806E-002
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.6747E-002
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3962E-002
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.3611E-002
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.5268E-002
73 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.3487E-004
74 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.4506E-004
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9713E-004
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.0906E-004
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6797E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.7106E-004
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.8247E-004
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.8326E-004
81 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1612
82 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1154
83 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1821
84 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1336
85 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1142
86 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.9166E-002
87 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.2056E-002
88 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.4300E-002
89 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.9837E-002
90 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 4.1443E-002
91 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.6075E-002
92 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.8659E-002
93 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.7319E-002
94 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.4067E-002
95 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2614E-002
96 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4669E-002
97 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2170E-002
98 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.4103E-002
99 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.0968E-002
100 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.6778E-002
101 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.7687E-002
102 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9509E-002
103 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.2056E-002
104 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4300E-002
105 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.6810E-002
106 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.9904E-002
107 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.2167E-002
108 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6662E-002
109 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.5169E-002
110 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.3039E-002
111 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.2615E-002
112 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4670E-002
113 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1613
114 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1154
115 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1821
116 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1336
117 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1142
118 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.9159E-002
119 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.2051E-002
120 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.4297E-002
121 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.9837E-002
122 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 4.1440E-002
123 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.6075E-002
124 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.8657E-002
125 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.7315E-002
126 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.4064E-002
127 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2609E-002
128 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4667E-002
129 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2172E-002
130 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.4102E-002
131 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.0969E-002
132 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.6777E-002
133 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.7684E-002
134 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9507E-002
135 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.2051E-002
136 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4297E-002
137 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.6810E-002
138 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.9902E-002
139 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.2167E-002
140 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6659E-002
141 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.5165E-002
142 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.3036E-002
143 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.2610E-002
144 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4667E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 35135.98406 35135.98406 2.56741 2.56741 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 5440.44009 5440.44009 0.23236 0.42469 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 28034.56172 28034.56172 2.04644 2.04644 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 21.70400 8.80930E-003 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 12214.43268 12214.43268 0.52325 0.52325 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 28537.10226 28537.10226 2.10340 2.10340 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 29.19200 8.82116E-003 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 21706.23749 21706.23749 0.93497 0.93497 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 8078.00370 8078.00370 0.59540 0.59540 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 29.29600 8.82133E-003 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 9754.38077 9754.38077 0.42164 0.42164 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 10560.29281 10560.29281 0.77835 0.77835 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 23.68000 8.81240E-003 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 6376.43691 6376.43691 0.27565 0.27565 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 15805.33482 15805.33482 1.16495 1.16495 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 29.14000 8.82108E-003 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 9696.99442 9696.99442 0.41915 0.41915 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 11579.47229 11579.47229 0.85347 0.85347 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 6343.61614 6343.61614 0.27423 0.27423 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 6435.11725 6435.11725 0.47431 0.47431 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 7245.44767 7245.44767 0.31288 0.31288 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 8726.19066 8726.19066 0.64317 0.64317 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 22.36267 8.81033E-003 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 4801.56001 4801.56001 0.20738 0.20738 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 12961.43090 12961.43090 0.95534 0.95534 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 29.31333 8.82136E-003 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 7191.22331 7191.22331 0.31053 0.31053 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 9683.88380 9683.88380 0.71376 0.71376 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 26.90400 8.81750E-003 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 4766.39869 4766.39869 0.20586 0.20586 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 7105.28388 7105.28388 0.52371 0.52371 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 29.40000 8.82150E-003 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 7567.64939 7567.64939 0.32682 0.32682 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 10566.16824 10566.16824 0.77879 0.77879 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 23.35067 8.81188E-003 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 4987.43258 4987.43258 0.21542 0.21542 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 14666.42763 14666.42763 1.08100 1.08100 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 29.05333 8.82094E-003 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 7509.52675 7509.52675 0.32430 0.32430 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 10802.48173 10802.48173 0.79621 0.79621 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 27.94400 8.81916E-003 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 4955.74736 4955.74736 0.21405 0.21405 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -4.20000 2.69032E-003 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 68393.76 4.65928 4.65928 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 19175.52 1.46133 1.46133 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00
3 PACU_VAV_MID Cooling Sensible 63935.23 4.32542 4.32542 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 PACU_VAV_MID Heating Sensible 19233.83 1.60384 1.60384 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00
5 PACU_VAV_TOP Cooling Sensible 71560.94 4.89963 4.89963 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 19311.54 2.32564 2.32564 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.56741
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29191
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24800
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63672
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.77843
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.30519E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.02881E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63672
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11759.97324
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.02881E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 259.17119
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.04644
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36622
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31100
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63644
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.97660
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.04035E-003
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.62119E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63644
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18531.25083
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.62119E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 463.70760
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.10340
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35631
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.30300
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63733
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.95015
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.06930E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.71079E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93497
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30985.98789
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.71079E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 818.23875
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.59540
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26535
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22600
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13456
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.70761
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.43582E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21927E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42164
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13936.97109
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21927E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 367.58698
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77835
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12850
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10900
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48407E-002
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34268
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.96489E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.97058E-005
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27565
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9110.86475
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.97058E-005
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 240.29089
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16495
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13562
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11500
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13397
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36166
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.80929E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21208E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.41915
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13854.87512
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21208E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 365.42379
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.85347
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11719
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10000
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.53474E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31250
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.25124E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.92951E-005
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.27423
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9063.91319
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.92951E-005
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.05373
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.47431
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33310
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28300
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13423
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88826
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14381E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.05353E-005
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31288
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10348.74081
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.05353E-005
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 273.03061
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.64317
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15551
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13200
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.48983E-002
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41470
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.44994E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.00015E-005
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20738
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6858.53866
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.00015E-005
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 180.93893
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.95534
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16538
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14100
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13470
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44101
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.30381E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.98568E-005
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31053
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10271.18579
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.98568E-005
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 270.98621
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.71376
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14012
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11900
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.49374E-002
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37367
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.71901E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.95614E-005
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20586
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6808.23224
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.95614E-005
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 179.61330
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.52371
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.30168
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25600
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13407
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.80448
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.26293E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.45598E-005
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32682
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10808.76588
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.45598E-005
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 285.15403
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77879
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34249
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.96653E-003
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.23229E-005
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21542
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
177 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7123.88896
178 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.23229E-005
179 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 187.93152
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.08100
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14615
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12400
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13404
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38974
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.60686E-003
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.38323E-005
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32430
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
191 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10725.60307
192 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.38323E-005
193 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 282.96257
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.79621
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12561
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10700
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.51940E-002
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33497
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.03308E-003
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.19263E-005
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.21405
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
205 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7078.55140
206 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.19263E-005
207 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 186.73680
208 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.67699
209 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07549
210 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 5.35398
211 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 1.46133
212 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 4.65928
213 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 4.65928
214 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
215 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.31364
216 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.61307
217 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07464
218 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 5.22614
219 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 1.60384
220 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.32542
221 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 4.32542
222 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.37079
224 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.74779
225 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07605
226 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 5.49557
227 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 2.32564
228 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 4.89963
229 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 4.89963
230 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.47466
232 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 4.65928
233 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 4.32542
234 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 4.89963
235 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.65928
236 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.65928
237 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 81077.85697
238 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80074
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.55294
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 27023.24973
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80074
242 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 15705.17518
243 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.37396E-004
244 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 269.26719
245 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 4.65928
246 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.37396E-004
247 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.32542
248 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.32542
249 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 75862.03064
250 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80001
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.44166
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 25284.81481
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80001
254 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 16818.90041
255 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.47139E-004
256 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 285.66846
257 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 4.32542
258 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.47139E-004
259 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.89963
260 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 4.89963
261 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 84840.32951
262 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80047
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.63305
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 28277.28183
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80047
266 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 16468.63988
267 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.44075E-004
268 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 282.39842
269 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 4.89963
270 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.44075E-004
271 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.97942E-003
272 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.23753
273 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.97942E-003
274 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 590.21276
275 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
276 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 226260.05841
277 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 226260.06000
278 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.97942E-003
279 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
280 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
281 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
282 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
283 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 11145.49
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 17551.17
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 29364.85
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 13204.85
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 8632.21
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 13127.08
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 8587.73
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 9805.67
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 6498.56
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9732.19
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 6450.90
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 10241.46
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 6749.93
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 10162.68
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 6706.98
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 13111.84
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 13788.27
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 13753.60


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 79867.25 272518.36 11.71 3.03 3.35 3.52 3.73 10.35 11.43 12.02 12.71 5.3121 4.2112 2.8247 1.1558
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 74755.68 255076.97 11.73 3.04 3.36 3.53 3.73 10.37 11.45 12.04 12.74 4.9315 3.9108 2.6239 1.0715
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 83554.88 285101.07 11.70 3.03 3.35 3.52 3.72 10.34 11.42 12.01 12.70 5.5861 4.4267 2.9694 1.2179


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.101 0.945   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.237 0.224   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.867 0.767   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.237 0.224   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.359 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.359 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.359 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.853 0.757   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.359 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 5.6503708339E-002 5.7469674910E-002 Pass Pass 0.1048019956 0.2962851361 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 8.6702256649E-002 5.1166969821E-002 Pass Pass 0.4109584340 0.4734005224 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.8232429965E-002 3.4031709264E-002 Pass Pass 0.2913367119 0.4148561188 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.0190518208E-002 4.2007528083E-002 Pass Pass 0.1301841685 0.3426984095 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 2.2725479213E-002 1.7644966653E-002 Pass Pass 0.6271601234 1.2689121640 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 1.8428229633E-002 2.0314809283E-002 Pass Pass 14.1440669645 49.1742754546 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.2282334132 0.2112440963 Pass Pass 22.5503038374 53.0974818570 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.2346937474 0.2193157187 Pass Pass 23.9341383883 56.8192015923 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.2185780551 0.2052332872 Pass Pass 23.0995464235 54.6959879220 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2386836708 0.2219641073 Pass Pass 23.7134012976 56.2959910406 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 9.8452373722E-002 0.1350563403 Pass Pass 0.6410378164 2.7579044798 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1127473355 0.1567151047 Pass Pass 0.5379692839 2.1575737525 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 9.5596668660E-002 0.1273165107 Pass Pass 0.7228154679 3.2421696141 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1147583903 0.1598848524 Pass Pass 0.5517830040 2.2290598446 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1197208136 0.1335235917 Pass Pass 126.0327044439 1366.8839025929 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1288458795 0.1445488561 Pass Pass 4.6202382582 25.9877792785 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1193594262 0.1310718964 Pass Pass 15.7277761430 143.1696929404 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1303475155 0.1464586026 Pass Pass 3.2238271465 11.5242910166 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3035.47 77.43 0.00 2340.55 451.44 5904.90



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB -4.20 0.00 -4.20 Wetbulb [C] 4.30 20.00
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 29.40 10.40 18.30 Wetbulb [C] 4.20 350.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 22.00 23      
Apr 0.00 0      
May 0.00 0      
Jun 16.00 20      
Jul 0.00 0      
Aug 24.00 18      
Sep 12.00 15      
Oct 61.00 41      
Nov 0.00 0      
Dec 45.00 41      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.945 1.101 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.945 1.101 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.228 0.237 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.767 0.867 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.767 0.867 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.228 0.237 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.757 0.853 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.757 0.853 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.359   41.85 0.00 0.00 41.85 41.85 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.359   1.65 0.00 0.00 1.65 1.65 2.062 0.360 0.396             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.359   21.75 0.00 0.00 21.75 21.75 2.062 0.360 0.396             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.359   41.85 0.00 0.00 41.85 41.85 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.359   1.65 0.00 0.00 1.65 1.65 2.062 0.360 0.396             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.359   65.26 0.00 0.00 65.26 65.26 2.062 0.360 0.396             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.359   43.51 0.00 0.00 43.51 43.51 2.062 0.360 0.396             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.062 0.360 0.396                      
North Total or Average             195.79 2.062 0.360 0.396                      
Non-North Total or Average             456.84 2.062 0.360 0.396                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.71 0.0000 Y 6.93
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.43 0.0000 Y 4.34
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.16 0.0000 Y 6.78
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.38 0.0000 Y 4.33
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.62 0.0000 Y 6.90
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.37 0.0000 Y 4.33
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.11 0.0000 Y 6.77
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.32 0.0000 Y 4.32
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.71 0.0000 Y 6.93
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.43 0.0000 Y 4.34
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.16 0.0000 Y 6.78
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 26.38 0.0000 Y 4.33
Interior Lighting Total       6.6636 4982.19 33199.39               233.88


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   42.59 42.59 4.51
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.55 63.07 4.83
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.55 47.80 42.30
Exterior Lighting Total 5686.19           51.64



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 226260.06 0.80        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   81077.86 64922.48 16155.38 0.80 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   75862.03 60690.03 15172.00 0.80 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   84840.33 67912.45 16927.88 0.80 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   79867.2 3.03 10.35 N/A N/A 11.71
PACU_VAV_MID COOLING COIL   74755.7 3.04 10.37 N/A N/A 11.73
PACU_VAV_TOP COOLING COIL   83554.9 3.03 10.34 N/A N/A 11.70
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 11759.97 11145.49 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 18531.25 17551.17 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 30985.99 29364.85 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13936.97 13204.85 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9110.86 8632.21 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 13854.88 13127.08 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9063.91 8587.73 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 10348.74 9805.67 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 6858.54 6498.56 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 10271.19 9732.19 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 6808.23 6450.90 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 10808.77 10241.46 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 7123.89 6749.93 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 10725.60 10162.68 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 7078.55 6706.98 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 15705.18 13111.84 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 16818.90 13788.27 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 16468.64 13753.60 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 4.66 10199.21 2189.01 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 4.33 9468.40 2189.01 1.00 1.14 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 4.90 10725.34 2189.01 1.00 1.13 General SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.001979 590.21 298174.34 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 79867.25 3.03 10.35 11.71 5.3121 3.35 11.43 4.2112 3.52 12.02 2.8247 3.73 12.71 1.1558
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 74755.68 3.04 10.37 11.73 4.9315 3.36 11.45 3.9108 3.53 12.04 2.6239 3.73 12.74 1.0715
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 83554.88 3.03 10.34 11.70 5.5861 3.35 11.42 4.4267 3.52 12.01 2.9694 3.72 12.70 1.2179
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 35135.98 35135.98 35.72 2.567 2.567 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00885 21.70 0.00881 0.425 0.00
CORE_MID 28034.56 28034.56 28.50 2.046 2.046 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00893 21.70 0.00881 0.425 0.00
CORE_TOP 28537.10 28537.10 29.01 2.103 2.103 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00892 29.19 0.00882 0.425 0.00
PERIMETER_TOP_ZN_3 8078.00 8078.00 38.96 0.595 0.595 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00881 29.30 0.00882 0.090 0.00
PERIMETER_TOP_ZN_2 10560.29 10560.29 80.45 0.778 0.778 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 09:00:00 24.00 24.00 0.00865 23.68 0.00881 0.057 0.00
PERIMETER_TOP_ZN_1 15805.33 15805.33 76.23 1.165 1.165 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00866 29.14 0.00882 0.090 0.00
PERIMETER_TOP_ZN_4 11579.47 11579.47 88.22 0.853 0.853 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00864 27.94 0.00882 0.057 0.00
PERIMETER_BOT_ZN_3 6435.12 6435.12 31.04 0.474 0.474 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00889 29.40 0.00882 0.090 0.00
PERIMETER_BOT_ZN_2 8726.19 8726.19 66.48 0.643 0.643 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 24.00 24.00 0.00869 22.36 0.00881 0.057 0.00
PERIMETER_BOT_ZN_1 12961.43 12961.43 62.51 0.955 0.955 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00870 29.31 0.00882 0.090 0.00
PERIMETER_BOT_ZN_4 9683.88 9683.88 73.78 0.714 0.714 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 24.00 24.00 0.00867 26.90 0.00882 0.057 0.00
PERIMETER_MID_ZN_3 7105.28 7105.28 34.27 0.524 0.524 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00886 29.40 0.00882 0.090 0.00
PERIMETER_MID_ZN_2 10566.17 10566.17 80.50 0.779 0.779 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 08:50:00 24.00 24.00 0.00865 23.35 0.00881 0.057 0.00
PERIMETER_MID_ZN_1 14666.43 14666.43 70.74 1.081 1.081 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 13:20:00 24.00 24.00 0.00867 29.05 0.00882 0.090 0.00
PERIMETER_MID_ZN_4 10802.48 10802.48 82.30 0.796 0.796 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00865 27.94 0.00882 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 5440.44 5440.44 5.53 0.232 0.425 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_MID 12214.43 12214.43 12.42 0.523 0.523 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
CORE_TOP 21706.24 21706.24 22.07 0.935 0.935 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -4.20 0.00269 0.425 0.00
PERIMETER_TOP_ZN_3 9754.38 9754.38 47.05 0.422 0.422 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_2 6376.44 6376.44 48.58 0.276 0.276 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
PERIMETER_TOP_ZN_1 9696.99 9696.99 46.77 0.419 0.419 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.090 0.00
PERIMETER_TOP_ZN_4 6343.62 6343.62 48.33 0.274 0.274 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_3 7245.45 7245.45 34.95 0.313 0.313 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00771 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_2 4801.56 4801.56 36.58 0.207 0.207 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -4.20 0.00269 0.057 0.00
PERIMETER_BOT_ZN_1 7191.22 7191.22 34.68 0.311 0.311 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00770 -4.20 0.00269 0.090 0.00
PERIMETER_BOT_ZN_4 4766.40 4766.40 36.31 0.206 0.206 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00772 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_3 7567.65 7567.65 36.50 0.327 0.327 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00764 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_2 4987.43 4987.43 38.00 0.215 0.215 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00766 -4.20 0.00269 0.057 0.00
PERIMETER_MID_ZN_1 7509.53 7509.53 36.22 0.324 0.324 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00764 -4.20 0.00269 0.090 0.00
PERIMETER_MID_ZN_4 4955.75 4955.75 37.76 0.214 0.214 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00765 -4.20 0.00269 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 4.66 4.66 1.46 1.46 4.6593 1.4613 4.6593 0.3136 0.3000
PACU_VAV_MID 4.33 4.33 1.60 1.60 4.3254 1.6038 4.3254 0.3708 0.3000
PACU_VAV_TOP 4.90 4.90 2.33 2.33 4.8996 2.3256 4.8996 0.4747 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 11759.973 11759.973 0.636717 0.00010288 259.171 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 11759.97 11759.97 0.636717 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 5440.44 0.00 11800.57 11800.57
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 18531.251 18531.251 0.636443 0.00016212 463.708 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 18531.25 18531.25 0.636443 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 12214.43 0.00 18588.99 18588.99
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 30985.988 30985.988 0.934970 0.00027108 818.239 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 30985.99 30985.99 0.934970 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00800000 50.9797 21706.24 0.00 31095.24 31095.24
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 13936.971 13936.971 0.421640 0.00012193 367.587 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13936.97 13936.97 0.421640 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00776788 49.5217 9754.38 0.00 13982.93 13982.93
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 9110.865 9110.865 0.275654 0.00007971 240.291 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9110.86 9110.86 0.275654 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00776794 49.5221 6376.44 0.00 9140.85 9140.85
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 13854.875 13854.875 0.419151 0.00012121 365.424 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13854.88 13854.88 0.419151 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00776560 49.5073 9696.99 0.00 13900.58 13900.58
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 9063.913 9063.913 0.274230 0.00007930 239.054 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9063.91 9063.91 0.274230 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00776605 49.5102 6343.62 0.00 9093.75 9093.75
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 10348.741 10348.741 0.312876 0.00009054 273.031 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10348.74 10348.74 0.312876 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00770725 49.1402 7245.45 0.00 10383.46 10383.46
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 6858.539 6858.539 0.207380 0.00006000 180.939 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6858.54 6858.54 0.207380 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00772094 49.2264 4801.56 0.00 6881.48 6881.48
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 10271.186 10271.186 0.310527 0.00008986 270.986 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10271.19 10271.19 0.310527 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00770240 49.1097 7191.22 0.00 10305.66 10305.66
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 6808.232 6808.232 0.205855 0.00005956 179.613 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6808.23 6808.23 0.205855 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00771641 49.1978 4766.40 0.00 6831.02 6831.02
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 10808.766 10808.766 0.326818 0.00009456 285.154 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10808.77 10808.77 0.326818 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00764471 48.7470 7567.65 0.00 10844.94 10844.94
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 7123.889 7123.889 0.215423 0.00006232 187.932 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7123.89 7123.89 0.215423 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00765912 48.8376 4987.43 0.00 7147.66 7147.66
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 10725.603 10725.603 0.324297 0.00009383 282.963 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 10725.60 10725.60 0.324297 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00763873 48.7093 7509.53 0.00 10761.51 10761.51
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 7078.551 7078.551 0.214049 0.00006193 186.737 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 7078.55 7078.55 0.214049 12.80 11.47 0.00800000 40.00 21.01 0.00800000 -4.20 0.00269032 -4.20 0.0000 21.00 0.00765395 48.8051 4955.75 0.00 7102.18 7102.18
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 81077.857 64922.476 4.659277 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 81904.65 77391.61 4.659277 25.11 16.90 0.00882066 10.99 10.99 0.00850000 29.40 0.00882150 18.34 20.5203 24.00 0.00882045 46.7835 63211.73 0.00 83602.15 65333.93
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 15705.175 15705.175 1.397783 0.00013740 269.267 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 15705.18 15705.18 1.397783 3.38 2.50 0.00423406 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 68.4012 19.72 0.00750669 51.8237 13291.14 0.00 15870.48 15870.48
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 75862.031 60690.033 4.325424 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 76695.45 72254.20 4.325424 25.19 16.95 0.00884009 10.99 10.99 0.00850000 29.40 0.00882150 18.34 22.1042 24.00 0.00884536 46.9138 58683.18 0.00 78223.94 61074.78
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 16818.900 16818.900 1.297627 0.00014714 285.668 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 16818.90 16818.90 1.297627 1.93 1.29 0.00394671 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 73.6806 19.64 0.00721389 50.0736 17190.45 0.00 16687.93 16687.93
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 84840.330 67912.452 4.899629 -999.0 -999.000 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 85664.08 81093.85 4.899629 25.05 16.87 0.00880870 10.99 10.99 0.00850000 29.40 0.00882150 18.34 19.5137 24.00 0.00880560 46.7058 66428.68 0.00 87481.77 68346.33
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 16468.640 16468.640 1.469889 0.00014407 282.398 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 16468.64 16468.64 1.469889 3.41 2.74 0.00439802 12.80 11.47 0.00800000 -4.20 0.00269032 -4.20 65.0457 17.60 0.00739579 58.3067 18797.77 0.00 16647.64 16647.64



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 11759.973 11759.973 0.636717 0.00010288 259.171 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 5.0950 5.197547 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 11759.97 11759.97 1.0000 0.75577720 0.636717 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.10287088 60.00 32.22 27.78 0.000 11759.97 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.67 0.00800000 21.00 0.00800000 50.9797 5440.44 0.00 11800.57 11800.57 0.75577720 12.80 11.60 0.00800000 33059.8 28.11 17.40 0.00800000 48673.6
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 18531.251 18531.251 0.636443 0.00016212 463.708 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 8.0287 8.190244 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 18531.25 18531.25 1.0000 0.75545250 0.636443 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.16210293 60.00 32.22 27.78 0.000 18531.25 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 50.9797 12214.43 0.00 18588.99 18588.99 0.75545250 12.80 11.60 0.00800000 33059.8 36.93 20.26 0.00800000 57666.3
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 30985.988 30985.988 0.934970 0.00027108 818.239 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 13.4247 13.694855 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 30985.99 30985.99 1.0000 1.10980093 0.934970 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.27105129 60.00 32.22 27.78 0.000 30985.99 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 50.9797 21706.24 0.00 31095.24 31095.24 1.10980093 12.80 11.60 0.00800000 33059.8 40.28 21.26 0.00800000 61078.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 13936.971 13936.971 0.421640 0.00012193 367.587 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 6.0382 6.159713 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13936.97 13936.97 1.0000 0.50048280 0.421640 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.12191427 60.00 32.22 27.78 0.000 13936.97 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00776788 21.00 0.00776788 49.5217 9754.38 0.00 13982.93 13982.93 0.50048280 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60998.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 9110.865 9110.865 0.275654 0.00007971 240.291 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 3.9473 4.026723 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9110.86 9110.86 1.0000 0.32719826 0.275654 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.07969769 60.00 32.22 27.78 0.000 9110.86 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00776794 21.00 0.00776794 49.5221 6376.44 0.00 9140.85 9140.85 0.32719826 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 13854.875 13854.875 0.419151 0.00012121 365.424 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 6.0026 6.123429 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13854.88 13854.88 1.0000 0.49752848 0.419151 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.12119613 60.00 32.22 27.78 0.000 13854.88 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00776560 21.00 0.00776560 49.5073 9696.99 0.00 13900.58 13900.58 0.49752848 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60999.1
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 9063.913 9063.913 0.274230 0.00007930 239.054 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 3.9269 4.005971 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9063.91 9063.91 1.0000 0.32550868 0.274230 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.07928698 60.00 32.22 27.78 0.000 9063.91 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00776605 21.00 0.00776605 49.5102 6343.62 0.00 9093.75 9093.75 0.32550868 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60996.9
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 10348.741 10348.741 0.312876 0.00009054 273.031 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 4.4836 4.573826 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10348.74 10348.74 1.0000 0.37138092 0.312876 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09052606 60.00 32.22 27.78 0.000 10348.74 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00770725 21.00 0.00770725 49.1402 7245.45 0.00 10383.46 10383.46 0.37138092 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61018.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 6858.539 6858.539 0.207380 0.00006000 180.939 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 2.9715 3.031264 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6858.54 6858.54 1.0000 0.24615846 0.207380 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.05999537 60.00 32.22 27.78 0.000 6858.54 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00772094 21.00 0.00772094 49.2264 4801.56 0.00 6881.48 6881.48 0.24615846 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61015.3
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 10271.186 10271.186 0.310527 0.00008986 270.986 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 4.4500 4.539549 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10271.19 10271.19 1.0000 0.36859258 0.310527 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.08984765 60.00 32.22 27.78 0.000 10271.19 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.91 0.00770240 21.00 0.00770240 49.1097 7191.22 0.00 10305.66 10305.66 0.36859258 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61019.3
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 6808.232 6808.232 0.205855 0.00005956 179.613 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 2.9497 3.009030 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6808.23 6808.23 1.0000 0.24434838 0.205855 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.05955531 60.00 32.22 27.78 0.000 6808.23 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00771641 21.00 0.00771641 49.1978 4766.40 0.00 6831.02 6831.02 0.24434838 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61015.9
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 10808.766 10808.766 0.326818 0.00009456 285.154 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 4.6829 4.777143 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10808.77 10808.77 1.0000 0.38792950 0.326818 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09455015 60.00 32.22 27.78 0.000 10808.77 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00764471 21.00 0.00764471 48.7470 7567.65 0.00 10844.94 10844.94 0.38792950 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61015.8
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 7123.889 7123.889 0.215423 0.00006232 187.932 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 3.0864 3.148540 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7123.89 7123.89 1.0000 0.25570517 0.215423 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06231653 60.00 32.22 27.78 0.000 7123.89 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00765912 21.00 0.00765912 48.8376 4987.43 0.00 7147.66 7147.66 0.25570517 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61012.6
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 10725.603 10725.603 0.324297 0.00009383 282.963 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 4.6469 4.740387 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 10725.60 10725.60 1.0000 0.38493727 0.324297 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.09382268 60.00 32.22 27.78 0.000 10725.60 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00763873 21.00 0.00763873 48.7093 7509.53 0.00 10761.51 10761.51 0.38493727 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61016.4
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 7078.551 7078.551 0.214049 0.00006193 186.737 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 unknown unknown -999.0 -999.0   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 3.0668 3.128502 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 7078.55 7078.55 1.0000 0.25407396 0.214049 12.80 11.47 0.00800000 33059.8 40.00 21.01 0.00800000 60796.0 0.06191994 60.00 32.22 27.78 0.000 7078.55 -4.20 0.00269032 -4.20 0.00000000 0.0000 20.95 0.00765395 21.00 0.00765395 48.8051 4955.75 0.00 7102.18 7102.18 0.25407396 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.0
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 81077.857 64922.476 4.659277 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2372 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 4.659277 5.53051936   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 81904.65 77391.61 1.0102 5.53051936 4.659277 25.11 16.90 0.00882066 47700.3 10.99 10.99 0.00850000 32479.1 -999.0 -999.00 -999.00 -999.00 10199.209 71705.44 29.40 0.00882150 18.34 0.95610000 20.5203 24.00 0.00882045 24.00 0.00882045 46.7835 63211.73 0.00 83602.15 65333.93 5.31210565 26.67 19.44 0.01118466 55322.4 14.65 14.12 0.00983631 39584.3
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15705.175 15705.175 1.397783 0.00013740 269.267 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_BOT FAN Fan:VariableVolume 4.659277 5.53051936   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 6.8043 6.941205 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:40:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 15705.18 15705.18 1.0000 1.65915581 1.397783 3.38 2.50 0.00423406 14012.1 12.80 11.47 0.00800000 33059.8 0.13738171 60.00 32.22 27.78 0.000 15705.18 -4.20 0.00269032 -4.20 0.95610000 68.4012 19.79 0.00757577 19.72 0.00750669 51.8237 13291.14 0.00 15870.48 15870.48 1.65915581 2.80 2.27 0.00423406 13424.7 12.25 7.19 0.00423406 22990.1
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 75862.031 60690.033 4.325424 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2733 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 4.325424 5.13423892   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 76695.45 72254.20 1.0110 5.13423892 4.325424 25.19 16.95 0.00884009 47837.2 10.99 10.99 0.00850000 32479.2 -999.0 -999.00 -999.00 -999.00 9468.402 67227.05 29.40 0.00882150 18.34 0.95610000 22.1042 24.00 0.00884536 24.00 0.00884536 46.9138 58683.18 0.00 78223.94 61074.78 4.93147529 26.67 19.44 0.01118466 55322.4 14.56 14.08 0.00982122 39460.2
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 16818.900 16818.900 1.297627 0.00014714 285.668 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_MID FAN Fan:VariableVolume 4.325424 5.13423892   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 7.2868 7.433438 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 06:30:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 16818.90 16818.90 1.0000 1.54027167 1.297627 1.93 1.29 0.00394671 11827.4 12.80 11.47 0.00800000 33059.8 0.14712407 60.00 32.22 27.78 0.000 16818.90 -4.20 0.00269032 -4.20 0.95610000 73.6806 19.10 0.00746396 19.64 0.00721389 50.0736 17190.45 0.00 16687.93 16687.93 1.54027167 2.80 1.87 0.00394671 12704.6 13.50 7.46 0.00394671 23539.0
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 84840.330 67912.452 4.899629 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2149 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 4.899629 5.81581478   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 85664.08 81093.85 1.0097 5.81581478 4.899629 25.05 16.87 0.00880870 47615.1 10.99 10.99 0.00850000 32479.1 -999.0 -999.00 -999.00 -999.00 10725.342 74938.73 29.40 0.00882150 18.34 0.95610000 19.5137 24.00 0.00880560 24.00 0.00880560 46.7058 66428.68 0.00 87481.77 68346.33 5.58613406 26.67 19.44 0.01118466 55322.4 14.71 14.15 0.00984159 39661.9
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 16468.640 16468.640 1.469889 0.00014407 282.398 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1870 PACU_VAV_TOP FAN Fan:VariableVolume 4.899629 5.81581478   4197.9300 999.8980 1.97921977 54.44 82.22 27.78 230813.63 7.1350 7.278633 SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 05:50:00 unknown unknown SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 16468.64 16468.64 1.0000 1.74474443 1.469889 3.41 2.74 0.00439802 14450.2 12.80 11.47 0.00800000 33059.8 0.14406015 60.00 32.22 27.78 0.000 16468.64 -4.20 0.00269032 -4.20 0.95610000 65.0457 17.56 0.00757585 17.60 0.00739579 58.3067 18797.77 0.00 16647.64 16647.64 1.74474443 2.80 2.50 0.00439802 13835.6 12.22 7.38 0.00439802 23377.2



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialDryBulb 0.00 4.66 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialDryBulb 0.00 4.33 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialDryBulb 0.00 4.90 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area PERIMETER_MID_ZN_2_OA_MULT 1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 1992.17 2019.67 32.00
CORE_MID 1273.17 3237.00 172.00
CORE_TOP 1508.00 3815.00 656.50
PERIMETER_TOP_ZN_3 2246.83 4272.33 1442.33
PERIMETER_TOP_ZN_2 2587.67 3841.83 1305.50
PERIMETER_TOP_ZN_1 2510.33 3701.17 1119.33
PERIMETER_TOP_ZN_4 2571.67 3999.17 1372.83
PERIMETER_BOT_ZN_3 1647.17 4287.00 994.17
PERIMETER_BOT_ZN_2 2161.83 3646.67 845.67
PERIMETER_BOT_ZN_1 2111.83 3844.00 854.83
PERIMETER_BOT_ZN_4 2215.67 3675.83 871.00
PERIMETER_MID_ZN_3 1841.33 3921.50 926.50
PERIMETER_MID_ZN_2 1920.67 3098.83 799.50
PERIMETER_MID_ZN_1 2236.50 3308.50 678.17
PERIMETER_MID_ZN_4 2223.83 3643.83 878.50
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4158.50 4669.00 1651.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 2.33 0.00 2.33 0.00
CORE_MID 3.33 0.00 3.33 0.00
CORE_TOP 5.83 0.00 5.67 0.00
PERIMETER_TOP_ZN_3 20.83 0.00 18.67 0.00
PERIMETER_TOP_ZN_2 9.17 13.50 7.33 13.50
PERIMETER_TOP_ZN_1 6.67 16.50 5.83 15.83
PERIMETER_TOP_ZN_4 7.67 22.50 6.17 13.67
PERIMETER_BOT_ZN_3 5.33 0.00 5.33 0.00
PERIMETER_BOT_ZN_2 3.33 9.50 3.17 9.50
PERIMETER_BOT_ZN_1 293.83 8.67 293.83 8.50
PERIMETER_BOT_ZN_4 3.33 15.33 3.00 7.83
PERIMETER_MID_ZN_3 5.17 0.00 5.17 0.00
PERIMETER_MID_ZN_2 2.50 12.50 2.33 12.50
PERIMETER_MID_ZN_1 2.33 16.83 2.33 16.83
PERIMETER_MID_ZN_4 2.67 21.50 2.50 13.17
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 307.33 92.67 304.33 74.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.63 52.94 2698.04 1.013 0.000 0.000 0.000
CORE_MID 21.63 52.94 2698.04 0.701 0.000 0.000 0.000
CORE_TOP 21.63 52.94 2698.04 0.674 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.56 11.16 568.77 0.723 0.035 0.000 0.000
PERIMETER_TOP_ZN_2 2.89 7.07 360.08 1.054 0.037 0.000 0.000
PERIMETER_TOP_ZN_1 4.56 11.16 568.77 1.152 0.035 0.000 0.000
PERIMETER_TOP_ZN_4 2.89 7.06 360.05 1.055 0.037 0.000 0.000
PERIMETER_BOT_ZN_3 4.56 11.16 568.77 0.628 0.019 0.000 0.000
PERIMETER_BOT_ZN_2 2.89 7.07 360.08 0.937 0.020 0.000 0.000
PERIMETER_BOT_ZN_1 4.56 11.16 568.77 0.928 0.829 0.000 0.000
PERIMETER_BOT_ZN_4 2.89 7.06 360.05 0.920 0.020 0.000 0.000
PERIMETER_MID_ZN_3 4.56 11.16 568.77 0.732 0.030 0.000 0.000
PERIMETER_MID_ZN_2 2.53 7.07 360.08 0.966 0.033 0.000 0.000
PERIMETER_MID_ZN_1 4.56 11.16 568.77 1.169 0.030 0.000 0.000
PERIMETER_MID_ZN_4 2.89 7.06 360.05 1.054 0.031 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.63 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.63 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.63 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.89 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.89 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.89 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.89 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.53 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.56 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.89 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.63 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.63 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.63 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.89 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.89 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.89 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.89 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.53 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.56 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.89 7.06 360.05 131.25 0.0000 0.057
Total Facility   109.20 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 15977466.67 0.00 15977466.67 0.00 15977466.67 13393058.27 4508.33 329.49 3922.19 43.81
CORE_MID 11096764.94 0.00 11096764.94 0.00 11096764.94 13393058.27 4542.07 1109.58 3108.35 50.42
CORE_TOP 10692349.76 0.00 10692349.76 0.00 10692349.76 13393058.27 4598.25 1207.89 2953.86 51.27
PERIMETER_TOP_ZN_3 2418676.44 0.00 2418676.44 242662.85 2661339.29 2823374.22 4432.88 1130.61 3196.51 51.27
PERIMETER_TOP_ZN_2 2225182.14 0.00 2225182.14 161774.26 2386956.40 1787429.43 4408.91 1329.71 3021.38 51.27
PERIMETER_TOP_ZN_1 3839729.50 0.00 3839729.50 242662.85 4082392.35 2823374.22 4359.63 1330.67 3069.70 51.27
PERIMETER_TOP_ZN_4 2244347.11 0.00 2244347.11 161774.26 2406121.37 1787312.18 4363.51 931.96 3464.53 51.27
PERIMETER_BOT_ZN_3 2098926.74 0.00 2098926.74 129022.55 2227949.28 2823374.22 5611.20 409.31 2739.49 43.81
PERIMETER_BOT_ZN_2 1976516.15 0.00 1976516.15 86014.52 2062530.66 1787429.43 5351.81 436.18 2972.01 43.81
PERIMETER_BOT_ZN_1 3100602.18 0.00 3100602.18 2835943.55 5936545.73 2823374.22 5017.56 327.34 3415.10 43.81
PERIMETER_BOT_ZN_4 1948755.69 0.00 1948755.69 86014.52 2034770.21 1787312.18 5427.77 415.52 2916.71 43.81
PERIMETER_MID_ZN_3 2445886.95 0.00 2445886.95 201998.19 2647885.14 2823374.22 4538.39 1199.26 3022.35 50.42
PERIMETER_MID_ZN_2 2072328.24 0.00 2072328.24 134664.65 2206992.89 1601953.02 4301.98 959.27 3498.75 959.42
PERIMETER_MID_ZN_1 3890880.79 0.00 3890880.79 201998.19 4092878.97 2823374.22 4292.77 1164.40 3302.83 50.42
PERIMETER_MID_ZN_4 2235700.80 0.00 2235700.80 134664.65 2370365.45 1787312.18 4431.77 909.79 3418.44 50.42
Total Facility 68264114.08 0.00 68264114.08 4619195.04 72883309.12 67658168.57 5857.08 1667.58 4497.24 986.39


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.7430 0.0000 0.7430 0.0000 0.7430 0.4247 1725.30 329.49 3888.21
CORE_MID 0.5145 0.0000 0.5145 0.0000 0.5145 0.4247 1764.15 1109.58 3069.27
CORE_TOP 0.4951 0.0000 0.4951 0.0000 0.4951 0.4247 1824.66 1207.89 2910.44
PERIMETER_TOP_ZN_3 0.1121 0.0000 0.1121 0.0055 0.1176 0.0895 1659.29 1130.61 3153.10
PERIMETER_TOP_ZN_2 0.1034 0.0000 0.1034 0.0037 0.1071 0.0567 1635.33 1329.71 2977.96
PERIMETER_TOP_ZN_1 0.1785 0.0000 0.1785 0.0055 0.1840 0.0895 1586.05 1330.67 3026.28
PERIMETER_TOP_ZN_4 0.1035 0.0000 0.1035 0.0037 0.1071 0.0567 1589.93 931.96 3421.11
PERIMETER_BOT_ZN_3 0.0973 0.0000 0.0973 0.0029 0.1002 0.0895 2828.18 409.31 2705.51
PERIMETER_BOT_ZN_2 0.0919 0.0000 0.0919 0.0020 0.0938 0.0567 2568.80 436.18 2938.01
PERIMETER_BOT_ZN_1 0.1441 0.0000 0.1441 0.1295 0.2736 0.0895 2234.53 327.34 3381.12
PERIMETER_BOT_ZN_4 0.0902 0.0000 0.0902 0.0020 0.0921 0.0567 2644.76 415.52 2882.72
PERIMETER_MID_ZN_3 0.1134 0.0000 0.1134 0.0046 0.1180 0.0895 1760.47 1199.26 2983.27
PERIMETER_MID_ZN_2 0.0947 0.0000 0.0947 0.0033 0.0980 0.0567 1524.06 959.27 2550.67
PERIMETER_MID_ZN_1 0.1810 0.0000 0.1810 0.0046 0.1856 0.0895 1514.85 1164.40 3263.75
PERIMETER_MID_ZN_4 0.1033 0.0000 0.1033 0.0031 0.1064 0.0567 1653.85 909.79 3379.36
Total Facility 3.1658 0.0000 3.1658 0.1702 3.3360 2.1513 3059.91 1667.58 4442.92


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 35367767.39 0.00 35367767.39 22614548.33 4080.97 4.04 4674.99 43.81
PACU_VAV_MID 30632710.76 0.00 30632710.76 22429071.92 4064.52 2.54 4692.94 50.42
PACU_VAV_TOP 30180048.77 0.00 30180048.77 22614548.33 4098.16 3.42 4658.42 51.27


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.6436 0.0000 1.6436 0.7171 1297.94 4.04 4641.02
PACU_VAV_MID 1.4209 0.0000 1.4209 0.7084 1286.61 2.54 4653.86
PACU_VAV_TOP 1.3982 0.0000 1.3982 0.7171 1324.58 3.42 4615.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 325.61 3057.80 0.00 0.00 0.00 1400.45 0.00 0.00 0.00
PACU_VAV_MID 0.00 35.82 2913.56 0.00 0.00 0.00 1874.06 0.00 0.00 0.00
PACU_VAV_TOP 0.00 32.00 2820.26 0.00 0.00 0.00 1968.46 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 1.3274 2.5788 0.0000 0.0000 0.0000 1.1187 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 1.2395 2.2627 0.0000 0.0000 0.0000 1.0261 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 1.1614 2.2538 0.0000 0.0000 0.0000 1.0336 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1005
Defaulted Fields 578
Fields with Defaults 2423
Autosized Fields 194
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
Electricity:Building 953.57 13383.13 23-APR-17:20 66674.30 02-JAN-16:30
Electricity:Zone:CORE_BOTTOM 306.02 5243.28 01-JAN-00:10 18955.76 02-JAN-08:10
Electricity:SpaceType:GENERAL 953.57 13383.13 23-APR-17:20 66674.30 02-JAN-16:30
InteriorLights:Electricity 233.88 905.38 23-APR-17:20 25003.79 02-JAN-16:30
InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 233.88 905.38 23-APR-17:20 25003.79 02-JAN-16:30
LightsWired:InteriorLights:Electricity 233.88 905.38 23-APR-17:20 25003.79 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 233.88 905.38 23-APR-17:20 25003.79 02-JAN-16:30
Electricity:Zone:CORE_MID 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:CORE_TOP 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 31.26 413.68 19-MAR-17:10 2475.80 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.93 27.57 08-JAN-10:30 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.93 27.57 08-JAN-10:30 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_2 19.74 261.88 09-APR-17:10 1567.33 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.34 17.46 01-JAN-09:50 658.76 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.34 17.46 01-JAN-09:50 658.76 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_1 31.12 413.67 19-MAR-17:10 2475.79 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.78 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.78 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_TOP_ZN_4 19.73 261.87 19-MAR-17:10 1567.28 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.33 17.46 01-JAN-13:00 658.71 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.33 17.46 01-JAN-13:00 658.71 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_3 31.24 413.68 19-MAR-17:10 2475.80 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.90 27.57 08-JAN-10:20 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.90 27.57 08-JAN-10:20 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_2 19.73 261.88 09-APR-17:10 1567.33 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.33 17.46 01-JAN-09:50 658.76 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.33 17.46 01-JAN-09:50 658.76 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_1 31.10 413.67 19-MAR-17:10 2475.79 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.77 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.77 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_BOT_ZN_4 19.72 261.87 19-MAR-17:10 1567.28 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.32 17.46 01-JAN-10:30 658.71 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.32 17.46 01-JAN-10:30 658.71 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_3 31.26 413.68 19-MAR-17:10 2475.80 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.93 27.57 08-JAN-10:30 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.93 27.57 08-JAN-10:30 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_2 19.74 261.88 09-APR-17:10 1567.33 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.34 17.46 01-JAN-09:50 658.76 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.34 17.46 01-JAN-09:50 658.76 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_1 31.12 413.67 19-MAR-17:10 2475.79 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.78 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.78 27.57 01-JAN-09:50 1040.56 02-JAN-16:30
Electricity:Zone:PERIMETER_MID_ZN_4 19.73 261.87 19-MAR-17:10 1567.28 02-JAN-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.33 17.46 01-JAN-13:00 658.71 02-JAN-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.33 17.46 01-JAN-13:00 658.71 02-JAN-16:30
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 170.70 367.92 01-JAN-00:10 80491.03 10-AUG-15:10
ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 02-JAN-08:10
Transformer:ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 02-JAN-08:10
ElectricityPurchased:Facility 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
ElectricityPurchased:Plant 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
Cogeneration:ElectricityPurchased 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
General:Cogeneration:ElectricityPurchased 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
ElectricityNet:Plant 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
Cogeneration:ElectricityNet 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
General:Cogeneration:ElectricityNet 1231.50 13751.66 04-JUN-17:40 146002.71 10-AUG-15:20
Fans:Electricity 74.09 0.00 01-JAN-00:10 28025.63 31-JUL-15:10
General:Fans:Electricity 74.09 0.00 01-JAN-00:10 28025.63 31-JUL-15:10
ExteriorLights:Electricity 51.64 0.00 01-JAN-08:10 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 51.64 0.00 01-JAN-08:10 5686.19 01-JAN-06:10
Cooling:Electricity 69.72 0.00 01-JAN-00:10 52760.88 29-AUG-15:30
General:Cooling:Electricity 69.72 0.00 01-JAN-00:10 52760.88 29-AUG-15:30
Electricity:Plant 55.59 0.00 01-JAN-00:10 6854.44 13-FEB-12:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 54.28 0.00 01-JAN-00:10 6514.69 10-FEB-12:50
Water Heater:WaterSystems:Electricity 54.28 0.00 01-JAN-00:10 6514.69 10-FEB-12:50
Pumps:Electricity 1.31 0.00 01-JAN-00:10 552.05 26-DEC-07:10
General:Pumps:Electricity 1.31 0.00 01-JAN-00:10 552.05 26-DEC-07:10
WIRED_LTG_ELECTRICITY 6.57 0.00 01-JAN-00:10 702.61 02-JAN-16:40
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 235.98 0.00 01-JAN-00:10 184170.64 26-DEC-07:20
NaturalGas:Plant 235.98 0.00 01-JAN-00:10 184170.64 26-DEC-07:20
Heating:NaturalGas 235.98 0.00 01-JAN-00:10 184170.64 26-DEC-07:20
Boiler:Heating:NaturalGas 235.98 0.00 01-JAN-00:10 184170.64 26-DEC-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:20
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1579.89 0.00 01-JAN-00:10 394997.00 26-DEC-07:20
EnergyTransfer:Building 896.24 0.00 01-JAN-00:10 156441.60 31-JUL-14:50
EnergyTransfer:Zone:CORE_BOTTOM 207.56 0.00 01-JAN-00:10 24449.68 14-AUG-07:40
Heating:EnergyTransfer 69.45 0.00 01-JAN-00:10 122432.42 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.09 0.00 01-JAN-00:10 4899.21 02-JAN-06:20
General:Heating:EnergyTransfer 69.45 0.00 01-JAN-00:10 122432.42 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.09 0.00 01-JAN-00:10 4899.21 02-JAN-06:20
Cooling:EnergyTransfer 826.79 0.00 01-JAN-00:10 156441.60 31-JUL-14:50
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 207.47 0.00 01-JAN-00:10 24449.68 14-AUG-07:40
General:Cooling:EnergyTransfer 826.79 0.00 01-JAN-00:10 156441.60 31-JUL-14:50
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 207.47 0.00 01-JAN-00:10 24449.68 14-AUG-07:40
EnergyTransfer:Zone:TOPFLOOR_PLENUM 34.17 0.00 01-JAN-00:10 10201.19 09-JAN-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 13.74 0.00 01-JAN-00:10 10201.19 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 13.74 0.00 01-JAN-00:10 10201.19 09-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 20.43 0.00 01-JAN-00:10 9937.18 10-AUG-14:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 20.43 0.00 01-JAN-00:10 9937.18 10-AUG-14:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 17.58 0.00 01-JAN-00:10 8455.01 02-JAN-08:40
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.01 0.00 01-JAN-00:10 8455.01 02-JAN-08:40
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 7.01 0.00 01-JAN-00:10 8455.01 02-JAN-08:40
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 10.57 0.00 01-JAN-00:10 4700.60 14-AUG-15:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 10.57 0.00 01-JAN-00:10 4700.60 14-AUG-15:20
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 20.77 0.00 01-JAN-00:10 6980.36 02-JAN-09:10
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.81 0.00 01-JAN-00:10 6980.36 02-JAN-09:10
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 4.81 0.00 01-JAN-00:10 6980.36 02-JAN-09:10
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 15.96 0.00 01-JAN-00:10 5170.10 14-AUG-15:00
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 15.96 0.00 01-JAN-00:10 5170.10 14-AUG-15:00
EnergyTransfer:Zone:CORE_MID 132.03 0.00 01-JAN-00:10 17520.99 14-AUG-07:40
Heating:EnergyTransfer:Zone:CORE_MID 0.54 0.00 01-JAN-00:10 12189.20 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_MID 0.54 0.00 01-JAN-00:10 12189.20 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_MID 131.48 0.00 01-JAN-00:10 17520.99 14-AUG-07:40
General:Cooling:EnergyTransfer:Zone:CORE_MID 131.48 0.00 01-JAN-00:10 17520.99 14-AUG-07:40
EnergyTransfer:Zone:CORE_TOP 119.86 0.00 01-JAN-00:10 18814.88 24-JUL-14:00
Heating:EnergyTransfer:Zone:CORE_TOP 2.76 0.00 01-JAN-00:10 18719.73 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 2.76 0.00 01-JAN-00:10 18719.73 02-JAN-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 117.09 0.00 01-JAN-00:10 18814.88 24-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 117.09 0.00 01-JAN-00:10 18814.88 24-JUL-14:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 28.84 0.00 01-JAN-00:10 6674.07 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.10 0.00 01-JAN-00:10 6674.07 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 6.10 0.00 01-JAN-00:10 6674.07 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 22.75 0.00 01-JAN-00:10 6285.20 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 22.75 0.00 01-JAN-00:10 6285.20 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 26.49 0.00 01-JAN-00:10 9031.25 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.61 0.00 01-JAN-00:10 5616.98 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 3.61 0.00 01-JAN-00:10 5616.98 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 22.88 0.00 01-JAN-00:10 9031.25 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 22.88 0.00 01-JAN-00:10 9031.25 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 46.11 0.00 01-JAN-00:10 13825.10 04-OCT-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.49 0.00 01-JAN-00:10 8538.30 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 4.49 0.00 01-JAN-00:10 8538.30 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 41.62 0.00 01-JAN-00:10 13825.10 04-OCT-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 41.62 0.00 01-JAN-00:10 13825.10 04-OCT-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 27.23 0.00 01-JAN-00:10 9729.86 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.81 0.00 01-JAN-00:10 5731.68 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 3.81 0.00 01-JAN-00:10 5731.68 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 23.42 0.00 01-JAN-00:10 9729.86 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 23.42 0.00 01-JAN-00:10 9729.86 10-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 23.57 0.00 01-JAN-00:10 5160.51 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.26 0.00 01-JAN-00:10 5160.51 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 2.26 0.00 01-JAN-00:10 5160.51 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 21.31 0.00 01-JAN-00:10 4871.17 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 21.31 0.00 01-JAN-00:10 4871.17 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 23.19 0.00 01-JAN-00:10 7389.52 24-JUL-08:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.33 0.00 01-JAN-00:10 4436.65 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 1.33 0.00 01-JAN-00:10 4436.65 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 21.86 0.00 01-JAN-00:10 7389.52 24-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 21.86 0.00 01-JAN-00:10 7389.52 24-JUL-08:50
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 41.05 0.00 01-JAN-00:10 12897.11 10-AUG-16:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.30 0.00 01-JAN-00:10 8149.57 26-DEC-07:40
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.30 0.00 01-JAN-00:10 8149.57 26-DEC-07:40
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 29.75 0.00 01-JAN-00:10 12897.11 10-AUG-16:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 29.75 0.00 01-JAN-00:10 12897.11 10-AUG-16:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 23.27 0.00 01-JAN-00:10 7955.31 31-JUL-17:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.33 0.00 01-JAN-00:10 4528.55 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.33 0.00 01-JAN-00:10 4528.55 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 21.94 0.00 01-JAN-00:10 7955.31 31-JUL-17:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 21.94 0.00 01-JAN-00:10 7955.31 31-JUL-17:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 27.47 0.00 01-JAN-00:10 5781.74 24-JUL-15:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.11 0.00 01-JAN-00:10 5502.70 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.11 0.00 01-JAN-00:10 5502.70 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 25.36 0.00 01-JAN-00:10 5781.74 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 25.36 0.00 01-JAN-00:10 5781.74 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 24.30 0.00 01-JAN-00:10 9061.08 31-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.31 0.00 01-JAN-00:10 4727.48 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.31 0.00 01-JAN-00:10 4727.48 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 23.00 0.00 01-JAN-00:10 9061.08 31-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 23.00 0.00 01-JAN-00:10 9061.08 31-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 46.37 0.00 01-JAN-00:10 13640.78 04-OCT-12:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.51 0.00 01-JAN-00:10 7031.93 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1.51 0.00 01-JAN-00:10 7031.93 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 44.86 0.00 01-JAN-00:10 13640.78 04-OCT-12:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 44.86 0.00 01-JAN-00:10 13640.78 04-OCT-12:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 26.36 0.00 01-JAN-00:10 9266.87 10-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.33 0.00 01-JAN-00:10 4726.58 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 1.33 0.00 01-JAN-00:10 4726.58 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 25.03 0.00 01-JAN-00:10 9266.87 10-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 25.03 0.00 01-JAN-00:10 9266.87 10-AUG-16:00
PlantLoopHeatingDemand:Facility 214.47 0.00 01-JAN-00:10 149614.58 26-DEC-07:10
PlantLoopHeatingDemand:Plant 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
EnergyTransfer:HVAC 470.45 0.00 01-JAN-00:10 212659.49 31-JUL-14:30
HeatingCoils:EnergyTransfer 162.98 0.00 01-JAN-00:10 147577.39 26-DEC-07:10
PlantLoopHeatingDemand:HVAC 162.98 0.00 01-JAN-00:10 147577.39 26-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 162.98 0.00 01-JAN-00:10 147577.39 26-DEC-07:10
CoolingCoils:EnergyTransfer 307.46 0.00 01-JAN-00:10 212646.48 31-JUL-14:30
EnergyTransfer:Plant 213.21 0.00 01-JAN-00:10 147967.20 26-DEC-07:20
WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 51.49 0.00 01-JAN-00:10 6247.39 10-FEB-12:10
Boilers:EnergyTransfer 161.72 0.00 01-JAN-00:10 145930.02 26-DEC-07:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.089 -207.467 0.000 0.000 32.860 55.599 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -131.504
CORE_MID 0.000 0.000 0.542 -131.484 0.000 0.000 33.966 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -74.047
CORE_TOP 0.000 0.000 2.765 -117.090 0.000 0.000 34.760 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -91.458
PERIMETER_TOP_ZN_3 0.000 0.000 6.096 -22.745 0.000 0.000 7.546 6.927 24.333 13.857 0.000 0.008 0.001 0.000 -28.335 0.000 -3.182 -4.505
PERIMETER_TOP_ZN_2 0.000 0.000 3.607 -22.883 0.000 0.000 4.709 4.339 15.404 26.280 0.000 0.005 0.000 0.000 -18.367 0.000 -2.154 -10.940
PERIMETER_TOP_ZN_1 0.000 0.000 4.492 -41.620 0.000 0.000 7.378 6.784 24.332 56.860 0.000 0.007 0.001 0.000 -28.182 0.000 -3.316 -26.735
PERIMETER_TOP_ZN_4 0.000 0.000 3.811 -23.418 0.000 0.000 4.746 4.331 15.403 28.391 0.000 0.005 0.000 0.000 -18.949 0.000 -2.176 -12.146
PERIMETER_BOT_ZN_3 0.000 0.000 2.259 -21.315 0.000 0.000 7.488 6.904 24.333 14.041 0.000 0.005 0.000 0.000 -29.690 0.000 -1.781 -2.244
PERIMETER_BOT_ZN_2 0.000 0.000 1.329 -21.864 0.000 0.000 4.663 4.329 15.404 26.342 0.000 0.003 0.001 0.000 -19.460 0.000 -1.221 -9.524
PERIMETER_BOT_ZN_1 0.000 0.000 11.303 -29.746 0.000 0.000 7.539 6.770 24.332 57.409 0.000 0.383 0.000 0.000 -29.689 0.000 -32.749 -15.553
PERIMETER_BOT_ZN_4 0.000 0.000 1.334 -21.939 0.000 0.000 4.687 4.321 15.403 28.541 0.000 0.003 0.002 0.000 -20.153 0.000 -1.235 -10.961
PERIMETER_MID_ZN_3 0.000 0.000 2.107 -25.358 0.000 0.000 7.426 6.927 24.333 13.549 0.000 0.008 4.091 0.000 -30.262 0.000 -2.820 -0.001
PERIMETER_MID_ZN_2 0.000 0.000 1.307 -22.998 0.000 0.000 3.428 4.339 15.404 25.968 0.000 0.004 0.002 0.000 -19.568 0.000 -1.909 -5.975
PERIMETER_MID_ZN_1 0.000 0.000 1.513 -44.857 0.000 0.000 7.263 6.784 24.332 56.508 0.000 0.006 0.001 0.000 -29.975 0.000 -2.931 -18.644
PERIMETER_MID_ZN_4 0.000 0.000 1.326 -25.030 0.000 0.000 4.671 4.331 15.403 28.204 0.000 0.004 0.001 0.000 -20.197 0.000 -1.924 -6.789
TOPFLOOR_PLENUM 13.740 -20.434 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.005 11.593 0.000 0.000 0.000 -4.904 -0.001
MIDFLOOR_PLENUM 7.009 -10.575 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.009 8.409 0.000 0.000 0.000 -4.853 -0.001
FIRSTFLOOR_PLENUM 4.815 -15.960 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.007 15.093 0.000 0.000 0.000 -3.954 -0.000
Total Facility 25.564 -46.969 43.881 -779.815 0.000 0.000 173.133 233.882 719.689 375.950 0.000 0.461 39.196 0.000 -292.827 0.000 -71.109 -421.029


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 28-AUG-05:12 0.00 0.00 0.00 -39446.24 0.00 0.00 313.03 548.43 7410.35 0.00 0.00 0.00 31174.43 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-05:12 0.00 0.00 0.00 -30634.21 0.00 0.00 325.07 548.43 3025.92 0.00 0.00 0.00 26734.79 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 14-AUG-06:02 0.00 0.00 0.00 -27856.74 0.00 0.00 711.92 1645.36 3025.92 0.00 0.00 0.00 22473.54 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24-JUL-06:03 0.00 0.00 0.00 -6845.78 0.00 0.00 148.57 165.45 637.89 2185.84 0.00 0.00 3722.98 0.00 -0.00 0.00 -14.94 0.00
PERIMETER_TOP_ZN_2 30-JUL-09:12 0.00 0.00 0.00 -14416.35 0.00 0.00 14.19 17.46 302.86 9590.43 0.00 0.00 4541.80 0.00 -0.00 0.00 -50.38 0.00
PERIMETER_TOP_ZN_1 10-SEP-12:02 0.00 0.00 0.00 -21364.54 0.00 0.00 22.85 27.57 478.41 15829.61 0.00 0.00 5085.88 0.00 -0.00 0.00 -79.79 0.00
PERIMETER_TOP_ZN_4 10-SEP-16:41 0.00 0.00 0.00 -15916.06 0.00 0.00 13.42 17.46 302.86 10125.35 0.00 0.00 5501.97 0.00 -0.00 0.00 -44.99 0.00
PERIMETER_BOT_ZN_3 24-JUL-06:03 0.00 0.00 0.00 -4890.89 0.00 0.00 151.30 165.45 637.89 2238.72 0.00 0.00 1705.36 0.00 -0.00 0.00 -7.82 0.00
PERIMETER_BOT_ZN_2 13-AUG-09:32 0.00 0.00 0.00 -11483.21 0.00 0.00 15.84 17.46 302.86 9063.62 0.00 0.00 2116.22 0.00 -0.00 0.00 -32.78 0.00
PERIMETER_BOT_ZN_1 13-AUG-12:52 0.00 0.00 0.00 -16934.32 0.00 0.00 25.24 27.57 478.41 12609.00 0.00 0.00 3804.78 0.00 -0.00 0.00 -10.69 0.00
PERIMETER_BOT_ZN_4 06-AUG-18:32 0.00 0.00 0.00 -12967.75 0.00 0.00 0.00 17.46 244.42 6630.29 0.00 0.00 6111.62 0.00 -0.00 0.00 -36.04 0.00
PERIMETER_MID_ZN_3 24-JUL-06:03 0.00 0.00 0.00 -7053.14 0.00 0.00 144.67 165.45 637.89 2149.22 0.00 0.00 3968.93 0.00 -0.00 0.00 -13.03 0.00
PERIMETER_MID_ZN_2 13-AUG-08:12 0.00 0.00 0.00 -14450.40 0.00 0.00 14.09 17.46 302.86 11266.13 0.00 0.00 2934.03 0.00 -0.00 0.00 -84.16 0.00
PERIMETER_MID_ZN_1 13-AUG-12:52 0.00 0.00 0.00 -19703.37 0.00 0.00 23.17 27.57 478.41 12505.56 0.00 0.00 6693.28 0.00 -0.00 0.00 -24.62 0.00
PERIMETER_MID_ZN_4 07-MAY-16:41 0.00 0.00 0.00 -15138.32 0.00 0.00 13.44 17.46 302.86 11059.46 0.00 0.00 3808.99 0.00 -0.00 0.00 -63.88 0.00
TOPFLOOR_PLENUM 10-AUG-14:40 0.00 -9936.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.35 9920.60 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 14-AUG-06:13 0.00 -4760.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4796.23 0.00 -0.00 0.00 -35.36 0.00
FIRSTFLOOR_PLENUM 14-AUG-06:13 0.00 -5293.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5320.98 0.00 -0.00 0.00 -27.44 0.00
Total Facility 24-JUL-06:03 0.00 -3934.17 0.00 -159632.81 0.00 0.00 3551.81 6557.23 22496.85 30666.85 0.00 0.00 105668.13 0.00 -148.49 0.00 -5225.40 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 02-JAN-06:11 0.00 0.00 5569.77 0.00 0.00 0.00 494.18 548.43 7410.35 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -14022.73
CORE_MID 02-JAN-06:11 0.00 0.00 13223.89 0.00 0.00 0.00 524.41 548.43 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -17322.65
CORE_TOP 02-JAN-06:11 0.00 0.00 20223.67 0.00 0.00 0.00 536.32 548.43 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -24334.33
PERIMETER_TOP_ZN_3 26-DEC-05:01 0.00 0.00 7319.35 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -1742.70 0.00 0.00 -6136.09
PERIMETER_TOP_ZN_2 26-DEC-05:01 0.00 0.00 6721.05 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1159.84 0.00 0.00 -5915.36
PERIMETER_TOP_ZN_1 26-DEC-05:01 0.00 0.00 10117.83 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -1751.64 0.00 0.00 -8925.63
PERIMETER_TOP_ZN_4 26-DEC-05:01 0.00 0.00 6968.33 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1159.81 0.00 0.00 -6162.67
PERIMETER_BOT_ZN_3 02-JAN-06:11 0.00 0.00 5539.49 0.00 0.00 0.00 112.89 115.61 637.89 0.00 0.00 0.00 0.00 0.00 -1092.93 0.00 -34.89 -5278.06
PERIMETER_BOT_ZN_2 02-JAN-06:11 0.00 0.00 5125.01 0.00 0.00 0.00 71.45 73.19 403.81 0.00 0.00 0.00 0.00 0.00 -741.97 0.00 -23.58 -4907.92
PERIMETER_BOT_ZN_1 26-DEC-07:40 0.00 0.00 8148.85 0.00 0.00 0.00 230.11 346.86 637.88 0.00 0.00 0.00 7176.28 0.00 -2133.42 0.00 -14406.57 0.00
PERIMETER_BOT_ZN_4 02-JAN-06:11 0.00 0.00 5310.40 0.00 0.00 0.00 71.45 73.19 403.81 0.00 0.00 0.00 0.00 0.00 -726.24 0.00 -23.62 -5108.99
PERIMETER_MID_ZN_3 02-JAN-06:11 0.00 0.00 5952.67 0.00 0.00 0.00 113.18 115.61 637.89 0.00 0.00 0.00 0.00 0.00 -1094.99 0.00 -54.78 -5669.57
PERIMETER_MID_ZN_2 02-JAN-06:11 0.00 0.00 5638.14 0.00 0.00 0.00 71.65 73.19 403.81 0.00 0.00 0.00 0.00 0.00 -746.33 0.00 -37.11 -5403.35
PERIMETER_MID_ZN_1 02-JAN-06:11 0.00 0.00 8251.57 0.00 0.00 0.00 113.18 115.61 637.88 0.00 0.00 0.00 0.00 0.00 -1121.42 0.00 -55.50 -7941.33
PERIMETER_MID_ZN_4 02-JAN-06:11 0.00 0.00 5659.58 0.00 0.00 0.00 71.65 73.19 403.81 0.00 0.00 0.00 0.00 0.00 -728.81 0.00 -37.12 -5442.29
TOPFLOOR_PLENUM 21-FEB-06:10 11226.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -54.52 -11171.75
MIDFLOOR_PLENUM 02-JAN-08:40 8632.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -76.44 -8556.56
FIRSTFLOOR_PLENUM 02-JAN-08:10 7118.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -49.05 -7069.79
Total Facility 02-JAN-06:11 7708.68 0.00 118493.19 0.00 0.00 0.00 2663.17 2778.13 19712.35 0.00 0.00 0.00 0.00 0.00 -10958.32 0.00 -1866.03 -138531.17



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 5.3540 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.6593 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 5.2261 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.3254 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 5.4956 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 4.8996 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 2.6770 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0755 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 2.6131 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0746 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 2.7478 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0760 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5674 2.5674 0.6367 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0464 2.0464 0.6364 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1034 2.1034 0.6373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5954 0.5954 0.1346 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7784 0.7784 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1649 1.1649 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8535 0.8535 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4743 0.4743 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6432 0.6432 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9553 0.9553 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7138 0.7138 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5237 0.5237 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7788 0.7788 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0810 1.0810 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7962 0.7962 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 5.3540 4.6593 5.3540 1.0755 0.0000 1.0000
PACU_VAV_MID 5.2261 4.3254 5.2261 1.0746 0.0000 1.0000
PACU_VAV_TOP 5.4956 4.8996 5.4956 1.0760 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2837 1.2837 0.6367 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0232 1.0232 0.6364 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0517 1.0517 0.6373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2977 0.2977 0.1346 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3892 0.3892 0.0848 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5825 0.5825 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4267 0.4267 0.0853 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2372 0.2372 0.1342 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3216 0.3216 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4777 0.4777 0.1347 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3569 0.3569 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2619 0.2619 0.1341 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3894 0.3894 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5405 0.5405 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3981 0.3981 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 2.6770 1.0755 1.0755 1.0755 0.0000 1.0000
PACU_VAV_MID 2.6131 1.0746 1.0746 1.0746 0.0000 1.0000
PACU_VAV_TOP 2.7478 1.0760 1.0760 1.0760 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 304.33
Number of hours cooling loads not met 74.33
Number of hours not met 378.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 235.98 184170.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 69.72 52760.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 233.88 25003.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 51.64 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.89 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 74.09 28025.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.31 552.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 54.28 6514.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1231.50
Natural Gas 0.00 235.98
Additional 0.00 0.00
Total 719.69 1467.48


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 46.94
Space Heating 0.00
Space Cooling 13.99
Fans (All) 14.87
Service Water Heating 10.89
Receptacle Equipment 144.45
Miscellaneous (All) 247.18
Subtotal 247.18


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 47.37
Service Water Heating 0.00
Miscellaneous (All) 47.37
Subtotal 47.37


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 15.94
Space Heating 16.08
Space Cooling 4.75
Fans (All) 5.05
Service Water Heating 3.70
Receptacle Equipment 49.04
Miscellaneous 5.44


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 862. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8697.33 62.67 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8759.50 0.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8744.50 15.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8737.17 22.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8728.00 32.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8749.50 10.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8740.50 19.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8733.83 26.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8744.50 15.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8738.50 21.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8729.50 30.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 8717.33 42.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8697.33 0.00 0.00 0.00 0.00
Max 8760.00 62.67 0.00 0.00 0.00
Average 8743.34 16.66 0.00 0.00 0.00
Sum 157380.17 299.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128276.33 27.67 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 27.67 0.00 0.00 0.00
Average 34141.80 1.54 0.00 0.00 0.00
Sum 614552.33 27.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8585.33 174.67 0.00 0.00 0.00
CORE_MID 8744.33 15.67 0.00 0.00 0.00
CORE_TOP 8756.33 3.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8754.50 5.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8738.17 21.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8725.50 34.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8722.33 37.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8753.50 6.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8736.67 23.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8728.17 31.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8703.67 56.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8753.33 6.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8733.67 26.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8725.83 34.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8720.83 39.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 8730.33 29.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8585.33 0.00 0.00 0.00 0.00
Max 8760.00 174.67 0.00 0.00 0.00
Average 8729.58 30.42 0.00 0.00 0.00
Sum 157132.50 547.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128209.50 94.50 0.00 0.00 0.00
CORE_MID 128296.67 7.33 0.00 0.00 0.00
CORE_TOP 128299.33 4.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128299.33 94.50 0.00 0.00 0.00
Average 34137.42 5.92 0.00 0.00 0.00
Sum 614473.50 106.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:02

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.496
February 5.822
March 8.326
April 10.851
May 12.973
June 15.587
July 17.665
August 18.800
September 15.086
October 11.426
November 8.070
December 5.416
   
Annual Sum or Average 11.241
Minimum of Months 4.496
Maximum of Months 18.800



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.862208E+10 11135.99 12-JAN-17:00 7.20 5.41 0.187432E+10 2606.62 20-JAN-10:00 5.60 3.25
February 0.991251E+10 14787.18 28-FEB-17:00 14.40 10.82 0.178338E+10 2606.65 08-FEB-10:09 14.40 10.82
March 0.154513E+11 18718.85 20-MAR-06:03 6.70 4.63 0.215454E+10 2606.66 09-MAR-14:09 6.70 4.63
April 0.170474E+11 35561.64 28-APR-06:02 11.10 10.22 0.191742E+10 2606.66 27-APR-13:20 11.10 10.22
May 0.216730E+11 38168.83 08-MAY-05:12 9.60 9.49 0.207809E+10 2606.68 05-MAY-09:09 9.60 9.49
June 0.231929E+11 39242.96 12-JUN-05:12 14.40 13.42 0.207247E+10 2606.70 05-JUN-13:00 14.40 13.42
July 0.237631E+11 39349.53 17-JUL-05:12 14.07 12.34 0.192806E+10 2606.65 20-JUL-13:20 26.30 16.68
August 0.257854E+11 39453.18 28-AUG-05:12 14.87 13.94 0.216302E+10 2606.85 09-AUG-09:00 14.87 13.94
September 0.215577E+11 39311.09 05-SEP-05:12 10.77 9.27 0.192080E+10 2606.66 22-SEP-09:20 14.83 14.31
October 0.177550E+11 38096.49 10-OCT-05:12 12.20 11.16 0.199411E+10 2606.65 05-OCT-09:00 12.20 11.16
November 0.125837E+11 28994.82 06-NOV-07:03 12.20 8.82 0.196299E+10 2606.63 10-NOV-10:09 6.88 5.74
December 0.101233E+11 13627.36 06-DEC-15:50 3.58 3.15 0.188510E+10 2606.65 13-DEC-14:09 7.10 5.11
                     
Annual Sum or Average 0.207467E+12         0.237343E+11        
Minimum of Months 0.862208E+10 11135.99   3.58 3.15 0.178338E+10 2606.62   5.60 3.25
Maximum of Months 0.257854E+11 39453.18   14.87 13.94 0.216302E+10 2606.85   26.30 16.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.92 4.99 0.00 0.00 01-JAN-00:10 5.92 4.99
February 47759164.40 1823.93 27-FEB-15:30 19.70 12.30 0.00 0.00 01-FEB-00:10 19.70 12.30
March 0.394721E+09 2914.98 14-MAR-15:10 16.28 10.42 0.00 0.00 01-MAR-00:10 16.28 10.42
April 0.142774E+10 8433.97 27-APR-14:30 26.65 17.06 0.00 0.00 01-APR-00:10 26.65 17.06
May 0.270702E+10 8836.77 15-MAY-14:20 23.30 13.21 0.00 0.00 01-MAY-00:10 23.30 13.21
June 0.352724E+10 8637.11 28-JUN-14:30 25.55 15.61 0.00 0.00 01-JUN-00:10 25.55 15.61
July 0.470201E+10 9838.89 24-JUL-13:40 29.03 18.20 0.00 0.00 01-JUL-00:10 29.03 18.20
August 0.457390E+10 9937.18 10-AUG-14:40 29.93 18.99 0.00 0.00 01-AUG-00:10 29.93 18.99
September 0.238330E+10 7763.91 14-SEP-14:40 23.90 17.01 0.00 0.00 01-SEP-00:10 23.90 17.01
October 0.626073E+09 5440.22 04-OCT-14:50 21.60 11.48 0.00 0.00 01-OCT-00:10 21.60 11.48
November 43254109.45 2302.28 04-NOV-14:30 21.10 15.94 0.00 0.00 01-NOV-00:10 21.10 15.94
December 1424304.53 293.71 02-DEC-15:05 11.52 5.36 0.00 0.00 01-DEC-00:10 11.52 5.36
                     
Annual Sum or Average 0.204344E+11         0.00        
Minimum of Months 0.00 0.00   5.92 4.99 0.00 0.00   5.92 4.99
Maximum of Months 0.470201E+10 9937.18   29.93 18.99 0.00 0.00   29.93 18.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 4968117.85 1613.35 14-JAN-06:11 2.20 1.14 0.00 0.00 01-JAN-00:10 2.20 1.14
February 40866239.89 1852.09 10-FEB-07:01 0.60 -0.1 0.00 0.00 01-FEB-00:10 0.60 -0.1
March 0.154986E+09 2786.69 01-MAR-07:01 -0.1 -1.7 0.00 0.00 01-MAR-00:10 -0.1 -1.7
April 0.485201E+09 2961.05 27-APR-16:00 27.20 16.90 0.00 0.00 01-APR-00:10 27.20 16.90
May 0.110539E+10 3365.66 15-MAY-15:20 23.50 12.70 0.00 0.00 01-MAY-00:10 23.50 12.70
June 0.179259E+10 3363.03 28-JUN-15:40 26.10 16.04 0.00 0.00 01-JUN-00:10 26.10 16.04
July 0.245945E+10 4626.37 31-JUL-15:10 28.40 18.96 0.00 0.00 01-JUL-00:10 28.40 18.96
August 0.273638E+10 4760.82 14-AUG-06:13 15.73 13.91 0.00 0.00 01-AUG-00:10 15.73 13.91
September 0.137058E+10 3757.16 11-SEP-15:30 23.30 15.99 0.00 0.00 01-SEP-00:10 23.30 15.99
October 0.367011E+09 2309.86 04-OCT-15:40 21.30 11.43 0.00 0.00 01-OCT-00:10 21.30 11.43
November 51993612.81 2105.67 10-NOV-07:02 4.08 3.61 0.00 0.00 01-NOV-00:10 4.08 3.61
December 5503382.76 1317.10 07-DEC-07:03 6.10 3.18 0.00 0.00 01-DEC-00:10 6.10 3.18
                     
Annual Sum or Average 0.105749E+11         0.00        
Minimum of Months 4968117.85 1317.10   -0.1 -1.7 0.00 0.00   -0.1 -1.7
Maximum of Months 0.273638E+10 4760.82   28.40 18.96 0.00 0.00   28.40 18.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 79525239.63 2274.79 13-JAN-06:11 3.13 2.22 0.00 0.00 01-JAN-00:10 3.13 2.22
February 0.138925E+09 2735.38 10-FEB-07:01 0.60 -0.1 0.00 0.00 01-FEB-00:10 0.60 -0.1
March 0.401829E+09 3354.60 01-MAR-07:01 -0.1 -1.7 0.00 0.00 01-MAR-00:10 -0.1 -1.7
April 0.950286E+09 3362.13 27-APR-16:00 27.20 16.90 0.00 0.00 01-APR-00:10 27.20 16.90
May 0.182193E+10 4003.94 08-MAY-06:08 9.90 9.62 0.00 0.00 01-MAY-00:10 9.90 9.62
June 0.249887E+10 3778.63 28-JUN-16:00 26.10 16.29 0.00 0.00 01-JUN-00:10 26.10 16.29
July 0.316351E+10 5044.63 31-JUL-15:50 28.80 19.14 0.00 0.00 01-JUL-00:10 28.80 19.14
August 0.355523E+10 5293.39 14-AUG-06:13 15.73 13.91 0.00 0.00 01-AUG-00:10 15.73 13.91
September 0.218361E+10 4559.15 11-SEP-15:50 23.30 16.09 0.00 0.00 01-SEP-00:10 23.30 16.09
October 0.858447E+09 3169.28 04-OCT-15:40 21.30 11.43 0.00 0.00 01-OCT-00:10 21.30 11.43
November 0.200741E+09 2510.15 16-NOV-07:02 3.48 2.25 0.00 0.00 01-NOV-00:10 3.48 2.25
December 0.107178E+09 2372.83 07-DEC-07:03 6.10 3.18 0.00 0.00 01-DEC-00:10 6.10 3.18
                     
Annual Sum or Average 0.159601E+11         0.00        
Minimum of Months 79525239.63 2274.79   -0.1 -1.7 0.00 0.00   -0.1 -1.7
Maximum of Months 0.355523E+10 5293.39   28.80 19.14 0.00 0.00   28.80 19.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.578408E+10 6199.75 06-JAN-08:20 -2.6 -2.6 0.162256E+10 2420.62 12-JAN-14:00 7.20 5.88
February 0.644146E+10 7995.20 28-FEB-17:00 14.40 10.82 0.158008E+10 2606.49 28-FEB-14:20 14.40 10.82
March 0.904932E+10 9486.92 02-MAR-17:00 12.80 8.57 0.205885E+10 2606.63 31-MAR-13:09 8.98 7.53
April 0.102917E+11 14268.91 27-APR-16:00 27.20 16.90 0.188385E+10 2606.66 14-APR-09:20 27.20 16.90
May 0.137143E+11 24101.37 08-MAY-06:02 9.90 9.62 0.206362E+10 2606.66 05-MAY-09:09 9.90 9.62
June 0.152711E+11 29913.98 12-JUN-05:12 14.40 13.42 0.206448E+10 2606.68 09-JUN-13:09 14.40 13.42
July 0.160723E+11 30043.78 31-JUL-05:12 17.40 14.58 0.192096E+10 2606.65 31-JUL-09:20 22.57 17.16
August 0.174057E+11 30634.56 14-AUG-05:12 15.33 13.50 0.215638E+10 2606.78 09-AUG-09:00 15.33 13.50
September 0.134325E+11 27553.24 11-SEP-06:01 12.07 10.69 0.190897E+10 2606.65 22-SEP-09:20 14.83 14.31
October 0.101503E+11 13837.17 04-OCT-16:00 21.10 11.40 0.194520E+10 2606.65 12-OCT-09:09 9.18 7.86
November 0.740880E+10 8786.26 06-NOV-17:00 11.70 10.80 0.179096E+10 2606.60 06-NOV-14:09 11.70 10.80
December 0.646313E+10 6294.40 06-DEC-16:10 2.93 2.59 0.163258E+10 2539.83 06-DEC-14:00 2.93 2.59
                     
Annual Sum or Average 0.131485E+12         0.226285E+11        
Minimum of Months 0.578408E+10 6199.75   -2.6 -2.6 0.158008E+10 2420.62   2.93 2.59
Maximum of Months 0.174057E+11 30634.56   27.20 16.90 0.215638E+10 2606.78   27.20 17.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.392436E+10 5764.07 06-JAN-10:30 -0.9 -0.9 0.153413E+10 2294.12 11-JAN-14:00 14.40 10.49
February 0.508057E+10 7018.64 28-FEB-17:00 14.40 10.82 0.147338E+10 2600.90 28-FEB-14:00 14.40 10.82
March 0.797562E+10 8525.16 02-MAR-17:00 12.80 8.57 0.193421E+10 2606.61 02-MAR-14:20 12.80 8.57
April 0.936607E+10 15649.88 27-APR-15:40 27.20 17.03 0.182419E+10 2606.66 27-APR-13:20 27.20 17.03
May 0.127324E+11 16782.74 15-MAY-15:30 23.60 12.74 0.204097E+10 2606.66 05-MAY-09:09 23.60 12.74
June 0.146322E+11 16988.44 28-JUN-15:50 26.10 16.17 0.205441E+10 2606.68 09-JUN-13:09 26.10 16.17
July 0.157355E+11 24132.02 24-JUL-06:03 17.48 14.11 0.191448E+10 2606.65 20-JUL-13:20 17.48 14.11
August 0.167320E+11 27857.89 14-AUG-06:02 15.47 13.75 0.214942E+10 2606.77 09-AUG-09:00 15.47 13.75
September 0.120463E+11 16585.34 11-SEP-15:40 23.30 16.04 0.188616E+10 2606.65 22-SEP-09:20 14.83 14.31
October 0.858826E+10 13717.33 04-OCT-16:00 21.10 11.40 0.185624E+10 2606.62 05-OCT-09:20 12.43 7.97
November 0.584557E+10 6457.03 02-NOV-16:00 13.30 10.88 0.165633E+10 2564.87 06-NOV-14:00 11.10 10.22
December 0.443213E+10 5844.71 05-DEC-16:15 6.10 4.53 0.151035E+10 2380.42 05-DEC-14:00 6.10 4.53
                     
Annual Sum or Average 0.117091E+12         0.218343E+11        
Minimum of Months 0.392436E+10 5764.07   -0.9 -0.9 0.147338E+10 2294.12   6.10 4.53
Maximum of Months 0.167320E+11 27857.89   27.20 17.03 0.214942E+10 2606.77   27.20 17.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.159520E+09 1011.57 11-JAN-16:20 13.67 10.10 0.306018E+09 439.37 11-JAN-14:00 13.67 10.10
February 0.450753E+09 1286.30 28-FEB-15:00 13.90 10.81 0.287075E+09 522.35 28-FEB-14:00 13.90 10.81
March 0.119500E+10 1370.43 10-MAR-14:50 16.20 11.59 0.370800E+09 549.41 10-MAR-14:00 16.10 11.51
April 0.175165E+10 4484.14 27-APR-15:20 27.20 17.16 0.362533E+09 549.50 27-APR-13:20 27.20 17.16
May 0.282617E+10 4836.91 15-MAY-14:30 23.30 13.06 0.419292E+09 549.50 05-MAY-09:20 23.30 13.06
June 0.352034E+10 5131.32 21-JUN-15:30 24.70 15.68 0.428969E+09 549.51 09-JUN-13:09 24.70 15.68
July 0.405560E+10 6845.41 24-JUL-06:03 17.48 14.11 0.401500E+09 549.50 20-JUL-13:20 17.48 14.11
August 0.412266E+10 5618.25 09-AUG-15:20 28.47 18.71 0.449725E+09 549.53 09-AUG-09:00 28.47 18.71
September 0.243959E+10 4265.78 12-SEP-14:50 24.40 16.68 0.385009E+09 549.49 15-SEP-09:20 16.70 14.42
October 0.140660E+10 2690.04 04-OCT-15:20 21.50 11.47 0.359763E+09 549.49 03-OCT-13:20 21.50 11.47
November 0.617589E+09 1229.15 02-NOV-14:40 13.67 11.26 0.317653E+09 502.26 02-NOV-13:00 13.67 11.26
December 0.200186E+09 949.64 05-DEC-15:10 9.35 6.62 0.295819E+09 425.52 05-DEC-14:00 9.35 6.62
                     
Annual Sum or Average 0.227457E+11         0.438416E+10        
Minimum of Months 0.159520E+09 949.64   9.35 6.62 0.287075E+09 425.52   9.35 6.62
Maximum of Months 0.412266E+10 6845.41   28.47 18.71 0.449725E+09 549.53   28.47 18.71



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148456E+09 700.34 05-JAN-09:20 0.53 0.46 0.194505E+09 282.87 11-JAN-14:00 14.40 10.49
February 0.377219E+09 861.28 27-FEB-15:50 19.50 12.39 0.188818E+09 343.44 27-FEB-14:00 19.50 12.39
March 0.987938E+09 2829.59 14-MAR-09:50 9.63 7.44 0.251096E+09 347.88 02-MAR-10:20 9.63 7.44
April 0.191755E+10 6790.76 27-APR-09:10 17.98 12.34 0.242305E+09 347.88 20-APR-09:00 17.98 12.34
May 0.279394E+10 10335.23 14-MAY-10:23 19.75 12.55 0.269774E+09 347.89 15-MAY-09:00 18.90 13.25
June 0.374716E+10 12374.51 25-JUN-08:62 15.78 11.63 0.273888E+09 347.88 09-JUN-13:09 15.78 11.63
July 0.405738E+10 14418.06 30-JUL-09:12 21.13 15.97 0.255472E+09 348.43 31-JUL-09:00 23.30 17.69
August 0.434949E+10 13288.98 13-AUG-09:02 21.20 16.02 0.286474E+09 348.41 08-AUG-09:00 21.20 16.02
September 0.259087E+10 13470.85 10-SEP-09:22 16.65 13.51 0.248268E+09 347.88 11-SEP-09:00 18.90 14.30
October 0.125558E+10 4886.95 04-OCT-09:20 16.13 10.66 0.238654E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.453186E+09 853.72 02-NOV-10:40 12.43 10.47 0.204987E+09 337.33 02-NOV-13:00 14.40 11.37
December 0.204440E+09 696.17 05-DEC-10:30 7.50 5.28 0.189277E+09 297.70 05-DEC-10:50 8.03 5.37
                     
Annual Sum or Average 0.228832E+11         0.284352E+10        
Minimum of Months 0.148456E+09 696.17   0.53 0.46 0.188818E+09 282.87   8.03 5.37
Maximum of Months 0.434949E+10 14418.06   21.20 16.02 0.286474E+09 348.43   23.30 17.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.588139E+09 6823.43 20-JAN-13:30 6.70 4.72 0.323618E+09 549.49 20-JAN-14:50 7.12 4.90
February 0.132522E+10 8997.67 27-FEB-14:30 19.15 11.80 0.315693E+09 549.49 27-FEB-14:00 20.00 12.17
March 0.277706E+10 10200.60 01-MAR-13:35 11.33 6.09 0.400363E+09 549.50 02-MAR-14:00 13.30 8.57
April 0.361409E+10 12120.98 27-APR-13:05 26.10 16.37 0.376943E+09 550.01 27-APR-13:00 26.10 16.83
May 0.449590E+10 19530.11 14-MAY-15:02 23.30 12.38 0.421988E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.489759E+10 10750.92 25-JUN-13:23 21.10 13.16 0.428820E+09 549.51 09-JUN-13:09 21.10 13.16
July 0.604195E+10 20415.85 30-JUL-11:52 26.10 17.22 0.401701E+09 550.02 31-JUL-13:00 28.30 18.92
August 0.687647E+10 19467.08 13-AUG-13:02 26.62 18.46 0.450730E+09 550.36 29-AUG-13:30 29.30 20.07
September 0.555178E+10 21361.29 10-SEP-12:02 19.60 13.52 0.391130E+09 550.28 15-SEP-13:50 21.70 16.50
October 0.344315E+10 20189.24 08-OCT-13:32 19.27 14.01 0.381372E+09 549.82 04-OCT-13:00 19.27 14.01
November 0.117961E+10 9418.60 04-NOV-13:30 20.85 16.00 0.340201E+09 549.49 15-NOV-14:00 8.90 6.49
December 0.829982E+09 6970.43 05-DEC-12:30 10.30 6.13 0.319502E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.416209E+11         0.455206E+10        
Minimum of Months 0.588139E+09 6823.43   6.70 4.72 0.315693E+09 549.49   7.12 4.90
Maximum of Months 0.687647E+10 21361.29   26.62 18.46 0.450730E+09 550.36   29.30 20.07



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.154725E+09 792.99 20-JAN-15:50 5.87 4.23 0.196045E+09 317.10 20-JAN-15:00 5.60 4.08
February 0.389206E+09 3637.83 27-FEB-15:30 19.70 12.30 0.188371E+09 347.83 28-FEB-14:50 13.98 10.93
March 0.105609E+10 5342.15 14-MAR-16:00 17.20 10.94 0.240609E+09 347.84 01-MAR-14:20 17.20 10.94
April 0.187098E+10 8288.79 26-APR-16:00 24.40 14.49 0.231952E+09 347.85 27-APR-13:20 26.10 16.46
May 0.299996E+10 15720.52 14-MAY-15:41 23.30 12.14 0.266077E+09 347.85 05-MAY-09:20 23.30 12.14
June 0.343515E+10 13189.20 18-JUN-17:02 17.12 12.23 0.271387E+09 347.85 05-JUN-13:00 17.12 12.23
July 0.454341E+10 15595.88 30-JUL-17:51 26.70 17.68 0.254585E+09 347.86 20-JUL-13:20 26.70 17.68
August 0.432518E+10 15071.36 06-AUG-16:42 23.47 15.19 0.285100E+09 347.87 09-AUG-09:00 23.80 15.92
September 0.274120E+10 15914.83 10-SEP-16:41 22.20 14.22 0.245401E+09 347.85 05-SEP-09:20 22.20 14.22
October 0.127104E+10 6730.77 04-OCT-16:00 21.10 11.40 0.231238E+09 347.85 25-OCT-13:20 13.50 10.37
November 0.444036E+09 2844.55 04-NOV-15:30 20.55 15.94 0.204198E+09 347.84 15-NOV-14:00 8.90 6.49
December 0.187260E+09 984.24 05-DEC-15:30 8.05 5.82 0.191134E+09 338.68 05-DEC-15:50 6.75 4.97
                     
Annual Sum or Average 0.234182E+11         0.280610E+10        
Minimum of Months 0.154725E+09 792.99   5.87 4.23 0.188371E+09 317.10   5.60 4.08
Maximum of Months 0.454341E+10 15914.83   26.70 17.68 0.285100E+09 347.87   26.70 17.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.282278E+09 989.47 11-JAN-16:20 13.67 10.10 0.307733E+09 436.73 11-JAN-14:00 13.67 10.10
February 0.580163E+09 1193.94 28-FEB-14:20 14.23 11.32 0.287732E+09 496.25 28-FEB-14:30 14.15 11.19
March 0.133074E+10 1238.95 10-MAR-14:50 16.20 11.59 0.371007E+09 510.23 10-MAR-14:00 16.10 11.51
April 0.156547E+10 2710.20 27-APR-16:00 27.20 16.90 0.360262E+09 549.50 27-APR-13:20 27.20 16.90
May 0.228909E+10 3176.98 05-MAY-15:30 24.70 17.20 0.422600E+09 549.50 05-MAY-09:20 24.70 17.20
June 0.285400E+10 3901.26 21-JUN-15:30 24.70 15.68 0.431206E+09 549.50 09-JUN-13:20 24.70 15.68
July 0.337895E+10 4890.93 24-JUL-06:03 17.48 14.11 0.403005E+09 549.50 20-JUL-13:20 17.48 14.11
August 0.357221E+10 4466.03 09-AUG-15:30 28.70 18.83 0.452143E+09 549.52 09-AUG-09:00 28.70 18.83
September 0.229907E+10 3358.73 12-SEP-15:20 24.40 16.82 0.393529E+09 549.49 05-SEP-09:20 24.40 16.82
October 0.163354E+10 2123.50 04-OCT-15:30 21.40 11.45 0.378855E+09 549.49 03-OCT-13:20 21.40 11.45
November 0.105330E+10 1264.79 06-NOV-12:00 13.90 10.05 0.334182E+09 514.05 06-NOV-14:09 11.60 10.16
December 0.475866E+09 980.28 14-DEC-13:40 9.63 7.19 0.300538E+09 434.18 14-DEC-14:09 8.90 6.73
                     
Annual Sum or Average 0.213147E+11         0.444279E+10        
Minimum of Months 0.282278E+09 980.28   9.63 7.19 0.287732E+09 434.18   8.90 6.73
Maximum of Months 0.357221E+10 4890.93   28.70 18.83 0.452143E+09 549.52   28.70 18.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234655E+09 715.65 05-JAN-09:00 -0.6 -0.6 0.195993E+09 282.91 20-JAN-10:00 5.60 3.25
February 0.468962E+09 797.96 27-FEB-15:40 19.60 12.34 0.190124E+09 326.44 27-FEB-14:00 19.60 12.34
March 0.102781E+10 1691.41 14-MAR-10:00 10.00 7.75 0.253637E+09 347.88 02-MAR-10:20 10.00 7.75
April 0.165423E+10 5104.60 27-APR-09:30 18.35 12.60 0.244682E+09 347.88 27-APR-13:20 26.10 16.46
May 0.235779E+10 8604.73 15-MAY-06:02 11.97 9.44 0.272255E+09 347.89 15-MAY-09:00 18.90 13.25
June 0.331698E+10 8708.61 19-JUN-06:02 11.88 9.64 0.275114E+09 347.88 28-JUN-13:50 24.90 15.66
July 0.363150E+10 9679.98 23-JUL-08:42 18.72 13.76 0.256280E+09 348.16 31-JUL-09:00 23.30 17.69
August 0.412904E+10 11483.94 13-AUG-09:32 22.10 16.37 0.287574E+09 348.19 14-AUG-09:00 21.10 15.94
September 0.253250E+10 7092.62 10-SEP-07:43 14.03 12.57 0.252563E+09 347.88 11-SEP-09:00 18.90 14.30
October 0.142812E+10 4135.43 04-OCT-08:30 14.75 10.13 0.249749E+09 347.88 05-OCT-09:00 13.90 9.28
November 0.711579E+09 987.59 02-NOV-10:30 12.25 10.40 0.217303E+09 341.00 02-NOV-09:00 12.25 10.40
December 0.370743E+09 751.10 05-DEC-10:30 7.50 5.28 0.194528E+09 314.11 05-DEC-10:39 7.77 5.32
                     
Annual Sum or Average 0.218639E+11         0.288980E+10        
Minimum of Months 0.234655E+09 715.65   -0.6 -0.6 0.190124E+09 282.91   5.60 3.25
Maximum of Months 0.412904E+10 11483.94   22.10 16.37 0.287574E+09 348.19   26.10 17.69



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244505E+09 2013.26 20-JAN-13:30 6.70 4.72 0.301453E+09 549.50 20-JAN-14:09 6.78 4.76
February 0.702261E+09 5411.93 27-FEB-15:00 20.00 12.17 0.297062E+09 549.51 07-FEB-14:09 20.00 12.17
March 0.155355E+10 7540.01 02-MAR-13:07 12.38 7.47 0.375730E+09 549.51 24-MAR-13:20 8.67 2.76
April 0.213805E+10 9334.72 27-APR-13:40 26.10 16.65 0.357873E+09 549.51 27-APR-13:20 26.10 16.65
May 0.273051E+10 8674.11 14-MAY-13:32 22.60 12.25 0.405706E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.320560E+10 7193.27 28-JUN-13:30 24.70 15.69 0.417576E+09 549.52 28-JUN-13:50 24.90 15.66
July 0.461701E+10 10999.94 31-JUL-16:10 28.80 19.11 0.397243E+09 549.58 31-JUL-13:00 28.80 19.11
August 0.601095E+10 16934.41 13-AUG-12:52 26.50 18.40 0.446778E+09 549.93 29-AUG-13:39 29.43 20.04
September 0.443990E+10 16269.06 10-SEP-15:43 22.30 14.46 0.386205E+09 549.95 15-SEP-13:00 21.70 16.45
October 0.268078E+10 11342.32 04-OCT-13:30 20.85 11.31 0.377715E+09 549.68 03-OCT-13:00 20.85 11.31
November 0.920057E+09 6973.80 04-NOV-13:40 20.93 15.98 0.325014E+09 549.50 15-NOV-14:00 8.90 6.49
December 0.503246E+09 4236.03 05-DEC-12:00 10.00 6.07 0.303068E+09 549.50 06-DEC-14:09 5.08 4.26
                     
Annual Sum or Average 0.297464E+11         0.439142E+10        
Minimum of Months 0.244505E+09 2013.26   6.70 4.72 0.297062E+09 549.50   5.08 2.76
Maximum of Months 0.601095E+10 16934.41   28.80 19.11 0.446778E+09 549.95   29.43 20.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.226325E+09 738.68 20-JAN-15:50 5.87 4.23 0.196749E+09 301.99 20-JAN-15:00 5.60 4.08
February 0.476011E+09 2308.01 27-FEB-15:40 19.60 12.34 0.189097E+09 347.83 27-FEB-14:39 19.60 12.34
March 0.103859E+10 3128.21 02-MAR-16:30 13.05 8.47 0.245107E+09 347.84 02-MAR-14:20 13.05 8.47
April 0.154521E+10 5938.90 26-APR-17:30 23.60 13.73 0.236794E+09 347.85 28-APR-09:20 11.70 11.07
May 0.248535E+10 12791.22 07-MAY-17:21 21.40 16.06 0.271231E+09 347.85 05-MAY-09:20 21.40 16.06
June 0.296579E+10 7562.62 25-JUN-18:03 21.42 13.27 0.274127E+09 347.85 28-JUN-13:00 25.00 15.65
July 0.407406E+10 12691.24 23-JUL-18:01 25.82 15.89 0.256451E+09 347.85 03-JUL-09:20 25.82 15.89
August 0.402960E+10 12968.28 06-AUG-18:32 22.47 15.07 0.287431E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.262614E+10 11671.08 10-SEP-17:42 20.87 13.88 0.252429E+09 347.86 22-SEP-09:20 14.83 14.31
October 0.140478E+10 5937.01 04-OCT-16:00 21.10 11.40 0.245984E+09 347.85 05-OCT-09:20 12.43 7.97
November 0.710401E+09 2394.64 04-NOV-15:30 20.55 15.94 0.215239E+09 347.83 10-NOV-14:00 10.00 6.84
December 0.357375E+09 849.93 05-DEC-15:40 7.40 5.40 0.194570E+09 334.84 05-DEC-15:39 7.40 5.40
                     
Annual Sum or Average 0.219396E+11         0.286521E+10        
Minimum of Months 0.226325E+09 738.68   5.87 4.23 0.189097E+09 301.99   5.60 4.08
Maximum of Months 0.407406E+10 12968.28   25.82 16.06 0.287431E+09 347.88   25.82 16.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.373177E+09 1067.15 11-JAN-16:20 13.67 10.10 0.309669E+09 457.61 11-JAN-14:00 13.67 10.10
February 0.739529E+09 1320.56 28-FEB-15:00 13.90 10.81 0.295326E+09 534.87 28-FEB-14:00 13.90 10.81
March 0.152025E+10 1452.75 10-MAR-14:30 16.40 11.76 0.391619E+09 549.46 10-MAR-14:00 16.10 11.51
April 0.193473E+10 4132.24 27-APR-15:20 27.20 17.16 0.377437E+09 549.50 27-APR-13:20 27.20 17.16
May 0.298965E+10 4456.88 15-MAY-14:30 23.30 13.06 0.428560E+09 549.50 05-MAY-09:20 23.30 13.06
June 0.364064E+10 4787.17 21-JUN-15:30 24.70 15.68 0.433094E+09 549.50 09-JUN-13:09 24.70 15.68
July 0.410302E+10 7053.20 24-JUL-06:03 17.48 14.11 0.403781E+09 550.33 24-JUL-13:20 28.67 18.27
August 0.422237E+10 6803.41 14-AUG-06:02 15.47 13.75 0.452852E+09 549.53 09-AUG-09:00 15.47 13.75
September 0.264459E+10 4117.97 12-SEP-14:40 24.40 16.65 0.395245E+09 549.50 22-SEP-09:20 14.83 14.31
October 0.170521E+10 2762.54 04-OCT-15:20 21.50 11.47 0.381489E+09 549.49 12-OCT-13:20 14.27 10.74
November 0.994173E+09 1281.79 02-NOV-14:10 14.22 11.35 0.333171E+09 521.76 02-NOV-13:00 14.22 11.35
December 0.491309E+09 1023.22 05-DEC-15:20 8.70 6.23 0.302084E+09 447.63 05-DEC-14:00 8.70 6.23
                     
Annual Sum or Average 0.253587E+11         0.450433E+10        
Minimum of Months 0.373177E+09 1023.22   8.70 6.23 0.295326E+09 447.63   8.70 6.23
Maximum of Months 0.422237E+10 7053.20   27.20 17.16 0.452852E+09 550.33   28.67 18.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.219705E+09 738.53 06-JAN-09:30 -1.7 -1.7 0.145803E+09 303.68 20-JAN-11:09 5.60 3.32
February 0.431128E+09 2271.91 27-FEB-15:05 19.90 12.22 0.144549E+09 356.46 08-FEB-11:09 19.90 12.22
March 0.106983E+10 5759.01 01-MAR-13:01 10.78 5.75 0.192533E+09 356.46 14-MAR-10:09 10.28 7.92
April 0.195233E+10 7483.17 27-APR-10:05 19.27 13.13 0.182801E+09 356.46 20-APR-10:09 19.27 13.13
May 0.276022E+10 12054.46 14-MAY-07:53 14.40 10.27 0.201948E+09 356.47 15-MAY-10:09 19.18 13.24
June 0.365696E+10 11247.59 25-JUN-10:23 18.60 13.07 0.203691E+09 356.46 07-JUN-10:09 18.60 13.07
July 0.389908E+10 13326.73 30-JUL-08:42 20.22 15.61 0.190478E+09 356.46 07-JUL-12:09 20.22 15.61
August 0.423932E+10 14452.68 13-AUG-08:12 19.97 15.36 0.212862E+09 356.51 09-AUG-10:09 19.97 15.36
September 0.259719E+10 11613.30 10-SEP-10:13 17.77 13.72 0.186735E+09 356.46 11-SEP-10:09 19.08 14.37
October 0.135465E+10 6024.50 04-OCT-10:05 17.48 10.97 0.183450E+09 356.46 05-OCT-10:09 14.08 9.36
November 0.535119E+09 4219.32 02-NOV-12:02 13.48 11.00 0.159792E+09 356.45 02-NOV-10:09 13.48 11.00
December 0.282486E+09 805.02 05-DEC-11:10 8.58 5.53 0.144258E+09 329.74 05-DEC-11:09 8.58 5.53
                     
Annual Sum or Average 0.229980E+11         0.214890E+10        
Minimum of Months 0.219705E+09 738.53   -1.7 -1.7 0.144258E+09 303.68   5.60 3.32
Maximum of Months 0.423932E+10 14452.68   20.22 15.61 0.212862E+09 356.51   20.22 15.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.846543E+09 7326.19 20-JAN-13:12 6.70 4.72 0.332465E+09 549.49 20-JAN-14:39 7.03 4.87
February 0.174087E+10 9148.82 27-FEB-14:10 18.58 11.55 0.325431E+09 549.50 08-FEB-10:09 18.58 11.55
March 0.324581E+10 10560.37 01-MAR-13:30 11.15 5.98 0.416963E+09 549.50 02-MAR-14:00 13.30 8.57
April 0.388847E+10 11676.62 02-APR-13:13 18.90 11.02 0.387657E+09 550.62 27-APR-13:20 26.10 16.46
May 0.466599E+10 18230.10 14-MAY-13:13 22.40 12.22 0.429928E+09 549.51 15-MAY-13:09 22.88 13.76
June 0.497869E+10 14409.13 11-JUN-13:13 21.87 15.28 0.433081E+09 549.52 28-JUN-13:50 24.90 15.66
July 0.601439E+10 15934.47 23-JUL-14:32 27.40 16.28 0.404199E+09 550.84 31-JUL-13:20 27.57 18.47
August 0.693169E+10 19704.87 13-AUG-12:52 26.50 18.40 0.453557E+09 550.87 14-AUG-13:20 25.93 17.49
September 0.577514E+10 18631.10 10-SEP-12:52 20.60 14.10 0.398642E+09 550.61 12-SEP-13:20 23.33 16.02
October 0.392905E+10 13640.78 04-OCT-12:50 20.60 11.27 0.396964E+09 550.17 04-OCT-13:20 20.77 11.28
November 0.162217E+10 9543.99 04-NOV-13:30 20.85 16.00 0.357788E+09 549.49 24-NOV-10:30 5.85 4.21
December 0.121860E+10 7942.13 05-DEC-12:30 10.30 6.13 0.330550E+09 549.50 05-DEC-14:00 10.00 7.01
                     
Annual Sum or Average 0.448574E+11         0.466722E+10        
Minimum of Months 0.846543E+09 7326.19   6.70 4.72 0.325431E+09 549.49   5.85 4.21
Maximum of Months 0.693169E+10 19704.87   27.40 18.40 0.453557E+09 550.87   27.57 18.47



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285419E+09 819.91 20-JAN-15:50 5.87 4.23 0.199091E+09 325.29 20-JAN-15:00 5.60 4.08
February 0.593231E+09 3741.77 27-FEB-15:30 19.70 12.30 0.193621E+09 347.84 03-FEB-14:00 19.70 12.30
March 0.128617E+10 5250.05 14-MAR-16:00 17.20 10.94 0.252797E+09 347.84 02-MAR-14:20 17.20 10.94
April 0.199637E+10 8026.26 26-APR-16:00 24.40 14.49 0.240911E+09 347.85 28-APR-09:20 11.70 11.07
May 0.309803E+10 15139.28 07-MAY-16:41 21.78 16.19 0.271800E+09 347.85 05-MAY-09:20 21.78 16.19
June 0.348472E+10 14535.62 18-JUN-16:52 17.20 12.22 0.274201E+09 347.86 28-JUN-13:50 24.90 15.66
July 0.451078E+10 14296.98 30-JUL-18:01 26.32 17.50 0.256059E+09 347.86 31-JUL-09:20 22.57 17.16
August 0.435580E+10 14672.82 06-AUG-18:22 22.80 15.13 0.287058E+09 347.88 09-AUG-09:00 23.80 15.92
September 0.287762E+10 13348.76 10-SEP-16:12 22.20 14.38 0.251345E+09 347.85 22-SEP-09:20 14.83 14.31
October 0.149070E+10 6687.43 04-OCT-16:00 21.10 11.40 0.244086E+09 347.85 04-OCT-09:20 21.10 11.40
November 0.681796E+09 2970.17 04-NOV-15:30 20.55 15.94 0.214154E+09 347.84 08-NOV-14:00 9.40 8.82
December 0.370134E+09 1321.47 05-DEC-15:30 8.05 5.82 0.195977E+09 347.72 05-DEC-14:00 8.05 5.82
                     
Annual Sum or Average 0.250308E+11         0.288110E+10        
Minimum of Months 0.285419E+09 819.91   5.87 4.23 0.193621E+09 325.29   5.60 4.08
Maximum of Months 0.451078E+10 15139.28   26.32 17.50 0.287058E+09 347.88   24.90 17.16



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 89024118.18 5569.78 02-JAN-06:11 6.10
February 0.00 0.00 01-FEB-00:10 7.00
March 0.00 0.00 01-MAR-00:10 5.92
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 0.00 0.00 01-NOV-00:10 9.22
December 0.00 0.00 01-DEC-00:10 4.40
         
Annual Sum or Average 89024118.18      
Minimum of Months 0.00 0.00   4.40
Maximum of Months 89024118.18 5569.78   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.312853E+10 10981.20 09-JAN-06:09 -1.5
February 0.188361E+10 11226.24 21-FEB-06:10 1.70
March 0.120938E+10 6561.20 06-MAR-07:04 6.70
April 0.682776E+09 4056.23 19-APR-06:02 2.48
May 0.432784E+09 3231.34 11-MAY-05:03 5.10
June 0.260482E+09 3129.49 25-JUN-08:62 15.78
July 0.195757E+09 3654.40 30-JUL-07:52 18.30
August 0.230271E+09 3580.32 06-AUG-08:62 14.38
September 0.435600E+09 3991.95 10-SEP-08:62 14.68
October 0.888954E+09 3955.14 16-OCT-06:03 6.60
November 0.170076E+10 9486.92 24-NOV-07:06 1.20
December 0.269121E+10 10700.37 18-DEC-06:18 3.53
         
Annual Sum or Average 0.137401E+11      
Minimum of Months 0.195757E+09 3129.49   -1.5
Maximum of Months 0.312853E+10 11226.24   18.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.176611E+10 8632.56 02-JAN-08:40 6.70
February 0.111841E+10 6004.15 21-FEB-07:12 1.50
March 0.796745E+09 2503.35 14-MAR-10:05 10.28
April 0.311416E+09 3441.63 02-APR-13:13 18.90
May 66156481.50 3973.31 29-MAY-17:02 16.60
June 23590341.64 2778.20 25-JUN-15:43 21.70
July 30710213.11 3930.82 23-JUL-14:32 27.40
August 23202226.09 4386.81 13-AUG-10:12 23.43
September 60826268.90 5088.91 10-SEP-10:13 17.77
October 0.429381E+09 4456.55 29-OCT-12:53 11.10
November 0.978700E+09 2652.34 24-NOV-11:10 6.20
December 0.140393E+10 6444.94 26-DEC-07:20 -1.5
         
Annual Sum or Average 0.700918E+10      
Minimum of Months 23202226.09 2503.35   -1.5
Maximum of Months 0.176611E+10 8632.56   27.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152033E+10 7118.78 02-JAN-08:10 6.70
February 0.820996E+09 2657.63 16-FEB-08:18 2.60
March 0.330966E+09 2647.41 06-MAR-08:08 6.78
April 68363755.79 1845.54 29-APR-05:13 8.50
May 28082307.06 2962.01 01-MAY-05:12 12.20
June 30811069.81 2571.56 19-JUN-05:12 11.30
July 34533686.69 2506.42 05-JUL-05:12 11.87
August 24819731.00 2821.16 13-AUG-14:52 28.10
September 31896404.67 2972.15 10-SEP-15:43 22.30
October 0.133307E+09 3151.77 10-OCT-05:12 12.20
November 0.653768E+09 2905.00 24-NOV-08:18 2.23
December 0.113649E+10 2711.95 05-DEC-08:06 4.08
         
Annual Sum or Average 0.481436E+10      
Minimum of Months 24819731.00 1845.54   2.23
Maximum of Months 0.152033E+10 7118.78   28.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.444015E+09 13223.89 02-JAN-06:11 6.10
February 29810201.34 9716.34 21-FEB-06:01 1.70
March 774356.59 6452.97 06-MAR-07:02 6.70
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 4012767.18 8758.54 27-NOV-07:03 11.70
December 63570787.87 10271.18 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.542184E+09      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.444015E+09 13223.89   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.133711E+10 20223.67 02-JAN-06:11 6.10
February 0.429307E+09 18419.00 21-FEB-06:01 1.70
March 49994411.75 15815.39 06-MAR-06:11 6.70
April 0.00 0.00 01-APR-00:10 7.93
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 6380443.40 14047.34 23-OCT-06:03 10.40
November 0.225630E+09 16492.87 27-NOV-06:11 11.70
December 0.716556E+09 19193.77 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.276498E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.133711E+10 20223.67   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.223936E+10 7314.55 17-JAN-05:01 1.60
February 0.107138E+10 7237.51 21-FEB-06:01 1.70
March 0.250083E+09 6560.47 06-MAR-06:11 6.70
April 50234126.77 5737.78 18-APR-05:13 3.30
May 1287593.12 5378.81 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 905290.89 2283.92 27-SEP-06:03 8.40
October 70528608.11 5844.87 30-OCT-05:12 7.20
November 0.706350E+09 6790.98 24-NOV-06:11 1.83
December 0.170631E+10 7319.33 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.609644E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.223936E+10 7319.33   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135507E+10 6712.82 17-JAN-05:01 1.60
February 0.598684E+09 6617.23 21-FEB-06:01 1.70
March 0.122188E+09 5774.47 06-MAR-06:11 6.70
April 20925737.17 4489.11 18-APR-06:02 3.40
May 1045893.18 4025.77 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 615419.02 1552.88 28-SEP-06:03 8.40
October 44663998.32 4785.74 16-OCT-05:12 7.03
November 0.425476E+09 6084.56 24-NOV-06:11 1.83
December 0.103787E+10 6721.01 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.360653E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.135507E+10 6721.01   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167762E+10 10110.33 17-JAN-05:01 1.60
February 0.710466E+09 9917.98 21-FEB-06:01 1.70
March 0.181423E+09 8669.01 06-MAR-06:11 6.70
April 43103245.28 6814.36 18-APR-06:02 3.40
May 1582397.83 6035.78 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 651228.99 1752.72 27-SEP-06:03 8.40
October 50759906.39 6957.54 16-OCT-05:12 7.03
November 0.521403E+09 9090.40 24-NOV-06:11 1.83
December 0.130519E+10 10117.77 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.449221E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.167762E+10 10117.77   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140529E+10 6957.73 17-JAN-05:01 1.60
February 0.637951E+09 6840.83 21-FEB-06:01 1.70
March 0.157814E+09 5942.24 06-MAR-06:11 6.70
April 33565770.65 4530.98 18-APR-06:02 3.40
May 1139908.71 4136.37 18-MAY-06:03 5.68
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 409338.42 1149.99 28-SEP-06:03 8.40
October 45803468.49 4805.46 16-OCT-05:12 7.03
November 0.452409E+09 6258.20 24-NOV-06:11 1.83
December 0.107708E+10 6968.28 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.381147E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.140529E+10 6968.28   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124630E+10 5539.48 02-JAN-06:11 6.10
February 0.404970E+09 5000.31 21-FEB-06:01 1.70
March 44847483.93 4460.99 06-MAR-06:11 6.70
April 4134015.26 4199.80 19-APR-06:02 2.48
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 659395.29 2628.70 30-OCT-06:03 7.20
November 74358304.02 4463.75 24-NOV-06:11 1.83
December 0.484009E+09 4975.37 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.225928E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.124630E+10 5539.48   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.758122E+09 5125.00 02-JAN-06:11 6.10
February 0.191509E+09 4326.00 21-FEB-06:01 1.70
March 15058719.39 3665.23 06-MAR-06:11 6.70
April 1157283.56 3328.43 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 59309.55 395.40 31-OCT-06:03 10.18
November 45508306.72 3728.52 24-NOV-06:11 1.83
December 0.317763E+09 4396.19 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.132918E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.758122E+09 5125.00   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.298390E+10 7951.60 17-JAN-08:00 1.70
February 0.160731E+10 7668.55 17-FEB-07:10 1.20
March 0.108879E+10 7099.13 01-MAR-07:10 -0.1
April 0.616442E+09 6818.05 19-APR-06:10 2.48
May 0.397748E+09 6083.12 18-MAY-06:10 5.68
June 0.187880E+09 5100.23 15-JUN-06:20 9.80
July 25444458.84 4682.07 03-JUL-06:07 11.88
August 45241274.96 4853.23 03-AUG-06:06 11.82
September 0.171187E+09 5444.39 28-SEP-06:10 8.40
October 0.565550E+09 5901.08 16-OCT-07:00 6.10
November 0.140386E+10 7596.89 24-NOV-07:10 1.20
December 0.221052E+10 8149.57 26-DEC-07:40 -1.3
         
Annual Sum or Average 0.113039E+11      
Minimum of Months 25444458.84 4682.07   -1.3
Maximum of Months 0.298390E+10 8149.57   11.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.762978E+09 5310.39 02-JAN-06:11 6.10
February 0.197855E+09 4384.74 21-FEB-06:01 1.70
March 19667416.02 3743.73 06-MAR-06:11 6.70
April 1774297.11 3351.23 19-APR-06:02 2.48
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 0.00 0.00 01-OCT-00:10 14.35
November 47089011.51 3760.66 24-NOV-06:11 1.83
December 0.304595E+09 4507.61 26-DEC-06:01 -0.8
         
Annual Sum or Average 0.133396E+10      
Minimum of Months 0.00 0.00   -0.8
Maximum of Months 0.762978E+09 5310.39   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104560E+10 5952.65 02-JAN-06:11 6.10
February 0.316163E+09 5331.48 21-FEB-06:01 1.70
March 30412297.06 4844.31 06-MAR-06:11 6.70
April 1992197.89 4434.70 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 3598840.73 4408.29 30-OCT-06:03 7.20
November 0.147477E+09 5021.57 24-NOV-06:11 1.83
December 0.561627E+09 5689.24 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.210687E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.104560E+10 5952.65   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.640802E+09 5638.12 02-JAN-06:11 6.10
February 0.182217E+09 4760.58 21-FEB-06:01 1.70
March 15185628.31 4076.60 06-MAR-06:11 6.70
April 922529.78 3448.49 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 2568224.15 3305.12 30-OCT-06:03 7.20
November 94709665.46 4353.91 24-NOV-06:11 1.83
December 0.370474E+09 5307.15 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.130688E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.640802E+09 5638.12   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.744161E+09 8251.55 02-JAN-06:11 6.10
February 0.206053E+09 7018.71 21-FEB-06:01 1.70
March 19822552.34 6002.87 06-MAR-06:11 6.70
April 1618446.21 5161.38 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 1476922.82 3453.76 16-OCT-06:03 6.60
November 0.100413E+09 6344.89 24-NOV-06:11 1.83
December 0.439480E+09 7611.13 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.151302E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.744161E+09 8251.55   17.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.649867E+09 5659.56 02-JAN-06:11 6.10
February 0.190417E+09 4760.95 21-FEB-06:01 1.70
March 19468259.44 4075.14 06-MAR-06:11 6.70
April 1625772.51 3439.13 18-APR-06:02 3.40
May 0.00 0.00 01-MAY-00:10 10.38
June 0.00 0.00 01-JUN-00:10 12.83
July 0.00 0.00 01-JUL-00:10 15.43
August 0.00 0.00 01-AUG-00:10 17.17
September 0.00 0.00 01-SEP-00:10 16.38
October 2027643.32 2723.31 16-OCT-06:03 6.60
November 98138525.24 4333.24 24-NOV-06:11 1.83
December 0.364302E+09 5314.08 26-DEC-05:01 -0.6
         
Annual Sum or Average 0.132585E+10      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.649867E+09 5659.56   17.17



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.250423E+12    
Minimum of Months 0.420695E+10 4936.01   0.191215E+11 14019.75  
Maximum of Months 0.500524E+10 4936.01   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.679453E+09 1040.56 02-JAN-16:30 0.204758E+10 1435.25 02-JAN-08:09
February 0.554537E+09 945.17 02-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.605089E+09 830.87 22-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511857E+09 667.05 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.538145E+09 541.21 17-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.526145E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.494536E+09 579.72 12-JUL-08:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.558699E+09 574.20 02-AUG-07:30 0.212947E+10 1435.25 01-AUG-07:10
September 0.528768E+09 837.22 25-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.592366E+09 1027.50 31-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.655754E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.681304E+09 1040.56 01-DEC-16:19 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.692665E+10     0.243325E+11    
Minimum of Months 0.494536E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.681304E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.416641E+09 658.76 02-JAN-16:30 0.129621E+10 908.57 02-JAN-08:09
February 0.346117E+09 604.68 02-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.380850E+09 502.99 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324117E+09 354.45 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.342443E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.335286E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.315061E+09 339.83 12-JUL-08:30 0.127534E+10 908.57 03-JUL-07:10
August 0.355534E+09 353.24 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.332304E+09 508.51 25-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.369493E+09 648.37 31-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.405418E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.415515E+09 658.76 01-DEC-16:19 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.433878E+10     0.154036E+11    
Minimum of Months 0.315061E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.416641E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.642314E+09 1040.56 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.534339E+09 922.83 02-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.597697E+09 821.38 22-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.512097E+09 583.86 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.540637E+09 542.27 17-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.529261E+09 530.72 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.499149E+09 574.59 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.562266E+09 572.97 02-AUG-07:30 0.212945E+10 1435.24 01-AUG-07:10
September 0.525585E+09 830.09 25-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.576811E+09 1025.02 31-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.626358E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.637362E+09 1040.56 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.678387E+10     0.243324E+11    
Minimum of Months 0.499149E+09 530.72   0.185364E+10 1435.24  
Maximum of Months 0.642314E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.416537E+09 658.71 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.342850E+09 582.59 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.380693E+09 534.11 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324033E+09 454.12 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.341100E+09 352.78 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.333466E+09 346.71 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314874E+09 468.46 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.354428E+09 462.90 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.334504E+09 537.17 25-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.369899E+09 650.62 31-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.403893E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.415132E+09 658.71 01-DEC-16:19 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.433141E+10     0.154035E+11    
Minimum of Months 0.314874E+09 346.71   0.117344E+10 908.57  
Maximum of Months 0.416537E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.675308E+09 1040.56 02-JAN-16:30 0.204758E+10 1435.25 02-JAN-08:09
February 0.551908E+09 941.40 02-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.603183E+09 822.79 22-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511139E+09 583.20 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.537733E+09 536.46 17-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.525872E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.494165E+09 576.91 12-JUL-08:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.558123E+09 571.03 02-AUG-07:30 0.212947E+10 1435.25 01-AUG-07:10
September 0.527671E+09 829.44 25-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.589639E+09 1027.00 31-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.652193E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.677239E+09 1040.56 01-DEC-16:19 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.690417E+10     0.243325E+11    
Minimum of Months 0.494165E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.677239E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.415134E+09 658.76 02-JAN-16:30 0.129621E+10 908.57 02-JAN-08:09
February 0.345084E+09 602.99 02-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.380122E+09 497.81 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.323766E+09 352.14 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.342135E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.335012E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.314770E+09 336.35 12-JUL-08:30 0.127534E+10 908.57 03-JUL-07:10
August 0.355113E+09 350.85 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.331724E+09 503.55 25-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.368473E+09 648.02 31-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.404154E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.413878E+09 658.76 01-DEC-16:19 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.432936E+10     0.154036E+11    
Minimum of Months 0.314770E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.415134E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.639961E+09 1040.56 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.533044E+09 917.32 02-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.596618E+09 812.84 22-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.511517E+09 581.12 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.540106E+09 537.57 17-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.528748E+09 525.50 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.498606E+09 571.49 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.561629E+09 569.72 02-AUG-07:30 0.212945E+10 1435.24 01-AUG-07:10
September 0.524892E+09 821.97 25-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.575517E+09 1024.40 31-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.624566E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.635200E+09 1040.56 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.677040E+10     0.243324E+11    
Minimum of Months 0.498606E+09 525.50   0.185364E+10 1435.24  
Maximum of Months 0.639961E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.414945E+09 658.71 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.341758E+09 580.25 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.379854E+09 530.30 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.323551E+09 447.91 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.340819E+09 350.54 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.333103E+09 344.24 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314379E+09 462.96 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.354011E+09 457.02 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.333740E+09 533.46 25-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.368822E+09 650.37 31-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.402363E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.413301E+09 658.71 01-DEC-16:19 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.432064E+10     0.154035E+11    
Minimum of Months 0.314379E+09 344.24   0.117344E+10 908.57  
Maximum of Months 0.414945E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.679449E+09 1040.56 02-JAN-16:30 0.204758E+10 1435.25 02-JAN-08:09
February 0.554534E+09 945.17 02-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.605087E+09 830.85 22-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511856E+09 667.02 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.538145E+09 541.20 17-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.526145E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.494536E+09 579.71 12-JUL-08:30 0.201461E+10 1435.25 03-JUL-07:10
August 0.558698E+09 574.19 02-AUG-07:30 0.212947E+10 1435.25 01-AUG-07:10
September 0.528767E+09 837.21 25-SEP-07:10 0.197634E+10 1435.25 01-SEP-07:10
October 0.592363E+09 1027.50 31-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.655749E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.681299E+09 1040.56 01-DEC-16:19 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.692663E+10     0.243325E+11    
Minimum of Months 0.494536E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.681299E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.416639E+09 658.76 02-JAN-16:30 0.129621E+10 908.57 02-JAN-08:09
February 0.346115E+09 604.67 02-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.380849E+09 502.98 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324116E+09 354.45 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.342443E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.335285E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.315061E+09 339.83 12-JUL-08:30 0.127534E+10 908.57 03-JUL-07:10
August 0.355534E+09 353.24 02-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.332303E+09 508.50 25-SEP-07:10 0.125111E+10 908.57 01-SEP-07:10
October 0.369492E+09 648.37 31-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.405416E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.415513E+09 658.76 01-DEC-16:19 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.433877E+10     0.154036E+11    
Minimum of Months 0.315061E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.416639E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.642312E+09 1040.56 02-JAN-16:30 0.204757E+10 1435.24 02-JAN-08:09
February 0.534338E+09 922.82 02-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.597695E+09 821.36 22-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.512096E+09 583.85 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.540636E+09 542.25 17-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.529261E+09 530.71 29-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.499148E+09 574.59 12-JUL-07:30 0.201460E+10 1435.24 03-JUL-07:10
August 0.562266E+09 572.96 02-AUG-07:30 0.212945E+10 1435.24 01-AUG-07:10
September 0.525584E+09 830.07 25-SEP-07:10 0.197632E+10 1435.24 01-SEP-07:10
October 0.576809E+09 1025.02 31-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.626356E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.637360E+09 1040.56 01-DEC-16:19 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.678386E+10     0.243324E+11    
Minimum of Months 0.499148E+09 530.71   0.185364E+10 1435.24  
Maximum of Months 0.642312E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.416535E+09 658.71 02-JAN-16:30 0.129620E+10 908.57 02-JAN-08:09
February 0.342848E+09 582.59 02-FEB-08:09 0.117344E+10 908.57 01-FEB-08:09
March 0.380692E+09 534.10 22-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324032E+09 454.11 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.341100E+09 352.77 17-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.333465E+09 346.70 29-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314873E+09 468.44 12-JUL-07:30 0.127533E+10 908.57 03-JUL-07:10
August 0.354427E+09 462.89 28-AUG-07:30 0.134804E+10 908.57 01-AUG-07:10
September 0.334503E+09 537.16 25-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.369898E+09 650.62 31-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.403861E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.415130E+09 658.71 01-DEC-16:19 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.433136E+10     0.154035E+11    
Minimum of Months 0.314873E+09 346.70   0.117344E+10 908.57  
Maximum of Months 0.416535E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.679453E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.367904E+09
February 0.901968E+09 0.554537E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.332157E+09
March 0.107774E+10 0.605089E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.332177E+09
April 0.956342E+09 0.511857E+09 0.197726E+10 0.00 0.00 0.00 0.00 736373.57 0.326997E+09
May 0.103597E+10 0.538145E+09 0.208852E+10 0.00 0.00 0.00 0.00 19006.54 0.266268E+09
June 0.103308E+10 0.526145E+09 0.205071E+10 0.00 0.00 0.00 0.00 210034.55 0.223621E+09
July 0.959235E+09 0.494536E+09 0.201461E+10 0.00 0.00 0.00 0.00 2684230.16 0.188067E+09
August 0.107774E+10 0.558699E+09 0.212947E+10 0.00 0.00 0.00 0.00 4736719.88 0.152281E+09
September 0.956342E+09 0.528768E+09 0.197634E+10 0.00 0.00 0.00 0.00 19426.29 0.121904E+09
October 0.994195E+09 0.592366E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.266162E+09
November 0.984487E+09 0.655754E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.290848E+09
December 0.959235E+09 0.681304E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.313549E+09
                   
Annual Sum or Average 0.119305E+11 0.692665E+10 0.243325E+11 0.00 0.00 0.00 0.00 8405790.98 0.318193E+10
Minimum of Months 0.901968E+09 0.494536E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.121904E+09
Maximum of Months 0.107774E+10 0.681304E+09 0.212947E+10 0.00 0.00 0.00 0.00 4736719.88 0.367904E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.416641E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.245279E+09
February 0.571020E+09 0.346117E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.225147E+09
March 0.682301E+09 0.380850E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.225317E+09
April 0.605444E+09 0.324117E+09 0.125169E+10 0.00 0.00 0.00 0.00 387416.54 0.223285E+09
May 0.655854E+09 0.342443E+09 0.132213E+10 0.00 0.00 0.00 0.00 12672.58 0.181270E+09
June 0.654023E+09 0.335286E+09 0.129819E+10 0.00 0.00 0.00 0.00 140027.20 0.152963E+09
July 0.607275E+09 0.315061E+09 0.127534E+10 0.00 0.00 0.00 0.00 1282126.32 0.128197E+09
August 0.682301E+09 0.355534E+09 0.134804E+10 0.00 0.00 0.00 0.00 2984934.78 0.104401E+09
September 0.605444E+09 0.332304E+09 0.125111E+10 0.00 0.00 0.00 0.00 12951.80 83217236.06
October 0.629407E+09 0.369493E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.180962E+09
November 0.623262E+09 0.405418E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.194416E+09
December 0.607275E+09 0.415515E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.209304E+09
                   
Annual Sum or Average 0.755301E+10 0.433878E+10 0.154036E+11 0.00 0.00 0.00 0.00 4820129.21 0.215376E+10
Minimum of Months 0.571020E+09 0.315061E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 83217236.06
Maximum of Months 0.682301E+09 0.416641E+09 0.134804E+10 0.00 0.00 0.00 0.00 2984934.78 0.245279E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.642314E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.378470E+09
February 0.901968E+09 0.534339E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.356000E+09
March 0.107774E+10 0.597697E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.348508E+09
April 0.956342E+09 0.512097E+09 0.197725E+10 0.00 0.00 0.00 0.00 430801.30 0.340402E+09
May 0.103597E+10 0.540637E+09 0.208851E+10 0.00 0.00 0.00 0.00 19002.71 0.273707E+09
June 0.103308E+10 0.529261E+09 0.205070E+10 0.00 0.00 0.00 0.00 210020.04 0.228411E+09
July 0.959235E+09 0.499149E+09 0.201460E+10 0.00 0.00 0.00 0.00 1870376.86 0.193435E+09
August 0.107774E+10 0.562266E+09 0.212945E+10 0.00 0.00 0.00 0.00 4444920.68 0.158176E+09
September 0.956342E+09 0.525585E+09 0.197632E+10 0.00 0.00 0.00 0.00 19380.29 0.128885E+09
October 0.994195E+09 0.576811E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.284232E+09
November 0.984487E+09 0.626358E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.300956E+09
December 0.959235E+09 0.637362E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.325073E+09
                   
Annual Sum or Average 0.119305E+11 0.678387E+10 0.243324E+11 0.00 0.00 0.00 0.00 6994501.89 0.331625E+10
Minimum of Months 0.901968E+09 0.499149E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.128885E+09
Maximum of Months 0.107774E+10 0.642314E+09 0.212945E+10 0.00 0.00 0.00 0.00 4444920.68 0.378470E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.416537E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.246088E+09
February 0.570983E+09 0.342850E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.226397E+09
March 0.682256E+09 0.380693E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.226702E+09
April 0.605404E+09 0.324033E+09 0.125169E+10 0.00 0.00 0.00 0.00 197502.17 0.224532E+09
May 0.655811E+09 0.341100E+09 0.132212E+10 0.00 0.00 0.00 0.00 12672.91 0.184968E+09
June 0.653980E+09 0.333466E+09 0.129818E+10 0.00 0.00 0.00 0.00 140021.92 0.153943E+09
July 0.607235E+09 0.314874E+09 0.127533E+10 0.00 0.00 0.00 0.00 1260944.98 0.132459E+09
August 0.682256E+09 0.354428E+09 0.134804E+10 0.00 0.00 0.00 0.00 2993913.96 0.106969E+09
September 0.605404E+09 0.334504E+09 0.125110E+10 0.00 0.00 0.00 0.00 12951.60 85850034.32
October 0.629366E+09 0.369899E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.182550E+09
November 0.623221E+09 0.403893E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.195118E+09
December 0.607235E+09 0.415132E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.210158E+09
                   
Annual Sum or Average 0.755252E+10 0.433141E+10 0.154035E+11 0.00 0.00 0.00 0.00 4618007.54 0.217573E+10
Minimum of Months 0.570983E+09 0.314874E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 85850034.32
Maximum of Months 0.682256E+09 0.416537E+09 0.134804E+10 0.00 0.00 0.00 0.00 2993913.96 0.246088E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.675308E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.209017E+09
February 0.901968E+09 0.551908E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.189376E+09
March 0.107774E+10 0.603183E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.183635E+09
April 0.956342E+09 0.511139E+09 0.197726E+10 0.00 0.00 0.00 0.00 463650.73 0.176875E+09
May 0.103597E+10 0.537733E+09 0.208852E+10 0.00 0.00 0.00 0.00 11815.83 0.142847E+09
June 0.103308E+10 0.525872E+09 0.205071E+10 0.00 0.00 0.00 0.00 118677.43 0.119967E+09
July 0.959235E+09 0.494165E+09 0.201461E+10 0.00 0.00 0.00 0.00 2069944.49 0.100974E+09
August 0.107774E+10 0.558123E+09 0.212947E+10 0.00 0.00 0.00 0.00 2758697.84 82469579.00
September 0.956342E+09 0.527671E+09 0.197634E+10 0.00 0.00 0.00 0.00 11771.71 67548302.79
October 0.994195E+09 0.589639E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.154367E+09
November 0.984487E+09 0.652193E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.171528E+09
December 0.959235E+09 0.677239E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.182771E+09
                   
Annual Sum or Average 0.119305E+11 0.690417E+10 0.243325E+11 0.00 0.00 0.00 0.00 5434558.04 0.178137E+10
Minimum of Months 0.901968E+09 0.494165E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 67548302.79
Maximum of Months 0.107774E+10 0.677239E+09 0.212947E+10 0.00 0.00 0.00 0.00 2758697.84 0.209017E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.415134E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.139381E+09
February 0.571020E+09 0.345084E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.128778E+09
March 0.682301E+09 0.380122E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.126523E+09
April 0.605444E+09 0.323766E+09 0.125169E+10 0.00 0.00 0.00 0.00 223547.87 0.123885E+09
May 0.655854E+09 0.342135E+09 0.132213E+10 0.00 0.00 0.00 0.00 7877.06 99220342.68
June 0.654023E+09 0.335012E+09 0.129819E+10 0.00 0.00 0.00 0.00 79117.91 84204669.05
July 0.607275E+09 0.314770E+09 0.127534E+10 0.00 0.00 0.00 0.00 774778.79 70206034.93
August 0.682301E+09 0.355113E+09 0.134804E+10 0.00 0.00 0.00 0.00 1624936.36 58188570.33
September 0.605444E+09 0.331724E+09 0.125111E+10 0.00 0.00 0.00 0.00 7847.71 46946263.28
October 0.629407E+09 0.368473E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.106189E+09
November 0.623262E+09 0.404154E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.115143E+09
December 0.607275E+09 0.413878E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.122247E+09
                   
Annual Sum or Average 0.755301E+10 0.432936E+10 0.154036E+11 0.00 0.00 0.00 0.00 2718105.71 0.122091E+10
Minimum of Months 0.571020E+09 0.314770E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 46946263.28
Maximum of Months 0.682301E+09 0.415134E+09 0.134804E+10 0.00 0.00 0.00 0.00 1624936.36 0.139381E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.639961E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.397769E+10
February 0.901968E+09 0.533044E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.349309E+10
March 0.107774E+10 0.596618E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.371412E+10
April 0.956342E+09 0.511517E+09 0.197725E+10 0.00 0.00 0.00 0.00 14199079.69 0.279850E+10
May 0.103597E+10 0.540106E+09 0.208851E+10 0.00 0.00 0.00 0.00 1604613.35 0.247457E+10
June 0.103308E+10 0.528748E+09 0.205070E+10 0.00 0.00 0.00 0.00 15758900.29 0.190031E+10
July 0.959235E+09 0.498606E+09 0.201460E+10 0.00 0.00 0.00 0.00 93264204.14 0.122717E+10
August 0.107774E+10 0.561629E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.254742E+09 0.117810E+10
September 0.956342E+09 0.524892E+09 0.197632E+10 0.00 0.00 0.00 0.00 3499200.74 0.178310E+10
October 0.994195E+09 0.575517E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.282922E+10
November 0.984487E+09 0.624566E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.351902E+10
December 0.959235E+09 0.635200E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.385442E+10
                   
Annual Sum or Average 0.119305E+11 0.677040E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.383068E+09 0.327493E+11
Minimum of Months 0.901968E+09 0.498606E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.117810E+10
Maximum of Months 0.107774E+10 0.639961E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.254742E+09 0.397769E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.414945E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.139803E+09
February 0.570983E+09 0.341758E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.129087E+09
March 0.682256E+09 0.379854E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.127033E+09
April 0.605404E+09 0.323551E+09 0.125169E+10 0.00 0.00 0.00 0.00 122615.64 0.123942E+09
May 0.655811E+09 0.340819E+09 0.132212E+10 0.00 0.00 0.00 0.00 7877.47 0.102273E+09
June 0.653980E+09 0.333103E+09 0.129818E+10 0.00 0.00 0.00 0.00 79118.13 84598041.67
July 0.607235E+09 0.314379E+09 0.127533E+10 0.00 0.00 0.00 0.00 727189.26 74075068.18
August 0.682256E+09 0.354011E+09 0.134804E+10 0.00 0.00 0.00 0.00 1622871.32 60086998.34
September 0.605404E+09 0.333740E+09 0.125110E+10 0.00 0.00 0.00 0.00 7847.67 48818288.89
October 0.629366E+09 0.368822E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.107142E+09
November 0.623221E+09 0.402363E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.115447E+09
December 0.607235E+09 0.413301E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.122587E+09
                   
Annual Sum or Average 0.755252E+10 0.432064E+10 0.154035E+11 0.00 0.00 0.00 0.00 2567519.48 0.123489E+10
Minimum of Months 0.570983E+09 0.314379E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 48818288.89
Maximum of Months 0.682256E+09 0.414945E+09 0.134804E+10 0.00 0.00 0.00 0.00 1622871.32 0.139803E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.679449E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.325374E+09
February 0.901968E+09 0.554534E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.297369E+09
March 0.107774E+10 0.605087E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.296956E+09
April 0.956342E+09 0.511856E+09 0.197726E+10 0.00 0.00 0.00 0.00 638055.95 0.288562E+09
May 0.103597E+10 0.538145E+09 0.208852E+10 0.00 0.00 0.00 0.00 17144.62 0.231294E+09
June 0.103308E+10 0.526145E+09 0.205071E+10 0.00 0.00 0.00 0.00 180270.54 0.192626E+09
July 0.959235E+09 0.494536E+09 0.201461E+10 0.00 0.00 0.00 0.00 2668200.91 0.161825E+09
August 0.107774E+10 0.558698E+09 0.212947E+10 0.00 0.00 0.00 0.00 4042746.81 0.132028E+09
September 0.956342E+09 0.528767E+09 0.197634E+10 0.00 0.00 0.00 0.00 17284.91 0.107378E+09
October 0.994195E+09 0.592363E+09 0.204804E+10 0.00 0.00 0.00 0.00 0.00 0.240875E+09
November 0.984487E+09 0.655749E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.263466E+09
December 0.959235E+09 0.681299E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.281951E+09
                   
Annual Sum or Average 0.119305E+11 0.692663E+10 0.243325E+11 0.00 0.00 0.00 0.00 7563703.74 0.281970E+10
Minimum of Months 0.901968E+09 0.494536E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.107378E+09
Maximum of Months 0.107774E+10 0.681299E+09 0.212947E+10 0.00 0.00 0.00 0.00 4042746.81 0.325374E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.416639E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.216917E+09
February 0.421807E+09 0.346115E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.201866E+09
March 0.502994E+09 0.380849E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.201512E+09
April 0.447140E+09 0.324116E+09 0.125169E+10 0.00 0.00 0.00 0.00 333689.62 0.196789E+09
May 0.484071E+09 0.342443E+09 0.132213E+10 0.00 0.00 0.00 0.00 10695.21 0.157377E+09
June 0.482240E+09 0.335285E+09 0.129819E+10 0.00 0.00 0.00 0.00 115715.41 0.131768E+09
July 0.448971E+09 0.315061E+09 0.127534E+10 0.00 0.00 0.00 0.00 1124420.64 0.110412E+09
August 0.502994E+09 0.355534E+09 0.134804E+10 0.00 0.00 0.00 0.00 2430529.76 90481860.80
September 0.447140E+09 0.332303E+09 0.125111E+10 0.00 0.00 0.00 0.00 10966.45 73253137.74
October 0.465148E+09 0.369492E+09 0.129650E+10 0.00 0.00 0.00 0.00 0.00 0.163578E+09
November 0.460569E+09 0.405416E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.176456E+09
December 0.448971E+09 0.415513E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.188446E+09
                   
Annual Sum or Average 0.557719E+10 0.433877E+10 0.154036E+11 0.00 0.00 0.00 0.00 4026017.10 0.190886E+10
Minimum of Months 0.421807E+09 0.315061E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 73253137.74
Maximum of Months 0.502994E+09 0.416639E+09 0.134804E+10 0.00 0.00 0.00 0.00 2430529.76 0.216917E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.642312E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.335295E+09
February 0.901968E+09 0.534338E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.317832E+09
March 0.107774E+10 0.597695E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.309808E+09
April 0.956342E+09 0.512096E+09 0.197725E+10 0.00 0.00 0.00 0.00 387659.32 0.298890E+09
May 0.103597E+10 0.540636E+09 0.208851E+10 0.00 0.00 0.00 0.00 17141.15 0.237333E+09
June 0.103308E+10 0.529261E+09 0.205070E+10 0.00 0.00 0.00 0.00 180256.95 0.196780E+09
July 0.959235E+09 0.499148E+09 0.201460E+10 0.00 0.00 0.00 0.00 1600260.34 0.166279E+09
August 0.107774E+10 0.562266E+09 0.212945E+10 0.00 0.00 0.00 0.00 3738854.74 0.136858E+09
September 0.956342E+09 0.525584E+09 0.197632E+10 0.00 0.00 0.00 0.00 17158.95 0.112772E+09
October 0.994195E+09 0.576809E+09 0.204803E+10 0.00 0.00 0.00 0.00 0.00 0.254530E+09
November 0.984487E+09 0.626356E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.272140E+09
December 0.959235E+09 0.637360E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.292147E+09
                   
Annual Sum or Average 0.119305E+11 0.678386E+10 0.243324E+11 0.00 0.00 0.00 0.00 5941331.47 0.293066E+10
Minimum of Months 0.901968E+09 0.499148E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.112772E+09
Maximum of Months 0.107774E+10 0.642312E+09 0.212945E+10 0.00 0.00 0.00 0.00 3738854.74 0.335295E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.416535E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.217580E+09
February 0.570983E+09 0.342848E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.202323E+09
March 0.682256E+09 0.380692E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.202077E+09
April 0.605404E+09 0.324032E+09 0.125169E+10 0.00 0.00 0.00 0.00 167243.89 0.197578E+09
May 0.655811E+09 0.341100E+09 0.132212E+10 0.00 0.00 0.00 0.00 11428.76 0.160421E+09
June 0.653980E+09 0.333465E+09 0.129818E+10 0.00 0.00 0.00 0.00 120181.14 0.132598E+09
July 0.607235E+09 0.314873E+09 0.127533E+10 0.00 0.00 0.00 0.00 1103484.06 0.113931E+09
August 0.682256E+09 0.354427E+09 0.134804E+10 0.00 0.00 0.00 0.00 2513259.54 92601475.44
September 0.605404E+09 0.334503E+09 0.125110E+10 0.00 0.00 0.00 0.00 11523.19 75174050.91
October 0.629366E+09 0.369898E+09 0.129649E+10 0.00 0.00 0.00 0.00 0.00 0.164464E+09
November 0.623221E+09 0.403861E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.176573E+09
December 0.607235E+09 0.415130E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.188904E+09
                   
Annual Sum or Average 0.755252E+10 0.433136E+10 0.154035E+11 0.00 0.00 0.00 0.00 3927120.59 0.192422E+10
Minimum of Months 0.570983E+09 0.314873E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 75174050.91
Maximum of Months 0.682256E+09 0.416535E+09 0.134804E+10 0.00 0.00 0.00 0.00 2513259.54 0.217580E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.456532E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.423831E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.418054E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 533200.48 0.398582E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1254.93 0.316610E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82666.11 0.262550E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2198073.72 0.221111E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3775212.68 0.182695E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 351.56 0.150278E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.343416E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.377285E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.403240E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6590759.48 0.395418E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.150278E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3775212.68 0.456532E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.551445E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.510835E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.514331E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 861753.75 0.496996E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1721.30 0.399485E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 106070.51 0.332718E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2954253.78 0.279170E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4955840.92 0.230331E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 384.02 0.187453E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.416957E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.450802E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.482083E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8880024.28 0.485261E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.187453E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4955840.92 0.551445E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.548068E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.509667E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.512859E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 366368.74 0.509607E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.420120E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33099.33 0.352548E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1092989.26 0.298064E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3547907.65 0.238457E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.191289E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.413401E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.439757E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.470579E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5040364.98 0.490442E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.191289E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3547907.65 0.548068E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 625.02 12-JAN-24:00
February 1306.65 01-FEB-10:09 945.17 02-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 572.64 16-FEB-22:03
March 1306.65 01-MAR-10:09 830.87 22-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 560.98 28-MAR-24:00
April 1306.65 03-APR-09:09 667.05 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 86.39 01-APR-17:03 604.40 07-APR-24:00
May 1306.65 01-MAY-09:09 541.21 17-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 2.50 05-MAY-16:00 447.31 22-MAY-24:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 9.53 28-JUN-16:00 595.14 13-JUN-03:00
July 1306.65 03-JUL-09:09 579.72 12-JUL-08:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 70.84 23-JUL-13:53 298.01 02-JUL-04:00
August 1306.65 01-AUG-09:09 574.20 02-AUG-07:30 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 38.50 08-AUG-17:00 420.71 11-AUG-04:00
September 1306.65 01-SEP-09:09 837.22 25-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 2.99 14-SEP-17:00 280.61 18-SEP-23:00
October 1306.65 02-OCT-09:09 1027.50 31-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 529.77 31-OCT-21:05
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 593.28 29-NOV-23:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 479.93 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   280.61  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 86.39   625.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 658.76 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 414.09 12-JAN-24:00
February 827.22 01-FEB-10:09 604.68 02-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 381.42 16-FEB-22:03
March 827.22 01-MAR-10:09 502.99 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 380.54 28-MAR-24:00
April 827.22 03-APR-09:09 354.45 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 44.71 01-APR-17:03 408.46 07-APR-24:00
May 827.22 01-MAY-09:09 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.67 05-MAY-16:00 298.05 22-MAY-24:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 6.35 28-JUN-16:00 395.40 13-JUN-03:00
July 827.22 03-JUL-09:09 339.83 12-JUL-08:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 26.41 23-JUL-15:36 202.14 02-JUL-10:00
August 827.22 01-AUG-09:09 353.24 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 25.66 08-AUG-17:00 281.21 11-AUG-04:00
September 827.22 01-SEP-09:09 508.51 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.99 14-SEP-17:00 186.68 18-SEP-23:00
October 827.22 02-OCT-09:09 648.37 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 352.74 31-OCT-21:05
November 827.22 01-NOV-09:09 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 393.32 29-NOV-23:00
December 827.22 01-DEC-10:09 658.76 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 318.51 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   186.68  
Maximum of Months 827.22   658.76   908.57   0.00 0.00 0.00 0.00 44.71   414.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 627.00 12-JAN-24:00
February 1306.65 01-FEB-10:09 922.83 02-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 614.65 19-FEB-12:00
March 1306.65 01-MAR-10:09 821.38 22-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 586.05 28-MAR-24:00
April 1306.65 03-APR-09:09 583.86 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 33.98 01-APR-17:30 615.87 07-APR-24:00
May 1306.65 01-MAY-09:09 542.27 17-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 2.50 05-MAY-16:00 449.73 22-MAY-24:00
June 1306.65 01-JUN-09:09 530.72 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 9.53 28-JUN-16:00 594.45 13-JUN-03:00
July 1306.65 03-JUL-09:09 574.59 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 42.10 23-JUL-15:36 301.04 02-JUL-04:00
August 1306.65 01-AUG-09:09 572.97 02-AUG-07:30 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 38.49 08-AUG-17:00 427.28 11-AUG-04:00
September 1306.65 01-SEP-09:09 830.09 25-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 2.99 14-SEP-17:00 282.98 18-SEP-23:00
October 1306.65 02-OCT-09:09 1025.02 31-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 529.77 31-OCT-21:05
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 593.18 29-NOV-23:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 482.71 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   530.72   1435.24   0.00 0.00 0.00 0.00 0.00   282.98  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 42.10   627.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 414.07 12-JAN-24:00
February 827.17 01-FEB-10:09 582.59 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 381.33 16-FEB-22:03
March 827.17 01-MAR-10:09 534.11 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 379.39 28-MAR-24:00
April 827.17 03-APR-09:09 454.12 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 15.13 01-APR-16:00 403.20 07-APR-24:00
May 827.17 01-MAY-09:09 352.78 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.67 05-MAY-16:00 299.69 22-MAY-24:00
June 827.17 01-JUN-09:09 346.71 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 6.35 28-JUN-16:00 393.91 13-JUN-03:00
July 827.17 03-JUL-09:09 468.46 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 23.05 23-JUL-15:54 201.77 02-JUL-04:00
August 827.17 01-AUG-09:09 462.90 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 25.66 08-AUG-17:00 288.85 11-AUG-04:00
September 827.17 01-SEP-09:09 537.17 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.99 14-SEP-17:00 186.90 18-SEP-23:00
October 827.17 02-OCT-09:09 650.62 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 352.52 31-OCT-21:05
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 392.58 29-NOV-23:00
December 827.17 01-DEC-10:09 658.71 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 319.07 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   346.71   908.57   0.00 0.00 0.00 0.00 0.00   186.90  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 25.66   414.07  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 356.26 12-JAN-24:00
February 1306.65 01-FEB-10:09 941.40 02-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 327.36 16-FEB-04:00
March 1306.65 01-MAR-10:09 822.79 22-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 310.05 28-MAR-24:00
April 1306.65 03-APR-09:09 583.20 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 59.82 01-APR-17:03 327.86 07-APR-24:00
May 1306.65 01-MAY-09:09 536.46 17-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 1.40 05-MAY-16:00 251.01 18-MAY-05:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 5.19 28-JUN-16:00 338.04 13-JUN-03:00
July 1306.65 03-JUL-09:09 576.91 12-JUL-08:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 50.45 23-JUL-15:50 168.61 02-JUL-04:00
August 1306.65 01-AUG-09:09 571.03 02-AUG-07:30 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 28.13 13-AUG-15:00 232.43 11-AUG-04:00
September 1306.65 01-SEP-09:09 829.44 25-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 1.67 14-SEP-17:00 159.99 18-SEP-23:00
October 1306.65 02-OCT-09:09 1027.00 31-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 288.96 31-OCT-21:10
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 341.35 29-NOV-23:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 269.11 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   159.99  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 59.82   356.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 658.76 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 236.37 12-JAN-24:00
February 827.22 01-FEB-10:09 602.99 02-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 217.19 16-FEB-04:00
March 827.22 01-MAR-10:09 497.81 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 217.80 28-MAR-24:00
April 827.22 03-APR-09:09 352.14 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 30.79 01-APR-17:03 230.41 07-APR-24:00
May 827.22 01-MAY-09:09 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 0.93 05-MAY-16:00 167.19 18-MAY-05:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 3.46 28-JUN-16:00 230.50 13-JUN-03:00
July 827.22 03-JUL-09:09 336.35 12-JUL-08:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 15.84 23-JUL-16:10 113.19 02-JUL-04:00
August 827.22 01-AUG-09:09 350.85 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 13.77 08-AUG-17:00 161.50 11-AUG-04:00
September 827.22 01-SEP-09:09 503.55 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.12 14-SEP-17:00 106.91 18-SEP-23:00
October 827.22 02-OCT-09:09 648.02 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 193.07 31-OCT-21:10
November 827.22 01-NOV-09:09 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 226.48 29-NOV-23:00
December 827.22 01-DEC-10:09 658.76 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 178.88 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   106.91  
Maximum of Months 827.22   658.76   908.57   0.00 0.00 0.00 0.00 30.79   236.37  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 19095.72 06-JAN-07:01
February 1306.65 01-FEB-10:09 917.32 02-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 17687.39 09-FEB-07:01
March 1306.65 01-MAR-10:09 812.84 22-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 17246.14 01-MAR-07:01
April 1306.65 03-APR-09:09 581.12 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 2392.06 27-APR-16:10 14871.96 19-APR-06:02
May 1306.65 01-MAY-09:09 537.57 17-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 508.33 05-MAY-16:10 12307.50 11-MAY-06:03
June 1306.65 01-JUN-09:09 525.50 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 2152.84 28-JUN-17:00 9655.18 13-JUN-11:01
July 1306.65 03-JUL-09:09 571.49 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 3809.74 31-JUL-16:10 8681.59 03-JUL-06:02
August 1306.65 01-AUG-09:09 569.72 02-AUG-07:30 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 6055.56 10-AUG-17:00 9727.09 01-AUG-06:01
September 1306.65 01-SEP-09:09 821.97 25-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 802.43 14-SEP-17:00 10386.14 27-SEP-06:03
October 1306.65 02-OCT-09:09 1024.40 31-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 12296.05 13-OCT-06:03
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 16150.31 24-NOV-07:01
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 18578.10 26-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   525.50   1435.24   0.00 0.00 0.00 0.00 0.00   8681.59  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 6055.56   19095.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 236.38 12-JAN-24:00
February 827.17 01-FEB-10:09 580.25 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 216.38 16-FEB-04:00
March 827.17 01-MAR-10:09 530.30 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 213.57 28-MAR-24:00
April 827.17 03-APR-09:09 447.91 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 8.18 01-APR-16:00 220.70 07-APR-24:00
May 827.17 01-MAY-09:09 350.54 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 0.93 05-MAY-16:00 168.95 22-MAY-24:00
June 827.17 01-JUN-09:09 344.24 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 3.46 28-JUN-16:00 225.60 13-JUN-03:00
July 827.17 03-JUL-09:09 462.96 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 12.93 23-JUL-13:43 117.30 02-JUL-04:00
August 827.17 01-AUG-09:09 457.02 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 13.77 08-AUG-17:00 167.25 11-AUG-04:00
September 827.17 01-SEP-09:09 533.46 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.12 14-SEP-17:00 107.11 18-SEP-23:00
October 827.17 02-OCT-09:09 650.37 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 193.91 31-OCT-21:10
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 226.00 29-NOV-23:00
December 827.17 01-DEC-10:09 658.71 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 179.19 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   344.24   908.57   0.00 0.00 0.00 0.00 0.00   107.11  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 13.77   236.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 557.29 12-JAN-24:00
February 1306.65 01-FEB-10:09 945.17 02-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 511.35 16-FEB-04:00
March 1306.65 01-MAR-10:09 830.85 22-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 503.58 28-MAR-24:00
April 1306.65 03-APR-09:09 667.02 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 75.56 01-APR-17:03 530.70 07-APR-24:00
May 1306.65 01-MAY-09:09 541.20 17-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 2.14 05-MAY-16:00 392.14 18-MAY-05:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 8.03 28-JUN-16:00 529.53 13-JUN-03:00
July 1306.65 03-JUL-09:09 579.71 12-JUL-08:30 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 69.57 23-JUL-16:00 265.49 02-JUL-04:00
August 1306.65 01-AUG-09:09 574.19 02-AUG-07:30 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 34.67 13-AUG-15:00 366.30 11-AUG-04:00
September 1306.65 01-SEP-09:09 837.21 25-SEP-07:10 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 2.55 14-SEP-17:00 250.17 18-SEP-23:00
October 1306.65 02-OCT-09:09 1027.50 31-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 449.20 31-OCT-21:10
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 524.39 29-NOV-23:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 418.76 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   250.17  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 75.56   557.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 658.76 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 369.32 12-JAN-24:00
February 805.43 01-FEB-08:09 604.67 02-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 338.77 16-FEB-04:00
March 805.43 01-MAR-08:09 502.98 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 340.49 28-MAR-24:00
April 805.43 03-APR-07:10 354.45 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 39.59 01-APR-17:03 358.05 07-APR-24:00
May 805.43 01-MAY-07:10 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.43 05-MAY-16:00 260.19 22-MAY-24:00
June 805.43 01-JUN-07:10 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 5.35 28-JUN-16:00 352.18 13-JUN-03:00
July 805.43 03-JUL-07:10 339.83 12-JUL-08:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 27.01 23-JUL-16:00 176.31 02-JUL-04:00
August 805.43 01-AUG-07:10 353.24 02-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 21.46 08-AUG-17:00 244.97 11-AUG-04:00
September 805.43 01-SEP-07:10 508.50 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.70 14-SEP-17:00 166.51 18-SEP-23:00
October 805.43 02-OCT-07:10 648.37 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.70 31-OCT-21:10
November 805.43 01-NOV-07:10 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 347.68 29-NOV-23:00
December 805.43 01-DEC-08:09 658.76 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 277.90 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   314.23   908.57   0.00 0.00 0.00 0.00 0.00   166.51  
Maximum of Months 805.43   658.76   908.57   0.00 0.00 0.00 0.00 39.59   369.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:30 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 559.33 12-JAN-24:00
February 1306.65 01-FEB-10:09 922.82 02-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 552.50 19-FEB-12:00
March 1306.65 01-MAR-10:09 821.36 22-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 522.62 28-MAR-24:00
April 1306.65 03-APR-09:09 583.85 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 33.50 01-APR-17:30 539.56 07-APR-24:00
May 1306.65 01-MAY-09:09 542.25 17-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 2.14 05-MAY-16:00 392.13 22-MAY-24:00
June 1306.65 01-JUN-09:09 530.71 29-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 8.03 28-JUN-16:00 529.07 13-JUN-03:00
July 1306.65 03-JUL-09:09 574.59 12-JUL-07:30 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 40.17 23-JUL-15:56 267.87 02-JUL-04:00
August 1306.65 01-AUG-09:09 572.96 02-AUG-07:30 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 32.19 08-AUG-17:00 371.68 11-AUG-04:00
September 1306.65 01-SEP-09:09 830.07 25-SEP-07:10 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 2.55 14-SEP-17:00 251.95 18-SEP-23:00
October 1306.65 02-OCT-09:09 1025.02 31-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 449.57 31-OCT-21:10
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 524.91 29-NOV-23:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:19 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 422.40 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   530.71   1435.24   0.00 0.00 0.00 0.00 0.00   251.95  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 40.17   559.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:30 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 369.22 12-JAN-24:00
February 827.17 01-FEB-10:09 582.59 02-FEB-08:09 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 337.50 16-FEB-04:00
March 827.17 01-MAR-10:09 534.10 22-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 339.74 28-MAR-24:00
April 827.17 03-APR-09:09 454.11 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 12.70 01-APR-16:00 353.99 07-APR-24:00
May 827.17 01-MAY-09:09 352.77 17-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 1.43 05-MAY-16:00 261.26 22-MAY-24:00
June 827.17 01-JUN-09:09 346.70 29-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 5.35 28-JUN-16:00 350.61 13-JUN-03:00
July 827.17 03-JUL-09:09 468.44 12-JUL-07:30 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 20.14 23-JUL-14:35 179.47 02-JUL-04:00
August 827.17 01-AUG-09:09 462.89 28-AUG-07:30 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 21.46 08-AUG-17:00 251.05 11-AUG-04:00
September 827.17 01-SEP-09:09 537.16 25-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 1.70 14-SEP-17:00 166.57 18-SEP-23:00
October 827.17 02-OCT-09:09 650.62 31-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.25 31-OCT-21:10
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 346.90 29-NOV-23:00
December 827.17 01-DEC-10:09 658.71 01-DEC-16:19 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 278.63 22-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   346.70   908.57   0.00 0.00 0.00 0.00 0.00   166.57  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 21.46   369.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 791.09 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 734.23 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 713.87 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.10 01-APR-17:03 738.42 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.92 05-MAY-16:00 552.37 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.56 28-JUN-15:00 740.90 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63.71 23-JUL-13:53 371.56 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.94 13-AUG-15:20 502.96 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.43 14-SEP-17:00 343.64 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 644.00 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 743.39 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 592.34 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   343.64  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.10   791.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 971.65 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 890.81 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 886.62 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.04 01-APR-17:03 933.79 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.22 05-MAY-16:00 690.14 18-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.50 28-JUN-15:00 933.38 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.62 23-JUL-13:53 465.27 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.11 13-AUG-15:20 639.84 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46 14-SEP-17:00 422.87 30-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 783.32 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 901.80 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 726.92 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   422.87  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.04   971.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 941.77 12-JAN-24:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 854.09 16-FEB-04:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 843.90 28-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.93 01-APR-17:03 925.18 07-APR-24:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 670.19 22-MAY-24:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.89 28-JUN-17:00 885.67 13-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.50 24-JUL-14:00 442.45 02-JUL-04:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.16 08-AUG-17:00 629.65 11-AUG-04:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 419.65 18-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 796.79 31-OCT-21:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 895.76 29-NOV-23:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 745.55 22-DEC-23:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   419.65  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.93   941.77  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11135.99 12-JAN-17:00 6035.01 4936.01 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
February 14787.18 28-FEB-17:00 6035.01 4936.01 13991.00 0.00 0.00 0.00 0.00 0.00 0.00
March 18718.85 20-MAR-06:03 5082.11 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
April 35561.64 28-APR-06:02 7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
May 38168.83 08-MAY-05:12 2541.06 2193.73 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
June 39242.96 12-JUN-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
July 39349.53 17-JUL-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
August 39453.18 28-AUG-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
September 39311.09 05-SEP-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
October 38096.49 10-OCT-05:12 2541.06 2193.73 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
November 28994.82 06-NOV-07:03 5082.11 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
December 13627.36 06-DEC-15:50 6035.01 4936.01 13979.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11135.99   2541.06 2193.73 13979.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 39453.18   7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 410.28
February 1823.93 27-FEB-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.92
March 2914.98 14-MAR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.67
April 8433.97 27-APR-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.64 0.00
May 8836.77 15-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.56
June 8637.11 28-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.84
July 9838.89 24-JUL-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.17 0.00
August 9937.18 10-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.35 0.00
September 7763.91 14-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.61
October 5440.22 04-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.14
November 2302.28 04-NOV-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.64
December 293.71 02-DEC-15:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.09
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9937.18   0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.17 410.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1613.35 14-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.39
February 1852.09 10-FEB-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.45
March 2786.69 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.63
April 2961.05 27-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.96 0.00
May 3365.66 15-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.56
June 3363.03 28-JUN-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.40 0.00
July 4626.37 31-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.87 0.00
August 4760.82 14-AUG-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 35.36
September 3757.16 11-SEP-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.45
October 2309.86 04-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.85
November 2105.67 10-NOV-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56.47
December 1317.10 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.16
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1317.10   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4760.82   0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.87 79.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2274.79 13-JAN-06:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 127.00
February 2735.38 10-FEB-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.61
March 3354.60 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.41
April 3362.13 27-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.71 0.00
May 4003.94 08-MAY-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.94
June 3778.63 28-JUN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.46 0.00
July 5044.63 31-JUL-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.03 0.00
August 5293.39 14-AUG-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.44
September 4559.15 11-SEP-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.32
October 3169.28 04-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.92
November 2510.15 16-NOV-07:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 56.54
December 2372.83 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 65.73
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2274.79   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5293.39   0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.03 127.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6199.75 06-JAN-08:20 48280.06 39488.12 54466.56 0.00 0.00 0.00 0.00 0.00 0.00
February 7995.20 28-FEB-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 9486.92 02-MAR-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14268.91 27-APR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 24101.37 08-MAY-06:02 7623.17 9872.16 18155.52 0.00 0.00 0.00 0.00 0.00 0.00
June 29913.98 12-JUN-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 30043.78 31-JUL-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 30634.56 14-AUG-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 27553.24 11-SEP-06:01 8893.70 11517.52 21181.44 0.00 0.00 0.00 0.00 0.00 0.00
October 13837.17 04-OCT-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 8786.26 06-NOV-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 6294.40 06-DEC-16:10 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6199.75   3176.32 2742.16 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30634.56   48280.06 39488.12 54466.56 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5764.07 06-JAN-10:30 6198.29 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 7018.64 28-FEB-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 8525.16 02-MAR-17:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 15649.88 27-APR-15:40 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 16782.74 15-MAY-15:30 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 16988.44 28-JUN-15:50 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
July 24132.02 24-JUL-06:03 5082.11 6581.44 12103.68 0.00 0.00 0.00 0.00 0.00 0.00
August 27857.89 14-AUG-06:02 6352.64 8226.80 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 16585.34 11-SEP-15:40 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
October 13717.33 04-OCT-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 6457.03 02-NOV-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 5844.71 05-DEC-16:15 12070.02 9872.03 13616.64 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5764.07   5082.11 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27857.89   12070.02 9872.03 15129.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1011.57 11-JAN-16:20 1272.23 966.90 1435.25 0.00 0.00 0.00 0.00 0.00 50.48
February 1286.30 28-FEB-15:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 1370.43 10-MAR-14:50 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 34.99
April 4484.14 27-APR-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 12.94 0.00
May 4836.91 15-MAY-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.55
June 5131.32 21-JUN-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 2.21 0.00
July 6845.41 24-JUL-06:03 1071.35 661.80 2551.55 0.00 0.00 0.00 0.00 0.00 14.94
August 5618.25 09-AUG-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 23.60 0.00
September 4265.78 12-SEP-14:50 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 1.10 0.00
October 2690.04 04-OCT-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 13.50
November 1229.15 02-NOV-14:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 27.90
December 949.64 05-DEC-15:10 1272.23 697.95 1435.25 0.00 0.00 0.00 0.00 0.00 38.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 949.64   1071.35 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6845.41   1306.65 966.90 2551.55 0.00 0.00 0.00 0.00 23.60 50.48



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 700.34 05-JAN-09:20 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 34.36
February 861.28 27-FEB-15:50 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 8.10
March 2829.59 14-MAR-09:50 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 22.54
April 6790.76 27-APR-09:10 1654.44 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 10.91
May 10335.23 14-MAY-10:23 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 90.24
June 12374.51 25-JUN-08:62 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 78.19
July 14418.06 30-JUL-09:12 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 0.00 50.38
August 13288.98 13-AUG-09:02 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 78.03
September 13470.85 10-SEP-09:22 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 52.54
October 4886.95 04-OCT-09:20 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 19.81
November 853.72 02-NOV-10:40 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 28.03
December 696.17 05-DEC-10:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 35.67
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 696.17   169.56 69.83 908.57 0.00 0.00 0.00 0.00 0.00 8.10
Maximum of Months 14418.06   1654.44 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 90.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6823.43 20-JAN-13:30 1272.23 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 14.18
February 8997.67 27-FEB-14:30 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 13.16
March 10200.60 01-MAR-13:35 2544.47 992.69 2870.47 0.00 0.00 0.00 0.00 0.00 30.92
April 12120.98 27-APR-13:05 2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 7.08 0.00
May 19530.11 14-MAY-15:02 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 109.36
June 10750.92 25-JUN-13:23 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 85.03
July 20415.85 30-JUL-11:52 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 23.49
August 19467.08 13-AUG-13:02 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 6.38
September 21361.29 10-SEP-12:02 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 79.79
October 20189.24 08-OCT-13:32 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 113.32
November 9418.60 04-NOV-13:30 275.09 165.44 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
December 6970.43 05-DEC-12:30 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 0.00 37.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6823.43   200.88 82.72 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21361.29   2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 7.08 113.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 792.99 20-JAN-15:50 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 33.12
February 3637.83 27-FEB-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 7.77
March 5342.15 14-MAR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 9.99
April 8288.79 26-APR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.73 0.00
May 15720.52 14-MAY-15:41 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 89.72
June 13189.20 18-JUN-17:02 0.00 87.28 1222.09 0.00 0.00 0.00 0.00 0.00 138.05
July 15595.88 30-JUL-17:51 0.00 139.64 1955.35 0.00 0.00 0.00 0.00 0.00 18.91
August 15071.36 06-AUG-16:42 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 52.15
September 15914.83 10-SEP-16:41 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 44.99
October 6730.77 04-OCT-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 10.42
November 2844.55 04-NOV-15:30 84.78 52.37 353.33 0.00 0.00 0.00 0.00 0.00 2.52
December 984.24 05-DEC-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 32.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 792.99   0.00 52.37 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15914.83   805.38 314.21 2119.99 0.00 0.00 0.00 0.00 0.73 138.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 989.47 11-JAN-16:20 1272.23 964.06 1435.25 0.00 0.00 0.00 0.00 0.00 26.28
February 1193.94 28-FEB-14:20 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 10.05
March 1238.95 10-MAR-14:50 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 16.63
April 2710.20 27-APR-16:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 6.99 0.00
May 3176.98 05-MAY-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 1.08 0.00
June 3901.26 21-JUN-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 1.27 0.00
July 4890.93 24-JUL-06:03 1071.35 661.80 2551.55 0.00 0.00 0.00 0.00 0.00 7.82
August 4466.03 09-AUG-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 12.88 0.00
September 3358.73 12-SEP-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.67 0.00
October 2123.50 04-OCT-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 7.31
November 1264.79 06-NOV-12:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 27.38
December 980.28 14-DEC-13:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 84.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 980.28   1071.35 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4890.93   1306.65 964.06 2551.55 0.00 0.00 0.00 0.00 12.88 84.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 715.65 05-JAN-09:00 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 17.76
February 797.96 27-FEB-15:40 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 3.58
March 1691.41 14-MAR-10:00 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 11.18
April 5104.60 27-APR-09:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 5.39
May 8604.73 15-MAY-06:02 1017.38 628.46 2422.86 0.00 0.00 0.00 0.00 0.00 8.06
June 8708.61 19-JUN-06:02 1017.38 628.46 2422.86 0.00 0.00 0.00 0.00 0.00 22.71
July 9679.98 23-JUL-08:42 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 0.00 53.79
August 11483.94 13-AUG-09:32 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 0.00 32.78
September 7092.62 10-SEP-07:43 127.17 52.37 908.57 0.00 0.00 0.00 0.00 0.00 0.00
October 4135.43 04-OCT-08:30 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 11.51
November 987.59 02-NOV-10:30 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 15.96
December 751.10 05-DEC-10:30 827.22 314.23 908.57 0.00 0.00 0.00 0.00 0.00 19.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 715.65   127.17 52.37 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11483.94   1017.38 628.46 2422.86 0.00 0.00 0.00 0.00 0.00 53.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2013.26 20-JAN-13:30 1272.23 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 1954.97
February 5411.93 27-FEB-15:00 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 431.29
March 7540.01 02-MAR-13:07 7633.40 2978.07 8611.42 0.00 0.00 0.00 0.00 0.00 1285.45
April 9334.72 27-APR-13:40 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 221.82 0.00
May 8674.11 14-MAY-13:32 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 70.63
June 7193.27 28-JUN-13:30 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 75.22 0.00
July 10999.94 31-JUL-16:10 401.76 275.75 797.35 0.00 0.00 0.00 0.00 3809.74 0.00
August 16934.41 13-AUG-12:52 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 10.69
September 16269.06 10-SEP-15:43 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 28.69
October 11342.32 04-OCT-13:30 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 339.37
November 6973.80 04-NOV-13:40 137.54 82.72 558.15 0.00 0.00 0.00 0.00 0.00 0.00
December 4236.03 05-DEC-12:00 1272.23 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 1557.24
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2013.26   137.54 82.72 558.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16934.41   7633.40 2978.07 8611.42 0.00 0.00 0.00 0.00 3809.74 1954.97



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 738.68 20-JAN-15:50 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 17.05
February 2308.01 27-FEB-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 4.18
March 3128.21 02-MAR-16:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 6.14
April 5938.90 26-APR-17:30 84.78 104.74 403.81 0.00 0.00 0.00 0.00 0.00 0.52
May 12791.22 07-MAY-17:21 0.00 122.19 1710.93 0.00 0.00 0.00 0.00 0.00 37.17
June 7562.62 25-JUN-18:03 0.00 69.82 977.67 0.00 0.00 0.00 0.00 0.00 42.90
July 12691.24 23-JUL-18:01 0.00 139.64 1955.35 0.00 0.00 0.00 0.00 0.00 11.77
August 12968.28 06-AUG-18:32 0.00 104.73 1466.51 0.00 0.00 0.00 0.00 0.00 36.04
September 11671.08 10-SEP-17:42 0.00 69.82 977.67 0.00 0.00 0.00 0.00 0.00 19.11
October 5937.01 04-OCT-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 5.44
November 2394.64 04-NOV-15:30 84.78 52.37 353.33 0.00 0.00 0.00 0.00 0.00 1.32
December 849.93 05-DEC-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 17.27
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 738.68   0.00 52.37 353.33 0.00 0.00 0.00 0.00 0.00 0.52
Maximum of Months 12968.28   805.38 314.21 1955.35 0.00 0.00 0.00 0.00 0.00 42.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1067.15 11-JAN-16:20 1272.23 966.89 1435.25 0.00 0.00 0.00 0.00 0.00 43.76
February 1320.56 28-FEB-15:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
March 1452.75 10-MAR-14:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 30.69
April 4132.24 27-APR-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 10.86 0.00
May 4456.88 15-MAY-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.05
June 4787.17 21-JUN-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 1.91 0.00
July 7053.20 24-JUL-06:03 1071.35 661.80 2551.55 0.00 0.00 0.00 0.00 0.00 13.03
August 6803.41 14-AUG-06:02 1339.19 827.25 3189.44 0.00 0.00 0.00 0.00 0.00 19.75
September 4117.97 12-SEP-14:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.98 0.00
October 2762.54 04-OCT-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 11.12
November 1281.79 02-NOV-14:10 2544.47 992.69 2870.49 0.00 0.00 0.00 0.00 0.00 24.62
December 1023.22 05-DEC-15:20 1272.23 728.58 1435.25 0.00 0.00 0.00 0.00 0.00 34.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1023.22   1071.35 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7053.20   2544.47 992.69 3189.44 0.00 0.00 0.00 0.00 10.86 43.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 738.53 06-JAN-09:30 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 0.00
February 2271.91 27-FEB-15:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 6.19
March 5759.01 01-MAR-13:01 5638.00 2199.59 6360.01 0.00 0.00 0.00 0.00 0.00 19.93
April 7483.17 27-APR-10:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 6.73
May 12054.46 14-MAY-07:53 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 104.77
June 11247.59 25-JUN-10:23 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 63.94
July 13326.73 30-JUL-08:42 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 39.25
August 14452.68 13-AUG-08:12 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 0.00 84.16
September 11613.30 10-SEP-10:13 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 39.42
October 6024.50 04-OCT-10:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 13.11
November 4219.32 02-NOV-12:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 16.70
December 805.02 05-DEC-11:10 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 19.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 738.53   169.56 69.83 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14452.68   5638.00 2199.59 6360.01 0.00 0.00 0.00 0.00 0.00 104.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7326.19 20-JAN-13:12 6361.16 2481.72 7176.19 0.00 0.00 0.00 0.00 0.00 7.86
February 9148.82 27-FEB-14:10 1306.65 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 12.19
March 10560.37 01-MAR-13:30 2544.47 992.69 2870.47 0.00 0.00 0.00 0.00 0.00 27.03
April 11676.62 02-APR-13:13 200.88 82.72 1435.24 0.00 0.00 0.00 0.00 0.00 131.44
May 18230.10 14-MAY-13:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 123.96
June 14409.13 11-JUN-13:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 61.00
July 15934.47 23-JUL-14:32 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 12.90 0.00
August 19704.87 13-AUG-12:52 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 24.62
September 18631.10 10-SEP-12:52 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 69.58
October 13640.78 04-OCT-12:50 1272.23 496.34 1435.24 0.00 0.00 0.00 0.00 0.00 12.50
November 9543.99 04-NOV-13:30 275.09 165.44 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
December 7942.13 05-DEC-12:30 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 0.00 31.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7326.19   200.88 82.72 1116.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19704.87   6361.16 2481.72 7176.19 0.00 0.00 0.00 0.00 12.90 131.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 819.91 20-JAN-15:50 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 27.95
February 3741.77 27-FEB-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 6.43
March 5250.05 14-MAR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 8.29
April 8026.26 26-APR-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.66 0.00
May 15139.28 07-MAY-16:41 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 63.88
June 14535.62 18-JUN-16:52 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 130.17
July 14296.98 30-JUL-18:01 0.00 122.19 1710.93 0.00 0.00 0.00 0.00 0.00 16.34
August 14672.82 06-AUG-18:22 0.00 104.73 1466.51 0.00 0.00 0.00 0.00 0.00 55.61
September 13348.76 10-SEP-16:12 211.94 87.28 1514.28 0.00 0.00 0.00 0.00 0.00 28.12
October 6687.43 04-OCT-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 8.60
November 2970.17 04-NOV-15:30 84.78 52.37 353.33 0.00 0.00 0.00 0.00 0.00 2.09
December 1321.47 05-DEC-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 26.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 819.91   0.00 52.37 353.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15139.28   805.38 314.21 2119.99 0.00 0.00 0.00 0.00 0.66 130.17



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.981934E+11 81477.08 13-JAN-16:49 0.741803E+11 174322.99 17-JAN-07:19
February 0.876421E+11 80265.56 27-FEB-15:09 0.413501E+11 166800.46 21-FEB-07:19
March 0.100024E+12 78011.66 14-MAR-15:00 0.169904E+11 101877.81 01-MAR-07:10
April 0.952830E+11 121700.57 27-APR-15:09 0.659458E+10 80716.45 19-APR-06:10
May 0.103502E+12 116669.63 15-MAY-15:20 0.208619E+10 47032.77 18-MAY-06:10
June 0.107452E+12 122219.03 28-JUN-15:39 0.520036E+09 18947.60 15-JUN-06:10
July 0.115873E+12 144206.19 31-JUL-15:09 86991631.25 8133.01 13-JUL-06:19
August 0.129635E+12 146002.71 10-AUG-15:20 0.124710E+09 14595.83 03-AUG-06:19
September 0.103892E+12 122936.54 12-SEP-15:20 0.615135E+09 32237.25 28-SEP-06:10
October 0.980517E+11 103202.80 04-OCT-15:20 0.489338E+10 67831.74 16-OCT-06:10
November 0.953444E+11 81592.31 06-NOV-16:49 0.301708E+11 133814.00 24-NOV-07:10
December 0.966017E+11 81581.04 06-DEC-16:19 0.583706E+11 184170.64 26-DEC-07:19
             
Annual Sum or Average 0.123150E+13     0.235983E+12    
Minimum of Months 0.876421E+11 78011.66   86991631.25 8133.01  
Maximum of Months 0.129635E+12 146002.71   0.741803E+11 184170.64  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.203678E+11 0.628818E+10 0.605851E+11 0.225730E+10 0.348918E+10 0.375839E+09 0.00 393395.59 0.00 0.00 0.00 0.482959E+10 0.00
February 0.179483E+11 0.491554E+10 0.548702E+11 0.204820E+10 0.308666E+10 0.218963E+09 0.00 0.143047E+09 0.00 0.00 0.00 0.441110E+10 0.00
March 0.209041E+11 0.442863E+10 0.627783E+11 0.235488E+10 0.399625E+10 98583079.83 0.00 0.316829E+09 0.00 0.00 0.00 0.514662E+10 0.00
April 0.184074E+11 0.340219E+10 0.586172E+11 0.219172E+10 0.496088E+10 46593451.78 0.00 0.313095E+10 0.00 0.00 0.00 0.452604E+10 0.00
May 0.197496E+11 0.290318E+10 0.616817E+11 0.230561E+10 0.700303E+10 24546461.97 0.00 0.515706E+10 0.00 0.00 0.00 0.467742E+10 0.00
June 0.195722E+11 0.254241E+10 0.604966E+11 0.226779E+10 0.868723E+10 15941530.66 0.00 0.939217E+10 0.00 0.00 0.00 0.447766E+10 0.00
July 0.183254E+11 0.273940E+10 0.597911E+11 0.222857E+10 0.109673E+11 12758274.74 0.00 0.176800E+11 0.00 0.00 0.00 0.412888E+10 0.00
August 0.205063E+11 0.320959E+10 0.627783E+11 0.235451E+10 0.125773E+11 13595439.59 0.00 0.236892E+11 0.00 0.00 0.00 0.450660E+10 0.00
September 0.185536E+11 0.386004E+10 0.585950E+11 0.219058E+10 0.794615E+10 15987927.51 0.00 0.860696E+10 0.00 0.00 0.00 0.412372E+10 0.00
October 0.196323E+11 0.500879E+10 0.605962E+11 0.225785E+10 0.477795E+10 37605655.01 0.00 0.135507E+10 0.00 0.00 0.00 0.438590E+10 0.00
November 0.200207E+11 0.580107E+10 0.591197E+11 0.220000E+10 0.332318E+10 0.158813E+09 0.00 0.247777E+09 0.00 0.00 0.00 0.447313E+10 0.00
December 0.198945E+11 0.653724E+10 0.597800E+11 0.222861E+10 0.327351E+10 0.294596E+09 0.00 1851434.03 0.00 0.00 0.00 0.459138E+10 0.00
                           
Annual Sum or Average 0.233882E+12 0.516363E+11 0.719689E+12 0.268856E+11 0.740886E+11 0.131382E+10 0.00 0.697212E+11 0.00 0.00 0.00 0.542780E+11 0.00
Minimum of Months 0.179483E+11 0.254241E+10 0.548702E+11 0.204820E+10 0.308666E+10 12758274.74 0.00 393395.59 0.00 0.00 0.00 0.412372E+10 0.00
Maximum of Months 0.209041E+11 0.653724E+10 0.627783E+11 0.235488E+10 0.125773E+11 0.375839E+09 0.00 0.236892E+11 0.00 0.00 0.00 0.514662E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.741803E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.413501E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.169904E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.659458E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 0.208619E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.520036E+09 0.00 0.00 0.00 0.00
July 0.00 0.00 86991631.25 0.00 0.00 0.00 0.00
August 0.00 0.00 0.124710E+09 0.00 0.00 0.00 0.00
September 0.00 0.00 0.615135E+09 0.00 0.00 0.00 0.00
October 0.00 0.00 0.489338E+10 0.00 0.00 0.00 0.00
November 0.00 0.00 0.301708E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.583706E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.235983E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 86991631.25 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.741803E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 25003.79 02-JAN-16:30 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 02-JAN-08:09 7625.96 02-JAN-06:30 548.81 09-JAN-07:49 0.00 01-JAN-00:10
February 23928.11 02-FEB-16:00 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 02-FEB-08:09 5953.31 21-FEB-07:10 537.74 21-FEB-07:00 0.00 01-FEB-00:10
March 22850.42 22-MAR-07:10 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 02-MAR-12:09 5706.79 02-MAR-15:09 443.71 06-MAR-07:10 0.00 01-MAR-00:10
April 20891.34 03-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 03-APR-11:09 19294.33 27-APR-14:30 356.41 19-APR-06:10 0.00 01-APR-00:10
May 20047.80 17-MAY-07:10 3328.83 01-MAY-19:19 41699.26 01-MAY-07:10 1410.29 01-MAY-11:09 21096.46 15-MAY-14:30 225.48 18-MAY-06:10 0.00 01-MAY-00:10
June 19864.35 29-JUN-07:10 3328.83 01-JUN-19:00 41699.26 01-JUN-07:10 1410.29 06-JUN-16:10 19862.33 28-JUN-15:20 106.90 15-JUN-06:10 0.00 01-JUN-00:10
July 20633.80 12-JUL-08:20 3328.83 01-JUL-20:10 41699.26 03-JUL-07:10 1410.29 12-JUL-11:09 28025.63 31-JUL-15:09 55.90 13-JUL-06:19 0.00 01-JUL-00:10
August 20471.70 28-AUG-07:30 5686.19 16-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-11:09 27911.00 14-AUG-15:20 88.90 18-AUG-06:19 0.00 01-AUG-00:10
September 22922.38 25-SEP-07:10 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 01-SEP-11:09 23292.44 11-SEP-15:30 152.69 28-SEP-06:10 0.00 01-SEP-00:10
October 24860.84 31-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 10-OCT-16:10 16215.22 04-OCT-15:39 301.95 16-OCT-06:10 0.00 01-OCT-00:10
November 25003.79 06-NOV-16:49 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 02-NOV-11:09 4206.25 24-NOV-07:10 489.23 24-NOV-07:19 0.00 01-NOV-00:10
December 25003.79 01-DEC-16:19 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 04-DEC-12:09 6576.16 26-DEC-07:10 552.05 26-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 19864.35   3328.83   41699.26   1410.29   4206.25   55.90   0.00  
Maximum of Months 25003.79   5686.19   41699.26   1410.29   28025.63   552.05   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 288.38 02-JAN-10:30 0.00 0.00 0.00 6449.73 25-JAN-12:39 0.00
February 8959.71 27-FEB-15:09 0.00 0.00 0.00 6514.69 10-FEB-12:50 0.00
March 7944.05 18-MAR-15:00 0.00 0.00 0.00 6438.04 01-MAR-12:20 0.00
April 36030.71 27-APR-14:00 0.00 0.00 0.00 6250.82 03-APR-11:20 0.00
May 29143.87 04-MAY-14:00 0.00 0.00 0.00 6200.04 01-MAY-11:50 0.00
June 35237.25 28-JUN-15:20 0.00 0.00 0.00 5815.83 01-JUN-11:50 0.00
July 50977.60 24-JUL-14:00 0.00 0.00 0.00 5765.13 05-JUL-11:00 0.00
August 52760.88 29-AUG-15:30 0.00 0.00 0.00 5694.33 29-AUG-11:30 0.00
September 34329.63 12-SEP-15:00 0.00 0.00 0.00 5776.61 29-SEP-11:30 0.00
October 20559.51 04-OCT-14:00 0.00 0.00 0.00 5828.87 31-OCT-11:20 0.00
November 12689.83 04-NOV-14:09 0.00 0.00 0.00 6212.28 30-NOV-12:30 0.00
December 931.80 05-DEC-11:00 0.00 0.00 0.00 6261.77 29-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 288.38   0.00 0.00 0.00 5694.33   0.00
Maximum of Months 52760.88   0.00 0.00 0.00 6514.69   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 81477.08 13-JAN-16:49 25003.79 41670.51 5686.19 1410.29 2449.55 274.59 0.00 0.00 0.00
February 80265.56 27-FEB-15:09 19671.42 41659.26 0.00 1410.29 4694.35 6.85 0.00 8959.71 0.00
March 78011.66 14-MAR-15:00 19671.42 41670.51 0.00 1410.29 5400.13 6.85 0.00 4871.67 0.00
April 121700.57 27-APR-15:09 19671.42 41670.51 0.00 1410.29 18491.75 6.85 0.00 35839.50 0.00
May 116669.63 15-MAY-15:20 19671.42 41670.51 0.00 1410.29 20844.84 6.85 0.00 28496.46 0.00
June 122219.03 28-JUN-15:39 19671.42 41670.51 0.00 1410.29 19755.08 6.85 0.00 35173.66 0.00
July 144206.19 31-JUL-15:09 19671.42 41670.51 0.00 1410.29 28025.63 6.90 0.00 49189.50 0.00
August 146002.71 10-AUG-15:20 19671.42 41670.51 0.00 1410.29 26940.71 6.90 0.00 52126.51 0.00
September 122936.54 12-SEP-15:20 19671.42 41670.51 0.00 1410.29 22166.83 6.90 0.00 33754.61 0.00
October 103202.80 04-OCT-15:20 19671.42 41670.51 0.00 1410.29 15963.78 6.85 0.00 19904.50 0.00
November 81592.31 06-NOV-16:49 25003.79 41670.51 5686.19 1410.29 3206.61 6.85 0.00 0.00 0.00
December 81581.04 06-DEC-16:19 25003.79 41670.51 5686.19 1410.29 2660.90 199.71 0.00 0.00 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 78011.66   19671.42 41659.26 0.00 1410.29 2449.55 6.85 0.00 0.00 0.00
Maximum of Months 146002.71   25003.79 41670.51 5686.19 1410.29 28025.63 274.59 0.00 52126.51 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 174322.99 17-JAN-07:19 0.00 0.00 0.00
February 0.00 0.00 166800.46 21-FEB-07:19 0.00 0.00 0.00
March 0.00 0.00 101877.81 01-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 80716.45 19-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 47032.77 18-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 18947.60 15-JUN-06:10 0.00 0.00 0.00
July 0.00 0.00 8133.01 13-JUL-06:19 0.00 0.00 0.00
August 0.00 0.00 14595.83 03-AUG-06:19 0.00 0.00 0.00
September 0.00 0.00 32237.25 28-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 67831.74 16-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 133814.00 24-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 184170.64 26-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 8133.01   0.00 0.00 0.00
Maximum of Months 0.00 0.00 184170.64   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 19.58 2.33 19.58 0.00 19.58 0.00 19.58
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.33 19.58 2.33 19.58 0.00 19.58 0.00 19.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.58 2.33 19.58 0.00 19.58 0.00 19.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 19.22 3.33 19.22 0.00 19.22 0.00 19.22
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.33 19.22 3.33 19.22 0.00 19.22 0.00 19.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.33 19.22 3.33 19.22 0.00 19.22 0.00 19.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 19.27 4.00 19.27 0.00 19.27 0.00 19.27
February 0.67 18.74 0.50 18.98 0.00 18.98 0.00 18.98
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 19.57 1.17 19.57 0.00 19.57 0.00 19.57
                 
Annual Sum or Average 5.83 19.27 5.67 19.30 0.00 19.30 0.00 19.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 19.57 4.00 19.57 0.00 19.57 0.00 19.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 10.67 18.73 9.33 18.90 0.00 18.90 0.00 18.90
February 4.17 18.51 3.67 18.72 0.00 18.72 0.00 18.72
March 0.17 19.27 0.17 19.27 0.00 19.27 0.00 19.27
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 19.11 0.50 19.11 0.00 19.11 0.00 19.11
December 5.33 19.19 5.00 19.26 0.00 19.26 0.00 19.26
                 
Annual Sum or Average 20.83 18.82 18.67 18.97 0.00 18.97 0.00 18.97
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.67 19.27 9.33 19.27 0.00 19.27 0.00 19.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.17 18.46 4.00 18.75 0.00 18.75 0.00 18.75
February 1.33 17.67 1.00 18.02 0.00 18.02 0.00 18.02
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.17 27.70 1.17 27.70
June 0.00 0.00 0.00 0.00 2.33 27.61 2.33 27.61
July 0.00 0.00 0.00 0.00 5.00 27.81 5.00 27.81
August 0.00 0.00 0.00 0.00 3.83 27.91 3.83 27.91
September 0.00 0.00 0.00 0.00 1.17 27.71 1.17 27.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.08 0.17 19.08 0.00 19.08 0.00 19.08
December 2.50 18.98 2.17 19.20 0.00 19.20 0.00 19.20
                 
Annual Sum or Average 9.17 18.50 7.33 18.78 13.50 22.83 13.50 24.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.17 19.08 4.00 19.20 5.00 27.91 5.00 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 19.15 3.50 19.33 0.00 19.33 0.00 19.33
February 0.83 18.54 0.67 18.88 0.00 18.88 0.00 18.88
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.56 0.83 27.56
May 0.00 0.00 0.00 0.00 2.83 27.64 2.83 27.64
June 0.00 0.00 0.00 0.00 2.67 27.48 2.67 27.48
July 0.00 0.00 0.00 0.00 4.17 27.82 3.83 27.84
August 0.00 0.00 0.00 0.00 3.50 28.00 3.33 28.02
September 0.00 0.00 0.00 0.00 1.83 28.23 1.67 28.27
October 0.00 0.00 0.00 0.00 0.67 27.66 0.67 27.66
November 0.17 19.13 0.17 19.13 0.00 19.13 0.00 19.13
December 1.67 19.23 1.50 19.36 0.00 19.36 0.00 19.36
                 
Annual Sum or Average 6.67 19.09 5.83 19.28 16.50 24.13 15.83 25.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 19.23 3.50 19.36 4.17 28.23 3.83 28.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.33 18.45 3.50 18.73 0.00 18.73 0.00 18.73
February 1.17 18.12 0.83 18.60 0.00 18.60 0.00 18.60
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.42 0.50 27.42
May 0.00 0.00 0.00 0.00 5.50 28.10 3.17 28.12
June 0.00 0.00 0.00 0.00 3.67 27.83 2.33 27.82
July 0.00 0.00 0.00 0.00 6.17 28.29 3.33 28.26
August 0.00 0.00 0.00 0.00 3.83 28.27 2.00 28.31
September 0.00 0.00 0.00 0.00 2.83 27.80 2.33 27.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 19.13 0.17 19.13 0.00 19.13 0.00 19.13
December 2.00 18.90 1.67 19.18 0.00 19.18 0.00 19.18
                 
Annual Sum or Average 7.67 18.53 6.17 18.84 22.50 24.57 13.67 25.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.33 19.13 3.50 19.18 6.17 28.29 3.33 28.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.83 19.38 4.83 19.38 0.00 19.38 0.00 19.38
February 0.17 19.17 0.17 19.17 0.00 19.17 0.00 19.17
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.75 0.33 19.75 0.00 19.75 0.00 19.75
                 
Annual Sum or Average 5.33 19.40 5.33 19.40 0.00 19.40 0.00 19.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.83 19.75 4.83 19.75 0.00 19.75 0.00 19.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 19.18 3.00 19.29 0.00 19.29 0.00 19.29
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.83 27.41 0.83 27.41
June 0.00 0.00 0.00 0.00 0.83 27.52 0.83 27.52
July 0.00 0.00 0.00 0.00 2.83 27.68 2.83 27.68
August 0.00 0.00 0.00 0.00 3.83 27.58 3.83 27.58
September 0.00 0.00 0.00 0.00 1.17 27.50 1.17 27.50
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.35 0.17 19.35 0.00 19.35 0.00 19.35
                 
Annual Sum or Average 3.33 19.19 3.17 19.30 9.50 24.22 9.50 25.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.35 3.00 19.35 3.83 27.68 3.83 27.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 72.50 18.36 72.50 18.36 0.00 18.36 0.00 18.36
February 42.33 18.57 42.33 18.57 0.00 18.57 0.00 18.57
March 35.17 19.21 35.17 19.21 0.00 19.21 0.00 19.21
April 17.67 19.31 17.67 19.31 0.00 19.31 0.00 19.31
May 7.17 19.90 7.17 19.90 0.83 20.31 0.83 20.68
June 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
July 0.00 0.00 0.00 0.00 2.17 27.54 2.17 27.54
August 0.00 0.00 0.00 0.00 2.83 27.66 2.83 27.66
September 2.00 20.06 2.00 20.06 2.00 22.66 1.83 23.89
October 13.50 19.98 13.50 19.98 0.67 20.16 0.67 20.33
November 42.17 19.09 42.17 19.09 0.00 19.09 0.00 19.09
December 61.33 18.57 61.33 18.57 0.00 18.57 0.00 18.57
                 
Annual Sum or Average 293.83 18.82 293.83 18.82 8.67 18.95 8.50 19.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.36 0.00 18.36
Maximum of Months 72.50 20.06 72.50 20.06 2.83 27.66 2.83 27.66



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.17 18.97 2.83 19.19 0.00 19.19 0.00 19.19
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 3.67 27.69 1.83 27.68
June 0.00 0.00 0.00 0.00 1.67 27.61 0.67 27.60
July 0.00 0.00 0.00 0.00 4.50 28.02 2.00 27.99
August 0.00 0.00 0.00 0.00 3.50 27.88 1.67 27.87
September 0.00 0.00 0.00 0.00 2.00 27.60 1.67 27.59
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.36 0.17 19.36 0.00 19.36 0.00 19.36
                 
Annual Sum or Average 3.33 18.99 3.00 19.20 15.33 25.29 7.83 25.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.36 2.83 19.36 4.50 28.02 2.00 27.99



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.00 19.33 4.00 19.33 0.00 19.33 0.00 19.33
February 0.17 19.22 0.17 19.22 0.00 19.22 0.00 19.22
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 19.76 1.00 19.76 0.00 19.76 0.00 19.76
                 
Annual Sum or Average 5.17 19.41 5.17 19.41 0.00 19.41 0.00 19.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.00 19.76 4.00 19.76 0.00 19.76 0.00 19.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.32 2.00 19.40 0.00 19.40 0.00 19.40
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.17 27.84 1.17 27.84
June 0.00 0.00 0.00 0.00 2.50 27.69 2.50 27.69
July 0.00 0.00 0.00 0.00 3.50 28.03 3.50 28.03
August 0.00 0.00 0.00 0.00 3.83 27.91 3.83 27.91
September 0.00 0.00 0.00 0.00 1.50 27.78 1.50 27.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.90 0.33 19.90 0.00 19.90 0.00 19.90
                 
Annual Sum or Average 2.50 19.40 2.33 19.47 12.50 25.53 12.50 26.52
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.90 2.00 19.90 3.83 28.03 3.83 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.42 2.17 19.42 0.00 19.42 0.00 19.42
February 0.00 0.00 0.00 0.00 0.33 27.27 0.33 27.27
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 27.48 1.17 27.48
May 0.00 0.00 0.00 0.00 2.67 27.57 2.67 27.57
June 0.00 0.00 0.00 0.00 1.83 27.46 1.83 27.46
July 0.00 0.00 0.00 0.00 3.50 27.77 3.50 27.77
August 0.00 0.00 0.00 0.00 3.50 27.89 3.50 27.89
September 0.00 0.00 0.00 0.00 2.33 28.00 2.33 28.00
October 0.00 0.00 0.00 0.00 1.00 27.70 1.00 27.70
November 0.00 0.00 0.00 0.00 0.33 27.36 0.33 27.36
December 0.17 19.36 0.17 19.36 0.17 21.99 0.17 23.31
                 
Annual Sum or Average 2.33 19.42 2.33 19.42 16.83 25.91 16.83 26.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.17 19.42 2.17 19.42 3.50 28.00 3.50 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 19.39 2.17 19.47 0.00 19.47 0.00 19.47
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 27.41 0.33 27.41
May 0.00 0.00 0.00 0.00 5.50 28.00 3.00 28.02
June 0.00 0.00 0.00 0.00 3.00 27.84 2.00 27.82
July 0.00 0.00 0.00 0.00 5.83 28.19 3.17 28.15
August 0.00 0.00 0.00 0.00 3.67 28.17 2.00 28.20
September 0.00 0.00 0.00 0.00 3.00 27.76 2.50 27.75
October 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.90 0.33 19.90 0.00 19.90 0.00 19.90
                 
Annual Sum or Average 2.67 19.45 2.50 19.52 21.50 26.37 13.17 26.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.90 2.17 19.90 5.83 28.19 3.17 28.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 23.07 32.00 22.88 32.00 22.70
February 406.33 23.75 0.00 23.75 0.00 23.75
March 259.67 24.02 12.50 24.08 0.00 24.08
April 70.33 24.01 107.67 24.78 0.00 24.78
May 0.00 0.00 210.17 24.91 0.00 24.91
June 0.00 0.00 265.50 24.77 0.00 24.77
July 0.00 0.00 400.67 24.66 0.00 24.66
August 0.00 0.00 467.00 24.49 0.00 24.49
September 0.00 0.00 344.83 24.69 0.00 24.69
October 20.67 24.00 114.33 25.28 0.00 25.28
November 269.00 23.88 37.50 24.03 0.00 24.03
December 491.67 23.69 0.00 23.69 0.00 23.69
             
Annual Sum or Average 2019.67 23.63 1992.17 24.15 32.00 24.12
Minimum of Months 0.00 0.00 0.00 22.88 0.00 22.70
Maximum of Months 502.00 24.02 467.00 25.28 32.00 25.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.42 110.50 21.19 110.50 21.03
February 450.00 22.18 34.83 22.07 34.83 21.97
March 503.17 23.24 0.00 23.24 0.00 23.24
April 322.33 23.56 29.50 23.67 0.00 23.67
May 136.33 23.72 70.00 24.01 0.00 24.01
June 22.67 23.75 132.67 24.49 0.00 24.49
July 0.67 23.69 289.67 24.45 0.00 24.45
August 6.00 23.68 366.00 24.33 0.00 24.33
September 43.33 23.51 198.50 24.32 0.00 24.32
October 307.33 23.32 14.83 23.40 0.00 23.40
November 446.17 22.54 1.00 22.54 1.00 22.53
December 497.00 21.89 25.67 21.82 25.67 21.75
             
Annual Sum or Average 3237.00 22.57 1273.17 22.95 172.00 22.85
Minimum of Months 0.67 21.42 0.00 21.19 0.00 21.03
Maximum of Months 503.17 23.75 366.00 24.49 110.50 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.74 240.17 20.48 240.17 20.35
February 451.67 21.36 132.67 21.10 132.67 20.93
March 510.83 22.47 24.17 22.39 24.17 22.31
April 376.50 23.06 19.67 23.13 0.00 23.13
May 224.33 23.39 51.17 23.57 0.00 23.57
June 94.00 23.54 95.83 23.97 0.00 23.97
July 41.50 23.62 255.00 24.24 0.00 24.24
August 41.00 23.49 308.83 24.17 0.00 24.17
September 158.00 23.33 120.33 23.73 0.00 23.73
October 429.67 22.79 0.67 22.79 0.00 22.79
November 488.50 21.76 72.50 21.57 72.50 21.42
December 497.00 21.03 187.00 20.81 187.00 20.68
             
Annual Sum or Average 3815.00 22.07 1508.00 22.19 656.50 21.96
Minimum of Months 41.00 20.74 0.67 20.48 0.00 20.35
Maximum of Months 510.83 23.62 308.83 24.24 240.17 24.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.08 395.33 19.96 395.33 19.92
February 454.00 20.53 260.00 20.31 260.00 20.21
March 513.33 21.45 124.00 21.22 124.00 21.06
April 416.50 22.32 48.00 22.27 30.17 22.16
May 280.00 22.81 58.50 23.05 1.00 23.04
June 155.83 23.22 103.83 23.66 0.00 23.66
July 101.83 23.37 255.83 24.02 0.00 24.02
August 119.33 23.29 281.67 23.93 0.00 23.93
September 266.17 22.80 87.83 23.15 0.00 23.15
October 477.33 21.90 41.50 21.76 41.50 21.64
November 489.00 20.82 218.17 20.57 218.17 20.44
December 497.00 20.27 372.17 20.16 372.17 20.11
             
Annual Sum or Average 4272.33 21.45 2246.83 21.47 1442.33 21.20
Minimum of Months 101.83 20.08 41.50 19.96 0.00 19.92
Maximum of Months 513.33 23.37 395.33 24.02 395.33 24.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.13 363.67 19.98 363.67 19.92
February 454.00 20.83 226.17 20.56 226.17 20.42
March 498.17 21.86 88.33 21.59 88.33 21.39
April 301.50 22.43 82.33 22.64 19.17 22.53
May 209.83 22.85 147.17 23.51 4.50 23.53
June 108.67 23.44 231.00 24.13 6.50 24.19
July 89.83 24.16 333.33 24.38 18.50 24.49
August 86.33 23.96 360.50 24.25 15.00 24.34
September 206.00 22.87 174.83 23.56 3.83 23.59
October 400.67 21.97 55.83 21.94 35.33 21.81
November 487.83 20.96 188.33 20.68 188.33 20.52
December 497.00 20.34 336.17 20.19 336.17 20.12
             
Annual Sum or Average 3841.83 21.51 2587.67 21.80 1305.50 21.53
Minimum of Months 86.33 20.13 55.83 19.98 3.83 19.92
Maximum of Months 502.00 24.16 363.67 24.38 363.67 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.83 20.52 308.83 20.25 308.17 20.13
February 404.00 21.07 198.00 20.88 181.67 20.70
March 408.00 21.69 117.83 21.61 84.17 21.41
April 297.67 22.33 113.33 22.70 23.83 22.60
May 237.33 22.86 151.67 23.48 9.83 23.55
June 156.00 23.27 190.67 23.92 6.17 23.97
July 113.83 23.71 297.33 24.24 13.00 24.33
August 115.50 23.69 332.33 24.17 13.00 24.26
September 200.17 22.99 210.67 23.71 7.50 23.77
October 349.83 22.08 120.33 22.46 30.50 22.36
November 451.17 21.15 184.83 21.01 160.50 20.81
December 470.83 20.66 284.50 20.42 281.00 20.30
             
Annual Sum or Average 3701.17 21.69 2510.33 22.04 1119.33 21.77
Minimum of Months 113.83 20.52 113.33 20.25 6.17 20.13
Maximum of Months 496.83 23.71 332.33 24.24 308.17 24.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.17 372.33 20.01 372.33 19.95
February 443.83 20.75 233.33 20.49 232.50 20.36
March 472.33 21.56 116.33 21.36 107.33 21.19
April 342.17 22.25 89.67 22.46 28.83 22.36
May 247.33 22.95 138.00 23.50 14.50 23.61
June 150.17 23.33 196.67 23.94 8.17 24.01
July 108.17 23.87 317.00 24.30 16.17 24.40
August 110.83 23.62 327.50 24.15 11.00 24.22
September 220.33 23.00 175.33 23.62 10.83 23.71
October 424.17 21.93 69.33 21.96 38.17 21.83
November 480.83 20.91 197.33 20.67 194.17 20.52
December 497.00 20.39 338.83 20.22 338.83 20.15
             
Annual Sum or Average 3999.17 21.52 2571.67 21.77 1372.83 21.51
Minimum of Months 108.17 20.17 69.33 20.01 8.17 19.95
Maximum of Months 502.00 23.87 372.33 24.30 372.33 24.40



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.42 360.50 20.32 360.50 20.27
February 454.00 20.82 219.33 20.66 219.33 20.58
March 514.00 21.56 58.67 21.45 58.67 21.36
April 455.50 22.43 7.17 22.43 3.83 22.41
May 351.00 23.16 25.67 23.23 0.00 23.23
June 169.00 23.48 56.17 23.68 0.00 23.68
July 65.67 23.62 215.33 24.10 0.00 24.10
August 72.00 23.50 272.83 24.05 0.00 24.05
September 240.50 23.24 79.17 23.48 0.00 23.48
October 477.33 22.57 0.50 22.57 0.00 22.57
November 489.00 21.48 79.00 21.34 79.00 21.23
December 497.00 20.72 272.83 20.61 272.83 20.55
             
Annual Sum or Average 4287.00 21.81 1647.17 21.83 994.17 21.61
Minimum of Months 65.67 20.42 0.50 20.32 0.00 20.27
Maximum of Months 514.00 23.62 360.50 24.10 360.50 24.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.47 332.33 20.34 332.33 20.29
February 454.00 21.14 165.67 20.94 165.67 20.83
March 512.50 22.16 28.33 22.06 28.33 21.98
April 319.67 22.83 49.17 23.01 1.67 23.00
May 213.67 23.20 108.67 23.66 0.50 23.66
June 73.83 23.52 223.00 24.27 0.83 24.28
July 34.00 24.63 349.50 24.48 10.00 24.54
August 38.50 24.52 386.17 24.38 11.17 24.45
September 144.00 23.34 203.83 23.97 3.17 23.99
October 374.17 22.73 23.17 22.85 0.00 22.85
November 483.33 21.65 62.83 21.50 62.83 21.38
December 497.00 20.85 229.17 20.68 229.17 20.60
             
Annual Sum or Average 3646.67 21.85 2161.83 22.23 845.67 22.01
Minimum of Months 34.00 20.47 23.17 20.34 0.00 20.29
Maximum of Months 512.50 24.63 386.17 24.48 332.33 24.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.50 20.32 320.00 20.11 320.00 20.01
February 427.17 21.04 138.83 20.80 134.00 20.61
March 458.50 21.60 53.00 21.47 44.17 21.31
April 356.33 22.15 74.17 22.40 15.50 22.29
May 305.67 22.56 88.17 23.02 2.00 23.01
June 206.33 22.82 125.17 23.50 0.17 23.50
July 90.33 23.07 302.50 24.15 5.50 24.19
August 83.33 23.18 343.33 24.15 9.50 24.21
September 153.67 22.74 233.83 23.81 6.83 23.87
October 330.17 22.29 95.00 22.85 3.83 22.86
November 454.67 21.23 96.00 21.18 75.17 21.00
December 479.33 20.69 241.83 20.47 238.17 20.34
             
Annual Sum or Average 3844.00 21.58 2111.83 21.97 854.83 21.73
Minimum of Months 83.33 20.32 53.00 20.11 0.17 20.01
Maximum of Months 498.50 23.18 343.33 24.15 320.00 24.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.50 333.67 20.36 333.67 20.30
February 452.33 21.11 168.17 20.90 168.17 20.78
March 492.50 21.95 39.67 21.85 38.17 21.76
April 360.33 22.67 49.67 22.88 2.00 22.87
May 218.17 23.34 118.17 23.78 3.67 23.81
June 96.83 23.53 184.67 24.12 1.33 24.14
July 31.83 24.73 369.83 24.52 9.67 24.58
August 33.83 24.27 389.83 24.35 8.17 24.40
September 118.50 23.50 224.17 24.13 5.50 24.17
October 393.17 22.71 32.67 22.87 0.00 22.87
November 479.33 21.60 67.50 21.49 63.00 21.37
December 497.00 20.85 237.67 20.69 237.67 20.61
             
Annual Sum or Average 3675.83 21.83 2215.67 22.22 871.00 22.00
Minimum of Months 31.83 20.50 32.67 20.36 0.00 20.30
Maximum of Months 502.00 24.73 389.83 24.52 333.67 24.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.41 324.67 20.25 324.67 20.18
February 454.00 20.96 182.67 20.73 182.67 20.60
March 512.33 22.04 36.17 21.93 36.17 21.84
April 398.50 22.82 20.50 22.88 1.83 22.87
May 239.17 23.26 62.33 23.47 0.00 23.47
June 96.50 23.52 113.33 23.95 0.00 23.95
July 38.50 23.65 280.67 24.22 0.00 24.22
August 45.00 23.45 317.83 24.13 0.00 24.13
September 199.33 23.23 115.83 23.61 0.00 23.61
October 450.17 22.51 7.17 22.54 1.00 22.53
November 489.00 21.38 114.50 21.18 114.50 21.04
December 497.00 20.67 265.67 20.52 265.67 20.45
             
Annual Sum or Average 3921.50 21.79 1841.33 21.92 926.50 21.68
Minimum of Months 38.50 20.41 7.17 20.25 0.00 20.18
Maximum of Months 512.33 23.65 324.67 24.22 324.67 24.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.36 272.50 20.17 272.50 20.09
February 383.83 21.19 137.83 20.93 137.83 20.78
March 411.50 22.25 29.83 22.12 29.67 22.01
April 253.17 22.88 59.83 23.18 1.33 23.17
May 168.83 23.30 117.00 23.85 4.17 23.90
June 74.50 23.84 200.17 24.38 7.67 24.45
July 33.83 24.94 288.50 24.62 12.67 24.71
August 41.67 24.70 312.33 24.47 14.50 24.57
September 145.83 23.36 163.33 23.96 5.00 24.01
October 327.00 22.51 26.00 22.66 1.00 22.65
November 409.67 21.43 95.83 21.20 95.67 21.04
December 422.00 20.70 217.50 20.50 217.50 20.41
             
Annual Sum or Average 3098.83 21.83 1920.67 22.19 799.50 21.95
Minimum of Months 33.83 20.36 26.00 20.17 1.00 20.09
Maximum of Months 427.00 24.94 312.33 24.62 272.50 24.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 488.83 20.88 236.67 20.62 233.17 20.47
February 389.17 21.48 128.50 21.39 105.83 21.20
March 390.33 22.26 61.83 22.35 22.83 22.26
April 266.67 22.82 101.83 23.30 2.00 23.29
May 202.83 23.35 157.17 23.84 7.67 23.91
June 111.33 23.60 209.33 24.15 4.83 24.19
July 60.17 24.28 327.17 24.44 12.00 24.51
August 50.33 24.35 361.50 24.35 13.17 24.43
September 134.83 23.46 244.00 24.08 8.00 24.14
October 317.33 22.71 105.17 23.20 3.33 23.23
November 438.17 21.72 105.83 21.70 75.83 21.53
December 458.50 21.09 197.50 20.90 189.50 20.75
             
Annual Sum or Average 3308.50 22.05 2236.50 22.54 678.17 22.34
Minimum of Months 50.33 20.88 61.83 20.62 2.00 20.47
Maximum of Months 488.83 24.35 361.50 24.44 233.17 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.50 294.83 20.31 294.83 20.22
February 439.33 21.16 154.33 20.92 153.00 20.77
March 464.33 22.14 46.00 22.08 35.33 21.97
April 317.83 22.79 70.83 23.10 3.00 23.10
May 206.83 23.46 145.50 23.90 13.00 24.01
June 96.17 23.66 208.17 24.17 5.67 24.23
July 52.17 24.57 345.67 24.49 14.33 24.57
August 48.00 24.18 366.00 24.33 10.33 24.39
September 154.00 23.49 210.00 24.03 10.83 24.11
October 393.67 22.55 39.17 22.74 0.67 22.74
November 472.50 21.44 107.17 21.27 101.33 21.12
December 497.00 20.82 236.17 20.61 236.17 20.51
             
Annual Sum or Average 3643.83 21.86 2223.83 22.23 878.50 22.02
Minimum of Months 48.00 20.50 39.17 20.31 0.67 20.22
Maximum of Months 502.00 24.57 366.00 24.49 294.83 24.57



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.07165 31.12831 -0.0355 6.57919
February 454.00000 23.81090 30.97198 0.16904 5.92828
March 514.00000 24.20583 29.77086 0.29315 6.90824
April 485.00000 24.38290 33.02166 0.38303 8.34076
May 508.00000 24.41199 36.30337 -0.4222 9.21108
June 496.00000 24.41781 38.16248 -0.3848 8.60915
July 497.00000 24.53311 42.20307 -0.3119 7.71779
August 514.00000 24.44798 45.39216 -0.3085 7.58016
September 485.00000 24.49254 43.04820 -0.3364 8.07107
October 502.00000 24.41603 35.88552 0.41137 8.82431
November 489.00000 24.10677 35.61796 0.29117 7.10551
December 497.00000 23.69353 31.11070 0.13439 5.60668
           
Annual Sum or Average 5943.00000 24.16809 36.08526 -0.0119 7.55123
Minimum of Months 454.00000 23.07165 29.77086 -0.4222 5.60668
Maximum of Months 514.00000 24.53311 45.39216 0.41137 9.21108



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.41550 34.10391 -0.4027 9.91540
February 454.00000 22.19823 34.41956 -0.1936 6.93819
March 514.00000 23.25624 32.92591 0.06959 5.61699
April 485.00000 23.78010 34.83314 0.23120 6.52199
May 508.00000 24.05156 37.86991 -0.5653 12.03420
June 496.00000 24.17087 39.40069 -0.4916 10.28617
July 497.00000 24.28248 43.27223 -0.4187 8.96709
August 514.00000 24.23904 46.43650 -0.4052 8.69898
September 485.00000 24.15970 44.66028 -0.4753 10.07212
October 502.00000 23.66296 38.84089 0.22393 6.50876
November 489.00000 22.67291 39.66670 -0.0400 6.14584
December 497.00000 21.88938 34.85239 -0.2726 7.25952
           
Annual Sum or Average 5943.00000 23.32360 38.46491 -0.2293 8.25958
Minimum of Months 454.00000 21.41550 32.92591 -0.5653 5.61699
Maximum of Months 514.00000 24.28248 46.43650 0.23120 12.03420



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.74064 35.08173 -0.5849 14.23959
February 454.00000 21.37437 35.56517 -0.4045 10.39987
March 514.00000 22.48436 34.31595 -0.1196 6.39026
April 485.00000 23.30037 35.82869 0.11274 6.18484
May 508.00000 23.79293 38.51618 -0.6586 14.95473
June 496.00000 24.03587 39.63441 -0.5411 11.49455
July 497.00000 24.17379 43.35143 -0.4565 9.70288
August 514.00000 24.12476 46.49526 -0.4490 9.56281
September 485.00000 23.86714 45.53201 -0.5859 12.87428
October 502.00000 22.97426 40.65396 0.05173 6.06859
November 489.00000 21.76071 41.62831 -0.2700 8.11814
December 497.00000 21.03118 36.27170 -0.4979 11.30506
           
Annual Sum or Average 5943.00000 22.81653 39.42733 -0.3672 10.10749
Minimum of Months 454.00000 20.74064 34.31595 -0.6586 6.06859
Maximum of Months 514.00000 24.17379 46.49526 0.11274 14.95473



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.07712 36.88378 -0.7830 20.44307
February 454.00000 20.53008 37.53629 -0.6304 15.92383
March 514.00000 21.45373 37.23667 -0.3629 9.34716
April 485.00000 22.56812 37.99590 -0.0558 7.02958
May 508.00000 23.38495 40.14225 -0.7850 20.27052
June 496.00000 23.84183 40.70308 -0.5941 13.49991
July 497.00000 24.03900 44.00396 -0.4837 10.80564
August 514.00000 23.95099 47.61486 -0.4951 11.10589
September 485.00000 23.37970 47.91817 -0.7498 18.73893
October 502.00000 22.00697 44.07576 -0.1737 7.26443
November 489.00000 20.81522 44.29773 -0.5107 12.41314
December 497.00000 20.26565 38.45962 -0.7183 17.45349
           
Annual Sum or Average 5943.00000 22.20642 41.42557 -0.5281 13.67279
Minimum of Months 454.00000 20.07712 36.88378 -0.7850 7.02958
Maximum of Months 514.00000 24.03900 47.91817 -0.0558 20.44307



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.12943 37.80011 -0.7594 19.63968
February 454.00000 20.82630 38.01560 -0.5482 13.91781
March 514.00000 21.92471 37.17406 -0.2380 8.56288
April 485.00000 23.07670 36.71111 0.09399 7.40986
May 508.00000 23.64908 39.39637 -0.6483 17.04619
June 496.00000 24.06682 39.78442 -0.4466 11.21959
July 497.00000 24.23312 43.38599 -0.3489 9.44106
August 514.00000 24.13932 46.82742 -0.3520 9.37799
September 485.00000 23.63437 47.08944 -0.6112 15.82054
October 502.00000 22.39927 43.47805 -0.0660 7.31955
November 489.00000 20.96247 44.98799 -0.4669 11.82173
December 497.00000 20.34115 39.34463 -0.6882 16.66654
           
Annual Sum or Average 5943.00000 22.46193 41.18180 -0.4227 12.33741
Minimum of Months 454.00000 20.12943 36.71111 -0.7594 7.31955
Maximum of Months 514.00000 24.23312 47.08944 0.09399 19.63968



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.55864 36.03598 -0.6443 17.21101
February 454.00000 21.41843 35.46548 -0.3919 12.39489
March 514.00000 22.18795 34.87527 -0.1574 8.84320
April 485.00000 23.07283 35.79314 0.10108 8.12039
May 508.00000 23.56760 38.98914 -0.6743 18.42249
June 496.00000 23.91682 40.02656 -0.5270 13.12500
July 497.00000 24.14386 43.35311 -0.3894 10.42066
August 514.00000 24.07387 46.66733 -0.3754 10.16844
September 485.00000 23.71314 45.94206 -0.5444 15.03234
October 502.00000 22.76122 41.14760 0.04328 8.24667
November 489.00000 21.41501 42.76517 -0.3519 11.04572
December 497.00000 20.85264 37.14207 -0.5534 14.86579
           
Annual Sum or Average 5943.00000 22.65028 39.87546 -0.3724 12.32466
Minimum of Months 454.00000 20.55864 34.87527 -0.6743 8.12039
Maximum of Months 514.00000 24.14386 46.66733 0.10108 18.42249



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.16586 37.69208 -0.7523 19.59963
February 454.00000 20.82695 37.78509 -0.5501 14.56906
March 514.00000 21.77360 37.09470 -0.2741 9.16820
April 485.00000 22.83452 37.46860 0.03455 7.85022
May 508.00000 23.55720 39.83633 -0.6724 18.68223
June 496.00000 23.91577 40.63141 -0.5136 12.82454
July 497.00000 24.17494 43.57057 -0.3529 10.09889
August 514.00000 24.06321 47.27143 -0.3846 10.30747
September 485.00000 23.63392 47.18069 -0.6068 16.23652
October 502.00000 22.28721 43.73823 -0.0925 7.51665
November 489.00000 20.96616 44.93080 -0.4681 11.94231
December 497.00000 20.39459 39.20937 -0.6785 16.67051
           
Annual Sum or Average 5943.00000 22.39559 41.38556 -0.4422 12.94212
Minimum of Months 454.00000 20.16586 37.09470 -0.7523 7.51665
Maximum of Months 514.00000 24.17494 47.27143 0.03455 19.59963



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.42335 36.66059 -0.6793 16.07309
February 454.00000 20.82059 37.42277 -0.5431 12.37027
March 514.00000 21.55811 37.02456 -0.3329 7.98453
April 485.00000 22.52981 39.05332 -0.0687 6.17493
May 508.00000 23.43493 40.72633 -0.7930 19.38500
June 496.00000 23.88436 41.22952 -0.6061 13.17500
July 497.00000 24.08924 44.44100 -0.4911 10.36896
August 514.00000 24.03479 47.96478 -0.4851 10.32449
September 485.00000 23.65640 47.44301 -0.6641 15.07534
October 502.00000 22.64819 42.49895 -0.0168 5.79844
November 489.00000 21.48009 42.97694 -0.3209 8.32311
December 497.00000 20.72039 37.83227 -0.5717 12.30958
           
Annual Sum or Average 5943.00000 22.45251 41.29356 -0.4645 11.44816
Minimum of Months 454.00000 20.42335 36.66059 -0.7930 5.79844
Maximum of Months 514.00000 24.08924 47.96478 -0.0168 19.38500



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.47338 37.64815 -0.6575 15.44202
February 454.00000 21.13669 37.95504 -0.4552 10.62454
March 514.00000 22.16112 36.94437 -0.1786 6.84472
April 485.00000 23.28087 37.36338 0.13518 6.68692
May 508.00000 23.79464 39.56544 -0.6241 14.96886
June 496.00000 24.17969 39.81667 -0.4318 10.08379
July 497.00000 24.32446 43.54745 -0.3400 8.54082
August 514.00000 24.25408 46.84599 -0.3238 8.28890
September 485.00000 23.95590 46.31400 -0.5074 11.92789
October 502.00000 23.09252 41.67560 0.10415 6.33820
November 489.00000 21.67390 43.63281 -0.2683 7.93872
December 497.00000 20.84501 38.71020 -0.5334 11.60178
           
Annual Sum or Average 5943.00000 22.77670 40.84986 -0.3398 9.93820
Minimum of Months 454.00000 20.47338 36.94437 -0.6575 6.33820
Maximum of Months 514.00000 24.32446 46.84599 0.13518 15.44202



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.35454 34.24657 -0.6490 15.93293
February 454.00000 21.24132 34.13906 -0.3863 10.69876
March 514.00000 21.88952 33.74606 -0.1950 7.80144
April 485.00000 22.74790 36.00468 0.04021 7.31023
May 508.00000 23.25690 39.41826 -0.7714 20.51384
June 496.00000 23.66956 40.59240 -0.6128 14.99389
July 497.00000 24.09500 43.78382 -0.4174 10.43623
August 514.00000 24.05428 47.10169 -0.3792 9.78507
September 485.00000 23.80305 45.36414 -0.4944 13.19927
October 502.00000 23.04146 39.10649 0.14106 7.69472
November 489.00000 21.48453 40.23089 -0.2781 9.06804
December 497.00000 20.83267 35.03661 -0.5011 12.44651
           
Annual Sum or Average 5943.00000 22.54926 39.09590 -0.3759 11.67254
Minimum of Months 454.00000 20.35454 33.74606 -0.7714 7.31023
Maximum of Months 514.00000 24.09500 47.10169 0.14106 20.51384



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.49615 37.59389 -0.6524 15.37981
February 454.00000 21.11740 37.86015 -0.4597 11.07915
March 514.00000 22.04187 36.91040 -0.2074 7.20046
April 485.00000 23.07818 37.93773 0.08252 6.76458
May 508.00000 23.83975 39.52854 -0.6061 14.64827
June 496.00000 24.08391 40.49581 -0.4820 10.88490
July 497.00000 24.37890 43.25085 -0.3056 8.14941
August 514.00000 24.25493 46.99409 -0.3323 8.39508
September 485.00000 24.06215 45.97119 -0.4702 11.16301
October 502.00000 23.05267 41.84962 0.09364 6.37924
November 489.00000 21.65452 43.64039 -0.2732 8.06190
December 497.00000 20.85345 38.67445 -0.5314 11.68583
           
Annual Sum or Average 5943.00000 22.75520 40.90785 -0.3451 9.97890
Minimum of Months 454.00000 20.49615 36.91040 -0.6524 6.37924
Maximum of Months 514.00000 24.37890 46.99409 0.09364 15.37981



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.40626 36.47323 -0.6689 16.15157
February 454.00000 20.95641 36.86860 -0.4956 11.95225
March 514.00000 22.04580 36.19560 -0.2063 6.97686
April 485.00000 23.04966 37.06652 0.06395 6.28292
May 508.00000 23.70165 39.32749 -0.6759 15.72227
June 496.00000 24.00956 40.27865 -0.5351 11.45461
July 497.00000 24.17067 43.77051 -0.4390 9.42383
August 514.00000 24.09786 47.32879 -0.4430 9.56576
September 485.00000 23.74731 46.80528 -0.6204 14.00972
October 502.00000 22.67952 42.38354 -0.0049 6.08382
November 489.00000 21.38396 43.10306 -0.3454 9.01818
December 497.00000 20.66881 37.74389 -0.5810 12.86266
           
Annual Sum or Average 5943.00000 22.58940 40.63275 -0.4125 10.78378
Minimum of Months 454.00000 20.40626 36.19560 -0.6759 6.08382
Maximum of Months 514.00000 24.17067 47.32879 0.06395 16.15157



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.35529 37.24433 -0.6732 16.43659
February 385.00000 21.19516 37.04327 -0.4333 10.97511
March 433.00000 22.33750 35.85604 -0.1268 6.90289
April 410.00000 23.40155 35.62113 0.16963 7.09086
May 430.00000 23.89005 38.37863 -0.5785 14.23919
June 418.00000 24.22235 39.29650 -0.4089 10.12137
July 422.00000 24.40353 42.81412 -0.3126 8.64650
August 433.00000 24.28810 46.25744 -0.3192 8.63159
September 410.00000 23.93243 45.84642 -0.5178 12.60969
October 427.00000 22.90519 41.76200 0.06074 6.56798
November 417.00000 21.47098 43.60612 -0.3196 9.00134
December 422.00000 20.69967 38.48627 -0.5671 12.78696
           
Annual Sum or Average 5034.00000 22.76774 40.20172 -0.3354 10.33057
Minimum of Months 385.00000 20.35529 35.62113 -0.6732 6.56798
Maximum of Months 433.00000 24.40353 46.25744 0.16963 16.43659



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.97343 35.43831 -0.5148 13.48817
February 454.00000 21.89616 34.62760 -0.2498 9.66441
March 514.00000 22.71666 33.79798 -0.0156 7.21428
April 485.00000 23.47833 34.93114 0.20453 7.71215
May 508.00000 23.86107 38.23833 -0.5728 14.18723
June 496.00000 24.09073 39.61326 -0.4676 10.94875
July 497.00000 24.28540 43.08920 -0.3439 8.89851
August 514.00000 24.21247 46.40190 -0.3277 8.69377
September 485.00000 24.01605 45.03240 -0.4354 11.28220
October 502.00000 23.31119 39.67500 0.18645 7.85343
November 489.00000 22.01405 41.43983 -0.1826 8.57945
December 497.00000 21.34691 36.19203 -0.4012 11.00576
           
Annual Sum or Average 5943.00000 23.02585 39.06663 -0.2607 9.96392
Minimum of Months 454.00000 20.97343 33.79798 -0.5728 7.21428
Maximum of Months 514.00000 24.28540 46.40190 0.20453 14.18723



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.50420 37.31221 -0.6367 15.46283
February 454.00000 21.25684 37.07041 -0.4157 11.03280
March 514.00000 22.33898 35.97702 -0.1241 7.07033
April 485.00000 23.29620 36.51627 0.14946 7.25278
May 508.00000 23.86644 38.98634 -0.5665 14.26232
June 496.00000 24.09007 40.15518 -0.4539 10.66054
July 497.00000 24.31502 43.27724 -0.3075 8.62904
August 514.00000 24.20851 46.95816 -0.3344 8.78698
September 485.00000 23.96626 46.10480 -0.4886 12.07830
October 502.00000 22.92185 42.07697 0.06803 6.62702
November 489.00000 21.53397 43.69149 -0.3038 8.82610
December 497.00000 20.81556 38.47433 -0.5388 12.30785
           
Annual Sum or Average 5943.00000 22.77150 40.56889 -0.3292 10.24377
Minimum of Months 454.00000 20.50420 35.97702 -0.6367 6.62702
Maximum of Months 514.00000 24.31502 46.95816 0.14946 15.46283



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.526211E+11 0.00 424.28 150171.43 25-JAN-07:02 0.00 37.23 50.49 0.22 0.00 0.09 0.66 25-JAN-07:02
February 0.281409E+11 0.00 326.61 153710.22 09-FEB-07:01 0.00 34.18 46.40 0.13 0.00 0.05 0.68 09-FEB-07:01
March 0.112648E+11 0.00 292.96 152296.43 01-MAR-07:01 0.00 31.00 42.04 0.04 0.00 0.02 0.67 01-MAR-07:01
April 0.439876E+10 0.00 174.17 124764.09 19-APR-06:02 0.00 29.96 36.82 0.02 0.00 0.01 0.55 19-APR-06:02
May 0.135780E+10 0.00 79.29 64550.75 18-MAY-06:03 0.00 34.37 37.05 0.00 0.00 0.00 0.29 18-MAY-06:03
June 0.313523E+09 0.00 26.37 11443.85 15-JUN-06:05 0.00 41.49 42.19 0.00 0.00 0.00 0.05 15-JUN-06:05
July 52338127.33 0.00 62.34 9902.67 27-JUL-06:08 0.00 34.82 37.01 0.00 0.00 0.00 0.04 27-JUL-06:08
August 74935531.34 0.00 116.94 10031.54 03-AUG-06:06 0.00 40.85 43.93 0.00 0.00 0.00 0.04 03-AUG-06:06
September 0.382376E+09 0.00 69.81 30429.29 28-SEP-06:03 0.00 40.68 42.64 0.00 0.00 0.00 0.13 28-SEP-06:03
October 0.315233E+10 0.00 155.39 116650.49 30-OCT-06:03 0.00 31.68 37.36 0.01 0.00 0.01 0.52 30-OCT-06:03
November 0.199345E+11 0.00 307.02 143128.52 16-NOV-07:02 0.00 33.27 44.77 0.08 0.00 0.03 0.63 16-NOV-07:02
December 0.400314E+11 0.00 384.08 146442.86 26-DEC-07:12 0.00 34.52 47.70 0.16 0.00 0.07 0.65 26-DEC-07:12
                           
Annual Sum or Average 0.161725E+12 0.00 2419.25     0.00 35.34 42.34 0.06 0.00 0.02    
Minimum of Months 52338127.33 0.00 26.37 9902.67   0.00 29.96 36.82 0.00 0.00 0.00 0.04  
Maximum of Months 0.526211E+11 0.00 424.28 153710.22   0.00 41.49 50.49 0.22 0.00 0.09 0.68  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1258189.69 338915.97 0.33 1125441.30 132748.39 0.00 0.05 02-JAN-10:30 0.00 01-JAN-00:05 1070.81 02-JAN-10:30 959.52 02-JAN-10:30 111.29 02-JAN-10:30 288.38 02-JAN-10:30 0.00
February 0.200641E+09 50082578.59 9.33 0.184550E+09 16091291.65 0.00 0.53 27-FEB-15:10 0.00 01-FEB-00:10 12969.88 27-FEB-15:10 12969.88 27-FEB-15:10 1251.39 27-FEB-17:13 3104.14 27-FEB-15:10 0.00
March 0.530421E+09 0.137868E+09 54.30 0.476885E+09 53536247.75 0.00 0.45 18-MAR-16:00 0.00 01-MAR-00:10 10915.52 18-MAR-16:00 10915.52 18-MAR-16:00 1375.26 09-MAR-12:00 2663.64 18-MAR-16:00 0.00
April 0.639404E+10 0.149428E+10 148.63 0.619764E+10 0.196397E+09 0.00 1.00 26-APR-12:10 0.00 01-APR-00:10 51578.74 27-APR-15:00 51578.74 27-APR-15:00 4113.06 28-APR-13:00 11763.75 27-APR-15:00 0.00
May 0.800266E+10 0.183288E+10 178.24 0.721387E+10 0.788788E+09 0.00 1.00 03-MAY-15:50 0.00 01-MAY-00:10 47197.76 15-MAY-16:00 47197.76 15-MAY-16:00 6409.79 07-MAY-17:21 9928.28 15-MAY-16:00 0.00
June 0.143724E+11 0.326573E+10 268.19 0.134310E+11 0.941381E+09 0.00 1.00 09-JUN-13:20 0.00 01-JUN-00:10 52946.67 28-JUN-15:30 52946.67 28-JUN-15:30 10094.15 12-JUN-06:02 11737.78 28-JUN-15:30 0.00
July 0.276307E+11 0.618611E+10 353.97 0.245183E+11 0.311234E+10 0.00 1.00 06-JUL-14:05 0.00 01-JUL-00:10 72039.91 31-JUL-15:50 67015.11 24-JUL-15:00 17354.32 31-JUL-06:03 17649.22 24-JUL-15:00 0.00
August 0.375451E+11 0.846185E+10 376.66 0.329391E+11 0.460594E+10 0.00 1.00 01-AUG-15:50 0.00 01-AUG-00:10 71006.32 10-AUG-15:40 67254.75 10-AUG-15:50 17160.10 30-AUG-13:00 17819.57 10-AUG-15:50 0.00
September 0.139503E+11 0.311537E+10 233.51 0.117035E+11 0.224679E+10 0.00 1.00 08-SEP-13:30 0.00 01-SEP-00:10 58396.42 12-SEP-16:00 54909.94 12-SEP-15:20 15156.14 14-SEP-13:00 12454.47 12-SEP-16:00 0.00
October 0.266424E+10 0.632768E+09 87.57 0.252042E+10 0.143822E+09 0.00 1.00 04-OCT-13:05 0.00 01-OCT-00:10 35126.82 04-OCT-15:00 35126.82 04-OCT-15:00 2667.09 08-OCT-14:00 7373.66 04-OCT-15:00 0.00
November 0.362717E+09 86041694.28 12.71 0.252449E+09 0.110268E+09 0.00 0.73 04-NOV-15:00 0.00 01-NOV-00:10 18890.90 04-NOV-15:00 14516.46 04-NOV-15:00 5290.35 04-NOV-16:00 4284.00 04-NOV-15:00 0.00
December 6678546.16 1769724.90 0.90 6169609.10 508937.06 0.00 0.16 05-DEC-12:00 0.00 01-DEC-00:10 3550.29 05-DEC-12:00 3369.61 05-DEC-12:00 413.80 05-DEC-12:02 931.80 05-DEC-12:00 0.00
                                       
Annual Sum or Average 0.111661E+12 0.252651E+11 1724.36 0.994451E+11 0.122160E+11 0.00                         0.00
Minimum of Months 1258189.69 338915.97 0.33 1125441.30 132748.39 0.00 0.05   0.00   1070.81   959.52   111.29   288.38   0.00
Maximum of Months 0.375451E+11 0.846185E+10 376.66 0.329391E+11 0.460594E+10 0.00 1.00   0.00   72039.91   67254.75   17354.32   17819.57   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 203097.43 54479.62 0.04 163444.72 39652.71 0.00 0.07 11-JAN-07:05 0.00 01-JAN-00:05 1353.98 11-JAN-07:05 1089.63 11-JAN-07:05 264.35 11-JAN-07:05 363.20 11-JAN-07:05 0.00
February 0.182989E+09 45717435.15 8.04 0.167667E+09 15322261.10 0.00 0.56 27-FEB-15:05 0.00 01-FEB-00:10 12920.73 27-FEB-15:05 12920.73 27-FEB-15:05 1214.30 27-FEB-17:13 3068.30 27-FEB-15:05 0.00
March 0.279433E+09 71371477.28 23.08 0.249260E+09 30172849.88 0.00 0.49 18-MAR-14:05 0.00 01-MAR-00:10 11221.09 18-MAR-14:05 11221.09 18-MAR-14:05 1204.21 09-MAR-12:00 2710.37 18-MAR-14:05 0.00
April 0.343582E+10 0.792603E+09 75.42 0.330552E+10 0.130299E+09 0.00 1.00 26-APR-13:00 0.00 01-APR-00:10 50319.97 27-APR-14:05 50319.97 27-APR-14:05 4256.11 28-APR-13:00 11298.07 27-APR-15:00 0.00
May 0.712293E+10 0.162291E+10 163.64 0.640224E+10 0.720686E+09 0.00 1.00 03-MAY-15:20 0.00 01-MAY-00:10 44026.64 04-MAY-15:00 44026.64 04-MAY-15:00 7422.13 07-MAY-16:01 9368.79 04-MAY-15:00 0.00
June 0.130912E+11 0.298318E+10 272.87 0.122071E+11 0.884044E+09 0.00 1.00 09-JUN-13:00 0.00 01-JUN-00:10 49084.63 28-JUN-15:30 49084.63 28-JUN-15:30 9245.26 12-JUN-06:02 10881.91 28-JUN-15:30 0.00
July 0.247676E+11 0.556146E+10 357.50 0.219924E+11 0.277523E+10 0.00 1.00 06-JUL-14:05 0.00 01-JUL-00:10 67971.42 31-JUL-14:05 60862.30 31-JUL-14:05 17404.82 31-JUL-06:03 15877.90 31-JUL-14:05 0.00
August 0.327368E+11 0.741084E+10 378.24 0.287115E+11 0.402525E+10 0.00 1.00 04-AUG-14:00 0.00 01-AUG-00:10 67015.65 10-AUG-14:05 61082.37 10-AUG-15:10 16137.16 30-AUG-13:00 16602.53 29-AUG-15:30 0.00
September 0.121953E+11 0.273499E+10 233.84 0.101700E+11 0.202524E+10 0.00 1.00 08-SEP-13:00 0.00 01-SEP-00:10 54286.94 13-SEP-14:05 49397.74 12-SEP-14:05 15244.36 14-SEP-13:00 11441.02 13-SEP-14:05 0.00
October 0.158148E+10 0.374436E+09 59.25 0.148336E+10 98118696.90 0.00 1.00 04-OCT-13:10 0.00 01-OCT-00:10 31703.47 04-OCT-15:00 31703.47 04-OCT-15:00 2495.61 01-OCT-13:25 6655.52 04-OCT-15:00 0.00
November 0.340540E+09 79783181.58 8.77 0.239897E+09 0.100643E+09 0.00 0.77 04-NOV-14:05 0.00 01-NOV-00:10 18844.83 04-NOV-14:05 14933.29 04-NOV-14:05 4815.39 04-NOV-16:00 4226.75 04-NOV-14:05 0.00
December 235862.49 63114.19 0.04 161238.58 74623.91 0.00 0.08 29-DEC-07:05 0.00 01-DEC-00:10 1572.42 29-DEC-07:05 1074.92 29-DEC-07:05 497.49 29-DEC-07:05 420.76 29-DEC-07:05 0.00
                                       
Annual Sum or Average 0.957345E+11 0.216774E+11 1580.73 0.849293E+11 0.108051E+11 0.00                         0.00
Minimum of Months 203097.43 54479.62 0.04 161238.58 39652.71 0.00 0.07   0.00   1353.98   1074.92   264.35   363.20   0.00
Maximum of Months 0.327368E+11 0.741084E+10 378.24 0.287115E+11 0.402525E+10 0.00 1.00   0.00   67971.42   61082.37   17404.82   16602.53   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 0.187718E+09 47247022.02 8.00 0.166529E+09 21188580.80 0.00 0.48 27-FEB-15:00 0.00 01-FEB-00:10 12047.39 27-FEB-15:00 12047.39 27-FEB-15:00 1414.89 27-FEB-17:05 2923.19 27-FEB-15:00 0.00
March 0.421801E+09 0.107590E+09 28.27 0.384852E+09 36949161.79 0.00 0.45 01-MAR-15:00 0.00 01-MAR-00:10 11377.32 01-MAR-15:00 11377.32 01-MAR-15:00 1329.15 09-MAR-12:00 2777.46 01-MAR-15:00 0.00
April 0.364843E+10 0.844071E+09 73.25 0.348248E+10 0.165942E+09 0.00 1.00 26-APR-13:05 0.00 01-APR-00:10 57162.53 27-APR-14:40 57162.53 27-APR-14:40 4043.58 28-APR-13:00 12968.88 27-APR-15:00 0.00
May 0.744064E+10 0.170126E+10 162.58 0.661351E+10 0.827125E+09 0.00 1.00 03-MAY-15:50 0.00 01-MAY-00:10 47729.89 04-MAY-15:00 47729.89 04-MAY-15:00 6706.77 07-MAY-16:12 10157.66 04-MAY-15:00 0.00
June 0.137330E+11 0.314326E+10 271.00 0.127004E+11 0.103258E+10 0.00 1.00 09-JUN-13:05 0.00 01-JUN-00:10 56945.21 28-JUN-15:20 56945.21 28-JUN-15:20 5390.05 12-JUN-12:40 12623.16 28-JUN-15:20 0.00
July 0.263174E+11 0.593238E+10 356.02 0.231729E+11 0.314444E+10 0.00 1.00 06-JUL-14:40 0.00 01-JUL-00:10 74463.78 31-JUL-14:40 67737.06 31-JUL-14:50 13207.91 31-JUL-10:30 17713.48 24-JUL-15:00 0.00
August 0.343100E+11 0.781647E+10 377.72 0.299547E+11 0.435537E+10 0.00 1.00 06-AUG-15:22 0.00 01-AUG-00:10 74478.81 10-AUG-14:50 69963.55 10-AUG-15:20 16116.48 30-AUG-13:00 18371.98 29-AUG-15:20 0.00
September 0.122129E+11 0.275660E+10 230.25 0.100581E+11 0.215482E+10 0.00 1.00 08-SEP-14:00 0.00 01-SEP-00:10 53643.15 14-SEP-13:30 49884.37 12-SEP-15:20 14681.18 14-SEP-13:00 11315.44 14-SEP-13:30 0.00
October 0.144981E+10 0.347861E+09 55.89 0.134149E+10 0.108313E+09 0.00 1.00 04-OCT-14:20 0.00 01-OCT-00:10 31099.77 04-OCT-15:00 31099.77 04-OCT-15:00 4238.19 08-OCT-13:32 6530.33 04-OCT-15:00 0.00
November 0.346211E+09 81951757.03 7.71 0.235736E+09 0.110475E+09 0.00 0.70 04-NOV-14:20 0.00 01-NOV-00:10 18724.29 04-NOV-14:20 14028.89 04-NOV-14:20 5358.19 04-NOV-13:00 4284.07 04-NOV-14:20 0.00
December 68427.90 18594.94 0.08 51442.45 16985.45 0.00 0.01 18-DEC-06:10 0.00 01-DEC-00:10 228.09 18-DEC-06:10 171.47 18-DEC-06:10 56.62 18-DEC-06:10 61.98 18-DEC-06:10 0.00
                                       
Annual Sum or Average 0.100068E+12 0.227787E+11 1570.77 0.881107E+11 0.119572E+11 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.343100E+11 0.781647E+10 377.72 0.299547E+11 0.435537E+10 0.00 1.00   0.00   74478.81   69963.55   16116.48   18371.98   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 240.22 0.00 240.22 11.97 1381.90 0.00 0.00 0.00
February 373.79 0.00 373.79 85.44 1231.56 0.00 0.00 0.00
March 550.72 0.00 550.72 245.84 1032.74 0.00 0.00 0.00
April 779.33 2.76 776.56 516.88 843.63 0.00 0.00 0.00
May 1002.80 29.79 973.01 822.10 692.05 0.00 0.00 0.00
June 1054.42 69.63 984.79 950.58 538.16 0.00 0.00 0.00
July 1002.17 78.57 923.59 1021.23 485.57 0.00 0.00 0.00
August 811.26 21.93 789.33 842.93 473.98 0.00 0.00 0.00
September 630.16 0.19 629.97 490.23 698.42 0.00 0.00 0.00
October 431.76 0.00 431.76 207.16 914.54 0.00 0.00 0.00
November 271.97 0.00 271.97 45.35 1119.49 0.00 0.00 0.00
December 204.13 0.00 204.13 6.70 1389.40 0.00 0.00 0.00
                 
Annual Sum or Average 613.91 17.03 596.88 439.40 898.49 0.00 0.00 0.00
Minimum of Months 204.13 0.00 204.13 6.70 473.98 0.00 0.00 0.00
Maximum of Months 1054.42 78.57 984.79 1021.23 1389.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 257.34 65.24 192.09 97.73 875.15 0.00 0.00 0.00
February 472.19 167.59 304.60 319.15 778.29 0.00 0.00 0.00
March 705.01 255.22 449.79 593.84 663.45 0.00 0.00 0.00
April 1092.89 454.11 638.78 1110.64 546.41 0.00 0.00 0.00
May 1162.93 404.32 758.61 1237.99 467.61 0.00 0.00 0.00
June 1392.74 605.99 786.75 1591.82 369.03 0.00 0.00 0.00
July 1296.96 582.15 714.81 1548.85 326.71 0.00 0.00 0.00
August 1274.74 637.70 637.04 1575.90 318.06 0.00 0.00 0.00
September 942.48 434.68 507.80 1038.72 452.28 0.00 0.00 0.00
October 614.31 261.02 353.28 565.59 592.31 0.00 0.00 0.00
November 301.10 85.00 216.10 166.84 721.05 0.00 0.00 0.00
December 246.97 79.51 167.46 121.75 889.63 0.00 0.00 0.00
                 
Annual Sum or Average 814.80 336.78 478.02 833.34 582.40 0.00 0.00 0.00
Minimum of Months 246.97 65.24 167.46 97.73 318.06 0.00 0.00 0.00
Maximum of Months 1392.74 637.70 786.75 1591.82 889.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1061.37 630.25 431.13 958.23 1257.39 0.00 0.00 0.00
February 1632.23 1010.37 621.86 1675.21 1152.02 0.00 0.00 0.00
March 1755.81 936.35 819.45 1874.74 1028.48 0.00 0.00 0.00
April 1853.80 804.91 1048.89 2088.70 889.45 0.00 0.00 0.00
May 1695.06 504.98 1190.09 1924.67 751.10 0.00 0.00 0.00
June 1550.82 416.37 1134.44 1795.54 597.85 0.00 0.00 0.00
July 1691.23 619.42 1071.81 2163.51 542.53 0.00 0.00 0.00
August 1817.02 847.31 969.71 2405.68 522.86 0.00 0.00 0.00
September 2013.18 1111.74 901.44 2505.15 718.38 0.00 0.00 0.00
October 1823.60 1125.94 697.66 2079.08 913.66 0.00 0.00 0.00
November 1078.17 617.88 460.29 1041.88 1066.55 0.00 0.00 0.00
December 1128.08 730.02 398.05 1118.42 1298.68 0.00 0.00 0.00
                 
Annual Sum or Average 1591.01 778.19 812.82 1803.01 893.64 0.00 0.00 0.00
Minimum of Months 1061.37 416.37 398.05 958.23 522.86 0.00 0.00 0.00
Maximum of Months 2013.18 1125.94 1190.09 2505.15 1298.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 271.43 80.04 191.39 121.56 882.36 0.00 0.00 0.00
February 486.65 182.90 303.75 352.05 789.35 0.00 0.00 0.00
March 681.92 230.17 451.75 579.63 677.99 0.00 0.00 0.00
April 1037.47 396.66 640.80 1050.98 574.27 0.00 0.00 0.00
May 1334.98 542.33 792.65 1474.44 490.32 0.00 0.00 0.00
June 1283.89 498.49 785.40 1447.90 388.95 0.00 0.00 0.00
July 1586.07 833.72 752.35 1962.21 357.92 0.00 0.00 0.00
August 1312.06 669.97 642.08 1648.21 347.69 0.00 0.00 0.00
September 1068.47 512.67 555.79 1236.49 478.61 0.00 0.00 0.00
October 608.28 247.85 360.44 569.11 609.40 0.00 0.00 0.00
November 302.92 85.44 217.48 174.82 725.02 0.00 0.00 0.00
December 254.66 87.27 167.40 142.78 899.03 0.00 0.00 0.00
                 
Annual Sum or Average 854.63 365.34 489.29 900.27 600.86 0.00 0.00 0.00
Minimum of Months 254.66 80.04 167.40 121.56 347.69 0.00 0.00 0.00
Maximum of Months 1586.07 833.72 792.65 1962.21 899.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.07 0.00 80.07 3.47 484.58 0.00 0.00 0.00
February 124.59 0.00 124.59 27.62 430.97 0.00 0.00 0.00
March 183.57 0.00 183.57 83.94 353.80 0.00 0.00 0.00
April 259.76 0.92 258.84 178.63 283.28 0.00 0.00 0.00
May 334.25 9.93 324.32 281.21 232.69 0.00 0.00 0.00
June 351.46 23.21 328.25 323.68 180.66 0.00 0.00 0.00
July 334.04 26.19 307.85 346.21 163.45 0.00 0.00 0.00
August 270.41 7.31 263.10 284.56 160.99 0.00 0.00 0.00
September 210.04 0.06 209.98 163.88 243.19 0.00 0.00 0.00
October 143.91 0.00 143.91 64.93 330.29 0.00 0.00 0.00
November 90.65 0.00 90.65 12.42 410.24 0.00 0.00 0.00
December 68.04 0.00 68.04 1.41 498.45 0.00 0.00 0.00
                 
Annual Sum or Average 204.63 5.68 198.95 148.41 313.81 0.00 0.00 0.00
Minimum of Months 68.04 0.00 68.04 1.41 160.99 0.00 0.00 0.00
Maximum of Months 351.46 26.19 328.25 346.21 498.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.07 0.00 80.07 3.47 484.61 0.00 0.00 0.00
February 124.60 0.00 124.60 27.62 430.99 0.00 0.00 0.00
March 183.57 0.00 183.57 83.94 353.83 0.00 0.00 0.00
April 259.77 0.92 258.85 178.64 283.29 0.00 0.00 0.00
May 334.26 9.93 324.33 281.21 232.71 0.00 0.00 0.00
June 351.47 23.21 328.26 323.69 180.67 0.00 0.00 0.00
July 334.05 26.19 307.86 346.23 163.46 0.00 0.00 0.00
August 270.42 7.31 263.11 284.58 161.00 0.00 0.00 0.00
September 210.05 0.06 209.99 163.89 243.21 0.00 0.00 0.00
October 143.92 0.00 143.92 64.93 330.31 0.00 0.00 0.00
November 90.66 0.00 90.66 12.42 410.27 0.00 0.00 0.00
December 68.04 0.00 68.04 1.41 498.49 0.00 0.00 0.00
                 
Annual Sum or Average 204.64 5.68 198.96 148.41 313.83 0.00 0.00 0.00
Minimum of Months 68.04 0.00 68.04 1.41 161.00 0.00 0.00 0.00
Maximum of Months 351.47 26.19 328.26 346.23 498.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.07 0.00 80.07 3.47 484.61 0.00 0.00 0.00
February 124.60 0.00 124.60 27.62 430.99 0.00 0.00 0.00
March 183.57 0.00 183.57 83.94 353.83 0.00 0.00 0.00
April 259.77 0.92 258.85 178.64 283.29 0.00 0.00 0.00
May 334.26 9.93 324.33 281.21 232.71 0.00 0.00 0.00
June 351.47 23.21 328.26 323.69 180.67 0.00 0.00 0.00
July 334.05 26.19 307.86 346.23 163.46 0.00 0.00 0.00
August 270.42 7.31 263.11 284.58 161.00 0.00 0.00 0.00
September 210.05 0.06 209.99 163.89 243.21 0.00 0.00 0.00
October 143.92 0.00 143.92 64.93 330.31 0.00 0.00 0.00
November 90.66 0.00 90.66 12.42 410.27 0.00 0.00 0.00
December 68.04 0.00 68.04 1.41 498.49 0.00 0.00 0.00
                 
Annual Sum or Average 204.64 5.68 198.96 148.41 313.83 0.00 0.00 0.00
Minimum of Months 68.04 0.00 68.04 1.41 161.00 0.00 0.00 0.00
Maximum of Months 351.47 26.19 328.26 346.23 498.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 247.55 62.76 184.78 91.25 885.24 0.00 0.00 0.00
February 454.22 161.21 293.01 303.72 789.27 0.00 0.00 0.00
March 678.19 245.51 432.68 574.60 666.10 0.00 0.00 0.00
April 1051.30 436.83 614.47 1076.31 544.65 0.00 0.00 0.00
May 1118.68 388.94 729.74 1201.84 463.01 0.00 0.00 0.00
June 1339.75 582.93 756.82 1543.07 367.81 0.00 0.00 0.00
July 1247.62 560.00 687.62 1500.18 324.48 0.00 0.00 0.00
August 1226.23 613.43 612.80 1522.86 320.68 0.00 0.00 0.00
September 906.62 418.14 488.48 999.30 462.89 0.00 0.00 0.00
October 590.93 251.09 339.84 535.20 625.31 0.00 0.00 0.00
November 289.64 81.77 207.87 151.79 764.12 0.00 0.00 0.00
December 237.57 76.48 161.09 111.73 921.21 0.00 0.00 0.00
                 
Annual Sum or Average 783.80 323.97 459.83 803.52 593.62 0.00 0.00 0.00
Minimum of Months 237.57 62.76 161.09 91.25 320.68 0.00 0.00 0.00
Maximum of Months 1339.75 613.43 756.82 1543.07 921.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.79 2.48 7.31 3.61 35.00 0.00 0.00 0.00
February 17.96 6.37 11.59 12.01 31.21 0.00 0.00 0.00
March 26.81 9.71 17.11 22.72 26.34 0.00 0.00 0.00
April 41.57 17.27 24.30 42.56 21.53 0.00 0.00 0.00
May 44.23 15.38 28.85 47.52 18.31 0.00 0.00 0.00
June 52.97 23.05 29.92 61.01 14.54 0.00 0.00 0.00
July 49.33 22.14 27.19 59.32 12.83 0.00 0.00 0.00
August 48.48 24.25 24.23 60.21 12.68 0.00 0.00 0.00
September 35.85 16.53 19.31 39.51 18.30 0.00 0.00 0.00
October 23.36 9.93 13.44 21.16 24.72 0.00 0.00 0.00
November 11.45 3.23 8.22 6.00 30.21 0.00 0.00 0.00
December 9.39 3.02 6.37 4.42 36.42 0.00 0.00 0.00
                 
Annual Sum or Average 30.99 12.81 18.18 31.77 23.47 0.00 0.00 0.00
Minimum of Months 9.39 2.48 6.37 3.61 12.68 0.00 0.00 0.00
Maximum of Months 52.97 24.25 29.92 61.01 36.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 353.78 210.08 143.71 321.93 438.41 0.00 0.00 0.00
February 544.07 336.78 207.28 562.24 407.20 0.00 0.00 0.00
March 585.26 312.11 273.15 633.58 358.51 0.00 0.00 0.00
April 617.92 268.30 349.63 707.82 303.32 0.00 0.00 0.00
May 565.01 168.32 396.69 654.19 253.72 0.00 0.00 0.00
June 516.93 138.79 378.14 610.60 201.49 0.00 0.00 0.00
July 563.74 206.47 357.27 729.92 185.87 0.00 0.00 0.00
August 605.66 282.43 323.23 808.50 182.42 0.00 0.00 0.00
September 671.05 370.57 300.48 838.54 256.34 0.00 0.00 0.00
October 607.86 375.31 232.55 693.55 334.95 0.00 0.00 0.00
November 359.38 205.96 153.43 346.38 386.84 0.00 0.00 0.00
December 376.02 243.34 132.68 372.73 462.26 0.00 0.00 0.00
                 
Annual Sum or Average 530.33 259.39 270.94 606.82 313.81 0.00 0.00 0.00
Minimum of Months 353.78 138.79 132.68 321.93 182.42 0.00 0.00 0.00
Maximum of Months 671.05 375.31 396.69 838.54 462.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 353.78 210.08 143.71 321.93 438.41 0.00 0.00 0.00
February 544.07 336.78 207.28 562.24 407.20 0.00 0.00 0.00
March 585.26 312.11 273.15 633.58 358.51 0.00 0.00 0.00
April 617.92 268.30 349.63 707.82 303.32 0.00 0.00 0.00
May 565.01 168.32 396.69 654.19 253.72 0.00 0.00 0.00
June 516.93 138.79 378.14 610.60 201.49 0.00 0.00 0.00
July 563.74 206.47 357.27 729.92 185.87 0.00 0.00 0.00
August 605.66 282.43 323.23 808.50 182.42 0.00 0.00 0.00
September 671.05 370.57 300.48 838.54 256.34 0.00 0.00 0.00
October 607.86 375.31 232.55 693.55 334.95 0.00 0.00 0.00
November 359.38 205.96 153.43 346.38 386.84 0.00 0.00 0.00
December 376.02 243.34 132.68 372.73 462.26 0.00 0.00 0.00
                 
Annual Sum or Average 530.33 259.39 270.94 606.82 313.81 0.00 0.00 0.00
Minimum of Months 353.78 138.79 132.68 321.93 182.42 0.00 0.00 0.00
Maximum of Months 671.05 375.31 396.69 838.54 462.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 353.76 210.07 143.70 321.91 438.38 0.00 0.00 0.00
February 544.03 336.76 207.27 562.20 407.18 0.00 0.00 0.00
March 585.22 312.09 273.13 633.54 358.49 0.00 0.00 0.00
April 617.88 268.28 349.60 707.77 303.30 0.00 0.00 0.00
May 564.98 168.31 396.67 654.15 253.70 0.00 0.00 0.00
June 516.90 138.78 378.12 610.56 201.48 0.00 0.00 0.00
July 563.70 206.46 357.25 729.87 185.86 0.00 0.00 0.00
August 605.63 282.41 323.21 808.45 182.41 0.00 0.00 0.00
September 671.01 370.55 300.46 838.49 256.32 0.00 0.00 0.00
October 607.82 375.28 232.54 693.50 334.93 0.00 0.00 0.00
November 359.36 205.94 153.42 346.36 386.81 0.00 0.00 0.00
December 376.00 243.32 132.67 372.71 462.23 0.00 0.00 0.00
                 
Annual Sum or Average 530.30 259.38 270.92 606.78 313.79 0.00 0.00 0.00
Minimum of Months 353.76 138.78 132.67 321.91 182.41 0.00 0.00 0.00
Maximum of Months 671.01 375.28 396.67 838.49 462.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 261.10 76.99 184.11 116.66 893.82 0.00 0.00 0.00
February 468.13 175.94 292.20 339.64 802.67 0.00 0.00 0.00
March 655.97 221.41 434.57 563.36 682.54 0.00 0.00 0.00
April 998.00 381.57 616.42 1023.47 571.32 0.00 0.00 0.00
May 1284.19 521.69 762.49 1432.05 491.77 0.00 0.00 0.00
June 1235.04 479.52 755.51 1407.79 388.16 0.00 0.00 0.00
July 1525.72 801.99 723.73 1900.34 363.12 0.00 0.00 0.00
August 1262.13 644.48 617.65 1594.53 353.56 0.00 0.00 0.00
September 1027.82 493.17 534.65 1190.80 494.40 0.00 0.00 0.00
October 585.14 238.42 346.72 540.32 645.10 0.00 0.00 0.00
November 291.40 82.19 209.21 161.40 769.15 0.00 0.00 0.00
December 244.97 83.95 161.03 135.16 932.04 0.00 0.00 0.00
                 
Annual Sum or Average 822.11 351.44 470.67 870.60 614.76 0.00 0.00 0.00
Minimum of Months 244.97 76.99 161.03 116.66 353.56 0.00 0.00 0.00
Maximum of Months 1525.72 801.99 762.49 1900.34 932.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.32 3.04 7.28 4.61 35.34 0.00 0.00 0.00
February 18.51 6.96 11.55 13.43 31.74 0.00 0.00 0.00
March 25.94 8.75 17.18 22.27 26.99 0.00 0.00 0.00
April 39.46 15.09 24.37 40.47 22.59 0.00 0.00 0.00
May 50.78 20.63 30.15 56.62 19.44 0.00 0.00 0.00
June 48.83 18.96 29.87 55.66 15.35 0.00 0.00 0.00
July 60.33 31.71 28.62 75.14 14.36 0.00 0.00 0.00
August 49.90 25.48 24.42 63.05 13.98 0.00 0.00 0.00
September 40.64 19.50 21.14 47.08 19.55 0.00 0.00 0.00
October 23.14 9.43 13.71 21.36 25.51 0.00 0.00 0.00
November 11.52 3.25 8.27 6.38 30.41 0.00 0.00 0.00
December 9.69 3.32 6.37 5.34 36.85 0.00 0.00 0.00
                 
Annual Sum or Average 32.51 13.90 18.61 34.42 24.31 0.00 0.00 0.00
Minimum of Months 9.69 3.04 6.37 4.61 13.98 0.00 0.00 0.00
Maximum of Months 60.33 31.71 30.15 75.14 36.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 240.22 0.00 240.22 9.14 1467.83 0.00 0.00 0.00
February 373.79 0.00 373.79 74.87 1321.38 0.00 0.00 0.00
March 550.72 0.00 550.72 227.36 1111.92 0.00 0.00 0.00
April 779.33 2.76 776.56 499.86 897.62 0.00 0.00 0.00
May 1002.80 29.79 973.01 809.91 727.62 0.00 0.00 0.00
June 1054.42 69.63 984.79 944.32 560.67 0.00 0.00 0.00
July 1002.17 78.57 923.59 1018.37 504.54 0.00 0.00 0.00
August 811.26 21.93 789.33 838.22 494.99 0.00 0.00 0.00
September 630.16 0.19 629.97 478.80 742.50 0.00 0.00 0.00
October 431.76 0.00 431.76 188.20 995.34 0.00 0.00 0.00
November 271.97 0.00 271.97 36.14 1219.50 0.00 0.00 0.00
December 204.13 0.00 204.13 3.97 1492.73 0.00 0.00 0.00
                 
Annual Sum or Average 613.91 17.03 596.88 429.64 959.59 0.00 0.00 0.00
Minimum of Months 204.13 0.00 204.13 3.97 494.99 0.00 0.00 0.00
Maximum of Months 1054.42 78.57 984.79 1018.37 1492.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 257.34 65.24 192.09 91.91 929.09 0.00 0.00 0.00
February 472.19 167.59 304.60 304.75 834.49 0.00 0.00 0.00
March 705.01 255.22 449.79 576.98 712.95 0.00 0.00 0.00
April 1092.89 454.11 638.78 1096.59 578.05 0.00 0.00 0.00
May 1162.93 404.32 758.61 1228.74 489.88 0.00 0.00 0.00
June 1392.74 605.99 786.75 1587.04 383.45 0.00 0.00 0.00
July 1296.96 582.15 714.81 1544.67 338.26 0.00 0.00 0.00
August 1274.74 637.70 637.04 1571.32 330.71 0.00 0.00 0.00
September 942.48 434.68 507.80 1028.78 478.55 0.00 0.00 0.00
October 614.31 261.02 353.28 549.43 641.72 0.00 0.00 0.00
November 301.10 85.00 216.10 155.14 785.70 0.00 0.00 0.00
December 246.97 79.51 167.46 114.32 955.70 0.00 0.00 0.00
                 
Annual Sum or Average 814.80 336.78 478.02 823.45 620.51 0.00 0.00 0.00
Minimum of Months 246.97 65.24 167.46 91.91 330.71 0.00 0.00 0.00
Maximum of Months 1392.74 637.70 786.75 1587.04 955.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1061.37 630.25 431.13 942.37 1335.50 0.00 0.00 0.00
February 1632.23 1010.37 621.86 1653.49 1231.64 0.00 0.00 0.00
March 1755.81 936.35 819.45 1858.08 1102.25 0.00 0.00 0.00
April 1853.80 804.91 1048.89 2076.67 940.69 0.00 0.00 0.00
May 1695.06 504.98 1190.09 1918.43 788.56 0.00 0.00 0.00
June 1550.82 416.37 1134.44 1794.45 623.58 0.00 0.00 0.00
July 1691.23 619.42 1071.81 2164.69 563.55 0.00 0.00 0.00
August 1817.02 847.31 969.71 2405.98 545.10 0.00 0.00 0.00
September 2013.18 1111.74 901.44 2497.07 758.43 0.00 0.00 0.00
October 1823.60 1125.94 697.66 2061.61 985.07 0.00 0.00 0.00
November 1078.17 617.88 460.29 1021.23 1156.09 0.00 0.00 0.00
December 1128.08 730.02 398.05 1101.99 1392.48 0.00 0.00 0.00
                 
Annual Sum or Average 1591.01 778.19 812.82 1791.86 950.51 0.00 0.00 0.00
Minimum of Months 1061.37 416.37 398.05 942.37 545.10 0.00 0.00 0.00
Maximum of Months 2013.18 1125.94 1190.09 2497.07 1392.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 271.43 80.04 191.39 117.13 936.93 0.00 0.00 0.00
February 486.65 182.90 303.75 342.28 845.56 0.00 0.00 0.00
March 681.92 230.17 451.75 567.63 728.69 0.00 0.00 0.00
April 1037.47 396.66 640.80 1041.12 609.21 0.00 0.00 0.00
May 1334.98 542.33 792.65 1469.85 515.27 0.00 0.00 0.00
June 1283.89 498.49 785.40 1447.30 405.97 0.00 0.00 0.00
July 1586.07 833.72 752.35 1963.69 372.10 0.00 0.00 0.00
August 1312.06 669.97 642.08 1648.15 362.61 0.00 0.00 0.00
September 1068.47 512.67 555.79 1230.75 506.38 0.00 0.00 0.00
October 608.28 247.85 360.44 556.95 661.04 0.00 0.00 0.00
November 302.92 85.44 217.48 165.84 788.30 0.00 0.00 0.00
December 254.66 87.27 167.40 138.11 964.94 0.00 0.00 0.00
                 
Annual Sum or Average 854.63 365.34 489.29 894.36 640.44 0.00 0.00 0.00
Minimum of Months 254.66 80.04 167.40 117.13 362.61 0.00 0.00 0.00
Maximum of Months 1586.07 833.72 792.65 1963.69 964.94 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.643410E+09 0.00 0.643410E+09 32059367.27 0.370127E+10
February 0.904276E+09 0.00 0.904276E+09 0.206707E+09 0.297939E+10
March 0.147506E+10 0.00 0.147506E+10 0.658464E+09 0.276610E+10
April 0.202002E+10 7165624.79 0.201285E+10 0.133976E+10 0.218668E+10
May 0.268590E+10 79794157.67 0.260611E+10 0.220191E+10 0.185358E+10
June 0.273305E+10 0.180480E+09 0.255258E+10 0.246391E+10 0.139492E+10
July 0.268421E+10 0.210454E+09 0.247375E+10 0.273526E+10 0.130054E+10
August 0.217288E+10 58739581.33 0.211414E+10 0.225770E+10 0.126951E+10
September 0.163337E+10 481656.94 0.163289E+10 0.127067E+10 0.181031E+10
October 0.115644E+10 0.00 0.115644E+10 0.554862E+09 0.244950E+10
November 0.704943E+09 0.00 0.704943E+09 0.117557E+09 0.290172E+10
December 0.546732E+09 0.00 0.546732E+09 17938774.49 0.372138E+10
           
Annual Sum or Average 0.193603E+11 0.537115E+09 0.188232E+11 0.138568E+11 0.283349E+11
Minimum of Months 0.546732E+09 0.00 0.546732E+09 17938774.49 0.126951E+10
Maximum of Months 0.273305E+10 0.210454E+09 0.260611E+10 0.273526E+10 0.372138E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.689252E+09 0.174748E+09 0.514504E+09 0.261768E+09 0.234399E+10
February 0.114232E+10 0.405433E+09 0.736886E+09 0.772079E+09 0.188283E+10
March 0.188830E+10 0.683582E+09 0.120472E+10 0.159055E+10 0.177698E+10
April 0.283277E+10 0.117706E+10 0.165571E+10 0.287879E+10 0.141629E+10
May 0.311479E+10 0.108294E+10 0.203185E+10 0.331583E+10 0.125244E+10
June 0.360998E+10 0.157073E+10 0.203925E+10 0.412600E+10 0.956524E+09
July 0.347379E+10 0.155924E+10 0.191455E+10 0.414843E+10 0.875051E+09
August 0.341425E+10 0.170800E+10 0.170625E+10 0.422090E+10 0.851890E+09
September 0.244291E+10 0.112669E+10 0.131622E+10 0.269236E+10 0.117232E+10
October 0.164536E+10 0.699123E+09 0.946237E+09 0.151487E+10 0.158646E+10
November 0.780449E+09 0.220329E+09 0.560121E+09 0.432439E+09 0.186895E+10
December 0.661482E+09 0.212951E+09 0.448531E+09 0.326086E+09 0.238278E+10
           
Annual Sum or Average 0.256957E+11 0.106208E+11 0.150748E+11 0.262801E+11 0.183665E+11
Minimum of Months 0.661482E+09 0.174748E+09 0.448531E+09 0.261768E+09 0.851890E+09
Maximum of Months 0.360998E+10 0.170800E+10 0.203925E+10 0.422090E+10 0.238278E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.284278E+10 0.168806E+10 0.115473E+10 0.256653E+10 0.336778E+10
February 0.394869E+10 0.244429E+10 0.150440E+10 0.405266E+10 0.278696E+10
March 0.470276E+10 0.250793E+10 0.219483E+10 0.502131E+10 0.275467E+10
April 0.480505E+10 0.208633E+10 0.271872E+10 0.541392E+10 0.230546E+10
May 0.454006E+10 0.135253E+10 0.318753E+10 0.515504E+10 0.201175E+10
June 0.401972E+10 0.107924E+10 0.294047E+10 0.465405E+10 0.154961E+10
July 0.452980E+10 0.165905E+10 0.287075E+10 0.579475E+10 0.145310E+10
August 0.486670E+10 0.226942E+10 0.259728E+10 0.644337E+10 0.140042E+10
September 0.521816E+10 0.288164E+10 0.233652E+10 0.649334E+10 0.186204E+10
October 0.488433E+10 0.301571E+10 0.186862E+10 0.556861E+10 0.244715E+10
November 0.279463E+10 0.160156E+10 0.119307E+10 0.270055E+10 0.276451E+10
December 0.302144E+10 0.195530E+10 0.106615E+10 0.299557E+10 0.347840E+10
           
Annual Sum or Average 0.501741E+11 0.245411E+11 0.256331E+11 0.568597E+11 0.281819E+11
Minimum of Months 0.279463E+10 0.107924E+10 0.106615E+10 0.256653E+10 0.140042E+10
Maximum of Months 0.521816E+10 0.301571E+10 0.318753E+10 0.649334E+10 0.347840E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.726993E+09 0.214377E+09 0.512616E+09 0.325589E+09 0.236332E+10
February 0.117730E+10 0.442463E+09 0.734839E+09 0.851691E+09 0.190959E+10
March 0.182646E+10 0.616478E+09 0.120998E+10 0.155247E+10 0.181592E+10
April 0.268912E+10 0.102815E+10 0.166096E+10 0.272415E+10 0.148850E+10
May 0.357561E+10 0.145258E+10 0.212303E+10 0.394915E+10 0.131328E+10
June 0.332783E+10 0.129209E+10 0.203574E+10 0.375296E+10 0.100816E+10
July 0.424812E+10 0.223303E+10 0.201509E+10 0.525558E+10 0.958650E+09
August 0.351421E+10 0.179446E+10 0.171975E+10 0.441456E+10 0.931240E+09
September 0.276947E+10 0.132885E+10 0.144062E+10 0.320499E+10 0.124057E+10
October 0.162922E+10 0.663831E+09 0.965393E+09 0.152430E+10 0.163222E+10
November 0.785171E+09 0.221451E+09 0.563720E+09 0.453129E+09 0.187924E+10
December 0.682091E+09 0.233735E+09 0.448356E+09 0.382423E+09 0.240797E+10
           
Annual Sum or Average 0.269516E+11 0.115215E+11 0.154301E+11 0.283910E+11 0.189486E+11
Minimum of Months 0.682091E+09 0.214377E+09 0.448356E+09 0.325589E+09 0.931240E+09
Maximum of Months 0.424812E+10 0.223303E+10 0.212303E+10 0.525558E+10 0.240797E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214460E+09 0.00 0.214460E+09 9286299.12 0.129791E+10
February 0.301411E+09 0.00 0.301411E+09 66822708.06 0.104260E+10
March 0.491662E+09 0.00 0.491662E+09 0.224828E+09 0.947625E+09
April 0.673308E+09 2388428.59 0.670920E+09 0.463019E+09 0.734254E+09
May 0.895257E+09 26596794.15 0.868661E+09 0.753181E+09 0.623249E+09
June 0.910975E+09 60156990.47 0.850818E+09 0.838984E+09 0.468281E+09
July 0.894693E+09 70148169.12 0.824545E+09 0.927299E+09 0.437798E+09
August 0.724260E+09 19578934.08 0.704681E+09 0.762178E+09 0.431202E+09
September 0.544432E+09 160544.72 0.544271E+09 0.424785E+09 0.630354E+09
October 0.385461E+09 0.00 0.385461E+09 0.173903E+09 0.884660E+09
November 0.234970E+09 0.00 0.234970E+09 32193398.15 0.106335E+10
December 0.182235E+09 0.00 0.182235E+09 3773467.59 0.133506E+10
           
Annual Sum or Average 0.645312E+10 0.179030E+09 0.627410E+10 0.468025E+10 0.989634E+10
Minimum of Months 0.182235E+09 0.00 0.182235E+09 3773467.59 0.431202E+09
Maximum of Months 0.910975E+09 70148169.12 0.868661E+09 0.927299E+09 0.133506E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214468E+09 0.00 0.214468E+09 9285410.11 0.129799E+10
February 0.301422E+09 0.00 0.301422E+09 66821561.76 0.104266E+10
March 0.491681E+09 0.00 0.491681E+09 0.224831E+09 0.947685E+09
April 0.673334E+09 2388492.79 0.670946E+09 0.463031E+09 0.734301E+09
May 0.895292E+09 26597509.08 0.868695E+09 0.753202E+09 0.623288E+09
June 0.911011E+09 60158607.51 0.850852E+09 0.839010E+09 0.468309E+09
July 0.894729E+09 70150054.72 0.824579E+09 0.927333E+09 0.437824E+09
August 0.724290E+09 19579460.37 0.704710E+09 0.762207E+09 0.431227E+09
September 0.544454E+09 160549.03 0.544293E+09 0.424797E+09 0.630392E+09
October 0.385475E+09 0.00 0.385475E+09 0.173905E+09 0.884715E+09
November 0.234979E+09 0.00 0.234979E+09 32192153.46 0.106342E+10
December 0.182242E+09 0.00 0.182242E+09 3773046.31 0.133515E+10
           
Annual Sum or Average 0.645338E+10 0.179035E+09 0.627434E+10 0.468039E+10 0.989696E+10
Minimum of Months 0.182242E+09 0.00 0.182242E+09 3773046.31 0.431227E+09
Maximum of Months 0.911011E+09 70150054.72 0.868695E+09 0.927333E+09 0.133515E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214468E+09 0.00 0.214468E+09 9285410.11 0.129799E+10
February 0.301422E+09 0.00 0.301422E+09 66821561.76 0.104266E+10
March 0.491681E+09 0.00 0.491681E+09 0.224831E+09 0.947685E+09
April 0.673334E+09 2388492.79 0.670946E+09 0.463031E+09 0.734301E+09
May 0.895292E+09 26597509.08 0.868695E+09 0.753202E+09 0.623288E+09
June 0.911011E+09 60158607.51 0.850852E+09 0.839010E+09 0.468309E+09
July 0.894729E+09 70150054.72 0.824579E+09 0.927333E+09 0.437824E+09
August 0.724290E+09 19579460.37 0.704710E+09 0.762207E+09 0.431227E+09
September 0.544454E+09 160549.03 0.544293E+09 0.424797E+09 0.630392E+09
October 0.385475E+09 0.00 0.385475E+09 0.173905E+09 0.884715E+09
November 0.234979E+09 0.00 0.234979E+09 32192153.46 0.106342E+10
December 0.182242E+09 0.00 0.182242E+09 3773046.31 0.133515E+10
           
Annual Sum or Average 0.645338E+10 0.179035E+09 0.627434E+10 0.468039E+10 0.989696E+10
Minimum of Months 0.182242E+09 0.00 0.182242E+09 3773046.31 0.431227E+09
Maximum of Months 0.911011E+09 70150054.72 0.868695E+09 0.927333E+09 0.133515E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.663026E+09 0.168099E+09 0.494928E+09 0.244392E+09 0.237101E+10
February 0.109885E+10 0.390005E+09 0.708849E+09 0.734759E+09 0.190940E+10
March 0.181645E+10 0.657569E+09 0.115888E+10 0.153900E+10 0.178408E+10
April 0.272498E+10 0.113226E+10 0.159271E+10 0.278980E+10 0.141173E+10
May 0.299628E+10 0.104173E+10 0.195454E+10 0.321900E+10 0.124014E+10
June 0.347262E+10 0.151096E+10 0.196167E+10 0.399965E+10 0.953371E+09
July 0.334161E+10 0.149990E+10 0.184171E+10 0.401809E+10 0.869095E+09
August 0.328434E+10 0.164301E+10 0.164133E+10 0.407882E+10 0.858897E+09
September 0.234995E+10 0.108382E+10 0.126614E+10 0.259019E+10 0.119980E+10
October 0.158275E+10 0.672519E+09 0.910234E+09 0.143347E+10 0.167484E+10
November 0.750753E+09 0.211944E+09 0.538809E+09 0.393436E+09 0.198059E+10
December 0.636312E+09 0.204847E+09 0.431465E+09 0.299263E+09 0.246736E+10
           
Annual Sum or Average 0.247179E+11 0.102167E+11 0.145013E+11 0.253399E+11 0.187203E+11
Minimum of Months 0.636312E+09 0.168099E+09 0.431465E+09 0.244392E+09 0.858897E+09
Maximum of Months 0.347262E+10 0.164301E+10 0.196167E+10 0.407882E+10 0.246736E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 26215457.77 6646464.26 19568993.51 9663026.36 93747770.03
February 43447695.55 15420448.04 28027247.51 29051702.04 75496112.59
March 71820864.26 25999666.84 45821197.41 60850592.22 70541042.49
April 0.107743E+09 44768711.23 62974500.44 0.110306E+09 55818466.28
May 0.118470E+09 41189145.54 77280911.26 0.127276E+09 49033925.97
June 0.137304E+09 59741882.25 77562527.03 0.158142E+09 37695446.64
July 0.132124E+09 59304779.97 72819649.84 0.158872E+09 34363224.73
August 0.129860E+09 64963042.56 64896715.45 0.161273E+09 33960027.02
September 92915081.92 42853079.58 50062002.35 0.102414E+09 47438992.22
October 62580638.09 26590795.31 35989842.77 56678093.25 66221533.97
November 29684100.24 8380085.62 21304014.63 15556101.99 78310688.16
December 25159213.77 8099466.92 17059746.85 11832571.64 97557014.70
           
Annual Sum or Average 0.977325E+09 0.403958E+09 0.573367E+09 0.100192E+10 0.740184E+09
Minimum of Months 25159213.77 6646464.26 17059746.85 9663026.36 33960027.02
Maximum of Months 0.137304E+09 64963042.56 77562527.03 0.161273E+09 97557014.70



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.947578E+09 0.562675E+09 0.384903E+09 0.862266E+09 0.117424E+10
February 0.131621E+10 0.814748E+09 0.501459E+09 0.136017E+10 0.985100E+09
March 0.156756E+10 0.835959E+09 0.731600E+09 0.169699E+10 0.960237E+09
April 0.160166E+10 0.695428E+09 0.906231E+09 0.183466E+10 0.786208E+09
May 0.151333E+10 0.450834E+09 0.106250E+10 0.175219E+10 0.679557E+09
June 0.133989E+10 0.359740E+09 0.980149E+09 0.158267E+10 0.522261E+09
July 0.150991E+10 0.553007E+09 0.956908E+09 0.195501E+10 0.497837E+09
August 0.162221E+10 0.756459E+09 0.865751E+09 0.216548E+10 0.488596E+09
September 0.173936E+10 0.960528E+09 0.778832E+09 0.217349E+10 0.664421E+09
October 0.162808E+10 0.100522E+10 0.622864E+09 0.185759E+10 0.897136E+09
November 0.931525E+09 0.533841E+09 0.397684E+09 0.897813E+09 0.100268E+10
December 0.100713E+10 0.651752E+09 0.355377E+09 0.998324E+09 0.123812E+10
           
Annual Sum or Average 0.167244E+11 0.818019E+10 0.854426E+10 0.191367E+11 0.989639E+10
Minimum of Months 0.931525E+09 0.359740E+09 0.355377E+09 0.862266E+09 0.488596E+09
Maximum of Months 0.173936E+10 0.100522E+10 0.106250E+10 0.217349E+10 0.123812E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.947578E+09 0.562675E+09 0.384903E+09 0.862266E+09 0.117424E+10
February 0.131621E+10 0.814748E+09 0.501459E+09 0.136017E+10 0.985100E+09
March 0.156756E+10 0.835959E+09 0.731600E+09 0.169699E+10 0.960237E+09
April 0.160166E+10 0.695428E+09 0.906231E+09 0.183466E+10 0.786208E+09
May 0.151333E+10 0.450834E+09 0.106250E+10 0.175219E+10 0.679557E+09
June 0.133989E+10 0.359740E+09 0.980149E+09 0.158267E+10 0.522261E+09
July 0.150991E+10 0.553007E+09 0.956908E+09 0.195501E+10 0.497837E+09
August 0.162221E+10 0.756459E+09 0.865751E+09 0.216548E+10 0.488596E+09
September 0.173936E+10 0.960528E+09 0.778832E+09 0.217349E+10 0.664421E+09
October 0.162808E+10 0.100522E+10 0.622864E+09 0.185759E+10 0.897136E+09
November 0.931525E+09 0.533841E+09 0.397684E+09 0.897813E+09 0.100268E+10
December 0.100713E+10 0.651752E+09 0.355377E+09 0.998324E+09 0.123812E+10
           
Annual Sum or Average 0.167244E+11 0.818019E+10 0.854426E+10 0.191367E+11 0.989639E+10
Minimum of Months 0.931525E+09 0.359740E+09 0.355377E+09 0.862266E+09 0.488596E+09
Maximum of Months 0.173936E+10 0.100522E+10 0.106250E+10 0.217349E+10 0.123812E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.947518E+09 0.562639E+09 0.384879E+09 0.862211E+09 0.117417E+10
February 0.131612E+10 0.814697E+09 0.501427E+09 0.136008E+10 0.985038E+09
March 0.156746E+10 0.835906E+09 0.731554E+09 0.169688E+10 0.960176E+09
April 0.160156E+10 0.695384E+09 0.906174E+09 0.183455E+10 0.786158E+09
May 0.151324E+10 0.450805E+09 0.106243E+10 0.175208E+10 0.679514E+09
June 0.133981E+10 0.359718E+09 0.980087E+09 0.158257E+10 0.522228E+09
July 0.150982E+10 0.552972E+09 0.956847E+09 0.195489E+10 0.497806E+09
August 0.162211E+10 0.756411E+09 0.865696E+09 0.216535E+10 0.488565E+09
September 0.173925E+10 0.960467E+09 0.778782E+09 0.217335E+10 0.664379E+09
October 0.162798E+10 0.100515E+10 0.622825E+09 0.185747E+10 0.897080E+09
November 0.931466E+09 0.533807E+09 0.397659E+09 0.897756E+09 0.100262E+10
December 0.100707E+10 0.651711E+09 0.355355E+09 0.998261E+09 0.123804E+10
           
Annual Sum or Average 0.167234E+11 0.817967E+10 0.854372E+10 0.191355E+11 0.989577E+10
Minimum of Months 0.931466E+09 0.359718E+09 0.355355E+09 0.862211E+09 0.488565E+09
Maximum of Months 0.173925E+10 0.100515E+10 0.106243E+10 0.217335E+10 0.123804E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.699333E+09 0.206220E+09 0.493113E+09 0.312469E+09 0.239402E+10
February 0.113251E+10 0.425627E+09 0.706881E+09 0.821660E+09 0.194181E+10
March 0.175696E+10 0.593020E+09 0.116394E+10 0.150890E+10 0.182813E+10
April 0.258680E+10 0.989031E+09 0.159777E+10 0.265284E+10 0.148086E+10
May 0.343957E+10 0.139731E+10 0.204226E+10 0.383561E+10 0.131715E+10
June 0.320122E+10 0.124292E+10 0.195829E+10 0.364900E+10 0.100610E+10
July 0.408649E+10 0.214806E+10 0.193843E+10 0.508987E+10 0.972582E+09
August 0.338050E+10 0.172618E+10 0.165433E+10 0.427079E+10 0.946963E+09
September 0.266410E+10 0.127829E+10 0.138581E+10 0.308657E+10 0.128147E+10
October 0.156724E+10 0.638572E+09 0.928664E+09 0.144720E+10 0.172784E+10
November 0.755297E+09 0.213025E+09 0.542273E+09 0.418338E+09 0.199363E+10
December 0.656139E+09 0.224842E+09 0.431298E+09 0.362023E+09 0.249636E+10
           
Annual Sum or Average 0.259262E+11 0.110831E+11 0.148431E+11 0.274553E+11 0.193869E+11
Minimum of Months 0.656139E+09 0.206220E+09 0.431298E+09 0.312469E+09 0.946963E+09
Maximum of Months 0.408649E+10 0.214806E+10 0.204226E+10 0.508987E+10 0.249636E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 27650915.06 8153722.29 19497192.77 12354671.65 94657381.76
February 44778247.18 16828866.23 27949380.95 32487535.69 76777418.79
March 69468548.27 23447401.83 46021146.44 59660417.24 72282498.59
April 0.102280E+09 39105269.61 63174340.74 0.104891E+09 58552016.51
May 0.135997E+09 55248024.25 80749036.80 0.151656E+09 52078985.71
June 0.126573E+09 49143820.67 77429023.39 0.144278E+09 39780408.49
July 0.161576E+09 84932032.48 76643484.53 0.201248E+09 38454995.23
August 0.133662E+09 68251229.16 65410395.83 0.168863E+09 37442052.15
September 0.105336E+09 50542232.62 54793546.51 0.122040E+09 50668270.38
October 61966936.11 25248478.46 36718457.65 57220722.19 68317204.82
November 29863697.12 8422773.34 21440923.78 16540623.97 78826529.70
December 25943078.99 8890003.39 17053075.60 14314000.34 98703962.12
           
Annual Sum or Average 0.102509E+10 0.438214E+09 0.586880E+09 0.108555E+10 0.766542E+09
Minimum of Months 25943078.99 8153722.29 17053075.60 12354671.65 37442052.15
Maximum of Months 0.161576E+09 84932032.48 80749036.80 0.201248E+09 98703962.12



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.643410E+09 0.00 0.643410E+09 24487282.78 0.393143E+10
February 0.904276E+09 0.00 0.904276E+09 0.181135E+09 0.319668E+10
March 0.147506E+10 0.00 0.147506E+10 0.608958E+09 0.297818E+10
April 0.202002E+10 7165624.79 0.201285E+10 0.129563E+10 0.232662E+10
May 0.268590E+10 79794157.67 0.260611E+10 0.216927E+10 0.194886E+10
June 0.273305E+10 0.180480E+09 0.255258E+10 0.244768E+10 0.145326E+10
July 0.268421E+10 0.210454E+09 0.247375E+10 0.272759E+10 0.135136E+10
August 0.217288E+10 58739581.33 0.211414E+10 0.224508E+10 0.132578E+10
September 0.163337E+10 481656.94 0.163289E+10 0.124106E+10 0.192457E+10
October 0.115644E+10 0.00 0.115644E+10 0.504071E+09 0.266591E+10
November 0.704943E+09 0.00 0.704943E+09 93668483.90 0.316094E+10
December 0.546732E+09 0.00 0.546732E+09 10634844.69 0.399814E+10
           
Annual Sum or Average 0.193603E+11 0.537115E+09 0.188232E+11 0.135493E+11 0.302617E+11
Minimum of Months 0.546732E+09 0.00 0.546732E+09 10634844.69 0.132578E+10
Maximum of Months 0.273305E+10 0.210454E+09 0.260611E+10 0.272759E+10 0.399814E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.689252E+09 0.174748E+09 0.514504E+09 0.246181E+09 0.248847E+10
February 0.114232E+10 0.405433E+09 0.736886E+09 0.737260E+09 0.201880E+10
March 0.188830E+10 0.683582E+09 0.120472E+10 0.154538E+10 0.190958E+10
April 0.283277E+10 0.117706E+10 0.165571E+10 0.284236E+10 0.149830E+10
May 0.311479E+10 0.108294E+10 0.203185E+10 0.329106E+10 0.131210E+10
June 0.360998E+10 0.157073E+10 0.203925E+10 0.411361E+10 0.993905E+09
July 0.347379E+10 0.155924E+10 0.191455E+10 0.413724E+10 0.905993E+09
August 0.341425E+10 0.170800E+10 0.170625E+10 0.420862E+10 0.885768E+09
September 0.244291E+10 0.112669E+10 0.131622E+10 0.266660E+10 0.124039E+10
October 0.164536E+10 0.699123E+09 0.946237E+09 0.147159E+10 0.171879E+10
November 0.780449E+09 0.220329E+09 0.560121E+09 0.402122E+09 0.203653E+10
December 0.661482E+09 0.212951E+09 0.448531E+09 0.306183E+09 0.255974E+10
           
Annual Sum or Average 0.256957E+11 0.106208E+11 0.150748E+11 0.259682E+11 0.195684E+11
Minimum of Months 0.661482E+09 0.174748E+09 0.448531E+09 0.246181E+09 0.885768E+09
Maximum of Months 0.360998E+10 0.170800E+10 0.203925E+10 0.420862E+10 0.255974E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.284278E+10 0.168806E+10 0.115473E+10 0.252404E+10 0.357701E+10
February 0.394869E+10 0.244429E+10 0.150440E+10 0.400013E+10 0.297958E+10
March 0.470276E+10 0.250793E+10 0.219483E+10 0.497668E+10 0.295227E+10
April 0.480505E+10 0.208633E+10 0.271872E+10 0.538273E+10 0.243827E+10
May 0.454006E+10 0.135253E+10 0.318753E+10 0.513831E+10 0.211207E+10
June 0.401972E+10 0.107924E+10 0.294047E+10 0.465121E+10 0.161631E+10
July 0.452980E+10 0.165905E+10 0.287075E+10 0.579791E+10 0.150940E+10
August 0.486670E+10 0.226942E+10 0.259728E+10 0.644417E+10 0.146000E+10
September 0.521816E+10 0.288164E+10 0.233652E+10 0.647241E+10 0.196585E+10
October 0.488433E+10 0.301571E+10 0.186862E+10 0.552181E+10 0.263842E+10
November 0.279463E+10 0.160156E+10 0.119307E+10 0.264703E+10 0.299658E+10
December 0.302144E+10 0.195530E+10 0.106615E+10 0.295158E+10 0.372963E+10
           
Annual Sum or Average 0.501741E+11 0.245411E+11 0.256331E+11 0.565080E+11 0.299754E+11
Minimum of Months 0.279463E+10 0.107924E+10 0.106615E+10 0.252404E+10 0.146000E+10
Maximum of Months 0.521816E+10 0.301571E+10 0.318753E+10 0.647241E+10 0.372963E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.726993E+09 0.214377E+09 0.512616E+09 0.313710E+09 0.250948E+10
February 0.117730E+10 0.442463E+09 0.734839E+09 0.828053E+09 0.204559E+10
March 0.182646E+10 0.616478E+09 0.120998E+10 0.152034E+10 0.195173E+10
April 0.268912E+10 0.102815E+10 0.166096E+10 0.269858E+10 0.157906E+10
May 0.357561E+10 0.145258E+10 0.212303E+10 0.393684E+10 0.138011E+10
June 0.332783E+10 0.129209E+10 0.203574E+10 0.375140E+10 0.105226E+10
July 0.424812E+10 0.223303E+10 0.201509E+10 0.525955E+10 0.996633E+09
August 0.351421E+10 0.179446E+10 0.171975E+10 0.441440E+10 0.971202E+09
September 0.276947E+10 0.132885E+10 0.144062E+10 0.319010E+10 0.131253E+10
October 0.162922E+10 0.663831E+09 0.965393E+09 0.149173E+10 0.177054E+10
November 0.785171E+09 0.221451E+09 0.563720E+09 0.429863E+09 0.204327E+10
December 0.682091E+09 0.233735E+09 0.448356E+09 0.369926E+09 0.258450E+10
           
Annual Sum or Average 0.269516E+11 0.115215E+11 0.154301E+11 0.282045E+11 0.201969E+11
Minimum of Months 0.682091E+09 0.214377E+09 0.448356E+09 0.313710E+09 0.971202E+09
Maximum of Months 0.424812E+10 0.223303E+10 0.212303E+10 0.525955E+10 0.258450E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 11.97 1381.90 240.22 0.00 240.22 0.00 0.00
February 85.44 1231.56 373.79 0.00 373.79 0.00 0.00
March 245.84 1032.74 550.72 0.00 550.72 0.00 0.00
April 516.88 843.63 779.33 2.76 776.56 0.00 0.00
May 822.10 692.05 1002.80 29.79 973.01 0.00 0.00
June 950.58 538.16 1054.42 69.63 984.79 0.00 0.00
July 1021.23 485.57 1002.17 78.57 923.59 0.00 0.00
August 842.93 473.98 811.26 21.93 789.33 0.00 0.00
September 490.23 698.42 630.16 0.19 629.97 0.00 0.00
October 207.16 914.54 431.76 0.00 431.76 0.00 0.00
November 45.35 1119.49 271.97 0.00 271.97 0.00 0.00
December 6.70 1389.40 204.13 0.00 204.13 0.00 0.00
               
Annual Sum or Average 439.40 898.49 613.91 17.03 596.88 0.00 0.00
Minimum of Months 6.70 473.98 204.13 0.00 204.13 0.00 0.00
Maximum of Months 1021.23 1389.40 1054.42 78.57 984.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 97.73 875.15 257.34 65.24 192.09 0.00 0.00
February 319.15 778.29 472.19 167.59 304.60 0.00 0.00
March 593.84 663.45 705.01 255.22 449.79 0.00 0.00
April 1110.64 546.41 1092.89 454.11 638.78 0.00 0.00
May 1237.99 467.61 1162.93 404.32 758.61 0.00 0.00
June 1591.82 369.03 1392.74 605.99 786.75 0.00 0.00
July 1548.85 326.71 1296.96 582.15 714.81 0.00 0.00
August 1575.90 318.06 1274.74 637.70 637.04 0.00 0.00
September 1038.72 452.28 942.48 434.68 507.80 0.00 0.00
October 565.59 592.31 614.31 261.02 353.28 0.00 0.00
November 166.84 721.05 301.10 85.00 216.10 0.00 0.00
December 121.75 889.63 246.97 79.51 167.46 0.00 0.00
               
Annual Sum or Average 833.34 582.40 814.80 336.78 478.02 0.00 0.00
Minimum of Months 97.73 318.06 246.97 65.24 167.46 0.00 0.00
Maximum of Months 1591.82 889.63 1392.74 637.70 786.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 958.23 1257.39 1061.37 630.25 431.13 0.00 0.00
February 1675.21 1152.02 1632.23 1010.37 621.86 0.00 0.00
March 1874.74 1028.48 1755.81 936.35 819.45 0.00 0.00
April 2088.70 889.45 1853.80 804.91 1048.89 0.00 0.00
May 1924.67 751.10 1695.06 504.98 1190.09 0.00 0.00
June 1795.54 597.85 1550.82 416.37 1134.44 0.00 0.00
July 2163.51 542.53 1691.23 619.42 1071.81 0.00 0.00
August 2405.68 522.86 1817.02 847.31 969.71 0.00 0.00
September 2505.15 718.38 2013.18 1111.74 901.44 0.00 0.00
October 2079.08 913.66 1823.60 1125.94 697.66 0.00 0.00
November 1041.88 1066.55 1078.17 617.88 460.29 0.00 0.00
December 1118.42 1298.68 1128.08 730.02 398.05 0.00 0.00
               
Annual Sum or Average 1803.01 893.64 1591.01 778.19 812.82 0.00 0.00
Minimum of Months 958.23 522.86 1061.37 416.37 398.05 0.00 0.00
Maximum of Months 2505.15 1298.68 2013.18 1125.94 1190.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 121.56 882.36 271.43 80.04 191.39 0.00 0.00
February 352.05 789.35 486.65 182.90 303.75 0.00 0.00
March 579.63 677.99 681.92 230.17 451.75 0.00 0.00
April 1050.98 574.27 1037.47 396.66 640.80 0.00 0.00
May 1474.44 490.32 1334.98 542.33 792.65 0.00 0.00
June 1447.90 388.95 1283.89 498.49 785.40 0.00 0.00
July 1962.21 357.92 1586.07 833.72 752.35 0.00 0.00
August 1648.21 347.69 1312.06 669.97 642.08 0.00 0.00
September 1236.49 478.61 1068.47 512.67 555.79 0.00 0.00
October 569.11 609.40 608.28 247.85 360.44 0.00 0.00
November 174.82 725.02 302.92 85.44 217.48 0.00 0.00
December 142.78 899.03 254.66 87.27 167.40 0.00 0.00
               
Annual Sum or Average 900.27 600.86 854.63 365.34 489.29 0.00 0.00
Minimum of Months 121.56 347.69 254.66 80.04 167.40 0.00 0.00
Maximum of Months 1962.21 899.03 1586.07 833.72 792.65 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 10.40 1453.81 240.22 0.00 240.22 0.00 0.00
February 82.86 1292.96 373.78 0.00 373.78 0.00 0.00
March 251.83 1061.45 550.71 0.00 550.71 0.00 0.00
April 535.91 849.87 779.31 2.76 776.55 0.00 0.00
May 843.63 698.11 1002.78 29.79 972.99 0.00 0.00
June 971.07 542.01 1054.40 69.63 984.77 0.00 0.00
July 1038.67 490.38 1002.15 78.57 923.57 0.00 0.00
August 853.72 483.00 811.25 21.93 789.32 0.00 0.00
September 491.66 729.61 630.15 0.19 629.96 0.00 0.00
October 194.78 990.92 431.75 0.00 431.75 0.00 0.00
November 37.26 1230.78 271.96 0.00 271.96 0.00 0.00
December 4.23 1495.43 204.12 0.00 204.12 0.00 0.00
               
Annual Sum or Average 445.24 941.47 613.90 17.03 596.87 0.00 0.00
Minimum of Months 4.23 483.00 204.12 0.00 204.12 0.00 0.00
Maximum of Months 1038.67 1495.43 1054.40 78.57 984.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 94.85 920.24 257.33 65.24 192.09 0.00 0.00
February 315.73 820.48 472.18 167.59 304.59 0.00 0.00
March 597.32 692.44 705.00 255.22 449.79 0.00 0.00
April 1118.87 566.18 1092.87 454.10 638.77 0.00 0.00
May 1249.36 481.32 1162.91 404.32 758.60 0.00 0.00
June 1604.09 382.36 1392.72 605.98 786.74 0.00 0.00
July 1559.50 337.31 1296.95 582.14 714.80 0.00 0.00
August 1583.07 333.35 1274.72 637.68 637.03 0.00 0.00
September 1038.81 481.19 942.47 434.67 507.79 0.00 0.00
October 556.36 650.04 614.30 261.02 353.28 0.00 0.00
November 157.79 794.33 301.09 85.00 216.09 0.00 0.00
December 116.15 957.63 246.97 79.51 167.46 0.00 0.00
               
Annual Sum or Average 835.29 617.09 814.79 336.78 478.01 0.00 0.00
Minimum of Months 94.85 333.35 246.97 65.24 167.46 0.00 0.00
Maximum of Months 1604.09 957.63 1392.72 637.68 786.74 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 965.78 1315.21 1061.33 630.22 431.11 0.00 0.00
February 1686.68 1221.58 1632.17 1010.33 621.84 0.00 0.00
March 1900.71 1075.51 1755.74 936.31 819.43 0.00 0.00
April 2123.41 909.94 1853.73 804.88 1048.86 0.00 0.00
May 1962.54 761.14 1695.00 504.96 1190.05 0.00 0.00
June 1831.75 604.46 1550.77 416.36 1134.41 0.00 0.00
July 2189.71 557.60 1691.18 619.39 1071.78 0.00 0.00
August 2425.45 547.25 1816.95 847.27 969.68 0.00 0.00
September 2515.56 768.99 2013.11 1111.70 901.41 0.00 0.00
October 2080.59 1004.84 1823.53 1125.89 697.64 0.00 0.00
November 1039.11 1160.48 1078.13 617.86 460.27 0.00 0.00
December 1118.17 1386.76 1128.03 729.99 398.04 0.00 0.00
               
Annual Sum or Average 1820.42 941.42 1590.95 778.16 812.79 0.00 0.00
Minimum of Months 965.78 547.25 1061.33 416.36 398.04 0.00 0.00
Maximum of Months 2515.56 1386.76 2013.11 1125.89 1190.05 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 121.28 929.17 271.42 80.04 191.39 0.00 0.00
February 353.07 834.40 486.64 182.89 303.75 0.00 0.00
March 585.63 709.53 681.91 230.16 451.75 0.00 0.00
April 1063.94 593.91 1037.45 396.66 640.80 0.00 0.00
May 1488.67 511.21 1334.96 542.32 792.64 0.00 0.00
June 1463.45 403.50 1283.87 498.48 785.39 0.00 0.00
July 1975.48 377.48 1586.04 833.70 752.34 0.00 0.00
August 1657.58 367.53 1312.04 669.96 642.08 0.00 0.00
September 1237.89 513.94 1068.45 512.67 555.79 0.00 0.00
October 561.69 670.61 608.27 247.84 360.43 0.00 0.00
November 167.78 799.56 302.92 85.43 217.48 0.00 0.00
December 140.51 968.89 254.66 87.27 167.39 0.00 0.00
               
Annual Sum or Average 905.02 639.06 854.62 365.34 489.28 0.00 0.00
Minimum of Months 121.28 367.53 254.66 80.04 167.39 0.00 0.00
Maximum of Months 1975.48 968.89 1586.04 833.70 792.64 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.14 1467.83 240.22 0.00 240.22 0.00 0.00
February 74.87 1321.38 373.79 0.00 373.79 0.00 0.00
March 227.36 1111.92 550.72 0.00 550.72 0.00 0.00
April 499.86 897.62 779.33 2.76 776.56 0.00 0.00
May 809.91 727.62 1002.80 29.79 973.01 0.00 0.00
June 944.32 560.67 1054.42 69.63 984.79 0.00 0.00
July 1018.37 504.54 1002.17 78.57 923.59 0.00 0.00
August 838.22 494.99 811.26 21.93 789.33 0.00 0.00
September 478.80 742.50 630.16 0.19 629.97 0.00 0.00
October 188.20 995.34 431.76 0.00 431.76 0.00 0.00
November 36.14 1219.50 271.97 0.00 271.97 0.00 0.00
December 3.97 1492.73 204.13 0.00 204.13 0.00 0.00
               
Annual Sum or Average 429.64 959.59 613.91 17.03 596.88 0.00 0.00
Minimum of Months 3.97 494.99 204.13 0.00 204.13 0.00 0.00
Maximum of Months 1018.37 1492.73 1054.42 78.57 984.79 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 91.91 929.09 257.34 65.24 192.09 0.00 0.00
February 304.75 834.49 472.19 167.59 304.60 0.00 0.00
March 576.98 712.95 705.01 255.22 449.79 0.00 0.00
April 1096.59 578.05 1092.89 454.11 638.78 0.00 0.00
May 1228.74 489.88 1162.93 404.32 758.61 0.00 0.00
June 1587.04 383.45 1392.74 605.99 786.75 0.00 0.00
July 1544.67 338.26 1296.96 582.15 714.81 0.00 0.00
August 1571.32 330.71 1274.74 637.70 637.04 0.00 0.00
September 1028.78 478.55 942.48 434.68 507.80 0.00 0.00
October 549.43 641.72 614.31 261.02 353.28 0.00 0.00
November 155.14 785.70 301.10 85.00 216.10 0.00 0.00
December 114.32 955.70 246.97 79.51 167.46 0.00 0.00
               
Annual Sum or Average 823.45 620.51 814.80 336.78 478.02 0.00 0.00
Minimum of Months 91.91 330.71 246.97 65.24 167.46 0.00 0.00
Maximum of Months 1587.04 955.70 1392.74 637.70 786.75 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 942.37 1335.50 1061.37 630.25 431.13 0.00 0.00
February 1653.49 1231.64 1632.23 1010.37 621.86 0.00 0.00
March 1858.08 1102.25 1755.81 936.35 819.45 0.00 0.00
April 2076.67 940.69 1853.80 804.91 1048.89 0.00 0.00
May 1918.43 788.56 1695.06 504.98 1190.09 0.00 0.00
June 1794.45 623.58 1550.82 416.37 1134.44 0.00 0.00
July 2164.69 563.55 1691.23 619.42 1071.81 0.00 0.00
August 2405.98 545.10 1817.02 847.31 969.71 0.00 0.00
September 2497.07 758.43 2013.18 1111.74 901.44 0.00 0.00
October 2061.61 985.07 1823.60 1125.94 697.66 0.00 0.00
November 1021.23 1156.09 1078.17 617.88 460.29 0.00 0.00
December 1101.99 1392.48 1128.08 730.02 398.05 0.00 0.00
               
Annual Sum or Average 1791.86 950.51 1591.01 778.19 812.82 0.00 0.00
Minimum of Months 942.37 545.10 1061.37 416.37 398.05 0.00 0.00
Maximum of Months 2497.07 1392.48 2013.18 1125.94 1190.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 117.13 936.93 271.43 80.04 191.39 0.00 0.00
February 342.28 845.56 486.65 182.90 303.75 0.00 0.00
March 567.63 728.69 681.92 230.17 451.75 0.00 0.00
April 1041.12 609.21 1037.47 396.66 640.80 0.00 0.00
May 1469.85 515.27 1334.98 542.33 792.65 0.00 0.00
June 1447.30 405.97 1283.89 498.49 785.40 0.00 0.00
July 1963.69 372.10 1586.07 833.72 752.35 0.00 0.00
August 1648.15 362.61 1312.06 669.97 642.08 0.00 0.00
September 1230.75 506.38 1068.47 512.67 555.79 0.00 0.00
October 556.95 661.04 608.28 247.85 360.44 0.00 0.00
November 165.84 788.30 302.92 85.44 217.48 0.00 0.00
December 138.11 964.94 254.66 87.27 167.40 0.00 0.00
               
Annual Sum or Average 894.36 640.44 854.63 365.34 489.29 0.00 0.00
Minimum of Months 117.13 362.61 254.66 80.04 167.40 0.00 0.00
Maximum of Months 1963.69 964.94 1586.07 833.72 792.65 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 32059367.27 0.370127E+10 0.643410E+09 0.00 0.643410E+09 0.00 0.00
February 0.206707E+09 0.297939E+10 0.904276E+09 0.00 0.904276E+09 0.00 0.00
March 0.658464E+09 0.276610E+10 0.147506E+10 0.00 0.147506E+10 0.00 0.00
April 0.133976E+10 0.218668E+10 0.202002E+10 7165624.79 0.201285E+10 0.00 0.00
May 0.220191E+10 0.185358E+10 0.268590E+10 79794157.67 0.260611E+10 0.00 0.00
June 0.246391E+10 0.139492E+10 0.273305E+10 0.180480E+09 0.255258E+10 0.00 0.00
July 0.273526E+10 0.130054E+10 0.268421E+10 0.210454E+09 0.247375E+10 0.00 0.00
August 0.225770E+10 0.126951E+10 0.217288E+10 58739581.33 0.211414E+10 0.00 0.00
September 0.127067E+10 0.181031E+10 0.163337E+10 481656.94 0.163289E+10 0.00 0.00
October 0.554862E+09 0.244950E+10 0.115644E+10 0.00 0.115644E+10 0.00 0.00
November 0.117557E+09 0.290172E+10 0.704943E+09 0.00 0.704943E+09 0.00 0.00
December 17938774.49 0.372138E+10 0.546732E+09 0.00 0.546732E+09 0.00 0.00
               
Annual Sum or Average 0.138568E+11 0.283349E+11 0.193603E+11 0.537115E+09 0.188232E+11 0.00 0.00
Minimum of Months 17938774.49 0.126951E+10 0.546732E+09 0.00 0.546732E+09 0.00 0.00
Maximum of Months 0.273526E+10 0.372138E+10 0.273305E+10 0.210454E+09 0.260611E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.261768E+09 0.234399E+10 0.689252E+09 0.174748E+09 0.514504E+09 0.00 0.00
February 0.772079E+09 0.188283E+10 0.114232E+10 0.405433E+09 0.736886E+09 0.00 0.00
March 0.159055E+10 0.177698E+10 0.188830E+10 0.683582E+09 0.120472E+10 0.00 0.00
April 0.287879E+10 0.141629E+10 0.283277E+10 0.117706E+10 0.165571E+10 0.00 0.00
May 0.331583E+10 0.125244E+10 0.311479E+10 0.108294E+10 0.203185E+10 0.00 0.00
June 0.412600E+10 0.956524E+09 0.360998E+10 0.157073E+10 0.203925E+10 0.00 0.00
July 0.414843E+10 0.875051E+09 0.347379E+10 0.155924E+10 0.191455E+10 0.00 0.00
August 0.422090E+10 0.851890E+09 0.341425E+10 0.170800E+10 0.170625E+10 0.00 0.00
September 0.269236E+10 0.117232E+10 0.244291E+10 0.112669E+10 0.131622E+10 0.00 0.00
October 0.151487E+10 0.158646E+10 0.164536E+10 0.699123E+09 0.946237E+09 0.00 0.00
November 0.432439E+09 0.186895E+10 0.780449E+09 0.220329E+09 0.560121E+09 0.00 0.00
December 0.326086E+09 0.238278E+10 0.661482E+09 0.212951E+09 0.448531E+09 0.00 0.00
               
Annual Sum or Average 0.262801E+11 0.183665E+11 0.256957E+11 0.106208E+11 0.150748E+11 0.00 0.00
Minimum of Months 0.261768E+09 0.851890E+09 0.661482E+09 0.174748E+09 0.448531E+09 0.00 0.00
Maximum of Months 0.422090E+10 0.238278E+10 0.360998E+10 0.170800E+10 0.203925E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.256653E+10 0.336778E+10 0.284278E+10 0.168806E+10 0.115473E+10 0.00 0.00
February 0.405266E+10 0.278696E+10 0.394869E+10 0.244429E+10 0.150440E+10 0.00 0.00
March 0.502131E+10 0.275467E+10 0.470276E+10 0.250793E+10 0.219483E+10 0.00 0.00
April 0.541392E+10 0.230546E+10 0.480505E+10 0.208633E+10 0.271872E+10 0.00 0.00
May 0.515504E+10 0.201175E+10 0.454006E+10 0.135253E+10 0.318753E+10 0.00 0.00
June 0.465405E+10 0.154961E+10 0.401972E+10 0.107924E+10 0.294047E+10 0.00 0.00
July 0.579475E+10 0.145310E+10 0.452980E+10 0.165905E+10 0.287075E+10 0.00 0.00
August 0.644337E+10 0.140042E+10 0.486670E+10 0.226942E+10 0.259728E+10 0.00 0.00
September 0.649334E+10 0.186204E+10 0.521816E+10 0.288164E+10 0.233652E+10 0.00 0.00
October 0.556861E+10 0.244715E+10 0.488433E+10 0.301571E+10 0.186862E+10 0.00 0.00
November 0.270055E+10 0.276451E+10 0.279463E+10 0.160156E+10 0.119307E+10 0.00 0.00
December 0.299557E+10 0.347840E+10 0.302144E+10 0.195530E+10 0.106615E+10 0.00 0.00
               
Annual Sum or Average 0.568597E+11 0.281819E+11 0.501741E+11 0.245411E+11 0.256331E+11 0.00 0.00
Minimum of Months 0.256653E+10 0.140042E+10 0.279463E+10 0.107924E+10 0.106615E+10 0.00 0.00
Maximum of Months 0.649334E+10 0.347840E+10 0.521816E+10 0.301571E+10 0.318753E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.325589E+09 0.236332E+10 0.726993E+09 0.214377E+09 0.512616E+09 0.00 0.00
February 0.851691E+09 0.190959E+10 0.117730E+10 0.442463E+09 0.734839E+09 0.00 0.00
March 0.155247E+10 0.181592E+10 0.182646E+10 0.616478E+09 0.120998E+10 0.00 0.00
April 0.272415E+10 0.148850E+10 0.268912E+10 0.102815E+10 0.166096E+10 0.00 0.00
May 0.394915E+10 0.131328E+10 0.357561E+10 0.145258E+10 0.212303E+10 0.00 0.00
June 0.375296E+10 0.100816E+10 0.332783E+10 0.129209E+10 0.203574E+10 0.00 0.00
July 0.525558E+10 0.958650E+09 0.424812E+10 0.223303E+10 0.201509E+10 0.00 0.00
August 0.441456E+10 0.931240E+09 0.351421E+10 0.179446E+10 0.171975E+10 0.00 0.00
September 0.320499E+10 0.124057E+10 0.276947E+10 0.132885E+10 0.144062E+10 0.00 0.00
October 0.152430E+10 0.163222E+10 0.162922E+10 0.663831E+09 0.965393E+09 0.00 0.00
November 0.453129E+09 0.187924E+10 0.785171E+09 0.221451E+09 0.563720E+09 0.00 0.00
December 0.382423E+09 0.240797E+10 0.682091E+09 0.233735E+09 0.448356E+09 0.00 0.00
               
Annual Sum or Average 0.283910E+11 0.189486E+11 0.269516E+11 0.115215E+11 0.154301E+11 0.00 0.00
Minimum of Months 0.325589E+09 0.931240E+09 0.682091E+09 0.214377E+09 0.448356E+09 0.00 0.00
Maximum of Months 0.525558E+10 0.240797E+10 0.424812E+10 0.223303E+10 0.212303E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 27857119.35 0.389389E+10 0.643395E+09 0.00 0.643395E+09 0.00 0.00
February 0.200466E+09 0.312792E+10 0.904256E+09 0.00 0.904256E+09 0.00 0.00
March 0.674490E+09 0.284300E+10 0.147502E+10 0.00 0.147502E+10 0.00 0.00
April 0.138908E+10 0.220286E+10 0.201998E+10 7165414.18 0.201281E+10 0.00 0.00
May 0.225959E+10 0.186982E+10 0.268584E+10 79791812.30 0.260605E+10 0.00 0.00
June 0.251700E+10 0.140490E+10 0.273300E+10 0.180474E+09 0.255252E+10 0.00 0.00
July 0.278196E+10 0.131345E+10 0.268415E+10 0.210448E+09 0.247370E+10 0.00 0.00
August 0.228659E+10 0.129366E+10 0.217284E+10 58737854.82 0.211410E+10 0.00 0.00
September 0.127438E+10 0.189114E+10 0.163334E+10 481642.78 0.163286E+10 0.00 0.00
October 0.521712E+09 0.265409E+10 0.115641E+10 0.00 0.115641E+10 0.00 0.00
November 96577705.07 0.319019E+10 0.704927E+09 0.00 0.704927E+09 0.00 0.00
December 11319560.20 0.400535E+10 0.546720E+09 0.00 0.546720E+09 0.00 0.00
               
Annual Sum or Average 0.140410E+11 0.296903E+11 0.193599E+11 0.537099E+09 0.188228E+11 0.00 0.00
Minimum of Months 11319560.20 0.129366E+10 0.546720E+09 0.00 0.546720E+09 0.00 0.00
Maximum of Months 0.278196E+10 0.400535E+10 0.273300E+10 0.210448E+09 0.260605E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.254055E+09 0.246476E+10 0.689242E+09 0.174745E+09 0.514497E+09 0.00 0.00
February 0.763811E+09 0.198490E+10 0.114230E+10 0.405425E+09 0.736876E+09 0.00 0.00
March 0.159985E+10 0.185462E+10 0.188827E+10 0.683568E+09 0.120470E+10 0.00 0.00
April 0.290011E+10 0.146755E+10 0.283272E+10 0.117703E+10 0.165569E+10 0.00 0.00
May 0.334627E+10 0.128917E+10 0.311475E+10 0.108292E+10 0.203182E+10 0.00 0.00
June 0.415779E+10 0.991067E+09 0.360993E+10 0.157070E+10 0.203923E+10 0.00 0.00
July 0.417696E+10 0.903458E+09 0.347374E+10 0.155921E+10 0.191453E+10 0.00 0.00
August 0.424009E+10 0.892857E+09 0.341420E+10 0.170797E+10 0.170623E+10 0.00 0.00
September 0.269260E+10 0.124724E+10 0.244287E+10 0.112667E+10 0.131620E+10 0.00 0.00
October 0.149015E+10 0.174106E+10 0.164533E+10 0.699110E+09 0.946224E+09 0.00 0.00
November 0.408992E+09 0.205890E+10 0.780437E+09 0.220324E+09 0.560113E+09 0.00 0.00
December 0.311095E+09 0.256491E+10 0.661471E+09 0.212946E+09 0.448525E+09 0.00 0.00
               
Annual Sum or Average 0.263418E+11 0.194605E+11 0.256953E+11 0.106206E+11 0.150746E+11 0.00 0.00
Minimum of Months 0.254055E+09 0.892857E+09 0.661471E+09 0.174745E+09 0.448525E+09 0.00 0.00
Maximum of Months 0.424009E+10 0.256491E+10 0.360993E+10 0.170797E+10 0.203923E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.258674E+10 0.352265E+10 0.284267E+10 0.168799E+10 0.115468E+10 0.00 0.00
February 0.408041E+10 0.295524E+10 0.394854E+10 0.244419E+10 0.150435E+10 0.00 0.00
March 0.509086E+10 0.288065E+10 0.470258E+10 0.250782E+10 0.219475E+10 0.00 0.00
April 0.550387E+10 0.235857E+10 0.480488E+10 0.208624E+10 0.271864E+10 0.00 0.00
May 0.525647E+10 0.203863E+10 0.453990E+10 0.135247E+10 0.318743E+10 0.00 0.00
June 0.474791E+10 0.156675E+10 0.401958E+10 0.107920E+10 0.294039E+10 0.00 0.00
July 0.586492E+10 0.149348E+10 0.452965E+10 0.165899E+10 0.287066E+10 0.00 0.00
August 0.649632E+10 0.146576E+10 0.486653E+10 0.226933E+10 0.259720E+10 0.00 0.00
September 0.652033E+10 0.199322E+10 0.521797E+10 0.288152E+10 0.233645E+10 0.00 0.00
October 0.557266E+10 0.269135E+10 0.488414E+10 0.301559E+10 0.186855E+10 0.00 0.00
November 0.269338E+10 0.300797E+10 0.279452E+10 0.160149E+10 0.119303E+10 0.00 0.00
December 0.299491E+10 0.371428E+10 0.302132E+10 0.195522E+10 0.106611E+10 0.00 0.00
               
Annual Sum or Average 0.574088E+11 0.296886E+11 0.501723E+11 0.245400E+11 0.256322E+11 0.00 0.00
Minimum of Months 0.258674E+10 0.146576E+10 0.279452E+10 0.107920E+10 0.106611E+10 0.00 0.00
Maximum of Months 0.652033E+10 0.371428E+10 0.521797E+10 0.301559E+10 0.318743E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.324824E+09 0.248868E+10 0.726984E+09 0.214374E+09 0.512610E+09 0.00 0.00
February 0.854147E+09 0.201859E+10 0.117729E+10 0.442456E+09 0.734831E+09 0.00 0.00
March 0.156856E+10 0.190041E+10 0.182643E+10 0.616467E+09 0.120996E+10 0.00 0.00
April 0.275773E+10 0.153942E+10 0.268908E+10 0.102814E+10 0.166095E+10 0.00 0.00
May 0.398726E+10 0.136923E+10 0.357557E+10 0.145255E+10 0.212301E+10 0.00 0.00
June 0.379327E+10 0.104588E+10 0.332779E+10 0.129206E+10 0.203572E+10 0.00 0.00
July 0.529111E+10 0.101104E+10 0.424806E+10 0.223299E+10 0.201507E+10 0.00 0.00
August 0.443965E+10 0.984405E+09 0.351416E+10 0.179443E+10 0.171974E+10 0.00 0.00
September 0.320860E+10 0.133214E+10 0.276943E+10 0.132883E+10 0.144060E+10 0.00 0.00
October 0.150442E+10 0.179616E+10 0.162920E+10 0.663820E+09 0.965383E+09 0.00 0.00
November 0.434879E+09 0.207246E+10 0.785161E+09 0.221447E+09 0.563714E+09 0.00 0.00
December 0.376337E+09 0.259507E+10 0.682082E+09 0.233732E+09 0.448351E+09 0.00 0.00
               
Annual Sum or Average 0.285408E+11 0.201535E+11 0.269512E+11 0.115213E+11 0.154299E+11 0.00 0.00
Minimum of Months 0.324824E+09 0.984405E+09 0.682082E+09 0.214374E+09 0.448351E+09 0.00 0.00
Maximum of Months 0.529111E+10 0.259507E+10 0.424806E+10 0.223299E+10 0.212301E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 24487282.78 0.393143E+10 0.643410E+09 0.00 0.643410E+09 0.00 0.00
February 0.181135E+09 0.319668E+10 0.904276E+09 0.00 0.904276E+09 0.00 0.00
March 0.608958E+09 0.297818E+10 0.147506E+10 0.00 0.147506E+10 0.00 0.00
April 0.129563E+10 0.232662E+10 0.202002E+10 7165624.79 0.201285E+10 0.00 0.00
May 0.216927E+10 0.194886E+10 0.268590E+10 79794157.67 0.260611E+10 0.00 0.00
June 0.244768E+10 0.145326E+10 0.273305E+10 0.180480E+09 0.255258E+10 0.00 0.00
July 0.272759E+10 0.135136E+10 0.268421E+10 0.210454E+09 0.247375E+10 0.00 0.00
August 0.224508E+10 0.132578E+10 0.217288E+10 58739581.33 0.211414E+10 0.00 0.00
September 0.124106E+10 0.192457E+10 0.163337E+10 481656.94 0.163289E+10 0.00 0.00
October 0.504071E+09 0.266591E+10 0.115644E+10 0.00 0.115644E+10 0.00 0.00
November 93668483.90 0.316094E+10 0.704943E+09 0.00 0.704943E+09 0.00 0.00
December 10634844.69 0.399814E+10 0.546732E+09 0.00 0.546732E+09 0.00 0.00
               
Annual Sum or Average 0.135493E+11 0.302617E+11 0.193603E+11 0.537115E+09 0.188232E+11 0.00 0.00
Minimum of Months 10634844.69 0.132578E+10 0.546732E+09 0.00 0.546732E+09 0.00 0.00
Maximum of Months 0.272759E+10 0.399814E+10 0.273305E+10 0.210454E+09 0.260611E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.246181E+09 0.248847E+10 0.689252E+09 0.174748E+09 0.514504E+09 0.00 0.00
February 0.737260E+09 0.201880E+10 0.114232E+10 0.405433E+09 0.736886E+09 0.00 0.00
March 0.154538E+10 0.190958E+10 0.188830E+10 0.683582E+09 0.120472E+10 0.00 0.00
April 0.284236E+10 0.149830E+10 0.283277E+10 0.117706E+10 0.165571E+10 0.00 0.00
May 0.329106E+10 0.131210E+10 0.311479E+10 0.108294E+10 0.203185E+10 0.00 0.00
June 0.411361E+10 0.993905E+09 0.360998E+10 0.157073E+10 0.203925E+10 0.00 0.00
July 0.413724E+10 0.905993E+09 0.347379E+10 0.155924E+10 0.191455E+10 0.00 0.00
August 0.420862E+10 0.885768E+09 0.341425E+10 0.170800E+10 0.170625E+10 0.00 0.00
September 0.266660E+10 0.124039E+10 0.244291E+10 0.112669E+10 0.131622E+10 0.00 0.00
October 0.147159E+10 0.171879E+10 0.164536E+10 0.699123E+09 0.946237E+09 0.00 0.00
November 0.402122E+09 0.203653E+10 0.780449E+09 0.220329E+09 0.560121E+09 0.00 0.00
December 0.306183E+09 0.255974E+10 0.661482E+09 0.212951E+09 0.448531E+09 0.00 0.00
               
Annual Sum or Average 0.259682E+11 0.195684E+11 0.256957E+11 0.106208E+11 0.150748E+11 0.00 0.00
Minimum of Months 0.246181E+09 0.885768E+09 0.661482E+09 0.174748E+09 0.448531E+09 0.00 0.00
Maximum of Months 0.420862E+10 0.255974E+10 0.360998E+10 0.170800E+10 0.203925E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.252404E+10 0.357701E+10 0.284278E+10 0.168806E+10 0.115473E+10 0.00 0.00
February 0.400013E+10 0.297958E+10 0.394869E+10 0.244429E+10 0.150440E+10 0.00 0.00
March 0.497668E+10 0.295227E+10 0.470276E+10 0.250793E+10 0.219483E+10 0.00 0.00
April 0.538273E+10 0.243827E+10 0.480505E+10 0.208633E+10 0.271872E+10 0.00 0.00
May 0.513831E+10 0.211207E+10 0.454006E+10 0.135253E+10 0.318753E+10 0.00 0.00
June 0.465121E+10 0.161631E+10 0.401972E+10 0.107924E+10 0.294047E+10 0.00 0.00
July 0.579791E+10 0.150940E+10 0.452980E+10 0.165905E+10 0.287075E+10 0.00 0.00
August 0.644417E+10 0.146000E+10 0.486670E+10 0.226942E+10 0.259728E+10 0.00 0.00
September 0.647241E+10 0.196585E+10 0.521816E+10 0.288164E+10 0.233652E+10 0.00 0.00
October 0.552181E+10 0.263842E+10 0.488433E+10 0.301571E+10 0.186862E+10 0.00 0.00
November 0.264703E+10 0.299658E+10 0.279463E+10 0.160156E+10 0.119307E+10 0.00 0.00
December 0.295158E+10 0.372963E+10 0.302144E+10 0.195530E+10 0.106615E+10 0.00 0.00
               
Annual Sum or Average 0.565080E+11 0.299754E+11 0.501741E+11 0.245411E+11 0.256331E+11 0.00 0.00
Minimum of Months 0.252404E+10 0.146000E+10 0.279463E+10 0.107924E+10 0.106615E+10 0.00 0.00
Maximum of Months 0.647241E+10 0.372963E+10 0.521816E+10 0.301571E+10 0.318753E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.313710E+09 0.250948E+10 0.726993E+09 0.214377E+09 0.512616E+09 0.00 0.00
February 0.828053E+09 0.204559E+10 0.117730E+10 0.442463E+09 0.734839E+09 0.00 0.00
March 0.152034E+10 0.195173E+10 0.182646E+10 0.616478E+09 0.120998E+10 0.00 0.00
April 0.269858E+10 0.157906E+10 0.268912E+10 0.102815E+10 0.166096E+10 0.00 0.00
May 0.393684E+10 0.138011E+10 0.357561E+10 0.145258E+10 0.212303E+10 0.00 0.00
June 0.375140E+10 0.105226E+10 0.332783E+10 0.129209E+10 0.203574E+10 0.00 0.00
July 0.525955E+10 0.996633E+09 0.424812E+10 0.223303E+10 0.201509E+10 0.00 0.00
August 0.441440E+10 0.971202E+09 0.351421E+10 0.179446E+10 0.171975E+10 0.00 0.00
September 0.319010E+10 0.131253E+10 0.276947E+10 0.132885E+10 0.144062E+10 0.00 0.00
October 0.149173E+10 0.177054E+10 0.162922E+10 0.663831E+09 0.965393E+09 0.00 0.00
November 0.429863E+09 0.204327E+10 0.785171E+09 0.221451E+09 0.563720E+09 0.00 0.00
December 0.369926E+09 0.258450E+10 0.682091E+09 0.233735E+09 0.448356E+09 0.00 0.00
               
Annual Sum or Average 0.282045E+11 0.201969E+11 0.269516E+11 0.115215E+11 0.154301E+11 0.00 0.00
Minimum of Months 0.313710E+09 0.971202E+09 0.682091E+09 0.214377E+09 0.448356E+09 0.00 0.00
Maximum of Months 0.525955E+10 0.258450E+10 0.424812E+10 0.223303E+10 0.212303E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.50 3.10 1.22 3.91 -4.2 29.50 44.23 0.00
February 5.82 4.07 1.77 3.94 -3.8 43.80 82.64 0.00
March 8.33 5.86 2.94 3.85 -1.4 65.55 100.60 0.02
April 10.85 8.04 5.25 4.23 1.22 89.73 150.02 0.00
May 12.97 10.02 7.49 3.85 3.75 114.98 168.60 0.00
June 15.59 11.80 8.88 4.02 5.93 107.53 199.74 0.01
July 17.66 13.41 10.38 3.76 8.02 92.25 247.81 0.00
August 18.80 14.57 11.86 3.84 8.90 79.20 215.47 0.01
September 15.09 12.55 10.74 2.23 5.47 68.06 162.11 0.01
October 11.43 9.19 7.19 4.02 2.10 48.18 106.36 0.04
November 8.07 6.72 5.29 3.86 0.13 33.26 46.10 0.00
December 5.42 4.09 2.46 3.51 -3.8 24.03 50.49 0.04
                 
Annual Sum or Average 11.24 8.64 6.31 3.75 1.89 66.43 131.49 0.01
Minimum of Months 4.50 3.10 1.22 2.23 -4.2 24.03 44.23 0.00
Maximum of Months 18.80 14.57 11.86 4.23 8.90 114.98 247.81 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.40 11-JAN-14:20 10.49 7.20 8.40 3.89 99.17 130.33
February 20.00 27-FEB-14:00 12.17 5.60 2.60 5.54 87.00 691.00
March 20.60 18-MAR-15:00 10.43 0.00 6.20 6.55 111.50 465.50
April 27.20 27-APR-15:09 17.22 11.02 4.10 12.63 151.33 598.33
May 25.00 05-MAY-15:00 17.36 12.80 2.60 18.99 208.50 29.50
June 26.70 28-JUN-16:00 16.74 10.60 3.10 11.84 131.50 527.00
July 30.60 24-JUL-14:00 18.78 12.20 3.10 20.75 267.00 383.50
August 31.80 10-AUG-16:00 18.70 11.10 2.60 16.85 50.50 750.50
September 25.00 14-SEP-16:00 16.69 11.70 3.10 13.54 100.50 235.00
October 21.70 04-OCT-14:00 11.49 1.70 5.20 4.92 56.50 783.50
November 21.10 04-NOV-13:00 15.94 12.80 0.00 6.95 52.50 729.00
December 13.30 14-DEC-11:00 8.44 3.60 13.90 5.33 127.50 85.00
                 
Annual Sum or Average                
Minimum of Months 13.30   8.44 0.00 0.00 3.89 50.50 29.50
Maximum of Months 31.80   18.78 12.80 13.90 20.75 267.00 783.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -3.9 07-JAN-07:00 -3.9 -3.9 2.10 -14.4 0.00 0.00
February -5.6 19-FEB-05:10 -6.1 -7.3 3.77 -22.8 0.00 0.00
March -0.6 01-MAR-06:00 -2.0 -3.9 1.50 -17.3 16.50 102.00
April 1.70 19-APR-04:00 1.21 0.60 3.10 -11.9 0.00 0.00
May 4.40 11-MAY-02:00 3.92 3.30 3.10 -10.9 0.00 0.00
June 8.30 15-JUN-02:00 7.50 6.70 3.10 -3.2 0.00 0.00
July 11.10 03-JUL-03:00 8.19 5.00 2.60 5.54 0.00 0.00
August 11.00 06-AUG-04:00 10.57 10.20 2.60 -3.2 11.00 135.50
September 7.20 27-SEP-04:49 6.72 6.20 0.25 -4.0 0.00 0.00
October 5.60 13-OCT-04:00 4.51 3.30 2.10 -8.5 0.00 0.00
November 0.00 11-NOV-06:00 -0.2 -0.6 2.10 -16.0 0.00 0.00
December -1.7 26-DEC-06:00 -1.7 -1.7 2.10 -15.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -6.1 -7.3 0.25 -22.8 0.00 0.00
Maximum of Months 11.10   10.57 10.20 3.77 5.54 16.50 135.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.49 11-JAN-13:00 14.40 7.20 8.20 2.85 105.50 249.00
February 12.42 27-FEB-15:00 19.40 6.70 2.60 6.35 88.00 342.50
March 12.45 09-MAR-11:00 17.20 8.90 2.10 12.41 178.00 40.00
April 17.29 27-APR-14:00 27.20 11.10 4.10 12.41 147.50 646.00
May 17.58 06-MAY-12:00 23.90 13.90 5.20 15.57 365.50 282.50
June 16.74 28-JUN-16:00 26.70 10.60 3.10 11.84 131.50 527.00
July 19.18 31-JUL-15:00 28.90 13.90 4.10 14.65 45.00 848.50
August 20.13 29-AUG-12:00 28.90 15.70 2.60 17.39 136.50 655.00
September 17.97 23-SEP-13:00 23.30 15.00 2.10 9.72 148.00 670.50
October 15.15 01-OCT-11:00 17.20 13.90 4.60 13.73 236.50 63.50
November 16.05 04-NOV-12:00 20.60 13.30 0.00 7.95 62.00 746.50
December 10.71 16-DEC-11:00 11.70 10.00 6.70 7.35 89.50 0.00
                 
Annual Sum or Average                
Minimum of Months 10.49   11.70 6.70 0.00 2.85 45.00 0.00
Maximum of Months 20.13   28.90 15.70 8.20 17.39 365.50 848.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.00 11-JAN-21:00 11.10 10.49 4.60 6.75 0.00 0.00
February 11.70 24-FEB-00:00 12.80 12.15 4.10 8.74 0.00 0.00
March 11.70 09-MAR-16:00 12.80 12.15 2.10 8.74 37.50 0.00
April 12.80 28-APR-12:00 16.70 14.35 4.10 8.35 265.50 596.00
May 13.90 05-MAY-16:00 22.80 17.10 2.60 19.17 111.50 27.50
June 13.90 12-JUN-12:00 16.70 15.00 3.60 13.16 263.50 0.00
July 15.00 11-JUL-09:20 16.13 15.49 4.60 12.91 204.17 28.17
August 16.40 30-AUG-07:00 17.40 16.77 5.20 12.41 168.50 34.50
September 15.00 14-SEP-11:20 20.37 16.93 2.10 6.89 152.83 748.17
October 13.90 01-OCT-10:00 16.70 15.01 4.10 13.16 184.50 0.00
November 13.90 03-NOV-19:00 15.00 14.31 4.60 11.46 0.00 0.00
December 10.00 16-DEC-10:00 11.10 10.48 7.70 6.75 81.00 0.00
                 
Annual Sum or Average                
Minimum of Months 10.00   11.10 10.48 2.10 6.75 0.00 0.00
Maximum of Months 16.40   22.80 17.10 7.70 19.17 265.50 748.17



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 11.48 8.35 0.00
February 18.00 13.00 16.00 11.14 14.81 0.00
March 18.00 13.00 16.00 11.69 23.26 0.00
April 18.00 13.00 16.00 12.99 36.00 0.00
May 18.00 13.00 16.00 14.72 45.46 0.00
June 18.00 13.00 16.00 16.40 49.26 0.00
July 18.00 13.00 16.00 17.58 51.50 0.00
August 18.00 13.00 16.00 17.95 42.11 0.00
September 18.00 13.00 16.00 17.39 30.76 0.00
October 18.00 13.00 16.00 16.06 18.91 0.00
November 18.00 13.00 16.00 14.32 9.65 0.00
December 18.00 13.00 16.00 12.65 7.39 0.00
             
Annual Sum or Average 18.00 13.00 16.00 14.55 28.19 0.00
Minimum of Months 18.00 13.00 16.00 11.14 7.39 0.00
Maximum of Months 18.00 13.00 16.00 17.95 51.50 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.482973E+10 -0.458408E+10 0.00 0.00 744.00 0.00 -245643482.3 60.05 0.00 0.00
February 0.441110E+10 -0.419457E+10 0.00 0.00 672.00 0.00 -216529522.0 60.05 0.00 0.00
March 0.514654E+10 -0.491064E+10 0.00 0.00 744.00 0.00 -235900998.4 60.05 0.00 0.00
April 0.452608E+10 -0.429981E+10 0.00 0.00 720.00 0.00 -226268527.3 60.05 0.00 0.00
May 0.467739E+10 -0.444432E+10 0.00 0.00 744.00 0.00 -233072698.0 60.05 0.00 0.00
June 0.447758E+10 -0.425257E+10 0.00 0.00 720.00 0.00 -225010380.2 60.05 0.00 0.00
July 0.412891E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -231469946.4 60.05 0.00 0.00
August 0.450668E+10 -0.427461E+10 0.00 0.00 744.00 0.00 -232070014.6 60.05 0.00 0.00
September 0.412371E+10 -0.389919E+10 0.00 0.00 720.00 0.00 -224514902.7 60.05 0.00 0.00
October 0.438594E+10 -0.415238E+10 0.00 0.00 744.00 0.00 -233561287.5 60.05 0.00 0.00
November 0.447300E+10 -0.424363E+10 0.00 0.00 720.00 0.00 -229364627.9 60.05 0.00 0.00
December 0.459149E+10 -0.435083E+10 0.00 0.00 744.00 0.00 -240657761.7 60.05 0.00 0.00
                     
Annual Sum or Average 0.542781E+11 -0.515041E+11 0.00 0.00 8760.00 0.00 -0.277406E+10 60.05 0.00 0.00
Minimum of Months 0.412371E+10 -0.491064E+10 0.00 0.00 672.00 0.00 -245643482.3 60.05 0.00 0.00
Maximum of Months 0.514654E+10 -0.389744E+10 0.00 0.00 744.00 0.00 -216529522.0 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.50 0.48 01-JAN-09:50 2744.45 32.28 222.33 218.83 2191.41 33.53 225.83 187.33
February 259.50 0.50 0.48 01-FEB-08:30 4676.02 33.24 243.17 243.33 2064.71 29.38 222.17 221.00
March 247.00 0.50 0.48 01-MAR-07:30 7743.27 33.05 208.83 311.67 1686.13 21.83 155.83 267.00
April 379.50 0.51 0.48 01-APR-07:10 2183.74 18.64 2.83 344.33 1216.73 20.87 212.67 307.00
May 427.83 0.51 0.48 01-MAY-07:10 1995.02 18.53 4.83 384.83 1093.07 20.71 209.50 343.00
June 375.17 0.52 0.48 01-JUN-05:00 1742.44 18.10 0.00 393.83 1003.97 20.32 190.50 343.67
July 471.00 0.53 0.48 01-JUL-05:30 1552.52 16.89 0.00 392.83 913.22 19.11 150.83 337.00
August 366.67 0.52 0.48 01-AUG-05:00 1846.74 17.94 2.67 372.67 1111.28 20.18 159.50 326.33
September 301.17 0.50 0.48 01-SEP-07:40 2983.68 20.78 41.67 319.00 1478.49 21.66 186.50 287.50
October 245.33 0.51 0.48 01-OCT-07:49 7195.48 34.58 220.50 284.67 1968.69 23.02 157.50 256.17
November 242.67 0.50 0.48 01-NOV-08:09 3058.65 31.81 224.67 224.17 2456.87 33.15 229.50 193.17
December 160.33 0.50 0.48 01-DEC-09:39 3686.25 35.42 149.50 206.83 3141.89 36.90 149.67 167.17
                         
Annual Sum or Average 3714.00 0.51     3101.84 23.95 1321.00 3697.00 1520.01 23.68 2250.00 3236.33
Minimum of Months 160.33 0.50 0.48   1552.52 16.89 0.00 206.83 913.22 19.11 149.67 167.17
Maximum of Months 471.00 0.53 0.48   7743.27 35.42 243.17 393.83 3141.89 36.90 229.50 343.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-09:50 911.09 18.95 61.50 198.67 567.91 21.21 75.67 128.67
February 259.50 0.52 0.48 01-FEB-08:30 1469.22 19.69 68.33 226.67 787.99 21.90 79.83 178.83
March 247.00 0.51 0.48 01-MAR-07:30 2659.52 22.08 79.00 302.00 1191.45 23.02 90.67 252.67
April 379.50 0.51 0.48 01-APR-06:19 2796.72 21.11 105.50 346.33 1584.43 23.20 103.83 306.17
May 427.83 0.50 0.48 01-MAY-06:00 2887.52 21.03 132.50 390.83 1263.95 21.35 91.67 349.17
June 375.17 0.51 0.48 01-JUN-05:10 3031.04 20.26 89.00 402.67 1682.49 22.31 77.67 355.83
July 471.00 0.52 0.48 01-JUL-04:00 2859.15 20.72 148.50 406.33 1302.06 21.66 101.67 370.17
August 366.67 0.51 0.48 01-AUG-05:30 3343.46 22.20 116.33 377.50 1464.14 21.98 74.00 337.33
September 301.17 0.50 0.48 01-SEP-07:40 2730.18 21.78 82.67 322.83 1531.78 23.01 77.67 284.33
October 245.33 0.52 0.48 01-OCT-07:40 2444.16 21.98 83.00 270.50 1096.07 22.64 89.17 224.67
November 242.67 0.52 0.48 01-NOV-07:00 1135.34 20.34 79.17 207.17 596.33 21.16 71.67 143.50
December 160.33 0.53 0.48 01-DEC-09:39 1069.58 21.49 56.33 182.00 582.30 22.14 57.00 104.17
                         
Annual Sum or Average 3714.00 0.51     2458.32 20.98 1101.83 3633.50 1218.50 22.12 990.50 3035.50
Minimum of Months 160.33 0.50 0.48   911.09 18.95 56.33 182.00 567.91 21.16 57.00 104.17
Maximum of Months 471.00 0.53 0.48   3343.46 22.20 148.50 406.33 1682.49 23.20 103.83 370.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.55 0.48 02-JAN-10:00 490.08 14.23 0.00 176.83 269.03 16.43 0.00 45.33
February 259.50 0.53 0.48 01-FEB-09:20 620.74 15.47 0.00 213.83 353.27 17.73 0.00 126.67
March 247.00 0.51 0.48 01-MAR-08:20 834.48 17.01 0.00 297.33 497.24 19.27 4.00 214.67
April 379.50 0.50 0.48 01-APR-07:10 980.20 17.76 0.00 347.83 570.78 19.89 31.83 300.33
May 427.83 0.50 0.48 01-MAY-07:10 1222.56 20.01 40.00 399.33 700.78 22.06 162.17 366.67
June 375.17 0.50 0.48 01-JUN-05:19 1281.10 21.20 60.83 412.67 757.07 23.27 193.50 383.67
July 471.00 0.51 0.48 01-JUL-04:00 1083.92 20.32 79.33 423.50 651.77 22.39 180.00 382.17
August 366.67 0.50 0.48 01-AUG-05:49 951.82 17.84 0.00 390.67 584.43 20.03 53.83 344.67
September 301.17 0.50 0.48 01-SEP-07:40 906.39 17.88 0.00 313.17 553.58 20.10 16.50 254.83
October 245.33 0.53 0.48 01-OCT-08:09 675.74 16.03 0.00 258.50 412.10 18.37 0.33 163.83
November 242.67 0.54 0.48 01-NOV-09:00 527.98 14.57 0.00 189.67 289.61 16.71 0.00 64.00
December 160.33 0.57 0.48 01-DEC-10:09 456.51 14.21 0.00 151.17 269.27 16.68 0.00 35.50
                         
Annual Sum or Average 3714.00 0.52     904.42 17.80 180.17 3574.50 533.52 19.97 642.17 2682.33
Minimum of Months 160.33 0.50 0.48   456.51 14.21 0.00 151.17 269.03 16.43 0.00 35.50
Maximum of Months 471.00 0.57 0.48   1281.10 21.20 79.33 423.50 757.07 23.27 193.50 383.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-10:30 1020.26 18.86 65.17 199.50 560.81 21.16 68.33 136.33
February 259.50 0.51 0.48 01-FEB-09:20 1467.67 19.86 66.67 228.83 768.83 21.67 71.67 181.67
March 247.00 0.51 0.48 01-MAR-08:20 2351.12 22.14 78.17 304.67 1270.38 23.10 93.67 251.17
April 379.50 0.51 0.48 01-APR-07:30 2820.83 20.83 105.50 344.17 1239.75 20.75 59.67 305.83
May 427.83 0.50 0.48 01-MAY-07:30 2912.82 17.71 52.50 390.33 1579.16 18.62 11.67 354.67
June 375.17 0.51 0.48 01-JUN-06:10 2981.49 17.33 42.83 401.67 1352.65 18.42 1.17 361.00
July 471.00 0.52 0.48 01-JUL-06:10 3282.06 16.47 58.83 402.67 1444.99 17.24 4.67 360.50
August 366.67 0.51 0.48 01-AUG-06:19 3109.00 19.27 75.83 380.00 1798.21 20.73 54.50 341.50
September 301.17 0.50 0.48 01-SEP-07:49 3432.57 22.97 100.50 314.67 1944.62 23.91 95.67 270.67
October 245.33 0.51 0.48 01-OCT-08:20 2348.42 22.32 87.33 272.00 1070.48 23.22 84.83 224.33
November 242.67 0.52 0.48 01-NOV-09:50 1090.60 18.82 63.33 208.50 583.82 20.51 59.83 140.17
December 160.33 0.53 0.48 01-DEC-09:00 1090.76 20.31 48.67 182.00 585.68 21.07 49.83 100.67
                         
Annual Sum or Average 3714.00 0.51     2524.17 19.42 845.33 3629.00 1271.95 20.49 655.50 3028.50
Minimum of Months 160.33 0.50 0.48   1020.26 16.47 42.83 182.00 560.81 17.24 1.17 100.67
Maximum of Months 471.00 0.53 0.48   3432.57 22.97 105.50 402.67 1944.62 23.91 95.67 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.51 0.48 01-JAN-09:50 2628.31 30.49 207.17 216.17 2123.85 33.20 222.50 182.50
February 259.50 0.50 0.48 01-FEB-08:39 4546.28 32.09 231.50 240.50 1973.39 27.94 157.17 219.00
March 247.00 0.50 0.48 01-MAR-07:30 7587.42 32.25 207.67 309.83 1574.26 18.97 12.33 263.33
April 379.50 0.51 0.48 01-APR-07:10 2076.41 14.68 0.00 342.83 1140.44 18.19 10.50 302.67
May 427.83 0.51 0.48 01-MAY-07:10 1906.79 14.64 0.00 382.67 1033.46 18.09 3.33 339.67
June 375.17 0.52 0.48 01-JUN-05:00 1665.73 14.46 0.00 392.00 952.27 17.92 0.00 340.00
July 471.00 0.53 0.48 01-JUL-05:30 1481.39 13.10 0.00 389.33 863.25 16.60 1.00 331.67
August 366.67 0.52 0.48 01-AUG-05:00 1751.18 14.23 0.00 369.33 1040.53 17.80 5.67 322.17
September 301.17 0.50 0.48 01-SEP-07:40 2846.76 17.24 27.00 317.83 1375.12 19.08 29.67 282.67
October 245.33 0.51 0.48 01-OCT-07:49 7032.68 33.75 218.00 282.33 1850.18 20.32 28.33 254.50
November 242.67 0.51 0.48 01-NOV-08:09 2948.99 30.64 215.33 222.17 2389.04 32.83 227.00 189.67
December 160.33 0.50 0.48 01-DEC-09:39 3551.89 34.93 149.17 204.83 3041.51 36.50 149.67 161.33
                         
Annual Sum or Average 3714.00 0.51     2992.81 21.19 1255.83 3669.83 1443.68 21.56 847.17 3189.17
Minimum of Months 160.33 0.50 0.48   1481.39 13.10 0.00 204.83 863.25 16.60 0.00 161.33
Maximum of Months 471.00 0.53 0.48   7587.42 34.93 231.50 392.00 3041.51 36.50 227.00 340.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-09:50 881.63 18.45 61.33 197.00 546.64 20.98 72.50 124.00
February 259.50 0.52 0.48 01-FEB-08:30 1425.96 19.19 68.00 225.50 754.71 21.67 74.33 174.83
March 247.00 0.51 0.48 01-MAR-07:30 2589.99 21.61 79.00 300.00 1137.92 22.82 80.50 248.83
April 379.50 0.51 0.48 01-APR-06:19 2721.69 20.65 105.33 344.50 1525.45 23.02 95.33 303.00
May 427.83 0.50 0.48 01-MAY-06:00 2816.61 20.60 132.33 388.33 1209.34 21.17 85.17 344.00
June 375.17 0.51 0.48 01-JUN-05:10 2941.69 19.80 89.00 400.67 1614.57 22.11 75.83 351.33
July 471.00 0.52 0.48 01-JUL-04:00 2778.71 20.13 146.50 404.00 1243.00 20.67 87.17 365.50
August 366.67 0.51 0.48 01-AUG-05:30 3196.03 20.22 98.50 373.50 1398.18 21.80 71.33 332.83
September 301.17 0.50 0.48 01-SEP-07:40 2656.31 21.30 82.67 319.67 1474.21 22.80 67.67 280.33
October 245.33 0.52 0.48 01-OCT-07:40 2374.30 21.29 81.00 267.83 1047.40 22.42 76.83 221.17
November 242.67 0.52 0.48 01-NOV-07:00 1081.37 18.45 65.67 203.67 572.12 20.92 67.83 137.83
December 160.33 0.53 0.48 01-DEC-09:39 1034.38 21.01 56.33 178.83 556.71 21.88 54.83 98.33
                         
Annual Sum or Average 3714.00 0.51     2383.52 20.24 1065.67 3603.50 1167.51 21.81 909.33 2982.00
Minimum of Months 160.33 0.50 0.48   881.63 18.45 56.33 178.83 546.64 20.67 54.83 98.33
Maximum of Months 471.00 0.53 0.48   3196.03 21.61 146.50 404.00 1614.57 23.02 95.33 365.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 02-JAN-11:09 471.86 10.05 0.00 172.50 258.54 13.60 0.00 33.50
February 259.50 0.53 0.48 01-FEB-09:20 598.02 11.55 0.00 210.33 340.49 15.12 0.00 120.17
March 247.00 0.51 0.48 01-MAR-08:20 804.54 13.48 0.00 293.00 480.87 17.02 0.00 205.67
April 379.50 0.51 0.48 01-APR-07:10 945.73 14.26 0.00 346.00 551.71 17.70 0.17 294.67
May 427.83 0.50 0.48 01-MAY-07:10 1176.28 16.05 26.67 397.83 676.44 19.98 51.33 362.00
June 375.17 0.50 0.48 01-JUN-05:30 1236.96 18.31 59.00 411.00 732.10 21.51 73.17 380.67
July 471.00 0.51 0.48 01-JUL-04:00 1043.28 15.66 44.67 420.83 631.63 20.52 86.50 378.33
August 366.67 0.50 0.48 01-AUG-05:49 919.73 14.48 0.00 389.17 567.23 18.09 1.50 339.67
September 301.17 0.51 0.48 01-SEP-07:40 873.52 14.66 0.00 311.17 535.98 18.16 0.00 247.50
October 245.33 0.53 0.48 01-OCT-08:20 650.67 12.50 0.00 255.67 398.59 16.11 0.00 156.00
November 242.67 0.55 0.48 01-NOV-10:09 508.67 10.41 0.00 184.00 278.51 13.91 0.00 53.00
December 160.33 0.57 0.48 01-DEC-10:09 438.08 10.25 0.00 145.00 259.03 14.04 0.00 28.67
                         
Annual Sum or Average 3714.00 0.52     871.66 14.06 130.33 3536.50 515.85 17.78 212.67 2599.83
Minimum of Months 160.33 0.50 0.48   438.08 10.05 0.00 145.00 258.54 13.60 0.00 28.67
Maximum of Months 471.00 0.57 0.48   1236.96 18.31 59.00 420.83 732.10 21.51 86.50 380.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-12:00 989.65 18.46 64.83 197.67 538.11 21.05 67.50 129.83
February 259.50 0.52 0.48 01-FEB-09:20 1422.40 19.45 66.50 227.17 721.52 20.56 60.67 175.67
March 247.00 0.51 0.48 01-MAR-08:20 2286.33 21.74 78.17 302.17 1215.08 22.90 91.33 245.50
April 379.50 0.51 0.48 01-APR-07:30 2709.70 20.40 105.50 342.00 1185.20 20.61 55.00 303.17
May 427.83 0.50 0.48 01-MAY-07:30 2827.03 17.22 52.33 389.67 1514.42 18.45 8.33 351.17
June 375.17 0.51 0.48 01-JUN-06:10 2862.82 16.84 42.83 398.50 1290.58 18.24 0.83 358.83
July 471.00 0.52 0.48 01-JUL-06:19 3151.66 15.98 58.83 399.00 1377.42 17.07 4.00 357.83
August 366.67 0.51 0.48 01-AUG-06:19 3022.21 18.82 75.83 376.67 1722.52 20.58 54.17 337.50
September 301.17 0.50 0.48 01-SEP-07:49 3341.71 22.57 100.50 312.67 1840.65 23.51 90.83 266.00
October 245.33 0.52 0.48 01-OCT-08:30 2285.19 21.93 87.33 269.00 991.96 21.85 73.50 218.83
November 242.67 0.52 0.48 01-NOV-09:50 1057.57 18.40 62.83 206.83 559.45 20.38 58.50 132.67
December 160.33 0.54 0.48 01-DEC-09:00 1056.11 19.91 48.67 180.50 560.32 20.96 49.67 94.00
                         
Annual Sum or Average 3714.00 0.51     2441.21 18.98 844.17 3601.83 1211.87 20.17 614.33 2971.00
Minimum of Months 160.33 0.50 0.48   989.65 15.98 42.83 180.50 538.11 17.07 0.83 94.00
Maximum of Months 471.00 0.54 0.48   3341.71 22.57 105.50 399.00 1840.65 23.51 91.33 358.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.51 0.48 01-JAN-09:50 2628.29 30.49 207.17 216.17 2123.78 33.20 222.50 182.50
February 259.50 0.50 0.48 01-FEB-08:39 4546.23 32.09 231.50 240.50 1973.30 27.94 157.17 219.00
March 247.00 0.50 0.48 01-MAR-07:30 7587.32 32.25 207.67 309.83 1574.14 18.97 12.33 263.33
April 379.50 0.51 0.48 01-APR-07:10 2076.28 14.68 0.00 342.83 1140.35 18.19 10.50 302.67
May 427.83 0.51 0.48 01-MAY-07:10 1906.67 14.64 0.00 382.67 1033.37 18.09 3.33 339.67
June 375.17 0.52 0.48 01-JUN-05:00 1665.64 14.46 0.00 392.00 952.20 17.92 0.00 340.00
July 471.00 0.53 0.48 01-JUL-05:30 1481.30 13.10 0.00 389.33 863.19 16.60 1.00 331.67
August 366.67 0.52 0.48 01-AUG-05:00 1751.09 14.23 0.00 369.33 1040.46 17.80 5.83 322.17
September 301.17 0.50 0.48 01-SEP-07:40 2846.65 17.25 27.00 317.83 1375.02 19.08 29.67 282.50
October 245.33 0.51 0.48 01-OCT-07:49 7032.63 33.75 218.00 282.33 1850.07 20.32 28.33 254.50
November 242.67 0.51 0.48 01-NOV-08:09 2948.96 30.64 215.33 222.17 2388.97 32.83 227.00 189.67
December 160.33 0.50 0.48 01-DEC-09:39 3551.91 34.93 149.17 204.83 3041.45 36.50 149.67 161.33
                         
Annual Sum or Average 3714.00 0.51     2992.73 21.19 1255.83 3669.83 1443.60 21.56 847.33 3189.00
Minimum of Months 160.33 0.50 0.48   1481.30 13.10 0.00 204.83 863.19 16.60 0.00 161.33
Maximum of Months 471.00 0.53 0.48   7587.32 34.93 231.50 392.00 3041.45 36.50 227.00 340.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-09:50 881.60 18.45 61.33 197.00 546.60 20.98 72.50 124.00
February 259.50 0.52 0.48 01-FEB-08:30 1425.92 19.19 68.00 225.50 754.66 21.67 74.33 174.83
March 247.00 0.51 0.48 01-MAR-07:30 2589.95 21.61 79.00 300.00 1137.86 22.82 80.50 248.83
April 379.50 0.51 0.48 01-APR-06:19 2721.63 20.65 105.33 344.50 1525.38 23.02 95.33 303.00
May 427.83 0.50 0.48 01-MAY-06:00 2816.53 20.60 132.33 388.33 1209.26 21.17 85.17 344.00
June 375.17 0.51 0.48 01-JUN-05:10 2941.63 19.81 89.00 400.83 1614.50 22.11 75.83 351.33
July 471.00 0.52 0.48 01-JUL-04:00 2778.66 20.14 146.50 404.00 1242.95 20.67 87.17 365.50
August 366.67 0.51 0.48 01-AUG-05:30 3195.99 20.23 98.50 373.50 1398.12 21.80 71.33 332.83
September 301.17 0.50 0.48 01-SEP-07:40 2656.27 21.30 82.67 319.67 1474.15 22.80 67.67 280.33
October 245.33 0.52 0.48 01-OCT-07:40 2374.28 21.29 81.00 267.83 1047.35 22.42 76.83 221.00
November 242.67 0.52 0.48 01-NOV-07:00 1081.33 18.45 65.67 203.67 572.09 20.92 67.83 137.83
December 160.33 0.53 0.48 01-DEC-09:39 1034.36 21.01 56.33 178.83 556.68 21.89 54.83 98.33
                         
Annual Sum or Average 3714.00 0.51     2383.47 20.24 1065.67 3603.67 1167.45 21.81 909.33 2981.83
Minimum of Months 160.33 0.50 0.48   881.60 18.45 56.33 178.83 546.60 20.67 54.83 98.33
Maximum of Months 471.00 0.53 0.48   3195.99 21.61 146.50 404.00 1614.50 23.02 95.33 365.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.56 0.48 02-JAN-11:09 471.83 10.05 0.00 172.50 258.52 13.60 0.00 33.50
February 259.50 0.53 0.48 01-FEB-09:20 597.99 11.55 0.00 210.33 340.46 15.12 0.00 120.17
March 247.00 0.51 0.48 01-MAR-08:20 804.51 13.48 0.00 293.00 480.83 17.02 0.00 205.67
April 379.50 0.51 0.48 01-APR-07:10 945.69 14.26 0.00 346.00 551.68 17.70 0.17 294.67
May 427.83 0.50 0.48 01-MAY-07:10 1176.23 16.06 26.67 397.83 676.39 19.98 51.33 362.00
June 375.17 0.50 0.48 01-JUN-05:30 1236.93 18.31 59.00 411.00 732.06 21.51 73.33 380.67
July 471.00 0.51 0.48 01-JUL-04:00 1043.25 15.66 44.67 420.83 631.59 20.52 86.50 378.33
August 366.67 0.50 0.48 01-AUG-05:49 919.70 14.48 0.00 389.17 567.20 18.09 1.50 339.67
September 301.17 0.51 0.48 01-SEP-07:40 873.50 14.66 0.00 311.17 535.95 18.16 0.00 247.50
October 245.33 0.53 0.48 01-OCT-08:20 650.65 12.50 0.00 255.67 398.56 16.11 0.00 156.00
November 242.67 0.55 0.48 01-NOV-10:09 508.64 10.42 0.00 184.00 278.48 13.91 0.00 53.00
December 160.33 0.57 0.48 01-DEC-10:09 438.06 10.25 0.00 145.00 259.01 14.04 0.00 28.67
                         
Annual Sum or Average 3714.00 0.52     871.63 14.06 130.33 3536.50 515.82 17.78 212.83 2599.83
Minimum of Months 160.33 0.50 0.48   438.06 10.05 0.00 145.00 258.52 13.60 0.00 28.67
Maximum of Months 471.00 0.57 0.48   1236.93 18.31 59.00 420.83 732.06 21.51 86.50 380.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 237.83 0.53 0.48 01-JAN-12:00 989.62 18.46 64.83 197.67 538.07 21.05 67.50 129.83
February 259.50 0.52 0.48 01-FEB-09:20 1422.37 19.45 66.50 227.17 721.47 20.56 60.67 175.67
March 247.00 0.51 0.48 01-MAR-08:20 2286.28 21.75 78.17 302.17 1215.01 22.90 91.33 245.50
April 379.50 0.51 0.48 01-APR-07:30 2709.64 20.41 105.50 342.00 1185.12 20.61 55.00 303.17
May 427.83 0.50 0.48 01-MAY-07:30 2826.95 17.22 52.33 389.67 1514.34 18.45 8.33 351.17
June 375.17 0.51 0.48 01-JUN-06:10 2862.76 16.84 42.83 398.50 1290.51 18.24 0.83 358.83
July 471.00 0.52 0.48 01-JUL-06:19 3151.60 15.98 58.83 399.00 1377.35 17.08 4.00 357.83
August 366.67 0.51 0.48 01-AUG-06:19 3022.18 18.82 75.83 376.67 1722.46 20.58 54.17 337.50
September 301.17 0.50 0.48 01-SEP-07:49 3341.68 22.57 100.50 312.67 1840.58 23.51 90.83 266.00
October 245.33 0.52 0.48 01-OCT-08:30 2285.16 21.93 87.33 269.00 991.91 21.85 73.50 218.83
November 242.67 0.52 0.48 01-NOV-09:50 1057.54 18.41 62.83 206.83 559.41 20.39 58.50 132.67
December 160.33 0.54 0.48 01-DEC-09:00 1056.10 19.91 48.67 180.50 560.29 20.96 49.67 94.00
                         
Annual Sum or Average 3714.00 0.51     2441.16 18.98 844.17 3601.83 1211.81 20.17 614.33 2971.00
Minimum of Months 160.33 0.50 0.48   989.62 15.98 42.83 180.50 538.07 17.08 0.83 94.00
Maximum of Months 471.00 0.54 0.48   3341.68 22.57 105.50 399.00 1840.58 23.51 91.33 358.83



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.716907E+10 11647.36 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.468387E+10 11498.36 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.169081E+10 10613.99 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.518884E+09 8141.04 19-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 48692973.02 4064.70 18-MAY-06:08 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 381884.38 5.51 31-JUL-15:20 0.00 0.00 0.00 0.00 0.00
August 962797.96 5.32 09-AUG-12:50 0.00 0.00 0.00 0.00 0.00
September 573580.58 667.73 28-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.159342E+09 3323.13 31-OCT-21:00 0.00 0.00 0.00 0.00 0.00
November 0.302535E+10 10716.28 13-NOV-08:04 0.00 0.00 0.00 0.00 0.00
December 0.595720E+10 11663.95 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.232551E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.716907E+10 11663.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.354830E+09 9669.16 03-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.354830E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.354830E+09 9669.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.433848E+10 8373.28 06-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.240995E+10 8118.77 09-FEB-08:00 0.00 0.00 0.00 0.00 0.00
March 0.161656E+10 7954.48 01-MAR-07:06 0.00 0.00 0.00 0.00 0.00
April 0.910715E+09 8147.18 26-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.603478E+09 8242.22 11-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.292130E+09 7999.20 08-JUN-06:07 0.00 0.00 0.00 0.00 0.00
July 53931858.55 7268.18 03-JUL-06:07 0.00 0.00 0.00 0.00 0.00
August 70321293.09 7922.78 03-AUG-06:06 0.00 0.00 0.00 0.00 0.00
September 0.258965E+09 7997.29 27-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.839929E+09 7969.96 11-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.214732E+10 7985.27 13-NOV-08:00 0.00 0.00 0.00 0.00 0.00
December 0.331428E+10 8264.86 26-DEC-08:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.168561E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 53931858.55 7268.18   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.433848E+10 8373.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.134877E+10 5480.35 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.480422E+09 5404.79 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 54496115.96 5296.50 24-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 4194362.23 5272.42 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 371096.23 948.27 31-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.185447E+09 5295.97 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.736369E+09 5489.86 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.281007E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134877E+10 5489.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.221566E+10 5894.90 06-JAN-07:25 0.00 0.00 0.00 0.00 0.00
February 0.966280E+09 5739.60 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.177807E+09 5639.17 02-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 18816042.82 5629.54 01-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3589863.87 3497.85 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.322990E+09 5635.48 18-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.121334E+10 5870.15 26-DEC-08:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.491849E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.221566E+10 5894.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137061E+10 5699.72 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.492630E+09 5620.98 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 72677561.56 5504.67 06-MAR-06:11 0.00 0.00 0.00 0.00 0.00
April 7965324.50 5489.62 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 182023.57 73.66 28-OCT-06:50 0.00 0.00 0.00 0.00 0.00
November 0.190626E+09 5507.09 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.738638E+09 5709.54 26-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.287333E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137061E+10 5709.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.756921E+10 12916.90 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.513369E+10 12822.56 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.268460E+10 11214.65 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.113311E+10 8567.92 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.267352E+09 4812.88 18-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 6781226.95 1137.89 15-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 329370.35 4.83 31-JUL-14:20 0.00 0.00 0.00 0.00 0.00
August 832631.53 4.78 14-AUG-11:00 0.00 0.00 0.00 0.00 0.00
September 34015869.11 2436.59 28-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.620615E+09 5072.00 16-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.380651E+10 11643.94 24-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.658365E+10 12685.95 26-DEC-07:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.278407E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 329370.35 4.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.756921E+10 12916.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.123006E+10 14482.03 03-JAN-07:15 0.00 0.00 0.00 0.00 0.00
February 0.155595E+09 14449.33 21-FEB-07:16 0.00 0.00 0.00 0.00 0.00
March 3221339.44 10466.88 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 31917999.16 14490.72 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.337619E+09 14479.17 27-DEC-07:06 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175841E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123006E+10 14490.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.138620E+10 8697.83 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.468103E+09 8628.38 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 59787517.88 8523.16 08-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 7700394.67 8508.75 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 8146976.91 4461.27 16-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.311730E+09 8563.06 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.944963E+09 8563.26 20-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.318663E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138620E+10 8697.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.111026E+10 5969.11 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.403631E+09 5921.42 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 41739372.88 5853.17 27-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 3717528.00 5838.91 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 10036727.78 5237.01 30-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.265778E+09 5877.20 13-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.750724E+09 5957.94 26-DEC-13:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.258588E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.111026E+10 5969.11   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.191396E+10 6184.65 09-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.758587E+09 6112.47 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 95284308.64 6072.38 06-MAR-07:04 0.00 0.00 0.00 0.00 0.00
April 9559240.01 6044.22 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 15886528.72 6052.43 16-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.456041E+09 6071.96 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.128630E+10 6275.08 26-DEC-08:14 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.453562E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.191396E+10 6275.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119689E+10 5997.39 06-JAN-07:12 0.00 0.00 0.00 0.00 0.00
February 0.439518E+09 5949.47 18-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 60995734.90 5883.97 02-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 7110171.46 5880.77 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 10229093.36 3698.25 16-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.288893E+09 5903.92 28-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.803131E+09 5904.05 20-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.280676E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119689E+10 5997.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.792022E+10 12318.62 06-JAN-07:17 0.00 0.00 0.00 0.00 0.00
February 0.540835E+10 11795.85 08-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.315651E+10 12434.98 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.146131E+10 11714.94 19-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.426415E+09 5859.04 18-MAY-06:08 0.00 0.00 0.00 0.00 0.00
June 23234118.52 2015.19 15-JUN-06:05 0.00 0.00 0.00 0.00 0.00
July 318829.78 5.05 31-JUL-14:40 0.00 0.00 0.00 0.00 0.00
August 775474.35 4.96 29-AUG-14:30 0.00 0.00 0.00 0.00 0.00
September 80797884.14 3430.15 27-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.923272E+09 5892.63 16-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.418961E+10 11722.85 24-NOV-07:20 0.00 0.00 0.00 0.00 0.00
December 0.702305E+10 12447.18 26-DEC-08:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.306139E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 318829.78 4.96   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.792022E+10 12447.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.370176E+10 20662.14 03-JAN-07:06 0.00 0.00 0.00 0.00 0.00
February 0.142285E+10 20672.24 23-FEB-07:05 0.00 0.00 0.00 0.00 0.00
March 0.149650E+09 20665.20 13-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 452174.48 3792.38 18-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 29111042.60 20503.72 23-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.923048E+09 20668.56 27-NOV-06:15 0.00 0.00 0.00 0.00 0.00
December 0.243859E+10 20662.54 28-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.866547E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.370176E+10 20672.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.258373E+10 10216.30 30-JAN-06:16 0.00 0.00 0.00 0.00 0.00
February 0.122955E+10 10215.15 22-FEB-06:14 0.00 0.00 0.00 0.00 0.00
March 0.375832E+09 10428.27 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.102722E+09 10189.96 20-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 5162897.91 8916.47 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 2792458.07 2624.53 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.135354E+09 10189.92 27-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.994269E+09 10215.14 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.208393E+10 10438.16 26-DEC-08:07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.751334E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.258373E+10 10438.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.207840E+10 7097.88 06-JAN-07:09 0.00 0.00 0.00 0.00 0.00
February 0.101569E+10 6952.98 09-FEB-07:12 0.00 0.00 0.00 0.00 0.00
March 0.253419E+09 6907.41 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 45119238.08 6745.51 17-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 3540049.92 6008.28 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1055673.27 2103.33 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.107893E+09 6759.46 30-OCT-05:12 0.00 0.00 0.00 0.00 0.00
November 0.782237E+09 6766.14 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.165416E+10 6922.74 26-DEC-08:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.594152E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.207840E+10 7097.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.338694E+10 7770.96 07-JAN-07:50 0.00 0.00 0.00 0.00 0.00
February 0.180940E+10 7659.02 18-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.536627E+09 7461.30 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.122182E+09 7310.29 18-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 4679813.71 7298.66 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 4461838.22 3158.94 27-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.197858E+09 7306.86 13-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.133163E+10 7413.96 13-NOV-07:30 0.00 0.00 0.00 0.00 0.00
December 0.274588E+10 7576.64 26-DEC-09:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101397E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.338694E+10 7770.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.214337E+10 7470.88 07-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.108861E+10 7030.47 13-FEB-06:24 0.00 0.00 0.00 0.00 0.00
March 0.327915E+09 7174.54 01-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 78818297.98 7010.16 20-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 3421303.13 6380.11 18-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 2242256.11 1704.36 28-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.123554E+09 7009.92 17-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.835690E+09 7027.18 28-NOV-06:13 0.00 0.00 0.00 0.00 0.00
December 0.172449E+10 7190.58 26-DEC-08:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.632812E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.214337E+10 7470.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1258189.69 1125441.30 1070.81 02-JAN-10:30 959.52 0.00
February 0.00 0.00 0.200641E+09 0.184550E+09 12969.88 27-FEB-15:10 12969.88 0.00
March 0.00 0.00 0.530421E+09 0.476885E+09 10915.52 18-MAR-16:00 10915.52 0.00
April 0.00 0.00 0.639404E+10 0.619764E+10 51578.74 27-APR-15:00 51578.74 0.00
May 0.00 0.00 0.800266E+10 0.721387E+10 47197.76 15-MAY-16:00 47197.76 0.00
June 0.00 0.00 0.143724E+11 0.134310E+11 52946.67 28-JUN-15:30 52946.67 0.00
July 0.00 0.00 0.276307E+11 0.245183E+11 72039.91 31-JUL-15:50 65857.24 0.00
August 0.00 0.00 0.375451E+11 0.329391E+11 71006.32 10-AUG-15:40 67198.63 0.00
September 0.00 0.00 0.139503E+11 0.117035E+11 58396.42 12-SEP-16:00 54336.93 0.00
October 0.00 0.00 0.266424E+10 0.252042E+10 35126.82 04-OCT-15:00 35126.82 0.00
November 0.00 0.00 0.362717E+09 0.252449E+09 18890.90 04-NOV-15:00 14516.46 0.00
December 0.00 0.00 6678546.16 6169609.10 3550.29 05-DEC-12:00 3369.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.111661E+12 0.994451E+11       0.00
Minimum of Months 0.00 0.00 1258189.69 1125441.30 1070.81   959.52 0.00
Maximum of Months 0.00 0.00 0.375451E+11 0.329391E+11 72039.91   67198.63 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 203097.43 163444.72 1353.98 11-JAN-07:05 1089.63 0.00
February 0.00 0.00 0.182989E+09 0.167667E+09 12920.73 27-FEB-15:05 12920.73 0.00
March 0.00 0.00 0.279433E+09 0.249260E+09 11221.09 18-MAR-14:05 11221.09 0.00
April 0.00 0.00 0.343582E+10 0.330552E+10 50319.97 27-APR-14:05 50319.97 0.00
May 0.00 0.00 0.712293E+10 0.640224E+10 44026.64 04-MAY-15:00 44026.64 0.00
June 0.00 0.00 0.130912E+11 0.122071E+11 49084.63 28-JUN-15:30 49084.63 0.00
July 0.00 0.00 0.247676E+11 0.219924E+11 67971.42 31-JUL-14:05 60862.30 0.00
August 0.00 0.00 0.327368E+11 0.287115E+11 67015.65 10-AUG-14:05 60549.30 0.00
September 0.00 0.00 0.121953E+11 0.101700E+11 54286.94 13-SEP-14:05 41905.70 0.00
October 0.00 0.00 0.158148E+10 0.148336E+10 31703.47 04-OCT-15:00 31703.47 0.00
November 0.00 0.00 0.340540E+09 0.239897E+09 18844.83 04-NOV-14:05 14933.29 0.00
December 0.00 0.00 235862.49 161238.58 1572.42 29-DEC-07:05 1074.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.957345E+11 0.849293E+11       0.00
Minimum of Months 0.00 0.00 203097.43 161238.58 1353.98   1074.92 0.00
Maximum of Months 0.00 0.00 0.327368E+11 0.287115E+11 67971.42   60862.30 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.187718E+09 0.166529E+09 12047.39 27-FEB-15:00 12047.39 0.00
March 0.00 0.00 0.421801E+09 0.384852E+09 11377.32 01-MAR-15:00 11377.32 0.00
April 0.00 0.00 0.364843E+10 0.348248E+10 57162.53 27-APR-14:40 57162.53 0.00
May 0.00 0.00 0.744064E+10 0.661351E+10 47729.89 04-MAY-15:00 47729.89 0.00
June 0.00 0.00 0.137330E+11 0.127004E+11 56945.21 28-JUN-15:20 56945.21 0.00
July 0.00 0.00 0.263174E+11 0.231729E+11 74463.78 31-JUL-14:40 67734.67 0.00
August 0.00 0.00 0.343100E+11 0.299547E+11 74478.81 10-AUG-14:50 69282.63 0.00
September 0.00 0.00 0.122129E+11 0.100581E+11 53643.15 14-SEP-13:30 42360.83 0.00
October 0.00 0.00 0.144981E+10 0.134149E+10 31099.77 04-OCT-15:00 31099.77 0.00
November 0.00 0.00 0.346211E+09 0.235736E+09 18724.29 04-NOV-14:20 14028.89 0.00
December 0.00 0.00 68427.90 51442.45 228.09 18-DEC-06:10 171.47 0.00
                 
Annual Sum or Average 0.00 0.00 0.100068E+12 0.881107E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.343100E+11 0.299547E+11 74478.81   69282.63 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 19646.46 150171.43 25-JAN-07:02
February 0.00 0.00 01-FEB-00:10 11632.31 153710.22 09-FEB-07:01
March 0.00 0.00 01-MAR-00:10 4205.80 152296.43 01-MAR-07:01
April 0.00 0.00 01-APR-00:10 1697.05 124764.09 19-APR-06:02
May 0.00 0.00 01-MAY-00:10 506.94 64550.75 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 120.96 11443.85 15-JUN-06:05
July 0.00 0.00 01-JUL-00:10 19.54 9902.67 27-JUL-06:08
August 0.00 0.00 01-AUG-00:10 27.98 10031.54 03-AUG-06:06
September 0.00 0.00 01-SEP-00:10 147.52 30429.29 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 1176.95 116650.49 30-OCT-06:03
November 0.00 0.00 01-NOV-00:10 7690.77 143128.52 16-NOV-07:02
December 0.00 0.00 01-DEC-00:10 14946.00 146442.86 26-DEC-07:12
             
Annual Sum or Average 0.00     5128.26    
Minimum of Months 0.00 0.00   19.54 9902.67  
Maximum of Months 0.00 0.00   19646.46 153710.22  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 1702.15 6226.75 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 1724.48 6234.21 10-FEB-12:15
March 0.00 0.00 01-MAR-00:10 1823.75 6212.93 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 1649.61 6074.28 03-APR-11:25
May 0.00 0.00 01-MAY-00:10 1649.95 5885.01 01-MAY-11:17
June 0.00 0.00 01-JUN-00:10 1631.24 5653.23 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 1446.19 5455.82 03-JUL-12:00
August 0.00 0.00 01-AUG-00:10 1586.59 5376.20 31-AUG-11:50
September 0.00 0.00 01-SEP-00:10 1495.25 5493.63 29-SEP-11:15
October 0.00 0.00 01-OCT-00:10 1541.18 5706.34 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 1627.90 5930.79 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 1615.25 6114.33 29-DEC-12:20
             
Annual Sum or Average 0.00     1623.90    
Minimum of Months 0.00 0.00   1446.19 5376.20  
Maximum of Months 0.00 0.00   1823.75 6234.21  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116777E+10 0.29 2511.88 02-JAN-06:11 0.78
February 0.108009E+10 0.29 1730.04 27-FEB-15:30 0.64
March 0.154017E+10 0.31 2566.15 20-MAR-06:03 0.79
April 0.189459E+10 0.32 6241.33 27-APR-14:50 1.32
May 0.266116E+10 0.38 7097.49 15-MAY-14:50 1.44
June 0.332059E+10 0.43 6910.61 28-JUN-15:20 1.41
July 0.420661E+10 0.46 10195.13 31-JUL-15:10 1.80
August 0.493518E+10 0.51 10195.13 14-AUG-15:10 1.80
September 0.321734E+10 0.41 9395.93 11-SEP-15:50 1.71
October 0.200387E+10 0.32 6643.87 04-OCT-15:40 1.39
November 0.127696E+10 0.28 3270.86 06-NOV-07:03 0.90
December 0.114338E+10 0.28 1462.08 01-DEC-07:01 0.60
           
Annual Sum or Average 0.284477E+11 0.36      
Minimum of Months 0.108009E+10 0.28 1462.08   0.60
Maximum of Months 0.493518E+10 0.51 10195.13   1.80



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.104464E+10 0.29 2607.82 02-JAN-06:11 0.83
February 0.933967E+09 0.28 2607.82 06-FEB-07:01 0.83
March 0.120034E+10 0.30 2306.34 01-MAR-13:01 0.78
April 0.156121E+10 0.32 6700.44 27-APR-14:05 1.45
May 0.225394E+10 0.37 7324.18 15-MAY-14:05 1.54
June 0.280011E+10 0.41 6499.87 28-JUN-14:05 1.42
July 0.350439E+10 0.44 9091.34 31-JUL-14:30 1.76
August 0.400212E+10 0.48 9464.61 14-AUG-06:02 1.81
September 0.250974E+10 0.38 7996.17 11-SEP-15:00 1.62
October 0.143292E+10 0.30 5577.98 04-OCT-15:10 1.30
November 0.967647E+09 0.28 2607.82 24-NOV-07:01 0.83
December 0.984471E+09 0.28 2607.82 11-DEC-07:01 0.83
           
Annual Sum or Average 0.231955E+11 0.34      
Minimum of Months 0.933967E+09 0.28 2306.34   0.78
Maximum of Months 0.400212E+10 0.48 9464.61   1.81



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.127677E+10 0.35 2506.27 02-JAN-06:11 0.76
February 0.107260E+10 0.32 2506.27 01-FEB-07:03 0.76
March 0.125574E+10 0.33 2506.27 06-MAR-06:11 0.76
April 0.150508E+10 0.32 6453.32 27-APR-14:30 1.31
May 0.208793E+10 0.36 6981.26 15-MAY-14:40 1.39
June 0.256653E+10 0.39 6558.24 28-JUN-15:20 1.33
July 0.325634E+10 0.41 8955.66 31-JUL-14:50 1.61
August 0.363996E+10 0.44 8892.66 10-AUG-15:10 1.60
September 0.221907E+10 0.36 7189.18 11-SEP-14:50 1.40
October 0.134117E+10 0.31 4747.24 04-OCT-15:00 1.09
November 0.107857E+10 0.31 2506.27 10-NOV-07:02 0.76
December 0.114565E+10 0.31 2506.27 01-DEC-07:01 0.76
           
Annual Sum or Average 0.224454E+11 0.35      
Minimum of Months 0.107260E+10 0.31 2506.27   0.76
Maximum of Months 0.363996E+10 0.44 8955.66   1.61



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.363459E+09 0.330384E+09 544.02 17-JAN-08:10 494.51 494.51 44.30 1.76
February 0.207766E+09 0.188860E+09 543.71 18-FEB-07:03 494.23 494.23 41.13 1.76
March 85907407.72 78089833.62 492.85 06-MAR-07:02 448.00 448.00 39.72 1.47
April 34632944.06 31481346.15 465.72 18-APR-06:02 423.34 423.34 35.43 1.19
May 12018754.91 10925048.22 360.60 18-MAY-06:03 327.78 327.78 33.45 0.58
June 3709753.69 3372166.10 100.07 15-JUN-06:05 90.96 90.96 35.48 0.11
July 501836.93 456169.77 81.92 03-JUL-06:07 74.47 74.47 37.38 0.09
August 919767.49 836068.64 82.23 21-AUG-06:06 74.75 74.75 47.44 0.09
September 4027419.78 3660924.58 196.26 27-SEP-06:03 178.40 178.40 36.61 0.24
October 25225912.99 22930354.91 459.03 16-OCT-06:03 417.26 417.26 35.54 1.12
November 0.146753E+09 0.133399E+09 523.16 24-NOV-07:01 475.55 475.55 42.57 1.67
December 0.282339E+09 0.256646E+09 548.68 26-DEC-07:01 498.75 498.75 42.53 1.78
                 
Annual Sum or Average 0.116726E+10 0.106104E+10            
Minimum of Months 501836.93 456169.77 81.92   74.47 74.47 33.45 0.09
Maximum of Months 0.363459E+09 0.330384E+09 548.68   498.75 498.75 47.44 1.78



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:05 2.06 2.06 58.14 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:05 2.06 2.06 56.83 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:03 2.06 2.06 56.93 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.91 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:03 2.06 2.06 57.22 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.21 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:05 2.06 2.06 57.22 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.36 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.35 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.20 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:05 2.06 2.06 57.10 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:03 2.06 2.06 57.07 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.83 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.20 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 40.08 40.08 19646.46 150171.43 25-JAN-07:02
February 0.00 0.00 01-FEB-00:10 33.11 33.11 11632.31 153710.22 09-FEB-07:01
March 0.00 0.00 01-MAR-00:10 27.73 27.73 4205.80 152296.43 01-MAR-07:01
April 0.00 0.00 01-APR-00:10 25.28 25.28 1697.05 124764.09 19-APR-06:02
May 0.00 0.00 01-MAY-00:10 31.78 31.78 506.94 64550.75 18-MAY-06:03
June 0.00 0.00 01-JUN-00:10 47.14 47.14 120.96 11443.85 15-JUN-06:05
July 0.00 0.00 01-JUL-00:10 37.33 37.33 19.54 9902.67 27-JUL-06:08
August 0.00 0.00 01-AUG-00:10 33.10 33.10 27.98 10031.54 03-AUG-06:06
September 0.00 0.00 01-SEP-00:10 39.08 39.08 147.52 30429.29 28-SEP-06:03
October 0.00 0.00 01-OCT-00:10 42.28 42.28 1176.95 116650.49 30-OCT-06:03
November 0.00 0.00 01-NOV-00:10 29.74 29.74 7690.77 143128.52 16-NOV-07:02
December 0.00 0.00 01-DEC-00:10 35.80 35.80 14946.00 146442.86 26-DEC-07:12
                 
Annual Sum or Average 0.00         5128.26    
Minimum of Months 0.00 0.00   25.28 25.28 19.54 9902.67  
Maximum of Months 0.00 0.00   47.14 47.14 19646.46 153710.22  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 58.14 58.14 1702.15 6226.75 31-JAN-12:17
February 0.00 0.00 01-FEB-00:10 57.61 57.61 1724.48 6234.21 10-FEB-12:15
March 0.00 0.00 01-MAR-00:10 57.62 57.62 1823.75 6212.93 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 57.67 57.67 1649.61 6074.28 03-APR-11:25
May 0.00 0.00 01-MAY-00:10 58.21 58.21 1649.95 5885.01 01-MAY-11:17
June 0.00 0.00 01-JUN-00:10 57.84 57.84 1631.24 5653.23 01-JUN-11:20
July 0.00 0.00 01-JUL-00:10 57.91 57.91 1446.19 5455.82 03-JUL-12:00
August 0.00 0.00 01-AUG-00:10 57.96 57.96 1586.59 5376.20 31-AUG-11:50
September 0.00 0.00 01-SEP-00:10 57.95 57.95 1495.25 5493.63 29-SEP-11:15
October 0.00 0.00 01-OCT-00:10 57.03 57.03 1541.18 5706.34 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 57.82 57.82 1627.90 5930.79 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 57.73 57.73 1615.25 6114.33 29-DEC-12:20
                 
Annual Sum or Average 0.00         1623.90    
Minimum of Months 0.00 0.00   57.03 57.03 1446.19 5376.20  
Maximum of Months 0.00 0.00   58.21 58.21 1823.75 6234.21  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.167974E+11 0.00 0.00 0.116811E+10 0.00 0.00
February 0.903316E+10 0.00 0.00 0.113017E+10 0.00 0.00
March 0.361235E+10 0.00 0.00 0.167803E+10 0.00 0.00
April 0.146057E+10 0.00 0.00 0.338887E+10 0.00 0.00
May 0.652171E+09 0.00 0.00 0.449405E+10 0.00 0.00
June 0.292130E+09 0.00 0.00 0.658633E+10 0.00 0.00
July 54313742.93 0.00 0.00 0.103927E+11 0.00 0.00
August 71284091.05 0.00 0.00 0.133970E+11 0.00 0.00
September 0.259538E+09 0.00 0.00 0.633271E+10 0.00 0.00
October 0.100341E+10 0.00 0.00 0.263663E+10 0.00 0.00
November 0.587173E+10 0.00 0.00 0.136301E+10 0.00 0.00
December 0.119598E+11 0.00 0.00 0.114515E+10 0.00 0.00
             
Annual Sum or Average 0.510679E+11 0.00 0.00 0.537128E+11 0.00 0.00
Minimum of Months 54313742.93 0.00 0.00 0.113017E+10 0.00 0.00
Maximum of Months 0.167974E+11 0.00 0.00 0.133970E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.144066E+11 0.00 0.00 0.104469E+10 0.00 0.00
February 0.735912E+10 0.00 0.00 0.979684E+09 0.00 0.00
March 0.294562E+10 0.00 0.00 0.127171E+10 0.00 0.00
April 0.116120E+10 0.00 0.00 0.235381E+10 0.00 0.00
May 0.267352E+09 0.00 0.00 0.387684E+10 0.00 0.00
June 6781226.95 0.00 0.00 0.578328E+10 0.00 0.00
July 329370.35 0.00 0.00 0.906586E+10 0.00 0.00
August 832631.53 0.00 0.00 0.114130E+11 0.00 0.00
September 34015869.11 0.00 0.00 0.524473E+10 0.00 0.00
October 0.664914E+09 0.00 0.00 0.180735E+10 0.00 0.00
November 0.516087E+10 0.00 0.00 0.104743E+10 0.00 0.00
December 0.107064E+11 0.00 0.00 0.984534E+09 0.00 0.00
             
Annual Sum or Average 0.427140E+11 0.00 0.00 0.448729E+11 0.00 0.00
Minimum of Months 329370.35 0.00 0.00 0.979684E+09 0.00 0.00
Maximum of Months 0.144066E+11 0.00 0.00 0.114130E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.218144E+11 0.00 0.00 0.127677E+10 0.00 0.00
February 0.119745E+11 0.00 0.00 0.111985E+10 0.00 0.00
March 0.479996E+10 0.00 0.00 0.136333E+10 0.00 0.00
April 0.181060E+10 0.00 0.00 0.234915E+10 0.00 0.00
May 0.443219E+09 0.00 0.00 0.378919E+10 0.00 0.00
June 23234118.52 0.00 0.00 0.570979E+10 0.00 0.00
July 318829.78 0.00 0.00 0.918872E+10 0.00 0.00
August 775474.35 0.00 0.00 0.114564E+11 0.00 0.00
September 91350109.82 0.00 0.00 0.497567E+10 0.00 0.00
October 0.151704E+10 0.00 0.00 0.168903E+10 0.00 0.00
November 0.905648E+10 0.00 0.00 0.116052E+10 0.00 0.00
December 0.176701E+11 0.00 0.00 0.114567E+10 0.00 0.00
             
Annual Sum or Average 0.692020E+11 0.00 0.00 0.452241E+11 0.00 0.00
Minimum of Months 318829.78 0.00 0.00 0.111985E+10 0.00 0.00
Maximum of Months 0.218144E+11 0.00 0.00 0.114564E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.116777E+10 1258189.69 0.167974E+11 0.00 0.00 0.00 0.00 0.00
February 0.108009E+10 0.200641E+09 0.903316E+10 0.00 0.00 0.00 0.00 0.00
March 0.154017E+10 0.530421E+09 0.361235E+10 0.00 0.00 0.00 0.00 0.00
April 0.189459E+10 0.639404E+10 0.146057E+10 0.00 0.00 0.00 0.00 0.00
May 0.266116E+10 0.800266E+10 0.652171E+09 0.00 0.00 0.00 0.00 0.00
June 0.332059E+10 0.143724E+11 0.292130E+09 0.00 0.00 0.00 0.00 0.00
July 0.420661E+10 0.276307E+11 54313742.93 0.00 0.00 0.00 0.00 0.00
August 0.493518E+10 0.375451E+11 71284091.05 0.00 0.00 0.00 0.00 0.00
September 0.321734E+10 0.139503E+11 0.259538E+09 0.00 0.00 0.00 0.00 0.00
October 0.200387E+10 0.266424E+10 0.100341E+10 0.00 0.00 0.00 0.00 0.00
November 0.127696E+10 0.362717E+09 0.587173E+10 0.00 0.00 0.00 0.00 0.00
December 0.114338E+10 6678546.16 0.119598E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.284477E+11 0.111661E+12 0.510679E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108009E+10 1258189.69 54313742.93 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.493518E+10 0.375451E+11 0.167974E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.104464E+10 203097.43 0.144066E+11 0.00 0.00 0.00 0.00 0.00
February 0.933967E+09 0.182989E+09 0.735912E+10 0.00 0.00 0.00 0.00 0.00
March 0.120034E+10 0.279433E+09 0.294562E+10 0.00 0.00 0.00 0.00 0.00
April 0.156121E+10 0.343582E+10 0.116120E+10 0.00 0.00 0.00 0.00 0.00
May 0.225394E+10 0.712293E+10 0.267352E+09 0.00 0.00 0.00 0.00 0.00
June 0.280011E+10 0.130912E+11 6781226.95 0.00 0.00 0.00 0.00 0.00
July 0.350439E+10 0.247676E+11 329370.35 0.00 0.00 0.00 0.00 0.00
August 0.400212E+10 0.327368E+11 832631.53 0.00 0.00 0.00 0.00 0.00
September 0.250974E+10 0.121953E+11 34015869.11 0.00 0.00 0.00 0.00 0.00
October 0.143292E+10 0.158148E+10 0.664914E+09 0.00 0.00 0.00 0.00 0.00
November 0.967647E+09 0.340540E+09 0.516087E+10 0.00 0.00 0.00 0.00 0.00
December 0.984471E+09 235862.49 0.107064E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.231955E+11 0.957345E+11 0.427140E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.933967E+09 203097.43 329370.35 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400212E+10 0.327368E+11 0.144066E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.127677E+10 0.00 0.218144E+11 0.00 0.00 0.00 0.00 0.00
February 0.107260E+10 0.187718E+09 0.119745E+11 0.00 0.00 0.00 0.00 0.00
March 0.125574E+10 0.421801E+09 0.479996E+10 0.00 0.00 0.00 0.00 0.00
April 0.150508E+10 0.364843E+10 0.181060E+10 0.00 0.00 0.00 0.00 0.00
May 0.208793E+10 0.744064E+10 0.443219E+09 0.00 0.00 0.00 0.00 0.00
June 0.256653E+10 0.137330E+11 23234118.52 0.00 0.00 0.00 0.00 0.00
July 0.325634E+10 0.263174E+11 318829.78 0.00 0.00 0.00 0.00 0.00
August 0.363996E+10 0.343100E+11 775474.35 0.00 0.00 0.00 0.00 0.00
September 0.221907E+10 0.122129E+11 91350109.82 0.00 0.00 0.00 0.00 0.00
October 0.134117E+10 0.144981E+10 0.151704E+10 0.00 0.00 0.00 0.00 0.00
November 0.107857E+10 0.346211E+09 0.905648E+10 0.00 0.00 0.00 0.00 0.00
December 0.114565E+10 68427.90 0.176701E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.224454E+11 0.100068E+12 0.692020E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.107260E+10 0.00 318829.78 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.363996E+10 0.343100E+11 0.218144E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.116777E+10 0.167974E+11 0.00 0.00 338915.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.108009E+10 0.903316E+10 0.00 0.00 50082578.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.154017E+10 0.361235E+10 0.00 0.00 0.137868E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189459E+10 0.146057E+10 0.00 0.00 0.149428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.266116E+10 0.652171E+09 0.00 0.00 0.183288E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.332059E+10 0.292130E+09 0.00 0.00 0.326573E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.420661E+10 54313742.93 0.00 0.00 0.618611E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.493518E+10 71284091.05 0.00 0.00 0.846185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.321734E+10 0.259538E+09 0.00 0.00 0.311537E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200387E+10 0.100341E+10 0.00 0.00 0.632768E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.127696E+10 0.587173E+10 0.00 0.00 86041694.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.114338E+10 0.119598E+11 0.00 0.00 1769724.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.284477E+11 0.510679E+11 0.00 0.00 0.252651E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108009E+10 54313742.93 0.00 0.00 338915.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.493518E+10 0.167974E+11 0.00 0.00 0.846185E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.104464E+10 0.144066E+11 0.00 0.00 54479.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.933967E+09 0.735912E+10 0.00 0.00 45717435.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.120034E+10 0.294562E+10 0.00 0.00 71371477.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.156121E+10 0.116120E+10 0.00 0.00 0.792603E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.225394E+10 0.267352E+09 0.00 0.00 0.162291E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.280011E+10 6781226.95 0.00 0.00 0.298318E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.350439E+10 329370.35 0.00 0.00 0.556146E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.400212E+10 832631.53 0.00 0.00 0.741084E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.250974E+10 34015869.11 0.00 0.00 0.273499E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.143292E+10 0.664914E+09 0.00 0.00 0.374436E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.967647E+09 0.516087E+10 0.00 0.00 79783181.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.984471E+09 0.107064E+11 0.00 0.00 63114.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.231955E+11 0.427140E+11 0.00 0.00 0.216774E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.933967E+09 329370.35 0.00 0.00 54479.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400212E+10 0.144066E+11 0.00 0.00 0.741084E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.127677E+10 0.218144E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.107260E+10 0.119745E+11 0.00 0.00 47247022.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.125574E+10 0.479996E+10 0.00 0.00 0.107590E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.150508E+10 0.181060E+10 0.00 0.00 0.844071E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.208793E+10 0.443219E+09 0.00 0.00 0.170126E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.256653E+10 23234118.52 0.00 0.00 0.314326E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.325634E+10 318829.78 0.00 0.00 0.593238E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.363996E+10 775474.35 0.00 0.00 0.781647E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.221907E+10 91350109.82 0.00 0.00 0.275660E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.134117E+10 0.151704E+10 0.00 0.00 0.347861E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.107857E+10 0.905648E+10 0.00 0.00 81951757.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.114565E+10 0.176701E+11 0.00 0.00 18594.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.224454E+11 0.692020E+11 0.00 0.00 0.227787E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.107260E+10 318829.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.363996E+10 0.218144E+11 0.00 0.00 0.781647E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.773309E+10 0.00 0.00 6892783.05 0.00 0.210284E+09 0.545117E+10 0.00 0.30
February 0.345389E+10 0.00 0.00 15798687.48 0.00 0.00 0.100879E+11 0.00 0.37
March 0.914824E+09 0.00 0.00 34619339.63 0.00 0.00 0.177137E+11 0.00 0.51
April 0.588327E+09 11398282.69 0.00 37789889.27 0.00 0.00 0.163724E+11 0.00 0.55
May 0.777302E+09 5947970.90 0.00 45976414.57 0.00 0.00 0.214732E+11 0.00 0.92
June 0.619959E+09 8478286.52 0.00 48447330.28 1343954.26 0.00 0.204021E+11 0.00 1.10
July 0.601362E+09 0.145998E+09 0.00 44340347.90 12019632.70 0.00 0.146454E+11 0.00 1.05
August 0.390155E+09 0.413820E+09 0.00 43531628.13 14498648.47 0.00 0.128313E+11 0.00 1.02
September 0.652138E+09 7289016.94 0.00 45437183.41 0.00 0.00 0.188341E+11 0.00 1.01
October 0.599668E+09 0.00 0.00 38399351.21 0.00 0.00 0.193870E+11 0.00 0.67
November 0.198430E+10 0.00 0.00 22997533.53 0.00 0.00 0.138585E+11 0.00 0.43
December 0.509253E+10 0.00 0.00 13409432.01 0.00 0.00 0.915357E+10 0.00 0.32
                   
Annual Sum or Average 0.234075E+11 0.592932E+09 0.00 0.397640E+09 27862235.43 0.210284E+09 0.180210E+12 0.00 0.69
Minimum of Months 0.390155E+09 0.00 0.00 6892783.05 0.00 0.00 0.545117E+10 0.00 0.30
Maximum of Months 0.773309E+10 0.413820E+09 0.00 48447330.28 14498648.47 0.210284E+09 0.214732E+11 0.00 1.10



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.118454E+11 0.00 0.00 0.00 0.00 0.551163E+09 0.00 0.00 0.29
February 0.100888E+11 0.00 0.00 641230.22 0.00 47204684.99 0.858370E+09 0.00 0.30
March 0.752265E+10 0.00 0.00 6072863.43 0.00 547010.06 0.521991E+10 0.00 0.34
April 0.413467E+10 4994189.11 0.00 13419145.70 4573824.42 0.00 0.807272E+10 0.00 0.41
May 0.224174E+10 4189721.41 0.00 23580500.49 0.00 0.00 0.123421E+11 0.00 0.60
June 0.121301E+10 4783740.16 0.00 28364571.95 1234226.49 0.00 0.126630E+11 0.00 0.73
July 0.108935E+10 0.102501E+09 0.00 26621396.73 9289984.53 0.00 0.908884E+10 0.00 0.71
August 0.776501E+09 0.302718E+09 0.00 25932222.33 11031100.27 0.00 0.794305E+10 0.00 0.69
September 0.170625E+10 4414696.95 0.00 23315556.73 0.00 0.00 0.103888E+11 0.00 0.64
October 0.461719E+10 0.00 0.00 11832904.97 0.00 0.00 0.786191E+10 0.00 0.42
November 0.912719E+10 0.00 0.00 2394869.38 0.00 3318247.42 0.224609E+10 0.00 0.31
December 0.117194E+11 0.00 0.00 86209.70 0.00 0.107433E+09 0.217869E+09 0.00 0.28
                   
Annual Sum or Average 0.660822E+11 0.423601E+09 0.00 0.162261E+09 26129135.71 0.709666E+09 0.769027E+11 0.00 0.48
Minimum of Months 0.776501E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.118454E+11 0.302718E+09 0.00 28364571.95 11031100.27 0.551163E+09 0.126630E+11 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.946198E+10 0.00 0.00 0.00 0.00 0.213255E+10 0.00 0.00 0.28
February 0.938729E+10 0.00 0.00 170817.97 0.00 0.718125E+09 0.171337E+09 0.00 0.30
March 0.959861E+10 0.00 0.00 1965713.84 0.00 58661171.38 0.216026E+10 0.00 0.33
April 0.551719E+10 1233783.47 0.00 9102046.46 53527.91 0.00 0.591657E+10 0.00 0.40
May 0.339243E+10 1165444.85 0.00 19223162.94 0.00 0.00 0.104451E+11 0.00 0.57
June 0.194743E+10 1581466.12 0.00 24345502.68 757601.64 0.00 0.114548E+11 0.00 0.71
July 0.157886E+10 84186888.01 0.00 22967666.33 10907986.38 0.00 0.826569E+10 0.00 0.71
August 0.120151E+10 0.229993E+09 0.00 22240071.76 29048358.95 0.00 0.659234E+10 0.00 0.68
September 0.294276E+10 938235.12 0.00 16712555.97 0.00 0.00 0.773550E+10 0.00 0.59
October 0.648765E+10 0.00 0.00 5699625.95 0.00 2859729.68 0.432580E+10 0.00 0.38
November 0.938042E+10 0.00 0.00 405400.90 0.00 0.293240E+09 0.631303E+09 0.00 0.30
December 0.971836E+10 0.00 0.00 0.00 0.00 0.135750E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.706145E+11 0.319099E+09 0.00 0.122833E+09 40767474.89 0.456294E+10 0.576987E+11 0.00 0.46
Minimum of Months 0.120151E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.971836E+10 0.229993E+09 0.00 24345502.68 29048358.95 0.213255E+10 0.114548E+11 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.572097E+09 0.00 0.00 0.00 0.00 0.197166E+10 0.00 0.00 0.29
February 0.991482E+09 0.00 0.00 0.00 0.00 0.122217E+10 0.00 0.00 0.30
March 0.207650E+10 0.00 0.00 35038.08 0.00 0.321542E+09 83745373.34 0.00 0.33
April 0.154558E+10 347044.33 0.00 1208079.58 11301.47 74384260.14 0.725907E+09 0.00 0.39
May 0.101628E+10 533673.09 0.00 3989918.69 0.00 2601703.00 0.203116E+10 0.00 0.63
June 0.576575E+09 480656.47 0.00 5684807.72 159954.10 0.00 0.249696E+10 0.00 0.83
July 0.433301E+09 26012062.01 0.00 5668924.18 2303027.13 0.00 0.192649E+10 0.00 0.86
August 0.393469E+09 69918857.62 0.00 4840169.99 5808646.88 0.00 0.133363E+10 0.00 0.76
September 0.993603E+09 259766.41 0.00 2799277.74 0.00 618889.31 0.117415E+10 0.00 0.59
October 0.173530E+10 0.00 0.00 406088.22 0.00 0.113039E+09 0.322133E+09 0.00 0.36
November 0.127546E+10 0.00 0.00 0.00 0.00 0.921966E+09 0.00 0.00 0.30
December 0.662598E+09 0.00 0.00 0.00 0.00 0.173926E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.122722E+11 97552059.93 0.00 24632304.22 8282929.58 0.636725E+10 0.100942E+11 0.00 0.49
Minimum of Months 0.393469E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.207650E+10 69918857.62 0.00 5684807.72 5808646.88 0.197166E+10 0.249696E+10 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.487183E+09 0.00 0.00 0.00 0.00 0.114808E+10 0.00 0.00 0.30
February 0.724245E+09 0.00 0.00 15186.37 0.00 0.659378E+09 21745941.62 0.00 0.30
March 0.110049E+10 0.00 0.00 725640.87 0.00 0.148710E+09 0.450916E+09 0.00 0.35
April 0.690722E+09 309992.13 0.00 3078339.99 0.00 26122588.36 0.155634E+10 0.00 0.62
May 0.489559E+09 483869.61 0.00 5152592.39 0.00 1653620.65 0.244935E+10 0.00 0.95
June 0.248378E+09 336585.20 0.00 7363862.76 100851.30 0.00 0.316961E+10 0.00 1.38
July 0.196319E+09 22819485.57 0.00 7506196.09 429261.64 0.00 0.222734E+10 0.00 1.37
August 0.157344E+09 64142226.07 0.00 6928176.13 815613.47 0.00 0.170904E+10 0.00 1.33
September 0.483869E+09 299320.42 0.00 4409123.91 0.00 390210.64 0.171654E+10 0.00 0.97
October 0.877469E+09 0.00 0.00 1283890.94 0.00 62352347.90 0.762881E+09 0.00 0.45
November 0.859968E+09 0.00 0.00 8343.31 0.00 0.516649E+09 14763367.83 0.00 0.30
December 0.541254E+09 0.00 0.00 0.00 0.00 0.100203E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.685680E+10 88391479.00 0.00 36471352.76 1345726.40 0.356537E+10 0.140785E+11 0.00 0.72
Minimum of Months 0.157344E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.110049E+10 64142226.07 0.00 7506196.09 815613.47 0.114808E+10 0.316961E+10 0.00 1.38



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.101433E+10 0.00 0.00 346410.04 0.00 0.140060E+10 0.226324E+09 0.00 0.30
February 0.108056E+10 0.00 0.00 2058801.58 0.00 0.734149E+09 0.105326E+10 0.00 0.40
March 0.146967E+10 0.00 0.00 4750972.70 0.00 0.228728E+09 0.244313E+10 0.00 0.56
April 0.101335E+10 958672.63 0.00 6341940.36 0.00 65630266.60 0.318012E+10 0.00 0.76
May 0.829714E+09 1011000.12 0.00 8414979.40 0.00 2805611.65 0.392554E+10 0.00 1.00
June 0.536563E+09 615939.09 0.00 8790066.65 159250.61 0.00 0.368197E+10 0.00 1.15
July 0.405577E+09 48224861.93 0.00 9327204.47 301815.03 0.00 0.286936E+10 0.00 1.26
August 0.335964E+09 0.145674E+09 0.00 8807692.86 757827.48 0.00 0.215232E+10 0.00 1.21
September 0.708014E+09 1427427.94 0.00 10191041.02 0.00 616167.40 0.359113E+10 0.00 1.33
October 0.117686E+10 0.00 0.00 5489445.65 0.00 81484785.13 0.307526E+10 0.00 0.76
November 0.131782E+10 0.00 0.00 1135807.55 0.00 0.663994E+09 0.470656E+09 0.00 0.36
December 0.941477E+09 0.00 0.00 1025734.67 0.00 0.122905E+10 0.532184E+09 0.00 0.32
                   
Annual Sum or Average 0.108299E+11 0.197912E+09 0.00 66680096.95 1218893.12 0.440706E+10 0.272012E+11 0.00 0.79
Minimum of Months 0.335964E+09 0.00 0.00 346410.04 0.00 0.00 0.226324E+09 0.00 0.30
Maximum of Months 0.146967E+10 0.145674E+09 0.00 10191041.02 757827.48 0.140060E+10 0.392554E+10 0.00 1.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.456261E+09 0.00 0.00 0.00 0.00 0.120001E+10 0.00 0.00 0.30
February 0.639887E+09 0.00 0.00 161163.75 0.00 0.697891E+09 0.121610E+09 0.00 0.32
March 0.109936E+10 0.00 0.00 951490.62 0.00 0.203310E+09 0.578075E+09 0.00 0.40
April 0.809035E+09 508233.25 0.00 2648196.99 0.00 52700824.42 0.133095E+10 0.00 0.63
May 0.515132E+09 426331.67 0.00 6202897.67 0.00 3402759.13 0.242917E+10 0.00 1.05
June 0.324973E+09 1207608.51 0.00 6345144.30 101453.62 0.00 0.236273E+10 0.00 1.26
July 0.238686E+09 45438304.81 0.00 7880879.69 370356.68 0.00 0.201450E+10 0.00 1.48
August 0.213343E+09 96774598.51 0.00 5800211.65 1667913.61 0.00 0.128338E+10 0.00 1.13
September 0.492204E+09 502816.97 0.00 4746730.35 0.00 392541.12 0.160087E+10 0.00 1.03
October 0.963872E+09 0.00 0.00 1185168.23 0.00 73229363.68 0.712640E+09 0.00 0.48
November 0.801651E+09 0.00 0.00 73408.06 0.00 0.561947E+09 43130861.23 0.00 0.31
December 0.492413E+09 0.00 0.00 5124.98 0.00 0.105371E+10 6319637.18 0.00 0.29
                   
Annual Sum or Average 0.704682E+10 0.144858E+09 0.00 36000416.31 2139723.91 0.384660E+10 0.124834E+11 0.00 0.73
Minimum of Months 0.213343E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.109936E+10 96774598.51 0.00 7880879.69 1667913.61 0.120001E+10 0.242917E+10 0.00 1.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.886414E+09 0.00 0.00 0.00 0.00 0.179750E+10 0.00 0.00 0.29
February 0.137703E+10 0.00 0.00 0.00 0.00 0.939593E+09 0.00 0.00 0.29
March 0.233387E+10 0.00 0.00 0.00 0.00 0.118710E+09 0.00 0.00 0.31
April 0.171714E+10 950912.70 0.00 303784.99 712174.47 9787739.88 0.208146E+09 0.00 0.30
May 0.116740E+10 986939.59 0.00 2456131.99 0.00 0.00 0.125821E+10 0.00 0.50
June 0.600482E+09 1295717.98 0.00 4307169.86 283326.95 0.00 0.186526E+10 0.00 0.66
July 0.376615E+09 25939558.43 0.00 4765241.97 2533929.88 0.00 0.157632E+10 0.00 0.70
August 0.366626E+09 75125778.84 0.00 4116007.68 3056545.85 0.00 0.122559E+10 0.00 0.64
September 0.962403E+09 906349.58 0.00 2551038.52 2568.38 0.00 0.111082E+10 0.00 0.54
October 0.187097E+10 0.00 0.00 457333.04 0.00 372645.71 0.324800E+09 0.00 0.35
November 0.196332E+10 0.00 0.00 0.00 0.00 0.329541E+09 0.00 0.00 0.29
December 0.129541E+10 0.00 0.00 0.00 0.00 0.125044E+10 0.00 0.00 0.27
                   
Annual Sum or Average 0.149177E+11 0.105205E+09 0.00 18956708.06 6588545.53 0.444594E+10 0.756914E+10 0.00 0.43
Minimum of Months 0.366626E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.233387E+10 75125778.84 0.00 4765241.97 3056545.85 0.179750E+10 0.186526E+10 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.673129E+09 0.00 0.00 0.00 0.00 0.105790E+10 0.00 0.00 0.29
February 0.104426E+10 0.00 0.00 0.00 0.00 0.428218E+09 0.00 0.00 0.30
March 0.131536E+10 0.00 0.00 396222.02 0.00 27108004.60 0.264247E+09 0.00 0.32
April 0.737458E+09 1222708.59 0.00 2380582.62 450438.82 2368705.40 0.893010E+09 0.00 0.42
May 0.499246E+09 1134190.08 0.00 4089640.96 0.00 0.00 0.185157E+10 0.00 0.79
June 0.233225E+09 1146684.25 0.00 6409939.11 179199.71 0.00 0.265145E+10 0.00 1.21
July 0.150158E+09 28980678.05 0.00 6413103.35 1373044.65 0.00 0.192749E+10 0.00 1.18
August 0.127505E+09 82152674.21 0.00 6268719.05 738751.76 0.00 0.166649E+10 0.00 1.19
September 0.407879E+09 1143877.86 0.00 4433962.40 0.00 0.00 0.171663E+10 0.00 0.93
October 0.908026E+09 0.00 0.00 1563421.14 0.00 94994.91 0.849410E+09 0.00 0.45
November 0.124491E+10 0.00 0.00 19836.24 0.00 0.183213E+09 26146067.78 0.00 0.29
December 0.919455E+09 0.00 0.00 0.00 0.00 0.708398E+09 0.00 0.00 0.28
                   
Annual Sum or Average 0.826062E+10 0.115781E+09 0.00 31975426.88 2741434.94 0.240730E+10 0.118464E+11 0.00 0.64
Minimum of Months 0.127505E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.131536E+10 82152674.21 0.00 6413103.35 1373044.65 0.105790E+10 0.265145E+10 0.00 1.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.630955E+09 0.00 0.00 17299.49 0.00 0.343502E+10 22106446.33 0.00 0.43
February 0.110078E+10 0.00 0.00 321158.27 0.00 0.201400E+10 0.203492E+09 0.00 0.42
March 0.164776E+10 0.00 0.00 1142094.04 0.00 0.116354E+10 0.696156E+09 0.00 0.45
April 0.129585E+10 5412118.78 0.00 1906482.69 0.00 0.605487E+09 0.750216E+09 0.00 0.44
May 0.130774E+10 2205590.05 0.00 3176330.28 0.00 0.381982E+09 0.134719E+10 0.00 0.67
June 0.936213E+09 1998517.22 0.00 4219607.89 284323.82 0.184233E+09 0.156868E+10 0.00 0.78
July 0.499577E+09 55894206.21 0.00 5849230.76 2051138.18 38892720.79 0.167323E+10 0.00 0.91
August 0.473317E+09 0.182191E+09 0.00 6009796.79 1154386.50 39514805.23 0.139816E+10 0.00 0.95
September 0.823792E+09 4723649.99 0.00 7346723.83 0.00 0.156719E+09 0.228395E+10 0.00 1.07
October 0.128582E+10 0.00 0.00 3357319.79 0.00 0.532493E+09 0.182653E+10 0.00 0.63
November 0.140111E+10 0.00 0.00 377508.16 0.00 0.170867E+10 0.118133E+09 0.00 0.42
December 0.854524E+09 0.00 0.00 250343.68 0.00 0.283661E+10 0.170203E+09 0.00 0.41
                   
Annual Sum or Average 0.122574E+11 0.252425E+09 0.00 33973895.66 3489848.51 0.130972E+11 0.120581E+11 0.00 0.63
Minimum of Months 0.473317E+09 0.00 0.00 17299.49 0.00 38892720.79 22106446.33 0.00 0.41
Maximum of Months 0.164776E+10 0.182191E+09 0.00 7346723.83 2051138.18 0.343502E+10 0.228395E+10 0.00 1.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.628537E+09 0.00 0.00 0.00 0.00 0.110781E+10 0.00 0.00 0.29
February 0.980986E+09 0.00 0.00 74348.67 0.00 0.443373E+09 61108965.73 0.00 0.30
March 0.131503E+10 0.00 0.00 469726.13 0.00 60456816.39 0.290031E+09 0.00 0.34
April 0.813495E+09 2030403.61 0.00 1698369.03 156886.47 6065162.41 0.713405E+09 0.00 0.41
May 0.462767E+09 971562.51 0.00 4772807.12 0.00 0.00 0.184329E+10 0.00 0.84
June 0.258245E+09 3345901.09 0.00 5385032.11 179282.05 0.00 0.198052E+10 0.00 1.06
July 0.147772E+09 46451065.36 0.00 6274587.32 422469.11 0.00 0.183463E+10 0.00 1.28
August 0.150837E+09 0.104442E+09 0.00 5407161.10 1437936.69 0.00 0.131520E+10 0.00 1.03
September 0.357076E+09 1653583.98 0.00 4601294.58 0.00 0.00 0.161314E+10 0.00 0.95
October 0.959650E+09 0.00 0.00 1314785.87 0.00 0.00 0.734937E+09 0.00 0.46
November 0.122893E+10 0.00 0.00 62239.13 0.00 0.186890E+09 42563210.73 0.00 0.30
December 0.909401E+09 0.00 0.00 2523.88 0.00 0.717697E+09 4291878.73 0.00 0.28
                   
Annual Sum or Average 0.821272E+10 0.158894E+09 0.00 30062874.94 2196574.32 0.252229E+10 0.104331E+11 0.00 0.63
Minimum of Months 0.147772E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.131503E+10 0.104442E+09 0.00 6274587.32 1437936.69 0.110781E+10 0.198052E+10 0.00 1.28



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106994E+10 0.00 0.00 0.00 0.00 0.156607E+10 0.00 0.00 0.29
February 0.165905E+10 0.00 0.00 6148.42 0.00 0.642182E+09 23495908.59 0.00 0.30
March 0.238999E+10 0.00 0.00 89527.51 0.00 70825638.80 0.140548E+09 0.00 0.33
April 0.149883E+10 1418525.92 0.00 1568852.58 963490.04 5025079.47 0.907555E+09 0.00 0.39
May 0.856517E+09 1851339.61 0.00 4612046.35 0.00 0.00 0.225053E+10 0.00 0.64
June 0.433073E+09 1520992.89 0.00 6337937.00 259993.57 0.00 0.267639E+10 0.00 0.84
July 0.308925E+09 32547021.00 0.00 6152142.61 1956963.53 0.00 0.204321E+10 0.00 0.85
August 0.297095E+09 92643643.19 0.00 5283716.19 2323734.86 0.00 0.155339E+10 0.00 0.76
September 0.840954E+09 1171458.18 0.00 3515103.22 0.00 0.00 0.147426E+10 0.00 0.62
October 0.182132E+10 0.00 0.00 762021.53 0.00 5426718.97 0.518753E+09 0.00 0.37
November 0.193767E+10 0.00 0.00 0.00 0.00 0.429886E+09 0.00 0.00 0.30
December 0.135848E+10 0.00 0.00 0.00 0.00 0.119823E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.144719E+11 0.131153E+09 0.00 28327495.40 5504181.99 0.391765E+10 0.115881E+11 0.00 0.50
Minimum of Months 0.297095E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.238999E+10 92643643.19 0.00 6337937.00 2323734.86 0.156607E+10 0.267639E+10 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.578338E+09 0.00 0.00 0.00 0.00 0.837231E+09 0.00 0.00 0.24
February 0.839217E+09 0.00 0.00 64786.47 0.00 0.335496E+09 53629946.55 0.00 0.25
March 0.103064E+10 0.00 0.00 1043046.85 0.00 27197672.28 0.585475E+09 0.00 0.32
April 0.573381E+09 1735686.56 0.00 3350867.49 2209.09 2731839.89 0.163996E+10 0.00 0.59
May 0.420249E+09 1570783.84 0.00 5215346.33 0.00 0.00 0.234846E+10 0.00 0.91
June 0.209287E+09 1055583.03 0.00 7375783.27 164619.24 0.00 0.300961E+10 0.00 1.30
July 0.150425E+09 27217201.16 0.00 7304590.86 1037489.27 0.00 0.212887E+10 0.00 1.28
August 0.128602E+09 78712627.60 0.00 6785373.51 711321.87 0.00 0.176775E+10 0.00 1.25
September 0.384576E+09 1030891.18 0.00 4683748.31 395.14 0.00 0.179691E+10 0.00 0.94
October 0.790971E+09 0.00 0.00 1630612.95 0.00 3730582.49 0.918921E+09 0.00 0.44
November 0.956152E+09 0.00 0.00 59836.94 0.00 0.251696E+09 43726803.09 0.00 0.25
December 0.708963E+09 0.00 0.00 0.00 0.00 0.662476E+09 0.00 0.00 0.24
                   
Annual Sum or Average 0.677080E+10 0.111323E+09 0.00 37513992.98 1916034.60 0.212056E+10 0.142933E+11 0.00 0.67
Minimum of Months 0.128602E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.103064E+10 78712627.60 0.00 7375783.27 1037489.27 0.837231E+09 0.300961E+10 0.00 1.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.142308E+10 0.00 0.00 593359.93 0.00 0.102209E+10 0.364355E+09 0.00 0.31
February 0.149664E+10 0.00 0.00 2567209.88 0.00 0.404285E+09 0.124976E+10 0.00 0.42
March 0.167913E+10 0.00 0.00 5611395.72 0.00 41643961.64 0.276256E+10 0.00 0.60
April 0.100302E+10 8121619.51 0.00 6800127.50 0.00 4493940.47 0.329795E+10 0.00 0.77
May 0.731107E+09 3467695.45 0.00 8918293.60 0.00 0.00 0.392700E+10 0.00 1.02
June 0.448113E+09 1908634.65 0.00 9198124.67 259946.29 0.00 0.364066E+10 0.00 1.15
July 0.329035E+09 56154010.98 0.00 9116977.07 1598077.16 0.00 0.276432E+10 0.00 1.22
August 0.273593E+09 0.182973E+09 0.00 8735987.00 769366.53 0.00 0.223992E+10 0.00 1.16
September 0.590345E+09 5976971.80 0.00 10763470.88 0.00 0.00 0.370128E+10 0.00 1.35
October 0.120691E+10 0.00 0.00 6557448.66 0.00 2327110.76 0.346598E+10 0.00 0.82
November 0.178291E+10 0.00 0.00 1600553.19 0.00 0.260217E+09 0.702068E+09 0.00 0.38
December 0.148295E+10 0.00 0.00 1437564.61 0.00 0.792733E+09 0.737006E+09 0.00 0.34
                   
Annual Sum or Average 0.124468E+11 0.258602E+09 0.00 71900512.68 2627389.98 0.252779E+10 0.288529E+11 0.00 0.80
Minimum of Months 0.273593E+09 0.00 0.00 593359.93 0.00 0.00 0.364355E+09 0.00 0.31
Maximum of Months 0.178291E+10 0.182973E+09 0.00 10763470.88 1598077.16 0.102209E+10 0.392700E+10 0.00 1.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.762895E+09 0.00 0.00 0.00 0.00 0.941813E+09 0.00 0.00 0.30
February 0.102421E+10 0.00 0.00 220886.08 0.00 0.364884E+09 0.155363E+09 0.00 0.32
March 0.129856E+10 0.00 0.00 1127777.77 0.00 48098357.40 0.650052E+09 0.00 0.42
April 0.777521E+09 3707487.09 0.00 2867104.28 100924.30 4843889.15 0.141408E+10 0.00 0.62
May 0.437410E+09 1586103.85 0.00 6572588.31 0.00 0.00 0.243770E+10 0.00 1.06
June 0.255013E+09 3904834.07 0.00 6652162.29 165212.99 0.00 0.236109E+10 0.00 1.24
July 0.179304E+09 54173191.06 0.00 6933817.77 310211.84 0.00 0.194569E+10 0.00 1.41
August 0.168390E+09 0.123935E+09 0.00 5842192.31 1220686.19 0.00 0.136229E+10 0.00 1.11
September 0.403416E+09 2159565.56 0.00 5099906.05 0.00 0.00 0.172781E+10 0.00 1.06
October 0.998380E+09 0.00 0.00 1521863.00 0.00 3207497.67 0.878939E+09 0.00 0.51
November 0.118861E+10 0.00 0.00 114865.31 0.00 0.270375E+09 65604560.94 0.00 0.32
December 0.916022E+09 0.00 0.00 19718.98 0.00 0.708850E+09 22665352.52 0.00 0.29
                   
Annual Sum or Average 0.840974E+10 0.189466E+09 0.00 36972882.17 1797035.30 0.234207E+10 0.130213E+11 0.00 0.72
Minimum of Months 0.168390E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.129856E+10 0.123935E+09 0.00 6933817.77 1220686.19 0.941813E+09 0.243770E+10 0.00 1.41



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:02

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.644905E+11 0.929941E+10 0.00 0.141711E+12 0.215610E+11
February 0.126341E+12 0.839670E+10 0.00 0.153724E+12 0.139236E+11
March 0.220771E+12 0.851911E+10 0.00 0.196182E+12 0.727406E+10
April 0.339673E+12 0.744259E+10 0.00 0.217698E+12 0.188051E+11
May 0.442037E+12 0.611550E+10 0.00 0.235865E+12 0.284517E+11
June 0.443640E+12 0.481181E+10 0.00 0.219863E+12 0.507952E+11
July 0.469731E+12 0.345747E+10 0.00 0.216517E+12 0.964303E+11
August 0.369953E+12 0.264751E+10 0.00 0.169482E+12 0.128331E+12
September 0.264927E+12 0.346261E+10 0.00 0.225939E+12 0.471982E+11
October 0.170540E+12 0.676682E+10 0.00 0.223453E+12 0.879164E+10
November 0.728724E+11 0.800378E+10 0.00 0.182054E+12 0.115335E+11
December 0.504951E+11 0.850785E+10 0.00 0.158062E+12 0.183480E+11
           
Annual Sum or Average 0.303547E+13 0.774311E+11 0.00 0.234055E+13 0.451443E+12
Minimum of Months 0.504951E+11 0.264751E+10 0.00 0.141711E+12 0.727406E+10
Maximum of Months 0.469731E+12 0.929941E+10 0.00 0.235865E+12 0.128331E+12