Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2024-07-03 12:20:06
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1779.34 | 357.14 | 357.14 |
Net Site Energy | 1779.34 | 357.14 | 357.14 |
Total Source Energy | 5635.15 | 1131.06 | 1131.06 |
Net Source Energy | 5635.15 | 1131.06 | 1131.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 613.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1779.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 613.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 1.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 613.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 96.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 39.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 357.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 357.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1779.335 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1779.335 | 100.00 |
Total On-Site and Utility Electric Sources | 1779.335 | 100.00 |
Total Electricity End Uses | 1779.335 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 17.67 |
Time Setpoint Not Met During Occupied Cooling | 577.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1461.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-15:30 | - | - | - | - | - | - | - | - | - | - | - | 20-MAR-11:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73097.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 14408.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2887.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 153152.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73097.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 14408.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2887.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 3.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1943.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 733.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 304.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 124.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5635.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 390.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1131.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 390.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1131.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.48 | 0.302149 | 0.257000 | 0.637467 | 0.805731 | 0.500000 | 0.001261 |
CORE_MID VAV BOX COMPONENT | 1.98 | 0.377576 | 0.321000 | 0.637157 | 1.00 | 0.500000 | 0.001009 |
CORE_TOP VAV BOX COMPONENT | 2.18 | 0.344494 | 0.293000 | 0.637429 | 0.918650 | 0.500000 | 0.001106 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.681500 | 0.231829 | 0.197000 | 0.134255 | 0.618212 | 0.500000 | 0.001643 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.651023 | 0.153638 | 0.131000 | 0.085284 | 0.409701 | 0.500000 | 0.002480 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.697487 | 0.226515 | 0.193000 | 0.134615 | 0.604041 | 0.500000 | 0.001682 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.739382 | 0.135269 | 0.115000 | 0.085029 | 0.360716 | 0.500000 | 0.002817 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.571975 | 0.276221 | 0.235000 | 0.134414 | 0.736589 | 0.500000 | 0.001379 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.578449 | 0.172914 | 0.147000 | 0.085032 | 0.461103 | 0.500000 | 0.002203 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.580211 | 0.272300 | 0.231000 | 0.134029 | 0.726134 | 0.500000 | 0.001399 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.611557 | 0.163542 | 0.139000 | 0.085006 | 0.436112 | 0.500000 | 0.002330 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.586869 | 0.269211 | 0.229000 | 0.134393 | 0.717897 | 0.500000 | 0.001415 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.622596 | 0.428408 | 0.500000 | 0.002372 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.596463 | 0.264881 | 0.225000 | 0.134204 | 0.706349 | 0.500000 | 0.001438 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.664415 | 0.150531 | 0.128000 | 0.085045 | 0.401417 | 0.500000 | 0.002531 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21265.48 |
CORE_MID VAV BOX REHEAT COIL | 21255.13 |
CORE_TOP VAV BOX REHEAT COIL | 23928.38 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 9481.84 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 6230.37 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 9473.66 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 6229.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5948.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3942.40 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5927.74 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3956.18 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 7408.26 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4886.95 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 7384.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4896.69 |
PACU_VAV_BOT HEATING COIL | 1218.09 |
PACU_VAV_MID HEATING COIL | 2508.16 |
PACU_VAV_TOP HEATING COIL | 260.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.41 | 1.08 | 4.82 | 1.08 | 4.37 | 4.37 | 0.300000 | 0.246167 | 4.37 |
PACU_VAV_MID | 2.23 | 1.08 | 4.46 | 1.16 | 3.94 | 3.94 | 0.300000 | 0.295005 | 3.94 |
PACU_VAV_TOP | 2.47 | 1.08 | 4.94 | 1.73 | 4.69 | 4.69 | 0.300000 | 0.368403 | 4.69 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.37 |
PACU_VAV_MID_OA_CONTROLLER | 3.94 |
PACU_VAV_TOP_OA_CONTROLLER | 4.69 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.37 | 103308.58 | 0.716488 | 1.46 | 34432.75 | 0.716488 |
PACU_VAV_MID COOLING COIL | 3.94 | 95736.76 | 0.708269 | 1.31 | 31909.06 | 0.708269 |
PACU_VAV_TOP COOLING COIL | 4.69 | 108623.46 | 0.723940 | 1.56 | 36204.20 | 0.723940 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.37 |
PACU_VAV_MID FAN | 3.94 |
PACU_VAV_TOP FAN | 4.69 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7231E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7585E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0057E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0349E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6709E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6931E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6735E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6886E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0730E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4018E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7798E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5357E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5950E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5094E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.9381E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0999E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7245E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7675E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0074E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0448E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.6726E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7010E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6734E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6884E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4362E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4907E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1673E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2825E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2407E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0880E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4526E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6264E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0366E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0501E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8275E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8374E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6423E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6460E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1204E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1256E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5909E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6240E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2027E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2292E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9224E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9411E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6734E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6884E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3609E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3229E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8459E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0219E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6627E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.0526E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9381E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0999E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5903E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6232E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2019E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2272E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9209E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9356E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6735E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6886E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5502E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0951E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1132E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8118E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3465E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6908E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4526E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6265E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4567E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4825E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1308E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1561E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0840E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0985E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1205E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1258E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5038E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3095E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.1677E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4878E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.1304E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.2730E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3524E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.5637E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2987E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4106E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0463E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2115E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1451E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0301E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3883E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5876E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7206E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7599E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1697E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4036E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9815E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0538E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3524E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5637E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4387E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0331E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0233E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7627E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2762E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6505E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3883E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5876E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5033E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.3091E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.1672E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4873E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.1298E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.2726E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.3521E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.5635E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2986E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4104E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0462E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2113E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1448E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0299E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3880E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5874E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7207E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7598E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1698E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4035E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9814E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0537E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3521E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5635E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4386E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0329E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0233E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7626E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2759E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6503E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3880E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5875E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34398.29743 | 34398.29743 | 2.48042 | 2.48042 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2208.21779 | 2208.21779 | 9.39248E-002 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27554.52377 | 27554.52377 | 1.98491 | 1.98491 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 8752.25218 | 8752.25218 | 0.36883 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29907.35832 | 29907.35832 | 2.17553 | 2.17553 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 16911.86061 | 16911.86061 | 0.71729 | 0.71729 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9368.23720 | 9368.23720 | 0.68150 | 0.68150 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 7249.55571 | 7249.55571 | 0.28423 | 0.28423 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8949.32432 | 8949.32432 | 0.65102 | 0.65102 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 4763.81314 | 4763.81314 | 0.18677 | 0.18677 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9588.01079 | 9588.01079 | 0.69749 | 0.69749 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 7243.39425 | 7243.39425 | 0.28399 | 0.28399 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10163.98439 | 10163.98439 | 0.73938 | 0.73938 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 4762.73213 | 4762.73213 | 0.18673 | 0.18673 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7862.86382 | 7862.86382 | 0.57198 | 0.57198 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 4197.90080 | 4197.90080 | 0.17832 | 0.17832 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7951.89889 | 7951.89889 | 0.57845 | 0.57845 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 2780.94079 | 2780.94079 | 0.11818 | 0.11818 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 7976.08310 | 7976.08310 | 0.58021 | 0.58021 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 4183.22101 | 4183.22101 | 0.17769 | 0.17769 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8407.04025 | 8407.04025 | 0.61156 | 0.61156 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.03867 | 1.71650E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 2790.56974 | 2790.56974 | 0.11859 | 0.11859 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8067.44724 | 8067.44724 | 0.58687 | 0.58687 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5219.41474 | 5219.41474 | 0.22207 | 0.22207 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8558.62771 | 8558.62771 | 0.62260 | 0.62260 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3442.20209 | 3442.20209 | 0.14649 | 0.14649 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8199.34133 | 8199.34133 | 0.59646 | 0.59646 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5202.64321 | 5202.64321 | 0.22136 | 0.22136 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9133.50683 | 9133.50683 | 0.66441 | 0.66441 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3449.01449 | 3449.01449 | 0.14679 | 0.14679 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 69328.85 | 4.37081 | 4.37081 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 4735.80 | 1.01748 | 1.01748 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63287.57 | 3.93689 | 3.93689 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 4736.25 | 1.16140 | 1.16140 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73670.30 | 4.69298 | 4.69298 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 4715.18 | 1.72891 | 1.72891 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48042 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30215 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63747 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80573 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26097E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21265.47645 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98491 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37758 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63716 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00907E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21255.13223 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17553 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34449 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63743 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91865 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10597E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23928.38141 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68150 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23183 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13426 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61821 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64345E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9481.84011 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65102 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15364 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13100 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52840E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40970 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47986E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6230.37372 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69749 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22652 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19300 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13462 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60404 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68200E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9473.65741 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73938 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13527 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50290E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36072 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81662E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6229.22485 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57198 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27622 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13441 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73659 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37933E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5948.74047 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57845 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17291 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50320E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46110 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20341E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3942.40248 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58021 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27230 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13403 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72613 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39919E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5927.74252 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61156 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16354 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13900 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50064E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43611 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32968E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3956.17565 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58687 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26921 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13439 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71790 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41525E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7408.25925 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62260 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42841 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37157E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4886.95102 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59646 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26488 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70635 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.43838E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7384.29497 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66441 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15053 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50451E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40142 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53104E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4896.68715 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.41130 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07595 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.82261 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07595 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.37081 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.37081 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.24617 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.22763 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07609 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.45525 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.16140 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.93689 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.93689 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.29500 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.47246 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07661 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.94492 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.72891 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.69298 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.69298 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.36840 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.37081 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.93689 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.69298 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.37081 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.37081 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 103308.58039 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71649 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.45679 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34432.74984 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71649 |
152 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 1218.08575 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.37081 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.93689 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.93689 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95736.76252 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70827 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.31217 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31909.06295 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70827 |
161 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 2508.15766 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.93689 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.69298 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.69298 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108623.45616 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72394 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56417 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36204.19794 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72394 |
170 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 260.24915 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.69298 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 102977.01 | 351372.16 | 12.42 | 3.19 | 3.56 | 3.75 | 3.90 | 10.87 | 12.14 | 12.80 | 13.31 | 5.0493 | 4.0130 | 2.6991 | 1.1440 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95517.32 | 325918.62 | 12.48 | 3.20 | 3.58 | 3.77 | 3.91 | 10.91 | 12.21 | 12.87 | 13.35 | 4.5481 | 3.6114 | 2.4300 | 1.0374 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 108199.59 | 369192.31 | 12.37 | 3.18 | 3.54 | 3.74 | 3.89 | 10.84 | 12.10 | 12.75 | 13.28 | 5.4215 | 4.3108 | 2.8990 | 1.2193 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.3285264669 | 0.2833184990 | Pass | Pass | 0.2832609962 | 0.4489670290 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.5201700396E-002 | 8.4657972724E-002 | Pass | Pass | 0.2464069763 | 0.5135193853 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6477318239E-002 | 4.2469988306E-002 | Pass | Pass | 0.2238790454 | 0.4141486958 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0184112746E-002 | 4.1486112013E-002 | Pass | Pass | 0.3108059019 | 0.4834512776 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1572311367 | 0.2235563514 | Pass | Pass | 0.2103071399 | 0.4062230452 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1353830369 | 0.1993869318 | Pass | Pass | 0.2023005770 | 0.3998393562 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1361417308 | 0.1973195723 | Pass | Pass | 0.2018573448 | 0.3990231100 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2133630226 | 0.3139571232 | Pass | Pass | 0.2151811693 | 0.4162622973 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2605311653 | 0.4399491795 | Pass | Pass | 0.2511501271 | 0.4826018812 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1576010896 | 0.2373461157 | Pass | Pass | 0.2033734996 | 0.3977060060 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2580447724 | 0.2340989031 | Pass | Pass | 0.2806186068 | 0.4474208787 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3272742400 | 0.3145805834 | Pass | Pass | 0.2901918850 | 0.4525372313 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3747517116 | 0.4052774048 | Pass | Pass | 0.3183845703 | 0.4999401744 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2665284818 | 0.2429496801 | Pass | Pass | 0.2803050253 | 0.4471252100 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1505423168 | 0.2125052341 | Pass | Pass | 0.2095055645 | 0.4049907989 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2253230209 | 0.3307827690 | Pass | Pass | 0.2469437221 | 0.4736064095 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2615906059 | 0.4161259606 | Pass | Pass | 0.2461396893 | 0.4628284865 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1642307698 | 0.2342248431 | Pass | Pass | 0.2096244687 | 0.4044097455 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2943.83 | -71.3 | 0.00 | -1094.7 | 3318.09 | 5095.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.229 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.229 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.229 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.230 | 0.253 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 4.21 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.41 | 0.0000 | Y | 6.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 4.20 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.66 | 0.0000 | Y | 6.65 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 4.20 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.53 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.72 | 0.0000 | Y | 6.67 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.62 | 0.0000 | Y | 4.21 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.41 | 0.0000 | Y | 6.59 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 4.20 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.76 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.82 | 41.82 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.82 | 62.82 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.82 | 46.78 | 41.40 | |
Exterior Lighting Total | 5686.19 | 50.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 103308.58 | 74019.39 | 29289.19 | 0.72 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95736.76 | 67807.37 | 27929.40 | 0.71 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108623.46 | 78636.89 | 29986.57 | 0.72 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 102977.0 | 3.19 | 10.87 | N/A | N/A | 12.42 | |
PACU_VAV_MID COOLING COIL | 95517.3 | 3.20 | 10.91 | N/A | N/A | 12.48 | |
PACU_VAV_TOP COOLING COIL | 108199.6 | 3.18 | 10.84 | N/A | N/A | 12.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21265.48 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21255.13 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 23928.38 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9481.84 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6230.37 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9473.66 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6229.22 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5948.74 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3942.40 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5927.74 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3956.18 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7408.26 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4886.95 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7384.29 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4896.69 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 1218.09 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 2508.16 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 260.25 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.37 | 9567.75 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.94 | 8617.90 | 2189.01 | 1.00 | 1.15 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.69 | 10272.98 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 102977.01 | 3.19 | 10.87 | 12.42 | 5.0493 | 3.56 | 12.14 | 4.0130 | 3.75 | 12.80 | 2.6991 | 3.90 | 13.31 | 1.1440 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95517.32 | 3.20 | 10.91 | 12.48 | 4.5481 | 3.58 | 12.21 | 3.6114 | 3.77 | 12.87 | 2.4300 | 3.91 | 13.35 | 1.0374 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 108199.59 | 3.18 | 10.84 | 12.37 | 5.4215 | 3.54 | 12.10 | 4.3108 | 3.74 | 12.75 | 2.8990 | 3.89 | 13.28 | 1.2193 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34398.30 | 34398.30 | 34.97 | 2.480 | 2.480 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_MID | 27554.52 | 27554.52 | 28.02 | 1.985 | 1.985 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_TOP | 29907.36 | 29907.36 | 30.41 | 2.176 | 2.176 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00890 | 33.13 | 0.01717 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9368.24 | 9368.24 | 45.18 | 0.681 | 0.681 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00894 | 32.26 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8949.32 | 8949.32 | 68.18 | 0.651 | 0.651 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00880 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9588.01 | 9588.01 | 46.24 | 0.697 | 0.697 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00893 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10163.98 | 10163.98 | 77.44 | 0.739 | 0.739 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00877 | 32.26 | 0.01717 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7862.86 | 7862.86 | 37.92 | 0.572 | 0.572 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00893 | 31.93 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7951.90 | 7951.90 | 60.58 | 0.578 | 0.578 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00878 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7976.08 | 7976.08 | 38.47 | 0.580 | 0.580 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00893 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8407.04 | 8407.04 | 64.05 | 0.612 | 0.612 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00876 | 32.04 | 0.01717 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8067.45 | 8067.45 | 38.91 | 0.587 | 0.587 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00898 | 31.82 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8558.63 | 8558.63 | 65.20 | 0.623 | 0.623 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00879 | 30.46 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8199.34 | 8199.34 | 39.55 | 0.596 | 0.596 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00897 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9133.51 | 9133.51 | 69.59 | 0.664 | 0.664 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00878 | 32.26 | 0.01717 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2208.22 | 2208.22 | 2.25 | 0.094 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_MID | 8752.25 | 8752.25 | 8.90 | 0.369 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_TOP | 16911.86 | 16911.86 | 17.19 | 0.717 | 0.717 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7249.56 | 7249.56 | 34.96 | 0.284 | 0.284 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 4763.81 | 4763.81 | 36.29 | 0.187 | 0.187 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 7243.39 | 7243.39 | 34.94 | 0.284 | 0.284 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 4762.73 | 4762.73 | 36.29 | 0.187 | 0.187 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 21.00 | 20.70 | 0.00781 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 4197.90 | 4197.90 | 20.25 | 0.178 | 0.178 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 2780.94 | 2780.94 | 21.19 | 0.118 | 0.118 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 4183.22 | 4183.22 | 20.18 | 0.178 | 0.178 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 2790.57 | 2790.57 | 21.26 | 0.119 | 0.119 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5219.41 | 5219.41 | 25.17 | 0.222 | 0.222 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3442.20 | 3442.20 | 26.22 | 0.146 | 0.146 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5202.64 | 5202.64 | 25.09 | 0.221 | 0.221 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3449.01 | 3449.01 | 26.28 | 0.147 | 0.147 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.37 | 4.37 | 1.02 | 1.02 | 4.3708 | 1.0759 | 4.3708 | 0.2462 | 0.3000 |
PACU_VAV_MID | 3.94 | 3.94 | 1.16 | 1.16 | 3.9369 | 1.1614 | 3.9369 | 0.2950 | 0.3000 |
PACU_VAV_TOP | 4.69 | 4.69 | 1.73 | 1.73 | 4.6930 | 1.7289 | 4.6930 | 0.3684 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21265.476 | 21265.476 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21265.48 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00799610 | 51.6312 | 2208.22 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21255.132 | 21255.132 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21255.13 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 8752.25 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 23928.381 | 23928.381 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23928.38 | 23928.38 | 0.717292 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 16911.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 9481.840 | 9481.840 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 9481.84 | 9481.84 | 0.284233 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00780722 | 51.3758 | 7249.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 6230.374 | 6230.374 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6230.37 | 6230.37 | 0.186765 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00780800 | 51.3815 | 4763.81 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 9473.657 | 9473.657 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 9473.66 | 9473.66 | 0.283988 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00780700 | 51.3743 | 7243.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 6229.225 | 6229.225 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 6229.22 | 6229.22 | 0.186731 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 20.70 | 0.00780803 | 51.3817 | 4762.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5948.740 | 5948.740 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5948.74 | 5948.74 | 0.178323 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788187 | 50.9036 | 4197.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3942.402 | 3942.402 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3942.40 | 3942.40 | 0.118180 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788358 | 50.9146 | 2780.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5927.743 | 5927.743 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5927.74 | 5927.74 | 0.177694 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788135 | 50.9003 | 4183.22 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3956.176 | 3956.176 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3956.18 | 3956.18 | 0.118593 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788409 | 50.9178 | 2790.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 7408.259 | 7408.259 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7408.26 | 7408.26 | 0.222074 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00787970 | 50.8900 | 5219.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4886.951 | 4886.951 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4886.95 | 4886.95 | 0.146494 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788216 | 50.9057 | 3442.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 7384.295 | 7384.295 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7384.29 | 7384.29 | 0.221356 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00787917 | 50.8866 | 5202.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4896.687 | 4896.687 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4896.69 | 4896.69 | 0.146786 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788247 | 50.9077 | 3449.01 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 103308.580 | 74019.392 | 4.370811 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 106262.10 | 76856.72 | 4.370811 | 25.99 | 18.86 | 0.01070762 | 11.02 | 11.02 | 0.00850000 | 33.07 | 0.01716695 | 25.29 | 21.8747 | 24.00 | 0.00888701 | 47.7575 | 59775.58 | 0.00 | 106525.01 | 75218.48 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 1218.086 | 1218.086 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1218.09 | 1218.09 | 1.311243 | 12.03 | 10.48 | 0.00725626 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 72.9155 | 21.00 | 0.00794737 | 51.3208 | 14128.15 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95736.763 | 67807.366 | 3.936893 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 99244.07 | 69808.13 | 3.936893 | 26.14 | 19.10 | 0.01095805 | 11.02 | 11.02 | 0.00850000 | 32.80 | 0.01716644 | 25.22 | 24.2857 | 24.00 | 0.00895859 | 48.1371 | 53953.79 | 0.00 | 98717.45 | 68937.09 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 2508.158 | 2508.158 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2508.16 | 2508.16 | 1.181068 | 11.04 | 9.96 | 0.00717776 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 80.9522 | 21.00 | 0.00795556 | 51.3730 | 18240.02 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108623.456 | 78636.889 | 4.692980 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 111452.95 | 81586.12 | 4.692980 | 25.81 | 18.70 | 0.01058546 | 11.02 | 11.02 | 0.00850000 | 32.87 | 0.01716657 | 25.24 | 20.3730 | 24.00 | 0.00889860 | 47.8193 | 64420.93 | 0.00 | 112005.36 | 79892.55 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 260.249 | 260.249 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 260.25 | 260.25 | 1.407894 | 12.65 | 10.80 | 0.00730363 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 67.9099 | 20.39 | 0.00795693 | 53.3350 | 20063.04 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21265.476 | 21265.476 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21265.48 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21265.48 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00799610 | 21.00 | 0.00799610 | 51.6312 | 2208.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21255.132 | 21255.132 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21255.13 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21255.13 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.89 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 8752.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 23928.381 | 23928.381 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23928.38 | 23928.38 | 1.0000 | 0.86271442 | 0.717292 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23928.38 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 16911.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9481.840 | 9481.840 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 9481.84 | 9481.84 | 1.0000 | 0.34185849 | 0.284233 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9481.84 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.51 | 0.00780722 | 20.70 | 0.00780722 | 51.3758 | 7249.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6230.374 | 6230.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6230.37 | 6230.37 | 1.0000 | 0.22463004 | 0.186765 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6230.37 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.51 | 0.00780800 | 20.70 | 0.00780800 | 51.3815 | 4763.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9473.657 | 9473.657 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 9473.66 | 9473.66 | 1.0000 | 0.34156347 | 0.283988 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9473.66 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.51 | 0.00780700 | 20.70 | 0.00780700 | 51.3743 | 7243.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6229.225 | 6229.225 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | Sensible | 6229.22 | 6229.22 | 1.0000 | 0.22458862 | 0.186731 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6229.22 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 19.51 | 0.00780803 | 20.70 | 0.00780803 | 51.3817 | 4762.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5948.740 | 5948.740 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5948.74 | 5948.74 | 1.0000 | 0.21447603 | 0.178323 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5948.74 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00788187 | 21.00 | 0.00788187 | 50.9036 | 4197.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3942.402 | 3942.402 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3942.40 | 3942.40 | 1.0000 | 0.14213947 | 0.118180 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3942.40 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00788358 | 21.00 | 0.00788358 | 50.9146 | 2780.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5927.743 | 5927.743 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5927.74 | 5927.74 | 1.0000 | 0.21371897 | 0.177694 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5927.74 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00788135 | 21.00 | 0.00788135 | 50.9003 | 4183.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 3956.176 | 3956.176 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3956.18 | 3956.18 | 1.0000 | 0.14263605 | 0.118593 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3956.18 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00788409 | 21.00 | 0.00788409 | 50.9178 | 2790.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7408.259 | 7408.259 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7408.26 | 7408.26 | 1.0000 | 0.26709755 | 0.222074 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7408.26 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00787970 | 21.00 | 0.00787970 | 50.8900 | 5219.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4886.951 | 4886.951 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4886.95 | 4886.95 | 1.0000 | 0.17619425 | 0.146494 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4886.95 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788216 | 21.00 | 0.00788216 | 50.9057 | 3442.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7384.295 | 7384.295 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7384.29 | 7384.29 | 1.0000 | 0.26623354 | 0.221356 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7384.29 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00787917 | 21.00 | 0.00787917 | 50.8866 | 5202.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4896.687 | 4896.687 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4896.69 | 4896.69 | 1.0000 | 0.17654527 | 0.146786 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4896.69 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00788247 | 21.00 | 0.00788247 | 50.9077 | 3449.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 103308.580 | 74019.392 | 4.370811 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7449 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.370811 | 5.25694423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 106262.10 | 76856.72 | 1.0286 | 5.25694423 | 4.370811 | 25.99 | 18.86 | 0.01070762 | 53414.6 | 11.02 | 11.02 | 0.00850000 | 32509.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9567.753 | 96694.35 | 33.07 | 0.01716695 | 25.29 | 0.95610000 | 21.8747 | 24.00 | 0.00888701 | 24.00 | 0.00888701 | 47.7575 | 59775.58 | 0.00 | 106525.01 | 75218.48 | 5.04933467 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.08 | 12.06 | 0.00875373 | 34225.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1218.086 | 1218.086 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.370811 | 5.25694423 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1218.09 | 1218.09 | 1.0000 | 1.57708327 | 1.311243 | 12.03 | 10.48 | 0.00725626 | 30399.4 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1218.09 | 8.70 | 0.00699286 | 8.70 | 0.95610000 | 72.9155 | 21.00 | 0.00796537 | 21.00 | 0.00794737 | 51.3208 | 14128.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95736.763 | 67807.366 | 3.936893 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.2105 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.936893 | 4.73505412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 99244.07 | 69808.13 | 1.0366 | 4.73505412 | 3.936893 | 26.14 | 19.10 | 0.01095805 | 54206.6 | 11.02 | 11.02 | 0.00850000 | 32510.3 | -999.0 | -999.00 | -999.00 | -999.00 | 8617.901 | 90626.17 | 32.80 | 0.01716644 | 25.22 | 0.95610000 | 24.2857 | 24.00 | 0.00895859 | 24.00 | 0.00895859 | 48.1371 | 53953.79 | 0.00 | 98717.45 | 68937.09 | 4.54805528 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.82 | 11.81 | 0.00861736 | 33617.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 2508.158 | 2508.158 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.936893 | 4.73505412 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2508.16 | 2508.16 | 1.0000 | 1.42051624 | 1.181068 | 11.04 | 9.96 | 0.00717776 | 29194.8 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2508.16 | 8.70 | 0.00699286 | 8.70 | 0.95610000 | 80.9522 | 21.00 | 0.00796361 | 21.00 | 0.00795556 | 51.3730 | 18240.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108623.456 | 78636.889 | 4.692980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5178 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.692980 | 5.64442973 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 111452.95 | 81586.12 | 1.0260 | 5.64442973 | 4.692980 | 25.81 | 18.70 | 0.01058546 | 52913.8 | 11.02 | 11.02 | 0.00850000 | 32509.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10272.985 | 101179.97 | 32.87 | 0.01716657 | 25.24 | 0.95610000 | 20.3730 | 24.00 | 0.00889860 | 24.00 | 0.00889860 | 47.8193 | 64420.93 | 0.00 | 112005.36 | 79892.55 | 5.42151743 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.24 | 12.23 | 0.00886230 | 34663.0 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 260.249 | 260.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.692980 | 5.64442973 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 260.25 | 260.25 | 1.0000 | 1.69332892 | 1.407894 | 12.65 | 10.80 | 0.00730363 | 31145.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 260.25 | 8.70 | 0.00699286 | 8.70 | 0.95610000 | 67.9099 | 21.00 | 0.00796131 | 20.39 | 0.00795693 | 53.3350 | 20063.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5420.67 | 22.83 | 0.00 |
CORE_MID | 4533.83 | 425.67 | 0.00 |
CORE_TOP | 4258.00 | 803.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 4397.00 | 1354.67 | 343.83 |
PERIMETER_TOP_ZN_2 | 4744.00 | 1166.67 | 496.67 |
PERIMETER_TOP_ZN_1 | 4837.83 | 1079.83 | 484.33 |
PERIMETER_TOP_ZN_4 | 4676.83 | 1277.50 | 485.33 |
PERIMETER_BOT_ZN_3 | 4716.17 | 772.83 | 93.67 |
PERIMETER_BOT_ZN_2 | 5122.83 | 650.00 | 315.67 |
PERIMETER_BOT_ZN_1 | 5296.17 | 1369.50 | 1056.67 |
PERIMETER_BOT_ZN_4 | 5106.00 | 659.00 | 254.67 |
PERIMETER_MID_ZN_3 | 4610.17 | 988.50 | 211.17 |
PERIMETER_MID_ZN_2 | 4122.50 | 909.17 | 432.17 |
PERIMETER_MID_ZN_1 | 5060.00 | 775.33 | 377.67 |
PERIMETER_MID_ZN_4 | 4889.83 | 951.33 | 377.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5588.83 | 2463.67 | 1461.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 22.83 | 0.00 | 20.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 65.67 | 0.00 | 61.67 |
PERIMETER_TOP_ZN_1 | 0.00 | 86.83 | 0.00 | 83.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 64.17 | 0.00 | 47.17 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 46.17 | 0.00 | 45.83 |
PERIMETER_BOT_ZN_1 | 17.67 | 445.67 | 17.67 | 444.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 41.50 | 0.00 | 31.00 |
PERIMETER_MID_ZN_3 | 0.00 | 3.17 | 0.00 | 2.67 |
PERIMETER_MID_ZN_2 | 0.00 | 56.00 | 0.00 | 55.67 |
PERIMETER_MID_ZN_1 | 0.00 | 132.50 | 0.00 | 131.67 |
PERIMETER_MID_ZN_4 | 0.00 | 46.33 | 0.00 | 34.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 17.67 | 604.33 | 17.67 | 577.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.07 | 52.94 | 2698.04 | 0.519 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.07 | 52.94 | 2698.04 | 0.448 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.07 | 52.94 | 2698.04 | 0.446 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.65 | 11.16 | 568.77 | 0.561 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.730 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.65 | 11.16 | 568.77 | 0.721 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.708 | 0.041 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.65 | 11.16 | 568.77 | 0.466 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.619 | 0.022 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.65 | 11.16 | 568.77 | 0.646 | 1.253 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.600 | 0.022 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.65 | 11.16 | 568.77 | 0.562 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.689 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.65 | 11.16 | 568.77 | 0.720 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.716 | 0.034 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.07 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.07 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.07 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.95 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.59 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.65 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.07 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.07 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.07 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.95 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.59 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.65 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.43 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8559447.78 | 0.00 | 8559447.78 | 0.00 | 8559447.78 | 13393058.27 | 5824.34 | 549.93 | 2385.74 | 257.75 |
CORE_MID | 7287127.45 | 0.00 | 7287127.45 | 0.00 | 7287127.45 | 13393058.27 | 7186.95 | 730.00 | 843.05 | 166.92 |
CORE_TOP | 7274401.79 | 0.00 | 7274401.79 | 0.00 | 7274401.79 | 13393058.27 | 7215.05 | 744.14 | 800.81 | 176.03 |
PERIMETER_TOP_ZN_3 | 1913092.04 | 0.00 | 1913092.04 | 242475.02 | 2155567.07 | 2823374.22 | 4440.30 | 835.26 | 3484.43 | 176.03 |
PERIMETER_TOP_ZN_2 | 1564323.37 | 0.00 | 1564323.37 | 161649.04 | 1725972.41 | 1787429.43 | 3789.10 | 316.25 | 4654.64 | 176.03 |
PERIMETER_TOP_ZN_1 | 2442275.55 | 0.00 | 2442275.55 | 242475.02 | 2684750.57 | 2823374.22 | 3742.76 | 390.71 | 4626.53 | 176.03 |
PERIMETER_TOP_ZN_4 | 1525878.68 | 0.00 | 1525878.68 | 161649.04 | 1687527.73 | 1787312.18 | 4006.00 | 611.04 | 4142.96 | 176.03 |
PERIMETER_BOT_ZN_3 | 1623699.97 | 0.00 | 1623699.97 | 128923.74 | 1752623.71 | 2823374.22 | 6524.82 | 603.34 | 1631.84 | 257.75 |
PERIMETER_BOT_ZN_2 | 1348780.38 | 0.00 | 1348780.38 | 85948.64 | 1434729.02 | 1787429.43 | 4283.50 | 567.19 | 3909.31 | 257.75 |
PERIMETER_BOT_ZN_1 | 2214365.62 | 0.00 | 2214365.62 | 4188758.26 | 6403123.88 | 2823374.22 | 4410.34 | 676.12 | 3673.53 | 257.75 |
PERIMETER_BOT_ZN_4 | 1312376.67 | 0.00 | 1312376.67 | 85948.64 | 1398325.31 | 1787312.18 | 4723.66 | 621.23 | 3415.10 | 257.75 |
PERIMETER_MID_ZN_3 | 1911379.21 | 0.00 | 1911379.21 | 201842.66 | 2113221.87 | 2823374.22 | 4551.83 | 679.58 | 3528.60 | 166.92 |
PERIMETER_MID_ZN_2 | 1495245.81 | 0.00 | 1495245.81 | 134560.97 | 1629806.78 | 1601953.02 | 3795.83 | 291.06 | 4673.11 | 1075.92 |
PERIMETER_MID_ZN_1 | 2435523.38 | 0.00 | 2435523.38 | 201842.66 | 2637366.04 | 2823374.22 | 3788.76 | 638.23 | 4333.01 | 166.92 |
PERIMETER_MID_ZN_4 | 1537427.83 | 0.00 | 1537427.83 | 134560.97 | 1671988.79 | 1787312.18 | 4078.53 | 543.01 | 4138.46 | 166.92 |
Total Facility | 44445345.52 | 0.00 | 44445345.52 | 5970634.68 | 50415980.21 | 67658168.57 | 8292.64 | 1976.67 | 5183.68 | 1236.89 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3811 | 0.0000 | 0.3811 | 0.0000 | 0.3811 | 0.4247 | 3237.66 | 400.39 | 2304.95 |
CORE_MID | 0.3287 | 0.0000 | 0.3287 | 0.0000 | 0.3287 | 0.4247 | 4512.80 | 607.66 | 822.55 |
CORE_TOP | 0.3276 | 0.0000 | 0.3276 | 0.0000 | 0.3276 | 0.4247 | 4543.00 | 619.55 | 780.45 |
PERIMETER_TOP_ZN_3 | 0.0867 | 0.0000 | 0.0867 | 0.0061 | 0.0928 | 0.0895 | 1774.83 | 701.69 | 3466.48 |
PERIMETER_TOP_ZN_2 | 0.0714 | 0.0000 | 0.0714 | 0.0040 | 0.0754 | 0.0567 | 1129.83 | 244.84 | 4568.33 |
PERIMETER_TOP_ZN_1 | 0.1114 | 0.0000 | 0.1114 | 0.0061 | 0.1175 | 0.0895 | 1081.61 | 300.10 | 4561.29 |
PERIMETER_TOP_ZN_4 | 0.0692 | 0.0000 | 0.0692 | 0.0040 | 0.0733 | 0.0567 | 1357.68 | 500.63 | 4084.68 |
PERIMETER_BOT_ZN_3 | 0.0721 | 0.0000 | 0.0721 | 0.0032 | 0.0753 | 0.0895 | 3919.25 | 455.06 | 1568.69 |
PERIMETER_BOT_ZN_2 | 0.0606 | 0.0000 | 0.0606 | 0.0021 | 0.0627 | 0.0567 | 1684.83 | 403.05 | 3855.12 |
PERIMETER_BOT_ZN_1 | 0.0996 | 0.0000 | 0.0996 | 0.1930 | 0.2926 | 0.0895 | 1810.52 | 477.54 | 3654.94 |
PERIMETER_BOT_ZN_4 | 0.0587 | 0.0000 | 0.0587 | 0.0021 | 0.0608 | 0.0567 | 2134.79 | 467.75 | 3340.46 |
PERIMETER_MID_ZN_3 | 0.0868 | 0.0000 | 0.0868 | 0.0050 | 0.0919 | 0.0895 | 1879.64 | 565.91 | 3497.45 |
PERIMETER_MID_ZN_2 | 0.0674 | 0.0000 | 0.0674 | 0.0035 | 0.0710 | 0.0567 | 1127.13 | 229.45 | 3677.42 |
PERIMETER_MID_ZN_1 | 0.1113 | 0.0000 | 0.1113 | 0.0050 | 0.1164 | 0.0895 | 1117.72 | 508.20 | 4317.08 |
PERIMETER_MID_ZN_4 | 0.0700 | 0.0000 | 0.0700 | 0.0034 | 0.0734 | 0.0567 | 1420.49 | 437.12 | 4085.39 |
Total Facility | 2.0029 | 0.0000 | 2.0029 | 0.2377 | 2.2406 | 2.1513 | 5548.49 | 1699.89 | 4992.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21783590.14 | 0.00 | 21783590.14 | 22614548.33 | 3506.74 | 0.86 | 5252.39 | 257.75 |
PACU_VAV_MID | 21216581.58 | 0.00 | 21216581.58 | 22429071.92 | 3590.42 | 0.77 | 5168.80 | 166.92 |
PACU_VAV_TOP | 21293599.82 | 0.00 | 21293599.82 | 22614548.33 | 3584.24 | 0.50 | 5175.26 | 176.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9723 | 0.0000 | 0.9723 | 0.7171 | 942.39 | 0.84 | 4999.78 |
PACU_VAV_MID | 0.9622 | 0.0000 | 0.9622 | 0.7084 | 937.12 | 0.62 | 5005.25 |
PACU_VAV_TOP | 0.9640 | 0.0000 | 0.9640 | 0.7171 | 939.82 | 0.44 | 5002.73 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 502.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4778.16 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 247.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4938.86 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 173.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5021.39 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2982 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1349 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.2345 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1346 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.1950 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1399 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2220 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
Electricity:Building | 951.45 | 13383.13 | 29-MAY-17:20 | 66703.05 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 951.45 | 13383.13 | 29-MAY-17:20 | 66703.05 | 27-SEP-07:10 |
InteriorLights:Electricity | 231.76 | 905.38 | 29-MAY-17:20 | 25003.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.76 | 905.38 | 29-MAY-17:20 | 25003.79 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 231.76 | 905.38 | 29-MAY-17:20 | 25003.79 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.76 | 905.38 | 29-MAY-17:20 | 25003.79 | 27-SEP-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.00 | 413.68 | 02-APR-17:10 | 2475.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.61 | 261.88 | 23-APR-17:10 | 1567.33 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.21 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.21 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.92 | 413.67 | 12-MAR-17:10 | 2475.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.59 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.59 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1567.28 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 658.71 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 658.71 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.99 | 413.68 | 02-APR-17:10 | 2475.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.65 | 27.57 | 01-JAN-09:30 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.65 | 27.57 | 01-JAN-09:30 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.60 | 261.88 | 23-APR-17:10 | 1567.33 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.20 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.20 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2475.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.59 | 261.87 | 12-MAR-17:10 | 1567.28 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:30 | 658.71 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:30 | 658.71 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.00 | 413.68 | 02-APR-17:10 | 2475.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.67 | 27.57 | 01-JAN-09:40 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.61 | 261.88 | 23-APR-17:10 | 1567.33 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.21 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.21 | 17.46 | 01-JAN-07:40 | 658.76 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.92 | 413.67 | 12-MAR-17:10 | 2475.79 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.59 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.59 | 27.57 | 01-JAN-07:40 | 1040.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1567.28 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 658.71 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 658.71 | 27-SEP-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 737.94 | 367.92 | 01-JAN-00:10 | 88915.93 | 28-JUL-15:30 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 25-JAN-08:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 25-JAN-08:10 |
ElectricityPurchased:Facility | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
ElectricityPurchased:Plant | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
Cogeneration:ElectricityPurchased | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
General:Cogeneration:ElectricityPurchased | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
ElectricityNet:Plant | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
Cogeneration:ElectricityNet | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
General:Cogeneration:ElectricityNet | 1779.34 | 13751.79 | 09-JUL-17:20 | 153152.05 | 28-JUL-15:30 |
Heating:Electricity | 1.06 | 0.00 | 01-JAN-00:10 | 29191.70 | 04-FEB-07:10 |
General:Heating:Electricity | 1.06 | 0.00 | 01-JAN-00:10 | 29191.70 | 04-FEB-07:10 |
Fans:Electricity | 96.21 | 0.00 | 01-JAN-00:10 | 15510.76 | 31-JUL-14:30 |
General:Fans:Electricity | 96.21 | 0.00 | 01-JAN-00:10 | 15510.76 | 31-JUL-14:30 |
ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.63 | 0.00 | 01-JAN-07:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 613.78 | 0.00 | 01-JAN-00:10 | 73097.16 | 28-JUL-15:30 |
General:Cooling:Electricity | 613.78 | 0.00 | 01-JAN-00:10 | 73097.16 | 28-JUL-15:30 |
Electricity:Plant | 39.31 | 0.00 | 01-JAN-00:10 | 4626.57 | 19-JAN-12:30 |
WaterSystems:Electricity | 39.17 | 0.00 | 01-JAN-00:10 | 4619.72 | 19-JAN-12:30 |
Water Heater:WaterSystems:Electricity | 39.17 | 0.00 | 01-JAN-00:10 | 4619.72 | 19-JAN-12:30 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 30-JAN-17:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 30-JAN-17:10 |
WIRED_LTG_ELECTRICITY | 6.51 | 0.00 | 01-JAN-00:10 | 702.61 | 27-SEP-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 20-MAR-11:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4378.33 | 0.00 | 01-JAN-00:10 | 447827.33 | 31-JUL-14:10 |
EnergyTransfer:Building | 1636.52 | 0.00 | 01-JAN-00:10 | 163751.83 | 31-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 310.84 | 0.00 | 01-JAN-00:10 | 25393.26 | 05-SEP-07:40 |
Heating:EnergyTransfer | 2.25 | 0.00 | 01-JAN-00:10 | 17785.08 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.25 | 0.00 | 01-JAN-00:10 | 17785.08 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1634.27 | 0.00 | 01-JAN-00:10 | 163751.83 | 31-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 310.84 | 0.00 | 01-JAN-00:10 | 25393.26 | 05-SEP-07:40 |
General:Cooling:EnergyTransfer | 1634.27 | 0.00 | 01-JAN-00:10 | 163751.83 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 310.84 | 0.00 | 01-JAN-00:10 | 25393.26 | 05-SEP-07:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.20 | 0.00 | 01-JAN-00:10 | 11215.14 | 28-JUL-15:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.31 | 0.00 | 01-JAN-00:10 | 3300.80 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.31 | 0.00 | 01-JAN-00:10 | 3300.80 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.89 | 0.00 | 01-JAN-00:10 | 11215.14 | 28-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 63.89 | 0.00 | 01-JAN-00:10 | 11215.14 | 28-JUL-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.99 | 0.00 | 01-JAN-00:10 | 4962.31 | 31-JUL-14:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1414.83 | 05-FEB-12:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1414.83 | 05-FEB-12:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.80 | 0.00 | 01-JAN-00:10 | 4962.31 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 35.80 | 0.00 | 01-JAN-00:10 | 4962.31 | 31-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.98 | 0.00 | 01-JAN-00:10 | 5275.22 | 31-JUL-15:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.28 | 0.00 | 01-JAN-00:10 | 1421.62 | 05-FEB-12:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.28 | 0.00 | 01-JAN-00:10 | 1421.62 | 05-FEB-12:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.71 | 0.00 | 01-JAN-00:10 | 5275.22 | 31-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 43.71 | 0.00 | 01-JAN-00:10 | 5275.22 | 31-JUL-15:20 |
EnergyTransfer:Zone:CORE_MID | 219.93 | 0.00 | 01-JAN-00:10 | 19465.65 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 219.93 | 0.00 | 01-JAN-00:10 | 19465.65 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 219.93 | 0.00 | 01-JAN-00:10 | 19465.65 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 225.86 | 0.00 | 01-JAN-00:10 | 21209.46 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 1351.30 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 1351.30 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 225.86 | 0.00 | 01-JAN-00:10 | 21209.46 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 225.86 | 0.00 | 01-JAN-00:10 | 21209.46 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 62.75 | 0.00 | 01-JAN-00:10 | 7698.27 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3041.91 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3041.91 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 62.70 | 0.00 | 01-JAN-00:10 | 7698.27 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 62.70 | 0.00 | 01-JAN-00:10 | 7698.27 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.38 | 0.00 | 01-JAN-00:10 | 7642.87 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1598.50 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1598.50 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.37 | 0.00 | 01-JAN-00:10 | 7642.87 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.37 | 0.00 | 01-JAN-00:10 | 7642.87 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.07 | 0.00 | 01-JAN-00:10 | 10493.53 | 02-JAN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2663.43 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2663.43 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.05 | 0.00 | 01-JAN-00:10 | 10493.53 | 02-JAN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 81.05 | 0.00 | 01-JAN-00:10 | 10493.53 | 02-JAN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.05 | 0.00 | 01-JAN-00:10 | 8205.99 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1843.91 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1843.91 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.03 | 0.00 | 01-JAN-00:10 | 8205.99 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.03 | 0.00 | 01-JAN-00:10 | 8205.99 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.13 | 0.00 | 01-JAN-00:10 | 6923.90 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.13 | 0.00 | 01-JAN-00:10 | 6923.90 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.13 | 0.00 | 01-JAN-00:10 | 6923.90 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.40 | 0.00 | 01-JAN-00:10 | 6885.15 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.40 | 0.00 | 01-JAN-00:10 | 6885.15 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.40 | 0.00 | 01-JAN-00:10 | 6885.15 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.67 | 0.00 | 01-JAN-00:10 | 10179.60 | 27-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.38 | 0.00 | 01-JAN-00:10 | 4332.84 | 16-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.38 | 0.00 | 01-JAN-00:10 | 4332.84 | 16-MAR-07:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.29 | 0.00 | 01-JAN-00:10 | 10179.60 | 27-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 87.29 | 0.00 | 01-JAN-00:10 | 10179.60 | 27-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.38 | 0.00 | 01-JAN-00:10 | 6806.93 | 01-SEP-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.38 | 0.00 | 01-JAN-00:10 | 6806.93 | 01-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 50.38 | 0.00 | 01-JAN-00:10 | 6806.93 | 01-SEP-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.29 | 0.00 | 01-JAN-00:10 | 6967.81 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1262.79 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1262.79 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.29 | 0.00 | 01-JAN-00:10 | 6967.81 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 60.29 | 0.00 | 01-JAN-00:10 | 6967.81 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.53 | 0.00 | 01-JAN-00:10 | 7411.45 | 25-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 803.03 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 803.03 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.53 | 0.00 | 01-JAN-00:10 | 7411.45 | 25-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 48.53 | 0.00 | 01-JAN-00:10 | 7411.45 | 25-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.07 | 0.00 | 01-JAN-00:10 | 9335.28 | 04-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1062.86 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1062.86 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.07 | 0.00 | 01-JAN-00:10 | 9335.28 | 04-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 78.07 | 0.00 | 01-JAN-00:10 | 9335.28 | 04-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.01 | 0.00 | 01-JAN-00:10 | 7576.90 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 883.66 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 883.66 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.01 | 0.00 | 01-JAN-00:10 | 7576.90 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 49.01 | 0.00 | 01-JAN-00:10 | 7576.90 | 17-MAY-16:00 |
PlantLoopHeatingDemand:Facility | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
PlantLoopHeatingDemand:Plant | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
EnergyTransfer:HVAC | 2705.38 | 0.00 | 01-JAN-00:10 | 282903.57 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 1.06 | 0.00 | 01-JAN-00:10 | 29191.70 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2704.31 | 0.00 | 01-JAN-00:10 | 282903.57 | 21-AUG-16:00 |
EnergyTransfer:Plant | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
WaterSystems:EnergyTransfer | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 36.44 | 0.00 | 01-JAN-00:10 | 4511.68 | 18-JAN-12:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -310.840 | 0.000 | 0.000 | 32.646 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -27.828 |
CORE_MID | 0.000 | 0.000 | 0.000 | -219.927 | 0.000 | 0.000 | 32.769 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 16.134 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.001 | -225.860 | 0.000 | 0.000 | 32.915 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 21.920 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.040 | -62.703 | 0.000 | 0.000 | 6.978 | 6.671 | 24.333 | 25.117 | 0.000 | 0.334 | 9.045 | 0.000 | -9.269 | 0.000 | -0.545 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.015 | -52.367 | 0.000 | 0.000 | 4.380 | 4.207 | 15.404 | 33.391 | 0.000 | 0.211 | 1.145 | 0.000 | -5.997 | 0.000 | -0.389 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.020 | -81.046 | 0.000 | 0.000 | 6.918 | 6.591 | 24.332 | 52.035 | 0.000 | 0.318 | 0.814 | 0.000 | -9.367 | 0.000 | -0.615 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.023 | -51.030 | 0.000 | 0.000 | 4.407 | 4.199 | 15.403 | 32.360 | 0.000 | 0.208 | 1.340 | 0.000 | -6.515 | 0.000 | -0.397 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -61.127 | 0.000 | 0.000 | 6.929 | 6.655 | 24.333 | 25.315 | 0.000 | 0.189 | 8.104 | 0.000 | -10.076 | 0.000 | -0.320 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -52.395 | 0.000 | 0.000 | 4.365 | 4.200 | 15.404 | 33.570 | 0.000 | 0.115 | 1.677 | 0.000 | -6.703 | 0.000 | -0.234 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.376 | -87.288 | 0.000 | 0.000 | 6.853 | 6.581 | 24.332 | 52.225 | 0.000 | 11.272 | 1.659 | 0.000 | -10.504 | 0.000 | -5.508 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -50.375 | 0.000 | 0.000 | 4.372 | 4.191 | 15.403 | 32.534 | 0.000 | 0.113 | 1.279 | 0.000 | -7.277 | 0.000 | -0.239 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.001 | -60.291 | 0.000 | 0.000 | 6.940 | 6.671 | 24.333 | 25.258 | 0.000 | 0.287 | 7.214 | 0.000 | -9.918 | 0.000 | -0.495 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -48.525 | 0.000 | 0.000 | 3.217 | 4.207 | 15.404 | 33.381 | 0.000 | 0.175 | 0.002 | 0.000 | -6.382 | 0.000 | -0.351 | -1.126 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.001 | -78.068 | 0.000 | 0.000 | 6.883 | 6.591 | 24.332 | 52.205 | 0.000 | 0.270 | 0.001 | 0.000 | -9.937 | 0.000 | -0.552 | -1.725 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.001 | -49.008 | 0.000 | 0.000 | 4.385 | 4.199 | 15.403 | 32.488 | 0.000 | 0.176 | 0.000 | 0.000 | -6.936 | 0.000 | -0.357 | -0.351 |
TOPFLOOR_PLENUM | 1.305 | -63.892 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.342 | 63.078 | 0.000 | 0.000 | 0.000 | -0.833 | -0.000 |
MIDFLOOR_PLENUM | 0.191 | -35.800 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.401 | 36.086 | 0.000 | 0.000 | 0.000 | -0.879 | -0.000 |
FIRSTFLOOR_PLENUM | 0.276 | -43.707 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.304 | 43.859 | 0.000 | 0.000 | 0.000 | -0.733 | -0.000 |
Total Facility | 1.773 | -143.398 | 0.480 | -1490.849 | 0.000 | 0.000 | 164.955 | 231.760 | 719.689 | 429.879 | 0.000 | 14.716 | 213.359 | 0.000 | -98.880 | 0.000 | -12.447 | -31.036 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | -42428.39 | 0.00 | 0.00 | 283.10 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 34523.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-OCT-04:04 | 0.00 | 0.00 | 0.00 | -33703.11 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31049.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | -35701.85 | 0.00 | 0.00 | 308.59 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 32155.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUN-15:42 | 0.00 | 0.00 | 0.00 | -11616.54 | 0.00 | 0.00 | 27.15 | 27.57 | 478.42 | 2334.18 | 0.00 | 89.04 | 8660.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:52 | 0.00 | 0.00 | 0.00 | -11457.14 | 0.00 | 0.00 | 14.15 | 17.46 | 302.86 | 5891.24 | 0.00 | 19.87 | 5211.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 20-FEB-14:12 | 0.00 | 0.00 | 0.00 | -13511.93 | 0.00 | 0.00 | 22.84 | 27.57 | 478.41 | 9405.57 | 0.00 | 0.00 | 3639.85 | 0.00 | -0.00 | 0.00 | -62.30 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-APR-16:22 | 0.00 | 0.00 | 0.00 | -13837.10 | 0.00 | 0.00 | 14.26 | 17.46 | 302.86 | 7429.65 | 0.00 | 0.00 | 6103.53 | 0.00 | -0.00 | 0.00 | -30.65 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-AUG-04:02 | 0.00 | 0.00 | 0.00 | -8001.46 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 12.06 | 7569.31 | 0.00 | -139.36 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-09:42 | 0.00 | 0.00 | 0.00 | -10762.24 | 0.00 | 0.00 | 15.35 | 17.46 | 302.86 | 6275.59 | 0.00 | 8.31 | 4142.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -11030.15 | 0.00 | 0.00 | 24.28 | 27.57 | 478.41 | 10332.77 | 0.00 | 25.76 | 141.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-APR-16:22 | 0.00 | 0.00 | 0.00 | -11111.66 | 0.00 | 0.00 | 15.88 | 17.46 | 302.86 | 7576.12 | 0.00 | 0.00 | 3211.17 | 0.00 | -0.00 | 0.00 | -11.82 | 0.00 |
PERIMETER_MID_ZN_3 | 29-MAY-16:32 | 0.00 | 0.00 | 0.00 | -9751.21 | 0.00 | 0.00 | 27.71 | 27.57 | 478.42 | 2563.71 | 0.00 | 162.66 | 6491.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-09:42 | 0.00 | 0.00 | 0.00 | -11783.62 | 0.00 | 0.00 | 14.55 | 17.46 | 302.86 | 6212.03 | 0.00 | 11.10 | 5225.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-12:32 | 0.00 | 0.00 | 0.00 | -11469.08 | 0.00 | 0.00 | 23.44 | 27.57 | 478.41 | 10225.38 | 0.00 | 34.51 | 679.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-16:42 | 0.00 | 0.00 | 0.00 | -11838.19 | 0.00 | 0.00 | 15.75 | 17.46 | 302.86 | 5699.21 | 0.00 | 0.00 | 5815.69 | 0.00 | -0.00 | 0.00 | -12.77 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:30 | 0.00 | -11214.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 11181.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 31-JUL-12:02 | 0.00 | -5046.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 5007.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 11-SEP-06:15 | 0.00 | -5921.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 5919.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUN-04:02 | 0.00 | 7927.30 | 0.00 | -192850.08 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 172368.17 | 0.00 | -4057.97 | 0.00 | -30.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-FEB-07:03 | 0.00 | 0.00 | 5405.25 | 0.00 | 0.00 | 0.00 | 444.03 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9423.63 |
PERIMETER_TOP_ZN_3 | 27-JAN-07:03 | 0.00 | 0.00 | 6541.20 | 0.00 | 0.00 | 0.00 | 191.78 | 346.86 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1574.05 | 0.00 | 0.00 | -6143.67 |
PERIMETER_TOP_ZN_2 | 16-MAR-06:03 | 0.00 | 0.00 | 4315.27 | 0.00 | 0.00 | 0.00 | 122.37 | 219.59 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1568.30 | 0.00 | -59.77 | -3432.96 |
PERIMETER_TOP_ZN_1 | 27-DEC-07:02 | 0.00 | 0.00 | 6562.67 | 0.00 | 0.00 | 0.00 | 189.56 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2080.53 | 0.00 | -81.84 | -5574.59 |
PERIMETER_TOP_ZN_4 | 16-MAR-06:03 | 0.00 | 0.00 | 4233.88 | 0.00 | 0.00 | 0.00 | 122.37 | 219.57 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1613.42 | 0.00 | -59.61 | -3306.60 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-MAR-07:00 | 0.00 | 0.00 | 4335.38 | 0.00 | 0.00 | 0.00 | 214.21 | 244.02 | 637.88 | 0.00 | 0.00 | 0.00 | 10496.28 | 0.00 | -1747.99 | 0.00 | -14179.78 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-FEB-07:03 | 0.00 | 0.00 | 4581.57 | 0.00 | 0.00 | 0.00 | 95.89 | 113.66 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2544.61 | 0.00 | -84.15 | -2800.24 |
PERIMETER_MID_ZN_2 | 04-FEB-07:03 | 0.00 | 0.00 | 3212.10 | 0.00 | 0.00 | 0.00 | 60.72 | 69.39 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -244.78 | 0.00 | -56.47 | -3444.77 |
PERIMETER_MID_ZN_1 | 04-FEB-07:03 | 0.00 | 0.00 | 4251.45 | 0.00 | 0.00 | 0.00 | 94.80 | 112.07 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2038.99 | 0.00 | -85.43 | -2971.78 |
PERIMETER_MID_ZN_4 | 04-FEB-07:03 | 0.00 | 0.00 | 3162.67 | 0.00 | 0.00 | 0.00 | 60.62 | 72.15 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1702.30 | 0.00 | -56.36 | -1940.58 |
TOPFLOOR_PLENUM | 23-OCT-05:01 | 6232.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4.51 | -6227.83 |
MIDFLOOR_PLENUM | 22-JAN-16:10 | 2315.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -35.66 | -2280.14 |
FIRSTFLOOR_PLENUM | 22-SEP-04:02 | 3686.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3708.52 |
Total Facility | 04-FEB-07:03 | -25168.52 | 26784.28 | 39680.29 | -26784.28 | 0.00 | 0.00 | 2138.71 | 2746.64 | 22473.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19487.17 | 0.00 | -1214.17 | -21168.89 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.8226 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3708 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.4553 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.9369 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.9449 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6930 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4113 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0759 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2276 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0761 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4725 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4804 | 2.4804 | 0.6375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9849 | 1.9849 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1755 | 2.1755 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6815 | 0.6815 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6510 | 0.6510 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6975 | 0.6975 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7394 | 0.7394 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5720 | 0.5720 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5784 | 0.5784 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5802 | 0.5802 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6116 | 0.6116 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5869 | 0.5869 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6226 | 0.6226 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5965 | 0.5965 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6644 | 0.6644 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.8226 | 4.3708 | 4.8226 | 1.0759 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.4553 | 3.9369 | 4.4553 | 1.0761 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.9449 | 4.6930 | 4.9449 | 1.0766 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2402 | 1.2402 | 0.6375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9925 | 0.9925 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0878 | 1.0878 | 0.6374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3407 | 0.3407 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3255 | 0.3255 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3487 | 0.3487 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3697 | 0.3697 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2860 | 0.2860 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2892 | 0.2892 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2901 | 0.2901 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3058 | 0.3058 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2934 | 0.2934 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3113 | 0.3113 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2982 | 0.2982 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3322 | 0.3322 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4113 | 1.0759 | 1.0759 | 1.0759 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2276 | 1.0761 | 1.0761 | 1.0761 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4725 | 1.0766 | 1.0766 | 1.0766 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 17.67 |
Number of hours cooling loads not met | 577.50 |
Number of hours not met | 595.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 1.06 | 29191.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 613.78 | 73097.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.76 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.63 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.21 | 15510.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 39.17 | 4619.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1779.34 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1779.34 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.52 |
Space Heating | 0.21 |
Space Cooling | 123.19 |
Fans (All) | 19.31 |
Service Water Heating | 7.86 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 357.14 |
Subtotal | 357.14 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.03 |
Space Heating | 0.06 |
Space Cooling | 34.49 |
Fans (All) | 5.41 |
Service Water Heating | 2.20 |
Receptacle Equipment | 40.45 |
Miscellaneous | 4.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1081. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7723.83 | 1036.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8702.00 | 58.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8475.67 | 284.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8264.83 | 495.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8292.50 | 467.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8154.83 | 605.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8708.33 | 51.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8372.00 | 388.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8375.67 | 384.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8239.50 | 520.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8554.50 | 205.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8294.00 | 466.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8335.00 | 425.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8166.50 | 593.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8179.33 | 580.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8732.33 | 27.67 | 0.00 | 0.00 | 0.00 |
Min | 7723.83 | 21.67 | 0.00 | 0.00 | 0.00 |
Max | 8738.33 | 1036.17 | 0.00 | 0.00 | 0.00 |
Average | 8388.68 | 371.32 | 0.00 | 0.00 | 0.00 |
Sum | 150996.17 | 6683.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127974.00 | 330.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128294.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128292.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24866.50 | 42.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128294.00 | 330.00 | 0.00 | 0.00 | 0.00 |
Average | 34121.45 | 21.88 | 0.00 | 0.00 | 0.00 |
Sum | 614186.17 | 393.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7196.17 | 1563.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8548.50 | 211.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8634.00 | 126.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6468.33 | 2291.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6307.50 | 2452.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6343.17 | 2416.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6218.00 | 2542.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6886.50 | 1873.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6466.67 | 2293.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5511.83 | 3248.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6324.67 | 2435.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6422.50 | 2337.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6210.17 | 2549.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6240.33 | 2519.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6089.00 | 2671.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6692.50 | 2067.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7137.00 | 1623.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 7392.83 | 1367.17 | 0.00 | 0.00 | 0.00 |
Min | 5511.83 | 126.00 | 0.00 | 0.00 | 0.00 |
Max | 8634.00 | 3248.17 | 0.00 | 0.00 | 0.00 |
Average | 6727.20 | 2032.80 | 0.00 | 0.00 | 0.00 |
Sum | 121089.67 | 36590.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127669.67 | 634.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128222.33 | 81.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128272.33 | 31.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24856.17 | 52.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24855.33 | 53.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24901.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 20073.00 | 4836.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24866.33 | 42.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24865.17 | 43.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128272.33 | 4836.00 | 0.00 | 0.00 | 0.00 |
Average | 33821.96 | 321.37 | 0.00 | 0.00 | 0.00 |
Sum | 608795.33 | 5784.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:06
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233109E+11 | 36426.31 | 02-JAN-06:12 | 19.23 | 19.01 | 0.199564E+10 | 2606.74 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.213103E+11 | 38355.29 | 13-FEB-06:12 | 20.60 | 19.45 | 0.181067E+10 | 2606.66 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.253167E+11 | 37498.37 | 28-MAR-05:12 | 21.50 | 19.84 | 0.216212E+10 | 2606.66 | 01-MAR-10:20 | 21.50 | 19.84 |
April | 0.247251E+11 | 38480.73 | 12-APR-04:03 | 24.40 | 22.16 | 0.192010E+10 | 2606.67 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.277553E+11 | 42428.06 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207902E+10 | 2606.60 | 30-MAY-13:20 | 26.33 | 24.24 |
June | 0.279424E+11 | 41184.40 | 06-JUN-05:03 | 23.98 | 23.24 | 0.207209E+10 | 2606.60 | 05-JUN-13:20 | 23.98 | 23.24 |
July | 0.279436E+11 | 38974.05 | 06-JUL-04:03 | 23.90 | 22.27 | 0.192587E+10 | 2606.60 | 14-JUL-13:20 | 28.90 | 25.24 |
August | 0.292540E+11 | 38329.57 | 12-AUG-04:03 | 23.90 | 23.16 | 0.216158E+10 | 2606.60 | 07-AUG-13:20 | 23.90 | 23.16 |
September | 0.274499E+11 | 38548.92 | 28-SEP-04:03 | 23.90 | 23.16 | 0.191952E+10 | 2606.59 | 11-SEP-13:20 | 23.90 | 23.16 |
October | 0.277328E+11 | 41515.04 | 23-OCT-05:03 | 23.72 | 21.83 | 0.199712E+10 | 2606.60 | 10-OCT-13:20 | 23.72 | 21.83 |
November | 0.251442E+11 | 38604.11 | 20-NOV-05:02 | 24.40 | 20.52 | 0.197788E+10 | 2606.75 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.229549E+11 | 36952.89 | 08-DEC-06:12 | 22.80 | 21.59 | 0.192616E+10 | 2606.66 | 15-DEC-14:20 | 19.27 | 14.31 |
Annual Sum or Average | 0.310840E+12 | 0.239478E+11 | ||||||||
Minimum of Months | 0.213103E+11 | 36426.31 | 19.23 | 19.01 | 0.181067E+10 | 2606.59 | 19.27 | 14.31 | ||
Maximum of Months | 0.292540E+11 | 42428.06 | 24.40 | 23.24 | 0.216212E+10 | 2606.75 | 28.90 | 25.24 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244946E+10 | 7850.82 | 02-JAN-15:05 | 28.35 | 22.91 | 0.00 | 0.00 | 01-JAN-00:10 | 28.35 | 22.91 |
February | 0.313124E+10 | 7788.77 | 22-FEB-15:20 | 27.80 | 14.51 | 0.00 | 0.00 | 01-FEB-00:10 | 27.80 | 14.51 |
March | 0.423885E+10 | 8983.55 | 27-MAR-15:00 | 27.80 | 22.40 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 22.40 |
April | 0.546765E+10 | 9760.03 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.696330E+10 | 10858.36 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.727664E+10 | 10421.13 | 11-JUN-13:43 | 31.78 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 31.78 | 23.81 |
July | 0.798336E+10 | 11215.14 | 28-JUL-15:30 | 35.00 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.05 |
August | 0.728423E+10 | 10711.67 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.673395E+10 | 10490.30 | 18-SEP-14:00 | 31.10 | 24.95 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 24.95 |
October | 0.568040E+10 | 10124.56 | 06-OCT-13:05 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.404243E+10 | 8244.29 | 10-NOV-14:05 | 28.90 | 24.10 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.10 |
December | 0.264102E+10 | 7157.83 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.638925E+11 | 0.00 | ||||||||
Minimum of Months | 0.244946E+10 | 7157.83 | 27.40 | 14.51 | 0.00 | 0.00 | 27.40 | 14.51 | ||
Maximum of Months | 0.798336E+10 | 11215.14 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143934E+10 | 3916.31 | 02-JAN-16:10 | 25.50 | 20.58 | 0.00 | 0.00 | 01-JAN-00:10 | 25.50 | 20.58 |
February | 0.165750E+10 | 3403.09 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.229114E+10 | 3962.96 | 27-MAR-15:50 | 27.30 | 22.22 | 0.00 | 0.00 | 01-MAR-00:10 | 27.30 | 22.22 |
April | 0.281772E+10 | 4150.46 | 17-APR-15:30 | 31.95 | 20.03 | 0.00 | 0.00 | 01-APR-00:10 | 31.95 | 20.03 |
May | 0.371264E+10 | 4583.62 | 30-MAY-12:02 | 30.18 | 24.35 | 0.00 | 0.00 | 01-MAY-00:10 | 30.18 | 24.35 |
June | 0.400042E+10 | 4508.53 | 26-JUN-12:08 | 30.68 | 25.17 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 25.17 |
July | 0.419573E+10 | 5046.24 | 31-JUL-12:02 | 32.93 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 25.13 |
August | 0.412843E+10 | 4751.59 | 21-AUG-12:15 | 28.17 | 25.80 | 0.00 | 0.00 | 01-AUG-00:10 | 28.17 | 25.80 |
September | 0.384644E+10 | 4892.81 | 11-SEP-12:08 | 31.52 | 24.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.52 | 24.53 |
October | 0.355916E+10 | 4755.68 | 10-OCT-06:03 | 23.98 | 22.48 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 22.48 |
November | 0.253620E+10 | 4097.12 | 06-NOV-16:40 | 27.80 | 20.25 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.25 |
December | 0.161558E+10 | 3748.11 | 11-DEC-07:03 | 22.12 | 20.55 | 0.00 | 0.00 | 01-DEC-00:10 | 22.12 | 20.55 |
Annual Sum or Average | 0.358003E+11 | 0.00 | ||||||||
Minimum of Months | 0.143934E+10 | 3403.09 | 22.12 | 14.07 | 0.00 | 0.00 | 22.12 | 14.07 | ||
Maximum of Months | 0.419573E+10 | 5046.24 | 32.93 | 25.80 | 0.00 | 0.00 | 32.93 | 25.80 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225396E+10 | 4557.11 | 02-JAN-16:10 | 25.50 | 20.58 | 0.00 | 0.00 | 01-JAN-00:10 | 25.50 | 20.58 |
February | 0.232968E+10 | 4160.08 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.296446E+10 | 4412.81 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.335297E+10 | 4622.88 | 17-APR-15:50 | 31.78 | 20.21 | 0.00 | 0.00 | 01-APR-00:10 | 31.78 | 20.21 |
May | 0.425515E+10 | 5074.96 | 22-MAY-12:10 | 33.48 | 23.09 | 0.00 | 0.00 | 01-MAY-00:10 | 33.48 | 23.09 |
June | 0.451706E+10 | 4843.51 | 26-JUN-10:50 | 30.00 | 25.23 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 25.23 |
July | 0.470875E+10 | 5394.95 | 31-JUL-12:10 | 32.93 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 25.13 |
August | 0.479582E+10 | 5013.76 | 21-AUG-15:50 | 31.83 | 26.22 | 0.00 | 0.00 | 01-AUG-00:10 | 31.83 | 26.22 |
September | 0.447060E+10 | 5921.16 | 11-SEP-06:15 | 26.70 | 24.27 | 0.00 | 0.00 | 01-SEP-00:10 | 26.70 | 24.27 |
October | 0.431935E+10 | 5276.67 | 30-OCT-06:15 | 26.70 | 25.38 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 25.38 |
November | 0.338684E+10 | 4607.12 | 06-NOV-16:20 | 27.80 | 20.13 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.13 |
December | 0.235254E+10 | 4097.85 | 11-DEC-16:10 | 23.72 | 17.48 | 0.00 | 0.00 | 01-DEC-00:10 | 23.72 | 17.48 |
Annual Sum or Average | 0.437072E+11 | 0.00 | ||||||||
Minimum of Months | 0.225396E+10 | 4097.85 | 23.72 | 14.07 | 0.00 | 0.00 | 23.72 | 14.07 | ||
Maximum of Months | 0.479582E+10 | 5921.16 | 33.48 | 26.22 | 0.00 | 0.00 | 33.48 | 26.22 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151537E+11 | 27329.45 | 02-JAN-07:03 | 19.08 | 19.01 | 0.197328E+10 | 2606.69 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.143681E+11 | 29139.17 | 13-FEB-06:12 | 20.60 | 19.45 | 0.179296E+10 | 2606.70 | 23-FEB-10:39 | 23.87 | 17.94 |
March | 0.174299E+11 | 26565.70 | 28-MAR-05:12 | 21.50 | 19.84 | 0.214762E+10 | 2606.66 | 17-MAR-13:20 | 21.50 | 19.84 |
April | 0.177375E+11 | 29173.93 | 24-APR-05:12 | 22.60 | 19.73 | 0.191237E+10 | 2606.68 | 20-APR-09:09 | 22.60 | 19.73 |
May | 0.202416E+11 | 33012.01 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207357E+10 | 2606.60 | 30-MAY-13:20 | 26.33 | 24.24 |
June | 0.206188E+11 | 32295.81 | 06-JUN-05:03 | 23.98 | 23.24 | 0.206792E+10 | 2606.60 | 26-JUN-13:20 | 29.63 | 24.41 |
July | 0.208191E+11 | 30244.56 | 31-JUL-04:04 | 26.10 | 24.52 | 0.192135E+10 | 2606.60 | 31-JUL-13:20 | 31.83 | 25.29 |
August | 0.214079E+11 | 29528.83 | 08-AUG-04:02 | 26.10 | 23.70 | 0.215703E+10 | 2606.60 | 07-AUG-13:20 | 26.10 | 23.70 |
September | 0.200058E+11 | 30666.80 | 12-SEP-04:02 | 24.40 | 22.75 | 0.191508E+10 | 2606.60 | 11-SEP-13:20 | 24.40 | 22.75 |
October | 0.197481E+11 | 33705.22 | 02-OCT-04:04 | 26.70 | 25.03 | 0.199173E+10 | 2606.60 | 10-OCT-13:20 | 24.23 | 22.85 |
November | 0.171620E+11 | 30114.25 | 20-NOV-05:02 | 24.40 | 20.52 | 0.196921E+10 | 2606.67 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.152336E+11 | 27222.25 | 09-DEC-06:03 | 24.90 | 22.63 | 0.190338E+10 | 2606.64 | 22-DEC-10:20 | 23.67 | 18.72 |
Annual Sum or Average | 0.219926E+12 | 0.238255E+11 | ||||||||
Minimum of Months | 0.143681E+11 | 26565.70 | 19.08 | 19.01 | 0.179296E+10 | 2606.60 | 21.50 | 15.05 | ||
Maximum of Months | 0.214079E+11 | 33705.22 | 26.70 | 25.03 | 0.215703E+10 | 2606.70 | 31.83 | 25.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141141E+11 | 19082.29 | 02-JAN-15:00 | 28.90 | 23.37 | 0.192807E+10 | 2606.65 | 17-JAN-14:20 | 21.87 | 15.57 |
February | 0.139220E+11 | 17555.45 | 21-FEB-15:40 | 26.10 | 13.89 | 0.176997E+10 | 2606.68 | 23-FEB-10:50 | 24.13 | 18.14 |
March | 0.173726E+11 | 19157.61 | 27-MAR-15:30 | 27.50 | 22.30 | 0.212519E+10 | 2606.67 | 17-MAR-13:20 | 27.50 | 22.30 |
April | 0.184828E+11 | 31651.40 | 13-APR-05:03 | 24.40 | 22.09 | 0.190808E+10 | 2606.69 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.216059E+11 | 35525.94 | 08-MAY-05:03 | 23.90 | 19.12 | 0.207340E+10 | 2606.59 | 30-MAY-13:20 | 26.33 | 24.24 |
June | 0.223731E+11 | 33681.21 | 19-JUN-04:03 | 24.40 | 22.82 | 0.206872E+10 | 2606.59 | 05-JUN-13:20 | 24.40 | 22.82 |
July | 0.226741E+11 | 33383.63 | 24-JUL-04:03 | 24.32 | 23.63 | 0.192254E+10 | 2606.59 | 14-JUL-13:20 | 24.32 | 23.63 |
August | 0.228147E+11 | 32658.89 | 28-AUG-04:03 | 26.10 | 24.57 | 0.215721E+10 | 2606.59 | 09-AUG-13:20 | 26.10 | 24.57 |
September | 0.211570E+11 | 32844.38 | 25-SEP-04:02 | 24.40 | 22.60 | 0.191507E+10 | 2606.59 | 11-SEP-13:20 | 24.40 | 22.60 |
October | 0.200870E+11 | 35702.24 | 23-OCT-05:03 | 23.72 | 21.83 | 0.198940E+10 | 2606.66 | 18-OCT-09:20 | 23.72 | 21.83 |
November | 0.168584E+11 | 32327.61 | 06-NOV-06:12 | 20.93 | 19.77 | 0.195820E+10 | 2606.66 | 27-NOV-14:20 | 23.90 | 17.11 |
December | 0.143979E+11 | 23270.81 | 11-DEC-07:03 | 22.12 | 20.55 | 0.186312E+10 | 2606.65 | 04-DEC-10:00 | 22.12 | 20.55 |
Annual Sum or Average | 0.225860E+12 | 0.236790E+11 | ||||||||
Minimum of Months | 0.139220E+11 | 17555.45 | 20.93 | 13.89 | 0.176997E+10 | 2606.59 | 21.87 | 15.57 | ||
Maximum of Months | 0.228147E+11 | 35702.24 | 28.90 | 24.57 | 0.215721E+10 | 2606.69 | 27.50 | 24.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293250E+10 | 5105.41 | 02-JAN-15:00 | 28.90 | 23.37 | 0.392892E+09 | 549.50 | 10-JAN-14:20 | 22.20 | 16.25 |
February | 0.320830E+10 | 5092.24 | 17-FEB-14:10 | 26.70 | 21.67 | 0.366943E+09 | 549.49 | 27-FEB-14:20 | 26.10 | 16.48 |
March | 0.415964E+10 | 5654.97 | 27-MAR-15:00 | 27.80 | 22.40 | 0.439306E+09 | 549.50 | 17-MAR-13:20 | 27.80 | 22.40 |
April | 0.496327E+10 | 9151.77 | 16-APR-14:13 | 31.70 | 21.16 | 0.401535E+09 | 549.50 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.660206E+10 | 11477.65 | 29-MAY-16:32 | 32.23 | 24.43 | 0.437792E+09 | 549.48 | 08-MAY-13:20 | 32.23 | 24.43 |
June | 0.724975E+10 | 11617.06 | 11-JUN-15:42 | 31.10 | 24.29 | 0.436853E+09 | 549.49 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.742808E+10 | 11483.26 | 30-JUL-16:12 | 29.80 | 25.10 | 0.406340E+09 | 549.48 | 10-JUL-09:20 | 29.80 | 25.10 |
August | 0.706505E+10 | 11547.75 | 20-AUG-13:32 | 32.20 | 25.18 | 0.455510E+09 | 549.49 | 07-AUG-13:20 | 32.20 | 25.18 |
September | 0.634007E+10 | 11464.99 | 04-SEP-13:23 | 30.00 | 24.33 | 0.404339E+09 | 549.49 | 05-SEP-13:20 | 26.47 | 23.62 |
October | 0.545269E+10 | 9299.75 | 23-OCT-05:01 | 23.72 | 21.83 | 0.419674E+09 | 549.50 | 18-OCT-09:20 | 23.72 | 21.83 |
November | 0.419354E+10 | 6023.54 | 04-NOV-05:03 | 25.10 | 23.95 | 0.410063E+09 | 549.50 | 27-NOV-14:20 | 23.90 | 17.11 |
December | 0.310976E+10 | 4902.52 | 08-DEC-14:10 | 27.70 | 22.74 | 0.381653E+09 | 549.50 | 04-DEC-10:20 | 27.70 | 22.74 |
Annual Sum or Average | 0.627047E+11 | 0.495290E+10 | ||||||||
Minimum of Months | 0.293250E+10 | 4902.52 | 23.72 | 21.16 | 0.366943E+09 | 549.48 | 22.20 | 16.25 | ||
Maximum of Months | 0.742808E+10 | 11617.06 | 32.23 | 25.18 | 0.455510E+09 | 549.50 | 32.23 | 25.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248065E+10 | 9202.07 | 01-JAN-11:02 | 26.60 | 21.53 | 0.259979E+09 | 347.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.280189E+10 | 5127.53 | 20-FEB-10:13 | 20.97 | 16.57 | 0.237683E+09 | 347.89 | 23-FEB-10:39 | 23.87 | 17.94 |
March | 0.382817E+10 | 6885.70 | 26-MAR-10:13 | 25.60 | 21.37 | 0.285502E+09 | 347.88 | 03-MAR-10:20 | 25.60 | 21.37 |
April | 0.456399E+10 | 11292.36 | 09-APR-09:02 | 24.27 | 18.85 | 0.255364E+09 | 347.89 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.547386E+10 | 11323.75 | 07-MAY-09:23 | 27.50 | 21.81 | 0.277408E+09 | 347.87 | 31-MAY-09:20 | 29.97 | 24.08 |
June | 0.576299E+10 | 11388.83 | 04-JUN-09:43 | 30.50 | 24.92 | 0.276734E+09 | 347.87 | 14-JUN-09:20 | 28.17 | 23.37 |
July | 0.596242E+10 | 11457.93 | 23-JUL-09:52 | 30.00 | 24.68 | 0.257536E+09 | 347.87 | 17-JUL-09:20 | 30.00 | 24.68 |
August | 0.570791E+10 | 11319.55 | 06-AUG-10:43 | 30.82 | 24.91 | 0.288569E+09 | 347.87 | 08-AUG-09:20 | 31.30 | 24.59 |
September | 0.523951E+10 | 11356.47 | 17-SEP-10:02 | 30.10 | 24.08 | 0.256328E+09 | 347.87 | 14-SEP-09:20 | 30.10 | 24.08 |
October | 0.467253E+10 | 9584.48 | 09-OCT-11:43 | 28.95 | 24.01 | 0.266232E+09 | 347.88 | 18-OCT-09:20 | 26.70 | 18.90 |
November | 0.345706E+10 | 5644.47 | 07-NOV-09:50 | 25.32 | 21.18 | 0.262124E+09 | 347.88 | 15-NOV-10:50 | 25.40 | 17.35 |
December | 0.241752E+10 | 4758.17 | 08-DEC-10:30 | 26.65 | 22.70 | 0.249155E+09 | 347.88 | 04-DEC-10:00 | 26.65 | 22.70 |
Annual Sum or Average | 0.523685E+11 | 0.317261E+10 | ||||||||
Minimum of Months | 0.241752E+10 | 4758.17 | 20.97 | 16.57 | 0.237683E+09 | 347.87 | 21.70 | 15.05 | ||
Maximum of Months | 0.596242E+10 | 11457.93 | 30.82 | 24.92 | 0.288569E+09 | 347.89 | 31.30 | 24.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591924E+10 | 13157.60 | 15-JAN-14:12 | 25.60 | 16.66 | 0.411646E+09 | 604.78 | 02-JAN-14:39 | 25.60 | 16.66 |
February | 0.569269E+10 | 13510.98 | 20-FEB-14:12 | 26.30 | 17.81 | 0.375995E+09 | 586.36 | 21-FEB-14:39 | 25.93 | 14.05 |
March | 0.623849E+10 | 12486.95 | 26-MAR-13:32 | 27.60 | 22.33 | 0.446293E+09 | 558.38 | 01-MAR-14:39 | 27.60 | 22.33 |
April | 0.587471E+10 | 12087.11 | 16-APR-14:13 | 31.70 | 21.16 | 0.401992E+09 | 549.50 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.658061E+10 | 11711.84 | 29-MAY-15:52 | 33.30 | 24.52 | 0.437654E+09 | 549.48 | 23-MAY-13:20 | 33.30 | 24.52 |
June | 0.691107E+10 | 11793.46 | 11-JUN-15:42 | 31.10 | 24.29 | 0.436684E+09 | 549.49 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.725163E+10 | 11801.74 | 30-JUL-16:12 | 29.80 | 25.10 | 0.406188E+09 | 549.48 | 10-JUL-09:20 | 29.80 | 25.10 |
August | 0.758754E+10 | 12200.51 | 20-AUG-13:32 | 32.20 | 25.18 | 0.455569E+09 | 549.49 | 07-AUG-13:20 | 32.20 | 25.18 |
September | 0.777345E+10 | 12376.96 | 17-SEP-11:23 | 30.85 | 24.38 | 0.404761E+09 | 561.43 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.810021E+10 | 12596.77 | 29-OCT-12:42 | 30.10 | 25.68 | 0.422244E+09 | 578.20 | 25-OCT-13:20 | 30.10 | 25.68 |
November | 0.704689E+10 | 12886.05 | 26-NOV-13:22 | 21.70 | 13.59 | 0.417086E+09 | 601.79 | 07-NOV-14:09 | 21.70 | 13.59 |
December | 0.607126E+10 | 12665.90 | 03-DEC-14:12 | 24.40 | 18.45 | 0.396832E+09 | 604.46 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.810478E+11 | 0.501294E+10 | ||||||||
Minimum of Months | 0.569269E+10 | 11711.84 | 21.70 | 13.59 | 0.375995E+09 | 549.48 | 21.70 | 13.59 | ||
Maximum of Months | 0.810021E+10 | 13510.98 | 33.30 | 25.68 | 0.455569E+09 | 604.78 | 33.30 | 25.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243549E+10 | 6546.73 | 01-JAN-15:02 | 26.02 | 21.87 | 0.251256E+09 | 347.85 | 19-JAN-14:20 | 25.00 | 18.32 |
February | 0.280811E+10 | 12675.80 | 20-FEB-14:52 | 26.70 | 17.88 | 0.233742E+09 | 347.85 | 23-FEB-10:00 | 24.40 | 18.34 |
March | 0.387587E+10 | 11957.98 | 12-MAR-16:32 | 24.40 | 18.55 | 0.279455E+09 | 347.85 | 03-MAR-10:20 | 24.40 | 18.55 |
April | 0.450857E+10 | 13833.91 | 02-APR-16:22 | 26.15 | 18.17 | 0.254789E+09 | 347.86 | 21-APR-09:20 | 25.40 | 18.57 |
May | 0.534529E+10 | 13041.95 | 29-MAY-16:32 | 32.23 | 24.43 | 0.277325E+09 | 347.84 | 23-MAY-09:20 | 32.23 | 24.43 |
June | 0.530484E+10 | 13006.79 | 11-JUN-15:42 | 31.10 | 24.29 | 0.276628E+09 | 347.84 | 05-JUN-13:20 | 31.10 | 24.29 |
July | 0.566640E+10 | 12945.97 | 09-JUL-16:42 | 30.18 | 25.15 | 0.257372E+09 | 347.84 | 10-JUL-09:20 | 25.73 | 23.67 |
August | 0.562470E+10 | 12704.22 | 20-AUG-16:12 | 30.60 | 24.86 | 0.288568E+09 | 347.85 | 28-AUG-09:20 | 22.80 | 22.16 |
September | 0.489681E+10 | 13010.45 | 10-SEP-15:42 | 31.10 | 25.01 | 0.256205E+09 | 347.84 | 14-SEP-09:20 | 28.53 | 24.80 |
October | 0.449227E+10 | 11945.94 | 09-OCT-16:22 | 29.15 | 23.75 | 0.266049E+09 | 347.85 | 18-OCT-09:20 | 26.70 | 18.90 |
November | 0.342702E+10 | 11540.80 | 05-NOV-15:23 | 27.80 | 23.97 | 0.260212E+09 | 347.85 | 15-NOV-10:20 | 24.80 | 17.20 |
December | 0.264598E+10 | 9266.25 | 10-DEC-15:22 | 28.60 | 22.59 | 0.244076E+09 | 347.85 | 04-DEC-10:20 | 28.60 | 22.59 |
Annual Sum or Average | 0.510314E+11 | 0.314568E+10 | ||||||||
Minimum of Months | 0.243549E+10 | 6546.73 | 24.40 | 17.88 | 0.233742E+09 | 347.84 | 22.80 | 17.20 | ||
Maximum of Months | 0.566640E+10 | 13833.91 | 32.23 | 25.15 | 0.288568E+09 | 347.86 | 32.23 | 24.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318853E+10 | 4531.32 | 02-JAN-15:00 | 28.90 | 23.37 | 0.407877E+09 | 549.50 | 12-JAN-10:20 | 24.07 | 19.17 |
February | 0.317572E+10 | 4458.52 | 17-FEB-13:40 | 26.70 | 21.06 | 0.374272E+09 | 549.50 | 27-FEB-10:20 | 22.93 | 16.26 |
March | 0.382318E+10 | 4683.56 | 06-MAR-14:10 | 24.90 | 22.15 | 0.445350E+09 | 549.50 | 23-MAR-09:20 | 23.17 | 17.42 |
April | 0.434967E+10 | 5651.14 | 17-APR-15:20 | 32.03 | 19.94 | 0.402583E+09 | 549.50 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.597392E+10 | 7589.72 | 24-MAY-05:02 | 23.98 | 22.69 | 0.437651E+09 | 549.49 | 31-MAY-09:20 | 29.97 | 24.08 |
June | 0.662180E+10 | 7650.37 | 12-JUN-04:02 | 25.60 | 24.44 | 0.436573E+09 | 549.49 | 05-JUN-13:20 | 25.60 | 24.44 |
July | 0.698249E+10 | 7641.37 | 17-JUL-04:02 | 26.02 | 23.69 | 0.406124E+09 | 549.49 | 17-JUL-09:20 | 28.70 | 25.06 |
August | 0.696314E+10 | 8003.58 | 02-AUG-04:02 | 27.20 | 23.27 | 0.455549E+09 | 549.49 | 07-AUG-13:20 | 29.07 | 24.82 |
September | 0.639718E+10 | 7640.26 | 04-SEP-13:23 | 30.00 | 24.33 | 0.404518E+09 | 549.49 | 14-SEP-09:20 | 28.53 | 24.80 |
October | 0.575233E+10 | 7544.28 | 30-OCT-04:02 | 26.28 | 24.93 | 0.420401E+09 | 549.49 | 26-OCT-13:20 | 26.28 | 24.93 |
November | 0.450211E+10 | 5978.66 | 24-NOV-07:03 | 21.10 | 21.10 | 0.414616E+09 | 549.51 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.339771E+10 | 5594.94 | 11-DEC-07:03 | 22.12 | 20.55 | 0.396330E+09 | 549.50 | 27-DEC-14:20 | 20.20 | 15.38 |
Annual Sum or Average | 0.611278E+11 | 0.500184E+10 | ||||||||
Minimum of Months | 0.317572E+10 | 4458.52 | 21.10 | 19.94 | 0.374272E+09 | 549.49 | 20.20 | 15.38 | ||
Maximum of Months | 0.698249E+10 | 8003.58 | 32.03 | 24.93 | 0.455549E+09 | 549.51 | 29.97 | 25.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284179E+10 | 9618.20 | 01-JAN-10:02 | 25.28 | 21.21 | 0.264161E+09 | 347.89 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.289229E+10 | 4748.88 | 28-FEB-10:00 | 24.40 | 16.28 | 0.240063E+09 | 347.88 | 27-FEB-10:09 | 24.40 | 16.28 |
March | 0.369868E+10 | 5781.46 | 27-MAR-10:30 | 25.85 | 21.67 | 0.287022E+09 | 347.88 | 01-MAR-10:20 | 25.85 | 21.67 |
April | 0.423833E+10 | 10347.94 | 16-APR-10:02 | 27.57 | 21.70 | 0.255844E+09 | 347.88 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.509084E+10 | 9927.79 | 07-MAY-09:13 | 27.23 | 21.79 | 0.277436E+09 | 347.87 | 31-MAY-09:20 | 29.97 | 24.08 |
June | 0.537264E+10 | 9953.94 | 04-JUN-09:43 | 30.50 | 24.92 | 0.276698E+09 | 347.87 | 14-JUN-09:20 | 28.17 | 23.37 |
July | 0.570974E+10 | 10762.63 | 23-JUL-09:42 | 30.10 | 24.77 | 0.257563E+09 | 347.87 | 17-JUL-09:20 | 30.10 | 24.77 |
August | 0.569210E+10 | 9959.22 | 06-AUG-10:43 | 30.82 | 24.91 | 0.288705E+09 | 347.87 | 08-AUG-09:20 | 31.30 | 24.59 |
September | 0.537794E+10 | 10347.07 | 10-SEP-10:12 | 30.20 | 24.63 | 0.256508E+09 | 347.87 | 14-SEP-09:20 | 28.53 | 24.80 |
October | 0.496328E+10 | 8653.81 | 29-OCT-12:32 | 30.20 | 25.52 | 0.266619E+09 | 347.87 | 11-OCT-09:20 | 30.20 | 25.52 |
November | 0.378490E+10 | 5442.67 | 20-NOV-07:03 | 24.40 | 20.33 | 0.263353E+09 | 347.89 | 27-NOV-10:50 | 21.65 | 16.17 |
December | 0.273288E+10 | 4940.81 | 11-DEC-07:03 | 22.12 | 20.55 | 0.254339E+09 | 347.88 | 21-DEC-10:20 | 19.27 | 15.54 |
Annual Sum or Average | 0.523954E+11 | 0.318831E+10 | ||||||||
Minimum of Months | 0.273288E+10 | 4748.88 | 22.12 | 16.28 | 0.240063E+09 | 347.87 | 19.27 | 15.05 | ||
Maximum of Months | 0.570974E+10 | 10762.63 | 30.82 | 25.52 | 0.288705E+09 | 347.89 | 31.30 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575181E+10 | 10528.86 | 01-JAN-12:02 | 26.28 | 21.27 | 0.415572E+09 | 636.46 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.568584E+10 | 10425.61 | 26-FEB-12:43 | 24.82 | 16.09 | 0.379512E+09 | 604.58 | 21-FEB-14:50 | 24.82 | 16.09 |
March | 0.574153E+10 | 10220.42 | 26-MAR-13:32 | 27.60 | 22.33 | 0.444664E+09 | 568.16 | 13-MAR-12:09 | 27.60 | 22.33 |
April | 0.575868E+10 | 9243.67 | 17-APR-16:10 | 31.60 | 20.14 | 0.402976E+09 | 610.73 | 13-APR-12:09 | 31.60 | 20.14 |
May | 0.720589E+10 | 9956.75 | 22-MAY-12:00 | 33.30 | 23.06 | 0.440435E+09 | 677.55 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.771568E+10 | 9197.98 | 09-JUN-12:00 | 31.10 | 24.24 | 0.439607E+09 | 617.14 | 09-JUN-12:09 | 31.02 | 24.35 |
July | 0.832948E+10 | 10179.60 | 27-JUL-16:50 | 34.50 | 24.87 | 0.411852E+09 | 687.42 | 31-JUL-12:09 | 32.93 | 25.13 |
August | 0.911180E+10 | 10054.36 | 23-AUG-12:00 | 33.30 | 23.92 | 0.463436E+09 | 683.21 | 23-AUG-12:09 | 33.40 | 24.17 |
September | 0.893987E+10 | 10256.69 | 24-SEP-10:52 | 31.10 | 25.31 | 0.415901E+09 | 669.29 | 11-SEP-12:09 | 31.10 | 25.31 |
October | 0.928813E+10 | 11029.56 | 29-OCT-12:32 | 30.20 | 25.52 | 0.436405E+09 | 677.53 | 03-OCT-12:09 | 30.20 | 25.52 |
November | 0.780682E+10 | 10460.78 | 19-NOV-11:23 | 26.70 | 21.51 | 0.426357E+09 | 643.45 | 08-NOV-13:09 | 26.70 | 21.51 |
December | 0.595550E+10 | 10503.83 | 25-DEC-15:02 | 26.10 | 23.34 | 0.401182E+09 | 628.38 | 04-DEC-14:39 | 26.10 | 23.34 |
Annual Sum or Average | 0.872910E+11 | 0.507790E+10 | ||||||||
Minimum of Months | 0.568584E+10 | 9197.98 | 24.82 | 16.09 | 0.379512E+09 | 568.16 | 24.82 | 16.09 | ||
Maximum of Months | 0.928813E+10 | 11029.56 | 34.50 | 25.52 | 0.463436E+09 | 687.42 | 33.48 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264737E+10 | 4962.23 | 17-JAN-16:30 | 21.95 | 15.46 | 0.261628E+09 | 347.85 | 17-JAN-10:20 | 21.95 | 15.46 |
February | 0.280944E+10 | 9323.68 | 19-FEB-16:52 | 26.70 | 21.74 | 0.238896E+09 | 347.85 | 27-FEB-10:20 | 22.93 | 16.26 |
March | 0.364022E+10 | 8078.02 | 26-MAR-14:53 | 27.80 | 21.74 | 0.284849E+09 | 347.85 | 01-MAR-10:20 | 27.80 | 21.74 |
April | 0.412944E+10 | 11110.27 | 02-APR-16:22 | 26.15 | 18.17 | 0.255812E+09 | 347.85 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.493447E+10 | 9409.60 | 20-MAY-17:05 | 29.22 | 21.97 | 0.277453E+09 | 347.85 | 18-MAY-09:20 | 29.22 | 21.97 |
June | 0.488181E+10 | 10662.98 | 11-JUN-15:42 | 31.10 | 24.29 | 0.276584E+09 | 347.85 | 12-JUN-09:20 | 29.80 | 23.82 |
July | 0.537576E+10 | 10715.20 | 09-JUL-16:42 | 30.18 | 25.15 | 0.257427E+09 | 347.85 | 17-JUL-09:20 | 28.70 | 25.06 |
August | 0.559635E+10 | 10497.95 | 20-AUG-16:12 | 30.60 | 24.86 | 0.288720E+09 | 347.85 | 28-AUG-09:20 | 22.80 | 22.16 |
September | 0.499330E+10 | 10765.06 | 10-SEP-15:31 | 31.10 | 25.07 | 0.256449E+09 | 347.85 | 14-SEP-09:20 | 28.53 | 24.80 |
October | 0.476897E+10 | 10688.30 | 15-OCT-15:02 | 29.32 | 21.07 | 0.266618E+09 | 347.85 | 02-OCT-09:20 | 29.32 | 21.07 |
November | 0.369540E+10 | 8946.66 | 05-NOV-15:23 | 27.80 | 23.97 | 0.263121E+09 | 347.86 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.290373E+10 | 9565.25 | 03-DEC-16:33 | 24.07 | 16.60 | 0.253333E+09 | 347.85 | 14-DEC-10:20 | 22.07 | 17.73 |
Annual Sum or Average | 0.503763E+11 | 0.318089E+10 | ||||||||
Minimum of Months | 0.264737E+10 | 4962.23 | 21.95 | 15.46 | 0.238896E+09 | 347.85 | 21.95 | 15.46 | ||
Maximum of Months | 0.559635E+10 | 11110.27 | 31.10 | 25.15 | 0.288720E+09 | 347.86 | 29.80 | 25.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.308943E+10 | 4815.64 | 02-JAN-15:00 | 28.90 | 23.37 | 0.403712E+09 | 549.50 | 10-JAN-14:20 | 22.20 | 16.25 |
February | 0.325335E+10 | 4697.98 | 17-FEB-13:40 | 26.70 | 21.06 | 0.372795E+09 | 549.51 | 23-FEB-10:20 | 23.33 | 17.54 |
March | 0.410274E+10 | 5101.88 | 27-MAR-13:30 | 27.25 | 22.08 | 0.445270E+09 | 549.50 | 02-MAR-10:20 | 27.25 | 22.08 |
April | 0.472350E+10 | 6144.20 | 17-APR-15:00 | 32.20 | 19.76 | 0.402821E+09 | 549.50 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.618354E+10 | 9752.36 | 29-MAY-16:32 | 32.23 | 24.43 | 0.437880E+09 | 549.49 | 31-MAY-09:20 | 29.97 | 24.08 |
June | 0.672300E+10 | 9187.24 | 11-JUN-15:42 | 31.10 | 24.29 | 0.436773E+09 | 549.49 | 12-JUN-09:20 | 29.80 | 23.82 |
July | 0.685086E+10 | 9628.38 | 04-JUL-16:41 | 30.28 | 25.19 | 0.406240E+09 | 549.49 | 03-JUL-13:20 | 30.28 | 25.19 |
August | 0.663673E+10 | 8786.34 | 20-AUG-13:32 | 32.20 | 25.18 | 0.455515E+09 | 549.49 | 07-AUG-13:20 | 32.20 | 25.18 |
September | 0.598785E+10 | 8004.03 | 30-SEP-05:03 | 24.40 | 22.82 | 0.404456E+09 | 549.49 | 11-SEP-13:20 | 24.40 | 22.82 |
October | 0.531094E+10 | 8090.51 | 10-OCT-04:02 | 24.32 | 22.47 | 0.420219E+09 | 549.49 | 26-OCT-13:20 | 26.83 | 22.68 |
November | 0.419892E+10 | 6735.05 | 04-NOV-05:03 | 25.10 | 23.95 | 0.413219E+09 | 549.50 | 15-NOV-10:20 | 24.80 | 17.20 |
December | 0.323162E+10 | 5134.22 | 11-DEC-07:03 | 22.12 | 20.55 | 0.391146E+09 | 549.50 | 04-DEC-10:20 | 22.12 | 20.55 |
Annual Sum or Average | 0.602925E+11 | 0.499005E+10 | ||||||||
Minimum of Months | 0.308943E+10 | 4697.98 | 22.12 | 19.76 | 0.372795E+09 | 549.49 | 22.12 | 16.25 | ||
Maximum of Months | 0.685086E+10 | 9752.36 | 32.23 | 25.19 | 0.455515E+09 | 549.51 | 32.20 | 25.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247527E+10 | 10704.58 | 01-JAN-10:02 | 25.28 | 21.21 | 0.194308E+09 | 356.47 | 27-JAN-11:09 | 21.88 | 15.22 |
February | 0.269054E+10 | 6391.26 | 26-FEB-10:03 | 22.48 | 16.09 | 0.177206E+09 | 356.46 | 27-FEB-11:09 | 24.60 | 16.46 |
March | 0.362715E+10 | 7537.47 | 27-MAR-10:05 | 25.28 | 21.59 | 0.211946E+09 | 356.46 | 23-MAR-10:09 | 25.28 | 21.59 |
April | 0.421223E+10 | 11383.11 | 16-APR-10:02 | 27.57 | 21.70 | 0.189850E+09 | 356.46 | 20-APR-10:09 | 24.68 | 18.29 |
May | 0.497122E+10 | 10796.99 | 07-MAY-09:13 | 27.23 | 21.79 | 0.205952E+09 | 356.45 | 01-MAY-10:09 | 27.23 | 21.79 |
June | 0.517888E+10 | 10831.36 | 04-JUN-07:42 | 27.52 | 24.83 | 0.205216E+09 | 356.45 | 12-JUN-10:09 | 30.60 | 24.46 |
July | 0.536542E+10 | 11784.03 | 23-JUL-09:42 | 30.10 | 24.77 | 0.191630E+09 | 356.45 | 25-JUL-10:09 | 32.88 | 25.45 |
August | 0.517913E+10 | 10728.38 | 06-AUG-10:02 | 29.68 | 24.70 | 0.213960E+09 | 356.45 | 08-AUG-10:09 | 31.88 | 24.65 |
September | 0.480722E+10 | 11242.75 | 10-SEP-09:32 | 29.43 | 24.83 | 0.190480E+09 | 356.45 | 11-SEP-14:09 | 27.33 | 24.11 |
October | 0.437187E+10 | 11140.01 | 09-OCT-08:52 | 28.30 | 24.27 | 0.198050E+09 | 356.45 | 26-OCT-10:09 | 28.90 | 23.36 |
November | 0.329109E+10 | 6026.16 | 02-NOV-10:05 | 26.78 | 21.36 | 0.195151E+09 | 356.46 | 13-NOV-11:09 | 21.47 | 15.13 |
December | 0.235618E+10 | 6121.32 | 20-DEC-13:01 | 13.98 | 7.33 | 0.186615E+09 | 356.45 | 13-DEC-15:09 | 13.98 | 7.33 |
Annual Sum or Average | 0.485262E+11 | 0.236037E+10 | ||||||||
Minimum of Months | 0.235618E+10 | 6026.16 | 13.98 | 7.33 | 0.177206E+09 | 356.45 | 13.98 | 7.33 | ||
Maximum of Months | 0.536542E+10 | 11784.03 | 30.10 | 24.83 | 0.213960E+09 | 356.47 | 32.88 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607419E+10 | 10844.92 | 15-JAN-11:43 | 24.72 | 17.05 | 0.419460E+09 | 629.67 | 02-JAN-14:39 | 24.72 | 17.05 |
February | 0.566051E+10 | 10850.85 | 19-FEB-13:32 | 26.83 | 21.86 | 0.381203E+09 | 611.26 | 21-FEB-14:20 | 25.77 | 14.45 |
March | 0.613113E+10 | 10603.22 | 26-MAR-14:02 | 27.80 | 22.29 | 0.450866E+09 | 580.30 | 01-MAR-14:20 | 27.80 | 22.29 |
April | 0.558607E+10 | 10083.03 | 16-APR-14:42 | 31.70 | 21.16 | 0.403292E+09 | 549.50 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.616052E+10 | 9600.14 | 29-MAY-15:52 | 33.30 | 24.52 | 0.437816E+09 | 549.49 | 22-MAY-13:20 | 33.30 | 24.52 |
June | 0.640384E+10 | 8361.28 | 26-JUN-04:03 | 25.60 | 24.44 | 0.436624E+09 | 549.49 | 21-JUN-13:20 | 25.60 | 24.44 |
July | 0.668255E+10 | 9874.06 | 30-JUL-16:12 | 29.80 | 25.10 | 0.406113E+09 | 549.49 | 03-JUL-13:20 | 29.80 | 25.10 |
August | 0.712946E+10 | 10228.35 | 20-AUG-12:53 | 32.20 | 25.55 | 0.455635E+09 | 555.49 | 31-AUG-13:20 | 31.70 | 24.32 |
September | 0.735320E+10 | 10529.98 | 24-SEP-10:52 | 31.10 | 25.31 | 0.405334E+09 | 574.27 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.782325E+10 | 11467.85 | 29-OCT-12:32 | 30.20 | 25.52 | 0.425361E+09 | 595.58 | 25-OCT-13:20 | 30.20 | 25.52 |
November | 0.690210E+10 | 10879.28 | 26-NOV-12:13 | 21.30 | 15.71 | 0.421910E+09 | 624.16 | 07-NOV-14:09 | 21.30 | 15.71 |
December | 0.616256E+10 | 10865.53 | 03-DEC-13:52 | 24.40 | 18.35 | 0.403906E+09 | 630.17 | 04-DEC-14:20 | 25.77 | 18.03 |
Annual Sum or Average | 0.780694E+11 | 0.504752E+10 | ||||||||
Minimum of Months | 0.558607E+10 | 8361.28 | 21.30 | 15.71 | 0.381203E+09 | 549.49 | 21.30 | 14.45 | ||
Maximum of Months | 0.782325E+10 | 11467.85 | 33.30 | 25.55 | 0.455635E+09 | 630.17 | 33.30 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253520E+10 | 5520.53 | 15-JAN-15:43 | 25.10 | 16.77 | 0.257685E+09 | 347.85 | 19-JAN-10:20 | 22.80 | 17.62 |
February | 0.280780E+10 | 10832.07 | 19-FEB-16:52 | 26.70 | 21.74 | 0.237177E+09 | 347.86 | 23-FEB-10:20 | 23.33 | 17.54 |
March | 0.379181E+10 | 11751.09 | 12-MAR-17:42 | 23.07 | 18.83 | 0.283116E+09 | 347.85 | 02-MAR-10:20 | 23.07 | 18.83 |
April | 0.428301E+10 | 11837.84 | 23-APR-16:42 | 26.60 | 21.27 | 0.255551E+09 | 347.86 | 20-APR-09:20 | 26.60 | 21.27 |
May | 0.501486E+10 | 11612.70 | 29-MAY-16:32 | 32.23 | 24.43 | 0.277431E+09 | 347.85 | 30-MAY-09:20 | 28.53 | 23.37 |
June | 0.492420E+10 | 11422.66 | 11-JUN-15:42 | 31.10 | 24.29 | 0.276612E+09 | 347.85 | 12-JUN-09:20 | 29.80 | 23.82 |
July | 0.523516E+10 | 11608.06 | 09-JUL-16:42 | 30.18 | 25.15 | 0.257354E+09 | 347.85 | 17-JUL-09:20 | 28.70 | 25.06 |
August | 0.529131E+10 | 11367.31 | 20-AUG-16:12 | 30.60 | 24.86 | 0.288586E+09 | 347.85 | 07-AUG-13:20 | 30.60 | 24.86 |
September | 0.463324E+10 | 11717.84 | 10-SEP-15:31 | 31.10 | 25.07 | 0.256299E+09 | 347.85 | 11-SEP-09:20 | 29.47 | 24.86 |
October | 0.436813E+10 | 11772.12 | 09-OCT-16:52 | 28.90 | 23.69 | 0.266361E+09 | 347.85 | 18-OCT-09:20 | 26.70 | 18.90 |
November | 0.340423E+10 | 10171.79 | 05-NOV-15:23 | 27.80 | 23.97 | 0.262083E+09 | 347.85 | 15-NOV-10:20 | 24.80 | 17.20 |
December | 0.272032E+10 | 9681.17 | 03-DEC-16:33 | 24.07 | 16.60 | 0.249453E+09 | 347.85 | 04-DEC-10:20 | 22.07 | 17.41 |
Annual Sum or Average | 0.490093E+11 | 0.316771E+10 | ||||||||
Minimum of Months | 0.253520E+10 | 5520.53 | 23.07 | 16.60 | 0.237177E+09 | 347.85 | 22.07 | 17.20 | ||
Maximum of Months | 0.529131E+10 | 11837.84 | 32.23 | 25.15 | 0.288586E+09 | 347.86 | 30.60 | 25.06 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.343916E+09 | 3478.18 | 25-JAN-06:03 | 9.40 |
February | 0.211865E+09 | 3752.89 | 04-FEB-07:03 | 5.28 |
March | 0.219646E+09 | 3668.85 | 16-MAR-05:03 | 6.70 |
April | 52596875.09 | 3014.06 | 13-APR-05:03 | 24.40 |
May | 20903125.60 | 5017.13 | 08-MAY-05:01 | 23.90 |
June | 18086973.21 | 4730.41 | 06-JUN-05:02 | 23.98 |
July | 22702643.49 | 5384.92 | 05-JUL-04:02 | 25.60 |
August | 17913902.38 | 4461.00 | 07-AUG-04:02 | 25.68 |
September | 18123535.13 | 4139.56 | 25-SEP-04:02 | 24.40 |
October | 24787856.32 | 6232.49 | 23-OCT-05:01 | 23.72 |
November | 86426349.63 | 3493.20 | 27-NOV-06:02 | 10.00 |
December | 0.268523E+09 | 3549.97 | 15-DEC-06:03 | 7.80 |
Annual Sum or Average | 0.130549E+10 | |||
Minimum of Months | 17913902.38 | 3014.06 | 5.28 | |
Maximum of Months | 0.343916E+09 | 6232.49 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34907545.94 | 2315.59 | 22-JAN-16:10 | 20.10 |
February | 23706821.96 | 2274.44 | 05-FEB-12:13 | 20.77 |
March | 11242931.25 | 1987.57 | 12-MAR-15:02 | 24.40 |
April | 10404366.14 | 1781.11 | 16-APR-14:42 | 31.70 |
May | 9217166.44 | 1815.49 | 24-MAY-05:02 | 23.98 |
June | 9676781.27 | 2020.04 | 08-JUN-04:03 | 28.80 |
July | 12394599.07 | 1666.26 | 19-JUL-04:03 | 26.78 |
August | 12265437.30 | 2107.09 | 01-AUG-04:02 | 28.30 |
September | 11749302.39 | 2193.19 | 22-SEP-04:02 | 27.80 |
October | 13270543.06 | 2067.25 | 30-OCT-04:02 | 26.28 |
November | 11632959.91 | 1849.14 | 30-NOV-06:03 | 25.60 |
December | 30863032.00 | 2207.13 | 31-DEC-12:10 | 23.80 |
Annual Sum or Average | 0.191331E+09 | |||
Minimum of Months | 9217166.44 | 1666.26 | 20.10 | |
Maximum of Months | 34907545.94 | 2315.59 | 31.70 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28716023.37 | 2292.50 | 09-JAN-06:13 | 11.87 |
February | 24604464.16 | 2226.56 | 05-FEB-12:13 | 20.77 |
March | 17604774.68 | 1685.13 | 15-MAR-05:13 | 12.03 |
April | 15853655.88 | 3043.26 | 12-APR-04:03 | 24.40 |
May | 20357119.62 | 3279.72 | 26-MAY-04:03 | 23.90 |
June | 18983986.68 | 3209.66 | 27-JUN-04:02 | 26.60 |
July | 22331250.96 | 3247.89 | 11-JUL-04:02 | 25.18 |
August | 24199701.00 | 3623.69 | 15-AUG-04:02 | 27.80 |
September | 23494051.35 | 3686.73 | 22-SEP-04:02 | 27.80 |
October | 27040337.49 | 3647.39 | 04-OCT-04:02 | 26.10 |
November | 25714283.84 | 3597.67 | 20-NOV-05:02 | 24.40 |
December | 27099164.94 | 2330.39 | 27-DEC-06:13 | 8.90 |
Annual Sum or Average | 0.275999E+09 | |||
Minimum of Months | 15853655.88 | 1685.13 | 8.90 | |
Maximum of Months | 28716023.37 | 3686.73 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 810780.72 | 5405.20 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 810780.72 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 810780.72 | 5405.20 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9707385.35 | 6541.22 | 27-JAN-07:03 | 12.38 |
February | 15593144.72 | 6114.35 | 04-FEB-06:12 | 5.40 |
March | 4827058.55 | 6326.21 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 758593.54 | 4556.50 | 27-NOV-07:02 | 10.37 |
December | 9602077.26 | 6317.95 | 15-DEC-07:01 | 7.88 |
Annual Sum or Average | 40488259.42 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 15593144.72 | 6541.22 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3591839.94 | 4182.99 | 23-JAN-07:03 | 13.58 |
February | 4246646.74 | 3894.27 | 04-FEB-06:12 | 5.40 |
March | 2034343.47 | 4315.29 | 16-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 210401.35 | 1753.34 | 27-NOV-07:02 | 10.37 |
December | 5367618.38 | 4256.11 | 15-DEC-07:03 | 7.88 |
Annual Sum or Average | 15450849.88 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 5367618.38 | 4315.29 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3711374.06 | 6209.85 | 25-JAN-07:02 | 9.50 |
February | 7459113.82 | 6272.50 | 04-FEB-06:12 | 5.40 |
March | 3337315.87 | 6236.32 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 5945404.02 | 6562.76 | 27-DEC-07:02 | 8.98 |
Annual Sum or Average | 20453207.77 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 7459113.82 | 6562.76 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5015785.02 | 3500.36 | 26-JAN-07:02 | 10.68 |
February | 9680596.09 | 4012.05 | 04-FEB-06:12 | 5.40 |
March | 2543152.28 | 4233.91 | 16-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 336393.68 | 1414.41 | 13-NOV-07:02 | 12.30 |
December | 5695089.21 | 4151.25 | 15-DEC-07:03 | 7.88 |
Annual Sum or Average | 23271016.28 | |||
Minimum of Months | 0.00 | 0.00 | 5.40 | |
Maximum of Months | 9680596.09 | 4233.91 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126117E+09 | 4143.53 | 11-JAN-07:10 | 14.60 |
February | 42310974.07 | 4002.17 | 22-FEB-07:50 | 12.62 |
March | 96564718.17 | 4335.49 | 16-MAR-07:00 | 6.70 |
April | 5212128.37 | 4011.40 | 19-APR-06:06 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 25271705.93 | 4041.11 | 13-NOV-07:40 | 12.60 |
December | 80816784.31 | 4072.48 | 13-DEC-08:00 | 13.90 |
Annual Sum or Average | 0.376293E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 0.126117E+09 | 4335.49 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66825.73 | 668.26 | 25-JAN-07:02 | 9.50 |
February | 908437.13 | 4581.60 | 04-FEB-07:03 | 5.28 |
March | 37211.61 | 434.14 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 1012474.47 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 908437.13 | 4581.60 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 481818.87 | 3212.13 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 481818.87 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 481818.87 | 3212.13 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 637716.44 | 4251.44 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 637716.44 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 637716.44 | 4251.44 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 634112.81 | 3162.69 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 634112.81 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 634112.81 | 3162.69 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599292E+09 | 881.92 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.519850E+09 | 728.72 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.593903E+09 | 785.48 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.519971E+09 | 735.03 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.548316E+09 | 571.08 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.543803E+09 | 875.87 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.507353E+09 | 565.66 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.574443E+09 | 734.40 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.529176E+09 | 1040.56 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.566239E+09 | 887.88 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.580673E+09 | 854.46 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.588056E+09 | 976.02 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.667107E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.507353E+09 | 565.66 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599292E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372472E+09 | 563.91 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.326498E+09 | 476.30 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.372584E+09 | 361.69 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329610E+09 | 367.55 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349557E+09 | 353.71 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.347678E+09 | 542.08 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323559E+09 | 349.97 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364043E+09 | 368.42 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335050E+09 | 658.76 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354064E+09 | 535.30 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.364315E+09 | 553.02 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367769E+09 | 618.30 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.420720E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323559E+09 | 349.97 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.372584E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.570395E+09 | 846.76 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.506623E+09 | 579.85 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587503E+09 | 735.65 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.521260E+09 | 743.24 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.554224E+09 | 578.49 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.554285E+09 | 894.57 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.513194E+09 | 576.81 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577262E+09 | 755.05 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527543E+09 | 1040.56 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.554492E+09 | 866.37 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.561105E+09 | 790.19 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.562975E+09 | 971.86 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.659086E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.506623E+09 | 576.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.587503E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368116E+09 | 522.62 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323599E+09 | 465.07 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375459E+09 | 514.66 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329208E+09 | 501.00 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350190E+09 | 433.39 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.349059E+09 | 576.94 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.324387E+09 | 428.29 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366277E+09 | 503.61 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335686E+09 | 658.71 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356726E+09 | 568.29 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.359663E+09 | 519.54 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.360781E+09 | 613.32 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419915E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323599E+09 | 428.29 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.375459E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596503E+09 | 875.80 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.518263E+09 | 716.24 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.592380E+09 | 773.50 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.519338E+09 | 722.96 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.548061E+09 | 567.67 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.543128E+09 | 869.58 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.506650E+09 | 561.97 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.573635E+09 | 722.27 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.528110E+09 | 1040.56 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.564628E+09 | 881.96 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.578576E+09 | 847.09 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.585549E+09 | 973.56 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.665482E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.506650E+09 | 561.97 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.596503E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.371398E+09 | 560.97 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325860E+09 | 470.77 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.372090E+09 | 359.55 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329246E+09 | 365.75 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349105E+09 | 352.06 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.347118E+09 | 538.53 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323146E+09 | 348.22 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.363617E+09 | 366.66 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334579E+09 | 658.76 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.353463E+09 | 531.04 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.363569E+09 | 549.69 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.366825E+09 | 617.06 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.420001E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323146E+09 | 348.22 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.372090E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569873E+09 | 838.88 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.506032E+09 | 576.82 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.586517E+09 | 720.01 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.520594E+09 | 731.57 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.553307E+09 | 575.52 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.553025E+09 | 888.95 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.512445E+09 | 573.78 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.576447E+09 | 743.91 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526625E+09 | 1040.56 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.553844E+09 | 859.38 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.560542E+09 | 779.54 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.562237E+09 | 969.19 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658149E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.506032E+09 | 573.78 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.586517E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.367108E+09 | 517.80 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323056E+09 | 458.50 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374642E+09 | 510.22 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328623E+09 | 496.18 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349654E+09 | 426.52 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.348348E+09 | 574.45 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323843E+09 | 421.25 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365593E+09 | 498.87 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335011E+09 | 658.71 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.355937E+09 | 565.50 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.358933E+09 | 515.26 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.359980E+09 | 611.85 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419073E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323056E+09 | 421.25 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374642E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599290E+09 | 881.91 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.519848E+09 | 728.72 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.593903E+09 | 785.48 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.519971E+09 | 735.00 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.548315E+09 | 571.07 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.543802E+09 | 875.86 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.507352E+09 | 565.65 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.574443E+09 | 734.37 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.529175E+09 | 1040.56 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.566237E+09 | 887.87 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.580671E+09 | 854.44 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.588054E+09 | 976.01 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.667106E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.507352E+09 | 565.65 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599290E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372441E+09 | 563.90 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.326497E+09 | 476.29 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.372583E+09 | 361.69 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329610E+09 | 367.55 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349556E+09 | 353.71 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.347677E+09 | 542.07 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.323559E+09 | 349.97 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364043E+09 | 368.41 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335049E+09 | 658.76 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354064E+09 | 535.29 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.364314E+09 | 553.01 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.367769E+09 | 618.30 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.420716E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323559E+09 | 349.97 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.372583E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.570395E+09 | 846.74 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.506622E+09 | 579.84 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.587502E+09 | 735.65 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.521260E+09 | 743.22 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.554223E+09 | 578.48 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.554284E+09 | 894.56 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.513193E+09 | 576.81 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577261E+09 | 755.02 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.527542E+09 | 1040.56 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.554492E+09 | 866.36 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.561104E+09 | 790.17 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.562975E+09 | 971.85 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.659085E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.506622E+09 | 576.81 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.587502E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368115E+09 | 522.61 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323598E+09 | 465.07 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375459E+09 | 514.65 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.329208E+09 | 500.99 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350190E+09 | 433.37 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.349058E+09 | 576.93 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.324386E+09 | 428.27 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366276E+09 | 503.60 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.335686E+09 | 658.71 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.356726E+09 | 568.28 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.359653E+09 | 519.52 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.360780E+09 | 613.31 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419913E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323598E+09 | 428.27 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.375459E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.599292E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4009477.35 | 83000410.47 |
February | 0.901968E+09 | 0.519850E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6871964.02 | 0.111199E+09 |
March | 0.107774E+10 | 0.593903E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7541706.20 | 0.102304E+09 |
April | 0.956342E+09 | 0.519971E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17165394.44 | 45347460.34 |
May | 0.103597E+10 | 0.548316E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41553995.67 | 18692709.24 |
June | 0.103308E+10 | 0.543803E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49680680.04 | 5893102.18 |
July | 0.959235E+09 | 0.507353E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46500461.25 | 5478778.53 |
August | 0.107774E+10 | 0.574443E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54611470.32 | 3139524.08 |
September | 0.956342E+09 | 0.529176E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51471099.45 | 5552145.18 |
October | 0.994195E+09 | 0.566239E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33552630.91 | 11713110.00 |
November | 0.984487E+09 | 0.580673E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15338634.12 | 69285668.08 |
December | 0.959235E+09 | 0.588056E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5588699.21 | 83554757.92 |
Annual Sum or Average | 0.119305E+11 | 0.667107E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333886E+09 | 0.545160E+09 |
Minimum of Months | 0.901968E+09 | 0.507353E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4009477.35 | 3139524.08 |
Maximum of Months | 0.107774E+10 | 0.599292E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54611470.32 | 0.111199E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.372472E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1745138.67 | 60057598.45 |
February | 0.571020E+09 | 0.326498E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3942382.71 | 79310851.49 |
March | 0.682301E+09 | 0.372584E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4669717.87 | 72422432.32 |
April | 0.605444E+09 | 0.329610E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9846556.16 | 32632302.53 |
May | 0.655854E+09 | 0.349557E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26829788.83 | 13188151.34 |
June | 0.654023E+09 | 0.347678E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32573405.08 | 4125987.98 |
July | 0.607275E+09 | 0.323559E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30080840.00 | 3868531.10 |
August | 0.682301E+09 | 0.364043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35309241.74 | 2194309.04 |
September | 0.605444E+09 | 0.335050E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32867079.70 | 3938660.24 |
October | 0.629407E+09 | 0.354064E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20717605.54 | 8352594.06 |
November | 0.623262E+09 | 0.364315E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9297344.68 | 50005382.50 |
December | 0.607275E+09 | 0.367769E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3012915.84 | 58536201.11 |
Annual Sum or Average | 0.755301E+10 | 0.420720E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210892E+09 | 0.388633E+09 |
Minimum of Months | 0.571020E+09 | 0.323559E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1745138.67 | 2194309.04 |
Maximum of Months | 0.682301E+09 | 0.372584E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35309241.74 | 79310851.49 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.570395E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2407241.31 | 97842068.55 |
February | 0.901968E+09 | 0.506623E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5327417.01 | 0.127508E+09 |
March | 0.107774E+10 | 0.587503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6786575.74 | 0.111071E+09 |
April | 0.956342E+09 | 0.521260E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15257221.38 | 47519284.00 |
May | 0.103597E+10 | 0.554224E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41906885.75 | 18625102.24 |
June | 0.103308E+10 | 0.554285E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50504113.63 | 5709939.51 |
July | 0.959235E+09 | 0.513194E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47183558.38 | 5311602.08 |
August | 0.107774E+10 | 0.577262E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54147234.83 | 3179598.55 |
September | 0.956342E+09 | 0.527543E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49090370.37 | 5924114.79 |
October | 0.994195E+09 | 0.554492E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29321092.70 | 13942685.68 |
November | 0.984487E+09 | 0.561105E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12580041.04 | 82220440.73 |
December | 0.959235E+09 | 0.562975E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3517593.83 | 96366468.94 |
Annual Sum or Average | 0.119305E+11 | 0.659086E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318029E+09 | 0.615220E+09 |
Minimum of Months | 0.901968E+09 | 0.506623E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2407241.31 | 3179598.55 |
Maximum of Months | 0.107774E+10 | 0.587503E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54147234.83 | 0.127508E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.368116E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2258780.43 | 58907933.47 |
February | 0.570983E+09 | 0.323599E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3781617.94 | 79894776.56 |
March | 0.682256E+09 | 0.375459E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4720712.79 | 74681965.80 |
April | 0.605404E+09 | 0.329208E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10275641.81 | 35490342.38 |
May | 0.655811E+09 | 0.350190E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26344397.19 | 14737449.98 |
June | 0.653980E+09 | 0.349059E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31808144.45 | 4263069.88 |
July | 0.607235E+09 | 0.324387E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29881869.91 | 4170488.65 |
August | 0.682256E+09 | 0.366277E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34399772.58 | 2363382.80 |
September | 0.605404E+09 | 0.335686E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32121058.13 | 4148979.55 |
October | 0.629366E+09 | 0.356726E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20394257.45 | 9165388.22 |
November | 0.623221E+09 | 0.359663E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9271806.67 | 49211110.96 |
December | 0.607235E+09 | 0.360781E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3075688.81 | 59781580.14 |
Annual Sum or Average | 0.755252E+10 | 0.419915E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208334E+09 | 0.396816E+09 |
Minimum of Months | 0.570983E+09 | 0.323599E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2258780.43 | 2363382.80 |
Maximum of Months | 0.682256E+09 | 0.375459E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34399772.58 | 79894776.56 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.596503E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2179707.13 | 50922730.43 |
February | 0.901968E+09 | 0.518263E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3987126.76 | 67328819.92 |
March | 0.107774E+10 | 0.592380E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4541738.34 | 57643177.23 |
April | 0.956342E+09 | 0.519338E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10493627.01 | 24540126.12 |
May | 0.103597E+10 | 0.548061E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23694101.71 | 9070530.29 |
June | 0.103308E+10 | 0.543128E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28167191.94 | 2456706.17 |
July | 0.959235E+09 | 0.506650E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26285600.61 | 2628194.61 |
August | 0.107774E+10 | 0.573635E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30192236.54 | 1668974.84 |
September | 0.956342E+09 | 0.528110E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28600743.10 | 3101414.75 |
October | 0.994195E+09 | 0.564628E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18943896.69 | 6762382.71 |
November | 0.984487E+09 | 0.578576E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8599883.79 | 42588314.49 |
December | 0.959235E+09 | 0.585549E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3105469.76 | 51688944.45 |
Annual Sum or Average | 0.119305E+11 | 0.665482E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188791E+09 | 0.320400E+09 |
Minimum of Months | 0.901968E+09 | 0.506650E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2179707.13 | 1668974.84 |
Maximum of Months | 0.107774E+10 | 0.596503E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30192236.54 | 67328819.92 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.371398E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984716.95 | 36877445.90 |
February | 0.571020E+09 | 0.325860E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2290619.44 | 48557627.84 |
March | 0.682301E+09 | 0.372090E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2636179.27 | 42165178.26 |
April | 0.605444E+09 | 0.329246E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5616509.15 | 18632229.86 |
May | 0.655854E+09 | 0.349105E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14731577.29 | 7123624.23 |
June | 0.654023E+09 | 0.347118E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17874098.84 | 1920646.30 |
July | 0.607275E+09 | 0.323146E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16429849.48 | 2113056.56 |
August | 0.682301E+09 | 0.363617E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18938849.11 | 1265895.84 |
September | 0.605444E+09 | 0.334579E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17676130.74 | 2400328.47 |
October | 0.629407E+09 | 0.353463E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11265338.56 | 5296251.65 |
November | 0.623262E+09 | 0.363569E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5120012.41 | 30902343.81 |
December | 0.607275E+09 | 0.366825E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1700819.37 | 36260179.54 |
Annual Sum or Average | 0.755301E+10 | 0.420001E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115265E+09 | 0.233515E+09 |
Minimum of Months | 0.571020E+09 | 0.323146E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 984716.95 | 1265895.84 |
Maximum of Months | 0.682301E+09 | 0.372090E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18938849.11 | 48557627.84 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569873E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98371030.16 | 0.155037E+10 |
February | 0.901968E+09 | 0.506032E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218153E+09 | 0.719525E+09 |
March | 0.107774E+10 | 0.586517E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272497E+09 | 0.100718E+10 |
April | 0.956342E+09 | 0.520594E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652355E+09 | 0.250977E+09 |
May | 0.103597E+10 | 0.553307E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142224E+10 | 41287202.39 |
June | 0.103308E+10 | 0.553025E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162798E+10 | 6596847.34 |
July | 0.959235E+09 | 0.512445E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181489E+10 | 9425709.32 |
August | 0.107774E+10 | 0.576447E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194210E+10 | 18373825.20 |
September | 0.956342E+09 | 0.526625E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140287E+10 | 22919224.07 |
October | 0.994195E+09 | 0.553844E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109995E+10 | 70689247.30 |
November | 0.984487E+09 | 0.560542E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597441E+09 | 0.420686E+09 |
December | 0.959235E+09 | 0.562237E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123538E+09 | 0.138996E+10 |
Annual Sum or Average | 0.119305E+11 | 0.658149E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112724E+11 | 0.550799E+10 |
Minimum of Months | 0.901968E+09 | 0.506032E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98371030.16 | 6596847.34 |
Maximum of Months | 0.107774E+10 | 0.586517E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194210E+10 | 0.155037E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.367108E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164969.21 | 36359784.90 |
February | 0.570983E+09 | 0.323056E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2068132.68 | 49136967.99 |
March | 0.682256E+09 | 0.374642E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2641260.69 | 43943628.41 |
April | 0.605404E+09 | 0.328623E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5681462.29 | 20286897.49 |
May | 0.655811E+09 | 0.349654E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14411900.25 | 7996737.20 |
June | 0.653980E+09 | 0.348348E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17535991.58 | 1957489.69 |
July | 0.607235E+09 | 0.323843E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16255989.28 | 2224317.30 |
August | 0.682256E+09 | 0.365593E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18403594.80 | 1356640.83 |
September | 0.605404E+09 | 0.335011E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17257222.75 | 2490396.50 |
October | 0.629366E+09 | 0.355937E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11031222.54 | 5728691.39 |
November | 0.623221E+09 | 0.358933E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5047988.51 | 30602591.38 |
December | 0.607235E+09 | 0.359980E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1654574.37 | 37294538.09 |
Annual Sum or Average | 0.755252E+10 | 0.419073E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113154E+09 | 0.239379E+09 |
Minimum of Months | 0.570983E+09 | 0.323056E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164969.21 | 1356640.83 |
Maximum of Months | 0.682256E+09 | 0.374642E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18403594.80 | 49136967.99 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.599290E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3348138.31 | 76481354.59 |
February | 0.901968E+09 | 0.519848E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6081417.02 | 0.102446E+09 |
March | 0.107774E+10 | 0.593903E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6698319.32 | 92067852.94 |
April | 0.956342E+09 | 0.519971E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15301984.77 | 40457814.64 |
May | 0.103597E+10 | 0.548315E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35618141.34 | 15930459.83 |
June | 0.103308E+10 | 0.543802E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42393992.72 | 4773510.13 |
July | 0.959235E+09 | 0.507352E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39909596.73 | 4569472.36 |
August | 0.107774E+10 | 0.574443E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46631904.39 | 2621350.38 |
September | 0.956342E+09 | 0.529175E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44028924.54 | 4837018.79 |
October | 0.994195E+09 | 0.566237E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28630660.17 | 10918175.00 |
November | 0.984487E+09 | 0.580671E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13185020.54 | 63587453.41 |
December | 0.959235E+09 | 0.588054E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4868851.15 | 76646602.74 |
Annual Sum or Average | 0.119305E+11 | 0.667106E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286697E+09 | 0.495337E+09 |
Minimum of Months | 0.901968E+09 | 0.507352E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3348138.31 | 2621350.38 |
Maximum of Months | 0.107774E+10 | 0.599290E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46631904.39 | 0.102446E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.372441E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1343540.92 | 54720814.92 |
February | 0.421807E+09 | 0.326497E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3147340.83 | 72549087.11 |
March | 0.502994E+09 | 0.372583E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3736134.31 | 64793282.68 |
April | 0.447140E+09 | 0.329610E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8173137.94 | 29004482.42 |
May | 0.484071E+09 | 0.349556E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22281074.57 | 11352993.72 |
June | 0.482240E+09 | 0.347677E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27130141.89 | 3390454.05 |
July | 0.448971E+09 | 0.323559E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25244862.82 | 3279531.40 |
August | 0.502994E+09 | 0.364043E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29469231.96 | 1864105.68 |
September | 0.447140E+09 | 0.335049E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27474729.73 | 3448063.31 |
October | 0.465148E+09 | 0.354064E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17125039.57 | 7784556.49 |
November | 0.460569E+09 | 0.364314E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7637654.09 | 45459653.12 |
December | 0.448971E+09 | 0.367769E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2483168.33 | 53506477.15 |
Annual Sum or Average | 0.557719E+10 | 0.420716E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175246E+09 | 0.351154E+09 |
Minimum of Months | 0.421807E+09 | 0.323559E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1343540.92 | 1864105.68 |
Maximum of Months | 0.502994E+09 | 0.372583E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29469231.96 | 72549087.11 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.570395E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1902945.25 | 88201077.42 |
February | 0.901968E+09 | 0.506622E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4338255.80 | 0.115472E+09 |
March | 0.107774E+10 | 0.587502E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5783638.62 | 99166315.08 |
April | 0.956342E+09 | 0.521260E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13219102.01 | 42170781.27 |
May | 0.103597E+10 | 0.554223E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35850202.31 | 15854999.47 |
June | 0.103308E+10 | 0.554284E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43138806.36 | 4621660.16 |
July | 0.959235E+09 | 0.513193E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40504844.79 | 4428037.78 |
August | 0.107774E+10 | 0.577261E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46081226.44 | 2660735.80 |
September | 0.956342E+09 | 0.527542E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41567055.80 | 5177940.29 |
October | 0.994195E+09 | 0.554492E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24369316.16 | 12865807.07 |
November | 0.984487E+09 | 0.561104E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10312870.02 | 74119762.19 |
December | 0.959235E+09 | 0.562975E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2845835.48 | 86778636.49 |
Annual Sum or Average | 0.119305E+11 | 0.659085E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269914E+09 | 0.551518E+09 |
Minimum of Months | 0.901968E+09 | 0.506622E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1902945.25 | 2660735.80 |
Maximum of Months | 0.107774E+10 | 0.587502E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46081226.44 | 0.115472E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.368115E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1831877.43 | 53747601.98 |
February | 0.570983E+09 | 0.323598E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3187870.84 | 72875621.34 |
March | 0.682256E+09 | 0.375459E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4056242.04 | 66755042.60 |
April | 0.605404E+09 | 0.329208E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8759607.71 | 31463098.28 |
May | 0.655811E+09 | 0.350190E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22283311.73 | 12554455.94 |
June | 0.653980E+09 | 0.349058E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26901459.11 | 3481522.82 |
July | 0.607235E+09 | 0.324386E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25285593.26 | 3507042.90 |
August | 0.682256E+09 | 0.366276E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29080388.53 | 1972284.06 |
September | 0.605404E+09 | 0.335686E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27152430.14 | 3614450.75 |
October | 0.629366E+09 | 0.356726E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17158806.33 | 8430161.11 |
November | 0.623221E+09 | 0.359653E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7879983.44 | 44799437.41 |
December | 0.607235E+09 | 0.360780E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2597187.90 | 54263888.82 |
Annual Sum or Average | 0.755252E+10 | 0.419913E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176175E+09 | 0.357465E+09 |
Minimum of Months | 0.570983E+09 | 0.323598E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1831877.43 | 1972284.06 |
Maximum of Months | 0.682256E+09 | 0.375459E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29080388.53 | 72875621.34 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1884778.41 | 0.117193E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3607379.04 | 0.155137E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4778501.89 | 0.135778E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13153185.54 | 57708704.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37584500.09 | 20018521.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50089528.51 | 5201367.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46446362.32 | 5258705.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54098897.38 | 3422479.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49871800.76 | 6563891.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28271842.04 | 14881932.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10975736.75 | 95268089.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3468445.02 | 0.116170E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304231E+09 | 0.732601E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1884778.41 | 3422479.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54098897.38 | 0.155137E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3250823.87 | 0.139759E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5326854.95 | 0.184938E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6725378.17 | 0.165156E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17632228.82 | 70386514.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48775692.02 | 24261162.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64540796.62 | 6737669.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59963301.22 | 6786738.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70711847.15 | 4212264.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65155232.15 | 7928549.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37874948.05 | 17683073.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15577954.80 | 0.113552E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5394679.55 | 0.137353E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400930E+09 | 0.878753E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3250823.87 | 4212264.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70711847.15 | 0.184938E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1439385.57 | 0.132882E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1773226.38 | 0.173126E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2097254.93 | 0.158199E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9057570.69 | 70327276.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41167402.06 | 22035232.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60491878.33 | 7668451.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51666485.04 | 7059812.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66919837.34 | 4632050.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57953482.76 | 6106614.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33081073.54 | 12349663.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13893680.01 | 0.107416E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2250921.41 | 0.131643E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341792E+09 | 0.833446E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1439385.57 | 4632050.40 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66919837.34 | 0.173126E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 881.92 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.04 | 29-JAN-12:00 | 237.78 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 728.72 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 | 20-FEB-15:40 | 399.64 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 785.48 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 | 05-MAR-14:00 | 404.78 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 735.03 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.98 | 15-APR-17:02 | 133.55 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 571.08 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.39 | 29-MAY-15:55 | 90.87 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 875.87 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.92 | 16-JUN-21:03 | 101.02 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 565.66 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.12 | 30-JUL-15:38 | 73.72 | 02-JUL-15:40 |
August | 1306.65 | 01-AUG-09:09 | 734.40 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.78 | 13-AUG-13:00 | 117.54 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.22 | 17-SEP-16:50 | 47.02 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 887.88 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.72 | 29-OCT-11:42 | 82.74 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 854.46 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.51 | 22-NOV-22:03 | 396.68 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 976.02 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.79 | 10-DEC-14:52 | 368.24 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 565.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.62 | 47.02 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 223.39 | 404.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.91 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 | 29-JAN-12:00 | 169.94 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 476.30 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 02-FEB-14:00 | 266.36 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 361.69 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 | 05-MAR-14:20 | 272.88 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 367.55 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.71 | 15-APR-17:02 | 89.80 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 353.71 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.61 | 29-MAY-15:55 | 66.69 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 542.08 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.83 | 25-JUN-13:48 | 67.34 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 349.97 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.33 | 30-JUL-15:38 | 55.27 | 02-JUL-15:40 |
August | 827.22 | 01-AUG-09:09 | 368.42 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.64 | 13-AUG-13:00 | 79.47 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 658.76 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.94 | 17-SEP-14:08 | 34.17 | 03-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 535.30 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 29-OCT-14:06 | 55.87 | 01-OCT-07:00 |
November | 827.22 | 01-NOV-09:09 | 553.02 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.20 | 22-NOV-22:03 | 313.98 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 618.30 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 10-DEC-14:52 | 245.87 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 349.97 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 | 34.17 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 155.61 | 313.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 846.76 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 07-JAN-13:00 | 248.69 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 579.85 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.27 | 02-FEB-14:00 | 409.53 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 735.65 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 | 05-MAR-14:20 | 417.99 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 743.24 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.31 | 15-APR-17:02 | 135.58 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 578.49 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.34 | 29-MAY-15:55 | 90.84 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 894.57 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.19 | 17-JUN-18:00 | 101.27 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 576.81 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 | 30-JUL-15:38 | 73.03 | 02-JUL-15:40 |
August | 1306.65 | 01-AUG-09:09 | 755.05 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.25 | 13-AUG-13:00 | 118.36 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.42 | 17-SEP-16:46 | 58.22 | 03-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 866.37 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 | 29-OCT-14:06 | 87.93 | 16-OCT-04:55 |
November | 1306.65 | 01-NOV-09:09 | 790.19 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.01 | 22-NOV-22:03 | 449.23 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 971.86 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.91 | 10-DEC-14:46 | 380.01 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 576.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 58.22 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 225.34 | 449.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 522.62 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 29-JAN-12:00 | 161.33 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 465.07 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 02-FEB-14:00 | 267.96 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 514.66 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.05 | 05-MAR-14:20 | 277.86 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 501.00 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 | 15-APR-17:07 | 96.56 | 30-APR-18:15 |
May | 827.17 | 01-MAY-09:09 | 433.39 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.72 | 29-MAY-15:57 | 73.99 | 07-MAY-18:55 |
June | 827.17 | 01-JUN-09:09 | 576.94 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.72 | 25-JUN-13:45 | 70.56 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 428.29 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.72 | 30-JUL-15:35 | 52.75 | 02-JUL-15:40 |
August | 827.17 | 01-AUG-09:09 | 503.61 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.51 | 20-AUG-12:18 | 82.38 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 658.71 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.10 | 17-SEP-14:05 | 40.06 | 03-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 568.29 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 | 29-OCT-11:42 | 57.59 | 16-OCT-04:55 |
November | 827.17 | 01-NOV-09:09 | 519.54 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.06 | 22-NOV-22:03 | 263.94 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 613.32 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 10-DEC-14:44 | 246.66 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 428.29 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 | 40.06 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 142.72 | 277.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 875.80 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.24 | 15-JAN-14:00 | 141.61 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 716.24 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 20-FEB-15:10 | 248.98 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 773.50 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.38 | 05-MAR-13:50 | 239.22 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 722.96 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.69 | 15-APR-17:02 | 76.05 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 567.67 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.97 | 29-MAY-16:10 | 49.72 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 869.58 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 17-JUN-17:30 | 46.97 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 561.97 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.54 | 30-JUL-15:40 | 37.34 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 722.27 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.28 | 13-AUG-12:40 | 61.65 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.66 | 17-SEP-14:00 | 26.58 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 881.96 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.93 | 29-OCT-14:00 | 48.39 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 847.09 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 | 22-NOV-22:03 | 240.95 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 973.56 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.42 | 10-DEC-14:30 | 230.17 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 561.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 | 26.58 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 119.97 | 248.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 560.97 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 29-JAN-12:00 | 97.33 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 470.77 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 19-FEB-15:40 | 167.34 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 359.55 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 05-MAR-14:20 | 164.25 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 365.75 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.74 | 15-APR-17:02 | 52.89 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 352.06 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 29-MAY-16:10 | 34.58 | 07-MAY-18:55 |
June | 827.22 | 01-JUN-09:09 | 538.53 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.44 | 17-JUN-17:30 | 32.41 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 348.22 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 30-JUL-15:38 | 29.07 | 02-JUL-16:00 |
August | 827.22 | 01-AUG-09:09 | 366.66 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.70 | 13-AUG-13:00 | 43.47 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 658.76 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 | 17-SEP-13:58 | 19.45 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 531.04 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.34 | 29-OCT-13:57 | 34.44 | 16-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 549.69 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 | 22-NOV-22:03 | 183.90 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 617.06 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.51 | 10-DEC-14:30 | 155.38 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 348.22 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 19.45 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 81.12 | 183.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 838.88 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.38 | 23-JAN-17:10 | 14931.49 | 25-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 576.82 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4021.27 | 02-FEB-13:00 | 13690.85 | 03-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 720.01 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5998.80 | 13-MAR-16:03 | 17571.66 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 731.57 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8553.81 | 17-APR-16:03 | 7881.80 | 19-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 575.52 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9809.76 | 22-MAY-16:02 | 3163.31 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 888.95 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8074.84 | 09-JUN-16:03 | 875.59 | 13-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 573.78 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12213.34 | 27-JUL-16:02 | 1511.97 | 14-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 743.91 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9963.80 | 08-AUG-11:02 | 2252.69 | 28-AUG-12:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8643.60 | 08-SEP-16:03 | 2093.47 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 859.38 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7348.00 | 03-OCT-11:02 | 2768.54 | 20-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 779.54 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4521.98 | 03-NOV-16:05 | 14637.24 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 969.19 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3302.75 | 08-DEC-12:05 | 17041.73 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.78 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2842.38 | 875.59 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12213.34 | 17571.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 517.80 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 29-JAN-12:00 | 98.83 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 458.50 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 02-FEB-14:00 | 168.36 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 510.22 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 | 05-MAR-13:50 | 167.66 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 496.18 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.82 | 15-APR-17:07 | 54.50 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 426.52 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 | 29-MAY-16:05 | 36.03 | 07-MAY-18:55 |
June | 827.17 | 01-JUN-09:09 | 574.45 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.78 | 25-JUN-13:55 | 34.20 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 421.25 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 30-JUL-15:38 | 27.60 | 02-JUL-16:00 |
August | 827.17 | 01-AUG-09:09 | 498.87 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.37 | 13-AUG-12:40 | 45.59 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 658.71 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.95 | 17-SEP-13:54 | 21.29 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 565.50 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.11 | 29-OCT-12:00 | 36.63 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 515.26 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.81 | 22-NOV-22:03 | 162.62 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 611.85 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | 10-DEC-14:02 | 156.63 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 421.25 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 21.29 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 | 168.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 881.91 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.15 | 15-JAN-14:00 | 213.84 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 728.72 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 20-FEB-15:10 | 369.89 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 785.48 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 | 26-MAR-14:53 | 364.84 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 735.00 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 | 15-APR-17:02 | 118.25 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 571.07 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.04 | 29-MAY-15:55 | 79.00 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 875.86 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.68 | 17-JUN-18:00 | 78.08 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 565.65 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.71 | 30-JUL-15:40 | 61.53 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 734.37 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.82 | 13-AUG-12:40 | 96.65 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.99 | 17-SEP-14:00 | 39.55 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 887.87 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 | 29-OCT-14:00 | 77.71 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 854.44 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.66 | 22-NOV-22:03 | 359.02 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 976.01 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.70 | 10-DEC-14:52 | 340.82 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 565.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 39.55 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 191.04 | 369.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.90 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 29-JAN-12:10 | 153.50 | 08-JAN-10:00 |
February | 805.43 | 01-FEB-08:09 | 476.29 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 19-FEB-15:40 | 246.40 | 04-FEB-05:00 |
March | 805.43 | 01-MAR-08:09 | 361.69 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.76 | 05-MAR-14:00 | 245.40 | 16-MAR-02:00 |
April | 805.43 | 03-APR-07:10 | 367.55 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.40 | 15-APR-17:02 | 79.57 | 18-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 353.71 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.84 | 29-MAY-15:55 | 52.31 | 25-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 542.07 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.20 | 17-JUN-17:30 | 52.21 | 18-JUN-20:00 |
July | 805.43 | 03-JUL-07:10 | 349.97 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.75 | 30-JUL-15:38 | 45.92 | 02-JUL-16:00 |
August | 805.43 | 01-AUG-07:10 | 368.41 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 | 13-AUG-13:00 | 65.73 | 14-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 658.76 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.94 | 17-SEP-13:58 | 27.48 | 19-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 535.29 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 | 29-OCT-13:57 | 52.05 | 16-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 553.01 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 22-NOV-22:03 | 281.08 | 11-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 618.30 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 10-DEC-14:52 | 227.14 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 349.97 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 27.48 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 128.84 | 281.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 846.74 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 07-JAN-13:00 | 222.89 | 08-JAN-10:00 |
February | 1306.65 | 01-FEB-10:09 | 579.84 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.73 | 02-FEB-14:00 | 377.66 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 735.65 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 05-MAR-14:00 | 375.30 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 743.22 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.51 | 15-APR-17:02 | 119.94 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 578.48 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 29-MAY-15:55 | 78.93 | 25-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 894.56 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.12 | 17-JUN-17:30 | 78.24 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 576.81 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.43 | 30-JUL-15:40 | 61.03 | 02-JUL-16:00 |
August | 1306.65 | 01-AUG-09:09 | 755.02 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.70 | 13-AUG-13:00 | 97.53 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 1040.56 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.09 | 17-SEP-16:36 | 42.34 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 866.36 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.78 | 29-OCT-13:57 | 83.22 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 790.17 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.49 | 22-NOV-22:03 | 403.20 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 971.85 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 | 10-DEC-14:46 | 349.42 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 576.81 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 | 42.34 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 191.36 | 403.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 522.61 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.65 | 29-JAN-12:10 | 144.72 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 465.07 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 | 02-FEB-14:00 | 247.49 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 514.65 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.26 | 05-MAR-14:00 | 249.56 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 500.99 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 15-APR-17:07 | 82.61 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 433.37 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.27 | 29-MAY-15:57 | 52.38 | 25-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 576.93 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.13 | 25-JUN-13:48 | 54.91 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 428.27 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 | 30-JUL-15:38 | 43.65 | 02-JUL-16:00 |
August | 827.17 | 01-AUG-09:09 | 503.60 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.60 | 20-AUG-12:20 | 68.33 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 658.71 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.65 | 17-SEP-13:54 | 30.00 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 568.28 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.30 | 29-OCT-12:00 | 54.47 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 519.52 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 22-NOV-22:03 | 238.79 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 613.31 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | 10-DEC-13:43 | 227.47 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 428.27 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 | 30.00 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 119.27 | 249.56 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 29-JAN-12:05 | 309.46 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 02-FEB-14:00 | 550.07 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.91 | 05-MAR-13:53 | 532.12 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.44 | 15-APR-17:02 | 167.72 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.51 | 29-MAY-15:52 | 99.03 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.08 | 25-JUN-14:00 | 88.43 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.46 | 30-JUL-15:50 | 71.79 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.35 | 20-AUG-12:00 | 116.08 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.81 | 17-SEP-14:00 | 44.87 | 04-SEP-23:57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.82 | 29-OCT-12:00 | 106.64 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 22-NOV-22:03 | 503.32 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.41 | 10-DEC-14:52 | 504.38 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 | 44.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.51 | 550.07 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 | 29-JAN-12:20 | 374.39 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 02-FEB-14:00 | 678.87 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 | 05-MAR-14:00 | 667.56 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.70 | 15-APR-17:02 | 212.52 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.22 | 29-MAY-16:00 | 120.49 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.96 | 25-JUN-14:00 | 115.25 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.73 | 30-JUL-15:50 | 93.37 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.01 | 13-AUG-12:43 | 148.30 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.86 | 17-SEP-14:00 | 58.06 | 04-SEP-23:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 | 29-OCT-12:00 | 135.61 | 16-OCT-04:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 04-NOV-17:05 | 624.93 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.88 | 10-DEC-15:00 | 620.82 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 58.06 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.22 | 678.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.14 | 29-JAN-12:00 | 351.90 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 02-FEB-14:00 | 579.36 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 | 13-MAR-17:00 | 590.61 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.47 | 15-APR-17:02 | 185.25 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.11 | 29-MAY-16:00 | 161.76 | 07-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.64 | 16-JUN-21:03 | 145.27 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.91 | 29-JUL-18:00 | 147.91 | 02-JUL-15:40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.71 | 20-AUG-11:55 | 162.78 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.77 | 21-SEP-21:03 | 109.43 | 03-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 29-OCT-08:55 | 121.21 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 22-NOV-22:03 | 589.29 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.36 | 10-DEC-09:53 | 528.59 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.23 | 109.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.11 | 590.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36426.31 | 02-JAN-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38355.29 | 13-FEB-06:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37498.37 | 28-MAR-05:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38480.73 | 12-APR-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42428.06 | 08-MAY-05:03 | 4446.85 | 1482.14 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41184.40 | 06-JUN-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38974.05 | 06-JUL-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38329.57 | 12-AUG-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38548.92 | 28-SEP-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41515.04 | 23-OCT-05:03 | 4446.85 | 1482.14 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38604.11 | 20-NOV-05:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36952.89 | 08-DEC-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36426.31 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42428.06 | 4446.85 | 2742.16 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7850.82 | 02-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.30 | 0.00 |
February | 7788.77 | 22-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 |
March | 8983.55 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 0.00 |
April | 9760.03 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 0.00 |
May | 10858.36 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 | 0.00 |
June | 10421.13 | 11-JUN-13:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.93 | 0.00 |
July | 11215.14 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.94 | 0.00 |
August | 10711.67 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.55 | 0.00 |
September | 10490.30 | 18-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.80 | 0.00 |
October | 10124.56 | 06-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 | 0.00 |
November | 8244.29 | 10-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 0.00 |
December | 7157.83 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7157.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 | |
Maximum of Months | 11215.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3916.31 | 02-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
February | 3403.09 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
March | 3962.96 | 27-MAR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 0.00 |
April | 4150.46 | 17-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 0.00 |
May | 4583.62 | 30-MAY-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 | 0.00 |
June | 4508.53 | 26-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.24 | 0.00 |
July | 5046.24 | 31-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 | 0.00 |
August | 4751.59 | 21-AUG-12:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 | 0.00 |
September | 4892.81 | 11-SEP-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 0.00 |
October | 4755.68 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 4097.12 | 06-NOV-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 0.00 |
December | 3748.11 | 11-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3403.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5046.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.24 | 17.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4557.11 | 02-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
February | 4160.08 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
March | 4412.81 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 0.00 |
April | 4622.88 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
May | 5074.96 | 22-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 | 0.00 |
June | 4843.51 | 26-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 0.00 |
July | 5394.95 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.34 | 0.00 |
August | 5013.76 | 21-AUG-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 0.00 |
September | 5921.16 | 11-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 0.00 |
October | 5276.67 | 30-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 | 0.00 |
November | 4607.12 | 06-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 0.00 |
December | 4097.85 | 11-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4097.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5921.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 | 10.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 27329.45 | 02-JAN-07:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29139.17 | 13-FEB-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26565.70 | 28-MAR-05:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29173.93 | 24-APR-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33012.01 | 08-MAY-05:03 | 4446.85 | 1482.14 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32295.81 | 06-JUN-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30244.56 | 31-JUL-04:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29528.83 | 08-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30666.80 | 12-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33705.22 | 02-OCT-04:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30114.25 | 20-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27222.25 | 09-DEC-06:03 | 1905.79 | 635.20 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26565.70 | 0.00 | 635.20 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33705.22 | 5082.11 | 6581.44 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19082.29 | 02-JAN-15:00 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17555.45 | 21-FEB-15:40 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19157.61 | 27-MAR-15:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31651.40 | 13-APR-05:03 | 2541.06 | 846.94 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35525.94 | 08-MAY-05:03 | 4446.85 | 1482.14 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33681.21 | 19-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33383.63 | 24-JUL-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32658.89 | 28-AUG-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32844.38 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35702.24 | 23-OCT-05:03 | 4446.85 | 1482.14 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32327.61 | 06-NOV-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23270.81 | 11-DEC-07:03 | 5082.11 | 6581.44 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17555.45 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35702.24 | 6198.29 | 6581.44 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5105.41 | 02-JAN-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 0.00 |
February | 5092.24 | 17-FEB-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 0.00 |
March | 5654.97 | 27-MAR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 0.00 |
April | 9151.77 | 16-APR-14:13 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 71.09 | 0.00 |
May | 11477.65 | 29-MAY-16:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 188.51 | 0.00 |
June | 11617.06 | 11-JUN-15:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 0.00 |
July | 11483.26 | 30-JUL-16:12 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 96.77 | 0.00 |
August | 11547.75 | 20-AUG-13:32 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 101.85 | 0.00 |
September | 11464.99 | 04-SEP-13:23 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 57.17 | 0.00 |
October | 9299.75 | 23-OCT-05:01 | 937.43 | 312.45 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
November | 6023.54 | 04-NOV-05:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
December | 4902.52 | 08-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4902.52 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11617.06 | 2613.31 | 992.69 | 4465.21 | 0.00 | 0.00 | 0.00 | 0.00 | 188.51 | 3.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9202.07 | 01-JAN-11:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
February | 5127.53 | 20-FEB-10:13 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.44 |
March | 6885.70 | 26-MAR-10:13 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
April | 11292.36 | 09-APR-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
May | 11323.75 | 07-MAY-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 |
June | 11388.83 | 04-JUN-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.39 | 0.00 |
July | 11457.93 | 23-JUL-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
August | 11319.55 | 06-AUG-10:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 0.00 |
September | 11356.47 | 17-SEP-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 0.00 |
October | 9584.48 | 09-OCT-11:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 0.00 |
November | 5644.47 | 07-NOV-09:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | 0.00 |
December | 4758.17 | 08-DEC-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4758.17 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11457.93 | 827.22 | 314.23 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 108.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13157.60 | 15-JAN-14:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 |
February | 13510.98 | 20-FEB-14:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.30 |
March | 12486.95 | 26-MAR-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 | 0.00 |
April | 12087.11 | 16-APR-14:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.26 | 0.00 |
May | 11711.84 | 29-MAY-15:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 208.49 | 0.00 |
June | 11793.46 | 11-JUN-15:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 0.00 |
July | 11801.74 | 30-JUL-16:12 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | 0.00 |
August | 12200.51 | 20-AUG-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 92.82 | 0.00 |
September | 12376.96 | 17-SEP-11:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 60.75 | 0.00 |
October | 12596.77 | 29-OCT-12:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.53 | 0.00 |
November | 12886.05 | 26-NOV-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.61 |
December | 12665.90 | 03-DEC-14:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11711.84 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13510.98 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 208.49 | 199.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6546.73 | 01-JAN-15:02 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
February | 12675.80 | 20-FEB-14:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
March | 11957.98 | 12-MAR-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
April | 13833.91 | 02-APR-16:22 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 |
May | 13041.95 | 29-MAY-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 109.94 | 0.00 |
June | 13006.79 | 11-JUN-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 | 0.00 |
July | 12945.97 | 09-JUL-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 42.20 | 0.00 |
August | 12704.22 | 20-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 | 0.00 |
September | 13010.45 | 10-SEP-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 | 0.00 |
October | 11945.94 | 09-OCT-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 | 0.00 |
November | 11540.80 | 05-NOV-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.02 | 0.00 |
December | 9266.25 | 10-DEC-15:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6546.73 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13833.91 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 109.94 | 40.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4531.32 | 02-JAN-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
February | 4458.52 | 17-FEB-13:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.73 | 0.00 |
March | 4683.56 | 06-MAR-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 | 0.00 |
April | 5651.14 | 17-APR-15:20 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 0.00 |
May | 7589.72 | 24-MAY-05:02 | 803.52 | 267.81 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 |
June | 7650.37 | 12-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 7641.37 | 17-JUL-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
August | 8003.58 | 02-AUG-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 0.00 |
September | 7640.26 | 04-SEP-13:23 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 0.00 |
October | 7544.28 | 30-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 | 0.00 |
November | 5978.66 | 24-NOV-07:03 | 803.52 | 968.38 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
December | 5594.94 | 11-DEC-07:03 | 1071.35 | 1374.06 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4458.52 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8003.58 | 2613.31 | 1374.06 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 7.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9618.20 | 01-JAN-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 |
February | 4748.88 | 28-FEB-10:00 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
March | 5781.46 | 27-MAR-10:30 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 0.00 |
April | 10347.94 | 16-APR-10:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
May | 9927.79 | 07-MAY-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
June | 9953.94 | 04-JUN-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 0.00 |
July | 10762.63 | 23-JUL-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 | 0.00 |
August | 9959.22 | 06-AUG-10:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.29 | 0.00 |
September | 10347.07 | 10-SEP-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 0.00 |
October | 8653.81 | 29-OCT-12:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 0.00 |
November | 5442.67 | 20-NOV-07:03 | 508.69 | 314.23 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
December | 4940.81 | 11-DEC-07:03 | 678.26 | 866.17 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4748.88 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10762.63 | 805.43 | 866.17 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 6.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10528.86 | 01-JAN-12:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
February | 10425.61 | 26-FEB-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 |
March | 10220.42 | 26-MAR-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
April | 9243.67 | 17-APR-16:10 | 1607.03 | 1102.99 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7108.14 | 0.00 |
May | 9956.75 | 22-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8027.88 | 0.00 |
June | 9197.98 | 09-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6768.36 | 0.00 |
July | 10179.60 | 27-JUL-16:50 | 401.76 | 275.75 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9090.68 | 0.00 |
August | 10054.36 | 23-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7932.96 | 0.00 |
September | 10256.69 | 24-SEP-10:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 0.00 |
October | 11029.56 | 29-OCT-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 0.00 |
November | 10460.78 | 19-NOV-11:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
December | 10503.83 | 25-DEC-15:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9197.98 | 267.84 | 110.30 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11029.56 | 1607.03 | 1102.99 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9090.68 | 23.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4962.23 | 17-JAN-16:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
February | 9323.68 | 19-FEB-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
March | 8078.02 | 26-MAR-14:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 0.00 |
April | 11110.27 | 02-APR-16:22 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 |
May | 9409.60 | 20-MAY-17:05 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 | 0.00 |
June | 10662.98 | 11-JUN-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
July | 10715.20 | 09-JUL-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 | 0.00 |
August | 10497.95 | 20-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 26.62 | 0.00 |
September | 10765.06 | 10-SEP-15:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 31.61 | 0.00 |
October | 10688.30 | 15-OCT-15:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 0.00 |
November | 8946.66 | 05-NOV-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 | 0.00 |
December | 9565.25 | 03-DEC-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4962.23 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11110.27 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 11.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4815.64 | 02-JAN-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.97 | 0.00 |
February | 4697.98 | 17-FEB-13:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
March | 5101.88 | 27-MAR-13:30 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 |
April | 6144.20 | 17-APR-15:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 35.41 | 0.00 |
May | 9752.36 | 29-MAY-16:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | 0.00 |
June | 9187.24 | 11-JUN-15:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 0.00 |
July | 9628.38 | 04-JUL-16:41 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 51.22 | 0.00 |
August | 8786.34 | 20-AUG-13:32 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 90.67 | 0.00 |
September | 8004.03 | 30-SEP-05:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 8090.51 | 10-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
November | 6735.05 | 04-NOV-05:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.00 |
December | 5134.22 | 11-DEC-07:03 | 1071.35 | 1374.55 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4697.98 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9752.36 | 1306.65 | 1374.55 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 162.66 | 6.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10704.58 | 01-JAN-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
February | 6391.26 | 26-FEB-10:03 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 |
March | 7537.47 | 27-MAR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
April | 11383.11 | 16-APR-10:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
May | 10796.99 | 07-MAY-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
June | 10831.36 | 04-JUN-07:42 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 0.00 |
July | 11784.03 | 23-JUL-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 0.00 |
August | 10728.38 | 06-AUG-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 |
September | 11242.75 | 10-SEP-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 | 0.00 |
October | 11140.01 | 09-OCT-08:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 0.00 |
November | 6026.16 | 02-NOV-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
December | 6121.32 | 20-DEC-13:01 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6026.16 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11784.03 | 5638.00 | 2199.59 | 6360.01 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 | 36.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10844.92 | 15-JAN-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.12 |
February | 10850.85 | 19-FEB-13:32 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 |
March | 10603.22 | 26-MAR-14:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 | 0.00 |
April | 10083.03 | 16-APR-14:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 | 0.00 |
May | 9600.14 | 29-MAY-15:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 177.93 | 0.00 |
June | 8361.28 | 26-JUN-04:03 | 0.00 | 178.54 | 2059.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
July | 9874.06 | 30-JUL-16:12 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 87.51 | 0.00 |
August | 10228.35 | 20-AUG-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | 0.00 |
September | 10529.98 | 24-SEP-10:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.25 | 0.00 |
October | 11467.85 | 29-OCT-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 34.51 | 0.00 |
November | 10879.28 | 26-NOV-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.98 |
December | 10865.53 | 03-DEC-13:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8361.28 | 0.00 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11467.85 | 401.76 | 178.54 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 177.93 | 174.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5520.53 | 15-JAN-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 |
February | 10832.07 | 19-FEB-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
March | 11751.09 | 12-MAR-17:42 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 |
April | 11837.84 | 23-APR-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 |
May | 11612.70 | 29-MAY-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 94.26 | 0.00 |
June | 11422.66 | 11-JUN-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 0.00 |
July | 11608.06 | 09-JUL-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 37.19 | 0.00 |
August | 11367.31 | 20-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 0.00 |
September | 11717.84 | 10-SEP-15:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 46.54 | 0.00 |
October | 11772.12 | 09-OCT-16:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 | 0.00 |
November | 10171.79 | 05-NOV-15:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 0.00 |
December | 9681.17 | 03-DEC-16:33 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5520.53 | 0.00 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11837.84 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 94.26 | 56.34 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.124796E+12 | 131731.49 | 02-JAN-13:00 | 0.00 | 0.00 |
February | 0.117273E+12 | 116531.64 | 17-FEB-15:09 | 0.00 | 0.00 |
March | 0.137278E+12 | 130047.72 | 27-MAR-15:30 | 0.00 | 0.00 |
April | 0.136931E+12 | 135719.30 | 14-APR-15:09 | 0.00 | 0.00 |
May | 0.159958E+12 | 143545.44 | 22-MAY-14:09 | 0.00 | 0.00 |
June | 0.166745E+12 | 141316.11 | 26-JUN-10:30 | 0.00 | 0.00 |
July | 0.170388E+12 | 153152.05 | 28-JUL-15:30 | 0.00 | 0.00 |
August | 0.176935E+12 | 150327.65 | 21-AUG-15:00 | 0.00 | 0.00 |
September | 0.163158E+12 | 148046.26 | 18-SEP-15:30 | 0.00 | 0.00 |
October | 0.158872E+12 | 145344.17 | 02-OCT-14:09 | 0.00 | 0.00 |
November | 0.141098E+12 | 132379.25 | 03-NOV-14:09 | 0.00 | 0.00 |
December | 0.125903E+12 | 125546.59 | 08-DEC-15:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.177934E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.117273E+12 | 116531.64 | 0.00 | 0.00 | |
Maximum of Months | 0.176935E+12 | 153152.05 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.196380E+11 | 0.512820E+10 | 0.605851E+11 | 0.225723E+10 | 0.528250E+10 | 12379742.02 | 0.297260E+09 | 0.280320E+11 | 0.00 | 0.00 | 0.00 | 0.356301E+10 | 0.00 |
February | 0.176472E+11 | 0.428778E+10 | 0.548702E+11 | 0.204813E+10 | 0.540334E+10 | 11196021.66 | 0.225040E+09 | 0.295707E+11 | 0.00 | 0.00 | 0.00 | 0.320902E+10 | 0.00 |
March | 0.208002E+11 | 0.434999E+10 | 0.627783E+11 | 0.235483E+10 | 0.665173E+10 | 12675672.10 | 0.222492E+09 | 0.364322E+11 | 0.00 | 0.00 | 0.00 | 0.367556E+10 | 0.00 |
April | 0.184911E+11 | 0.383914E+10 | 0.586172E+11 | 0.219183E+10 | 0.725496E+10 | 11960507.72 | 9786517.59 | 0.433312E+11 | 0.00 | 0.00 | 0.00 | 0.318422E+10 | 0.00 |
May | 0.198688E+11 | 0.362394E+10 | 0.616817E+11 | 0.230575E+10 | 0.924674E+10 | 12527707.06 | 0.00 | 0.599640E+11 | 0.00 | 0.00 | 0.00 | 0.325400E+10 | 0.00 |
June | 0.197824E+11 | 0.337880E+10 | 0.604966E+11 | 0.226802E+10 | 0.973249E+10 | 12231776.97 | 0.00 | 0.679643E+11 | 0.00 | 0.00 | 0.00 | 0.310983E+10 | 0.00 |
July | 0.184593E+11 | 0.355877E+10 | 0.597911E+11 | 0.222874E+10 | 0.103148E+11 | 12256437.81 | 0.00 | 0.731195E+11 | 0.00 | 0.00 | 0.00 | 0.290366E+10 | 0.00 |
August | 0.206589E+11 | 0.384121E+10 | 0.627783E+11 | 0.235469E+10 | 0.105691E+11 | 12675672.10 | 0.00 | 0.734991E+11 | 0.00 | 0.00 | 0.00 | 0.322139E+10 | 0.00 |
September | 0.185724E+11 | 0.402405E+10 | 0.585950E+11 | 0.219062E+10 | 0.970057E+10 | 11960507.72 | 0.00 | 0.670486E+11 | 0.00 | 0.00 | 0.00 | 0.301520E+10 | 0.00 |
October | 0.194036E+11 | 0.455503E+10 | 0.605962E+11 | 0.225779E+10 | 0.928884E+10 | 12379742.02 | 0.00 | 0.595009E+11 | 0.00 | 0.00 | 0.00 | 0.325740E+10 | 0.00 |
November | 0.193478E+11 | 0.482873E+10 | 0.591197E+11 | 0.219988E+10 | 0.727764E+10 | 12059151.09 | 46565023.15 | 0.449209E+11 | 0.00 | 0.00 | 0.00 | 0.334444E+10 | 0.00 |
December | 0.190901E+11 | 0.521691E+10 | 0.597800E+11 | 0.222852E+10 | 0.548933E+10 | 12256437.81 | 0.262163E+09 | 0.303961E+11 | 0.00 | 0.00 | 0.00 | 0.342788E+10 | 0.00 |
Annual Sum or Average | 0.231760E+12 | 0.506325E+11 | 0.719689E+12 | 0.268860E+11 | 0.962120E+11 | 0.146559E+09 | 0.106331E+10 | 0.613780E+12 | 0.00 | 0.00 | 0.00 | 0.391656E+11 | 0.00 |
Minimum of Months | 0.176472E+11 | 0.337880E+10 | 0.548702E+11 | 0.204813E+10 | 0.528250E+10 | 11196021.66 | 0.00 | 0.280320E+11 | 0.00 | 0.00 | 0.00 | 0.290366E+10 | 0.00 |
Maximum of Months | 0.208002E+11 | 0.521691E+10 | 0.627783E+11 | 0.235483E+10 | 0.105691E+11 | 12675672.10 | 0.297260E+09 | 0.734991E+11 | 0.00 | 0.00 | 0.00 | 0.367556E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 23231.87 | 04-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 25-JAN-08:09 | 11900.24 | 02-JAN-15:09 | 6.85 | 30-JAN-17:10 | 18344.20 | 25-JAN-07:10 |
February | 21159.28 | 08-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-08:09 | 11059.38 | 21-FEB-16:19 | 6.85 | 03-FEB-17:10 | 29191.70 | 04-FEB-07:10 |
March | 21823.05 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 15-MAR-11:09 | 12510.71 | 27-MAR-15:30 | 6.85 | 15-MAR-11:09 | 19261.99 | 16-MAR-06:10 |
April | 21818.08 | 12-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-07:10 | 12788.33 | 17-APR-15:20 | 6.85 | 01-APR-05:10 | 3693.49 | 19-APR-06:19 |
May | 20581.62 | 25-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 22-MAY-12:09 | 13464.62 | 22-MAY-14:09 | 6.85 | 29-MAY-16:30 | 0.00 | 01-MAY-00:10 |
June | 23372.55 | 15-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-16:10 | 12936.23 | 26-JUN-10:30 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 20527.39 | 05-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 07-JUL-12:09 | 15510.76 | 31-JUL-14:30 | 6.85 | 27-JUL-17:10 | 0.00 | 01-JUL-00:10 |
August | 21862.63 | 28-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 23-AUG-12:09 | 14230.93 | 21-AUG-14:30 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 25003.79 | 27-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 01-SEP-11:20 | 14519.26 | 18-SEP-14:09 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 23361.56 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-12:09 | 13790.73 | 02-OCT-14:30 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 22802.61 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-07:19 | 12537.33 | 06-NOV-15:30 | 6.85 | 01-NOV-05:10 | 7383.08 | 27-NOV-07:10 |
December | 24338.66 | 15-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 20-DEC-12:09 | 10499.30 | 11-DEC-15:09 | 6.85 | 01-DEC-06:10 | 18100.43 | 15-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20527.39 | 5686.19 | 41699.26 | 1410.29 | 10499.30 | 6.85 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 15510.76 | 6.85 | 29191.70 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 56230.11 | 02-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4619.72 | 19-JAN-12:30 | 0.00 |
February | 43030.78 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 4617.46 | 01-FEB-12:20 | 0.00 |
March | 51569.00 | 27-MAR-14:00 | 0.00 | 0.00 | 0.00 | 4600.95 | 01-MAR-12:00 | 0.00 |
April | 58817.65 | 14-APR-14:00 | 0.00 | 0.00 | 0.00 | 4488.16 | 04-APR-11:30 | 0.00 |
May | 65294.72 | 22-MAY-12:00 | 0.00 | 0.00 | 0.00 | 4229.20 | 01-MAY-11:39 | 0.00 |
June | 63296.91 | 26-JUN-12:30 | 0.00 | 0.00 | 0.00 | 4132.30 | 02-JUN-11:30 | 0.00 |
July | 73097.16 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 3880.23 | 03-JUL-11:00 | 0.00 |
August | 70605.70 | 21-AUG-15:00 | 0.00 | 0.00 | 0.00 | 3893.44 | 31-AUG-11:20 | 0.00 |
September | 67727.30 | 18-SEP-15:30 | 0.00 | 0.00 | 0.00 | 4220.35 | 29-SEP-11:39 | 0.00 |
October | 66579.86 | 02-OCT-14:09 | 0.00 | 0.00 | 0.00 | 4462.59 | 31-OCT-11:00 | 0.00 |
November | 56292.35 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 4594.69 | 30-NOV-12:39 | 0.00 |
December | 49623.08 | 08-DEC-15:00 | 0.00 | 0.00 | 0.00 | 4615.22 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 43030.78 | 0.00 | 0.00 | 0.00 | 3880.23 | 0.00 | ||
Maximum of Months | 73097.16 | 0.00 | 0.00 | 0.00 | 4619.72 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 131731.49 | 02-JAN-13:00 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 10907.48 | 6.85 | 0.00 | 56230.11 | 0.00 |
February | 116531.64 | 17-FEB-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 8878.24 | 6.85 | 0.00 | 42334.07 | 0.00 |
March | 130047.72 | 27-MAR-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 12510.71 | 6.85 | 0.00 | 51256.05 | 0.00 |
April | 135719.30 | 14-APR-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 11374.02 | 6.85 | 0.00 | 58379.17 | 0.00 |
May | 143545.44 | 22-MAY-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 13464.62 | 6.85 | 0.00 | 64929.49 | 0.00 |
June | 141316.11 | 26-JUN-10:30 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 12936.23 | 6.85 | 0.00 | 62421.83 | 0.00 |
July | 153152.05 | 28-JUL-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 14408.49 | 6.85 | 0.00 | 73097.16 | 0.00 |
August | 150327.65 | 21-AUG-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 14070.70 | 6.85 | 0.00 | 70605.70 | 0.00 |
September | 148046.26 | 18-SEP-15:30 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 14365.62 | 6.85 | 0.00 | 67727.30 | 0.00 |
October | 145344.17 | 02-OCT-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 13470.75 | 6.85 | 0.00 | 66579.86 | 0.00 |
November | 132379.25 | 03-NOV-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 10781.19 | 6.85 | 0.00 | 56292.35 | 0.00 |
December | 125546.59 | 08-DEC-15:50 | 19884.85 | 41659.26 | 0.00 | 1410.29 | 10236.25 | 6.85 | 0.00 | 49545.19 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 116531.64 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 8878.24 | 6.85 | 0.00 | 42334.07 | 0.00 | |
Maximum of Months | 153152.05 | 19884.85 | 41670.51 | 0.00 | 1410.29 | 14408.49 | 6.85 | 0.00 | 73097.16 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.21 | 0.00 | 26.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.20 | 0.00 | 26.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.18 | 0.00 | 26.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.46 | 0.00 | 26.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 26.26 | 0.00 | 26.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.46 | 0.00 | 26.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.51 | 2.33 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.48 | 3.00 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.48 | 7.33 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.48 | 3.67 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.39 | 3.83 | 27.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.83 | 27.47 | 20.17 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.51 | 7.33 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.68 | 6.17 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.60 | 7.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.75 | 7.33 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.89 | 13.83 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.71 | 7.83 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.71 | 10.00 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.51 | 7.17 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 65.67 | 27.71 | 61.67 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.89 | 13.83 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.59 | 9.00 | 26.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.47 | 8.17 | 26.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 2.17 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.51 | 3.17 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 2.50 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 3.00 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.49 | 7.50 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.62 | 4.17 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.81 | 7.50 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.70 | 9.50 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 25.94 | 17.50 | 25.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.82 | 8.83 | 26.82 |
Annual Sum or Average | 0.00 | 0.00 | 86.83 | 26.98 | 83.00 | 26.97 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.94 | 2.17 | 25.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.81 | 17.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.94 | 2.33 | 27.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 1.67 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.97 | 4.33 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.80 | 4.83 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.75 | 4.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.86 | 8.33 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.93 | 4.33 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.83 | 6.50 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.87 | 5.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.56 | 2.50 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.66 | 2.17 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 64.17 | 27.83 | 47.17 | 27.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.97 | 8.33 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 3.67 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.42 | 3.67 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.52 | 5.67 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.63 | 12.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.53 | 6.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.52 | 8.67 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.48 | 4.17 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.17 | 27.54 | 45.83 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.63 | 12.83 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 19.87 | 4.67 | 19.87 | 20.67 | 23.92 | 20.67 | 24.67 |
February | 2.00 | 19.87 | 2.00 | 19.87 | 22.67 | 24.50 | 22.67 | 24.87 |
March | 5.67 | 19.34 | 5.67 | 19.34 | 2.17 | 20.31 | 2.17 | 21.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.13 | 8.33 | 25.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 25.09 | 24.50 | 25.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 25.04 | 30.67 | 25.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 25.52 | 38.00 | 25.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 25.40 | 47.00 | 25.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 25.39 | 70.83 | 25.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 94.83 | 25.35 | 94.00 | 25.34 |
November | 0.33 | 20.41 | 0.33 | 20.41 | 63.00 | 25.24 | 63.00 | 25.27 |
December | 5.00 | 19.62 | 5.00 | 19.62 | 22.33 | 23.79 | 22.33 | 24.55 |
Annual Sum or Average | 17.67 | 19.64 | 17.67 | 19.64 | 445.67 | 24.94 | 444.17 | 25.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 20.31 | 2.17 | 21.02 |
Maximum of Months | 5.67 | 20.41 | 5.67 | 20.41 | 94.83 | 25.52 | 94.00 | 25.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.83 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.62 | 1.00 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.69 | 3.33 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.69 | 2.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.69 | 5.33 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 3.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.60 | 4.67 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.66 | 4.00 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.45 | 1.83 | 27.45 |
Annual Sum or Average | 0.00 | 0.00 | 41.50 | 27.64 | 31.00 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.75 | 5.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 0.83 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.34 | 1.50 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 27.34 | 2.67 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 1.50 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 1.00 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.63 | 5.67 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.52 | 5.83 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.63 | 6.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.74 | 13.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.55 | 7.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.59 | 9.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.52 | 4.67 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 56.00 | 27.61 | 55.67 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.74 | 13.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 25.73 | 19.50 | 25.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 25.60 | 18.33 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.23 | 2.33 | 26.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.46 | 1.00 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 1.00 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.46 | 1.33 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.45 | 2.33 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.66 | 6.33 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 25.82 | 24.00 | 25.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 25.35 | 37.00 | 25.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 25.81 | 18.50 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 132.50 | 25.81 | 131.67 | 25.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 27.66 | 37.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.82 | 2.17 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.73 | 1.33 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.83 | 3.67 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.77 | 3.00 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.65 | 3.00 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.79 | 5.67 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.84 | 3.33 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.79 | 4.67 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.74 | 4.17 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.49 | 1.67 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 2.00 | 27.55 |
Annual Sum or Average | 0.00 | 0.00 | 46.33 | 27.76 | 34.67 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.84 | 5.67 | 27.88 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 24.00 | 357.00 | 24.62 | 0.00 | 24.62 |
February | 11.33 | 24.00 | 349.33 | 24.56 | 0.00 | 24.56 |
March | 2.17 | 24.00 | 393.17 | 24.54 | 0.00 | 24.54 |
April | 0.00 | 0.00 | 467.17 | 24.47 | 0.00 | 24.47 |
May | 0.00 | 0.00 | 508.00 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 496.00 | 24.42 | 0.00 | 24.42 |
July | 0.00 | 0.00 | 497.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 514.00 | 24.42 | 0.00 | 24.42 |
September | 0.00 | 0.00 | 485.00 | 24.45 | 0.00 | 24.45 |
October | 0.00 | 0.00 | 502.00 | 24.51 | 0.00 | 24.51 |
November | 0.00 | 0.00 | 477.17 | 24.54 | 0.00 | 24.54 |
December | 3.17 | 24.00 | 374.83 | 24.61 | 0.00 | 24.61 |
Annual Sum or Average | 22.83 | 24.00 | 5420.67 | 24.50 | 0.00 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 349.33 | 24.42 | 0.00 | 24.42 |
Maximum of Months | 11.33 | 24.00 | 514.00 | 24.62 | 0.00 | 24.62 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.50 | 23.44 | 183.50 | 24.00 | 0.00 | 24.00 |
February | 86.83 | 23.30 | 215.17 | 24.08 | 0.00 | 24.08 |
March | 76.67 | 23.50 | 286.33 | 24.17 | 0.00 | 24.17 |
April | 3.33 | 23.58 | 362.67 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 481.00 | 24.30 | 0.00 | 24.30 |
June | 0.00 | 0.00 | 488.00 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 487.33 | 24.31 | 0.00 | 24.31 |
August | 0.00 | 0.00 | 500.33 | 24.28 | 0.00 | 24.28 |
September | 0.00 | 0.00 | 474.17 | 24.30 | 0.00 | 24.30 |
October | 0.00 | 0.00 | 468.17 | 24.37 | 0.00 | 24.37 |
November | 9.50 | 23.60 | 385.00 | 24.36 | 0.00 | 24.36 |
December | 115.83 | 23.30 | 202.17 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 425.67 | 23.39 | 4533.83 | 24.25 | 0.00 | 24.25 |
Minimum of Months | 0.00 | 0.00 | 183.50 | 23.98 | 0.00 | 23.98 |
Maximum of Months | 133.50 | 23.60 | 500.33 | 24.37 | 0.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.33 | 23.14 | 121.00 | 23.51 | 0.00 | 23.51 |
February | 152.00 | 23.01 | 179.00 | 23.71 | 0.00 | 23.71 |
March | 123.33 | 23.22 | 258.83 | 23.94 | 0.00 | 23.94 |
April | 20.33 | 23.46 | 351.67 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 470.33 | 24.32 | 0.00 | 24.32 |
June | 0.00 | 0.00 | 492.83 | 24.31 | 0.00 | 24.31 |
July | 0.00 | 0.00 | 490.50 | 24.37 | 0.00 | 24.37 |
August | 2.33 | 23.32 | 498.50 | 24.30 | 0.00 | 24.30 |
September | 0.00 | 0.00 | 469.00 | 24.33 | 0.00 | 24.33 |
October | 3.00 | 23.36 | 442.17 | 24.37 | 0.00 | 24.37 |
November | 45.17 | 23.25 | 321.17 | 24.21 | 0.00 | 24.21 |
December | 207.00 | 23.04 | 163.00 | 23.59 | 0.00 | 23.59 |
Annual Sum or Average | 803.50 | 23.12 | 4258.00 | 24.13 | 0.00 | 24.13 |
Minimum of Months | 0.00 | 0.00 | 121.00 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 250.33 | 23.46 | 498.50 | 24.37 | 0.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.33 | 22.60 | 123.00 | 23.02 | 7.00 | 22.99 |
February | 205.33 | 22.81 | 189.67 | 23.41 | 21.50 | 23.40 |
March | 189.00 | 23.08 | 274.17 | 23.78 | 27.67 | 23.82 |
April | 61.17 | 23.95 | 363.33 | 24.29 | 16.67 | 24.34 |
May | 39.50 | 26.14 | 495.83 | 24.56 | 39.50 | 24.67 |
June | 33.50 | 26.52 | 496.00 | 24.58 | 33.50 | 24.70 |
July | 42.50 | 26.66 | 494.00 | 24.73 | 42.50 | 24.87 |
August | 38.50 | 26.27 | 508.33 | 24.55 | 38.50 | 24.66 |
September | 31.33 | 26.35 | 474.83 | 24.58 | 31.33 | 24.68 |
October | 41.83 | 25.43 | 453.33 | 24.55 | 32.83 | 24.64 |
November | 103.00 | 23.51 | 337.00 | 24.12 | 24.33 | 24.17 |
December | 266.67 | 22.68 | 187.50 | 23.30 | 28.50 | 23.32 |
Annual Sum or Average | 1354.67 | 23.45 | 4397.00 | 24.17 | 343.83 | 24.25 |
Minimum of Months | 31.33 | 22.60 | 123.00 | 23.02 | 7.00 | 22.99 |
Maximum of Months | 302.33 | 26.66 | 508.33 | 24.73 | 42.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.67 | 22.82 | 201.33 | 23.59 | 10.83 | 23.61 |
February | 144.50 | 23.12 | 243.67 | 23.85 | 18.17 | 23.87 |
March | 116.83 | 23.59 | 330.83 | 24.14 | 32.50 | 24.21 |
April | 66.67 | 25.28 | 403.67 | 24.58 | 41.33 | 24.73 |
May | 57.83 | 26.44 | 503.17 | 24.68 | 57.83 | 24.85 |
June | 47.83 | 26.69 | 496.00 | 24.68 | 47.83 | 24.85 |
July | 65.33 | 26.89 | 496.17 | 24.89 | 65.33 | 25.10 |
August | 48.33 | 26.59 | 512.17 | 24.65 | 48.33 | 24.80 |
September | 53.67 | 26.69 | 481.17 | 24.75 | 53.67 | 24.93 |
October | 67.50 | 26.30 | 471.00 | 24.76 | 63.50 | 24.94 |
November | 75.83 | 24.08 | 387.83 | 24.34 | 27.50 | 24.43 |
December | 214.67 | 22.87 | 217.00 | 23.62 | 29.83 | 23.68 |
Annual Sum or Average | 1166.67 | 24.27 | 4744.00 | 24.43 | 496.67 | 24.57 |
Minimum of Months | 47.83 | 22.82 | 201.33 | 23.59 | 10.83 | 23.61 |
Maximum of Months | 214.67 | 26.89 | 512.17 | 24.89 | 65.33 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 187.83 | 23.21 | 254.00 | 23.98 | 24.33 | 24.09 |
February | 131.83 | 23.54 | 265.67 | 24.13 | 34.67 | 24.24 |
March | 135.33 | 23.59 | 324.33 | 24.12 | 38.00 | 24.22 |
April | 69.83 | 24.55 | 372.67 | 24.44 | 29.67 | 24.55 |
May | 43.33 | 25.98 | 493.83 | 24.55 | 41.17 | 24.66 |
June | 29.17 | 26.46 | 493.83 | 24.54 | 29.17 | 24.64 |
July | 40.83 | 26.64 | 491.67 | 24.70 | 40.83 | 24.84 |
August | 40.33 | 26.33 | 509.33 | 24.57 | 40.33 | 24.69 |
September | 42.83 | 26.63 | 477.33 | 24.69 | 42.83 | 24.84 |
October | 68.00 | 26.39 | 470.67 | 24.82 | 63.50 | 25.01 |
November | 92.67 | 24.79 | 401.67 | 24.60 | 48.67 | 24.76 |
December | 197.83 | 23.52 | 282.83 | 24.11 | 51.17 | 24.28 |
Annual Sum or Average | 1079.83 | 24.36 | 4837.83 | 24.46 | 484.33 | 24.59 |
Minimum of Months | 29.17 | 23.21 | 254.00 | 23.98 | 24.33 | 24.09 |
Maximum of Months | 197.83 | 26.64 | 509.33 | 24.82 | 63.50 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.17 | 22.67 | 182.17 | 23.35 | 9.17 | 23.34 |
February | 170.17 | 23.08 | 232.67 | 23.75 | 30.83 | 23.81 |
March | 151.17 | 23.42 | 321.67 | 24.05 | 38.67 | 24.14 |
April | 66.67 | 25.03 | 389.67 | 24.53 | 37.83 | 24.67 |
May | 55.00 | 26.33 | 498.83 | 24.67 | 55.00 | 24.82 |
June | 41.50 | 26.56 | 495.67 | 24.64 | 41.50 | 24.77 |
July | 52.17 | 26.76 | 494.33 | 24.80 | 52.17 | 24.97 |
August | 45.50 | 26.42 | 512.83 | 24.63 | 45.50 | 24.76 |
September | 44.67 | 26.61 | 478.33 | 24.70 | 44.67 | 24.85 |
October | 61.17 | 26.05 | 467.50 | 24.71 | 54.00 | 24.87 |
November | 105.17 | 23.96 | 369.50 | 24.30 | 36.50 | 24.40 |
December | 233.17 | 22.94 | 233.67 | 23.65 | 39.50 | 23.73 |
Annual Sum or Average | 1277.50 | 23.98 | 4676.83 | 24.35 | 485.33 | 24.48 |
Minimum of Months | 41.50 | 22.67 | 182.17 | 23.35 | 9.17 | 23.34 |
Maximum of Months | 251.17 | 26.76 | 512.83 | 24.80 | 55.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.00 | 23.13 | 169.50 | 23.62 | 0.00 | 23.62 |
February | 149.83 | 23.23 | 219.83 | 23.83 | 9.50 | 23.87 |
March | 159.50 | 23.35 | 284.00 | 23.94 | 18.17 | 23.99 |
April | 24.00 | 24.45 | 387.33 | 24.30 | 9.00 | 24.33 |
May | 5.33 | 26.07 | 508.00 | 24.40 | 5.33 | 24.42 |
June | 7.83 | 26.37 | 496.00 | 24.44 | 7.83 | 24.47 |
July | 4.33 | 26.76 | 497.00 | 24.54 | 4.33 | 24.56 |
August | 12.00 | 26.22 | 514.00 | 24.46 | 12.00 | 24.50 |
September | 3.00 | 26.70 | 485.00 | 24.47 | 3.00 | 24.48 |
October | 9.83 | 26.15 | 499.33 | 24.48 | 9.83 | 24.51 |
November | 30.67 | 24.35 | 419.33 | 24.32 | 11.00 | 24.37 |
December | 162.50 | 23.17 | 236.83 | 23.87 | 3.67 | 23.88 |
Annual Sum or Average | 772.83 | 23.47 | 4716.17 | 24.25 | 93.67 | 24.28 |
Minimum of Months | 3.00 | 23.13 | 169.50 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 204.00 | 26.76 | 514.00 | 24.54 | 18.17 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 109.33 | 23.44 | 280.50 | 24.15 | 4.17 | 24.18 |
February | 70.83 | 23.67 | 297.67 | 24.23 | 11.50 | 24.28 |
March | 72.67 | 23.95 | 365.67 | 24.28 | 20.17 | 24.34 |
April | 27.17 | 26.24 | 441.83 | 24.55 | 23.50 | 24.65 |
May | 29.00 | 26.71 | 508.00 | 24.60 | 29.00 | 24.71 |
June | 33.33 | 26.79 | 496.00 | 24.63 | 33.33 | 24.76 |
July | 57.33 | 26.88 | 497.00 | 24.87 | 57.33 | 25.06 |
August | 37.67 | 26.76 | 514.00 | 24.65 | 37.67 | 24.78 |
September | 40.50 | 26.84 | 485.00 | 24.74 | 40.50 | 24.89 |
October | 39.33 | 26.72 | 502.00 | 24.72 | 39.33 | 24.86 |
November | 17.83 | 25.66 | 458.17 | 24.48 | 13.17 | 24.53 |
December | 115.00 | 23.39 | 277.00 | 24.16 | 6.00 | 24.19 |
Annual Sum or Average | 650.00 | 24.92 | 5122.83 | 24.54 | 315.67 | 24.65 |
Minimum of Months | 17.83 | 23.39 | 277.00 | 24.15 | 4.17 | 24.18 |
Maximum of Months | 115.00 | 26.88 | 514.00 | 24.87 | 57.33 | 25.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.67 | 23.57 | 351.33 | 24.32 | 41.00 | 24.41 |
February | 92.50 | 23.79 | 340.50 | 24.39 | 41.17 | 24.48 |
March | 136.83 | 23.40 | 366.83 | 24.09 | 58.50 | 24.13 |
April | 56.17 | 24.10 | 418.17 | 24.35 | 41.33 | 24.37 |
May | 92.17 | 24.33 | 506.83 | 24.42 | 92.17 | 24.41 |
June | 128.67 | 24.45 | 496.00 | 24.46 | 128.67 | 24.45 |
July | 110.50 | 24.72 | 497.00 | 24.64 | 110.50 | 24.66 |
August | 139.67 | 24.84 | 514.00 | 24.64 | 139.67 | 24.68 |
September | 128.83 | 25.11 | 485.00 | 24.82 | 128.83 | 24.87 |
October | 126.33 | 25.53 | 502.00 | 24.98 | 126.33 | 25.07 |
November | 107.83 | 25.02 | 469.00 | 24.78 | 100.00 | 24.85 |
December | 124.33 | 23.88 | 349.50 | 24.44 | 48.50 | 24.57 |
Annual Sum or Average | 1369.50 | 24.42 | 5296.17 | 24.55 | 1056.67 | 24.60 |
Minimum of Months | 56.17 | 23.40 | 340.50 | 24.09 | 41.00 | 24.13 |
Maximum of Months | 139.67 | 25.53 | 514.00 | 24.98 | 139.67 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.83 | 23.31 | 259.67 | 24.00 | 0.00 | 24.00 |
February | 96.33 | 23.68 | 291.00 | 24.23 | 17.33 | 24.31 |
March | 99.50 | 23.90 | 363.67 | 24.28 | 23.50 | 24.36 |
April | 29.50 | 26.23 | 445.00 | 24.56 | 25.67 | 24.67 |
May | 21.33 | 26.66 | 508.00 | 24.58 | 21.33 | 24.66 |
June | 19.33 | 26.74 | 496.00 | 24.55 | 19.33 | 24.63 |
July | 30.00 | 26.86 | 497.00 | 24.73 | 30.00 | 24.85 |
August | 28.50 | 26.69 | 514.00 | 24.61 | 28.50 | 24.72 |
September | 26.67 | 26.86 | 485.00 | 24.68 | 26.67 | 24.78 |
October | 34.00 | 26.71 | 501.67 | 24.70 | 34.00 | 24.82 |
November | 25.83 | 25.31 | 448.17 | 24.48 | 16.67 | 24.54 |
December | 119.17 | 23.57 | 296.83 | 24.22 | 11.67 | 24.28 |
Annual Sum or Average | 659.00 | 24.54 | 5106.00 | 24.49 | 254.67 | 24.58 |
Minimum of Months | 19.33 | 23.31 | 259.67 | 24.00 | 0.00 | 24.00 |
Maximum of Months | 128.83 | 26.86 | 514.00 | 24.73 | 34.00 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.50 | 22.97 | 145.67 | 23.44 | 0.67 | 23.44 |
February | 157.00 | 23.09 | 211.67 | 23.73 | 13.83 | 23.77 |
March | 155.00 | 23.38 | 294.33 | 23.98 | 23.83 | 24.04 |
April | 29.67 | 24.64 | 393.50 | 24.35 | 14.83 | 24.40 |
May | 25.00 | 26.13 | 507.17 | 24.50 | 25.00 | 24.57 |
June | 16.17 | 26.49 | 496.00 | 24.50 | 16.17 | 24.56 |
July | 17.83 | 26.65 | 496.67 | 24.61 | 17.83 | 24.68 |
August | 20.83 | 26.21 | 514.00 | 24.48 | 20.83 | 24.54 |
September | 12.50 | 26.33 | 484.83 | 24.49 | 12.50 | 24.54 |
October | 24.17 | 26.03 | 478.50 | 24.53 | 23.83 | 24.60 |
November | 63.67 | 24.04 | 376.67 | 24.27 | 21.67 | 24.33 |
December | 222.17 | 23.06 | 211.17 | 23.66 | 20.17 | 23.72 |
Annual Sum or Average | 988.50 | 23.58 | 4610.17 | 24.25 | 211.17 | 24.31 |
Minimum of Months | 12.50 | 22.97 | 145.67 | 23.44 | 0.67 | 23.44 |
Maximum of Months | 244.50 | 26.65 | 514.00 | 24.61 | 25.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 156.67 | 23.15 | 185.67 | 23.92 | 6.33 | 23.97 |
February | 103.17 | 23.53 | 218.00 | 24.14 | 17.50 | 24.21 |
March | 92.83 | 23.86 | 287.00 | 24.29 | 27.33 | 24.38 |
April | 44.17 | 26.00 | 351.67 | 24.72 | 35.83 | 24.88 |
May | 46.33 | 26.56 | 429.67 | 24.76 | 46.33 | 24.92 |
June | 43.17 | 26.73 | 418.00 | 24.78 | 43.17 | 24.94 |
July | 62.17 | 26.88 | 422.00 | 25.01 | 62.17 | 25.22 |
August | 43.50 | 26.68 | 433.00 | 24.75 | 43.50 | 24.91 |
September | 49.33 | 26.74 | 410.00 | 24.86 | 49.33 | 25.04 |
October | 52.83 | 26.59 | 416.17 | 24.86 | 52.83 | 25.03 |
November | 47.33 | 24.72 | 354.50 | 24.51 | 24.50 | 24.60 |
December | 167.67 | 23.26 | 196.83 | 23.96 | 23.33 | 24.05 |
Annual Sum or Average | 909.17 | 24.67 | 4122.50 | 24.59 | 432.17 | 24.74 |
Minimum of Months | 43.17 | 23.15 | 185.67 | 23.92 | 6.33 | 23.97 |
Maximum of Months | 167.67 | 26.88 | 433.00 | 25.01 | 62.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 138.50 | 23.72 | 290.83 | 24.33 | 22.83 | 24.46 |
February | 97.83 | 24.03 | 293.67 | 24.41 | 29.00 | 24.54 |
March | 98.33 | 23.89 | 346.83 | 24.27 | 30.17 | 24.37 |
April | 32.67 | 25.21 | 401.83 | 24.47 | 20.83 | 24.55 |
May | 25.50 | 26.09 | 504.33 | 24.49 | 25.50 | 24.57 |
June | 15.17 | 26.38 | 496.00 | 24.46 | 15.17 | 24.52 |
July | 17.00 | 26.65 | 496.67 | 24.58 | 17.00 | 24.65 |
August | 28.33 | 26.36 | 514.00 | 24.52 | 28.33 | 24.61 |
September | 36.00 | 26.73 | 485.00 | 24.67 | 36.00 | 24.80 |
October | 61.17 | 26.71 | 491.83 | 24.86 | 61.17 | 25.04 |
November | 64.50 | 25.57 | 432.83 | 24.74 | 45.50 | 24.88 |
December | 160.33 | 24.03 | 306.17 | 24.42 | 46.17 | 24.60 |
Annual Sum or Average | 775.33 | 24.73 | 5060.00 | 24.53 | 377.67 | 24.65 |
Minimum of Months | 15.17 | 23.72 | 290.83 | 24.27 | 15.17 | 24.37 |
Maximum of Months | 160.33 | 26.73 | 514.00 | 24.86 | 61.17 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 189.00 | 23.04 | 208.83 | 23.74 | 2.17 | 23.75 |
February | 126.00 | 23.43 | 260.67 | 24.06 | 23.17 | 24.15 |
March | 116.67 | 23.76 | 346.33 | 24.22 | 32.33 | 24.32 |
April | 40.67 | 25.97 | 422.83 | 24.58 | 34.00 | 24.71 |
May | 40.50 | 26.43 | 508.00 | 24.63 | 40.50 | 24.75 |
June | 29.67 | 26.64 | 496.00 | 24.59 | 29.67 | 24.70 |
July | 36.67 | 26.81 | 496.83 | 24.74 | 36.67 | 24.87 |
August | 35.17 | 26.49 | 514.00 | 24.60 | 35.17 | 24.71 |
September | 34.50 | 26.68 | 485.00 | 24.66 | 34.50 | 24.79 |
October | 46.83 | 26.50 | 489.50 | 24.71 | 46.50 | 24.85 |
November | 61.17 | 24.58 | 404.83 | 24.42 | 31.33 | 24.52 |
December | 194.50 | 23.36 | 257.00 | 23.98 | 31.00 | 24.07 |
Annual Sum or Average | 951.33 | 24.30 | 4889.83 | 24.44 | 377.00 | 24.55 |
Minimum of Months | 29.67 | 23.04 | 208.83 | 23.74 | 2.17 | 23.75 |
Maximum of Months | 194.50 | 26.81 | 514.00 | 24.74 | 46.50 | 24.87 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45846 | 41.37170 | 0.50295 | 10.64893 |
February | 454.00000 | 24.46345 | 42.24358 | 0.51244 | 10.90538 |
March | 514.00000 | 24.42745 | 42.95654 | 0.51536 | 10.93926 |
April | 485.00000 | 24.45677 | 46.07114 | 0.55148 | 11.66528 |
May | 508.00000 | 24.45143 | 47.47943 | -0.2716 | 7.13326 |
June | 496.00000 | 24.42213 | 47.71445 | -0.2752 | 7.15720 |
July | 497.00000 | 24.46699 | 47.42843 | -0.2619 | 7.02190 |
August | 514.00000 | 24.41761 | 47.68137 | -0.2746 | 7.13797 |
September | 485.00000 | 24.45216 | 47.38224 | -0.2665 | 7.08426 |
October | 502.00000 | 24.51440 | 47.04111 | 0.58317 | 12.49959 |
November | 489.00000 | 24.53071 | 46.19260 | 0.57109 | 12.20260 |
December | 497.00000 | 24.47357 | 43.01936 | 0.51835 | 10.99419 |
Annual Sum or Average | 5943.00000 | 24.46099 | 45.56642 | 0.19722 | 9.59979 |
Minimum of Months | 454.00000 | 24.41761 | 41.37170 | -0.2752 | 7.02190 |
Maximum of Months | 514.00000 | 24.53071 | 47.71445 | 0.58317 | 12.49959 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.99330 | 42.84918 | 0.37669 | 8.35534 |
February | 454.00000 | 24.03224 | 43.62375 | 0.39724 | 8.83605 |
March | 514.00000 | 24.10471 | 44.21676 | 0.42576 | 9.13177 |
April | 485.00000 | 24.21517 | 47.23552 | 0.48384 | 10.06865 |
May | 508.00000 | 24.26766 | 48.79148 | -0.3481 | 7.87188 |
June | 496.00000 | 24.27256 | 48.93493 | -0.3390 | 7.74244 |
July | 497.00000 | 24.29941 | 48.65372 | -0.3295 | 7.61628 |
August | 514.00000 | 24.26185 | 48.97268 | -0.3422 | 7.76814 |
September | 485.00000 | 24.29023 | 48.69151 | -0.3355 | 7.72614 |
October | 502.00000 | 24.33460 | 48.27359 | 0.53025 | 11.13482 |
November | 489.00000 | 24.26617 | 47.55794 | 0.49438 | 10.34555 |
December | 497.00000 | 23.99352 | 44.60531 | 0.39140 | 8.60600 |
Annual Sum or Average | 5943.00000 | 24.19513 | 46.88477 | 0.11410 | 8.76212 |
Minimum of Months | 454.00000 | 23.99330 | 42.84918 | -0.3481 | 7.61628 |
Maximum of Months | 514.00000 | 24.33460 | 48.97268 | 0.53025 | 11.13482 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62467 | 42.93015 | 0.27986 | 7.44008 |
February | 454.00000 | 23.78054 | 43.37854 | 0.33148 | 8.29199 |
March | 514.00000 | 23.95625 | 43.87544 | 0.38729 | 8.75952 |
April | 485.00000 | 24.17323 | 46.56360 | 0.47585 | 9.94120 |
May | 508.00000 | 24.28895 | 48.38403 | -0.3274 | 7.60829 |
June | 496.00000 | 24.31218 | 48.68876 | -0.3085 | 7.38840 |
July | 497.00000 | 24.35913 | 48.33289 | -0.2903 | 7.21968 |
August | 514.00000 | 24.28546 | 48.83820 | -0.3195 | 7.51683 |
September | 485.00000 | 24.31389 | 48.51162 | -0.3143 | 7.48733 |
October | 502.00000 | 24.30566 | 48.03753 | 0.52604 | 11.04412 |
November | 489.00000 | 24.13235 | 47.44667 | 0.45927 | 9.74933 |
December | 497.00000 | 23.67553 | 44.70581 | 0.30853 | 7.82222 |
Annual Sum or Average | 5943.00000 | 24.10255 | 46.65931 | 0.09803 | 8.35191 |
Minimum of Months | 454.00000 | 23.62467 | 42.93015 | -0.3274 | 7.21968 |
Maximum of Months | 514.00000 | 24.35913 | 48.83820 | 0.52604 | 11.04412 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19448 | 46.49986 | 0.18629 | 7.57581 |
February | 454.00000 | 23.50602 | 46.81096 | 0.28398 | 8.64098 |
March | 514.00000 | 23.75039 | 47.63937 | 0.36238 | 9.45196 |
April | 485.00000 | 24.18105 | 49.08247 | 0.50601 | 10.91868 |
May | 508.00000 | 24.41797 | 50.95296 | -0.2236 | 7.12282 |
June | 496.00000 | 24.44967 | 50.50400 | -0.1916 | 6.83479 |
July | 497.00000 | 24.55476 | 49.55249 | -0.1553 | 6.85796 |
August | 514.00000 | 24.41406 | 50.78756 | -0.2164 | 7.03029 |
September | 485.00000 | 24.44523 | 50.32734 | -0.2187 | 7.11645 |
October | 502.00000 | 24.39337 | 50.88613 | 0.57953 | 12.69011 |
November | 489.00000 | 24.03667 | 50.60456 | 0.46049 | 10.37927 |
December | 497.00000 | 23.35574 | 49.08331 | 0.25004 | 8.28663 |
Annual Sum or Average | 5943.00000 | 24.06157 | 49.41054 | 0.13316 | 8.56910 |
Minimum of Months | 454.00000 | 23.19448 | 46.49986 | -0.2236 | 6.83479 |
Maximum of Months | 514.00000 | 24.55476 | 50.95296 | 0.57953 | 12.69011 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.64269 | 45.32596 | 0.31230 | 9.05776 |
February | 454.00000 | 23.84871 | 45.84130 | 0.39163 | 9.86414 |
March | 514.00000 | 24.02376 | 46.51098 | 0.46320 | 10.88577 |
April | 485.00000 | 24.34325 | 48.24712 | 0.58950 | 13.20477 |
May | 508.00000 | 24.47426 | 50.51297 | -0.1513 | 6.90508 |
June | 496.00000 | 24.49034 | 50.18939 | -0.1288 | 6.73277 |
July | 497.00000 | 24.62571 | 49.06004 | -0.0779 | 7.13582 |
August | 514.00000 | 24.46065 | 50.38304 | -0.1508 | 6.88588 |
September | 485.00000 | 24.52791 | 49.73669 | -0.1361 | 7.02755 |
October | 502.00000 | 24.49180 | 50.27557 | 0.64015 | 14.48540 |
November | 489.00000 | 24.21598 | 49.94374 | 0.52868 | 11.80170 |
December | 497.00000 | 23.63243 | 48.57296 | 0.33116 | 9.43303 |
Annual Sum or Average | 5943.00000 | 24.23361 | 48.73468 | 0.21539 | 9.43922 |
Minimum of Months | 454.00000 | 23.63243 | 45.32596 | -0.1513 | 6.73277 |
Maximum of Months | 514.00000 | 24.62571 | 50.51297 | 0.64015 | 14.48540 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86719 | 43.33506 | 0.39975 | 10.85610 |
February | 454.00000 | 23.99240 | 44.54676 | 0.44962 | 11.38196 |
March | 514.00000 | 23.99111 | 46.14400 | 0.45812 | 11.05855 |
April | 485.00000 | 24.25406 | 48.57629 | 0.54157 | 11.92011 |
May | 508.00000 | 24.40720 | 51.03590 | -0.2282 | 7.20036 |
June | 496.00000 | 24.42385 | 50.72530 | -0.2103 | 6.92600 |
July | 497.00000 | 24.52979 | 49.70187 | -0.1689 | 6.91776 |
August | 514.00000 | 24.42317 | 50.62522 | -0.1994 | 6.97336 |
September | 485.00000 | 24.50361 | 49.74199 | -0.1573 | 7.09385 |
October | 502.00000 | 24.54053 | 49.60285 | 0.66554 | 15.34501 |
November | 489.00000 | 24.36625 | 48.51061 | 0.59270 | 13.73556 |
December | 497.00000 | 23.90702 | 46.09376 | 0.43519 | 11.63964 |
Annual Sum or Average | 5943.00000 | 24.26837 | 48.24515 | 0.21204 | 10.06955 |
Minimum of Months | 454.00000 | 23.86719 | 43.33506 | -0.2282 | 6.91776 |
Maximum of Months | 514.00000 | 24.54053 | 51.03590 | 0.66554 | 15.34501 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44634 | 45.93417 | 0.26420 | 8.58680 |
February | 454.00000 | 23.73707 | 46.21252 | 0.36480 | 10.11043 |
March | 514.00000 | 23.93330 | 46.95964 | 0.44271 | 11.01293 |
April | 485.00000 | 24.30652 | 48.60509 | 0.57750 | 12.94642 |
May | 508.00000 | 24.47376 | 50.88105 | -0.1578 | 7.02285 |
June | 496.00000 | 24.47494 | 50.66412 | -0.1544 | 6.83540 |
July | 497.00000 | 24.59170 | 49.59817 | -0.1044 | 6.98304 |
August | 514.00000 | 24.46745 | 50.66229 | -0.1522 | 6.88190 |
September | 485.00000 | 24.50911 | 50.21975 | -0.1587 | 7.17188 |
October | 502.00000 | 24.47887 | 50.60101 | 0.63207 | 14.28225 |
November | 489.00000 | 24.15519 | 50.28043 | 0.51326 | 11.67880 |
December | 497.00000 | 23.59868 | 48.46753 | 0.32942 | 9.65932 |
Annual Sum or Average | 5943.00000 | 24.18364 | 49.10847 | 0.19755 | 9.41711 |
Minimum of Months | 454.00000 | 23.44634 | 45.93417 | -0.1587 | 6.83540 |
Maximum of Months | 514.00000 | 24.59170 | 50.88105 | 0.63207 | 14.28225 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70107 | 45.76773 | 0.31368 | 7.83256 |
February | 454.00000 | 23.81688 | 46.52884 | 0.35796 | 8.62396 |
March | 514.00000 | 23.88774 | 47.64724 | 0.38663 | 9.02890 |
April | 485.00000 | 24.19792 | 49.23876 | 0.49455 | 10.38135 |
May | 508.00000 | 24.38343 | 49.95608 | -0.2676 | 7.14079 |
June | 496.00000 | 24.40585 | 49.57017 | -0.2374 | 6.86062 |
July | 497.00000 | 24.51857 | 48.62241 | -0.1950 | 6.66066 |
August | 514.00000 | 24.41534 | 49.40408 | -0.2327 | 6.86278 |
September | 485.00000 | 24.45350 | 48.91838 | -0.2293 | 6.87258 |
October | 502.00000 | 24.43965 | 49.36163 | 0.58340 | 12.54937 |
November | 489.00000 | 24.25373 | 49.22103 | 0.51164 | 10.85358 |
December | 497.00000 | 23.86564 | 47.68813 | 0.37441 | 8.78537 |
Annual Sum or Average | 5943.00000 | 24.19693 | 48.50573 | 0.15250 | 8.53070 |
Minimum of Months | 454.00000 | 23.70107 | 45.76773 | -0.2676 | 6.66066 |
Maximum of Months | 514.00000 | 24.51857 | 49.95608 | 0.58340 | 12.54937 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.09439 | 44.52500 | 0.43261 | 9.80684 |
February | 454.00000 | 24.15184 | 45.44237 | 0.46728 | 10.32000 |
March | 514.00000 | 24.17905 | 46.32276 | 0.49476 | 10.87247 |
April | 485.00000 | 24.40591 | 48.14879 | 0.59015 | 12.88014 |
May | 508.00000 | 24.47830 | 49.45853 | -0.1805 | 6.73336 |
June | 496.00000 | 24.48568 | 49.17002 | -0.1603 | 6.62266 |
July | 497.00000 | 24.63447 | 48.07285 | -0.1020 | 6.77492 |
August | 514.00000 | 24.49213 | 48.97052 | -0.1545 | 6.61869 |
September | 485.00000 | 24.56523 | 48.30996 | -0.1337 | 6.68147 |
October | 502.00000 | 24.56561 | 48.72724 | 0.65316 | 14.63530 |
November | 489.00000 | 24.40634 | 48.63883 | 0.57782 | 12.47529 |
December | 497.00000 | 24.08514 | 47.11398 | 0.44590 | 10.11959 |
Annual Sum or Average | 5943.00000 | 24.37968 | 47.75571 | 0.24159 | 9.52977 |
Minimum of Months | 454.00000 | 24.08514 | 44.52500 | -0.1805 | 6.61869 |
Maximum of Months | 514.00000 | 24.63447 | 49.45853 | 0.65316 | 14.63530 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18846 | 45.25761 | 0.51936 | 12.33193 |
February | 454.00000 | 24.23898 | 47.04612 | 0.53888 | 12.47597 |
March | 514.00000 | 24.03153 | 49.25750 | 0.49175 | 11.53167 |
April | 485.00000 | 24.28726 | 52.63747 | 0.56328 | 12.14731 |
May | 508.00000 | 24.43621 | 56.61155 | -0.2078 | 6.56868 |
June | 496.00000 | 24.45553 | 58.72831 | -0.1726 | 6.23647 |
July | 497.00000 | 24.62824 | 56.62752 | -0.1156 | 6.18791 |
August | 514.00000 | 24.59078 | 57.81878 | -0.1060 | 6.18994 |
September | 485.00000 | 24.73565 | 55.74475 | -0.0464 | 6.34926 |
October | 502.00000 | 24.84245 | 54.03673 | 0.77236 | 18.37778 |
November | 489.00000 | 24.65773 | 52.56065 | 0.70579 | 16.42265 |
December | 497.00000 | 24.22674 | 47.72461 | 0.54982 | 13.13615 |
Annual Sum or Average | 5943.00000 | 24.44356 | 52.87908 | 0.28805 | 10.63857 |
Minimum of Months | 454.00000 | 24.03153 | 45.25761 | -0.2078 | 6.18791 |
Maximum of Months | 514.00000 | 24.84245 | 58.72831 | 0.77236 | 18.37778 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.00294 | 44.94224 | 0.40429 | 9.17168 |
February | 454.00000 | 24.11094 | 45.62947 | 0.45409 | 10.37528 |
March | 514.00000 | 24.17739 | 46.53484 | 0.49170 | 10.95747 |
April | 485.00000 | 24.40504 | 48.35269 | 0.58633 | 12.76730 |
May | 508.00000 | 24.48799 | 49.65026 | -0.1840 | 6.78193 |
June | 496.00000 | 24.46360 | 49.56719 | -0.1895 | 6.73144 |
July | 497.00000 | 24.60538 | 48.45506 | -0.1269 | 6.63882 |
August | 514.00000 | 24.49985 | 49.12165 | -0.1558 | 6.60324 |
September | 485.00000 | 24.55518 | 48.64228 | -0.1548 | 6.79259 |
October | 502.00000 | 24.56690 | 48.91543 | 0.64794 | 14.49431 |
November | 489.00000 | 24.38750 | 48.79248 | 0.57023 | 12.31816 |
December | 497.00000 | 24.12825 | 46.90970 | 0.46031 | 10.44713 |
Annual Sum or Average | 5943.00000 | 24.36718 | 47.97338 | 0.23109 | 9.49062 |
Minimum of Months | 454.00000 | 24.00294 | 44.94224 | -0.1895 | 6.60324 |
Maximum of Months | 514.00000 | 24.60538 | 49.65026 | 0.64794 | 14.49431 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.54611 | 46.10373 | 0.27587 | 7.70536 |
February | 454.00000 | 23.73864 | 46.68075 | 0.34252 | 8.69213 |
March | 514.00000 | 23.91057 | 47.57197 | 0.40008 | 9.44616 |
April | 485.00000 | 24.23807 | 49.31850 | 0.51480 | 10.91044 |
May | 508.00000 | 24.41663 | 50.78720 | -0.2421 | 7.10639 |
June | 496.00000 | 24.43101 | 50.32361 | -0.2184 | 6.87749 |
July | 497.00000 | 24.53358 | 49.44435 | -0.1858 | 6.79534 |
August | 514.00000 | 24.40590 | 50.51711 | -0.2371 | 7.02454 |
September | 485.00000 | 24.44258 | 50.10336 | -0.2364 | 7.06918 |
October | 502.00000 | 24.42597 | 50.63601 | 0.58088 | 12.61223 |
November | 489.00000 | 24.16668 | 50.27972 | 0.49074 | 10.59163 |
December | 497.00000 | 23.65644 | 48.56413 | 0.32514 | 8.43372 |
Annual Sum or Average | 5943.00000 | 24.16178 | 49.20936 | 0.14847 | 8.59854 |
Minimum of Months | 454.00000 | 23.54611 | 46.10373 | -0.2421 | 6.79534 |
Maximum of Months | 514.00000 | 24.53358 | 50.78720 | 0.58088 | 12.61223 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.88878 | 44.79029 | 0.36969 | 9.37531 |
February | 385.00000 | 24.04565 | 45.56519 | 0.43069 | 10.10063 |
March | 433.00000 | 24.14903 | 46.60838 | 0.48199 | 11.00126 |
April | 410.00000 | 24.46792 | 48.26283 | 0.59642 | 13.33903 |
May | 430.00000 | 24.56871 | 50.37240 | -0.1597 | 7.00518 |
June | 418.00000 | 24.57525 | 49.97715 | -0.1429 | 6.89979 |
July | 422.00000 | 24.73150 | 48.77657 | -0.0900 | 7.24616 |
August | 433.00000 | 24.55105 | 50.08493 | -0.1601 | 6.98919 |
September | 410.00000 | 24.63054 | 49.43322 | -0.1420 | 7.13557 |
October | 427.00000 | 24.61717 | 50.02288 | 0.64793 | 14.73208 |
November | 417.00000 | 24.37060 | 49.55774 | 0.55358 | 12.17185 |
December | 422.00000 | 23.86957 | 48.06896 | 0.38586 | 9.70240 |
Annual Sum or Average | 5034.00000 | 24.37352 | 48.47763 | 0.22911 | 9.63277 |
Minimum of Months | 385.00000 | 23.86957 | 44.79029 | -0.1601 | 6.89979 |
Maximum of Months | 433.00000 | 24.73150 | 50.37240 | 0.64793 | 14.73208 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15642 | 43.09511 | 0.47515 | 11.46997 |
February | 454.00000 | 24.20929 | 44.44271 | 0.50310 | 11.79481 |
March | 514.00000 | 24.13577 | 46.05673 | 0.49094 | 11.14200 |
April | 485.00000 | 24.32077 | 48.75890 | 0.55103 | 11.91276 |
May | 508.00000 | 24.40958 | 50.85199 | -0.2455 | 7.15796 |
June | 496.00000 | 24.40496 | 50.53999 | -0.2367 | 6.97992 |
July | 497.00000 | 24.51020 | 49.58581 | -0.1987 | 6.85925 |
August | 514.00000 | 24.41953 | 50.33638 | -0.2192 | 6.94731 |
September | 485.00000 | 24.51679 | 49.45745 | -0.1721 | 6.96496 |
October | 502.00000 | 24.61070 | 49.24963 | 0.67242 | 15.43238 |
November | 489.00000 | 24.51381 | 48.22138 | 0.62477 | 14.24099 |
December | 497.00000 | 24.16415 | 45.70708 | 0.49985 | 12.13470 |
Annual Sum or Average | 5943.00000 | 24.36465 | 48.04922 | 0.22564 | 10.23314 |
Minimum of Months | 454.00000 | 24.13577 | 43.09511 | -0.2455 | 6.85925 |
Maximum of Months | 514.00000 | 24.61070 | 50.85199 | 0.67242 | 15.43238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.77635 | 45.54726 | 0.34851 | 8.81734 |
February | 454.00000 | 23.96162 | 46.07215 | 0.42055 | 10.22851 |
March | 514.00000 | 24.09355 | 46.87205 | 0.47895 | 11.04656 |
April | 485.00000 | 24.37384 | 48.79284 | 0.58690 | 12.94636 |
May | 508.00000 | 24.48397 | 50.67526 | -0.1742 | 6.91860 |
June | 496.00000 | 24.46513 | 50.44625 | -0.1794 | 6.82107 |
July | 497.00000 | 24.58385 | 49.43075 | -0.1322 | 6.83458 |
August | 514.00000 | 24.46526 | 50.35860 | -0.1723 | 6.81200 |
September | 485.00000 | 24.51689 | 49.95261 | -0.1747 | 7.04884 |
October | 502.00000 | 24.51650 | 50.33070 | 0.63337 | 14.20000 |
November | 489.00000 | 24.27975 | 49.96838 | 0.54152 | 11.87165 |
December | 497.00000 | 23.87677 | 47.97428 | 0.39899 | 9.86341 |
Annual Sum or Average | 5943.00000 | 24.28455 | 48.88521 | 0.21223 | 9.43588 |
Minimum of Months | 454.00000 | 23.77635 | 45.54726 | -0.1794 | 6.81200 |
Maximum of Months | 514.00000 | 24.58385 | 50.67526 | 0.63337 | 14.20000 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.486245E+11 | 0.107358E+11 | 420.08 | 0.355144E+11 | 0.131101E+11 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:05 | 83312.21 | 02-JAN-14:00 | 58467.58 | 02-JAN-15:05 | 32057.55 | 07-JAN-07:03 | 19388.71 | 02-JAN-14:10 | 0.00 |
February | 0.497638E+11 | 0.109546E+11 | 374.68 | 0.370304E+11 | 0.127334E+11 | 0.00 | 1.00 | 01-FEB-10:00 | 0.00 | 01-FEB-00:10 | 76209.59 | 18-FEB-07:03 | 54356.29 | 21-FEB-16:30 | 34691.39 | 13-FEB-06:12 | 16098.24 | 18-FEB-07:03 | 0.00 |
March | 0.602014E+11 | 0.132231E+11 | 434.83 | 0.436347E+11 | 0.165667E+11 | 0.00 | 1.00 | 01-MAR-11:05 | 0.00 | 01-MAR-00:10 | 87784.60 | 14-MAR-06:03 | 56953.88 | 27-MAR-15:40 | 41041.40 | 14-MAR-06:03 | 18432.45 | 14-MAR-06:03 | 0.00 |
April | 0.688958E+11 | 0.153697E+11 | 422.31 | 0.493688E+11 | 0.195271E+11 | 0.00 | 1.00 | 01-APR-05:12 | 0.00 | 01-APR-00:10 | 89183.64 | 12-APR-06:03 | 62738.68 | 17-APR-15:20 | 36260.21 | 13-APR-04:03 | 20190.57 | 14-APR-15:00 | 0.00 |
May | 0.932845E+11 | 0.213053E+11 | 459.42 | 0.621367E+11 | 0.311478E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 105969.76 | 31-MAY-06:03 | 74816.04 | 15-MAY-06:03 | 43130.76 | 24-MAY-05:03 | 22936.76 | 31-MAY-06:03 | 0.00 |
June | 0.105181E+12 | 0.240813E+11 | 462.64 | 0.654721E+11 | 0.397086E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 111599.65 | 08-JUN-06:03 | 76151.51 | 26-JUN-06:03 | 41780.78 | 07-JUN-04:03 | 25576.38 | 08-JUN-06:03 | 0.00 |
July | 0.111063E+12 | 0.259836E+11 | 474.53 | 0.692660E+11 | 0.417974E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 110105.36 | 11-JUL-06:03 | 77652.52 | 10-JUL-06:03 | 38851.11 | 22-JUL-05:03 | 24982.62 | 28-JUL-15:30 | 0.00 |
August | 0.114728E+12 | 0.266089E+11 | 479.91 | 0.713129E+11 | 0.434152E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 112765.26 | 18-AUG-04:03 | 78044.40 | 21-AUG-06:03 | 41312.90 | 21-AUG-12:03 | 25611.77 | 01-AUG-04:02 | 0.00 |
September | 0.105690E+12 | 0.242969E+11 | 463.99 | 0.661283E+11 | 0.395616E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 113458.60 | 19-SEP-04:02 | 77974.82 | 11-SEP-06:03 | 43018.80 | 23-SEP-04:03 | 25508.12 | 22-SEP-04:02 | 0.00 |
October | 0.971864E+11 | 0.220288E+11 | 458.78 | 0.635918E+11 | 0.335946E+11 | 0.00 | 1.00 | 01-OCT-09:43 | 0.00 | 01-OCT-00:10 | 114256.17 | 04-OCT-04:02 | 76290.07 | 02-OCT-06:03 | 45213.16 | 30-OCT-06:07 | 25065.08 | 03-OCT-04:02 | 0.00 |
November | 0.762765E+11 | 0.168626E+11 | 413.78 | 0.510111E+11 | 0.252654E+11 | 0.00 | 1.00 | 01-NOV-05:12 | 0.00 | 01-NOV-00:10 | 103262.71 | 04-NOV-04:03 | 70655.47 | 20-NOV-07:03 | 50397.42 | 04-NOV-04:03 | 21834.35 | 04-NOV-04:03 | 0.00 |
December | 0.521823E+11 | 0.114735E+11 | 413.32 | 0.368034E+11 | 0.153789E+11 | 0.00 | 1.00 | 01-DEC-06:12 | 0.00 | 01-DEC-00:10 | 94493.57 | 11-DEC-07:03 | 70047.94 | 11-DEC-07:03 | 36468.99 | 09-DEC-06:03 | 19955.95 | 11-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.983077E+12 | 0.222924E+12 | 5278.27 | 0.651270E+12 | 0.331807E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.486245E+11 | 0.107358E+11 | 374.68 | 0.355144E+11 | 0.127334E+11 | 0.00 | 1.00 | 0.00 | 76209.59 | 54356.29 | 32057.55 | 16098.24 | 0.00 | ||||||
Maximum of Months | 0.114728E+12 | 0.266089E+11 | 479.91 | 0.713129E+11 | 0.434152E+11 | 0.00 | 1.00 | 0.00 | 114256.17 | 78044.40 | 50397.42 | 25611.77 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.384415E+11 | 0.858899E+10 | 410.92 | 0.268582E+11 | 0.115833E+11 | 0.00 | 1.00 | 01-JAN-09:23 | 0.00 | 01-JAN-00:05 | 76829.92 | 02-JAN-14:00 | 52843.00 | 02-JAN-15:05 | 27322.12 | 14-JAN-06:03 | 17809.38 | 02-JAN-14:00 | 0.00 |
February | 0.410897E+11 | 0.911344E+10 | 373.39 | 0.294303E+11 | 0.116594E+11 | 0.00 | 1.00 | 01-FEB-11:50 | 0.00 | 01-FEB-00:10 | 62620.40 | 13-FEB-06:12 | 46782.16 | 21-FEB-15:05 | 30758.57 | 13-FEB-06:12 | 13976.32 | 11-FEB-15:05 | 0.00 |
March | 0.512012E+11 | 0.112958E+11 | 434.33 | 0.359481E+11 | 0.152531E+11 | 0.00 | 1.00 | 01-MAR-13:05 | 0.00 | 01-MAR-00:10 | 83517.85 | 06-MAR-07:03 | 50934.37 | 27-MAR-15:30 | 32670.68 | 06-MAR-07:03 | 17597.24 | 06-MAR-07:03 | 0.00 |
April | 0.601173E+11 | 0.134390E+11 | 424.39 | 0.419362E+11 | 0.181810E+11 | 0.00 | 1.00 | 01-APR-12:05 | 0.00 | 01-APR-00:10 | 78752.02 | 13-APR-05:03 | 56154.03 | 17-APR-14:05 | 30178.32 | 13-APR-05:03 | 18459.22 | 14-APR-14:05 | 0.00 |
May | 0.818727E+11 | 0.186212E+11 | 454.88 | 0.526934E+11 | 0.291793E+11 | 0.00 | 1.00 | 01-MAY-06:03 | 0.00 | 01-MAY-00:10 | 103554.12 | 30-MAY-04:02 | 68316.56 | 30-MAY-04:02 | 40541.21 | 27-MAY-05:03 | 23040.22 | 29-MAY-15:52 | 0.00 |
June | 0.930355E+11 | 0.211440E+11 | 454.36 | 0.557402E+11 | 0.372953E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 108290.88 | 19-JUN-04:03 | 68011.69 | 12-JUN-04:02 | 47416.80 | 19-JUN-04:03 | 23717.71 | 08-JUN-04:03 | 0.00 |
July | 0.977668E+11 | 0.226849E+11 | 462.37 | 0.587674E+11 | 0.389994E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 106412.91 | 03-JUL-04:02 | 68727.52 | 31-JUL-06:03 | 40554.35 | 03-JUL-04:02 | 23028.72 | 31-JUL-04:02 | 0.00 |
August | 0.988328E+11 | 0.227366E+11 | 469.32 | 0.588469E+11 | 0.399859E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 106613.47 | 14-AUG-05:12 | 69436.56 | 21-AUG-04:02 | 42775.26 | 14-AUG-05:12 | 23830.37 | 01-AUG-04:02 | 0.00 |
September | 0.909063E+11 | 0.207534E+11 | 448.88 | 0.544529E+11 | 0.364535E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 106391.36 | 19-SEP-04:02 | 69943.43 | 18-SEP-04:02 | 41640.96 | 22-SEP-04:02 | 23750.11 | 22-SEP-04:02 | 0.00 |
October | 0.811318E+11 | 0.183499E+11 | 437.94 | 0.512623E+11 | 0.298695E+11 | 0.00 | 1.00 | 01-OCT-10:20 | 0.00 | 01-OCT-00:10 | 108657.42 | 02-OCT-04:02 | 67214.09 | 10-OCT-04:02 | 46790.30 | 04-OCT-04:02 | 23542.18 | 02-OCT-04:02 | 0.00 |
November | 0.623768E+11 | 0.137967E+11 | 402.22 | 0.397756E+11 | 0.226012E+11 | 0.00 | 1.00 | 01-NOV-08:00 | 0.00 | 01-NOV-00:10 | 103014.66 | 04-NOV-05:03 | 59825.09 | 04-NOV-05:03 | 44694.54 | 30-NOV-06:03 | 22043.08 | 04-NOV-05:03 | 0.00 |
December | 0.422109E+11 | 0.936437E+10 | 408.54 | 0.282453E+11 | 0.139656E+11 | 0.00 | 1.00 | 01-DEC-08:50 | 0.00 | 01-DEC-00:10 | 83446.51 | 11-DEC-07:03 | 55905.34 | 11-DEC-07:03 | 30861.84 | 09-DEC-06:03 | 17619.85 | 11-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.838983E+12 | 0.189888E+12 | 5181.55 | 0.533957E+12 | 0.305027E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.384415E+11 | 0.858899E+10 | 373.39 | 0.268582E+11 | 0.115833E+11 | 0.00 | 1.00 | 0.00 | 62620.40 | 46782.16 | 27322.12 | 13976.32 | 0.00 | ||||||
Maximum of Months | 0.988328E+11 | 0.227366E+11 | 469.32 | 0.588469E+11 | 0.399859E+11 | 0.00 | 1.00 | 0.00 | 108657.42 | 69943.43 | 47416.80 | 23830.37 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.384854E+11 | 0.870726E+10 | 409.14 | 0.263376E+11 | 0.121478E+11 | 0.00 | 1.00 | 01-JAN-10:23 | 0.00 | 01-JAN-00:05 | 82248.03 | 02-JAN-14:00 | 57790.23 | 02-JAN-15:00 | 26621.27 | 02-JAN-14:00 | 19036.53 | 02-JAN-14:00 | 0.00 |
February | 0.424513E+11 | 0.950262E+10 | 372.50 | 0.302136E+11 | 0.122377E+11 | 0.00 | 1.00 | 01-FEB-13:20 | 0.00 | 01-FEB-00:10 | 66434.56 | 17-FEB-14:10 | 52217.90 | 22-FEB-16:00 | 25557.60 | 11-FEB-16:00 | 14834.95 | 17-FEB-14:10 | 0.00 |
March | 0.536299E+11 | 0.119132E+11 | 435.10 | 0.376981E+11 | 0.159318E+11 | 0.00 | 1.00 | 01-MAR-13:50 | 0.00 | 01-MAR-00:10 | 78289.39 | 27-MAR-15:00 | 59095.47 | 27-MAR-15:00 | 26374.09 | 14-MAR-09:50 | 17897.47 | 27-MAR-15:00 | 0.00 |
April | 0.645006E+11 | 0.145225E+11 | 427.48 | 0.455624E+11 | 0.189382E+11 | 0.00 | 1.00 | 01-APR-12:40 | 0.00 | 01-APR-00:10 | 94612.89 | 13-APR-05:03 | 70667.54 | 16-APR-14:13 | 37867.44 | 13-APR-05:03 | 20276.61 | 14-APR-15:00 | 0.00 |
May | 0.876219E+11 | 0.200375E+11 | 454.29 | 0.579767E+11 | 0.296453E+11 | 0.00 | 1.00 | 01-MAY-07:50 | 0.00 | 01-MAY-00:10 | 118348.15 | 30-MAY-04:02 | 78321.71 | 30-MAY-04:02 | 40635.86 | 27-MAY-05:03 | 27036.20 | 29-MAY-15:52 | 0.00 |
June | 0.995949E+11 | 0.227390E+11 | 457.83 | 0.617948E+11 | 0.378000E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 114651.12 | 25-JUN-13:43 | 79130.28 | 12-JUN-04:02 | 50165.78 | 19-JUN-04:03 | 26530.58 | 25-JUN-13:43 | 0.00 |
July | 0.104801E+12 | 0.244509E+11 | 465.87 | 0.653685E+11 | 0.394325E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 119450.43 | 03-JUL-04:02 | 79342.50 | 10-JUL-04:02 | 44447.63 | 03-JUL-04:02 | 25843.27 | 04-JUL-12:53 | 0.00 |
August | 0.104511E+12 | 0.241536E+11 | 469.68 | 0.641939E+11 | 0.403170E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 118517.54 | 01-AUG-04:02 | 80421.76 | 21-AUG-04:02 | 46435.69 | 13-AUG-14:13 | 27967.99 | 20-AUG-13:32 | 0.00 |
September | 0.958605E+11 | 0.219983E+11 | 450.74 | 0.590326E+11 | 0.368279E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 120856.94 | 19-SEP-04:02 | 81156.57 | 18-SEP-04:02 | 48995.89 | 22-SEP-04:02 | 26958.27 | 22-SEP-04:02 | 0.00 |
October | 0.841260E+11 | 0.191222E+11 | 437.83 | 0.538253E+11 | 0.303007E+11 | 0.00 | 1.00 | 01-OCT-10:20 | 0.00 | 01-OCT-00:10 | 122371.53 | 02-OCT-04:02 | 73118.32 | 30-OCT-04:02 | 52372.61 | 02-OCT-04:02 | 26634.90 | 02-OCT-04:02 | 0.00 |
November | 0.640377E+11 | 0.142615E+11 | 401.42 | 0.408494E+11 | 0.231884E+11 | 0.00 | 1.00 | 01-NOV-09:20 | 0.00 | 01-NOV-00:10 | 103538.05 | 04-NOV-05:03 | 58207.12 | 04-NOV-05:03 | 45330.93 | 04-NOV-05:03 | 22140.90 | 04-NOV-05:03 | 0.00 |
December | 0.426340E+11 | 0.955814E+10 | 405.60 | 0.281150E+11 | 0.145190E+11 | 0.00 | 1.00 | 01-DEC-10:00 | 0.00 | 01-DEC-00:10 | 74640.41 | 08-DEC-15:50 | 52435.14 | 08-DEC-15:30 | 29810.33 | 25-DEC-15:32 | 16781.33 | 08-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.882254E+12 | 0.200967E+12 | 5187.49 | 0.570968E+12 | 0.311286E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.384854E+11 | 0.870726E+10 | 372.50 | 0.263376E+11 | 0.121478E+11 | 0.00 | 1.00 | 0.00 | 66434.56 | 52217.90 | 25557.60 | 14834.95 | 0.00 | ||||||
Maximum of Months | 0.104801E+12 | 0.244509E+11 | 469.68 | 0.653685E+11 | 0.403170E+11 | 0.00 | 1.00 | 0.00 | 122371.53 | 81156.57 | 52372.61 | 27967.99 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.75 | 0.00 | 287.75 | 320.27 | 653.70 | 0.00 | 0.00 | 0.00 |
February | 340.59 | 0.00 | 340.59 | 476.22 | 541.91 | 0.00 | 0.00 | 0.00 |
March | 406.18 | 0.00 | 406.18 | 560.97 | 456.84 | 0.00 | 0.00 | 0.00 |
April | 455.15 | 2.04 | 453.10 | 778.18 | 298.26 | 0.00 | 0.00 | 0.00 |
May | 519.75 | 23.25 | 496.50 | 1074.56 | 156.61 | 0.00 | 0.00 | 0.00 |
June | 555.21 | 39.98 | 515.23 | 1238.40 | 71.72 | 0.00 | 0.00 | 0.00 |
July | 561.85 | 27.53 | 534.32 | 1312.65 | 105.51 | 0.00 | 0.00 | 0.00 |
August | 497.25 | 4.57 | 492.67 | 1108.18 | 69.86 | 0.00 | 0.00 | 0.00 |
September | 441.12 | 0.03 | 441.08 | 1019.55 | 114.48 | 0.00 | 0.00 | 0.00 |
October | 369.55 | 0.00 | 369.55 | 754.12 | 180.39 | 0.00 | 0.00 | 0.00 |
November | 321.33 | 0.00 | 321.33 | 535.87 | 337.60 | 0.00 | 0.00 | 0.00 |
December | 284.62 | 0.00 | 284.62 | 359.97 | 552.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.43 | 8.16 | 412.27 | 796.46 | 293.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 284.62 | 0.00 | 284.62 | 320.27 | 69.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 561.85 | 39.98 | 534.32 | 1312.65 | 653.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 461.90 | 221.28 | 240.62 | 674.09 | 416.27 | 0.00 | 0.00 | 0.00 |
February | 533.34 | 246.88 | 286.46 | 841.10 | 345.09 | 0.00 | 0.00 | 0.00 |
March | 651.17 | 307.84 | 343.32 | 1024.49 | 286.62 | 0.00 | 0.00 | 0.00 |
April | 706.68 | 315.32 | 391.36 | 1242.14 | 201.24 | 0.00 | 0.00 | 0.00 |
May | 668.55 | 266.23 | 402.32 | 1287.88 | 101.90 | 0.00 | 0.00 | 0.00 |
June | 659.87 | 253.45 | 406.42 | 1338.27 | 47.45 | 0.00 | 0.00 | 0.00 |
July | 678.02 | 244.51 | 433.51 | 1422.39 | 72.20 | 0.00 | 0.00 | 0.00 |
August | 619.99 | 207.31 | 412.68 | 1265.80 | 46.40 | 0.00 | 0.00 | 0.00 |
September | 597.71 | 216.08 | 381.64 | 1235.56 | 77.64 | 0.00 | 0.00 | 0.00 |
October | 550.17 | 236.94 | 313.23 | 1055.85 | 120.96 | 0.00 | 0.00 | 0.00 |
November | 446.54 | 178.05 | 268.48 | 769.59 | 215.90 | 0.00 | 0.00 | 0.00 |
December | 360.70 | 127.35 | 233.36 | 538.89 | 358.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 577.98 | 234.95 | 343.04 | 1058.82 | 190.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 360.70 | 127.35 | 233.36 | 538.89 | 46.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 706.68 | 315.32 | 433.51 | 1422.39 | 416.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1352.39 | 878.62 | 473.77 | 2184.54 | 642.60 | 0.00 | 0.00 | 0.00 |
February | 1223.44 | 707.91 | 515.53 | 2087.21 | 542.43 | 0.00 | 0.00 | 0.00 |
March | 939.32 | 397.14 | 542.18 | 1619.30 | 454.00 | 0.00 | 0.00 | 0.00 |
April | 638.72 | 112.01 | 526.71 | 1210.88 | 310.33 | 0.00 | 0.00 | 0.00 |
May | 511.83 | 11.07 | 500.76 | 1062.67 | 152.85 | 0.00 | 0.00 | 0.00 |
June | 487.99 | 0.92 | 487.07 | 1094.10 | 72.87 | 0.00 | 0.00 | 0.00 |
July | 522.50 | 4.84 | 517.66 | 1227.70 | 105.28 | 0.00 | 0.00 | 0.00 |
August | 593.02 | 50.04 | 542.98 | 1329.90 | 70.59 | 0.00 | 0.00 | 0.00 |
September | 759.15 | 186.03 | 573.12 | 1688.43 | 120.53 | 0.00 | 0.00 | 0.00 |
October | 1043.98 | 489.80 | 554.18 | 2059.48 | 198.21 | 0.00 | 0.00 | 0.00 |
November | 1187.82 | 662.94 | 524.89 | 2107.41 | 346.64 | 0.00 | 0.00 | 0.00 |
December | 1303.33 | 822.07 | 481.26 | 2154.67 | 560.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 878.70 | 358.74 | 519.96 | 1650.01 | 297.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 487.99 | 0.92 | 473.77 | 1062.67 | 70.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1352.39 | 878.62 | 573.12 | 2184.54 | 642.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.94 | 178.89 | 236.05 | 614.47 | 441.27 | 0.00 | 0.00 | 0.00 |
February | 518.87 | 234.82 | 284.05 | 850.30 | 375.06 | 0.00 | 0.00 | 0.00 |
March | 646.15 | 295.07 | 351.09 | 1055.11 | 319.07 | 0.00 | 0.00 | 0.00 |
April | 711.23 | 329.32 | 381.91 | 1267.52 | 219.14 | 0.00 | 0.00 | 0.00 |
May | 648.38 | 249.59 | 398.78 | 1265.21 | 117.15 | 0.00 | 0.00 | 0.00 |
June | 549.37 | 154.10 | 395.27 | 1141.38 | 54.46 | 0.00 | 0.00 | 0.00 |
July | 613.97 | 189.94 | 424.03 | 1309.68 | 78.00 | 0.00 | 0.00 | 0.00 |
August | 612.58 | 199.64 | 412.94 | 1253.23 | 54.42 | 0.00 | 0.00 | 0.00 |
September | 522.56 | 154.09 | 368.48 | 1100.23 | 82.12 | 0.00 | 0.00 | 0.00 |
October | 519.85 | 202.65 | 317.20 | 1009.77 | 134.24 | 0.00 | 0.00 | 0.00 |
November | 428.82 | 157.30 | 271.53 | 758.42 | 236.66 | 0.00 | 0.00 | 0.00 |
December | 429.59 | 192.07 | 237.52 | 676.53 | 376.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 551.61 | 211.40 | 340.21 | 1026.13 | 206.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.94 | 154.09 | 236.05 | 614.47 | 54.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.23 | 329.32 | 424.03 | 1309.68 | 441.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.91 | 0.00 | 95.91 | 102.63 | 244.29 | 0.00 | 0.00 | 0.00 |
February | 113.53 | 0.00 | 113.53 | 157.55 | 198.26 | 0.00 | 0.00 | 0.00 |
March | 135.39 | 0.00 | 135.39 | 191.07 | 160.43 | 0.00 | 0.00 | 0.00 |
April | 151.71 | 0.68 | 151.03 | 266.03 | 101.11 | 0.00 | 0.00 | 0.00 |
May | 173.24 | 7.75 | 165.49 | 365.14 | 51.56 | 0.00 | 0.00 | 0.00 |
June | 185.06 | 13.32 | 171.74 | 420.39 | 22.63 | 0.00 | 0.00 | 0.00 |
July | 187.28 | 9.18 | 178.10 | 443.58 | 34.79 | 0.00 | 0.00 | 0.00 |
August | 165.74 | 1.52 | 164.22 | 371.42 | 24.96 | 0.00 | 0.00 | 0.00 |
September | 147.03 | 0.01 | 147.02 | 342.29 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 123.18 | 0.00 | 123.18 | 252.10 | 66.26 | 0.00 | 0.00 | 0.00 |
November | 107.10 | 0.00 | 107.10 | 176.78 | 127.86 | 0.00 | 0.00 | 0.00 |
December | 94.87 | 0.00 | 94.87 | 115.55 | 209.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.14 | 2.72 | 137.42 | 267.57 | 106.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.87 | 0.00 | 94.87 | 102.63 | 22.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.28 | 13.32 | 178.10 | 443.58 | 244.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.91 | 0.00 | 95.91 | 102.64 | 244.30 | 0.00 | 0.00 | 0.00 |
February | 113.53 | 0.00 | 113.53 | 157.56 | 198.27 | 0.00 | 0.00 | 0.00 |
March | 135.39 | 0.00 | 135.39 | 191.07 | 160.44 | 0.00 | 0.00 | 0.00 |
April | 151.71 | 0.68 | 151.03 | 266.04 | 101.11 | 0.00 | 0.00 | 0.00 |
May | 173.25 | 7.75 | 165.50 | 365.16 | 51.56 | 0.00 | 0.00 | 0.00 |
June | 185.07 | 13.33 | 171.74 | 420.41 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 187.28 | 9.18 | 178.11 | 443.60 | 34.79 | 0.00 | 0.00 | 0.00 |
August | 165.75 | 1.52 | 164.22 | 371.44 | 24.96 | 0.00 | 0.00 | 0.00 |
September | 147.04 | 0.01 | 147.03 | 342.30 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 123.18 | 0.00 | 123.18 | 252.11 | 66.26 | 0.00 | 0.00 | 0.00 |
November | 107.11 | 0.00 | 107.11 | 176.79 | 127.86 | 0.00 | 0.00 | 0.00 |
December | 94.87 | 0.00 | 94.87 | 115.55 | 209.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.14 | 2.72 | 137.42 | 267.58 | 106.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.87 | 0.00 | 94.87 | 102.64 | 22.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.28 | 13.33 | 178.11 | 443.60 | 244.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.91 | 0.00 | 95.91 | 102.64 | 244.30 | 0.00 | 0.00 | 0.00 |
February | 113.53 | 0.00 | 113.53 | 157.56 | 198.27 | 0.00 | 0.00 | 0.00 |
March | 135.39 | 0.00 | 135.39 | 191.07 | 160.44 | 0.00 | 0.00 | 0.00 |
April | 151.71 | 0.68 | 151.03 | 266.04 | 101.11 | 0.00 | 0.00 | 0.00 |
May | 173.25 | 7.75 | 165.50 | 365.16 | 51.56 | 0.00 | 0.00 | 0.00 |
June | 185.07 | 13.33 | 171.74 | 420.41 | 22.64 | 0.00 | 0.00 | 0.00 |
July | 187.28 | 9.18 | 178.11 | 443.60 | 34.79 | 0.00 | 0.00 | 0.00 |
August | 165.75 | 1.52 | 164.22 | 371.44 | 24.96 | 0.00 | 0.00 | 0.00 |
September | 147.04 | 0.01 | 147.03 | 342.30 | 41.08 | 0.00 | 0.00 | 0.00 |
October | 123.18 | 0.00 | 123.18 | 252.11 | 66.26 | 0.00 | 0.00 | 0.00 |
November | 107.11 | 0.00 | 107.11 | 176.79 | 127.86 | 0.00 | 0.00 | 0.00 |
December | 94.87 | 0.00 | 94.87 | 115.55 | 209.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.14 | 2.72 | 137.42 | 267.58 | 106.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.87 | 0.00 | 94.87 | 102.64 | 22.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.28 | 13.33 | 178.11 | 443.60 | 244.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 444.32 | 212.86 | 231.47 | 639.94 | 454.75 | 0.00 | 0.00 | 0.00 |
February | 513.05 | 237.49 | 275.56 | 808.75 | 371.31 | 0.00 | 0.00 | 0.00 |
March | 626.39 | 296.13 | 330.26 | 996.64 | 298.98 | 0.00 | 0.00 | 0.00 |
April | 679.79 | 303.32 | 376.47 | 1211.73 | 206.43 | 0.00 | 0.00 | 0.00 |
May | 643.11 | 256.10 | 387.01 | 1255.45 | 103.07 | 0.00 | 0.00 | 0.00 |
June | 634.76 | 243.81 | 390.96 | 1301.75 | 46.91 | 0.00 | 0.00 | 0.00 |
July | 652.22 | 235.20 | 417.02 | 1380.30 | 73.97 | 0.00 | 0.00 | 0.00 |
August | 596.40 | 199.42 | 396.98 | 1222.16 | 52.41 | 0.00 | 0.00 | 0.00 |
September | 574.97 | 207.85 | 367.12 | 1193.43 | 84.44 | 0.00 | 0.00 | 0.00 |
October | 529.24 | 227.92 | 301.32 | 1019.37 | 135.15 | 0.00 | 0.00 | 0.00 |
November | 429.55 | 171.28 | 258.27 | 738.01 | 239.73 | 0.00 | 0.00 | 0.00 |
December | 346.98 | 122.50 | 224.48 | 510.99 | 394.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 555.99 | 226.00 | 329.99 | 1024.01 | 204.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 346.98 | 122.50 | 224.48 | 510.99 | 46.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 679.79 | 303.32 | 417.02 | 1380.30 | 454.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.57 | 8.42 | 9.15 | 25.30 | 17.98 | 0.00 | 0.00 | 0.00 |
February | 20.29 | 9.39 | 10.90 | 31.98 | 14.68 | 0.00 | 0.00 | 0.00 |
March | 24.77 | 11.71 | 13.06 | 39.41 | 11.82 | 0.00 | 0.00 | 0.00 |
April | 26.88 | 11.99 | 14.89 | 47.91 | 8.16 | 0.00 | 0.00 | 0.00 |
May | 25.43 | 10.13 | 15.30 | 49.64 | 4.08 | 0.00 | 0.00 | 0.00 |
June | 25.10 | 9.64 | 15.46 | 51.47 | 1.85 | 0.00 | 0.00 | 0.00 |
July | 25.79 | 9.30 | 16.49 | 54.58 | 2.92 | 0.00 | 0.00 | 0.00 |
August | 23.58 | 7.89 | 15.70 | 48.32 | 2.07 | 0.00 | 0.00 | 0.00 |
September | 22.73 | 8.22 | 14.52 | 47.19 | 3.34 | 0.00 | 0.00 | 0.00 |
October | 20.93 | 9.01 | 11.91 | 40.30 | 5.34 | 0.00 | 0.00 | 0.00 |
November | 16.98 | 6.77 | 10.21 | 29.18 | 9.48 | 0.00 | 0.00 | 0.00 |
December | 13.72 | 4.84 | 8.88 | 20.20 | 15.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.98 | 8.94 | 13.05 | 40.49 | 8.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.72 | 4.84 | 8.88 | 20.20 | 1.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.88 | 11.99 | 16.49 | 54.58 | 17.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.79 | 292.87 | 157.92 | 727.75 | 246.40 | 0.00 | 0.00 | 0.00 |
February | 407.81 | 235.96 | 171.84 | 698.15 | 204.53 | 0.00 | 0.00 | 0.00 |
March | 313.10 | 132.38 | 180.73 | 547.48 | 163.13 | 0.00 | 0.00 | 0.00 |
April | 212.91 | 37.33 | 175.57 | 410.94 | 107.42 | 0.00 | 0.00 | 0.00 |
May | 170.61 | 3.69 | 166.92 | 359.87 | 51.19 | 0.00 | 0.00 | 0.00 |
June | 162.66 | 0.31 | 162.35 | 369.97 | 23.08 | 0.00 | 0.00 | 0.00 |
July | 174.17 | 1.61 | 172.55 | 412.22 | 35.26 | 0.00 | 0.00 | 0.00 |
August | 197.67 | 16.68 | 180.99 | 441.72 | 26.79 | 0.00 | 0.00 | 0.00 |
September | 253.05 | 62.01 | 191.04 | 560.58 | 45.95 | 0.00 | 0.00 | 0.00 |
October | 347.99 | 163.26 | 184.72 | 684.44 | 79.83 | 0.00 | 0.00 | 0.00 |
November | 395.93 | 220.97 | 174.96 | 701.35 | 137.33 | 0.00 | 0.00 | 0.00 |
December | 434.43 | 274.02 | 160.42 | 718.68 | 216.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292.89 | 119.58 | 173.32 | 552.03 | 111.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.66 | 0.31 | 157.92 | 359.87 | 23.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 450.79 | 292.87 | 191.04 | 727.75 | 246.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.79 | 292.87 | 157.92 | 727.75 | 246.40 | 0.00 | 0.00 | 0.00 |
February | 407.81 | 235.96 | 171.84 | 698.15 | 204.53 | 0.00 | 0.00 | 0.00 |
March | 313.10 | 132.38 | 180.73 | 547.48 | 163.13 | 0.00 | 0.00 | 0.00 |
April | 212.91 | 37.33 | 175.57 | 410.94 | 107.42 | 0.00 | 0.00 | 0.00 |
May | 170.61 | 3.69 | 166.92 | 359.87 | 51.19 | 0.00 | 0.00 | 0.00 |
June | 162.66 | 0.31 | 162.35 | 369.97 | 23.08 | 0.00 | 0.00 | 0.00 |
July | 174.17 | 1.61 | 172.55 | 412.22 | 35.26 | 0.00 | 0.00 | 0.00 |
August | 197.67 | 16.68 | 180.99 | 441.72 | 26.79 | 0.00 | 0.00 | 0.00 |
September | 253.05 | 62.01 | 191.04 | 560.58 | 45.95 | 0.00 | 0.00 | 0.00 |
October | 347.99 | 163.26 | 184.72 | 684.44 | 79.83 | 0.00 | 0.00 | 0.00 |
November | 395.93 | 220.97 | 174.96 | 701.35 | 137.33 | 0.00 | 0.00 | 0.00 |
December | 434.43 | 274.02 | 160.42 | 718.68 | 216.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292.89 | 119.58 | 173.32 | 552.03 | 111.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.66 | 0.31 | 157.92 | 359.87 | 23.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 450.79 | 292.87 | 191.04 | 727.75 | 246.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.76 | 292.85 | 157.91 | 727.70 | 246.38 | 0.00 | 0.00 | 0.00 |
February | 407.78 | 235.95 | 171.83 | 698.11 | 204.52 | 0.00 | 0.00 | 0.00 |
March | 313.08 | 132.37 | 180.71 | 547.45 | 163.12 | 0.00 | 0.00 | 0.00 |
April | 212.89 | 37.33 | 175.56 | 410.92 | 107.42 | 0.00 | 0.00 | 0.00 |
May | 170.60 | 3.69 | 166.91 | 359.85 | 51.18 | 0.00 | 0.00 | 0.00 |
June | 162.65 | 0.31 | 162.34 | 369.95 | 23.07 | 0.00 | 0.00 | 0.00 |
July | 174.16 | 1.61 | 172.54 | 412.20 | 35.25 | 0.00 | 0.00 | 0.00 |
August | 197.66 | 16.68 | 180.98 | 441.69 | 26.79 | 0.00 | 0.00 | 0.00 |
September | 253.03 | 62.01 | 191.03 | 560.55 | 45.95 | 0.00 | 0.00 | 0.00 |
October | 347.97 | 163.25 | 184.71 | 684.40 | 79.83 | 0.00 | 0.00 | 0.00 |
November | 395.91 | 220.96 | 174.95 | 701.30 | 137.32 | 0.00 | 0.00 | 0.00 |
December | 434.41 | 274.00 | 160.41 | 718.64 | 216.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 292.88 | 119.57 | 173.31 | 551.99 | 111.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.65 | 0.31 | 157.91 | 359.85 | 23.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 450.76 | 292.85 | 191.03 | 727.70 | 246.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 399.15 | 172.08 | 227.07 | 585.45 | 483.81 | 0.00 | 0.00 | 0.00 |
February | 499.13 | 225.88 | 273.25 | 818.29 | 403.71 | 0.00 | 0.00 | 0.00 |
March | 621.57 | 283.84 | 337.73 | 1025.04 | 334.47 | 0.00 | 0.00 | 0.00 |
April | 684.17 | 316.79 | 367.38 | 1233.10 | 224.52 | 0.00 | 0.00 | 0.00 |
May | 623.71 | 240.10 | 383.61 | 1231.76 | 118.12 | 0.00 | 0.00 | 0.00 |
June | 528.47 | 148.24 | 380.23 | 1111.50 | 52.35 | 0.00 | 0.00 | 0.00 |
July | 590.61 | 182.72 | 407.90 | 1270.97 | 79.48 | 0.00 | 0.00 | 0.00 |
August | 589.27 | 192.04 | 397.23 | 1210.52 | 60.53 | 0.00 | 0.00 | 0.00 |
September | 502.68 | 148.22 | 354.46 | 1063.11 | 89.04 | 0.00 | 0.00 | 0.00 |
October | 500.07 | 194.94 | 305.13 | 974.19 | 147.90 | 0.00 | 0.00 | 0.00 |
November | 412.51 | 151.31 | 261.20 | 728.38 | 262.23 | 0.00 | 0.00 | 0.00 |
December | 413.25 | 184.76 | 228.49 | 644.99 | 416.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 530.62 | 203.36 | 327.26 | 992.40 | 221.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 399.15 | 148.22 | 227.07 | 585.45 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 684.17 | 316.79 | 407.90 | 1270.97 | 483.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.78 | 6.80 | 8.98 | 23.15 | 19.13 | 0.00 | 0.00 | 0.00 |
February | 19.74 | 8.93 | 10.80 | 32.35 | 15.96 | 0.00 | 0.00 | 0.00 |
March | 24.58 | 11.22 | 13.35 | 40.53 | 13.22 | 0.00 | 0.00 | 0.00 |
April | 27.05 | 12.53 | 14.53 | 48.76 | 8.88 | 0.00 | 0.00 | 0.00 |
May | 24.66 | 9.49 | 15.17 | 48.70 | 4.67 | 0.00 | 0.00 | 0.00 |
June | 20.90 | 5.86 | 15.03 | 43.95 | 2.07 | 0.00 | 0.00 | 0.00 |
July | 23.35 | 7.22 | 16.13 | 50.25 | 3.14 | 0.00 | 0.00 | 0.00 |
August | 23.30 | 7.59 | 15.71 | 47.86 | 2.39 | 0.00 | 0.00 | 0.00 |
September | 19.88 | 5.86 | 14.01 | 42.03 | 3.52 | 0.00 | 0.00 | 0.00 |
October | 19.77 | 7.71 | 12.06 | 38.52 | 5.85 | 0.00 | 0.00 | 0.00 |
November | 16.31 | 5.98 | 10.33 | 28.80 | 10.37 | 0.00 | 0.00 | 0.00 |
December | 16.34 | 7.31 | 9.03 | 25.50 | 16.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.98 | 8.04 | 12.94 | 39.24 | 8.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.78 | 5.86 | 8.98 | 23.15 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.05 | 12.53 | 16.13 | 50.25 | 19.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 287.75 | 0.00 | 287.75 | 309.50 | 712.50 | 0.00 | 0.00 | 0.00 |
February | 340.59 | 0.00 | 340.59 | 470.32 | 585.86 | 0.00 | 0.00 | 0.00 |
March | 406.18 | 0.00 | 406.18 | 561.50 | 488.02 | 0.00 | 0.00 | 0.00 |
April | 455.15 | 2.04 | 453.10 | 785.61 | 312.78 | 0.00 | 0.00 | 0.00 |
May | 519.75 | 23.25 | 496.50 | 1086.25 | 160.31 | 0.00 | 0.00 | 0.00 |
June | 555.21 | 39.98 | 515.23 | 1253.18 | 72.19 | 0.00 | 0.00 | 0.00 |
July | 561.85 | 27.53 | 534.32 | 1328.81 | 105.89 | 0.00 | 0.00 | 0.00 |
August | 497.25 | 4.57 | 492.67 | 1119.28 | 71.64 | 0.00 | 0.00 | 0.00 |
September | 441.12 | 0.03 | 441.08 | 1032.21 | 118.72 | 0.00 | 0.00 | 0.00 |
October | 369.55 | 0.00 | 369.55 | 759.80 | 191.81 | 0.00 | 0.00 | 0.00 |
November | 321.33 | 0.00 | 321.33 | 534.36 | 366.54 | 0.00 | 0.00 | 0.00 |
December | 284.62 | 0.00 | 284.62 | 351.32 | 601.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 420.43 | 8.16 | 412.27 | 800.93 | 314.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 284.62 | 0.00 | 284.62 | 309.50 | 71.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 561.85 | 39.98 | 534.32 | 1328.81 | 712.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 461.90 | 221.28 | 240.62 | 662.86 | 449.03 | 0.00 | 0.00 | 0.00 |
February | 533.34 | 246.88 | 286.46 | 833.31 | 370.26 | 0.00 | 0.00 | 0.00 |
March | 651.17 | 307.84 | 343.32 | 1022.23 | 303.69 | 0.00 | 0.00 | 0.00 |
April | 706.68 | 315.32 | 391.36 | 1244.91 | 210.76 | 0.00 | 0.00 | 0.00 |
May | 668.55 | 266.23 | 402.32 | 1293.04 | 105.11 | 0.00 | 0.00 | 0.00 |
June | 659.87 | 253.45 | 406.42 | 1344.28 | 48.15 | 0.00 | 0.00 | 0.00 |
July | 678.02 | 244.51 | 433.51 | 1429.47 | 72.91 | 0.00 | 0.00 | 0.00 |
August | 619.99 | 207.31 | 412.68 | 1269.44 | 48.09 | 0.00 | 0.00 | 0.00 |
September | 597.71 | 216.08 | 381.64 | 1240.49 | 80.48 | 0.00 | 0.00 | 0.00 |
October | 550.17 | 236.94 | 313.23 | 1056.83 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 446.54 | 178.05 | 268.48 | 765.12 | 232.58 | 0.00 | 0.00 | 0.00 |
December | 360.70 | 127.35 | 233.36 | 529.85 | 387.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 577.98 | 234.95 | 343.04 | 1058.50 | 202.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 360.70 | 127.35 | 233.36 | 529.85 | 48.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 706.68 | 315.32 | 433.51 | 1429.47 | 449.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1352.39 | 878.62 | 473.77 | 2174.18 | 690.87 | 0.00 | 0.00 | 0.00 |
February | 1223.44 | 707.91 | 515.53 | 2082.72 | 580.36 | 0.00 | 0.00 | 0.00 |
March | 939.32 | 397.14 | 542.18 | 1622.13 | 481.67 | 0.00 | 0.00 | 0.00 |
April | 638.72 | 112.01 | 526.71 | 1219.68 | 324.99 | 0.00 | 0.00 | 0.00 |
May | 511.83 | 11.07 | 500.76 | 1074.97 | 157.48 | 0.00 | 0.00 | 0.00 |
June | 487.99 | 0.92 | 487.07 | 1108.61 | 73.61 | 0.00 | 0.00 | 0.00 |
July | 522.50 | 4.84 | 517.66 | 1243.88 | 105.79 | 0.00 | 0.00 | 0.00 |
August | 593.02 | 50.04 | 542.98 | 1341.79 | 72.55 | 0.00 | 0.00 | 0.00 |
September | 759.15 | 186.03 | 573.12 | 1702.02 | 124.73 | 0.00 | 0.00 | 0.00 |
October | 1043.98 | 489.80 | 554.18 | 2065.89 | 209.34 | 0.00 | 0.00 | 0.00 |
November | 1187.82 | 662.94 | 524.89 | 2105.92 | 371.33 | 0.00 | 0.00 | 0.00 |
December | 1303.33 | 822.07 | 481.26 | 2148.77 | 602.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 878.70 | 358.74 | 519.96 | 1655.41 | 315.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 487.99 | 0.92 | 473.77 | 1074.97 | 72.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1352.39 | 878.62 | 573.12 | 2174.18 | 690.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.94 | 178.89 | 236.05 | 608.87 | 479.02 | 0.00 | 0.00 | 0.00 |
February | 518.87 | 234.82 | 284.05 | 848.11 | 403.25 | 0.00 | 0.00 | 0.00 |
March | 646.15 | 295.07 | 351.09 | 1057.57 | 339.40 | 0.00 | 0.00 | 0.00 |
April | 711.23 | 329.32 | 381.91 | 1273.82 | 229.14 | 0.00 | 0.00 | 0.00 |
May | 648.38 | 249.59 | 398.78 | 1274.11 | 120.14 | 0.00 | 0.00 | 0.00 |
June | 549.37 | 154.10 | 395.27 | 1151.33 | 54.91 | 0.00 | 0.00 | 0.00 |
July | 613.97 | 189.94 | 424.03 | 1320.60 | 78.74 | 0.00 | 0.00 | 0.00 |
August | 612.58 | 199.64 | 412.94 | 1261.42 | 55.63 | 0.00 | 0.00 | 0.00 |
September | 522.56 | 154.09 | 368.48 | 1108.91 | 84.88 | 0.00 | 0.00 | 0.00 |
October | 519.85 | 202.65 | 317.20 | 1014.52 | 141.68 | 0.00 | 0.00 | 0.00 |
November | 428.82 | 157.30 | 271.53 | 758.63 | 255.06 | 0.00 | 0.00 | 0.00 |
December | 429.59 | 192.07 | 237.52 | 672.44 | 406.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 551.61 | 211.40 | 340.21 | 1030.20 | 219.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 414.94 | 154.09 | 236.05 | 608.87 | 54.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.23 | 329.32 | 424.03 | 1320.60 | 479.02 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770701E+09 | 0.00 | 0.770701E+09 | 0.857822E+09 | 0.175087E+10 |
February | 0.823965E+09 | 0.00 | 0.823965E+09 | 0.115208E+10 | 0.131100E+10 |
March | 0.108792E+10 | 0.00 | 0.108792E+10 | 0.150249E+10 | 0.122361E+10 |
April | 0.117974E+10 | 5299525.40 | 0.117444E+10 | 0.201705E+10 | 0.773084E+09 |
May | 0.139211E+10 | 62272328.66 | 0.132984E+10 | 0.287809E+10 | 0.419464E+09 |
June | 0.143910E+10 | 0.103620E+09 | 0.133548E+10 | 0.320992E+10 | 0.185897E+09 |
July | 0.150487E+10 | 73741369.08 | 0.143112E+10 | 0.351581E+10 | 0.282608E+09 |
August | 0.133183E+10 | 12249154.86 | 0.131958E+10 | 0.296815E+10 | 0.187101E+09 |
September | 0.114338E+10 | 90452.03 | 0.114329E+10 | 0.264266E+10 | 0.296735E+09 |
October | 0.989802E+09 | 0.00 | 0.989802E+09 | 0.201983E+10 | 0.483165E+09 |
November | 0.832876E+09 | 0.00 | 0.832876E+09 | 0.138899E+10 | 0.875054E+09 |
December | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.964140E+09 | 0.148064E+10 |
Annual Sum or Average | 0.132586E+11 | 0.257273E+09 | 0.130013E+11 | 0.251170E+11 | 0.926922E+10 |
Minimum of Months | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.857822E+09 | 0.185897E+09 |
Maximum of Months | 0.150487E+10 | 0.103620E+09 | 0.143112E+10 | 0.351581E+10 | 0.175087E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123715E+10 | 0.592673E+09 | 0.644480E+09 | 0.180548E+10 | 0.111494E+10 |
February | 0.129026E+10 | 0.597264E+09 | 0.692996E+09 | 0.203478E+10 | 0.834833E+09 |
March | 0.174409E+10 | 0.824532E+09 | 0.919560E+09 | 0.274399E+10 | 0.767689E+09 |
April | 0.183172E+10 | 0.817307E+09 | 0.101442E+10 | 0.321962E+10 | 0.521607E+09 |
May | 0.179065E+10 | 0.713077E+09 | 0.107757E+10 | 0.344946E+10 | 0.272938E+09 |
June | 0.171038E+10 | 0.656947E+09 | 0.105344E+10 | 0.346880E+10 | 0.122978E+09 |
July | 0.181602E+10 | 0.654893E+09 | 0.116112E+10 | 0.380974E+10 | 0.193370E+09 |
August | 0.166059E+10 | 0.555266E+09 | 0.110532E+10 | 0.339031E+10 | 0.124290E+09 |
September | 0.154927E+10 | 0.560069E+09 | 0.989205E+09 | 0.320257E+10 | 0.201246E+09 |
October | 0.147358E+10 | 0.634613E+09 | 0.838965E+09 | 0.282798E+10 | 0.323967E+09 |
November | 0.115742E+10 | 0.461509E+09 | 0.695913E+09 | 0.199478E+10 | 0.559610E+09 |
December | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.144337E+10 | 0.959421E+09 |
Annual Sum or Average | 0.182272E+11 | 0.740923E+10 | 0.108180E+11 | 0.333909E+11 | 0.599689E+10 |
Minimum of Months | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.144337E+10 | 0.122978E+09 |
Maximum of Months | 0.183172E+10 | 0.824532E+09 | 0.116112E+10 | 0.380974E+10 | 0.111494E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362225E+10 | 0.235329E+10 | 0.126895E+10 | 0.585108E+10 | 0.172113E+10 |
February | 0.295974E+10 | 0.171257E+10 | 0.124717E+10 | 0.504938E+10 | 0.131225E+10 |
March | 0.251588E+10 | 0.106369E+10 | 0.145219E+10 | 0.433714E+10 | 0.121599E+10 |
April | 0.165557E+10 | 0.290323E+09 | 0.136524E+10 | 0.313860E+10 | 0.804381E+09 |
May | 0.137089E+10 | 29658913.09 | 0.134123E+10 | 0.284624E+10 | 0.409396E+09 |
June | 0.126486E+10 | 2387010.47 | 0.126248E+10 | 0.283590E+10 | 0.188880E+09 |
July | 0.139947E+10 | 12971867.25 | 0.138650E+10 | 0.328827E+10 | 0.281992E+09 |
August | 0.158835E+10 | 0.134034E+09 | 0.145432E+10 | 0.356201E+10 | 0.189076E+09 |
September | 0.196771E+10 | 0.482193E+09 | 0.148552E+10 | 0.437641E+10 | 0.312420E+09 |
October | 0.279620E+10 | 0.131189E+10 | 0.148431E+10 | 0.551610E+10 | 0.530872E+09 |
November | 0.307883E+10 | 0.171833E+10 | 0.136050E+10 | 0.546241E+10 | 0.898479E+09 |
December | 0.349083E+10 | 0.220182E+10 | 0.128901E+10 | 0.577106E+10 | 0.150169E+10 |
Annual Sum or Average | 0.277106E+11 | 0.113132E+11 | 0.163974E+11 | 0.520346E+11 | 0.936655E+10 |
Minimum of Months | 0.126486E+10 | 2387010.47 | 0.124717E+10 | 0.283590E+10 | 0.188880E+09 |
Maximum of Months | 0.362225E+10 | 0.235329E+10 | 0.148552E+10 | 0.585108E+10 | 0.172113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111138E+10 | 0.479130E+09 | 0.632246E+09 | 0.164579E+10 | 0.118190E+10 |
February | 0.125525E+10 | 0.568074E+09 | 0.687180E+09 | 0.205704E+10 | 0.907334E+09 |
March | 0.173066E+10 | 0.790310E+09 | 0.940349E+09 | 0.282600E+10 | 0.854609E+09 |
April | 0.184350E+10 | 0.853602E+09 | 0.989901E+09 | 0.328540E+10 | 0.568022E+09 |
May | 0.173661E+10 | 0.668514E+09 | 0.106810E+10 | 0.338873E+10 | 0.313768E+09 |
June | 0.142398E+10 | 0.399438E+09 | 0.102454E+10 | 0.295845E+10 | 0.141172E+09 |
July | 0.164447E+10 | 0.508748E+09 | 0.113572E+10 | 0.350785E+10 | 0.208928E+09 |
August | 0.164073E+10 | 0.534711E+09 | 0.110602E+10 | 0.335665E+10 | 0.145754E+09 |
September | 0.135448E+10 | 0.399394E+09 | 0.955087E+09 | 0.285180E+10 | 0.212853E+09 |
October | 0.139237E+10 | 0.542790E+09 | 0.849583E+09 | 0.270456E+10 | 0.359550E+09 |
November | 0.111151E+10 | 0.407709E+09 | 0.703803E+09 | 0.196583E+10 | 0.613427E+09 |
December | 0.115062E+10 | 0.514433E+09 | 0.636185E+09 | 0.181202E+10 | 0.100777E+10 |
Annual Sum or Average | 0.173956E+11 | 0.666685E+10 | 0.107287E+11 | 0.323601E+11 | 0.651508E+10 |
Minimum of Months | 0.111138E+10 | 0.399394E+09 | 0.632246E+09 | 0.164579E+10 | 0.141172E+09 |
Maximum of Months | 0.184350E+10 | 0.853602E+09 | 0.113572E+10 | 0.350785E+10 | 0.118190E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256888E+09 | 0.00 | 0.256888E+09 | 0.274889E+09 | 0.654310E+09 |
February | 0.274642E+09 | 0.00 | 0.274642E+09 | 0.381143E+09 | 0.479631E+09 |
March | 0.362623E+09 | 0.00 | 0.362623E+09 | 0.511749E+09 | 0.429692E+09 |
April | 0.393228E+09 | 1766424.89 | 0.391462E+09 | 0.689541E+09 | 0.262070E+09 |
May | 0.464015E+09 | 20756460.81 | 0.443258E+09 | 0.978004E+09 | 0.138095E+09 |
June | 0.479678E+09 | 34538271.59 | 0.445140E+09 | 0.108965E+10 | 58668452.50 |
July | 0.501598E+09 | 24579293.41 | 0.477019E+09 | 0.118809E+10 | 93182985.97 |
August | 0.443922E+09 | 4082858.44 | 0.439839E+09 | 0.994824E+09 | 66862874.09 |
September | 0.381109E+09 | 30149.25 | 0.381079E+09 | 0.887207E+09 | 0.106484E+09 |
October | 0.329918E+09 | 0.00 | 0.329918E+09 | 0.675228E+09 | 0.177474E+09 |
November | 0.277612E+09 | 0.00 | 0.277612E+09 | 0.458213E+09 | 0.331404E+09 |
December | 0.254095E+09 | 0.00 | 0.254095E+09 | 0.309485E+09 | 0.560732E+09 |
Annual Sum or Average | 0.441933E+10 | 85753458.39 | 0.433357E+10 | 0.843802E+10 | 0.335861E+10 |
Minimum of Months | 0.254095E+09 | 0.00 | 0.254095E+09 | 0.274889E+09 | 58668452.50 |
Maximum of Months | 0.501598E+09 | 34538271.59 | 0.477019E+09 | 0.118809E+10 | 0.654310E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256899E+09 | 0.00 | 0.256899E+09 | 0.274900E+09 | 0.654346E+09 |
February | 0.274653E+09 | 0.00 | 0.274653E+09 | 0.381160E+09 | 0.479657E+09 |
March | 0.362638E+09 | 0.00 | 0.362638E+09 | 0.511771E+09 | 0.429714E+09 |
April | 0.393245E+09 | 1766472.37 | 0.391478E+09 | 0.689573E+09 | 0.262082E+09 |
May | 0.464033E+09 | 20757018.75 | 0.443276E+09 | 0.978048E+09 | 0.138100E+09 |
June | 0.479697E+09 | 34539199.99 | 0.445157E+09 | 0.108970E+10 | 58669965.10 |
July | 0.501618E+09 | 24579954.11 | 0.477038E+09 | 0.118814E+10 | 93185723.63 |
August | 0.443939E+09 | 4082968.19 | 0.439856E+09 | 0.994871E+09 | 66864400.51 |
September | 0.381124E+09 | 30150.06 | 0.381094E+09 | 0.887250E+09 | 0.106488E+09 |
October | 0.329932E+09 | 0.00 | 0.329932E+09 | 0.675260E+09 | 0.177480E+09 |
November | 0.277623E+09 | 0.00 | 0.277623E+09 | 0.458233E+09 | 0.331420E+09 |
December | 0.254105E+09 | 0.00 | 0.254105E+09 | 0.309497E+09 | 0.560764E+09 |
Annual Sum or Average | 0.441950E+10 | 85755763.46 | 0.433375E+10 | 0.843840E+10 | 0.335877E+10 |
Minimum of Months | 0.254105E+09 | 0.00 | 0.254105E+09 | 0.274900E+09 | 58669965.10 |
Maximum of Months | 0.501618E+09 | 34539199.99 | 0.477038E+09 | 0.118814E+10 | 0.654346E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256899E+09 | 0.00 | 0.256899E+09 | 0.274900E+09 | 0.654346E+09 |
February | 0.274653E+09 | 0.00 | 0.274653E+09 | 0.381160E+09 | 0.479657E+09 |
March | 0.362638E+09 | 0.00 | 0.362638E+09 | 0.511771E+09 | 0.429714E+09 |
April | 0.393245E+09 | 1766472.37 | 0.391478E+09 | 0.689573E+09 | 0.262082E+09 |
May | 0.464033E+09 | 20757018.75 | 0.443276E+09 | 0.978048E+09 | 0.138100E+09 |
June | 0.479697E+09 | 34539199.99 | 0.445157E+09 | 0.108970E+10 | 58669965.10 |
July | 0.501618E+09 | 24579954.11 | 0.477038E+09 | 0.118814E+10 | 93185723.63 |
August | 0.443939E+09 | 4082968.19 | 0.439856E+09 | 0.994871E+09 | 66864400.51 |
September | 0.381124E+09 | 30150.06 | 0.381094E+09 | 0.887250E+09 | 0.106488E+09 |
October | 0.329932E+09 | 0.00 | 0.329932E+09 | 0.675260E+09 | 0.177480E+09 |
November | 0.277623E+09 | 0.00 | 0.277623E+09 | 0.458233E+09 | 0.331420E+09 |
December | 0.254105E+09 | 0.00 | 0.254105E+09 | 0.309497E+09 | 0.560764E+09 |
Annual Sum or Average | 0.441950E+10 | 85755763.46 | 0.433375E+10 | 0.843840E+10 | 0.335877E+10 |
Minimum of Months | 0.254105E+09 | 0.00 | 0.254105E+09 | 0.274900E+09 | 58669965.10 |
Maximum of Months | 0.501618E+09 | 34539199.99 | 0.477038E+09 | 0.118814E+10 | 0.654346E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119008E+10 | 0.570119E+09 | 0.619959E+09 | 0.171401E+10 | 0.121800E+10 |
February | 0.124117E+10 | 0.574535E+09 | 0.666630E+09 | 0.195652E+10 | 0.898267E+09 |
March | 0.167773E+10 | 0.793155E+09 | 0.884574E+09 | 0.266941E+10 | 0.800775E+09 |
April | 0.176203E+10 | 0.786205E+09 | 0.975822E+09 | 0.314081E+10 | 0.535056E+09 |
May | 0.172251E+10 | 0.685942E+09 | 0.103657E+10 | 0.336259E+10 | 0.276072E+09 |
June | 0.164530E+10 | 0.631947E+09 | 0.101336E+10 | 0.337413E+10 | 0.121594E+09 |
July | 0.174692E+10 | 0.629972E+09 | 0.111695E+10 | 0.369701E+10 | 0.198119E+09 |
August | 0.159741E+10 | 0.534136E+09 | 0.106327E+10 | 0.327345E+10 | 0.140366E+09 |
September | 0.149032E+10 | 0.538756E+09 | 0.951568E+09 | 0.309338E+10 | 0.218872E+09 |
October | 0.141751E+10 | 0.610463E+09 | 0.807045E+09 | 0.273027E+10 | 0.361982E+09 |
November | 0.111338E+10 | 0.443947E+09 | 0.669435E+09 | 0.191291E+10 | 0.621368E+09 |
December | 0.929350E+09 | 0.328104E+09 | 0.601246E+09 | 0.136863E+10 | 0.105712E+10 |
Annual Sum or Average | 0.175337E+11 | 0.712728E+10 | 0.104064E+11 | 0.322931E+11 | 0.644760E+10 |
Minimum of Months | 0.929350E+09 | 0.328104E+09 | 0.601246E+09 | 0.136863E+10 | 0.121594E+09 |
Maximum of Months | 0.176203E+10 | 0.793155E+09 | 0.111695E+10 | 0.369701E+10 | 0.121800E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47054627.53 | 22541993.42 | 24512634.11 | 67770309.81 | 48158796.16 |
February | 49074548.65 | 22716614.25 | 26357934.40 | 77358909.38 | 35516670.07 |
March | 66335879.78 | 31360633.25 | 34975246.53 | 0.105546E+09 | 31661939.55 |
April | 69668948.92 | 31085840.69 | 38583108.23 | 0.124185E+09 | 21155647.09 |
May | 68106595.48 | 27121516.10 | 40985079.38 | 0.132954E+09 | 10915636.40 |
June | 65053835.03 | 24986627.52 | 40067207.52 | 0.133410E+09 | 4807707.47 |
July | 69071571.60 | 24908528.68 | 44163042.92 | 0.146176E+09 | 7833442.81 |
August | 63159970.15 | 21119258.87 | 42040711.28 | 0.129429E+09 | 5549951.92 |
September | 58926073.91 | 21301919.90 | 37624154.01 | 0.122310E+09 | 8653990.15 |
October | 56047004.96 | 24137172.81 | 31909832.16 | 0.107953E+09 | 14312456.05 |
November | 44022108.69 | 17553255.81 | 26468852.88 | 75634838.51 | 24568312.84 |
December | 36745642.75 | 12972935.04 | 23772707.71 | 54114220.29 | 41797724.84 |
Annual Sum or Average | 0.693267E+09 | 0.281806E+09 | 0.411461E+09 | 0.127684E+10 | 0.254932E+09 |
Minimum of Months | 36745642.75 | 12972935.04 | 23772707.71 | 54114220.29 | 4807707.47 |
Maximum of Months | 69668948.92 | 31360633.25 | 44163042.92 | 0.146176E+09 | 48158796.16 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120739E+10 | 0.784415E+09 | 0.422980E+09 | 0.194920E+10 | 0.659948E+09 |
February | 0.986564E+09 | 0.570846E+09 | 0.415717E+09 | 0.168897E+10 | 0.494809E+09 |
March | 0.838615E+09 | 0.354557E+09 | 0.484057E+09 | 0.146638E+10 | 0.436919E+09 |
April | 0.551850E+09 | 96772200.14 | 0.455078E+09 | 0.106516E+10 | 0.278443E+09 |
May | 0.456960E+09 | 9886102.36 | 0.447074E+09 | 0.963888E+09 | 0.137098E+09 |
June | 0.421618E+09 | 795653.90 | 0.420823E+09 | 0.958961E+09 | 59813207.56 |
July | 0.466487E+09 | 4323867.40 | 0.462163E+09 | 0.110410E+10 | 94427690.64 |
August | 0.529446E+09 | 44677086.16 | 0.484769E+09 | 0.118310E+10 | 71756359.54 |
September | 0.655896E+09 | 0.160728E+09 | 0.495168E+09 | 0.145304E+10 | 0.119098E+09 |
October | 0.932052E+09 | 0.437288E+09 | 0.494764E+09 | 0.183320E+10 | 0.213822E+09 |
November | 0.102626E+10 | 0.572765E+09 | 0.453495E+09 | 0.181789E+10 | 0.355969E+09 |
December | 0.116359E+10 | 0.733925E+09 | 0.429665E+09 | 0.192492E+10 | 0.579390E+09 |
Annual Sum or Average | 0.923673E+10 | 0.377098E+10 | 0.546575E+10 | 0.174088E+11 | 0.350149E+10 |
Minimum of Months | 0.421618E+09 | 795653.90 | 0.415717E+09 | 0.958961E+09 | 59813207.56 |
Maximum of Months | 0.120739E+10 | 0.784415E+09 | 0.495168E+09 | 0.194920E+10 | 0.659948E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120739E+10 | 0.784415E+09 | 0.422980E+09 | 0.194920E+10 | 0.659948E+09 |
February | 0.986564E+09 | 0.570846E+09 | 0.415717E+09 | 0.168897E+10 | 0.494809E+09 |
March | 0.838615E+09 | 0.354557E+09 | 0.484057E+09 | 0.146638E+10 | 0.436919E+09 |
April | 0.551850E+09 | 96772200.14 | 0.455078E+09 | 0.106516E+10 | 0.278443E+09 |
May | 0.456960E+09 | 9886102.36 | 0.447074E+09 | 0.963888E+09 | 0.137098E+09 |
June | 0.421618E+09 | 795653.90 | 0.420823E+09 | 0.958961E+09 | 59813207.56 |
July | 0.466487E+09 | 4323867.40 | 0.462163E+09 | 0.110410E+10 | 94427690.64 |
August | 0.529446E+09 | 44677086.16 | 0.484769E+09 | 0.118310E+10 | 71756359.54 |
September | 0.655896E+09 | 0.160728E+09 | 0.495168E+09 | 0.145304E+10 | 0.119098E+09 |
October | 0.932052E+09 | 0.437288E+09 | 0.494764E+09 | 0.183320E+10 | 0.213822E+09 |
November | 0.102626E+10 | 0.572765E+09 | 0.453495E+09 | 0.181789E+10 | 0.355969E+09 |
December | 0.116359E+10 | 0.733925E+09 | 0.429665E+09 | 0.192492E+10 | 0.579390E+09 |
Annual Sum or Average | 0.923673E+10 | 0.377098E+10 | 0.546575E+10 | 0.174088E+11 | 0.350149E+10 |
Minimum of Months | 0.421618E+09 | 795653.90 | 0.415717E+09 | 0.958961E+09 | 59813207.56 |
Maximum of Months | 0.120739E+10 | 0.784415E+09 | 0.495168E+09 | 0.194920E+10 | 0.659948E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120732E+10 | 0.784365E+09 | 0.422953E+09 | 0.194907E+10 | 0.659906E+09 |
February | 0.986501E+09 | 0.570810E+09 | 0.415691E+09 | 0.168887E+10 | 0.494778E+09 |
March | 0.838562E+09 | 0.354535E+09 | 0.484027E+09 | 0.146629E+10 | 0.436891E+09 |
April | 0.551815E+09 | 96766084.68 | 0.455049E+09 | 0.106509E+10 | 0.278425E+09 |
May | 0.456932E+09 | 9885477.61 | 0.447046E+09 | 0.963827E+09 | 0.137089E+09 |
June | 0.421592E+09 | 795603.62 | 0.420796E+09 | 0.958901E+09 | 59809427.70 |
July | 0.466457E+09 | 4323594.16 | 0.462134E+09 | 0.110403E+10 | 94421723.35 |
August | 0.529413E+09 | 44674262.83 | 0.484738E+09 | 0.118303E+10 | 71751824.94 |
September | 0.655855E+09 | 0.160717E+09 | 0.495137E+09 | 0.145294E+10 | 0.119090E+09 |
October | 0.931993E+09 | 0.437261E+09 | 0.494733E+09 | 0.183308E+10 | 0.213808E+09 |
November | 0.102620E+10 | 0.572728E+09 | 0.453467E+09 | 0.181777E+10 | 0.355946E+09 |
December | 0.116352E+10 | 0.733879E+09 | 0.429638E+09 | 0.192480E+10 | 0.579353E+09 |
Annual Sum or Average | 0.923615E+10 | 0.377074E+10 | 0.546541E+10 | 0.174077E+11 | 0.350127E+10 |
Minimum of Months | 0.421592E+09 | 795603.62 | 0.415691E+09 | 0.958901E+09 | 59809427.70 |
Maximum of Months | 0.120732E+10 | 0.784365E+09 | 0.495137E+09 | 0.194907E+10 | 0.659906E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106909E+10 | 0.460899E+09 | 0.608192E+09 | 0.156807E+10 | 0.129585E+10 |
February | 0.120750E+10 | 0.546459E+09 | 0.661036E+09 | 0.197961E+10 | 0.976660E+09 |
March | 0.166481E+10 | 0.760238E+09 | 0.904574E+09 | 0.274546E+10 | 0.895856E+09 |
April | 0.177336E+10 | 0.821122E+09 | 0.952241E+09 | 0.319620E+10 | 0.581963E+09 |
May | 0.167054E+10 | 0.643077E+09 | 0.102746E+10 | 0.329914E+10 | 0.316382E+09 |
June | 0.136980E+10 | 0.384239E+09 | 0.985559E+09 | 0.288100E+10 | 0.135687E+09 |
July | 0.158190E+10 | 0.489389E+09 | 0.109251E+10 | 0.340416E+10 | 0.212884E+09 |
August | 0.157830E+10 | 0.514365E+09 | 0.106394E+10 | 0.324226E+10 | 0.162131E+09 |
September | 0.130295E+10 | 0.384196E+09 | 0.918751E+09 | 0.275558E+10 | 0.230796E+09 |
October | 0.133940E+10 | 0.522137E+09 | 0.817261E+09 | 0.260926E+10 | 0.396139E+09 |
November | 0.106922E+10 | 0.392196E+09 | 0.677027E+09 | 0.188797E+10 | 0.679698E+09 |
December | 0.110684E+10 | 0.494858E+09 | 0.611981E+09 | 0.172753E+10 | 0.111617E+10 |
Annual Sum or Average | 0.167337E+11 | 0.641317E+10 | 0.103205E+11 | 0.312962E+11 | 0.700021E+10 |
Minimum of Months | 0.106909E+10 | 0.384196E+09 | 0.608192E+09 | 0.156807E+10 | 0.135687E+09 |
Maximum of Months | 0.177336E+10 | 0.821122E+09 | 0.109251E+10 | 0.340416E+10 | 0.129585E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42270789.24 | 18223466.12 | 24047323.13 | 61999939.28 | 51236527.36 |
February | 47743138.60 | 21606415.46 | 26136723.14 | 78271589.19 | 38616214.79 |
March | 65824986.39 | 30059021.94 | 35765964.45 | 0.108553E+09 | 35421313.31 |
April | 70116957.64 | 32466303.65 | 37650653.99 | 0.126374E+09 | 23010278.78 |
May | 66051412.57 | 25426596.88 | 40624815.70 | 0.130445E+09 | 12509429.64 |
June | 54160475.55 | 15192429.77 | 38968045.77 | 0.113912E+09 | 5364925.19 |
July | 62546854.75 | 19349951.39 | 43196903.35 | 0.134597E+09 | 8417236.31 |
August | 62404589.49 | 20337464.13 | 42067125.36 | 0.128196E+09 | 6410486.43 |
September | 51517223.18 | 15190729.58 | 36326493.60 | 0.108953E+09 | 9125458.43 |
October | 52958432.59 | 20644750.74 | 32313681.85 | 0.103167E+09 | 15662935.85 |
November | 42275966.13 | 15507006.95 | 26768959.17 | 74648567.03 | 26874622.58 |
December | 43763315.96 | 19566177.91 | 24197138.05 | 68304692.50 | 44132203.21 |
Annual Sum or Average | 0.661634E+09 | 0.253570E+09 | 0.408064E+09 | 0.123742E+10 | 0.276782E+09 |
Minimum of Months | 42270789.24 | 15190729.58 | 24047323.13 | 61999939.28 | 5364925.19 |
Maximum of Months | 70116957.64 | 32466303.65 | 43196903.35 | 0.134597E+09 | 51236527.36 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.770701E+09 | 0.00 | 0.770701E+09 | 0.828975E+09 | 0.190837E+10 |
February | 0.823965E+09 | 0.00 | 0.823965E+09 | 0.113781E+10 | 0.141731E+10 |
March | 0.108792E+10 | 0.00 | 0.108792E+10 | 0.150393E+10 | 0.130712E+10 |
April | 0.117974E+10 | 5299525.40 | 0.117444E+10 | 0.203630E+10 | 0.810714E+09 |
May | 0.139211E+10 | 62272328.66 | 0.132984E+10 | 0.290943E+10 | 0.429365E+09 |
June | 0.143910E+10 | 0.103620E+09 | 0.133548E+10 | 0.324824E+10 | 0.187107E+09 |
July | 0.150487E+10 | 73741369.08 | 0.143112E+10 | 0.355908E+10 | 0.283612E+09 |
August | 0.133183E+10 | 12249154.86 | 0.131958E+10 | 0.299789E+10 | 0.191886E+09 |
September | 0.114338E+10 | 90452.03 | 0.114329E+10 | 0.267549E+10 | 0.307727E+09 |
October | 0.989802E+09 | 0.00 | 0.989802E+09 | 0.203506E+10 | 0.513739E+09 |
November | 0.832876E+09 | 0.00 | 0.832876E+09 | 0.138507E+10 | 0.950072E+09 |
December | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.940986E+09 | 0.161093E+10 |
Annual Sum or Average | 0.132586E+11 | 0.257273E+09 | 0.130013E+11 | 0.252583E+11 | 0.991795E+10 |
Minimum of Months | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.828975E+09 | 0.187107E+09 |
Maximum of Months | 0.150487E+10 | 0.103620E+09 | 0.143112E+10 | 0.355908E+10 | 0.190837E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123715E+10 | 0.592673E+09 | 0.644480E+09 | 0.177540E+10 | 0.120268E+10 |
February | 0.129026E+10 | 0.597264E+09 | 0.692996E+09 | 0.201595E+10 | 0.895723E+09 |
March | 0.174409E+10 | 0.824532E+09 | 0.919560E+09 | 0.273793E+10 | 0.813410E+09 |
April | 0.183172E+10 | 0.817307E+09 | 0.101442E+10 | 0.322680E+10 | 0.546298E+09 |
May | 0.179065E+10 | 0.713077E+09 | 0.107757E+10 | 0.346328E+10 | 0.281519E+09 |
June | 0.171038E+10 | 0.656947E+09 | 0.105344E+10 | 0.348439E+10 | 0.124817E+09 |
July | 0.181602E+10 | 0.654893E+09 | 0.116112E+10 | 0.382868E+10 | 0.195286E+09 |
August | 0.166059E+10 | 0.555266E+09 | 0.110532E+10 | 0.340006E+10 | 0.128794E+09 |
September | 0.154927E+10 | 0.560069E+09 | 0.989205E+09 | 0.321534E+10 | 0.208595E+09 |
October | 0.147358E+10 | 0.634613E+09 | 0.838965E+09 | 0.283062E+10 | 0.344165E+09 |
November | 0.115742E+10 | 0.461509E+09 | 0.695913E+09 | 0.198319E+10 | 0.602855E+09 |
December | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.141914E+10 | 0.103742E+10 |
Annual Sum or Average | 0.182272E+11 | 0.740923E+10 | 0.108180E+11 | 0.333808E+11 | 0.638156E+10 |
Minimum of Months | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.141914E+10 | 0.124817E+09 |
Maximum of Months | 0.183172E+10 | 0.824532E+09 | 0.116112E+10 | 0.382868E+10 | 0.120268E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.362225E+10 | 0.235329E+10 | 0.126895E+10 | 0.582333E+10 | 0.185043E+10 |
February | 0.295974E+10 | 0.171257E+10 | 0.124717E+10 | 0.503852E+10 | 0.140402E+10 |
March | 0.251588E+10 | 0.106369E+10 | 0.145219E+10 | 0.434471E+10 | 0.129011E+10 |
April | 0.165557E+10 | 0.290323E+09 | 0.136524E+10 | 0.316140E+10 | 0.842376E+09 |
May | 0.137089E+10 | 29658913.09 | 0.134123E+10 | 0.287919E+10 | 0.421789E+09 |
June | 0.126486E+10 | 2387010.47 | 0.126248E+10 | 0.287352E+10 | 0.190803E+09 |
July | 0.139947E+10 | 12971867.25 | 0.138650E+10 | 0.333162E+10 | 0.283338E+09 |
August | 0.158835E+10 | 0.134034E+09 | 0.145432E+10 | 0.359385E+10 | 0.194308E+09 |
September | 0.196771E+10 | 0.482193E+09 | 0.148552E+10 | 0.441164E+10 | 0.323292E+09 |
October | 0.279620E+10 | 0.131189E+10 | 0.148431E+10 | 0.553328E+10 | 0.560691E+09 |
November | 0.307883E+10 | 0.171833E+10 | 0.136050E+10 | 0.545856E+10 | 0.962487E+09 |
December | 0.349083E+10 | 0.220182E+10 | 0.128901E+10 | 0.575526E+10 | 0.161317E+10 |
Annual Sum or Average | 0.277106E+11 | 0.113132E+11 | 0.163974E+11 | 0.522049E+11 | 0.993682E+10 |
Minimum of Months | 0.126486E+10 | 2387010.47 | 0.124717E+10 | 0.287352E+10 | 0.190803E+09 |
Maximum of Months | 0.362225E+10 | 0.235329E+10 | 0.148552E+10 | 0.582333E+10 | 0.185043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111138E+10 | 0.479130E+09 | 0.632246E+09 | 0.163079E+10 | 0.128302E+10 |
February | 0.125525E+10 | 0.568074E+09 | 0.687180E+09 | 0.205175E+10 | 0.975537E+09 |
March | 0.173066E+10 | 0.790310E+09 | 0.940349E+09 | 0.283259E+10 | 0.909049E+09 |
April | 0.184350E+10 | 0.853602E+09 | 0.989901E+09 | 0.330174E+10 | 0.593923E+09 |
May | 0.173661E+10 | 0.668514E+09 | 0.106810E+10 | 0.341257E+10 | 0.321776E+09 |
June | 0.142398E+10 | 0.399438E+09 | 0.102454E+10 | 0.298425E+10 | 0.142327E+09 |
July | 0.164447E+10 | 0.508748E+09 | 0.113572E+10 | 0.353711E+10 | 0.210892E+09 |
August | 0.164073E+10 | 0.534711E+09 | 0.110602E+10 | 0.337858E+10 | 0.149008E+09 |
September | 0.135448E+10 | 0.399394E+09 | 0.955087E+09 | 0.287429E+10 | 0.220014E+09 |
October | 0.139237E+10 | 0.542790E+09 | 0.849583E+09 | 0.271728E+10 | 0.379486E+09 |
November | 0.111151E+10 | 0.407709E+09 | 0.703803E+09 | 0.196637E+10 | 0.661109E+09 |
December | 0.115062E+10 | 0.514433E+09 | 0.636185E+09 | 0.180106E+10 | 0.109002E+10 |
Annual Sum or Average | 0.173956E+11 | 0.666685E+10 | 0.107287E+11 | 0.324884E+11 | 0.693616E+10 |
Minimum of Months | 0.111138E+10 | 0.399394E+09 | 0.632246E+09 | 0.163079E+10 | 0.142327E+09 |
Maximum of Months | 0.184350E+10 | 0.853602E+09 | 0.113572E+10 | 0.353711E+10 | 0.128302E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.27 | 653.70 | 287.75 | 0.00 | 287.75 | 0.00 | 0.00 |
February | 476.22 | 541.91 | 340.59 | 0.00 | 340.59 | 0.00 | 0.00 |
March | 560.97 | 456.84 | 406.18 | 0.00 | 406.18 | 0.00 | 0.00 |
April | 778.18 | 298.26 | 455.15 | 2.04 | 453.10 | 0.00 | 0.00 |
May | 1074.56 | 156.61 | 519.75 | 23.25 | 496.50 | 0.00 | 0.00 |
June | 1238.40 | 71.72 | 555.21 | 39.98 | 515.23 | 0.00 | 0.00 |
July | 1312.65 | 105.51 | 561.85 | 27.53 | 534.32 | 0.00 | 0.00 |
August | 1108.18 | 69.86 | 497.25 | 4.57 | 492.67 | 0.00 | 0.00 |
September | 1019.55 | 114.48 | 441.12 | 0.03 | 441.08 | 0.00 | 0.00 |
October | 754.12 | 180.39 | 369.55 | 0.00 | 369.55 | 0.00 | 0.00 |
November | 535.87 | 337.60 | 321.33 | 0.00 | 321.33 | 0.00 | 0.00 |
December | 359.97 | 552.81 | 284.62 | 0.00 | 284.62 | 0.00 | 0.00 |
Annual Sum or Average | 796.46 | 293.93 | 420.43 | 8.16 | 412.27 | 0.00 | 0.00 |
Minimum of Months | 320.27 | 69.86 | 284.62 | 0.00 | 284.62 | 0.00 | 0.00 |
Maximum of Months | 1312.65 | 653.70 | 561.85 | 39.98 | 534.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 674.09 | 416.27 | 461.90 | 221.28 | 240.62 | 0.00 | 0.00 |
February | 841.10 | 345.09 | 533.34 | 246.88 | 286.46 | 0.00 | 0.00 |
March | 1024.49 | 286.62 | 651.17 | 307.84 | 343.32 | 0.00 | 0.00 |
April | 1242.14 | 201.24 | 706.68 | 315.32 | 391.36 | 0.00 | 0.00 |
May | 1287.88 | 101.90 | 668.55 | 266.23 | 402.32 | 0.00 | 0.00 |
June | 1338.27 | 47.45 | 659.87 | 253.45 | 406.42 | 0.00 | 0.00 |
July | 1422.39 | 72.20 | 678.02 | 244.51 | 433.51 | 0.00 | 0.00 |
August | 1265.80 | 46.40 | 619.99 | 207.31 | 412.68 | 0.00 | 0.00 |
September | 1235.56 | 77.64 | 597.71 | 216.08 | 381.64 | 0.00 | 0.00 |
October | 1055.85 | 120.96 | 550.17 | 236.94 | 313.23 | 0.00 | 0.00 |
November | 769.59 | 215.90 | 446.54 | 178.05 | 268.48 | 0.00 | 0.00 |
December | 538.89 | 358.21 | 360.70 | 127.35 | 233.36 | 0.00 | 0.00 |
Annual Sum or Average | 1058.82 | 190.16 | 577.98 | 234.95 | 343.04 | 0.00 | 0.00 |
Minimum of Months | 538.89 | 46.40 | 360.70 | 127.35 | 233.36 | 0.00 | 0.00 |
Maximum of Months | 1422.39 | 416.27 | 706.68 | 315.32 | 433.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2184.54 | 642.60 | 1352.39 | 878.62 | 473.77 | 0.00 | 0.00 |
February | 2087.21 | 542.43 | 1223.44 | 707.91 | 515.53 | 0.00 | 0.00 |
March | 1619.30 | 454.00 | 939.32 | 397.14 | 542.18 | 0.00 | 0.00 |
April | 1210.88 | 310.33 | 638.72 | 112.01 | 526.71 | 0.00 | 0.00 |
May | 1062.67 | 152.85 | 511.83 | 11.07 | 500.76 | 0.00 | 0.00 |
June | 1094.10 | 72.87 | 487.99 | 0.92 | 487.07 | 0.00 | 0.00 |
July | 1227.70 | 105.28 | 522.50 | 4.84 | 517.66 | 0.00 | 0.00 |
August | 1329.90 | 70.59 | 593.02 | 50.04 | 542.98 | 0.00 | 0.00 |
September | 1688.43 | 120.53 | 759.15 | 186.03 | 573.12 | 0.00 | 0.00 |
October | 2059.48 | 198.21 | 1043.98 | 489.80 | 554.18 | 0.00 | 0.00 |
November | 2107.41 | 346.64 | 1187.82 | 662.94 | 524.89 | 0.00 | 0.00 |
December | 2154.67 | 560.67 | 1303.33 | 822.07 | 481.26 | 0.00 | 0.00 |
Annual Sum or Average | 1650.01 | 297.01 | 878.70 | 358.74 | 519.96 | 0.00 | 0.00 |
Minimum of Months | 1062.67 | 70.59 | 487.99 | 0.92 | 473.77 | 0.00 | 0.00 |
Maximum of Months | 2184.54 | 642.60 | 1352.39 | 878.62 | 573.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 614.47 | 441.27 | 414.94 | 178.89 | 236.05 | 0.00 | 0.00 |
February | 850.30 | 375.06 | 518.87 | 234.82 | 284.05 | 0.00 | 0.00 |
March | 1055.11 | 319.07 | 646.15 | 295.07 | 351.09 | 0.00 | 0.00 |
April | 1267.52 | 219.14 | 711.23 | 329.32 | 381.91 | 0.00 | 0.00 |
May | 1265.21 | 117.15 | 648.38 | 249.59 | 398.78 | 0.00 | 0.00 |
June | 1141.38 | 54.46 | 549.37 | 154.10 | 395.27 | 0.00 | 0.00 |
July | 1309.68 | 78.00 | 613.97 | 189.94 | 424.03 | 0.00 | 0.00 |
August | 1253.23 | 54.42 | 612.58 | 199.64 | 412.94 | 0.00 | 0.00 |
September | 1100.23 | 82.12 | 522.56 | 154.09 | 368.48 | 0.00 | 0.00 |
October | 1009.77 | 134.24 | 519.85 | 202.65 | 317.20 | 0.00 | 0.00 |
November | 758.42 | 236.66 | 428.82 | 157.30 | 271.53 | 0.00 | 0.00 |
December | 676.53 | 376.26 | 429.59 | 192.07 | 237.52 | 0.00 | 0.00 |
Annual Sum or Average | 1026.13 | 206.59 | 551.61 | 211.40 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 614.47 | 54.42 | 414.94 | 154.09 | 236.05 | 0.00 | 0.00 |
Maximum of Months | 1309.68 | 441.27 | 711.23 | 329.32 | 424.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 307.90 | 732.90 | 287.74 | 0.00 | 287.74 | 0.00 | 0.00 |
February | 472.66 | 594.80 | 340.59 | 0.00 | 340.59 | 0.00 | 0.00 |
March | 573.21 | 481.30 | 406.17 | 0.00 | 406.17 | 0.00 | 0.00 |
April | 798.10 | 303.33 | 455.14 | 2.04 | 453.09 | 0.00 | 0.00 |
May | 1095.47 | 154.68 | 519.74 | 23.25 | 496.49 | 0.00 | 0.00 |
June | 1261.20 | 67.90 | 555.20 | 39.98 | 515.22 | 0.00 | 0.00 |
July | 1330.79 | 104.37 | 561.84 | 27.53 | 534.31 | 0.00 | 0.00 |
August | 1114.31 | 74.89 | 497.24 | 4.57 | 492.66 | 0.00 | 0.00 |
September | 1026.89 | 123.25 | 441.11 | 0.03 | 441.07 | 0.00 | 0.00 |
October | 756.33 | 198.79 | 369.54 | 0.00 | 369.54 | 0.00 | 0.00 |
November | 530.35 | 383.58 | 321.32 | 0.00 | 321.32 | 0.00 | 0.00 |
December | 346.65 | 628.08 | 284.61 | 0.00 | 284.61 | 0.00 | 0.00 |
Annual Sum or Average | 802.73 | 319.51 | 420.42 | 8.16 | 412.26 | 0.00 | 0.00 |
Minimum of Months | 307.90 | 67.90 | 284.61 | 0.00 | 284.61 | 0.00 | 0.00 |
Maximum of Months | 1330.79 | 732.90 | 561.84 | 39.98 | 534.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 665.24 | 472.73 | 461.89 | 221.27 | 240.62 | 0.00 | 0.00 |
February | 840.72 | 385.99 | 533.33 | 246.88 | 286.45 | 0.00 | 0.00 |
March | 1036.05 | 310.80 | 651.16 | 307.84 | 343.32 | 0.00 | 0.00 |
April | 1259.64 | 214.59 | 706.67 | 315.31 | 391.36 | 0.00 | 0.00 |
May | 1305.08 | 107.15 | 668.54 | 266.23 | 402.31 | 0.00 | 0.00 |
June | 1353.22 | 48.77 | 659.86 | 253.45 | 406.41 | 0.00 | 0.00 |
July | 1434.88 | 76.89 | 678.01 | 244.50 | 433.51 | 0.00 | 0.00 |
August | 1270.49 | 54.48 | 619.98 | 207.31 | 412.68 | 0.00 | 0.00 |
September | 1240.62 | 87.78 | 597.70 | 216.07 | 381.63 | 0.00 | 0.00 |
October | 1059.67 | 140.49 | 550.16 | 236.93 | 313.23 | 0.00 | 0.00 |
November | 767.19 | 249.20 | 446.53 | 178.05 | 268.48 | 0.00 | 0.00 |
December | 531.19 | 410.29 | 360.70 | 127.34 | 233.36 | 0.00 | 0.00 |
Annual Sum or Average | 1064.50 | 212.54 | 577.97 | 234.94 | 343.03 | 0.00 | 0.00 |
Minimum of Months | 531.19 | 48.77 | 360.70 | 127.34 | 233.36 | 0.00 | 0.00 |
Maximum of Months | 1434.88 | 472.73 | 706.67 | 315.31 | 433.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2183.19 | 739.17 | 1352.34 | 878.58 | 473.76 | 0.00 | 0.00 |
February | 2094.42 | 613.59 | 1223.39 | 707.88 | 515.51 | 0.00 | 0.00 |
March | 1642.41 | 489.37 | 939.29 | 397.12 | 542.17 | 0.00 | 0.00 |
April | 1232.80 | 322.26 | 638.70 | 112.00 | 526.70 | 0.00 | 0.00 |
May | 1079.60 | 153.56 | 511.82 | 11.07 | 500.74 | 0.00 | 0.00 |
June | 1109.89 | 69.23 | 487.97 | 0.92 | 487.05 | 0.00 | 0.00 |
July | 1236.64 | 105.76 | 522.49 | 4.84 | 517.64 | 0.00 | 0.00 |
August | 1325.13 | 80.37 | 593.01 | 50.04 | 542.96 | 0.00 | 0.00 |
September | 1681.72 | 137.84 | 759.12 | 186.02 | 573.10 | 0.00 | 0.00 |
October | 2053.27 | 239.49 | 1043.94 | 489.78 | 554.16 | 0.00 | 0.00 |
November | 2103.99 | 411.99 | 1187.78 | 662.91 | 524.87 | 0.00 | 0.00 |
December | 2156.01 | 648.94 | 1303.28 | 822.03 | 481.25 | 0.00 | 0.00 |
Annual Sum or Average | 1656.05 | 333.09 | 878.67 | 358.72 | 519.94 | 0.00 | 0.00 |
Minimum of Months | 1079.60 | 69.23 | 487.97 | 0.92 | 473.76 | 0.00 | 0.00 |
Maximum of Months | 2183.19 | 739.17 | 1352.34 | 878.58 | 573.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 608.60 | 502.94 | 414.94 | 178.88 | 236.05 | 0.00 | 0.00 |
February | 850.64 | 419.67 | 518.86 | 234.82 | 284.05 | 0.00 | 0.00 |
March | 1065.57 | 347.70 | 646.15 | 295.06 | 351.08 | 0.00 | 0.00 |
April | 1281.86 | 233.40 | 711.22 | 329.32 | 381.90 | 0.00 | 0.00 |
May | 1280.46 | 122.79 | 648.37 | 249.59 | 398.78 | 0.00 | 0.00 |
June | 1155.44 | 54.42 | 549.37 | 154.10 | 395.27 | 0.00 | 0.00 |
July | 1321.22 | 82.62 | 613.97 | 189.94 | 424.03 | 0.00 | 0.00 |
August | 1258.38 | 62.93 | 612.57 | 199.64 | 412.94 | 0.00 | 0.00 |
September | 1105.14 | 92.56 | 522.56 | 154.08 | 368.47 | 0.00 | 0.00 |
October | 1012.70 | 153.75 | 519.85 | 202.65 | 317.19 | 0.00 | 0.00 |
November | 757.18 | 272.60 | 428.82 | 157.29 | 271.53 | 0.00 | 0.00 |
December | 670.49 | 433.21 | 429.59 | 192.06 | 237.52 | 0.00 | 0.00 |
Annual Sum or Average | 1031.64 | 230.75 | 551.60 | 211.40 | 340.20 | 0.00 | 0.00 |
Minimum of Months | 608.60 | 54.42 | 414.94 | 154.08 | 236.05 | 0.00 | 0.00 |
Maximum of Months | 1321.22 | 502.94 | 711.22 | 329.32 | 424.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.50 | 712.50 | 287.75 | 0.00 | 287.75 | 0.00 | 0.00 |
February | 470.32 | 585.86 | 340.59 | 0.00 | 340.59 | 0.00 | 0.00 |
March | 561.50 | 488.02 | 406.18 | 0.00 | 406.18 | 0.00 | 0.00 |
April | 785.61 | 312.78 | 455.15 | 2.04 | 453.10 | 0.00 | 0.00 |
May | 1086.25 | 160.31 | 519.75 | 23.25 | 496.50 | 0.00 | 0.00 |
June | 1253.18 | 72.19 | 555.21 | 39.98 | 515.23 | 0.00 | 0.00 |
July | 1328.81 | 105.89 | 561.85 | 27.53 | 534.32 | 0.00 | 0.00 |
August | 1119.28 | 71.64 | 497.25 | 4.57 | 492.67 | 0.00 | 0.00 |
September | 1032.21 | 118.72 | 441.12 | 0.03 | 441.08 | 0.00 | 0.00 |
October | 759.80 | 191.81 | 369.55 | 0.00 | 369.55 | 0.00 | 0.00 |
November | 534.36 | 366.54 | 321.33 | 0.00 | 321.33 | 0.00 | 0.00 |
December | 351.32 | 601.45 | 284.62 | 0.00 | 284.62 | 0.00 | 0.00 |
Annual Sum or Average | 800.93 | 314.50 | 420.43 | 8.16 | 412.27 | 0.00 | 0.00 |
Minimum of Months | 309.50 | 71.64 | 284.62 | 0.00 | 284.62 | 0.00 | 0.00 |
Maximum of Months | 1328.81 | 712.50 | 561.85 | 39.98 | 534.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 662.86 | 449.03 | 461.90 | 221.28 | 240.62 | 0.00 | 0.00 |
February | 833.31 | 370.26 | 533.34 | 246.88 | 286.46 | 0.00 | 0.00 |
March | 1022.23 | 303.69 | 651.17 | 307.84 | 343.32 | 0.00 | 0.00 |
April | 1244.91 | 210.76 | 706.68 | 315.32 | 391.36 | 0.00 | 0.00 |
May | 1293.04 | 105.11 | 668.55 | 266.23 | 402.32 | 0.00 | 0.00 |
June | 1344.28 | 48.15 | 659.87 | 253.45 | 406.42 | 0.00 | 0.00 |
July | 1429.47 | 72.91 | 678.02 | 244.51 | 433.51 | 0.00 | 0.00 |
August | 1269.44 | 48.09 | 619.99 | 207.31 | 412.68 | 0.00 | 0.00 |
September | 1240.49 | 80.48 | 597.71 | 216.08 | 381.64 | 0.00 | 0.00 |
October | 1056.83 | 128.50 | 550.17 | 236.94 | 313.23 | 0.00 | 0.00 |
November | 765.12 | 232.58 | 446.54 | 178.05 | 268.48 | 0.00 | 0.00 |
December | 529.85 | 387.33 | 360.70 | 127.35 | 233.36 | 0.00 | 0.00 |
Annual Sum or Average | 1058.50 | 202.36 | 577.98 | 234.95 | 343.04 | 0.00 | 0.00 |
Minimum of Months | 529.85 | 48.09 | 360.70 | 127.35 | 233.36 | 0.00 | 0.00 |
Maximum of Months | 1429.47 | 449.03 | 706.68 | 315.32 | 433.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2174.18 | 690.87 | 1352.39 | 878.62 | 473.77 | 0.00 | 0.00 |
February | 2082.72 | 580.36 | 1223.44 | 707.91 | 515.53 | 0.00 | 0.00 |
March | 1622.13 | 481.67 | 939.32 | 397.14 | 542.18 | 0.00 | 0.00 |
April | 1219.68 | 324.99 | 638.72 | 112.01 | 526.71 | 0.00 | 0.00 |
May | 1074.97 | 157.48 | 511.83 | 11.07 | 500.76 | 0.00 | 0.00 |
June | 1108.61 | 73.61 | 487.99 | 0.92 | 487.07 | 0.00 | 0.00 |
July | 1243.88 | 105.79 | 522.50 | 4.84 | 517.66 | 0.00 | 0.00 |
August | 1341.79 | 72.55 | 593.02 | 50.04 | 542.98 | 0.00 | 0.00 |
September | 1702.02 | 124.73 | 759.15 | 186.03 | 573.12 | 0.00 | 0.00 |
October | 2065.89 | 209.34 | 1043.98 | 489.80 | 554.18 | 0.00 | 0.00 |
November | 2105.92 | 371.33 | 1187.82 | 662.94 | 524.89 | 0.00 | 0.00 |
December | 2148.77 | 602.29 | 1303.33 | 822.07 | 481.26 | 0.00 | 0.00 |
Annual Sum or Average | 1655.41 | 315.09 | 878.70 | 358.74 | 519.96 | 0.00 | 0.00 |
Minimum of Months | 1074.97 | 72.55 | 487.99 | 0.92 | 473.77 | 0.00 | 0.00 |
Maximum of Months | 2174.18 | 690.87 | 1352.39 | 878.62 | 573.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 608.87 | 479.02 | 414.94 | 178.89 | 236.05 | 0.00 | 0.00 |
February | 848.11 | 403.25 | 518.87 | 234.82 | 284.05 | 0.00 | 0.00 |
March | 1057.57 | 339.40 | 646.15 | 295.07 | 351.09 | 0.00 | 0.00 |
April | 1273.82 | 229.14 | 711.23 | 329.32 | 381.91 | 0.00 | 0.00 |
May | 1274.11 | 120.14 | 648.38 | 249.59 | 398.78 | 0.00 | 0.00 |
June | 1151.33 | 54.91 | 549.37 | 154.10 | 395.27 | 0.00 | 0.00 |
July | 1320.60 | 78.74 | 613.97 | 189.94 | 424.03 | 0.00 | 0.00 |
August | 1261.42 | 55.63 | 612.58 | 199.64 | 412.94 | 0.00 | 0.00 |
September | 1108.91 | 84.88 | 522.56 | 154.09 | 368.48 | 0.00 | 0.00 |
October | 1014.52 | 141.68 | 519.85 | 202.65 | 317.20 | 0.00 | 0.00 |
November | 758.63 | 255.06 | 428.82 | 157.30 | 271.53 | 0.00 | 0.00 |
December | 672.44 | 406.97 | 429.59 | 192.07 | 237.52 | 0.00 | 0.00 |
Annual Sum or Average | 1030.20 | 219.94 | 551.61 | 211.40 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 608.87 | 54.91 | 414.94 | 154.09 | 236.05 | 0.00 | 0.00 |
Maximum of Months | 1320.60 | 479.02 | 711.23 | 329.32 | 424.03 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.857822E+09 | 0.175087E+10 | 0.770701E+09 | 0.00 | 0.770701E+09 | 0.00 | 0.00 |
February | 0.115208E+10 | 0.131100E+10 | 0.823965E+09 | 0.00 | 0.823965E+09 | 0.00 | 0.00 |
March | 0.150249E+10 | 0.122361E+10 | 0.108792E+10 | 0.00 | 0.108792E+10 | 0.00 | 0.00 |
April | 0.201705E+10 | 0.773084E+09 | 0.117974E+10 | 5299525.40 | 0.117444E+10 | 0.00 | 0.00 |
May | 0.287809E+10 | 0.419464E+09 | 0.139211E+10 | 62272328.66 | 0.132984E+10 | 0.00 | 0.00 |
June | 0.320992E+10 | 0.185897E+09 | 0.143910E+10 | 0.103620E+09 | 0.133548E+10 | 0.00 | 0.00 |
July | 0.351581E+10 | 0.282608E+09 | 0.150487E+10 | 73741369.08 | 0.143112E+10 | 0.00 | 0.00 |
August | 0.296815E+10 | 0.187101E+09 | 0.133183E+10 | 12249154.86 | 0.131958E+10 | 0.00 | 0.00 |
September | 0.264266E+10 | 0.296735E+09 | 0.114338E+10 | 90452.03 | 0.114329E+10 | 0.00 | 0.00 |
October | 0.201983E+10 | 0.483165E+09 | 0.989802E+09 | 0.00 | 0.989802E+09 | 0.00 | 0.00 |
November | 0.138899E+10 | 0.875054E+09 | 0.832876E+09 | 0.00 | 0.832876E+09 | 0.00 | 0.00 |
December | 0.964140E+09 | 0.148064E+10 | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251170E+11 | 0.926922E+10 | 0.132586E+11 | 0.257273E+09 | 0.130013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.857822E+09 | 0.185897E+09 | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.351581E+10 | 0.175087E+10 | 0.150487E+10 | 0.103620E+09 | 0.143112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180548E+10 | 0.111494E+10 | 0.123715E+10 | 0.592673E+09 | 0.644480E+09 | 0.00 | 0.00 |
February | 0.203478E+10 | 0.834833E+09 | 0.129026E+10 | 0.597264E+09 | 0.692996E+09 | 0.00 | 0.00 |
March | 0.274399E+10 | 0.767689E+09 | 0.174409E+10 | 0.824532E+09 | 0.919560E+09 | 0.00 | 0.00 |
April | 0.321962E+10 | 0.521607E+09 | 0.183172E+10 | 0.817307E+09 | 0.101442E+10 | 0.00 | 0.00 |
May | 0.344946E+10 | 0.272938E+09 | 0.179065E+10 | 0.713077E+09 | 0.107757E+10 | 0.00 | 0.00 |
June | 0.346880E+10 | 0.122978E+09 | 0.171038E+10 | 0.656947E+09 | 0.105344E+10 | 0.00 | 0.00 |
July | 0.380974E+10 | 0.193370E+09 | 0.181602E+10 | 0.654893E+09 | 0.116112E+10 | 0.00 | 0.00 |
August | 0.339031E+10 | 0.124290E+09 | 0.166059E+10 | 0.555266E+09 | 0.110532E+10 | 0.00 | 0.00 |
September | 0.320257E+10 | 0.201246E+09 | 0.154927E+10 | 0.560069E+09 | 0.989205E+09 | 0.00 | 0.00 |
October | 0.282798E+10 | 0.323967E+09 | 0.147358E+10 | 0.634613E+09 | 0.838965E+09 | 0.00 | 0.00 |
November | 0.199478E+10 | 0.559610E+09 | 0.115742E+10 | 0.461509E+09 | 0.695913E+09 | 0.00 | 0.00 |
December | 0.144337E+10 | 0.959421E+09 | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333909E+11 | 0.599689E+10 | 0.182272E+11 | 0.740923E+10 | 0.108180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144337E+10 | 0.122978E+09 | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380974E+10 | 0.111494E+10 | 0.183172E+10 | 0.824532E+09 | 0.116112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.585108E+10 | 0.172113E+10 | 0.362225E+10 | 0.235329E+10 | 0.126895E+10 | 0.00 | 0.00 |
February | 0.504938E+10 | 0.131225E+10 | 0.295974E+10 | 0.171257E+10 | 0.124717E+10 | 0.00 | 0.00 |
March | 0.433714E+10 | 0.121599E+10 | 0.251588E+10 | 0.106369E+10 | 0.145219E+10 | 0.00 | 0.00 |
April | 0.313860E+10 | 0.804381E+09 | 0.165557E+10 | 0.290323E+09 | 0.136524E+10 | 0.00 | 0.00 |
May | 0.284624E+10 | 0.409396E+09 | 0.137089E+10 | 29658913.09 | 0.134123E+10 | 0.00 | 0.00 |
June | 0.283590E+10 | 0.188880E+09 | 0.126486E+10 | 2387010.47 | 0.126248E+10 | 0.00 | 0.00 |
July | 0.328827E+10 | 0.281992E+09 | 0.139947E+10 | 12971867.25 | 0.138650E+10 | 0.00 | 0.00 |
August | 0.356201E+10 | 0.189076E+09 | 0.158835E+10 | 0.134034E+09 | 0.145432E+10 | 0.00 | 0.00 |
September | 0.437641E+10 | 0.312420E+09 | 0.196771E+10 | 0.482193E+09 | 0.148552E+10 | 0.00 | 0.00 |
October | 0.551610E+10 | 0.530872E+09 | 0.279620E+10 | 0.131189E+10 | 0.148431E+10 | 0.00 | 0.00 |
November | 0.546241E+10 | 0.898479E+09 | 0.307883E+10 | 0.171833E+10 | 0.136050E+10 | 0.00 | 0.00 |
December | 0.577106E+10 | 0.150169E+10 | 0.349083E+10 | 0.220182E+10 | 0.128901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.520346E+11 | 0.936655E+10 | 0.277106E+11 | 0.113132E+11 | 0.163974E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283590E+10 | 0.188880E+09 | 0.126486E+10 | 2387010.47 | 0.124717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.585108E+10 | 0.172113E+10 | 0.362225E+10 | 0.235329E+10 | 0.148552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164579E+10 | 0.118190E+10 | 0.111138E+10 | 0.479130E+09 | 0.632246E+09 | 0.00 | 0.00 |
February | 0.205704E+10 | 0.907334E+09 | 0.125525E+10 | 0.568074E+09 | 0.687180E+09 | 0.00 | 0.00 |
March | 0.282600E+10 | 0.854609E+09 | 0.173066E+10 | 0.790310E+09 | 0.940349E+09 | 0.00 | 0.00 |
April | 0.328540E+10 | 0.568022E+09 | 0.184350E+10 | 0.853602E+09 | 0.989901E+09 | 0.00 | 0.00 |
May | 0.338873E+10 | 0.313768E+09 | 0.173661E+10 | 0.668514E+09 | 0.106810E+10 | 0.00 | 0.00 |
June | 0.295845E+10 | 0.141172E+09 | 0.142398E+10 | 0.399438E+09 | 0.102454E+10 | 0.00 | 0.00 |
July | 0.350785E+10 | 0.208928E+09 | 0.164447E+10 | 0.508748E+09 | 0.113572E+10 | 0.00 | 0.00 |
August | 0.335665E+10 | 0.145754E+09 | 0.164073E+10 | 0.534711E+09 | 0.110602E+10 | 0.00 | 0.00 |
September | 0.285180E+10 | 0.212853E+09 | 0.135448E+10 | 0.399394E+09 | 0.955087E+09 | 0.00 | 0.00 |
October | 0.270456E+10 | 0.359550E+09 | 0.139237E+10 | 0.542790E+09 | 0.849583E+09 | 0.00 | 0.00 |
November | 0.196583E+10 | 0.613427E+09 | 0.111151E+10 | 0.407709E+09 | 0.703803E+09 | 0.00 | 0.00 |
December | 0.181202E+10 | 0.100777E+10 | 0.115062E+10 | 0.514433E+09 | 0.636185E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323601E+11 | 0.651508E+10 | 0.173956E+11 | 0.666685E+10 | 0.107287E+11 | 0.00 | 0.00 |
Minimum of Months | 0.164579E+10 | 0.141172E+09 | 0.111138E+10 | 0.399394E+09 | 0.632246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.350785E+10 | 0.118190E+10 | 0.184350E+10 | 0.853602E+09 | 0.113572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.824688E+09 | 0.196300E+10 | 0.770685E+09 | 0.00 | 0.770685E+09 | 0.00 | 0.00 |
February | 0.114346E+10 | 0.143895E+10 | 0.823949E+09 | 0.00 | 0.823949E+09 | 0.00 | 0.00 |
March | 0.153529E+10 | 0.128912E+10 | 0.108790E+10 | 0.00 | 0.108790E+10 | 0.00 | 0.00 |
April | 0.206869E+10 | 0.786235E+09 | 0.117972E+10 | 5299369.63 | 0.117442E+10 | 0.00 | 0.00 |
May | 0.293410E+10 | 0.414296E+09 | 0.139208E+10 | 62270498.31 | 0.132981E+10 | 0.00 | 0.00 |
June | 0.326904E+10 | 0.176008E+09 | 0.143907E+10 | 0.103617E+09 | 0.133545E+10 | 0.00 | 0.00 |
July | 0.356438E+10 | 0.279554E+09 | 0.150483E+10 | 73739201.62 | 0.143109E+10 | 0.00 | 0.00 |
August | 0.298457E+10 | 0.200592E+09 | 0.133180E+10 | 12248794.82 | 0.131955E+10 | 0.00 | 0.00 |
September | 0.266171E+10 | 0.319459E+09 | 0.114336E+10 | 90449.37 | 0.114327E+10 | 0.00 | 0.00 |
October | 0.202575E+10 | 0.532435E+09 | 0.989782E+09 | 0.00 | 0.989782E+09 | 0.00 | 0.00 |
November | 0.137468E+10 | 0.994244E+09 | 0.832858E+09 | 0.00 | 0.832858E+09 | 0.00 | 0.00 |
December | 0.928478E+09 | 0.168226E+10 | 0.762304E+09 | 0.00 | 0.762304E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.253148E+11 | 0.100762E+11 | 0.132583E+11 | 0.257265E+09 | 0.130011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.824688E+09 | 0.176008E+09 | 0.762304E+09 | 0.00 | 0.762304E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356438E+10 | 0.196300E+10 | 0.150483E+10 | 0.103617E+09 | 0.143109E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.178178E+10 | 0.126616E+10 | 0.123713E+10 | 0.592661E+09 | 0.644472E+09 | 0.00 | 0.00 |
February | 0.203388E+10 | 0.933784E+09 | 0.129024E+10 | 0.597252E+09 | 0.692988E+09 | 0.00 | 0.00 |
March | 0.277496E+10 | 0.832437E+09 | 0.174406E+10 | 0.824516E+09 | 0.919549E+09 | 0.00 | 0.00 |
April | 0.326499E+10 | 0.556212E+09 | 0.183170E+10 | 0.817291E+09 | 0.101440E+10 | 0.00 | 0.00 |
May | 0.349554E+10 | 0.286988E+09 | 0.179062E+10 | 0.713063E+09 | 0.107756E+10 | 0.00 | 0.00 |
June | 0.350754E+10 | 0.126401E+09 | 0.171036E+10 | 0.656934E+09 | 0.105342E+10 | 0.00 | 0.00 |
July | 0.384318E+10 | 0.205952E+09 | 0.181599E+10 | 0.654881E+09 | 0.116111E+10 | 0.00 | 0.00 |
August | 0.340287E+10 | 0.145916E+09 | 0.166057E+10 | 0.555255E+09 | 0.110531E+10 | 0.00 | 0.00 |
September | 0.321569E+10 | 0.227526E+09 | 0.154925E+10 | 0.560058E+09 | 0.989192E+09 | 0.00 | 0.00 |
October | 0.283822E+10 | 0.376295E+09 | 0.147356E+10 | 0.634601E+09 | 0.838955E+09 | 0.00 | 0.00 |
November | 0.198855E+10 | 0.645936E+09 | 0.115740E+10 | 0.461500E+09 | 0.695904E+09 | 0.00 | 0.00 |
December | 0.142274E+10 | 0.109892E+10 | 0.966095E+09 | 0.341077E+09 | 0.625018E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.335699E+11 | 0.670253E+10 | 0.182270E+11 | 0.740909E+10 | 0.108179E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142274E+10 | 0.126401E+09 | 0.966095E+09 | 0.341077E+09 | 0.625018E+09 | 0.00 | 0.00 |
Maximum of Months | 0.384318E+10 | 0.126616E+10 | 0.183170E+10 | 0.824516E+09 | 0.116111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.584747E+10 | 0.197980E+10 | 0.362211E+10 | 0.235320E+10 | 0.126891E+10 | 0.00 | 0.00 |
February | 0.506681E+10 | 0.148440E+10 | 0.295963E+10 | 0.171250E+10 | 0.124713E+10 | 0.00 | 0.00 |
March | 0.439904E+10 | 0.131073E+10 | 0.251579E+10 | 0.106365E+10 | 0.145214E+10 | 0.00 | 0.00 |
April | 0.319542E+10 | 0.835310E+09 | 0.165552E+10 | 0.290310E+09 | 0.136521E+10 | 0.00 | 0.00 |
May | 0.289160E+10 | 0.411286E+09 | 0.137085E+10 | 29657682.32 | 0.134119E+10 | 0.00 | 0.00 |
June | 0.287682E+10 | 0.179436E+09 | 0.126483E+10 | 2386911.41 | 0.126244E+10 | 0.00 | 0.00 |
July | 0.331223E+10 | 0.283277E+09 | 0.139943E+10 | 12971328.95 | 0.138646E+10 | 0.00 | 0.00 |
August | 0.354923E+10 | 0.215265E+09 | 0.158830E+10 | 0.134028E+09 | 0.145428E+10 | 0.00 | 0.00 |
September | 0.435902E+10 | 0.357286E+09 | 0.196765E+10 | 0.482173E+09 | 0.148547E+10 | 0.00 | 0.00 |
October | 0.549948E+10 | 0.641452E+09 | 0.279610E+10 | 0.131184E+10 | 0.148426E+10 | 0.00 | 0.00 |
November | 0.545355E+10 | 0.106788E+10 | 0.307872E+10 | 0.171826E+10 | 0.136046E+10 | 0.00 | 0.00 |
December | 0.577464E+10 | 0.173813E+10 | 0.349070E+10 | 0.220173E+10 | 0.128897E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.522253E+11 | 0.105043E+11 | 0.277096E+11 | 0.113127E+11 | 0.163969E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287682E+10 | 0.179436E+09 | 0.126483E+10 | 2386911.41 | 0.124713E+10 | 0.00 | 0.00 |
Maximum of Months | 0.584747E+10 | 0.197980E+10 | 0.362211E+10 | 0.235320E+10 | 0.148547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163007E+10 | 0.134708E+10 | 0.111136E+10 | 0.479122E+09 | 0.632240E+09 | 0.00 | 0.00 |
February | 0.205788E+10 | 0.101528E+10 | 0.125524E+10 | 0.568065E+09 | 0.687173E+09 | 0.00 | 0.00 |
March | 0.285402E+10 | 0.931277E+09 | 0.173064E+10 | 0.790297E+09 | 0.940340E+09 | 0.00 | 0.00 |
April | 0.332257E+10 | 0.604974E+09 | 0.184348E+10 | 0.853588E+09 | 0.989891E+09 | 0.00 | 0.00 |
May | 0.342959E+10 | 0.328891E+09 | 0.173659E+10 | 0.668503E+09 | 0.106809E+10 | 0.00 | 0.00 |
June | 0.299491E+10 | 0.141052E+09 | 0.142396E+10 | 0.399432E+09 | 0.102453E+10 | 0.00 | 0.00 |
July | 0.353875E+10 | 0.221302E+09 | 0.164445E+10 | 0.508739E+09 | 0.113571E+10 | 0.00 | 0.00 |
August | 0.337045E+10 | 0.168541E+09 | 0.164071E+10 | 0.534702E+09 | 0.110601E+10 | 0.00 | 0.00 |
September | 0.286453E+10 | 0.239922E+09 | 0.135446E+10 | 0.399387E+09 | 0.955077E+09 | 0.00 | 0.00 |
October | 0.271243E+10 | 0.411802E+09 | 0.139236E+10 | 0.542782E+09 | 0.849574E+09 | 0.00 | 0.00 |
November | 0.196262E+10 | 0.706573E+09 | 0.111150E+10 | 0.407703E+09 | 0.703796E+09 | 0.00 | 0.00 |
December | 0.179583E+10 | 0.116030E+10 | 0.115060E+10 | 0.514424E+09 | 0.636179E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.325337E+11 | 0.727699E+10 | 0.173953E+11 | 0.666674E+10 | 0.107286E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163007E+10 | 0.141052E+09 | 0.111136E+10 | 0.399387E+09 | 0.632240E+09 | 0.00 | 0.00 |
Maximum of Months | 0.353875E+10 | 0.134708E+10 | 0.184348E+10 | 0.853588E+09 | 0.113571E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.828975E+09 | 0.190837E+10 | 0.770701E+09 | 0.00 | 0.770701E+09 | 0.00 | 0.00 |
February | 0.113781E+10 | 0.141731E+10 | 0.823965E+09 | 0.00 | 0.823965E+09 | 0.00 | 0.00 |
March | 0.150393E+10 | 0.130712E+10 | 0.108792E+10 | 0.00 | 0.108792E+10 | 0.00 | 0.00 |
April | 0.203630E+10 | 0.810714E+09 | 0.117974E+10 | 5299525.40 | 0.117444E+10 | 0.00 | 0.00 |
May | 0.290943E+10 | 0.429365E+09 | 0.139211E+10 | 62272328.66 | 0.132984E+10 | 0.00 | 0.00 |
June | 0.324824E+10 | 0.187107E+09 | 0.143910E+10 | 0.103620E+09 | 0.133548E+10 | 0.00 | 0.00 |
July | 0.355908E+10 | 0.283612E+09 | 0.150487E+10 | 73741369.08 | 0.143112E+10 | 0.00 | 0.00 |
August | 0.299789E+10 | 0.191886E+09 | 0.133183E+10 | 12249154.86 | 0.131958E+10 | 0.00 | 0.00 |
September | 0.267549E+10 | 0.307727E+09 | 0.114338E+10 | 90452.03 | 0.114329E+10 | 0.00 | 0.00 |
October | 0.203506E+10 | 0.513739E+09 | 0.989802E+09 | 0.00 | 0.989802E+09 | 0.00 | 0.00 |
November | 0.138507E+10 | 0.950072E+09 | 0.832876E+09 | 0.00 | 0.832876E+09 | 0.00 | 0.00 |
December | 0.940986E+09 | 0.161093E+10 | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.252583E+11 | 0.991795E+10 | 0.132586E+11 | 0.257273E+09 | 0.130013E+11 | 0.00 | 0.00 |
Minimum of Months | 0.828975E+09 | 0.187107E+09 | 0.762320E+09 | 0.00 | 0.762320E+09 | 0.00 | 0.00 |
Maximum of Months | 0.355908E+10 | 0.190837E+10 | 0.150487E+10 | 0.103620E+09 | 0.143112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177540E+10 | 0.120268E+10 | 0.123715E+10 | 0.592673E+09 | 0.644480E+09 | 0.00 | 0.00 |
February | 0.201595E+10 | 0.895723E+09 | 0.129026E+10 | 0.597264E+09 | 0.692996E+09 | 0.00 | 0.00 |
March | 0.273793E+10 | 0.813410E+09 | 0.174409E+10 | 0.824532E+09 | 0.919560E+09 | 0.00 | 0.00 |
April | 0.322680E+10 | 0.546298E+09 | 0.183172E+10 | 0.817307E+09 | 0.101442E+10 | 0.00 | 0.00 |
May | 0.346328E+10 | 0.281519E+09 | 0.179065E+10 | 0.713077E+09 | 0.107757E+10 | 0.00 | 0.00 |
June | 0.348439E+10 | 0.124817E+09 | 0.171038E+10 | 0.656947E+09 | 0.105344E+10 | 0.00 | 0.00 |
July | 0.382868E+10 | 0.195286E+09 | 0.181602E+10 | 0.654893E+09 | 0.116112E+10 | 0.00 | 0.00 |
August | 0.340006E+10 | 0.128794E+09 | 0.166059E+10 | 0.555266E+09 | 0.110532E+10 | 0.00 | 0.00 |
September | 0.321534E+10 | 0.208595E+09 | 0.154927E+10 | 0.560069E+09 | 0.989205E+09 | 0.00 | 0.00 |
October | 0.283062E+10 | 0.344165E+09 | 0.147358E+10 | 0.634613E+09 | 0.838965E+09 | 0.00 | 0.00 |
November | 0.198319E+10 | 0.602855E+09 | 0.115742E+10 | 0.461509E+09 | 0.695913E+09 | 0.00 | 0.00 |
December | 0.141914E+10 | 0.103742E+10 | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333808E+11 | 0.638156E+10 | 0.182272E+11 | 0.740923E+10 | 0.108180E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141914E+10 | 0.124817E+09 | 0.966110E+09 | 0.341084E+09 | 0.625026E+09 | 0.00 | 0.00 |
Maximum of Months | 0.382868E+10 | 0.120268E+10 | 0.183172E+10 | 0.824532E+09 | 0.116112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.582333E+10 | 0.185043E+10 | 0.362225E+10 | 0.235329E+10 | 0.126895E+10 | 0.00 | 0.00 |
February | 0.503852E+10 | 0.140402E+10 | 0.295974E+10 | 0.171257E+10 | 0.124717E+10 | 0.00 | 0.00 |
March | 0.434471E+10 | 0.129011E+10 | 0.251588E+10 | 0.106369E+10 | 0.145219E+10 | 0.00 | 0.00 |
April | 0.316140E+10 | 0.842376E+09 | 0.165557E+10 | 0.290323E+09 | 0.136524E+10 | 0.00 | 0.00 |
May | 0.287919E+10 | 0.421789E+09 | 0.137089E+10 | 29658913.09 | 0.134123E+10 | 0.00 | 0.00 |
June | 0.287352E+10 | 0.190803E+09 | 0.126486E+10 | 2387010.47 | 0.126248E+10 | 0.00 | 0.00 |
July | 0.333162E+10 | 0.283338E+09 | 0.139947E+10 | 12971867.25 | 0.138650E+10 | 0.00 | 0.00 |
August | 0.359385E+10 | 0.194308E+09 | 0.158835E+10 | 0.134034E+09 | 0.145432E+10 | 0.00 | 0.00 |
September | 0.441164E+10 | 0.323292E+09 | 0.196771E+10 | 0.482193E+09 | 0.148552E+10 | 0.00 | 0.00 |
October | 0.553328E+10 | 0.560691E+09 | 0.279620E+10 | 0.131189E+10 | 0.148431E+10 | 0.00 | 0.00 |
November | 0.545856E+10 | 0.962487E+09 | 0.307883E+10 | 0.171833E+10 | 0.136050E+10 | 0.00 | 0.00 |
December | 0.575526E+10 | 0.161317E+10 | 0.349083E+10 | 0.220182E+10 | 0.128901E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.522049E+11 | 0.993682E+10 | 0.277106E+11 | 0.113132E+11 | 0.163974E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287352E+10 | 0.190803E+09 | 0.126486E+10 | 2387010.47 | 0.124717E+10 | 0.00 | 0.00 |
Maximum of Months | 0.582333E+10 | 0.185043E+10 | 0.362225E+10 | 0.235329E+10 | 0.148552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.163079E+10 | 0.128302E+10 | 0.111138E+10 | 0.479130E+09 | 0.632246E+09 | 0.00 | 0.00 |
February | 0.205175E+10 | 0.975537E+09 | 0.125525E+10 | 0.568074E+09 | 0.687180E+09 | 0.00 | 0.00 |
March | 0.283259E+10 | 0.909049E+09 | 0.173066E+10 | 0.790310E+09 | 0.940349E+09 | 0.00 | 0.00 |
April | 0.330174E+10 | 0.593923E+09 | 0.184350E+10 | 0.853602E+09 | 0.989901E+09 | 0.00 | 0.00 |
May | 0.341257E+10 | 0.321776E+09 | 0.173661E+10 | 0.668514E+09 | 0.106810E+10 | 0.00 | 0.00 |
June | 0.298425E+10 | 0.142327E+09 | 0.142398E+10 | 0.399438E+09 | 0.102454E+10 | 0.00 | 0.00 |
July | 0.353711E+10 | 0.210892E+09 | 0.164447E+10 | 0.508748E+09 | 0.113572E+10 | 0.00 | 0.00 |
August | 0.337858E+10 | 0.149008E+09 | 0.164073E+10 | 0.534711E+09 | 0.110602E+10 | 0.00 | 0.00 |
September | 0.287429E+10 | 0.220014E+09 | 0.135448E+10 | 0.399394E+09 | 0.955087E+09 | 0.00 | 0.00 |
October | 0.271728E+10 | 0.379486E+09 | 0.139237E+10 | 0.542790E+09 | 0.849583E+09 | 0.00 | 0.00 |
November | 0.196637E+10 | 0.661109E+09 | 0.111151E+10 | 0.407709E+09 | 0.703803E+09 | 0.00 | 0.00 |
December | 0.180106E+10 | 0.109002E+10 | 0.115062E+10 | 0.514433E+09 | 0.636185E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.324884E+11 | 0.693616E+10 | 0.173956E+11 | 0.666685E+10 | 0.107287E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163079E+10 | 0.142327E+09 | 0.111138E+10 | 0.399394E+09 | 0.632246E+09 | 0.00 | 0.00 |
Maximum of Months | 0.353711E+10 | 0.128302E+10 | 0.184350E+10 | 0.853602E+09 | 0.113572E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.356314E+10 | -0.333105E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232089427.2 | 60.05 | 0.00 | 0.00 |
February | 0.320889E+10 | -0.299936E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209531961.4 | 60.05 | 0.00 | 0.00 |
March | 0.367566E+10 | -0.344344E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232215635.9 | 60.05 | 0.00 | 0.00 |
April | 0.318424E+10 | -0.295991E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224323465.5 | 60.05 | 0.00 | 0.00 |
May | 0.325392E+10 | -0.302209E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231826420.2 | 60.05 | 0.00 | 0.00 |
June | 0.310988E+10 | -0.288520E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224672733.0 | 60.05 | 0.00 | 0.00 |
July | 0.290363E+10 | -0.267180E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231830097.6 | 60.05 | 0.00 | 0.00 |
August | 0.322138E+10 | -0.298917E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232214179.6 | 60.05 | 0.00 | 0.00 |
September | 0.301527E+10 | -0.279079E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224484524.4 | 60.05 | 0.00 | 0.00 |
October | 0.325739E+10 | -0.302594E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231448181.2 | 60.05 | 0.00 | 0.00 |
November | 0.334437E+10 | -0.312062E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223751685.2 | 60.05 | 0.00 | 0.00 |
December | 0.342793E+10 | -0.319605E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231881115.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.391657E+11 | -0.364354E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273027E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.290363E+10 | -0.344344E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -232215635.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.367566E+10 | -0.267180E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209531961.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.50 | 0.48 | 01-JAN-07:40 | 6551.06 | 35.71 | 274.83 | 291.17 | 1299.40 | 24.73 | 181.00 | 272.50 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2424.36 | 24.88 | 135.17 | 277.00 | 1008.79 | 20.26 | 116.83 | 248.50 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1485.35 | 18.47 | 5.67 | 324.83 | 826.62 | 20.35 | 126.83 | 289.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 1148.20 | 17.89 | 0.00 | 324.17 | 655.66 | 19.99 | 66.33 | 284.67 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:10 | 981.82 | 17.39 | 0.00 | 342.67 | 552.14 | 19.51 | 32.17 | 286.33 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:10 | 927.07 | 16.71 | 0.00 | 320.17 | 516.33 | 18.85 | 25.67 | 267.00 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1039.40 | 17.59 | 0.00 | 351.00 | 580.18 | 19.74 | 52.33 | 296.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1238.23 | 18.08 | 0.00 | 340.67 | 678.77 | 20.20 | 111.00 | 297.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 1494.04 | 18.28 | 0.00 | 315.00 | 799.17 | 20.43 | 155.17 | 275.33 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:40 | 1992.52 | 20.13 | 31.67 | 314.67 | 996.08 | 21.27 | 175.83 | 283.50 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3729.21 | 30.94 | 246.67 | 290.33 | 1123.45 | 24.09 | 223.00 | 270.17 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6223.44 | 35.99 | 278.50 | 277.67 | 1507.38 | 26.10 | 197.83 | 259.17 |
Annual Sum or Average | 4111.50 | 0.51 | 2252.27 | 21.98 | 972.50 | 3769.33 | 846.78 | 21.08 | 1464.00 | 3330.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 927.07 | 16.71 | 0.00 | 277.00 | 516.33 | 18.85 | 25.67 | 248.50 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6551.06 | 35.99 | 278.50 | 351.00 | 1507.38 | 26.10 | 223.00 | 297.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-07:40 | 2063.74 | 22.34 | 102.50 | 264.17 | 1093.16 | 22.78 | 74.17 | 217.17 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-07:49 | 2157.38 | 21.44 | 100.33 | 256.83 | 819.47 | 20.53 | 45.67 | 218.00 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 2002.86 | 19.42 | 86.00 | 316.83 | 1086.51 | 21.57 | 67.67 | 280.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2386.03 | 20.44 | 99.83 | 321.00 | 1277.45 | 21.50 | 70.67 | 283.00 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2185.03 | 19.78 | 103.67 | 352.33 | 933.61 | 20.45 | 57.67 | 302.33 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2117.96 | 19.94 | 111.33 | 336.67 | 913.48 | 20.72 | 64.67 | 290.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2100.83 | 20.32 | 115.50 | 359.00 | 912.24 | 20.22 | 54.00 | 310.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2073.97 | 20.59 | 97.17 | 341.33 | 941.91 | 20.56 | 47.00 | 300.17 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 2033.13 | 21.20 | 103.67 | 307.17 | 1059.16 | 22.12 | 74.83 | 264.50 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 2009.85 | 21.31 | 94.33 | 300.00 | 1070.13 | 22.25 | 68.00 | 262.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1598.90 | 20.19 | 84.50 | 268.67 | 825.26 | 21.74 | 60.17 | 224.00 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:39 | 1733.51 | 21.04 | 87.17 | 250.17 | 715.57 | 20.42 | 36.83 | 200.83 |
Annual Sum or Average | 4111.50 | 0.51 | 2049.29 | 20.60 | 1186.00 | 3674.17 | 974.52 | 21.20 | 721.33 | 3153.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1598.90 | 19.42 | 84.50 | 250.17 | 715.57 | 20.22 | 36.83 | 200.83 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2386.03 | 22.34 | 115.50 | 359.00 | 1277.45 | 22.78 | 74.83 | 310.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.55 | 0.48 | 01-JAN-09:30 | 513.21 | 14.58 | 0.00 | 239.17 | 327.22 | 17.03 | 0.00 | 132.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-08:00 | 585.34 | 15.46 | 0.00 | 245.50 | 363.05 | 17.74 | 0.00 | 163.33 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-09:20 | 700.99 | 16.70 | 0.00 | 307.83 | 426.03 | 18.86 | 0.00 | 243.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 838.20 | 17.64 | 0.00 | 329.67 | 501.97 | 19.70 | 5.67 | 284.67 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:40 | 1000.24 | 19.08 | 27.00 | 364.33 | 557.09 | 20.15 | 66.83 | 321.50 |
June | 388.17 | 0.50 | 0.48 | 01-JUN-06:10 | 1066.65 | 20.53 | 66.17 | 353.33 | 586.71 | 21.36 | 113.50 | 310.50 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1118.28 | 19.36 | 26.17 | 371.50 | 617.85 | 21.48 | 144.67 | 333.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:10 | 1005.75 | 18.08 | 0.00 | 347.50 | 572.63 | 20.18 | 56.17 | 308.33 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 844.56 | 17.22 | 0.00 | 311.67 | 486.26 | 19.32 | 0.67 | 254.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 670.92 | 16.31 | 0.00 | 289.83 | 411.89 | 18.53 | 0.00 | 214.67 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-07:00 | 591.12 | 15.61 | 0.00 | 250.33 | 355.94 | 17.88 | 0.00 | 161.17 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:00 | 560.80 | 15.31 | 0.00 | 235.00 | 346.71 | 17.71 | 0.00 | 143.83 |
Annual Sum or Average | 4111.50 | 0.52 | 812.69 | 17.34 | 119.33 | 3645.67 | 473.09 | 19.31 | 387.50 | 2871.17 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 513.21 | 14.58 | 0.00 | 235.00 | 327.22 | 17.03 | 0.00 | 132.17 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 1118.28 | 20.53 | 66.17 | 371.50 | 617.85 | 21.48 | 144.67 | 333.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-09:30 | 1776.15 | 21.19 | 91.33 | 265.50 | 971.09 | 22.00 | 65.83 | 213.00 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1632.78 | 19.32 | 70.83 | 262.00 | 835.79 | 20.22 | 46.50 | 220.00 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-09:09 | 1965.78 | 19.37 | 86.00 | 314.00 | 1038.87 | 21.57 | 69.17 | 278.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:50 | 2176.28 | 19.11 | 80.67 | 331.33 | 1174.72 | 20.37 | 51.83 | 293.00 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1961.86 | 14.27 | 0.00 | 346.50 | 1022.61 | 17.55 | 0.00 | 302.67 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-07:30 | 1641.16 | 13.97 | 0.00 | 330.00 | 744.13 | 17.18 | 0.00 | 282.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:10 | 1859.86 | 14.93 | 3.67 | 354.33 | 839.52 | 17.99 | 0.00 | 311.00 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:00 | 2005.77 | 17.84 | 56.83 | 338.83 | 1043.92 | 18.38 | 5.50 | 298.33 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:40 | 1652.11 | 19.23 | 80.50 | 310.83 | 862.75 | 20.43 | 51.83 | 270.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 1992.89 | 21.55 | 103.00 | 296.67 | 1058.63 | 22.63 | 77.67 | 258.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:09 | 1554.98 | 19.77 | 82.83 | 268.83 | 822.86 | 21.93 | 67.50 | 224.50 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 1780.22 | 21.32 | 84.50 | 261.50 | 963.85 | 23.20 | 67.50 | 222.67 |
Annual Sum or Average | 4111.50 | 0.51 | 1839.41 | 18.24 | 740.17 | 3680.33 | 947.28 | 20.10 | 503.33 | 3174.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1554.98 | 13.97 | 0.00 | 261.50 | 744.13 | 17.18 | 0.00 | 213.00 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2176.28 | 21.55 | 103.00 | 354.33 | 1174.72 | 23.20 | 77.67 | 311.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 6431.45 | 35.41 | 274.67 | 290.17 | 1207.40 | 22.30 | 81.17 | 270.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2328.36 | 22.48 | 134.33 | 275.00 | 936.66 | 17.38 | 0.00 | 245.50 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1415.75 | 14.76 | 5.67 | 322.00 | 776.92 | 17.97 | 0.00 | 285.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 1101.71 | 14.38 | 0.00 | 321.67 | 626.19 | 17.84 | 0.00 | 280.50 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:19 | 945.77 | 13.76 | 0.00 | 340.67 | 530.96 | 17.19 | 0.00 | 280.33 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:19 | 893.48 | 12.99 | 0.00 | 318.17 | 496.62 | 16.45 | 0.00 | 261.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1000.81 | 13.91 | 0.00 | 348.67 | 557.46 | 17.38 | 0.00 | 292.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:30 | 1189.68 | 14.48 | 0.00 | 339.00 | 648.80 | 17.90 | 0.00 | 294.33 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 1430.38 | 14.44 | 0.00 | 312.50 | 757.19 | 17.89 | 0.00 | 271.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:49 | 1904.46 | 16.56 | 31.67 | 314.00 | 932.60 | 18.75 | 9.17 | 280.50 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3627.73 | 29.90 | 244.83 | 289.50 | 1048.45 | 21.61 | 71.33 | 268.33 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6099.58 | 35.77 | 278.50 | 276.50 | 1413.85 | 23.73 | 92.50 | 257.50 |
Annual Sum or Average | 4111.50 | 0.51 | 2183.52 | 19.09 | 969.67 | 3747.83 | 798.69 | 18.66 | 254.17 | 3288.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 893.48 | 12.99 | 0.00 | 275.00 | 496.62 | 16.45 | 0.00 | 245.50 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6431.45 | 35.77 | 278.50 | 348.67 | 1413.85 | 23.73 | 92.50 | 294.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-07:40 | 2013.81 | 21.89 | 102.50 | 263.00 | 1054.00 | 22.58 | 74.17 | 213.83 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-07:49 | 2106.20 | 20.98 | 99.83 | 254.50 | 780.16 | 20.32 | 45.50 | 214.33 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 1948.62 | 18.91 | 86.00 | 315.00 | 1039.62 | 21.38 | 67.67 | 276.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2312.02 | 19.98 | 99.83 | 318.67 | 1229.00 | 21.32 | 70.67 | 279.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2128.04 | 19.32 | 103.50 | 350.33 | 879.50 | 19.66 | 50.17 | 296.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2070.25 | 19.50 | 111.17 | 333.67 | 871.65 | 20.57 | 64.50 | 286.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2047.28 | 19.87 | 115.50 | 355.67 | 868.95 | 20.06 | 54.00 | 305.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2007.45 | 20.15 | 97.17 | 340.33 | 898.81 | 20.38 | 47.17 | 296.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 1974.46 | 20.58 | 101.83 | 305.83 | 1016.27 | 21.94 | 74.83 | 261.67 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 1913.12 | 19.48 | 81.33 | 297.17 | 1024.87 | 21.93 | 66.00 | 259.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1551.11 | 19.69 | 84.33 | 266.17 | 773.15 | 20.70 | 51.83 | 217.67 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:39 | 1691.55 | 20.55 | 87.00 | 248.50 | 683.61 | 20.17 | 34.50 | 195.33 |
Annual Sum or Average | 4111.50 | 0.52 | 1990.86 | 20.02 | 1170.00 | 3648.83 | 930.16 | 20.88 | 701.00 | 3102.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1551.11 | 18.91 | 81.33 | 248.50 | 683.61 | 19.66 | 34.50 | 195.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2312.02 | 21.89 | 115.50 | 355.67 | 1229.00 | 22.58 | 74.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.55 | 0.48 | 01-JAN-09:39 | 494.61 | 11.03 | 0.00 | 235.00 | 317.51 | 14.74 | 0.00 | 121.83 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-08:00 | 564.74 | 11.91 | 0.00 | 242.00 | 352.10 | 15.51 | 0.00 | 157.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:20 | 676.43 | 13.29 | 0.00 | 303.50 | 412.76 | 16.82 | 0.00 | 236.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 808.49 | 14.28 | 0.00 | 326.33 | 485.64 | 17.76 | 0.00 | 279.50 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:30 | 964.08 | 15.67 | 26.67 | 363.50 | 541.56 | 18.92 | 25.83 | 320.67 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:10 | 1027.18 | 17.40 | 64.83 | 351.67 | 562.80 | 19.08 | 32.83 | 305.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 1073.34 | 14.57 | 0.00 | 368.17 | 593.11 | 19.26 | 26.17 | 328.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:10 | 968.60 | 14.57 | 0.00 | 345.83 | 551.17 | 18.03 | 0.00 | 302.83 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 814.00 | 13.66 | 0.00 | 309.67 | 468.90 | 17.09 | 0.00 | 245.67 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 646.18 | 12.94 | 0.00 | 286.83 | 398.50 | 16.46 | 0.00 | 206.50 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:09 | 569.57 | 11.93 | 0.00 | 246.50 | 344.16 | 15.54 | 0.00 | 149.83 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-09:09 | 540.01 | 11.67 | 0.00 | 231.17 | 335.56 | 15.37 | 0.00 | 131.50 |
Annual Sum or Average | 4111.50 | 0.52 | 782.78 | 13.75 | 91.50 | 3610.17 | 456.84 | 17.21 | 84.83 | 2785.33 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 494.61 | 11.03 | 0.00 | 231.17 | 317.51 | 14.74 | 0.00 | 121.83 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 1073.34 | 17.40 | 64.83 | 368.17 | 593.11 | 19.26 | 32.83 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1731.85 | 20.80 | 91.17 | 262.00 | 936.57 | 21.89 | 65.83 | 208.33 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1582.12 | 18.89 | 70.83 | 260.00 | 797.84 | 20.09 | 46.50 | 217.17 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-09:20 | 1911.79 | 18.91 | 86.00 | 311.50 | 992.52 | 21.43 | 69.17 | 275.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:50 | 2052.25 | 18.64 | 80.67 | 327.17 | 1125.66 | 20.20 | 51.83 | 290.17 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1903.01 | 13.71 | 0.00 | 344.67 | 981.53 | 17.34 | 0.00 | 297.67 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:30 | 1598.34 | 13.39 | 0.00 | 327.67 | 710.23 | 16.95 | 0.00 | 277.67 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1807.57 | 14.37 | 3.67 | 352.33 | 800.96 | 17.77 | 0.00 | 306.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:00 | 1938.68 | 17.35 | 56.83 | 337.50 | 1000.43 | 18.20 | 5.50 | 294.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:40 | 1605.44 | 18.78 | 80.50 | 308.50 | 825.53 | 20.28 | 51.83 | 266.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 1939.62 | 21.14 | 103.00 | 294.17 | 1018.09 | 22.51 | 77.17 | 255.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:09 | 1509.32 | 19.34 | 82.50 | 266.67 | 788.63 | 21.81 | 67.50 | 221.17 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 1726.14 | 20.63 | 81.83 | 258.50 | 924.10 | 23.10 | 67.17 | 218.50 |
Annual Sum or Average | 4111.50 | 0.51 | 1781.21 | 17.74 | 737.00 | 3650.67 | 907.44 | 19.94 | 502.50 | 3128.33 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1509.32 | 13.39 | 0.00 | 258.50 | 710.23 | 16.95 | 0.00 | 208.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2052.25 | 21.14 | 103.00 | 352.33 | 1125.66 | 23.10 | 77.17 | 306.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 6431.39 | 35.41 | 274.67 | 290.17 | 1207.32 | 22.30 | 81.17 | 270.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:20 | 2328.28 | 22.48 | 134.33 | 275.00 | 936.59 | 17.38 | 0.00 | 245.50 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:49 | 1415.68 | 14.76 | 5.67 | 322.00 | 776.86 | 17.97 | 0.00 | 285.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 1101.65 | 14.38 | 0.00 | 321.67 | 626.14 | 17.84 | 0.00 | 280.50 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:19 | 945.72 | 13.76 | 0.00 | 340.67 | 530.92 | 17.19 | 0.00 | 280.33 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:19 | 893.42 | 12.99 | 0.00 | 318.17 | 496.58 | 16.45 | 0.00 | 261.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1000.76 | 13.91 | 0.00 | 348.67 | 557.42 | 17.38 | 0.00 | 292.67 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:30 | 1189.60 | 14.48 | 0.00 | 339.00 | 648.75 | 17.90 | 0.00 | 294.33 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 1430.28 | 14.45 | 0.00 | 312.50 | 757.12 | 17.89 | 0.00 | 271.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:49 | 1904.36 | 16.56 | 31.67 | 314.00 | 932.52 | 18.75 | 9.17 | 280.50 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3627.64 | 29.90 | 244.83 | 289.50 | 1048.36 | 21.61 | 71.33 | 268.33 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 6099.52 | 35.77 | 278.50 | 276.50 | 1413.77 | 23.73 | 92.50 | 257.33 |
Annual Sum or Average | 4111.50 | 0.51 | 2183.45 | 19.09 | 969.67 | 3747.83 | 798.64 | 18.66 | 254.17 | 3288.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 893.42 | 12.99 | 0.00 | 275.00 | 496.58 | 16.45 | 0.00 | 245.50 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6431.39 | 35.77 | 278.50 | 348.67 | 1413.77 | 23.73 | 92.50 | 294.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-07:40 | 2013.79 | 21.89 | 102.50 | 263.00 | 1053.96 | 22.58 | 74.17 | 213.83 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-07:49 | 2106.17 | 20.98 | 99.83 | 254.50 | 780.11 | 20.32 | 45.50 | 214.33 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 1948.58 | 18.92 | 86.00 | 315.00 | 1039.58 | 21.38 | 67.67 | 276.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2311.97 | 19.98 | 99.83 | 318.67 | 1228.94 | 21.32 | 70.67 | 279.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2127.98 | 19.32 | 103.50 | 350.33 | 879.45 | 19.66 | 50.17 | 296.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-05:00 | 2070.18 | 19.50 | 111.17 | 333.67 | 871.60 | 20.57 | 64.50 | 286.83 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:19 | 2047.22 | 19.87 | 115.50 | 355.67 | 868.89 | 20.06 | 54.00 | 305.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2007.38 | 20.15 | 97.17 | 340.33 | 898.74 | 20.38 | 47.17 | 296.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 1974.39 | 20.58 | 101.83 | 305.83 | 1016.21 | 21.94 | 74.83 | 261.67 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-07:10 | 1913.08 | 19.48 | 81.33 | 297.17 | 1024.82 | 21.93 | 66.00 | 259.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1551.08 | 19.69 | 84.33 | 266.17 | 773.11 | 20.71 | 51.83 | 217.67 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:39 | 1691.51 | 20.55 | 87.00 | 248.50 | 683.57 | 20.17 | 34.50 | 195.33 |
Annual Sum or Average | 4111.50 | 0.52 | 1990.81 | 20.02 | 1170.00 | 3648.83 | 930.11 | 20.88 | 701.00 | 3102.83 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1551.08 | 18.92 | 81.33 | 248.50 | 683.57 | 19.66 | 34.50 | 195.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2311.97 | 21.89 | 115.50 | 355.67 | 1228.94 | 22.58 | 74.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.55 | 0.48 | 01-JAN-09:39 | 494.60 | 11.04 | 0.00 | 235.00 | 317.49 | 14.74 | 0.00 | 121.83 |
February | 304.33 | 0.54 | 0.48 | 01-FEB-08:00 | 564.73 | 11.91 | 0.00 | 242.00 | 352.07 | 15.51 | 0.00 | 157.50 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-09:20 | 676.41 | 13.29 | 0.00 | 303.50 | 412.73 | 16.82 | 0.00 | 236.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 808.47 | 14.28 | 0.00 | 326.33 | 485.61 | 17.76 | 0.00 | 279.50 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:30 | 964.04 | 15.67 | 26.67 | 363.50 | 541.52 | 18.92 | 25.83 | 320.67 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:10 | 1027.12 | 17.40 | 64.83 | 351.67 | 562.76 | 19.08 | 32.83 | 305.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 1073.28 | 14.57 | 0.00 | 368.17 | 593.07 | 19.26 | 26.17 | 328.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:10 | 968.55 | 14.57 | 0.00 | 345.83 | 551.13 | 18.03 | 0.00 | 302.83 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 813.96 | 13.67 | 0.00 | 309.67 | 468.87 | 17.09 | 0.00 | 245.67 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 646.17 | 12.94 | 0.00 | 286.83 | 398.48 | 16.46 | 0.00 | 206.50 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:09 | 569.55 | 11.93 | 0.00 | 246.50 | 344.14 | 15.54 | 0.00 | 149.83 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-09:09 | 540.00 | 11.67 | 0.00 | 231.17 | 335.54 | 15.37 | 0.00 | 131.50 |
Annual Sum or Average | 4111.50 | 0.52 | 782.75 | 13.75 | 91.50 | 3610.17 | 456.81 | 17.21 | 84.83 | 2785.33 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 494.60 | 11.04 | 0.00 | 231.17 | 317.49 | 14.74 | 0.00 | 121.83 | |
Maximum of Months | 403.83 | 0.55 | 0.48 | 1073.28 | 17.40 | 64.83 | 368.17 | 593.07 | 19.26 | 32.83 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1731.82 | 20.80 | 91.17 | 262.00 | 936.53 | 21.89 | 65.83 | 208.33 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1582.09 | 18.89 | 70.83 | 260.00 | 797.79 | 20.10 | 46.50 | 217.17 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-09:20 | 1911.75 | 18.91 | 86.00 | 311.50 | 992.47 | 21.43 | 69.17 | 275.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-08:50 | 2052.20 | 18.64 | 80.67 | 327.17 | 1125.61 | 20.20 | 51.83 | 290.17 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1902.95 | 13.71 | 0.00 | 344.67 | 981.48 | 17.35 | 0.00 | 297.67 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:30 | 1598.28 | 13.40 | 0.00 | 327.67 | 710.18 | 16.95 | 0.00 | 277.67 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1807.51 | 14.37 | 3.67 | 352.33 | 800.90 | 17.77 | 0.00 | 306.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:00 | 1938.61 | 17.35 | 56.83 | 337.50 | 1000.37 | 18.20 | 5.50 | 294.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:40 | 1605.38 | 18.79 | 80.50 | 308.50 | 825.48 | 20.28 | 51.83 | 266.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 1939.58 | 21.14 | 103.00 | 294.17 | 1018.03 | 22.51 | 77.17 | 255.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-08:09 | 1509.28 | 19.34 | 82.50 | 266.67 | 788.58 | 21.81 | 67.50 | 221.17 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:09 | 1726.11 | 20.63 | 81.83 | 258.50 | 924.05 | 23.10 | 67.17 | 218.50 |
Annual Sum or Average | 4111.50 | 0.51 | 1781.17 | 17.74 | 737.00 | 3650.67 | 907.39 | 19.95 | 502.50 | 3128.33 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1509.28 | 13.40 | 0.00 | 258.50 | 710.18 | 16.95 | 0.00 | 208.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 2052.20 | 21.14 | 103.00 | 352.33 | 1125.61 | 23.10 | 77.17 | 306.83 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5685904.88 | 1218.09 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5685904.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5685904.88 | 1218.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213962E+09 | 5927.74 | 09-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74715402.04 | 5927.74 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163195E+09 | 5927.74 | 01-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9786517.59 | 5927.74 | 19-APR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39808719.47 | 5927.74 | 13-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142832E+09 | 5927.74 | 12-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213962E+09 | 5927.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53205.33 | 233.71 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 53205.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53205.33 | 233.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12135471.45 | 2225.02 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2866070.48 | 508.85 | 16-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15001541.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12135471.45 | 2225.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2244823.56 | 6073.14 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2244823.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2244823.56 | 6073.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 102900.60 | 828.18 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 987000.55 | 4886.95 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 177903.98 | 507.64 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91067.61 | 495.13 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1358872.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 987000.55 | 4886.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 836488.16 | 2008.02 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7560608.47 | 7408.26 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 953794.31 | 1776.19 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 287692.70 | 958.63 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9638583.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7560608.47 | 7408.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1130.61 | 11.31 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4725657.96 | 4896.69 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82435.10 | 355.38 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4809223.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4725657.96 | 4896.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2342242.38 | 260.25 | 04-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2731603.68 | 260.25 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1829179.76 | 260.25 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6903025.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2731603.68 | 260.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7633006.45 | 12198.99 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7633006.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7633006.45 | 12198.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12345094.32 | 9473.66 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21850017.80 | 9473.66 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13030855.23 | 9473.66 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23993726.98 | 9473.66 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71219694.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23993726.98 | 9473.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10298663.66 | 6230.37 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12377531.93 | 6230.37 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7571063.19 | 6230.37 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 313205.41 | 2610.05 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21648588.02 | 6230.37 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52209052.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21648588.02 | 6230.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 39110922.31 | 9481.84 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45288227.04 | 9481.84 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21108629.72 | 9481.84 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4343431.25 | 6524.72 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45311346.54 | 9481.84 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45311346.54 | 9481.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20603028.03 | 6229.22 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27441011.29 | 6229.22 | 04-FEB-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10856467.33 | 6229.22 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2099667.01 | 2262.92 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26087807.48 | 6229.22 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 87087981.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27441011.29 | 6229.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.486245E+11 | 0.355144E+11 | 83312.21 | 02-JAN-14:00 | 56084.14 | 0.00 |
February | 0.00 | 0.00 | 0.497638E+11 | 0.370304E+11 | 76209.59 | 18-FEB-07:03 | 49082.18 | 0.00 |
March | 0.00 | 0.00 | 0.602014E+11 | 0.436347E+11 | 87784.60 | 14-MAR-06:03 | 46743.20 | 0.00 |
April | 0.00 | 0.00 | 0.688958E+11 | 0.493688E+11 | 89183.64 | 12-APR-06:03 | 53155.60 | 0.00 |
May | 0.00 | 0.00 | 0.932845E+11 | 0.621367E+11 | 105969.76 | 31-MAY-06:03 | 70330.57 | 0.00 |
June | 0.00 | 0.00 | 0.105181E+12 | 0.654721E+11 | 111599.65 | 08-JUN-06:03 | 74218.52 | 0.00 |
July | 0.00 | 0.00 | 0.111063E+12 | 0.692660E+11 | 110105.36 | 11-JUL-06:03 | 75339.22 | 0.00 |
August | 0.00 | 0.00 | 0.114728E+12 | 0.713129E+11 | 112765.26 | 18-AUG-04:03 | 73998.27 | 0.00 |
September | 0.00 | 0.00 | 0.105690E+12 | 0.661283E+11 | 113458.60 | 19-SEP-04:02 | 73611.71 | 0.00 |
October | 0.00 | 0.00 | 0.971864E+11 | 0.635918E+11 | 114256.17 | 04-OCT-04:02 | 70506.53 | 0.00 |
November | 0.00 | 0.00 | 0.762765E+11 | 0.510111E+11 | 103262.71 | 04-NOV-04:03 | 52865.30 | 0.00 |
December | 0.00 | 0.00 | 0.521823E+11 | 0.368034E+11 | 94493.57 | 11-DEC-07:03 | 70047.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.983077E+12 | 0.651270E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.486245E+11 | 0.355144E+11 | 76209.59 | 46743.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114728E+12 | 0.713129E+11 | 114256.17 | 75339.22 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.384415E+11 | 0.268582E+11 | 76829.92 | 02-JAN-14:00 | 50271.66 | 0.00 |
February | 0.00 | 0.00 | 0.410897E+11 | 0.294303E+11 | 62620.40 | 13-FEB-06:12 | 31861.83 | 0.00 |
March | 0.00 | 0.00 | 0.512012E+11 | 0.359481E+11 | 83517.85 | 06-MAR-07:03 | 50847.18 | 0.00 |
April | 0.00 | 0.00 | 0.601173E+11 | 0.419362E+11 | 78752.02 | 13-APR-05:03 | 48573.71 | 0.00 |
May | 0.00 | 0.00 | 0.818727E+11 | 0.526934E+11 | 103554.12 | 30-MAY-04:02 | 68316.56 | 0.00 |
June | 0.00 | 0.00 | 0.930355E+11 | 0.557402E+11 | 108290.88 | 19-JUN-04:03 | 60874.08 | 0.00 |
July | 0.00 | 0.00 | 0.977668E+11 | 0.587674E+11 | 106412.91 | 03-JUL-04:02 | 65858.56 | 0.00 |
August | 0.00 | 0.00 | 0.988328E+11 | 0.588469E+11 | 106613.47 | 14-AUG-05:12 | 63838.22 | 0.00 |
September | 0.00 | 0.00 | 0.909063E+11 | 0.544529E+11 | 106391.36 | 19-SEP-04:02 | 64964.43 | 0.00 |
October | 0.00 | 0.00 | 0.811318E+11 | 0.512623E+11 | 108657.42 | 02-OCT-04:02 | 62009.27 | 0.00 |
November | 0.00 | 0.00 | 0.623768E+11 | 0.397756E+11 | 103014.66 | 04-NOV-05:03 | 59825.09 | 0.00 |
December | 0.00 | 0.00 | 0.422109E+11 | 0.282453E+11 | 83446.51 | 11-DEC-07:03 | 55905.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.838983E+12 | 0.533957E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.384415E+11 | 0.268582E+11 | 62620.40 | 31861.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.988328E+11 | 0.588469E+11 | 108657.42 | 68316.56 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.384854E+11 | 0.263376E+11 | 82248.03 | 02-JAN-14:00 | 55626.76 | 0.00 |
February | 0.00 | 0.00 | 0.424513E+11 | 0.302136E+11 | 66434.56 | 17-FEB-14:10 | 48862.09 | 0.00 |
March | 0.00 | 0.00 | 0.536299E+11 | 0.376981E+11 | 78289.39 | 27-MAR-15:00 | 59095.47 | 0.00 |
April | 0.00 | 0.00 | 0.645006E+11 | 0.455624E+11 | 94612.89 | 13-APR-05:03 | 56745.45 | 0.00 |
May | 0.00 | 0.00 | 0.876219E+11 | 0.579767E+11 | 118348.15 | 30-MAY-04:02 | 78321.71 | 0.00 |
June | 0.00 | 0.00 | 0.995949E+11 | 0.617948E+11 | 114651.12 | 25-JUN-13:43 | 72118.98 | 0.00 |
July | 0.00 | 0.00 | 0.104801E+12 | 0.653685E+11 | 119450.43 | 03-JUL-04:02 | 75002.80 | 0.00 |
August | 0.00 | 0.00 | 0.104511E+12 | 0.641939E+11 | 118517.54 | 01-AUG-04:02 | 78158.99 | 0.00 |
September | 0.00 | 0.00 | 0.958605E+11 | 0.590326E+11 | 120856.94 | 19-SEP-04:02 | 75162.22 | 0.00 |
October | 0.00 | 0.00 | 0.841260E+11 | 0.538253E+11 | 122371.53 | 02-OCT-04:02 | 69998.92 | 0.00 |
November | 0.00 | 0.00 | 0.640377E+11 | 0.408494E+11 | 103538.05 | 04-NOV-05:03 | 58207.12 | 0.00 |
December | 0.00 | 0.00 | 0.426340E+11 | 0.281150E+11 | 74640.41 | 08-DEC-15:50 | 52148.27 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.882254E+12 | 0.570968E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.384854E+11 | 0.263376E+11 | 66434.56 | 48862.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104801E+12 | 0.653685E+11 | 122371.53 | 78321.71 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1234.94 | 4498.46 | 18-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1231.08 | 4486.76 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1276.68 | 4397.95 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1133.37 | 4208.07 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1119.67 | 4017.02 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1104.42 | 3828.66 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 989.21 | 3713.35 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1107.31 | 3799.99 | 31-AUG-11:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1068.20 | 3964.29 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1121.18 | 4181.69 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1195.21 | 4364.22 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1184.68 | 4474.93 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1146.71 | ||||
Minimum of Months | 0.00 | 0.00 | 989.21 | 3713.35 | ||
Maximum of Months | 0.00 | 0.00 | 1276.68 | 4498.46 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.220559E+10 | 0.35 | 4563.59 | 02-JAN-15:10 | 1.12 |
February | 0.220149E+10 | 0.36 | 4376.30 | 21-FEB-16:50 | 1.10 |
March | 0.261493E+10 | 0.38 | 4931.63 | 06-MAR-07:03 | 1.18 |
April | 0.280067E+10 | 0.40 | 5454.86 | 17-APR-06:03 | 1.25 |
May | 0.362383E+10 | 0.46 | 9563.93 | 08-MAY-05:01 | 1.78 |
June | 0.380397E+10 | 0.49 | 9563.93 | 05-JUN-06:03 | 1.78 |
July | 0.407990E+10 | 0.49 | 9563.93 | 03-JUL-06:03 | 1.78 |
August | 0.430987E+10 | 0.51 | 9563.93 | 01-AUG-04:02 | 1.78 |
September | 0.394500E+10 | 0.49 | 9563.93 | 02-SEP-06:03 | 1.78 |
October | 0.384773E+10 | 0.47 | 9563.93 | 02-OCT-06:03 | 1.78 |
November | 0.307863E+10 | 0.41 | 8733.70 | 20-NOV-07:03 | 1.68 |
December | 0.227900E+10 | 0.35 | 9432.67 | 11-DEC-07:03 | 1.77 |
Annual Sum or Average | 0.387906E+11 | 0.43 | |||
Minimum of Months | 0.220149E+10 | 0.35 | 4376.30 | 1.10 | |
Maximum of Months | 0.430987E+10 | 0.51 | 9563.93 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159258E+10 | 0.32 | 4088.04 | 02-JAN-15:05 | 1.12 |
February | 0.164398E+10 | 0.34 | 3513.19 | 21-FEB-15:05 | 1.02 |
March | 0.206080E+10 | 0.36 | 5216.68 | 06-MAR-07:03 | 1.30 |
April | 0.223427E+10 | 0.38 | 4688.90 | 17-APR-06:03 | 1.22 |
May | 0.280811E+10 | 0.42 | 8614.45 | 08-MAY-05:01 | 1.78 |
June | 0.295262E+10 | 0.44 | 8614.45 | 03-JUN-05:03 | 1.78 |
July | 0.309242E+10 | 0.44 | 8614.45 | 03-JUL-04:02 | 1.78 |
August | 0.314680E+10 | 0.45 | 8614.45 | 01-AUG-04:02 | 1.78 |
September | 0.290439E+10 | 0.44 | 8614.45 | 02-SEP-05:03 | 1.78 |
October | 0.280907E+10 | 0.41 | 8614.45 | 02-OCT-04:02 | 1.78 |
November | 0.218268E+10 | 0.36 | 7194.73 | 04-NOV-05:03 | 1.59 |
December | 0.165626E+10 | 0.32 | 6707.95 | 11-DEC-07:03 | 1.52 |
Annual Sum or Average | 0.290840E+11 | 0.39 | |||
Minimum of Months | 0.159258E+10 | 0.32 | 3513.19 | 1.02 | |
Maximum of Months | 0.314680E+10 | 0.45 | 8614.45 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148433E+10 | 0.31 | 3558.46 | 02-JAN-15:00 | 0.93 |
February | 0.155786E+10 | 0.32 | 3231.51 | 21-FEB-16:20 | 0.88 |
March | 0.197600E+10 | 0.35 | 3936.94 | 27-MAR-15:20 | 0.98 |
April | 0.222002E+10 | 0.37 | 5186.15 | 13-APR-05:03 | 1.16 |
May | 0.281479E+10 | 0.40 | 10268.88 | 30-MAY-04:02 | 1.78 |
June | 0.297590E+10 | 0.42 | 10268.88 | 12-JUN-04:02 | 1.78 |
July | 0.314245E+10 | 0.42 | 10268.88 | 10-JUL-04:02 | 1.78 |
August | 0.311247E+10 | 0.42 | 10268.88 | 21-AUG-04:02 | 1.78 |
September | 0.285119E+10 | 0.41 | 10268.88 | 18-SEP-04:02 | 1.78 |
October | 0.263203E+10 | 0.38 | 10268.88 | 23-OCT-05:01 | 1.78 |
November | 0.201633E+10 | 0.34 | 5246.95 | 04-NOV-05:03 | 1.17 |
December | 0.155407E+10 | 0.31 | 3137.25 | 08-DEC-15:30 | 0.86 |
Annual Sum or Average | 0.283375E+11 | 0.37 | |||
Minimum of Months | 0.148433E+10 | 0.31 | 3137.25 | 0.86 | |
Maximum of Months | 0.314245E+10 | 0.42 | 10268.88 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.79 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 57.89 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 57.93 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.21 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.18 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.23 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:05 | 2.06 | 2.06 | 58.14 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.20 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.71 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 57.99 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.86 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.79 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.71 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.65 | 58.65 | 1234.94 | 4498.46 | 18-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.30 | 58.30 | 1231.08 | 4486.76 | 01-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.33 | 58.33 | 1276.68 | 4397.95 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.40 | 58.40 | 1133.37 | 4208.07 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.80 | 58.80 | 1119.67 | 4017.02 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.55 | 58.55 | 1104.42 | 3828.66 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.60 | 58.60 | 989.21 | 3713.35 | 03-JUL-11:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.61 | 58.61 | 1107.31 | 3799.99 | 31-AUG-11:17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.57 | 58.57 | 1068.20 | 3964.29 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.88 | 57.88 | 1121.18 | 4181.69 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.42 | 58.42 | 1195.21 | 4364.22 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.35 | 58.35 | 1184.68 | 4474.93 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 1146.71 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.88 | 57.88 | 989.21 | 3713.35 | ||
Maximum of Months | 0.00 | 0.00 | 58.80 | 58.80 | 1276.68 | 4498.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.131553E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132366E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.160013E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181802E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.249291E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.278853E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.300635E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.309188E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.282419E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.258766E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.199811E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138954E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.262365E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.131553E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.309188E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.101825E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107851E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.133606E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156733E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.214293E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.240966E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.257773E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.258834E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.236578E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.211590E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159794E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110211E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.219005E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.101825E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.258834E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.102739E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.111774E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.139445E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.167425E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.228523E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.257149E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.275934E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.272660E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.248495E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.217543E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162846E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.112311E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.229685E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.102739E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.275934E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.220559E+10 | 0.486245E+11 | 0.213962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220149E+10 | 0.497638E+11 | 80454512.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261493E+10 | 0.602014E+11 | 0.163195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280067E+10 | 0.688958E+11 | 9786517.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.362383E+10 | 0.932845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.380397E+10 | 0.105181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407990E+10 | 0.111063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.430987E+10 | 0.114728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394500E+10 | 0.105690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384773E+10 | 0.971864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307863E+10 | 0.762765E+11 | 39808719.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227900E+10 | 0.521823E+11 | 0.142832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387906E+11 | 0.983077E+12 | 0.650039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220149E+10 | 0.486245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.430987E+10 | 0.114728E+12 | 0.213962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159258E+10 | 0.384415E+11 | 940519.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164398E+10 | 0.410897E+11 | 27653562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206080E+10 | 0.512012E+11 | 3997768.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223427E+10 | 0.601173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280811E+10 | 0.818727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295262E+10 | 0.930355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.309242E+10 | 0.977668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314680E+10 | 0.988328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290439E+10 | 0.909063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280907E+10 | 0.811318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218268E+10 | 0.623768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165626E+10 | 0.422109E+11 | 461195.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290840E+11 | 0.838983E+12 | 33053045.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159258E+10 | 0.384415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314680E+10 | 0.988328E+11 | 27653562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148433E+10 | 0.384854E+11 | 82357708.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155786E+10 | 0.424513E+11 | 0.116932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197600E+10 | 0.536299E+11 | 55298619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222002E+10 | 0.645006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281479E+10 | 0.876219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.297590E+10 | 0.995949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314245E+10 | 0.104801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311247E+10 | 0.104511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285119E+10 | 0.958605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263203E+10 | 0.841260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201633E+10 | 0.640377E+11 | 6756303.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155407E+10 | 0.426340E+11 | 0.118871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283375E+11 | 0.882254E+12 | 0.380215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148433E+10 | 0.384854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314245E+10 | 0.104801E+12 | 0.118871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.220559E+10 | 0.00 | 0.00 | 0.00 | 0.107358E+11 | 0.213962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220149E+10 | 0.00 | 0.00 | 0.00 | 0.109546E+11 | 80454512.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261493E+10 | 0.00 | 0.00 | 0.00 | 0.132231E+11 | 0.163195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280067E+10 | 0.00 | 0.00 | 0.00 | 0.153697E+11 | 9786517.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.362383E+10 | 0.00 | 0.00 | 0.00 | 0.213053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.380397E+10 | 0.00 | 0.00 | 0.00 | 0.240813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.407990E+10 | 0.00 | 0.00 | 0.00 | 0.259836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.430987E+10 | 0.00 | 0.00 | 0.00 | 0.266089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394500E+10 | 0.00 | 0.00 | 0.00 | 0.242969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.384773E+10 | 0.00 | 0.00 | 0.00 | 0.220288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307863E+10 | 0.00 | 0.00 | 0.00 | 0.168626E+11 | 39808719.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227900E+10 | 0.00 | 0.00 | 0.00 | 0.114735E+11 | 0.142832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387906E+11 | 0.00 | 0.00 | 0.00 | 0.222924E+12 | 0.650039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.220149E+10 | 0.00 | 0.00 | 0.00 | 0.107358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.430987E+10 | 0.00 | 0.00 | 0.00 | 0.266089E+11 | 0.213962E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159258E+10 | 0.00 | 0.00 | 0.00 | 0.858899E+10 | 940519.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164398E+10 | 0.00 | 0.00 | 0.00 | 0.911344E+10 | 27653562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206080E+10 | 0.00 | 0.00 | 0.00 | 0.112958E+11 | 3997768.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223427E+10 | 0.00 | 0.00 | 0.00 | 0.134390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.280811E+10 | 0.00 | 0.00 | 0.00 | 0.186212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295262E+10 | 0.00 | 0.00 | 0.00 | 0.211440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.309242E+10 | 0.00 | 0.00 | 0.00 | 0.226849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.314680E+10 | 0.00 | 0.00 | 0.00 | 0.227366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.290439E+10 | 0.00 | 0.00 | 0.00 | 0.207534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280907E+10 | 0.00 | 0.00 | 0.00 | 0.183499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218268E+10 | 0.00 | 0.00 | 0.00 | 0.137967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165626E+10 | 0.00 | 0.00 | 0.00 | 0.936437E+10 | 461195.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290840E+11 | 0.00 | 0.00 | 0.00 | 0.189888E+12 | 33053045.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159258E+10 | 0.00 | 0.00 | 0.00 | 0.858899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314680E+10 | 0.00 | 0.00 | 0.00 | 0.227366E+11 | 27653562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148433E+10 | 0.00 | 0.00 | 0.00 | 0.870726E+10 | 82357708.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155786E+10 | 0.00 | 0.00 | 0.00 | 0.950262E+10 | 0.116932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197600E+10 | 0.00 | 0.00 | 0.00 | 0.119132E+11 | 55298619.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222002E+10 | 0.00 | 0.00 | 0.00 | 0.145225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.281479E+10 | 0.00 | 0.00 | 0.00 | 0.200375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.297590E+10 | 0.00 | 0.00 | 0.00 | 0.227390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314245E+10 | 0.00 | 0.00 | 0.00 | 0.244509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.311247E+10 | 0.00 | 0.00 | 0.00 | 0.241536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.285119E+10 | 0.00 | 0.00 | 0.00 | 0.219983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.263203E+10 | 0.00 | 0.00 | 0.00 | 0.191222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201633E+10 | 0.00 | 0.00 | 0.00 | 0.142615E+11 | 6756303.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155407E+10 | 0.00 | 0.00 | 0.00 | 0.955814E+10 | 0.118871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.283375E+11 | 0.00 | 0.00 | 0.00 | 0.200967E+12 | 0.380215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148433E+10 | 0.00 | 0.00 | 0.00 | 0.870726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.314245E+10 | 0.00 | 0.00 | 0.00 | 0.244509E+11 | 0.118871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188087E+09 | 0.332504E+10 | 0.00 | 23282488.21 | 0.416293E+09 | 0.00 | 0.327133E+10 | 0.00 | 0.41 |
February | 89035564.84 | 0.378757E+10 | 0.00 | 15373624.90 | 0.285345E+09 | 0.00 | 0.170493E+10 | 0.00 | 0.39 |
March | 59581423.38 | 0.520026E+10 | 0.00 | 17319698.10 | 0.519273E+09 | 0.00 | 0.251951E+10 | 0.00 | 0.41 |
April | 8886183.92 | 0.690548E+10 | 0.00 | 4789229.17 | 0.973407E+09 | 0.00 | 0.399694E+09 | 0.00 | 0.37 |
May | 0.00 | 0.121812E+11 | 0.00 | 0.00 | 0.193026E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.161821E+11 | 0.00 | 0.00 | 0.228257E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.163704E+11 | 0.00 | 0.00 | 0.372950E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.175518E+11 | 0.00 | 0.00 | 0.250184E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.150551E+11 | 0.00 | 0.00 | 0.318958E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.00 | 0.123163E+11 | 0.00 | 0.00 | 0.251614E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 0.134260E+09 | 0.910080E+10 | 0.00 | 5172827.06 | 0.913089E+09 | 0.00 | 0.343727E+09 | 0.00 | 0.36 |
December | 72901446.57 | 0.389927E+10 | 0.00 | 20460101.64 | 0.889401E+09 | 0.00 | 0.286716E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.552752E+09 | 0.121875E+12 | 0.00 | 86397969.07 | 0.201467E+11 | 0.00 | 0.111063E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.332504E+10 | 0.00 | 0.00 | 0.285345E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.188087E+09 | 0.175518E+11 | 0.00 | 23282488.21 | 0.372950E+10 | 0.00 | 0.327133E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.922703E+09 | 0.241419E+10 | 0.00 | 7898092.48 | 0.691159E+09 | 0.00 | 0.153941E+10 | 0.00 | 0.31 |
February | 0.505827E+09 | 0.291497E+10 | 0.00 | 6715236.86 | 0.555404E+09 | 0.00 | 0.858126E+09 | 0.00 | 0.31 |
March | 0.473594E+09 | 0.396557E+10 | 0.00 | 7133677.13 | 0.874188E+09 | 0.00 | 0.139854E+10 | 0.00 | 0.32 |
April | 30040844.50 | 0.560483E+10 | 0.00 | 2768282.63 | 0.116686E+10 | 0.00 | 0.281017E+09 | 0.00 | 0.31 |
May | 0.00 | 0.105260E+11 | 0.00 | 0.00 | 0.219284E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.143635E+11 | 0.00 | 0.00 | 0.268212E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.148313E+11 | 0.00 | 0.00 | 0.380981E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.158952E+11 | 0.00 | 0.00 | 0.282460E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.135581E+11 | 0.00 | 0.00 | 0.328754E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.108815E+11 | 0.00 | 0.00 | 0.226780E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.171103E+09 | 0.794856E+10 | 0.00 | 2158978.27 | 0.932551E+09 | 0.00 | 0.174518E+09 | 0.00 | 0.30 |
December | 0.607474E+09 | 0.254760E+10 | 0.00 | 8009846.65 | 0.159945E+10 | 0.00 | 0.150587E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.271074E+10 | 0.105451E+12 | 0.00 | 34684114.02 | 0.228843E+11 | 0.00 | 0.575748E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.241419E+10 | 0.00 | 0.00 | 0.555404E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.922703E+09 | 0.158952E+11 | 0.00 | 8009846.65 | 0.380981E+10 | 0.00 | 0.153941E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114487E+10 | 0.199414E+10 | 0.00 | 4631951.05 | 0.121273E+10 | 0.00 | 0.952987E+09 | 0.00 | 0.31 |
February | 0.539288E+09 | 0.259527E+10 | 0.00 | 4674083.41 | 0.877940E+09 | 942586.80 | 0.610670E+09 | 0.00 | 0.30 |
March | 0.673441E+09 | 0.372327E+10 | 0.00 | 5490596.36 | 0.108065E+10 | 0.00 | 0.998022E+09 | 0.00 | 0.32 |
April | 28903025.43 | 0.536249E+10 | 0.00 | 2481398.56 | 0.128504E+10 | 0.00 | 0.245422E+09 | 0.00 | 0.32 |
May | 0.00 | 0.101736E+11 | 0.00 | 0.00 | 0.214896E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.140106E+11 | 0.00 | 0.00 | 0.272119E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.144493E+11 | 0.00 | 0.00 | 0.375892E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.153727E+11 | 0.00 | 0.00 | 0.295713E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.132632E+11 | 0.00 | 0.00 | 0.329868E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.105361E+11 | 0.00 | 0.00 | 0.244231E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.219595E+09 | 0.752306E+10 | 0.00 | 1334919.27 | 0.133978E+10 | 0.00 | 72489407.43 | 0.00 | 0.30 |
December | 0.826159E+09 | 0.229807E+10 | 0.00 | 4928241.27 | 0.185768E+10 | 0.00 | 0.919708E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.343226E+10 | 0.101302E+12 | 0.00 | 23541189.92 | 0.249810E+11 | 942586.80 | 0.379930E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.199414E+10 | 0.00 | 0.00 | 0.877940E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.114487E+10 | 0.153727E+11 | 0.00 | 5490596.36 | 0.375892E+10 | 942586.80 | 0.998022E+09 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336966E+09 | 0.453576E+09 | 0.00 | 445889.15 | 0.263873E+09 | 7222810.58 | 78531344.81 | 0.00 | 0.31 |
February | 0.133625E+09 | 0.633357E+09 | 55140.33 | 854070.60 | 0.217948E+09 | 18105157.98 | 90185825.57 | 143.99 | 0.33 |
March | 0.228162E+09 | 0.968227E+09 | 0.00 | 822563.71 | 0.233292E+09 | 5133587.68 | 0.105999E+09 | 0.00 | 0.35 |
April | 10484388.76 | 0.146379E+10 | 0.00 | 537823.26 | 0.296636E+09 | 0.00 | 51769020.81 | 0.00 | 0.38 |
May | 0.00 | 0.327648E+10 | 0.00 | 0.00 | 0.370061E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.488156E+10 | 0.00 | 0.00 | 0.403224E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.524075E+10 | 0.00 | 0.00 | 0.533473E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.507932E+10 | 0.00 | 0.00 | 0.432431E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.422849E+10 | 0.00 | 0.00 | 0.563181E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.291029E+10 | 0.00 | 0.00 | 0.509686E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 48024121.35 | 0.193434E+10 | 0.00 | 282226.27 | 0.300035E+09 | 457094.69 | 14263846.64 | 0.00 | 0.34 |
December | 0.262308E+09 | 0.590429E+09 | 0.00 | 532037.70 | 0.376143E+09 | 8948091.95 | 80741408.90 | 0.00 | 0.31 |
Annual Sum or Average | 0.101957E+10 | 0.316606E+11 | 55140.33 | 3474610.68 | 0.449998E+10 | 39866742.87 | 0.421490E+09 | 143.99 | 0.39 |
Minimum of Months | 0.00 | 0.453576E+09 | 0.00 | 0.00 | 0.217948E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.336966E+09 | 0.524075E+10 | 55140.33 | 854070.60 | 0.563181E+09 | 18105157.98 | 0.105999E+09 | 143.99 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133725E+09 | 0.478256E+09 | 0.00 | 1111330.34 | 0.100933E+09 | 1529588.99 | 0.193582E+09 | 0.00 | 0.39 |
February | 68282600.25 | 0.609124E+09 | 0.00 | 1142494.66 | 97112054.53 | 6660795.13 | 0.110722E+09 | 0.00 | 0.43 |
March | 62685950.90 | 0.937718E+09 | 0.00 | 1636364.37 | 97229688.32 | 1617819.58 | 0.284128E+09 | 0.00 | 0.50 |
April | 4403675.79 | 0.146941E+10 | 0.00 | 610422.84 | 0.131513E+09 | 0.00 | 56919500.28 | 0.00 | 0.55 |
May | 0.00 | 0.278025E+10 | 0.00 | 0.00 | 0.180666E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.396191E+10 | 0.00 | 0.00 | 0.205762E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.436112E+10 | 0.00 | 0.00 | 0.248912E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.418820E+10 | 0.00 | 0.00 | 0.224519E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.365151E+10 | 0.00 | 0.00 | 0.262528E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.265466E+10 | 0.00 | 0.00 | 0.225098E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 27182959.11 | 0.162217E+10 | 0.00 | 322837.35 | 0.150824E+09 | 74804.11 | 16448045.04 | 0.00 | 0.43 |
December | 0.108687E+09 | 0.544148E+09 | 0.00 | 756539.78 | 0.202357E+09 | 5074758.19 | 0.133288E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.404967E+09 | 0.272585E+11 | 0.00 | 5579989.34 | 0.212746E+10 | 14957765.99 | 0.795087E+09 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.478256E+09 | 0.00 | 0.00 | 97112054.53 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.133725E+09 | 0.436112E+10 | 0.00 | 1636364.37 | 0.262528E+09 | 6660795.13 | 0.284128E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162183E+09 | 0.103786E+10 | 0.00 | 4884889.59 | 0.126296E+09 | 2662080.22 | 0.693113E+09 | 0.00 | 0.55 |
February | 96004624.99 | 0.114821E+10 | 0.00 | 3213906.45 | 0.124545E+09 | 11122907.24 | 0.307619E+09 | 0.00 | 0.52 |
March | 0.138258E+09 | 0.140606E+10 | 0.00 | 2924752.74 | 0.162658E+09 | 4844636.44 | 0.403156E+09 | 0.00 | 0.50 |
April | 10314513.12 | 0.176484E+10 | 0.00 | 718761.48 | 0.265935E+09 | 0.00 | 67841200.27 | 0.00 | 0.44 |
May | 0.00 | 0.322366E+10 | 0.00 | 0.00 | 0.380489E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.456713E+10 | 0.00 | 0.00 | 0.452246E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.503211E+10 | 0.00 | 0.00 | 0.582382E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.541527E+10 | 0.00 | 0.00 | 0.417854E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.531698E+10 | 0.00 | 0.00 | 0.437583E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.450073E+10 | 0.00 | 0.00 | 0.321653E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 26396768.72 | 0.321093E+10 | 0.00 | 1329186.49 | 0.167313E+09 | 0.00 | 71340032.56 | 0.00 | 0.53 |
December | 0.137440E+09 | 0.141974E+10 | 0.00 | 3284823.83 | 0.211783E+09 | 4858835.68 | 0.543845E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.570597E+09 | 0.380435E+11 | 0.00 | 16356320.57 | 0.365074E+10 | 23488459.59 | 0.208691E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.103786E+10 | 0.00 | 0.00 | 0.124545E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.162183E+09 | 0.541527E+10 | 0.00 | 4884889.59 | 0.582382E+09 | 11122907.24 | 0.693113E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169122E+09 | 0.393407E+09 | 0.00 | 1064555.06 | 0.136521E+09 | 4264388.40 | 0.182224E+09 | 0.00 | 0.38 |
February | 74321948.71 | 0.567946E+09 | 0.00 | 1223488.35 | 97185906.65 | 11112951.94 | 0.127117E+09 | 0.00 | 0.42 |
March | 0.121576E+09 | 0.895612E+09 | 0.00 | 1540830.75 | 0.107643E+09 | 3293035.54 | 0.206220E+09 | 0.00 | 0.50 |
April | 6252771.79 | 0.143662E+10 | 0.00 | 573027.51 | 0.126650E+09 | 0.00 | 59674900.66 | 0.00 | 0.54 |
May | 0.00 | 0.272799E+10 | 0.00 | 0.00 | 0.169802E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.365045E+10 | 0.00 | 0.00 | 0.209455E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.412087E+10 | 0.00 | 0.00 | 0.257861E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.416347E+10 | 0.00 | 0.00 | 0.211558E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.342304E+10 | 0.00 | 0.00 | 0.254967E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.248377E+10 | 0.00 | 0.00 | 0.245689E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 26829566.23 | 0.158900E+10 | 0.00 | 361419.04 | 0.156225E+09 | 179010.11 | 21573573.27 | 0.00 | 0.42 |
December | 0.133463E+09 | 0.581640E+09 | 0.00 | 950685.12 | 0.186447E+09 | 5704485.99 | 0.137063E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.531565E+09 | 0.260338E+11 | 0.00 | 5714005.84 | 0.216000E+10 | 24553871.99 | 0.733872E+09 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.393407E+09 | 0.00 | 0.00 | 97185906.65 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.169122E+09 | 0.416347E+10 | 0.00 | 1540830.75 | 0.257861E+09 | 11112951.94 | 0.206220E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.325474E+09 | 0.448685E+09 | 0.00 | 790965.57 | 0.151416E+09 | 0.00 | 0.127530E+09 | 0.00 | 0.28 |
February | 0.164793E+09 | 0.553878E+09 | 0.00 | 903160.96 | 0.123356E+09 | 0.00 | 86302832.05 | 0.00 | 0.28 |
March | 0.231152E+09 | 0.783043E+09 | 0.00 | 673725.22 | 0.184783E+09 | 0.00 | 88865036.13 | 0.00 | 0.29 |
April | 10777822.43 | 0.116476E+10 | 0.00 | 496125.63 | 0.267140E+09 | 0.00 | 48329112.50 | 0.00 | 0.31 |
May | 0.00 | 0.252042E+10 | 0.00 | 0.00 | 0.498397E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.374748E+10 | 0.00 | 0.00 | 0.588035E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.413793E+10 | 0.00 | 0.00 | 0.789409E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.414125E+10 | 0.00 | 0.00 | 0.577383E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.346779E+10 | 0.00 | 0.00 | 0.734742E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.244609E+10 | 0.00 | 0.00 | 0.636964E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 51892033.71 | 0.163995E+10 | 0.00 | 409979.69 | 0.262957E+09 | 0.00 | 18602802.68 | 0.00 | 0.30 |
December | 0.236528E+09 | 0.577400E+09 | 0.00 | 1005850.42 | 0.265353E+09 | 0.00 | 0.146562E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.102062E+10 | 0.256287E+11 | 0.00 | 4279807.48 | 0.507994E+10 | 0.00 | 0.516191E+09 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.448685E+09 | 0.00 | 0.00 | 0.123356E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.325474E+09 | 0.414125E+10 | 0.00 | 1005850.42 | 0.789409E+09 | 0.00 | 0.146562E+09 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132110E+09 | 0.436367E+09 | 0.00 | 1800243.49 | 61469139.93 | 0.00 | 0.249809E+09 | 0.00 | 0.37 |
February | 65174742.87 | 0.504824E+09 | 0.00 | 1625333.26 | 55896474.68 | 0.00 | 0.142841E+09 | 0.00 | 0.38 |
March | 63383451.05 | 0.771925E+09 | 0.00 | 1854103.27 | 83683375.99 | 0.00 | 0.270094E+09 | 0.00 | 0.43 |
April | 5295157.26 | 0.120163E+10 | 0.00 | 632538.42 | 0.129105E+09 | 0.00 | 57051508.80 | 0.00 | 0.45 |
May | 0.00 | 0.225132E+10 | 0.00 | 0.00 | 0.225530E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.322627E+10 | 0.00 | 0.00 | 0.234835E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.367417E+10 | 0.00 | 0.00 | 0.299321E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.355561E+10 | 0.00 | 0.00 | 0.231262E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.316007E+10 | 0.00 | 0.00 | 0.298715E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.228432E+10 | 0.00 | 0.00 | 0.276668E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
November | 25415893.61 | 0.137312E+10 | 0.00 | 560810.13 | 0.145533E+09 | 0.00 | 29841385.90 | 0.00 | 0.39 |
December | 0.104947E+09 | 0.503982E+09 | 0.00 | 1322696.41 | 0.144865E+09 | 0.00 | 0.186167E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.396327E+09 | 0.229436E+11 | 0.00 | 7795724.98 | 0.218688E+10 | 0.00 | 0.935804E+09 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.436367E+09 | 0.00 | 0.00 | 55896474.68 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.132110E+09 | 0.367417E+10 | 0.00 | 1854103.27 | 0.299321E+09 | 0.00 | 0.270094E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191251E+09 | 0.945364E+09 | 0.00 | 3908217.78 | 82543552.65 | 66210315.02 | 0.441648E+09 | 0.00 | 0.46 |
February | 0.122463E+09 | 0.100889E+10 | 0.00 | 3533076.59 | 77347236.87 | 28247359.48 | 0.224693E+09 | 0.00 | 0.46 |
March | 0.178018E+09 | 0.125007E+10 | 0.00 | 1863678.11 | 0.145214E+09 | 65532985.69 | 0.176775E+09 | 0.00 | 0.42 |
April | 13938737.63 | 0.159309E+10 | 0.00 | 505840.67 | 0.269889E+09 | 1845108.53 | 46089711.51 | 0.00 | 0.38 |
May | 0.00 | 0.297768E+10 | 0.00 | 0.00 | 0.507139E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.426085E+10 | 0.00 | 0.00 | 0.608780E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.482899E+10 | 0.00 | 0.00 | 0.781916E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.539213E+10 | 0.00 | 0.00 | 0.479086E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.508338E+10 | 0.00 | 0.00 | 0.503356E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.433191E+10 | 0.00 | 0.00 | 0.325803E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 24686379.20 | 0.293719E+10 | 0.00 | 1455431.52 | 0.145968E+09 | 11227800.16 | 64206272.82 | 0.00 | 0.48 |
December | 0.157621E+09 | 0.133543E+10 | 260182.06 | 2563122.08 | 0.125283E+09 | 52863298.85 | 0.346717E+09 | 5173.20 | 0.45 |
Annual Sum or Average | 0.687978E+09 | 0.359450E+11 | 260182.06 | 13829366.75 | 0.405232E+10 | 0.225927E+09 | 0.130013E+10 | 5173.20 | 0.46 |
Minimum of Months | 0.00 | 0.945364E+09 | 0.00 | 0.00 | 77347236.87 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.191251E+09 | 0.539213E+10 | 260182.06 | 3908217.78 | 0.781916E+09 | 66210315.02 | 0.441648E+09 | 5173.20 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145401E+09 | 0.389284E+09 | 0.00 | 1425276.07 | 72804772.82 | 0.00 | 0.215125E+09 | 0.00 | 0.34 |
February | 85196917.05 | 0.501930E+09 | 0.00 | 1401622.74 | 49377910.22 | 0.00 | 0.117635E+09 | 0.00 | 0.37 |
March | 0.101358E+09 | 0.783543E+09 | 0.00 | 1454709.39 | 74859648.96 | 0.00 | 0.180689E+09 | 0.00 | 0.42 |
April | 5639900.66 | 0.123941E+10 | 0.00 | 563754.93 | 0.100701E+09 | 0.00 | 53414786.11 | 0.00 | 0.45 |
May | 0.00 | 0.223514E+10 | 0.00 | 0.00 | 0.216247E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.292218E+10 | 0.00 | 0.00 | 0.274718E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.345843E+10 | 0.00 | 0.00 | 0.322291E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.354760E+10 | 0.00 | 0.00 | 0.229749E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.296616E+10 | 0.00 | 0.00 | 0.296657E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.220207E+10 | 0.00 | 0.00 | 0.270969E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 28892719.20 | 0.138765E+10 | 0.00 | 434094.31 | 0.128392E+09 | 0.00 | 21431955.81 | 0.00 | 0.38 |
December | 0.100721E+09 | 0.566420E+09 | 0.00 | 1373107.36 | 0.123892E+09 | 0.00 | 0.194563E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.467211E+09 | 0.221998E+11 | 0.00 | 6652564.79 | 0.216066E+10 | 0.00 | 0.782860E+09 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.389284E+09 | 0.00 | 0.00 | 49377910.22 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.145401E+09 | 0.354760E+10 | 0.00 | 1454709.39 | 0.322291E+09 | 0.00 | 0.215125E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.362102E+09 | 0.526205E+09 | 0.00 | 602608.78 | 0.167701E+09 | 170217.53 | 0.116389E+09 | 0.00 | 0.31 |
February | 0.176831E+09 | 0.706719E+09 | 0.00 | 960109.87 | 0.146101E+09 | 3358416.22 | 95219945.92 | 0.00 | 0.33 |
March | 0.253779E+09 | 0.104774E+10 | 0.00 | 770913.07 | 0.171806E+09 | 155045.63 | 0.106826E+09 | 0.00 | 0.35 |
April | 12766328.57 | 0.156421E+10 | 0.00 | 535056.77 | 0.256003E+09 | 0.00 | 55468298.29 | 0.00 | 0.38 |
May | 0.00 | 0.339810E+10 | 0.00 | 0.00 | 0.407227E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.502589E+10 | 0.00 | 0.00 | 0.452737E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.539036E+10 | 0.00 | 0.00 | 0.617118E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.521734E+10 | 0.00 | 0.00 | 0.484134E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.432849E+10 | 0.00 | 0.00 | 0.611993E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.299940E+10 | 0.00 | 0.00 | 0.488525E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
November | 54153216.21 | 0.201646E+10 | 0.00 | 333866.04 | 0.230811E+09 | 0.00 | 16483761.03 | 0.00 | 0.34 |
December | 0.292599E+09 | 0.663578E+09 | 0.00 | 730624.73 | 0.302065E+09 | 0.00 | 0.113840E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.115223E+10 | 0.328845E+11 | 0.00 | 3933179.27 | 0.433622E+10 | 3683679.38 | 0.504227E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.526205E+09 | 0.00 | 0.00 | 0.146101E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.362102E+09 | 0.539036E+10 | 0.00 | 960109.87 | 0.617118E+09 | 3358416.22 | 0.116389E+09 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155763E+09 | 0.456320E+09 | 0.00 | 1279841.10 | 66219475.93 | 0.00 | 0.214895E+09 | 0.00 | 0.37 |
February | 77087938.77 | 0.585596E+09 | 0.00 | 1394589.73 | 67480268.98 | 370073.53 | 0.129563E+09 | 0.00 | 0.41 |
March | 75197796.60 | 0.895763E+09 | 0.00 | 1653478.38 | 86124905.70 | 0.00 | 0.294762E+09 | 0.00 | 0.48 |
April | 6290543.58 | 0.144129E+10 | 0.00 | 589465.84 | 0.122708E+09 | 0.00 | 57726099.76 | 0.00 | 0.52 |
May | 0.00 | 0.275839E+10 | 0.00 | 0.00 | 0.195176E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.393577E+10 | 0.00 | 0.00 | 0.209159E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.435788E+10 | 0.00 | 0.00 | 0.265692E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.414447E+10 | 0.00 | 0.00 | 0.226645E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.359710E+10 | 0.00 | 0.00 | 0.285981E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.256678E+10 | 0.00 | 0.00 | 0.224357E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 27011208.58 | 0.154962E+10 | 0.00 | 397157.24 | 0.126845E+09 | 0.00 | 26348482.68 | 0.00 | 0.41 |
December | 0.131310E+09 | 0.534295E+09 | 0.00 | 877178.29 | 0.164364E+09 | 0.00 | 0.146177E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.472660E+09 | 0.268233E+11 | 0.00 | 6191710.58 | 0.204075E+10 | 370073.53 | 0.869471E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.456320E+09 | 0.00 | 0.00 | 66219475.93 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.155763E+09 | 0.435788E+10 | 0.00 | 1653478.38 | 0.285981E+09 | 370073.53 | 0.294762E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187149E+09 | 0.107886E+10 | 0.00 | 5195657.58 | 67615661.74 | 0.00 | 0.726225E+09 | 0.00 | 0.55 |
February | 0.123692E+09 | 0.123079E+10 | 0.00 | 3696701.23 | 75075769.57 | 395993.58 | 0.314566E+09 | 0.00 | 0.52 |
March | 0.151151E+09 | 0.149772E+10 | 0.00 | 2969686.22 | 0.124535E+09 | 0.00 | 0.404072E+09 | 0.00 | 0.50 |
April | 12102139.02 | 0.190112E+10 | 0.00 | 698064.33 | 0.227430E+09 | 0.00 | 70955351.06 | 0.00 | 0.44 |
May | 0.00 | 0.336665E+10 | 0.00 | 0.00 | 0.406963E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.472155E+10 | 0.00 | 0.00 | 0.487080E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.520162E+10 | 0.00 | 0.00 | 0.649254E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.560922E+10 | 0.00 | 0.00 | 0.451076E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.552395E+10 | 0.00 | 0.00 | 0.471582E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.466667E+10 | 0.00 | 0.00 | 0.284833E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 29962628.39 | 0.324845E+10 | 0.00 | 1404318.01 | 0.124950E+09 | 0.00 | 73177360.97 | 0.00 | 0.52 |
December | 0.154472E+09 | 0.150067E+10 | 0.00 | 3704643.43 | 0.149900E+09 | 0.00 | 0.596948E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.658529E+09 | 0.395473E+11 | 0.00 | 17669070.78 | 0.352029E+10 | 395993.58 | 0.218594E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.107886E+10 | 0.00 | 0.00 | 67615661.74 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.187149E+09 | 0.560922E+10 | 0.00 | 5195657.58 | 0.649254E+09 | 395993.58 | 0.726225E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192427E+09 | 0.438789E+09 | 0.00 | 1192229.10 | 84008686.13 | 0.00 | 0.196567E+09 | 0.00 | 0.38 |
February | 99625092.57 | 0.620281E+09 | 0.00 | 1298383.45 | 61167708.85 | 1359628.30 | 0.128476E+09 | 0.00 | 0.42 |
March | 0.132041E+09 | 0.963666E+09 | 0.00 | 1488061.61 | 80948239.21 | 0.00 | 0.197520E+09 | 0.00 | 0.50 |
April | 7449313.38 | 0.156393E+10 | 0.00 | 549413.95 | 0.101311E+09 | 0.00 | 61152185.52 | 0.00 | 0.55 |
May | 0.00 | 0.289477E+10 | 0.00 | 0.00 | 0.188219E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.382944E+10 | 0.00 | 0.00 | 0.226298E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.433865E+10 | 0.00 | 0.00 | 0.280681E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.435562E+10 | 0.00 | 0.00 | 0.227215E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.355478E+10 | 0.00 | 0.00 | 0.281955E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.259297E+10 | 0.00 | 0.00 | 0.224577E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 30895573.36 | 0.165194E+10 | 0.00 | 380565.95 | 0.117620E+09 | 0.00 | 21411808.07 | 0.00 | 0.42 |
December | 0.151675E+09 | 0.632253E+09 | 0.00 | 1069542.53 | 0.149251E+09 | 0.00 | 0.160458E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.614113E+09 | 0.274371E+11 | 0.00 | 5978196.61 | 0.202325E+10 | 1359628.30 | 0.765585E+09 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.438789E+09 | 0.00 | 0.00 | 61167708.85 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.192427E+09 | 0.435562E+10 | 0.00 | 1488061.61 | 0.281955E+09 | 1359628.30 | 0.197520E+09 | 0.00 | 0.58 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:06
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.198164E+12 | 0.576907E+09 | 0.00 | -0.503611E+10 | 0.153583E+12 |
February | 0.209917E+12 | -697385783.6 | 0.00 | -0.143341E+11 | 0.162875E+12 |
March | 0.282235E+12 | -0.170647E+10 | 0.00 | -0.279840E+11 | 0.201465E+12 |
April | 0.299562E+12 | -0.400138E+10 | 0.00 | -0.578180E+11 | 0.236845E+12 |
May | 0.284102E+12 | -0.922220E+10 | 0.00 | -0.114451E+12 | 0.322743E+12 |
June | 0.254360E+12 | -0.106700E+11 | 0.00 | -0.154802E+12 | 0.365775E+12 |
July | 0.277882E+12 | -0.103321E+11 | 0.00 | -0.168747E+12 | 0.386751E+12 |
August | 0.301724E+12 | -0.116413E+11 | 0.00 | -0.170317E+12 | 0.391571E+12 |
September | 0.232447E+12 | -0.993868E+10 | 0.00 | -0.153559E+12 | 0.359505E+12 |
October | 0.234024E+12 | -0.845912E+10 | 0.00 | -0.126058E+12 | 0.321945E+12 |
November | 0.177476E+12 | -0.463597E+10 | 0.00 | -0.740799E+11 | 0.247612E+12 |
December | 0.191935E+12 | -599840071.7 | 0.00 | -0.274764E+11 | 0.167423E+12 |
Annual Sum or Average | 0.294383E+13 | -0.713275E+11 | 0.00 | -0.109466E+13 | 0.331809E+13 |
Minimum of Months | 0.177476E+12 | -0.116413E+11 | 0.00 | -0.170317E+12 | 0.153583E+12 |
Maximum of Months | 0.301724E+12 | 0.576907E+09 | 0.00 | -0.503611E+10 | 0.391571E+12 |