Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2024-07-03 12:21:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2069.55 | 415.39 | 415.39 |
Net Site Energy | 2069.55 | 415.39 | 415.39 |
Total Source Energy | 6554.26 | 1315.54 | 1315.54 |
Net Source Energy | 6554.26 | 1315.54 | 1315.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 884.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2069.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 884.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 122.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 884.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 122.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 415.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 415.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2069.548 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2069.548 | 100.00 |
Total On-Site and Utility Electric Sources | 2069.548 | 100.00 |
Total Electricity End Uses | 2069.548 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 938.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2250.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 13-JUN-15:09 | - | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88919.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16133.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2868.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 170680.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 88919.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16133.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2868.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2800.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 156.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 386.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6554.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 562.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 77.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1315.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 562.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 77.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1315.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.48 | 0.301976 | 0.257000 | 0.637832 | 0.805269 | 0.500000 | 0.001262 |
CORE_MID VAV BOX COMPONENT | 1.98 | 0.377580 | 0.321000 | 0.637150 | 1.00 | 0.500000 | 0.001009 |
CORE_TOP VAV BOX COMPONENT | 2.14 | 0.350487 | 0.298000 | 0.637220 | 0.934632 | 0.500000 | 0.001087 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.704690 | 0.224200 | 0.191000 | 0.134596 | 0.597867 | 0.500000 | 0.001699 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.639275 | 0.156461 | 0.133000 | 0.085024 | 0.417230 | 0.500000 | 0.002435 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.685402 | 0.230510 | 0.196000 | 0.134339 | 0.614692 | 0.500000 | 0.001653 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.741726 | 0.134841 | 0.115000 | 0.085298 | 0.359577 | 0.500000 | 0.002826 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.604088 | 0.261537 | 0.222000 | 0.134108 | 0.697433 | 0.500000 | 0.001457 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.579237 | 0.172679 | 0.147000 | 0.085148 | 0.460476 | 0.500000 | 0.002206 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.585898 | 0.269657 | 0.229000 | 0.134171 | 0.719086 | 0.500000 | 0.001413 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.625304 | 0.159946 | 0.136000 | 0.085041 | 0.426524 | 0.500000 | 0.002382 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.609989 | 0.259007 | 0.220000 | 0.134198 | 0.690686 | 0.500000 | 0.001471 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.614823 | 0.433824 | 0.500000 | 0.002342 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.592726 | 0.266551 | 0.227000 | 0.134549 | 0.710802 | 0.500000 | 0.001429 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.670948 | 0.149066 | 0.127000 | 0.085210 | 0.397508 | 0.500000 | 0.002556 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21292.81 |
CORE_MID VAV BOX REHEAT COIL | 21270.04 |
CORE_TOP VAV BOX REHEAT COIL | 21272.39 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 4493.23 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 2838.35 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 4484.64 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 2847.53 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4476.93 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2842.50 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4479.03 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2838.95 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 4479.93 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 1518.83 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 4491.66 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 2844.59 |
PACU_VAV_BOT HEATING COIL | 20810.27 |
PACU_VAV_MID HEATING COIL | 18668.43 |
PACU_VAV_TOP HEATING COIL | 21864.25 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.44 | 1.08 | 4.88 | 1.08 | 4.48 | 4.48 | 0.300000 | 0.240199 | 4.48 |
PACU_VAV_MID | 2.24 | 1.08 | 4.47 | 1.08 | 4.02 | 4.02 | 0.300000 | 0.267671 | 4.02 |
PACU_VAV_TOP | 2.45 | 1.08 | 4.91 | 1.08 | 4.71 | 4.71 | 0.300000 | 0.228658 | 4.71 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.48 |
PACU_VAV_MID_OA_CONTROLLER | 4.02 |
PACU_VAV_TOP_OA_CONTROLLER | 4.71 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.48 | 108536.81 | 0.709256 | 1.49 | 36175.32 | 0.709256 |
PACU_VAV_MID COOLING COIL | 4.02 | 99818.19 | 0.701083 | 1.34 | 33269.40 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.71 | 112376.83 | 0.713961 | 1.57 | 37455.20 | 0.713961 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.48 |
PACU_VAV_MID FAN | 4.02 |
PACU_VAV_TOP FAN | 4.71 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4948E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5299E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5444E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5739E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8634E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8838E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5578E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5722E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7040E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4042E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8747E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3484E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9905E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8485E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8099E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0520E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4941E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5275E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5437E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5713E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8626E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8815E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5576E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5721E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4266E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9748E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0401E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7223E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9948E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4984E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3022E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5557E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3212E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3330E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0378E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0464E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8511E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8542E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9854E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9904E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3993E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4292E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0703E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0936E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7640E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7771E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5576E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5721E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1630E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1788E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7217E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2626E-003 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4412E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1004E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8099E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0520E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3997E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4298E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0707E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0944E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7645E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7786E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5578E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5722E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6396E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0668E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2858E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8280E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2277E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5987E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3022E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5557E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4672E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4865E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2087E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2266E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0054E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0164E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9855E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9905E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1736E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1298E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3254E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0836E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4767E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.4881E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2063E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4956E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.3226E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9159E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9554E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6746E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9341E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4630E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2406E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5186E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5036E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5868E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0312E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2870E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.7371E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.3161E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2063E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4956E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5298E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0039E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1942E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7756E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1607E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5589E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2406E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5186E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1732E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1295E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3249E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0832E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4761E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.4879E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2060E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4955E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.3226E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9157E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9553E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6745E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9339E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4628E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2403E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5184E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5036E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5867E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0312E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2869E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.7369E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.3153E-003 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2060E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4955E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5297E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0038E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1940E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7755E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1605E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5587E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2403E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 34442.53537 | 34442.53537 | 2.48184 | 2.48184 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 0.42469 | 00:10:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 | |
3 | CORE_MID | Cooling | 27573.92567 | 27573.92567 | 1.98489 | 1.98489 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 1194.45047 | 1194.45047 | 5.08335E-002 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29416.83857 | 29416.83857 | 2.13832 | 2.13832 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 4647.48420 | 4647.48420 | 0.19538 | 0.42469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9693.98229 | 9693.98229 | 0.70469 | 0.70469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 1567.85305 | 1567.85305 | 6.58278E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8794.13051 | 8794.13051 | 0.63927 | 0.63927 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 31.72917 | 1.71515E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 1018.68987 | 1018.68987 | 4.27742E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9428.63424 | 9428.63424 | 0.68540 | 0.68540 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 1617.97946 | 1617.97946 | 6.78985E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10203.51026 | 10203.51026 | 0.74173 | 0.74173 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 1018.65467 | 1018.65467 | 4.27728E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 8310.26307 | 8310.26307 | 0.60409 | 0.60409 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 121.97353 | 121.97353 | 5.21826E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7968.42137 | 7968.42137 | 0.57924 | 0.57924 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 31.48833 | 1.71511E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 92.90479 | 92.90479 | 3.97326E-003 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8060.01634 | 8060.01634 | 0.58590 | 0.58590 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 156.05113 | 156.05113 | 6.67242E-003 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8602.17511 | 8602.17511 | 0.62530 | 0.62530 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 34.35000 | 1.71565E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 92.90283 | 92.90283 | 3.97317E-003 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8391.29792 | 8391.29792 | 0.60999 | 0.60999 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 828.50398 | 828.50398 | 3.50378E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8457.83278 | 8457.83278 | 0.61482 | 0.61482 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 549.03549 | 549.03549 | 2.32164E-002 | 5.66790E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 8153.80865 | 8153.80865 | 0.59273 | 0.59273 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 871.75555 | 871.75555 | 3.68474E-002 | 8.95286E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9229.92374 | 9229.92374 | 0.67095 | 0.67095 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 549.02489 | 549.02489 | 2.32160E-002 | 5.66753E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73409.85 | 4.48086 | 4.48086 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | PACU_VAV_MID | Cooling | Sensible | 67048.85 | 4.01968 | 4.01968 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | PACU_VAV_TOP | Cooling | Sensible | 76419.85 | 4.70780 | 4.70780 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.48184 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30198 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63783 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80527 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26169E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21292.81149 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98489 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37758 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63715 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00906E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21270.04127 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.13832 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35049 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63722 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93463 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08706E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21272.38852 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70469 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22420 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13460 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59787 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69937E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4493.22541 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63927 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15646 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50236E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41723 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43511E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2838.34988 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68540 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23051 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.19600 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13434 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61469 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65286E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4484.64212 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74173 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13484 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52985E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35958 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82554E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2847.52682 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60409 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26154 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13411 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69743 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45677E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4476.92777 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57924 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17268 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14700 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51478E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46048 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20641E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2842.49847 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58590 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26966 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13417 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71909 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41290E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4479.03042 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62530 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15995 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13600 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.50414E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42652 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38205E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2838.94523 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60999 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25901 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13420 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69069 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47100E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4479.93402 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61482 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43382 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34197E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 1518.82792 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59273 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26655 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13455 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71080 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42937E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4491.65561 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67095 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14907 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52104E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39751 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55592E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2844.58669 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.43818 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07630 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.87636 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07630 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.48086 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.48086 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.24020 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.23669 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07595 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.47338 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07595 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.01968 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.01968 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.26767 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45471 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07648 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.90942 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07648 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.70780 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.70780 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.22866 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.48086 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.01968 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.70780 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.48086 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.48086 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108536.80571 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70926 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.49347 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36175.31734 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70926 |
152 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 20810.26571 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.48086 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.01968 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.01968 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 99818.18812 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.33976 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33269.40210 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
161 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 18668.43250 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.01968 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.70780 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.70780 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112376.82538 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71396 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56911 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37455.19590 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71396 |
170 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 21864.25084 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.70780 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 108274.41 | 369447.63 | 12.47 | 3.20 | 3.57 | 3.77 | 3.91 | 10.90 | 12.20 | 12.86 | 13.35 | 5.1801 | 4.1134 | 2.7670 | 1.1799 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 99655.16 | 340037.52 | 12.53 | 3.21 | 3.59 | 3.79 | 3.92 | 10.94 | 12.25 | 12.92 | 13.38 | 4.6470 | 3.6786 | 2.4755 | 1.0670 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 112052.25 | 382338.14 | 12.44 | 3.19 | 3.57 | 3.76 | 3.90 | 10.88 | 12.17 | 12.82 | 13.32 | 5.4425 | 4.3161 | 2.9059 | 1.2346 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.4811313235 | 0.3052764841 | Pass | Pass | 0.3067767932 | 0.5173440596 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.9877259122E-002 | 7.1467092853E-002 | Pass | Pass | 0.2306246675 | 0.4157871561 | Fail | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2590959512E-002 | 5.3610742729E-002 | Pass | Pass | 0.3071196461 | 1.1921663655 | Fail | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1107200752E-002 | 5.0305939348E-002 | Pass | Pass | 0.3148790736 | 0.6811302975 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2309781294 | 0.2749010321 | Pass | Pass | 0.2003940766 | 0.4056260960 | Pass | Fail |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2395585321 | 0.2741971822 | Pass | Pass | 0.2119943650 | 0.4063957368 | Pass | Fail |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2379656207 | 0.2837700917 | Pass | Pass | 0.2180467527 | 0.4162017423 | Pass | Fail |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2524367757 | 0.3040212151 | Pass | Pass | 0.2217265858 | 0.4269321804 | Pass | Fail |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2613488177 | 0.3149263889 | Pass | Pass | 0.2272194453 | 0.4369440415 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2508422619 | 0.2997146975 | Pass | Pass | 0.2245433070 | 0.4330048627 | Pass | Fail |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4014212572 | 0.2716819570 | Pass | Pass | 0.2446569695 | 0.4286280775 | Pass | Fail |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3996823696 | 0.2919793023 | Pass | Pass | 0.2785074080 | 0.4858158567 | Pass | Fail |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4058119713 | 0.2922290341 | Pass | Pass | 0.2755200667 | 0.4825220351 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3981431151 | 0.2799069437 | Pass | Pass | 0.2524721084 | 0.4389465204 | Pass | Fail |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2169065042 | 0.2712550352 | Pass | Pass | 0.1994444853 | 0.4024088909 | Pass | Fail |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2188108278 | 0.2854029831 | Pass | Pass | 0.2269805673 | 0.4543247568 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2256535511 | 0.2913580452 | Pass | Pass | 0.2259204978 | 0.4508846408 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2194587725 | 0.2815208516 | Pass | Pass | 0.2113097975 | 0.4250401845 | Pass | Fail |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3161.97 | -129.3 | 0.00 | -2152.2 | 4689.50 | 5570.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.43 | 0.0000 | Y | 6.60 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 4.19 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.36 | 0.0000 | Y | 6.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.31 | 0.0000 | Y | 4.16 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.40 | 0.0000 | Y | 6.59 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.33 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.28 | 0.0000 | Y | 4.15 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.43 | 0.0000 | Y | 6.60 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.36 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.31 | 0.0000 | Y | 4.16 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.33 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.93 | 41.93 | 4.44 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.83 | 62.88 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.83 | 45.49 | 40.26 | |
Exterior Lighting Total | 5686.19 | 49.51 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108536.81 | 76980.35 | 31556.45 | 0.71 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 99818.19 | 69980.86 | 29837.33 | 0.70 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112376.83 | 80232.64 | 32144.19 | 0.71 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 108274.4 | 3.20 | 10.90 | N/A | N/A | 12.47 | |
PACU_VAV_MID COOLING COIL | 99655.2 | 3.21 | 10.94 | N/A | N/A | 12.53 | |
PACU_VAV_TOP COOLING COIL | 112052.2 | 3.19 | 10.88 | N/A | N/A | 12.44 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21292.81 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21270.04 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 21272.39 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4493.23 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2838.35 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4484.64 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2847.53 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4476.93 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2842.50 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4479.03 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2838.95 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4479.93 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1518.83 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4491.66 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2844.59 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 20810.27 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 18668.43 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 21864.25 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.48 | 9808.65 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.02 | 8799.12 | 2189.01 | 1.00 | 1.15 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.71 | 10305.43 | 2189.01 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 108274.41 | 3.20 | 10.90 | 12.47 | 5.1801 | 3.57 | 12.20 | 4.1134 | 3.77 | 12.86 | 2.7670 | 3.91 | 13.35 | 1.1799 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 99655.16 | 3.21 | 10.94 | 12.53 | 4.6470 | 3.59 | 12.25 | 3.6786 | 3.79 | 12.92 | 2.4755 | 3.92 | 13.38 | 1.0670 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112052.25 | 3.19 | 10.88 | 12.44 | 5.4425 | 3.57 | 12.17 | 4.3161 | 3.76 | 12.82 | 2.9059 | 3.90 | 13.32 | 1.2346 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 34442.54 | 34442.54 | 35.02 | 2.482 | 2.482 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00886 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_MID | 27573.93 | 27573.93 | 28.04 | 1.985 | 1.985 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 28.91 | 0.01715 | 0.425 | 0.00 |
CORE_TOP | 29416.84 | 29416.84 | 29.91 | 2.138 | 2.138 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 35.20 | 0.01716 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9693.98 | 9693.98 | 46.75 | 0.705 | 0.705 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00891 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8794.13 | 8794.13 | 67.00 | 0.639 | 0.639 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:50:00 | 24.00 | 24.00 | 0.00880 | 31.73 | 0.01715 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9428.63 | 9428.63 | 45.47 | 0.685 | 0.685 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00892 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10203.51 | 10203.51 | 77.74 | 0.742 | 0.742 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00875 | 34.58 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 8310.26 | 8310.26 | 40.08 | 0.604 | 0.604 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00890 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7968.42 | 7968.42 | 60.71 | 0.579 | 0.579 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:40:00 | 24.00 | 24.00 | 0.00877 | 31.49 | 0.01715 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8060.02 | 8060.02 | 38.87 | 0.586 | 0.586 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00891 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8602.18 | 8602.18 | 65.54 | 0.625 | 0.625 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:30:00 | 24.00 | 24.00 | 0.00875 | 34.35 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8391.30 | 8391.30 | 40.47 | 0.610 | 0.610 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00895 | 34.95 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8457.83 | 8457.83 | 64.43 | 0.615 | 0.615 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00879 | 31.25 | 0.01715 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 8153.81 | 8153.81 | 39.33 | 0.593 | 0.593 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00896 | 35.20 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9229.92 | 9229.92 | 70.32 | 0.671 | 0.671 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00876 | 34.58 | 0.01716 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 0.425 | 00:10:00 | 15.60 | 22.19 | 0.01480 | 20.10 | 0.01480 | 0.425 | 0.00 | |
CORE_MID | 1194.45 | 1194.45 | 1.21 | 0.051 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00801 | 20.10 | 0.01480 | 0.425 | 0.00 |
CORE_TOP | 4647.48 | 4647.48 | 4.73 | 0.195 | 0.425 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 1567.85 | 1567.85 | 7.56 | 0.066 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00999 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 1018.69 | 1018.69 | 7.76 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01005 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 1617.98 | 1617.98 | 7.80 | 0.068 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00996 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 1018.65 | 1018.65 | 7.76 | 0.043 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01005 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 121.97 | 121.97 | 0.59 | 0.005 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01209 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 92.90 | 92.90 | 0.71 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01187 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 156.05 | 156.05 | 0.75 | 0.007 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01168 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 92.90 | 92.90 | 0.71 | 0.004 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01187 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 828.50 | 828.50 | 4.00 | 0.035 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01030 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 549.04 | 549.04 | 4.18 | 0.023 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01034 | 20.10 | 0.01480 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 871.76 | 871.76 | 4.20 | 0.037 | 0.090 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01025 | 20.10 | 0.01480 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 549.02 | 549.02 | 4.18 | 0.023 | 0.057 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01034 | 20.10 | 0.01480 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.48 | 4.48 | 0.00 | 0.00 | 4.4809 | 1.0763 | 4.4809 | 0.2402 | 0.3000 |
PACU_VAV_MID | 4.02 | 4.02 | 0.00 | 0.00 | 4.0197 | 1.0760 | 4.0197 | 0.2677 | 0.3000 |
PACU_VAV_TOP | 4.71 | 4.71 | 0.00 | 0.00 | 4.7078 | 1.0765 | 4.7078 | 0.2287 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21292.811 | 21292.811 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 21292.81 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21270.041 | 21270.041 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21270.04 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800820 | 51.7451 | 1194.45 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 21272.389 | 21272.389 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21272.39 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 4647.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 4493.225 | 4493.225 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4493.23 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00999438 | 64.3701 | 1567.85 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 2838.350 | 2838.350 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2838.35 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01004625 | 64.6986 | 1018.69 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 4484.642 | 4484.642 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4484.64 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00996293 | 64.1707 | 1617.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 2847.527 | 2847.527 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2847.53 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01004632 | 64.6990 | 1018.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4476.928 | 4476.928 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4476.93 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01209488 | 77.6465 | 121.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2842.498 | 2842.498 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2842.50 | 1892.12 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01187381 | 76.2537 | 92.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4479.030 | 4479.030 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4479.03 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01168209 | 75.0451 | 156.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2838.945 | 2838.945 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2838.95 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01187385 | 76.2539 | 92.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 4479.934 | 4479.934 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4479.93 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01030236 | 66.3240 | 828.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 1518.828 | 1518.828 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 1518.83 | 1518.83 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01033858 | 66.5531 | 549.04 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 4491.656 | 4491.656 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4491.66 | 2988.74 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01024749 | 65.9764 | 871.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 2844.587 | 2844.587 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 2844.59 | 1892.00 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01033863 | 66.5535 | 549.02 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 108536.806 | 76980.353 | 4.480857 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 110239.10 | 80921.30 | 4.480857 | 26.40 | 18.95 | 0.01064711 | 11.02 | 11.02 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 21.3374 | 24.00 | 0.00887235 | 47.7137 | 61406.72 | 0.00 | 111916.02 | 78294.38 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 20810.266 | 20810.266 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 20810.27 | 20810.27 | 1.344257 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 71.1248 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 99818.188 | 69980.857 | 4.019678 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 102233.20 | 73079.22 | 4.019678 | 26.63 | 19.22 | 0.01090083 | 11.03 | 11.03 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 23.7855 | 24.00 | 0.00894104 | 48.0782 | 55145.33 | 0.00 | 102925.95 | 71200.73 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 18668.432 | 18668.432 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 18668.43 | 18668.43 | 1.205904 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 79.2849 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 112376.825 | 80232.637 | 4.707801 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 113962.34 | 84220.86 | 4.707801 | 26.24 | 18.84 | 0.01057105 | 11.02 | 11.02 | 0.00850000 | 35.03 | 0.01715783 | 25.79 | 20.3088 | 24.00 | 0.00888919 | 47.8034 | 64663.48 | 0.00 | 115875.59 | 81577.41 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 21864.251 | 21864.251 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 21864.25 | 21864.25 | 1.412340 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 67.6962 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21292.811 | 21292.811 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 21292.81 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21292.81 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21270.041 | 21270.041 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21270.04 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21270.04 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.87 | 0.00800820 | 21.00 | 0.00800820 | 51.7451 | 1194.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 21272.389 | 21272.389 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21272.39 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21272.39 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.70 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 4647.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4493.225 | 4493.225 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4493.23 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4493.23 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.00999438 | 21.00 | 0.00999438 | 64.3701 | 1567.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 2838.350 | 2838.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2838.35 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2838.35 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01004625 | 21.00 | 0.01004625 | 64.6986 | 1018.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4484.642 | 4484.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4484.64 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4484.64 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.56 | 0.00996293 | 21.00 | 0.00996293 | 64.1707 | 1617.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2847.527 | 2847.527 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2847.53 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2847.53 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.57 | 0.01004632 | 21.00 | 0.01004632 | 64.6990 | 1018.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4476.928 | 4476.928 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4476.93 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4476.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.97 | 0.01209488 | 21.00 | 0.01209488 | 77.6465 | 121.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 2842.498 | 2842.498 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2842.50 | 1892.12 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2842.50 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01187381 | 21.00 | 0.01187381 | 76.2537 | 92.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4479.030 | 4479.030 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4479.03 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4479.03 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01168209 | 21.00 | 0.01168209 | 75.0451 | 156.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2838.945 | 2838.945 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2838.95 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2838.95 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.96 | 0.01187385 | 21.00 | 0.01187385 | 76.2539 | 92.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4479.934 | 4479.934 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4479.93 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4479.93 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01030236 | 21.00 | 0.01030236 | 66.3240 | 828.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 1518.828 | 1518.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 1518.83 | 1518.83 | 1.0000 | 0.06821858 | 0.056679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1518.83 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01033858 | 21.00 | 0.01033858 | 66.5531 | 549.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4491.656 | 4491.656 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4491.66 | 2988.74 | 1.0000 | 0.10775618 | 0.089529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4491.66 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.75 | 0.01024749 | 21.00 | 0.01024749 | 65.9764 | 871.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2844.587 | 2844.587 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 2844.59 | 1892.00 | 1.0000 | 0.06821410 | 0.056675 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2844.59 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.76 | 0.01033863 | 21.00 | 0.01033863 | 66.5535 | 549.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108536.806 | 76980.353 | 4.480857 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6325 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.480857 | 5.39313699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 110239.10 | 80921.30 | 1.0157 | 5.39313699 | 4.480857 | 26.40 | 18.95 | 0.01064711 | 53675.9 | 11.02 | 11.02 | 0.00850000 | 32510.6 | -999.0 | -999.00 | -999.00 | -999.00 | 9808.645 | 100430.46 | 35.20 | 0.01715815 | 25.83 | 0.95610000 | 21.3374 | 24.00 | 0.00887235 | 24.00 | 0.00887235 | 47.7137 | 61406.72 | 0.00 | 111916.02 | 78294.38 | 5.18014885 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.86 | 11.85 | 0.00863989 | 33717.6 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20810.266 | 20810.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.480857 | 5.39313699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 20810.27 | 20810.27 | 1.0000 | 1.61794110 | 1.344257 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20810.27 | 0.00 | 0.00000000 | -6.26 | 0.95610000 | 71.1248 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 99818.188 | 69980.857 | 4.019678 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99352 | 1025.1041 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.019678 | 4.83806479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | Sensible | 102233.20 | 73079.22 | 1.0242 | 4.83806479 | 4.019678 | 26.63 | 19.22 | 0.01090083 | 54560.5 | 11.03 | 11.03 | 0.00850000 | 32511.4 | -999.0 | -999.00 | -999.00 | -999.00 | 8799.120 | 93434.08 | 35.03 | 0.01715783 | 25.79 | 0.95610000 | 23.7855 | 24.00 | 0.00894104 | 24.00 | 0.00894104 | 48.0782 | 55145.33 | 0.00 | 102925.95 | 71200.73 | 4.64699781 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850793 | 33173.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18668.432 | 18668.432 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.019678 | 4.83806479 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 18668.43 | 18668.43 | 1.0000 | 1.45141944 | 1.205904 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18668.43 | 0.00 | 0.00000000 | -6.26 | 0.95610000 | 79.2849 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112376.825 | 80232.637 | 4.707801 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4911 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.707801 | 5.66628517 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | Sensible | 113962.34 | 84220.86 | 1.0141 | 5.66628517 | 4.707801 | 26.24 | 18.84 | 0.01057105 | 53322.6 | 11.02 | 11.02 | 0.00850000 | 32510.3 | -999.0 | -999.00 | -999.00 | -999.00 | 10305.427 | 103656.91 | 35.03 | 0.01715783 | 25.79 | 0.95610000 | 20.3088 | 24.00 | 0.00888919 | 24.00 | 0.00888919 | 47.8034 | 64663.48 | 0.00 | 115875.59 | 81577.41 | 5.44250974 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.99 | 11.98 | 0.00871382 | 34031.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21864.251 | 21864.251 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.707801 | 5.66628517 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 21864.25 | 21864.25 | 1.0000 | 1.69988555 | 1.412340 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21864.25 | 0.00 | 0.00000000 | -6.26 | 0.95610000 | 67.6962 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5943.00 | 0.00 | 0.00 |
CORE_MID | 5779.67 | 0.00 | 0.00 |
CORE_TOP | 5730.50 | 1.17 | 0.00 |
PERIMETER_TOP_ZN_3 | 5841.00 | 449.00 | 439.17 |
PERIMETER_TOP_ZN_2 | 5914.17 | 667.00 | 666.67 |
PERIMETER_TOP_ZN_1 | 5902.33 | 543.67 | 542.50 |
PERIMETER_TOP_ZN_4 | 5874.83 | 565.83 | 558.67 |
PERIMETER_BOT_ZN_3 | 5939.83 | 145.67 | 145.67 |
PERIMETER_BOT_ZN_2 | 5942.33 | 464.00 | 464.00 |
PERIMETER_BOT_ZN_1 | 5942.67 | 1789.33 | 1789.33 |
PERIMETER_BOT_ZN_4 | 5941.67 | 348.17 | 348.17 |
PERIMETER_MID_ZN_3 | 5917.83 | 271.67 | 271.00 |
PERIMETER_MID_ZN_2 | 5028.00 | 573.33 | 573.33 |
PERIMETER_MID_ZN_1 | 5936.00 | 411.00 | 411.00 |
PERIMETER_MID_ZN_4 | 5929.50 | 446.50 | 446.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 2259.00 | 2250.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 4.33 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 59.00 | 0.00 | 52.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 122.00 | 0.00 | 115.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 106.17 | 0.00 | 101.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 99.50 | 0.00 | 80.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 22.33 | 0.00 | 19.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 94.67 | 0.00 | 91.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 776.83 | 0.00 | 775.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 78.00 | 0.00 | 62.67 |
PERIMETER_MID_ZN_3 | 0.00 | 28.17 | 0.00 | 26.00 |
PERIMETER_MID_ZN_2 | 0.00 | 97.17 | 0.00 | 95.50 |
PERIMETER_MID_ZN_1 | 0.00 | 111.17 | 0.00 | 110.67 |
PERIMETER_MID_ZN_4 | 0.00 | 74.67 | 0.00 | 62.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 971.83 | 0.00 | 938.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.467 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.440 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.441 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.650 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.789 | 0.026 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.712 | 0.025 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.772 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.544 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.663 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.682 | 1.228 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.653 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.651 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.753 | 0.023 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.711 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.779 | 0.022 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 7946385.90 | 0.00 | 7946385.90 | 0.00 | 7946385.90 | 13393058.27 | 7211.89 | 956.24 | 591.87 | 445.83 |
CORE_MID | 7240073.96 | 0.00 | 7240073.96 | 0.00 | 7240073.96 | 13393058.27 | 7918.73 | 813.18 | 28.09 | 266.89 |
CORE_TOP | 7275646.46 | 0.00 | 7275646.46 | 0.00 | 7275646.46 | 13393058.27 | 7892.90 | 849.81 | 17.29 | 278.78 |
PERIMETER_TOP_ZN_3 | 2221008.18 | 0.00 | 2221008.18 | 148624.63 | 2369632.81 | 2823374.22 | 3681.82 | 828.93 | 4249.25 | 278.78 |
PERIMETER_TOP_ZN_2 | 1693493.20 | 0.00 | 1693493.20 | 99082.49 | 1792575.69 | 1787429.43 | 3529.70 | 723.29 | 4507.01 | 278.78 |
PERIMETER_TOP_ZN_1 | 2422418.06 | 0.00 | 2422418.06 | 148624.63 | 2571042.68 | 2823374.22 | 3562.18 | 789.59 | 4408.23 | 278.78 |
PERIMETER_TOP_ZN_4 | 1666874.18 | 0.00 | 1666874.18 | 99082.49 | 1765956.67 | 1787312.18 | 3553.06 | 717.33 | 4489.61 | 278.78 |
PERIMETER_BOT_ZN_3 | 1920693.18 | 0.00 | 1920693.18 | 79023.74 | 1999716.92 | 2823374.22 | 4809.30 | 1069.47 | 2881.22 | 445.83 |
PERIMETER_BOT_ZN_2 | 1464459.93 | 0.00 | 1464459.93 | 52682.17 | 1517142.11 | 1787429.43 | 3448.57 | 816.31 | 4495.11 | 445.83 |
PERIMETER_BOT_ZN_1 | 2365651.94 | 0.00 | 2365651.94 | 4024723.19 | 6390375.13 | 2823374.22 | 3596.23 | 861.59 | 4302.18 | 445.83 |
PERIMETER_BOT_ZN_4 | 1450807.08 | 0.00 | 1450807.08 | 52682.17 | 1503489.26 | 1787312.18 | 3742.77 | 896.44 | 4120.79 | 445.83 |
PERIMETER_MID_ZN_3 | 2218923.39 | 0.00 | 2218923.39 | 123719.22 | 2342642.62 | 2823374.22 | 3726.73 | 797.26 | 4236.01 | 266.89 |
PERIMETER_MID_ZN_2 | 1624155.72 | 0.00 | 1624155.72 | 82478.99 | 1706634.70 | 1601953.02 | 3554.40 | 681.74 | 4523.87 | 1175.89 |
PERIMETER_MID_ZN_1 | 2415637.45 | 0.00 | 2415637.45 | 123719.22 | 2539356.68 | 2823374.22 | 3578.31 | 742.71 | 4438.98 | 266.89 |
PERIMETER_MID_ZN_4 | 1675611.15 | 0.00 | 1675611.15 | 82478.99 | 1758090.14 | 1787312.18 | 3573.84 | 698.12 | 4488.05 | 266.89 |
Total Facility | 45601839.78 | 0.00 | 45601839.78 | 5116921.93 | 50718761.71 | 67658168.57 | 8299.94 | 1785.68 | 5001.36 | 1443.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3390 | 0.0000 | 0.3390 | 0.0000 | 0.3390 | 0.4247 | 4782.75 | 604.26 | 555.99 |
CORE_MID | 0.3196 | 0.0000 | 0.3196 | 0.0000 | 0.3196 | 0.4247 | 5329.24 | 591.14 | 22.62 |
CORE_TOP | 0.3205 | 0.0000 | 0.3205 | 0.0000 | 0.3205 | 0.4247 | 5304.74 | 624.13 | 14.13 |
PERIMETER_TOP_ZN_3 | 0.0995 | 0.0000 | 0.0995 | 0.0038 | 0.1033 | 0.0895 | 1113.46 | 602.13 | 4227.41 |
PERIMETER_TOP_ZN_2 | 0.0764 | 0.0000 | 0.0764 | 0.0025 | 0.0790 | 0.0567 | 960.25 | 498.73 | 4484.02 |
PERIMETER_TOP_ZN_1 | 0.1090 | 0.0000 | 0.1090 | 0.0038 | 0.1127 | 0.0895 | 988.52 | 564.09 | 4390.39 |
PERIMETER_TOP_ZN_4 | 0.0748 | 0.0000 | 0.0748 | 0.0025 | 0.0773 | 0.0567 | 1002.35 | 512.40 | 4428.24 |
PERIMETER_BOT_ZN_3 | 0.0832 | 0.0000 | 0.0832 | 0.0020 | 0.0852 | 0.0895 | 2355.50 | 718.08 | 2869.43 |
PERIMETER_BOT_ZN_2 | 0.0642 | 0.0000 | 0.0642 | 0.0013 | 0.0655 | 0.0567 | 1008.62 | 463.25 | 4471.13 |
PERIMETER_BOT_ZN_1 | 0.1039 | 0.0000 | 0.1039 | 0.1864 | 0.2904 | 0.0895 | 1145.63 | 509.95 | 4287.42 |
PERIMETER_BOT_ZN_4 | 0.0633 | 0.0000 | 0.0633 | 0.0013 | 0.0646 | 0.0567 | 1321.93 | 563.13 | 4057.94 |
PERIMETER_MID_ZN_3 | 0.0997 | 0.0000 | 0.0997 | 0.0031 | 0.1028 | 0.0895 | 1145.32 | 576.01 | 4221.67 |
PERIMETER_MID_ZN_2 | 0.0730 | 0.0000 | 0.0730 | 0.0022 | 0.0752 | 0.0567 | 972.11 | 461.55 | 3600.35 |
PERIMETER_MID_ZN_1 | 0.1089 | 0.0000 | 0.1089 | 0.0031 | 0.1120 | 0.0895 | 996.99 | 520.43 | 4425.57 |
PERIMETER_MID_ZN_4 | 0.0755 | 0.0000 | 0.0755 | 0.0021 | 0.0776 | 0.0567 | 1010.04 | 494.10 | 4438.86 |
Total Facility | 2.0105 | 0.0000 | 2.0105 | 0.2142 | 2.2247 | 2.1513 | 5605.80 | 1328.83 | 4867.29 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21943986.76 | 0.00 | 21943986.76 | 22614548.33 | 3223.76 | 1.17 | 5535.08 | 445.83 |
PACU_VAV_MID | 21982267.76 | 0.00 | 21982267.76 | 22429071.92 | 3409.24 | 1.81 | 5348.95 | 266.89 |
PACU_VAV_TOP | 22134385.22 | 0.00 | 22134385.22 | 22614548.33 | 3397.18 | 1.22 | 5361.60 | 278.78 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9469 | 0.0000 | 0.9469 | 0.7171 | 843.83 | 0.85 | 5098.32 |
PACU_VAV_MID | 0.9807 | 0.0000 | 0.9807 | 0.7084 | 852.92 | 1.57 | 5088.50 |
PACU_VAV_TOP | 0.9855 | 0.0000 | 0.9855 | 0.7171 | 852.66 | 1.01 | 5089.32 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 101.11 | 0.00 | 0.00 | 0.00 | 0.00 | 5469.80 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 262.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5122.76 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 140.48 | 0.00 | 0.00 | 0.00 | 0.00 | 5260.23 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.8206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1021 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.1988 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1359 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0335 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1465 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2220 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
Electricity:Building | 951.02 | 13399.00 | 04-JUL-17:20 | 64821.47 | 18-DEC-17:00 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 951.02 | 13399.00 | 04-JUL-17:20 | 64821.47 | 18-DEC-17:00 |
InteriorLights:Electricity | 231.33 | 921.25 | 04-JUL-17:20 | 23150.96 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.33 | 921.25 | 04-JUL-17:20 | 23150.96 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity | 231.33 | 921.25 | 04-JUL-17:20 | 23150.96 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.33 | 921.25 | 04-JUL-17:20 | 23150.96 | 18-DEC-17:00 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.93 | 413.68 | 02-APR-17:10 | 2313.75 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.60 | 27.57 | 01-JAN-08:20 | 878.50 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.60 | 27.57 | 01-JAN-08:20 | 878.50 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.60 | 263.78 | 04-JUL-17:10 | 1472.53 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 563.95 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 563.95 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.91 | 415.77 | 26-MAR-17:10 | 2268.94 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 833.71 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 833.71 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.56 | 261.87 | 12-MAR-17:10 | 1421.13 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.16 | 17.46 | 01-JAN-08:30 | 512.56 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.16 | 17.46 | 01-JAN-08:30 | 512.56 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.92 | 413.68 | 02-APR-17:10 | 2307.45 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.59 | 27.57 | 01-JAN-08:10 | 872.20 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.59 | 27.57 | 01-JAN-08:10 | 872.20 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.59 | 263.66 | 04-JUL-17:10 | 1469.59 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 561.02 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 561.02 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.90 | 415.49 | 26-MAR-17:10 | 2260.68 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:30 | 825.45 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-07:30 | 825.45 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.55 | 261.87 | 12-MAR-17:10 | 1415.42 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.15 | 17.46 | 01-JAN-08:30 | 506.85 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.15 | 17.46 | 01-JAN-08:30 | 506.85 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.93 | 413.68 | 02-APR-17:10 | 2313.73 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.60 | 27.57 | 01-JAN-08:20 | 878.49 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.60 | 27.57 | 01-JAN-08:20 | 878.49 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.60 | 263.78 | 04-JUL-17:10 | 1472.52 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 563.94 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.19 | 17.46 | 01-JAN-07:10 | 563.94 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.91 | 415.77 | 26-MAR-17:10 | 2268.93 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 833.69 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-07:40 | 833.69 | 18-DEC-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.56 | 261.87 | 12-MAR-17:10 | 1421.12 | 18-DEC-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.16 | 17.46 | 01-JAN-08:30 | 512.55 | 18-DEC-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.16 | 17.46 | 01-JAN-08:30 | 512.55 | 18-DEC-17:00 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 1033.22 | 367.92 | 01-JAN-00:10 | 106554.99 | 13-JUN-15:00 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 15-FEB-13:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 15-FEB-13:10 |
ElectricityPurchased:Facility | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
ElectricityPurchased:Plant | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
Cogeneration:ElectricityPurchased | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
General:Cogeneration:ElectricityPurchased | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
ElectricityNet:Plant | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
Cogeneration:ElectricityNet | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
General:Cogeneration:ElectricityNet | 2069.55 | 13794.12 | 26-MAR-17:20 | 170680.94 | 13-JUN-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 122.16 | 0.00 | 01-JAN-00:10 | 17026.58 | 12-JUN-15:20 |
General:Fans:Electricity | 122.16 | 0.00 | 01-JAN-00:10 | 17026.58 | 12-JUN-15:20 |
ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.51 | 0.00 | 01-JAN-06:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 884.18 | 0.00 | 01-JAN-00:10 | 89027.53 | 13-JUN-15:00 |
General:Cooling:Electricity | 884.18 | 0.00 | 01-JAN-00:10 | 89027.53 | 13-JUN-15:00 |
Electricity:Plant | 35.80 | 0.00 | 01-JAN-00:10 | 4209.75 | 12-JAN-13:00 |
WaterSystems:Electricity | 35.65 | 0.00 | 01-JAN-00:10 | 4202.90 | 12-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 35.65 | 0.00 | 01-JAN-00:10 | 4202.90 | 12-JAN-13:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-14:50 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 19-MAR-14:50 |
WIRED_LTG_ELECTRICITY | 6.50 | 0.00 | 01-JAN-00:10 | 650.54 | 18-DEC-17:10 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 5774.02 | 0.00 | 01-JAN-00:10 | 498223.58 | 13-JUN-15:30 |
EnergyTransfer:Building | 1935.78 | 0.00 | 01-JAN-00:10 | 172516.93 | 21-FEB-15:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 336.37 | 0.00 | 01-JAN-00:10 | 26874.86 | 02-JAN-08:30 |
Heating:EnergyTransfer | 0.63 | 0.00 | 01-JAN-00:10 | 1820.12 | 02-AUG-04:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.63 | 0.00 | 01-JAN-00:10 | 1820.12 | 02-AUG-04:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1935.15 | 0.00 | 01-JAN-00:10 | 172516.93 | 21-FEB-15:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 336.37 | 0.00 | 01-JAN-00:10 | 26874.86 | 02-JAN-08:30 |
General:Cooling:EnergyTransfer | 1935.15 | 0.00 | 01-JAN-00:10 | 172516.93 | 21-FEB-15:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 336.37 | 0.00 | 01-JAN-00:10 | 26874.86 | 02-JAN-08:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.40 | 0.00 | 01-JAN-00:10 | 10733.40 | 05-MAY-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1422.16 | 23-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.19 | 0.00 | 01-JAN-00:10 | 1422.16 | 23-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.21 | 0.00 | 01-JAN-00:10 | 10733.40 | 05-MAY-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 81.21 | 0.00 | 01-JAN-00:10 | 10733.40 | 05-MAY-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 48.75 | 0.00 | 01-JAN-00:10 | 5427.68 | 30-MAY-12:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.14 | 0.00 | 01-JAN-00:10 | 625.35 | 17-DEC-10:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.14 | 0.00 | 01-JAN-00:10 | 625.35 | 17-DEC-10:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 48.60 | 0.00 | 01-JAN-00:10 | 5427.68 | 30-MAY-12:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 48.60 | 0.00 | 01-JAN-00:10 | 5427.68 | 30-MAY-12:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 56.90 | 0.00 | 01-JAN-00:10 | 5776.12 | 30-MAY-11:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.30 | 0.00 | 01-JAN-00:10 | 887.57 | 28-SEP-04:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.30 | 0.00 | 01-JAN-00:10 | 887.57 | 28-SEP-04:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 56.60 | 0.00 | 01-JAN-00:10 | 5776.12 | 30-MAY-11:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 56.60 | 0.00 | 01-JAN-00:10 | 5776.12 | 30-MAY-11:00 |
EnergyTransfer:Zone:CORE_MID | 245.34 | 0.00 | 01-JAN-00:10 | 20112.42 | 02-JAN-08:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 245.34 | 0.00 | 01-JAN-00:10 | 20112.42 | 02-JAN-08:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 245.34 | 0.00 | 01-JAN-00:10 | 20112.42 | 02-JAN-08:30 |
EnergyTransfer:Zone:CORE_TOP | 258.40 | 0.00 | 01-JAN-00:10 | 21591.23 | 21-FEB-14:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 258.40 | 0.00 | 01-JAN-00:10 | 21591.23 | 21-FEB-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 258.40 | 0.00 | 01-JAN-00:10 | 21591.23 | 21-FEB-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.36 | 0.00 | 01-JAN-00:10 | 9441.43 | 12-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.36 | 0.00 | 01-JAN-00:10 | 9441.43 | 12-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.36 | 0.00 | 01-JAN-00:10 | 9441.43 | 12-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.89 | 0.00 | 01-JAN-00:10 | 7515.50 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.89 | 0.00 | 01-JAN-00:10 | 7515.50 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.89 | 0.00 | 01-JAN-00:10 | 7515.50 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.65 | 0.00 | 01-JAN-00:10 | 10133.33 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.65 | 0.00 | 01-JAN-00:10 | 10133.33 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.65 | 0.00 | 01-JAN-00:10 | 10133.33 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.02 | 0.00 | 01-JAN-00:10 | 8246.85 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.02 | 0.00 | 01-JAN-00:10 | 8246.85 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 63.02 | 0.00 | 01-JAN-00:10 | 8246.85 | 11-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.27 | 0.00 | 01-JAN-00:10 | 8533.70 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.27 | 0.00 | 01-JAN-00:10 | 8533.70 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 84.27 | 0.00 | 01-JAN-00:10 | 8533.70 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.22 | 0.00 | 01-JAN-00:10 | 7059.25 | 20-MAR-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.22 | 0.00 | 01-JAN-00:10 | 7059.25 | 20-MAR-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.22 | 0.00 | 01-JAN-00:10 | 7059.25 | 20-MAR-09:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 109.36 | 0.00 | 01-JAN-00:10 | 11107.01 | 05-MAY-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 109.36 | 0.00 | 01-JAN-00:10 | 11107.01 | 05-MAY-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 109.36 | 0.00 | 01-JAN-00:10 | 11107.01 | 05-MAY-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 64.11 | 0.00 | 01-JAN-00:10 | 7419.96 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 64.11 | 0.00 | 01-JAN-00:10 | 7419.96 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 64.11 | 0.00 | 01-JAN-00:10 | 7419.96 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 78.89 | 0.00 | 01-JAN-00:10 | 8473.00 | 12-JUN-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 78.89 | 0.00 | 01-JAN-00:10 | 8473.00 | 12-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 78.89 | 0.00 | 01-JAN-00:10 | 8473.00 | 12-JUN-15:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 58.43 | 0.00 | 01-JAN-00:10 | 7402.38 | 20-MAR-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 58.43 | 0.00 | 01-JAN-00:10 | 7402.38 | 20-MAR-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 58.43 | 0.00 | 01-JAN-00:10 | 7402.38 | 20-MAR-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 86.69 | 0.00 | 01-JAN-00:10 | 8987.54 | 26-DEC-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 86.69 | 0.00 | 01-JAN-00:10 | 8987.54 | 26-DEC-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 86.69 | 0.00 | 01-JAN-00:10 | 8987.54 | 26-DEC-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.73 | 0.00 | 01-JAN-00:10 | 7627.17 | 11-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.73 | 0.00 | 01-JAN-00:10 | 7627.17 | 11-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 59.73 | 0.00 | 01-JAN-00:10 | 7627.17 | 11-APR-15:40 |
PlantLoopHeatingDemand:Facility | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
EnergyTransfer:HVAC | 3805.32 | 0.00 | 01-JAN-00:10 | 328060.81 | 13-JUN-15:40 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3805.32 | 0.00 | 01-JAN-00:10 | 328060.81 | 13-JUN-15:40 |
EnergyTransfer:Plant | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
WaterSystems:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 3872.68 | 12-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -336.375 | 0.000 | 0.000 | 32.648 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -2.295 |
CORE_MID | 0.000 | 0.000 | 0.000 | -245.335 | 0.000 | 0.000 | 32.704 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 41.608 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -258.405 | 0.000 | 0.000 | 32.702 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 54.679 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -83.357 | 0.000 | 0.000 | 6.885 | 6.596 | 24.333 | 37.620 | 0.000 | 0.452 | 11.272 | 0.000 | -3.724 | 0.000 | -0.076 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -63.890 | 0.000 | 0.000 | 4.355 | 4.193 | 15.404 | 37.390 | 0.000 | 0.294 | 4.738 | 0.000 | -2.429 | 0.000 | -0.054 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -91.653 | 0.000 | 0.000 | 6.875 | 6.576 | 24.332 | 48.310 | 0.000 | 0.447 | 8.892 | 0.000 | -3.698 | 0.000 | -0.082 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -63.014 | 0.000 | 0.000 | 4.356 | 4.156 | 15.403 | 37.435 | 0.000 | 0.289 | 4.098 | 0.000 | -2.666 | 0.000 | -0.057 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -84.272 | 0.000 | 0.000 | 6.882 | 6.586 | 24.333 | 37.789 | 0.000 | 0.247 | 12.462 | 0.000 | -3.986 | 0.000 | -0.043 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -65.224 | 0.000 | 0.000 | 4.353 | 4.188 | 15.404 | 37.509 | 0.000 | 0.158 | 6.372 | 0.000 | -2.728 | 0.000 | -0.032 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -109.349 | 0.000 | 0.000 | 6.739 | 6.569 | 24.332 | 48.024 | 0.000 | 20.866 | 7.424 | 0.000 | -4.223 | 0.000 | -0.382 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -64.110 | 0.000 | 0.000 | 4.354 | 4.151 | 15.403 | 37.569 | 0.000 | 0.155 | 5.502 | 0.000 | -2.990 | 0.000 | -0.034 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -78.886 | 0.000 | 0.000 | 6.884 | 6.596 | 24.333 | 37.949 | 0.000 | 0.384 | 6.627 | 0.000 | -3.819 | 0.000 | -0.067 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -58.433 | 0.000 | 0.000 | 3.201 | 4.193 | 15.404 | 37.487 | 0.000 | 0.245 | 0.452 | 0.000 | -2.501 | 0.000 | -0.047 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -86.685 | 0.000 | 0.000 | 6.865 | 6.576 | 24.332 | 48.631 | 0.000 | 0.379 | 3.766 | 0.000 | -3.793 | 0.000 | -0.071 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -59.724 | 0.000 | 0.000 | 4.356 | 4.156 | 15.403 | 37.672 | 0.000 | 0.244 | 0.672 | 0.000 | -2.730 | 0.000 | -0.049 | -0.000 |
TOPFLOOR_PLENUM | 0.192 | -81.212 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.541 | 80.571 | 0.000 | 0.000 | 0.000 | -0.093 | 0.000 |
MIDFLOOR_PLENUM | 0.144 | -48.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.571 | 47.989 | 0.000 | 0.000 | 0.000 | -0.102 | 0.000 |
FIRSTFLOOR_PLENUM | 0.298 | -56.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.437 | 55.948 | 0.000 | 0.000 | 0.000 | -0.084 | -0.000 |
Total Facility | 0.634 | -186.412 | 0.000 | -1748.712 | 0.000 | 0.000 | 164.159 | 231.332 | 719.689 | 483.385 | 0.000 | 25.709 | 353.072 | 0.000 | -39.287 | 0.000 | -1.273 | -2.301 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | -41292.00 | 0.00 | 0.00 | 289.74 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 33380.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-OCT-04:04 | 0.00 | 0.00 | 0.00 | -33887.50 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 31233.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | -35875.43 | 0.00 | 0.00 | 294.96 | 211.73 | 3025.92 | 0.00 | 0.00 | 0.00 | 32342.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 18-JUN-10:32 | 0.00 | 0.00 | 0.00 | -12447.32 | 0.00 | 0.00 | 25.94 | 27.57 | 478.42 | 4463.52 | 0.00 | 90.50 | 7361.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-10:32 | 0.00 | 0.00 | 0.00 | -11481.04 | 0.00 | 0.00 | 14.98 | 17.46 | 302.86 | 3399.85 | 0.00 | 57.34 | 7688.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 08-JAN-12:13 | 0.00 | 0.00 | 0.00 | -12438.91 | 0.00 | 0.00 | 25.26 | 27.57 | 478.41 | 7492.59 | 0.00 | 44.70 | 4370.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 19-MAR-15:32 | 0.00 | 0.00 | 0.00 | -13251.09 | 0.00 | 0.00 | 12.29 | 17.46 | 302.86 | 6452.51 | 0.00 | 153.78 | 6312.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-10:32 | 0.00 | 0.00 | 0.00 | -10603.93 | 0.00 | 0.00 | 27.09 | 27.57 | 478.42 | 4549.64 | 0.00 | 50.73 | 5470.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-09:52 | 0.00 | 0.00 | 0.00 | -10366.86 | 0.00 | 0.00 | 15.94 | 17.46 | 302.86 | 4235.10 | 0.00 | 11.72 | 5783.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-JAN-12:42 | 0.00 | 0.00 | 0.00 | -11136.20 | 0.00 | 0.00 | 24.03 | 27.57 | 478.41 | 8322.37 | 0.00 | 9.17 | 2274.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:31 | 0.00 | 0.00 | 0.00 | -11728.54 | 0.00 | 0.00 | 14.36 | 17.46 | 302.86 | 5991.80 | 0.00 | 21.89 | 5380.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 18-JUN-10:32 | 0.00 | 0.00 | 0.00 | -10673.03 | 0.00 | 0.00 | 26.89 | 27.57 | 478.42 | 4527.46 | 0.00 | 78.07 | 5534.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 27-AUG-09:22 | 0.00 | 0.00 | 0.00 | -11079.50 | 0.00 | 0.00 | 15.81 | 17.46 | 302.86 | 5314.01 | 0.00 | 20.40 | 5408.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 16-JAN-12:42 | 0.00 | 0.00 | 0.00 | -11292.67 | 0.00 | 0.00 | 23.52 | 27.57 | 478.41 | 8277.90 | 0.00 | 13.23 | 2472.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-16:31 | 0.00 | 0.00 | 0.00 | -12553.26 | 0.00 | 0.00 | 13.91 | 17.46 | 302.86 | 5938.29 | 0.00 | 32.75 | 6248.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 05-MAY-13:05 | 0.00 | -10738.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.68 | 10672.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 30-MAY-12:02 | 0.00 | -5562.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 5549.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 30-MAY-12:10 | 0.00 | -5912.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 5903.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JUL-04:02 | 0.00 | 7878.15 | 0.00 | -197556.14 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 0.00 | 0.00 | 0.00 | 177679.21 | 0.00 | -4555.26 | 0.00 | -88.85 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 06-FEB-06:02 | 4974.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4974.92 |
MIDFLOOR_PLENUM | 02-AUG-04:02 | 2412.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.04 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2460.97 |
FIRSTFLOOR_PLENUM | 02-AUG-04:02 | 4063.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4099.06 |
Total Facility | 02-AUG-04:02 | -173461.53 | 182538.19 | 0.00 | -182538.19 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 3089.77 | 0.00 | 434.35 | 153294.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.8764 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4809 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.4734 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0197 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.9094 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7078 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4382 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0763 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2367 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4547 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0765 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4818 | 2.4818 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9849 | 1.9849 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1383 | 2.1383 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7047 | 0.7047 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6393 | 0.6393 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6854 | 0.6854 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7417 | 0.7417 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6041 | 0.6041 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5792 | 0.5792 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5859 | 0.5859 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6253 | 0.6253 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6100 | 0.6100 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6148 | 0.6148 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5927 | 0.5927 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6709 | 0.6709 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.8764 | 4.4809 | 4.8764 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.4734 | 4.0197 | 4.4734 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.9094 | 4.7078 | 4.9094 | 1.0765 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2409 | 1.2409 | 0.6378 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9924 | 0.9924 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0692 | 1.0692 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3523 | 0.3523 | 0.1346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3196 | 0.3196 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3427 | 0.3427 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3709 | 0.3709 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3020 | 0.3020 | 0.1341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2896 | 0.2896 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2929 | 0.2929 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3127 | 0.3127 | 0.0850 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3050 | 0.3050 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3074 | 0.3074 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2964 | 0.2964 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3355 | 0.3355 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4382 | 1.0763 | 1.0763 | 1.0763 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2367 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4547 | 1.0765 | 1.0765 | 1.0765 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 4982.19 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 938.67 |
Number of hours not met | 938.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 884.18 | 89027.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.33 | 23150.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.51 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 122.16 | 17026.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 35.65 | 4202.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 2069.55 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2069.55 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.43 |
Space Heating | 0.00 |
Space Cooling | 177.47 |
Fans (All) | 24.52 |
Service Water Heating | 7.16 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 415.39 |
Subtotal | 415.39 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.18 |
Space Heating | 0.00 |
Space Cooling | 42.72 |
Fans (All) | 5.90 |
Service Water Heating | 1.72 |
Receptacle Equipment | 34.78 |
Miscellaneous | 3.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1089. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7113.50 | 1646.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8621.00 | 139.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8635.67 | 124.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8140.33 | 619.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7883.67 | 876.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7991.83 | 768.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7695.50 | 1064.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8407.83 | 352.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7969.17 | 790.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8068.33 | 691.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7663.33 | 1096.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8238.00 | 522.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7924.67 | 835.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8063.17 | 696.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7727.33 | 1032.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8068.67 | 691.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8630.83 | 129.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8632.17 | 127.83 | 0.00 | 0.00 | 0.00 |
Min | 7113.50 | 124.33 | 0.00 | 0.00 | 0.00 |
Max | 8635.67 | 1646.50 | 0.00 | 0.00 | 0.00 |
Average | 8081.94 | 678.06 | 0.00 | 0.00 | 0.00 |
Sum | 145475.00 | 12205.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 127865.67 | 438.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128291.33 | 12.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128295.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24521.33 | 387.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128295.00 | 438.33 | 0.00 | 0.00 | 0.00 |
Average | 34096.24 | 47.09 | 0.00 | 0.00 | 0.00 |
Sum | 613732.33 | 847.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6502.83 | 2257.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8430.33 | 329.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8499.00 | 261.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5448.83 | 3311.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5279.00 | 3481.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5346.83 | 3413.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5198.17 | 3561.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6017.67 | 2742.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5549.17 | 3210.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 3778.17 | 4981.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5428.83 | 3331.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5461.33 | 3298.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5235.00 | 3525.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5310.67 | 3449.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5146.33 | 3613.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 6325.33 | 2434.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 6495.83 | 2264.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6844.67 | 1915.33 | 0.00 | 0.00 | 0.00 |
Min | 3778.17 | 261.00 | 0.00 | 0.00 | 0.00 |
Max | 8499.00 | 4981.83 | 0.00 | 0.00 | 0.00 |
Average | 5905.44 | 2854.56 | 0.00 | 0.00 | 0.00 |
Sum | 106298.00 | 51382.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127540.67 | 763.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128248.00 | 56.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128262.67 | 41.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24843.67 | 65.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14015.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24843.17 | 65.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14015.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24900.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 15889.50 | 9019.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24862.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24863.67 | 45.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128262.67 | 9019.50 | 0.00 | 0.00 | 0.00 |
Average | 33581.53 | 561.81 | 0.00 | 0.00 | 0.00 |
Sum | 604467.50 | 10112.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283427E+11 | 38503.29 | 12-JAN-05:03 | 24.00 | 22.62 | 0.199713E+10 | 2606.59 | 02-JAN-14:20 | 24.00 | 22.62 |
February | 0.257778E+11 | 38623.60 | 07-FEB-05:02 | 24.00 | 21.84 | 0.181086E+10 | 2606.59 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.296104E+11 | 38700.48 | 08-MAR-05:03 | 24.00 | 22.62 | 0.216122E+10 | 2606.59 | 03-MAR-10:20 | 24.00 | 22.62 |
April | 0.276980E+11 | 38451.00 | 22-APR-04:03 | 24.58 | 23.40 | 0.191900E+10 | 2606.60 | 20-APR-13:20 | 24.58 | 23.40 |
May | 0.295588E+11 | 38573.82 | 26-MAY-04:03 | 24.00 | 23.90 | 0.207840E+10 | 2606.59 | 25-MAY-13:20 | 24.00 | 23.90 |
June | 0.291849E+11 | 38133.16 | 03-JUN-04:03 | 25.42 | 25.21 | 0.207204E+10 | 2606.60 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.278881E+11 | 38544.89 | 22-JUL-04:53 | 24.00 | 23.26 | 0.192638E+10 | 2606.59 | 03-JUL-13:20 | 24.00 | 23.26 |
August | 0.291256E+11 | 38952.49 | 22-AUG-04:02 | 24.08 | 23.67 | 0.216182E+10 | 2606.60 | 17-AUG-13:20 | 24.08 | 23.67 |
September | 0.271740E+11 | 41296.06 | 19-SEP-05:03 | 24.00 | 24.00 | 0.191917E+10 | 2606.59 | 14-SEP-13:20 | 24.00 | 24.00 |
October | 0.277700E+11 | 38738.06 | 12-OCT-04:03 | 24.00 | 24.00 | 0.199635E+10 | 2606.60 | 30-OCT-13:20 | 24.33 | 24.25 |
November | 0.272126E+11 | 38564.97 | 09-NOV-05:03 | 24.00 | 23.57 | 0.197697E+10 | 2606.60 | 08-NOV-14:20 | 24.00 | 23.57 |
December | 0.270314E+11 | 38273.45 | 30-DEC-05:03 | 24.00 | 24.00 | 0.192693E+10 | 2606.59 | 11-DEC-14:20 | 24.00 | 24.00 |
Annual Sum or Average | 0.336374E+12 | 0.239463E+11 | ||||||||
Minimum of Months | 0.257778E+11 | 38133.16 | 24.00 | 21.84 | 0.181086E+10 | 2606.59 | 23.53 | 20.42 | ||
Maximum of Months | 0.296104E+11 | 41296.06 | 25.42 | 25.21 | 0.216182E+10 | 2606.60 | 34.13 | 26.89 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.654849E+10 | 9595.06 | 04-JAN-14:05 | 33.83 | 23.50 | 0.00 | 0.00 | 01-JAN-00:10 | 33.83 | 23.50 |
February | 0.653689E+10 | 10706.03 | 21-FEB-14:40 | 34.33 | 21.86 | 0.00 | 0.00 | 01-FEB-00:10 | 34.33 | 21.86 |
March | 0.791951E+10 | 10733.31 | 20-MAR-14:00 | 35.00 | 23.21 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 23.21 |
April | 0.758446E+10 | 10000.40 | 11-APR-14:20 | 34.87 | 26.08 | 0.00 | 0.00 | 01-APR-00:10 | 34.87 | 26.08 |
May | 0.760076E+10 | 10738.37 | 05-MAY-13:05 | 36.33 | 27.23 | 0.00 | 0.00 | 01-MAY-00:10 | 36.33 | 27.23 |
June | 0.799716E+10 | 10535.88 | 16-JUN-14:00 | 36.00 | 27.59 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 27.59 |
July | 0.647105E+10 | 9204.42 | 14-JUL-14:30 | 32.25 | 24.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.25 | 24.82 |
August | 0.654257E+10 | 9830.93 | 14-AUG-13:50 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.629626E+10 | 9747.27 | 06-SEP-14:00 | 34.00 | 26.51 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 26.51 |
October | 0.575757E+10 | 9324.97 | 02-OCT-13:30 | 31.00 | 26.24 | 0.00 | 0.00 | 01-OCT-00:10 | 31.00 | 26.24 |
November | 0.595739E+10 | 9178.54 | 22-NOV-13:02 | 31.50 | 24.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.50 | 24.57 |
December | 0.600041E+10 | 9523.79 | 26-DEC-14:05 | 31.17 | 22.67 | 0.00 | 0.00 | 01-DEC-00:10 | 31.17 | 22.67 |
Annual Sum or Average | 0.812125E+11 | 0.00 | ||||||||
Minimum of Months | 0.575757E+10 | 9178.54 | 31.00 | 21.86 | 0.00 | 0.00 | 31.00 | 21.86 | ||
Maximum of Months | 0.799716E+10 | 10738.37 | 36.33 | 27.67 | 0.00 | 0.00 | 36.33 | 27.67 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402833E+10 | 4972.58 | 17-JAN-15:30 | 30.30 | 22.71 | 0.00 | 0.00 | 01-JAN-00:10 | 30.30 | 22.71 |
February | 0.385032E+10 | 5406.89 | 21-FEB-15:30 | 32.95 | 22.99 | 0.00 | 0.00 | 01-FEB-00:10 | 32.95 | 22.99 |
March | 0.448354E+10 | 5161.11 | 20-MAR-15:00 | 35.00 | 24.82 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 24.82 |
April | 0.424968E+10 | 4771.97 | 17-APR-15:30 | 33.05 | 26.46 | 0.00 | 0.00 | 01-APR-00:10 | 33.05 | 26.46 |
May | 0.453841E+10 | 5562.06 | 30-MAY-12:02 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.471617E+10 | 5361.08 | 12-JUN-16:00 | 35.40 | 27.71 | 0.00 | 0.00 | 01-JUN-00:10 | 35.40 | 27.71 |
July | 0.392728E+10 | 4606.29 | 17-JUL-12:08 | 30.80 | 25.66 | 0.00 | 0.00 | 01-JUL-00:10 | 30.80 | 25.66 |
August | 0.399191E+10 | 4885.45 | 14-AUG-12:02 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.376001E+10 | 5081.60 | 05-SEP-12:02 | 33.02 | 26.93 | 0.00 | 0.00 | 01-SEP-00:10 | 33.02 | 26.93 |
October | 0.369647E+10 | 5040.64 | 10-OCT-14:20 | 30.83 | 26.20 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 26.20 |
November | 0.374694E+10 | 5162.88 | 13-NOV-13:02 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.361339E+10 | 5031.61 | 26-DEC-15:20 | 31.40 | 22.76 | 0.00 | 0.00 | 01-DEC-00:10 | 31.40 | 22.76 |
Annual Sum or Average | 0.486024E+11 | 0.00 | ||||||||
Minimum of Months | 0.361339E+10 | 4606.29 | 30.30 | 22.71 | 0.00 | 0.00 | 30.30 | 22.71 | ||
Maximum of Months | 0.471617E+10 | 5562.06 | 35.40 | 27.71 | 0.00 | 0.00 | 35.40 | 27.71 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470997E+10 | 5720.79 | 02-JAN-07:10 | 23.85 | 23.26 | 0.00 | 0.00 | 01-JAN-00:10 | 23.85 | 23.26 |
February | 0.442283E+10 | 5685.04 | 21-FEB-15:50 | 32.25 | 23.66 | 0.00 | 0.00 | 01-FEB-00:10 | 32.25 | 23.66 |
March | 0.511097E+10 | 5356.14 | 20-MAR-16:00 | 34.30 | 24.91 | 0.00 | 0.00 | 01-MAR-00:10 | 34.30 | 24.91 |
April | 0.481818E+10 | 5242.33 | 17-APR-16:00 | 32.60 | 26.25 | 0.00 | 0.00 | 01-APR-00:10 | 32.60 | 26.25 |
May | 0.517931E+10 | 5913.44 | 30-MAY-12:10 | 33.10 | 27.55 | 0.00 | 0.00 | 01-MAY-00:10 | 33.10 | 27.55 |
June | 0.538625E+10 | 5737.00 | 12-JUN-12:10 | 34.05 | 27.94 | 0.00 | 0.00 | 01-JUN-00:10 | 34.05 | 27.94 |
July | 0.462835E+10 | 5169.28 | 17-JUL-14:05 | 31.67 | 26.15 | 0.00 | 0.00 | 01-JUL-00:10 | 31.67 | 26.15 |
August | 0.477161E+10 | 5362.61 | 14-AUG-12:10 | 33.13 | 27.67 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 27.67 |
September | 0.443421E+10 | 5540.50 | 05-SEP-12:10 | 33.02 | 26.93 | 0.00 | 0.00 | 01-SEP-00:10 | 33.02 | 26.93 |
October | 0.436707E+10 | 5348.88 | 10-OCT-06:10 | 23.95 | 23.25 | 0.00 | 0.00 | 01-OCT-00:10 | 23.95 | 23.25 |
November | 0.442751E+10 | 5362.50 | 13-NOV-13:10 | 31.92 | 25.57 | 0.00 | 0.00 | 01-NOV-00:10 | 31.92 | 25.57 |
December | 0.434324E+10 | 5346.81 | 26-DEC-15:05 | 31.70 | 22.81 | 0.00 | 0.00 | 01-DEC-00:10 | 31.70 | 22.81 |
Annual Sum or Average | 0.565995E+11 | 0.00 | ||||||||
Minimum of Months | 0.434324E+10 | 5169.28 | 23.85 | 22.81 | 0.00 | 0.00 | 23.85 | 22.81 | ||
Maximum of Months | 0.538625E+10 | 5913.44 | 34.30 | 27.94 | 0.00 | 0.00 | 34.30 | 27.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204485E+11 | 30333.86 | 10-JAN-05:02 | 23.95 | 22.91 | 0.199202E+10 | 2606.60 | 02-JAN-14:20 | 23.95 | 22.91 |
February | 0.188219E+11 | 33645.52 | 21-FEB-05:04 | 25.00 | 21.63 | 0.180655E+10 | 2606.60 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.218042E+11 | 30505.80 | 07-MAR-05:02 | 24.00 | 22.62 | 0.215698E+10 | 2606.60 | 03-MAR-10:20 | 24.00 | 22.62 |
April | 0.206229E+11 | 29867.54 | 10-APR-04:03 | 25.17 | 23.75 | 0.191479E+10 | 2606.60 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.219283E+11 | 33471.47 | 22-MAY-04:04 | 27.00 | 26.56 | 0.207441E+10 | 2606.60 | 30-MAY-13:20 | 31.73 | 26.90 |
June | 0.217223E+11 | 30222.78 | 01-JUN-04:02 | 24.17 | 24.06 | 0.206821E+10 | 2606.60 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.203250E+11 | 30530.99 | 18-JUL-04:22 | 24.00 | 23.32 | 0.192132E+10 | 2606.60 | 03-JUL-13:20 | 24.00 | 23.32 |
August | 0.210209E+11 | 30343.47 | 21-AUG-04:03 | 24.17 | 23.75 | 0.215690E+10 | 2606.60 | 17-AUG-13:20 | 24.17 | 23.75 |
September | 0.197169E+11 | 32289.92 | 19-SEP-05:03 | 24.00 | 24.00 | 0.191454E+10 | 2606.60 | 14-SEP-13:20 | 24.00 | 24.00 |
October | 0.200337E+11 | 33890.02 | 10-OCT-04:04 | 24.00 | 23.63 | 0.199136E+10 | 2606.60 | 30-OCT-13:20 | 24.33 | 24.25 |
November | 0.195702E+11 | 32659.08 | 13-NOV-05:04 | 25.00 | 24.24 | 0.197203E+10 | 2606.60 | 16-NOV-14:20 | 29.70 | 25.44 |
December | 0.193203E+11 | 29346.19 | 05-DEC-06:12 | 22.33 | 22.02 | 0.192125E+10 | 2606.60 | 11-DEC-14:20 | 30.00 | 25.50 |
Annual Sum or Average | 0.245335E+12 | 0.238904E+11 | ||||||||
Minimum of Months | 0.188219E+11 | 29346.19 | 22.33 | 21.63 | 0.180655E+10 | 2606.60 | 23.53 | 20.42 | ||
Maximum of Months | 0.219283E+11 | 33890.02 | 27.00 | 26.56 | 0.215698E+10 | 2606.60 | 34.13 | 26.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210221E+11 | 32699.67 | 09-JAN-05:03 | 23.92 | 23.24 | 0.199130E+10 | 2606.64 | 24-JAN-10:20 | 22.27 | 18.67 |
February | 0.196506E+11 | 35876.66 | 06-FEB-06:03 | 23.95 | 22.59 | 0.180639E+10 | 2606.59 | 07-FEB-14:20 | 31.33 | 25.85 |
March | 0.232485E+11 | 32538.32 | 06-MAR-05:03 | 24.00 | 21.84 | 0.215734E+10 | 2606.60 | 03-MAR-10:20 | 24.00 | 21.84 |
April | 0.223215E+11 | 32781.55 | 10-APR-04:03 | 25.17 | 23.75 | 0.191597E+10 | 2606.60 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.235106E+11 | 32975.16 | 09-MAY-04:02 | 24.17 | 24.17 | 0.207514E+10 | 2606.59 | 25-MAY-13:20 | 30.73 | 27.73 |
June | 0.233363E+11 | 32729.78 | 26-JUN-04:03 | 24.00 | 23.59 | 0.206904E+10 | 2606.60 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.214499E+11 | 32633.11 | 06-JUL-04:02 | 25.17 | 23.75 | 0.192224E+10 | 2606.59 | 03-JUL-13:20 | 25.17 | 23.75 |
August | 0.220917E+11 | 32279.80 | 07-AUG-04:02 | 24.92 | 23.94 | 0.215692E+10 | 2606.59 | 17-AUG-13:20 | 27.40 | 25.59 |
September | 0.208670E+11 | 32367.16 | 26-SEP-04:02 | 26.00 | 25.44 | 0.191515E+10 | 2606.60 | 14-SEP-13:20 | 26.00 | 25.44 |
October | 0.207749E+11 | 33072.31 | 10-OCT-04:02 | 24.00 | 23.63 | 0.199169E+10 | 2606.60 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.202770E+11 | 32629.64 | 20-NOV-05:03 | 24.00 | 22.62 | 0.197153E+10 | 2606.60 | 16-NOV-14:20 | 24.00 | 22.62 |
December | 0.198549E+11 | 31499.59 | 18-DEC-06:12 | 23.13 | 23.13 | 0.191954E+10 | 2606.61 | 21-DEC-10:20 | 26.33 | 20.63 |
Annual Sum or Average | 0.258405E+12 | 0.238922E+11 | ||||||||
Minimum of Months | 0.196506E+11 | 31499.59 | 23.13 | 21.84 | 0.180639E+10 | 2606.59 | 22.27 | 18.67 | ||
Maximum of Months | 0.235106E+11 | 35876.66 | 26.00 | 25.44 | 0.215734E+10 | 2606.64 | 34.13 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.612847E+10 | 9431.31 | 02-JAN-06:12 | 23.37 | 23.04 | 0.420065E+09 | 549.50 | 24-JAN-10:20 | 22.27 | 18.67 |
February | 0.593880E+10 | 11846.50 | 19-FEB-15:52 | 31.50 | 24.19 | 0.381345E+09 | 549.49 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.730446E+10 | 11861.58 | 26-MAR-12:43 | 34.42 | 25.47 | 0.455402E+09 | 549.49 | 03-MAR-10:20 | 34.42 | 25.47 |
April | 0.733284E+10 | 11921.83 | 30-APR-12:43 | 33.50 | 26.85 | 0.404869E+09 | 549.49 | 20-APR-13:20 | 33.50 | 26.85 |
May | 0.841403E+10 | 12214.49 | 14-MAY-13:02 | 34.50 | 26.67 | 0.438601E+09 | 549.49 | 30-MAY-13:20 | 31.73 | 26.90 |
June | 0.906011E+10 | 12445.95 | 18-JUN-10:32 | 32.83 | 27.25 | 0.437241E+09 | 549.49 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.751296E+10 | 12137.64 | 04-JUL-13:43 | 32.12 | 24.90 | 0.406334E+09 | 549.49 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.725871E+10 | 11835.52 | 27-AUG-12:53 | 33.10 | 26.13 | 0.455448E+09 | 549.49 | 17-AUG-13:20 | 33.10 | 26.13 |
September | 0.652993E+10 | 11834.15 | 04-SEP-12:02 | 32.08 | 27.48 | 0.404531E+09 | 549.49 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.618581E+10 | 11855.12 | 09-OCT-12:43 | 29.83 | 26.26 | 0.420634E+09 | 549.49 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.596951E+10 | 10637.61 | 05-NOV-14:32 | 30.67 | 24.44 | 0.416289E+09 | 549.49 | 08-NOV-14:20 | 30.50 | 25.79 |
December | 0.572301E+10 | 10506.66 | 31-DEC-16:12 | 30.60 | 24.09 | 0.404997E+09 | 549.49 | 21-DEC-10:20 | 30.60 | 24.09 |
Annual Sum or Average | 0.833587E+11 | 0.504576E+10 | ||||||||
Minimum of Months | 0.572301E+10 | 9431.31 | 23.37 | 23.04 | 0.381345E+09 | 549.49 | 22.27 | 18.67 | ||
Maximum of Months | 0.906011E+10 | 12445.95 | 34.50 | 27.48 | 0.455448E+09 | 549.50 | 34.42 | 26.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496361E+10 | 10969.21 | 16-JAN-10:13 | 28.43 | 21.42 | 0.266531E+09 | 347.88 | 24-JAN-10:20 | 22.27 | 18.67 |
February | 0.493995E+10 | 10426.24 | 19-FEB-15:52 | 31.50 | 24.19 | 0.241875E+09 | 347.87 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.615463E+10 | 11230.69 | 05-MAR-09:23 | 28.75 | 22.64 | 0.288629E+09 | 347.87 | 03-MAR-10:20 | 28.75 | 22.64 |
April | 0.605149E+10 | 11240.22 | 02-APR-08:53 | 29.00 | 25.22 | 0.256591E+09 | 347.87 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.595993E+10 | 11131.07 | 07-MAY-07:53 | 31.00 | 27.23 | 0.277787E+09 | 347.87 | 30-MAY-09:20 | 31.80 | 27.48 |
June | 0.611241E+10 | 11481.08 | 18-JUN-10:32 | 32.83 | 27.25 | 0.276842E+09 | 347.87 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.512360E+10 | 11051.03 | 30-JUL-10:02 | 29.67 | 24.39 | 0.257315E+09 | 347.87 | 26-JUL-09:20 | 29.67 | 24.39 |
August | 0.547916E+10 | 10813.87 | 27-AUG-12:13 | 33.03 | 27.19 | 0.288505E+09 | 347.87 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.510375E+10 | 11169.83 | 04-SEP-08:43 | 29.67 | 26.75 | 0.256407E+09 | 347.87 | 14-SEP-09:20 | 30.27 | 26.50 |
October | 0.481055E+10 | 11219.58 | 08-OCT-09:23 | 30.00 | 26.31 | 0.266564E+09 | 347.87 | 11-OCT-09:20 | 28.87 | 25.72 |
November | 0.462390E+10 | 9918.03 | 05-NOV-11:13 | 30.67 | 23.05 | 0.263956E+09 | 347.87 | 13-NOV-10:20 | 26.97 | 24.85 |
December | 0.456808E+10 | 10524.23 | 31-DEC-10:53 | 31.00 | 25.04 | 0.257113E+09 | 347.87 | 29-DEC-10:20 | 31.00 | 25.04 |
Annual Sum or Average | 0.638911E+11 | 0.319811E+10 | ||||||||
Minimum of Months | 0.456808E+10 | 9918.03 | 28.43 | 21.42 | 0.241875E+09 | 347.87 | 22.27 | 18.67 | ||
Maximum of Months | 0.615463E+10 | 11481.08 | 33.03 | 27.25 | 0.288629E+09 | 347.88 | 34.13 | 27.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897218E+10 | 12438.15 | 08-JAN-12:13 | 31.40 | 23.67 | 0.423480E+09 | 585.65 | 04-JAN-14:09 | 31.40 | 23.67 |
February | 0.803332E+10 | 12258.91 | 26-FEB-12:13 | 32.83 | 24.74 | 0.383125E+09 | 582.60 | 21-FEB-14:20 | 32.83 | 24.74 |
March | 0.837455E+10 | 12049.91 | 26-MAR-12:43 | 34.42 | 25.47 | 0.455627E+09 | 549.49 | 03-MAR-10:20 | 34.42 | 25.47 |
April | 0.721275E+10 | 11662.04 | 02-APR-12:53 | 33.90 | 26.03 | 0.404825E+09 | 549.49 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.758918E+10 | 11554.15 | 14-MAY-13:02 | 34.50 | 26.67 | 0.438353E+09 | 549.49 | 30-MAY-13:20 | 31.73 | 26.90 |
June | 0.751235E+10 | 11531.96 | 18-JUN-10:32 | 32.83 | 27.25 | 0.436923E+09 | 549.49 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.663247E+10 | 11550.76 | 09-JUL-14:43 | 31.92 | 25.35 | 0.406076E+09 | 549.49 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.685391E+10 | 11425.44 | 27-AUG-12:53 | 33.10 | 26.13 | 0.455316E+09 | 549.49 | 17-AUG-13:20 | 33.10 | 26.13 |
September | 0.682233E+10 | 11661.16 | 04-SEP-12:02 | 32.08 | 27.48 | 0.404601E+09 | 549.49 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.726436E+10 | 12159.27 | 29-OCT-11:02 | 31.50 | 26.00 | 0.420944E+09 | 549.49 | 13-OCT-13:20 | 31.50 | 26.00 |
November | 0.789160E+10 | 12377.02 | 23-NOV-11:43 | 30.88 | 24.99 | 0.417096E+09 | 556.18 | 20-NOV-14:09 | 30.88 | 24.99 |
December | 0.849586E+10 | 12434.13 | 31-DEC-16:12 | 30.60 | 24.09 | 0.408942E+09 | 590.61 | 26-DEC-14:09 | 30.60 | 24.09 |
Annual Sum or Average | 0.916549E+11 | 0.505531E+10 | ||||||||
Minimum of Months | 0.663247E+10 | 11425.44 | 30.60 | 23.67 | 0.383125E+09 | 549.49 | 26.00 | 23.67 | ||
Maximum of Months | 0.897218E+10 | 12438.15 | 34.50 | 27.48 | 0.455627E+09 | 590.61 | 34.42 | 26.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499031E+10 | 12780.29 | 16-JAN-16:12 | 30.53 | 22.11 | 0.266213E+09 | 347.85 | 24-JAN-10:20 | 22.27 | 18.67 |
February | 0.490848E+10 | 13023.84 | 19-FEB-15:52 | 31.50 | 24.19 | 0.241641E+09 | 347.85 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.614870E+10 | 13252.06 | 19-MAR-15:32 | 34.80 | 24.95 | 0.288542E+09 | 347.85 | 03-MAR-10:20 | 34.80 | 24.95 |
April | 0.594126E+10 | 13152.35 | 02-APR-16:12 | 33.00 | 27.09 | 0.256511E+09 | 347.84 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.583602E+10 | 12726.74 | 14-MAY-15:42 | 34.83 | 27.45 | 0.277683E+09 | 347.84 | 30-MAY-09:20 | 31.80 | 27.48 |
June | 0.595171E+10 | 13039.86 | 25-JUN-16:32 | 30.40 | 27.67 | 0.276784E+09 | 347.85 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.501880E+10 | 12770.37 | 04-JUL-16:22 | 30.50 | 25.28 | 0.257255E+09 | 347.84 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.532301E+10 | 12775.00 | 27-AUG-16:12 | 32.67 | 25.94 | 0.288430E+09 | 347.84 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.496836E+10 | 12988.42 | 04-SEP-16:42 | 32.17 | 26.80 | 0.256282E+09 | 347.84 | 07-SEP-09:20 | 29.40 | 26.98 |
October | 0.473218E+10 | 13008.69 | 15-OCT-15:52 | 29.40 | 25.43 | 0.266473E+09 | 347.85 | 13-OCT-13:20 | 29.40 | 25.43 |
November | 0.460304E+10 | 11744.82 | 19-NOV-15:02 | 31.27 | 25.08 | 0.263745E+09 | 347.85 | 08-NOV-14:20 | 31.27 | 25.08 |
December | 0.459378E+10 | 13083.80 | 31-DEC-16:12 | 30.60 | 24.09 | 0.256668E+09 | 347.84 | 21-DEC-10:20 | 30.60 | 24.09 |
Annual Sum or Average | 0.630157E+11 | 0.319623E+10 | ||||||||
Minimum of Months | 0.459378E+10 | 11744.82 | 29.40 | 22.11 | 0.241641E+09 | 347.84 | 22.27 | 18.67 | ||
Maximum of Months | 0.614870E+10 | 13252.06 | 34.83 | 27.67 | 0.288542E+09 | 347.85 | 34.80 | 27.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622485E+10 | 7740.53 | 02-JAN-07:03 | 23.85 | 23.26 | 0.420378E+09 | 549.49 | 31-JAN-10:20 | 25.33 | 21.80 |
February | 0.592896E+10 | 10026.34 | 20-FEB-16:32 | 31.03 | 23.92 | 0.381498E+09 | 549.49 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.708309E+10 | 8208.71 | 28-MAR-04:02 | 27.25 | 25.19 | 0.455386E+09 | 549.49 | 03-MAR-10:20 | 27.25 | 25.19 |
April | 0.708847E+10 | 8448.67 | 20-APR-04:02 | 26.83 | 25.14 | 0.404756E+09 | 549.49 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.841905E+10 | 10426.66 | 28-MAY-10:32 | 32.80 | 27.22 | 0.438689E+09 | 549.93 | 30-MAY-13:09 | 32.67 | 26.86 |
June | 0.910596E+10 | 10603.43 | 18-JUN-10:32 | 32.83 | 27.25 | 0.437741E+09 | 561.56 | 12-JUN-13:00 | 32.83 | 27.25 |
July | 0.779441E+10 | 10440.40 | 04-JUL-17:22 | 28.40 | 25.05 | 0.406557E+09 | 549.49 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.755052E+10 | 10249.04 | 27-AUG-16:42 | 32.17 | 26.59 | 0.455730E+09 | 549.49 | 17-AUG-13:20 | 32.17 | 26.59 |
September | 0.672612E+10 | 10298.50 | 04-SEP-16:31 | 32.33 | 26.80 | 0.404653E+09 | 549.49 | 18-SEP-09:20 | 24.30 | 24.14 |
October | 0.633522E+10 | 8245.69 | 16-OCT-04:02 | 26.00 | 25.22 | 0.420694E+09 | 549.49 | 11-OCT-09:20 | 26.00 | 25.22 |
November | 0.614960E+10 | 7824.55 | 13-NOV-07:03 | 26.08 | 24.64 | 0.416451E+09 | 549.49 | 08-NOV-14:20 | 26.08 | 24.64 |
December | 0.586656E+10 | 7760.18 | 11-DEC-07:03 | 24.58 | 23.72 | 0.405591E+09 | 549.49 | 04-DEC-10:20 | 24.58 | 23.72 |
Annual Sum or Average | 0.842728E+11 | 0.504812E+10 | ||||||||
Minimum of Months | 0.586656E+10 | 7740.53 | 23.85 | 23.26 | 0.381498E+09 | 549.49 | 23.53 | 20.42 | ||
Maximum of Months | 0.910596E+10 | 10603.43 | 32.83 | 27.25 | 0.455730E+09 | 561.56 | 33.70 | 27.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511272E+10 | 9933.29 | 16-JAN-11:22 | 29.90 | 21.44 | 0.266679E+09 | 347.87 | 17-JAN-10:20 | 27.47 | 22.36 |
February | 0.504838E+10 | 10340.92 | 20-FEB-09:52 | 29.40 | 22.77 | 0.242009E+09 | 347.87 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.610090E+10 | 10027.15 | 05-MAR-09:13 | 28.50 | 22.57 | 0.288754E+09 | 347.87 | 03-MAR-10:20 | 28.50 | 22.57 |
April | 0.594153E+10 | 10028.71 | 02-APR-08:53 | 29.00 | 25.22 | 0.256640E+09 | 347.87 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.601398E+10 | 10359.05 | 28-MAY-09:12 | 31.47 | 27.83 | 0.277856E+09 | 347.87 | 30-MAY-09:20 | 31.80 | 27.48 |
June | 0.615846E+10 | 10277.03 | 18-JUN-10:32 | 32.83 | 27.25 | 0.276931E+09 | 347.87 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.531904E+10 | 9687.13 | 30-JUL-10:32 | 30.17 | 24.41 | 0.257464E+09 | 347.87 | 26-JUL-09:20 | 30.17 | 24.41 |
August | 0.572219E+10 | 10365.44 | 27-AUG-10:02 | 31.58 | 26.86 | 0.288710E+09 | 347.87 | 16-AUG-09:20 | 31.58 | 26.86 |
September | 0.530188E+10 | 10367.59 | 04-SEP-09:52 | 30.20 | 27.28 | 0.256540E+09 | 347.87 | 14-SEP-09:20 | 30.27 | 26.50 |
October | 0.493192E+10 | 8257.47 | 29-OCT-11:02 | 31.50 | 26.00 | 0.266692E+09 | 347.87 | 11-OCT-09:20 | 31.50 | 26.00 |
November | 0.482341E+10 | 9148.31 | 05-NOV-09:43 | 28.67 | 24.05 | 0.264104E+09 | 347.87 | 13-NOV-10:20 | 26.97 | 24.85 |
December | 0.475056E+10 | 9819.25 | 31-DEC-11:22 | 31.00 | 24.77 | 0.257349E+09 | 347.87 | 29-DEC-10:20 | 31.00 | 24.77 |
Annual Sum or Average | 0.652250E+11 | 0.319973E+10 | ||||||||
Minimum of Months | 0.475056E+10 | 8257.47 | 28.50 | 21.44 | 0.242009E+09 | 347.87 | 23.53 | 20.42 | ||
Maximum of Months | 0.615846E+10 | 10367.59 | 32.83 | 27.83 | 0.288754E+09 | 347.87 | 34.13 | 27.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100042E+11 | 11138.47 | 16-JAN-12:42 | 30.72 | 22.01 | 0.443723E+09 | 747.52 | 04-JAN-13:09 | 30.72 | 22.01 |
February | 0.904173E+10 | 10842.26 | 21-FEB-13:00 | 34.10 | 22.08 | 0.403762E+09 | 741.05 | 21-FEB-13:09 | 34.25 | 22.07 |
March | 0.994334E+10 | 10731.82 | 21-MAR-12:00 | 35.00 | 23.21 | 0.470612E+09 | 730.53 | 21-MAR-12:09 | 35.23 | 23.19 |
April | 0.880946E+10 | 10249.00 | 18-APR-12:00 | 34.00 | 26.52 | 0.412499E+09 | 687.39 | 18-APR-12:09 | 34.03 | 26.51 |
May | 0.944832E+10 | 11107.01 | 05-MAY-12:00 | 37.00 | 25.95 | 0.447718E+09 | 757.59 | 05-MAY-12:09 | 36.90 | 26.19 |
June | 0.945214E+10 | 10616.32 | 16-JUN-12:00 | 35.00 | 28.16 | 0.446644E+09 | 713.86 | 16-JUN-12:09 | 35.17 | 28.24 |
July | 0.812020E+10 | 9756.55 | 26-JUL-17:00 | 33.00 | 26.23 | 0.410087E+09 | 632.48 | 27-JUL-12:09 | 31.48 | 25.75 |
August | 0.878502E+10 | 10258.51 | 15-AUG-12:00 | 33.70 | 27.96 | 0.461038E+09 | 685.38 | 15-AUG-12:09 | 33.32 | 27.86 |
September | 0.839094E+10 | 10109.59 | 05-SEP-12:00 | 33.00 | 26.98 | 0.410699E+09 | 675.56 | 05-SEP-12:09 | 33.02 | 26.93 |
October | 0.862473E+10 | 10358.37 | 29-OCT-11:02 | 31.50 | 26.00 | 0.427620E+09 | 673.88 | 04-OCT-12:09 | 31.50 | 26.00 |
November | 0.924702E+10 | 10727.21 | 19-NOV-12:12 | 32.40 | 24.63 | 0.430886E+09 | 678.64 | 22-NOV-13:09 | 31.50 | 24.57 |
December | 0.948811E+10 | 10859.90 | 31-DEC-12:02 | 31.17 | 24.59 | 0.426148E+09 | 715.87 | 26-DEC-13:09 | 31.17 | 24.59 |
Annual Sum or Average | 0.109355E+12 | 0.519144E+10 | ||||||||
Minimum of Months | 0.812020E+10 | 9756.55 | 30.72 | 22.01 | 0.403762E+09 | 632.48 | 30.72 | 22.01 | ||
Maximum of Months | 0.100042E+11 | 11138.47 | 37.00 | 28.16 | 0.470612E+09 | 757.59 | 36.90 | 28.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509023E+10 | 11484.62 | 16-JAN-16:42 | 29.38 | 22.09 | 0.266557E+09 | 347.85 | 31-JAN-10:20 | 25.33 | 21.80 |
February | 0.497001E+10 | 11292.55 | 20-FEB-16:32 | 31.03 | 23.92 | 0.241882E+09 | 347.85 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.606535E+10 | 11300.87 | 05-MAR-15:52 | 30.20 | 24.33 | 0.288721E+09 | 347.85 | 03-MAR-10:20 | 30.20 | 24.33 |
April | 0.581468E+10 | 11014.15 | 02-APR-16:12 | 33.00 | 27.09 | 0.256605E+09 | 347.85 | 24-APR-09:20 | 30.43 | 25.56 |
May | 0.587211E+10 | 10857.74 | 14-MAY-16:11 | 33.87 | 27.36 | 0.277804E+09 | 347.85 | 30-MAY-09:20 | 31.80 | 27.48 |
June | 0.601329E+10 | 10948.17 | 25-JUN-16:22 | 30.60 | 27.65 | 0.276910E+09 | 347.85 | 05-JUN-09:20 | 30.60 | 27.65 |
July | 0.521838E+10 | 11237.67 | 04-JUL-17:22 | 28.40 | 25.05 | 0.257446E+09 | 347.85 | 11-JUL-09:20 | 26.00 | 24.56 |
August | 0.556055E+10 | 11310.89 | 27-AUG-16:42 | 32.17 | 26.59 | 0.288686E+09 | 347.85 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.515449E+10 | 11729.13 | 04-SEP-16:31 | 32.33 | 26.80 | 0.256456E+09 | 347.85 | 18-SEP-09:20 | 24.30 | 24.14 |
October | 0.485848E+10 | 10779.99 | 15-OCT-16:12 | 29.10 | 25.57 | 0.266645E+09 | 347.85 | 11-OCT-09:20 | 29.10 | 25.57 |
November | 0.477068E+10 | 11007.42 | 19-NOV-16:12 | 29.90 | 25.62 | 0.263976E+09 | 347.85 | 13-NOV-10:20 | 29.90 | 25.62 |
December | 0.472299E+10 | 10995.38 | 31-DEC-16:02 | 31.00 | 24.10 | 0.257177E+09 | 347.85 | 26-DEC-10:20 | 31.00 | 24.10 |
Annual Sum or Average | 0.641112E+11 | 0.319886E+10 | ||||||||
Minimum of Months | 0.472299E+10 | 10779.99 | 28.40 | 22.09 | 0.241882E+09 | 347.85 | 23.53 | 20.42 | ||
Maximum of Months | 0.606535E+10 | 11729.13 | 33.87 | 27.65 | 0.288721E+09 | 347.85 | 31.80 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591118E+10 | 7782.45 | 02-JAN-07:03 | 23.85 | 23.26 | 0.420290E+09 | 549.49 | 09-JAN-14:20 | 30.73 | 24.38 |
February | 0.566376E+10 | 10184.12 | 20-FEB-16:32 | 31.03 | 23.92 | 0.381463E+09 | 549.49 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.684485E+10 | 9422.84 | 19-MAR-15:32 | 34.80 | 24.95 | 0.455399E+09 | 549.49 | 03-MAR-10:20 | 34.80 | 24.95 |
April | 0.678996E+10 | 9771.40 | 30-APR-17:22 | 31.00 | 26.90 | 0.404747E+09 | 549.49 | 20-APR-13:20 | 31.00 | 26.90 |
May | 0.787880E+10 | 10493.45 | 28-MAY-10:32 | 32.80 | 27.22 | 0.438577E+09 | 549.49 | 30-MAY-13:20 | 31.73 | 26.90 |
June | 0.847245E+10 | 10671.78 | 18-JUN-10:32 | 32.83 | 27.25 | 0.437258E+09 | 551.23 | 12-JUN-13:00 | 32.83 | 27.25 |
July | 0.708117E+10 | 10623.11 | 04-JUL-16:52 | 29.50 | 25.20 | 0.406310E+09 | 549.49 | 17-JUL-09:20 | 27.50 | 24.44 |
August | 0.689642E+10 | 10277.34 | 27-AUG-16:42 | 32.17 | 26.59 | 0.455495E+09 | 549.49 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.616992E+10 | 10329.67 | 04-SEP-16:31 | 32.33 | 26.80 | 0.404497E+09 | 549.49 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.592014E+10 | 9408.30 | 09-OCT-12:43 | 29.83 | 26.26 | 0.420643E+09 | 549.49 | 13-OCT-13:20 | 31.60 | 26.55 |
November | 0.574130E+10 | 8548.73 | 13-NOV-05:02 | 25.00 | 24.24 | 0.416384E+09 | 549.49 | 08-NOV-14:20 | 25.00 | 24.24 |
December | 0.551817E+10 | 8162.93 | 11-DEC-06:12 | 23.43 | 23.19 | 0.405407E+09 | 549.49 | 04-DEC-14:20 | 23.43 | 23.19 |
Annual Sum or Average | 0.788881E+11 | 0.504647E+10 | ||||||||
Minimum of Months | 0.551817E+10 | 7782.45 | 23.43 | 23.19 | 0.381463E+09 | 549.49 | 23.43 | 20.42 | ||
Maximum of Months | 0.847245E+10 | 10671.78 | 34.80 | 27.25 | 0.455495E+09 | 551.23 | 34.80 | 27.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460698E+10 | 10525.45 | 16-JAN-11:22 | 29.90 | 21.44 | 0.198213E+09 | 356.45 | 17-JAN-11:09 | 29.33 | 22.62 |
February | 0.457847E+10 | 11063.28 | 20-FEB-09:52 | 29.40 | 22.77 | 0.179825E+09 | 356.45 | 22-FEB-11:09 | 31.17 | 22.09 |
March | 0.560123E+10 | 10745.69 | 05-MAR-09:13 | 28.50 | 22.57 | 0.214023E+09 | 356.45 | 03-MAR-11:09 | 28.50 | 22.57 |
April | 0.545220E+10 | 10744.21 | 23-APR-09:02 | 27.78 | 23.87 | 0.190666E+09 | 356.45 | 20-APR-14:09 | 27.78 | 23.87 |
May | 0.541136E+10 | 11074.78 | 28-MAY-09:12 | 31.47 | 27.83 | 0.206273E+09 | 356.45 | 30-MAY-10:09 | 33.33 | 27.85 |
June | 0.553289E+10 | 10872.55 | 18-JUN-10:32 | 32.83 | 27.25 | 0.205321E+09 | 356.45 | 30-JUN-10:09 | 31.00 | 27.90 |
July | 0.465297E+10 | 10298.76 | 30-JUL-09:53 | 29.50 | 24.38 | 0.191419E+09 | 356.45 | 17-JUL-14:09 | 29.50 | 24.38 |
August | 0.501698E+10 | 11079.11 | 27-AUG-09:22 | 31.15 | 27.70 | 0.213900E+09 | 356.45 | 28-AUG-10:09 | 31.08 | 26.90 |
September | 0.465982E+10 | 10987.25 | 04-SEP-09:52 | 30.20 | 27.28 | 0.190512E+09 | 356.45 | 06-SEP-10:09 | 31.25 | 27.63 |
October | 0.440628E+10 | 10716.60 | 08-OCT-09:13 | 29.83 | 26.26 | 0.198213E+09 | 356.45 | 11-OCT-10:09 | 29.67 | 26.13 |
November | 0.428212E+10 | 10174.35 | 05-NOV-09:43 | 28.67 | 24.05 | 0.196301E+09 | 356.45 | 13-NOV-11:09 | 29.60 | 25.38 |
December | 0.423332E+10 | 10431.92 | 31-DEC-11:22 | 31.00 | 24.77 | 0.191331E+09 | 356.45 | 26-DEC-11:09 | 31.00 | 24.77 |
Annual Sum or Average | 0.584346E+11 | 0.237600E+10 | ||||||||
Minimum of Months | 0.423332E+10 | 10174.35 | 27.78 | 21.44 | 0.179825E+09 | 356.45 | 27.78 | 22.09 | ||
Maximum of Months | 0.560123E+10 | 11079.11 | 32.83 | 27.83 | 0.214023E+09 | 356.45 | 33.33 | 27.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854512E+10 | 11293.95 | 16-JAN-12:42 | 30.72 | 22.01 | 0.427004E+09 | 602.48 | 17-JAN-14:20 | 30.90 | 22.68 |
February | 0.763806E+10 | 10838.95 | 20-FEB-11:52 | 31.50 | 24.01 | 0.385438E+09 | 597.22 | 21-FEB-14:20 | 34.67 | 21.94 |
March | 0.785836E+10 | 10245.92 | 26-MAR-12:43 | 34.42 | 25.47 | 0.455674E+09 | 551.99 | 20-MAR-13:20 | 34.42 | 25.47 |
April | 0.668389E+10 | 9847.97 | 02-APR-12:53 | 33.90 | 26.03 | 0.404691E+09 | 549.49 | 20-APR-13:20 | 33.70 | 26.45 |
May | 0.710092E+10 | 9810.82 | 14-MAY-14:51 | 35.00 | 26.75 | 0.438293E+09 | 549.49 | 30-MAY-13:20 | 31.73 | 26.90 |
June | 0.701605E+10 | 9222.26 | 11-JUN-15:52 | 34.50 | 28.11 | 0.436843E+09 | 549.49 | 28-JUN-13:20 | 34.13 | 26.89 |
July | 0.626092E+10 | 9182.17 | 09-JUL-14:43 | 31.92 | 25.35 | 0.406002E+09 | 549.49 | 31-JUL-09:20 | 27.70 | 24.62 |
August | 0.651744E+10 | 9783.90 | 27-AUG-16:42 | 32.17 | 26.59 | 0.455353E+09 | 549.49 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.644796E+10 | 10073.16 | 04-SEP-16:31 | 32.33 | 26.80 | 0.404573E+09 | 549.49 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.693409E+10 | 10485.27 | 29-OCT-11:02 | 31.50 | 26.00 | 0.420990E+09 | 551.93 | 10-OCT-13:20 | 31.50 | 26.00 |
November | 0.757530E+10 | 10873.83 | 19-NOV-12:12 | 32.40 | 24.63 | 0.418508E+09 | 570.85 | 20-NOV-14:20 | 31.00 | 24.73 |
December | 0.810873E+10 | 11047.98 | 03-DEC-12:22 | 31.25 | 24.81 | 0.412318E+09 | 606.47 | 26-DEC-14:09 | 31.17 | 22.67 |
Annual Sum or Average | 0.866869E+11 | 0.506569E+10 | ||||||||
Minimum of Months | 0.626092E+10 | 9182.17 | 30.72 | 22.01 | 0.385438E+09 | 549.49 | 27.70 | 21.94 | ||
Maximum of Months | 0.854512E+10 | 11293.95 | 35.00 | 28.11 | 0.455674E+09 | 606.47 | 34.67 | 27.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479703E+10 | 12272.57 | 16-JAN-16:42 | 29.38 | 22.09 | 0.266370E+09 | 347.85 | 02-JAN-10:20 | 29.38 | 22.09 |
February | 0.469913E+10 | 12077.54 | 20-FEB-16:32 | 31.03 | 23.92 | 0.241717E+09 | 347.85 | 21-FEB-10:20 | 23.53 | 20.42 |
March | 0.578054E+10 | 12118.17 | 05-MAR-15:52 | 30.20 | 24.33 | 0.288566E+09 | 347.85 | 03-MAR-10:20 | 30.20 | 24.33 |
April | 0.552301E+10 | 11850.95 | 23-APR-15:42 | 33.25 | 24.64 | 0.256469E+09 | 347.85 | 24-APR-09:20 | 30.43 | 25.56 |
May | 0.547383E+10 | 11605.22 | 14-MAY-16:11 | 33.87 | 27.36 | 0.277674E+09 | 347.85 | 30-MAY-09:20 | 31.80 | 27.48 |
June | 0.557946E+10 | 11706.04 | 25-JUN-16:22 | 30.60 | 27.65 | 0.276758E+09 | 347.85 | 05-JUN-09:20 | 30.60 | 27.65 |
July | 0.473250E+10 | 12246.89 | 04-JUL-16:52 | 29.50 | 25.20 | 0.257249E+09 | 347.85 | 31-JUL-09:20 | 27.70 | 24.62 |
August | 0.506593E+10 | 12055.34 | 27-AUG-16:42 | 32.17 | 26.59 | 0.288471E+09 | 347.85 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.470866E+10 | 12553.65 | 04-SEP-16:31 | 32.33 | 26.80 | 0.256276E+09 | 347.85 | 05-SEP-09:20 | 30.40 | 26.94 |
October | 0.451583E+10 | 11541.02 | 15-OCT-16:42 | 28.65 | 25.76 | 0.266502E+09 | 347.85 | 11-OCT-09:20 | 28.65 | 25.76 |
November | 0.443057E+10 | 11741.76 | 19-NOV-16:12 | 29.90 | 25.62 | 0.263830E+09 | 347.85 | 13-NOV-10:20 | 29.90 | 25.62 |
December | 0.441852E+10 | 11807.41 | 03-DEC-15:42 | 29.75 | 22.28 | 0.256938E+09 | 347.85 | 11-DEC-10:20 | 29.47 | 25.02 |
Annual Sum or Average | 0.597250E+11 | 0.319682E+10 | ||||||||
Minimum of Months | 0.441852E+10 | 11541.02 | 28.65 | 22.09 | 0.241717E+09 | 347.85 | 23.53 | 20.42 | ||
Maximum of Months | 0.578054E+10 | 12553.65 | 33.87 | 27.65 | 0.288566E+09 | 347.85 | 31.80 | 27.65 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20640470.08 | 3486.17 | 09-JAN-05:03 | 23.92 |
February | 18009061.14 | 4974.96 | 06-FEB-06:02 | 23.95 |
March | 16480900.17 | 3960.61 | 20-MAR-04:02 | 27.08 |
April | 16457853.53 | 3688.43 | 24-APR-04:02 | 25.00 |
May | 13776249.43 | 3585.58 | 15-MAY-04:02 | 26.33 |
June | 13117834.64 | 3740.05 | 12-JUN-04:02 | 26.33 |
July | 14920029.26 | 4158.14 | 17-JUL-04:02 | 24.42 |
August | 14455059.59 | 4012.39 | 28-AUG-04:02 | 25.33 |
September | 13955479.72 | 3953.42 | 25-SEP-04:02 | 26.00 |
October | 13665589.91 | 3895.01 | 10-OCT-04:02 | 24.00 |
November | 15382341.02 | 4318.97 | 13-NOV-05:02 | 25.00 |
December | 21472253.74 | 2718.17 | 09-DEC-06:03 | 24.15 |
Annual Sum or Average | 0.192333E+09 | |||
Minimum of Months | 13117834.64 | 2718.17 | 23.92 | |
Maximum of Months | 21472253.74 | 4974.96 | 27.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13169807.71 | 1638.31 | 09-JAN-05:03 | 23.92 |
February | 10391986.04 | 1973.19 | 26-FEB-15:21 | 34.55 |
March | 13882547.19 | 2021.37 | 28-MAR-04:02 | 27.25 |
April | 13118184.78 | 2105.71 | 12-APR-04:02 | 27.08 |
May | 12618749.92 | 2343.65 | 10-MAY-04:02 | 28.33 |
June | 11903809.91 | 2165.39 | 16-JUN-04:02 | 27.33 |
July | 9892245.05 | 1909.08 | 24-JUL-04:02 | 25.67 |
August | 10704648.90 | 2412.83 | 02-AUG-04:02 | 29.25 |
September | 10633493.30 | 2094.77 | 18-SEP-04:03 | 25.42 |
October | 11325874.45 | 1848.48 | 20-OCT-05:03 | 24.97 |
November | 12833191.49 | 1885.01 | 24-NOV-05:03 | 24.42 |
December | 13301713.14 | 1550.32 | 03-DEC-09:43 | 28.50 |
Annual Sum or Average | 0.143776E+09 | |||
Minimum of Months | 9892245.05 | 1550.32 | 23.92 | |
Maximum of Months | 13882547.19 | 2412.83 | 34.55 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26883085.18 | 3413.29 | 04-JAN-05:02 | 24.87 |
February | 21163088.77 | 3358.57 | 23-FEB-05:02 | 24.08 |
March | 22835884.69 | 3593.41 | 30-MAR-04:02 | 26.83 |
April | 24396706.19 | 3643.98 | 26-APR-04:02 | 26.98 |
May | 25810123.77 | 3824.50 | 10-MAY-04:02 | 28.33 |
June | 22504325.22 | 3766.40 | 06-JUN-04:02 | 26.83 |
July | 26677103.21 | 3608.88 | 06-JUL-04:02 | 25.17 |
August | 24494697.79 | 4063.50 | 02-AUG-04:02 | 29.25 |
September | 23130493.43 | 3754.27 | 08-SEP-04:02 | 26.75 |
October | 26087550.24 | 3519.33 | 03-OCT-04:02 | 25.58 |
November | 27605342.07 | 3569.94 | 14-NOV-05:02 | 26.00 |
December | 26000236.35 | 2923.10 | 30-DEC-05:03 | 24.00 |
Annual Sum or Average | 0.297589E+09 | |||
Minimum of Months | 21163088.77 | 2923.10 | 24.00 | |
Maximum of Months | 27605342.07 | 4063.50 | 29.25 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569745E+09 | 812.69 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.510623E+09 | 578.08 | 01-FEB-17:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.590345E+09 | 583.93 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516852E+09 | 541.10 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.557542E+09 | 549.62 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.549539E+09 | 533.99 | 20-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.517735E+09 | 539.27 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.578290E+09 | 544.73 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.526608E+09 | 544.89 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.552376E+09 | 571.67 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.567491E+09 | 861.32 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.558770E+09 | 878.50 | 18-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.659592E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.510623E+09 | 533.99 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.590345E+09 | 878.50 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.360869E+09 | 534.31 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323803E+09 | 453.84 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374154E+09 | 454.66 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328960E+09 | 339.49 | 13-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.355448E+09 | 347.47 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.351150E+09 | 336.05 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330880E+09 | 344.47 | 17-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.368082E+09 | 339.02 | 24-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334112E+09 | 347.62 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.350114E+09 | 367.39 | 30-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.361201E+09 | 561.43 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.354305E+09 | 563.95 | 18-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419308E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323803E+09 | 336.05 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374154E+09 | 563.95 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.558653E+09 | 694.87 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.505269E+09 | 578.08 | 01-FEB-17:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588791E+09 | 578.08 | 01-MAR-17:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.519721E+09 | 548.63 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.562915E+09 | 564.92 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.556343E+09 | 558.77 | 20-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.524618E+09 | 561.19 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.582575E+09 | 557.94 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526775E+09 | 545.43 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.547772E+09 | 556.20 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.556675E+09 | 799.61 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.545843E+09 | 833.71 | 18-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657595E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.505269E+09 | 545.43 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.588791E+09 | 833.71 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.354232E+09 | 365.95 | 02-JAN-17:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.319249E+09 | 365.95 | 01-FEB-17:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.371822E+09 | 365.95 | 01-MAR-17:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328116E+09 | 360.69 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.354675E+09 | 365.42 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.349823E+09 | 361.43 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330773E+09 | 363.21 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.367781E+09 | 363.71 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333572E+09 | 361.21 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.348062E+09 | 367.86 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.351896E+09 | 470.03 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.346038E+09 | 512.56 | 18-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.415604E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.319249E+09 | 360.69 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.371822E+09 | 512.56 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.568730E+09 | 803.74 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.509873E+09 | 578.08 | 01-FEB-17:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.589614E+09 | 581.24 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516316E+09 | 536.29 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.556987E+09 | 545.12 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.549086E+09 | 528.58 | 20-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.517242E+09 | 534.14 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.577639E+09 | 540.02 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525825E+09 | 540.32 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.551352E+09 | 568.44 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.566118E+09 | 854.18 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.557587E+09 | 872.20 | 18-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.658637E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.509873E+09 | 528.58 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.589614E+09 | 872.20 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.360326E+09 | 530.47 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323477E+09 | 447.58 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.373723E+09 | 448.44 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328669E+09 | 336.95 | 13-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.355105E+09 | 345.15 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.350774E+09 | 333.59 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330452E+09 | 342.04 | 17-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.367718E+09 | 336.45 | 24-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333687E+09 | 345.36 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.349578E+09 | 365.79 | 30-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.360582E+09 | 558.38 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.353619E+09 | 561.02 | 18-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418771E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323477E+09 | 333.59 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.373723E+09 | 561.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.558360E+09 | 681.52 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.504937E+09 | 578.08 | 01-FEB-17:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588057E+09 | 578.08 | 01-MAR-17:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.519016E+09 | 544.28 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.562039E+09 | 561.35 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.555473E+09 | 554.97 | 20-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.523772E+09 | 557.49 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.581545E+09 | 554.05 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526070E+09 | 540.89 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.547204E+09 | 552.06 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.556637E+09 | 794.02 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.545405E+09 | 825.45 | 18-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.656851E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.504937E+09 | 540.89 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.588057E+09 | 825.45 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353874E+09 | 365.95 | 02-JAN-17:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.319027E+09 | 365.95 | 01-FEB-17:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.371425E+09 | 365.95 | 01-MAR-17:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.327599E+09 | 358.87 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.354244E+09 | 363.75 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.349416E+09 | 359.62 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330227E+09 | 361.47 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.367359E+09 | 362.00 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333100E+09 | 359.41 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.347551E+09 | 366.29 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.351545E+09 | 462.07 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.345627E+09 | 506.85 | 18-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.415099E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.319027E+09 | 358.87 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.371425E+09 | 506.85 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569744E+09 | 812.68 | 02-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.510623E+09 | 578.08 | 01-FEB-17:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.590344E+09 | 583.92 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.516852E+09 | 541.09 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.557542E+09 | 549.61 | 17-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.549539E+09 | 533.98 | 20-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.517735E+09 | 539.25 | 11-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.578289E+09 | 544.72 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.526607E+09 | 544.88 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.552375E+09 | 571.66 | 30-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.567490E+09 | 861.30 | 27-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.558769E+09 | 878.49 | 18-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.659591E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.510623E+09 | 533.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.590344E+09 | 878.49 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.360857E+09 | 534.30 | 02-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323802E+09 | 453.83 | 07-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.374154E+09 | 454.65 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328960E+09 | 339.49 | 13-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.355448E+09 | 347.46 | 22-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.351150E+09 | 336.04 | 01-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330880E+09 | 344.46 | 17-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.368071E+09 | 339.01 | 24-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.334112E+09 | 347.61 | 22-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.350114E+09 | 367.39 | 30-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.361200E+09 | 561.42 | 27-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.354305E+09 | 563.94 | 18-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419305E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.323802E+09 | 336.04 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.374154E+09 | 563.94 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.558653E+09 | 694.85 | 02-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.505268E+09 | 578.08 | 01-FEB-17:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.588774E+09 | 578.08 | 01-MAR-17:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.519720E+09 | 548.62 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.562896E+09 | 564.91 | 17-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.556342E+09 | 558.76 | 20-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.524617E+09 | 561.18 | 11-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.582574E+09 | 557.93 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.526774E+09 | 545.42 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.547754E+09 | 556.20 | 23-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.556674E+09 | 799.59 | 09-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.545843E+09 | 833.69 | 18-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657589E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.505268E+09 | 545.42 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.588774E+09 | 833.69 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.354232E+09 | 365.95 | 02-JAN-17:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.319248E+09 | 365.95 | 01-FEB-17:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.371822E+09 | 365.95 | 01-MAR-17:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.328116E+09 | 360.69 | 21-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.354685E+09 | 365.42 | 17-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.349823E+09 | 361.43 | 20-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.330773E+09 | 363.20 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.367781E+09 | 363.70 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333572E+09 | 361.20 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.348061E+09 | 367.86 | 23-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.351896E+09 | 470.02 | 09-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.346038E+09 | 512.55 | 18-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.415605E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.319248E+09 | 360.69 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.371822E+09 | 512.55 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569745E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22728022.27 | 15164796.85 |
February | 0.901968E+09 | 0.510623E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32666850.71 | 3746641.30 |
March | 0.107774E+10 | 0.590345E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56133217.21 | 5670676.95 |
April | 0.956342E+09 | 0.516852E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56073882.21 | 1006846.17 |
May | 0.103597E+10 | 0.557542E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61348958.95 | 3089380.71 |
June | 0.103308E+10 | 0.549539E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54619746.62 | 3831123.28 |
July | 0.959235E+09 | 0.517735E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33745752.68 | 3297621.56 |
August | 0.107774E+10 | 0.578290E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41022348.10 | 6068632.83 |
September | 0.956342E+09 | 0.526608E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30800408.44 | 3724419.97 |
October | 0.994195E+09 | 0.552376E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24633080.30 | 6765784.62 |
November | 0.984487E+09 | 0.567491E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19667173.37 | 8174475.30 |
December | 0.959235E+09 | 0.558770E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18277371.77 | 15931777.94 |
Annual Sum or Average | 0.119305E+11 | 0.659592E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451717E+09 | 76472177.48 |
Minimum of Months | 0.901968E+09 | 0.510623E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18277371.77 | 1006846.17 |
Maximum of Months | 0.107774E+10 | 0.590345E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61348958.95 | 15931777.94 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.360869E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14503932.48 | 10760576.91 |
February | 0.571020E+09 | 0.323803E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20888510.57 | 2924998.99 |
March | 0.682301E+09 | 0.374154E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35885563.50 | 4269454.72 |
April | 0.605444E+09 | 0.328960E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36308726.07 | 789830.38 |
May | 0.655854E+09 | 0.355448E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40767487.25 | 2032712.65 |
June | 0.654023E+09 | 0.351150E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36867729.46 | 2468413.11 |
July | 0.607275E+09 | 0.330880E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22486205.41 | 2142041.81 |
August | 0.682301E+09 | 0.368082E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26738025.33 | 4139676.36 |
September | 0.605444E+09 | 0.334112E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19750183.29 | 2675665.14 |
October | 0.629407E+09 | 0.350114E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15764364.83 | 4778150.14 |
November | 0.623262E+09 | 0.361201E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12378616.56 | 5804049.23 |
December | 0.607275E+09 | 0.354305E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11500568.20 | 11163301.75 |
Annual Sum or Average | 0.755301E+10 | 0.419308E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293840E+09 | 53948871.19 |
Minimum of Months | 0.571020E+09 | 0.323803E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11500568.20 | 789830.38 |
Maximum of Months | 0.682301E+09 | 0.374154E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40767487.25 | 11163301.75 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.558653E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20840510.50 | 17163135.10 |
February | 0.901968E+09 | 0.505269E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30730960.53 | 4517933.15 |
March | 0.107774E+10 | 0.588791E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54636625.94 | 6275554.34 |
April | 0.956342E+09 | 0.519721E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56360313.26 | 988674.70 |
May | 0.103597E+10 | 0.562915E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62678000.74 | 2946985.81 |
June | 0.103308E+10 | 0.556343E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56749059.64 | 3510191.37 |
July | 0.959235E+09 | 0.524618E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34936280.52 | 2991790.78 |
August | 0.107774E+10 | 0.582575E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41893552.88 | 5821334.22 |
September | 0.956342E+09 | 0.526775E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30504719.40 | 3807405.62 |
October | 0.994195E+09 | 0.547772E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23538775.24 | 7338792.57 |
November | 0.984487E+09 | 0.556675E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18153052.57 | 9071286.50 |
December | 0.959235E+09 | 0.545843E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16415224.93 | 17602123.51 |
Annual Sum or Average | 0.119305E+11 | 0.657595E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447437E+09 | 82035207.67 |
Minimum of Months | 0.901968E+09 | 0.505269E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16415224.93 | 988674.70 |
Maximum of Months | 0.107774E+10 | 0.588791E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62678000.74 | 17602123.51 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.354232E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14300786.17 | 11105050.94 |
February | 0.570983E+09 | 0.319249E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20635309.13 | 3053162.58 |
March | 0.682256E+09 | 0.371822E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35160217.12 | 4883346.11 |
April | 0.605404E+09 | 0.328116E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35115384.52 | 844725.97 |
May | 0.655811E+09 | 0.354675E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40074804.52 | 2193154.51 |
June | 0.653980E+09 | 0.349823E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35924236.36 | 2669932.41 |
July | 0.607235E+09 | 0.330773E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22080281.75 | 2365093.60 |
August | 0.682256E+09 | 0.367781E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26542261.23 | 4552336.97 |
September | 0.605404E+09 | 0.333572E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19514435.17 | 2901185.21 |
October | 0.629366E+09 | 0.348062E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15678314.26 | 5096219.18 |
November | 0.623221E+09 | 0.351896E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12456103.28 | 5923014.33 |
December | 0.607235E+09 | 0.346038E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11441051.86 | 11327067.07 |
Annual Sum or Average | 0.755252E+10 | 0.415604E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288923E+09 | 56914288.87 |
Minimum of Months | 0.570983E+09 | 0.319249E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11441051.86 | 844725.97 |
Maximum of Months | 0.682256E+09 | 0.371822E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40074804.52 | 11327067.07 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.568730E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12615657.49 | 8063972.35 |
February | 0.901968E+09 | 0.509873E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17904433.37 | 2039113.90 |
March | 0.107774E+10 | 0.589614E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31149766.01 | 3041672.88 |
April | 0.956342E+09 | 0.516316E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30959346.39 | 524304.22 |
May | 0.103597E+10 | 0.556987E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33423239.86 | 1854282.95 |
June | 0.103308E+10 | 0.549086E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29310584.00 | 2192370.68 |
July | 0.959235E+09 | 0.517242E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18387093.13 | 1880652.37 |
August | 0.107774E+10 | 0.577639E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22085357.58 | 3817328.46 |
September | 0.956342E+09 | 0.525825E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16798621.86 | 2087789.76 |
October | 0.994195E+09 | 0.551352E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13746561.83 | 3334342.79 |
November | 0.984487E+09 | 0.566118E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10817646.21 | 4512431.94 |
December | 0.959235E+09 | 0.557587E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10247038.51 | 9239050.41 |
Annual Sum or Average | 0.119305E+11 | 0.658637E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247445E+09 | 42587312.70 |
Minimum of Months | 0.901968E+09 | 0.509873E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10247038.51 | 524304.22 |
Maximum of Months | 0.107774E+10 | 0.589614E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33423239.86 | 9239050.41 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.360326E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7892557.38 | 6023488.35 |
February | 0.571020E+09 | 0.323477E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11195805.36 | 1784424.94 |
March | 0.682301E+09 | 0.373723E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19227160.19 | 2664686.58 |
April | 0.605444E+09 | 0.328669E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19392326.58 | 466669.24 |
May | 0.655854E+09 | 0.355105E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21975697.34 | 1261492.62 |
June | 0.654023E+09 | 0.350774E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19737875.18 | 1446082.36 |
July | 0.607275E+09 | 0.330452E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12195665.12 | 1263733.36 |
August | 0.682301E+09 | 0.367718E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14289622.45 | 2755797.88 |
September | 0.605444E+09 | 0.333687E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10577398.38 | 1622686.25 |
October | 0.629407E+09 | 0.349578E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8552839.79 | 2588356.99 |
November | 0.623262E+09 | 0.360582E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6669704.69 | 3388429.70 |
December | 0.607275E+09 | 0.353619E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6295831.75 | 6646666.47 |
Annual Sum or Average | 0.755301E+10 | 0.418771E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158002E+09 | 31912514.75 |
Minimum of Months | 0.571020E+09 | 0.323477E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6295831.75 | 466669.24 |
Maximum of Months | 0.682301E+09 | 0.373723E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21975697.34 | 6646666.47 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.558360E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144098E+10 | 0.121482E+09 |
February | 0.901968E+09 | 0.504937E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151129E+10 | 70976903.17 |
March | 0.107774E+10 | 0.588057E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220100E+10 | 10432117.05 |
April | 0.956342E+09 | 0.519016E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215215E+10 | 814837.87 |
May | 0.103597E+10 | 0.562039E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225947E+10 | 3751047.87 |
June | 0.103308E+10 | 0.555473E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234486E+10 | 7027063.03 |
July | 0.959235E+09 | 0.523772E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143643E+10 | 5432373.04 |
August | 0.107774E+10 | 0.581545E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189504E+10 | 6575607.77 |
September | 0.956342E+09 | 0.526070E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158908E+10 | 5441512.44 |
October | 0.994195E+09 | 0.547204E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140832E+10 | 16368637.82 |
November | 0.984487E+09 | 0.556637E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142742E+10 | 24607240.33 |
December | 0.959235E+09 | 0.545405E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119959E+10 | 0.108894E+09 |
Annual Sum or Average | 0.119305E+11 | 0.656851E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208656E+11 | 0.381804E+09 |
Minimum of Months | 0.901968E+09 | 0.504937E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119959E+10 | 814837.87 |
Maximum of Months | 0.107774E+10 | 0.588057E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234486E+10 | 0.121482E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.353874E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7719910.10 | 6241190.00 |
February | 0.570983E+09 | 0.319027E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11065317.11 | 1892134.47 |
March | 0.682256E+09 | 0.371425E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18769001.98 | 3060373.65 |
April | 0.605404E+09 | 0.327599E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18691310.85 | 522055.81 |
May | 0.655811E+09 | 0.354244E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21541682.62 | 1361307.17 |
June | 0.653980E+09 | 0.349416E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19130643.55 | 1550211.99 |
July | 0.607235E+09 | 0.330227E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11944385.96 | 1388302.30 |
August | 0.682256E+09 | 0.367359E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14043486.08 | 2981911.77 |
September | 0.605404E+09 | 0.333100E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10443032.46 | 1737617.51 |
October | 0.629366E+09 | 0.347551E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8483225.51 | 2770896.20 |
November | 0.623221E+09 | 0.351545E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6671840.36 | 3467371.50 |
December | 0.607235E+09 | 0.345627E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6201937.51 | 6783302.27 |
Annual Sum or Average | 0.755252E+10 | 0.415099E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154706E+09 | 33756674.65 |
Minimum of Months | 0.570983E+09 | 0.319027E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6201937.51 | 522055.81 |
Maximum of Months | 0.682256E+09 | 0.371425E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21541682.62 | 6783302.27 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569744E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19435106.70 | 13198334.94 |
February | 0.901968E+09 | 0.510623E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27532147.92 | 3378101.75 |
March | 0.107774E+10 | 0.590344E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47700647.01 | 4970505.28 |
April | 0.956342E+09 | 0.516852E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47792872.77 | 886224.05 |
May | 0.103597E+10 | 0.557542E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51770964.13 | 2624320.08 |
June | 0.103308E+10 | 0.549539E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46265329.30 | 3191153.56 |
July | 0.959235E+09 | 0.517735E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28734622.75 | 2749780.46 |
August | 0.107774E+10 | 0.578289E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34668027.02 | 5325940.16 |
September | 0.956342E+09 | 0.526607E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26230456.36 | 3064887.35 |
October | 0.994195E+09 | 0.552375E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21210835.62 | 5686871.03 |
November | 0.984487E+09 | 0.567490E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16667254.37 | 7269837.77 |
December | 0.959235E+09 | 0.558769E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15660627.05 | 14187295.29 |
Annual Sum or Average | 0.119305E+11 | 0.659591E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383669E+09 | 66533251.71 |
Minimum of Months | 0.901968E+09 | 0.510623E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15660627.05 | 886224.05 |
Maximum of Months | 0.107774E+10 | 0.590344E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51770964.13 | 14187295.29 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.360857E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12139373.60 | 9349159.07 |
February | 0.421807E+09 | 0.323802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17305722.92 | 2644458.85 |
March | 0.502994E+09 | 0.374154E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29938106.32 | 3777171.94 |
April | 0.447140E+09 | 0.328960E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30466030.19 | 706347.07 |
May | 0.484071E+09 | 0.355448E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34002961.30 | 1747139.24 |
June | 0.482240E+09 | 0.351150E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30904046.88 | 2068815.91 |
July | 0.448971E+09 | 0.330880E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18810680.42 | 1805892.41 |
August | 0.502994E+09 | 0.368071E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22188486.51 | 3677238.55 |
September | 0.447140E+09 | 0.334112E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16441690.88 | 2238686.62 |
October | 0.465148E+09 | 0.350114E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13164209.09 | 4051273.95 |
November | 0.460569E+09 | 0.361200E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10193836.18 | 5163549.16 |
December | 0.448971E+09 | 0.354305E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9582486.75 | 9916853.05 |
Annual Sum or Average | 0.557719E+10 | 0.419305E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245138E+09 | 47146585.80 |
Minimum of Months | 0.421807E+09 | 0.323802E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9582486.75 | 706347.07 |
Maximum of Months | 0.502994E+09 | 0.374154E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34002961.30 | 9916853.05 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.558653E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17376710.46 | 14881783.22 |
February | 0.901968E+09 | 0.505268E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25694986.74 | 4063768.49 |
March | 0.107774E+10 | 0.588774E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46150619.92 | 5493154.32 |
April | 0.956342E+09 | 0.519720E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48108515.37 | 868204.25 |
May | 0.103597E+10 | 0.562896E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53128458.67 | 2504511.92 |
June | 0.103308E+10 | 0.556342E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48371113.23 | 2910402.93 |
July | 0.959235E+09 | 0.524617E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30111906.86 | 2469751.50 |
August | 0.107774E+10 | 0.582574E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35467616.66 | 5116254.24 |
September | 0.956342E+09 | 0.526774E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25941814.33 | 3129544.46 |
October | 0.994195E+09 | 0.547754E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20020027.75 | 6178217.37 |
November | 0.984487E+09 | 0.556674E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15188349.25 | 8048946.17 |
December | 0.959235E+09 | 0.545843E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13755413.66 | 15594795.18 |
Annual Sum or Average | 0.119305E+11 | 0.657589E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379316E+09 | 71259334.04 |
Minimum of Months | 0.901968E+09 | 0.505268E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13755413.66 | 868204.25 |
Maximum of Months | 0.107774E+10 | 0.588774E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53128458.67 | 15594795.18 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.354232E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12060712.65 | 9617679.92 |
February | 0.570983E+09 | 0.319248E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17332884.41 | 2731606.71 |
March | 0.682256E+09 | 0.371822E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29571663.85 | 4270173.69 |
April | 0.605404E+09 | 0.328116E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29683049.60 | 756842.56 |
May | 0.655811E+09 | 0.354685E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33716356.63 | 1848337.78 |
June | 0.653980E+09 | 0.349823E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30385811.17 | 2225191.63 |
July | 0.607235E+09 | 0.330773E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18743487.24 | 1968433.15 |
August | 0.682256E+09 | 0.367781E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22287162.45 | 3982762.96 |
September | 0.605404E+09 | 0.333572E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16492583.71 | 2406644.08 |
October | 0.629366E+09 | 0.348061E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13303538.14 | 4301550.30 |
November | 0.623221E+09 | 0.351896E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10451100.44 | 5247921.43 |
December | 0.607235E+09 | 0.346038E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9660284.02 | 10047076.60 |
Annual Sum or Average | 0.755252E+10 | 0.415605E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243689E+09 | 49404220.81 |
Minimum of Months | 0.570983E+09 | 0.319248E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9660284.02 | 756842.56 |
Maximum of Months | 0.682256E+09 | 0.371822E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33716356.63 | 10047076.60 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19444913.72 | 18096288.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29756304.63 | 4250601.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53608619.90 | 6130867.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56937644.70 | 947407.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62534551.10 | 3045749.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56249164.45 | 3631692.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33894597.89 | 2959049.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39566268.03 | 5873899.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29474024.21 | 3505604.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23034268.27 | 7000287.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17230695.88 | 9328128.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15644538.07 | 19619017.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437376E+09 | 84388594.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15644538.07 | 947407.90 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62534551.10 | 19619017.04 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25676468.48 | 22450006.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39132451.23 | 5033796.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69972402.71 | 7376985.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73917330.85 | 1125204.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80818042.34 | 3670166.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72860901.93 | 4526478.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44507607.80 | 3629178.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51979479.21 | 6655008.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38578797.25 | 4130216.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30156489.85 | 8662499.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22758861.31 | 11135725.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20770213.00 | 24029562.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571129E+09 | 0.102425E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20770213.00 | 1125204.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80818042.34 | 24029562.28 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23323363.15 | 20145933.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36661040.90 | 3333904.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68979096.81 | 5189927.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73081496.63 | 769740.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81601136.22 | 3325947.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71594481.59 | 4909260.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37535843.84 | 4105962.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50351112.50 | 6093707.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34827749.58 | 4765807.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25232960.95 | 8970523.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20194357.78 | 10056448.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17320240.28 | 21188956.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540703E+09 | 92856119.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17320240.28 | 769740.94 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81601136.22 | 21188956.78 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 812.69 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 | 15-JAN-13:00 | 204.63 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 160.51 | 19-FEB-14:52 | 23.63 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 583.93 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.84 | 19-MAR-16:00 | 41.88 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 541.10 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.10 | 30-APR-15:26 | 15.72 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 549.62 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.25 | 07-MAY-15:00 | 83.38 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 533.99 | 20-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.75 | 18-JUN-14:20 | 96.00 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 539.27 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.97 | 04-JUL-13:48 | 48.28 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 544.73 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.57 | 06-AUG-12:40 | 91.01 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 544.89 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.12 | 10-SEP-15:00 | 50.59 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 571.67 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.92 | 29-OCT-13:08 | 41.88 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 861.32 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 | 11-NOV-15:50 | 43.24 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 878.50 | 18-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 69.48 | 31-DEC-09:53 | 78.44 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 533.99 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 69.48 | 15.72 | |||||
Maximum of Months | 1306.65 | 878.50 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 282.84 | 204.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 534.31 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.65 | 15-JAN-13:00 | 136.85 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 453.84 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 | 19-FEB-14:52 | 25.06 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 454.66 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 19-MAR-15:35 | 28.58 | 05-MAR-07:20 |
April | 827.22 | 03-APR-09:09 | 339.49 | 13-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.10 | 02-APR-15:35 | 15.74 | 23-APR-07:07 |
May | 827.22 | 01-MAY-09:09 | 347.47 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.23 | 07-MAY-14:36 | 55.71 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 336.05 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 | 18-JUN-14:36 | 62.93 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 344.47 | 17-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.20 | 04-JUL-13:48 | 31.55 | 02-JUL-13:40 |
August | 827.22 | 01-AUG-09:09 | 339.02 | 24-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 06-AUG-12:40 | 64.45 | 20-AUG-11:00 |
September | 827.22 | 01-SEP-09:09 | 347.62 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.98 | 10-SEP-15:00 | 34.28 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 367.39 | 30-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.92 | 29-OCT-13:08 | 28.08 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 561.43 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 | 11-NOV-15:50 | 31.77 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 563.95 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 24-DEC-14:58 | 52.30 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 336.05 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 15.74 | |||||
Maximum of Months | 827.22 | 563.95 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 189.48 | 136.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 694.87 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.11 | 15-JAN-12:55 | 211.36 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 | 19-FEB-15:00 | 27.35 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 578.08 | 01-MAR-17:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 19-MAR-16:00 | 42.49 | 14-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 548.63 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.31 | 30-APR-15:26 | 15.48 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 564.92 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.35 | 07-MAY-14:36 | 82.39 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 558.77 | 20-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.22 | 18-JUN-14:36 | 92.89 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 561.19 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.89 | 04-JUL-13:48 | 40.58 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 557.94 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.82 | 06-AUG-12:40 | 90.23 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 545.43 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.66 | 10-SEP-15:00 | 51.14 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 556.20 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.16 | 29-OCT-13:05 | 42.74 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 799.61 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.97 | 11-NOV-15:48 | 47.58 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 833.71 | 18-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 31-DEC-12:56 | 80.08 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 545.43 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 | 15.48 | |||||
Maximum of Months | 1306.65 | 833.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 282.83 | 211.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 365.95 | 02-JAN-17:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 15-JAN-13:00 | 137.66 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 365.95 | 01-FEB-17:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.99 | 19-FEB-14:52 | 16.82 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 365.95 | 01-MAR-17:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 19-MAR-16:00 | 28.65 | 14-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 360.69 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 30-APR-15:24 | 15.14 | 09-APR-16:00 |
May | 827.17 | 01-MAY-09:09 | 365.42 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.17 | 07-MAY-15:00 | 56.33 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 361.43 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.79 | 18-JUN-13:54 | 64.67 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 363.21 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.84 | 04-JUL-13:45 | 32.78 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 363.71 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.66 | 06-AUG-12:40 | 60.51 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 361.21 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.98 | 10-SEP-15:00 | 35.30 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 367.86 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.41 | 29-OCT-13:05 | 33.02 | 29-OCT-17:00 |
November | 827.17 | 01-NOV-09:09 | 470.03 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.47 | 11-NOV-15:48 | 29.32 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 512.56 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 31-DEC-09:53 | 52.66 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 360.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 15.14 | |||||
Maximum of Months | 827.17 | 512.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 | 137.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 803.74 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 | 15-JAN-13:00 | 129.00 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.49 | 20-FEB-16:00 | 13.99 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 581.24 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.91 | 19-MAR-16:00 | 24.46 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 536.29 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.27 | 30-APR-15:28 | 9.82 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 545.12 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.76 | 07-MAY-15:00 | 49.18 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 528.58 | 20-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 18-JUN-14:20 | 53.89 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 534.14 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 | 04-JUL-14:08 | 20.32 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 540.02 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.52 | 06-AUG-12:40 | 50.89 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 540.32 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.57 | 10-SEP-15:00 | 31.41 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 568.44 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 29-OCT-13:10 | 22.14 | 22-OCT-18:00 |
November | 1306.65 | 01-NOV-09:09 | 854.18 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 | 11-NOV-16:00 | 24.71 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 872.20 | 18-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 | 24-DEC-15:00 | 46.86 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 528.58 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 | 9.82 | |||||
Maximum of Months | 1306.65 | 872.20 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 155.91 | 129.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 530.47 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.55 | 15-JAN-13:20 | 89.91 | 07-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 447.58 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 | 20-FEB-15:54 | 14.13 | 19-FEB-07:00 |
March | 827.22 | 01-MAR-10:09 | 448.44 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 19-MAR-16:00 | 17.31 | 14-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 336.95 | 13-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 02-APR-15:35 | 8.88 | 23-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 345.15 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.79 | 07-MAY-14:36 | 33.69 | 08-MAY-22:00 |
June | 827.22 | 01-JUN-09:09 | 333.59 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.25 | 18-JUN-14:36 | 35.64 | 20-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 342.04 | 17-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.53 | 04-JUL-14:08 | 13.74 | 02-JUL-13:40 |
August | 827.22 | 01-AUG-09:09 | 336.45 | 24-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.30 | 06-AUG-12:20 | 36.11 | 20-AUG-10:50 |
September | 827.22 | 01-SEP-09:09 | 345.36 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | 10-SEP-15:00 | 21.97 | 15-SEP-22:00 |
October | 827.22 | 02-OCT-09:09 | 365.79 | 30-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.01 | 29-OCT-13:08 | 15.10 | 22-OCT-18:00 |
November | 827.22 | 01-NOV-09:09 | 558.38 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.27 | 11-NOV-15:43 | 18.20 | 26-NOV-10:00 |
December | 827.22 | 01-DEC-10:09 | 561.02 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 | 24-DEC-15:00 | 31.71 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 333.59 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 | 8.88 | |||||
Maximum of Months | 827.22 | 561.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 89.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 681.52 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9148.92 | 04-JAN-12:02 | 5329.73 | 23-JAN-07:03 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8880.47 | 24-FEB-17:03 | 3479.50 | 02-FEB-07:03 |
March | 1306.65 | 01-MAR-10:09 | 578.08 | 01-MAR-17:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11086.66 | 21-MAR-11:02 | 972.63 | 15-MAR-06:03 |
April | 1306.65 | 03-APR-09:09 | 544.28 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11557.36 | 11-APR-16:02 | 198.83 | 14-APR-16:00 |
May | 1306.65 | 01-MAY-09:09 | 561.35 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13570.79 | 05-MAY-11:01 | 180.36 | 11-MAY-05:03 |
June | 1306.65 | 01-JUN-09:09 | 554.97 | 20-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12139.61 | 12-JUN-16:02 | 777.58 | 21-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 557.49 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9840.30 | 20-JUL-16:02 | 423.40 | 13-JUL-05:03 |
August | 1306.65 | 01-AUG-09:09 | 554.05 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10884.75 | 15-AUG-11:02 | 412.55 | 21-AUG-11:05 |
September | 1306.65 | 01-SEP-09:09 | 540.89 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9525.90 | 13-SEP-16:02 | 1246.95 | 15-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 552.06 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8897.96 | 04-OCT-11:02 | 1243.94 | 30-OCT-17:00 |
November | 1306.65 | 01-NOV-09:09 | 794.02 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8494.89 | 10-NOV-12:02 | 2431.09 | 27-NOV-07:03 |
December | 1306.65 | 01-DEC-10:09 | 825.45 | 18-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7544.26 | 08-DEC-12:02 | 5817.48 | 21-DEC-07:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 540.89 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 7544.26 | 180.36 | |||||
Maximum of Months | 1306.65 | 825.45 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13570.79 | 5817.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 365.95 | 02-JAN-17:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.82 | 15-JAN-12:53 | 90.33 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 365.95 | 01-FEB-17:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.31 | 20-FEB-15:54 | 10.66 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 365.95 | 01-MAR-17:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 19-MAR-16:00 | 17.24 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 358.87 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.10 | 30-APR-15:24 | 7.73 | 09-APR-16:03 |
May | 827.17 | 01-MAY-09:09 | 363.75 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.84 | 07-MAY-15:00 | 33.99 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 359.62 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.72 | 18-JUN-14:34 | 36.54 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 361.47 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.93 | 04-JUL-14:05 | 13.85 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 362.00 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.25 | 06-AUG-12:35 | 34.14 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 359.41 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | 10-SEP-15:00 | 22.55 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 366.29 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.26 | 29-OCT-13:08 | 15.43 | 22-OCT-18:00 |
November | 827.17 | 01-NOV-09:09 | 462.07 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 | 11-NOV-15:38 | 16.98 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 506.85 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 31-DEC-12:50 | 31.86 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 358.87 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 7.73 | |||||
Maximum of Months | 827.17 | 506.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 | 90.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 812.68 | 02-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.26 | 15-JAN-13:00 | 189.07 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.90 | 20-FEB-15:56 | 21.58 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 583.92 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.40 | 19-MAR-16:00 | 37.11 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 541.09 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.00 | 30-APR-15:26 | 14.44 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 549.61 | 17-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.12 | 07-MAY-15:00 | 70.27 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 533.98 | 20-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 | 18-JUN-14:20 | 78.09 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 539.25 | 11-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.02 | 04-JUL-14:16 | 33.06 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 544.72 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 | 06-AUG-12:40 | 77.70 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 544.88 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.83 | 10-SEP-15:00 | 44.58 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 571.66 | 30-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.31 | 29-OCT-13:10 | 35.62 | 23-OCT-04:55 |
November | 1306.65 | 01-NOV-09:09 | 861.30 | 27-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.59 | 11-NOV-16:00 | 37.39 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 878.49 | 18-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 | 24-DEC-15:00 | 70.05 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 533.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 60.15 | 14.44 | |||||
Maximum of Months | 1306.65 | 878.49 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 236.40 | 189.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 534.30 | 02-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 15-JAN-13:20 | 126.62 | 07-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 453.83 | 07-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.37 | 20-FEB-15:54 | 22.17 | 19-FEB-07:00 |
March | 805.43 | 01-MAR-08:09 | 454.65 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.47 | 19-MAR-16:00 | 24.88 | 03-MAR-05:30 |
April | 805.43 | 03-APR-07:10 | 339.49 | 13-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 | 02-APR-15:35 | 13.90 | 23-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 347.46 | 22-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.42 | 07-MAY-14:36 | 47.17 | 08-MAY-22:00 |
June | 805.43 | 01-JUN-07:10 | 336.04 | 01-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.96 | 18-JUN-14:36 | 51.50 | 20-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 344.46 | 17-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.40 | 04-JUL-14:16 | 21.71 | 02-JUL-13:40 |
August | 805.43 | 01-AUG-07:10 | 339.01 | 24-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.00 | 06-AUG-12:40 | 55.29 | 20-AUG-10:50 |
September | 805.43 | 01-SEP-07:10 | 347.61 | 22-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.38 | 10-SEP-15:00 | 30.37 | 15-SEP-22:00 |
October | 805.43 | 02-OCT-07:10 | 367.39 | 30-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.90 | 29-OCT-13:08 | 23.60 | 23-OCT-04:55 |
November | 805.43 | 01-NOV-07:10 | 561.42 | 27-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.59 | 11-NOV-16:00 | 27.12 | 26-NOV-10:00 |
December | 805.43 | 01-DEC-08:09 | 563.94 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 31-DEC-12:45 | 46.73 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 336.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.12 | 13.90 | |||||
Maximum of Months | 805.43 | 563.94 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 157.47 | 126.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 694.85 | 02-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 15-JAN-12:53 | 195.25 | 07-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 578.08 | 01-FEB-17:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.31 | 20-FEB-15:54 | 24.65 | 19-FEB-07:00 |
March | 1306.65 | 01-MAR-10:09 | 578.08 | 01-MAR-17:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.20 | 19-MAR-16:00 | 37.58 | 03-MAR-05:30 |
April | 1306.65 | 03-APR-09:09 | 548.62 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.18 | 30-APR-15:28 | 14.24 | 22-APR-03:00 |
May | 1306.65 | 01-MAY-09:09 | 564.91 | 17-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.49 | 07-MAY-14:36 | 69.39 | 08-MAY-22:00 |
June | 1306.65 | 01-JUN-09:09 | 558.76 | 20-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.14 | 18-JUN-14:36 | 75.52 | 20-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 561.18 | 11-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.90 | 04-JUL-14:20 | 23.91 | 02-JUL-13:40 |
August | 1306.65 | 01-AUG-09:09 | 557.93 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.59 | 06-AUG-12:40 | 77.01 | 20-AUG-11:00 |
September | 1306.65 | 01-SEP-09:09 | 545.42 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.07 | 10-SEP-15:00 | 45.07 | 15-SEP-22:00 |
October | 1306.65 | 02-OCT-09:09 | 556.20 | 23-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.81 | 29-OCT-13:05 | 35.82 | 23-OCT-04:55 |
November | 1306.65 | 01-NOV-09:09 | 799.59 | 09-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 | 11-NOV-15:38 | 40.50 | 26-NOV-10:00 |
December | 1306.65 | 01-DEC-10:09 | 833.69 | 18-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 31-DEC-12:56 | 71.39 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 545.42 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 52.86 | 14.24 | |||||
Maximum of Months | 1306.65 | 833.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 236.20 | 195.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 365.95 | 02-JAN-17:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 | 15-JAN-12:53 | 126.97 | 07-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 365.95 | 01-FEB-17:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.05 | 20-FEB-15:54 | 15.25 | 19-FEB-07:00 |
March | 827.17 | 01-MAR-10:09 | 365.95 | 01-MAR-17:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 | 19-MAR-16:00 | 25.21 | 03-MAR-05:30 |
April | 827.17 | 03-APR-09:09 | 360.69 | 21-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 | 30-APR-15:24 | 12.93 | 09-APR-16:03 |
May | 827.17 | 01-MAY-09:09 | 365.42 | 17-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.08 | 07-MAY-15:00 | 47.45 | 08-MAY-22:00 |
June | 827.17 | 01-JUN-09:09 | 361.43 | 20-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 | 18-JUN-14:34 | 52.63 | 20-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 363.20 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | 04-JUL-14:14 | 22.38 | 02-JUL-13:40 |
August | 827.17 | 01-AUG-09:09 | 363.70 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.56 | 06-AUG-12:40 | 51.64 | 20-AUG-11:00 |
September | 827.17 | 01-SEP-09:09 | 361.20 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.39 | 10-SEP-15:00 | 30.96 | 15-SEP-22:00 |
October | 827.17 | 02-OCT-09:09 | 367.86 | 23-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 | 29-OCT-13:05 | 23.72 | 23-OCT-04:55 |
November | 827.17 | 01-NOV-09:09 | 470.02 | 09-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.32 | 11-NOV-15:38 | 25.07 | 26-NOV-10:00 |
December | 827.17 | 01-DEC-10:09 | 512.55 | 18-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 31-DEC-12:52 | 46.96 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 360.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 36.04 | 12.93 | |||||
Maximum of Months | 827.17 | 512.55 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 157.46 | 126.97 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.15 | 15-JAN-13:00 | 275.06 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.86 | 19-FEB-14:52 | 30.44 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.53 | 19-MAR-16:00 | 49.11 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.32 | 30-APR-15:50 | 18.62 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.89 | 07-MAY-15:00 | 83.71 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.01 | 18-JUN-14:20 | 81.24 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.65 | 04-JUL-13:53 | 27.22 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.05 | 06-AUG-12:43 | 83.43 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.06 | 10-SEP-15:00 | 56.16 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.87 | 29-OCT-12:52 | 44.14 | 23-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 | 11-NOV-16:00 | 51.08 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 24-DEC-15:00 | 98.33 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 18.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.53 | 275.06 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.19 | 15-JAN-13:00 | 332.76 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.00 | 19-FEB-14:52 | 38.41 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.08 | 19-MAR-16:00 | 60.11 | 03-MAR-05:40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.08 | 23-APR-14:51 | 22.35 | 22-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.76 | 07-MAY-15:00 | 107.10 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.17 | 18-JUN-14:20 | 101.44 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.87 | 04-JUL-13:53 | 34.32 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.81 | 06-AUG-12:43 | 99.88 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.30 | 10-SEP-15:00 | 68.79 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.81 | 29-OCT-12:52 | 57.94 | 23-OCT-04:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.74 | 11-NOV-16:00 | 63.69 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.23 | 24-DEC-15:00 | 122.46 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.23 | 22.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.08 | 332.76 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 | 15-JAN-13:00 | 266.54 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.81 | 19-FEB-15:00 | 36.34 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.35 | 19-MAR-16:00 | 54.41 | 03-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.05 | 09-APR-15:00 | 16.22 | 13-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.51 | 21-MAY-12:00 | 101.27 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.86 | 18-JUN-14:00 | 122.82 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.81 | 04-JUL-14:00 | 100.31 | 02-JUL-13:43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.66 | 06-AUG-12:40 | 124.07 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.38 | 10-SEP-15:00 | 91.89 | 03-SEP-16:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.45 | 29-OCT-12:52 | 80.80 | 29-OCT-17:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.17 | 11-NOV-16:00 | 62.58 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 | 31-DEC-09:53 | 111.94 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 | 16.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.35 | 266.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38503.29 | 12-JAN-05:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38623.60 | 07-FEB-05:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38700.48 | 08-MAR-05:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38451.00 | 22-APR-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38573.82 | 26-MAY-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38133.16 | 03-JUN-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38544.89 | 22-JUL-04:53 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38952.49 | 22-AUG-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41296.06 | 19-SEP-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38738.06 | 12-OCT-04:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38564.97 | 09-NOV-05:03 | 0.00 | 846.94 | 22568.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38273.45 | 30-DEC-05:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 38133.16 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41296.06 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9595.06 | 04-JAN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 | 0.00 |
February | 10706.03 | 21-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 | 0.00 |
March | 10733.31 | 20-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.12 | 0.00 |
April | 10000.40 | 11-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 0.00 |
May | 10738.37 | 05-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.68 | 0.00 |
June | 10535.88 | 16-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 | 0.00 |
July | 9204.42 | 14-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 | 0.00 |
August | 9830.93 | 14-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 |
September | 9747.27 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.52 | 0.00 |
October | 9324.97 | 02-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.94 | 0.00 |
November | 9178.54 | 22-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
December | 9523.79 | 26-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9178.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 | |
Maximum of Months | 10738.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4972.58 | 17-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 | 0.00 |
February | 5406.89 | 21-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.68 | 0.00 |
March | 5161.11 | 20-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 0.00 |
April | 4771.97 | 17-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.52 | 0.00 |
May | 5562.06 | 30-MAY-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 0.00 |
June | 5361.08 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.63 | 0.00 |
July | 4606.29 | 17-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 | 0.00 |
August | 4885.45 | 14-AUG-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | 0.00 |
September | 5081.60 | 05-SEP-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 0.00 |
October | 5040.64 | 10-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
November | 5162.88 | 13-NOV-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.87 | 0.00 |
December | 5031.61 | 26-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4606.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 0.00 | |
Maximum of Months | 5562.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5720.79 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
February | 5685.04 | 21-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.11 | 0.00 |
March | 5356.14 | 20-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 0.00 |
April | 5242.33 | 17-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.86 | 0.00 |
May | 5913.44 | 30-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 0.00 |
June | 5737.00 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.32 | 0.00 |
July | 5169.28 | 17-JUL-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 | 0.00 |
August | 5362.61 | 14-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 | 0.00 |
September | 5540.50 | 05-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
October | 5348.88 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
November | 5362.50 | 13-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
December | 5346.81 | 26-DEC-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5169.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5913.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 4.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30333.86 | 10-JAN-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33645.52 | 21-FEB-05:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30505.80 | 07-MAR-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29867.54 | 10-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33471.47 | 22-MAY-04:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30222.78 | 01-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30530.99 | 18-JUL-04:22 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30343.47 | 21-AUG-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32289.92 | 19-SEP-05:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33890.02 | 10-OCT-04:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32659.08 | 13-NOV-05:04 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29346.19 | 05-DEC-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29346.19 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33890.02 | 3811.58 | 2742.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32699.67 | 09-JAN-05:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 35876.66 | 06-FEB-06:03 | 3811.58 | 1270.40 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32538.32 | 06-MAR-05:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32781.55 | 10-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32975.16 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32729.78 | 26-JUN-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32633.11 | 06-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32279.80 | 07-AUG-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32367.16 | 26-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33072.31 | 10-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32629.64 | 20-NOV-05:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31499.59 | 18-DEC-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 31499.59 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35876.66 | 3811.58 | 2193.73 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9431.31 | 02-JAN-06:12 | 535.68 | 453.28 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11846.50 | 19-FEB-15:52 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 71.88 | 0.00 |
March | 11861.58 | 26-MAR-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 108.32 | 0.00 |
April | 11921.83 | 30-APR-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 0.00 |
May | 12214.49 | 14-MAY-13:02 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 88.89 | 0.00 |
June | 12445.95 | 18-JUN-10:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 | 0.00 |
July | 12137.64 | 04-JUL-13:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 0.00 |
August | 11835.52 | 27-AUG-12:53 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 122.77 | 0.00 |
September | 11834.15 | 04-SEP-12:02 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 62.27 | 0.00 |
October | 11855.12 | 09-OCT-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 61.85 | 0.00 |
November | 10637.61 | 05-NOV-14:32 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 28.42 | 0.00 |
December | 10506.66 | 31-DEC-16:12 | 334.80 | 147.99 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 35.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9431.31 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12445.95 | 535.68 | 453.28 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 134.94 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10969.21 | 16-JAN-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 |
February | 10426.24 | 19-FEB-15:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 49.74 | 0.00 |
March | 11230.69 | 05-MAR-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 | 0.00 |
April | 11240.22 | 02-APR-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 | 0.00 |
May | 11131.07 | 07-MAY-07:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 | 0.00 |
June | 11481.08 | 18-JUN-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 57.34 | 0.00 |
July | 11051.03 | 30-JUL-10:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 0.00 |
August | 10813.87 | 27-AUG-12:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 80.46 | 0.00 |
September | 11169.83 | 04-SEP-08:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 0.00 |
October | 11219.58 | 08-OCT-09:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 | 0.00 |
November | 9918.03 | 05-NOV-11:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 39.04 | 0.00 |
December | 10524.23 | 31-DEC-10:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9918.03 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 0.00 | |
Maximum of Months | 11481.08 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 80.46 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12438.15 | 08-JAN-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 0.00 |
February | 12258.91 | 26-FEB-12:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 36.13 | 0.00 |
March | 12049.91 | 26-MAR-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 99.37 | 0.00 |
April | 11662.04 | 02-APR-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 | 0.00 |
May | 11554.15 | 14-MAY-13:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 | 0.00 |
June | 11531.96 | 18-JUN-10:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 102.48 | 0.00 |
July | 11550.76 | 09-JUL-14:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 89.06 | 0.00 |
August | 11425.44 | 27-AUG-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 0.00 |
September | 11661.16 | 04-SEP-12:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 60.10 | 0.00 |
October | 12159.27 | 29-OCT-11:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 111.58 | 0.00 |
November | 12377.02 | 23-NOV-11:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 | 0.00 |
December | 12434.13 | 31-DEC-16:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11425.44 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 0.00 | |
Maximum of Months | 12438.15 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12780.29 | 16-JAN-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
February | 13023.84 | 19-FEB-15:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 | 0.00 |
March | 13252.06 | 19-MAR-15:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 0.00 |
April | 13152.35 | 02-APR-16:12 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 72.55 | 0.00 |
May | 12726.74 | 14-MAY-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 0.00 |
June | 13039.86 | 25-JUN-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 0.00 |
July | 12770.37 | 04-JUL-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 | 0.00 |
August | 12775.00 | 27-AUG-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 63.65 | 0.00 |
September | 12988.42 | 04-SEP-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 49.89 | 0.00 |
October | 13008.69 | 15-OCT-15:52 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 |
November | 11744.82 | 19-NOV-15:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 31.78 | 0.00 |
December | 13083.80 | 31-DEC-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11744.82 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.91 | 0.00 | |
Maximum of Months | 13252.06 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7740.53 | 02-JAN-07:03 | 1071.35 | 959.44 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
February | 10026.34 | 20-FEB-16:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 | 0.00 |
March | 8208.71 | 28-MAR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 0.00 |
April | 8448.67 | 20-APR-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 | 0.00 |
May | 10426.66 | 28-MAY-10:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 0.00 |
June | 10603.43 | 18-JUN-10:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 | 0.00 |
July | 10440.40 | 04-JUL-17:22 | 0.00 | 137.87 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 0.00 |
August | 10249.04 | 27-AUG-16:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 36.60 | 0.00 |
September | 10298.50 | 04-SEP-16:31 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 | 0.00 |
October | 8245.69 | 16-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
November | 7824.55 | 13-NOV-07:03 | 803.52 | 496.35 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
December | 7760.18 | 11-DEC-07:03 | 803.52 | 574.45 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7740.53 | 0.00 | 137.87 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10603.43 | 1071.35 | 959.44 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 50.73 | 0.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9933.29 | 16-JAN-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
February | 10340.92 | 20-FEB-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
March | 10027.15 | 05-MAR-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.99 | 0.00 |
April | 10028.71 | 02-APR-08:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 0.00 |
May | 10359.05 | 28-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 0.00 |
June | 10277.03 | 18-JUN-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 32.81 | 0.00 |
July | 9687.13 | 30-JUL-10:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 0.00 |
August | 10365.44 | 27-AUG-10:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.90 | 0.00 |
September | 10367.59 | 04-SEP-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 | 0.00 |
October | 8257.47 | 29-OCT-11:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 | 0.00 |
November | 9148.31 | 05-NOV-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
December | 9819.25 | 31-DEC-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 15.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8257.47 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.61 | 0.00 | |
Maximum of Months | 10367.59 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11138.47 | 16-JAN-12:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 0.00 |
February | 10842.26 | 21-FEB-13:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7605.08 | 0.00 |
March | 10731.82 | 21-MAR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8843.77 | 0.00 |
April | 10249.00 | 18-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8601.97 | 0.00 |
May | 11107.01 | 05-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 10632.51 | 0.00 |
June | 10616.32 | 16-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9193.66 | 0.00 |
July | 9756.55 | 26-JUL-17:00 | 401.76 | 296.53 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8218.22 | 0.00 |
August | 10258.51 | 15-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8268.10 | 0.00 |
September | 10109.59 | 05-SEP-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7681.23 | 0.00 |
October | 10358.37 | 29-OCT-11:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 | 0.00 |
November | 10727.21 | 19-NOV-12:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 19.38 | 0.00 |
December | 10859.90 | 31-DEC-12:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9756.55 | 267.84 | 110.30 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 0.00 | |
Maximum of Months | 11138.47 | 687.71 | 496.34 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 10632.51 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11484.62 | 16-JAN-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 0.00 |
February | 11292.55 | 20-FEB-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 0.00 |
March | 11300.87 | 05-MAR-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 0.00 |
April | 11014.15 | 02-APR-16:12 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 0.00 |
May | 10857.74 | 14-MAY-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
June | 10948.17 | 25-JUN-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
July | 11237.67 | 04-JUL-17:22 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 |
August | 11310.89 | 27-AUG-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | 0.00 |
September | 11729.13 | 04-SEP-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 0.00 |
October | 10779.99 | 15-OCT-16:12 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 0.00 |
November | 11007.42 | 19-NOV-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 | 0.00 |
December | 10995.38 | 31-DEC-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10779.99 | 0.00 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 0.00 | |
Maximum of Months | 11729.13 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 41.43 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7782.45 | 02-JAN-07:03 | 1071.35 | 975.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
February | 10184.12 | 20-FEB-16:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 72.98 | 0.00 |
March | 9422.84 | 19-MAR-15:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 220.40 | 0.00 |
April | 9771.40 | 30-APR-17:22 | 0.00 | 158.03 | 1930.52 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 0.00 |
May | 10493.45 | 28-MAY-10:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 | 0.00 |
June | 10671.78 | 18-JUN-10:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 78.07 | 0.00 |
July | 10623.11 | 04-JUL-16:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 43.51 | 0.00 |
August | 10277.34 | 27-AUG-16:42 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 | 0.00 |
September | 10329.67 | 04-SEP-16:31 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 68.50 | 0.00 |
October | 9408.30 | 09-OCT-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 0.00 |
November | 8548.73 | 13-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
December | 8162.93 | 11-DEC-06:12 | 669.60 | 547.90 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7782.45 | 0.00 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10671.78 | 1071.35 | 975.41 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 220.40 | 4.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10525.45 | 16-JAN-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 7.75 | 0.00 |
February | 11063.28 | 20-FEB-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 0.00 |
March | 10745.69 | 05-MAR-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 0.00 |
April | 10744.21 | 23-APR-09:02 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 0.00 |
May | 11074.78 | 28-MAY-09:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 0.00 |
June | 10872.55 | 18-JUN-10:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 0.00 |
July | 10298.76 | 30-JUL-09:53 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 30.29 | 0.00 |
August | 11079.11 | 27-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 0.00 |
September | 10987.25 | 04-SEP-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.92 | 0.00 |
October | 10716.60 | 08-OCT-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 0.00 |
November | 10174.35 | 05-NOV-09:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 | 0.00 |
December | 10431.92 | 31-DEC-11:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10174.35 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 0.00 | |
Maximum of Months | 11079.11 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11293.95 | 16-JAN-12:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 |
February | 10838.95 | 20-FEB-11:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 | 0.00 |
March | 10245.92 | 26-MAR-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 86.17 | 0.00 |
April | 9847.97 | 02-APR-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 | 0.00 |
May | 9810.82 | 14-MAY-14:51 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 53.95 | 0.00 |
June | 9222.26 | 11-JUN-15:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 101.52 | 0.00 |
July | 9182.17 | 09-JUL-14:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 77.39 | 0.00 |
August | 9783.90 | 27-AUG-16:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 0.00 |
September | 10073.16 | 04-SEP-16:31 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 67.83 | 0.00 |
October | 10485.27 | 29-OCT-11:02 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 95.56 | 0.00 |
November | 10873.83 | 19-NOV-12:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 | 0.00 |
December | 11047.98 | 03-DEC-12:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9182.17 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 | |
Maximum of Months | 11293.95 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 101.52 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12272.57 | 16-JAN-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 0.00 |
February | 12077.54 | 20-FEB-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 35.81 | 0.00 |
March | 12118.17 | 05-MAR-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 0.00 |
April | 11850.95 | 23-APR-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
May | 11605.22 | 14-MAY-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 33.21 | 0.00 |
June | 11706.04 | 25-JUN-16:22 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 | 0.00 |
July | 12246.89 | 04-JUL-16:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 |
August | 12055.34 | 27-AUG-16:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 | 0.00 |
September | 12553.65 | 04-SEP-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 | 0.00 |
October | 11541.02 | 15-OCT-16:42 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 | 0.00 |
November | 11741.76 | 19-NOV-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 0.00 |
December | 11807.41 | 03-DEC-15:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11541.02 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 | 0.00 | |
Maximum of Months | 12553.65 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.163795E+12 | 145573.13 | 30-JAN-15:09 | 0.00 | 0.00 |
February | 0.152878E+12 | 155171.18 | 13-FEB-15:09 | 0.00 | 0.00 |
March | 0.180706E+12 | 156836.44 | 20-MAR-15:09 | 0.00 | 0.00 |
April | 0.176210E+12 | 155916.90 | 11-APR-15:00 | 0.00 | 0.00 |
May | 0.192124E+12 | 162754.10 | 05-MAY-14:09 | 0.00 | 0.00 |
June | 0.191799E+12 | 170680.94 | 13-JUN-15:09 | 0.00 | 0.00 |
July | 0.166557E+12 | 147461.04 | 17-JUL-14:09 | 0.00 | 0.00 |
August | 0.183686E+12 | 157015.29 | 14-AUG-14:09 | 0.00 | 0.00 |
September | 0.169640E+12 | 153887.53 | 05-SEP-14:09 | 0.00 | 0.00 |
October | 0.169340E+12 | 152110.65 | 16-OCT-14:09 | 0.00 | 0.00 |
November | 0.163610E+12 | 147904.17 | 13-NOV-13:50 | 0.00 | 0.00 |
December | 0.159204E+12 | 142891.60 | 26-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.206955E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.152878E+12 | 142891.60 | 0.00 | 0.00 | |
Maximum of Months | 0.192124E+12 | 170680.94 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.194409E+11 | 0.456186E+10 | 0.605851E+11 | 0.225707E+10 | 0.101731E+11 | 12379742.02 | 0.00 | 0.636731E+11 | 0.00 | 0.00 | 0.00 | 0.309155E+10 | 0.00 |
February | 0.175960E+11 | 0.400802E+10 | 0.548702E+11 | 0.204803E+10 | 0.977143E+10 | 11196021.66 | 0.00 | 0.617800E+11 | 0.00 | 0.00 | 0.00 | 0.279258E+10 | 0.00 |
March | 0.207887E+11 | 0.419680E+10 | 0.627783E+11 | 0.235484E+10 | 0.113149E+11 | 12675672.10 | 0.00 | 0.760153E+11 | 0.00 | 0.00 | 0.00 | 0.324432E+10 | 0.00 |
April | 0.184721E+11 | 0.388710E+10 | 0.586172E+11 | 0.219180E+10 | 0.105200E+11 | 11960507.72 | 0.00 | 0.796314E+11 | 0.00 | 0.00 | 0.00 | 0.287812E+10 | 0.00 |
May | 0.199537E+11 | 0.388975E+10 | 0.616817E+11 | 0.230585E+10 | 0.112897E+11 | 12527707.06 | 0.00 | 0.899717E+11 | 0.00 | 0.00 | 0.00 | 0.301872E+10 | 0.00 |
June | 0.198196E+11 | 0.371634E+10 | 0.604966E+11 | 0.226810E+10 | 0.119392E+11 | 12231776.97 | 0.00 | 0.905932E+11 | 0.00 | 0.00 | 0.00 | 0.295360E+10 | 0.00 |
July | 0.185659E+11 | 0.390630E+10 | 0.597911E+11 | 0.222887E+10 | 0.970889E+10 | 12256437.81 | 0.00 | 0.695544E+11 | 0.00 | 0.00 | 0.00 | 0.278956E+10 | 0.00 |
August | 0.207033E+11 | 0.397154E+10 | 0.627783E+11 | 0.235475E+10 | 0.101465E+11 | 12675672.10 | 0.00 | 0.806382E+11 | 0.00 | 0.00 | 0.00 | 0.308050E+10 | 0.00 |
September | 0.185540E+11 | 0.400992E+10 | 0.585950E+11 | 0.219062E+10 | 0.936033E+10 | 11960507.72 | 0.00 | 0.740870E+11 | 0.00 | 0.00 | 0.00 | 0.283114E+10 | 0.00 |
October | 0.193050E+11 | 0.434010E+10 | 0.605962E+11 | 0.225770E+10 | 0.919268E+10 | 12379742.02 | 0.00 | 0.706534E+11 | 0.00 | 0.00 | 0.00 | 0.298239E+10 | 0.00 |
November | 0.192641E+11 | 0.440359E+10 | 0.591197E+11 | 0.219979E+10 | 0.948448E+10 | 12059151.09 | 0.00 | 0.661405E+11 | 0.00 | 0.00 | 0.00 | 0.298545E+10 | 0.00 |
December | 0.188685E+11 | 0.461491E+10 | 0.597800E+11 | 0.222835E+10 | 0.925695E+10 | 12256437.81 | 0.00 | 0.614410E+11 | 0.00 | 0.00 | 0.00 | 0.300250E+10 | 0.00 |
Annual Sum or Average | 0.231332E+12 | 0.495062E+11 | 0.719689E+12 | 0.268858E+11 | 0.122158E+12 | 0.146559E+09 | 0.00 | 0.884179E+12 | 0.00 | 0.00 | 0.00 | 0.356504E+11 | 0.00 |
Minimum of Months | 0.175960E+11 | 0.371634E+10 | 0.548702E+11 | 0.204803E+10 | 0.919268E+10 | 11196021.66 | 0.00 | 0.614410E+11 | 0.00 | 0.00 | 0.00 | 0.278956E+10 | 0.00 |
Maximum of Months | 0.207887E+11 | 0.461491E+10 | 0.627783E+11 | 0.235484E+10 | 0.119392E+11 | 12675672.10 | 0.00 | 0.905932E+11 | 0.00 | 0.00 | 0.00 | 0.324432E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21974.93 | 02-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 03-JAN-12:20 | 14870.82 | 17-JAN-15:09 | 6.85 | 01-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 20444.04 | 07-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 15-FEB-13:09 | 16829.08 | 21-FEB-15:09 | 6.85 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 20572.14 | 01-MAR-16:00 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 03-MAR-13:09 | 16013.19 | 20-MAR-14:50 | 6.85 | 19-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 20090.99 | 21-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 04-APR-12:09 | 14658.77 | 17-APR-15:20 | 6.85 | 02-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 20180.84 | 17-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 02-MAY-11:09 | 15699.53 | 30-MAY-10:30 | 6.85 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 20102.25 | 20-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 06-JUN-11:09 | 17026.58 | 12-JUN-15:20 | 6.85 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 20131.12 | 11-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-11:09 | 13920.99 | 24-JUL-14:30 | 6.85 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 20139.53 | 21-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 01-AUG-12:09 | 14630.48 | 14-AUG-14:30 | 6.85 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 20094.39 | 21-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 06-SEP-12:09 | 14514.94 | 05-SEP-14:09 | 6.85 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 20215.91 | 23-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-16:10 | 14740.03 | 10-OCT-14:30 | 6.85 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 22844.99 | 09-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 14286.20 | 20-NOV-15:09 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 23150.96 | 18-DEC-16:00 | 5686.19 | 01-DEC-17:30 | 41699.26 | 01-DEC-08:09 | 1410.29 | 01-DEC-12:09 | 15067.07 | 26-DEC-15:09 | 6.85 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 20090.99 | 5686.19 | 41699.26 | 1410.29 | 13920.99 | 6.85 | 0.00 | |||||||
Maximum of Months | 23150.96 | 5686.19 | 41699.26 | 1410.29 | 17026.58 | 6.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 65706.00 | 30-JAN-15:09 | 0.00 | 0.00 | 0.00 | 4202.90 | 12-JAN-12:00 | 0.00 |
February | 75101.01 | 13-FEB-15:09 | 0.00 | 0.00 | 0.00 | 4201.41 | 01-FEB-12:50 | 0.00 |
March | 75560.24 | 20-MAR-14:00 | 0.00 | 0.00 | 0.00 | 4024.75 | 02-MAR-12:39 | 0.00 |
April | 76352.05 | 18-APR-14:09 | 0.00 | 0.00 | 0.00 | 3882.73 | 03-APR-11:30 | 0.00 |
May | 85332.66 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 3871.21 | 01-MAY-11:00 | 0.00 |
June | 89027.53 | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | 3860.54 | 01-JUN-11:50 | 0.00 |
July | 68882.30 | 17-JUL-14:09 | 0.00 | 0.00 | 0.00 | 3855.03 | 28-JUL-11:30 | 0.00 |
August | 77530.41 | 14-AUG-14:09 | 0.00 | 0.00 | 0.00 | 3862.06 | 31-AUG-11:20 | 0.00 |
September | 74627.76 | 05-SEP-12:09 | 0.00 | 0.00 | 0.00 | 3872.52 | 29-SEP-11:50 | 0.00 |
October | 73185.86 | 16-OCT-14:09 | 0.00 | 0.00 | 0.00 | 3885.61 | 31-OCT-11:20 | 0.00 |
November | 70094.21 | 13-NOV-13:00 | 0.00 | 0.00 | 0.00 | 4054.21 | 27-NOV-12:20 | 0.00 |
December | 66289.31 | 11-DEC-13:09 | 0.00 | 0.00 | 0.00 | 4200.24 | 26-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 65706.00 | 0.00 | 0.00 | 0.00 | 3855.03 | 0.00 | ||
Maximum of Months | 89027.53 | 0.00 | 0.00 | 0.00 | 4202.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 145573.13 | 30-JAN-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14580.70 | 6.85 | 0.00 | 65706.00 | 0.00 |
February | 155171.18 | 13-FEB-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14959.39 | 6.85 | 0.00 | 75101.01 | 0.00 |
March | 156836.44 | 20-MAR-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 15942.00 | 6.85 | 0.00 | 75250.61 | 0.00 |
April | 155916.90 | 11-APR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 13934.47 | 6.85 | 0.00 | 76335.46 | 0.00 |
May | 162754.10 | 05-MAY-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 15013.52 | 6.85 | 0.00 | 82746.36 | 0.00 |
June | 170680.94 | 13-JUN-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 16133.96 | 6.85 | 0.00 | 88919.65 | 0.00 |
July | 147461.04 | 17-JUL-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 13589.43 | 6.85 | 0.00 | 68882.30 | 0.00 |
August | 157015.29 | 14-AUG-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14494.50 | 6.85 | 0.00 | 77530.41 | 0.00 |
September | 153887.53 | 05-SEP-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14514.94 | 6.85 | 0.00 | 74380.31 | 0.00 |
October | 152110.65 | 16-OCT-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 13927.46 | 6.85 | 0.00 | 73185.86 | 0.00 |
November | 147904.17 | 13-NOV-13:50 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 14017.29 | 6.85 | 0.00 | 70005.80 | 0.00 |
December | 142891.60 | 26-DEC-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 15067.07 | 6.85 | 0.00 | 62820.22 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 142891.60 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 13589.43 | 6.85 | 0.00 | 62820.22 | 0.00 | |
Maximum of Months | 170680.94 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 16133.96 | 6.85 | 0.00 | 88919.65 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.00 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.19 | 0.00 | 26.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.45 | 0.17 | 26.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.19 | 0.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.39 | 0.00 | 26.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.33 | 26.44 | 0.17 | 26.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.17 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.43 | 4.00 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.51 | 4.67 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.53 | 6.33 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.74 | 7.50 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.78 | 7.83 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.54 | 8.17 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.58 | 3.17 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.46 | 4.67 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.42 | 4.67 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.29 | 0.83 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
Annual Sum or Average | 0.00 | 0.00 | 59.00 | 27.58 | 52.67 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.78 | 8.17 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.47 | 9.00 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.63 | 11.33 | 27.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.85 | 9.17 | 27.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.86 | 11.33 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.89 | 10.17 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.79 | 9.00 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.56 | 10.83 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.78 | 6.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.76 | 9.67 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.61 | 10.67 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.51 | 8.67 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.53 | 9.83 | 27.53 |
Annual Sum or Average | 0.00 | 0.00 | 122.00 | 27.69 | 115.83 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.47 | 6.17 | 27.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.89 | 11.33 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 26.65 | 17.67 | 26.63 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.42 | 11.00 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.74 | 6.50 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.54 | 6.00 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.58 | 5.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.52 | 5.17 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.41 | 4.83 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.67 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.54 | 5.17 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.64 | 8.50 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.80 | 9.00 | 27.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.52 | 19.17 | 26.52 |
Annual Sum or Average | 0.00 | 0.00 | 106.17 | 27.23 | 101.00 | 27.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.52 | 2.67 | 26.52 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.80 | 19.17 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.96 | 7.00 | 27.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.92 | 7.00 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.11 | 6.00 | 28.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.94 | 8.00 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.92 | 7.33 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.98 | 6.50 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.71 | 8.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.95 | 4.33 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.90 | 6.00 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.72 | 7.17 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.75 | 6.17 | 27.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.96 | 6.83 | 27.97 |
Annual Sum or Average | 0.00 | 0.00 | 99.50 | 27.90 | 80.33 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.71 | 4.33 | 27.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.11 | 8.00 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.49 | 6.00 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.50 | 6.50 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.39 | 3.50 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.36 | 2.00 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.33 | 1.00 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.33 | 27.45 | 19.50 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.50 | 6.50 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.45 | 2.50 | 27.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.47 | 9.33 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.60 | 9.17 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.62 | 10.67 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.63 | 9.50 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.54 | 8.67 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.40 | 8.17 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.60 | 5.50 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.54 | 9.33 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.51 | 6.50 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.39 | 6.17 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.41 | 6.00 | 27.41 |
Annual Sum or Average | 0.00 | 0.00 | 94.67 | 27.53 | 91.50 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.39 | 2.50 | 27.39 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.63 | 10.67 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 25.45 | 124.00 | 25.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 116.00 | 25.50 | 115.83 | 25.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 25.56 | 76.67 | 25.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 25.71 | 41.67 | 25.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 | 25.70 | 48.83 | 25.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 25.85 | 45.33 | 25.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 25.28 | 29.67 | 25.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 25.52 | 32.83 | 25.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 25.55 | 34.00 | 25.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.46 | 45.83 | 25.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 25.42 | 78.67 | 25.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 102.67 | 25.53 | 102.17 | 25.52 |
Annual Sum or Average | 0.00 | 0.00 | 776.83 | 25.53 | 775.50 | 25.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 25.28 | 29.67 | 25.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 124.67 | 25.85 | 124.00 | 25.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 5.83 | 27.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.74 | 5.83 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.77 | 5.00 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.79 | 5.17 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.66 | 5.17 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.69 | 5.67 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.55 | 5.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.69 | 3.83 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.71 | 4.67 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.56 | 5.67 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.55 | 5.00 | 27.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.76 | 5.50 | 27.76 |
Annual Sum or Average | 0.00 | 0.00 | 78.00 | 27.69 | 62.67 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.55 | 3.83 | 27.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.79 | 5.83 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.32 | 1.33 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.36 | 1.50 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.37 | 2.33 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.57 | 6.50 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.63 | 6.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.39 | 4.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.40 | 1.67 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.39 | 1.00 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 28.17 | 27.50 | 26.00 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.63 | 6.83 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.47 | 3.50 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.53 | 9.83 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.68 | 9.33 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.71 | 10.83 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.76 | 9.67 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.63 | 8.50 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.44 | 7.50 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.65 | 5.50 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.61 | 8.83 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.53 | 7.50 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.42 | 7.33 | 27.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.45 | 7.17 | 27.45 |
Annual Sum or Average | 0.00 | 0.00 | 97.17 | 27.59 | 95.50 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.42 | 3.50 | 27.42 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.76 | 10.83 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 25.79 | 28.50 | 25.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.49 | 14.33 | 26.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.54 | 6.00 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 3.17 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.39 | 2.33 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.40 | 2.00 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.53 | 6.50 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.67 | 8.00 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 25.60 | 38.00 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 111.17 | 26.29 | 110.67 | 26.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.00 | 27.67 | 38.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.88 | 5.83 | 27.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.84 | 5.83 | 27.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.02 | 5.00 | 28.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.92 | 5.33 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.83 | 5.33 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.85 | 5.33 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.64 | 5.33 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 3.67 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.80 | 4.50 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.63 | 5.50 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.63 | 5.17 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.84 | 5.83 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 74.67 | 27.81 | 62.67 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.63 | 3.67 | 27.63 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.02 | 5.83 | 28.05 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 24.51 | 0.00 | 24.51 |
February | 0.00 | 0.00 | 454.00 | 24.47 | 0.00 | 24.47 |
March | 0.00 | 0.00 | 514.00 | 24.40 | 0.00 | 24.40 |
April | 0.00 | 0.00 | 485.00 | 24.43 | 0.00 | 24.43 |
May | 0.00 | 0.00 | 508.00 | 24.44 | 0.00 | 24.44 |
June | 0.00 | 0.00 | 496.00 | 24.42 | 0.00 | 24.42 |
July | 0.00 | 0.00 | 497.00 | 24.49 | 0.00 | 24.49 |
August | 0.00 | 0.00 | 514.00 | 24.43 | 0.00 | 24.43 |
September | 0.00 | 0.00 | 485.00 | 24.44 | 0.00 | 24.44 |
October | 0.00 | 0.00 | 502.00 | 24.49 | 0.00 | 24.49 |
November | 0.00 | 0.00 | 489.00 | 24.50 | 0.00 | 24.50 |
December | 0.00 | 0.00 | 497.00 | 24.49 | 0.00 | 24.49 |
Annual Sum or Average | 0.00 | 5943.00 | 24.46 | 0.00 | 24.46 | |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.40 | 0.00 | 24.40 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.51 | 0.00 | 24.51 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 494.00 | 24.34 | 0.00 | 24.34 |
February | 0.00 | 0.00 | 446.83 | 24.31 | 0.00 | 24.31 |
March | 0.00 | 0.00 | 503.00 | 24.26 | 0.00 | 24.26 |
April | 0.00 | 0.00 | 475.67 | 24.29 | 0.00 | 24.29 |
May | 0.00 | 0.00 | 503.33 | 24.30 | 0.00 | 24.30 |
June | 0.00 | 0.00 | 491.83 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 479.17 | 24.33 | 0.00 | 24.33 |
August | 0.00 | 0.00 | 491.83 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 466.33 | 24.29 | 0.00 | 24.29 |
October | 0.00 | 0.00 | 479.50 | 24.34 | 0.00 | 24.34 |
November | 0.00 | 0.00 | 479.50 | 24.33 | 0.00 | 24.33 |
December | 0.00 | 0.00 | 468.67 | 24.32 | 0.00 | 24.32 |
Annual Sum or Average | 0.00 | 5779.67 | 24.31 | 0.00 | 24.31 | |
Minimum of Months | 0.00 | 0.00 | 446.83 | 24.26 | 0.00 | 24.26 |
Maximum of Months | 0.00 | 0.00 | 503.33 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 474.17 | 24.35 | 0.00 | 24.35 |
February | 0.00 | 0.00 | 434.67 | 24.33 | 0.00 | 24.33 |
March | 0.00 | 0.00 | 503.17 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 481.67 | 24.33 | 0.00 | 24.33 |
May | 0.00 | 0.00 | 501.50 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 494.00 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 486.83 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 494.33 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 469.67 | 24.32 | 0.00 | 24.32 |
October | 0.00 | 0.00 | 477.33 | 24.38 | 0.00 | 24.38 |
November | 0.00 | 0.00 | 466.17 | 24.34 | 0.00 | 24.34 |
December | 1.17 | 23.47 | 447.00 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 1.17 | 23.47 | 5730.50 | 24.33 | 0.00 | 24.33 |
Minimum of Months | 0.00 | 0.00 | 434.67 | 24.29 | 0.00 | 24.29 |
Maximum of Months | 1.17 | 23.47 | 503.17 | 24.38 | 0.00 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.00 | 25.75 | 478.67 | 24.50 | 13.83 | 24.55 |
February | 25.17 | 26.55 | 446.17 | 24.56 | 25.17 | 24.66 |
March | 34.50 | 26.33 | 510.50 | 24.52 | 34.50 | 24.63 |
April | 44.50 | 26.49 | 485.00 | 24.68 | 44.50 | 24.82 |
May | 54.50 | 26.52 | 506.67 | 24.72 | 54.50 | 24.88 |
June | 52.50 | 26.57 | 495.50 | 24.71 | 52.50 | 24.87 |
July | 42.50 | 26.76 | 496.50 | 24.73 | 42.50 | 24.88 |
August | 48.83 | 26.03 | 512.00 | 24.54 | 48.83 | 24.66 |
September | 33.33 | 26.40 | 482.67 | 24.58 | 33.33 | 24.69 |
October | 43.33 | 26.48 | 492.33 | 24.66 | 43.33 | 24.80 |
November | 24.00 | 26.48 | 479.67 | 24.55 | 24.00 | 24.64 |
December | 27.83 | 25.59 | 455.33 | 24.51 | 22.17 | 24.58 |
Annual Sum or Average | 449.00 | 26.38 | 5841.00 | 24.61 | 439.17 | 24.73 |
Minimum of Months | 18.00 | 25.59 | 446.17 | 24.50 | 13.83 | 24.55 |
Maximum of Months | 54.50 | 26.76 | 512.00 | 24.73 | 54.50 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.00 | 26.74 | 498.50 | 24.75 | 50.83 | 24.92 |
February | 53.50 | 26.77 | 454.00 | 24.78 | 53.50 | 24.97 |
March | 49.33 | 26.71 | 512.67 | 24.67 | 49.33 | 24.83 |
April | 58.50 | 26.81 | 485.00 | 24.82 | 58.50 | 25.01 |
May | 60.50 | 26.64 | 507.00 | 24.78 | 60.50 | 24.96 |
June | 52.50 | 26.63 | 495.67 | 24.71 | 52.50 | 24.88 |
July | 56.50 | 26.78 | 496.67 | 24.80 | 56.50 | 24.99 |
August | 56.17 | 26.31 | 514.00 | 24.62 | 56.17 | 24.78 |
September | 56.17 | 26.72 | 484.33 | 24.76 | 56.17 | 24.94 |
October | 64.00 | 26.67 | 498.00 | 24.80 | 64.00 | 24.99 |
November | 53.33 | 26.67 | 483.83 | 24.76 | 53.33 | 24.93 |
December | 55.50 | 26.67 | 484.50 | 24.75 | 55.33 | 24.93 |
Annual Sum or Average | 667.00 | 26.68 | 5914.17 | 24.75 | 666.67 | 24.93 |
Minimum of Months | 49.33 | 26.31 | 454.00 | 24.62 | 49.33 | 24.78 |
Maximum of Months | 64.00 | 26.81 | 514.00 | 24.82 | 64.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.83 | 26.91 | 497.00 | 24.80 | 48.67 | 24.97 |
February | 44.50 | 26.84 | 454.00 | 24.75 | 44.50 | 24.92 |
March | 41.33 | 26.51 | 511.83 | 24.59 | 41.33 | 24.72 |
April | 43.50 | 26.47 | 485.00 | 24.66 | 43.50 | 24.80 |
May | 44.83 | 26.33 | 506.00 | 24.64 | 44.83 | 24.77 |
June | 43.67 | 26.32 | 495.17 | 24.61 | 43.67 | 24.74 |
July | 34.67 | 26.67 | 493.83 | 24.66 | 34.67 | 24.79 |
August | 44.50 | 25.89 | 511.67 | 24.50 | 44.50 | 24.60 |
September | 35.83 | 26.46 | 483.00 | 24.60 | 35.83 | 24.72 |
October | 54.00 | 26.67 | 495.50 | 24.76 | 54.00 | 24.93 |
November | 50.00 | 26.81 | 485.17 | 24.77 | 50.00 | 24.94 |
December | 58.00 | 26.75 | 484.17 | 24.82 | 57.00 | 25.01 |
Annual Sum or Average | 543.67 | 26.56 | 5902.33 | 24.68 | 542.50 | 24.83 |
Minimum of Months | 34.67 | 25.89 | 454.00 | 24.50 | 34.67 | 24.60 |
Maximum of Months | 58.00 | 26.91 | 511.83 | 24.82 | 57.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.83 | 26.48 | 484.67 | 24.66 | 36.83 | 24.80 |
February | 34.67 | 26.76 | 451.00 | 24.67 | 34.67 | 24.81 |
March | 43.00 | 26.59 | 512.17 | 24.63 | 43.00 | 24.77 |
April | 56.00 | 26.64 | 485.00 | 24.78 | 56.00 | 24.96 |
May | 58.33 | 26.50 | 507.00 | 24.74 | 58.33 | 24.91 |
June | 51.33 | 26.51 | 496.00 | 24.69 | 51.33 | 24.85 |
July | 45.83 | 26.77 | 494.83 | 24.76 | 45.83 | 24.92 |
August | 54.50 | 26.14 | 513.67 | 24.59 | 54.50 | 24.73 |
September | 42.67 | 26.58 | 484.17 | 24.67 | 42.67 | 24.82 |
October | 53.00 | 26.61 | 495.67 | 24.75 | 53.00 | 24.91 |
November | 42.33 | 26.66 | 483.83 | 24.69 | 42.33 | 24.83 |
December | 44.33 | 26.26 | 466.83 | 24.65 | 40.17 | 24.79 |
Annual Sum or Average | 565.83 | 26.53 | 5874.83 | 24.69 | 558.67 | 24.84 |
Minimum of Months | 34.67 | 26.14 | 451.00 | 24.59 | 34.67 | 24.73 |
Maximum of Months | 58.33 | 26.77 | 513.67 | 24.78 | 58.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 501.83 | 24.43 | 0.00 | 24.43 |
February | 1.83 | 27.05 | 454.00 | 24.46 | 1.83 | 24.47 |
March | 5.17 | 26.45 | 514.00 | 24.41 | 5.17 | 24.43 |
April | 9.33 | 26.70 | 485.00 | 24.53 | 9.33 | 24.57 |
May | 32.00 | 26.79 | 508.00 | 24.68 | 32.00 | 24.79 |
June | 33.33 | 26.85 | 496.00 | 24.68 | 33.33 | 24.81 |
July | 25.17 | 26.81 | 497.00 | 24.70 | 25.17 | 24.80 |
August | 28.17 | 26.49 | 514.00 | 24.55 | 28.17 | 24.65 |
September | 7.17 | 26.80 | 485.00 | 24.51 | 7.17 | 24.54 |
October | 3.00 | 26.85 | 502.00 | 24.51 | 3.00 | 24.52 |
November | 0.50 | 26.87 | 489.00 | 24.47 | 0.50 | 24.48 |
December | 0.00 | 0.00 | 494.00 | 24.43 | 0.00 | 24.43 |
Annual Sum or Average | 145.67 | 26.74 | 5939.83 | 24.53 | 145.67 | 24.58 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.41 | 0.00 | 24.43 |
Maximum of Months | 33.33 | 27.05 | 514.00 | 24.70 | 33.33 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 26.95 | 502.00 | 24.65 | 17.50 | 24.73 |
February | 38.00 | 26.87 | 454.00 | 24.76 | 38.00 | 24.91 |
March | 41.83 | 26.83 | 514.00 | 24.68 | 41.83 | 24.83 |
April | 50.50 | 26.85 | 485.00 | 24.81 | 50.50 | 24.98 |
May | 48.67 | 26.86 | 508.00 | 24.77 | 48.67 | 24.94 |
June | 41.17 | 26.85 | 496.00 | 24.71 | 41.17 | 24.86 |
July | 41.50 | 26.81 | 497.00 | 24.78 | 41.50 | 24.92 |
August | 42.17 | 26.74 | 514.00 | 24.66 | 42.17 | 24.81 |
September | 43.17 | 26.85 | 485.00 | 24.76 | 43.17 | 24.92 |
October | 40.83 | 26.85 | 502.00 | 24.76 | 40.83 | 24.90 |
November | 29.33 | 26.86 | 489.00 | 24.72 | 29.33 | 24.83 |
December | 29.33 | 26.86 | 496.33 | 24.70 | 29.33 | 24.81 |
Annual Sum or Average | 464.00 | 26.84 | 5942.33 | 24.73 | 464.00 | 24.87 |
Minimum of Months | 17.50 | 26.74 | 454.00 | 24.65 | 17.50 | 24.73 |
Maximum of Months | 50.50 | 26.95 | 514.00 | 24.81 | 50.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.00 | 25.72 | 502.00 | 25.09 | 116.00 | 25.19 |
February | 102.50 | 25.78 | 454.00 | 25.10 | 102.50 | 25.20 |
March | 119.00 | 25.28 | 514.00 | 24.81 | 119.00 | 24.89 |
April | 122.50 | 24.85 | 485.00 | 24.70 | 122.50 | 24.72 |
May | 196.17 | 24.67 | 508.00 | 24.68 | 196.17 | 24.67 |
June | 186.33 | 24.72 | 496.00 | 24.68 | 186.33 | 24.69 |
July | 121.50 | 24.53 | 497.00 | 24.60 | 121.50 | 24.59 |
August | 227.50 | 24.51 | 514.00 | 24.52 | 227.50 | 24.52 |
September | 158.83 | 24.56 | 485.00 | 24.60 | 158.83 | 24.59 |
October | 173.33 | 24.82 | 502.00 | 24.72 | 173.33 | 24.74 |
November | 144.00 | 25.22 | 489.00 | 24.92 | 144.00 | 24.97 |
December | 121.67 | 25.61 | 496.67 | 25.03 | 121.67 | 25.12 |
Annual Sum or Average | 1789.33 | 24.94 | 5942.67 | 24.78 | 1789.33 | 24.81 |
Minimum of Months | 102.50 | 24.51 | 454.00 | 24.52 | 102.50 | 24.52 |
Maximum of Months | 227.50 | 25.78 | 514.00 | 25.10 | 227.50 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.17 | 26.94 | 502.00 | 24.65 | 23.17 | 24.75 |
February | 24.17 | 26.93 | 454.00 | 24.68 | 24.17 | 24.79 |
March | 27.17 | 26.87 | 514.00 | 24.62 | 27.17 | 24.73 |
April | 33.33 | 26.90 | 485.00 | 24.74 | 33.33 | 24.87 |
May | 38.50 | 26.85 | 508.00 | 24.73 | 38.50 | 24.87 |
June | 32.50 | 26.86 | 496.00 | 24.68 | 32.50 | 24.81 |
July | 30.17 | 26.82 | 497.00 | 24.74 | 30.17 | 24.85 |
August | 37.00 | 26.65 | 514.00 | 24.64 | 37.00 | 24.76 |
September | 24.50 | 26.89 | 485.00 | 24.67 | 24.50 | 24.77 |
October | 30.50 | 26.83 | 502.00 | 24.71 | 30.50 | 24.82 |
November | 22.83 | 26.85 | 489.00 | 24.67 | 22.83 | 24.76 |
December | 24.33 | 26.92 | 495.67 | 24.65 | 24.33 | 24.75 |
Annual Sum or Average | 348.17 | 26.85 | 5941.67 | 24.68 | 348.17 | 24.79 |
Minimum of Months | 22.83 | 26.65 | 454.00 | 24.62 | 22.83 | 24.73 |
Maximum of Months | 38.50 | 26.94 | 514.00 | 24.74 | 38.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 26.26 | 495.00 | 24.44 | 1.33 | 24.44 |
February | 9.83 | 26.67 | 454.00 | 24.49 | 9.83 | 24.54 |
March | 19.50 | 26.29 | 513.33 | 24.46 | 19.50 | 24.52 |
April | 27.17 | 26.44 | 485.00 | 24.59 | 27.17 | 24.68 |
May | 45.67 | 26.55 | 507.50 | 24.69 | 45.67 | 24.83 |
June | 46.00 | 26.62 | 496.00 | 24.68 | 46.00 | 24.83 |
July | 31.67 | 26.72 | 497.00 | 24.68 | 31.67 | 24.80 |
August | 38.00 | 26.17 | 514.00 | 24.53 | 38.00 | 24.63 |
September | 18.17 | 26.36 | 484.50 | 24.52 | 18.17 | 24.58 |
October | 20.33 | 26.43 | 500.50 | 24.56 | 20.33 | 24.63 |
November | 8.83 | 26.46 | 486.17 | 24.50 | 8.83 | 24.53 |
December | 5.17 | 25.64 | 484.83 | 24.43 | 4.50 | 24.44 |
Annual Sum or Average | 271.67 | 26.46 | 5917.83 | 24.55 | 271.00 | 24.63 |
Minimum of Months | 1.33 | 25.64 | 454.00 | 24.43 | 1.33 | 24.44 |
Maximum of Months | 46.00 | 26.72 | 514.00 | 24.69 | 46.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 26.84 | 426.67 | 24.79 | 30.00 | 24.92 |
February | 47.67 | 26.80 | 385.00 | 24.90 | 47.67 | 25.09 |
March | 46.33 | 26.78 | 432.67 | 24.78 | 46.33 | 24.95 |
April | 56.17 | 26.80 | 410.00 | 24.93 | 56.17 | 25.13 |
May | 56.50 | 26.70 | 429.83 | 24.89 | 56.50 | 25.08 |
June | 49.17 | 26.66 | 418.00 | 24.82 | 49.17 | 24.99 |
July | 47.33 | 26.76 | 422.00 | 24.89 | 47.33 | 25.06 |
August | 49.50 | 26.46 | 433.00 | 24.73 | 49.50 | 24.89 |
September | 50.67 | 26.74 | 410.00 | 24.86 | 50.67 | 25.05 |
October | 54.50 | 26.69 | 426.67 | 24.89 | 54.50 | 25.07 |
November | 44.17 | 26.75 | 416.33 | 24.86 | 44.17 | 25.03 |
December | 41.33 | 26.76 | 417.83 | 24.83 | 41.33 | 24.99 |
Annual Sum or Average | 573.33 | 26.72 | 5028.00 | 24.85 | 573.33 | 25.02 |
Minimum of Months | 30.00 | 26.46 | 385.00 | 24.73 | 30.00 | 24.89 |
Maximum of Months | 56.50 | 26.84 | 433.00 | 24.93 | 56.50 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.33 | 26.96 | 501.67 | 24.83 | 44.33 | 24.99 |
February | 38.50 | 26.90 | 454.00 | 24.77 | 38.50 | 24.93 |
March | 35.33 | 26.58 | 513.50 | 24.57 | 35.33 | 24.69 |
April | 25.50 | 26.39 | 485.00 | 24.57 | 25.50 | 24.66 |
May | 31.67 | 26.32 | 507.33 | 24.58 | 31.67 | 24.68 |
June | 29.67 | 26.29 | 496.00 | 24.54 | 29.67 | 24.64 |
July | 10.83 | 26.62 | 497.00 | 24.54 | 10.83 | 24.59 |
August | 31.83 | 25.98 | 513.83 | 24.48 | 31.83 | 24.56 |
September | 25.33 | 26.46 | 484.67 | 24.56 | 25.33 | 24.65 |
October | 45.83 | 26.67 | 501.17 | 24.72 | 45.83 | 24.87 |
November | 44.17 | 26.85 | 488.83 | 24.78 | 44.17 | 24.93 |
December | 48.00 | 26.93 | 493.00 | 24.84 | 48.00 | 25.01 |
Annual Sum or Average | 411.00 | 26.62 | 5936.00 | 24.65 | 411.00 | 24.77 |
Minimum of Months | 10.83 | 25.98 | 454.00 | 24.48 | 10.83 | 24.56 |
Maximum of Months | 48.00 | 26.96 | 513.83 | 24.84 | 48.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.33 | 26.87 | 497.33 | 24.64 | 28.33 | 24.75 |
February | 28.83 | 26.82 | 454.00 | 24.65 | 28.83 | 24.78 |
March | 34.50 | 26.64 | 514.00 | 24.60 | 34.50 | 24.72 |
April | 43.83 | 26.69 | 485.00 | 24.73 | 43.83 | 24.88 |
May | 49.17 | 26.56 | 507.67 | 24.71 | 49.17 | 24.86 |
June | 44.33 | 26.55 | 496.00 | 24.67 | 44.33 | 24.81 |
July | 31.83 | 26.79 | 497.00 | 24.70 | 31.83 | 24.82 |
August | 46.50 | 26.28 | 514.00 | 24.59 | 46.50 | 24.72 |
September | 32.83 | 26.62 | 485.00 | 24.64 | 32.83 | 24.76 |
October | 42.50 | 26.62 | 501.50 | 24.71 | 42.50 | 24.84 |
November | 31.67 | 26.75 | 488.67 | 24.66 | 31.67 | 24.78 |
December | 32.17 | 26.70 | 489.33 | 24.63 | 31.83 | 24.75 |
Annual Sum or Average | 446.50 | 26.63 | 5929.50 | 24.66 | 446.17 | 24.79 |
Minimum of Months | 28.33 | 26.28 | 454.00 | 24.59 | 28.33 | 24.72 |
Maximum of Months | 49.17 | 26.87 | 514.00 | 24.73 | 49.17 | 24.88 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50873 | 46.81546 | 0.58544 | 12.53374 |
February | 454.00000 | 24.46843 | 47.00918 | 0.57866 | 12.32265 |
March | 514.00000 | 24.40151 | 47.22008 | 0.56417 | 11.93198 |
April | 485.00000 | 24.43499 | 47.15324 | 0.56974 | 12.08255 |
May | 508.00000 | 24.43578 | 47.10906 | -0.2693 | 7.07234 |
June | 496.00000 | 24.41624 | 47.07583 | -0.2717 | 7.09295 |
July | 497.00000 | 24.48969 | 47.01825 | -0.2588 | 7.04845 |
August | 514.00000 | 24.43056 | 47.31647 | -0.2756 | 7.20291 |
September | 485.00000 | 24.44108 | 47.32613 | -0.2713 | 7.10132 |
October | 502.00000 | 24.49379 | 47.18568 | 0.57938 | 12.38257 |
November | 489.00000 | 24.50141 | 47.09211 | 0.58249 | 12.45479 |
December | 497.00000 | 24.49084 | 47.09441 | 0.57933 | 12.35392 |
Annual Sum or Average | 5943.00000 | 24.45917 | 47.11897 | 0.22095 | 10.11041 |
Minimum of Months | 454.00000 | 24.40151 | 46.81546 | -0.2756 | 7.04845 |
Maximum of Months | 514.00000 | 24.50873 | 47.32613 | 0.58544 | 12.53374 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32998 | 48.00332 | 0.53304 | 11.15719 |
February | 454.00000 | 24.29935 | 48.13688 | 0.52896 | 11.02975 |
March | 514.00000 | 24.25535 | 48.36215 | 0.52011 | 10.81216 |
April | 485.00000 | 24.27661 | 48.30087 | 0.52479 | 10.92674 |
May | 508.00000 | 24.29253 | 48.24329 | -0.3309 | 7.63025 |
June | 496.00000 | 24.27976 | 48.21142 | -0.3320 | 7.63246 |
July | 497.00000 | 24.30656 | 48.28969 | -0.3333 | 7.70333 |
August | 514.00000 | 24.26490 | 48.60460 | -0.3472 | 7.86913 |
September | 485.00000 | 24.27129 | 48.57975 | -0.3435 | 7.81147 |
October | 502.00000 | 24.31944 | 48.41036 | 0.52947 | 11.08133 |
November | 489.00000 | 24.31985 | 48.31358 | 0.53040 | 11.08189 |
December | 497.00000 | 24.29535 | 48.25135 | 0.52202 | 10.87551 |
Annual Sum or Average | 5943.00000 | 24.29244 | 48.31037 | 0.16334 | 9.62074 |
Minimum of Months | 454.00000 | 24.25535 | 48.00332 | -0.3472 | 7.63025 |
Maximum of Months | 514.00000 | 24.32998 | 48.60460 | 0.53304 | 11.15719 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32701 | 47.76260 | 0.53719 | 11.25293 |
February | 454.00000 | 24.31055 | 47.88381 | 0.53859 | 11.26708 |
March | 514.00000 | 24.28136 | 48.13215 | 0.53629 | 11.19985 |
April | 485.00000 | 24.33153 | 48.11426 | 0.54992 | 11.54842 |
May | 508.00000 | 24.33173 | 48.13245 | -0.3021 | 7.35840 |
June | 496.00000 | 24.31936 | 48.10850 | -0.3014 | 7.32529 |
July | 497.00000 | 24.35456 | 48.10336 | -0.3060 | 7.41108 |
August | 514.00000 | 24.27422 | 48.58588 | -0.3320 | 7.65660 |
September | 485.00000 | 24.30027 | 48.48272 | -0.3199 | 7.55122 |
October | 502.00000 | 24.34880 | 48.35139 | 0.54278 | 11.43202 |
November | 489.00000 | 24.31566 | 48.27945 | 0.53646 | 11.22155 |
December | 497.00000 | 24.28317 | 48.13080 | 0.52373 | 10.93242 |
Annual Sum or Average | 5943.00000 | 24.31473 | 48.17453 | 0.18018 | 9.66416 |
Minimum of Months | 454.00000 | 24.27422 | 47.76260 | -0.3320 | 7.32529 |
Maximum of Months | 514.00000 | 24.35456 | 48.58588 | 0.54992 | 11.54842 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41476 | 49.25691 | 0.59049 | 12.82045 |
February | 454.00000 | 24.43485 | 49.13629 | 0.60563 | 13.25497 |
March | 514.00000 | 24.39381 | 49.94492 | 0.61082 | 13.33686 |
April | 485.00000 | 24.51136 | 49.84617 | 0.64912 | 14.51814 |
May | 508.00000 | 24.52908 | 49.74905 | -0.1415 | 6.94710 |
June | 496.00000 | 24.50710 | 49.43902 | -0.1245 | 6.79066 |
July | 497.00000 | 24.56009 | 48.99345 | -0.1569 | 7.00385 |
August | 514.00000 | 24.40068 | 51.16353 | -0.2122 | 7.00091 |
September | 485.00000 | 24.45115 | 50.04436 | -0.2101 | 7.03107 |
October | 502.00000 | 24.48837 | 50.25000 | 0.61604 | 13.66705 |
November | 489.00000 | 24.44639 | 49.79426 | 0.60255 | 13.16633 |
December | 497.00000 | 24.38203 | 49.73028 | 0.57830 | 12.56234 |
Annual Sum or Average | 5943.00000 | 24.45983 | 49.78737 | 0.28082 | 10.64773 |
Minimum of Months | 454.00000 | 24.38203 | 48.99345 | -0.2122 | 6.79066 |
Maximum of Months | 514.00000 | 24.56009 | 51.16353 | 0.64912 | 14.51814 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54127 | 48.70533 | 0.65388 | 14.69503 |
February | 454.00000 | 24.54875 | 48.52131 | 0.67274 | 15.30628 |
March | 514.00000 | 24.46809 | 49.29662 | 0.67207 | 15.21936 |
April | 485.00000 | 24.57944 | 49.23536 | 0.70674 | 16.38670 |
May | 508.00000 | 24.55376 | 49.67904 | -0.1082 | 7.03995 |
June | 496.00000 | 24.51073 | 49.51742 | -0.1098 | 6.75437 |
July | 497.00000 | 24.57764 | 49.09261 | -0.1361 | 6.98713 |
August | 514.00000 | 24.44006 | 50.92838 | -0.1630 | 6.91460 |
September | 485.00000 | 24.53268 | 49.61632 | -0.1400 | 7.07339 |
October | 502.00000 | 24.55352 | 49.92652 | 0.65865 | 14.99804 |
November | 489.00000 | 24.54408 | 49.39513 | 0.65260 | 14.71288 |
December | 497.00000 | 24.51984 | 49.14068 | 0.64068 | 14.42402 |
Annual Sum or Average | 5943.00000 | 24.53021 | 49.43199 | 0.33002 | 11.67296 |
Minimum of Months | 454.00000 | 24.44006 | 48.52131 | -0.1630 | 6.75437 |
Maximum of Months | 514.00000 | 24.57944 | 50.92838 | 0.70674 | 16.38670 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58563 | 48.09612 | 0.68652 | 15.80433 |
February | 454.00000 | 24.54764 | 48.25257 | 0.67738 | 15.47363 |
March | 514.00000 | 24.42838 | 49.54778 | 0.63917 | 14.19327 |
April | 485.00000 | 24.50290 | 49.91864 | 0.64470 | 14.38320 |
May | 508.00000 | 24.48797 | 50.13442 | -0.1779 | 6.93227 |
June | 496.00000 | 24.45545 | 50.06043 | -0.1849 | 6.88241 |
July | 497.00000 | 24.51767 | 49.39923 | -0.1965 | 7.10833 |
August | 514.00000 | 24.37846 | 51.39159 | -0.2308 | 7.06155 |
September | 485.00000 | 24.46349 | 49.92338 | -0.1975 | 6.99903 |
October | 502.00000 | 24.53885 | 49.73552 | 0.64871 | 14.69136 |
November | 489.00000 | 24.55380 | 48.89776 | 0.66661 | 15.17878 |
December | 497.00000 | 24.57355 | 48.40984 | 0.67842 | 15.67354 |
Annual Sum or Average | 5943.00000 | 24.50201 | 49.49432 | 0.30086 | 11.66238 |
Minimum of Months | 454.00000 | 24.37846 | 48.09612 | -0.2308 | 6.88241 |
Maximum of Months | 514.00000 | 24.58563 | 51.39159 | 0.68652 | 15.80433 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.48529 | 49.07709 | 0.64136 | 14.41856 |
February | 454.00000 | 24.50098 | 48.92000 | 0.65932 | 14.91662 |
March | 514.00000 | 24.45880 | 49.68024 | 0.66928 | 15.16651 |
April | 485.00000 | 24.57000 | 49.68868 | 0.70102 | 16.21569 |
May | 508.00000 | 24.53843 | 50.03653 | -0.1198 | 7.01441 |
June | 496.00000 | 24.50645 | 49.89551 | -0.1188 | 6.88698 |
July | 497.00000 | 24.57015 | 49.33930 | -0.1445 | 7.07961 |
August | 514.00000 | 24.42968 | 51.28384 | -0.1733 | 6.96201 |
September | 485.00000 | 24.50580 | 49.98304 | -0.1560 | 7.03859 |
October | 502.00000 | 24.53994 | 50.19450 | 0.65313 | 14.81822 |
November | 489.00000 | 24.50630 | 49.68071 | 0.64313 | 14.42676 |
December | 497.00000 | 24.45048 | 49.56478 | 0.62540 | 14.02177 |
Annual Sum or Average | 5943.00000 | 24.50481 | 49.78904 | 0.32006 | 11.54682 |
Minimum of Months | 454.00000 | 24.42968 | 48.92000 | -0.1733 | 6.88698 |
Maximum of Months | 514.00000 | 24.57015 | 51.28384 | 0.70102 | 16.21569 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.43360 | 48.27196 | 0.58607 | 12.52637 |
February | 454.00000 | 24.45247 | 48.23818 | 0.59849 | 12.90578 |
March | 514.00000 | 24.39017 | 48.79712 | 0.59364 | 12.73400 |
April | 485.00000 | 24.49228 | 48.54813 | 0.62632 | 13.69490 |
May | 508.00000 | 24.54315 | 48.20990 | -0.1528 | 6.67645 |
June | 496.00000 | 24.53521 | 47.90996 | -0.1294 | 6.52014 |
July | 497.00000 | 24.59084 | 47.73669 | -0.1519 | 6.66085 |
August | 514.00000 | 24.44493 | 49.20569 | -0.2068 | 6.79040 |
September | 485.00000 | 24.47373 | 48.56368 | -0.2124 | 6.78471 |
October | 502.00000 | 24.49225 | 48.79125 | 0.60584 | 13.19367 |
November | 489.00000 | 24.47011 | 48.53576 | 0.59857 | 12.91031 |
December | 497.00000 | 24.42294 | 48.69479 | 0.58148 | 12.42486 |
Annual Sum or Average | 5943.00000 | 24.47839 | 48.46255 | 0.27495 | 10.29164 |
Minimum of Months | 454.00000 | 24.39017 | 47.73669 | -0.2124 | 6.52014 |
Maximum of Months | 514.00000 | 24.59084 | 49.20569 | 0.62632 | 13.69490 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.57071 | 47.75640 | 0.65462 | 14.55508 |
February | 454.00000 | 24.58581 | 47.63931 | 0.67332 | 15.18281 |
March | 514.00000 | 24.49963 | 48.14483 | 0.66625 | 14.92272 |
April | 485.00000 | 24.59642 | 47.95661 | 0.69448 | 15.85391 |
May | 508.00000 | 24.57375 | 48.15777 | -0.1158 | 6.73491 |
June | 496.00000 | 24.53491 | 48.03297 | -0.1152 | 6.49649 |
July | 497.00000 | 24.61058 | 47.84292 | -0.1304 | 6.64597 |
August | 514.00000 | 24.49075 | 49.00173 | -0.1536 | 6.64714 |
September | 485.00000 | 24.57043 | 48.17308 | -0.1350 | 6.75930 |
October | 502.00000 | 24.58675 | 48.45851 | 0.65624 | 14.76762 |
November | 489.00000 | 24.58656 | 48.14027 | 0.65481 | 14.64715 |
December | 497.00000 | 24.56723 | 48.15689 | 0.64755 | 14.43347 |
Annual Sum or Average | 5943.00000 | 24.56385 | 48.12811 | 0.32977 | 11.43359 |
Minimum of Months | 454.00000 | 24.49075 | 47.63931 | -0.1536 | 6.49649 |
Maximum of Months | 514.00000 | 24.61058 | 49.00173 | 0.69448 | 15.85391 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.94266 | 52.34383 | 0.79628 | 19.17699 |
February | 454.00000 | 24.94556 | 52.37815 | 0.79163 | 19.01978 |
March | 514.00000 | 24.70321 | 54.97640 | 0.72988 | 16.83201 |
April | 485.00000 | 24.65701 | 57.06111 | 0.71816 | 16.41080 |
May | 508.00000 | 24.67601 | 59.90827 | -0.0611 | 6.20911 |
June | 496.00000 | 24.66067 | 59.93206 | -0.0613 | 6.22497 |
July | 497.00000 | 24.62194 | 56.88142 | -0.1109 | 6.18040 |
August | 514.00000 | 24.53099 | 61.80981 | -0.1081 | 6.17679 |
September | 485.00000 | 24.61347 | 58.95106 | -0.0883 | 6.16855 |
October | 502.00000 | 24.68908 | 58.67651 | 0.74473 | 17.33390 |
November | 489.00000 | 24.82579 | 56.06347 | 0.77890 | 18.51197 |
December | 497.00000 | 24.88727 | 52.90614 | 0.78362 | 18.80708 |
Annual Sum or Average | 5943.00000 | 24.72757 | 56.86439 | 0.40583 | 13.03280 |
Minimum of Months | 454.00000 | 24.53099 | 52.34383 | -0.1109 | 6.16855 |
Maximum of Months | 514.00000 | 24.94556 | 61.80981 | 0.79628 | 19.17699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54546 | 47.92490 | 0.64765 | 14.39023 |
February | 454.00000 | 24.55856 | 47.85135 | 0.66370 | 14.87444 |
March | 514.00000 | 24.49929 | 48.33812 | 0.66480 | 14.88381 |
April | 485.00000 | 24.59415 | 48.19723 | 0.68977 | 15.70454 |
May | 508.00000 | 24.56847 | 48.34558 | -0.1244 | 6.69378 |
June | 496.00000 | 24.53673 | 48.22776 | -0.1217 | 6.58473 |
July | 497.00000 | 24.61209 | 47.97160 | -0.1351 | 6.70161 |
August | 514.00000 | 24.49278 | 49.19963 | -0.1598 | 6.69263 |
September | 485.00000 | 24.55368 | 48.38211 | -0.1478 | 6.70584 |
October | 502.00000 | 24.57963 | 48.59193 | 0.65232 | 14.63127 |
November | 489.00000 | 24.56392 | 48.29226 | 0.64801 | 14.42616 |
December | 497.00000 | 24.53274 | 48.36342 | 0.63872 | 14.16671 |
Annual Sum or Average | 5943.00000 | 24.55271 | 48.31319 | 0.32306 | 11.33662 |
Minimum of Months | 454.00000 | 24.49278 | 47.85135 | -0.1598 | 6.58473 |
Maximum of Months | 514.00000 | 24.61209 | 49.19963 | 0.68977 | 15.70454 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42649 | 49.09199 | 0.58489 | 12.57506 |
February | 454.00000 | 24.44676 | 48.99159 | 0.59736 | 12.95890 |
March | 514.00000 | 24.38754 | 49.71130 | 0.59529 | 12.84927 |
April | 485.00000 | 24.48706 | 49.60194 | 0.62696 | 13.79779 |
May | 508.00000 | 24.52159 | 49.42562 | -0.1650 | 6.89975 |
June | 496.00000 | 24.50095 | 49.12433 | -0.1497 | 6.74889 |
July | 497.00000 | 24.55180 | 48.79594 | -0.1769 | 6.92136 |
August | 514.00000 | 24.40639 | 50.70399 | -0.2272 | 7.03441 |
September | 485.00000 | 24.44540 | 49.76401 | -0.2298 | 7.03045 |
October | 502.00000 | 24.48196 | 49.91515 | 0.60419 | 13.24055 |
November | 489.00000 | 24.45800 | 49.50553 | 0.59533 | 12.90870 |
December | 497.00000 | 24.40380 | 49.50574 | 0.57566 | 12.35654 |
Annual Sum or Average | 5943.00000 | 24.45962 | 49.51838 | 0.26606 | 10.41741 |
Minimum of Months | 454.00000 | 24.38754 | 48.79594 | -0.2298 | 6.74889 |
Maximum of Months | 514.00000 | 24.55180 | 50.70399 | 0.62696 | 13.79779 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.64778 | 48.41429 | 0.65657 | 14.79585 |
February | 385.00000 | 24.66523 | 48.23352 | 0.67470 | 15.42433 |
March | 433.00000 | 24.56201 | 49.03256 | 0.66473 | 15.06889 |
April | 410.00000 | 24.67676 | 48.95493 | 0.69746 | 16.16109 |
May | 430.00000 | 24.64955 | 49.33431 | -0.1167 | 7.15660 |
June | 418.00000 | 24.60054 | 49.22019 | -0.1230 | 6.88901 |
July | 422.00000 | 24.67687 | 48.77214 | -0.1402 | 7.04503 |
August | 433.00000 | 24.53195 | 50.59445 | -0.1690 | 7.07540 |
September | 410.00000 | 24.63297 | 49.23886 | -0.1450 | 7.18729 |
October | 427.00000 | 24.65569 | 49.53669 | 0.65874 | 15.03320 |
November | 417.00000 | 24.65897 | 48.99871 | 0.65656 | 14.88359 |
December | 422.00000 | 24.63566 | 48.80345 | 0.64717 | 14.62112 |
Annual Sum or Average | 5034.00000 | 24.63218 | 49.10411 | 0.32750 | 11.74875 |
Minimum of Months | 385.00000 | 24.53195 | 48.23352 | -0.1690 | 6.88901 |
Maximum of Months | 433.00000 | 24.67687 | 50.59445 | 0.69746 | 16.16109 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.64638 | 47.80770 | 0.68844 | 15.78311 |
February | 454.00000 | 24.59153 | 48.01519 | 0.67386 | 15.28671 |
March | 514.00000 | 24.43032 | 49.28585 | 0.62463 | 13.72770 |
April | 485.00000 | 24.47656 | 49.67249 | 0.62230 | 13.65695 |
May | 508.00000 | 24.47386 | 49.81943 | -0.2025 | 6.92129 |
June | 496.00000 | 24.43942 | 49.76430 | -0.2113 | 6.89706 |
July | 497.00000 | 24.49797 | 49.21517 | -0.2186 | 7.03545 |
August | 514.00000 | 24.38241 | 50.92978 | -0.2458 | 7.10956 |
September | 485.00000 | 24.45902 | 49.63312 | -0.2173 | 6.98489 |
October | 502.00000 | 24.54057 | 49.38409 | 0.63773 | 14.28745 |
November | 489.00000 | 24.58849 | 48.54222 | 0.66243 | 14.99392 |
December | 497.00000 | 24.63618 | 48.08285 | 0.68156 | 15.65984 |
Annual Sum or Average | 5943.00000 | 24.51254 | 49.19213 | 0.28759 | 11.49348 |
Minimum of Months | 454.00000 | 24.38241 | 47.80770 | -0.2458 | 6.89706 |
Maximum of Months | 514.00000 | 24.64638 | 50.92978 | 0.68844 | 15.78311 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50641 | 48.86588 | 0.63652 | 14.17643 |
February | 454.00000 | 24.51611 | 48.74309 | 0.65076 | 14.58061 |
March | 514.00000 | 24.46040 | 49.40725 | 0.65428 | 14.65039 |
April | 485.00000 | 24.55677 | 49.39619 | 0.68020 | 15.49267 |
May | 508.00000 | 24.53246 | 49.69211 | -0.1430 | 6.92196 |
June | 496.00000 | 24.49799 | 49.56684 | -0.1441 | 6.81739 |
July | 497.00000 | 24.56334 | 49.12315 | -0.1639 | 6.96628 |
August | 514.00000 | 24.43975 | 50.79710 | -0.1874 | 6.95223 |
September | 485.00000 | 24.50578 | 49.67422 | -0.1750 | 6.96869 |
October | 502.00000 | 24.54211 | 49.82966 | 0.64223 | 14.41193 |
November | 489.00000 | 24.52602 | 49.35711 | 0.63664 | 14.18172 |
December | 497.00000 | 24.48270 | 49.29440 | 0.62362 | 13.83929 |
Annual Sum or Average | 5943.00000 | 24.51040 | 49.48790 | 0.30592 | 11.29757 |
Minimum of Months | 454.00000 | 24.43975 | 48.74309 | -0.1874 | 6.81739 |
Maximum of Months | 514.00000 | 24.56334 | 50.79710 | 0.68020 | 15.49267 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.994608E+11 | 0.232160E+11 | 460.25 | 0.674484E+11 | 0.320124E+11 | 0.00 | 1.00 | 01-JAN-00:43 | 0.00 | 01-JAN-00:03 | 105622.73 | 09-JAN-07:03 | 77232.87 | 02-JAN-07:03 | 34919.79 | 27-JAN-06:12 | 22813.70 | 12-JAN-13:02 | 0.00 |
February | 0.940382E+11 | 0.222878E+11 | 420.42 | 0.638633E+11 | 0.301750E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 104332.26 | 16-FEB-07:03 | 78197.14 | 21-FEB-07:03 | 35827.43 | 10-FEB-05:03 | 25909.81 | 13-FEB-15:05 | 0.00 |
March | 0.114021E+12 | 0.273410E+11 | 485.91 | 0.754350E+11 | 0.385862E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 118514.27 | 28-MAR-04:02 | 78775.60 | 27-MAR-06:03 | 42659.68 | 25-MAR-04:03 | 26487.27 | 28-MAR-04:02 | 0.00 |
April | 0.119333E+12 | 0.284574E+11 | 466.91 | 0.720337E+11 | 0.472992E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 118704.72 | 12-APR-04:02 | 79651.05 | 03-APR-06:03 | 45061.07 | 30-APR-17:22 | 26716.79 | 11-APR-16:00 | 0.00 |
May | 0.137213E+12 | 0.324135E+11 | 495.62 | 0.769039E+11 | 0.603096E+11 | 0.00 | 1.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:23 | 120618.82 | 06-MAY-04:03 | 79140.19 | 30-MAY-04:02 | 56852.96 | 04-MAY-06:07 | 29649.23 | 04-MAY-13:00 | 0.00 |
June | 0.137471E+12 | 0.326176E+11 | 477.41 | 0.777743E+11 | 0.596969E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 121712.79 | 10-JUN-04:03 | 78597.63 | 12-JUN-06:03 | 53211.18 | 16-JUN-06:07 | 30903.99 | 13-JUN-15:00 | 0.00 |
July | 0.110619E+12 | 0.254012E+11 | 471.17 | 0.673999E+11 | 0.432190E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 108706.79 | 28-JUL-06:03 | 78159.45 | 03-JUL-06:03 | 39300.24 | 01-JUL-04:03 | 24563.71 | 17-JUL-14:05 | 0.00 |
August | 0.128749E+12 | 0.295125E+11 | 479.36 | 0.710968E+11 | 0.576523E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 120004.07 | 12-AUG-05:03 | 78125.76 | 14-AUG-06:03 | 55654.13 | 13-AUG-14:42 | 28366.39 | 13-AUG-14:42 | 0.00 |
September | 0.117557E+12 | 0.269746E+11 | 457.82 | 0.660791E+11 | 0.514778E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 117812.18 | 25-SEP-06:03 | 79759.14 | 05-SEP-04:02 | 52153.05 | 04-SEP-14:32 | 27274.95 | 05-SEP-12:02 | 0.00 |
October | 0.114221E+12 | 0.258488E+11 | 464.25 | 0.645524E+11 | 0.496682E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 115785.04 | 03-OCT-06:03 | 78610.11 | 16-OCT-06:03 | 45054.62 | 16-OCT-12:03 | 25540.35 | 16-OCT-14:05 | 0.00 |
November | 0.106356E+12 | 0.242793E+11 | 445.67 | 0.641928E+11 | 0.421633E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 115649.43 | 14-NOV-07:03 | 79733.24 | 13-NOV-07:03 | 45281.25 | 10-NOV-13:02 | 25579.20 | 14-NOV-07:03 | 0.00 |
December | 0.973988E+11 | 0.224084E+11 | 446.14 | 0.634321E+11 | 0.339667E+11 | 0.00 | 1.00 | 01-DEC-06:12 | 0.00 | 01-DEC-00:10 | 108992.31 | 11-DEC-07:03 | 76752.52 | 11-DEC-07:03 | 45562.15 | 30-DEC-05:03 | 24088.40 | 11-DEC-13:02 | 0.00 |
Annual Sum or Average | 0.137644E+13 | 0.320758E+12 | 5570.91 | 0.830212E+12 | 0.546226E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.940382E+11 | 0.222878E+11 | 420.42 | 0.634321E+11 | 0.301750E+11 | 0.00 | 1.00 | 0.00 | 104332.26 | 76752.52 | 34919.79 | 22813.70 | 0.00 | ||||||
Maximum of Months | 0.137471E+12 | 0.326176E+11 | 495.62 | 0.777743E+11 | 0.603096E+11 | 0.00 | 1.00 | 0.00 | 121712.79 | 79759.14 | 56852.96 | 30903.99 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.847624E+11 | 0.197242E+11 | 443.67 | 0.557891E+11 | 0.289733E+11 | 0.00 | 1.00 | 01-JAN-05:33 | 0.00 | 01-JAN-00:03 | 100585.22 | 09-JAN-05:03 | 69052.82 | 02-JAN-07:03 | 41336.67 | 02-JAN-07:05 | 21523.46 | 04-JAN-13:02 | 0.00 |
February | 0.812261E+11 | 0.191747E+11 | 408.06 | 0.534429E+11 | 0.277832E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 109046.48 | 06-FEB-06:02 | 70367.52 | 21-FEB-05:02 | 39851.35 | 06-FEB-06:02 | 24178.88 | 26-FEB-13:22 | 0.00 |
March | 0.986951E+11 | 0.235237E+11 | 473.88 | 0.632061E+11 | 0.354890E+11 | 0.00 | 1.00 | 01-MAR-05:02 | 0.00 | 01-MAR-00:10 | 110148.33 | 28-MAR-04:02 | 71439.11 | 20-MAR-04:02 | 42373.22 | 28-MAR-04:02 | 24494.59 | 19-MAR-15:32 | 0.00 |
April | 0.104705E+12 | 0.247219E+11 | 455.39 | 0.604858E+11 | 0.442188E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 110362.28 | 12-APR-04:02 | 70938.22 | 03-APR-04:02 | 48443.46 | 30-APR-17:22 | 27602.35 | 02-APR-14:52 | 0.00 |
May | 0.119274E+12 | 0.279500E+11 | 478.98 | 0.638780E+11 | 0.553962E+11 | 0.00 | 1.00 | 01-MAY-00:50 | 0.00 | 01-MAY-00:05 | 114300.86 | 22-MAY-04:02 | 70828.07 | 08-MAY-06:03 | 54412.10 | 22-MAY-04:04 | 28129.14 | 14-MAY-15:31 | 0.00 |
June | 0.119807E+12 | 0.281629E+11 | 464.57 | 0.645844E+11 | 0.552228E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 113499.59 | 10-JUN-05:03 | 70308.53 | 12-JUN-06:03 | 54007.27 | 10-JUN-04:03 | 28198.40 | 11-JUN-13:52 | 0.00 |
July | 0.941970E+11 | 0.214490E+11 | 453.53 | 0.545493E+11 | 0.396476E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 104831.34 | 10-JUL-04:02 | 69602.77 | 24-JUL-04:02 | 40143.85 | 04-JUL-16:52 | 22686.67 | 10-JUL-04:02 | 0.00 |
August | 0.109936E+12 | 0.249782E+11 | 462.94 | 0.571265E+11 | 0.528095E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 114683.31 | 21-AUG-05:03 | 69468.48 | 14-AUG-06:03 | 59504.81 | 21-AUG-04:03 | 27688.91 | 13-AUG-12:53 | 0.00 |
September | 0.100969E+12 | 0.229649E+11 | 442.06 | 0.535618E+11 | 0.474072E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 113944.01 | 04-SEP-14:32 | 71086.83 | 05-SEP-04:02 | 53980.32 | 04-SEP-13:52 | 26893.08 | 04-SEP-15:11 | 0.00 |
October | 0.976034E+11 | 0.219256E+11 | 444.39 | 0.525080E+11 | 0.450954E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 111227.52 | 30-OCT-04:03 | 69713.26 | 16-OCT-04:02 | 47956.82 | 09-OCT-11:23 | 24108.90 | 09-OCT-12:02 | 0.00 |
November | 0.901309E+11 | 0.204693E+11 | 425.47 | 0.522555E+11 | 0.378754E+11 | 0.00 | 1.00 | 01-NOV-04:53 | 0.00 | 01-NOV-00:10 | 108594.44 | 13-NOV-05:02 | 71018.80 | 13-NOV-07:03 | 45817.47 | 13-NOV-05:04 | 23318.27 | 13-NOV-07:03 | 0.00 |
December | 0.830275E+11 | 0.190287E+11 | 431.86 | 0.519104E+11 | 0.311171E+11 | 0.00 | 1.00 | 01-DEC-06:12 | 0.00 | 01-DEC-00:10 | 103966.86 | 11-DEC-06:12 | 67828.61 | 26-DEC-07:03 | 39169.47 | 10-DEC-17:12 | 22189.20 | 11-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.118433E+13 | 0.274073E+12 | 5384.80 | 0.683298E+12 | 0.501035E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.812261E+11 | 0.190287E+11 | 408.06 | 0.519104E+11 | 0.277832E+11 | 0.00 | 1.00 | 0.00 | 100585.22 | 67828.61 | 39169.47 | 21523.46 | 0.00 | ||||||
Maximum of Months | 0.119807E+12 | 0.281629E+11 | 478.98 | 0.645844E+11 | 0.553962E+11 | 0.00 | 1.00 | 0.00 | 114683.31 | 71439.11 | 59504.81 | 28198.40 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.885651E+11 | 0.207330E+11 | 440.96 | 0.593379E+11 | 0.292271E+11 | 0.00 | 1.00 | 01-JAN-06:13 | 0.00 | 01-JAN-00:03 | 104670.97 | 02-JAN-07:03 | 74750.83 | 02-JAN-07:03 | 35765.46 | 09-JAN-05:03 | 22877.67 | 05-JAN-15:00 | 0.00 |
February | 0.855442E+11 | 0.203175E+11 | 407.78 | 0.574457E+11 | 0.280985E+11 | 0.00 | 1.00 | 01-FEB-06:12 | 0.00 | 01-FEB-00:10 | 118306.21 | 06-FEB-06:02 | 76513.77 | 21-FEB-05:02 | 44130.47 | 06-FEB-06:03 | 26106.00 | 05-FEB-14:32 | 0.00 |
March | 0.104931E+12 | 0.251506E+11 | 473.91 | 0.690609E+11 | 0.358701E+11 | 0.00 | 1.00 | 01-MAR-05:53 | 0.00 | 01-MAR-00:10 | 123178.46 | 13-MAR-04:02 | 81461.81 | 19-MAR-14:52 | 46810.86 | 28-MAR-04:02 | 28800.40 | 19-MAR-15:32 | 0.00 |
April | 0.111521E+12 | 0.264522E+11 | 459.31 | 0.666723E+11 | 0.448484E+11 | 0.00 | 1.00 | 01-APR-04:03 | 0.00 | 01-APR-00:10 | 127054.92 | 02-APR-15:32 | 81647.50 | 17-APR-04:02 | 53522.08 | 30-APR-17:22 | 31746.18 | 02-APR-14:52 | 0.00 |
May | 0.125795E+12 | 0.296082E+11 | 483.39 | 0.696093E+11 | 0.561856E+11 | 0.00 | 1.00 | 01-MAY-00:20 | 0.00 | 01-MAY-00:05 | 128415.57 | 22-MAY-04:02 | 80631.03 | 01-MAY-04:02 | 59159.42 | 13-MAY-05:03 | 31648.79 | 14-MAY-15:42 | 0.00 |
June | 0.126273E+12 | 0.298127E+11 | 466.10 | 0.705940E+11 | 0.556791E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:10 | 127893.00 | 10-JUN-05:03 | 80029.34 | 19-JUN-04:02 | 59963.23 | 10-JUN-05:03 | 32344.94 | 18-JUN-13:52 | 0.00 |
July | 0.992027E+11 | 0.227041E+11 | 456.53 | 0.589471E+11 | 0.402556E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 114202.74 | 10-JUL-04:02 | 79602.63 | 31-JUL-04:02 | 44180.67 | 02-JUL-11:43 | 26537.99 | 30-JUL-14:02 | 0.00 |
August | 0.114738E+12 | 0.261475E+11 | 463.47 | 0.614221E+11 | 0.533164E+11 | 0.00 | 1.00 | 01-AUG-04:02 | 0.00 | 01-AUG-00:10 | 127516.77 | 13-AUG-12:13 | 79415.14 | 14-AUG-04:02 | 58520.16 | 21-AUG-04:03 | 31172.59 | 13-AUG-12:53 | 0.00 |
September | 0.105813E+12 | 0.241474E+11 | 443.88 | 0.579026E+11 | 0.479108E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 125405.51 | 24-SEP-14:53 | 81452.80 | 05-SEP-04:02 | 57309.49 | 24-SEP-14:53 | 29342.77 | 04-SEP-16:02 | 0.00 |
October | 0.101479E+12 | 0.228790E+11 | 445.06 | 0.558442E+11 | 0.456344E+11 | 0.00 | 1.00 | 01-OCT-06:23 | 0.00 | 01-OCT-00:10 | 120560.78 | 09-OCT-12:02 | 79023.75 | 16-OCT-04:02 | 52384.52 | 09-OCT-15:23 | 28020.15 | 09-OCT-12:02 | 0.00 |
November | 0.938341E+11 | 0.213920E+11 | 426.53 | 0.555386E+11 | 0.382955E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 112768.11 | 13-NOV-05:02 | 73883.11 | 13-NOV-07:03 | 44931.98 | 11-NOV-15:43 | 24225.46 | 13-NOV-05:02 | 0.00 |
December | 0.868489E+11 | 0.200039E+11 | 433.81 | 0.552060E+11 | 0.316429E+11 | 0.00 | 1.00 | 01-DEC-08:70 | 0.00 | 01-DEC-00:10 | 100979.92 | 26-DEC-07:03 | 74554.72 | 26-DEC-07:03 | 44348.88 | 10-DEC-17:12 | 23529.77 | 31-DEC-16:12 | 0.00 |
Annual Sum or Average | 0.124455E+13 | 0.289348E+12 | 5400.71 | 0.737581E+12 | 0.506964E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.855442E+11 | 0.200039E+11 | 407.78 | 0.552060E+11 | 0.280985E+11 | 0.00 | 1.00 | 0.00 | 100979.92 | 73883.11 | 35765.46 | 22877.67 | 0.00 | ||||||
Maximum of Months | 0.126273E+12 | 0.298127E+11 | 483.39 | 0.705940E+11 | 0.561856E+11 | 0.00 | 1.00 | 0.00 | 128415.57 | 81647.50 | 59963.23 | 32344.94 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 399.04 | 0.00 | 399.04 | 906.55 | 208.59 | 0.00 | 0.00 | 0.00 |
February | 425.67 | 0.00 | 425.67 | 1016.95 | 158.52 | 0.00 | 0.00 | 0.00 |
March | 436.87 | 0.00 | 436.87 | 1108.56 | 105.99 | 0.00 | 0.00 | 0.00 |
April | 475.43 | 6.74 | 468.69 | 1242.19 | 47.15 | 0.00 | 0.00 | 0.00 |
May | 609.44 | 64.92 | 544.52 | 1586.31 | 57.10 | 0.00 | 0.00 | 0.00 |
June | 744.45 | 150.45 | 594.01 | 1884.69 | 65.43 | 0.00 | 0.00 | 0.00 |
July | 640.16 | 67.10 | 573.06 | 1477.60 | 114.73 | 0.00 | 0.00 | 0.00 |
August | 527.06 | 22.47 | 504.59 | 1237.13 | 86.63 | 0.00 | 0.00 | 0.00 |
September | 448.73 | 0.21 | 448.52 | 1086.32 | 87.84 | 0.00 | 0.00 | 0.00 |
October | 432.37 | 0.00 | 432.37 | 966.86 | 116.21 | 0.00 | 0.00 | 0.00 |
November | 409.12 | 0.00 | 409.12 | 923.99 | 140.47 | 0.00 | 0.00 | 0.00 |
December | 387.67 | 0.00 | 387.67 | 872.71 | 227.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 494.96 | 26.06 | 468.90 | 1192.93 | 118.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.67 | 0.00 | 387.67 | 872.71 | 47.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.45 | 150.45 | 594.01 | 1884.69 | 227.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.98 | 172.89 | 340.09 | 1071.39 | 133.36 | 0.00 | 0.00 | 0.00 |
February | 581.72 | 213.29 | 368.43 | 1245.47 | 99.77 | 0.00 | 0.00 | 0.00 |
March | 634.18 | 248.34 | 385.84 | 1393.43 | 65.94 | 0.00 | 0.00 | 0.00 |
April | 640.94 | 244.87 | 396.07 | 1445.61 | 30.10 | 0.00 | 0.00 | 0.00 |
May | 550.94 | 166.77 | 384.17 | 1295.12 | 37.55 | 0.00 | 0.00 | 0.00 |
June | 586.80 | 193.26 | 393.54 | 1362.00 | 42.12 | 0.00 | 0.00 | 0.00 |
July | 501.21 | 112.28 | 388.93 | 1091.52 | 74.99 | 0.00 | 0.00 | 0.00 |
August | 551.59 | 162.14 | 389.45 | 1185.22 | 58.03 | 0.00 | 0.00 | 0.00 |
September | 518.01 | 141.16 | 376.85 | 1142.55 | 60.15 | 0.00 | 0.00 | 0.00 |
October | 485.49 | 124.21 | 361.29 | 1017.69 | 79.12 | 0.00 | 0.00 | 0.00 |
November | 469.86 | 129.84 | 340.01 | 990.01 | 94.57 | 0.00 | 0.00 | 0.00 |
December | 480.82 | 154.30 | 326.52 | 999.58 | 148.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 542.44 | 171.55 | 370.89 | 1185.62 | 77.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 469.86 | 112.28 | 326.52 | 990.01 | 30.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 640.94 | 248.34 | 396.07 | 1445.61 | 148.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1056.52 | 440.79 | 615.73 | 2234.13 | 211.89 | 0.00 | 0.00 | 0.00 |
February | 897.15 | 292.50 | 604.64 | 2044.30 | 156.94 | 0.00 | 0.00 | 0.00 |
March | 612.25 | 82.23 | 530.03 | 1546.72 | 100.65 | 0.00 | 0.00 | 0.00 |
April | 456.46 | 0.20 | 456.26 | 1209.21 | 42.16 | 0.00 | 0.00 | 0.00 |
May | 456.77 | 0.00 | 456.77 | 1242.52 | 52.46 | 0.00 | 0.00 | 0.00 |
June | 455.13 | 0.00 | 455.13 | 1234.79 | 58.03 | 0.00 | 0.00 | 0.00 |
July | 468.85 | 0.00 | 468.85 | 1097.30 | 108.84 | 0.00 | 0.00 | 0.00 |
August | 456.43 | 0.71 | 455.73 | 1078.62 | 80.19 | 0.00 | 0.00 | 0.00 |
September | 505.30 | 16.50 | 488.80 | 1216.69 | 88.07 | 0.00 | 0.00 | 0.00 |
October | 661.08 | 105.40 | 555.68 | 1459.86 | 122.08 | 0.00 | 0.00 | 0.00 |
November | 859.63 | 262.26 | 597.37 | 1848.67 | 149.30 | 0.00 | 0.00 | 0.00 |
December | 1055.98 | 449.28 | 606.70 | 2199.48 | 236.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 660.88 | 136.96 | 523.92 | 1531.89 | 117.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.13 | 0.00 | 455.13 | 1078.62 | 42.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1056.52 | 449.28 | 615.73 | 2234.13 | 236.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.76 | 182.76 | 336.99 | 1099.74 | 148.97 | 0.00 | 0.00 | 0.00 |
February | 570.84 | 202.01 | 368.84 | 1236.26 | 113.63 | 0.00 | 0.00 | 0.00 |
March | 639.87 | 252.74 | 387.14 | 1413.09 | 81.70 | 0.00 | 0.00 | 0.00 |
April | 643.04 | 246.29 | 396.75 | 1439.09 | 37.88 | 0.00 | 0.00 | 0.00 |
May | 547.15 | 162.10 | 385.06 | 1277.15 | 38.77 | 0.00 | 0.00 | 0.00 |
June | 592.91 | 204.36 | 388.55 | 1363.71 | 43.86 | 0.00 | 0.00 | 0.00 |
July | 505.49 | 119.21 | 386.28 | 1097.01 | 78.53 | 0.00 | 0.00 | 0.00 |
August | 549.57 | 162.75 | 386.81 | 1172.92 | 60.31 | 0.00 | 0.00 | 0.00 |
September | 514.75 | 142.77 | 371.98 | 1128.99 | 64.18 | 0.00 | 0.00 | 0.00 |
October | 483.45 | 124.62 | 358.83 | 1011.45 | 84.34 | 0.00 | 0.00 | 0.00 |
November | 471.46 | 128.58 | 342.88 | 996.07 | 100.73 | 0.00 | 0.00 | 0.00 |
December | 482.50 | 157.84 | 324.67 | 1019.64 | 161.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.04 | 173.53 | 369.51 | 1187.05 | 84.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.46 | 119.21 | 324.67 | 996.07 | 37.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 643.04 | 252.74 | 396.75 | 1439.09 | 161.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.01 | 0.00 | 133.01 | 303.80 | 72.31 | 0.00 | 0.00 | 0.00 |
February | 141.88 | 0.00 | 141.88 | 340.95 | 55.94 | 0.00 | 0.00 | 0.00 |
March | 145.62 | 0.00 | 145.62 | 371.96 | 36.91 | 0.00 | 0.00 | 0.00 |
April | 158.47 | 2.25 | 156.22 | 417.33 | 16.30 | 0.00 | 0.00 | 0.00 |
May | 203.14 | 21.64 | 181.50 | 531.11 | 21.04 | 0.00 | 0.00 | 0.00 |
June | 248.14 | 50.15 | 197.99 | 630.02 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 213.38 | 22.37 | 191.01 | 494.80 | 42.09 | 0.00 | 0.00 | 0.00 |
August | 175.68 | 7.49 | 168.19 | 412.48 | 32.96 | 0.00 | 0.00 | 0.00 |
September | 149.57 | 0.07 | 149.50 | 363.19 | 32.07 | 0.00 | 0.00 | 0.00 |
October | 144.12 | 0.00 | 144.12 | 324.43 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 136.37 | 0.00 | 136.37 | 309.56 | 50.00 | 0.00 | 0.00 | 0.00 |
December | 129.22 | 0.00 | 129.22 | 291.69 | 81.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.98 | 8.69 | 156.29 | 399.42 | 42.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.22 | 0.00 | 129.22 | 291.69 | 16.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 248.14 | 50.15 | 197.99 | 630.02 | 81.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.01 | 0.00 | 133.01 | 303.82 | 72.31 | 0.00 | 0.00 | 0.00 |
February | 141.89 | 0.00 | 141.89 | 340.97 | 55.94 | 0.00 | 0.00 | 0.00 |
March | 145.62 | 0.00 | 145.62 | 371.98 | 36.91 | 0.00 | 0.00 | 0.00 |
April | 158.47 | 2.25 | 156.23 | 417.35 | 16.30 | 0.00 | 0.00 | 0.00 |
May | 203.14 | 21.64 | 181.50 | 531.14 | 21.04 | 0.00 | 0.00 | 0.00 |
June | 248.15 | 50.15 | 198.00 | 630.04 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 213.38 | 22.37 | 191.02 | 494.82 | 42.09 | 0.00 | 0.00 | 0.00 |
August | 175.69 | 7.49 | 168.19 | 412.50 | 32.96 | 0.00 | 0.00 | 0.00 |
September | 149.58 | 0.07 | 149.51 | 363.21 | 32.07 | 0.00 | 0.00 | 0.00 |
October | 144.12 | 0.00 | 144.12 | 324.45 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 136.37 | 0.00 | 136.37 | 309.57 | 50.00 | 0.00 | 0.00 | 0.00 |
December | 129.22 | 0.00 | 129.22 | 291.71 | 81.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.99 | 8.69 | 156.30 | 399.44 | 42.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.22 | 0.00 | 129.22 | 291.71 | 16.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 248.15 | 50.15 | 198.00 | 630.04 | 81.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 133.01 | 0.00 | 133.01 | 303.82 | 72.31 | 0.00 | 0.00 | 0.00 |
February | 141.89 | 0.00 | 141.89 | 340.97 | 55.94 | 0.00 | 0.00 | 0.00 |
March | 145.62 | 0.00 | 145.62 | 371.98 | 36.91 | 0.00 | 0.00 | 0.00 |
April | 158.47 | 2.25 | 156.23 | 417.35 | 16.30 | 0.00 | 0.00 | 0.00 |
May | 203.14 | 21.64 | 181.50 | 531.14 | 21.04 | 0.00 | 0.00 | 0.00 |
June | 248.15 | 50.15 | 198.00 | 630.04 | 24.41 | 0.00 | 0.00 | 0.00 |
July | 213.38 | 22.37 | 191.02 | 494.82 | 42.09 | 0.00 | 0.00 | 0.00 |
August | 175.69 | 7.49 | 168.19 | 412.50 | 32.96 | 0.00 | 0.00 | 0.00 |
September | 149.58 | 0.07 | 149.51 | 363.21 | 32.07 | 0.00 | 0.00 | 0.00 |
October | 144.12 | 0.00 | 144.12 | 324.45 | 40.32 | 0.00 | 0.00 | 0.00 |
November | 136.37 | 0.00 | 136.37 | 309.57 | 50.00 | 0.00 | 0.00 | 0.00 |
December | 129.22 | 0.00 | 129.22 | 291.71 | 81.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.99 | 8.69 | 156.30 | 399.44 | 42.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 129.22 | 0.00 | 129.22 | 291.71 | 16.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 248.15 | 50.15 | 198.00 | 630.04 | 81.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 493.46 | 166.31 | 327.15 | 1034.25 | 138.55 | 0.00 | 0.00 | 0.00 |
February | 559.58 | 205.17 | 354.41 | 1202.06 | 107.91 | 0.00 | 0.00 | 0.00 |
March | 610.05 | 238.89 | 371.16 | 1346.86 | 73.75 | 0.00 | 0.00 | 0.00 |
April | 616.55 | 235.55 | 381.00 | 1396.24 | 34.73 | 0.00 | 0.00 | 0.00 |
May | 529.98 | 160.42 | 369.56 | 1249.09 | 41.39 | 0.00 | 0.00 | 0.00 |
June | 564.47 | 185.91 | 378.57 | 1313.32 | 46.30 | 0.00 | 0.00 | 0.00 |
July | 482.14 | 108.01 | 374.13 | 1053.68 | 80.83 | 0.00 | 0.00 | 0.00 |
August | 530.60 | 155.97 | 374.63 | 1141.22 | 66.74 | 0.00 | 0.00 | 0.00 |
September | 498.30 | 135.79 | 362.51 | 1101.52 | 67.16 | 0.00 | 0.00 | 0.00 |
October | 467.02 | 119.48 | 347.54 | 983.53 | 83.28 | 0.00 | 0.00 | 0.00 |
November | 451.98 | 124.90 | 327.08 | 956.00 | 101.18 | 0.00 | 0.00 | 0.00 |
December | 462.53 | 148.43 | 314.10 | 964.12 | 156.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 521.80 | 165.02 | 356.78 | 1144.18 | 83.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 451.98 | 108.01 | 314.10 | 956.00 | 34.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 616.55 | 238.89 | 381.00 | 1396.24 | 156.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.51 | 6.58 | 12.94 | 40.89 | 5.48 | 0.00 | 0.00 | 0.00 |
February | 22.13 | 8.11 | 14.01 | 47.53 | 4.27 | 0.00 | 0.00 | 0.00 |
March | 24.12 | 9.45 | 14.68 | 53.25 | 2.92 | 0.00 | 0.00 | 0.00 |
April | 24.38 | 9.31 | 15.06 | 55.21 | 1.37 | 0.00 | 0.00 | 0.00 |
May | 20.95 | 6.34 | 14.61 | 49.39 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 22.32 | 7.35 | 14.97 | 51.93 | 1.83 | 0.00 | 0.00 | 0.00 |
July | 19.06 | 4.27 | 14.79 | 41.66 | 3.20 | 0.00 | 0.00 | 0.00 |
August | 20.98 | 6.17 | 14.81 | 45.12 | 2.64 | 0.00 | 0.00 | 0.00 |
September | 19.70 | 5.37 | 14.33 | 43.55 | 2.66 | 0.00 | 0.00 | 0.00 |
October | 18.47 | 4.72 | 13.74 | 38.89 | 3.29 | 0.00 | 0.00 | 0.00 |
November | 17.87 | 4.94 | 12.93 | 37.80 | 4.00 | 0.00 | 0.00 | 0.00 |
December | 18.29 | 5.87 | 12.42 | 38.12 | 6.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.63 | 6.52 | 14.11 | 45.24 | 3.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.87 | 4.27 | 12.42 | 37.80 | 1.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.38 | 9.45 | 15.06 | 55.21 | 6.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 352.17 | 146.93 | 205.24 | 739.82 | 80.45 | 0.00 | 0.00 | 0.00 |
February | 299.04 | 97.50 | 201.55 | 675.45 | 61.88 | 0.00 | 0.00 | 0.00 |
March | 204.08 | 27.41 | 176.67 | 511.76 | 39.15 | 0.00 | 0.00 | 0.00 |
April | 152.15 | 0.07 | 152.08 | 401.20 | 15.73 | 0.00 | 0.00 | 0.00 |
May | 152.26 | 0.00 | 152.26 | 411.26 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 151.71 | 0.00 | 151.71 | 407.27 | 21.39 | 0.00 | 0.00 | 0.00 |
July | 156.28 | 0.00 | 156.28 | 365.56 | 39.93 | 0.00 | 0.00 | 0.00 |
August | 152.14 | 0.24 | 151.91 | 356.54 | 31.40 | 0.00 | 0.00 | 0.00 |
September | 168.43 | 5.50 | 162.93 | 403.87 | 33.33 | 0.00 | 0.00 | 0.00 |
October | 220.36 | 35.13 | 185.22 | 486.21 | 44.92 | 0.00 | 0.00 | 0.00 |
November | 286.54 | 87.42 | 199.12 | 612.84 | 57.59 | 0.00 | 0.00 | 0.00 |
December | 351.99 | 149.76 | 202.23 | 729.29 | 90.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.29 | 45.65 | 174.64 | 507.62 | 44.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.71 | 0.00 | 151.71 | 356.54 | 15.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.17 | 149.76 | 205.24 | 739.82 | 90.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 352.17 | 146.93 | 205.24 | 739.82 | 80.45 | 0.00 | 0.00 | 0.00 |
February | 299.04 | 97.50 | 201.55 | 675.45 | 61.88 | 0.00 | 0.00 | 0.00 |
March | 204.08 | 27.41 | 176.67 | 511.76 | 39.15 | 0.00 | 0.00 | 0.00 |
April | 152.15 | 0.07 | 152.08 | 401.20 | 15.73 | 0.00 | 0.00 | 0.00 |
May | 152.26 | 0.00 | 152.26 | 411.26 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 151.71 | 0.00 | 151.71 | 407.27 | 21.39 | 0.00 | 0.00 | 0.00 |
July | 156.28 | 0.00 | 156.28 | 365.56 | 39.93 | 0.00 | 0.00 | 0.00 |
August | 152.14 | 0.24 | 151.91 | 356.54 | 31.40 | 0.00 | 0.00 | 0.00 |
September | 168.43 | 5.50 | 162.93 | 403.87 | 33.33 | 0.00 | 0.00 | 0.00 |
October | 220.36 | 35.13 | 185.22 | 486.21 | 44.92 | 0.00 | 0.00 | 0.00 |
November | 286.54 | 87.42 | 199.12 | 612.84 | 57.59 | 0.00 | 0.00 | 0.00 |
December | 351.99 | 149.76 | 202.23 | 729.29 | 90.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.29 | 45.65 | 174.64 | 507.62 | 44.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.71 | 0.00 | 151.71 | 356.54 | 15.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.17 | 149.76 | 205.24 | 739.82 | 90.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 352.15 | 146.92 | 205.23 | 739.77 | 80.44 | 0.00 | 0.00 | 0.00 |
February | 299.03 | 97.49 | 201.53 | 675.40 | 61.88 | 0.00 | 0.00 | 0.00 |
March | 204.07 | 27.41 | 176.66 | 511.73 | 39.15 | 0.00 | 0.00 | 0.00 |
April | 152.14 | 0.07 | 152.08 | 401.18 | 15.73 | 0.00 | 0.00 | 0.00 |
May | 152.25 | 0.00 | 152.25 | 411.23 | 19.67 | 0.00 | 0.00 | 0.00 |
June | 151.70 | 0.00 | 151.70 | 407.25 | 21.39 | 0.00 | 0.00 | 0.00 |
July | 156.27 | 0.00 | 156.27 | 365.53 | 39.93 | 0.00 | 0.00 | 0.00 |
August | 152.13 | 0.24 | 151.90 | 356.52 | 31.40 | 0.00 | 0.00 | 0.00 |
September | 168.42 | 5.50 | 162.92 | 403.84 | 33.32 | 0.00 | 0.00 | 0.00 |
October | 220.34 | 35.13 | 185.21 | 486.18 | 44.92 | 0.00 | 0.00 | 0.00 |
November | 286.52 | 87.41 | 199.11 | 612.80 | 57.59 | 0.00 | 0.00 | 0.00 |
December | 351.97 | 149.75 | 202.22 | 729.24 | 90.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 220.28 | 45.65 | 174.63 | 507.59 | 44.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.70 | 0.00 | 151.70 | 356.52 | 15.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 352.15 | 149.75 | 205.23 | 739.77 | 90.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.98 | 175.81 | 324.17 | 1061.96 | 154.59 | 0.00 | 0.00 | 0.00 |
February | 549.13 | 194.32 | 354.80 | 1194.31 | 122.06 | 0.00 | 0.00 | 0.00 |
March | 615.53 | 243.12 | 372.41 | 1365.43 | 88.82 | 0.00 | 0.00 | 0.00 |
April | 618.57 | 236.92 | 381.65 | 1390.28 | 42.66 | 0.00 | 0.00 | 0.00 |
May | 526.34 | 155.93 | 370.41 | 1232.17 | 43.55 | 0.00 | 0.00 | 0.00 |
June | 570.35 | 196.59 | 373.77 | 1315.24 | 49.07 | 0.00 | 0.00 | 0.00 |
July | 486.25 | 114.67 | 371.58 | 1060.41 | 85.33 | 0.00 | 0.00 | 0.00 |
August | 528.66 | 156.56 | 372.10 | 1130.30 | 70.18 | 0.00 | 0.00 | 0.00 |
September | 495.16 | 137.34 | 357.83 | 1089.48 | 71.27 | 0.00 | 0.00 | 0.00 |
October | 465.06 | 119.88 | 345.18 | 977.70 | 88.83 | 0.00 | 0.00 | 0.00 |
November | 453.52 | 123.69 | 329.83 | 961.56 | 107.45 | 0.00 | 0.00 | 0.00 |
December | 464.15 | 151.83 | 312.32 | 983.38 | 170.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 522.38 | 166.93 | 355.45 | 1146.00 | 91.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 453.52 | 114.67 | 312.32 | 961.56 | 42.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 618.57 | 243.12 | 381.65 | 1390.28 | 170.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.77 | 6.95 | 12.82 | 41.99 | 6.11 | 0.00 | 0.00 | 0.00 |
February | 21.71 | 7.68 | 14.03 | 47.22 | 4.83 | 0.00 | 0.00 | 0.00 |
March | 24.34 | 9.61 | 14.72 | 53.99 | 3.51 | 0.00 | 0.00 | 0.00 |
April | 24.46 | 9.37 | 15.09 | 54.97 | 1.69 | 0.00 | 0.00 | 0.00 |
May | 20.81 | 6.17 | 14.65 | 48.72 | 1.72 | 0.00 | 0.00 | 0.00 |
June | 22.55 | 7.77 | 14.78 | 52.00 | 1.94 | 0.00 | 0.00 | 0.00 |
July | 19.23 | 4.53 | 14.69 | 41.93 | 3.37 | 0.00 | 0.00 | 0.00 |
August | 20.90 | 6.19 | 14.71 | 44.69 | 2.77 | 0.00 | 0.00 | 0.00 |
September | 19.58 | 5.43 | 14.15 | 43.08 | 2.82 | 0.00 | 0.00 | 0.00 |
October | 18.39 | 4.74 | 13.65 | 38.66 | 3.51 | 0.00 | 0.00 | 0.00 |
November | 17.93 | 4.89 | 13.04 | 38.02 | 4.25 | 0.00 | 0.00 | 0.00 |
December | 18.35 | 6.00 | 12.35 | 38.88 | 6.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.65 | 6.60 | 14.05 | 45.31 | 3.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.93 | 4.53 | 12.35 | 38.02 | 1.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.46 | 9.61 | 15.09 | 54.97 | 6.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 399.04 | 0.00 | 399.04 | 913.69 | 215.35 | 0.00 | 0.00 | 0.00 |
February | 425.67 | 0.00 | 425.67 | 1025.54 | 164.97 | 0.00 | 0.00 | 0.00 |
March | 436.87 | 0.00 | 436.87 | 1119.32 | 108.46 | 0.00 | 0.00 | 0.00 |
April | 475.43 | 6.74 | 468.69 | 1257.10 | 47.19 | 0.00 | 0.00 | 0.00 |
May | 609.44 | 64.92 | 544.52 | 1600.10 | 57.62 | 0.00 | 0.00 | 0.00 |
June | 744.45 | 150.45 | 594.01 | 1899.14 | 64.70 | 0.00 | 0.00 | 0.00 |
July | 640.16 | 67.10 | 573.06 | 1490.49 | 115.65 | 0.00 | 0.00 | 0.00 |
August | 527.06 | 22.47 | 504.59 | 1246.15 | 88.92 | 0.00 | 0.00 | 0.00 |
September | 448.73 | 0.21 | 448.52 | 1097.49 | 88.65 | 0.00 | 0.00 | 0.00 |
October | 432.37 | 0.00 | 432.37 | 976.07 | 118.01 | 0.00 | 0.00 | 0.00 |
November | 409.12 | 0.00 | 409.12 | 931.50 | 146.28 | 0.00 | 0.00 | 0.00 |
December | 387.67 | 0.00 | 387.67 | 878.41 | 237.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 494.96 | 26.06 | 468.90 | 1203.35 | 121.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.67 | 0.00 | 387.67 | 878.41 | 47.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.45 | 150.45 | 594.01 | 1899.14 | 237.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 512.98 | 172.89 | 340.09 | 1072.56 | 137.59 | 0.00 | 0.00 | 0.00 |
February | 581.72 | 213.29 | 368.43 | 1247.62 | 104.32 | 0.00 | 0.00 | 0.00 |
March | 634.18 | 248.34 | 385.84 | 1397.37 | 68.39 | 0.00 | 0.00 | 0.00 |
April | 640.94 | 244.87 | 396.07 | 1451.74 | 30.68 | 0.00 | 0.00 | 0.00 |
May | 550.94 | 166.77 | 384.17 | 1300.03 | 38.21 | 0.00 | 0.00 | 0.00 |
June | 586.80 | 193.26 | 393.54 | 1367.03 | 41.96 | 0.00 | 0.00 | 0.00 |
July | 501.21 | 112.28 | 388.93 | 1095.62 | 76.01 | 0.00 | 0.00 | 0.00 |
August | 551.59 | 162.14 | 389.45 | 1187.22 | 59.95 | 0.00 | 0.00 | 0.00 |
September | 518.01 | 141.16 | 376.85 | 1146.11 | 61.01 | 0.00 | 0.00 | 0.00 |
October | 485.49 | 124.21 | 361.29 | 1020.04 | 80.65 | 0.00 | 0.00 | 0.00 |
November | 469.86 | 129.84 | 340.01 | 991.45 | 98.58 | 0.00 | 0.00 | 0.00 |
December | 480.82 | 154.30 | 326.52 | 999.84 | 154.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 542.44 | 171.55 | 370.89 | 1188.70 | 79.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 469.86 | 112.28 | 326.52 | 991.45 | 30.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 640.94 | 248.34 | 396.07 | 1451.74 | 154.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1056.52 | 440.79 | 615.73 | 2239.61 | 218.12 | 0.00 | 0.00 | 0.00 |
February | 897.15 | 292.50 | 604.64 | 2052.43 | 163.29 | 0.00 | 0.00 | 0.00 |
March | 612.25 | 82.23 | 530.03 | 1558.31 | 103.71 | 0.00 | 0.00 | 0.00 |
April | 456.46 | 0.20 | 456.26 | 1224.01 | 42.58 | 0.00 | 0.00 | 0.00 |
May | 456.77 | 0.00 | 456.77 | 1255.89 | 53.23 | 0.00 | 0.00 | 0.00 |
June | 455.13 | 0.00 | 455.13 | 1248.28 | 57.58 | 0.00 | 0.00 | 0.00 |
July | 468.85 | 0.00 | 468.85 | 1109.97 | 109.98 | 0.00 | 0.00 | 0.00 |
August | 456.43 | 0.71 | 455.73 | 1087.45 | 82.86 | 0.00 | 0.00 | 0.00 |
September | 505.30 | 16.50 | 488.80 | 1228.34 | 88.91 | 0.00 | 0.00 | 0.00 |
October | 661.08 | 105.40 | 555.68 | 1470.01 | 123.64 | 0.00 | 0.00 | 0.00 |
November | 859.63 | 262.26 | 597.37 | 1856.30 | 154.72 | 0.00 | 0.00 | 0.00 |
December | 1055.98 | 449.28 | 606.70 | 2204.03 | 244.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 660.88 | 136.96 | 523.92 | 1542.08 | 120.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 455.13 | 0.00 | 455.13 | 1087.45 | 42.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1056.52 | 449.28 | 615.73 | 2239.61 | 244.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.76 | 182.76 | 336.99 | 1105.12 | 153.41 | 0.00 | 0.00 | 0.00 |
February | 570.84 | 202.01 | 368.84 | 1243.12 | 117.84 | 0.00 | 0.00 | 0.00 |
March | 639.87 | 252.74 | 387.14 | 1421.18 | 83.37 | 0.00 | 0.00 | 0.00 |
April | 643.04 | 246.29 | 396.75 | 1449.25 | 37.72 | 0.00 | 0.00 | 0.00 |
May | 547.15 | 162.10 | 385.06 | 1286.51 | 39.21 | 0.00 | 0.00 | 0.00 |
June | 592.91 | 204.36 | 388.55 | 1373.60 | 43.58 | 0.00 | 0.00 | 0.00 |
July | 505.49 | 119.21 | 386.28 | 1105.92 | 79.38 | 0.00 | 0.00 | 0.00 |
August | 549.57 | 162.75 | 386.81 | 1179.82 | 62.08 | 0.00 | 0.00 | 0.00 |
September | 514.75 | 142.77 | 371.98 | 1137.19 | 64.67 | 0.00 | 0.00 | 0.00 |
October | 483.45 | 124.62 | 358.83 | 1018.13 | 85.51 | 0.00 | 0.00 | 0.00 |
November | 471.46 | 128.58 | 342.88 | 1001.57 | 104.47 | 0.00 | 0.00 | 0.00 |
December | 482.50 | 157.84 | 324.67 | 1023.98 | 167.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 543.04 | 173.53 | 369.51 | 1194.56 | 86.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.46 | 119.21 | 324.67 | 1001.57 | 37.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 643.04 | 252.74 | 396.75 | 1449.25 | 167.51 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106880E+10 | 0.00 | 0.106880E+10 | 0.242811E+10 | 0.558696E+09 |
February | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.246020E+10 | 0.383493E+09 |
March | 0.117011E+10 | 0.00 | 0.117011E+10 | 0.296916E+10 | 0.283884E+09 |
April | 0.123231E+10 | 17464121.58 | 0.121484E+10 | 0.321976E+10 | 0.122222E+09 |
May | 0.163233E+10 | 0.173892E+09 | 0.145844E+10 | 0.424878E+10 | 0.152937E+09 |
June | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.488513E+10 | 0.169590E+09 |
July | 0.171460E+10 | 0.179721E+09 | 0.153488E+10 | 0.395760E+10 | 0.307291E+09 |
August | 0.141168E+10 | 60195066.80 | 0.135148E+10 | 0.331352E+10 | 0.232033E+09 |
September | 0.116312E+10 | 556964.20 | 0.116256E+10 | 0.281575E+10 | 0.227691E+09 |
October | 0.115807E+10 | 0.00 | 0.115807E+10 | 0.258963E+10 | 0.311258E+09 |
November | 0.106044E+10 | 0.00 | 0.106044E+10 | 0.239498E+10 | 0.364089E+09 |
December | 0.103832E+10 | 0.00 | 0.103832E+10 | 0.233747E+10 | 0.610501E+09 |
Annual Sum or Average | 0.156092E+11 | 0.821791E+09 | 0.147874E+11 | 0.376201E+11 | 0.372369E+10 |
Minimum of Months | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.233747E+10 | 0.122222E+09 |
Maximum of Months | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.488513E+10 | 0.610501E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137397E+10 | 0.463066E+09 | 0.910900E+09 | 0.286961E+10 | 0.357179E+09 |
February | 0.140729E+10 | 0.515982E+09 | 0.891308E+09 | 0.301303E+10 | 0.241360E+09 |
March | 0.169859E+10 | 0.665161E+09 | 0.103343E+10 | 0.373217E+10 | 0.176619E+09 |
April | 0.166131E+10 | 0.634691E+09 | 0.102662E+10 | 0.374701E+10 | 78020543.09 |
May | 0.147565E+10 | 0.446675E+09 | 0.102897E+10 | 0.346885E+10 | 0.100578E+09 |
June | 0.152099E+10 | 0.500933E+09 | 0.102006E+10 | 0.353029E+10 | 0.109164E+09 |
July | 0.134244E+10 | 0.300739E+09 | 0.104170E+10 | 0.292352E+10 | 0.200860E+09 |
August | 0.147738E+10 | 0.434287E+09 | 0.104309E+10 | 0.317450E+10 | 0.155427E+09 |
September | 0.134268E+10 | 0.365887E+09 | 0.976797E+09 | 0.296148E+10 | 0.155910E+09 |
October | 0.130034E+10 | 0.332673E+09 | 0.967667E+09 | 0.272579E+10 | 0.211912E+09 |
November | 0.121787E+10 | 0.336554E+09 | 0.881318E+09 | 0.256611E+10 | 0.245130E+09 |
December | 0.128784E+10 | 0.413280E+09 | 0.874559E+09 | 0.267728E+10 | 0.396974E+09 |
Annual Sum or Average | 0.171063E+11 | 0.540993E+10 | 0.116964E+11 | 0.373896E+11 | 0.242914E+10 |
Minimum of Months | 0.121787E+10 | 0.300739E+09 | 0.874559E+09 | 0.256611E+10 | 78020543.09 |
Maximum of Months | 0.169859E+10 | 0.665161E+09 | 0.104309E+10 | 0.374701E+10 | 0.396974E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282979E+10 | 0.118062E+10 | 0.164917E+10 | 0.598388E+10 | 0.567527E+09 |
February | 0.217038E+10 | 0.707624E+09 | 0.146275E+10 | 0.494558E+10 | 0.379672E+09 |
March | 0.163985E+10 | 0.220233E+09 | 0.141962E+10 | 0.414273E+10 | 0.269572E+09 |
April | 0.118315E+10 | 531125.50 | 0.118262E+10 | 0.313426E+10 | 0.109267E+09 |
May | 0.122342E+10 | 0.00 | 0.122342E+10 | 0.332796E+10 | 0.140506E+09 |
June | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.320058E+10 | 0.150420E+09 |
July | 0.125577E+10 | 0.00 | 0.125577E+10 | 0.293901E+10 | 0.291519E+09 |
August | 0.122251E+10 | 1889408.72 | 0.122062E+10 | 0.288898E+10 | 0.214789E+09 |
September | 0.130974E+10 | 42777181.36 | 0.126697E+10 | 0.315365E+10 | 0.228277E+09 |
October | 0.177064E+10 | 0.282315E+09 | 0.148833E+10 | 0.391009E+10 | 0.326971E+09 |
November | 0.222815E+10 | 0.679778E+09 | 0.154837E+10 | 0.479176E+10 | 0.386993E+09 |
December | 0.282834E+10 | 0.120334E+10 | 0.162500E+10 | 0.589108E+10 | 0.632693E+09 |
Annual Sum or Average | 0.208414E+11 | 0.431911E+10 | 0.165223E+11 | 0.483096E+11 | 0.369821E+10 |
Minimum of Months | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.288898E+10 | 0.109267E+09 |
Maximum of Months | 0.282979E+10 | 0.120334E+10 | 0.164917E+10 | 0.598388E+10 | 0.632693E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139212E+10 | 0.489515E+09 | 0.902607E+09 | 0.294554E+10 | 0.399008E+09 |
February | 0.138099E+10 | 0.488699E+09 | 0.892288E+09 | 0.299077E+10 | 0.274897E+09 |
March | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.378482E+10 | 0.218831E+09 |
April | 0.166676E+10 | 0.638392E+09 | 0.102836E+10 | 0.373011E+10 | 98190766.21 |
May | 0.146550E+10 | 0.434160E+09 | 0.103134E+10 | 0.342072E+10 | 0.103838E+09 |
June | 0.153682E+10 | 0.529707E+09 | 0.100712E+10 | 0.353475E+10 | 0.113675E+09 |
July | 0.135390E+10 | 0.319280E+09 | 0.103462E+10 | 0.293822E+10 | 0.210337E+09 |
August | 0.147195E+10 | 0.435910E+09 | 0.103605E+10 | 0.314156E+10 | 0.161535E+09 |
September | 0.133423E+10 | 0.370056E+09 | 0.964172E+09 | 0.292634E+10 | 0.166367E+09 |
October | 0.129487E+10 | 0.333790E+09 | 0.961082E+09 | 0.270907E+10 | 0.225902E+09 |
November | 0.122203E+10 | 0.333284E+09 | 0.888744E+09 | 0.258182E+10 | 0.261093E+09 |
December | 0.129234E+10 | 0.422747E+09 | 0.869591E+09 | 0.273100E+10 | 0.432635E+09 |
Annual Sum or Average | 0.171253E+11 | 0.547247E+10 | 0.116529E+11 | 0.374347E+11 | 0.266631E+10 |
Minimum of Months | 0.122203E+10 | 0.319280E+09 | 0.869591E+09 | 0.258182E+10 | 98190766.21 |
Maximum of Months | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.378482E+10 | 0.432635E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.356249E+09 | 0.00 | 0.356249E+09 | 0.813708E+09 | 0.193664E+09 |
February | 0.343244E+09 | 0.00 | 0.343244E+09 | 0.824836E+09 | 0.135320E+09 |
March | 0.390017E+09 | 0.00 | 0.390017E+09 | 0.996254E+09 | 98861324.86 |
April | 0.410750E+09 | 5821098.44 | 0.404929E+09 | 0.108171E+10 | 42247388.15 |
May | 0.544084E+09 | 57961237.92 | 0.486122E+09 | 0.142253E+10 | 56345528.44 |
June | 0.643178E+09 | 0.129981E+09 | 0.513197E+09 | 0.163300E+10 | 63267104.94 |
July | 0.571508E+09 | 59904233.95 | 0.511604E+09 | 0.132526E+10 | 0.112742E+09 |
August | 0.470537E+09 | 20064072.95 | 0.450473E+09 | 0.110479E+10 | 88287941.24 |
September | 0.387688E+09 | 185645.95 | 0.387502E+09 | 0.941388E+09 | 83134330.47 |
October | 0.386004E+09 | 0.00 | 0.386004E+09 | 0.868955E+09 | 0.107993E+09 |
November | 0.353463E+09 | 0.00 | 0.353463E+09 | 0.802380E+09 | 0.129598E+09 |
December | 0.346091E+09 | 0.00 | 0.346091E+09 | 0.781267E+09 | 0.217088E+09 |
Annual Sum or Average | 0.520281E+10 | 0.273917E+09 | 0.492890E+10 | 0.125961E+11 | 0.132855E+10 |
Minimum of Months | 0.343244E+09 | 0.00 | 0.343244E+09 | 0.781267E+09 | 42247388.15 |
Maximum of Months | 0.643178E+09 | 0.129981E+09 | 0.513197E+09 | 0.163300E+10 | 0.217088E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.356263E+09 | 0.00 | 0.356263E+09 | 0.813747E+09 | 0.193673E+09 |
February | 0.343258E+09 | 0.00 | 0.343258E+09 | 0.824877E+09 | 0.135324E+09 |
March | 0.390033E+09 | 0.00 | 0.390033E+09 | 0.996305E+09 | 98864008.17 |
April | 0.410767E+09 | 5821254.91 | 0.404946E+09 | 0.108177E+10 | 42247767.91 |
May | 0.544103E+09 | 57962795.93 | 0.486140E+09 | 0.142259E+10 | 56347392.60 |
June | 0.643200E+09 | 0.129985E+09 | 0.513216E+09 | 0.163307E+10 | 63269358.53 |
July | 0.571528E+09 | 59905844.19 | 0.511622E+09 | 0.132531E+10 | 0.112746E+09 |
August | 0.470555E+09 | 20064612.28 | 0.450490E+09 | 0.110484E+10 | 88291038.72 |
September | 0.387703E+09 | 185650.94 | 0.387517E+09 | 0.941432E+09 | 83137440.72 |
October | 0.386019E+09 | 0.00 | 0.386019E+09 | 0.868994E+09 | 0.107998E+09 |
November | 0.353477E+09 | 0.00 | 0.353477E+09 | 0.802416E+09 | 0.129603E+09 |
December | 0.346104E+09 | 0.00 | 0.346104E+09 | 0.781304E+09 | 0.217098E+09 |
Annual Sum or Average | 0.520301E+10 | 0.273925E+09 | 0.492908E+10 | 0.125967E+11 | 0.132860E+10 |
Minimum of Months | 0.343258E+09 | 0.00 | 0.343258E+09 | 0.781304E+09 | 42247767.91 |
Maximum of Months | 0.643200E+09 | 0.129985E+09 | 0.513216E+09 | 0.163307E+10 | 0.217098E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.356263E+09 | 0.00 | 0.356263E+09 | 0.813747E+09 | 0.193673E+09 |
February | 0.343258E+09 | 0.00 | 0.343258E+09 | 0.824877E+09 | 0.135324E+09 |
March | 0.390033E+09 | 0.00 | 0.390033E+09 | 0.996305E+09 | 98864008.17 |
April | 0.410767E+09 | 5821254.91 | 0.404946E+09 | 0.108177E+10 | 42247767.91 |
May | 0.544103E+09 | 57962795.93 | 0.486140E+09 | 0.142259E+10 | 56347392.60 |
June | 0.643200E+09 | 0.129985E+09 | 0.513216E+09 | 0.163307E+10 | 63269358.53 |
July | 0.571528E+09 | 59905844.19 | 0.511622E+09 | 0.132531E+10 | 0.112746E+09 |
August | 0.470555E+09 | 20064612.28 | 0.450490E+09 | 0.110484E+10 | 88291038.72 |
September | 0.387703E+09 | 185650.94 | 0.387517E+09 | 0.941432E+09 | 83137440.72 |
October | 0.386019E+09 | 0.00 | 0.386019E+09 | 0.868994E+09 | 0.107998E+09 |
November | 0.353477E+09 | 0.00 | 0.353477E+09 | 0.802416E+09 | 0.129603E+09 |
December | 0.346104E+09 | 0.00 | 0.346104E+09 | 0.781304E+09 | 0.217098E+09 |
Annual Sum or Average | 0.520301E+10 | 0.273925E+09 | 0.492908E+10 | 0.125967E+11 | 0.132860E+10 |
Minimum of Months | 0.343258E+09 | 0.00 | 0.343258E+09 | 0.781304E+09 | 42247767.91 |
Maximum of Months | 0.643200E+09 | 0.129985E+09 | 0.513216E+09 | 0.163307E+10 | 0.217098E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132169E+10 | 0.445445E+09 | 0.876243E+09 | 0.277013E+10 | 0.371094E+09 |
February | 0.135374E+10 | 0.496347E+09 | 0.857396E+09 | 0.290803E+10 | 0.261065E+09 |
March | 0.163396E+10 | 0.639849E+09 | 0.994113E+09 | 0.360743E+10 | 0.197542E+09 |
April | 0.159810E+10 | 0.610538E+09 | 0.987560E+09 | 0.361905E+10 | 90029814.29 |
May | 0.141950E+10 | 0.429678E+09 | 0.989820E+09 | 0.334557E+10 | 0.110851E+09 |
June | 0.146312E+10 | 0.481870E+09 | 0.981245E+09 | 0.340414E+10 | 0.120011E+09 |
July | 0.129136E+10 | 0.289295E+09 | 0.100206E+10 | 0.282218E+10 | 0.216484E+09 |
August | 0.142116E+10 | 0.417760E+09 | 0.100340E+10 | 0.305664E+10 | 0.178767E+09 |
September | 0.129160E+10 | 0.351964E+09 | 0.939632E+09 | 0.285514E+10 | 0.174067E+09 |
October | 0.125086E+10 | 0.320014E+09 | 0.930849E+09 | 0.263429E+10 | 0.223065E+09 |
November | 0.117153E+10 | 0.323747E+09 | 0.847785E+09 | 0.247794E+10 | 0.262254E+09 |
December | 0.123884E+10 | 0.397553E+09 | 0.841284E+09 | 0.258229E+10 | 0.418730E+09 |
Annual Sum or Average | 0.164555E+11 | 0.520406E+10 | 0.112514E+11 | 0.360828E+11 | 0.262396E+10 |
Minimum of Months | 0.117153E+10 | 0.289295E+09 | 0.841284E+09 | 0.247794E+10 | 90029814.29 |
Maximum of Months | 0.163396E+10 | 0.639849E+09 | 0.100340E+10 | 0.361905E+10 | 0.418730E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52258320.87 | 17612479.66 | 34645841.21 | 0.109528E+09 | 14672716.63 |
February | 53525782.67 | 19625110.22 | 33900672.45 | 0.114981E+09 | 10322260.21 |
March | 64605398.17 | 25299052.27 | 39306345.90 | 0.142635E+09 | 7810636.07 |
April | 63187374.59 | 24140127.76 | 39047246.83 | 0.143094E+09 | 3559697.80 |
May | 56125666.49 | 16989063.45 | 39136603.05 | 0.132281E+09 | 4382935.22 |
June | 57850250.51 | 19052725.41 | 38797525.10 | 0.134596E+09 | 4745114.82 |
July | 51059159.06 | 11438458.18 | 39620700.88 | 0.111586E+09 | 8559594.01 |
August | 56191552.40 | 16517864.61 | 39673687.78 | 0.120857E+09 | 7068283.92 |
September | 51068505.90 | 13916321.21 | 37152184.69 | 0.112889E+09 | 6882458.48 |
October | 49457968.10 | 12653053.06 | 36804915.05 | 0.104158E+09 | 8819799.51 |
November | 46321324.63 | 12800658.10 | 33520666.53 | 97975588.97 | 10369279.64 |
December | 48982488.72 | 15718876.87 | 33263611.85 | 0.102101E+09 | 16556226.52 |
Annual Sum or Average | 0.650634E+09 | 0.205764E+09 | 0.444870E+09 | 0.142668E+10 | 0.103749E+09 |
Minimum of Months | 46321324.63 | 11438458.18 | 33263611.85 | 97975588.97 | 3559697.80 |
Maximum of Months | 64605398.17 | 25299052.27 | 39673687.78 | 0.143094E+09 | 16556226.52 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.943248E+09 | 0.393532E+09 | 0.549716E+09 | 0.198153E+10 | 0.215471E+09 |
February | 0.723448E+09 | 0.235870E+09 | 0.487579E+09 | 0.163404E+10 | 0.149705E+09 |
March | 0.546612E+09 | 73409655.31 | 0.473203E+09 | 0.137070E+10 | 0.104853E+09 |
April | 0.394381E+09 | 177038.22 | 0.394204E+09 | 0.103991E+10 | 40763225.40 |
May | 0.407805E+09 | 0.00 | 0.407805E+09 | 0.110151E+10 | 52686641.06 |
June | 0.393229E+09 | 0.00 | 0.393229E+09 | 0.105565E+10 | 55443677.29 |
July | 0.418587E+09 | 0.00 | 0.418587E+09 | 0.979111E+09 | 0.106943E+09 |
August | 0.407499E+09 | 629790.04 | 0.406869E+09 | 0.954963E+09 | 84103537.76 |
September | 0.436577E+09 | 14258769.10 | 0.422318E+09 | 0.104683E+10 | 86380004.99 |
October | 0.590207E+09 | 94103161.64 | 0.496104E+09 | 0.130226E+10 | 0.120316E+09 |
November | 0.742705E+09 | 0.226588E+09 | 0.516117E+09 | 0.158847E+10 | 0.149282E+09 |
December | 0.942765E+09 | 0.401106E+09 | 0.541659E+09 | 0.195333E+10 | 0.241727E+09 |
Annual Sum or Average | 0.694706E+10 | 0.143967E+10 | 0.550739E+10 | 0.160083E+11 | 0.140767E+10 |
Minimum of Months | 0.393229E+09 | 0.00 | 0.393229E+09 | 0.954963E+09 | 40763225.40 |
Maximum of Months | 0.943248E+09 | 0.401106E+09 | 0.549716E+09 | 0.198153E+10 | 0.241727E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.943248E+09 | 0.393532E+09 | 0.549716E+09 | 0.198153E+10 | 0.215471E+09 |
February | 0.723448E+09 | 0.235870E+09 | 0.487579E+09 | 0.163404E+10 | 0.149705E+09 |
March | 0.546612E+09 | 73409655.31 | 0.473203E+09 | 0.137070E+10 | 0.104853E+09 |
April | 0.394381E+09 | 177038.22 | 0.394204E+09 | 0.103991E+10 | 40763225.40 |
May | 0.407805E+09 | 0.00 | 0.407805E+09 | 0.110151E+10 | 52686641.06 |
June | 0.393229E+09 | 0.00 | 0.393229E+09 | 0.105565E+10 | 55443677.29 |
July | 0.418587E+09 | 0.00 | 0.418587E+09 | 0.979111E+09 | 0.106943E+09 |
August | 0.407499E+09 | 629790.04 | 0.406869E+09 | 0.954963E+09 | 84103537.76 |
September | 0.436577E+09 | 14258769.10 | 0.422318E+09 | 0.104683E+10 | 86380004.99 |
October | 0.590207E+09 | 94103161.64 | 0.496104E+09 | 0.130226E+10 | 0.120316E+09 |
November | 0.742705E+09 | 0.226588E+09 | 0.516117E+09 | 0.158847E+10 | 0.149282E+09 |
December | 0.942765E+09 | 0.401106E+09 | 0.541659E+09 | 0.195333E+10 | 0.241727E+09 |
Annual Sum or Average | 0.694706E+10 | 0.143967E+10 | 0.550739E+10 | 0.160083E+11 | 0.140767E+10 |
Minimum of Months | 0.393229E+09 | 0.00 | 0.393229E+09 | 0.954963E+09 | 40763225.40 |
Maximum of Months | 0.943248E+09 | 0.401106E+09 | 0.549716E+09 | 0.198153E+10 | 0.241727E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.943188E+09 | 0.393507E+09 | 0.549681E+09 | 0.198141E+10 | 0.215457E+09 |
February | 0.723403E+09 | 0.235855E+09 | 0.487548E+09 | 0.163394E+10 | 0.149695E+09 |
March | 0.546578E+09 | 73405016.23 | 0.473173E+09 | 0.137061E+10 | 0.104846E+09 |
April | 0.394356E+09 | 177027.03 | 0.394179E+09 | 0.103985E+10 | 40760649.40 |
May | 0.407779E+09 | 0.00 | 0.407779E+09 | 0.110144E+10 | 52683311.56 |
June | 0.393205E+09 | 0.00 | 0.393205E+09 | 0.105559E+10 | 55440173.56 |
July | 0.418561E+09 | 0.00 | 0.418561E+09 | 0.979049E+09 | 0.106936E+09 |
August | 0.407473E+09 | 629750.24 | 0.406843E+09 | 0.954903E+09 | 84098222.90 |
September | 0.436549E+09 | 14257868.02 | 0.422291E+09 | 0.104676E+10 | 86374546.26 |
October | 0.590170E+09 | 94097214.85 | 0.496072E+09 | 0.130218E+10 | 0.120308E+09 |
November | 0.742658E+09 | 0.226574E+09 | 0.516084E+09 | 0.158837E+10 | 0.149272E+09 |
December | 0.942705E+09 | 0.401081E+09 | 0.541624E+09 | 0.195320E+10 | 0.241711E+09 |
Annual Sum or Average | 0.694662E+10 | 0.143958E+10 | 0.550704E+10 | 0.160073E+11 | 0.140758E+10 |
Minimum of Months | 0.393205E+09 | 0.00 | 0.393205E+09 | 0.954903E+09 | 40760649.40 |
Maximum of Months | 0.943188E+09 | 0.401081E+09 | 0.549681E+09 | 0.198141E+10 | 0.241711E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133916E+10 | 0.470889E+09 | 0.868267E+09 | 0.284437E+10 | 0.414050E+09 |
February | 0.132844E+10 | 0.470104E+09 | 0.858341E+09 | 0.288928E+10 | 0.295294E+09 |
March | 0.164863E+10 | 0.651175E+09 | 0.997456E+09 | 0.365717E+10 | 0.237892E+09 |
April | 0.160334E+10 | 0.614101E+09 | 0.989239E+09 | 0.360362E+10 | 0.110563E+09 |
May | 0.140974E+10 | 0.417640E+09 | 0.992101E+09 | 0.330025E+10 | 0.116638E+09 |
June | 0.147835E+10 | 0.509551E+09 | 0.968801E+09 | 0.340910E+10 | 0.127189E+09 |
July | 0.130238E+10 | 0.307131E+09 | 0.995253E+09 | 0.284021E+10 | 0.228552E+09 |
August | 0.141595E+10 | 0.419323E+09 | 0.996628E+09 | 0.302739E+10 | 0.187960E+09 |
September | 0.128346E+10 | 0.355975E+09 | 0.927489E+09 | 0.282392E+10 | 0.184727E+09 |
October | 0.124561E+10 | 0.321089E+09 | 0.924517E+09 | 0.261866E+10 | 0.237911E+09 |
November | 0.117553E+10 | 0.320602E+09 | 0.854930E+09 | 0.249236E+10 | 0.278505E+09 |
December | 0.124317E+10 | 0.406661E+09 | 0.836507E+09 | 0.263388E+10 | 0.456847E+09 |
Annual Sum or Average | 0.164738E+11 | 0.526424E+10 | 0.112095E+11 | 0.361402E+11 | 0.287613E+10 |
Minimum of Months | 0.117553E+10 | 0.307131E+09 | 0.836507E+09 | 0.249236E+10 | 0.110563E+09 |
Maximum of Months | 0.164863E+10 | 0.651175E+09 | 0.997456E+09 | 0.365717E+10 | 0.456847E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52948845.56 | 18618447.44 | 34330398.12 | 0.112463E+09 | 16371123.50 |
February | 52525354.95 | 18587419.03 | 33937935.91 | 0.114239E+09 | 11675642.30 |
March | 65185232.29 | 25746802.40 | 39438429.89 | 0.144601E+09 | 9405991.16 |
April | 63394441.56 | 24280902.53 | 39113539.02 | 0.142483E+09 | 4371546.11 |
May | 55739740.82 | 16513046.34 | 39226694.48 | 0.130489E+09 | 4611736.35 |
June | 58452562.05 | 20147136.04 | 38305426.01 | 0.134792E+09 | 5028907.90 |
July | 51494931.20 | 12143637.43 | 39351293.77 | 0.112299E+09 | 9036740.35 |
August | 55985288.32 | 16579605.17 | 39405683.14 | 0.119700E+09 | 7431763.40 |
September | 50746894.66 | 14074894.01 | 36672000.66 | 0.111655E+09 | 7303915.78 |
October | 49250003.63 | 12695530.37 | 36554473.26 | 0.103539E+09 | 9406789.78 |
November | 46479383.61 | 12676287.24 | 33803096.37 | 98545359.81 | 11011814.47 |
December | 49153640.19 | 16078976.34 | 33074663.85 | 0.104141E+09 | 18063283.01 |
Annual Sum or Average | 0.651356E+09 | 0.208143E+09 | 0.443214E+09 | 0.142895E+10 | 0.113719E+09 |
Minimum of Months | 46479383.61 | 12143637.43 | 33074663.85 | 98545359.81 | 4371546.11 |
Maximum of Months | 65185232.29 | 25746802.40 | 39438429.89 | 0.144601E+09 | 18063283.01 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106880E+10 | 0.00 | 0.106880E+10 | 0.244724E+10 | 0.576795E+09 |
February | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.248099E+10 | 0.399093E+09 |
March | 0.117011E+10 | 0.00 | 0.117011E+10 | 0.299799E+10 | 0.290491E+09 |
April | 0.123231E+10 | 17464121.58 | 0.121484E+10 | 0.325841E+10 | 0.122313E+09 |
May | 0.163233E+10 | 0.173892E+09 | 0.145844E+10 | 0.428571E+10 | 0.154326E+09 |
June | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.492257E+10 | 0.167691E+09 |
July | 0.171460E+10 | 0.179721E+09 | 0.153488E+10 | 0.399213E+10 | 0.309762E+09 |
August | 0.141168E+10 | 60195066.80 | 0.135148E+10 | 0.333769E+10 | 0.238169E+09 |
September | 0.116312E+10 | 556964.20 | 0.116256E+10 | 0.284470E+10 | 0.229781E+09 |
October | 0.115807E+10 | 0.00 | 0.115807E+10 | 0.261431E+10 | 0.316072E+09 |
November | 0.106044E+10 | 0.00 | 0.106044E+10 | 0.241445E+10 | 0.379160E+09 |
December | 0.103832E+10 | 0.00 | 0.103832E+10 | 0.235272E+10 | 0.635363E+09 |
Annual Sum or Average | 0.156092E+11 | 0.821791E+09 | 0.147874E+11 | 0.379489E+11 | 0.381902E+10 |
Minimum of Months | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.235272E+10 | 0.122313E+09 |
Maximum of Months | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.492257E+10 | 0.635363E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137397E+10 | 0.463066E+09 | 0.910900E+09 | 0.287274E+10 | 0.368521E+09 |
February | 0.140729E+10 | 0.515982E+09 | 0.891308E+09 | 0.301824E+10 | 0.252380E+09 |
March | 0.169859E+10 | 0.665161E+09 | 0.103343E+10 | 0.374272E+10 | 0.183186E+09 |
April | 0.166131E+10 | 0.634691E+09 | 0.102662E+10 | 0.376292E+10 | 79516932.65 |
May | 0.147565E+10 | 0.446675E+09 | 0.102897E+10 | 0.348200E+10 | 0.102354E+09 |
June | 0.152099E+10 | 0.500933E+09 | 0.102006E+10 | 0.354334E+10 | 0.108748E+09 |
July | 0.134244E+10 | 0.300739E+09 | 0.104170E+10 | 0.293452E+10 | 0.203594E+09 |
August | 0.147738E+10 | 0.434287E+09 | 0.104309E+10 | 0.317984E+10 | 0.160558E+09 |
September | 0.134268E+10 | 0.365887E+09 | 0.976797E+09 | 0.297071E+10 | 0.158130E+09 |
October | 0.130034E+10 | 0.332673E+09 | 0.967667E+09 | 0.273206E+10 | 0.216022E+09 |
November | 0.121787E+10 | 0.336554E+09 | 0.881318E+09 | 0.256984E+10 | 0.255520E+09 |
December | 0.128784E+10 | 0.413280E+09 | 0.874559E+09 | 0.267797E+10 | 0.412522E+09 |
Annual Sum or Average | 0.171063E+11 | 0.540993E+10 | 0.116964E+11 | 0.374869E+11 | 0.250105E+10 |
Minimum of Months | 0.121787E+10 | 0.300739E+09 | 0.874559E+09 | 0.256984E+10 | 79516932.65 |
Maximum of Months | 0.169859E+10 | 0.665161E+09 | 0.104309E+10 | 0.376292E+10 | 0.412522E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282979E+10 | 0.118062E+10 | 0.164917E+10 | 0.599858E+10 | 0.584216E+09 |
February | 0.217038E+10 | 0.707624E+09 | 0.146275E+10 | 0.496524E+10 | 0.395042E+09 |
March | 0.163985E+10 | 0.220233E+09 | 0.141962E+10 | 0.417377E+10 | 0.277787E+09 |
April | 0.118315E+10 | 531125.50 | 0.118262E+10 | 0.317263E+10 | 0.110362E+09 |
May | 0.122342E+10 | 0.00 | 0.122342E+10 | 0.336378E+10 | 0.142582E+09 |
June | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.323555E+10 | 0.149254E+09 |
July | 0.125577E+10 | 0.00 | 0.125577E+10 | 0.297294E+10 | 0.294578E+09 |
August | 0.122251E+10 | 1889408.72 | 0.122062E+10 | 0.291263E+10 | 0.221938E+09 |
September | 0.130974E+10 | 42777181.36 | 0.126697E+10 | 0.318386E+10 | 0.230443E+09 |
October | 0.177064E+10 | 0.282315E+09 | 0.148833E+10 | 0.393728E+10 | 0.331171E+09 |
November | 0.222815E+10 | 0.679778E+09 | 0.154837E+10 | 0.481154E+10 | 0.401030E+09 |
December | 0.282834E+10 | 0.120334E+10 | 0.162500E+10 | 0.590327E+10 | 0.654500E+09 |
Annual Sum or Average | 0.208414E+11 | 0.431911E+10 | 0.165223E+11 | 0.486311E+11 | 0.379290E+10 |
Minimum of Months | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.291263E+10 | 0.110362E+09 |
Maximum of Months | 0.282979E+10 | 0.120334E+10 | 0.164917E+10 | 0.599858E+10 | 0.654500E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139212E+10 | 0.489515E+09 | 0.902607E+09 | 0.295996E+10 | 0.410905E+09 |
February | 0.138099E+10 | 0.488699E+09 | 0.892288E+09 | 0.300735E+10 | 0.285079E+09 |
March | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.380650E+10 | 0.223294E+09 |
April | 0.166676E+10 | 0.638392E+09 | 0.102836E+10 | 0.375645E+10 | 97770061.07 |
May | 0.146550E+10 | 0.434160E+09 | 0.103134E+10 | 0.344579E+10 | 0.105022E+09 |
June | 0.153682E+10 | 0.529707E+09 | 0.100712E+10 | 0.356038E+10 | 0.112952E+09 |
July | 0.135390E+10 | 0.319280E+09 | 0.103462E+10 | 0.296210E+10 | 0.212605E+09 |
August | 0.147195E+10 | 0.435910E+09 | 0.103605E+10 | 0.316003E+10 | 0.166287E+09 |
September | 0.133423E+10 | 0.370056E+09 | 0.964172E+09 | 0.294759E+10 | 0.167616E+09 |
October | 0.129487E+10 | 0.333790E+09 | 0.961082E+09 | 0.272696E+10 | 0.229030E+09 |
November | 0.122203E+10 | 0.333284E+09 | 0.888744E+09 | 0.259606E+10 | 0.270777E+09 |
December | 0.129234E+10 | 0.422747E+09 | 0.869591E+09 | 0.274263E+10 | 0.448648E+09 |
Annual Sum or Average | 0.171253E+11 | 0.547247E+10 | 0.116529E+11 | 0.376718E+11 | 0.272999E+10 |
Minimum of Months | 0.122203E+10 | 0.319280E+09 | 0.869591E+09 | 0.259606E+10 | 97770061.07 |
Maximum of Months | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.380650E+10 | 0.448648E+09 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 906.55 | 208.59 | 399.04 | 0.00 | 399.04 | 0.00 | 0.00 |
February | 1016.95 | 158.52 | 425.67 | 0.00 | 425.67 | 0.00 | 0.00 |
March | 1108.56 | 105.99 | 436.87 | 0.00 | 436.87 | 0.00 | 0.00 |
April | 1242.19 | 47.15 | 475.43 | 6.74 | 468.69 | 0.00 | 0.00 |
May | 1586.31 | 57.10 | 609.44 | 64.92 | 544.52 | 0.00 | 0.00 |
June | 1884.69 | 65.43 | 744.45 | 150.45 | 594.01 | 0.00 | 0.00 |
July | 1477.60 | 114.73 | 640.16 | 67.10 | 573.06 | 0.00 | 0.00 |
August | 1237.13 | 86.63 | 527.06 | 22.47 | 504.59 | 0.00 | 0.00 |
September | 1086.32 | 87.84 | 448.73 | 0.21 | 448.52 | 0.00 | 0.00 |
October | 966.86 | 116.21 | 432.37 | 0.00 | 432.37 | 0.00 | 0.00 |
November | 923.99 | 140.47 | 409.12 | 0.00 | 409.12 | 0.00 | 0.00 |
December | 872.71 | 227.94 | 387.67 | 0.00 | 387.67 | 0.00 | 0.00 |
Annual Sum or Average | 1192.93 | 118.08 | 494.96 | 26.06 | 468.90 | 0.00 | 0.00 |
Minimum of Months | 872.71 | 47.15 | 387.67 | 0.00 | 387.67 | 0.00 | 0.00 |
Maximum of Months | 1884.69 | 227.94 | 744.45 | 150.45 | 594.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1071.39 | 133.36 | 512.98 | 172.89 | 340.09 | 0.00 | 0.00 |
February | 1245.47 | 99.77 | 581.72 | 213.29 | 368.43 | 0.00 | 0.00 |
March | 1393.43 | 65.94 | 634.18 | 248.34 | 385.84 | 0.00 | 0.00 |
April | 1445.61 | 30.10 | 640.94 | 244.87 | 396.07 | 0.00 | 0.00 |
May | 1295.12 | 37.55 | 550.94 | 166.77 | 384.17 | 0.00 | 0.00 |
June | 1362.00 | 42.12 | 586.80 | 193.26 | 393.54 | 0.00 | 0.00 |
July | 1091.52 | 74.99 | 501.21 | 112.28 | 388.93 | 0.00 | 0.00 |
August | 1185.22 | 58.03 | 551.59 | 162.14 | 389.45 | 0.00 | 0.00 |
September | 1142.55 | 60.15 | 518.01 | 141.16 | 376.85 | 0.00 | 0.00 |
October | 1017.69 | 79.12 | 485.49 | 124.21 | 361.29 | 0.00 | 0.00 |
November | 990.01 | 94.57 | 469.86 | 129.84 | 340.01 | 0.00 | 0.00 |
December | 999.58 | 148.21 | 480.82 | 154.30 | 326.52 | 0.00 | 0.00 |
Annual Sum or Average | 1185.62 | 77.03 | 542.44 | 171.55 | 370.89 | 0.00 | 0.00 |
Minimum of Months | 990.01 | 30.10 | 469.86 | 112.28 | 326.52 | 0.00 | 0.00 |
Maximum of Months | 1445.61 | 148.21 | 640.94 | 248.34 | 396.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2234.13 | 211.89 | 1056.52 | 440.79 | 615.73 | 0.00 | 0.00 |
February | 2044.30 | 156.94 | 897.15 | 292.50 | 604.64 | 0.00 | 0.00 |
March | 1546.72 | 100.65 | 612.25 | 82.23 | 530.03 | 0.00 | 0.00 |
April | 1209.21 | 42.16 | 456.46 | 0.20 | 456.26 | 0.00 | 0.00 |
May | 1242.52 | 52.46 | 456.77 | 0.00 | 456.77 | 0.00 | 0.00 |
June | 1234.79 | 58.03 | 455.13 | 0.00 | 455.13 | 0.00 | 0.00 |
July | 1097.30 | 108.84 | 468.85 | 0.00 | 468.85 | 0.00 | 0.00 |
August | 1078.62 | 80.19 | 456.43 | 0.71 | 455.73 | 0.00 | 0.00 |
September | 1216.69 | 88.07 | 505.30 | 16.50 | 488.80 | 0.00 | 0.00 |
October | 1459.86 | 122.08 | 661.08 | 105.40 | 555.68 | 0.00 | 0.00 |
November | 1848.67 | 149.30 | 859.63 | 262.26 | 597.37 | 0.00 | 0.00 |
December | 2199.48 | 236.22 | 1055.98 | 449.28 | 606.70 | 0.00 | 0.00 |
Annual Sum or Average | 1531.89 | 117.27 | 660.88 | 136.96 | 523.92 | 0.00 | 0.00 |
Minimum of Months | 1078.62 | 42.16 | 455.13 | 0.00 | 455.13 | 0.00 | 0.00 |
Maximum of Months | 2234.13 | 236.22 | 1056.52 | 449.28 | 615.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1099.74 | 148.97 | 519.76 | 182.76 | 336.99 | 0.00 | 0.00 |
February | 1236.26 | 113.63 | 570.84 | 202.01 | 368.84 | 0.00 | 0.00 |
March | 1413.09 | 81.70 | 639.87 | 252.74 | 387.14 | 0.00 | 0.00 |
April | 1439.09 | 37.88 | 643.04 | 246.29 | 396.75 | 0.00 | 0.00 |
May | 1277.15 | 38.77 | 547.15 | 162.10 | 385.06 | 0.00 | 0.00 |
June | 1363.71 | 43.86 | 592.91 | 204.36 | 388.55 | 0.00 | 0.00 |
July | 1097.01 | 78.53 | 505.49 | 119.21 | 386.28 | 0.00 | 0.00 |
August | 1172.92 | 60.31 | 549.57 | 162.75 | 386.81 | 0.00 | 0.00 |
September | 1128.99 | 64.18 | 514.75 | 142.77 | 371.98 | 0.00 | 0.00 |
October | 1011.45 | 84.34 | 483.45 | 124.62 | 358.83 | 0.00 | 0.00 |
November | 996.07 | 100.73 | 471.46 | 128.58 | 342.88 | 0.00 | 0.00 |
December | 1019.64 | 161.53 | 482.50 | 157.84 | 324.67 | 0.00 | 0.00 |
Annual Sum or Average | 1187.05 | 84.55 | 543.04 | 173.53 | 369.51 | 0.00 | 0.00 |
Minimum of Months | 996.07 | 37.88 | 471.46 | 119.21 | 324.67 | 0.00 | 0.00 |
Maximum of Months | 1439.09 | 161.53 | 643.04 | 252.74 | 396.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 911.44 | 216.92 | 399.03 | 0.00 | 399.03 | 0.00 | 0.00 |
February | 1022.90 | 167.81 | 425.66 | 0.00 | 425.66 | 0.00 | 0.00 |
March | 1115.91 | 110.73 | 436.86 | 0.00 | 436.86 | 0.00 | 0.00 |
April | 1252.02 | 48.90 | 475.42 | 6.74 | 468.68 | 0.00 | 0.00 |
May | 1593.38 | 63.11 | 609.43 | 64.92 | 544.51 | 0.00 | 0.00 |
June | 1890.10 | 73.23 | 744.44 | 150.44 | 593.99 | 0.00 | 0.00 |
July | 1484.43 | 126.28 | 640.14 | 67.10 | 573.05 | 0.00 | 0.00 |
August | 1237.48 | 98.89 | 527.05 | 22.47 | 504.57 | 0.00 | 0.00 |
September | 1089.60 | 96.22 | 448.72 | 0.21 | 448.51 | 0.00 | 0.00 |
October | 973.32 | 120.96 | 432.36 | 0.00 | 432.36 | 0.00 | 0.00 |
November | 928.71 | 150.00 | 409.11 | 0.00 | 409.11 | 0.00 | 0.00 |
December | 875.10 | 243.16 | 387.66 | 0.00 | 387.66 | 0.00 | 0.00 |
Annual Sum or Average | 1198.29 | 126.39 | 494.95 | 26.06 | 468.89 | 0.00 | 0.00 |
Minimum of Months | 875.10 | 48.90 | 387.66 | 0.00 | 387.66 | 0.00 | 0.00 |
Maximum of Months | 1890.10 | 243.16 | 744.44 | 150.44 | 593.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1075.14 | 144.03 | 512.97 | 172.89 | 340.09 | 0.00 | 0.00 |
February | 1249.59 | 112.18 | 581.71 | 213.28 | 368.43 | 0.00 | 0.00 |
March | 1400.11 | 76.67 | 634.17 | 248.34 | 385.83 | 0.00 | 0.00 |
April | 1451.44 | 36.11 | 640.93 | 244.86 | 396.07 | 0.00 | 0.00 |
May | 1298.48 | 43.02 | 550.93 | 166.77 | 384.17 | 0.00 | 0.00 |
June | 1365.25 | 48.13 | 586.79 | 193.26 | 393.53 | 0.00 | 0.00 |
July | 1095.34 | 84.02 | 501.20 | 112.28 | 388.92 | 0.00 | 0.00 |
August | 1186.34 | 69.38 | 551.58 | 162.14 | 389.44 | 0.00 | 0.00 |
September | 1145.07 | 69.81 | 518.00 | 141.16 | 376.85 | 0.00 | 0.00 |
October | 1022.42 | 86.58 | 485.48 | 124.20 | 361.28 | 0.00 | 0.00 |
November | 993.80 | 105.18 | 469.85 | 129.84 | 340.01 | 0.00 | 0.00 |
December | 1002.24 | 162.52 | 480.82 | 154.30 | 326.52 | 0.00 | 0.00 |
Annual Sum or Average | 1189.42 | 86.50 | 542.43 | 171.54 | 370.89 | 0.00 | 0.00 |
Minimum of Months | 993.80 | 36.11 | 469.85 | 112.28 | 326.52 | 0.00 | 0.00 |
Maximum of Months | 1451.44 | 162.52 | 640.93 | 248.34 | 396.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2219.41 | 241.34 | 1056.48 | 440.77 | 615.71 | 0.00 | 0.00 |
February | 2026.30 | 185.64 | 897.11 | 292.49 | 604.62 | 0.00 | 0.00 |
March | 1535.25 | 117.44 | 612.23 | 82.22 | 530.01 | 0.00 | 0.00 |
April | 1203.58 | 47.18 | 456.45 | 0.20 | 456.25 | 0.00 | 0.00 |
May | 1233.75 | 59.01 | 456.76 | 0.00 | 456.76 | 0.00 | 0.00 |
June | 1221.79 | 64.17 | 455.12 | 0.00 | 455.12 | 0.00 | 0.00 |
July | 1096.65 | 119.78 | 468.84 | 0.00 | 468.84 | 0.00 | 0.00 |
August | 1069.61 | 94.20 | 456.42 | 0.71 | 455.71 | 0.00 | 0.00 |
September | 1211.58 | 99.97 | 505.29 | 16.50 | 488.78 | 0.00 | 0.00 |
October | 1458.60 | 134.76 | 661.06 | 105.40 | 555.66 | 0.00 | 0.00 |
November | 1838.47 | 172.78 | 859.59 | 262.25 | 597.34 | 0.00 | 0.00 |
December | 2187.82 | 270.75 | 1055.94 | 449.26 | 606.68 | 0.00 | 0.00 |
Annual Sum or Average | 1522.83 | 133.91 | 660.86 | 136.95 | 523.90 | 0.00 | 0.00 |
Minimum of Months | 1069.61 | 47.18 | 455.12 | 0.00 | 455.12 | 0.00 | 0.00 |
Maximum of Months | 2219.41 | 270.75 | 1056.48 | 449.26 | 615.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1103.95 | 160.70 | 519.75 | 182.76 | 336.99 | 0.00 | 0.00 |
February | 1241.53 | 126.89 | 570.84 | 202.01 | 368.83 | 0.00 | 0.00 |
March | 1419.42 | 92.33 | 639.87 | 252.73 | 387.13 | 0.00 | 0.00 |
April | 1445.25 | 44.34 | 643.03 | 246.29 | 396.74 | 0.00 | 0.00 |
May | 1280.89 | 45.27 | 547.15 | 162.09 | 385.05 | 0.00 | 0.00 |
June | 1367.24 | 51.01 | 592.90 | 204.36 | 388.54 | 0.00 | 0.00 |
July | 1102.34 | 88.71 | 505.48 | 119.20 | 386.28 | 0.00 | 0.00 |
August | 1174.99 | 72.95 | 549.56 | 162.75 | 386.81 | 0.00 | 0.00 |
September | 1132.55 | 74.09 | 514.74 | 142.77 | 371.98 | 0.00 | 0.00 |
October | 1016.35 | 92.34 | 483.44 | 124.62 | 358.82 | 0.00 | 0.00 |
November | 999.58 | 111.70 | 471.46 | 128.58 | 342.88 | 0.00 | 0.00 |
December | 1022.26 | 177.31 | 482.50 | 157.83 | 324.66 | 0.00 | 0.00 |
Annual Sum or Average | 1191.31 | 94.81 | 543.03 | 173.53 | 369.51 | 0.00 | 0.00 |
Minimum of Months | 999.58 | 44.34 | 471.46 | 119.20 | 324.66 | 0.00 | 0.00 |
Maximum of Months | 1445.25 | 177.31 | 643.03 | 252.73 | 396.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 913.69 | 215.35 | 399.04 | 0.00 | 399.04 | 0.00 | 0.00 |
February | 1025.54 | 164.97 | 425.67 | 0.00 | 425.67 | 0.00 | 0.00 |
March | 1119.32 | 108.46 | 436.87 | 0.00 | 436.87 | 0.00 | 0.00 |
April | 1257.10 | 47.19 | 475.43 | 6.74 | 468.69 | 0.00 | 0.00 |
May | 1600.10 | 57.62 | 609.44 | 64.92 | 544.52 | 0.00 | 0.00 |
June | 1899.14 | 64.70 | 744.45 | 150.45 | 594.01 | 0.00 | 0.00 |
July | 1490.49 | 115.65 | 640.16 | 67.10 | 573.06 | 0.00 | 0.00 |
August | 1246.15 | 88.92 | 527.06 | 22.47 | 504.59 | 0.00 | 0.00 |
September | 1097.49 | 88.65 | 448.73 | 0.21 | 448.52 | 0.00 | 0.00 |
October | 976.07 | 118.01 | 432.37 | 0.00 | 432.37 | 0.00 | 0.00 |
November | 931.50 | 146.28 | 409.12 | 0.00 | 409.12 | 0.00 | 0.00 |
December | 878.41 | 237.22 | 387.67 | 0.00 | 387.67 | 0.00 | 0.00 |
Annual Sum or Average | 1203.35 | 121.10 | 494.96 | 26.06 | 468.90 | 0.00 | 0.00 |
Minimum of Months | 878.41 | 47.19 | 387.67 | 0.00 | 387.67 | 0.00 | 0.00 |
Maximum of Months | 1899.14 | 237.22 | 744.45 | 150.45 | 594.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1072.56 | 137.59 | 512.98 | 172.89 | 340.09 | 0.00 | 0.00 |
February | 1247.62 | 104.32 | 581.72 | 213.29 | 368.43 | 0.00 | 0.00 |
March | 1397.37 | 68.39 | 634.18 | 248.34 | 385.84 | 0.00 | 0.00 |
April | 1451.74 | 30.68 | 640.94 | 244.87 | 396.07 | 0.00 | 0.00 |
May | 1300.03 | 38.21 | 550.94 | 166.77 | 384.17 | 0.00 | 0.00 |
June | 1367.03 | 41.96 | 586.80 | 193.26 | 393.54 | 0.00 | 0.00 |
July | 1095.62 | 76.01 | 501.21 | 112.28 | 388.93 | 0.00 | 0.00 |
August | 1187.22 | 59.95 | 551.59 | 162.14 | 389.45 | 0.00 | 0.00 |
September | 1146.11 | 61.01 | 518.01 | 141.16 | 376.85 | 0.00 | 0.00 |
October | 1020.04 | 80.65 | 485.49 | 124.21 | 361.29 | 0.00 | 0.00 |
November | 991.45 | 98.58 | 469.86 | 129.84 | 340.01 | 0.00 | 0.00 |
December | 999.84 | 154.02 | 480.82 | 154.30 | 326.52 | 0.00 | 0.00 |
Annual Sum or Average | 1188.70 | 79.31 | 542.44 | 171.55 | 370.89 | 0.00 | 0.00 |
Minimum of Months | 991.45 | 30.68 | 469.86 | 112.28 | 326.52 | 0.00 | 0.00 |
Maximum of Months | 1451.74 | 154.02 | 640.94 | 248.34 | 396.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2239.61 | 218.12 | 1056.52 | 440.79 | 615.73 | 0.00 | 0.00 |
February | 2052.43 | 163.29 | 897.15 | 292.50 | 604.64 | 0.00 | 0.00 |
March | 1558.31 | 103.71 | 612.25 | 82.23 | 530.03 | 0.00 | 0.00 |
April | 1224.01 | 42.58 | 456.46 | 0.20 | 456.26 | 0.00 | 0.00 |
May | 1255.89 | 53.23 | 456.77 | 0.00 | 456.77 | 0.00 | 0.00 |
June | 1248.28 | 57.58 | 455.13 | 0.00 | 455.13 | 0.00 | 0.00 |
July | 1109.97 | 109.98 | 468.85 | 0.00 | 468.85 | 0.00 | 0.00 |
August | 1087.45 | 82.86 | 456.43 | 0.71 | 455.73 | 0.00 | 0.00 |
September | 1228.34 | 88.91 | 505.30 | 16.50 | 488.80 | 0.00 | 0.00 |
October | 1470.01 | 123.64 | 661.08 | 105.40 | 555.68 | 0.00 | 0.00 |
November | 1856.30 | 154.72 | 859.63 | 262.26 | 597.37 | 0.00 | 0.00 |
December | 2204.03 | 244.36 | 1055.98 | 449.28 | 606.70 | 0.00 | 0.00 |
Annual Sum or Average | 1542.08 | 120.27 | 660.88 | 136.96 | 523.92 | 0.00 | 0.00 |
Minimum of Months | 1087.45 | 42.58 | 455.13 | 0.00 | 455.13 | 0.00 | 0.00 |
Maximum of Months | 2239.61 | 244.36 | 1056.52 | 449.28 | 615.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1105.12 | 153.41 | 519.76 | 182.76 | 336.99 | 0.00 | 0.00 |
February | 1243.12 | 117.84 | 570.84 | 202.01 | 368.84 | 0.00 | 0.00 |
March | 1421.18 | 83.37 | 639.87 | 252.74 | 387.14 | 0.00 | 0.00 |
April | 1449.25 | 37.72 | 643.04 | 246.29 | 396.75 | 0.00 | 0.00 |
May | 1286.51 | 39.21 | 547.15 | 162.10 | 385.06 | 0.00 | 0.00 |
June | 1373.60 | 43.58 | 592.91 | 204.36 | 388.55 | 0.00 | 0.00 |
July | 1105.92 | 79.38 | 505.49 | 119.21 | 386.28 | 0.00 | 0.00 |
August | 1179.82 | 62.08 | 549.57 | 162.75 | 386.81 | 0.00 | 0.00 |
September | 1137.19 | 64.67 | 514.75 | 142.77 | 371.98 | 0.00 | 0.00 |
October | 1018.13 | 85.51 | 483.45 | 124.62 | 358.83 | 0.00 | 0.00 |
November | 1001.57 | 104.47 | 471.46 | 128.58 | 342.88 | 0.00 | 0.00 |
December | 1023.98 | 167.51 | 482.50 | 157.84 | 324.67 | 0.00 | 0.00 |
Annual Sum or Average | 1194.56 | 86.57 | 543.04 | 173.53 | 369.51 | 0.00 | 0.00 |
Minimum of Months | 1001.57 | 37.72 | 471.46 | 119.21 | 324.67 | 0.00 | 0.00 |
Maximum of Months | 1449.25 | 167.51 | 643.04 | 252.74 | 396.75 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.242811E+10 | 0.558696E+09 | 0.106880E+10 | 0.00 | 0.106880E+10 | 0.00 | 0.00 |
February | 0.246020E+10 | 0.383493E+09 | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.00 | 0.00 |
March | 0.296916E+10 | 0.283884E+09 | 0.117011E+10 | 0.00 | 0.117011E+10 | 0.00 | 0.00 |
April | 0.321976E+10 | 0.122222E+09 | 0.123231E+10 | 17464121.58 | 0.121484E+10 | 0.00 | 0.00 |
May | 0.424878E+10 | 0.152937E+09 | 0.163233E+10 | 0.173892E+09 | 0.145844E+10 | 0.00 | 0.00 |
June | 0.488513E+10 | 0.169590E+09 | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.00 | 0.00 |
July | 0.395760E+10 | 0.307291E+09 | 0.171460E+10 | 0.179721E+09 | 0.153488E+10 | 0.00 | 0.00 |
August | 0.331352E+10 | 0.232033E+09 | 0.141168E+10 | 60195066.80 | 0.135148E+10 | 0.00 | 0.00 |
September | 0.281575E+10 | 0.227691E+09 | 0.116312E+10 | 556964.20 | 0.116256E+10 | 0.00 | 0.00 |
October | 0.258963E+10 | 0.311258E+09 | 0.115807E+10 | 0.00 | 0.115807E+10 | 0.00 | 0.00 |
November | 0.239498E+10 | 0.364089E+09 | 0.106044E+10 | 0.00 | 0.106044E+10 | 0.00 | 0.00 |
December | 0.233747E+10 | 0.610501E+09 | 0.103832E+10 | 0.00 | 0.103832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.376201E+11 | 0.372369E+10 | 0.156092E+11 | 0.821791E+09 | 0.147874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233747E+10 | 0.122222E+09 | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.488513E+10 | 0.610501E+09 | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286961E+10 | 0.357179E+09 | 0.137397E+10 | 0.463066E+09 | 0.910900E+09 | 0.00 | 0.00 |
February | 0.301303E+10 | 0.241360E+09 | 0.140729E+10 | 0.515982E+09 | 0.891308E+09 | 0.00 | 0.00 |
March | 0.373217E+10 | 0.176619E+09 | 0.169859E+10 | 0.665161E+09 | 0.103343E+10 | 0.00 | 0.00 |
April | 0.374701E+10 | 78020543.09 | 0.166131E+10 | 0.634691E+09 | 0.102662E+10 | 0.00 | 0.00 |
May | 0.346885E+10 | 0.100578E+09 | 0.147565E+10 | 0.446675E+09 | 0.102897E+10 | 0.00 | 0.00 |
June | 0.353029E+10 | 0.109164E+09 | 0.152099E+10 | 0.500933E+09 | 0.102006E+10 | 0.00 | 0.00 |
July | 0.292352E+10 | 0.200860E+09 | 0.134244E+10 | 0.300739E+09 | 0.104170E+10 | 0.00 | 0.00 |
August | 0.317450E+10 | 0.155427E+09 | 0.147738E+10 | 0.434287E+09 | 0.104309E+10 | 0.00 | 0.00 |
September | 0.296148E+10 | 0.155910E+09 | 0.134268E+10 | 0.365887E+09 | 0.976797E+09 | 0.00 | 0.00 |
October | 0.272579E+10 | 0.211912E+09 | 0.130034E+10 | 0.332673E+09 | 0.967667E+09 | 0.00 | 0.00 |
November | 0.256611E+10 | 0.245130E+09 | 0.121787E+10 | 0.336554E+09 | 0.881318E+09 | 0.00 | 0.00 |
December | 0.267728E+10 | 0.396974E+09 | 0.128784E+10 | 0.413280E+09 | 0.874559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373896E+11 | 0.242914E+10 | 0.171063E+11 | 0.540993E+10 | 0.116964E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256611E+10 | 78020543.09 | 0.121787E+10 | 0.300739E+09 | 0.874559E+09 | 0.00 | 0.00 |
Maximum of Months | 0.374701E+10 | 0.396974E+09 | 0.169859E+10 | 0.665161E+09 | 0.104309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598388E+10 | 0.567527E+09 | 0.282979E+10 | 0.118062E+10 | 0.164917E+10 | 0.00 | 0.00 |
February | 0.494558E+10 | 0.379672E+09 | 0.217038E+10 | 0.707624E+09 | 0.146275E+10 | 0.00 | 0.00 |
March | 0.414273E+10 | 0.269572E+09 | 0.163985E+10 | 0.220233E+09 | 0.141962E+10 | 0.00 | 0.00 |
April | 0.313426E+10 | 0.109267E+09 | 0.118315E+10 | 531125.50 | 0.118262E+10 | 0.00 | 0.00 |
May | 0.332796E+10 | 0.140506E+09 | 0.122342E+10 | 0.00 | 0.122342E+10 | 0.00 | 0.00 |
June | 0.320058E+10 | 0.150420E+09 | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.00 | 0.00 |
July | 0.293901E+10 | 0.291519E+09 | 0.125577E+10 | 0.00 | 0.125577E+10 | 0.00 | 0.00 |
August | 0.288898E+10 | 0.214789E+09 | 0.122251E+10 | 1889408.72 | 0.122062E+10 | 0.00 | 0.00 |
September | 0.315365E+10 | 0.228277E+09 | 0.130974E+10 | 42777181.36 | 0.126697E+10 | 0.00 | 0.00 |
October | 0.391009E+10 | 0.326971E+09 | 0.177064E+10 | 0.282315E+09 | 0.148833E+10 | 0.00 | 0.00 |
November | 0.479176E+10 | 0.386993E+09 | 0.222815E+10 | 0.679778E+09 | 0.154837E+10 | 0.00 | 0.00 |
December | 0.589108E+10 | 0.632693E+09 | 0.282834E+10 | 0.120334E+10 | 0.162500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.483096E+11 | 0.369821E+10 | 0.208414E+11 | 0.431911E+10 | 0.165223E+11 | 0.00 | 0.00 |
Minimum of Months | 0.288898E+10 | 0.109267E+09 | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.598388E+10 | 0.632693E+09 | 0.282979E+10 | 0.120334E+10 | 0.164917E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294554E+10 | 0.399008E+09 | 0.139212E+10 | 0.489515E+09 | 0.902607E+09 | 0.00 | 0.00 |
February | 0.299077E+10 | 0.274897E+09 | 0.138099E+10 | 0.488699E+09 | 0.892288E+09 | 0.00 | 0.00 |
March | 0.378482E+10 | 0.218831E+09 | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.00 | 0.00 |
April | 0.373011E+10 | 98190766.21 | 0.166676E+10 | 0.638392E+09 | 0.102836E+10 | 0.00 | 0.00 |
May | 0.342072E+10 | 0.103838E+09 | 0.146550E+10 | 0.434160E+09 | 0.103134E+10 | 0.00 | 0.00 |
June | 0.353475E+10 | 0.113675E+09 | 0.153682E+10 | 0.529707E+09 | 0.100712E+10 | 0.00 | 0.00 |
July | 0.293822E+10 | 0.210337E+09 | 0.135390E+10 | 0.319280E+09 | 0.103462E+10 | 0.00 | 0.00 |
August | 0.314156E+10 | 0.161535E+09 | 0.147195E+10 | 0.435910E+09 | 0.103605E+10 | 0.00 | 0.00 |
September | 0.292634E+10 | 0.166367E+09 | 0.133423E+10 | 0.370056E+09 | 0.964172E+09 | 0.00 | 0.00 |
October | 0.270907E+10 | 0.225902E+09 | 0.129487E+10 | 0.333790E+09 | 0.961082E+09 | 0.00 | 0.00 |
November | 0.258182E+10 | 0.261093E+09 | 0.122203E+10 | 0.333284E+09 | 0.888744E+09 | 0.00 | 0.00 |
December | 0.273100E+10 | 0.432635E+09 | 0.129234E+10 | 0.422747E+09 | 0.869591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374347E+11 | 0.266631E+10 | 0.171253E+11 | 0.547247E+10 | 0.116529E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258182E+10 | 98190766.21 | 0.122203E+10 | 0.319280E+09 | 0.869591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.378482E+10 | 0.432635E+09 | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244120E+10 | 0.581009E+09 | 0.106877E+10 | 0.00 | 0.106877E+10 | 0.00 | 0.00 |
February | 0.247459E+10 | 0.405969E+09 | 0.102976E+10 | 0.00 | 0.102976E+10 | 0.00 | 0.00 |
March | 0.298886E+10 | 0.296589E+09 | 0.117008E+10 | 0.00 | 0.117008E+10 | 0.00 | 0.00 |
April | 0.324525E+10 | 0.126743E+09 | 0.123228E+10 | 17463608.27 | 0.121482E+10 | 0.00 | 0.00 |
May | 0.426772E+10 | 0.169040E+09 | 0.163229E+10 | 0.173887E+09 | 0.145840E+10 | 0.00 | 0.00 |
June | 0.489914E+10 | 0.189806E+09 | 0.192958E+10 | 0.389950E+09 | 0.153963E+10 | 0.00 | 0.00 |
July | 0.397589E+10 | 0.338234E+09 | 0.171456E+10 | 0.179716E+09 | 0.153485E+10 | 0.00 | 0.00 |
August | 0.331446E+10 | 0.264870E+09 | 0.141165E+10 | 60193297.51 | 0.135145E+10 | 0.00 | 0.00 |
September | 0.282425E+10 | 0.249409E+09 | 0.116309E+10 | 556947.83 | 0.116254E+10 | 0.00 | 0.00 |
October | 0.260694E+10 | 0.323988E+09 | 0.115804E+10 | 0.00 | 0.115804E+10 | 0.00 | 0.00 |
November | 0.240721E+10 | 0.388805E+09 | 0.106042E+10 | 0.00 | 0.106042E+10 | 0.00 | 0.00 |
December | 0.234387E+10 | 0.651283E+09 | 0.103830E+10 | 0.00 | 0.103830E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.377894E+11 | 0.398575E+10 | 0.156088E+11 | 0.821767E+09 | 0.147871E+11 | 0.00 | 0.00 |
Minimum of Months | 0.234387E+10 | 0.126743E+09 | 0.102976E+10 | 0.00 | 0.102976E+10 | 0.00 | 0.00 |
Maximum of Months | 0.489914E+10 | 0.651283E+09 | 0.192958E+10 | 0.389950E+09 | 0.153963E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287966E+10 | 0.385767E+09 | 0.137395E+10 | 0.463057E+09 | 0.910888E+09 | 0.00 | 0.00 |
February | 0.302301E+10 | 0.271387E+09 | 0.140727E+10 | 0.515972E+09 | 0.891297E+09 | 0.00 | 0.00 |
March | 0.375006E+10 | 0.205353E+09 | 0.169857E+10 | 0.665148E+09 | 0.103342E+10 | 0.00 | 0.00 |
April | 0.376214E+10 | 93589512.09 | 0.166129E+10 | 0.634678E+09 | 0.102661E+10 | 0.00 | 0.00 |
May | 0.347785E+10 | 0.115234E+09 | 0.147562E+10 | 0.446667E+09 | 0.102896E+10 | 0.00 | 0.00 |
June | 0.353873E+10 | 0.124756E+09 | 0.152097E+10 | 0.500923E+09 | 0.102004E+10 | 0.00 | 0.00 |
July | 0.293377E+10 | 0.225044E+09 | 0.134242E+10 | 0.300733E+09 | 0.104168E+10 | 0.00 | 0.00 |
August | 0.317749E+10 | 0.185835E+09 | 0.147736E+10 | 0.434278E+09 | 0.104308E+10 | 0.00 | 0.00 |
September | 0.296802E+10 | 0.180950E+09 | 0.134266E+10 | 0.365880E+09 | 0.976784E+09 | 0.00 | 0.00 |
October | 0.273845E+10 | 0.231885E+09 | 0.130032E+10 | 0.332667E+09 | 0.967654E+09 | 0.00 | 0.00 |
November | 0.257592E+10 | 0.272623E+09 | 0.121785E+10 | 0.336547E+09 | 0.881306E+09 | 0.00 | 0.00 |
December | 0.268439E+10 | 0.435287E+09 | 0.128782E+10 | 0.413272E+09 | 0.874548E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375095E+11 | 0.272771E+10 | 0.171061E+11 | 0.540982E+10 | 0.116963E+11 | 0.00 | 0.00 |
Minimum of Months | 0.257592E+10 | 93589512.09 | 0.121785E+10 | 0.300733E+09 | 0.874548E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376214E+10 | 0.435287E+09 | 0.169857E+10 | 0.665148E+09 | 0.104308E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.594448E+10 | 0.646398E+09 | 0.282968E+10 | 0.118057E+10 | 0.164911E+10 | 0.00 | 0.00 |
February | 0.490202E+10 | 0.449105E+09 | 0.217030E+10 | 0.707595E+09 | 0.146270E+10 | 0.00 | 0.00 |
March | 0.411201E+10 | 0.314551E+09 | 0.163980E+10 | 0.220224E+09 | 0.141958E+10 | 0.00 | 0.00 |
April | 0.311967E+10 | 0.122287E+09 | 0.118312E+10 | 531103.46 | 0.118259E+10 | 0.00 | 0.00 |
May | 0.330447E+10 | 0.158057E+09 | 0.122339E+10 | 0.00 | 0.122339E+10 | 0.00 | 0.00 |
June | 0.316689E+10 | 0.166328E+09 | 0.117966E+10 | 0.00 | 0.117966E+10 | 0.00 | 0.00 |
July | 0.293727E+10 | 0.320822E+09 | 0.125574E+10 | 0.00 | 0.125574E+10 | 0.00 | 0.00 |
August | 0.286483E+10 | 0.252305E+09 | 0.122247E+10 | 1889330.31 | 0.122058E+10 | 0.00 | 0.00 |
September | 0.314043E+10 | 0.259135E+09 | 0.130970E+10 | 42775406.21 | 0.126693E+10 | 0.00 | 0.00 |
October | 0.390671E+10 | 0.360940E+09 | 0.177058E+10 | 0.282304E+09 | 0.148828E+10 | 0.00 | 0.00 |
November | 0.476530E+10 | 0.447836E+09 | 0.222807E+10 | 0.679750E+09 | 0.154832E+10 | 0.00 | 0.00 |
December | 0.585986E+10 | 0.725165E+09 | 0.282823E+10 | 0.120329E+10 | 0.162494E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.480239E+11 | 0.422293E+10 | 0.208408E+11 | 0.431893E+10 | 0.165218E+11 | 0.00 | 0.00 |
Minimum of Months | 0.286483E+10 | 0.122287E+09 | 0.117966E+10 | 0.00 | 0.117966E+10 | 0.00 | 0.00 |
Maximum of Months | 0.594448E+10 | 0.725165E+09 | 0.282968E+10 | 0.120329E+10 | 0.164911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295683E+10 | 0.430421E+09 | 0.139210E+10 | 0.489507E+09 | 0.902597E+09 | 0.00 | 0.00 |
February | 0.300352E+10 | 0.306970E+09 | 0.138097E+10 | 0.488691E+09 | 0.892279E+09 | 0.00 | 0.00 |
March | 0.380177E+10 | 0.247298E+09 | 0.171382E+10 | 0.676922E+09 | 0.103689E+10 | 0.00 | 0.00 |
April | 0.374610E+10 | 0.114935E+09 | 0.166673E+10 | 0.638381E+09 | 0.102835E+10 | 0.00 | 0.00 |
May | 0.343074E+10 | 0.121249E+09 | 0.146548E+10 | 0.434153E+09 | 0.103133E+10 | 0.00 | 0.00 |
June | 0.354389E+10 | 0.132217E+09 | 0.153680E+10 | 0.529698E+09 | 0.100711E+10 | 0.00 | 0.00 |
July | 0.295251E+10 | 0.237589E+09 | 0.135388E+10 | 0.319274E+09 | 0.103460E+10 | 0.00 | 0.00 |
August | 0.314709E+10 | 0.195392E+09 | 0.147194E+10 | 0.435903E+09 | 0.103603E+10 | 0.00 | 0.00 |
September | 0.293558E+10 | 0.192031E+09 | 0.133421E+10 | 0.370050E+09 | 0.964161E+09 | 0.00 | 0.00 |
October | 0.272220E+10 | 0.247318E+09 | 0.129486E+10 | 0.333785E+09 | 0.961071E+09 | 0.00 | 0.00 |
November | 0.259090E+10 | 0.289517E+09 | 0.122201E+10 | 0.333279E+09 | 0.888734E+09 | 0.00 | 0.00 |
December | 0.273802E+10 | 0.474910E+09 | 0.129232E+10 | 0.422740E+09 | 0.869582E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375691E+11 | 0.298985E+10 | 0.171251E+11 | 0.547238E+10 | 0.116527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259090E+10 | 0.114935E+09 | 0.122201E+10 | 0.319274E+09 | 0.869582E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380177E+10 | 0.474910E+09 | 0.171382E+10 | 0.676922E+09 | 0.103689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244724E+10 | 0.576795E+09 | 0.106880E+10 | 0.00 | 0.106880E+10 | 0.00 | 0.00 |
February | 0.248099E+10 | 0.399093E+09 | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.00 | 0.00 |
March | 0.299799E+10 | 0.290491E+09 | 0.117011E+10 | 0.00 | 0.117011E+10 | 0.00 | 0.00 |
April | 0.325841E+10 | 0.122313E+09 | 0.123231E+10 | 17464121.58 | 0.121484E+10 | 0.00 | 0.00 |
May | 0.428571E+10 | 0.154326E+09 | 0.163233E+10 | 0.173892E+09 | 0.145844E+10 | 0.00 | 0.00 |
June | 0.492257E+10 | 0.167691E+09 | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.00 | 0.00 |
July | 0.399213E+10 | 0.309762E+09 | 0.171460E+10 | 0.179721E+09 | 0.153488E+10 | 0.00 | 0.00 |
August | 0.333769E+10 | 0.238169E+09 | 0.141168E+10 | 60195066.80 | 0.135148E+10 | 0.00 | 0.00 |
September | 0.284470E+10 | 0.229781E+09 | 0.116312E+10 | 556964.20 | 0.116256E+10 | 0.00 | 0.00 |
October | 0.261431E+10 | 0.316072E+09 | 0.115807E+10 | 0.00 | 0.115807E+10 | 0.00 | 0.00 |
November | 0.241445E+10 | 0.379160E+09 | 0.106044E+10 | 0.00 | 0.106044E+10 | 0.00 | 0.00 |
December | 0.235272E+10 | 0.635363E+09 | 0.103832E+10 | 0.00 | 0.103832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.379489E+11 | 0.381902E+10 | 0.156092E+11 | 0.821791E+09 | 0.147874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.235272E+10 | 0.122313E+09 | 0.102978E+10 | 0.00 | 0.102978E+10 | 0.00 | 0.00 |
Maximum of Months | 0.492257E+10 | 0.635363E+09 | 0.192962E+10 | 0.389962E+09 | 0.153966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.287274E+10 | 0.368521E+09 | 0.137397E+10 | 0.463066E+09 | 0.910900E+09 | 0.00 | 0.00 |
February | 0.301824E+10 | 0.252380E+09 | 0.140729E+10 | 0.515982E+09 | 0.891308E+09 | 0.00 | 0.00 |
March | 0.374272E+10 | 0.183186E+09 | 0.169859E+10 | 0.665161E+09 | 0.103343E+10 | 0.00 | 0.00 |
April | 0.376292E+10 | 79516932.65 | 0.166131E+10 | 0.634691E+09 | 0.102662E+10 | 0.00 | 0.00 |
May | 0.348200E+10 | 0.102354E+09 | 0.147565E+10 | 0.446675E+09 | 0.102897E+10 | 0.00 | 0.00 |
June | 0.354334E+10 | 0.108748E+09 | 0.152099E+10 | 0.500933E+09 | 0.102006E+10 | 0.00 | 0.00 |
July | 0.293452E+10 | 0.203594E+09 | 0.134244E+10 | 0.300739E+09 | 0.104170E+10 | 0.00 | 0.00 |
August | 0.317984E+10 | 0.160558E+09 | 0.147738E+10 | 0.434287E+09 | 0.104309E+10 | 0.00 | 0.00 |
September | 0.297071E+10 | 0.158130E+09 | 0.134268E+10 | 0.365887E+09 | 0.976797E+09 | 0.00 | 0.00 |
October | 0.273206E+10 | 0.216022E+09 | 0.130034E+10 | 0.332673E+09 | 0.967667E+09 | 0.00 | 0.00 |
November | 0.256984E+10 | 0.255520E+09 | 0.121787E+10 | 0.336554E+09 | 0.881318E+09 | 0.00 | 0.00 |
December | 0.267797E+10 | 0.412522E+09 | 0.128784E+10 | 0.413280E+09 | 0.874559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374869E+11 | 0.250105E+10 | 0.171063E+11 | 0.540993E+10 | 0.116964E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256984E+10 | 79516932.65 | 0.121787E+10 | 0.300739E+09 | 0.874559E+09 | 0.00 | 0.00 |
Maximum of Months | 0.376292E+10 | 0.412522E+09 | 0.169859E+10 | 0.665161E+09 | 0.104309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.599858E+10 | 0.584216E+09 | 0.282979E+10 | 0.118062E+10 | 0.164917E+10 | 0.00 | 0.00 |
February | 0.496524E+10 | 0.395042E+09 | 0.217038E+10 | 0.707624E+09 | 0.146275E+10 | 0.00 | 0.00 |
March | 0.417377E+10 | 0.277787E+09 | 0.163985E+10 | 0.220233E+09 | 0.141962E+10 | 0.00 | 0.00 |
April | 0.317263E+10 | 0.110362E+09 | 0.118315E+10 | 531125.50 | 0.118262E+10 | 0.00 | 0.00 |
May | 0.336378E+10 | 0.142582E+09 | 0.122342E+10 | 0.00 | 0.122342E+10 | 0.00 | 0.00 |
June | 0.323555E+10 | 0.149254E+09 | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.00 | 0.00 |
July | 0.297294E+10 | 0.294578E+09 | 0.125577E+10 | 0.00 | 0.125577E+10 | 0.00 | 0.00 |
August | 0.291263E+10 | 0.221938E+09 | 0.122251E+10 | 1889408.72 | 0.122062E+10 | 0.00 | 0.00 |
September | 0.318386E+10 | 0.230443E+09 | 0.130974E+10 | 42777181.36 | 0.126697E+10 | 0.00 | 0.00 |
October | 0.393728E+10 | 0.331171E+09 | 0.177064E+10 | 0.282315E+09 | 0.148833E+10 | 0.00 | 0.00 |
November | 0.481154E+10 | 0.401030E+09 | 0.222815E+10 | 0.679778E+09 | 0.154837E+10 | 0.00 | 0.00 |
December | 0.590327E+10 | 0.654500E+09 | 0.282834E+10 | 0.120334E+10 | 0.162500E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.486311E+11 | 0.379290E+10 | 0.208414E+11 | 0.431911E+10 | 0.165223E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291263E+10 | 0.110362E+09 | 0.117970E+10 | 0.00 | 0.117970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.599858E+10 | 0.654500E+09 | 0.282979E+10 | 0.120334E+10 | 0.164917E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295996E+10 | 0.410905E+09 | 0.139212E+10 | 0.489515E+09 | 0.902607E+09 | 0.00 | 0.00 |
February | 0.300735E+10 | 0.285079E+09 | 0.138099E+10 | 0.488699E+09 | 0.892288E+09 | 0.00 | 0.00 |
March | 0.380650E+10 | 0.223294E+09 | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.00 | 0.00 |
April | 0.375645E+10 | 97770061.07 | 0.166676E+10 | 0.638392E+09 | 0.102836E+10 | 0.00 | 0.00 |
May | 0.344579E+10 | 0.105022E+09 | 0.146550E+10 | 0.434160E+09 | 0.103134E+10 | 0.00 | 0.00 |
June | 0.356038E+10 | 0.112952E+09 | 0.153682E+10 | 0.529707E+09 | 0.100712E+10 | 0.00 | 0.00 |
July | 0.296210E+10 | 0.212605E+09 | 0.135390E+10 | 0.319280E+09 | 0.103462E+10 | 0.00 | 0.00 |
August | 0.316003E+10 | 0.166287E+09 | 0.147195E+10 | 0.435910E+09 | 0.103605E+10 | 0.00 | 0.00 |
September | 0.294759E+10 | 0.167616E+09 | 0.133423E+10 | 0.370056E+09 | 0.964172E+09 | 0.00 | 0.00 |
October | 0.272696E+10 | 0.229030E+09 | 0.129487E+10 | 0.333790E+09 | 0.961082E+09 | 0.00 | 0.00 |
November | 0.259606E+10 | 0.270777E+09 | 0.122203E+10 | 0.333284E+09 | 0.888744E+09 | 0.00 | 0.00 |
December | 0.274263E+10 | 0.448648E+09 | 0.129234E+10 | 0.422747E+09 | 0.869591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376718E+11 | 0.272999E+10 | 0.171253E+11 | 0.547247E+10 | 0.116529E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259606E+10 | 97770061.07 | 0.122203E+10 | 0.319280E+09 | 0.869591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380650E+10 | 0.448648E+09 | 0.171384E+10 | 0.676933E+09 | 0.103690E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.309158E+10 | -0.286027E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231306970.8 | 60.05 | 0.00 | 0.00 |
February | 0.279267E+10 | -0.258354E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209133766.0 | 60.05 | 0.00 | 0.00 |
March | 0.324423E+10 | -0.301192E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232311479.1 | 60.05 | 0.00 | 0.00 |
April | 0.287815E+10 | -0.265355E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224593657.7 | 60.05 | 0.00 | 0.00 |
May | 0.301872E+10 | -0.278642E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232302501.5 | 60.05 | 0.00 | 0.00 |
June | 0.295358E+10 | -0.272880E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224782922.2 | 60.05 | 0.00 | 0.00 |
July | 0.278961E+10 | -0.255790E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231707486.6 | 60.05 | 0.00 | 0.00 |
August | 0.308041E+10 | -0.284818E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232229102.7 | 60.05 | 0.00 | 0.00 |
September | 0.283122E+10 | -0.260680E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224420303.8 | 60.05 | 0.00 | 0.00 |
October | 0.298231E+10 | -0.275070E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231605714.9 | 60.05 | 0.00 | 0.00 |
November | 0.298546E+10 | -0.276145E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224011949.1 | 60.05 | 0.00 | 0.00 |
December | 0.300247E+10 | -0.277121E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231262645.4 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.356504E+11 | -0.329208E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.272967E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.278961E+10 | -0.301192E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -232311479.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.324423E+10 | -0.255790E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209133766.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:30 | 2207.23 | 25.15 | 147.67 | 322.83 | 1089.07 | 24.83 | 304.00 | 311.50 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:00 | 1741.31 | 19.00 | 0.00 | 293.83 | 920.80 | 21.19 | 196.83 | 272.83 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-07:40 | 1316.04 | 18.80 | 0.00 | 326.50 | 733.59 | 20.90 | 159.17 | 299.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1079.19 | 18.45 | 0.00 | 323.00 | 613.29 | 20.58 | 66.83 | 286.83 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:49 | 923.75 | 17.35 | 0.00 | 329.67 | 514.35 | 19.45 | 0.00 | 281.67 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:30 | 902.10 | 17.53 | 0.00 | 323.00 | 518.83 | 19.69 | 0.00 | 276.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:10 | 873.98 | 16.91 | 0.00 | 326.00 | 475.10 | 18.97 | 0.00 | 274.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:00 | 1033.40 | 17.86 | 0.00 | 327.67 | 566.01 | 19.95 | 32.00 | 286.33 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1168.10 | 17.72 | 0.00 | 313.50 | 615.16 | 19.76 | 83.83 | 275.17 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1513.16 | 19.17 | 15.00 | 324.00 | 770.09 | 20.73 | 143.50 | 286.00 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-06:00 | 1912.48 | 23.55 | 114.83 | 312.83 | 937.72 | 21.72 | 231.83 | 281.33 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2216.50 | 25.18 | 148.67 | 319.67 | 1089.04 | 24.77 | 300.67 | 303.67 |
Annual Sum or Average | 4292.33 | 0.51 | 1391.25 | 19.65 | 426.17 | 3842.50 | 729.49 | 21.00 | 1518.67 | 3436.00 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 873.98 | 16.91 | 0.00 | 293.83 | 475.10 | 18.97 | 0.00 | 272.83 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2216.50 | 25.18 | 148.67 | 329.67 | 1089.07 | 24.83 | 304.00 | 311.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:10 | 1855.18 | 21.58 | 108.50 | 308.17 | 973.64 | 22.50 | 77.50 | 272.67 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2058.50 | 21.69 | 99.00 | 286.17 | 1084.46 | 22.61 | 71.17 | 258.50 |
March | 361.17 | 0.50 | 0.48 | 01-MAR-06:00 | 2336.21 | 21.73 | 112.17 | 321.50 | 970.16 | 21.24 | 52.17 | 293.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:10 | 1926.31 | 19.97 | 84.17 | 328.33 | 1010.20 | 21.21 | 54.33 | 296.50 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:49 | 1651.30 | 19.19 | 87.33 | 337.83 | 864.12 | 21.38 | 67.33 | 298.33 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-06:40 | 1771.80 | 19.60 | 84.50 | 334.17 | 933.28 | 21.66 | 63.33 | 300.17 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1473.40 | 18.87 | 86.67 | 336.00 | 757.36 | 20.87 | 64.17 | 293.50 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1680.35 | 19.54 | 86.00 | 336.17 | 870.62 | 20.77 | 55.00 | 298.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1586.23 | 18.95 | 83.67 | 313.67 | 812.17 | 20.12 | 54.50 | 274.50 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1584.16 | 19.50 | 86.17 | 315.67 | 808.58 | 20.64 | 55.17 | 275.67 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:30 | 1597.67 | 20.15 | 84.50 | 298.17 | 802.46 | 21.01 | 51.33 | 259.50 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-06:30 | 1803.63 | 21.66 | 112.50 | 301.67 | 827.23 | 21.39 | 56.00 | 267.50 |
Annual Sum or Average | 4292.33 | 0.51 | 1773.21 | 20.17 | 1115.17 | 3817.50 | 890.87 | 21.27 | 722.00 | 3388.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1473.40 | 18.87 | 83.67 | 286.17 | 757.36 | 20.12 | 51.33 | 258.50 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2336.21 | 21.73 | 112.50 | 337.83 | 1084.46 | 22.61 | 77.50 | 300.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-08:09 | 737.19 | 16.49 | 0.00 | 298.00 | 435.35 | 18.66 | 0.00 | 240.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:30 | 811.44 | 17.02 | 0.00 | 279.83 | 481.04 | 19.17 | 0.00 | 240.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 926.86 | 17.95 | 0.00 | 322.67 | 548.73 | 20.07 | 1.17 | 289.17 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1133.19 | 18.92 | 0.00 | 333.00 | 642.01 | 21.03 | 115.50 | 302.67 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1316.52 | 18.73 | 3.83 | 349.33 | 691.45 | 20.80 | 139.50 | 317.00 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-07:10 | 1577.07 | 23.12 | 112.83 | 348.50 | 805.15 | 22.65 | 223.67 | 323.17 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:40 | 1364.44 | 22.64 | 116.00 | 351.33 | 684.89 | 22.81 | 167.50 | 319.50 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1222.04 | 18.64 | 0.00 | 342.50 | 655.51 | 20.73 | 121.33 | 307.83 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:40 | 991.97 | 17.44 | 0.00 | 314.67 | 536.95 | 19.46 | 40.00 | 273.33 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:10 | 876.77 | 17.22 | 0.00 | 311.17 | 481.61 | 19.26 | 0.00 | 260.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-07:30 | 784.76 | 16.84 | 0.00 | 288.17 | 442.14 | 18.92 | 0.00 | 235.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:19 | 717.82 | 16.25 | 0.00 | 290.67 | 418.75 | 18.41 | 0.00 | 232.83 |
Annual Sum or Average | 4292.33 | 0.51 | 1047.77 | 18.51 | 232.67 | 3829.83 | 572.65 | 20.21 | 808.67 | 3342.00 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 717.82 | 16.25 | 0.00 | 279.83 | 418.75 | 18.41 | 0.00 | 232.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1577.07 | 23.12 | 116.00 | 351.33 | 805.15 | 22.81 | 223.67 | 323.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:30 | 1915.31 | 21.73 | 109.33 | 307.33 | 1002.80 | 22.58 | 77.50 | 275.17 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:49 | 2146.58 | 21.66 | 102.33 | 283.33 | 903.30 | 21.04 | 46.67 | 255.00 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:09 | 2382.50 | 21.47 | 112.67 | 331.00 | 987.70 | 20.92 | 51.17 | 297.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2321.49 | 15.22 | 0.00 | 327.67 | 976.48 | 18.56 | 0.00 | 296.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:00 | 1827.80 | 14.95 | 0.00 | 337.17 | 821.80 | 18.06 | 0.00 | 298.00 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:49 | 1723.18 | 15.39 | 0.00 | 332.33 | 902.17 | 18.62 | 0.00 | 299.33 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:30 | 1473.54 | 14.75 | 0.00 | 335.50 | 751.59 | 17.77 | 0.00 | 291.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-07:10 | 1688.73 | 15.55 | 8.50 | 334.33 | 853.20 | 18.25 | 0.00 | 296.00 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1740.30 | 18.75 | 87.00 | 311.50 | 790.01 | 18.00 | 7.67 | 275.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:49 | 1653.05 | 20.63 | 101.67 | 315.33 | 852.37 | 21.85 | 72.67 | 277.67 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:49 | 1633.10 | 19.91 | 85.00 | 299.83 | 846.25 | 21.98 | 66.00 | 263.67 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:30 | 1695.83 | 20.02 | 90.00 | 304.83 | 898.61 | 22.05 | 71.83 | 269.67 |
Annual Sum or Average | 4292.33 | 0.51 | 1846.19 | 18.24 | 696.50 | 3820.17 | 880.99 | 19.92 | 393.50 | 3395.17 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1473.54 | 14.75 | 0.00 | 283.33 | 751.59 | 17.77 | 0.00 | 255.00 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2382.50 | 21.73 | 112.67 | 337.17 | 1002.80 | 22.58 | 77.50 | 299.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:40 | 2116.54 | 22.70 | 147.50 | 322.17 | 1025.85 | 22.64 | 88.50 | 309.17 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:00 | 1665.54 | 15.14 | 0.00 | 293.67 | 869.25 | 18.72 | 0.00 | 271.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:40 | 1263.02 | 15.33 | 0.00 | 325.83 | 700.54 | 18.78 | 0.00 | 297.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1038.65 | 15.06 | 0.00 | 320.00 | 589.76 | 18.52 | 0.00 | 282.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:00 | 890.17 | 13.68 | 0.00 | 326.83 | 494.73 | 17.09 | 0.00 | 277.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:40 | 868.74 | 14.01 | 0.00 | 319.67 | 499.71 | 17.49 | 0.00 | 272.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:10 | 843.15 | 13.08 | 0.00 | 324.00 | 456.80 | 16.48 | 0.00 | 269.33 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:00 | 995.30 | 14.25 | 0.00 | 325.67 | 543.43 | 17.65 | 0.00 | 280.17 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1124.02 | 13.99 | 0.00 | 310.17 | 588.18 | 17.32 | 0.00 | 273.00 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1452.65 | 15.41 | 15.00 | 322.50 | 732.16 | 18.34 | 4.50 | 281.17 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-06:00 | 1833.69 | 20.85 | 114.33 | 312.00 | 891.15 | 20.37 | 39.83 | 282.17 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2124.84 | 22.75 | 148.50 | 318.33 | 1025.19 | 22.53 | 87.50 | 302.50 |
Annual Sum or Average | 4292.33 | 0.51 | 1336.11 | 16.27 | 425.33 | 3820.83 | 694.51 | 18.78 | 220.33 | 3398.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 843.15 | 13.08 | 0.00 | 293.67 | 456.80 | 16.48 | 0.00 | 269.33 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2124.84 | 22.75 | 148.50 | 326.83 | 1025.85 | 22.64 | 88.50 | 309.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:10 | 1798.90 | 21.12 | 108.50 | 306.83 | 934.59 | 22.30 | 77.50 | 269.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2005.78 | 21.25 | 99.00 | 285.33 | 1040.53 | 22.42 | 71.17 | 255.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-06:00 | 2273.06 | 21.29 | 112.17 | 320.50 | 924.30 | 21.07 | 52.17 | 291.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:10 | 1856.21 | 19.50 | 84.17 | 325.33 | 963.73 | 21.05 | 54.33 | 293.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1612.01 | 18.73 | 87.33 | 335.50 | 825.82 | 21.22 | 67.33 | 294.83 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1720.44 | 19.15 | 84.50 | 331.33 | 892.40 | 21.48 | 63.00 | 296.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:19 | 1433.09 | 18.42 | 86.67 | 332.50 | 718.09 | 19.97 | 56.33 | 287.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1632.00 | 19.08 | 86.00 | 334.17 | 830.99 | 20.60 | 55.00 | 294.83 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1526.99 | 18.49 | 83.67 | 312.17 | 775.19 | 19.94 | 54.50 | 271.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1541.21 | 19.02 | 86.17 | 313.50 | 772.40 | 20.44 | 55.17 | 272.00 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:40 | 1547.67 | 19.66 | 84.50 | 295.17 | 766.75 | 20.80 | 51.33 | 256.17 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-06:40 | 1752.11 | 21.20 | 112.50 | 299.67 | 790.66 | 21.17 | 56.00 | 265.17 |
Annual Sum or Average | 4292.33 | 0.51 | 1721.22 | 19.71 | 1115.17 | 3792.00 | 850.98 | 21.02 | 713.83 | 3348.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1433.09 | 18.42 | 83.67 | 285.33 | 718.09 | 19.94 | 51.33 | 255.83 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2273.06 | 21.29 | 112.50 | 335.50 | 1040.53 | 22.42 | 77.50 | 296.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-08:20 | 710.36 | 13.01 | 0.00 | 295.00 | 420.40 | 16.49 | 0.00 | 234.17 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:40 | 782.03 | 13.64 | 0.00 | 277.67 | 464.63 | 17.10 | 0.00 | 235.17 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:00 | 892.69 | 14.67 | 0.00 | 320.00 | 529.60 | 18.12 | 0.00 | 285.67 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1090.34 | 15.51 | 0.00 | 330.67 | 617.01 | 19.02 | 0.00 | 298.50 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1265.99 | 14.90 | 3.83 | 347.00 | 659.92 | 18.28 | 1.17 | 313.50 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-07:10 | 1515.67 | 20.46 | 112.17 | 347.50 | 765.81 | 20.34 | 33.17 | 319.33 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:40 | 1313.35 | 19.88 | 115.50 | 350.00 | 652.41 | 20.54 | 59.17 | 315.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1175.59 | 14.93 | 0.00 | 340.33 | 627.26 | 18.38 | 0.00 | 304.33 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 955.85 | 13.78 | 0.00 | 312.50 | 515.50 | 17.11 | 0.00 | 270.33 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:10 | 845.57 | 13.50 | 0.00 | 309.33 | 463.31 | 16.88 | 0.00 | 255.67 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-07:30 | 756.90 | 13.16 | 0.00 | 286.00 | 426.11 | 16.59 | 0.00 | 228.67 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:19 | 691.76 | 12.69 | 0.00 | 288.83 | 404.13 | 16.15 | 0.00 | 227.00 |
Annual Sum or Average | 4292.33 | 0.51 | 1008.72 | 15.08 | 231.50 | 3804.83 | 549.26 | 17.96 | 93.50 | 3287.50 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 691.76 | 12.69 | 0.00 | 277.67 | 404.13 | 16.15 | 0.00 | 227.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1515.67 | 20.46 | 115.50 | 350.00 | 765.81 | 20.54 | 59.17 | 319.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:30 | 1859.52 | 21.33 | 109.33 | 305.83 | 963.33 | 22.46 | 77.50 | 271.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:00 | 2092.67 | 21.26 | 102.33 | 281.83 | 861.01 | 20.91 | 46.67 | 252.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:20 | 2325.90 | 21.05 | 112.67 | 328.67 | 941.58 | 20.77 | 51.17 | 293.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2243.73 | 14.65 | 0.00 | 325.50 | 930.91 | 18.36 | 0.00 | 293.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:10 | 1788.82 | 14.38 | 0.00 | 335.17 | 784.19 | 17.83 | 0.00 | 293.50 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:00 | 1676.30 | 14.82 | 0.00 | 330.67 | 861.43 | 18.39 | 0.00 | 295.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:40 | 1434.38 | 14.17 | 0.00 | 333.33 | 717.90 | 17.53 | 0.00 | 288.50 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1637.52 | 14.99 | 8.50 | 331.17 | 814.44 | 18.03 | 0.00 | 291.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1681.39 | 18.09 | 85.00 | 310.50 | 753.56 | 17.80 | 7.67 | 270.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:00 | 1593.95 | 18.91 | 87.50 | 312.67 | 816.26 | 21.71 | 72.67 | 274.00 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:00 | 1581.44 | 19.47 | 85.00 | 297.83 | 810.12 | 21.86 | 66.00 | 260.33 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:40 | 1638.96 | 19.36 | 87.33 | 303.50 | 860.67 | 21.93 | 71.83 | 266.83 |
Annual Sum or Average | 4292.33 | 0.51 | 1792.46 | 17.61 | 677.67 | 3796.67 | 841.79 | 19.74 | 393.50 | 3351.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1434.38 | 14.17 | 0.00 | 281.83 | 717.90 | 17.53 | 0.00 | 252.33 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2325.90 | 21.33 | 112.67 | 335.17 | 963.33 | 22.46 | 77.50 | 295.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.50 | 0.48 | 01-JAN-07:40 | 2116.42 | 22.70 | 147.50 | 322.17 | 1025.76 | 22.64 | 88.50 | 309.17 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:00 | 1665.43 | 15.14 | 0.00 | 293.67 | 869.18 | 18.72 | 0.00 | 271.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:40 | 1262.95 | 15.33 | 0.00 | 325.83 | 700.48 | 18.78 | 0.00 | 297.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:00 | 1038.60 | 15.06 | 0.00 | 320.00 | 589.72 | 18.52 | 0.00 | 282.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:00 | 890.12 | 13.69 | 0.00 | 326.83 | 494.69 | 17.09 | 0.00 | 277.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-07:40 | 868.70 | 14.01 | 0.00 | 319.67 | 499.68 | 17.49 | 0.00 | 272.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:10 | 843.10 | 13.08 | 0.00 | 324.00 | 456.76 | 16.48 | 0.00 | 269.17 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-06:00 | 995.24 | 14.26 | 0.00 | 325.67 | 543.39 | 17.65 | 0.00 | 280.17 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1123.94 | 13.99 | 0.00 | 310.17 | 588.12 | 17.32 | 0.00 | 273.00 |
October | 356.83 | 0.50 | 0.48 | 01-OCT-06:30 | 1452.54 | 15.41 | 15.00 | 322.50 | 732.09 | 18.34 | 4.50 | 281.17 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-06:00 | 1833.57 | 20.85 | 114.33 | 312.00 | 891.06 | 20.37 | 39.83 | 282.17 |
December | 349.33 | 0.50 | 0.48 | 01-DEC-06:40 | 2124.72 | 22.75 | 148.50 | 318.33 | 1025.10 | 22.53 | 87.50 | 302.50 |
Annual Sum or Average | 4292.33 | 0.51 | 1336.03 | 16.28 | 425.33 | 3820.83 | 694.46 | 18.78 | 220.33 | 3398.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 843.10 | 13.08 | 0.00 | 293.67 | 456.76 | 16.48 | 0.00 | 269.17 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2124.72 | 22.75 | 148.50 | 326.83 | 1025.76 | 22.64 | 88.50 | 309.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:10 | 1798.84 | 21.12 | 108.50 | 306.83 | 934.54 | 22.30 | 77.50 | 269.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-06:40 | 2005.73 | 21.25 | 99.00 | 285.33 | 1040.47 | 22.43 | 71.17 | 255.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-06:00 | 2273.01 | 21.29 | 112.17 | 320.50 | 924.24 | 21.07 | 52.17 | 291.00 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:10 | 1856.15 | 19.50 | 84.17 | 325.33 | 963.67 | 21.05 | 54.33 | 293.67 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1611.94 | 18.73 | 87.33 | 335.50 | 825.76 | 21.23 | 67.33 | 294.83 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1720.37 | 19.15 | 84.50 | 331.33 | 892.33 | 21.49 | 63.00 | 296.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:19 | 1433.00 | 18.42 | 86.67 | 332.50 | 718.03 | 19.97 | 56.33 | 287.83 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1631.92 | 19.08 | 86.00 | 334.17 | 830.93 | 20.60 | 55.00 | 294.83 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:10 | 1526.91 | 18.49 | 83.67 | 312.17 | 775.13 | 19.94 | 54.50 | 271.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-05:00 | 1541.13 | 19.02 | 86.17 | 313.50 | 772.34 | 20.44 | 55.17 | 272.00 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-06:40 | 1547.60 | 19.66 | 84.50 | 295.17 | 766.69 | 20.80 | 51.33 | 256.17 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-06:40 | 1752.05 | 21.20 | 112.50 | 299.67 | 790.60 | 21.17 | 56.00 | 265.17 |
Annual Sum or Average | 4292.33 | 0.51 | 1721.16 | 19.71 | 1115.17 | 3792.00 | 850.91 | 21.02 | 713.83 | 3348.83 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1433.00 | 18.42 | 83.67 | 285.33 | 718.03 | 19.94 | 51.33 | 255.83 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2273.01 | 21.29 | 112.50 | 335.50 | 1040.47 | 22.43 | 77.50 | 296.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.53 | 0.48 | 01-JAN-08:20 | 710.33 | 13.01 | 0.00 | 295.00 | 420.37 | 16.49 | 0.00 | 234.17 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-07:40 | 782.00 | 13.64 | 0.00 | 277.67 | 464.60 | 17.10 | 0.00 | 235.17 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:00 | 892.66 | 14.68 | 0.00 | 320.00 | 529.57 | 18.12 | 0.00 | 285.50 |
April | 358.33 | 0.49 | 0.48 | 01-APR-06:40 | 1090.28 | 15.52 | 0.00 | 330.67 | 616.97 | 19.02 | 0.00 | 298.50 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1265.91 | 14.90 | 3.83 | 347.00 | 659.86 | 18.28 | 1.17 | 313.50 |
June | 370.50 | 0.49 | 0.48 | 01-JUN-07:10 | 1515.58 | 20.46 | 112.17 | 347.50 | 765.75 | 20.34 | 33.17 | 319.33 |
July | 383.17 | 0.50 | 0.48 | 01-JUL-06:40 | 1313.26 | 19.88 | 115.50 | 350.00 | 652.35 | 20.54 | 59.17 | 315.17 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1175.52 | 14.93 | 0.00 | 340.33 | 627.21 | 18.39 | 0.00 | 304.33 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-06:49 | 955.79 | 13.78 | 0.00 | 312.50 | 515.46 | 17.11 | 0.00 | 270.33 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:10 | 845.52 | 13.50 | 0.00 | 309.33 | 463.27 | 16.88 | 0.00 | 255.67 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-07:30 | 756.86 | 13.17 | 0.00 | 286.00 | 426.08 | 16.59 | 0.00 | 228.67 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:19 | 691.73 | 12.69 | 0.00 | 288.83 | 404.10 | 16.15 | 0.00 | 227.00 |
Annual Sum or Average | 4292.33 | 0.51 | 1008.67 | 15.09 | 231.50 | 3804.83 | 549.21 | 17.96 | 93.50 | 3287.33 | ||
Minimum of Months | 321.17 | 0.49 | 0.48 | 691.73 | 12.69 | 0.00 | 277.67 | 404.10 | 16.15 | 0.00 | 227.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 1515.58 | 20.46 | 115.50 | 350.00 | 765.75 | 20.54 | 59.17 | 319.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-08:30 | 1859.47 | 21.33 | 109.33 | 305.83 | 963.27 | 22.46 | 77.50 | 271.33 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:00 | 2092.62 | 21.26 | 102.33 | 281.83 | 860.95 | 20.91 | 46.67 | 252.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:20 | 2325.84 | 21.06 | 112.67 | 328.67 | 941.52 | 20.77 | 51.17 | 293.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-07:19 | 2243.67 | 14.65 | 0.00 | 325.50 | 930.84 | 18.36 | 0.00 | 293.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-07:10 | 1788.74 | 14.38 | 0.00 | 335.17 | 784.13 | 17.83 | 0.00 | 293.50 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:00 | 1676.23 | 14.82 | 0.00 | 330.67 | 861.37 | 18.39 | 0.00 | 295.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-07:40 | 1434.30 | 14.17 | 0.00 | 333.33 | 717.84 | 17.53 | 0.00 | 288.50 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1637.45 | 14.99 | 8.50 | 331.17 | 814.38 | 18.03 | 0.00 | 291.50 |
September | 357.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1681.31 | 18.09 | 85.00 | 310.50 | 753.50 | 17.81 | 7.67 | 270.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-07:00 | 1593.88 | 18.92 | 87.50 | 312.67 | 816.19 | 21.71 | 72.67 | 274.00 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:00 | 1581.37 | 19.48 | 85.00 | 297.83 | 810.06 | 21.86 | 66.00 | 260.33 |
December | 349.33 | 0.52 | 0.48 | 01-DEC-07:40 | 1638.91 | 19.36 | 87.33 | 303.50 | 860.62 | 21.94 | 71.83 | 266.83 |
Annual Sum or Average | 4292.33 | 0.51 | 1792.39 | 17.61 | 677.67 | 3796.67 | 841.73 | 19.74 | 393.50 | 3351.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 1434.30 | 14.17 | 0.00 | 281.83 | 717.84 | 17.53 | 0.00 | 252.33 | |
Maximum of Months | 383.17 | 0.52 | 0.48 | 2325.84 | 21.33 | 112.67 | 335.17 | 963.27 | 22.46 | 77.50 | 295.50 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.994608E+11 | 0.674484E+11 | 105622.73 | 09-JAN-07:03 | 75660.18 | 0.00 |
February | 0.00 | 0.00 | 0.940382E+11 | 0.638633E+11 | 104332.26 | 16-FEB-07:03 | 69296.93 | 0.00 |
March | 0.00 | 0.00 | 0.114021E+12 | 0.754350E+11 | 118514.27 | 28-MAR-04:02 | 77228.28 | 0.00 |
April | 0.00 | 0.00 | 0.119333E+12 | 0.720337E+11 | 118704.72 | 12-APR-04:02 | 76630.07 | 0.00 |
May | 0.00 | 0.00 | 0.137213E+12 | 0.769039E+11 | 120618.82 | 06-MAY-04:03 | 72886.59 | 0.00 |
June | 0.00 | 0.00 | 0.137471E+12 | 0.777743E+11 | 121712.79 | 10-JUN-04:03 | 70422.46 | 0.00 |
July | 0.00 | 0.00 | 0.110619E+12 | 0.673999E+11 | 108706.79 | 28-JUL-06:03 | 73449.21 | 0.00 |
August | 0.00 | 0.00 | 0.128749E+12 | 0.710968E+11 | 120004.07 | 12-AUG-05:03 | 72324.49 | 0.00 |
September | 0.00 | 0.00 | 0.117557E+12 | 0.660791E+11 | 117812.18 | 25-SEP-06:03 | 77748.81 | 0.00 |
October | 0.00 | 0.00 | 0.114221E+12 | 0.645524E+11 | 115785.04 | 03-OCT-06:03 | 76808.87 | 0.00 |
November | 0.00 | 0.00 | 0.106356E+12 | 0.641928E+11 | 115649.43 | 14-NOV-07:03 | 77344.24 | 0.00 |
December | 0.00 | 0.00 | 0.973988E+11 | 0.634321E+11 | 108992.31 | 11-DEC-07:03 | 76752.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137644E+13 | 0.830212E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.940382E+11 | 0.634321E+11 | 104332.26 | 69296.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137471E+12 | 0.777743E+11 | 121712.79 | 77748.81 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847624E+11 | 0.557891E+11 | 100585.22 | 09-JAN-05:03 | 63771.78 | 0.00 |
February | 0.00 | 0.00 | 0.812261E+11 | 0.534429E+11 | 109046.48 | 06-FEB-06:02 | 69195.13 | 0.00 |
March | 0.00 | 0.00 | 0.986951E+11 | 0.632061E+11 | 110148.33 | 28-MAR-04:02 | 67775.11 | 0.00 |
April | 0.00 | 0.00 | 0.104705E+12 | 0.604858E+11 | 110362.28 | 12-APR-04:02 | 67203.49 | 0.00 |
May | 0.00 | 0.00 | 0.119274E+12 | 0.638780E+11 | 114300.86 | 22-MAY-04:02 | 62448.98 | 0.00 |
June | 0.00 | 0.00 | 0.119807E+12 | 0.645844E+11 | 113499.59 | 10-JUN-05:03 | 61143.09 | 0.00 |
July | 0.00 | 0.00 | 0.941970E+11 | 0.545493E+11 | 104831.34 | 10-JUL-04:02 | 69545.62 | 0.00 |
August | 0.00 | 0.00 | 0.109936E+12 | 0.571265E+11 | 114683.31 | 21-AUG-05:03 | 56437.46 | 0.00 |
September | 0.00 | 0.00 | 0.100969E+12 | 0.535618E+11 | 113944.01 | 04-SEP-14:32 | 60941.40 | 0.00 |
October | 0.00 | 0.00 | 0.976034E+11 | 0.525080E+11 | 111227.52 | 30-OCT-04:03 | 67177.23 | 0.00 |
November | 0.00 | 0.00 | 0.901309E+11 | 0.522555E+11 | 108594.44 | 13-NOV-05:02 | 69603.36 | 0.00 |
December | 0.00 | 0.00 | 0.830275E+11 | 0.519104E+11 | 103966.86 | 11-DEC-06:12 | 66701.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118433E+13 | 0.683298E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.812261E+11 | 0.519104E+11 | 100585.22 | 56437.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119807E+12 | 0.645844E+11 | 114683.31 | 69603.36 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.885651E+11 | 0.593379E+11 | 104670.97 | 02-JAN-07:03 | 74750.83 | 0.00 |
February | 0.00 | 0.00 | 0.855442E+11 | 0.574457E+11 | 118306.21 | 06-FEB-06:02 | 76171.04 | 0.00 |
March | 0.00 | 0.00 | 0.104931E+12 | 0.690609E+11 | 123178.46 | 13-MAR-04:02 | 79555.46 | 0.00 |
April | 0.00 | 0.00 | 0.111521E+12 | 0.666723E+11 | 127054.92 | 02-APR-15:32 | 78016.81 | 0.00 |
May | 0.00 | 0.00 | 0.125795E+12 | 0.696093E+11 | 128415.57 | 22-MAY-04:02 | 70808.31 | 0.00 |
June | 0.00 | 0.00 | 0.126273E+12 | 0.705940E+11 | 127893.00 | 10-JUN-05:03 | 67929.77 | 0.00 |
July | 0.00 | 0.00 | 0.992027E+11 | 0.589471E+11 | 114202.74 | 10-JUL-04:02 | 79013.25 | 0.00 |
August | 0.00 | 0.00 | 0.114738E+12 | 0.614221E+11 | 127516.77 | 13-AUG-12:13 | 69454.97 | 0.00 |
September | 0.00 | 0.00 | 0.105813E+12 | 0.579026E+11 | 125405.51 | 24-SEP-14:53 | 68096.03 | 0.00 |
October | 0.00 | 0.00 | 0.101479E+12 | 0.558442E+11 | 120560.78 | 09-OCT-12:02 | 69446.00 | 0.00 |
November | 0.00 | 0.00 | 0.938341E+11 | 0.555386E+11 | 112768.11 | 13-NOV-05:02 | 72833.02 | 0.00 |
December | 0.00 | 0.00 | 0.868489E+11 | 0.552060E+11 | 100979.92 | 26-DEC-07:03 | 74554.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124455E+13 | 0.737581E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.855442E+11 | 0.552060E+11 | 100979.92 | 67929.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.126273E+12 | 0.705940E+11 | 128415.57 | 79555.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1059.41 | 3859.55 | 11-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1059.43 | 3850.51 | 01-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1115.79 | 3809.07 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1015.33 | 3729.50 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 1031.80 | 3654.08 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1044.17 | 3583.29 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 946.74 | 3548.81 | 31-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1054.75 | 3593.48 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 997.32 | 3662.45 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1018.56 | 3748.82 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1056.83 | 3817.25 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1026.27 | 3854.66 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1035.42 | ||||
Minimum of Months | 0.00 | 0.00 | 946.74 | 3548.81 | ||
Maximum of Months | 0.00 | 0.00 | 1115.79 | 3859.55 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.408271E+10 | 0.48 | 9804.72 | 06-JAN-07:03 | 1.78 |
February | 0.387179E+10 | 0.49 | 9804.72 | 13-FEB-07:03 | 1.78 |
March | 0.449983E+10 | 0.52 | 9804.72 | 06-MAR-07:03 | 1.78 |
April | 0.421413E+10 | 0.51 | 9804.72 | 03-APR-04:02 | 1.78 |
May | 0.457748E+10 | 0.53 | 9804.72 | 02-MAY-04:02 | 1.78 |
June | 0.485129E+10 | 0.55 | 9804.72 | 06-JUN-04:02 | 1.78 |
July | 0.402803E+10 | 0.48 | 9804.72 | 03-JUL-06:03 | 1.78 |
August | 0.424323E+10 | 0.50 | 9804.72 | 02-AUG-04:02 | 1.78 |
September | 0.386909E+10 | 0.48 | 9804.72 | 05-SEP-04:02 | 1.78 |
October | 0.376762E+10 | 0.46 | 9804.72 | 02-OCT-06:03 | 1.78 |
November | 0.385907E+10 | 0.47 | 9804.72 | 06-NOV-07:03 | 1.78 |
December | 0.375216E+10 | 0.45 | 9804.72 | 04-DEC-07:03 | 1.78 |
Annual Sum or Average | 0.496164E+11 | 0.49 | |||
Minimum of Months | 0.375216E+10 | 0.45 | 9804.72 | 1.78 | |
Maximum of Months | 0.485129E+10 | 0.55 | 9804.72 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309923E+10 | 0.43 | 8795.60 | 02-JAN-07:03 | 1.78 |
February | 0.298025E+10 | 0.45 | 8795.60 | 06-FEB-06:02 | 1.78 |
March | 0.339963E+10 | 0.47 | 8795.60 | 06-MAR-07:03 | 1.78 |
April | 0.312148E+10 | 0.45 | 8795.60 | 03-APR-04:02 | 1.78 |
May | 0.335092E+10 | 0.46 | 8795.60 | 01-MAY-06:03 | 1.78 |
June | 0.354044E+10 | 0.49 | 8795.60 | 05-JUN-04:02 | 1.78 |
July | 0.285699E+10 | 0.42 | 8795.60 | 03-JUL-06:03 | 1.78 |
August | 0.297388E+10 | 0.43 | 8795.60 | 02-AUG-04:02 | 1.78 |
September | 0.274983E+10 | 0.42 | 8795.60 | 05-SEP-04:02 | 1.78 |
October | 0.275281E+10 | 0.41 | 8795.60 | 10-OCT-04:02 | 1.78 |
November | 0.286464E+10 | 0.42 | 8795.60 | 06-NOV-06:12 | 1.78 |
December | 0.280166E+10 | 0.40 | 8795.60 | 11-DEC-06:12 | 1.78 |
Annual Sum or Average | 0.364918E+11 | 0.44 | |||
Minimum of Months | 0.274983E+10 | 0.40 | 8795.60 | 1.78 | |
Maximum of Months | 0.354044E+10 | 0.49 | 8795.60 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.299114E+10 | 0.40 | 9588.51 | 02-JAN-07:03 | 1.70 |
February | 0.291940E+10 | 0.42 | 10301.31 | 06-FEB-06:02 | 1.78 |
March | 0.341547E+10 | 0.44 | 10301.31 | 13-MAR-04:02 | 1.78 |
April | 0.318436E+10 | 0.43 | 10301.31 | 03-APR-04:02 | 1.78 |
May | 0.336131E+10 | 0.44 | 10301.31 | 01-MAY-04:02 | 1.78 |
June | 0.354746E+10 | 0.46 | 10301.31 | 12-JUN-04:02 | 1.78 |
July | 0.282387E+10 | 0.40 | 10301.31 | 31-JUL-04:02 | 1.78 |
August | 0.292935E+10 | 0.41 | 10301.31 | 14-AUG-04:02 | 1.78 |
September | 0.274141E+10 | 0.40 | 10301.31 | 05-SEP-04:02 | 1.78 |
October | 0.267225E+10 | 0.39 | 10032.08 | 16-OCT-04:02 | 1.75 |
November | 0.276076E+10 | 0.39 | 8920.42 | 06-NOV-06:12 | 1.62 |
December | 0.270312E+10 | 0.38 | 9993.11 | 26-DEC-07:03 | 1.75 |
Annual Sum or Average | 0.360499E+11 | 0.41 | |||
Minimum of Months | 0.267225E+10 | 0.38 | 8920.42 | 1.62 | |
Maximum of Months | 0.354746E+10 | 0.46 | 10301.31 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 58.84 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 58.11 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:03 | 2.06 | 2.06 | 58.13 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:03 | 2.06 | 2.06 | 58.18 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 58.37 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 58.26 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 58.33 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.26 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 58.29 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.82 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 58.17 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 58.14 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 58.11 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.84 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 58.85 | 58.85 | 1059.41 | 3859.55 | 11-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.55 | 58.55 | 1059.43 | 3850.51 | 01-FEB-12:15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.56 | 58.56 | 1115.79 | 3809.07 | 01-MAR-12:17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.59 | 58.59 | 1015.33 | 3729.50 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.92 | 58.92 | 1031.80 | 3654.08 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.65 | 58.65 | 1044.17 | 3583.29 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.67 | 58.67 | 946.74 | 3548.81 | 31-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.66 | 58.66 | 1054.75 | 3593.48 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.65 | 58.65 | 997.32 | 3662.45 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.05 | 58.05 | 1018.56 | 3748.82 | 31-OCT-11:15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.59 | 58.59 | 1056.83 | 3817.25 | 30-NOV-12:15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.56 | 58.56 | 1026.27 | 3854.66 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 1035.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.05 | 58.05 | 946.74 | 3548.81 | ||
Maximum of Months | 0.00 | 0.00 | 58.92 | 58.92 | 1115.79 | 3859.55 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.272987E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.261596E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.318408E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.326715E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.369910E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.374689E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.294293E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.337557E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.308437E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.296164E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.281384E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261606E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.370375E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.261596E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.374689E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.228234E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.221550E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.269233E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.278434E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.313009E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.317033E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.243060E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.279521E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.257147E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.246784E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.233339E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.218304E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.310565E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.218304E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.317033E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.237241E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.232369E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.285661E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.296365E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.329695E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.333602E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.255280E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.290769E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268888E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.255512E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.241527E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.227070E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.325398E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.227070E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.333602E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.408271E+10 | 0.994608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387179E+10 | 0.940382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449983E+10 | 0.114021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.421413E+10 | 0.119333E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457748E+10 | 0.137213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.485129E+10 | 0.137471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.402803E+10 | 0.110619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.424323E+10 | 0.128749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.386909E+10 | 0.117557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376762E+10 | 0.114221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385907E+10 | 0.106356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375216E+10 | 0.973988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496164E+11 | 0.137644E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375216E+10 | 0.940382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485129E+10 | 0.137471E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.309923E+10 | 0.847624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298025E+10 | 0.812261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339963E+10 | 0.986951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312148E+10 | 0.104705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335092E+10 | 0.119274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354044E+10 | 0.119807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285699E+10 | 0.941970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.297388E+10 | 0.109936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274983E+10 | 0.100969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275281E+10 | 0.976034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286464E+10 | 0.901309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280166E+10 | 0.830275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364918E+11 | 0.118433E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274983E+10 | 0.812261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354044E+10 | 0.119807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.299114E+10 | 0.885651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291940E+10 | 0.855442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341547E+10 | 0.104931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318436E+10 | 0.111521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336131E+10 | 0.125795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354746E+10 | 0.126273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282387E+10 | 0.992027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292935E+10 | 0.114738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274141E+10 | 0.105813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267225E+10 | 0.101479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276076E+10 | 0.938341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270312E+10 | 0.868489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360499E+11 | 0.124455E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267225E+10 | 0.855442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354746E+10 | 0.126273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.408271E+10 | 0.00 | 0.00 | 0.00 | 0.232160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.387179E+10 | 0.00 | 0.00 | 0.00 | 0.222878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449983E+10 | 0.00 | 0.00 | 0.00 | 0.273410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.421413E+10 | 0.00 | 0.00 | 0.00 | 0.284574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.457748E+10 | 0.00 | 0.00 | 0.00 | 0.324135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.485129E+10 | 0.00 | 0.00 | 0.00 | 0.326176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.402803E+10 | 0.00 | 0.00 | 0.00 | 0.254012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.424323E+10 | 0.00 | 0.00 | 0.00 | 0.295125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.386909E+10 | 0.00 | 0.00 | 0.00 | 0.269746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.376762E+10 | 0.00 | 0.00 | 0.00 | 0.258488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.385907E+10 | 0.00 | 0.00 | 0.00 | 0.242793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375216E+10 | 0.00 | 0.00 | 0.00 | 0.224084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.496164E+11 | 0.00 | 0.00 | 0.00 | 0.320758E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375216E+10 | 0.00 | 0.00 | 0.00 | 0.222878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485129E+10 | 0.00 | 0.00 | 0.00 | 0.326176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.309923E+10 | 0.00 | 0.00 | 0.00 | 0.197242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298025E+10 | 0.00 | 0.00 | 0.00 | 0.191747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339963E+10 | 0.00 | 0.00 | 0.00 | 0.235237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.312148E+10 | 0.00 | 0.00 | 0.00 | 0.247219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.335092E+10 | 0.00 | 0.00 | 0.00 | 0.279500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354044E+10 | 0.00 | 0.00 | 0.00 | 0.281629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.285699E+10 | 0.00 | 0.00 | 0.00 | 0.214490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.297388E+10 | 0.00 | 0.00 | 0.00 | 0.249782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274983E+10 | 0.00 | 0.00 | 0.00 | 0.229649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275281E+10 | 0.00 | 0.00 | 0.00 | 0.219256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286464E+10 | 0.00 | 0.00 | 0.00 | 0.204693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280166E+10 | 0.00 | 0.00 | 0.00 | 0.190287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364918E+11 | 0.00 | 0.00 | 0.00 | 0.274073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.274983E+10 | 0.00 | 0.00 | 0.00 | 0.190287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354044E+10 | 0.00 | 0.00 | 0.00 | 0.281629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.299114E+10 | 0.00 | 0.00 | 0.00 | 0.207330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291940E+10 | 0.00 | 0.00 | 0.00 | 0.203175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341547E+10 | 0.00 | 0.00 | 0.00 | 0.251506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.318436E+10 | 0.00 | 0.00 | 0.00 | 0.264522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.336131E+10 | 0.00 | 0.00 | 0.00 | 0.296082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354746E+10 | 0.00 | 0.00 | 0.00 | 0.298127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.282387E+10 | 0.00 | 0.00 | 0.00 | 0.227041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292935E+10 | 0.00 | 0.00 | 0.00 | 0.261475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.274141E+10 | 0.00 | 0.00 | 0.00 | 0.241474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267225E+10 | 0.00 | 0.00 | 0.00 | 0.228790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276076E+10 | 0.00 | 0.00 | 0.00 | 0.213920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270312E+10 | 0.00 | 0.00 | 0.00 | 0.200039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360499E+11 | 0.00 | 0.00 | 0.00 | 0.289348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.267225E+10 | 0.00 | 0.00 | 0.00 | 0.200039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.354746E+10 | 0.00 | 0.00 | 0.00 | 0.298127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 403033.21 | 0.121288E+11 | 0.00 | 33861.91 | 0.229749E+10 | 0.00 | 113908.74 | 0.00 | 0.34 |
February | 0.00 | 0.116788E+11 | 0.00 | 0.00 | 0.241358E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.157208E+11 | 0.00 | 0.00 | 0.243109E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.185870E+11 | 0.00 | 0.00 | 0.418203E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.228370E+11 | 0.00 | 0.00 | 0.538157E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.228806E+11 | 0.00 | 0.00 | 0.421629E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.161712E+11 | 0.00 | 0.00 | 0.376615E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.228800E+11 | 0.00 | 0.00 | 0.317744E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.199587E+11 | 0.00 | 0.00 | 0.404044E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.00 | 0.192510E+11 | 0.00 | 0.00 | 0.370033E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.160587E+11 | 0.00 | 0.00 | 0.303833E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.126741E+11 | 0.00 | 0.00 | 0.282719E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 403033.21 | 0.210827E+12 | 0.00 | 33861.91 | 0.414719E+11 | 0.00 | 113908.74 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.116788E+11 | 0.00 | 0.00 | 0.229749E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 403033.21 | 0.228806E+11 | 0.00 | 33861.91 | 0.538157E+10 | 0.00 | 113908.74 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1039504.51 | 0.110356E+11 | 0.00 | 88653.17 | 0.212023E+10 | 0.00 | 1631874.45 | 0.00 | 0.31 |
February | 0.00 | 0.106804E+11 | 0.00 | 0.00 | 0.231307E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.142389E+11 | 0.00 | 0.00 | 0.258449E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.170766E+11 | 0.00 | 0.00 | 0.436364E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.211659E+11 | 0.00 | 0.00 | 0.534148E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.213251E+11 | 0.00 | 0.00 | 0.441859E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.148510E+11 | 0.00 | 0.00 | 0.378473E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.211268E+11 | 0.00 | 0.00 | 0.348353E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.184176E+11 | 0.00 | 0.00 | 0.412828E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.174306E+11 | 0.00 | 0.00 | 0.368033E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.146181E+11 | 0.00 | 0.00 | 0.293075E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.115838E+11 | 0.00 | 0.00 | 0.255247E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 1039504.51 | 0.193551E+12 | 0.00 | 88653.17 | 0.417016E+11 | 0.00 | 1631874.45 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.106804E+11 | 0.00 | 0.00 | 0.212023E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 1039504.51 | 0.213251E+11 | 0.00 | 88653.17 | 0.534148E+10 | 0.00 | 1631874.45 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 168686.85 | 0.107403E+11 | 0.00 | 25485.10 | 0.208291E+10 | 0.00 | 17883.00 | 0.00 | 0.30 |
February | 0.00 | 0.103792E+11 | 0.00 | 0.00 | 0.238429E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
March | 0.00 | 0.138708E+11 | 0.00 | 0.00 | 0.257675E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.167399E+11 | 0.00 | 0.00 | 0.438365E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.208797E+11 | 0.00 | 0.00 | 0.549066E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.210433E+11 | 0.00 | 0.00 | 0.433966E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.145740E+11 | 0.00 | 0.00 | 0.379086E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.208085E+11 | 0.00 | 0.00 | 0.351518E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.181431E+11 | 0.00 | 0.00 | 0.416232E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.172127E+11 | 0.00 | 0.00 | 0.362502E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.143616E+11 | 0.00 | 0.00 | 0.300327E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.112366E+11 | 0.00 | 0.00 | 0.269920E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 168686.85 | 0.189990E+12 | 0.00 | 25485.10 | 0.420538E+11 | 0.00 | 17883.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.103792E+11 | 0.00 | 0.00 | 0.208291E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 168686.85 | 0.210433E+11 | 0.00 | 25485.10 | 0.549066E+10 | 0.00 | 17883.00 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39172.28 | 0.323874E+10 | 0.00 | 0.00 | 0.412635E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
February | 0.00 | 0.333876E+10 | 0.00 | 0.00 | 0.415176E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
March | 0.00 | 0.458583E+10 | 0.00 | 0.00 | 0.421123E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
April | 0.00 | 0.607450E+10 | 0.00 | 0.00 | 0.627773E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.832762E+10 | 0.00 | 0.00 | 0.666178E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.908887E+10 | 0.00 | 0.00 | 0.411146E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.565523E+10 | 0.00 | 0.00 | 0.528874E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.723762E+10 | 0.00 | 0.00 | 0.548363E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.607329E+10 | 0.00 | 0.00 | 0.696630E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.542080E+10 | 0.00 | 0.00 | 0.606817E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 0.00 | 0.439509E+10 | 0.00 | 0.00 | 0.538487E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.338562E+10 | 0.00 | 0.00 | 0.525687E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 39172.28 | 0.668220E+11 | 0.00 | 0.00 | 0.639889E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.323874E+10 | 0.00 | 0.00 | 0.411146E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 39172.28 | 0.908887E+10 | 0.00 | 0.00 | 0.696630E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24744.95 | 0.272984E+10 | 0.00 | 0.00 | 0.165867E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.00 | 0.287757E+10 | 0.00 | 0.00 | 0.141856E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.397376E+10 | 0.00 | 0.00 | 0.193873E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.516918E+10 | 0.00 | 0.00 | 0.306043E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.598970E+10 | 0.00 | 0.00 | 0.379214E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.615428E+10 | 0.00 | 0.00 | 0.270703E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.390387E+10 | 0.00 | 0.00 | 0.305579E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.557639E+10 | 0.00 | 0.00 | 0.268341E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.495888E+10 | 0.00 | 0.00 | 0.299851E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.436626E+10 | 0.00 | 0.00 | 0.293423E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.354493E+10 | 0.00 | 0.00 | 0.205290E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.285304E+10 | 0.00 | 0.00 | 0.204780E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 24744.95 | 0.520977E+11 | 0.00 | 0.00 | 0.303482E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.272984E+10 | 0.00 | 0.00 | 0.141856E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 24744.95 | 0.615428E+10 | 0.00 | 0.00 | 0.379214E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39097.45 | 0.490811E+10 | 0.00 | 0.00 | 0.232362E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
February | 0.00 | 0.467305E+10 | 0.00 | 0.00 | 0.258471E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.531301E+10 | 0.00 | 0.00 | 0.357813E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.594810E+10 | 0.00 | 0.00 | 0.638449E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.732641E+10 | 0.00 | 0.00 | 0.822866E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.733102E+10 | 0.00 | 0.00 | 0.597903E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.487773E+10 | 0.00 | 0.00 | 0.612096E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.674922E+10 | 0.00 | 0.00 | 0.605259E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.638036E+10 | 0.00 | 0.00 | 0.670098E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.653456E+10 | 0.00 | 0.00 | 0.486538E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.601572E+10 | 0.00 | 0.00 | 0.325089E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
December | 0.00 | 0.528482E+10 | 0.00 | 0.00 | 0.287716E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 39097.45 | 0.713421E+11 | 0.00 | 0.00 | 0.589466E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.467305E+10 | 0.00 | 0.00 | 0.232362E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 39097.45 | 0.733102E+10 | 0.00 | 0.00 | 0.822866E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24824.95 | 0.272686E+10 | 0.00 | 0.00 | 0.190354E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
February | 0.00 | 0.288283E+10 | 0.00 | 0.00 | 0.192032E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.402475E+10 | 0.00 | 0.00 | 0.185641E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
April | 0.00 | 0.513460E+10 | 0.00 | 0.00 | 0.272881E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
May | 0.00 | 0.587358E+10 | 0.00 | 0.00 | 0.374117E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.599559E+10 | 0.00 | 0.00 | 0.270117E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.384184E+10 | 0.00 | 0.00 | 0.298742E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.542702E+10 | 0.00 | 0.00 | 0.278056E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.480677E+10 | 0.00 | 0.00 | 0.323950E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.428365E+10 | 0.00 | 0.00 | 0.312161E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.352013E+10 | 0.00 | 0.00 | 0.256179E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.282062E+10 | 0.00 | 0.00 | 0.257466E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 24824.95 | 0.513382E+11 | 0.00 | 0.00 | 0.321169E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.272686E+10 | 0.00 | 0.00 | 0.185641E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 24824.95 | 0.599559E+10 | 0.00 | 0.00 | 0.374117E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 105461.73 | 0.261544E+10 | 0.00 | 0.00 | 0.558712E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
February | 0.00 | 0.268480E+10 | 0.00 | 0.00 | 0.543627E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.372058E+10 | 0.00 | 0.00 | 0.566009E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
April | 0.00 | 0.490124E+10 | 0.00 | 0.00 | 0.794660E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
May | 0.00 | 0.695933E+10 | 0.00 | 0.00 | 0.817955E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.773593E+10 | 0.00 | 0.00 | 0.498273E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.483668E+10 | 0.00 | 0.00 | 0.582718E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.605897E+10 | 0.00 | 0.00 | 0.614369E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.503030E+10 | 0.00 | 0.00 | 0.825528E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.432261E+10 | 0.00 | 0.00 | 0.859650E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 0.00 | 0.356040E+10 | 0.00 | 0.00 | 0.707938E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.269694E+10 | 0.00 | 0.00 | 0.664485E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 105461.73 | 0.551232E+11 | 0.00 | 0.00 | 0.803392E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.261544E+10 | 0.00 | 0.00 | 0.498273E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 105461.73 | 0.773593E+10 | 0.00 | 0.00 | 0.859650E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66959.94 | 0.224073E+10 | 0.00 | 0.00 | 0.270507E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
February | 0.00 | 0.243933E+10 | 0.00 | 0.00 | 0.200775E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.339836E+10 | 0.00 | 0.00 | 0.205330E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.435300E+10 | 0.00 | 0.00 | 0.329854E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
May | 0.00 | 0.509215E+10 | 0.00 | 0.00 | 0.445129E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.520841E+10 | 0.00 | 0.00 | 0.337171E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.332400E+10 | 0.00 | 0.00 | 0.346725E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.471229E+10 | 0.00 | 0.00 | 0.299655E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.422335E+10 | 0.00 | 0.00 | 0.342955E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.362540E+10 | 0.00 | 0.00 | 0.347037E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.297094E+10 | 0.00 | 0.00 | 0.290153E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.235529E+10 | 0.00 | 0.00 | 0.274473E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 66959.94 | 0.439433E+11 | 0.00 | 0.00 | 0.368976E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.224073E+10 | 0.00 | 0.00 | 0.200775E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 66959.94 | 0.520841E+10 | 0.00 | 0.00 | 0.445129E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 105511.26 | 0.448716E+10 | 0.00 | 0.00 | 0.288875E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
February | 0.00 | 0.432917E+10 | 0.00 | 0.00 | 0.288493E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
March | 0.00 | 0.527697E+10 | 0.00 | 0.00 | 0.389980E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.588039E+10 | 0.00 | 0.00 | 0.799763E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.731431E+10 | 0.00 | 0.00 | 0.101116E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.738442E+10 | 0.00 | 0.00 | 0.762559E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.470506E+10 | 0.00 | 0.00 | 0.773086E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.675770E+10 | 0.00 | 0.00 | 0.693642E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.623274E+10 | 0.00 | 0.00 | 0.745413E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.618211E+10 | 0.00 | 0.00 | 0.571911E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.569885E+10 | 0.00 | 0.00 | 0.391377E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
December | 0.00 | 0.479767E+10 | 0.00 | 0.00 | 0.311411E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 105511.26 | 0.690466E+11 | 0.00 | 0.00 | 0.702767E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.432917E+10 | 0.00 | 0.00 | 0.288493E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 105511.26 | 0.738442E+10 | 0.00 | 0.00 | 0.101116E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 66876.24 | 0.229888E+10 | 0.00 | 0.00 | 0.247361E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
February | 0.00 | 0.246108E+10 | 0.00 | 0.00 | 0.223361E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.347892E+10 | 0.00 | 0.00 | 0.188262E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.435381E+10 | 0.00 | 0.00 | 0.304253E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.502763E+10 | 0.00 | 0.00 | 0.421558E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.517401E+10 | 0.00 | 0.00 | 0.305621E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.331990E+10 | 0.00 | 0.00 | 0.326734E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.465075E+10 | 0.00 | 0.00 | 0.272079E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.412873E+10 | 0.00 | 0.00 | 0.346346E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.358019E+10 | 0.00 | 0.00 | 0.368199E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.297284E+10 | 0.00 | 0.00 | 0.310055E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.236466E+10 | 0.00 | 0.00 | 0.292262E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 66876.24 | 0.438114E+11 | 0.00 | 0.00 | 0.360609E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.229888E+10 | 0.00 | 0.00 | 0.188262E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 66876.24 | 0.517401E+10 | 0.00 | 0.00 | 0.421558E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 515312.01 | 0.331443E+10 | 0.00 | 0.00 | 0.445831E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
February | 0.00 | 0.341102E+10 | 0.00 | 0.00 | 0.441557E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
March | 0.00 | 0.471937E+10 | 0.00 | 0.00 | 0.456069E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
April | 0.00 | 0.617980E+10 | 0.00 | 0.00 | 0.685648E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
May | 0.00 | 0.848361E+10 | 0.00 | 0.00 | 0.695236E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 0.00 | 0.931486E+10 | 0.00 | 0.00 | 0.445207E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.575301E+10 | 0.00 | 0.00 | 0.552690E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.736689E+10 | 0.00 | 0.00 | 0.570252E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.615849E+10 | 0.00 | 0.00 | 0.745191E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.541573E+10 | 0.00 | 0.00 | 0.696083E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 0.00 | 0.445703E+10 | 0.00 | 0.00 | 0.556963E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.343014E+10 | 0.00 | 0.00 | 0.544405E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 515312.01 | 0.680044E+11 | 0.00 | 0.00 | 0.683513E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.331443E+10 | 0.00 | 0.00 | 0.441557E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 515312.01 | 0.931486E+10 | 0.00 | 0.00 | 0.745191E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 150691.74 | 0.263793E+10 | 0.00 | 3922.70 | 0.194404E+09 | 0.00 | 172740.63 | 0.00 | 0.49 |
February | 0.00 | 0.281348E+10 | 0.00 | 0.00 | 0.162033E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
March | 0.00 | 0.393288E+10 | 0.00 | 0.00 | 0.195076E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.509074E+10 | 0.00 | 0.00 | 0.304781E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.588228E+10 | 0.00 | 0.00 | 0.378947E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.601360E+10 | 0.00 | 0.00 | 0.302062E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.377419E+10 | 0.00 | 0.00 | 0.322649E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.540529E+10 | 0.00 | 0.00 | 0.281183E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.481980E+10 | 0.00 | 0.00 | 0.323940E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.418381E+10 | 0.00 | 0.00 | 0.306884E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.343136E+10 | 0.00 | 0.00 | 0.221725E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 0.00 | 0.274933E+10 | 0.00 | 0.00 | 0.209644E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 150691.74 | 0.507347E+11 | 0.00 | 3922.70 | 0.320333E+10 | 0.00 | 172740.63 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.263793E+10 | 0.00 | 0.00 | 0.162033E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 150691.74 | 0.601360E+10 | 0.00 | 3922.70 | 0.378947E+09 | 0.00 | 172740.63 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 219515.15 | 0.500602E+10 | 0.00 | 5940.42 | 0.233940E+09 | 0.00 | 295431.68 | 0.00 | 0.57 |
February | 0.00 | 0.481114E+10 | 0.00 | 0.00 | 0.267431E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
March | 0.00 | 0.551994E+10 | 0.00 | 0.00 | 0.372169E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.605823E+10 | 0.00 | 0.00 | 0.700812E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.744362E+10 | 0.00 | 0.00 | 0.855122E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.744075E+10 | 0.00 | 0.00 | 0.683000E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.489767E+10 | 0.00 | 0.00 | 0.706401E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.685669E+10 | 0.00 | 0.00 | 0.645041E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.651146E+10 | 0.00 | 0.00 | 0.696083E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.660509E+10 | 0.00 | 0.00 | 0.521869E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.614164E+10 | 0.00 | 0.00 | 0.327430E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 0.00 | 0.537929E+10 | 0.00 | 0.00 | 0.264067E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 219515.15 | 0.726715E+11 | 0.00 | 5940.42 | 0.627336E+10 | 0.00 | 295431.68 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.481114E+10 | 0.00 | 0.00 | 0.233940E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 219515.15 | 0.744362E+10 | 0.00 | 5940.42 | 0.855122E+09 | 0.00 | 295431.68 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 231571.68 | 0.281568E+10 | 0.00 | 1232.19 | 0.202310E+09 | 0.00 | 94399.54 | 0.00 | 0.51 |
February | 0.00 | 0.299432E+10 | 0.00 | 0.00 | 0.210059E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
March | 0.00 | 0.422492E+10 | 0.00 | 0.00 | 0.189456E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
April | 0.00 | 0.532813E+10 | 0.00 | 0.00 | 0.282788E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 0.00 | 0.603363E+10 | 0.00 | 0.00 | 0.388078E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.619938E+10 | 0.00 | 0.00 | 0.286737E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.392120E+10 | 0.00 | 0.00 | 0.327856E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.558003E+10 | 0.00 | 0.00 | 0.284151E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.493479E+10 | 0.00 | 0.00 | 0.348306E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.434229E+10 | 0.00 | 0.00 | 0.336348E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.359778E+10 | 0.00 | 0.00 | 0.269552E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
December | 0.00 | 0.289750E+10 | 0.00 | 0.00 | 0.248541E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 231571.68 | 0.528696E+11 | 0.00 | 1232.19 | 0.337418E+10 | 0.00 | 94399.54 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.281568E+10 | 0.00 | 0.00 | 0.189456E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 231571.68 | 0.619938E+10 | 0.00 | 1232.19 | 0.388078E+09 | 0.00 | 94399.54 | 0.00 | 0.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234731E+12 | -0.713264E+10 | 0.00 | -0.121764E+12 | 0.336461E+12 |
February | 0.228680E+12 | -0.711993E+10 | 0.00 | -0.122203E+12 | 0.322588E+12 |
March | 0.292684E+12 | -0.112544E+11 | 0.00 | -0.152952E+12 | 0.393663E+12 |
April | 0.288467E+12 | -0.122870E+11 | 0.00 | -0.196330E+12 | 0.415190E+12 |
May | 0.289913E+12 | -0.154338E+11 | 0.00 | -0.239560E+12 | 0.472254E+12 |
June | 0.300496E+12 | -0.152218E+11 | 0.00 | -0.232882E+12 | 0.474145E+12 |
July | 0.250415E+12 | -0.933399E+10 | 0.00 | -0.172778E+12 | 0.373573E+12 |
August | 0.311122E+12 | -0.141950E+11 | 0.00 | -0.216994E+12 | 0.434062E+12 |
September | 0.246204E+12 | -0.110075E+11 | 0.00 | -0.204228E+12 | 0.398426E+12 |
October | 0.271994E+12 | -0.106122E+11 | 0.00 | -0.194268E+12 | 0.383956E+12 |
November | 0.225484E+12 | -0.898695E+10 | 0.00 | -0.163355E+12 | 0.356462E+12 |
December | 0.221778E+12 | -0.671507E+10 | 0.00 | -0.134846E+12 | 0.328716E+12 |
Annual Sum or Average | 0.316197E+13 | -0.129300E+12 | 0.00 | -0.215216E+13 | 0.468950E+13 |
Minimum of Months | 0.221778E+12 | -0.154338E+11 | 0.00 | -0.239560E+12 | 0.322588E+12 |
Maximum of Months | 0.311122E+12 | -0.671507E+10 | 0.00 | -0.121764E+12 | 0.474145E+12 |