Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:20:02
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1905.75 | 382.51 | 382.51 |
Net Site Energy | 1905.75 | 382.51 | 382.51 |
Total Source Energy | 4765.59 | 956.53 | 956.53 |
Net Source Energy | 4765.59 | 956.53 | 956.53 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 609.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 97.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 59.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1296.09 | 609.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 609.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 104.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 97.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 59.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 609.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 104.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 232.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 51.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 97.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 59.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.17 | 122.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 260.14 | 122.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 57.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 53.17 | 122.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 260.14 | 122.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1296.088 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1296.088 | 100.00 |
Total On-Site and Utility Electric Sources | 1296.088 | 100.00 |
Total Electricity End Uses | 1296.088 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 488.17 |
Time Setpoint Not Met During Occupied Cooling | 113.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2675.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-15:39 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 0.00 | 312287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73453.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33211.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4505.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 173928.84 | 312287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 312287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 73453.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 33211.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4505.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 660.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 331.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 737.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 164.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 309.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 10.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 186.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4104.71 | 660.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 823.88 | 132.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 148.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 823.88 | 132.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.90 | 0.258213 | 0.219000 | 0.635640 | 0.688569 | 0.500000 | 0.001476 | 0.000130 | 0.635640 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 2.33 | 0.321321 | 0.273000 | 0.636750 | 0.856856 | 0.500000 | 0.001186 | 0.000227 | 0.882851 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 2.46 | 0.304905 | 0.259000 | 0.636620 | 0.813081 | 0.500000 | 0.001250 | 0.000407 | 1.58 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.763506 | 0.206929 | 0.176000 | 0.134377 | 0.551811 | 0.500000 | 0.001841 | 0.000184 | 0.718376 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.919485 | 0.108780 | 0.092000 | 0.084593 | 0.300000 | 0.500000 | 0.003502 | 0.000120 | 0.469636 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.22 | 0.129900 | 0.110000 | 0.133788 | 0.346401 | 0.500000 | 0.002933 | 0.000186 | 0.724039 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.04 | 0.096563 | 0.082000 | 0.084932 | 0.300000 | 0.500000 | 0.003946 | 0.000121 | 0.473785 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.590436 | 0.267585 | 0.227000 | 0.134029 | 0.713559 | 0.500000 | 0.001424 | 0.000143 | 0.558738 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.751491 | 0.133098 | 0.113000 | 0.084918 | 0.354928 | 0.500000 | 0.002863 | 0.000094 | 0.368356 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.966003 | 0.163552 | 0.139000 | 0.134274 | 0.436139 | 0.500000 | 0.002330 | 0.000145 | 0.564215 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.815451 | 0.122650 | 0.104000 | 0.084807 | 0.327067 | 0.500000 | 0.003106 | 0.000095 | 0.371960 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.662316 | 0.238544 | 0.203000 | 0.134450 | 0.636118 | 0.500000 | 0.001597 | 0.000143 | 0.556302 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.910035 | 0.300000 | 0.500000 | 0.003466 | 0.000094 | 0.366114 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.11 | 0.142153 | 0.121000 | 0.134481 | 0.379076 | 0.500000 | 0.002680 | 0.000144 | 0.561125 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.958103 | 0.104389 | 0.089000 | 0.085271 | 0.300000 | 0.500000 | 0.003650 | 0.000095 | 0.369790 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 14879.39 | 0.000130 | 359.69 |
CORE_MID VAV BOX REHEAT COIL | 25966.67 | 0.000227 | 685.78 |
CORE_TOP VAV BOX REHEAT COIL | 46487.42 | 0.000407 | 1226.51 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21049.72 | 0.000184 | 554.97 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13760.64 | 0.000120 | 362.79 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21215.46 | 0.000186 | 559.34 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13882.05 | 0.000121 | 365.99 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16377.44 | 0.000143 | 431.85 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10796.36 | 0.000094 | 284.68 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16537.72 | 0.000145 | 436.07 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10901.84 | 0.000095 | 287.46 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16306.40 | 0.000143 | 429.98 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10730.91 | 0.000094 | 282.95 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16447.56 | 0.000144 | 433.70 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10838.49 | 0.000095 | 285.79 |
PACU_VAV_BOT HEATING COIL | 37169.29 | 0.000325 | 591.79 |
PACU_VAV_MID HEATING COIL | 38089.70 | 0.000333 | 600.55 |
PACU_VAV_TOP HEATING COIL | 36656.15 | 0.000321 | 589.88 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.01 | 1.07 | 6.03 | 2.30 | 5.28 | 5.28 | 0.300000 | 0.436292 | 5.28 |
PACU_VAV_MID | 2.99 | 1.08 | 5.97 | 2.74 | 4.97 | 4.97 | 0.300000 | 0.550895 | 4.97 |
PACU_VAV_TOP | 3.20 | 1.07 | 6.39 | 3.97 | 5.74 | 5.74 | 0.300000 | 0.691091 | 5.74 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.28 |
PACU_VAV_MID_OA_CONTROLLER | 4.97 |
PACU_VAV_TOP_OA_CONTROLLER | 5.74 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.28 | 87391.18 | 0.800655 | 1.76 | 29127.48 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.97 | 82218.16 | 0.800655 | 1.66 | 27403.31 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.74 | 95088.46 | 0.800655 | 1.91 | 31692.98 | 0.800655 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.28 |
PACU_VAV_MID FAN | 4.97 |
PACU_VAV_TOP FAN | 5.74 |
Maximum Actuated Flow [m3/s] | |
PACU_VAV_BOT_HEATC_CONTROLLER | 0.000325 |
PACU_VAV_MID_HEATC_CONTROLLER | 0.000333 |
PACU_VAV_TOP_HEATC_CONTROLLER | 0.000321 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003308 | 0.396927 |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
HEATSYS1 PUMP | 0.003308 | 986.28 | 0.000000 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 378093.22 | 378093.22 | 0.003308 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7597 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7464 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.9868 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.082 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.106 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7793 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.31468885E-12 | 0.58742715E-14 | -0.96802560E-13 | 0.16792992E-15 |
43 | 6 | 0.28872123E-07 | 0.21416477E-09 | 0.66123209E-08 | -0.13627602E-12 |
44 | 5 | -0.19112651E-03 | 0.18301600E-05 | -0.98293898E-04 | 0.65360363E-08 |
45 | 4 | 0.29333920 | 0.88954174E-03 | 0.10011225 | -0.33739231E-04 |
46 | 3 | -7.2899446 | 0.27524297E-01 | -2.3459205 | 0.29124746E-01 |
47 | 2 | 40.949034 | 0.97737712E-01 | 15.293846 | -0.33420785 |
48 | 1 | -80.605481 | 0.44056480E-01 | -29.167461 | 1.0798913 |
49 | 0 | 46.824338 | 0.88531397E-03 | 16.290617 | |
50 | 7 | -0.30618227E-12 | 0.12614254E-14 | -0.97456297E-13 | 0.16278992E-15 |
51 | 6 | 0.29029541E-07 | 0.21075172E-09 | 0.66470638E-08 | -0.13712239E-12 |
52 | 5 | -0.19192439E-03 | 0.17992386E-05 | -0.98693455E-04 | 0.65698920E-08 |
53 | 4 | 0.29427084 | 0.87374093E-03 | 0.10044741 | -0.33870887E-04 |
54 | 3 | -7.3083902 | 0.27014250E-01 | -2.3513943 | 0.29215155E-01 |
55 | 2 | 41.009863 | 0.95860246E-01 | 15.316286 | -0.33488536 |
56 | 1 | -80.652088 | 0.43184114E-01 | -29.187576 | 1.0808846 |
57 | 0 | 46.824338 | 0.86726935E-03 | 16.290137 | |
58 | 7 | -0.27636417E-12 | 0.12990813E-14 | -0.82271001E-13 | 0.80162457E-16 |
59 | 6 | 0.26158967E-07 | 0.26982527E-09 | 0.60134738E-08 | -0.12176112E-12 |
60 | 5 | -0.17726759E-03 | 0.23481051E-05 | -0.91336903E-04 | 0.59516496E-08 |
61 | 4 | 0.27699908 | 0.11597994E-02 | 0.94241662E-01 | -0.31446529E-04 |
62 | 3 | -6.9660490 | 0.36401088E-01 | -2.2498311 | 0.27538282E-01 |
63 | 2 | 39.880486 | 0.13088809 | 14.898993 | -0.32230875 |
64 | 1 | -79.786295 | 0.59645051E-01 | -28.813249 | 1.0624348 |
65 | 0 | 46.824344 | 0.12114519E-02 | 16.299244 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 35 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 36 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
3 | WINDOW_U_0.342_SHGC_WEST_0.379 | 37 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 | ||
4 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 38 | 1 | VerySmooth | 1.943 | 1.943 | 1.000 | 0.380 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.82380E-002 | 0.29270 | 0.50360 | 0.50360 | 0.41690 | 0.13592 | 0.17539 | 0.00000 | 0.84000 | 0.84000 | 0.11194 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.679 | 3.273E-003 | 4.819E-003 | 4.296 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2826E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4398E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4454E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1269E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1721E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3624E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3867E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1720 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9229E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1976 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1150 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1139 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9799E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8200E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8082E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2829E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2912E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4401E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4478E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1298E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1855E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3621E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3864E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.4873E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9222E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.3153E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7343E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8300E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9514E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6593E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6671E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.4257E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.4535E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2433E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.2635E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4630E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4702E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0914E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0997E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8454E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9058E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0466E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0962E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4906E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5282E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3621E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3864E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7185E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7016E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6490E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0678E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3365E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4030E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8200E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8082E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8449E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.9067E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0453E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0939E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4881E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.5186E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.3624E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3867E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.6238E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9876E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9297E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5321E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4708E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3008E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6593E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6671E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2370E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.3171E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7148E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8045E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6324E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6628E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0916E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0999E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1765 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1213 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2003 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1401 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1232 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.3186E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.4952E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.5650E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2011E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.7573E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0460E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.5784E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.6403E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8382E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5541E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6039E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.3552E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.5005E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2139E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7538E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.9008E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0271E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.4952E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5650E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.4002E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8640E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7412E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4299E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3224E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2150E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5542E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6040E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1765 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1213 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2003 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1401 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1232 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.3178E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.4947E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.5647E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2011E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.7570E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0459E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.5781E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.6399E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8377E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5536E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6036E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.3554E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.5004E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2140E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7536E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.9005E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0269E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.4947E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5647E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.4002E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8638E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7412E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4297E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3220E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2147E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5536E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6037E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 35228.74076 | 35228.74076 | 2.90246 | 2.90246 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 9281.96269 | 9281.96269 | 0.45504 | 0.45504 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 28334.38119 | 28334.38119 | 2.33242 | 2.33242 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18192.31345 | 18192.31345 | 0.88285 | 0.88285 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29587.27276 | 29587.27276 | 2.45799 | 2.45799 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 32538.79454 | 32538.79454 | 1.58400 | 1.58400 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9190.77712 | 9190.77712 | 0.76351 | 0.76351 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 32.92000 | 6.30608E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 14725.62663 | 14725.62663 | 0.71838 | 0.71838 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11068.48904 | 11068.48904 | 0.91948 | 0.91948 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 9626.30713 | 9626.30713 | 0.46964 | 0.46964 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14640.82461 | 14640.82461 | 1.21625 | 1.21625 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 14841.50024 | 14841.50024 | 0.72404 | 0.72404 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12468.10481 | 12468.10481 | 1.03575 | 1.03575 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 9711.19076 | 9711.19076 | 0.47378 | 0.47378 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7107.34512 | 7107.34512 | 0.59044 | 0.59044 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11458.19584 | 11458.19584 | 0.55874 | 0.55874 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9046.12688 | 9046.12688 | 0.75149 | 0.75149 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.86667 | 6.29676E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7553.28782 | 7553.28782 | 0.36836 | 0.36836 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11628.27601 | 11628.27601 | 0.96600 | 0.96600 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11570.24525 | 11570.24525 | 0.56421 | 0.56421 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9816.05934 | 9816.05934 | 0.81545 | 0.81545 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 28.36000 | 6.29904E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7627.02944 | 7627.02944 | 0.37196 | 0.37196 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7972.65741 | 7972.65741 | 0.66232 | 0.66232 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11409.13456 | 11409.13456 | 0.55630 | 0.55630 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10954.70443 | 10954.70443 | 0.91004 | 0.91004 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.05333 | 6.29402E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7507.93192 | 7507.93192 | 0.36611 | 0.36611 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13378.80434 | 13378.80434 | 1.11142 | 1.11142 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11507.81583 | 11507.81583 | 0.56113 | 0.56113 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11533.31681 | 11533.31681 | 0.95810 | 0.95810 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7583.14267 | 7583.14267 | 0.36979 | 0.36979 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 72008.87 | 5.27930 | 5.27930 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40594.06 | 2.30332 | 2.30332 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 68207.62 | 4.96680 | 4.96680 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40720.42 | 2.73618 | 2.73618 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 77199.53 | 5.74429 | 5.74429 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40869.83 | 3.96983 | 3.96983 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.90246 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25821 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63564 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68857 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47552E-003 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30171E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63564 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14879.38609 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30171E-004 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 359.68708 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33242 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32132 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63675 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85686 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18573E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27168E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.88285 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25966.67192 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27168E-004 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 685.78399 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45799 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30491 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63662 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81308 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24957E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.06692E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58400 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 46487.41638 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.06692E-004 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1226.51195 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76351 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20693 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13438 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55181 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84121E-003 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.84152E-004 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71838 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21049.72056 |
55 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84152E-004 |
56 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 554.96898 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91948 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10878 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.20000E-002 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.45926E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50247E-003 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20384E-004 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46964 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13760.63599 |
69 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20384E-004 |
70 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.78787 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21625 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12990 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13379 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34640 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93302E-003 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85602E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72404 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21215.46208 |
83 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85602E-004 |
84 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 559.33621 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03575 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.65628E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.20000E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49318E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.94562E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21446E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47378 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13882.05022 |
97 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21446E-004 |
98 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.98709 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59044 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26758 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13403 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71356 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42385E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43277E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55874 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16377.44383 |
111 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43277E-004 |
112 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 431.85099 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75149 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13310 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49185E-002 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35493 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86256E-003 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.44513E-005 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36836 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
124 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10796.36098 |
125 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.44513E-005 |
126 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.67708 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96600 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16355 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13900 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13427 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43614 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32953E-003 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44679E-004 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56421 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
138 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16537.72202 |
139 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44679E-004 |
140 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 436.07420 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81545 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12265 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10400 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48069E-002 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32707 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10640E-003 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.53741E-005 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37196 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
152 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10901.84298 |
153 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.53741E-005 |
154 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.45643 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66232 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23854 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20300 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63612 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59719E-003 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42656E-004 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55630 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
166 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16306.40326 |
167 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42656E-004 |
168 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 429.98204 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91004 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46648E-003 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.38787E-005 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36611 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
177 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10730.91337 |
178 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.38787E-005 |
179 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.95429 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11142 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14215 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13448 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37908 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68020E-003 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43890E-004 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56113 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
191 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16447.55763 |
192 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43890E-004 |
193 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 433.70135 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95810 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10439 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.90000E-002 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52711E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64982E-003 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.48199E-005 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36979 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
205 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10838.49495 |
206 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.48199E-005 |
207 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.78898 |
208 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.01292 |
209 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07367 |
210 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.02584 |
211 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.30332 |
212 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.27930 |
213 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.27930 |
214 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
215 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.43629 |
216 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.98714 |
217 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07559 |
218 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.97429 |
219 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.73618 |
220 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.96680 |
221 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.96680 |
222 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.55089 |
224 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.19649 |
225 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07431 |
226 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.39299 |
227 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.96983 |
228 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.74429 |
229 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.74429 |
230 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.69109 |
232 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.27930 |
233 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.96680 |
234 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.74429 |
235 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.27930 |
236 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.27930 |
237 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 87391.18086 |
238 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
239 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.75959 |
240 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29127.48058 |
241 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Rated Capacity [W] | 37169.28504 |
243 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.25173E-004 |
244 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 591.78743 |
245 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.27930 |
246 | Controller:WaterCoil | PACU_VAV_BOT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.25173E-004 |
247 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.96680 |
248 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.96680 |
249 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 82218.15837 |
250 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
251 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.65543 |
252 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27403.31219 |
253 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
254 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Rated Capacity [W] | 38089.69798 |
255 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33225E-004 |
256 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 600.55477 |
257 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.96680 |
258 | Controller:WaterCoil | PACU_VAV_MID_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.33225E-004 |
259 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.74429 |
260 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.74429 |
261 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95088.45729 |
262 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.91457 |
264 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31692.98281 |
265 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
266 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Rated Capacity [W] | 36656.15454 |
267 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20684E-004 |
268 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 589.88313 |
269 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.74429 |
270 | Controller:WaterCoil | PACU_VAV_TOP_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.20684E-004 |
271 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.30772E-003 |
272 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.39693 |
273 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.30772E-003 |
274 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 986.27855 |
275 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
276 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 378093.21981 |
277 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 378093.22000 |
278 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.30772E-003 |
279 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
280 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
281 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
282 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
283 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14099.33 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 24614.74 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 44058.83 |
4 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19947.34 |
5 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13039.94 |
6 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20104.38 |
7 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13154.98 |
8 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15520.19 |
9 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10231.18 |
10 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15672.06 |
11 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10331.13 |
12 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 15452.89 |
13 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10169.18 |
14 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 15586.64 |
15 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10271.12 |
16 | Coil:Heating:Water | PACU_VAV_BOT HEATING COIL | 26707.33 |
17 | Coil:Heating:Water | PACU_VAV_MID HEATING COIL | 26791.78 |
18 | Coil:Heating:Water | PACU_VAV_TOP HEATING COIL | 26948.01 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 85887.40 | 293059.96 | 11.87 | 3.01 | 3.40 | 3.58 | 3.76 | 10.26 | 11.60 | 12.22 | 12.82 | 5.3403 | 4.2225 | 2.8302 | 1.1917 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 80803.39 | 275712.61 | 11.87 | 3.01 | 3.40 | 3.58 | 3.76 | 10.26 | 11.60 | 12.22 | 12.82 | 5.0242 | 3.9726 | 2.6627 | 1.1211 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 93452.22 | 318872.22 | 11.87 | 3.01 | 3.40 | 3.58 | 3.76 | 10.26 | 11.60 | 12.22 | 12.82 | 5.8106 | 4.5945 | 3.0795 | 1.2966 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.987 | 0.860 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.760 | 0.682 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_NORTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_EAST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_SOUTH_0.379 | N/A | 1.943 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.746 | 0.671 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.342_SHGC_WEST_0.379 | N/A | 1.943 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.0748652437E-003 | 5.7281571907E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1098989458 | 6.8415631531E-002 | Pass | Pass | 0.2071533922 | 0.3956443683 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.5504650183E-002 | 1.0895995309E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3273095127E-002 | 9.0485203128E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.1647561629E-002 | 7.6868412247E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.9630689018E-002 | 2.1244892311E-002 | Pass | Pass | 0.2595687631 | 0.5596745400 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1264387484 | 0.1717545124 | Pass | Pass | 27.2695028824 | 137.8441121774 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1126759678 | 0.1396530093 | Pass | Pass | 168.2555074869 | 1664.1272882720 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1459838893 | 0.1335696071 | Pass | Pass | 104.5672730530 | 1070.0234435455 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1426419922 | 0.1507680659 | Pass | Pass | 208.7667135126 | 2072.3889428711 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.9361964341E-002 | 1.6155067553E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.0696541272E-002 | 6.4013244973E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.4609116942E-002 | 9.5418063086E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.2440139359E-002 | 4.3138399156E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.2285268313E-002 | 1.7410448190E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1442292942E-002 | 7.5393459669E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1265801275 | 0.1268757311 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.5076553190E-002 | 5.7407440133E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3583.26 | 112.04 | 0.00 | 2169.57 | 728.86 | 6593.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.860 | 0.987 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.682 | 0.760 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.671 | 0.746 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.342_SHGC_NORTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.342_SHGC_EAST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.342_SHGC_EAST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.342_SHGC_WEST_0.379 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.342_SHGC_WEST_0.379 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 1.943 | 0.380 | 0.418 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.342_SHGC_NORTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.342_SHGC_EAST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.342_SHGC_SOUTH_0.379 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.342_SHGC_WEST_0.379 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 1.943 | 0.380 | 0.418 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
North Total or Average | 195.79 | 1.943 | 0.380 | 0.418 | |||||||||||||||||
Non-North Total or Average | 456.84 | 1.943 | 0.380 | 0.418 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.24 | 0.0000 | Y | 6.81 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.19 | 0.0000 | Y | 6.79 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.92 | 0.0000 | Y | 4.26 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.73 | 0.0000 | Y | 6.67 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.97 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.24 | 0.0000 | Y | 6.81 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.96 | 0.0000 | Y | 4.26 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.77 | 0.0000 | Y | 6.68 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 26.02 | 0.0000 | Y | 4.27 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 232.83 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 42.11 | 42.11 | 4.46 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.57 | 62.84 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.57 | 48.07 | 42.54 | |
Exterior Lighting Total | 5686.19 | 51.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 378093.22 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 87391.18 | 69970.21 | 17420.97 | 0.80 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 82218.16 | 65828.40 | 16389.76 | 0.80 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95088.46 | 76133.07 | 18955.38 | 0.80 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 85887.4 | 3.01 | 10.26 | N/A | N/A | 11.87 | |
PACU_VAV_MID COOLING COIL | 80803.4 | 3.01 | 10.26 | N/A | N/A | 11.87 | |
PACU_VAV_TOP COOLING COIL | 93452.2 | 3.01 | 10.26 | N/A | N/A | 11.87 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 14879.39 | 14099.33 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 25966.67 | 24614.74 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 46487.42 | 44058.83 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21049.72 | 19947.34 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13760.64 | 13039.94 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21215.46 | 20104.38 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13882.05 | 13154.98 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16377.44 | 15520.19 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10796.36 | 10231.18 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16537.72 | 15672.06 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10901.84 | 10331.13 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16306.40 | 15452.89 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10730.91 | 10169.18 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16447.56 | 15586.64 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10838.49 | 10271.12 | - |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | 37169.29 | 26707.33 | - |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | 38089.70 | 26791.78 | - |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | 36656.15 | 26948.01 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.28 | 12134.27 | 2298.46 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.97 | 11416.00 | 2298.46 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.74 | 12493.20 | 2174.89 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003308 | 986.28 | 298174.34 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 85887.40 | 3.01 | 10.26 | 11.87 | 5.3403 | 3.40 | 11.60 | 4.2225 | 3.58 | 12.22 | 2.8302 | 3.76 | 12.82 | 1.1917 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 80803.39 | 3.01 | 10.26 | 11.87 | 5.0242 | 3.40 | 11.60 | 3.9726 | 3.58 | 12.22 | 2.6627 | 3.76 | 12.82 | 1.1211 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93452.22 | 3.01 | 10.26 | 11.87 | 5.8106 | 3.40 | 11.60 | 4.5945 | 3.58 | 12.22 | 3.0795 | 3.76 | 12.82 | 1.2966 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 35228.74 | 35228.74 | 35.82 | 2.902 | 2.902 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00885 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_MID | 28334.38 | 28334.38 | 28.81 | 2.332 | 2.332 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.56 | 0.00629 | 0.425 | 0.00 |
CORE_TOP | 29587.27 | 29587.27 | 30.08 | 2.458 | 2.458 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00891 | 32.76 | 0.00631 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9190.78 | 9190.78 | 44.33 | 0.764 | 0.764 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00872 | 32.92 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 11068.49 | 11068.49 | 84.32 | 0.919 | 0.919 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00862 | 25.96 | 0.00630 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14640.82 | 14640.82 | 70.61 | 1.216 | 1.216 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00864 | 33.27 | 0.00631 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12468.10 | 12468.10 | 94.99 | 1.036 | 1.036 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00860 | 30.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7107.35 | 7107.35 | 34.28 | 0.590 | 0.590 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00882 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 9046.13 | 9046.13 | 68.92 | 0.751 | 0.751 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00866 | 26.87 | 0.00630 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11628.28 | 11628.28 | 56.08 | 0.966 | 0.966 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00870 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9816.06 | 9816.06 | 74.79 | 0.815 | 0.815 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.00 | 24.00 | 0.00865 | 28.36 | 0.00630 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7972.66 | 7972.66 | 38.45 | 0.662 | 0.662 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00877 | 33.40 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10954.70 | 10954.70 | 83.46 | 0.910 | 0.910 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00862 | 25.05 | 0.00629 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13378.80 | 13378.80 | 64.53 | 1.111 | 1.111 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00866 | 33.13 | 0.00631 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 11533.32 | 11533.32 | 87.87 | 0.958 | 0.958 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00862 | 30.36 | 0.00630 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 9281.96 | 9281.96 | 9.44 | 0.455 | 0.455 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_MID | 18192.31 | 18192.31 | 18.50 | 0.883 | 0.883 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
CORE_TOP | 32538.79 | 32538.79 | 33.08 | 1.584 | 1.584 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 14725.63 | 14725.63 | 71.02 | 0.718 | 0.718 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9626.31 | 9626.31 | 73.34 | 0.470 | 0.470 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14841.50 | 14841.50 | 71.58 | 0.724 | 0.724 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9711.19 | 9711.19 | 73.99 | 0.474 | 0.474 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11458.20 | 11458.20 | 55.26 | 0.559 | 0.559 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7553.29 | 7553.29 | 57.54 | 0.368 | 0.368 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11570.25 | 11570.25 | 55.80 | 0.564 | 0.564 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7627.03 | 7627.03 | 58.11 | 0.372 | 0.372 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11409.13 | 11409.13 | 55.03 | 0.556 | 0.556 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7507.93 | 7507.93 | 57.20 | 0.366 | 0.366 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11507.82 | 11507.82 | 55.50 | 0.561 | 0.561 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7583.14 | 7583.14 | 57.77 | 0.370 | 0.370 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -27.60 | 0.00034 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.28 | 5.28 | 2.30 | 2.30 | 5.2793 | 2.3033 | 5.2793 | 0.4363 | 0.3000 |
PACU_VAV_MID | 4.97 | 4.97 | 2.74 | 2.74 | 4.9668 | 2.7362 | 4.9668 | 0.5509 | 0.3000 |
PACU_VAV_TOP | 5.74 | 5.74 | 3.97 | 3.97 | 5.7443 | 3.9698 | 5.7443 | 0.6911 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 14879.386 | 14879.386 | 0.635640 | 0.00013017 | 359.687 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 14879.39 | 14879.39 | 0.635640 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 9281.96 | 0.00 | 14927.50 | 14927.50 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 25966.672 | 25966.672 | 0.882851 | 0.00022717 | 685.784 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25966.67 | 25966.67 | 0.882851 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 18192.31 | 0.00 | 26058.86 | 26058.86 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 46487.416 | 46487.416 | 1.583996 | 0.00040669 | 1226.512 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 46487.42 | 46487.42 | 1.583996 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 32538.79 | 0.00 | 46643.65 | 46643.65 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21049.721 | 21049.721 | 0.718376 | 0.00018415 | 554.969 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21049.72 | 21049.72 | 0.718376 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788213 | 44.5748 | 14725.63 | 0.00 | 21117.57 | 21117.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13760.636 | 13760.636 | 0.469636 | 0.00012038 | 362.788 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13760.64 | 13760.64 | 0.469636 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787982 | 44.5620 | 9626.31 | 0.00 | 13804.94 | 13804.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21215.462 | 21215.462 | 0.724039 | 0.00018560 | 559.336 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21215.46 | 21215.46 | 0.724039 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788304 | 44.5799 | 14841.50 | 0.00 | 21283.83 | 21283.83 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13882.050 | 13882.050 | 0.473785 | 0.00012145 | 365.987 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13882.05 | 13882.05 | 0.473785 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788086 | 44.5678 | 9711.19 | 0.00 | 13926.74 | 13926.74 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16377.444 | 16377.444 | 0.558738 | 0.00014328 | 431.851 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16377.44 | 16377.44 | 0.558738 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791804 | 44.7745 | 11458.20 | 0.00 | 16430.70 | 16430.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10796.361 | 10796.361 | 0.368356 | 0.00009445 | 284.677 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10796.36 | 10796.36 | 0.368356 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791751 | 44.7716 | 7553.29 | 0.00 | 10831.41 | 10831.41 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16537.722 | 16537.722 | 0.564215 | 0.00014468 | 436.074 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16537.72 | 16537.72 | 0.564215 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791893 | 44.7795 | 11570.25 | 0.00 | 16591.48 | 16591.48 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10901.843 | 10901.843 | 0.371960 | 0.00009537 | 287.456 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10901.84 | 10901.84 | 0.371960 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00791838 | 44.7764 | 7627.03 | 0.00 | 10937.22 | 10937.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16306.403 | 16306.403 | 0.556302 | 0.00014266 | 429.982 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16306.40 | 16306.40 | 0.556302 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787245 | 44.5205 | 11409.13 | 0.00 | 16359.46 | 16359.46 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10730.913 | 10730.913 | 0.366114 | 0.00009388 | 282.954 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10730.91 | 10730.91 | 0.366114 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787116 | 44.5134 | 7507.93 | 0.00 | 10765.77 | 10765.77 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16447.558 | 16447.558 | 0.561125 | 0.00014389 | 433.701 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16447.56 | 16447.56 | 0.561125 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787361 | 44.5270 | 11507.82 | 0.00 | 16501.06 | 16501.06 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10838.495 | 10838.495 | 0.369790 | 0.00009482 | 285.789 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10838.49 | 10838.49 | 0.369790 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787250 | 44.5208 | 7583.14 | 0.00 | 10873.69 | 10873.69 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 87391.181 | 69970.209 | 5.279301 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 85421.85 | 85421.85 | 5.279301 | 25.70 | 15.47 | 0.00835269 | 10.66 | 9.88 | 0.00835269 | 33.40 | 0.00630683 | 16.37 | 18.1104 | 24.00 | 0.00880576 | 41.4399 | 63478.32 | 0.00 | 90112.04 | 66394.71 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_BOT | 37169.285 | 37169.285 | 1.583790 | 0.00032517 | 591.787 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37169.29 | 37169.29 | 1.583790 | -9.38 | -9.38 | 0.00329931 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 60.3678 | 18.33 | 0.00781082 | 52.1413 | 14497.52 | 0.00 | 32300.93 | 32300.93 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 82218.158 | 65828.401 | 4.966799 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80365.40 | 80365.40 | 4.966799 | 25.81 | 15.50 | 0.00833312 | 10.66 | 9.86 | 0.00833312 | 33.40 | 0.00630683 | 16.37 | 19.2498 | 24.00 | 0.00881787 | 41.4959 | 59617.43 | 0.00 | 84777.96 | 62464.55 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_MID | 38089.698 | 38089.698 | 1.490040 | 0.00033323 | 600.555 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38089.70 | 38089.70 | 1.490040 | -11.36 | -11.36 | 0.00299262 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 64.1661 | 17.60 | 0.00754771 | 52.7776 | 14480.36 | 0.00 | 32397.22 | 32397.22 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 95088.457 | 76133.073 | 5.744294 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 93059.42 | 93059.42 | 5.744294 | 25.54 | 15.43 | 0.00835996 | 10.78 | 9.94 | 0.00835996 | 33.24 | 0.00630658 | 16.31 | 16.6443 | 24.00 | 0.00877163 | 41.2812 | 68915.04 | 0.00 | 98048.96 | 72242.65 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoopHVAC | PACU_VAV_TOP | 36656.155 | 36656.155 | 1.723288 | 0.00032068 | 589.883 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36656.15 | 36656.15 | 1.723288 | -7.30 | -7.30 | 0.00363401 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 55.4811 | 16.07 | 0.00781011 | 60.1537 | 13920.97 | 0.00 | 32597.84 | 32597.84 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 14879.386 | 14879.386 | 0.635640 | 0.00013017 | 359.687 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 3.8577 | 3.935375 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 14879.39 | 14879.39 | 1.0000 | 0.66941732 | 0.635640 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.13015808 | 60.00 | 32.22 | 27.78 | 0.000 | 14879.39 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 9281.96 | 0.00 | 14927.50 | 14927.50 | 0.66941732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.67 | 19.55 | 0.00800000 | 55359.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 25966.672 | 25966.672 | 0.882851 | 0.00022717 | 685.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 6.7323 | 6.867796 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25966.67 | 25966.67 | 1.0000 | 0.92976533 | 0.882851 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.22714460 | 60.00 | 32.22 | 27.78 | 0.000 | 25966.67 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 18192.31 | 0.00 | 26058.86 | 26058.86 | 0.92976533 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61087.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 46487.416 | 46487.416 | 1.583996 | 0.00040669 | 1226.512 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 12.0527 | 12.295226 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 46487.42 | 46487.42 | 1.0000 | 1.66816916 | 1.583996 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.40665071 | 60.00 | 32.22 | 27.78 | 0.000 | 46487.42 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 32538.79 | 0.00 | 46643.65 | 46643.65 | 1.66816916 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21049.721 | 21049.721 | 0.718376 | 0.00018415 | 554.969 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 5.4575 | 5.567336 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21049.72 | 21049.72 | 1.0000 | 0.75654990 | 0.718376 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18413335 | 60.00 | 32.22 | 27.78 | 0.000 | 21049.72 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788213 | 21.00 | 0.00788213 | 44.5748 | 14725.63 | 0.00 | 21117.57 | 21117.57 | 0.75654990 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13760.636 | 13760.636 | 0.469636 | 0.00012038 | 362.788 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 3.5677 | 3.639482 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13760.64 | 13760.64 | 1.0000 | 0.49459252 | 0.469636 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12037177 | 60.00 | 32.22 | 27.78 | 0.000 | 13760.64 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787982 | 21.00 | 0.00787982 | 44.5620 | 9626.31 | 0.00 | 13804.94 | 13804.94 | 0.49459252 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21215.462 | 21215.462 | 0.724039 | 0.00018560 | 559.336 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 5.5005 | 5.611172 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21215.46 | 21215.46 | 1.0000 | 0.76251428 | 0.724039 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18558318 | 60.00 | 32.22 | 27.78 | 0.000 | 21215.46 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788304 | 21.00 | 0.00788304 | 44.5799 | 14841.50 | 0.00 | 21283.83 | 21283.83 | 0.76251428 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13882.050 | 13882.050 | 0.473785 | 0.00012145 | 365.987 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 3.5992 | 3.671595 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13882.05 | 13882.05 | 1.0000 | 0.49896173 | 0.473785 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12143384 | 60.00 | 32.22 | 27.78 | 0.000 | 13882.05 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788086 | 21.00 | 0.00788086 | 44.5678 | 9711.19 | 0.00 | 13926.74 | 13926.74 | 0.49896173 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16377.444 | 16377.444 | 0.558738 | 0.00014328 | 431.851 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 4.2461 | 4.331589 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16377.44 | 16377.44 | 1.0000 | 0.58842913 | 0.558738 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.14326241 | 60.00 | 32.22 | 27.78 | 0.000 | 16377.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791804 | 21.00 | 0.00791804 | 44.7745 | 11458.20 | 0.00 | 16430.70 | 16430.70 | 0.58842913 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10796.361 | 10796.361 | 0.368356 | 0.00009445 | 284.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 2.7991 | 2.855476 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10796.36 | 10796.36 | 1.0000 | 0.38792987 | 0.368356 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09444164 | 60.00 | 32.22 | 27.78 | 0.000 | 10796.36 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791751 | 21.00 | 0.00791751 | 44.7716 | 7553.29 | 0.00 | 10831.41 | 10831.41 | 0.38792987 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16537.722 | 16537.722 | 0.564215 | 0.00014468 | 436.074 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 4.2877 | 4.373980 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16537.72 | 16537.72 | 1.0000 | 0.59419708 | 0.564215 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.14466445 | 60.00 | 32.22 | 27.78 | 0.000 | 16537.72 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791893 | 21.00 | 0.00791893 | 44.7795 | 11570.25 | 0.00 | 16591.48 | 16591.48 | 0.59419708 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10901.843 | 10901.843 | 0.371960 | 0.00009537 | 287.456 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 2.8265 | 2.883374 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10901.84 | 10901.84 | 1.0000 | 0.39172592 | 0.371960 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09536435 | 60.00 | 32.22 | 27.78 | 0.000 | 10901.84 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00791838 | 21.00 | 0.00791838 | 44.7764 | 7627.03 | 0.00 | 10937.22 | 10937.22 | 0.39172592 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16306.403 | 16306.403 | 0.556302 | 0.00014266 | 429.982 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 4.2277 | 4.312800 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16306.40 | 16306.40 | 1.0000 | 0.58586389 | 0.556302 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.14264098 | 60.00 | 32.22 | 27.78 | 0.000 | 16306.40 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787245 | 21.00 | 0.00787245 | 44.5205 | 11409.13 | 0.00 | 16359.46 | 16359.46 | 0.58586389 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10730.913 | 10730.913 | 0.366114 | 0.00009388 | 282.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 2.7822 | 2.838166 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10730.91 | 10730.91 | 1.0000 | 0.38556952 | 0.366114 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09386913 | 60.00 | 32.22 | 27.78 | 0.000 | 10730.91 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787116 | 21.00 | 0.00787116 | 44.5134 | 7507.93 | 0.00 | 10765.77 | 10765.77 | 0.38556952 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16447.558 | 16447.558 | 0.561125 | 0.00014389 | 433.701 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 4.2643 | 4.350133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16447.56 | 16447.56 | 1.0000 | 0.59094364 | 0.561125 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.14387573 | 60.00 | 32.22 | 27.78 | 0.000 | 16447.56 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787361 | 21.00 | 0.00787361 | 44.5270 | 11507.82 | 0.00 | 16501.06 | 16501.06 | 0.59094364 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60983.1 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10838.495 | 10838.495 | 0.369790 | 0.00009482 | 285.789 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 2.8101 | 2.866620 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10838.49 | 10838.49 | 1.0000 | 0.38944108 | 0.369790 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09481021 | 60.00 | 32.22 | 27.78 | 0.000 | 10838.49 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787250 | 21.00 | 0.00787250 | 44.5208 | 7583.14 | 0.00 | 10873.69 | 10873.69 | 0.38944108 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.1 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 87391.181 | 69970.209 | 5.279301 | -999.0 | -999.000 | -999.0000 | 1.02932 | 1.00000 | 1020.3672 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.279301 | 5.55984267 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 85421.85 | 85421.85 | 0.9775 | 5.55984267 | 5.279301 | 25.70 | 15.47 | 0.00835269 | 47116.4 | 10.66 | 9.88 | 0.00835269 | 31767.8 | -999.0 | -999.00 | -999.00 | -999.00 | 12134.271 | 73287.58 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 18.1104 | 24.00 | 0.00880576 | 24.00 | 0.00880576 | 41.4399 | 63478.32 | 0.00 | 90112.04 | 66394.71 | 5.34027091 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 37169.285 | 37169.285 | 1.583790 | 0.00032517 | 591.787 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.279301 | 5.55984267 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 9.6368 | 9.830720 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37169.29 | 37169.29 | 1.0000 | 1.66795280 | 1.583790 | -9.38 | -9.38 | 0.00329931 | -1228.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.32513995 | 60.00 | 32.22 | 27.78 | 0.000 | 37169.29 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 60.3678 | 18.38 | 0.00780404 | 18.33 | 0.00781082 | 52.1413 | 14497.52 | 0.00 | 32300.93 | 32300.93 | 1.66795280 | 2.80 | 0.96 | 0.00329931 | 11082.1 | 21.96 | 10.59 | 0.00329931 | 30447.7 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 82218.158 | 65828.401 | 4.966799 | -999.0 | -999.000 | -999.0000 | 1.02218 | 1.00000 | 1020.3309 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.966799 | 5.23073405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 80365.40 | 80365.40 | 0.9775 | 5.23073405 | 4.966799 | 25.81 | 15.50 | 0.00833312 | 47179.2 | 10.66 | 9.86 | 0.00833312 | 31718.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11415.996 | 68949.40 | 33.40 | 0.00630683 | 16.37 | 0.95610000 | 19.2498 | 24.00 | 0.00881787 | 24.00 | 0.00881787 | 41.4959 | 59617.43 | 0.00 | 84777.96 | 62464.55 | 5.02415959 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 38089.698 | 38089.698 | 1.490040 | 0.00033323 | 600.555 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.966799 | 5.23073405 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 9.8754 | 10.074155 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38089.70 | 38089.70 | 1.0000 | 1.56922021 | 1.490040 | -11.36 | -11.36 | 0.00299262 | -3989.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.33319130 | 60.00 | 32.22 | 27.78 | 0.000 | 38089.70 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 64.1661 | 17.73 | 0.00773913 | 17.60 | 0.00754771 | 52.7776 | 14480.36 | 0.00 | 32397.22 | 32397.22 | 1.56922021 | 2.80 | 0.51 | 0.00299262 | 10313.5 | 23.23 | 10.82 | 0.00299262 | 30958.9 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95088.457 | 76133.073 | 5.744294 | -999.0 | -999.000 | -999.0000 | 1.04954 | 1.00000 | 1020.3807 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.744294 | 6.04954478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 93059.42 | 93059.42 | 0.9787 | 6.04954478 | 5.744294 | 25.54 | 15.43 | 0.00835996 | 46970.5 | 10.78 | 9.94 | 0.00835996 | 31903.5 | -999.0 | -999.00 | -999.00 | -999.00 | 12493.197 | 80566.23 | 33.24 | 0.00630658 | 16.31 | 0.95610000 | 16.6443 | 24.00 | 0.00877163 | 24.00 | 0.00877163 | 41.2812 | 68915.04 | 0.00 | 98048.96 | 72242.65 | 5.81063350 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 13.70 | 0.00944336 | 38448.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 36656.155 | 36656.155 | 1.723288 | 0.00032068 | 589.883 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.744294 | 6.04954478 | 4197.9300 | 999.8980 | 3.30738700 | 54.44 | 82.22 | 27.78 | 385702.50 | 9.5037 | 9.695004 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36656.15 | 36656.15 | 1.0000 | 1.81486344 | 1.723288 | -7.30 | -7.30 | 0.00363401 | 1703.7 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.32065132 | 60.00 | 32.22 | 27.78 | 0.000 | 36656.15 | -27.60 | 0.00034190 | -27.60 | 0.95610000 | 55.4811 | 18.00 | 0.00773676 | 16.07 | 0.00781011 | 60.1537 | 13920.97 | 0.00 | 32597.84 | 32597.84 | 1.81486344 | 2.80 | 1.43 | 0.00363401 | 11920.9 | 20.56 | 10.34 | 0.00363401 | 29882.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.28 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.97 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1359.67 | 2923.67 | 144.33 |
CORE_MID | 1518.50 | 3927.00 | 737.17 |
CORE_TOP | 2199.17 | 4216.67 | 1511.83 |
PERIMETER_TOP_ZN_3 | 3149.83 | 4421.83 | 2399.50 |
PERIMETER_TOP_ZN_2 | 3276.33 | 3988.83 | 2111.67 |
PERIMETER_TOP_ZN_1 | 2968.83 | 3771.67 | 1736.00 |
PERIMETER_TOP_ZN_4 | 3257.67 | 4103.00 | 2180.33 |
PERIMETER_BOT_ZN_3 | 2728.50 | 4547.67 | 2163.33 |
PERIMETER_BOT_ZN_2 | 2899.33 | 3875.17 | 1699.17 |
PERIMETER_BOT_ZN_1 | 2698.67 | 3851.50 | 1513.83 |
PERIMETER_BOT_ZN_4 | 2857.83 | 3988.17 | 1760.17 |
PERIMETER_MID_ZN_3 | 2699.50 | 4215.33 | 1873.00 |
PERIMETER_MID_ZN_2 | 2461.17 | 3290.83 | 1460.00 |
PERIMETER_MID_ZN_1 | 2654.83 | 3460.33 | 1256.67 |
PERIMETER_MID_ZN_4 | 2876.33 | 3858.83 | 1689.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4649.00 | 4795.67 | 2675.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 3.50 | 0.00 | 3.33 | 0.00 |
CORE_TOP | 16.17 | 0.00 | 14.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 185.33 | 8.00 | 111.67 | 5.50 |
PERIMETER_TOP_ZN_2 | 109.83 | 32.83 | 43.50 | 29.17 |
PERIMETER_TOP_ZN_1 | 93.50 | 34.17 | 39.67 | 29.50 |
PERIMETER_TOP_ZN_4 | 113.17 | 35.83 | 48.17 | 18.83 |
PERIMETER_BOT_ZN_3 | 94.67 | 0.00 | 77.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 51.67 | 24.33 | 36.00 | 23.00 |
PERIMETER_BOT_ZN_1 | 444.00 | 30.33 | 433.50 | 27.67 |
PERIMETER_BOT_ZN_4 | 52.83 | 25.17 | 37.83 | 13.17 |
PERIMETER_MID_ZN_3 | 81.50 | 3.83 | 57.00 | 2.67 |
PERIMETER_MID_ZN_2 | 41.50 | 32.33 | 19.17 | 30.17 |
PERIMETER_MID_ZN_1 | 34.00 | 35.83 | 18.17 | 33.00 |
PERIMETER_MID_ZN_4 | 43.50 | 34.17 | 22.17 | 18.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 590.33 | 145.83 | 488.17 | 113.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.925 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.665 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.634 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.729 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.187 | 0.054 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.210 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 1.068 | 0.054 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.591 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.002 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.953 | 0.849 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.866 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.720 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.082 | 0.048 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.229 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 1.049 | 0.045 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.77 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.91 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.55 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.59 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.91 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.93 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14721421.29 | 0.00 | 14721421.29 | 0.00 | 14721421.29 | 13393058.27 | 5010.22 | 363.40 | 3386.37 | 151.59 |
CORE_MID | 10629436.06 | 0.00 | 10629436.06 | 0.00 | 10629436.06 | 13393058.27 | 5270.24 | 779.35 | 2710.41 | 166.91 |
CORE_TOP | 10166473.30 | 0.00 | 10166473.30 | 0.00 | 10166473.30 | 13393058.27 | 5458.72 | 727.86 | 2573.43 | 98.12 |
PERIMETER_TOP_ZN_3 | 2459984.20 | 0.00 | 2459984.20 | 341693.17 | 2801677.38 | 2823374.22 | 4670.81 | 600.01 | 3489.18 | 98.12 |
PERIMETER_TOP_ZN_2 | 2519206.81 | 0.00 | 2519206.81 | 227794.08 | 2747000.89 | 1787429.43 | 4594.19 | 1055.18 | 3110.63 | 98.12 |
PERIMETER_TOP_ZN_1 | 4055723.79 | 0.00 | 4055723.79 | 341693.17 | 4397416.96 | 2823374.22 | 4524.60 | 980.62 | 3254.79 | 98.12 |
PERIMETER_TOP_ZN_4 | 2294951.64 | 0.00 | 2294951.64 | 227794.08 | 2522745.72 | 1787312.18 | 4572.98 | 695.44 | 3491.58 | 98.12 |
PERIMETER_BOT_ZN_3 | 2001827.05 | 0.00 | 2001827.05 | 181675.92 | 2183502.97 | 2823374.22 | 6194.73 | 372.15 | 2193.12 | 151.59 |
PERIMETER_BOT_ZN_2 | 2129713.94 | 0.00 | 2129713.94 | 121116.55 | 2250830.49 | 1787429.43 | 5606.95 | 364.97 | 2788.07 | 151.59 |
PERIMETER_BOT_ZN_1 | 3211937.69 | 0.00 | 3211937.69 | 2939420.97 | 6151358.67 | 2823374.22 | 5241.51 | 311.11 | 3207.38 | 151.59 |
PERIMETER_BOT_ZN_4 | 1855295.73 | 0.00 | 1855295.73 | 121116.55 | 1976412.28 | 1787312.18 | 5712.91 | 401.36 | 2645.73 | 151.59 |
PERIMETER_MID_ZN_3 | 2425575.06 | 0.00 | 2425575.06 | 284432.92 | 2710007.98 | 2823374.22 | 4863.44 | 665.27 | 3231.30 | 166.91 |
PERIMETER_MID_ZN_2 | 2365431.94 | 0.00 | 2365431.94 | 189620.80 | 2555052.74 | 1601953.02 | 4489.85 | 947.71 | 3322.44 | 1075.89 |
PERIMETER_MID_ZN_1 | 4114590.38 | 0.00 | 4114590.38 | 284432.92 | 4399023.30 | 2823374.22 | 4464.53 | 639.99 | 3655.48 | 166.91 |
PERIMETER_MID_ZN_4 | 2246406.35 | 0.00 | 2246406.35 | 189620.80 | 2436027.15 | 1787312.18 | 4682.04 | 534.64 | 3543.31 | 166.89 |
Total Facility | 67197975.23 | 0.00 | 67197975.23 | 5450411.94 | 72648387.17 | 67658168.57 | 6891.31 | 1657.75 | 4596.99 | 1173.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6805 | 0.0000 | 0.6805 | 0.0000 | 0.6805 | 0.4247 | 2256.50 | 363.32 | 3323.18 |
CORE_MID | 0.4898 | 0.0000 | 0.4898 | 0.0000 | 0.4898 | 0.4247 | 2512.74 | 779.18 | 2651.08 |
CORE_TOP | 0.4677 | 0.0000 | 0.4677 | 0.0000 | 0.4677 | 0.4247 | 2710.72 | 727.69 | 2504.59 |
PERIMETER_TOP_ZN_3 | 0.1134 | 0.0000 | 0.1134 | 0.0080 | 0.1214 | 0.0895 | 1922.81 | 599.85 | 3420.34 |
PERIMETER_TOP_ZN_2 | 0.1167 | 0.0000 | 0.1167 | 0.0053 | 0.1221 | 0.0567 | 1846.11 | 1055.10 | 3041.79 |
PERIMETER_TOP_ZN_1 | 0.1879 | 0.0000 | 0.1879 | 0.0080 | 0.1959 | 0.0895 | 1776.60 | 980.45 | 3185.95 |
PERIMETER_TOP_ZN_4 | 0.1051 | 0.0000 | 0.1051 | 0.0053 | 0.1104 | 0.0567 | 1824.98 | 695.27 | 3422.74 |
PERIMETER_BOT_ZN_3 | 0.0920 | 0.0000 | 0.0920 | 0.0043 | 0.0962 | 0.0895 | 3441.04 | 371.98 | 2129.98 |
PERIMETER_BOT_ZN_2 | 0.0985 | 0.0000 | 0.0985 | 0.0028 | 0.1013 | 0.0567 | 2853.37 | 364.79 | 2724.84 |
PERIMETER_BOT_ZN_1 | 0.1484 | 0.0000 | 0.1484 | 0.1332 | 0.2816 | 0.0895 | 2487.82 | 310.94 | 3144.24 |
PERIMETER_BOT_ZN_4 | 0.0852 | 0.0000 | 0.0852 | 0.0028 | 0.0880 | 0.0567 | 2959.36 | 401.28 | 2582.36 |
PERIMETER_MID_ZN_3 | 0.1119 | 0.0000 | 0.1119 | 0.0067 | 0.1185 | 0.0895 | 2105.94 | 665.10 | 3171.96 |
PERIMETER_MID_ZN_2 | 0.1064 | 0.0000 | 0.1064 | 0.0047 | 0.1111 | 0.0567 | 1732.34 | 947.71 | 2353.95 |
PERIMETER_MID_ZN_1 | 0.1908 | 0.0000 | 0.1908 | 0.0067 | 0.1974 | 0.0895 | 1707.03 | 639.82 | 3596.15 |
PERIMETER_MID_ZN_4 | 0.1031 | 0.0000 | 0.1031 | 0.0044 | 0.1076 | 0.0567 | 1924.72 | 534.47 | 3483.80 |
Total Facility | 3.0973 | 0.0000 | 3.0973 | 0.1923 | 3.2896 | 2.1513 | 4104.50 | 1657.40 | 4496.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 26529975.31 | 0.00 | 26529975.31 | 22614548.33 | 4140.67 | 2.56 | 4616.77 | 151.59 |
PACU_VAV_MID | 24157853.42 | 0.00 | 24157853.42 | 22429071.92 | 4129.49 | 3.05 | 4627.47 | 166.66 |
PACU_VAV_TOP | 23841610.56 | 0.00 | 23841610.56 | 22614548.33 | 4143.87 | 3.09 | 4613.04 | 98.12 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.2250 | 0.0000 | 1.2250 | 0.7171 | 1387.03 | 2.56 | 4553.41 |
PACU_VAV_MID | 1.1149 | 0.0000 | 1.1149 | 0.7084 | 1372.15 | 3.05 | 4567.80 |
PACU_VAV_TOP | 1.0989 | 0.0000 | 1.0989 | 0.7171 | 1395.87 | 3.09 | 4544.04 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 874.86 | 2244.75 | 0.00 | 0.00 | 0.00 | 1832.32 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 223.11 | 2343.89 | 0.00 | 0.00 | 0.00 | 2429.65 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 219.01 | 2181.10 | 0.00 | 0.00 | 0.00 | 2478.20 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.0517 | 2.2611 | 0.0000 | 0.0000 | 0.0000 | 0.8890 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0232 | 2.0019 | 0.0000 | 0.0000 | 0.0000 | 0.8400 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0192 | 2.0216 | 0.0000 | 0.0000 | 0.0000 | 0.8465 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1005 |
Defaulted Fields | 578 |
Fields with Defaults | 2423 |
Autosized Fields | 194 |
Autosizable Fields | 250 |
Autocalculated Fields | 156 |
Autocalculatable Fields | 277 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
Electricity:Building | 952.52 | 13383.13 | 26-MAR-17:20 | 66703.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 952.52 | 13383.13 | 26-MAR-17:20 | 66703.05 | 02-JAN-08:10 |
InteriorLights:Electricity | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 232.83 | 905.38 | 26-MAR-17:20 | 25003.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.14 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.67 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.68 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.12 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.79 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.79 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.66 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.26 | 17.46 | 01-JAN-08:40 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.67 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.67 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.67 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.26 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.26 | 17.46 | 01-JAN-10:00 | 658.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.14 | 413.68 | 12-MAR-17:10 | 2475.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.81 | 27.57 | 01-JAN-10:10 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.67 | 261.88 | 26-MAR-17:10 | 1567.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.26 | 17.46 | 01-JAN-08:50 | 658.76 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 31.01 | 413.67 | 12-MAR-17:10 | 2475.79 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.68 | 27.57 | 01-JAN-08:50 | 1040.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.68 | 261.87 | 12-MAR-17:10 | 1567.28 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.27 | 17.46 | 01-JAN-10:10 | 658.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 229.53 | 367.92 | 01-JAN-00:10 | 108074.54 | 17-JUL-15:40 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 02-JAN-12:10 |
ElectricityPurchased:Facility | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
ElectricityPurchased:Plant | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
Cogeneration:ElectricityPurchased | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
General:Cogeneration:ElectricityPurchased | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
ElectricityNet:Plant | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
Cogeneration:ElectricityNet | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
General:Cogeneration:ElectricityNet | 1296.09 | 13751.66 | 26-MAR-17:30 | 173928.84 | 17-JUL-15:40 |
Fans:Electricity | 97.82 | 0.00 | 01-JAN-00:10 | 33893.32 | 25-JUL-15:50 |
General:Fans:Electricity | 97.82 | 0.00 | 01-JAN-00:10 | 33893.32 | 25-JUL-15:50 |
ExteriorLights:Electricity | 51.81 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 51.81 | 0.00 | 01-JAN-08:20 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 104.82 | 0.00 | 01-JAN-00:10 | 73892.65 | 17-JUL-16:00 |
General:Cooling:Electricity | 104.82 | 0.00 | 01-JAN-00:10 | 73892.65 | 17-JUL-16:00 |
Electricity:Plant | 62.24 | 0.00 | 01-JAN-00:10 | 8104.77 | 09-JAN-12:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 59.04 | 0.00 | 01-JAN-00:10 | 7227.29 | 17-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 59.04 | 0.00 | 01-JAN-00:10 | 7227.29 | 17-FEB-12:40 |
Pumps:Electricity | 3.20 | 0.00 | 01-JAN-00:10 | 1020.53 | 09-JAN-07:10 |
General:Pumps:Electricity | 3.20 | 0.00 | 01-JAN-00:10 | 1020.53 | 09-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 6.54 | 0.00 | 01-JAN-00:10 | 702.61 | 02-JAN-08:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 609.67 | 0.00 | 01-JAN-00:10 | 312287.93 | 09-JAN-07:20 |
NaturalGas:Plant | 609.67 | 0.00 | 01-JAN-00:10 | 312287.93 | 09-JAN-07:20 |
Heating:NaturalGas | 609.67 | 0.00 | 01-JAN-00:10 | 312287.93 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 609.67 | 0.00 | 01-JAN-00:10 | 312287.93 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2405.60 | 0.00 | 01-JAN-00:10 | 641220.42 | 09-JAN-07:10 |
EnergyTransfer:Building | 1040.12 | 0.00 | 01-JAN-00:10 | 182517.91 | 17-JUL-15:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 203.00 | 0.00 | 01-JAN-00:10 | 27697.67 | 05-SEP-07:20 |
Heating:EnergyTransfer | 192.52 | 0.00 | 01-JAN-00:10 | 155396.87 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 3882.59 | 09-JAN-07:10 |
General:Heating:EnergyTransfer | 192.52 | 0.00 | 01-JAN-00:10 | 155396.87 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 3882.59 | 09-JAN-07:10 |
Cooling:EnergyTransfer | 847.60 | 0.00 | 01-JAN-00:10 | 182517.91 | 17-JUL-15:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 202.99 | 0.00 | 01-JAN-00:10 | 27697.67 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 847.60 | 0.00 | 01-JAN-00:10 | 182517.91 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 202.99 | 0.00 | 01-JAN-00:10 | 27697.67 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 52.46 | 0.00 | 01-JAN-00:10 | 16910.05 | 11-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.37 | 0.00 | 01-JAN-00:10 | 16910.05 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.37 | 0.00 | 01-JAN-00:10 | 16910.05 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.10 | 0.00 | 01-JAN-00:10 | 12598.78 | 17-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 24.10 | 0.00 | 01-JAN-00:10 | 12598.78 | 17-JUL-15:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 24.62 | 0.00 | 01-JAN-00:10 | 9599.95 | 09-JAN-08:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.33 | 0.00 | 01-JAN-00:10 | 9599.95 | 09-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.33 | 0.00 | 01-JAN-00:10 | 9599.95 | 09-JAN-08:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.30 | 0.00 | 01-JAN-00:10 | 6057.50 | 17-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.30 | 0.00 | 01-JAN-00:10 | 6057.50 | 17-JUL-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 24.90 | 0.00 | 01-JAN-00:10 | 6216.61 | 17-JUL-16:00 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:10 | 4689.34 | 30-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 7.81 | 0.00 | 01-JAN-00:10 | 4689.34 | 30-JAN-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.09 | 0.00 | 01-JAN-00:10 | 6216.61 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 17.09 | 0.00 | 01-JAN-00:10 | 6216.61 | 17-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 128.35 | 0.00 | 01-JAN-00:10 | 20421.21 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.93 | 0.00 | 01-JAN-00:10 | 14943.44 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.93 | 0.00 | 01-JAN-00:10 | 14943.44 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 126.42 | 0.00 | 01-JAN-00:10 | 20421.21 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 126.42 | 0.00 | 01-JAN-00:10 | 20421.21 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 121.96 | 0.00 | 01-JAN-00:10 | 23326.65 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.45 | 0.00 | 01-JAN-00:10 | 23326.65 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.45 | 0.00 | 01-JAN-00:10 | 23326.65 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 110.52 | 0.00 | 01-JAN-00:10 | 21375.53 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 110.52 | 0.00 | 01-JAN-00:10 | 21375.53 | 17-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.21 | 0.00 | 01-JAN-00:10 | 9331.30 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 20.15 | 0.00 | 01-JAN-00:10 | 9331.30 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 20.15 | 0.00 | 01-JAN-00:10 | 9331.30 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.06 | 0.00 | 01-JAN-00:10 | 7327.62 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.06 | 0.00 | 01-JAN-00:10 | 7327.62 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 38.25 | 0.00 | 01-JAN-00:10 | 10324.73 | 07-AUG-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.50 | 0.00 | 01-JAN-00:10 | 7844.66 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.50 | 0.00 | 01-JAN-00:10 | 7844.66 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.75 | 0.00 | 01-JAN-00:10 | 10324.73 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.75 | 0.00 | 01-JAN-00:10 | 10324.73 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.19 | 0.00 | 01-JAN-00:10 | 14398.91 | 01-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 13.89 | 0.00 | 01-JAN-00:10 | 11362.45 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 13.89 | 0.00 | 01-JAN-00:10 | 11362.45 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.30 | 0.00 | 01-JAN-00:10 | 14398.91 | 01-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 47.30 | 0.00 | 01-JAN-00:10 | 14398.91 | 01-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.82 | 0.00 | 01-JAN-00:10 | 10703.59 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.42 | 0.00 | 01-JAN-00:10 | 8200.22 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.42 | 0.00 | 01-JAN-00:10 | 8200.22 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.40 | 0.00 | 01-JAN-00:10 | 10703.59 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.40 | 0.00 | 01-JAN-00:10 | 10703.59 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 30.83 | 0.00 | 01-JAN-00:10 | 6941.04 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.98 | 0.00 | 01-JAN-00:10 | 6941.04 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 10.98 | 0.00 | 01-JAN-00:10 | 6941.04 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.84 | 0.00 | 01-JAN-00:10 | 5781.34 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 19.84 | 0.00 | 01-JAN-00:10 | 5781.34 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.47 | 0.00 | 01-JAN-00:10 | 8505.71 | 17-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.84 | 0.00 | 01-JAN-00:10 | 5749.82 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.84 | 0.00 | 01-JAN-00:10 | 5749.82 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.63 | 0.00 | 01-JAN-00:10 | 8505.71 | 17-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 24.63 | 0.00 | 01-JAN-00:10 | 8505.71 | 17-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 56.89 | 0.00 | 01-JAN-00:10 | 13058.68 | 17-JUL-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.66 | 0.00 | 01-JAN-00:10 | 12771.19 | 11-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.66 | 0.00 | 01-JAN-00:10 | 12771.19 | 11-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.23 | 0.00 | 01-JAN-00:10 | 13058.68 | 17-JUL-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 35.23 | 0.00 | 01-JAN-00:10 | 13058.68 | 17-JUL-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.63 | 0.00 | 01-JAN-00:10 | 8493.35 | 04-AUG-18:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.27 | 0.00 | 01-JAN-00:10 | 5893.51 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.27 | 0.00 | 01-JAN-00:10 | 5893.51 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.37 | 0.00 | 01-JAN-00:10 | 8493.35 | 04-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.37 | 0.00 | 01-JAN-00:10 | 8493.35 | 04-AUG-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.06 | 0.00 | 01-JAN-00:10 | 7595.79 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 9.96 | 0.00 | 01-JAN-00:10 | 7595.79 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 9.96 | 0.00 | 01-JAN-00:10 | 7595.79 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.11 | 0.00 | 01-JAN-00:10 | 6651.52 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.11 | 0.00 | 01-JAN-00:10 | 6651.52 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 32.66 | 0.00 | 01-JAN-00:10 | 10300.38 | 07-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.67 | 0.00 | 01-JAN-00:10 | 6532.84 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.67 | 0.00 | 01-JAN-00:10 | 6532.84 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.99 | 0.00 | 01-JAN-00:10 | 10300.38 | 07-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 26.99 | 0.00 | 01-JAN-00:10 | 10300.38 | 07-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 57.04 | 0.00 | 01-JAN-00:10 | 13617.32 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.20 | 0.00 | 01-JAN-00:10 | 9267.40 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.20 | 0.00 | 01-JAN-00:10 | 9267.40 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.84 | 0.00 | 01-JAN-00:10 | 13617.32 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.84 | 0.00 | 01-JAN-00:10 | 13617.32 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.77 | 0.00 | 01-JAN-00:10 | 10118.93 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.08 | 0.00 | 01-JAN-00:10 | 6508.94 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.08 | 0.00 | 01-JAN-00:10 | 6508.94 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.68 | 0.00 | 01-JAN-00:10 | 10118.93 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.68 | 0.00 | 01-JAN-00:10 | 10118.93 | 17-JUL-17:00 |
PlantLoopHeatingDemand:Facility | 490.05 | 0.00 | 01-JAN-00:10 | 250935.21 | 09-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
EnergyTransfer:HVAC | 878.72 | 0.00 | 01-JAN-00:10 | 279536.70 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 433.82 | 0.00 | 01-JAN-00:10 | 248625.66 | 09-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 433.82 | 0.00 | 01-JAN-00:10 | 248625.66 | 09-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 433.82 | 0.00 | 01-JAN-00:10 | 248625.66 | 09-JAN-07:30 |
CoolingCoils:EnergyTransfer | 444.90 | 0.00 | 01-JAN-00:10 | 279533.71 | 07-SEP-15:00 |
EnergyTransfer:Plant | 486.75 | 0.00 | 01-JAN-00:10 | 249679.43 | 09-JAN-07:30 |
WaterSystems:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 56.23 | 0.00 | 01-JAN-00:10 | 7105.18 | 17-FEB-12:10 |
Boilers:EnergyTransfer | 430.53 | 0.00 | 01-JAN-00:10 | 247369.88 | 09-JAN-07:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.016 | -202.985 | 0.000 | 0.000 | 33.059 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -136.112 |
CORE_MID | 0.000 | 0.000 | 1.928 | -126.417 | 0.000 | 0.000 | 34.231 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -80.765 |
CORE_TOP | 0.000 | 0.000 | 11.446 | -110.515 | 0.000 | 0.000 | 35.097 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -107.052 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 20.148 | -23.062 | 0.000 | 0.000 | 7.621 | 6.807 | 24.333 | 16.885 | 0.000 | 0.048 | 0.003 | 0.000 | -39.191 | 0.000 | -5.215 | -8.373 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 11.503 | -26.747 | 0.000 | 0.000 | 4.722 | 4.263 | 15.404 | 37.674 | 0.000 | 0.031 | 0.001 | 0.000 | -24.747 | 0.000 | -3.552 | -18.551 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 13.886 | -47.302 | 0.000 | 0.000 | 7.369 | 6.683 | 24.332 | 81.406 | 0.000 | 0.046 | 0.002 | 0.000 | -37.089 | 0.000 | -5.492 | -43.838 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 12.423 | -25.397 | 0.000 | 0.000 | 4.776 | 4.272 | 15.403 | 35.985 | 0.000 | 0.031 | 0.001 | 0.000 | -25.942 | 0.000 | -3.561 | -17.989 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 10.984 | -19.842 | 0.000 | 0.000 | 7.597 | 6.791 | 24.333 | 17.224 | 0.000 | 0.028 | 0.000 | 0.000 | -40.294 | 0.000 | -2.891 | -3.931 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 5.844 | -24.627 | 0.000 | 0.000 | 4.684 | 4.256 | 15.404 | 37.792 | 0.000 | 0.017 | 0.001 | 0.000 | -25.829 | 0.000 | -1.998 | -15.543 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 21.661 | -35.231 | 0.000 | 0.000 | 7.578 | 6.673 | 24.332 | 82.176 | 0.000 | 1.205 | 0.003 | 0.000 | -38.627 | 0.000 | -42.289 | -27.478 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 6.266 | -22.366 | 0.000 | 0.000 | 4.728 | 4.264 | 15.403 | 36.209 | 0.000 | 0.017 | 0.000 | 0.000 | -27.078 | 0.000 | -2.003 | -15.440 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 9.958 | -25.106 | 0.000 | 0.000 | 7.506 | 6.807 | 24.333 | 16.568 | 0.000 | 0.041 | 5.641 | 0.000 | -41.165 | 0.000 | -4.582 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 5.671 | -26.994 | 0.000 | 0.000 | 3.444 | 4.263 | 15.404 | 37.347 | 0.000 | 0.026 | 0.001 | 0.000 | -25.942 | 0.000 | -3.119 | -10.099 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 6.202 | -50.840 | 0.000 | 0.000 | 7.259 | 6.683 | 24.332 | 81.025 | 0.000 | 0.039 | 0.002 | 0.000 | -38.940 | 0.000 | -4.819 | -30.940 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.084 | -26.683 | 0.000 | 0.000 | 4.704 | 4.272 | 15.403 | 35.781 | 0.000 | 0.026 | 0.002 | 0.000 | -27.232 | 0.000 | -3.124 | -9.232 |
TOPFLOOR_PLENUM | 28.366 | -24.095 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.049 | 3.634 | 0.000 | 0.000 | 0.000 | -7.953 | -0.000 |
MIDFLOOR_PLENUM | 12.328 | -12.297 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.059 | 7.775 | 0.000 | 0.000 | 0.000 | -7.866 | -0.000 |
FIRSTFLOOR_PLENUM | 7.808 | -17.091 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.046 | 15.612 | 0.000 | 0.000 | 0.000 | -6.374 | -0.000 |
Total Facility | 48.502 | -53.482 | 144.019 | -794.115 | 0.000 | 0.000 | 174.374 | 232.828 | 719.689 | 516.072 | 0.000 | 1.708 | 32.677 | 0.000 | -392.076 | 0.000 | -104.840 | -525.343 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-05:12 | 0.00 | 0.00 | 0.00 | -39178.46 | 0.00 | 0.00 | 312.03 | 548.43 | 7410.35 | 0.00 | 0.00 | 0.00 | 30907.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | -31045.17 | 0.00 | 0.00 | 685.35 | 1645.36 | 3025.92 | 0.00 | 0.00 | 0.00 | 25688.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-05:12 | 0.00 | 0.00 | 0.00 | -32091.45 | 0.00 | 0.00 | 311.09 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 28206.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -11298.90 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4134.57 | 0.00 | 52.14 | 6698.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:52 | 0.00 | 0.00 | 0.00 | -14763.19 | 0.00 | 0.00 | 11.46 | 17.46 | 302.86 | 12721.23 | 0.00 | 0.00 | 1716.57 | 0.00 | -0.00 | 0.00 | -6.39 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-13:01 | 0.00 | 0.00 | 0.00 | -21325.74 | 0.00 | 0.00 | 17.83 | 27.57 | 478.41 | 16417.79 | 0.00 | 98.80 | 4285.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-17:01 | 0.00 | 0.00 | 0.00 | -17901.40 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 12569.57 | 0.00 | 0.00 | 5087.96 | 0.00 | -0.00 | 0.00 | -18.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-18:21 | 0.00 | 0.00 | 0.00 | -8521.45 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4511.66 | 0.00 | 27.77 | 3568.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 16-JUL-09:41 | 0.00 | 0.00 | 0.00 | -12484.89 | 0.00 | 0.00 | 14.58 | 17.46 | 302.86 | 9806.25 | 0.00 | 0.00 | 2371.53 | 0.00 | -0.00 | 0.00 | -27.79 | 0.00 |
PERIMETER_BOT_ZN_1 | 03-SEP-13:12 | 0.00 | 0.00 | 0.00 | -15283.03 | 0.00 | 0.00 | 21.16 | 27.57 | 478.41 | 16292.72 | 0.00 | 82.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1618.98 |
PERIMETER_BOT_ZN_4 | 16-JUL-18:21 | 0.00 | 0.00 | 0.00 | -14243.55 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 11781.24 | 0.00 | 9.30 | 2191.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:22 | 0.00 | 0.00 | 0.00 | -10549.62 | 0.00 | 0.00 | 0.00 | 27.57 | 386.10 | 4415.16 | 0.00 | 43.77 | 5677.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -15914.06 | 0.00 | 0.00 | 12.23 | 17.46 | 302.86 | 11454.60 | 0.00 | 0.00 | 4183.15 | 0.00 | -0.00 | 0.00 | -56.23 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-13:31 | 0.00 | 0.00 | 0.00 | -19043.23 | 0.00 | 0.00 | 20.84 | 27.57 | 478.41 | 19037.69 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -171.45 | -349.83 |
PERIMETER_MID_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -17101.18 | 0.00 | 0.00 | 0.00 | 17.46 | 244.42 | 13307.97 | 0.00 | 14.24 | 3517.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:00 | 0.00 | -12598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12598.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-06:10 | 0.00 | -6749.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6773.02 | 0.00 | -0.00 | 0.00 | -23.89 | 0.00 |
FIRSTFLOOR_PLENUM | 05-SEP-06:10 | 0.00 | -6470.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6488.27 | 0.00 | -0.00 | 0.00 | -18.18 | 0.00 |
Total Facility | 07-AUG-06:03 | 0.00 | -7252.76 | 0.00 | -182794.67 | 0.00 | 0.00 | 3474.27 | 6640.78 | 22496.85 | 20645.90 | 0.00 | 0.00 | 141573.68 | 0.00 | -1185.67 | 0.00 | -3598.40 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 09-JAN-06:02 | 0.00 | 0.00 | 6774.67 | 0.00 | 0.00 | 0.00 | 466.56 | 211.73 | 7410.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -14863.31 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 17208.27 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19862.06 |
CORE_TOP | 31-DEC-22:02 | 0.00 | 0.00 | 25909.46 | 0.00 | 0.00 | 0.00 | 0.00 | 211.73 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27952.74 |
PERIMETER_TOP_ZN_3 | 30-JAN-04:42 | 0.00 | 0.00 | 10273.94 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3401.75 | 0.00 | -788.28 | -6643.35 |
PERIMETER_TOP_ZN_2 | 30-JAN-04:42 | 0.00 | 0.00 | 9500.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2268.19 | 0.00 | -530.96 | -7055.49 |
PERIMETER_TOP_ZN_1 | 31-DEC-08:62 | 0.00 | 0.00 | 13389.25 | 0.00 | 0.00 | 0.00 | 60.55 | 57.81 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4568.93 | 0.00 | -723.15 | -8693.94 |
PERIMETER_TOP_ZN_4 | 30-JAN-04:42 | 0.00 | 0.00 | 10140.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2334.22 | 0.00 | -532.90 | -7627.92 |
PERIMETER_BOT_ZN_3 | 31-DEC-22:02 | 0.00 | 0.00 | 7504.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4231.46 | 0.00 | -182.55 | -3521.47 |
PERIMETER_BOT_ZN_2 | 31-DEC-22:02 | 0.00 | 0.00 | 7039.73 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2823.77 | 0.00 | -122.58 | -4366.06 |
PERIMETER_BOT_ZN_1 | 09-JAN-07:08 | 0.00 | 0.00 | 13803.01 | 0.00 | 0.00 | 0.00 | 218.87 | 346.86 | 637.88 | 0.00 | 0.00 | 0.00 | 18702.88 | 0.00 | -4623.65 | 0.00 | -29085.84 | 0.00 |
PERIMETER_BOT_ZN_4 | 31-DEC-22:02 | 0.00 | 0.00 | 7393.12 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2770.66 | 0.00 | -122.59 | -4772.54 |
PERIMETER_MID_ZN_3 | 29-JAN-22:42 | 0.00 | 0.00 | 8223.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4415.81 | 0.00 | -466.40 | -3771.79 |
PERIMETER_MID_ZN_2 | 30-JAN-04:42 | 0.00 | 0.00 | 7993.17 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2350.86 | 0.00 | -455.27 | -5541.20 |
PERIMETER_MID_ZN_1 | 09-JAN-05:11 | 0.00 | 0.00 | 10694.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4358.74 | 0.00 | -393.59 | -6501.11 |
PERIMETER_MID_ZN_4 | 30-JAN-04:42 | 0.00 | 0.00 | 8218.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.26 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2418.29 | 0.00 | -456.13 | -5698.32 |
TOPFLOOR_PLENUM | 29-DEC-06:09 | 17764.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17764.87 |
MIDFLOOR_PLENUM | 09-JAN-08:30 | 9694.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -48.78 | -9646.10 |
FIRSTFLOOR_PLENUM | 06-NOV-06:01 | 6444.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -67.64 | -6377.07 |
Total Facility | 09-JAN-06:02 | 27644.48 | 0.00 | 137849.36 | 0.00 | 0.00 | 0.00 | 2512.81 | 1072.56 | 19712.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45852.93 | 0.00 | -6492.47 | -136446.16 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.0258 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.2793 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.9743 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.3930 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.7443 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.0129 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0737 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.9871 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0756 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.1965 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0743 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9025 | 2.9025 | 0.6356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3324 | 2.3324 | 0.6368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4580 | 2.4580 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7635 | 0.7635 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9195 | 0.9195 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2163 | 1.2163 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0358 | 1.0358 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5904 | 0.5904 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7515 | 0.7515 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9660 | 0.9660 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8155 | 0.8155 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6623 | 0.6623 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9100 | 0.9100 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1114 | 1.1114 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9581 | 0.9581 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.0258 | 5.2793 | 6.0258 | 1.0737 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.9743 | 4.9668 | 5.9743 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.3930 | 5.7443 | 6.3930 | 1.0743 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4512 | 1.4512 | 0.6356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1662 | 1.1662 | 0.6368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2290 | 1.2290 | 0.6366 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3818 | 0.3818 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4597 | 0.4597 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6081 | 0.6081 | 0.1338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5179 | 0.5179 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2952 | 0.2952 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3757 | 0.3757 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4830 | 0.4830 | 0.1343 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4077 | 0.4077 | 0.0848 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3312 | 0.3312 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4550 | 0.4550 | 0.0846 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5557 | 0.5557 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4791 | 0.4791 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.0129 | 1.0737 | 1.0737 | 1.0737 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.9871 | 1.0756 | 1.0756 | 1.0756 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.1965 | 1.0743 | 1.0743 | 1.0743 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 488.17 |
Number of hours cooling loads not met | 113.50 |
Number of hours not met | 601.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 609.67 | 312287.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 104.82 | 73892.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 232.83 | 25003.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 51.81 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 97.82 | 33893.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 3.20 | 1020.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 59.04 | 7227.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 1296.09 |
Natural Gas | 0.00 | 609.67 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 1905.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.73 |
Space Heating | 0.00 |
Space Cooling | 21.04 |
Fans (All) | 19.63 |
Service Water Heating | 11.85 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 260.14 |
Subtotal | 260.14 |
Natural Gas [MJ/m2] | |
Space Heating | 122.37 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 122.37 |
Subtotal | 122.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.22 |
Space Heating | 31.99 |
Space Cooling | 5.50 |
Fans (All) | 5.13 |
Service Water Heating | 3.10 |
Receptacle Equipment | 37.76 |
Miscellaneous | 4.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 737. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8736.67 | 23.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8687.33 | 72.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8687.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 72.67 | 0.00 | 0.00 | 0.00 |
Average | 8745.05 | 14.95 | 0.00 | 0.00 | 0.00 |
Sum | 157410.83 | 269.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128282.67 | 21.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 21.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.15 | 1.19 | 0.00 | 0.00 | 0.00 |
Sum | 614558.67 | 21.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8713.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 46.33 | 0.00 | 0.00 | 0.00 |
Average | 8750.32 | 9.68 | 0.00 | 0.00 | 0.00 |
Sum | 157505.83 | 174.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128269.50 | 34.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128285.67 | 18.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128297.00 | 7.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128297.00 | 34.50 | 0.00 | 0.00 | 0.00 |
Average | 34140.01 | 3.32 | 0.00 | 0.00 | 0.00 |
Sum | 614520.17 | 59.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:02
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841510E+10 | 9198.49 | 19-JAN-16:40 | -6.1 | -7.8 | 0.180156E+10 | 2606.63 | 20-JAN-10:20 | -2.9 | -5.7 |
February | 0.885107E+10 | 16618.59 | 28-FEB-17:00 | 10.00 | 4.31 | 0.172473E+10 | 2606.63 | 28-FEB-10:20 | 10.00 | 4.31 |
March | 0.128993E+11 | 18957.57 | 01-MAR-07:01 | -9.6 | -10.3 | 0.213204E+10 | 2606.64 | 01-MAR-10:09 | 0.47 | -1.2 |
April | 0.150278E+11 | 33098.86 | 27-APR-06:02 | -1.7 | -3.3 | 0.191419E+10 | 2606.64 | 06-APR-09:09 | -1.7 | -3.3 |
May | 0.186095E+11 | 38945.13 | 30-MAY-05:12 | 15.60 | 11.34 | 0.207756E+10 | 2606.81 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.240920E+11 | 38704.10 | 26-JUN-05:12 | 10.33 | 9.12 | 0.207229E+10 | 2606.67 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.256033E+11 | 39184.49 | 05-JUL-05:12 | 9.40 | 8.79 | 0.192820E+10 | 2606.70 | 13-JUL-09:00 | 23.30 | 13.98 |
August | 0.265573E+11 | 38800.30 | 01-AUG-05:12 | 12.40 | 9.51 | 0.216340E+10 | 2606.66 | 15-AUG-13:30 | 25.00 | 13.67 |
September | 0.222141E+11 | 39087.40 | 06-SEP-05:12 | 15.00 | 12.76 | 0.192031E+10 | 2606.72 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.183220E+11 | 35348.77 | 19-OCT-06:02 | 12.02 | 5.45 | 0.199379E+10 | 2606.64 | 13-OCT-09:20 | 12.02 | 5.45 |
November | 0.129573E+11 | 35232.92 | 06-NOV-06:01 | -3.5 | -4.3 | 0.196074E+10 | 2606.64 | 03-NOV-09:09 | -3.5 | -4.3 |
December | 0.943679E+10 | 13269.63 | 07-DEC-16:10 | 6.32 | 2.06 | 0.184651E+10 | 2606.64 | 07-DEC-10:09 | 6.32 | 2.06 |
Annual Sum or Average | 0.202986E+12 | 0.235353E+11 | ||||||||
Minimum of Months | 0.841510E+10 | 9198.49 | -9.6 | -10.3 | 0.172473E+10 | 2606.63 | -3.5 | -5.7 | ||
Maximum of Months | 0.265573E+11 | 39184.49 | 15.60 | 12.76 | 0.216340E+10 | 2606.81 | 25.17 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 902198.35 | 235.73 | 14-JAN-13:30 | 10.00 | 4.73 | 0.00 | 0.00 | 01-JAN-00:10 | 10.00 | 4.73 |
February | 69181833.02 | 1692.85 | 26-FEB-14:54 | 16.70 | 6.48 | 0.00 | 0.00 | 01-FEB-00:10 | 16.70 | 6.48 |
March | 0.291514E+09 | 2252.71 | 28-MAR-15:20 | 10.60 | 3.01 | 0.00 | 0.00 | 01-MAR-00:10 | 10.60 | 3.01 |
April | 0.102282E+10 | 5918.86 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.230605E+10 | 8902.43 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.491332E+10 | 10114.10 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.654214E+10 | 12598.78 | 17-JUL-15:00 | 36.10 | 17.00 | 0.00 | 0.00 | 01-JUL-00:10 | 36.10 | 17.00 |
August | 0.562408E+10 | 11380.50 | 07-AUG-15:30 | 32.50 | 16.07 | 0.00 | 0.00 | 01-AUG-00:10 | 32.50 | 16.07 |
September | 0.261916E+10 | 8501.42 | 05-SEP-14:20 | 24.40 | 15.02 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 15.02 |
October | 0.671345E+09 | 5403.15 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 34495825.42 | 1324.71 | 03-NOV-14:40 | 14.73 | 7.74 | 0.00 | 0.00 | 01-NOV-00:10 | 14.73 | 7.74 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.240950E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.654214E+10 | 12598.78 | 36.10 | 17.00 | 0.00 | 0.00 | 36.10 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13670427.19 | 3566.64 | 26-JAN-05:01 | -22.2 | -22.7 | 0.00 | 0.00 | 01-JAN-00:10 | -22.2 | -22.7 |
February | 13537477.77 | 3662.04 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 47251467.27 | 3323.32 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.242070E+09 | 2316.86 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.757556E+09 | 3120.98 | 19-MAY-16:00 | 27.80 | 14.54 | 0.00 | 0.00 | 01-MAY-00:10 | 27.80 | 14.54 |
June | 0.253703E+10 | 4562.68 | 26-JUN-06:08 | 13.03 | 10.64 | 0.00 | 0.00 | 01-JUN-00:10 | 13.03 | 10.64 |
July | 0.362519E+10 | 6057.50 | 17-JUL-15:40 | 36.83 | 17.19 | 0.00 | 0.00 | 01-JUL-00:10 | 36.83 | 17.19 |
August | 0.325327E+10 | 6200.88 | 07-AUG-06:10 | 19.45 | 10.91 | 0.00 | 0.00 | 01-AUG-00:10 | 19.45 | 10.91 |
September | 0.150500E+10 | 6748.51 | 05-SEP-06:10 | 18.90 | 13.05 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 13.05 |
October | 0.264511E+09 | 2348.12 | 05-OCT-06:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.2 |
November | 31628696.16 | 2674.67 | 10-NOV-07:01 | -4.5 | -5.4 | 0.00 | 0.00 | 01-NOV-00:10 | -4.5 | -5.4 |
December | 6030043.08 | 3150.76 | 28-DEC-05:11 | -22.4 | -22.8 | 0.00 | 0.00 | 01-DEC-00:10 | -22.4 | -22.8 |
Annual Sum or Average | 0.122967E+11 | 0.00 | ||||||||
Minimum of Months | 6030043.08 | 2316.86 | -22.4 | -22.8 | 0.00 | 0.00 | -22.4 | -22.8 | ||
Maximum of Months | 0.362519E+10 | 6748.51 | 36.83 | 17.19 | 0.00 | 0.00 | 36.83 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138756E+09 | 3582.85 | 27-JAN-05:01 | -27.8 | -28.2 | 0.00 | 0.00 | 01-JAN-00:10 | -27.8 | -28.2 |
February | 0.140608E+09 | 3526.12 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 0.234275E+09 | 3428.94 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.585380E+09 | 3453.07 | 29-APR-05:01 | -7.7 | -8.6 | 0.00 | 0.00 | 01-APR-00:10 | -7.7 | -8.6 |
May | 0.121089E+10 | 3549.63 | 30-MAY-06:15 | 15.40 | 11.37 | 0.00 | 0.00 | 01-MAY-00:10 | 15.40 | 11.37 |
June | 0.310479E+10 | 4864.85 | 26-JUN-06:15 | 13.87 | 11.01 | 0.00 | 0.00 | 01-JUN-00:10 | 13.87 | 11.01 |
July | 0.421020E+10 | 6216.61 | 17-JUL-16:00 | 37.20 | 17.28 | 0.00 | 0.00 | 01-JUL-00:10 | 37.20 | 17.28 |
August | 0.401336E+10 | 5893.05 | 07-AUG-16:00 | 32.20 | 16.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 16.16 |
September | 0.229343E+10 | 6469.39 | 05-SEP-06:10 | 18.90 | 13.05 | 0.00 | 0.00 | 01-SEP-00:10 | 18.90 | 13.05 |
October | 0.869048E+09 | 2843.13 | 18-OCT-16:00 | 24.40 | 11.02 | 0.00 | 0.00 | 01-OCT-00:10 | 24.40 | 11.02 |
November | 0.170386E+09 | 2152.60 | 09-NOV-07:06 | -1.5 | -2.5 | 0.00 | 0.00 | 01-NOV-00:10 | -1.5 | -2.5 |
December | 0.119805E+09 | 3376.43 | 29-DEC-05:11 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.170909E+11 | 0.00 | ||||||||
Minimum of Months | 0.119805E+09 | 2152.60 | -27.8 | -28.2 | 0.00 | 0.00 | -27.8 | -28.2 | ||
Maximum of Months | 0.421020E+10 | 6469.39 | 37.20 | 17.28 | 0.00 | 0.00 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.446331E+10 | 7311.44 | 27-JAN-17:11 | -23.7 | -24.3 | 0.154829E+10 | 2276.83 | 13-JAN-16:00 | -23.7 | -24.3 |
February | 0.531859E+10 | 9310.35 | 28-FEB-17:00 | 10.00 | 4.31 | 0.152909E+10 | 2606.63 | 28-FEB-10:20 | 10.00 | 4.31 |
March | 0.750530E+10 | 9270.93 | 01-MAR-17:00 | 7.80 | 3.22 | 0.198414E+10 | 2606.64 | 01-MAR-10:20 | 7.80 | 3.22 |
April | 0.894226E+10 | 12543.18 | 25-APR-16:00 | 17.80 | 7.70 | 0.186833E+10 | 2606.65 | 06-APR-09:09 | 17.80 | 7.70 |
May | 0.113542E+11 | 30166.89 | 30-MAY-05:12 | 15.60 | 11.34 | 0.203196E+10 | 2606.81 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.165396E+11 | 31043.98 | 26-JUN-06:03 | 13.03 | 10.64 | 0.206516E+10 | 2606.66 | 01-JUN-09:20 | 13.03 | 10.64 |
July | 0.181645E+11 | 30903.35 | 31-JUL-05:12 | 14.60 | 10.97 | 0.192281E+10 | 2610.39 | 17-JUL-09:39 | 14.60 | 10.97 |
August | 0.182101E+11 | 30647.97 | 08-AUG-05:12 | 18.13 | 11.59 | 0.215756E+10 | 2611.27 | 07-AUG-09:39 | 18.13 | 11.59 |
September | 0.137843E+11 | 30292.55 | 06-SEP-05:12 | 15.00 | 12.76 | 0.190890E+10 | 2606.70 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.997002E+10 | 13240.53 | 18-OCT-16:00 | 24.40 | 11.02 | 0.195227E+10 | 2606.64 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.689218E+10 | 9923.38 | 03-NOV-16:00 | 14.30 | 7.69 | 0.180105E+10 | 2606.64 | 03-NOV-09:09 | 14.30 | 7.69 |
December | 0.527342E+10 | 6107.58 | 29-DEC-16:50 | -20.9 | -21.4 | 0.159397E+10 | 2562.92 | 07-DEC-14:00 | -20.9 | -21.4 |
Annual Sum or Average | 0.126418E+12 | 0.223635E+11 | ||||||||
Minimum of Months | 0.446331E+10 | 6107.58 | -23.7 | -24.3 | 0.152909E+10 | 2276.83 | -23.7 | -24.3 | ||
Maximum of Months | 0.182101E+11 | 31043.98 | 24.40 | 12.76 | 0.215756E+10 | 2611.27 | 18.13 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228968E+10 | 7443.32 | 07-JAN-17:03 | -21.8 | -22.3 | 0.147614E+10 | 2216.92 | 13-JAN-16:00 | 7.80 | 3.93 |
February | 0.363473E+10 | 7550.53 | 28-FEB-17:00 | 10.00 | 4.31 | 0.142620E+10 | 2606.55 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.604125E+10 | 7840.70 | 29-MAR-16:00 | 12.20 | 4.07 | 0.183892E+10 | 2606.59 | 23-MAR-13:20 | 12.20 | 4.07 |
April | 0.776699E+10 | 13462.83 | 25-APR-16:00 | 17.80 | 7.70 | 0.178107E+10 | 2606.62 | 25-APR-09:20 | 17.80 | 7.70 |
May | 0.104064E+11 | 16643.24 | 30-MAY-15:30 | 19.40 | 10.94 | 0.197783E+10 | 2606.82 | 02-MAY-13:09 | 19.40 | 10.94 |
June | 0.161645E+11 | 28425.22 | 26-JUN-06:02 | 13.03 | 10.64 | 0.205699E+10 | 2606.67 | 01-JUN-09:39 | 13.03 | 10.64 |
July | 0.182204E+11 | 31618.43 | 17-JUL-05:12 | 16.83 | 12.38 | 0.191925E+10 | 2606.66 | 13-JUL-09:00 | 16.83 | 12.38 |
August | 0.175647E+11 | 32051.15 | 07-AUG-05:12 | 17.77 | 10.09 | 0.215137E+10 | 2606.65 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.122143E+11 | 32089.80 | 05-SEP-05:12 | 18.50 | 11.75 | 0.187591E+10 | 2606.69 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.797708E+10 | 13142.55 | 18-OCT-16:00 | 24.40 | 11.02 | 0.185874E+10 | 2606.62 | 16-OCT-09:20 | 24.40 | 11.02 |
November | 0.511902E+10 | 7913.88 | 03-NOV-16:00 | 14.30 | 7.69 | 0.165677E+10 | 2606.53 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.311677E+10 | 5284.77 | 07-DEC-16:25 | 5.55 | 1.71 | 0.147780E+10 | 2410.40 | 07-DEC-14:00 | 5.55 | 1.71 |
Annual Sum or Average | 0.110516E+12 | 0.214970E+11 | ||||||||
Minimum of Months | 0.228968E+10 | 5284.77 | -21.8 | -22.3 | 0.142620E+10 | 2216.92 | 5.55 | 1.71 | ||
Maximum of Months | 0.182204E+11 | 32089.80 | 24.40 | 12.38 | 0.215137E+10 | 2606.82 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21897839.14 | 1432.88 | 07-JAN-17:03 | -21.8 | -22.3 | 0.299826E+09 | 406.82 | 25-JAN-10:09 | -13.3 | -14.0 |
February | 0.218737E+09 | 1188.70 | 04-FEB-17:03 | -17.9 | -18.3 | 0.281470E+09 | 515.13 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.641952E+09 | 1245.71 | 29-MAR-15:40 | 12.40 | 4.13 | 0.352957E+09 | 535.00 | 29-MAR-15:00 | 12.20 | 4.07 |
April | 0.125173E+10 | 3535.41 | 07-APR-14:30 | 22.50 | 9.29 | 0.345493E+09 | 549.49 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.226633E+10 | 5267.30 | 19-MAY-16:00 | 27.80 | 14.54 | 0.397651E+09 | 549.53 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.442751E+10 | 8850.32 | 21-JUN-06:03 | 17.38 | 13.20 | 0.429781E+09 | 549.50 | 01-JUN-09:20 | 17.38 | 13.20 |
July | 0.532352E+10 | 11298.88 | 16-JUL-18:31 | 32.40 | 17.11 | 0.404139E+09 | 549.51 | 21-JUL-13:20 | 25.97 | 12.49 |
August | 0.457459E+10 | 11074.70 | 06-AUG-16:11 | 35.40 | 16.13 | 0.449204E+09 | 549.50 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.256511E+10 | 11185.66 | 03-SEP-15:01 | 32.57 | 15.68 | 0.378516E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.121046E+10 | 2810.26 | 19-OCT-14:40 | 21.50 | 10.24 | 0.359164E+09 | 549.49 | 19-OCT-13:20 | 21.50 | 10.24 |
November | 0.470995E+09 | 1103.96 | 08-NOV-15:00 | 13.20 | 7.65 | 0.317210E+09 | 512.05 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 89366404.43 | 882.96 | 06-DEC-15:50 | 9.68 | 4.65 | 0.293865E+09 | 435.86 | 06-DEC-14:00 | 9.68 | 4.65 |
Annual Sum or Average | 0.230622E+11 | 0.430927E+10 | ||||||||
Minimum of Months | 21897839.14 | 882.96 | -21.8 | -22.3 | 0.281470E+09 | 406.82 | -13.3 | -14.0 | ||
Maximum of Months | 0.532352E+10 | 11298.88 | 35.40 | 17.11 | 0.449204E+09 | 549.53 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59916427.13 | 916.62 | 07-JAN-17:03 | -21.8 | -22.3 | 0.192828E+09 | 280.88 | 20-JAN-10:39 | -2.6 | -5.4 |
February | 0.301541E+09 | 2042.66 | 27-FEB-10:30 | 13.05 | 4.83 | 0.188133E+09 | 347.87 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.763056E+09 | 4069.37 | 23-MAR-10:00 | 8.30 | 1.60 | 0.243051E+09 | 347.88 | 22-MAR-09:00 | 8.30 | 1.60 |
April | 0.167561E+10 | 6525.39 | 25-APR-09:20 | 10.33 | 5.07 | 0.231928E+09 | 347.88 | 25-APR-09:20 | 10.33 | 5.07 |
May | 0.267522E+10 | 7911.23 | 19-MAY-08:50 | 17.52 | 11.29 | 0.263797E+09 | 347.89 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.500750E+10 | 13398.00 | 18-JUN-09:32 | 17.77 | 12.44 | 0.274255E+09 | 348.56 | 23-JUN-09:00 | 27.80 | 15.44 |
July | 0.613678E+10 | 14692.07 | 09-JUL-09:42 | 22.43 | 11.86 | 0.256875E+09 | 348.46 | 03-JUL-09:00 | 22.43 | 11.86 |
August | 0.546069E+10 | 14763.91 | 06-AUG-08:52 | 27.20 | 14.17 | 0.286641E+09 | 348.62 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.288830E+10 | 14049.74 | 03-SEP-11:41 | 32.23 | 15.82 | 0.247381E+09 | 347.88 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.123220E+10 | 4862.04 | 18-OCT-09:40 | 19.07 | 8.41 | 0.244929E+09 | 347.88 | 16-OCT-09:20 | 19.07 | 8.41 |
November | 0.430225E+09 | 1912.88 | 03-NOV-09:40 | 7.90 | 4.84 | 0.212730E+09 | 347.88 | 06-NOV-10:20 | 2.80 | 0.07 |
December | 0.115965E+09 | 611.17 | 06-DEC-11:00 | 10.00 | 5.61 | 0.188650E+09 | 296.14 | 06-DEC-10:00 | 10.00 | 5.61 |
Annual Sum or Average | 0.267470E+11 | 0.283120E+10 | ||||||||
Minimum of Months | 59916427.13 | 611.17 | -21.8 | -22.3 | 0.188133E+09 | 280.88 | -2.6 | -5.4 | ||
Maximum of Months | 0.613678E+10 | 14763.91 | 32.23 | 15.82 | 0.286641E+09 | 348.62 | 27.80 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644813E+09 | 5273.06 | 19-JAN-13:40 | -6.0 | -7.8 | 0.327972E+09 | 549.49 | 13-JAN-14:00 | -6.0 | -7.8 |
February | 0.167519E+10 | 16399.17 | 26-FEB-14:12 | 15.97 | 6.00 | 0.323310E+09 | 549.54 | 28-FEB-14:20 | 10.20 | 4.61 |
March | 0.258720E+10 | 11422.24 | 01-MAR-13:55 | 6.70 | 2.77 | 0.390796E+09 | 549.55 | 23-MAR-13:39 | 9.80 | 2.29 |
April | 0.301266E+10 | 15285.52 | 16-APR-13:43 | 19.22 | 8.29 | 0.360935E+09 | 549.80 | 25-APR-13:00 | 16.10 | 6.69 |
May | 0.389594E+10 | 10618.63 | 19-MAY-13:30 | 26.65 | 14.96 | 0.405983E+09 | 549.53 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.601666E+10 | 16612.98 | 18-JUN-15:32 | 24.80 | 14.77 | 0.428917E+09 | 549.50 | 01-JUN-09:20 | 24.80 | 14.77 |
July | 0.763087E+10 | 18310.38 | 16-JUL-13:12 | 30.17 | 18.28 | 0.404033E+09 | 550.17 | 18-JUL-13:50 | 32.07 | 17.42 |
August | 0.830031E+10 | 18846.32 | 06-AUG-13:32 | 34.23 | 15.17 | 0.450435E+09 | 550.04 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.627457E+10 | 21325.45 | 03-SEP-13:01 | 33.40 | 15.99 | 0.388365E+09 | 550.13 | 05-SEP-13:00 | 24.40 | 15.14 |
October | 0.423236E+10 | 18622.48 | 15-OCT-13:42 | 23.12 | 11.08 | 0.390788E+09 | 549.70 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.210451E+10 | 11670.03 | 03-NOV-13:30 | 14.35 | 7.74 | 0.362155E+09 | 550.43 | 03-NOV-13:50 | 14.78 | 7.82 |
December | 0.927886E+09 | 5889.95 | 06-DEC-14:30 | 11.40 | 5.46 | 0.327924E+09 | 549.49 | 19-DEC-14:20 | 11.33 | 6.98 |
Annual Sum or Average | 0.473030E+11 | 0.456161E+10 | ||||||||
Minimum of Months | 0.644813E+09 | 5273.06 | -6.0 | -7.8 | 0.323310E+09 | 549.49 | -6.0 | -7.8 | ||
Maximum of Months | 0.830031E+10 | 21325.45 | 34.23 | 18.28 | 0.450435E+09 | 550.43 | 32.07 | 17.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 77820937.60 | 989.33 | 27-JAN-16:20 | -22.4 | -23.1 | 0.194021E+09 | 334.36 | 13-JAN-16:10 | -22.4 | -23.1 |
February | 0.348265E+09 | 4410.89 | 28-FEB-16:40 | 10.37 | 4.49 | 0.185885E+09 | 347.84 | 27-FEB-14:20 | 10.37 | 4.49 |
March | 0.799969E+09 | 5602.80 | 28-MAR-16:00 | 10.60 | 3.09 | 0.231348E+09 | 347.83 | 02-MAR-14:20 | 10.60 | 3.09 |
April | 0.160558E+10 | 16221.48 | 16-APR-17:02 | 19.90 | 8.94 | 0.222109E+09 | 347.85 | 07-APR-13:20 | 19.90 | 8.94 |
May | 0.284063E+10 | 15913.48 | 28-MAY-17:02 | 20.92 | 10.40 | 0.253938E+09 | 347.87 | 02-MAY-13:09 | 20.92 | 10.40 |
June | 0.454989E+10 | 16874.79 | 18-JUN-16:11 | 25.20 | 14.35 | 0.271617E+09 | 347.86 | 01-JUN-09:20 | 25.20 | 14.35 |
July | 0.546408E+10 | 17898.39 | 09-JUL-17:01 | 28.22 | 13.01 | 0.255871E+09 | 347.86 | 21-JUL-13:20 | 25.97 | 12.49 |
August | 0.485482E+10 | 16369.27 | 06-AUG-16:11 | 35.40 | 16.13 | 0.284621E+09 | 347.86 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.287949E+10 | 16499.23 | 04-SEP-16:21 | 32.80 | 16.63 | 0.241267E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.133866E+10 | 11019.11 | 15-OCT-16:23 | 21.65 | 10.63 | 0.233157E+09 | 347.85 | 19-OCT-13:20 | 21.10 | 10.10 |
November | 0.502837E+09 | 3446.23 | 03-NOV-15:40 | 14.40 | 7.69 | 0.211157E+09 | 347.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.136085E+09 | 1448.24 | 06-DEC-15:40 | 9.97 | 4.80 | 0.191408E+09 | 345.07 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.253981E+11 | 0.277640E+10 | ||||||||
Minimum of Months | 77820937.60 | 989.33 | -22.4 | -23.1 | 0.185885E+09 | 334.36 | -22.4 | -23.1 | ||
Maximum of Months | 0.546408E+10 | 17898.39 | 35.40 | 16.63 | 0.284621E+09 | 347.87 | 28.73 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16402795.04 | 1256.34 | 28-JAN-17:01 | -21.3 | -22.0 | 0.299955E+09 | 406.80 | 27-JAN-14:50 | -21.3 | -22.0 |
February | 0.218453E+09 | 1028.05 | 27-FEB-13:30 | 17.75 | 6.76 | 0.280972E+09 | 471.93 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.561087E+09 | 1036.88 | 04-MAR-17:02 | -17.9 | -18.7 | 0.345440E+09 | 483.82 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.101067E+10 | 1309.31 | 07-APR-14:30 | 22.50 | 9.29 | 0.330935E+09 | 549.40 | 07-APR-13:00 | 22.50 | 9.29 |
May | 0.167617E+10 | 3337.91 | 30-MAY-15:30 | 19.40 | 10.94 | 0.391459E+09 | 549.49 | 19-MAY-13:20 | 19.40 | 10.94 |
June | 0.325268E+10 | 4695.69 | 30-JUN-06:02 | 12.67 | 9.41 | 0.430770E+09 | 549.50 | 01-JUN-09:20 | 12.67 | 9.41 |
July | 0.430349E+10 | 8521.45 | 16-JUL-18:21 | 32.50 | 17.04 | 0.404361E+09 | 549.50 | 03-JUL-13:20 | 32.50 | 17.04 |
August | 0.381718E+10 | 6755.58 | 07-AUG-06:03 | 19.45 | 10.91 | 0.452031E+09 | 549.50 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.250804E+10 | 6867.40 | 05-SEP-06:03 | 18.90 | 13.05 | 0.389570E+09 | 549.50 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.151022E+10 | 2503.51 | 19-OCT-14:30 | 21.40 | 10.24 | 0.380598E+09 | 549.49 | 19-OCT-09:20 | 21.40 | 10.24 |
November | 0.788969E+09 | 1131.74 | 08-NOV-14:00 | 13.90 | 7.97 | 0.330832E+09 | 523.75 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.178513E+09 | 891.87 | 06-DEC-16:00 | 9.40 | 4.51 | 0.296750E+09 | 442.66 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.198419E+11 | 0.433367E+10 | ||||||||
Minimum of Months | 16402795.04 | 891.87 | -21.3 | -22.0 | 0.280972E+09 | 406.80 | -21.3 | -22.0 | ||
Maximum of Months | 0.430349E+10 | 8521.45 | 32.50 | 17.04 | 0.452031E+09 | 549.50 | 32.50 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68044903.95 | 840.45 | 28-JAN-17:01 | -21.3 | -22.0 | 0.192719E+09 | 285.32 | 20-JAN-10:20 | -21.3 | -22.0 |
February | 0.314978E+09 | 1663.04 | 27-FEB-10:30 | 13.05 | 4.83 | 0.189180E+09 | 347.88 | 28-FEB-10:20 | 2.03 | 0.11 |
March | 0.685289E+09 | 2477.96 | 28-MAR-08:35 | 4.07 | -0.3 | 0.242360E+09 | 347.88 | 01-MAR-10:09 | 4.07 | -0.3 |
April | 0.125782E+10 | 4217.63 | 25-APR-09:30 | 10.80 | 5.26 | 0.232457E+09 | 347.88 | 25-APR-09:20 | 10.80 | 5.26 |
May | 0.204464E+10 | 5741.91 | 19-MAY-06:03 | 12.57 | 9.29 | 0.264736E+09 | 347.89 | 02-MAY-13:09 | 12.57 | 9.29 |
June | 0.421023E+10 | 10737.70 | 25-JUN-08:41 | 16.52 | 11.73 | 0.275096E+09 | 348.32 | 23-JUN-09:00 | 16.52 | 11.73 |
July | 0.556661E+10 | 12486.03 | 16-JUL-09:41 | 23.12 | 16.45 | 0.257291E+09 | 348.41 | 13-JUL-09:50 | 23.12 | 16.45 |
August | 0.509534E+10 | 11545.44 | 06-AUG-09:32 | 29.07 | 14.77 | 0.287959E+09 | 348.30 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.293134E+10 | 11319.07 | 04-SEP-08:51 | 26.70 | 14.88 | 0.253195E+09 | 347.88 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.157141E+10 | 4152.14 | 18-OCT-09:40 | 19.07 | 8.41 | 0.255659E+09 | 347.88 | 16-OCT-09:20 | 19.07 | 8.41 |
November | 0.661079E+09 | 2132.47 | 03-NOV-09:20 | 7.10 | 4.34 | 0.225729E+09 | 347.87 | 06-NOV-10:20 | 2.80 | 0.07 |
December | 0.220020E+09 | 646.25 | 07-DEC-10:50 | 5.55 | 2.29 | 0.192226E+09 | 307.60 | 07-DEC-10:00 | 6.10 | 2.52 |
Annual Sum or Average | 0.246268E+11 | 0.286861E+10 | ||||||||
Minimum of Months | 68044903.95 | 646.25 | -21.3 | -22.0 | 0.189180E+09 | 285.32 | -21.3 | -22.0 | ||
Maximum of Months | 0.556661E+10 | 12486.03 | 29.07 | 16.45 | 0.287959E+09 | 348.41 | 27.80 | 16.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241286E+09 | 2400.06 | 14-JAN-12:30 | 10.30 | 4.97 | 0.280675E+09 | 549.47 | 02-JAN-14:09 | 10.30 | 4.97 |
February | 0.911572E+09 | 13589.49 | 26-FEB-14:42 | 16.52 | 6.36 | 0.289077E+09 | 549.58 | 27-FEB-14:09 | 18.40 | 7.06 |
March | 0.113183E+10 | 7970.96 | 01-MAR-13:06 | 5.78 | 2.13 | 0.361461E+09 | 549.51 | 13-MAR-13:09 | 8.80 | 2.43 |
April | 0.137649E+10 | 7258.58 | 25-APR-12:07 | 15.28 | 6.55 | 0.338825E+09 | 549.51 | 13-APR-13:09 | 15.28 | 6.55 |
May | 0.209628E+10 | 7567.42 | 19-MAY-14:00 | 27.20 | 15.02 | 0.381963E+09 | 549.51 | 02-MAY-13:09 | 27.20 | 15.02 |
June | 0.424809E+10 | 10912.73 | 29-JUN-12:00 | 30.60 | 14.31 | 0.419354E+09 | 549.52 | 19-JUN-13:50 | 30.60 | 14.31 |
July | 0.671393E+10 | 14947.48 | 16-JUL-12:22 | 28.60 | 17.88 | 0.402429E+09 | 607.04 | 17-JUL-12:09 | 35.18 | 16.48 |
August | 0.734554E+10 | 14712.59 | 06-AUG-13:32 | 34.23 | 15.17 | 0.447994E+09 | 604.49 | 07-AUG-12:09 | 32.80 | 15.88 |
September | 0.542355E+10 | 15283.09 | 03-SEP-13:12 | 33.50 | 16.05 | 0.387097E+09 | 564.26 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.363808E+10 | 14720.43 | 15-OCT-13:42 | 23.12 | 11.08 | 0.389675E+09 | 556.41 | 16-OCT-13:00 | 21.10 | 9.34 |
November | 0.161073E+10 | 9553.09 | 03-NOV-12:07 | 12.62 | 7.22 | 0.353545E+09 | 549.50 | 13-NOV-14:09 | 4.88 | -1.5 |
December | 0.494034E+09 | 3582.39 | 02-DEC-13:30 | 9.40 | 4.37 | 0.300791E+09 | 549.50 | 21-DEC-14:09 | 1.60 | -3.1 |
Annual Sum or Average | 0.352314E+11 | 0.435289E+10 | ||||||||
Minimum of Months | 0.241286E+09 | 2400.06 | 5.78 | 2.13 | 0.280675E+09 | 549.47 | 1.60 | -3.1 | ||
Maximum of Months | 0.734554E+10 | 15283.09 | 34.23 | 17.88 | 0.447994E+09 | 607.04 | 35.18 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63300192.89 | 921.30 | 27-JAN-16:20 | -22.4 | -23.1 | 0.193247E+09 | 308.43 | 13-JAN-16:10 | -22.4 | -23.1 |
February | 0.323609E+09 | 3418.71 | 28-FEB-16:40 | 10.37 | 4.49 | 0.185569E+09 | 347.84 | 27-FEB-14:20 | 10.37 | 4.49 |
March | 0.659123E+09 | 3578.78 | 28-MAR-17:30 | 9.75 | 2.59 | 0.230499E+09 | 347.84 | 02-MAR-14:20 | 9.75 | 2.59 |
April | 0.113073E+10 | 6834.80 | 16-APR-17:32 | 19.60 | 8.82 | 0.222620E+09 | 347.84 | 26-APR-13:20 | 11.10 | 4.81 |
May | 0.208687E+10 | 10662.40 | 28-MAY-18:02 | 19.82 | 10.31 | 0.258187E+09 | 347.85 | 04-MAY-13:20 | 19.82 | 10.31 |
June | 0.365814E+10 | 11008.91 | 24-JUN-17:42 | 26.38 | 11.78 | 0.274062E+09 | 347.86 | 29-JUN-09:20 | 25.17 | 12.64 |
July | 0.479282E+10 | 14244.32 | 16-JUL-18:21 | 32.50 | 17.04 | 0.256857E+09 | 347.86 | 13-JUL-09:00 | 32.50 | 17.04 |
August | 0.439529E+10 | 12552.30 | 06-AUG-16:11 | 35.40 | 16.13 | 0.287243E+09 | 347.86 | 07-AUG-09:20 | 28.73 | 14.88 |
September | 0.279704E+10 | 13093.48 | 04-SEP-16:51 | 32.80 | 16.77 | 0.250797E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.153841E+10 | 10467.57 | 15-OCT-16:23 | 21.65 | 10.63 | 0.249737E+09 | 347.85 | 13-OCT-09:20 | 21.65 | 10.63 |
November | 0.715473E+09 | 3108.01 | 03-NOV-15:50 | 14.35 | 7.69 | 0.221823E+09 | 347.84 | 03-NOV-13:39 | 14.35 | 7.69 |
December | 0.205504E+09 | 1124.30 | 06-DEC-15:30 | 10.25 | 4.94 | 0.193655E+09 | 338.68 | 06-DEC-16:19 | 8.50 | 3.80 |
Annual Sum or Average | 0.223663E+11 | 0.282430E+10 | ||||||||
Minimum of Months | 63300192.89 | 921.30 | -22.4 | -23.1 | 0.185569E+09 | 308.43 | -22.4 | -23.1 | ||
Maximum of Months | 0.479282E+10 | 14244.32 | 35.40 | 17.04 | 0.287243E+09 | 347.86 | 32.50 | 17.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52021188.37 | 1253.17 | 28-JAN-17:01 | -21.3 | -22.0 | 0.302814E+09 | 412.85 | 13-JAN-14:00 | -21.3 | -22.0 |
February | 0.374234E+09 | 1345.16 | 27-FEB-13:30 | 17.75 | 6.76 | 0.287322E+09 | 528.38 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.961503E+09 | 1454.35 | 29-MAR-16:00 | 12.20 | 4.07 | 0.367676E+09 | 549.37 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.151819E+10 | 3499.12 | 07-APR-14:30 | 22.50 | 9.29 | 0.363076E+09 | 549.49 | 13-APR-13:20 | 12.97 | 7.01 |
May | 0.244191E+10 | 4772.77 | 19-MAY-16:00 | 27.80 | 14.54 | 0.410582E+09 | 549.53 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.447410E+10 | 7773.45 | 30-JUN-06:02 | 12.67 | 9.41 | 0.433519E+09 | 549.51 | 29-JUN-09:20 | 12.67 | 9.41 |
July | 0.527418E+10 | 10550.05 | 16-JUL-18:22 | 32.50 | 17.04 | 0.405231E+09 | 550.57 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.463691E+10 | 9169.89 | 06-AUG-16:31 | 35.20 | 15.91 | 0.453034E+09 | 550.62 | 07-AUG-09:39 | 29.67 | 15.17 |
September | 0.278976E+10 | 9594.05 | 04-SEP-12:42 | 31.28 | 15.73 | 0.390969E+09 | 549.51 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.158034E+10 | 3087.94 | 19-OCT-14:30 | 21.40 | 10.24 | 0.380330E+09 | 549.49 | 19-OCT-13:20 | 21.40 | 10.24 |
November | 0.791639E+09 | 1339.93 | 03-NOV-13:30 | 14.35 | 7.74 | 0.332454E+09 | 538.77 | 08-NOV-14:20 | 13.67 | 7.87 |
December | 0.211036E+09 | 944.92 | 06-DEC-16:00 | 9.40 | 4.51 | 0.297736E+09 | 456.83 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.251058E+11 | 0.442474E+10 | ||||||||
Minimum of Months | 52021188.37 | 944.92 | -21.3 | -22.0 | 0.287322E+09 | 412.85 | -21.3 | -22.0 | ||
Maximum of Months | 0.527418E+10 | 10550.05 | 35.20 | 17.04 | 0.453034E+09 | 550.62 | 33.17 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94415742.32 | 791.00 | 28-JAN-17:01 | -21.3 | -22.0 | 0.142822E+09 | 303.11 | 20-JAN-11:09 | -21.3 | -22.0 |
February | 0.348694E+09 | 4565.83 | 28-FEB-13:02 | 9.08 | 4.04 | 0.142417E+09 | 356.45 | 28-FEB-13:09 | 9.08 | 4.04 |
March | 0.873605E+09 | 6332.50 | 01-MAR-13:01 | 5.78 | 2.13 | 0.184534E+09 | 356.46 | 22-MAR-10:09 | 8.22 | 3.50 |
April | 0.179811E+10 | 7409.59 | 25-APR-10:05 | 12.57 | 5.85 | 0.176833E+09 | 356.46 | 13-APR-14:09 | 12.57 | 5.85 |
May | 0.270520E+10 | 8095.90 | 19-MAY-10:05 | 20.37 | 12.65 | 0.198179E+09 | 356.48 | 02-MAY-12:09 | 20.37 | 12.65 |
June | 0.485423E+10 | 13949.23 | 11-JUN-08:32 | 17.97 | 10.86 | 0.204130E+09 | 356.47 | 20-JUN-10:09 | 21.57 | 13.11 |
July | 0.593779E+10 | 15914.37 | 02-JUL-09:01 | 22.48 | 15.33 | 0.191403E+09 | 357.22 | 17-JUL-10:09 | 31.97 | 17.44 |
August | 0.528888E+10 | 14594.75 | 06-AUG-09:12 | 28.13 | 14.48 | 0.213149E+09 | 359.50 | 07-AUG-10:09 | 30.60 | 15.34 |
September | 0.294596E+10 | 13481.30 | 04-SEP-11:22 | 30.80 | 15.64 | 0.186575E+09 | 356.46 | 14-SEP-14:09 | 21.70 | 13.36 |
October | 0.144635E+10 | 6265.90 | 18-OCT-10:05 | 20.28 | 8.90 | 0.186236E+09 | 356.45 | 18-OCT-14:09 | 25.00 | 11.44 |
November | 0.533996E+09 | 5696.63 | 02-NOV-12:01 | 6.88 | 2.55 | 0.164757E+09 | 356.45 | 02-NOV-12:09 | 6.88 | 2.55 |
December | 0.166625E+09 | 701.13 | 07-DEC-11:10 | 6.38 | 2.62 | 0.141993E+09 | 322.94 | 07-DEC-11:09 | 6.38 | 2.62 |
Annual Sum or Average | 0.269939E+11 | 0.213303E+10 | ||||||||
Minimum of Months | 94415742.32 | 701.13 | -21.3 | -22.0 | 0.141993E+09 | 303.11 | -21.3 | -22.0 | ||
Maximum of Months | 0.593779E+10 | 15914.37 | 30.80 | 15.64 | 0.213149E+09 | 359.50 | 31.97 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873358E+09 | 6335.84 | 19-JAN-13:30 | -6.2 | -7.9 | 0.335134E+09 | 549.49 | 06-JAN-14:20 | -6.2 | -7.9 |
February | 0.206755E+10 | 16825.34 | 26-FEB-13:32 | 15.40 | 5.68 | 0.332757E+09 | 549.75 | 27-FEB-14:30 | 18.60 | 7.13 |
March | 0.306978E+10 | 12204.03 | 01-MAR-13:35 | 6.33 | 2.52 | 0.405596E+09 | 549.71 | 23-MAR-13:50 | 9.90 | 2.40 |
April | 0.337759E+10 | 15993.48 | 16-APR-13:53 | 19.40 | 8.41 | 0.375097E+09 | 550.25 | 06-APR-13:20 | 19.40 | 8.41 |
May | 0.409675E+10 | 10167.27 | 14-MAY-12:33 | 15.77 | 6.71 | 0.416807E+09 | 549.98 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.599306E+10 | 13462.19 | 11-JUN-13:13 | 25.53 | 13.23 | 0.433177E+09 | 549.88 | 30-JUN-13:20 | 27.77 | 13.75 |
July | 0.752718E+10 | 17593.80 | 16-JUL-12:22 | 28.60 | 17.88 | 0.405464E+09 | 550.93 | 19-JUL-13:20 | 30.53 | 17.76 |
August | 0.825888E+10 | 16982.52 | 06-AUG-13:12 | 34.07 | 14.98 | 0.453810E+09 | 553.70 | 30-AUG-13:20 | 25.97 | 14.23 |
September | 0.655401E+10 | 17968.60 | 03-SEP-12:32 | 33.13 | 15.93 | 0.397218E+09 | 567.10 | 07-SEP-15:09 | 24.78 | 20.11 |
October | 0.497480E+10 | 19042.69 | 15-OCT-13:31 | 22.93 | 11.00 | 0.403152E+09 | 564.56 | 18-OCT-13:20 | 24.60 | 11.01 |
November | 0.276474E+10 | 12272.31 | 03-NOV-13:10 | 13.92 | 7.65 | 0.375047E+09 | 549.68 | 06-NOV-14:30 | 8.05 | 3.12 |
December | 0.128328E+10 | 6918.47 | 12-DEC-12:30 | -2.8 | -5.7 | 0.338514E+09 | 549.49 | 13-DEC-14:39 | -5.6 | -7.0 |
Annual Sum or Average | 0.508410E+11 | 0.467177E+10 | ||||||||
Minimum of Months | 0.873358E+09 | 6335.84 | -6.2 | -7.9 | 0.332757E+09 | 549.49 | -6.2 | -7.9 | ||
Maximum of Months | 0.825888E+10 | 19042.69 | 34.07 | 17.88 | 0.453810E+09 | 567.10 | 30.53 | 20.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107975E+09 | 956.33 | 27-JAN-16:35 | -22.6 | -23.3 | 0.195743E+09 | 338.68 | 13-JAN-16:19 | -22.6 | -23.3 |
February | 0.469595E+09 | 4699.00 | 28-FEB-16:40 | 10.37 | 4.49 | 0.190099E+09 | 347.84 | 24-FEB-14:50 | 10.37 | 4.49 |
March | 0.102011E+10 | 5673.21 | 28-MAR-16:00 | 10.60 | 3.09 | 0.240154E+09 | 347.84 | 29-MAR-13:20 | 12.40 | 4.30 |
April | 0.178589E+10 | 11093.71 | 16-APR-16:32 | 20.00 | 8.92 | 0.232810E+09 | 347.85 | 26-APR-13:20 | 11.10 | 4.81 |
May | 0.294854E+10 | 14785.20 | 28-MAY-17:02 | 20.92 | 10.40 | 0.261643E+09 | 347.87 | 02-MAY-13:09 | 20.92 | 10.40 |
June | 0.451361E+10 | 14638.49 | 24-JUN-17:42 | 26.38 | 11.78 | 0.274347E+09 | 347.86 | 19-JUN-13:50 | 26.38 | 11.78 |
July | 0.538672E+10 | 17101.37 | 16-JUL-17:01 | 33.22 | 17.33 | 0.256752E+09 | 348.46 | 17-JUL-09:39 | 30.77 | 17.46 |
August | 0.483534E+10 | 15010.63 | 06-AUG-16:31 | 35.20 | 15.91 | 0.287023E+09 | 348.57 | 07-AUG-09:39 | 29.67 | 15.17 |
September | 0.301770E+10 | 15149.08 | 04-SEP-16:41 | 32.80 | 16.72 | 0.248706E+09 | 347.86 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.163594E+10 | 7888.20 | 15-OCT-15:32 | 22.40 | 10.89 | 0.245309E+09 | 347.85 | 16-OCT-09:20 | 17.60 | 9.11 |
November | 0.736549E+09 | 3806.15 | 03-NOV-15:40 | 14.40 | 7.69 | 0.220399E+09 | 347.83 | 15-NOV-14:00 | 8.70 | 2.85 |
December | 0.226120E+09 | 1728.56 | 06-DEC-15:40 | 9.97 | 4.80 | 0.195499E+09 | 347.82 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.266841E+11 | 0.284848E+10 | ||||||||
Minimum of Months | 0.107975E+09 | 956.33 | -22.6 | -23.3 | 0.190099E+09 | 338.68 | -22.6 | -23.3 | ||
Maximum of Months | 0.538672E+10 | 17101.37 | 35.20 | 17.33 | 0.287023E+09 | 348.57 | 30.77 | 17.46 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14531412.73 | 6774.66 | 09-JAN-06:02 | -27.2 |
February | 1555740.23 | 5740.54 | 06-FEB-07:01 | 0.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 16087152.96 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 14531412.73 | 6774.66 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819450E+10 | 17515.13 | 27-JAN-06:09 | -27.6 |
February | 0.402830E+10 | 16294.41 | 01-FEB-06:07 | -25.0 |
March | 0.278708E+10 | 15448.32 | 06-MAR-05:13 | -17.8 |
April | 0.118231E+10 | 9363.85 | 29-APR-06:03 | -6.8 |
May | 0.851383E+09 | 9643.15 | 08-MAY-06:02 | -2.7 |
June | 0.340895E+09 | 3677.40 | 26-JUN-05:12 | 10.33 |
July | 0.194013E+09 | 5081.26 | 09-JUL-07:42 | 15.63 |
August | 0.316568E+09 | 4233.26 | 06-AUG-07:32 | 22.57 |
September | 0.622036E+09 | 3847.22 | 24-SEP-08:20 | 12.80 |
October | 0.120853E+10 | 11161.79 | 10-OCT-06:03 | -6.1 |
November | 0.279754E+10 | 14946.11 | 27-NOV-05:12 | -15.3 |
December | 0.584247E+10 | 17764.86 | 29-DEC-06:09 | -25.1 |
Annual Sum or Average | 0.283656E+11 | |||
Minimum of Months | 0.194013E+09 | 3677.40 | -27.6 | |
Maximum of Months | 0.819450E+10 | 17764.86 | 22.57 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.329770E+10 | 9694.61 | 09-JAN-08:30 | -26.9 |
February | 0.188622E+10 | 8621.59 | 06-FEB-07:12 | 0.40 |
March | 0.147645E+10 | 8089.24 | 06-MAR-06:09 | -16.3 |
April | 0.577235E+09 | 5530.93 | 16-APR-13:53 | 19.40 |
May | 0.485414E+09 | 3293.52 | 28-MAY-17:02 | 20.92 |
June | 37698476.05 | 3947.53 | 18-JUN-15:42 | 24.90 |
July | 42937558.85 | 5084.34 | 30-JUL-15:31 | 30.97 |
August | 28228353.83 | 4320.88 | 06-AUG-10:32 | 30.40 |
September | 0.189234E+09 | 5968.45 | 24-SEP-10:23 | 19.45 |
October | 0.612017E+09 | 6542.14 | 15-OCT-15:32 | 22.40 |
November | 0.144580E+10 | 7467.69 | 27-NOV-07:06 | -13.5 |
December | 0.224907E+10 | 8387.36 | 26-DEC-07:16 | -8.7 |
Annual Sum or Average | 0.123280E+11 | |||
Minimum of Months | 28228353.83 | 3293.52 | -26.9 | |
Maximum of Months | 0.329770E+10 | 9694.61 | 30.97 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227248E+10 | 5589.70 | 09-JAN-07:01 | -27.2 |
February | 0.131740E+10 | 5245.74 | 06-FEB-07:01 | 0.50 |
March | 0.890302E+09 | 3861.98 | 06-MAR-09:10 | -9.5 |
April | 0.236582E+09 | 3024.92 | 27-APR-05:03 | -1.2 |
May | 0.214062E+09 | 4541.23 | 16-MAY-05:03 | 1.28 |
June | 28647989.48 | 2500.54 | 05-JUN-05:12 | 11.33 |
July | 36135867.04 | 2815.90 | 16-JUL-15:41 | 32.88 |
August | 30136700.80 | 2875.87 | 06-AUG-15:32 | 35.20 |
September | 55737840.63 | 2888.06 | 17-SEP-12:02 | 10.68 |
October | 0.194158E+09 | 5810.27 | 04-OCT-05:02 | -0.5 |
November | 0.839418E+09 | 6443.57 | 06-NOV-06:01 | -3.5 |
December | 0.169261E+10 | 3705.49 | 26-DEC-08:19 | -9.8 |
Annual Sum or Average | 0.780767E+10 | |||
Minimum of Months | 28647989.48 | 2500.54 | -27.2 | |
Maximum of Months | 0.227248E+10 | 6443.57 | 35.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114298E+10 | 17208.28 | 09-JAN-05:11 | -27.2 |
February | 0.258342E+09 | 16341.49 | 06-FEB-05:01 | -0.4 |
March | 97727073.58 | 15363.11 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 157877.16 | 1841.90 | 01-MAY-06:01 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 62476448.02 | 14443.17 | 27-NOV-06:01 | -14.5 |
December | 0.365929E+09 | 15538.23 | 26-DEC-06:01 | -7.9 |
Annual Sum or Average | 0.192761E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.114298E+10 | 17208.28 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503693E+10 | 25863.44 | 30-JAN-04:42 | -17.3 |
February | 0.181193E+10 | 25310.49 | 06-FEB-05:01 | -0.4 |
March | 0.775396E+09 | 25155.21 | 06-MAR-05:01 | -18.4 |
April | 26246311.99 | 19279.30 | 29-APR-06:03 | -6.8 |
May | 86878141.29 | 21111.32 | 01-MAY-05:01 | -0.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 60672490.46 | 21316.15 | 10-OCT-05:01 | -6.1 |
November | 0.855459E+09 | 24861.27 | 27-NOV-05:01 | -15.4 |
December | 0.279248E+10 | 25909.40 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.114460E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.503693E+10 | 25909.40 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723024E+10 | 10273.97 | 30-JAN-04:42 | -17.3 |
February | 0.347990E+10 | 9878.01 | 05-FEB-07:42 | -20.0 |
March | 0.180126E+10 | 9991.04 | 06-MAR-03:32 | -18.5 |
April | 0.275609E+09 | 8240.54 | 29-APR-05:01 | -7.7 |
May | 0.183853E+09 | 8712.87 | 08-MAY-04:02 | -2.3 |
June | 138266.73 | 691.33 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 26996763.62 | 7209.99 | 19-SEP-06:03 | 2.20 |
October | 0.282511E+09 | 8838.27 | 10-OCT-04:02 | -5.2 |
November | 0.187327E+10 | 9909.83 | 27-NOV-04:22 | -15.7 |
December | 0.499424E+10 | 10255.37 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.201480E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.723024E+10 | 10273.97 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431972E+10 | 9500.51 | 30-JAN-04:42 | -17.3 |
February | 0.190418E+10 | 9037.75 | 05-FEB-07:42 | -20.0 |
March | 0.960884E+09 | 9135.51 | 06-MAR-03:32 | -18.5 |
April | 0.117276E+09 | 7096.92 | 29-APR-05:01 | -7.7 |
May | 92775246.63 | 7633.72 | 08-MAY-04:02 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 12161044.50 | 5502.70 | 19-SEP-06:03 | 2.20 |
October | 0.135595E+09 | 7810.62 | 10-OCT-04:02 | -5.2 |
November | 0.105072E+10 | 9045.84 | 27-NOV-04:22 | -15.7 |
December | 0.291022E+10 | 9475.63 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.115035E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.431972E+10 | 9500.51 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.520030E+10 | 13349.24 | 08-JAN-07:02 | -27.2 |
February | 0.219233E+10 | 12868.38 | 05-FEB-07:42 | -20.0 |
March | 0.129379E+10 | 12960.18 | 06-MAR-03:32 | -18.5 |
April | 0.239355E+09 | 10339.54 | 29-APR-05:01 | -7.7 |
May | 0.198533E+09 | 10976.29 | 08-MAY-04:02 | -2.3 |
June | 1443426.61 | 5072.37 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 416438.95 | 2082.19 | 18-AUG-06:03 | 8.17 |
September | 19311242.11 | 8398.83 | 19-SEP-06:03 | 2.20 |
October | 0.172617E+09 | 11165.88 | 10-OCT-04:02 | -5.2 |
November | 0.120816E+10 | 12834.74 | 27-NOV-04:22 | -15.7 |
December | 0.335940E+10 | 13389.27 | 31-DEC-08:62 | -27.6 |
Annual Sum or Average | 0.138857E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.520030E+10 | 13389.27 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458641E+10 | 10140.91 | 30-JAN-04:42 | -17.3 |
February | 0.204292E+10 | 9610.20 | 05-FEB-07:42 | -20.0 |
March | 0.110999E+10 | 9751.18 | 06-MAR-03:32 | -18.5 |
April | 0.170101E+09 | 7467.16 | 29-APR-05:01 | -7.7 |
May | 0.125130E+09 | 8070.93 | 08-MAY-04:02 | -2.3 |
June | 1038386.71 | 3348.14 | 17-JUN-06:03 | 6.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 345577.42 | 1710.32 | 18-AUG-06:03 | 8.17 |
September | 15576183.71 | 5536.13 | 19-SEP-06:03 | 2.20 |
October | 0.166902E+09 | 8281.33 | 10-OCT-04:02 | -5.2 |
November | 0.111980E+10 | 9655.31 | 27-NOV-04:22 | -15.7 |
December | 0.308468E+10 | 10116.72 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.124229E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.9 | |
Maximum of Months | 0.458641E+10 | 10140.91 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.467008E+10 | 7442.87 | 09-JAN-04:51 | -27.2 |
February | 0.231084E+10 | 7217.57 | 05-FEB-07:42 | -20.0 |
March | 0.101275E+10 | 7286.82 | 06-MAR-03:32 | -18.5 |
April | 0.107100E+09 | 6160.00 | 29-APR-05:01 | -7.7 |
May | 46057862.26 | 6214.27 | 01-MAY-05:01 | -0.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 11754771.47 | 5776.60 | 10-OCT-06:01 | -6.1 |
November | 0.511521E+09 | 6922.91 | 27-NOV-05:01 | -15.4 |
December | 0.231370E+10 | 7504.75 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.109838E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.467008E+10 | 7504.75 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265970E+10 | 7003.33 | 09-JAN-04:51 | -27.2 |
February | 0.116389E+10 | 6586.77 | 06-FEB-05:01 | -0.4 |
March | 0.412163E+09 | 6577.08 | 06-MAR-05:01 | -18.4 |
April | 30538667.99 | 5345.58 | 29-APR-05:01 | -7.7 |
May | 15784485.24 | 5357.21 | 01-MAY-05:01 | -0.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 4135527.84 | 4904.79 | 10-OCT-06:01 | -6.1 |
November | 0.271601E+09 | 6306.91 | 27-NOV-05:01 | -15.4 |
December | 0.128611E+10 | 7039.73 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.584393E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.265970E+10 | 7039.73 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635594E+10 | 13803.37 | 09-JAN-07:08 | -27.2 |
February | 0.344860E+10 | 12461.41 | 01-FEB-07:10 | -24.9 |
March | 0.242906E+10 | 12072.73 | 06-MAR-07:10 | -19.7 |
April | 0.126472E+10 | 10020.43 | 28-APR-06:10 | -5.2 |
May | 0.108581E+10 | 9472.35 | 08-MAY-06:10 | -2.7 |
June | 0.208081E+09 | 7744.46 | 16-JUN-07:00 | 2.20 |
July | 15899567.65 | 6669.12 | 05-JUL-06:05 | 9.40 |
August | 0.123836E+09 | 6900.93 | 18-AUG-06:10 | 8.17 |
September | 0.379104E+09 | 7786.86 | 19-SEP-06:10 | 2.20 |
October | 0.646446E+09 | 9449.25 | 10-OCT-06:10 | -6.1 |
November | 0.178635E+10 | 11170.39 | 27-NOV-07:10 | -13.5 |
December | 0.391789E+10 | 12740.69 | 29-DEC-07:10 | -26.0 |
Annual Sum or Average | 0.216617E+11 | |||
Minimum of Months | 15899567.65 | 6669.12 | -27.2 | |
Maximum of Months | 0.635594E+10 | 13803.37 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287467E+10 | 7330.82 | 09-JAN-04:51 | -27.2 |
February | 0.120642E+10 | 6894.90 | 06-FEB-05:01 | -0.4 |
March | 0.493140E+09 | 6880.83 | 06-MAR-05:01 | -18.4 |
April | 41935421.36 | 5394.76 | 29-APR-05:01 | -7.7 |
May | 19590577.72 | 5418.96 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 |
October | 5336991.31 | 5074.48 | 10-OCT-06:01 | -6.1 |
November | 0.266851E+09 | 6609.40 | 27-NOV-05:01 | -15.4 |
December | 0.135792E+10 | 7393.13 | 31-DEC-22:02 | -23.9 |
Annual Sum or Average | 0.626585E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.287467E+10 | 7393.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435232E+10 | 8223.29 | 29-JAN-22:42 | -26.3 |
February | 0.180695E+10 | 7771.35 | 05-FEB-19:03 | -18.2 |
March | 0.630992E+09 | 7772.75 | 06-MAR-04:42 | -18.8 |
April | 29412146.92 | 6405.79 | 29-APR-05:01 | -7.7 |
May | 31522341.98 | 6556.02 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 487009.78 | 1685.91 | 19-SEP-06:03 | 2.20 |
October | 37761327.87 | 6580.63 | 10-OCT-05:01 | -6.1 |
November | 0.654724E+09 | 7646.35 | 27-NOV-05:01 | -15.4 |
December | 0.241378E+10 | 7996.04 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.995794E+10 | |||
Minimum of Months | 0.00 | 0.00 | -26.3 | |
Maximum of Months | 0.435232E+10 | 8223.29 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255034E+10 | 7993.18 | 30-JAN-04:42 | -17.3 |
February | 0.964786E+09 | 7430.00 | 06-FEB-05:01 | -0.4 |
March | 0.323534E+09 | 7205.10 | 06-MAR-05:01 | -18.4 |
April | 11215590.01 | 5622.85 | 29-APR-05:01 | -7.7 |
May | 16579267.60 | 5815.25 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 296408.23 | 1066.12 | 19-SEP-06:03 | 2.20 |
October | 18825843.05 | 5860.19 | 10-OCT-05:01 | -6.1 |
November | 0.390581E+09 | 7279.53 | 27-NOV-05:01 | -15.4 |
December | 0.139477E+10 | 7736.70 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.567093E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.255034E+10 | 7993.18 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286114E+10 | 10693.99 | 09-JAN-05:11 | -27.2 |
February | 0.975450E+09 | 10084.94 | 06-FEB-05:01 | -0.4 |
March | 0.379051E+09 | 9905.32 | 06-MAR-05:01 | -18.4 |
April | 26662150.59 | 7874.71 | 29-APR-05:01 | -7.7 |
May | 37454142.91 | 8108.32 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 67660.50 | 451.07 | 19-SEP-06:03 | 2.20 |
October | 23579371.00 | 8139.17 | 10-OCT-05:01 | -6.1 |
November | 0.409363E+09 | 9987.67 | 27-NOV-05:01 | -15.4 |
December | 0.148900E+10 | 10513.25 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.620177E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.286114E+10 | 10693.99 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272347E+10 | 8218.59 | 30-JAN-04:42 | -17.3 |
February | 0.102693E+10 | 7650.29 | 06-FEB-05:01 | -0.4 |
March | 0.384991E+09 | 7409.47 | 06-MAR-05:01 | -18.4 |
April | 20365634.36 | 5614.65 | 29-APR-05:01 | -7.7 |
May | 23123283.56 | 5957.53 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 |
September | 240123.31 | 1310.10 | 19-SEP-06:03 | 2.20 |
October | 24124094.65 | 6009.84 | 10-OCT-05:01 | -6.1 |
November | 0.396607E+09 | 7490.16 | 27-NOV-05:01 | -15.4 |
December | 0.148440E+10 | 7978.28 | 31-DEC-23:51 | -23.3 |
Annual Sum or Average | 0.608424E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.272347E+10 | 8218.59 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670341E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538726E+09 | 888.78 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599316E+09 | 988.92 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.510378E+09 | 755.21 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532392E+09 | 582.38 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.519101E+09 | 532.07 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495023E+09 | 560.07 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.555001E+09 | 572.32 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523596E+09 | 769.87 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579262E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.630401E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.653089E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.680663E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495023E+09 | 532.07 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.670341E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411749E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335833E+09 | 529.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376164E+09 | 625.70 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321979E+09 | 454.18 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337827E+09 | 362.16 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331228E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314208E+09 | 344.75 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352720E+09 | 349.08 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329684E+09 | 421.02 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359738E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390393E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401383E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426291E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314208E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.411749E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.638238E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.521519E+09 | 776.21 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593158E+09 | 988.92 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510986E+09 | 753.56 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534979E+09 | 583.36 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522916E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497600E+09 | 561.62 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.558297E+09 | 573.39 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521470E+09 | 748.12 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563598E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601442E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.618412E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668261E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497600E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638238E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415567E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335618E+09 | 571.57 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378183E+09 | 625.66 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324178E+09 | 488.24 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337737E+09 | 425.07 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328780E+09 | 341.47 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314214E+09 | 359.10 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352231E+09 | 367.83 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331179E+09 | 527.33 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.363550E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388606E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401803E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427165E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314214E+09 | 341.47 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415567E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.667665E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.537015E+09 | 880.64 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598150E+09 | 986.98 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.509688E+09 | 744.29 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532146E+09 | 579.58 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.518835E+09 | 528.45 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.494802E+09 | 556.22 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.554703E+09 | 569.04 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.522801E+09 | 759.06 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.577284E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.628186E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.650196E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.679147E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.494802E+09 | 528.45 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.667665E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.410252E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335102E+09 | 523.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.375690E+09 | 624.69 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321660E+09 | 447.35 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337549E+09 | 360.19 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331025E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314062E+09 | 341.96 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352409E+09 | 346.52 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329242E+09 | 368.55 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359082E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.389538E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400033E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425564E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314062E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.410252E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.637064E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.520801E+09 | 756.17 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.592338E+09 | 986.98 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510378E+09 | 742.56 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534475E+09 | 580.62 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522431E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497142E+09 | 557.86 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.557740E+09 | 570.17 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.520775E+09 | 736.21 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.562804E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.600433E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.616747E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.667313E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497142E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.637064E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.414563E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.334924E+09 | 568.53 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377526E+09 | 624.65 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.323754E+09 | 483.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337407E+09 | 370.18 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328562E+09 | 338.77 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314029E+09 | 357.08 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.351938E+09 | 366.20 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.330677E+09 | 523.36 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.362684E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.387270E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.400865E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426420E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314029E+09 | 338.77 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.414563E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.670338E+09 | 1040.56 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.538724E+09 | 888.78 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599315E+09 | 988.92 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.510377E+09 | 755.18 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.532391E+09 | 582.38 | 03-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.519101E+09 | 532.07 | 26-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.495023E+09 | 560.06 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.555001E+09 | 572.31 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.523595E+09 | 769.85 | 11-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.579261E+09 | 1040.56 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.630399E+09 | 1040.56 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.653087E+09 | 1040.56 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.680661E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.495023E+09 | 532.07 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.670338E+09 | 1040.56 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.411748E+09 | 658.76 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335832E+09 | 529.58 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.376164E+09 | 625.69 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.321979E+09 | 454.17 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337827E+09 | 362.16 | 03-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.331227E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314208E+09 | 344.74 | 07-JUL-07:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352720E+09 | 349.07 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.329684E+09 | 421.00 | 13-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.359737E+09 | 658.76 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.390392E+09 | 658.76 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401382E+09 | 658.76 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426290E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.314208E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.411748E+09 | 658.76 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.638237E+09 | 1040.56 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.521519E+09 | 776.20 | 02-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.593157E+09 | 988.92 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.510985E+09 | 753.53 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.534978E+09 | 583.36 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.522916E+09 | 496.34 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.497599E+09 | 561.61 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.558296E+09 | 573.38 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.521470E+09 | 748.10 | 11-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.563597E+09 | 1040.56 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.601442E+09 | 1040.56 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.618412E+09 | 1040.56 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.668261E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.497599E+09 | 496.34 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.638237E+09 | 1040.56 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.415566E+09 | 658.71 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.335618E+09 | 571.56 | 02-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378182E+09 | 625.65 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.324177E+09 | 488.22 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.337737E+09 | 425.05 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.328780E+09 | 341.46 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.314214E+09 | 359.10 | 07-JUL-07:30 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.352231E+09 | 367.82 | 17-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.331179E+09 | 527.32 | 11-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.363549E+09 | 658.71 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.388605E+09 | 658.71 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.401803E+09 | 658.71 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.427164E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.314214E+09 | 341.46 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.415566E+09 | 658.71 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.670341E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788497E+09 |
February | 0.901968E+09 | 0.538726E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605955E+09 |
March | 0.107774E+10 | 0.599316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564541E+09 |
April | 0.956342E+09 | 0.510378E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408596E+09 |
May | 0.103597E+10 | 0.532392E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1005826.71 | 0.422055E+09 |
June | 0.103308E+10 | 0.519101E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5208719.93 | 0.219295E+09 |
July | 0.959235E+09 | 0.495023E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17592277.03 | 0.148276E+09 |
August | 0.107774E+10 | 0.555001E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15241931.24 | 0.159574E+09 |
September | 0.956342E+09 | 0.523596E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9223585.23 | 0.279098E+09 |
October | 0.994195E+09 | 0.579262E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180833.42 | 0.388012E+09 |
November | 0.984487E+09 | 0.630401E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541271E+09 |
December | 0.959235E+09 | 0.653089E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690154E+09 |
Annual Sum or Average | 0.119305E+11 | 0.680663E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48453173.56 | 0.521532E+10 |
Minimum of Months | 0.901968E+09 | 0.495023E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148276E+09 |
Maximum of Months | 0.107774E+10 | 0.670341E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17592277.03 | 0.788497E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.411749E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529606E+09 |
February | 0.571020E+09 | 0.335833E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414177E+09 |
March | 0.682301E+09 | 0.376164E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385783E+09 |
April | 0.605444E+09 | 0.321979E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282516E+09 |
May | 0.655854E+09 | 0.337827E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 661277.99 | 0.285109E+09 |
June | 0.654023E+09 | 0.331228E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3446516.56 | 0.149593E+09 |
July | 0.607275E+09 | 0.314208E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11097373.05 | 0.102669E+09 |
August | 0.682301E+09 | 0.352720E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9930400.56 | 0.109466E+09 |
September | 0.605444E+09 | 0.329684E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5785790.04 | 0.192752E+09 |
October | 0.629407E+09 | 0.359738E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38783.91 | 0.270172E+09 |
November | 0.623262E+09 | 0.390393E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366188E+09 |
December | 0.607275E+09 | 0.401383E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463695E+09 |
Annual Sum or Average | 0.755301E+10 | 0.426291E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30960142.11 | 0.355173E+10 |
Minimum of Months | 0.571020E+09 | 0.314208E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102669E+09 |
Maximum of Months | 0.682301E+09 | 0.411749E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11097373.05 | 0.529606E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.638238E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818233E+09 |
February | 0.901968E+09 | 0.521519E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655780E+09 |
March | 0.107774E+10 | 0.593158E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596409E+09 |
April | 0.956342E+09 | 0.510986E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430825E+09 |
May | 0.103597E+10 | 0.534979E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 978255.35 | 0.430965E+09 |
June | 0.103308E+10 | 0.522916E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5155194.74 | 0.221575E+09 |
July | 0.959235E+09 | 0.497600E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16614419.36 | 0.151615E+09 |
August | 0.107774E+10 | 0.558297E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14824554.42 | 0.164839E+09 |
September | 0.956342E+09 | 0.521470E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8283074.30 | 0.293346E+09 |
October | 0.994195E+09 | 0.563598E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57697.07 | 0.425983E+09 |
November | 0.984487E+09 | 0.601442E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576181E+09 |
December | 0.959235E+09 | 0.618412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726647E+09 |
Annual Sum or Average | 0.119305E+11 | 0.668261E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45913195.25 | 0.549240E+10 |
Minimum of Months | 0.901968E+09 | 0.497600E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151615E+09 |
Maximum of Months | 0.107774E+10 | 0.638238E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16614419.36 | 0.818233E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.415567E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528610E+09 |
February | 0.570983E+09 | 0.335618E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413978E+09 |
March | 0.682256E+09 | 0.378183E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385680E+09 |
April | 0.605404E+09 | 0.324178E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284318E+09 |
May | 0.655811E+09 | 0.337737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 641138.37 | 0.291389E+09 |
June | 0.653980E+09 | 0.328780E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3417911.87 | 0.150835E+09 |
July | 0.607235E+09 | 0.314214E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11062453.66 | 0.104322E+09 |
August | 0.682256E+09 | 0.352231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9899936.89 | 0.110184E+09 |
September | 0.605404E+09 | 0.331179E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5778596.81 | 0.192284E+09 |
October | 0.629366E+09 | 0.363550E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38797.84 | 0.268304E+09 |
November | 0.623221E+09 | 0.388606E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367264E+09 |
December | 0.607235E+09 | 0.401803E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464274E+09 |
Annual Sum or Average | 0.755252E+10 | 0.427165E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30838835.44 | 0.356144E+10 |
Minimum of Months | 0.570983E+09 | 0.314214E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104322E+09 |
Maximum of Months | 0.682256E+09 | 0.415567E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11062453.66 | 0.528610E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.667665E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435996E+09 |
February | 0.901968E+09 | 0.537015E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336895E+09 |
March | 0.107774E+10 | 0.598150E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307023E+09 |
April | 0.956342E+09 | 0.509688E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216346E+09 |
May | 0.103597E+10 | 0.532146E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 598578.66 | 0.224672E+09 |
June | 0.103308E+10 | 0.518835E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2978056.72 | 0.115179E+09 |
July | 0.959235E+09 | 0.494802E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10497131.44 | 77855241.38 |
August | 0.107774E+10 | 0.554703E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8567611.29 | 85829912.97 |
September | 0.956342E+09 | 0.522801E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5540440.95 | 0.156461E+09 |
October | 0.994195E+09 | 0.577284E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58318.50 | 0.227395E+09 |
November | 0.984487E+09 | 0.628186E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314109E+09 |
December | 0.959235E+09 | 0.650196E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393037E+09 |
Annual Sum or Average | 0.119305E+11 | 0.679147E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28240137.56 | 0.289080E+10 |
Minimum of Months | 0.901968E+09 | 0.494802E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77855241.38 |
Maximum of Months | 0.107774E+10 | 0.667665E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10497131.44 | 0.435996E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.410252E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293640E+09 |
February | 0.571020E+09 | 0.335102E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231928E+09 |
March | 0.682301E+09 | 0.375690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212126E+09 |
April | 0.605444E+09 | 0.321660E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153831E+09 |
May | 0.655854E+09 | 0.337549E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370260.33 | 0.156212E+09 |
June | 0.654023E+09 | 0.331025E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1880228.10 | 81514292.60 |
July | 0.607275E+09 | 0.314062E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6114783.41 | 56685262.55 |
August | 0.682301E+09 | 0.352409E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5396776.29 | 60907394.90 |
September | 0.605444E+09 | 0.329242E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3194509.86 | 0.110230E+09 |
October | 0.629407E+09 | 0.359082E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22190.87 | 0.160415E+09 |
November | 0.623262E+09 | 0.389538E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215018E+09 |
December | 0.607275E+09 | 0.400033E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265278E+09 |
Annual Sum or Average | 0.755301E+10 | 0.425564E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16978748.86 | 0.199779E+10 |
Minimum of Months | 0.571020E+09 | 0.314062E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56685262.55 |
Maximum of Months | 0.682301E+09 | 0.410252E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6114783.41 | 0.293640E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.637064E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699462E+10 |
February | 0.901968E+09 | 0.520801E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525663E+10 |
March | 0.107774E+10 | 0.592338E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510133E+10 |
April | 0.956342E+09 | 0.510378E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327477E+10 |
May | 0.103597E+10 | 0.534475E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14991216.98 | 0.306944E+10 |
June | 0.103308E+10 | 0.522431E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219921E+09 | 0.150095E+10 |
July | 0.959235E+09 | 0.497142E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527942E+09 | 0.653141E+09 |
August | 0.107774E+10 | 0.557740E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377568E+09 | 0.118911E+10 |
September | 0.956342E+09 | 0.520775E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63397689.40 | 0.206687E+10 |
October | 0.994195E+09 | 0.562804E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 812205.30 | 0.316390E+10 |
November | 0.984487E+09 | 0.600433E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438071E+10 |
December | 0.959235E+09 | 0.616747E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563796E+10 |
Annual Sum or Average | 0.119305E+11 | 0.667313E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120463E+10 | 0.422894E+11 |
Minimum of Months | 0.901968E+09 | 0.497142E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653141E+09 |
Maximum of Months | 0.107774E+10 | 0.637064E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527942E+09 | 0.699462E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.414563E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292891E+09 |
February | 0.570983E+09 | 0.334924E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231224E+09 |
March | 0.682256E+09 | 0.377526E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211609E+09 |
April | 0.605404E+09 | 0.323754E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154279E+09 |
May | 0.655811E+09 | 0.337407E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356466.02 | 0.160927E+09 |
June | 0.653980E+09 | 0.328562E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1848888.09 | 82081281.56 |
July | 0.607235E+09 | 0.314029E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6113175.05 | 57774154.10 |
August | 0.682256E+09 | 0.351938E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5362414.39 | 61207786.28 |
September | 0.605404E+09 | 0.330677E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3176342.61 | 0.110718E+09 |
October | 0.629366E+09 | 0.362684E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22197.38 | 0.159874E+09 |
November | 0.623221E+09 | 0.387270E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215295E+09 |
December | 0.607235E+09 | 0.400865E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265201E+09 |
Annual Sum or Average | 0.755252E+10 | 0.426420E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16879483.55 | 0.200308E+10 |
Minimum of Months | 0.570983E+09 | 0.314029E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57774154.10 |
Maximum of Months | 0.682256E+09 | 0.414563E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6113175.05 | 0.292891E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.670338E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681325E+09 |
February | 0.901968E+09 | 0.538724E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534091E+09 |
March | 0.107774E+10 | 0.599315E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494691E+09 |
April | 0.956342E+09 | 0.510377E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360808E+09 |
May | 0.103597E+10 | 0.532391E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 858957.03 | 0.369271E+09 |
June | 0.103308E+10 | 0.519101E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4416502.48 | 0.188241E+09 |
July | 0.959235E+09 | 0.495023E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15047156.84 | 0.127821E+09 |
August | 0.107774E+10 | 0.555001E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12894599.31 | 0.138179E+09 |
September | 0.956342E+09 | 0.523595E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7934735.64 | 0.246836E+09 |
October | 0.994195E+09 | 0.579261E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61062.86 | 0.351803E+09 |
November | 0.984487E+09 | 0.630399E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484298E+09 |
December | 0.959235E+09 | 0.653087E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604595E+09 |
Annual Sum or Average | 0.119305E+11 | 0.680661E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41213014.15 | 0.458196E+10 |
Minimum of Months | 0.901968E+09 | 0.495023E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127821E+09 |
Maximum of Months | 0.107774E+10 | 0.670338E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15047156.84 | 0.681325E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.411748E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457158E+09 |
February | 0.421807E+09 | 0.335832E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365258E+09 |
March | 0.502994E+09 | 0.376164E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338172E+09 |
April | 0.447140E+09 | 0.321979E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248787E+09 |
May | 0.484071E+09 | 0.337827E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 543530.50 | 0.249189E+09 |
June | 0.482240E+09 | 0.331227E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2817153.33 | 0.128523E+09 |
July | 0.448971E+09 | 0.314208E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9215546.05 | 88330746.17 |
August | 0.502994E+09 | 0.352720E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8219741.98 | 94722368.48 |
September | 0.447140E+09 | 0.329684E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4869599.35 | 0.169547E+09 |
October | 0.465148E+09 | 0.359737E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25921.27 | 0.243593E+09 |
November | 0.460569E+09 | 0.390392E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328312E+09 |
December | 0.448971E+09 | 0.401382E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407169E+09 |
Annual Sum or Average | 0.557719E+10 | 0.426290E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25691492.48 | 0.311876E+10 |
Minimum of Months | 0.421807E+09 | 0.314208E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88330746.17 |
Maximum of Months | 0.502994E+09 | 0.411748E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9215546.05 | 0.457158E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.638237E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709113E+09 |
February | 0.901968E+09 | 0.521519E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576416E+09 |
March | 0.107774E+10 | 0.593157E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521321E+09 |
April | 0.956342E+09 | 0.510985E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378280E+09 |
May | 0.103597E+10 | 0.534978E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836395.52 | 0.376319E+09 |
June | 0.103308E+10 | 0.522916E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4350451.51 | 0.190526E+09 |
July | 0.959235E+09 | 0.497599E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14034236.50 | 0.130737E+09 |
August | 0.107774E+10 | 0.558296E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12470253.70 | 0.142520E+09 |
September | 0.956342E+09 | 0.521470E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7023546.62 | 0.257347E+09 |
October | 0.994195E+09 | 0.563597E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41758.05 | 0.380353E+09 |
November | 0.984487E+09 | 0.601442E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514396E+09 |
December | 0.959235E+09 | 0.618412E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641646E+09 |
Annual Sum or Average | 0.119305E+11 | 0.668261E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38756641.90 | 0.481897E+10 |
Minimum of Months | 0.901968E+09 | 0.497599E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130737E+09 |
Maximum of Months | 0.107774E+10 | 0.638237E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14034236.50 | 0.709113E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.415566E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456433E+09 |
February | 0.570983E+09 | 0.335618E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364484E+09 |
March | 0.682256E+09 | 0.378182E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337429E+09 |
April | 0.605404E+09 | 0.324177E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250144E+09 |
May | 0.655811E+09 | 0.337737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541838.18 | 0.254486E+09 |
June | 0.653980E+09 | 0.328780E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2866870.58 | 0.129651E+09 |
July | 0.607235E+09 | 0.314214E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9300071.60 | 89965966.12 |
August | 0.682256E+09 | 0.352231E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8317775.04 | 95302523.55 |
September | 0.605404E+09 | 0.331179E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4881848.17 | 0.169391E+09 |
October | 0.629366E+09 | 0.363549E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33495.18 | 0.241922E+09 |
November | 0.623221E+09 | 0.388605E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328227E+09 |
December | 0.607235E+09 | 0.401803E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406994E+09 |
Annual Sum or Average | 0.755252E+10 | 0.427164E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25941898.76 | 0.312443E+10 |
Minimum of Months | 0.570983E+09 | 0.314214E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89965966.12 |
Maximum of Months | 0.682256E+09 | 0.415566E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9300071.60 | 0.456433E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929154E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747531E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686024E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499140E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811411.34 | 0.503168E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4447500.65 | 0.253811E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16793599.35 | 0.172706E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14486673.85 | 0.189066E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8972744.74 | 0.344652E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12707.16 | 0.503125E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690360E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855509E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45524637.09 | 0.637425E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172706E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16793599.35 | 0.929154E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114783E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.916002E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851491E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623963E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063350.67 | 0.633326E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5735271.13 | 0.324006E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21918326.95 | 0.219575E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18788852.02 | 0.239579E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11803485.37 | 0.430826E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29320.92 | 0.611055E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833118E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103537E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59338607.07 | 0.786615E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219575E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21918326.95 | 0.114783E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116974E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920746E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.866457E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637598E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643454.99 | 0.653999E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4794722.98 | 0.341232E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17392435.64 | 0.229339E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16677879.05 | 0.245809E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9022780.61 | 0.433847E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.605078E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818874E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103076E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48531273.27 | 0.795349E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229339E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17392435.64 | 0.116974E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1439.06 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 888.78 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 793.62 | 08-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1026.92 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 755.21 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 717.77 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 | 20-MAY-17:03 | 1361.67 | 22-MAY-04:03 |
June | 1306.65 | 01-JUN-09:09 | 532.07 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 29-JUN-15:00 | 580.80 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 560.07 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.14 | 30-JUL-12:00 | 345.67 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 572.32 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.22 | 06-AUG-17:36 | 423.01 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 769.87 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.24 | 03-SEP-12:51 | 762.20 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 15-OCT-14:00 | 638.02 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 803.49 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1103.84 | 01-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.67 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 201.24 | 1439.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 961.91 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 529.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 528.78 | 08-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 625.70 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 686.25 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 454.18 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 479.53 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 362.16 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.82 | 19-MAY-16:00 | 902.87 | 22-MAY-04:03 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 | 29-JUN-15:00 | 383.81 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 344.75 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 30-JUL-12:00 | 230.53 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 349.08 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.11 | 06-AUG-17:34 | 282.73 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 421.02 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 03-SEP-13:03 | 506.53 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 18-OCT-14:00 | 429.63 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 535.20 | 29-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 730.04 | 01-DEC-05:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 133.05 | 961.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1443.94 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 776.21 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 799.12 | 19-FEB-13:00 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1058.82 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 753.56 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 723.91 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 583.36 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.73 | 19-MAY-16:00 | 1365.95 | 22-MAY-04:03 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 | 29-JUN-15:00 | 579.51 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 561.62 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.38 | 30-JUL-13:50 | 349.12 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 573.39 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.34 | 06-AUG-17:34 | 429.88 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 748.12 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.82 | 03-SEP-13:04 | 765.55 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 18-OCT-14:10 | 672.81 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 803.75 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1093.73 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.12 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 191.82 | 1443.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 961.06 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 571.57 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 529.41 | 08-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 625.66 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 695.87 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 488.24 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 481.30 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 425.07 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.82 | 19-MAY-16:00 | 901.34 | 22-MAY-04:03 |
June | 827.17 | 01-JUN-09:09 | 341.47 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.86 | 29-JUN-15:00 | 388.66 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 359.10 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.12 | 30-JUL-12:00 | 238.14 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 367.83 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 | 06-AUG-17:34 | 288.55 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 527.33 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.54 | 03-SEP-13:03 | 504.58 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 | 18-OCT-14:00 | 433.24 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 535.12 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 729.15 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 341.47 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.14 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 141.54 | 961.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 769.13 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 880.64 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 435.63 | 17-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 986.98 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 554.26 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 744.29 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 386.07 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 579.58 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 | 20-MAY-17:03 | 787.62 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 528.45 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 29-JUN-15:00 | 321.76 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 556.22 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 30-JUL-12:00 | 190.76 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 569.04 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.45 | 06-AUG-18:00 | 241.44 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 759.06 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.65 | 03-SEP-12:51 | 450.01 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.74 | 15-OCT-14:00 | 369.23 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 429.81 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 648.44 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 528.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.76 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.65 | 787.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 512.63 | 05-JAN-22:01 |
February | 827.22 | 01-FEB-10:09 | 523.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 292.89 | 17-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 624.69 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 375.75 | 02-MAR-23:00 |
April | 827.22 | 03-APR-09:09 | 447.35 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 267.90 | 27-APR-02:00 |
May | 827.22 | 01-MAY-09:09 | 360.19 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 20-MAY-17:03 | 527.03 | 22-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 29-JUN-15:00 | 216.87 | 14-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 341.96 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 30-JUL-12:00 | 130.98 | 05-JUL-01:00 |
August | 827.22 | 01-AUG-09:09 | 346.52 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.39 | 06-AUG-17:36 | 166.25 | 23-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 368.55 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.19 | 03-SEP-12:51 | 301.21 | 12-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 18-OCT-14:00 | 253.26 | 30-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 288.55 | 26-NOV-20:00 |
December | 827.22 | 01-DEC-10:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 429.48 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.98 | |||||
Maximum of Months | 827.22 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.19 | 527.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 36916.15 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 756.17 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 36266.26 | 01-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 986.98 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 30465.71 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 742.56 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 19408.06 | 28-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 580.62 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2494.51 | 19-MAY-16:10 | 17416.34 | 08-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4898.79 | 28-JUN-16:10 | 13560.78 | 16-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 557.86 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8556.95 | 17-JUL-16:03 | 9561.21 | 05-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 570.17 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.23 | 10-AUG-17:00 | 11594.91 | 28-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 736.21 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2958.61 | 01-SEP-16:10 | 14006.21 | 19-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.80 | 18-OCT-15:00 | 20431.07 | 10-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 26732.20 | 27-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 35869.23 | 29-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9561.21 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8556.95 | 36916.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 512.56 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 568.53 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 295.57 | 17-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 624.65 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 384.66 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 483.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 267.32 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 370.18 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 20-MAY-17:03 | 528.21 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 338.77 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.14 | 29-JUN-15:00 | 219.20 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 357.08 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.83 | 30-JUL-12:00 | 133.96 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 366.20 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 | 06-AUG-17:34 | 166.65 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 523.36 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.64 | 03-SEP-12:51 | 301.63 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 18-OCT-14:00 | 255.37 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 288.82 | 26-NOV-20:00 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 433.16 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 338.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.96 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 74.64 | 528.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1204.39 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 888.78 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 686.33 | 17-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 891.52 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 755.18 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 631.26 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 582.38 | 03-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 20-MAY-17:03 | 1228.95 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 532.07 | 26-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.20 | 29-JUN-15:00 | 511.36 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 560.06 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.04 | 30-JUL-12:00 | 303.89 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 572.31 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.57 | 06-AUG-17:58 | 378.93 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 769.85 | 11-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 | 03-SEP-12:51 | 684.59 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 15-OCT-14:00 | 570.74 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 672.60 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 973.88 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 532.07 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.89 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 182.36 | 1228.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 658.76 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 802.69 | 05-JAN-22:01 |
February | 805.43 | 01-FEB-08:09 | 529.58 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 457.18 | 17-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 625.69 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 596.18 | 02-MAR-23:00 |
April | 805.43 | 03-APR-07:10 | 454.17 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 421.42 | 27-APR-02:00 |
May | 805.43 | 01-MAY-07:10 | 362.16 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 20-MAY-17:03 | 815.28 | 22-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 29-JUN-15:00 | 338.56 | 14-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 344.74 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 30-JUL-12:18 | 202.64 | 05-JUL-01:00 |
August | 805.43 | 01-AUG-07:10 | 349.07 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.24 | 06-AUG-17:56 | 252.80 | 23-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 421.00 | 13-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.16 | 03-SEP-12:51 | 455.22 | 12-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 658.76 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 18-OCT-14:30 | 383.69 | 30-OCT-22:00 |
November | 805.43 | 01-NOV-07:10 | 658.76 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 447.98 | 29-NOV-22:03 |
December | 805.43 | 01-DEC-08:09 | 658.76 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 644.34 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.64 | |||||
Maximum of Months | 805.43 | 658.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 112.16 | 815.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 1040.56 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1204.79 | 05-JAN-22:01 |
February | 1306.65 | 01-FEB-10:09 | 776.20 | 02-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 723.43 | 19-FEB-13:00 |
March | 1306.65 | 01-MAR-10:09 | 988.92 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 918.86 | 02-MAR-23:00 |
April | 1306.65 | 03-APR-09:09 | 753.53 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 635.63 | 27-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 583.36 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 | 20-MAY-17:03 | 1232.61 | 22-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.20 | 29-JUN-15:00 | 510.59 | 14-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 561.61 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 | 30-JUL-12:00 | 306.62 | 05-JUL-01:00 |
August | 1306.65 | 01-AUG-09:09 | 573.38 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.48 | 06-AUG-17:54 | 384.12 | 23-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 748.10 | 11-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.22 | 03-SEP-12:51 | 687.22 | 12-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 1040.56 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 | 18-OCT-14:50 | 596.75 | 30-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 1040.56 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 674.91 | 26-NOV-13:45 |
December | 1306.65 | 01-DEC-10:09 | 1040.56 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 990.43 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.62 | |||||
Maximum of Months | 1306.65 | 1040.56 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 168.22 | 1232.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 658.71 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 802.59 | 05-JAN-22:01 |
February | 827.17 | 01-FEB-10:09 | 571.56 | 02-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 460.32 | 17-FEB-04:00 |
March | 827.17 | 01-MAR-10:09 | 625.65 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 604.35 | 02-MAR-23:00 |
April | 827.17 | 03-APR-09:09 | 488.22 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 422.72 | 27-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 425.05 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.99 | 19-MAY-16:00 | 813.95 | 22-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 341.46 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 29-JUN-15:00 | 342.02 | 14-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 359.10 | 07-JUL-07:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.61 | 30-JUL-12:00 | 208.78 | 05-JUL-01:00 |
August | 827.17 | 01-AUG-09:09 | 367.82 | 17-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 06-AUG-17:54 | 254.55 | 23-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 527.32 | 11-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.16 | 03-SEP-12:51 | 453.45 | 12-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 658.71 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 18-OCT-14:00 | 386.56 | 30-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 658.71 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 448.00 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 658.71 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 647.68 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 341.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.78 | |||||
Maximum of Months | 827.17 | 658.71 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 115.16 | 813.95 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1528.26 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 991.77 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1233.22 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 870.71 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.16 | 20-MAY-17:03 | 1768.13 | 22-MAY-04:07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.16 | 29-JUN-15:00 | 702.60 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.33 | 30-JUL-12:00 | 415.55 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.18 | 06-AUG-18:00 | 530.65 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.37 | 03-SEP-13:00 | 966.01 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 18-OCT-14:05 | 804.79 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 933.93 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1436.26 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.55 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.37 | 1768.13 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1942.10 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1221.98 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1559.85 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1109.13 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 | 20-MAY-17:03 | 2192.76 | 22-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 29-JUN-15:00 | 893.61 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.05 | 30-JUL-12:00 | 522.24 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.21 | 06-AUG-17:40 | 668.90 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.81 | 03-SEP-13:00 | 1206.41 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 18-OCT-14:40 | 994.75 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1125.97 | 26-NOV-20:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1732.08 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.81 | 2192.76 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2110.27 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1153.16 | 08-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1592.47 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1094.53 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 20-MAY-17:03 | 2092.84 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.74 | 29-JUN-15:00 | 922.91 | 04-JUN-13:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.67 | 30-JUL-12:00 | 518.82 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.80 | 06-AUG-18:00 | 660.19 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.70 | 03-SEP-12:51 | 1160.14 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 984.72 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1136.76 | 29-NOV-22:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1575.40 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.70 | 2110.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9198.49 | 19-JAN-16:40 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16618.59 | 28-FEB-17:00 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18957.57 | 01-MAR-07:01 | 12705.28 | 16453.60 | 101948.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33098.86 | 27-APR-06:02 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38945.13 | 30-MAY-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38704.10 | 26-JUN-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39184.49 | 05-JUL-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38800.30 | 01-AUG-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39087.40 | 06-SEP-05:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35348.77 | 19-OCT-06:02 | 7623.17 | 9872.16 | 61169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35232.92 | 06-NOV-06:01 | 4446.85 | 1482.14 | 51872.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13269.63 | 07-DEC-16:10 | 6035.01 | 4936.01 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 9198.49 | 3176.32 | 1482.14 | 13991.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39184.49 | 12705.28 | 16453.60 | 101948.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 235.73 | 14-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.60 |
February | 1692.85 | 26-FEB-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.19 |
March | 2252.71 | 28-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 |
April | 5918.86 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
May | 8902.43 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 0.00 |
June | 10114.10 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.64 | 0.00 |
July | 12598.78 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11380.50 | 07-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 | 0.00 |
September | 8501.42 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
October | 5403.15 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
November | 1324.71 | 03-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12598.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 1021.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3566.64 | 26-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.87 |
February | 3662.04 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.22 |
March | 3323.32 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.55 |
April | 2316.86 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.47 |
May | 3120.98 | 19-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.38 | 0.00 |
June | 4562.68 | 26-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 |
July | 6057.50 | 17-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | 0.00 |
August | 6200.88 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 |
September | 6748.51 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 |
October | 2348.12 | 05-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.43 |
November | 2674.67 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.50 |
December | 3150.76 | 28-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2316.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6748.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.38 | 854.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3582.85 | 27-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.53 |
February | 3526.12 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.36 |
March | 3428.94 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.09 |
April | 3453.07 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.80 |
May | 3549.63 | 30-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.92 |
June | 4864.85 | 26-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 |
July | 6216.61 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 0.00 |
August | 5893.05 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 0.00 |
September | 6469.39 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 |
October | 2843.13 | 18-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
November | 2152.60 | 09-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.62 |
December | 3376.43 | 29-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2152.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6469.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 688.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7311.44 | 27-JAN-17:11 | 17152.13 | 24680.01 | 34041.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9310.35 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9270.93 | 01-MAR-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12543.18 | 25-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30166.89 | 30-MAY-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31043.98 | 26-JUN-06:03 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30903.35 | 31-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30647.97 | 08-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30292.55 | 06-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13240.53 | 18-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9923.38 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6107.58 | 29-DEC-16:50 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6107.58 | 3176.32 | 2742.16 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31043.98 | 17152.13 | 24680.01 | 34041.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7443.32 | 07-JAN-17:03 | 2223.42 | 1919.51 | 15886.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7550.53 | 28-FEB-17:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7840.70 | 29-MAR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13462.83 | 25-APR-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16643.24 | 30-MAY-15:30 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28425.22 | 26-JUN-06:02 | 7623.17 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31618.43 | 17-JUL-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32051.15 | 07-AUG-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32089.80 | 05-SEP-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13142.55 | 18-OCT-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7913.88 | 03-NOV-16:00 | 6035.01 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5284.77 | 07-DEC-16:25 | 12070.02 | 9872.03 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5284.77 | 2223.42 | 1919.51 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32089.80 | 12070.02 | 9872.16 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1432.88 | 07-JAN-17:03 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.94 |
February | 1188.70 | 04-FEB-17:03 | 468.72 | 328.46 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.07 |
March | 1245.71 | 29-MAR-15:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.32 |
April | 3535.41 | 07-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 |
May | 5267.30 | 19-MAY-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 44.73 | 0.00 |
June | 8850.32 | 21-JUN-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 |
July | 11298.88 | 16-JUL-18:31 | 0.00 | 193.02 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 52.14 | 0.00 |
August | 11074.70 | 06-AUG-16:11 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 157.39 | 0.00 |
September | 11185.66 | 03-SEP-15:01 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 146.15 | 0.00 |
October | 2810.26 | 19-OCT-14:40 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 |
November | 1103.96 | 08-NOV-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.64 |
December | 882.96 | 06-DEC-15:50 | 1272.23 | 703.52 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 882.96 | 0.00 | 193.02 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11298.88 | 1306.65 | 703.52 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 157.39 | 162.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 916.62 | 07-JAN-17:03 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.34 |
February | 2042.66 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.78 |
March | 4069.37 | 23-MAR-10:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 |
April | 6525.39 | 25-APR-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49 |
May | 7911.23 | 19-MAY-08:50 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 |
June | 13398.00 | 18-JUN-09:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.01 |
July | 14692.07 | 09-JUL-09:42 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.11 |
August | 14763.91 | 06-AUG-08:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 |
September | 14049.74 | 03-SEP-11:41 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 | 0.00 |
October | 4862.04 | 18-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
November | 1912.88 | 03-NOV-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.32 |
December | 611.17 | 06-DEC-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 611.17 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14763.91 | 827.22 | 314.23 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 43.45 | 137.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5273.06 | 19-JAN-13:40 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.20 |
February | 16399.17 | 26-FEB-14:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.20 |
March | 11422.24 | 01-MAR-13:55 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 |
April | 15285.52 | 16-APR-13:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.00 |
May | 10618.63 | 19-MAY-13:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 0.00 |
June | 16612.98 | 18-JUN-15:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
July | 18310.38 | 16-JUL-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 | 0.00 |
August | 18846.32 | 06-AUG-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 118.88 | 0.00 |
September | 21325.45 | 03-SEP-13:01 | 602.64 | 248.17 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 0.00 |
October | 18622.48 | 15-OCT-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.33 |
November | 11670.03 | 03-NOV-13:30 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 |
December | 5889.95 | 06-DEC-14:30 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5273.06 | 267.84 | 110.30 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21325.45 | 2613.31 | 992.69 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 118.88 | 239.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.33 | 27-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.72 |
February | 4410.89 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 |
March | 5602.80 | 28-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.93 |
April | 16221.48 | 16-APR-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.99 |
May | 15913.48 | 28-MAY-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.51 |
June | 16874.79 | 18-JUN-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 |
July | 17898.39 | 09-JUL-17:01 | 0.00 | 157.10 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
August | 16369.27 | 06-AUG-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 89.80 | 0.00 |
September | 16499.23 | 04-SEP-16:21 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 0.00 |
October | 11019.11 | 15-OCT-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.81 |
November | 3446.23 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 |
December | 1448.24 | 06-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 989.33 | 0.00 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17898.39 | 805.38 | 314.21 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 89.80 | 149.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1256.34 | 28-JAN-17:01 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 |
February | 1028.05 | 27-FEB-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 |
March | 1036.88 | 04-MAR-17:02 | 401.76 | 181.33 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.15 |
April | 1309.31 | 07-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
May | 3337.91 | 30-MAY-15:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4695.69 | 30-JUN-06:02 | 1607.03 | 992.70 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
July | 8521.45 | 16-JUL-18:21 | 0.00 | 275.74 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 0.00 |
August | 6755.58 | 07-AUG-06:03 | 1071.35 | 661.80 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
September | 6867.40 | 05-SEP-06:03 | 1071.35 | 1333.85 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 |
October | 2503.51 | 19-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
November | 1131.74 | 08-NOV-14:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 |
December | 891.87 | 06-DEC-16:00 | 1272.23 | 741.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 891.87 | 0.00 | 181.33 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8521.45 | 1607.03 | 1333.85 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 27.77 | 76.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 840.45 | 28-JAN-17:01 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 |
February | 1663.04 | 27-FEB-10:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
March | 2477.96 | 28-MAR-08:35 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.47 |
April | 4217.63 | 25-APR-09:30 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
May | 5741.91 | 19-MAY-06:03 | 678.26 | 418.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
June | 10737.70 | 25-JUN-08:41 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 |
July | 12486.03 | 16-JUL-09:41 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.79 |
August | 11545.44 | 06-AUG-09:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 | 0.00 |
September | 11319.07 | 04-SEP-08:51 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
October | 4152.14 | 18-OCT-09:40 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 |
November | 2132.47 | 03-NOV-09:20 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 |
December | 646.25 | 07-DEC-10:50 | 1654.44 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 646.25 | 254.35 | 104.74 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12486.03 | 1654.44 | 628.45 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10.65 | 49.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2400.06 | 14-JAN-12:30 | 137.54 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.72 |
February | 13589.49 | 26-FEB-14:42 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.85 |
March | 7970.96 | 01-MAR-13:06 | 11450.09 | 4467.10 | 12917.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1854.59 |
April | 7258.58 | 25-APR-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 861.02 |
May | 7567.42 | 19-MAY-14:00 | 1306.65 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 309.56 | 0.00 |
June | 10912.73 | 29-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4596.95 | 0.00 |
July | 14947.48 | 16-JUL-12:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 0.00 |
August | 14712.59 | 06-AUG-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 | 0.00 |
September | 15283.09 | 03-SEP-13:12 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 82.14 | 0.00 |
October | 14720.43 | 15-OCT-13:42 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.31 |
November | 9553.09 | 03-NOV-12:07 | 3816.70 | 1489.03 | 4305.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.16 |
December | 3582.39 | 02-DEC-13:30 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2400.06 | 133.92 | 82.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15283.09 | 11450.09 | 4467.10 | 12917.13 | 0.00 | 0.00 | 0.00 | 0.00 | 4596.95 | 1854.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 921.30 | 27-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
February | 3418.71 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 |
March | 3578.78 | 28-MAR-17:30 | 84.78 | 104.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 |
April | 6834.80 | 16-APR-17:32 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.97 |
May | 10662.40 | 28-MAY-18:02 | 0.00 | 87.28 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.66 |
June | 11008.91 | 24-JUN-17:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
July | 14244.32 | 16-JUL-18:21 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 0.00 |
August | 12552.30 | 06-AUG-16:11 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 | 0.00 |
September | 13093.48 | 04-SEP-16:51 | 423.88 | 174.55 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 |
October | 10467.57 | 15-OCT-16:23 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 |
November | 3108.01 | 03-NOV-15:50 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
December | 1124.30 | 06-DEC-15:30 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 921.30 | 0.00 | 69.82 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14244.32 | 805.38 | 314.21 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 | 80.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1253.17 | 28-JAN-17:01 | 468.72 | 404.65 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.88 |
February | 1345.16 | 27-FEB-13:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.52 |
March | 1454.35 | 29-MAR-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.43 |
April | 3499.12 | 07-APR-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 |
May | 4772.77 | 19-MAY-16:00 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 37.49 | 0.00 |
June | 7773.45 | 30-JUN-06:02 | 1607.03 | 992.70 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
July | 10550.05 | 16-JUL-18:22 | 0.00 | 275.74 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 43.77 | 0.00 |
August | 9169.89 | 06-AUG-16:31 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 135.55 | 0.00 |
September | 9594.05 | 04-SEP-12:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 95.77 | 0.00 |
October | 3087.94 | 19-OCT-14:30 | 1272.23 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 |
November | 1339.93 | 03-NOV-13:30 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.28 |
December | 944.92 | 06-DEC-16:00 | 1272.23 | 756.40 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 944.92 | 0.00 | 137.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10550.05 | 2613.31 | 992.70 | 3861.03 | 0.00 | 0.00 | 0.00 | 0.00 | 135.55 | 123.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 791.00 | 28-JAN-17:01 | 296.74 | 256.18 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 |
February | 4565.83 | 28-FEB-13:02 | 4832.57 | 1885.36 | 5451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.25 |
March | 6332.50 | 01-MAR-13:01 | 7248.86 | 2828.05 | 8177.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 |
April | 7409.59 | 25-APR-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
May | 8095.90 | 19-MAY-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
June | 13949.23 | 11-JUN-08:32 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.03 |
July | 15914.37 | 02-JUL-09:01 | 339.13 | 139.65 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 |
August | 14594.75 | 06-AUG-09:12 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 | 0.00 |
September | 13481.30 | 04-SEP-11:22 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.52 | 0.00 |
October | 6265.90 | 18-OCT-10:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
November | 5696.63 | 02-NOV-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
December | 701.13 | 07-DEC-11:10 | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 701.13 | 211.95 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15914.37 | 7248.86 | 2828.05 | 8177.16 | 0.00 | 0.00 | 0.00 | 0.00 | 43.52 | 72.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6335.84 | 19-JAN-13:30 | 1272.23 | 496.34 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.18 |
February | 16825.34 | 26-FEB-13:32 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.30 |
March | 12204.03 | 01-MAR-13:35 | 2544.47 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.40 |
April | 15993.48 | 16-APR-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.27 |
May | 10167.27 | 14-MAY-12:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.94 |
June | 13462.19 | 11-JUN-13:13 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 |
July | 17593.80 | 16-JUL-12:22 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 0.00 |
August | 16982.52 | 06-AUG-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 102.20 | 0.00 |
September | 17968.60 | 03-SEP-12:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 | 0.00 |
October | 19042.69 | 15-OCT-13:31 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.45 |
November | 12272.31 | 03-NOV-13:10 | 2613.31 | 992.69 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 |
December | 6918.47 | 12-DEC-12:30 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6335.84 | 200.88 | 82.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19042.69 | 2613.31 | 992.69 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 107.75 | 367.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 956.33 | 27-JAN-16:35 | 1610.75 | 628.41 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 |
February | 4699.00 | 28-FEB-16:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 |
March | 5673.21 | 28-MAR-16:00 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 |
April | 11093.71 | 16-APR-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.06 |
May | 14785.20 | 28-MAY-17:02 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.64 |
June | 14638.49 | 24-JUN-17:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 |
July | 17101.37 | 16-JUL-17:01 | 0.00 | 174.55 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 0.00 |
August | 15010.63 | 06-AUG-16:31 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
September | 15149.08 | 04-SEP-16:41 | 339.11 | 139.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 | 0.00 |
October | 7888.20 | 15-OCT-15:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 |
November | 3806.15 | 03-NOV-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.86 |
December | 1728.56 | 06-DEC-15:40 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 956.33 | 0.00 | 87.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17101.37 | 1610.75 | 628.41 | 2444.18 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 125.64 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.101039E+12 | 86628.39 | 09-JAN-08:09 | 0.193612E+12 | 312287.93 | 09-JAN-07:19 |
February | 0.895329E+11 | 82297.96 | 27-FEB-15:30 | 0.104560E+12 | 276098.23 | 01-FEB-07:19 |
March | 0.101670E+12 | 80672.70 | 28-MAR-15:50 | 0.684052E+11 | 277427.53 | 06-MAR-07:19 |
April | 0.949216E+11 | 99550.69 | 06-APR-15:00 | 0.230455E+11 | 124611.72 | 29-APR-06:10 |
May | 0.104672E+12 | 129260.95 | 19-MAY-15:20 | 0.142012E+11 | 139499.07 | 08-MAY-06:10 |
June | 0.121996E+12 | 145585.38 | 29-JUN-15:09 | 0.120001E+10 | 45207.46 | 16-JUN-06:10 |
July | 0.138155E+12 | 173928.84 | 17-JUL-15:39 | 61943224.10 | 20177.25 | 05-JUL-06:19 |
August | 0.137498E+12 | 159055.29 | 07-AUG-15:39 | 0.482844E+09 | 37388.12 | 18-AUG-06:10 |
September | 0.110175E+12 | 154732.57 | 07-SEP-14:00 | 0.405375E+10 | 72347.72 | 19-SEP-06:10 |
October | 0.101248E+12 | 111939.54 | 18-OCT-15:00 | 0.152537E+11 | 160986.09 | 10-OCT-06:10 |
November | 0.967821E+11 | 85453.97 | 07-NOV-16:00 | 0.536484E+11 | 255712.23 | 27-NOV-07:19 |
December | 0.983991E+11 | 84406.28 | 29-DEC-08:09 | 0.131142E+12 | 289830.67 | 29-DEC-07:19 |
Annual Sum or Average | 0.129609E+13 | 0.609665E+12 | ||||
Minimum of Months | 0.895329E+11 | 80672.70 | 61943224.10 | 20177.25 | ||
Maximum of Months | 0.138155E+12 | 173928.84 | 0.193612E+12 | 312287.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.203139E+11 | 0.626771E+10 | 0.605851E+11 | 0.225731E+10 | 0.526078E+10 | 0.947024E+09 | 0.00 | 233456.15 | 0.00 | 0.00 | 0.00 | 0.540706E+10 | 0.00 |
February | 0.178121E+11 | 0.491554E+10 | 0.548702E+11 | 0.204820E+10 | 0.410573E+10 | 0.545111E+09 | 0.00 | 0.247503E+09 | 0.00 | 0.00 | 0.00 | 0.498852E+10 | 0.00 |
March | 0.208531E+11 | 0.447730E+10 | 0.627783E+11 | 0.235486E+10 | 0.472261E+10 | 0.360979E+09 | 0.00 | 0.296533E+09 | 0.00 | 0.00 | 0.00 | 0.582642E+10 | 0.00 |
April | 0.183937E+11 | 0.347008E+10 | 0.586172E+11 | 0.219169E+10 | 0.501893E+10 | 0.123194E+09 | 0.00 | 0.203095E+10 | 0.00 | 0.00 | 0.00 | 0.507575E+10 | 0.00 |
May | 0.196916E+11 | 0.289027E+10 | 0.616817E+11 | 0.230553E+10 | 0.700772E+10 | 86905601.25 | 0.00 | 0.585364E+10 | 0.00 | 0.00 | 0.00 | 0.515426E+10 | 0.00 |
June | 0.195061E+11 | 0.253198E+10 | 0.604966E+11 | 0.226771E+10 | 0.134271E+11 | 19943474.11 | 0.00 | 0.189298E+11 | 0.00 | 0.00 | 0.00 | 0.481700E+10 | 0.00 |
July | 0.183183E+11 | 0.272636E+10 | 0.597911E+11 | 0.222857E+10 | 0.176105E+11 | 12663221.73 | 0.00 | 0.331252E+11 | 0.00 | 0.00 | 0.00 | 0.434254E+10 | 0.00 |
August | 0.204689E+11 | 0.326860E+10 | 0.627783E+11 | 0.235447E+10 | 0.163634E+11 | 16169976.32 | 0.00 | 0.275694E+11 | 0.00 | 0.00 | 0.00 | 0.467852E+10 | 0.00 |
September | 0.185086E+11 | 0.391803E+10 | 0.585950E+11 | 0.219057E+10 | 0.965464E+10 | 34395969.06 | 0.00 | 0.129916E+11 | 0.00 | 0.00 | 0.00 | 0.428181E+10 | 0.00 |
October | 0.195068E+11 | 0.500538E+10 | 0.605962E+11 | 0.225783E+10 | 0.584504E+10 | 88467651.71 | 0.00 | 0.333334E+10 | 0.00 | 0.00 | 0.00 | 0.461513E+10 | 0.00 |
November | 0.197818E+11 | 0.579766E+10 | 0.591197E+11 | 0.220000E+10 | 0.434497E+10 | 0.287566E+09 | 0.00 | 0.444776E+09 | 0.00 | 0.00 | 0.00 | 0.480566E+10 | 0.00 |
December | 0.196735E+11 | 0.653724E+10 | 0.597800E+11 | 0.222859E+10 | 0.445779E+10 | 0.676622E+09 | 0.00 | 630448.12 | 0.00 | 0.00 | 0.00 | 0.504472E+10 | 0.00 |
Annual Sum or Average | 0.232828E+12 | 0.518061E+11 | 0.719689E+12 | 0.268853E+11 | 0.978191E+11 | 0.319904E+10 | 0.00 | 0.104824E+12 | 0.00 | 0.00 | 0.00 | 0.590374E+11 | 0.00 |
Minimum of Months | 0.178121E+11 | 0.253198E+10 | 0.548702E+11 | 0.204820E+10 | 0.410573E+10 | 12663221.73 | 0.00 | 233456.15 | 0.00 | 0.00 | 0.00 | 0.428181E+10 | 0.00 |
Maximum of Months | 0.208531E+11 | 0.653724E+10 | 0.627783E+11 | 0.235486E+10 | 0.176105E+11 | 0.947024E+09 | 0.00 | 0.331252E+11 | 0.00 | 0.00 | 0.00 | 0.582642E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.193612E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.104560E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.684052E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.230455E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.142012E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.120001E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 61943224.10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.482844E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.405375E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152537E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.536484E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.131142E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.609665E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 61943224.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.193612E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 25003.79 | 02-JAN-08:09 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 02-JAN-12:09 | 8528.58 | 09-JAN-07:10 | 1020.53 | 09-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 22756.81 | 02-FEB-08:09 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 03-FEB-12:20 | 8039.82 | 06-FEB-07:10 | 948.45 | 04-FEB-07:19 | 0.00 | 01-FEB-00:10 |
March | 24489.72 | 17-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-12:09 | 7595.50 | 06-MAR-07:10 | 946.94 | 06-MAR-07:40 | 0.00 | 01-MAR-00:10 |
April | 22127.58 | 14-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 03-APR-11:09 | 14217.57 | 25-APR-15:50 | 637.85 | 29-APR-06:19 | 0.00 | 01-APR-00:10 |
May | 20604.53 | 03-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 03-MAY-11:09 | 22586.07 | 19-MAY-15:30 | 714.82 | 08-MAY-06:10 | 0.00 | 01-MAY-00:10 |
June | 19774.97 | 26-JUN-11:30 | 3328.83 | 01-JUN-20:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-11:09 | 28337.20 | 29-JUN-14:30 | 245.93 | 16-JUN-06:30 | 0.00 | 01-JUN-00:10 |
July | 20272.22 | 07-JUL-07:30 | 3328.83 | 01-JUL-20:30 | 41699.26 | 03-JUL-07:10 | 1410.29 | 05-JUL-07:19 | 33893.32 | 25-JUL-15:50 | 121.36 | 05-JUL-06:19 | 0.00 | 01-JUL-00:10 |
August | 20385.19 | 17-AUG-07:10 | 5686.19 | 03-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 30-AUG-07:10 | 31896.59 | 07-AUG-15:39 | 187.41 | 18-AUG-06:10 | 0.00 | 01-AUG-00:10 |
September | 21941.55 | 11-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 11-SEP-11:09 | 29267.27 | 07-SEP-14:00 | 386.25 | 19-SEP-06:10 | 0.00 | 01-SEP-00:10 |
October | 25003.79 | 30-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 03-OCT-11:09 | 16157.59 | 18-OCT-15:00 | 763.27 | 10-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 25003.79 | 01-NOV-07:10 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-11:09 | 7964.41 | 03-NOV-15:20 | 890.65 | 27-NOV-07:30 | 0.00 | 01-NOV-00:10 |
December | 25003.79 | 01-DEC-16:40 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 06-DEC-08:09 | 7568.57 | 26-DEC-07:19 | 953.68 | 29-DEC-07:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19774.97 | 3328.83 | 41699.26 | 1410.29 | 7568.57 | 121.36 | 0.00 | |||||||
Maximum of Months | 25003.79 | 5686.19 | 41699.26 | 1410.29 | 33893.32 | 1020.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 120.79 | 10-JAN-06:40 | 0.00 | 0.00 | 0.00 | 7216.14 | 31-JAN-12:30 | 0.00 |
February | 8500.58 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 7227.29 | 17-FEB-12:39 | 0.00 |
March | 5901.98 | 28-MAR-15:39 | 0.00 | 0.00 | 0.00 | 7222.99 | 01-MAR-12:20 | 0.00 |
April | 19327.32 | 06-APR-15:00 | 0.00 | 0.00 | 0.00 | 7160.66 | 03-APR-11:50 | 0.00 |
May | 38959.17 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 | 6727.59 | 01-MAY-11:30 | 0.00 |
June | 51060.46 | 29-JUN-14:00 | 0.00 | 0.00 | 0.00 | 6279.50 | 01-JUN-11:00 | 0.00 |
July | 73892.65 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 6052.92 | 06-JUL-11:00 | 0.00 |
August | 60261.28 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 | 5803.88 | 01-AUG-11:50 | 0.00 |
September | 59219.55 | 07-SEP-14:00 | 0.00 | 0.00 | 0.00 | 5851.67 | 29-SEP-11:20 | 0.00 |
October | 28962.46 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 | 6252.69 | 31-OCT-11:39 | 0.00 |
November | 6063.05 | 03-NOV-14:09 | 0.00 | 0.00 | 0.00 | 6694.53 | 30-NOV-12:00 | 0.00 |
December | 320.73 | 07-DEC-15:50 | 0.00 | 0.00 | 0.00 | 7134.69 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 120.79 | 0.00 | 0.00 | 0.00 | 5803.88 | 0.00 | ||
Maximum of Months | 73892.65 | 0.00 | 0.00 | 0.00 | 7227.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 86628.39 | 09-JAN-08:09 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 7595.50 | 993.60 | 0.00 | 0.00 | 0.00 |
February | 82297.96 | 27-FEB-15:30 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 6935.43 | 6.85 | 0.00 | 8500.58 | 0.00 |
March | 80672.70 | 28-MAR-15:50 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 6407.85 | 6.85 | 0.00 | 5890.96 | 0.00 |
April | 99550.69 | 06-APR-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 12054.81 | 6.85 | 0.00 | 19327.32 | 0.00 |
May | 129260.95 | 19-MAY-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 22533.77 | 6.85 | 0.00 | 38959.17 | 0.00 |
June | 145585.38 | 29-JUN-15:09 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 27765.52 | 6.85 | 0.00 | 50459.56 | 0.00 |
July | 173928.84 | 17-JUL-15:39 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 33211.03 | 6.85 | 0.00 | 73453.22 | 0.00 |
August | 159055.29 | 07-AUG-15:39 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 31896.59 | 6.85 | 0.00 | 59964.56 | 0.00 |
September | 154732.57 | 07-SEP-14:00 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 29267.27 | 6.87 | 0.00 | 59219.55 | 0.00 |
October | 111939.54 | 18-OCT-15:00 | 19905.30 | 41670.51 | 0.00 | 1410.29 | 16157.59 | 6.85 | 0.00 | 28025.93 | 0.00 |
November | 85453.97 | 07-NOV-16:00 | 25003.79 | 41670.51 | 5686.19 | 1410.29 | 3563.29 | 6.85 | 0.00 | 3256.45 | 0.00 |
December | 84406.28 | 29-DEC-08:09 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 5595.71 | 878.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 80672.70 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 3563.29 | 6.85 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 173928.84 | 25003.79 | 41699.26 | 5686.19 | 1410.29 | 33211.03 | 993.60 | 0.00 | 73453.22 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 312287.93 | 09-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 276098.23 | 01-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 277427.53 | 06-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 124611.72 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 139499.07 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 45207.46 | 16-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 20177.25 | 05-JUL-06:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 37388.12 | 18-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 72347.72 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 160986.09 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 255712.23 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 289830.67 | 29-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 20177.25 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 312287.93 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.51 | 2.67 | 19.60 | 0.00 | 19.60 | 0.00 | 19.60 |
February | 0.33 | 19.68 | 0.33 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
March | 0.17 | 19.28 | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.23 | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 3.50 | 19.50 | 3.33 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.68 | 2.67 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 19.01 | 7.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 2.17 | 19.13 | 1.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 1.67 | 19.13 | 1.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 19.22 | 1.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 2.33 | 19.07 | 2.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Annual Sum or Average | 16.17 | 19.06 | 14.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 19.22 | 7.83 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 93.83 | 17.51 | 63.17 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
February | 27.50 | 17.31 | 16.67 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
March | 11.83 | 16.44 | 5.50 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.46 | 1.67 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.55 | 1.33 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.51 | 2.50 | 27.52 |
October | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
November | 9.83 | 16.64 | 4.83 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 42.00 | 16.62 | 21.50 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
Annual Sum or Average | 185.33 | 17.16 | 111.67 | 17.70 | 8.00 | 17.96 | 5.50 | 18.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.83 | 17.51 | 63.17 | 18.03 | 3.17 | 27.55 | 2.50 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.00 | 16.50 | 26.50 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 14.83 | 15.76 | 4.17 | 16.22 | 0.00 | 16.22 | 0.00 | 16.22 |
March | 7.67 | 15.32 | 1.83 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.80 | 7.33 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.97 | 12.67 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.21 | 3.67 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.93 | 5.50 | 27.96 |
October | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
November | 6.00 | 15.86 | 1.50 | 16.30 | 0.00 | 16.30 | 0.00 | 16.30 |
December | 29.00 | 15.78 | 9.50 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
Annual Sum or Average | 109.83 | 16.09 | 43.50 | 16.64 | 32.83 | 18.64 | 29.17 | 19.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.00 | 17.09 | 26.50 | 17.12 | 14.50 | 28.21 | 12.67 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.00 | 16.79 | 23.67 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
February | 11.83 | 16.08 | 3.17 | 16.61 | 1.17 | 17.43 | 1.17 | 18.14 |
March | 7.83 | 15.81 | 2.50 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
May | 0.17 | 17.16 | 0.00 | 17.16 | 1.33 | 26.39 | 1.33 | 26.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.65 | 4.17 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.88 | 8.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.02 | 4.33 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.16 | 7.00 | 28.20 |
October | 0.17 | 17.10 | 0.00 | 17.10 | 2.50 | 27.39 | 2.50 | 27.72 |
November | 5.17 | 16.29 | 1.33 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
December | 22.33 | 16.17 | 9.00 | 16.63 | 0.00 | 16.63 | 0.00 | 16.63 |
Annual Sum or Average | 93.50 | 16.44 | 39.67 | 17.05 | 34.17 | 19.27 | 29.50 | 20.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 | 0.00 | 16.29 |
Maximum of Months | 46.00 | 17.16 | 23.67 | 17.46 | 10.17 | 28.16 | 8.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.67 | 16.77 | 29.33 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
February | 14.00 | 15.61 | 4.00 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
March | 8.17 | 15.57 | 2.67 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.09 | 0.67 | 28.15 |
May | 0.17 | 17.08 | 0.00 | 17.08 | 4.50 | 27.66 | 2.00 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.14 | 2.83 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.43 | 6.00 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.17 | 3.33 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.26 | 3.50 | 28.32 |
October | 0.17 | 16.99 | 0.00 | 16.99 | 0.50 | 25.14 | 0.50 | 26.30 |
November | 6.50 | 15.57 | 1.83 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
December | 29.50 | 15.71 | 10.33 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
Annual Sum or Average | 113.17 | 16.20 | 48.17 | 16.75 | 35.83 | 18.84 | 18.83 | 19.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 0.00 | 15.81 |
Maximum of Months | 54.67 | 17.08 | 29.33 | 17.43 | 12.00 | 28.43 | 6.00 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.00 | 18.53 | 58.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 7.83 | 19.33 | 6.83 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
March | 4.00 | 18.72 | 3.33 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.03 | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 10.17 | 18.31 | 7.83 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
Annual Sum or Average | 94.67 | 18.58 | 77.17 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.00 | 19.33 | 58.67 | 19.50 | 0.00 | 19.50 | 0.00 | 19.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.00 | 18.31 | 31.67 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
February | 1.83 | 18.06 | 0.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
March | 1.00 | 17.54 | 0.50 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.58 | 4.17 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.74 | 10.00 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.87 | 3.17 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.67 | 5.67 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
December | 5.67 | 16.95 | 3.17 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
Annual Sum or Average | 51.67 | 18.14 | 36.00 | 18.64 | 24.33 | 20.61 | 23.00 | 21.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.00 | 18.31 | 31.67 | 18.80 | 10.50 | 27.87 | 10.00 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 140.67 | 16.65 | 133.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
February | 66.50 | 17.44 | 65.83 | 17.44 | 1.33 | 17.54 | 1.33 | 17.64 |
March | 50.17 | 18.05 | 50.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
April | 28.83 | 18.82 | 28.83 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
May | 21.33 | 18.86 | 21.33 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
June | 1.17 | 19.52 | 1.17 | 19.52 | 0.50 | 20.89 | 0.50 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.80 | 8.00 | 26.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.41 | 6.50 | 26.37 |
September | 5.00 | 19.86 | 5.00 | 19.86 | 8.50 | 23.56 | 6.83 | 24.75 |
October | 12.67 | 19.09 | 12.67 | 19.09 | 3.33 | 20.11 | 3.33 | 20.91 |
November | 33.83 | 18.03 | 33.83 | 18.03 | 1.17 | 18.19 | 1.17 | 18.34 |
December | 83.83 | 17.38 | 81.83 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
Annual Sum or Average | 444.00 | 17.53 | 433.50 | 17.55 | 30.33 | 17.88 | 27.67 | 18.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.69 | 0.00 | 16.69 |
Maximum of Months | 140.67 | 19.86 | 133.00 | 19.86 | 8.50 | 26.80 | 8.00 | 26.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.50 | 18.36 | 32.67 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
February | 1.33 | 17.99 | 0.50 | 18.54 | 0.00 | 18.54 | 0.00 | 18.54 |
March | 2.00 | 18.41 | 1.33 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.17 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.74 | 1.17 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.76 | 1.67 | 27.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.05 | 4.67 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.89 | 2.17 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.92 | 2.83 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.69 | 0.50 | 27.69 |
November | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
December | 5.83 | 16.89 | 3.33 | 17.31 | 0.00 | 17.31 | 0.00 | 17.31 |
Annual Sum or Average | 52.83 | 18.19 | 37.83 | 18.67 | 25.17 | 20.68 | 13.17 | 21.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 0.00 | 17.07 |
Maximum of Months | 43.50 | 18.41 | 32.67 | 19.03 | 8.67 | 28.05 | 4.67 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.17 | 17.96 | 39.33 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
February | 6.50 | 18.18 | 4.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
March | 3.67 | 18.09 | 2.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 0.67 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.35 | 0.67 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.41 | 1.33 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 18.67 | 1.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 13.83 | 17.56 | 9.50 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
Annual Sum or Average | 81.50 | 17.94 | 57.00 | 18.40 | 3.83 | 18.64 | 2.67 | 18.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.17 | 18.67 | 39.33 | 19.08 | 1.50 | 27.41 | 1.33 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.33 | 16.95 | 14.67 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
February | 2.50 | 15.74 | 0.50 | 15.61 | 0.00 | 15.61 | 0.00 | 15.61 |
March | 1.33 | 16.22 | 0.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.90 | 6.67 | 27.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.98 | 11.83 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.03 | 4.17 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.84 | 6.33 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
November | 0.83 | 16.78 | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
December | 7.50 | 16.14 | 3.50 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
Annual Sum or Average | 41.50 | 16.70 | 19.17 | 17.28 | 32.33 | 20.98 | 30.17 | 22.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 | 0.00 | 15.61 |
Maximum of Months | 29.33 | 16.95 | 14.67 | 17.62 | 12.67 | 28.03 | 11.83 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.50 | 17.43 | 14.17 | 18.04 | 0.33 | 18.12 | 0.33 | 18.19 |
February | 0.83 | 17.44 | 0.17 | 17.77 | 1.67 | 24.18 | 1.67 | 25.66 |
March | 1.50 | 17.31 | 0.67 | 18.02 | 0.50 | 19.80 | 0.50 | 21.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.62 | 1.33 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.50 | 1.67 | 27.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.56 | 3.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.76 | 8.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.95 | 4.00 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.10 | 7.00 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.12 | 3.17 | 28.12 |
November | 0.50 | 17.32 | 0.17 | 17.74 | 1.50 | 24.53 | 1.50 | 25.76 |
December | 6.67 | 16.48 | 3.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Annual Sum or Average | 34.00 | 17.24 | 18.17 | 17.82 | 35.83 | 21.91 | 33.00 | 23.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 0.00 | 16.93 |
Maximum of Months | 24.50 | 17.44 | 14.17 | 18.04 | 9.00 | 28.12 | 8.00 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.67 | 17.11 | 16.67 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
February | 2.33 | 15.82 | 0.83 | 15.61 | 0.17 | 16.19 | 0.17 | 16.72 |
March | 1.67 | 17.04 | 0.67 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.06 | 0.67 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.02 | 1.83 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.06 | 2.50 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.32 | 5.67 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.09 | 3.00 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.08 | 3.50 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.67 | 27.80 |
November | 0.83 | 16.78 | 0.17 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
December | 8.00 | 16.11 | 3.83 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
Annual Sum or Average | 43.50 | 16.85 | 22.17 | 17.38 | 34.17 | 21.06 | 18.00 | 22.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.19 | 0.00 | 16.40 |
Maximum of Months | 30.67 | 17.11 | 16.67 | 17.80 | 11.17 | 28.32 | 5.67 | 28.34 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.59 | 100.50 | 22.34 | 100.50 | 22.17 |
February | 449.17 | 23.32 | 15.50 | 23.25 | 15.50 | 23.18 |
March | 489.00 | 23.85 | 2.00 | 23.84 | 2.00 | 23.83 |
April | 303.33 | 24.06 | 9.17 | 24.11 | 0.00 | 24.11 |
May | 168.33 | 24.01 | 84.50 | 24.63 | 0.00 | 24.63 |
June | 0.00 | 0.00 | 238.83 | 24.79 | 0.00 | 24.79 |
July | 1.00 | 27.06 | 368.83 | 24.71 | 1.00 | 24.71 |
August | 0.00 | 0.00 | 253.50 | 24.92 | 0.00 | 24.92 |
September | 15.50 | 24.00 | 201.67 | 24.92 | 0.00 | 24.92 |
October | 123.67 | 24.01 | 52.17 | 24.58 | 0.00 | 24.58 |
November | 374.67 | 23.96 | 7.67 | 23.99 | 0.00 | 23.99 |
December | 497.00 | 23.34 | 25.33 | 23.22 | 25.33 | 23.11 |
Annual Sum or Average | 2923.67 | 23.52 | 1359.67 | 23.85 | 144.33 | 23.76 |
Minimum of Months | 0.00 | 0.00 | 2.00 | 22.34 | 0.00 | 22.17 |
Maximum of Months | 502.00 | 27.06 | 368.83 | 24.92 | 100.50 | 24.92 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.04 | 313.83 | 20.87 | 313.83 | 20.80 |
February | 454.00 | 21.86 | 128.67 | 21.60 | 128.67 | 21.43 |
March | 514.00 | 22.70 | 50.33 | 22.51 | 50.33 | 22.35 |
April | 460.83 | 23.44 | 0.00 | 23.44 | 0.00 | 23.44 |
May | 326.67 | 23.58 | 49.33 | 23.80 | 1.33 | 23.79 |
June | 69.50 | 23.82 | 155.83 | 24.25 | 0.00 | 24.25 |
July | 16.83 | 23.99 | 286.50 | 24.50 | 0.00 | 24.50 |
August | 19.67 | 23.87 | 158.17 | 24.63 | 0.00 | 24.63 |
September | 156.00 | 23.79 | 134.50 | 24.21 | 1.67 | 24.21 |
October | 421.50 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
November | 489.00 | 22.76 | 46.33 | 22.61 | 46.33 | 22.47 |
December | 497.00 | 21.54 | 195.00 | 21.25 | 195.00 | 21.09 |
Annual Sum or Average | 3927.00 | 22.58 | 1518.50 | 22.61 | 737.17 | 22.37 |
Minimum of Months | 16.83 | 21.04 | 0.00 | 20.87 | 0.00 | 20.80 |
Maximum of Months | 514.00 | 23.99 | 313.83 | 24.63 | 313.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.41 | 439.00 | 20.34 | 439.00 | 20.32 |
February | 454.00 | 21.09 | 284.83 | 20.86 | 284.83 | 20.76 |
March | 514.00 | 21.81 | 153.50 | 21.49 | 153.50 | 21.28 |
April | 468.33 | 22.79 | 40.83 | 22.62 | 40.83 | 22.48 |
May | 348.67 | 23.14 | 45.83 | 23.16 | 19.00 | 23.05 |
June | 121.67 | 23.64 | 145.00 | 24.04 | 0.00 | 24.04 |
July | 35.33 | 23.76 | 259.50 | 24.37 | 0.00 | 24.37 |
August | 72.33 | 23.71 | 145.83 | 24.30 | 0.00 | 24.30 |
September | 232.50 | 23.34 | 113.83 | 23.76 | 3.67 | 23.77 |
October | 481.83 | 22.89 | 21.33 | 22.79 | 21.33 | 22.70 |
November | 489.00 | 21.70 | 187.00 | 21.37 | 187.00 | 21.19 |
December | 497.00 | 20.65 | 362.67 | 20.46 | 362.67 | 20.39 |
Annual Sum or Average | 4216.67 | 21.94 | 2199.17 | 21.85 | 1511.83 | 21.57 |
Minimum of Months | 35.33 | 20.41 | 21.33 | 20.34 | 0.00 | 20.32 |
Maximum of Months | 514.00 | 23.76 | 439.00 | 24.37 | 439.00 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.70 | 495.83 | 19.69 | 495.83 | 19.69 |
February | 454.00 | 20.29 | 410.83 | 20.22 | 410.83 | 20.19 |
March | 514.00 | 20.81 | 326.50 | 20.57 | 326.50 | 20.47 |
April | 473.50 | 21.85 | 136.50 | 21.50 | 136.50 | 21.28 |
May | 370.50 | 22.46 | 96.33 | 22.34 | 63.00 | 22.10 |
June | 142.67 | 23.24 | 178.67 | 23.87 | 0.50 | 23.86 |
July | 57.67 | 23.83 | 288.83 | 24.39 | 5.17 | 24.42 |
August | 133.00 | 23.40 | 164.67 | 24.00 | 3.33 | 24.03 |
September | 292.33 | 22.63 | 122.50 | 23.05 | 28.67 | 22.99 |
October | 496.17 | 21.84 | 122.67 | 21.54 | 122.67 | 21.34 |
November | 489.00 | 20.58 | 331.67 | 20.36 | 331.67 | 20.27 |
December | 497.00 | 19.89 | 474.83 | 19.86 | 474.83 | 19.85 |
Annual Sum or Average | 4421.83 | 21.18 | 3149.83 | 21.15 | 2399.50 | 20.88 |
Minimum of Months | 57.67 | 19.70 | 96.33 | 19.69 | 0.50 | 19.69 |
Maximum of Months | 514.00 | 23.83 | 495.83 | 24.39 | 495.83 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 477.33 | 19.89 | 477.33 | 19.88 |
February | 454.00 | 20.75 | 330.00 | 20.50 | 330.00 | 20.40 |
March | 502.83 | 21.35 | 242.83 | 20.96 | 242.83 | 20.76 |
April | 370.00 | 22.02 | 116.00 | 21.80 | 93.33 | 21.54 |
May | 271.00 | 22.49 | 133.33 | 22.69 | 46.67 | 22.42 |
June | 110.67 | 24.00 | 276.17 | 24.40 | 21.17 | 24.54 |
July | 63.33 | 25.70 | 391.50 | 24.76 | 38.33 | 24.95 |
August | 83.83 | 23.83 | 305.67 | 24.34 | 12.83 | 24.43 |
September | 217.67 | 23.06 | 186.17 | 23.72 | 35.17 | 23.80 |
October | 429.00 | 22.23 | 83.67 | 21.93 | 80.33 | 21.70 |
November | 487.50 | 21.00 | 283.83 | 20.68 | 283.83 | 20.54 |
December | 497.00 | 20.04 | 449.83 | 19.97 | 449.83 | 19.94 |
Annual Sum or Average | 3988.83 | 21.42 | 3276.33 | 21.58 | 2111.67 | 21.30 |
Minimum of Months | 63.33 | 19.92 | 83.67 | 19.89 | 12.83 | 19.88 |
Maximum of Months | 502.83 | 25.70 | 477.33 | 24.76 | 477.33 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.17 | 20.54 | 389.67 | 20.29 | 387.33 | 20.18 |
February | 401.83 | 21.19 | 264.17 | 20.92 | 247.50 | 20.73 |
March | 428.50 | 21.30 | 251.00 | 21.10 | 219.67 | 20.88 |
April | 361.67 | 21.93 | 154.50 | 21.88 | 107.33 | 21.62 |
May | 297.33 | 22.37 | 147.33 | 22.57 | 60.00 | 22.31 |
June | 157.17 | 23.41 | 213.67 | 24.03 | 14.50 | 24.12 |
July | 85.00 | 24.55 | 326.67 | 24.56 | 28.50 | 24.72 |
August | 121.67 | 23.70 | 275.83 | 24.24 | 14.17 | 24.34 |
September | 206.00 | 23.01 | 218.00 | 23.77 | 34.83 | 23.84 |
October | 340.00 | 22.23 | 156.50 | 22.37 | 77.00 | 22.16 |
November | 413.67 | 21.41 | 229.50 | 21.16 | 203.17 | 20.93 |
December | 469.67 | 20.60 | 342.00 | 20.30 | 342.00 | 20.18 |
Annual Sum or Average | 3771.67 | 21.68 | 2968.83 | 21.86 | 1736.00 | 21.57 |
Minimum of Months | 85.00 | 20.54 | 147.33 | 20.29 | 14.17 | 20.18 |
Maximum of Months | 489.17 | 24.55 | 389.67 | 24.56 | 387.33 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.93 | 472.67 | 19.87 | 472.67 | 19.85 |
February | 443.50 | 20.61 | 343.67 | 20.41 | 340.83 | 20.32 |
March | 482.00 | 21.02 | 281.50 | 20.74 | 276.50 | 20.59 |
April | 401.67 | 21.91 | 149.50 | 21.74 | 119.33 | 21.51 |
May | 291.00 | 22.44 | 150.33 | 22.63 | 63.67 | 22.43 |
June | 143.50 | 23.41 | 249.67 | 24.07 | 13.17 | 24.15 |
July | 79.83 | 24.59 | 338.50 | 24.57 | 27.00 | 24.73 |
August | 122.17 | 23.61 | 253.67 | 24.20 | 13.33 | 24.28 |
September | 243.17 | 22.73 | 176.33 | 23.41 | 33.33 | 23.42 |
October | 423.17 | 21.91 | 123.83 | 21.73 | 102.50 | 21.51 |
November | 474.00 | 20.90 | 283.50 | 20.59 | 283.50 | 20.45 |
December | 497.00 | 20.09 | 434.50 | 19.97 | 434.50 | 19.93 |
Annual Sum or Average | 4103.00 | 21.33 | 3257.67 | 21.46 | 2180.33 | 21.19 |
Minimum of Months | 79.83 | 19.93 | 123.83 | 19.87 | 13.17 | 19.85 |
Maximum of Months | 502.00 | 24.59 | 472.67 | 24.57 | 472.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.95 | 501.17 | 19.95 | 501.17 | 19.95 |
February | 454.00 | 20.47 | 418.50 | 20.43 | 418.50 | 20.41 |
March | 514.00 | 20.80 | 355.83 | 20.67 | 355.83 | 20.61 |
April | 485.00 | 21.55 | 136.50 | 21.34 | 136.50 | 21.20 |
May | 444.83 | 22.53 | 64.50 | 22.42 | 49.17 | 22.27 |
June | 210.00 | 23.54 | 105.50 | 23.77 | 0.00 | 23.77 |
July | 45.67 | 23.82 | 238.67 | 24.33 | 0.00 | 24.33 |
August | 124.83 | 23.64 | 115.67 | 24.04 | 0.00 | 24.04 |
September | 280.17 | 23.10 | 93.17 | 23.48 | 3.17 | 23.48 |
October | 501.17 | 22.62 | 12.83 | 22.57 | 12.83 | 22.53 |
November | 489.00 | 21.26 | 230.00 | 21.01 | 230.00 | 20.89 |
December | 497.00 | 20.30 | 456.17 | 20.26 | 456.17 | 20.24 |
Annual Sum or Average | 4547.67 | 21.50 | 2728.50 | 21.37 | 2163.33 | 21.12 |
Minimum of Months | 45.67 | 19.95 | 12.83 | 19.95 | 0.00 | 19.95 |
Maximum of Months | 514.00 | 23.82 | 501.17 | 24.33 | 501.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 477.83 | 20.16 | 477.83 | 20.15 |
February | 454.00 | 21.00 | 303.17 | 20.75 | 303.17 | 20.65 |
March | 512.00 | 21.52 | 224.50 | 21.19 | 224.50 | 21.01 |
April | 418.83 | 22.32 | 63.50 | 22.16 | 55.33 | 21.98 |
May | 303.67 | 22.82 | 75.50 | 23.00 | 19.67 | 22.88 |
June | 87.50 | 23.89 | 265.00 | 24.40 | 9.00 | 24.47 |
July | 35.50 | 26.18 | 409.17 | 24.76 | 25.67 | 24.89 |
August | 40.17 | 24.42 | 327.17 | 24.52 | 9.83 | 24.58 |
September | 164.17 | 23.64 | 189.17 | 24.25 | 16.83 | 24.35 |
October | 373.83 | 23.02 | 11.67 | 23.05 | 4.67 | 23.02 |
November | 486.50 | 21.86 | 153.50 | 21.55 | 153.50 | 21.35 |
December | 497.00 | 20.50 | 399.17 | 20.38 | 399.17 | 20.34 |
Annual Sum or Average | 3875.17 | 21.75 | 2899.33 | 21.94 | 1699.17 | 21.66 |
Minimum of Months | 35.50 | 20.18 | 11.67 | 20.16 | 4.67 | 20.15 |
Maximum of Months | 512.00 | 26.18 | 477.83 | 24.76 | 477.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.50 | 19.58 | 404.50 | 19.33 | 400.50 | 19.22 |
February | 410.33 | 20.58 | 271.83 | 20.37 | 254.17 | 20.17 |
March | 465.33 | 21.01 | 210.00 | 20.68 | 205.00 | 20.48 |
April | 423.17 | 21.75 | 118.67 | 21.56 | 99.83 | 21.33 |
May | 363.83 | 21.96 | 108.00 | 22.03 | 60.17 | 21.79 |
June | 190.17 | 22.78 | 168.33 | 23.57 | 0.83 | 23.56 |
July | 61.67 | 23.65 | 328.50 | 24.44 | 10.17 | 24.51 |
August | 87.50 | 23.03 | 288.83 | 24.22 | 7.50 | 24.28 |
September | 177.50 | 23.08 | 228.83 | 24.03 | 25.83 | 24.15 |
October | 295.50 | 22.62 | 108.83 | 23.05 | 19.17 | 22.99 |
November | 401.50 | 21.64 | 147.17 | 21.47 | 117.33 | 21.18 |
December | 480.50 | 20.34 | 315.17 | 20.00 | 313.33 | 19.85 |
Annual Sum or Average | 3851.50 | 21.33 | 2698.67 | 21.56 | 1513.83 | 21.21 |
Minimum of Months | 61.67 | 19.58 | 108.00 | 19.33 | 0.83 | 19.22 |
Maximum of Months | 494.50 | 23.65 | 404.50 | 24.44 | 400.50 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.17 | 478.17 | 20.13 | 478.17 | 20.12 |
February | 449.83 | 20.86 | 326.67 | 20.66 | 325.67 | 20.58 |
March | 503.67 | 21.26 | 249.83 | 20.98 | 249.83 | 20.85 |
April | 444.00 | 22.19 | 84.17 | 22.04 | 71.83 | 21.87 |
May | 309.67 | 22.81 | 88.33 | 23.04 | 24.83 | 22.92 |
June | 120.83 | 23.67 | 217.50 | 24.19 | 5.17 | 24.23 |
July | 32.00 | 25.44 | 378.00 | 24.65 | 15.50 | 24.73 |
August | 61.67 | 23.91 | 261.50 | 24.45 | 5.67 | 24.50 |
September | 193.00 | 23.50 | 183.67 | 24.12 | 12.67 | 24.20 |
October | 399.33 | 22.94 | 25.33 | 23.01 | 6.17 | 22.98 |
November | 475.17 | 21.75 | 167.17 | 21.43 | 167.17 | 21.24 |
December | 497.00 | 20.50 | 397.50 | 20.36 | 397.50 | 20.31 |
Annual Sum or Average | 3988.17 | 21.69 | 2857.83 | 21.83 | 1760.17 | 21.54 |
Minimum of Months | 32.00 | 20.17 | 25.33 | 20.13 | 5.17 | 20.12 |
Maximum of Months | 503.67 | 25.44 | 478.17 | 24.65 | 478.17 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 489.17 | 20.00 | 489.17 | 20.00 |
February | 454.00 | 20.64 | 350.00 | 20.51 | 350.00 | 20.46 |
March | 514.00 | 21.28 | 227.50 | 21.00 | 227.50 | 20.85 |
April | 475.00 | 22.41 | 50.50 | 22.23 | 50.50 | 22.08 |
May | 343.67 | 22.85 | 70.67 | 22.93 | 27.17 | 22.78 |
June | 103.00 | 23.61 | 189.67 | 24.11 | 0.00 | 24.11 |
July | 24.67 | 24.08 | 316.33 | 24.50 | 1.83 | 24.51 |
August | 81.00 | 23.63 | 171.83 | 24.24 | 0.67 | 24.25 |
September | 248.00 | 23.07 | 111.50 | 23.59 | 3.83 | 23.61 |
October | 484.00 | 22.52 | 34.83 | 22.39 | 34.83 | 22.28 |
November | 489.00 | 21.20 | 246.33 | 20.91 | 246.33 | 20.77 |
December | 497.00 | 20.22 | 441.17 | 20.15 | 441.17 | 20.12 |
Annual Sum or Average | 4215.33 | 21.55 | 2699.50 | 21.54 | 1873.00 | 21.26 |
Minimum of Months | 24.67 | 20.02 | 34.83 | 20.00 | 0.00 | 20.00 |
Maximum of Months | 514.00 | 24.08 | 489.17 | 24.50 | 489.17 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.08 | 389.67 | 20.02 | 389.67 | 19.99 |
February | 379.50 | 20.98 | 246.67 | 20.71 | 245.33 | 20.59 |
March | 419.17 | 21.63 | 151.33 | 21.26 | 151.33 | 21.05 |
April | 316.67 | 22.51 | 62.17 | 22.50 | 34.67 | 22.34 |
May | 217.83 | 22.80 | 99.50 | 23.19 | 19.50 | 23.03 |
June | 80.00 | 24.48 | 230.67 | 24.65 | 20.00 | 24.80 |
July | 47.50 | 26.36 | 335.00 | 24.98 | 36.50 | 25.17 |
August | 53.00 | 24.43 | 251.33 | 24.62 | 13.33 | 24.73 |
September | 166.17 | 23.50 | 156.33 | 24.19 | 19.17 | 24.34 |
October | 347.50 | 22.68 | 29.00 | 22.63 | 21.00 | 22.52 |
November | 414.50 | 21.55 | 167.50 | 21.19 | 167.50 | 21.00 |
December | 422.00 | 20.27 | 342.00 | 20.14 | 342.00 | 20.08 |
Annual Sum or Average | 3290.83 | 21.72 | 2461.17 | 21.92 | 1460.00 | 21.64 |
Minimum of Months | 47.50 | 20.08 | 29.00 | 20.02 | 13.33 | 19.99 |
Maximum of Months | 427.00 | 26.36 | 389.67 | 24.98 | 389.67 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.00 | 20.88 | 348.00 | 20.62 | 342.50 | 20.48 |
February | 386.33 | 21.56 | 229.67 | 21.37 | 201.67 | 21.15 |
March | 416.67 | 21.80 | 178.00 | 21.66 | 138.50 | 21.42 |
April | 344.33 | 22.50 | 85.50 | 22.61 | 38.33 | 22.46 |
May | 266.83 | 22.77 | 119.33 | 23.14 | 25.50 | 23.00 |
June | 118.33 | 23.77 | 223.33 | 24.25 | 9.17 | 24.32 |
July | 56.17 | 25.16 | 359.00 | 24.67 | 24.83 | 24.80 |
August | 77.00 | 24.13 | 294.33 | 24.44 | 12.83 | 24.53 |
September | 170.83 | 23.60 | 234.17 | 24.25 | 22.17 | 24.40 |
October | 299.50 | 22.86 | 120.33 | 23.22 | 24.17 | 23.20 |
November | 389.00 | 21.97 | 174.17 | 21.84 | 132.50 | 21.59 |
December | 453.33 | 20.99 | 289.00 | 20.69 | 284.50 | 20.53 |
Annual Sum or Average | 3460.33 | 22.06 | 2654.83 | 22.34 | 1256.67 | 22.07 |
Minimum of Months | 56.17 | 20.88 | 85.50 | 20.62 | 9.17 | 20.48 |
Maximum of Months | 482.00 | 25.16 | 359.00 | 24.67 | 342.50 | 24.80 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.22 | 459.33 | 20.15 | 459.33 | 20.13 |
February | 437.83 | 20.94 | 291.67 | 20.72 | 287.67 | 20.60 |
March | 478.67 | 21.50 | 195.50 | 21.19 | 188.83 | 21.00 |
April | 392.00 | 22.50 | 76.00 | 22.49 | 46.83 | 22.35 |
May | 257.17 | 22.85 | 127.17 | 23.24 | 27.83 | 23.16 |
June | 97.50 | 23.80 | 259.50 | 24.28 | 9.67 | 24.35 |
July | 49.00 | 25.37 | 373.00 | 24.68 | 24.17 | 24.82 |
August | 76.00 | 24.04 | 270.33 | 24.43 | 11.00 | 24.51 |
September | 206.00 | 23.29 | 182.00 | 23.98 | 15.83 | 24.08 |
October | 400.17 | 22.60 | 53.83 | 22.60 | 30.67 | 22.49 |
November | 466.17 | 21.51 | 199.83 | 21.16 | 199.83 | 20.97 |
December | 496.33 | 20.44 | 388.17 | 20.26 | 388.17 | 20.19 |
Annual Sum or Average | 3858.83 | 21.69 | 2876.33 | 21.88 | 1689.83 | 21.60 |
Minimum of Months | 49.00 | 20.22 | 53.83 | 20.15 | 9.67 | 20.13 |
Maximum of Months | 502.00 | 25.37 | 459.33 | 24.68 | 459.33 | 24.82 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.59361 | 16.00357 | -0.2522 | 7.61412 |
February | 454.00000 | 23.33965 | 15.88897 | -0.0603 | 6.10310 |
March | 514.00000 | 23.91163 | 16.81428 | 0.10816 | 5.68039 |
April | 485.00000 | 24.26272 | 20.29235 | 0.24608 | 6.40793 |
May | 508.00000 | 24.42364 | 23.09873 | -0.5479 | 12.24252 |
June | 496.00000 | 24.40407 | 30.67608 | -0.4336 | 9.46325 |
July | 497.00000 | 24.53001 | 34.38674 | -0.3503 | 8.34698 |
August | 514.00000 | 24.46182 | 30.51234 | -0.4027 | 9.03010 |
September | 485.00000 | 24.46674 | 30.12250 | -0.4314 | 9.67518 |
October | 502.00000 | 24.39397 | 22.40903 | 0.31545 | 7.28757 |
November | 489.00000 | 24.12265 | 18.14143 | 0.17615 | 6.01484 |
December | 497.00000 | 23.33837 | 15.46417 | -0.0624 | 6.14689 |
Annual Sum or Average | 5943.00000 | 24.02489 | 22.86225 | -0.1429 | 7.85304 |
Minimum of Months | 454.00000 | 22.59361 | 15.46417 | -0.5479 | 5.68039 |
Maximum of Months | 514.00000 | 24.53001 | 34.38674 | 0.31545 | 12.24252 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.03826 | 16.74817 | -0.6170 | 14.07507 |
February | 454.00000 | 21.85684 | 17.55044 | -0.3960 | 9.85841 |
March | 514.00000 | 22.69769 | 19.02005 | -0.1722 | 7.15831 |
April | 485.00000 | 23.49744 | 21.80149 | 0.06115 | 5.75664 |
May | 508.00000 | 23.91145 | 24.42801 | -0.7368 | 17.95852 |
June | 496.00000 | 24.18473 | 31.68214 | -0.5284 | 11.22935 |
July | 497.00000 | 24.33600 | 35.36809 | -0.4345 | 9.40663 |
August | 514.00000 | 24.27088 | 31.46389 | -0.4906 | 10.39142 |
September | 485.00000 | 24.17573 | 31.31771 | -0.5611 | 12.43800 |
October | 502.00000 | 23.70945 | 24.14523 | 0.13392 | 5.79377 |
November | 489.00000 | 22.76304 | 20.51048 | -0.1474 | 6.88639 |
December | 497.00000 | 21.53617 | 17.41860 | -0.4769 | 11.44612 |
Annual Sum or Average | 5943.00000 | 23.17381 | 24.33053 | -0.3646 | 10.21686 |
Minimum of Months | 454.00000 | 21.03826 | 16.74817 | -0.7368 | 5.75664 |
Maximum of Months | 514.00000 | 24.33600 | 35.36809 | 0.13392 | 17.95852 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41400 | 15.94237 | -0.8089 | 20.54470 |
February | 454.00000 | 21.08651 | 18.12441 | -0.6031 | 14.52833 |
March | 514.00000 | 21.80891 | 19.76693 | -0.3953 | 10.53183 |
April | 485.00000 | 22.83264 | 22.75960 | -0.1020 | 6.79034 |
May | 508.00000 | 23.52344 | 24.85472 | -0.8756 | 23.66822 |
June | 496.00000 | 24.07095 | 31.69437 | -0.5698 | 12.50231 |
July | 497.00000 | 24.26309 | 35.15022 | -0.4576 | 9.89157 |
August | 514.00000 | 24.18437 | 31.42955 | -0.5266 | 11.32709 |
September | 485.00000 | 23.86417 | 31.91549 | -0.6814 | 16.63475 |
October | 502.00000 | 22.93000 | 25.51468 | -0.0627 | 6.35112 |
November | 489.00000 | 21.69673 | 21.49714 | -0.4181 | 10.90935 |
December | 497.00000 | 20.64585 | 17.84186 | -0.7206 | 18.22788 |
Annual Sum or Average | 5943.00000 | 22.62140 | 24.74644 | -0.5187 | 13.49972 |
Minimum of Months | 454.00000 | 20.41400 | 15.94237 | -0.8756 | 6.35112 |
Maximum of Months | 514.00000 | 24.26309 | 35.15022 | -0.0627 | 23.66822 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.69826 | 15.82818 | -1.0658 | 31.12705 |
February | 454.00000 | 20.28827 | 19.09330 | -0.8487 | 22.31381 |
March | 514.00000 | 20.81136 | 21.27220 | -0.6543 | 16.56062 |
April | 485.00000 | 21.89765 | 24.72547 | -0.3223 | 9.95590 |
May | 508.00000 | 22.95914 | 26.56449 | -1.0486 | 31.81328 |
June | 496.00000 | 23.94212 | 32.24596 | -0.5860 | 13.97220 |
July | 497.00000 | 24.26934 | 35.22868 | -0.4216 | 10.01061 |
August | 514.00000 | 24.02106 | 32.17441 | -0.5634 | 13.24382 |
September | 485.00000 | 23.30984 | 33.77333 | -0.8627 | 25.07983 |
October | 502.00000 | 21.86646 | 27.79217 | -0.3158 | 9.39599 |
November | 489.00000 | 20.57982 | 23.25475 | -0.7090 | 18.33661 |
December | 497.00000 | 19.89023 | 18.63739 | -0.9719 | 27.33146 |
Annual Sum or Average | 5943.00000 | 21.97463 | 25.91974 | -0.6970 | 19.08158 |
Minimum of Months | 454.00000 | 19.69826 | 15.82818 | -1.0658 | 9.39599 |
Maximum of Months | 514.00000 | 24.26934 | 35.22868 | -0.3158 | 31.81328 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92089 | 16.56050 | -0.9934 | 28.09200 |
February | 454.00000 | 20.74868 | 19.55299 | -0.7135 | 18.99394 |
March | 514.00000 | 21.40595 | 21.21562 | -0.4894 | 14.08696 |
April | 485.00000 | 22.54062 | 23.70606 | -0.1356 | 9.21873 |
May | 508.00000 | 23.32988 | 25.67312 | -0.8610 | 25.20101 |
June | 496.00000 | 24.20101 | 31.43722 | -0.3953 | 11.25439 |
July | 497.00000 | 24.47977 | 34.51894 | -0.2229 | 8.52725 |
August | 514.00000 | 24.22106 | 31.35288 | -0.3805 | 10.46588 |
September | 485.00000 | 23.74225 | 32.75124 | -0.6529 | 19.14655 |
October | 502.00000 | 22.50460 | 27.06480 | -0.1450 | 8.39665 |
November | 489.00000 | 21.00908 | 23.68858 | -0.5926 | 15.67303 |
December | 497.00000 | 20.03885 | 19.38489 | -0.9170 | 25.31673 |
Annual Sum or Average | 5943.00000 | 22.35764 | 25.60789 | -0.5409 | 16.18488 |
Minimum of Months | 454.00000 | 19.92089 | 16.56050 | -0.9934 | 8.39665 |
Maximum of Months | 514.00000 | 24.47977 | 34.51894 | -0.1356 | 28.09200 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.63843 | 15.30047 | -0.7862 | 23.04274 |
February | 454.00000 | 21.57433 | 17.42015 | -0.4768 | 16.10825 |
March | 514.00000 | 21.78618 | 19.27305 | -0.3732 | 13.39884 |
April | 485.00000 | 22.55037 | 22.90079 | -0.1311 | 9.83129 |
May | 508.00000 | 23.18398 | 25.40870 | -0.9234 | 28.24607 |
June | 496.00000 | 23.96754 | 31.83730 | -0.5292 | 14.08249 |
July | 497.00000 | 24.31793 | 34.82400 | -0.3363 | 9.95002 |
August | 514.00000 | 24.13781 | 31.30198 | -0.4184 | 11.55887 |
September | 485.00000 | 23.76369 | 31.97271 | -0.5965 | 18.96854 |
October | 502.00000 | 22.88719 | 24.85730 | -0.0108 | 9.33505 |
November | 489.00000 | 21.85730 | 20.96269 | -0.3583 | 13.18101 |
December | 497.00000 | 20.78911 | 17.60126 | -0.7015 | 20.70568 |
Annual Sum or Average | 5943.00000 | 22.62892 | 24.51324 | -0.4710 | 15.71231 |
Minimum of Months | 454.00000 | 20.63843 | 15.30047 | -0.9234 | 9.33505 |
Maximum of Months | 514.00000 | 24.31793 | 34.82400 | -0.0108 | 28.24607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.92678 | 16.37068 | -1.0012 | 28.66296 |
February | 454.00000 | 20.69609 | 19.30348 | -0.7309 | 20.10175 |
March | 514.00000 | 21.21291 | 21.24778 | -0.5400 | 15.25008 |
April | 485.00000 | 22.31477 | 24.36973 | -0.1939 | 9.93437 |
May | 508.00000 | 23.21626 | 26.14499 | -0.8978 | 27.67683 |
June | 496.00000 | 23.99607 | 32.19215 | -0.4917 | 13.45802 |
July | 497.00000 | 24.33721 | 35.13271 | -0.3135 | 9.89855 |
August | 514.00000 | 24.11300 | 31.94903 | -0.4492 | 12.01546 |
September | 485.00000 | 23.53991 | 33.36860 | -0.7255 | 22.16957 |
October | 502.00000 | 22.27987 | 27.29434 | -0.1962 | 9.26982 |
November | 489.00000 | 20.99884 | 23.34004 | -0.5956 | 16.35764 |
December | 497.00000 | 20.08802 | 19.23453 | -0.9112 | 25.53243 |
Annual Sum or Average | 5943.00000 | 22.23868 | 25.86448 | -0.5868 | 17.51581 |
Minimum of Months | 454.00000 | 19.92678 | 16.37068 | -1.0012 | 9.26982 |
Maximum of Months | 514.00000 | 24.33721 | 35.13271 | -0.1939 | 28.66296 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95346 | 16.17409 | -0.9768 | 26.91079 |
February | 454.00000 | 20.47340 | 19.23747 | -0.7927 | 19.55572 |
March | 514.00000 | 20.80327 | 21.58471 | -0.6544 | 15.24636 |
April | 485.00000 | 21.55436 | 26.11907 | -0.4094 | 9.65823 |
May | 508.00000 | 22.75723 | 27.90489 | -1.1403 | 34.88491 |
June | 496.00000 | 23.89068 | 32.99163 | -0.6472 | 14.69964 |
July | 497.00000 | 24.23175 | 35.66898 | -0.4707 | 10.16494 |
August | 514.00000 | 24.07837 | 32.47491 | -0.5709 | 12.50634 |
September | 485.00000 | 23.61790 | 33.54133 | -0.7630 | 19.60348 |
October | 502.00000 | 22.61999 | 27.22287 | -0.1222 | 6.38336 |
November | 489.00000 | 21.26312 | 22.92328 | -0.5095 | 12.07978 |
December | 497.00000 | 20.29674 | 18.80720 | -0.8276 | 21.04603 |
Annual Sum or Average | 5943.00000 | 22.14088 | 26.26026 | -0.6570 | 16.90732 |
Minimum of Months | 454.00000 | 19.95346 | 16.17409 | -1.1403 | 6.38336 |
Maximum of Months | 514.00000 | 24.23175 | 35.66898 | -0.1222 | 34.88491 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18308 | 16.91696 | -0.9031 | 24.01110 |
February | 454.00000 | 21.00143 | 19.72380 | -0.6414 | 16.19041 |
March | 514.00000 | 21.52750 | 21.69633 | -0.4542 | 11.99352 |
April | 485.00000 | 22.58819 | 24.83318 | -0.1369 | 7.83028 |
May | 508.00000 | 23.41376 | 26.51519 | -0.8640 | 24.10608 |
June | 496.00000 | 24.25903 | 31.62104 | -0.4152 | 10.51017 |
July | 497.00000 | 24.54597 | 34.51733 | -0.2299 | 7.74683 |
August | 514.00000 | 24.34094 | 31.23320 | -0.3569 | 8.99164 |
September | 485.00000 | 24.11882 | 32.11980 | -0.5245 | 13.43041 |
October | 502.00000 | 23.31905 | 25.98952 | 0.06527 | 6.34567 |
November | 489.00000 | 21.87424 | 23.13476 | -0.3540 | 9.94925 |
December | 497.00000 | 20.49822 | 19.58061 | -0.7623 | 19.02576 |
Annual Sum or Average | 5943.00000 | 22.65054 | 25.68988 | -0.4645 | 13.34636 |
Minimum of Months | 454.00000 | 20.18308 | 16.91696 | -0.9031 | 6.34567 |
Maximum of Months | 514.00000 | 24.54597 | 34.51733 | 0.06527 | 24.10608 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67136 | 13.61827 | -0.9268 | 27.69578 |
February | 454.00000 | 20.99325 | 15.95061 | -0.5521 | 17.40135 |
March | 514.00000 | 21.31422 | 18.01367 | -0.4402 | 12.85707 |
April | 485.00000 | 22.09926 | 22.62133 | -0.2294 | 9.25793 |
May | 508.00000 | 22.66462 | 25.60554 | -1.0918 | 34.25579 |
June | 496.00000 | 23.71532 | 32.27211 | -0.6390 | 16.31930 |
July | 497.00000 | 24.30229 | 34.69688 | -0.3721 | 9.69327 |
August | 514.00000 | 24.13754 | 30.96640 | -0.4266 | 11.16227 |
September | 485.00000 | 23.93219 | 31.18323 | -0.5135 | 15.30617 |
October | 502.00000 | 23.34651 | 23.35305 | 0.14070 | 8.03451 |
November | 489.00000 | 22.18102 | 19.03753 | -0.2150 | 10.49431 |
December | 497.00000 | 20.48950 | 15.84866 | -0.6870 | 19.73086 |
Annual Sum or Average | 5943.00000 | 22.41256 | 23.64415 | -0.4971 | 16.04378 |
Minimum of Months | 454.00000 | 19.67136 | 13.61827 | -1.0918 | 8.03451 |
Maximum of Months | 514.00000 | 24.30229 | 34.69688 | 0.14070 | 34.25579 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16516 | 16.79428 | -0.9162 | 24.54388 |
February | 454.00000 | 20.89421 | 19.62704 | -0.6679 | 16.95542 |
March | 514.00000 | 21.31669 | 21.77184 | -0.5081 | 12.89376 |
April | 485.00000 | 22.36336 | 25.38800 | -0.1957 | 8.06534 |
May | 508.00000 | 23.42503 | 26.71390 | -0.8627 | 24.70758 |
June | 496.00000 | 24.12430 | 32.24003 | -0.4902 | 11.68774 |
July | 497.00000 | 24.45437 | 35.00709 | -0.3036 | 8.32245 |
August | 514.00000 | 24.27795 | 31.72030 | -0.4134 | 9.94701 |
September | 485.00000 | 24.04137 | 32.50307 | -0.5610 | 14.51758 |
October | 502.00000 | 23.21129 | 26.26214 | 0.03826 | 6.46950 |
November | 489.00000 | 21.80939 | 22.90370 | -0.3668 | 10.24450 |
December | 497.00000 | 20.50055 | 19.51700 | -0.7644 | 19.41983 |
Annual Sum or Average | 5943.00000 | 22.56029 | 25.90564 | -0.5008 | 13.98374 |
Minimum of Months | 454.00000 | 20.16516 | 16.79428 | -0.9162 | 6.46950 |
Maximum of Months | 514.00000 | 24.45437 | 35.00709 | 0.03826 | 24.70758 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01557 | 16.02322 | -0.9438 | 25.71390 |
February | 454.00000 | 20.64487 | 19.08342 | -0.7213 | 17.73745 |
March | 514.00000 | 21.27584 | 20.98553 | -0.5095 | 12.58620 |
April | 485.00000 | 22.44407 | 24.04181 | -0.1785 | 7.41011 |
May | 508.00000 | 23.33810 | 26.09662 | -0.9115 | 25.74048 |
June | 496.00000 | 24.09319 | 32.05941 | -0.5340 | 11.81559 |
July | 497.00000 | 24.36247 | 35.29281 | -0.3931 | 9.08084 |
August | 514.00000 | 24.16207 | 31.99254 | -0.5135 | 11.34072 |
September | 485.00000 | 23.70636 | 33.05040 | -0.7209 | 18.79388 |
October | 502.00000 | 22.57096 | 26.68297 | -0.1331 | 6.83708 |
November | 489.00000 | 21.20415 | 22.65456 | -0.5234 | 13.06616 |
December | 497.00000 | 20.21673 | 18.69063 | -0.8398 | 21.96735 |
Annual Sum or Average | 5943.00000 | 22.34897 | 25.59132 | -0.5766 | 15.17041 |
Minimum of Months | 454.00000 | 20.01557 | 16.02322 | -0.9438 | 6.83708 |
Maximum of Months | 514.00000 | 24.36247 | 35.29281 | -0.1331 | 25.74048 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.07512 | 16.32801 | -0.9139 | 24.75027 |
February | 385.00000 | 21.03659 | 19.16798 | -0.6116 | 16.02294 |
March | 433.00000 | 21.71134 | 20.55664 | -0.3909 | 11.49527 |
April | 410.00000 | 22.93134 | 22.89121 | -0.0356 | 7.63256 |
May | 430.00000 | 23.59074 | 25.12987 | -0.7757 | 21.74304 |
June | 418.00000 | 24.36489 | 31.05325 | -0.3612 | 10.23071 |
July | 422.00000 | 24.64206 | 34.23446 | -0.2002 | 8.30029 |
August | 433.00000 | 24.38015 | 30.89070 | -0.3542 | 9.61711 |
September | 410.00000 | 24.04534 | 31.91688 | -0.5559 | 15.60094 |
October | 427.00000 | 22.97766 | 25.63469 | -0.0215 | 6.93086 |
November | 417.00000 | 21.55988 | 22.59309 | -0.4321 | 11.76856 |
December | 422.00000 | 20.27103 | 19.05173 | -0.8143 | 21.37276 |
Annual Sum or Average | 5034.00000 | 22.64065 | 24.97814 | -0.4555 | 13.79013 |
Minimum of Months | 385.00000 | 20.07512 | 16.32801 | -0.9139 | 6.93086 |
Maximum of Months | 433.00000 | 24.64206 | 34.23446 | -0.0215 | 24.75027 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.03565 | 15.16851 | -0.6501 | 18.70258 |
February | 454.00000 | 22.00692 | 17.06376 | -0.3386 | 13.02676 |
March | 514.00000 | 22.27320 | 18.82070 | -0.2272 | 10.39210 |
April | 485.00000 | 23.03293 | 22.17396 | -0.0017 | 7.85829 |
May | 508.00000 | 23.52403 | 24.96029 | -0.7984 | 22.72816 |
June | 496.00000 | 24.13873 | 31.61708 | -0.4732 | 11.62429 |
July | 497.00000 | 24.42639 | 34.83454 | -0.3051 | 8.76349 |
August | 514.00000 | 24.27381 | 31.13903 | -0.3724 | 9.76716 |
September | 485.00000 | 24.07536 | 31.35957 | -0.4805 | 14.19767 |
October | 502.00000 | 23.42771 | 23.81843 | 0.13691 | 8.11666 |
November | 489.00000 | 22.48120 | 20.14201 | -0.1771 | 10.18272 |
December | 497.00000 | 21.28943 | 17.24745 | -0.5389 | 16.15754 |
Annual Sum or Average | 5943.00000 | 23.00547 | 24.07161 | -0.3533 | 12.63891 |
Minimum of Months | 454.00000 | 21.03565 | 15.16851 | -0.7984 | 7.85829 |
Maximum of Months | 514.00000 | 24.42639 | 34.83454 | 0.13691 | 22.72816 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.22306 | 16.63183 | -0.8837 | 23.69953 |
February | 454.00000 | 21.07154 | 19.25027 | -0.6015 | 15.99276 |
March | 514.00000 | 21.67753 | 20.86957 | -0.3967 | 11.64904 |
April | 485.00000 | 22.84419 | 23.60256 | -0.0549 | 7.71678 |
May | 508.00000 | 23.57143 | 25.62850 | -0.7687 | 22.02272 |
June | 496.00000 | 24.16464 | 31.92850 | -0.4364 | 11.05573 |
July | 497.00000 | 24.44642 | 35.12251 | -0.2818 | 8.71377 |
August | 514.00000 | 24.25256 | 31.72779 | -0.4014 | 10.14251 |
September | 485.00000 | 23.91072 | 32.62775 | -0.5922 | 16.41050 |
October | 502.00000 | 22.93376 | 26.14629 | -0.0248 | 7.17774 |
November | 489.00000 | 21.62790 | 22.59767 | -0.4115 | 11.74126 |
December | 497.00000 | 20.44013 | 19.31827 | -0.7749 | 20.45470 |
Annual Sum or Average | 5943.00000 | 22.60811 | 25.48950 | -0.4689 | 13.89417 |
Minimum of Months | 454.00000 | 20.22306 | 16.63183 | -0.8837 | 7.17774 |
Maximum of Months | 514.00000 | 24.44642 | 35.12251 | -0.0248 | 23.69953 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.143099E+12 | 0.00 | 532.98 | 254752.16 | 17-JAN-06:11 | 0.00 | 39.28 | 52.94 | 0.75 | 0.00 | 0.14 | 0.67 | 17-JAN-06:11 |
February | 0.742448E+11 | 0.00 | 385.21 | 236463.54 | 13-FEB-06:11 | 0.00 | 35.26 | 47.99 | 0.42 | 0.00 | 0.08 | 0.63 | 13-FEB-06:11 |
March | 0.457909E+11 | 0.00 | 400.29 | 221423.37 | 06-MAR-07:11 | 0.00 | 32.05 | 46.03 | 0.20 | 0.00 | 0.05 | 0.59 | 06-MAR-07:11 |
April | 0.145198E+11 | 0.00 | 239.06 | 213262.08 | 03-APR-06:02 | 0.00 | 29.05 | 38.63 | 0.05 | 0.00 | 0.01 | 0.56 | 03-APR-06:02 |
May | 0.927337E+10 | 0.00 | 171.84 | 174603.89 | 09-MAY-05:01 | 0.00 | 35.92 | 42.15 | 0.03 | 0.00 | 0.01 | 0.46 | 09-MAY-05:01 |
June | 0.787589E+09 | 0.00 | 70.06 | 39200.03 | 17-JUN-06:03 | 0.00 | 36.63 | 39.18 | 0.00 | 0.00 | 0.00 | 0.10 | 17-JUN-06:03 |
July | 37676771.41 | 0.00 | 43.30 | 17897.57 | 05-JUL-06:05 | 0.00 | 38.57 | 39.84 | 0.00 | 0.00 | 0.00 | 0.05 | 05-JUL-06:05 |
August | 0.300277E+09 | 0.00 | 38.31 | 30000.80 | 18-AUG-06:03 | 0.00 | 41.91 | 42.90 | 0.00 | 0.00 | 0.00 | 0.08 | 18-AUG-06:03 |
September | 0.272114E+10 | 0.00 | 104.97 | 100564.59 | 20-SEP-06:03 | 0.00 | 36.06 | 39.89 | 0.01 | 0.00 | 0.00 | 0.27 | 20-SEP-06:03 |
October | 0.990854E+10 | 0.00 | 192.97 | 179889.30 | 06-OCT-06:02 | 0.00 | 29.01 | 36.67 | 0.03 | 0.00 | 0.01 | 0.48 | 06-OCT-06:02 |
November | 0.362601E+11 | 0.00 | 329.56 | 205657.65 | 27-NOV-07:11 | 0.00 | 32.87 | 44.49 | 0.16 | 0.00 | 0.04 | 0.54 | 27-NOV-07:11 |
December | 0.935839E+11 | 0.00 | 487.64 | 230610.36 | 29-DEC-07:05 | 0.00 | 37.74 | 51.61 | 0.47 | 0.00 | 0.09 | 0.61 | 29-DEC-07:05 |
Annual Sum or Average | 0.430527E+12 | 0.00 | 2996.20 | 0.00 | 35.38 | 43.52 | 0.18 | 0.00 | 0.04 | ||||
Minimum of Months | 37676771.41 | 0.00 | 38.31 | 17897.57 | 0.00 | 29.01 | 36.67 | 0.00 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.143099E+12 | 0.00 | 532.98 | 254752.16 | 0.00 | 41.91 | 52.94 | 0.75 | 0.00 | 0.14 | 0.67 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 54488.82 | 14788.37 | 0.04 | 50822.52 | 3666.30 | 0.00 | 0.02 | 24-JAN-07:05 | 0.00 | 01-JAN-00:10 | 363.26 | 24-JAN-07:05 | 338.82 | 24-JAN-07:05 | 24.44 | 24-JAN-07:05 | 98.59 | 24-JAN-07:05 | 0.00 |
February | 0.315747E+09 | 77827102.76 | 12.75 | 0.315094E+09 | 653705.43 | 0.00 | 0.64 | 27-FEB-12:00 | 0.00 | 01-FEB-00:10 | 17348.27 | 27-FEB-12:00 | 17348.27 | 27-FEB-12:00 | 186.43 | 28-FEB-12:02 | 4034.13 | 27-FEB-12:00 | 0.00 |
March | 0.147711E+09 | 38985503.56 | 18.34 | 0.147361E+09 | 350140.38 | 0.00 | 0.27 | 23-MAR-11:00 | 0.00 | 01-MAR-00:10 | 6687.95 | 23-MAR-11:00 | 6687.95 | 23-MAR-11:00 | 95.41 | 01-MAR-12:01 | 1708.78 | 23-MAR-11:00 | 0.00 |
April | 0.418659E+10 | 0.985018E+09 | 118.45 | 0.415946E+10 | 27130109.67 | 0.00 | 1.00 | 06-APR-15:00 | 0.00 | 01-APR-00:10 | 32816.40 | 06-APR-16:00 | 32816.40 | 06-APR-16:00 | 830.83 | 18-APR-06:05 | 6890.50 | 06-APR-16:00 | 0.00 |
May | 0.967670E+10 | 0.228086E+10 | 222.50 | 0.944549E+10 | 0.231210E+09 | 0.00 | 1.00 | 18-MAY-15:00 | 0.00 | 01-MAY-00:10 | 52319.13 | 19-MAY-15:30 | 52319.13 | 19-MAY-15:30 | 4879.57 | 02-MAY-13:00 | 12212.11 | 19-MAY-15:20 | 0.00 |
June | 0.277581E+11 | 0.639374E+10 | 322.65 | 0.265402E+11 | 0.121790E+10 | 0.00 | 1.00 | 05-JUN-10:50 | 0.00 | 01-JUN-00:10 | 65688.82 | 20-JUN-16:00 | 64017.45 | 29-JUN-14:50 | 13129.13 | 22-JUN-06:03 | 16783.86 | 29-JUN-15:00 | 0.00 |
July | 0.480109E+11 | 0.114044E+11 | 407.36 | 0.463463E+11 | 0.166453E+10 | 0.00 | 1.00 | 01-JUL-09:40 | 0.00 | 01-JUL-00:10 | 81417.45 | 17-JUL-16:00 | 81417.45 | 17-JUL-16:00 | 23893.67 | 19-JUL-06:03 | 24838.63 | 17-JUL-16:00 | 0.00 |
August | 0.409376E+11 | 0.960462E+10 | 372.93 | 0.404970E+11 | 0.440614E+09 | 0.00 | 1.00 | 01-AUG-10:05 | 0.00 | 01-AUG-00:10 | 73929.23 | 07-AUG-16:00 | 73929.23 | 07-AUG-16:00 | 4846.78 | 08-AUG-16:10 | 19375.48 | 07-AUG-16:00 | 0.00 |
September | 0.211079E+11 | 0.489796E+10 | 298.37 | 0.193572E+11 | 0.175068E+10 | 0.00 | 1.00 | 01-SEP-09:05 | 0.00 | 01-SEP-00:10 | 97035.80 | 07-SEP-14:55 | 61012.43 | 01-SEP-16:00 | 46709.92 | 07-SEP-14:50 | 20552.78 | 07-SEP-14:55 | 0.00 |
October | 0.737840E+10 | 0.171408E+10 | 186.97 | 0.733494E+10 | 43458794.48 | 0.00 | 1.00 | 02-OCT-15:10 | 0.00 | 01-OCT-00:10 | 48418.97 | 18-OCT-15:50 | 48418.97 | 18-OCT-15:50 | 1323.94 | 25-OCT-06:02 | 10328.88 | 18-OCT-15:50 | 0.00 |
November | 0.118051E+10 | 0.290794E+09 | 54.36 | 0.117022E+10 | 10293512.76 | 0.00 | 0.86 | 03-NOV-15:30 | 0.00 | 01-NOV-00:10 | 24655.18 | 03-NOV-15:30 | 24655.18 | 03-NOV-15:30 | 787.96 | 03-NOV-17:08 | 5400.57 | 03-NOV-15:30 | 0.00 |
December | 1841089.41 | 497317.27 | 0.69 | 1762125.63 | 78963.78 | 0.00 | 0.05 | 07-DEC-15:50 | 0.00 | 01-DEC-00:10 | 1191.39 | 07-DEC-15:50 | 1170.82 | 07-DEC-15:50 | 91.65 | 07-DEC-12:01 | 320.73 | 07-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.160702E+12 | 0.376888E+11 | 2015.41 | 0.155315E+12 | 0.538691E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 54488.82 | 14788.37 | 0.04 | 50822.52 | 3666.30 | 0.00 | 0.02 | 0.00 | 363.26 | 338.82 | 24.44 | 98.59 | 0.00 | ||||||
Maximum of Months | 0.480109E+11 | 0.114044E+11 | 407.36 | 0.463463E+11 | 0.175068E+10 | 0.00 | 1.00 | 0.00 | 97035.80 | 81417.45 | 46709.92 | 24838.63 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.363499E+09 | 91072421.32 | 18.23 | 0.362984E+09 | 515034.46 | 0.00 | 0.51 | 28-FEB-15:40 | 0.00 | 01-FEB-00:10 | 12581.91 | 28-FEB-15:40 | 12581.91 | 28-FEB-15:40 | 129.58 | 28-FEB-17:13 | 3027.21 | 28-FEB-15:40 | 0.00 |
March | 0.448737E+09 | 0.114093E+09 | 25.99 | 0.448284E+09 | 453202.40 | 0.00 | 0.47 | 28-MAR-15:40 | 0.00 | 01-MAR-00:10 | 11395.62 | 28-MAR-15:40 | 11395.62 | 28-MAR-15:40 | 196.73 | 02-MAR-17:01 | 2772.28 | 28-MAR-15:40 | 0.00 |
April | 0.205025E+10 | 0.492667E+09 | 73.41 | 0.203209E+10 | 18154027.86 | 0.00 | 1.00 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 28854.80 | 06-APR-16:00 | 28854.80 | 06-APR-16:00 | 716.85 | 23-APR-14:10 | 6059.36 | 06-APR-16:00 | 0.00 |
May | 0.745524E+10 | 0.173642E+10 | 162.16 | 0.725919E+10 | 0.196053E+09 | 0.00 | 1.00 | 18-MAY-14:50 | 0.00 | 01-MAY-00:10 | 53078.16 | 19-MAY-15:30 | 53078.16 | 19-MAY-15:30 | 4699.73 | 02-MAY-13:00 | 12400.35 | 19-MAY-15:20 | 0.00 |
June | 0.262308E+11 | 0.603831E+10 | 318.01 | 0.250824E+11 | 0.114843E+10 | 0.00 | 1.00 | 05-JUN-11:00 | 0.00 | 01-JUN-00:10 | 62611.83 | 21-JUN-14:05 | 61458.98 | 29-JUN-14:40 | 13545.58 | 22-JUN-06:03 | 16055.78 | 29-JUN-15:00 | 0.00 |
July | 0.439514E+11 | 0.104691E+11 | 405.85 | 0.425541E+11 | 0.139735E+10 | 0.00 | 1.00 | 01-JUL-09:50 | 0.00 | 01-JUL-00:10 | 76758.45 | 17-JUL-15:40 | 76758.45 | 17-JUL-15:40 | 19722.86 | 19-JUL-06:03 | 23151.30 | 17-JUL-15:40 | 0.00 |
August | 0.369462E+11 | 0.870692E+10 | 371.56 | 0.365316E+11 | 0.414617E+09 | 0.00 | 1.00 | 01-AUG-10:05 | 0.00 | 01-AUG-00:10 | 72705.50 | 07-AUG-15:20 | 72705.50 | 07-AUG-15:20 | 3946.02 | 22-AUG-15:30 | 19278.29 | 07-AUG-15:20 | 0.00 |
September | 0.170632E+11 | 0.396322E+10 | 237.69 | 0.156351E+11 | 0.142812E+10 | 0.00 | 1.00 | 01-SEP-09:20 | 0.00 | 01-SEP-00:10 | 91291.87 | 07-SEP-14:55 | 64456.16 | 04-SEP-14:41 | 44432.70 | 07-SEP-14:50 | 19336.18 | 07-SEP-14:55 | 0.00 |
October | 0.355323E+10 | 0.823798E+09 | 100.36 | 0.352720E+10 | 26031764.94 | 0.00 | 1.00 | 16-OCT-14:05 | 0.00 | 01-OCT-00:10 | 43115.50 | 18-OCT-15:50 | 43115.50 | 18-OCT-15:50 | 886.94 | 15-OCT-11:34 | 9244.90 | 18-OCT-15:20 | 0.00 |
November | 0.379875E+09 | 99192591.34 | 36.04 | 0.368220E+09 | 11654738.93 | 0.00 | 0.36 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 8590.81 | 09-NOV-15:10 | 8590.81 | 09-NOV-15:10 | 517.77 | 17-NOV-17:08 | 2146.38 | 09-NOV-15:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.138442E+12 | 0.325348E+11 | 1749.30 | 0.133801E+12 | 0.464138E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.439514E+11 | 0.104691E+11 | 405.85 | 0.425541E+11 | 0.142812E+10 | 0.00 | 1.00 | 0.00 | 91291.87 | 76758.45 | 44432.70 | 23151.30 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 807627.15 | 218667.78 | 0.46 | 795185.78 | 12441.37 | 0.00 | 0.04 | 10-JAN-06:40 | 0.00 | 01-JAN-00:10 | 894.13 | 10-JAN-06:40 | 894.13 | 10-JAN-06:40 | 20.74 | 01-JAN-23:10 | 241.58 | 10-JAN-06:40 | 0.00 |
February | 0.306848E+09 | 78603204.70 | 17.85 | 0.305472E+09 | 1375671.72 | 0.00 | 0.38 | 28-FEB-15:40 | 0.00 | 01-FEB-00:10 | 10616.51 | 28-FEB-15:40 | 10616.51 | 28-FEB-15:40 | 356.92 | 28-FEB-17:02 | 2637.54 | 28-FEB-15:40 | 0.00 |
March | 0.560481E+09 | 0.143454E+09 | 29.72 | 0.559117E+09 | 1363504.84 | 0.00 | 0.46 | 28-MAR-15:40 | 0.00 | 01-MAR-00:10 | 12828.15 | 28-MAR-15:40 | 12828.15 | 28-MAR-15:40 | 307.25 | 01-MAR-17:01 | 3129.70 | 28-MAR-15:40 | 0.00 |
April | 0.227082E+10 | 0.553270E+09 | 78.21 | 0.223870E+10 | 32123594.67 | 0.00 | 0.93 | 06-APR-16:00 | 0.00 | 01-APR-00:10 | 29732.43 | 06-APR-16:00 | 29732.43 | 06-APR-16:00 | 889.19 | 23-APR-14:30 | 6377.46 | 06-APR-16:00 | 0.00 |
May | 0.782449E+10 | 0.183635E+10 | 157.12 | 0.755489E+10 | 0.269597E+09 | 0.00 | 1.00 | 19-MAY-11:40 | 0.00 | 01-MAY-00:10 | 61383.40 | 19-MAY-15:30 | 61383.40 | 19-MAY-15:30 | 5160.67 | 02-MAY-13:00 | 14346.70 | 19-MAY-15:20 | 0.00 |
June | 0.280127E+11 | 0.649778E+10 | 317.19 | 0.267047E+11 | 0.130798E+10 | 0.00 | 1.00 | 05-JUN-12:20 | 0.00 | 01-JUN-00:10 | 70292.75 | 20-JUN-15:10 | 69556.56 | 29-JUN-14:50 | 8275.40 | 21-JUN-06:03 | 18220.82 | 29-JUN-15:00 | 0.00 |
July | 0.468101E+11 | 0.112517E+11 | 407.79 | 0.451920E+11 | 0.161809E+10 | 0.00 | 1.00 | 01-JUL-11:40 | 0.00 | 01-JUL-00:10 | 87870.67 | 17-JUL-15:20 | 87870.67 | 17-JUL-15:20 | 12229.56 | 17-JUL-06:03 | 26326.56 | 17-JUL-15:30 | 0.00 |
August | 0.388698E+11 | 0.925790E+10 | 369.39 | 0.383179E+11 | 0.551926E+09 | 0.00 | 1.00 | 01-AUG-11:30 | 0.00 | 01-AUG-00:10 | 82585.94 | 06-AUG-16:11 | 82585.94 | 06-AUG-16:11 | 4258.87 | 22-AUG-15:30 | 23836.68 | 06-AUG-16:11 | 0.00 |
September | 0.175473E+11 | 0.413044E+10 | 237.06 | 0.159705E+11 | 0.157679E+10 | 0.00 | 1.00 | 01-SEP-09:50 | 0.00 | 01-SEP-00:10 | 93884.37 | 07-SEP-15:20 | 82404.78 | 03-SEP-15:01 | 44703.84 | 07-SEP-15:00 | 22180.23 | 03-SEP-13:01 | 0.00 |
October | 0.334340E+10 | 0.795458E+09 | 98.11 | 0.328476E+10 | 58645458.37 | 0.00 | 1.00 | 18-OCT-12:40 | 0.00 | 01-OCT-00:10 | 44013.60 | 18-OCT-15:00 | 44013.60 | 18-OCT-15:00 | 1223.41 | 15-OCT-11:45 | 9505.30 | 18-OCT-15:00 | 0.00 |
November | 0.206408E+09 | 54788707.00 | 26.86 | 0.186714E+09 | 19694480.28 | 0.00 | 0.20 | 09-NOV-14:50 | 0.00 | 01-NOV-00:10 | 5235.18 | 09-NOV-14:50 | 5105.73 | 09-NOV-14:50 | 653.03 | 17-NOV-17:00 | 1361.26 | 09-NOV-14:50 | 0.00 |
December | 490818.53 | 133130.85 | 0.38 | 479817.80 | 11000.73 | 0.00 | 0.02 | 30-DEC-06:20 | 0.00 | 01-DEC-00:10 | 597.57 | 30-DEC-06:20 | 597.57 | 30-DEC-06:20 | 21.36 | 03-DEC-09:20 | 161.88 | 30-DEC-06:20 | 0.00 |
Annual Sum or Average | 0.145754E+12 | 0.346001E+11 | 1740.13 | 0.140316E+12 | 0.543761E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 490818.53 | 133130.85 | 0.38 | 479817.80 | 11000.73 | 0.00 | 0.02 | 0.00 | 597.57 | 597.57 | 20.74 | 161.88 | 0.00 | ||||||
Maximum of Months | 0.468101E+11 | 0.112517E+11 | 407.79 | 0.451920E+11 | 0.161809E+10 | 0.00 | 1.00 | 0.00 | 93884.37 | 87870.67 | 44703.84 | 26326.56 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.01 | 0.00 | 316.01 | 13.93 | 2552.43 | 0.00 | 0.00 | 0.00 |
February | 446.19 | 0.00 | 446.19 | 90.58 | 1882.47 | 0.00 | 0.00 | 0.00 |
March | 724.82 | 0.00 | 724.82 | 282.42 | 1511.89 | 0.00 | 0.00 | 0.00 |
April | 826.45 | 4.82 | 821.63 | 464.80 | 1077.35 | 0.00 | 0.00 | 0.00 |
May | 1085.32 | 64.31 | 1021.01 | 834.45 | 816.26 | 0.00 | 0.00 | 0.00 |
June | 1263.80 | 145.26 | 1118.54 | 1312.94 | 535.10 | 0.00 | 0.00 | 0.00 |
July | 1154.55 | 108.14 | 1046.41 | 1420.65 | 450.08 | 0.00 | 0.00 | 0.00 |
August | 925.15 | 24.80 | 900.35 | 1037.06 | 509.26 | 0.00 | 0.00 | 0.00 |
September | 692.87 | 0.25 | 692.62 | 609.81 | 769.71 | 0.00 | 0.00 | 0.00 |
October | 505.41 | 0.00 | 505.41 | 251.24 | 1109.75 | 0.00 | 0.00 | 0.00 |
November | 343.58 | 0.00 | 343.58 | 66.67 | 1561.40 | 0.00 | 0.00 | 0.00 |
December | 265.00 | 0.00 | 265.00 | 7.63 | 2166.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.86 | 29.11 | 684.75 | 535.43 | 1242.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.00 | 0.00 | 265.00 | 7.63 | 450.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.80 | 145.26 | 1118.54 | 1420.65 | 2552.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.77 | 221.79 | 261.98 | 272.54 | 1567.86 | 0.00 | 0.00 | 0.00 |
February | 756.66 | 375.66 | 381.00 | 591.84 | 1158.00 | 0.00 | 0.00 | 0.00 |
March | 1017.40 | 420.97 | 596.43 | 860.02 | 956.26 | 0.00 | 0.00 | 0.00 |
April | 1298.10 | 643.33 | 654.77 | 1284.92 | 695.49 | 0.00 | 0.00 | 0.00 |
May | 1433.92 | 638.00 | 795.92 | 1513.00 | 554.66 | 0.00 | 0.00 | 0.00 |
June | 1856.02 | 955.11 | 900.91 | 2243.93 | 369.83 | 0.00 | 0.00 | 0.00 |
July | 1947.95 | 1101.23 | 846.72 | 2538.41 | 303.58 | 0.00 | 0.00 | 0.00 |
August | 1692.85 | 943.21 | 749.65 | 2155.74 | 339.90 | 0.00 | 0.00 | 0.00 |
September | 1197.53 | 618.16 | 579.37 | 1385.05 | 492.15 | 0.00 | 0.00 | 0.00 |
October | 859.16 | 436.27 | 422.89 | 835.95 | 705.25 | 0.00 | 0.00 | 0.00 |
November | 544.52 | 254.22 | 290.30 | 397.55 | 960.39 | 0.00 | 0.00 | 0.00 |
December | 401.62 | 172.49 | 229.12 | 215.61 | 1329.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.05 | 566.02 | 560.03 | 1194.64 | 784.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.62 | 172.49 | 229.12 | 215.61 | 303.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1947.95 | 1101.23 | 900.91 | 2538.41 | 1567.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2227.55 | 1590.96 | 636.59 | 2131.80 | 2199.91 | 0.00 | 0.00 | 0.00 |
February | 2836.75 | 2040.30 | 796.45 | 2978.31 | 1655.05 | 0.00 | 0.00 | 0.00 |
March | 2535.68 | 1423.92 | 1111.76 | 2653.28 | 1482.08 | 0.00 | 0.00 | 0.00 |
April | 2038.27 | 974.92 | 1063.35 | 2208.77 | 1115.48 | 0.00 | 0.00 | 0.00 |
May | 1810.95 | 601.47 | 1209.48 | 1989.29 | 892.19 | 0.00 | 0.00 | 0.00 |
June | 1799.36 | 524.78 | 1274.58 | 2247.54 | 620.05 | 0.00 | 0.00 | 0.00 |
July | 1939.89 | 716.59 | 1223.30 | 2704.19 | 496.14 | 0.00 | 0.00 | 0.00 |
August | 2305.43 | 1162.36 | 1143.07 | 3121.96 | 553.76 | 0.00 | 0.00 | 0.00 |
September | 2557.00 | 1566.76 | 990.24 | 3212.16 | 785.89 | 0.00 | 0.00 | 0.00 |
October | 2673.21 | 1848.49 | 824.72 | 3094.81 | 1086.35 | 0.00 | 0.00 | 0.00 |
November | 2437.17 | 1765.39 | 671.78 | 2589.50 | 1384.11 | 0.00 | 0.00 | 0.00 |
December | 2118.27 | 1529.61 | 588.67 | 2081.03 | 1862.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.38 | 1307.28 | 962.09 | 2581.37 | 1176.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1799.36 | 524.78 | 588.67 | 1989.29 | 496.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.75 | 2040.30 | 1274.58 | 3212.16 | 2199.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.19 | 176.60 | 261.60 | 236.35 | 1632.31 | 0.00 | 0.00 | 0.00 |
February | 747.93 | 367.65 | 380.28 | 595.95 | 1187.63 | 0.00 | 0.00 | 0.00 |
March | 957.17 | 350.72 | 606.45 | 792.71 | 996.42 | 0.00 | 0.00 | 0.00 |
April | 1249.59 | 553.63 | 695.96 | 1247.85 | 735.49 | 0.00 | 0.00 | 0.00 |
May | 1545.65 | 704.90 | 840.75 | 1679.23 | 587.06 | 0.00 | 0.00 | 0.00 |
June | 1681.61 | 772.43 | 909.18 | 2036.38 | 407.55 | 0.00 | 0.00 | 0.00 |
July | 1722.62 | 870.47 | 852.15 | 2265.24 | 340.98 | 0.00 | 0.00 | 0.00 |
August | 1462.74 | 717.88 | 744.86 | 1872.65 | 368.19 | 0.00 | 0.00 | 0.00 |
September | 1176.68 | 594.88 | 581.80 | 1381.92 | 524.56 | 0.00 | 0.00 | 0.00 |
October | 841.00 | 417.85 | 423.15 | 837.77 | 739.92 | 0.00 | 0.00 | 0.00 |
November | 595.35 | 295.34 | 300.01 | 485.15 | 996.56 | 0.00 | 0.00 | 0.00 |
December | 400.18 | 168.91 | 231.28 | 227.76 | 1369.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1069.68 | 499.75 | 569.93 | 1141.07 | 822.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.18 | 168.91 | 231.28 | 227.76 | 340.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1722.62 | 870.47 | 909.18 | 2265.24 | 1632.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.33 | 0.00 | 105.33 | 3.81 | 866.61 | 0.00 | 0.00 | 0.00 |
February | 148.72 | 0.00 | 148.72 | 30.15 | 639.06 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 98.80 | 509.85 | 0.00 | 0.00 | 0.00 |
April | 275.47 | 1.61 | 273.86 | 166.27 | 354.09 | 0.00 | 0.00 | 0.00 |
May | 361.76 | 21.44 | 340.32 | 291.06 | 271.08 | 0.00 | 0.00 | 0.00 |
June | 421.25 | 48.42 | 372.83 | 448.20 | 176.15 | 0.00 | 0.00 | 0.00 |
July | 384.83 | 36.04 | 348.79 | 480.99 | 148.65 | 0.00 | 0.00 | 0.00 |
August | 308.37 | 8.27 | 300.10 | 350.32 | 171.19 | 0.00 | 0.00 | 0.00 |
September | 230.95 | 0.08 | 230.86 | 204.08 | 268.21 | 0.00 | 0.00 | 0.00 |
October | 168.46 | 0.00 | 168.46 | 78.12 | 400.06 | 0.00 | 0.00 | 0.00 |
November | 114.52 | 0.00 | 114.52 | 19.39 | 559.92 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.32 | 755.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.94 | 9.70 | 228.24 | 182.06 | 425.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.32 | 148.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.25 | 48.42 | 372.83 | 480.99 | 866.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.34 | 0.00 | 105.34 | 3.81 | 866.66 | 0.00 | 0.00 | 0.00 |
February | 148.73 | 0.00 | 148.73 | 30.15 | 639.10 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 98.81 | 509.88 | 0.00 | 0.00 | 0.00 |
April | 275.48 | 1.61 | 273.87 | 166.27 | 354.12 | 0.00 | 0.00 | 0.00 |
May | 361.77 | 21.44 | 340.33 | 291.07 | 271.10 | 0.00 | 0.00 | 0.00 |
June | 421.26 | 48.42 | 372.84 | 448.21 | 176.16 | 0.00 | 0.00 | 0.00 |
July | 384.85 | 36.05 | 348.80 | 481.01 | 148.65 | 0.00 | 0.00 | 0.00 |
August | 308.38 | 8.27 | 300.11 | 350.33 | 171.20 | 0.00 | 0.00 | 0.00 |
September | 230.96 | 0.08 | 230.87 | 204.09 | 268.22 | 0.00 | 0.00 | 0.00 |
October | 168.47 | 0.00 | 168.47 | 78.12 | 400.09 | 0.00 | 0.00 | 0.00 |
November | 114.53 | 0.00 | 114.53 | 19.39 | 559.96 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.32 | 755.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.95 | 9.70 | 228.25 | 182.06 | 425.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.32 | 148.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.26 | 48.42 | 372.84 | 481.01 | 866.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.34 | 0.00 | 105.34 | 3.81 | 866.66 | 0.00 | 0.00 | 0.00 |
February | 148.73 | 0.00 | 148.73 | 30.15 | 639.10 | 0.00 | 0.00 | 0.00 |
March | 241.60 | 0.00 | 241.60 | 98.81 | 509.88 | 0.00 | 0.00 | 0.00 |
April | 275.48 | 1.61 | 273.87 | 166.27 | 354.12 | 0.00 | 0.00 | 0.00 |
May | 361.77 | 21.44 | 340.33 | 291.07 | 271.10 | 0.00 | 0.00 | 0.00 |
June | 421.26 | 48.42 | 372.84 | 448.21 | 176.16 | 0.00 | 0.00 | 0.00 |
July | 384.85 | 36.05 | 348.80 | 481.01 | 148.65 | 0.00 | 0.00 | 0.00 |
August | 308.38 | 8.27 | 300.11 | 350.33 | 171.20 | 0.00 | 0.00 | 0.00 |
September | 230.96 | 0.08 | 230.87 | 204.09 | 268.22 | 0.00 | 0.00 | 0.00 |
October | 168.47 | 0.00 | 168.47 | 78.12 | 400.09 | 0.00 | 0.00 | 0.00 |
November | 114.53 | 0.00 | 114.53 | 19.39 | 559.96 | 0.00 | 0.00 | 0.00 |
December | 88.33 | 0.00 | 88.33 | 2.32 | 755.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 237.95 | 9.70 | 228.25 | 182.06 | 425.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.33 | 0.00 | 88.33 | 2.32 | 148.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.26 | 48.42 | 372.84 | 481.01 | 866.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 465.36 | 213.35 | 252.01 | 260.45 | 1543.10 | 0.00 | 0.00 | 0.00 |
February | 727.87 | 361.37 | 366.50 | 570.14 | 1144.47 | 0.00 | 0.00 | 0.00 |
March | 978.68 | 404.95 | 573.73 | 835.83 | 945.76 | 0.00 | 0.00 | 0.00 |
April | 1248.71 | 618.85 | 629.86 | 1252.11 | 681.05 | 0.00 | 0.00 | 0.00 |
May | 1379.36 | 613.73 | 765.63 | 1472.00 | 546.10 | 0.00 | 0.00 | 0.00 |
June | 1785.40 | 918.76 | 866.64 | 2174.15 | 363.32 | 0.00 | 0.00 | 0.00 |
July | 1873.83 | 1059.32 | 814.51 | 2453.23 | 303.21 | 0.00 | 0.00 | 0.00 |
August | 1628.44 | 907.31 | 721.13 | 2082.14 | 342.26 | 0.00 | 0.00 | 0.00 |
September | 1151.96 | 594.64 | 557.33 | 1332.58 | 507.74 | 0.00 | 0.00 | 0.00 |
October | 826.47 | 419.67 | 406.80 | 791.04 | 745.83 | 0.00 | 0.00 | 0.00 |
November | 523.80 | 244.55 | 279.26 | 368.02 | 1004.72 | 0.00 | 0.00 | 0.00 |
December | 386.33 | 165.93 | 220.40 | 202.08 | 1342.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1083.20 | 544.48 | 538.73 | 1152.79 | 787.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 386.33 | 165.93 | 220.40 | 202.08 | 303.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1873.83 | 1059.32 | 866.64 | 2453.23 | 1543.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.40 | 8.44 | 9.96 | 10.30 | 61.01 | 0.00 | 0.00 | 0.00 |
February | 28.78 | 14.29 | 14.49 | 22.54 | 45.25 | 0.00 | 0.00 | 0.00 |
March | 38.70 | 16.01 | 22.68 | 33.05 | 37.39 | 0.00 | 0.00 | 0.00 |
April | 49.37 | 24.47 | 24.90 | 49.51 | 26.93 | 0.00 | 0.00 | 0.00 |
May | 54.54 | 24.27 | 30.27 | 58.20 | 21.59 | 0.00 | 0.00 | 0.00 |
June | 70.59 | 36.33 | 34.27 | 85.96 | 14.37 | 0.00 | 0.00 | 0.00 |
July | 74.09 | 41.88 | 32.20 | 97.00 | 11.99 | 0.00 | 0.00 | 0.00 |
August | 64.39 | 35.87 | 28.51 | 82.33 | 13.53 | 0.00 | 0.00 | 0.00 |
September | 45.55 | 23.51 | 22.04 | 52.69 | 20.08 | 0.00 | 0.00 | 0.00 |
October | 32.68 | 16.59 | 16.08 | 31.28 | 29.49 | 0.00 | 0.00 | 0.00 |
November | 20.71 | 9.67 | 11.04 | 14.55 | 39.73 | 0.00 | 0.00 | 0.00 |
December | 15.28 | 6.56 | 8.71 | 7.99 | 53.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.83 | 21.53 | 21.30 | 45.58 | 31.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.28 | 6.56 | 8.71 | 7.99 | 11.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.09 | 41.88 | 34.27 | 97.00 | 61.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.50 | 530.31 | 212.19 | 720.81 | 742.82 | 0.00 | 0.00 | 0.00 |
February | 945.57 | 680.09 | 265.48 | 1005.23 | 571.85 | 0.00 | 0.00 | 0.00 |
March | 845.21 | 474.63 | 370.58 | 897.57 | 510.43 | 0.00 | 0.00 | 0.00 |
April | 679.41 | 324.97 | 354.45 | 750.34 | 375.78 | 0.00 | 0.00 | 0.00 |
May | 603.64 | 200.48 | 403.16 | 679.12 | 298.10 | 0.00 | 0.00 | 0.00 |
June | 599.78 | 174.92 | 424.86 | 762.66 | 205.86 | 0.00 | 0.00 | 0.00 |
July | 646.62 | 238.86 | 407.76 | 909.55 | 169.02 | 0.00 | 0.00 | 0.00 |
August | 768.47 | 387.44 | 381.02 | 1047.70 | 192.82 | 0.00 | 0.00 | 0.00 |
September | 852.32 | 522.24 | 330.08 | 1075.61 | 283.33 | 0.00 | 0.00 | 0.00 |
October | 891.05 | 616.15 | 274.90 | 1031.35 | 402.44 | 0.00 | 0.00 | 0.00 |
November | 812.38 | 588.45 | 223.92 | 860.39 | 505.32 | 0.00 | 0.00 | 0.00 |
December | 706.08 | 509.86 | 196.22 | 695.45 | 649.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.45 | 435.75 | 320.69 | 868.62 | 408.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.78 | 174.92 | 196.22 | 679.12 | 169.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.57 | 680.09 | 424.86 | 1075.61 | 742.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.50 | 530.31 | 212.19 | 720.81 | 742.82 | 0.00 | 0.00 | 0.00 |
February | 945.57 | 680.09 | 265.48 | 1005.23 | 571.85 | 0.00 | 0.00 | 0.00 |
March | 845.21 | 474.63 | 370.58 | 897.57 | 510.43 | 0.00 | 0.00 | 0.00 |
April | 679.41 | 324.97 | 354.45 | 750.34 | 375.78 | 0.00 | 0.00 | 0.00 |
May | 603.64 | 200.48 | 403.16 | 679.12 | 298.10 | 0.00 | 0.00 | 0.00 |
June | 599.78 | 174.92 | 424.86 | 762.66 | 205.86 | 0.00 | 0.00 | 0.00 |
July | 646.62 | 238.86 | 407.76 | 909.55 | 169.02 | 0.00 | 0.00 | 0.00 |
August | 768.47 | 387.44 | 381.02 | 1047.70 | 192.82 | 0.00 | 0.00 | 0.00 |
September | 852.32 | 522.24 | 330.08 | 1075.61 | 283.33 | 0.00 | 0.00 | 0.00 |
October | 891.05 | 616.15 | 274.90 | 1031.35 | 402.44 | 0.00 | 0.00 | 0.00 |
November | 812.38 | 588.45 | 223.92 | 860.39 | 505.32 | 0.00 | 0.00 | 0.00 |
December | 706.08 | 509.86 | 196.22 | 695.45 | 649.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.45 | 435.75 | 320.69 | 868.62 | 408.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.78 | 174.92 | 196.22 | 679.12 | 169.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.57 | 680.09 | 424.86 | 1075.61 | 742.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 742.46 | 530.28 | 212.18 | 720.77 | 742.77 | 0.00 | 0.00 | 0.00 |
February | 945.51 | 680.04 | 265.46 | 1005.17 | 571.81 | 0.00 | 0.00 | 0.00 |
March | 845.16 | 474.60 | 370.56 | 897.51 | 510.40 | 0.00 | 0.00 | 0.00 |
April | 679.37 | 324.94 | 354.42 | 750.30 | 375.75 | 0.00 | 0.00 | 0.00 |
May | 603.60 | 200.47 | 403.13 | 679.08 | 298.08 | 0.00 | 0.00 | 0.00 |
June | 599.74 | 174.91 | 424.83 | 762.61 | 205.85 | 0.00 | 0.00 | 0.00 |
July | 646.58 | 238.84 | 407.74 | 909.50 | 169.01 | 0.00 | 0.00 | 0.00 |
August | 768.42 | 387.42 | 381.00 | 1047.64 | 192.81 | 0.00 | 0.00 | 0.00 |
September | 852.27 | 522.21 | 330.06 | 1075.54 | 283.31 | 0.00 | 0.00 | 0.00 |
October | 891.00 | 616.11 | 274.89 | 1031.28 | 402.42 | 0.00 | 0.00 | 0.00 |
November | 812.32 | 588.41 | 223.91 | 860.34 | 505.29 | 0.00 | 0.00 | 0.00 |
December | 706.03 | 509.83 | 196.21 | 695.41 | 649.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.40 | 435.72 | 320.67 | 868.56 | 408.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.74 | 174.91 | 196.21 | 679.08 | 169.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 945.51 | 680.04 | 424.83 | 1075.54 | 742.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 421.52 | 169.88 | 251.65 | 228.96 | 1602.29 | 0.00 | 0.00 | 0.00 |
February | 719.47 | 353.66 | 365.82 | 579.94 | 1174.89 | 0.00 | 0.00 | 0.00 |
March | 920.75 | 337.38 | 583.37 | 776.26 | 982.54 | 0.00 | 0.00 | 0.00 |
April | 1202.04 | 532.56 | 669.48 | 1220.51 | 718.27 | 0.00 | 0.00 | 0.00 |
May | 1486.84 | 678.08 | 808.76 | 1633.46 | 582.66 | 0.00 | 0.00 | 0.00 |
June | 1617.63 | 743.03 | 874.59 | 1977.26 | 401.93 | 0.00 | 0.00 | 0.00 |
July | 1657.08 | 837.34 | 819.74 | 2191.58 | 340.76 | 0.00 | 0.00 | 0.00 |
August | 1407.08 | 690.56 | 716.52 | 1810.75 | 370.60 | 0.00 | 0.00 | 0.00 |
September | 1131.91 | 572.25 | 559.66 | 1331.24 | 543.35 | 0.00 | 0.00 | 0.00 |
October | 809.00 | 401.95 | 407.06 | 795.29 | 784.53 | 0.00 | 0.00 | 0.00 |
November | 572.70 | 284.11 | 288.59 | 458.77 | 1042.54 | 0.00 | 0.00 | 0.00 |
December | 384.96 | 162.48 | 222.48 | 217.72 | 1382.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1028.98 | 480.74 | 548.25 | 1104.51 | 825.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 384.96 | 162.48 | 222.48 | 217.72 | 340.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.08 | 837.34 | 874.59 | 2191.58 | 1602.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.67 | 6.72 | 9.95 | 9.05 | 63.35 | 0.00 | 0.00 | 0.00 |
February | 28.45 | 13.98 | 14.46 | 22.93 | 46.45 | 0.00 | 0.00 | 0.00 |
March | 36.41 | 13.34 | 23.07 | 30.69 | 38.85 | 0.00 | 0.00 | 0.00 |
April | 47.53 | 21.06 | 26.47 | 48.26 | 28.40 | 0.00 | 0.00 | 0.00 |
May | 58.79 | 26.81 | 31.98 | 64.59 | 23.04 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 29.38 | 34.58 | 78.18 | 15.89 | 0.00 | 0.00 | 0.00 |
July | 65.52 | 33.11 | 32.41 | 86.65 | 13.47 | 0.00 | 0.00 | 0.00 |
August | 55.63 | 27.30 | 28.33 | 71.60 | 14.65 | 0.00 | 0.00 | 0.00 |
September | 44.75 | 22.63 | 22.13 | 52.64 | 21.48 | 0.00 | 0.00 | 0.00 |
October | 31.99 | 15.89 | 16.09 | 31.45 | 31.02 | 0.00 | 0.00 | 0.00 |
November | 22.64 | 11.23 | 11.41 | 18.14 | 41.22 | 0.00 | 0.00 | 0.00 |
December | 15.22 | 6.42 | 8.80 | 8.61 | 54.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 19.01 | 21.68 | 43.67 | 32.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.22 | 6.42 | 8.80 | 8.61 | 13.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.52 | 33.11 | 34.58 | 86.65 | 63.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.01 | 0.00 | 316.01 | 10.51 | 2634.35 | 0.00 | 0.00 | 0.00 |
February | 446.19 | 0.00 | 446.19 | 80.17 | 1964.42 | 0.00 | 0.00 | 0.00 |
March | 724.82 | 0.00 | 724.82 | 264.34 | 1592.55 | 0.00 | 0.00 | 0.00 |
April | 826.45 | 4.82 | 821.63 | 446.66 | 1145.38 | 0.00 | 0.00 | 0.00 |
May | 1085.32 | 64.31 | 1021.01 | 819.19 | 860.87 | 0.00 | 0.00 | 0.00 |
June | 1263.80 | 145.26 | 1118.54 | 1307.17 | 553.74 | 0.00 | 0.00 | 0.00 |
July | 1154.55 | 108.14 | 1046.41 | 1418.89 | 463.14 | 0.00 | 0.00 | 0.00 |
August | 925.15 | 24.80 | 900.35 | 1033.44 | 529.79 | 0.00 | 0.00 | 0.00 |
September | 692.87 | 0.25 | 692.62 | 599.24 | 816.30 | 0.00 | 0.00 | 0.00 |
October | 505.41 | 0.00 | 505.41 | 229.48 | 1195.78 | 0.00 | 0.00 | 0.00 |
November | 343.58 | 0.00 | 343.58 | 55.80 | 1673.11 | 0.00 | 0.00 | 0.00 |
December | 265.00 | 0.00 | 265.00 | 6.20 | 2264.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.86 | 29.11 | 684.75 | 525.35 | 1305.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.00 | 0.00 | 265.00 | 6.20 | 463.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.80 | 145.26 | 1118.54 | 1418.89 | 2634.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.77 | 221.79 | 261.98 | 265.57 | 1615.78 | 0.00 | 0.00 | 0.00 |
February | 756.66 | 375.66 | 381.00 | 578.18 | 1207.87 | 0.00 | 0.00 | 0.00 |
March | 1017.40 | 420.97 | 596.43 | 842.62 | 1006.79 | 0.00 | 0.00 | 0.00 |
April | 1298.10 | 643.33 | 654.77 | 1270.25 | 736.69 | 0.00 | 0.00 | 0.00 |
May | 1433.92 | 638.00 | 795.92 | 1502.93 | 582.92 | 0.00 | 0.00 | 0.00 |
June | 1856.02 | 955.11 | 900.91 | 2239.79 | 381.88 | 0.00 | 0.00 | 0.00 |
July | 1947.95 | 1101.23 | 846.72 | 2536.78 | 312.36 | 0.00 | 0.00 | 0.00 |
August | 1692.85 | 943.21 | 749.65 | 2152.34 | 352.33 | 0.00 | 0.00 | 0.00 |
September | 1197.53 | 618.16 | 579.37 | 1376.08 | 518.54 | 0.00 | 0.00 | 0.00 |
October | 859.16 | 436.27 | 422.89 | 817.45 | 755.84 | 0.00 | 0.00 | 0.00 |
November | 544.52 | 254.22 | 290.30 | 380.05 | 1027.85 | 0.00 | 0.00 | 0.00 |
December | 401.62 | 172.49 | 229.12 | 207.54 | 1389.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1126.05 | 566.02 | 560.03 | 1184.26 | 822.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 401.62 | 172.49 | 229.12 | 207.54 | 312.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1947.95 | 1101.23 | 900.91 | 2536.78 | 1615.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2227.55 | 1590.96 | 636.59 | 2116.41 | 2276.81 | 0.00 | 0.00 | 0.00 |
February | 2836.75 | 2040.30 | 796.45 | 2959.49 | 1730.84 | 0.00 | 0.00 | 0.00 |
March | 2535.68 | 1423.92 | 1111.76 | 2634.72 | 1560.12 | 0.00 | 0.00 | 0.00 |
April | 2038.27 | 974.92 | 1063.35 | 2194.80 | 1180.84 | 0.00 | 0.00 | 0.00 |
May | 1810.95 | 601.47 | 1209.48 | 1980.77 | 939.25 | 0.00 | 0.00 | 0.00 |
June | 1799.36 | 524.78 | 1274.58 | 2247.40 | 643.86 | 0.00 | 0.00 | 0.00 |
July | 1939.89 | 716.59 | 1223.30 | 2706.98 | 512.90 | 0.00 | 0.00 | 0.00 |
August | 2305.43 | 1162.36 | 1143.07 | 3123.78 | 576.11 | 0.00 | 0.00 | 0.00 |
September | 2557.00 | 1566.76 | 990.24 | 3207.00 | 828.25 | 0.00 | 0.00 | 0.00 |
October | 2673.21 | 1848.49 | 824.72 | 3076.09 | 1160.97 | 0.00 | 0.00 | 0.00 |
November | 2437.17 | 1765.39 | 671.78 | 2561.01 | 1476.52 | 0.00 | 0.00 | 0.00 |
December | 2118.27 | 1529.61 | 588.67 | 2058.42 | 1952.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.38 | 1307.28 | 962.09 | 2569.27 | 1234.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1799.36 | 524.78 | 588.67 | 1980.77 | 512.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2836.75 | 2040.30 | 1274.58 | 3207.00 | 2276.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.19 | 176.60 | 261.60 | 232.28 | 1683.82 | 0.00 | 0.00 | 0.00 |
February | 747.93 | 367.65 | 380.28 | 587.06 | 1240.57 | 0.00 | 0.00 | 0.00 |
March | 957.17 | 350.72 | 606.45 | 781.00 | 1049.38 | 0.00 | 0.00 | 0.00 |
April | 1249.59 | 553.63 | 695.96 | 1236.59 | 779.36 | 0.00 | 0.00 | 0.00 |
May | 1545.65 | 704.90 | 840.75 | 1672.95 | 618.21 | 0.00 | 0.00 | 0.00 |
June | 1681.61 | 772.43 | 909.18 | 2036.33 | 423.27 | 0.00 | 0.00 | 0.00 |
July | 1722.62 | 870.47 | 852.15 | 2266.95 | 352.14 | 0.00 | 0.00 | 0.00 |
August | 1462.74 | 717.88 | 744.86 | 1872.77 | 383.09 | 0.00 | 0.00 | 0.00 |
September | 1176.68 | 594.88 | 581.80 | 1376.57 | 554.95 | 0.00 | 0.00 | 0.00 |
October | 841.00 | 417.85 | 423.15 | 823.82 | 795.13 | 0.00 | 0.00 | 0.00 |
November | 595.35 | 295.34 | 300.01 | 473.08 | 1066.29 | 0.00 | 0.00 | 0.00 |
December | 400.18 | 168.91 | 231.28 | 221.91 | 1432.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1069.68 | 499.75 | 569.93 | 1134.62 | 863.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 400.18 | 168.91 | 231.28 | 221.91 | 352.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1722.62 | 870.47 | 909.18 | 2266.95 | 1683.82 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846413E+09 | 0.00 | 0.846413E+09 | 37298374.86 | 0.683642E+10 |
February | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.219124E+09 | 0.455407E+10 |
March | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.756443E+09 | 0.404944E+10 |
April | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.120476E+10 | 0.279250E+10 |
May | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.223499E+10 | 0.218627E+10 |
June | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.340314E+10 | 0.138697E+10 |
July | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.380508E+10 | 0.120548E+10 |
August | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.277765E+10 | 0.136400E+10 |
September | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.158062E+10 | 0.199509E+10 |
October | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.672928E+09 | 0.297235E+10 |
November | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.172808E+09 | 0.404715E+10 |
December | 0.709765E+09 | 0.00 | 0.709765E+09 | 20424101.42 | 0.580173E+10 |
Annual Sum or Average | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.168853E+11 | 0.391915E+11 |
Minimum of Months | 0.709765E+09 | 0.00 | 0.709765E+09 | 20424101.42 | 0.120548E+10 |
Maximum of Months | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.380508E+10 | 0.683642E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.729968E+09 | 0.419937E+10 |
February | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.143177E+10 | 0.280143E+10 |
March | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.230348E+10 | 0.256126E+10 |
April | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.333052E+10 | 0.180270E+10 |
May | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.405242E+10 | 0.148560E+10 |
June | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.581628E+10 | 0.958597E+09 |
July | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.679888E+10 | 0.813117E+09 |
August | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.577393E+10 | 0.910394E+09 |
September | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.359004E+10 | 0.127564E+10 |
October | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.223901E+10 | 0.188894E+10 |
November | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.103044E+10 | 0.248932E+10 |
December | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.577496E+09 | 0.356101E+10 |
Annual Sum or Average | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.376742E+11 | 0.247474E+11 |
Minimum of Months | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.577496E+09 | 0.813117E+09 |
Maximum of Months | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.679888E+10 | 0.419937E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.570982E+10 | 0.589223E+10 |
February | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.720513E+10 | 0.400390E+10 |
March | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.710656E+10 | 0.396961E+10 |
April | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.572514E+10 | 0.289133E+10 |
May | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.532812E+10 | 0.238964E+10 |
June | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.582562E+10 | 0.160717E+10 |
July | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.724291E+10 | 0.132886E+10 |
August | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.836186E+10 | 0.148318E+10 |
September | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.832593E+10 | 0.203702E+10 |
October | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.828913E+10 | 0.290967E+10 |
November | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.671199E+10 | 0.358761E+10 |
December | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.557383E+10 | 0.498875E+10 |
Annual Sum or Average | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.814060E+11 | 0.370890E+11 |
Minimum of Months | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.532812E+10 | 0.132886E+10 |
Maximum of Months | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.836186E+10 | 0.589223E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.633043E+09 | 0.437198E+10 |
February | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.144172E+10 | 0.287311E+10 |
March | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.212319E+10 | 0.266880E+10 |
April | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.323443E+10 | 0.190640E+10 |
May | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.449765E+10 | 0.157238E+10 |
June | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.527829E+10 | 0.105637E+10 |
July | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.606722E+10 | 0.913274E+09 |
August | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.501570E+10 | 0.986159E+09 |
September | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.358194E+10 | 0.135966E+10 |
October | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.224390E+10 | 0.198181E+10 |
November | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.125752E+10 | 0.258307E+10 |
December | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.610032E+09 | 0.366930E+10 |
Annual Sum or Average | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.359846E+11 | 0.259423E+11 |
Minimum of Months | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.610032E+09 | 0.913274E+09 |
Maximum of Months | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.606722E+10 | 0.437198E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282124E+09 | 0.00 | 0.282124E+09 | 10212502.77 | 0.232112E+10 |
February | 0.359792E+09 | 0.00 | 0.359792E+09 | 72937997.82 | 0.154600E+10 |
March | 0.647089E+09 | 0.00 | 0.647089E+09 | 0.264639E+09 | 0.136558E+10 |
April | 0.714018E+09 | 4166847.54 | 0.709851E+09 | 0.430962E+09 | 0.917814E+09 |
May | 0.968932E+09 | 57415206.47 | 0.911517E+09 | 0.779585E+09 | 0.726069E+09 |
June | 0.109187E+10 | 0.125501E+09 | 0.966370E+09 | 0.116173E+10 | 0.456591E+09 |
July | 0.103073E+10 | 96540600.17 | 0.934193E+09 | 0.128828E+10 | 0.398134E+09 |
August | 0.825932E+09 | 22138846.40 | 0.803794E+09 | 0.938286E+09 | 0.458517E+09 |
September | 0.598612E+09 | 214814.61 | 0.598398E+09 | 0.528981E+09 | 0.695195E+09 |
October | 0.451208E+09 | 0.00 | 0.451208E+09 | 0.209229E+09 | 0.107153E+10 |
November | 0.296841E+09 | 0.00 | 0.296841E+09 | 50258490.02 | 0.145132E+10 |
December | 0.236577E+09 | 0.00 | 0.236577E+09 | 6204463.18 | 0.202276E+10 |
Annual Sum or Average | 0.750373E+10 | 0.305978E+09 | 0.719775E+10 | 0.574130E+10 | 0.134306E+11 |
Minimum of Months | 0.236577E+09 | 0.00 | 0.236577E+09 | 6204463.18 | 0.398134E+09 |
Maximum of Months | 0.109187E+10 | 0.125501E+09 | 0.966370E+09 | 0.128828E+10 | 0.232112E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282135E+09 | 0.00 | 0.282135E+09 | 10211900.51 | 0.232127E+10 |
February | 0.359807E+09 | 0.00 | 0.359807E+09 | 72938257.38 | 0.154610E+10 |
March | 0.647114E+09 | 0.00 | 0.647114E+09 | 0.264641E+09 | 0.136567E+10 |
April | 0.714046E+09 | 4166959.55 | 0.709879E+09 | 0.430973E+09 | 0.917873E+09 |
May | 0.968970E+09 | 57416749.81 | 0.911553E+09 | 0.779607E+09 | 0.726115E+09 |
June | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.116177E+10 | 0.456618E+09 |
July | 0.103078E+10 | 96543195.21 | 0.934233E+09 | 0.128833E+10 | 0.398156E+09 |
August | 0.825967E+09 | 22139441.50 | 0.803827E+09 | 0.938325E+09 | 0.458544E+09 |
September | 0.598637E+09 | 214820.38 | 0.598422E+09 | 0.529001E+09 | 0.695237E+09 |
October | 0.451226E+09 | 0.00 | 0.451226E+09 | 0.209233E+09 | 0.107159E+10 |
November | 0.296852E+09 | 0.00 | 0.296852E+09 | 50258327.06 | 0.145142E+10 |
December | 0.236586E+09 | 0.00 | 0.236586E+09 | 6204096.62 | 0.202289E+10 |
Annual Sum or Average | 0.750403E+10 | 0.305986E+09 | 0.719805E+10 | 0.574149E+10 | 0.134315E+11 |
Minimum of Months | 0.236586E+09 | 0.00 | 0.236586E+09 | 6204096.62 | 0.398156E+09 |
Maximum of Months | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.128833E+10 | 0.232127E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282135E+09 | 0.00 | 0.282135E+09 | 10211900.51 | 0.232127E+10 |
February | 0.359807E+09 | 0.00 | 0.359807E+09 | 72938257.38 | 0.154610E+10 |
March | 0.647114E+09 | 0.00 | 0.647114E+09 | 0.264641E+09 | 0.136567E+10 |
April | 0.714046E+09 | 4166959.55 | 0.709879E+09 | 0.430973E+09 | 0.917873E+09 |
May | 0.968970E+09 | 57416749.81 | 0.911553E+09 | 0.779607E+09 | 0.726115E+09 |
June | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.116177E+10 | 0.456618E+09 |
July | 0.103078E+10 | 96543195.21 | 0.934233E+09 | 0.128833E+10 | 0.398156E+09 |
August | 0.825967E+09 | 22139441.50 | 0.803827E+09 | 0.938325E+09 | 0.458544E+09 |
September | 0.598637E+09 | 214820.38 | 0.598422E+09 | 0.529001E+09 | 0.695237E+09 |
October | 0.451226E+09 | 0.00 | 0.451226E+09 | 0.209233E+09 | 0.107159E+10 |
November | 0.296852E+09 | 0.00 | 0.296852E+09 | 50258327.06 | 0.145142E+10 |
December | 0.236586E+09 | 0.00 | 0.236586E+09 | 6204096.62 | 0.202289E+10 |
Annual Sum or Average | 0.750403E+10 | 0.305986E+09 | 0.719805E+10 | 0.574149E+10 | 0.134315E+11 |
Minimum of Months | 0.236586E+09 | 0.00 | 0.236586E+09 | 6204096.62 | 0.398156E+09 |
Maximum of Months | 0.109191E+10 | 0.125505E+09 | 0.966410E+09 | 0.128833E+10 | 0.232127E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124643E+10 | 0.571434E+09 | 0.674992E+09 | 0.697591E+09 | 0.413305E+10 |
February | 0.176086E+10 | 0.874221E+09 | 0.886637E+09 | 0.137929E+10 | 0.276871E+10 |
March | 0.262131E+10 | 0.108462E+10 | 0.153669E+10 | 0.223868E+10 | 0.253313E+10 |
April | 0.323664E+10 | 0.160405E+10 | 0.163259E+10 | 0.324548E+10 | 0.176527E+10 |
May | 0.369447E+10 | 0.164380E+10 | 0.205067E+10 | 0.394260E+10 | 0.146268E+10 |
June | 0.462776E+10 | 0.238143E+10 | 0.224633E+10 | 0.563539E+10 | 0.941723E+09 |
July | 0.501886E+10 | 0.283728E+10 | 0.218157E+10 | 0.657074E+10 | 0.812108E+09 |
August | 0.436161E+10 | 0.243015E+10 | 0.193147E+10 | 0.557679E+10 | 0.916721E+09 |
September | 0.298588E+10 | 0.154130E+10 | 0.144459E+10 | 0.345406E+10 | 0.131607E+10 |
October | 0.221362E+10 | 0.112404E+10 | 0.108958E+10 | 0.211873E+10 | 0.199763E+10 |
November | 0.135769E+10 | 0.633862E+09 | 0.723832E+09 | 0.953906E+09 | 0.260424E+10 |
December | 0.103476E+10 | 0.444429E+09 | 0.590328E+09 | 0.541250E+09 | 0.359519E+10 |
Annual Sum or Average | 0.341599E+11 | 0.171706E+11 | 0.169893E+11 | 0.363545E+11 | 0.248465E+11 |
Minimum of Months | 0.103476E+10 | 0.444429E+09 | 0.590328E+09 | 0.541250E+09 | 0.812108E+09 |
Maximum of Months | 0.501886E+10 | 0.283728E+10 | 0.224633E+10 | 0.657074E+10 | 0.413305E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49282560.53 | 22593984.42 | 26688576.11 | 27582102.80 | 0.163417E+09 |
February | 69622741.96 | 34565919.09 | 35056822.87 | 54535831.31 | 0.109472E+09 |
March | 0.103644E+09 | 42884921.75 | 60759293.88 | 88515248.52 | 0.100157E+09 |
April | 0.127974E+09 | 63422758.57 | 64551256.57 | 0.128323E+09 | 69797309.81 |
May | 0.146076E+09 | 64994474.23 | 81081693.83 | 0.155887E+09 | 57833092.50 |
June | 0.182977E+09 | 94159662.78 | 88817684.97 | 0.222818E+09 | 37234870.69 |
July | 0.198441E+09 | 0.112184E+09 | 86257492.47 | 0.259801E+09 | 32110004.09 |
August | 0.172454E+09 | 96085787.95 | 76368419.92 | 0.220501E+09 | 36246314.31 |
September | 0.118059E+09 | 60941443.07 | 57117668.76 | 0.136570E+09 | 52036074.58 |
October | 87524590.74 | 44443476.32 | 43081114.42 | 83772687.66 | 78984558.87 |
November | 53681997.10 | 25062350.78 | 28619646.32 | 37716569.95 | 0.102969E+09 |
December | 40913366.01 | 17572326.64 | 23341039.37 | 21400551.10 | 0.142151E+09 |
Annual Sum or Average | 0.135065E+10 | 0.678911E+09 | 0.671741E+09 | 0.143742E+10 | 0.982409E+09 |
Minimum of Months | 40913366.01 | 17572326.64 | 23341039.37 | 21400551.10 | 32110004.09 |
Maximum of Months | 0.198441E+09 | 0.112184E+09 | 88817684.97 | 0.259801E+09 | 0.163417E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198872E+10 | 0.142038E+10 | 0.568338E+09 | 0.193063E+10 | 0.198957E+10 |
February | 0.228751E+10 | 0.164526E+10 | 0.642252E+09 | 0.243186E+10 | 0.138341E+10 |
March | 0.226382E+10 | 0.127125E+10 | 0.992567E+09 | 0.240406E+10 | 0.136714E+10 |
April | 0.176103E+10 | 0.842310E+09 | 0.918725E+09 | 0.194489E+10 | 0.974012E+09 |
May | 0.161679E+10 | 0.536977E+09 | 0.107982E+10 | 0.181897E+10 | 0.798424E+09 |
June | 0.155463E+10 | 0.453399E+09 | 0.110123E+10 | 0.197681E+10 | 0.533602E+09 |
July | 0.173191E+10 | 0.639757E+09 | 0.109215E+10 | 0.243615E+10 | 0.452693E+09 |
August | 0.205826E+10 | 0.103773E+10 | 0.102053E+10 | 0.280617E+10 | 0.516443E+09 |
September | 0.220921E+10 | 0.135365E+10 | 0.855561E+09 | 0.278798E+10 | 0.734395E+09 |
October | 0.238660E+10 | 0.165030E+10 | 0.736299E+09 | 0.276236E+10 | 0.107790E+10 |
November | 0.210568E+10 | 0.152527E+10 | 0.580412E+09 | 0.223014E+10 | 0.130979E+10 |
December | 0.189116E+10 | 0.136561E+10 | 0.525553E+09 | 0.186270E+10 | 0.173845E+10 |
Annual Sum or Average | 0.238553E+11 | 0.137419E+11 | 0.101134E+11 | 0.273927E+11 | 0.128758E+11 |
Minimum of Months | 0.155463E+10 | 0.453399E+09 | 0.525553E+09 | 0.181897E+10 | 0.452693E+09 |
Maximum of Months | 0.238660E+10 | 0.165030E+10 | 0.110123E+10 | 0.280617E+10 | 0.198957E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198872E+10 | 0.142038E+10 | 0.568338E+09 | 0.193063E+10 | 0.198957E+10 |
February | 0.228751E+10 | 0.164526E+10 | 0.642252E+09 | 0.243186E+10 | 0.138341E+10 |
March | 0.226382E+10 | 0.127125E+10 | 0.992567E+09 | 0.240406E+10 | 0.136714E+10 |
April | 0.176103E+10 | 0.842310E+09 | 0.918725E+09 | 0.194489E+10 | 0.974012E+09 |
May | 0.161679E+10 | 0.536977E+09 | 0.107982E+10 | 0.181897E+10 | 0.798424E+09 |
June | 0.155463E+10 | 0.453399E+09 | 0.110123E+10 | 0.197681E+10 | 0.533602E+09 |
July | 0.173191E+10 | 0.639757E+09 | 0.109215E+10 | 0.243615E+10 | 0.452693E+09 |
August | 0.205826E+10 | 0.103773E+10 | 0.102053E+10 | 0.280617E+10 | 0.516443E+09 |
September | 0.220921E+10 | 0.135365E+10 | 0.855561E+09 | 0.278798E+10 | 0.734395E+09 |
October | 0.238660E+10 | 0.165030E+10 | 0.736299E+09 | 0.276236E+10 | 0.107790E+10 |
November | 0.210568E+10 | 0.152527E+10 | 0.580412E+09 | 0.223014E+10 | 0.130979E+10 |
December | 0.189116E+10 | 0.136561E+10 | 0.525553E+09 | 0.186270E+10 | 0.173845E+10 |
Annual Sum or Average | 0.238553E+11 | 0.137419E+11 | 0.101134E+11 | 0.273927E+11 | 0.128758E+11 |
Minimum of Months | 0.155463E+10 | 0.453399E+09 | 0.525553E+09 | 0.181897E+10 | 0.452693E+09 |
Maximum of Months | 0.238660E+10 | 0.165030E+10 | 0.110123E+10 | 0.280617E+10 | 0.198957E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198859E+10 | 0.142029E+10 | 0.568302E+09 | 0.193051E+10 | 0.198944E+10 |
February | 0.228737E+10 | 0.164516E+10 | 0.642211E+09 | 0.243171E+10 | 0.138332E+10 |
March | 0.226368E+10 | 0.127117E+10 | 0.992505E+09 | 0.240390E+10 | 0.136706E+10 |
April | 0.176092E+10 | 0.842257E+09 | 0.918667E+09 | 0.194477E+10 | 0.973950E+09 |
May | 0.161669E+10 | 0.536943E+09 | 0.107975E+10 | 0.181885E+10 | 0.798373E+09 |
June | 0.155453E+10 | 0.453371E+09 | 0.110116E+10 | 0.197668E+10 | 0.533568E+09 |
July | 0.173180E+10 | 0.639717E+09 | 0.109209E+10 | 0.243600E+10 | 0.452664E+09 |
August | 0.205813E+10 | 0.103767E+10 | 0.102046E+10 | 0.280599E+10 | 0.516410E+09 |
September | 0.220907E+10 | 0.135356E+10 | 0.855507E+09 | 0.278780E+10 | 0.734348E+09 |
October | 0.238644E+10 | 0.165019E+10 | 0.736253E+09 | 0.276219E+10 | 0.107783E+10 |
November | 0.210554E+10 | 0.152517E+10 | 0.580375E+09 | 0.222999E+10 | 0.130971E+10 |
December | 0.189104E+10 | 0.136552E+10 | 0.525520E+09 | 0.186259E+10 | 0.173834E+10 |
Annual Sum or Average | 0.238538E+11 | 0.137410E+11 | 0.101128E+11 | 0.273910E+11 | 0.128750E+11 |
Minimum of Months | 0.155453E+10 | 0.453371E+09 | 0.525520E+09 | 0.181885E+10 | 0.452664E+09 |
Maximum of Months | 0.238644E+10 | 0.165019E+10 | 0.110116E+10 | 0.280599E+10 | 0.198944E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.112900E+10 | 0.454994E+09 | 0.674006E+09 | 0.613244E+09 | 0.429156E+10 |
February | 0.174055E+10 | 0.855565E+09 | 0.884982E+09 | 0.140300E+10 | 0.284230E+10 |
March | 0.246614E+10 | 0.903626E+09 | 0.156251E+10 | 0.207914E+10 | 0.263163E+10 |
April | 0.311570E+10 | 0.138039E+10 | 0.173530E+10 | 0.316357E+10 | 0.186176E+10 |
May | 0.398236E+10 | 0.181616E+10 | 0.216619E+10 | 0.437507E+10 | 0.156059E+10 |
June | 0.419289E+10 | 0.192594E+10 | 0.226695E+10 | 0.512506E+10 | 0.104179E+10 |
July | 0.443832E+10 | 0.224274E+10 | 0.219558E+10 | 0.586994E+10 | 0.912695E+09 |
August | 0.376873E+10 | 0.184961E+10 | 0.191912E+10 | 0.484992E+10 | 0.992617E+09 |
September | 0.293391E+10 | 0.148326E+10 | 0.145065E+10 | 0.345058E+10 | 0.140837E+10 |
October | 0.216684E+10 | 0.107658E+10 | 0.109026E+10 | 0.213011E+10 | 0.210128E+10 |
November | 0.148443E+10 | 0.736404E+09 | 0.748030E+09 | 0.118914E+10 | 0.270227E+10 |
December | 0.103107E+10 | 0.435185E+09 | 0.595886E+09 | 0.583134E+09 | 0.370168E+10 |
Annual Sum or Average | 0.324499E+11 | 0.151605E+11 | 0.172895E+11 | 0.348319E+11 | 0.260486E+11 |
Minimum of Months | 0.103107E+10 | 0.435185E+09 | 0.595886E+09 | 0.583134E+09 | 0.912695E+09 |
Maximum of Months | 0.443832E+10 | 0.224274E+10 | 0.226695E+10 | 0.586994E+10 | 0.429156E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44639550.14 | 17990008.39 | 26649541.75 | 24247018.10 | 0.169685E+09 |
February | 68819454.54 | 33828143.04 | 34991311.50 | 55473205.77 | 0.112382E+09 |
March | 97508508.38 | 35728456.44 | 61780051.94 | 82207065.67 | 0.104052E+09 |
April | 0.123191E+09 | 54579328.96 | 68612164.61 | 0.125084E+09 | 73612326.23 |
May | 0.157458E+09 | 71809164.42 | 85649193.40 | 0.172986E+09 | 61704489.10 |
June | 0.165783E+09 | 76149843.14 | 89632786.20 | 0.202640E+09 | 41191473.69 |
July | 0.175487E+09 | 88675655.80 | 86811074.97 | 0.232091E+09 | 36087105.23 |
August | 0.149012E+09 | 73131587.33 | 75880294.79 | 0.191761E+09 | 39247182.72 |
September | 0.116004E+09 | 58646641.15 | 57357250.15 | 0.136433E+09 | 55685801.84 |
October | 85674584.70 | 42566934.75 | 43107649.96 | 84222380.30 | 83082733.71 |
November | 58692998.15 | 29116645.43 | 29576352.72 | 47017381.31 | 0.106845E+09 |
December | 40767505.90 | 17206757.42 | 23560748.48 | 23056458.27 | 0.146361E+09 |
Annual Sum or Average | 0.128304E+10 | 0.599429E+09 | 0.683608E+09 | 0.137722E+10 | 0.102994E+10 |
Minimum of Months | 40767505.90 | 17206757.42 | 23560748.48 | 23056458.27 | 36087105.23 |
Maximum of Months | 0.175487E+09 | 88675655.80 | 89632786.20 | 0.232091E+09 | 0.169685E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846413E+09 | 0.00 | 0.846413E+09 | 28141540.10 | 0.705584E+10 |
February | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.193942E+09 | 0.475232E+10 |
March | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.708002E+09 | 0.426548E+10 |
April | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.115774E+10 | 0.296884E+10 |
May | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.219412E+10 | 0.230574E+10 |
June | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.338817E+10 | 0.143529E+10 |
July | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.380034E+10 | 0.124047E+10 |
August | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.276797E+10 | 0.141900E+10 |
September | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.155323E+10 | 0.211584E+10 |
October | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.614628E+09 | 0.320278E+10 |
November | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.144628E+09 | 0.433671E+10 |
December | 0.709765E+09 | 0.00 | 0.709765E+09 | 16593791.03 | 0.606623E+10 |
Annual Sum or Average | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.165675E+11 | 0.411645E+11 |
Minimum of Months | 0.709765E+09 | 0.00 | 0.709765E+09 | 16593791.03 | 0.124047E+10 |
Maximum of Months | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.380034E+10 | 0.705584E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.711298E+09 | 0.432772E+10 |
February | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.139873E+10 | 0.292208E+10 |
March | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.225687E+10 | 0.269659E+10 |
April | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.329249E+10 | 0.190949E+10 |
May | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.402544E+10 | 0.156130E+10 |
June | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.580553E+10 | 0.989841E+09 |
July | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.679451E+10 | 0.836632E+09 |
August | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.576481E+10 | 0.943682E+09 |
September | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.356680E+10 | 0.134405E+10 |
October | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.218946E+10 | 0.202444E+10 |
November | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.985092E+09 | 0.266418E+10 |
December | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.555873E+09 | 0.372215E+10 |
Annual Sum or Average | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.373469E+11 | 0.259422E+11 |
Minimum of Months | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.555873E+09 | 0.836632E+09 |
Maximum of Months | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.679451E+10 | 0.432772E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.566859E+10 | 0.609820E+10 |
February | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.715960E+10 | 0.418724E+10 |
March | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.705683E+10 | 0.417863E+10 |
April | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.568891E+10 | 0.306075E+10 |
May | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.530529E+10 | 0.251568E+10 |
June | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.582527E+10 | 0.166889E+10 |
July | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.725036E+10 | 0.137375E+10 |
August | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.836673E+10 | 0.154305E+10 |
September | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.831254E+10 | 0.214683E+10 |
October | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.823899E+10 | 0.310954E+10 |
November | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.663815E+10 | 0.382713E+10 |
December | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.551328E+10 | 0.523014E+10 |
Annual Sum or Average | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.810245E+11 | 0.389398E+11 |
Minimum of Months | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.530529E+10 | 0.137375E+10 |
Maximum of Months | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.836673E+10 | 0.609820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.622142E+09 | 0.450994E+10 |
February | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.142023E+10 | 0.300119E+10 |
March | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.209183E+10 | 0.281065E+10 |
April | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.320525E+10 | 0.202010E+10 |
May | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.448084E+10 | 0.165582E+10 |
June | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.527817E+10 | 0.109712E+10 |
July | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.607179E+10 | 0.943163E+09 |
August | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.501602E+10 | 0.102607E+10 |
September | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.356808E+10 | 0.143843E+10 |
October | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.220653E+10 | 0.212968E+10 |
November | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.122621E+10 | 0.276383E+10 |
December | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.594362E+09 | 0.383555E+10 |
Annual Sum or Average | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.357814E+11 | 0.272315E+11 |
Minimum of Months | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.594362E+09 | 0.943163E+09 |
Maximum of Months | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.607179E+10 | 0.450994E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.93 | 2552.43 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 90.58 | 1882.47 | 446.19 | 0.00 | 446.19 | 0.00 | 0.00 |
March | 282.42 | 1511.89 | 724.82 | 0.00 | 724.82 | 0.00 | 0.00 |
April | 464.80 | 1077.35 | 826.45 | 4.82 | 821.63 | 0.00 | 0.00 |
May | 834.45 | 816.26 | 1085.32 | 64.31 | 1021.01 | 0.00 | 0.00 |
June | 1312.94 | 535.10 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
July | 1420.65 | 450.08 | 1154.55 | 108.14 | 1046.41 | 0.00 | 0.00 |
August | 1037.06 | 509.26 | 925.15 | 24.80 | 900.35 | 0.00 | 0.00 |
September | 609.81 | 769.71 | 692.87 | 0.25 | 692.62 | 0.00 | 0.00 |
October | 251.24 | 1109.75 | 505.41 | 0.00 | 505.41 | 0.00 | 0.00 |
November | 66.67 | 1561.40 | 343.58 | 0.00 | 343.58 | 0.00 | 0.00 |
December | 7.63 | 2166.12 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Annual Sum or Average | 535.43 | 1242.75 | 713.86 | 29.11 | 684.75 | 0.00 | 0.00 |
Minimum of Months | 7.63 | 450.08 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Maximum of Months | 1420.65 | 2552.43 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.54 | 1567.86 | 483.77 | 221.79 | 261.98 | 0.00 | 0.00 |
February | 591.84 | 1158.00 | 756.66 | 375.66 | 381.00 | 0.00 | 0.00 |
March | 860.02 | 956.26 | 1017.40 | 420.97 | 596.43 | 0.00 | 0.00 |
April | 1284.92 | 695.49 | 1298.10 | 643.33 | 654.77 | 0.00 | 0.00 |
May | 1513.00 | 554.66 | 1433.92 | 638.00 | 795.92 | 0.00 | 0.00 |
June | 2243.93 | 369.83 | 1856.02 | 955.11 | 900.91 | 0.00 | 0.00 |
July | 2538.41 | 303.58 | 1947.95 | 1101.23 | 846.72 | 0.00 | 0.00 |
August | 2155.74 | 339.90 | 1692.85 | 943.21 | 749.65 | 0.00 | 0.00 |
September | 1385.05 | 492.15 | 1197.53 | 618.16 | 579.37 | 0.00 | 0.00 |
October | 835.95 | 705.25 | 859.16 | 436.27 | 422.89 | 0.00 | 0.00 |
November | 397.55 | 960.39 | 544.52 | 254.22 | 290.30 | 0.00 | 0.00 |
December | 215.61 | 1329.53 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1194.64 | 784.73 | 1126.05 | 566.02 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 215.61 | 303.58 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2538.41 | 1567.86 | 1947.95 | 1101.23 | 900.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2131.80 | 2199.91 | 2227.55 | 1590.96 | 636.59 | 0.00 | 0.00 |
February | 2978.31 | 1655.05 | 2836.75 | 2040.30 | 796.45 | 0.00 | 0.00 |
March | 2653.28 | 1482.08 | 2535.68 | 1423.92 | 1111.76 | 0.00 | 0.00 |
April | 2208.77 | 1115.48 | 2038.27 | 974.92 | 1063.35 | 0.00 | 0.00 |
May | 1989.29 | 892.19 | 1810.95 | 601.47 | 1209.48 | 0.00 | 0.00 |
June | 2247.54 | 620.05 | 1799.36 | 524.78 | 1274.58 | 0.00 | 0.00 |
July | 2704.19 | 496.14 | 1939.89 | 716.59 | 1223.30 | 0.00 | 0.00 |
August | 3121.96 | 553.76 | 2305.43 | 1162.36 | 1143.07 | 0.00 | 0.00 |
September | 3212.16 | 785.89 | 2557.00 | 1566.76 | 990.24 | 0.00 | 0.00 |
October | 3094.81 | 1086.35 | 2673.21 | 1848.49 | 824.72 | 0.00 | 0.00 |
November | 2589.50 | 1384.11 | 2437.17 | 1765.39 | 671.78 | 0.00 | 0.00 |
December | 2081.03 | 1862.59 | 2118.27 | 1529.61 | 588.67 | 0.00 | 0.00 |
Annual Sum or Average | 2581.37 | 1176.08 | 2269.38 | 1307.28 | 962.09 | 0.00 | 0.00 |
Minimum of Months | 1989.29 | 496.14 | 1799.36 | 524.78 | 588.67 | 0.00 | 0.00 |
Maximum of Months | 3212.16 | 2199.91 | 2836.75 | 2040.30 | 1274.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.35 | 1632.31 | 438.19 | 176.60 | 261.60 | 0.00 | 0.00 |
February | 595.95 | 1187.63 | 747.93 | 367.65 | 380.28 | 0.00 | 0.00 |
March | 792.71 | 996.42 | 957.17 | 350.72 | 606.45 | 0.00 | 0.00 |
April | 1247.85 | 735.49 | 1249.59 | 553.63 | 695.96 | 0.00 | 0.00 |
May | 1679.23 | 587.06 | 1545.65 | 704.90 | 840.75 | 0.00 | 0.00 |
June | 2036.38 | 407.55 | 1681.61 | 772.43 | 909.18 | 0.00 | 0.00 |
July | 2265.24 | 340.98 | 1722.62 | 870.47 | 852.15 | 0.00 | 0.00 |
August | 1872.65 | 368.19 | 1462.74 | 717.88 | 744.86 | 0.00 | 0.00 |
September | 1381.92 | 524.56 | 1176.68 | 594.88 | 581.80 | 0.00 | 0.00 |
October | 837.77 | 739.92 | 841.00 | 417.85 | 423.15 | 0.00 | 0.00 |
November | 485.15 | 996.56 | 595.35 | 295.34 | 300.01 | 0.00 | 0.00 |
December | 227.76 | 1369.96 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1141.07 | 822.63 | 1069.68 | 499.75 | 569.93 | 0.00 | 0.00 |
Minimum of Months | 227.76 | 340.98 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2265.24 | 1632.31 | 1722.62 | 870.47 | 909.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.44 | 2599.94 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 90.45 | 1917.25 | 446.18 | 0.00 | 446.18 | 0.00 | 0.00 |
March | 296.42 | 1529.61 | 724.80 | 0.00 | 724.80 | 0.00 | 0.00 |
April | 498.81 | 1062.33 | 826.43 | 4.82 | 821.61 | 0.00 | 0.00 |
May | 873.21 | 813.28 | 1085.30 | 64.31 | 1020.99 | 0.00 | 0.00 |
June | 1344.63 | 528.48 | 1263.77 | 145.26 | 1118.51 | 0.00 | 0.00 |
July | 1443.00 | 445.95 | 1154.53 | 108.13 | 1046.39 | 0.00 | 0.00 |
August | 1050.98 | 513.59 | 925.13 | 24.80 | 900.33 | 0.00 | 0.00 |
September | 612.26 | 804.66 | 692.86 | 0.25 | 692.61 | 0.00 | 0.00 |
October | 234.35 | 1200.24 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
November | 58.17 | 1679.84 | 343.57 | 0.00 | 343.57 | 0.00 | 0.00 |
December | 6.95 | 2265.73 | 264.99 | 0.00 | 264.99 | 0.00 | 0.00 |
Annual Sum or Average | 546.18 | 1277.70 | 713.84 | 29.11 | 684.74 | 0.00 | 0.00 |
Minimum of Months | 6.95 | 445.95 | 264.99 | 0.00 | 264.99 | 0.00 | 0.00 |
Maximum of Months | 1443.00 | 2599.94 | 1263.77 | 145.26 | 1118.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 270.75 | 1604.12 | 483.76 | 221.78 | 261.98 | 0.00 | 0.00 |
February | 592.69 | 1189.72 | 756.65 | 375.66 | 380.99 | 0.00 | 0.00 |
March | 868.87 | 983.16 | 1017.38 | 420.96 | 596.42 | 0.00 | 0.00 |
April | 1301.62 | 707.97 | 1298.08 | 643.32 | 654.76 | 0.00 | 0.00 |
May | 1530.20 | 567.69 | 1433.90 | 637.99 | 795.91 | 0.00 | 0.00 |
June | 2260.11 | 377.68 | 1855.99 | 955.09 | 900.90 | 0.00 | 0.00 |
July | 2550.23 | 315.19 | 1947.92 | 1101.21 | 846.71 | 0.00 | 0.00 |
August | 2164.46 | 355.80 | 1692.83 | 943.19 | 749.64 | 0.00 | 0.00 |
September | 1385.27 | 527.82 | 1197.51 | 618.15 | 579.36 | 0.00 | 0.00 |
October | 822.32 | 775.32 | 859.15 | 436.26 | 422.89 | 0.00 | 0.00 |
November | 382.57 | 1044.45 | 544.51 | 254.21 | 290.30 | 0.00 | 0.00 |
December | 210.07 | 1395.36 | 401.61 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1198.37 | 819.03 | 1126.03 | 566.00 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 210.07 | 315.19 | 401.61 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2550.23 | 1604.12 | 1947.92 | 1101.21 | 900.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2162.40 | 2228.41 | 2227.46 | 1590.89 | 636.57 | 0.00 | 0.00 |
February | 3015.64 | 1715.50 | 2836.64 | 2040.21 | 796.43 | 0.00 | 0.00 |
March | 2692.66 | 1531.27 | 2535.59 | 1423.87 | 1111.72 | 0.00 | 0.00 |
April | 2250.98 | 1127.30 | 2038.19 | 974.88 | 1063.32 | 0.00 | 0.00 |
May | 2037.33 | 894.27 | 1810.89 | 601.44 | 1209.45 | 0.00 | 0.00 |
June | 2287.92 | 617.58 | 1799.30 | 524.76 | 1274.54 | 0.00 | 0.00 |
July | 2728.61 | 507.04 | 1939.82 | 716.56 | 1223.27 | 0.00 | 0.00 |
August | 3143.05 | 578.44 | 2305.35 | 1162.31 | 1143.04 | 0.00 | 0.00 |
September | 3226.76 | 849.98 | 2556.90 | 1566.69 | 990.21 | 0.00 | 0.00 |
October | 3093.98 | 1207.30 | 2673.10 | 1848.41 | 824.69 | 0.00 | 0.00 |
November | 2581.12 | 1515.93 | 2437.08 | 1765.32 | 671.76 | 0.00 | 0.00 |
December | 2086.32 | 1947.14 | 2118.19 | 1529.54 | 588.64 | 0.00 | 0.00 |
Annual Sum or Average | 2605.80 | 1224.84 | 2269.29 | 1307.23 | 962.06 | 0.00 | 0.00 |
Minimum of Months | 2037.33 | 507.04 | 1799.30 | 524.76 | 588.64 | 0.00 | 0.00 |
Maximum of Months | 3226.76 | 2228.41 | 2836.64 | 2040.21 | 1274.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 238.01 | 1665.64 | 438.19 | 176.59 | 261.59 | 0.00 | 0.00 |
February | 602.87 | 1221.34 | 747.92 | 367.64 | 380.28 | 0.00 | 0.00 |
March | 806.96 | 1021.39 | 957.15 | 350.71 | 606.44 | 0.00 | 0.00 |
April | 1268.77 | 746.67 | 1249.57 | 553.62 | 695.95 | 0.00 | 0.00 |
May | 1698.05 | 605.70 | 1545.63 | 704.89 | 840.74 | 0.00 | 0.00 |
June | 2055.44 | 417.82 | 1681.59 | 772.41 | 909.17 | 0.00 | 0.00 |
July | 2278.24 | 354.23 | 1722.60 | 870.45 | 852.15 | 0.00 | 0.00 |
August | 1882.35 | 385.25 | 1462.72 | 717.87 | 744.85 | 0.00 | 0.00 |
September | 1383.88 | 564.84 | 1176.66 | 594.87 | 581.79 | 0.00 | 0.00 |
October | 826.74 | 815.55 | 840.99 | 417.84 | 423.15 | 0.00 | 0.00 |
November | 476.91 | 1083.76 | 595.34 | 295.34 | 300.00 | 0.00 | 0.00 |
December | 226.33 | 1436.69 | 400.18 | 168.90 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1148.18 | 858.65 | 1069.67 | 499.74 | 569.92 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 354.23 | 400.18 | 168.90 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2278.24 | 1665.64 | 1722.60 | 870.45 | 909.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.51 | 2634.35 | 316.01 | 0.00 | 316.01 | 0.00 | 0.00 |
February | 80.17 | 1964.42 | 446.19 | 0.00 | 446.19 | 0.00 | 0.00 |
March | 264.34 | 1592.55 | 724.82 | 0.00 | 724.82 | 0.00 | 0.00 |
April | 446.66 | 1145.38 | 826.45 | 4.82 | 821.63 | 0.00 | 0.00 |
May | 819.19 | 860.87 | 1085.32 | 64.31 | 1021.01 | 0.00 | 0.00 |
June | 1307.17 | 553.74 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
July | 1418.89 | 463.14 | 1154.55 | 108.14 | 1046.41 | 0.00 | 0.00 |
August | 1033.44 | 529.79 | 925.15 | 24.80 | 900.35 | 0.00 | 0.00 |
September | 599.24 | 816.30 | 692.87 | 0.25 | 692.62 | 0.00 | 0.00 |
October | 229.48 | 1195.78 | 505.41 | 0.00 | 505.41 | 0.00 | 0.00 |
November | 55.80 | 1673.11 | 343.58 | 0.00 | 343.58 | 0.00 | 0.00 |
December | 6.20 | 2264.87 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Annual Sum or Average | 525.35 | 1305.32 | 713.86 | 29.11 | 684.75 | 0.00 | 0.00 |
Minimum of Months | 6.20 | 463.14 | 265.00 | 0.00 | 265.00 | 0.00 | 0.00 |
Maximum of Months | 1418.89 | 2634.35 | 1263.80 | 145.26 | 1118.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.57 | 1615.78 | 483.77 | 221.79 | 261.98 | 0.00 | 0.00 |
February | 578.18 | 1207.87 | 756.66 | 375.66 | 381.00 | 0.00 | 0.00 |
March | 842.62 | 1006.79 | 1017.40 | 420.97 | 596.43 | 0.00 | 0.00 |
April | 1270.25 | 736.69 | 1298.10 | 643.33 | 654.77 | 0.00 | 0.00 |
May | 1502.93 | 582.92 | 1433.92 | 638.00 | 795.92 | 0.00 | 0.00 |
June | 2239.79 | 381.88 | 1856.02 | 955.11 | 900.91 | 0.00 | 0.00 |
July | 2536.78 | 312.36 | 1947.95 | 1101.23 | 846.72 | 0.00 | 0.00 |
August | 2152.34 | 352.33 | 1692.85 | 943.21 | 749.65 | 0.00 | 0.00 |
September | 1376.08 | 518.54 | 1197.53 | 618.16 | 579.37 | 0.00 | 0.00 |
October | 817.45 | 755.84 | 859.16 | 436.27 | 422.89 | 0.00 | 0.00 |
November | 380.05 | 1027.85 | 544.52 | 254.22 | 290.30 | 0.00 | 0.00 |
December | 207.54 | 1389.69 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Annual Sum or Average | 1184.26 | 822.62 | 1126.05 | 566.02 | 560.03 | 0.00 | 0.00 |
Minimum of Months | 207.54 | 312.36 | 401.62 | 172.49 | 229.12 | 0.00 | 0.00 |
Maximum of Months | 2536.78 | 1615.78 | 1947.95 | 1101.23 | 900.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2116.41 | 2276.81 | 2227.55 | 1590.96 | 636.59 | 0.00 | 0.00 |
February | 2959.49 | 1730.84 | 2836.75 | 2040.30 | 796.45 | 0.00 | 0.00 |
March | 2634.72 | 1560.12 | 2535.68 | 1423.92 | 1111.76 | 0.00 | 0.00 |
April | 2194.80 | 1180.84 | 2038.27 | 974.92 | 1063.35 | 0.00 | 0.00 |
May | 1980.77 | 939.25 | 1810.95 | 601.47 | 1209.48 | 0.00 | 0.00 |
June | 2247.40 | 643.86 | 1799.36 | 524.78 | 1274.58 | 0.00 | 0.00 |
July | 2706.98 | 512.90 | 1939.89 | 716.59 | 1223.30 | 0.00 | 0.00 |
August | 3123.78 | 576.11 | 2305.43 | 1162.36 | 1143.07 | 0.00 | 0.00 |
September | 3207.00 | 828.25 | 2557.00 | 1566.76 | 990.24 | 0.00 | 0.00 |
October | 3076.09 | 1160.97 | 2673.21 | 1848.49 | 824.72 | 0.00 | 0.00 |
November | 2561.01 | 1476.52 | 2437.17 | 1765.39 | 671.78 | 0.00 | 0.00 |
December | 2058.42 | 1952.71 | 2118.27 | 1529.61 | 588.67 | 0.00 | 0.00 |
Annual Sum or Average | 2569.27 | 1234.77 | 2269.38 | 1307.28 | 962.09 | 0.00 | 0.00 |
Minimum of Months | 1980.77 | 512.90 | 1799.36 | 524.78 | 588.67 | 0.00 | 0.00 |
Maximum of Months | 3207.00 | 2276.81 | 2836.75 | 2040.30 | 1274.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 232.28 | 1683.82 | 438.19 | 176.60 | 261.60 | 0.00 | 0.00 |
February | 587.06 | 1240.57 | 747.93 | 367.65 | 380.28 | 0.00 | 0.00 |
March | 781.00 | 1049.38 | 957.17 | 350.72 | 606.45 | 0.00 | 0.00 |
April | 1236.59 | 779.36 | 1249.59 | 553.63 | 695.96 | 0.00 | 0.00 |
May | 1672.95 | 618.21 | 1545.65 | 704.90 | 840.75 | 0.00 | 0.00 |
June | 2036.33 | 423.27 | 1681.61 | 772.43 | 909.18 | 0.00 | 0.00 |
July | 2266.95 | 352.14 | 1722.62 | 870.47 | 852.15 | 0.00 | 0.00 |
August | 1872.77 | 383.09 | 1462.74 | 717.88 | 744.86 | 0.00 | 0.00 |
September | 1376.57 | 554.95 | 1176.68 | 594.88 | 581.80 | 0.00 | 0.00 |
October | 823.82 | 795.13 | 841.00 | 417.85 | 423.15 | 0.00 | 0.00 |
November | 473.08 | 1066.29 | 595.35 | 295.34 | 300.01 | 0.00 | 0.00 |
December | 221.91 | 1432.03 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Annual Sum or Average | 1134.62 | 863.51 | 1069.68 | 499.75 | 569.93 | 0.00 | 0.00 |
Minimum of Months | 221.91 | 352.14 | 400.18 | 168.91 | 231.28 | 0.00 | 0.00 |
Maximum of Months | 2266.95 | 1683.82 | 1722.62 | 870.47 | 909.18 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 37298374.86 | 0.683642E+10 | 0.846413E+09 | 0.00 | 0.846413E+09 | 0.00 | 0.00 |
February | 0.219124E+09 | 0.455407E+10 | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.00 | 0.00 |
March | 0.756443E+09 | 0.404944E+10 | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.00 | 0.00 |
April | 0.120476E+10 | 0.279250E+10 | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.00 | 0.00 |
May | 0.223499E+10 | 0.218627E+10 | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.00 | 0.00 |
June | 0.340314E+10 | 0.138697E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
July | 0.380508E+10 | 0.120548E+10 | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.00 | 0.00 |
August | 0.277765E+10 | 0.136400E+10 | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.00 | 0.00 |
September | 0.158062E+10 | 0.199509E+10 | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.00 | 0.00 |
October | 0.672928E+09 | 0.297235E+10 | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.00 | 0.00 |
November | 0.172808E+09 | 0.404715E+10 | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.00 | 0.00 |
December | 20424101.42 | 0.580173E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168853E+11 | 0.391915E+11 | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.00 | 0.00 |
Minimum of Months | 20424101.42 | 0.120548E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380508E+10 | 0.683642E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.729968E+09 | 0.419937E+10 | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.00 | 0.00 |
February | 0.143177E+10 | 0.280143E+10 | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.00 | 0.00 |
March | 0.230348E+10 | 0.256126E+10 | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.00 | 0.00 |
April | 0.333052E+10 | 0.180270E+10 | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.00 | 0.00 |
May | 0.405242E+10 | 0.148560E+10 | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.00 | 0.00 |
June | 0.581628E+10 | 0.958597E+09 | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.00 | 0.00 |
July | 0.679888E+10 | 0.813117E+09 | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.00 | 0.00 |
August | 0.577393E+10 | 0.910394E+09 | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.00 | 0.00 |
September | 0.359004E+10 | 0.127564E+10 | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.00 | 0.00 |
October | 0.223901E+10 | 0.188894E+10 | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.00 | 0.00 |
November | 0.103044E+10 | 0.248932E+10 | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.00 | 0.00 |
December | 0.577496E+09 | 0.356101E+10 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.376742E+11 | 0.247474E+11 | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.00 | 0.00 |
Minimum of Months | 0.577496E+09 | 0.813117E+09 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679888E+10 | 0.419937E+10 | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.570982E+10 | 0.589223E+10 | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.00 | 0.00 |
February | 0.720513E+10 | 0.400390E+10 | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.00 | 0.00 |
March | 0.710656E+10 | 0.396961E+10 | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.00 | 0.00 |
April | 0.572514E+10 | 0.289133E+10 | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.00 | 0.00 |
May | 0.532812E+10 | 0.238964E+10 | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.00 | 0.00 |
June | 0.582562E+10 | 0.160717E+10 | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.00 | 0.00 |
July | 0.724291E+10 | 0.132886E+10 | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.00 | 0.00 |
August | 0.836186E+10 | 0.148318E+10 | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.00 | 0.00 |
September | 0.832593E+10 | 0.203702E+10 | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.00 | 0.00 |
October | 0.828913E+10 | 0.290967E+10 | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.00 | 0.00 |
November | 0.671199E+10 | 0.358761E+10 | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.00 | 0.00 |
December | 0.557383E+10 | 0.498875E+10 | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.814060E+11 | 0.370890E+11 | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.532812E+10 | 0.132886E+10 | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.00 | 0.00 |
Maximum of Months | 0.836186E+10 | 0.589223E+10 | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.633043E+09 | 0.437198E+10 | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.00 | 0.00 |
February | 0.144172E+10 | 0.287311E+10 | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.00 | 0.00 |
March | 0.212319E+10 | 0.266880E+10 | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.00 | 0.00 |
April | 0.323443E+10 | 0.190640E+10 | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.00 | 0.00 |
May | 0.449765E+10 | 0.157238E+10 | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.00 | 0.00 |
June | 0.527829E+10 | 0.105637E+10 | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.00 | 0.00 |
July | 0.606722E+10 | 0.913274E+09 | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.00 | 0.00 |
August | 0.501570E+10 | 0.986159E+09 | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.00 | 0.00 |
September | 0.358194E+10 | 0.135966E+10 | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.00 | 0.00 |
October | 0.224390E+10 | 0.198181E+10 | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.00 | 0.00 |
November | 0.125752E+10 | 0.258307E+10 | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.00 | 0.00 |
December | 0.610032E+09 | 0.366930E+10 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.359846E+11 | 0.259423E+11 | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.00 | 0.00 |
Minimum of Months | 0.610032E+09 | 0.913274E+09 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.606722E+10 | 0.437198E+10 | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30636303.80 | 0.696367E+10 | 0.846395E+09 | 0.00 | 0.846395E+09 | 0.00 | 0.00 |
February | 0.218815E+09 | 0.463821E+10 | 0.107941E+10 | 0.00 | 0.107941E+10 | 0.00 | 0.00 |
March | 0.793921E+09 | 0.409691E+10 | 0.194132E+10 | 0.00 | 0.194132E+10 | 0.00 | 0.00 |
April | 0.129291E+10 | 0.275356E+10 | 0.214211E+10 | 12500766.64 | 0.212961E+10 | 0.00 | 0.00 |
May | 0.233880E+10 | 0.217830E+10 | 0.290687E+10 | 0.172249E+09 | 0.273462E+10 | 0.00 | 0.00 |
June | 0.348527E+10 | 0.136983E+10 | 0.327570E+10 | 0.376511E+09 | 0.289919E+10 | 0.00 | 0.00 |
July | 0.386494E+10 | 0.119445E+10 | 0.309229E+10 | 0.289627E+09 | 0.280266E+10 | 0.00 | 0.00 |
August | 0.281494E+10 | 0.137560E+10 | 0.247787E+10 | 66417729.40 | 0.241145E+10 | 0.00 | 0.00 |
September | 0.158698E+10 | 0.208567E+10 | 0.179589E+10 | 644455.37 | 0.179524E+10 | 0.00 | 0.00 |
October | 0.627695E+09 | 0.321472E+10 | 0.135366E+10 | 0.00 | 0.135366E+10 | 0.00 | 0.00 |
November | 0.150775E+09 | 0.435415E+10 | 0.890546E+09 | 0.00 | 0.890546E+09 | 0.00 | 0.00 |
December | 18612656.43 | 0.606854E+10 | 0.709750E+09 | 0.00 | 0.709750E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172243E+11 | 0.402936E+11 | 0.225118E+11 | 0.917949E+09 | 0.215938E+11 | 0.00 | 0.00 |
Minimum of Months | 18612656.43 | 0.119445E+10 | 0.709750E+09 | 0.00 | 0.709750E+09 | 0.00 | 0.00 |
Maximum of Months | 0.386494E+10 | 0.696367E+10 | 0.327570E+10 | 0.376511E+09 | 0.289919E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.725173E+09 | 0.429647E+10 | 0.129571E+10 | 0.594028E+09 | 0.701681E+09 | 0.00 | 0.00 |
February | 0.143382E+10 | 0.287818E+10 | 0.183048E+10 | 0.908787E+09 | 0.921694E+09 | 0.00 | 0.00 |
March | 0.232719E+10 | 0.263328E+10 | 0.272495E+10 | 0.112751E+10 | 0.159745E+10 | 0.00 | 0.00 |
April | 0.337380E+10 | 0.183507E+10 | 0.336462E+10 | 0.166747E+10 | 0.169714E+10 | 0.00 | 0.00 |
May | 0.409848E+10 | 0.152051E+10 | 0.384055E+10 | 0.170880E+10 | 0.213175E+10 | 0.00 | 0.00 |
June | 0.585821E+10 | 0.978958E+09 | 0.481073E+10 | 0.247559E+10 | 0.233514E+10 | 0.00 | 0.00 |
July | 0.683054E+10 | 0.844218E+09 | 0.521730E+10 | 0.294947E+10 | 0.226783E+10 | 0.00 | 0.00 |
August | 0.579729E+10 | 0.952967E+09 | 0.453407E+10 | 0.252623E+10 | 0.200783E+10 | 0.00 | 0.00 |
September | 0.359063E+10 | 0.136810E+10 | 0.310394E+10 | 0.160224E+10 | 0.150170E+10 | 0.00 | 0.00 |
October | 0.220250E+10 | 0.207662E+10 | 0.230115E+10 | 0.116848E+10 | 0.113266E+10 | 0.00 | 0.00 |
November | 0.991622E+09 | 0.270721E+10 | 0.141138E+10 | 0.658925E+09 | 0.752451E+09 | 0.00 | 0.00 |
December | 0.562651E+09 | 0.373734E+10 | 0.107567E+10 | 0.462001E+09 | 0.613669E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377919E+11 | 0.258289E+11 | 0.355105E+11 | 0.178495E+11 | 0.176610E+11 | 0.00 | 0.00 |
Minimum of Months | 0.562651E+09 | 0.844218E+09 | 0.107567E+10 | 0.462001E+09 | 0.613669E+09 | 0.00 | 0.00 |
Maximum of Months | 0.683054E+10 | 0.429647E+10 | 0.521730E+10 | 0.294947E+10 | 0.233514E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.579176E+10 | 0.596858E+10 | 0.596603E+10 | 0.426105E+10 | 0.170498E+10 | 0.00 | 0.00 |
February | 0.729544E+10 | 0.415014E+10 | 0.686240E+10 | 0.493568E+10 | 0.192671E+10 | 0.00 | 0.00 |
March | 0.721201E+10 | 0.410134E+10 | 0.679132E+10 | 0.381368E+10 | 0.297764E+10 | 0.00 | 0.00 |
April | 0.583454E+10 | 0.292197E+10 | 0.528299E+10 | 0.252688E+10 | 0.275612E+10 | 0.00 | 0.00 |
May | 0.545678E+10 | 0.239522E+10 | 0.485028E+10 | 0.161090E+10 | 0.323938E+10 | 0.00 | 0.00 |
June | 0.593029E+10 | 0.160077E+10 | 0.466378E+10 | 0.136017E+10 | 0.330361E+10 | 0.00 | 0.00 |
July | 0.730830E+10 | 0.135805E+10 | 0.519563E+10 | 0.191923E+10 | 0.327639E+10 | 0.00 | 0.00 |
August | 0.841834E+10 | 0.154930E+10 | 0.617465E+10 | 0.311313E+10 | 0.306152E+10 | 0.00 | 0.00 |
September | 0.836375E+10 | 0.220314E+10 | 0.662749E+10 | 0.406086E+10 | 0.256663E+10 | 0.00 | 0.00 |
October | 0.828692E+10 | 0.323364E+10 | 0.715963E+10 | 0.495078E+10 | 0.220885E+10 | 0.00 | 0.00 |
November | 0.669027E+10 | 0.392930E+10 | 0.631690E+10 | 0.457570E+10 | 0.174120E+10 | 0.00 | 0.00 |
December | 0.558799E+10 | 0.521523E+10 | 0.567336E+10 | 0.409673E+10 | 0.157663E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.821764E+11 | 0.386267E+11 | 0.715645E+11 | 0.412248E+11 | 0.303397E+11 | 0.00 | 0.00 |
Minimum of Months | 0.545678E+10 | 0.135805E+10 | 0.466378E+10 | 0.136017E+10 | 0.157663E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841834E+10 | 0.596858E+10 | 0.715963E+10 | 0.495078E+10 | 0.330361E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.637491E+09 | 0.446125E+10 | 0.117364E+10 | 0.472984E+09 | 0.700656E+09 | 0.00 | 0.00 |
February | 0.145848E+10 | 0.295468E+10 | 0.180937E+10 | 0.889393E+09 | 0.919973E+09 | 0.00 | 0.00 |
March | 0.216135E+10 | 0.273569E+10 | 0.256364E+10 | 0.939355E+09 | 0.162429E+10 | 0.00 | 0.00 |
April | 0.328866E+10 | 0.193537E+10 | 0.323889E+10 | 0.143497E+10 | 0.180392E+10 | 0.00 | 0.00 |
May | 0.454806E+10 | 0.162230E+10 | 0.413981E+10 | 0.188797E+10 | 0.225184E+10 | 0.00 | 0.00 |
June | 0.532770E+10 | 0.108298E+10 | 0.435867E+10 | 0.200209E+10 | 0.235658E+10 | 0.00 | 0.00 |
July | 0.610203E+10 | 0.948782E+09 | 0.461381E+10 | 0.233142E+10 | 0.228239E+10 | 0.00 | 0.00 |
August | 0.504168E+10 | 0.103186E+10 | 0.391774E+10 | 0.192274E+10 | 0.199500E+10 | 0.00 | 0.00 |
September | 0.358702E+10 | 0.146406E+10 | 0.304992E+10 | 0.154191E+10 | 0.150801E+10 | 0.00 | 0.00 |
October | 0.221433E+10 | 0.218436E+10 | 0.225251E+10 | 0.111915E+10 | 0.113336E+10 | 0.00 | 0.00 |
November | 0.123616E+10 | 0.280911E+10 | 0.154313E+10 | 0.765520E+09 | 0.777606E+09 | 0.00 | 0.00 |
December | 0.606190E+09 | 0.384804E+10 | 0.107184E+10 | 0.452392E+09 | 0.619447E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362091E+11 | 0.270785E+11 | 0.337330E+11 | 0.157599E+11 | 0.179731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.606190E+09 | 0.948782E+09 | 0.107184E+10 | 0.452392E+09 | 0.619447E+09 | 0.00 | 0.00 |
Maximum of Months | 0.610203E+10 | 0.446125E+10 | 0.461381E+10 | 0.233142E+10 | 0.235658E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 28141540.10 | 0.705584E+10 | 0.846413E+09 | 0.00 | 0.846413E+09 | 0.00 | 0.00 |
February | 0.193942E+09 | 0.475232E+10 | 0.107943E+10 | 0.00 | 0.107943E+10 | 0.00 | 0.00 |
March | 0.708002E+09 | 0.426548E+10 | 0.194136E+10 | 0.00 | 0.194136E+10 | 0.00 | 0.00 |
April | 0.115774E+10 | 0.296884E+10 | 0.214215E+10 | 12501134.09 | 0.212965E+10 | 0.00 | 0.00 |
May | 0.219412E+10 | 0.230574E+10 | 0.290693E+10 | 0.172254E+09 | 0.273468E+10 | 0.00 | 0.00 |
June | 0.338817E+10 | 0.143529E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
July | 0.380034E+10 | 0.124047E+10 | 0.309235E+10 | 0.289636E+09 | 0.280271E+10 | 0.00 | 0.00 |
August | 0.276797E+10 | 0.141900E+10 | 0.247791E+10 | 66419681.66 | 0.241150E+10 | 0.00 | 0.00 |
September | 0.155323E+10 | 0.211584E+10 | 0.179592E+10 | 644474.31 | 0.179528E+10 | 0.00 | 0.00 |
October | 0.614628E+09 | 0.320278E+10 | 0.135369E+10 | 0.00 | 0.135369E+10 | 0.00 | 0.00 |
November | 0.144628E+09 | 0.433671E+10 | 0.890565E+09 | 0.00 | 0.890565E+09 | 0.00 | 0.00 |
December | 16593791.03 | 0.606623E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.165675E+11 | 0.411645E+11 | 0.225123E+11 | 0.917976E+09 | 0.215943E+11 | 0.00 | 0.00 |
Minimum of Months | 16593791.03 | 0.124047E+10 | 0.709765E+09 | 0.00 | 0.709765E+09 | 0.00 | 0.00 |
Maximum of Months | 0.380034E+10 | 0.705584E+10 | 0.327577E+10 | 0.376522E+09 | 0.289925E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711298E+09 | 0.432772E+10 | 0.129573E+10 | 0.594040E+09 | 0.701690E+09 | 0.00 | 0.00 |
February | 0.139873E+10 | 0.292208E+10 | 0.183051E+10 | 0.908805E+09 | 0.921705E+09 | 0.00 | 0.00 |
March | 0.225687E+10 | 0.269659E+10 | 0.272500E+10 | 0.112753E+10 | 0.159747E+10 | 0.00 | 0.00 |
April | 0.329249E+10 | 0.190949E+10 | 0.336467E+10 | 0.166751E+10 | 0.169717E+10 | 0.00 | 0.00 |
May | 0.402544E+10 | 0.156130E+10 | 0.384061E+10 | 0.170883E+10 | 0.213178E+10 | 0.00 | 0.00 |
June | 0.580553E+10 | 0.989841E+09 | 0.481081E+10 | 0.247564E+10 | 0.233517E+10 | 0.00 | 0.00 |
July | 0.679451E+10 | 0.836632E+09 | 0.521738E+10 | 0.294953E+10 | 0.226786E+10 | 0.00 | 0.00 |
August | 0.576481E+10 | 0.943682E+09 | 0.453414E+10 | 0.252628E+10 | 0.200786E+10 | 0.00 | 0.00 |
September | 0.356680E+10 | 0.134405E+10 | 0.310399E+10 | 0.160227E+10 | 0.150172E+10 | 0.00 | 0.00 |
October | 0.218946E+10 | 0.202444E+10 | 0.230118E+10 | 0.116850E+10 | 0.113268E+10 | 0.00 | 0.00 |
November | 0.985092E+09 | 0.266418E+10 | 0.141140E+10 | 0.658938E+09 | 0.752461E+09 | 0.00 | 0.00 |
December | 0.555873E+09 | 0.372215E+10 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373469E+11 | 0.259422E+11 | 0.355111E+11 | 0.178499E+11 | 0.176612E+11 | 0.00 | 0.00 |
Minimum of Months | 0.555873E+09 | 0.836632E+09 | 0.107569E+10 | 0.462010E+09 | 0.613678E+09 | 0.00 | 0.00 |
Maximum of Months | 0.679451E+10 | 0.432772E+10 | 0.521738E+10 | 0.294953E+10 | 0.233517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.566859E+10 | 0.609820E+10 | 0.596627E+10 | 0.426123E+10 | 0.170504E+10 | 0.00 | 0.00 |
February | 0.715960E+10 | 0.418724E+10 | 0.686267E+10 | 0.493589E+10 | 0.192678E+10 | 0.00 | 0.00 |
March | 0.705683E+10 | 0.417863E+10 | 0.679158E+10 | 0.381384E+10 | 0.297774E+10 | 0.00 | 0.00 |
April | 0.568891E+10 | 0.306075E+10 | 0.528318E+10 | 0.252698E+10 | 0.275620E+10 | 0.00 | 0.00 |
May | 0.530529E+10 | 0.251568E+10 | 0.485044E+10 | 0.161096E+10 | 0.323948E+10 | 0.00 | 0.00 |
June | 0.582527E+10 | 0.166889E+10 | 0.466394E+10 | 0.136023E+10 | 0.330371E+10 | 0.00 | 0.00 |
July | 0.725036E+10 | 0.137375E+10 | 0.519580E+10 | 0.191931E+10 | 0.327649E+10 | 0.00 | 0.00 |
August | 0.836673E+10 | 0.154305E+10 | 0.617486E+10 | 0.311326E+10 | 0.306161E+10 | 0.00 | 0.00 |
September | 0.831254E+10 | 0.214683E+10 | 0.662774E+10 | 0.406103E+10 | 0.256671E+10 | 0.00 | 0.00 |
October | 0.823899E+10 | 0.310954E+10 | 0.715991E+10 | 0.495099E+10 | 0.220892E+10 | 0.00 | 0.00 |
November | 0.663815E+10 | 0.382713E+10 | 0.631715E+10 | 0.457589E+10 | 0.174126E+10 | 0.00 | 0.00 |
December | 0.551328E+10 | 0.523014E+10 | 0.567359E+10 | 0.409690E+10 | 0.157668E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.810245E+11 | 0.389398E+11 | 0.715671E+11 | 0.412265E+11 | 0.303406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.530529E+10 | 0.137375E+10 | 0.466394E+10 | 0.136023E+10 | 0.157668E+10 | 0.00 | 0.00 |
Maximum of Months | 0.836673E+10 | 0.609820E+10 | 0.715991E+10 | 0.495099E+10 | 0.330371E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.622142E+09 | 0.450994E+10 | 0.117366E+10 | 0.472992E+09 | 0.700664E+09 | 0.00 | 0.00 |
February | 0.142023E+10 | 0.300119E+10 | 0.180939E+10 | 0.889407E+09 | 0.919983E+09 | 0.00 | 0.00 |
March | 0.209183E+10 | 0.281065E+10 | 0.256368E+10 | 0.939370E+09 | 0.162431E+10 | 0.00 | 0.00 |
April | 0.320525E+10 | 0.202010E+10 | 0.323893E+10 | 0.143500E+10 | 0.180393E+10 | 0.00 | 0.00 |
May | 0.448084E+10 | 0.165582E+10 | 0.413987E+10 | 0.188800E+10 | 0.225187E+10 | 0.00 | 0.00 |
June | 0.527817E+10 | 0.109712E+10 | 0.435873E+10 | 0.200213E+10 | 0.235660E+10 | 0.00 | 0.00 |
July | 0.607179E+10 | 0.943163E+09 | 0.461387E+10 | 0.233145E+10 | 0.228241E+10 | 0.00 | 0.00 |
August | 0.501602E+10 | 0.102607E+10 | 0.391779E+10 | 0.192277E+10 | 0.199502E+10 | 0.00 | 0.00 |
September | 0.356808E+10 | 0.143843E+10 | 0.304996E+10 | 0.154193E+10 | 0.150802E+10 | 0.00 | 0.00 |
October | 0.220653E+10 | 0.212968E+10 | 0.225254E+10 | 0.111917E+10 | 0.113338E+10 | 0.00 | 0.00 |
November | 0.122621E+10 | 0.276383E+10 | 0.154315E+10 | 0.765533E+09 | 0.777615E+09 | 0.00 | 0.00 |
December | 0.594362E+09 | 0.383555E+10 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357814E+11 | 0.272315E+11 | 0.337334E+11 | 0.157602E+11 | 0.179733E+11 | 0.00 | 0.00 |
Minimum of Months | 0.594362E+09 | 0.943163E+09 | 0.107185E+10 | 0.452399E+09 | 0.619454E+09 | 0.00 | 0.00 |
Maximum of Months | 0.607179E+10 | 0.450994E+10 | 0.461387E+10 | 0.233145E+10 | 0.235660E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.540718E+10 | -0.515797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -249204872.1 | 60.05 | 0.00 | 0.00 |
February | 0.498839E+10 | -0.476848E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -219909572.2 | 60.05 | 0.00 | 0.00 |
March | 0.582652E+10 | -0.558766E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -238858634.9 | 60.05 | 0.00 | 0.00 |
April | 0.507566E+10 | -0.484790E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -227763687.6 | 60.05 | 0.00 | 0.00 |
May | 0.515432E+10 | -0.492077E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233547255.9 | 60.05 | 0.00 | 0.00 |
June | 0.481704E+10 | -0.459195E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -225086449.7 | 60.05 | 0.00 | 0.00 |
July | 0.434252E+10 | -0.411123E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231290141.8 | 60.05 | 0.00 | 0.00 |
August | 0.467849E+10 | -0.444657E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231916654.8 | 60.05 | 0.00 | 0.00 |
September | 0.428179E+10 | -0.405707E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224717355.4 | 60.05 | 0.00 | 0.00 |
October | 0.461512E+10 | -0.438146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233663275.3 | 60.05 | 0.00 | 0.00 |
November | 0.480566E+10 | -0.457646E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -229202577.0 | 60.05 | 0.00 | 0.00 |
December | 0.504477E+10 | -0.480114E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -243622317.4 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.590375E+11 | -0.562487E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.278878E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.428179E+10 | -0.558766E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -249204872.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.582652E+10 | -0.405707E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -219909572.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5944.25 | 36.69 | 217.17 | 230.00 | 5014.28 | 37.70 | 219.33 | 213.50 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:09 | 8041.97 | 37.03 | 267.50 | 258.33 | 3500.79 | 31.87 | 238.83 | 246.33 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9360.43 | 32.84 | 259.33 | 321.67 | 1962.01 | 22.44 | 212.00 | 293.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2347.31 | 19.23 | 8.17 | 346.83 | 1365.28 | 21.50 | 191.50 | 313.67 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:19 | 2062.90 | 19.00 | 1.00 | 395.67 | 1174.07 | 21.23 | 212.83 | 354.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1761.79 | 18.47 | 0.00 | 408.50 | 1035.97 | 20.74 | 221.67 | 362.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1897.86 | 18.87 | 2.17 | 403.17 | 1148.54 | 21.17 | 190.00 | 368.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:30 | 2043.31 | 18.35 | 1.50 | 381.17 | 1241.93 | 20.62 | 182.50 | 345.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2903.63 | 19.82 | 37.17 | 326.17 | 1487.68 | 20.99 | 167.67 | 297.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 8136.21 | 34.62 | 285.50 | 301.33 | 2364.24 | 25.11 | 208.67 | 284.83 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 6064.13 | 36.88 | 260.33 | 249.83 | 5380.03 | 38.37 | 263.50 | 239.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4683.43 | 36.05 | 218.33 | 230.33 | 4152.61 | 38.73 | 239.00 | 218.33 |
Annual Sum or Average | 3965.83 | 0.50 | 4219.33 | 25.76 | 1558.17 | 3853.00 | 2207.41 | 25.40 | 2547.50 | 3537.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1761.79 | 18.35 | 0.00 | 230.00 | 1035.97 | 20.62 | 167.67 | 213.50 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9360.43 | 37.03 | 285.50 | 408.50 | 5380.03 | 38.73 | 263.50 | 368.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:39 | 1850.09 | 23.62 | 89.67 | 214.50 | 1061.15 | 23.88 | 90.00 | 180.00 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 2026.50 | 21.12 | 75.17 | 243.83 | 1083.01 | 21.87 | 90.50 | 211.33 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3231.10 | 22.72 | 94.67 | 317.67 | 1805.07 | 23.62 | 130.50 | 285.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3249.13 | 21.93 | 85.17 | 354.83 | 1818.93 | 23.03 | 76.17 | 319.00 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3568.58 | 22.18 | 113.67 | 405.83 | 1574.09 | 22.13 | 62.33 | 367.17 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4341.11 | 22.52 | 134.17 | 419.67 | 1902.34 | 23.13 | 91.00 | 389.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4724.15 | 23.34 | 132.67 | 418.67 | 2036.55 | 22.97 | 77.50 | 393.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3730.22 | 21.64 | 115.67 | 388.00 | 2185.06 | 23.68 | 109.83 | 357.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2833.91 | 21.92 | 104.17 | 325.50 | 1584.55 | 22.89 | 106.67 | 292.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2533.05 | 22.31 | 107.00 | 287.17 | 1461.12 | 23.50 | 122.00 | 252.00 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1598.28 | 21.01 | 83.17 | 229.00 | 916.86 | 23.04 | 100.50 | 196.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1436.00 | 23.53 | 100.67 | 206.83 | 858.98 | 24.04 | 98.17 | 164.33 |
Annual Sum or Average | 3965.83 | 0.50 | 3125.21 | 22.30 | 1235.83 | 3811.50 | 1602.50 | 23.12 | 1155.17 | 3407.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1436.00 | 21.01 | 75.17 | 206.83 | 858.98 | 21.87 | 62.33 | 164.33 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4724.15 | 23.62 | 134.17 | 419.67 | 2185.06 | 24.04 | 130.50 | 393.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 596.47 | 14.85 | 0.00 | 189.33 | 354.35 | 17.31 | 0.00 | 118.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 652.62 | 15.86 | 0.00 | 228.17 | 403.48 | 18.34 | 0.00 | 170.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:00 | 1029.76 | 17.91 | 0.00 | 309.00 | 607.52 | 20.17 | 31.33 | 267.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1072.56 | 18.59 | 0.00 | 350.17 | 642.45 | 20.76 | 57.33 | 310.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1328.78 | 20.56 | 42.67 | 411.00 | 750.25 | 21.34 | 148.83 | 373.50 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1379.97 | 22.12 | 98.33 | 439.17 | 785.07 | 22.63 | 225.67 | 413.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1351.91 | 21.69 | 77.00 | 425.17 | 782.50 | 21.59 | 172.33 | 397.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1047.27 | 18.21 | 0.00 | 398.67 | 668.79 | 20.44 | 90.83 | 375.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 855.62 | 17.21 | 0.00 | 321.83 | 533.12 | 19.47 | 10.83 | 275.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:50 | 706.51 | 16.24 | 0.00 | 269.83 | 432.45 | 18.64 | 0.00 | 207.00 |
November | 269.50 | 0.54 | 0.48 | 01-NOV-08:39 | 559.58 | 14.96 | 0.00 | 206.00 | 338.17 | 17.45 | 0.00 | 127.83 |
December | 236.83 | 0.55 | 0.48 | 01-DEC-09:39 | 486.97 | 14.27 | 0.00 | 180.83 | 293.24 | 16.85 | 0.00 | 79.33 |
Annual Sum or Average | 3965.83 | 0.51 | 979.81 | 18.18 | 218.00 | 3729.17 | 582.30 | 19.92 | 737.17 | 3115.33 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 486.97 | 14.27 | 0.00 | 180.83 | 293.24 | 16.85 | 0.00 | 79.33 | |
Maximum of Months | 434.17 | 0.55 | 0.48 | 1379.97 | 22.12 | 98.33 | 439.17 | 785.07 | 22.63 | 225.67 | 413.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-09:00 | 1719.09 | 22.28 | 85.00 | 207.17 | 1008.70 | 22.82 | 82.17 | 170.00 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:20 | 2141.46 | 21.09 | 77.33 | 241.17 | 1220.03 | 23.60 | 108.17 | 213.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 3019.01 | 22.28 | 92.17 | 314.17 | 1689.45 | 24.26 | 125.50 | 283.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 3160.30 | 20.65 | 75.83 | 347.17 | 1783.59 | 21.90 | 62.17 | 311.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:40 | 3604.24 | 19.60 | 75.00 | 401.17 | 1691.93 | 19.16 | 1.33 | 366.00 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3690.88 | 17.74 | 52.00 | 423.33 | 1675.96 | 18.84 | 3.33 | 387.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:49 | 4281.89 | 19.70 | 79.67 | 408.83 | 1948.77 | 19.17 | 4.00 | 378.33 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3288.04 | 19.45 | 88.50 | 386.17 | 1851.28 | 20.94 | 64.50 | 356.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 3268.69 | 21.37 | 98.67 | 325.83 | 1399.61 | 22.30 | 85.33 | 293.50 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:50 | 2169.56 | 20.91 | 85.00 | 283.67 | 1240.37 | 23.10 | 108.67 | 249.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1919.30 | 23.05 | 102.83 | 227.67 | 1098.22 | 23.71 | 102.67 | 193.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:30 | 1310.94 | 20.99 | 78.17 | 207.67 | 764.04 | 23.07 | 89.83 | 168.83 |
Annual Sum or Average | 3965.83 | 0.51 | 2964.75 | 20.52 | 990.17 | 3774.00 | 1511.78 | 21.59 | 837.67 | 3370.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1310.94 | 17.74 | 52.00 | 207.17 | 764.04 | 18.84 | 1.33 | 168.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4281.89 | 23.05 | 102.83 | 423.33 | 1948.77 | 24.26 | 125.50 | 387.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5761.76 | 36.42 | 216.17 | 229.67 | 4871.14 | 37.41 | 215.33 | 212.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 7824.34 | 35.80 | 256.33 | 255.83 | 3350.81 | 30.45 | 179.83 | 245.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9178.21 | 32.07 | 253.50 | 320.00 | 1828.97 | 19.60 | 20.00 | 290.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2225.75 | 15.42 | 0.00 | 345.50 | 1276.15 | 18.99 | 18.83 | 310.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1968.68 | 15.31 | 0.00 | 393.17 | 1108.99 | 18.81 | 14.17 | 351.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1683.39 | 14.87 | 0.00 | 405.67 | 983.14 | 18.45 | 0.50 | 357.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1808.88 | 15.29 | 0.00 | 401.00 | 1086.52 | 18.90 | 10.00 | 365.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1935.56 | 14.60 | 0.00 | 379.50 | 1161.54 | 18.19 | 8.83 | 342.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 2762.12 | 16.17 | 29.50 | 325.17 | 1378.76 | 18.36 | 22.17 | 294.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 7955.56 | 33.77 | 279.67 | 298.83 | 2232.34 | 22.69 | 83.00 | 283.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 5853.77 | 35.14 | 246.17 | 247.17 | 5248.20 | 38.16 | 263.00 | 238.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4447.55 | 32.89 | 196.83 | 226.50 | 4026.70 | 38.53 | 232.17 | 217.17 |
Annual Sum or Average | 3965.83 | 0.50 | 4075.89 | 23.06 | 1478.17 | 3828.00 | 2107.42 | 23.42 | 1067.83 | 3507.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1683.39 | 14.60 | 0.00 | 226.50 | 983.14 | 18.19 | 0.50 | 212.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9178.21 | 36.42 | 279.67 | 405.67 | 5248.20 | 38.53 | 263.00 | 365.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:50 | 1711.82 | 20.99 | 74.83 | 210.67 | 1021.88 | 23.66 | 81.67 | 175.67 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 1960.13 | 20.62 | 75.00 | 242.00 | 1030.76 | 21.64 | 80.83 | 208.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3143.21 | 22.27 | 94.17 | 316.33 | 1735.74 | 23.42 | 117.33 | 282.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3160.03 | 21.46 | 85.17 | 353.17 | 1748.36 | 22.83 | 65.50 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3482.36 | 21.73 | 113.33 | 404.00 | 1505.53 | 21.94 | 58.33 | 363.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4238.69 | 22.07 | 134.17 | 417.17 | 1808.12 | 22.25 | 79.33 | 383.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4613.72 | 22.89 | 132.67 | 417.50 | 1947.76 | 22.81 | 75.67 | 390.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3611.31 | 20.95 | 112.67 | 386.67 | 2105.12 | 23.51 | 103.50 | 354.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2661.53 | 19.80 | 85.17 | 321.67 | 1519.74 | 22.70 | 96.50 | 289.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2469.49 | 21.84 | 107.00 | 284.17 | 1410.59 | 23.29 | 114.83 | 248.33 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1548.68 | 20.33 | 80.83 | 226.83 | 878.76 | 22.81 | 89.17 | 193.33 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1322.48 | 20.56 | 80.00 | 202.33 | 829.04 | 23.81 | 90.50 | 158.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3024.26 | 21.38 | 1175.00 | 3782.50 | 1536.53 | 22.84 | 1053.17 | 3364.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1322.48 | 19.80 | 74.83 | 202.33 | 829.04 | 21.64 | 58.33 | 158.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4613.72 | 22.89 | 134.17 | 417.50 | 2105.12 | 23.81 | 117.33 | 390.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 573.79 | 11.13 | 0.00 | 186.33 | 341.89 | 14.79 | 0.00 | 110.00 |
February | 275.00 | 0.53 | 0.48 | 01-FEB-10:30 | 628.42 | 12.21 | 0.00 | 224.83 | 390.59 | 15.95 | 0.00 | 164.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 993.33 | 14.46 | 0.00 | 307.17 | 587.52 | 17.98 | 0.00 | 263.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1035.26 | 15.27 | 0.00 | 349.33 | 622.33 | 18.79 | 3.83 | 304.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1283.33 | 17.43 | 38.50 | 409.83 | 756.27 | 20.68 | 54.17 | 374.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1332.20 | 19.42 | 96.33 | 437.50 | 757.81 | 20.67 | 66.67 | 410.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1307.02 | 18.88 | 72.17 | 423.50 | 757.88 | 19.58 | 38.67 | 394.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1011.69 | 14.86 | 0.00 | 395.83 | 649.88 | 18.48 | 6.67 | 373.00 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 825.57 | 13.88 | 0.00 | 319.33 | 517.36 | 17.42 | 0.00 | 270.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:00 | 680.72 | 12.69 | 0.00 | 266.33 | 418.66 | 16.36 | 0.00 | 202.17 |
November | 269.50 | 0.55 | 0.48 | 01-NOV-08:50 | 538.36 | 11.19 | 0.00 | 202.50 | 326.65 | 14.96 | 0.00 | 118.67 |
December | 236.83 | 0.56 | 0.48 | 01-DEC-09:39 | 467.29 | 10.41 | 0.00 | 174.67 | 282.46 | 14.21 | 0.00 | 68.33 |
Annual Sum or Average | 3965.83 | 0.51 | 945.47 | 14.86 | 207.00 | 3697.17 | 566.58 | 17.89 | 170.00 | 3053.00 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 467.29 | 10.41 | 0.00 | 174.67 | 282.46 | 14.21 | 0.00 | 68.33 | |
Maximum of Months | 434.17 | 0.56 | 0.48 | 1332.20 | 19.42 | 96.33 | 437.50 | 757.88 | 20.68 | 66.67 | 410.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-10:09 | 1673.03 | 21.93 | 84.83 | 205.50 | 973.58 | 22.74 | 79.50 | 164.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:30 | 2080.41 | 20.68 | 77.33 | 239.50 | 1170.56 | 23.51 | 107.17 | 210.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2938.65 | 21.87 | 91.67 | 312.83 | 1601.63 | 23.28 | 113.33 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3067.16 | 20.20 | 75.83 | 345.00 | 1711.93 | 21.75 | 55.83 | 309.00 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3445.83 | 19.14 | 75.00 | 398.00 | 1615.06 | 19.00 | 0.50 | 363.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3598.24 | 17.23 | 52.00 | 421.33 | 1604.31 | 18.66 | 2.33 | 384.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:49 | 4179.09 | 19.23 | 79.67 | 407.00 | 1868.12 | 19.01 | 3.83 | 376.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3199.99 | 18.99 | 88.33 | 384.17 | 1781.87 | 20.78 | 62.67 | 353.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3190.79 | 20.95 | 98.67 | 324.00 | 1335.09 | 22.19 | 83.17 | 291.17 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:00 | 2086.05 | 20.13 | 80.83 | 281.00 | 1188.93 | 23.00 | 106.83 | 246.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1770.99 | 20.47 | 82.33 | 224.67 | 1058.16 | 23.62 | 101.50 | 189.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:39 | 1270.44 | 20.61 | 77.67 | 205.00 | 732.97 | 22.98 | 88.67 | 163.17 |
Annual Sum or Average | 3965.83 | 0.51 | 2872.26 | 19.90 | 964.17 | 3748.00 | 1448.12 | 21.39 | 805.33 | 3330.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1270.44 | 17.23 | 52.00 | 205.00 | 732.97 | 18.66 | 0.50 | 163.17 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4179.09 | 21.93 | 98.67 | 421.33 | 1868.12 | 23.62 | 113.33 | 384.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.50 | 0.48 | 01-JAN-08:50 | 5761.76 | 36.42 | 216.17 | 229.67 | 4871.05 | 37.41 | 215.33 | 212.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 7824.31 | 35.80 | 256.33 | 255.83 | 3350.71 | 30.45 | 179.83 | 245.00 |
March | 304.00 | 0.49 | 0.48 | 01-MAR-07:49 | 9178.09 | 32.07 | 253.50 | 320.00 | 1828.84 | 19.60 | 20.17 | 290.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:39 | 2225.63 | 15.42 | 0.00 | 345.50 | 1276.05 | 18.99 | 18.83 | 310.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:30 | 1968.56 | 15.31 | 0.00 | 393.17 | 1108.91 | 18.81 | 14.17 | 351.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 1683.31 | 14.88 | 0.00 | 405.67 | 983.07 | 18.45 | 0.50 | 357.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 1808.79 | 15.30 | 0.00 | 401.00 | 1086.45 | 18.90 | 10.00 | 365.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 1935.47 | 14.60 | 0.00 | 379.50 | 1161.47 | 18.19 | 8.83 | 342.17 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 2762.03 | 16.18 | 29.50 | 325.17 | 1378.67 | 18.36 | 22.33 | 294.17 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:20 | 7955.51 | 33.77 | 279.67 | 298.83 | 2232.24 | 22.69 | 83.00 | 283.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:49 | 5853.77 | 35.14 | 246.17 | 247.17 | 5248.11 | 38.16 | 263.00 | 238.83 |
December | 236.83 | 0.50 | 0.48 | 01-DEC-08:50 | 4447.57 | 32.89 | 196.83 | 226.50 | 4026.64 | 38.53 | 232.17 | 217.17 |
Annual Sum or Average | 3965.83 | 0.50 | 4075.82 | 23.06 | 1478.17 | 3828.00 | 2107.34 | 23.43 | 1068.17 | 3507.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1683.31 | 14.60 | 0.00 | 226.50 | 983.07 | 18.19 | 0.50 | 212.00 | |
Maximum of Months | 434.17 | 0.51 | 0.48 | 9178.09 | 36.42 | 279.67 | 405.67 | 5248.11 | 38.53 | 263.00 | 365.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.52 | 0.48 | 01-JAN-08:50 | 1711.79 | 20.99 | 74.83 | 210.67 | 1021.84 | 23.66 | 81.67 | 175.67 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-08:09 | 1960.11 | 20.62 | 75.00 | 242.00 | 1030.72 | 21.64 | 81.00 | 208.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3143.16 | 22.27 | 94.17 | 316.33 | 1735.66 | 23.43 | 117.33 | 282.17 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3159.98 | 21.46 | 85.17 | 353.17 | 1748.29 | 22.84 | 65.50 | 316.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:40 | 3482.29 | 21.73 | 113.33 | 404.00 | 1505.45 | 21.94 | 58.50 | 363.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4238.64 | 22.07 | 134.17 | 417.17 | 1808.05 | 22.25 | 79.33 | 383.83 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 4613.69 | 22.90 | 132.67 | 417.50 | 1947.69 | 22.81 | 75.67 | 390.17 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3611.27 | 20.95 | 112.67 | 386.67 | 2105.05 | 23.51 | 103.50 | 354.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 2661.50 | 19.80 | 85.17 | 321.67 | 1519.68 | 22.70 | 96.50 | 289.67 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:09 | 2469.46 | 21.85 | 107.00 | 284.17 | 1410.54 | 23.29 | 114.83 | 248.33 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-07:49 | 1548.66 | 20.33 | 80.83 | 226.83 | 878.72 | 22.81 | 89.17 | 193.33 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-08:50 | 1322.46 | 20.57 | 80.00 | 202.33 | 829.00 | 23.81 | 90.50 | 158.83 |
Annual Sum or Average | 3965.83 | 0.50 | 3024.22 | 21.38 | 1175.00 | 3782.50 | 1536.47 | 22.84 | 1053.50 | 3364.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1322.46 | 19.80 | 74.83 | 202.33 | 829.00 | 21.64 | 58.50 | 158.83 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4613.69 | 22.90 | 134.17 | 417.50 | 2105.05 | 23.81 | 117.33 | 390.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.55 | 0.48 | 01-JAN-10:09 | 573.77 | 11.13 | 0.00 | 186.33 | 341.86 | 14.80 | 0.00 | 110.00 |
February | 275.00 | 0.53 | 0.48 | 01-FEB-10:30 | 628.41 | 12.21 | 0.00 | 224.83 | 390.57 | 15.95 | 0.00 | 164.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 993.29 | 14.47 | 0.00 | 307.17 | 587.48 | 17.98 | 0.00 | 263.33 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:50 | 1035.23 | 15.27 | 0.00 | 349.33 | 622.29 | 18.79 | 3.83 | 304.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1283.29 | 17.43 | 38.50 | 409.83 | 756.22 | 20.68 | 54.17 | 374.00 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1332.17 | 19.42 | 96.33 | 437.50 | 757.76 | 20.67 | 66.67 | 410.00 |
July | 417.33 | 0.48 | 0.48 | 01-JUL-06:40 | 1307.00 | 18.88 | 72.17 | 423.50 | 757.84 | 19.58 | 38.67 | 394.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1011.67 | 14.86 | 0.00 | 395.83 | 649.84 | 18.48 | 6.67 | 373.00 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:00 | 825.55 | 13.88 | 0.00 | 319.33 | 517.33 | 17.42 | 0.00 | 270.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:00 | 680.70 | 12.69 | 0.00 | 266.33 | 418.63 | 16.36 | 0.00 | 202.17 |
November | 269.50 | 0.55 | 0.48 | 01-NOV-08:50 | 538.35 | 11.20 | 0.00 | 202.50 | 326.63 | 14.96 | 0.00 | 118.67 |
December | 236.83 | 0.56 | 0.48 | 01-DEC-09:39 | 467.28 | 10.41 | 0.00 | 174.67 | 282.44 | 14.21 | 0.00 | 68.17 |
Annual Sum or Average | 3965.83 | 0.51 | 945.45 | 14.86 | 207.00 | 3697.17 | 566.54 | 17.89 | 170.00 | 3052.83 | ||
Minimum of Months | 226.83 | 0.48 | 0.48 | 467.28 | 10.41 | 0.00 | 174.67 | 282.44 | 14.21 | 0.00 | 68.17 | |
Maximum of Months | 434.17 | 0.56 | 0.48 | 1332.17 | 19.42 | 96.33 | 437.50 | 757.84 | 20.68 | 66.67 | 410.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-10:09 | 1673.00 | 21.93 | 84.83 | 205.50 | 973.54 | 22.74 | 79.50 | 164.83 |
February | 275.00 | 0.51 | 0.48 | 01-FEB-10:30 | 2080.38 | 20.68 | 77.33 | 239.50 | 1170.52 | 23.51 | 107.17 | 210.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:09 | 2938.58 | 21.88 | 91.67 | 312.83 | 1601.55 | 23.28 | 113.33 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3067.10 | 20.20 | 75.83 | 345.00 | 1711.85 | 21.75 | 56.00 | 309.00 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3445.77 | 19.14 | 75.00 | 398.00 | 1614.98 | 19.00 | 0.50 | 363.67 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 3598.18 | 17.24 | 52.00 | 421.33 | 1604.23 | 18.66 | 2.33 | 384.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:49 | 4179.05 | 19.23 | 79.67 | 407.00 | 1868.04 | 19.01 | 3.83 | 376.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-06:40 | 3199.95 | 18.99 | 88.33 | 384.17 | 1781.80 | 20.78 | 62.67 | 353.83 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3190.76 | 20.95 | 98.67 | 324.00 | 1335.03 | 22.19 | 83.17 | 291.17 |
October | 317.67 | 0.51 | 0.48 | 01-OCT-08:00 | 2086.02 | 20.13 | 80.83 | 281.00 | 1188.88 | 23.00 | 106.83 | 246.17 |
November | 269.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1770.97 | 20.47 | 82.33 | 224.67 | 1058.12 | 23.62 | 101.50 | 189.00 |
December | 236.83 | 0.53 | 0.48 | 01-DEC-09:39 | 1270.42 | 20.61 | 77.67 | 205.00 | 732.94 | 22.99 | 88.67 | 163.17 |
Annual Sum or Average | 3965.83 | 0.51 | 2872.22 | 19.91 | 964.17 | 3748.00 | 1448.05 | 21.39 | 805.50 | 3330.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1270.42 | 17.24 | 52.00 | 205.00 | 732.94 | 18.66 | 0.50 | 163.17 | |
Maximum of Months | 434.17 | 0.53 | 0.48 | 4179.05 | 21.93 | 98.67 | 421.33 | 1868.04 | 23.62 | 113.33 | 384.33 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200555E+11 | 28965.08 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127671E+11 | 28666.55 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.874574E+10 | 27402.47 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.274724E+10 | 17252.95 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150383E+10 | 13000.10 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24660171.47 | 5509.06 | 16-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 312646.89 | 4.85 | 19-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 243524.32 | 1150.68 | 28-AUG-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208299E+09 | 6979.08 | 19-SEP-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161513E+10 | 16998.35 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.610471E+10 | 26216.91 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148417E+11 | 28942.35 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 243524.32 | 4.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200555E+11 | 28965.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.284441E+09 | 13006.50 | 30-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6059607.70 | 13009.46 | 06-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.284441E+09 | 13009.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.807370E+10 | 10879.32 | 27-JAN-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442641E+10 | 10727.55 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315019E+10 | 10215.09 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174727E+10 | 10007.76 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143491E+10 | 10067.33 | 22-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.286925E+09 | 10052.55 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23964656.70 | 9666.55 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174347E+09 | 9688.57 | 18-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.511334E+09 | 10071.86 | 12-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.852452E+09 | 9914.22 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223144E+10 | 9884.09 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510210E+10 | 10837.31 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 23964656.70 | 9666.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.807370E+10 | 10879.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396807E+10 | 7732.43 | 27-JAN-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170490E+10 | 7624.13 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.675637E+09 | 7258.15 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81718220.86 | 6806.01 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34738464.82 | 6859.60 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10191614.53 | 6799.93 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450316E+09 | 6921.47 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196308E+10 | 7702.16 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.888866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.396807E+10 | 7732.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.644364E+10 | 8209.98 | 27-JAN-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332868E+10 | 8096.68 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169476E+10 | 7810.27 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.306562E+09 | 7561.21 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104107E+09 | 7296.19 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36284862.71 | 7233.30 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.883400E+09 | 7468.59 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345795E+10 | 8178.12 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.644364E+10 | 8209.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.434974E+10 | 8089.50 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177441E+10 | 8001.06 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.801923E+09 | 7616.23 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106730E+09 | 7153.92 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40430439.11 | 7196.66 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13292201.15 | 7122.41 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444663E+09 | 7262.15 | 27-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208194E+10 | 8083.22 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.961313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.434974E+10 | 8089.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.196395E+11 | 30994.82 | 27-JAN-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124949E+11 | 29422.45 | 01-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.917673E+10 | 29384.59 | 04-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372628E+10 | 18449.77 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231916E+10 | 14832.65 | 08-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.187441E+09 | 6624.91 | 16-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 793058.96 | 630.23 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28518517.79 | 2096.31 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.812606E+09 | 7174.44 | 19-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268127E+10 | 19516.55 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.673048E+10 | 23930.61 | 27-NOV-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145979E+11 | 31127.41 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 793058.96 | 630.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196395E+11 | 31127.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345096E+10 | 18791.37 | 09-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100681E+10 | 18778.52 | 13-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.321260E+09 | 18717.54 | 07-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 478067.63 | 5433.64 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240816E+09 | 18772.07 | 29-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134891E+10 | 18765.62 | 19-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.636923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.345096E+10 | 18791.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.410937E+10 | 11436.63 | 27-JAN-08:28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146535E+10 | 10817.62 | 01-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634552E+09 | 10801.66 | 04-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69543444.00 | 10222.39 | 22-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71703792.95 | 10213.12 | 08-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 585577.01 | 1226.08 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 43352493.27 | 10207.24 | 10-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.648574E+09 | 10241.85 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220160E+10 | 11490.69 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.924463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410937E+10 | 11490.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369910E+10 | 8445.52 | 27-JAN-21:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138329E+10 | 7929.49 | 01-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.501525E+09 | 7917.56 | 04-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 30323079.85 | 7475.82 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32143587.67 | 7476.64 | 23-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 637830.70 | 1553.21 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35762618.73 | 7484.65 | 06-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.587444E+09 | 7505.48 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.201447E+10 | 8425.95 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.828470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.369910E+10 | 8445.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.603927E+10 | 8784.76 | 27-JAN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261736E+10 | 8622.27 | 01-FEB-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100958E+10 | 8267.15 | 04-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83000589.77 | 7757.58 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61438131.21 | 7760.92 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2400392.34 | 2459.85 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80224643.66 | 7764.03 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105113E+10 | 7791.35 | 30-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352338E+10 | 8695.72 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.603927E+10 | 8784.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.406359E+10 | 8775.14 | 27-JAN-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150326E+10 | 8584.06 | 01-FEB-08:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.617525E+09 | 8159.62 | 04-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53415903.78 | 7703.41 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42572284.24 | 7709.10 | 09-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1287747.63 | 1800.68 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45828713.53 | 7712.62 | 06-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627478E+09 | 7734.33 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218915E+10 | 8684.31 | 29-DEC-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406359E+10 | 8775.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.214345E+11 | 29329.25 | 10-JAN-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132864E+11 | 28482.84 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.997536E+10 | 28127.52 | 04-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.416511E+10 | 17845.43 | 29-APR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.258002E+10 | 14719.62 | 08-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.299753E+09 | 7475.30 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8126747.95 | 1417.40 | 08-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98313214.41 | 3186.46 | 28-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104992E+10 | 10277.71 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.315783E+10 | 20004.03 | 10-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.757218E+10 | 25087.19 | 27-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160810E+11 | 28681.09 | 28-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.797085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8126747.95 | 1417.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.214345E+11 | 29329.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.966224E+10 | 26645.99 | 09-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396163E+10 | 26097.68 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166310E+10 | 26032.63 | 06-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129277E+09 | 25507.12 | 21-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166123E+09 | 25688.00 | 08-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124585E+09 | 25587.78 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178309E+10 | 25683.80 | 29-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.580165E+10 | 26249.17 | 29-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.966224E+10 | 26645.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.697308E+10 | 13818.81 | 27-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299226E+10 | 13543.06 | 01-FEB-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179903E+10 | 13094.03 | 04-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408346E+09 | 12208.75 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.312785E+09 | 12197.83 | 09-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3950996.38 | 6530.38 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1267988.12 | 2852.06 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41047035.11 | 11596.63 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283810E+09 | 12208.68 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165340E+10 | 12199.35 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448526E+10 | 13368.33 | 28-DEC-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697308E+10 | 13818.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.594956E+10 | 9712.08 | 27-JAN-17:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259546E+10 | 9136.41 | 01-FEB-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131869E+10 | 9151.38 | 04-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209667E+09 | 8510.86 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141917E+09 | 8519.15 | 09-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94353.61 | 67.12 | 16-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25322410.69 | 7636.56 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.226947E+09 | 8504.03 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143161E+10 | 8523.40 | 21-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391369E+10 | 9469.48 | 29-DEC-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.594956E+10 | 9712.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.948730E+10 | 10716.78 | 27-JAN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.470212E+10 | 10565.20 | 01-FEB-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252988E+10 | 10125.64 | 04-MAR-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.490118E+09 | 9369.67 | 14-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.295133E+09 | 9376.99 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 304231.31 | 1483.75 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 124632.02 | 623.16 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59606078.35 | 9378.65 | 13-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499573E+09 | 9378.79 | 05-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258365E+10 | 9497.39 | 27-NOV-08:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654638E+10 | 10496.06 | 29-DEC-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.948730E+10 | 10716.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.644083E+10 | 10443.90 | 27-JAN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281227E+10 | 10293.46 | 01-FEB-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154724E+10 | 9770.41 | 04-MAR-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.288895E+09 | 9087.73 | 27-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195603E+09 | 9096.40 | 10-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2826295.01 | 4309.95 | 17-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1211853.98 | 2198.64 | 18-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35389606.99 | 7670.41 | 19-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.284597E+09 | 9081.65 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152469E+10 | 9089.68 | 27-NOV-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414432E+10 | 10179.99 | 29-DEC-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.644083E+10 | 10443.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 54488.82 | 50822.52 | 363.26 | 24-JAN-07:05 | 338.82 | 0.00 |
February | 0.00 | 0.00 | 0.315747E+09 | 0.315094E+09 | 17348.27 | 27-FEB-12:00 | 17348.27 | 0.00 |
March | 0.00 | 0.00 | 0.147711E+09 | 0.147361E+09 | 6687.95 | 23-MAR-11:00 | 6687.95 | 0.00 |
April | 0.00 | 0.00 | 0.418659E+10 | 0.415946E+10 | 32816.40 | 06-APR-16:00 | 32816.40 | 0.00 |
May | 0.00 | 0.00 | 0.967670E+10 | 0.944549E+10 | 52319.13 | 19-MAY-15:30 | 52319.13 | 0.00 |
June | 0.00 | 0.00 | 0.277581E+11 | 0.265402E+11 | 65688.82 | 20-JUN-16:00 | 57595.27 | 0.00 |
July | 0.00 | 0.00 | 0.480109E+11 | 0.463463E+11 | 81417.45 | 17-JUL-16:00 | 81417.45 | 0.00 |
August | 0.00 | 0.00 | 0.409376E+11 | 0.404970E+11 | 73929.23 | 07-AUG-16:00 | 73929.23 | 0.00 |
September | 0.00 | 0.00 | 0.211079E+11 | 0.193572E+11 | 97035.80 | 07-SEP-14:55 | 51207.26 | 0.00 |
October | 0.00 | 0.00 | 0.737840E+10 | 0.733494E+10 | 48418.97 | 18-OCT-15:50 | 48418.97 | 0.00 |
November | 0.00 | 0.00 | 0.118051E+10 | 0.117022E+10 | 24655.18 | 03-NOV-15:30 | 24655.18 | 0.00 |
December | 0.00 | 0.00 | 1841089.41 | 1762125.63 | 1191.39 | 07-DEC-15:50 | 1170.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160702E+12 | 0.155315E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 54488.82 | 50822.52 | 363.26 | 338.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.480109E+11 | 0.463463E+11 | 97035.80 | 81417.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.363499E+09 | 0.362984E+09 | 12581.91 | 28-FEB-15:40 | 12581.91 | 0.00 |
March | 0.00 | 0.00 | 0.448737E+09 | 0.448284E+09 | 11395.62 | 28-MAR-15:40 | 11395.62 | 0.00 |
April | 0.00 | 0.00 | 0.205025E+10 | 0.203209E+10 | 28854.80 | 06-APR-16:00 | 28854.80 | 0.00 |
May | 0.00 | 0.00 | 0.745524E+10 | 0.725919E+10 | 53078.16 | 19-MAY-15:30 | 53078.16 | 0.00 |
June | 0.00 | 0.00 | 0.262308E+11 | 0.250824E+11 | 62611.83 | 21-JUN-14:05 | 56384.10 | 0.00 |
July | 0.00 | 0.00 | 0.439514E+11 | 0.425541E+11 | 76758.45 | 17-JUL-15:40 | 76758.45 | 0.00 |
August | 0.00 | 0.00 | 0.369462E+11 | 0.365316E+11 | 72705.50 | 07-AUG-15:20 | 72705.50 | 0.00 |
September | 0.00 | 0.00 | 0.170632E+11 | 0.156351E+11 | 91291.87 | 07-SEP-14:55 | 48176.10 | 0.00 |
October | 0.00 | 0.00 | 0.355323E+10 | 0.352720E+10 | 43115.50 | 18-OCT-15:50 | 43115.50 | 0.00 |
November | 0.00 | 0.00 | 0.379875E+09 | 0.368220E+09 | 8590.81 | 09-NOV-15:10 | 8590.81 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138442E+12 | 0.133801E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.439514E+11 | 0.425541E+11 | 91291.87 | 76758.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 807627.15 | 795185.78 | 894.13 | 10-JAN-06:40 | 894.13 | 0.00 |
February | 0.00 | 0.00 | 0.306848E+09 | 0.305472E+09 | 10616.51 | 28-FEB-15:40 | 10616.51 | 0.00 |
March | 0.00 | 0.00 | 0.560481E+09 | 0.559117E+09 | 12828.15 | 28-MAR-15:40 | 12828.15 | 0.00 |
April | 0.00 | 0.00 | 0.227082E+10 | 0.223870E+10 | 29732.43 | 06-APR-16:00 | 29732.43 | 0.00 |
May | 0.00 | 0.00 | 0.782449E+10 | 0.755489E+10 | 61383.40 | 19-MAY-15:30 | 61383.40 | 0.00 |
June | 0.00 | 0.00 | 0.280127E+11 | 0.267047E+11 | 70292.75 | 20-JUN-15:10 | 62526.66 | 0.00 |
July | 0.00 | 0.00 | 0.468101E+11 | 0.451920E+11 | 87870.67 | 17-JUL-15:20 | 87870.67 | 0.00 |
August | 0.00 | 0.00 | 0.388698E+11 | 0.383179E+11 | 82585.94 | 06-AUG-16:11 | 82585.94 | 0.00 |
September | 0.00 | 0.00 | 0.175473E+11 | 0.159705E+11 | 93884.37 | 07-SEP-15:20 | 50952.75 | 0.00 |
October | 0.00 | 0.00 | 0.334340E+10 | 0.328476E+10 | 44013.60 | 18-OCT-15:00 | 44013.60 | 0.00 |
November | 0.00 | 0.00 | 0.206408E+09 | 0.186714E+09 | 5235.18 | 09-NOV-14:50 | 5105.73 | 0.00 |
December | 0.00 | 0.00 | 490818.53 | 479817.80 | 597.57 | 30-DEC-06:20 | 597.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145754E+12 | 0.140316E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 490818.53 | 479817.80 | 597.57 | 597.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.468101E+11 | 0.451920E+11 | 93884.37 | 87870.67 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 53427.03 | 254752.16 | 17-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30689.81 | 236463.54 | 13-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17096.36 | 221423.37 | 06-MAR-07:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5601.78 | 213262.08 | 03-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 3462.28 | 174603.89 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 303.85 | 39200.03 | 17-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.07 | 17897.57 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 112.11 | 30000.80 | 18-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1049.82 | 100564.59 | 20-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3699.43 | 179889.30 | 06-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13989.22 | 205657.65 | 27-NOV-07:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 34940.24 | 230610.36 | 29-DEC-07:05 |
Annual Sum or Average | 0.00 | 13651.92 | ||||
Minimum of Months | 0.00 | 0.00 | 14.07 | 17897.57 | ||
Maximum of Months | 0.00 | 0.00 | 53427.03 | 254752.16 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1916.14 | 7053.97 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1961.40 | 7091.44 | 17-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2076.18 | 7078.82 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1860.80 | 6886.30 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1827.61 | 6581.42 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1762.01 | 6179.91 | 01-JUN-11:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1525.91 | 5809.89 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1650.70 | 5604.88 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1556.08 | 5739.51 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1626.60 | 6081.19 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1756.14 | 6469.99 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1783.17 | 6811.81 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1774.15 | ||||
Minimum of Months | 0.00 | 0.00 | 1525.91 | 5604.88 | ||
Maximum of Months | 0.00 | 0.00 | 2076.18 | 7091.44 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164837E+10 | 0.43 | 2944.91 | 09-JAN-06:02 | 0.92 |
February | 0.137294E+10 | 0.39 | 3085.82 | 28-FEB-16:30 | 0.94 |
March | 0.165883E+10 | 0.39 | 5266.30 | 01-MAR-07:01 | 1.28 |
April | 0.183643E+10 | 0.37 | 5245.95 | 27-APR-06:02 | 1.28 |
May | 0.257893E+10 | 0.41 | 7689.17 | 23-MAY-06:02 | 1.62 |
June | 0.495937E+10 | 0.58 | 9931.38 | 29-JUN-14:30 | 1.89 |
July | 0.657514E+10 | 0.66 | 12129.42 | 25-JUL-12:10 | 2.14 |
August | 0.626427E+10 | 0.65 | 12129.42 | 07-AUG-06:03 | 2.15 |
September | 0.401581E+10 | 0.52 | 12129.42 | 05-SEP-06:03 | 2.14 |
October | 0.251879E+10 | 0.40 | 5900.83 | 05-OCT-06:01 | 1.37 |
November | 0.162950E+10 | 0.36 | 5657.27 | 10-NOV-07:01 | 1.34 |
December | 0.141090E+10 | 0.37 | 1611.94 | 01-DEC-06:01 | 0.69 |
Annual Sum or Average | 0.364693E+11 | 0.46 | |||
Minimum of Months | 0.137294E+10 | 0.36 | 1611.94 | 0.69 | |
Maximum of Months | 0.657514E+10 | 0.66 | 12129.42 | 2.15 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162074E+10 | 0.44 | 3112.56 | 02-JAN-07:02 | 0.97 |
February | 0.128072E+10 | 0.41 | 3112.56 | 01-FEB-07:01 | 0.98 |
March | 0.147806E+10 | 0.41 | 3112.56 | 06-MAR-07:03 | 0.98 |
April | 0.162928E+10 | 0.39 | 5343.63 | 25-APR-15:40 | 1.34 |
May | 0.231059E+10 | 0.42 | 7920.37 | 19-MAY-15:30 | 1.70 |
June | 0.452975E+10 | 0.58 | 11411.43 | 26-JUN-06:02 | 2.14 |
July | 0.589006E+10 | 0.64 | 11411.43 | 03-JUL-06:02 | 2.14 |
August | 0.543738E+10 | 0.62 | 11411.43 | 07-AUG-09:10 | 2.14 |
September | 0.305500E+10 | 0.48 | 11411.43 | 07-SEP-14:55 | 2.12 |
October | 0.177666E+10 | 0.38 | 5955.78 | 18-OCT-16:00 | 1.43 |
November | 0.130419E+10 | 0.38 | 3112.56 | 27-NOV-07:11 | 0.98 |
December | 0.131473E+10 | 0.39 | 3112.56 | 16-DEC-07:03 | 0.98 |
Annual Sum or Average | 0.316272E+11 | 0.46 | |||
Minimum of Months | 0.128072E+10 | 0.38 | 3112.56 | 0.97 | |
Maximum of Months | 0.589006E+10 | 0.64 | 11411.43 | 2.14 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.199167E+10 | 0.49 | 2870.99 | 02-JAN-05:01 | 0.84 |
February | 0.145206E+10 | 0.44 | 2870.99 | 01-FEB-06:01 | 0.85 |
March | 0.158572E+10 | 0.45 | 2870.99 | 01-MAR-07:01 | 0.84 |
April | 0.155321E+10 | 0.40 | 4617.50 | 25-APR-15:50 | 1.10 |
May | 0.211820E+10 | 0.42 | 7533.59 | 19-MAY-15:30 | 1.47 |
June | 0.393797E+10 | 0.51 | 8886.45 | 29-JUN-14:30 | 1.64 |
July | 0.514526E+10 | 0.55 | 12488.20 | 17-JUL-15:00 | 2.02 |
August | 0.466172E+10 | 0.53 | 12308.57 | 07-AUG-15:40 | 2.01 |
September | 0.258383E+10 | 0.45 | 9341.79 | 05-SEP-14:40 | 1.68 |
October | 0.154959E+10 | 0.38 | 4863.29 | 18-OCT-15:40 | 1.14 |
November | 0.141128E+10 | 0.42 | 2870.99 | 06-NOV-07:02 | 0.84 |
December | 0.173216E+10 | 0.48 | 2870.99 | 01-DEC-06:01 | 0.85 |
Annual Sum or Average | 0.297227E+11 | 0.46 | |||
Minimum of Months | 0.141128E+10 | 0.38 | 2870.99 | 0.84 | |
Maximum of Months | 0.514526E+10 | 0.55 | 12488.20 | 2.02 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.934644E+09 | 0.849591E+09 | 1019.52 | 09-JAN-07:01 | 926.74 | 926.74 | 43.22 | 3.29 |
February | 0.533915E+09 | 0.485329E+09 | 967.13 | 04-FEB-07:15 | 879.12 | 879.12 | 43.04 | 3.14 |
March | 0.348303E+09 | 0.316607E+09 | 946.88 | 06-MAR-07:40 | 860.71 | 860.71 | 43.57 | 3.07 |
April | 0.111233E+09 | 0.101111E+09 | 817.01 | 29-APR-06:03 | 742.67 | 742.67 | 42.17 | 2.40 |
May | 74377894.19 | 67609505.82 | 804.85 | 08-MAY-06:01 | 731.61 | 731.61 | 42.78 | 2.29 |
June | 7711697.14 | 7009932.70 | 249.63 | 17-JUN-06:03 | 226.92 | 226.92 | 27.99 | 0.29 |
July | 406783.91 | 369766.58 | 142.31 | 05-JUL-06:05 | 129.36 | 129.36 | 32.69 | 0.16 |
August | 3494304.22 | 3176322.53 | 218.36 | 18-AUG-06:03 | 198.49 | 198.49 | 31.43 | 0.25 |
September | 22435461.33 | 20393834.35 | 600.96 | 19-SEP-06:03 | 546.27 | 546.27 | 35.61 | 0.97 |
October | 76087909.70 | 69163909.92 | 820.54 | 10-OCT-06:01 | 745.87 | 745.87 | 42.99 | 2.43 |
November | 0.275507E+09 | 0.250436E+09 | 899.16 | 27-NOV-07:25 | 817.34 | 817.34 | 43.12 | 2.90 |
December | 0.664365E+09 | 0.603908E+09 | 960.02 | 29-DEC-07:01 | 872.65 | 872.65 | 44.38 | 3.11 |
Annual Sum or Average | 0.305248E+10 | 0.277471E+10 | ||||||
Minimum of Months | 406783.91 | 369766.58 | 142.31 | 129.36 | 129.36 | 27.99 | 0.16 | |
Maximum of Months | 0.934644E+09 | 0.849591E+09 | 1019.52 | 926.74 | 926.74 | 44.38 | 3.29 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 57.91 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:01 | 2.06 | 2.06 | 56.77 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:01 | 2.06 | 2.06 | 56.77 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 56.49 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:01 | 2.06 | 2.06 | 57.26 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 56.94 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 57.03 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 57.23 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 57.24 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.12 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:05 | 2.06 | 2.06 | 56.90 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:01 | 2.06 | 2.06 | 57.05 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 56.49 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.12 | 0.05 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 44.36 | 44.36 | 53427.03 | 254752.16 | 17-JAN-06:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 41.18 | 41.18 | 30689.81 | 236463.54 | 13-FEB-06:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 31.06 | 31.06 | 17096.36 | 221423.37 | 06-MAR-07:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.23 | 32.23 | 5601.78 | 213262.08 | 03-APR-06:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.59 | 26.59 | 3462.28 | 174603.89 | 09-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 44.87 | 44.87 | 303.85 | 39200.03 | 17-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.36 | 32.36 | 14.07 | 17897.57 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 38.26 | 38.26 | 112.11 | 30000.80 | 18-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 38.00 | 38.00 | 1049.82 | 100564.59 | 20-SEP-06:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33.77 | 33.77 | 3699.43 | 179889.30 | 06-OCT-06:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32.33 | 32.33 | 13989.22 | 205657.65 | 27-NOV-07:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 38.68 | 38.68 | 34940.24 | 230610.36 | 29-DEC-07:05 |
Annual Sum or Average | 0.00 | 13651.92 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.59 | 26.59 | 14.07 | 17897.57 | ||
Maximum of Months | 0.00 | 0.00 | 44.87 | 44.87 | 53427.03 | 254752.16 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.91 | 57.91 | 1916.14 | 7053.97 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.29 | 57.29 | 1961.40 | 7091.44 | 17-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.28 | 57.28 | 2076.18 | 7078.82 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.35 | 57.35 | 1860.80 | 6886.30 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.99 | 57.99 | 1827.61 | 6581.42 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.63 | 57.63 | 1762.01 | 6179.91 | 01-JUN-11:17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.76 | 57.76 | 1525.91 | 5809.89 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.86 | 57.86 | 1650.70 | 5604.88 | 01-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.87 | 57.87 | 1556.08 | 5739.51 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.90 | 56.90 | 1626.60 | 6081.19 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.68 | 57.68 | 1756.14 | 6469.99 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.53 | 57.53 | 1783.17 | 6811.81 | 29-DEC-12:35 |
Annual Sum or Average | 0.00 | 1774.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.90 | 56.90 | 1525.91 | 5604.88 | ||
Maximum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 2076.18 | 7091.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.431751E+11 | 0.00 | 0.00 | 0.164838E+10 | 0.00 | 0.00 |
February | 0.240076E+11 | 0.00 | 0.00 | 0.145077E+10 | 0.00 | 0.00 |
March | 0.150683E+11 | 0.00 | 0.00 | 0.169782E+10 | 0.00 | 0.00 |
April | 0.498952E+10 | 0.00 | 0.00 | 0.282145E+10 | 0.00 | 0.00 |
May | 0.311802E+10 | 0.00 | 0.00 | 0.485979E+10 | 0.00 | 0.00 |
June | 0.311585E+09 | 0.00 | 0.00 | 0.113531E+11 | 0.00 | 0.00 |
July | 24277303.59 | 0.00 | 0.00 | 0.179795E+11 | 0.00 | 0.00 |
August | 0.174590E+09 | 0.00 | 0.00 | 0.158689E+11 | 0.00 | 0.00 |
September | 0.719633E+09 | 0.00 | 0.00 | 0.891377E+10 | 0.00 | 0.00 |
October | 0.252735E+10 | 0.00 | 0.00 | 0.423287E+10 | 0.00 | 0.00 |
November | 0.101145E+11 | 0.00 | 0.00 | 0.192029E+10 | 0.00 | 0.00 |
December | 0.274468E+11 | 0.00 | 0.00 | 0.141140E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.131677E+12 | 0.00 | 0.00 | 0.741580E+11 | 0.00 | 0.00 |
Minimum of Months | 24277303.59 | 0.00 | 0.00 | 0.141140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.431751E+11 | 0.00 | 0.00 | 0.179795E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.410018E+11 | 0.00 | 0.00 | 0.162074E+10 | 0.00 | 0.00 |
February | 0.204710E+11 | 0.00 | 0.00 | 0.137180E+10 | 0.00 | 0.00 |
March | 0.122612E+11 | 0.00 | 0.00 | 0.159215E+10 | 0.00 | 0.00 |
April | 0.396256E+10 | 0.00 | 0.00 | 0.212195E+10 | 0.00 | 0.00 |
May | 0.252750E+10 | 0.00 | 0.00 | 0.404702E+10 | 0.00 | 0.00 |
June | 0.187441E+09 | 0.00 | 0.00 | 0.105681E+11 | 0.00 | 0.00 |
July | 793058.96 | 0.00 | 0.00 | 0.163591E+11 | 0.00 | 0.00 |
August | 28518517.79 | 0.00 | 0.00 | 0.141443E+11 | 0.00 | 0.00 |
September | 0.817518E+09 | 0.00 | 0.00 | 0.701822E+10 | 0.00 | 0.00 |
October | 0.288644E+10 | 0.00 | 0.00 | 0.260046E+10 | 0.00 | 0.00 |
November | 0.988592E+10 | 0.00 | 0.00 | 0.140339E+10 | 0.00 | 0.00 |
December | 0.258754E+11 | 0.00 | 0.00 | 0.131473E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.119906E+12 | 0.00 | 0.00 | 0.641619E+11 | 0.00 | 0.00 |
Minimum of Months | 793058.96 | 0.00 | 0.00 | 0.131473E+10 | 0.00 | 0.00 |
Maximum of Months | 0.410018E+11 | 0.00 | 0.00 | 0.163591E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.599476E+11 | 0.00 | 0.00 | 0.199189E+10 | 0.00 | 0.00 |
February | 0.303501E+11 | 0.00 | 0.00 | 0.153066E+10 | 0.00 | 0.00 |
March | 0.188333E+11 | 0.00 | 0.00 | 0.172917E+10 | 0.00 | 0.00 |
April | 0.569141E+10 | 0.00 | 0.00 | 0.210648E+10 | 0.00 | 0.00 |
May | 0.369158E+10 | 0.00 | 0.00 | 0.395455E+10 | 0.00 | 0.00 |
June | 0.306928E+09 | 0.00 | 0.00 | 0.104358E+11 | 0.00 | 0.00 |
July | 8126747.95 | 0.00 | 0.00 | 0.163970E+11 | 0.00 | 0.00 |
August | 0.100918E+09 | 0.00 | 0.00 | 0.139196E+11 | 0.00 | 0.00 |
September | 0.121128E+10 | 0.00 | 0.00 | 0.671428E+10 | 0.00 | 0.00 |
October | 0.457734E+10 | 0.00 | 0.00 | 0.234505E+10 | 0.00 | 0.00 |
November | 0.165486E+11 | 0.00 | 0.00 | 0.146607E+10 | 0.00 | 0.00 |
December | 0.409723E+11 | 0.00 | 0.00 | 0.173229E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.182239E+12 | 0.00 | 0.00 | 0.643228E+11 | 0.00 | 0.00 |
Minimum of Months | 8126747.95 | 0.00 | 0.00 | 0.146607E+10 | 0.00 | 0.00 |
Maximum of Months | 0.599476E+11 | 0.00 | 0.00 | 0.163970E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164837E+10 | 54488.82 | 0.431751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137294E+10 | 0.315747E+09 | 0.240076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165883E+10 | 0.147711E+09 | 0.150683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183643E+10 | 0.418659E+10 | 0.498952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257893E+10 | 0.967670E+10 | 0.311802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.495937E+10 | 0.277581E+11 | 0.311585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.657514E+10 | 0.480109E+11 | 24277303.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.626427E+10 | 0.409376E+11 | 0.174590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.401581E+10 | 0.211079E+11 | 0.719633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251879E+10 | 0.737840E+10 | 0.252735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162950E+10 | 0.118051E+10 | 0.101145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141090E+10 | 1841089.41 | 0.274468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364693E+11 | 0.160702E+12 | 0.131677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137294E+10 | 54488.82 | 24277303.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657514E+10 | 0.480109E+11 | 0.431751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162074E+10 | 0.00 | 0.410018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128072E+10 | 0.363499E+09 | 0.204710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147806E+10 | 0.448737E+09 | 0.122612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162928E+10 | 0.205025E+10 | 0.396256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231059E+10 | 0.745524E+10 | 0.252750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.452975E+10 | 0.262308E+11 | 0.187441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.589006E+10 | 0.439514E+11 | 793058.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.543738E+10 | 0.369462E+11 | 28518517.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305500E+10 | 0.170632E+11 | 0.817518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177666E+10 | 0.355323E+10 | 0.288644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130419E+10 | 0.379875E+09 | 0.988592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131473E+10 | 0.00 | 0.258754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316272E+11 | 0.138442E+12 | 0.119906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128072E+10 | 0.00 | 793058.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.589006E+10 | 0.439514E+11 | 0.410018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.199167E+10 | 807627.15 | 0.599476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145206E+10 | 0.306848E+09 | 0.303501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158572E+10 | 0.560481E+09 | 0.188333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155321E+10 | 0.227082E+10 | 0.569141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211820E+10 | 0.782449E+10 | 0.369158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.393797E+10 | 0.280127E+11 | 0.306928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.514526E+10 | 0.468101E+11 | 8126747.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.466172E+10 | 0.388698E+11 | 0.100918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258383E+10 | 0.175473E+11 | 0.121128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154959E+10 | 0.334340E+10 | 0.457734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141128E+10 | 0.206408E+09 | 0.165486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173216E+10 | 490818.53 | 0.409723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297227E+11 | 0.145754E+12 | 0.182239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141128E+10 | 490818.53 | 8126747.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.514526E+10 | 0.468101E+11 | 0.599476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164837E+10 | 0.431751E+11 | 0.00 | 0.00 | 14788.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137294E+10 | 0.240076E+11 | 0.00 | 0.00 | 77827102.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165883E+10 | 0.150683E+11 | 0.00 | 0.00 | 38985503.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183643E+10 | 0.498952E+10 | 0.00 | 0.00 | 0.985018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.257893E+10 | 0.311802E+10 | 0.00 | 0.00 | 0.228086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.495937E+10 | 0.311585E+09 | 0.00 | 0.00 | 0.639374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.657514E+10 | 24277303.59 | 0.00 | 0.00 | 0.114044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.626427E+10 | 0.174590E+09 | 0.00 | 0.00 | 0.960462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.401581E+10 | 0.719633E+09 | 0.00 | 0.00 | 0.489796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251879E+10 | 0.252735E+10 | 0.00 | 0.00 | 0.171408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162950E+10 | 0.101145E+11 | 0.00 | 0.00 | 0.290794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141090E+10 | 0.274468E+11 | 0.00 | 0.00 | 497317.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364693E+11 | 0.131677E+12 | 0.00 | 0.00 | 0.376888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137294E+10 | 24277303.59 | 0.00 | 0.00 | 14788.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.657514E+10 | 0.431751E+11 | 0.00 | 0.00 | 0.114044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.162074E+10 | 0.410018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128072E+10 | 0.204710E+11 | 0.00 | 0.00 | 91072421.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147806E+10 | 0.122612E+11 | 0.00 | 0.00 | 0.114093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162928E+10 | 0.396256E+10 | 0.00 | 0.00 | 0.492667E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231059E+10 | 0.252750E+10 | 0.00 | 0.00 | 0.173642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.452975E+10 | 0.187441E+09 | 0.00 | 0.00 | 0.603831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.589006E+10 | 793058.96 | 0.00 | 0.00 | 0.104691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.543738E+10 | 28518517.79 | 0.00 | 0.00 | 0.870692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.305500E+10 | 0.817518E+09 | 0.00 | 0.00 | 0.396322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177666E+10 | 0.288644E+10 | 0.00 | 0.00 | 0.823798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130419E+10 | 0.988592E+10 | 0.00 | 0.00 | 99192591.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131473E+10 | 0.258754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316272E+11 | 0.119906E+12 | 0.00 | 0.00 | 0.325348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128072E+10 | 793058.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.589006E+10 | 0.410018E+11 | 0.00 | 0.00 | 0.104691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.199167E+10 | 0.599476E+11 | 0.00 | 0.00 | 218667.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145206E+10 | 0.303501E+11 | 0.00 | 0.00 | 78603204.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.158572E+10 | 0.188333E+11 | 0.00 | 0.00 | 0.143454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155321E+10 | 0.569141E+10 | 0.00 | 0.00 | 0.553270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211820E+10 | 0.369158E+10 | 0.00 | 0.00 | 0.183635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.393797E+10 | 0.306928E+09 | 0.00 | 0.00 | 0.649778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.514526E+10 | 8126747.95 | 0.00 | 0.00 | 0.112517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.466172E+10 | 0.100918E+09 | 0.00 | 0.00 | 0.925790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258383E+10 | 0.121128E+10 | 0.00 | 0.00 | 0.413044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154959E+10 | 0.457734E+10 | 0.00 | 0.00 | 0.795458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141128E+10 | 0.165486E+11 | 0.00 | 0.00 | 54788707.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173216E+10 | 0.409723E+11 | 0.00 | 0.00 | 133130.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297227E+11 | 0.182239E+12 | 0.00 | 0.00 | 0.346001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141128E+10 | 8126747.95 | 0.00 | 0.00 | 133130.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.514526E+10 | 0.599476E+11 | 0.00 | 0.00 | 0.112517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133724E+11 | 0.00 | 0.00 | 2710681.03 | 0.00 | 72526658.76 | 0.409898E+10 | 0.00 | 0.27 |
February | 0.816018E+10 | 0.00 | 0.00 | 11062003.91 | 0.00 | 1728654.71 | 0.791330E+10 | 0.00 | 0.35 |
March | 0.325144E+10 | 0.00 | 0.00 | 27737114.28 | 0.00 | 0.00 | 0.165771E+11 | 0.00 | 0.43 |
April | 0.607540E+09 | 0.00 | 0.00 | 34025514.53 | 0.00 | 0.00 | 0.163836E+11 | 0.00 | 0.51 |
May | 0.656930E+09 | 14970611.40 | 0.00 | 39334841.39 | 2556086.41 | 0.00 | 0.172430E+11 | 0.00 | 0.72 |
June | 0.509945E+09 | 0.182941E+09 | 0.00 | 44158779.87 | 31369666.34 | 0.00 | 0.156567E+11 | 0.00 | 1.05 |
July | 0.544797E+09 | 0.382651E+09 | 0.00 | 37119552.26 | 19946232.78 | 0.00 | 0.848215E+10 | 0.00 | 0.88 |
August | 0.527856E+09 | 0.212820E+09 | 0.00 | 45012510.86 | 19098815.50 | 0.00 | 0.131305E+11 | 0.00 | 1.03 |
September | 0.579612E+09 | 0.269408E+09 | 0.00 | 42345744.92 | 17414567.22 | 0.00 | 0.166255E+11 | 0.00 | 0.93 |
October | 0.580684E+09 | 0.00 | 0.00 | 41855980.09 | 0.00 | 0.00 | 0.184923E+11 | 0.00 | 0.67 |
November | 0.190486E+10 | 0.00 | 0.00 | 28217547.95 | 0.00 | 0.00 | 0.158710E+11 | 0.00 | 0.46 |
December | 0.864635E+10 | 0.00 | 0.00 | 12410568.76 | 0.00 | 0.00 | 0.906212E+10 | 0.00 | 0.32 |
Annual Sum or Average | 0.393426E+11 | 0.106279E+10 | 0.00 | 0.365991E+09 | 90385368.24 | 74255313.47 | 0.159536E+12 | 0.00 | 0.63 |
Minimum of Months | 0.509945E+09 | 0.00 | 0.00 | 2710681.03 | 0.00 | 0.00 | 0.409898E+10 | 0.00 | 0.27 |
Maximum of Months | 0.133724E+11 | 0.382651E+09 | 0.00 | 45012510.86 | 31369666.34 | 72526658.76 | 0.184923E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341298E+10 | 0.00 | 0.00 | 0.27 |
February | 0.124867E+11 | 0.00 | 0.00 | 750975.83 | 0.00 | 0.111065E+10 | 0.499403E+09 | 0.00 | 0.30 |
March | 0.105674E+11 | 0.00 | 0.00 | 3882977.21 | 0.00 | 0.183393E+09 | 0.392812E+10 | 0.00 | 0.31 |
April | 0.504221E+10 | 0.00 | 0.00 | 10965387.94 | 0.00 | 0.00 | 0.764735E+10 | 0.00 | 0.40 |
May | 0.374417E+10 | 9973955.89 | 0.00 | 17104363.02 | 3609130.63 | 478112.20 | 0.908854E+10 | 0.00 | 0.51 |
June | 0.111598E+10 | 0.136765E+09 | 0.00 | 27374201.91 | 27025577.35 | 0.00 | 0.988311E+10 | 0.00 | 0.73 |
July | 0.767961E+09 | 0.266288E+09 | 0.00 | 24268794.53 | 15997901.29 | 0.00 | 0.536586E+10 | 0.00 | 0.62 |
August | 0.882976E+09 | 0.151644E+09 | 0.00 | 28267333.70 | 19572596.16 | 0.00 | 0.817052E+10 | 0.00 | 0.70 |
September | 0.164475E+10 | 0.196686E+09 | 0.00 | 21609664.61 | 16590032.62 | 0.00 | 0.976976E+10 | 0.00 | 0.61 |
October | 0.441343E+10 | 0.00 | 0.00 | 13919777.77 | 0.00 | 0.00 | 0.822755E+10 | 0.00 | 0.44 |
November | 0.924835E+10 | 0.00 | 0.00 | 4546305.86 | 0.00 | 94303010.63 | 0.302443E+10 | 0.00 | 0.31 |
December | 0.135439E+11 | 0.00 | 0.00 | 115267.91 | 0.00 | 0.151765E+10 | 0.210546E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.772799E+11 | 0.761357E+09 | 0.00 | 0.152805E+09 | 82795238.05 | 0.631945E+10 | 0.658152E+11 | 0.00 | 0.46 |
Minimum of Months | 0.767961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.138220E+11 | 0.266288E+09 | 0.00 | 28267333.70 | 27025577.35 | 0.341298E+10 | 0.988311E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.741369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789739E+10 | 0.00 | 0.00 | 0.25 |
February | 0.938972E+10 | 0.00 | 0.00 | 266061.27 | 0.00 | 0.330489E+10 | 0.164668E+09 | 0.00 | 0.28 |
March | 0.112525E+11 | 0.00 | 0.00 | 1034054.16 | 0.00 | 0.131642E+10 | 0.962163E+09 | 0.00 | 0.30 |
April | 0.717847E+10 | 0.00 | 0.00 | 6320270.45 | 0.00 | 56367721.36 | 0.433099E+10 | 0.00 | 0.38 |
May | 0.476002E+10 | 3325013.98 | 0.00 | 13164318.60 | 1672596.18 | 91258382.85 | 0.727947E+10 | 0.00 | 0.50 |
June | 0.156178E+10 | 99320051.42 | 0.00 | 25291601.28 | 6907059.69 | 0.00 | 0.880126E+10 | 0.00 | 0.73 |
July | 0.920454E+09 | 0.201680E+09 | 0.00 | 22838465.84 | 17621989.77 | 0.00 | 0.474159E+10 | 0.00 | 0.63 |
August | 0.120644E+10 | 0.104234E+09 | 0.00 | 25517823.91 | 16390718.36 | 0.00 | 0.683075E+10 | 0.00 | 0.67 |
September | 0.304073E+10 | 0.189271E+09 | 0.00 | 15056379.28 | 14075595.11 | 0.00 | 0.659897E+10 | 0.00 | 0.56 |
October | 0.637803E+10 | 0.00 | 0.00 | 6516834.55 | 0.00 | 73121846.52 | 0.422147E+10 | 0.00 | 0.39 |
November | 0.887825E+10 | 0.00 | 0.00 | 967918.31 | 0.00 | 0.124166E+10 | 0.922535E+09 | 0.00 | 0.29 |
December | 0.882866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486688E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.708087E+11 | 0.597831E+09 | 0.00 | 0.116974E+09 | 56667959.11 | 0.188480E+11 | 0.448539E+11 | 0.00 | 0.44 |
Minimum of Months | 0.920454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.112525E+11 | 0.201680E+09 | 0.00 | 25517823.91 | 17621989.77 | 0.789739E+10 | 0.880126E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530842E+10 | 0.00 | 0.00 | 0.38 |
February | 0.577170E+09 | 0.00 | 0.00 | 63.25 | 0.00 | 0.289895E+10 | 2308147.54 | 0.00 | 0.34 |
March | 0.147135E+10 | 0.00 | 0.00 | 14786.61 | 0.00 | 0.156118E+10 | 25871868.66 | 0.00 | 0.31 |
April | 0.157337E+10 | 0.00 | 0.00 | 748662.66 | 0.00 | 0.332894E+09 | 0.474819E+09 | 0.00 | 0.37 |
May | 0.119059E+10 | 1645493.09 | 0.00 | 2801102.39 | 353049.86 | 0.173544E+09 | 0.129101E+10 | 0.00 | 0.56 |
June | 0.432598E+09 | 33728939.75 | 0.00 | 6716348.64 | 1457934.95 | 288716.86 | 0.206768E+10 | 0.00 | 0.91 |
July | 0.211036E+09 | 71579718.08 | 0.00 | 6448838.17 | 3403692.37 | 0.00 | 0.116857E+10 | 0.00 | 0.80 |
August | 0.395159E+09 | 39844581.15 | 0.00 | 5942634.25 | 3459735.72 | 0.00 | 0.136548E+10 | 0.00 | 0.77 |
September | 0.980413E+09 | 56119438.32 | 0.00 | 2523905.57 | 2926170.89 | 33541637.50 | 0.891970E+09 | 0.00 | 0.55 |
October | 0.147296E+10 | 0.00 | 0.00 | 546719.43 | 0.00 | 0.378094E+09 | 0.302807E+09 | 0.00 | 0.37 |
November | 0.955824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156066E+10 | 0.00 | 0.00 | 0.31 |
December | 0.295326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370404E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.965603E+10 | 0.202918E+09 | 0.00 | 25743060.96 | 11600583.80 | 0.159516E+11 | 0.759051E+10 | 0.00 | 0.50 |
Minimum of Months | 0.100240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.157337E+10 | 71579718.08 | 0.00 | 6716348.64 | 3459735.72 | 0.530842E+10 | 0.206768E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346425E+10 | 0.00 | 0.00 | 0.40 |
February | 0.538810E+09 | 0.00 | 0.00 | 143575.31 | 0.00 | 0.155832E+10 | 85060469.73 | 0.00 | 0.34 |
March | 0.918021E+09 | 0.00 | 0.00 | 960162.02 | 0.00 | 0.727900E+09 | 0.482633E+09 | 0.00 | 0.35 |
April | 0.777321E+09 | 0.00 | 0.00 | 2831256.77 | 0.00 | 0.131914E+09 | 0.147622E+10 | 0.00 | 0.62 |
May | 0.493491E+09 | 1195311.00 | 0.00 | 4840070.44 | 222250.80 | 87965602.21 | 0.235862E+10 | 0.00 | 0.97 |
June | 0.175260E+09 | 27717989.55 | 0.00 | 10046505.99 | 702284.91 | 0.00 | 0.284079E+10 | 0.00 | 1.70 |
July | 85326104.45 | 61021105.58 | 0.00 | 10592293.91 | 1082390.57 | 0.00 | 0.190749E+10 | 0.00 | 1.66 |
August | 0.170500E+09 | 41209778.58 | 0.00 | 8498277.22 | 1625333.24 | 0.00 | 0.221716E+10 | 0.00 | 1.57 |
September | 0.441296E+09 | 48303072.18 | 0.00 | 4135280.89 | 1152162.41 | 13885776.42 | 0.157988E+10 | 0.00 | 0.96 |
October | 0.719103E+09 | 0.00 | 0.00 | 1546576.77 | 0.00 | 0.152350E+09 | 0.807235E+09 | 0.00 | 0.49 |
November | 0.725965E+09 | 0.00 | 0.00 | 83674.13 | 0.00 | 0.802207E+09 | 61224410.76 | 0.00 | 0.31 |
December | 0.331694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223516E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.558166E+10 | 0.179447E+09 | 0.00 | 43677673.44 | 4784421.93 | 0.917395E+10 | 0.138163E+11 | 0.00 | 0.81 |
Minimum of Months | 85326104.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.918021E+09 | 61021105.58 | 0.00 | 10592293.91 | 1625333.24 | 0.346425E+10 | 0.284079E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.670602E+09 | 0.00 | 0.00 | 956462.52 | 0.00 | 0.362486E+10 | 0.660849E+09 | 0.00 | 0.36 |
February | 0.890228E+09 | 0.00 | 0.00 | 3367405.74 | 0.00 | 0.168971E+10 | 0.169697E+10 | 0.00 | 0.51 |
March | 0.128516E+10 | 0.00 | 0.00 | 5445377.15 | 0.00 | 0.100995E+10 | 0.259786E+10 | 0.00 | 0.54 |
April | 0.111191E+10 | 0.00 | 0.00 | 5505541.44 | 0.00 | 0.285427E+09 | 0.284525E+10 | 0.00 | 0.73 |
May | 0.892669E+09 | 2329752.67 | 0.00 | 6866279.17 | 351501.62 | 0.178831E+09 | 0.318455E+10 | 0.00 | 0.92 |
June | 0.436116E+09 | 48132949.82 | 0.00 | 9899171.92 | 902842.33 | 2648313.29 | 0.284578E+10 | 0.00 | 1.22 |
July | 0.227933E+09 | 0.105293E+09 | 0.00 | 10160335.21 | 1337869.65 | 0.00 | 0.167641E+10 | 0.00 | 1.11 |
August | 0.342057E+09 | 80376624.80 | 0.00 | 11859447.66 | 1937489.95 | 276881.18 | 0.258646E+10 | 0.00 | 1.37 |
September | 0.675553E+09 | 0.137481E+09 | 0.00 | 9252674.62 | 724300.89 | 21686157.02 | 0.332503E+10 | 0.00 | 1.29 |
October | 0.915764E+09 | 0.00 | 0.00 | 8365425.45 | 0.00 | 0.172264E+09 | 0.377427E+10 | 0.00 | 0.98 |
November | 0.900081E+09 | 0.00 | 0.00 | 3996955.80 | 0.00 | 0.930248E+09 | 0.213356E+10 | 0.00 | 0.52 |
December | 0.856590E+09 | 0.00 | 0.00 | 1505441.30 | 0.00 | 0.239593E+10 | 0.906466E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.920466E+10 | 0.373613E+09 | 0.00 | 77180517.97 | 5254004.44 | 0.103118E+11 | 0.282335E+11 | 0.00 | 0.83 |
Minimum of Months | 0.227933E+09 | 0.00 | 0.00 | 956462.52 | 0.00 | 0.00 | 0.660849E+09 | 0.00 | 0.36 |
Maximum of Months | 0.128516E+10 | 0.137481E+09 | 0.00 | 11859447.66 | 1937489.95 | 0.362486E+10 | 0.377427E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211579E+09 | 0.00 | 0.00 | 1972.74 | 0.00 | 0.392022E+10 | 3242389.08 | 0.00 | 0.44 |
February | 0.483636E+09 | 0.00 | 0.00 | 350476.27 | 0.00 | 0.171150E+10 | 0.180505E+09 | 0.00 | 0.37 |
March | 0.859622E+09 | 0.00 | 0.00 | 1099482.87 | 0.00 | 0.901773E+09 | 0.557392E+09 | 0.00 | 0.38 |
April | 0.818571E+09 | 0.00 | 0.00 | 2642855.65 | 0.00 | 0.188529E+09 | 0.133287E+10 | 0.00 | 0.65 |
May | 0.542629E+09 | 1458250.51 | 0.00 | 5549965.89 | 223142.02 | 0.111151E+09 | 0.231122E+10 | 0.00 | 1.03 |
June | 0.256238E+09 | 38581369.22 | 0.00 | 8152108.24 | 254215.83 | 2197269.70 | 0.207918E+10 | 0.00 | 1.42 |
July | 0.122219E+09 | 83964843.33 | 0.00 | 7841360.68 | 702659.83 | 0.00 | 0.112835E+10 | 0.00 | 1.19 |
August | 0.226622E+09 | 45174329.67 | 0.00 | 6711686.07 | 750366.39 | 431385.54 | 0.137172E+10 | 0.00 | 1.21 |
September | 0.517813E+09 | 81303186.60 | 0.00 | 3588437.85 | 261059.81 | 20160688.30 | 0.126927E+10 | 0.00 | 0.91 |
October | 0.778569E+09 | 0.00 | 0.00 | 1732600.21 | 0.00 | 0.204592E+09 | 0.860172E+09 | 0.00 | 0.55 |
November | 0.609742E+09 | 0.00 | 0.00 | 332642.80 | 0.00 | 0.863733E+09 | 0.256991E+09 | 0.00 | 0.34 |
December | 0.342065E+09 | 0.00 | 0.00 | 17874.35 | 0.00 | 0.234870E+10 | 16039679.04 | 0.00 | 0.35 |
Annual Sum or Average | 0.576931E+10 | 0.250482E+09 | 0.00 | 38021463.61 | 2191443.89 | 0.102730E+11 | 0.113669E+11 | 0.00 | 0.74 |
Minimum of Months | 0.122219E+09 | 0.00 | 0.00 | 1972.74 | 0.00 | 0.00 | 3242389.08 | 0.00 | 0.34 |
Maximum of Months | 0.859622E+09 | 83964843.33 | 0.00 | 8152108.24 | 750366.39 | 0.392022E+10 | 0.231122E+10 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73981060.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503522E+10 | 0.00 | 0.00 | 0.35 |
February | 0.628289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281050E+10 | 0.00 | 0.00 | 0.32 |
March | 0.140831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156847E+10 | 0.00 | 0.00 | 0.29 |
April | 0.168075E+10 | 0.00 | 0.00 | 27998.94 | 0.00 | 0.277348E+09 | 10961832.55 | 0.00 | 0.27 |
May | 0.140005E+10 | 1325627.33 | 0.00 | 1042997.60 | 1340669.97 | 88837667.45 | 0.426984E+09 | 0.00 | 0.37 |
June | 0.459933E+09 | 33105417.63 | 0.00 | 4340402.56 | 6614514.80 | 0.00 | 0.138277E+10 | 0.00 | 0.64 |
July | 0.220647E+09 | 84298614.41 | 0.00 | 4684012.95 | 4205803.48 | 0.00 | 0.934936E+09 | 0.00 | 0.62 |
August | 0.391206E+09 | 44805000.16 | 0.00 | 4442437.26 | 4027119.59 | 0.00 | 0.116587E+10 | 0.00 | 0.63 |
September | 0.879890E+09 | 47551251.04 | 0.00 | 2417422.10 | 3679589.73 | 0.00 | 0.899704E+09 | 0.00 | 0.51 |
October | 0.152958E+10 | 0.00 | 0.00 | 666752.46 | 0.00 | 37946618.73 | 0.365081E+09 | 0.00 | 0.32 |
November | 0.152740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890551E+09 | 0.00 | 0.00 | 0.28 |
December | 0.574736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313213E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.107748E+11 | 0.211086E+09 | 0.00 | 17622023.87 | 19867697.57 | 0.138410E+11 | 0.518631E+10 | 0.00 | 0.41 |
Minimum of Months | 73981060.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.168075E+10 | 84298614.41 | 0.00 | 4684012.95 | 6614514.80 | 0.503522E+10 | 0.138277E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338352E+10 | 0.00 | 0.00 | 0.38 |
February | 0.591925E+09 | 0.00 | 0.00 | 123295.94 | 0.00 | 0.152608E+10 | 69114757.93 | 0.00 | 0.32 |
March | 0.107789E+10 | 0.00 | 0.00 | 501907.79 | 0.00 | 0.607797E+09 | 0.265238E+09 | 0.00 | 0.31 |
April | 0.843092E+09 | 0.00 | 0.00 | 1653988.02 | 0.00 | 80067831.16 | 0.671183E+09 | 0.00 | 0.37 |
May | 0.574058E+09 | 2285522.73 | 0.00 | 3345986.18 | 341481.19 | 35141684.33 | 0.135097E+10 | 0.00 | 0.65 |
June | 0.150629E+09 | 37885213.91 | 0.00 | 7631231.42 | 3794602.46 | 0.00 | 0.230147E+10 | 0.00 | 1.36 |
July | 72898290.98 | 86944176.13 | 0.00 | 8670336.09 | 1805118.76 | 0.00 | 0.171248E+10 | 0.00 | 1.41 |
August | 0.140024E+09 | 51496274.64 | 0.00 | 7615389.29 | 2478697.28 | 0.00 | 0.212355E+10 | 0.00 | 1.43 |
September | 0.310896E+09 | 42586226.66 | 0.00 | 4530468.81 | 1919534.40 | 0.00 | 0.167675E+10 | 0.00 | 0.93 |
October | 0.672275E+09 | 0.00 | 0.00 | 2345456.56 | 0.00 | 11467997.95 | 0.980640E+09 | 0.00 | 0.48 |
November | 0.938088E+09 | 0.00 | 0.00 | 308960.57 | 0.00 | 0.445508E+09 | 0.183631E+09 | 0.00 | 0.28 |
December | 0.621988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181489E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.629231E+10 | 0.221197E+09 | 0.00 | 36727020.66 | 10339434.10 | 0.790447E+10 | 0.113350E+11 | 0.00 | 0.69 |
Minimum of Months | 72898290.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.107789E+10 | 86944176.13 | 0.00 | 8670336.09 | 3794602.46 | 0.338352E+10 | 0.230147E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.528716E+09 | 0.00 | 0.00 | 38356.73 | 0.00 | 0.729341E+10 | 37394520.94 | 0.00 | 0.52 |
February | 0.742590E+09 | 0.00 | 0.00 | 1375258.68 | 0.00 | 0.407587E+10 | 0.637926E+09 | 0.00 | 0.54 |
March | 0.118705E+10 | 0.00 | 0.00 | 1183996.12 | 0.00 | 0.252231E+10 | 0.741103E+09 | 0.00 | 0.44 |
April | 0.969690E+09 | 0.00 | 0.00 | 1420978.71 | 0.00 | 0.122044E+10 | 0.564847E+09 | 0.00 | 0.39 |
May | 0.106270E+10 | 3741462.94 | 0.00 | 2310082.27 | 782005.21 | 0.845587E+09 | 0.752201E+09 | 0.00 | 0.54 |
June | 0.674950E+09 | 59883506.24 | 0.00 | 4864197.17 | 6105079.95 | 0.135416E+09 | 0.121091E+10 | 0.00 | 0.78 |
July | 0.304187E+09 | 0.154115E+09 | 0.00 | 6738698.92 | 2703106.60 | 12753294.15 | 0.105074E+10 | 0.00 | 0.84 |
August | 0.408192E+09 | 0.104056E+09 | 0.00 | 8644246.67 | 3065167.31 | 89466265.95 | 0.177542E+10 | 0.00 | 1.11 |
September | 0.601731E+09 | 0.122957E+09 | 0.00 | 7369179.34 | 873369.52 | 0.248883E+09 | 0.229088E+10 | 0.00 | 1.05 |
October | 0.892218E+09 | 0.00 | 0.00 | 6384996.27 | 0.00 | 0.510865E+09 | 0.234503E+10 | 0.00 | 0.75 |
November | 0.116761E+10 | 0.00 | 0.00 | 2001905.51 | 0.00 | 0.167495E+10 | 0.103512E+10 | 0.00 | 0.45 |
December | 0.948738E+09 | 0.00 | 0.00 | 228442.07 | 0.00 | 0.469448E+10 | 0.209969E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.948836E+10 | 0.444753E+09 | 0.00 | 42560338.46 | 13528728.60 | 0.233244E+11 | 0.126515E+11 | 0.00 | 0.65 |
Minimum of Months | 0.304187E+09 | 0.00 | 0.00 | 38356.73 | 0.00 | 12753294.15 | 37394520.94 | 0.00 | 0.39 |
Maximum of Months | 0.118705E+10 | 0.154115E+09 | 0.00 | 8644246.67 | 6105079.95 | 0.729341E+10 | 0.234503E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210091E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385322E+10 | 0.00 | 0.00 | 0.41 |
February | 0.587868E+09 | 0.00 | 0.00 | 196163.42 | 0.00 | 0.156458E+10 | 0.104208E+09 | 0.00 | 0.34 |
March | 0.105874E+10 | 0.00 | 0.00 | 479498.63 | 0.00 | 0.726400E+09 | 0.258612E+09 | 0.00 | 0.32 |
April | 0.918252E+09 | 0.00 | 0.00 | 1197817.61 | 0.00 | 93132296.11 | 0.476139E+09 | 0.00 | 0.35 |
May | 0.574545E+09 | 1776556.24 | 0.00 | 3591917.15 | 589838.19 | 34200312.11 | 0.125532E+10 | 0.00 | 0.65 |
June | 0.212950E+09 | 47081406.27 | 0.00 | 5597256.76 | 1836037.91 | 0.00 | 0.161894E+10 | 0.00 | 1.08 |
July | 89523912.38 | 0.108308E+09 | 0.00 | 5978377.07 | 1298227.41 | 0.00 | 0.103808E+10 | 0.00 | 1.01 |
August | 0.171314E+09 | 58202166.26 | 0.00 | 5587873.96 | 1147145.86 | 0.00 | 0.132106E+10 | 0.00 | 1.07 |
September | 0.368162E+09 | 67093065.85 | 0.00 | 3721252.92 | 766861.05 | 0.00 | 0.129725E+10 | 0.00 | 0.84 |
October | 0.729229E+09 | 0.00 | 0.00 | 2017668.45 | 0.00 | 15335810.70 | 0.865392E+09 | 0.00 | 0.48 |
November | 0.969542E+09 | 0.00 | 0.00 | 375814.77 | 0.00 | 0.430801E+09 | 0.235066E+09 | 0.00 | 0.30 |
December | 0.554955E+09 | 0.00 | 0.00 | 11650.26 | 0.00 | 0.193946E+10 | 10761258.93 | 0.00 | 0.31 |
Annual Sum or Average | 0.644517E+10 | 0.282461E+09 | 0.00 | 28755290.99 | 5638110.42 | 0.865713E+10 | 0.848084E+10 | 0.00 | 0.60 |
Minimum of Months | 89523912.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.105874E+10 | 0.108308E+09 | 0.00 | 5978377.07 | 1836037.91 | 0.385322E+10 | 0.161894E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471451E+10 | 0.00 | 0.00 | 0.34 |
February | 0.926306E+09 | 0.00 | 0.00 | 6592.63 | 0.00 | 0.234516E+10 | 8438285.89 | 0.00 | 0.31 |
March | 0.213304E+10 | 0.00 | 0.00 | 47670.94 | 0.00 | 0.915393E+09 | 59946090.95 | 0.00 | 0.31 |
April | 0.175812E+10 | 0.00 | 0.00 | 996737.39 | 0.00 | 87866569.24 | 0.619697E+09 | 0.00 | 0.38 |
May | 0.118948E+10 | 3801628.91 | 0.00 | 3179394.22 | 977193.63 | 51948908.69 | 0.141191E+10 | 0.00 | 0.55 |
June | 0.349775E+09 | 47532466.12 | 0.00 | 6859947.66 | 5706467.66 | 0.00 | 0.221725E+10 | 0.00 | 0.90 |
July | 0.178368E+09 | 98993031.81 | 0.00 | 6403176.29 | 3355065.89 | 0.00 | 0.127073E+10 | 0.00 | 0.78 |
August | 0.317515E+09 | 58874474.53 | 0.00 | 5968265.81 | 4132765.99 | 0.00 | 0.155100E+10 | 0.00 | 0.79 |
September | 0.904024E+09 | 60193003.73 | 0.00 | 3089015.97 | 3494982.22 | 607258.64 | 0.117390E+10 | 0.00 | 0.58 |
October | 0.164465E+10 | 0.00 | 0.00 | 1008944.15 | 0.00 | 84681729.38 | 0.585113E+09 | 0.00 | 0.38 |
November | 0.154738E+10 | 0.00 | 0.00 | 10172.99 | 0.00 | 0.996746E+09 | 38530267.36 | 0.00 | 0.30 |
December | 0.688961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308513E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.119307E+11 | 0.269395E+09 | 0.00 | 27569918.05 | 17666475.39 | 0.122820E+11 | 0.893652E+10 | 0.00 | 0.49 |
Minimum of Months | 0.178368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.213304E+10 | 98993031.81 | 0.00 | 6859947.66 | 5706467.66 | 0.471451E+10 | 0.221725E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303037E+10 | 0.00 | 0.00 | 0.34 |
February | 0.557673E+09 | 0.00 | 0.00 | 269846.33 | 0.00 | 0.120726E+10 | 0.134777E+09 | 0.00 | 0.29 |
March | 0.987071E+09 | 0.00 | 0.00 | 1217211.06 | 0.00 | 0.436870E+09 | 0.589893E+09 | 0.00 | 0.32 |
April | 0.732530E+09 | 0.00 | 0.00 | 3171708.63 | 0.00 | 25321723.25 | 0.159821E+10 | 0.00 | 0.60 |
May | 0.457126E+09 | 3947784.63 | 0.00 | 5049204.15 | 413229.70 | 31715914.98 | 0.231857E+10 | 0.00 | 0.92 |
June | 0.130534E+09 | 39387093.67 | 0.00 | 9619205.11 | 2863669.74 | 0.00 | 0.281185E+10 | 0.00 | 1.59 |
July | 70707209.16 | 80824020.77 | 0.00 | 10170468.87 | 1439753.86 | 0.00 | 0.193378E+10 | 0.00 | 1.55 |
August | 0.137369E+09 | 53482909.82 | 0.00 | 8170101.69 | 2552307.38 | 0.00 | 0.227593E+10 | 0.00 | 1.50 |
September | 0.356827E+09 | 47926282.30 | 0.00 | 4586884.55 | 1967095.53 | 382255.19 | 0.178080E+10 | 0.00 | 0.96 |
October | 0.721094E+09 | 0.00 | 0.00 | 2136041.85 | 0.00 | 31602878.25 | 0.104607E+10 | 0.00 | 0.51 |
November | 0.752910E+09 | 0.00 | 0.00 | 322708.29 | 0.00 | 0.503190E+09 | 0.214350E+09 | 0.00 | 0.27 |
December | 0.482027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170907E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.569391E+10 | 0.225568E+09 | 0.00 | 44713380.54 | 9236056.22 | 0.697578E+10 | 0.147042E+11 | 0.00 | 0.76 |
Minimum of Months | 70707209.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.987071E+09 | 80824020.77 | 0.00 | 10170468.87 | 2863669.74 | 0.303037E+10 | 0.281185E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101119E+10 | 0.00 | 0.00 | 1475141.65 | 0.00 | 0.318059E+10 | 0.955897E+09 | 0.00 | 0.37 |
February | 0.116823E+10 | 0.00 | 0.00 | 4314059.86 | 0.00 | 0.131535E+10 | 0.209795E+10 | 0.00 | 0.54 |
March | 0.170105E+10 | 0.00 | 0.00 | 6374988.04 | 0.00 | 0.626222E+09 | 0.286528E+10 | 0.00 | 0.58 |
April | 0.131946E+10 | 0.00 | 0.00 | 6133019.49 | 0.00 | 69842522.78 | 0.302062E+10 | 0.00 | 0.78 |
May | 0.943198E+09 | 9398705.02 | 0.00 | 7234278.02 | 666039.17 | 58436414.62 | 0.312590E+10 | 0.00 | 0.91 |
June | 0.364560E+09 | 74227481.59 | 0.00 | 9482904.40 | 2685129.73 | 0.00 | 0.283446E+10 | 0.00 | 1.17 |
July | 0.206123E+09 | 0.148143E+09 | 0.00 | 9339243.40 | 1888128.52 | 0.00 | 0.162090E+10 | 0.00 | 1.04 |
August | 0.281098E+09 | 0.119971E+09 | 0.00 | 11184587.47 | 2912812.17 | 0.00 | 0.257919E+10 | 0.00 | 1.34 |
September | 0.583192E+09 | 0.150116E+09 | 0.00 | 9944854.17 | 1022156.06 | 311605.66 | 0.358239E+10 | 0.00 | 1.32 |
October | 0.969674E+09 | 0.00 | 0.00 | 10341628.44 | 0.00 | 43187140.71 | 0.442030E+10 | 0.00 | 1.07 |
November | 0.121739E+10 | 0.00 | 0.00 | 5527205.85 | 0.00 | 0.559381E+09 | 0.272126E+10 | 0.00 | 0.57 |
December | 0.122689E+10 | 0.00 | 0.00 | 2186635.63 | 0.00 | 0.189047E+10 | 0.132520E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.109921E+11 | 0.501857E+09 | 0.00 | 83538546.43 | 9174265.65 | 0.774379E+10 | 0.311493E+11 | 0.00 | 0.84 |
Minimum of Months | 0.206123E+09 | 0.00 | 0.00 | 1475141.65 | 0.00 | 0.00 | 0.955897E+09 | 0.00 | 0.37 |
Maximum of Months | 0.170105E+10 | 0.150116E+09 | 0.00 | 11184587.47 | 2912812.17 | 0.318059E+10 | 0.442030E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.346939E+09 | 0.00 | 0.00 | 5688.32 | 0.00 | 0.349077E+10 | 9388743.29 | 0.00 | 0.40 |
February | 0.701411E+09 | 0.00 | 0.00 | 450749.80 | 0.00 | 0.134008E+10 | 0.211543E+09 | 0.00 | 0.36 |
March | 0.122655E+10 | 0.00 | 0.00 | 1259371.68 | 0.00 | 0.555396E+09 | 0.605200E+09 | 0.00 | 0.39 |
April | 0.904976E+09 | 0.00 | 0.00 | 2873310.44 | 0.00 | 57277215.68 | 0.142372E+10 | 0.00 | 0.68 |
May | 0.568684E+09 | 3551451.22 | 0.00 | 5752232.57 | 445082.17 | 35404709.81 | 0.225899E+10 | 0.00 | 1.00 |
June | 0.209109E+09 | 57362216.93 | 0.00 | 7425550.27 | 1740643.69 | 0.00 | 0.206470E+10 | 0.00 | 1.35 |
July | 96890082.94 | 0.120878E+09 | 0.00 | 7188821.20 | 713067.63 | 0.00 | 0.113187E+10 | 0.00 | 1.12 |
August | 0.186569E+09 | 69965886.69 | 0.00 | 6277318.29 | 845232.26 | 0.00 | 0.142087E+10 | 0.00 | 1.19 |
September | 0.471811E+09 | 87097773.62 | 0.00 | 3972292.63 | 445991.51 | 385136.19 | 0.142348E+10 | 0.00 | 0.94 |
October | 0.857657E+09 | 0.00 | 0.00 | 2259422.39 | 0.00 | 45850495.48 | 0.110523E+10 | 0.00 | 0.59 |
November | 0.899780E+09 | 0.00 | 0.00 | 527642.86 | 0.00 | 0.577502E+09 | 0.359650E+09 | 0.00 | 0.35 |
December | 0.580753E+09 | 0.00 | 0.00 | 31004.88 | 0.00 | 0.191167E+10 | 28046855.51 | 0.00 | 0.32 |
Annual Sum or Average | 0.705112E+10 | 0.338855E+09 | 0.00 | 38023405.34 | 4190017.27 | 0.801434E+10 | 0.120427E+11 | 0.00 | 0.72 |
Minimum of Months | 96890082.94 | 0.00 | 0.00 | 5688.32 | 0.00 | 0.00 | 9388743.29 | 0.00 | 0.32 |
Maximum of Months | 0.122655E+10 | 0.120878E+09 | 0.00 | 7425550.27 | 1740643.69 | 0.349077E+10 | 0.225899E+10 | 0.00 | 1.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:02
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.147642E+12 | 0.172609E+11 | 0.00 | 0.157670E+12 | 0.505137E+11 |
February | 0.199234E+12 | 0.134115E+11 | 0.00 | 0.150806E+12 | 0.315484E+11 |
March | 0.325164E+12 | 0.129650E+11 | 0.00 | 0.180847E+12 | 0.240677E+11 |
April | 0.344113E+12 | 0.902551E+10 | 0.00 | 0.203549E+12 | 0.190643E+11 |
May | 0.451800E+12 | 0.868324E+10 | 0.00 | 0.210163E+12 | 0.357379E+11 |
June | 0.487375E+12 | 0.416215E+10 | 0.00 | 0.189483E+12 | 0.101344E+12 |
July | 0.484400E+12 | 0.208226E+10 | 0.00 | 0.157536E+12 | 0.171922E+12 |
August | 0.406323E+12 | 0.304629E+10 | 0.00 | 0.181242E+12 | 0.144506E+12 |
September | 0.311803E+12 | 0.573110E+10 | 0.00 | 0.188177E+12 | 0.700426E+11 |
October | 0.209713E+12 | 0.879201E+10 | 0.00 | 0.219040E+12 | 0.229535E+11 |
November | 0.119064E+12 | 0.119698E+11 | 0.00 | 0.176419E+12 | 0.195999E+11 |
December | 0.966235E+11 | 0.149138E+11 | 0.00 | 0.154619E+12 | 0.375608E+11 |
Annual Sum or Average | 0.358326E+13 | 0.112044E+12 | 0.00 | 0.216955E+13 | 0.728860E+12 |
Minimum of Months | 0.966235E+11 | 0.208226E+10 | 0.00 | 0.150806E+12 | 0.190643E+11 |
Maximum of Months | 0.487375E+12 | 0.172609E+11 | 0.00 | 0.219040E+12 | 0.171922E+12 |