Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:20:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2031.89 | 407.83 | 407.83 |
Net Site Energy | 2031.89 | 407.83 | 407.83 |
Total Source Energy | 6435.00 | 1291.60 | 1291.60 |
Net Source Energy | 6435.00 | 1291.60 | 1291.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 794.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 172.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2031.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 794.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 134.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 172.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 794.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 231.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 719.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 26.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 172.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 201.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 407.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 56.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 201.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 407.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2031.891 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2031.891 | 100.00 |
Total On-Site and Utility Electric Sources | 2031.891 | 100.00 |
Total Electricity End Uses | 2031.891 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.33 |
Time Setpoint Not Met During Occupied Cooling | 584.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1252.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 89.4590 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 6.6636 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 6.6636 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 6.6636 | 18.58 | 24.1370 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.6636 | 18.58 | 89.4590 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 6.6636 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.6636 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.6636 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.6636 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.6636 | 18.58 | 8.0700 | |
Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Conditioned Total | 4982.19 | 6.6636 | 9.29 | 24.1370 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 6.6636 | 18.58 | 24.1370 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 28-APR-11:20 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113130.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 41670.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27758.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 2543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 206191.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 113130.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 19671.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | ElevatorLift | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 27758.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 2543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2515.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 733.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 85.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 547.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1291.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 147.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 457.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 17.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 109.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1291.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.57 | 0.291727 | 0.248000 | 0.637120 | 0.777938 | 0.500000 | 0.001306 |
CORE_MID VAV BOX COMPONENT | 2.12 | 0.354016 | 0.301000 | 0.637220 | 0.944042 | 0.500000 | 0.001076 |
CORE_TOP VAV BOX COMPONENT | 2.37 | 0.315578 | 0.268000 | 0.636463 | 0.841543 | 0.500000 | 0.001207 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.878729 | 0.179796 | 0.153000 | 0.134446 | 0.479455 | 0.500000 | 0.002119 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.700253 | 0.142837 | 0.121000 | 0.084731 | 0.380898 | 0.500000 | 0.002667 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.979511 | 0.161296 | 0.137000 | 0.134193 | 0.430124 | 0.500000 | 0.002362 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.795612 | 0.125709 | 0.107000 | 0.085130 | 0.335223 | 0.500000 | 0.003031 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.761169 | 0.207565 | 0.176000 | 0.133966 | 0.553506 | 0.500000 | 0.001836 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.641083 | 0.156020 | 0.133000 | 0.085264 | 0.416054 | 0.500000 | 0.002442 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.855002 | 0.184785 | 0.157000 | 0.134235 | 0.492760 | 0.500000 | 0.002062 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.679407 | 0.147210 | 0.125000 | 0.084926 | 0.392559 | 0.500000 | 0.002588 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.755738 | 0.209056 | 0.178000 | 0.134521 | 0.557483 | 0.500000 | 0.001822 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.655257 | 0.407054 | 0.500000 | 0.002496 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.854871 | 0.184813 | 0.157000 | 0.134215 | 0.492836 | 0.500000 | 0.002062 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.707347 | 0.141395 | 0.120000 | 0.084882 | 0.377053 | 0.500000 | 0.002695 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21269.02 |
CORE_MID VAV BOX REHEAT COIL | 21272.37 |
CORE_TOP VAV BOX REHEAT COIL | 21247.09 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 7057.68 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 4609.48 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 7023.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 4628.90 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4472.19 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2846.38 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4481.19 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2835.09 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 5032.70 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 3321.16 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 5007.19 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 3335.15 |
PACU_VAV_BOT HEATING COIL | 0.000000 |
PACU_VAV_MID HEATING COIL | 0.000000 |
PACU_VAV_TOP HEATING COIL | 0.000000 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.75 | 1.08 | 5.51 | 1.08 | 5.14 | 5.14 | 0.300000 | 0.209080 | 5.14 |
PACU_VAV_MID | 2.55 | 1.08 | 5.09 | 1.08 | 4.67 | 4.67 | 0.300000 | 0.230251 | 4.67 |
PACU_VAV_TOP | 2.86 | 1.07 | 5.73 | 1.19 | 5.57 | 5.57 | 0.300000 | 0.213518 | 5.57 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.14 |
PACU_VAV_MID_OA_CONTROLLER | 4.67 |
PACU_VAV_TOP_OA_CONTROLLER | 5.57 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.14 | 119386.85 | 0.722227 | 1.71 | 39791.64 | 0.722227 |
PACU_VAV_MID COOLING COIL | 4.67 | 111000.20 | 0.715229 | 1.56 | 36996.37 | 0.715229 |
PACU_VAV_TOP COOLING COIL | 5.57 | 126942.78 | 0.728924 | 1.86 | 42310.03 | 0.728924 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.14 |
PACU_VAV_MID FAN | 4.67 |
PACU_VAV_TOP FAN | 5.57 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 89.459 | 0.000 | 0.000 | 0.000 | 0.000 | 96.123 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.733 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 6.664 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.734 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 6553.914 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6553.914 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 874.681 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.681 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1381.623 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1381.623 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 874.624 | 6.664 | 123.802 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 874.624 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | CORE_BOTTOM | 983.54 | 52.9 | 76724.000 | 78.008 | 1449.300 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4561.242 |
2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | CORE_BOTTOM | 983.54 | 52.9 | 3200.000 | 3.254 | 60.447 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2563.936 | 3200.000 |
3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
4 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
5 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
6 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
7 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
8 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
9 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
10 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
11 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
12 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
13 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
14 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
15 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
16 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
17 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
18 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 6 | 0.167 | 1.328 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 6 | 0.167 | 1.313 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.592 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5188 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5277 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3941 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 6 | 0.22034119E-07 | 0.34186667E-09 | 0.51028043E-08 | -0.99966795E-13 |
43 | 5 | -0.15575685E-03 | 0.30726149E-05 | -0.80471308E-04 | 0.50596976E-08 |
44 | 4 | 0.25098773 | 0.15612093E-02 | 0.84928613E-01 | -0.27863917E-04 |
45 | 3 | -6.4488769 | 0.50236036E-01 | -2.0965073 | 0.25009644E-01 |
46 | 2 | 38.172500 | 0.18459162 | 14.265034 | -0.30329881 |
47 | 1 | -78.474946 | 0.85697261E-01 | -28.243456 | 1.0344939 |
48 | 0 | 46.824353 | 0.17727373E-02 | 16.313943 | |
49 | 6 | 0.22220471E-07 | 0.33897870E-09 | 0.51439591E-08 | -0.10094351E-12 |
50 | 5 | -0.15674173E-03 | 0.30417725E-05 | -0.80970714E-04 | 0.51000978E-08 |
51 | 4 | 0.25219758 | 0.15433791E-02 | 0.85360851E-01 | -0.28028645E-04 |
52 | 3 | -6.4729780 | 0.49601353E-01 | -2.1036496 | 0.25127351E-01 |
53 | 2 | 38.252148 | 0.18206636 | 14.294681 | -0.30418501 |
54 | 1 | -78.536155 | 0.84448529E-01 | -28.270134 | 1.0357980 |
55 | 0 | 46.824353 | 0.17453530E-02 | 16.313230 | |
56 | 6 | 0.18845480E-07 | 0.38509844E-09 | 0.43982754E-08 | -0.83379515E-13 |
57 | 5 | -0.13867918E-03 | 0.35672754E-05 | -0.71780061E-04 | 0.43666335E-08 |
58 | 4 | 0.22968634 | 0.18605187E-02 | 0.77334699E-01 | -0.24995801E-04 |
59 | 3 | -6.0237384 | 0.61253070E-01 | -1.9705638 | 0.22935651E-01 |
60 | 2 | 36.766583 | 0.22953206 | 13.740229 | -0.28766105 |
61 | 1 | -77.393480 | 0.10834582 | -27.770672 | 1.0114547 |
62 | 0 | 46.824361 | 0.22782066E-02 | 16.327018 | |
63 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
64 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
65 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
66 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
67 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
68 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
69 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
70 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
71 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
72 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
73 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
74 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
75 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
76 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
77 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
78 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
79 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
80 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
81 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
82 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
83 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
84 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
85 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
86 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
87 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
88 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
89 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
90 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
91 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
92 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
93 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
94 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
95 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
96 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
97 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
98 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
99 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
100 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
101 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
102 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
103 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 27.185 | 0.8451 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.492E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.509E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.509E-002 | 1.693E-004 | 2.563E-004 | 0.222 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.339E-002 | 1.782E-004 | 2.563E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.563E-004 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 5.199E-002 | 3.130E-005 | 2.790E-005 | 9.244E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4296E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4635E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6887E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7167E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4486E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4698E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5578E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5722E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6220E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2028E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2708E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3184E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2613E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3760E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8099E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0520E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4309E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4714E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6901E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7253E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4501E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4767E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5576E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5721E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1837E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3527E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9154E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1486E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9954E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9683E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3022E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5557E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8234E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8362E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6164E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6257E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4487E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4522E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9854E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9904E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4722E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5037E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1032E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1285E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8332E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8508E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5576E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5721E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2493E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2592E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7599E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7337E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5795E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.7005E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8099E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0520E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4717E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5031E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1025E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1267E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8319E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8460E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5578E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5722E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4071E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0064E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9932E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7376E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2056E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6181E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3022E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5557E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3143E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3387E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0058E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0296E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9549E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9686E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9855E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9905E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0102E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.0646E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.6112E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2210E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.7641E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1035E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.2063E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4956E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0542E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2773E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.8020E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0822E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9057E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9140E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2406E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.5186E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5930E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6764E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0694E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3379E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8837E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0026E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2063E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4956E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3003E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9469E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9070E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6904E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1382E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5793E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2406E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5186E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0098E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.0641E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6107E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2205E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.7635E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1031E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.2060E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4955E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0541E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2771E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.8018E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0820E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9055E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9138E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2403E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.5184E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5931E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6763E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0695E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3378E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8836E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0025E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2060E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4955E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3003E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9468E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9069E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6903E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1380E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5791E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2403E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5184E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 35648.82964 | 35648.82964 | 2.56903 | 2.56903 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 476.02725 | 476.02725 | 2.03690E-002 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 29401.72290 | 29401.72290 | 2.11701 | 2.11701 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 6700.51884 | 6700.51884 | 0.28011 | 0.42469 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 32670.92627 | 32670.92627 | 2.37486 | 2.37486 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 42.50900 | 1.07813E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 11614.96985 | 11614.96985 | 0.49023 | 0.49023 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 12088.65362 | 12088.65362 | 0.87873 | 0.87873 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 4974.06535 | 4974.06535 | 0.21141 | 0.21141 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9633.37981 | 9633.37981 | 0.70025 | 0.70025 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 3247.95954 | 3247.95954 | 0.13808 | 0.13808 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 13475.12369 | 13475.12369 | 0.97951 | 0.97951 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 4949.96008 | 4949.96008 | 0.21038 | 0.21038 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10945.25658 | 10945.25658 | 0.79561 | 0.79561 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 3261.55890 | 3261.55890 | 0.13866 | 0.13866 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 10471.43567 | 10471.43567 | 0.76117 | 0.76117 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 2498.03129 | 2498.03129 | 0.10547 | 0.10547 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8819.43443 | 8819.43443 | 0.64108 | 0.64108 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 40.08400 | 1.07771E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 1657.47604 | 1657.47604 | 7.00321E-002 | 7.00321E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11762.31760 | 11762.31760 | 0.85500 | 0.85500 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 2487.52129 | 2487.52129 | 0.10502 | 0.10502 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9346.66690 | 9346.66690 | 0.67941 | 0.67941 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 1664.41780 | 1664.41780 | 7.03298E-002 | 7.03298E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 10396.67763 | 10396.67763 | 0.75574 | 0.75574 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 3556.28887 | 3556.28887 | 0.15076 | 0.15076 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9014.38350 | 9014.38350 | 0.65526 | 0.65526 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2346.16769 | 2346.16769 | 9.94862E-002 | 9.94862E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11760.46637 | 11760.46637 | 0.85487 | 0.85487 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 3538.38330 | 3538.38330 | 0.14999 | 0.14999 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9730.99381 | 9730.99381 | 0.70735 | 0.70735 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 2355.99792 | 2355.99792 | 9.99053E-002 | 9.99053E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 91392.64 | 5.14400 | 5.14400 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 94.34 | 0.78004 | 0.78004 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 84946.17 | 4.67325 | 4.67325 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 111.85 | 0.92483 | 0.92483 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 96939.93 | 5.56754 | 5.56754 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 115.44 | 1.18877 | 1.18877 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.56903 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29173 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63712 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77794 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30602E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21269.02386 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11701 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35402 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63722 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94404 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07622E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21272.36846 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.37486 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31558 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26800 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.63646 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84154 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20731E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21247.09274 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87873 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17980 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15300 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13445 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47946 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11907E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7057.68234 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70025 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14284 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.47306E-002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38090 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66738E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4609.47924 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97951 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16130 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13419 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43012 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36211E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7023.25352 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79561 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12571 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10700 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.51305E-002 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33522 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03082E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4628.90011 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76117 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20756 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13397 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55351 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83557E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4472.18956 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64108 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15602 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13300 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.52640E-002 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41605 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44199E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2846.37564 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18479 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13424 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49276 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06185E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4481.18973 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67941 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14721 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.49258E-002 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39256 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58814E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 2835.08700 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75574 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20906 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13452 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55748 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82248E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5032.70020 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65526 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40705 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49598E-003 |
101 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3321.15735 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85487 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18481 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13421 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49284 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06154E-003 |
109 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5007.19432 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.70735 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14139 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.48816E-002 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37705 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69458E-003 |
117 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3335.14997 |
118 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75285 |
119 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07551 |
120 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.50569 |
121 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07551 |
122 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.14400 |
123 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.14400 |
124 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
125 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.20908 |
126 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.54511 |
127 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07602 |
128 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.09022 |
129 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07602 |
130 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.67325 |
131 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.67325 |
132 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
133 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.23025 |
134 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.86448 |
135 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07496 |
136 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.72897 |
137 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18877 |
138 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.56754 |
139 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.56754 |
140 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
141 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.21352 |
142 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.14400 |
143 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.67325 |
144 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.56754 |
145 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.14400 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.14400 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 119386.85147 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72223 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.71450 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 39791.63759 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72223 |
152 | Coil:Heating:Electric | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
153 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.14400 |
154 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.67325 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.67325 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111000.20488 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.71523 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55760 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36996.36829 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.71523 |
161 | Coil:Heating:Electric | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
162 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.67325 |
163 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.56754 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.56754 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 126942.77781 |
166 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72892 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.85566 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 42310.02784 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72892 |
170 | Coil:Heating:Electric | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
171 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.56754 |
172 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
173 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
174 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
175 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
176 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 118931.81 | 405812.17 | 12.38 | 3.18 | 3.55 | 3.74 | 3.89 | 10.84 | 12.10 | 12.75 | 13.28 | 5.9468 | 4.7195 | 3.1766 | 1.3401 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 110661.72 | 377593.47 | 12.43 | 3.19 | 3.56 | 3.75 | 3.90 | 10.88 | 12.15 | 12.81 | 13.32 | 5.4026 | 4.2845 | 2.8840 | 1.2240 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 126383.17 | 431237.27 | 12.34 | 3.17 | 3.53 | 3.72 | 3.88 | 10.81 | 12.06 | 12.70 | 13.25 | 6.4364 | 5.1245 | 3.4483 | 1.4408 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.592 | 1.286 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.328 | 1.108 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.313 | 1.097 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1443766261 | 0.2128693889 | Pass | Pass | 9.4570950112E-002 | 0.2922374419 | Pass | Fail |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6138666972E-002 | 5.3651966756E-002 | Pass | Pass | 1.3333484933E-002 | 8.3266690945E-002 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6409909655E-002 | 2.2475745039E-002 | Pass | Pass | 0.2550102232 | 1.3315712287 | Fail | Fail |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.1678486708E-002 | 3.4093108791E-002 | Pass | Pass | 0.5022275617 | 1.7631176482 | Fail | Fail |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.7043358629E-002 | 0.1317609540 | Pass | Pass | 3.5661714130E-002 | 0.1855674306 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.9157723553E-002 | 9.5733963315E-002 | Pass | Pass | 1.4471583747E-002 | 0.1194696747 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.5085193040E-002 | 8.5268565413E-002 | Pass | Pass | 1.4243837462E-002 | 0.1185173731 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9052799662E-002 | 8.5917976972E-002 | Pass | Pass | 1.4296139553E-002 | 0.1187326921 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.7924160921E-002 | 0.1173421900 | Pass | Pass | 2.1651355561E-002 | 0.1592676563 | Pass | Fail |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.4061064093E-002 | 9.7866527239E-002 | Pass | Pass | 1.4046209425E-002 | 0.1176531173 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1121988835 | 0.1540925040 | Pass | Fail | 9.2049223145E-002 | 0.2885170384 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1187910434 | 0.1580183653 | Pass | Fail | 9.2219950563E-002 | 0.2887791014 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1370750692 | 0.1950508390 | Pass | Fail | 0.1102943748 | 0.3501691575 | Pass | Fail |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1198074504 | 0.1683194265 | Pass | Fail | 9.1697932584E-002 | 0.2875119158 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 7.2997490619E-002 | 0.1144782609 | Pass | Pass | 3.5381627976E-002 | 0.1847381335 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.7735934632E-002 | 0.1163379440 | Pass | Pass | 3.5466156160E-002 | 0.1849471815 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1021637405 | 0.1567693432 | Pass | Pass | 6.8330805253E-002 | 0.3353832151 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.8838706097E-002 | 0.1259880661 | Pass | Pass | 3.4924716308E-002 | 0.1829422510 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2121.15 | -83.5 | 0.00 | -1086.3 | 3879.61 | 4830.93 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.286 | 1.592 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.108 | 1.328 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.097 | 1.313 | 91.28 | 47.77 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 652.62 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 195.79 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 456.84 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.6636 | 983.54 | 6553.91 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 45.19 | 0.0000 | Y | 55.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 4.20 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.20 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.58 | 0.0000 | Y | 6.63 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.54 | 0.0000 | Y | 4.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.35 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.51 | 0.0000 | Y | 4.19 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.63 | 0.0000 | Y | 6.65 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.6636 | 131.26 | 874.68 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.57 | 0.0000 | Y | 4.20 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.6636 | 207.34 | 1381.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.38 | 0.0000 | Y | 6.58 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.6636 | 131.25 | 874.62 | LightsWired | LTG_SCH_OFFICE | 47.17 | 168.00 | 25.55 | 0.0000 | Y | 4.20 |
Interior Lighting Total | 6.6636 | 4982.19 | 33199.39 | 231.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.68 | 335.44 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.68 | 122.02 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1381.62 | 529.85 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1381.62 | 192.74 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 874.62 | 335.42 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 874.62 | 122.01 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 563.81 | AstronomicalClock | - | 41.85 | 41.85 | 4.43 | |
EXTERIOR_LIGHTS_B | 407.66 | AstronomicalClock | - | 83.85 | 62.85 | 4.81 | |
EXTERIOR_LIGHTS_C | 4714.72 | AstronomicalClock | - | 83.85 | 46.68 | 41.32 | |
Exterior Lighting Total | 5686.19 | 50.55 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 119386.85 | 86224.36 | 33162.49 | 0.72 | 3.70 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111000.20 | 79390.51 | 31609.69 | 0.72 | 3.70 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 126942.78 | 92531.61 | 34411.17 | 0.73 | 3.70 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 118931.8 | 3.18 | 10.84 | N/A | N/A | 12.38 | |
PACU_VAV_MID COOLING COIL | 110661.7 | 3.19 | 10.88 | N/A | N/A | 12.43 | |
PACU_VAV_TOP COOLING COIL | 126383.2 | 3.17 | 10.81 | N/A | N/A | 12.34 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21269.02 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 21272.37 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 21247.09 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7057.68 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4609.48 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7023.25 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4628.90 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4472.19 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2846.38 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4481.19 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2835.09 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5032.70 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3321.16 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5007.19 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3335.15 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.14 | 11187.63 | 2174.89 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.67 | 10229.80 | 2189.01 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.57 | 12108.78 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 1.00 | 27.19 | 0.85 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 118931.81 | 3.18 | 10.84 | 12.38 | 5.9468 | 3.55 | 12.10 | 4.7195 | 3.74 | 12.75 | 3.1766 | 3.89 | 13.28 | 1.3401 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 110661.72 | 3.19 | 10.88 | 12.43 | 5.4026 | 3.56 | 12.15 | 4.2845 | 3.75 | 12.81 | 2.8840 | 3.90 | 13.32 | 1.2240 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 126383.17 | 3.17 | 10.81 | 12.34 | 6.4364 | 3.53 | 12.06 | 5.1245 | 3.72 | 12.70 | 3.4483 | 3.88 | 13.25 | 1.4408 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 35648.83 | 35648.83 | 36.25 | 2.569 | 2.569 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00884 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_MID | 29401.72 | 29401.72 | 29.89 | 2.117 | 2.117 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 35.62 | 0.01077 | 0.425 | 0.00 |
CORE_TOP | 32670.93 | 32670.93 | 33.22 | 2.375 | 2.375 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 42.51 | 0.01078 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12088.65 | 12088.65 | 58.30 | 0.879 | 0.879 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00875 | 42.70 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9633.38 | 9633.38 | 73.39 | 0.700 | 0.700 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00870 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13475.12 | 13475.12 | 64.99 | 0.980 | 0.980 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00872 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10945.26 | 10945.26 | 83.39 | 0.796 | 0.796 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00867 | 41.96 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10471.44 | 10471.44 | 50.50 | 0.761 | 0.761 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00876 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8819.43 | 8819.43 | 67.19 | 0.641 | 0.641 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 24.00 | 24.00 | 0.00870 | 40.08 | 0.01078 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11762.32 | 11762.32 | 56.73 | 0.855 | 0.855 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00873 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9346.67 | 9346.67 | 71.21 | 0.679 | 0.679 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00869 | 41.83 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10396.68 | 10396.68 | 50.14 | 0.756 | 0.756 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00878 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9014.38 | 9014.38 | 68.67 | 0.655 | 0.655 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00870 | 39.60 | 0.01078 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11760.47 | 11760.47 | 56.72 | 0.855 | 0.855 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00875 | 42.80 | 0.01078 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9730.99 | 9730.99 | 74.14 | 0.707 | 0.707 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00869 | 41.96 | 0.01078 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 476.03 | 476.03 | 0.48 | 0.020 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00867 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_MID | 6700.52 | 6700.52 | 6.81 | 0.280 | 0.425 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
CORE_TOP | 11614.97 | 11614.97 | 11.81 | 0.490 | 0.490 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 4974.07 | 4974.07 | 23.99 | 0.211 | 0.211 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 3247.96 | 3247.96 | 24.74 | 0.138 | 0.138 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 4949.96 | 4949.96 | 23.87 | 0.210 | 0.210 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 3261.56 | 3261.56 | 24.85 | 0.139 | 0.139 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00813 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 2498.03 | 2498.03 | 12.05 | 0.105 | 0.105 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 1657.48 | 1657.48 | 12.63 | 0.070 | 0.070 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 2487.52 | 2487.52 | 12.00 | 0.105 | 0.105 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00815 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 1664.42 | 1664.42 | 12.68 | 0.070 | 0.070 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00816 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 3556.29 | 3556.29 | 17.15 | 0.151 | 0.151 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2346.17 | 2346.17 | 17.87 | 0.099 | 0.099 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 3538.38 | 3538.38 | 17.07 | 0.150 | 0.150 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 2356.00 | 2356.00 | 17.95 | 0.100 | 0.100 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.14 | 5.14 | 0.78 | 0.78 | 5.1440 | 1.0755 | 5.1440 | 0.2091 | 0.3000 |
PACU_VAV_MID | 4.67 | 4.67 | 0.92 | 0.92 | 4.6733 | 1.0760 | 4.6733 | 0.2303 | 0.3000 |
PACU_VAV_TOP | 5.57 | 5.57 | 1.19 | 1.19 | 5.5675 | 1.1888 | 5.5675 | 0.2135 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21269.024 | 21269.024 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21269.02 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00867276 | 55.9800 | 476.03 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 21272.368 | 21272.368 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21272.37 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 6700.52 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 21247.093 | 21247.093 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21247.09 | 16365.53 | 0.490234 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11614.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 7057.682 | 7057.682 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7057.68 | 7057.68 | 0.211415 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813236 | 52.5360 | 4974.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 4609.479 | 4609.479 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4609.48 | 4609.48 | 0.138078 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813344 | 52.5428 | 3247.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 7023.254 | 7023.254 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7023.25 | 7023.25 | 0.210384 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813323 | 52.5415 | 4949.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 4628.900 | 4628.900 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4628.90 | 4628.90 | 0.138660 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00813265 | 52.5378 | 3261.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4472.190 | 4472.190 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4472.19 | 3520.94 | 0.105471 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815391 | 52.6738 | 2498.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2846.376 | 2846.376 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2846.38 | 2337.89 | 0.070032 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815624 | 52.6886 | 1657.48 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4481.190 | 4481.190 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4481.19 | 3505.89 | 0.105020 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815441 | 52.6770 | 2487.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2835.087 | 2835.087 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2835.09 | 2347.83 | 0.070330 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00815571 | 52.6852 | 1664.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 5032.700 | 5032.700 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5032.70 | 5032.70 | 0.150756 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816517 | 52.7453 | 3556.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 3321.157 | 3321.157 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3321.16 | 3321.16 | 0.099486 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816635 | 52.7528 | 2346.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 5007.194 | 5007.194 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5007.19 | 5007.19 | 0.149992 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816604 | 52.7509 | 3538.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 3335.150 | 3335.150 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3335.15 | 3335.15 | 0.099905 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00816558 | 52.7479 | 2356.00 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 119386.851 | 86224.357 | 5.144004 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 110527.81 | 100049.43 | 5.144004 | 27.49 | 18.14 | 0.00916611 | 11.03 | 11.03 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 18.5867 | 24.00 | 0.00879711 | 47.3142 | 70745.85 | 0.00 | 123103.87 | 87632.02 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_BOT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 0.00 | 0.00 | 1.543201 | 15.86 | 13.69 | 0.00887569 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 61.9556 | 21.00 | 0.00815502 | 52.6810 | 8678.66 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 111000.205 | 79390.511 | 4.673253 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 103252.29 | 92788.40 | 4.673253 | 27.85 | 18.31 | 0.00923312 | 11.02 | 11.02 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 20.4590 | 24.00 | 0.00883407 | 47.5103 | 64198.09 | 0.00 | 114456.11 | 80732.19 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_MID | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.401976 | 15.25 | 13.39 | 0.00881512 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 68.1966 | 21.00 | 0.00810625 | 52.3699 | 18497.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 126942.778 | 92531.610 | 5.567540 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 117258.09 | 106560.44 | 5.567540 | 27.21 | 18.01 | 0.00912740 | 11.03 | 11.03 | 0.00850000 | 42.70 | 0.01078164 | 23.83 | 17.1728 | 24.00 | 0.00878389 | 47.2442 | 76494.16 | 0.00 | 130895.04 | 94019.73 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | PACU_VAV_TOP | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 1.670262 | 16.25 | 13.65 | 0.00867188 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 57.2425 | 21.00 | 0.00802909 | 51.8782 | 20798.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21269.024 | 21269.024 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21269.02 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21269.02 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00867276 | 21.00 | 0.00867276 | 55.9800 | 476.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 21272.368 | 21272.368 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21272.37 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21272.37 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 6700.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 21247.093 | 21247.093 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21247.09 | 16365.53 | 1.0000 | 0.59004313 | 0.490234 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21247.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11614.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7057.682 | 7057.682 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7057.68 | 7057.68 | 1.0000 | 0.25445784 | 0.211415 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7057.68 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813236 | 21.00 | 0.00813236 | 52.5360 | 4974.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4609.479 | 4609.479 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4609.48 | 4609.48 | 1.0000 | 0.16619027 | 0.138078 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4609.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813344 | 21.00 | 0.00813344 | 52.5428 | 3247.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7023.254 | 7023.254 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7023.25 | 7023.25 | 1.0000 | 0.25321655 | 0.210384 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7023.25 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813323 | 21.00 | 0.00813323 | 52.5415 | 4949.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4628.900 | 4628.900 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4628.90 | 4628.90 | 1.0000 | 0.16689047 | 0.138660 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4628.90 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00813265 | 21.00 | 0.00813265 | 52.5378 | 3261.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 4472.190 | 4472.190 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4472.19 | 3520.94 | 1.0000 | 0.12694397 | 0.105471 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4472.19 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815391 | 21.00 | 0.00815391 | 52.6738 | 2498.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 2846.376 | 2846.376 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2846.38 | 2337.89 | 1.0000 | 0.08429025 | 0.070032 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2846.38 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815624 | 21.00 | 0.00815624 | 52.6886 | 1657.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 4481.190 | 4481.190 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4481.19 | 3505.89 | 1.0000 | 0.12640127 | 0.105020 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4481.19 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815441 | 21.00 | 0.00815441 | 52.6770 | 2487.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 2835.087 | 2835.087 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2835.09 | 2347.83 | 1.0000 | 0.08464855 | 0.070330 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 2835.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00815571 | 21.00 | 0.00815571 | 52.6852 | 1664.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5032.700 | 5032.700 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5032.70 | 5032.70 | 1.0000 | 0.18144909 | 0.150756 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5032.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816517 | 21.00 | 0.00816517 | 52.7453 | 3556.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3321.157 | 3321.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3321.16 | 3321.16 | 1.0000 | 0.11974108 | 0.099486 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3321.16 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816635 | 21.00 | 0.00816635 | 52.7528 | 2346.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5007.194 | 5007.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5007.19 | 5007.19 | 1.0000 | 0.18052950 | 0.149992 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5007.19 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816604 | 21.00 | 0.00816604 | 52.7509 | 3538.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 3335.150 | 3335.150 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3335.15 | 3335.15 | 1.0000 | 0.12024558 | 0.099905 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3335.15 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.86 | 0.00816558 | 21.00 | 0.00816558 | 52.7479 | 2356.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 119386.851 | 86224.357 | 5.144004 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8793 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.144004 | 6.19129685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 110527.81 | 100049.43 | 0.9258 | 6.19129685 | 5.144004 | 27.49 | 18.14 | 0.00916611 | 51019.8 | 11.03 | 11.03 | 0.00850000 | 32517.4 | -999.0 | -999.00 | -999.00 | -999.00 | 11187.633 | 99340.18 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 18.5867 | 24.00 | 0.00879711 | 24.00 | 0.00879711 | 47.3142 | 70745.85 | 0.00 | 123103.87 | 87632.02 | 5.94678743 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.24 | 12.21 | 0.00884597 | 34621.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.144004 | 6.19129685 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.85738905 | 1.543201 | 15.86 | 13.69 | 0.00887569 | 38394.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 61.9556 | 21.00 | 0.00842336 | 21.00 | 0.00815502 | 52.6810 | 8678.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111000.205 | 79390.511 | 4.673253 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0039 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.673253 | 5.62470371 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 103252.29 | 92788.40 | 0.9302 | 5.62470371 | 4.673253 | 27.85 | 18.31 | 0.00923312 | 51555.1 | 11.02 | 11.02 | 0.00850000 | 32505.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10229.802 | 93022.48 | 42.80 | 0.01078182 | 23.86 | 0.95610000 | 20.4590 | 24.00 | 0.00883407 | 24.00 | 0.00883407 | 47.5103 | 64198.09 | 0.00 | 114456.11 | 80732.19 | 5.40257043 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.03 | 12.02 | 0.00873723 | 34136.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.673253 | 5.62470371 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 1.68741111 | 1.401976 | 15.25 | 13.39 | 0.00881512 | 37624.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 68.1966 | 20.73 | 0.00808964 | 21.00 | 0.00810625 | 52.3699 | 18497.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 126942.778 | 92531.610 | 5.567540 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8074 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.567540 | 6.70106291 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 117258.09 | 106560.44 | 0.9237 | 6.70106291 | 5.567540 | 27.21 | 18.01 | 0.00912740 | 50635.5 | 11.03 | 11.03 | 0.00850000 | 32517.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12108.777 | 105149.31 | 42.70 | 0.01078164 | 23.83 | 0.95610000 | 17.1728 | 24.00 | 0.00878389 | 24.00 | 0.00878389 | 47.2442 | 76494.16 | 0.00 | 130895.04 | 94019.73 | 6.43642158 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.37 | 12.36 | 0.00893838 | 34985.8 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.567540 | 6.70106291 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 2.01031887 | 1.670262 | 16.25 | 13.65 | 0.00867188 | 38277.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 0.95610000 | 57.2425 | 21.00 | 0.00802718 | 21.00 | 0.00802909 | 51.8782 | 20798.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | PERIMETER_MID_ZN_2_OA_MULT | 1.00 | 1.00 | |
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5602.50 | 0.00 | 0.00 |
CORE_MID | 4979.83 | 80.33 | 0.67 |
CORE_TOP | 4593.67 | 451.33 | 10.33 |
PERIMETER_TOP_ZN_3 | 4545.67 | 1108.83 | 343.33 |
PERIMETER_TOP_ZN_2 | 4846.00 | 981.33 | 446.33 |
PERIMETER_TOP_ZN_1 | 4939.33 | 946.33 | 446.83 |
PERIMETER_TOP_ZN_4 | 4742.00 | 1105.17 | 451.67 |
PERIMETER_BOT_ZN_3 | 4997.50 | 474.17 | 220.00 |
PERIMETER_BOT_ZN_2 | 5315.50 | 488.50 | 366.83 |
PERIMETER_BOT_ZN_1 | 5376.17 | 1176.33 | 985.00 |
PERIMETER_BOT_ZN_4 | 5261.33 | 532.00 | 375.17 |
PERIMETER_MID_ZN_3 | 4785.67 | 771.00 | 299.00 |
PERIMETER_MID_ZN_2 | 4229.00 | 713.50 | 411.67 |
PERIMETER_MID_ZN_1 | 5165.17 | 656.33 | 397.50 |
PERIMETER_MID_ZN_4 | 4983.67 | 783.83 | 414.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5736.17 | 2060.67 | 1252.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 97.50 | 0.00 | 62.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 130.33 | 0.00 | 89.17 |
PERIMETER_TOP_ZN_1 | 0.00 | 127.83 | 0.00 | 89.50 |
PERIMETER_TOP_ZN_4 | 0.00 | 136.17 | 0.00 | 77.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 64.50 | 0.00 | 45.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 117.83 | 0.00 | 81.67 |
PERIMETER_BOT_ZN_1 | 2.33 | 460.17 | 2.33 | 429.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 126.83 | 0.00 | 68.83 |
PERIMETER_MID_ZN_3 | 0.00 | 69.17 | 0.00 | 50.33 |
PERIMETER_MID_ZN_2 | 0.00 | 108.17 | 0.00 | 84.17 |
PERIMETER_MID_ZN_1 | 0.00 | 103.50 | 0.00 | 82.50 |
PERIMETER_MID_ZN_4 | 0.00 | 110.33 | 0.00 | 67.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.33 | 702.00 | 2.33 | 584.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.497 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.434 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.431 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.610 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.757 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.753 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.741 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.515 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.645 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.732 | 1.236 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.636 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.606 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.716 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.747 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.741 | 0.028 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.49 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.53 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.49 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.53 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.48 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8624889.72 | 0.00 | 8624889.72 | 0.00 | 8624889.72 | 13393058.27 | 6722.64 | 575.58 | 1461.78 | 613.42 |
CORE_MID | 7441813.70 | 0.00 | 7441813.70 | 0.00 | 7441813.70 | 13393058.27 | 7611.91 | 695.39 | 452.70 | 485.56 |
CORE_TOP | 7488361.36 | 0.00 | 7488361.36 | 0.00 | 7488361.36 | 13393058.27 | 7570.92 | 893.17 | 295.90 | 549.14 |
PERIMETER_TOP_ZN_3 | 2183891.23 | 0.00 | 2183891.23 | 186056.00 | 2369947.23 | 2823374.22 | 4236.71 | 956.64 | 3566.65 | 549.14 |
PERIMETER_TOP_ZN_2 | 1690453.87 | 0.00 | 1690453.87 | 124036.59 | 1814490.46 | 1787429.43 | 3666.89 | 805.91 | 4287.20 | 549.14 |
PERIMETER_TOP_ZN_1 | 2658188.82 | 0.00 | 2658188.82 | 186056.00 | 2844244.82 | 2823374.22 | 3613.31 | 813.12 | 4333.57 | 549.14 |
PERIMETER_TOP_ZN_4 | 1673724.90 | 0.00 | 1673724.90 | 124036.59 | 1797761.48 | 1787312.18 | 3741.93 | 852.79 | 4165.28 | 549.14 |
PERIMETER_BOT_ZN_3 | 1879795.96 | 0.00 | 1879795.96 | 98926.03 | 1978721.99 | 2823374.22 | 5966.30 | 489.62 | 2304.08 | 613.42 |
PERIMETER_BOT_ZN_2 | 1469777.11 | 0.00 | 1469777.11 | 65950.29 | 1535727.40 | 1787429.43 | 4006.65 | 723.48 | 4029.87 | 613.42 |
PERIMETER_BOT_ZN_1 | 2598427.82 | 0.00 | 2598427.82 | 4077227.68 | 6675655.50 | 2823374.22 | 4111.92 | 488.44 | 4159.64 | 613.42 |
PERIMETER_BOT_ZN_4 | 1463347.26 | 0.00 | 1463347.26 | 65950.29 | 1529297.55 | 1787312.18 | 4451.24 | 502.40 | 3806.36 | 613.42 |
PERIMETER_MID_ZN_3 | 2142564.64 | 0.00 | 2142564.64 | 154878.15 | 2297442.79 | 2823374.22 | 4561.60 | 796.96 | 3401.44 | 485.56 |
PERIMETER_MID_ZN_2 | 1589864.91 | 0.00 | 1589864.91 | 103251.48 | 1693116.38 | 1601953.02 | 3683.75 | 709.93 | 4366.32 | 1394.56 |
PERIMETER_MID_ZN_1 | 2607551.26 | 0.00 | 2607551.26 | 154878.15 | 2762429.40 | 2823374.22 | 3802.12 | 634.45 | 4323.43 | 485.56 |
PERIMETER_MID_ZN_4 | 1651977.27 | 0.00 | 1651977.27 | 103251.48 | 1755228.75 | 1787312.18 | 4069.22 | 666.11 | 4024.67 | 485.56 |
Total Facility | 47164629.84 | 0.00 | 47164629.84 | 5444498.70 | 52609128.54 | 67658168.57 | 8604.01 | 2021.00 | 5309.15 | 1720.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3607 | 0.0000 | 0.3607 | 0.0000 | 0.3607 | 0.4247 | 4152.40 | 345.02 | 1445.59 |
CORE_MID | 0.3146 | 0.0000 | 0.3146 | 0.0000 | 0.3146 | 0.4247 | 4948.66 | 543.58 | 450.76 |
CORE_TOP | 0.3129 | 0.0000 | 0.3129 | 0.0000 | 0.3129 | 0.4247 | 4933.88 | 714.32 | 294.80 |
PERIMETER_TOP_ZN_3 | 0.0931 | 0.0000 | 0.0931 | 0.0049 | 0.0980 | 0.0895 | 1787.94 | 704.95 | 3450.10 |
PERIMETER_TOP_ZN_2 | 0.0731 | 0.0000 | 0.0731 | 0.0033 | 0.0764 | 0.0567 | 1106.03 | 690.93 | 4146.04 |
PERIMETER_TOP_ZN_1 | 0.1151 | 0.0000 | 0.1151 | 0.0049 | 0.1201 | 0.0895 | 1106.87 | 628.72 | 4207.41 |
PERIMETER_TOP_ZN_4 | 0.0716 | 0.0000 | 0.0716 | 0.0033 | 0.0749 | 0.0567 | 1349.98 | 612.22 | 3980.80 |
PERIMETER_BOT_ZN_3 | 0.0786 | 0.0000 | 0.0786 | 0.0026 | 0.0812 | 0.0895 | 3365.09 | 337.57 | 2240.34 |
PERIMETER_BOT_ZN_2 | 0.0624 | 0.0000 | 0.0624 | 0.0018 | 0.0641 | 0.0567 | 1657.02 | 383.28 | 3902.70 |
PERIMETER_BOT_ZN_1 | 0.1116 | 0.0000 | 0.1116 | 0.1886 | 0.3002 | 0.0895 | 1610.72 | 289.26 | 4043.02 |
PERIMETER_BOT_ZN_4 | 0.0615 | 0.0000 | 0.0615 | 0.0018 | 0.0632 | 0.0567 | 1984.52 | 334.52 | 3623.96 |
PERIMETER_MID_ZN_3 | 0.0925 | 0.0000 | 0.0925 | 0.0041 | 0.0966 | 0.0895 | 2012.77 | 601.01 | 3329.22 |
PERIMETER_MID_ZN_2 | 0.0692 | 0.0000 | 0.0692 | 0.0029 | 0.0721 | 0.0567 | 1161.40 | 512.02 | 3360.57 |
PERIMETER_MID_ZN_1 | 0.1141 | 0.0000 | 0.1141 | 0.0041 | 0.1182 | 0.0895 | 1191.81 | 509.75 | 4241.44 |
PERIMETER_MID_ZN_4 | 0.0716 | 0.0000 | 0.0716 | 0.0027 | 0.0744 | 0.0567 | 1508.16 | 557.08 | 3877.75 |
Total Facility | 2.0025 | 0.0000 | 2.0025 | 0.2250 | 2.2275 | 2.1513 | 5819.44 | 1505.45 | 4969.26 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23230691.33 | 0.00 | 23230691.33 | 22614548.33 | 3088.18 | 2.55 | 5669.27 | 613.42 |
PACU_VAV_MID | 22357956.76 | 0.00 | 22357956.76 | 22429071.92 | 3234.54 | 1.46 | 5524.00 | 485.56 |
PACU_VAV_TOP | 22735810.62 | 0.00 | 22735810.62 | 22614548.33 | 3173.25 | 1.04 | 5585.71 | 549.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9774 | 0.0000 | 0.9774 | 0.7171 | 865.67 | 1.65 | 5075.68 |
PACU_VAV_MID | 0.9592 | 0.0000 | 0.9592 | 0.7084 | 892.79 | 1.18 | 5049.02 |
PACU_VAV_TOP | 0.9645 | 0.0000 | 0.9645 | 0.7171 | 891.26 | 0.71 | 5051.03 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 471.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5255.07 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 200.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5367.38 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 192.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5441.39 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 1.2234 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1282 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 1.0851 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1232 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 1.0380 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1304 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 943 |
Defaulted Fields | 546 |
Fields with Defaults | 2232 |
Autosized Fields | 150 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
Electricity:Building | 951.32 | 13387.10 | 29-MAY-17:20 | 65700.59 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 306.02 | 5243.28 | 01-JAN-00:10 | 18955.76 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 951.32 | 13387.10 | 29-MAY-17:20 | 65700.59 | 15-MAR-07:10 |
InteriorLights:Electricity | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 231.63 | 909.35 | 29-MAY-17:20 | 24001.33 | 15-MAR-07:10 |
Electricity:Zone:CORE_MID | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 171.02 | 2043.28 | 01-JAN-00:10 | 11744.33 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 55.60 | 211.73 | 01-JAN-00:10 | 4936.01 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.98 | 413.68 | 02-APR-17:10 | 2376.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.63 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.63 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.60 | 262.93 | 29-MAY-17:10 | 1496.42 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.85 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.85 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2374.87 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.63 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.63 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1508.01 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.44 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.44 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.97 | 413.68 | 02-APR-17:10 | 2373.08 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.63 | 27.57 | 01-JAN-09:40 | 937.83 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.63 | 27.57 | 01-JAN-09:40 | 937.83 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.60 | 261.88 | 29-MAY-17:10 | 1494.08 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 585.51 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.19 | 17.46 | 01-JAN-08:00 | 585.51 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2370.98 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-08:00 | 935.74 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 27.57 | 01-JAN-08:00 | 935.74 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.59 | 261.87 | 12-MAR-17:10 | 1506.19 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:40 | 597.62 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.19 | 17.46 | 01-JAN-09:40 | 597.62 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.98 | 413.68 | 02-APR-17:10 | 2376.86 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.62 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.65 | 27.57 | 01-JAN-09:50 | 941.62 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.60 | 262.93 | 29-MAY-17:10 | 1496.41 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.84 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.20 | 17.46 | 01-JAN-08:00 | 587.84 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.91 | 413.67 | 12-MAR-17:10 | 2374.86 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.62 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.58 | 27.57 | 01-JAN-08:00 | 939.62 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.60 | 261.87 | 12-MAR-17:10 | 1508.00 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.43 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.20 | 17.46 | 01-JAN-09:40 | 599.43 | 14-MAR-07:10 |
InteriorEquipment:Electricity | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 250.42 | 5031.54 | 01-JAN-00:10 | 14019.75 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 719.69 | 12477.75 | 01-JAN-00:10 | 41699.26 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.36 | 3200.00 | 01-JAN-00:10 | 7125.18 | 02-JAN-07:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
Electricity:HVAC | 994.42 | 367.92 | 01-JAN-00:10 | 142299.09 | 10-AUG-16:00 |
ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 01-MAR-13:10 |
Transformer:ExteriorEquipment:Electricity | 26.89 | 367.92 | 01-JAN-00:10 | 1410.29 | 01-MAR-13:10 |
ElectricityPurchased:Facility | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
ElectricityNet:Plant | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 2031.89 | 13755.76 | 25-JUN-17:20 | 206191.73 | 10-AUG-16:00 |
Heating:Electricity | 0.37 | 0.00 | 01-JAN-00:10 | 4481.19 | 02-JAN-07:50 |
General:Heating:Electricity | 0.37 | 0.00 | 01-JAN-00:10 | 4481.19 | 02-JAN-07:50 |
Fans:Electricity | 172.91 | 0.00 | 01-JAN-00:10 | 27758.08 | 10-AUG-16:00 |
General:Fans:Electricity | 172.91 | 0.00 | 01-JAN-00:10 | 27758.08 | 10-AUG-16:00 |
ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.55 | 0.00 | 01-JAN-07:10 | 5686.19 | 01-JAN-06:10 |
Cooling:Electricity | 794.25 | 0.00 | 01-JAN-00:10 | 113657.46 | 10-AUG-15:30 |
General:Cooling:Electricity | 794.25 | 0.00 | 01-JAN-00:10 | 113657.46 | 10-AUG-15:30 |
Electricity:Plant | 35.59 | 0.00 | 01-JAN-00:10 | 4623.72 | 12-JAN-13:00 |
WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.87 | 12-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 35.45 | 0.00 | 01-JAN-00:10 | 4616.87 | 12-JAN-13:00 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 27-MAR-12:10 |
WIRED_LTG_ELECTRICITY | 6.51 | 0.00 | 01-JAN-00:10 | 674.44 | 15-MAR-07:20 |
WIRED_INT_EQUIP1 | 680.83 | 12477.75 | 01-JAN-00:10 | 37555.83 | 02-JAN-13:10 |
WIRED_INT_EQUIP2 | 624.19 | 9277.75 | 01-JAN-00:10 | 39135.32 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 28-APR-11:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4998.82 | 0.00 | 01-JAN-00:10 | 538642.19 | 10-AUG-15:40 |
EnergyTransfer:Building | 1880.36 | 0.00 | 01-JAN-00:10 | 195144.22 | 05-SEP-14:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 326.65 | 0.00 | 01-JAN-00:10 | 28304.45 | 05-SEP-07:20 |
Heating:EnergyTransfer | 2.31 | 0.00 | 01-JAN-00:10 | 4759.38 | 02-JAN-07:50 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 2.31 | 0.00 | 01-JAN-00:10 | 4759.38 | 02-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1878.05 | 0.00 | 01-JAN-00:10 | 195144.22 | 05-SEP-14:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 326.65 | 0.00 | 01-JAN-00:10 | 28304.45 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer | 1878.05 | 0.00 | 01-JAN-00:10 | 195144.22 | 05-SEP-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 326.65 | 0.00 | 01-JAN-00:10 | 28304.45 | 05-SEP-07:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 86.33 | 0.00 | 01-JAN-00:10 | 14162.87 | 16-AUG-13:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.34 | 0.00 | 01-JAN-00:10 | 2249.97 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.34 | 0.00 | 01-JAN-00:10 | 2249.97 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.99 | 0.00 | 01-JAN-00:10 | 14162.87 | 16-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.99 | 0.00 | 01-JAN-00:10 | 14162.87 | 16-AUG-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.32 | 0.00 | 01-JAN-00:10 | 7354.44 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1446.76 | 01-JAN-13:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1446.76 | 01-JAN-13:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.08 | 0.00 | 01-JAN-00:10 | 7354.44 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 52.08 | 0.00 | 01-JAN-00:10 | 7354.44 | 05-SEP-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 60.31 | 0.00 | 01-JAN-00:10 | 7650.59 | 05-SEP-07:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.48 | 0.00 | 01-JAN-00:10 | 1497.28 | 16-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.48 | 0.00 | 01-JAN-00:10 | 1497.28 | 16-JAN-10:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.83 | 0.00 | 01-JAN-00:10 | 7650.59 | 05-SEP-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 59.83 | 0.00 | 01-JAN-00:10 | 7650.59 | 05-SEP-07:10 |
EnergyTransfer:Zone:CORE_MID | 232.51 | 0.00 | 01-JAN-00:10 | 21761.99 | 05-SEP-07:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 232.51 | 0.00 | 01-JAN-00:10 | 21761.99 | 05-SEP-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 232.51 | 0.00 | 01-JAN-00:10 | 21761.99 | 05-SEP-07:20 |
EnergyTransfer:Zone:CORE_TOP | 239.20 | 0.00 | 01-JAN-00:10 | 22600.57 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 239.20 | 0.00 | 01-JAN-00:10 | 22600.57 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 239.20 | 0.00 | 01-JAN-00:10 | 22600.57 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.13 | 0.00 | 01-JAN-00:10 | 9228.72 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.13 | 0.00 | 01-JAN-00:10 | 9228.72 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.13 | 0.00 | 01-JAN-00:10 | 9228.72 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 60.45 | 0.00 | 01-JAN-00:10 | 7928.22 | 31-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 60.45 | 0.00 | 01-JAN-00:10 | 7928.22 | 31-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 60.45 | 0.00 | 01-JAN-00:10 | 7928.22 | 31-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.27 | 0.00 | 01-JAN-00:10 | 11159.91 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.27 | 0.00 | 01-JAN-00:10 | 11159.91 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 93.27 | 0.00 | 01-JAN-00:10 | 11159.91 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.69 | 0.00 | 01-JAN-00:10 | 8065.96 | 09-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.69 | 0.00 | 01-JAN-00:10 | 8065.96 | 09-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.69 | 0.00 | 01-JAN-00:10 | 8065.96 | 09-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 8984.27 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 8984.27 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 78.15 | 0.00 | 01-JAN-00:10 | 8984.27 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.00 | 0.00 | 01-JAN-00:10 | 7604.64 | 31-JUL-10:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.00 | 0.00 | 01-JAN-00:10 | 7604.64 | 31-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.00 | 0.00 | 01-JAN-00:10 | 7604.64 | 31-JUL-10:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.40 | 0.00 | 01-JAN-00:10 | 18105.60 | 16-AUG-12:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 3480.76 | 04-JAN-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.24 | 0.00 | 01-JAN-00:10 | 3480.76 | 04-JAN-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.15 | 0.00 | 01-JAN-00:10 | 18105.60 | 16-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 116.15 | 0.00 | 01-JAN-00:10 | 18105.60 | 16-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 61.07 | 0.00 | 01-JAN-00:10 | 7579.35 | 05-SEP-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 61.07 | 0.00 | 01-JAN-00:10 | 7579.35 | 05-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 61.07 | 0.00 | 01-JAN-00:10 | 7579.35 | 05-SEP-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.38 | 0.00 | 01-JAN-00:10 | 8328.69 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.38 | 0.00 | 01-JAN-00:10 | 8328.69 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 73.38 | 0.00 | 01-JAN-00:10 | 8328.69 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.49 | 0.00 | 01-JAN-00:10 | 7720.13 | 31-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.49 | 0.00 | 01-JAN-00:10 | 7720.13 | 31-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 55.49 | 0.00 | 01-JAN-00:10 | 7720.13 | 31-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.17 | 0.00 | 01-JAN-00:10 | 10398.49 | 02-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.17 | 0.00 | 01-JAN-00:10 | 10398.49 | 02-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 89.17 | 0.00 | 01-JAN-00:10 | 10398.49 | 02-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 56.85 | 0.00 | 01-JAN-00:10 | 7510.43 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 56.85 | 0.00 | 01-JAN-00:10 | 7510.43 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 56.85 | 0.00 | 01-JAN-00:10 | 7510.43 | 31-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 3085.74 | 0.00 | 01-JAN-00:10 | 359881.06 | 03-AUG-14:10 |
HeatingCoils:EnergyTransfer | 0.37 | 0.00 | 01-JAN-00:10 | 4481.19 | 02-JAN-07:50 |
CoolingCoils:EnergyTransfer | 3085.36 | 0.00 | 01-JAN-00:10 | 359881.06 | 03-AUG-14:10 |
EnergyTransfer:Plant | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 32.72 | 0.00 | 01-JAN-00:10 | 4496.47 | 12-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -326.651 | 0.000 | 0.000 | 32.637 | 55.599 | 250.423 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -12.008 |
CORE_MID | 0.000 | 0.000 | 0.000 | -232.508 | 0.000 | 0.000 | 32.698 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 28.786 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -239.200 | 0.000 | 0.000 | 32.746 | 55.599 | 115.425 | 0.000 | 0.000 | 0.000 | 35.430 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -77.127 | 0.000 | 0.000 | 6.923 | 6.648 | 24.333 | 36.511 | 0.000 | 0.983 | 10.091 | 0.000 | -8.079 | 0.000 | -0.281 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -60.450 | 0.000 | 0.000 | 4.368 | 4.199 | 15.404 | 36.842 | 0.000 | 0.646 | 4.321 | 0.000 | -5.134 | 0.000 | -0.196 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -93.274 | 0.000 | 0.000 | 6.902 | 6.582 | 24.332 | 57.692 | 0.000 | 0.970 | 5.178 | 0.000 | -8.069 | 0.000 | -0.314 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -59.690 | 0.000 | 0.000 | 4.378 | 4.195 | 15.403 | 37.419 | 0.000 | 0.644 | 3.390 | 0.000 | -5.541 | 0.000 | -0.199 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -78.148 | 0.000 | 0.000 | 6.891 | 6.634 | 24.333 | 36.306 | 0.000 | 0.531 | 12.568 | 0.000 | -8.944 | 0.000 | -0.171 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -62.003 | 0.000 | 0.000 | 4.357 | 4.193 | 15.404 | 36.704 | 0.000 | 0.347 | 6.860 | 0.000 | -5.741 | 0.000 | -0.120 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.243 | -116.154 | 0.000 | 0.000 | 6.828 | 6.573 | 24.332 | 57.323 | 0.000 | 26.129 | 8.156 | 0.000 | -9.073 | 0.000 | -4.359 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -61.072 | 0.000 | 0.000 | 4.358 | 4.188 | 15.403 | 37.337 | 0.000 | 0.345 | 5.792 | 0.000 | -6.229 | 0.000 | -0.122 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -73.378 | 0.000 | 0.000 | 6.901 | 6.648 | 24.333 | 36.649 | 0.000 | 0.825 | 6.873 | 0.000 | -8.595 | 0.000 | -0.255 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -55.486 | 0.000 | 0.000 | 3.208 | 4.199 | 15.404 | 36.804 | 0.000 | 0.538 | 0.943 | 0.000 | -5.433 | 0.000 | -0.178 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -89.173 | 0.000 | 0.000 | 6.888 | 6.582 | 24.332 | 57.880 | 0.000 | 0.814 | 1.482 | 0.000 | -8.523 | 0.000 | -0.281 | -0.000 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -56.846 | 0.000 | 0.000 | 4.365 | 4.195 | 15.403 | 37.549 | 0.000 | 0.538 | 0.851 | 0.000 | -5.876 | 0.000 | -0.179 | -0.000 |
TOPFLOOR_PLENUM | 1.343 | -84.989 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.334 | 82.739 | 0.000 | 0.000 | 0.000 | -0.427 | -0.001 |
MIDFLOOR_PLENUM | 0.243 | -52.080 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.294 | 50.995 | 0.000 | 0.000 | 0.000 | -0.451 | 0.000 |
FIRSTFLOOR_PLENUM | 0.479 | -59.833 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.997 | 58.733 | 0.000 | 0.000 | 0.000 | -0.376 | 0.000 |
Total Facility | 2.065 | -196.902 | 0.243 | -1681.159 | 0.000 | 0.000 | 164.446 | 231.631 | 719.689 | 505.015 | 0.000 | 36.935 | 323.189 | 0.000 | -85.238 | 0.000 | -7.909 | -12.012 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 25-APR-04:52 | 0.00 | 0.00 | 0.00 | -41511.28 | 0.00 | 0.00 | 0.00 | 211.73 | 5642.06 | 0.00 | 0.00 | 0.00 | 35657.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 15-MAY-05:14 | 0.00 | 0.00 | 0.00 | -34668.70 | 0.00 | 0.00 | 316.30 | 548.43 | 3025.92 | 0.00 | 0.00 | 0.00 | 30778.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 25-SEP-04:02 | 0.00 | 0.00 | 0.00 | -36652.98 | 0.00 | 0.00 | 0.00 | 211.73 | 2442.06 | 0.00 | 0.00 | 0.00 | 33999.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-JUL-10:01 | 0.00 | 0.00 | 0.00 | -15319.81 | 0.00 | 0.00 | 26.39 | 27.57 | 478.42 | 4014.12 | 0.00 | 219.88 | 10553.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-JUL-10:01 | 0.00 | 0.00 | 0.00 | -13501.05 | 0.00 | 0.00 | 13.08 | 17.46 | 302.86 | 6377.33 | 0.00 | 132.17 | 6658.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 12-NOV-13:22 | 0.00 | 0.00 | 0.00 | -17648.48 | 0.00 | 0.00 | 24.21 | 27.57 | 478.41 | 7255.09 | 0.00 | 42.02 | 9821.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-15:52 | 0.00 | 0.00 | 0.00 | -13913.15 | 0.00 | 0.00 | 12.97 | 17.46 | 302.86 | 5345.44 | 0.00 | 160.83 | 8073.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-SEP-11:22 | 0.00 | 0.00 | 0.00 | -13325.80 | 0.00 | 0.00 | 26.52 | 27.57 | 478.42 | 3736.29 | 0.00 | 89.87 | 8967.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-10:01 | 0.00 | 0.00 | 0.00 | -11974.23 | 0.00 | 0.00 | 14.41 | 17.46 | 302.86 | 6463.09 | 0.00 | 73.17 | 5103.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | -18105.21 | 0.00 | 0.00 | 219.28 | 496.34 | 1275.77 | 5934.68 | 0.00 | 18414.37 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8235.23 |
PERIMETER_BOT_ZN_4 | 23-JUL-15:52 | 0.00 | 0.00 | 0.00 | -12438.95 | 0.00 | 0.00 | 14.68 | 17.46 | 302.86 | 5273.09 | 0.00 | 59.13 | 6771.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-15:11 | 0.00 | 0.00 | 0.00 | -13671.52 | 0.00 | 0.00 | 25.30 | 27.57 | 478.42 | 3610.51 | 0.00 | 212.02 | 9317.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-10:32 | 0.00 | 0.00 | 0.00 | -11984.76 | 0.00 | 0.00 | 14.57 | 17.46 | 302.86 | 4402.64 | 0.00 | 97.53 | 7149.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-15:11 | 0.00 | 0.00 | 0.00 | -15949.63 | 0.00 | 0.00 | 23.46 | 27.57 | 478.41 | 4613.62 | 0.00 | 204.51 | 10602.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-15:51 | 0.00 | 0.00 | 0.00 | -13623.81 | 0.00 | 0.00 | 13.22 | 17.46 | 302.86 | 5612.41 | 0.00 | 128.94 | 7548.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:02 | 0.00 | -14203.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 | 14092.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-12:04 | 0.00 | -7745.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 7666.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:10 | 0.00 | -8972.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.32 | 8897.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-MAY-04:02 | 0.00 | 8148.27 | 0.00 | -226107.40 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 496.20 | 0.00 | 208.93 | 200611.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-JAN-07:15 | 0.00 | 0.00 | 3499.66 | 0.00 | 0.00 | 0.00 | 192.42 | 324.03 | 637.88 | 0.00 | 0.00 | 0.00 | 8020.12 | 0.00 | -1371.97 | 0.00 | -11302.14 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 08-MAY-04:02 | 5346.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5348.80 |
MIDFLOOR_PLENUM | 25-AUG-04:02 | 3187.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3230.08 |
FIRSTFLOOR_PLENUM | 28-SEP-04:02 | 4621.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4646.86 |
Total Facility | 15-SEP-04:02 | -192426.82 | 202849.52 | 0.00 | -202849.52 | 0.00 | 0.00 | 0.00 | 1072.56 | 15570.33 | 78.94 | 0.00 | 314.50 | 175580.56 | 0.00 | -190.07 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.5057 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.1440 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0902 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6733 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7290 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.5675 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7528 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5451 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0760 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8645 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.0750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5690 | 2.5690 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1170 | 2.1170 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3749 | 2.3749 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8787 | 0.8787 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7003 | 0.7003 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9795 | 0.9795 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7956 | 0.7956 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7612 | 0.7612 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6411 | 0.6411 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8550 | 0.8550 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6794 | 0.6794 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7557 | 0.7557 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6553 | 0.6553 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8549 | 0.8549 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7073 | 0.7073 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.5057 | 5.1440 | 5.5057 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0902 | 4.6733 | 5.0902 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7290 | 5.5675 | 5.7290 | 1.0750 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2845 | 1.2845 | 0.6371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0585 | 1.0585 | 0.6372 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1874 | 1.1874 | 0.6365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4394 | 0.4394 | 0.1344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3501 | 0.3501 | 0.0847 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4898 | 0.4898 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3978 | 0.3978 | 0.0851 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3806 | 0.3806 | 0.1340 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3205 | 0.3205 | 0.0853 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4275 | 0.4275 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3397 | 0.3397 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3779 | 0.3779 | 0.1345 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3276 | 0.3276 | 0.0852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4274 | 0.4274 | 0.1342 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3537 | 0.3537 | 0.0849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7528 | 1.0755 | 1.0755 | 1.0755 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5451 | 1.0760 | 1.0760 | 1.0760 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8645 | 1.0750 | 1.0750 | 1.0750 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 2.33 |
Number of hours cooling loads not met | 584.17 |
Number of hours not met | 586.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.37 | 4481.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 794.25 | 113657.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 231.63 | 24001.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.55 | 5686.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 134.36 | 7125.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 26.89 | 1410.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 172.91 | 27758.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 35.45 | 4616.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 719.69 | 2031.89 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 719.69 | 2031.89 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.49 |
Space Heating | 0.08 |
Space Cooling | 159.42 |
Fans (All) | 34.71 |
Service Water Heating | 7.11 |
Receptacle Equipment | 144.45 |
Miscellaneous (All) | 407.83 |
Subtotal | 407.83 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.40 |
Space Heating | 0.02 |
Space Cooling | 39.09 |
Fans (All) | 8.51 |
Service Water Heating | 1.74 |
Receptacle Equipment | 35.42 |
Miscellaneous | 3.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 145. | 3744. |
ELEVATOR_STANDBY_SCH | 8276. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2460. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1026. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 7902.17 | 857.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7908.83 | 851.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7727.67 | 1032.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7780.33 | 979.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7664.50 | 1095.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8132.83 | 627.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7784.00 | 976.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7692.33 | 1067.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7663.67 | 1096.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7941.17 | 818.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7705.33 | 1054.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7774.00 | 986.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7618.00 | 1142.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7917.17 | 842.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8297.50 | 462.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8349.50 | 410.50 | 0.00 | 0.00 | 0.00 |
Min | 7618.00 | 29.50 | 0.00 | 0.00 | 0.00 |
Max | 8730.50 | 1142.00 | 0.00 | 0.00 | 0.00 |
Average | 7961.59 | 798.41 | 0.00 | 0.00 | 0.00 |
Sum | 143308.67 | 14371.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128042.67 | 261.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128298.33 | 5.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128287.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24449.67 | 459.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128298.33 | 459.33 | 0.00 | 0.00 | 0.00 |
Average | 34102.04 | 41.30 | 0.00 | 0.00 | 0.00 |
Sum | 613836.67 | 743.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 6666.00 | 2094.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7212.83 | 1547.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7340.33 | 1419.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6595.50 | 2164.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6503.67 | 2256.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6495.33 | 2264.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6496.83 | 2263.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6532.83 | 2227.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6338.17 | 2421.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5624.83 | 3135.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6311.33 | 2448.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6450.83 | 2309.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6327.83 | 2432.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6316.17 | 2443.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6310.17 | 2449.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4577.83 | 4182.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5550.83 | 3209.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 6131.67 | 2628.33 | 0.00 | 0.00 | 0.00 |
Min | 4577.83 | 1419.67 | 0.00 | 0.00 | 0.00 |
Max | 7340.33 | 4182.17 | 0.00 | 0.00 | 0.00 |
Average | 6321.28 | 2438.72 | 0.00 | 0.00 | 0.00 |
Sum | 113783.00 | 43897.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127138.17 | 1165.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 127529.50 | 774.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 127512.83 | 791.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24824.67 | 84.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24826.00 | 83.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24834.00 | 75.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 21495.50 | 3413.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24815.67 | 93.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24815.50 | 93.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 127529.50 | 3413.50 | 0.00 | 0.00 | 0.00 |
Average | 33778.10 | 365.23 | 0.00 | 0.00 | 0.00 |
Sum | 608005.83 | 6574.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229384E+11 | 40032.44 | 30-JAN-06:12 | 20.07 | 17.42 | 0.199729E+10 | 2606.69 | 24-JAN-10:00 | 20.07 | 17.42 |
February | 0.211718E+11 | 39913.57 | 27-FEB-06:12 | 17.53 | 15.85 | 0.181231E+10 | 2606.75 | 15-FEB-14:09 | 17.53 | 15.85 |
March | 0.256859E+11 | 40668.90 | 28-MAR-04:02 | 26.08 | 14.62 | 0.216323E+10 | 2606.81 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.251384E+11 | 41520.08 | 25-APR-04:52 | 24.00 | 12.96 | 0.192083E+10 | 2606.88 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.295982E+11 | 41467.85 | 04-MAY-05:03 | 24.00 | 18.14 | 0.207993E+10 | 2606.77 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.297700E+11 | 40175.77 | 07-JUN-04:02 | 24.83 | 21.13 | 0.207272E+10 | 2606.70 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.308623E+11 | 37843.56 | 29-JUL-04:03 | 29.42 | 25.46 | 0.192615E+10 | 2606.84 | 03-JUL-09:09 | 29.42 | 25.46 |
August | 0.328255E+11 | 35450.93 | 15-AUG-04:02 | 29.75 | 23.27 | 0.216065E+10 | 2606.62 | 25-AUG-13:20 | 36.47 | 27.84 |
September | 0.296126E+11 | 39560.42 | 30-SEP-04:03 | 24.52 | 21.72 | 0.192026E+10 | 2606.65 | 26-SEP-09:20 | 24.52 | 21.72 |
October | 0.292166E+11 | 39941.19 | 28-OCT-04:03 | 24.00 | 21.39 | 0.199745E+10 | 2606.64 | 20-OCT-09:20 | 24.00 | 21.39 |
November | 0.263970E+11 | 40169.63 | 25-NOV-05:03 | 25.00 | 18.54 | 0.197847E+10 | 2606.66 | 22-NOV-10:20 | 25.00 | 18.54 |
December | 0.234318E+11 | 39412.99 | 27-DEC-06:12 | 20.97 | 15.81 | 0.192770E+10 | 2606.70 | 08-DEC-10:39 | 20.97 | 15.81 |
Annual Sum or Average | 0.326648E+12 | 0.239570E+11 | ||||||||
Minimum of Months | 0.211718E+11 | 35450.93 | 17.53 | 12.96 | 0.181231E+10 | 2606.62 | 17.53 | 15.81 | ||
Maximum of Months | 0.328255E+11 | 41520.08 | 29.75 | 25.46 | 0.216323E+10 | 2606.88 | 36.47 | 27.84 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207215E+10 | 5290.98 | 31-JAN-14:05 | 23.00 | 16.33 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 16.33 |
February | 0.278409E+10 | 8067.65 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.460398E+10 | 10946.48 | 27-MAR-13:50 | 35.17 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 35.17 | 19.46 |
April | 0.617225E+10 | 11986.16 | 28-APR-12:30 | 39.35 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 39.35 | 21.60 |
May | 0.976951E+10 | 12416.52 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.106318E+11 | 13118.63 | 12-JUN-13:05 | 40.25 | 27.32 | 0.00 | 0.00 | 01-JUN-00:10 | 40.25 | 27.32 |
July | 0.118462E+11 | 14204.17 | 21-JUL-12:02 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.124207E+11 | 14162.87 | 16-AUG-13:40 | 44.07 | 25.61 | 0.00 | 0.00 | 01-AUG-00:10 | 44.07 | 25.61 |
September | 0.959870E+10 | 13141.98 | 05-SEP-14:20 | 39.67 | 25.10 | 0.00 | 0.00 | 01-SEP-00:10 | 39.67 | 25.10 |
October | 0.758232E+10 | 11079.57 | 02-OCT-14:05 | 35.82 | 20.34 | 0.00 | 0.00 | 01-OCT-00:10 | 35.82 | 20.34 |
November | 0.488211E+10 | 9176.69 | 06-NOV-14:20 | 32.67 | 20.87 | 0.00 | 0.00 | 01-NOV-00:10 | 32.67 | 20.87 |
December | 0.262476E+10 | 6837.03 | 04-DEC-13:50 | 27.17 | 20.95 | 0.00 | 0.00 | 01-DEC-00:10 | 27.17 | 20.95 |
Annual Sum or Average | 0.849886E+11 | 0.00 | ||||||||
Minimum of Months | 0.207215E+10 | 5290.98 | 23.00 | 16.33 | 0.00 | 0.00 | 23.00 | 16.33 | ||
Maximum of Months | 0.124207E+11 | 14204.17 | 45.38 | 27.32 | 0.00 | 0.00 | 45.38 | 27.32 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128101E+10 | 2316.15 | 31-JAN-15:30 | 22.80 | 16.62 | 0.00 | 0.00 | 01-JAN-00:10 | 22.80 | 16.62 |
February | 0.168480E+10 | 4193.16 | 06-FEB-15:20 | 32.13 | 17.39 | 0.00 | 0.00 | 01-FEB-00:10 | 32.13 | 17.39 |
March | 0.279296E+10 | 5448.80 | 27-MAR-15:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.364366E+10 | 5703.84 | 24-APR-12:03 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.584996E+10 | 7711.68 | 30-MAY-06:15 | 27.17 | 24.99 | 0.00 | 0.00 | 01-MAY-00:10 | 27.17 | 24.99 |
June | 0.630099E+10 | 7367.92 | 19-JUN-06:15 | 28.20 | 25.08 | 0.00 | 0.00 | 01-JUN-00:10 | 28.20 | 25.08 |
July | 0.682358E+10 | 7615.87 | 31-JUL-12:04 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.728461E+10 | 7653.01 | 21-AUG-06:15 | 30.00 | 28.39 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 28.39 |
September | 0.597885E+10 | 7745.99 | 05-SEP-12:04 | 40.98 | 24.12 | 0.00 | 0.00 | 01-SEP-00:10 | 40.98 | 24.12 |
October | 0.511534E+10 | 7484.39 | 10-OCT-06:15 | 25.93 | 23.95 | 0.00 | 0.00 | 01-OCT-00:10 | 25.93 | 23.95 |
November | 0.349754E+10 | 5410.74 | 13-NOV-15:20 | 32.07 | 19.51 | 0.00 | 0.00 | 01-NOV-00:10 | 32.07 | 19.51 |
December | 0.182686E+10 | 3559.95 | 04-DEC-15:20 | 26.73 | 21.25 | 0.00 | 0.00 | 01-DEC-00:10 | 26.73 | 21.25 |
Annual Sum or Average | 0.520802E+11 | 0.00 | ||||||||
Minimum of Months | 0.128101E+10 | 2316.15 | 22.80 | 16.62 | 0.00 | 0.00 | 22.80 | 16.62 | ||
Maximum of Months | 0.728461E+10 | 7745.99 | 40.98 | 28.39 | 0.00 | 0.00 | 40.98 | 28.39 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235451E+10 | 3773.54 | 02-JAN-07:07 | 13.00 | 10.98 | 0.00 | 0.00 | 01-JAN-00:10 | 13.00 | 10.98 |
February | 0.255895E+10 | 5002.17 | 06-FEB-13:10 | 30.25 | 18.19 | 0.00 | 0.00 | 01-FEB-00:10 | 30.25 | 18.19 |
March | 0.361192E+10 | 7570.15 | 27-MAR-12:09 | 37.08 | 19.46 | 0.00 | 0.00 | 01-MAR-00:10 | 37.08 | 19.46 |
April | 0.421652E+10 | 7038.11 | 24-APR-12:07 | 37.07 | 17.93 | 0.00 | 0.00 | 01-APR-00:10 | 37.07 | 17.93 |
May | 0.621849E+10 | 8691.37 | 08-MAY-12:06 | 36.92 | 22.10 | 0.00 | 0.00 | 01-MAY-00:10 | 36.92 | 22.10 |
June | 0.663047E+10 | 8343.64 | 26-JUN-12:07 | 38.97 | 25.98 | 0.00 | 0.00 | 01-JUN-00:10 | 38.97 | 25.98 |
July | 0.694259E+10 | 8973.25 | 31-JUL-12:10 | 40.98 | 25.84 | 0.00 | 0.00 | 01-JUL-00:10 | 40.98 | 25.84 |
August | 0.747905E+10 | 8614.97 | 14-AUG-12:09 | 37.95 | 26.72 | 0.00 | 0.00 | 01-AUG-00:10 | 37.95 | 26.72 |
September | 0.642939E+10 | 8536.31 | 05-SEP-17:08 | 37.67 | 25.56 | 0.00 | 0.00 | 01-SEP-00:10 | 37.67 | 25.56 |
October | 0.587683E+10 | 8368.63 | 10-OCT-06:15 | 25.93 | 23.95 | 0.00 | 0.00 | 01-OCT-00:10 | 25.93 | 23.95 |
November | 0.457154E+10 | 6196.17 | 13-NOV-07:10 | 20.75 | 17.82 | 0.00 | 0.00 | 01-NOV-00:10 | 20.75 | 17.82 |
December | 0.294244E+10 | 4821.61 | 04-DEC-13:10 | 27.83 | 21.18 | 0.00 | 0.00 | 01-DEC-00:10 | 27.83 | 21.18 |
Annual Sum or Average | 0.598327E+11 | 0.00 | ||||||||
Minimum of Months | 0.235451E+10 | 3773.54 | 13.00 | 10.98 | 0.00 | 0.00 | 13.00 | 10.98 | ||
Maximum of Months | 0.747905E+10 | 8973.25 | 40.98 | 26.72 | 0.00 | 0.00 | 40.98 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138094E+11 | 27348.83 | 30-JAN-06:12 | 20.07 | 17.42 | 0.198543E+10 | 2606.69 | 17-JAN-10:09 | 20.07 | 17.42 |
February | 0.134308E+11 | 31668.58 | 06-FEB-06:12 | 21.77 | 18.83 | 0.180413E+10 | 2606.73 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.172270E+11 | 32355.85 | 28-MAR-04:02 | 26.08 | 14.62 | 0.215705E+10 | 2606.79 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.178662E+11 | 33076.22 | 25-APR-04:52 | 24.00 | 12.96 | 0.191630E+10 | 2606.82 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.223362E+11 | 34672.28 | 15-MAY-05:14 | 23.00 | 17.48 | 0.207702E+10 | 2606.76 | 08-MAY-13:39 | 23.00 | 17.48 |
June | 0.227357E+11 | 32118.79 | 07-JUN-04:02 | 24.83 | 21.13 | 0.207007E+10 | 2606.75 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.240520E+11 | 29598.18 | 03-JUL-06:03 | 28.20 | 16.17 | 0.192343E+10 | 2606.83 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.253135E+11 | 29087.53 | 15-AUG-06:03 | 29.85 | 21.21 | 0.215866E+10 | 2606.63 | 07-AUG-13:20 | 29.85 | 21.21 |
September | 0.219884E+11 | 31837.41 | 29-SEP-04:02 | 26.00 | 24.56 | 0.191792E+10 | 2606.66 | 26-SEP-09:20 | 26.00 | 24.56 |
October | 0.210845E+11 | 32785.01 | 31-OCT-04:02 | 24.33 | 22.73 | 0.199436E+10 | 2606.64 | 20-OCT-09:20 | 24.33 | 22.73 |
November | 0.179127E+11 | 32525.59 | 13-NOV-06:12 | 20.83 | 17.71 | 0.197338E+10 | 2606.70 | 28-NOV-10:09 | 25.67 | 19.42 |
December | 0.147495E+11 | 31516.76 | 11-DEC-06:12 | 21.80 | 19.16 | 0.191876E+10 | 2606.67 | 08-DEC-10:20 | 21.80 | 19.16 |
Annual Sum or Average | 0.232506E+12 | 0.238965E+11 | ||||||||
Minimum of Months | 0.134308E+11 | 27348.83 | 20.07 | 12.96 | 0.180413E+10 | 2606.63 | 20.07 | 17.42 | ||
Maximum of Months | 0.253135E+11 | 34672.28 | 29.85 | 24.56 | 0.215866E+10 | 2606.83 | 35.57 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122769E+11 | 14733.60 | 30-JAN-14:50 | 22.17 | 20.62 | 0.196534E+10 | 2606.67 | 24-JAN-10:00 | 22.17 | 20.62 |
February | 0.125130E+11 | 23583.61 | 06-FEB-06:12 | 21.77 | 18.83 | 0.179242E+10 | 2606.74 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.167624E+11 | 35584.44 | 27-MAR-05:12 | 21.93 | 13.41 | 0.215074E+10 | 2606.80 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.182884E+11 | 35547.13 | 17-APR-04:03 | 24.33 | 19.27 | 0.191496E+10 | 2606.83 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.240420E+11 | 36348.08 | 09-MAY-04:02 | 26.08 | 19.67 | 0.207800E+10 | 2606.80 | 08-MAY-13:39 | 26.08 | 19.67 |
June | 0.248312E+11 | 36445.51 | 07-JUN-04:02 | 24.83 | 21.13 | 0.207114E+10 | 2606.80 | 02-JUN-13:09 | 24.83 | 21.13 |
July | 0.267837E+11 | 34665.61 | 03-JUL-04:02 | 29.00 | 16.97 | 0.192556E+10 | 2606.86 | 03-JUL-09:39 | 35.47 | 24.64 |
August | 0.279458E+11 | 33424.89 | 07-AUG-05:02 | 32.82 | 23.16 | 0.216001E+10 | 2606.61 | 03-AUG-13:20 | 32.82 | 23.16 |
September | 0.235176E+11 | 36658.18 | 25-SEP-04:02 | 24.17 | 23.10 | 0.191894E+10 | 2606.66 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.214994E+11 | 36467.09 | 23-OCT-04:02 | 25.42 | 23.19 | 0.199463E+10 | 2606.70 | 30-OCT-09:09 | 28.42 | 20.17 |
November | 0.172654E+11 | 36268.65 | 20-NOV-05:02 | 26.00 | 18.81 | 0.197108E+10 | 2606.70 | 28-NOV-10:50 | 25.93 | 20.29 |
December | 0.134718E+11 | 17492.56 | 11-DEC-07:03 | 21.50 | 18.56 | 0.190567E+10 | 2606.67 | 01-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.239198E+12 | 0.238485E+11 | ||||||||
Minimum of Months | 0.122769E+11 | 14733.60 | 21.50 | 13.41 | 0.179242E+10 | 2606.61 | 21.50 | 18.27 | ||
Maximum of Months | 0.279458E+11 | 36658.18 | 32.82 | 23.19 | 0.216001E+10 | 2606.86 | 35.57 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250624E+10 | 4133.25 | 23-JAN-14:10 | 27.50 | 16.66 | 0.403710E+09 | 549.50 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.288290E+10 | 5825.74 | 06-FEB-15:00 | 32.50 | 17.28 | 0.372165E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.443795E+10 | 8488.16 | 02-MAR-06:03 | 28.80 | 15.43 | 0.450321E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.559651E+10 | 13188.31 | 30-APR-12:43 | 37.08 | 20.98 | 0.403338E+09 | 549.54 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.858965E+10 | 14894.05 | 21-MAY-12:52 | 38.00 | 22.80 | 0.438989E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.938582E+10 | 14273.40 | 11-JUN-16:12 | 36.60 | 26.54 | 0.437686E+09 | 549.54 | 02-JUN-13:09 | 36.60 | 26.54 |
July | 0.104650E+11 | 15318.48 | 30-JUL-10:01 | 42.83 | 21.77 | 0.407370E+09 | 549.55 | 03-JUL-09:39 | 42.83 | 21.77 |
August | 0.106580E+11 | 14743.78 | 06-AUG-15:02 | 40.85 | 24.99 | 0.456604E+09 | 549.52 | 04-AUG-13:09 | 40.85 | 24.99 |
September | 0.827792E+10 | 14900.97 | 04-SEP-12:52 | 40.60 | 25.48 | 0.405524E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.672756E+10 | 13885.88 | 08-OCT-11:32 | 33.67 | 27.19 | 0.421126E+09 | 549.51 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.463315E+10 | 7941.33 | 12-NOV-14:42 | 29.17 | 18.00 | 0.414784E+09 | 549.51 | 17-NOV-10:20 | 27.40 | 19.69 |
December | 0.296648E+10 | 4612.12 | 11-DEC-14:10 | 26.77 | 18.23 | 0.396203E+09 | 549.50 | 01-DEC-14:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.771271E+11 | 0.500782E+10 | ||||||||
Minimum of Months | 0.250624E+10 | 4133.25 | 26.77 | 15.43 | 0.372165E+09 | 549.50 | 25.67 | 16.66 | ||
Maximum of Months | 0.106580E+11 | 15318.48 | 42.83 | 27.19 | 0.456604E+09 | 549.55 | 42.83 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202824E+10 | 3087.74 | 24-JAN-11:00 | 24.00 | 17.69 | 0.260828E+09 | 347.88 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.233594E+10 | 5613.26 | 05-FEB-14:43 | 31.93 | 19.38 | 0.238468E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.356530E+10 | 8667.80 | 26-MAR-12:23 | 34.50 | 17.70 | 0.286413E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.461353E+10 | 11804.64 | 30-APR-12:43 | 37.08 | 20.98 | 0.255848E+09 | 347.91 | 25-APR-09:09 | 37.08 | 20.98 |
May | 0.679550E+10 | 12143.48 | 21-MAY-10:12 | 38.00 | 20.42 | 0.278080E+09 | 348.03 | 22-MAY-09:00 | 36.70 | 22.71 |
June | 0.712024E+10 | 12099.39 | 11-JUN-10:12 | 38.33 | 26.65 | 0.277177E+09 | 347.90 | 02-JUN-13:09 | 38.33 | 26.65 |
July | 0.785762E+10 | 13499.92 | 30-JUL-10:01 | 42.83 | 21.77 | 0.258013E+09 | 348.01 | 21-JUL-09:30 | 42.83 | 21.77 |
August | 0.817885E+10 | 12536.97 | 20-AUG-09:22 | 35.90 | 25.76 | 0.289167E+09 | 348.06 | 30-AUG-09:50 | 39.75 | 24.22 |
September | 0.651457E+10 | 12119.13 | 04-SEP-10:12 | 38.00 | 23.07 | 0.256884E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.539957E+10 | 12024.85 | 08-OCT-10:13 | 32.33 | 26.51 | 0.266866E+09 | 347.89 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.371809E+10 | 7952.26 | 12-NOV-14:02 | 29.83 | 18.49 | 0.263335E+09 | 347.89 | 28-NOV-10:39 | 25.87 | 20.07 |
December | 0.232233E+10 | 3539.43 | 04-DEC-11:00 | 26.00 | 20.51 | 0.253658E+09 | 347.88 | 01-DEC-10:20 | 26.00 | 20.51 |
Annual Sum or Average | 0.604498E+11 | 0.318474E+10 | ||||||||
Minimum of Months | 0.202824E+10 | 3087.74 | 24.00 | 17.69 | 0.238468E+09 | 347.88 | 24.00 | 17.69 | ||
Maximum of Months | 0.817885E+10 | 13499.92 | 42.83 | 26.65 | 0.289167E+09 | 348.06 | 42.83 | 26.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458058E+10 | 10331.67 | 22-JAN-14:13 | 26.00 | 16.21 | 0.412178E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.477520E+10 | 17193.04 | 05-FEB-13:23 | 31.35 | 19.49 | 0.376061E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.609076E+10 | 16843.54 | 26-MAR-12:23 | 34.50 | 17.70 | 0.451657E+09 | 549.68 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.640082E+10 | 16795.87 | 30-APR-12:43 | 37.08 | 20.98 | 0.403587E+09 | 549.55 | 28-APR-13:09 | 37.08 | 20.98 |
May | 0.862967E+10 | 16564.00 | 21-MAY-12:52 | 38.00 | 22.80 | 0.438958E+09 | 549.54 | 08-MAY-13:39 | 38.00 | 22.80 |
June | 0.901911E+10 | 13967.45 | 11-JUN-14:52 | 37.00 | 27.77 | 0.437623E+09 | 549.54 | 02-JUN-13:09 | 37.00 | 27.77 |
July | 0.103534E+11 | 17128.68 | 30-JUL-14:02 | 43.50 | 24.98 | 0.407336E+09 | 549.55 | 03-JUL-09:39 | 43.50 | 24.98 |
August | 0.112513E+11 | 16556.82 | 20-AUG-13:22 | 38.60 | 26.70 | 0.456640E+09 | 549.60 | 16-AUG-13:50 | 38.60 | 26.70 |
September | 0.991173E+10 | 17102.20 | 04-SEP-12:52 | 40.60 | 25.48 | 0.405713E+09 | 549.73 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.943434E+10 | 17271.19 | 09-OCT-13:12 | 37.40 | 20.06 | 0.421643E+09 | 549.78 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.753374E+10 | 17649.36 | 12-NOV-13:22 | 29.65 | 18.98 | 0.416214E+09 | 549.82 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.529298E+10 | 17218.26 | 03-DEC-12:43 | 29.50 | 17.81 | 0.401412E+09 | 549.51 | 26-DEC-14:20 | 25.67 | 19.16 |
Annual Sum or Average | 0.932736E+11 | 0.502902E+10 | ||||||||
Minimum of Months | 0.458058E+10 | 10331.67 | 26.00 | 16.21 | 0.376061E+09 | 549.51 | 24.00 | 16.45 | ||
Maximum of Months | 0.112513E+11 | 17649.36 | 43.50 | 27.77 | 0.456640E+09 | 549.82 | 43.50 | 27.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202605E+10 | 3754.69 | 31-JAN-16:20 | 22.73 | 16.79 | 0.256442E+09 | 347.86 | 17-JAN-14:20 | 22.73 | 16.79 |
February | 0.238276E+10 | 8331.46 | 05-FEB-14:43 | 31.93 | 19.38 | 0.236157E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.366390E+10 | 8420.98 | 26-MAR-15:43 | 31.93 | 18.55 | 0.285532E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.445184E+10 | 11702.54 | 23-APR-14:13 | 32.00 | 18.41 | 0.255568E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.655723E+10 | 13718.89 | 21-MAY-16:12 | 37.33 | 23.24 | 0.278018E+09 | 347.88 | 08-MAY-13:39 | 37.33 | 23.24 |
June | 0.702530E+10 | 13617.82 | 11-JUN-16:12 | 36.60 | 26.54 | 0.277168E+09 | 347.88 | 02-JUN-13:09 | 36.60 | 26.54 |
July | 0.774668E+10 | 13918.11 | 02-JUL-15:52 | 38.40 | 23.03 | 0.257977E+09 | 347.88 | 03-JUL-09:39 | 35.47 | 24.64 |
August | 0.803876E+10 | 13755.11 | 06-AUG-15:42 | 40.25 | 25.55 | 0.289158E+09 | 347.85 | 14-AUG-09:20 | 35.13 | 23.91 |
September | 0.641504E+10 | 13399.58 | 03-SEP-16:32 | 36.93 | 26.59 | 0.256864E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.528518E+10 | 13526.32 | 09-OCT-15:12 | 36.93 | 20.06 | 0.266782E+09 | 347.86 | 30-OCT-09:20 | 28.83 | 20.32 |
November | 0.371581E+10 | 12615.74 | 12-NOV-14:42 | 29.17 | 18.00 | 0.262885E+09 | 347.86 | 17-NOV-10:20 | 27.40 | 19.69 |
December | 0.238176E+10 | 5083.02 | 03-DEC-14:43 | 27.00 | 20.88 | 0.251488E+09 | 347.86 | 26-DEC-14:20 | 25.67 | 19.16 |
Annual Sum or Average | 0.596903E+11 | 0.317404E+10 | ||||||||
Minimum of Months | 0.202605E+10 | 3754.69 | 22.73 | 16.79 | 0.236157E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.803876E+10 | 13918.11 | 40.25 | 26.59 | 0.289158E+09 | 347.88 | 37.33 | 26.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303062E+10 | 4213.17 | 23-JAN-14:10 | 27.50 | 16.66 | 0.416311E+09 | 549.51 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.306048E+10 | 5311.44 | 06-FEB-14:50 | 32.42 | 17.27 | 0.378573E+09 | 549.51 | 15-FEB-14:39 | 24.67 | 17.94 |
March | 0.419234E+10 | 6125.65 | 27-MAR-13:40 | 35.33 | 19.53 | 0.453223E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.499142E+10 | 6405.98 | 28-APR-12:30 | 39.35 | 21.60 | 0.403764E+09 | 549.55 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.775392E+10 | 12479.12 | 21-MAY-16:01 | 37.42 | 23.26 | 0.438764E+09 | 549.53 | 04-MAY-13:00 | 37.42 | 23.26 |
June | 0.869496E+10 | 10748.11 | 16-JUN-04:02 | 28.83 | 20.58 | 0.437539E+09 | 549.51 | 28-JUN-13:09 | 37.58 | 26.82 |
July | 0.980876E+10 | 13300.89 | 23-JUL-15:52 | 38.60 | 26.17 | 0.407198E+09 | 549.55 | 03-JUL-09:09 | 38.60 | 26.17 |
August | 0.107180E+11 | 13089.55 | 20-AUG-13:22 | 38.60 | 26.70 | 0.456513E+09 | 549.49 | 04-AUG-13:00 | 38.60 | 26.70 |
September | 0.875747E+10 | 13331.17 | 04-SEP-11:22 | 39.50 | 23.23 | 0.405531E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.765799E+10 | 10727.84 | 04-OCT-04:02 | 26.92 | 20.11 | 0.421476E+09 | 549.50 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.572595E+10 | 10103.30 | 06-NOV-07:03 | 20.58 | 17.98 | 0.416477E+09 | 549.50 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.375586E+10 | 7029.35 | 11-DEC-07:03 | 21.50 | 18.56 | 0.404004E+09 | 549.51 | 08-DEC-10:20 | 21.50 | 18.56 |
Annual Sum or Average | 0.781478E+11 | 0.503937E+10 | ||||||||
Minimum of Months | 0.303062E+10 | 4213.17 | 20.58 | 16.66 | 0.378573E+09 | 549.49 | 21.50 | 16.66 | ||
Maximum of Months | 0.107180E+11 | 13331.17 | 39.50 | 26.70 | 0.456513E+09 | 549.55 | 38.60 | 26.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253417E+10 | 3849.50 | 30-JAN-07:03 | 20.17 | 17.39 | 0.264972E+09 | 347.88 | 24-JAN-10:00 | 20.17 | 17.39 |
February | 0.253943E+10 | 4207.30 | 06-FEB-07:03 | 21.25 | 17.86 | 0.240636E+09 | 347.89 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.343976E+10 | 6026.95 | 26-MAR-10:53 | 33.00 | 16.79 | 0.287569E+09 | 347.90 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.421070E+10 | 8528.48 | 23-APR-11:32 | 33.00 | 17.03 | 0.256123E+09 | 347.91 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.627146E+10 | 11045.59 | 21-MAY-10:02 | 37.85 | 20.18 | 0.278025E+09 | 348.08 | 08-MAY-09:30 | 37.85 | 20.18 |
June | 0.669764E+10 | 9897.38 | 11-JUN-10:12 | 38.33 | 26.65 | 0.277133E+09 | 347.88 | 28-JUN-13:09 | 37.58 | 26.82 |
July | 0.745942E+10 | 11973.50 | 30-JUL-10:01 | 42.83 | 21.77 | 0.257941E+09 | 347.91 | 03-JUL-09:09 | 42.83 | 21.77 |
August | 0.830874E+10 | 11313.41 | 20-AUG-09:22 | 35.90 | 25.76 | 0.289143E+09 | 347.87 | 04-AUG-13:00 | 35.90 | 25.76 |
September | 0.692422E+10 | 11752.01 | 04-SEP-11:22 | 39.50 | 23.23 | 0.256921E+09 | 347.88 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.610523E+10 | 11019.66 | 09-OCT-09:13 | 31.10 | 27.33 | 0.267097E+09 | 347.88 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.453967E+10 | 9240.10 | 05-NOV-11:52 | 34.00 | 17.15 | 0.264086E+09 | 347.88 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.297277E+10 | 5690.72 | 04-DEC-07:02 | 17.83 | 16.73 | 0.256336E+09 | 347.88 | 08-DEC-10:20 | 23.20 | 18.74 |
Annual Sum or Average | 0.620032E+11 | 0.319598E+10 | ||||||||
Minimum of Months | 0.253417E+10 | 3849.50 | 17.83 | 16.73 | 0.240636E+09 | 347.87 | 20.17 | 17.19 | ||
Maximum of Months | 0.830874E+10 | 11973.50 | 42.83 | 27.33 | 0.289143E+09 | 348.08 | 42.83 | 26.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465986E+10 | 11100.03 | 23-JAN-13:00 | 27.40 | 16.52 | 0.413090E+09 | 549.52 | 23-JAN-14:39 | 26.00 | 16.86 |
February | 0.485709E+10 | 12900.50 | 07-FEB-13:00 | 31.00 | 20.84 | 0.376800E+09 | 588.60 | 07-FEB-13:09 | 31.00 | 20.70 |
March | 0.640765E+10 | 15125.09 | 27-MAR-12:00 | 37.30 | 19.38 | 0.451575E+09 | 708.59 | 27-MAR-12:09 | 37.08 | 19.46 |
April | 0.717294E+10 | 16436.45 | 28-APR-12:00 | 42.00 | 19.18 | 0.405203E+09 | 784.55 | 28-APR-12:09 | 41.12 | 20.13 |
May | 0.107237E+11 | 16046.54 | 09-MAY-12:00 | 41.00 | 19.42 | 0.446388E+09 | 760.20 | 09-MAY-12:09 | 41.02 | 19.49 |
June | 0.117676E+11 | 16925.21 | 12-JUN-12:00 | 43.00 | 24.56 | 0.447457E+09 | 802.91 | 12-JUN-12:09 | 42.65 | 25.06 |
July | 0.132555E+11 | 17791.23 | 21-JUL-12:00 | 46.00 | 22.01 | 0.418634E+09 | 859.61 | 21-JUL-12:09 | 45.38 | 23.17 |
August | 0.154067E+11 | 18105.60 | 16-AUG-12:00 | 46.00 | 25.38 | 0.472978E+09 | 872.97 | 16-AUG-12:09 | 45.70 | 25.45 |
September | 0.132963E+11 | 16804.76 | 05-SEP-12:00 | 41.00 | 24.24 | 0.418012E+09 | 796.38 | 05-SEP-12:09 | 40.98 | 24.12 |
October | 0.126029E+11 | 15624.04 | 04-OCT-12:00 | 38.00 | 19.81 | 0.430658E+09 | 733.64 | 04-OCT-12:09 | 37.77 | 20.04 |
November | 0.988360E+10 | 15536.61 | 05-NOV-11:52 | 34.00 | 17.15 | 0.419499E+09 | 645.77 | 06-NOV-13:09 | 32.42 | 19.73 |
December | 0.612050E+10 | 15171.25 | 25-DEC-13:53 | 27.00 | 18.66 | 0.402330E+09 | 563.78 | 04-DEC-13:09 | 27.00 | 18.66 |
Annual Sum or Average | 0.116154E+12 | 0.510262E+10 | ||||||||
Minimum of Months | 0.465986E+10 | 11100.03 | 27.00 | 16.52 | 0.376800E+09 | 549.52 | 26.00 | 16.86 | ||
Maximum of Months | 0.154067E+11 | 18105.60 | 46.00 | 25.38 | 0.472978E+09 | 872.97 | 45.70 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245658E+10 | 3964.20 | 30-JAN-07:03 | 20.17 | 17.39 | 0.264420E+09 | 347.86 | 17-JAN-10:20 | 20.17 | 17.39 |
February | 0.253467E+10 | 5562.45 | 05-FEB-16:23 | 31.50 | 18.69 | 0.240320E+09 | 347.86 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.352431E+10 | 7299.54 | 26-MAR-16:12 | 31.60 | 18.63 | 0.287518E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.404533E+10 | 8147.52 | 02-APR-17:12 | 30.00 | 18.66 | 0.256029E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.603300E+10 | 11738.32 | 21-MAY-16:01 | 37.42 | 23.26 | 0.277985E+09 | 347.88 | 04-MAY-13:00 | 37.42 | 23.26 |
June | 0.661459E+10 | 10771.81 | 18-JUN-16:02 | 35.98 | 27.42 | 0.277141E+09 | 347.86 | 28-JUN-13:09 | 37.58 | 26.82 |
July | 0.736121E+10 | 12445.83 | 23-JUL-15:52 | 38.60 | 26.17 | 0.257920E+09 | 347.88 | 03-JUL-09:09 | 38.60 | 26.17 |
August | 0.817990E+10 | 11891.00 | 06-AUG-16:22 | 40.05 | 25.93 | 0.289147E+09 | 347.85 | 04-AUG-13:00 | 40.05 | 25.93 |
September | 0.683519E+10 | 12282.16 | 04-SEP-18:02 | 37.70 | 25.12 | 0.256924E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.599196E+10 | 11568.13 | 22-OCT-15:32 | 31.60 | 23.78 | 0.267071E+09 | 347.85 | 20-OCT-09:20 | 31.60 | 23.78 |
November | 0.450815E+10 | 11641.85 | 05-NOV-15:12 | 31.80 | 21.10 | 0.263997E+09 | 347.86 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.298650E+10 | 5515.51 | 25-DEC-15:13 | 26.53 | 16.47 | 0.256225E+09 | 347.86 | 08-DEC-10:20 | 26.53 | 16.47 |
Annual Sum or Average | 0.610714E+11 | 0.319470E+10 | ||||||||
Minimum of Months | 0.245658E+10 | 3964.20 | 20.17 | 16.47 | 0.240320E+09 | 347.85 | 20.17 | 16.47 | ||
Maximum of Months | 0.817990E+10 | 12445.83 | 40.05 | 27.42 | 0.289147E+09 | 347.88 | 40.05 | 26.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272198E+10 | 4059.15 | 23-JAN-14:10 | 27.50 | 16.66 | 0.412185E+09 | 549.51 | 17-JAN-10:20 | 27.50 | 16.66 |
February | 0.299944E+10 | 5480.84 | 06-FEB-14:50 | 32.42 | 17.27 | 0.376918E+09 | 549.52 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.444084E+10 | 7065.40 | 02-MAR-06:03 | 28.80 | 15.43 | 0.452966E+09 | 549.53 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.538007E+10 | 10741.30 | 30-APR-16:32 | 31.17 | 25.64 | 0.403996E+09 | 549.55 | 28-APR-13:09 | 31.17 | 25.64 |
May | 0.798724E+10 | 12865.16 | 28-MAY-16:32 | 35.00 | 23.27 | 0.438949E+09 | 549.53 | 04-MAY-13:00 | 35.00 | 23.27 |
June | 0.865376E+10 | 11441.78 | 11-JUN-16:12 | 36.60 | 26.54 | 0.437608E+09 | 550.45 | 12-JUN-13:20 | 39.60 | 27.47 |
July | 0.935740E+10 | 12802.77 | 02-JUL-13:23 | 39.35 | 22.79 | 0.407283E+09 | 550.50 | 31-JUL-13:20 | 40.60 | 26.80 |
August | 0.977873E+10 | 13034.51 | 06-AUG-10:52 | 40.00 | 24.45 | 0.456526E+09 | 550.47 | 02-AUG-13:20 | 40.00 | 24.45 |
September | 0.771570E+10 | 13677.75 | 04-SEP-15:11 | 40.90 | 24.16 | 0.405451E+09 | 549.50 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.649532E+10 | 11809.79 | 29-OCT-14:12 | 33.33 | 19.69 | 0.421178E+09 | 549.50 | 20-OCT-09:20 | 33.33 | 19.69 |
November | 0.468851E+10 | 8488.61 | 20-NOV-05:02 | 26.00 | 18.81 | 0.415669E+09 | 549.51 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.315867E+10 | 4549.02 | 11-DEC-14:10 | 26.77 | 18.23 | 0.401158E+09 | 549.50 | 11-DEC-10:20 | 26.77 | 18.23 |
Annual Sum or Average | 0.733777E+11 | 0.502989E+10 | ||||||||
Minimum of Months | 0.272198E+10 | 4059.15 | 26.00 | 15.43 | 0.376918E+09 | 549.50 | 25.67 | 16.66 | ||
Maximum of Months | 0.977873E+10 | 13677.75 | 40.90 | 26.54 | 0.456526E+09 | 550.50 | 40.60 | 27.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204302E+10 | 4430.49 | 24-JAN-11:05 | 24.00 | 18.08 | 0.195161E+09 | 356.46 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.226673E+10 | 5494.33 | 07-FEB-13:03 | 31.00 | 20.70 | 0.177858E+09 | 356.46 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.335821E+10 | 9413.83 | 27-MAR-12:01 | 37.08 | 19.46 | 0.212739E+09 | 356.48 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.425391E+10 | 10314.07 | 23-APR-11:23 | 33.00 | 16.90 | 0.190244E+09 | 356.48 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.615527E+10 | 11766.16 | 07-MAY-09:52 | 36.50 | 17.98 | 0.206563E+09 | 356.49 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.640070E+10 | 11240.12 | 11-JUN-10:12 | 38.33 | 26.65 | 0.205640E+09 | 356.47 | 02-JUN-12:09 | 38.33 | 26.65 |
July | 0.687630E+10 | 11497.90 | 30-JUL-10:12 | 43.27 | 21.89 | 0.192081E+09 | 356.45 | 03-JUL-10:09 | 43.27 | 21.89 |
August | 0.734912E+10 | 11909.75 | 06-AUG-10:52 | 40.00 | 24.45 | 0.214502E+09 | 356.45 | 04-AUG-14:09 | 40.00 | 24.45 |
September | 0.590907E+10 | 11991.07 | 04-SEP-10:32 | 38.00 | 23.07 | 0.190958E+09 | 356.46 | 26-SEP-10:09 | 37.25 | 21.73 |
October | 0.502529E+10 | 11271.85 | 09-OCT-09:13 | 31.10 | 27.33 | 0.198534E+09 | 356.46 | 20-OCT-10:09 | 30.83 | 18.35 |
November | 0.354807E+10 | 8652.91 | 05-NOV-11:42 | 33.72 | 17.44 | 0.195914E+09 | 356.46 | 22-NOV-11:09 | 26.17 | 17.78 |
December | 0.229972E+10 | 4863.35 | 04-DEC-11:05 | 26.25 | 20.62 | 0.189363E+09 | 356.46 | 20-DEC-13:09 | 24.30 | 21.04 |
Annual Sum or Average | 0.554854E+11 | 0.236955E+10 | ||||||||
Minimum of Months | 0.204302E+10 | 4430.49 | 24.00 | 16.90 | 0.177858E+09 | 356.45 | 24.00 | 17.78 | ||
Maximum of Months | 0.734912E+10 | 11991.07 | 43.27 | 27.33 | 0.214502E+09 | 356.49 | 43.27 | 26.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485890E+10 | 9930.02 | 22-JAN-14:33 | 26.00 | 16.51 | 0.416977E+09 | 549.51 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.487876E+10 | 11527.98 | 05-FEB-11:43 | 30.67 | 18.90 | 0.379112E+09 | 549.54 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.603504E+10 | 14286.91 | 26-MAR-15:53 | 31.80 | 18.54 | 0.453809E+09 | 550.36 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.613449E+10 | 13614.66 | 30-APR-11:53 | 37.00 | 20.68 | 0.404262E+09 | 549.55 | 28-APR-13:09 | 37.00 | 20.68 |
May | 0.802222E+10 | 14397.45 | 07-MAY-15:52 | 34.10 | 22.06 | 0.438915E+09 | 549.53 | 04-MAY-13:00 | 34.10 | 22.06 |
June | 0.831098E+10 | 12718.59 | 29-JUN-04:02 | 32.67 | 25.60 | 0.437530E+09 | 549.52 | 02-JUN-13:09 | 32.67 | 25.60 |
July | 0.925100E+10 | 14336.55 | 02-JUL-13:23 | 39.35 | 22.79 | 0.407232E+09 | 549.54 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.103355E+11 | 14781.34 | 06-AUG-10:52 | 40.00 | 24.45 | 0.456566E+09 | 550.51 | 29-AUG-13:20 | 37.40 | 29.98 |
September | 0.926587E+10 | 15957.81 | 04-SEP-15:11 | 40.90 | 24.16 | 0.405692E+09 | 550.54 | 11-SEP-13:20 | 34.93 | 28.49 |
October | 0.910988E+10 | 15639.43 | 29-OCT-13:32 | 34.37 | 18.20 | 0.421742E+09 | 550.43 | 17-OCT-13:20 | 34.37 | 18.20 |
November | 0.746215E+10 | 15699.30 | 05-NOV-13:02 | 33.33 | 20.98 | 0.416783E+09 | 550.44 | 07-NOV-14:20 | 31.00 | 22.83 |
December | 0.550843E+10 | 15187.85 | 03-DEC-12:53 | 29.80 | 17.63 | 0.404062E+09 | 550.39 | 04-DEC-14:20 | 27.00 | 21.10 |
Annual Sum or Average | 0.891732E+11 | 0.504268E+10 | ||||||||
Minimum of Months | 0.485890E+10 | 9930.02 | 26.00 | 16.51 | 0.379112E+09 | 549.51 | 24.00 | 17.69 | ||
Maximum of Months | 0.103355E+11 | 15957.81 | 40.90 | 25.60 | 0.456566E+09 | 550.54 | 37.40 | 29.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216561E+10 | 3673.03 | 31-JAN-16:20 | 22.73 | 16.79 | 0.261597E+09 | 347.86 | 17-JAN-10:20 | 22.73 | 16.79 |
February | 0.244512E+10 | 6496.44 | 05-FEB-16:23 | 31.50 | 18.69 | 0.239050E+09 | 347.87 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.363491E+10 | 11950.05 | 26-MAR-15:53 | 31.80 | 18.54 | 0.287098E+09 | 347.87 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.426590E+10 | 12304.85 | 23-APR-16:42 | 31.25 | 19.17 | 0.255995E+09 | 347.88 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.612404E+10 | 12697.48 | 28-MAY-16:32 | 35.00 | 23.27 | 0.278007E+09 | 347.88 | 04-MAY-13:00 | 35.00 | 23.27 |
June | 0.651035E+10 | 12102.43 | 18-JUN-16:02 | 35.98 | 27.42 | 0.277128E+09 | 347.86 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.696494E+10 | 12135.83 | 02-JUL-16:02 | 38.17 | 23.16 | 0.257931E+09 | 347.88 | 03-JUL-09:09 | 34.37 | 23.66 |
August | 0.742683E+10 | 12229.41 | 13-AUG-17:32 | 37.33 | 25.70 | 0.289115E+09 | 347.85 | 04-AUG-09:20 | 37.33 | 25.70 |
September | 0.600068E+10 | 13632.28 | 04-SEP-15:51 | 40.70 | 24.03 | 0.256836E+09 | 347.86 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.509852E+10 | 12205.88 | 15-OCT-16:12 | 33.33 | 21.44 | 0.266827E+09 | 347.85 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.370770E+10 | 12032.69 | 05-NOV-15:02 | 31.90 | 20.93 | 0.263428E+09 | 347.86 | 28-NOV-10:20 | 25.73 | 19.64 |
December | 0.250188E+10 | 4562.88 | 03-DEC-14:53 | 27.00 | 20.88 | 0.254444E+09 | 347.86 | 11-DEC-10:20 | 24.07 | 19.01 |
Annual Sum or Average | 0.568465E+11 | 0.318746E+10 | ||||||||
Minimum of Months | 0.216561E+10 | 3673.03 | 22.73 | 16.79 | 0.239050E+09 | 347.85 | 22.73 | 16.79 | ||
Maximum of Months | 0.742683E+10 | 13632.28 | 40.70 | 27.42 | 0.289115E+09 | 347.88 | 37.33 | 27.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389135E+09 | 2692.42 | 03-JAN-06:03 | 12.93 |
February | 0.241214E+09 | 2540.56 | 13-FEB-06:03 | 13.03 |
March | 0.200963E+09 | 4598.87 | 28-MAR-05:03 | 25.67 |
April | 84001139.63 | 4465.21 | 25-APR-05:03 | 23.83 |
May | 22686807.85 | 5346.93 | 08-MAY-04:02 | 26.67 |
June | 14722739.86 | 3788.88 | 02-JUN-04:02 | 28.33 |
July | 6852454.28 | 2610.94 | 06-JUL-04:02 | 29.17 |
August | 4665324.78 | 2979.93 | 15-AUG-04:02 | 29.75 |
September | 16121906.77 | 5022.30 | 25-SEP-04:02 | 24.17 |
October | 27784645.58 | 4982.14 | 16-OCT-04:02 | 25.83 |
November | 76364993.76 | 4010.68 | 20-NOV-05:02 | 26.00 |
December | 0.258898E+09 | 2531.40 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.134341E+10 | |||
Minimum of Months | 4665324.78 | 2531.40 | 12.93 | |
Maximum of Months | 0.389135E+09 | 5346.93 | 29.75 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23976473.30 | 2111.04 | 22-JAN-12:00 | 24.00 |
February | 14566383.42 | 2437.17 | 05-FEB-11:43 | 30.67 |
March | 12742854.48 | 1979.39 | 26-MAR-15:53 | 31.80 |
April | 16118290.86 | 1976.92 | 30-APR-13:12 | 36.07 |
May | 17884315.15 | 2885.48 | 12-MAY-04:02 | 28.67 |
June | 17900673.22 | 2760.22 | 16-JUN-04:02 | 28.83 |
July | 28331768.25 | 3125.41 | 27-JUL-04:02 | 30.33 |
August | 27007444.91 | 3187.65 | 25-AUG-04:02 | 31.17 |
September | 18614443.27 | 3149.04 | 08-SEP-04:02 | 30.62 |
October | 21362408.09 | 2594.08 | 29-OCT-13:32 | 34.37 |
November | 21551346.78 | 2298.63 | 20-NOV-05:02 | 26.00 |
December | 22607099.24 | 2392.31 | 25-DEC-12:23 | 26.25 |
Annual Sum or Average | 0.242664E+09 | |||
Minimum of Months | 12742854.48 | 1976.92 | 24.00 | |
Maximum of Months | 28331768.25 | 3187.65 | 36.07 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50544361.29 | 3293.58 | 02-JAN-06:03 | 13.00 |
February | 30125180.98 | 2872.63 | 13-FEB-06:12 | 13.07 |
March | 25679663.70 | 3430.62 | 01-MAR-05:03 | 23.92 |
April | 21520207.35 | 3145.71 | 25-APR-04:52 | 24.00 |
May | 25953500.80 | 3798.98 | 12-MAY-04:02 | 28.67 |
June | 28851273.98 | 3845.15 | 28-JUN-04:02 | 29.00 |
July | 56636927.93 | 4152.39 | 13-JUL-04:02 | 30.58 |
August | 60095743.12 | 4178.08 | 25-AUG-04:02 | 31.17 |
September | 47578893.88 | 4620.93 | 28-SEP-04:02 | 27.75 |
October | 42643546.63 | 4436.94 | 05-OCT-04:02 | 27.83 |
November | 46298675.15 | 3966.27 | 01-NOV-04:42 | 23.95 |
December | 43150099.79 | 2808.01 | 18-DEC-06:12 | 13.33 |
Annual Sum or Average | 0.479078E+09 | |||
Minimum of Months | 21520207.35 | 2808.01 | 13.00 | |
Maximum of Months | 60095743.12 | 4620.93 | 31.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120424E+09 | 3499.45 | 09-JAN-07:15 | 12.33 |
February | 80485278.91 | 3453.04 | 01-FEB-08:00 | 14.00 |
March | 23367410.55 | 3426.91 | 16-MAR-06:07 | 15.00 |
April | 25129.43 | 209.41 | 05-APR-06:10 | 17.02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 18310403.77 | 3314.16 | 19-DEC-07:07 | 14.92 |
Annual Sum or Average | 0.242612E+09 | |||
Minimum of Months | 0.00 | 0.00 | 12.33 | |
Maximum of Months | 0.120424E+09 | 3499.45 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.210964E+11 | 14019.75 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.191215E+11 | 14019.75 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.217104E+11 | 14019.75 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.204846E+11 | 14019.75 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.214034E+11 | 14019.75 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.209475E+11 | 14019.75 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.209382E+11 | 14019.75 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.217104E+11 | 14019.75 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.204802E+11 | 14019.75 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.210986E+11 | 14019.75 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.204961E+11 | 14019.75 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.209360E+11 | 14019.75 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.250423E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.191215E+11 | 14019.75 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.217104E+11 | 14019.75 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.463753E+10 | 4936.01 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.420695E+10 | 4936.01 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.500524E+10 | 4936.01 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.446441E+10 | 4936.01 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.482138E+10 | 4936.01 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.480039E+10 | 4936.01 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.448540E+10 | 4936.01 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.500520E+10 | 4936.01 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.446441E+10 | 4936.01 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.463757E+10 | 4936.01 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.458488E+10 | 4936.01 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.448544E+10 | 4936.01 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.555988E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.420695E+10 | 4936.01 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.500524E+10 | 4936.01 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590529E+09 | 792.70 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.517549E+09 | 813.11 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599709E+09 | 941.63 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521785E+09 | 785.65 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547560E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.539355E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.513373E+09 | 583.25 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575141E+09 | 551.29 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525409E+09 | 564.90 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.560812E+09 | 714.53 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.576439E+09 | 879.27 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.579907E+09 | 901.00 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.664757E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.513373E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599709E+09 | 941.63 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369077E+09 | 525.69 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325937E+09 | 525.43 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378133E+09 | 587.85 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330389E+09 | 455.14 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349002E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344322E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326643E+09 | 356.57 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365062E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332465E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.352446E+09 | 345.00 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.363318E+09 | 571.14 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.362117E+09 | 577.45 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419891E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325937E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378133E+09 | 587.85 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569592E+09 | 705.49 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.507171E+09 | 772.61 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595851E+09 | 939.63 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522939E+09 | 790.72 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.553254E+09 | 536.28 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545592E+09 | 545.65 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517902E+09 | 701.96 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577811E+09 | 547.73 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524575E+09 | 562.30 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.553190E+09 | 558.02 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.558346E+09 | 769.90 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.555427E+09 | 846.20 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658165E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.507171E+09 | 536.28 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.595851E+09 | 939.63 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366426E+09 | 498.25 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323851E+09 | 474.33 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380529E+09 | 599.44 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.332320E+09 | 519.45 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350165E+09 | 357.81 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344765E+09 | 359.26 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.328188E+09 | 471.92 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366651E+09 | 431.03 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333678E+09 | 446.68 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354807E+09 | 486.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356977E+09 | 488.51 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356900E+09 | 552.17 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419526E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323851E+09 | 357.81 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380529E+09 | 599.44 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.588594E+09 | 782.53 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.516194E+09 | 804.35 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.598509E+09 | 937.83 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521171E+09 | 775.70 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547150E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.538957E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.512835E+09 | 580.42 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.574662E+09 | 547.07 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.524785E+09 | 561.29 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.559508E+09 | 700.40 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.574699E+09 | 872.81 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.577423E+09 | 895.55 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.663449E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.512835E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.598509E+09 | 937.83 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.368337E+09 | 521.32 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325324E+09 | 521.33 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.377556E+09 | 585.51 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330027E+09 | 447.86 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.348621E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344002E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326217E+09 | 354.28 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.364677E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332138E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.351888E+09 | 342.86 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.362596E+09 | 568.37 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361274E+09 | 574.92 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419266E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325324E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.377556E+09 | 585.51 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569021E+09 | 691.77 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.506486E+09 | 762.02 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.594720E+09 | 935.74 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522230E+09 | 781.02 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.552508E+09 | 531.47 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.544985E+09 | 541.29 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517189E+09 | 688.84 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577109E+09 | 543.29 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.523958E+09 | 558.54 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.552648E+09 | 553.81 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.557885E+09 | 758.35 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.554675E+09 | 838.20 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.657341E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.506486E+09 | 531.47 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594720E+09 | 935.74 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.365397E+09 | 493.27 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323203E+09 | 468.67 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.379808E+09 | 597.62 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.331745E+09 | 515.20 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349703E+09 | 356.00 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344178E+09 | 357.47 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.327703E+09 | 466.22 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366213E+09 | 424.22 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333122E+09 | 440.35 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354100E+09 | 480.84 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356290E+09 | 482.37 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356124E+09 | 548.88 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.418759E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323203E+09 | 356.00 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.379808E+09 | 597.62 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590527E+09 | 792.68 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.517548E+09 | 813.09 | 09-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.599708E+09 | 941.62 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.521784E+09 | 785.63 | 18-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.547560E+09 | 496.34 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.539354E+09 | 496.34 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.513372E+09 | 583.24 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.575140E+09 | 551.28 | 29-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.525408E+09 | 564.89 | 06-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.560811E+09 | 714.51 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.576437E+09 | 879.26 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.579905E+09 | 900.98 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.664755E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.513372E+09 | 496.34 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.599708E+09 | 941.62 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369076E+09 | 525.68 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.325936E+09 | 525.42 | 09-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.378132E+09 | 587.84 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.330389E+09 | 455.13 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.349001E+09 | 314.23 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344322E+09 | 314.23 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.326642E+09 | 356.57 | 20-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.365062E+09 | 314.23 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.332465E+09 | 314.23 | 01-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.352446E+09 | 344.99 | 27-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.363317E+09 | 571.13 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.362117E+09 | 577.44 | 14-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419891E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.325936E+09 | 314.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.378132E+09 | 587.84 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.569591E+09 | 705.47 | 23-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.507170E+09 | 772.59 | 09-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.595850E+09 | 939.62 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.522938E+09 | 790.70 | 18-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.553237E+09 | 536.27 | 23-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.545591E+09 | 545.64 | 08-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.517901E+09 | 701.93 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.577811E+09 | 547.72 | 29-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.524575E+09 | 562.29 | 06-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.553190E+09 | 558.01 | 27-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.558346E+09 | 769.88 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.555427E+09 | 846.18 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658163E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.507170E+09 | 536.27 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.595850E+09 | 939.62 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.366425E+09 | 498.23 | 09-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.323849E+09 | 474.32 | 09-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.380528E+09 | 599.43 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.332309E+09 | 519.44 | 18-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.350165E+09 | 357.81 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.344764E+09 | 359.26 | 08-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.328187E+09 | 471.91 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.366650E+09 | 431.01 | 29-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.333678E+09 | 446.66 | 06-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.354807E+09 | 486.90 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.356977E+09 | 488.50 | 03-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.356899E+09 | 552.16 | 15-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.419524E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.323849E+09 | 357.81 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.380528E+09 | 599.43 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.210964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.204846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.214034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.209475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.209382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.204802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.210986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.204961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.209360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.250423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.191215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.217104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.463753E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.446441E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.482138E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.480039E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.448540E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.500520E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.446441E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.463757E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.458488E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.448544E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.555988E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.420695E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.500524E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.590529E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007751.24 | 71967586.08 |
February | 0.901968E+09 | 0.517549E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7787696.03 | 73142328.54 |
March | 0.107774E+10 | 0.599709E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19251576.71 | 40468819.84 |
April | 0.956342E+09 | 0.521785E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46155867.01 | 18424232.65 |
May | 0.103597E+10 | 0.547560E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114217E+09 | 2117188.42 |
June | 0.103308E+10 | 0.539355E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142543E+09 | 206510.62 |
July | 0.959235E+09 | 0.513373E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203758E+09 | 0.00 |
August | 0.107774E+10 | 0.575141E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195435E+09 | 0.00 |
September | 0.956342E+09 | 0.525409E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136821E+09 | 314163.67 |
October | 0.994195E+09 | 0.560812E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78148350.88 | 3015272.11 |
November | 0.984487E+09 | 0.576439E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32377117.42 | 18985051.31 |
December | 0.959235E+09 | 0.579907E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5125637.56 | 52729750.29 |
Annual Sum or Average | 0.119305E+11 | 0.664757E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982628E+09 | 0.281371E+09 |
Minimum of Months | 0.901968E+09 | 0.513373E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007751.24 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.599709E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203758E+09 | 73142328.54 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.369077E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362061.88 | 50666992.33 |
February | 0.571020E+09 | 0.325937E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4535333.81 | 50765470.03 |
March | 0.682301E+09 | 0.378133E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12527900.61 | 28107009.99 |
April | 0.605444E+09 | 0.330389E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29844706.52 | 12690809.99 |
May | 0.655854E+09 | 0.349002E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75467037.35 | 1482679.03 |
June | 0.654023E+09 | 0.344322E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94566701.67 | 154706.55 |
July | 0.607275E+09 | 0.326643E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135164E+09 | 0.00 |
August | 0.682301E+09 | 0.365062E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129575E+09 | 0.00 |
September | 0.605444E+09 | 0.332465E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90261302.45 | 222992.11 |
October | 0.629407E+09 | 0.352446E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51086895.48 | 2203445.76 |
November | 0.623262E+09 | 0.363318E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20130805.61 | 13514487.34 |
December | 0.607275E+09 | 0.362117E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2957077.88 | 36577548.30 |
Annual Sum or Average | 0.755301E+10 | 0.419891E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646479E+09 | 0.196386E+09 |
Minimum of Months | 0.571020E+09 | 0.325937E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 362061.88 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.378133E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135164E+09 | 50765470.03 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569592E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401810.27 | 82774875.12 |
February | 0.901968E+09 | 0.507171E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6588879.54 | 80137457.59 |
March | 0.107774E+10 | 0.595851E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18592154.58 | 43690453.26 |
April | 0.956342E+09 | 0.522939E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45144459.12 | 18898872.18 |
May | 0.103597E+10 | 0.553254E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114347E+09 | 2127488.38 |
June | 0.103308E+10 | 0.545592E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142970E+09 | 201359.71 |
July | 0.959235E+09 | 0.517902E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204072E+09 | 0.00 |
August | 0.107774E+10 | 0.577811E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195188E+09 | 0.00 |
September | 0.956342E+09 | 0.524575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135415E+09 | 337479.40 |
October | 0.994195E+09 | 0.553190E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75419488.03 | 3549233.31 |
November | 0.984487E+09 | 0.558346E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28530137.90 | 21501830.82 |
December | 0.959235E+09 | 0.555427E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3802232.36 | 60411035.23 |
Annual Sum or Average | 0.119305E+11 | 0.658165E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970470E+09 | 0.313630E+09 |
Minimum of Months | 0.901968E+09 | 0.507171E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401810.27 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.595851E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204072E+09 | 82774875.12 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.366426E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508589.76 | 50937090.29 |
February | 0.570983E+09 | 0.323851E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4869519.88 | 51229198.56 |
March | 0.682256E+09 | 0.380529E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12479388.36 | 29041576.66 |
April | 0.605404E+09 | 0.332320E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29636126.32 | 13156139.85 |
May | 0.655811E+09 | 0.350165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75101543.66 | 1529891.56 |
June | 0.653980E+09 | 0.344765E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93875511.13 | 159758.93 |
July | 0.607235E+09 | 0.328188E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134802E+09 | 0.00 |
August | 0.682256E+09 | 0.366651E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129144E+09 | 0.00 |
September | 0.605404E+09 | 0.333678E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89663123.71 | 228541.04 |
October | 0.629366E+09 | 0.354807E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50584193.13 | 2239238.69 |
November | 0.623221E+09 | 0.356977E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20091959.00 | 13416236.36 |
December | 0.607235E+09 | 0.356900E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952892.16 | 37332542.36 |
Annual Sum or Average | 0.755252E+10 | 0.419526E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643708E+09 | 0.199270E+09 |
Minimum of Months | 0.570983E+09 | 0.323851E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 508589.76 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.380529E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134802E+09 | 51229198.56 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.588594E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497742.51 | 44818901.80 |
February | 0.901968E+09 | 0.516194E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4312426.58 | 43380815.81 |
March | 0.107774E+10 | 0.598509E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10662052.67 | 22816718.73 |
April | 0.956342E+09 | 0.521171E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26029537.83 | 9893208.23 |
May | 0.103597E+10 | 0.547150E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62306402.89 | 949471.50 |
June | 0.103308E+10 | 0.538957E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77163388.92 | 95219.34 |
July | 0.959235E+09 | 0.512835E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109884E+09 | 0.00 |
August | 0.107774E+10 | 0.574662E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105215E+09 | 0.00 |
September | 0.956342E+09 | 0.524785E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73682192.43 | 175707.47 |
October | 0.994195E+09 | 0.559508E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41777417.57 | 1992138.11 |
November | 0.984487E+09 | 0.574699E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17266011.59 | 12580036.79 |
December | 0.959235E+09 | 0.577423E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2667685.63 | 33947074.80 |
Annual Sum or Average | 0.119305E+11 | 0.663449E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531464E+09 | 0.170649E+09 |
Minimum of Months | 0.901968E+09 | 0.512835E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497742.51 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.598509E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109884E+09 | 44818901.80 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.368337E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191651.44 | 31493349.71 |
February | 0.571020E+09 | 0.325324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2505377.91 | 30311635.74 |
March | 0.682301E+09 | 0.377556E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6821153.15 | 16012979.31 |
April | 0.605444E+09 | 0.330027E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16341180.91 | 7054776.87 |
May | 0.655854E+09 | 0.348621E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40763098.11 | 735054.31 |
June | 0.654023E+09 | 0.344002E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50830410.06 | 79879.56 |
July | 0.607275E+09 | 0.326217E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72547588.53 | 0.00 |
August | 0.682301E+09 | 0.364677E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69453126.96 | 0.00 |
September | 0.605444E+09 | 0.332138E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48279807.98 | 136815.14 |
October | 0.629407E+09 | 0.351888E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27083620.54 | 1544233.67 |
November | 0.623262E+09 | 0.362596E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10710397.15 | 9106614.18 |
December | 0.607275E+09 | 0.361274E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1574434.56 | 23522169.81 |
Annual Sum or Average | 0.755301E+10 | 0.419266E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347102E+09 | 0.119998E+09 |
Minimum of Months | 0.571020E+09 | 0.325324E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191651.44 | 0.00 |
Maximum of Months | 0.682301E+09 | 0.377556E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72547588.53 | 31493349.71 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569021E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21402002.68 | 0.146454E+10 |
February | 0.901968E+09 | 0.506486E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251362E+09 | 0.892808E+09 |
March | 0.107774E+10 | 0.594720E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874620E+09 | 0.575867E+09 |
April | 0.956342E+09 | 0.522230E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161675E+10 | 0.210049E+09 |
May | 0.103597E+10 | 0.552508E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333277E+10 | 36508631.25 |
June | 0.103308E+10 | 0.544985E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392003E+10 | 1350499.34 |
July | 0.959235E+09 | 0.517189E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412404E+10 | 0.00 |
August | 0.107774E+10 | 0.577109E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476464E+10 | 0.00 |
September | 0.956342E+09 | 0.523958E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331660E+10 | 2823191.01 |
October | 0.994195E+09 | 0.552648E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240834E+10 | 24659485.33 |
November | 0.984487E+09 | 0.557885E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129798E+10 | 0.302231E+09 |
December | 0.959235E+09 | 0.554675E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200735E+09 | 0.847772E+09 |
Annual Sum or Average | 0.119305E+11 | 0.657341E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261293E+11 | 0.435861E+10 |
Minimum of Months | 0.901968E+09 | 0.506486E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21402002.68 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.594720E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476464E+10 | 0.146454E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.365397E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240468.60 | 31719374.56 |
February | 0.570983E+09 | 0.323203E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2608657.75 | 30670246.96 |
March | 0.682256E+09 | 0.379808E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6739054.20 | 16728275.79 |
April | 0.605404E+09 | 0.331745E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16158553.10 | 7326574.94 |
May | 0.655811E+09 | 0.349703E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40455025.46 | 773936.08 |
June | 0.653980E+09 | 0.344178E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50314776.27 | 86463.45 |
July | 0.607235E+09 | 0.327703E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72245383.79 | 0.00 |
August | 0.682256E+09 | 0.366213E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69147842.07 | 0.00 |
September | 0.605404E+09 | 0.333122E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47891372.88 | 143577.75 |
October | 0.629366E+09 | 0.354100E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26760570.42 | 1598000.53 |
November | 0.623221E+09 | 0.356290E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10596181.44 | 9159776.48 |
December | 0.607235E+09 | 0.356124E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548615.68 | 23954881.49 |
Annual Sum or Average | 0.755252E+10 | 0.418759E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344707E+09 | 0.122161E+09 |
Minimum of Months | 0.570983E+09 | 0.323203E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240468.60 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.379808E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72245383.79 | 31719374.56 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.590527E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 857382.99 | 66056841.81 |
February | 0.901968E+09 | 0.517548E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6666165.64 | 65671545.28 |
March | 0.107774E+10 | 0.599708E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16284072.31 | 36154829.58 |
April | 0.956342E+09 | 0.521784E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39282811.55 | 16352073.19 |
May | 0.103597E+10 | 0.547560E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96065850.55 | 1849059.28 |
June | 0.103308E+10 | 0.539354E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119563E+09 | 167499.76 |
July | 0.959235E+09 | 0.513372E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170513E+09 | 0.00 |
August | 0.107774E+10 | 0.575140E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163415E+09 | 0.00 |
September | 0.956342E+09 | 0.525408E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114814E+09 | 261411.63 |
October | 0.994195E+09 | 0.560811E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65677560.32 | 2720873.43 |
November | 0.984487E+09 | 0.576437E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27519891.06 | 17674029.33 |
December | 0.959235E+09 | 0.579905E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4322577.16 | 48398624.59 |
Annual Sum or Average | 0.119305E+11 | 0.664755E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824981E+09 | 0.255307E+09 |
Minimum of Months | 0.901968E+09 | 0.513372E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 857382.99 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.599708E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170513E+09 | 66056841.81 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.369076E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 282224.45 | 46298500.63 |
February | 0.421807E+09 | 0.325936E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3729678.60 | 45532424.60 |
March | 0.502994E+09 | 0.378132E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10239786.78 | 25102927.99 |
April | 0.447140E+09 | 0.330389E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24809565.99 | 11254536.88 |
May | 0.484071E+09 | 0.349001E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63008782.96 | 1294424.64 |
June | 0.482240E+09 | 0.344322E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78807003.36 | 126582.51 |
July | 0.448971E+09 | 0.326642E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112600E+09 | 0.00 |
August | 0.502994E+09 | 0.365062E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107808E+09 | 0.00 |
September | 0.447140E+09 | 0.332465E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75242690.20 | 185913.15 |
October | 0.465148E+09 | 0.352446E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42539523.95 | 1977521.02 |
November | 0.460569E+09 | 0.363317E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16739813.47 | 12478262.78 |
December | 0.448971E+09 | 0.362117E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2373199.86 | 33483090.23 |
Annual Sum or Average | 0.557719E+10 | 0.419891E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538180E+09 | 0.177734E+09 |
Minimum of Months | 0.421807E+09 | 0.325936E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 282224.45 | 0.00 |
Maximum of Months | 0.502994E+09 | 0.378132E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112600E+09 | 46298500.63 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.569591E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 344523.57 | 74367299.31 |
February | 0.901968E+09 | 0.507170E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5538995.98 | 71260292.10 |
March | 0.107774E+10 | 0.595850E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15551714.47 | 38775738.66 |
April | 0.956342E+09 | 0.522938E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38091845.38 | 16734995.72 |
May | 0.103597E+10 | 0.553237E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96222578.58 | 1856024.12 |
June | 0.103308E+10 | 0.545591E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120062E+09 | 162168.56 |
July | 0.959235E+09 | 0.517901E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170854E+09 | 0.00 |
August | 0.107774E+10 | 0.577811E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163174E+09 | 0.00 |
September | 0.956342E+09 | 0.524575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113431E+09 | 281887.28 |
October | 0.994195E+09 | 0.553190E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63200585.28 | 3155001.92 |
November | 0.984487E+09 | 0.558346E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23856279.20 | 19743837.23 |
December | 0.959235E+09 | 0.555427E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3215208.31 | 54276283.16 |
Annual Sum or Average | 0.119305E+11 | 0.658163E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813542E+09 | 0.280614E+09 |
Minimum of Months | 0.901968E+09 | 0.507170E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 344523.57 | 0.00 |
Maximum of Months | 0.107774E+10 | 0.595850E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170854E+09 | 74367299.31 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.366425E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 419181.62 | 46310181.95 |
February | 0.570983E+09 | 0.323849E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4083995.45 | 45721895.92 |
March | 0.682256E+09 | 0.380528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10450771.64 | 25820608.73 |
April | 0.605404E+09 | 0.332309E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24896204.49 | 11613034.93 |
May | 0.655811E+09 | 0.350165E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62953990.62 | 1334281.53 |
June | 0.653980E+09 | 0.344764E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78575830.37 | 128871.00 |
July | 0.607235E+09 | 0.328187E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112574E+09 | 0.00 |
August | 0.682256E+09 | 0.366650E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107832E+09 | 0.00 |
September | 0.605404E+09 | 0.333678E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74990520.06 | 191200.78 |
October | 0.629366E+09 | 0.354807E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42364993.39 | 2001715.50 |
November | 0.623221E+09 | 0.356977E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16844342.00 | 12408631.30 |
December | 0.607235E+09 | 0.356899E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2482351.25 | 33925169.68 |
Annual Sum or Average | 0.755252E+10 | 0.419524E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538469E+09 | 0.179456E+09 |
Minimum of Months | 0.570983E+09 | 0.323849E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 419181.62 | 0.00 |
Maximum of Months | 0.682256E+09 | 0.380528E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112574E+09 | 46310181.95 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474583.13 | 99587343.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7052084.59 | 96399233.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17686008.43 | 52255578.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45507852.48 | 22308289.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117213E+09 | 2229329.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147430E+09 | 221384.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211281E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201085E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139821E+09 | 356612.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76897873.33 | 3940456.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28808064.91 | 25620203.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3689899.61 | 72960279.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996946E+09 | 0.375879E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474583.13 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211281E+09 | 99587343.77 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052100.49 | 0.117461E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9742872.44 | 0.116738E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23388010.94 | 63740659.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59191316.80 | 27863490.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150881E+09 | 2894864.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190069E+09 | 273702.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272603E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260054E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181317E+09 | 445144.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100742E+09 | 4572730.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39240591.81 | 30417948.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5574760.07 | 86383498.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129386E+10 | 0.450791E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052100.49 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272603E+09 | 0.117461E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320711.53 | 0.115577E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8079053.50 | 0.114068E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22605713.76 | 62947848.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52577974.47 | 23660295.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153562E+09 | 2035253.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200182E+09 | 208941.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285297E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275759E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189884E+09 | 308350.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104805E+09 | 2759207.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37077188.80 | 23549310.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3530470.64 | 81786618.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133368E+10 | 0.426900E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320711.53 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285297E+09 | 0.115577E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 14019.75 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 14019.75 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 14019.75 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 14019.75 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 14019.75 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 14019.75 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 14019.75 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 14019.75 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 14019.75 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 14019.75 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 14019.75 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 14019.75 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 14019.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4936.01 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4936.01 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4936.01 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4936.01 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4936.01 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4936.01 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4936.01 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4936.01 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4936.01 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4936.01 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4936.01 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4936.01 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 792.70 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 29-JAN-11:50 | 187.53 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 813.11 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 169.46 | 05-FEB-15:00 | 156.94 | 10-FEB-23:10 |
March | 1306.65 | 01-MAR-10:09 | 941.63 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.92 | 26-MAR-13:53 | 165.07 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 785.65 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.66 | 30-APR-12:53 | 106.12 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.33 | 21-MAY-12:54 | 38.74 | 01-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.95 | 11-JUN-12:55 | 27.79 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 583.25 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 451.35 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 551.29 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.70 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 564.90 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.15 | 03-SEP-15:54 | 28.74 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 714.53 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.99 | 09-OCT-15:14 | 51.67 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 879.27 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.93 | 19-NOV-13:52 | 85.24 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 901.00 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.89 | 10-DEC-12:20 | 122.62 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.84 | 0.00 | |||||
Maximum of Months | 1306.65 | 941.63 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.33 | 187.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 525.69 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 | 29-JAN-11:50 | 125.39 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 525.43 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.19 | 05-FEB-14:48 | 105.23 | 10-FEB-23:10 |
March | 827.22 | 01-MAR-10:09 | 587.85 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.62 | 26-MAR-13:53 | 113.28 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 455.14 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 | 30-APR-12:53 | 70.96 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 811.52 | 21-MAY-12:54 | 26.04 | 01-MAY-04:55 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.91 | 11-JUN-14:54 | 18.75 | 07-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 356.57 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.42 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.13 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.57 | 03-SEP-15:54 | 19.39 | 25-SEP-05:00 |
October | 827.22 | 02-OCT-09:09 | 345.00 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.24 | 09-OCT-15:14 | 34.52 | 20-OCT-04:50 |
November | 827.22 | 01-NOV-09:09 | 571.14 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 | 19-NOV-14:08 | 56.54 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 577.45 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.75 | 10-DEC-12:20 | 81.06 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 | 0.00 | |||||
Maximum of Months | 827.22 | 587.85 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 811.52 | 125.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 705.49 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 23-JAN-13:00 | 195.03 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 772.61 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 | 05-FEB-14:45 | 166.01 | 10-FEB-23:10 |
March | 1306.65 | 01-MAR-10:09 | 939.63 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 141.85 | 26-MAR-13:53 | 187.57 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 790.72 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.52 | 30-APR-12:53 | 107.42 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 536.28 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.37 | 21-MAY-12:54 | 39.10 | 01-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 545.65 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.20 | 11-JUN-14:54 | 27.88 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 701.96 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.56 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.73 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.69 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 562.30 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.02 | 03-SEP-15:54 | 29.27 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 558.02 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.47 | 09-OCT-15:00 | 53.23 | 20-OCT-04:50 |
November | 1306.65 | 01-NOV-09:09 | 769.90 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.52 | 19-NOV-14:05 | 86.73 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 846.20 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.73 | 10-DEC-12:47 | 122.97 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.28 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 | 0.00 | |||||
Maximum of Months | 1306.65 | 939.63 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1218.37 | 195.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 498.25 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 29-JAN-11:50 | 126.33 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 474.33 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.64 | 05-FEB-14:45 | 108.45 | 10-FEB-23:10 |
March | 827.17 | 01-MAR-10:09 | 599.44 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.60 | 26-MAR-13:53 | 120.72 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 519.45 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.81 | 30-APR-12:53 | 72.51 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 357.81 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 814.48 | 21-MAY-12:54 | 26.40 | 01-MAY-04:55 |
June | 827.17 | 01-JUN-09:09 | 359.26 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.22 | 11-JUN-12:55 | 19.27 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 471.92 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.34 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 431.03 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.13 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 446.68 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.99 | 03-SEP-16:00 | 19.62 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 486.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.39 | 09-OCT-15:14 | 35.10 | 20-OCT-04:50 |
November | 827.17 | 01-NOV-09:09 | 488.51 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.44 | 19-NOV-14:05 | 56.98 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 552.17 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 | 10-DEC-11:50 | 81.11 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 357.81 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 0.00 | |||||
Maximum of Months | 827.17 | 599.44 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 814.48 | 126.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 782.53 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 29-JAN-11:55 | 120.17 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 804.35 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 05-FEB-14:50 | 95.48 | 10-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 937.83 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.73 | 26-MAR-14:00 | 84.01 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 775.70 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.97 | 30-APR-13:00 | 59.66 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.18 | 21-MAY-12:52 | 18.50 | 01-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.56 | 11-JUN-14:56 | 12.63 | 07-JUN-04:45 |
July | 1306.65 | 03-JUL-09:09 | 580.42 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.06 | 30-JUL-14:44 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.07 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.12 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 561.29 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 | 03-SEP-15:56 | 15.67 | 25-SEP-04:55 |
October | 1306.65 | 02-OCT-09:09 | 700.40 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.04 | 09-OCT-15:16 | 34.93 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 872.81 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.59 | 19-NOV-14:00 | 55.35 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 895.55 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 10-DEC-12:00 | 77.16 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 0.00 | |||||
Maximum of Months | 1306.65 | 937.83 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 639.18 | 120.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 521.32 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 29-JAN-12:00 | 82.53 | 18-JAN-04:00 |
February | 827.22 | 01-FEB-10:09 | 521.33 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.56 | 05-FEB-14:50 | 65.07 | 13-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 585.51 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.31 | 26-MAR-13:53 | 56.89 | 05-MAR-15:00 |
April | 827.22 | 03-APR-09:09 | 447.86 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.56 | 30-APR-12:57 | 40.66 | 05-APR-01:00 |
May | 827.22 | 01-MAY-09:09 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 21-MAY-12:52 | 13.11 | 01-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.42 | 11-JUN-14:54 | 8.99 | 07-JUN-04:45 |
July | 827.22 | 03-JUL-09:09 | 354.28 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.27 | 30-JUL-14:43 | 0.00 | 01-JUL-00:10 |
August | 827.22 | 01-AUG-09:09 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.00 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.22 | 01-SEP-09:09 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.74 | 03-SEP-15:54 | 11.16 | 25-SEP-04:55 |
October | 827.22 | 02-OCT-09:09 | 342.86 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 | 09-OCT-15:16 | 24.39 | 20-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 568.37 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.31 | 19-NOV-13:56 | 37.15 | 22-NOV-06:00 |
December | 827.22 | 01-DEC-10:09 | 574.92 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 10-DEC-12:40 | 51.28 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 0.00 | |||||
Maximum of Months | 827.22 | 585.51 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 82.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 691.77 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.12 | 23-JAN-13:00 | 12613.26 | 09-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 762.02 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7288.94 | 07-FEB-13:00 | 11200.16 | 13-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 935.74 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15717.05 | 27-MAR-11:01 | 9153.35 | 07-MAR-07:02 |
April | 1306.65 | 03-APR-09:09 | 781.02 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18416.20 | 28-APR-11:01 | 6897.14 | 05-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 531.47 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18230.18 | 09-MAY-11:01 | 4388.73 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 541.29 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20235.26 | 12-JUN-11:01 | 538.52 | 22-JUN-08:00 |
July | 1306.65 | 03-JUL-09:09 | 688.84 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23271.79 | 21-JUL-11:01 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 543.29 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22493.49 | 16-AUG-11:01 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 558.54 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17821.71 | 12-SEP-11:01 | 1053.78 | 25-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 553.81 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14146.13 | 04-OCT-11:01 | 2696.35 | 30-OCT-06:03 |
November | 1306.65 | 01-NOV-09:09 | 758.35 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9199.71 | 01-NOV-11:02 | 7986.69 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 838.20 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4860.39 | 01-DEC-12:05 | 11853.47 | 26-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 531.47 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.12 | 0.00 | |||||
Maximum of Months | 1306.65 | 935.74 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 23271.79 | 12613.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 493.27 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 29-JAN-11:55 | 82.71 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 468.67 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.01 | 05-FEB-15:07 | 66.09 | 10-FEB-23:20 |
March | 827.17 | 01-MAR-10:09 | 597.62 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 | 26-MAR-13:53 | 61.14 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 515.20 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.48 | 30-APR-12:57 | 41.66 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 356.00 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.11 | 21-MAY-12:52 | 13.35 | 01-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 357.47 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.35 | 11-JUN-12:55 | 9.47 | 07-JUN-04:45 |
July | 827.17 | 03-JUL-09:09 | 466.22 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.37 | 30-JUL-14:50 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 424.22 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.00 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 440.35 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.30 | 03-SEP-15:54 | 11.36 | 25-SEP-04:55 |
October | 827.17 | 02-OCT-09:09 | 480.84 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.84 | 09-OCT-15:14 | 24.89 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 482.37 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 19-NOV-13:56 | 37.60 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 548.88 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 10-DEC-12:00 | 51.31 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 356.00 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 0.00 | |||||
Maximum of Months | 827.17 | 597.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 426.11 | 82.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 792.68 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 29-JAN-11:55 | 174.23 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 813.09 | 09-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.93 | 05-FEB-14:50 | 143.35 | 13-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 941.62 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.63 | 26-MAR-14:00 | 136.03 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 785.63 | 18-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.38 | 30-APR-12:53 | 93.64 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 496.34 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.81 | 21-MAY-12:54 | 32.88 | 01-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 496.34 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.54 | 11-JUN-14:54 | 23.75 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 583.24 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.46 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 551.28 | 29-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.22 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 564.89 | 06-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.46 | 03-SEP-15:54 | 24.68 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 714.51 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.51 | 09-OCT-15:16 | 47.41 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 879.26 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.70 | 19-NOV-14:00 | 78.43 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 900.98 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 10-DEC-12:10 | 110.70 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 56.42 | 0.00 | |||||
Maximum of Months | 1306.65 | 941.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.81 | 174.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 525.68 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 29-JAN-12:00 | 116.46 | 18-JAN-04:00 |
February | 805.43 | 01-FEB-08:09 | 525.42 | 09-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.83 | 05-FEB-14:50 | 95.95 | 13-FEB-04:00 |
March | 805.43 | 01-MAR-08:09 | 587.84 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.44 | 26-MAR-13:57 | 93.24 | 05-MAR-15:00 |
April | 805.43 | 03-APR-07:10 | 455.13 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 | 30-APR-12:53 | 62.67 | 05-APR-01:00 |
May | 805.43 | 01-MAY-07:10 | 314.23 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.51 | 21-MAY-12:54 | 22.10 | 01-MAY-04:55 |
June | 805.43 | 01-JUN-07:10 | 314.23 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.81 | 11-JUN-14:54 | 16.06 | 07-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 356.57 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.68 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 805.43 | 01-AUG-07:10 | 314.23 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.81 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 805.43 | 01-SEP-07:10 | 314.23 | 01-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.53 | 03-SEP-15:54 | 16.63 | 25-SEP-05:00 |
October | 805.43 | 02-OCT-07:10 | 344.99 | 27-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 | 09-OCT-15:16 | 31.74 | 20-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 571.13 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.66 | 19-NOV-14:00 | 52.01 | 22-NOV-06:00 |
December | 805.43 | 01-DEC-08:09 | 577.44 | 14-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 10-DEC-12:50 | 73.27 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 0.00 | |||||
Maximum of Months | 805.43 | 587.84 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 679.51 | 116.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 705.47 | 23-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 23-JAN-13:00 | 180.11 | 18-JAN-04:00 |
February | 1306.65 | 01-FEB-10:09 | 772.59 | 09-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.60 | 05-FEB-15:07 | 149.11 | 10-FEB-23:20 |
March | 1306.65 | 01-MAR-10:09 | 939.62 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.77 | 26-MAR-13:57 | 153.25 | 05-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 790.70 | 18-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.30 | 30-APR-12:53 | 94.70 | 05-APR-01:00 |
May | 1306.65 | 01-MAY-09:09 | 536.27 | 23-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.83 | 21-MAY-12:54 | 33.20 | 01-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 545.64 | 08-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.44 | 11-JUN-14:54 | 23.80 | 07-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 701.93 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.65 | 30-JUL-14:54 | 0.00 | 01-JUL-00:10 |
August | 1306.65 | 01-AUG-09:09 | 547.72 | 29-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.22 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1306.65 | 01-SEP-09:09 | 562.29 | 06-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.17 | 03-SEP-15:54 | 25.19 | 25-SEP-05:00 |
October | 1306.65 | 02-OCT-09:09 | 558.01 | 27-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.88 | 09-OCT-15:00 | 48.78 | 20-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 769.88 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 19-NOV-14:00 | 79.57 | 22-NOV-06:00 |
December | 1306.65 | 01-DEC-10:09 | 846.18 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 | 10-DEC-12:30 | 110.91 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 536.27 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 17.72 | 0.00 | |||||
Maximum of Months | 1306.65 | 939.62 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.83 | 180.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 498.23 | 09-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 | 29-JAN-11:55 | 117.03 | 18-JAN-04:00 |
February | 827.17 | 01-FEB-10:09 | 474.32 | 09-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.48 | 05-FEB-15:07 | 97.53 | 10-FEB-23:20 |
March | 827.17 | 01-MAR-10:09 | 599.43 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 26-MAR-13:57 | 99.22 | 05-MAR-15:00 |
April | 827.17 | 03-APR-09:09 | 519.44 | 18-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.87 | 30-APR-12:53 | 63.86 | 05-APR-01:00 |
May | 827.17 | 01-MAY-09:09 | 357.81 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 677.97 | 21-MAY-12:54 | 22.44 | 01-MAY-04:55 |
June | 827.17 | 01-JUN-09:09 | 359.26 | 08-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.88 | 11-JUN-12:55 | 16.43 | 07-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 471.91 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.97 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 827.17 | 01-AUG-09:09 | 431.01 | 29-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.81 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 827.17 | 01-SEP-09:09 | 446.66 | 06-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.76 | 03-SEP-15:54 | 16.84 | 25-SEP-05:00 |
October | 827.17 | 02-OCT-09:09 | 486.90 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 | 09-OCT-15:14 | 32.09 | 20-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 488.50 | 03-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.91 | 19-NOV-13:38 | 52.32 | 22-NOV-06:00 |
December | 827.17 | 01-DEC-10:09 | 552.16 | 15-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.32 | 10-DEC-12:10 | 73.19 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 357.81 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 | 0.00 | |||||
Maximum of Months | 827.17 | 599.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 677.97 | 117.03 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.45 | 29-JAN-12:00 | 256.46 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.30 | 05-FEB-14:53 | 209.99 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.03 | 26-MAR-14:00 | 187.78 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.51 | 30-APR-12:53 | 130.40 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.00 | 21-MAY-13:00 | 41.30 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.56 | 11-JUN-13:20 | 31.18 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.24 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.84 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.38 | 03-SEP-16:00 | 33.83 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.92 | 09-OCT-15:00 | 64.56 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.91 | 19-NOV-14:00 | 113.99 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 10-DEC-12:03 | 160.23 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.45 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.00 | 256.46 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 29-JAN-12:00 | 305.10 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.09 | 05-FEB-14:53 | 255.77 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.61 | 26-MAR-14:00 | 229.40 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.86 | 30-APR-12:57 | 164.42 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.96 | 21-MAY-13:00 | 55.20 | 01-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.67 | 11-JUN-13:20 | 38.05 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.87 | 30-JUL-14:40 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 560.79 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.42 | 03-SEP-16:00 | 42.15 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.91 | 09-OCT-15:00 | 76.92 | 20-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.62 | 19-NOV-14:00 | 140.23 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.92 | 10-DEC-12:13 | 196.74 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584.96 | 305.10 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 29-JAN-11:55 | 271.78 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.85 | 05-FEB-15:00 | 241.77 | 19-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.85 | 02-MAR-04:00 | 293.52 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.34 | 30-APR-13:00 | 147.76 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.66 | 21-MAY-13:00 | 53.75 | 01-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.07 | 09-JUN-02:55 | 32.01 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.90 | 30-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.15 | 13-AUG-14:10 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.55 | 04-SEP-17:00 | 36.81 | 25-SEP-04:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.06 | 09-OCT-15:00 | 63.81 | 20-OCT-04:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.11 | 19-NOV-13:52 | 117.81 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.69 | 10-DEC-11:53 | 181.44 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.25 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.66 | 293.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 40032.44 | 30-JAN-06:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39913.57 | 27-FEB-06:12 | 3176.32 | 2742.16 | 37051.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40668.90 | 28-MAR-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41520.08 | 25-APR-04:52 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41467.85 | 04-MAY-05:03 | 3811.58 | 1270.40 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40175.77 | 07-JUN-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37843.56 | 29-JUL-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35450.93 | 15-AUG-04:02 | 0.00 | 1058.67 | 28210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39560.42 | 30-SEP-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39941.19 | 28-OCT-04:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40169.63 | 25-NOV-05:03 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39412.99 | 27-DEC-06:12 | 2541.06 | 2193.73 | 29641.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 35450.93 | 0.00 | 846.94 | 20126.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41520.08 | 3811.58 | 2742.16 | 44462.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5290.98 | 31-JAN-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
February | 8067.65 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.57 | 0.00 |
March | 10946.48 | 27-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.64 | 0.00 |
April | 11986.16 | 28-APR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.43 | 0.00 |
May | 12416.52 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.98 | 0.00 |
June | 13118.63 | 12-JUN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.70 | 0.00 |
July | 14204.17 | 21-JUL-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 | 0.00 |
August | 14162.87 | 16-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.07 | 0.00 |
September | 13141.98 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.32 | 0.00 |
October | 11079.57 | 02-OCT-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.96 | 0.00 |
November | 9176.69 | 06-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 0.00 |
December | 6837.03 | 04-DEC-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5290.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14204.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.70 | 14.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2316.15 | 31-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 |
February | 4193.16 | 06-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.04 | 0.00 |
March | 5448.80 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.83 | 0.00 |
April | 5703.84 | 24-APR-12:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 0.00 |
May | 7711.68 | 30-MAY-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 0.00 |
June | 7367.92 | 19-JUN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 0.00 |
July | 7615.87 | 31-JUL-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 | 0.00 |
August | 7653.01 | 21-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 0.00 |
September | 7745.99 | 05-SEP-12:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 0.00 |
October | 7484.39 | 10-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 | 0.00 |
November | 5410.74 | 13-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 0.00 |
December | 3559.95 | 04-DEC-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2316.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7745.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 | 14.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3773.54 | 02-JAN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 |
February | 5002.17 | 06-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.51 | 0.00 |
March | 7570.15 | 27-MAR-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 | 0.00 |
April | 7038.11 | 24-APR-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 | 0.00 |
May | 8691.37 | 08-MAY-12:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 0.00 |
June | 8343.64 | 26-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 | 0.00 |
July | 8973.25 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.32 | 0.00 |
August | 8614.97 | 14-AUG-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 | 0.00 |
September | 8536.31 | 05-SEP-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.78 | 0.00 |
October | 8368.63 | 10-OCT-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 | 0.00 |
November | 6196.17 | 13-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.14 |
December | 4821.61 | 04-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3773.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8973.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 | 14.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 27348.83 | 30-JAN-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31668.58 | 06-FEB-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32355.85 | 28-MAR-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33076.22 | 25-APR-04:52 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34672.28 | 15-MAY-05:14 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32118.79 | 07-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29598.18 | 03-JUL-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29087.53 | 15-AUG-06:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31837.41 | 29-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32785.01 | 31-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32525.59 | 13-NOV-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31516.76 | 11-DEC-06:12 | 2541.06 | 2193.73 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27348.83 | 0.00 | 1058.67 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34672.28 | 3811.58 | 4936.08 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 14733.60 | 30-JAN-14:50 | 6198.29 | 4936.01 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23583.61 | 06-FEB-06:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35584.44 | 27-MAR-05:12 | 3176.32 | 2742.16 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35547.13 | 17-APR-04:03 | 0.00 | 846.94 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36348.08 | 09-MAY-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36445.51 | 07-JUN-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34665.61 | 03-JUL-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33424.89 | 07-AUG-05:02 | 3176.32 | 1058.67 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36658.18 | 25-SEP-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36467.09 | 23-OCT-04:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36268.65 | 20-NOV-05:02 | 0.00 | 1058.67 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17492.56 | 11-DEC-07:03 | 3811.58 | 4936.08 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14733.60 | 0.00 | 846.94 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36658.18 | 6198.29 | 4936.08 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4133.25 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 0.00 |
February | 5825.74 | 06-FEB-15:00 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 0.00 |
March | 8488.16 | 02-MAR-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 | 0.00 |
April | 13188.31 | 30-APR-12:43 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 184.55 | 0.00 |
May | 14894.05 | 21-MAY-12:52 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.35 | 0.00 |
June | 14273.40 | 11-JUN-16:12 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 247.45 | 0.00 |
July | 15318.48 | 30-JUL-10:01 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 219.88 | 0.00 |
August | 14743.78 | 06-AUG-15:02 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 266.07 | 0.00 |
September | 14900.97 | 04-SEP-12:52 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 269.16 | 0.00 |
October | 13885.88 | 08-OCT-11:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 | 0.00 |
November | 7941.33 | 12-NOV-14:42 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 46.35 | 0.00 |
December | 4612.12 | 11-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4133.25 | 267.84 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.59 | 0.00 | |
Maximum of Months | 15318.48 | 2613.31 | 992.69 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.35 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3087.74 | 24-JAN-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
February | 5613.26 | 05-FEB-14:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 98.60 | 0.00 |
March | 8667.80 | 26-MAR-12:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 | 0.00 |
April | 11804.64 | 30-APR-12:43 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 121.80 | 0.00 |
May | 12143.48 | 21-MAY-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 175.34 | 0.00 |
June | 12099.39 | 11-JUN-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 124.65 | 0.00 |
July | 13499.92 | 30-JUL-10:01 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.17 | 0.00 |
August | 12536.97 | 20-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 | 0.00 |
September | 12119.13 | 04-SEP-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 130.08 | 0.00 |
October | 12024.85 | 08-OCT-10:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 0.00 |
November | 7952.26 | 12-NOV-14:02 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 0.00 |
December | 3539.43 | 04-DEC-11:00 | 827.22 | 314.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3087.74 | 169.56 | 69.83 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13499.92 | 827.22 | 314.23 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.34 | 0.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10331.67 | 22-JAN-14:13 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
February | 17193.04 | 05-FEB-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 114.42 | 0.00 |
March | 16843.54 | 26-MAR-12:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 0.00 |
April | 16795.87 | 30-APR-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 178.56 | 0.00 |
May | 16564.00 | 21-MAY-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.80 | 0.00 |
June | 13967.45 | 11-JUN-14:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 283.36 | 0.00 |
July | 17128.68 | 30-JUL-14:02 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 423.96 | 0.00 |
August | 16556.82 | 20-AUG-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 266.78 | 0.00 |
September | 17102.20 | 04-SEP-12:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 261.19 | 0.00 |
October | 17271.19 | 09-OCT-13:12 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 193.39 | 0.00 |
November | 17649.36 | 12-NOV-13:22 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 42.02 | 0.00 |
December | 17218.26 | 03-DEC-12:43 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 10.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10331.67 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17649.36 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.80 | 7.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3754.69 | 31-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
February | 8331.46 | 05-FEB-14:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 | 0.00 |
March | 8420.98 | 26-MAR-15:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 66.31 | 0.00 |
April | 11702.54 | 23-APR-14:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 71.37 | 0.00 |
May | 13718.89 | 21-MAY-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 177.60 | 0.00 |
June | 13617.82 | 11-JUN-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 161.58 | 0.00 |
July | 13918.11 | 02-JUL-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 160.83 | 0.00 |
August | 13755.11 | 06-AUG-15:42 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 150.94 | 0.00 |
September | 13399.58 | 03-SEP-16:32 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 187.85 | 0.00 |
October | 13526.32 | 09-OCT-15:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 173.79 | 0.00 |
November | 12615.74 | 12-NOV-14:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 0.00 |
December | 5083.02 | 03-DEC-14:43 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3754.69 | 169.55 | 69.82 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13918.11 | 805.38 | 314.21 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 187.85 | 5.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4213.17 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 0.00 |
February | 5311.44 | 06-FEB-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.73 | 0.00 |
March | 6125.65 | 27-MAR-13:40 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 | 0.00 |
April | 6405.98 | 28-APR-12:30 | 2544.47 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 0.00 |
May | 12479.12 | 21-MAY-16:01 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 154.21 | 0.00 |
June | 10748.11 | 16-JUN-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
July | 13300.89 | 23-JUL-15:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 94.44 | 0.00 |
August | 13089.55 | 20-AUG-13:22 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 151.61 | 0.00 |
September | 13331.17 | 04-SEP-11:22 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 89.87 | 0.00 |
October | 10727.84 | 04-OCT-04:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 | 0.00 |
November | 10103.30 | 06-NOV-07:03 | 1071.35 | 936.36 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
December | 7029.35 | 11-DEC-07:03 | 803.52 | 954.71 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4213.17 | 0.00 | 137.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13331.17 | 2613.31 | 992.69 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 154.21 | 4.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3849.50 | 30-JAN-07:03 | 678.26 | 862.48 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
February | 4207.30 | 06-FEB-07:03 | 508.69 | 507.31 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
March | 6026.95 | 26-MAR-10:53 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 0.00 |
April | 8528.48 | 23-APR-11:32 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 0.00 |
May | 11045.59 | 21-MAY-10:02 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 93.67 | 0.00 |
June | 9897.38 | 11-JUN-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 67.24 | 0.00 |
July | 11973.50 | 30-JUL-10:01 | 296.74 | 122.20 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 0.00 |
August | 11313.41 | 20-AUG-09:22 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 63.69 | 0.00 |
September | 11752.01 | 04-SEP-11:22 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 | 0.00 |
October | 11019.66 | 09-OCT-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 |
November | 9240.10 | 05-NOV-11:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 0.00 |
December | 5690.72 | 04-DEC-07:02 | 847.82 | 573.96 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3849.50 | 127.17 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11973.50 | 847.82 | 862.48 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.67 | 3.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11100.03 | 23-JAN-13:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4203.12 | 0.00 |
February | 12900.50 | 07-FEB-13:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7288.94 | 0.00 |
March | 15125.09 | 27-MAR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11991.83 | 0.00 |
April | 16436.45 | 28-APR-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15772.94 | 0.00 |
May | 16046.54 | 09-MAY-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 15095.12 | 0.00 |
June | 16925.21 | 12-JUN-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 16392.28 | 0.00 |
July | 17791.23 | 21-JUL-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18531.05 | 0.00 |
August | 18105.60 | 16-AUG-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 18414.37 | 0.00 |
September | 16804.76 | 05-SEP-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 14363.76 | 0.00 |
October | 15624.04 | 04-OCT-12:00 | 687.71 | 496.34 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 12260.59 | 0.00 |
November | 15536.61 | 05-NOV-11:52 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 27.70 | 0.00 |
December | 15171.25 | 25-DEC-13:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11100.03 | 267.84 | 110.30 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18105.60 | 687.71 | 496.34 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 18531.05 | 2.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3964.20 | 30-JAN-07:03 | 678.21 | 870.42 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 |
February | 5562.45 | 05-FEB-16:23 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 41.75 | 0.00 |
March | 7299.54 | 26-MAR-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 0.00 |
April | 8147.52 | 02-APR-17:12 | 0.00 | 69.82 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 0.00 |
May | 11738.32 | 21-MAY-16:01 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 0.00 |
June | 10771.81 | 18-JUN-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 76.38 | 0.00 |
July | 12445.83 | 23-JUL-15:52 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 | 0.00 |
August | 11891.00 | 06-AUG-16:22 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 79.61 | 0.00 |
September | 12282.16 | 04-SEP-18:02 | 0.00 | 114.38 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 75.92 | 0.00 |
October | 11568.13 | 22-OCT-15:32 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 0.00 |
November | 11641.85 | 05-NOV-15:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 45.45 | 0.00 |
December | 5515.51 | 25-DEC-15:13 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3964.20 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12445.83 | 678.21 | 870.42 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 2.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4059.15 | 23-JAN-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 0.00 |
February | 5480.84 | 06-FEB-14:50 | 1306.65 | 496.34 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 0.00 |
March | 7065.40 | 02-MAR-06:03 | 535.68 | 178.54 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | 0.00 |
April | 10741.30 | 30-APR-16:32 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 82.49 | 0.00 |
May | 12865.16 | 28-MAY-16:32 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 116.90 | 0.00 |
June | 11441.78 | 11-JUN-16:12 | 334.80 | 137.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 207.46 | 0.00 |
July | 12802.77 | 02-JUL-13:23 | 267.84 | 110.30 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 212.07 | 0.00 |
August | 13034.51 | 06-AUG-10:52 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 146.20 | 0.00 |
September | 13677.75 | 04-SEP-15:11 | 468.72 | 193.02 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 212.02 | 0.00 |
October | 11809.79 | 29-OCT-14:12 | 401.76 | 165.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 0.00 |
November | 8488.61 | 20-NOV-05:02 | 0.00 | 223.18 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 0.00 |
December | 4549.02 | 11-DEC-14:10 | 2613.31 | 992.69 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4059.15 | 0.00 | 110.30 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 0.00 | |
Maximum of Months | 13677.75 | 2613.31 | 992.69 | 3348.91 | 0.00 | 0.00 | 0.00 | 0.00 | 212.07 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4430.49 | 24-JAN-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
February | 5494.33 | 07-FEB-13:03 | 2416.29 | 942.68 | 2725.72 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 | 0.00 |
March | 9413.83 | 27-MAR-12:01 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 0.00 |
April | 10314.07 | 23-APR-11:23 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 58.65 | 0.00 |
May | 11766.16 | 07-MAY-09:52 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 40.81 | 0.00 |
June | 11240.12 | 11-JUN-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 104.69 | 0.00 |
July | 11497.90 | 30-JUL-10:12 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 132.26 | 0.00 |
August | 11909.75 | 06-AUG-10:52 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 91.72 | 0.00 |
September | 11991.07 | 04-SEP-10:32 | 254.35 | 104.74 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 | 0.00 |
October | 11271.85 | 09-OCT-09:13 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 0.00 |
November | 8652.91 | 05-NOV-11:42 | 211.95 | 87.28 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 33.07 | 0.00 |
December | 4863.35 | 04-DEC-11:05 | 1610.86 | 628.45 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4430.49 | 169.56 | 69.83 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11991.07 | 6443.43 | 2513.82 | 7268.59 | 0.00 | 0.00 | 0.00 | 0.00 | 132.26 | 0.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9930.02 | 22-JAN-14:33 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
February | 11527.98 | 05-FEB-11:43 | 200.88 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | 0.00 |
March | 14286.91 | 26-MAR-15:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 81.24 | 0.00 |
April | 13614.66 | 30-APR-11:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 0.00 |
May | 14397.45 | 07-MAY-15:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 165.89 | 0.00 |
June | 12718.59 | 29-JUN-04:02 | 0.00 | 223.18 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.04 | 0.00 |
July | 14336.55 | 02-JUL-13:23 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 | 0.00 |
August | 14781.34 | 06-AUG-10:52 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 145.80 | 0.00 |
September | 15957.81 | 04-SEP-15:11 | 468.72 | 193.02 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 204.51 | 0.00 |
October | 15639.43 | 29-OCT-13:32 | 401.76 | 165.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 | 0.00 |
November | 15699.30 | 05-NOV-13:02 | 334.80 | 137.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 82.46 | 0.00 |
December | 15187.85 | 03-DEC-12:53 | 267.84 | 110.30 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9930.02 | 0.00 | 82.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15957.81 | 468.72 | 223.18 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 214.47 | 5.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3673.03 | 31-JAN-16:20 | 805.38 | 314.21 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 |
February | 6496.44 | 05-FEB-16:23 | 127.16 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 0.00 |
March | 11950.05 | 26-MAR-15:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 0.00 |
April | 12304.85 | 23-APR-16:42 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 0.00 |
May | 12697.48 | 28-MAY-16:32 | 254.33 | 104.73 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 70.40 | 0.00 |
June | 12102.43 | 18-JUN-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 118.37 | 0.00 |
July | 12135.83 | 02-JUL-16:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 131.29 | 0.00 |
August | 12229.41 | 13-AUG-17:32 | 0.00 | 104.73 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 117.66 | 0.00 |
September | 13632.28 | 04-SEP-15:51 | 296.72 | 122.19 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 128.94 | 0.00 |
October | 12205.88 | 15-OCT-16:12 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 65.74 | 0.00 |
November | 12032.69 | 05-NOV-15:02 | 211.94 | 87.28 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 72.86 | 0.00 |
December | 4562.88 | 03-DEC-14:53 | 169.55 | 69.82 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 3.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3673.03 | 0.00 | 52.37 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13632.28 | 805.38 | 314.21 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 131.29 | 4.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.120147E+12 | 106559.53 | 23-JAN-13:00 | 0.00 | 0.00 |
February | 0.114288E+12 | 129445.93 | 06-FEB-15:09 | 0.00 | 0.00 |
March | 0.139999E+12 | 151423.26 | 27-MAR-10:00 | 0.00 | 0.00 |
April | 0.144895E+12 | 158594.26 | 28-APR-12:09 | 0.00 | 0.00 |
May | 0.186810E+12 | 182278.44 | 30-MAY-14:00 | 0.00 | 0.00 |
June | 0.203617E+12 | 188616.23 | 12-JUN-10:00 | 0.00 | 0.00 |
July | 0.225778E+12 | 194483.98 | 31-JUL-14:09 | 0.00 | 0.00 |
August | 0.243720E+12 | 206191.73 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.200720E+12 | 186301.11 | 05-SEP-15:39 | 0.00 | 0.00 |
October | 0.177740E+12 | 161261.46 | 06-OCT-15:20 | 0.00 | 0.00 |
November | 0.147976E+12 | 150227.47 | 01-NOV-14:09 | 0.00 | 0.00 |
December | 0.126203E+12 | 121972.46 | 04-DEC-15:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.203189E+13 | 0.00 | 0.00 | ||
Minimum of Months | 0.114288E+12 | 106559.53 | 0.00 | 0.00 | |
Maximum of Months | 0.243720E+12 | 206191.73 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.195952E+11 | 0.507020E+10 | 0.605851E+11 | 0.225721E+10 | 0.666402E+10 | 12379742.02 | 0.181591E+09 | 0.222345E+11 | 0.00 | 0.00 | 0.00 | 0.354661E+10 | 0.00 |
February | 0.176411E+11 | 0.427755E+10 | 0.548702E+11 | 0.204811E+10 | 0.709044E+10 | 11196021.66 | 0.115001E+09 | 0.250948E+11 | 0.00 | 0.00 | 0.00 | 0.314006E+10 | 0.00 |
March | 0.208747E+11 | 0.435515E+10 | 0.627783E+11 | 0.235487E+10 | 0.998319E+10 | 12675672.10 | 41119805.49 | 0.361352E+11 | 0.00 | 0.00 | 0.00 | 0.346325E+10 | 0.00 |
April | 0.185132E+11 | 0.382924E+10 | 0.586172E+11 | 0.219185E+10 | 0.117942E+11 | 11960507.72 | 484374.41 | 0.470907E+11 | 0.00 | 0.00 | 0.00 | 0.284652E+10 | 0.00 |
May | 0.198621E+11 | 0.363967E+10 | 0.616817E+11 | 0.230575E+10 | 0.185410E+11 | 12527707.06 | 0.00 | 0.780190E+11 | 0.00 | 0.00 | 0.00 | 0.274831E+10 | 0.00 |
June | 0.197214E+11 | 0.340476E+10 | 0.604966E+11 | 0.226798E+10 | 0.201432E+11 | 12231776.97 | 0.00 | 0.950631E+11 | 0.00 | 0.00 | 0.00 | 0.250730E+10 | 0.00 |
July | 0.185123E+11 | 0.358307E+10 | 0.597911E+11 | 0.222881E+10 | 0.211699E+11 | 12256437.81 | 0.00 | 0.118161E+12 | 0.00 | 0.00 | 0.00 | 0.231940E+10 | 0.00 |
August | 0.206676E+11 | 0.383930E+10 | 0.627783E+11 | 0.235472E+10 | 0.229561E+11 | 12675672.10 | 0.00 | 0.128469E+12 | 0.00 | 0.00 | 0.00 | 0.264273E+10 | 0.00 |
September | 0.185395E+11 | 0.401557E+10 | 0.585950E+11 | 0.219061E+10 | 0.185626E+11 | 11960507.72 | 0.00 | 0.961882E+11 | 0.00 | 0.00 | 0.00 | 0.261630E+10 | 0.00 |
October | 0.193733E+11 | 0.454821E+10 | 0.605962E+11 | 0.225779E+10 | 0.159897E+11 | 12379742.02 | 0.00 | 0.719655E+11 | 0.00 | 0.00 | 0.00 | 0.299629E+10 | 0.00 |
November | 0.193163E+11 | 0.480143E+10 | 0.591197E+11 | 0.219986E+10 | 0.120881E+11 | 12059151.09 | 0.00 | 0.472146E+11 | 0.00 | 0.00 | 0.00 | 0.322367E+10 | 0.00 |
December | 0.190145E+11 | 0.518961E+10 | 0.597800E+11 | 0.222847E+10 | 0.793080E+10 | 12256437.81 | 35881976.16 | 0.286156E+11 | 0.00 | 0.00 | 0.00 | 0.339586E+10 | 0.00 |
Annual Sum or Average | 0.231631E+12 | 0.505538E+11 | 0.719689E+12 | 0.268860E+11 | 0.172913E+12 | 0.146559E+09 | 0.374079E+09 | 0.794251E+12 | 0.00 | 0.00 | 0.00 | 0.354463E+11 | 0.00 |
Minimum of Months | 0.176411E+11 | 0.340476E+10 | 0.548702E+11 | 0.204811E+10 | 0.666402E+10 | 11196021.66 | 0.00 | 0.222345E+11 | 0.00 | 0.00 | 0.00 | 0.231940E+10 | 0.00 |
Maximum of Months | 0.208747E+11 | 0.518961E+10 | 0.627783E+11 | 0.235487E+10 | 0.229561E+11 | 12675672.10 | 0.181591E+09 | 0.128469E+12 | 0.00 | 0.00 | 0.00 | 0.354661E+10 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21884.97 | 23-JAN-16:00 | 5686.19 | 01-JAN-06:10 | 41699.26 | 02-JAN-08:09 | 1410.29 | 04-JAN-08:20 | 11132.06 | 23-JAN-13:30 | 6.85 | 01-JAN-06:10 | 4481.19 | 02-JAN-07:49 |
February | 22491.26 | 09-FEB-16:00 | 5686.19 | 01-FEB-06:10 | 41699.26 | 01-FEB-08:09 | 1410.29 | 01-FEB-08:20 | 16889.63 | 06-FEB-15:30 | 6.85 | 01-FEB-06:10 | 4481.19 | 01-FEB-07:40 |
March | 24001.33 | 15-MAR-07:10 | 5686.19 | 01-MAR-06:10 | 41699.26 | 01-MAR-08:09 | 1410.29 | 01-MAR-13:09 | 21187.24 | 27-MAR-15:30 | 6.85 | 27-MAR-12:09 | 4481.19 | 07-MAR-07:19 |
April | 22429.67 | 18-APR-07:10 | 5686.19 | 01-APR-05:10 | 41699.26 | 03-APR-07:10 | 1410.29 | 26-APR-11:09 | 23201.91 | 24-APR-15:20 | 6.85 | 28-APR-11:09 | 332.02 | 05-APR-06:49 |
May | 19915.40 | 23-MAY-07:10 | 5686.19 | 01-MAY-05:10 | 41699.26 | 01-MAY-07:10 | 1410.29 | 05-MAY-11:09 | 26240.84 | 30-MAY-15:09 | 6.85 | 05-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 19948.33 | 08-JUN-07:10 | 5686.19 | 01-JUN-05:10 | 41699.26 | 01-JUN-07:10 | 1410.29 | 01-JUN-11:09 | 26019.35 | 12-JUN-14:20 | 6.85 | 01-JUN-11:09 | 0.00 | 01-JUN-00:10 |
July | 21125.16 | 20-JUL-07:10 | 5686.19 | 01-JUL-05:10 | 41699.26 | 03-JUL-07:10 | 1410.29 | 03-JUL-12:09 | 26349.75 | 31-JUL-14:39 | 6.85 | 02-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 20325.36 | 29-AUG-07:10 | 5686.19 | 01-AUG-05:10 | 41699.26 | 01-AUG-07:10 | 1410.29 | 03-AUG-16:10 | 27758.08 | 10-AUG-15:00 | 6.85 | 02-AUG-17:10 | 0.00 | 01-AUG-00:10 |
September | 20458.64 | 06-SEP-07:10 | 5686.19 | 01-SEP-05:10 | 41699.26 | 01-SEP-07:10 | 1410.29 | 05-SEP-11:09 | 27260.21 | 05-SEP-15:39 | 6.85 | 03-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 20823.85 | 31-OCT-07:10 | 5686.19 | 01-OCT-05:10 | 41699.26 | 02-OCT-07:10 | 1410.29 | 02-OCT-11:09 | 22208.59 | 10-OCT-15:30 | 6.85 | 04-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 22832.36 | 29-NOV-16:00 | 5686.19 | 01-NOV-05:10 | 41699.26 | 01-NOV-07:10 | 1410.29 | 01-NOV-16:10 | 18495.71 | 13-NOV-15:20 | 6.85 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 23331.01 | 15-DEC-16:00 | 5686.19 | 01-DEC-06:10 | 41699.26 | 01-DEC-08:09 | 1410.29 | 26-DEC-08:09 | 14850.77 | 04-DEC-15:30 | 6.85 | 01-DEC-06:10 | 3991.20 | 18-DEC-07:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 19915.40 | 5686.19 | 41699.26 | 1410.29 | 11132.06 | 6.85 | 0.00 | |||||||
Maximum of Months | 24001.33 | 5686.19 | 41699.26 | 1410.29 | 27758.08 | 6.85 | 4481.19 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 30936.20 | 23-JAN-13:00 | 0.00 | 0.00 | 0.00 | 4616.87 | 12-JAN-12:00 | 0.00 |
February | 47207.30 | 06-FEB-15:09 | 0.00 | 0.00 | 0.00 | 4608.10 | 01-FEB-12:00 | 0.00 |
March | 65795.97 | 27-MAR-10:00 | 0.00 | 0.00 | 0.00 | 4569.12 | 01-MAR-12:20 | 0.00 |
April | 77180.81 | 28-APR-12:09 | 0.00 | 0.00 | 0.00 | 3897.85 | 03-APR-11:20 | 0.00 |
May | 91426.28 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 3561.38 | 01-MAY-11:00 | 0.00 |
June | 100733.77 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 | 3204.29 | 01-JUN-11:20 | 0.00 |
July | 105827.73 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 3183.52 | 31-JUL-11:50 | 0.00 |
August | 113657.46 | 10-AUG-15:30 | 0.00 | 0.00 | 0.00 | 3367.19 | 29-AUG-11:39 | 0.00 |
September | 97226.66 | 07-SEP-12:00 | 0.00 | 0.00 | 0.00 | 3826.82 | 28-SEP-11:39 | 0.00 |
October | 76294.99 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 | 4214.21 | 31-OCT-11:50 | 0.00 |
November | 69147.17 | 01-NOV-14:09 | 0.00 | 0.00 | 0.00 | 4577.72 | 30-NOV-12:39 | 0.00 |
December | 43825.84 | 04-DEC-13:09 | 0.00 | 0.00 | 0.00 | 4612.39 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 30936.20 | 0.00 | 0.00 | 0.00 | 3183.52 | 0.00 | ||
Maximum of Months | 113657.46 | 0.00 | 0.00 | 0.00 | 4616.87 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 106559.53 | 23-JAN-13:00 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 11031.93 | 6.85 | 0.00 | 30936.20 | 0.00 |
February | 129445.93 | 06-FEB-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 16635.83 | 6.85 | 0.00 | 47207.30 | 0.00 |
March | 151423.26 | 27-MAR-10:00 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 19357.24 | 6.85 | 0.00 | 65795.97 | 0.00 |
April | 158594.26 | 28-APR-12:09 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 17865.98 | 6.85 | 0.00 | 77180.81 | 0.00 |
May | 182278.44 | 30-MAY-14:00 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 26161.64 | 6.85 | 0.00 | 91426.28 | 0.00 |
June | 188616.23 | 12-JUN-10:00 | 19671.42 | 41666.76 | 0.00 | 1410.29 | 24970.30 | 6.85 | 0.00 | 98329.58 | 0.00 |
July | 194483.98 | 31-JUL-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 25815.45 | 6.85 | 0.00 | 104261.83 | 0.00 |
August | 206191.73 | 10-AUG-15:00 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 27758.08 | 6.85 | 0.00 | 113130.73 | 0.00 |
September | 186301.11 | 05-SEP-15:39 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 27260.21 | 6.85 | 0.00 | 93721.23 | 0.00 |
October | 161261.46 | 06-OCT-15:20 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 19329.76 | 6.85 | 0.00 | 76294.99 | 0.00 |
November | 150227.47 | 01-NOV-14:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 15789.13 | 6.85 | 0.00 | 69147.17 | 0.00 |
December | 121972.46 | 04-DEC-15:09 | 19671.42 | 41659.26 | 0.00 | 1410.29 | 14629.13 | 6.85 | 0.00 | 42031.85 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 106559.53 | 19671.42 | 38932.26 | 0.00 | 1410.29 | 11031.93 | 6.85 | 0.00 | 30936.20 | 0.00 | |
Maximum of Months | 206191.73 | 19671.42 | 41670.51 | 0.00 | 1410.29 | 27758.08 | 6.85 | 0.00 | 113130.73 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.29 | 0.00 | 26.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.85 | 0.00 | 26.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.25 | 0.00 | 26.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.24 | 0.00 | 26.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 26.70 | 0.00 | 26.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.21 | 0.00 | 26.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.35 | 0.00 | 26.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.35 | 0.00 | 26.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.35 | 0.00 | 26.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.32 | 0.83 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.44 | 3.50 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.66 | 9.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.64 | 8.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.63 | 13.50 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.58 | 8.83 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.65 | 9.17 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.53 | 7.83 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 97.50 | 27.61 | 62.17 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.66 | 13.50 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.51 | 2.17 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.63 | 9.83 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.92 | 12.00 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.84 | 10.33 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.82 | 15.67 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.75 | 10.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.86 | 12.00 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.73 | 13.00 | 27.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.39 | 3.67 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 130.33 | 27.79 | 89.17 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.92 | 15.67 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.67 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.58 | 3.00 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.60 | 3.33 | 27.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.60 | 6.83 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.68 | 9.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.61 | 8.00 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.65 | 12.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.68 | 9.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.86 | 10.17 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 28.00 | 11.50 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.80 | 9.67 | 27.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.58 | 4.17 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 127.83 | 27.72 | 89.50 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.67 | 27.36 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 28.00 | 12.83 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 1.00 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.66 | 2.50 | 27.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.77 | 6.17 | 27.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.91 | 10.17 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.85 | 8.67 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.79 | 14.00 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.74 | 10.00 | 27.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.86 | 10.17 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.85 | 9.17 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.62 | 5.17 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 136.17 | 27.81 | 77.00 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.91 | 14.00 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.36 | 5.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.36 | 6.17 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.42 | 11.67 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.31 | 7.83 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.40 | 8.67 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.34 | 5.17 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 64.50 | 27.37 | 45.00 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.42 | 11.67 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.32 | 1.00 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.45 | 5.17 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.63 | 11.50 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.64 | 9.33 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.62 | 14.67 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.45 | 10.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.60 | 12.17 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.56 | 13.67 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.37 | 4.17 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 117.83 | 27.56 | 81.67 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.64 | 14.67 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 20.16 | 2.33 | 20.16 | 2.50 | 22.66 | 2.50 | 23.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.47 | 3.50 | 26.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.90 | 8.17 | 25.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25.79 | 16.33 | 25.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 26.07 | 49.67 | 26.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 26.29 | 54.67 | 26.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 26.62 | 63.00 | 26.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 26.53 | 76.17 | 26.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 | 26.48 | 61.67 | 26.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 26.16 | 59.50 | 26.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 26.17 | 28.33 | 26.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.44 | 6.00 | 27.44 |
Annual Sum or Average | 2.33 | 20.16 | 2.33 | 20.16 | 460.17 | 26.30 | 429.50 | 26.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.66 | 2.50 | 23.86 |
Maximum of Months | 2.33 | 20.16 | 2.33 | 20.16 | 84.67 | 27.44 | 76.17 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 0.83 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.56 | 3.83 | 27.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.67 | 7.83 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.62 | 7.33 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.56 | 13.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.44 | 10.33 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.60 | 10.50 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.63 | 9.00 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.52 | 5.00 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 126.83 | 27.56 | 68.83 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.67 | 13.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.47 | 8.33 | 27.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.48 | 7.33 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.48 | 12.50 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.48 | 7.83 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.50 | 8.33 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.41 | 5.17 | 27.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.17 | 27.48 | 50.33 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.50 | 12.50 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.40 | 2.00 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.51 | 8.83 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.76 | 12.17 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.74 | 9.67 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.71 | 15.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.67 | 9.83 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.76 | 11.67 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.61 | 12.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 1.83 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 108.17 | 27.68 | 84.17 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.76 | 15.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 1.50 | 27.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.67 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 2.83 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.45 | 5.67 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.49 | 8.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.46 | 7.00 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.50 | 11.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.56 | 8.17 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.76 | 9.33 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.86 | 11.33 | 27.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.72 | 9.67 | 27.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.55 | 4.33 | 27.55 |
Annual Sum or Average | 0.00 | 0.00 | 103.50 | 27.60 | 82.50 | 27.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 1.50 | 27.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.86 | 11.67 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.46 | 0.67 | 27.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.56 | 1.83 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.65 | 5.17 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.78 | 8.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.76 | 7.67 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.68 | 12.50 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.63 | 9.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.75 | 9.33 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.76 | 7.83 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.52 | 4.50 | 27.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 110.33 | 27.70 | 67.50 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.78 | 12.50 | 27.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 377.67 | 24.68 | 0.00 | 24.68 |
February | 0.00 | 0.00 | 398.33 | 24.60 | 0.00 | 24.60 |
March | 0.00 | 0.00 | 434.67 | 24.54 | 0.00 | 24.54 |
April | 0.00 | 0.00 | 468.33 | 24.50 | 0.00 | 24.50 |
May | 0.00 | 0.00 | 502.00 | 24.49 | 0.00 | 24.49 |
June | 0.00 | 0.00 | 496.00 | 24.44 | 0.00 | 24.44 |
July | 0.00 | 0.00 | 497.00 | 24.47 | 0.00 | 24.47 |
August | 0.00 | 0.00 | 514.00 | 24.37 | 0.00 | 24.37 |
September | 0.00 | 0.00 | 485.00 | 24.48 | 0.00 | 24.48 |
October | 0.00 | 0.00 | 493.67 | 24.54 | 0.00 | 24.54 |
November | 0.00 | 0.00 | 484.17 | 24.55 | 0.00 | 24.55 |
December | 0.00 | 0.00 | 451.67 | 24.57 | 0.00 | 24.57 |
Annual Sum or Average | 0.00 | 5602.50 | 24.51 | 0.00 | 24.51 | |
Minimum of Months | 0.00 | 0.00 | 377.67 | 24.37 | 0.00 | 24.37 |
Maximum of Months | 0.00 | 0.00 | 514.00 | 24.68 | 0.00 | 24.68 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.83 | 23.68 | 200.00 | 24.25 | 0.00 | 24.25 |
February | 7.50 | 23.72 | 277.17 | 24.38 | 0.00 | 24.38 |
March | 1.67 | 23.76 | 343.17 | 24.38 | 0.00 | 24.38 |
April | 0.00 | 0.00 | 415.83 | 24.37 | 0.00 | 24.37 |
May | 0.00 | 0.00 | 491.33 | 24.38 | 0.00 | 24.38 |
June | 0.00 | 0.00 | 496.00 | 24.34 | 0.00 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 514.00 | 24.30 | 0.00 | 24.30 |
September | 0.00 | 0.00 | 485.00 | 24.38 | 0.00 | 24.38 |
October | 0.67 | 27.15 | 484.33 | 24.43 | 0.67 | 24.43 |
November | 0.00 | 0.00 | 463.00 | 24.37 | 0.00 | 24.37 |
December | 17.67 | 23.69 | 313.00 | 24.33 | 0.00 | 24.33 |
Annual Sum or Average | 80.33 | 23.72 | 4979.83 | 24.36 | 0.67 | 24.36 |
Minimum of Months | 0.00 | 0.00 | 200.00 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 52.83 | 27.15 | 514.00 | 24.43 | 0.67 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 196.17 | 23.48 | 107.50 | 23.71 | 0.00 | 23.71 |
February | 90.67 | 23.50 | 200.83 | 24.03 | 0.00 | 24.03 |
March | 46.17 | 23.59 | 288.00 | 24.21 | 0.00 | 24.21 |
April | 2.00 | 23.57 | 395.67 | 24.38 | 0.00 | 24.38 |
May | 0.50 | 26.68 | 488.83 | 24.43 | 0.50 | 24.44 |
June | 0.00 | 0.00 | 496.00 | 24.38 | 0.00 | 24.38 |
July | 4.83 | 26.66 | 496.83 | 24.47 | 4.83 | 24.49 |
August | 1.17 | 26.70 | 514.00 | 24.36 | 1.17 | 24.36 |
September | 3.83 | 26.59 | 485.00 | 24.45 | 3.83 | 24.46 |
October | 0.00 | 0.00 | 480.50 | 24.44 | 0.00 | 24.44 |
November | 2.33 | 23.63 | 418.17 | 24.34 | 0.00 | 24.34 |
December | 103.67 | 23.49 | 222.33 | 24.00 | 0.00 | 24.00 |
Annual Sum or Average | 451.33 | 23.57 | 4593.67 | 24.31 | 10.33 | 24.31 |
Minimum of Months | 0.00 | 0.00 | 107.50 | 23.71 | 0.00 | 23.71 |
Maximum of Months | 196.17 | 26.70 | 514.00 | 24.47 | 4.83 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 277.83 | 22.97 | 95.83 | 23.27 | 0.00 | 23.27 |
February | 156.67 | 23.08 | 185.00 | 23.71 | 0.00 | 23.71 |
March | 99.33 | 23.28 | 287.83 | 24.04 | 0.67 | 24.04 |
April | 39.00 | 24.64 | 402.50 | 24.49 | 16.00 | 24.56 |
May | 39.83 | 26.86 | 503.33 | 24.75 | 39.83 | 24.90 |
June | 52.83 | 26.70 | 496.00 | 24.78 | 52.83 | 24.95 |
July | 72.33 | 26.90 | 497.00 | 24.98 | 72.33 | 25.20 |
August | 52.50 | 26.83 | 514.00 | 24.78 | 52.50 | 24.95 |
September | 59.33 | 26.65 | 485.00 | 24.83 | 59.33 | 25.01 |
October | 49.00 | 26.51 | 486.83 | 24.75 | 47.83 | 24.90 |
November | 26.83 | 23.60 | 391.50 | 24.34 | 2.00 | 24.35 |
December | 183.33 | 23.12 | 200.83 | 23.68 | 0.00 | 23.68 |
Annual Sum or Average | 1108.83 | 24.22 | 4545.67 | 24.45 | 343.33 | 24.59 |
Minimum of Months | 26.83 | 22.97 | 95.83 | 23.27 | 0.00 | 23.27 |
Maximum of Months | 277.83 | 26.90 | 514.00 | 24.98 | 72.33 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 200.33 | 23.06 | 158.17 | 23.62 | 0.00 | 23.62 |
February | 112.50 | 23.15 | 231.50 | 23.97 | 0.50 | 23.98 |
March | 75.50 | 23.47 | 336.33 | 24.20 | 4.33 | 24.23 |
April | 61.00 | 25.93 | 433.67 | 24.70 | 46.00 | 24.88 |
May | 53.67 | 26.97 | 507.67 | 24.85 | 53.67 | 25.03 |
June | 60.17 | 26.83 | 496.00 | 24.84 | 60.17 | 25.03 |
July | 80.50 | 27.01 | 497.00 | 25.05 | 80.50 | 25.29 |
August | 61.50 | 26.94 | 514.00 | 24.84 | 61.50 | 25.04 |
September | 67.00 | 26.83 | 485.00 | 24.92 | 67.00 | 25.12 |
October | 60.67 | 26.82 | 495.83 | 24.87 | 60.67 | 25.06 |
November | 24.17 | 25.08 | 428.50 | 24.53 | 12.00 | 24.59 |
December | 124.33 | 23.15 | 262.33 | 23.93 | 0.00 | 23.93 |
Annual Sum or Average | 981.33 | 24.84 | 4846.00 | 24.60 | 446.33 | 24.77 |
Minimum of Months | 24.17 | 23.06 | 158.17 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 200.33 | 27.01 | 514.00 | 25.05 | 80.50 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 183.17 | 23.20 | 227.67 | 23.94 | 5.17 | 23.98 |
February | 109.50 | 23.40 | 258.83 | 24.13 | 8.83 | 24.19 |
March | 87.67 | 23.62 | 327.67 | 24.22 | 8.17 | 24.28 |
April | 53.67 | 25.30 | 412.33 | 24.59 | 31.33 | 24.72 |
May | 39.17 | 26.86 | 501.00 | 24.75 | 39.17 | 24.89 |
June | 49.17 | 26.66 | 496.00 | 24.75 | 49.17 | 24.91 |
July | 69.67 | 26.89 | 497.00 | 24.97 | 69.67 | 25.18 |
August | 53.83 | 26.86 | 514.00 | 24.79 | 53.83 | 24.97 |
September | 65.00 | 26.77 | 485.00 | 24.89 | 65.00 | 25.09 |
October | 61.83 | 26.86 | 495.33 | 24.89 | 61.83 | 25.09 |
November | 51.83 | 26.06 | 432.33 | 24.71 | 39.00 | 24.87 |
December | 121.83 | 23.64 | 292.17 | 24.26 | 15.67 | 24.35 |
Annual Sum or Average | 946.33 | 24.89 | 4939.33 | 24.62 | 446.83 | 24.77 |
Minimum of Months | 39.17 | 23.20 | 227.67 | 23.94 | 5.17 | 23.98 |
Maximum of Months | 183.17 | 26.89 | 514.00 | 24.97 | 69.67 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 242.33 | 22.99 | 156.83 | 23.53 | 0.33 | 23.53 |
February | 132.83 | 23.13 | 223.83 | 23.89 | 2.50 | 23.91 |
March | 93.17 | 23.55 | 317.67 | 24.18 | 7.33 | 24.23 |
April | 52.00 | 25.38 | 412.83 | 24.62 | 31.67 | 24.75 |
May | 48.00 | 26.95 | 502.00 | 24.82 | 48.00 | 24.99 |
June | 64.17 | 26.84 | 496.00 | 24.86 | 64.17 | 25.06 |
July | 80.83 | 26.97 | 497.00 | 25.04 | 80.83 | 25.28 |
August | 67.50 | 26.93 | 514.00 | 24.87 | 67.50 | 25.08 |
September | 72.83 | 26.76 | 485.00 | 24.93 | 72.83 | 25.14 |
October | 56.67 | 26.69 | 489.83 | 24.83 | 56.00 | 25.01 |
November | 40.83 | 25.06 | 410.17 | 24.52 | 19.83 | 24.61 |
December | 154.00 | 23.10 | 236.83 | 23.86 | 0.67 | 23.86 |
Annual Sum or Average | 1105.17 | 24.62 | 4742.00 | 24.57 | 451.67 | 24.73 |
Minimum of Months | 40.83 | 22.99 | 156.83 | 23.53 | 0.33 | 23.53 |
Maximum of Months | 242.33 | 26.97 | 514.00 | 25.04 | 80.83 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 113.83 | 23.55 | 175.33 | 23.95 | 0.00 | 23.95 |
February | 60.00 | 23.46 | 251.50 | 24.12 | 0.00 | 24.12 |
March | 48.00 | 23.53 | 323.83 | 24.19 | 0.00 | 24.19 |
April | 5.00 | 23.96 | 424.83 | 24.40 | 0.67 | 24.40 |
May | 20.50 | 26.87 | 506.83 | 24.64 | 20.50 | 24.72 |
June | 33.67 | 26.71 | 496.00 | 24.69 | 33.67 | 24.81 |
July | 56.17 | 26.84 | 497.00 | 24.90 | 56.17 | 25.08 |
August | 36.83 | 26.85 | 514.00 | 24.70 | 36.83 | 24.84 |
September | 41.33 | 26.81 | 485.00 | 24.78 | 41.33 | 24.93 |
October | 30.83 | 26.72 | 499.50 | 24.73 | 30.83 | 24.84 |
November | 0.00 | 0.00 | 478.67 | 24.47 | 0.00 | 24.47 |
December | 28.00 | 23.58 | 345.00 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 474.17 | 25.05 | 4997.50 | 24.54 | 220.00 | 24.63 |
Minimum of Months | 0.00 | 0.00 | 175.33 | 23.95 | 0.00 | 23.95 |
Maximum of Months | 113.83 | 26.87 | 514.00 | 24.90 | 56.17 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.50 | 23.56 | 274.67 | 24.26 | 0.17 | 24.26 |
February | 29.67 | 23.49 | 313.83 | 24.32 | 0.00 | 24.32 |
March | 25.00 | 23.59 | 386.00 | 24.31 | 0.50 | 24.32 |
April | 17.67 | 26.64 | 460.83 | 24.59 | 16.00 | 24.66 |
May | 47.33 | 26.93 | 508.00 | 24.81 | 47.33 | 24.97 |
June | 45.17 | 26.89 | 496.00 | 24.78 | 45.17 | 24.94 |
July | 74.33 | 26.95 | 497.00 | 25.01 | 74.33 | 25.23 |
August | 55.00 | 26.97 | 514.00 | 24.81 | 55.00 | 25.00 |
September | 60.50 | 26.94 | 485.00 | 24.91 | 60.50 | 25.12 |
October | 57.00 | 26.91 | 502.00 | 24.90 | 57.00 | 25.09 |
November | 10.83 | 27.03 | 485.50 | 24.64 | 10.83 | 24.69 |
December | 13.50 | 23.63 | 392.67 | 24.38 | 0.00 | 24.38 |
Annual Sum or Average | 488.50 | 26.09 | 5315.50 | 24.69 | 366.83 | 24.82 |
Minimum of Months | 10.83 | 23.49 | 274.67 | 24.26 | 0.00 | 24.26 |
Maximum of Months | 74.33 | 27.03 | 514.00 | 25.01 | 74.33 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.00 | 22.70 | 317.83 | 24.24 | 4.17 | 24.27 |
February | 52.83 | 23.01 | 345.33 | 24.29 | 11.50 | 24.31 |
March | 57.33 | 23.00 | 381.33 | 24.23 | 14.83 | 24.23 |
April | 36.83 | 24.04 | 433.50 | 24.48 | 24.50 | 24.49 |
May | 58.50 | 25.63 | 504.50 | 24.81 | 58.50 | 24.89 |
June | 127.33 | 25.39 | 496.00 | 24.89 | 127.33 | 24.97 |
July | 176.33 | 25.65 | 497.00 | 25.13 | 176.33 | 25.24 |
August | 178.50 | 25.77 | 514.00 | 25.13 | 178.50 | 25.26 |
September | 157.17 | 25.86 | 485.00 | 25.14 | 157.17 | 25.28 |
October | 127.83 | 25.84 | 502.00 | 25.07 | 127.83 | 25.20 |
November | 76.00 | 25.65 | 485.33 | 24.81 | 74.33 | 24.92 |
December | 58.67 | 24.08 | 414.33 | 24.50 | 30.00 | 24.57 |
Annual Sum or Average | 1176.33 | 25.14 | 5376.17 | 24.79 | 985.00 | 24.90 |
Minimum of Months | 36.83 | 22.70 | 317.83 | 24.23 | 4.17 | 24.23 |
Maximum of Months | 178.50 | 25.86 | 514.00 | 25.14 | 178.50 | 25.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 70.83 | 23.54 | 259.33 | 24.21 | 0.00 | 24.21 |
February | 40.00 | 23.51 | 310.50 | 24.29 | 0.33 | 24.29 |
March | 26.00 | 23.75 | 376.67 | 24.34 | 1.67 | 24.35 |
April | 14.17 | 26.87 | 447.33 | 24.57 | 13.83 | 24.64 |
May | 35.67 | 26.95 | 508.00 | 24.76 | 35.67 | 24.90 |
June | 52.50 | 26.88 | 496.00 | 24.81 | 52.50 | 24.99 |
July | 76.67 | 26.94 | 497.00 | 25.01 | 76.67 | 25.24 |
August | 62.17 | 26.97 | 514.00 | 24.85 | 62.17 | 25.06 |
September | 67.00 | 26.93 | 485.00 | 24.94 | 67.00 | 25.16 |
October | 49.83 | 26.87 | 502.00 | 24.87 | 49.83 | 25.04 |
November | 15.00 | 26.97 | 485.83 | 24.63 | 15.00 | 24.70 |
December | 22.17 | 23.73 | 379.67 | 24.39 | 0.50 | 24.39 |
Annual Sum or Average | 532.00 | 25.93 | 5261.33 | 24.69 | 375.17 | 24.82 |
Minimum of Months | 14.17 | 23.51 | 259.33 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 76.67 | 26.97 | 514.00 | 25.01 | 76.67 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.50 | 23.32 | 130.50 | 23.65 | 0.00 | 23.65 |
February | 96.50 | 23.34 | 223.67 | 23.98 | 0.00 | 23.98 |
March | 57.17 | 23.49 | 319.67 | 24.18 | 0.00 | 24.18 |
April | 15.50 | 24.89 | 427.33 | 24.47 | 7.33 | 24.51 |
May | 36.00 | 26.80 | 506.50 | 24.72 | 36.00 | 24.85 |
June | 47.67 | 26.63 | 496.00 | 24.74 | 47.67 | 24.89 |
July | 68.67 | 26.81 | 497.00 | 24.95 | 68.67 | 25.15 |
August | 46.67 | 26.76 | 514.00 | 24.74 | 46.67 | 24.89 |
September | 55.83 | 26.64 | 485.00 | 24.81 | 55.83 | 24.98 |
October | 36.33 | 26.57 | 491.00 | 24.71 | 36.33 | 24.83 |
November | 4.00 | 23.67 | 440.50 | 24.38 | 0.50 | 24.38 |
December | 108.17 | 23.41 | 254.50 | 23.98 | 0.00 | 23.98 |
Annual Sum or Average | 771.00 | 24.66 | 4785.67 | 24.52 | 299.00 | 24.63 |
Minimum of Months | 4.00 | 23.32 | 130.50 | 23.65 | 0.00 | 23.65 |
Maximum of Months | 198.50 | 26.81 | 514.00 | 24.95 | 68.67 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 131.83 | 23.37 | 157.67 | 23.97 | 0.17 | 23.98 |
February | 60.17 | 23.34 | 217.50 | 24.24 | 0.17 | 24.24 |
March | 41.17 | 23.74 | 293.67 | 24.37 | 3.00 | 24.40 |
April | 39.67 | 26.49 | 382.83 | 24.80 | 35.50 | 24.96 |
May | 53.33 | 26.92 | 430.00 | 24.97 | 53.33 | 25.16 |
June | 54.17 | 26.80 | 418.00 | 24.94 | 54.17 | 25.13 |
July | 80.17 | 26.94 | 422.00 | 25.19 | 80.17 | 25.43 |
August | 56.50 | 26.90 | 433.00 | 24.95 | 56.50 | 25.15 |
September | 62.33 | 26.86 | 410.00 | 25.04 | 62.33 | 25.25 |
October | 59.50 | 26.83 | 424.67 | 25.00 | 59.50 | 25.20 |
November | 8.17 | 26.37 | 389.00 | 24.64 | 6.83 | 24.68 |
December | 66.50 | 23.39 | 250.67 | 24.21 | 0.00 | 24.21 |
Annual Sum or Average | 713.50 | 25.40 | 4229.00 | 24.77 | 411.67 | 24.93 |
Minimum of Months | 8.17 | 23.34 | 157.67 | 23.97 | 0.00 | 23.98 |
Maximum of Months | 131.83 | 26.94 | 433.00 | 25.19 | 80.17 | 25.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.50 | 23.49 | 261.67 | 24.24 | 3.67 | 24.26 |
February | 60.33 | 23.72 | 300.50 | 24.33 | 7.17 | 24.38 |
March | 47.83 | 23.91 | 363.17 | 24.34 | 5.50 | 24.37 |
April | 27.50 | 25.94 | 436.17 | 24.58 | 20.50 | 24.68 |
May | 35.00 | 26.82 | 506.00 | 24.71 | 35.00 | 24.84 |
June | 42.67 | 26.58 | 496.00 | 24.71 | 42.67 | 24.84 |
July | 63.83 | 26.79 | 497.00 | 24.92 | 63.83 | 25.12 |
August | 47.67 | 26.81 | 514.00 | 24.75 | 47.67 | 24.91 |
September | 60.33 | 26.78 | 485.00 | 24.87 | 60.33 | 25.06 |
October | 58.17 | 26.88 | 498.67 | 24.88 | 58.17 | 25.07 |
November | 38.33 | 26.80 | 465.83 | 24.73 | 36.67 | 24.88 |
December | 66.17 | 24.23 | 341.17 | 24.47 | 16.33 | 24.57 |
Annual Sum or Average | 656.33 | 25.46 | 5165.17 | 24.66 | 397.50 | 24.80 |
Minimum of Months | 27.50 | 23.49 | 261.67 | 24.24 | 3.67 | 24.26 |
Maximum of Months | 108.50 | 26.88 | 514.00 | 24.92 | 63.83 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.17 | 23.30 | 190.67 | 23.88 | 0.00 | 23.88 |
February | 74.00 | 23.36 | 268.17 | 24.14 | 1.50 | 24.15 |
March | 50.67 | 23.77 | 353.67 | 24.30 | 4.17 | 24.33 |
April | 32.67 | 26.09 | 437.83 | 24.63 | 25.83 | 24.74 |
May | 44.00 | 26.91 | 506.50 | 24.79 | 44.00 | 24.95 |
June | 59.67 | 26.77 | 496.00 | 24.82 | 59.67 | 25.01 |
July | 83.17 | 26.90 | 497.00 | 25.03 | 83.17 | 25.27 |
August | 63.00 | 26.89 | 514.00 | 24.84 | 63.00 | 25.04 |
September | 68.67 | 26.76 | 485.00 | 24.91 | 68.67 | 25.11 |
October | 50.17 | 26.73 | 493.17 | 24.82 | 50.17 | 24.98 |
November | 17.50 | 26.27 | 453.67 | 24.54 | 14.33 | 24.61 |
December | 81.17 | 23.34 | 288.00 | 24.14 | 0.33 | 24.14 |
Annual Sum or Average | 783.83 | 25.18 | 4983.67 | 24.63 | 414.83 | 24.78 |
Minimum of Months | 17.50 | 23.30 | 190.67 | 23.88 | 0.00 | 23.88 |
Maximum of Months | 159.17 | 26.91 | 514.00 | 25.03 | 83.17 | 25.27 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.51382 | 42.74033 | 0.52361 | 11.05115 |
February | 454.00000 | 24.52373 | 45.99033 | 0.55214 | 11.71827 |
March | 514.00000 | 24.46041 | 45.48670 | 0.54278 | 11.47457 |
April | 485.00000 | 24.48454 | 48.10471 | 0.57593 | 12.28568 |
May | 508.00000 | 24.48150 | 49.90032 | -0.2316 | 6.78807 |
June | 496.00000 | 24.43733 | 52.75949 | -0.2204 | 6.64934 |
July | 497.00000 | 24.46899 | 51.94794 | -0.2172 | 6.53560 |
August | 514.00000 | 24.36718 | 52.17843 | -0.2429 | 6.66767 |
September | 485.00000 | 24.47569 | 51.99154 | -0.2137 | 6.62798 |
October | 502.00000 | 24.52904 | 50.36132 | 0.61703 | 13.39654 |
November | 489.00000 | 24.54346 | 49.85624 | 0.60687 | 13.03064 |
December | 497.00000 | 24.52099 | 47.23785 | 0.56383 | 11.99096 |
Annual Sum or Average | 5943.00000 | 24.48320 | 49.05877 | 0.23476 | 9.82958 |
Minimum of Months | 454.00000 | 24.36718 | 42.74033 | -0.2429 | 6.53560 |
Maximum of Months | 514.00000 | 24.54346 | 52.75949 | 0.61703 | 13.39654 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17083 | 43.21000 | 0.41208 | 8.71248 |
February | 454.00000 | 24.24069 | 46.48120 | 0.45996 | 9.59219 |
March | 514.00000 | 24.25897 | 45.77805 | 0.47252 | 9.83166 |
April | 485.00000 | 24.31849 | 49.20837 | 0.52433 | 10.95187 |
May | 508.00000 | 24.36924 | 51.83929 | -0.2771 | 7.07469 |
June | 496.00000 | 24.33542 | 54.93652 | -0.2598 | 6.83508 |
July | 497.00000 | 24.36362 | 54.85064 | -0.2471 | 6.65989 |
August | 514.00000 | 24.30184 | 55.65381 | -0.2588 | 6.71953 |
September | 485.00000 | 24.38435 | 55.14120 | -0.2440 | 6.74922 |
October | 502.00000 | 24.40740 | 52.90961 | 0.58744 | 12.52195 |
November | 489.00000 | 24.35571 | 51.15660 | 0.54717 | 11.42688 |
December | 497.00000 | 24.23514 | 47.31973 | 0.46597 | 9.72635 |
Annual Sum or Average | 5943.00000 | 24.31199 | 50.72811 | 0.17888 | 8.88822 |
Minimum of Months | 454.00000 | 24.17083 | 43.21000 | -0.2771 | 6.65989 |
Maximum of Months | 514.00000 | 24.40740 | 55.65381 | 0.58744 | 12.52195 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87002 | 43.11213 | 0.32622 | 7.55675 |
February | 454.00000 | 24.04674 | 46.04061 | 0.40196 | 8.64728 |
March | 514.00000 | 24.16734 | 45.06284 | 0.44231 | 9.31352 |
April | 485.00000 | 24.30894 | 48.36779 | 0.52005 | 10.88916 |
May | 508.00000 | 24.41480 | 51.34688 | -0.2477 | 6.92163 |
June | 496.00000 | 24.38199 | 54.78312 | -0.2243 | 6.62128 |
July | 497.00000 | 24.45254 | 54.60391 | -0.1944 | 6.49580 |
August | 514.00000 | 24.35121 | 55.56209 | -0.2182 | 6.48971 |
September | 485.00000 | 24.42949 | 55.19349 | -0.2124 | 6.63018 |
October | 502.00000 | 24.42635 | 52.60852 | 0.59428 | 12.73994 |
November | 489.00000 | 24.30089 | 50.44088 | 0.52448 | 10.91259 |
December | 497.00000 | 24.01057 | 46.77114 | 0.39805 | 8.61083 |
Annual Sum or Average | 5943.00000 | 24.26454 | 50.34634 | 0.17325 | 8.47706 |
Minimum of Months | 454.00000 | 23.87002 | 43.11213 | -0.2477 | 6.48971 |
Maximum of Months | 514.00000 | 24.45254 | 55.56209 | 0.59428 | 12.73994 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.46655 | 45.87514 | 0.23511 | 7.14543 |
February | 454.00000 | 23.78216 | 48.76868 | 0.35205 | 8.41236 |
March | 514.00000 | 24.03724 | 46.56096 | 0.42864 | 9.46787 |
April | 485.00000 | 24.35692 | 49.44064 | 0.56497 | 12.32833 |
May | 508.00000 | 24.58264 | 51.40449 | -0.1093 | 6.72584 |
June | 496.00000 | 24.57282 | 54.94598 | -0.0585 | 6.52918 |
July | 497.00000 | 24.70547 | 54.48673 | 0.00218 | 6.85486 |
August | 514.00000 | 24.56652 | 55.49765 | -0.0380 | 6.46081 |
September | 485.00000 | 24.61111 | 55.75107 | -0.0689 | 6.73486 |
October | 502.00000 | 24.55282 | 53.48733 | 0.66390 | 14.97589 |
November | 489.00000 | 24.28791 | 51.75757 | 0.53908 | 11.51795 |
December | 497.00000 | 23.75817 | 49.37167 | 0.34605 | 8.30069 |
Annual Sum or Average | 5943.00000 | 24.27629 | 51.45395 | 0.23635 | 8.77955 |
Minimum of Months | 454.00000 | 23.46655 | 45.87514 | -0.1093 | 6.46081 |
Maximum of Months | 514.00000 | 24.70547 | 55.75107 | 0.66390 | 14.97589 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.74021 | 45.16932 | 0.31537 | 8.05466 |
February | 454.00000 | 23.97875 | 48.20179 | 0.41790 | 9.52874 |
March | 514.00000 | 24.14527 | 46.24387 | 0.47854 | 10.53325 |
April | 485.00000 | 24.45023 | 49.04017 | 0.62192 | 13.96966 |
May | 508.00000 | 24.62082 | 51.22319 | -0.0399 | 6.77142 |
June | 496.00000 | 24.59341 | 54.84062 | -0.0032 | 6.63344 |
July | 497.00000 | 24.73133 | 54.37660 | 0.05971 | 7.20558 |
August | 514.00000 | 24.58883 | 55.36222 | 0.02473 | 6.61347 |
September | 485.00000 | 24.65056 | 55.49196 | -0.0008 | 6.91120 |
October | 502.00000 | 24.61993 | 53.08154 | 0.71487 | 16.62604 |
November | 489.00000 | 24.42655 | 51.39462 | 0.59820 | 13.11948 |
December | 497.00000 | 23.95060 | 48.91480 | 0.40736 | 9.25061 |
Annual Sum or Average | 5943.00000 | 24.37684 | 51.12221 | 0.29776 | 9.58785 |
Minimum of Months | 454.00000 | 23.74021 | 45.16932 | -0.0399 | 6.61347 |
Maximum of Months | 514.00000 | 24.73133 | 55.49196 | 0.71487 | 16.62604 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.92718 | 43.57652 | 0.38319 | 9.60223 |
February | 454.00000 | 24.05411 | 47.17442 | 0.45747 | 10.60997 |
March | 514.00000 | 24.14769 | 45.80006 | 0.48719 | 10.85400 |
April | 485.00000 | 24.39401 | 49.20157 | 0.59098 | 13.10596 |
May | 508.00000 | 24.57693 | 51.42811 | -0.1104 | 6.74705 |
June | 496.00000 | 24.56123 | 55.02876 | -0.0730 | 6.53496 |
July | 497.00000 | 24.69861 | 54.52222 | -0.0031 | 6.84689 |
August | 514.00000 | 24.57176 | 55.41798 | -0.0207 | 6.50823 |
September | 485.00000 | 24.64206 | 55.44614 | -0.0121 | 6.91149 |
October | 502.00000 | 24.63522 | 52.81033 | 0.73678 | 17.39380 |
November | 489.00000 | 24.47412 | 50.59392 | 0.64321 | 14.58909 |
December | 497.00000 | 24.12988 | 47.34289 | 0.47924 | 11.14618 |
Annual Sum or Average | 5943.00000 | 24.40287 | 50.71020 | 0.29435 | 10.05335 |
Minimum of Months | 454.00000 | 23.92718 | 43.57652 | -0.1104 | 6.50823 |
Maximum of Months | 514.00000 | 24.69861 | 55.44614 | 0.73678 | 17.39380 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62867 | 45.58578 | 0.28871 | 8.04768 |
February | 454.00000 | 23.90264 | 48.49560 | 0.40101 | 9.42780 |
March | 514.00000 | 24.11710 | 46.34466 | 0.47406 | 10.56165 |
April | 485.00000 | 24.41540 | 49.33345 | 0.60724 | 13.61352 |
May | 508.00000 | 24.61400 | 51.38540 | -0.0567 | 6.90307 |
June | 496.00000 | 24.59912 | 54.92144 | -0.0092 | 6.74892 |
July | 497.00000 | 24.73012 | 54.45864 | 0.05054 | 7.21015 |
August | 514.00000 | 24.59602 | 55.43834 | 0.01855 | 6.72655 |
September | 485.00000 | 24.65331 | 55.64219 | -0.0075 | 7.01366 |
October | 502.00000 | 24.60393 | 53.42156 | 0.70674 | 16.39013 |
November | 489.00000 | 24.36408 | 51.58507 | 0.58298 | 12.80900 |
December | 497.00000 | 23.89234 | 49.10668 | 0.39475 | 9.32366 |
Annual Sum or Average | 5943.00000 | 24.34560 | 51.31924 | 0.28586 | 9.55299 |
Minimum of Months | 454.00000 | 23.62867 | 45.58578 | -0.0567 | 6.72655 |
Maximum of Months | 514.00000 | 24.73012 | 55.64219 | 0.70674 | 16.39013 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.01288 | 45.85795 | 0.38654 | 8.39429 |
February | 454.00000 | 24.09684 | 49.12586 | 0.43912 | 9.31122 |
March | 514.00000 | 24.15205 | 47.72476 | 0.45924 | 9.66935 |
April | 485.00000 | 24.34755 | 49.76652 | 0.54915 | 11.62130 |
May | 508.00000 | 24.54790 | 50.36734 | -0.1563 | 6.54505 |
June | 496.00000 | 24.54870 | 53.05583 | -0.1019 | 6.34087 |
July | 497.00000 | 24.67876 | 51.82109 | -0.0433 | 6.47934 |
August | 514.00000 | 24.55063 | 51.96562 | -0.0690 | 6.28413 |
September | 485.00000 | 24.61005 | 52.21313 | -0.0835 | 6.50111 |
October | 502.00000 | 24.60418 | 50.86935 | 0.67552 | 15.20577 |
November | 489.00000 | 24.45907 | 50.88758 | 0.60129 | 12.84107 |
December | 497.00000 | 24.20367 | 49.61396 | 0.48100 | 10.09075 |
Annual Sum or Average | 5943.00000 | 24.40264 | 50.27104 | 0.25923 | 9.09449 |
Minimum of Months | 454.00000 | 24.01288 | 45.85795 | -0.1563 | 6.28413 |
Maximum of Months | 514.00000 | 24.67876 | 53.05583 | 0.67552 | 15.20577 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.19671 | 45.34361 | 0.45137 | 9.61315 |
February | 454.00000 | 24.25644 | 48.65468 | 0.49942 | 10.60850 |
March | 514.00000 | 24.25906 | 47.39945 | 0.51006 | 10.83418 |
April | 485.00000 | 24.47684 | 49.26628 | 0.61393 | 13.46180 |
May | 508.00000 | 24.60933 | 50.09205 | -0.0775 | 6.46351 |
June | 496.00000 | 24.58372 | 52.88695 | -0.0405 | 6.36778 |
July | 497.00000 | 24.71702 | 51.66312 | 0.01972 | 6.72950 |
August | 514.00000 | 24.58392 | 51.78409 | 0.00008 | 6.36960 |
September | 485.00000 | 24.65928 | 51.93143 | -0.0093 | 6.64426 |
October | 502.00000 | 24.67539 | 50.51796 | 0.73016 | 16.99470 |
November | 489.00000 | 24.57769 | 50.57231 | 0.65888 | 14.58205 |
December | 497.00000 | 24.32246 | 49.32012 | 0.52941 | 11.22659 |
Annual Sum or Average | 5943.00000 | 24.49415 | 49.95292 | 0.32155 | 9.97211 |
Minimum of Months | 454.00000 | 24.19671 | 45.34361 | -0.0775 | 6.36778 |
Maximum of Months | 514.00000 | 24.71702 | 52.88695 | 0.73016 | 16.99470 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18590 | 44.65333 | 0.48958 | 11.09458 |
February | 454.00000 | 24.22841 | 48.60668 | 0.52802 | 11.70390 |
March | 514.00000 | 24.20162 | 47.44015 | 0.51225 | 11.19671 |
April | 485.00000 | 24.42093 | 50.27738 | 0.58880 | 12.83902 |
May | 508.00000 | 24.70931 | 51.77675 | -0.1000 | 6.44483 |
June | 496.00000 | 24.76097 | 56.28903 | -0.0319 | 6.36725 |
July | 497.00000 | 24.94068 | 56.64060 | 0.06079 | 6.82375 |
August | 514.00000 | 24.90394 | 57.57804 | 0.08895 | 7.01268 |
September | 485.00000 | 24.90861 | 56.23781 | 0.08444 | 7.00437 |
October | 502.00000 | 24.87779 | 53.05644 | 0.81273 | 19.74002 |
November | 489.00000 | 24.66681 | 52.25448 | 0.73268 | 16.95618 |
December | 497.00000 | 24.35926 | 49.31964 | 0.58582 | 13.13927 |
Annual Sum or Average | 5943.00000 | 24.59914 | 52.02652 | 0.36043 | 10.83990 |
Minimum of Months | 454.00000 | 24.18590 | 44.65333 | -0.1000 | 6.36725 |
Maximum of Months | 514.00000 | 24.94068 | 57.57804 | 0.81273 | 19.74002 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17111 | 45.42804 | 0.44152 | 9.47489 |
February | 454.00000 | 24.23539 | 48.69792 | 0.49337 | 10.49365 |
March | 514.00000 | 24.26684 | 47.31466 | 0.51365 | 10.92513 |
April | 485.00000 | 24.45593 | 49.49870 | 0.60369 | 13.16632 |
May | 508.00000 | 24.60662 | 50.25006 | -0.0915 | 6.53360 |
June | 496.00000 | 24.59343 | 52.94301 | -0.0435 | 6.44166 |
July | 497.00000 | 24.71862 | 51.73550 | 0.01282 | 6.71343 |
August | 514.00000 | 24.59288 | 51.86495 | -0.0045 | 6.44913 |
September | 485.00000 | 24.66829 | 52.04828 | -0.0130 | 6.70229 |
October | 502.00000 | 24.67585 | 50.72030 | 0.72571 | 16.85339 |
November | 489.00000 | 24.55433 | 50.67915 | 0.65214 | 14.37324 |
December | 497.00000 | 24.32071 | 49.29007 | 0.52836 | 11.25309 |
Annual Sum or Average | 5943.00000 | 24.48953 | 50.03912 | 0.31599 | 9.93094 |
Minimum of Months | 454.00000 | 24.17111 | 45.42804 | -0.0915 | 6.44166 |
Maximum of Months | 514.00000 | 24.71862 | 52.94301 | 0.72571 | 16.85339 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.79359 | 45.74058 | 0.32266 | 7.65429 |
February | 454.00000 | 23.99385 | 48.82159 | 0.40966 | 8.92894 |
March | 514.00000 | 24.14734 | 46.99342 | 0.45962 | 9.75864 |
April | 485.00000 | 24.39203 | 49.97184 | 0.57156 | 12.29436 |
May | 508.00000 | 24.57345 | 51.65523 | -0.1308 | 6.62934 |
June | 496.00000 | 24.55949 | 54.83538 | -0.0871 | 6.45555 |
July | 497.00000 | 24.69251 | 54.36399 | -0.0323 | 6.65063 |
August | 514.00000 | 24.55549 | 55.31246 | -0.0699 | 6.38149 |
September | 485.00000 | 24.59802 | 55.41660 | -0.0944 | 6.62798 |
October | 502.00000 | 24.55675 | 53.49293 | 0.65830 | 14.73384 |
November | 489.00000 | 24.34940 | 52.13120 | 0.55923 | 11.81135 |
December | 497.00000 | 23.99337 | 49.56268 | 0.41202 | 8.96787 |
Annual Sum or Average | 5943.00000 | 24.35253 | 51.53319 | 0.24612 | 8.89681 |
Minimum of Months | 454.00000 | 23.79359 | 45.74058 | -0.1308 | 6.38149 |
Maximum of Months | 514.00000 | 24.69251 | 55.41660 | 0.65830 | 14.73384 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.99802 | 44.78682 | 0.37730 | 8.59815 |
February | 385.00000 | 24.17920 | 48.02310 | 0.46057 | 10.06192 |
March | 433.00000 | 24.28561 | 46.24085 | 0.50013 | 10.79721 |
April | 410.00000 | 24.57524 | 49.34479 | 0.63211 | 14.19263 |
May | 430.00000 | 24.72701 | 51.21480 | -0.0481 | 6.84647 |
June | 418.00000 | 24.69401 | 54.59037 | -0.0184 | 6.74711 |
July | 422.00000 | 24.85235 | 53.86037 | 0.04478 | 7.23929 |
August | 433.00000 | 24.69117 | 54.97247 | 0.00504 | 6.70453 |
September | 410.00000 | 24.76032 | 54.97359 | -0.0101 | 7.01572 |
October | 427.00000 | 24.73775 | 52.88213 | 0.71971 | 16.81742 |
November | 417.00000 | 24.56114 | 51.03523 | 0.61724 | 13.55487 |
December | 422.00000 | 24.16482 | 48.78579 | 0.45766 | 9.94557 |
Annual Sum or Average | 5034.00000 | 24.52039 | 50.89967 | 0.31001 | 9.86663 |
Minimum of Months | 385.00000 | 23.99802 | 44.78682 | -0.0481 | 6.70453 |
Maximum of Months | 433.00000 | 24.85235 | 54.97359 | 0.71971 | 16.81742 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.17476 | 43.73486 | 0.45417 | 10.29697 |
February | 454.00000 | 24.22985 | 47.38001 | 0.50678 | 11.17194 |
March | 514.00000 | 24.25217 | 46.25807 | 0.51573 | 11.13996 |
April | 485.00000 | 24.43657 | 49.70566 | 0.59811 | 13.09093 |
May | 508.00000 | 24.56693 | 51.67691 | -0.1321 | 6.63946 |
June | 496.00000 | 24.54574 | 54.92650 | -0.1019 | 6.46857 |
July | 497.00000 | 24.68382 | 54.40611 | -0.0381 | 6.64112 |
August | 514.00000 | 24.56134 | 55.22118 | -0.0531 | 6.39570 |
September | 485.00000 | 24.63265 | 55.07889 | -0.0381 | 6.71311 |
October | 502.00000 | 24.64265 | 52.78787 | 0.73027 | 17.08563 |
November | 489.00000 | 24.53495 | 51.03572 | 0.66122 | 14.90673 |
December | 497.00000 | 24.30331 | 47.77383 | 0.53192 | 11.87648 |
Annual Sum or Average | 5943.00000 | 24.46480 | 50.84656 | 0.30037 | 10.18178 |
Minimum of Months | 454.00000 | 24.17476 | 43.73486 | -0.1321 | 6.39570 |
Maximum of Months | 514.00000 | 24.68382 | 55.22118 | 0.73027 | 17.08563 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93757 | 45.47179 | 0.37188 | 8.59707 |
February | 454.00000 | 24.10448 | 48.55484 | 0.45581 | 9.94665 |
March | 514.00000 | 24.22559 | 46.76551 | 0.50381 | 10.84632 |
April | 485.00000 | 24.46030 | 49.85361 | 0.61516 | 13.61447 |
May | 508.00000 | 24.60898 | 51.63400 | -0.0773 | 6.72375 |
June | 496.00000 | 24.58955 | 54.80014 | -0.0372 | 6.59634 |
July | 497.00000 | 24.72189 | 54.32408 | 0.01689 | 6.91965 |
August | 514.00000 | 24.58802 | 55.23389 | -0.0133 | 6.55449 |
September | 485.00000 | 24.64593 | 55.28654 | -0.0324 | 6.81547 |
October | 502.00000 | 24.61155 | 53.42088 | 0.70130 | 16.12820 |
November | 489.00000 | 24.43265 | 51.96351 | 0.60353 | 13.12991 |
December | 497.00000 | 24.11057 | 49.31574 | 0.45660 | 9.99017 |
Annual Sum or Average | 5943.00000 | 24.42149 | 51.39471 | 0.29500 | 9.64034 |
Minimum of Months | 454.00000 | 23.93757 | 45.47179 | -0.0773 | 6.55449 |
Maximum of Months | 514.00000 | 24.72189 | 55.28654 | 0.70130 | 16.12820 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.397423E+11 | 0.896432E+10 | 412.67 | 0.343736E+11 | 0.536865E+10 | 0.00 | 1.00 | 02-JAN-13:20 | 0.00 | 01-JAN-00:10 | 61107.72 | 30-JAN-07:03 | 50155.45 | 23-JAN-14:00 | 14760.83 | 30-JAN-15:05 | 12883.14 | 30-JAN-07:03 | 0.00 |
February | 0.425245E+11 | 0.963136E+10 | 370.39 | 0.361591E+11 | 0.636541E+10 | 0.00 | 1.00 | 01-FEB-13:30 | 0.00 | 01-FEB-00:10 | 73316.49 | 07-FEB-16:00 | 64258.43 | 06-FEB-15:20 | 24789.60 | 09-FEB-07:03 | 17838.17 | 07-FEB-13:03 | 0.00 |
March | 0.569443E+11 | 0.133159E+11 | 438.39 | 0.501142E+11 | 0.683006E+10 | 0.00 | 1.00 | 01-MAR-06:13 | 0.00 | 01-MAR-00:10 | 77948.69 | 02-MAR-07:03 | 77948.69 | 02-MAR-07:03 | 26324.00 | 29-MAR-06:03 | 22887.44 | 27-MAR-11:00 | 0.00 |
April | 0.685346E+11 | 0.168305E+11 | 432.72 | 0.586406E+11 | 0.989395E+10 | 0.00 | 1.00 | 01-APR-05:12 | 0.00 | 01-APR-00:10 | 86424.70 | 10-APR-12:00 | 75155.65 | 28-APR-12:02 | 31383.55 | 10-APR-11:50 | 25972.80 | 28-APR-12:02 | 0.00 |
May | 0.103919E+12 | 0.276843E+11 | 501.43 | 0.857865E+11 | 0.181329E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 130893.72 | 31-MAY-04:02 | 93876.11 | 22-MAY-06:03 | 54474.44 | 24-MAY-04:02 | 33828.19 | 31-MAY-12:02 | 0.00 |
June | 0.125508E+12 | 0.337348E+11 | 504.18 | 0.923571E+11 | 0.331513E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:03 | 133814.97 | 20-JUN-04:02 | 91561.07 | 26-JUN-04:02 | 57137.13 | 24-JUN-04:03 | 35798.84 | 12-JUN-12:02 | 0.00 |
July | 0.153365E+12 | 0.419129E+11 | 577.87 | 0.102904E+12 | 0.504617E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 135257.52 | 20-JUL-06:07 | 93311.50 | 03-JUL-06:03 | 76958.57 | 20-JUL-06:07 | 37649.60 | 30-JUL-14:41 | 0.00 |
August | 0.170100E+12 | 0.466216E+11 | 603.85 | 0.111922E+12 | 0.581779E+11 | 0.00 | 1.00 | 01-AUG-00:20 | 0.00 | 01-AUG-00:05 | 133828.87 | 08-AUG-06:15 | 97547.57 | 07-AUG-05:02 | 66351.92 | 08-AUG-06:15 | 38965.05 | 10-AUG-14:30 | 0.00 |
September | 0.136346E+12 | 0.355794E+11 | 525.03 | 0.926208E+11 | 0.437248E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:15 | 134980.56 | 10-SEP-17:42 | 95196.71 | 13-SEP-04:02 | 70019.88 | 10-SEP-17:42 | 35993.31 | 04-SEP-14:01 | 0.00 |
October | 0.109786E+12 | 0.273389E+11 | 505.42 | 0.824984E+11 | 0.272878E+11 | 0.00 | 1.00 | 01-OCT-08:53 | 0.00 | 01-OCT-00:10 | 132315.48 | 18-OCT-04:02 | 92759.30 | 10-OCT-04:02 | 55907.05 | 07-OCT-04:03 | 29466.17 | 05-OCT-04:02 | 0.00 |
November | 0.788091E+11 | 0.184912E+11 | 442.44 | 0.634798E+11 | 0.153293E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 129728.97 | 02-NOV-06:03 | 89281.99 | 20-NOV-05:02 | 46247.15 | 03-NOV-06:03 | 27345.92 | 02-NOV-06:03 | 0.00 |
December | 0.506833E+11 | 0.113424E+11 | 411.92 | 0.423239E+11 | 0.835940E+10 | 0.00 | 1.00 | 01-DEC-09:40 | 0.00 | 01-DEC-00:10 | 83705.85 | 12-DEC-07:03 | 67077.61 | 11-DEC-07:03 | 26165.13 | 05-DEC-12:40 | 17812.38 | 04-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.113626E+13 | 0.291448E+12 | 5726.31 | 0.853180E+12 | 0.283083E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.397423E+11 | 0.896432E+10 | 370.39 | 0.343736E+11 | 0.536865E+10 | 0.00 | 1.00 | 0.00 | 61107.72 | 50155.45 | 14760.83 | 12883.14 | 0.00 | ||||||
Maximum of Months | 0.170100E+12 | 0.466216E+11 | 603.85 | 0.111922E+12 | 0.581779E+11 | 0.00 | 1.00 | 0.00 | 135257.52 | 97547.57 | 76958.57 | 38965.05 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.288214E+11 | 0.667852E+10 | 404.89 | 0.233690E+11 | 0.545247E+10 | 0.00 | 1.00 | 23-JAN-13:05 | 0.00 | 01-JAN-00:10 | 45094.26 | 30-JAN-14:00 | 40303.93 | 23-JAN-13:30 | 12871.45 | 30-JAN-15:05 | 9532.26 | 30-JAN-14:00 | 0.00 |
February | 0.330966E+11 | 0.765298E+10 | 371.06 | 0.269323E+11 | 0.616431E+10 | 0.00 | 1.00 | 06-FEB-06:12 | 0.00 | 01-FEB-00:10 | 64916.94 | 07-FEB-15:05 | 57875.34 | 06-FEB-15:05 | 17133.86 | 07-FEB-16:00 | 15039.69 | 06-FEB-15:05 | 0.00 |
March | 0.470054E+11 | 0.111368E+11 | 438.94 | 0.403485E+11 | 0.665681E+10 | 0.00 | 1.00 | 01-MAR-10:00 | 0.00 | 01-MAR-00:10 | 67566.29 | 27-MAR-12:01 | 67566.29 | 27-MAR-12:01 | 15247.97 | 28-MAR-16:00 | 20993.75 | 27-MAR-11:00 | 0.00 |
April | 0.590968E+11 | 0.145757E+11 | 433.75 | 0.500292E+11 | 0.906766E+10 | 0.00 | 1.00 | 01-APR-14:05 | 0.00 | 01-APR-00:10 | 113624.31 | 30-APR-16:32 | 71549.66 | 28-APR-12:02 | 48002.49 | 30-APR-16:32 | 26504.73 | 30-APR-16:32 | 0.00 |
May | 0.907719E+11 | 0.240673E+11 | 498.18 | 0.751802E+11 | 0.155918E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:15 | 122505.04 | 31-MAY-04:02 | 83131.07 | 23-MAY-04:02 | 54527.52 | 24-MAY-04:02 | 31992.31 | 31-MAY-12:01 | 0.00 |
June | 0.110172E+12 | 0.293478E+11 | 502.07 | 0.805168E+11 | 0.296553E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:25 | 125751.52 | 20-JUN-04:02 | 82900.27 | 01-JUN-04:02 | 56996.72 | 25-JUN-15:22 | 35013.25 | 12-JUN-12:01 | 0.00 |
July | 0.133653E+12 | 0.362353E+11 | 560.26 | 0.900881E+11 | 0.435651E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 125587.01 | 06-JUL-04:02 | 92104.56 | 30-JUL-14:12 | 59984.93 | 30-JUL-16:53 | 36664.11 | 30-JUL-14:12 | 0.00 |
August | 0.143974E+12 | 0.392038E+11 | 571.21 | 0.960111E+11 | 0.479627E+11 | 0.00 | 1.00 | 01-AUG-00:25 | 0.00 | 01-AUG-00:05 | 126646.42 | 08-AUG-04:02 | 88152.02 | 06-AUG-14:51 | 58487.85 | 08-AUG-12:02 | 38143.16 | 16-AUG-12:01 | 0.00 |
September | 0.112815E+12 | 0.292471E+11 | 491.67 | 0.768079E+11 | 0.360070E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:05 | 126076.89 | 24-SEP-16:42 | 91208.47 | 04-SEP-15:11 | 64013.08 | 10-SEP-18:03 | 35252.87 | 04-SEP-14:32 | 0.00 |
October | 0.876452E+11 | 0.217803E+11 | 472.17 | 0.660943E+11 | 0.215509E+11 | 0.00 | 1.00 | 01-OCT-08:33 | 0.00 | 01-OCT-00:10 | 123907.45 | 07-OCT-05:03 | 84847.76 | 10-OCT-04:02 | 56171.93 | 07-OCT-05:03 | 28118.65 | 08-OCT-14:42 | 0.00 |
November | 0.601236E+11 | 0.141932E+11 | 417.31 | 0.475875E+11 | 0.125361E+11 | 0.00 | 1.00 | 01-NOV-04:42 | 0.00 | 01-NOV-00:10 | 91735.24 | 03-NOV-05:03 | 72397.02 | 20-NOV-05:02 | 39025.44 | 03-NOV-05:03 | 22653.06 | 01-NOV-12:02 | 0.00 |
December | 0.376368E+11 | 0.862545E+10 | 406.06 | 0.295299E+11 | 0.810688E+10 | 0.00 | 1.00 | 01-DEC-11:05 | 0.00 | 01-DEC-00:10 | 62857.45 | 05-DEC-15:05 | 48648.48 | 04-DEC-13:05 | 19543.60 | 05-DEC-15:05 | 14173.25 | 04-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.944812E+12 | 0.242744E+12 | 5567.56 | 0.702495E+12 | 0.242317E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.288214E+11 | 0.667852E+10 | 371.06 | 0.233690E+11 | 0.545247E+10 | 0.00 | 1.00 | 0.00 | 45094.26 | 40303.93 | 12871.45 | 9532.26 | 0.00 | ||||||
Maximum of Months | 0.143974E+12 | 0.392038E+11 | 571.21 | 0.960111E+11 | 0.479627E+11 | 0.00 | 1.00 | 0.00 | 126646.42 | 92104.56 | 64013.08 | 38143.16 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.280034E+11 | 0.659163E+10 | 402.31 | 0.218133E+11 | 0.619005E+10 | 0.00 | 0.98 | 23-JAN-14:00 | 0.00 | 01-JAN-00:10 | 44007.32 | 30-JAN-14:10 | 42193.70 | 23-JAN-14:00 | 13005.66 | 30-JAN-15:10 | 9886.11 | 23-JAN-14:00 | 0.00 |
February | 0.333037E+11 | 0.781042E+10 | 370.36 | 0.265451E+11 | 0.675858E+10 | 0.00 | 1.00 | 05-FEB-13:23 | 0.00 | 01-FEB-00:10 | 68002.09 | 07-FEB-15:30 | 61131.04 | 06-FEB-15:00 | 16905.66 | 07-FEB-16:00 | 15903.71 | 06-FEB-15:00 | 0.00 |
March | 0.487273E+11 | 0.116824E+11 | 438.00 | 0.413624E+11 | 0.736492E+10 | 0.00 | 1.00 | 01-MAR-10:50 | 0.00 | 01-MAR-00:10 | 74647.52 | 27-MAR-13:50 | 74647.52 | 27-MAR-13:50 | 16208.57 | 31-MAR-18:10 | 22447.88 | 27-MAR-12:03 | 0.00 |
April | 0.629479E+11 | 0.156845E+11 | 435.86 | 0.531933E+11 | 0.975463E+10 | 0.00 | 1.00 | 01-APR-13:50 | 0.00 | 01-APR-00:10 | 95252.55 | 30-APR-12:43 | 89781.49 | 30-APR-12:43 | 31949.72 | 30-APR-18:03 | 27495.23 | 28-APR-12:02 | 0.00 |
May | 0.985271E+11 | 0.262673E+11 | 505.68 | 0.821336E+11 | 0.163934E+11 | 0.00 | 1.00 | 01-MAY-05:12 | 0.00 | 01-MAY-00:05 | 139824.35 | 31-MAY-04:02 | 100291.75 | 12-MAY-04:02 | 59031.34 | 24-MAY-05:03 | 32913.07 | 29-MAY-15:12 | 0.00 |
June | 0.119535E+12 | 0.319805E+11 | 512.82 | 0.887540E+11 | 0.307813E+11 | 0.00 | 1.00 | 01-JUN-04:02 | 0.00 | 01-JUN-00:15 | 143845.00 | 14-JUN-04:02 | 97663.14 | 26-JUN-04:02 | 64033.51 | 20-JUN-04:02 | 37240.35 | 04-JUN-15:52 | 0.00 |
July | 0.147218E+12 | 0.400125E+11 | 581.65 | 0.101190E+12 | 0.460280E+11 | 0.00 | 1.00 | 01-JUL-04:02 | 0.00 | 01-JUL-00:10 | 143523.40 | 16-JUL-18:42 | 112093.63 | 30-JUL-13:22 | 63279.58 | 16-JUL-17:22 | 42651.04 | 30-JUL-14:02 | 0.00 |
August | 0.156189E+12 | 0.426434E+11 | 591.35 | 0.106227E+12 | 0.499619E+11 | 0.00 | 1.00 | 01-AUG-00:20 | 0.00 | 01-AUG-00:05 | 143329.28 | 26-AUG-04:02 | 105370.61 | 07-AUG-05:02 | 61683.34 | 26-AUG-06:03 | 40184.12 | 06-AUG-15:02 | 0.00 |
September | 0.120538E+12 | 0.313617E+11 | 501.78 | 0.834540E+11 | 0.370838E+11 | 0.00 | 1.00 | 01-SEP-04:02 | 0.00 | 01-SEP-00:15 | 143708.41 | 10-SEP-18:12 | 111286.07 | 04-SEP-16:12 | 69403.63 | 10-SEP-18:12 | 40315.94 | 04-SEP-14:12 | 0.00 |
October | 0.912836E+11 | 0.228464E+11 | 471.42 | 0.692921E+11 | 0.219915E+11 | 0.00 | 1.00 | 01-OCT-09:13 | 0.00 | 01-OCT-00:10 | 143786.91 | 08-OCT-11:32 | 93320.93 | 09-OCT-14:32 | 61682.17 | 08-OCT-11:32 | 35003.72 | 08-OCT-11:32 | 0.00 |
November | 0.609047E+11 | 0.145302E+11 | 416.33 | 0.478442E+11 | 0.130605E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 96162.46 | 03-NOV-05:03 | 68769.93 | 20-NOV-06:03 | 40843.43 | 03-NOV-05:03 | 22855.78 | 01-NOV-14:00 | 0.00 |
December | 0.371103E+11 | 0.864774E+10 | 405.50 | 0.282227E+11 | 0.888761E+10 | 0.00 | 1.00 | 01-DEC-13:05 | 0.00 | 01-DEC-00:10 | 63343.07 | 05-DEC-15:00 | 49647.42 | 04-DEC-13:20 | 19001.74 | 05-DEC-15:00 | 13829.70 | 05-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.100429E+13 | 0.260059E+12 | 5633.06 | 0.750032E+12 | 0.254256E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.280034E+11 | 0.659163E+10 | 370.36 | 0.218133E+11 | 0.619005E+10 | 0.00 | 0.98 | 0.00 | 44007.32 | 42193.70 | 13005.66 | 9886.11 | 0.00 | ||||||
Maximum of Months | 0.156189E+12 | 0.426434E+11 | 591.35 | 0.106227E+12 | 0.499619E+11 | 0.00 | 1.00 | 0.00 | 143845.00 | 112093.63 | 69403.63 | 42651.04 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 364.15 | 686.50 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 500.52 | 577.30 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 719.99 | 439.79 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1044.05 | 277.72 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1587.92 | 71.33 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1838.03 | 18.36 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2054.04 | 0.51 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2027.22 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1521.66 | 26.42 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1088.27 | 116.42 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 690.01 | 316.57 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 408.48 | 561.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1157.75 | 256.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 364.15 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2054.04 | 686.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 525.49 | 433.10 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 634.61 | 367.31 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 808.78 | 281.68 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1156.18 | 179.65 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1565.91 | 45.52 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1655.72 | 10.98 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1790.29 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1851.01 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1497.83 | 15.87 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1170.72 | 71.93 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 811.48 | 201.11 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 513.91 | 357.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1168.26 | 162.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 513.91 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1851.01 | 433.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1619.38 | 671.48 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1616.62 | 576.55 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1489.95 | 449.22 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1391.36 | 284.30 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1583.17 | 71.90 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1685.56 | 14.83 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 1991.29 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2234.14 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2202.76 | 26.39 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2284.14 | 116.57 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2119.96 | 317.89 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1716.64 | 559.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1829.41 | 255.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1391.36 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2284.14 | 671.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 539.13 | 462.41 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 677.06 | 389.56 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 907.30 | 301.33 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1149.10 | 195.98 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1528.96 | 53.43 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1680.49 | 12.78 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1784.94 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1840.47 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1509.17 | 19.80 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1169.69 | 84.03 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 845.60 | 219.31 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 571.42 | 381.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1186.54 | 175.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 539.13 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1840.47 | 462.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.20 | 259.62 | 0.00 | 0.00 | 0.00 |
February | 120.56 | 0.00 | 120.56 | 164.54 | 211.20 | 0.00 | 0.00 | 0.00 |
March | 138.48 | 0.00 | 138.48 | 242.01 | 154.05 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.70 | 353.10 | 92.87 | 0.00 | 0.00 | 0.00 |
May | 175.62 | 5.15 | 170.47 | 533.88 | 22.62 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 614.77 | 5.85 | 0.00 | 0.00 | 0.00 |
July | 172.54 | 4.97 | 167.57 | 684.95 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 160.62 | 1.33 | 159.29 | 670.77 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.31 | 0.02 | 146.29 | 500.96 | 10.52 | 0.00 | 0.00 | 0.00 |
October | 129.70 | 0.00 | 129.70 | 355.78 | 45.77 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.21 | 122.56 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 129.48 | 215.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.96 | 1.86 | 140.11 | 383.73 | 94.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.20 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 684.95 | 259.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.20 | 259.63 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 164.54 | 211.22 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 242.02 | 154.06 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 353.12 | 92.87 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 533.91 | 22.62 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 614.81 | 5.85 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 684.99 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 670.81 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 500.99 | 10.53 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 355.80 | 45.77 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.22 | 122.57 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 129.49 | 215.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 383.75 | 94.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.20 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 684.99 | 259.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.18 | 0.00 | 105.18 | 115.20 | 259.63 | 0.00 | 0.00 | 0.00 |
February | 120.57 | 0.00 | 120.57 | 164.54 | 211.22 | 0.00 | 0.00 | 0.00 |
March | 138.49 | 0.00 | 138.49 | 242.02 | 154.06 | 0.00 | 0.00 | 0.00 |
April | 156.03 | 0.32 | 155.71 | 353.12 | 92.87 | 0.00 | 0.00 | 0.00 |
May | 175.63 | 5.15 | 170.48 | 533.91 | 22.62 | 0.00 | 0.00 | 0.00 |
June | 188.04 | 10.44 | 177.60 | 614.81 | 5.85 | 0.00 | 0.00 | 0.00 |
July | 172.55 | 4.97 | 167.58 | 684.99 | 0.16 | 0.00 | 0.00 | 0.00 |
August | 160.63 | 1.33 | 159.30 | 670.81 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 146.32 | 0.02 | 146.30 | 500.99 | 10.53 | 0.00 | 0.00 | 0.00 |
October | 129.71 | 0.00 | 129.71 | 355.80 | 45.77 | 0.00 | 0.00 | 0.00 |
November | 111.35 | 0.00 | 111.35 | 223.22 | 122.57 | 0.00 | 0.00 | 0.00 |
December | 98.17 | 0.00 | 98.17 | 129.49 | 215.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 141.97 | 1.86 | 140.11 | 383.75 | 94.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.17 | 0.00 | 98.17 | 115.20 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 188.04 | 10.44 | 177.60 | 684.99 | 259.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 366.07 | 110.75 | 255.32 | 490.65 | 471.88 | 0.00 | 0.00 | 0.00 |
February | 398.93 | 108.11 | 290.82 | 605.44 | 389.41 | 0.00 | 0.00 | 0.00 |
March | 440.66 | 108.61 | 332.05 | 782.31 | 287.65 | 0.00 | 0.00 | 0.00 |
April | 536.52 | 156.32 | 380.20 | 1122.77 | 178.16 | 0.00 | 0.00 | 0.00 |
May | 599.58 | 191.03 | 408.55 | 1515.70 | 44.58 | 0.00 | 0.00 | 0.00 |
June | 587.19 | 179.57 | 407.62 | 1597.26 | 11.33 | 0.00 | 0.00 | 0.00 |
July | 548.05 | 158.00 | 390.05 | 1722.32 | 0.34 | 0.00 | 0.00 | 0.00 |
August | 561.20 | 172.24 | 388.96 | 1770.45 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 527.59 | 163.07 | 364.52 | 1429.32 | 19.87 | 0.00 | 0.00 | 0.00 |
October | 478.74 | 156.40 | 322.33 | 1115.18 | 86.39 | 0.00 | 0.00 | 0.00 |
November | 401.18 | 127.07 | 274.11 | 768.66 | 228.29 | 0.00 | 0.00 | 0.00 |
December | 324.72 | 89.09 | 235.63 | 479.63 | 395.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.19 | 143.50 | 337.69 | 1119.61 | 175.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 324.72 | 89.09 | 235.63 | 479.63 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 599.58 | 191.03 | 408.55 | 1770.45 | 471.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.47 | 4.38 | 10.09 | 19.40 | 18.66 | 0.00 | 0.00 | 0.00 |
February | 15.77 | 4.27 | 11.50 | 23.94 | 15.40 | 0.00 | 0.00 | 0.00 |
March | 17.42 | 4.29 | 13.13 | 30.93 | 11.37 | 0.00 | 0.00 | 0.00 |
April | 21.21 | 6.18 | 15.03 | 44.39 | 7.04 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 7.55 | 16.15 | 59.93 | 1.76 | 0.00 | 0.00 | 0.00 |
June | 23.22 | 7.10 | 16.12 | 63.15 | 0.45 | 0.00 | 0.00 | 0.00 |
July | 21.67 | 6.25 | 15.42 | 68.10 | 0.01 | 0.00 | 0.00 | 0.00 |
August | 22.19 | 6.81 | 15.38 | 70.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20.86 | 6.45 | 14.41 | 56.51 | 0.79 | 0.00 | 0.00 | 0.00 |
October | 18.93 | 6.18 | 12.74 | 44.09 | 3.42 | 0.00 | 0.00 | 0.00 |
November | 15.86 | 5.02 | 10.84 | 30.39 | 9.03 | 0.00 | 0.00 | 0.00 |
December | 12.84 | 3.52 | 9.32 | 18.96 | 15.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.03 | 5.67 | 13.35 | 44.27 | 6.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.84 | 3.52 | 9.32 | 18.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.71 | 7.55 | 16.15 | 70.00 | 18.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 537.26 | 254.32 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 540.31 | 213.36 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 500.41 | 159.10 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 468.52 | 96.48 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 528.21 | 23.71 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 557.49 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 657.29 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 730.05 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 721.71 | 11.83 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 752.67 | 50.27 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 702.29 | 127.72 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 569.27 | 215.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 605.91 | 95.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 468.52 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 752.67 | 254.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.93 | 159.82 | 180.12 | 537.26 | 254.32 | 0.00 | 0.00 | 0.00 |
February | 319.21 | 130.57 | 188.64 | 540.31 | 213.36 | 0.00 | 0.00 | 0.00 |
March | 262.73 | 71.33 | 191.40 | 500.41 | 159.10 | 0.00 | 0.00 | 0.00 |
April | 206.52 | 21.90 | 184.63 | 468.52 | 96.48 | 0.00 | 0.00 | 0.00 |
May | 174.94 | 2.68 | 172.26 | 528.21 | 23.71 | 0.00 | 0.00 | 0.00 |
June | 164.76 | 0.20 | 164.55 | 557.49 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 164.75 | 1.40 | 163.35 | 657.29 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 191.10 | 13.54 | 177.56 | 730.05 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.97 | 57.74 | 194.22 | 721.71 | 11.83 | 0.00 | 0.00 | 0.00 |
October | 329.87 | 131.14 | 198.73 | 752.67 | 50.27 | 0.00 | 0.00 | 0.00 |
November | 363.91 | 175.43 | 188.48 | 702.29 | 127.72 | 0.00 | 0.00 | 0.00 |
December | 337.82 | 166.87 | 170.95 | 569.27 | 215.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.60 | 77.44 | 181.16 | 605.91 | 95.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.75 | 0.20 | 163.35 | 468.52 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.91 | 175.43 | 198.73 | 752.67 | 254.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 339.91 | 159.81 | 180.10 | 537.23 | 254.31 | 0.00 | 0.00 | 0.00 |
February | 319.19 | 130.56 | 188.63 | 540.27 | 213.35 | 0.00 | 0.00 | 0.00 |
March | 262.71 | 71.32 | 191.39 | 500.38 | 159.09 | 0.00 | 0.00 | 0.00 |
April | 206.51 | 21.89 | 184.62 | 468.49 | 96.47 | 0.00 | 0.00 | 0.00 |
May | 174.93 | 2.68 | 172.25 | 528.18 | 23.71 | 0.00 | 0.00 | 0.00 |
June | 164.75 | 0.20 | 164.54 | 557.45 | 5.21 | 0.00 | 0.00 | 0.00 |
July | 164.74 | 1.40 | 163.34 | 657.25 | 0.11 | 0.00 | 0.00 | 0.00 |
August | 191.09 | 13.54 | 177.55 | 730.00 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 251.95 | 57.74 | 194.21 | 721.67 | 11.83 | 0.00 | 0.00 | 0.00 |
October | 329.85 | 131.13 | 198.72 | 752.62 | 50.27 | 0.00 | 0.00 | 0.00 |
November | 363.89 | 175.42 | 188.47 | 702.25 | 127.71 | 0.00 | 0.00 | 0.00 |
December | 337.80 | 166.86 | 170.94 | 569.23 | 215.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 258.58 | 77.43 | 181.15 | 605.88 | 95.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.74 | 0.20 | 163.34 | 468.49 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 363.89 | 175.42 | 198.72 | 752.62 | 254.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 359.00 | 103.11 | 255.89 | 509.64 | 508.14 | 0.00 | 0.00 | 0.00 |
February | 409.94 | 116.90 | 293.04 | 650.20 | 415.84 | 0.00 | 0.00 | 0.00 |
March | 485.58 | 143.76 | 341.83 | 880.28 | 310.13 | 0.00 | 0.00 | 0.00 |
April | 530.66 | 149.09 | 381.57 | 1117.62 | 194.93 | 0.00 | 0.00 | 0.00 |
May | 577.62 | 172.90 | 404.72 | 1479.84 | 52.47 | 0.00 | 0.00 | 0.00 |
June | 596.92 | 188.17 | 408.76 | 1618.92 | 13.51 | 0.00 | 0.00 | 0.00 |
July | 547.61 | 156.66 | 390.95 | 1716.57 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 561.79 | 170.81 | 390.98 | 1760.82 | 0.14 | 0.00 | 0.00 | 0.00 |
September | 534.41 | 167.89 | 366.51 | 1440.76 | 24.28 | 0.00 | 0.00 | 0.00 |
October | 474.93 | 153.42 | 321.52 | 1114.87 | 98.86 | 0.00 | 0.00 | 0.00 |
November | 408.14 | 133.48 | 274.67 | 803.91 | 249.51 | 0.00 | 0.00 | 0.00 |
December | 341.68 | 103.28 | 238.40 | 540.00 | 424.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.96 | 146.72 | 339.24 | 1138.92 | 190.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 341.68 | 103.11 | 238.40 | 509.64 | 0.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 596.92 | 188.17 | 408.76 | 1760.82 | 508.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.19 | 4.08 | 10.12 | 20.15 | 20.09 | 0.00 | 0.00 | 0.00 |
February | 16.21 | 4.62 | 11.59 | 25.71 | 16.44 | 0.00 | 0.00 | 0.00 |
March | 19.20 | 5.68 | 13.52 | 34.81 | 12.26 | 0.00 | 0.00 | 0.00 |
April | 20.98 | 5.89 | 15.09 | 44.19 | 7.71 | 0.00 | 0.00 | 0.00 |
May | 22.84 | 6.84 | 16.00 | 58.51 | 2.07 | 0.00 | 0.00 | 0.00 |
June | 23.60 | 7.44 | 16.16 | 64.01 | 0.53 | 0.00 | 0.00 | 0.00 |
July | 21.65 | 6.19 | 15.46 | 67.87 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 22.21 | 6.75 | 15.46 | 69.62 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 21.13 | 6.64 | 14.49 | 56.97 | 0.96 | 0.00 | 0.00 | 0.00 |
October | 18.78 | 6.07 | 12.71 | 44.08 | 3.91 | 0.00 | 0.00 | 0.00 |
November | 16.14 | 5.28 | 10.86 | 31.79 | 9.87 | 0.00 | 0.00 | 0.00 |
December | 13.51 | 4.08 | 9.43 | 21.35 | 16.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.21 | 5.80 | 13.41 | 45.03 | 7.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.51 | 4.08 | 9.43 | 20.15 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.60 | 7.44 | 16.16 | 69.62 | 20.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 315.55 | 0.00 | 315.55 | 352.39 | 741.38 | 0.00 | 0.00 | 0.00 |
February | 361.71 | 0.00 | 361.71 | 494.09 | 616.56 | 0.00 | 0.00 | 0.00 |
March | 415.47 | 0.00 | 415.47 | 719.70 | 464.26 | 0.00 | 0.00 | 0.00 |
April | 468.10 | 0.96 | 467.13 | 1050.30 | 288.30 | 0.00 | 0.00 | 0.00 |
May | 526.89 | 15.45 | 511.43 | 1600.15 | 72.12 | 0.00 | 0.00 | 0.00 |
June | 564.13 | 31.32 | 532.81 | 1851.46 | 17.96 | 0.00 | 0.00 | 0.00 |
July | 517.65 | 14.91 | 502.73 | 2071.48 | 0.46 | 0.00 | 0.00 | 0.00 |
August | 481.88 | 3.99 | 477.90 | 2042.31 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 438.95 | 0.05 | 438.90 | 1532.06 | 26.81 | 0.00 | 0.00 | 0.00 |
October | 389.12 | 0.00 | 389.12 | 1093.61 | 121.36 | 0.00 | 0.00 | 0.00 |
November | 334.05 | 0.00 | 334.05 | 688.89 | 336.86 | 0.00 | 0.00 | 0.00 |
December | 294.52 | 0.00 | 294.52 | 399.81 | 604.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 425.91 | 5.58 | 420.34 | 1162.13 | 272.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 294.52 | 0.00 | 294.52 | 352.39 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 564.13 | 31.32 | 532.81 | 2071.48 | 741.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 380.55 | 115.13 | 265.41 | 511.90 | 463.39 | 0.00 | 0.00 | 0.00 |
February | 414.71 | 112.39 | 302.32 | 625.50 | 389.71 | 0.00 | 0.00 | 0.00 |
March | 458.09 | 112.90 | 345.19 | 804.01 | 296.20 | 0.00 | 0.00 | 0.00 |
April | 557.74 | 162.51 | 395.23 | 1156.32 | 186.24 | 0.00 | 0.00 | 0.00 |
May | 623.29 | 198.58 | 424.71 | 1570.68 | 46.31 | 0.00 | 0.00 | 0.00 |
June | 610.42 | 186.67 | 423.75 | 1660.89 | 10.90 | 0.00 | 0.00 | 0.00 |
July | 569.73 | 164.25 | 405.48 | 1798.06 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 583.40 | 179.05 | 404.34 | 1857.07 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 548.46 | 169.52 | 378.94 | 1501.31 | 16.26 | 0.00 | 0.00 | 0.00 |
October | 497.67 | 162.59 | 335.08 | 1171.16 | 75.31 | 0.00 | 0.00 | 0.00 |
November | 417.05 | 132.10 | 284.95 | 806.91 | 213.14 | 0.00 | 0.00 | 0.00 |
December | 337.56 | 92.61 | 244.95 | 503.26 | 382.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 500.22 | 149.18 | 351.04 | 1167.06 | 172.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 337.56 | 92.61 | 244.95 | 503.26 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 623.29 | 198.58 | 424.71 | 1857.07 | 463.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1019.82 | 479.46 | 540.35 | 1608.78 | 716.82 | 0.00 | 0.00 | 0.00 |
February | 957.65 | 391.72 | 565.93 | 1612.83 | 611.40 | 0.00 | 0.00 | 0.00 |
March | 788.19 | 213.99 | 574.20 | 1491.75 | 472.65 | 0.00 | 0.00 | 0.00 |
April | 619.58 | 65.69 | 553.89 | 1398.41 | 295.21 | 0.00 | 0.00 | 0.00 |
May | 524.83 | 8.04 | 516.80 | 1595.95 | 73.21 | 0.00 | 0.00 | 0.00 |
June | 494.27 | 0.61 | 493.66 | 1698.73 | 14.72 | 0.00 | 0.00 | 0.00 |
July | 494.26 | 4.20 | 490.06 | 2009.33 | 0.25 | 0.00 | 0.00 | 0.00 |
August | 573.30 | 40.62 | 532.68 | 2250.05 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 755.91 | 173.24 | 582.67 | 2215.23 | 26.87 | 0.00 | 0.00 | 0.00 |
October | 989.63 | 393.43 | 596.20 | 2292.87 | 121.31 | 0.00 | 0.00 | 0.00 |
November | 1091.76 | 526.31 | 565.45 | 2121.72 | 335.90 | 0.00 | 0.00 | 0.00 |
December | 1013.48 | 500.63 | 512.85 | 1710.04 | 594.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 775.80 | 232.32 | 543.49 | 1835.35 | 270.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 494.26 | 0.61 | 490.06 | 1398.41 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1091.76 | 526.31 | 596.20 | 2292.87 | 716.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 373.20 | 107.19 | 266.01 | 532.79 | 497.73 | 0.00 | 0.00 | 0.00 |
February | 426.15 | 121.52 | 304.63 | 674.38 | 414.92 | 0.00 | 0.00 | 0.00 |
March | 504.79 | 149.44 | 355.35 | 908.84 | 317.38 | 0.00 | 0.00 | 0.00 |
April | 551.65 | 154.98 | 396.67 | 1154.44 | 203.27 | 0.00 | 0.00 | 0.00 |
May | 600.47 | 179.74 | 420.72 | 1538.10 | 54.23 | 0.00 | 0.00 | 0.00 |
June | 620.53 | 195.61 | 424.92 | 1689.90 | 12.66 | 0.00 | 0.00 | 0.00 |
July | 569.27 | 162.86 | 406.41 | 1797.10 | 0.29 | 0.00 | 0.00 | 0.00 |
August | 584.01 | 177.56 | 406.45 | 1851.67 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 555.54 | 174.54 | 381.01 | 1517.11 | 20.01 | 0.00 | 0.00 | 0.00 |
October | 493.72 | 159.48 | 334.23 | 1174.54 | 87.24 | 0.00 | 0.00 | 0.00 |
November | 424.29 | 138.76 | 285.53 | 846.20 | 232.70 | 0.00 | 0.00 | 0.00 |
December | 355.19 | 107.37 | 247.83 | 567.22 | 408.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.19 | 152.53 | 352.66 | 1190.66 | 186.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 355.19 | 107.19 | 247.83 | 532.79 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.53 | 195.61 | 424.92 | 1851.67 | 497.73 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.975336E+09 | 0.183873E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.121087E+10 | 0.139659E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.192841E+10 | 0.117793E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.270618E+10 | 0.719845E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.425308E+10 | 0.191038E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.476417E+10 | 47581801.18 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.550154E+10 | 1357718.96 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.542971E+10 | 264906.11 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.394414E+10 | 68487654.36 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.291483E+10 | 0.311816E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.178852E+10 | 0.820556E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.109408E+10 | 0.150502E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.365109E+11 | 0.807922E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.975336E+09 | 264906.11 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.550154E+10 | 0.183873E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.140747E+10 | 0.116002E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.153525E+10 | 0.888606E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.216623E+10 | 0.754454E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.299681E+10 | 0.465661E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.419413E+10 | 0.121914E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.429162E+10 | 28469883.43 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.479511E+10 | 752761.45 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.495774E+10 | 114096.42 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.388236E+10 | 41145597.48 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.313565E+10 | 0.192652E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.210336E+10 | 0.521279E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.137646E+10 | 0.958770E+09 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368422E+11 | 0.513384E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.137646E+10 | 114096.42 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.495774E+10 | 0.116002E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.433734E+10 | 0.179848E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.391094E+10 | 0.139479E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.399067E+10 | 0.120319E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.360640E+10 | 0.736918E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.424036E+10 | 0.192590E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.436897E+10 | 38438875.51 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.533348E+10 | 709514.91 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.598392E+10 | 163232.17 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.570956E+10 | 68415006.48 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.611783E+10 | 0.312232E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.549492E+10 | 0.823960E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.459786E+10 | 0.149946E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.576922E+11 | 0.806935E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.360640E+10 | 163232.17 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.611783E+10 | 0.179848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.144401E+10 | 0.123852E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.163795E+10 | 0.942434E+09 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.243012E+10 | 0.807084E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.297846E+10 | 0.507972E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.409516E+10 | 0.143101E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.435582E+10 | 33129537.83 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.478079E+10 | 838636.81 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.492953E+10 | 260517.12 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.391178E+10 | 51320145.40 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.313291E+10 | 0.225064E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219180E+10 | 0.568440E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.153049E+10 | 0.102242E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.374188E+11 | 0.554058E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.144401E+10 | 260517.12 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.492953E+10 | 0.123852E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281707E+09 | 0.00 | 0.281707E+09 | 0.308547E+09 | 0.695364E+09 |
February | 0.291667E+09 | 0.00 | 0.291667E+09 | 0.398051E+09 | 0.510944E+09 |
March | 0.370914E+09 | 0.00 | 0.370914E+09 | 0.648194E+09 | 0.412602E+09 |
April | 0.404418E+09 | 833282.96 | 0.403585E+09 | 0.915235E+09 | 0.240712E+09 |
May | 0.470382E+09 | 13796024.38 | 0.456586E+09 | 0.142995E+10 | 60576145.39 |
June | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.159350E+10 | 15165913.54 |
July | 0.462133E+09 | 13315161.00 | 0.448818E+09 | 0.183458E+10 | 437977.57 |
August | 0.430206E+09 | 3558230.40 | 0.426648E+09 | 0.179658E+10 | 86206.03 |
September | 0.379237E+09 | 43457.08 | 0.379193E+09 | 0.129848E+10 | 27280681.77 |
October | 0.347392E+09 | 0.00 | 0.347392E+09 | 0.952929E+09 | 0.122588E+09 |
November | 0.288608E+09 | 0.00 | 0.288608E+09 | 0.578564E+09 | 0.317687E+09 |
December | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.346803E+09 | 0.577929E+09 |
Annual Sum or Average | 0.447699E+10 | 58604415.66 | 0.441838E+10 | 0.121014E+11 | 0.298137E+10 |
Minimum of Months | 0.262937E+09 | 0.00 | 0.262937E+09 | 0.308547E+09 | 86206.03 |
Maximum of Months | 0.487387E+09 | 27058259.84 | 0.460329E+09 | 0.183458E+10 | 0.695364E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.308557E+09 | 0.695402E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.398066E+09 | 0.510972E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.648223E+09 | 0.412622E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.915280E+09 | 0.240722E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143002E+10 | 60577415.70 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159358E+10 | 15165545.54 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183469E+10 | 437926.31 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.179669E+10 | 86183.03 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.129856E+10 | 27280915.90 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.952981E+09 | 0.122592E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.578593E+09 | 0.317701E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.346816E+09 | 0.577960E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121021E+11 | 0.298152E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.308557E+09 | 86183.03 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183469E+10 | 0.695402E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.281718E+09 | 0.00 | 0.281718E+09 | 0.308557E+09 | 0.695402E+09 |
February | 0.291678E+09 | 0.00 | 0.291678E+09 | 0.398066E+09 | 0.510972E+09 |
March | 0.370928E+09 | 0.00 | 0.370928E+09 | 0.648223E+09 | 0.412622E+09 |
April | 0.404434E+09 | 833305.35 | 0.403601E+09 | 0.915280E+09 | 0.240722E+09 |
May | 0.470401E+09 | 13796395.22 | 0.456604E+09 | 0.143002E+10 | 60577415.70 |
June | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.159358E+10 | 15165545.54 |
July | 0.462151E+09 | 13315518.92 | 0.448835E+09 | 0.183469E+10 | 437926.31 |
August | 0.430223E+09 | 3558326.05 | 0.426665E+09 | 0.179669E+10 | 86183.03 |
September | 0.379252E+09 | 43458.25 | 0.379209E+09 | 0.129856E+10 | 27280915.90 |
October | 0.347405E+09 | 0.00 | 0.347405E+09 | 0.952981E+09 | 0.122592E+09 |
November | 0.288619E+09 | 0.00 | 0.288619E+09 | 0.578593E+09 | 0.317701E+09 |
December | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.346816E+09 | 0.577960E+09 |
Annual Sum or Average | 0.447716E+10 | 58605990.96 | 0.441856E+10 | 0.121021E+11 | 0.298152E+10 |
Minimum of Months | 0.262947E+09 | 0.00 | 0.262947E+09 | 0.308557E+09 | 86183.03 |
Maximum of Months | 0.487406E+09 | 27058987.17 | 0.460347E+09 | 0.183469E+10 | 0.695402E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.980477E+09 | 0.296641E+09 | 0.683836E+09 | 0.131416E+10 | 0.126388E+10 |
February | 0.965092E+09 | 0.261544E+09 | 0.703548E+09 | 0.146469E+10 | 0.942056E+09 |
March | 0.118026E+10 | 0.290890E+09 | 0.889372E+09 | 0.209534E+10 | 0.770450E+09 |
April | 0.139066E+10 | 0.405192E+09 | 0.985471E+09 | 0.291023E+10 | 0.461780E+09 |
May | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.405966E+10 | 0.119414E+09 |
June | 0.152201E+10 | 0.465444E+09 | 0.105656E+10 | 0.414009E+10 | 29376733.54 |
July | 0.146791E+10 | 0.423193E+09 | 0.104472E+10 | 0.461305E+10 | 902655.78 |
August | 0.150311E+10 | 0.461324E+09 | 0.104179E+10 | 0.474196E+10 | 175988.35 |
September | 0.136752E+10 | 0.422681E+09 | 0.944836E+09 | 0.370480E+10 | 51506156.31 |
October | 0.128225E+10 | 0.418909E+09 | 0.863339E+09 | 0.298691E+10 | 0.231374E+09 |
November | 0.103987E+10 | 0.329375E+09 | 0.710490E+09 | 0.199236E+10 | 0.591738E+09 |
December | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.128464E+10 | 0.106031E+10 |
Annual Sum or Average | 0.151748E+11 | 0.452546E+10 | 0.106493E+11 | 0.353079E+11 | 0.552296E+10 |
Minimum of Months | 0.869726E+09 | 0.238617E+09 | 0.631110E+09 | 0.128464E+10 | 175988.35 |
Maximum of Months | 0.160591E+10 | 0.511648E+09 | 0.109426E+10 | 0.474196E+10 | 0.126388E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38767169.86 | 11728917.87 | 27038251.99 | 51960542.28 | 49972637.20 |
February | 38158864.13 | 10341197.48 | 27817666.66 | 57912577.31 | 37248058.44 |
March | 46666517.65 | 11501534.46 | 35164983.19 | 82847796.09 | 30462897.86 |
April | 54985543.05 | 16020907.39 | 38964635.67 | 0.115068E+09 | 18258380.45 |
May | 63496079.79 | 20230091.31 | 43265988.49 | 0.160515E+09 | 4721515.90 |
June | 60178723.78 | 18403232.06 | 41775491.72 | 0.163696E+09 | 1161529.60 |
July | 58039777.31 | 16732677.45 | 41307099.86 | 0.182396E+09 | 35690.20 |
August | 59431730.36 | 18240318.79 | 41191411.57 | 0.187493E+09 | 6958.42 |
September | 54070390.91 | 16712442.13 | 37357948.79 | 0.146485E+09 | 2036507.05 |
October | 50698923.30 | 16563295.94 | 34135627.36 | 0.118100E+09 | 9148316.72 |
November | 41115338.64 | 13023186.67 | 28092151.97 | 78776292.97 | 23396779.02 |
December | 34388199.46 | 9434693.58 | 24953505.89 | 50793692.04 | 41923650.34 |
Annual Sum or Average | 0.599997E+09 | 0.178932E+09 | 0.421065E+09 | 0.139604E+10 | 0.218373E+09 |
Minimum of Months | 34388199.46 | 9434693.58 | 24953505.89 | 50793692.04 | 6958.42 |
Maximum of Months | 63496079.79 | 20230091.31 | 43265988.49 | 0.187493E+09 | 49972637.20 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.143899E+10 | 0.681179E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.130711E+10 | 0.516169E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134030E+10 | 0.426141E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121439E+10 | 0.250072E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141475E+10 | 63503080.30 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144501E+10 | 13514141.50 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176050E+10 | 281494.11 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.195537E+10 | 120304.50 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187068E+10 | 30652508.61 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201595E+10 | 0.134642E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182035E+10 | 0.331058E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152472E+10 | 0.577071E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191081E+11 | 0.302440E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121439E+10 | 120304.50 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201595E+10 | 0.681179E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910476E+09 | 0.428054E+09 | 0.482421E+09 | 0.143899E+10 | 0.681179E+09 |
February | 0.772236E+09 | 0.315877E+09 | 0.456359E+09 | 0.130711E+10 | 0.516169E+09 |
March | 0.703685E+09 | 0.191046E+09 | 0.512640E+09 | 0.134030E+10 | 0.426141E+09 |
April | 0.535307E+09 | 56752191.30 | 0.478555E+09 | 0.121439E+10 | 0.250072E+09 |
May | 0.468568E+09 | 7175566.92 | 0.461393E+09 | 0.141475E+10 | 63503080.30 |
June | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.144501E+10 | 13514141.50 |
July | 0.441272E+09 | 3749415.45 | 0.437522E+09 | 0.176050E+10 | 281494.11 |
August | 0.511839E+09 | 36265474.26 | 0.475574E+09 | 0.195537E+10 | 120304.50 |
September | 0.653094E+09 | 0.149674E+09 | 0.503419E+09 | 0.187068E+10 | 30652508.61 |
October | 0.883526E+09 | 0.351250E+09 | 0.532276E+09 | 0.201595E+10 | 0.134642E+09 |
November | 0.943266E+09 | 0.454723E+09 | 0.488543E+09 | 0.182035E+10 | 0.331058E+09 |
December | 0.904824E+09 | 0.446954E+09 | 0.457870E+09 | 0.152472E+10 | 0.577071E+09 |
Annual Sum or Average | 0.815514E+10 | 0.244205E+10 | 0.571309E+10 | 0.191081E+11 | 0.302440E+10 |
Minimum of Months | 0.427049E+09 | 528482.05 | 0.426520E+09 | 0.121439E+10 | 120304.50 |
Maximum of Months | 0.943266E+09 | 0.454723E+09 | 0.532276E+09 | 0.201595E+10 | 0.681179E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.910418E+09 | 0.428027E+09 | 0.482391E+09 | 0.143890E+10 | 0.681136E+09 |
February | 0.772188E+09 | 0.315857E+09 | 0.456330E+09 | 0.130703E+10 | 0.516136E+09 |
March | 0.703641E+09 | 0.191033E+09 | 0.512607E+09 | 0.134021E+10 | 0.426114E+09 |
April | 0.535274E+09 | 56748604.88 | 0.478525E+09 | 0.121432E+10 | 0.250056E+09 |
May | 0.468539E+09 | 7175113.46 | 0.461363E+09 | 0.141466E+10 | 63499067.27 |
June | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.144492E+10 | 13513287.48 |
July | 0.441244E+09 | 3749178.51 | 0.437495E+09 | 0.176039E+10 | 281476.32 |
August | 0.511807E+09 | 36263182.48 | 0.475544E+09 | 0.195524E+10 | 120296.90 |
September | 0.653053E+09 | 0.149665E+09 | 0.503388E+09 | 0.187056E+10 | 30650571.55 |
October | 0.883470E+09 | 0.351228E+09 | 0.532243E+09 | 0.201582E+10 | 0.134633E+09 |
November | 0.943206E+09 | 0.454694E+09 | 0.488512E+09 | 0.182023E+10 | 0.331037E+09 |
December | 0.904767E+09 | 0.446926E+09 | 0.457841E+09 | 0.152462E+10 | 0.577035E+09 |
Annual Sum or Average | 0.815463E+10 | 0.244189E+10 | 0.571273E+10 | 0.191069E+11 | 0.302421E+10 |
Minimum of Months | 0.427022E+09 | 528448.65 | 0.426494E+09 | 0.121432E+10 | 120296.90 |
Maximum of Months | 0.943206E+09 | 0.454694E+09 | 0.532243E+09 | 0.201582E+10 | 0.681136E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961538E+09 | 0.276161E+09 | 0.685377E+09 | 0.136503E+10 | 0.136099E+10 |
February | 0.991722E+09 | 0.282798E+09 | 0.708924E+09 | 0.157296E+10 | 0.100601E+10 |
March | 0.130059E+10 | 0.385041E+09 | 0.915547E+09 | 0.235773E+10 | 0.830642E+09 |
April | 0.137547E+10 | 0.386432E+09 | 0.989039E+09 | 0.289687E+10 | 0.505264E+09 |
May | 0.154710E+10 | 0.463108E+09 | 0.108399E+10 | 0.396360E+10 | 0.140536E+09 |
June | 0.154723E+10 | 0.487725E+09 | 0.105950E+10 | 0.419624E+10 | 35019255.55 |
July | 0.146673E+10 | 0.419600E+09 | 0.104713E+10 | 0.459767E+10 | 1173319.43 |
August | 0.150470E+10 | 0.457491E+09 | 0.104721E+10 | 0.471619E+10 | 365772.15 |
September | 0.138518E+10 | 0.435183E+09 | 0.950000E+09 | 0.373445E+10 | 62943687.98 |
October | 0.127205E+10 | 0.410907E+09 | 0.861147E+09 | 0.298606E+10 | 0.264776E+09 |
November | 0.105791E+10 | 0.345969E+09 | 0.711940E+09 | 0.208373E+10 | 0.646738E+09 |
December | 0.915157E+09 | 0.276635E+09 | 0.638522E+09 | 0.144634E+10 | 0.113790E+10 |
Annual Sum or Average | 0.153254E+11 | 0.462705E+10 | 0.106983E+11 | 0.359169E+11 | 0.599236E+10 |
Minimum of Months | 0.915157E+09 | 0.276161E+09 | 0.638522E+09 | 0.136503E+10 | 365772.15 |
Maximum of Months | 0.154723E+10 | 0.487725E+09 | 0.108399E+10 | 0.471619E+10 | 0.136099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38018247.76 | 10919117.73 | 27099130.02 | 53971921.78 | 53812384.05 |
February | 39211705.00 | 11181551.15 | 28030153.85 | 62193193.07 | 39776509.20 |
March | 51423957.87 | 15224122.20 | 36199835.67 | 93222277.51 | 32842808.66 |
April | 54384761.88 | 15279138.20 | 39105623.68 | 0.114539E+09 | 19977665.04 |
May | 61170809.08 | 18310794.40 | 42860014.69 | 0.156717E+09 | 5556666.42 |
June | 61175738.81 | 19284136.55 | 41891602.26 | 0.165915E+09 | 1384620.11 |
July | 57992905.15 | 16590541.44 | 41402363.71 | 0.181787E+09 | 46390.99 |
August | 59494269.60 | 18088714.83 | 41405554.77 | 0.186474E+09 | 14461.97 |
September | 54768728.67 | 17206686.11 | 37562042.56 | 0.147657E+09 | 2488724.83 |
October | 50295743.05 | 16246847.94 | 34048895.11 | 0.118066E+09 | 10468979.37 |
November | 41828685.86 | 13679270.35 | 28149415.51 | 82388610.93 | 25571403.24 |
December | 36184378.39 | 10937853.43 | 25246524.96 | 57186802.53 | 44991508.17 |
Annual Sum or Average | 0.605950E+09 | 0.182949E+09 | 0.423001E+09 | 0.142012E+10 | 0.236932E+09 |
Minimum of Months | 36184378.39 | 10919117.73 | 25246524.96 | 53971921.78 | 14461.97 |
Maximum of Months | 61175738.81 | 19284136.55 | 42860014.69 | 0.186474E+09 | 53812384.05 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.943849E+09 | 0.198571E+10 |
February | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.119531E+10 | 0.149157E+10 |
March | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.192763E+10 | 0.124348E+10 |
April | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.272237E+10 | 0.747264E+09 |
May | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.428585E+10 | 0.193168E+09 |
June | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.479898E+10 | 46561143.76 |
July | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.554826E+10 | 1220641.48 |
August | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.547012E+10 | 182039.02 |
September | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.397109E+10 | 69497321.94 |
October | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.292914E+10 | 0.325051E+09 |
November | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.178560E+10 | 0.873137E+09 |
December | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.107084E+10 | 0.161802E+10 |
Annual Sum or Average | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.366490E+11 | 0.859486E+10 |
Minimum of Months | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.943849E+09 | 182039.02 |
Maximum of Months | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.554826E+10 | 0.198571E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.137109E+10 | 0.124113E+10 |
February | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.151321E+10 | 0.942783E+09 |
March | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.215347E+10 | 0.793333E+09 |
April | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.299718E+10 | 0.482746E+09 |
May | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.420690E+10 | 0.124044E+09 |
June | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.430502E+10 | 28261778.03 |
July | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.481592E+10 | 694874.04 |
August | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.497398E+10 | 74593.33 |
September | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.389140E+10 | 42140343.85 |
October | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.313682E+10 | 0.201711E+09 |
November | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.209152E+10 | 0.552459E+09 |
December | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.134792E+10 | 0.102317E+10 |
Annual Sum or Average | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.368044E+11 | 0.543255E+10 |
Minimum of Months | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.134792E+10 | 74593.33 |
Maximum of Months | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.497398E+10 | 0.124113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.430897E+10 | 0.191993E+10 |
February | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.390175E+10 | 0.147910E+10 |
March | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.399550E+10 | 0.126594E+10 |
April | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.362468E+10 | 0.765192E+09 |
May | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.427459E+10 | 0.196088E+09 |
June | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.440312E+10 | 38158663.18 |
July | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.538178E+10 | 657091.56 |
August | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.602654E+10 | 97753.06 |
September | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.574188E+10 | 69659564.45 |
October | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.614123E+10 | 0.324907E+09 |
November | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.549949E+10 | 0.870661E+09 |
December | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.458016E+10 | 0.159276E+10 |
Annual Sum or Average | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.578797E+11 | 0.852315E+10 |
Minimum of Months | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.362468E+10 | 97753.06 |
Maximum of Months | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.614123E+10 | 0.191993E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.142702E+10 | 0.133311E+10 |
February | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.163146E+10 | 0.100379E+10 |
March | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.243422E+10 | 0.850083E+09 |
April | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.299232E+10 | 0.526878E+09 |
May | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.411965E+10 | 0.145241E+09 |
June | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.438023E+10 | 32805575.60 |
July | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.481336E+10 | 764875.36 |
August | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.495951E+10 | 213464.01 |
September | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.393235E+10 | 51869142.98 |
October | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.314589E+10 | 0.233670E+09 |
November | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.219334E+10 | 0.603165E+09 |
December | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.151924E+10 | 0.109444E+10 |
Annual Sum or Average | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.375486E+11 | 0.587603E+10 |
Minimum of Months | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.142702E+10 | 213464.01 |
Maximum of Months | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.495951E+10 | 0.133311E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 364.15 | 686.50 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 500.52 | 577.30 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 719.99 | 439.79 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1044.05 | 277.72 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1587.92 | 71.33 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1838.03 | 18.36 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2054.04 | 0.51 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2027.22 | 0.10 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1521.66 | 26.42 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1088.27 | 116.42 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 690.01 | 316.57 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 408.48 | 561.91 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1157.75 | 256.19 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 364.15 | 0.10 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2054.04 | 686.50 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 525.49 | 433.10 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 634.61 | 367.31 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 808.78 | 281.68 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1156.18 | 179.65 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1565.91 | 45.52 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1655.72 | 10.98 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1790.29 | 0.28 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1851.01 | 0.04 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1497.83 | 15.87 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1170.72 | 71.93 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 811.48 | 201.11 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 513.91 | 357.96 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1168.26 | 162.79 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 513.91 | 0.04 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1851.01 | 433.10 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1619.38 | 671.48 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1616.62 | 576.55 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1489.95 | 449.22 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1391.36 | 284.30 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1583.17 | 71.90 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1685.56 | 14.83 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 1991.29 | 0.26 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2234.14 | 0.06 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2202.76 | 26.39 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2284.14 | 116.57 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2119.96 | 317.89 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1716.64 | 559.83 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1829.41 | 255.88 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1391.36 | 0.06 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2284.14 | 671.48 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 539.13 | 462.41 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 677.06 | 389.56 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 907.30 | 301.33 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1149.10 | 195.98 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1528.96 | 53.43 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1680.49 | 12.78 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1784.94 | 0.31 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1840.47 | 0.10 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1509.17 | 19.80 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1169.69 | 84.03 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 845.60 | 219.31 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 571.42 | 381.73 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1186.54 | 175.69 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 539.13 | 0.10 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1840.47 | 462.41 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 345.60 | 778.89 | 315.54 | 0.00 | 315.54 | 0.00 | 0.00 |
February | 493.63 | 633.63 | 361.70 | 0.00 | 361.70 | 0.00 | 0.00 |
March | 726.05 | 462.16 | 415.46 | 0.00 | 415.46 | 0.00 | 0.00 |
April | 1059.33 | 278.61 | 468.09 | 0.96 | 467.12 | 0.00 | 0.00 |
May | 1601.70 | 67.85 | 526.88 | 15.45 | 511.42 | 0.00 | 0.00 |
June | 1844.39 | 17.55 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
July | 2054.94 | 0.49 | 517.64 | 14.91 | 502.72 | 0.00 | 0.00 |
August | 2012.38 | 0.10 | 481.87 | 3.99 | 477.89 | 0.00 | 0.00 |
September | 1502.93 | 31.58 | 438.94 | 0.05 | 438.89 | 0.00 | 0.00 |
October | 1067.39 | 137.31 | 389.11 | 0.00 | 389.11 | 0.00 | 0.00 |
November | 669.66 | 367.70 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 388.45 | 647.35 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1151.24 | 283.63 | 425.90 | 5.58 | 420.33 | 0.00 | 0.00 |
Minimum of Months | 345.60 | 0.10 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2054.94 | 778.89 | 564.12 | 31.32 | 532.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 510.05 | 490.54 | 380.54 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 629.38 | 404.81 | 414.70 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 813.24 | 299.03 | 458.08 | 112.90 | 345.18 | 0.00 | 0.00 |
April | 1167.17 | 185.20 | 557.73 | 162.50 | 395.23 | 0.00 | 0.00 |
May | 1575.63 | 46.35 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
June | 1660.41 | 11.78 | 610.41 | 186.67 | 423.74 | 0.00 | 0.00 |
July | 1790.41 | 0.35 | 569.72 | 164.25 | 405.47 | 0.00 | 0.00 |
August | 1840.45 | 0.07 | 583.39 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1485.84 | 20.66 | 548.45 | 169.52 | 378.93 | 0.00 | 0.00 |
October | 1159.28 | 89.80 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 799.05 | 237.32 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 498.60 | 411.53 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1163.87 | 182.06 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 498.60 | 0.07 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1840.45 | 490.54 | 623.28 | 198.58 | 424.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1611.74 | 762.95 | 1019.78 | 479.44 | 540.34 | 0.00 | 0.00 |
February | 1620.89 | 640.08 | 957.61 | 391.70 | 565.91 | 0.00 | 0.00 |
March | 1501.20 | 477.30 | 788.16 | 213.98 | 574.18 | 0.00 | 0.00 |
April | 1405.52 | 289.43 | 619.56 | 65.68 | 553.87 | 0.00 | 0.00 |
May | 1584.59 | 71.13 | 524.82 | 8.04 | 516.78 | 0.00 | 0.00 |
June | 1672.43 | 15.64 | 494.26 | 0.61 | 493.65 | 0.00 | 0.00 |
July | 1971.84 | 0.32 | 494.25 | 4.20 | 490.05 | 0.00 | 0.00 |
August | 2190.11 | 0.13 | 573.28 | 40.62 | 532.67 | 0.00 | 0.00 |
September | 2165.09 | 35.48 | 755.88 | 173.23 | 582.65 | 0.00 | 0.00 |
October | 2257.96 | 150.81 | 989.59 | 393.42 | 596.18 | 0.00 | 0.00 |
November | 2106.84 | 383.16 | 1091.72 | 526.29 | 565.43 | 0.00 | 0.00 |
December | 1707.76 | 646.35 | 1013.45 | 500.61 | 512.84 | 0.00 | 0.00 |
Annual Sum or Average | 1817.70 | 287.70 | 775.78 | 232.31 | 543.47 | 0.00 | 0.00 |
Minimum of Months | 1405.52 | 0.13 | 494.25 | 0.61 | 490.05 | 0.00 | 0.00 |
Maximum of Months | 2257.96 | 762.95 | 1091.72 | 526.29 | 596.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 529.79 | 528.23 | 373.19 | 107.18 | 266.01 | 0.00 | 0.00 |
February | 675.91 | 432.28 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 915.08 | 322.39 | 504.78 | 149.44 | 355.34 | 0.00 | 0.00 |
April | 1161.81 | 202.64 | 551.64 | 154.98 | 396.66 | 0.00 | 0.00 |
May | 1538.35 | 54.54 | 600.46 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1682.93 | 14.04 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1784.44 | 0.46 | 569.27 | 162.85 | 406.41 | 0.00 | 0.00 |
August | 1830.44 | 0.14 | 584.00 | 177.56 | 406.44 | 0.00 | 0.00 |
September | 1497.73 | 25.24 | 555.54 | 174.53 | 381.00 | 0.00 | 0.00 |
October | 1158.95 | 102.76 | 493.71 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 835.69 | 259.38 | 424.28 | 138.75 | 285.53 | 0.00 | 0.00 |
December | 561.35 | 441.64 | 355.19 | 107.37 | 247.82 | 0.00 | 0.00 |
Annual Sum or Average | 1183.95 | 197.53 | 505.18 | 152.52 | 352.65 | 0.00 | 0.00 |
Minimum of Months | 529.79 | 0.14 | 355.19 | 107.18 | 247.82 | 0.00 | 0.00 |
Maximum of Months | 1830.44 | 528.23 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 352.39 | 741.38 | 315.55 | 0.00 | 315.55 | 0.00 | 0.00 |
February | 494.09 | 616.56 | 361.71 | 0.00 | 361.71 | 0.00 | 0.00 |
March | 719.70 | 464.26 | 415.47 | 0.00 | 415.47 | 0.00 | 0.00 |
April | 1050.30 | 288.30 | 468.10 | 0.96 | 467.13 | 0.00 | 0.00 |
May | 1600.15 | 72.12 | 526.89 | 15.45 | 511.43 | 0.00 | 0.00 |
June | 1851.46 | 17.96 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
July | 2071.48 | 0.46 | 517.65 | 14.91 | 502.73 | 0.00 | 0.00 |
August | 2042.31 | 0.07 | 481.88 | 3.99 | 477.90 | 0.00 | 0.00 |
September | 1532.06 | 26.81 | 438.95 | 0.05 | 438.90 | 0.00 | 0.00 |
October | 1093.61 | 121.36 | 389.12 | 0.00 | 389.12 | 0.00 | 0.00 |
November | 688.89 | 336.86 | 334.05 | 0.00 | 334.05 | 0.00 | 0.00 |
December | 399.81 | 604.10 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Annual Sum or Average | 1162.13 | 272.54 | 425.91 | 5.58 | 420.34 | 0.00 | 0.00 |
Minimum of Months | 352.39 | 0.07 | 294.52 | 0.00 | 294.52 | 0.00 | 0.00 |
Maximum of Months | 2071.48 | 741.38 | 564.13 | 31.32 | 532.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 511.90 | 463.39 | 380.55 | 115.13 | 265.41 | 0.00 | 0.00 |
February | 625.50 | 389.71 | 414.71 | 112.39 | 302.32 | 0.00 | 0.00 |
March | 804.01 | 296.20 | 458.09 | 112.90 | 345.19 | 0.00 | 0.00 |
April | 1156.32 | 186.24 | 557.74 | 162.51 | 395.23 | 0.00 | 0.00 |
May | 1570.68 | 46.31 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
June | 1660.89 | 10.90 | 610.42 | 186.67 | 423.75 | 0.00 | 0.00 |
July | 1798.06 | 0.26 | 569.73 | 164.25 | 405.48 | 0.00 | 0.00 |
August | 1857.07 | 0.03 | 583.40 | 179.05 | 404.34 | 0.00 | 0.00 |
September | 1501.31 | 16.26 | 548.46 | 169.52 | 378.94 | 0.00 | 0.00 |
October | 1171.16 | 75.31 | 497.67 | 162.59 | 335.08 | 0.00 | 0.00 |
November | 806.91 | 213.14 | 417.05 | 132.10 | 284.95 | 0.00 | 0.00 |
December | 503.26 | 382.01 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Annual Sum or Average | 1167.06 | 172.27 | 500.22 | 149.18 | 351.04 | 0.00 | 0.00 |
Minimum of Months | 503.26 | 0.03 | 337.56 | 92.61 | 244.95 | 0.00 | 0.00 |
Maximum of Months | 1857.07 | 463.39 | 623.29 | 198.58 | 424.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1608.78 | 716.82 | 1019.82 | 479.46 | 540.35 | 0.00 | 0.00 |
February | 1612.83 | 611.40 | 957.65 | 391.72 | 565.93 | 0.00 | 0.00 |
March | 1491.75 | 472.65 | 788.19 | 213.99 | 574.20 | 0.00 | 0.00 |
April | 1398.41 | 295.21 | 619.58 | 65.69 | 553.89 | 0.00 | 0.00 |
May | 1595.95 | 73.21 | 524.83 | 8.04 | 516.80 | 0.00 | 0.00 |
June | 1698.73 | 14.72 | 494.27 | 0.61 | 493.66 | 0.00 | 0.00 |
July | 2009.33 | 0.25 | 494.26 | 4.20 | 490.06 | 0.00 | 0.00 |
August | 2250.05 | 0.04 | 573.30 | 40.62 | 532.68 | 0.00 | 0.00 |
September | 2215.23 | 26.87 | 755.91 | 173.24 | 582.67 | 0.00 | 0.00 |
October | 2292.87 | 121.31 | 989.63 | 393.43 | 596.20 | 0.00 | 0.00 |
November | 2121.72 | 335.90 | 1091.76 | 526.31 | 565.45 | 0.00 | 0.00 |
December | 1710.04 | 594.67 | 1013.48 | 500.63 | 512.85 | 0.00 | 0.00 |
Annual Sum or Average | 1835.35 | 270.27 | 775.80 | 232.32 | 543.49 | 0.00 | 0.00 |
Minimum of Months | 1398.41 | 0.04 | 494.26 | 0.61 | 490.06 | 0.00 | 0.00 |
Maximum of Months | 2292.87 | 716.82 | 1091.76 | 526.31 | 596.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 532.79 | 497.73 | 373.20 | 107.19 | 266.01 | 0.00 | 0.00 |
February | 674.38 | 414.92 | 426.15 | 121.52 | 304.63 | 0.00 | 0.00 |
March | 908.84 | 317.38 | 504.79 | 149.44 | 355.35 | 0.00 | 0.00 |
April | 1154.44 | 203.27 | 551.65 | 154.98 | 396.67 | 0.00 | 0.00 |
May | 1538.10 | 54.23 | 600.47 | 179.74 | 420.72 | 0.00 | 0.00 |
June | 1689.90 | 12.66 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
July | 1797.10 | 0.29 | 569.27 | 162.86 | 406.41 | 0.00 | 0.00 |
August | 1851.67 | 0.08 | 584.01 | 177.56 | 406.45 | 0.00 | 0.00 |
September | 1517.11 | 20.01 | 555.54 | 174.54 | 381.01 | 0.00 | 0.00 |
October | 1174.54 | 87.24 | 493.72 | 159.48 | 334.23 | 0.00 | 0.00 |
November | 846.20 | 232.70 | 424.29 | 138.76 | 285.53 | 0.00 | 0.00 |
December | 567.22 | 408.62 | 355.19 | 107.37 | 247.83 | 0.00 | 0.00 |
Annual Sum or Average | 1190.66 | 186.33 | 505.19 | 152.53 | 352.66 | 0.00 | 0.00 |
Minimum of Months | 532.79 | 0.08 | 355.19 | 107.19 | 247.83 | 0.00 | 0.00 |
Maximum of Months | 1851.67 | 497.73 | 620.53 | 195.61 | 424.92 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.975336E+09 | 0.183873E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.121087E+10 | 0.139659E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.192841E+10 | 0.117793E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.270618E+10 | 0.719845E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.425308E+10 | 0.191038E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.476417E+10 | 47581801.18 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.550154E+10 | 1357718.96 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.542971E+10 | 264906.11 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.394414E+10 | 68487654.36 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.291483E+10 | 0.311816E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.178852E+10 | 0.820556E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.109408E+10 | 0.150502E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.365109E+11 | 0.807922E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.975336E+09 | 264906.11 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550154E+10 | 0.183873E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.140747E+10 | 0.116002E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.153525E+10 | 0.888606E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.216623E+10 | 0.754454E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.299681E+10 | 0.465661E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.419413E+10 | 0.121914E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.429162E+10 | 28469883.43 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.479511E+10 | 752761.45 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.495774E+10 | 114096.42 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.388236E+10 | 41145597.48 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.313565E+10 | 0.192652E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.210336E+10 | 0.521279E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.137646E+10 | 0.958770E+09 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368422E+11 | 0.513384E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137646E+10 | 114096.42 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495774E+10 | 0.116002E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433734E+10 | 0.179848E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.391094E+10 | 0.139479E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.399067E+10 | 0.120319E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.360640E+10 | 0.736918E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.424036E+10 | 0.192590E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.436897E+10 | 38438875.51 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.533348E+10 | 709514.91 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.598392E+10 | 163232.17 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.570956E+10 | 68415006.48 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.611783E+10 | 0.312232E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.549492E+10 | 0.823960E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.459786E+10 | 0.149946E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.576922E+11 | 0.806935E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.360640E+10 | 163232.17 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611783E+10 | 0.179848E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144401E+10 | 0.123852E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.163795E+10 | 0.942434E+09 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.243012E+10 | 0.807084E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.297846E+10 | 0.507972E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.409516E+10 | 0.143101E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.435582E+10 | 33129537.83 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.478079E+10 | 838636.81 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.492953E+10 | 260517.12 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.391178E+10 | 51320145.40 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.313291E+10 | 0.225064E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219180E+10 | 0.568440E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.153049E+10 | 0.102242E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.374188E+11 | 0.554058E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144401E+10 | 260517.12 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492953E+10 | 0.123852E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.925661E+09 | 0.208617E+10 | 0.845143E+09 | 0.00 | 0.845143E+09 | 0.00 | 0.00 |
February | 0.119418E+10 | 0.153289E+10 | 0.875023E+09 | 0.00 | 0.875023E+09 | 0.00 | 0.00 |
March | 0.194464E+10 | 0.123785E+10 | 0.111277E+10 | 0.00 | 0.111277E+10 | 0.00 | 0.00 |
April | 0.274579E+10 | 0.722157E+09 | 0.121329E+10 | 2499893.67 | 0.121079E+10 | 0.00 | 0.00 |
May | 0.428999E+10 | 0.181731E+09 | 0.141118E+10 | 41388814.81 | 0.136979E+10 | 0.00 | 0.00 |
June | 0.478066E+10 | 45497004.62 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
July | 0.550395E+10 | 1313830.19 | 0.138643E+10 | 39946198.84 | 0.134649E+10 | 0.00 | 0.00 |
August | 0.538996E+10 | 258572.09 | 0.129065E+10 | 10674882.49 | 0.127998E+10 | 0.00 | 0.00 |
September | 0.389559E+10 | 81842513.57 | 0.113774E+10 | 130373.59 | 0.113761E+10 | 0.00 | 0.00 |
October | 0.285889E+10 | 0.367773E+09 | 0.104220E+10 | 0.00 | 0.104220E+10 | 0.00 | 0.00 |
November | 0.173575E+10 | 0.953088E+09 | 0.865846E+09 | 0.00 | 0.865846E+09 | 0.00 | 0.00 |
December | 0.104043E+10 | 0.173385E+10 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.363055E+11 | 0.894441E+10 | 0.134313E+11 | 0.175816E+09 | 0.132555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.925661E+09 | 258572.09 | 0.788831E+09 | 0.00 | 0.788831E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550395E+10 | 0.208617E+10 | 0.146220E+10 | 81176234.19 | 0.138102E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136612E+10 | 0.131385E+10 | 0.101924E+10 | 0.308370E+09 | 0.710874E+09 | 0.00 | 0.00 |
February | 0.152260E+10 | 0.979304E+09 | 0.100325E+10 | 0.271885E+09 | 0.731366E+09 | 0.00 | 0.00 |
March | 0.217819E+10 | 0.800913E+09 | 0.122693E+10 | 0.302392E+09 | 0.924537E+09 | 0.00 | 0.00 |
April | 0.302530E+10 | 0.480039E+09 | 0.144565E+10 | 0.421212E+09 | 0.102444E+10 | 0.00 | 0.00 |
May | 0.422018E+10 | 0.124135E+09 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
June | 0.430379E+10 | 30538263.14 | 0.158218E+10 | 0.483847E+09 | 0.109834E+10 | 0.00 | 0.00 |
July | 0.479545E+10 | 938345.98 | 0.152595E+10 | 0.439926E+09 | 0.108602E+10 | 0.00 | 0.00 |
August | 0.492946E+10 | 182946.77 | 0.156254E+10 | 0.479564E+09 | 0.108298E+10 | 0.00 | 0.00 |
September | 0.385129E+10 | 53542663.35 | 0.142159E+10 | 0.439394E+09 | 0.982194E+09 | 0.00 | 0.00 |
October | 0.310501E+10 | 0.240522E+09 | 0.133295E+10 | 0.435473E+09 | 0.897474E+09 | 0.00 | 0.00 |
November | 0.207114E+10 | 0.615135E+09 | 0.108098E+10 | 0.342398E+09 | 0.738583E+09 | 0.00 | 0.00 |
December | 0.133544E+10 | 0.110223E+10 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.367039E+11 | 0.574133E+10 | 0.157748E+11 | 0.470439E+10 | 0.110704E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133544E+10 | 182946.77 | 0.904115E+09 | 0.248051E+09 | 0.656063E+09 | 0.00 | 0.00 |
Maximum of Months | 0.492946E+10 | 0.131385E+10 | 0.166940E+10 | 0.531878E+09 | 0.113752E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431689E+10 | 0.204349E+10 | 0.273137E+10 | 0.128414E+10 | 0.144723E+10 | 0.00 | 0.00 |
February | 0.392125E+10 | 0.154847E+10 | 0.231666E+10 | 0.947611E+09 | 0.136905E+10 | 0.00 | 0.00 |
March | 0.402080E+10 | 0.127840E+10 | 0.211101E+10 | 0.573124E+09 | 0.153789E+10 | 0.00 | 0.00 |
April | 0.364310E+10 | 0.750199E+09 | 0.160589E+10 | 0.170253E+09 | 0.143564E+10 | 0.00 | 0.00 |
May | 0.424417E+10 | 0.190505E+09 | 0.140567E+10 | 21526247.30 | 0.138415E+10 | 0.00 | 0.00 |
June | 0.433494E+10 | 40541570.48 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
July | 0.528138E+10 | 844464.55 | 0.132379E+10 | 11248009.42 | 0.131254E+10 | 0.00 | 0.00 |
August | 0.586598E+10 | 360905.90 | 0.153548E+10 | 0.108794E+09 | 0.142669E+10 | 0.00 | 0.00 |
September | 0.561192E+10 | 91955588.77 | 0.195924E+10 | 0.449014E+09 | 0.151023E+10 | 0.00 | 0.00 |
October | 0.604772E+10 | 0.403917E+09 | 0.265052E+10 | 0.105373E+10 | 0.159680E+10 | 0.00 | 0.00 |
November | 0.546092E+10 | 0.993154E+09 | 0.282974E+10 | 0.136414E+10 | 0.146560E+10 | 0.00 | 0.00 |
December | 0.457406E+10 | 0.173118E+10 | 0.271441E+10 | 0.134083E+10 | 0.137358E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.573231E+11 | 0.907302E+10 | 0.244649E+11 | 0.732599E+10 | 0.171389E+11 | 0.00 | 0.00 |
Minimum of Months | 0.364310E+10 | 360905.90 | 0.128112E+10 | 1585412.74 | 0.127953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.604772E+10 | 0.204349E+10 | 0.282974E+10 | 0.136414E+10 | 0.159680E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.141900E+10 | 0.141481E+10 | 0.999556E+09 | 0.287080E+09 | 0.712476E+09 | 0.00 | 0.00 |
February | 0.163515E+10 | 0.104578E+10 | 0.103093E+10 | 0.293980E+09 | 0.736954E+09 | 0.00 | 0.00 |
March | 0.245095E+10 | 0.863485E+09 | 0.135201E+10 | 0.400265E+09 | 0.951747E+09 | 0.00 | 0.00 |
April | 0.301141E+10 | 0.525242E+09 | 0.142986E+10 | 0.401712E+09 | 0.102814E+10 | 0.00 | 0.00 |
May | 0.412032E+10 | 0.146093E+09 | 0.160827E+10 | 0.481418E+09 | 0.112685E+10 | 0.00 | 0.00 |
June | 0.436216E+10 | 36403875.66 | 0.160840E+10 | 0.507009E+09 | 0.110139E+10 | 0.00 | 0.00 |
July | 0.477945E+10 | 1219710.42 | 0.152472E+10 | 0.436190E+09 | 0.108853E+10 | 0.00 | 0.00 |
August | 0.490266E+10 | 380234.12 | 0.156419E+10 | 0.475579E+09 | 0.108861E+10 | 0.00 | 0.00 |
September | 0.388211E+10 | 65432412.80 | 0.143995E+10 | 0.452390E+09 | 0.987562E+09 | 0.00 | 0.00 |
October | 0.310412E+10 | 0.275245E+09 | 0.132235E+10 | 0.427154E+09 | 0.895196E+09 | 0.00 | 0.00 |
November | 0.216612E+10 | 0.672310E+09 | 0.109974E+10 | 0.359649E+09 | 0.740090E+09 | 0.00 | 0.00 |
December | 0.150353E+10 | 0.118289E+10 | 0.951341E+09 | 0.287573E+09 | 0.663769E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.373370E+11 | 0.622929E+10 | 0.159313E+11 | 0.481000E+10 | 0.111213E+11 | 0.00 | 0.00 |
Minimum of Months | 0.141900E+10 | 380234.12 | 0.951341E+09 | 0.287080E+09 | 0.663769E+09 | 0.00 | 0.00 |
Maximum of Months | 0.490266E+10 | 0.141481E+10 | 0.160840E+10 | 0.507009E+09 | 0.112685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.943849E+09 | 0.198571E+10 | 0.845162E+09 | 0.00 | 0.845162E+09 | 0.00 | 0.00 |
February | 0.119531E+10 | 0.149157E+10 | 0.875042E+09 | 0.00 | 0.875042E+09 | 0.00 | 0.00 |
March | 0.192763E+10 | 0.124348E+10 | 0.111279E+10 | 0.00 | 0.111279E+10 | 0.00 | 0.00 |
April | 0.272237E+10 | 0.747264E+09 | 0.121331E+10 | 2499967.15 | 0.121081E+10 | 0.00 | 0.00 |
May | 0.428585E+10 | 0.193168E+09 | 0.141121E+10 | 41390031.38 | 0.136982E+10 | 0.00 | 0.00 |
June | 0.479898E+10 | 46561143.76 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
July | 0.554826E+10 | 1220641.48 | 0.138646E+10 | 39947373.00 | 0.134652E+10 | 0.00 | 0.00 |
August | 0.547012E+10 | 182039.02 | 0.129068E+10 | 10675196.26 | 0.128000E+10 | 0.00 | 0.00 |
September | 0.397109E+10 | 69497321.94 | 0.113776E+10 | 130377.42 | 0.113763E+10 | 0.00 | 0.00 |
October | 0.292914E+10 | 0.325051E+09 | 0.104222E+10 | 0.00 | 0.104222E+10 | 0.00 | 0.00 |
November | 0.178560E+10 | 0.873137E+09 | 0.865865E+09 | 0.00 | 0.865865E+09 | 0.00 | 0.00 |
December | 0.107084E+10 | 0.161802E+10 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.366490E+11 | 0.859486E+10 | 0.134316E+11 | 0.175822E+09 | 0.132558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.943849E+09 | 182039.02 | 0.788849E+09 | 0.00 | 0.788849E+09 | 0.00 | 0.00 |
Maximum of Months | 0.554826E+10 | 0.198571E+10 | 0.146223E+10 | 81178620.25 | 0.138105E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137109E+10 | 0.124113E+10 | 0.101926E+10 | 0.308376E+09 | 0.710884E+09 | 0.00 | 0.00 |
February | 0.151321E+10 | 0.942783E+09 | 0.100327E+10 | 0.271890E+09 | 0.731376E+09 | 0.00 | 0.00 |
March | 0.215347E+10 | 0.793333E+09 | 0.122695E+10 | 0.302398E+09 | 0.924550E+09 | 0.00 | 0.00 |
April | 0.299718E+10 | 0.482746E+09 | 0.144567E+10 | 0.421221E+09 | 0.102445E+10 | 0.00 | 0.00 |
May | 0.420690E+10 | 0.124044E+09 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
June | 0.430502E+10 | 28261778.03 | 0.158221E+10 | 0.483857E+09 | 0.109835E+10 | 0.00 | 0.00 |
July | 0.481592E+10 | 694874.04 | 0.152597E+10 | 0.439934E+09 | 0.108604E+10 | 0.00 | 0.00 |
August | 0.497398E+10 | 74593.33 | 0.156257E+10 | 0.479573E+09 | 0.108299E+10 | 0.00 | 0.00 |
September | 0.389140E+10 | 42140343.85 | 0.142161E+10 | 0.439402E+09 | 0.982206E+09 | 0.00 | 0.00 |
October | 0.313682E+10 | 0.201711E+09 | 0.133297E+10 | 0.435481E+09 | 0.897486E+09 | 0.00 | 0.00 |
November | 0.209152E+10 | 0.552459E+09 | 0.108100E+10 | 0.342405E+09 | 0.738593E+09 | 0.00 | 0.00 |
December | 0.134792E+10 | 0.102317E+10 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.368044E+11 | 0.543255E+10 | 0.157750E+11 | 0.470448E+10 | 0.110705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134792E+10 | 74593.33 | 0.904128E+09 | 0.248056E+09 | 0.656072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.497398E+10 | 0.124113E+10 | 0.166943E+10 | 0.531888E+09 | 0.113754E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.430897E+10 | 0.191993E+10 | 0.273147E+10 | 0.128419E+10 | 0.144728E+10 | 0.00 | 0.00 |
February | 0.390175E+10 | 0.147910E+10 | 0.231675E+10 | 0.947651E+09 | 0.136910E+10 | 0.00 | 0.00 |
March | 0.399550E+10 | 0.126594E+10 | 0.211109E+10 | 0.573148E+09 | 0.153794E+10 | 0.00 | 0.00 |
April | 0.362468E+10 | 0.765192E+09 | 0.160594E+10 | 0.170260E+09 | 0.143568E+10 | 0.00 | 0.00 |
May | 0.427459E+10 | 0.196088E+09 | 0.140572E+10 | 21527140.62 | 0.138419E+10 | 0.00 | 0.00 |
June | 0.440312E+10 | 38158663.18 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
July | 0.538178E+10 | 657091.56 | 0.132383E+10 | 11248476.20 | 0.131258E+10 | 0.00 | 0.00 |
August | 0.602654E+10 | 97753.06 | 0.153553E+10 | 0.108799E+09 | 0.142673E+10 | 0.00 | 0.00 |
September | 0.574188E+10 | 69659564.45 | 0.195931E+10 | 0.449032E+09 | 0.151027E+10 | 0.00 | 0.00 |
October | 0.614123E+10 | 0.324907E+09 | 0.265062E+10 | 0.105377E+10 | 0.159685E+10 | 0.00 | 0.00 |
November | 0.549949E+10 | 0.870661E+09 | 0.282984E+10 | 0.136420E+10 | 0.146565E+10 | 0.00 | 0.00 |
December | 0.458016E+10 | 0.159276E+10 | 0.271452E+10 | 0.134089E+10 | 0.137363E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.578797E+11 | 0.852315E+10 | 0.244658E+11 | 0.732630E+10 | 0.171395E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362468E+10 | 97753.06 | 0.128116E+10 | 1585478.53 | 0.127957E+10 | 0.00 | 0.00 |
Maximum of Months | 0.614123E+10 | 0.191993E+10 | 0.282984E+10 | 0.136420E+10 | 0.159685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.142702E+10 | 0.133311E+10 | 0.999569E+09 | 0.287085E+09 | 0.712484E+09 | 0.00 | 0.00 |
February | 0.163146E+10 | 0.100379E+10 | 0.103095E+10 | 0.293985E+09 | 0.736963E+09 | 0.00 | 0.00 |
March | 0.243422E+10 | 0.850083E+09 | 0.135203E+10 | 0.400272E+09 | 0.951758E+09 | 0.00 | 0.00 |
April | 0.299232E+10 | 0.526878E+09 | 0.142987E+10 | 0.401718E+09 | 0.102816E+10 | 0.00 | 0.00 |
May | 0.411965E+10 | 0.145241E+09 | 0.160829E+10 | 0.481426E+09 | 0.112687E+10 | 0.00 | 0.00 |
June | 0.438023E+10 | 32805575.60 | 0.160842E+10 | 0.507017E+09 | 0.110140E+10 | 0.00 | 0.00 |
July | 0.481336E+10 | 764875.36 | 0.152474E+10 | 0.436197E+09 | 0.108854E+10 | 0.00 | 0.00 |
August | 0.495951E+10 | 213464.01 | 0.156421E+10 | 0.475587E+09 | 0.108862E+10 | 0.00 | 0.00 |
September | 0.393235E+10 | 51869142.98 | 0.143997E+10 | 0.452397E+09 | 0.987572E+09 | 0.00 | 0.00 |
October | 0.314589E+10 | 0.233670E+09 | 0.132237E+10 | 0.427161E+09 | 0.895206E+09 | 0.00 | 0.00 |
November | 0.219334E+10 | 0.603165E+09 | 0.109975E+10 | 0.359654E+09 | 0.740098E+09 | 0.00 | 0.00 |
December | 0.151924E+10 | 0.109444E+10 | 0.951354E+09 | 0.287577E+09 | 0.663776E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.375486E+11 | 0.587603E+10 | 0.159315E+11 | 0.481008E+10 | 0.111214E+11 | 0.00 | 0.00 |
Minimum of Months | 0.142702E+10 | 213464.01 | 0.951354E+09 | 0.287085E+09 | 0.663776E+09 | 0.00 | 0.00 |
Maximum of Months | 0.495951E+10 | 0.133311E+10 | 0.160842E+10 | 0.507017E+09 | 0.112687E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.354663E+10 | -0.331502E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231611881.7 | 60.05 | 0.00 | 0.00 |
February | 0.314014E+10 | -0.293107E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -209074300.9 | 60.05 | 0.00 | 0.00 |
March | 0.346323E+10 | -0.323128E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231952447.7 | 60.05 | 0.00 | 0.00 |
April | 0.284648E+10 | -0.262248E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223999890.5 | 60.05 | 0.00 | 0.00 |
May | 0.274830E+10 | -0.251643E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231874173.7 | 60.05 | 0.00 | 0.00 |
June | 0.250729E+10 | -0.228242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224865651.8 | 60.05 | 0.00 | 0.00 |
July | 0.231945E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -232897626.7 | 60.05 | 0.00 | 0.00 |
August | 0.264274E+10 | -0.240878E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -233956080.0 | 60.05 | 0.00 | 0.00 |
September | 0.261631E+10 | -0.239148E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -224825392.9 | 60.05 | 0.00 | 0.00 |
October | 0.299633E+10 | -0.276466E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231668203.7 | 60.05 | 0.00 | 0.00 |
November | 0.322363E+10 | -0.299995E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -223681979.5 | 60.05 | 0.00 | 0.00 |
December | 0.339588E+10 | -0.316457E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -231313383.4 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.354464E+11 | -0.327147E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.273172E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.231945E+10 | -0.331502E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -233956080.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.354663E+10 | -0.208655E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -209074300.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4165.40 | 34.10 | 310.83 | 292.67 | 1091.39 | 24.99 | 288.50 | 280.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2142.31 | 24.98 | 142.00 | 274.00 | 971.87 | 20.80 | 176.33 | 243.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1573.30 | 18.39 | 5.00 | 313.33 | 824.91 | 20.36 | 144.83 | 276.83 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1224.30 | 17.39 | 0.00 | 321.50 | 653.43 | 19.46 | 84.17 | 283.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1037.58 | 17.33 | 0.00 | 348.00 | 572.30 | 19.45 | 16.50 | 303.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 992.35 | 17.23 | 0.00 | 343.50 | 556.25 | 19.40 | 7.50 | 296.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1043.82 | 17.15 | 0.00 | 343.50 | 578.05 | 19.30 | 41.00 | 302.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1228.01 | 17.65 | 0.00 | 342.67 | 663.58 | 19.78 | 132.83 | 302.83 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1542.23 | 18.38 | 0.00 | 318.17 | 820.60 | 20.53 | 187.67 | 284.00 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2072.38 | 20.36 | 34.50 | 317.00 | 996.12 | 21.43 | 230.50 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3503.94 | 31.74 | 256.33 | 297.50 | 1130.97 | 24.83 | 300.33 | 282.00 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4154.16 | 34.47 | 307.00 | 288.50 | 1165.61 | 26.17 | 287.67 | 275.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1963.57 | 21.89 | 1055.67 | 3800.33 | 815.15 | 21.19 | 1897.83 | 3418.50 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 992.35 | 17.15 | 0.00 | 274.00 | 556.25 | 19.30 | 7.50 | 243.83 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4165.40 | 34.47 | 310.83 | 348.00 | 1165.61 | 26.17 | 300.33 | 303.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1512.95 | 21.78 | 111.83 | 272.33 | 798.35 | 22.49 | 80.67 | 233.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1634.75 | 21.36 | 102.33 | 261.17 | 706.79 | 20.76 | 47.17 | 224.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1522.54 | 19.17 | 83.83 | 306.33 | 787.26 | 21.37 | 66.00 | 268.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1791.97 | 20.37 | 109.33 | 318.50 | 918.91 | 21.37 | 79.83 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2023.85 | 20.25 | 118.83 | 355.33 | 865.64 | 20.92 | 67.83 | 318.83 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1944.47 | 19.98 | 114.33 | 348.83 | 853.40 | 20.99 | 66.67 | 315.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1835.56 | 19.90 | 114.17 | 347.17 | 814.98 | 20.64 | 61.83 | 309.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1890.37 | 20.49 | 113.83 | 339.83 | 848.20 | 20.38 | 56.00 | 305.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1884.22 | 21.34 | 107.00 | 310.00 | 975.28 | 22.34 | 77.33 | 283.00 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1752.13 | 21.26 | 104.67 | 303.83 | 911.81 | 22.30 | 76.00 | 272.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1505.13 | 20.48 | 84.33 | 275.33 | 785.64 | 22.26 | 63.00 | 241.17 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1246.09 | 20.33 | 85.50 | 267.17 | 628.02 | 20.91 | 50.67 | 222.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1729.56 | 20.52 | 1250.00 | 3705.83 | 829.32 | 21.36 | 793.00 | 3276.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1246.09 | 19.17 | 83.83 | 261.17 | 628.02 | 20.38 | 47.17 | 222.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 2023.85 | 21.78 | 118.83 | 355.33 | 975.28 | 22.49 | 80.67 | 318.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:39 | 581.30 | 15.19 | 0.00 | 258.00 | 336.26 | 17.33 | 0.00 | 172.67 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 661.11 | 16.04 | 0.00 | 251.67 | 381.33 | 18.17 | 0.00 | 188.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 771.41 | 16.70 | 0.00 | 305.17 | 438.69 | 18.78 | 0.00 | 252.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 884.53 | 17.02 | 0.00 | 325.50 | 496.49 | 19.04 | 0.00 | 285.17 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1043.93 | 18.04 | 2.83 | 367.83 | 578.21 | 20.12 | 54.83 | 333.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:19 | 1155.84 | 21.18 | 77.67 | 366.00 | 631.89 | 21.73 | 157.00 | 336.83 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1117.31 | 19.00 | 27.00 | 357.33 | 611.95 | 21.14 | 128.50 | 327.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1010.71 | 17.69 | 0.00 | 348.83 | 566.63 | 19.81 | 53.33 | 315.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 880.62 | 17.38 | 0.00 | 316.67 | 505.49 | 19.49 | 0.00 | 273.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 727.75 | 16.49 | 0.00 | 298.33 | 427.45 | 18.63 | 0.00 | 245.33 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 630.06 | 16.11 | 0.00 | 260.33 | 371.49 | 18.32 | 0.00 | 193.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 563.66 | 15.28 | 0.00 | 247.33 | 326.72 | 17.46 | 0.00 | 150.17 |
Annual Sum or Average | 4323.33 | 0.52 | 854.57 | 17.31 | 107.50 | 3703.00 | 482.38 | 19.28 | 393.67 | 3073.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 563.66 | 15.19 | 0.00 | 247.33 | 326.72 | 17.33 | 0.00 | 150.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1155.84 | 21.18 | 77.67 | 367.83 | 631.89 | 21.73 | 157.00 | 336.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1465.81 | 21.39 | 108.17 | 273.17 | 766.99 | 22.11 | 77.17 | 233.00 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1434.95 | 19.78 | 76.33 | 260.33 | 728.09 | 20.67 | 48.33 | 222.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1636.32 | 19.43 | 85.83 | 307.67 | 840.51 | 21.39 | 65.67 | 270.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1662.92 | 16.77 | 55.00 | 322.67 | 867.51 | 17.26 | 0.00 | 285.17 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1747.35 | 14.42 | 0.00 | 348.83 | 904.71 | 17.57 | 0.00 | 311.67 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1856.25 | 14.60 | 0.00 | 345.17 | 827.69 | 17.77 | 0.00 | 310.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1777.71 | 14.63 | 3.67 | 346.83 | 809.63 | 17.55 | 0.00 | 307.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1815.78 | 17.24 | 59.83 | 342.00 | 941.08 | 17.96 | 5.50 | 306.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1746.04 | 19.75 | 86.83 | 316.33 | 908.86 | 20.82 | 57.33 | 283.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1815.24 | 21.42 | 107.83 | 301.67 | 945.05 | 22.46 | 79.33 | 271.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1562.64 | 20.44 | 85.00 | 275.50 | 820.26 | 22.58 | 69.00 | 242.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1365.77 | 19.99 | 87.33 | 266.83 | 716.56 | 22.16 | 71.17 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1670.30 | 18.11 | 755.83 | 3707.00 | 843.97 | 19.85 | 473.50 | 3269.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1365.77 | 14.42 | 0.00 | 260.33 | 716.56 | 17.26 | 0.00 | 222.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1856.25 | 21.42 | 108.17 | 348.83 | 945.05 | 22.58 | 79.33 | 311.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4068.03 | 33.81 | 310.17 | 292.00 | 1023.94 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.96 | 22.69 | 141.00 | 272.50 | 911.34 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.18 | 14.49 | 5.00 | 311.33 | 779.07 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.28 | 13.72 | 0.00 | 320.50 | 623.12 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.17 | 13.73 | 0.00 | 345.67 | 549.41 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.80 | 13.56 | 0.00 | 342.33 | 534.82 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.19 | 13.42 | 0.00 | 342.67 | 555.15 | 16.83 | 0.00 | 297.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.43 | 14.00 | 0.00 | 341.67 | 634.30 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.18 | 14.67 | 0.00 | 317.17 | 777.94 | 18.09 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.91 | 16.78 | 34.50 | 316.17 | 935.96 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.96 | 30.74 | 255.67 | 296.17 | 1059.69 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.16 | 34.23 | 306.00 | 287.50 | 1096.76 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.14 | 19.01 | 1052.33 | 3785.67 | 771.61 | 18.75 | 292.17 | 3386.33 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.80 | 13.42 | 0.00 | 272.50 | 534.82 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4068.03 | 34.23 | 310.17 | 345.67 | 1096.76 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.74 | 21.32 | 111.83 | 271.00 | 767.44 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1591.03 | 20.90 | 102.33 | 259.33 | 674.70 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.80 | 18.68 | 83.83 | 303.50 | 753.22 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.78 | 19.93 | 109.33 | 316.33 | 881.83 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.22 | 19.81 | 118.83 | 354.33 | 818.82 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.13 | 19.53 | 114.33 | 347.17 | 814.52 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.50 | 19.47 | 114.17 | 345.33 | 775.26 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.23 | 20.06 | 113.67 | 338.17 | 808.87 | 20.21 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.64 | 20.73 | 105.17 | 308.67 | 935.55 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.74 | 19.29 | 87.83 | 301.83 | 873.61 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.94 | 19.98 | 84.33 | 273.33 | 750.98 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.63 | 19.83 | 85.17 | 264.83 | 599.92 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.82 | 19.93 | 1230.83 | 3683.83 | 792.31 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.63 | 18.68 | 83.83 | 259.33 | 599.92 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.22 | 21.32 | 118.83 | 354.33 | 935.55 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.47 | 11.54 | 0.00 | 253.50 | 324.54 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.65 | 12.30 | 0.00 | 250.00 | 368.10 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.27 | 13.02 | 0.00 | 302.50 | 423.19 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.99 | 13.47 | 0.00 | 324.00 | 478.20 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.79 | 14.40 | 2.83 | 366.33 | 555.59 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.67 | 18.32 | 77.33 | 363.00 | 605.82 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.97 | 15.54 | 26.83 | 356.33 | 587.19 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.41 | 14.11 | 0.00 | 347.50 | 544.82 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.55 | 13.94 | 0.00 | 315.00 | 487.17 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.31 | 13.04 | 0.00 | 295.83 | 412.65 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.97 | 12.51 | 0.00 | 256.67 | 358.64 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.05 | 0.00 | 136.67 |
Annual Sum or Average | 4323.33 | 0.52 | 823.44 | 13.78 | 107.00 | 3674.17 | 464.30 | 17.02 | 62.67 | 2996.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.18 | 11.51 | 0.00 | 243.50 | 315.21 | 15.00 | 0.00 | 136.67 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.67 | 18.32 | 77.33 | 366.33 | 605.82 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.55 | 21.01 | 108.17 | 271.00 | 736.54 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.30 | 19.36 | 76.33 | 258.83 | 694.80 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.53 | 18.99 | 85.83 | 306.50 | 802.73 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.86 | 16.29 | 55.00 | 320.17 | 830.02 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.85 | 13.87 | 0.00 | 347.83 | 866.89 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.08 | 14.05 | 0.00 | 343.50 | 788.43 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.20 | 14.08 | 3.67 | 345.00 | 772.28 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.23 | 16.76 | 59.83 | 339.83 | 901.70 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.99 | 19.32 | 86.83 | 314.33 | 868.51 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.55 | 21.02 | 107.83 | 300.00 | 907.15 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.72 | 20.01 | 85.00 | 273.17 | 785.33 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.36 | 19.56 | 87.33 | 264.83 | 686.01 | 22.05 | 71.33 | 222.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1619.05 | 17.64 | 755.83 | 3685.00 | 807.36 | 19.69 | 473.83 | 3230.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.36 | 13.87 | 0.00 | 258.83 | 686.01 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.08 | 21.02 | 108.17 | 347.83 | 907.15 | 22.47 | 79.33 | 309.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4067.94 | 33.81 | 310.17 | 292.00 | 1023.85 | 22.66 | 91.67 | 279.50 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2054.84 | 22.70 | 141.00 | 272.50 | 911.26 | 17.89 | 0.00 | 241.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1505.07 | 14.49 | 5.00 | 311.33 | 779.00 | 17.71 | 0.00 | 273.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1176.20 | 13.72 | 0.00 | 320.50 | 623.06 | 17.04 | 0.00 | 280.33 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:19 | 999.11 | 13.73 | 0.00 | 345.67 | 549.37 | 17.13 | 0.00 | 299.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:10 | 955.75 | 13.56 | 0.00 | 342.33 | 534.78 | 17.03 | 0.00 | 294.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:10 | 1005.13 | 13.42 | 0.00 | 342.67 | 555.10 | 16.83 | 0.00 | 297.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:19 | 1180.36 | 14.00 | 0.00 | 341.67 | 634.24 | 17.39 | 0.00 | 299.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 1477.08 | 14.67 | 0.00 | 317.17 | 777.87 | 18.10 | 0.00 | 281.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 1985.79 | 16.78 | 34.50 | 316.17 | 935.88 | 18.92 | 10.67 | 284.83 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3403.85 | 30.74 | 255.67 | 296.17 | 1059.59 | 22.44 | 76.67 | 280.50 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:30 | 4055.08 | 34.23 | 306.00 | 287.50 | 1096.67 | 24.01 | 113.17 | 274.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1898.05 | 19.01 | 1052.33 | 3785.67 | 771.54 | 18.75 | 292.17 | 3386.17 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 955.75 | 13.42 | 0.00 | 272.50 | 534.78 | 16.83 | 0.00 | 241.67 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4067.94 | 34.23 | 310.17 | 345.67 | 1096.67 | 24.01 | 113.17 | 299.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-07:00 | 1470.69 | 21.32 | 111.83 | 271.00 | 767.39 | 22.27 | 80.83 | 229.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1590.97 | 20.90 | 102.33 | 259.33 | 674.64 | 20.54 | 47.17 | 221.83 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-07:00 | 1479.74 | 18.68 | 83.83 | 303.50 | 753.16 | 21.17 | 66.00 | 264.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-06:00 | 1737.71 | 19.93 | 109.33 | 316.33 | 881.78 | 21.20 | 79.83 | 277.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 1969.15 | 19.81 | 118.83 | 354.33 | 818.76 | 19.93 | 57.33 | 312.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:10 | 1898.06 | 19.53 | 114.33 | 347.17 | 814.47 | 20.80 | 66.33 | 312.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:40 | 1786.43 | 19.47 | 114.17 | 345.33 | 775.20 | 19.67 | 52.50 | 306.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1829.16 | 20.06 | 113.67 | 338.17 | 808.81 | 20.22 | 56.00 | 303.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-06:49 | 1830.57 | 20.73 | 105.17 | 308.67 | 935.49 | 22.16 | 77.33 | 280.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1679.69 | 19.30 | 87.83 | 301.83 | 873.56 | 22.11 | 76.00 | 268.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1458.89 | 19.98 | 84.33 | 273.33 | 750.93 | 22.03 | 63.00 | 237.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1207.59 | 19.83 | 85.33 | 264.83 | 599.87 | 20.66 | 50.67 | 218.00 |
Annual Sum or Average | 4323.33 | 0.52 | 1678.76 | 19.93 | 1231.00 | 3683.83 | 792.26 | 21.02 | 773.00 | 3230.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1207.59 | 18.68 | 83.83 | 259.33 | 599.87 | 19.67 | 47.17 | 218.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1969.15 | 21.32 | 118.83 | 354.33 | 935.49 | 22.27 | 80.83 | 312.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.55 | 0.48 | 01-JAN-09:50 | 560.45 | 11.54 | 0.00 | 253.50 | 324.52 | 15.00 | 0.00 | 160.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 637.62 | 12.30 | 0.00 | 250.00 | 368.07 | 15.80 | 0.00 | 182.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:50 | 744.23 | 13.02 | 0.00 | 302.50 | 423.15 | 16.46 | 0.00 | 246.00 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 852.95 | 13.47 | 0.00 | 324.00 | 478.16 | 16.82 | 0.00 | 280.83 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1005.74 | 14.40 | 2.83 | 366.33 | 555.55 | 17.84 | 1.17 | 328.17 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:30 | 1112.61 | 18.32 | 77.33 | 363.00 | 605.77 | 19.53 | 34.17 | 333.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:49 | 1075.91 | 15.54 | 26.83 | 356.33 | 587.15 | 18.86 | 27.33 | 324.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 973.36 | 14.11 | 0.00 | 347.50 | 544.78 | 17.55 | 0.00 | 310.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:19 | 848.52 | 13.94 | 0.00 | 315.00 | 487.14 | 17.35 | 0.00 | 270.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-07:40 | 701.28 | 13.05 | 0.00 | 295.83 | 412.62 | 16.51 | 0.00 | 239.67 |
November | 318.83 | 0.53 | 0.48 | 01-NOV-07:00 | 606.95 | 12.51 | 0.00 | 256.67 | 358.61 | 16.09 | 0.00 | 184.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.05 | 0.00 | 136.50 |
Annual Sum or Average | 4323.33 | 0.52 | 823.40 | 13.79 | 107.00 | 3674.17 | 464.26 | 17.02 | 62.67 | 2996.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 543.16 | 11.51 | 0.00 | 243.50 | 315.19 | 15.00 | 0.00 | 136.50 | |
Maximum of Months | 405.33 | 0.55 | 0.48 | 1112.61 | 18.32 | 77.33 | 366.33 | 605.77 | 19.53 | 34.17 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.53 | 0.48 | 01-JAN-09:39 | 1424.51 | 21.01 | 108.17 | 271.00 | 736.49 | 22.00 | 77.17 | 228.67 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-09:09 | 1389.24 | 19.36 | 76.33 | 258.83 | 694.75 | 20.55 | 48.33 | 218.17 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:00 | 1589.47 | 18.99 | 85.83 | 306.50 | 802.67 | 21.27 | 65.83 | 265.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:20 | 1592.79 | 16.29 | 55.00 | 320.17 | 829.96 | 17.08 | 0.00 | 282.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:49 | 1691.78 | 13.87 | 0.00 | 347.83 | 866.84 | 17.36 | 0.00 | 309.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:40 | 1808.01 | 14.05 | 0.00 | 343.50 | 788.37 | 17.56 | 0.00 | 306.17 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1726.12 | 14.09 | 3.67 | 345.00 | 772.22 | 17.34 | 0.00 | 304.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1754.16 | 16.76 | 59.83 | 339.83 | 901.64 | 17.77 | 5.50 | 304.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:00 | 1695.93 | 19.32 | 86.83 | 314.33 | 868.45 | 20.68 | 57.33 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-08:09 | 1764.50 | 21.02 | 107.83 | 300.00 | 907.09 | 22.34 | 79.33 | 268.33 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:20 | 1515.67 | 20.01 | 85.00 | 273.17 | 785.28 | 22.47 | 69.00 | 239.83 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:50 | 1324.31 | 19.56 | 87.33 | 264.83 | 685.96 | 22.05 | 71.33 | 221.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1618.99 | 17.64 | 755.83 | 3685.00 | 807.30 | 19.69 | 473.83 | 3229.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1324.31 | 13.87 | 0.00 | 258.83 | 685.96 | 17.08 | 0.00 | 218.17 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 1808.01 | 21.02 | 108.17 | 347.83 | 907.09 | 22.47 | 79.33 | 309.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181591E+09 | 4481.19 | 02-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115001E+09 | 4481.19 | 01-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41119805.49 | 4481.19 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 484374.41 | 1099.18 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35881976.16 | 4481.19 | 18-DEC-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.374079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181591E+09 | 4481.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397423E+11 | 0.343736E+11 | 61107.72 | 30-JAN-07:03 | 48911.81 | 0.00 |
February | 0.00 | 0.00 | 0.425245E+11 | 0.361591E+11 | 73316.49 | 07-FEB-16:00 | 55340.34 | 0.00 |
March | 0.00 | 0.00 | 0.569443E+11 | 0.501142E+11 | 77948.69 | 02-MAR-07:03 | 77948.69 | 0.00 |
April | 0.00 | 0.00 | 0.685346E+11 | 0.586406E+11 | 86424.70 | 10-APR-12:00 | 55434.86 | 0.00 |
May | 0.00 | 0.00 | 0.103919E+12 | 0.857865E+11 | 130893.72 | 31-MAY-04:02 | 86257.49 | 0.00 |
June | 0.00 | 0.00 | 0.125508E+12 | 0.923571E+11 | 133814.97 | 20-JUN-04:02 | 80026.97 | 0.00 |
July | 0.00 | 0.00 | 0.153365E+12 | 0.102904E+12 | 135257.52 | 20-JUL-06:07 | 58298.95 | 0.00 |
August | 0.00 | 0.00 | 0.170100E+12 | 0.111922E+12 | 133828.87 | 08-AUG-06:15 | 67476.95 | 0.00 |
September | 0.00 | 0.00 | 0.136346E+12 | 0.926208E+11 | 134980.56 | 10-SEP-17:42 | 64960.68 | 0.00 |
October | 0.00 | 0.00 | 0.109786E+12 | 0.824984E+11 | 132315.48 | 18-OCT-04:02 | 81879.45 | 0.00 |
November | 0.00 | 0.00 | 0.788091E+11 | 0.634798E+11 | 129728.97 | 02-NOV-06:03 | 83498.71 | 0.00 |
December | 0.00 | 0.00 | 0.506833E+11 | 0.423239E+11 | 83705.85 | 12-DEC-07:03 | 67062.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113626E+13 | 0.853180E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.397423E+11 | 0.343736E+11 | 61107.72 | 48911.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.170100E+12 | 0.111922E+12 | 135257.52 | 86257.49 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.288214E+11 | 0.233690E+11 | 45094.26 | 30-JAN-14:00 | 32471.72 | 0.00 |
February | 0.00 | 0.00 | 0.330966E+11 | 0.269323E+11 | 64916.94 | 07-FEB-15:05 | 49336.54 | 0.00 |
March | 0.00 | 0.00 | 0.470054E+11 | 0.403485E+11 | 67566.29 | 27-MAR-12:01 | 67566.29 | 0.00 |
April | 0.00 | 0.00 | 0.590968E+11 | 0.500292E+11 | 113624.31 | 30-APR-16:32 | 65621.83 | 0.00 |
May | 0.00 | 0.00 | 0.907719E+11 | 0.751802E+11 | 122505.04 | 31-MAY-04:02 | 77885.85 | 0.00 |
June | 0.00 | 0.00 | 0.110172E+12 | 0.805168E+11 | 125751.52 | 20-JUN-04:02 | 71373.78 | 0.00 |
July | 0.00 | 0.00 | 0.133653E+12 | 0.900881E+11 | 125587.01 | 06-JUL-04:02 | 72247.77 | 0.00 |
August | 0.00 | 0.00 | 0.143974E+12 | 0.960111E+11 | 126646.42 | 08-AUG-04:02 | 70618.02 | 0.00 |
September | 0.00 | 0.00 | 0.112815E+12 | 0.768079E+11 | 126076.89 | 24-SEP-16:42 | 70473.00 | 0.00 |
October | 0.00 | 0.00 | 0.876452E+11 | 0.660943E+11 | 123907.45 | 07-OCT-05:03 | 67735.52 | 0.00 |
November | 0.00 | 0.00 | 0.601236E+11 | 0.475875E+11 | 91735.24 | 03-NOV-05:03 | 52709.79 | 0.00 |
December | 0.00 | 0.00 | 0.376368E+11 | 0.295299E+11 | 62857.45 | 05-DEC-15:05 | 43313.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.944812E+12 | 0.702495E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.288214E+11 | 0.233690E+11 | 45094.26 | 32471.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.143974E+12 | 0.960111E+11 | 126646.42 | 77885.85 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.280034E+11 | 0.218133E+11 | 44007.32 | 30-JAN-14:10 | 32483.79 | 0.00 |
February | 0.00 | 0.00 | 0.333037E+11 | 0.265451E+11 | 68002.09 | 07-FEB-15:30 | 52215.97 | 0.00 |
March | 0.00 | 0.00 | 0.487273E+11 | 0.413624E+11 | 74647.52 | 27-MAR-13:50 | 74647.52 | 0.00 |
April | 0.00 | 0.00 | 0.629479E+11 | 0.531933E+11 | 95252.55 | 30-APR-12:43 | 89781.49 | 0.00 |
May | 0.00 | 0.00 | 0.985271E+11 | 0.821336E+11 | 139824.35 | 31-MAY-04:02 | 88878.48 | 0.00 |
June | 0.00 | 0.00 | 0.119535E+12 | 0.887540E+11 | 143845.00 | 14-JUN-04:02 | 79931.71 | 0.00 |
July | 0.00 | 0.00 | 0.147218E+12 | 0.101190E+12 | 143523.40 | 16-JUL-18:42 | 86633.45 | 0.00 |
August | 0.00 | 0.00 | 0.156189E+12 | 0.106227E+12 | 143329.28 | 26-AUG-04:02 | 84550.22 | 0.00 |
September | 0.00 | 0.00 | 0.120538E+12 | 0.834540E+11 | 143708.41 | 10-SEP-18:12 | 74304.78 | 0.00 |
October | 0.00 | 0.00 | 0.912836E+11 | 0.692921E+11 | 143786.91 | 08-OCT-11:32 | 82104.74 | 0.00 |
November | 0.00 | 0.00 | 0.609047E+11 | 0.478442E+11 | 96162.46 | 03-NOV-05:03 | 55319.03 | 0.00 |
December | 0.00 | 0.00 | 0.371103E+11 | 0.282227E+11 | 63343.07 | 05-DEC-15:00 | 44341.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.100429E+13 | 0.750032E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.280034E+11 | 0.218133E+11 | 44007.32 | 32483.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.156189E+12 | 0.106227E+12 | 143845.00 | 89781.49 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1228.96 | 4483.27 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1202.89 | 4436.51 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1197.58 | 4225.52 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1003.36 | 3823.21 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 931.13 | 3441.37 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 872.20 | 3086.20 | 01-JUN-11:18 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 771.00 | 2915.85 | 31-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 890.93 | 3142.36 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 914.37 | 3491.97 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1023.76 | 3927.54 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1148.72 | 4272.12 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1172.94 | 4459.60 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 1028.89 | ||||
Minimum of Months | 0.00 | 0.00 | 771.00 | 2915.85 | ||
Maximum of Months | 0.00 | 0.00 | 1228.96 | 4483.27 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.301710E+10 | 0.37 | 5221.78 | 17-JAN-15:10 | 1.10 |
February | 0.303409E+10 | 0.39 | 7106.67 | 06-FEB-16:00 | 1.33 |
March | 0.401628E+10 | 0.43 | 9261.07 | 27-MAR-12:09 | 1.57 |
April | 0.457136E+10 | 0.48 | 9046.05 | 24-APR-15:30 | 1.55 |
May | 0.692598E+10 | 0.62 | 11183.16 | 08-MAY-12:06 | 1.77 |
June | 0.742765E+10 | 0.66 | 11183.16 | 01-JUN-04:02 | 1.77 |
July | 0.743336E+10 | 0.69 | 11183.16 | 01-JUL-04:02 | 1.76 |
August | 0.781904E+10 | 0.73 | 11183.16 | 01-AUG-04:02 | 1.76 |
September | 0.665265E+10 | 0.64 | 11183.16 | 01-SEP-04:02 | 1.77 |
October | 0.613136E+10 | 0.58 | 11183.16 | 04-OCT-04:02 | 1.77 |
November | 0.518065E+10 | 0.52 | 11183.16 | 20-NOV-05:02 | 1.77 |
December | 0.364842E+10 | 0.40 | 6882.67 | 04-DEC-15:30 | 1.30 |
Annual Sum or Average | 0.658579E+11 | 0.54 | |||
Minimum of Months | 0.301710E+10 | 0.37 | 5221.78 | 1.10 | |
Maximum of Months | 0.781904E+10 | 0.73 | 11183.16 | 1.77 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.192627E+10 | 0.33 | 3468.43 | 23-JAN-13:30 | 0.91 |
February | 0.213595E+10 | 0.35 | 6238.64 | 06-FEB-15:05 | 1.30 |
March | 0.311635E+10 | 0.41 | 9639.48 | 02-MAR-07:03 | 1.72 |
April | 0.372679E+10 | 0.45 | 8733.56 | 28-APR-12:02 | 1.62 |
May | 0.592239E+10 | 0.59 | 10225.71 | 08-MAY-04:02 | 1.78 |
June | 0.644260E+10 | 0.64 | 10225.71 | 01-JUN-04:02 | 1.78 |
July | 0.687355E+10 | 0.67 | 10225.71 | 01-JUL-04:02 | 1.78 |
August | 0.763166E+10 | 0.72 | 10225.71 | 01-AUG-06:03 | 1.78 |
September | 0.605699E+10 | 0.61 | 10225.71 | 01-SEP-04:02 | 1.78 |
October | 0.510442E+10 | 0.53 | 10225.71 | 02-OCT-04:02 | 1.78 |
November | 0.369367E+10 | 0.44 | 8755.49 | 13-NOV-07:03 | 1.61 |
December | 0.228397E+10 | 0.35 | 4989.40 | 04-DEC-15:05 | 1.13 |
Annual Sum or Average | 0.549146E+11 | 0.51 | |||
Minimum of Months | 0.192627E+10 | 0.33 | 3468.43 | 0.91 | |
Maximum of Months | 0.763166E+10 | 0.72 | 10225.71 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.172065E+10 | 0.33 | 2751.84 | 23-JAN-14:00 | 0.73 |
February | 0.192040E+10 | 0.35 | 5093.67 | 06-FEB-15:00 | 1.03 |
March | 0.285056E+10 | 0.38 | 9562.71 | 02-MAR-06:03 | 1.52 |
April | 0.349608E+10 | 0.42 | 7358.15 | 24-APR-14:00 | 1.29 |
May | 0.569263E+10 | 0.55 | 12103.93 | 12-MAY-04:02 | 1.77 |
June | 0.627295E+10 | 0.60 | 12103.93 | 12-JUN-04:02 | 1.77 |
July | 0.686299E+10 | 0.65 | 12103.93 | 01-JUL-04:02 | 1.76 |
August | 0.750541E+10 | 0.68 | 12103.93 | 01-AUG-04:02 | 1.76 |
September | 0.585294E+10 | 0.57 | 12103.93 | 01-SEP-04:02 | 1.77 |
October | 0.475396E+10 | 0.48 | 10597.33 | 16-OCT-04:02 | 1.62 |
November | 0.321379E+10 | 0.40 | 6437.15 | 06-NOV-14:40 | 1.19 |
December | 0.199840E+10 | 0.34 | 3950.46 | 04-DEC-14:10 | 0.89 |
Annual Sum or Average | 0.521408E+11 | 0.48 | |||
Minimum of Months | 0.172065E+10 | 0.33 | 2751.84 | 0.73 | |
Maximum of Months | 0.750541E+10 | 0.68 | 12103.93 | 1.77 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379742.02 | 3713922.60 | 6.85 | 01-JAN-06:10 | 2.06 | 2.06 | 58.65 | 0.05 |
February | 11196021.66 | 3358806.50 | 6.85 | 01-FEB-06:03 | 2.06 | 2.06 | 57.87 | 0.05 |
March | 12675672.10 | 3802701.63 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 57.87 | 0.05 |
April | 11960507.72 | 3588152.32 | 6.85 | 01-APR-05:05 | 2.06 | 2.06 | 58.06 | 0.05 |
May | 12527707.06 | 3758312.12 | 6.85 | 01-MAY-05:05 | 2.06 | 2.06 | 58.33 | 0.05 |
June | 12231776.97 | 3669533.09 | 6.85 | 01-JUN-05:10 | 2.06 | 2.06 | 58.41 | 0.05 |
July | 12256437.81 | 3676931.34 | 6.85 | 01-JUL-05:05 | 2.06 | 2.06 | 58.56 | 0.05 |
August | 12675672.10 | 3802701.63 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 58.63 | 0.05 |
September | 11960507.72 | 3588152.32 | 6.85 | 01-SEP-05:05 | 2.06 | 2.06 | 58.42 | 0.05 |
October | 12379742.02 | 3713922.60 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 58.87 | 0.05 |
November | 12059151.09 | 3617745.33 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 58.07 | 0.05 |
December | 12256437.81 | 3676931.34 | 6.85 | 01-DEC-06:03 | 2.06 | 2.06 | 57.90 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967812.83 | ||||||
Minimum of Months | 11196021.66 | 3358806.50 | 6.85 | 2.06 | 2.06 | 57.87 | 0.05 | |
Maximum of Months | 12675672.10 | 3802701.63 | 6.85 | 2.06 | 2.06 | 58.87 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.65 | 58.65 | 1228.96 | 4483.27 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.31 | 58.31 | 1202.89 | 4436.51 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 1197.58 | 4225.52 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.55 | 58.55 | 1003.36 | 3823.21 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.97 | 58.97 | 931.13 | 3441.37 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.85 | 58.85 | 872.20 | 3086.20 | 01-JUN-11:18 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.92 | 58.92 | 771.00 | 2915.85 | 31-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.92 | 58.92 | 890.93 | 3142.36 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.83 | 58.83 | 914.37 | 3491.97 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.13 | 58.13 | 1023.76 | 3927.54 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.51 | 58.51 | 1148.72 | 4272.12 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.39 | 58.39 | 1172.94 | 4459.60 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 1028.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 771.00 | 2915.85 | ||
Maximum of Months | 0.00 | 0.00 | 58.97 | 58.97 | 1228.96 | 4483.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.121630E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127805E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.173733E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.214023E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.346103E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.411624E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.493463E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.544406E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.422321E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.334702E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.236718E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.150267E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.357680E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.121630E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.544406E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.860479E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.978893E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.142532E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183025E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.299897E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.357904E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.431088E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.468355E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.353040E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.268847E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.178868E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.109094E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.297659E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.860479E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.468355E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.831228E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.973082E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145330E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.191806E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.319600E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.382535E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.468755E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.501488E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.372146E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.276004E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.177440E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.106461E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.312200E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.831228E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.501488E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.301710E+10 | 0.397423E+11 | 0.181591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303409E+10 | 0.425245E+11 | 0.115001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401628E+10 | 0.569443E+11 | 41119805.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457136E+10 | 0.685346E+11 | 484374.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692598E+10 | 0.103919E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742765E+10 | 0.125508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.743336E+10 | 0.153365E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.781904E+10 | 0.170100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665265E+10 | 0.136346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.613136E+10 | 0.109786E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.518065E+10 | 0.788091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364842E+10 | 0.506833E+11 | 35881976.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658579E+11 | 0.113626E+13 | 0.374079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301710E+10 | 0.397423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.781904E+10 | 0.170100E+12 | 0.181591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.192627E+10 | 0.288214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213595E+10 | 0.330966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311635E+10 | 0.470054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372679E+10 | 0.590968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592239E+10 | 0.907719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644260E+10 | 0.110172E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687355E+10 | 0.133653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.763166E+10 | 0.143974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605699E+10 | 0.112815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510442E+10 | 0.876452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369367E+10 | 0.601236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228397E+10 | 0.376368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549146E+11 | 0.944812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192627E+10 | 0.288214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763166E+10 | 0.143974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.172065E+10 | 0.280034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192040E+10 | 0.333037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285056E+10 | 0.487273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349608E+10 | 0.629479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569263E+10 | 0.985271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627295E+10 | 0.119535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686299E+10 | 0.147218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750541E+10 | 0.156189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.585294E+10 | 0.120538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475396E+10 | 0.912836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321379E+10 | 0.609047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199840E+10 | 0.371103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521408E+11 | 0.100429E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172065E+10 | 0.280034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750541E+10 | 0.156189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.301710E+10 | 0.00 | 0.00 | 0.00 | 0.896432E+10 | 0.181591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303409E+10 | 0.00 | 0.00 | 0.00 | 0.963136E+10 | 0.115001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401628E+10 | 0.00 | 0.00 | 0.00 | 0.133159E+11 | 41119805.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.457136E+10 | 0.00 | 0.00 | 0.00 | 0.168305E+11 | 484374.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.692598E+10 | 0.00 | 0.00 | 0.00 | 0.276843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.742765E+10 | 0.00 | 0.00 | 0.00 | 0.337348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.743336E+10 | 0.00 | 0.00 | 0.00 | 0.419129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.781904E+10 | 0.00 | 0.00 | 0.00 | 0.466216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.665265E+10 | 0.00 | 0.00 | 0.00 | 0.355794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.613136E+10 | 0.00 | 0.00 | 0.00 | 0.273389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.518065E+10 | 0.00 | 0.00 | 0.00 | 0.184912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364842E+10 | 0.00 | 0.00 | 0.00 | 0.113424E+11 | 35881976.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658579E+11 | 0.00 | 0.00 | 0.00 | 0.291448E+12 | 0.374079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.301710E+10 | 0.00 | 0.00 | 0.00 | 0.896432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.781904E+10 | 0.00 | 0.00 | 0.00 | 0.466216E+11 | 0.181591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.192627E+10 | 0.00 | 0.00 | 0.00 | 0.667852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213595E+10 | 0.00 | 0.00 | 0.00 | 0.765298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311635E+10 | 0.00 | 0.00 | 0.00 | 0.111368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.372679E+10 | 0.00 | 0.00 | 0.00 | 0.145757E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592239E+10 | 0.00 | 0.00 | 0.00 | 0.240673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.644260E+10 | 0.00 | 0.00 | 0.00 | 0.293478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.687355E+10 | 0.00 | 0.00 | 0.00 | 0.362353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.763166E+10 | 0.00 | 0.00 | 0.00 | 0.392038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.605699E+10 | 0.00 | 0.00 | 0.00 | 0.292471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510442E+10 | 0.00 | 0.00 | 0.00 | 0.217803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369367E+10 | 0.00 | 0.00 | 0.00 | 0.141932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228397E+10 | 0.00 | 0.00 | 0.00 | 0.862545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549146E+11 | 0.00 | 0.00 | 0.00 | 0.242744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.192627E+10 | 0.00 | 0.00 | 0.00 | 0.667852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.763166E+10 | 0.00 | 0.00 | 0.00 | 0.392038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.172065E+10 | 0.00 | 0.00 | 0.00 | 0.659163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192040E+10 | 0.00 | 0.00 | 0.00 | 0.781042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.285056E+10 | 0.00 | 0.00 | 0.00 | 0.116824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349608E+10 | 0.00 | 0.00 | 0.00 | 0.156845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.569263E+10 | 0.00 | 0.00 | 0.00 | 0.262673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.627295E+10 | 0.00 | 0.00 | 0.00 | 0.319805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.686299E+10 | 0.00 | 0.00 | 0.00 | 0.400125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.750541E+10 | 0.00 | 0.00 | 0.00 | 0.426434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.585294E+10 | 0.00 | 0.00 | 0.00 | 0.313617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.475396E+10 | 0.00 | 0.00 | 0.00 | 0.228464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.321379E+10 | 0.00 | 0.00 | 0.00 | 0.145302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.199840E+10 | 0.00 | 0.00 | 0.00 | 0.864774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.521408E+11 | 0.00 | 0.00 | 0.00 | 0.260059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.172065E+10 | 0.00 | 0.00 | 0.00 | 0.659163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.750541E+10 | 0.00 | 0.00 | 0.00 | 0.426434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243889E+09 | 0.296515E+09 | 0.00 | 38560712.36 | 0.153965E+09 | 0.00 | 0.384974E+10 | 0.00 | 0.42 |
February | 0.109448E+09 | 0.104732E+10 | 0.00 | 27266637.88 | 0.151913E+09 | 0.00 | 0.205434E+10 | 0.00 | 0.40 |
March | 0.118159E+09 | 0.203057E+10 | 0.00 | 25138581.58 | 0.203893E+09 | 0.00 | 0.164993E+10 | 0.00 | 0.40 |
April | 53293487.45 | 0.437713E+10 | 0.00 | 8957013.90 | 0.113048E+10 | 0.00 | 0.551987E+09 | 0.00 | 0.37 |
May | 16626351.65 | 0.904111E+10 | 0.00 | 2049739.91 | 0.285624E+10 | 0.00 | 82385995.75 | 0.00 | 0.36 |
June | 2074870.10 | 0.144281E+11 | 0.00 | 385769.22 | 0.453892E+10 | 0.00 | 9778642.70 | 0.00 | 0.36 |
July | 1536837.50 | 0.184988E+11 | 0.00 | 8720.61 | 0.970924E+10 | 0.00 | 238776.27 | 0.00 | 0.39 |
August | 0.00 | 0.210165E+11 | 0.00 | 0.00 | 0.969422E+10 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 33157.11 | 0.160420E+11 | 0.00 | 80264.25 | 0.645528E+10 | 0.00 | 349497.74 | 0.00 | 0.37 |
October | 28119700.44 | 0.101176E+11 | 0.00 | 1571592.33 | 0.377914E+10 | 0.00 | 73834467.97 | 0.00 | 0.35 |
November | 15831706.51 | 0.524172E+10 | 0.00 | 5236365.67 | 0.866731E+09 | 0.00 | 0.144969E+09 | 0.00 | 0.34 |
December | 0.104931E+09 | 0.146630E+10 | 0.00 | 28340290.42 | 0.377169E+09 | 0.00 | 0.182704E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.693943E+09 | 0.103604E+12 | 0.00 | 0.137596E+09 | 0.399172E+11 | 0.00 | 0.102446E+11 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.296515E+09 | 0.00 | 0.00 | 0.151913E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.243889E+09 | 0.210165E+11 | 0.00 | 38560712.36 | 0.970924E+10 | 0.00 | 0.384974E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.553036E+09 | 0.308227E+09 | 0.00 | 17818691.09 | 0.161621E+09 | 0.00 | 0.228463E+10 | 0.00 | 0.32 |
February | 0.316536E+09 | 0.884828E+09 | 0.00 | 13832831.45 | 0.179407E+09 | 0.00 | 0.119689E+10 | 0.00 | 0.31 |
March | 0.246414E+09 | 0.172745E+10 | 0.00 | 13729573.29 | 0.242777E+09 | 0.00 | 0.101179E+10 | 0.00 | 0.32 |
April | 0.102310E+09 | 0.361120E+10 | 0.00 | 5191720.26 | 0.112934E+10 | 0.00 | 0.376263E+09 | 0.00 | 0.31 |
May | 26057139.24 | 0.776505E+10 | 0.00 | 1554914.18 | 0.280179E+10 | 0.00 | 73812254.19 | 0.00 | 0.33 |
June | 3133141.77 | 0.129196E+11 | 0.00 | 300524.96 | 0.450454E+10 | 0.00 | 11815703.02 | 0.00 | 0.34 |
July | 3721163.72 | 0.168389E+11 | 0.00 | 679.10 | 0.893323E+10 | 0.00 | 554572.92 | 0.00 | 0.37 |
August | 0.00 | 0.195223E+11 | 0.00 | 0.00 | 0.790797E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 286872.08 | 0.146553E+11 | 0.00 | 127003.67 | 0.502697E+10 | 0.00 | 2458486.40 | 0.00 | 0.33 |
October | 39562903.21 | 0.897368E+10 | 0.00 | 1143349.44 | 0.286848E+10 | 0.00 | 54635000.35 | 0.00 | 0.31 |
November | 23749773.36 | 0.473610E+10 | 0.00 | 2826784.10 | 0.664405E+09 | 0.00 | 88974637.76 | 0.00 | 0.30 |
December | 0.263238E+09 | 0.140468E+10 | 0.00 | 14153352.33 | 0.342824E+09 | 0.00 | 0.104680E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.157805E+10 | 0.933473E+11 | 0.00 | 70679423.87 | 0.347633E+11 | 0.00 | 0.614862E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.308227E+09 | 0.00 | 0.00 | 0.161621E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.553036E+09 | 0.195223E+11 | 0.00 | 17818691.09 | 0.893323E+10 | 0.00 | 0.228463E+10 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.902982E+09 | 0.337471E+09 | 0.00 | 11708029.79 | 0.210410E+09 | 0.00 | 0.133986E+10 | 0.00 | 0.31 |
February | 0.454237E+09 | 0.920472E+09 | 0.00 | 9953135.84 | 0.218872E+09 | 0.00 | 0.751638E+09 | 0.00 | 0.30 |
March | 0.299900E+09 | 0.178639E+10 | 0.00 | 9406015.68 | 0.215162E+09 | 0.00 | 0.660823E+09 | 0.00 | 0.32 |
April | 0.107828E+09 | 0.362157E+10 | 0.00 | 3866784.41 | 0.111074E+10 | 0.00 | 0.218830E+09 | 0.00 | 0.31 |
May | 23410947.83 | 0.764780E+10 | 0.00 | 1179656.68 | 0.289035E+10 | 0.00 | 47735253.73 | 0.00 | 0.33 |
June | 4030292.47 | 0.127588E+11 | 0.00 | 350171.47 | 0.474841E+10 | 0.00 | 11152886.98 | 0.00 | 0.35 |
July | 1579118.60 | 0.170142E+11 | 0.00 | 0.00 | 0.921121E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.194034E+11 | 0.00 | 0.00 | 0.871170E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 151788.24 | 0.144537E+11 | 0.00 | 102591.94 | 0.533229E+10 | 0.00 | 1683407.80 | 0.00 | 0.34 |
October | 37878607.28 | 0.875813E+10 | 0.00 | 1105996.47 | 0.291169E+10 | 0.00 | 30387509.29 | 0.00 | 0.31 |
November | 14708042.53 | 0.480866E+10 | 0.00 | 2197933.33 | 0.715522E+09 | 0.00 | 57658731.98 | 0.00 | 0.30 |
December | 0.382954E+09 | 0.144048E+10 | 0.00 | 8969121.51 | 0.454142E+09 | 0.00 | 0.543222E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.222966E+10 | 0.929511E+11 | 0.00 | 48839437.12 | 0.367305E+11 | 0.00 | 0.366299E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.337471E+09 | 0.00 | 0.00 | 0.210410E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.902982E+09 | 0.194034E+11 | 0.00 | 11708029.79 | 0.921121E+10 | 0.00 | 0.133986E+10 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267666E+09 | 65670373.37 | 0.00 | 1996142.58 | 52428582.78 | 0.00 | 0.190466E+09 | 0.00 | 0.30 |
February | 0.123252E+09 | 0.193833E+09 | 0.00 | 2162312.68 | 72337154.00 | 0.00 | 0.139095E+09 | 0.00 | 0.32 |
March | 87448160.83 | 0.499187E+09 | 0.00 | 2067507.92 | 46992928.73 | 0.00 | 0.127511E+09 | 0.00 | 0.37 |
April | 37866362.90 | 0.124959E+10 | 0.00 | 906910.80 | 0.171292E+09 | 0.00 | 33407356.54 | 0.00 | 0.42 |
May | 4313532.89 | 0.330141E+10 | 0.00 | 318658.34 | 0.289606E+09 | 0.00 | 12364375.17 | 0.00 | 0.53 |
June | 699917.06 | 0.582015E+10 | 0.00 | 117030.57 | 0.420341E+09 | 0.00 | 3020678.08 | 0.00 | 0.58 |
July | 201327.51 | 0.846883E+10 | 0.00 | 8836.65 | 0.936080E+09 | 0.00 | 137349.33 | 0.00 | 0.65 |
August | 0.00 | 0.897359E+10 | 0.00 | 0.00 | 0.946896E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 32063.56 | 0.599128E+10 | 0.00 | 21731.47 | 0.608557E+09 | 0.00 | 370518.54 | 0.00 | 0.53 |
October | 8173147.58 | 0.300619E+10 | 0.00 | 333810.79 | 0.430428E+09 | 0.00 | 7473573.98 | 0.00 | 0.44 |
November | 4013488.98 | 0.129162E+10 | 0.00 | 549508.04 | 0.158098E+09 | 0.00 | 14223007.14 | 0.00 | 0.36 |
December | 96461260.01 | 0.321067E+09 | 0.00 | 1794222.09 | 0.112144E+09 | 0.00 | 99362247.99 | 0.00 | 0.31 |
Annual Sum or Average | 0.630128E+09 | 0.391824E+11 | 0.00 | 10276671.95 | 0.424520E+10 | 0.00 | 0.627431E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 65670373.37 | 0.00 | 0.00 | 46992928.73 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.267666E+09 | 0.897359E+10 | 0.00 | 2162312.68 | 0.946896E+09 | 0.00 | 0.190466E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134786E+09 | 61685183.63 | 0.00 | 2060643.59 | 27846137.04 | 0.00 | 0.207515E+09 | 0.00 | 0.37 |
February | 64984602.83 | 0.164571E+09 | 0.00 | 2021934.97 | 29777546.93 | 0.00 | 0.135181E+09 | 0.00 | 0.40 |
March | 49085252.61 | 0.415713E+09 | 0.00 | 1826156.54 | 23573693.11 | 0.00 | 0.109373E+09 | 0.00 | 0.47 |
April | 21214200.87 | 0.106072E+10 | 0.00 | 888502.60 | 70913383.60 | 0.00 | 33954724.25 | 0.00 | 0.55 |
May | 2302922.98 | 0.256823E+10 | 0.00 | 270264.30 | 0.151605E+09 | 0.00 | 9405470.95 | 0.00 | 0.65 |
June | 441103.37 | 0.437263E+10 | 0.00 | 96321.04 | 0.241164E+09 | 0.00 | 2214172.66 | 0.00 | 0.68 |
July | 122573.88 | 0.629017E+10 | 0.00 | 7256.54 | 0.555232E+09 | 0.00 | 117217.98 | 0.00 | 0.76 |
August | 0.00 | 0.681541E+10 | 0.00 | 0.00 | 0.546884E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 20207.17 | 0.468776E+10 | 0.00 | 14644.29 | 0.324512E+09 | 0.00 | 238442.17 | 0.00 | 0.65 |
October | 2296261.94 | 0.252056E+10 | 0.00 | 400120.52 | 0.196320E+09 | 0.00 | 10943389.14 | 0.00 | 0.55 |
November | 1988938.01 | 0.107163E+10 | 0.00 | 437415.50 | 75195710.96 | 0.00 | 10947242.56 | 0.00 | 0.45 |
December | 49539021.95 | 0.270576E+09 | 0.00 | 1599780.22 | 56833156.33 | 0.00 | 93303746.73 | 0.00 | 0.37 |
Annual Sum or Average | 0.326781E+09 | 0.302997E+11 | 0.00 | 9623040.11 | 0.229986E+10 | 0.00 | 0.613194E+09 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 61685183.63 | 0.00 | 0.00 | 23573693.11 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.134786E+09 | 0.681541E+10 | 0.00 | 2060643.59 | 0.555232E+09 | 0.00 | 0.207515E+09 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194742E+09 | 0.172802E+09 | 0.00 | 5198718.02 | 20331710.40 | 0.00 | 0.506333E+09 | 0.00 | 0.49 |
February | 0.102125E+09 | 0.348561E+09 | 0.00 | 4486288.84 | 28215365.40 | 0.00 | 0.284121E+09 | 0.00 | 0.49 |
March | 79462703.97 | 0.688059E+09 | 0.00 | 3215644.88 | 32771528.25 | 0.00 | 0.196937E+09 | 0.00 | 0.49 |
April | 37180381.37 | 0.148234E+10 | 0.00 | 1062813.57 | 0.134281E+09 | 0.00 | 36671684.72 | 0.00 | 0.48 |
May | 4389411.06 | 0.328604E+10 | 0.00 | 317423.17 | 0.298492E+09 | 0.00 | 12216366.11 | 0.00 | 0.53 |
June | 698602.41 | 0.553188E+10 | 0.00 | 113542.82 | 0.453857E+09 | 0.00 | 2984683.09 | 0.00 | 0.55 |
July | 200949.35 | 0.831879E+10 | 0.00 | 8578.56 | 0.975199E+09 | 0.00 | 130460.86 | 0.00 | 0.64 |
August | 0.00 | 0.944717E+10 | 0.00 | 0.00 | 0.929162E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 32003.33 | 0.720709E+10 | 0.00 | 22732.98 | 0.505547E+09 | 0.00 | 375636.59 | 0.00 | 0.62 |
October | 5527217.60 | 0.432235E+10 | 0.00 | 765575.53 | 0.267752E+09 | 0.00 | 15949875.55 | 0.00 | 0.60 |
November | 3412229.01 | 0.211566E+10 | 0.00 | 964060.87 | 76024057.73 | 0.00 | 24498889.80 | 0.00 | 0.56 |
December | 74678309.53 | 0.677904E+09 | 0.00 | 4135598.80 | 49308669.32 | 0.00 | 0.230384E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.502449E+09 | 0.435986E+11 | 0.00 | 20290978.03 | 0.377094E+10 | 0.00 | 0.131060E+10 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.172802E+09 | 0.00 | 0.00 | 20331710.40 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.194742E+09 | 0.944717E+10 | 0.00 | 5198718.02 | 0.975199E+09 | 0.00 | 0.506333E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154292E+09 | 64245024.98 | 0.00 | 1950474.96 | 25743585.93 | 0.00 | 0.188909E+09 | 0.00 | 0.36 |
February | 73129262.63 | 0.173095E+09 | 0.00 | 2051462.57 | 30076966.45 | 0.00 | 0.136164E+09 | 0.00 | 0.40 |
March | 52487811.45 | 0.431218E+09 | 0.00 | 1858415.77 | 19046306.08 | 0.00 | 0.122079E+09 | 0.00 | 0.48 |
April | 23421234.11 | 0.109677E+10 | 0.00 | 683539.79 | 73021521.92 | 0.00 | 23554093.43 | 0.00 | 0.53 |
May | 2575789.22 | 0.267006E+10 | 0.00 | 227586.75 | 0.137909E+09 | 0.00 | 8505313.06 | 0.00 | 0.64 |
June | 443185.29 | 0.452151E+10 | 0.00 | 78118.86 | 0.214939E+09 | 0.00 | 2019025.86 | 0.00 | 0.68 |
July | 123152.40 | 0.643808E+10 | 0.00 | 7093.37 | 0.520801E+09 | 0.00 | 101365.04 | 0.00 | 0.75 |
August | 0.00 | 0.701525E+10 | 0.00 | 0.00 | 0.509520E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 20302.54 | 0.491798E+10 | 0.00 | 14998.24 | 0.280636E+09 | 0.00 | 241529.05 | 0.00 | 0.64 |
October | 4822630.05 | 0.249615E+10 | 0.00 | 243270.37 | 0.190323E+09 | 0.00 | 5379163.84 | 0.00 | 0.54 |
November | 2541328.62 | 0.106254E+10 | 0.00 | 479388.38 | 72273235.41 | 0.00 | 13141035.33 | 0.00 | 0.45 |
December | 57442294.93 | 0.281684E+09 | 0.00 | 1627671.30 | 58991790.06 | 0.00 | 94440622.70 | 0.00 | 0.37 |
Annual Sum or Average | 0.371299E+09 | 0.311686E+11 | 0.00 | 9222020.37 | 0.213328E+10 | 0.00 | 0.594534E+09 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 64245024.98 | 0.00 | 0.00 | 19046306.08 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.154292E+09 | 0.701525E+10 | 0.00 | 2051462.57 | 0.520801E+09 | 0.00 | 0.188909E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195466E+09 | 44080269.47 | 0.00 | 3512800.62 | 32889668.06 | 0.00 | 0.316812E+09 | 0.00 | 0.26 |
February | 0.108445E+09 | 0.164086E+09 | 0.00 | 2722683.05 | 35665783.11 | 0.00 | 0.172614E+09 | 0.00 | 0.27 |
March | 95748465.01 | 0.371403E+09 | 0.00 | 2364989.13 | 46292375.93 | 0.00 | 0.137785E+09 | 0.00 | 0.29 |
April | 44275323.95 | 0.917868E+09 | 0.00 | 779978.02 | 0.239807E+09 | 0.00 | 38160570.62 | 0.00 | 0.33 |
May | 5540641.87 | 0.268832E+10 | 0.00 | 249998.53 | 0.415238E+09 | 0.00 | 11215343.20 | 0.00 | 0.42 |
June | 564264.23 | 0.481400E+10 | 0.00 | 54063.54 | 0.535227E+09 | 0.00 | 1557642.30 | 0.00 | 0.47 |
July | 323147.35 | 0.724250E+10 | 0.00 | 1405.82 | 0.112046E+10 | 0.00 | 50634.79 | 0.00 | 0.55 |
August | 0.00 | 0.816668E+10 | 0.00 | 0.00 | 0.120806E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 6971.87 | 0.555888E+10 | 0.00 | 16487.69 | 0.852004E+09 | 0.00 | 68322.64 | 0.00 | 0.48 |
October | 6433063.87 | 0.293015E+10 | 0.00 | 270045.76 | 0.599885E+09 | 0.00 | 12823738.55 | 0.00 | 0.41 |
November | 9054789.55 | 0.118777E+10 | 0.00 | 702213.66 | 0.187495E+09 | 0.00 | 16245048.43 | 0.00 | 0.34 |
December | 85552838.99 | 0.256463E+09 | 0.00 | 3319196.57 | 80876238.97 | 0.00 | 0.183660E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.551410E+09 | 0.343422E+11 | 0.00 | 13993862.40 | 0.535390E+10 | 0.00 | 0.890993E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 44080269.47 | 0.00 | 0.00 | 32889668.06 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.195466E+09 | 0.816668E+10 | 0.00 | 3512800.62 | 0.120806E+10 | 0.00 | 0.316812E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 89803279.70 | 37052714.74 | 0.00 | 3523614.30 | 20546564.07 | 0.00 | 0.314553E+09 | 0.00 | 0.33 |
February | 55380388.78 | 0.128817E+09 | 0.00 | 2693087.79 | 18332550.75 | 0.00 | 0.168861E+09 | 0.00 | 0.34 |
March | 48489451.01 | 0.309906E+09 | 0.00 | 2244033.71 | 24317190.15 | 0.00 | 0.127989E+09 | 0.00 | 0.37 |
April | 21779546.03 | 0.835231E+09 | 0.00 | 828111.83 | 88778586.37 | 0.00 | 42029743.30 | 0.00 | 0.43 |
May | 2645334.85 | 0.222230E+10 | 0.00 | 241700.97 | 0.181110E+09 | 0.00 | 9549872.49 | 0.00 | 0.53 |
June | 359132.35 | 0.377483E+10 | 0.00 | 41287.02 | 0.254966E+09 | 0.00 | 1138079.22 | 0.00 | 0.57 |
July | 205670.78 | 0.563965E+10 | 0.00 | 1336.58 | 0.570493E+09 | 0.00 | 35360.24 | 0.00 | 0.65 |
August | 0.00 | 0.643916E+10 | 0.00 | 0.00 | 0.639749E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 4437.33 | 0.451287E+10 | 0.00 | 12215.16 | 0.414468E+09 | 0.00 | 49965.21 | 0.00 | 0.60 |
October | 1425621.36 | 0.251539E+10 | 0.00 | 333661.46 | 0.244117E+09 | 0.00 | 15297861.96 | 0.00 | 0.52 |
November | 4497948.76 | 0.970226E+09 | 0.00 | 623774.26 | 84291613.37 | 0.00 | 15507759.67 | 0.00 | 0.42 |
December | 41332158.62 | 0.200738E+09 | 0.00 | 2919177.28 | 50267716.03 | 0.00 | 0.168111E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.265923E+09 | 0.275862E+11 | 0.00 | 13462000.37 | 0.259144E+10 | 0.00 | 0.863123E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 37052714.74 | 0.00 | 0.00 | 18332550.75 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 89803279.70 | 0.643916E+10 | 0.00 | 3523614.30 | 0.639749E+09 | 0.00 | 0.314553E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170879E+09 | 0.106123E+09 | 0.00 | 5926758.98 | 12011566.78 | 56499147.61 | 0.449453E+09 | 0.00 | 0.39 |
February | 92024427.79 | 0.297651E+09 | 0.00 | 4648627.35 | 17469622.37 | 26615124.53 | 0.260131E+09 | 0.00 | 0.40 |
March | 91635198.23 | 0.629142E+09 | 0.00 | 3364254.74 | 30711948.62 | 9809751.35 | 0.179074E+09 | 0.00 | 0.42 |
April | 48627762.60 | 0.139095E+10 | 0.00 | 940554.36 | 0.180984E+09 | 47511.45 | 38237308.19 | 0.00 | 0.43 |
May | 5983854.61 | 0.351962E+10 | 0.00 | 339187.76 | 0.424518E+09 | 0.00 | 13140637.76 | 0.00 | 0.54 |
June | 565399.80 | 0.593522E+10 | 0.00 | 59968.32 | 0.611369E+09 | 0.00 | 1721476.17 | 0.00 | 0.59 |
July | 323797.67 | 0.915841E+10 | 0.00 | 1817.98 | 0.115627E+10 | 0.00 | 50327.36 | 0.00 | 0.67 |
August | 0.00 | 0.112167E+11 | 0.00 | 0.00 | 0.110475E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 6985.90 | 0.835373E+10 | 0.00 | 21920.96 | 0.622329E+09 | 0.00 | 89996.54 | 0.00 | 0.68 |
October | 2539951.83 | 0.512566E+10 | 0.00 | 600527.65 | 0.283356E+09 | 0.00 | 22126891.75 | 0.00 | 0.64 |
November | 10170881.40 | 0.225286E+10 | 0.00 | 1045984.09 | 74020006.52 | 0.00 | 21135845.83 | 0.00 | 0.55 |
December | 83283728.33 | 0.535657E+09 | 0.00 | 5375682.00 | 33098764.28 | 10298790.94 | 0.276231E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.506041E+09 | 0.485218E+11 | 0.00 | 22325284.18 | 0.455089E+10 | 0.103270E+09 | 0.126139E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.106123E+09 | 0.00 | 0.00 | 12011566.78 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.170879E+09 | 0.112167E+11 | 0.00 | 5926758.98 | 0.115627E+10 | 56499147.61 | 0.449453E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112788E+09 | 39567545.98 | 0.00 | 3166300.03 | 18785020.20 | 0.00 | 0.274577E+09 | 0.00 | 0.32 |
February | 65077961.88 | 0.141872E+09 | 0.00 | 2494060.18 | 16542286.41 | 0.00 | 0.155265E+09 | 0.00 | 0.34 |
March | 52125566.49 | 0.340018E+09 | 0.00 | 2169706.64 | 16816634.31 | 0.00 | 0.130300E+09 | 0.00 | 0.38 |
April | 20738470.36 | 0.888299E+09 | 0.00 | 626920.67 | 77000334.45 | 0.00 | 34388447.12 | 0.00 | 0.41 |
May | 2849072.72 | 0.233926E+10 | 0.00 | 196973.42 | 0.145939E+09 | 0.00 | 8598878.19 | 0.00 | 0.52 |
June | 245630.51 | 0.395910E+10 | 0.00 | 43948.46 | 0.198452E+09 | 0.00 | 1332119.04 | 0.00 | 0.57 |
July | 204855.10 | 0.581222E+10 | 0.00 | 1620.79 | 0.522068E+09 | 0.00 | 42532.05 | 0.00 | 0.65 |
August | 0.00 | 0.665735E+10 | 0.00 | 0.00 | 0.578554E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 4419.73 | 0.476034E+10 | 0.00 | 12771.15 | 0.349578E+09 | 0.00 | 52033.44 | 0.00 | 0.60 |
October | 4018247.34 | 0.255813E+10 | 0.00 | 208420.59 | 0.217774E+09 | 0.00 | 9110452.84 | 0.00 | 0.51 |
November | 4624989.14 | 0.100574E+10 | 0.00 | 575742.47 | 74289309.65 | 0.00 | 13719290.33 | 0.00 | 0.42 |
December | 49014468.05 | 0.222842E+09 | 0.00 | 2750695.05 | 43354102.49 | 0.00 | 0.155823E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.311692E+09 | 0.287247E+11 | 0.00 | 12247159.47 | 0.225915E+10 | 0.00 | 0.783209E+09 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 39567545.98 | 0.00 | 0.00 | 16542286.41 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.112788E+09 | 0.665735E+10 | 0.00 | 3166300.03 | 0.578554E+09 | 0.00 | 0.274577E+09 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285363E+09 | 62983969.89 | 0.00 | 2496093.46 | 38992574.92 | 0.00 | 0.255269E+09 | 0.00 | 0.30 |
February | 0.140987E+09 | 0.203106E+09 | 0.00 | 2437913.28 | 48828119.29 | 0.00 | 0.166615E+09 | 0.00 | 0.32 |
March | 0.103902E+09 | 0.499333E+09 | 0.00 | 2468909.37 | 50360487.90 | 0.00 | 0.155570E+09 | 0.00 | 0.37 |
April | 41971687.68 | 0.124719E+10 | 0.00 | 959947.90 | 0.203422E+09 | 0.00 | 55355080.50 | 0.00 | 0.42 |
May | 6364531.48 | 0.331385E+10 | 0.00 | 396751.41 | 0.327996E+09 | 0.00 | 16738906.49 | 0.00 | 0.52 |
June | 728748.65 | 0.582802E+10 | 0.00 | 89303.61 | 0.437713E+09 | 0.00 | 2782954.22 | 0.00 | 0.57 |
July | 591777.04 | 0.831114E+10 | 0.00 | 12800.92 | 0.877439E+09 | 0.00 | 347205.80 | 0.00 | 0.61 |
August | 0.00 | 0.898947E+10 | 0.00 | 0.00 | 0.885202E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 60560.65 | 0.595849E+10 | 0.00 | 25911.68 | 0.638091E+09 | 0.00 | 533903.08 | 0.00 | 0.51 |
October | 8997243.79 | 0.299957E+10 | 0.00 | 292460.41 | 0.475082E+09 | 0.00 | 11159239.61 | 0.00 | 0.43 |
November | 9404891.64 | 0.127538E+10 | 0.00 | 516096.36 | 0.153245E+09 | 0.00 | 14273396.27 | 0.00 | 0.36 |
December | 0.121975E+09 | 0.320647E+09 | 0.00 | 2245726.84 | 82453494.32 | 0.00 | 0.138935E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.720346E+09 | 0.390092E+11 | 0.00 | 11941915.24 | 0.421882E+10 | 0.00 | 0.817579E+09 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 62983969.89 | 0.00 | 0.00 | 38992574.92 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.285363E+09 | 0.898947E+10 | 0.00 | 2496093.46 | 0.885202E+09 | 0.00 | 0.255269E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140456E+09 | 48868452.12 | 0.00 | 2315225.41 | 22068122.47 | 0.00 | 0.247368E+09 | 0.00 | 0.34 |
February | 74332558.82 | 0.152573E+09 | 0.00 | 2158680.06 | 20429685.36 | 0.00 | 0.152468E+09 | 0.00 | 0.37 |
March | 55744262.42 | 0.382727E+09 | 0.00 | 2090794.55 | 25825408.58 | 0.00 | 0.129336E+09 | 0.00 | 0.43 |
April | 24609387.50 | 0.101841E+10 | 0.00 | 895115.50 | 78500598.15 | 0.00 | 49717293.01 | 0.00 | 0.52 |
May | 2704523.07 | 0.250662E+10 | 0.00 | 341623.88 | 0.165191E+09 | 0.00 | 14157762.93 | 0.00 | 0.62 |
June | 461467.61 | 0.425920E+10 | 0.00 | 70241.48 | 0.237116E+09 | 0.00 | 1951596.75 | 0.00 | 0.65 |
July | 367107.49 | 0.604463E+10 | 0.00 | 14133.89 | 0.483956E+09 | 0.00 | 308485.55 | 0.00 | 0.70 |
August | 0.00 | 0.668078E+10 | 0.00 | 0.00 | 0.484471E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 33556.21 | 0.454485E+10 | 0.00 | 17398.91 | 0.322006E+09 | 0.00 | 349450.32 | 0.00 | 0.61 |
October | 2656423.05 | 0.241936E+10 | 0.00 | 356394.80 | 0.210536E+09 | 0.00 | 15131553.68 | 0.00 | 0.52 |
November | 4665549.51 | 0.975096E+09 | 0.00 | 432689.91 | 76457417.74 | 0.00 | 12729755.43 | 0.00 | 0.42 |
December | 62242907.40 | 0.234101E+09 | 0.00 | 1889188.08 | 47240689.56 | 0.00 | 0.122488E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.368274E+09 | 0.292672E+11 | 0.00 | 10581486.47 | 0.217380E+10 | 0.00 | 0.746006E+09 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 48868452.12 | 0.00 | 0.00 | 20429685.36 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.140456E+09 | 0.668078E+10 | 0.00 | 2315225.41 | 0.484471E+09 | 0.00 | 0.247368E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203997E+09 | 0.159430E+09 | 0.00 | 5973702.96 | 10687594.75 | 0.00 | 0.591484E+09 | 0.00 | 0.48 |
February | 0.119573E+09 | 0.351343E+09 | 0.00 | 4745725.45 | 16421904.62 | 0.00 | 0.314461E+09 | 0.00 | 0.48 |
March | 94037540.32 | 0.706542E+09 | 0.00 | 3649424.59 | 28146853.70 | 0.00 | 0.226439E+09 | 0.00 | 0.49 |
April | 41335426.07 | 0.151448E+10 | 0.00 | 1066740.35 | 0.146103E+09 | 0.00 | 58172369.62 | 0.00 | 0.47 |
May | 6356527.14 | 0.329747E+10 | 0.00 | 386720.30 | 0.345518E+09 | 0.00 | 16476329.78 | 0.00 | 0.52 |
June | 727087.69 | 0.551333E+10 | 0.00 | 86438.31 | 0.501866E+09 | 0.00 | 2752316.61 | 0.00 | 0.54 |
July | 599797.51 | 0.813482E+10 | 0.00 | 11744.58 | 0.948163E+09 | 0.00 | 314042.93 | 0.00 | 0.61 |
August | 0.00 | 0.951031E+10 | 0.00 | 0.00 | 0.851537E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 52871.11 | 0.726600E+10 | 0.00 | 27090.64 | 0.509381E+09 | 0.00 | 549239.63 | 0.00 | 0.61 |
October | 6110452.91 | 0.439715E+10 | 0.00 | 715458.42 | 0.289819E+09 | 0.00 | 19694851.04 | 0.00 | 0.60 |
November | 7794739.37 | 0.209050E+10 | 0.00 | 924221.97 | 60883269.95 | 0.00 | 24677301.74 | 0.00 | 0.54 |
December | 95210376.44 | 0.644943E+09 | 0.00 | 4920703.87 | 36494456.26 | 0.00 | 0.290433E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.575795E+09 | 0.435863E+11 | 0.00 | 22507971.45 | 0.374502E+10 | 0.00 | 0.154545E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.159430E+09 | 0.00 | 0.00 | 10687594.75 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.203997E+09 | 0.951031E+10 | 0.00 | 5973702.96 | 0.948163E+09 | 0.00 | 0.591484E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160376E+09 | 59604157.28 | 0.00 | 2313467.42 | 19772040.63 | 0.00 | 0.237049E+09 | 0.00 | 0.35 |
February | 82767765.45 | 0.176654E+09 | 0.00 | 2209274.02 | 19757359.78 | 0.00 | 0.153974E+09 | 0.00 | 0.39 |
March | 62650486.25 | 0.445304E+09 | 0.00 | 2105299.74 | 16370149.87 | 0.00 | 0.139058E+09 | 0.00 | 0.47 |
April | 25174545.64 | 0.113954E+10 | 0.00 | 692064.42 | 72063410.23 | 0.00 | 37852019.60 | 0.00 | 0.53 |
May | 3513938.96 | 0.275999E+10 | 0.00 | 275618.81 | 0.134975E+09 | 0.00 | 11596600.37 | 0.00 | 0.63 |
June | 459832.76 | 0.462899E+10 | 0.00 | 60092.39 | 0.189910E+09 | 0.00 | 1878861.11 | 0.00 | 0.68 |
July | 360321.54 | 0.644422E+10 | 0.00 | 10218.51 | 0.444751E+09 | 0.00 | 256813.34 | 0.00 | 0.72 |
August | 0.00 | 0.714378E+10 | 0.00 | 0.00 | 0.447316E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 33437.32 | 0.498186E+10 | 0.00 | 17961.71 | 0.272020E+09 | 0.00 | 352005.85 | 0.00 | 0.63 |
October | 5589942.00 | 0.253683E+10 | 0.00 | 210751.35 | 0.202990E+09 | 0.00 | 7464807.06 | 0.00 | 0.54 |
November | 5853277.00 | 0.105929E+10 | 0.00 | 442067.19 | 62783703.45 | 0.00 | 12361750.31 | 0.00 | 0.44 |
December | 72661880.70 | 0.276379E+09 | 0.00 | 1931516.70 | 45637984.52 | 0.00 | 0.121929E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.419442E+09 | 0.316525E+11 | 0.00 | 10268332.26 | 0.192835E+10 | 0.00 | 0.723774E+09 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 59604157.28 | 0.00 | 0.00 | 16370149.87 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.160376E+09 | 0.714378E+10 | 0.00 | 2313467.42 | 0.447316E+09 | 0.00 | 0.237049E+09 | 0.00 | 0.74 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.148252E+12 | 0.202004E+10 | 0.00 | 0.233445E+11 | 0.118802E+12 |
February | 0.162579E+12 | 0.689208E+09 | 0.00 | 0.651175E+10 | 0.134020E+12 |
March | 0.198549E+12 | -640627180.2 | 0.00 | -0.478970E+10 | 0.188812E+12 |
April | 0.208122E+12 | -0.335037E+10 | 0.00 | -0.405251E+11 | 0.237670E+12 |
May | 0.215450E+12 | -0.801636E+10 | 0.00 | -0.977994E+11 | 0.371237E+12 |
June | 0.204991E+12 | -0.128042E+11 | 0.00 | -0.161534E+12 | 0.450279E+12 |
July | 0.201856E+12 | -0.169300E+11 | 0.00 | -0.222366E+12 | 0.552397E+12 |
August | 0.196357E+12 | -0.188257E+11 | 0.00 | -0.238364E+12 | 0.598732E+12 |
September | 0.176306E+12 | -0.136664E+11 | 0.00 | -0.185970E+12 | 0.465886E+12 |
October | 0.153949E+12 | -0.829507E+10 | 0.00 | -0.114765E+12 | 0.360680E+12 |
November | 0.127018E+12 | -0.392335E+10 | 0.00 | -0.476073E+11 | 0.247052E+12 |
December | 0.127720E+12 | 0.214396E+09 | 0.00 | -0.247081E+10 | 0.154046E+12 |
Annual Sum or Average | 0.212115E+13 | -0.835284E+11 | 0.00 | -0.108634E+13 | 0.387961E+13 |
Minimum of Months | 0.127018E+12 | -0.188257E+11 | 0.00 | -0.238364E+12 | 0.118802E+12 |
Maximum of Months | 0.215450E+12 | 0.202004E+10 | 0.00 | 0.233445E+11 | 0.598732E+12 |