Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20

Tabular Output Report in Format: HTML

Building: OfficeMedium

Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695

Simulation Timestamp: 2024-07-03 12:20:08


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1713.11 343.85 343.85
Net Site Energy 1713.11 343.85 343.85
Total Source Energy 4713.39 946.05 946.05
Net Source Energy 4713.39 946.05 946.05


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4982.19
Net Conditioned Building Area 4982.19
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 341.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 165.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 232.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 50.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 118.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 55.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1371.28 341.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 341.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 165.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 232.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 50.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 134.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 0.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 584.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 118.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
  Water Heater 55.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 341.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 165.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 232.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 50.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 719.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 26.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 118.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 55.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.06
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 68.58 68.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 275.24 68.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 56.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 68.58 68.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Other 149.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 275.24 68.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1371.281 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1371.281 100.00
     
Total On-Site and Utility Electric Sources 1371.281 100.00
Total Electricity End Uses 1371.281 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 271.06 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 271.06 100.00
Total Water End Uses 271.06 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 280.83
Time Setpoint Not Met During Occupied Cooling 215.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2220.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneHeatingSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ZoneElectricSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

SpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

ComfortReportSimple55Monthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

OccupantComfortDataSummaryMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

WindowEnergyZoneSummaryMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| PACU_VAV_BOT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_MID HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_TOP HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

FanReportMonthly

| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |

PumpReportMonthly

| HEATSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

AirLoopSystemEnergyAndWaterUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentLoadsMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

AirLoopSystemComponentEnergyUseMonthly

| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |

MechanicalVentilationLoadsMonthly

| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
RunPeriod RUNPERIOD 1
Weather File Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Latitude [deg] 39.72
Longitude [deg] -104.8
Elevation [m] 1726.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Above Ground Wall Area [m2] 1977.67 593.30 395.53 593.30 395.53
Window Opening Area [m2] 652.62 195.79 130.53 195.79 130.53
Gross Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00
Above Ground Window-Wall Ratio [%] 33.00 33.00 33.00 33.00 33.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1660.73
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_BOTTOM 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 89.4590
TOPFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
FIRSTFLOOR_PLENUM 1660.73 Yes No 2024.76 1.00 202.84 0.00 0.00 0.00 0.0000   0.0000
CORE_MID 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
CORE_TOP 983.54 Yes Yes 2698.04 1.00 0.00 0.00 0.00 0.00 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_TOP_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_TOP_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_TOP_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_BOT_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_BOT_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_BOT_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
PERIMETER_MID_ZN_3 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0700
PERIMETER_MID_ZN_2 131.26 Yes Yes 360.08 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0695
PERIMETER_MID_ZN_1 207.34 Yes Yes 568.77 1.00 136.92 0.00 65.26 65.26 6.6636 18.58 8.0699
PERIMETER_MID_ZN_4 131.25 Yes Yes 360.05 1.00 91.28 0.00 43.51 43.51 6.6636 18.58 8.0700
Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Conditioned Total 4982.19     13667.13   1369.16 0.00 652.62 652.62 6.6636 18.58 24.1370
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 4982.19     6074.28   608.51 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_BOTTOM 983.54 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.6636 18.58 89.4590  
TOPFLOOR_PLENUM 1660.73 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 1660.73 Yes No 1.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
FIRSTFLOOR_PLENUM 1660.73 Yes No 1.00 FIRSTFLOOR_PLENUM GENERAL FIRSTFLOOR_PLENUM 0.0000 0.00 0.0000  
CORE_MID 983.54 Yes Yes 1.00 CORE_MID GENERAL CORE_MID 6.6636 18.58 8.0700  
CORE_TOP 983.54 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_3 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.6636 18.58 8.0700  
PERIMETER_TOP_ZN_2 131.26 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.6636 18.58 8.0695  
PERIMETER_TOP_ZN_1 207.34 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.6636 18.58 8.0699  
PERIMETER_TOP_ZN_4 131.25 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_3 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.6636 18.58 8.0700  
PERIMETER_BOT_ZN_2 131.26 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.6636 18.58 8.0695  
PERIMETER_BOT_ZN_1 207.34 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.6636 18.58 8.0699  
PERIMETER_BOT_ZN_4 131.25 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_3 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.6636 18.58 8.0700  
PERIMETER_MID_ZN_2 131.26 Yes Yes 1.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.6636 18.58 8.0695  
PERIMETER_MID_ZN_1 207.34 Yes Yes 1.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.6636 18.58 8.0699  
PERIMETER_MID_ZN_4 131.25 Yes Yes 1.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.6636 18.58 8.0700  
Total 4982.19             6.6636 9.29 24.1370  
Conditioned Total 4982.19             6.6636 9.29 24.1370  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 4982.19             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 4982.19 4982.19 0.00 4982.19 6.6636 18.58 24.1370
Total 4982.19 4982.19 0.00 4982.19      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JUN-15:09 23-DEC-07:19 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 242080.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 78282.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 19671.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41670.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 33911.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4249.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 179202.45 242080.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 242080.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 78282.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 19671.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment ElevatorLift 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 57.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MiscPlug 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 33911.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 6.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4249.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 370.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 523.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 735.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 160.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2279.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 85.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 376.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 6.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 176.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 4342.85 370.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 105.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 147.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 75.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 871.67 74.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 74.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 105.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 147.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 32.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 457.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 17.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 75.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 871.67 74.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 3.11 0.240930 0.205000 0.637687 0.642481 0.500000 0.001581 0.000113 0.637687 12.80 0.008000
CORE_MID VAV BOX COMPONENT 2.50 0.299852 0.255000 0.637351 0.799606 0.500000 0.001271 0.000201 0.841069 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 2.67 0.280525 0.238000 0.635844 0.748068 0.500000 0.001358 0.000357 1.50 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.842796 0.187461 0.159000 0.134005 0.499897 0.500000 0.002032 0.000158 0.665214 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.967537 0.103378 0.088000 0.085143 0.300000 0.500000 0.003686 0.000104 0.438072 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.15 0.136861 0.116000 0.133910 0.364963 0.500000 0.002784 0.000159 0.669650 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.12 0.089201 0.076000 0.085213 0.300000 0.500000 0.004271 0.000104 0.438064 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.645882 0.244614 0.208000 0.134344 0.652303 0.500000 0.001558 0.000120 0.502999 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.786340 0.127199 0.108000 0.084925 0.339198 0.500000 0.002995 0.000080 0.334449 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 0.907604 0.174076 0.148000 0.134325 0.464202 0.500000 0.002189 0.000121 0.507458 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 0.868183 0.115201 0.098000 0.085082 0.307202 0.500000 0.003307 0.000080 0.334446 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 0.727280 0.217236 0.185000 0.134547 0.579297 0.500000 0.001754 0.000123 0.516962 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 0.955971       0.300000 0.500000 0.003641 0.000082 0.343114 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 1.04 0.152128 0.129000 0.133973 0.405674 0.500000 0.002504 0.000124 0.520764 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 1.03 0.097049 0.082000 0.084507 0.300000 0.500000 0.003926 0.000082 0.343111 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 12951.56 0.000113 306.56
CORE_MID VAV BOX REHEAT COIL 22966.20 0.000201 606.62
CORE_TOP VAV BOX REHEAT COIL 40759.18 0.000357 1075.46
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18092.85 0.000158 477.04
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11914.28 0.000104 314.12
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18213.35 0.000159 480.21
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11914.07 0.000104 314.12
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13686.33 0.000120 360.92
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9099.40 0.000080 239.95
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 13807.43 0.000121 364.11
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 9099.31 0.000080 239.95
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 14065.89 0.000123 370.92
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 9334.95 0.000082 246.16
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 14169.16 0.000124 373.65
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 9334.85 0.000082 246.16
PACU_VAV_BOT HEATING COIL 24587.88 0.000215 407.20
PACU_VAV_MID HEATING COIL 25321.72 0.000222 416.04
PACU_VAV_TOP HEATING COIL 24311.53 0.000213 406.32
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PACU_VAV_BOT 3.16 1.08 6.32 2.10 5.57 5.57 0.300000 0.377664 5.57
PACU_VAV_MID 3.13 1.08 6.25 2.57 5.25 5.25 0.300000 0.488174 5.25
PACU_VAV_TOP 3.38 1.07 6.76 3.71 6.14 6.14 0.300000 0.603691 6.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s]
PACU_VAV_BOT_OA_CONTROLLER 5.57
PACU_VAV_MID_OA_CONTROLLER 5.25
PACU_VAV_TOP_OA_CONTROLLER 6.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:TwoSpeed

Design Size High Speed Rated Air Flow Rate [m3/s] Design Size High Speed Gross Rated Total Cooling Capacity [W] Design Size High Speed Rated Sensible Heat Ratio Design Size Low Speed Rated Air Flow Rate [m3/s] Design Size Low Speed Gross Rated Total Cooling Capacity [W] Design Size Low Speed Gross Rated Sensible Heat Ratio
PACU_VAV_BOT COOLING COIL 5.57 92223.28 0.800655 1.86 30738.02 0.800655
PACU_VAV_MID COOLING COIL 5.25 86977.54 0.800655 1.75 28989.61 0.800655
PACU_VAV_TOP COOLING COIL 6.14 101651.65 0.800655 2.05 33880.49 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
PACU_VAV_BOT FAN 5.57
PACU_VAV_MID FAN 5.25
PACU_VAV_TOP FAN 6.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s]
PACU_VAV_BOT_HEATC_CONTROLLER 0.000215
PACU_VAV_MID_HEATC_CONTROLLER 0.000222
PACU_VAV_TOP_HEATC_CONTROLLER 0.000213
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002656 0.318754
SWHSYS1 0.000054 0.006435
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
HEATSYS1 PUMP 0.002656 792.04 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 303629.94 303629.94 0.002656
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000054 6.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000054
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 7.10 3.00 -1.00 0.80 -0.20 4.80 6.10 13.70 22.20 22.70 21.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 39.72 -104.75 -7.00 1726.00 82237 0.9774


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.95 23.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeMedium 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 18 167 24


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_BOTTOM 0.0 0.00 0.00 0.00 24.96 16.64 1.37 1 1 1 4.57 45.34 4.57 28.70 0.00 2.74 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
2 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 11.28 1 1 1 0.00 49.91 0.00 33.27 10.67 11.89 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 10 0 0 No
3 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 7.32 1 1 1 0.00 49.91 0.00 33.27 6.71 7.92 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
4 FIRSTFLOOR_PLENUM 0.0 0.00 0.00 0.00 24.96 16.64 3.35 1 1 1 0.00 49.91 0.00 33.27 2.74 3.96 1.22 2024.76 TARP TARP 1660.73 202.84 202.84 0.00 14 0 0 No
5 CORE_MID 0.0 0.00 0.00 0.00 24.96 16.64 5.33 1 1 1 4.57 45.34 4.57 28.70 3.96 6.71 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
6 CORE_TOP 0.0 0.00 0.00 0.00 24.96 16.64 9.30 1 1 1 4.57 45.34 4.57 28.70 7.92 10.67 2.74 2698.04 TARP TARP 983.54 0.00 0.00 0.00 6 0 0 Yes
7 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 9.30 1 1 1 0.00 49.91 28.70 33.27 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
8 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 9.30 1 1 1 45.34 49.91 0.00 33.27 7.92 10.67 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
9 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 9.30 1 1 1 0.00 49.91 0.00 4.57 7.92 10.67 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
10 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 9.30 1 1 1 0.00 4.57 0.00 33.27 7.92 10.67 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes
11 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 1.37 1 1 1 0.00 49.91 28.70 33.27 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
12 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 1.37 1 1 1 45.34 49.91 0.00 33.27 0.00 2.74 2.74 360.08 TARP TARP 131.26 91.28 45.82 43.51 6 3 0 Yes
13 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 1.37 1 1 1 0.00 49.91 0.00 4.57 0.00 2.74 2.74 568.77 TARP TARP 207.34 136.92 67.75 65.26 6 5 0 Yes
14 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 1.37 1 1 1 0.00 4.57 0.00 33.27 0.00 2.74 2.74 360.05 TARP TARP 131.25 91.28 45.82 43.51 6 3 0 Yes
15 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 24.96 31.11 5.33 1 1 1 0.00 49.91 28.70 33.27 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
16 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 47.82 16.64 5.33 1 1 1 45.34 49.91 0.00 33.27 3.96 6.71 2.74 360.08 TARP TARP 131.26 91.28 47.77 43.51 6 1 0 Yes
17 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 24.96 2.16 5.33 1 1 1 0.00 49.91 0.00 4.57 3.96 6.71 2.74 568.77 TARP TARP 207.34 136.92 71.65 65.26 6 1 0 Yes
18 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.09 16.64 5.33 1 1 1 0.00 4.57 0.00 33.27 3.96 6.71 2.74 360.05 TARP TARP 131.25 91.28 47.77 43.51 6 1 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_BOTTOM 983.54 52.9 18.579 5.382E-002 6.664 89.459 0.000 0.000 0.000 0.000 96.123 No
2 TOPFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 MIDFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 FIRSTFLOOR_PLENUM 1660.73 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
5 CORE_MID 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
6 CORE_TOP 983.54 52.9 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
7 PERIMETER_TOP_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
8 PERIMETER_TOP_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
9 PERIMETER_TOP_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
10 PERIMETER_TOP_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
11 PERIMETER_BOT_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
12 PERIMETER_BOT_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
13 PERIMETER_BOT_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
14 PERIMETER_BOT_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
15 PERIMETER_MID_ZN_3 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
16 PERIMETER_MID_ZN_2 131.26 7.1 18.579 5.382E-002 6.664 8.069 0.000 0.000 0.000 0.000 14.733 No
17 PERIMETER_MID_ZN_1 207.34 11.2 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No
18 PERIMETER_MID_ZN_4 131.25 7.1 18.579 5.382E-002 6.664 8.070 0.000 0.000 0.000 0.000 14.734 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 983.54 52.9 52.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 53 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 131.26 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 207.34 11.2 11.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 131.25 7.1 7.1 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 7 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
2 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
3 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 983.54 52.9 6553.914 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 6553.914
4 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
5 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
6 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
7 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
8 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
9 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
10 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
11 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624
12 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
13 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 131.26 7.1 874.681 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.681
14 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 207.34 11.2 1381.623 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1381.623
15 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 131.25 7.1 874.624 6.664 123.802 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 874.624


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 ELEVATOR_LIFT_RUNNING ELEVATOR_RUNNING_SCH CORE_BOTTOM 983.54 52.9 76724.000 78.008 1449.300 0.000 0.500 0.000 0.500 ElevatorLift 0.000 4561.242
2 ELEVATOR_LIFT_STANDBY ELEVATOR_STANDBY_SCH CORE_BOTTOM 983.54 52.9 3200.000 3.254 60.447 0.000 0.500 0.000 0.500 ElevatorLift 2563.936 3200.000
3 ELEVATORS_LIGHTS_FAN ELEV_LIGHT_FAN_SCH_ADD_DF CORE_BOTTOM 983.54 52.9 125.000 0.127 2.361 0.000 0.500 0.000 0.500 ElevatorLightsFan 0.000 86.250
4 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
5 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
6 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 983.54 52.9 7937.156 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 7937.156
7 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
8 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
9 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
10 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
11 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
12 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
13 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
14 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210
15 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 207.34 11.2 1673.214 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.214
16 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 131.26 7.1 1059.217 8.069 149.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.217
17 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 207.34 11.2 1673.203 8.070 149.929 0.000 0.500 0.000 0.500 MiscPlug 0.000 1673.203
18 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 131.25 7.1 1059.210 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1059.210


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.065 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
7 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
8 NONRES_EXT_WALL_GRD 20 4 7 0.167 0.8022 0.900 0.900 0.700 0.700 Smooth
9 NONRES_EXT_WALL_MID 21 4 7 0.167 0.7887 0.900 0.900 0.700 0.700 Smooth
10 NONRES_EXT_WALL_TOP 22 4 7 0.167 1.032 0.900 0.900 0.700 0.700 Smooth
11 PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 39 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
12 PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 40 2 7 0.167 0.2365 0.000 0.900 0.000 0.700 MediumRough
13 PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 41 2 7 0.167 0.2242 0.000 0.900 0.000 0.700 MediumRough
14 PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 42 2 7 0.167 0.2366 0.000 0.900 0.000 0.700 MediumRough
15 CORE_BOT_ZN_5_FLOOR_FFACTOR 43 2 8 0.167 0.5650E-02 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.3263
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
9 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
10 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
11 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
12 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
13 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.013
16 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
17 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
18 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 1.034
20 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
21 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
22 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
23 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7350
24 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
25 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 4.383
26 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
27 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 4.151
28 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
29 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 4.383
30 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
31 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 4.150
32 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
33 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 176.9
34 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.0649134 3.0649134 3.0649134  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
23 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
24 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
25 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
26 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
27 2 51.553741 0.22121684 1.2284947 -0.25833933
28 1 -128.86110 0.21944682 -5.1479470 1.1228340
29 0 81.526494 0.16043334E-01 4.4519351  
30 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
31 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
32 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
33 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
34 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
35 2 1.2284947 0.22121684 51.553741 -0.25833933
36 1 -5.1479470 0.21944682 -128.86110 1.1228340
37 0 4.4519351 0.16043334E-01 81.526494  
38 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
39 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
40 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
41 0 21.357363 0.71091016E-01 5.4032014  
42 7 -0.29755900E-12 0.81313074E-15 -0.93602003E-13 0.14510957E-15
43 6 0.28367368E-07 0.22496401E-09 0.65009128E-08 -0.13359594E-12
44 5 -0.18856357E-03 0.19286971E-05 -0.97009749E-04 0.64274374E-08
45 4 0.29034011 0.94012602E-03 0.99033658E-01 -0.33316087E-04
46 3 -7.2305496 0.29163423E-01 -2.3282961 0.28833673E-01
47 2 40.753148 0.10379063 15.221555 -0.33202618
48 1 -80.455373 0.46876469E-01 -29.102648 1.0766925
49 0 46.824339 0.94379271E-03 16.292168  
50 7 -0.29905644E-12 0.21441847E-14 -0.94350753E-13 0.15229914E-15
51 6 0.28527035E-07 0.22156944E-09 0.65361533E-08 -0.13441220E-12
52 5 -0.18937502E-03 0.18976302E-05 -0.97416439E-04 0.64617957E-08
53 4 0.29129073 0.92413897E-03 0.99375489E-01 -0.33450099E-04
54 3 -7.2493786 0.28644335E-01 -2.3338831 0.28925940E-01
55 2 40.815249 0.10187053 15.244478 -0.33271782
56 1 -80.502964 0.45980673E-01 -29.123201 1.0777067
57 0 46.824339 0.92519179E-03 16.291675  
58 7 -0.27570686E-12 0.13707328E-14 -0.80264236E-13 0.78378346E-16
59 6 0.25615968E-07 0.28022365E-09 0.58936169E-08 -0.11887149E-12
60 5 -0.17446821E-03 0.24481169E-05 -0.89927666E-04 0.58344893E-08
61 4 0.27366067 0.12133616E-02 0.93044102E-01 -0.30982017E-04
62 3 -6.8997845 0.38197916E-01 -2.2301787 0.27213971E-01
63 2 39.661773 0.13771433 14.818013 -0.31987377
64 1 -79.618511 0.62899977E-01 -28.740542 1.0588596
65 0 46.824345 0.12804488E-02 16.301062  
66 7 -0.18778705E-08 -0.48456698E-15 0.68415356E-14 -0.90766841E-16
67 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
68 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
69 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
70 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
71 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
72 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
73 0 0.22781756 0.11275910E-04 60.838472  
74 7 -0.17777358E-08 -0.41207670E-15 0.60771148E-14 -0.79247013E-16
75 6 0.66205355E-05 0.45347915E-08 0.31869553E-02 -0.26734852E-04
76 5 -0.47643654E-03 0.26865296E-05 -0.22355891 0.19546881E-02
77 4 0.10961386E-01 0.12229770E-03 4.8267865 -0.45238458E-01
78 3 -0.96263561E-01 0.97262436E-03 -38.005829 0.39848146
79 2 0.34182167 0.16181264E-02 116.45361 -1.4175335
80 1 -0.49337445 0.49308431E-03 -143.88945 2.0487464
81 0 0.24054552 0.11921404E-04 60.838472  
82 7 -0.18778705E-08 -0.48456747E-15 0.68415356E-14 -0.90766840E-16
83 6 0.62832840E-05 0.42957215E-08 0.31879255E-02 -0.26742991E-04
84 5 -0.45150393E-03 0.25448514E-05 -0.22361406 0.19551748E-02
85 4 0.10383635E-01 0.11583744E-03 4.8277051 -0.45247288E-01
86 3 -0.91177470E-01 0.92119394E-03 -38.011019 0.39853883
87 2 0.32374524 0.15324382E-02 116.46371 -1.4176686
88 1 -0.46727348 0.46697369E-03 -143.89540 2.0488441
89 0 0.22781756 0.11275910E-04 60.838472  
90 7 -0.17776120E-08 -0.41258204E-15 0.60425363E-14 -0.82023253E-16
91 6 0.66209765E-05 0.45351028E-08 0.31869540E-02 -0.26734841E-04
92 5 -0.47646911E-03 0.26867147E-05 -0.22355884 0.19546874E-02
93 4 0.10962140E-01 0.12230614E-03 4.8267853 -0.45238446E-01
94 3 -0.96270204E-01 0.97269154E-03 -38.005822 0.39848139
95 2 0.34184528 0.16182383E-02 116.45360 -1.4175333
96 1 -0.49340854 0.49311848E-03 -143.88944 2.0487463
97 0 0.24056214 0.11922214E-04 60.838472  
98 8 0.57026216E-10 -0.29656739E-13 0.26072253E-13 -0.16907584E-15
99 7 -0.80728763E-07 0.14958947E-11 -0.10196182E-04 0.85534123E-07
100 6 0.59163330E-05 0.23390251E-08 0.39199948E-02 -0.33137873E-04
101 5 -0.14678961E-03 0.29443049E-06 -0.24001665 0.21083805E-02
102 4 0.15257864E-02 0.63469284E-05 4.9653291 -0.46676227E-01
103 3 -0.74362311E-02 0.30151767E-04 -38.474208 0.40407555
104 2 0.17883035E-01 0.32406056E-04 117.10039 -1.4265819
105 1 -0.20235698E-01 0.62001922E-05 -144.19380 2.0537490
106 0 0.84795330E-02 0.69040512E-07 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.363_SHGC_EAST_0.378 35 1 VerySmooth 2.062 2.062 1.000 0.379    
2 WINDOW_U_0.363_SHGC_SOUTH_0.378 36 1 VerySmooth 2.062 2.062 1.000 0.379    
3 WINDOW_U_0.363_SHGC_WEST_0.378 37 1 VerySmooth 2.062 2.062 1.000 0.379    
4 WINDOW_U_0.363_SHGC_NORTH_0.378 38 1 VerySmooth 2.062 2.062 1.000 0.379    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.62716E-002 0.29167 0.50232 0.50232 0.41580 0.13603 0.17565 0.00000 0.84000 0.84000 0.11617 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_TOP_ZN_3 1 0
2 PERIMETER_TOP_ZN_2 1 0
3 PERIMETER_TOP_ZN_1 1 0
4 PERIMETER_TOP_ZN_4 1 0
5 PERIMETER_BOT_ZN_3 3 0
6 PERIMETER_BOT_ZN_2 2 0
7 PERIMETER_BOT_ZN_1 3 0
8 PERIMETER_BOT_ZN_4 2 0
9 PERIMETER_MID_ZN_3 1 0
10 PERIMETER_MID_ZN_2 1 0
11 PERIMETER_MID_ZN_1 1 0
12 PERIMETER_MID_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_TOP_ZN_3 0  
2 PERIMETER_TOP_ZN_2 0  
3 PERIMETER_TOP_ZN_1 0  
4 PERIMETER_TOP_ZN_4 0  
5 PERIMETER_BOT_ZN_3 0  
6 PERIMETER_BOT_ZN_2 0  
7 PERIMETER_BOT_ZN_1 0  
8 PERIMETER_BOT_ZN_4 0  
9 PERIMETER_MID_ZN_3 0  
10 PERIMETER_MID_ZN_2 0  
11 PERIMETER_MID_ZN_1 0  
12 PERIMETER_MID_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 27.185 0.8451


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
2 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
3 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
4 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
5 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
6 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
7 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
8 PERIMETER_TOP_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
9 PERIMETER_TOP_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
10 PERIMETER_TOP_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
11 PERIMETER_TOP_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
12 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
13 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
14 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
15 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
16 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
17 BUILDING_ROOF 0 1660.73 183.01 0.00 0 1.22 166.37 39.93 0.00 0 No No
18 PERIMETER_MID_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
19 PERIMETER_MID_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
20 PERIMETER_MID_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
21 PERIMETER_MID_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
22 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
23 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
24 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
25 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
26 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
27 iz-PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
28 iz-PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
29 iz-PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
30 iz-PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
31 iz-CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
32 PERIMETER_BOT_PLENUM_WALL_NORTH 0 593.30 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
33 PERIMETER_BOT_PLENUM_WALL_EAST 0 395.53 143.75 11.89 0 1.22 166.37 39.93 0.00 0 No No
34 PERIMETER_BOT_PLENUM_WALL_SOUTH 0 593.30 123.60 11.89 0 1.22 166.37 39.93 0.00 0 No No
35 PERIMETER_BOT_PLENUM_WALL_WEST 0 395.53 90.32 11.89 0 1.22 166.37 39.93 0.00 0 No No
36 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
37 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
38 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
39 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
40 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
41 iz-PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
42 iz-PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
43 iz-PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
44 iz-PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
45 iz-CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 1.22 166.37 39.93 0.00 0 No No
46 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
47 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
48 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
49 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
50 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
51 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
52 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
53 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
54 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
55 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
56 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
57 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
58 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
59 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 30.31 -999.00 0 No No
60 PERIMETER_TOP_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
62 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
64 iz-CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
65 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
66 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
68 PERIMETER_TOP_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
70 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
72 iz-CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
73 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
74 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
76 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
78 PERIMETER_TOP_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
80 iz-CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
81 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
82 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
84 PERIMETER_TOP_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
86 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
88 iz-CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
89 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
90 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
92 PERIMETER_BOT_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 0 No No
98 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
100 iz-CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
101 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
102 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
104 PERIMETER_BOT_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 0 No No
108 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
110 iz-CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
111 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
112 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
114 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 0 No No
120 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
122 iz-CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
123 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
124 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
126 PERIMETER_BOT_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 0 No No
130 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
132 iz-CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
133 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
134 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
136 PERIMETER_MID_ZN_3_WALL_NORTH 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 3 No No
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 593.30 143.75 11.89 0 2.74 49.91 7.61 0.48 2 No No
138 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
140 iz-CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
141 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
142 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
144 PERIMETER_MID_ZN_2_WALL_EAST 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 3 No No
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 395.53 143.75 11.89 0 2.74 33.27 6.94 0.48 2 No No
146 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
147 iz-PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
148 iz-CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
149 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
150 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
152 PERIMETER_MID_ZN_1_WALL_SOUTH 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 3 No No
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 593.30 123.60 11.89 0 2.74 49.91 7.61 0.48 2 No No
154 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
156 iz-CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
157 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
158 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 49.91 7.61 0.48 0 No No
160 PERIMETER_MID_ZN_4_WALL_WEST 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 3 No No
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 395.53 90.32 11.89 0 2.74 33.27 6.94 0.48 2 No No
162 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
163 iz-PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
164 iz-CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
165 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
166 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 33.27 6.94 0.48 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
2 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
3 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
4 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
5 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
6 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
7 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.492E-004 0.222 0.000 0.000 0.224 0.000
8 PERIMETER_BOT_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_BOT_ZN_1 207.34 11.2 0.679 3.273E-003 4.819E-003 4.296 1.000 0.000 0.000 0.000
9 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.509E-004 0.234 0.000 0.000 0.224 0.000
10 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
11 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 131.26 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
12 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 207.34 11.2 3.509E-002 1.693E-004 2.563E-004 0.222 0.000 0.000 0.224 0.000
13 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 131.25 7.1 2.339E-002 1.782E-004 2.563E-004 0.234 0.000 0.000 0.224 0.000
14 FIRSTFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL FIRSTFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
15 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.563E-004 9.244E-002 0.000 0.000 0.224 0.000
16 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 1660.73 0.0 5.199E-002 3.130E-005 2.790E-005 9.244E-002 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_BOTTOM Mixing/Well-Stirred
2 TOPFLOOR_PLENUM Mixing/Well-Stirred
3 MIDFLOOR_PLENUM Mixing/Well-Stirred
4 FIRSTFLOOR_PLENUM Mixing/Well-Stirred
5 CORE_MID Mixing/Well-Stirred
6 CORE_TOP Mixing/Well-Stirred
7 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
8 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
9 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
10 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
11 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
12 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
13 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
14 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
15 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
16 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
17 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
18 PERIMETER_MID_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2115E-002
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2185E-002
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.3381E-002
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.3442E-002
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2296E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2785E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3510E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3752E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1673
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.9797E-002
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1898
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1018
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1171
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9932E-002
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.8073E-002
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8035E-002
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2114E-002
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2182E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.3379E-002
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.3439E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.2287E-003
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2767E-003
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.3507E-003
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.3749E-003
25 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.9676E-002
26 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.1014E-002
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.4146E-002
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.7166E-002
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.8760E-002
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.4795E-002
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.6444E-002
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6601E-002
33 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.4127E-004
34 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.4391E-004
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.9814E-004
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.0004E-004
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.8688E-004
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.8752E-004
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 5.0780E-004
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 5.0864E-004
41 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6216E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.6789E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.8576E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9030E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3633E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3952E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3507E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3749E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.4064E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.5257E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3885E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9215E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1342E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3231E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.8073E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8035E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6219E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.6792E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.8579E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.9035E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.3638E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.3963E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.3510E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 4.3752E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 7.1305E-002
66 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1788E-002
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.6184E-002
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8137E-002
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 7.0092E-002
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5415E-002
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.6444E-002
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.6601E-002
73 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.5398E-004
74 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.6232E-004
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 6.1423E-004
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 6.2355E-004
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.9599E-004
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.9915E-004
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0782E-004
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.0865E-004
81 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1655
82 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1068
83 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1844
84 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1201
85 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1252
86 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.3046E-002
87 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.4807E-002
88 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.5582E-002
89 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.7376E-002
90 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.9712E-002
91 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.2148E-002
92 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.6039E-002
93 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 6.7160E-002
94 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.3853E-002
95 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.5395E-002
96 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.5971E-002
97 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.0217E-002
98 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.2920E-002
99 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.9352E-002
100 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.5798E-002
101 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.6825E-002
102 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9276E-002
103 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.4807E-002
104 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.5582E-002
105 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.8959E-002
106 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.0471E-002
107 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.4126E-002
108 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.6992E-002
109 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.8457E-002
110 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.4455E-002
111 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.5395E-002
112 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.5971E-002
113 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1655
114 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1068
115 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1844
116 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1200
117 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1252
118 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.3038E-002
119 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.4802E-002
120 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.5579E-002
121 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.7376E-002
122 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.9709E-002
123 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.2147E-002
124 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.6037E-002
125 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 6.7156E-002
126 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.3849E-002
127 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.5390E-002
128 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.5968E-002
129 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.0219E-002
130 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.2919E-002
131 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.9353E-002
132 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.5797E-002
133 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.6823E-002
134 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9274E-002
135 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.4802E-002
136 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.5579E-002
137 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.8959E-002
138 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.0468E-002
139 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.4125E-002
140 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.6989E-002
141 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.8453E-002
142 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.4451E-002
143 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.5390E-002
144 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.5968E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_BOTTOM Cooling 35034.94723 35034.94723 3.11067 3.11067 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.94800 5.45871E-003 983.53657 52.93867 0.42469 0.00000
2 CORE_BOTTOM Heating 7739.75268 7739.75268 0.40167 0.42469 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 983.53657 52.93867 0.42469 0.00000
3 CORE_MID Cooling 28173.38487 28173.38487 2.49941 2.49941 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 22.94800 5.45871E-003 983.53657 52.93867 0.42469 0.00000
4 CORE_MID Heating 16092.15829 16092.15829 0.84107 0.84107 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 983.53657 52.93867 0.42469 0.00000
5 CORE_TOP Cooling 29846.87911 29846.87911 2.67161 2.67161 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.60400 5.47481E-003 983.53657 52.93867 0.42469 0.00000
6 CORE_TOP Heating 28531.33821 28531.33821 1.49613 1.49613 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 983.53657 52.93867 0.42469 0.00000
7 PERIMETER_TOP_ZN_3 Cooling 9415.93307 9415.93307 0.84280 0.84280 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.75200 5.47504E-003 207.33814 11.15994 8.95286E-002 0.00000
8 PERIMETER_TOP_ZN_3 Heating 12657.48264 12657.48264 0.66521 0.66521 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
9 PERIMETER_TOP_ZN_2 Cooling 10809.67001 10809.67001 0.96754 0.96754 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 26.17933 5.46350E-003 131.26219 7.06516 5.66790E-002 0.00000
10 PERIMETER_TOP_ZN_2 Heating 8334.86989 8334.86989 0.43807 0.43807 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.26219 7.06516 5.66790E-002 0.00000
11 PERIMETER_TOP_ZN_1 Cooling 12897.22601 12897.22601 1.15439 1.15439 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.53000 5.47470E-003 207.33814 11.15994 8.95286E-002 0.00000
12 PERIMETER_TOP_ZN_1 Heating 12741.72275 12741.72275 0.66965 0.66965 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
13 PERIMETER_TOP_ZN_4 Cooling 12526.78600 12526.78600 1.12123 1.12123 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.82800 5.47208E-003 131.25358 7.06470 5.66753E-002 0.00000
14 PERIMETER_TOP_ZN_4 Heating 8334.72425 8334.72425 0.43806 0.43806 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.25358 7.06470 5.66753E-002 0.00000
15 PERIMETER_BOT_ZN_3 Cooling 7215.87122 7215.87122 0.64588 0.64588 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.90000 5.47527E-003 207.33814 11.15994 8.95286E-002 0.00000
16 PERIMETER_BOT_ZN_3 Heating 9576.08565 9576.08565 0.50300 0.50300 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
17 PERIMETER_BOT_ZN_2 Cooling 8785.17156 8785.17156 0.78634 0.78634 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 27.01800 5.46476E-003 131.26219 7.06516 5.66790E-002 0.00000
18 PERIMETER_BOT_ZN_2 Heating 6366.45056 6366.45056 0.33445 0.33445 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.26219 7.06516 5.66790E-002 0.00000
19 PERIMETER_BOT_ZN_1 Cooling 10139.89460 10139.89460 0.90760 0.90760 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 33.65333 5.47489E-003 207.33814 11.15994 8.95286E-002 0.00000
20 PERIMETER_BOT_ZN_1 Heating 9660.74626 9660.74626 0.50746 0.50746 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
21 PERIMETER_BOT_ZN_4 Cooling 9699.55031 9699.55031 0.86818 0.86818 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.08800 5.47095E-003 131.25358 7.06470 5.66753E-002 0.00000
22 PERIMETER_BOT_ZN_4 Heating 6366.38768 6366.38768 0.33445 0.33445 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.25358 7.06470 5.66753E-002 0.00000
23 PERIMETER_MID_ZN_3 Cooling 8125.31912 8125.31912 0.72728 0.72728 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.90000 5.47527E-003 207.33814 11.15994 8.95286E-002 0.00000
24 PERIMETER_MID_ZN_3 Heating 9841.91229 9841.91229 0.51696 0.51696 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
25 PERIMETER_MID_ZN_2 Cooling 10680.42241 10680.42241 0.95597 0.95597 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 25.29133 5.46218E-003 131.26219 7.06516 5.66790E-002 0.00000
26 PERIMETER_MID_ZN_2 Heating 6531.44186 6531.44186 0.34311 0.34311 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.26219 7.06516 5.66790E-002 0.00000
27 PERIMETER_MID_ZN_1 Cooling 11602.90476 11602.90476 1.03855 1.03855 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 33.40667 5.47451E-003 207.33814 11.15994 8.95286E-002 0.00000
28 PERIMETER_MID_ZN_1 Heating 9914.10936 9914.10936 0.52076 0.52076 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 207.33814 11.15994 8.95286E-002 0.00000
29 PERIMETER_MID_ZN_4 Cooling 11513.84791 11513.84791 1.03057 1.03057 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.82800 5.47208E-003 131.25358 7.06470 5.66753E-002 0.00000
30 PERIMETER_MID_ZN_4 Heating 6531.37571 6531.37571 0.34311 0.34311 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -17.90000 9.55238E-004 131.25358 7.06470 5.66753E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PACU_VAV_BOT Cooling Sensible 70551.72 5.57121 5.57121 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 PACU_VAV_BOT Heating Sensible 28783.02 2.10404 2.10404 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00
3 PACU_VAV_MID Cooling Sensible 66963.38 5.25431 5.25431 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 PACU_VAV_MID Heating Sensible 28505.31 2.56502 2.56502 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00
5 PACU_VAV_TOP Cooling Sensible 76596.34 6.14078 6.14078 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 PACU_VAV_TOP Heating Sensible 28814.78 3.70713 3.70713 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 03:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.11067
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24093
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20500
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63769
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64248
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.58137E-003
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13306E-004
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63769
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12951.55587
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13306E-004
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 306.56454
15 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.49941
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.29985
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25500
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63735
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.79961
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.27063E-003
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.00918E-004
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84107
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22966.19891
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.00918E-004
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 606.62145
29 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.67161
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28053
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23800
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.63584
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74807
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.35817E-003
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.56579E-004
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.49613
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 40759.18160
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.56579E-004
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1075.46074
43 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84280
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18746
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15900
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13400
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.49990
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.03242E-003
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58284E-004
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.66521
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18092.85348
55 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58284E-004
56 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 477.03622
57 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96754
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10338
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.80000E-002
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.51432E-002
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.68551E-003
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04231E-004
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43807
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11914.27785
69 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04231E-004
70 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 314.12414
71 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.15439
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13686
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11600
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13391
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36496
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.78384E-003
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.59338E-004
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.66965
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18213.34961
83 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.59338E-004
84 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 480.21122
85 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12123
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.92014E-002
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 7.60000E-002
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.52134E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.27123E-003
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.04229E-004
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43806
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11914.06997
97 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.04229E-004
98 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 314.11865
99 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.64588
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24461
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20800
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13434
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65230
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55756E-003
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.19734E-004
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.50300
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
110 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13686.32798
111 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.19734E-004
112 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 360.91981
113 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.78634
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12720
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10800
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.49247E-002
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33920
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.99530E-003
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.96055E-005
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33445
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
124 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9099.39738
125 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.96055E-005
126 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.94924
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.90760
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17408
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.14800
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13433
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46420
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.18870E-003
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20793E-004
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.50746
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
138 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13807.43271
139 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20793E-004
140 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 364.11081
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.86818
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11520
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.80000E-002
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.50819E-002
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30720
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30727E-003
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.96047E-005
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.33445
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
152 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9099.30788
153 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.96047E-005
154 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 239.94687
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.72728
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21724
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18500
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13455
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57930
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.75385E-003
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.23055E-004
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.51696
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
166 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14065.88934
167 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.23055E-004
168 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 370.92482
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.95597
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.64145E-003
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.16662E-005
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34311
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
177 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9334.94874
178 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.16662E-005
179 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.15820
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.03855
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15213
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12900
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13397
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40567
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.50448E-003
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.23958E-004
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52076
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
191 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14169.16290
192 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.23958E-004
193 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 373.64598
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.03057
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.70486E-002
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.20000E-002
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 8.45066E-002
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.92587E-003
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.16654E-005
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.34311
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
205 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9334.85457
206 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.16654E-005
207 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.15571
208 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.15934
209 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07636
210 AirLoopHVAC PACU_VAV_BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 6.31868
211 AirLoopHVAC PACU_VAV_BOT Adjusted Heating Design Air Flow Rate [m3/s] 2.10404
212 AirLoopHVAC PACU_VAV_BOT Adjusted Cooling Design Air Flow Rate [m3/s] 5.57121
213 AirLoopHVAC PACU_VAV_BOT Adjusted Main Design Air Flow Rate [m3/s] 5.57121
214 AirLoopHVAC PACU_VAV_BOT User Heating Air Flow Ratio [] 0.30000
215 AirLoopHVAC PACU_VAV_BOT Calculated Heating Air Flow Ratio [] 0.37766
216 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.12589
217 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07546
218 AirLoopHVAC PACU_VAV_MID Sum of Air Terminal Maximum Flow Rates [m3/s] 6.25178
219 AirLoopHVAC PACU_VAV_MID Adjusted Heating Design Air Flow Rate [m3/s] 2.56502
220 AirLoopHVAC PACU_VAV_MID Adjusted Cooling Design Air Flow Rate [m3/s] 5.25431
221 AirLoopHVAC PACU_VAV_MID Adjusted Main Design Air Flow Rate [m3/s] 5.25431
222 AirLoopHVAC PACU_VAV_MID User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC PACU_VAV_MID Calculated Heating Air Flow Ratio [] 0.48817
224 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 3.37878
225 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.07411
226 AirLoopHVAC PACU_VAV_TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 6.75757
227 AirLoopHVAC PACU_VAV_TOP Adjusted Heating Design Air Flow Rate [m3/s] 3.70713
228 AirLoopHVAC PACU_VAV_TOP Adjusted Cooling Design Air Flow Rate [m3/s] 6.14078
229 AirLoopHVAC PACU_VAV_TOP Adjusted Main Design Air Flow Rate [m3/s] 6.14078
230 AirLoopHVAC PACU_VAV_TOP User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC PACU_VAV_TOP Calculated Heating Air Flow Ratio [] 0.60369
232 AirLoopHVAC PACU_VAV_BOT Design Supply Air Flow Rate [m3/s] 5.57121
233 AirLoopHVAC PACU_VAV_MID Design Supply Air Flow Rate [m3/s] 5.25431
234 AirLoopHVAC PACU_VAV_TOP Design Supply Air Flow Rate [m3/s] 6.14078
235 Controller:OutdoorAir PACU_VAV_BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.57121
236 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.57121
237 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 92223.28153
238 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80066
239 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.85688
240 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 30738.01973
241 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80066
242 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Rated Capacity [W] 24587.88159
243 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.15106E-004
244 Coil:Heating:Water PACU_VAV_BOT HEATING COIL Design Size U-Factor Times Area Value [W/K] 407.19766
245 Fan:VariableVolume PACU_VAV_BOT FAN Design Size Maximum Flow Rate [m3/s] 5.57121
246 Controller:WaterCoil PACU_VAV_BOT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.15106E-004
247 Controller:OutdoorAir PACU_VAV_MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.25431
248 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 5.25431
249 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 86977.53889
250 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80066
251 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 1.75126
252 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 28989.61371
253 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80066
254 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Rated Capacity [W] 25321.72363
255 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.21525E-004
256 Coil:Heating:Water PACU_VAV_MID HEATING COIL Design Size U-Factor Times Area Value [W/K] 416.03905
257 Fan:VariableVolume PACU_VAV_MID FAN Design Size Maximum Flow Rate [m3/s] 5.25431
258 Controller:WaterCoil PACU_VAV_MID_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.21525E-004
259 Controller:OutdoorAir PACU_VAV_TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 6.14078
260 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Air Flow Rate [m3/s] 6.14078
261 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Gross Rated Total Cooling Capacity [W] 101651.64753
262 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size High Speed Rated Sensible Heat Ratio 0.80066
263 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Rated Air Flow Rate [m3/s] 2.04672
264 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Total Cooling Capacity [W] 33880.49412
265 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL Design Size Low Speed Gross Rated Sensible Heat Ratio 0.80066
266 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Rated Capacity [W] 24311.52743
267 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.12688E-004
268 Coil:Heating:Water PACU_VAV_TOP HEATING COIL Design Size U-Factor Times Area Value [W/K] 406.31917
269 Fan:VariableVolume PACU_VAV_TOP FAN Design Size Maximum Flow Rate [m3/s] 6.14078
270 Controller:WaterCoil PACU_VAV_TOP_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.12688E-004
271 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.65629E-003
272 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.31875
273 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.65629E-003
274 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 792.03668
275 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
276 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 303629.94143
277 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 303629.94000
278 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.65629E-003
279 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 5.36267E-005
280 PlantLoop SWHSYS1 Plant Loop Volume [m3] 6.43520E-003
281 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 5.36267E-005
282 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 6.85023
283 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 5.36267E-005


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 12275.59
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 21774.66
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 38636.83
4 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17148.33
5 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11292.25
6 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17262.53
7 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11292.06
8 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 12972.29
9 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 8624.61
10 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 13087.06
11 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8624.52
12 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 13332.02
13 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 8847.85
14 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 13429.89
15 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 8847.76
16 Coil:Heating:Water PACU_VAV_BOT HEATING COIL 19177.61
17 Coil:Heating:Water PACU_VAV_MID HEATING COIL 19433.43
18 Coil:Heating:Water PACU_VAV_TOP HEATING COIL 19314.26


VAV DX Cooling Coil Standard Rating Information

DX Coil Type DX Coil Name Fan Type Fan Name Standard Net Cooling Capacity {W} Standard Net Cooling Capacity {Btu/h} IEER {Btu/W-h} COP 100% Capacity {W/W} COP 75% Capacity {W/W} COP 50% Capacity {W/W} COP 25% Capacity {W/W} EER 100% Capacity {Btu/W-h} EER 75% Capacity {Btu/W-h} EER 50% Capacity {Btu/W-h} EER 25% Capacity {Btu/W-h} Supply Air Flow 100% {kg/s} Supply Air Flow 75% {kg/s} Supply Air Flow 50% {kg/s} Supply Air Flow 25% {kg/s}
1 Coil:Cooling:DX:TwoSpeed PACU_VAV_BOT COOLING COIL N/A N/A 90636.35 309264.06 12.05 3.01 3.45 3.64 3.80 10.26 11.78 12.42 12.98 5.2305 4.1352 2.7721 1.1740
2 Coil:Cooling:DX:TwoSpeed PACU_VAV_MID COOLING COIL N/A N/A 85480.87 291672.84 12.05 3.01 3.45 3.64 3.80 10.26 11.78 12.42 12.98 4.9329 3.9000 2.6144 1.1072
3 Coil:Cooling:DX:TwoSpeed PACU_VAV_TOP COOLING COIL N/A N/A 99902.48 340881.40 12.05 3.01 3.45 3.64 3.80 10.26 11.78 12.42 12.98 5.7652 4.5580 3.0555 1.2940


Zone Surfaces

Zone Name # Surfaces
1 CORE_BOTTOM 7
2 TOPFLOOR_PLENUM 10
3 MIDFLOOR_PLENUM 14
4 FIRSTFLOOR_PLENUM 14
5 CORE_MID 7
6 CORE_TOP 7
7 PERIMETER_TOP_ZN_3 8
8 PERIMETER_TOP_ZN_2 8
9 PERIMETER_TOP_ZN_1 8
10 PERIMETER_TOP_ZN_4 8
11 PERIMETER_BOT_ZN_3 12
12 PERIMETER_BOT_ZN_2 10
13 PERIMETER_BOT_ZN_1 12
14 PERIMETER_BOT_ZN_4 10
15 PERIMETER_MID_ZN_3 8
16 PERIMETER_MID_ZN_2 8
17 PERIMETER_MID_ZN_1 8
18 PERIMETER_MID_ZN_4 8


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction CORE_BOT_ZN_5_FLOOR_FFACTOR 5.650E-003 5.642E-003   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
8 PERIMETER_TOP_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
9 PERIMETER_TOP_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
10 PERIMETER_TOP_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
11 PERIMETER_TOP_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 225.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
13 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 135.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
14 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 45.00 180.00 6.47 40.76 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
15 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 315.00 180.00 6.47 24.13 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
16 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 180.00 180.00 40.76 24.13 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   1660.73 1660.73 1660.73 0.00 0.00 49.91 33.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
18 PERIMETER_MID_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
19 PERIMETER_MID_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
20 PERIMETER_MID_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
21 PERIMETER_MID_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
22 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
23 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
25 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
26 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
27 iz-PERIMETER_TOP_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
28 iz-PERIMETER_TOP_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
29 iz-PERIMETER_TOP_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 iz-PERIMETER_TOP_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
31 iz-CORE_TOP_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 PERIMETER_BOT_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   60.85 60.85 60.85 0.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
33 PERIMETER_BOT_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   40.57 40.57 40.57 90.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   60.85 60.85 60.85 180.00 90.00 49.91 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   40.57 40.57 40.57 270.00 90.00 33.27 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
37 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
38 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
39 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
40 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
41 iz-PERIMETER_MID_ZN_1_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
42 iz-PERIMETER_MID_ZN_2_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
43 iz-PERIMETER_MID_ZN_3_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
44 iz-PERIMETER_MID_ZN_4_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 iz-CORE_MID_ZN_5_FLOOR Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
46 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
47 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
48 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
49 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
51 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 180.00 0.00 40.76 24.13 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
52 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
53 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
54 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
55 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
56 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 iz-CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
57 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   983.54 983.54 983.54 0.00 180.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
58 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   983.54 983.54 983.54 0.00 0.00 40.76 24.13 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
59 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   1967.08 1967.08 1967.08 0.00 90.00 1967.08 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
60 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
61 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
62 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
63 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
64 iz-CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
65 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
66 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 225.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
67 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
68 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
71 iz-PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 iz-CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
74 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 315.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
75 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
76 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
77 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
78 PERIMETER_TOP_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 iz-CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
82 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 45.00 0.00 6.47 49.91 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
83 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
84 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.032 0.894   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
87 iz-PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 iz-CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
89 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
90 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 135.00 0.00 6.47 33.27 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
91 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
92 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   67.75 136.92 67.75 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
93 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 21.75 21.75 21.75 0.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
99 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 iz-CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   45.82 91.28 45.82 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 41.85 41.85 41.85 90.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 1.65 1.65 1.65 90.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
107 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
108 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 iz-PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
110 iz-CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 0.237 0.224   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
112 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
113 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
114 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   67.75 136.92 67.75 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
115 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
116 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
117 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 21.75 21.75 21.75 180.00 90.00 15.82 1.37 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
118 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
119 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
121 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 iz-CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
123 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 0.224 0.213   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
124 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
125 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
126 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.802 0.716   45.82 91.28 45.82 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
127 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 41.85 41.85 41.85 270.00 90.00 30.84 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 1.65 1.65 1.65 270.00 90.00 1.22 1.36 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.065 3.065   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 iz-PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 iz-CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
133 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 0.237 0.224   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   71.65 136.92 71.65 0.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_NORTH_0.378 N/A 2.062 No 65.26 65.26 65.26 0.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 iz-PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 iz-CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 180.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 0.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 180.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.68 414.68 414.68 0.00 90.00 414.68 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   47.77 91.28 47.77 90.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_EAST_0.378 N/A 2.062 No 43.51 43.51 43.51 90.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 iz-PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 iz-CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 270.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.26 131.26 131.26 90.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
150 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.26 131.26 131.26 270.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
151 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
152 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   71.65 136.92 71.65 180.00 90.00 49.91 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
153 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_SOUTH_0.378 N/A 2.062 No 65.26 65.26 65.26 180.00 90.00 49.91 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 iz-CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.82 111.82 111.82 0.00 90.00 40.76 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
157 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   207.34 207.34 207.34 180.00 180.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   207.34 207.34 207.34 0.00 0.00 40.76 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
159 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   414.67 414.67 414.67 0.00 90.00 414.67 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
160 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.789 0.705   47.77 91.28 47.77 270.00 90.00 33.27 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
161 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.363_SHGC_WEST_0.378 N/A 2.062 No 43.51 43.51 43.51 270.00 90.00 33.27 1.31 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 135.00 90.00 6.47 2.74 0.00 iz-PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
163 iz-PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.74 17.74 17.74 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
164 iz-CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   66.19 66.19 66.19 90.00 90.00 24.13 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
165 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   131.25 131.25 131.25 270.00 180.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   131.25 131.25 131.25 90.00 0.00 24.13 6.47 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
167 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   262.51 262.51 262.51 0.00 90.00 262.51 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_BOTTOM RunPeriod: RUNPERIOD 1 5.4077172154E-002 0.1062042187 Pass Pass 9.0263471112E-002 0.2837319765 Pass Pass
2 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1118151182 8.8523523951E-002 Pass Pass 7.1027669696E-002 0.2456217911 Pass Pass
3 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.6188744401E-002 5.1816524374E-002 Pass Pass 9.9905184740E-002 0.3474989301 Pass Pass
4 FIRSTFLOOR_PLENUM RunPeriod: RUNPERIOD 1 2.8926282713E-002 3.2772775615E-002 Pass Pass 0.1178638584 0.3642309411 Pass Pass
5 CORE_MID RunPeriod: RUNPERIOD 1 3.8591747163E-002 6.7103902798E-002 Pass Pass 7.6577977824E-002 0.2644968232 Pass Pass
6 CORE_TOP RunPeriod: RUNPERIOD 1 5.1628350661E-002 3.6665363027E-002 Pass Pass 7.6319564601E-002 0.2733203657 Pass Pass
7 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 6.8534530425E-002 0.1025430944 Pass Pass 0.7240698139 7.7243701716 Pass Pass
8 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1033403382 0.1298031804 Pass Pass 0.2325404496 1.9005769515 Pass Pass
9 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1748013321 0.1589288069 Pass Pass 0.1082703723 0.4721395946 Pass Pass
10 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1189501750 0.1139947270 Pass Pass 0.7010078697 7.4242591007 Pass Pass
11 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 3.4112971056E-002 3.7323928477E-002 Pass Pass 9.2114001199E-002 0.2866974866 Pass Pass
12 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 8.6189920306E-002 0.1181596683 Pass Pass 9.2082653567E-002 0.2885079605 Pass Pass
13 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1483262152 0.1807800589 Pass Pass 9.9632987917E-002 0.3060937510 Pass Pass
14 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 7.5102857893E-002 0.1012094842 Pass Pass 8.7694321838E-002 0.2739701859 Pass Pass
15 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 3.4922457930E-002 3.8653557946E-002 Pass Pass 7.6643465193E-002 0.2650044565 Pass Pass
16 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1020886157 0.1379176180 Pass Pass 7.8219778888E-002 0.2693874430 Pass Pass
17 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1904417195 0.2245780915 Pass Pass 0.1002540293 0.3604059655 Pass Pass
18 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 9.1010040825E-002 0.1113266884 Pass Pass 7.3536211888E-002 0.2514382906 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4148.04 75.20 0.00 1967.66 965.01 7155.91



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB -17.90 0.00 -17.90 Wetbulb [C] 2.50 180.00
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 33.90 14.80 15.00 Wetbulb [C] 3.60 30.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 11.00 10      
Feb 15.00 16      
Mar 88.00 32      
Apr 159.00 54      
May 30.00 24      
Jun 11.00 4      
Jul 167.00 26      
Aug 33.00 24      
Sep 8.00 8      
Oct 13.00 10      
Nov 12.00 22      
Dec 11.00 18      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.894 1.032 60.85 60.85 0.00 90.00 N
PERIMETER_TOP_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.894 1.032 40.57 40.57 90.00 90.00 E
PERIMETER_TOP_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.894 1.032 60.85 60.85 180.00 90.00 S
PERIMETER_TOP_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.894 1.032 40.57 40.57 270.00 90.00 W
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 1660.73 1660.73 0.00 0.00  
PERIMETER_MID_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.705 0.789 60.85 60.85 0.00 90.00 N
PERIMETER_MID_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.705 0.789 40.57 40.57 90.00 90.00 E
PERIMETER_MID_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.705 0.789 60.85 60.85 180.00 90.00 S
PERIMETER_MID_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.705 0.789 40.57 40.57 270.00 90.00 W
PERIMETER_BOT_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.716 0.802 60.85 60.85 0.00 90.00 N
PERIMETER_BOT_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.716 0.802 40.57 40.57 90.00 90.00 E
PERIMETER_BOT_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.716 0.802 60.85 60.85 180.00 90.00 S
PERIMETER_BOT_PLENUM_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.716 0.802 40.57 40.57 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.894 1.032 136.92 71.65 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.894 1.032 91.28 47.77 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 0.894 1.032 136.92 71.65 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 0.894 1.032 91.28 47.77 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.716 0.802 136.92 67.75 0.00 90.00 N
PERIMETER_BOT_ZN_3_FLOOR PERIMETER_BOT_ZN_3_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 0.00 180.00  
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.716 0.802 91.28 45.82 90.00 90.00 E
PERIMETER_BOT_ZN_2_FLOOR PERIMETER_BOT_ZN_2_FLOOR_FFACTOR 1.00 0.228 0.237 131.26 131.26 90.00 180.00  
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.716 0.802 136.92 67.75 180.00 90.00 S
PERIMETER_BOT_ZN_1_FLOOR PERIMETER_BOT_ZN_1_FLOOR_FFACTOR 1.00 0.216 0.224 207.34 207.34 180.00 180.00  
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.716 0.802 91.28 45.82 270.00 90.00 W
PERIMETER_BOT_ZN_4_FLOOR PERIMETER_BOT_ZN_4_FLOOR_FFACTOR 1.00 0.228 0.237 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.705 0.789 136.92 71.65 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.705 0.789 91.28 47.77 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.705 0.789 136.92 71.65 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.705 0.789 91.28 47.77 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_BOT_ZN_5_FLOOR CORE_BOT_ZN_5_FLOOR_FFACTOR 1.00 0.006 0.006 983.54 983.54 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 135.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 315.00 180.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_TOP_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 90.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 270.00 180.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 180.00  
iz-PERIMETER_MID_ZN_1_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 0.00 0.00  
iz-PERIMETER_MID_ZN_2_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.26 131.26 270.00 0.00  
iz-PERIMETER_MID_ZN_3_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 207.34 207.34 180.00 0.00  
iz-PERIMETER_MID_ZN_4_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 131.25 131.25 90.00 0.00  
iz-CORE_MID_ZN_5_FLOOR INT_SLAB_CEILING 0.30 1.887 3.839 983.54 983.54 180.00 0.00  
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 180.00 0.00  
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 983.54 983.54 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 983.54 983.54 0.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 225.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 315.00 0.00  
PERIMETER_TOP_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 45.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 135.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 111.82 111.82 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 225.00 90.00 W
iz-CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 66.19 66.19 270.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.26 131.26 90.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 131.26 131.26 270.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 315.00 90.00 N
iz-CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 111.82 111.82 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 207.34 207.34 180.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 207.34 207.34 0.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.74 17.74 135.00 90.00 S
iz-PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.74 17.74 45.00 90.00 E
iz-CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 66.19 66.19 90.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 131.25 131.25 270.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 131.25 131.25 90.00 0.00  
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 1967.08   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.68   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 414.67   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 262.51   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   65.26 0.00 0.00 65.26 65.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   43.51 0.00 0.00 43.51 43.51 2.062 0.379 0.417             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   65.26 0.00 0.00 65.26 65.26 2.062 0.379 0.417             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   43.51 0.00 0.00 43.51 43.51 2.062 0.379 0.417             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.363_SHGC_NORTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.363_SHGC_NORTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.363_SHGC_NORTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.363_SHGC_EAST_0.378   41.85 0.00 0.00 41.85 41.85 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.363_SHGC_EAST_0.378   1.65 0.00 0.00 1.65 1.65 2.062 0.379 0.417             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.363_SHGC_SOUTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.363_SHGC_SOUTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.363_SHGC_SOUTH_0.378   21.75 0.00 0.00 21.75 21.75 2.062 0.379 0.417             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.363_SHGC_WEST_0.378   41.85 0.00 0.00 41.85 41.85 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.363_SHGC_WEST_0.378   1.65 0.00 0.00 1.65 1.65 2.062 0.379 0.417             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.363_SHGC_NORTH_0.378   65.26 0.00 0.00 65.26 65.26 2.062 0.379 0.417             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.363_SHGC_EAST_0.378   43.51 0.00 0.00 43.51 43.51 2.062 0.379 0.417             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.363_SHGC_SOUTH_0.378   65.26 0.00 0.00 65.26 65.26 2.062 0.379 0.417             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.363_SHGC_WEST_0.378   43.51 0.00 0.00 43.51 43.51 2.062 0.379 0.417             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             652.62 2.062 0.379 0.417                      
North Total or Average             195.79 2.062 0.379 0.417                      
Non-North Total or Average             456.84 2.062 0.379 0.417                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR SWINGING DOOR_CON 2.101 3.065 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.6636 983.54 6553.91 LightsWired LTG_SCH_OFFICE 47.17 168.00 45.19 0.0000 Y 55.60
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.95 0.0000 Y 6.73
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.91 0.0000 Y 4.25
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.60 0.0000 Y 6.64
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.60 0.0000 Y 4.20
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.91 0.0000 Y 6.72
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.87 0.0000 Y 4.25
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.56 0.0000 Y 6.63
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.57 0.0000 Y 4.20
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.95 0.0000 Y 6.73
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.6636 131.26 874.68 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.91 0.0000 Y 4.25
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.6636 207.34 1381.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.60 0.0000 Y 6.64
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.6636 131.25 874.62 LightsWired LTG_SCH_OFFICE 47.17 168.00 25.60 0.0000 Y 4.20
Interior Lighting Total       6.6636 4982.19 33199.39               232.25


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.38 874.68 335.44
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 874.68 122.02
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.38 1381.62 529.85
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 1381.62 192.74
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.38 874.62 335.42
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 874.62 122.01


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 563.81 AstronomicalClock -   42.26 42.26 4.47
EXTERIOR_LIGHTS_B 407.66 AstronomicalClock -   83.67 62.97 4.82
EXTERIOR_LIGHTS_C 4714.72 AstronomicalClock -   83.67 46.88 41.49
Exterior Lighting Total 5686.19           50.78



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 303629.94 0.80        


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed   92223.28 73839.06 18384.23 0.80 3.70    
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed   86977.54 69639.02 17338.51 0.80 3.70    
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed   101651.65 81387.93 20263.72 0.80 3.70    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PACU_VAV_BOT COOLING COIL   90636.3 3.01 10.26 N/A N/A 12.05
PACU_VAV_MID COOLING COIL   85480.9 3.01 10.26 N/A N/A 12.05
PACU_VAV_TOP COOLING COIL   99902.5 3.01 10.26 N/A N/A 12.05
ANSI/AHRI ratings include supply fan

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed                
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 12951.56 12275.59 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 22966.20 21774.66 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 40759.18 38636.83 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 18092.85 17148.33 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11914.28 11292.25 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 18213.35 17262.53 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11914.07 11292.06 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13686.33 12972.29 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9099.40 8624.61 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 13807.43 13087.06 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9099.31 8624.52 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 14065.89 13332.02 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9334.95 8847.85 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 14169.16 13429.89 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 9334.85 8847.76 -
PACU_VAV_BOT HEATING COIL Coil:Heating:Water 24587.88 19177.61 -
PACU_VAV_MID HEATING COIL Coil:Heating:Water 25321.72 19433.43 -
PACU_VAV_TOP HEATING COIL Coil:Heating:Water 24311.53 19314.26 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PACU_VAV_BOT FAN Fan:VariableVolume 0.60 1314.72 5.57 12116.76 2174.89 1.00 1.13 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00
PACU_VAV_MID FAN Fan:VariableVolume 0.60 1314.72 5.25 11427.54 2174.89 1.00 1.14 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
PACU_VAV_TOP FAN Fan:VariableVolume 0.60 1314.72 6.14 13355.50 2174.89 1.00 1.13 General DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002656 792.04 298174.34 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000054 6.85 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 1.00 27.19 0.85


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed None 90636.35 3.01 10.26 12.05 5.2305 3.45 11.78 4.1352 3.64 12.42 2.7721 3.80 12.98 1.1740
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed None 85480.87 3.01 10.26 12.05 4.9329 3.45 11.78 3.9000 3.64 12.42 2.6144 3.80 12.98 1.1072
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed None 99902.48 3.01 10.26 12.05 5.7652 3.45 11.78 4.5580 3.64 12.42 3.0555 3.80 12.98 1.2940
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {{W/1000cfm}} (773.3 {{W/(m3/s)}})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 35034.95 35034.95 35.62 3.111 3.111 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00885 22.95 0.00546 0.425 0.00
CORE_MID 28173.38 28173.38 28.64 2.499 2.499 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 22.95 0.00546 0.425 0.00
CORE_TOP 29846.88 29846.88 30.35 2.672 2.672 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00890 33.60 0.00547 0.425 0.00
PERIMETER_TOP_ZN_3 9415.93 9415.93 45.41 0.843 0.843 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 24.00 24.00 0.00872 33.75 0.00548 0.090 0.00
PERIMETER_TOP_ZN_2 10809.67 10809.67 82.35 0.968 0.968 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00862 26.18 0.00546 0.057 0.00
PERIMETER_TOP_ZN_1 12897.23 12897.23 62.20 1.154 1.154 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00866 33.53 0.00547 0.090 0.00
PERIMETER_TOP_ZN_4 12526.79 12526.79 95.44 1.121 1.121 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00861 31.83 0.00547 0.057 0.00
PERIMETER_BOT_ZN_3 7215.87 7215.87 34.80 0.646 0.646 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00882 33.90 0.00548 0.090 0.00
PERIMETER_BOT_ZN_2 8785.17 8785.17 66.93 0.786 0.786 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00866 27.02 0.00546 0.057 0.00
PERIMETER_BOT_ZN_1 10139.89 10139.89 48.91 0.908 0.908 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00873 33.65 0.00547 0.090 0.00
PERIMETER_BOT_ZN_4 9699.55 9699.55 73.90 0.868 0.868 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00865 31.09 0.00547 0.057 0.00
PERIMETER_MID_ZN_3 8125.32 8125.32 39.19 0.727 0.727 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00877 33.90 0.00548 0.090 0.00
PERIMETER_MID_ZN_2 10680.42 10680.42 81.37 0.956 0.956 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00863 25.29 0.00546 0.057 0.00
PERIMETER_MID_ZN_1 11602.90 11602.90 55.96 1.039 1.039 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 24.00 24.00 0.00869 33.41 0.00547 0.090 0.00
PERIMETER_MID_ZN_4 11513.85 11513.85 87.72 1.031 1.031 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00862 31.83 0.00547 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_BOTTOM 7739.75 7739.75 7.87 0.402 0.425 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -17.90 0.00096 0.425 0.00
CORE_MID 16092.16 16092.16 16.36 0.841 0.841 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -17.90 0.00096 0.425 0.00
CORE_TOP 28531.34 28531.34 29.01 1.496 1.496 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 -17.90 0.00096 0.425 0.00
PERIMETER_TOP_ZN_3 12657.48 12657.48 61.05 0.665 0.665 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -17.90 0.00096 0.090 0.00
PERIMETER_TOP_ZN_2 8334.87 8334.87 63.50 0.438 0.438 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.057 0.00
PERIMETER_TOP_ZN_1 12741.72 12741.72 61.45 0.670 0.670 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00790 -17.90 0.00096 0.090 0.00
PERIMETER_TOP_ZN_4 8334.72 8334.72 63.50 0.438 0.438 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.057 0.00
PERIMETER_BOT_ZN_3 9576.09 9576.09 46.19 0.503 0.503 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -17.90 0.00096 0.090 0.00
PERIMETER_BOT_ZN_2 6366.45 6366.45 48.50 0.334 0.334 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -17.90 0.00096 0.057 0.00
PERIMETER_BOT_ZN_1 9660.75 9660.75 46.59 0.507 0.507 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -17.90 0.00096 0.090 0.00
PERIMETER_BOT_ZN_4 6366.39 6366.39 48.50 0.334 0.334 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00792 -17.90 0.00096 0.057 0.00
PERIMETER_MID_ZN_3 9841.91 9841.91 47.47 0.517 0.517 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.090 0.00
PERIMETER_MID_ZN_2 6531.44 6531.44 49.76 0.343 0.343 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.057 0.00
PERIMETER_MID_ZN_1 9914.11 9914.11 47.82 0.521 0.521 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.090 0.00
PERIMETER_MID_ZN_4 6531.38 6531.38 49.76 0.343 0.343 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00789 -17.90 0.00096 0.057 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PACU_VAV_BOT 5.57 5.57 2.10 2.10 5.5712 2.1040 5.5712 0.3777 0.3000
PACU_VAV_MID 5.25 5.25 2.57 2.57 5.2543 2.5650 5.2543 0.4882 0.3000
PACU_VAV_TOP 6.14 6.14 3.71 3.71 6.1408 3.7071 6.1408 0.6037 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 12951.556 12951.556 0.637687 0.00011331 306.565 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 12951.56 12951.56 0.637687 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00800000 41.9796 7739.75 0.00 12993.84 12993.84
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 22966.199 22966.199 0.841069 0.00020092 606.621 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 22966.20 22966.20 0.841069 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00800000 41.9796 16092.16 0.00 23048.31 23048.31
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 40759.182 40759.182 1.496131 0.00035658 1075.461 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 40759.18 40759.18 1.496131 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00800000 41.9796 28531.34 0.00 40896.75 40896.75
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 18092.853 18092.853 0.665214 0.00015828 477.036 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 18092.85 18092.85 0.665214 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00789565 41.4403 12657.48 0.00 18151.35 18151.35
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 11914.278 11914.278 0.438072 0.00010423 314.124 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 11914.28 11914.28 0.438072 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00789441 41.4340 8334.87 0.00 11952.74 11952.74
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 18213.350 18213.350 0.669650 0.00015934 480.211 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 18213.35 18213.35 0.669650 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00789634 41.4439 12741.72 0.00 18272.22 18272.22
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11914.070 11914.070 0.438064 0.00010423 314.119 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 11914.07 11914.07 0.438064 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00789441 41.4340 8334.72 0.00 11952.53 11952.53
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 13686.328 13686.328 0.502999 0.00011973 360.920 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13686.33 13686.33 0.502999 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00792255 41.5793 9576.09 0.00 13731.05 13731.05
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 9099.397 9099.397 0.334449 0.00007961 239.949 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9099.40 9099.40 0.334449 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00792370 41.5852 6366.45 0.00 9129.06 9129.06
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 13807.433 13807.433 0.507458 0.00012079 364.111 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13807.43 13807.43 0.507458 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00792354 41.5844 9660.75 0.00 13852.53 13852.53
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 9099.308 9099.308 0.334446 0.00007960 239.947 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9099.31 9099.31 0.334446 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00792370 41.5852 6366.39 0.00 9128.97 9128.97
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 14065.889 14065.889 0.516962 0.00012305 370.925 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14065.89 14065.89 0.516962 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00788601 41.3903 9841.91 0.00 14111.82 14111.82
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 9334.949 9334.949 0.343114 0.00008167 246.158 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9334.95 9334.95 0.343114 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00788635 41.3921 6531.44 0.00 9365.37 9365.37
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 14169.163 14169.163 0.520764 0.00012396 373.646 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14169.16 14169.16 0.520764 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00788699 41.3954 9914.11 0.00 14215.42 14215.42
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 9334.855 9334.855 0.343111 0.00008167 246.156 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9334.85 9334.85 0.343111 12.80 9.74 0.00800000 40.00 18.76 0.00800000 -17.90 0.00095524 -17.90 0.0000 21.00 0.00788635 41.3921 6531.38 0.00 9365.27 9365.27
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_BOT 92223.282 73839.055 5.571208 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 89794.61 89794.61 5.571208 25.70 14.60 0.00824002 10.62 9.10 0.00824002 33.90 0.00547527 15.07 17.1614 24.00 0.00881307 38.4927 62215.82 0.00 95094.58 67737.27
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_BOT 24587.882 24587.882 1.671363 0.00021511 407.198 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24587.88 24587.88 1.671363 -2.18 -2.20 0.00386830 12.80 9.74 0.00800000 -17.90 0.00095524 -17.90 57.2048 18.43 0.00776125 47.8022 12274.72 0.00 23201.53 23201.53
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_MID 86977.539 69639.024 5.254313 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 84687.01 84687.01 5.254313 25.80 14.62 0.00821436 10.62 9.07 0.00821436 33.90 0.00547527 15.07 18.1965 24.00 0.00882530 38.5452 58571.17 0.00 89685.52 63884.32
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_MID 25321.724 25321.724 1.576294 0.00022153 416.039 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 25321.72 25321.72 1.576294 -3.56 -3.56 0.00362148 12.80 9.74 0.00800000 -17.90 0.00095524 -17.90 60.6549 17.70 0.00775331 49.9954 13509.90 0.00 23508.32 23508.32
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoopHVAC PACU_VAV_TOP 101651.648 81387.926 6.140776 -999.0 -999.000 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 98974.68 98974.68 6.140776 25.55 14.57 0.00825980 10.62 9.12 0.00825980 33.90 0.00547527 15.07 15.5697 24.00 0.00877552 38.3307 68355.47 0.00 104816.49 74662.33
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoopHVAC PACU_VAV_TOP 24311.527 24311.527 1.842233 0.00021269 406.319 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 03:20:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 24311.53 24311.53 1.842233 -0.64 -0.90 0.00422743 12.80 9.74 0.00800000 -17.90 0.00095524 -17.90 51.8990 15.84 0.00781807 56.7313 12993.97 0.00 23370.03 23370.03



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 12951.556 12951.556 0.637687 0.00011331 306.565 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 4.1814 4.265573 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 12951.56 12951.56 1.0000 0.62329933 0.637687 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.11329430 60.00 32.22 27.78 0.000 12951.56 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 41.9796 7739.75 0.00 12993.84 12993.84 0.62329933 12.80 11.60 0.00800000 33059.8 33.24 19.10 0.00800000 53906.7
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 22966.199 22966.199 0.841069 0.00020092 606.621 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 7.4147 7.563878 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 22966.20 22966.20 1.0000 0.82209287 0.841069 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.20089783 60.00 32.22 27.78 0.000 22966.20 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 41.9796 16092.16 0.00 23048.31 23048.31 0.82209287 12.80 11.60 0.00800000 33059.8 40.29 21.27 0.00800000 61096.0
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 40759.182 40759.182 1.496131 0.00035658 1075.461 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 13.1591 13.423966 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 40759.18 40759.18 1.0000 1.46237467 1.496131 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.35654273 60.00 32.22 27.78 0.000 40759.18 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 41.9796 28531.34 0.00 40896.75 40896.75 1.46237467 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61025.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 18092.853 18092.853 0.665214 0.00015828 477.036 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 5.8413 5.958850 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 18092.85 18092.85 1.0000 0.65020506 0.665214 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.15826803 60.00 32.22 27.78 0.000 18092.85 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00789565 21.00 0.00789565 41.4403 12657.48 0.00 18151.35 18151.35 0.65020506 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60976.2
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 11914.278 11914.278 0.438072 0.00010423 314.124 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 3.8465 3.923947 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 11914.28 11914.28 1.0000 0.42818794 0.438072 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.10422067 60.00 32.22 27.78 0.000 11914.28 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00789441 21.00 0.00789441 41.4340 8334.87 0.00 11952.74 11952.74 0.42818794 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60974.5
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 18213.350 18213.350 0.669650 0.00015934 480.211 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 5.8802 5.998535 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 18213.35 18213.35 1.0000 0.65454132 0.669650 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.15932207 60.00 32.22 27.78 0.000 18213.35 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00789634 21.00 0.00789634 41.4439 12741.72 0.00 18272.22 18272.22 0.65454132 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60975.9
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11914.070 11914.070 0.438064 0.00010423 314.119 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 3.8465 3.923878 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 11914.07 11914.07 1.0000 0.42818049 0.438064 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.10421885 60.00 32.22 27.78 0.000 11914.07 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00789441 21.00 0.00789441 41.4340 8334.72 0.00 11952.53 11952.53 0.42818049 12.80 11.60 0.00800000 33059.8 40.18 21.23 0.00800000 60974.5
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 13686.328 13686.328 0.502999 0.00011973 360.920 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 4.4186 4.507569 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13686.33 13686.33 1.0000 0.49165028 0.502999 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.11972175 60.00 32.22 27.78 0.000 13686.33 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00792255 21.00 0.00792255 41.5793 9576.09 0.00 13731.05 13731.05 0.49165028 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60988.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 9099.397 9099.397 0.334449 0.00007961 239.949 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 2.9377 2.996871 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9099.40 9099.40 1.0000 0.32690325 0.334449 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.07959738 60.00 32.22 27.78 0.000 9099.40 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00792370 21.00 0.00792370 41.5852 6366.45 0.00 9129.06 9129.06 0.32690325 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 13807.433 13807.433 0.507458 0.00012079 364.111 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 4.4577 4.547454 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13807.43 13807.43 1.0000 0.49600852 0.507458 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.12078112 60.00 32.22 27.78 0.000 13807.43 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00792354 21.00 0.00792354 41.5844 9660.75 0.00 13852.53 13852.53 0.49600852 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.8
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 9099.308 9099.308 0.334446 0.00007960 239.947 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 2.9377 2.996841 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9099.31 9099.31 1.0000 0.32690007 0.334446 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.07959659 60.00 32.22 27.78 0.000 9099.31 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00792370 21.00 0.00792370 41.5852 6366.39 0.00 9128.97 9128.97 0.32690007 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.7
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 14065.889 14065.889 0.516962 0.00012305 370.925 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 4.5412 4.632577 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14065.89 14065.89 1.0000 0.50529809 0.516962 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.12304198 60.00 32.22 27.78 0.000 14065.89 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00788601 21.00 0.00788601 41.3903 9841.91 0.00 14111.82 14111.82 0.50529809 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.5
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 9334.949 9334.949 0.343114 0.00008167 246.158 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 3.0138 3.074449 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9334.95 9334.95 1.0000 0.33537301 0.343114 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.08165787 60.00 32.22 27.78 0.000 9334.95 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00788635 21.00 0.00788635 41.3921 6531.44 0.00 9365.37 9365.37 0.33537301 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.1
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 14169.163 14169.163 0.520764 0.00012396 373.646 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 4.5745 4.666589 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14169.16 14169.16 1.0000 0.50901465 0.520764 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.12394537 60.00 32.22 27.78 0.000 14169.16 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00788699 21.00 0.00788699 41.3954 9914.11 0.00 14215.42 14215.42 0.50901465 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60987.2
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 9334.855 9334.855 0.343111 0.00008167 246.156 1.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 3.0138 3.074418 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9334.85 9334.85 1.0000 0.33536965 0.343111 12.80 9.74 0.00800000 33059.8 40.00 18.76 0.00800000 60796.0 0.08165705 60.00 32.22 27.78 0.000 9334.85 -17.90 0.00095524 -17.90 0.00000000 0.0000 20.95 0.00788635 21.00 0.00788635 41.3921 6531.38 0.00 9365.27 9365.27 0.33536965 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60985.0
PACU_VAV_BOT COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 92223.282 73839.055 5.571208 -999.0 -999.000 -999.0000 1.10194 1.00000 1020.1578 1004.8586 0.9774 PACU_VAV_BOT FAN Fan:VariableVolume 5.571208 5.44550867   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 89794.61 89794.61 0.9737 5.44550867 5.571208 25.70 14.60 0.00824002 46824.5 10.62 9.10 0.00824002 31440.7 -999.0 -999.00 -999.00 -999.00 12116.756 77677.86 33.90 0.00547527 15.07 0.95610000 17.1614 24.00 0.00881307 24.00 0.00881307 38.4927 62215.82 0.00 95094.58 67737.27 5.23045224 26.67 19.44 0.01118466 55322.4 13.99 13.21 0.00913394 37141.4
PACU_VAV_BOT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_BOT CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24587.882 24587.882 1.671363 0.00021511 407.198 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PACU_VAV_BOT FAN Fan:VariableVolume 5.571208 5.44550867   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 7.9382 8.097977 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24587.88 24587.88 1.0000 1.63365260 1.671363 -2.18 -2.20 0.00386830 7470.1 12.80 9.74 0.00800000 33059.8 0.21508357 60.00 32.22 27.78 0.000 24587.88 -17.90 0.00095524 -17.90 0.95610000 57.2048 18.84 0.00776222 18.43 0.00776125 47.8022 12274.72 0.00 23201.53 23201.53 1.63365260 2.80 1.76 0.00386830 12508.1 16.83 8.93 0.00386830 26710.3
PACU_VAV_MID COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 86977.539 69639.024 5.254313 -999.0 -999.000 -999.0000 1.09463 1.00000 1020.1101 1004.8586 0.9774 PACU_VAV_MID FAN Fan:VariableVolume 5.254313 5.13576327   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 84687.01 84687.01 0.9737 5.13576327 5.254313 25.80 14.62 0.00821436 46867.0 10.62 9.07 0.00821436 31375.9 -999.0 -999.00 -999.00 -999.00 11427.544 73259.47 33.90 0.00547527 15.07 0.95610000 18.1965 24.00 0.00882530 24.00 0.00882530 38.5452 58571.17 0.00 89685.52 63884.32 4.93293945 26.67 19.44 0.01118466 55322.4 13.99 13.21 0.00913394 37141.4
PACU_VAV_MID HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_MID CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 25321.724 25321.724 1.576294 0.00022153 416.039 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PACU_VAV_MID FAN Fan:VariableVolume 5.254313 5.13576327   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 8.1751 8.339666 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 05:40:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 25321.72 25321.72 1.0000 1.54072898 1.576294 -3.56 -3.56 0.00362148 5460.5 12.80 9.74 0.00800000 33059.8 0.22150289 60.00 32.22 27.78 0.000 25321.72 -17.90 0.00095524 -17.90 0.95610000 60.6549 18.56 0.00773181 17.70 0.00775331 49.9954 13509.90 0.00 23508.32 23508.32 1.54072898 2.80 1.41 0.00362148 11889.5 17.88 9.13 0.00362148 27147.4
PACU_VAV_TOP COOLING COIL Coil:Cooling:DX:TwoSpeed AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes unknown No 101651.648 81387.926 6.140776 -999.0 -999.000 -999.0000 1.11266 1.00000 1020.1946 1004.8586 0.9774 PACU_VAV_TOP FAN Fan:VariableVolume 6.140776 6.00222546   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 98974.68 98974.68 0.9737 6.00222546 6.140776 25.55 14.57 0.00825980 46719.2 10.62 9.12 0.00825980 31490.7 -999.0 -999.00 -999.00 -999.00 13355.502 85619.18 33.90 0.00547527 15.07 0.95610000 15.5697 24.00 0.00877552 24.00 0.00877552 38.3307 68355.47 0.00 104816.49 74662.33 5.76518293 26.67 19.44 0.01118466 55322.4 13.99 13.21 0.00913394 37141.4
PACU_VAV_TOP HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC PACU_VAV_TOP CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24311.527 24311.527 1.842233 0.00021269 406.319 -999.0000 1.00000 1.00000 1019.7116 1004.8586 0.9774 PACU_VAV_TOP FAN Fan:VariableVolume 6.140776 6.00222546   4197.9300 999.8980 2.65601621 54.44 82.22 27.78 309740.61 7.8490 8.006960 DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 03:20:00 unknown unknown DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 24311.53 24311.53 1.0000 1.80066764 1.842233 -0.64 -0.90 0.00422743 9928.4 12.80 9.74 0.00800000 33059.8 0.21266615 60.00 32.22 27.78 0.000 24311.53 -17.90 0.00095524 -17.90 0.95610000 51.8990 17.99 0.00775799 15.84 0.00781807 56.7313 12993.97 0.00 23370.03 23370.03 1.80066764 2.80 2.26 0.00422743 13408.1 15.62 8.78 0.00422743 26386.6



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PACU_VAV_BOT_OA_CONTROLLER DifferentialDryBulb 0.00 5.57 -      
PACU_VAV_MID_OA_CONTROLLER DifferentialDryBulb 0.00 5.25 -      
PACU_VAV_TOP_OA_CONTROLLER DifferentialDryBulb 0.00 6.14 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 PACU_VAV_TOP_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 PACU_VAV_BOT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area PERIMETER_MID_ZN_2_OA_MULT 1.00 1.00  
PERIMETER_MID_ZN_1 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 PACU_VAV_MID_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_BOTTOM 1582.17 2485.17 23.00
CORE_MID 1380.50 3518.83 318.67
CORE_TOP 1886.00 3805.67 897.00
PERIMETER_TOP_ZN_3 3041.00 3991.50 1889.00
PERIMETER_TOP_ZN_2 3063.50 3525.33 1492.50
PERIMETER_TOP_ZN_1 3035.67 3062.50 1261.83
PERIMETER_TOP_ZN_4 3104.67 3619.67 1653.83
PERIMETER_BOT_ZN_3 2487.33 4040.17 1509.33
PERIMETER_BOT_ZN_2 2696.83 3377.67 1026.17
PERIMETER_BOT_ZN_1 2528.17 3032.67 866.00
PERIMETER_BOT_ZN_4 2570.33 3483.67 1061.00
PERIMETER_MID_ZN_3 2500.83 3834.00 1268.33
PERIMETER_MID_ZN_2 2372.17 2926.83 1011.50
PERIMETER_MID_ZN_1 2795.67 2762.00 857.17
PERIMETER_MID_ZN_4 2697.50 3393.00 1130.33
TOPFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00
Facility 4672.67 4436.00 2220.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_BOTTOM 0.00 1.33 0.00 0.00
CORE_MID 0.33 0.00 0.33 0.00
CORE_TOP 5.33 0.00 4.83 0.00
PERIMETER_TOP_ZN_3 69.83 15.17 41.33 12.00
PERIMETER_TOP_ZN_2 42.83 48.00 14.83 44.50
PERIMETER_TOP_ZN_1 33.83 59.83 16.33 56.67
PERIMETER_TOP_ZN_4 44.00 45.33 17.33 31.50
PERIMETER_BOT_ZN_3 11.67 0.33 10.67 0.33
PERIMETER_BOT_ZN_2 4.33 37.17 3.33 36.17
PERIMETER_BOT_ZN_1 261.33 75.00 260.50 72.83
PERIMETER_BOT_ZN_4 5.33 31.67 4.50 21.50
PERIMETER_MID_ZN_3 14.67 5.17 11.33 4.00
PERIMETER_MID_ZN_2 7.50 46.17 4.00 45.00
PERIMETER_MID_ZN_1 6.00 76.17 4.50 75.00
PERIMETER_MID_ZN_4 9.67 40.67 6.67 29.33
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 317.50 240.83 280.83 215.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.74 52.94 2698.04 0.996 0.000 0.000 0.000
CORE_MID 21.74 52.94 2698.04 0.693 0.000 0.000 0.000
CORE_TOP 21.74 52.94 2698.04 0.673 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.58 11.16 568.77 0.771 0.038 0.000 0.000
PERIMETER_TOP_ZN_2 2.90 7.07 360.08 1.330 0.040 0.000 0.000
PERIMETER_TOP_ZN_1 4.58 11.16 568.77 1.434 0.038 0.000 0.000
PERIMETER_TOP_ZN_4 2.90 7.06 360.05 1.172 0.040 0.000 0.000
PERIMETER_BOT_ZN_3 4.58 11.16 568.77 0.620 0.020 0.000 0.000
PERIMETER_BOT_ZN_2 2.90 7.07 360.08 1.114 0.021 0.000 0.000
PERIMETER_BOT_ZN_1 4.58 11.16 568.77 1.077 0.833 0.000 0.000
PERIMETER_BOT_ZN_4 2.90 7.06 360.05 0.937 0.021 0.000 0.000
PERIMETER_MID_ZN_3 4.58 11.16 568.77 0.757 0.031 0.000 0.000
PERIMETER_MID_ZN_2 2.54 7.07 360.08 1.246 0.035 0.000 0.000
PERIMETER_MID_ZN_1 4.58 11.16 568.77 1.418 0.031 0.000 0.000
PERIMETER_MID_ZN_4 2.90 7.06 360.05 1.138 0.033 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_BOTTOM 21.74 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_MID 21.74 52.94 2698.04 0.000 0.000 0.000 0.000
CORE_TOP 21.74 52.94 2698.04 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 2.90 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 2.90 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 2.90 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 2.90 7.06 360.05 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 2.54 7.07 360.08 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 4.58 11.16 568.77 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 2.90 7.06 360.05 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_BOTTOM PACU_VAV_BOT 21.74 52.94 2698.04 983.54 0.0000 0.425
CORE_MID PACU_VAV_MID 21.74 52.94 2698.04 983.54 0.0000 0.425
CORE_TOP PACU_VAV_TOP 21.74 52.94 2698.04 983.54 0.0000 0.425
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 2.90 7.07 360.08 131.26 0.0000 0.057
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 2.90 7.06 360.05 131.25 0.0000 0.057
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 2.90 7.07 360.08 131.26 0.0000 0.057
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 2.90 7.06 360.05 131.25 0.0000 0.057
PERIMETER_MID_ZN_3 PACU_VAV_MID 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_2 PACU_VAV_MID 2.54 7.07 360.08 131.26 0.0000 0.057
PERIMETER_MID_ZN_1 PACU_VAV_MID 4.58 11.16 568.77 207.34 0.0000 0.090
PERIMETER_MID_ZN_4 PACU_VAV_MID 2.90 7.06 360.05 131.25 0.0000 0.057
Total Facility   109.75 268.17 13667.13 4982.19 0.0000 2.151


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_BOTTOM 15917243.04 0.00 15917243.04 0.00 15917243.04 13393058.27 4972.00 244.73 3543.27 80.69
CORE_MID 11087655.59 0.00 11087655.59 0.00 11087655.59 13393058.27 5546.19 614.64 2599.17 79.81
CORE_TOP 10821479.92 0.00 10821479.92 0.00 10821479.92 13393058.27 5637.30 751.12 2371.57 109.84
PERIMETER_TOP_ZN_3 2614002.17 0.00 2614002.17 260558.58 2874560.76 2823374.22 4758.26 723.19 3278.54 109.84
PERIMETER_TOP_ZN_2 2836621.49 0.00 2836621.49 173704.68 3010326.16 1787429.43 4547.35 543.36 3669.30 109.84
PERIMETER_TOP_ZN_1 4828422.26 0.00 4828422.26 260558.58 5088980.84 2823374.22 4312.72 779.36 3667.92 109.84
PERIMETER_TOP_ZN_4 2521882.64 0.00 2521882.64 173704.68 2695587.32 1787312.18 4547.12 496.87 3716.01 109.84
PERIMETER_BOT_ZN_3 2106243.00 0.00 2106243.00 138537.43 2244780.43 2823374.22 6396.18 265.54 2098.28 80.69
PERIMETER_BOT_ZN_2 2379391.99 0.00 2379391.99 92357.73 2471749.73 1787429.43 5505.87 278.79 2975.34 80.69
PERIMETER_BOT_ZN_1 3639518.37 0.00 3639518.37 2868995.21 6508513.58 2823374.22 5067.75 253.91 3438.34 80.69
PERIMETER_BOT_ZN_4 2013388.64 0.00 2013388.64 92357.73 2105746.37 1787312.18 5686.67 265.41 2807.92 80.69
PERIMETER_MID_ZN_3 2555840.85 0.00 2555840.85 216894.87 2772735.72 2823374.22 4925.95 536.23 3297.82 79.81
PERIMETER_MID_ZN_2 2662651.87 0.00 2662651.87 144595.71 2807247.57 1601953.02 4429.81 489.88 3840.31 988.81
PERIMETER_MID_ZN_1 4762672.14 0.00 4762672.14 216894.87 4979567.00 2823374.22 4304.11 775.05 3680.84 79.81
PERIMETER_MID_ZN_4 2435634.77 0.00 2435634.77 144595.71 2580230.48 1787312.18 4748.17 887.89 3123.94 79.81
Total Facility 73182648.74 0.00 73182648.74 4783755.77 77966404.52 67658168.57 6883.82 1326.31 4773.36 1094.22


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_BOTTOM 0.7362 0.0000 0.7362 0.0000 0.7362 0.4247 2224.39 244.73 3473.88
CORE_MID 0.5127 0.0000 0.5127 0.0000 0.5127 0.4247 2778.79 614.47 2549.73
CORE_TOP 0.4986 0.0000 0.4986 0.0000 0.4986 0.4247 2885.75 751.12 2306.12
PERIMETER_TOP_ZN_3 0.1206 0.0000 0.1206 0.0059 0.1265 0.0895 2006.74 723.19 3213.07
PERIMETER_TOP_ZN_2 0.1315 0.0000 0.1315 0.0039 0.1355 0.0567 1795.80 543.36 3603.85
PERIMETER_TOP_ZN_1 0.2241 0.0000 0.2241 0.0059 0.2299 0.0895 1561.17 779.36 3602.47
PERIMETER_TOP_ZN_4 0.1159 0.0000 0.1159 0.0039 0.1199 0.0567 1795.60 496.87 3650.53
PERIMETER_BOT_ZN_3 0.0968 0.0000 0.0968 0.0031 0.1000 0.0895 3648.37 265.54 2029.09
PERIMETER_BOT_ZN_2 0.1102 0.0000 0.1102 0.0021 0.1123 0.0567 2758.23 278.79 2905.98
PERIMETER_BOT_ZN_1 0.1684 0.0000 0.1684 0.1308 0.2992 0.0895 2319.95 253.91 3369.14
PERIMETER_BOT_ZN_4 0.0927 0.0000 0.0927 0.0021 0.0948 0.0567 2939.03 265.41 2738.56
PERIMETER_MID_ZN_3 0.1183 0.0000 0.1183 0.0049 0.1232 0.0895 2158.55 536.06 3248.39
PERIMETER_MID_ZN_2 0.1231 0.0000 0.1231 0.0035 0.1266 0.0567 1662.60 489.71 2881.69
PERIMETER_MID_ZN_1 0.2214 0.0000 0.2214 0.0049 0.2263 0.0895 1536.71 774.88 3631.41
PERIMETER_MID_ZN_4 0.1125 0.0000 0.1125 0.0033 0.1158 0.0567 1981.01 887.73 3074.27
Total Facility 3.3831 0.0000 3.3831 0.1742 3.5573 2.1513 4092.42 1326.15 4663.15


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PACU_VAV_BOT 24893124.85 0.00 24893124.85 22614548.33 4631.04 264.99 3863.97 80.69
PACU_VAV_MID 22455799.98 0.00 22455799.98 22429071.92 5178.27 83.05 3498.68 79.81
PACU_VAV_TOP 22568452.13 0.00 22568452.13 22614548.33 5173.47 117.95 3468.58 109.63


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PACU_VAV_BOT 1.1506 0.0000 1.1506 0.7171 1883.34 264.99 3794.67
PACU_VAV_MID 1.0400 0.0000 1.0400 0.7084 2410.70 82.96 3449.34
PACU_VAV_TOP 1.0421 0.0000 1.0421 0.7171 2421.94 117.62 3403.44


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PACU_VAV_BOT 0.00 922.84 2224.42 0.00 0.00 0.00 1750.89 0.00 0.00 0.00
PACU_VAV_MID 0.00 451.04 2275.98 0.00 0.00 0.00 2201.16 0.00 0.00 0.00
PACU_VAV_TOP 0.00 364.04 2331.30 0.00 0.00 0.00 2263.09 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PACU_VAV_BOT 0.0000 0.9049 2.1810 0.0000 0.0000 0.0000 0.7587 0.0000 0.0000 0.0000
PACU_VAV_MID 0.0000 0.8964 1.8992 0.0000 0.0000 0.0000 0.7296 0.0000 0.0000 0.0000
PACU_VAV_TOP 0.0000 0.8897 1.8944 0.0000 0.0000 0.0000 0.7339 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Surfaces by Class

Total Outdoors
Wall 72 24
Floor 30 4
Roof 26 1
Internal Mass 15 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 18 18
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 3
Conditioned Zones 18
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1005
Defaulted Fields 578
Fields with Defaults 2423
Autosized Fields 194
Autosizable Fields 250
Autocalculated Fields 156
Autocalculatable Fields 277



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
Electricity:Building 951.94 13383.13 14-MAY-17:20 66674.30 02-JAN-16:50
Electricity:Zone:CORE_BOTTOM 306.02 5243.28 01-JAN-00:10 18955.76 02-JAN-08:10
Electricity:SpaceType:GENERAL 951.94 13383.13 14-MAY-17:20 66674.30 02-JAN-16:50
InteriorLights:Electricity 232.25 905.38 14-MAY-17:20 25003.79 02-JAN-16:50
InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 232.25 905.38 14-MAY-17:20 25003.79 02-JAN-16:50
LightsWired:InteriorLights:Electricity 232.25 905.38 14-MAY-17:20 25003.79 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 232.25 905.38 14-MAY-17:20 25003.79 02-JAN-16:50
Electricity:Zone:CORE_MID 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:CORE_TOP 171.02 2043.28 01-JAN-00:10 11744.33 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 55.60 211.73 01-JAN-00:10 4936.01 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 31.06 413.68 09-APR-17:10 2475.80 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.73 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 6.73 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_2 19.66 261.88 14-MAY-17:10 1567.33 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_1 30.97 413.67 12-MAR-17:10 2475.79 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.64 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 6.64 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_TOP_ZN_4 19.61 261.87 12-MAR-17:10 1567.28 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_3 31.05 413.68 09-APR-17:10 2475.80 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.72 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 6.72 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_2 19.65 261.88 14-MAY-17:10 1567.33 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_1 30.96 413.67 12-MAR-17:10 2475.79 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.63 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 6.63 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_BOT_ZN_4 19.60 261.87 12-MAR-17:10 1567.28 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_3 31.06 413.68 09-APR-17:10 2475.80 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.73 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 6.73 27.57 01-JAN-09:00 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_2 19.66 261.88 14-MAY-17:10 1567.33 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 4.25 17.46 01-JAN-07:50 658.76 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_1 30.97 413.67 12-MAR-17:10 2475.79 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.64 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 6.64 27.57 01-JAN-07:50 1040.56 02-JAN-16:50
Electricity:Zone:PERIMETER_MID_ZN_4 19.61 261.87 12-MAR-17:10 1567.28 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 4.20 17.46 01-JAN-09:00 658.71 02-JAN-16:50
InteriorEquipment:Electricity 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 250.42 5031.54 01-JAN-00:10 14019.75 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 719.69 12477.75 01-JAN-00:10 41699.26 02-JAN-08:10
ElevatorLift:InteriorEquipment:Electricity 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL 134.36 3200.00 01-JAN-00:10 7125.18 02-JAN-07:10
ElevatorLightsFan:InteriorEquipment:Electricity 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL 0.64 0.00 01-JAN-00:10 86.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 584.69 9277.75 01-JAN-00:10 34487.83 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 115.43 1831.54 01-JAN-00:10 6808.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 24.33 386.10 01-JAN-00:10 1435.25 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 24.33 386.10 01-JAN-00:10 1435.24 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 15.40 244.42 01-JAN-00:10 908.57 02-JAN-08:10
Electricity:HVAC 310.93 367.92 01-JAN-00:10 113604.43 26-JUN-15:10
ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 03-JAN-13:10
Transformer:ExteriorEquipment:Electricity 26.89 367.92 01-JAN-00:10 1410.29 03-JAN-13:10
ElectricityPurchased:Facility 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
ElectricityPurchased:Plant 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
Cogeneration:ElectricityPurchased 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
General:Cogeneration:ElectricityPurchased 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
ElectricityNet:Plant 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
Cogeneration:ElectricityNet 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
General:Cogeneration:ElectricityNet 1371.28 13751.79 14-MAY-17:20 179202.45 26-JUN-15:10
Fans:Electricity 118.83 0.00 01-JAN-00:10 35471.95 24-JUL-15:20
General:Fans:Electricity 118.83 0.00 01-JAN-00:10 35471.95 24-JUL-15:20
ExteriorLights:Electricity 50.78 0.00 01-JAN-07:30 5686.19 01-JAN-06:10
General:ExteriorLights:Electricity 50.78 0.00 01-JAN-07:30 5686.19 01-JAN-06:10
Cooling:Electricity 165.22 0.00 01-JAN-00:10 78403.23 26-JUN-15:00
General:Cooling:Electricity 165.22 0.00 01-JAN-00:10 78403.23 26-JUN-15:00
Electricity:Plant 57.64 0.00 01-JAN-00:10 7363.87 06-FEB-12:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:Electricity 55.70 0.00 01-JAN-00:10 6796.72 14-FEB-12:30
Water Heater:WaterSystems:Electricity 55.70 0.00 01-JAN-00:10 6796.72 14-FEB-12:30
Pumps:Electricity 1.93 0.00 01-JAN-00:10 771.61 23-DEC-07:10
General:Pumps:Electricity 1.93 0.00 01-JAN-00:10 771.61 23-DEC-07:10
WIRED_LTG_ELECTRICITY 6.53 0.00 01-JAN-00:10 702.61 02-JAN-17:00
WIRED_INT_EQUIP1 680.83 12477.75 01-JAN-00:10 37555.83 02-JAN-13:10
WIRED_INT_EQUIP2 624.19 9277.75 01-JAN-00:10 39135.32 02-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 341.83 0.00 01-JAN-00:10 242080.55 23-DEC-07:20
NaturalGas:Plant 341.83 0.00 01-JAN-00:10 242080.55 23-DEC-07:20
Heating:NaturalGas 341.83 0.00 01-JAN-00:10 242080.55 23-DEC-07:20
Boiler:Heating:NaturalGas 341.83 0.00 01-JAN-00:10 242080.55 23-DEC-07:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Facility 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 271.06 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2340.13 0.00 01-JAN-00:10 493573.90 22-DEC-07:10
EnergyTransfer:Building 1124.54 0.00 01-JAN-00:10 174842.49 26-JUN-15:00
EnergyTransfer:Zone:CORE_BOTTOM 223.41 0.00 01-JAN-00:10 26283.32 05-SEP-07:30
Heating:EnergyTransfer 101.33 0.00 01-JAN-00:10 125795.88 06-FEB-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 101.33 0.00 01-JAN-00:10 125795.88 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 1023.21 0.00 01-JAN-00:10 174842.49 26-JUN-15:00
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 223.41 0.00 01-JAN-00:10 26283.32 05-SEP-07:30
General:Cooling:EnergyTransfer 1023.21 0.00 01-JAN-00:10 174842.49 26-JUN-15:00
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 223.41 0.00 01-JAN-00:10 26283.32 05-SEP-07:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 51.71 0.00 01-JAN-00:10 14412.81 22-DEC-06:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 17.76 0.00 01-JAN-00:10 14412.81 22-DEC-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 17.76 0.00 01-JAN-00:10 14412.81 22-DEC-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 33.96 0.00 01-JAN-00:10 12292.68 26-JUN-13:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 33.96 0.00 01-JAN-00:10 12292.68 26-JUN-13:40
EnergyTransfer:Zone:MIDFLOOR_PLENUM 25.62 0.00 01-JAN-00:10 7528.29 26-DEC-07:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 9.07 0.00 01-JAN-00:10 7528.29 26-DEC-07:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 9.07 0.00 01-JAN-00:10 7528.29 26-DEC-07:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.55 0.00 01-JAN-00:10 5766.46 17-JUL-10:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 16.55 0.00 01-JAN-00:10 5766.46 17-JUL-10:30
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 27.31 0.00 01-JAN-00:10 5958.65 17-JUL-12:20
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 5.33 0.00 01-JAN-00:10 3264.73 06-FEB-09:00
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 5.33 0.00 01-JAN-00:10 3264.73 06-FEB-09:00
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 21.98 0.00 01-JAN-00:10 5958.65 17-JUL-12:20
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM 21.98 0.00 01-JAN-00:10 5958.65 17-JUL-12:20
EnergyTransfer:Zone:CORE_MID 141.93 0.00 01-JAN-00:10 20020.95 17-JUL-07:20
Heating:EnergyTransfer:Zone:CORE_MID 0.39 0.00 01-JAN-00:10 11751.13 26-DEC-06:30
General:Heating:EnergyTransfer:Zone:CORE_MID 0.39 0.00 01-JAN-00:10 11751.13 26-DEC-06:30
Cooling:EnergyTransfer:Zone:CORE_MID 141.54 0.00 01-JAN-00:10 20020.95 17-JUL-07:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 141.54 0.00 01-JAN-00:10 20020.95 17-JUL-07:20
EnergyTransfer:Zone:CORE_TOP 134.35 0.00 01-JAN-00:10 21070.40 17-JUL-14:00
Heating:EnergyTransfer:Zone:CORE_TOP 4.85 0.00 01-JAN-00:10 21067.51 26-DEC-06:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 4.85 0.00 01-JAN-00:10 21067.51 26-DEC-06:20
Cooling:EnergyTransfer:Zone:CORE_TOP 129.50 0.00 01-JAN-00:10 21070.40 17-JUL-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 129.50 0.00 01-JAN-00:10 21070.40 17-JUL-14:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 41.35 0.00 01-JAN-00:10 8359.37 21-DEC-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 11.52 0.00 01-JAN-00:10 8359.37 21-DEC-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 11.52 0.00 01-JAN-00:10 8359.37 21-DEC-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 29.83 0.00 01-JAN-00:10 8008.71 17-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 29.83 0.00 01-JAN-00:10 8008.71 17-JUL-13:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 40.24 0.00 01-JAN-00:10 10122.21 17-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 6.09 0.00 01-JAN-00:10 6393.08 22-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 6.09 0.00 01-JAN-00:10 6393.08 22-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 34.15 0.00 01-JAN-00:10 10122.21 17-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 34.15 0.00 01-JAN-00:10 10122.21 17-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 69.23 0.00 01-JAN-00:10 13976.88 28-SEP-13:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 7.41 0.00 01-JAN-00:10 8935.49 22-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 7.41 0.00 01-JAN-00:10 8935.49 22-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 61.81 0.00 01-JAN-00:10 13976.88 28-SEP-13:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 61.81 0.00 01-JAN-00:10 13976.88 28-SEP-13:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 38.59 0.00 01-JAN-00:10 10954.95 16-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.66 0.00 01-JAN-00:10 6684.32 22-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.66 0.00 01-JAN-00:10 6684.32 22-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.93 0.00 01-JAN-00:10 10954.95 16-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.93 0.00 01-JAN-00:10 10954.95 16-AUG-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 30.80 0.00 01-JAN-00:10 6481.47 17-JUL-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.98 0.00 01-JAN-00:10 5748.87 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 4.98 0.00 01-JAN-00:10 5748.87 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 25.82 0.00 01-JAN-00:10 6481.47 17-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 25.82 0.00 01-JAN-00:10 6481.47 17-JUL-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 33.93 0.00 01-JAN-00:10 8155.62 17-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.13 0.00 01-JAN-00:10 4696.50 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 2.13 0.00 01-JAN-00:10 4696.50 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 31.80 0.00 01-JAN-00:10 8155.62 17-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 31.80 0.00 01-JAN-00:10 8155.62 17-JUL-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 60.51 0.00 01-JAN-00:10 11585.15 16-AUG-12:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.03 0.00 01-JAN-00:10 9717.63 21-DEC-08:00
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 11.03 0.00 01-JAN-00:10 9717.63 21-DEC-08:00
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 49.49 0.00 01-JAN-00:10 11585.15 16-AUG-12:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 49.49 0.00 01-JAN-00:10 11585.15 16-AUG-12:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 30.52 0.00 01-JAN-00:10 8527.64 26-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.21 0.00 01-JAN-00:10 4734.58 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 2.21 0.00 01-JAN-00:10 4734.58 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 28.31 0.00 01-JAN-00:10 8527.64 26-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 28.31 0.00 01-JAN-00:10 8527.64 26-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 35.84 0.00 01-JAN-00:10 7460.41 17-JUL-13:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.43 0.00 01-JAN-00:10 6399.27 23-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.43 0.00 01-JAN-00:10 6399.27 23-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 31.41 0.00 01-JAN-00:10 7460.41 17-JUL-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 31.41 0.00 01-JAN-00:10 7460.41 17-JUL-13:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 36.31 0.00 01-JAN-00:10 10002.45 17-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.36 0.00 01-JAN-00:10 5412.81 23-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 2.36 0.00 01-JAN-00:10 5412.81 23-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 33.95 0.00 01-JAN-00:10 10002.45 17-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 33.95 0.00 01-JAN-00:10 10002.45 17-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 67.57 0.00 01-JAN-00:10 12896.85 28-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.62 0.00 01-JAN-00:10 7237.88 23-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 2.62 0.00 01-JAN-00:10 7237.88 23-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 64.95 0.00 01-JAN-00:10 12896.85 28-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 64.95 0.00 01-JAN-00:10 12896.85 28-SEP-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 35.33 0.00 01-JAN-00:10 10327.71 16-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.49 0.00 01-JAN-00:10 5430.15 23-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 2.49 0.00 01-JAN-00:10 5430.15 23-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 32.84 0.00 01-JAN-00:10 10327.71 16-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 32.84 0.00 01-JAN-00:10 10327.71 16-AUG-16:00
PlantLoopHeatingDemand:Facility 289.10 0.00 01-JAN-00:10 193966.73 23-DEC-07:20
PlantLoopHeatingDemand:Plant 52.92 0.00 01-JAN-00:10 6664.15 13-FEB-12:10
WaterSystems:PlantLoopHeatingDemand 52.92 0.00 01-JAN-00:10 6664.15 13-FEB-12:10
General:WaterSystems:PlantLoopHeatingDemand 52.92 0.00 01-JAN-00:10 6664.15 13-FEB-12:10
EnergyTransfer:HVAC 928.41 0.00 01-JAN-00:10 240164.94 26-JUN-15:10
HeatingCoils:EnergyTransfer 236.18 0.00 01-JAN-00:10 192731.25 23-DEC-07:20
PlantLoopHeatingDemand:HVAC 236.18 0.00 01-JAN-00:10 192731.25 23-DEC-07:20
HeatingCoils:PlantLoopHeatingDemand 236.18 0.00 01-JAN-00:10 192731.25 23-DEC-07:20
CoolingCoils:EnergyTransfer 692.23 0.00 01-JAN-00:10 240164.94 26-JUN-15:10
EnergyTransfer:Plant 287.18 0.00 01-JAN-00:10 192918.31 23-DEC-07:20
WaterSystems:EnergyTransfer 52.92 0.00 01-JAN-00:10 6664.15 13-FEB-12:10
WaterUse:WaterSystems:EnergyTransfer 52.92 0.00 01-JAN-00:10 6664.15 13-FEB-12:10
Boilers:EnergyTransfer 234.27 0.00 01-JAN-00:10 191682.84 23-DEC-07:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_BOTTOM 0.000 0.000 0.000 -223.407 0.000 0.000 32.778 55.599 250.423 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -115.393
CORE_MID 0.000 0.000 0.390 -141.538 0.000 0.000 33.702 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -63.578
CORE_TOP 0.000 0.000 4.853 -129.495 0.000 0.000 34.431 55.599 115.425 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -80.813
PERIMETER_TOP_ZN_3 0.000 0.000 11.520 -29.827 0.000 0.000 7.474 6.731 24.333 20.593 0.000 0.070 0.003 0.000 -35.952 0.000 -3.338 -1.604
PERIMETER_TOP_ZN_2 0.000 0.000 6.085 -34.154 0.000 0.000 4.597 4.254 15.404 46.267 0.000 0.045 0.001 0.000 -23.246 0.000 -2.285 -16.967
PERIMETER_TOP_ZN_1 0.000 0.000 7.413 -61.812 0.000 0.000 7.183 6.638 24.332 95.910 0.000 0.068 0.003 0.000 -35.152 0.000 -3.513 -41.068
PERIMETER_TOP_ZN_4 0.000 0.000 6.660 -31.929 0.000 0.000 4.664 4.203 15.403 42.499 0.000 0.045 0.001 0.000 -23.878 0.000 -2.291 -15.377
PERIMETER_BOT_ZN_3 0.000 0.000 4.984 -25.816 0.000 0.000 7.462 6.719 24.333 20.934 0.000 0.040 0.310 0.000 -37.121 0.000 -1.845 -0.001
PERIMETER_BOT_ZN_2 0.000 0.000 2.132 -31.802 0.000 0.000 4.564 4.248 15.404 46.431 0.000 0.025 0.000 0.000 -24.543 0.000 -1.292 -15.166
PERIMETER_BOT_ZN_1 0.000 0.000 11.025 -49.486 0.000 0.000 7.288 6.630 24.332 96.544 0.000 2.293 0.001 0.000 -37.425 0.000 -31.438 -29.765
PERIMETER_BOT_ZN_4 0.000 0.000 2.213 -28.306 0.000 0.000 4.616 4.197 15.403 42.717 0.000 0.025 0.000 0.000 -25.235 0.000 -1.296 -14.336
PERIMETER_MID_ZN_3 0.000 0.000 4.432 -31.405 0.000 0.000 7.381 6.731 24.333 20.350 0.000 0.059 9.006 0.000 -37.956 0.000 -2.932 0.000
PERIMETER_MID_ZN_2 0.000 0.000 2.363 -33.947 0.000 0.000 3.358 4.254 15.404 45.993 0.000 0.037 0.000 0.000 -24.480 0.000 -2.005 -10.977
PERIMETER_MID_ZN_1 0.000 0.000 2.616 -64.952 0.000 0.000 7.105 6.638 24.332 95.638 0.000 0.057 0.002 0.000 -37.010 0.000 -3.079 -31.346
PERIMETER_MID_ZN_4 0.000 0.000 2.489 -32.839 0.000 0.000 4.606 4.203 15.403 42.345 0.000 0.038 0.000 0.000 -25.189 0.000 -2.010 -9.045
TOPFLOOR_PLENUM 17.756 -33.956 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.071 21.256 0.000 0.000 0.000 -5.127 -0.000
MIDFLOOR_PLENUM 9.070 -16.552 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.087 12.490 0.000 0.000 0.000 -5.094 -0.002
FIRSTFLOOR_PLENUM 5.328 -21.978 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.067 20.691 0.000 0.000 0.000 -4.108 -0.000
Total Facility 32.154 -72.486 69.176 -950.716 0.000 0.000 171.210 232.246 719.689 616.221 0.000 3.028 63.764 0.000 -367.186 0.000 -71.653 -445.439


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM 31-JUL-05:12 0.00 0.00 0.00 -38846.52 0.00 0.00 311.13 548.43 7410.35 0.00 0.00 0.00 30576.61 0.00 -0.00 0.00 0.00 0.00
CORE_MID 05-SEP-05:12 0.00 0.00 0.00 -31453.65 0.00 0.00 309.22 548.43 3025.92 0.00 0.00 0.00 27570.07 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUL-05:12 0.00 0.00 0.00 -32510.21 0.00 0.00 319.28 548.43 3025.92 0.00 0.00 0.00 28616.58 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 16-JUL-14:22 0.00 0.00 0.00 -11498.49 0.00 0.00 24.73 27.57 478.42 5883.63 0.00 179.59 4904.56 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 06-AUG-09:12 0.00 0.00 0.00 -14055.33 0.00 0.00 12.68 17.46 302.86 10604.68 0.00 0.00 3128.58 0.00 -0.00 0.00 -10.92 0.00
PERIMETER_TOP_ZN_1 12-MAR-12:41 0.00 0.00 0.00 -17864.27 0.00 0.00 22.02 27.57 478.41 17151.60 0.00 0.00 477.90 0.00 -0.00 0.00 -293.24 0.00
PERIMETER_TOP_ZN_4 11-JUN-16:21 0.00 0.00 0.00 -16679.01 0.00 0.00 10.28 17.46 302.86 12036.85 0.00 1.24 4310.34 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-18:21 0.00 0.00 0.00 -8755.42 0.00 0.00 0.00 27.57 386.10 3589.25 0.00 47.03 4705.46 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 11-JUN-08:51 0.00 0.00 0.00 -11420.92 0.00 0.00 16.07 17.46 302.86 10089.06 0.00 0.00 1027.78 0.00 -0.00 0.00 -32.30 0.00
PERIMETER_BOT_ZN_1 09-OCT-13:21 0.00 0.00 0.00 -14750.70 0.00 0.00 20.43 27.57 478.41 16808.91 0.00 0.00 0.00 0.00 -0.00 0.00 -23.76 -2560.87
PERIMETER_BOT_ZN_4 10-SEP-17:11 0.00 0.00 0.00 -13742.66 0.00 0.00 0.00 17.46 244.42 8585.05 0.00 4.49 4891.26 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 25-JUN-17:01 0.00 0.00 0.00 -9960.44 0.00 0.00 0.00 27.57 386.10 3503.35 0.00 82.59 5960.82 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 06-AUG-09:01 0.00 0.00 0.00 -15309.11 0.00 0.00 12.62 17.46 302.86 11035.27 0.00 0.00 3957.21 0.00 -0.00 0.00 -16.30 0.00
PERIMETER_MID_ZN_1 08-OCT-12:51 0.00 0.00 0.00 -17028.49 0.00 0.00 19.79 27.57 478.41 17363.09 0.00 0.00 0.00 0.00 -0.00 0.00 -62.08 -798.29
PERIMETER_MID_ZN_4 25-JUN-16:21 0.00 0.00 0.00 -16642.12 0.00 0.00 10.66 17.46 302.86 12241.23 0.00 22.88 4047.03 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 26-JUN-13:40 0.00 -12291.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.39 12258.18 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 17-JUL-10:10 0.00 -5946.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.51 5905.69 0.00 -0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 17-JUL-12:08 0.00 -6492.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.24 6465.70 0.00 -0.00 0.00 0.00 0.00
Total Facility 17-JUL-06:03 0.00 -8346.70 0.00 -178584.07 0.00 0.00 3473.74 6557.23 22496.85 35373.32 0.00 0.00 120159.31 0.00 0.00 0.00 -1129.68 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 26-DEC-06:11 0.00 0.00 14119.58 0.00 0.00 0.00 495.78 548.43 3025.92 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18189.71
CORE_TOP 06-FEB-05:01 0.00 0.00 23456.42 0.00 0.00 0.00 0.00 211.73 2442.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -26110.21
PERIMETER_TOP_ZN_3 24-DEC-03:42 0.00 0.00 9562.76 0.00 0.00 0.00 0.00 44.64 386.10 0.00 0.00 0.00 0.00 0.00 -3951.18 0.00 -699.01 -5343.31
PERIMETER_TOP_ZN_2 24-DEC-03:42 0.00 0.00 8472.89 0.00 0.00 0.00 0.00 28.26 244.42 0.00 0.00 0.00 0.00 0.00 -2708.47 0.00 -469.39 -5567.71
PERIMETER_TOP_ZN_1 24-DEC-06:22 0.00 0.00 11299.05 0.00 0.00 0.00 59.82 57.81 478.41 0.00 0.00 0.00 0.00 0.00 -3939.50 0.00 -639.00 -7316.59
PERIMETER_TOP_ZN_4 24-DEC-03:42 0.00 0.00 9102.42 0.00 0.00 0.00 0.00 28.26 244.42 0.00 0.00 0.00 0.00 0.00 -2713.06 0.00 -471.24 -6190.79
PERIMETER_BOT_ZN_3 06-FEB-05:01 0.00 0.00 6666.59 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -2968.74 0.00 -174.90 -4082.39
PERIMETER_BOT_ZN_2 06-FEB-05:01 0.00 0.00 6014.29 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1970.55 0.00 -116.76 -4281.12
PERIMETER_BOT_ZN_1 22-DEC-07:10 0.00 0.00 9899.37 0.00 0.00 0.00 206.35 346.86 637.88 0.00 0.00 0.00 15686.89 0.00 -4274.26 0.00 -22503.10 0.00
PERIMETER_BOT_ZN_4 06-FEB-05:01 0.00 0.00 6291.11 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -2013.35 0.00 -116.91 -4515.00
PERIMETER_MID_ZN_3 06-FEB-05:11 0.00 0.00 7400.90 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -2933.99 0.00 -288.53 -4737.81
PERIMETER_MID_ZN_2 06-FEB-05:11 0.00 0.00 6898.75 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1949.33 0.00 -193.24 -5110.33
PERIMETER_MID_ZN_1 06-FEB-05:11 0.00 0.00 8866.08 0.00 0.00 0.00 0.00 44.64 514.80 0.00 0.00 0.00 0.00 0.00 -3005.17 0.00 -289.51 -6130.83
PERIMETER_MID_ZN_4 06-FEB-05:11 0.00 0.00 7138.31 0.00 0.00 0.00 0.00 28.26 325.89 0.00 0.00 0.00 0.00 0.00 -1994.79 0.00 -193.23 -5304.44
TOPFLOOR_PLENUM 22-DEC-06:13 15334.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -167.31 -15166.74
MIDFLOOR_PLENUM 05-NOV-15:02 7927.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -31.78 -7895.57
FIRSTFLOOR_PLENUM 23-OCT-05:01 7229.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -144.69 -7084.69
Total Facility 06-FEB-06:01 10218.04 3779.65 119410.97 -3779.65 0.00 0.00 2505.57 1072.56 19712.35 0.00 0.00 0.00 0.00 0.00 -30930.43 0.00 -4057.17 -117931.90



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 6.3187 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.5712 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 6.2518 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 5.2543 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 6.7576 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 6.1408 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PACU_VAV_BOT 3.1593 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0764 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_MID 3.1259 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0755 0.0000 1.0000 Not calculated 0.0000 0.0000    
PACU_VAV_TOP 3.3788 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 1.0741 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_BOTTOM PACU_VAV_BOT 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID PACU_VAV_MID 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP PACU_VAV_TOP 0.000000 52.9387 0.000432 983.54 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID 0.000000 7.0652 0.000432 131.26 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID 0.000000 11.1599 0.000432 207.34 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID 0.000000 7.0647 0.000432 131.25 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PACU_VAV_BOT   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_MID   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000
PACU_VAV_TOP   0.00 0.000432 1660.7286 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.1107 3.1107 0.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4994 2.4994 0.6374 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6716 2.6716 0.6358 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8428 0.8428 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9675 0.9675 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1544 1.1544 0.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1212 1.1212 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6459 0.6459 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7863 0.7863 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9076 0.9076 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8682 0.8682 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7273 0.7273 0.1345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9560 0.9560 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0385 1.0385 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0306 1.0306 0.0845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 6.3187 5.5712 6.3187 1.0764 0.0000 1.0000
PACU_VAV_MID 6.2518 5.2543 6.2518 1.0755 0.0000 1.0000
PACU_VAV_TOP 6.7576 6.1408 6.7576 1.0741 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_BOTTOM PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5553 1.5553 0.6377 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2497 1.2497 0.6374 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3358 1.3358 0.6358 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4214 0.4214 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4838 0.4838 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5772 0.5772 0.1339 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 PACU_VAV_TOP AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5606 0.5606 0.0852 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3229 0.3229 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3932 0.3932 0.0849 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4538 0.4538 0.1343 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 PACU_VAV_BOT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4341 0.4341 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3636 0.3636 0.1345 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4780 0.4780 0.0851 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5193 0.5193 0.1340 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 PACU_VAV_MID AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5153 0.5153 0.0845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PACU_VAV_BOT 3.1593 1.0764 1.0764 1.0764 0.0000 1.0000
PACU_VAV_MID 3.1259 1.0755 1.0755 1.0755 0.0000 1.0000
PACU_VAV_TOP 3.3788 1.0741 1.0741 1.0741 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Total gross floor area [m2] 4982.19
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_BOTTOM 983.54 983.54 0.00 113.98
CORE_MID 983.54 983.54 0.00 113.98
CORE_TOP 983.54 983.54 0.00 113.98
PERIMETER_TOP_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_TOP_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_TOP_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_BOT_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_2 131.26 131.26 0.00 113.98
PERIMETER_BOT_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_BOT_ZN_4 131.25 131.25 0.00 113.98
PERIMETER_MID_ZN_3 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_2 131.26 131.26 0.00 96.54
PERIMETER_MID_ZN_1 207.34 207.34 0.00 113.98
PERIMETER_MID_ZN_4 131.25 131.25 0.00 113.98
TOPFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
MIDFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
FIRSTFLOOR_PLENUM 1660.73 1660.73 0.00 0.00
Totals 4982.19 4982.19 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 280.83
Number of hours cooling loads not met 215.50
Number of hours not met 496.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 341.83 242080.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 165.22 78403.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 232.25 25003.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 50.78 5686.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLift 134.36 7125.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ElevatorLightsFan 0.64 86.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 584.69 34487.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 26.89 1410.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 118.83 35471.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1.93 771.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 55.70 6796.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 719.69 1371.28
Natural Gas 0.00 341.83
Additional 0.00 0.00
Total 719.69 1713.11


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 46.62
Space Heating 0.00
Space Cooling 33.16
Fans (All) 23.85
Service Water Heating 11.18
Receptacle Equipment 144.45
Miscellaneous (All) 275.24
Subtotal 275.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 68.61
Service Water Heating 0.00
Miscellaneous (All) 68.61
Subtotal 68.61


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.56
Space Heating 19.95
Space Cooling 9.64
Fans (All) 6.94
Service Water Heating 3.25
Receptacle Equipment 42.01
Miscellaneous 4.65


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
ELEVATOR_RUNNING_SCH 145. 3744.
ELEVATOR_STANDBY_SCH 8276. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2460. 8760.
BLDG_EQUIP_SCH 4095. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2545. 5992.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 1470. 4212.
BLDG_SWH_SCH 1441. 5992.
WORK_EFF_SCH 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED 438. 8760.
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
INFIL_SCH_PNNL 5172. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
PERIMETER_MID_ZN_2_OA_MULT 7824. 7824.
PERIMETER_MID_ZN_2_MDP_SCH 706. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 8737.67 22.33 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8757.17 2.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8727.83 32.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8734.67 25.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8729.33 30.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8742.67 17.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8746.33 13.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8741.33 18.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.83 0.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8730.33 29.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8736.50 23.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8733.17 26.83 0.00 0.00 0.00
TOPFLOOR_PLENUM 8654.17 105.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8654.17 0.00 0.00 0.00 0.00
Max 8760.00 105.83 0.00 0.00 0.00
Average 8740.61 19.39 0.00 0.00 0.00
Sum 157331.00 349.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_BOTTOM 128303.33 0.67 0.00 0.00 0.00
CORE_MID 128304.00 0.00 0.00 0.00 0.00
CORE_TOP 128304.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128304.00 0.67 0.00 0.00 0.00
Average 34143.30 0.04 0.00 0.00 0.00
Sum 614579.33 0.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 8672.33 87.67 0.00 0.00 0.00
CORE_MID 8728.83 31.17 0.00 0.00 0.00
CORE_TOP 8750.17 9.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8748.83 11.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8734.50 25.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8742.00 18.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8741.67 18.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8748.50 11.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8757.83 2.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8752.33 7.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8754.50 5.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8734.67 25.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8742.67 17.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8738.33 21.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 8736.33 23.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
Min 8672.33 0.00 0.00 0.00 0.00
Max 8760.00 87.67 0.00 0.00 0.00
Average 8742.42 17.58 0.00 0.00 0.00
Sum 157363.50 316.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_BOTTOM 128273.83 30.17 0.00 0.00 0.00
CORE_MID 128297.67 6.33 0.00 0.00 0.00
CORE_TOP 128303.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 14016.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 14016.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 10134.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 14016.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 128303.00 30.17 0.00 0.00 0.00
Average 34141.25 2.08 0.00 0.00 0.00
Sum 614542.50 37.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-07-03 12:20:08

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 14016.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 14016.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 10134.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 14016.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
FIRSTFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 24909.00 0.00
Average 0.00 0.00 12759.33 0.00
Sum 0.00 0.00 229668.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 0.846
February -0.25
March 4.824
April 6.083
May 13.735
June 22.164
July 22.707
August 21.737
September 18.538
October 7.117
November 3.031
December -1.01
   
Annual Sum or Average 10.017
Minimum of Months -1.01
Maximum of Months 22.707



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.123641E+11 27364.98 26-JAN-07:02 -1.7 -2.2 0.197224E+10 2606.66 10-JAN-10:09 -1.7 -2.2
February 0.109614E+11 32731.82 28-FEB-07:02 -2.7 -3.1 0.178173E+10 2606.64 28-FEB-10:20 2.67 1.45
March 0.155918E+11 34880.14 15-MAR-06:02 10.00 2.57 0.214946E+10 2606.64 27-MAR-09:20 1.33 -0.7
April 0.142999E+11 31768.03 10-APR-06:03 3.17 -3.0 0.191229E+10 2606.66 13-APR-13:00 15.00 9.82
May 0.210213E+11 37275.53 30-MAY-05:12 8.33 7.37 0.207980E+10 2606.71 26-MAY-13:09 8.33 7.37
June 0.261171E+11 38307.10 05-JUN-05:12 13.47 9.51 0.207343E+10 2606.69 08-JUN-13:09 24.58 13.90
July 0.257206E+11 38852.05 31-JUL-05:12 16.00 14.00 0.192804E+10 2606.67 11-JUL-09:30 16.00 14.00
August 0.273076E+11 38428.14 08-AUG-05:12 16.00 13.81 0.216344E+10 2606.69 10-AUG-09:50 25.33 13.99
September 0.243760E+11 38612.36 06-SEP-05:12 13.30 10.69 0.192123E+10 2606.88 05-SEP-09:09 13.30 10.69
October 0.192408E+11 38297.41 10-OCT-05:12 8.67 4.93 0.199373E+10 2606.70 03-OCT-13:09 8.67 4.93
November 0.147482E+11 34862.68 09-NOV-07:01 10.17 5.62 0.196852E+10 2606.63 01-NOV-09:39 10.17 5.62
December 0.116586E+11 23827.21 05-DEC-07:02 -2.7 -4.1 0.187222E+10 2606.63 18-DEC-10:20 3.33 -0.7
                     
Annual Sum or Average 0.223408E+12         0.238161E+11        
Minimum of Months 0.109614E+11 23827.21   -2.7 -4.1 0.178173E+10 2606.63   -1.7 -2.2
Maximum of Months 0.273076E+11 38852.05   16.00 14.00 0.216344E+10 2606.88   25.33 14.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.258822E+09 3393.84 20-JAN-15:05 19.67 6.93 0.00 0.00 01-JAN-00:10 19.67 6.93
February 0.349180E+09 3189.40 18-FEB-14:30 19.50 7.87 0.00 0.00 01-FEB-00:10 19.50 7.87
March 0.128884E+10 7329.47 14-MAR-14:05 23.00 7.59 0.00 0.00 01-MAR-00:10 23.00 7.59
April 0.131878E+10 6498.89 21-APR-13:30 15.50 6.04 0.00 0.00 01-APR-00:10 15.50 6.04
May 0.319329E+10 9058.25 31-MAY-14:30 28.00 14.75 0.00 0.00 01-MAY-00:10 28.00 14.75
June 0.731935E+10 12292.68 26-JUN-13:40 37.33 15.29 0.00 0.00 01-JUN-00:10 37.33 15.29
July 0.670866E+10 10774.17 17-JUL-14:00 35.00 14.93 0.00 0.00 01-JUL-00:10 35.00 14.93
August 0.684041E+10 12139.09 16-AUG-15:00 36.00 16.15 0.00 0.00 01-AUG-00:10 36.00 16.15
September 0.442386E+10 9195.96 12-SEP-14:20 29.40 13.78 0.00 0.00 01-SEP-00:10 29.40 13.78
October 0.157103E+10 7200.48 11-OCT-15:10 25.67 9.32 0.00 0.00 01-OCT-00:10 25.67 9.32
November 0.533507E+09 4456.19 09-NOV-13:05 20.00 8.90 0.00 0.00 01-NOV-00:10 20.00 8.90
December 0.150787E+09 2020.19 01-DEC-14:40 21.33 7.55 0.00 0.00 01-DEC-00:10 21.33 7.55
                     
Annual Sum or Average 0.339565E+11         0.00        
Minimum of Months 0.150787E+09 2020.19   15.50 6.04 0.00 0.00   15.50 6.04
Maximum of Months 0.731935E+10 12292.68   37.33 16.15 0.00 0.00   37.33 16.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 45774521.49 2913.63 05-JAN-05:01 -17.0 -17.0 0.00 0.00 01-JAN-00:10 -17.0 -17.0
February 42479388.57 2222.57 10-FEB-06:01 -8.2 -9.1 0.00 0.00 01-FEB-00:10 -8.2 -9.1
March 0.377161E+09 2875.90 15-MAR-16:00 19.00 5.38 0.00 0.00 01-MAR-00:10 19.00 5.38
April 0.260435E+09 2424.78 15-APR-06:03 -4.8 -5.7 0.00 0.00 01-APR-00:10 -4.8 -5.7
May 0.127208E+10 2911.54 18-MAY-14:20 23.67 11.39 0.00 0.00 01-MAY-00:10 23.67 11.39
June 0.383666E+10 5647.50 26-JUN-15:20 39.20 15.68 0.00 0.00 01-JUN-00:10 39.20 15.68
July 0.377004E+10 5946.06 17-JUL-10:10 34.17 14.38 0.00 0.00 01-JUL-00:10 34.17 14.38
August 0.373513E+10 5172.52 21-AUG-14:40 27.00 14.47 0.00 0.00 01-AUG-00:10 27.00 14.47
September 0.251579E+10 5060.83 05-SEP-15:40 24.60 13.98 0.00 0.00 01-SEP-00:10 24.60 13.98
October 0.553670E+09 3469.84 10-OCT-16:00 25.00 8.21 0.00 0.00 01-OCT-00:10 25.00 8.21
November 0.118949E+09 2458.96 30-NOV-05:01 -12.8 -13.4 0.00 0.00 01-NOV-00:10 -12.8 -13.4
December 24223461.15 3259.89 20-DEC-05:01 -19.0 -19.2 0.00 0.00 01-DEC-00:10 -19.0 -19.2
                     
Annual Sum or Average 0.165524E+11         0.00        
Minimum of Months 24223461.15 2222.57   -19.0 -19.2 0.00 0.00   -19.0 -19.2
Maximum of Months 0.383666E+10 5946.06   39.20 15.68 0.00 0.00   39.20 15.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241989E+09 2673.50 06-JAN-05:01 -7.8 -7.9 0.00 0.00 01-JAN-00:10 -7.8 -7.9
February 0.211844E+09 2577.82 02-FEB-06:01 -9.2 -9.2 0.00 0.00 01-FEB-00:10 -9.2 -9.2
March 0.722969E+09 3211.52 15-MAR-16:00 19.00 5.38 0.00 0.00 01-MAR-00:10 19.00 5.38
April 0.529148E+09 2364.49 03-APR-05:01 -8.0 -8.0 0.00 0.00 01-APR-00:10 -8.0 -8.0
May 0.184882E+10 3211.11 16-MAY-15:50 27.00 11.83 0.00 0.00 01-MAY-00:10 27.00 11.83
June 0.433229E+10 6484.05 26-JUN-12:08 36.18 15.20 0.00 0.00 01-JUN-00:10 36.18 15.20
July 0.425042E+10 6492.93 17-JUL-12:08 36.00 14.76 0.00 0.00 01-JUL-00:10 36.00 14.76
August 0.446480E+10 5377.69 21-AUG-15:00 26.00 14.34 0.00 0.00 01-AUG-00:10 26.00 14.34
September 0.344663E+10 5587.41 05-SEP-06:07 13.90 7.58 0.00 0.00 01-SEP-00:10 13.90 7.58
October 0.132504E+10 4007.94 10-OCT-16:00 25.00 8.21 0.00 0.00 01-OCT-00:10 25.00 8.21
November 0.457286E+09 2373.36 07-NOV-16:40 17.00 6.30 0.00 0.00 01-NOV-00:10 17.00 6.30
December 0.147012E+09 3156.47 21-DEC-17:10 -22.0 -22.1 0.00 0.00 01-DEC-00:10 -22.0 -22.1
                     
Annual Sum or Average 0.219782E+11         0.00        
Minimum of Months 0.147012E+09 2364.49   -22.0 -22.1 0.00 0.00   -22.0 -22.1
Maximum of Months 0.446480E+10 6492.93   36.18 15.20 0.00 0.00   36.18 15.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.710595E+10 10551.32 25-JAN-16:20 13.67 4.08 0.180886E+10 2606.64 27-JAN-10:20 2.33 2.17
February 0.621489E+10 10476.94 27-FEB-16:30 13.00 4.47 0.163361E+10 2606.63 28-FEB-10:20 2.67 1.45
March 0.931625E+10 14408.88 15-MAR-16:00 19.00 5.38 0.203517E+10 2606.65 17-MAR-09:20 6.67 6.28
April 0.832916E+10 13051.08 21-APR-14:00 15.00 5.55 0.181784E+10 2606.73 13-APR-13:00 15.00 5.55
May 0.133208E+11 18509.84 22-MAY-06:02 11.17 10.50 0.206323E+10 2606.66 26-MAY-13:09 12.83 7.87
June 0.186244E+11 29887.54 05-JUN-05:12 13.47 9.51 0.206900E+10 2606.68 08-JUN-13:09 24.58 13.90
July 0.183641E+11 30750.65 03-JUL-05:12 11.00 7.64 0.192314E+10 2606.65 11-JUL-09:30 25.50 13.66
August 0.190119E+11 30742.02 07-AUG-05:12 16.33 11.48 0.215869E+10 2606.67 10-AUG-09:50 25.33 13.99
September 0.160501E+11 31454.59 05-SEP-05:12 14.20 8.43 0.191429E+10 2606.86 05-SEP-09:09 16.47 11.53
October 0.107289E+11 27592.54 10-OCT-06:01 8.33 4.27 0.192664E+10 2606.63 03-OCT-13:20 8.33 4.27
November 0.797877E+10 12727.26 08-NOV-16:20 16.33 7.18 0.185422E+10 2606.60 17-NOV-14:20 13.33 5.89
December 0.649368E+10 8684.30 15-DEC-16:00 6.00 2.22 0.168728E+10 2606.62 15-DEC-10:20 6.00 2.22
                     
Annual Sum or Average 0.141539E+12         0.228920E+11        
Minimum of Months 0.621489E+10 8684.30   6.00 2.22 0.163361E+10 2606.60   2.33 1.45
Maximum of Months 0.190119E+11 31454.59   19.00 11.48 0.215869E+10 2606.86   25.50 13.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.537366E+10 9600.40 20-JAN-16:30 15.00 6.47 0.168680E+10 2606.58 26-JAN-14:20 9.00 2.97
February 0.482840E+10 9284.24 27-FEB-16:20 13.00 4.42 0.154164E+10 2606.59 22-FEB-14:20 13.00 4.42
March 0.800332E+10 15390.49 15-MAR-15:20 19.67 5.62 0.194788E+10 2606.65 17-MAR-09:20 6.67 6.28
April 0.740720E+10 14401.11 21-APR-14:00 15.00 5.55 0.175425E+10 2606.73 13-APR-13:00 15.00 5.55
May 0.126030E+11 16413.68 31-MAY-15:50 28.00 14.82 0.203721E+10 2606.66 18-MAY-09:09 28.00 14.82
June 0.191840E+11 32013.61 19-JUN-05:12 18.27 12.22 0.206740E+10 2606.68 08-JUN-13:09 18.27 12.22
July 0.187726E+11 32509.28 24-JUL-05:12 18.00 14.77 0.192217E+10 2606.65 11-JUL-09:30 18.00 14.77
August 0.191041E+11 32340.89 21-AUG-05:12 19.83 12.23 0.215654E+10 2606.66 10-AUG-09:50 19.83 12.23
September 0.149837E+11 32429.63 05-SEP-05:12 14.20 8.43 0.190378E+10 2606.85 05-SEP-09:09 16.47 11.53
October 0.852244E+10 16211.72 11-OCT-15:30 25.00 9.04 0.183986E+10 2606.64 03-OCT-13:20 25.00 9.04
November 0.611632E+10 11914.00 07-NOV-16:10 20.00 7.03 0.172959E+10 2606.59 08-NOV-14:20 19.00 7.64
December 0.459728E+10 7576.49 23-DEC-17:03 -16.2 -16.6 0.157571E+10 2606.55 15-DEC-14:00 -16.2 -16.6
                     
Annual Sum or Average 0.129496E+12         0.221628E+11        
Minimum of Months 0.459728E+10 7576.49   -16.2 -16.6 0.154164E+10 2606.55   -16.2 -16.6
Maximum of Months 0.191840E+11 32509.28   28.00 14.82 0.215654E+10 2606.85   28.00 14.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.495330E+09 1442.12 20-JAN-14:40 20.33 6.84 0.322543E+09 535.22 20-JAN-14:00 20.00 6.78
February 0.452326E+09 1297.21 26-FEB-14:22 17.00 4.35 0.293261E+09 543.91 27-FEB-14:00 14.00 4.75
March 0.111606E+10 3779.20 14-MAR-14:30 23.00 7.59 0.381105E+09 549.49 16-MAR-13:20 16.00 5.23
April 0.126486E+10 3836.61 20-APR-13:30 21.50 8.83 0.350148E+09 549.51 13-APR-13:00 21.50 8.83
May 0.308680E+10 5765.70 17-MAY-13:30 29.00 11.78 0.421766E+09 549.50 17-MAY-09:20 29.00 11.78
June 0.607833E+10 11404.20 25-JUN-17:11 32.33 14.00 0.435877E+09 549.88 12-JUN-13:09 32.33 14.00
July 0.591193E+10 11498.50 16-JUL-14:22 35.50 14.51 0.405397E+09 549.77 18-JUL-13:09 34.33 14.01
August 0.539780E+10 8375.56 20-AUG-15:41 28.00 14.08 0.453551E+09 549.50 21-AUG-09:20 25.67 14.10
September 0.367078E+10 7566.23 10-SEP-16:01 31.92 12.68 0.395897E+09 549.54 05-SEP-09:09 31.92 12.68
October 0.132620E+10 4161.02 11-OCT-14:30 26.50 9.60 0.361887E+09 549.49 11-OCT-13:20 26.50 9.60
November 0.680470E+09 2459.46 09-NOV-13:40 20.00 8.72 0.331941E+09 549.48 09-NOV-14:20 19.33 8.45
December 0.346551E+09 1495.37 23-DEC-17:03 -16.2 -16.6 0.302685E+09 521.84 04-DEC-14:00 -16.2 -16.6
                     
Annual Sum or Average 0.298274E+11         0.445606E+10        
Minimum of Months 0.346551E+09 1297.21   -16.2 -16.6 0.293261E+09 521.84   -16.2 -16.6
Maximum of Months 0.607833E+10 11498.50   35.50 14.51 0.453551E+09 549.88   34.33 14.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.593912E+09 2776.02 20-JAN-09:50 13.33 4.49 0.223953E+09 347.88 10-JAN-10:09 13.33 4.49
February 0.715061E+09 4048.38 27-FEB-09:20 9.33 2.70 0.208693E+09 347.88 23-FEB-10:20 9.33 2.70
March 0.173468E+10 8543.90 12-MAR-10:02 15.17 5.61 0.262363E+09 347.88 27-MAR-09:39 0.67 -0.6
April 0.184007E+10 7394.41 21-APR-08:50 11.83 5.97 0.236975E+09 347.89 13-APR-13:00 11.83 5.97
May 0.348548E+10 8067.57 16-MAY-08:40 22.00 11.45 0.273406E+09 347.90 17-MAY-09:09 25.33 11.72
June 0.640910E+10 11594.38 11-JUN-09:02 20.37 10.85 0.276552E+09 348.73 27-JUN-09:00 26.60 12.07
July 0.600932E+10 13978.93 16-JUL-09:02 33.17 14.76 0.257362E+09 348.78 18-JUL-09:00 31.00 14.50
August 0.619233E+10 14054.88 06-AUG-09:12 25.67 15.47 0.288021E+09 348.65 31-AUG-09:50 26.67 13.56
September 0.426987E+10 11829.78 04-SEP-09:22 25.25 13.40 0.254050E+09 347.92 06-SEP-09:30 25.75 13.14
October 0.169128E+10 9448.60 01-OCT-09:02 13.17 7.72 0.240959E+09 347.88 03-OCT-13:09 12.17 8.60
November 0.816983E+09 3850.06 07-NOV-09:10 14.00 4.09 0.226852E+09 347.87 14-NOV-10:20 3.33 2.24
December 0.396039E+09 1136.28 14-DEC-09:45 9.67 1.34 0.207141E+09 347.88 18-DEC-10:20 3.33 -0.7
                     
Annual Sum or Average 0.341541E+11         0.295633E+10        
Minimum of Months 0.396039E+09 1136.28   9.33 1.34 0.207141E+09 347.87   0.67 -0.7
Maximum of Months 0.640910E+10 14054.88   33.17 15.47 0.288021E+09 348.78   31.00 14.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.393822E+10 16158.91 22-JAN-12:23 6.50 3.36 0.381359E+09 567.42 20-JAN-14:09 6.50 3.36
February 0.370452E+10 17859.15 26-FEB-13:01 17.83 4.74 0.346677E+09 549.74 27-FEB-14:00 14.00 4.75
March 0.429966E+10 17860.58 12-MAR-12:41 18.83 6.01 0.412645E+09 562.51 15-MAR-13:30 20.50 6.02
April 0.284765E+10 9653.15 21-APR-13:05 15.83 6.37 0.366076E+09 549.83 21-APR-13:39 15.33 5.87
May 0.424974E+10 8484.33 16-MAY-13:10 27.17 12.14 0.423840E+09 549.51 26-MAY-13:09 12.83 7.87
June 0.696393E+10 15460.26 25-JUN-14:32 33.43 13.43 0.435346E+09 549.98 30-JUN-13:30 35.25 14.01
July 0.703450E+10 15831.81 23-JUL-13:32 34.67 16.62 0.405323E+09 549.51 11-JUL-09:30 34.67 16.62
August 0.827044E+10 16069.87 06-AUG-12:32 31.33 15.82 0.454200E+09 563.30 31-AUG-13:09 30.00 11.91
September 0.757461E+10 17002.18 04-SEP-13:22 29.40 13.40 0.400334E+09 603.53 28-SEP-13:20 30.50 11.31
October 0.553226E+10 17228.39 09-OCT-13:32 22.00 8.78 0.382640E+09 588.60 10-OCT-13:09 24.17 8.07
November 0.431809E+10 16949.04 05-NOV-13:12 21.00 6.50 0.381696E+09 572.73 07-NOV-14:09 22.00 7.34
December 0.307933E+10 16122.71 03-DEC-13:12 17.47 6.39 0.357686E+09 549.65 15-DEC-14:50 9.50 3.13
                     
Annual Sum or Average 0.618130E+11         0.474782E+10        
Minimum of Months 0.284765E+10 8484.33   6.50 3.36 0.346677E+09 549.51   6.50 3.13
Maximum of Months 0.827044E+10 17860.58   34.67 16.62 0.454200E+09 603.53   35.25 16.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.765439E+09 5127.11 20-JAN-15:40 18.67 7.30 0.218577E+09 347.83 27-JAN-14:00 10.00 5.47
February 0.845840E+09 5518.82 17-FEB-16:30 13.50 6.66 0.199470E+09 347.84 22-FEB-14:20 8.00 3.90
March 0.176676E+10 16113.39 12-MAR-16:02 18.00 5.74 0.248159E+09 347.84 16-MAR-13:20 16.00 5.23
April 0.168641E+10 11657.96 08-APR-17:05 15.67 5.07 0.225434E+09 347.87 13-APR-13:00 15.00 9.82
May 0.319279E+10 9842.53 28-MAY-14:53 20.00 10.08 0.267450E+09 347.85 17-MAY-09:20 20.00 10.08
June 0.586650E+10 16680.74 11-JUN-16:21 28.35 12.62 0.275861E+09 347.86 20-JUN-13:00 23.30 16.53
July 0.516823E+10 16599.48 02-JUL-16:51 28.00 12.40 0.256678E+09 347.86 11-JUL-09:30 25.50 13.66
August 0.532561E+10 16212.64 13-AUG-16:32 22.33 9.94 0.287397E+09 347.86 21-AUG-09:20 25.67 14.10
September 0.386502E+10 16445.81 10-SEP-16:01 31.92 12.68 0.251438E+09 347.88 05-SEP-09:09 31.92 12.68
October 0.196659E+10 12865.78 09-OCT-14:52 22.00 9.18 0.232926E+09 347.85 11-OCT-13:20 26.33 9.54
November 0.979123E+09 6293.43 07-NOV-15:30 21.50 7.27 0.221309E+09 347.85 09-NOV-14:20 19.33 8.45
December 0.500985E+09 3833.71 01-DEC-15:30 19.50 7.14 0.204121E+09 347.84 15-DEC-14:00 9.00 3.00
                     
Annual Sum or Average 0.319293E+11         0.288882E+10        
Minimum of Months 0.500985E+09 3833.71   13.50 5.07 0.199470E+09 347.83   8.00 3.00
Maximum of Months 0.586650E+10 16680.74   31.92 12.68 0.287397E+09 347.88   31.92 16.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.529719E+09 1310.57 20-JAN-14:50 20.17 6.81 0.320276E+09 486.83 25-JAN-14:00 14.00 4.48
February 0.406036E+09 1212.02 27-FEB-13:40 14.00 4.75 0.288792E+09 494.12 27-FEB-14:00 14.00 4.75
March 0.869150E+09 1867.19 14-MAR-15:00 23.00 7.59 0.370122E+09 549.48 16-MAR-13:20 16.00 5.23
April 0.101382E+10 1760.50 20-APR-13:30 21.50 8.83 0.342715E+09 549.49 13-APR-13:20 21.50 8.83
May 0.214982E+10 3964.24 17-MAY-13:30 29.00 11.78 0.421249E+09 549.50 18-MAY-09:09 20.33 11.73
June 0.475761E+10 8755.41 25-JUN-18:21 30.50 13.77 0.435621E+09 550.05 13-JUN-13:39 30.50 13.77
July 0.475022E+10 7260.40 17-JUL-06:03 22.50 11.12 0.405056E+09 549.66 25-JUL-13:20 28.67 16.33
August 0.465421E+10 5481.22 21-AUG-14:00 29.00 14.55 0.454168E+09 549.50 21-AUG-09:20 29.00 14.55
September 0.368308E+10 6433.77 05-SEP-06:02 13.90 7.58 0.400791E+09 549.54 05-SEP-09:09 16.47 11.53
October 0.156317E+10 3512.06 11-OCT-14:30 26.50 9.60 0.379557E+09 549.49 03-OCT-13:20 26.50 9.60
November 0.934052E+09 2104.47 09-NOV-13:30 20.00 8.78 0.342134E+09 549.49 09-NOV-10:20 20.00 8.78
December 0.505290E+09 1440.44 23-DEC-17:01 -16.2 -16.6 0.308336E+09 509.60 04-DEC-14:00 -16.2 -16.6
                     
Annual Sum or Average 0.258162E+11         0.446882E+10        
Minimum of Months 0.406036E+09 1212.02   -16.2 -16.6 0.288792E+09 486.83   -16.2 -16.6
Maximum of Months 0.475761E+10 8755.41   30.50 14.55 0.454168E+09 550.05   30.50 16.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.626559E+09 1915.23 20-JAN-09:50 13.33 4.49 0.226356E+09 347.87 24-JAN-10:20 12.00 3.75
February 0.673221E+09 3352.79 27-FEB-08:35 7.67 2.12 0.208135E+09 347.88 17-FEB-10:20 7.67 2.12
March 0.143195E+10 4807.91 15-MAR-09:10 14.17 4.19 0.262601E+09 347.88 27-MAR-09:20 1.33 -0.7
April 0.151150E+10 5123.40 21-APR-09:00 12.00 5.98 0.237782E+09 347.88 19-APR-09:09 12.00 5.98
May 0.276005E+10 7636.08 16-MAY-06:02 13.67 8.41 0.274188E+09 347.90 31-MAY-09:00 25.00 13.24
June 0.560888E+10 11418.37 11-JUN-08:51 20.00 10.75 0.276685E+09 348.85 29-JUN-09:09 28.58 13.43
July 0.526688E+10 11036.34 16-JUL-09:02 33.17 14.76 0.257479E+09 348.36 18-JUL-09:00 31.00 14.50
August 0.583120E+10 11352.03 06-AUG-09:31 26.33 15.50 0.288479E+09 348.34 31-AUG-09:50 26.67 13.56
September 0.450687E+10 10996.62 04-SEP-09:11 24.97 13.41 0.255619E+09 348.43 08-SEP-09:50 25.82 12.10
October 0.202063E+10 8032.22 09-OCT-10:02 15.50 9.03 0.249964E+09 347.88 03-OCT-13:09 15.50 9.03
November 0.104668E+10 3639.67 07-NOV-08:25 12.00 3.43 0.236727E+09 347.87 14-NOV-10:20 3.33 2.24
December 0.517819E+09 1601.91 18-DEC-08:30 -1.5 -3.4 0.214674E+09 347.88 18-DEC-10:20 3.33 -0.7
                     
Annual Sum or Average 0.318022E+11         0.298869E+10        
Minimum of Months 0.517819E+09 1601.91   -1.5 -3.4 0.208135E+09 347.87   1.33 -0.7
Maximum of Months 0.583120E+10 11418.37   33.17 15.50 0.288479E+09 348.85   31.00 14.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.260634E+10 12636.86 22-JAN-15:13 8.33 4.26 0.368689E+09 554.63 20-JAN-14:09 8.33 4.26
February 0.208199E+10 11925.64 26-FEB-13:23 17.50 4.55 0.327065E+09 549.66 27-FEB-14:00 14.00 4.75
March 0.252200E+10 12760.14 12-MAR-13:11 18.33 5.83 0.396614E+09 557.10 13-MAR-13:00 23.00 7.20
April 0.151385E+10 6802.09 21-APR-12:07 14.33 6.08 0.347782E+09 549.51 13-APR-13:39 14.33 6.08
May 0.247717E+10 7006.36 16-MAY-12:00 27.00 11.84 0.410621E+09 549.52 26-MAY-13:09 12.83 7.87
June 0.600330E+10 12234.95 25-JUN-16:21 32.70 13.84 0.433979E+09 609.50 26-JUN-12:09 36.18 15.20
July 0.609590E+10 11355.77 17-JUL-12:00 36.00 14.76 0.404087E+09 607.91 17-JUL-12:09 36.00 14.76
August 0.778160E+10 11585.15 16-AUG-12:00 35.00 12.77 0.454233E+09 622.46 16-AUG-12:09 35.17 12.78
September 0.760571E+10 13744.45 10-SEP-11:51 30.00 12.50 0.401849E+09 617.93 28-SEP-12:09 30.08 11.35
October 0.496512E+10 14747.66 09-OCT-13:21 22.00 8.88 0.384006E+09 621.42 10-OCT-13:39 24.67 8.45
November 0.353304E+10 14286.67 05-NOV-13:01 21.00 6.54 0.373277E+09 590.18 07-NOV-14:09 22.00 7.34
December 0.230062E+10 12821.27 17-DEC-13:52 18.00 5.77 0.340341E+09 549.75 15-DEC-14:00 18.00 5.77
                     
Annual Sum or Average 0.494866E+11         0.464254E+10        
Minimum of Months 0.151385E+10 6802.09   8.33 4.26 0.327065E+09 549.51   8.33 4.26
Maximum of Months 0.778160E+10 14747.66   36.00 14.76 0.454233E+09 622.46   36.18 15.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.713187E+09 3913.83 23-JAN-16:10 18.17 6.14 0.221036E+09 347.83 25-JAN-14:20 14.67 4.64
February 0.676702E+09 4116.84 17-FEB-16:30 13.50 6.66 0.200797E+09 347.85 22-FEB-14:20 8.00 3.90
March 0.130973E+10 8236.53 12-MAR-16:32 18.00 5.65 0.249942E+09 347.85 16-MAR-09:20 11.67 3.37
April 0.125327E+10 7958.96 08-APR-17:05 15.67 5.07 0.228101E+09 347.85 13-APR-13:00 15.00 9.82
May 0.235057E+10 6271.58 31-MAY-16:00 28.00 14.86 0.270178E+09 347.85 17-MAY-09:20 28.00 14.86
June 0.497301E+10 13511.30 25-JUN-16:21 32.70 13.84 0.276336E+09 347.86 27-JUN-09:20 25.53 11.25
July 0.434331E+10 12589.19 02-JUL-17:11 28.00 12.39 0.256920E+09 347.85 11-JUL-09:30 25.50 13.66
August 0.486810E+10 13460.26 13-AUG-17:01 22.17 9.93 0.288249E+09 347.86 15-AUG-13:39 25.33 13.66
September 0.397535E+10 13742.44 10-SEP-17:11 30.13 12.08 0.255062E+09 347.88 05-SEP-09:09 30.13 12.08
October 0.212437E+10 12986.56 08-OCT-16:11 17.67 8.51 0.247305E+09 347.85 19-OCT-09:20 9.67 2.68
November 0.112149E+10 5571.30 07-NOV-15:40 21.33 7.24 0.232115E+09 347.85 07-NOV-10:20 21.33 7.24
December 0.597064E+09 3239.46 04-DEC-15:30 18.00 5.80 0.209998E+09 347.83 04-DEC-14:20 18.00 5.80
                     
Annual Sum or Average 0.283061E+11         0.293604E+10        
Minimum of Months 0.597064E+09 3239.46   13.50 5.07 0.200797E+09 347.83   8.00 2.68
Maximum of Months 0.497301E+10 13742.44   32.70 14.86 0.288249E+09 347.88   30.13 14.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.736521E+09 1460.86 20-JAN-15:10 19.67 6.93 0.333087E+09 535.01 20-JAN-16:30 15.00 6.47
February 0.664532E+09 1475.51 27-FEB-15:30 13.50 4.54 0.301583E+09 547.03 27-FEB-14:00 13.50 4.54
March 0.134330E+10 3635.02 14-MAR-14:40 23.00 7.59 0.393112E+09 549.49 16-MAR-09:20 11.67 3.37
April 0.146458E+10 3520.65 20-APR-13:30 21.50 8.83 0.361251E+09 549.51 13-APR-13:00 21.50 8.83
May 0.321777E+10 5444.36 17-MAY-13:30 29.00 11.78 0.428847E+09 549.50 18-MAY-09:09 20.33 11.73
June 0.588831E+10 9960.29 25-JUN-17:01 32.52 14.00 0.436392E+09 550.53 14-JUN-13:20 32.52 14.00
July 0.574716E+10 9807.52 16-JUL-12:12 36.33 14.58 0.405824E+09 550.52 24-JUL-13:20 32.00 16.99
August 0.531383E+10 7236.54 21-AUG-06:03 19.75 12.40 0.454538E+09 550.45 18-AUG-13:20 19.75 12.40
September 0.382157E+10 7534.24 11-SEP-06:03 19.00 9.04 0.400197E+09 549.54 05-SEP-09:09 19.00 9.04
October 0.163053E+10 4109.52 10-OCT-15:20 25.00 8.38 0.377947E+09 549.50 06-OCT-09:20 25.00 8.38
November 0.991924E+09 2670.47 09-NOV-13:30 20.00 8.78 0.344336E+09 549.49 17-NOV-14:20 13.33 5.89
December 0.585054E+09 1419.16 23-DEC-17:01 -16.2 -16.6 0.311954E+09 541.62 04-DEC-14:00 -16.2 -16.6
                     
Annual Sum or Average 0.314051E+11         0.454907E+10        
Minimum of Months 0.585054E+09 1419.16   -16.2 -16.6 0.301583E+09 535.01   -16.2 -16.6
Maximum of Months 0.588831E+10 9960.29   36.33 14.58 0.454538E+09 550.53   32.52 16.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.678821E+09 3823.35 26-JAN-13:02 9.00 2.97 0.170561E+09 356.46 10-JAN-11:09 9.00 2.97
February 0.841613E+09 5262.60 27-FEB-09:05 9.17 2.67 0.157313E+09 356.45 10-FEB-11:09 9.17 2.67
March 0.186960E+10 9997.97 12-MAR-08:13 12.00 4.32 0.196088E+09 356.46 27-MAR-10:09 0.33 -0.4
April 0.191181E+10 7756.23 21-APR-08:30 11.50 5.93 0.177718E+09 356.47 13-APR-10:09 11.50 5.93
May 0.345541E+10 10194.48 28-MAY-09:02 12.33 8.71 0.203843E+09 356.48 31-MAY-10:09 25.17 13.22
June 0.606862E+10 14545.28 11-JUN-08:51 20.00 10.75 0.205259E+09 356.47 20-JUN-14:09 23.67 16.48
July 0.569578E+10 14886.66 16-JUL-08:51 33.00 14.82 0.191652E+09 356.46 18-JUL-14:09 31.00 15.46
August 0.589820E+10 15308.44 06-AUG-09:01 25.33 15.45 0.213709E+09 356.49 30-AUG-10:09 25.17 12.29
September 0.423453E+10 13435.30 17-SEP-08:12 16.07 9.64 0.189139E+09 356.48 18-SEP-10:09 25.18 11.04
October 0.189340E+10 10158.64 09-OCT-09:32 14.00 8.70 0.182265E+09 356.46 10-OCT-14:09 25.00 8.67
November 0.943568E+09 4941.46 07-NOV-08:50 13.33 3.89 0.172967E+09 356.46 07-NOV-11:09 16.67 5.90
December 0.456242E+09 2215.95 14-DEC-11:05 13.50 3.41 0.158264E+09 356.46 29-DEC-11:09 8.17 2.65
                     
Annual Sum or Average 0.339476E+11         0.221878E+10        
Minimum of Months 0.456242E+09 2215.95   9.00 2.67 0.157313E+09 356.45   0.33 -0.4
Maximum of Months 0.606862E+10 15308.44   33.00 15.45 0.213709E+09 356.49   31.00 16.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.462449E+10 14642.96 22-JAN-12:42 6.83 3.54 0.390513E+09 589.90 20-JAN-14:09 6.83 3.54
February 0.422614E+10 15024.66 26-FEB-13:12 17.67 4.65 0.353788E+09 555.95 17-FEB-14:09 17.67 4.65
March 0.465840E+10 14874.87 12-MAR-12:52 19.00 5.98 0.421204E+09 579.20 15-MAR-13:20 20.33 5.93
April 0.305167E+10 9210.13 21-APR-13:05 15.83 6.37 0.375915E+09 550.37 21-APR-13:50 15.17 5.71
May 0.436153E+10 7957.21 16-MAY-13:10 27.17 12.14 0.430276E+09 549.51 10-MAY-13:50 27.17 12.14
June 0.671332E+10 14128.74 25-JUN-16:21 32.70 13.84 0.436174E+09 550.84 30-JUN-13:20 34.97 13.87
July 0.680745E+10 14294.10 23-JUL-12:42 33.67 16.02 0.405902E+09 550.74 31-JUL-13:20 26.67 17.30
August 0.809146E+10 15087.58 27-AUG-12:22 25.00 15.13 0.455397E+09 573.61 31-AUG-13:20 30.00 11.86
September 0.768791E+10 16154.74 17-SEP-12:51 26.10 10.84 0.403477E+09 621.20 28-SEP-13:20 30.50 11.31
October 0.603097E+10 17026.85 08-OCT-12:51 21.00 8.56 0.394108E+09 613.52 10-OCT-13:09 24.17 8.07
November 0.503073E+10 16891.57 05-NOV-13:01 21.00 6.54 0.391901E+09 597.80 07-NOV-14:09 22.00 7.34
December 0.366865E+10 14928.42 17-DEC-13:12 18.00 5.78 0.367049E+09 554.51 14-DEC-14:09 18.00 5.78
                     
Annual Sum or Average 0.649527E+11         0.482570E+10        
Minimum of Months 0.305167E+10 7957.21   6.83 3.54 0.353788E+09 549.51   6.83 3.54
Maximum of Months 0.809146E+10 17026.85   33.67 16.02 0.455397E+09 621.20   34.97 17.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.976564E+09 5084.23 20-JAN-15:40 18.67 7.30 0.224875E+09 347.84 26-JAN-14:20 9.00 2.97
February 0.100868E+10 6421.37 26-FEB-15:53 18.00 5.19 0.204685E+09 347.84 28-FEB-14:30 4.50 2.83
March 0.191114E+10 10783.34 12-MAR-16:12 18.00 5.71 0.255527E+09 347.85 16-MAR-09:20 11.67 3.37
April 0.178745E+10 10745.98 08-APR-17:05 15.67 5.07 0.232639E+09 347.87 13-APR-13:00 15.00 9.82
May 0.325001E+10 9627.52 28-MAY-15:02 20.00 10.02 0.271901E+09 347.86 10-MAY-13:50 20.00 10.02
June 0.567818E+10 16641.97 25-JUN-16:21 32.70 13.84 0.276350E+09 347.86 27-JUN-09:20 25.53 11.25
July 0.500041E+10 15218.30 02-JUL-16:31 28.00 12.40 0.257033E+09 347.86 11-JUL-09:30 25.50 13.66
August 0.521269E+10 16377.48 13-AUG-17:01 22.17 9.93 0.288077E+09 347.86 15-AUG-13:39 25.33 13.66
September 0.393224E+10 16115.82 10-SEP-17:11 30.13 12.08 0.253982E+09 347.88 05-SEP-09:09 30.13 12.08
October 0.219000E+10 15322.25 08-OCT-15:31 18.67 8.79 0.242572E+09 347.85 06-OCT-09:20 18.67 8.79
November 0.121550E+10 10641.91 05-NOV-15:02 20.67 6.59 0.229058E+09 347.85 09-NOV-14:20 19.33 8.45
December 0.677116E+09 3849.14 14-DEC-15:30 14.50 4.64 0.209908E+09 347.84 18-DEC-14:00 5.00 0.54
                     
Annual Sum or Average 0.328400E+11         0.294661E+10        
Minimum of Months 0.677116E+09 3849.14   14.50 4.64 0.204685E+09 347.84   4.50 0.54
Maximum of Months 0.567818E+10 16641.97   32.70 13.84 0.288077E+09 347.88   30.13 13.66



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 0.50
February 0.00 0.00 01-FEB-00:10 -5.3
March 0.00 0.00 01-MAR-00:10 -1.1
April 0.00 0.00 01-APR-00:10 5.90
May 0.00 0.00 01-MAY-00:10 5.43
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.00 0.00 01-OCT-00:10 10.30
November 0.00 0.00 01-NOV-00:10 -5.7
December 0.00 0.00 01-DEC-00:10 2.77
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -5.7
Maximum of Months 0.00 0.00   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.268563E+10 13993.91 05-JAN-06:13 -17.0
February 0.279549E+10 14284.67 06-FEB-06:08 -10.0
March 0.189857E+10 11286.79 20-MAR-05:12 0.00
April 0.127187E+10 13204.10 17-APR-05:12 -8.0
May 0.451390E+09 5562.90 01-MAY-06:03 6.33
June 0.133760E+09 4801.02 26-JUN-05:12 17.53
July 0.107483E+09 4606.52 02-JUL-06:53 15.00
August 0.146208E+09 4362.67 13-AUG-07:53 15.00
September 0.351270E+09 4295.58 22-SEP-06:02 -1.4
October 0.167403E+10 12713.05 30-OCT-05:07 -10.0
November 0.207845E+10 13995.69 30-NOV-06:06 -12.0
December 0.416187E+10 15334.03 22-DEC-06:13 -20.7
         
Annual Sum or Average 0.177560E+11      
Minimum of Months 0.107483E+09 4295.58   -20.7
Maximum of Months 0.416187E+10 15334.03   17.53



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156184E+10 7470.06 15-JAN-13:23 4.00
February 0.155507E+10 7242.90 06-FEB-07:19 -9.3
March 0.101296E+10 6780.64 20-MAR-06:12 0.00
April 0.784004E+09 5098.94 03-APR-06:12 -7.3
May 0.168444E+09 3365.80 28-MAY-09:02 12.33
June 27761038.28 4645.39 11-JUN-15:31 28.87
July 36885537.65 3960.73 16-JUL-09:31 33.67
August 25615944.46 4240.78 06-AUG-10:21 28.50
September 69879236.66 5151.54 17-SEP-14:12 26.60
October 0.643770E+09 6095.73 08-OCT-14:51 20.00
November 0.128419E+10 7927.24 05-NOV-15:02 20.67
December 0.189915E+10 7921.27 26-DEC-07:13 6.67
         
Annual Sum or Average 0.906957E+10      
Minimum of Months 25615944.46 3365.80   -9.3
Maximum of Months 0.189915E+10 7927.24   33.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.920316E+09 4674.91 15-JAN-14:02 6.00
February 0.899854E+09 3501.25 28-FEB-06:03 -3.0
March 0.625755E+09 2993.63 12-MAR-15:52 18.00
April 0.470829E+09 4152.67 11-APR-05:03 -2.7
May 82138083.00 4101.30 12-MAY-05:03 1.50
June 27221778.27 2507.72 25-JUN-15:01 33.62
July 32882659.38 2475.37 04-JUL-14:51 27.00
August 30299731.50 2792.86 13-AUG-15:01 23.00
September 49314254.99 4642.34 22-SEP-05:03 -1.7
October 0.378063E+09 7228.22 23-OCT-05:01 -4.0
November 0.691199E+09 6393.93 20-NOV-06:01 -3.0
December 0.112007E+10 4249.59 17-DEC-13:12 18.00
         
Annual Sum or Average 0.532794E+10      
Minimum of Months 27221778.27 2475.37   -4.0
Maximum of Months 0.112007E+10 7228.22   33.62



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 27609689.64 11975.46 06-JAN-07:01 -7.0
February 0.137046E+09 13859.91 06-FEB-06:01 -10.0
March 31012249.23 12917.72 20-MAR-05:01 0.00
April 11883283.58 11954.98 17-APR-06:01 -7.7
May 0.00 0.00 01-MAY-00:10 5.43
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 4392469.42 11682.03 31-OCT-06:01 -9.0
November 6328071.62 11826.24 01-NOV-06:01 -2.8
December 0.171654E+09 14119.51 26-DEC-06:11 7.00
         
Annual Sum or Average 0.389926E+09      
Minimum of Months 0.00 0.00   -10.0
Maximum of Months 0.171654E+09 14119.51   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.747512E+09 20810.77 17-JAN-06:01 -0.2
February 0.107241E+10 23456.46 06-FEB-05:01 -10.0
March 0.414333E+09 22275.12 20-MAR-04:01 0.83
April 0.358862E+09 21450.50 03-APR-04:01 -8.0
May 5811284.77 17668.62 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.300162E+09 20693.46 30-OCT-05:01 -10.0
November 0.413577E+09 20546.57 30-NOV-06:01 -12.0
December 0.154074E+10 23227.97 26-DEC-06:11 7.00
         
Annual Sum or Average 0.485341E+10      
Minimum of Months 0.00 0.00   -12.0
Maximum of Months 0.154074E+10 23456.46   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.198611E+10 8778.30 02-JAN-05:01 -2.2
February 0.221868E+10 9270.16 12-FEB-05:33 -19.3
March 0.109724E+10 9152.13 19-MAR-07:53 -12.9
April 0.591022E+09 8966.02 03-APR-04:01 -8.0
May 31338705.19 7547.00 01-MAY-05:12 6.00
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 10839990.46 6821.18 22-SEP-06:02 -1.4
October 0.832692E+09 8895.73 30-OCT-04:11 -10.0
November 0.139265E+10 8884.43 30-NOV-05:01 -12.8
December 0.335954E+10 9562.82 24-DEC-03:42 -20.2
         
Annual Sum or Average 0.115201E+11      
Minimum of Months 0.00 0.00   -20.2
Maximum of Months 0.335954E+10 9562.82   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.962054E+09 7561.14 02-JAN-05:01 -2.2
February 0.114121E+10 8095.35 12-FEB-05:33 -19.3
March 0.576950E+09 7978.53 19-MAR-07:53 -12.9
April 0.308693E+09 7850.90 03-APR-04:01 -8.0
May 9676187.21 6196.75 01-MAY-05:12 6.00
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 4880683.95 5342.84 22-SEP-06:02 -1.4
October 0.529226E+09 7743.08 30-OCT-04:11 -10.0
November 0.727058E+09 7763.13 29-NOV-05:01 -10.0
December 0.182539E+10 8472.92 24-DEC-03:42 -20.2
         
Annual Sum or Average 0.608514E+10      
Minimum of Months 0.00 0.00   -20.2
Maximum of Months 0.182539E+10 8472.92   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.100883E+10 10246.03 05-JAN-05:01 -17.0
February 0.142057E+10 10943.67 06-FEB-04:42 -10.0
March 0.861267E+09 10793.35 19-MAR-07:53 -12.9
April 0.535748E+09 10616.99 03-APR-04:01 -8.0
May 35265240.53 8675.64 01-MAY-05:12 6.00
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 9504980.19 7672.29 22-SEP-06:02 -1.4
October 0.749128E+09 10480.03 30-OCT-04:11 -10.0
November 0.822554E+09 10440.33 29-NOV-05:01 -10.0
December 0.197018E+10 11299.08 24-DEC-06:22 -19.0
         
Annual Sum or Average 0.741305E+10      
Minimum of Months 0.00 0.00   -19.0
Maximum of Months 0.197018E+10 11299.08   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107335E+10 8058.71 02-JAN-05:01 -2.2
February 0.125473E+10 8655.88 06-FEB-04:42 -10.0
March 0.661547E+09 8554.33 19-MAR-07:53 -12.9
April 0.379744E+09 8415.88 03-APR-04:01 -8.0
May 22959739.47 6545.44 01-MAY-05:12 6.00
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 7949677.51 5563.00 22-SEP-06:02 -1.4
October 0.535748E+09 8293.92 30-OCT-04:11 -10.0
November 0.792778E+09 8338.16 29-NOV-05:01 -10.0
December 0.193127E+10 9102.44 24-DEC-03:42 -20.2
         
Annual Sum or Average 0.666008E+10      
Minimum of Months 0.00 0.00   -20.2
Maximum of Months 0.193127E+10 9102.44   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107300E+10 6204.83 06-JAN-05:01 -7.8
February 0.129179E+10 6666.69 06-FEB-05:01 -10.0
March 0.525327E+09 6083.02 20-MAR-04:01 0.83
April 0.215185E+09 6087.03 17-APR-05:01 -8.0
May 4076166.21 5208.86 02-MAY-06:02 0.17
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.164739E+09 5767.00 31-OCT-05:01 -8.2
November 0.317680E+09 6003.57 30-NOV-06:01 -12.0
December 0.139253E+10 6519.81 23-DEC-05:01 -21.4
         
Annual Sum or Average 0.498434E+10      
Minimum of Months 0.00 0.00   -21.4
Maximum of Months 0.139253E+10 6666.69   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.370849E+09 5428.34 06-JAN-05:01 -7.8
February 0.564715E+09 6014.52 06-FEB-05:01 -10.0
March 0.225047E+09 5302.94 20-MAR-04:01 0.83
April 96283534.51 5243.89 03-APR-05:01 -8.0
May 489947.52 2365.69 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.102430E+09 4902.84 31-OCT-05:01 -8.2
November 0.143744E+09 5198.12 30-NOV-06:01 -12.0
December 0.628964E+09 5798.86 22-DEC-05:01 -21.0
         
Annual Sum or Average 0.213252E+10      
Minimum of Months 0.00 0.00   -21.0
Maximum of Months 0.628964E+09 6014.52   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152349E+10 9552.10 05-JAN-07:10 -17.0
February 0.188227E+10 9428.20 06-FEB-07:50 -8.3
March 0.158803E+10 8237.35 29-MAR-06:10 -7.7
April 0.112923E+10 8598.44 03-APR-07:00 -6.0
May 0.387549E+09 7405.69 02-MAY-06:10 0.17
June 7633746.92 5745.77 09-JUN-06:06 9.37
July 698768.78 1247.77 03-JUL-06:07 11.00
August 495464.46 2520.88 23-AUG-06:08 12.50
September 61766781.77 6968.14 22-SEP-06:10 -1.4
October 0.114706E+10 8667.87 30-OCT-06:10 -10.0
November 0.121455E+10 8726.43 28-NOV-17:10 -8.0
December 0.208307E+10 9899.56 22-DEC-07:10 -20.0
         
Annual Sum or Average 0.110258E+11      
Minimum of Months 495464.46 1247.77   -20.0
Maximum of Months 0.208307E+10 9899.56   12.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.394315E+09 5560.34 06-JAN-05:01 -7.8
February 0.559504E+09 6291.39 06-FEB-05:01 -10.0
March 0.236381E+09 5515.88 20-MAR-04:01 0.83
April 0.118608E+09 5532.58 17-APR-05:01 -8.0
May 2018066.17 4202.43 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.104966E+09 5070.88 31-OCT-05:01 -8.2
November 0.133991E+09 5315.41 30-NOV-06:01 -12.0
December 0.663183E+09 6000.72 22-DEC-05:01 -21.0
         
Annual Sum or Average 0.221297E+10      
Minimum of Months 0.00 0.00   -21.0
Maximum of Months 0.663183E+09 6291.39   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.755279E+09 6856.48 06-JAN-05:01 -7.8
February 0.916848E+09 7401.12 06-FEB-05:11 -10.0
March 0.300521E+09 6750.95 20-MAR-04:01 0.83
April 0.183871E+09 6691.61 03-APR-04:01 -8.0
May 1977466.93 5427.61 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 143425.34 1434.25 22-SEP-06:02 -1.4
October 0.292566E+09 6419.21 30-OCT-05:01 -10.0
November 0.443869E+09 6744.22 30-NOV-05:01 -12.8
December 0.153704E+10 7378.06 24-DEC-06:52 -20.0
         
Annual Sum or Average 0.443211E+10      
Minimum of Months 0.00 0.00   -20.0
Maximum of Months 0.153704E+10 7401.12   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.356287E+09 6221.84 06-JAN-05:01 -7.8
February 0.480148E+09 6898.99 06-FEB-05:11 -10.0
March 0.165959E+09 6066.50 20-MAR-04:01 0.83
April 99351384.27 6038.74 03-APR-04:01 -8.0
May 426363.97 2842.43 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 0.00 0.00 01-SEP-00:10 18.18
October 0.202261E+09 5588.51 30-OCT-05:01 -10.0
November 0.246227E+09 6101.08 30-NOV-05:01 -12.8
December 0.812356E+09 6716.83 22-DEC-05:01 -21.0
         
Annual Sum or Average 0.236301E+10      
Minimum of Months 0.00 0.00   -21.0
Maximum of Months 0.812356E+09 6898.99   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324468E+09 7957.89 06-JAN-05:01 -7.8
February 0.582117E+09 8866.41 06-FEB-05:11 -10.0
March 0.231718E+09 7928.63 20-MAR-04:01 0.83
April 0.172334E+09 7863.68 03-APR-04:01 -8.0
May 2801392.45 6083.02 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 71754.18 717.54 22-SEP-06:02 -1.4
October 0.269845E+09 7463.21 30-OCT-05:01 -10.0
November 0.242855E+09 7752.91 30-NOV-05:01 -12.8
December 0.789965E+09 8615.08 21-DEC-05:01 -18.2
         
Annual Sum or Average 0.261618E+10      
Minimum of Months 0.00 0.00   -18.2
Maximum of Months 0.789965E+09 8866.41   22.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.387659E+09 6321.42 06-JAN-05:01 -7.8
February 0.506660E+09 7138.56 06-FEB-05:11 -10.0
March 0.178946E+09 6229.65 20-MAR-04:01 0.83
April 0.124006E+09 6175.60 03-APR-04:01 -8.0
May 1895181.11 4237.03 01-MAY-06:03 6.33
June 0.00 0.00 01-JUN-00:10 15.88
July 0.00 0.00 01-JUL-00:10 22.27
August 0.00 0.00 01-AUG-00:10 18.93
September 194713.87 1947.14 22-SEP-06:02 -1.4
October 0.195429E+09 5716.30 30-OCT-05:01 -10.0
November 0.247907E+09 6192.00 30-NOV-05:01 -12.8
December 0.845968E+09 6914.64 22-DEC-05:01 -21.0
         
Annual Sum or Average 0.248867E+10      
Minimum of Months 0.00 0.00   -21.0
Maximum of Months 0.845968E+09 7138.56   22.27



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.210964E+11 14019.75 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.191215E+11 14019.75 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.217104E+11 14019.75 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.204846E+11 14019.75 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.214034E+11 14019.75 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.209475E+11 14019.75 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.209382E+11 14019.75 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.217104E+11 14019.75 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.204802E+11 14019.75 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.210986E+11 14019.75 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.204961E+11 14019.75 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.209360E+11 14019.75 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.250423E+12    
Minimum of Months 0.420695E+10 4936.01   0.191215E+11 14019.75  
Maximum of Months 0.500524E+10 4936.01   0.217104E+11 14019.75  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463753E+10 4936.01 02-JAN-08:09 0.971303E+10 6808.32 02-JAN-08:09
February 0.420695E+10 4936.01 01-FEB-08:09 0.879311E+10 6808.32 01-FEB-08:09
March 0.500524E+10 4936.01 01-MAR-08:09 0.101015E+11 6808.32 01-MAR-08:09
April 0.446441E+10 4936.01 03-APR-07:10 0.937947E+10 6808.32 03-APR-07:10
May 0.482138E+10 4936.01 01-MAY-07:10 0.990724E+10 6808.32 01-MAY-07:10
June 0.480039E+10 4936.01 01-JUN-07:10 0.972788E+10 6808.32 01-JUN-07:10
July 0.448540E+10 4936.01 03-JUL-07:10 0.955663E+10 6808.32 03-JUL-07:10
August 0.500520E+10 4936.01 01-AUG-07:10 0.101015E+11 6808.32 01-AUG-07:10
September 0.446441E+10 4936.01 01-SEP-07:10 0.937507E+10 6808.32 01-SEP-07:10
October 0.463757E+10 4936.01 02-OCT-07:10 0.971523E+10 6808.32 02-OCT-07:10
November 0.458488E+10 4936.01 01-NOV-07:10 0.950025E+10 6808.32 01-NOV-07:10
December 0.448544E+10 4936.01 01-DEC-08:09 0.955443E+10 6808.32 01-DEC-08:09
             
Annual Sum or Average 0.555988E+11     0.115425E+12    
Minimum of Months 0.420695E+10 4936.01   0.879311E+10 6808.32  
Maximum of Months 0.500524E+10 4936.01   0.101015E+11 6808.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.632433E+09 1040.56 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.536537E+09 974.20 06-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.594511E+09 777.79 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511746E+09 678.88 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.536936E+09 496.34 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.527790E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.497008E+09 496.34 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.564921E+09 547.00 28-AUG-15:00 0.212947E+10 1435.25 01-AUG-07:10
September 0.518404E+09 552.40 21-SEP-15:00 0.197634E+10 1435.25 01-SEP-07:10
October 0.573174E+09 887.12 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.618415E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.619577E+09 1040.56 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.673145E+10     0.243325E+11    
Minimum of Months 0.497008E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.632433E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.395215E+09 658.76 02-JAN-16:49 0.129621E+10 908.57 02-JAN-08:09
February 0.337499E+09 616.86 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.375865E+09 471.32 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324744E+09 366.22 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.342216E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.336681E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.316982E+09 314.23 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.359535E+09 350.07 28-AUG-15:00 0.134804E+10 908.57 01-AUG-07:10
September 0.328456E+09 354.08 21-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.360182E+09 552.23 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.388642E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.388271E+09 658.76 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.425429E+10     0.154036E+11    
Minimum of Months 0.316982E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.395215E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.600824E+09 1040.56 02-JAN-16:49 0.204757E+10 1435.24 02-JAN-08:09
February 0.522739E+09 972.69 06-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.590523E+09 769.18 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.512944E+09 673.29 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.539455E+09 496.34 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.531316E+09 496.34 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.500275E+09 496.34 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.567221E+09 543.37 28-AUG-15:00 0.212945E+10 1435.24 01-AUG-07:10
September 0.517323E+09 542.97 21-SEP-15:00 0.197632E+10 1435.24 01-SEP-07:10
October 0.564566E+09 878.91 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.595172E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.596135E+09 1040.56 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.663849E+10     0.243324E+11    
Minimum of Months 0.500275E+09 496.34   0.185364E+10 1435.24  
Maximum of Months 0.600824E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.384905E+09 658.71 02-JAN-16:49 0.129620E+10 908.57 02-JAN-08:09
February 0.332041E+09 614.32 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.373250E+09 498.44 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.323044E+09 444.61 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.339556E+09 314.21 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.334084E+09 337.36 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314742E+09 334.18 28-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.356078E+09 345.27 21-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.327008E+09 357.99 22-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.358866E+09 562.41 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.379519E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.380113E+09 658.71 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.420321E+10     0.154035E+11    
Minimum of Months 0.314742E+09 314.21   0.117344E+10 908.57  
Maximum of Months 0.384905E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.630231E+09 1040.56 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.534669E+09 971.69 06-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.593606E+09 767.76 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511305E+09 585.81 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.536580E+09 496.34 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.527501E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.496642E+09 496.34 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.565059E+09 542.56 28-AUG-15:00 0.212947E+10 1435.25 01-AUG-07:10
September 0.517762E+09 548.23 21-SEP-15:00 0.197634E+10 1435.25 01-SEP-07:10
October 0.571603E+09 881.29 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.616578E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.617828E+09 1040.56 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.671937E+10     0.243325E+11    
Minimum of Months 0.496642E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.630231E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.394283E+09 658.76 02-JAN-16:49 0.129621E+10 908.57 02-JAN-08:09
February 0.336740E+09 615.58 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.375234E+09 465.28 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324507E+09 364.40 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.341987E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.336478E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.316808E+09 314.23 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.359231E+09 347.68 28-AUG-15:00 0.134804E+10 908.57 01-AUG-07:10
September 0.328100E+09 351.87 21-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.359599E+09 548.83 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.387566E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.387212E+09 658.76 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.424775E+10     0.154036E+11    
Minimum of Months 0.316808E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.394283E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.600306E+09 1040.56 02-JAN-16:49 0.204757E+10 1435.24 02-JAN-08:09
February 0.522022E+09 970.10 06-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.590089E+09 758.74 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.512460E+09 584.95 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.539041E+09 496.34 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.530893E+09 496.34 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.499906E+09 496.34 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.566731E+09 538.71 28-AUG-15:00 0.212945E+10 1435.24 01-AUG-07:10
September 0.516886E+09 538.24 21-SEP-15:00 0.197632E+10 1435.24 01-SEP-07:10
October 0.563871E+09 872.67 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.594080E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.593969E+09 1040.56 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.663025E+10     0.243324E+11    
Minimum of Months 0.499906E+09 496.34   0.185364E+10 1435.24  
Maximum of Months 0.600306E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.384236E+09 658.71 02-JAN-16:49 0.129620E+10 908.57 02-JAN-08:09
February 0.331468E+09 612.93 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.372847E+09 493.55 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.322816E+09 438.10 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.339369E+09 314.21 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.333945E+09 334.46 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314566E+09 314.21 03-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.355875E+09 343.12 21-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.326701E+09 356.14 22-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.358190E+09 559.46 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.377694E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.379572E+09 658.71 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.419728E+10     0.154035E+11    
Minimum of Months 0.314566E+09 314.21   0.117344E+10 908.57  
Maximum of Months 0.384236E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.632432E+09 1040.56 02-JAN-16:49 0.204758E+10 1435.25 02-JAN-08:09
February 0.536536E+09 974.19 06-FEB-16:00 0.185366E+10 1435.25 01-FEB-08:09
March 0.594510E+09 777.76 21-MAR-07:10 0.212947E+10 1435.25 01-MAR-08:09
April 0.511746E+09 678.85 03-APR-07:10 0.197726E+10 1435.25 03-APR-07:10
May 0.536936E+09 496.34 01-MAY-07:10 0.208852E+10 1435.25 01-MAY-07:10
June 0.527790E+09 496.34 01-JUN-07:10 0.205071E+10 1435.25 01-JUN-07:10
July 0.497007E+09 496.34 03-JUL-07:10 0.201461E+10 1435.25 03-JUL-07:10
August 0.564921E+09 546.99 28-AUG-15:00 0.212947E+10 1435.25 01-AUG-07:10
September 0.518404E+09 552.39 21-SEP-15:00 0.197634E+10 1435.25 01-SEP-07:10
October 0.573173E+09 887.10 30-OCT-07:10 0.204804E+10 1435.25 02-OCT-07:10
November 0.618413E+09 1040.56 06-NOV-16:49 0.200273E+10 1435.25 01-NOV-07:10
December 0.619576E+09 1040.56 01-DEC-16:30 0.201415E+10 1435.25 01-DEC-08:09
             
Annual Sum or Average 0.673144E+10     0.243325E+11    
Minimum of Months 0.497007E+09 496.34   0.185366E+10 1435.25  
Maximum of Months 0.632432E+09 1040.56   0.212947E+10 1435.25  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.395215E+09 658.76 02-JAN-16:49 0.129621E+10 908.57 02-JAN-08:09
February 0.337498E+09 616.85 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.375865E+09 471.30 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.324744E+09 366.21 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.342216E+09 314.23 01-MAY-07:10 0.132213E+10 908.57 01-MAY-07:10
June 0.336681E+09 314.23 01-JUN-07:10 0.129819E+10 908.57 01-JUN-07:10
July 0.316981E+09 314.23 03-JUL-07:10 0.127534E+10 908.57 03-JUL-07:10
August 0.359535E+09 350.07 28-AUG-15:00 0.134804E+10 908.57 01-AUG-07:10
September 0.328456E+09 354.08 21-SEP-15:00 0.125111E+10 908.57 01-SEP-07:10
October 0.360181E+09 552.22 30-OCT-07:10 0.129650E+10 908.57 02-OCT-07:10
November 0.388641E+09 658.76 06-NOV-16:49 0.126781E+10 908.57 01-NOV-07:10
December 0.388271E+09 658.76 01-DEC-16:30 0.127504E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.425428E+10     0.154036E+11    
Minimum of Months 0.316981E+09 314.23   0.117344E+10 908.57  
Maximum of Months 0.395215E+09 658.76   0.134804E+10 908.57  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.600823E+09 1040.56 02-JAN-16:49 0.204757E+10 1435.24 02-JAN-08:09
February 0.522738E+09 972.68 06-FEB-16:00 0.185364E+10 1435.24 01-FEB-08:09
March 0.590523E+09 769.15 21-MAR-07:10 0.212945E+10 1435.24 01-MAR-08:09
April 0.512944E+09 673.25 03-APR-07:10 0.197725E+10 1435.24 03-APR-07:10
May 0.539455E+09 496.34 01-MAY-07:10 0.208851E+10 1435.24 01-MAY-07:10
June 0.531316E+09 496.34 01-JUN-07:10 0.205070E+10 1435.24 01-JUN-07:10
July 0.500274E+09 496.34 03-JUL-07:10 0.201460E+10 1435.24 03-JUL-07:10
August 0.567221E+09 543.36 28-AUG-15:00 0.212945E+10 1435.24 01-AUG-07:10
September 0.517322E+09 542.95 21-SEP-15:00 0.197632E+10 1435.24 01-SEP-07:10
October 0.564566E+09 878.90 30-OCT-07:10 0.204803E+10 1435.24 02-OCT-07:10
November 0.595171E+09 1040.56 06-NOV-16:49 0.200271E+10 1435.24 01-NOV-07:10
December 0.596135E+09 1040.56 01-DEC-16:30 0.201413E+10 1435.24 01-DEC-08:09
             
Annual Sum or Average 0.663849E+10     0.243324E+11    
Minimum of Months 0.500274E+09 496.34   0.185364E+10 1435.24  
Maximum of Months 0.600823E+09 1040.56   0.212945E+10 1435.24  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.384904E+09 658.71 02-JAN-16:49 0.129620E+10 908.57 02-JAN-08:09
February 0.332041E+09 614.32 06-FEB-16:00 0.117344E+10 908.57 01-FEB-08:09
March 0.373249E+09 498.42 21-MAR-07:10 0.134804E+10 908.57 01-MAR-08:09
April 0.323044E+09 444.59 03-APR-07:10 0.125169E+10 908.57 03-APR-07:10
May 0.339556E+09 314.21 01-MAY-07:10 0.132212E+10 908.57 01-MAY-07:10
June 0.334084E+09 337.35 16-JUN-07:10 0.129818E+10 908.57 01-JUN-07:10
July 0.314742E+09 334.17 28-JUL-07:10 0.127533E+10 908.57 03-JUL-07:10
August 0.356078E+09 345.27 21-AUG-07:10 0.134804E+10 908.57 01-AUG-07:10
September 0.327008E+09 357.99 22-SEP-07:10 0.125110E+10 908.57 01-SEP-07:10
October 0.358865E+09 562.40 30-OCT-07:10 0.129649E+10 908.57 02-OCT-07:10
November 0.379519E+09 658.71 06-NOV-16:49 0.126780E+10 908.57 01-NOV-07:10
December 0.380113E+09 658.71 01-DEC-16:30 0.127503E+10 908.57 01-DEC-08:09
             
Annual Sum or Average 0.420320E+10     0.154035E+11    
Minimum of Months 0.314742E+09 314.21   0.117344E+10 908.57  
Maximum of Months 0.384904E+09 658.71   0.134804E+10 908.57  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.210964E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.204846E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.214034E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.209475E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.209382E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.204802E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.210986E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.204961E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.209360E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.250423E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.191215E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.217104E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.471610E+10 0.463753E+10 0.971303E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453654E+10 0.446441E+10 0.937947E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.491426E+10 0.482138E+10 0.990724E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.490054E+10 0.480039E+10 0.972788E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.455026E+10 0.448540E+10 0.955663E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.511242E+10 0.500520E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.453654E+10 0.446441E+10 0.937507E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471610E+10 0.463757E+10 0.971523E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.467005E+10 0.458488E+10 0.950025E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.455026E+10 0.448544E+10 0.955443E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.565941E+11 0.555988E+11 0.115425E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.427861E+10 0.420695E+10 0.879311E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.511242E+10 0.500524E+10 0.101015E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.632433E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.240771E+09
February 0.901968E+09 0.536537E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.388594E+09
March 0.107774E+10 0.594511E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.421414E+09
April 0.956342E+09 0.511746E+09 0.197726E+10 0.00 0.00 0.00 0.00 0.00 0.450806E+09
May 0.103597E+10 0.536936E+09 0.208852E+10 0.00 0.00 0.00 0.00 992388.83 0.243012E+09
June 0.103308E+10 0.527790E+09 0.205071E+10 0.00 0.00 0.00 0.00 20755229.69 0.106798E+09
July 0.959235E+09 0.497008E+09 0.201461E+10 0.00 0.00 0.00 0.00 26125704.70 0.106234E+09
August 0.107774E+10 0.564921E+09 0.212947E+10 0.00 0.00 0.00 0.00 14149988.51 0.104778E+09
September 0.956342E+09 0.518404E+09 0.197634E+10 0.00 0.00 0.00 0.00 7565646.70 0.153324E+09
October 0.994195E+09 0.573174E+09 0.204804E+10 0.00 0.00 0.00 0.00 139095.76 0.324537E+09
November 0.984487E+09 0.618415E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.277190E+09
December 0.959235E+09 0.619577E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.520219E+09
                   
Annual Sum or Average 0.119305E+11 0.673145E+10 0.243325E+11 0.00 0.00 0.00 0.00 69728054.19 0.333768E+10
Minimum of Months 0.901968E+09 0.497008E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.104778E+09
Maximum of Months 0.107774E+10 0.632433E+09 0.212947E+10 0.00 0.00 0.00 0.00 26125704.70 0.520219E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.395215E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.165335E+09
February 0.571020E+09 0.337499E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.265848E+09
March 0.682301E+09 0.375865E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.289349E+09
April 0.605444E+09 0.324744E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.308139E+09
May 0.655854E+09 0.342216E+09 0.132213E+10 0.00 0.00 0.00 0.00 661329.98 0.165621E+09
June 0.654023E+09 0.336681E+09 0.129819E+10 0.00 0.00 0.00 0.00 13578346.33 72605712.72
July 0.607275E+09 0.316982E+09 0.127534E+10 0.00 0.00 0.00 0.00 17011466.09 73520645.81
August 0.682301E+09 0.359535E+09 0.134804E+10 0.00 0.00 0.00 0.00 9183104.16 72203163.07
September 0.605444E+09 0.328456E+09 0.125111E+10 0.00 0.00 0.00 0.00 4701140.27 0.106588E+09
October 0.629407E+09 0.360182E+09 0.129650E+10 0.00 0.00 0.00 0.00 92728.83 0.223880E+09
November 0.623262E+09 0.388642E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.188932E+09
December 0.607275E+09 0.388271E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.352587E+09
                   
Annual Sum or Average 0.755301E+10 0.425429E+10 0.154036E+11 0.00 0.00 0.00 0.00 45228115.66 0.228461E+10
Minimum of Months 0.571020E+09 0.316982E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 72203163.07
Maximum of Months 0.682301E+09 0.395215E+09 0.134804E+10 0.00 0.00 0.00 0.00 17011466.09 0.352587E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.600824E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.264976E+09
February 0.901968E+09 0.522739E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.413504E+09
March 0.107774E+10 0.590523E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.443446E+09
April 0.956342E+09 0.512944E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.00 0.461856E+09
May 0.103597E+10 0.539455E+09 0.208851E+10 0.00 0.00 0.00 0.00 991893.65 0.246656E+09
June 0.103308E+10 0.531316E+09 0.205070E+10 0.00 0.00 0.00 0.00 20587915.85 0.106472E+09
July 0.959235E+09 0.500275E+09 0.201460E+10 0.00 0.00 0.00 0.00 25856905.69 0.106743E+09
August 0.107774E+10 0.567221E+09 0.212945E+10 0.00 0.00 0.00 0.00 13738198.13 0.108802E+09
September 0.956342E+09 0.517323E+09 0.197632E+10 0.00 0.00 0.00 0.00 6784211.01 0.162594E+09
October 0.994195E+09 0.564566E+09 0.204803E+10 0.00 0.00 0.00 0.00 113870.91 0.344967E+09
November 0.984487E+09 0.595172E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.298811E+09
December 0.959235E+09 0.596135E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.554286E+09
                   
Annual Sum or Average 0.119305E+11 0.663849E+10 0.243324E+11 0.00 0.00 0.00 0.00 68072995.24 0.351311E+10
Minimum of Months 0.901968E+09 0.500275E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.106472E+09
Maximum of Months 0.107774E+10 0.600824E+09 0.212945E+10 0.00 0.00 0.00 0.00 25856905.69 0.554286E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.384905E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.165879E+09
February 0.570983E+09 0.332041E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.266375E+09
March 0.682256E+09 0.373250E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.289452E+09
April 0.605404E+09 0.323044E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.306538E+09
May 0.655811E+09 0.339556E+09 0.132212E+10 0.00 0.00 0.00 0.00 661113.84 0.167478E+09
June 0.653980E+09 0.334084E+09 0.129818E+10 0.00 0.00 0.00 0.00 13532393.94 74401692.29
July 0.607235E+09 0.314742E+09 0.127533E+10 0.00 0.00 0.00 0.00 16901333.63 73351480.10
August 0.682256E+09 0.356078E+09 0.134804E+10 0.00 0.00 0.00 0.00 9279373.05 74062228.91
September 0.605404E+09 0.327008E+09 0.125110E+10 0.00 0.00 0.00 0.00 4646666.85 0.107571E+09
October 0.629366E+09 0.358866E+09 0.129649E+10 0.00 0.00 0.00 0.00 92739.47 0.222724E+09
November 0.623221E+09 0.379519E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.189996E+09
December 0.607235E+09 0.380113E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.353509E+09
                   
Annual Sum or Average 0.755252E+10 0.420321E+10 0.154035E+11 0.00 0.00 0.00 0.00 45113620.78 0.229134E+10
Minimum of Months 0.570983E+09 0.314742E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 73351480.10
Maximum of Months 0.682256E+09 0.384905E+09 0.134804E+10 0.00 0.00 0.00 0.00 16901333.63 0.353509E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.630231E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.134767E+09
February 0.901968E+09 0.534669E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.212468E+09
March 0.107774E+10 0.593606E+09 0.212947E+10 0.00 0.00 0.00 0.00 2.02 0.230421E+09
April 0.956342E+09 0.511305E+09 0.197726E+10 0.00 0.00 0.00 0.00 0.00 0.248462E+09
May 0.103597E+10 0.536580E+09 0.208852E+10 0.00 0.00 0.00 0.00 545225.49 0.128817E+09
June 0.103308E+10 0.527501E+09 0.205071E+10 0.00 0.00 0.00 0.00 11862528.73 55523142.55
July 0.959235E+09 0.496642E+09 0.201461E+10 0.00 0.00 0.00 0.00 15512711.08 54906897.82
August 0.107774E+10 0.565059E+09 0.212947E+10 0.00 0.00 0.00 0.00 8045754.26 55894365.00
September 0.956342E+09 0.517762E+09 0.197634E+10 0.00 0.00 0.00 0.00 4360034.67 85974947.37
October 0.994195E+09 0.571603E+09 0.204804E+10 0.00 0.00 0.00 0.00 76838.67 0.187191E+09
November 0.984487E+09 0.616578E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.158589E+09
December 0.959235E+09 0.617828E+09 0.201415E+10 0.00 0.00 0.00 0.00 356.73 0.292127E+09
                   
Annual Sum or Average 0.119305E+11 0.671937E+10 0.243325E+11 0.00 0.00 0.00 0.00 40403451.66 0.184514E+10
Minimum of Months 0.901968E+09 0.496642E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 54906897.82
Maximum of Months 0.107774E+10 0.630231E+09 0.212947E+10 0.00 0.00 0.00 0.00 15512711.08 0.292127E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629407E+09 0.394283E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 94013914.54
February 0.571020E+09 0.336740E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.148105E+09
March 0.682301E+09 0.375234E+09 0.134804E+10 0.00 0.00 0.00 0.00 1.11 0.161632E+09
April 0.605444E+09 0.324507E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.174191E+09
May 0.655854E+09 0.341987E+09 0.132213E+10 0.00 0.00 0.00 0.00 360984.76 90479163.57
June 0.654023E+09 0.336478E+09 0.129819E+10 0.00 0.00 0.00 0.00 7416969.83 39654344.09
July 0.607275E+09 0.316808E+09 0.127534E+10 0.00 0.00 0.00 0.00 9354777.87 40113202.32
August 0.682301E+09 0.359231E+09 0.134804E+10 0.00 0.00 0.00 0.00 4960638.13 40654665.06
September 0.605444E+09 0.328100E+09 0.125111E+10 0.00 0.00 0.00 0.00 2553806.88 61765367.48
October 0.629407E+09 0.359599E+09 0.129650E+10 0.00 0.00 0.00 0.00 51223.99 0.131018E+09
November 0.623262E+09 0.387566E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.109709E+09
December 0.607275E+09 0.387212E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.200869E+09
                   
Annual Sum or Average 0.755301E+10 0.424775E+10 0.154036E+11 0.00 0.00 0.00 0.00 24698402.57 0.129221E+10
Minimum of Months 0.571020E+09 0.316808E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 39654344.09
Maximum of Months 0.682301E+09 0.394283E+09 0.134804E+10 0.00 0.00 0.00 0.00 9354777.87 0.200869E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.600306E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.427015E+10
February 0.901968E+09 0.522022E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.422876E+10
March 0.107774E+10 0.590089E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.368876E+10
April 0.956342E+09 0.512460E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.00 0.280844E+10
May 0.103597E+10 0.539041E+09 0.208851E+10 0.00 0.00 0.00 0.00 53528905.33 0.179929E+10
June 0.103308E+10 0.530893E+09 0.205070E+10 0.00 0.00 0.00 0.00 0.730933E+09 0.455570E+09
July 0.959235E+09 0.499906E+09 0.201460E+10 0.00 0.00 0.00 0.00 0.590462E+09 0.430582E+09
August 0.107774E+10 0.566731E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.641787E+09 0.627606E+09
September 0.956342E+09 0.516886E+09 0.197632E+10 0.00 0.00 0.00 0.00 0.272540E+09 0.977457E+09
October 0.994195E+09 0.563871E+09 0.204803E+10 0.00 0.00 0.00 0.00 3896896.95 0.331101E+10
November 0.984487E+09 0.594080E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.407938E+10
December 0.959235E+09 0.593969E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.476121E+10
                   
Annual Sum or Average 0.119305E+11 0.663025E+10 0.243324E+11 0.00 0.00 0.00 0.00 0.229315E+10 0.314382E+11
Minimum of Months 0.901968E+09 0.499906E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.430582E+09
Maximum of Months 0.107774E+10 0.600306E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.730933E+09 0.476121E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.384236E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 94351655.78
February 0.570983E+09 0.331468E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.148353E+09
March 0.682256E+09 0.372847E+09 0.134804E+10 0.00 0.00 0.00 0.00 1.38 0.161234E+09
April 0.605404E+09 0.322816E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.173073E+09
May 0.655811E+09 0.339369E+09 0.132212E+10 0.00 0.00 0.00 0.00 359963.02 91227363.74
June 0.653980E+09 0.333945E+09 0.129818E+10 0.00 0.00 0.00 0.00 7403937.85 40894538.59
July 0.607235E+09 0.314566E+09 0.127533E+10 0.00 0.00 0.00 0.00 9318256.52 39814256.56
August 0.682256E+09 0.355875E+09 0.134804E+10 0.00 0.00 0.00 0.00 5059476.51 41679109.07
September 0.605404E+09 0.326701E+09 0.125110E+10 0.00 0.00 0.00 0.00 2526627.93 62470343.02
October 0.629366E+09 0.358190E+09 0.129649E+10 0.00 0.00 0.00 0.00 51229.10 0.130914E+09
November 0.623221E+09 0.377694E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.110297E+09
December 0.607235E+09 0.379572E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.201199E+09
                   
Annual Sum or Average 0.755252E+10 0.419728E+10 0.154035E+11 0.00 0.00 0.00 0.00 24719492.32 0.129551E+10
Minimum of Months 0.570983E+09 0.314566E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 39814256.56
Maximum of Months 0.682256E+09 0.384236E+09 0.134804E+10 0.00 0.00 0.00 0.00 9318256.52 0.201199E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.632432E+09 0.204758E+10 0.00 0.00 0.00 0.00 0.00 0.214665E+09
February 0.901968E+09 0.536536E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 0.339163E+09
March 0.107774E+10 0.594510E+09 0.212947E+10 0.00 0.00 0.00 0.00 0.00 0.370463E+09
April 0.956342E+09 0.511746E+09 0.197726E+10 0.00 0.00 0.00 0.00 0.00 0.399678E+09
May 0.103597E+10 0.536936E+09 0.208852E+10 0.00 0.00 0.00 0.00 836522.22 0.211150E+09
June 0.103308E+10 0.527790E+09 0.205071E+10 0.00 0.00 0.00 0.00 17561750.85 91734327.67
July 0.959235E+09 0.497007E+09 0.201461E+10 0.00 0.00 0.00 0.00 22381178.31 91259027.84
August 0.107774E+10 0.564921E+09 0.212947E+10 0.00 0.00 0.00 0.00 12041715.17 90594139.49
September 0.956342E+09 0.518404E+09 0.197634E+10 0.00 0.00 0.00 0.00 6484376.99 0.134702E+09
October 0.994195E+09 0.573173E+09 0.204804E+10 0.00 0.00 0.00 0.00 118020.25 0.288940E+09
November 0.984487E+09 0.618413E+09 0.200273E+10 0.00 0.00 0.00 0.00 0.00 0.245825E+09
December 0.959235E+09 0.619576E+09 0.201415E+10 0.00 0.00 0.00 0.00 0.00 0.454095E+09
                   
Annual Sum or Average 0.119305E+11 0.673144E+10 0.243325E+11 0.00 0.00 0.00 0.00 59423563.78 0.293227E+10
Minimum of Months 0.901968E+09 0.497007E+09 0.185366E+10 0.00 0.00 0.00 0.00 0.00 90594139.49
Maximum of Months 0.107774E+10 0.632432E+09 0.212947E+10 0.00 0.00 0.00 0.00 22381178.31 0.454095E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.465148E+09 0.395215E+09 0.129621E+10 0.00 0.00 0.00 0.00 0.00 0.147424E+09
February 0.421807E+09 0.337498E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.232048E+09
March 0.502994E+09 0.375865E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.253631E+09
April 0.447140E+09 0.324744E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.272514E+09
May 0.484071E+09 0.342216E+09 0.132213E+10 0.00 0.00 0.00 0.00 522484.60 0.143701E+09
June 0.482240E+09 0.336681E+09 0.129819E+10 0.00 0.00 0.00 0.00 11233761.95 62406227.93
July 0.448971E+09 0.316981E+09 0.127534E+10 0.00 0.00 0.00 0.00 14186186.46 63097175.90
August 0.502994E+09 0.359535E+09 0.134804E+10 0.00 0.00 0.00 0.00 7534887.89 62405290.00
September 0.447140E+09 0.328456E+09 0.125111E+10 0.00 0.00 0.00 0.00 3860336.01 93132539.34
October 0.465148E+09 0.360181E+09 0.129650E+10 0.00 0.00 0.00 0.00 68683.86 0.198272E+09
November 0.460569E+09 0.388641E+09 0.126781E+10 0.00 0.00 0.00 0.00 0.00 0.167596E+09
December 0.448971E+09 0.388271E+09 0.127504E+10 0.00 0.00 0.00 0.00 0.00 0.308490E+09
                   
Annual Sum or Average 0.557719E+10 0.425428E+10 0.154036E+11 0.00 0.00 0.00 0.00 37406340.77 0.200472E+10
Minimum of Months 0.421807E+09 0.316981E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 62405290.00
Maximum of Months 0.502994E+09 0.395215E+09 0.134804E+10 0.00 0.00 0.00 0.00 14186186.46 0.308490E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.994195E+09 0.600823E+09 0.204757E+10 0.00 0.00 0.00 0.00 0.00 0.234515E+09
February 0.901968E+09 0.522738E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 0.360811E+09
March 0.107774E+10 0.590523E+09 0.212945E+10 0.00 0.00 0.00 0.00 0.00 0.388459E+09
April 0.956342E+09 0.512944E+09 0.197725E+10 0.00 0.00 0.00 0.00 0.00 0.408795E+09
May 0.103597E+10 0.539455E+09 0.208851E+10 0.00 0.00 0.00 0.00 835602.45 0.214039E+09
June 0.103308E+10 0.531316E+09 0.205070E+10 0.00 0.00 0.00 0.00 17321512.58 91586690.77
July 0.959235E+09 0.500274E+09 0.201460E+10 0.00 0.00 0.00 0.00 21959801.05 91874476.94
August 0.107774E+10 0.567221E+09 0.212945E+10 0.00 0.00 0.00 0.00 11546187.80 94037826.46
September 0.956342E+09 0.517322E+09 0.197632E+10 0.00 0.00 0.00 0.00 5705009.49 0.142076E+09
October 0.994195E+09 0.564566E+09 0.204803E+10 0.00 0.00 0.00 0.00 74566.37 0.304706E+09
November 0.984487E+09 0.595171E+09 0.200271E+10 0.00 0.00 0.00 0.00 0.00 0.263150E+09
December 0.959235E+09 0.596135E+09 0.201413E+10 0.00 0.00 0.00 0.00 0.00 0.485155E+09
                   
Annual Sum or Average 0.119305E+11 0.663849E+10 0.243324E+11 0.00 0.00 0.00 0.00 57442679.75 0.307921E+10
Minimum of Months 0.901968E+09 0.500274E+09 0.185364E+10 0.00 0.00 0.00 0.00 0.00 91586690.77
Maximum of Months 0.107774E+10 0.600823E+09 0.212945E+10 0.00 0.00 0.00 0.00 21959801.05 0.485155E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.629366E+09 0.384904E+09 0.129620E+10 0.00 0.00 0.00 0.00 0.00 0.147562E+09
February 0.570983E+09 0.332041E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 0.232352E+09
March 0.682256E+09 0.373249E+09 0.134804E+10 0.00 0.00 0.00 0.00 0.00 0.253812E+09
April 0.605404E+09 0.323044E+09 0.125169E+10 0.00 0.00 0.00 0.00 0.00 0.271435E+09
May 0.655811E+09 0.339556E+09 0.132212E+10 0.00 0.00 0.00 0.00 556840.48 0.145298E+09
June 0.653980E+09 0.334084E+09 0.129818E+10 0.00 0.00 0.00 0.00 11368358.49 64022099.42
July 0.607235E+09 0.314742E+09 0.127533E+10 0.00 0.00 0.00 0.00 14238091.22 63155551.58
August 0.682256E+09 0.356078E+09 0.134804E+10 0.00 0.00 0.00 0.00 7804542.51 63999860.63
September 0.605404E+09 0.327008E+09 0.125110E+10 0.00 0.00 0.00 0.00 3906630.98 94251226.45
October 0.629366E+09 0.358865E+09 0.129649E+10 0.00 0.00 0.00 0.00 78683.06 0.197522E+09
November 0.623221E+09 0.379519E+09 0.126780E+10 0.00 0.00 0.00 0.00 0.00 0.168087E+09
December 0.607235E+09 0.380113E+09 0.127503E+10 0.00 0.00 0.00 0.00 0.00 0.308722E+09
                   
Annual Sum or Average 0.755252E+10 0.420320E+10 0.154035E+11 0.00 0.00 0.00 0.00 37953146.74 0.201022E+10
Minimum of Months 0.570983E+09 0.314742E+09 0.117344E+10 0.00 0.00 0.00 0.00 0.00 63155551.58
Maximum of Months 0.682256E+09 0.384904E+09 0.134804E+10 0.00 0.00 0.00 0.00 14238091.22 0.308722E+09



Table of Contents

Report: SpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.305261E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.477494E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.522028E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.558290E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 765403.98 0.286179E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20050812.92 0.122811E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26673237.60 0.122143E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12822686.04 0.123706E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6517730.77 0.188964E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53837.38 0.409472E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.348731E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.642461E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66883708.68 0.410754E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122143E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26673237.60 0.642461E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.373954E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.591024E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.647835E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.692573E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 999839.89 0.361644E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25887075.02 0.157124E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34449550.33 0.156323E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16739263.67 0.156691E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8868676.69 0.236480E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79784.07 0.505322E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.427782E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.787375E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87024189.67 0.509413E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.156323E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34449550.33 0.787375E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.372086E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.596103E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.653496E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.696451E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 643126.07 0.376611E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22144611.93 0.159514E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27481001.84 0.160032E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14074184.61 0.159678E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6259966.06 0.235873E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21715.30 0.503586E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.426389E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.787294E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 70624605.81 0.512711E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.159514E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27481001.84 0.787294E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 14019.75 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 14019.75 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 14019.75 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 14019.75 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 14019.75 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 14019.75 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 14019.75 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 14019.75 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 14019.75 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 14019.75 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 14019.75 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 14019.75 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   14019.75   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6198.29 02-JAN-10:09 4936.01 02-JAN-08:09 6808.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 6198.29 01-FEB-10:09 4936.01 01-FEB-08:09 6808.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 6198.29 01-MAR-10:09 4936.01 01-MAR-08:09 6808.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 6198.29 03-APR-09:09 4936.01 03-APR-07:10 6808.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 6198.29 01-MAY-09:09 4936.01 01-MAY-07:10 6808.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 6198.29 01-JUN-09:09 4936.01 01-JUN-07:10 6808.32 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 6198.29 03-JUL-09:09 4936.01 03-JUL-07:10 6808.32 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 6198.29 01-AUG-09:09 4936.01 01-AUG-07:10 6808.32 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 6198.29 01-SEP-09:09 4936.01 01-SEP-07:10 6808.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 6198.29 02-OCT-09:09 4936.01 02-OCT-07:10 6808.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 6198.29 01-NOV-09:09 4936.01 01-NOV-07:10 6808.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 6198.29 01-DEC-10:09 4936.01 01-DEC-08:09 6808.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6198.29   4936.01   6808.32   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 458.53 13-JAN-05:00
February 1306.65 01-FEB-10:09 974.20 06-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 594.34 23-FEB-24:00
March 1306.65 01-MAR-10:09 777.79 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1296.76 19-MAR-07:00
April 1306.65 03-APR-09:09 678.88 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 828.41 15-APR-05:00
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 24.44 17-MAY-14:50 482.58 03-MAY-03:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 141.40 25-JUN-17:55 307.50 08-JUN-23:00
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 218.22 16-JUL-12:00 300.69 03-JUL-03:00
August 1306.65 01-AUG-09:09 547.00 28-AUG-15:00 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 77.14 02-AUG-16:00 396.84 27-AUG-18:00
September 1306.65 01-SEP-09:09 552.40 21-SEP-15:00 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 85.95 10-SEP-15:00 321.37 21-SEP-23:00
October 1306.65 02-OCT-09:09 887.12 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 11.28 11-OCT-14:00 704.33 29-OCT-09:00
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 719.71 01-NOV-04:10
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1070.43 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   300.69  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 218.22   1296.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 658.76 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 306.18 13-JAN-05:00
February 827.22 01-FEB-10:09 616.86 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 402.00 23-FEB-24:00
March 827.22 01-MAR-10:09 471.32 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 864.54 19-MAR-07:00
April 827.22 03-APR-09:09 366.22 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 550.97 15-APR-05:00
May 827.22 01-MAY-09:09 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 16.29 17-MAY-14:50 322.35 03-MAY-03:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 94.95 25-JUN-17:55 205.12 08-JUN-23:00
July 827.22 03-JUL-09:09 314.23 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 145.48 16-JUL-12:00 215.22 02-JUL-08:50
August 827.22 01-AUG-09:09 350.07 28-AUG-15:00 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 51.42 02-AUG-16:00 271.24 27-AUG-18:00
September 827.22 01-SEP-09:09 354.08 21-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 58.16 10-SEP-14:45 214.56 21-SEP-23:00
October 827.22 02-OCT-09:09 552.23 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 7.52 11-OCT-14:00 472.44 29-OCT-09:00
November 827.22 01-NOV-09:09 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 479.81 01-NOV-04:10
December 827.22 01-DEC-10:09 658.76 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 710.67 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   205.12  
Maximum of Months 827.22   658.76   908.57   0.00 0.00 0.00 0.00 145.48   864.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 476.71 13-JAN-05:00
February 1306.65 01-FEB-10:09 972.69 06-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 631.92 19-FEB-17:00
March 1306.65 01-MAR-10:09 769.18 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1296.75 19-MAR-07:00
April 1306.65 03-APR-09:09 673.29 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 832.91 15-APR-05:00
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 24.44 17-MAY-14:50 488.58 03-MAY-03:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 142.66 25-JUN-17:55 306.35 08-JUN-23:00
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 218.22 16-JUL-12:00 301.40 03-JUL-03:00
August 1306.65 01-AUG-09:09 543.37 28-AUG-15:00 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 77.14 02-AUG-16:00 427.59 27-AUG-18:00
September 1306.65 01-SEP-09:09 542.97 21-SEP-15:00 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 81.62 10-SEP-15:00 324.16 21-SEP-23:00
October 1306.65 02-OCT-09:09 878.91 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 9.36 11-OCT-14:00 722.08 29-OCT-09:00
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 720.99 01-NOV-04:05
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1089.39 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.24   0.00 0.00 0.00 0.00 0.00   301.40  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 218.22   1296.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 308.66 13-JAN-05:00
February 827.17 01-FEB-10:09 614.32 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 407.82 23-FEB-24:00
March 827.17 01-MAR-10:09 498.44 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 864.56 19-MAR-07:00
April 827.17 03-APR-09:09 444.61 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 549.47 15-APR-05:00
May 827.17 01-MAY-09:09 314.21 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 16.29 17-MAY-14:50 328.58 03-MAY-03:00
June 827.17 01-JUN-09:09 337.36 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 87.63 25-JUN-18:00 216.88 08-JUN-23:00
July 827.17 03-JUL-09:09 334.18 28-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 145.48 16-JUL-12:00 206.98 03-JUL-03:00
August 827.17 01-AUG-09:09 345.27 21-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 51.42 02-AUG-16:00 288.56 27-AUG-18:00
September 827.17 01-SEP-09:09 357.99 22-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 54.41 10-SEP-15:00 213.23 21-SEP-23:00
October 827.17 02-OCT-09:09 562.41 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 7.52 11-OCT-14:00 469.02 29-OCT-09:00
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 479.80 01-NOV-04:08
December 827.17 01-DEC-10:09 658.71 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 716.56 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   314.21   908.57   0.00 0.00 0.00 0.00 0.00   206.98  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 145.48   864.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 268.45 13-JAN-05:00
February 1306.65 01-FEB-10:09 971.69 06-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 323.72 23-FEB-24:00
March 1306.65 01-MAR-10:09 767.76 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 14-MAR-13:00 718.32 19-MAR-07:00
April 1306.65 03-APR-09:09 585.81 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 479.31 15-APR-05:00
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 13.20 17-MAY-14:50 270.93 03-MAY-03:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 73.88 25-JUN-17:50 164.81 08-JUN-23:00
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 121.50 16-JUL-12:00 159.21 03-JUL-03:00
August 1306.65 01-AUG-09:09 542.56 28-AUG-15:00 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 41.32 02-AUG-16:00 198.11 27-AUG-18:00
September 1306.65 01-SEP-09:09 548.23 21-SEP-15:00 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 48.23 10-SEP-15:00 188.88 22-SEP-02:00
October 1306.65 02-OCT-09:09 881.29 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 6.10 11-OCT-14:00 427.77 29-OCT-09:00
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 405.37 01-NOV-04:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.43 02-DEC-15:00 599.79 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   159.21  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 121.50   718.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.22 02-JAN-10:09 658.76 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 184.19 13-JAN-05:00
February 827.22 01-FEB-10:09 615.58 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 228.27 23-FEB-24:00
March 827.22 01-MAR-10:09 465.28 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 14-MAR-13:00 478.35 19-MAR-07:00
April 827.22 03-APR-09:09 364.40 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 325.69 15-APR-05:00
May 827.22 01-MAY-09:09 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 8.80 17-MAY-14:50 185.44 03-MAY-03:00
June 827.22 01-JUN-09:09 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 49.81 25-JUN-17:43 114.96 08-JUN-23:00
July 827.22 03-JUL-09:09 314.23 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 77.78 16-JUL-12:00 112.95 03-JUL-03:00
August 827.22 01-AUG-09:09 347.68 28-AUG-15:00 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 27.54 02-AUG-16:00 143.20 27-AUG-18:00
September 827.22 01-SEP-09:09 351.87 21-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 30.53 10-SEP-14:34 127.36 22-SEP-02:00
October 827.22 02-OCT-09:09 548.83 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.07 11-OCT-14:00 292.95 29-OCT-09:00
November 827.22 01-NOV-09:09 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 268.90 01-NOV-04:00
December 827.22 01-DEC-10:09 658.76 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 398.36 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.22   314.23   908.57   0.00 0.00 0.00 0.00 0.00   112.95  
Maximum of Months 827.22   658.76   908.57   0.00 0.00 0.00 0.00 77.78   478.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 27156.67 05-JAN-17:01
February 1306.65 01-FEB-10:09 970.10 06-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 21398.23 02-FEB-07:01
March 1306.65 01-MAR-10:09 758.74 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 20637.14 02-MAR-07:01
April 1306.65 03-APR-09:09 584.95 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 19964.16 17-APR-06:01
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 2542.67 31-MAY-16:10 13762.70 02-MAY-06:02
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 8937.78 26-JUN-16:03 8675.27 09-JUN-06:02
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 6919.36 17-JUL-11:03 8345.01 03-JUL-06:01
August 1306.65 01-AUG-09:09 538.71 28-AUG-15:00 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 7847.06 16-AUG-16:03 7519.59 17-AUG-06:02
September 1306.65 01-SEP-09:09 538.24 21-SEP-15:00 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 4228.47 12-SEP-16:05 15973.25 21-SEP-16:01
October 1306.65 02-OCT-09:09 872.67 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 662.46 10-OCT-16:50 21768.33 30-OCT-06:01
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 23426.88 29-NOV-17:01
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 31428.42 21-DEC-17:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.24   0.00 0.00 0.00 0.00 0.00   7519.59  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 8937.78   31428.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 185.30 13-JAN-05:00
February 827.17 01-FEB-10:09 612.93 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 228.82 23-FEB-24:00
March 827.17 01-MAR-10:09 493.55 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 14-MAR-13:00 477.15 19-MAR-07:00
April 827.17 03-APR-09:09 438.10 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 320.63 15-APR-05:00
May 827.17 01-MAY-09:09 314.21 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 8.80 17-MAY-14:50 189.69 03-MAY-03:00
June 827.17 01-JUN-09:09 334.46 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 47.25 25-JUN-17:43 120.79 08-JUN-23:00
July 827.17 03-JUL-09:09 314.21 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 79.63 16-JUL-12:00 116.90 03-JUL-03:00
August 827.17 01-AUG-09:09 343.12 21-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 27.54 02-AUG-16:00 156.18 27-AUG-18:00
September 827.17 01-SEP-09:09 356.14 22-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 29.24 10-SEP-15:00 126.22 22-SEP-02:00
October 827.17 02-OCT-09:09 559.46 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 4.07 11-OCT-14:00 289.23 29-OCT-09:00
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 268.49 01-NOV-04:00
December 827.17 01-DEC-10:09 658.71 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 401.42 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   314.21   908.57   0.00 0.00 0.00 0.00 0.00   116.90  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 79.63   477.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.25 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 424.65 13-JAN-05:00
February 1306.65 01-FEB-10:09 974.19 06-FEB-16:00 1435.25 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 526.27 23-FEB-24:00
March 1306.65 01-MAR-10:09 777.76 21-MAR-07:10 1435.25 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1093.72 19-MAR-07:00
April 1306.65 03-APR-09:09 678.85 03-APR-07:10 1435.25 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 748.88 15-APR-05:00
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.25 01-MAY-07:10 0.00 0.00 0.00 0.00 20.50 17-MAY-14:50 435.05 03-MAY-03:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.25 01-JUN-07:10 0.00 0.00 0.00 0.00 110.77 25-JUN-17:43 263.39 08-JUN-23:00
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.25 03-JUL-07:10 0.00 0.00 0.00 0.00 182.16 16-JUL-12:00 258.22 03-JUL-03:00
August 1306.65 01-AUG-09:09 546.99 28-AUG-15:00 1435.25 01-AUG-07:10 0.00 0.00 0.00 0.00 64.45 02-AUG-16:00 328.20 27-AUG-18:00
September 1306.65 01-SEP-09:09 552.39 21-SEP-15:00 1435.25 01-SEP-07:10 0.00 0.00 0.00 0.00 70.29 10-SEP-14:40 286.37 22-SEP-02:00
October 1306.65 02-OCT-09:09 887.10 30-OCT-07:10 1435.25 02-OCT-07:10 0.00 0.00 0.00 0.00 9.47 11-OCT-14:00 646.80 29-OCT-09:00
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.25 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 603.42 01-NOV-04:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.25 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 926.43 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.25   0.00 0.00 0.00 0.00 0.00   258.22  
Maximum of Months 1306.65   1040.56   1435.25   0.00 0.00 0.00 0.00 182.16   1093.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 805.43 02-JAN-08:09 658.76 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 283.89 13-JAN-05:00
February 805.43 01-FEB-08:09 616.85 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 355.87 23-FEB-24:00
March 805.43 01-MAR-08:09 471.30 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 725.55 19-MAR-07:00
April 805.43 03-APR-07:10 366.21 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 499.50 16-APR-15:00
May 805.43 01-MAY-07:10 314.23 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 13.67 17-MAY-14:50 290.31 03-MAY-03:00
June 805.43 01-JUN-07:10 314.23 01-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 78.21 25-JUN-17:43 175.98 08-JUN-23:00
July 805.43 03-JUL-07:10 314.23 03-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 121.44 16-JUL-12:00 175.14 02-JUL-08:30
August 805.43 01-AUG-07:10 350.07 28-AUG-15:00 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 42.97 02-AUG-16:00 225.08 27-AUG-18:00
September 805.43 01-SEP-07:10 354.08 21-SEP-15:00 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 47.72 10-SEP-14:34 190.75 22-SEP-02:00
October 805.43 02-OCT-07:10 552.22 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 6.19 11-OCT-14:10 433.42 29-OCT-09:00
November 805.43 01-NOV-07:10 658.76 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 402.36 01-NOV-04:02
December 805.43 01-DEC-08:09 658.76 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 613.41 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 805.43   314.23   908.57   0.00 0.00 0.00 0.00 0.00   175.14  
Maximum of Months 805.43   658.76   908.57   0.00 0.00 0.00 0.00 121.44   725.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1306.65 02-JAN-10:09 1040.56 02-JAN-16:49 1435.24 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 440.25 13-JAN-05:00
February 1306.65 01-FEB-10:09 972.68 06-FEB-16:00 1435.24 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 554.12 23-FEB-24:00
March 1306.65 01-MAR-10:09 769.15 21-MAR-07:10 1435.24 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1096.93 19-MAR-07:00
April 1306.65 03-APR-09:09 673.25 03-APR-07:10 1435.24 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 752.79 15-APR-05:00
May 1306.65 01-MAY-09:09 496.34 01-MAY-07:10 1435.24 01-MAY-07:10 0.00 0.00 0.00 0.00 20.50 17-MAY-14:50 439.48 03-MAY-03:00
June 1306.65 01-JUN-09:09 496.34 01-JUN-07:10 1435.24 01-JUN-07:10 0.00 0.00 0.00 0.00 117.30 25-JUN-17:43 262.56 08-JUN-23:00
July 1306.65 03-JUL-09:09 496.34 03-JUL-07:10 1435.24 03-JUL-07:10 0.00 0.00 0.00 0.00 182.16 16-JUL-12:00 258.99 03-JUL-03:00
August 1306.65 01-AUG-09:09 543.36 28-AUG-15:00 1435.24 01-AUG-07:10 0.00 0.00 0.00 0.00 64.45 02-AUG-16:00 355.19 27-AUG-18:00
September 1306.65 01-SEP-09:09 542.95 21-SEP-15:00 1435.24 01-SEP-07:10 0.00 0.00 0.00 0.00 68.42 10-SEP-14:34 287.72 22-SEP-02:00
October 1306.65 02-OCT-09:09 878.90 30-OCT-07:10 1435.24 02-OCT-07:10 0.00 0.00 0.00 0.00 6.73 11-OCT-14:00 660.70 29-OCT-09:00
November 1306.65 01-NOV-09:09 1040.56 06-NOV-16:49 1435.24 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 605.27 01-NOV-04:00
December 1306.65 01-DEC-10:09 1040.56 01-DEC-16:30 1435.24 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 940.87 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1306.65   496.34   1435.24   0.00 0.00 0.00 0.00 0.00   258.99  
Maximum of Months 1306.65   1040.56   1435.24   0.00 0.00 0.00 0.00 182.16   1096.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 827.17 02-JAN-10:09 658.71 02-JAN-16:49 908.57 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 285.57 13-JAN-05:00
February 827.17 01-FEB-10:09 614.32 06-FEB-16:00 908.57 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 360.70 23-FEB-24:00
March 827.17 01-MAR-10:09 498.42 21-MAR-07:10 908.57 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 723.95 19-MAR-07:00
April 827.17 03-APR-09:09 444.59 03-APR-07:10 908.57 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 496.87 15-APR-05:00
May 827.17 01-MAY-09:09 314.21 01-MAY-07:10 908.57 01-MAY-07:10 0.00 0.00 0.00 0.00 13.67 17-MAY-14:50 295.33 03-MAY-03:00
June 827.17 01-JUN-09:09 337.35 16-JUN-07:10 908.57 01-JUN-07:10 0.00 0.00 0.00 0.00 73.93 25-JUN-17:43 185.34 08-JUN-23:00
July 827.17 03-JUL-09:09 334.17 28-JUL-07:10 908.57 03-JUL-07:10 0.00 0.00 0.00 0.00 121.44 16-JUL-12:00 178.03 03-JUL-03:00
August 827.17 01-AUG-09:09 345.27 21-AUG-07:10 908.57 01-AUG-07:10 0.00 0.00 0.00 0.00 42.96 02-AUG-16:00 239.49 27-AUG-18:00
September 827.17 01-SEP-09:09 357.99 22-SEP-07:10 908.57 01-SEP-07:10 0.00 0.00 0.00 0.00 45.53 10-SEP-15:00 189.65 22-SEP-02:00
October 827.17 02-OCT-09:09 562.40 30-OCT-07:10 908.57 02-OCT-07:10 0.00 0.00 0.00 0.00 6.32 11-OCT-14:00 430.51 29-OCT-09:00
November 827.17 01-NOV-09:09 658.71 06-NOV-16:49 908.57 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 402.54 01-NOV-04:02
December 827.17 01-DEC-10:09 658.71 01-DEC-16:30 908.57 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 618.51 21-DEC-22:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 827.17   314.21   908.57   0.00 0.00 0.00 0.00 0.00   178.03  
Maximum of Months 827.17   658.71   908.57   0.00 0.00 0.00 0.00 121.44   723.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 619.71 13-JAN-05:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 744.32 23-FEB-24:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1583.15 19-MAR-07:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1067.53 15-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.84 17-MAY-14:40 614.90 03-MAY-03:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.65 25-JUN-18:00 350.19 08-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 235.65 16-JUL-12:00 346.27 03-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.22 06-AUG-12:00 425.11 27-AUG-18:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.67 10-SEP-15:00 402.03 22-SEP-02:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.76 11-OCT-14:00 926.80 29-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 884.08 01-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1277.51 21-DEC-22:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   346.27  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 235.65   1583.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 764.13 13-JAN-05:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 935.90 23-FEB-24:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1943.79 19-MAR-07:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1336.71 15-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.99 17-MAY-14:40 769.58 03-MAY-03:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 177.04 25-JUN-18:00 447.39 08-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 305.97 16-JUL-12:00 445.89 03-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.30 06-AUG-12:00 537.45 27-AUG-18:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 118.10 10-SEP-15:00 506.51 22-SEP-02:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.49 11-OCT-14:00 1126.79 29-OCT-09:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1063.03 01-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1604.02 21-DEC-22:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   445.89  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 305.97   1943.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 698.28 31-JAN-02:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 951.58 19-FEB-17:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1938.25 19-MAR-07:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1262.03 15-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.92 17-MAY-13:00 712.60 03-MAY-03:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.93 25-JUN-17:40 448.42 08-JUN-23:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.89 16-JUL-12:00 442.33 03-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 92.67 02-AUG-16:00 630.68 27-AUG-18:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.43 10-SEP-14:30 483.31 21-SEP-23:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.74 11-OCT-14:00 1080.36 29-OCT-13:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 985.82 01-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1644.23 21-DEC-22:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   442.33  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 271.89   1938.25  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 27364.98 26-JAN-07:02 7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
February 32731.82 28-FEB-07:02 7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
March 34880.14 15-MAR-06:02 7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
April 31768.03 10-APR-06:03 5082.11 6581.44 40779.39 0.00 0.00 0.00 0.00 0.00 0.00
May 37275.53 30-MAY-05:12 2541.06 2193.73 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
June 38307.10 05-JUN-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
July 38852.05 31-JUL-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
August 38428.14 08-AUG-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
September 38612.36 06-SEP-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
October 38297.41 10-OCT-05:12 3176.32 2742.16 37051.74 0.00 0.00 0.00 0.00 0.00 0.00
November 34862.68 09-NOV-07:01 8893.70 11517.52 71363.93 0.00 0.00 0.00 0.00 0.00 0.00
December 23827.21 05-DEC-07:02 7623.17 9872.16 61169.09 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 23827.21   2541.06 2193.73 29641.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38852.05   8893.70 11517.52 71363.93 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3393.84 20-JAN-15:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.40
February 3189.40 18-FEB-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.59
March 7329.47 14-MAR-14:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.39
April 6498.89 21-APR-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.30
May 9058.25 31-MAY-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.03 0.00
June 12292.68 26-JUN-13:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.39 0.00
July 10774.17 17-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.49 0.00
August 12139.09 16-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.90 0.00
September 9195.96 12-SEP-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.17 0.00
October 7200.48 11-OCT-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.15
November 4456.19 09-NOV-13:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.24
December 2020.19 01-DEC-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.51
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2020.19   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12292.68   0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.49 66.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2913.63 05-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 204.47
February 2222.57 10-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 135.75
March 2875.90 15-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.16
April 2424.78 15-APR-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 189.95
May 2911.54 18-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.90
June 5647.50 26-JUN-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.72 0.00
July 5946.06 17-JUL-10:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.51 0.00
August 5172.52 21-AUG-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.60 0.00
September 5060.83 05-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.94
October 3469.84 10-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.21 0.00
November 2458.96 30-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 595.06
December 3259.89 20-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 752.35
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2222.57   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5946.06   0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.72 752.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2673.50 06-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 299.45
February 2577.82 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.14
March 3211.52 15-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.09
April 2364.49 03-APR-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.74
May 3211.11 16-MAY-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.76 0.00
June 6484.05 26-JUN-12:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.85 0.00
July 6492.93 17-JUL-12:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.24 0.00
August 5377.69 21-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.99 0.00
September 5587.41 05-SEP-06:07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.17
October 4007.94 10-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08
November 2373.36 07-NOV-16:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.25
December 3156.47 21-DEC-17:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.25
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2364.49   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6492.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 27.24 299.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 10551.32 25-JAN-16:20 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 10476.94 27-FEB-16:30 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 14408.88 15-MAR-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 13051.08 21-APR-14:00 6198.29 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 18509.84 22-MAY-06:02 6352.64 8226.80 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
June 29887.54 05-JUN-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 30750.65 03-JUL-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 30742.02 07-AUG-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 31454.59 05-SEP-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 27592.54 10-OCT-06:01 10164.22 13162.88 24207.36 0.00 0.00 0.00 0.00 0.00 0.00
November 12727.26 08-NOV-16:20 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 8684.30 15-DEC-16:00 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 8684.30   3176.32 2742.16 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31454.59   10164.22 13162.88 24207.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 9600.40 20-JAN-16:30 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
February 9284.24 27-FEB-16:20 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
March 15390.49 15-MAR-15:20 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
April 14401.11 21-APR-14:00 6198.29 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
May 16413.68 31-MAY-15:50 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
June 32013.61 19-JUN-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
July 32509.28 24-JUL-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
August 32340.89 21-AUG-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
September 32429.63 05-SEP-05:12 3176.32 2742.16 15129.60 0.00 0.00 0.00 0.00 0.00 0.00
October 16211.72 11-OCT-15:30 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
November 11914.00 07-NOV-16:10 6035.01 4936.01 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
December 7576.49 23-DEC-17:03 2223.42 1919.51 15886.08 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 7576.49   2223.42 1919.51 6808.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32509.28   6198.29 4936.01 15886.08 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1442.12 20-JAN-14:40 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 6.47
February 1297.21 26-FEB-14:22 334.80 137.87 2392.08 0.00 0.00 0.00 0.00 0.00 99.68
March 3779.20 14-MAR-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 3.18
April 3836.61 20-APR-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 5.60
May 5765.70 17-MAY-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 19.92 0.00
June 11404.20 25-JUN-17:11 0.00 193.02 2702.72 0.00 0.00 0.00 0.00 113.40 0.00
July 11498.50 16-JUL-14:22 334.80 137.87 2392.08 0.00 0.00 0.00 0.00 179.59 0.00
August 8375.56 20-AUG-15:41 468.72 193.02 3348.91 0.00 0.00 0.00 0.00 12.20 0.00
September 7566.23 10-SEP-16:01 468.72 193.02 3348.91 0.00 0.00 0.00 0.00 36.72 0.00
October 4161.02 11-OCT-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 10.51 0.00
November 2459.46 09-NOV-13:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.85
December 1495.37 23-DEC-17:03 468.72 404.65 3348.91 0.00 0.00 0.00 0.00 0.00 55.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1297.21   0.00 137.87 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11498.50   1306.65 496.34 3348.91 0.00 0.00 0.00 0.00 179.59 99.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2776.02 20-JAN-09:50 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 22.46
February 4048.38 27-FEB-09:20 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 35.29
March 8543.90 12-MAR-10:02 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 205.14
April 7394.41 21-APR-08:50 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 30.07
May 8067.57 16-MAY-08:40 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 3.44
June 11594.38 11-JUN-09:02 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 57.20
July 13978.93 16-JUL-09:02 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 47.47 0.00
August 14054.88 06-AUG-09:12 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 0.00 10.92
September 11829.78 04-SEP-09:22 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 11.22
October 9448.60 01-OCT-09:02 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 190.26
November 3850.06 07-NOV-09:10 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 17.19
December 1136.28 14-DEC-09:45 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 52.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1136.28   169.56 69.83 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14054.88   1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 47.47 205.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16158.91 22-JAN-12:23 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 319.83
February 17859.15 26-FEB-13:01 468.72 193.02 3348.89 0.00 0.00 0.00 0.00 0.00 190.55
March 17860.58 12-MAR-12:41 468.72 193.02 3348.89 0.00 0.00 0.00 0.00 0.00 293.24
April 9653.15 21-APR-13:05 2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 0.00 35.17
May 8484.33 16-MAY-13:10 2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 12.91 0.00
June 15460.26 25-JUN-14:32 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 35.82 0.00
July 15831.81 23-JUL-13:32 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 90.76 0.00
August 16069.87 06-AUG-12:32 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 42.56 0.00
September 17002.18 04-SEP-13:22 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 20.53 0.00
October 17228.39 09-OCT-13:32 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 38.49
November 16949.04 05-NOV-13:12 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 0.00 15.41
December 16122.71 03-DEC-13:12 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 177.61
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8484.33   267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17860.58   2613.31 992.69 3348.89 0.00 0.00 0.00 0.00 90.76 319.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5127.11 20-JAN-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 5.74
February 5518.82 17-FEB-16:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 19.17
March 16113.39 12-MAR-16:02 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 86.88
April 11657.96 08-APR-17:05 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 122.95
May 9842.53 28-MAY-14:53 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 0.00 57.15
June 16680.74 11-JUN-16:21 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 1.24 0.00
July 16599.48 02-JUL-16:51 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 4.17
August 16212.64 13-AUG-16:32 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 32.72
September 16445.81 10-SEP-16:01 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 18.54 0.00
October 12865.78 09-OCT-14:52 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 34.82
November 6293.43 07-NOV-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 3.77
December 3833.71 01-DEC-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 7.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3833.71   169.55 69.82 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16680.74   805.38 314.21 2119.99 0.00 0.00 0.00 0.00 18.54 122.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1310.57 20-JAN-14:50 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.72
February 1212.02 27-FEB-13:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 48.75
March 1867.19 14-MAR-15:00 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 1.16
April 1760.50 20-APR-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.92
May 3964.24 17-MAY-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 10.70 0.00
June 8755.41 25-JUN-18:21 0.00 220.59 3088.82 0.00 0.00 0.00 0.00 47.03 0.00
July 7260.40 17-JUL-06:03 803.52 496.35 1913.66 0.00 0.00 0.00 0.00 0.00 3.24
August 5481.22 21-AUG-14:00 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 10.18 0.00
September 6433.77 05-SEP-06:02 1607.03 1608.45 3827.32 0.00 0.00 0.00 0.00 0.00 19.46
October 3512.06 11-OCT-14:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 5.70 0.00
November 2104.47 09-NOV-13:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 1.35
December 1440.44 23-DEC-17:01 468.72 404.65 3348.91 0.00 0.00 0.00 0.00 0.00 30.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1212.02   0.00 220.59 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8755.41   1607.03 1608.45 3827.32 0.00 0.00 0.00 0.00 47.03 48.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1915.23 20-JAN-09:50 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 11.88
February 3352.79 27-FEB-08:35 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 16.68
March 4807.91 15-MAR-09:10 1654.44 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 5.77
April 5123.40 21-APR-09:00 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 15.09
May 7636.08 16-MAY-06:02 847.82 523.72 2019.05 0.00 0.00 0.00 0.00 0.00 12.45
June 11418.37 11-JUN-08:51 296.74 122.20 2120.00 0.00 0.00 0.00 0.00 0.00 32.30
July 11036.34 16-JUL-09:02 254.35 104.74 1817.15 0.00 0.00 0.00 0.00 27.39 0.00
August 11352.03 06-AUG-09:31 339.13 139.65 2422.86 0.00 0.00 0.00 0.00 0.00 3.87
September 10996.62 04-SEP-09:11 296.74 122.20 2120.00 0.00 0.00 0.00 0.00 0.00 7.19
October 8032.22 09-OCT-10:02 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 13.88
November 3639.67 07-NOV-08:25 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 10.66
December 1601.91 18-DEC-08:30 2416.29 942.68 2725.72 0.00 0.00 0.00 0.00 0.00 27.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1601.91   211.95 87.28 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11418.37   2416.29 942.68 2725.72 0.00 0.00 0.00 0.00 27.39 32.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12636.86 22-JAN-15:13 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 161.32
February 11925.64 26-FEB-13:23 267.84 110.30 1913.65 0.00 0.00 0.00 0.00 0.00 91.73
March 12760.14 12-MAR-13:11 468.72 193.02 3348.89 0.00 0.00 0.00 0.00 0.00 152.30
April 6802.09 21-APR-12:07 3816.70 1489.03 4305.71 0.00 0.00 0.00 0.00 0.00 862.80
May 7006.36 16-MAY-12:00 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 1991.43 0.00
June 12234.95 25-JUN-16:21 669.60 275.74 4784.12 0.00 0.00 0.00 0.00 46.24 0.00
July 11355.77 17-JUL-12:00 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 6837.24 0.00
August 11585.15 16-AUG-12:00 687.71 496.34 1275.77 0.00 0.00 0.00 0.00 6008.13 0.00
September 13744.45 10-SEP-11:51 468.72 193.02 3348.89 0.00 0.00 0.00 0.00 4.79 0.00
October 14747.66 09-OCT-13:21 535.68 220.59 3827.30 0.00 0.00 0.00 0.00 0.00 23.76
November 14286.67 05-NOV-13:01 535.68 220.59 3827.30 0.00 0.00 0.00 0.00 0.00 8.25
December 12821.27 17-DEC-13:52 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 85.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6802.09   267.84 110.30 1275.77 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14747.66   3816.70 1489.03 4784.12 0.00 0.00 0.00 0.00 6837.24 862.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3913.83 23-JAN-16:10 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 4.61
February 4116.84 17-FEB-16:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 10.14
March 8236.53 12-MAR-16:32 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 53.56
April 7958.96 08-APR-17:05 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 64.60
May 6271.58 31-MAY-16:00 805.38 314.21 908.57 0.00 0.00 0.00 0.00 5.47 0.00
June 13511.30 25-JUN-16:21 423.88 174.55 3028.56 0.00 0.00 0.00 0.00 19.55 0.00
July 12589.19 02-JUL-17:11 0.00 122.19 1710.93 0.00 0.00 0.00 0.00 8.56 0.00
August 13460.26 13-AUG-17:01 0.00 157.10 2199.77 0.00 0.00 0.00 0.00 0.00 18.75
September 13742.44 10-SEP-17:11 0.00 157.10 2199.77 0.00 0.00 0.00 0.00 4.49 0.00
October 12986.56 08-OCT-16:11 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 63.37
November 5571.30 07-NOV-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 1.96
December 3239.46 04-DEC-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 12.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3239.46   0.00 104.73 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13742.44   805.38 314.21 3028.56 0.00 0.00 0.00 0.00 19.55 64.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1460.86 20-JAN-15:10 2544.47 1069.98 2870.49 0.00 0.00 0.00 0.00 0.00 7.03
February 1475.51 27-FEB-15:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 71.99
March 3635.02 14-MAR-14:40 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.34
April 3520.65 20-APR-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 4.61
May 5444.36 17-MAY-13:30 1306.65 496.34 1435.25 0.00 0.00 0.00 0.00 16.67 0.00
June 9960.29 25-JUN-17:01 0.00 275.74 3861.03 0.00 0.00 0.00 0.00 82.59 0.00
July 9807.52 16-JUL-12:12 334.80 137.87 2392.08 0.00 0.00 0.00 0.00 146.12 0.00
August 7236.54 21-AUG-06:03 803.52 496.35 1913.66 0.00 0.00 0.00 0.00 0.00 12.47
September 7534.24 11-SEP-06:03 1071.35 934.12 2551.55 0.00 0.00 0.00 0.00 0.00 11.55
October 4109.52 10-OCT-15:20 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 1.87 0.00
November 2670.47 09-NOV-13:30 1272.23 496.34 1435.25 0.00 0.00 0.00 0.00 0.00 2.12
December 1419.16 23-DEC-17:01 468.72 404.65 3348.91 0.00 0.00 0.00 0.00 0.00 47.34
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1419.16   0.00 137.87 1435.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9960.29   2544.47 1069.98 3861.03 0.00 0.00 0.00 0.00 146.12 71.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3823.35 26-JAN-13:02 4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 0.00 12.41
February 5262.60 27-FEB-09:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 27.86
March 9997.97 12-MAR-08:13 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 187.20
April 7756.23 21-APR-08:30 805.43 314.23 908.57 0.00 0.00 0.00 0.00 0.00 27.69
May 10194.48 28-MAY-09:02 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 66.50
June 14545.28 11-JUN-08:51 296.74 122.20 2120.00 0.00 0.00 0.00 0.00 0.00 55.95
July 14886.66 16-JUL-08:51 339.13 139.65 2422.86 0.00 0.00 0.00 0.00 31.56 0.00
August 15308.44 06-AUG-09:01 339.13 139.65 2422.86 0.00 0.00 0.00 0.00 0.00 16.30
September 13435.30 17-SEP-08:12 211.95 87.28 1514.29 0.00 0.00 0.00 0.00 0.00 72.22
October 10158.64 09-OCT-09:32 169.56 69.83 1211.43 0.00 0.00 0.00 0.00 0.00 29.12
November 4941.46 07-NOV-08:50 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 15.68
December 2215.95 14-DEC-11:05 1610.86 628.45 1817.15 0.00 0.00 0.00 0.00 0.00 21.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2215.95   169.56 69.83 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15308.44   4027.14 1571.14 4542.87 0.00 0.00 0.00 0.00 31.56 187.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14642.96 22-JAN-12:42 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 293.11
February 15024.66 26-FEB-13:12 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 148.54
March 14874.87 12-MAR-12:52 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 244.82
April 9210.13 21-APR-13:05 2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 0.00 29.19
May 7957.21 16-MAY-13:10 2613.31 992.69 2870.47 0.00 0.00 0.00 0.00 10.83 0.00
June 14128.74 25-JUN-16:21 669.60 275.74 4784.12 0.00 0.00 0.00 0.00 66.67 0.00
July 14294.10 23-JUL-12:42 401.76 165.44 2870.47 0.00 0.00 0.00 0.00 42.86 0.00
August 15087.58 27-AUG-12:22 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 55.33
September 16154.74 17-SEP-12:51 468.72 193.02 3348.89 0.00 0.00 0.00 0.00 0.00 14.26
October 17026.85 08-OCT-12:51 535.68 220.59 3827.30 0.00 0.00 0.00 0.00 0.00 62.08
November 16891.57 05-NOV-13:01 535.68 220.59 3827.30 0.00 0.00 0.00 0.00 0.00 13.84
December 14928.42 17-DEC-13:12 334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 157.08
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7957.21   334.80 137.87 2392.06 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17026.85   2613.31 992.69 4784.12 0.00 0.00 0.00 0.00 66.67 293.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5084.23 20-JAN-15:40 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 4.76
February 6421.37 26-FEB-15:53 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 0.00 111.25
March 10783.34 12-MAR-16:12 211.94 87.28 1514.28 0.00 0.00 0.00 0.00 0.00 73.49
April 10745.98 08-APR-17:05 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 102.63
May 9627.52 28-MAY-15:02 169.55 69.82 1211.42 0.00 0.00 0.00 0.00 0.00 46.20
June 16641.97 25-JUN-16:21 423.88 174.55 3028.56 0.00 0.00 0.00 0.00 22.88 0.00
July 15218.30 02-JUL-16:31 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.49 0.00
August 16377.48 13-AUG-17:01 0.00 157.10 2199.77 0.00 0.00 0.00 0.00 0.00 31.89
September 16115.82 10-SEP-17:11 0.00 157.10 2199.77 0.00 0.00 0.00 0.00 5.88 0.00
October 15322.25 08-OCT-15:31 296.72 122.19 2119.99 0.00 0.00 0.00 0.00 0.00 114.31
November 10641.91 05-NOV-15:02 254.33 104.73 1817.13 0.00 0.00 0.00 0.00 0.00 27.37
December 3849.14 14-DEC-15:30 805.38 314.21 908.57 0.00 0.00 0.00 0.00 0.00 10.84
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3849.14   0.00 69.82 908.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16641.97   805.38 314.21 3028.56 0.00 0.00 0.00 0.00 22.88 114.31



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.100222E+12 89022.00 24-JAN-16:19 0.582915E+11 220981.35 05-JAN-07:19
February 0.899701E+11 81020.47 23-FEB-11:00 0.617880E+11 222456.53 06-FEB-07:19
March 0.105003E+12 111362.43 13-MAR-15:00 0.395854E+11 178401.74 20-MAR-06:19
April 0.955555E+11 95923.08 07-APR-15:30 0.238169E+11 194602.18 03-APR-06:10
May 0.110767E+12 124537.97 31-MAY-15:20 0.259821E+10 85694.51 02-MAY-06:10
June 0.148059E+12 179202.45 26-JUN-15:09 19264481.02 11156.17 09-JUN-06:19
July 0.144638E+12 164565.60 17-JUL-10:50 3775804.78 931.73 03-JUL-06:00
August 0.149538E+12 160911.54 16-AUG-15:09 2990192.06 1797.48 23-AUG-06:10
September 0.125216E+12 141922.49 12-SEP-15:39 0.111869E+10 76750.50 22-SEP-06:10
October 0.105164E+12 120971.22 10-OCT-15:50 0.270115E+11 189079.41 30-OCT-06:10
November 0.986994E+11 96377.25 07-NOV-15:50 0.436726E+11 197878.22 30-NOV-07:10
December 0.984476E+11 85953.35 14-DEC-16:30 0.839201E+11 242080.55 23-DEC-07:19
             
Annual Sum or Average 0.137128E+13     0.341829E+12    
Minimum of Months 0.899701E+11 81020.47   2990192.06 931.73  
Maximum of Months 0.149538E+12 179202.45   0.839201E+11 242080.55  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.199484E+11 0.576619E+10 0.605851E+11 0.225725E+10 0.479699E+10 0.318349E+09 0.00 0.144808E+10 0.00 0.00 0.00 0.510182E+10 0.00
February 0.178034E+11 0.464601E+10 0.548702E+11 0.204812E+10 0.458317E+10 0.346403E+09 0.00 0.984057E+09 0.00 0.00 0.00 0.468874E+10 0.00
March 0.208158E+11 0.436023E+10 0.627783E+11 0.235484E+10 0.633133E+10 0.225754E+09 0.00 0.268099E+10 0.00 0.00 0.00 0.545597E+10 0.00
April 0.184093E+11 0.352061E+10 0.586172E+11 0.219172E+10 0.534431E+10 0.136404E+09 0.00 0.259221E+10 0.00 0.00 0.00 0.474381E+10 0.00
May 0.197375E+11 0.315424E+10 0.616817E+11 0.230559E+10 0.917557E+10 28117459.71 0.00 0.987014E+10 0.00 0.00 0.00 0.481465E+10 0.00
June 0.195897E+11 0.285754E+10 0.604966E+11 0.226781E+10 0.196550E+11 12392088.09 0.00 0.386677E+11 0.00 0.00 0.00 0.451240E+10 0.00
July 0.183421E+11 0.302979E+10 0.597911E+11 0.222860E+10 0.185727E+11 12284027.33 0.00 0.385696E+11 0.00 0.00 0.00 0.409158E+10 0.00
August 0.205580E+11 0.340742E+10 0.627783E+11 0.235457E+10 0.189016E+11 12695986.42 0.00 0.370909E+11 0.00 0.00 0.00 0.443417E+10 0.00
September 0.184650E+11 0.388526E+10 0.585950E+11 0.219052E+10 0.140277E+11 18582175.14 0.00 0.239548E+11 0.00 0.00 0.00 0.407949E+10 0.00
October 0.194795E+11 0.481774E+10 0.605962E+11 0.225784E+10 0.729445E+10 0.154573E+09 0.00 0.615794E+10 0.00 0.00 0.00 0.440613E+10 0.00
November 0.196941E+11 0.537119E+10 0.591197E+11 0.219991E+10 0.524867E+10 0.243445E+09 0.00 0.224080E+10 0.00 0.00 0.00 0.458157E+10 0.00
December 0.194031E+11 0.596407E+10 0.597800E+11 0.222855E+10 0.489413E+10 0.425446E+09 0.00 0.961332E+09 0.00 0.00 0.00 0.479104E+10 0.00
                           
Annual Sum or Average 0.232246E+12 0.507803E+11 0.719689E+12 0.268853E+11 0.118826E+12 0.193445E+10 0.00 0.165219E+12 0.00 0.00 0.00 0.557014E+11 0.00
Minimum of Months 0.178034E+11 0.285754E+10 0.548702E+11 0.204812E+10 0.458317E+10 12284027.33 0.00 0.961332E+09 0.00 0.00 0.00 0.407949E+10 0.00
Maximum of Months 0.208158E+11 0.596407E+10 0.627783E+11 0.235484E+10 0.196550E+11 0.425446E+09 0.00 0.386677E+11 0.00 0.00 0.00 0.545597E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.582915E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.617880E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.395854E+11 0.00 0.00 0.00 0.00
April 0.00 0.00 0.238169E+11 0.00 0.00 0.00 0.00
May 0.00 0.00 0.259821E+10 0.00 0.00 0.00 0.00
June 0.00 0.00 19264481.02 0.00 0.00 0.00 0.00
July 0.00 0.00 3775804.78 0.00 0.00 0.00 0.00
August 0.00 0.00 2990192.06 0.00 0.00 0.00 0.00
September 0.00 0.00 0.111869E+10 0.00 0.00 0.00 0.00
October 0.00 0.00 0.270115E+11 0.00 0.00 0.00 0.00
November 0.00 0.00 0.436726E+11 0.00 0.00 0.00 0.00
December 0.00 0.00 0.839201E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.341829E+12 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 2990192.06 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.839201E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 25003.79 02-JAN-16:49 5686.19 01-JAN-06:10 41699.26 02-JAN-08:09 1410.29 03-JAN-13:09 9223.78 24-JAN-16:19 738.42 05-JAN-07:10 0.00 01-JAN-00:10
February 24334.46 06-FEB-16:00 5686.19 01-FEB-06:10 41699.26 01-FEB-08:09 1410.29 01-FEB-08:20 9530.99 27-FEB-15:39 735.59 06-FEB-07:00 0.00 01-FEB-00:10
March 22326.73 21-MAR-07:10 5686.19 01-MAR-06:10 41699.26 01-MAR-08:09 1410.29 01-MAR-13:09 20386.09 15-MAR-15:00 676.69 20-MAR-06:00 0.00 01-MAR-00:10
April 21107.22 03-APR-07:10 5686.19 01-APR-05:10 41699.26 03-APR-07:10 1410.29 03-APR-07:19 13034.53 21-APR-13:39 730.66 03-APR-06:40 0.00 01-APR-00:10
May 19671.42 01-MAY-07:10 3328.83 01-MAY-18:49 41699.26 01-MAY-07:10 1410.29 01-MAY-16:10 20628.92 31-MAY-15:20 397.97 02-MAY-06:10 0.00 01-MAY-00:10
June 19737.96 16-JUN-07:10 3328.83 01-JUN-19:19 41699.26 01-JUN-07:10 1410.29 01-JUN-07:19 34015.60 26-JUN-15:20 99.98 09-JUN-06:19 0.00 01-JUN-00:10
July 19711.36 28-JUL-07:10 3328.83 01-JUL-19:30 41699.26 03-JUL-07:10 1410.29 03-JUL-07:10 35471.95 24-JUL-15:20 13.62 03-JUL-06:00 0.00 01-JUL-00:10
August 20060.48 28-AUG-15:00 5686.19 10-AUG-05:10 41699.26 01-AUG-07:10 1410.29 01-AUG-07:19 30966.02 21-AUG-14:39 18.86 23-AUG-06:10 0.00 01-AUG-00:10
September 20087.88 21-SEP-15:00 5686.19 01-SEP-05:10 41699.26 01-SEP-07:10 1410.29 01-SEP-07:10 28795.12 05-SEP-15:39 384.00 22-SEP-06:10 0.00 01-SEP-00:10
October 23431.59 30-OCT-07:10 5686.19 01-OCT-05:10 41699.26 02-OCT-07:10 1410.29 02-OCT-16:10 19757.51 11-OCT-15:00 713.68 30-OCT-06:30 0.00 01-OCT-00:10
November 25003.79 06-NOV-16:49 5686.19 01-NOV-05:10 41699.26 01-NOV-07:10 1410.29 01-NOV-12:09 11794.04 08-NOV-15:50 717.58 30-NOV-07:19 0.00 01-NOV-00:10
December 25003.79 01-DEC-16:30 5686.19 01-DEC-06:10 41699.26 01-DEC-08:09 1410.29 01-DEC-17:10 7331.88 26-DEC-07:10 771.61 23-DEC-07:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 19671.42   3328.83   41699.26   1410.29   7331.88   13.62   0.00  
Maximum of Months 25003.79   5686.19   41699.26   1410.29   35471.95   771.61   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 15268.51 20-JAN-13:00 0.00 0.00 0.00 6742.94 31-JAN-12:30 0.00
February 11308.17 18-FEB-13:39 0.00 0.00 0.00 6796.72 14-FEB-12:30 0.00
March 25139.86 13-MAR-15:00 0.00 0.00 0.00 6740.54 01-MAR-12:20 0.00
April 17108.12 20-APR-12:00 0.00 0.00 0.00 6671.48 06-APR-11:39 0.00
May 36539.01 31-MAY-15:20 0.00 0.00 0.00 6264.75 01-MAY-11:20 0.00
June 78403.23 26-JUN-14:00 0.00 0.00 0.00 5915.39 02-JUN-11:20 0.00
July 63769.38 17-JUL-12:00 0.00 0.00 0.00 5763.53 03-JUL-11:30 0.00
August 65837.77 16-AUG-15:00 0.00 0.00 0.00 5408.74 31-AUG-11:20 0.00
September 49366.96 12-SEP-15:00 0.00 0.00 0.00 5768.93 29-SEP-11:50 0.00
October 36547.96 11-OCT-14:30 0.00 0.00 0.00 6089.48 31-OCT-11:00 0.00
November 19692.63 07-NOV-15:09 0.00 0.00 0.00 6270.27 30-NOV-12:39 0.00
December 13551.02 01-DEC-13:00 0.00 0.00 0.00 6686.43 29-DEC-12:50 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 11308.17   0.00 0.00 0.00 5408.74   0.00
Maximum of Months 78403.23   0.00 0.00 0.00 6796.72   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 89022.00 24-JAN-16:19 21551.04 41670.51 0.00 1410.29 9223.78 6.85 0.00 10108.99 0.00
February 81020.47 23-FEB-11:00 19671.42 41666.76 0.00 1410.29 5283.23 6.85 0.00 7530.94 0.00
March 111362.43 13-MAR-15:00 19671.42 41670.51 0.00 1410.29 18164.00 6.85 0.00 25139.86 0.00
April 95923.08 07-APR-15:30 19671.42 41670.51 0.00 1410.29 12230.83 6.85 0.00 15919.23 0.00
May 124537.97 31-MAY-15:20 19671.42 41670.51 0.00 1410.29 20628.92 6.85 0.00 36539.01 0.00
June 179202.45 26-JUN-15:09 19671.42 41670.51 0.00 1410.29 33911.97 6.85 0.00 78282.17 0.00
July 164565.60 17-JUL-10:50 19671.42 41666.76 0.00 1410.29 34384.74 6.85 0.00 62900.81 0.00
August 160911.54 16-AUG-15:09 19671.42 41670.51 0.00 1410.29 28896.52 6.85 0.00 65338.43 0.00
September 141922.49 12-SEP-15:39 19671.42 41670.51 0.00 1410.29 25949.89 6.85 0.00 48966.88 0.00
October 120971.22 10-OCT-15:50 19671.42 41670.51 0.00 1410.29 19738.17 6.85 0.00 34198.25 0.00
November 96377.25 07-NOV-15:50 20509.30 41659.26 0.00 1410.29 11512.26 6.85 0.00 17919.87 0.00
December 85953.35 14-DEC-16:30 25003.79 41670.51 5686.19 1410.29 4226.80 6.85 0.00 2947.99 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 81020.47   19671.42 41659.26 0.00 1410.29 4226.80 6.85 0.00 2947.99 0.00
Maximum of Months 179202.45   25003.79 41670.51 5686.19 1410.29 34384.74 6.85 0.00 78282.17 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 220981.35 05-JAN-07:19 0.00 0.00 0.00
February 0.00 0.00 222456.53 06-FEB-07:19 0.00 0.00 0.00
March 0.00 0.00 178401.74 20-MAR-06:19 0.00 0.00 0.00
April 0.00 0.00 194602.18 03-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 85694.51 02-MAY-06:10 0.00 0.00 0.00
June 0.00 0.00 11156.17 09-JUN-06:19 0.00 0.00 0.00
July 0.00 0.00 931.73 03-JUL-06:00 0.00 0.00 0.00
August 0.00 0.00 1797.48 23-AUG-06:10 0.00 0.00 0.00
September 0.00 0.00 76750.50 22-SEP-06:10 0.00 0.00 0.00
October 0.00 0.00 189079.41 30-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 197878.22 30-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 242080.55 23-DEC-07:19 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 931.73   0.00 0.00 0.00
Maximum of Months 0.00 0.00 242080.55   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 1.33 27.32 0.00 27.32
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.33 27.32 0.00 27.32
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 27.32 0.00 27.32



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 19.86 0.33 19.86 0.00 19.86 0.00 19.86
                 
Annual Sum or Average 0.33 19.86 0.33 19.86 0.00 19.86 0.00 19.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 19.86 0.33 19.86 0.00 19.86 0.00 19.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.39 0.50 19.39 0.00 19.39 0.00 19.39
February 1.83 19.08 1.50 19.29 0.00 19.29 0.00 19.29
March 0.17 19.11 0.17 19.11 0.00 19.11 0.00 19.11
April 0.33 19.33 0.33 19.33 0.00 19.33 0.00 19.33
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 19.38 0.17 19.38 0.00 19.38 0.00 19.38
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 2.33 19.19 2.17 19.27 0.00 19.27 0.00 19.27
                 
Annual Sum or Average 5.33 19.19 4.83 19.29 0.00 19.29 0.00 19.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.39 2.17 19.39 0.00 19.39 0.00 19.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 18.19 4.33 18.57 0.00 18.57 0.00 18.57
February 15.33 16.66 7.17 17.21 0.00 17.21 0.00 17.21
March 3.33 16.61 2.50 16.66 0.00 16.66 0.00 16.66
April 2.83 18.72 2.00 19.10 0.00 19.10 0.00 19.10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 5.00 27.47 3.33 27.46
July 0.00 0.00 0.00 0.00 7.50 27.56 6.00 27.57
August 0.00 0.00 0.00 0.00 1.33 27.33 1.33 27.33
September 0.00 0.00 0.00 0.00 1.33 27.34 1.33 27.34
October 2.17 18.87 1.67 19.24 0.00 19.24 0.00 19.24
November 2.83 18.59 1.83 18.98 0.00 18.98 0.00 18.98
December 37.17 17.40 21.83 18.02 0.00 18.02 0.00 18.02
                 
Annual Sum or Average 69.83 17.42 41.33 17.96 15.17 19.11 12.00 19.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37.17 18.87 21.83 19.24 7.50 27.56 6.00 27.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.33 17.60 1.50 18.20 0.00 18.20 0.00 18.20
February 10.50 15.94 3.00 16.39 0.00 16.39 0.00 16.39
March 3.00 15.48 1.67 15.39 0.67 16.94 0.67 18.14
April 1.83 16.44 0.33 16.87 0.33 18.28 0.33 19.35
May 0.00 0.00 0.00 0.00 0.83 27.63 0.83 27.63
June 0.00 0.00 0.00 0.00 11.67 27.85 10.50 27.87
July 0.00 0.00 0.00 0.00 17.00 28.10 15.50 28.13
August 0.00 0.00 0.00 0.00 8.00 28.02 7.67 28.03
September 0.00 0.00 0.00 0.00 7.83 27.72 7.33 27.74
October 0.67 16.74 0.17 17.21 1.67 24.13 1.67 25.51
November 1.83 16.72 0.17 16.95 0.00 16.95 0.00 16.95
December 21.67 16.34 8.00 17.00 0.00 17.00 0.00 17.00
                 
Annual Sum or Average 42.83 16.31 14.83 16.82 48.00 21.87 44.50 23.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.39 0.00 16.39
Maximum of Months 21.67 17.60 8.00 18.20 17.00 28.10 15.50 28.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.67 18.62 1.50 19.11 1.67 21.55 1.67 22.92
February 8.17 16.43 3.33 16.95 2.17 18.69 2.17 19.96
March 2.33 15.84 1.67 15.79 2.17 20.11 2.17 22.19
April 1.67 18.08 0.83 18.60 0.00 18.60 0.00 18.60
May 0.00 0.00 0.00 0.00 0.17 27.39 0.17 27.39
June 0.00 0.00 0.00 0.00 7.17 27.71 6.33 27.72
July 0.00 0.00 0.00 0.00 11.50 27.81 10.33 27.83
August 0.00 0.00 0.00 0.00 6.67 27.94 6.33 27.95
September 0.00 0.00 0.00 0.00 11.83 27.35 11.00 27.34
October 1.00 17.82 0.50 18.41 9.67 26.16 9.67 26.72
November 1.00 17.18 0.17 17.48 4.33 25.61 4.33 26.57
December 17.00 17.03 8.33 17.70 2.50 18.63 2.50 19.41
                 
Annual Sum or Average 33.83 17.01 16.33 17.55 59.83 23.06 56.67 24.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.60 0.00 18.60
Maximum of Months 17.00 18.62 8.33 19.11 11.83 27.94 11.00 27.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 18.23 1.00 18.81 0.00 18.81 0.00 18.81
February 9.17 15.70 2.83 16.02 0.17 16.18 0.17 16.33
March 3.67 15.50 1.67 15.41 1.67 18.40 1.00 19.62
April 2.17 15.89 0.17 16.13 0.17 16.94 0.17 17.64
May 0.00 0.00 0.00 0.00 3.33 27.67 3.00 27.67
June 0.00 0.00 0.00 0.00 9.83 28.54 5.83 28.58
July 0.00 0.00 0.00 0.00 12.67 28.15 8.67 28.17
August 0.00 0.00 0.00 0.00 6.50 28.22 4.17 28.23
September 0.00 0.00 0.00 0.00 7.67 28.27 5.33 28.33
October 0.67 16.78 0.17 17.28 3.00 25.77 2.83 26.79
November 1.00 16.35 0.00 16.35 0.33 19.16 0.33 20.85
December 25.17 16.74 11.50 17.41 0.00 17.41 0.00 17.41
                 
Annual Sum or Average 44.00 16.44 17.33 16.97 45.33 21.75 31.50 23.23
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.18 0.00 16.33
Maximum of Months 25.17 18.23 11.50 18.81 12.67 28.54 8.67 28.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.72 0.50 19.72 0.00 19.72 0.00 19.72
February 4.17 19.41 3.67 19.57 0.00 19.57 0.00 19.57
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.33 19.37 0.33 19.37 0.00 19.37 0.00 19.37
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 27.37 0.33 27.37
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 6.67 19.60 6.17 19.71 0.00 19.71 0.00 19.71
                 
Annual Sum or Average 11.67 19.53 10.67 19.65 0.33 19.76 0.33 19.87
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.67 19.72 6.17 19.72 0.33 27.37 0.33 27.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 1.17 18.75 0.67 19.23 0.00 19.23 0.00 19.23
March 0.00 0.00 0.00 0.00 0.33 27.28 0.33 27.28
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
June 0.00 0.00 0.00 0.00 6.83 27.55 6.67 27.56
July 0.00 0.00 0.00 0.00 14.17 27.73 13.67 27.74
August 0.00 0.00 0.00 0.00 6.67 27.78 6.67 27.78
September 0.00 0.00 0.00 0.00 6.67 27.59 6.33 27.59
October 0.00 0.00 0.00 0.00 2.33 27.47 2.33 27.47
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 3.17 19.52 2.67 19.75 0.00 19.75 0.00 19.75
                 
Annual Sum or Average 4.33 19.32 3.33 19.63 37.17 26.29 36.17 26.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.17 19.52 2.67 19.75 14.17 27.78 13.67 27.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 40.33 18.01 40.33 18.01 2.50 18.29 2.50 18.56
February 43.17 17.93 42.83 17.94 2.17 18.18 2.17 18.41
March 29.83 18.26 29.83 18.26 1.50 18.49 1.50 18.71
April 25.50 18.67 25.50 18.67 0.00 18.67 0.00 18.67
May 5.50 19.31 5.50 19.31 0.00 19.31 0.00 19.31
June 0.00 0.00 0.00 0.00 6.17 25.39 6.17 25.39
July 0.00 0.00 0.00 0.00 6.50 26.76 6.50 26.76
August 0.00 0.00 0.00 0.00 12.33 25.96 12.33 25.96
September 1.50 19.13 1.50 19.13 16.83 25.42 15.50 25.88
October 23.50 18.07 23.50 18.07 16.50 20.28 15.67 21.52
November 30.50 18.11 30.50 18.11 7.50 19.03 7.50 19.78
December 61.50 17.58 61.00 17.59 3.00 17.84 3.00 18.07
                 
Annual Sum or Average 261.33 18.04 260.50 18.04 75.00 19.11 72.83 19.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.84 0.00 18.07
Maximum of Months 61.50 19.31 61.00 19.31 16.83 26.76 15.67 26.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.83 18.77 0.50 19.24 0.00 19.24 0.00 19.24
March 0.00 0.00 0.00 0.00 0.67 27.65 0.33 27.67
April 0.00 0.00 0.00 0.00 0.17 27.89 0.17 27.89
May 0.00 0.00 0.00 0.00 1.00 27.32 0.83 27.31
June 0.00 0.00 0.00 0.00 7.83 28.05 4.17 28.08
July 0.00 0.00 0.00 0.00 7.83 27.89 5.67 27.85
August 0.00 0.00 0.00 0.00 4.33 28.01 2.83 28.01
September 0.00 0.00 0.00 0.00 7.00 27.94 4.83 27.95
October 0.00 0.00 0.00 0.00 2.50 27.98 2.33 27.99
November 0.00 0.00 0.00 0.00 0.33 27.39 0.33 27.39
December 4.50 19.75 4.00 19.92 0.00 19.92 0.00 19.92
                 
Annual Sum or Average 5.33 19.60 4.50 19.83 31.67 26.02 21.50 26.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.50 19.75 4.00 19.92 7.83 28.05 5.67 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.31 0.17 18.68 0.00 18.68 0.00 18.68
February 3.33 18.83 2.50 19.16 0.00 19.16 0.00 19.16
March 0.17 19.43 0.17 19.43 0.00 19.43 0.00 19.43
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.67 27.43 1.17 27.41
July 0.00 0.00 0.00 0.00 3.50 27.49 2.83 27.51
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 18.31 0.17 18.67 0.00 18.67 0.00 18.67
December 10.50 18.66 8.33 18.98 0.00 18.98 0.00 18.98
                 
Annual Sum or Average 14.67 18.69 11.33 19.02 5.17 20.42 4.00 21.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 10.50 19.43 8.33 19.43 3.50 27.49 2.83 27.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 17.17 0.00 17.17 0.00 17.17 0.00 17.17
February 1.17 17.88 0.50 18.50 0.00 18.50 0.00 18.50
March 0.17 17.24 0.00 17.24 1.17 26.45 1.17 27.06
April 0.00 0.00 0.00 0.00 0.83 27.65 0.83 27.65
May 0.00 0.00 0.00 0.00 1.33 27.68 1.33 27.68
June 0.00 0.00 0.00 0.00 10.83 27.74 10.50 27.75
July 0.00 0.00 0.00 0.00 15.83 28.02 15.00 28.04
August 0.00 0.00 0.00 0.00 7.00 28.03 7.00 28.03
September 0.00 0.00 0.00 0.00 6.50 27.81 6.50 27.81
October 0.00 0.00 0.00 0.00 2.67 27.75 2.67 27.75
November 0.17 17.14 0.00 17.14 0.00 17.14 0.00 17.14
December 5.67 18.04 3.50 18.58 0.00 18.58 0.00 18.58
                 
Annual Sum or Average 7.50 17.94 4.00 18.48 46.17 26.01 45.00 26.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.14 0.00 17.14
Maximum of Months 5.67 18.04 3.50 18.58 15.83 28.03 15.00 28.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 7.83 26.39 7.83 26.39
February 1.67 18.82 1.17 19.26 2.83 23.64 2.83 25.10
March 0.00 0.00 0.00 0.00 2.67 27.63 2.67 27.63
April 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
May 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
June 0.00 0.00 0.00 0.00 5.50 27.55 5.17 27.55
July 0.00 0.00 0.00 0.00 10.00 27.64 9.67 27.65
August 0.00 0.00 0.00 0.00 6.17 27.82 6.17 27.82
September 0.00 0.00 0.00 0.00 12.83 27.12 12.33 27.11
October 0.00 0.00 0.00 0.00 13.83 26.78 13.83 26.78
November 0.00 0.00 0.00 0.00 10.67 26.62 10.67 26.62
December 4.33 18.93 3.33 19.23 3.50 22.02 3.50 23.48
                 
Annual Sum or Average 6.00 18.90 4.50 19.24 76.17 26.21 75.00 26.65
Minimum of Months 0.00 0.00 0.00 0.00 0.17 22.02 0.17 23.48
Maximum of Months 4.33 18.93 3.33 19.26 13.83 27.82 13.83 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 17.17 0.00 17.17 0.00 17.17 0.00 17.17
February 1.17 17.90 0.50 18.51 0.33 20.01 0.33 21.08
March 0.17 17.24 0.00 17.24 1.33 26.92 1.00 27.42
April 0.00 0.00 0.00 0.00 0.33 27.75 0.33 27.75
May 0.00 0.00 0.00 0.00 3.00 27.62 2.83 27.61
June 0.00 0.00 0.00 0.00 8.67 28.43 4.83 28.50
July 0.00 0.00 0.00 0.00 10.50 28.07 7.50 28.05
August 0.00 0.00 0.00 0.00 5.50 28.18 3.67 28.20
September 0.00 0.00 0.00 0.00 7.33 28.16 5.33 28.19
October 0.00 0.00 0.00 0.00 3.17 28.11 3.00 28.13
November 0.17 17.18 0.00 17.18 0.50 24.99 0.50 26.11
December 8.00 18.73 6.17 19.11 0.00 19.11 0.00 19.11
                 
Annual Sum or Average 9.67 18.55 6.67 18.99 40.67 25.52 29.33 26.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.17 0.00 17.17
Maximum of Months 8.00 18.73 6.17 19.11 10.50 28.43 7.50 28.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 409.17 23.79 1.67 23.80 0.00 23.80
February 355.83 23.73 4.83 23.76 0.00 23.76
March 421.67 23.95 10.67 23.98 0.00 23.98
April 269.67 24.01 36.17 24.17 0.00 24.17
May 85.00 24.01 169.50 24.85 0.00 24.85
June 0.33 24.00 324.67 24.66 0.33 24.66
July 17.17 24.71 385.67 24.66 17.17 24.66
August 0.83 24.00 358.50 24.65 0.33 24.65
September 22.67 24.00 191.50 25.00 0.00 25.00
October 165.17 23.96 75.33 24.55 0.00 24.55
November 264.00 23.97 18.50 24.08 0.00 24.08
December 473.67 23.62 5.17 23.60 5.17 23.57
             
Annual Sum or Average 2485.17 23.85 1582.17 24.24 23.00 24.24
Minimum of Months 0.33 23.62 1.67 23.60 0.00 23.57
Maximum of Months 473.67 24.71 385.67 25.00 17.17 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 498.33 22.60 63.50 22.40 63.50 22.25
February 448.17 22.64 66.67 22.40 66.67 22.21
March 489.83 23.05 18.00 22.97 18.00 22.90
April 428.50 23.18 9.17 23.15 6.67 23.11
May 183.50 23.81 56.33 24.02 0.00 24.02
June 11.50 24.01 282.17 24.43 0.00 24.43
July 34.83 24.26 327.50 24.45 25.67 24.44
August 4.17 24.06 295.50 24.47 0.17 24.47
September 110.00 23.93 118.33 24.42 0.00 24.42
October 359.50 23.44 12.67 23.41 8.17 23.35
November 453.50 23.05 10.33 23.01 9.50 22.97
December 497.00 22.21 120.33 21.88 120.33 21.65
             
Annual Sum or Average 3518.83 22.95 1380.50 23.17 318.67 23.03
Minimum of Months 4.17 22.21 9.17 21.88 0.00 21.65
Maximum of Months 498.33 24.26 327.50 24.47 120.33 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.68 161.67 21.33 161.67 21.11
February 454.00 21.83 156.67 21.46 156.67 21.23
March 505.00 22.42 91.50 22.08 91.50 21.82
April 446.67 22.54 72.00 22.23 71.67 22.00
May 253.83 23.56 36.33 23.63 2.83 23.60
June 15.00 23.91 279.00 24.39 0.00 24.39
July 29.33 24.21 319.83 24.43 25.67 24.42
August 16.33 23.95 286.17 24.38 0.17 24.38
September 154.17 23.69 96.00 24.09 0.00 24.09
October 448.33 22.88 58.17 22.64 58.17 22.44
November 484.00 22.19 83.17 21.98 83.17 21.82
December 497.00 21.30 245.50 20.96 245.50 20.78
             
Annual Sum or Average 3805.67 22.30 1886.00 22.38 897.00 22.12
Minimum of Months 15.00 21.30 36.33 20.96 0.00 20.78
Maximum of Months 505.00 24.21 319.83 24.43 245.50 24.42



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.54 329.00 20.29 329.00 20.18
February 454.00 20.71 301.17 20.47 301.17 20.37
March 513.50 21.52 212.50 21.09 212.50 20.86
April 454.50 21.61 158.67 21.16 155.50 20.88
May 266.50 23.00 92.00 23.24 13.50 23.15
June 29.33 24.47 345.50 24.42 10.00 24.46
July 58.50 24.65 374.67 24.53 45.33 24.56
August 57.00 23.71 308.33 24.26 4.17 24.28
September 197.00 23.19 109.00 23.65 7.67 23.59
October 475.17 21.93 139.83 21.56 139.83 21.32
November 487.00 21.07 269.83 20.79 269.83 20.66
December 497.00 20.26 400.50 20.10 400.50 20.04
             
Annual Sum or Average 3991.50 21.43 3041.00 21.59 1889.00 21.30
Minimum of Months 29.33 20.26 92.00 20.10 4.17 20.04
Maximum of Months 513.50 24.65 400.50 24.53 400.50 24.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 499.50 21.21 240.50 20.81 240.50 20.61
February 428.83 21.37 202.50 20.92 201.00 20.68
March 417.33 21.74 172.33 21.39 154.33 21.09
April 365.00 21.67 162.17 21.38 125.67 21.05
May 171.00 23.17 176.33 23.80 9.67 23.75
June 42.33 26.38 420.17 24.66 37.33 24.82
July 91.17 25.89 441.00 24.84 88.50 25.00
August 50.17 25.39 401.17 24.54 28.00 24.67
September 129.83 23.77 218.17 24.28 20.83 24.36
October 370.83 22.03 153.50 21.94 112.17 21.66
November 462.33 21.59 172.17 21.25 171.00 21.04
December 497.00 20.83 303.50 20.45 303.50 20.28
             
Annual Sum or Average 3525.33 21.85 3063.50 22.20 1492.50 21.93
Minimum of Months 42.33 20.83 153.50 20.45 9.67 20.28
Maximum of Months 499.50 26.38 441.00 24.84 303.50 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 352.83 21.45 241.17 21.51 165.67 21.23
February 317.00 21.32 229.33 21.34 163.17 21.05
March 370.67 21.67 207.00 21.54 155.00 21.27
April 364.17 21.49 165.67 21.23 130.83 20.91
May 229.83 22.92 136.67 23.40 13.33 23.30
June 62.83 24.54 340.50 24.45 21.00 24.55
July 93.83 24.93 378.50 24.62 64.00 24.73
August 68.50 24.63 365.17 24.46 23.50 24.58
September 148.83 23.88 238.50 24.31 31.17 24.45
October 327.83 22.19 233.83 22.43 127.50 22.24
November 328.83 21.82 227.83 22.03 135.83 21.78
December 397.33 21.21 271.50 21.05 230.83 20.82
             
Annual Sum or Average 3062.50 22.02 3035.67 22.49 1261.83 22.23
Minimum of Months 62.83 21.21 136.67 21.05 13.33 20.82
Maximum of Months 397.33 24.93 378.50 24.62 230.83 24.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 466.50 20.96 265.50 20.62 263.33 20.45
February 406.17 21.03 247.83 20.76 235.00 20.58
March 433.00 21.54 206.00 21.27 178.67 21.02
April 381.00 21.48 171.00 21.21 137.83 20.92
May 224.17 23.03 156.67 23.56 19.00 23.53
June 62.50 24.97 369.50 24.55 28.00 24.68
July 94.83 25.01 398.33 24.64 68.50 24.74
August 67.33 24.48 367.00 24.44 21.67 24.54
September 172.17 23.62 188.00 24.13 27.67 24.25
October 398.83 21.94 183.00 21.88 133.50 21.65
November 433.17 21.35 213.50 21.07 203.33 20.88
December 480.00 20.66 338.33 20.36 337.33 20.23
             
Annual Sum or Average 3619.67 21.70 3104.67 22.01 1653.83 21.74
Minimum of Months 62.50 20.66 156.67 20.36 19.00 20.23
Maximum of Months 480.00 25.01 398.33 24.64 337.33 24.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.75 299.17 20.57 299.17 20.48
February 454.00 20.77 297.50 20.61 297.50 20.54
March 514.00 21.40 209.83 21.10 209.83 20.94
April 481.50 21.74 128.00 21.45 128.00 21.27
May 360.33 23.23 30.33 23.24 8.67 23.19
June 24.83 23.98 284.17 24.31 4.00 24.31
July 37.67 24.10 330.67 24.40 34.67 24.37
August 29.17 23.93 272.83 24.30 1.00 24.30
September 170.83 23.64 108.33 24.06 0.00 24.06
October 479.83 22.63 59.67 22.41 59.67 22.24
November 489.00 21.62 134.67 21.42 134.67 21.29
December 497.00 20.68 332.17 20.50 332.17 20.42
             
Annual Sum or Average 4040.17 21.69 2487.33 21.82 1509.33 21.56
Minimum of Months 24.83 20.68 30.33 20.50 0.00 20.42
Maximum of Months 514.00 24.10 332.17 24.40 332.17 24.37



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.62 176.67 21.31 176.67 21.12
February 432.00 21.66 181.83 21.26 179.50 21.04
March 451.00 22.12 120.50 21.78 115.00 21.52
April 391.50 22.25 95.67 22.05 76.67 21.81
May 173.83 23.40 140.83 23.94 2.17 23.92
June 15.17 26.62 426.17 24.58 15.17 24.65
July 69.83 25.59 456.33 24.76 69.83 24.86
August 22.33 26.60 430.50 24.59 20.67 24.69
September 63.00 24.18 250.50 24.63 9.67 24.70
October 317.33 22.72 98.83 22.88 46.67 22.68
November 442.67 22.30 78.50 22.09 73.67 21.91
December 497.00 21.43 240.50 21.07 240.50 20.88
             
Annual Sum or Average 3377.67 22.21 2696.83 22.64 1026.17 22.41
Minimum of Months 15.17 21.43 78.50 21.07 2.17 20.88
Maximum of Months 502.00 26.62 456.33 24.76 240.50 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 360.00 21.64 162.67 21.69 95.67 21.36
February 333.33 21.24 183.33 21.16 132.67 20.82
March 397.17 21.57 149.17 21.28 132.17 21.00
April 419.00 21.65 106.83 21.38 99.50 21.14
May 318.33 22.76 62.33 22.98 11.83 22.89
June 52.00 23.23 288.50 24.25 5.33 24.25
July 73.00 23.97 348.00 24.42 46.50 24.41
August 46.00 23.95 381.83 24.44 17.00 24.50
September 84.83 23.83 279.17 24.55 22.00 24.67
October 264.33 22.30 199.17 22.84 75.50 22.69
November 295.17 21.89 170.50 22.34 67.17 22.09
December 389.50 21.18 196.67 20.96 160.67 20.63
             
Annual Sum or Average 3032.67 21.91 2528.17 22.50 866.00 22.22
Minimum of Months 46.00 21.18 62.33 20.96 5.33 20.63
Maximum of Months 419.00 23.97 381.83 24.55 160.67 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 481.17 21.45 186.33 21.16 185.33 20.99
February 429.67 21.48 191.50 21.14 189.50 20.95
March 459.50 21.90 139.17 21.58 133.00 21.34
April 417.50 22.11 95.17 21.87 84.00 21.65
May 237.00 23.32 111.83 23.73 3.83 23.69
June 28.33 25.79 381.83 24.58 19.83 24.68
July 50.17 24.97 410.83 24.58 50.17 24.62
August 19.33 25.64 407.67 24.53 13.17 24.59
September 91.50 24.21 222.83 24.61 15.67 24.72
October 347.33 22.81 101.17 22.87 51.00 22.70
November 433.17 22.21 77.33 22.03 71.67 21.86
December 489.00 21.29 244.67 20.95 243.83 20.78
             
Annual Sum or Average 3483.67 22.11 2570.33 22.49 1061.00 22.25
Minimum of Months 19.33 21.29 77.33 20.95 3.83 20.78
Maximum of Months 489.00 25.79 410.83 24.61 243.83 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.07 237.83 20.78 237.83 20.64
February 454.00 21.12 229.67 20.83 229.67 20.68
March 510.83 21.90 133.50 21.53 133.50 21.28
April 455.17 22.16 92.50 21.84 90.17 21.61
May 234.83 23.39 82.00 23.65 3.50 23.61
June 8.67 24.38 362.17 24.45 3.83 24.45
July 36.33 24.56 392.00 24.53 36.33 24.53
August 20.50 23.90 323.00 24.36 1.83 24.36
September 165.33 23.54 116.50 24.05 0.00 24.05
October 463.33 22.50 67.83 22.24 67.83 22.04
November 486.00 21.61 151.33 21.38 151.33 21.23
December 497.00 20.70 312.50 20.46 312.50 20.36
             
Annual Sum or Average 3834.00 21.81 2500.83 22.05 1268.33 21.77
Minimum of Months 8.67 20.70 67.83 20.46 0.00 20.36
Maximum of Months 510.83 24.56 392.00 24.53 312.50 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 415.00 21.57 155.50 21.24 154.33 21.04
February 352.17 21.56 153.67 21.18 146.33 20.93
March 352.83 21.99 108.33 21.74 89.67 21.46
April 311.83 22.13 102.83 21.99 69.83 21.73
May 134.67 23.54 154.50 24.16 5.67 24.17
June 31.50 26.75 353.50 24.80 31.17 24.95
July 80.50 25.99 379.17 24.99 80.50 25.14
August 34.50 26.09 337.17 24.71 26.67 24.85
September 100.00 24.12 185.17 24.61 15.00 24.74
October 315.50 22.51 108.67 22.59 65.17 22.38
November 379.00 21.97 103.67 21.73 97.17 21.53
December 419.33 21.15 230.00 20.77 230.00 20.58
             
Annual Sum or Average 2926.83 22.18 2372.17 22.60 1011.50 22.37
Minimum of Months 31.50 21.15 102.83 20.77 5.67 20.58
Maximum of Months 419.33 26.75 379.17 24.99 230.00 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 329.67 21.98 187.67 22.21 98.83 21.97
February 298.67 21.75 200.33 21.86 123.00 21.56
March 352.33 22.04 149.00 22.01 93.33 21.75
April 357.67 22.13 106.17 21.97 73.83 21.72
May 197.00 23.32 132.83 23.80 4.00 23.76
June 26.33 25.23 356.33 24.50 14.17 24.57
July 57.83 25.24 394.00 24.65 52.67 24.73
August 34.67 25.58 390.33 24.55 20.50 24.65
September 112.67 24.33 253.50 24.58 26.00 24.75
October 303.17 22.76 204.83 23.07 88.00 22.96
November 307.50 22.40 191.50 22.77 83.50 22.61
December 384.50 21.75 229.17 21.65 179.33 21.41
             
Annual Sum or Average 2762.00 22.42 2795.67 22.99 857.17 22.80
Minimum of Months 26.33 21.75 106.17 21.65 4.00 21.41
Maximum of Months 384.50 25.58 394.00 24.65 179.33 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 457.83 21.47 181.17 21.16 175.83 20.97
February 397.50 21.43 191.67 21.15 177.67 20.93
March 426.83 21.97 136.17 21.75 108.83 21.49
April 375.83 22.11 108.67 21.95 76.50 21.70
May 191.17 23.43 159.33 23.93 9.17 23.94
June 35.17 25.91 389.17 24.61 25.33 24.73
July 62.50 25.42 415.67 24.68 61.17 24.77
August 33.00 25.40 389.67 24.54 19.83 24.63
September 136.00 24.02 199.33 24.45 21.00 24.60
October 380.67 22.55 125.67 22.56 74.00 22.38
November 421.67 21.89 132.00 21.71 114.83 21.52
December 474.83 21.09 269.00 20.76 266.17 20.59
             
Annual Sum or Average 3393.00 22.09 2697.50 22.49 1130.33 22.25
Minimum of Months 33.00 21.09 108.67 20.76 9.17 20.59
Maximum of Months 474.83 25.91 415.67 24.68 266.17 24.77



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.93579 19.52965 0.13345 5.81631
February 454.00000 23.94335 17.76419 0.12026 5.92220
March 514.00000 24.09643 17.54059 0.18035 5.89198
April 485.00000 24.22596 21.56656 0.23985 6.46041
May 508.00000 24.48125 24.51594 -0.4896 10.80866
June 496.00000 24.44124 32.68856 -0.3867 8.73204
July 497.00000 24.51997 34.48220 -0.3499 8.18567
August 514.00000 24.45883 33.19506 -0.3753 8.61511
September 485.00000 24.49689 24.48552 -0.4381 9.82903
October 502.00000 24.41115 19.32789 0.30273 7.31963
November 489.00000 24.23719 20.12219 0.23452 6.40905
December 497.00000 23.69267 14.58757 0.03793 5.96784
           
Annual Sum or Average 5943.00000 24.24725 23.36865 -0.0679 7.50970
Minimum of Months 454.00000 23.69267 14.58757 -0.4896 5.81631
Maximum of Months 514.00000 24.51997 34.48220 0.30273 10.80866



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.61143 21.78046 -0.1733 7.14858
February 454.00000 22.65433 19.89803 -0.1789 7.49447
March 514.00000 23.12051 19.57604 -0.0517 6.39080
April 485.00000 23.30350 23.40470 0.01793 6.16298
May 508.00000 24.12685 25.69130 -0.6292 13.89049
June 496.00000 24.28403 33.55257 -0.4595 9.74898
July 497.00000 24.34371 35.34180 -0.4273 9.17201
August 514.00000 24.30095 34.01229 -0.4528 9.64471
September 485.00000 24.27081 25.29240 -0.5434 11.77288
October 502.00000 23.70111 20.72939 0.11414 6.28667
November 489.00000 23.13268 22.66399 -0.0333 6.01055
December 497.00000 22.20949 16.38844 -0.3087 9.15102
           
Annual Sum or Average 5943.00000 23.51208 24.90695 -0.2616 8.58585
Minimum of Months 454.00000 22.20949 16.38844 -0.6292 6.01055
Maximum of Months 514.00000 24.34371 35.34180 0.11414 13.89049



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.67537 22.67963 -0.4132 11.10915
February 454.00000 21.83341 20.71306 -0.3902 11.05549
March 514.00000 22.45018 20.07328 -0.2223 8.82890
April 485.00000 22.65673 24.23189 -0.1419 7.96630
May 508.00000 23.88140 25.86970 -0.7169 16.92029
June 496.00000 24.26209 33.31874 -0.4611 9.82148
July 497.00000 24.33469 35.16990 -0.4256 9.21645
August 514.00000 24.25793 33.93004 -0.4654 9.87102
September 485.00000 24.11981 25.23380 -0.6049 13.64838
October 502.00000 23.01837 21.60951 -0.0639 7.09107
November 489.00000 22.20683 23.94212 -0.2673 8.32965
December 497.00000 21.30088 17.18578 -0.5464 14.04509
           
Annual Sum or Average 5943.00000 23.01009 25.37133 -0.3936 10.65989
Minimum of Months 454.00000 21.30088 17.18578 -0.7169 7.09107
Maximum of Months 514.00000 24.33469 35.16990 -0.0639 16.92029



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.53994 25.06656 -0.7160 18.73885
February 454.00000 20.70989 22.79261 -0.6911 18.02682
March 514.00000 21.52219 21.94392 -0.4602 13.30966
April 485.00000 21.75887 25.86166 -0.3552 12.07557
May 508.00000 23.57483 27.09589 -0.8019 21.08129
June 496.00000 24.30122 33.36460 -0.3976 9.20866
July 497.00000 24.40482 35.31614 -0.3536 8.79155
August 514.00000 24.19408 34.69390 -0.4557 10.25797
September 485.00000 23.85972 26.31983 -0.6809 17.49610
October 502.00000 22.04914 24.07635 -0.3054 10.29085
November 489.00000 21.08342 26.36556 -0.5600 13.96506
December 497.00000 20.25847 18.45732 -0.8428 22.84699
           
Annual Sum or Average 5943.00000 22.36952 26.81628 -0.5507 14.64634
Minimum of Months 454.00000 20.25847 18.45732 -0.8428 8.79155
Maximum of Months 514.00000 24.40482 35.31614 -0.3054 22.84699



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.22444 24.93904 -0.5291 14.61713
February 454.00000 21.53066 22.39526 -0.4638 14.89959
March 514.00000 22.21524 20.96032 -0.2545 11.85341
April 485.00000 22.29090 24.84315 -0.1868 11.49652
May 508.00000 23.92252 26.05531 -0.6111 15.69354
June 496.00000 24.42418 32.76266 -0.2394 7.80370
July 497.00000 24.56950 34.82085 -0.1924 8.03108
August 514.00000 24.33842 33.88239 -0.2834 8.50405
September 485.00000 24.16650 25.39619 -0.4815 13.07372
October 502.00000 22.67401 22.88933 -0.1279 10.43870
November 489.00000 21.73384 25.88899 -0.3828 11.54754
December 497.00000 20.82601 18.87101 -0.6854 19.10501
           
Annual Sum or Average 5943.00000 22.83843 26.17592 -0.3691 12.23272
Minimum of Months 454.00000 20.82601 18.87101 -0.6854 7.80370
Maximum of Months 514.00000 24.56950 34.82085 -0.1279 19.10501



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.30679 21.29473 -0.2070 12.61699
February 454.00000 22.22097 19.51937 -0.2407 14.14292
March 514.00000 22.37573 19.60290 -0.1898 12.22907
April 485.00000 22.14921 24.38841 -0.2257 11.90255
May 508.00000 23.67537 26.45593 -0.7319 19.67200
June 496.00000 24.27313 33.30210 -0.3807 9.51223
July 497.00000 24.41255 35.16056 -0.3166 8.96070
August 514.00000 24.27949 34.08661 -0.3442 9.26592
September 485.00000 24.14229 25.04118 -0.4645 13.74353
October 502.00000 22.91011 21.32599 -0.0153 11.79171
November 489.00000 22.66888 22.50005 -0.0968 11.54858
December 497.00000 21.84045 16.07461 -0.3807 15.68240
           
Annual Sum or Average 5943.00000 23.11270 24.94548 -0.3003 12.58071
Minimum of Months 454.00000 21.84045 16.07461 -0.7319 8.96070
Maximum of Months 514.00000 24.41255 35.16056 -0.0153 19.67200



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.17756 24.44313 -0.5402 15.84984
February 454.00000 21.37016 22.08697 -0.5048 15.88494
March 514.00000 21.96286 21.48706 -0.3176 12.78505
April 485.00000 22.04169 25.57300 -0.2535 12.17470
May 508.00000 23.72321 26.89153 -0.6923 19.13154
June 496.00000 24.33554 33.34277 -0.3020 9.15082
July 497.00000 24.43598 35.31003 -0.2825 8.74583
August 514.00000 24.28056 34.51505 -0.3461 9.41165
September 485.00000 24.02567 25.99890 -0.5514 15.59576
October 502.00000 22.43409 23.46101 -0.1752 10.97105
November 489.00000 21.67412 25.68760 -0.3952 12.39625
December 497.00000 20.78064 18.38693 -0.6984 20.06515
           
Annual Sum or Average 5943.00000 22.69898 26.47154 -0.4210 13.49354
Minimum of Months 454.00000 20.78064 18.38693 -0.6984 8.74583
Maximum of Months 514.00000 24.43598 35.31003 -0.1752 20.06515



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.75245 25.33850 -0.6491 15.36493
February 454.00000 20.77237 22.83897 -0.6691 15.99861
March 514.00000 21.39753 22.58057 -0.4898 11.95168
April 485.00000 21.75405 26.97213 -0.3578 9.62466
May 508.00000 23.50181 28.17411 -0.8651 22.47460
June 496.00000 24.23369 33.82114 -0.4672 9.90972
July 497.00000 24.32449 35.57719 -0.4232 9.21367
August 514.00000 24.20808 34.67259 -0.4787 10.14466
September 485.00000 24.07575 26.23289 -0.6091 14.05763
October 502.00000 22.69878 23.90527 -0.1281 7.20555
November 489.00000 21.62051 25.87966 -0.3996 9.70406
December 497.00000 20.68467 18.57751 -0.7038 17.30310
           
Annual Sum or Average 5943.00000 22.51602 27.08726 -0.5195 12.73660
Minimum of Months 454.00000 20.68467 18.57751 -0.8651 7.20555
Maximum of Months 514.00000 24.32449 35.57719 -0.1281 22.47460



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.62134 25.18541 -0.4156 10.91136
February 454.00000 21.78662 22.38965 -0.3946 12.18082
March 514.00000 22.39720 21.33073 -0.2128 9.59734
April 485.00000 22.62967 25.36206 -0.1130 8.46447
May 508.00000 24.00997 26.61165 -0.6184 14.91398
June 496.00000 24.44432 32.87153 -0.2726 7.57582
July 497.00000 24.58652 34.76051 -0.2251 7.56329
August 514.00000 24.42490 33.56006 -0.2732 7.71459
September 485.00000 24.38977 25.14441 -0.3954 10.03200
October 502.00000 23.37382 22.48102 0.06647 8.11419
November 489.00000 22.48099 25.01560 -0.1752 7.99247
December 497.00000 21.43440 18.90755 -0.5052 13.36008
           
Annual Sum or Average 5943.00000 23.14264 26.17056 -0.2943 9.85886
Minimum of Months 454.00000 21.43440 18.90755 -0.6184 7.56329
Maximum of Months 514.00000 24.58652 34.76051 0.06647 14.91398



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.46528 20.09729 -0.1141 10.60018
February 454.00000 22.10881 18.28785 -0.2216 12.97743
March 514.00000 22.20009 18.79314 -0.2093 10.85454
April 485.00000 22.00420 24.09236 -0.2462 9.53969
May 508.00000 23.34459 26.88560 -0.8608 23.41579
June 496.00000 24.19097 33.18358 -0.4557 10.36527
July 497.00000 24.34289 35.15405 -0.3818 9.25910
August 514.00000 24.30747 33.43470 -0.3553 8.96697
September 485.00000 24.32450 24.44062 -0.3848 10.98796
October 502.00000 23.31089 20.20695 0.12959 10.90177
November 489.00000 22.94882 20.78269 0.03397 10.32204
December 497.00000 21.90219 14.54303 -0.2915 13.92687
           
Annual Sum or Average 5943.00000 23.12887 24.21305 -0.2811 11.85213
Minimum of Months 454.00000 21.90219 14.54303 -0.8608 8.96697
Maximum of Months 514.00000 24.34289 35.15405 0.12959 23.41579



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.56208 24.85301 -0.4281 11.53476
February 454.00000 21.63395 22.24432 -0.4318 12.48229
March 514.00000 22.15518 21.82797 -0.2758 10.15297
April 485.00000 22.39687 26.15759 -0.1787 8.69406
May 508.00000 23.87105 27.34389 -0.6870 17.28246
June 496.00000 24.39148 33.37114 -0.3243 8.41424
July 497.00000 24.46508 35.28110 -0.3137 8.17193
August 514.00000 24.39270 34.12450 -0.3306 8.34599
September 485.00000 24.34558 25.50537 -0.4389 11.08149
October 502.00000 23.28857 22.76906 0.04902 8.02866
November 489.00000 22.43780 24.89133 -0.1833 8.10486
December 497.00000 21.33896 18.58971 -0.5266 14.12321
           
Annual Sum or Average 5943.00000 23.03448 26.45293 -0.3390 10.53076
Minimum of Months 454.00000 21.33896 18.58971 -0.6870 8.02866
Maximum of Months 514.00000 24.46508 35.28110 0.04902 17.28246



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.06564 24.69571 -0.5550 13.64445
February 454.00000 21.12158 22.28797 -0.5583 14.13086
March 514.00000 21.91455 21.49763 -0.3419 10.36845
April 485.00000 22.26899 25.26081 -0.2203 8.74412
May 508.00000 23.83926 26.73878 -0.7086 17.12956
June 496.00000 24.34662 33.45893 -0.3898 8.79838
July 497.00000 24.44560 35.31861 -0.3471 8.34791
August 514.00000 24.26707 34.57879 -0.4355 9.51507
September 485.00000 24.06308 26.18260 -0.6066 14.40517
October 502.00000 22.62377 23.43092 -0.1481 7.78555
November 489.00000 21.62804 25.72190 -0.3975 10.07774
December 497.00000 20.70278 18.31253 -0.6949 17.65577
           
Annual Sum or Average 5943.00000 22.70416 26.49558 -0.4497 11.70090
Minimum of Months 454.00000 20.70278 18.31253 -0.7086 7.78555
Maximum of Months 514.00000 24.44560 35.31861 -0.1481 17.65577



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 21.64625 24.31421 -0.4004 11.24947
February 385.00000 21.80500 21.73048 -0.3700 12.69673
March 433.00000 22.43178 20.41278 -0.1842 10.20191
April 410.00000 22.62336 24.43053 -0.0984 9.07674
May 430.00000 24.13022 25.90161 -0.5502 13.68307
June 418.00000 24.54270 32.61976 -0.2319 7.79127
July 422.00000 24.70903 34.46261 -0.1790 7.97816
August 433.00000 24.47085 33.72215 -0.2733 8.33951
September 410.00000 24.34818 25.25923 -0.4367 11.74641
October 427.00000 23.06361 22.25524 -0.0184 9.05783
November 417.00000 22.19038 25.10434 -0.2483 9.17819
December 422.00000 21.17889 18.32618 -0.5674 15.53458
           
Annual Sum or Average 5034.00000 23.10412 25.74151 -0.2961 10.53149
Minimum of Months 385.00000 21.17889 18.32618 -0.5674 7.79127
Maximum of Months 433.00000 24.70903 34.46261 -0.0184 15.53458



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.80665 20.81662 -0.0552 10.28729
February 454.00000 22.64364 18.84841 -0.1106 11.85427
March 514.00000 22.73562 19.08997 -0.0811 10.14297
April 485.00000 22.65679 23.72400 -0.0934 8.78007
May 508.00000 23.92730 26.11570 -0.6433 15.89312
June 496.00000 24.33888 33.35159 -0.3681 8.85576
July 497.00000 24.46868 35.11862 -0.3070 8.34420
August 514.00000 24.36014 33.94763 -0.3241 8.48851
September 485.00000 24.31214 25.00121 -0.4024 11.36058
October 502.00000 23.36731 20.83583 0.11618 10.31395
November 489.00000 23.15293 21.81251 0.04933 10.02849
December 497.00000 22.34086 15.62965 -0.2272 12.42502
           
Annual Sum or Average 5943.00000 23.43261 24.57633 -0.2051 10.56047
Minimum of Months 454.00000 22.34086 15.62965 -0.6433 8.34420
Maximum of Months 514.00000 24.46868 35.11862 0.11618 15.89312



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.70477 24.04562 -0.3809 11.60926
February 454.00000 21.79282 21.56507 -0.3719 12.61814
March 514.00000 22.35749 21.01518 -0.2007 10.24673
April 485.00000 22.56361 24.93898 -0.1180 8.97021
May 508.00000 23.98195 26.50131 -0.6021 15.29225
June 496.00000 24.39948 33.38925 -0.2901 8.46380
July 497.00000 24.49266 35.28190 -0.2725 8.11086
August 514.00000 24.36275 34.37364 -0.3249 8.60969
September 485.00000 24.22113 25.85649 -0.4811 12.73006
October 502.00000 22.97418 22.87485 -0.0263 8.81672
November 489.00000 22.21705 25.01424 -0.2353 9.25428
December 497.00000 21.23737 18.17073 -0.5502 15.51730
           
Annual Sum or Average 5943.00000 23.03626 26.12686 -0.3210 10.84206
Minimum of Months 454.00000 21.23737 18.17073 -0.6021 8.11086
Maximum of Months 514.00000 24.49266 35.28190 -0.0263 15.51730



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.398497E+11 0.00 341.30 182308.07 05-JAN-07:11 0.00 35.75 46.52 0.19 0.00 0.05 0.60 05-JAN-07:11
February 0.429979E+11 0.00 340.55 177024.32 06-FEB-07:05 0.00 35.92 46.94 0.24 0.00 0.06 0.58 06-FEB-07:05
March 0.263038E+11 0.00 290.16 168082.15 30-MAR-06:01 0.00 35.64 44.92 0.11 0.00 0.03 0.55 30-MAR-06:01
April 0.159589E+11 0.00 225.35 167784.06 25-APR-06:02 0.00 33.52 41.59 0.07 0.00 0.02 0.55 25-APR-06:02
May 0.168971E+10 0.00 63.30 157001.58 02-MAY-06:02 0.00 38.80 40.72 0.01 0.00 0.00 0.52 02-MAY-06:02
June 11591610.79 0.00 42.24 9177.60 09-JUN-06:06 0.00 42.65 43.68 0.00 0.00 0.00 0.03 09-JUN-06:06
July 2271479.42 0.00 75.94 1307.03 03-JUL-06:07 0.00 40.45 42.48 0.00 0.00 0.00 0.00 03-JUL-06:07
August 1799552.16 0.00 54.55 4909.15 23-AUG-06:08 0.00 39.46 40.96 0.00 0.00 0.00 0.02 23-AUG-06:08
September 0.780668E+09 0.00 25.44 98841.74 22-SEP-06:02 0.00 35.89 36.77 0.00 0.00 0.00 0.33 22-SEP-06:02
October 0.184904E+11 0.00 197.14 163006.61 30-OCT-06:02 0.00 31.22 37.74 0.09 0.00 0.02 0.54 30-OCT-06:02
November 0.289290E+11 0.00 279.39 167205.05 30-NOV-07:12 0.00 33.19 42.67 0.14 0.00 0.04 0.55 30-NOV-07:12
December 0.592499E+11 0.00 405.72 196516.58 23-DEC-07:15 0.00 36.91 48.71 0.30 0.00 0.07 0.65 23-DEC-07:15
                           
Annual Sum or Average 0.234266E+12 0.00 2341.08     0.00 36.63 42.79 0.10 0.00 0.02    
Minimum of Months 1799552.16 0.00 25.44 1307.03   0.00 31.22 36.77 0.00 0.00 0.00 0.00  
Maximum of Months 0.592499E+11 0.00 405.72 196516.58   0.00 42.65 48.71 0.30 0.00 0.07 0.65  



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.314348E+10 0.731237E+09 72.48 0.312868E+10 14796303.01 0.00 0.97 23-JAN-16:00 0.00 01-JAN-00:10 30392.94 23-JAN-16:00 30392.94 23-JAN-16:00 852.42 19-JAN-12:10 6445.21 23-JAN-16:00 0.00
February 0.136758E+10 0.342999E+09 66.92 0.135076E+10 16822020.00 0.00 0.62 18-FEB-12:00 0.00 01-FEB-00:10 17744.35 18-FEB-12:00 17744.35 18-FEB-12:00 826.52 23-FEB-12:02 4144.88 18-FEB-12:00 0.00
March 0.402132E+10 0.936693E+09 107.83 0.401559E+10 5737525.73 0.00 1.00 13-MAR-13:05 0.00 01-MAR-00:10 39904.80 13-MAR-16:00 39904.80 13-MAR-16:00 1422.31 17-MAR-16:06 8376.66 13-MAR-16:00 0.00
April 0.509721E+10 0.122172E+10 147.62 0.497912E+10 0.118085E+09 0.00 1.00 12-APR-14:05 0.00 01-APR-00:10 32361.04 12-APR-14:10 32361.04 12-APR-14:10 2768.27 28-APR-14:05 6795.66 12-APR-14:10 0.00
May 0.146845E+11 0.337197E+10 239.25 0.143920E+11 0.292504E+09 0.00 1.00 04-MAY-14:05 0.00 01-MAY-00:10 50268.62 31-MAY-16:00 50268.62 31-MAY-16:00 3408.98 31-MAY-06:02 11714.86 31-MAY-16:00 0.00
June 0.544203E+11 0.132068E+11 436.76 0.519154E+11 0.250491E+10 0.00 1.00 01-JUN-10:05 0.00 01-JUN-00:10 79419.84 26-JUN-15:20 79419.84 26-JUN-15:20 24257.04 21-JUN-06:03 25855.70 26-JUN-15:10 0.00
July 0.553920E+11 0.132397E+11 447.14 0.510377E+11 0.435437E+10 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 75230.76 31-JUL-15:00 74546.41 17-JUL-10:50 35372.73 31-JUL-15:50 21151.94 17-JUL-10:50 0.00
August 0.546399E+11 0.130042E+11 439.20 0.518616E+11 0.277835E+10 0.00 1.00 01-AUG-12:05 0.00 01-AUG-00:10 73265.48 16-AUG-16:00 73265.48 16-AUG-16:00 35030.04 04-AUG-06:03 22228.17 16-AUG-16:00 0.00
September 0.382332E+11 0.880886E+10 376.03 0.376675E+11 0.565726E+09 0.00 1.00 01-SEP-09:50 0.00 01-SEP-00:10 66039.18 11-SEP-15:00 66039.18 11-SEP-15:00 10140.80 01-SEP-14:00 16757.09 12-SEP-16:00 0.00
October 0.126580E+11 0.286438E+10 214.67 0.125555E+11 0.102541E+09 0.00 1.00 10-OCT-09:50 0.00 01-OCT-00:10 57947.80 10-OCT-15:30 57947.80 10-OCT-15:30 1662.24 03-OCT-11:10 12583.46 11-OCT-14:20 0.00
November 0.369644E+10 0.869563E+09 96.60 0.366147E+10 34962973.62 0.00 1.00 07-NOV-14:50 0.00 01-NOV-00:10 33472.00 07-NOV-15:10 33472.00 07-NOV-15:10 1083.27 13-NOV-13:05 7028.56 07-NOV-15:10 0.00
December 0.154664E+10 0.378443E+09 59.55 0.154446E+10 2174863.17 0.00 0.76 14-DEC-15:10 0.00 01-DEC-00:10 22425.20 14-DEC-15:10 22425.20 14-DEC-15:10 349.53 29-DEC-12:02 5048.62 14-DEC-15:10 0.00
                                       
Annual Sum or Average 0.248901E+12 0.589765E+11 2704.05 0.238110E+12 0.107910E+11 0.00                         0.00
Minimum of Months 0.136758E+10 0.342999E+09 59.55 0.135076E+10 2174863.17 0.00 0.62   0.00   17744.35   17744.35   349.53   4144.88   0.00
Maximum of Months 0.553920E+11 0.132397E+11 447.14 0.519154E+11 0.435437E+10 0.00 1.00   0.00   79419.84   79419.84   35372.73   25855.70   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.191206E+10 0.458272E+09 55.36 0.189717E+10 14894811.37 0.00 0.83 24-JAN-15:05 0.00 01-JAN-00:10 23810.02 24-JAN-15:05 23810.02 24-JAN-15:05 1303.75 27-JAN-13:30 5245.93 24-JAN-15:05 0.00
February 0.109316E+10 0.276591E+09 59.65 0.106654E+10 26617640.03 0.00 0.60 18-FEB-13:05 0.00 01-FEB-00:10 16170.44 18-FEB-13:05 16170.44 18-FEB-13:05 1123.96 23-FEB-12:02 3795.47 18-FEB-13:05 0.00
March 0.379707E+10 0.877538E+09 98.45 0.379381E+10 3265966.89 0.00 1.00 13-MAR-13:10 0.00 01-MAR-00:10 39256.56 13-MAR-15:50 39256.56 13-MAR-15:50 561.16 17-MAR-13:00 8239.88 13-MAR-15:50 0.00
April 0.286784E+10 0.691911E+09 95.85 0.282950E+10 38334912.57 0.00 0.89 20-APR-13:00 0.00 01-APR-00:10 25973.13 20-APR-13:00 25973.13 20-APR-13:00 2754.29 28-APR-14:00 5624.87 20-APR-13:00 0.00
May 0.136546E+11 0.313400E+10 241.50 0.132965E+11 0.358030E+09 0.00 1.00 04-MAY-13:50 0.00 01-MAY-00:10 49588.52 16-MAY-14:05 49588.52 16-MAY-14:05 2873.66 31-MAY-07:40 11503.55 16-MAY-14:05 0.00
June 0.498065E+11 0.121206E+11 437.03 0.475471E+11 0.225939E+10 0.00 1.00 01-JUN-09:00 0.00 01-JUN-00:10 74659.79 26-JUN-15:20 74659.79 26-JUN-15:20 16349.59 22-JUN-13:20 24360.52 26-JUN-15:00 0.00
July 0.505299E+11 0.121250E+11 445.11 0.466782E+11 0.385169E+10 0.00 1.00 01-JUL-06:03 0.00 01-JUL-00:10 71081.58 17-JUL-12:02 71081.58 17-JUL-12:02 32390.00 31-JUL-15:50 20904.47 17-JUL-12:02 0.00
August 0.480937E+11 0.115112E+11 433.29 0.456987E+11 0.239498E+10 0.00 1.00 01-AUG-12:05 0.00 01-AUG-00:10 69079.10 16-AUG-15:00 69079.10 16-AUG-15:00 21339.96 28-AUG-06:02 20396.33 16-AUG-14:05 0.00
September 0.319416E+11 0.741230E+10 358.74 0.314364E+11 0.505186E+09 0.00 1.00 01-SEP-10:00 0.00 01-SEP-00:10 61891.57 11-SEP-14:05 61891.57 11-SEP-14:05 8685.21 01-SEP-14:00 15495.54 12-SEP-15:50 0.00
October 0.768924E+10 0.176240E+10 146.25 0.764880E+10 40435028.15 0.00 1.00 10-OCT-10:05 0.00 01-OCT-00:10 51501.14 11-OCT-14:05 51501.14 11-OCT-14:05 2106.67 03-OCT-11:05 11636.14 11-OCT-14:05 0.00
November 0.308199E+10 0.732719E+09 83.81 0.304506E+10 36928835.25 0.00 1.00 07-NOV-15:05 0.00 01-NOV-00:10 31041.87 07-NOV-15:05 31041.87 07-NOV-15:05 1129.55 14-NOV-13:04 6518.46 07-NOV-15:05 0.00
December 0.125716E+10 0.311896E+09 56.27 0.125278E+10 4373873.23 0.00 0.72 01-DEC-14:00 0.00 01-DEC-00:10 19858.56 01-DEC-14:00 19858.56 01-DEC-14:00 234.26 29-DEC-12:50 4518.64 01-DEC-14:00 0.00
                                       
Annual Sum or Average 0.215725E+12 0.514145E+11 2511.32 0.206191E+12 0.953413E+10 0.00                         0.00
Minimum of Months 0.109316E+10 0.276591E+09 55.36 0.106654E+10 3265966.89 0.00 0.60   0.00   16170.44   16170.44   234.26   3795.47   0.00
Maximum of Months 0.505299E+11 0.121250E+11 445.11 0.475471E+11 0.385169E+10 0.00 1.00   0.00   74659.79   74659.79   32390.00   24360.52   0.00



Table of Contents

Report: DXReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.103896E+10 0.258572E+09 42.86 0.102037E+10 18589675.31 0.00 0.66 20-JAN-14:10 0.00 01-JAN-00:10 20908.44 20-JAN-14:10 20908.44 20-JAN-14:10 1067.27 27-JAN-14:00 4836.44 20-JAN-14:10 0.00
February 0.144632E+10 0.364467E+09 63.44 0.141805E+10 28267742.95 0.00 0.65 27-FEB-15:10 0.00 01-FEB-00:10 20579.08 27-FEB-15:10 20579.08 27-FEB-15:10 1043.25 23-FEB-13:15 4771.58 27-FEB-15:10 0.00
March 0.371211E+10 0.866755E+09 91.52 0.370895E+10 3158518.84 0.00 1.00 13-MAR-13:40 0.00 01-MAR-00:10 40700.12 13-MAR-15:50 40700.12 13-MAR-15:50 477.84 30-MAR-16:25 8544.88 13-MAR-15:50 0.00
April 0.279370E+10 0.678581E+09 87.96 0.274271E+10 50988402.24 0.00 0.84 20-APR-13:00 0.00 01-APR-00:10 27866.88 20-APR-13:00 27866.88 20-APR-13:00 3098.10 28-APR-14:00 6138.08 20-APR-13:00 0.00
May 0.145211E+11 0.336416E+10 242.36 0.140220E+11 0.499060E+09 0.00 1.00 04-MAY-13:50 0.00 01-MAY-00:10 57976.35 31-MAY-15:20 57976.35 31-MAY-15:20 3433.40 31-MAY-08:00 13509.51 31-MAY-15:20 0.00
June 0.543468E+11 0.133403E+11 439.16 0.518699E+11 0.247691E+10 0.00 1.00 01-JUN-10:30 0.00 01-JUN-00:10 86490.00 26-JUN-15:10 86490.00 26-JUN-15:10 17569.78 22-JUN-13:20 28269.14 26-JUN-15:00 0.00
July 0.544878E+11 0.132049E+11 448.09 0.504002E+11 0.408761E+10 0.00 1.00 01-JUL-08:40 0.00 01-JUL-00:10 79826.75 31-JUL-14:20 78931.08 17-JUL-14:00 33137.27 31-JUL-15:40 22797.58 17-JUL-13:10 0.00
August 0.520154E+11 0.125756E+11 433.84 0.494835E+11 0.253182E+10 0.00 1.00 02-AUG-09:50 0.00 01-AUG-00:10 81807.74 16-AUG-15:10 81807.74 16-AUG-15:10 17273.98 21-AUG-16:00 24184.77 16-AUG-15:10 0.00
September 0.329507E+11 0.773362E+10 360.20 0.322795E+11 0.671220E+09 0.00 1.00 01-SEP-10:50 0.00 01-SEP-00:10 69392.85 12-SEP-15:40 69392.85 12-SEP-15:40 8358.66 01-SEP-14:00 17339.39 12-SEP-15:40 0.00
October 0.658264E+10 0.153115E+10 127.02 0.654088E+10 41754987.44 0.00 1.00 10-OCT-12:05 0.00 01-OCT-00:10 56377.08 11-OCT-15:00 56377.08 11-OCT-15:00 1262.94 01-OCT-12:22 12553.71 11-OCT-14:30 0.00
November 0.263198E+10 0.638515E+09 76.17 0.258597E+10 46008545.10 0.00 0.89 07-NOV-14:50 0.00 01-NOV-00:10 30079.51 07-NOV-14:50 30079.51 07-NOV-14:50 975.80 14-NOV-15:40 6526.30 07-NOV-14:50 0.00
December 0.107413E+10 0.270994E+09 49.78 0.106662E+10 7509706.17 0.00 0.60 01-DEC-14:00 0.00 01-DEC-00:10 18784.53 01-DEC-14:00 18784.53 01-DEC-14:00 440.66 29-DEC-16:20 4412.72 01-DEC-14:00 0.00
                                       
Annual Sum or Average 0.227602E+12 0.548275E+11 2462.38 0.217139E+12 0.104629E+11 0.00                         0.00
Minimum of Months 0.103896E+10 0.258572E+09 42.86 0.102037E+10 3158518.84 0.00 0.60   0.00   18784.53   18784.53   440.66   4412.72   0.00
Maximum of Months 0.544878E+11 0.133403E+11 448.09 0.518699E+11 0.408761E+10 0.00 1.00   0.00   86490.00   86490.00   33137.27   28269.14   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 384.46 0.00 384.46 83.06 1772.98 0.00 0.00 0.00
February 483.22 0.00 483.22 99.93 1808.66 0.00 0.00 0.00
March 657.51 0.00 657.51 311.28 1374.40 0.00 0.00 0.00
April 825.73 4.58 821.15 467.69 1175.66 0.00 0.00 0.00
May 1128.00 37.29 1090.72 1027.53 719.71 0.00 0.00 0.00
June 1236.93 137.13 1099.80 1641.16 405.22 0.00 0.00 0.00
July 1169.80 75.72 1094.08 1569.52 384.29 0.00 0.00 0.00
August 931.07 22.03 909.05 1194.59 438.08 0.00 0.00 0.00
September 782.10 0.18 781.92 886.37 671.60 0.00 0.00 0.00
October 560.17 0.00 560.17 316.54 1363.20 0.00 0.00 0.00
November 425.24 0.00 425.24 130.77 1611.85 0.00 0.00 0.00
December 359.71 0.00 359.71 70.53 1996.89 0.00 0.00 0.00
                 
Annual Sum or Average 746.69 23.13 723.56 652.99 1140.02 0.00 0.00 0.00
Minimum of Months 359.71 0.00 359.71 70.53 384.29 0.00 0.00 0.00
Maximum of Months 1236.93 137.13 1099.80 1641.16 1996.89 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 802.58 491.85 310.74 728.52 1113.45 0.00 0.00 0.00
February 1066.14 673.05 393.09 1012.28 1158.98 0.00 0.00 0.00
March 1286.81 750.58 536.22 1312.87 885.91 0.00 0.00 0.00
April 1319.69 642.84 676.85 1317.64 767.85 0.00 0.00 0.00
May 1542.70 644.39 898.31 1749.61 487.26 0.00 0.00 0.00
June 1882.25 988.13 894.12 2522.13 272.56 0.00 0.00 0.00
July 1711.11 814.79 896.32 2311.75 258.47 0.00 0.00 0.00
August 1725.89 950.56 775.33 2319.12 294.17 0.00 0.00 0.00
September 1436.03 780.09 655.94 1830.87 433.00 0.00 0.00 0.00
October 1039.97 569.84 470.13 1096.09 893.36 0.00 0.00 0.00
November 809.48 457.04 352.44 771.07 1041.32 0.00 0.00 0.00
December 700.80 403.71 297.09 607.93 1265.97 0.00 0.00 0.00
                 
Annual Sum or Average 1277.76 680.24 597.52 1467.12 737.12 0.00 0.00 0.00
Minimum of Months 700.80 403.71 297.09 607.93 258.47 0.00 0.00 0.00
Maximum of Months 1882.25 988.13 898.31 2522.13 1265.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3684.63 3031.01 653.63 4240.57 1623.46 0.00 0.00 0.00
February 3534.25 2817.72 716.52 4023.14 1697.83 0.00 0.00 0.00
March 2605.72 1714.42 891.30 3004.45 1353.80 0.00 0.00 0.00
April 1687.66 678.61 1009.04 1776.45 1213.45 0.00 0.00 0.00
May 1546.55 283.47 1263.08 1767.85 789.08 0.00 0.00 0.00
June 1425.87 260.61 1165.26 2050.01 443.19 0.00 0.00 0.00
July 1484.30 265.80 1218.50 2138.52 411.63 0.00 0.00 0.00
August 1889.81 790.01 1099.80 2741.07 462.75 0.00 0.00 0.00
September 2431.43 1356.72 1074.70 3310.04 691.33 0.00 0.00 0.00
October 2907.28 2062.78 844.50 3532.21 1358.64 0.00 0.00 0.00
November 3542.11 2823.58 718.53 4159.58 1551.77 0.00 0.00 0.00
December 3387.18 2741.54 645.64 3818.67 1817.50 0.00 0.00 0.00
                 
Annual Sum or Average 2504.77 1561.76 943.01 3041.30 1114.67 0.00 0.00 0.00
Minimum of Months 1425.87 260.61 645.64 1767.85 411.63 0.00 0.00 0.00
Maximum of Months 3684.63 3031.01 1263.08 4240.57 1817.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 853.77 540.99 312.77 826.42 1140.52 0.00 0.00 0.00
February 1029.52 638.00 391.52 981.97 1173.03 0.00 0.00 0.00
March 1205.51 665.11 540.40 1220.63 902.91 0.00 0.00 0.00
April 1135.04 480.56 654.48 1098.78 787.18 0.00 0.00 0.00
May 1387.31 489.08 898.23 1575.87 516.10 0.00 0.00 0.00
June 1696.77 816.38 880.39 2304.39 305.46 0.00 0.00 0.00
July 1382.46 506.37 876.09 1881.86 280.11 0.00 0.00 0.00
August 1442.90 712.81 730.09 1938.64 311.70 0.00 0.00 0.00
September 1279.42 613.57 665.85 1644.23 462.38 0.00 0.00 0.00
October 1076.33 615.20 461.13 1172.32 909.21 0.00 0.00 0.00
November 883.19 536.20 346.98 875.95 1054.14 0.00 0.00 0.00
December 713.37 421.41 291.96 632.52 1270.00 0.00 0.00 0.00
                 
Annual Sum or Average 1174.16 585.60 588.56 1347.65 757.17 0.00 0.00 0.00
Minimum of Months 713.37 421.41 291.96 632.52 280.11 0.00 0.00 0.00
Maximum of Months 1696.77 816.38 898.23 2304.39 1270.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.15 0.00 128.15 27.67 609.82 0.00 0.00 0.00
February 161.07 0.00 161.07 35.71 613.77 0.00 0.00 0.00
March 219.16 0.00 219.16 110.98 463.48 0.00 0.00 0.00
April 275.23 1.53 273.70 163.57 402.07 0.00 0.00 0.00
May 375.98 12.43 363.55 352.90 237.69 0.00 0.00 0.00
June 412.29 45.71 366.58 556.51 132.77 0.00 0.00 0.00
July 389.92 25.24 364.68 532.30 125.24 0.00 0.00 0.00
August 310.34 7.34 303.00 402.97 147.35 0.00 0.00 0.00
September 260.69 0.06 260.63 295.46 235.10 0.00 0.00 0.00
October 186.72 0.00 186.72 102.18 486.59 0.00 0.00 0.00
November 141.74 0.00 141.74 40.31 571.75 0.00 0.00 0.00
December 119.90 0.00 119.90 22.18 696.70 0.00 0.00 0.00
                 
Annual Sum or Average 248.89 7.71 241.18 221.27 392.35 0.00 0.00 0.00
Minimum of Months 119.90 0.00 119.90 22.18 125.24 0.00 0.00 0.00
Maximum of Months 412.29 45.71 366.58 556.51 696.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.15 0.00 128.15 27.67 609.86 0.00 0.00 0.00
February 161.07 0.00 161.07 35.71 613.81 0.00 0.00 0.00
March 219.17 0.00 219.17 110.98 463.51 0.00 0.00 0.00
April 275.24 1.53 273.72 163.58 402.10 0.00 0.00 0.00
May 376.00 12.43 363.57 352.91 237.70 0.00 0.00 0.00
June 412.31 45.71 366.60 556.54 132.78 0.00 0.00 0.00
July 389.93 25.24 364.69 532.32 125.25 0.00 0.00 0.00
August 310.36 7.34 303.01 402.99 147.36 0.00 0.00 0.00
September 260.70 0.06 260.64 295.48 235.11 0.00 0.00 0.00
October 186.72 0.00 186.72 102.18 486.62 0.00 0.00 0.00
November 141.75 0.00 141.75 40.31 571.78 0.00 0.00 0.00
December 119.90 0.00 119.90 22.18 696.74 0.00 0.00 0.00
                 
Annual Sum or Average 248.90 7.71 241.19 221.27 392.38 0.00 0.00 0.00
Minimum of Months 119.90 0.00 119.90 22.18 125.25 0.00 0.00 0.00
Maximum of Months 412.31 45.71 366.60 556.54 696.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 128.15 0.00 128.15 27.67 609.86 0.00 0.00 0.00
February 161.07 0.00 161.07 35.71 613.81 0.00 0.00 0.00
March 219.17 0.00 219.17 110.98 463.51 0.00 0.00 0.00
April 275.24 1.53 273.72 163.58 402.10 0.00 0.00 0.00
May 376.00 12.43 363.57 352.91 237.70 0.00 0.00 0.00
June 412.31 45.71 366.60 556.54 132.78 0.00 0.00 0.00
July 389.93 25.24 364.69 532.32 125.25 0.00 0.00 0.00
August 310.36 7.34 303.01 402.99 147.36 0.00 0.00 0.00
September 260.70 0.06 260.64 295.48 235.11 0.00 0.00 0.00
October 186.72 0.00 186.72 102.18 486.62 0.00 0.00 0.00
November 141.75 0.00 141.75 40.31 571.78 0.00 0.00 0.00
December 119.90 0.00 119.90 22.18 696.74 0.00 0.00 0.00
                 
Annual Sum or Average 248.90 7.71 241.19 221.27 392.38 0.00 0.00 0.00
Minimum of Months 119.90 0.00 119.90 22.18 125.25 0.00 0.00 0.00
Maximum of Months 412.31 45.71 366.60 556.54 696.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 772.04 473.13 298.91 697.55 1124.09 0.00 0.00 0.00
February 1025.58 647.44 378.14 979.05 1155.79 0.00 0.00 0.00
March 1237.84 722.02 515.82 1274.76 886.12 0.00 0.00 0.00
April 1269.47 618.38 651.09 1278.53 781.56 0.00 0.00 0.00
May 1484.00 619.87 864.13 1698.92 478.17 0.00 0.00 0.00
June 1810.63 950.53 860.10 2442.00 268.88 0.00 0.00 0.00
July 1646.00 783.78 862.22 2238.83 254.67 0.00 0.00 0.00
August 1660.22 914.39 745.83 2239.56 299.45 0.00 0.00 0.00
September 1381.39 750.41 630.98 1761.76 449.95 0.00 0.00 0.00
October 1000.40 548.16 452.24 1049.76 937.53 0.00 0.00 0.00
November 778.68 439.65 339.03 731.80 1083.38 0.00 0.00 0.00
December 674.13 388.35 285.78 578.54 1290.34 0.00 0.00 0.00
                 
Annual Sum or Average 1229.14 654.35 574.79 1416.30 748.65 0.00 0.00 0.00
Minimum of Months 674.13 388.35 285.78 578.54 254.67 0.00 0.00 0.00
Maximum of Months 1810.63 950.53 864.13 2442.00 1290.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.53 18.71 11.82 27.58 44.45 0.00 0.00 0.00
February 40.55 25.60 14.95 38.71 45.70 0.00 0.00 0.00
March 48.94 28.55 20.40 50.40 35.04 0.00 0.00 0.00
April 50.19 24.45 25.74 50.55 30.90 0.00 0.00 0.00
May 58.68 24.51 34.17 67.17 18.91 0.00 0.00 0.00
June 71.59 37.58 34.01 96.55 10.63 0.00 0.00 0.00
July 65.08 30.99 34.09 88.52 10.07 0.00 0.00 0.00
August 65.64 36.15 29.49 88.55 11.84 0.00 0.00 0.00
September 54.62 29.67 24.95 69.66 17.79 0.00 0.00 0.00
October 39.55 21.67 17.88 41.51 37.07 0.00 0.00 0.00
November 30.79 17.38 13.41 28.93 42.84 0.00 0.00 0.00
December 26.65 15.35 11.30 22.87 51.02 0.00 0.00 0.00
                 
Annual Sum or Average 48.60 25.87 22.73 56.00 29.60 0.00 0.00 0.00
Minimum of Months 26.65 15.35 11.30 22.87 10.07 0.00 0.00 0.00
Maximum of Months 71.59 37.58 34.17 96.55 51.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1228.19 1010.32 217.87 1415.79 586.71 0.00 0.00 0.00
February 1178.06 939.22 238.84 1351.02 601.23 0.00 0.00 0.00
March 868.56 571.46 297.10 1012.42 472.35 0.00 0.00 0.00
April 562.54 226.20 336.34 602.69 422.88 0.00 0.00 0.00
May 515.51 94.49 421.02 602.61 261.58 0.00 0.00 0.00
June 475.29 86.87 388.42 693.15 146.85 0.00 0.00 0.00
July 494.76 88.60 406.16 722.05 136.47 0.00 0.00 0.00
August 629.93 263.33 366.60 919.58 161.47 0.00 0.00 0.00
September 810.46 452.23 358.23 1105.77 251.21 0.00 0.00 0.00
October 969.08 687.58 281.50 1178.12 498.37 0.00 0.00 0.00
November 1180.68 941.17 239.51 1388.48 568.51 0.00 0.00 0.00
December 1129.04 913.83 215.21 1276.77 653.04 0.00 0.00 0.00
                 
Annual Sum or Average 834.91 520.58 314.33 1020.49 395.58 0.00 0.00 0.00
Minimum of Months 475.29 86.87 215.21 602.61 136.47 0.00 0.00 0.00
Maximum of Months 1228.19 1010.32 421.02 1415.79 653.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1228.19 1010.32 217.87 1415.79 586.71 0.00 0.00 0.00
February 1178.06 939.22 238.84 1351.02 601.23 0.00 0.00 0.00
March 868.56 571.46 297.10 1012.42 472.35 0.00 0.00 0.00
April 562.54 226.20 336.34 602.69 422.88 0.00 0.00 0.00
May 515.51 94.49 421.02 602.61 261.58 0.00 0.00 0.00
June 475.29 86.87 388.42 693.15 146.85 0.00 0.00 0.00
July 494.76 88.60 406.16 722.05 136.47 0.00 0.00 0.00
August 629.93 263.33 366.60 919.58 161.47 0.00 0.00 0.00
September 810.46 452.23 358.23 1105.77 251.21 0.00 0.00 0.00
October 969.08 687.58 281.50 1178.12 498.37 0.00 0.00 0.00
November 1180.68 941.17 239.51 1388.48 568.51 0.00 0.00 0.00
December 1129.04 913.83 215.21 1276.77 653.04 0.00 0.00 0.00
                 
Annual Sum or Average 834.91 520.58 314.33 1020.49 395.58 0.00 0.00 0.00
Minimum of Months 475.29 86.87 215.21 602.61 136.47 0.00 0.00 0.00
Maximum of Months 1228.19 1010.32 421.02 1415.79 653.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1228.11 1010.25 217.86 1415.70 586.67 0.00 0.00 0.00
February 1177.99 939.16 238.82 1350.93 601.19 0.00 0.00 0.00
March 868.50 571.42 297.08 1012.36 472.32 0.00 0.00 0.00
April 562.51 226.19 336.32 602.65 422.85 0.00 0.00 0.00
May 515.48 94.48 421.00 602.57 261.57 0.00 0.00 0.00
June 475.26 86.86 388.39 693.10 146.84 0.00 0.00 0.00
July 494.73 88.59 406.14 722.00 136.46 0.00 0.00 0.00
August 629.89 263.32 366.57 919.52 161.46 0.00 0.00 0.00
September 810.41 452.20 358.21 1105.70 251.19 0.00 0.00 0.00
October 969.01 687.54 281.48 1178.04 498.34 0.00 0.00 0.00
November 1180.61 941.11 239.49 1388.39 568.48 0.00 0.00 0.00
December 1128.97 913.77 215.20 1276.69 653.00 0.00 0.00 0.00
                 
Annual Sum or Average 834.86 520.54 314.31 1020.42 395.56 0.00 0.00 0.00
Minimum of Months 475.26 86.86 215.20 602.57 136.46 0.00 0.00 0.00
Maximum of Months 1228.11 1010.25 421.00 1415.70 653.00 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 821.28 520.41 300.88 797.48 1154.96 0.00 0.00 0.00
February 990.35 613.72 376.63 953.56 1174.23 0.00 0.00 0.00
March 1159.64 639.80 519.84 1188.47 902.20 0.00 0.00 0.00
April 1091.86 462.27 629.58 1068.56 798.69 0.00 0.00 0.00
May 1334.53 470.47 864.06 1533.40 507.01 0.00 0.00 0.00
June 1632.21 785.32 846.89 2232.26 302.88 0.00 0.00 0.00
July 1329.86 487.10 842.76 1825.71 273.78 0.00 0.00 0.00
August 1388.00 685.69 702.31 1873.74 315.08 0.00 0.00 0.00
September 1230.74 590.22 640.52 1581.96 480.76 0.00 0.00 0.00
October 1035.38 591.79 443.58 1121.00 956.83 0.00 0.00 0.00
November 849.58 515.80 333.78 835.86 1099.53 0.00 0.00 0.00
December 686.23 405.37 280.86 606.68 1297.38 0.00 0.00 0.00
                 
Annual Sum or Average 1129.49 563.32 566.17 1303.01 769.75 0.00 0.00 0.00
Minimum of Months 686.23 405.37 280.86 606.68 273.78 0.00 0.00 0.00
Maximum of Months 1632.21 785.32 864.06 2232.26 1297.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.47 20.58 11.90 31.53 45.67 0.00 0.00 0.00
February 39.16 24.27 14.89 37.70 46.43 0.00 0.00 0.00
March 45.85 25.30 20.55 46.99 35.67 0.00 0.00 0.00
April 43.17 18.28 24.89 42.25 31.58 0.00 0.00 0.00
May 52.77 18.60 34.16 60.63 20.05 0.00 0.00 0.00
June 64.54 31.05 33.49 88.26 11.98 0.00 0.00 0.00
July 52.58 19.26 33.32 72.19 10.83 0.00 0.00 0.00
August 54.88 27.11 27.77 74.09 12.46 0.00 0.00 0.00
September 48.66 23.34 25.33 62.55 19.01 0.00 0.00 0.00
October 40.94 23.40 17.54 44.32 37.83 0.00 0.00 0.00
November 33.59 20.39 13.20 33.05 43.47 0.00 0.00 0.00
December 27.13 16.03 11.10 23.99 51.30 0.00 0.00 0.00
                 
Annual Sum or Average 44.66 22.27 22.39 51.52 30.44 0.00 0.00 0.00
Minimum of Months 27.13 16.03 11.10 23.99 10.83 0.00 0.00 0.00
Maximum of Months 64.54 31.05 34.16 88.26 51.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 384.46 0.00 384.46 72.49 1883.33 0.00 0.00 0.00
February 483.22 0.00 483.22 90.55 1902.91 0.00 0.00 0.00
March 657.51 0.00 657.51 299.76 1454.34 0.00 0.00 0.00
April 825.73 4.58 821.15 454.80 1259.95 0.00 0.00 0.00
May 1128.00 37.29 1090.72 1014.71 751.50 0.00 0.00 0.00
June 1236.93 137.13 1099.80 1643.10 415.84 0.00 0.00 0.00
July 1169.80 75.72 1094.08 1572.45 393.94 0.00 0.00 0.00
August 931.07 22.03 909.05 1195.38 453.34 0.00 0.00 0.00
September 782.10 0.18 781.92 881.27 704.05 0.00 0.00 0.00
October 560.17 0.00 560.17 301.73 1452.22 0.00 0.00 0.00
November 425.24 0.00 425.24 117.01 1716.57 0.00 0.00 0.00
December 359.71 0.00 359.71 63.04 2099.29 0.00 0.00 0.00
                 
Annual Sum or Average 746.69 23.13 723.56 645.28 1203.56 0.00 0.00 0.00
Minimum of Months 359.71 0.00 359.71 63.04 393.94 0.00 0.00 0.00
Maximum of Months 1236.93 137.13 1099.80 1643.10 2099.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 802.58 491.85 310.74 711.56 1180.70 0.00 0.00 0.00
February 1066.14 673.05 393.09 999.91 1217.14 0.00 0.00 0.00
March 1286.81 750.58 536.22 1302.57 934.24 0.00 0.00 0.00
April 1319.69 642.84 676.85 1307.02 820.31 0.00 0.00 0.00
May 1542.70 644.39 898.31 1740.80 506.79 0.00 0.00 0.00
June 1882.25 988.13 894.12 2521.97 279.75 0.00 0.00 0.00
July 1711.11 814.79 896.32 2312.09 265.19 0.00 0.00 0.00
August 1725.89 950.56 775.33 2318.12 304.16 0.00 0.00 0.00
September 1436.03 780.09 655.94 1825.97 451.63 0.00 0.00 0.00
October 1039.97 569.84 470.13 1085.61 947.18 0.00 0.00 0.00
November 809.48 457.04 352.44 755.21 1106.32 0.00 0.00 0.00
December 700.80 403.71 297.09 594.55 1329.93 0.00 0.00 0.00
                 
Annual Sum or Average 1277.76 680.24 597.52 1458.43 776.26 0.00 0.00 0.00
Minimum of Months 700.80 403.71 297.09 594.55 265.19 0.00 0.00 0.00
Maximum of Months 1882.25 988.13 898.31 2521.97 1329.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3684.63 3031.01 653.63 4217.32 1715.71 0.00 0.00 0.00
February 3534.25 2817.72 716.52 4008.19 1783.51 0.00 0.00 0.00
March 2605.72 1714.42 891.30 2994.29 1428.82 0.00 0.00 0.00
April 1687.66 678.61 1009.04 1765.61 1297.29 0.00 0.00 0.00
May 1546.55 283.47 1263.08 1760.71 824.90 0.00 0.00 0.00
June 1425.87 260.61 1165.26 2054.46 457.18 0.00 0.00 0.00
July 1484.30 265.80 1218.50 2143.40 423.85 0.00 0.00 0.00
August 1889.81 790.01 1099.80 2744.72 479.32 0.00 0.00 0.00
September 2431.43 1356.72 1074.70 3308.84 722.09 0.00 0.00 0.00
October 2907.28 2062.78 844.50 3520.82 1438.46 0.00 0.00 0.00
November 3542.11 2823.58 718.53 4141.13 1641.82 0.00 0.00 0.00
December 3387.18 2741.54 645.64 3798.96 1910.30 0.00 0.00 0.00
                 
Annual Sum or Average 2504.77 1561.76 943.01 3032.65 1173.57 0.00 0.00 0.00
Minimum of Months 1425.87 260.61 645.64 1760.71 423.85 0.00 0.00 0.00
Maximum of Months 3684.63 3031.01 1263.08 4217.32 1910.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 853.77 540.99 312.77 816.07 1209.87 0.00 0.00 0.00
February 1029.52 638.00 391.52 974.38 1234.23 0.00 0.00 0.00
March 1205.51 665.11 540.40 1213.71 955.04 0.00 0.00 0.00
April 1135.04 480.56 654.48 1090.56 842.58 0.00 0.00 0.00
May 1387.31 489.08 898.23 1570.93 539.68 0.00 0.00 0.00
June 1696.77 816.38 880.39 2307.96 314.97 0.00 0.00 0.00
July 1382.46 506.37 876.09 1885.33 288.37 0.00 0.00 0.00
August 1442.90 712.81 730.09 1940.68 322.71 0.00 0.00 0.00
September 1279.42 613.57 665.85 1642.15 483.86 0.00 0.00 0.00
October 1076.33 615.20 461.13 1163.36 965.98 0.00 0.00 0.00
November 883.19 536.20 346.98 865.06 1120.46 0.00 0.00 0.00
December 713.37 421.41 291.96 624.45 1335.40 0.00 0.00 0.00
                 
Annual Sum or Average 1174.16 585.60 588.56 1342.75 798.75 0.00 0.00 0.00
Minimum of Months 713.37 421.41 291.96 624.45 288.37 0.00 0.00 0.00
Maximum of Months 1696.77 816.38 898.23 2307.96 1335.40 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102974E+10 0.00 0.102974E+10 0.222472E+09 0.474876E+10
February 0.116901E+10 0.00 0.116901E+10 0.241753E+09 0.437552E+10
March 0.176107E+10 0.00 0.176107E+10 0.833736E+09 0.368121E+10
April 0.214030E+10 11873484.46 0.212843E+10 0.121225E+10 0.304731E+10
May 0.302124E+10 99870170.09 0.292137E+10 0.275214E+10 0.192767E+10
June 0.320613E+10 0.355452E+09 0.285068E+10 0.425388E+10 0.105034E+10
July 0.313320E+10 0.202818E+09 0.293038E+10 0.420381E+10 0.102927E+10
August 0.249379E+10 58994652.25 0.243479E+10 0.319960E+10 0.117336E+10
September 0.202721E+10 476155.58 0.202673E+10 0.229746E+10 0.174078E+10
October 0.150037E+10 0.00 0.150037E+10 0.847829E+09 0.365120E+10
November 0.110223E+10 0.00 0.110223E+10 0.338962E+09 0.417791E+10
December 0.963454E+09 0.00 0.963454E+09 0.188904E+09 0.534847E+10
           
Annual Sum or Average 0.235478E+11 0.729484E+09 0.228183E+11 0.205928E+11 0.359518E+11
Minimum of Months 0.963454E+09 0.00 0.963454E+09 0.188904E+09 0.102927E+10
Maximum of Months 0.320613E+10 0.355452E+09 0.293038E+10 0.425388E+10 0.534847E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214964E+10 0.131736E+10 0.832275E+09 0.195127E+10 0.298227E+10
February 0.257921E+10 0.162825E+10 0.950966E+09 0.244891E+10 0.280381E+10
March 0.344658E+10 0.201036E+10 0.143622E+10 0.351639E+10 0.237281E+10
April 0.342063E+10 0.166625E+10 0.175438E+10 0.341533E+10 0.199026E+10
May 0.413195E+10 0.172593E+10 0.240602E+10 0.468614E+10 0.130509E+10
June 0.487878E+10 0.256123E+10 0.231755E+10 0.653735E+10 0.706483E+09
July 0.458304E+10 0.218233E+10 0.240071E+10 0.619178E+10 0.692289E+09
August 0.462263E+10 0.254598E+10 0.207665E+10 0.621152E+10 0.787908E+09
September 0.372219E+10 0.202200E+10 0.170019E+10 0.474562E+10 0.112232E+10
October 0.278546E+10 0.152627E+10 0.125919E+10 0.293578E+10 0.239277E+10
November 0.209818E+10 0.118466E+10 0.913528E+09 0.199861E+10 0.269910E+10
December 0.187702E+10 0.108129E+10 0.795721E+09 0.162829E+10 0.339077E+10
           
Annual Sum or Average 0.402953E+11 0.214519E+11 0.188434E+11 0.462670E+11 0.232459E+11
Minimum of Months 0.187702E+10 0.108129E+10 0.795721E+09 0.162829E+10 0.692289E+09
Maximum of Months 0.487878E+10 0.256123E+10 0.240602E+10 0.653735E+10 0.339077E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.986892E+10 0.811825E+10 0.175067E+10 0.113579E+11 0.434828E+10
February 0.855005E+10 0.681664E+10 0.173341E+10 0.973277E+10 0.410740E+10
March 0.697916E+10 0.459189E+10 0.238727E+10 0.804712E+10 0.362602E+10
April 0.437441E+10 0.175897E+10 0.261544E+10 0.460456E+10 0.314527E+10
May 0.414228E+10 0.759251E+09 0.338303E+10 0.473500E+10 0.211347E+10
June 0.369585E+10 0.675498E+09 0.302035E+10 0.531363E+10 0.114876E+10
July 0.397554E+10 0.711908E+09 0.326363E+10 0.572780E+10 0.110251E+10
August 0.506167E+10 0.211597E+10 0.294570E+10 0.734167E+10 0.123943E+10
September 0.630226E+10 0.351663E+10 0.278563E+10 0.857963E+10 0.179192E+10
October 0.778685E+10 0.552495E+10 0.226190E+10 0.946066E+10 0.363899E+10
November 0.918115E+10 0.731871E+10 0.186244E+10 0.107816E+11 0.402220E+10
December 0.907223E+10 0.734294E+10 0.172929E+10 0.102279E+11 0.486800E+10
           
Annual Sum or Average 0.789904E+11 0.492516E+11 0.297388E+11 0.959104E+11 0.351523E+11
Minimum of Months 0.369585E+10 0.675498E+09 0.172929E+10 0.460456E+10 0.110251E+10
Maximum of Months 0.986892E+10 0.811825E+10 0.338303E+10 0.113579E+11 0.486800E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228674E+10 0.144900E+10 0.837735E+09 0.221348E+10 0.305478E+10
February 0.249063E+10 0.154345E+10 0.947175E+09 0.237557E+10 0.283780E+10
March 0.322883E+10 0.178142E+10 0.144741E+10 0.326935E+10 0.241836E+10
April 0.294203E+10 0.124560E+10 0.169642E+10 0.284805E+10 0.204037E+10
May 0.371577E+10 0.130995E+10 0.240582E+10 0.422082E+10 0.138233E+10
June 0.439802E+10 0.211606E+10 0.228196E+10 0.597299E+10 0.791749E+09
July 0.370279E+10 0.135626E+10 0.234652E+10 0.504038E+10 0.750241E+09
August 0.386466E+10 0.190920E+10 0.195546E+10 0.519246E+10 0.834861E+09
September 0.331625E+10 0.159036E+10 0.172589E+10 0.426183E+10 0.119850E+10
October 0.288284E+10 0.164776E+10 0.123508E+10 0.313995E+10 0.243522E+10
November 0.228922E+10 0.138984E+10 0.899379E+09 0.227046E+10 0.273232E+10
December 0.191070E+10 0.112870E+10 0.781997E+09 0.169413E+10 0.340156E+10
           
Annual Sum or Average 0.370285E+11 0.184676E+11 0.185609E+11 0.424995E+11 0.238781E+11
Minimum of Months 0.191070E+10 0.112870E+10 0.781997E+09 0.169413E+10 0.750241E+09
Maximum of Months 0.439802E+10 0.211606E+10 0.240582E+10 0.597299E+10 0.340156E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.343232E+09 0.00 0.343232E+09 74101221.68 0.163334E+10
February 0.389652E+09 0.00 0.389652E+09 86378286.98 0.148484E+10
March 0.586995E+09 0.00 0.586995E+09 0.297248E+09 0.124139E+10
April 0.713401E+09 3957640.90 0.709443E+09 0.423984E+09 0.104217E+10
May 0.100703E+10 33288481.68 0.973745E+09 0.945215E+09 0.636630E+09
June 0.106866E+10 0.118478E+09 0.950182E+09 0.144248E+10 0.344143E+09
July 0.104435E+10 67602645.39 0.976748E+09 0.142572E+10 0.335443E+09
August 0.831224E+09 19663953.70 0.811560E+09 0.107932E+10 0.394664E+09
September 0.675704E+09 158711.02 0.675546E+09 0.765844E+09 0.609377E+09
October 0.500100E+09 0.00 0.500100E+09 0.273672E+09 0.130327E+10
November 0.367392E+09 0.00 0.367392E+09 0.104482E+09 0.148196E+10
December 0.321136E+09 0.00 0.321136E+09 59394980.71 0.186604E+10
           
Annual Sum or Average 0.784888E+10 0.243150E+09 0.760573E+10 0.697784E+10 0.123733E+11
Minimum of Months 0.321136E+09 0.00 0.321136E+09 59394980.71 0.335443E+09
Maximum of Months 0.106866E+10 0.118478E+09 0.976748E+09 0.144248E+10 0.186604E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.343246E+09 0.00 0.343246E+09 74102142.31 0.163344E+10
February 0.389669E+09 0.00 0.389669E+09 86379974.93 0.148494E+10
March 0.587020E+09 0.00 0.587020E+09 0.297256E+09 0.124147E+10
April 0.713429E+09 3957747.28 0.709472E+09 0.423996E+09 0.104224E+10
May 0.100707E+10 33289376.48 0.973784E+09 0.945245E+09 0.636669E+09
June 0.106870E+10 0.118481E+09 0.950222E+09 0.144254E+10 0.344161E+09
July 0.104439E+10 67604462.56 0.976787E+09 0.142578E+10 0.335462E+09
August 0.831259E+09 19664482.27 0.811595E+09 0.107937E+10 0.394686E+09
September 0.675733E+09 158715.28 0.675574E+09 0.765877E+09 0.609411E+09
October 0.500121E+09 0.00 0.500121E+09 0.273681E+09 0.130335E+10
November 0.367408E+09 0.00 0.367408E+09 0.104484E+09 0.148206E+10
December 0.321149E+09 0.00 0.321149E+09 59396262.64 0.186616E+10
           
Annual Sum or Average 0.784920E+10 0.243156E+09 0.760605E+10 0.697811E+10 0.123740E+11
Minimum of Months 0.321149E+09 0.00 0.321149E+09 59396262.64 0.335462E+09
Maximum of Months 0.106870E+10 0.118481E+09 0.976787E+09 0.144254E+10 0.186616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.343246E+09 0.00 0.343246E+09 74102142.31 0.163344E+10
February 0.389669E+09 0.00 0.389669E+09 86379974.93 0.148494E+10
March 0.587020E+09 0.00 0.587020E+09 0.297256E+09 0.124147E+10
April 0.713429E+09 3957747.28 0.709472E+09 0.423996E+09 0.104224E+10
May 0.100707E+10 33289376.48 0.973784E+09 0.945245E+09 0.636669E+09
June 0.106870E+10 0.118481E+09 0.950222E+09 0.144254E+10 0.344161E+09
July 0.104439E+10 67604462.56 0.976787E+09 0.142578E+10 0.335462E+09
August 0.831259E+09 19664482.27 0.811595E+09 0.107937E+10 0.394686E+09
September 0.675733E+09 158715.28 0.675574E+09 0.765877E+09 0.609411E+09
October 0.500121E+09 0.00 0.500121E+09 0.273681E+09 0.130335E+10
November 0.367408E+09 0.00 0.367408E+09 0.104484E+09 0.148206E+10
December 0.321149E+09 0.00 0.321149E+09 59396262.64 0.186616E+10
           
Annual Sum or Average 0.784920E+10 0.243156E+09 0.760605E+10 0.697811E+10 0.123740E+11
Minimum of Months 0.321149E+09 0.00 0.321149E+09 59396262.64 0.335462E+09
Maximum of Months 0.106870E+10 0.118481E+09 0.976787E+09 0.144254E+10 0.186616E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206784E+10 0.126723E+10 0.800611E+09 0.186833E+10 0.301077E+10
February 0.248107E+10 0.156629E+10 0.914786E+09 0.236851E+10 0.279608E+10
March 0.331543E+10 0.193386E+10 0.138158E+10 0.341431E+10 0.237339E+10
April 0.329048E+10 0.160284E+10 0.168763E+10 0.331395E+10 0.202582E+10
May 0.397473E+10 0.166025E+10 0.231448E+10 0.455039E+10 0.128074E+10
June 0.469314E+10 0.246377E+10 0.222938E+10 0.632966E+10 0.696937E+09
July 0.440866E+10 0.209929E+10 0.230937E+10 0.599648E+10 0.682112E+09
August 0.444673E+10 0.244909E+10 0.199764E+10 0.599845E+10 0.802045E+09
September 0.358056E+10 0.194505E+10 0.163550E+10 0.456647E+10 0.116627E+10
October 0.267947E+10 0.146819E+10 0.121128E+10 0.281168E+10 0.251108E+10
November 0.201835E+10 0.113957E+10 0.878772E+09 0.189682E+10 0.280813E+10
December 0.180559E+10 0.104015E+10 0.765447E+09 0.154955E+10 0.345604E+10
           
Annual Sum or Average 0.387621E+11 0.206356E+11 0.181265E+11 0.446646E+11 0.236094E+11
Minimum of Months 0.180559E+10 0.104015E+10 0.765447E+09 0.154955E+10 0.682112E+09
Maximum of Months 0.469314E+10 0.246377E+10 0.231448E+10 0.632966E+10 0.345604E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 81760686.43 50105254.26 31655432.17 73871982.85 0.119043E+09
February 98099357.20 61929538.73 36169818.47 93648866.65 0.110555E+09
March 0.131089E+09 76462961.31 54626324.10 0.134999E+09 93841628.51
April 0.130102E+09 63374965.96 66727507.05 0.131030E+09 80098924.65
May 0.157157E+09 65644977.66 91512381.12 0.179918E+09 50639438.72
June 0.185563E+09 97415121.80 88147574.49 0.250269E+09 27556274.27
July 0.174314E+09 83003846.61 91310418.94 0.237095E+09 26970097.53
August 0.175820E+09 96834891.99 78984946.19 0.237173E+09 31712149.13
September 0.141572E+09 76905604.65 64666355.52 0.180554E+09 46113268.69
October 0.105944E+09 58050904.71 47892977.97 0.111171E+09 99285731.34
November 79803621.74 45057757.81 34745863.93 74998377.12 0.111031E+09
December 71391537.52 41126470.69 30265066.83 61267797.53 0.136649E+09
           
Annual Sum or Average 0.153262E+10 0.815912E+09 0.716705E+09 0.176600E+10 0.933495E+09
Minimum of Months 71391537.52 41126470.69 30265066.83 61267797.53 26970097.53
Maximum of Months 0.185563E+09 97415121.80 91512381.12 0.250269E+09 0.136649E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.328958E+10 0.270603E+10 0.583550E+09 0.379204E+10 0.157144E+10
February 0.284996E+10 0.227217E+10 0.577798E+09 0.326838E+10 0.145449E+10
March 0.232635E+10 0.153060E+10 0.795748E+09 0.271167E+10 0.126515E+10
April 0.145812E+10 0.586310E+09 0.871805E+09 0.156217E+10 0.109610E+10
May 0.138075E+10 0.253078E+09 0.112767E+10 0.161404E+10 0.700622E+09
June 0.123194E+10 0.225161E+09 0.100678E+10 0.179664E+10 0.380642E+09
July 0.132517E+10 0.237298E+09 0.108787E+10 0.193393E+10 0.365528E+09
August 0.168720E+10 0.705309E+09 0.981894E+09 0.246301E+10 0.432487E+09
September 0.210072E+10 0.117218E+10 0.928536E+09 0.286617E+10 0.651130E+09
October 0.259557E+10 0.184161E+10 0.753960E+09 0.315546E+10 0.133483E+10
November 0.306033E+10 0.243952E+10 0.620807E+09 0.359894E+10 0.147359E+10
December 0.302402E+10 0.244760E+10 0.576423E+09 0.341971E+10 0.174911E+10
           
Annual Sum or Average 0.263297E+11 0.164169E+11 0.991283E+10 0.321822E+11 0.124751E+11
Minimum of Months 0.123194E+10 0.225161E+09 0.576423E+09 0.156217E+10 0.365528E+09
Maximum of Months 0.328958E+10 0.270603E+10 0.112767E+10 0.379204E+10 0.174911E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.328958E+10 0.270603E+10 0.583550E+09 0.379204E+10 0.157144E+10
February 0.284996E+10 0.227217E+10 0.577798E+09 0.326838E+10 0.145449E+10
March 0.232635E+10 0.153060E+10 0.795748E+09 0.271167E+10 0.126515E+10
April 0.145812E+10 0.586310E+09 0.871805E+09 0.156217E+10 0.109610E+10
May 0.138075E+10 0.253078E+09 0.112767E+10 0.161404E+10 0.700622E+09
June 0.123194E+10 0.225161E+09 0.100678E+10 0.179664E+10 0.380642E+09
July 0.132517E+10 0.237298E+09 0.108787E+10 0.193393E+10 0.365528E+09
August 0.168720E+10 0.705309E+09 0.981894E+09 0.246301E+10 0.432487E+09
September 0.210072E+10 0.117218E+10 0.928536E+09 0.286617E+10 0.651130E+09
October 0.259557E+10 0.184161E+10 0.753960E+09 0.315546E+10 0.133483E+10
November 0.306033E+10 0.243952E+10 0.620807E+09 0.359894E+10 0.147359E+10
December 0.302402E+10 0.244760E+10 0.576423E+09 0.341971E+10 0.174911E+10
           
Annual Sum or Average 0.263297E+11 0.164169E+11 0.991283E+10 0.321822E+11 0.124751E+11
Minimum of Months 0.123194E+10 0.225161E+09 0.576423E+09 0.156217E+10 0.365528E+09
Maximum of Months 0.328958E+10 0.270603E+10 0.112767E+10 0.379204E+10 0.174911E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.328937E+10 0.270586E+10 0.583513E+09 0.379180E+10 0.157134E+10
February 0.284978E+10 0.227202E+10 0.577762E+09 0.326818E+10 0.145440E+10
March 0.232620E+10 0.153050E+10 0.795698E+09 0.271150E+10 0.126507E+10
April 0.145802E+10 0.586273E+09 0.871750E+09 0.156207E+10 0.109604E+10
May 0.138066E+10 0.253062E+09 0.112760E+10 0.161393E+10 0.700577E+09
June 0.123186E+10 0.225147E+09 0.100672E+10 0.179652E+10 0.380618E+09
July 0.132508E+10 0.237283E+09 0.108780E+10 0.193381E+10 0.365505E+09
August 0.168710E+10 0.705264E+09 0.981832E+09 0.246285E+10 0.432459E+09
September 0.210059E+10 0.117211E+10 0.928477E+09 0.286598E+10 0.651089E+09
October 0.259541E+10 0.184149E+10 0.753912E+09 0.315527E+10 0.133474E+10
November 0.306013E+10 0.243937E+10 0.620768E+09 0.359871E+10 0.147350E+10
December 0.302383E+10 0.244744E+10 0.576387E+09 0.341950E+10 0.174900E+10
           
Annual Sum or Average 0.263280E+11 0.164158E+11 0.991221E+10 0.321801E+11 0.124743E+11
Minimum of Months 0.123186E+10 0.225147E+09 0.576387E+09 0.156207E+10 0.365505E+09
Maximum of Months 0.328937E+10 0.270586E+10 0.112760E+10 0.379180E+10 0.174900E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.219973E+10 0.139386E+10 0.805865E+09 0.213597E+10 0.309345E+10
February 0.239586E+10 0.148472E+10 0.911142E+09 0.230684E+10 0.284069E+10
March 0.310598E+10 0.171363E+10 0.139235E+10 0.318321E+10 0.241646E+10
April 0.283009E+10 0.119821E+10 0.163188E+10 0.276971E+10 0.207022E+10
May 0.357440E+10 0.126010E+10 0.231429E+10 0.410707E+10 0.135797E+10
June 0.423068E+10 0.203554E+10 0.219515E+10 0.578601E+10 0.785062E+09
July 0.356191E+10 0.130466E+10 0.225725E+10 0.488998E+10 0.733294E+09
August 0.371762E+10 0.183655E+10 0.188107E+10 0.501862E+10 0.843909E+09
September 0.319008E+10 0.152985E+10 0.166023E+10 0.410043E+10 0.124612E+10
October 0.277316E+10 0.158506E+10 0.118810E+10 0.300249E+10 0.256277E+10
November 0.220212E+10 0.133695E+10 0.865163E+09 0.216654E+10 0.284998E+10
December 0.183800E+10 0.108575E+10 0.752247E+09 0.162492E+10 0.347491E+10
           
Annual Sum or Average 0.356196E+11 0.177649E+11 0.178547E+11 0.410918E+11 0.242748E+11
Minimum of Months 0.183800E+10 0.108575E+10 0.752247E+09 0.162492E+10 0.733294E+09
Maximum of Months 0.423068E+10 0.203554E+10 0.231429E+10 0.578601E+10 0.347491E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86975063.61 55111960.46 31863103.15 84454004.55 0.122312E+09
February 94730006.39 58704353.86 36025652.54 91210172.58 0.112318E+09
March 0.122807E+09 67755274.10 55052016.37 0.125861E+09 95544727.40
April 0.111899E+09 47375869.14 64522999.00 0.109512E+09 81854501.96
May 0.141328E+09 49823187.03 91504875.63 0.162389E+09 53692928.30
June 0.167277E+09 80483061.54 86793885.65 0.228773E+09 31040634.47
July 0.140834E+09 51584726.00 89249486.79 0.193345E+09 28993781.21
August 0.146991E+09 72615278.85 74375646.53 0.198431E+09 33367388.87
September 0.126132E+09 60488701.33 65643764.97 0.162127E+09 49270579.40
October 0.109648E+09 62671682.37 46976140.24 0.118715E+09 0.101330E+09
November 87069489.53 52861796.30 34207693.24 85662639.29 0.112686E+09
December 72672600.43 42929506.76 29743093.67 64247563.67 0.137395E+09
           
Annual Sum or Average 0.140836E+10 0.702405E+09 0.705958E+09 0.162473E+10 0.959805E+09
Minimum of Months 72672600.43 42929506.76 29743093.67 64247563.67 28993781.21
Maximum of Months 0.167277E+09 80483061.54 91504875.63 0.228773E+09 0.137395E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.102974E+10 0.00 0.102974E+10 0.194169E+09 0.504432E+10
February 0.116901E+10 0.00 0.116901E+10 0.219056E+09 0.460352E+10
March 0.176107E+10 0.00 0.176107E+10 0.802886E+09 0.389531E+10
April 0.214030E+10 11873484.46 0.212843E+10 0.117884E+10 0.326579E+10
May 0.302124E+10 99870170.09 0.292137E+10 0.271780E+10 0.201281E+10
June 0.320613E+10 0.355452E+09 0.285068E+10 0.425891E+10 0.107785E+10
July 0.313320E+10 0.202818E+09 0.293038E+10 0.421166E+10 0.105514E+10
August 0.249379E+10 58994652.25 0.243479E+10 0.320170E+10 0.121421E+10
September 0.202721E+10 476155.58 0.202673E+10 0.228425E+10 0.182491E+10
October 0.150037E+10 0.00 0.150037E+10 0.808162E+09 0.388963E+10
November 0.110223E+10 0.00 0.110223E+10 0.303298E+09 0.444934E+10
December 0.963454E+09 0.00 0.963454E+09 0.168843E+09 0.562274E+10
           
Annual Sum or Average 0.235478E+11 0.729484E+09 0.228183E+11 0.203496E+11 0.379556E+11
Minimum of Months 0.963454E+09 0.00 0.963454E+09 0.168843E+09 0.105514E+10
Maximum of Months 0.320613E+10 0.355452E+09 0.293038E+10 0.425891E+10 0.562274E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214964E+10 0.131736E+10 0.832275E+09 0.190585E+10 0.316238E+10
February 0.257921E+10 0.162825E+10 0.950966E+09 0.241897E+10 0.294451E+10
March 0.344658E+10 0.201036E+10 0.143622E+10 0.348881E+10 0.250226E+10
April 0.342063E+10 0.166625E+10 0.175438E+10 0.338779E+10 0.212624E+10
May 0.413195E+10 0.172593E+10 0.240602E+10 0.466255E+10 0.135739E+10
June 0.487878E+10 0.256123E+10 0.231755E+10 0.653695E+10 0.725106E+09
July 0.458304E+10 0.218233E+10 0.240071E+10 0.619271E+10 0.710296E+09
August 0.462263E+10 0.254598E+10 0.207665E+10 0.620885E+10 0.814659E+09
September 0.372219E+10 0.202200E+10 0.170019E+10 0.473292E+10 0.117063E+10
October 0.278546E+10 0.152627E+10 0.125919E+10 0.290770E+10 0.253691E+10
November 0.209818E+10 0.118466E+10 0.913528E+09 0.195751E+10 0.286758E+10
December 0.187702E+10 0.108129E+10 0.795721E+09 0.159243E+10 0.356210E+10
           
Annual Sum or Average 0.402953E+11 0.214519E+11 0.188434E+11 0.459930E+11 0.244801E+11
Minimum of Months 0.187702E+10 0.108129E+10 0.795721E+09 0.159243E+10 0.710296E+09
Maximum of Months 0.487878E+10 0.256123E+10 0.240602E+10 0.653695E+10 0.356210E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.986892E+10 0.811825E+10 0.175067E+10 0.112957E+11 0.459536E+10
February 0.855005E+10 0.681664E+10 0.173341E+10 0.969662E+10 0.431468E+10
March 0.697916E+10 0.459189E+10 0.238727E+10 0.801992E+10 0.382695E+10
April 0.437441E+10 0.175897E+10 0.261544E+10 0.457647E+10 0.336257E+10
May 0.414228E+10 0.759251E+09 0.338303E+10 0.471589E+10 0.220942E+10
June 0.369585E+10 0.675498E+09 0.302035E+10 0.532515E+10 0.118501E+10
July 0.397554E+10 0.711908E+09 0.326363E+10 0.574088E+10 0.113523E+10
August 0.506167E+10 0.211597E+10 0.294570E+10 0.735145E+10 0.128382E+10
September 0.630226E+10 0.351663E+10 0.278563E+10 0.857652E+10 0.187165E+10
October 0.778685E+10 0.552495E+10 0.226190E+10 0.943016E+10 0.385278E+10
November 0.918115E+10 0.731871E+10 0.186244E+10 0.107338E+11 0.425559E+10
December 0.907223E+10 0.734294E+10 0.172929E+10 0.101751E+11 0.511654E+10
           
Annual Sum or Average 0.789904E+11 0.492516E+11 0.297388E+11 0.956377E+11 0.370096E+11
Minimum of Months 0.369585E+10 0.675498E+09 0.172929E+10 0.457647E+10 0.113523E+10
Maximum of Months 0.986892E+10 0.811825E+10 0.338303E+10 0.112957E+11 0.511654E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228674E+10 0.144900E+10 0.837735E+09 0.218576E+10 0.324053E+10
February 0.249063E+10 0.154345E+10 0.947175E+09 0.235723E+10 0.298585E+10
March 0.322883E+10 0.178142E+10 0.144741E+10 0.325079E+10 0.255799E+10
April 0.294203E+10 0.124560E+10 0.169642E+10 0.282673E+10 0.218398E+10
May 0.371577E+10 0.130995E+10 0.240582E+10 0.420759E+10 0.144547E+10
June 0.439802E+10 0.211606E+10 0.228196E+10 0.598222E+10 0.816409E+09
July 0.370279E+10 0.135626E+10 0.234652E+10 0.504966E+10 0.772374E+09
August 0.386466E+10 0.190920E+10 0.195546E+10 0.519791E+10 0.864349E+09
September 0.331625E+10 0.159036E+10 0.172589E+10 0.425646E+10 0.125416E+10
October 0.288284E+10 0.164776E+10 0.123508E+10 0.311595E+10 0.258728E+10
November 0.228922E+10 0.138984E+10 0.899379E+09 0.224224E+10 0.290424E+10
December 0.191070E+10 0.112870E+10 0.781997E+09 0.167253E+10 0.357673E+10
           
Annual Sum or Average 0.370285E+11 0.184676E+11 0.185609E+11 0.423451E+11 0.251894E+11
Minimum of Months 0.191070E+10 0.112870E+10 0.781997E+09 0.167253E+10 0.772374E+09
Maximum of Months 0.439802E+10 0.211606E+10 0.240582E+10 0.598222E+10 0.357673E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 83.06 1772.98 384.46 0.00 384.46 0.00 0.00
February 99.93 1808.66 483.22 0.00 483.22 0.00 0.00
March 311.28 1374.40 657.51 0.00 657.51 0.00 0.00
April 467.69 1175.66 825.73 4.58 821.15 0.00 0.00
May 1027.53 719.71 1128.00 37.29 1090.72 0.00 0.00
June 1641.16 405.22 1236.93 137.13 1099.80 0.00 0.00
July 1569.52 384.29 1169.80 75.72 1094.08 0.00 0.00
August 1194.59 438.08 931.07 22.03 909.05 0.00 0.00
September 886.37 671.60 782.10 0.18 781.92 0.00 0.00
October 316.54 1363.20 560.17 0.00 560.17 0.00 0.00
November 130.77 1611.85 425.24 0.00 425.24 0.00 0.00
December 70.53 1996.89 359.71 0.00 359.71 0.00 0.00
               
Annual Sum or Average 652.99 1140.02 746.69 23.13 723.56 0.00 0.00
Minimum of Months 70.53 384.29 359.71 0.00 359.71 0.00 0.00
Maximum of Months 1641.16 1996.89 1236.93 137.13 1099.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 728.52 1113.45 802.58 491.85 310.74 0.00 0.00
February 1012.28 1158.98 1066.14 673.05 393.09 0.00 0.00
March 1312.87 885.91 1286.81 750.58 536.22 0.00 0.00
April 1317.64 767.85 1319.69 642.84 676.85 0.00 0.00
May 1749.61 487.26 1542.70 644.39 898.31 0.00 0.00
June 2522.13 272.56 1882.25 988.13 894.12 0.00 0.00
July 2311.75 258.47 1711.11 814.79 896.32 0.00 0.00
August 2319.12 294.17 1725.89 950.56 775.33 0.00 0.00
September 1830.87 433.00 1436.03 780.09 655.94 0.00 0.00
October 1096.09 893.36 1039.97 569.84 470.13 0.00 0.00
November 771.07 1041.32 809.48 457.04 352.44 0.00 0.00
December 607.93 1265.97 700.80 403.71 297.09 0.00 0.00
               
Annual Sum or Average 1467.12 737.12 1277.76 680.24 597.52 0.00 0.00
Minimum of Months 607.93 258.47 700.80 403.71 297.09 0.00 0.00
Maximum of Months 2522.13 1265.97 1882.25 988.13 898.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4240.57 1623.46 3684.63 3031.01 653.63 0.00 0.00
February 4023.14 1697.83 3534.25 2817.72 716.52 0.00 0.00
March 3004.45 1353.80 2605.72 1714.42 891.30 0.00 0.00
April 1776.45 1213.45 1687.66 678.61 1009.04 0.00 0.00
May 1767.85 789.08 1546.55 283.47 1263.08 0.00 0.00
June 2050.01 443.19 1425.87 260.61 1165.26 0.00 0.00
July 2138.52 411.63 1484.30 265.80 1218.50 0.00 0.00
August 2741.07 462.75 1889.81 790.01 1099.80 0.00 0.00
September 3310.04 691.33 2431.43 1356.72 1074.70 0.00 0.00
October 3532.21 1358.64 2907.28 2062.78 844.50 0.00 0.00
November 4159.58 1551.77 3542.11 2823.58 718.53 0.00 0.00
December 3818.67 1817.50 3387.18 2741.54 645.64 0.00 0.00
               
Annual Sum or Average 3041.30 1114.67 2504.77 1561.76 943.01 0.00 0.00
Minimum of Months 1767.85 411.63 1425.87 260.61 645.64 0.00 0.00
Maximum of Months 4240.57 1817.50 3684.63 3031.01 1263.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 826.42 1140.52 853.77 540.99 312.77 0.00 0.00
February 981.97 1173.03 1029.52 638.00 391.52 0.00 0.00
March 1220.63 902.91 1205.51 665.11 540.40 0.00 0.00
April 1098.78 787.18 1135.04 480.56 654.48 0.00 0.00
May 1575.87 516.10 1387.31 489.08 898.23 0.00 0.00
June 2304.39 305.46 1696.77 816.38 880.39 0.00 0.00
July 1881.86 280.11 1382.46 506.37 876.09 0.00 0.00
August 1938.64 311.70 1442.90 712.81 730.09 0.00 0.00
September 1644.23 462.38 1279.42 613.57 665.85 0.00 0.00
October 1172.32 909.21 1076.33 615.20 461.13 0.00 0.00
November 875.95 1054.14 883.19 536.20 346.98 0.00 0.00
December 632.52 1270.00 713.37 421.41 291.96 0.00 0.00
               
Annual Sum or Average 1347.65 757.17 1174.16 585.60 588.56 0.00 0.00
Minimum of Months 632.52 280.11 713.37 421.41 291.96 0.00 0.00
Maximum of Months 2304.39 1270.00 1696.77 816.38 898.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 83.00 1829.53 384.45 0.00 384.45 0.00 0.00
February 107.12 1841.40 483.21 0.00 483.21 0.00 0.00
March 332.95 1390.51 657.49 0.00 657.49 0.00 0.00
April 490.73 1206.26 825.72 4.58 821.14 0.00 0.00
May 1058.73 713.10 1127.98 37.29 1090.69 0.00 0.00
June 1669.58 398.33 1236.91 137.13 1099.78 0.00 0.00
July 1596.95 375.73 1169.78 75.72 1094.06 0.00 0.00
August 1208.95 442.07 931.06 22.03 909.03 0.00 0.00
September 886.42 705.32 782.09 0.18 781.90 0.00 0.00
October 306.54 1459.82 560.16 0.00 560.16 0.00 0.00
November 120.93 1715.31 425.23 0.00 425.23 0.00 0.00
December 66.53 2090.19 359.71 0.00 359.71 0.00 0.00
               
Annual Sum or Average 663.81 1177.11 746.68 23.13 723.55 0.00 0.00
Minimum of Months 66.53 375.73 359.71 0.00 359.71 0.00 0.00
Maximum of Months 1669.58 2090.19 1236.91 137.13 1099.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 725.13 1168.54 802.57 491.84 310.73 0.00 0.00
February 1017.76 1201.49 1066.13 673.04 393.09 0.00 0.00
March 1325.16 921.16 1286.78 750.57 536.22 0.00 0.00
April 1329.08 812.47 1319.67 642.83 676.84 0.00 0.00
May 1766.09 497.08 1542.67 644.38 898.29 0.00 0.00
June 2538.55 279.51 1882.22 988.11 894.11 0.00 0.00
July 2327.35 264.74 1711.08 814.77 896.31 0.00 0.00
August 2328.11 311.29 1725.86 950.54 775.32 0.00 0.00
September 1831.41 467.74 1436.01 780.08 655.93 0.00 0.00
October 1091.27 974.60 1039.95 569.83 470.12 0.00 0.00
November 760.73 1126.22 809.47 457.03 352.44 0.00 0.00
December 601.41 1341.36 700.79 403.70 297.08 0.00 0.00
               
Annual Sum or Average 1472.30 778.25 1277.74 680.22 597.51 0.00 0.00
Minimum of Months 601.41 264.74 700.79 403.70 297.08 0.00 0.00
Maximum of Months 2538.55 1341.36 1882.22 988.11 898.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4247.27 1760.08 3684.49 3030.88 653.60 0.00 0.00
February 4052.97 1803.65 3534.11 2817.61 716.50 0.00 0.00
March 3037.20 1417.03 2605.62 1714.34 891.28 0.00 0.00
April 1808.02 1268.61 1687.60 678.59 1009.01 0.00 0.00
May 1807.80 784.73 1546.50 283.46 1263.04 0.00 0.00
June 2079.40 440.55 1425.83 260.60 1165.23 0.00 0.00
July 2166.10 409.41 1484.25 265.79 1218.46 0.00 0.00
August 2758.69 484.41 1889.75 789.98 1099.77 0.00 0.00
September 3317.25 753.61 2431.34 1356.67 1074.67 0.00 0.00
October 3534.27 1495.07 2907.16 2062.69 844.47 0.00 0.00
November 4165.35 1705.51 3541.97 2823.46 718.51 0.00 0.00
December 3830.24 1959.09 3387.05 2741.43 645.62 0.00 0.00
               
Annual Sum or Average 3061.40 1186.73 2504.67 1561.69 942.98 0.00 0.00
Minimum of Months 1807.80 409.41 1425.83 260.60 645.62 0.00 0.00
Maximum of Months 4247.27 1959.09 3684.49 3030.88 1263.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 829.01 1200.63 853.76 540.99 312.77 0.00 0.00
February 991.26 1220.65 1029.51 637.99 391.52 0.00 0.00
March 1235.47 937.88 1205.49 665.09 540.40 0.00 0.00
April 1110.81 830.27 1135.03 480.55 654.48 0.00 0.00
May 1594.03 527.05 1387.29 489.07 898.22 0.00 0.00
June 2320.52 314.85 1696.74 816.37 880.38 0.00 0.00
July 1897.90 284.61 1382.45 506.36 876.08 0.00 0.00
August 1947.83 327.54 1442.88 712.80 730.08 0.00 0.00
September 1644.50 499.77 1279.40 613.56 665.85 0.00 0.00
October 1165.33 994.66 1076.32 615.19 461.12 0.00 0.00
November 868.90 1143.00 883.17 536.19 346.98 0.00 0.00
December 630.66 1348.68 713.36 421.40 291.96 0.00 0.00
               
Annual Sum or Average 1354.53 800.19 1174.15 585.59 588.56 0.00 0.00
Minimum of Months 630.66 284.61 713.36 421.40 291.96 0.00 0.00
Maximum of Months 2320.52 1348.68 1696.74 816.37 898.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 72.49 1883.33 384.46 0.00 384.46 0.00 0.00
February 90.55 1902.91 483.22 0.00 483.22 0.00 0.00
March 299.76 1454.34 657.51 0.00 657.51 0.00 0.00
April 454.80 1259.95 825.73 4.58 821.15 0.00 0.00
May 1014.71 751.50 1128.00 37.29 1090.72 0.00 0.00
June 1643.10 415.84 1236.93 137.13 1099.80 0.00 0.00
July 1572.45 393.94 1169.80 75.72 1094.08 0.00 0.00
August 1195.38 453.34 931.07 22.03 909.05 0.00 0.00
September 881.27 704.05 782.10 0.18 781.92 0.00 0.00
October 301.73 1452.22 560.17 0.00 560.17 0.00 0.00
November 117.01 1716.57 425.24 0.00 425.24 0.00 0.00
December 63.04 2099.29 359.71 0.00 359.71 0.00 0.00
               
Annual Sum or Average 645.28 1203.56 746.69 23.13 723.56 0.00 0.00
Minimum of Months 63.04 393.94 359.71 0.00 359.71 0.00 0.00
Maximum of Months 1643.10 2099.29 1236.93 137.13 1099.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 711.56 1180.70 802.58 491.85 310.74 0.00 0.00
February 999.91 1217.14 1066.14 673.05 393.09 0.00 0.00
March 1302.57 934.24 1286.81 750.58 536.22 0.00 0.00
April 1307.02 820.31 1319.69 642.84 676.85 0.00 0.00
May 1740.80 506.79 1542.70 644.39 898.31 0.00 0.00
June 2521.97 279.75 1882.25 988.13 894.12 0.00 0.00
July 2312.09 265.19 1711.11 814.79 896.32 0.00 0.00
August 2318.12 304.16 1725.89 950.56 775.33 0.00 0.00
September 1825.97 451.63 1436.03 780.09 655.94 0.00 0.00
October 1085.61 947.18 1039.97 569.84 470.13 0.00 0.00
November 755.21 1106.32 809.48 457.04 352.44 0.00 0.00
December 594.55 1329.93 700.80 403.71 297.09 0.00 0.00
               
Annual Sum or Average 1458.43 776.26 1277.76 680.24 597.52 0.00 0.00
Minimum of Months 594.55 265.19 700.80 403.71 297.09 0.00 0.00
Maximum of Months 2521.97 1329.93 1882.25 988.13 898.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4217.32 1715.71 3684.63 3031.01 653.63 0.00 0.00
February 4008.19 1783.51 3534.25 2817.72 716.52 0.00 0.00
March 2994.29 1428.82 2605.72 1714.42 891.30 0.00 0.00
April 1765.61 1297.29 1687.66 678.61 1009.04 0.00 0.00
May 1760.71 824.90 1546.55 283.47 1263.08 0.00 0.00
June 2054.46 457.18 1425.87 260.61 1165.26 0.00 0.00
July 2143.40 423.85 1484.30 265.80 1218.50 0.00 0.00
August 2744.72 479.32 1889.81 790.01 1099.80 0.00 0.00
September 3308.84 722.09 2431.43 1356.72 1074.70 0.00 0.00
October 3520.82 1438.46 2907.28 2062.78 844.50 0.00 0.00
November 4141.13 1641.82 3542.11 2823.58 718.53 0.00 0.00
December 3798.96 1910.30 3387.18 2741.54 645.64 0.00 0.00
               
Annual Sum or Average 3032.65 1173.57 2504.77 1561.76 943.01 0.00 0.00
Minimum of Months 1760.71 423.85 1425.87 260.61 645.64 0.00 0.00
Maximum of Months 4217.32 1910.30 3684.63 3031.01 1263.08 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 816.07 1209.87 853.77 540.99 312.77 0.00 0.00
February 974.38 1234.23 1029.52 638.00 391.52 0.00 0.00
March 1213.71 955.04 1205.51 665.11 540.40 0.00 0.00
April 1090.56 842.58 1135.04 480.56 654.48 0.00 0.00
May 1570.93 539.68 1387.31 489.08 898.23 0.00 0.00
June 2307.96 314.97 1696.77 816.38 880.39 0.00 0.00
July 1885.33 288.37 1382.46 506.37 876.09 0.00 0.00
August 1940.68 322.71 1442.90 712.81 730.09 0.00 0.00
September 1642.15 483.86 1279.42 613.57 665.85 0.00 0.00
October 1163.36 965.98 1076.33 615.20 461.13 0.00 0.00
November 865.06 1120.46 883.19 536.20 346.98 0.00 0.00
December 624.45 1335.40 713.37 421.41 291.96 0.00 0.00
               
Annual Sum or Average 1342.75 798.75 1174.16 585.60 588.56 0.00 0.00
Minimum of Months 624.45 288.37 713.37 421.41 291.96 0.00 0.00
Maximum of Months 2307.96 1335.40 1696.77 816.38 898.23 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.222472E+09 0.474876E+10 0.102974E+10 0.00 0.102974E+10 0.00 0.00
February 0.241753E+09 0.437552E+10 0.116901E+10 0.00 0.116901E+10 0.00 0.00
March 0.833736E+09 0.368121E+10 0.176107E+10 0.00 0.176107E+10 0.00 0.00
April 0.121225E+10 0.304731E+10 0.214030E+10 11873484.46 0.212843E+10 0.00 0.00
May 0.275214E+10 0.192767E+10 0.302124E+10 99870170.09 0.292137E+10 0.00 0.00
June 0.425388E+10 0.105034E+10 0.320613E+10 0.355452E+09 0.285068E+10 0.00 0.00
July 0.420381E+10 0.102927E+10 0.313320E+10 0.202818E+09 0.293038E+10 0.00 0.00
August 0.319960E+10 0.117336E+10 0.249379E+10 58994652.25 0.243479E+10 0.00 0.00
September 0.229746E+10 0.174078E+10 0.202721E+10 476155.58 0.202673E+10 0.00 0.00
October 0.847829E+09 0.365120E+10 0.150037E+10 0.00 0.150037E+10 0.00 0.00
November 0.338962E+09 0.417791E+10 0.110223E+10 0.00 0.110223E+10 0.00 0.00
December 0.188904E+09 0.534847E+10 0.963454E+09 0.00 0.963454E+09 0.00 0.00
               
Annual Sum or Average 0.205928E+11 0.359518E+11 0.235478E+11 0.729484E+09 0.228183E+11 0.00 0.00
Minimum of Months 0.188904E+09 0.102927E+10 0.963454E+09 0.00 0.963454E+09 0.00 0.00
Maximum of Months 0.425388E+10 0.534847E+10 0.320613E+10 0.355452E+09 0.293038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.195127E+10 0.298227E+10 0.214964E+10 0.131736E+10 0.832275E+09 0.00 0.00
February 0.244891E+10 0.280381E+10 0.257921E+10 0.162825E+10 0.950966E+09 0.00 0.00
March 0.351639E+10 0.237281E+10 0.344658E+10 0.201036E+10 0.143622E+10 0.00 0.00
April 0.341533E+10 0.199026E+10 0.342063E+10 0.166625E+10 0.175438E+10 0.00 0.00
May 0.468614E+10 0.130509E+10 0.413195E+10 0.172593E+10 0.240602E+10 0.00 0.00
June 0.653735E+10 0.706483E+09 0.487878E+10 0.256123E+10 0.231755E+10 0.00 0.00
July 0.619178E+10 0.692289E+09 0.458304E+10 0.218233E+10 0.240071E+10 0.00 0.00
August 0.621152E+10 0.787908E+09 0.462263E+10 0.254598E+10 0.207665E+10 0.00 0.00
September 0.474562E+10 0.112232E+10 0.372219E+10 0.202200E+10 0.170019E+10 0.00 0.00
October 0.293578E+10 0.239277E+10 0.278546E+10 0.152627E+10 0.125919E+10 0.00 0.00
November 0.199861E+10 0.269910E+10 0.209818E+10 0.118466E+10 0.913528E+09 0.00 0.00
December 0.162829E+10 0.339077E+10 0.187702E+10 0.108129E+10 0.795721E+09 0.00 0.00
               
Annual Sum or Average 0.462670E+11 0.232459E+11 0.402953E+11 0.214519E+11 0.188434E+11 0.00 0.00
Minimum of Months 0.162829E+10 0.692289E+09 0.187702E+10 0.108129E+10 0.795721E+09 0.00 0.00
Maximum of Months 0.653735E+10 0.339077E+10 0.487878E+10 0.256123E+10 0.240602E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113579E+11 0.434828E+10 0.986892E+10 0.811825E+10 0.175067E+10 0.00 0.00
February 0.973277E+10 0.410740E+10 0.855005E+10 0.681664E+10 0.173341E+10 0.00 0.00
March 0.804712E+10 0.362602E+10 0.697916E+10 0.459189E+10 0.238727E+10 0.00 0.00
April 0.460456E+10 0.314527E+10 0.437441E+10 0.175897E+10 0.261544E+10 0.00 0.00
May 0.473500E+10 0.211347E+10 0.414228E+10 0.759251E+09 0.338303E+10 0.00 0.00
June 0.531363E+10 0.114876E+10 0.369585E+10 0.675498E+09 0.302035E+10 0.00 0.00
July 0.572780E+10 0.110251E+10 0.397554E+10 0.711908E+09 0.326363E+10 0.00 0.00
August 0.734167E+10 0.123943E+10 0.506167E+10 0.211597E+10 0.294570E+10 0.00 0.00
September 0.857963E+10 0.179192E+10 0.630226E+10 0.351663E+10 0.278563E+10 0.00 0.00
October 0.946066E+10 0.363899E+10 0.778685E+10 0.552495E+10 0.226190E+10 0.00 0.00
November 0.107816E+11 0.402220E+10 0.918115E+10 0.731871E+10 0.186244E+10 0.00 0.00
December 0.102279E+11 0.486800E+10 0.907223E+10 0.734294E+10 0.172929E+10 0.00 0.00
               
Annual Sum or Average 0.959104E+11 0.351523E+11 0.789904E+11 0.492516E+11 0.297388E+11 0.00 0.00
Minimum of Months 0.460456E+10 0.110251E+10 0.369585E+10 0.675498E+09 0.172929E+10 0.00 0.00
Maximum of Months 0.113579E+11 0.486800E+10 0.986892E+10 0.811825E+10 0.338303E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.221348E+10 0.305478E+10 0.228674E+10 0.144900E+10 0.837735E+09 0.00 0.00
February 0.237557E+10 0.283780E+10 0.249063E+10 0.154345E+10 0.947175E+09 0.00 0.00
March 0.326935E+10 0.241836E+10 0.322883E+10 0.178142E+10 0.144741E+10 0.00 0.00
April 0.284805E+10 0.204037E+10 0.294203E+10 0.124560E+10 0.169642E+10 0.00 0.00
May 0.422082E+10 0.138233E+10 0.371577E+10 0.130995E+10 0.240582E+10 0.00 0.00
June 0.597299E+10 0.791749E+09 0.439802E+10 0.211606E+10 0.228196E+10 0.00 0.00
July 0.504038E+10 0.750241E+09 0.370279E+10 0.135626E+10 0.234652E+10 0.00 0.00
August 0.519246E+10 0.834861E+09 0.386466E+10 0.190920E+10 0.195546E+10 0.00 0.00
September 0.426183E+10 0.119850E+10 0.331625E+10 0.159036E+10 0.172589E+10 0.00 0.00
October 0.313995E+10 0.243522E+10 0.288284E+10 0.164776E+10 0.123508E+10 0.00 0.00
November 0.227046E+10 0.273232E+10 0.228922E+10 0.138984E+10 0.899379E+09 0.00 0.00
December 0.169413E+10 0.340156E+10 0.191070E+10 0.112870E+10 0.781997E+09 0.00 0.00
               
Annual Sum or Average 0.424995E+11 0.238781E+11 0.370285E+11 0.184676E+11 0.185609E+11 0.00 0.00
Minimum of Months 0.169413E+10 0.750241E+09 0.191070E+10 0.112870E+10 0.781997E+09 0.00 0.00
Maximum of Months 0.597299E+10 0.340156E+10 0.439802E+10 0.211606E+10 0.240582E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.222306E+09 0.490021E+10 0.102972E+10 0.00 0.102972E+10 0.00 0.00
February 0.259138E+09 0.445472E+10 0.116899E+10 0.00 0.116899E+10 0.00 0.00
March 0.891760E+09 0.372434E+10 0.176103E+10 0.00 0.176103E+10 0.00 0.00
April 0.127198E+10 0.312664E+10 0.214026E+10 11873135.46 0.212839E+10 0.00 0.00
May 0.283571E+10 0.190997E+10 0.302118E+10 99867234.64 0.292131E+10 0.00 0.00
June 0.432756E+10 0.103247E+10 0.320607E+10 0.355441E+09 0.285063E+10 0.00 0.00
July 0.427728E+10 0.100637E+10 0.313313E+10 0.202812E+09 0.293032E+10 0.00 0.00
August 0.323806E+10 0.118404E+10 0.249374E+10 58992918.24 0.243475E+10 0.00 0.00
September 0.229760E+10 0.182820E+10 0.202717E+10 476141.58 0.202669E+10 0.00 0.00
October 0.821034E+09 0.390998E+10 0.150034E+10 0.00 0.150034E+10 0.00 0.00
November 0.313451E+09 0.444608E+10 0.110221E+10 0.00 0.110221E+10 0.00 0.00
December 0.178188E+09 0.559837E+10 0.963435E+09 0.00 0.963435E+09 0.00 0.00
               
Annual Sum or Average 0.209340E+11 0.371214E+11 0.235473E+11 0.729462E+09 0.228178E+11 0.00 0.00
Minimum of Months 0.178188E+09 0.100637E+10 0.963435E+09 0.00 0.963435E+09 0.00 0.00
Maximum of Months 0.432756E+10 0.559837E+10 0.320607E+10 0.355441E+09 0.293032E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.194220E+10 0.312981E+10 0.214960E+10 0.131734E+10 0.832266E+09 0.00 0.00
February 0.246216E+10 0.290664E+10 0.257917E+10 0.162822E+10 0.950956E+09 0.00 0.00
March 0.354931E+10 0.246723E+10 0.344652E+10 0.201032E+10 0.143620E+10 0.00 0.00
April 0.344498E+10 0.210591E+10 0.342058E+10 0.166622E+10 0.175436E+10 0.00 0.00
May 0.473030E+10 0.133138E+10 0.413189E+10 0.172590E+10 0.240599E+10 0.00 0.00
June 0.657993E+10 0.724494E+09 0.487871E+10 0.256118E+10 0.231752E+10 0.00 0.00
July 0.623357E+10 0.709082E+09 0.458297E+10 0.218229E+10 0.240068E+10 0.00 0.00
August 0.623562E+10 0.833757E+09 0.462255E+10 0.254593E+10 0.207663E+10 0.00 0.00
September 0.474703E+10 0.121238E+10 0.372213E+10 0.202196E+10 0.170017E+10 0.00 0.00
October 0.292286E+10 0.261036E+10 0.278542E+10 0.152624E+10 0.125917E+10 0.00 0.00
November 0.197181E+10 0.291916E+10 0.209815E+10 0.118463E+10 0.913518E+09 0.00 0.00
December 0.161082E+10 0.359269E+10 0.187698E+10 0.108127E+10 0.795712E+09 0.00 0.00
               
Annual Sum or Average 0.464306E+11 0.245429E+11 0.402947E+11 0.214515E+11 0.188432E+11 0.00 0.00
Minimum of Months 0.161082E+10 0.709082E+09 0.187698E+10 0.108127E+10 0.795712E+09 0.00 0.00
Maximum of Months 0.657993E+10 0.359269E+10 0.487871E+10 0.256118E+10 0.240599E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113759E+11 0.471421E+10 0.986853E+10 0.811791E+10 0.175061E+10 0.00 0.00
February 0.980494E+10 0.436339E+10 0.854971E+10 0.681636E+10 0.173336E+10 0.00 0.00
March 0.813484E+10 0.379538E+10 0.697889E+10 0.459170E+10 0.238719E+10 0.00 0.00
April 0.468640E+10 0.328824E+10 0.437425E+10 0.175889E+10 0.261536E+10 0.00 0.00
May 0.484200E+10 0.210182E+10 0.414215E+10 0.759219E+09 0.338293E+10 0.00 0.00
June 0.538980E+10 0.114190E+10 0.369574E+10 0.675470E+09 0.302027E+10 0.00 0.00
July 0.580168E+10 0.109656E+10 0.397541E+10 0.711879E+09 0.326354E+10 0.00 0.00
August 0.738887E+10 0.129743E+10 0.506150E+10 0.211588E+10 0.294562E+10 0.00 0.00
September 0.859832E+10 0.195335E+10 0.630203E+10 0.351648E+10 0.278555E+10 0.00 0.00
October 0.946619E+10 0.400439E+10 0.778655E+10 0.552472E+10 0.226183E+10 0.00 0.00
November 0.107966E+11 0.442067E+10 0.918079E+10 0.731841E+10 0.186238E+10 0.00 0.00
December 0.102589E+11 0.524721E+10 0.907187E+10 0.734263E+10 0.172923E+10 0.00 0.00
               
Annual Sum or Average 0.965444E+11 0.374246E+11 0.789874E+11 0.492495E+11 0.297379E+11 0.00 0.00
Minimum of Months 0.468640E+10 0.109656E+10 0.369574E+10 0.675470E+09 0.172923E+10 0.00 0.00
Maximum of Months 0.113759E+11 0.524721E+10 0.986853E+10 0.811791E+10 0.338293E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.222042E+10 0.321576E+10 0.228670E+10 0.144898E+10 0.837728E+09 0.00 0.00
February 0.239805E+10 0.295301E+10 0.249059E+10 0.154343E+10 0.947167E+09 0.00 0.00
March 0.330907E+10 0.251201E+10 0.322879E+10 0.178139E+10 0.144740E+10 0.00 0.00
April 0.287922E+10 0.215207E+10 0.294199E+10 0.124558E+10 0.169640E+10 0.00 0.00
May 0.426946E+10 0.141166E+10 0.371573E+10 0.130993E+10 0.240580E+10 0.00 0.00
June 0.601478E+10 0.816103E+09 0.439796E+10 0.211602E+10 0.228194E+10 0.00 0.00
July 0.508332E+10 0.762288E+09 0.370274E+10 0.135624E+10 0.234650E+10 0.00 0.00
August 0.521706E+10 0.877277E+09 0.386461E+10 0.190916E+10 0.195545E+10 0.00 0.00
September 0.426256E+10 0.129539E+10 0.331621E+10 0.159034E+10 0.172587E+10 0.00 0.00
October 0.312121E+10 0.266410E+10 0.288280E+10 0.164773E+10 0.123507E+10 0.00 0.00
November 0.225220E+10 0.296267E+10 0.228919E+10 0.138982E+10 0.899371E+09 0.00 0.00
December 0.168917E+10 0.361231E+10 0.191067E+10 0.112868E+10 0.781990E+09 0.00 0.00
               
Annual Sum or Average 0.427165E+11 0.252346E+11 0.370280E+11 0.184673E+11 0.185607E+11 0.00 0.00
Minimum of Months 0.168917E+10 0.762288E+09 0.191067E+10 0.112868E+10 0.781990E+09 0.00 0.00
Maximum of Months 0.601478E+10 0.361231E+10 0.439796E+10 0.211602E+10 0.240580E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.194169E+09 0.504432E+10 0.102974E+10 0.00 0.102974E+10 0.00 0.00
February 0.219056E+09 0.460352E+10 0.116901E+10 0.00 0.116901E+10 0.00 0.00
March 0.802886E+09 0.389531E+10 0.176107E+10 0.00 0.176107E+10 0.00 0.00
April 0.117884E+10 0.326579E+10 0.214030E+10 11873484.46 0.212843E+10 0.00 0.00
May 0.271780E+10 0.201281E+10 0.302124E+10 99870170.09 0.292137E+10 0.00 0.00
June 0.425891E+10 0.107785E+10 0.320613E+10 0.355452E+09 0.285068E+10 0.00 0.00
July 0.421166E+10 0.105514E+10 0.313320E+10 0.202818E+09 0.293038E+10 0.00 0.00
August 0.320170E+10 0.121421E+10 0.249379E+10 58994652.25 0.243479E+10 0.00 0.00
September 0.228425E+10 0.182491E+10 0.202721E+10 476155.58 0.202673E+10 0.00 0.00
October 0.808162E+09 0.388963E+10 0.150037E+10 0.00 0.150037E+10 0.00 0.00
November 0.303298E+09 0.444934E+10 0.110223E+10 0.00 0.110223E+10 0.00 0.00
December 0.168843E+09 0.562274E+10 0.963454E+09 0.00 0.963454E+09 0.00 0.00
               
Annual Sum or Average 0.203496E+11 0.379556E+11 0.235478E+11 0.729484E+09 0.228183E+11 0.00 0.00
Minimum of Months 0.168843E+09 0.105514E+10 0.963454E+09 0.00 0.963454E+09 0.00 0.00
Maximum of Months 0.425891E+10 0.562274E+10 0.320613E+10 0.355452E+09 0.293038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.190585E+10 0.316238E+10 0.214964E+10 0.131736E+10 0.832275E+09 0.00 0.00
February 0.241897E+10 0.294451E+10 0.257921E+10 0.162825E+10 0.950966E+09 0.00 0.00
March 0.348881E+10 0.250226E+10 0.344658E+10 0.201036E+10 0.143622E+10 0.00 0.00
April 0.338779E+10 0.212624E+10 0.342063E+10 0.166625E+10 0.175438E+10 0.00 0.00
May 0.466255E+10 0.135739E+10 0.413195E+10 0.172593E+10 0.240602E+10 0.00 0.00
June 0.653695E+10 0.725106E+09 0.487878E+10 0.256123E+10 0.231755E+10 0.00 0.00
July 0.619271E+10 0.710296E+09 0.458304E+10 0.218233E+10 0.240071E+10 0.00 0.00
August 0.620885E+10 0.814659E+09 0.462263E+10 0.254598E+10 0.207665E+10 0.00 0.00
September 0.473292E+10 0.117063E+10 0.372219E+10 0.202200E+10 0.170019E+10 0.00 0.00
October 0.290770E+10 0.253691E+10 0.278546E+10 0.152627E+10 0.125919E+10 0.00 0.00
November 0.195751E+10 0.286758E+10 0.209818E+10 0.118466E+10 0.913528E+09 0.00 0.00
December 0.159243E+10 0.356210E+10 0.187702E+10 0.108129E+10 0.795721E+09 0.00 0.00
               
Annual Sum or Average 0.459930E+11 0.244801E+11 0.402953E+11 0.214519E+11 0.188434E+11 0.00 0.00
Minimum of Months 0.159243E+10 0.710296E+09 0.187702E+10 0.108129E+10 0.795721E+09 0.00 0.00
Maximum of Months 0.653695E+10 0.356210E+10 0.487878E+10 0.256123E+10 0.240602E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.112957E+11 0.459536E+10 0.986892E+10 0.811825E+10 0.175067E+10 0.00 0.00
February 0.969662E+10 0.431468E+10 0.855005E+10 0.681664E+10 0.173341E+10 0.00 0.00
March 0.801992E+10 0.382695E+10 0.697916E+10 0.459189E+10 0.238727E+10 0.00 0.00
April 0.457647E+10 0.336257E+10 0.437441E+10 0.175897E+10 0.261544E+10 0.00 0.00
May 0.471589E+10 0.220942E+10 0.414228E+10 0.759251E+09 0.338303E+10 0.00 0.00
June 0.532515E+10 0.118501E+10 0.369585E+10 0.675498E+09 0.302035E+10 0.00 0.00
July 0.574088E+10 0.113523E+10 0.397554E+10 0.711908E+09 0.326363E+10 0.00 0.00
August 0.735145E+10 0.128382E+10 0.506167E+10 0.211597E+10 0.294570E+10 0.00 0.00
September 0.857652E+10 0.187165E+10 0.630226E+10 0.351663E+10 0.278563E+10 0.00 0.00
October 0.943016E+10 0.385278E+10 0.778685E+10 0.552495E+10 0.226190E+10 0.00 0.00
November 0.107338E+11 0.425559E+10 0.918115E+10 0.731871E+10 0.186244E+10 0.00 0.00
December 0.101751E+11 0.511654E+10 0.907223E+10 0.734294E+10 0.172929E+10 0.00 0.00
               
Annual Sum or Average 0.956377E+11 0.370096E+11 0.789904E+11 0.492516E+11 0.297388E+11 0.00 0.00
Minimum of Months 0.457647E+10 0.113523E+10 0.369585E+10 0.675498E+09 0.172929E+10 0.00 0.00
Maximum of Months 0.112957E+11 0.511654E+10 0.986892E+10 0.811825E+10 0.338303E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.218576E+10 0.324053E+10 0.228674E+10 0.144900E+10 0.837735E+09 0.00 0.00
February 0.235723E+10 0.298585E+10 0.249063E+10 0.154345E+10 0.947175E+09 0.00 0.00
March 0.325079E+10 0.255799E+10 0.322883E+10 0.178142E+10 0.144741E+10 0.00 0.00
April 0.282673E+10 0.218398E+10 0.294203E+10 0.124560E+10 0.169642E+10 0.00 0.00
May 0.420759E+10 0.144547E+10 0.371577E+10 0.130995E+10 0.240582E+10 0.00 0.00
June 0.598222E+10 0.816409E+09 0.439802E+10 0.211606E+10 0.228196E+10 0.00 0.00
July 0.504966E+10 0.772374E+09 0.370279E+10 0.135626E+10 0.234652E+10 0.00 0.00
August 0.519791E+10 0.864349E+09 0.386466E+10 0.190920E+10 0.195546E+10 0.00 0.00
September 0.425646E+10 0.125416E+10 0.331625E+10 0.159036E+10 0.172589E+10 0.00 0.00
October 0.311595E+10 0.258728E+10 0.288284E+10 0.164776E+10 0.123508E+10 0.00 0.00
November 0.224224E+10 0.290424E+10 0.228922E+10 0.138984E+10 0.899379E+09 0.00 0.00
December 0.167253E+10 0.357673E+10 0.191070E+10 0.112870E+10 0.781997E+09 0.00 0.00
               
Annual Sum or Average 0.423451E+11 0.251894E+11 0.370285E+11 0.184676E+11 0.185609E+11 0.00 0.00
Minimum of Months 0.167253E+10 0.772374E+09 0.191070E+10 0.112870E+10 0.781997E+09 0.00 0.00
Maximum of Months 0.598222E+10 0.357673E+10 0.439802E+10 0.211606E+10 0.240582E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 0.85 -1.5 -4.5 2.30 -12.1 27.63 226.20 0.01
February -0.2 -2.7 -6.1 3.74 -13.6 32.55 253.27 0.01
March 4.82 0.36 -5.5 4.48 -7.8 54.65 233.06 0.03
April 6.08 2.29 -2.0 5.23 -4.9 81.86 179.11 0.05
May 13.74 7.52 1.82 4.10 2.75 117.64 180.87 0.01
June 22.16 12.46 5.10 4.19 9.76 95.26 290.95 0.00
July 22.71 13.25 6.43 4.25 12.01 110.54 215.12 0.03
August 21.74 12.79 6.20 3.81 10.76 77.72 272.61 0.02
September 18.54 9.35 1.35 4.13 5.52 70.51 233.03 0.01
October 7.12 2.51 -2.7 3.54 -5.8 44.60 216.74 0.01
November 3.03 0.31 -2.9 2.79 -8.8 30.71 220.86 0.01
December -1.0 -4.5 -9.5 4.43 -15.4 27.45 194.75 0.01
                 
Annual Sum or Average 10.02 4.37 -1.0 3.91 -2.2 64.46 226.11 0.02
Minimum of Months -1.0 -4.5 -9.5 2.30 -15.4 27.45 179.11 0.00
Maximum of Months 22.71 13.25 6.43 5.23 12.01 117.64 290.95 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 20-JAN-12:00 6.97 -11.0 0.50 6.55 41.00 961.00
February 20.00 18-FEB-12:00 7.74 -5.0 3.60 6.35 56.00 998.00
March 24.00 14-MAR-12:00 7.90 -12.0 3.10 11.65 160.00 837.50
April 22.00 19-APR-13:09 8.49 -5.7 5.52 11.55 235.67 789.67
May 29.00 17-MAY-12:00 11.92 -3.0 5.10 18.99 432.50 162.00
June 39.40 26-JUN-14:00 15.63 -2.8 4.60 21.96 136.50 752.00
July 37.00 16-JUL-12:00 14.90 -3.0 3.10 26.65 319.50 109.50
August 37.00 16-AUG-13:00 16.36 3.00 3.60 28.27 90.00 895.00
September 32.70 09-SEP-12:00 13.05 -3.9 3.00 16.30 270.50 562.00
October 27.00 11-OCT-13:00 9.73 -9.0 4.60 12.03 89.50 844.00
November 22.00 06-NOV-13:09 7.10 -13.0 2.60 4.92 88.67 883.33
December 22.00 01-DEC-13:00 7.94 -8.0 2.60 5.13 49.00 862.00
                 
Annual Sum or Average                
Minimum of Months 20.00   6.97 -13.0 0.50 4.92 41.00 109.50
Maximum of Months 39.40   16.36 3.00 5.52 28.27 432.50 998.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -19.0 05-JAN-18:00 -19.0 -19.0 1.50 -37.1 0.00 0.00
February -20.0 12-FEB-04:00 -20.0 -20.0 3.60 -39.1 0.00 0.00
March -15.6 19-MAR-06:00 -15.6 -15.6 10.80 -25.3 24.00 0.00
April -8.0 03-APR-02:00 -8.0 -8.0 3.10 -22.2 0.00 0.00
May -1.0 03-MAY-01:00 -2.4 -4.0 4.10 -15.7 0.00 0.00
June 6.60 09-JUN-03:00 3.45 0.00 3.60 -6.9 0.00 0.00
July 9.00 02-JUL-04:00 3.30 -3.0 3.60 -5.3 20.00 184.50
August 11.00 12-AUG-22:00 7.22 4.00 4.10 5.13 0.00 0.00
September -1.7 22-SEP-05:10 -2.9 -4.3 3.60 -15.8 0.00 0.00
October -10.0 30-OCT-03:00 -10.0 -10.0 2.60 -18.6 0.00 0.00
November -15.0 29-NOV-20:00 -15.0 -15.0 3.10 -33.5 0.00 0.00
December -23.0 22-DEC-02:00 -23.0 -23.0 3.60 -42.7 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -23.0   -23.0 -23.0 1.50 -42.7 0.00 0.00
Maximum of Months 11.00   7.22 4.00 10.80 5.13 24.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 7.55 20-JAN-11:00 20.00 -6.0 2.60 7.95 43.00 971.50
February 7.98 18-FEB-14:00 19.00 -3.0 3.60 5.94 151.00 410.00
March 8.00 31-MAR-17:00 15.00 2.00 2.60 1.58 19.50 261.00
April 12.50 28-APR-13:00 18.00 9.00 9.80 9.72 335.00 196.50
May 14.87 31-MAY-13:00 28.00 7.00 4.60 14.47 157.50 830.50
June 19.65 18-JUN-11:00 29.40 15.50 6.10 16.85 272.50 596.00
July 19.75 30-JUL-13:00 29.00 16.00 3.60 18.99 217.50 412.00
August 18.80 05-AUG-14:09 25.83 15.33 6.62 20.54 196.33 4.00
September 14.95 01-SEP-11:00 24.40 9.40 3.00 10.69 193.50 684.00
October 9.73 11-OCT-13:00 27.00 -9.0 4.60 12.03 89.50 844.00
November 9.33 09-NOV-10:00 20.00 0.00 1.50 11.07 112.00 860.50
December 7.94 01-DEC-13:00 22.00 -8.0 2.60 5.13 49.00 862.00
                 
Annual Sum or Average                
Minimum of Months 7.55   15.00 -9.0 1.50 1.58 19.50 4.00
Maximum of Months 19.75   29.40 16.00 9.80 20.54 335.00 971.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 5.00 28-JAN-10:00 5.00 5.00 1.00 -6.2 207.00 309.00
February 5.00 19-FEB-14:30 5.00 5.00 1.80 -0.4 188.00 467.00
March 7.00 17-MAR-14:00 8.00 7.39 8.20 1.16 121.50 3.00
April 9.00 28-APR-13:00 18.00 12.50 9.80 9.72 335.00 196.50
May 11.00 21-MAY-21:10 12.83 11.73 2.68 6.78 0.00 0.00
June 15.50 18-JUN-11:00 29.40 19.65 6.10 16.85 272.50 596.00
July 17.00 28-JUL-16:00 20.00 17.92 5.70 15.02 155.00 32.00
August 18.00 04-AUG-01:00 18.00 18.00 2.60 8.74 0.00 0.00
September 12.20 30-SEP-14:00 17.20 13.90 5.10 9.72 209.00 82.50
October 6.00 01-OCT-19:00 9.00 7.28 3.10 3.69 0.00 0.00
November 7.00 09-NOV-23:00 8.00 7.40 4.10 3.06 0.00 0.00
December 1.00 30-DEC-14:00 7.00 4.06 9.80 -1.2 101.00 91.50
                 
Annual Sum or Average                
Minimum of Months 1.00   5.00 4.06 1.00 -6.2 0.00 0.00
Maximum of Months 18.00   29.40 19.65 9.80 16.85 335.00 596.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 8.52 21.53 0.00
February 18.00 13.00 16.00 7.90 29.36 0.00
March 18.00 13.00 16.00 8.65 35.75 0.00
April 18.00 13.00 16.00 10.64 38.62 0.00
May 18.00 13.00 16.00 13.34 48.35 0.00
June 18.00 13.00 16.00 16.03 59.81 0.00
July 18.00 13.00 16.00 17.97 52.29 0.00
August 18.00 13.00 16.00 18.66 51.98 0.00
September 18.00 13.00 16.00 17.88 41.73 0.00
October 18.00 13.00 16.00 15.85 30.82 0.00
November 18.00 13.00 16.00 13.14 23.90 0.00
December 18.00 13.00 16.00 10.46 18.59 0.00
             
Annual Sum or Average 18.00 13.00 16.00 13.28 37.76 0.00
Minimum of Months 18.00 13.00 16.00 7.90 18.59 0.00
Maximum of Months 18.00 13.00 16.00 18.66 59.81 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.510182E+10 -0.486322E+10 0.00 0.00 744.00 0.00 -238596336.3 60.05 0.00 0.00
February 0.468887E+10 -0.447350E+10 0.00 0.00 672.00 0.00 -215372119.9 60.05 0.00 0.00
March 0.545593E+10 -0.521901E+10 0.00 0.00 744.00 0.00 -236922144.8 60.05 0.00 0.00
April 0.474371E+10 -0.451551E+10 0.00 0.00 720.00 0.00 -228202785.8 60.05 0.00 0.00
May 0.481467E+10 -0.458213E+10 0.00 0.00 744.00 0.00 -232540895.0 60.05 0.00 0.00
June 0.451251E+10 -0.428800E+10 0.00 0.00 720.00 0.00 -224510837.0 60.05 0.00 0.00
July 0.409144E+10 -0.386026E+10 0.00 0.00 744.00 0.00 -231183317.0 60.05 0.00 0.00
August 0.443429E+10 -0.420254E+10 0.00 0.00 744.00 0.00 -231749037.0 60.05 0.00 0.00
September 0.407949E+10 -0.385535E+10 0.00 0.00 720.00 0.00 -224137448.4 60.05 0.00 0.00
October 0.440603E+10 -0.417274E+10 0.00 0.00 744.00 0.00 -233296186.2 60.05 0.00 0.00
November 0.458155E+10 -0.435358E+10 0.00 0.00 720.00 0.00 -227969178.9 60.05 0.00 0.00
December 0.479110E+10 -0.455072E+10 0.00 0.00 744.00 0.00 -240378120.6 60.05 0.00 0.00
                     
Annual Sum or Average 0.557014E+11 -0.529366E+11 0.00 0.00 8760.00 0.00 -0.276486E+10 60.05 0.00 0.00
Minimum of Months 0.407949E+10 -0.521901E+10 0.00 0.00 672.00 0.00 -240378120.6 60.05 0.00 0.00
Maximum of Months 0.545593E+10 -0.385535E+10 0.00 0.00 744.00 0.00 -215372119.9 60.05 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.50 0.48 01-JAN-07:49 10608.03 39.55 274.17 267.83 5719.64 35.01 235.50 259.67
February 245.50 0.49 0.48 01-FEB-10:39 14167.50 39.31 241.00 264.33 2392.44 24.90 117.50 243.67
March 296.17 0.50 0.48 01-MAR-06:00 2839.00 19.18 18.33 327.33 1624.12 21.08 131.00 293.00
April 296.67 0.50 0.48 03-APR-09:39 2130.57 18.95 8.33 340.67 1246.71 21.17 163.00 303.33
May 415.33 0.50 0.48 01-MAY-06:10 1901.51 19.05 0.83 393.00 1053.77 21.25 261.67 357.17
June 421.50 0.50 0.48 01-JUN-05:49 1543.19 18.56 0.00 392.33 927.84 20.84 187.17 352.50
July 430.33 0.51 0.48 01-JUL-06:10 1732.54 18.69 2.83 396.00 985.19 20.91 236.67 357.50
August 394.50 0.51 0.48 01-AUG-06:10 1864.30 18.43 4.67 371.33 1143.72 20.67 171.83 337.00
September 354.00 0.50 0.48 01-SEP-06:19 3030.28 20.24 39.50 333.00 1425.63 21.08 169.33 305.00
October 262.67 0.49 0.48 01-OCT-06:40 13789.60 36.66 239.83 300.50 2004.95 21.67 123.83 277.33
November 257.67 0.49 0.48 01-NOV-08:39 12101.16 39.11 250.50 264.67 3682.56 29.94 180.00 243.17
December 251.17 0.49 0.48 01-DEC-07:40 9938.22 39.96 250.67 258.50 8039.11 40.64 248.33 248.00
                         
Annual Sum or Average 3902.00 0.50     5411.17 25.59 1330.67 3909.50 2235.50 24.13 2225.83 3577.33
Minimum of Months 245.50 0.49 0.48   1543.19 18.43 0.00 258.50 927.84 20.67 117.50 243.17
Maximum of Months 430.33 0.51 0.48   14167.50 39.96 274.17 396.00 8039.11 40.64 261.67 357.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.53 0.48 01-JAN-07:49 2470.79 21.00 82.67 235.00 1495.14 23.48 97.00 205.83
February 245.50 0.50 0.48 01-FEB-10:39 3941.77 23.33 84.33 250.83 2348.44 23.86 73.00 206.17
March 296.17 0.50 0.48 01-MAR-06:49 3771.68 22.39 83.50 319.83 2112.10 23.24 77.33 281.17
April 296.67 0.50 0.48 03-APR-09:39 4103.61 21.88 84.83 341.83 1828.33 22.74 58.67 303.33
May 415.33 0.50 0.48 01-MAY-05:40 3292.41 21.79 111.67 400.67 1795.85 23.03 88.00 367.50
June 421.50 0.50 0.48 01-JUN-04:00 3919.40 21.43 109.00 404.67 2258.66 23.52 92.17 376.17
July 430.33 0.50 0.48 01-JUL-05:10 3526.81 21.64 116.33 406.67 1909.60 22.72 87.83 374.83
August 394.50 0.51 0.48 01-AUG-05:40 4852.18 22.98 131.00 373.50 1938.65 22.15 70.00 340.00
September 354.00 0.50 0.48 01-SEP-05:49 3960.04 22.54 108.33 332.33 1557.02 21.78 67.17 308.83
October 262.67 0.50 0.48 01-OCT-06:19 3651.12 22.94 79.83 290.33 2053.80 23.69 68.00 250.00
November 257.67 0.52 0.48 01-NOV-08:39 2486.69 21.33 70.50 242.83 1298.53 21.79 81.00 201.67
December 251.17 0.52 0.48 01-DEC-07:40 2621.82 23.62 91.83 233.00 1547.91 24.16 97.17 195.17
                         
Annual Sum or Average 3902.00 0.50     3612.72 22.18 1153.83 3831.50 1859.65 22.96 957.33 3410.67
Minimum of Months 245.50 0.50 0.48   2470.79 21.00 70.50 233.00 1298.53 21.78 58.67 195.17
Maximum of Months 430.33 0.53 0.48   4852.18 23.62 131.00 406.67 2348.44 24.16 97.17 376.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.55 0.48 01-JAN-08:00 561.88 14.46 0.00 219.17 375.14 17.24 0.00 156.50
February 245.50 0.51 0.48 01-FEB-10:39 669.75 16.01 0.00 241.33 462.42 18.71 1.50 176.17
March 296.17 0.50 0.48 01-MAR-07:19 869.31 17.35 0.00 315.67 564.64 19.73 10.83 261.33
April 296.67 0.50 0.48 03-APR-09:39 1160.94 18.58 0.00 345.67 690.29 20.73 78.33 302.17
May 415.33 0.49 0.48 01-MAY-05:00 1410.42 19.27 4.50 408.67 785.99 21.47 204.00 381.00
June 421.50 0.49 0.48 01-JUN-04:00 1542.23 21.90 76.17 418.17 863.67 24.04 255.17 404.83
July 430.33 0.49 0.48 01-JUL-05:30 1453.34 20.28 35.67 420.00 805.96 22.46 236.83 393.50
August 394.50 0.50 0.48 01-AUG-05:00 1130.92 18.46 2.83 380.00 701.28 20.64 113.83 347.00
September 354.00 0.50 0.48 01-SEP-06:19 952.33 17.85 0.00 330.83 602.78 20.13 42.83 290.33
October 262.67 0.51 0.48 01-OCT-06:00 812.11 17.11 0.00 281.33 547.99 19.64 1.33 218.67
November 257.67 0.53 0.48 01-NOV-08:50 630.78 15.48 0.00 229.50 429.70 18.22 0.33 168.67
December 251.17 0.53 0.48 01-DEC-08:30 580.44 15.08 0.00 217.83 385.47 17.88 0.00 151.17
                         
Annual Sum or Average 3902.00 0.51     1047.62 18.05 119.17 3808.17 632.52 20.42 945.00 3251.33
Minimum of Months 245.50 0.49 0.48   561.88 14.46 0.00 217.83 375.14 17.24 0.00 151.17
Maximum of Months 430.33 0.55 0.48   1542.23 21.90 76.17 420.00 863.67 24.04 255.17 404.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.51 0.48 01-JAN-08:00 2956.45 24.16 108.67 252.17 1770.26 24.45 104.33 219.00
February 245.50 0.49 0.48 01-FEB-10:39 3024.31 21.70 68.50 255.83 1733.33 23.94 73.67 214.17
March 296.17 0.49 0.48 01-MAR-07:30 3562.68 22.98 99.33 328.50 2025.92 23.79 91.17 294.50
April 296.67 0.50 0.48 03-APR-09:39 3330.95 21.52 85.33 347.50 1513.87 21.47 39.33 312.50
May 415.33 0.50 0.48 01-MAY-06:30 2880.74 18.33 53.17 398.50 1519.72 19.14 6.50 367.50
June 421.50 0.50 0.48 01-JUN-05:49 3421.95 15.28 1.83 403.33 1934.97 18.78 1.00 378.33
July 430.33 0.50 0.48 01-JUL-06:10 2885.83 17.92 54.83 405.33 1579.80 18.93 7.50 376.17
August 394.50 0.50 0.48 01-AUG-06:19 2994.80 17.88 53.67 380.67 1706.67 18.89 8.33 357.50
September 354.00 0.50 0.48 01-SEP-06:40 3332.56 22.34 109.83 334.50 1810.81 23.37 98.67 310.00
October 262.67 0.50 0.48 01-OCT-06:00 4290.26 23.95 93.83 295.83 1695.50 23.65 66.50 260.00
November 257.67 0.50 0.48 01-NOV-08:50 2991.04 24.46 96.50 252.67 1714.95 25.00 99.83 214.50
December 251.17 0.51 0.48 01-DEC-08:30 2355.03 22.36 80.67 240.67 1422.42 24.74 93.83 212.83
                         
Annual Sum or Average 3902.00 0.50     3161.00 20.54 906.17 3895.50 1704.14 21.70 690.67 3517.00
Minimum of Months 245.50 0.49 0.48   2355.03 15.28 1.83 240.67 1422.42 18.78 1.00 212.83
Maximum of Months 430.33 0.51 0.48   4290.26 24.46 109.83 405.33 2025.92 25.00 104.33 378.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.50 0.48 01-JAN-07:49 10373.60 39.34 274.17 267.83 5523.90 33.85 205.33 259.00
February 245.50 0.49 0.48 01-FEB-10:39 13943.54 39.05 241.00 263.00 2197.93 22.23 69.67 240.83
March 296.17 0.50 0.48 01-MAR-06:00 2723.10 15.35 10.33 327.83 1497.05 18.54 19.00 289.67
April 296.67 0.51 0.48 03-APR-09:39 2026.45 15.27 0.00 339.00 1171.96 18.80 16.83 298.67
May 415.33 0.50 0.48 01-MAY-06:10 1823.21 15.36 0.00 391.50 1003.21 18.85 3.50 354.17
June 421.50 0.51 0.48 01-JUN-05:49 1481.48 15.08 0.00 390.00 889.14 18.67 0.00 348.83
July 430.33 0.51 0.48 01-JUL-06:10 1662.14 15.06 0.00 394.17 940.20 18.57 4.33 354.67
August 394.50 0.51 0.48 01-AUG-06:10 1773.32 14.85 0.00 369.00 1078.52 18.41 20.00 333.83
September 354.00 0.50 0.48 01-SEP-06:19 2900.87 16.73 29.50 331.50 1326.52 18.58 15.33 302.33
October 262.67 0.49 0.48 01-OCT-06:40 13588.53 36.18 239.67 300.00 1839.24 18.86 21.67 273.67
November 257.67 0.49 0.48 01-NOV-08:39 11850.67 38.57 248.50 262.83 3481.37 27.91 131.83 240.83
December 251.17 0.49 0.48 01-DEC-07:40 9577.86 37.58 233.50 254.33 7837.92 40.39 247.17 246.33
                         
Annual Sum or Average 3902.00 0.50     5266.78 22.92 1276.67 3891.00 2126.57 21.96 754.67 3542.83
Minimum of Months 245.50 0.49 0.48   1481.48 14.85 0.00 254.33 889.14 18.41 0.00 240.83
Maximum of Months 430.33 0.51 0.48   13943.54 39.34 274.17 394.17 7837.92 40.39 247.17 354.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.53 0.48 01-JAN-07:49 2406.25 20.52 82.67 233.67 1442.05 23.27 94.00 203.33
February 245.50 0.50 0.48 01-FEB-10:39 3857.75 22.86 84.33 249.50 2277.68 23.66 70.67 204.50
March 296.17 0.50 0.48 01-MAR-06:49 3506.00 20.27 68.83 315.67 2031.95 23.04 72.00 279.17
April 296.67 0.50 0.48 03-APR-09:39 3997.26 21.42 84.83 340.83 1745.70 22.55 54.50 298.17
May 415.33 0.50 0.48 01-MAY-05:40 3194.45 21.34 111.67 399.33 1723.71 22.84 86.17 364.67
June 421.50 0.50 0.48 01-JUN-04:00 3811.40 20.96 109.00 402.50 2149.97 22.57 79.83 373.50
July 430.33 0.50 0.48 01-JUL-05:10 3417.29 21.06 114.50 404.50 1832.86 22.56 86.67 372.17
August 394.50 0.51 0.48 01-AUG-05:40 4657.50 21.37 116.50 368.83 1849.40 21.98 69.83 337.50
September 354.00 0.50 0.48 01-SEP-05:49 3866.36 22.08 108.33 330.33 1479.41 21.59 61.00 307.00
October 262.67 0.50 0.48 01-OCT-06:19 3556.48 22.47 79.83 289.00 1974.79 23.48 63.50 244.50
November 257.67 0.52 0.48 01-NOV-08:39 2392.56 20.69 69.50 239.67 1238.95 21.57 76.83 200.33
December 251.17 0.52 0.48 01-DEC-07:49 2406.15 21.34 78.00 228.33 1495.91 23.95 93.50 192.17
                         
Annual Sum or Average 3902.00 0.51     3485.78 21.33 1108.00 3802.17 1782.53 22.69 908.50 3377.00
Minimum of Months 245.50 0.50 0.48   2392.56 20.27 68.83 228.33 1238.95 21.57 54.50 192.17
Maximum of Months 430.33 0.53 0.48   4657.50 22.86 116.50 404.50 2277.68 23.95 94.00 373.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.55 0.48 01-JAN-08:00 541.66 10.86 0.00 214.67 365.10 14.80 0.00 150.67
February 245.50 0.51 0.48 01-FEB-10:39 647.35 12.57 0.00 239.00 451.84 16.51 0.00 172.00
March 296.17 0.51 0.48 01-MAR-07:30 840.34 14.11 0.00 313.67 550.13 17.76 0.00 253.00
April 296.67 0.50 0.48 03-APR-09:39 1121.65 15.32 0.00 344.17 669.16 18.82 9.50 295.67
May 415.33 0.49 0.48 01-MAY-05:00 1361.02 15.67 0.00 406.67 758.51 19.31 20.50 377.00
June 421.50 0.49 0.48 01-JUN-04:00 1460.28 15.87 0.00 416.33 834.75 22.29 110.17 402.67
July 430.33 0.49 0.48 01-JUL-05:30 1396.28 15.58 0.00 416.50 777.93 20.45 61.67 391.83
August 394.50 0.50 0.48 01-AUG-05:00 1118.37 15.17 0.00 380.83 681.46 18.77 22.17 344.00
September 354.00 0.50 0.48 01-SEP-06:30 919.91 14.63 0.00 327.67 586.01 18.22 0.00 286.67
October 262.67 0.51 0.48 01-OCT-06:00 783.29 13.87 0.00 278.50 533.83 17.63 0.00 212.67
November 257.67 0.53 0.48 01-NOV-08:50 607.60 11.97 0.00 225.83 418.32 15.90 0.00 164.83
December 251.17 0.54 0.48 01-DEC-08:30 557.96 11.47 0.00 215.00 374.08 15.43 0.00 144.67
                         
Annual Sum or Average 3902.00 0.51     1010.06 14.22 0.00 3778.83 613.33 18.37 224.00 3195.67
Minimum of Months 245.50 0.49 0.48   541.66 10.86 0.00 214.67 365.10 14.80 0.00 144.67
Maximum of Months 430.33 0.55 0.48   1460.28 15.87 0.00 416.50 834.75 22.29 110.17 402.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.52 0.48 01-JAN-08:00 2891.23 23.80 108.67 250.00 1715.82 24.36 104.00 215.67
February 245.50 0.49 0.48 01-FEB-10:39 2937.24 21.28 68.50 254.17 1661.33 23.84 72.83 210.50
March 296.17 0.50 0.48 01-MAR-07:30 3476.67 22.57 99.33 326.67 1955.01 23.67 88.33 289.50
April 296.67 0.50 0.48 03-APR-09:39 3244.53 21.08 85.33 344.83 1447.07 21.31 38.83 308.33
May 415.33 0.50 0.48 01-MAY-06:30 2792.87 17.83 53.17 397.00 1454.50 18.96 4.67 364.33
June 421.50 0.50 0.48 01-JUN-05:00 3322.49 14.75 1.83 401.17 1841.17 18.60 1.00 374.83
July 430.33 0.50 0.48 01-JUL-06:10 2800.80 17.42 54.83 403.83 1517.12 18.74 5.50 374.67
August 394.50 0.50 0.48 01-AUG-06:19 2908.59 17.39 53.67 379.67 1637.99 18.72 7.83 354.33
September 354.00 0.50 0.48 01-SEP-06:40 3251.92 21.91 109.83 332.17 1739.44 23.04 94.50 306.00
October 262.67 0.50 0.48 01-OCT-06:00 4193.72 23.45 92.83 294.00 1554.14 22.47 57.00 252.83
November 257.67 0.50 0.48 01-NOV-08:50 2755.46 21.58 77.17 248.83 1654.72 24.91 99.17 212.50
December 251.17 0.51 0.48 01-DEC-08:30 2289.34 21.97 80.67 239.67 1368.88 24.66 92.50 208.83
                         
Annual Sum or Average 3902.00 0.50     3066.01 19.92 885.83 3872.00 1630.95 21.47 666.17 3472.33
Minimum of Months 245.50 0.49 0.48   2289.34 14.75 1.83 239.67 1368.88 18.60 1.00 208.83
Maximum of Months 430.33 0.52 0.48   4193.72 23.80 109.83 403.83 1955.01 24.91 104.00 374.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.50 0.48 01-JAN-07:49 10373.60 39.34 274.17 267.83 5523.82 33.85 205.33 259.00
February 245.50 0.49 0.48 01-FEB-10:39 13943.51 39.05 241.00 263.00 2197.85 22.23 69.67 240.83
March 296.17 0.50 0.48 01-MAR-06:00 2723.01 15.35 10.33 327.83 1496.97 18.54 19.00 289.67
April 296.67 0.51 0.48 03-APR-09:39 2026.34 15.28 0.00 339.00 1171.87 18.80 16.83 298.67
May 415.33 0.50 0.48 01-MAY-06:10 1823.10 15.36 0.00 391.50 1003.13 18.85 3.50 354.17
June 421.50 0.51 0.48 01-JUN-05:49 1481.42 15.08 0.00 390.00 889.08 18.67 0.17 348.67
July 430.33 0.51 0.48 01-JUL-06:10 1662.05 15.06 0.00 394.17 940.13 18.57 4.33 354.67
August 394.50 0.51 0.48 01-AUG-06:10 1773.24 14.85 0.00 369.00 1078.45 18.41 20.00 333.67
September 354.00 0.50 0.48 01-SEP-06:19 2900.76 16.73 29.50 331.50 1326.43 18.58 15.33 302.33
October 262.67 0.49 0.48 01-OCT-06:40 13588.46 36.18 239.67 300.00 1839.15 18.86 21.67 273.67
November 257.67 0.49 0.48 01-NOV-08:39 11850.67 38.57 248.50 262.83 3481.27 27.91 131.83 240.83
December 251.17 0.49 0.48 01-DEC-07:40 9577.89 37.58 233.50 254.33 7837.83 40.39 247.17 246.33
                         
Annual Sum or Average 3902.00 0.50     5266.71 22.92 1276.67 3891.00 2126.49 21.96 754.83 3542.50
Minimum of Months 245.50 0.49 0.48   1481.42 14.85 0.00 254.33 889.08 18.41 0.17 240.83
Maximum of Months 430.33 0.51 0.48   13943.51 39.34 274.17 394.17 7837.83 40.39 247.17 354.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.53 0.48 01-JAN-07:49 2406.24 20.52 82.67 233.67 1442.02 23.27 94.00 203.33
February 245.50 0.50 0.48 01-FEB-10:39 3857.75 22.86 84.33 249.50 2277.64 23.66 70.83 204.50
March 296.17 0.50 0.48 01-MAR-06:49 3505.98 20.27 68.83 315.67 2031.89 23.04 72.00 279.17
April 296.67 0.50 0.48 03-APR-09:39 3997.21 21.42 84.83 340.83 1745.63 22.56 54.50 298.17
May 415.33 0.50 0.48 01-MAY-05:40 3194.38 21.34 111.67 399.33 1723.62 22.84 86.33 364.67
June 421.50 0.50 0.48 01-JUN-04:00 3811.36 20.96 109.00 402.50 2149.89 22.57 79.83 373.50
July 430.33 0.50 0.48 01-JUL-05:10 3417.23 21.06 114.50 404.50 1832.78 22.56 86.67 372.17
August 394.50 0.51 0.48 01-AUG-05:40 4657.46 21.37 116.50 368.83 1849.33 21.98 69.83 337.50
September 354.00 0.50 0.48 01-SEP-05:49 3866.32 22.08 108.33 330.33 1479.35 21.59 61.00 307.00
October 262.67 0.50 0.48 01-OCT-06:19 3556.47 22.47 79.83 289.00 1974.74 23.48 63.50 244.50
November 257.67 0.52 0.48 01-NOV-08:39 2392.56 20.70 69.50 239.67 1238.91 21.57 76.83 200.33
December 251.17 0.52 0.48 01-DEC-07:49 2406.14 21.35 78.00 228.33 1495.88 23.95 93.50 192.17
                         
Annual Sum or Average 3902.00 0.51     3485.75 21.34 1108.00 3802.17 1782.47 22.69 908.83 3377.00
Minimum of Months 245.50 0.50 0.48   2392.56 20.27 68.83 228.33 1238.91 21.57 54.50 192.17
Maximum of Months 430.33 0.53 0.48   4657.46 22.86 116.50 404.50 2277.64 23.95 94.00 373.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.55 0.48 01-JAN-08:00 541.66 10.86 0.00 214.67 365.08 14.80 0.00 150.67
February 245.50 0.51 0.48 01-FEB-10:39 647.35 12.58 0.00 239.00 451.82 16.51 0.00 172.00
March 296.17 0.51 0.48 01-MAR-07:30 840.33 14.11 0.00 313.67 550.10 17.76 0.00 253.00
April 296.67 0.50 0.48 03-APR-09:39 1121.62 15.32 0.00 344.17 669.12 18.82 9.50 295.67
May 415.33 0.49 0.48 01-MAY-05:00 1360.97 15.67 0.00 406.67 758.46 19.31 20.50 377.00
June 421.50 0.49 0.48 01-JUN-04:00 1460.24 15.87 0.00 416.33 834.70 22.29 110.17 402.67
July 430.33 0.49 0.48 01-JUL-05:30 1396.23 15.58 0.00 416.50 777.88 20.45 61.67 391.83
August 394.50 0.50 0.48 01-AUG-05:00 1118.35 15.18 0.00 380.83 681.42 18.77 22.17 344.00
September 354.00 0.50 0.48 01-SEP-06:30 919.89 14.64 0.00 327.67 585.98 18.22 0.00 286.67
October 262.67 0.51 0.48 01-OCT-06:00 783.29 13.87 0.00 278.50 533.80 17.63 0.00 212.67
November 257.67 0.53 0.48 01-NOV-08:50 607.60 11.97 0.00 225.83 418.30 15.90 0.00 164.83
December 251.17 0.54 0.48 01-DEC-08:30 557.96 11.47 0.00 215.00 374.06 15.43 0.00 144.67
                         
Annual Sum or Average 3902.00 0.51     1010.04 14.22 0.00 3778.83 613.30 18.37 224.00 3195.67
Minimum of Months 245.50 0.49 0.48   541.66 10.86 0.00 214.67 365.08 14.80 0.00 144.67
Maximum of Months 430.33 0.55 0.48   1460.24 15.87 0.00 416.50 834.70 22.29 110.17 402.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 276.50 0.52 0.48 01-JAN-08:00 2891.22 23.80 108.67 250.00 1715.78 24.36 104.00 215.67
February 245.50 0.49 0.48 01-FEB-10:39 2937.24 21.28 68.50 254.17 1661.29 23.84 72.83 210.50
March 296.17 0.50 0.48 01-MAR-07:30 3476.65 22.57 99.33 326.67 1954.95 23.67 88.50 289.50
April 296.67 0.50 0.48 03-APR-09:39 3244.47 21.08 85.33 344.83 1447.00 21.31 38.83 308.33
May 415.33 0.50 0.48 01-MAY-06:30 2792.78 17.84 53.17 397.00 1454.41 18.96 4.67 364.33
June 421.50 0.50 0.48 01-JUN-05:00 3322.44 14.75 1.83 401.17 1841.10 18.60 1.00 374.83
July 430.33 0.50 0.48 01-JUL-06:10 2800.73 17.43 54.83 403.83 1517.04 18.74 5.67 374.67
August 394.50 0.50 0.48 01-AUG-06:19 2908.56 17.40 53.67 379.67 1637.93 18.72 7.83 354.33
September 354.00 0.50 0.48 01-SEP-06:40 3251.88 21.92 109.83 332.17 1739.37 23.04 94.50 306.00
October 262.67 0.50 0.48 01-OCT-06:00 4193.72 23.46 92.83 294.00 1554.09 22.47 57.00 252.83
November 257.67 0.50 0.48 01-NOV-08:50 2755.46 21.58 77.17 248.83 1654.68 24.91 99.17 212.50
December 251.17 0.51 0.48 01-DEC-08:30 2289.33 21.97 80.67 239.67 1368.84 24.66 92.50 208.83
                         
Annual Sum or Average 3902.00 0.50     3065.97 19.92 885.83 3872.00 1630.89 21.47 666.50 3472.33
Minimum of Months 245.50 0.49 0.48   2289.33 14.75 1.83 239.67 1368.84 18.60 1.00 208.83
Maximum of Months 430.33 0.52 0.48   4193.72 23.80 109.83 403.83 1954.95 24.91 104.00 374.83



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT HEATING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.713196E+10 18626.85 05-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.735654E+10 17657.03 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.465978E+10 17047.96 29-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.267366E+10 17260.94 17-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 0.172529E+09 8497.76 02-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 305184.92 4.77 19-JUN-09:50 0.00 0.00 0.00 0.00 0.00
July 642982.84 5.02 25-JUL-14:05 0.00 0.00 0.00 0.00 0.00
August 428659.87 4.96 29-AUG-10:30 0.00 0.00 0.00 0.00 0.00
September 0.114261E+09 8142.22 22-SEP-06:07 0.00 0.00 0.00 0.00 0.00
October 0.270083E+10 17502.93 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.529029E+10 17729.94 30-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.841048E+10 19565.12 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.385117E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 305184.92 4.77   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.841048E+10 19565.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 177519.58 1183.46 26-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 177519.58     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 177519.58 1183.46   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.203316E+10 9227.05 05-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 0.238684E+10 8529.63 28-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.208742E+10 8308.94 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.149595E+10 8469.65 10-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.523892E+09 8536.93 09-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 10775856.89 8180.14 09-JUN-06:06 0.00 0.00 0.00 0.00 0.00
July 2286098.94 1961.76 03-JUL-06:07 0.00 0.00 0.00 0.00 0.00
August 1015045.05 3228.92 23-AUG-06:08 0.00 0.00 0.00 0.00 0.00
September 84932102.35 8562.97 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.148176E+10 8572.17 03-OCT-06:03 0.00 0.00 0.00 0.00 0.00
November 0.156512E+10 8779.89 29-NOV-18:03 0.00 0.00 0.00 0.00 0.00
December 0.296450E+10 9633.82 21-DEC-17:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.146376E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 1015045.05 1961.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.296450E+10 9633.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.648024E+09 6974.54 05-JAN-18:12 0.00 0.00 0.00 0.00 0.00
February 0.815544E+09 6399.30 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.379777E+09 6193.10 07-MAR-06:11 0.00 0.00 0.00 0.00 0.00
April 0.157626E+09 6245.23 17-APR-06:01 0.00 0.00 0.00 0.00 0.00
May 655632.67 3029.79 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.177334E+09 6340.61 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.262760E+09 6424.18 30-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.116773E+10 7164.07 21-DEC-17:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.360945E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116773E+10 7164.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.172782E+10 7618.84 05-JAN-19:00 0.00 0.00 0.00 0.00 0.00
February 0.192479E+10 7088.84 28-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.938107E+09 6850.89 02-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.402321E+09 7005.74 11-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 11859800.33 6789.71 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.296291E+09 7101.24 23-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.614807E+09 7150.75 30-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.232855E+10 7860.75 21-DEC-17:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.824455E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.232855E+10 7860.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.671702E+09 7236.32 05-JAN-08:18 0.00 0.00 0.00 0.00 0.00
February 0.831850E+09 6718.39 06-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.421800E+09 6540.74 02-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.194322E+09 6567.99 17-APR-06:12 0.00 0.00 0.00 0.00 0.00
May 5579286.93 6479.93 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.180047E+09 6656.53 30-OCT-06:01 0.00 0.00 0.00 0.00 0.00
November 0.251639E+09 6744.80 30-NOV-07:01 0.00 0.00 0.00 0.00 0.00
December 0.123601E+10 7497.23 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.379295E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.123601E+10 7497.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID HEATING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.756227E+10 19950.52 05-JAN-07:35 0.00 0.00 0.00 0.00 0.00
February 0.771113E+10 18912.12 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.524677E+10 18390.51 02-MAR-07:01 0.00 0.00 0.00 0.00 0.00
April 0.330295E+10 16592.76 03-APR-06:07 0.00 0.00 0.00 0.00 0.00
May 0.338928E+09 8736.74 02-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 321294.74 204.59 09-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 539489.57 4.82 24-JUL-06:03 0.00 0.00 0.00 0.00 0.00
August 327748.65 4.38 28-AUG-13:20 0.00 0.00 0.00 0.00 0.00
September 0.236754E+09 9017.78 22-SEP-06:03 0.00 0.00 0.00 0.00 0.00
October 0.361440E+10 18996.81 30-OCT-06:12 0.00 0.00 0.00 0.00 0.00
November 0.615507E+10 19076.76 29-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.915261E+10 20676.79 23-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.433221E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 321294.74 4.38   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.915261E+10 20676.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.177362E+09 17506.86 17-JAN-07:04 0.00 0.00 0.00 0.00 0.00
February 0.399672E+09 17460.30 08-FEB-07:04 0.00 0.00 0.00 0.00 0.00
March 0.108106E+09 17419.54 20-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 47276127.83 17429.57 17-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 48996094.62 17398.64 30-OCT-06:02 0.00 0.00 0.00 0.00 0.00
November 52051299.17 17399.30 01-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.922942E+09 17490.67 26-DEC-06:17 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175641E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.922942E+09 17506.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.547928E+09 9517.93 05-JAN-07:35 0.00 0.00 0.00 0.00 0.00
February 0.830236E+09 8999.27 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.428386E+09 8882.81 20-MAR-06:13 0.00 0.00 0.00 0.00 0.00
April 0.265513E+09 8873.09 03-APR-06:04 0.00 0.00 0.00 0.00 0.00
May 7996057.15 8844.32 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 175989.99 1433.77 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.417837E+09 9043.37 30-OCT-06:12 0.00 0.00 0.00 0.00 0.00
November 0.402605E+09 9081.96 29-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.127151E+10 9882.22 23-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.417218E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127151E+10 9882.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.601623E+09 7729.33 05-JAN-19:00 0.00 0.00 0.00 0.00 0.00
February 0.687542E+09 7008.79 02-FEB-07:01 0.00 0.00 0.00 0.00 0.00
March 0.282305E+09 6900.43 22-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.151977E+09 6891.19 03-APR-12:01 0.00 0.00 0.00 0.00 0.00
May 588215.47 3659.23 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 44816.72 448.17 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.297522E+09 7043.60 30-OCT-06:12 0.00 0.00 0.00 0.00 0.00
November 0.394024E+09 7073.77 29-NOV-07:12 0.00 0.00 0.00 0.00 0.00
December 0.140675E+10 8071.71 21-DEC-16:55 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.382238E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140675E+10 8071.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.126719E+10 7914.61 05-JAN-07:35 0.00 0.00 0.00 0.00 0.00
February 0.137250E+10 7591.43 13-FEB-07:06 0.00 0.00 0.00 0.00 0.00
March 0.574873E+09 7439.60 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.300474E+09 7499.58 17-APR-06:06 0.00 0.00 0.00 0.00 0.00
May 6203707.29 7362.15 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 438475.89 2152.53 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.451973E+09 7633.86 30-OCT-06:06 0.00 0.00 0.00 0.00 0.00
November 0.764465E+09 7714.81 29-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.244553E+10 8480.54 21-DEC-17:09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.718365E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.244553E+10 8480.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.641223E+09 7922.71 05-JAN-08:23 0.00 0.00 0.00 0.00 0.00
February 0.750549E+09 7352.96 13-FEB-07:06 0.00 0.00 0.00 0.00 0.00
March 0.327162E+09 7202.54 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.190845E+09 7122.06 26-APR-06:02 0.00 0.00 0.00 0.00 0.00
May 5321548.17 6536.28 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 824683.87 2496.59 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.296816E+09 7285.67 30-OCT-06:12 0.00 0.00 0.00 0.00 0.00
November 0.415009E+09 7417.12 30-NOV-07:06 0.00 0.00 0.00 0.00 0.00
December 0.153775E+10 8147.07 21-DEC-10:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.416550E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153775E+10 8147.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP HEATING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.799809E+10 19149.69 05-JAN-08:45 0.00 0.00 0.00 0.00 0.00
February 0.816793E+10 17451.69 02-FEB-07:16 0.00 0.00 0.00 0.00 0.00
March 0.560943E+10 18083.33 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.357849E+10 17508.45 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 0.440584E+09 10502.72 02-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 1274904.22 1200.86 09-JUN-06:04 0.00 0.00 0.00 0.00 0.00
July 489031.55 5.13 31-JUL-14:50 0.00 0.00 0.00 0.00 0.00
August 302750.59 4.99 03-AUG-10:30 0.00 0.00 0.00 0.00 0.00
September 0.294706E+09 13854.18 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.410342E+10 17877.86 30-OCT-06:09 0.00 0.00 0.00 0.00 0.00
November 0.658184E+10 18044.28 29-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.981266E+10 19462.90 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.465892E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 302750.59 4.99   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.981266E+10 19462.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.184608E+10 24400.44 05-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.214911E+10 24199.11 21-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 0.956519E+09 24199.74 21-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.672655E+09 24204.18 05-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 19511657.93 24027.05 01-MAY-06:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.797734E+09 24113.80 31-OCT-05:06 0.00 0.00 0.00 0.00 0.00
November 0.105319E+10 24180.17 03-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.365619E+10 25103.51 23-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.111510E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.365619E+10 25103.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.147394E+10 11702.83 05-JAN-08:45 0.00 0.00 0.00 0.00 0.00
February 0.185068E+10 10630.04 06-FEB-08:30 0.00 0.00 0.00 0.00 0.00
March 0.120853E+10 11077.85 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.770584E+09 10659.38 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 55043279.49 10622.94 02-MAY-05:12 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 17120023.74 10598.40 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.105804E+10 10815.42 31-OCT-06:17 0.00 0.00 0.00 0.00 0.00
November 0.117414E+10 10997.35 29-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.280872E+10 11863.03 20-DEC-20:55 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104168E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.280872E+10 11863.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.141649E+10 8880.54 05-JAN-18:01 0.00 0.00 0.00 0.00 0.00
February 0.149436E+10 8247.10 02-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.803712E+09 7860.58 27-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.459035E+09 7888.86 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 15690134.66 7838.95 02-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 8452493.65 7843.85 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.752497E+09 8004.53 31-OCT-06:17 0.00 0.00 0.00 0.00 0.00
November 0.103407E+10 8157.55 02-NOV-06:07 0.00 0.00 0.00 0.00 0.00
December 0.273575E+10 9300.07 21-DEC-16:55 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.872005E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.273575E+10 9300.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.285829E+10 10080.68 05-JAN-18:23 0.00 0.00 0.00 0.00 0.00
February 0.295592E+10 9376.03 02-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.156845E+10 9325.75 02-MAR-07:12 0.00 0.00 0.00 0.00 0.00
April 0.881608E+09 9063.25 03-APR-07:03 0.00 0.00 0.00 0.00 0.00
May 51385510.73 8953.77 03-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 19725795.39 8923.34 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.119325E+10 9424.88 30-OCT-07:12 0.00 0.00 0.00 0.00 0.00
November 0.202309E+10 9357.36 29-NOV-07:50 0.00 0.00 0.00 0.00 0.00
December 0.479439E+10 10295.60 22-DEC-08:25 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163461E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.479439E+10 10295.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.157202E+10 9567.64 05-JAN-10:10 0.00 0.00 0.00 0.00 0.00
February 0.167494E+10 8455.47 01-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.930101E+09 8829.68 04-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.551912E+09 8492.96 15-APR-06:03 0.00 0.00 0.00 0.00 0.00
May 36169215.37 8461.97 03-MAY-06:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 13938329.63 8444.04 22-SEP-06:02 0.00 0.00 0.00 0.00 0.00
October 0.764988E+09 8618.35 31-OCT-06:17 0.00 0.00 0.00 0.00 0.00
November 0.114392E+10 8764.81 29-NOV-07:17 0.00 0.00 0.00 0.00 0.00
December 0.304847E+10 9769.47 22-DEC-08:25 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.973646E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.304847E+10 9769.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_BOT COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.314348E+10 0.312868E+10 30392.94 23-JAN-16:00 30392.94 0.00
February 0.00 0.00 0.136758E+10 0.135076E+10 17744.35 18-FEB-12:00 17744.35 0.00
March 0.00 0.00 0.402132E+10 0.401559E+10 39904.80 13-MAR-16:00 39904.80 0.00
April 0.00 0.00 0.509721E+10 0.497912E+10 32361.04 12-APR-14:10 32361.04 0.00
May 0.00 0.00 0.146845E+11 0.143920E+11 50268.62 31-MAY-16:00 50268.62 0.00
June 0.00 0.00 0.544203E+11 0.519154E+11 79419.84 26-JUN-15:20 79419.84 0.00
July 0.00 0.00 0.553920E+11 0.510377E+11 75230.76 31-JUL-15:00 53531.73 0.00
August 0.00 0.00 0.546399E+11 0.518616E+11 73265.48 16-AUG-16:00 73265.48 0.00
September 0.00 0.00 0.382332E+11 0.376675E+11 66039.18 11-SEP-15:00 66039.18 0.00
October 0.00 0.00 0.126580E+11 0.125555E+11 57947.80 10-OCT-15:30 57947.80 0.00
November 0.00 0.00 0.369644E+10 0.366147E+10 33472.00 07-NOV-15:10 33472.00 0.00
December 0.00 0.00 0.154664E+10 0.154446E+10 22425.20 14-DEC-15:10 22425.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.248901E+12 0.238110E+12       0.00
Minimum of Months 0.00 0.00 0.136758E+10 0.135076E+10 17744.35   17744.35 0.00
Maximum of Months 0.00 0.00 0.553920E+11 0.519154E+11 79419.84   79419.84 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_MID COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.191206E+10 0.189717E+10 23810.02 24-JAN-15:05 23810.02 0.00
February 0.00 0.00 0.109316E+10 0.106654E+10 16170.44 18-FEB-13:05 16170.44 0.00
March 0.00 0.00 0.379707E+10 0.379381E+10 39256.56 13-MAR-15:50 39256.56 0.00
April 0.00 0.00 0.286784E+10 0.282950E+10 25973.13 20-APR-13:00 25973.13 0.00
May 0.00 0.00 0.136546E+11 0.132965E+11 49588.52 16-MAY-14:05 49588.52 0.00
June 0.00 0.00 0.498065E+11 0.475471E+11 74659.79 26-JUN-15:20 74659.79 0.00
July 0.00 0.00 0.505299E+11 0.466782E+11 71081.58 17-JUL-12:02 71081.58 0.00
August 0.00 0.00 0.480937E+11 0.456987E+11 69079.10 16-AUG-15:00 69079.10 0.00
September 0.00 0.00 0.319416E+11 0.314364E+11 61891.57 11-SEP-14:05 61891.57 0.00
October 0.00 0.00 0.768924E+10 0.764880E+10 51501.14 11-OCT-14:05 51501.14 0.00
November 0.00 0.00 0.308199E+10 0.304506E+10 31041.87 07-NOV-15:05 31041.87 0.00
December 0.00 0.00 0.125716E+10 0.125278E+10 19858.56 01-DEC-14:00 19858.56 0.00
                 
Annual Sum or Average 0.00 0.00 0.215725E+12 0.206191E+12       0.00
Minimum of Months 0.00 0.00 0.109316E+10 0.106654E+10 16170.44   16170.44 0.00
Maximum of Months 0.00 0.00 0.505299E+11 0.475471E+11 74659.79   74659.79 0.00



Table of Contents

Report: CoilReportMonthly

For: PACU_VAV_TOP COOLING COIL

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.103896E+10 0.102037E+10 20908.44 20-JAN-14:10 20908.44 0.00
February 0.00 0.00 0.144632E+10 0.141805E+10 20579.08 27-FEB-15:10 20579.08 0.00
March 0.00 0.00 0.371211E+10 0.370895E+10 40700.12 13-MAR-15:50 40700.12 0.00
April 0.00 0.00 0.279370E+10 0.274271E+10 27866.88 20-APR-13:00 27866.88 0.00
May 0.00 0.00 0.145211E+11 0.140220E+11 57976.35 31-MAY-15:20 57976.35 0.00
June 0.00 0.00 0.543468E+11 0.518699E+11 86490.00 26-JUN-15:10 86490.00 0.00
July 0.00 0.00 0.544878E+11 0.504002E+11 79826.75 31-JUL-14:20 59497.50 0.00
August 0.00 0.00 0.520154E+11 0.494835E+11 81807.74 16-AUG-15:10 81807.74 0.00
September 0.00 0.00 0.329507E+11 0.322795E+11 69392.85 12-SEP-15:40 69392.85 0.00
October 0.00 0.00 0.658264E+10 0.654088E+10 56377.08 11-OCT-15:00 56377.08 0.00
November 0.00 0.00 0.263198E+10 0.258597E+10 30079.51 07-NOV-14:50 30079.51 0.00
December 0.00 0.00 0.107413E+10 0.106662E+10 18784.53 01-DEC-14:00 18784.53 0.00
                 
Annual Sum or Average 0.00 0.00 0.227602E+12 0.217139E+12       0.00
Minimum of Months 0.00 0.00 0.103896E+10 0.102037E+10 18784.53   18784.53 0.00
Maximum of Months 0.00 0.00 0.544878E+11 0.518699E+11 86490.00   86490.00 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 14878.18 182308.07 05-JAN-07:11
February 0.00 0.00 01-FEB-00:10 17773.61 177024.32 06-FEB-07:05
March 0.00 0.00 01-MAR-00:10 9820.70 168082.15 30-MAR-06:01
April 0.00 0.00 01-APR-00:10 6156.99 167784.06 25-APR-06:02
May 0.00 0.00 01-MAY-00:10 630.87 157001.58 02-MAY-06:02
June 0.00 0.00 01-JUN-00:10 4.47 9177.60 09-JUN-06:06
July 0.00 0.00 01-JUL-00:10 0.85 1307.03 03-JUL-06:07
August 0.00 0.00 01-AUG-00:10 0.67 4909.15 23-AUG-06:08
September 0.00 0.00 01-SEP-00:10 301.18 98841.74 22-SEP-06:02
October 0.00 0.00 01-OCT-00:10 6903.52 163006.61 30-OCT-06:02
November 0.00 0.00 01-NOV-00:10 11160.87 167205.05 30-NOV-07:12
December 0.00 0.00 01-DEC-00:10 22121.36 196516.58 23-DEC-07:15
             
Annual Sum or Average 0.00     7428.51    
Minimum of Months 0.00 0.00   0.67 1307.03  
Maximum of Months 0.00 0.00   22121.36 196516.58  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 1806.24 6633.33 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 1839.64 6650.95 14-FEB-12:10
March 0.00 0.00 01-MAR-00:10 1938.73 6625.00 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 1732.73 6419.00 03-APR-11:12
May 0.00 0.00 01-MAY-00:10 1701.34 6125.94 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 1644.90 5759.52 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 1432.33 5439.66 03-JUL-11:50
August 0.00 0.00 01-AUG-00:10 1559.71 5288.00 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 1478.36 5461.90 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 1548.77 5790.88 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 1670.26 6145.88 30-NOV-12:10
December 0.00 0.00 01-DEC-00:10 1689.79 6442.60 29-DEC-12:30
             
Annual Sum or Average 0.00     1669.26    
Minimum of Months 0.00 0.00   1432.33 5288.00  
Maximum of Months 0.00 0.00   1938.73 6650.95  



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_BOT FAN

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.170169E+10 0.39 5520.68 26-JAN-07:02 1.35
February 0.157770E+10 0.39 5219.35 28-FEB-07:02 1.30
March 0.226993E+10 0.43 6931.32 15-MAR-16:00 1.55
April 0.188490E+10 0.38 5219.35 11-APR-06:02 1.30
May 0.335538E+10 0.46 6952.95 16-MAY-14:30 1.54
June 0.720343E+10 0.73 12111.91 12-JUN-12:10 2.19
July 0.686918E+10 0.70 12111.91 17-JUL-10:50 2.19
August 0.713286E+10 0.71 11756.19 18-AUG-16:00 2.15
September 0.568652E+10 0.64 12111.91 05-SEP-06:02 2.19
October 0.305123E+10 0.46 7658.78 10-OCT-08:50 1.64
November 0.206081E+10 0.40 5424.58 08-NOV-16:00 1.33
December 0.161698E+10 0.38 5394.86 05-DEC-07:02 1.33
           
Annual Sum or Average 0.444106E+11 0.51      
Minimum of Months 0.157770E+10 0.38 5219.35   1.30
Maximum of Months 0.720343E+10 0.73 12111.91   2.19



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_MID FAN

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.145517E+10 0.40 3090.60 20-JAN-16:10 0.99
February 0.138562E+10 0.40 3140.01 27-FEB-15:30 1.00
March 0.198563E+10 0.45 7006.06 15-MAR-16:00 1.62
April 0.168349E+10 0.41 4617.61 21-APR-13:40 1.25
May 0.302527E+10 0.48 7190.64 16-MAY-14:05 1.63
June 0.638145E+10 0.70 11422.97 26-JUN-10:10 2.18
July 0.604803E+10 0.66 11422.97 17-JUL-05:12 2.19
August 0.608194E+10 0.67 11422.97 07-AUG-10:10 2.18
September 0.442559E+10 0.57 11422.97 05-SEP-06:02 2.19
October 0.217903E+10 0.44 7684.02 10-OCT-16:00 1.71
November 0.157236E+10 0.41 4620.95 07-NOV-16:00 1.26
December 0.144669E+10 0.41 3040.36 11-DEC-07:03 0.99
           
Annual Sum or Average 0.376703E+11 0.50      
Minimum of Months 0.138562E+10 0.40 3040.36   0.99
Maximum of Months 0.638145E+10 0.70 11422.97   2.19



Table of Contents

Report: FanReportMonthly

For: PACU_VAV_TOP FAN

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.164013E+10 0.46 2996.26 04-JAN-06:01 0.90
February 0.161985E+10 0.49 2996.26 06-FEB-07:02 0.90
March 0.207578E+10 0.51 6719.03 15-MAR-15:50 1.44
April 0.177592E+10 0.45 4841.80 21-APR-13:30 1.17
May 0.279491E+10 0.48 6985.03 31-MAY-15:20 1.45
June 0.607008E+10 0.65 11899.41 26-JUN-15:10 2.03
July 0.565545E+10 0.61 12104.53 17-JUL-10:40 2.06
August 0.568679E+10 0.61 11573.10 14-AUG-15:00 2.00
September 0.391561E+10 0.53 10391.33 05-SEP-15:30 1.86
October 0.206418E+10 0.46 7125.00 11-OCT-16:00 1.49
November 0.161550E+10 0.44 3789.72 07-NOV-15:50 1.02
December 0.183046E+10 0.51 2996.26 11-DEC-07:17 0.90
           
Annual Sum or Average 0.367447E+11 0.52      
Minimum of Months 0.161550E+10 0.44 2996.26   0.90
Maximum of Months 0.607008E+10 0.65 12104.53   2.06



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.305969E+09 0.278126E+09 766.95 07-JAN-07:03 697.15 697.15 43.92 2.49
February 0.335207E+09 0.304703E+09 732.72 06-FEB-08:30 666.04 666.04 44.50 2.37
March 0.213079E+09 0.193688E+09 703.63 29-MAR-06:01 639.60 639.60 43.31 2.24
April 0.124443E+09 0.113119E+09 723.81 03-APR-06:40 657.94 657.94 45.65 2.33
May 15589752.65 14171085.15 633.46 01-MAY-06:03 575.82 575.82 39.78 1.70
June 160311.11 145722.80 117.51 09-JUN-06:06 106.81 106.81 43.01 0.13
July 27589.52 25078.87 16.89 03-JUL-06:07 15.35 15.35 42.09 0.02
August 20314.32 18465.71 54.41 23-AUG-06:08 49.46 49.46 39.60 0.06
September 6621667.41 6019095.68 536.61 22-SEP-06:02 487.77 487.77 35.53 0.97
October 0.142194E+09 0.129254E+09 732.21 31-OCT-06:12 665.58 665.58 43.56 2.37
November 0.231385E+09 0.210329E+09 732.89 30-NOV-07:17 666.20 666.20 44.02 2.37
December 0.413190E+09 0.375589E+09 784.65 23-DEC-07:03 713.24 713.24 42.33 2.54
                 
Annual Sum or Average 0.178789E+10 0.162519E+10            
Minimum of Months 20314.32 18465.71 16.89   15.35 15.35 35.53 0.02
Maximum of Months 0.413190E+09 0.375589E+09 784.65   713.24 713.24 45.65 2.54



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 12379742.02 3713922.60 6.85 01-JAN-06:10 2.06 2.06 58.03 0.05
February 11196021.66 3358806.50 6.85 01-FEB-06:01 2.06 2.06 56.97 0.05
March 12675672.10 3802701.63 6.85 01-MAR-06:02 2.06 2.06 56.93 0.05
April 11960507.72 3588152.32 6.85 01-APR-05:05 2.06 2.06 56.72 0.05
May 12527707.06 3758312.12 6.85 01-MAY-05:05 2.06 2.06 56.98 0.05
June 12231776.97 3669533.09 6.85 01-JUN-05:03 2.06 2.06 57.16 0.05
July 12256437.81 3676931.34 6.85 01-JUL-05:05 2.06 2.06 57.23 0.05
August 12675672.10 3802701.63 6.85 01-AUG-05:03 2.06 2.06 57.40 0.05
September 11960507.72 3588152.32 6.85 01-SEP-05:03 2.06 2.06 57.39 0.05
October 12379742.02 3713922.60 6.85 01-OCT-05:10 2.06 2.06 58.21 0.05
November 12059151.09 3617745.33 6.85 01-NOV-05:01 2.06 2.06 57.36 0.05
December 12256437.81 3676931.34 6.85 01-DEC-06:05 2.06 2.06 56.87 0.05
                 
Annual Sum or Average 0.146559E+09 43967812.83            
Minimum of Months 11196021.66 3358806.50 6.85   2.06 2.06 56.72 0.05
Maximum of Months 12675672.10 3802701.63 6.85   2.06 2.06 58.21 0.05



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 40.62 40.62 14878.18 182308.07 05-JAN-07:11
February 0.00 0.00 01-FEB-00:10 42.04 42.04 17773.61 177024.32 06-FEB-07:05
March 0.00 0.00 01-MAR-00:10 33.89 33.89 9820.70 168082.15 30-MAR-06:01
April 0.00 0.00 01-APR-00:10 31.39 31.39 6156.99 167784.06 25-APR-06:02
May 0.00 0.00 01-MAY-00:10 22.53 22.53 630.87 157001.58 02-MAY-06:02
June 0.00 0.00 01-JUN-00:10 43.51 43.51 4.47 9177.60 09-JUN-06:06
July 0.00 0.00 01-JUL-00:10 42.13 42.13 0.85 1307.03 03-JUL-06:07
August 0.00 0.00 01-AUG-00:10 39.65 39.65 0.67 4909.15 23-AUG-06:08
September 0.00 0.00 01-SEP-00:10 39.27 39.27 301.18 98841.74 22-SEP-06:02
October 0.00 0.00 01-OCT-00:10 33.64 33.64 6903.52 163006.61 30-OCT-06:02
November 0.00 0.00 01-NOV-00:10 45.84 45.84 11160.87 167205.05 30-NOV-07:12
December 0.00 0.00 01-DEC-00:10 40.02 40.02 22121.36 196516.58 23-DEC-07:15
                 
Annual Sum or Average 0.00         7428.51    
Minimum of Months 0.00 0.00   22.53 22.53 0.67 1307.03  
Maximum of Months 0.00 0.00   45.84 45.84 22121.36 196516.58  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 58.03 58.03 1806.24 6633.33 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 57.45 57.45 1839.64 6650.95 14-FEB-12:10
March 0.00 0.00 01-MAR-00:10 57.46 57.46 1938.73 6625.00 01-MAR-13:00
April 0.00 0.00 01-APR-00:10 57.53 57.53 1732.73 6419.00 03-APR-11:12
May 0.00 0.00 01-MAY-00:10 58.13 58.13 1701.34 6125.94 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 57.80 57.80 1644.90 5759.52 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.92 57.92 1432.33 5439.66 03-JUL-11:50
August 0.00 0.00 01-AUG-00:10 57.99 57.99 1559.71 5288.00 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 57.98 57.98 1478.36 5461.90 29-SEP-11:40
October 0.00 0.00 01-OCT-00:10 57.05 57.05 1548.77 5790.88 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 57.79 57.79 1670.26 6145.88 30-NOV-12:10
December 0.00 0.00 01-DEC-00:10 57.65 57.65 1689.79 6442.60 29-DEC-12:30
                 
Annual Sum or Average 0.00         1669.26    
Minimum of Months 0.00 0.00   57.05 57.05 1432.33 5288.00  
Maximum of Months 0.00 0.00   58.13 58.13 1938.73 6650.95  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: FIRSTFLOOR_PLENUM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.122127E+11 0.00 0.00 0.243293E+10 0.00 0.00
February 0.133156E+11 0.00 0.00 0.192070E+10 0.00 0.00
March 0.848689E+10 0.00 0.00 0.320662E+10 0.00 0.00
April 0.492387E+10 0.00 0.00 0.310662E+10 0.00 0.00
May 0.714516E+09 0.00 0.00 0.672736E+10 0.00 0.00
June 11081041.81 0.00 0.00 0.204103E+11 0.00 0.00
July 2929081.77 0.00 0.00 0.201089E+11 0.00 0.00
August 1443704.92 0.00 0.00 0.201370E+11 0.00 0.00
September 0.199193E+09 0.00 0.00 0.144954E+11 0.00 0.00
October 0.483626E+10 0.00 0.00 0.591562E+10 0.00 0.00
November 0.798462E+10 0.00 0.00 0.293037E+10 0.00 0.00
December 0.161074E+11 0.00 0.00 0.199542E+10 0.00 0.00
             
Annual Sum or Average 0.687965E+11 0.00 0.00 0.103387E+12 0.00 0.00
Minimum of Months 1443704.92 0.00 0.00 0.192070E+10 0.00 0.00
Maximum of Months 0.161074E+11 0.00 0.00 0.204103E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.107976E+11 0.00 0.00 0.191344E+10 0.00 0.00
February 0.117516E+11 0.00 0.00 0.166221E+10 0.00 0.00
March 0.696760E+10 0.00 0.00 0.286316E+10 0.00 0.00
April 0.425903E+10 0.00 0.00 0.237540E+10 0.00 0.00
May 0.359038E+09 0.00 0.00 0.615927E+10 0.00 0.00
June 321294.74 0.00 0.00 0.185020E+11 0.00 0.00
July 539489.57 0.00 0.00 0.181730E+11 0.00 0.00
August 327748.65 0.00 0.00 0.175932E+11 0.00 0.00
September 0.238237E+09 0.00 0.00 0.118379E+11 0.00 0.00
October 0.512754E+10 0.00 0.00 0.394143E+10 0.00 0.00
November 0.818323E+10 0.00 0.00 0.230508E+10 0.00 0.00
December 0.167371E+11 0.00 0.00 0.175858E+10 0.00 0.00
             
Annual Sum or Average 0.644222E+11 0.00 0.00 0.890847E+11 0.00 0.00
Minimum of Months 321294.74 0.00 0.00 0.166221E+10 0.00 0.00
Maximum of Months 0.167371E+11 0.00 0.00 0.185020E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.171649E+11 0.00 0.00 0.189870E+10 0.00 0.00
February 0.182929E+11 0.00 0.00 0.198432E+10 0.00 0.00
March 0.110768E+11 0.00 0.00 0.294253E+10 0.00 0.00
April 0.691428E+10 0.00 0.00 0.245450E+10 0.00 0.00
May 0.618384E+09 0.00 0.00 0.615908E+10 0.00 0.00
June 1274904.22 0.00 0.00 0.194103E+11 0.00 0.00
July 489031.55 0.00 0.00 0.188604E+11 0.00 0.00
August 302750.59 0.00 0.00 0.182623E+11 0.00 0.00
September 0.353942E+09 0.00 0.00 0.116492E+11 0.00 0.00
October 0.866994E+10 0.00 0.00 0.359534E+10 0.00 0.00
November 0.130102E+11 0.00 0.00 0.225402E+10 0.00 0.00
December 0.268562E+11 0.00 0.00 0.210146E+10 0.00 0.00
             
Annual Sum or Average 0.102960E+12 0.00 0.00 0.915722E+11 0.00 0.00
Minimum of Months 302750.59 0.00 0.00 0.189870E+10 0.00 0.00
Maximum of Months 0.268562E+11 0.00 0.00 0.194103E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.170169E+10 0.314348E+10 0.122127E+11 0.00 0.00 0.00 0.00 0.00
February 0.157770E+10 0.136758E+10 0.133156E+11 0.00 0.00 0.00 0.00 0.00
March 0.226993E+10 0.402132E+10 0.848689E+10 0.00 0.00 0.00 0.00 0.00
April 0.188490E+10 0.509721E+10 0.492387E+10 0.00 0.00 0.00 0.00 0.00
May 0.335538E+10 0.146845E+11 0.714516E+09 0.00 0.00 0.00 0.00 0.00
June 0.720343E+10 0.544203E+11 11081041.81 0.00 0.00 0.00 0.00 0.00
July 0.686918E+10 0.553920E+11 2929081.77 0.00 0.00 0.00 0.00 0.00
August 0.713286E+10 0.546399E+11 1443704.92 0.00 0.00 0.00 0.00 0.00
September 0.568652E+10 0.382332E+11 0.199193E+09 0.00 0.00 0.00 0.00 0.00
October 0.305123E+10 0.126580E+11 0.483626E+10 0.00 0.00 0.00 0.00 0.00
November 0.206081E+10 0.369644E+10 0.798462E+10 0.00 0.00 0.00 0.00 0.00
December 0.161698E+10 0.154664E+10 0.161074E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.444106E+11 0.248901E+12 0.687965E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.157770E+10 0.136758E+10 1443704.92 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.720343E+10 0.553920E+11 0.161074E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.145517E+10 0.191206E+10 0.107976E+11 0.00 0.00 0.00 0.00 0.00
February 0.138562E+10 0.109316E+10 0.117516E+11 0.00 0.00 0.00 0.00 0.00
March 0.198563E+10 0.379707E+10 0.696760E+10 0.00 0.00 0.00 0.00 0.00
April 0.168349E+10 0.286784E+10 0.425903E+10 0.00 0.00 0.00 0.00 0.00
May 0.302527E+10 0.136546E+11 0.359038E+09 0.00 0.00 0.00 0.00 0.00
June 0.638145E+10 0.498065E+11 321294.74 0.00 0.00 0.00 0.00 0.00
July 0.604803E+10 0.505299E+11 539489.57 0.00 0.00 0.00 0.00 0.00
August 0.608194E+10 0.480937E+11 327748.65 0.00 0.00 0.00 0.00 0.00
September 0.442559E+10 0.319416E+11 0.238237E+09 0.00 0.00 0.00 0.00 0.00
October 0.217903E+10 0.768924E+10 0.512754E+10 0.00 0.00 0.00 0.00 0.00
November 0.157236E+10 0.308199E+10 0.818323E+10 0.00 0.00 0.00 0.00 0.00
December 0.144669E+10 0.125716E+10 0.167371E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376703E+11 0.215725E+12 0.644222E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138562E+10 0.109316E+10 321294.74 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.638145E+10 0.505299E+11 0.167371E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.164013E+10 0.103896E+10 0.171649E+11 0.00 0.00 0.00 0.00 0.00
February 0.161985E+10 0.144632E+10 0.182929E+11 0.00 0.00 0.00 0.00 0.00
March 0.207578E+10 0.371211E+10 0.110768E+11 0.00 0.00 0.00 0.00 0.00
April 0.177592E+10 0.279370E+10 0.691428E+10 0.00 0.00 0.00 0.00 0.00
May 0.279491E+10 0.145211E+11 0.618384E+09 0.00 0.00 0.00 0.00 0.00
June 0.607008E+10 0.543468E+11 1274904.22 0.00 0.00 0.00 0.00 0.00
July 0.565545E+10 0.544878E+11 489031.55 0.00 0.00 0.00 0.00 0.00
August 0.568679E+10 0.520154E+11 302750.59 0.00 0.00 0.00 0.00 0.00
September 0.391561E+10 0.329507E+11 0.353942E+09 0.00 0.00 0.00 0.00 0.00
October 0.206418E+10 0.658264E+10 0.866994E+10 0.00 0.00 0.00 0.00 0.00
November 0.161550E+10 0.263198E+10 0.130102E+11 0.00 0.00 0.00 0.00 0.00
December 0.183046E+10 0.107413E+10 0.268562E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.367447E+11 0.227602E+12 0.102960E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.161550E+10 0.103896E+10 302750.59 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.607008E+10 0.544878E+11 0.268562E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_BOT

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.170169E+10 0.122127E+11 0.00 0.00 0.731237E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.157770E+10 0.133156E+11 0.00 0.00 0.342999E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.226993E+10 0.848689E+10 0.00 0.00 0.936693E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.188490E+10 0.492387E+10 0.00 0.00 0.122172E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.335538E+10 0.714516E+09 0.00 0.00 0.337197E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.720343E+10 11081041.81 0.00 0.00 0.132068E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.686918E+10 2929081.77 0.00 0.00 0.132397E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.713286E+10 1443704.92 0.00 0.00 0.130042E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568652E+10 0.199193E+09 0.00 0.00 0.880886E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.305123E+10 0.483626E+10 0.00 0.00 0.286438E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.206081E+10 0.798462E+10 0.00 0.00 0.869563E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.161698E+10 0.161074E+11 0.00 0.00 0.378443E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.444106E+11 0.687965E+11 0.00 0.00 0.589765E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.157770E+10 1443704.92 0.00 0.00 0.342999E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.720343E+10 0.161074E+11 0.00 0.00 0.132397E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.145517E+10 0.107976E+11 0.00 0.00 0.458272E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138562E+10 0.117516E+11 0.00 0.00 0.276591E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.198563E+10 0.696760E+10 0.00 0.00 0.877538E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.168349E+10 0.425903E+10 0.00 0.00 0.691911E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.302527E+10 0.359038E+09 0.00 0.00 0.313400E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.638145E+10 321294.74 0.00 0.00 0.121206E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.604803E+10 539489.57 0.00 0.00 0.121250E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.608194E+10 327748.65 0.00 0.00 0.115112E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.442559E+10 0.238237E+09 0.00 0.00 0.741230E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.217903E+10 0.512754E+10 0.00 0.00 0.176240E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.157236E+10 0.818323E+10 0.00 0.00 0.732719E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144669E+10 0.167371E+11 0.00 0.00 0.311896E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.376703E+11 0.644222E+11 0.00 0.00 0.514145E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138562E+10 321294.74 0.00 0.00 0.276591E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.638145E+10 0.167371E+11 0.00 0.00 0.121250E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PACU_VAV_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.164013E+10 0.171649E+11 0.00 0.00 0.258572E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.161985E+10 0.182929E+11 0.00 0.00 0.364467E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.207578E+10 0.110768E+11 0.00 0.00 0.866755E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.177592E+10 0.691428E+10 0.00 0.00 0.678581E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.279491E+10 0.618384E+09 0.00 0.00 0.336416E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.607008E+10 1274904.22 0.00 0.00 0.133403E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.565545E+10 489031.55 0.00 0.00 0.132049E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.568679E+10 302750.59 0.00 0.00 0.125756E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.391561E+10 0.353942E+09 0.00 0.00 0.773362E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.206418E+10 0.866994E+10 0.00 0.00 0.153115E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.161550E+10 0.130102E+11 0.00 0.00 0.638515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.183046E+10 0.268562E+11 0.00 0.00 0.270994E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.367447E+11 0.102960E+12 0.00 0.00 0.548275E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.161550E+10 302750.59 0.00 0.00 0.258572E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.607008E+10 0.268562E+11 0.00 0.00 0.133403E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.328113E+10 0.00 0.00 26777747.48 0.00 0.00 0.132947E+11 0.00 0.39
February 0.333228E+10 0.00 0.00 23670537.59 0.00 0.00 0.126857E+11 0.00 0.41
March 0.179064E+10 0.00 0.00 33719569.75 0.00 0.00 0.174948E+11 0.00 0.65
April 0.103096E+10 0.00 0.00 30395147.47 0.00 0.00 0.143818E+11 0.00 0.57
May 0.380726E+09 2639056.51 0.00 43959915.24 360773.87 0.00 0.175408E+11 0.00 1.01
June 0.315742E+09 0.474233E+09 0.00 32812722.32 62259615.75 0.00 0.582480E+10 0.00 0.85
July 0.308033E+09 0.645649E+09 0.00 28949620.57 0.116861E+09 0.00 0.423909E+10 0.00 0.80
August 0.403816E+09 0.465302E+09 0.00 41189738.21 44759883.65 0.00 0.768088E+10 0.00 0.90
September 0.562481E+09 67221712.21 0.00 45553393.47 19673122.79 0.00 0.112941E+11 0.00 0.99
October 0.146192E+10 0.00 0.00 42929903.81 0.00 0.00 0.166833E+11 0.00 0.64
November 0.168046E+10 0.00 0.00 34683942.59 0.00 0.00 0.170492E+11 0.00 0.55
December 0.458934E+10 0.00 0.00 22394484.16 0.00 0.00 0.121639E+11 0.00 0.39
                   
Annual Sum or Average 0.191375E+11 0.165504E+10 0.00 0.407037E+09 0.243915E+09 0.00 0.150333E+12 0.00 0.68
Minimum of Months 0.308033E+09 0.00 0.00 22394484.16 0.00 0.00 0.423909E+10 0.00 0.39
Maximum of Months 0.458934E+10 0.645649E+09 0.00 45553393.47 0.116861E+09 0.00 0.175408E+11 0.00 1.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100451E+11 0.00 0.00 4160528.30 0.00 89365613.79 0.229615E+10 0.00 0.30
February 0.879143E+10 0.00 0.00 3740897.48 0.00 0.372137E+09 0.249660E+10 0.00 0.30
March 0.717960E+10 0.00 0.00 10793077.76 0.00 40496986.62 0.610590E+10 0.00 0.44
April 0.553649E+10 0.00 0.00 9698159.68 0.00 40198446.24 0.576123E+10 0.00 0.42
May 0.152995E+10 1296342.79 0.00 24083805.23 1417385.35 0.00 0.101172E+11 0.00 0.66
June 0.509369E+09 0.327665E+09 0.00 22780174.65 58280650.30 0.00 0.377439E+10 0.00 0.61
July 0.386505E+09 0.443544E+09 0.00 20099285.95 0.118157E+09 0.00 0.279786E+10 0.00 0.57
August 0.578497E+09 0.322175E+09 0.00 28167705.59 31421196.30 0.00 0.496707E+10 0.00 0.63
September 0.814007E+09 48384925.54 0.00 27464005.48 19142303.29 0.00 0.688667E+10 0.00 0.66
October 0.478257E+10 0.00 0.00 15895318.85 0.00 10545333.60 0.785759E+10 0.00 0.45
November 0.795110E+10 0.00 0.00 7093994.23 0.00 12432182.53 0.429578E+10 0.00 0.35
December 0.105866E+11 0.00 0.00 2260197.57 0.00 0.511952E+09 0.186827E+10 0.00 0.30
                   
Annual Sum or Average 0.586912E+11 0.114306E+10 0.00 0.176237E+09 0.228418E+09 0.107713E+10 0.592247E+11 0.00 0.47
Minimum of Months 0.386505E+09 0.00 0.00 2260197.57 0.00 0.00 0.186827E+10 0.00 0.30
Maximum of Months 0.105866E+11 0.443544E+09 0.00 28167705.59 0.118157E+09 0.511952E+09 0.101172E+11 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.897732E+10 0.00 0.00 1658029.16 0.00 0.124078E+10 0.132966E+10 0.00 0.29
February 0.787089E+10 0.00 0.00 1681722.41 0.00 0.155114E+10 0.120069E+10 0.00 0.28
March 0.735757E+10 0.00 0.00 7292870.56 0.00 0.563032E+09 0.454600E+10 0.00 0.42
April 0.564607E+10 0.00 0.00 7623227.81 0.00 0.420957E+09 0.485147E+10 0.00 0.41
May 0.225685E+10 198752.61 0.00 20506682.01 446135.60 16578538.88 0.886481E+10 0.00 0.65
June 0.623495E+09 0.257221E+09 0.00 23950530.10 53981713.65 0.00 0.345028E+10 0.00 0.64
July 0.455238E+09 0.346571E+09 0.00 20805382.78 0.120461E+09 0.00 0.241581E+10 0.00 0.59
August 0.635754E+09 0.265106E+09 0.00 27251603.19 31011778.61 0.00 0.430712E+10 0.00 0.62
September 0.129634E+10 34623404.29 0.00 23445469.20 14249601.35 0.00 0.536253E+10 0.00 0.62
October 0.553465E+10 0.00 0.00 8987623.02 0.00 0.666866E+09 0.497550E+10 0.00 0.43
November 0.816882E+10 0.00 0.00 3473771.09 0.00 0.663020E+09 0.218352E+10 0.00 0.32
December 0.862354E+10 0.00 0.00 642072.89 0.00 0.233114E+10 0.647102E+09 0.00 0.28
                   
Annual Sum or Average 0.574465E+11 0.903720E+09 0.00 0.147319E+09 0.220150E+09 0.745351E+10 0.441345E+11 0.00 0.46
Minimum of Months 0.455238E+09 0.00 0.00 642072.89 0.00 0.00 0.647102E+09 0.00 0.28
Maximum of Months 0.897732E+10 0.346571E+09 0.00 27251603.19 0.120461E+09 0.233114E+10 0.886481E+10 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.960812E+09 0.00 0.00 18816.84 0.00 0.178114E+10 28713628.32 0.00 0.32
February 0.915827E+09 0.00 0.00 18363.89 0.00 0.157498E+10 10134944.17 0.00 0.30
March 0.120286E+10 0.00 0.00 824782.91 0.00 0.926704E+09 0.453793E+09 0.00 0.40
April 0.114154E+10 0.00 0.00 1230900.49 0.00 0.506882E+09 0.688623E+09 0.00 0.43
May 0.660877E+09 73111.05 0.00 4931706.90 94023.45 25752696.46 0.183882E+10 0.00 0.76
June 0.128516E+09 98454973.20 0.00 7482954.24 9434755.70 0.00 0.929079E+09 0.00 0.88
July 0.105262E+09 0.131667E+09 0.00 6207368.20 20153008.58 0.00 0.610334E+09 0.00 0.78
August 0.179838E+09 90636129.37 0.00 7180008.76 6041680.43 0.00 0.956074E+09 0.00 0.74
September 0.394961E+09 13436632.41 0.00 5336441.79 2910943.71 13931244.15 0.981452E+09 0.00 0.66
October 0.113459E+10 0.00 0.00 1002481.29 0.00 0.747626E+09 0.452357E+09 0.00 0.41
November 0.993971E+09 0.00 0.00 253672.69 0.00 0.132639E+10 0.139094E+09 0.00 0.33
December 0.730893E+09 0.00 0.00 0.00 0.00 0.267706E+10 0.00 0.00 0.35
                   
Annual Sum or Average 0.854994E+10 0.334268E+09 0.00 34487498.02 38634411.87 0.958046E+10 0.708848E+10 0.00 0.53
Minimum of Months 0.105262E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.120286E+10 0.131667E+09 0.00 7482954.24 20153008.58 0.267706E+10 0.183882E+10 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.713065E+09 0.00 0.00 498450.46 0.00 0.879417E+09 0.268901E+09 0.00 0.35
February 0.644176E+09 0.00 0.00 942101.28 0.00 0.689883E+09 0.480850E+09 0.00 0.36
March 0.582193E+09 0.00 0.00 3159675.14 0.00 0.428803E+09 0.162726E+10 0.00 0.72
April 0.535469E+09 0.00 0.00 3355853.75 0.00 0.245726E+09 0.179362E+10 0.00 0.79
May 0.253751E+09 63580.72 0.00 6764362.52 59740.21 7623471.65 0.262291E+10 0.00 1.34
June 39574963.66 83957585.84 0.00 9704644.75 3906146.15 0.00 0.148713E+10 0.00 1.67
July 37105700.46 0.127412E+09 0.00 8247662.14 6104489.40 0.00 0.791861E+09 0.00 1.33
August 66824776.42 79118198.73 0.00 10325989.49 3363783.71 0.00 0.172201E+10 0.00 1.55
September 0.151192E+09 12320663.20 0.00 8066476.58 1815416.71 6296390.64 0.161863E+10 0.00 1.34
October 0.509391E+09 0.00 0.00 2883955.80 0.00 0.463701E+09 0.127455E+10 0.00 0.68
November 0.668515E+09 0.00 0.00 968376.93 0.00 0.652903E+09 0.446050E+09 0.00 0.40
December 0.610460E+09 0.00 0.00 113772.18 0.00 0.157263E+10 82416873.52 0.00 0.35
                   
Annual Sum or Average 0.481172E+10 0.302872E+09 0.00 55031321.03 15249576.17 0.494699E+10 0.142162E+11 0.00 0.91
Minimum of Months 37105700.46 0.00 0.00 113772.18 0.00 0.00 82416873.52 0.00 0.35
Maximum of Months 0.713065E+09 0.127412E+09 0.00 10325989.49 6104489.40 0.157263E+10 0.262291E+10 0.00 1.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.811790E+09 0.00 0.00 8738992.60 0.00 0.835484E+09 0.433414E+10 0.00 0.86
February 0.726403E+09 0.00 0.00 8918709.70 0.00 0.807686E+09 0.403142E+10 0.00 0.76
March 0.790067E+09 0.00 0.00 9132610.08 0.00 0.660067E+09 0.438194E+10 0.00 1.06
April 0.911957E+09 0.00 0.00 5047229.22 0.00 0.382438E+09 0.277920E+10 0.00 0.82
May 0.543831E+09 87507.37 0.00 7597478.24 93956.85 26994312.45 0.289897E+10 0.00 1.04
June 0.161651E+09 0.113155E+09 0.00 8612477.60 8373125.71 0.00 0.988732E+09 0.00 0.97
July 0.110768E+09 0.188144E+09 0.00 7417802.85 12126728.10 0.00 0.676976E+09 0.00 0.90
August 0.157126E+09 0.133411E+09 0.00 11903897.92 5478572.94 0.00 0.149057E+10 0.00 1.06
September 0.274924E+09 26390653.15 0.00 14124014.22 2535561.02 11400868.51 0.240044E+10 0.00 1.34
October 0.604170E+09 0.00 0.00 13100282.56 0.00 0.669773E+09 0.477133E+10 0.00 1.28
November 0.754381E+09 0.00 0.00 9770886.58 0.00 0.694151E+09 0.416459E+10 0.00 0.92
December 0.873428E+09 0.00 0.00 6460709.11 0.00 0.133554E+10 0.292335E+10 0.00 0.73
                   
Annual Sum or Average 0.672050E+10 0.461188E+09 0.00 0.110825E+09 28607944.63 0.542353E+10 0.358417E+11 0.00 0.98
Minimum of Months 0.110768E+09 0.00 0.00 5047229.22 0.00 0.00 0.676976E+09 0.00 0.73
Maximum of Months 0.911957E+09 0.188144E+09 0.00 14124014.22 12126728.10 0.133554E+10 0.477133E+10 0.00 1.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.595078E+09 0.00 0.00 878500.72 0.00 0.957995E+09 0.568149E+09 0.00 0.43
February 0.555780E+09 0.00 0.00 1243880.35 0.00 0.833373E+09 0.680269E+09 0.00 0.41
March 0.649279E+09 0.00 0.00 3165418.05 0.00 0.515104E+09 0.147100E+10 0.00 0.78
April 0.615457E+09 0.00 0.00 2859257.64 0.00 0.288873E+09 0.151152E+10 0.00 0.78
May 0.319764E+09 89508.29 0.00 5947184.11 59789.43 17556758.65 0.214426E+10 0.00 1.22
June 91995951.25 0.116970E+09 0.00 7428590.05 2888994.36 0.00 0.720300E+09 0.00 1.20
July 67237322.33 0.134790E+09 0.00 5365372.11 7829594.08 0.00 0.494674E+09 0.00 1.04
August 98269688.15 0.100490E+09 0.00 7641282.67 2200364.71 0.00 0.815981E+09 0.00 1.04
September 0.204508E+09 16483238.72 0.00 6740918.50 999099.77 9653391.81 0.113087E+10 0.00 1.08
October 0.564200E+09 0.00 0.00 3596882.61 0.00 0.469127E+09 0.139897E+10 0.00 0.80
November 0.591198E+09 0.00 0.00 1287425.34 0.00 0.717013E+09 0.655281E+09 0.00 0.47
December 0.506381E+09 0.00 0.00 451362.71 0.00 0.190369E+10 0.274784E+09 0.00 0.44
                   
Annual Sum or Average 0.485915E+10 0.368823E+09 0.00 46606074.87 13977842.36 0.571238E+10 0.118661E+11 0.00 0.81
Minimum of Months 67237322.33 0.00 0.00 451362.71 0.00 0.00 0.274784E+09 0.00 0.41
Maximum of Months 0.649279E+09 0.134790E+09 0.00 7641282.67 7829594.08 0.190369E+10 0.214426E+10 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100952E+10 0.00 0.00 0.00 0.00 0.156757E+10 0.00 0.00 0.27
February 0.854766E+09 0.00 0.00 0.00 0.00 0.159113E+10 0.00 0.00 0.28
March 0.129257E+10 0.00 0.00 185176.07 0.00 0.935293E+09 98125676.28 0.00 0.34
April 0.136428E+10 0.00 0.00 250313.19 0.00 0.331062E+09 0.127087E+09 0.00 0.30
May 0.775789E+09 334531.45 0.00 2846649.00 83513.90 10262262.66 0.100855E+10 0.00 0.51
June 0.139672E+09 0.103669E+09 0.00 4656499.81 13116430.90 0.00 0.688499E+09 0.00 0.63
July 0.131740E+09 0.134182E+09 0.00 4024317.46 25293546.92 0.00 0.489093E+09 0.00 0.60
August 0.177122E+09 94843984.62 0.00 5594959.86 9454191.97 0.00 0.865700E+09 0.00 0.63
September 0.373311E+09 13927203.35 0.00 5240692.51 4168989.29 0.00 0.105385E+10 0.00 0.65
October 0.116514E+10 0.00 0.00 1108197.68 0.00 0.364779E+09 0.405224E+09 0.00 0.32
November 0.145320E+10 0.00 0.00 199835.79 0.00 0.676107E+09 0.106882E+09 0.00 0.29
December 0.101233E+10 0.00 0.00 0.00 0.00 0.203271E+10 0.00 0.00 0.30
                   
Annual Sum or Average 0.974944E+10 0.346957E+09 0.00 24106641.36 52116672.99 0.750892E+10 0.484301E+10 0.00 0.43
Minimum of Months 0.131740E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.145320E+10 0.134182E+09 0.00 5594959.86 25293546.92 0.203271E+10 0.105385E+10 0.00 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.860189E+09 0.00 0.00 407832.12 0.00 0.684540E+09 0.133581E+09 0.00 0.28
February 0.685755E+09 0.00 0.00 835085.88 0.00 0.663824E+09 0.375678E+09 0.00 0.32
March 0.674467E+09 0.00 0.00 2409297.06 0.00 0.335871E+09 0.114456E+10 0.00 0.57
April 0.648446E+09 0.00 0.00 2511755.76 0.00 0.120288E+09 0.100238E+10 0.00 0.52
May 0.253947E+09 380794.31 0.00 5231405.91 48046.45 277199.87 0.193701E+10 0.00 1.01
June 37902660.65 97675884.96 0.00 7112622.94 6310234.62 0.00 0.123258E+10 0.00 1.34
July 38536378.87 0.137854E+09 0.00 6070897.30 8197318.95 0.00 0.736412E+09 0.00 1.10
August 69227851.46 99640596.58 0.00 8766319.98 4966978.51 0.00 0.158832E+10 0.00 1.40
September 0.147473E+09 14551209.19 0.00 8123591.37 2423892.70 0.00 0.177147E+10 0.00 1.34
October 0.513069E+09 0.00 0.00 3684112.20 0.00 0.206882E+09 0.115839E+10 0.00 0.56
November 0.883496E+09 0.00 0.00 1329706.24 0.00 0.251462E+09 0.556564E+09 0.00 0.39
December 0.760355E+09 0.00 0.00 191319.02 0.00 0.114840E+10 0.115365E+09 0.00 0.31
                   
Annual Sum or Average 0.557286E+10 0.350102E+09 0.00 46673945.80 21946471.23 0.341154E+10 0.117523E+11 0.00 0.76
Minimum of Months 37902660.65 0.00 0.00 191319.02 0.00 0.00 0.115365E+09 0.00 0.28
Maximum of Months 0.883496E+09 0.137854E+09 0.00 8766319.98 8197318.95 0.114840E+10 0.193701E+10 0.00 1.40



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.992800E+09 0.00 0.00 4624148.82 0.00 0.174581E+10 0.186302E+10 0.00 0.54
February 0.867511E+09 0.00 0.00 3857418.38 0.00 0.189603E+10 0.178108E+10 0.00 0.58
March 0.906038E+09 0.00 0.00 4270975.77 0.00 0.144415E+10 0.187173E+10 0.00 0.77
April 0.102844E+10 0.00 0.00 1577420.20 0.00 0.977016E+09 0.668745E+09 0.00 0.47
May 0.823712E+09 603153.84 0.00 3251872.00 75995.06 0.267918E+09 0.931732E+09 0.00 0.61
June 0.230699E+09 0.141575E+09 0.00 5012921.26 12853686.23 7801776.44 0.536850E+09 0.00 0.68
July 0.188583E+09 0.196126E+09 0.00 4360169.87 19154785.83 2617828.77 0.408081E+09 0.00 0.67
August 0.255591E+09 0.171260E+09 0.00 9303167.28 6558985.41 722622.99 0.107520E+10 0.00 0.90
September 0.344986E+09 30747782.52 0.00 12287779.60 3220307.44 52470197.52 0.203071E+10 0.00 1.25
October 0.515207E+09 0.00 0.00 12395201.56 0.00 0.107732E+10 0.308558E+10 0.00 0.94
November 0.847318E+09 0.00 0.00 7369628.39 0.00 0.127051E+10 0.284782E+10 0.00 0.80
December 0.991287E+09 0.00 0.00 4262927.30 0.00 0.266286E+10 0.170383E+10 0.00 0.64
                   
Annual Sum or Average 0.799217E+10 0.540311E+09 0.00 72573630.44 41863759.97 0.114052E+11 0.188044E+11 0.00 0.74
Minimum of Months 0.188583E+09 0.00 0.00 1577420.20 0.00 722622.99 0.408081E+09 0.00 0.47
Maximum of Months 0.102844E+10 0.196126E+09 0.00 12395201.56 19154785.83 0.266286E+10 0.308558E+10 0.00 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.854892E+09 0.00 0.00 520316.14 0.00 0.634210E+09 0.222199E+09 0.00 0.30
February 0.694940E+09 0.00 0.00 679893.03 0.00 0.704742E+09 0.391631E+09 0.00 0.34
March 0.745925E+09 0.00 0.00 1888452.22 0.00 0.416949E+09 0.829880E+09 0.00 0.57
April 0.720149E+09 0.00 0.00 1672185.79 0.00 0.157394E+09 0.664960E+09 0.00 0.47
May 0.323822E+09 550449.90 0.00 4065394.74 48135.42 5178701.29 0.137977E+10 0.00 0.85
June 73398261.79 0.131328E+09 0.00 4935869.37 3304535.04 0.00 0.625752E+09 0.00 0.94
July 73292959.60 0.143023E+09 0.00 3518090.11 10273985.04 0.00 0.455115E+09 0.00 0.84
August 83722941.38 0.114302E+09 0.00 6099895.17 3934728.33 0.00 0.829939E+09 0.00 0.96
September 0.174057E+09 17490741.00 0.00 6454544.95 1252927.24 0.00 0.123841E+10 0.00 1.08
October 0.505709E+09 0.00 0.00 3842861.86 0.00 0.203641E+09 0.124135E+10 0.00 0.63
November 0.888225E+09 0.00 0.00 1234745.29 0.00 0.252813E+09 0.589894E+09 0.00 0.41
December 0.811797E+09 0.00 0.00 360259.85 0.00 0.115972E+10 0.195040E+09 0.00 0.35
                   
Annual Sum or Average 0.594993E+10 0.406693E+09 0.00 35272508.52 18814311.07 0.353464E+10 0.866394E+10 0.00 0.65
Minimum of Months 73292959.60 0.00 0.00 360259.85 0.00 0.00 0.195040E+09 0.00 0.30
Maximum of Months 0.888225E+09 0.143023E+09 0.00 6454544.95 10273985.04 0.115972E+10 0.137977E+10 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.136870E+10 0.00 0.00 41367.23 0.00 0.125014E+10 31041050.30 0.00 0.29
February 0.125885E+10 0.00 0.00 29834.80 0.00 0.119000E+10 36309245.45 0.00 0.29
March 0.152287E+10 0.00 0.00 968242.99 0.00 0.582792E+09 0.503868E+09 0.00 0.40
April 0.138080E+10 0.00 0.00 1317476.22 0.00 0.247488E+09 0.670181E+09 0.00 0.42
May 0.580833E+09 593561.41 0.00 5357020.68 299214.73 5047333.54 0.195830E+10 0.00 0.75
June 98163140.11 0.126124E+09 0.00 6611322.92 11791947.23 0.00 0.973555E+09 0.00 0.82
July 91982023.75 0.171433E+09 0.00 5499917.91 22938802.25 0.00 0.671371E+09 0.00 0.76
August 0.153512E+09 0.116037E+09 0.00 7068746.68 6565639.58 0.00 0.105736E+10 0.00 0.74
September 0.352335E+09 19617569.90 0.00 5587812.88 3944591.73 246262.73 0.113254E+10 0.00 0.68
October 0.126145E+10 0.00 0.00 1377842.68 0.00 0.465716E+09 0.601766E+09 0.00 0.40
November 0.144511E+10 0.00 0.00 392928.13 0.00 0.827656E+09 0.190579E+09 0.00 0.32
December 0.114256E+10 0.00 0.00 11146.46 0.00 0.203880E+10 12292328.57 0.00 0.32
                   
Annual Sum or Average 0.106572E+11 0.433805E+09 0.00 34263659.56 45540195.52 0.660789E+10 0.783916E+10 0.00 0.52
Minimum of Months 91982023.75 0.00 0.00 11146.46 0.00 0.00 12292328.57 0.00 0.29
Maximum of Months 0.152287E+10 0.171433E+09 0.00 7068746.68 22938802.25 0.203880E+10 0.195830E+10 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.733502E+09 0.00 0.00 782608.30 0.00 0.606156E+09 0.338191E+09 0.00 0.29
February 0.581542E+09 0.00 0.00 1495358.70 0.00 0.538982E+09 0.714866E+09 0.00 0.36
March 0.642781E+09 0.00 0.00 3719726.72 0.00 0.235921E+09 0.173721E+10 0.00 0.69
April 0.528588E+09 0.00 0.00 3666004.36 0.00 0.110887E+09 0.174324E+10 0.00 0.74
May 0.209009E+09 471324.61 0.00 6890355.03 189210.01 240681.12 0.260030E+10 0.00 1.27
June 30255511.68 98631404.95 0.00 8574793.25 5886144.90 0.00 0.148244E+10 0.00 1.52
July 29662327.02 0.150660E+09 0.00 7341730.69 7503601.75 0.00 0.846986E+09 0.00 1.25
August 64274833.05 99481094.58 0.00 9682663.10 2811098.27 0.00 0.175191E+10 0.00 1.48
September 0.145498E+09 17268322.79 0.00 7829760.88 2413178.64 155725.53 0.171600E+10 0.00 1.30
October 0.524509E+09 0.00 0.00 3569083.69 0.00 0.280097E+09 0.131397E+10 0.00 0.62
November 0.729604E+09 0.00 0.00 1370094.06 0.00 0.384430E+09 0.552023E+09 0.00 0.38
December 0.638922E+09 0.00 0.00 320144.79 0.00 0.128177E+10 0.167219E+09 0.00 0.31
                   
Annual Sum or Average 0.485815E+10 0.366513E+09 0.00 55242323.58 18803233.57 0.343864E+10 0.149644E+11 0.00 0.85
Minimum of Months 29662327.02 0.00 0.00 320144.79 0.00 0.00 0.167219E+09 0.00 0.29
Maximum of Months 0.733502E+09 0.150660E+09 0.00 9682663.10 7503601.75 0.128177E+10 0.260030E+10 0.00 1.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111510E+10 0.00 0.00 10669836.88 0.00 0.484155E+09 0.441725E+10 0.00 0.83
February 0.857692E+09 0.00 0.00 10248605.53 0.00 0.610213E+09 0.456731E+10 0.00 0.84
March 0.105515E+10 0.00 0.00 9885063.62 0.00 0.388764E+09 0.429448E+10 0.00 1.07
April 0.104811E+10 0.00 0.00 5345590.64 0.00 0.200232E+09 0.257275E+10 0.00 0.81
May 0.508264E+09 849613.51 0.00 7900695.26 297937.65 6672367.95 0.285906E+10 0.00 1.02
June 0.142223E+09 0.144253E+09 0.00 7272329.44 11810727.29 0.00 0.936881E+09 0.00 0.89
July 0.107811E+09 0.236796E+09 0.00 6176343.39 14358023.78 0.00 0.682090E+09 0.00 0.84
August 0.139278E+09 0.187642E+09 0.00 11093764.22 2996787.21 0.00 0.150217E+10 0.00 1.04
September 0.268752E+09 40356794.54 0.00 12972543.75 3344513.40 245211.66 0.235723E+10 0.00 1.31
October 0.704600E+09 0.00 0.00 14948255.90 0.00 0.434484E+09 0.458767E+10 0.00 1.22
November 0.101699E+10 0.00 0.00 12160272.87 0.00 0.370155E+09 0.451241E+10 0.00 0.96
December 0.110335E+10 0.00 0.00 8151639.96 0.00 0.924323E+09 0.336308E+10 0.00 0.76
                   
Annual Sum or Average 0.806732E+10 0.609897E+09 0.00 0.116825E+09 32807989.33 0.341924E+10 0.366524E+11 0.00 0.97
Minimum of Months 0.107811E+09 0.00 0.00 5345590.64 0.00 0.00 0.682090E+09 0.00 0.76
Maximum of Months 0.111510E+10 0.236796E+09 0.00 14948255.90 14358023.78 0.924323E+09 0.458767E+10 0.00 1.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.864015E+09 0.00 0.00 1064036.64 0.00 0.597151E+09 0.555102E+09 0.00 0.39
February 0.740985E+09 0.00 0.00 1427729.88 0.00 0.596036E+09 0.771211E+09 0.00 0.43
March 0.799739E+09 0.00 0.00 3298193.92 0.00 0.325890E+09 0.142794E+10 0.00 0.77
April 0.700687E+09 0.00 0.00 2939131.54 0.00 0.146804E+09 0.141000E+10 0.00 0.76
May 0.291798E+09 794941.84 0.00 6103026.50 187605.61 5059906.26 0.209343E+10 0.00 1.19
June 74176186.65 0.156352E+09 0.00 6063230.27 2651815.05 0.00 0.689914E+09 0.00 1.09
July 61994877.28 0.183581E+09 0.00 4283365.75 8318789.91 0.00 0.498038E+09 0.00 0.97
August 85152886.93 0.134892E+09 0.00 7020475.46 1937022.69 0.00 0.845881E+09 0.00 1.03
September 0.192024E+09 24688284.59 0.00 6204718.84 1051768.07 188900.00 0.115263E+10 0.00 1.07
October 0.610292E+09 0.00 0.00 4087872.58 0.00 0.293924E+09 0.147191E+10 0.00 0.78
November 0.839033E+09 0.00 0.00 1553904.77 0.00 0.423449E+09 0.701715E+09 0.00 0.47
December 0.774051E+09 0.00 0.00 567676.69 0.00 0.143006E+10 0.308751E+09 0.00 0.41
                   
Annual Sum or Average 0.603395E+10 0.500308E+09 0.00 44613362.83 14147001.32 0.381856E+10 0.119265E+11 0.00 0.78
Minimum of Months 61994877.28 0.00 0.00 567676.69 0.00 0.00 0.308751E+09 0.00 0.39
Maximum of Months 0.864015E+09 0.183581E+09 0.00 7020475.46 8318789.91 0.143006E+10 0.209343E+10 0.00 1.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2024-07-03 12:20:08

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.246514E+12 0.789836E+10 0.00 0.174331E+12 0.259844E+11
February 0.303773E+12 0.967870E+10 0.00 0.162341E+12 0.236812E+11
March 0.367873E+12 0.961058E+10 0.00 0.188388E+12 0.274931E+11
April 0.380878E+12 0.904621E+10 0.00 0.187028E+12 0.212089E+11
May 0.443809E+12 0.498864E+10 0.00 0.208505E+12 0.536388E+11
June 0.461382E+12 0.124693E+10 0.00 0.124667E+12 0.197249E+12
July 0.431142E+12 0.869063E+09 0.00 0.966784E+11 0.198981E+12
August 0.429208E+12 0.122420E+10 0.00 0.100180E+12 0.191841E+12
September 0.326666E+12 0.283818E+10 0.00 0.159596E+12 0.127418E+12
October 0.290750E+12 0.781533E+10 0.00 0.208624E+12 0.416090E+11
November 0.259086E+12 0.813153E+10 0.00 0.190298E+12 0.263948E+11
December 0.206959E+12 0.118508E+11 0.00 0.166993E+12 0.295095E+11
           
Annual Sum or Average 0.414804E+13 0.751985E+11 0.00 0.196763E+13 0.965009E+12
Minimum of Months 0.206959E+12 0.869063E+09 0.00 0.966784E+11 0.212089E+11
Maximum of Months 0.461382E+12 0.118508E+11 0.00 0.208624E+12 0.198981E+12